LIEBERT-GP-CONDITIONS-MIB
- Registered at
- 1.3.6.1.4.1.476.1.42.1.3.11.3.6.1.4.1.476.1.42.3.2.11.3.6.1.4.1.476.1.42.3.2.41.3.6.1.4.1.476.1.42.3.2.7
- Last updated
- 2013-02-12 00:00
- Organization
- Liebert Corporation
- Revisions
- 2013-02-12 00:00, 2008-11-17 00:00, 2008-07-02 00:00, 2008-01-10 00:00, 2007-05-29 00:00, 2006-08-15 00:00, 2006-02-22 00:00
- Namespace
- liebert
- Source file
LIEBERT-GP-CONDITIONS-MIB- Digest
sha256:3fdac9085c398196ac47baa3b2602e80073f01a629fd8b0a27f35e81e7f6b5d7
Description
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008,2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Contact
Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com Author: Gregory M. Hoge
Imports
| From | Symbols |
|---|---|
| LIEBERT-GP-REGISTRATION-MIB | lgpConditions, liebertConditionsModuleReg |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Gauge32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
3 module(s) in this corpus import this one.
Load order
Every file a consumer needs in order to load this module, dependencies first.
LIEBERT-GP-CONDITIONS-MIB LIEBERT-GP-REGISTRATION-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Under this module's arcs
Where the registration tree carries on below this module.
| Arc | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.2.7.1 | lgpFlexConditionsWellKnown | LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| lgpConditionsWellKnown OBJECT-IDENTITY | 1.3.6.1.4.1.476.1.42.3.2.1 | |||
| lgpConditionHighTemperature OBJECT-IDENTITY The temperature has exceeded the high temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.1 | current | ||
| lgpConditionLowTemperature OBJECT-IDENTITY The temperature is below the low temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.2 | current | ||
| lgpConditionHighHumidity OBJECT-IDENTITY The humidity has exceeded the high humidity threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.3 | current | ||
| lgpConditionLowHumidity OBJECT-IDENTITY The humidity is below the low humidity threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.4 | current | ||
| lgpConditionLossOfAirflow OBJECT-IDENTITY The system has detected a loss of air flow. | 1.3.6.1.4.1.476.1.42.3.2.1.5 | current | ||
| lgpConditionLossOfAirflow1 OBJECT-IDENTITY The system has detected a loss of air flow at sensor 1. | 1.3.6.1.4.1.476.1.42.3.2.1.5.1 | current | ||
| lgpConditionLossOfAirflow2 OBJECT-IDENTITY The system has detected a loss of air flow at sensor 2. | 1.3.6.1.4.1.476.1.42.3.2.1.5.2 | current | ||
| lgpConditionLossOfAirflowBlower1 OBJECT-IDENTITY The system has detected a loss of air flow from blower 1. | 1.3.6.1.4.1.476.1.42.3.2.1.5.3 | current | ||
| lgpConditionLossOfAirflowAllBlowers OBJECT-IDENTITY No air flow through the unit due to failure of all blowers. | 1.3.6.1.4.1.476.1.42.3.2.1.5.4 | current | ||
| lgpConditionChangeFilter OBJECT-IDENTITY The system has detected a condition indicating the air filter should be changed. | 1.3.6.1.4.1.476.1.42.3.2.1.6 | current | ||
| lgpConditionCompressorHighHeadPressure OBJECT-IDENTITY This system has detected an excessive head pressure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.7 | current | ||
| lgpConditionCompressor1HighHeadPressure OBJECT-IDENTITY The system has detected excessive head pressure in compressor 1. | 1.3.6.1.4.1.476.1.42.3.2.1.7.1 | current | ||
| lgpConditionCompressor1AHighHeadPressure OBJECT-IDENTITY The system has detected excessive head pressure in compressor 1A. | 1.3.6.1.4.1.476.1.42.3.2.1.7.1.1 | current | ||
| lgpConditionCompressor1BHighHeadPressure OBJECT-IDENTITY The system has detected excessive head pressure in compressor 1B. | 1.3.6.1.4.1.476.1.42.3.2.1.7.1.2 | current | ||
| lgpConditionCompressor2HighHeadPressure OBJECT-IDENTITY The system has detected excessive head pressure in compressor 2. | 1.3.6.1.4.1.476.1.42.3.2.1.7.2 | current | ||
| lgpConditionCompressor2AHighHeadPressure OBJECT-IDENTITY The system has detected excessive head pressure in compressor 2A. | 1.3.6.1.4.1.476.1.42.3.2.1.7.2.1 | current | ||
| lgpConditionCompressor2BHighHeadPressure OBJECT-IDENTITY The system has detected excessive head pressure in compressor 2B. | 1.3.6.1.4.1.476.1.42.3.2.1.7.2.2 | current | ||
| lgpConditionCompressor3HighHeadPressure OBJECT-IDENTITY The system has detected excessive head pressure in compressor 3. | 1.3.6.1.4.1.476.1.42.3.2.1.7.3 | current | ||
| lgpConditionCompressor4HighHeadPressure OBJECT-IDENTITY The system has detected excessive head pressure in compressor 4. | 1.3.6.1.4.1.476.1.42.3.2.1.7.4 | current | ||
| lgpConditionCompressorOverload OBJECT-IDENTITY This system has detected a compressor overload condition. | 1.3.6.1.4.1.476.1.42.3.2.1.8 | current | ||
| lgpConditionCompressor1Overload OBJECT-IDENTITY The system has detected an overload condition on compressor 1. | 1.3.6.1.4.1.476.1.42.3.2.1.8.1 | current | ||
| lgpConditionCompressor2Overload OBJECT-IDENTITY The system has detected an overload condition on compressor 2. | 1.3.6.1.4.1.476.1.42.3.2.1.8.2 | current | ||
| lgpConditionCompressor3Overload OBJECT-IDENTITY The system has detected an overload condition on compressor 3. | 1.3.6.1.4.1.476.1.42.3.2.1.8.3 | current | ||
| lgpConditionCompressor4Overload OBJECT-IDENTITY The system has detected an overload condition on compressor 4. | 1.3.6.1.4.1.476.1.42.3.2.1.8.4 | current | ||
| lgpConditionCompressorShortCycle OBJECT-IDENTITY A compressor has exceeded the maximum number of starts in a minimum time period. | 1.3.6.1.4.1.476.1.42.3.2.1.9 | current | ||
| lgpConditionCompressor1ShortCycle OBJECT-IDENTITY The system has detected a short cycle event on compressor 1. The compressor has exceeded the maximum number of starts for specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.9.1 | current | ||
| lgpConditionCompressor1AShortCycle OBJECT-IDENTITY The system has detected a short cycle event on compressor 1A. The compressor has exceeded the maximum number of starts for specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.9.1.1 | current | ||
| lgpConditionCompressor1BShortCycle OBJECT-IDENTITY The system has detected a short cycle event on compressor 1B. The compressor has exceeded the maximum number of starts for specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.9.1.2 | current | ||
| lgpConditionCompressor2ShortCycle OBJECT-IDENTITY The system has detected a short cycle event on compressor 2. The compressor has exceeded the maximum number of starts for specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.9.2 | current | ||
| lgpConditionCompressor2AShortCycle OBJECT-IDENTITY The system has detected a short cycle event on compressor 2A. The compressor has exceeded the maximum number of starts for specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.9.2.1 | current | ||
| lgpConditionCompressor2BShortCycle OBJECT-IDENTITY The system has detected a short cycle event on compressor 2B. The compressor has exceeded the maximum number of starts for specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.9.2.2 | current | ||
| lgpConditionCompressor3ShortCycle OBJECT-IDENTITY The system has detected a short cycle event on compressor 3. The compressor has exceeded the maximum number of starts for specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.9.3 | current | ||
| lgpConditionCompressor4ShortCycle OBJECT-IDENTITY The system has detected a short cycle event on compressor 4. The compressor has exceeded the maximum number of starts for specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.9.4 | current | ||
| lgpConditionCompressorLowSuctionPressure OBJECT-IDENTITY The pressure at a compressor inlet has dropped below the minimum setting. | 1.3.6.1.4.1.476.1.42.3.2.1.10 | current | ||
| lgpConditionCompressor1LowSuctionPressure OBJECT-IDENTITY The pressure at compressor 1 inlet has dropped below the minimum setting. | 1.3.6.1.4.1.476.1.42.3.2.1.10.1 | current | ||
| lgpConditionCompressor2LowSuctionPressure OBJECT-IDENTITY The pressure at compressor 2 inlet has dropped below the minimum setting. | 1.3.6.1.4.1.476.1.42.3.2.1.10.2 | current | ||
| lgpConditionCompressor3LowSuctionPressure OBJECT-IDENTITY The pressure at compressor 3 inlet has dropped below the minimum setting. | 1.3.6.1.4.1.476.1.42.3.2.1.10.3 | current | ||
| lgpConditionCompressor4LowSuctionPressure OBJECT-IDENTITY The pressure at compressor 4 inlet has dropped below the minimum setting. | 1.3.6.1.4.1.476.1.42.3.2.1.10.4 | current | ||
| lgpConditionMainFanOverLoad OBJECT-IDENTITY The system has detected a main fan overload condition. | 1.3.6.1.4.1.476.1.42.3.2.1.11 | current | ||
| lgpConditionManualOverride OBJECT-IDENTITY The system has detected a manual override condition. | 1.3.6.1.4.1.476.1.42.3.2.1.12 | current | ||
| lgpConditionStandbyGlycoolPumpOn OBJECT-IDENTITY The standby Glycol or Glycool pump is activated. | 1.3.6.1.4.1.476.1.42.3.2.1.13 | current | ||
| lgpConditionWaterUnderFloor OBJECT-IDENTITY Moisture has been detected under the floor. | 1.3.6.1.4.1.476.1.42.3.2.1.14 | current | ||
| lgpConditionHumidifierProblem OBJECT-IDENTITY The system has detected a humidifier problem. | 1.3.6.1.4.1.476.1.42.3.2.1.15 | current | ||
| lgpConditionLowWaterInHumidifier OBJECT-IDENTITY The system has detected a low water condition in the humidifier reservoir. | 1.3.6.1.4.1.476.1.42.3.2.1.16 | current | ||
| lgpConditionSmokeDetected OBJECT-IDENTITY The system has detected smoke. | 1.3.6.1.4.1.476.1.42.3.2.1.17 | current | ||
| lgpConditionLowWaterFlow OBJECT-IDENTITY The system has detected a low water flow rate condition. | 1.3.6.1.4.1.476.1.42.3.2.1.18 | current | ||
| lgpConditionLostPower OBJECT-IDENTITY The system has lost power before being switched off using the controls. This condition is activated when power is restored. | 1.3.6.1.4.1.476.1.42.3.2.1.19 | current | ||
| lgpGeneralFault OBJECT-IDENTITY A fault condition has been detected that is not identified in the well known list. | 1.3.6.1.4.1.476.1.42.3.2.1.20 | current | ||
| lgpConditionLocalAlarm OBJECT-IDENTITY This system has detected a local, or customer, alarm condition. | 1.3.6.1.4.1.476.1.42.3.2.1.21 | current | ||
| lgpConditionLocalAlarm1 OBJECT-IDENTITY The system has detected that customer alarm condition 1 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.21.1 | current | ||
| lgpConditionLocalAlarm2 OBJECT-IDENTITY The system has detected that customer alarm condition 2 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.21.2 | current | ||
| lgpConditionLocalAlarm3 OBJECT-IDENTITY The system has detected that customer alarm condition 3 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.21.3 | current | ||
| lgpConditionLocalAlarm4 OBJECT-IDENTITY The system has detected that customer alarm condition 4 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.21.4 | current | ||
| lgpConditionLocalAlarm5 OBJECT-IDENTITY The system has detected that customer alarm condition 5 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.21.5 | current | ||
| lgpConditionLocalAlarm6 OBJECT-IDENTITY The system has detected that customer alarm condition 6 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.21.6 | current | ||
| lgpConditionLocalAlarm7 OBJECT-IDENTITY The system has detected that customer alarm condition 7 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.21.7 | current | ||
| lgpConditionLocalAlarm8 OBJECT-IDENTITY The system has detected that customer alarm condition 8 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.21.8 | current | ||
| lgpConditionStandbyUnitOn OBJECT-IDENTITY The system has detected the standby unit is operating. | 1.3.6.1.4.1.476.1.42.3.2.1.22 | current | ||
| lgpConditionCompressorLowPressure OBJECT-IDENTITY This system has detected a low head compressor condition. | 1.3.6.1.4.1.476.1.42.3.2.1.23 | current | ||
| lgpConditionCompressor1LowPressure OBJECT-IDENTITY The system has detected low pressure in compressor 1. | 1.3.6.1.4.1.476.1.42.3.2.1.23.1 | current | ||
| lgpConditionTandemCompressorCircuit1LowPressure OBJECT-IDENTITY The system has detected low pressure in tandem compressor circuit 1. | 1.3.6.1.4.1.476.1.42.3.2.1.23.1.1 | current | ||
| lgpConditionCompressor2LowPressure OBJECT-IDENTITY The system has detected low pressure in compressor 2. | 1.3.6.1.4.1.476.1.42.3.2.1.23.2 | current | ||
| lgpConditionTandemCompressorCircuit2LowPressure OBJECT-IDENTITY The system has detected low pressure in tandem compressor circuit 2. | 1.3.6.1.4.1.476.1.42.3.2.1.23.2.1 | current | ||
| lgpConditionCompressor3LowPressure OBJECT-IDENTITY The system has detected low pressure in compressor 3. | 1.3.6.1.4.1.476.1.42.3.2.1.23.3 | current | ||
| lgpConditionCompressor4LowPressure OBJECT-IDENTITY The system has detected low pressure in compressor 4. | 1.3.6.1.4.1.476.1.42.3.2.1.23.4 | current | ||
| lgpConditionHighWaterInPan OBJECT-IDENTITY The system has detected a high water condition in the condenser pan. | 1.3.6.1.4.1.476.1.42.3.2.1.24 | current | ||
| lgpConditionFaultySensor OBJECT-IDENTITY The system has detected a faulty temperature/humidity sensor. | 1.3.6.1.4.1.476.1.42.3.2.1.25 | current | ||
| lgpConditionServiceCooling OBJECT-IDENTITY The Cooling system requires scheduled maintenance. | 1.3.6.1.4.1.476.1.42.3.2.1.26 | current | ||
| lgpConditionServiceHumidifier OBJECT-IDENTITY The Humidifier requires scheduled maintenance. | 1.3.6.1.4.1.476.1.42.3.2.1.27 | current | ||
| lgpConditionSystemControlBatteryLow OBJECT-IDENTITY Charge level of the system control's battery is below the alarm set point. | 1.3.6.1.4.1.476.1.42.3.2.1.28 | current | ||
| lgpConditionGroundSystemFault OBJECT-IDENTITY The system has detected a ground system fault. | 1.3.6.1.4.1.476.1.42.3.2.1.29 | current | ||
| lgpConditionGroundFailure OBJECT-IDENTITY The system has detected a ground failure. | 1.3.6.1.4.1.476.1.42.3.2.1.30 | current | ||
| lgpConditionSecurityBreach OBJECT-IDENTITY The system has detected a security breach. | 1.3.6.1.4.1.476.1.42.3.2.1.31 | current | ||
| lgpConditionEmergencyShutdown OBJECT-IDENTITY The system has detected an emergency shutdown condition. The System is shutting down as a result of this emergency. | 1.3.6.1.4.1.476.1.42.3.2.1.32 | current | ||
| lgpConditionOnBypass OBJECT-IDENTITY This system has detected the load is being powered by a bypass source. | 1.3.6.1.4.1.476.1.42.3.2.1.33 | current | ||
| lgpConditionLoadOnBypass OBJECT-IDENTITY The load is being powered by a bypass source. | 1.3.6.1.4.1.476.1.42.3.2.1.33.1 | obsolete | ||
| lgpConditionLoadOnMaintenceBypass OBJECT-IDENTITY The load is being powered by a maintenance bypass source. | 1.3.6.1.4.1.476.1.42.3.2.1.33.2 | current | ||
| lgpConditionParallelSysLoadOnBypass OBJECT-IDENTITY The parallel system has transferred to bypass. | 1.3.6.1.4.1.476.1.42.3.2.1.33.3 | current | ||
| lgpConditionLoadOnBypassByImpact OBJECT-IDENTITY The system has detected a load impact and has transferred the load to the bypass source. | 1.3.6.1.4.1.476.1.42.3.2.1.33.4 | current | ||
| lgpConditionLoadTransferedToBypass OBJECT-IDENTITY The system has transferred to bypass. The load is being powered by the bypass source. | 1.3.6.1.4.1.476.1.42.3.2.1.33.5 | current | ||
