MIBs Depot

LIEBERT-GP-CONDITIONS-MIB

Registered at
1.3.6.1.4.1.476.1.42.1.3.1
1.3.6.1.4.1.476.1.42.3.2.1
1.3.6.1.4.1.476.1.42.3.2.4
1.3.6.1.4.1.476.1.42.3.2.7
Last updated
2013-02-12 00:00
Organization
Liebert Corporation
Revisions
2013-02-12 00:00, 2008-11-17 00:00, 2008-07-02 00:00, 2008-01-10 00:00, 2007-05-29 00:00, 2006-08-15 00:00, 2006-02-22 00:00
Namespace
liebert
Source file
LIEBERT-GP-CONDITIONS-MIB
Digest
sha256:3fdac9085c398196ac47baa3b2602e80073f01a629fd8b0a27f35e81e7f6b5d7

Description

The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008,2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.

Contact

Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com Author: Gregory M. Hoge

Imports

FromSymbols
LIEBERT-GP-REGISTRATION-MIBlgpConditions, liebertConditionsModuleReg
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIGauge32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

3 module(s) in this corpus import this one.

Load order

Every file a consumer needs in order to load this module, dependencies first.

LIEBERT-GP-CONDITIONS-MIB
LIEBERT-GP-REGISTRATION-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Under this module's arcs

Where the registration tree carries on below this module.

ArcNameModule
1.3.6.1.4.1.476.1.42.3.2.7.1lgpFlexConditionsWellKnownLIEBERT-GP-FLEXIBLE-CONDITIONS-MIB

