Description

The MIB module to describe Uninterruptible Power Supplies.

Contact

Jeffrey D. Case Postal: SNMP Research, Incorporated 3001 Kimberlin Heights Road Knoxville, TN 37920 US Tel: +1 615 573 1434 Fax: +1 615 573 9197 E-mail: case@snmp.com

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-SMICounter32, Gauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso, mib-2
SNMPv2-TCAutonomousType, DisplayString, TEXTUAL-CONVENTION, TestAndIncr, TimeInterval, TimeStamp

Imported by

3 module(s) in this corpus import this one.

Load order

Every file a consumer needs in order to load this module, dependencies first.

SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC
UPS-MIB

Textual conventions

NameOIDSyntaxAccessStatus
NonNegativeInteger
TEXTUAL-CONVENTION
This data type is a non-negative value.
current
PositiveInteger
TEXTUAL-CONVENTION
This data type is a non-zero and non-negative value.
current

Objects

NameOIDSyntaxAccessStatus
upsObjects
OBJECT-IDENTITY
1.3.6.1.2.1.33.1
upsIdent
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.1
upsIdentManufacturer
OBJECT-TYPE
The name of the UPS manufacturer.
1.3.6.1.2.1.33.1.1.1DisplayString (SIZE(0..31))read-onlycurrent
upsIdentModel
OBJECT-TYPE
The UPS Model designation.
1.3.6.1.2.1.33.1.1.2DisplayString (SIZE(0..63))read-onlycurrent
upsIdentUPSSoftwareVersion
OBJECT-TYPE
The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.
1.3.6.1.2.1.33.1.1.3DisplayString (SIZE(0..63))read-onlycurrent
upsIdentAgentSoftwareVersion
OBJECT-TYPE
The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.2.1.33.1.1.4DisplayString (SIZE(0..63))read-onlycurrent
upsIdentName
OBJECT-TYPE
A string identifying the UPS. This object should be set by the administrator.
1.3.6.1.2.1.33.1.1.5DisplayString (SIZE(0..63))read-writecurrent
upsIdentAttachedDevices
OBJECT-TYPE
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
1.3.6.1.2.1.33.1.1.6DisplayString (SIZE(0..63))read-writecurrent
upsBattery
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.2
upsBatteryStatus
OBJECT-TYPE
The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).
1.3.6.1.2.1.33.1.2.1INTEGER {unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4)}read-onlycurrent
upsSecondsOnBattery
OBJECT-TYPE
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
1.3.6.1.2.1.33.1.2.2NonNegativeIntegerread-onlycurrent
upsEstimatedMinutesRemaining
OBJECT-TYPE
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
1.3.6.1.2.1.33.1.2.3PositiveIntegerread-onlycurrent
upsEstimatedChargeRemaining
OBJECT-TYPE
An estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.2.1.33.1.2.4INTEGER (0..100)read-onlycurrent
upsBatteryVoltage
OBJECT-TYPE
The magnitude of the present battery voltage.
1.3.6.1.2.1.33.1.2.5NonNegativeIntegerread-onlycurrent
upsBatteryCurrent
OBJECT-TYPE
The present battery current.
1.3.6.1.2.1.33.1.2.6Integer32read-onlycurrent
upsBatteryTemperature
OBJECT-TYPE
The ambient temperature at or near the UPS Battery casing.
1.3.6.1.2.1.33.1.2.7Integer32read-onlycurrent
upsInput
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.3
upsInputLineBads
OBJECT-TYPE
A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.
1.3.6.1.2.1.33.1.3.1Counter32read-onlycurrent
upsInputNumLines
OBJECT-TYPE
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.2.1.33.1.3.2NonNegativeIntegerread-onlycurrent
upsInputTable
OBJECT-TYPE
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
1.3.6.1.2.1.33.1.3.3not-accessiblecurrent
upsInputEntry
OBJECT-TYPE
An entry containing information applicable to a particular input line.
1.3.6.1.2.1.33.1.3.3.1not-accessiblecurrent
upsInputLineIndex
OBJECT-TYPE
The input line identifier.
1.3.6.1.2.1.33.1.3.3.1.1PositiveIntegernot-accessiblecurrent
upsInputFrequency
OBJECT-TYPE
The present input frequency.