| lgpConditionEmergencyTransferToBypass OBJECT-IDENTITY The system has performed an emergency transfer to bypass. | 1.3.6.1.4.1.476.1.42.3.2.1.33.6 | current | ||
| lgpConditionOutputToLoadVoltTHD OBJECT-IDENTITY The total harmonic distortion (THD) of the output voltage has exceeded a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.34 | current | ||
| lgpConditionLogicFailure OBJECT-IDENTITY The system has detected a control logic failure. | 1.3.6.1.4.1.476.1.42.3.2.1.35 | current | ||
| lgpConditionPowerSupplyFault OBJECT-IDENTITY This system had detected a power supply fault condition. | 1.3.6.1.4.1.476.1.42.3.2.1.36 | current | ||
| lgpConditionPowerSupply1Fault OBJECT-IDENTITY The system has detected power supply 1 is in a fault condition. | 1.3.6.1.4.1.476.1.42.3.2.1.36.1 | current | ||
| lgpConditionPowerSupply2Fault OBJECT-IDENTITY The system has detected power supply 2 is in a fault condition. | 1.3.6.1.4.1.476.1.42.3.2.1.36.2 | current | ||
| lgpConditionPowerSupplyFailure OBJECT-IDENTITY This system has detected a power supply failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.37 | current | ||
| lgpConditionPowerSupply1Failure OBJECT-IDENTITY The system has detected power supply 1 has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.37.1 | current | ||
| lgpConditionPowerSupply2Failure OBJECT-IDENTITY The system has detected power supply 2 has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.37.2 | current | ||
| lgpConditionSource1PowerSupplyInputFailure OBJECT-IDENTITY The system has detected the source 1 Power supply input has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.37.3 | current | ||
| lgpConditionSource2PowerSupplyInputFailure OBJECT-IDENTITY The system has detected the source 2 Power supply input has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.37.4 | current | ||
| lgpConditionPowerSupplyLogicFailure OBJECT-IDENTITY The system has detected a power supply logic failure. | 1.3.6.1.4.1.476.1.42.3.2.1.37.5 | current | ||
| lgpConditionCompressorPowerSupplyFailure OBJECT-IDENTITY The system has detected the power supply to the compressors has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.37.6 | current | ||
| lgpConditionOverVoltage OBJECT-IDENTITY This system has detected an over voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.1.38 | current | ||
| lgpConditionSource1OverVoltage OBJECT-IDENTITY The system has detected an over voltage condition on source 1. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.38.1 | current | ||
| lgpConditionSource2OverVoltage OBJECT-IDENTITY The system has detected an over voltage condition on source 2. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.38.2 | current | ||
| lgpConditionOutputToLoadOverVoltage OBJECT-IDENTITY The system has detected the output to load is in an over-voltage condition. The voltage for the load has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.38.3 | current | ||
| lgpConditionInputOverVoltage OBJECT-IDENTITY The system has detected an input over voltage condition. The voltage measurement has risen above a pre-determined threshold for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.38.4 | current | ||
| lgpConditionBypassOverVoltage OBJECT-IDENTITY The system has detected an over voltage condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.38.5 | current | ||
| lgpConditionBypassOverVoltageFailure OBJECT-IDENTITY The system has detected an over voltage failure condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.38.6 | current | ||
| lgpConditionBatteryOverVoltage OBJECT-IDENTITY The system has detected a battery over voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.1.38.7 | current | ||
| lgpConditionDcBusOverVoltage OBJECT-IDENTITY This system has detected a DC Bus over voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.1.38.8 | current | ||
| lgpConditionDcBus1OverVoltage OBJECT-IDENTITY The system has detected an over voltage condition on DC Bus 1. | 1.3.6.1.4.1.476.1.42.3.2.1.38.8.1 | current | ||
| lgpConditionDcBus2OverVoltage OBJECT-IDENTITY The system has detected an over voltage condition on DC Bus 2. | 1.3.6.1.4.1.476.1.42.3.2.1.38.8.2 | current | ||
| lgpConditionDcBus1OverVoltageFailure OBJECT-IDENTITY The system has detected an over voltage failure condition on DC Bus 1. | 1.3.6.1.4.1.476.1.42.3.2.1.38.8.3 | current | ||
| lgpConditionDcBus2OverVoltageFailure OBJECT-IDENTITY The system has detected an over voltage failure condition on DC Bus 2. | 1.3.6.1.4.1.476.1.42.3.2.1.38.8.4 | current | ||
| lgpConditionUnderVoltage OBJECT-IDENTITY This system has detected an under voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.1.39 | current | ||
| lgpConditionSource1UnderVoltage OBJECT-IDENTITY The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.39.1 | current | ||
| lgpConditionSource2UnderVoltage OBJECT-IDENTITY The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.39.2 | current | ||
| lgpConditionOutputToLoadUnderVoltage OBJECT-IDENTITY The system has detected the output to load is in an under-voltage condition. The voltage for the load has fallen below a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.39.3 | current | ||
| lgpConditionSource1UnderVoltageRMS OBJECT-IDENTITY The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.39.4 | current | ||
| lgpConditionSource2UnderVoltageRMS OBJECT-IDENTITY The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.39.5 | current | ||
| lgpConditionInputUnderVoltage OBJECT-IDENTITY The system has detected an input under voltage condition. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.39.6 | current | ||
| lgpConditionBypassUnderVoltage OBJECT-IDENTITY The system has detected an under voltage condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.39.7 | current | ||
| lgpConditionBypassUnderVoltageFailure OBJECT-IDENTITY The system has detected an under voltage failure condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.39.8 | current | ||
| lgpConditionBatteryUnderVoltage OBJECT-IDENTITY The system has detected a battery under voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.1.39.9 | current | ||
| lgpConditionDcBusUnderVoltage OBJECT-IDENTITY This system has detected a DC bus under voltage condition | 1.3.6.1.4.1.476.1.42.3.2.1.39.10 | current | ||
| lgpConditionDcBus1UnderVoltage OBJECT-IDENTITY The system has detected an under voltage condition on DC Bus 1. | 1.3.6.1.4.1.476.1.42.3.2.1.39.10.1 | current | ||
| lgpConditionDcBus2UnderVoltage OBJECT-IDENTITY The system has detected an under voltage condition on DC Bus 2. | 1.3.6.1.4.1.476.1.42.3.2.1.39.10.2 | current | ||
| lgpConditionDcBus1UnderVoltageFailure OBJECT-IDENTITY The system has detected an under voltage failure condition on DC Bus 1. | 1.3.6.1.4.1.476.1.42.3.2.1.39.10.3 | current | ||
| lgpConditionDcBus2UnderVoltageFailure OBJECT-IDENTITY The system has detected an under voltage failure condition on DC Bus 2. | 1.3.6.1.4.1.476.1.42.3.2.1.39.10.4 | current | ||
| lgpConditionOverload OBJECT-IDENTITY This system has detected an overload condition. | 1.3.6.1.4.1.476.1.42.3.2.1.40 | current | ||
| lgpConditionSource1Overload OBJECT-IDENTITY The system has detected an overload condition on source 1. The power requirement for this source has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.40.1 | current | ||
| lgpConditionSystemOverload OBJECT-IDENTITY The system has detected an overload condition. | 1.3.6.1.4.1.476.1.42.3.2.1.40.2 | current | ||
| lgpConditionSource1PeakCurrentOverLoad OBJECT-IDENTITY The system has detected source 1 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.40.3 | current | ||
| lgpConditionSource2PeakCurrentOverLoad OBJECT-IDENTITY The system has detected source 2 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.40.4 | current | ||
| lgpConditionOutputToLoadOverLimit OBJECT-IDENTITY The system had detected that the output to the load has exceeded the lgpPwrOutputToLoadUserOverloadLimit. | 1.3.6.1.4.1.476.1.42.3.2.1.40.5 | current | ||
| lgpConditionOutputToLoadOverload OBJECT-IDENTITY The system has detected an output overload condition. | 1.3.6.1.4.1.476.1.42.3.2.1.40.6 | current | ||
| lgpConditionParallelSysOverload OBJECT-IDENTITY The parallel system has detected an overload condition. | 1.3.6.1.4.1.476.1.42.3.2.1.40.7 | current | ||
| lgpConditionBypassCurrentOverload OBJECT-IDENTITY With the load on bypass static switch, the measured output RMS current has exceeded a specified percentage of the nominal RMS current. | 1.3.6.1.4.1.476.1.42.3.2.1.40.8 | current | ||
| lgpConditionBypassCurrentOverloadPhsA OBJECT-IDENTITY With the load on bypass static switch, the measured phase A output RMS current has exceeded a specified percentage of the nominal per-phase RMS current. | 1.3.6.1.4.1.476.1.42.3.2.1.40.8.1 | current | ||
| lgpConditionBypassCurrentOverloadPhsB OBJECT-IDENTITY With the load on bypass static switch, the measured phase B output RMS current has exceeded a specified percentage of the nominal per-phase RMS current. | 1.3.6.1.4.1.476.1.42.3.2.1.40.8.2 | current | ||
| lgpConditionBypassCurrentOverloadPhsC OBJECT-IDENTITY With the load on bypass static switch, the measured phase C output RMS current has exceeded a specified percentage of the nominal per-phase RMS current. | 1.3.6.1.4.1.476.1.42.3.2.1.40.8.3 | current | ||
| lgpConditionScrShort OBJECT-IDENTITY This system has detected a Silicon Controlled Rectifier (SCR) short condition. | 1.3.6.1.4.1.476.1.42.3.2.1.41 | current | ||
| lgpConditionSource1ScrShort OBJECT-IDENTITY The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition. | 1.3.6.1.4.1.476.1.42.3.2.1.41.1 | current | ||
| lgpConditionSource2ScrShort OBJECT-IDENTITY The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition. | 1.3.6.1.4.1.476.1.42.3.2.1.41.2 | current | ||
| lgpConditionBypassScrShort OBJECT-IDENTITY The system has detected a Silicon Controlled Rectifier (SCR) short condition on the bypass. | 1.3.6.1.4.1.476.1.42.3.2.1.41.3 | current | ||
| lgpConditionInvStaticSwScrShort OBJECT-IDENTITY The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCRs). | 1.3.6.1.4.1.476.1.42.3.2.1.41.4 | current | ||
| lgpConditionSource1NeutralScrShort OBJECT-IDENTITY The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition on the neutral line. | 1.3.6.1.4.1.476.1.42.3.2.1.41.5 | current | ||
| lgpConditionSource2NeutralScrShort OBJECT-IDENTITY The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition on the neutral line. | 1.3.6.1.4.1.476.1.42.3.2.1.41.6 | current | ||
| lgpConditionScrOpen OBJECT-IDENTITY This system has detected a Silicon Controlled Rectifier (SCR) open condition. | 1.3.6.1.4.1.476.1.42.3.2.1.42 | current | ||
| lgpConditionSource1ScrOpen OBJECT-IDENTITY The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition. | 1.3.6.1.4.1.476.1.42.3.2.1.42.1 | current | ||
| lgpConditionSource2ScrOpen OBJECT-IDENTITY The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition. | 1.3.6.1.4.1.476.1.42.3.2.1.42.2 | current | ||
| lgpConditionBypassScrOpen OBJECT-IDENTITY The system has detected a Silicon Controlled Rectifier (SCR) open condition on the bypass. | 1.3.6.1.4.1.476.1.42.3.2.1.42.3 | current | ||
| lgpConditionSource1NeutralScrOpen OBJECT-IDENTITY The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition on the neutral line. | 1.3.6.1.4.1.476.1.42.3.2.1.42.4 | current | ||
| lgpConditionSource2NeutralScrOpen OBJECT-IDENTITY The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition on the neutral line. | 1.3.6.1.4.1.476.1.42.3.2.1.42.5 | current | ||
| lgpConditionFanFailure OBJECT-IDENTITY This system has detected a fan failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.43 | current | ||
| lgpConditionFan1Failure OBJECT-IDENTITY The system has detected a fan 1 failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.43.1 | current | ||
| lgpConditionRedundantFanFailure OBJECT-IDENTITY A failure has occurred in a fan that cools the system's internal components and has resulted in a loss of fan redundancy. | 1.3.6.1.4.1.476.1.42.3.2.1.43.2 | current | ||
| lgpConditionMultipleFanFailure OBJECT-IDENTITY Multiple fans have failed resulting in a decreased ability to cool the system's internal components. | 1.3.6.1.4.1.476.1.42.3.2.1.43.3 | current | ||
| lgpConditionBlowerFanFailure OBJECT-IDENTITY The system has detected a problem with one or more of the blower fans. These are not the system internal cooling fans. | 1.3.6.1.4.1.476.1.42.3.2.1.43.4 | current | ||
| lgpConditionBottomBlowerFanFailure OBJECT-IDENTITY The bottom environmental unit blower fan is not operating within its normal parameters. | 1.3.6.1.4.1.476.1.42.3.2.1.43.4.1 | current | ||
| lgpConditionTopBlowerFanFailure OBJECT-IDENTITY The top environmental unit blower fan is not operating within its normal parameters. | 1.3.6.1.4.1.476.1.42.3.2.1.43.4.2 | current | ||
| lgpConditionCondenserFanVFDFailure OBJECT-IDENTITY The system has detected a problem with the Variable Frequency Drive system for the condenser fan. | 1.3.6.1.4.1.476.1.42.3.2.1.43.5 | current | ||
| lgpConditionFanPowerFailure OBJECT-IDENTITY The system has detected a power failure on one or more fans. | 1.3.6.1.4.1.476.1.42.3.2.1.43.6 | current | ||
| lgpConditionTransferInhibited OBJECT-IDENTITY The system is preventing a transfer of the load to the alternate source. | 1.3.6.1.4.1.476.1.42.3.2.1.44 | current | ||
| lgpConditionAutoReTransferPrimed OBJECT-IDENTITY The system is capable to retransfer to the preferred source. | 1.3.6.1.4.1.476.1.42.3.2.1.45 | current | ||
| lgpConditionSourcesOutOfSync OBJECT-IDENTITY The system has detected that the input sources are not within the specified phase difference (synchronization window). | 1.3.6.1.4.1.476.1.42.3.2.1.46 | current | ||
| lgpConditionSourceFailure OBJECT-IDENTITY This system has detected an input source failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.47 | current | ||
| lgpConditionSource1Failure OBJECT-IDENTITY The system has detected source 1 has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.47.1 | current | ||
| lgpConditionSource2Failure OBJECT-IDENTITY The system has detected source 2 has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.47.2 | current | ||
| lgpConditionAutoReTransferInhibited OBJECT-IDENTITY The system is preventing a retransfer of the load back to the preferred source. | 1.3.6.1.4.1.476.1.42.3.2.1.48 | current | ||
| lgpConditionAutoReTransferFailed OBJECT-IDENTITY The system is failing to automatically retransfer the load back to the preferred source. | 1.3.6.1.4.1.476.1.42.3.2.1.49 | current | ||
| lgpConditionFuseOpen OBJECT-IDENTITY This system has detected an open fuse condition. | 1.3.6.1.4.1.476.1.42.3.2.1.50 | current | ||
| lgpConditionControlFuse1Open OBJECT-IDENTITY The system has detected a control power fuse 1 open condition. | 1.3.6.1.4.1.476.1.42.3.2.1.50.1 | current | ||
| lgpConditionControlFuse2Open OBJECT-IDENTITY The system has detected a control power fuse 2 open condition. | 1.3.6.1.4.1.476.1.42.3.2.1.50.2 | current | ||
| lgpConditionRectifierFuseOpen OBJECT-IDENTITY The system has detected a rectifier fuse open condition. | 1.3.6.1.4.1.476.1.42.3.2.1.50.3 | current | ||
| lgpConditionInverterFuseOpen OBJECT-IDENTITY The system has detected an inverter fuse open condition. | 1.3.6.1.4.1.476.1.42.3.2.1.50.4 | current | ||