Objects

NameOIDSyntaxAccessStatus
lgpConditionsWellKnown
OBJECT-IDENTITY
1.3.6.1.4.1.476.1.42.3.2.1
lgpConditionHighTemperature
OBJECT-IDENTITY
The temperature has exceeded the high temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.1current
lgpConditionLowTemperature
OBJECT-IDENTITY
The temperature is below the low temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.2current
lgpConditionHighHumidity
OBJECT-IDENTITY
The humidity has exceeded the high humidity threshold.
1.3.6.1.4.1.476.1.42.3.2.1.3current
lgpConditionLowHumidity
OBJECT-IDENTITY
The humidity is below the low humidity threshold.
1.3.6.1.4.1.476.1.42.3.2.1.4current
lgpConditionLossOfAirflow
OBJECT-IDENTITY
The system has detected a loss of air flow.
1.3.6.1.4.1.476.1.42.3.2.1.5current
lgpConditionLossOfAirflow1
OBJECT-IDENTITY
The system has detected a loss of air flow at sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.5.1current
lgpConditionLossOfAirflow2
OBJECT-IDENTITY
The system has detected a loss of air flow at sensor 2.
1.3.6.1.4.1.476.1.42.3.2.1.5.2current
lgpConditionLossOfAirflowBlower1
OBJECT-IDENTITY
The system has detected a loss of air flow from blower 1.
1.3.6.1.4.1.476.1.42.3.2.1.5.3current
lgpConditionLossOfAirflowAllBlowers
OBJECT-IDENTITY
No air flow through the unit due to failure of all blowers.
1.3.6.1.4.1.476.1.42.3.2.1.5.4current
lgpConditionChangeFilter
OBJECT-IDENTITY
The system has detected a condition indicating the air filter should be changed.
1.3.6.1.4.1.476.1.42.3.2.1.6current
lgpConditionCompressorHighHeadPressure
OBJECT-IDENTITY
This system has detected an excessive head pressure condition.
1.3.6.1.4.1.476.1.42.3.2.1.7current
lgpConditionCompressor1HighHeadPressure
OBJECT-IDENTITY
The system has detected excessive head pressure in compressor 1.
1.3.6.1.4.1.476.1.42.3.2.1.7.1current
lgpConditionCompressor1AHighHeadPressure
OBJECT-IDENTITY
The system has detected excessive head pressure in compressor 1A.
1.3.6.1.4.1.476.1.42.3.2.1.7.1.1current
lgpConditionCompressor1BHighHeadPressure
OBJECT-IDENTITY
The system has detected excessive head pressure in compressor 1B.
1.3.6.1.4.1.476.1.42.3.2.1.7.1.2current
lgpConditionCompressor2HighHeadPressure
OBJECT-IDENTITY
The system has detected excessive head pressure in compressor 2.
1.3.6.1.4.1.476.1.42.3.2.1.7.2current
lgpConditionCompressor2AHighHeadPressure
OBJECT-IDENTITY
The system has detected excessive head pressure in compressor 2A.
1.3.6.1.4.1.476.1.42.3.2.1.7.2.1current
lgpConditionCompressor2BHighHeadPressure
OBJECT-IDENTITY
The system has detected excessive head pressure in compressor 2B.
1.3.6.1.4.1.476.1.42.3.2.1.7.2.2current
lgpConditionCompressor3HighHeadPressure
OBJECT-IDENTITY
The system has detected excessive head pressure in compressor 3.
1.3.6.1.4.1.476.1.42.3.2.1.7.3current
lgpConditionCompressor4HighHeadPressure
OBJECT-IDENTITY
The system has detected excessive head pressure in compressor 4.
1.3.6.1.4.1.476.1.42.3.2.1.7.4current
lgpConditionCompressorOverload
OBJECT-IDENTITY
This system has detected a compressor overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.8current
lgpConditionCompressor1Overload
OBJECT-IDENTITY
The system has detected an overload condition on compressor 1.
1.3.6.1.4.1.476.1.42.3.2.1.8.1current
lgpConditionCompressor2Overload
OBJECT-IDENTITY
The system has detected an overload condition on compressor 2.
1.3.6.1.4.1.476.1.42.3.2.1.8.2current
lgpConditionCompressor3Overload
OBJECT-IDENTITY
The system has detected an overload condition on compressor 3.
1.3.6.1.4.1.476.1.42.3.2.1.8.3current
lgpConditionCompressor4Overload
OBJECT-IDENTITY
The system has detected an overload condition on compressor 4.
1.3.6.1.4.1.476.1.42.3.2.1.8.4current
lgpConditionCompressorShortCycle
OBJECT-IDENTITY
A compressor has exceeded the maximum number of starts in a minimum time period.
1.3.6.1.4.1.476.1.42.3.2.1.9current
lgpConditionCompressor1ShortCycle
OBJECT-IDENTITY
The system has detected a short cycle event on compressor 1. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.1current
lgpConditionCompressor1AShortCycle
OBJECT-IDENTITY
The system has detected a short cycle event on compressor 1A. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.1.1current
lgpConditionCompressor1BShortCycle
OBJECT-IDENTITY
The system has detected a short cycle event on compressor 1B. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.1.2current
lgpConditionCompressor2ShortCycle
OBJECT-IDENTITY
The system has detected a short cycle event on compressor 2. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.2current
lgpConditionCompressor2AShortCycle
OBJECT-IDENTITY
The system has detected a short cycle event on compressor 2A. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.2.1current
lgpConditionCompressor2BShortCycle
OBJECT-IDENTITY
The system has detected a short cycle event on compressor 2B. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.2.2current
lgpConditionCompressor3ShortCycle
OBJECT-IDENTITY
The system has detected a short cycle event on compressor 3. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.3current
lgpConditionCompressor4ShortCycle
OBJECT-IDENTITY
The system has detected a short cycle event on compressor 4. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.4current
lgpConditionCompressorLowSuctionPressure
OBJECT-IDENTITY
The pressure at a compressor inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.10current
lgpConditionCompressor1LowSuctionPressure
OBJECT-IDENTITY
The pressure at compressor 1 inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.10.1current
lgpConditionCompressor2LowSuctionPressure
OBJECT-IDENTITY
The pressure at compressor 2 inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.10.2current
lgpConditionCompressor3LowSuctionPressure
OBJECT-IDENTITY
The pressure at compressor 3 inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.10.3current
lgpConditionCompressor4LowSuctionPressure
OBJECT-IDENTITY
The pressure at compressor 4 inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.10.4current
lgpConditionMainFanOverLoad
OBJECT-IDENTITY
The system has detected a main fan overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.11current
lgpConditionManualOverride
OBJECT-IDENTITY
The system has detected a manual override condition.
1.3.6.1.4.1.476.1.42.3.2.1.12current
lgpConditionStandbyGlycoolPumpOn
OBJECT-IDENTITY
The standby Glycol or Glycool pump is activated.
1.3.6.1.4.1.476.1.42.3.2.1.13current
lgpConditionWaterUnderFloor
OBJECT-IDENTITY
Moisture has been detected under the floor.
1.3.6.1.4.1.476.1.42.3.2.1.14current
lgpConditionHumidifierProblem
OBJECT-IDENTITY
The system has detected a humidifier problem.
1.3.6.1.4.1.476.1.42.3.2.1.15current
lgpConditionLowWaterInHumidifier
OBJECT-IDENTITY
The system has detected a low water condition in the humidifier reservoir.
1.3.6.1.4.1.476.1.42.3.2.1.16current
lgpConditionSmokeDetected
OBJECT-IDENTITY
The system has detected smoke.
1.3.6.1.4.1.476.1.42.3.2.1.17current
lgpConditionLowWaterFlow
OBJECT-IDENTITY
The system has detected a low water flow rate condition.
1.3.6.1.4.1.476.1.42.3.2.1.18current
lgpConditionLostPower
OBJECT-IDENTITY
The system has lost power before being switched off using the controls. This condition is activated when power is restored.
1.3.6.1.4.1.476.1.42.3.2.1.19current
lgpGeneralFault
OBJECT-IDENTITY
A fault condition has been detected that is not identified in the well known list.
1.3.6.1.4.1.476.1.42.3.2.1.20current
lgpConditionLocalAlarm
OBJECT-IDENTITY
This system has detected a local, or customer, alarm condition.
1.3.6.1.4.1.476.1.42.3.2.1.21current
lgpConditionLocalAlarm1
OBJECT-IDENTITY
The system has detected that customer alarm condition 1 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.1current
lgpConditionLocalAlarm2
OBJECT-IDENTITY
The system has detected that customer alarm condition 2 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.2current
lgpConditionLocalAlarm3
OBJECT-IDENTITY
The system has detected that customer alarm condition 3 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.3current
lgpConditionLocalAlarm4
OBJECT-IDENTITY
The system has detected that customer alarm condition 4 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.4current
lgpConditionLocalAlarm5
OBJECT-IDENTITY
The system has detected that customer alarm condition 5 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.5current
lgpConditionLocalAlarm6
OBJECT-IDENTITY
The system has detected that customer alarm condition 6 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.6current
lgpConditionLocalAlarm7
OBJECT-IDENTITY
The system has detected that customer alarm condition 7 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.7current
lgpConditionLocalAlarm8
OBJECT-IDENTITY
The system has detected that customer alarm condition 8 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.8current
lgpConditionStandbyUnitOn
OBJECT-IDENTITY
The system has detected the standby unit is operating.
1.3.6.1.4.1.476.1.42.3.2.1.22current
lgpConditionCompressorLowPressure
OBJECT-IDENTITY
This system has detected a low head compressor condition.
1.3.6.1.4.1.476.1.42.3.2.1.23current
lgpConditionCompressor1LowPressure
OBJECT-IDENTITY
The system has detected low pressure in compressor 1.
1.3.6.1.4.1.476.1.42.3.2.1.23.1current
lgpConditionTandemCompressorCircuit1LowPressure
OBJECT-IDENTITY
The system has detected low pressure in tandem compressor circuit 1.
1.3.6.1.4.1.476.1.42.3.2.1.23.1.1current
lgpConditionCompressor2LowPressure
OBJECT-IDENTITY
The system has detected low pressure in compressor 2.
1.3.6.1.4.1.476.1.42.3.2.1.23.2current
lgpConditionTandemCompressorCircuit2LowPressure
OBJECT-IDENTITY
The system has detected low pressure in tandem compressor circuit 2.
1.3.6.1.4.1.476.1.42.3.2.1.23.2.1current
lgpConditionCompressor3LowPressure
OBJECT-IDENTITY
The system has detected low pressure in compressor 3.
1.3.6.1.4.1.476.1.42.3.2.1.23.3current
lgpConditionCompressor4LowPressure
OBJECT-IDENTITY
The system has detected low pressure in compressor 4.
1.3.6.1.4.1.476.1.42.3.2.1.23.4current
lgpConditionHighWaterInPan
OBJECT-IDENTITY
The system has detected a high water condition in the condenser pan.