1.3.6.1.2.1.33.1.3.3.1.2NonNegativeIntegerread-onlycurrent
upsInputVoltage
OBJECT-TYPE
The magnitude of the present input voltage.
1.3.6.1.2.1.33.1.3.3.1.3NonNegativeIntegerread-onlycurrent
upsInputCurrent
OBJECT-TYPE
The magnitude of the present input current.
1.3.6.1.2.1.33.1.3.3.1.4NonNegativeIntegerread-onlycurrent
upsInputTruePower
OBJECT-TYPE
The magnitude of the present input true power.
1.3.6.1.2.1.33.1.3.3.1.5NonNegativeIntegerread-onlycurrent
upsOutput
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.4
upsOutputSource
OBJECT-TYPE
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
1.3.6.1.2.1.33.1.4.1INTEGER {other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7)}read-onlycurrent
upsOutputFrequency
OBJECT-TYPE
The present output frequency.
1.3.6.1.2.1.33.1.4.2NonNegativeIntegerread-onlycurrent
upsOutputNumLines
OBJECT-TYPE
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.2.1.33.1.4.3NonNegativeIntegerread-onlycurrent
upsOutputTable
OBJECT-TYPE
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.2.1.33.1.4.4not-accessiblecurrent
upsOutputEntry
OBJECT-TYPE
An entry containing information applicable to a particular output line.
1.3.6.1.2.1.33.1.4.4.1not-accessiblecurrent
upsOutputLineIndex
OBJECT-TYPE
The output line identifier.
1.3.6.1.2.1.33.1.4.4.1.1PositiveIntegernot-accessiblecurrent
upsOutputVoltage
OBJECT-TYPE
The present output voltage.
1.3.6.1.2.1.33.1.4.4.1.2NonNegativeIntegerread-onlycurrent
upsOutputCurrent
OBJECT-TYPE
The present output current.
1.3.6.1.2.1.33.1.4.4.1.3NonNegativeIntegerread-onlycurrent
upsOutputPower
OBJECT-TYPE
The present output true power.
1.3.6.1.2.1.33.1.4.4.1.4NonNegativeIntegerread-onlycurrent
upsOutputPercentLoad
OBJECT-TYPE
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
1.3.6.1.2.1.33.1.4.4.1.5INTEGER (0..200)read-onlycurrent
upsBypass
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.5
upsBypassFrequency
OBJECT-TYPE
The present bypass frequency.
1.3.6.1.2.1.33.1.5.1NonNegativeIntegerread-onlycurrent
upsBypassNumLines
OBJECT-TYPE
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
1.3.6.1.2.1.33.1.5.2NonNegativeIntegerread-onlycurrent
upsBypassTable
OBJECT-TYPE
A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
1.3.6.1.2.1.33.1.5.3not-accessiblecurrent
upsBypassEntry
OBJECT-TYPE
An entry containing information applicable to a particular bypass input.
1.3.6.1.2.1.33.1.5.3.1not-accessiblecurrent
upsBypassLineIndex
OBJECT-TYPE
The bypass line identifier.
1.3.6.1.2.1.33.1.5.3.1.1PositiveIntegernot-accessiblecurrent
upsBypassVoltage
OBJECT-TYPE
The present bypass voltage.
1.3.6.1.2.1.33.1.5.3.1.2NonNegativeIntegerread-onlycurrent
upsBypassCurrent
OBJECT-TYPE
The present bypass current.
1.3.6.1.2.1.33.1.5.3.1.3NonNegativeIntegerread-onlycurrent
upsBypassPower
OBJECT-TYPE
The present true power conveyed by the bypass.
1.3.6.1.2.1.33.1.5.3.1.4NonNegativeIntegerread-onlycurrent
upsAlarm
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.6
upsAlarmsPresent
OBJECT-TYPE
The present number of active alarm conditions.
1.3.6.1.2.1.33.1.6.1Gauge32read-onlycurrent
upsAlarmTable
OBJECT-TYPE
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.
1.3.6.1.2.1.33.1.6.2not-accessiblecurrent
upsAlarmEntry
OBJECT-TYPE
An entry containing information applicable to a particular alarm.
1.3.6.1.2.1.33.1.6.2.1not-accessiblecurrent
upsAlarmId
OBJECT-TYPE
A unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.2.1.33.1.6.2.1.1PositiveIntegernot-accessiblecurrent
upsAlarmDescr
OBJECT-TYPE
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
1.3.6.1.2.1.33.1.6.2.1.2AutonomousTyperead-onlycurrent
upsAlarmTime
OBJECT-TYPE
The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.
1.3.6.1.2.1.33.1.6.2.1.3TimeStampread-onlycurrent
upsWellKnownAlarms
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.6.3
upsAlarmBatteryBad