| lgpConditionOutputToLoadFuseOpen OBJECT-IDENTITY The system has detected an output to load fuse open condition. | 1.3.6.1.4.1.476.1.42.3.2.1.50.5 | current | ||
| lgpConditionDcCapacitorFuseOpen OBJECT-IDENTITY The system has detected a DC capacitor fuse open condition. | 1.3.6.1.4.1.476.1.42.3.2.1.50.6 | current | ||
| lgpConditionDisconnect OBJECT-IDENTITY The system has detected a disconnect condition. | 1.3.6.1.4.1.476.1.42.3.2.1.51 | current | ||
| lgpConditionSource1DisconnectOpen OBJECT-IDENTITY The system has detected the source 1 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.1 | current | ||
| lgpConditionSource2DisconnectOpen OBJECT-IDENTITY The system has detected the source 2 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.2 | current | ||
| lgpConditionSource1PduDisconnectOpen OBJECT-IDENTITY The system has detected the source 1 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.3 | current | ||
| lgpConditionSource2PduDisconnectOpen OBJECT-IDENTITY The system has detected the source 2 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.4 | current | ||
| lgpConditionOutputToLoadDisconnect1Open OBJECT-IDENTITY The system has detected Output to load disconnect 1 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.5 | current | ||
| lgpConditionOutputToLoadDisconnect2Open OBJECT-IDENTITY The system has detected Output to load disconnect 2 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.6 | current | ||
| lgpConditionSource1BypassDisconnectClosed OBJECT-IDENTITY The system has detected the source 1 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.7 | current | ||
| lgpConditionSource2BypassDisconnectClosed OBJECT-IDENTITY The system has detected the source 2 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.8 | current | ||
| lgpConditionOutputToLoadNeutralDisconnectOpen OBJECT-IDENTITY The system has detected the output to load neutral disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.9 | current | ||
| lgpConditionBatteryDisconnectOpen OBJECT-IDENTITY The system has detected the battery disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.10 | current | ||
| lgpConditionBatteryDiscOpenCab01 OBJECT-IDENTITY The system has detected the cabinet 1 battery disconnect is open. | 1.3.6.1.4.1.476.1.42.3.2.1.51.10.1 | current | ||
| lgpConditionBatteryDiscOpenCab02 OBJECT-IDENTITY The system has detected the cabinet 2 battery disconnect is open. | 1.3.6.1.4.1.476.1.42.3.2.1.51.10.2 | current | ||
| lgpConditionBatteryDiscOpenCab03 OBJECT-IDENTITY The system has detected the cabinet 3 battery disconnect is open. | 1.3.6.1.4.1.476.1.42.3.2.1.51.10.3 | current | ||
| lgpConditionBatteryDiscOpenCab04 OBJECT-IDENTITY The system has detected the cabinet 4 battery disconnect is open. | 1.3.6.1.4.1.476.1.42.3.2.1.51.10.4 | current | ||
| lgpConditionBatteryDiscOpenCab05 OBJECT-IDENTITY The system has detected the cabinet 5 battery disconnect is open. | 1.3.6.1.4.1.476.1.42.3.2.1.51.10.5 | current | ||
| lgpConditionBatteryDiscOpenCab06 OBJECT-IDENTITY The system has detected the cabinet 6 battery disconnect is open. | 1.3.6.1.4.1.476.1.42.3.2.1.51.10.6 | current | ||
| lgpConditionBatteryDiscOpenCab07 OBJECT-IDENTITY The system has detected the cabinet 7 battery disconnect is open. | 1.3.6.1.4.1.476.1.42.3.2.1.51.10.7 | current | ||
| lgpConditionBatteryDiscOpenCab08 OBJECT-IDENTITY The system has detected the cabinet 8 battery disconnect is open. | 1.3.6.1.4.1.476.1.42.3.2.1.51.10.8 | current | ||
| lgpConditionInputDisconnectOpen OBJECT-IDENTITY The system has detected the input disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.11 | current | ||
| lgpConditionOutputToLoadDisconnectOpen OBJECT-IDENTITY The system has detected the Output to load disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.12 | current | ||
| lgpConditionBypassDisconnectOpen OBJECT-IDENTITY The system has detected the bypass disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.13 | current | ||
| lgpConditionStaticSwitchDisconnectOpen OBJECT-IDENTITY The system has detected the static switch disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.51.14 | current | ||
| lgpConditionBreakerOpenFailure OBJECT-IDENTITY A breaker in the system has failed to respond to an Open signal. | 1.3.6.1.4.1.476.1.42.3.2.1.51.15 | current | ||
| lgpConditionBreakerCloseFailure OBJECT-IDENTITY A breaker in the system has failed to respond to a Close signal. | 1.3.6.1.4.1.476.1.42.3.2.1.51.16 | current | ||
| lgpConditionFrequencyDeviation OBJECT-IDENTITY This system has detected a frequency deviation condition. The frequency of a source is outside of the pre-determined thresholds for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.52 | current | ||
| lgpConditionSource1FrequencyDeviation OBJECT-IDENTITY The frequency for source 1 has been outside of the pre-determined thresholds for a specified period of time. | 1.3.6.1.4.1.476.1.42.3.2.1.52.1 | current | ||
| lgpConditionSource2FrequencyDeviation OBJECT-IDENTITY The frequency for source 2 has been outside of the pre-determined thresholds for a specified period of time. | 1.3.6.1.4.1.476.1.42.3.2.1.52.2 | current | ||
| lgpConditionInputFrequencyDeviation OBJECT-IDENTITY The frequency for the input has been outside of the pre-determined thresholds for a specified period of time. | 1.3.6.1.4.1.476.1.42.3.2.1.52.3 | current | ||
| lgpConditionOutputToLoadFrequencyDeviation OBJECT-IDENTITY The frequency for the output has been outside of the pre-determined thresholds for a specified period of time. | 1.3.6.1.4.1.476.1.42.3.2.1.52.4 | current | ||
| lgpConditionBypassFrequencyDeviation OBJECT-IDENTITY The frequency for the bypass input has been outside of the pre-determined thresholds for a specified period of time. | 1.3.6.1.4.1.476.1.42.3.2.1.52.5 | current | ||
| lgpConditionOverCurrent OBJECT-IDENTITY This system has detected an over-current condition. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53 | current | ||
| lgpConditionSource1OverCurrent OBJECT-IDENTITY The system has detected an over current condition on source 1. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.1 | current | ||
| lgpConditionSource2OverCurrent OBJECT-IDENTITY The system has detected an over current condition on source 2. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.2 | current | ||
| lgpConditionOutputToLoadOverCurrent OBJECT-IDENTITY The system has detected the output to load is in an over-current condition. The current for the load has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.3 | current | ||
| lgpConditionOutputToLoadOverCurrentPhsA OBJECT-IDENTITY The system has detected the output to load on phase A is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.3.1 | current | ||
| lgpConditionOutputToLoadOverCurrentPhsB OBJECT-IDENTITY The system has detected the output to load on phase B is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.3.2 | current | ||
| lgpConditionOutputToLoadOverCurrentPhsC OBJECT-IDENTITY The system has detected the output to load on phase C is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.3.3 | current | ||
| lgpConditionGroundOverCurrent OBJECT-IDENTITY A ground source is experiencing an over-current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.4 | current | ||
| lgpConditionRectifierOverCurrent OBJECT-IDENTITY The system has detected a rectifier over current condition. The current for the rectifier has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.5 | current | ||
| lgpConditionInverterOverCurrent OBJECT-IDENTITY The system has detected an inverter over current condition. The current for the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.6 | current | ||
| lgpConditionInverterOverCurrentPhsA OBJECT-IDENTITY The system has detected an inverter over current condition on phase A. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.6.1 | current | ||
| lgpConditionInverterOverCurrentPhsB OBJECT-IDENTITY The system has detected an inverter over current condition on phase B. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.6.2 | current | ||
| lgpConditionInverterOverCurrentPhsC OBJECT-IDENTITY The system has detected an inverter over current condition on phase C. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.6.3 | current | ||
| lgpConditionBatteryConverterOverCurrent OBJECT-IDENTITY The system has detected an over current condition on the battery converter. The current of the converter has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.7 | current | ||
| lgpConditionBatteryBalancerOverCurrent OBJECT-IDENTITY The system has detected a battery balancer over current condition. The current at this point has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.8 | current | ||
| lgpConditionHumidifierOverCurrent OBJECT-IDENTITY The system has detected an over current condition on the humidifier. The current of the humidifier has risen above a pre-determined threshold for a defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.9 | current | ||
| lgpConditionInputOverCurrent OBJECT-IDENTITY There is an over current condition on the system input power. The input current has risen above a pre-determined threshold for a pre-defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.10 | current | ||
| lgpConditionSource1NeutralOverCurrent OBJECT-IDENTITY The system has detected an over current condition on the neutral line of source 1. The neutral current at source 1 has risen above a pre-determined threshold for a pre-defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.11 | current | ||
| lgpConditionSource2NeutralOverCurrent OBJECT-IDENTITY The system has detected an over current condition on the neutral line of source 2. The neutral current at source 2 has risen above a pre-determined threshold for a pre-defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.53.12 | current | ||
| lgpConditionSensorFailure OBJECT-IDENTITY This system has detected a sensor failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.54 | current | ||
| lgpConditionOutputToLoadVoltageSensorFailure OBJECT-IDENTITY The system had detected an output to load voltage sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.1 | current | ||
| lgpConditionSource1VoltageSensorFailure OBJECT-IDENTITY The system had detected a source 1 voltage sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.2 | current | ||
| lgpConditionSource2VoltageSensorFailure OBJECT-IDENTITY The system had detected a source 2 voltage sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.3 | current | ||
| lgpConditionSource1ScrSensorFailure OBJECT-IDENTITY The system had detected a source 1 SCR (Silicon Controlled Rectifier) sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.4 | current | ||
| lgpConditionSource2ScrSensorFailure OBJECT-IDENTITY The system had detected a source 2 SCR (Silicon Controlled Rectifier) sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.5 | current | ||
| lgpConditionSource1CurrentSensorFailure OBJECT-IDENTITY The system has detected a source 1 current sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.6 | current | ||
| lgpConditionSource2CurrentSensorFailure OBJECT-IDENTITY The system has detected a source 2 current sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.7 | current | ||
| lgpConditionRoomTempHumiditySensorFailure OBJECT-IDENTITY The system has detected a device temperature and humidity sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.8 | current | ||
| lgpConditionGlycolTempSensorFailure OBJECT-IDENTITY The system has detected a glycol temperature sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.9 | current | ||
| lgpConditionLocal1SensorFailure OBJECT-IDENTITY The system has detected a local 1 sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.10 | current | ||
| lgpConditionCompressor1SensorFailure OBJECT-IDENTITY The system has detected a compressor 1 digital scroll sensor failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.54.11 | current | ||
| lgpConditionCompressor2SensorFailure OBJECT-IDENTITY The system has detected a compressor 2 digital scroll sensor failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.54.12 | current | ||
| lgpConditionSupplySensorFailure OBJECT-IDENTITY The system has detected a supply sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.13 | current | ||
| lgpConditionCabinetTemperatureSensorFailure OBJECT-IDENTITY The system has detected a cabinet temperature sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.14 | current | ||
| lgpConditionCabinetHumiditySensorFailure OBJECT-IDENTITY The system has detected a cabinet humidity sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.15 | current | ||
| lgpConditionRoomTempSensorFailure OBJECT-IDENTITY The system has detected a room temperature sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.16 | current | ||
| lgpConditionBatteryTempSensorFailure OBJECT-IDENTITY The system has detected a battery temperature sensor failure. | 1.3.6.1.4.1.476.1.42.3.2.1.54.17 | current | ||
| lgpConditionAirSensorAFailure OBJECT-IDENTITY The system has detected a failure with air sensor A. The sensor may have been disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.18 | current | ||
| lgpConditionAirSensorBFailure OBJECT-IDENTITY The system has detected a failure with air sensor B. The sensor may have been disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.19 | current | ||
| lgpConditionChilledWaterSupplySensorFailure OBJECT-IDENTITY The system has detected a failure with the chilled water supply sensor. The sensor may have been disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.20 | current | ||
| lgpConditionRefrigerantSupplySensorFailure OBJECT-IDENTITY The system has detected a failure with the refrigerant supply sensor. The sensor may have been disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.21 | current | ||
| lgpConditionFluidSupplySensorFailure OBJECT-IDENTITY The system has detected a failure with the fluid supply sensor. The sensor may have been disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.22 | current | ||
| lgpConditionCompressorLowPressureSensorFailure OBJECT-IDENTITY The system has detected that a compressor low pressure transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.23 | current | ||
| lgpConditionCompressor1LowPressureSensorFailure OBJECT-IDENTITY The system has detected that compressor 1 low pressure transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.23.1 | current | ||
| lgpConditionRemoteSensorFailure OBJECT-IDENTITY The system has detected that a remote sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.24 | current | ||
| lgpConditionAirSupplyTempSensorFailure OBJECT-IDENTITY The system has detected that the supply air temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.25 | current | ||
| lgpConditionAirReturnTempSensorFailure OBJECT-IDENTITY The system has detected that the return air temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.26 | current | ||
| lgpConditionCompressorHighPressureSensorFailure OBJECT-IDENTITY The system has detected that a compressor high pressure transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.27 | current | ||