1.3.6.1.4.1.476.1.42.3.2.1.24current
lgpConditionFaultySensor
OBJECT-IDENTITY
The system has detected a faulty temperature/humidity sensor.
1.3.6.1.4.1.476.1.42.3.2.1.25current
lgpConditionServiceCooling
OBJECT-IDENTITY
The Cooling system requires scheduled maintenance.
1.3.6.1.4.1.476.1.42.3.2.1.26current
lgpConditionServiceHumidifier
OBJECT-IDENTITY
The Humidifier requires scheduled maintenance.
1.3.6.1.4.1.476.1.42.3.2.1.27current
lgpConditionSystemControlBatteryLow
OBJECT-IDENTITY
Charge level of the system control's battery is below the alarm set point.
1.3.6.1.4.1.476.1.42.3.2.1.28current
lgpConditionGroundSystemFault
OBJECT-IDENTITY
The system has detected a ground system fault.
1.3.6.1.4.1.476.1.42.3.2.1.29current
lgpConditionGroundFailure
OBJECT-IDENTITY
The system has detected a ground failure.
1.3.6.1.4.1.476.1.42.3.2.1.30current
lgpConditionSecurityBreach
OBJECT-IDENTITY
The system has detected a security breach.
1.3.6.1.4.1.476.1.42.3.2.1.31current
lgpConditionEmergencyShutdown
OBJECT-IDENTITY
The system has detected an emergency shutdown condition. The System is shutting down as a result of this emergency.
1.3.6.1.4.1.476.1.42.3.2.1.32current
lgpConditionOnBypass
OBJECT-IDENTITY
This system has detected the load is being powered by a bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33current
lgpConditionLoadOnBypass
OBJECT-IDENTITY
The load is being powered by a bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33.1obsolete
lgpConditionLoadOnMaintenceBypass
OBJECT-IDENTITY
The load is being powered by a maintenance bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33.2current
lgpConditionParallelSysLoadOnBypass
OBJECT-IDENTITY
The parallel system has transferred to bypass.
1.3.6.1.4.1.476.1.42.3.2.1.33.3current
lgpConditionLoadOnBypassByImpact
OBJECT-IDENTITY
The system has detected a load impact and has transferred the load to the bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33.4current
lgpConditionLoadTransferedToBypass
OBJECT-IDENTITY
The system has transferred to bypass. The load is being powered by the bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33.5current
lgpConditionEmergencyTransferToBypass
OBJECT-IDENTITY
The system has performed an emergency transfer to bypass.
1.3.6.1.4.1.476.1.42.3.2.1.33.6current
lgpConditionOutputToLoadVoltTHD
OBJECT-IDENTITY
The total harmonic distortion (THD) of the output voltage has exceeded a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.34current
lgpConditionLogicFailure
OBJECT-IDENTITY
The system has detected a control logic failure.
1.3.6.1.4.1.476.1.42.3.2.1.35current
lgpConditionPowerSupplyFault
OBJECT-IDENTITY
This system had detected a power supply fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.36current
lgpConditionPowerSupply1Fault
OBJECT-IDENTITY
The system has detected power supply 1 is in a fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.36.1current
lgpConditionPowerSupply2Fault
OBJECT-IDENTITY
The system has detected power supply 2 is in a fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.36.2current
lgpConditionPowerSupplyFailure
OBJECT-IDENTITY
This system has detected a power supply failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.37current
lgpConditionPowerSupply1Failure
OBJECT-IDENTITY
The system has detected power supply 1 has failed.
1.3.6.1.4.1.476.1.42.3.2.1.37.1current
lgpConditionPowerSupply2Failure
OBJECT-IDENTITY
The system has detected power supply 2 has failed.
1.3.6.1.4.1.476.1.42.3.2.1.37.2current
lgpConditionSource1PowerSupplyInputFailure
OBJECT-IDENTITY
The system has detected the source 1 Power supply input has failed.
1.3.6.1.4.1.476.1.42.3.2.1.37.3current
lgpConditionSource2PowerSupplyInputFailure
OBJECT-IDENTITY
The system has detected the source 2 Power supply input has failed.
1.3.6.1.4.1.476.1.42.3.2.1.37.4current
lgpConditionPowerSupplyLogicFailure
OBJECT-IDENTITY
The system has detected a power supply logic failure.
1.3.6.1.4.1.476.1.42.3.2.1.37.5current
lgpConditionCompressorPowerSupplyFailure
OBJECT-IDENTITY
The system has detected the power supply to the compressors has failed.
1.3.6.1.4.1.476.1.42.3.2.1.37.6current
lgpConditionOverVoltage
OBJECT-IDENTITY
This system has detected an over voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.38current
lgpConditionSource1OverVoltage
OBJECT-IDENTITY
The system has detected an over voltage condition on source 1. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.38.1current
lgpConditionSource2OverVoltage
OBJECT-IDENTITY
The system has detected an over voltage condition on source 2. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.38.2current
lgpConditionOutputToLoadOverVoltage
OBJECT-IDENTITY
The system has detected the output to load is in an over-voltage condition. The voltage for the load has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.38.3current
lgpConditionInputOverVoltage
OBJECT-IDENTITY
The system has detected an input over voltage condition. The voltage measurement has risen above a pre-determined threshold for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.38.4current
lgpConditionBypassOverVoltage
OBJECT-IDENTITY
The system has detected an over voltage condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.38.5current
lgpConditionBypassOverVoltageFailure
OBJECT-IDENTITY
The system has detected an over voltage failure condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.38.6current
lgpConditionBatteryOverVoltage
OBJECT-IDENTITY
The system has detected a battery over voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.38.7current
lgpConditionDcBusOverVoltage
OBJECT-IDENTITY
This system has detected a DC Bus over voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.38.8current
lgpConditionDcBus1OverVoltage
OBJECT-IDENTITY
The system has detected an over voltage condition on DC Bus 1.
1.3.6.1.4.1.476.1.42.3.2.1.38.8.1current
lgpConditionDcBus2OverVoltage
OBJECT-IDENTITY
The system has detected an over voltage condition on DC Bus 2.
1.3.6.1.4.1.476.1.42.3.2.1.38.8.2current
lgpConditionDcBus1OverVoltageFailure
OBJECT-IDENTITY
The system has detected an over voltage failure condition on DC Bus 1.
1.3.6.1.4.1.476.1.42.3.2.1.38.8.3current
lgpConditionDcBus2OverVoltageFailure
OBJECT-IDENTITY
The system has detected an over voltage failure condition on DC Bus 2.
1.3.6.1.4.1.476.1.42.3.2.1.38.8.4current
lgpConditionUnderVoltage
OBJECT-IDENTITY
This system has detected an under voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.39current
lgpConditionSource1UnderVoltage
OBJECT-IDENTITY
The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.39.1current
lgpConditionSource2UnderVoltage
OBJECT-IDENTITY
The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.39.2current
lgpConditionOutputToLoadUnderVoltage
OBJECT-IDENTITY
The system has detected the output to load is in an under-voltage condition. The voltage for the load has fallen below a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.39.3current
lgpConditionSource1UnderVoltageRMS
OBJECT-IDENTITY
The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.39.4current
lgpConditionSource2UnderVoltageRMS
OBJECT-IDENTITY
The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.39.5current
lgpConditionInputUnderVoltage
OBJECT-IDENTITY
The system has detected an input under voltage condition. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.39.6current
lgpConditionBypassUnderVoltage
OBJECT-IDENTITY
The system has detected an under voltage condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.39.7current
lgpConditionBypassUnderVoltageFailure
OBJECT-IDENTITY
The system has detected an under voltage failure condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.39.8current
lgpConditionBatteryUnderVoltage
OBJECT-IDENTITY
The system has detected a battery under voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.39.9current
lgpConditionDcBusUnderVoltage
OBJECT-IDENTITY
This system has detected a DC bus under voltage condition
1.3.6.1.4.1.476.1.42.3.2.1.39.10current
lgpConditionDcBus1UnderVoltage
OBJECT-IDENTITY
The system has detected an under voltage condition on DC Bus 1.
1.3.6.1.4.1.476.1.42.3.2.1.39.10.1current
lgpConditionDcBus2UnderVoltage
OBJECT-IDENTITY
The system has detected an under voltage condition on DC Bus 2.
1.3.6.1.4.1.476.1.42.3.2.1.39.10.2current
lgpConditionDcBus1UnderVoltageFailure
OBJECT-IDENTITY
The system has detected an under voltage failure condition on DC Bus 1.
1.3.6.1.4.1.476.1.42.3.2.1.39.10.3current
lgpConditionDcBus2UnderVoltageFailure
OBJECT-IDENTITY
The system has detected an under voltage failure condition on DC Bus 2.
1.3.6.1.4.1.476.1.42.3.2.1.39.10.4current
lgpConditionOverload
OBJECT-IDENTITY
This system has detected an overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.40current
lgpConditionSource1Overload
OBJECT-IDENTITY
The system has detected an overload condition on source 1. The power requirement for this source has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.40.1current
lgpConditionSystemOverload
OBJECT-IDENTITY
The system has detected an overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.40.2current
lgpConditionSource1PeakCurrentOverLoad
OBJECT-IDENTITY
The system has detected source 1 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.40.3current
lgpConditionSource2PeakCurrentOverLoad
OBJECT-IDENTITY
The system has detected source 2 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.40.4current
lgpConditionOutputToLoadOverLimit
OBJECT-IDENTITY
The system had detected that the output to the load has exceeded the lgpPwrOutputToLoadUserOverloadLimit.
1.3.6.1.4.1.476.1.42.3.2.1.40.5current
lgpConditionOutputToLoadOverload
OBJECT-IDENTITY
The system has detected an output overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.40.6current
lgpConditionParallelSysOverload
OBJECT-IDENTITY
The parallel system has detected an overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.40.7current
lgpConditionBypassCurrentOverload
OBJECT-IDENTITY
With the load on bypass static switch, the measured output RMS current has exceeded a specified percentage of the nominal RMS current.
1.3.6.1.4.1.476.1.42.3.2.1.40.8current