OBJECT-IDENTITY
One or more batteries have been determined to require replacement.
1.3.6.1.2.1.33.1.6.3.1current
upsAlarmOnBattery
OBJECT-IDENTITY
The UPS is drawing power from the batteries.
1.3.6.1.2.1.33.1.6.3.2current
upsAlarmLowBattery
OBJECT-IDENTITY
The remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.2.1.33.1.6.3.3current
upsAlarmDepletedBattery
OBJECT-IDENTITY
The UPS will be unable to sustain the present load when and if the utility power is lost.
1.3.6.1.2.1.33.1.6.3.4current
upsAlarmTempBad
OBJECT-IDENTITY
A temperature is out of tolerance.
1.3.6.1.2.1.33.1.6.3.5current
upsAlarmInputBad
OBJECT-IDENTITY
An input condition is out of tolerance.
1.3.6.1.2.1.33.1.6.3.6current
upsAlarmOutputBad
OBJECT-IDENTITY
An output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.2.1.33.1.6.3.7current
upsAlarmOutputOverload
OBJECT-IDENTITY
The output load exceeds the UPS output capacity.
1.3.6.1.2.1.33.1.6.3.8current
upsAlarmOnBypass
OBJECT-IDENTITY
The Bypass is presently engaged on the UPS.
1.3.6.1.2.1.33.1.6.3.9current
upsAlarmBypassBad
OBJECT-IDENTITY
The Bypass is out of tolerance.
1.3.6.1.2.1.33.1.6.3.10current
upsAlarmOutputOffAsRequested
OBJECT-IDENTITY
The UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.2.1.33.1.6.3.11current
upsAlarmUpsOffAsRequested
OBJECT-IDENTITY
The entire UPS has shutdown as commanded.
1.3.6.1.2.1.33.1.6.3.12current
upsAlarmChargerFailed
OBJECT-IDENTITY
An uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.2.1.33.1.6.3.13current
upsAlarmUpsOutputOff
OBJECT-IDENTITY
The output of the UPS is in the off state.
1.3.6.1.2.1.33.1.6.3.14current
upsAlarmUpsSystemOff
OBJECT-IDENTITY
The UPS system is in the off state.
1.3.6.1.2.1.33.1.6.3.15current
upsAlarmFanFailure
OBJECT-IDENTITY
The failure of one or more fans in the UPS has been detected.
1.3.6.1.2.1.33.1.6.3.16current
upsAlarmFuseFailure
OBJECT-IDENTITY
The failure of one or more fuses has been detected.
1.3.6.1.2.1.33.1.6.3.17current
upsAlarmGeneralFault
OBJECT-IDENTITY
A general fault in the UPS has been detected.
1.3.6.1.2.1.33.1.6.3.18current
upsAlarmDiagnosticTestFailed
OBJECT-IDENTITY
The result of the last diagnostic test indicates a failure.
1.3.6.1.2.1.33.1.6.3.19current
upsAlarmCommunicationsLost
OBJECT-IDENTITY
A problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.2.1.33.1.6.3.20current
upsAlarmAwaitingPower
OBJECT-IDENTITY
The UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.2.1.33.1.6.3.21current
upsAlarmShutdownPending
OBJECT-IDENTITY
A upsShutdownAfterDelay countdown is underway.
1.3.6.1.2.1.33.1.6.3.22current
upsAlarmShutdownImminent
OBJECT-IDENTITY
The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.2.1.33.1.6.3.23current
upsAlarmTestInProgress
OBJECT-IDENTITY
A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
1.3.6.1.2.1.33.1.6.3.24current
upsTest
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.7
upsTestId
OBJECT-TYPE
The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.
1.3.6.1.2.1.33.1.7.1OBJECT IDENTIFIERread-writecurrent
upsTestSpinLock
OBJECT-TYPE
A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: try_again: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lock_value = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lock_value, upsTestId = requested_test) if (error_index == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto try_again } if (error_index == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lock_value + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.
1.3.6.1.2.1.33.1.7.2TestAndIncrread-writecurrent
upsTestResultsSummary
OBJECT-TYPE
The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
1.3.6.1.2.1.33.1.7.3INTEGER {donePass(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6)}read-onlycurrent
upsTestResultsDetail
OBJECT-TYPE
Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