| lgpConditionCompressor2HighPressureSensorFailure OBJECT-IDENTITY The system has detected that compressor 2 high pressure transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.27.2 | current | ||
| lgpConditionCompressor3HighPressureSensorFailure OBJECT-IDENTITY The system has detected that compressor 3 high pressure transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.27.3 | current | ||
| lgpConditionCompressor4HighPressureSensorFailure OBJECT-IDENTITY The system has detected that compressor 4 high pressure transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.54.27.4 | current | ||
| lgpConditionInternalCommunicationFailure OBJECT-IDENTITY This system has detected an internal communication failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.55 | current | ||
| lgpConditionExternalCommunicationFailure OBJECT-IDENTITY This system has detected an external communication failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.56 | current | ||
| lgpConditionSourceGateDriveFailure OBJECT-IDENTITY This system has detected a source gate drive failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.57 | current | ||
| lgpConditionSource1GateDriveFailure OBJECT-IDENTITY The system has detected a source 1 gate drive failure. | 1.3.6.1.4.1.476.1.42.3.2.1.57.1 | current | ||
| lgpConditionSource2GateDriveFailure OBJECT-IDENTITY The system has detected a source 2 gate drive failure. | 1.3.6.1.4.1.476.1.42.3.2.1.57.2 | current | ||
| lgpConditionDisconnectFailure OBJECT-IDENTITY This system has detected a disconnect failure condition. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.58 | current | ||
| lgpConditionOutputToLoadNeutralDisconnectFailure OBJECT-IDENTITY The system has detected the output to load neutral disconnect has failed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.58.1 | current | ||
| lgpConditionSource1DisconnectShuntTripFailure OBJECT-IDENTITY The system has detected a shunt trip failure of a disconnecting device on source 1. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.58.2 | current | ||
| lgpConditionSource2DisconnectShuntTripFailure OBJECT-IDENTITY The system has detected a shunt trip failure of a disconnecting device on source 2. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.58.3 | current | ||
| lgpConditionInverterDisconnectFailure OBJECT-IDENTITY The system has detected an inverter disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.58.4 | current | ||
| lgpConditionBatteryDisconnectFailure OBJECT-IDENTITY The system has detected a battery disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.58.5 | current | ||
| lgpConditionRectifierDisconnectFailure OBJECT-IDENTITY The system has detected a rectifier disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | 1.3.6.1.4.1.476.1.42.3.2.1.58.6 | current | ||
| lgpConditionOverTemperature OBJECT-IDENTITY This system has detected an over temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.1.59 | current | ||
| lgpConditionHeatSink1OverTemperature OBJECT-IDENTITY The system has detected a heat sink 1 over temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.1.59.1 | current | ||
| lgpConditionAmbient1OverTemperature OBJECT-IDENTITY The system has detected an ambient over temperature condition at location 1. | 1.3.6.1.4.1.476.1.42.3.2.1.59.2 | current | ||
| lgpConditionSystemOverTemperature OBJECT-IDENTITY The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.59.3 | current | ||
| lgpConditionTransformerOverTemperature OBJECT-IDENTITY The transformer is experiencing an over temperature condition. The transformer's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.59.4 | current | ||
| lgpConditionBatteryOverTemperature OBJECT-IDENTITY The battery is experiencing an over temperature condition. The battery's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.59.5 | current | ||
| lgpConditionRectifierOverTemperature OBJECT-IDENTITY The system has detected a rectifier over temperature condition. The rectifier's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.59.6 | current | ||
| lgpConditionInverterOverTemperature OBJECT-IDENTITY The system has detected an inverter over temperature condition. The inverter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.59.7 | current | ||
| lgpConditionRectifierInductorOverTemperature OBJECT-IDENTITY The system has detected a rectifier inductor over temperature condition. The rectifier's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.59.8 | current | ||
| lgpConditionInverterInductorOverTemperature OBJECT-IDENTITY The system has detected an inverter inductor over temperature condition. The inverter's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.59.9 | current | ||
| lgpConditionBatteryConverterOverTemperature OBJECT-IDENTITY The system has detected a battery converter over temperature condition. The battery converter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.59.10 | current | ||
| lgpConditionBatteryBalancerInductorOverTemperature OBJECT-IDENTITY The system has detected a battery balancer Inductor over temperature condition. The battery balancer Inductor's temperature has exceeded a pre-determined threshold for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.59.11 | current | ||
| lgpConditionChilledWaterOverTemperature OBJECT-IDENTITY The system has detected a chilled water over temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.1.59.12 | current | ||
| lgpConditionElectricHeatersOverTemperature OBJECT-IDENTITY The system has detected an electric heater over temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.1.59.13 | current | ||
| lgpConditionInletAirOverTemperature OBJECT-IDENTITY The system has detected an inlet air over temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.1.59.14 | current | ||
| lgpConditionSystemOverTempWarning OBJECT-IDENTITY The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a normal operating range for a device, or system, defined amount of time. The system is still operational but a threshold has been exceeded. | 1.3.6.1.4.1.476.1.42.3.2.1.59.15 | current | ||
| lgpConditionHighTemperatureBattString OBJECT-IDENTITY The system has detected a high temperature on a battery string. The temperature has exceeded a specified temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.59.16 | current | ||
| lgpConditionLoadOnAlternateSource OBJECT-IDENTITY The system has detected that the load is being supplied by the alternate source. | 1.3.6.1.4.1.476.1.42.3.2.1.60 | current | ||
| lgpConditionPhaseRotationError OBJECT-IDENTITY This system has detected a phase rotation error condition. | 1.3.6.1.4.1.476.1.42.3.2.1.61 | current | ||
| lgpConditionSource1PhaseRotationError OBJECT-IDENTITY The system has detected a phase rotation error on source 1. | 1.3.6.1.4.1.476.1.42.3.2.1.61.1 | current | ||
| lgpConditionSource2PhaseRotationError OBJECT-IDENTITY The system has detected a phase rotation error on source 2. | 1.3.6.1.4.1.476.1.42.3.2.1.61.2 | current | ||
| lgpConditionBypassPhaseRotationError OBJECT-IDENTITY The system has detected a phase rotation error on the bypass. | 1.3.6.1.4.1.476.1.42.3.2.1.61.3 | current | ||
| lgpConditionInputPhaseRotationError OBJECT-IDENTITY The system has detected a phase rotation error on the input. | 1.3.6.1.4.1.476.1.42.3.2.1.61.4 | current | ||
| lgpConditionControlModuleFailure OBJECT-IDENTITY This system has detected a control module failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.62 | current | ||
| lgpConditionControlModule1Failure OBJECT-IDENTITY The system has detected a control module 1 failure. | 1.3.6.1.4.1.476.1.42.3.2.1.62.1 | current | ||
| lgpConditionHistoryLogFull OBJECT-IDENTITY The system has detected the history log is full. | 1.3.6.1.4.1.476.1.42.3.2.1.63 | current | ||
| lgpConditionConfigurationModified OBJECT-IDENTITY The system has detected the configuration has been modified. | 1.3.6.1.4.1.476.1.42.3.2.1.64 | current | ||
| lgpConditionPasswordModified OBJECT-IDENTITY The system has detected the password has been modified. | 1.3.6.1.4.1.476.1.42.3.2.1.65 | current | ||
| lgpConditionTimeModified OBJECT-IDENTITY The system has detected the time has been modified. | 1.3.6.1.4.1.476.1.42.3.2.1.66 | current | ||
| lgpConditionDateModified OBJECT-IDENTITY The system has detected the date has been modified. | 1.3.6.1.4.1.476.1.42.3.2.1.67 | current | ||
| lgpConditionEventLogCleared OBJECT-IDENTITY The system has detected the event log has been cleared. | 1.3.6.1.4.1.476.1.42.3.2.1.68 | current | ||
| lgpConditionHistoryLogCleared OBJECT-IDENTITY The system has detected the history log has been cleared. | 1.3.6.1.4.1.476.1.42.3.2.1.69 | current | ||
| lgpConditionUtilityFailure OBJECT-IDENTITY The system has detected a utility failure. | 1.3.6.1.4.1.476.1.42.3.2.1.70 | current | ||
| lgpConditionBatteryTestInProgress OBJECT-IDENTITY The system is performing a battery test at this time. | 1.3.6.1.4.1.476.1.42.3.2.1.71 | current | ||
| lgpConditionLoadOnBattery OBJECT-IDENTITY The system load is being supported by the battery. | 1.3.6.1.4.1.476.1.42.3.2.1.72 | current | ||
| lgpConditionReplaceBattery OBJECT-IDENTITY The system has detected the batteries are due to be replaced. | 1.3.6.1.4.1.476.1.42.3.2.1.74 | current | ||
| lgpConditionUpsShutdownPending OBJECT-IDENTITY The system is in a shutdown pending condition. | 1.3.6.1.4.1.476.1.42.3.2.1.75 | current | ||
| lgpConditionBatteryChargerFailed OBJECT-IDENTITY The system has detected the battery charger has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.76 | current | ||
| lgpConditionBypassVoltageUnqualified OBJECT-IDENTITY The system has detected the bypass voltage is unqualified. The voltage measurement is outside a pre-determined threshold range for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.77 | current | ||
| lgpConditionCheckAirFilter OBJECT-IDENTITY The system has detected it is time to check the air filter. | 1.3.6.1.4.1.476.1.42.3.2.1.78 | current | ||
| lgpConditionBrownOut OBJECT-IDENTITY The system has detected a brown out condition. | 1.3.6.1.4.1.476.1.42.3.2.1.79 | current | ||
| lgpConditionMultipleTransferLockout OBJECT-IDENTITY The system has locked out transfers to bypass. Too many transfers have occurred over a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.80 | current | ||
| lgpConditionBypassPhaseLost OBJECT-IDENTITY The system has detected one or more bypass phases are missing. | 1.3.6.1.4.1.476.1.42.3.2.1.81 | current | ||
| lgpConditionMaintenceBypassInhibited OBJECT-IDENTITY The system is preventing a transfer of the load to maintenance bypass. | 1.3.6.1.4.1.476.1.42.3.2.1.82 | current | ||
| lgpConditionLoadLockedOnBypass OBJECT-IDENTITY An error has been detected requiring the system to be put into a 'locked on bypass' state. | 1.3.6.1.4.1.476.1.42.3.2.1.83 | current | ||
| lgpConditionOutputToLoadShort OBJECT-IDENTITY The system has detected an output to load short circuit condition. | 1.3.6.1.4.1.476.1.42.3.2.1.84 | current | ||
| lgpConditionEmergencyTransferToInverter OBJECT-IDENTITY The system has detected an emergency transfer of the load to inverter. | 1.3.6.1.4.1.476.1.42.3.2.1.85 | current | ||
| lgpConditonEmergencyPowerOff OBJECT-IDENTITY The system has detected an Emergency Power Off (EPO) condition. An external EPO switch has cut off the power source to the system. | 1.3.6.1.4.1.476.1.42.3.2.1.86 | current | ||
| lgpConditionInverterBackFeed OBJECT-IDENTITY The system has detected an inverter back-feed condition. The inverter is feeding power through the bypass back to the input. | 1.3.6.1.4.1.476.1.42.3.2.1.87 | current | ||
| lgpConditionDcGroundFault OBJECT-IDENTITY The system has detected a DC ground fault. | 1.3.6.1.4.1.476.1.42.3.2.1.88 | current | ||
| lgpConditionDcGroundFaultPos OBJECT-IDENTITY Ground fault current has been detected in the positive DC link to ground. | 1.3.6.1.4.1.476.1.42.3.2.1.88.1 | current | ||
| lgpConditionDcGroundFaultNeg OBJECT-IDENTITY Ground fault current has been detected in the negative DC link to ground. | 1.3.6.1.4.1.476.1.42.3.2.1.88.2 | current | ||
| lgpConditionStaticTransferSwitchInhibited OBJECT-IDENTITY The system is preventing the use of the static transfer switch. | 1.3.6.1.4.1.476.1.42.3.2.1.89 | current | ||
| lgpConditionBatteryLogFullWarning OBJECT-IDENTITY The system has detected the battery log is approaching the maximum record limit. | 1.3.6.1.4.1.476.1.42.3.2.1.90 | current | ||
| lgpConditionInputCurrentUnbalanced OBJECT-IDENTITY The system has detected an unbalanced input current condition. The currents of input phases are out of tolerance. | 1.3.6.1.4.1.476.1.42.3.2.1.91 | current | ||
| lgpConditionSelfTestFailed OBJECT-IDENTITY The system has detected a self-test failure. | 1.3.6.1.4.1.476.1.42.3.2.1.92 | current | ||
| lgpConditionInverterOutOfSynchronization OBJECT-IDENTITY The system has detected an Inverter out of sync condition. | 1.3.6.1.4.1.476.1.42.3.2.1.93 | current | ||
| lgpConditionModuleAlarm OBJECT-IDENTITY This system has detected an alarm within the multi-module system. | 1.3.6.1.4.1.476.1.42.3.2.1.94 | current | ||
| lgpConditioniModuleUnit1Alarm OBJECT-IDENTITY The multi-module system has detected an alarm condition on unit 1. | 1.3.6.1.4.1.476.1.42.3.2.1.94.1 | current | ||
| lgpConditioniModuleUnit2Alarm OBJECT-IDENTITY The multi-module system has detected an alarm condition on unit 2. | 1.3.6.1.4.1.476.1.42.3.2.1.94.2 | current | ||
| lgpConditioniModuleUnit3Alarm OBJECT-IDENTITY The multi-module system has detected an alarm condition on unit 3. | 1.3.6.1.4.1.476.1.42.3.2.1.94.3 | current | ||
| lgpConditioniModuleUnit4Alarm OBJECT-IDENTITY The multi-module system has detected an alarm condition on unit 4. | 1.3.6.1.4.1.476.1.42.3.2.1.94.4 | current | ||
| lgpConditioniModuleUnit5Alarm OBJECT-IDENTITY The multi-module system has detected an alarm condition on unit 5. | 1.3.6.1.4.1.476.1.42.3.2.1.94.5 | current | ||
| lgpConditioniModuleUnit6Alarm OBJECT-IDENTITY The multi-module system has detected an alarm condition on unit 6. | 1.3.6.1.4.1.476.1.42.3.2.1.94.6 | current | ||
| lgpConditioniModuleUnit7Alarm OBJECT-IDENTITY The multi-module system has detected an alarm condition on unit 7. | 1.3.6.1.4.1.476.1.42.3.2.1.94.7 | current | ||
| lgpConditioniModuleUnit8Alarm OBJECT-IDENTITY The multi-module system has detected an alarm condition on unit 8. | 1.3.6.1.4.1.476.1.42.3.2.1.94.8 | current | ||
| lgpConditionActiveModuleAlarm OBJECT-IDENTITY The system has detected an active alarm in one, or more, of the sub-modules of the multi-module system. | 1.3.6.1.4.1.476.1.42.3.2.1.95 | current | ||
| lgpConditionControlFailure OBJECT-IDENTITY This system has detected a control failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.96 | current | ||
| lgpConditionMainControlFailure OBJECT-IDENTITY The system has detected a main control failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.96.1 | current | ||
| lgpConditionRedundantControlFailure OBJECT-IDENTITY The system has detected a redundant control failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.96.2 | current | ||
| lgpConditionParallelSysControlFailure OBJECT-IDENTITY The parallel system has detected a control failure condition with one of the controls. | 1.3.6.1.4.1.476.1.42.3.2.1.96.3 | current | ||