lgpConditionBypassCurrentOverloadPhsA
OBJECT-IDENTITY
With the load on bypass static switch, the measured phase A output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
1.3.6.1.4.1.476.1.42.3.2.1.40.8.1current
lgpConditionBypassCurrentOverloadPhsB
OBJECT-IDENTITY
With the load on bypass static switch, the measured phase B output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
1.3.6.1.4.1.476.1.42.3.2.1.40.8.2current
lgpConditionBypassCurrentOverloadPhsC
OBJECT-IDENTITY
With the load on bypass static switch, the measured phase C output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
1.3.6.1.4.1.476.1.42.3.2.1.40.8.3current
lgpConditionScrShort
OBJECT-IDENTITY
This system has detected a Silicon Controlled Rectifier (SCR) short condition.
1.3.6.1.4.1.476.1.42.3.2.1.41current
lgpConditionSource1ScrShort
OBJECT-IDENTITY
The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition.
1.3.6.1.4.1.476.1.42.3.2.1.41.1current
lgpConditionSource2ScrShort
OBJECT-IDENTITY
The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition.
1.3.6.1.4.1.476.1.42.3.2.1.41.2current
lgpConditionBypassScrShort
OBJECT-IDENTITY
The system has detected a Silicon Controlled Rectifier (SCR) short condition on the bypass.
1.3.6.1.4.1.476.1.42.3.2.1.41.3current
lgpConditionInvStaticSwScrShort
OBJECT-IDENTITY
The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCRs).
1.3.6.1.4.1.476.1.42.3.2.1.41.4current
lgpConditionSource1NeutralScrShort
OBJECT-IDENTITY
The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition on the neutral line.
1.3.6.1.4.1.476.1.42.3.2.1.41.5current
lgpConditionSource2NeutralScrShort
OBJECT-IDENTITY
The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition on the neutral line.
1.3.6.1.4.1.476.1.42.3.2.1.41.6current
lgpConditionScrOpen
OBJECT-IDENTITY
This system has detected a Silicon Controlled Rectifier (SCR) open condition.
1.3.6.1.4.1.476.1.42.3.2.1.42current
lgpConditionSource1ScrOpen
OBJECT-IDENTITY
The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition.
1.3.6.1.4.1.476.1.42.3.2.1.42.1current
lgpConditionSource2ScrOpen
OBJECT-IDENTITY
The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition.
1.3.6.1.4.1.476.1.42.3.2.1.42.2current
lgpConditionBypassScrOpen
OBJECT-IDENTITY
The system has detected a Silicon Controlled Rectifier (SCR) open condition on the bypass.
1.3.6.1.4.1.476.1.42.3.2.1.42.3current
lgpConditionSource1NeutralScrOpen
OBJECT-IDENTITY
The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition on the neutral line.
1.3.6.1.4.1.476.1.42.3.2.1.42.4current
lgpConditionSource2NeutralScrOpen
OBJECT-IDENTITY
The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition on the neutral line.
1.3.6.1.4.1.476.1.42.3.2.1.42.5current
lgpConditionFanFailure
OBJECT-IDENTITY
This system has detected a fan failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.43current
lgpConditionFan1Failure
OBJECT-IDENTITY
The system has detected a fan 1 failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.43.1current
lgpConditionRedundantFanFailure
OBJECT-IDENTITY
A failure has occurred in a fan that cools the system's internal components and has resulted in a loss of fan redundancy.
1.3.6.1.4.1.476.1.42.3.2.1.43.2current
lgpConditionMultipleFanFailure
OBJECT-IDENTITY
Multiple fans have failed resulting in a decreased ability to cool the system's internal components.
1.3.6.1.4.1.476.1.42.3.2.1.43.3current
lgpConditionBlowerFanFailure
OBJECT-IDENTITY
The system has detected a problem with one or more of the blower fans. These are not the system internal cooling fans.
1.3.6.1.4.1.476.1.42.3.2.1.43.4current
lgpConditionBottomBlowerFanFailure
OBJECT-IDENTITY
The bottom environmental unit blower fan is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.1.43.4.1current
lgpConditionTopBlowerFanFailure
OBJECT-IDENTITY
The top environmental unit blower fan is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.1.43.4.2current
lgpConditionCondenserFanVFDFailure
OBJECT-IDENTITY
The system has detected a problem with the Variable Frequency Drive system for the condenser fan.
1.3.6.1.4.1.476.1.42.3.2.1.43.5current
lgpConditionFanPowerFailure
OBJECT-IDENTITY
The system has detected a power failure on one or more fans.
1.3.6.1.4.1.476.1.42.3.2.1.43.6current
lgpConditionTransferInhibited
OBJECT-IDENTITY
The system is preventing a transfer of the load to the alternate source.
1.3.6.1.4.1.476.1.42.3.2.1.44current
lgpConditionAutoReTransferPrimed
OBJECT-IDENTITY
The system is capable to retransfer to the preferred source.
1.3.6.1.4.1.476.1.42.3.2.1.45current
lgpConditionSourcesOutOfSync
OBJECT-IDENTITY
The system has detected that the input sources are not within the specified phase difference (synchronization window).
1.3.6.1.4.1.476.1.42.3.2.1.46current
lgpConditionSourceFailure
OBJECT-IDENTITY
This system has detected an input source failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.47current
lgpConditionSource1Failure
OBJECT-IDENTITY
The system has detected source 1 has failed.
1.3.6.1.4.1.476.1.42.3.2.1.47.1current
lgpConditionSource2Failure
OBJECT-IDENTITY
The system has detected source 2 has failed.
1.3.6.1.4.1.476.1.42.3.2.1.47.2current
lgpConditionAutoReTransferInhibited
OBJECT-IDENTITY
The system is preventing a retransfer of the load back to the preferred source.
1.3.6.1.4.1.476.1.42.3.2.1.48current
lgpConditionAutoReTransferFailed
OBJECT-IDENTITY
The system is failing to automatically retransfer the load back to the preferred source.
1.3.6.1.4.1.476.1.42.3.2.1.49current
lgpConditionFuseOpen
OBJECT-IDENTITY
This system has detected an open fuse condition.
1.3.6.1.4.1.476.1.42.3.2.1.50current
lgpConditionControlFuse1Open
OBJECT-IDENTITY
The system has detected a control power fuse 1 open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.1current
lgpConditionControlFuse2Open
OBJECT-IDENTITY
The system has detected a control power fuse 2 open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.2current
lgpConditionRectifierFuseOpen
OBJECT-IDENTITY
The system has detected a rectifier fuse open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.3current
lgpConditionInverterFuseOpen
OBJECT-IDENTITY
The system has detected an inverter fuse open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.4current
lgpConditionOutputToLoadFuseOpen
OBJECT-IDENTITY
The system has detected an output to load fuse open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.5current
lgpConditionDcCapacitorFuseOpen
OBJECT-IDENTITY
The system has detected a DC capacitor fuse open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.6current
lgpConditionDisconnect
OBJECT-IDENTITY
The system has detected a disconnect condition.
1.3.6.1.4.1.476.1.42.3.2.1.51current
lgpConditionSource1DisconnectOpen
OBJECT-IDENTITY
The system has detected the source 1 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.1current
lgpConditionSource2DisconnectOpen
OBJECT-IDENTITY
The system has detected the source 2 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.2current
lgpConditionSource1PduDisconnectOpen
OBJECT-IDENTITY
The system has detected the source 1 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.3current
lgpConditionSource2PduDisconnectOpen
OBJECT-IDENTITY
The system has detected the source 2 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.4current
lgpConditionOutputToLoadDisconnect1Open
OBJECT-IDENTITY
The system has detected Output to load disconnect 1 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.5current
lgpConditionOutputToLoadDisconnect2Open
OBJECT-IDENTITY
The system has detected Output to load disconnect 2 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.6current
lgpConditionSource1BypassDisconnectClosed
OBJECT-IDENTITY
The system has detected the source 1 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.7current
lgpConditionSource2BypassDisconnectClosed
OBJECT-IDENTITY
The system has detected the source 2 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.8current
lgpConditionOutputToLoadNeutralDisconnectOpen
OBJECT-IDENTITY
The system has detected the output to load neutral disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.9current
lgpConditionBatteryDisconnectOpen
OBJECT-IDENTITY
The system has detected the battery disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.10current
lgpConditionBatteryDiscOpenCab01
OBJECT-IDENTITY
The system has detected the cabinet 1 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.1current
lgpConditionBatteryDiscOpenCab02
OBJECT-IDENTITY
The system has detected the cabinet 2 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.2current
lgpConditionBatteryDiscOpenCab03
OBJECT-IDENTITY
The system has detected the cabinet 3 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.3current
lgpConditionBatteryDiscOpenCab04
OBJECT-IDENTITY
The system has detected the cabinet 4 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.4current
lgpConditionBatteryDiscOpenCab05
OBJECT-IDENTITY
The system has detected the cabinet 5 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.5current
lgpConditionBatteryDiscOpenCab06
OBJECT-IDENTITY
The system has detected the cabinet 6 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.6current
lgpConditionBatteryDiscOpenCab07
OBJECT-IDENTITY
The system has detected the cabinet 7 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.7current
lgpConditionBatteryDiscOpenCab08
OBJECT-IDENTITY
The system has detected the cabinet 8 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.8current
lgpConditionInputDisconnectOpen
OBJECT-IDENTITY
The system has detected the input disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.11current
lgpConditionOutputToLoadDisconnectOpen
OBJECT-IDENTITY
The system has detected the Output to load disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.12current
lgpConditionBypassDisconnectOpen
OBJECT-IDENTITY
The system has detected the bypass disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.13current
lgpConditionStaticSwitchDisconnectOpen
OBJECT-IDENTITY
The system has detected the static switch disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.51.14current
lgpConditionBreakerOpenFailure
OBJECT-IDENTITY