1.3.6.1.2.1.33.1.7.4DisplayString (SIZE(0..255))read-onlycurrent
upsTestStartTime
OBJECT-TYPE
The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.
1.3.6.1.2.1.33.1.7.5TimeStampread-onlycurrent
upsTestElapsedTime
OBJECT-TYPE
The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.
1.3.6.1.2.1.33.1.7.6TimeIntervalread-onlycurrent
upsWellKnownTests
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.7.7
upsTestNoTestsInitiated
OBJECT-IDENTITY
No tests have been initiated and no test is in progress.
1.3.6.1.2.1.33.1.7.7.1current
upsTestAbortTestInProgress
OBJECT-IDENTITY
The test in progress is to be aborted / the test in progress was aborted.
1.3.6.1.2.1.33.1.7.7.2current
upsTestGeneralSystemsTest
OBJECT-IDENTITY
The manufacturer's standard test of UPS device systems.
1.3.6.1.2.1.33.1.7.7.3current
upsTestQuickBatteryTest
OBJECT-IDENTITY
A test that is sufficient to determine if the battery needs replacement.
1.3.6.1.2.1.33.1.7.7.4current
upsTestDeepBatteryCalibration
OBJECT-IDENTITY
The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.
1.3.6.1.2.1.33.1.7.7.5current
upsControl
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.8
upsShutdownType
OBJECT-TYPE
This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.
1.3.6.1.2.1.33.1.8.1INTEGER {output(1), system(2)}read-writecurrent
upsShutdownAfterDelay
OBJECT-TYPE
Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.
1.3.6.1.2.1.33.1.8.2INTEGER (-1..2147483647)read-writecurrent
upsStartupAfterDelay
OBJECT-TYPE
Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.
1.3.6.1.2.1.33.1.8.3INTEGER (-1..2147483647)read-writecurrent
upsRebootWithDuration
OBJECT-TYPE
Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.
1.3.6.1.2.1.33.1.8.4INTEGER (-1..300)read-writecurrent
upsAutoRestart
OBJECT-TYPE
Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.
1.3.6.1.2.1.33.1.8.5INTEGER {on(1), off(2)}read-writecurrent
upsConfig
OBJECT-IDENTITY
1.3.6.1.2.1.33.1.9
upsConfigInputVoltage
OBJECT-TYPE
The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
1.3.6.1.2.1.33.1.9.1NonNegativeIntegerread-writecurrent
upsConfigInputFreq
OBJECT-TYPE
The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
1.3.6.1.2.1.33.1.9.2NonNegativeIntegerread-writecurrent
upsConfigOutputVoltage
OBJECT-TYPE
The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
1.3.6.1.2.1.33.1.9.3NonNegativeIntegerread-writecurrent
upsConfigOutputFreq
OBJECT-TYPE
The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
1.3.6.1.2.1.33.1.9.4NonNegativeIntegerread-writecurrent
upsConfigOutputVA
OBJECT-TYPE
The magnitude of the nominal Volt-Amp rating.
1.3.6.1.2.1.33.1.9.5NonNegativeIntegerread-onlycurrent
upsConfigOutputPower
OBJECT-TYPE
The magnitude of the nominal true power rating.
1.3.6.1.2.1.33.1.9.6NonNegativeIntegerread-onlycurrent
upsConfigLowBattTime
OBJECT-TYPE
The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.
1.3.6.1.2.1.33.1.9.7NonNegativeIntegerread-writecurrent
upsConfigAudibleStatus
OBJECT-TYPE
The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.
1.3.6.1.2.1.33.1.9.8INTEGER {disabled(1), enabled(2), muted(3)}read-writecurrent
upsConfigLowVoltageTransferPoint
OBJECT-TYPE
The minimum input line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.2.1.33.1.9.9NonNegativeIntegerread-writecurrent
upsConfigHighVoltageTransferPoint
OBJECT-TYPE
The maximum line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.2.1.33.1.9.10NonNegativeIntegerread-writecurrent
upsTraps
OBJECT-IDENTITY
1.3.6.1.2.1.33.2
upsConformance
OBJECT-IDENTITY
1.3.6.1.2.1.33.3
upsCompliances
OBJECT-IDENTITY
1.3.6.1.2.1.33.3.1
upsGroups
OBJECT-IDENTITY
1.3.6.1.2.1.33.3.2
upsSubsetGroups
OBJECT-IDENTITY
1.3.6.1.2.1.33.3.2.1
upsBasicGroups
OBJECT-IDENTITY
1.3.6.1.2.1.33.3.2.2
upsFullGroups
OBJECT-IDENTITY
1.3.6.1.2.1.33.3.2.3