| lgpConditionMainControlCommFailure OBJECT-IDENTITY One or more communications failures have occurred in the main control. | 1.3.6.1.4.1.476.1.42.3.2.1.96.4 | current | ||
| lgpConditionControlBoardFailure OBJECT-IDENTITY The system has detected a control board failure. | 1.3.6.1.4.1.476.1.42.3.2.1.96.5 | current | ||
| lgpConditionHumidifierControlBdFailure OBJECT-IDENTITY Humidifier control board is required to be connected, but no signal is detected. | 1.3.6.1.4.1.476.1.42.3.2.1.96.5.1 | current | ||
| lgpConditionControlWarning OBJECT-IDENTITY This system has detected a control warning conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.97 | current | ||
| lgpConditionMainControlWarning OBJECT-IDENTITY The system has detected a main control warning condition. | 1.3.6.1.4.1.476.1.42.3.2.1.97.1 | current | ||
| lgpConditionRedundantControlWarning OBJECT-IDENTITY The system has detected a redundant control warning condition. | 1.3.6.1.4.1.476.1.42.3.2.1.97.2 | current | ||
| lgpConditionUserInterfaceFailure OBJECT-IDENTITY The system has detected a user interface control failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.98 | current | ||
| lgpConditionLostPowerRedundancy OBJECT-IDENTITY The system has detected the number of redundant power modules has fallen below the minimum redundant power module setting. | 1.3.6.1.4.1.476.1.42.3.2.1.99 | current | ||
| lgpConditionPowerModuleFailure OBJECT-IDENTITY The system has detected a power module failure condition in the system. | 1.3.6.1.4.1.476.1.42.3.2.1.100 | current | ||
| lgpConditionBatteryModuleFailure OBJECT-IDENTITY The system has detected a battery module failure condition in the system. | 1.3.6.1.4.1.476.1.42.3.2.1.101 | current | ||
| lgpConditionOutputToLoadOff OBJECT-IDENTITY The system has detected that there is no power being supplied to the load. | 1.3.6.1.4.1.476.1.42.3.2.1.102 | current | ||
| lgpConditionSystemOff OBJECT-IDENTITY The system is off. | 1.3.6.1.4.1.476.1.42.3.2.1.103 | current | ||
| lgpConditionRectifierStartupFailure OBJECT-IDENTITY The system has detected a rectifier under voltage start-up failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.104 | current | ||
| lgpConditionRectifierFault OBJECT-IDENTITY The system has detected a rectifier fault condition. | 1.3.6.1.4.1.476.1.42.3.2.1.105 | current | ||
| lgpConditionInverterShutdownLowDc OBJECT-IDENTITY The system has shutdown the inverter due to a DC bus under voltage. | 1.3.6.1.4.1.476.1.42.3.2.1.106 | current | ||
| lgpConditionInverterFault OBJECT-IDENTITY The system has detected an inverter fault condition. | 1.3.6.1.4.1.476.1.42.3.2.1.107 | current | ||
| lgpConditionInverterDcOffsetOverrun OBJECT-IDENTITY The system has detected an over run of the inverter DC offset voltage. | 1.3.6.1.4.1.476.1.42.3.2.1.108 | current | ||
| lgpConditionParallelSysLowBatteryWarning OBJECT-IDENTITY The parallel system has detected a low battery warning condition. | 1.3.6.1.4.1.476.1.42.3.2.1.109 | current | ||
| lgpConditionParallelSysLoadShareFault OBJECT-IDENTITY The parallel system has detected a load share fault condition. | 1.3.6.1.4.1.476.1.42.3.2.1.110 | current | ||
| lgpConditionBatteryFault OBJECT-IDENTITY The system has detected a battery fault condition. The battery conductors are either reversed or disconnected. | 1.3.6.1.4.1.476.1.42.3.2.1.111 | current | ||
| lgpConditionBatteryConverterFailure OBJECT-IDENTITY The system has detected a battery converter failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.112 | current | ||
| lgpConditionBatteryBalancerFault OBJECT-IDENTITY The system has detected a battery balancer fault condition. | 1.3.6.1.4.1.476.1.42.3.2.1.113 | current | ||
| lgpConditionpsUpsOperationFault OBJECT-IDENTITY The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence. | 1.3.6.1.4.1.476.1.42.3.2.1.114 | deprecated | ||
| lgpConditionOutputToLoadOnJointMode OBJECT-IDENTITY The system load is being supported by both the battery and rectifier. | 1.3.6.1.4.1.476.1.42.3.2.1.115 | current | ||
| lgpConditionInputNeutralLost OBJECT-IDENTITY The system had detected the main input neutral is disconnected. | 1.3.6.1.4.1.476.1.42.3.2.1.116 | current | ||
| lgpConditionLowBatteryWarning OBJECT-IDENTITY The battery's remaining charge is less than or equal to the configured low threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.117 | current | ||
| lgpConditionInternalFault OBJECT-IDENTITY The system has detected an internal fault. | 1.3.6.1.4.1.476.1.42.3.2.1.118 | current | ||
| lgpConditionBatteryTestFailed OBJECT-IDENTITY The system has detected a battery self-test failure. | 1.3.6.1.4.1.476.1.42.3.2.1.119 | current | ||
| lgpConditionPowerModuleWarning OBJECT-IDENTITY The system has detected an alarm condition on one, or more, power modules. | 1.3.6.1.4.1.476.1.42.3.2.1.120 | current | ||
| lgpConditionBatteryModuleWarning OBJECT-IDENTITY The system has detected an alarm condition on one, or more, battery modules. | 1.3.6.1.4.1.476.1.42.3.2.1.121 | current | ||
| lgpConditionControlModuleWarning OBJECT-IDENTITY The system has detected a control module warning. | 1.3.6.1.4.1.476.1.42.3.2.1.122 | current | ||
| lgpConditionUpsOperationFault OBJECT-IDENTITY The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence. | 1.3.6.1.4.1.476.1.42.3.2.1.123 | current | ||
| lgpConditionActiveAlarm OBJECT-IDENTITY The system has detected an alarm condition. | 1.3.6.1.4.1.476.1.42.3.2.1.124 | current | ||
| lgpConditionRectifierCommunicationFailure OBJECT-IDENTITY The system has detected an internal communication failure condition with the rectifier. | 1.3.6.1.4.1.476.1.42.3.2.1.125 | current | ||
| lgpConditionInverterCommunicationFailure OBJECT-IDENTITY The system has detected an internal communication failure condition with the inverter. | 1.3.6.1.4.1.476.1.42.3.2.1.126 | current | ||
| lgpConditionParallelSysConnectionFault OBJECT-IDENTITY The parallel system has detected a connection fault. One or more of the devices are not properly connected. | 1.3.6.1.4.1.476.1.42.3.2.1.127 | current | ||
| lgpConditionParallelSysCommunicationFailure OBJECT-IDENTITY The parallel system has detected a communication failure. | 1.3.6.1.4.1.476.1.42.3.2.1.128 | current | ||
| lgpConditionLostBatteryRedundancy OBJECT-IDENTITY The system has detected the number of redundant battery modules has fallen below the configured redundant battery module threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.129 | current | ||
| lgpConditionCompPumpDownFailure OBJECT-IDENTITY The system has detected that a compressor has failed to pump down. | 1.3.6.1.4.1.476.1.42.3.2.1.130 | current | ||
| lgpConditionComp1PumpDownFailure OBJECT-IDENTITY The system has detected that compressor 1 has failed to pump down. | 1.3.6.1.4.1.476.1.42.3.2.1.130.1 | current | ||
| lgpConditionComp2PumpDownFailure OBJECT-IDENTITY The system has detected that compressor 2 has failed to pump down. | 1.3.6.1.4.1.476.1.42.3.2.1.130.2 | current | ||
| lgpConditionComp3PumpDownFailure OBJECT-IDENTITY The system has detected that compressor 3 has failed to pump down. | 1.3.6.1.4.1.476.1.42.3.2.1.130.3 | current | ||
| lgpConditionComp4PumpDownFailure OBJECT-IDENTITY The system has detected that compressor 4 has failed to pump down. | 1.3.6.1.4.1.476.1.42.3.2.1.130.4 | current | ||
| lgpConditionChilledWaterLowWaterFlow OBJECT-IDENTITY The system has detected a chilled water low water flow condition. | 1.3.6.1.4.1.476.1.42.3.2.1.131 | current | ||
| lgpConditionChilledWaterLowWaterFlowCircuit2 OBJECT-IDENTITY The system has detected a chilled water low water flow condition for circuit 2. | 1.3.6.1.4.1.476.1.42.3.2.1.131.2 | current | ||
| lgpConditionAirFilterClogged OBJECT-IDENTITY The system has detected a air filter clogged condition. | 1.3.6.1.4.1.476.1.42.3.2.1.132 | deprecated | ||
| lgpConditionHumidifierFailure OBJECT-IDENTITY The system has detected a humidifier failure condition. | 1.3.6.1.4.1.476.1.42.3.2.1.133 | current | ||
| lgpConditionRunHoursExceeded OBJECT-IDENTITY The system has detected a pre-determined run hours threshold has been exceeded. | 1.3.6.1.4.1.476.1.42.3.2.1.134 | current | ||
| lgpConditionUnitRunHrsExceeded OBJECT-IDENTITY The system has detected the system run hours has exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.1 | current | ||
| lgpConditionComp1RunHrsExceeded OBJECT-IDENTITY The system has detected the compressor 1 run hours has exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.2 | current | ||
| lgpConditionComp2RunHrsExceeded OBJECT-IDENTITY The system has detected the compressor 2 run hours has exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.3 | current | ||
| lgpConditionFreeCoolRunHrsExceeded OBJECT-IDENTITY The system has detected the free cooling run hours has exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.4 | current | ||
| lgpConditionElectricalHeater1RunHrsExceeded OBJECT-IDENTITY The system has detected the electrical heater's run hours have exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.5 | current | ||
| lgpConditionElectricalHeater2RunHrsExceeded OBJECT-IDENTITY The system has detected the electrical heater's run hours have exceeded the pre-determined limit. | 1.3.6.1.4.1.476.1.42.3.2.1.134.6 | current | ||
| lgpConditionElectricalHeater3RunHrsExceeded OBJECT-IDENTITY The system has detected the electrical heater's run hours have exceeded the pre-determined limit. | 1.3.6.1.4.1.476.1.42.3.2.1.134.7 | current | ||
| lgpConditionHotWaterRunHrsExceeded OBJECT-IDENTITY The system has detected the hot water run hours have exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.8 | current | ||
| lgpConditionHotGasRunHrsExceeded OBJECT-IDENTITY The system has detected the hot gas run hours have exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.9 | current | ||
| lgpConditionHumidifierRunHrsExceeded OBJECT-IDENTITY The system has detected the humidifier run hours have exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.10 | current | ||
| lgpConditionDehumidiferRunHrsExceeded OBJECT-IDENTITY The system has detected the dehumidifier run hours have exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.11 | current | ||
| lgpConditionFanRunHrsExceeded OBJECT-IDENTITY The system has detected the unit blower fan run hours have exceeded the pre-determined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.134.12 | current | ||
| lgpConditionCommWarning OBJECT-IDENTITY The system has detected a loss of communications with another module. | 1.3.6.1.4.1.476.1.42.3.2.1.135 | current | ||
| lgpConditionCommWarningUnit1 OBJECT-IDENTITY The system has detected a loss of communications with unit 1. | 1.3.6.1.4.1.476.1.42.3.2.1.135.1 | current | ||
| lgpConditionCommWarningUnit2 OBJECT-IDENTITY The system has detected a loss of communications with unit 2. | 1.3.6.1.4.1.476.1.42.3.2.1.135.2 | current | ||
| lgpConditionCommWarningUnit3 OBJECT-IDENTITY The system has detected a loss of communications with unit 3. | 1.3.6.1.4.1.476.1.42.3.2.1.135.3 | current | ||
| lgpConditionCommWarningUnit4 OBJECT-IDENTITY The system has detected a loss of communications with unit 4. | 1.3.6.1.4.1.476.1.42.3.2.1.135.4 | current | ||
| lgpConditionCommWarningUnit5 OBJECT-IDENTITY The system has detected a loss of communications with unit 5. | 1.3.6.1.4.1.476.1.42.3.2.1.135.5 | current | ||
| lgpConditionCommWarningUnit6 OBJECT-IDENTITY The system has detected a loss of communications with unit 6. | 1.3.6.1.4.1.476.1.42.3.2.1.135.6 | current | ||
| lgpConditionCommWarningUnit7 OBJECT-IDENTITY The system has detected a loss of communications with unit 7. | 1.3.6.1.4.1.476.1.42.3.2.1.135.7 | current | ||
| lgpConditionCommWarningUnit8 OBJECT-IDENTITY The system has detected a loss of communications with unit 8. | 1.3.6.1.4.1.476.1.42.3.2.1.135.8 | current | ||
| lgpConditionCommWarningUnit9 OBJECT-IDENTITY The system has detected a loss of communications with unit 9. | 1.3.6.1.4.1.476.1.42.3.2.1.135.9 | current | ||
| lgpConditionCommWarningUnit10 OBJECT-IDENTITY The system has detected a loss of communications with unit 10. | 1.3.6.1.4.1.476.1.42.3.2.1.135.10 | current | ||
| lgpConditionCommWarningUnit11 OBJECT-IDENTITY The system has detected a loss of communications with unit 11. | 1.3.6.1.4.1.476.1.42.3.2.1.135.11 | current | ||
| lgpConditionCommWarningUnit12 OBJECT-IDENTITY The system has detected a loss of communications with unit 12. | 1.3.6.1.4.1.476.1.42.3.2.1.135.12 | current | ||
| lgpConditionCommWarningUnit13 OBJECT-IDENTITY The system has detected a loss of communications with unit 13. | 1.3.6.1.4.1.476.1.42.3.2.1.135.13 | current | ||
| lgpConditionCommWarningUnit14 OBJECT-IDENTITY The system has detected a loss of communications with unit 14. | 1.3.6.1.4.1.476.1.42.3.2.1.135.14 | current | ||
| lgpConditionCommWarningUnit15 OBJECT-IDENTITY The system has detected a loss of communications with unit 15. | 1.3.6.1.4.1.476.1.42.3.2.1.135.15 | current | ||
| lgpConditionCommWarningUnit16 OBJECT-IDENTITY The system has detected a loss of communications with unit 16. | 1.3.6.1.4.1.476.1.42.3.2.1.135.16 | current | ||
| lgpConditionUnitOn OBJECT-IDENTITY The unit is on. | 1.3.6.1.4.1.476.1.42.3.2.1.136 | current | ||
| lgpConditionUnitOff OBJECT-IDENTITY The unit is off. | 1.3.6.1.4.1.476.1.42.3.2.1.137 | current | ||
| lgpConditionSleepModeOff OBJECT-IDENTITY The system sleep mode operation has been turned off. | 1.3.6.1.4.1.476.1.42.3.2.1.138 | current | ||
| lgpConditionPowerOn OBJECT-IDENTITY The system power is on. | 1.3.6.1.4.1.476.1.42.3.2.1.139 | current | ||
| lgpConditionSystemOnStanby OBJECT-IDENTITY The system is on standby. | 1.3.6.1.4.1.476.1.42.3.2.1.140 | current | ||
| lgpConditionPowerOff OBJECT-IDENTITY The system power is off. | 1.3.6.1.4.1.476.1.42.3.2.1.141 | current | ||
| lgpConditionHighTemperatureGroup OBJECT-IDENTITY The system has detected a high temperature condition. This group contains various high temperature conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.142 | current | ||
| lgpConditionHighTemperatureSensor1 OBJECT-IDENTITY The temperature has exceeded the high temperature threshold for sensor 1. | 1.3.6.1.4.1.476.1.42.3.2.1.142.1 | current | ||
| lgpConditionHighTemperatureDigitalScroll1 OBJECT-IDENTITY The system has detected a high temperature event on Digital Scroll Compressor 1. The temperature has exceeded a specified temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.142.2 | current | ||
| lgpConditionHighTemperatureDigitalScroll2 OBJECT-IDENTITY The system has detected a high temperature event on Digital Scroll Compressor 2. The temperature has exceeded a specified temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.142.3 | current | ||
| lgpConditionHighTemperatureUser1 OBJECT-IDENTITY The temperature has exceeded the high temperature threshold for user configured temperature sensor 1. | 1.3.6.1.4.1.476.1.42.3.2.1.142.4 | current | ||
| lgpConditionHighTemperatureInternal OBJECT-IDENTITY The system has detected a high internal temperature condition. The temperature has exceeded a specified temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.142.5 | current | ||