A breaker in the system has failed to respond to an Open signal.
1.3.6.1.4.1.476.1.42.3.2.1.51.15current
lgpConditionBreakerCloseFailure
OBJECT-IDENTITY
A breaker in the system has failed to respond to a Close signal.
1.3.6.1.4.1.476.1.42.3.2.1.51.16current
lgpConditionFrequencyDeviation
OBJECT-IDENTITY
This system has detected a frequency deviation condition. The frequency of a source is outside of the pre-determined thresholds for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.52current
lgpConditionSource1FrequencyDeviation
OBJECT-IDENTITY
The frequency for source 1 has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.1current
lgpConditionSource2FrequencyDeviation
OBJECT-IDENTITY
The frequency for source 2 has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.2current
lgpConditionInputFrequencyDeviation
OBJECT-IDENTITY
The frequency for the input has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.3current
lgpConditionOutputToLoadFrequencyDeviation
OBJECT-IDENTITY
The frequency for the output has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.4current
lgpConditionBypassFrequencyDeviation
OBJECT-IDENTITY
The frequency for the bypass input has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.5current
lgpConditionOverCurrent
OBJECT-IDENTITY
This system has detected an over-current condition. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53current
lgpConditionSource1OverCurrent
OBJECT-IDENTITY
The system has detected an over current condition on source 1. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.1current
lgpConditionSource2OverCurrent
OBJECT-IDENTITY
The system has detected an over current condition on source 2. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.2current
lgpConditionOutputToLoadOverCurrent
OBJECT-IDENTITY
The system has detected the output to load is in an over-current condition. The current for the load has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.3current
lgpConditionOutputToLoadOverCurrentPhsA
OBJECT-IDENTITY
The system has detected the output to load on phase A is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.3.1current
lgpConditionOutputToLoadOverCurrentPhsB
OBJECT-IDENTITY
The system has detected the output to load on phase B is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.3.2current
lgpConditionOutputToLoadOverCurrentPhsC
OBJECT-IDENTITY
The system has detected the output to load on phase C is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.3.3current
lgpConditionGroundOverCurrent
OBJECT-IDENTITY
A ground source is experiencing an over-current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.4current
lgpConditionRectifierOverCurrent
OBJECT-IDENTITY
The system has detected a rectifier over current condition. The current for the rectifier has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.5current
lgpConditionInverterOverCurrent
OBJECT-IDENTITY
The system has detected an inverter over current condition. The current for the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.6current
lgpConditionInverterOverCurrentPhsA
OBJECT-IDENTITY
The system has detected an inverter over current condition on phase A. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.6.1current
lgpConditionInverterOverCurrentPhsB
OBJECT-IDENTITY
The system has detected an inverter over current condition on phase B. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.6.2current
lgpConditionInverterOverCurrentPhsC
OBJECT-IDENTITY
The system has detected an inverter over current condition on phase C. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.6.3current
lgpConditionBatteryConverterOverCurrent
OBJECT-IDENTITY
The system has detected an over current condition on the battery converter. The current of the converter has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.7current
lgpConditionBatteryBalancerOverCurrent
OBJECT-IDENTITY
The system has detected a battery balancer over current condition. The current at this point has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.8current
lgpConditionHumidifierOverCurrent
OBJECT-IDENTITY
The system has detected an over current condition on the humidifier. The current of the humidifier has risen above a pre-determined threshold for a defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.9current
lgpConditionInputOverCurrent
OBJECT-IDENTITY
There is an over current condition on the system input power. The input current has risen above a pre-determined threshold for a pre-defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.10current
lgpConditionSource1NeutralOverCurrent
OBJECT-IDENTITY
The system has detected an over current condition on the neutral line of source 1. The neutral current at source 1 has risen above a pre-determined threshold for a pre-defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.11current
lgpConditionSource2NeutralOverCurrent
OBJECT-IDENTITY
The system has detected an over current condition on the neutral line of source 2. The neutral current at source 2 has risen above a pre-determined threshold for a pre-defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.12current
lgpConditionSensorFailure
OBJECT-IDENTITY
This system has detected a sensor failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.54current
lgpConditionOutputToLoadVoltageSensorFailure
OBJECT-IDENTITY
The system had detected an output to load voltage sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.1current
lgpConditionSource1VoltageSensorFailure
OBJECT-IDENTITY
The system had detected a source 1 voltage sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.2current
lgpConditionSource2VoltageSensorFailure
OBJECT-IDENTITY
The system had detected a source 2 voltage sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.3current
lgpConditionSource1ScrSensorFailure
OBJECT-IDENTITY
The system had detected a source 1 SCR (Silicon Controlled Rectifier) sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.4current
lgpConditionSource2ScrSensorFailure
OBJECT-IDENTITY
The system had detected a source 2 SCR (Silicon Controlled Rectifier) sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.5current
lgpConditionSource1CurrentSensorFailure
OBJECT-IDENTITY
The system has detected a source 1 current sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.6current
lgpConditionSource2CurrentSensorFailure
OBJECT-IDENTITY
The system has detected a source 2 current sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.7current
lgpConditionRoomTempHumiditySensorFailure
OBJECT-IDENTITY
The system has detected a device temperature and humidity sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.8current
lgpConditionGlycolTempSensorFailure
OBJECT-IDENTITY
The system has detected a glycol temperature sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.9current
lgpConditionLocal1SensorFailure
OBJECT-IDENTITY
The system has detected a local 1 sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.10current
lgpConditionCompressor1SensorFailure
OBJECT-IDENTITY
The system has detected a compressor 1 digital scroll sensor failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.54.11current
lgpConditionCompressor2SensorFailure
OBJECT-IDENTITY
The system has detected a compressor 2 digital scroll sensor failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.54.12current
lgpConditionSupplySensorFailure
OBJECT-IDENTITY
The system has detected a supply sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.13current
lgpConditionCabinetTemperatureSensorFailure
OBJECT-IDENTITY
The system has detected a cabinet temperature sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.14current
lgpConditionCabinetHumiditySensorFailure
OBJECT-IDENTITY
The system has detected a cabinet humidity sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.15current
lgpConditionRoomTempSensorFailure
OBJECT-IDENTITY
The system has detected a room temperature sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.16current
lgpConditionBatteryTempSensorFailure
OBJECT-IDENTITY
The system has detected a battery temperature sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.17current
lgpConditionAirSensorAFailure
OBJECT-IDENTITY
The system has detected a failure with air sensor A. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.18current
lgpConditionAirSensorBFailure
OBJECT-IDENTITY
The system has detected a failure with air sensor B. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.19current
lgpConditionChilledWaterSupplySensorFailure
OBJECT-IDENTITY
The system has detected a failure with the chilled water supply sensor. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.20current
lgpConditionRefrigerantSupplySensorFailure
OBJECT-IDENTITY
The system has detected a failure with the refrigerant supply sensor. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.21current
lgpConditionFluidSupplySensorFailure
OBJECT-IDENTITY
The system has detected a failure with the fluid supply sensor. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.22current
lgpConditionCompressorLowPressureSensorFailure
OBJECT-IDENTITY
The system has detected that a compressor low pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.23current
lgpConditionCompressor1LowPressureSensorFailure
OBJECT-IDENTITY
The system has detected that compressor 1 low pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.23.1current
lgpConditionRemoteSensorFailure
OBJECT-IDENTITY
The system has detected that a remote sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.24current
lgpConditionAirSupplyTempSensorFailure
OBJECT-IDENTITY
The system has detected that the supply air temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.25current
lgpConditionAirReturnTempSensorFailure
OBJECT-IDENTITY
The system has detected that the return air temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.26current
lgpConditionCompressorHighPressureSensorFailure
OBJECT-IDENTITY
The system has detected that a compressor high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.27current
lgpConditionCompressor2HighPressureSensorFailure
OBJECT-IDENTITY
The system has detected that compressor 2 high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.27.2current