Notifications

NameOIDStatus
upsTrapOnBattery
NOTIFICATION-TYPE
The UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery.
1.3.6.1.2.1.33.2.1current
upsTrapTestCompleted
NOTIFICATION-TYPE
This trap is sent upon completion of a UPS diagnostic test.
1.3.6.1.2.1.33.2.2current
upsTrapAlarmEntryAdded
NOTIFICATION-TYPE
This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and upsAlarmTestInProgress.
1.3.6.1.2.1.33.2.3current
upsTrapAlarmEntryRemoved
NOTIFICATION-TYPE
This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress.
1.3.6.1.2.1.33.2.4current

Conformance

NameOIDStatus
upsSubsetCompliance
MODULE-COMPLIANCE
The compliance statement for UPSs that only support the two-contact communication protocol.
1.3.6.1.2.1.33.3.1.1current
upsBasicCompliance
MODULE-COMPLIANCE
The compliance statement for UPSs that support full-featured functions, such as control.
1.3.6.1.2.1.33.3.1.2current
upsFullCompliance
MODULE-COMPLIANCE
The compliance statement for UPSs that support advanced full-featured functions.
1.3.6.1.2.1.33.3.1.3current
upsSubsetIdentGroup
OBJECT-GROUP
The upsSubsetIdentGroup defines objects which are common across all UPSs which meet subset compliance. Most devices which conform to the upsSubsetIdentGroup will provide access to these objects via a proxy agent. If the proxy agent is compatible with multiple UPS types, configuration of the proxy agent will require specifying some of these values, either individually, or as a group (perhaps through a table lookup mechanism based on the UPS model number).
1.3.6.1.2.1.33.3.2.1.1current
upsSubsetBatteryGroup
OBJECT-GROUP
The upsSubsetBatteryGroup defines the objects that are common to battery groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.2current
upsSubsetInputGroup
OBJECT-GROUP
The upsSubsetInputGroup defines the objects that are common to the Input groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.3current
upsSubsetOutputGroup
OBJECT-GROUP
The upsSubsetOutputGroup defines the objects that are common to the Output groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.4current
upsSubsetAlarmGroup
OBJECT-GROUP
The upsSubsetAlarmGroup defines the objects that are common to the Alarm groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.6current
upsSubsetControlGroup
OBJECT-GROUP
The upsSubsetControlGroup defines the objects that are common to the Control groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.8current
upsSubsetConfigGroup
OBJECT-GROUP
The upsSubsetConfigGroup defines the objects that are common to the Config groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.9current
upsBasicIdentGroup
OBJECT-GROUP
The upsBasicIdentGroup defines objects which are common to the Ident group of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.1current
upsBasicBatteryGroup
OBJECT-GROUP
The upsBasicBatteryGroup defines the objects that are common to the battery groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.2current
upsBasicInputGroup
OBJECT-GROUP
The upsBasicInputGroup defines the objects that are common to the Input groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.3current
upsBasicOutputGroup
OBJECT-GROUP
The upsBasicOutputGroup defines the objects that are common to the Output groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.4current
upsBasicBypassGroup
OBJECT-GROUP
The upsBasicBypassGroup defines the objects that are common to the Bypass groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.5current
upsBasicAlarmGroup
OBJECT-GROUP
The upsBasicAlarmGroup defines the objects that are common to the Alarm groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.6current
upsBasicTestGroup
OBJECT-GROUP
The upsBasicTestGroup defines the objects that are common to the Test groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.7current
upsBasicControlGroup
OBJECT-GROUP
The upsBasicControlGroup defines the objects that are common to the Control groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.8current
upsBasicConfigGroup
OBJECT-GROUP
The upsBasicConfigGroup defines the objects that are common to the Config groups of UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.9current
upsFullIdentGroup
OBJECT-GROUP
The upsFullIdentGroup defines objects which are common to the Ident group of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.1current
upsFullBatteryGroup
OBJECT-GROUP
The upsFullBatteryGroup defines the objects that are common to the battery groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.2current
upsFullInputGroup
OBJECT-GROUP
The upsFullInputGroup defines the objects that are common to the Input groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.3current
upsFullOutputGroup
OBJECT-GROUP
The upsFullOutputGroup defines the objects that are common to the Output groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.4current
upsFullBypassGroup
OBJECT-GROUP
The upsFullBypassGroup defines the objects that are common to the Bypass groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.5current
upsFullAlarmGroup
OBJECT-GROUP
The upsFullAlarmGroup defines the objects that are common to the Alarm groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.6current
upsFullTestGroup
OBJECT-GROUP
The upsFullTestGroup defines the objects that are common to the Test groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.7current
upsFullControlGroup
OBJECT-GROUP
The upsFullControlGroup defines the objects that are common to the Control groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.8current
upsFullConfigGroup
OBJECT-GROUP
The upsFullConfigGroup defines the objects that are common to the Config groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.9current