| lgpConditionHighTemperatureExternalAirSensorA OBJECT-IDENTITY The temperature has exceeded the high temperature threshold for external air sensor A. | 1.3.6.1.4.1.476.1.42.3.2.1.142.6 | current | ||
| lgpConditionHighTemperatureExternalAirSensorB OBJECT-IDENTITY The temperature has exceeded the high temperature threshold for external air sensor B. | 1.3.6.1.4.1.476.1.42.3.2.1.142.7 | current | ||
| lgpConditionHighTemperatureRefrigerantSupply OBJECT-IDENTITY The temperature has exceeded the high temperature threshold for the refrigerant supply. | 1.3.6.1.4.1.476.1.42.3.2.1.142.8 | current | ||
| lgpConditionHighTemperatureFluidSupply OBJECT-IDENTITY The temperature has exceeded the high temperature threshold for the fluid supply. | 1.3.6.1.4.1.476.1.42.3.2.1.142.9 | current | ||
| lgpConditionHighTemperatureSupplyAir OBJECT-IDENTITY The temperature has exceeded the high temperature threshold for the supply air. | 1.3.6.1.4.1.476.1.42.3.2.1.142.10 | current | ||
| lgpConditionHighTemperatureReturnAir OBJECT-IDENTITY The temperature has exceeded the high temperature threshold for the return air. | 1.3.6.1.4.1.476.1.42.3.2.1.142.11 | current | ||
| lgpConditionLowTemperatureGroup OBJECT-IDENTITY The system has detected a low temperature condition. This group contains various low temperature conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.143 | current | ||
| lgpConditionLowTemperatureSensor1 OBJECT-IDENTITY The temperature is below the low temperature threshold for sensor 1. | 1.3.6.1.4.1.476.1.42.3.2.1.143.1 | current | ||
| lgpConditionLowTemperatureInternal OBJECT-IDENTITY The system has detected a low internal temperature condition. The temperature is below a specified temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.143.2 | current | ||
| lgpConditionLowTemperatureExternalAirSensorA OBJECT-IDENTITY The temperature is below the low temperature threshold for external air sensor A. | 1.3.6.1.4.1.476.1.42.3.2.1.143.3 | current | ||
| lgpConditionLowTemperatureExternalAirSensorB OBJECT-IDENTITY The temperature is below the low temperature threshold for external air sensor B. | 1.3.6.1.4.1.476.1.42.3.2.1.143.4 | current | ||
| lgpConditionLowTemperatureRefrigerantSupply OBJECT-IDENTITY The temperature is below the low temperature threshold for the refrigerant supply. | 1.3.6.1.4.1.476.1.42.3.2.1.143.5 | current | ||
| lgpConditionLowTemperatureFluidSupply OBJECT-IDENTITY The temperature is below the low temperature threshold for the fluid supply. | 1.3.6.1.4.1.476.1.42.3.2.1.143.6 | current | ||
| lgpConditionLowTemperatureSupplyAir OBJECT-IDENTITY The temperature is below the low temperature threshold for the supply air. | 1.3.6.1.4.1.476.1.42.3.2.1.143.7 | current | ||
| lgpConditionHighHumidityGroup OBJECT-IDENTITY The system has detected a high humidity condition. This group contains various high humidity conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.144 | current | ||
| lgpConditionHighHumiditySensor1 OBJECT-IDENTITY The humidity has exceeded the high humidity threshold for sensor 1. | 1.3.6.1.4.1.476.1.42.3.2.1.144.1 | current | ||
| lgpConditionHighHumidityReturnAir OBJECT-IDENTITY The humidity has exceeded the high humidity threshold for the return air. | 1.3.6.1.4.1.476.1.42.3.2.1.144.2 | current | ||
| lgpConditionLowHumidityGroup OBJECT-IDENTITY The system has detected a low humidity condition. This group contains various high humidity conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.145 | current | ||
| lgpConditionLowHumiditySensor1 OBJECT-IDENTITY The humidity is below the low humidity threshold for sensor 1. | 1.3.6.1.4.1.476.1.42.3.2.1.145.1 | current | ||
| lgpConditionLowHumidityReturnAir OBJECT-IDENTITY The humidity is below the low humidity threshold for the return air. | 1.3.6.1.4.1.476.1.42.3.2.1.145.2 | current | ||
| lgpConditionPeerNetworkNoMaster OBJECT-IDENTITY The system is unable to communicate with the master on the peer to peer network. | 1.3.6.1.4.1.476.1.42.3.2.1.146 | current | ||
| lgpConditionNoOnOffPermissions OBJECT-IDENTITY The system lacks the permissions to execute the on/off operation. | 1.3.6.1.4.1.476.1.42.3.2.1.147 | current | ||
| lgpConditionPeerNetworkFailure OBJECT-IDENTITY The system has detected a communication failure on the peer to peer network. | 1.3.6.1.4.1.476.1.42.3.2.1.148 | current | ||
| lgpConditionUnitDisabled OBJECT-IDENTITY The unit is disabled. | 1.3.6.1.4.1.476.1.42.3.2.1.149 | current | ||
| lgpConditionUnitShutdown OBJECT-IDENTITY The system has shutdown. | 1.3.6.1.4.1.476.1.42.3.2.1.150 | current | ||
| lgpConditionPeerNetworkDiscovered OBJECT-IDENTITY The system has established communications on the peer to peer network. | 1.3.6.1.4.1.476.1.42.3.2.1.151 | current | ||
| lgpConditionLossOfWaterFlow OBJECT-IDENTITY The system has detected a loss of water flow condition. | 1.3.6.1.4.1.476.1.42.3.2.1.152 | current | ||
| lgpConditionCondensatePumpHighWater OBJECT-IDENTITY The system has detected high water in the condensate pump. | 1.3.6.1.4.1.476.1.42.3.2.1.153 | current | ||
| lgpConditionGeneralAlarm OBJECT-IDENTITY The system has detected a general alarm condition. | 1.3.6.1.4.1.476.1.42.3.2.1.154 | current | ||
| lgpConditionProductSpecific OBJECT-IDENTITY The system has detected a product specific condition. This condition is not currently available via the agent card. | 1.3.6.1.4.1.476.1.42.3.2.1.155 | current | ||
| lgpConditionReheatLockout OBJECT-IDENTITY The system has locked out the electrical reheat operation for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.156 | current | ||
| lgpConditionHumidifierLockout OBJECT-IDENTITY The system has locked out the humidifier operation for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.157 | current | ||
| lgpConditionCompressorsLockout OBJECT-IDENTITY The system has locked out compressor operation for a specified amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.158 | current | ||
| lgpConditionCallService OBJECT-IDENTITY The system has detected a condition that requires a service representative be contacted. | 1.3.6.1.4.1.476.1.42.3.2.1.159 | current | ||
| lgpConditionLowMemoryGroup OBJECT-IDENTITY This group contains various low memory conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.160 | current | ||
| lgpConditionLowMemory1 OBJECT-IDENTITY The system has detected a low memory condition. The control board is low in memory resources. | 1.3.6.1.4.1.476.1.42.3.2.1.160.1 | current | ||
| lgpConditionMemoryFailureGroup OBJECT-IDENTITY This group contains various memory device failure conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.161 | current | ||
| lgpConditionMemory1Failure OBJECT-IDENTITY The system has detected a memory 1 module failure. | 1.3.6.1.4.1.476.1.42.3.2.1.161.1 | current | ||
| lgpConditionMemory2Failure OBJECT-IDENTITY The system has detected a memory 2 module failure. | 1.3.6.1.4.1.476.1.42.3.2.1.161.2 | current | ||
| lgpConditionUnitCodeErrorGroup OBJECT-IDENTITY This group contains various memory device failure conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.162 | current | ||
| lgpConditionUnitCodeNotConfigured OBJECT-IDENTITY The system has detected the unit code is not configured. The unit code must be configured before system start-up. | 1.3.6.1.4.1.476.1.42.3.2.1.162.1 | current | ||
| lgpConditionUnitCode01OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.2 | current | ||
| lgpConditionUnitCode02OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.3 | current | ||
| lgpConditionUnitCode03OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.4 | current | ||
| lgpConditionUnitCode04OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.5 | current | ||
| lgpConditionUnitCode05OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.6 | current | ||
| lgpConditionUnitCode06OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.7 | current | ||
| lgpConditionUnitCode07OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.8 | current | ||
| lgpConditionUnitCode08OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.9 | current | ||
| lgpConditionUnitCode09OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.10 | current | ||
| lgpConditionUnitCode10OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.11 | current | ||
| lgpConditionUnitCode11OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.12 | current | ||
| lgpConditionUnitCode12OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.13 | current | ||
| lgpConditionUnitCode13OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.14 | current | ||
| lgpConditionUnitCode14OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.15 | current | ||
| lgpConditionUnitCode15OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.16 | current | ||
| lgpConditionUnitCode16OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.17 | current | ||
| lgpConditionUnitCode17OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.18 | current | ||
| lgpConditionUnitCode18OutOfRange OBJECT-IDENTITY The system has detected a unit code error. This digit of the unit code value is out of range. | 1.3.6.1.4.1.476.1.42.3.2.1.162.19 | current | ||
| lgpConditionHighExternalDewPoint OBJECT-IDENTITY The system has detected a high external dew point condition. The room dew point has exceeded the specified threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.163 | current | ||
| lgpConditionHcbDisconnected OBJECT-IDENTITY The system has detected the humidifier control board is disconnected or not installed. | 1.3.6.1.4.1.476.1.42.3.2.1.164 | current | ||
| lgpConditionBmsResetTimerExpired OBJECT-IDENTITY The BMS fan speed control reset counter has timed out. | 1.3.6.1.4.1.476.1.42.3.2.1.165 | current | ||
| lgpConditionAgentFirmwareCorrupt OBJECT-IDENTITY The firmware update to the agent card has failed and the firmware is now corrupt. | 1.3.6.1.4.1.476.1.42.3.2.1.166 | current | ||
| lgpConditionSystemAccessGroup OBJECT-IDENTITY This group contains various system access conditions. An examples is an open access panel. | 1.3.6.1.4.1.476.1.42.3.2.1.175 | current | ||
| lgpConditionFrontAccessOpen OBJECT-IDENTITY The system has detected the front access panel/door is open. | 1.3.6.1.4.1.476.1.42.3.2.1.175.1 | current | ||
| lgpConditionRearAccessOpen OBJECT-IDENTITY The system has detected the rear access panel/door is open. | 1.3.6.1.4.1.476.1.42.3.2.1.175.2 | current | ||
| lgpConditionsDamperFailure OBJECT-IDENTITY This group contains various damper failure conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.176 | current | ||
| lgpConditionEmergencyDamperFailure OBJECT-IDENTITY The system has detected an emergency damper failure. The damper is in the wrong position. | 1.3.6.1.4.1.476.1.42.3.2.1.176.1 | current | ||
| lgpConditionRemoteShutdown OBJECT-IDENTITY A remote shutdown occurred. | 1.3.6.1.4.1.476.1.42.3.2.1.177 | current | ||
| lgpConditionFireAlarm OBJECT-IDENTITY Fire Alarm. | 1.3.6.1.4.1.476.1.42.3.2.1.178 | current | ||
| lgpConditionHeatersOverheated OBJECT-IDENTITY Heaters Overheated. | 1.3.6.1.4.1.476.1.42.3.2.1.179 | current | ||
| lgpConditionCondenserFailureGroup OBJECT-IDENTITY This group contains condenser failure conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.180 | current | ||
| lgpConditionCondenser1Failure OBJECT-IDENTITY Condenser 1 Failure. | 1.3.6.1.4.1.476.1.42.3.2.1.180.1 | current | ||
| lgpConditionCondenser2Failure OBJECT-IDENTITY Condenser 2 Failure. | 1.3.6.1.4.1.476.1.42.3.2.1.180.2 | current | ||
| lgpConditionCondenserTVSSFailure OBJECT-IDENTITY The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.180.3 | current | ||
| lgpConditionHumidifierCyclinderWorn OBJECT-IDENTITY The system has detected the humidifier cylinder is worn. | 1.3.6.1.4.1.476.1.42.3.2.1.181 | current | ||
| lgpConditionUnderCurrent OBJECT-IDENTITY The system has detected a low current condition. The current of one or more sources in the system has fallen below a threshold for a specified amount of time. The threshold and time that triggered this condition is system dependent. | 1.3.6.1.4.1.476.1.42.3.2.1.182 | current | ||
| lgpConditionHumidifierUnderCurrent OBJECT-IDENTITY The system has detected a low current condition on the humidifier. The current of the humidifier has fallen below a pre-determined threshold for a defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.182.1 | current | ||
| lgpConditionInputUnderCurrent OBJECT-IDENTITY There is a low current condition on the input power source. The current of the input power source has fallen below a pre-determined threshold for a defined amount of time. | 1.3.6.1.4.1.476.1.42.3.2.1.182.2 | current | ||
| lgpConditionHeatRejectorGroup OBJECT-IDENTITY This group contains failure conditions for the heat rejection unit. | 1.3.6.1.4.1.476.1.42.3.2.1.183 | current | ||
| lgpConditionHeatRejectorFanFailure OBJECT-IDENTITY The heat rejecter fan has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.183.1 | current | ||
| lgpConditionHeatRejectorVoltageSuppressionFailure OBJECT-IDENTITY The heat rejecter voltage suppression has failed and is no longer able to protect the unit from power fluctuations. | 1.3.6.1.4.1.476.1.42.3.2.1.183.2 | current | ||
| lgpConditionFreeCoolLockout OBJECT-IDENTITY The free cooling capability has been disabled. | 1.3.6.1.4.1.476.1.42.3.2.1.184 | current | ||
| lgpConditionWaterLeakSensorFailure OBJECT-IDENTITY The sensor used to detect water leaks is not connected or has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.185 | current | ||
| lgpConditionNoLoadDetectedWarning OBJECT-IDENTITY There is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been left on external bypass. This warning is triggered after a delay. The delay is specified by the object 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output current falls below a certain threshold specified by the object 'lgpPwrNoLoadWarningLimit' | 1.3.6.1.4.1.476.1.42.3.2.1.186 | current | ||
| lgpConditionFirmwareGroup OBJECT-IDENTITY Grouping level for firmware related conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.187 | current | ||
| lgpConditionFirmwareUpdateRequired OBJECT-IDENTITY The firmware on the system or one or more components of the system must be updated. This typically indicates that one or more components of the system contain corrupted firmware or the firmware on one or more components are incompatible with one another. When this condition is active the system may not be able to function to its full capacity or may not be able to function at all. | 1.3.6.1.4.1.476.1.42.3.2.1.187.3 | current | ||
| lgpConditionTestGroup OBJECT-IDENTITY Objects in this group of conditions are related to testing or test events. This object is never active. | 1.3.6.1.4.1.476.1.42.3.2.1.188 | current | ||
| lgpConditionTest01 OBJECT-IDENTITY This is a 'test' condition. It is a generic test event that can be utilized to evaluate system handling of events. Some products will support the activation of this event upon user request so that user management stations can execute end-to-end event handling tests. | 1.3.6.1.4.1.476.1.42.3.2.1.188.5 | current | ||
| lgpConditionReceptacleBranchGroup OBJECT-IDENTITY Grouping level for receptacle branch conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.190 | current | ||