lgpConditionCompressor3HighPressureSensorFailure
OBJECT-IDENTITY
The system has detected that compressor 3 high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.27.3current
lgpConditionCompressor4HighPressureSensorFailure
OBJECT-IDENTITY
The system has detected that compressor 4 high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.27.4current
lgpConditionInternalCommunicationFailure
OBJECT-IDENTITY
This system has detected an internal communication failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.55current
lgpConditionExternalCommunicationFailure
OBJECT-IDENTITY
This system has detected an external communication failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.56current
lgpConditionSourceGateDriveFailure
OBJECT-IDENTITY
This system has detected a source gate drive failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.57current
lgpConditionSource1GateDriveFailure
OBJECT-IDENTITY
The system has detected a source 1 gate drive failure.
1.3.6.1.4.1.476.1.42.3.2.1.57.1current
lgpConditionSource2GateDriveFailure
OBJECT-IDENTITY
The system has detected a source 2 gate drive failure.
1.3.6.1.4.1.476.1.42.3.2.1.57.2current
lgpConditionDisconnectFailure
OBJECT-IDENTITY
This system has detected a disconnect failure condition. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.58current
lgpConditionOutputToLoadNeutralDisconnectFailure
OBJECT-IDENTITY
The system has detected the output to load neutral disconnect has failed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.58.1current
lgpConditionSource1DisconnectShuntTripFailure
OBJECT-IDENTITY
The system has detected a shunt trip failure of a disconnecting device on source 1. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.58.2current
lgpConditionSource2DisconnectShuntTripFailure
OBJECT-IDENTITY
The system has detected a shunt trip failure of a disconnecting device on source 2. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.58.3current
lgpConditionInverterDisconnectFailure
OBJECT-IDENTITY
The system has detected an inverter disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.58.4current
lgpConditionBatteryDisconnectFailure
OBJECT-IDENTITY
The system has detected a battery disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.58.5current
lgpConditionRectifierDisconnectFailure
OBJECT-IDENTITY
The system has detected a rectifier disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
1.3.6.1.4.1.476.1.42.3.2.1.58.6current
lgpConditionOverTemperature
OBJECT-IDENTITY
This system has detected an over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59current
lgpConditionHeatSink1OverTemperature
OBJECT-IDENTITY
The system has detected a heat sink 1 over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59.1current
lgpConditionAmbient1OverTemperature
OBJECT-IDENTITY
The system has detected an ambient over temperature condition at location 1.
1.3.6.1.4.1.476.1.42.3.2.1.59.2current
lgpConditionSystemOverTemperature
OBJECT-IDENTITY
The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.59.3current
lgpConditionTransformerOverTemperature
OBJECT-IDENTITY
The transformer is experiencing an over temperature condition. The transformer's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.59.4current
lgpConditionBatteryOverTemperature
OBJECT-IDENTITY
The battery is experiencing an over temperature condition. The battery's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.59.5current
lgpConditionRectifierOverTemperature
OBJECT-IDENTITY
The system has detected a rectifier over temperature condition. The rectifier's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.59.6current
lgpConditionInverterOverTemperature
OBJECT-IDENTITY
The system has detected an inverter over temperature condition. The inverter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.59.7current
lgpConditionRectifierInductorOverTemperature
OBJECT-IDENTITY
The system has detected a rectifier inductor over temperature condition. The rectifier's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.59.8current
lgpConditionInverterInductorOverTemperature
OBJECT-IDENTITY
The system has detected an inverter inductor over temperature condition. The inverter's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.59.9current
lgpConditionBatteryConverterOverTemperature
OBJECT-IDENTITY
The system has detected a battery converter over temperature condition. The battery converter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.59.10current
lgpConditionBatteryBalancerInductorOverTemperature
OBJECT-IDENTITY
The system has detected a battery balancer Inductor over temperature condition. The battery balancer Inductor's temperature has exceeded a pre-determined threshold for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.59.11current
lgpConditionChilledWaterOverTemperature
OBJECT-IDENTITY
The system has detected a chilled water over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59.12current
lgpConditionElectricHeatersOverTemperature
OBJECT-IDENTITY
The system has detected an electric heater over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59.13current
lgpConditionInletAirOverTemperature
OBJECT-IDENTITY
The system has detected an inlet air over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59.14current
lgpConditionSystemOverTempWarning
OBJECT-IDENTITY
The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a normal operating range for a device, or system, defined amount of time. The system is still operational but a threshold has been exceeded.
1.3.6.1.4.1.476.1.42.3.2.1.59.15current
lgpConditionHighTemperatureBattString
OBJECT-IDENTITY
The system has detected a high temperature on a battery string. The temperature has exceeded a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.59.16current
lgpConditionLoadOnAlternateSource
OBJECT-IDENTITY
The system has detected that the load is being supplied by the alternate source.
1.3.6.1.4.1.476.1.42.3.2.1.60current
lgpConditionPhaseRotationError
OBJECT-IDENTITY
This system has detected a phase rotation error condition.
1.3.6.1.4.1.476.1.42.3.2.1.61current
lgpConditionSource1PhaseRotationError
OBJECT-IDENTITY
The system has detected a phase rotation error on source 1.
1.3.6.1.4.1.476.1.42.3.2.1.61.1current
lgpConditionSource2PhaseRotationError
OBJECT-IDENTITY
The system has detected a phase rotation error on source 2.
1.3.6.1.4.1.476.1.42.3.2.1.61.2current
lgpConditionBypassPhaseRotationError
OBJECT-IDENTITY
The system has detected a phase rotation error on the bypass.
1.3.6.1.4.1.476.1.42.3.2.1.61.3current
lgpConditionInputPhaseRotationError
OBJECT-IDENTITY
The system has detected a phase rotation error on the input.
1.3.6.1.4.1.476.1.42.3.2.1.61.4current
lgpConditionControlModuleFailure
OBJECT-IDENTITY
This system has detected a control module failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.62current
lgpConditionControlModule1Failure
OBJECT-IDENTITY
The system has detected a control module 1 failure.
1.3.6.1.4.1.476.1.42.3.2.1.62.1current
lgpConditionHistoryLogFull
OBJECT-IDENTITY
The system has detected the history log is full.
1.3.6.1.4.1.476.1.42.3.2.1.63current
lgpConditionConfigurationModified
OBJECT-IDENTITY
The system has detected the configuration has been modified.
1.3.6.1.4.1.476.1.42.3.2.1.64current
lgpConditionPasswordModified
OBJECT-IDENTITY
The system has detected the password has been modified.
1.3.6.1.4.1.476.1.42.3.2.1.65current
lgpConditionTimeModified
OBJECT-IDENTITY
The system has detected the time has been modified.
1.3.6.1.4.1.476.1.42.3.2.1.66current
lgpConditionDateModified
OBJECT-IDENTITY
The system has detected the date has been modified.
1.3.6.1.4.1.476.1.42.3.2.1.67current
lgpConditionEventLogCleared
OBJECT-IDENTITY
The system has detected the event log has been cleared.
1.3.6.1.4.1.476.1.42.3.2.1.68current
lgpConditionHistoryLogCleared
OBJECT-IDENTITY
The system has detected the history log has been cleared.
1.3.6.1.4.1.476.1.42.3.2.1.69current
lgpConditionUtilityFailure
OBJECT-IDENTITY
The system has detected a utility failure.
1.3.6.1.4.1.476.1.42.3.2.1.70current
lgpConditionBatteryTestInProgress
OBJECT-IDENTITY
The system is performing a battery test at this time.
1.3.6.1.4.1.476.1.42.3.2.1.71current
lgpConditionLoadOnBattery
OBJECT-IDENTITY
The system load is being supported by the battery.
1.3.6.1.4.1.476.1.42.3.2.1.72current
lgpConditionReplaceBattery
OBJECT-IDENTITY
The system has detected the batteries are due to be replaced.
1.3.6.1.4.1.476.1.42.3.2.1.74current
lgpConditionUpsShutdownPending
OBJECT-IDENTITY
The system is in a shutdown pending condition.
1.3.6.1.4.1.476.1.42.3.2.1.75current
lgpConditionBatteryChargerFailed
OBJECT-IDENTITY
The system has detected the battery charger has failed.
1.3.6.1.4.1.476.1.42.3.2.1.76current
lgpConditionBypassVoltageUnqualified
OBJECT-IDENTITY
The system has detected the bypass voltage is unqualified. The voltage measurement is outside a pre-determined threshold range for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.77current
lgpConditionCheckAirFilter
OBJECT-IDENTITY
The system has detected it is time to check the air filter.
1.3.6.1.4.1.476.1.42.3.2.1.78current
lgpConditionBrownOut
OBJECT-IDENTITY
The system has detected a brown out condition.
1.3.6.1.4.1.476.1.42.3.2.1.79current
lgpConditionMultipleTransferLockout
OBJECT-IDENTITY
The system has locked out transfers to bypass. Too many transfers have occurred over a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.80current
lgpConditionBypassPhaseLost
OBJECT-IDENTITY
The system has detected one or more bypass phases are missing.
1.3.6.1.4.1.476.1.42.3.2.1.81current
lgpConditionMaintenceBypassInhibited
OBJECT-IDENTITY
The system is preventing a transfer of the load to maintenance bypass.
1.3.6.1.4.1.476.1.42.3.2.1.82current
lgpConditionLoadLockedOnBypass
OBJECT-IDENTITY
An error has been detected requiring the system to be put into a 'locked on bypass' state.
1.3.6.1.4.1.476.1.42.3.2.1.83current
lgpConditionOutputToLoadShort
OBJECT-IDENTITY
The system has detected an output to load short circuit condition.
1.3.6.1.4.1.476.1.42.3.2.1.84current
lgpConditionEmergencyTransferToInverter
OBJECT-IDENTITY