| lgpConditionRcpBranchFailure OBJECT-IDENTITY The receptacle branch module or control system has failed. Service is required. | 1.3.6.1.4.1.476.1.42.3.2.1.190.5 | current | ||
| lgpConditionRcpBranchBreakerOpen OBJECT-IDENTITY The receptacle branch breaker is open. | 1.3.6.1.4.1.476.1.42.3.2.1.190.10 | current | ||
| lgpConditionInputUnqualified OBJECT-IDENTITY The input is not qualified to provide power to the system. This may be due to system input over-voltage, system input under-voltage, system input frequency out of range, or other similar issues. | 1.3.6.1.4.1.476.1.42.3.2.1.192 | current | ||
| lgpConditionBypassUnavailable OBJECT-IDENTITY This summary event is asserted when the bypass is not available. Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass Overvoltage, Bypass Undervoltage, Bypass Phase Rotation Error, or other similar causes. | 1.3.6.1.4.1.476.1.42.3.2.1.193 | current | ||
| lgpConditionAutoTransferFailed OBJECT-IDENTITY The system is failing to automatically transfer the load to the alternate source. | 1.3.6.1.4.1.476.1.42.3.2.1.194 | current | ||
| lgpConditionSBSUnavailable OBJECT-IDENTITY A Static Bypass Switch (SBS) Failure has been detected. Possible causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier) Shorted, SBS Overload Exceeded, Bypass Power Supply Fail, Static Bypass Switch Fuse Failure, or other similar causes. | 1.3.6.1.4.1.476.1.42.3.2.1.195 | current | ||
| lgpConditionSBSOverload OBJECT-IDENTITY On at least one phase of the static bypass switch (SBS), the power dissipation limit has been exceeded. | 1.3.6.1.4.1.476.1.42.3.2.1.196 | current | ||
| lgpConditionExcessPulseParallel OBJECT-IDENTITY The system has performed too many pulse parallel operations within the specified time interval. A pulse parallel operation is a momentary operation of the static bypass switch (SBS) in parallel with the inverter. | 1.3.6.1.4.1.476.1.42.3.2.1.197 | current | ||
| lgpConditionRemoteBypassSwitchOffExt OBJECT-IDENTITY The static bypass switch is off due to the state of an external signal. | 1.3.6.1.4.1.476.1.42.3.2.1.198 | current | ||
| lgpConditionManTransferInhibited OBJECT-IDENTITY Manual transfer from inverter to bypass is inhibited. Bypass is not qualified. | 1.3.6.1.4.1.476.1.42.3.2.1.199 | current | ||
| lgpConditionManReTransferInhibited OBJECT-IDENTITY Manual retransfer from bypass to inverter is inhibited. | 1.3.6.1.4.1.476.1.42.3.2.1.200 | current | ||
| lgpConditionBatteryChargeError OBJECT-IDENTITY The battery is not charging properly. Some reasons for this condition include, but are not limited to: battery charger failure, battery failure, etc. | 1.3.6.1.4.1.476.1.42.3.2.1.201 | current | ||
| lgpConditionBatteryAutoTestInhibited OBJECT-IDENTITY Automatic (scheduled) battery tests are inhibited. | 1.3.6.1.4.1.476.1.42.3.2.1.202 | current | ||
| lgpConditionBatteryChargeReducedExt OBJECT-IDENTITY A reduced battery charging algorithm is being used due to an external signal. | 1.3.6.1.4.1.476.1.42.3.2.1.203 | current | ||
| lgpConditionBatteryCapacityLow OBJECT-IDENTITY The battery capacity is low. Some reasons for this condition include, but are not limited to: a battery is offline, the battery age has reduced its capabilities, etc. | 1.3.6.1.4.1.476.1.42.3.2.1.204 | current | ||
| lgpConditionBatteryTempImbalance OBJECT-IDENTITY The temperature difference between two batteries in the system exceeds the predefined threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.205 | current | ||
| lgpConditionBatteryEqualize OBJECT-IDENTITY The rectifier output voltage has been increased to equalize the battery voltage level. | 1.3.6.1.4.1.476.1.42.3.2.1.206 | current | ||
| lgpConditionBatteryChargeInhibitedExt OBJECT-IDENTITY Battery charging is inhibited due to an external inhibit signal. | 1.3.6.1.4.1.476.1.42.3.2.1.207 | current | ||
| lgpConditionServiceExtBatteryMonitorGroup OBJECT-IDENTITY This group contains battery monitor service conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.208 | current | ||
| lgpConditionServiceExtBatteryMonitor1 OBJECT-IDENTITY External battery monitor 1 indicates battery maintenance is required. | 1.3.6.1.4.1.476.1.42.3.2.1.208.1 | current | ||
| lgpConditionServiceExtBatteryMonitor2 OBJECT-IDENTITY External battery monitor 2 indicates battery maintenance is required. | 1.3.6.1.4.1.476.1.42.3.2.1.208.2 | current | ||
| lgpConditionBatteryGroundFault OBJECT-IDENTITY Battery system ground fault amperage exceeds the threshold. | 1.3.6.1.4.1.476.1.42.3.2.1.209 | current | ||
| lgpConditionBatteryLowShutdown OBJECT-IDENTITY With the battery breaker closed, the battery voltage has dropped below the calculated End-Of-Discharge (EOD) limit. | 1.3.6.1.4.1.476.1.42.3.2.1.210 | current | ||
| lgpConditionEmergencyPowerOffLocal OBJECT-IDENTITY The system has detected an Emergency Power Off (EPO) condition. The local EPO switch has cut off the power source to the system. | 1.3.6.1.4.1.476.1.42.3.2.1.211 | current | ||
| lgpConditionOutputLowPFLagging OBJECT-IDENTITY The system has detected a lagging output power factor below the threshold, resulting in reduced load capacity. | 1.3.6.1.4.1.476.1.42.3.2.1.212 | current | ||
| lgpConditionOutputLowPFLeading OBJECT-IDENTITY The system has detected a leading output power factor below the threshold, resulting in reduced load capacity. | 1.3.6.1.4.1.476.1.42.3.2.1.213 | current | ||
| lgpConditionOutputToLoadFault OBJECT-IDENTITY The system has detected an output to load fault. This could be caused by over or under voltage, or by over or under frequency. | 1.3.6.1.4.1.476.1.42.3.2.1.214 | current | ||
| lgpConditionInvRestartInhibitedExt OBJECT-IDENTITY Restart of the inverter is inhibited by an external signal. | 1.3.6.1.4.1.476.1.42.3.2.1.215 | current | ||
| lgpConditionInverterShutdownOverload OBJECT-IDENTITY The system has shutdown the inverter due to a sustained overload. This event does not indicate if the load has been dropped or transferred to bypass. At least one phase of the inverter power dissipation limit has been exceeded. | 1.3.6.1.4.1.476.1.42.3.2.1.216 | current | ||
| lgpConditionInverterOffExt OBJECT-IDENTITY The inverter is off due to the state of an external signal. | 1.3.6.1.4.1.476.1.42.3.2.1.217 | current | ||
| lgpConditionInputContactGroup OBJECT-IDENTITY The system has detected an active input contact. | 1.3.6.1.4.1.476.1.42.3.2.1.218 | current | ||
| lgpConditionInputContact01 OBJECT-IDENTITY The system has detected that input contact 1 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.1 | current | ||
| lgpConditionInputContact02 OBJECT-IDENTITY The system has detected that input contact 2 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.2 | current | ||
| lgpConditionInputContact03 OBJECT-IDENTITY The system has detected that input contact 3 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.3 | current | ||
| lgpConditionInputContact04 OBJECT-IDENTITY The system has detected that input contact 4 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.4 | current | ||
| lgpConditionInputContact05 OBJECT-IDENTITY The system has detected that input contact 5 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.5 | current | ||
| lgpConditionInputContact06 OBJECT-IDENTITY The system has detected that input contact 6 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.6 | current | ||
| lgpConditionInputContact07 OBJECT-IDENTITY The system has detected that input contact 7 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.7 | current | ||
| lgpConditionInputContact08 OBJECT-IDENTITY The system has detected that input contact 8 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.8 | current | ||
| lgpConditionInputContact09 OBJECT-IDENTITY The system has detected that input contact 9 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.9 | current | ||
| lgpConditionInputContact10 OBJECT-IDENTITY The system has detected that input contact 10 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.10 | current | ||
| lgpConditionInputContact11 OBJECT-IDENTITY The system has detected that input contact 11 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.11 | current | ||
| lgpConditionInputContact12 OBJECT-IDENTITY The system has detected that input contact 12 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.12 | current | ||
| lgpConditionInputContact13 OBJECT-IDENTITY The system has detected that input contact 13 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.13 | current | ||
| lgpConditionInputContact14 OBJECT-IDENTITY The system has detected that input contact 14 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.14 | current | ||
| lgpConditionInputContact15 OBJECT-IDENTITY The system has detected that input contact 15 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.15 | current | ||
| lgpConditionInputContact16 OBJECT-IDENTITY The system has detected that input contact 16 is active. | 1.3.6.1.4.1.476.1.42.3.2.1.218.16 | current | ||
| lgpConditionRectifierOperInhibited OBJECT-IDENTITY The operation of the rectifier is inhibited by an external signal. | 1.3.6.1.4.1.476.1.42.3.2.1.219 | current | ||
| lgpConditionBypassBackFeedBrkrOpen OBJECT-IDENTITY The bypass backfeed breaker is in the open position. | 1.3.6.1.4.1.476.1.42.3.2.1.220 | current | ||
| lgpConditionAutoRestartInProgress OBJECT-IDENTITY Auto restart is in progress. Becomes inactive when auto restart completes or fails. | 1.3.6.1.4.1.476.1.42.3.2.1.221 | current | ||
| lgpConditionAutoRestartInhibitedExt OBJECT-IDENTITY Auto restart is inhibited due to an external signal. | 1.3.6.1.4.1.476.1.42.3.2.1.222 | current | ||
| lgpConditionAutoRestartFailed OBJECT-IDENTITY Auto restart has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.223 | current | ||
| lgpConditionInputOnGenerator OBJECT-IDENTITY A generator is supplying the power to the system. | 1.3.6.1.4.1.476.1.42.3.2.1.224 | current | ||
| lgpConditionInputFilterCycleLock OBJECT-IDENTITY The input filter disconnect has opened too many times within a given period of time. | 1.3.6.1.4.1.476.1.42.3.2.1.225 | current | ||
| lgpConditionServiceCodeActive OBJECT-IDENTITY The system is in an operational mode intended for testing. In normal operating conditions, the system should not be in this state. | 1.3.6.1.4.1.476.1.42.3.2.1.226 | current | ||
| lgpConditionLoadBusSyncActive OBJECT-IDENTITY Load Bus Sync Operation is active. This synchronizes the UPS output with the output of another UPS. | 1.3.6.1.4.1.476.1.42.3.2.1.227 | current | ||
| lgpConditionLoadBusSyncInhibited OBJECT-IDENTITY The system has detected that conditions to perform Load Bus Sync Operation are not satisfied. | 1.3.6.1.4.1.476.1.42.3.2.1.228 | current | ||
| lgpConditionControlsResetRequired OBJECT-IDENTITY A controls reset is required because one or more critical settings have changed. | 1.3.6.1.4.1.476.1.42.3.2.1.229 | current | ||
| lgpConditionEquipTempSensorFailed OBJECT-IDENTITY A temperature sensor is reporting a value outside the bounds of a properly operating sensor. | 1.3.6.1.4.1.476.1.42.3.2.1.230 | current | ||
| lgpConditionInputCurrentImbalance OBJECT-IDENTITY The current on one input phase is much greater or lower than the average current of all the phases. This may indicate improper operation of the rectifier or input filter. | 1.3.6.1.4.1.476.1.42.3.2.1.231 | current | ||
| lgpConditionPumpGroup OBJECT-IDENTITY The system has detected an alarm with one of the pumps. | 1.3.6.1.4.1.476.1.42.3.2.1.232 | current | ||
| lgpConditionPumpFlowLoss OBJECT-IDENTITY The system has detected a loss of flow with one or more pumps. | 1.3.6.1.4.1.476.1.42.3.2.1.232.1 | current | ||
| lgpConditionPump1FlowLoss OBJECT-IDENTITY The system has detected a loss of flow with pump 1. | 1.3.6.1.4.1.476.1.42.3.2.1.232.1.1 | current | ||
| lgpConditionPump2FlowLoss OBJECT-IDENTITY The system has detected a loss of flow with pump 2. | 1.3.6.1.4.1.476.1.42.3.2.1.232.1.2 | current | ||
| lgpConditionPumpShortCycle OBJECT-IDENTITY The system has detected a short cycling of the pumps. One or more of the pumps has been turned on and off a number of times within a specified time period. | 1.3.6.1.4.1.476.1.42.3.2.1.232.2 | current | ||
| lgpConditionPumpInverterShortCycle OBJECT-IDENTITY The system has detected a short cycling of one or more pump inverters and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.1.232.3 | current | ||
| lgpConditionPump1InverterShortCycle OBJECT-IDENTITY The system has detected a short cycling of the inverter for pump 1 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.1.232.3.1 | current | ||
| lgpConditionPump2InverterShortCycle OBJECT-IDENTITY The system has detected a short cycling of the inverter for pump 2 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.1.232.3.2 | current | ||
| lgpConditionValveGroup OBJECT-IDENTITY The system has detected an alarm with one of the valves. | 1.3.6.1.4.1.476.1.42.3.2.1.233 | current | ||
| lgpConditionChilledWaterValvePosition OBJECT-IDENTITY The system has detected a problem with the chilled water valve position. The position of the chilled water control valve does not match an expected value. | 1.3.6.1.4.1.476.1.42.3.2.1.233.1 | current | ||
| lgpConditionCondensationDetected OBJECT-IDENTITY The system has detected condensation. | 1.3.6.1.4.1.476.1.42.3.2.1.234 | current | ||
| lgpConditionMaintenanceGroup OBJECT-IDENTITY The system has detected a maintenance condition. This group contains various maintenance conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.235 | current | ||
| lgpConditionMaintenanceDue OBJECT-IDENTITY System is due for maintenance. | 1.3.6.1.4.1.476.1.42.3.2.1.235.1 | current | ||
| lgpConditionMaintenanceComplete OBJECT-IDENTITY The system maintenance has been completed. | 1.3.6.1.4.1.476.1.42.3.2.1.235.2 | current | ||
| lgpConditionExternalEventSignalGroup OBJECT-IDENTITY This group contains various conditions signalled by external inputs. Each event is deactivated when the signal is inactive. | 1.3.6.1.4.1.476.1.42.3.2.1.236 | current | ||
| lgpConditionExternalFireDetect OBJECT-IDENTITY Fire detected, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.1.236.1 | current | ||
| lgpConditionExternalFlowLoss OBJECT-IDENTITY Loss of flow is detected, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.1.236.2 | current | ||
| lgpConditionExternalReheatLockout OBJECT-IDENTITY The reheater is shut down and disabled by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.1.236.3 | current | ||
| lgpConditionExternalOverTemp OBJECT-IDENTITY A temperature has exceeded its threshold, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.1.236.4 | current | ||
| lgpConditionExternalCompLockout OBJECT-IDENTITY The compressor is shut down and disabled by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.1.236.5 | current | ||
| lgpConditionExternalHumidifierLockout OBJECT-IDENTITY The humidifier is shut down and disabled by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.1.236.6 | current | ||
| lgpConditionComponentShutdownGroup OBJECT-IDENTITY This group contains conditions signaling shutdown of various system components. | 1.3.6.1.4.1.476.1.42.3.2.1.237 | current | ||
| lgpConditionComponentShutdownPartial OBJECT-IDENTITY An event has occurred requiring some system components to be shutdown and disabled. | 1.3.6.1.4.1.476.1.42.3.2.1.237.1 | current | ||
| lgpConditionComponentShutdownHighPower OBJECT-IDENTITY Supply to high power components has been shutdown. | 1.3.6.1.4.1.476.1.42.3.2.1.237.2 | current | ||
| lgpConditionCondenserProblemGroup OBJECT-IDENTITY This group contains condenser conditions. | 1.3.6.1.4.1.476.1.42.3.2.1.238 | current | ||
| lgpConditionCondenser1Problem OBJECT-IDENTITY Condenser 1 is not operating within its normal parameters. | 1.3.6.1.4.1.476.1.42.3.2.1.238.1 | current | ||
| lgpConditionHumidityOutOfPropBand OBJECT-IDENTITY The system has detected a humidity reading that remained outside of the proportional control band for an extended period of time. | 1.3.6.1.4.1.476.1.42.3.2.1.239 | current | ||
| lgpConditionEnvRemoteSensorGroup OBJECT-IDENTITY This group contains remote sensors. | 1.3.6.1.4.1.476.1.42.3.2.1.240 | current | ||
| lgpConditionEnvRemoteSensor1Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.1 | current | ||
| lgpConditionEnvRemoteSensor2Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.2 | current | ||
| lgpConditionEnvRemoteSensor3Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.3 | current | ||
| lgpConditionEnvRemoteSensor4Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.4 | current | ||
| lgpConditionEnvRemoteSensor5Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.5 | current | ||
| lgpConditionEnvRemoteSensor6Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.6 | current | ||
| lgpConditionEnvRemoteSensor7Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.7 | current | ||
| lgpConditionEnvRemoteSensor8Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.8 | current | ||
| lgpConditionEnvRemoteSensor9Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.9 | current | ||
| lgpConditionEnvRemoteSensor10Issue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. | 1.3.6.1.4.1.476.1.42.3.2.1.240.10 | current | ||
| lgpConditionNeutralSnubberBoardCommFailure OBJECT-IDENTITY The Neutral Snubber board has stopped communicating. | 1.3.6.1.4.1.476.1.42.3.2.1.241 | current | ||
| lgpConditionRedundantChargerFailure OBJECT-IDENTITY The redundant charger has failed. | 1.3.6.1.4.1.476.1.42.3.2.1.242 | current | ||
| lgpConditionBoardInputContactorPowerFailure OBJECT-IDENTITY Board input contactor power failure. | 1.3.6.1.4.1.476.1.42.3.2.1.243 | current | ||
| lgpConditionBoard1InputContactorPowerFailure OBJECT-IDENTITY Board1 input contactor power failure. | 1.3.6.1.4.1.476.1.42.3.2.1.243.1 | current | ||
| lgpConditionBoard2InputContactorPowerFailure OBJECT-IDENTITY Board2 input contactor power failure. | 1.3.6.1.4.1.476.1.42.3.2.1.243.2 | current | ||
| lgpConditionTooManySensors OBJECT-IDENTITY The number of sensors installed on the device has exceeded the pre-determined limit. | 1.3.6.1.4.1.476.1.42.3.2.1.5423 | current | ||
| lgpConditionDoorSwitchOpen OBJECT-IDENTITY An open door has been detected. | 1.3.6.1.4.1.476.1.42.3.2.1.5471 | current | ||
| lgpConditionContactClosureOpen OBJECT-IDENTITY An open circuit has been detected. | 1.3.6.1.4.1.476.1.42.3.2.1.5479 | current | ||
| lgpConditionContactClosureClosed OBJECT-IDENTITY A closed circuit has been detected. | 1.3.6.1.4.1.476.1.42.3.2.1.5480 | current | ||
| lgpConditionSensorsNotDisplayed OBJECT-IDENTITY The number of sensors that can be displayed (monitored) on the device has exceeded the pre-determined limit. Note this condition differs from the lgpConditionTooManySensors in that the system may currently have less than the maximum of installed sensors present but one or more of those sensors can not be displayed because the display order table (lgpPduAuxMeasOrderTable) contains entries for sensors that are not currently installed. This condition effectively prevents one or more installed sensors from being presented in the lgpPduAuxMeasTable. It is possible for both this condition and the lgpConditionTooManySensors condition to be active at the same time. | 1.3.6.1.4.1.476.1.42.3.2.1.6119 | current | ||
| lgpConditionsPresent OBJECT-TYPE The present number of conditions (rows) in the lgpConditionsTable. | 1.3.6.1.4.1.476.1.42.3.2.2 | Gauge32 | read-only | current |
| lgpConditionsTable OBJECT-TYPE A list of condition table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions in effect. The number of rows in the table is given by (lgpConditionsPresent). The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row subject to the following rules: Rows are removed from the table based on the following rules: 1. If a condition does not require acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState'). 2. If a condition requires acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState') AND the condition is acknowledged (see 'lgpConditionAcknowledged'). 3. If the columns 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are not present for the condition then the condition will be removed as soon as the issue causing the condition clears. The agent creates the first row with lgpConditionId equal to 1, and increments the value of 'lgpConditionId' each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of lgpConditionId would otherwise be exceeded. The number of rows in the table at any given time is reflected by the value of 'lgpConditionsPresent'. | 1.3.6.1.4.1.476.1.42.3.2.3 | not-accessible | current | |
| lgpConditionEntry OBJECT-TYPE This entry defines the contents of the rows for the table 'lgpConditionsTable'. A row in this table cannot be created or deleted by SNMP operations on columns of the table. | 1.3.6.1.4.1.476.1.42.3.2.3.1 | not-accessible | current | |
| lgpConditionId OBJECT-TYPE A unique identifier for a condition. This value must remain constant between agent initializations. This OID is used as an index to identify a row in the table 'lgpConditionsTable'. | 1.3.6.1.4.1.476.1.42.3.2.3.1.1 | Unsigned32 | read-only | current |
| lgpConditionDescr OBJECT-TYPE A reference to a condition description object. The object referenced should not be accessible, but rather be used to provide a unique description. | 1.3.6.1.4.1.476.1.42.3.2.3.1.2 | OBJECT IDENTIFIER | read-only | current |
| lgpConditionTime OBJECT-TYPE The value of sysUpTime when the condition occurred (became active). | 1.3.6.1.4.1.476.1.42.3.2.3.1.3 | TimeTicks | read-only | current |
| lgpConditionTableRef OBJECT-TYPE This object will be included as a varbind in some rows of the table. It is a reference to a table object in the MIB. The value of this object will be the OID of a table that the object that the condition applies to is defined. The table row corresponding to this object will also contain a varbind 'lgpConditionTableRowRef' that will specify which instance (row) in the referenced table the object is defined in. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType alarm lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required In the above example the breaker opened for a Receptacle branch. The specific receptacle branch is specified by the additional varbind (lgpEventParmTableRowRef). In this case the notification is for the 4th receptacle branch on the 1st PDU in the cluster. | 1.3.6.1.4.1.476.1.42.3.2.3.1.5 | OBJECT IDENTIFIER | read-only | current |
| lgpConditionTableRowRef OBJECT-TYPE This is a reference to the (cell) in the table specified by the companion varbind (lgpConditionTableRef) in this condition. The row in the table where this cell exists represents the object that this condition applies to. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required The table containing the definition of the receptacle branch (lgpPduRbTable) is given by the varbind (lgpConditionTableRef) The specific receptacle branch (instance) is specified by the varbind (lgpConditionTableRowRef). In this case the condition is for the 4th receptacle branch on the 1st PDU in the PDU cluster. If one wanted to retrieve the serial number for this receptacle branch the OID would be: lgpPduRbEntrySerialNum.1.4. | 1.3.6.1.4.1.476.1.42.3.2.3.1.6 | OBJECT IDENTIFIER | read-only | current |
| lgpConditionType OBJECT-TYPE The type of condition in this row in the table. | 1.3.6.1.4.1.476.1.42.3.2.3.1.10 | INTEGER {not-specified(0), message(2), warning(4), alarm(6), fault(8)} | read-only | current |
| lgpConditionCurrentState OBJECT-TYPE Indication of the current state of the event. If the state is 'active' then the condition currently exists. If the state is 'inactive' then the condition no longer exists (i.e. the situation causing the condition has cleared or been resolved). The behavior of some devices is to remove the condition from this table when the condition clears. The behavior of other devices is to leave the condition entry in the table until the condition is acknowledged ( see lgpConditionAcknowledged and lgpConditionAckReq). | 1.3.6.1.4.1.476.1.42.3.2.3.1.12 | INTEGER {active(1), inactive(2)} | read-only | current |
| lgpConditionSeverity OBJECT-TYPE This represents the relative severity of the condition. | 1.3.6.1.4.1.476.1.42.3.2.3.1.14 | INTEGER {not-applicable(0), minor(3), major(6), critical(9)} | read-only | current |
| lgpConditionAcknowledged OBJECT-TYPE This indicates if the condition has been acknowledged. If the value is 'notAcknowledged' then the condition has not been acknowledged. If the value is 'acknowledged' then the condition has been acknowledged. Writing a value of 'acknowledged' to this object acknowledges the condition and the value will be changed to 'acknowledged'. If the current state of the condition is 'active' (see lgpConditionCurrentState) the condition will, for all devices remain in the table regardless of the state of the 'lgpConditionAcknowledged' object. If the 'lgpConditionAckReq' is 'notRequired' or this column does not exist for the row then this object has no affect on the duration the condition stays in the lgpConditionsTable. If the 'lgpConditionAckReq' is 'required' then the condition will remain in the condition table until both the 'lgpConditionCurrentState' is 'inactive' AND 'lgpConditionAcknowledged' is 'acknowledged'. | 1.3.6.1.4.1.476.1.42.3.2.3.1.18 | INTEGER {notAcknowledged(1), acknowledged(2)} | read-write | current |
| lgpConditionAckReq OBJECT-TYPE This indicates if the corresponding condition does or does not require user acknowledgement. Conditions that require user acknowledgement will have a value of 'required'. Those conditions that do not require user acknowledgement will have a value of 'notRequired' or in some devices the column may not be present at all. If a condition requires acknowledgement it will remain in the table until both the 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are 'inactive' and 'acknowledged' respectively (see lgpConditionAcknowledged). If a condition does not require acknowledgement it will be removed from the table as soon as its 'lgpConditionCurrentState' is 'inactive'. | 1.3.6.1.4.1.476.1.42.3.2.3.1.19 | INTEGER {required(1), notRequired(2)} | read-only | current |
| lgpConditionControl OBJECT-IDENTITY | 1.3.6.1.4.1.476.1.42.3.2.4 | |||
| lgpConditionControlEventReset OBJECT-TYPE Event Reset Command. This command will reset all of the device's events. On some units, when an event is activated, a 'set' field is also marked and maintained even when the event has become inactive. The 'set' field is only cleared when the user clears it and the event is no longer active. This item will clear the 'set' field for all events that are not active. | 1.3.6.1.4.1.476.1.42.3.2.4.1 | INTEGER {noAction(1), resetAll(2)} | read-write | current |
| lgpConditionControlEventAck OBJECT-TYPE Event Acknowledge Command. This command will acknowledge all of the device's events. | 1.3.6.1.4.1.476.1.42.3.2.4.2 | INTEGER {noAction(1), ackAll(2)} | read-write | current |
| lgpConditionControlTable OBJECT-TYPE A list of condition control table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions that are controllable by the unit. This table does not necessarily contain all conditions supported by the unit. This table only contains conditions that are end-user modifiable. | 1.3.6.1.4.1.476.1.42.3.2.4.20 | not-accessible | current | |
| lgpConditionControlEntry OBJECT-TYPE This entry defines the contents of the rows for the table 'lgpConditionControlTable'. A row in this table cannot be created or deleted by user initiated SNMP operations on columns of the table. | 1.3.6.1.4.1.476.1.42.3.2.4.20.1 | not-accessible | current | |
| lgpConditionControlIndex OBJECT-TYPE This is the index indicating the nth element of the table. | 1.3.6.1.4.1.476.1.42.3.2.4.20.1.1 | Unsigned32 | not-accessible | current |
| lgpConditionControlDescr OBJECT-TYPE A reference to an Object Identifier (OID) representing a unique condition. The referenced OID is used solely for identification purposes. The object identifier referenced here will be the same object identifier referenced in the lgpConditionsTable (column: lgpConditionDescr) when the condition is activated. | 1.3.6.1.4.1.476.1.42.3.2.4.20.1.2 | OBJECT IDENTIFIER | read-only | current |
| lgpConditionControlEnableStatus OBJECT-TYPE The value in this column determines if the device is currently capable of generating this event. If the value is 'enabled' then the event will be generated if the condition indicated by lgpConditionControlDescr becomes active. If the value is 'disabled' the device will never generate the event. This value is stored on the managed device. Some devices do not allow write access to some entries in this column. The 'lgpConditionControlEnableCapability' column indicates whether this entry can be written. | 1.3.6.1.4.1.476.1.42.3.2.4.20.1.3 | INTEGER {not-specified(0), enabled(1), disabled(2)} | read-write | current |
| lgpConditionControlType OBJECT-TYPE The 'type' assigned or configured for this condition. The value assigned to the condition here is displayed in the lgpConditionsTable (column: lgpConditionType). For some units this is user configurable. This value is stored on the managed device. | 1.3.6.1.4.1.476.1.42.3.2.4.20.1.4 | INTEGER {not-specified(0), message(2), warning(4), alarm(6), fault(8)} | read-write | current |
| lgpConditionControlEnableCapability OBJECT-TYPE Some devices do not allow write access to some entries in the 'lgpConditionControlEnableStatus' column. This column indicates whether the 'lgpConditionControlEnableStatus' entry for this row can be written. | 1.3.6.1.4.1.476.1.42.3.2.4.20.1.5 | INTEGER {not-specified(0), readonly(1), readwrite(2)} | read-only | current |
| lgpConditionDescription OBJECT-TYPE The ASCII text description for the condition. | 1.3.6.1.4.1.476.1.42.3.2.5 | DisplayString (SIZE(255)) | read-only | current |
| lgpNetworkName OBJECT-TYPE The network name in a node.domain.com like format. This object is intended to be used as a varbind object by other notifications that have a context of a network address. As an example the lgpAgentDnsLookupFailure trap which describes a network name that is failing or has failed to be resolved from a Domain Name Service (DNS) lookup. Refer to RFC 952 for further information. | 1.3.6.1.4.1.476.1.42.3.2.6 | DisplayString (SIZE(255)) | read-only | current |
| lgpFlexConditions OBJECT-IDENTITY | 1.3.6.1.4.1.476.1.42.3.2.7 |