The system has detected an emergency transfer of the load to inverter.
1.3.6.1.4.1.476.1.42.3.2.1.85current
lgpConditonEmergencyPowerOff
OBJECT-IDENTITY
The system has detected an Emergency Power Off (EPO) condition. An external EPO switch has cut off the power source to the system.
1.3.6.1.4.1.476.1.42.3.2.1.86current
lgpConditionInverterBackFeed
OBJECT-IDENTITY
The system has detected an inverter back-feed condition. The inverter is feeding power through the bypass back to the input.
1.3.6.1.4.1.476.1.42.3.2.1.87current
lgpConditionDcGroundFault
OBJECT-IDENTITY
The system has detected a DC ground fault.
1.3.6.1.4.1.476.1.42.3.2.1.88current
lgpConditionDcGroundFaultPos
OBJECT-IDENTITY
Ground fault current has been detected in the positive DC link to ground.
1.3.6.1.4.1.476.1.42.3.2.1.88.1current
lgpConditionDcGroundFaultNeg
OBJECT-IDENTITY
Ground fault current has been detected in the negative DC link to ground.
1.3.6.1.4.1.476.1.42.3.2.1.88.2current
lgpConditionStaticTransferSwitchInhibited
OBJECT-IDENTITY
The system is preventing the use of the static transfer switch.
1.3.6.1.4.1.476.1.42.3.2.1.89current
lgpConditionBatteryLogFullWarning
OBJECT-IDENTITY
The system has detected the battery log is approaching the maximum record limit.
1.3.6.1.4.1.476.1.42.3.2.1.90current
lgpConditionInputCurrentUnbalanced
OBJECT-IDENTITY
The system has detected an unbalanced input current condition. The currents of input phases are out of tolerance.
1.3.6.1.4.1.476.1.42.3.2.1.91current
lgpConditionSelfTestFailed
OBJECT-IDENTITY
The system has detected a self-test failure.
1.3.6.1.4.1.476.1.42.3.2.1.92current
lgpConditionInverterOutOfSynchronization
OBJECT-IDENTITY
The system has detected an Inverter out of sync condition.
1.3.6.1.4.1.476.1.42.3.2.1.93current
lgpConditionModuleAlarm
OBJECT-IDENTITY
This system has detected an alarm within the multi-module system.
1.3.6.1.4.1.476.1.42.3.2.1.94current
lgpConditioniModuleUnit1Alarm
OBJECT-IDENTITY
The multi-module system has detected an alarm condition on unit 1.
1.3.6.1.4.1.476.1.42.3.2.1.94.1current
lgpConditioniModuleUnit2Alarm
OBJECT-IDENTITY
The multi-module system has detected an alarm condition on unit 2.
1.3.6.1.4.1.476.1.42.3.2.1.94.2current
lgpConditioniModuleUnit3Alarm
OBJECT-IDENTITY
The multi-module system has detected an alarm condition on unit 3.
1.3.6.1.4.1.476.1.42.3.2.1.94.3current
lgpConditioniModuleUnit4Alarm
OBJECT-IDENTITY
The multi-module system has detected an alarm condition on unit 4.
1.3.6.1.4.1.476.1.42.3.2.1.94.4current
lgpConditioniModuleUnit5Alarm
OBJECT-IDENTITY
The multi-module system has detected an alarm condition on unit 5.
1.3.6.1.4.1.476.1.42.3.2.1.94.5current
lgpConditioniModuleUnit6Alarm
OBJECT-IDENTITY
The multi-module system has detected an alarm condition on unit 6.
1.3.6.1.4.1.476.1.42.3.2.1.94.6current
lgpConditioniModuleUnit7Alarm
OBJECT-IDENTITY
The multi-module system has detected an alarm condition on unit 7.
1.3.6.1.4.1.476.1.42.3.2.1.94.7current
lgpConditioniModuleUnit8Alarm
OBJECT-IDENTITY
The multi-module system has detected an alarm condition on unit 8.
1.3.6.1.4.1.476.1.42.3.2.1.94.8current
lgpConditionActiveModuleAlarm
OBJECT-IDENTITY
The system has detected an active alarm in one, or more, of the sub-modules of the multi-module system.
1.3.6.1.4.1.476.1.42.3.2.1.95current
lgpConditionControlFailure
OBJECT-IDENTITY
This system has detected a control failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.96current
lgpConditionMainControlFailure
OBJECT-IDENTITY
The system has detected a main control failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.96.1current
lgpConditionRedundantControlFailure
OBJECT-IDENTITY
The system has detected a redundant control failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.96.2current
lgpConditionParallelSysControlFailure
OBJECT-IDENTITY
The parallel system has detected a control failure condition with one of the controls.
1.3.6.1.4.1.476.1.42.3.2.1.96.3current
lgpConditionMainControlCommFailure
OBJECT-IDENTITY
One or more communications failures have occurred in the main control.
1.3.6.1.4.1.476.1.42.3.2.1.96.4current
lgpConditionControlBoardFailure
OBJECT-IDENTITY
The system has detected a control board failure.
1.3.6.1.4.1.476.1.42.3.2.1.96.5current
lgpConditionHumidifierControlBdFailure
OBJECT-IDENTITY
Humidifier control board is required to be connected, but no signal is detected.
1.3.6.1.4.1.476.1.42.3.2.1.96.5.1current
lgpConditionControlWarning
OBJECT-IDENTITY
This system has detected a control warning conditions.
1.3.6.1.4.1.476.1.42.3.2.1.97current
lgpConditionMainControlWarning
OBJECT-IDENTITY
The system has detected a main control warning condition.
1.3.6.1.4.1.476.1.42.3.2.1.97.1current
lgpConditionRedundantControlWarning
OBJECT-IDENTITY
The system has detected a redundant control warning condition.
1.3.6.1.4.1.476.1.42.3.2.1.97.2current
lgpConditionUserInterfaceFailure
OBJECT-IDENTITY
The system has detected a user interface control failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.98current
lgpConditionLostPowerRedundancy
OBJECT-IDENTITY
The system has detected the number of redundant power modules has fallen below the minimum redundant power module setting.
1.3.6.1.4.1.476.1.42.3.2.1.99current
lgpConditionPowerModuleFailure
OBJECT-IDENTITY
The system has detected a power module failure condition in the system.
1.3.6.1.4.1.476.1.42.3.2.1.100current
lgpConditionBatteryModuleFailure
OBJECT-IDENTITY
The system has detected a battery module failure condition in the system.
1.3.6.1.4.1.476.1.42.3.2.1.101current
lgpConditionOutputToLoadOff
OBJECT-IDENTITY
The system has detected that there is no power being supplied to the load.
1.3.6.1.4.1.476.1.42.3.2.1.102current
lgpConditionSystemOff
OBJECT-IDENTITY
The system is off.
1.3.6.1.4.1.476.1.42.3.2.1.103current
lgpConditionRectifierStartupFailure
OBJECT-IDENTITY
The system has detected a rectifier under voltage start-up failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.104current
lgpConditionRectifierFault
OBJECT-IDENTITY
The system has detected a rectifier fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.105current
lgpConditionInverterShutdownLowDc
OBJECT-IDENTITY
The system has shutdown the inverter due to a DC bus under voltage.
1.3.6.1.4.1.476.1.42.3.2.1.106current
lgpConditionInverterFault
OBJECT-IDENTITY
The system has detected an inverter fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.107current
lgpConditionInverterDcOffsetOverrun
OBJECT-IDENTITY
The system has detected an over run of the inverter DC offset voltage.
1.3.6.1.4.1.476.1.42.3.2.1.108current
lgpConditionParallelSysLowBatteryWarning
OBJECT-IDENTITY
The parallel system has detected a low battery warning condition.
1.3.6.1.4.1.476.1.42.3.2.1.109current
lgpConditionParallelSysLoadShareFault
OBJECT-IDENTITY
The parallel system has detected a load share fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.110current
lgpConditionBatteryFault
OBJECT-IDENTITY
The system has detected a battery fault condition. The battery conductors are either reversed or disconnected.
1.3.6.1.4.1.476.1.42.3.2.1.111current
lgpConditionBatteryConverterFailure
OBJECT-IDENTITY
The system has detected a battery converter failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.112current
lgpConditionBatteryBalancerFault
OBJECT-IDENTITY
The system has detected a battery balancer fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.113current
lgpConditionpsUpsOperationFault
OBJECT-IDENTITY
The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
1.3.6.1.4.1.476.1.42.3.2.1.114deprecated
lgpConditionOutputToLoadOnJointMode
OBJECT-IDENTITY
The system load is being supported by both the battery and rectifier.
1.3.6.1.4.1.476.1.42.3.2.1.115current
lgpConditionInputNeutralLost
OBJECT-IDENTITY
The system had detected the main input neutral is disconnected.
1.3.6.1.4.1.476.1.42.3.2.1.116current
lgpConditionLowBatteryWarning
OBJECT-IDENTITY
The battery's remaining charge is less than or equal to the configured low threshold.
1.3.6.1.4.1.476.1.42.3.2.1.117current
lgpConditionInternalFault
OBJECT-IDENTITY
The system has detected an internal fault.
1.3.6.1.4.1.476.1.42.3.2.1.118current
lgpConditionBatteryTestFailed
OBJECT-IDENTITY
The system has detected a battery self-test failure.
1.3.6.1.4.1.476.1.42.3.2.1.119current
lgpConditionPowerModuleWarning
OBJECT-IDENTITY
The system has detected an alarm condition on one, or more, power modules.
1.3.6.1.4.1.476.1.42.3.2.1.120current
lgpConditionBatteryModuleWarning
OBJECT-IDENTITY
The system has detected an alarm condition on one, or more, battery modules.
1.3.6.1.4.1.476.1.42.3.2.1.121current
lgpConditionControlModuleWarning
OBJECT-IDENTITY
The system has detected a control module warning.
1.3.6.1.4.1.476.1.42.3.2.1.122current
lgpConditionUpsOperationFault
OBJECT-IDENTITY
The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
1.3.6.1.4.1.476.1.42.3.2.1.123current
lgpConditionActiveAlarm
OBJECT-IDENTITY
The system has detected an alarm condition.
1.3.6.1.4.1.476.1.42.3.2.1.124current
lgpConditionRectifierCommunicationFailure
OBJECT-IDENTITY
The system has detected an internal communication failure condition with the rectifier.
1.3.6.1.4.1.476.1.42.3.2.1.125current
lgpConditionInverterCommunicationFailure
OBJECT-IDENTITY
The system has detected an internal communication failure condition with the inverter.
1.3.6.1.4.1.476.1.42.3.2.1.126current
lgpConditionParallelSysConnectionFault
OBJECT-IDENTITY
The parallel system has detected a connection fault. One or more of the devices are not properly connected.
1.3.6.1.4.1.476.1.42.3.2.1.127current
lgpConditionParallelSysCommunicationFailure
OBJECT-IDENTITY
The parallel system has detected a communication failure.
1.3.6.1.4.1.476.1.42.3.2.1.128current
lgpConditionLostBatteryRedundancy
OBJECT-IDENTITY
The system has detected the number of redundant battery modules has fallen below the configured redundant battery module threshold.
1.3.6.1.4.1.476.1.42.3.2.1.129current
lgpConditionCompPumpDownFailure
OBJECT-IDENTITY
The system has detected that a compressor has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.130current
lgpConditionComp1PumpDownFailure
OBJECT-IDENTITY
The system has detected that compressor 1 has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.130.1current
lgpConditionComp2PumpDownFailure
OBJECT-IDENTITY
The system has detected that compressor 2 has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.130.2current
lgpConditionComp3PumpDownFailure
OBJECT-IDENTITY
The system has detected that compressor 3 has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.130.3current
lgpConditionComp4PumpDownFailure
OBJECT-IDENTITY
The system has detected that compressor 4 has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.130.4current
lgpConditionChilledWaterLowWaterFlow
OBJECT-IDENTITY
The system has detected a chilled water low water flow condition.
1.3.6.1.4.1.476.1.42.3.2.1.131current
lgpConditionChilledWaterLowWaterFlowCircuit2
OBJECT-IDENTITY
The system has detected a chilled water low water flow condition for circuit 2.
1.3.6.1.4.1.476.1.42.3.2.1.131.2current
lgpConditionAirFilterClogged
OBJECT-IDENTITY
The system has detected a air filter clogged condition.
1.3.6.1.4.1.476.1.42.3.2.1.132deprecated
lgpConditionHumidifierFailure
OBJECT-IDENTITY
The system has detected a humidifier failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.133current
lgpConditionRunHoursExceeded
OBJECT-IDENTITY
The system has detected a pre-determined run hours threshold has been exceeded.
1.3.6.1.4.1.476.1.42.3.2.1.134current
lgpConditionUnitRunHrsExceeded
OBJECT-IDENTITY
The system has detected the system run hours has exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.1current
lgpConditionComp1RunHrsExceeded
OBJECT-IDENTITY
The system has detected the compressor 1 run hours has exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.2current
lgpConditionComp2RunHrsExceeded
OBJECT-IDENTITY
The system has detected the compressor 2 run hours has exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.3current
lgpConditionFreeCoolRunHrsExceeded
OBJECT-IDENTITY
The system has detected the free cooling run hours has exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.4current
lgpConditionElectricalHeater1RunHrsExceeded
OBJECT-IDENTITY
The system has detected the electrical heater's run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.5current
lgpConditionElectricalHeater2RunHrsExceeded
OBJECT-IDENTITY
The system has detected the electrical heater's run hours have exceeded the pre-determined limit.
1.3.6.1.4.1.476.1.42.3.2.1.134.6current
lgpConditionElectricalHeater3RunHrsExceeded
OBJECT-IDENTITY
The system has detected the electrical heater's run hours have exceeded the pre-determined limit.
1.3.6.1.4.1.476.1.42.3.2.1.134.7current
lgpConditionHotWaterRunHrsExceeded
OBJECT-IDENTITY
The system has detected the hot water run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.8current
lgpConditionHotGasRunHrsExceeded
OBJECT-IDENTITY
The system has detected the hot gas run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.9current
lgpConditionHumidifierRunHrsExceeded
OBJECT-IDENTITY
The system has detected the humidifier run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.10current
lgpConditionDehumidiferRunHrsExceeded
OBJECT-IDENTITY
The system has detected the dehumidifier run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.11current
lgpConditionFanRunHrsExceeded
OBJECT-IDENTITY
The system has detected the unit blower fan run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.12current
lgpConditionCommWarning
OBJECT-IDENTITY
The system has detected a loss of communications with another module.
1.3.6.1.4.1.476.1.42.3.2.1.135current
lgpConditionCommWarningUnit1
OBJECT-IDENTITY
The system has detected a loss of communications with unit 1.
1.3.6.1.4.1.476.1.42.3.2.1.135.1current
lgpConditionCommWarningUnit2
OBJECT-IDENTITY
The system has detected a loss of communications with unit 2.
1.3.6.1.4.1.476.1.42.3.2.1.135.2current
lgpConditionCommWarningUnit3
OBJECT-IDENTITY
The system has detected a loss of communications with unit 3.
1.3.6.1.4.1.476.1.42.3.2.1.135.3current
lgpConditionCommWarningUnit4
OBJECT-IDENTITY
The system has detected a loss of communications with unit 4.
1.3.6.1.4.1.476.1.42.3.2.1.135.4current
lgpConditionCommWarningUnit5
OBJECT-IDENTITY
The system has detected a loss of communications with unit 5.
1.3.6.1.4.1.476.1.42.3.2.1.135.5current
lgpConditionCommWarningUnit6
OBJECT-IDENTITY
The system has detected a loss of communications with unit 6.
1.3.6.1.4.1.476.1.42.3.2.1.135.6current
lgpConditionCommWarningUnit7
OBJECT-IDENTITY
The system has detected a loss of communications with unit 7.
1.3.6.1.4.1.476.1.42.3.2.1.135.7current
lgpConditionCommWarningUnit8
OBJECT-IDENTITY
The system has detected a loss of communications with unit 8.
1.3.6.1.4.1.476.1.42.3.2.1.135.8current
lgpConditionCommWarningUnit9
OBJECT-IDENTITY
The system has detected a loss of communications with unit 9.
1.3.6.1.4.1.476.1.42.3.2.1.135.9current
lgpConditionCommWarningUnit10
OBJECT-IDENTITY
The system has detected a loss of communications with unit 10.
1.3.6.1.4.1.476.1.42.3.2.1.135.10current
lgpConditionCommWarningUnit11
OBJECT-IDENTITY
The system has detected a loss of communications with unit 11.
1.3.6.1.4.1.476.1.42.3.2.1.135.11current
lgpConditionCommWarningUnit12
OBJECT-IDENTITY
The system has detected a loss of communications with unit 12.
1.3.6.1.4.1.476.1.42.3.2.1.135.12current
lgpConditionCommWarningUnit13
OBJECT-IDENTITY
The system has detected a loss of communications with unit 13.
1.3.6.1.4.1.476.1.42.3.2.1.135.13current
lgpConditionCommWarningUnit14
OBJECT-IDENTITY
The system has detected a loss of communications with unit 14.
1.3.6.1.4.1.476.1.42.3.2.1.135.14current
lgpConditionCommWarningUnit15
OBJECT-IDENTITY
The system has detected a loss of communications with unit 15.
1.3.6.1.4.1.476.1.42.3.2.1.135.15current
lgpConditionCommWarningUnit16
OBJECT-IDENTITY
The system has detected a loss of communications with unit 16.
1.3.6.1.4.1.476.1.42.3.2.1.135.16current
lgpConditionUnitOn
OBJECT-IDENTITY
The unit is on.
1.3.6.1.4.1.476.1.42.3.2.1.136current
lgpConditionUnitOff
OBJECT-IDENTITY
The unit is off.
1.3.6.1.4.1.476.1.42.3.2.1.137current
lgpConditionSleepModeOff
OBJECT-IDENTITY
The system sleep mode operation has been turned off.
1.3.6.1.4.1.476.1.42.3.2.1.138current
lgpConditionPowerOn
OBJECT-IDENTITY
The system power is on.
1.3.6.1.4.1.476.1.42.3.2.1.139current
lgpConditionSystemOnStanby
OBJECT-IDENTITY
The system is on standby.
1.3.6.1.4.1.476.1.42.3.2.1.140current
lgpConditionPowerOff
OBJECT-IDENTITY
The system power is off.
1.3.6.1.4.1.476.1.42.3.2.1.141current
lgpConditionHighTemperatureGroup
OBJECT-IDENTITY
The system has detected a high temperature condition. This group contains various high temperature conditions.
1.3.6.1.4.1.476.1.42.3.2.1.142current
lgpConditionHighTemperatureSensor1
OBJECT-IDENTITY
The temperature has exceeded the high temperature threshold for sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.142.1current
lgpConditionHighTemperatureDigitalScroll1
OBJECT-IDENTITY
The system has detected a high temperature event on Digital Scroll Compressor 1. The temperature has exceeded a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.142.2current
lgpConditionHighTemperatureDigitalScroll2
OBJECT-IDENTITY
The system has detected a high temperature event on Digital Scroll Compressor 2. The temperature has exceeded a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.142.3current
lgpConditionHighTemperatureUser1
OBJECT-IDENTITY
The temperature has exceeded the high temperature threshold for user configured temperature sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.142.4current
lgpConditionHighTemperatureInternal
OBJECT-IDENTITY
The system has detected a high internal temperature condition. The temperature has exceeded a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.142.5current
lgpConditionHighTemperatureExternalAirSensorA
OBJECT-IDENTITY
The temperature has exceeded the high temperature threshold for external air sensor A.
1.3.6.1.4.1.476.1.42.3.2.1.142.6current
lgpConditionHighTemperatureExternalAirSensorB
OBJECT-IDENTITY
The temperature has exceeded the high temperature threshold for external air sensor B.
1.3.6.1.4.1.476.1.42.3.2.1.142.7current
lgpConditionHighTemperatureRefrigerantSupply
OBJECT-IDENTITY
The temperature has exceeded the high temperature threshold for the refrigerant supply.
1.3.6.1.4.1.476.1.42.3.2.1.142.8current
lgpConditionHighTemperatureFluidSupply
OBJECT-IDENTITY
The temperature has exceeded the high temperature threshold for the fluid supply.
1.3.6.1.4.1.476.1.42.3.2.1.142.9current
lgpConditionHighTemperatureSupplyAir
OBJECT-IDENTITY
The temperature has exceeded the high temperature threshold for the supply air.
1.3.6.1.4.1.476.1.42.3.2.1.142.10current
lgpConditionHighTemperatureReturnAir
OBJECT-IDENTITY
The temperature has exceeded the high temperature threshold for the return air.
1.3.6.1.4.1.476.1.42.3.2.1.142.11current
lgpConditionLowTemperatureGroup
OBJECT-IDENTITY
The system has detected a low temperature condition. This group contains various low temperature conditions.
1.3.6.1.4.1.476.1.42.3.2.1.143current
lgpConditionLowTemperatureSensor1
OBJECT-IDENTITY
The temperature is below the low temperature threshold for sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.143.1current
lgpConditionLowTemperatureInternal
OBJECT-IDENTITY
The system has detected a low internal temperature condition. The temperature is below a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.143.2current
lgpConditionLowTemperatureExternalAirSensorA
OBJECT-IDENTITY
The temperature is below the low temperature threshold for external air sensor A.
1.3.6.1.4.1.476.1.42.3.2.1.143.3current
lgpConditionLowTemperatureExternalAirSensorB
OBJECT-IDENTITY
The temperature is below the low temperature threshold for external air sensor B.
1.3.6.1.4.1.476.1.42.3.2.1.143.4current
lgpConditionLowTemperatureRefrigerantSupply
OBJECT-IDENTITY
The temperature is below the low temperature threshold for the refrigerant supply.
1.3.6.1.4.1.476.1.42.3.2.1.143.5current
lgpConditionLowTemperatureFluidSupply
OBJECT-IDENTITY
The temperature is below the low temperature threshold for the fluid supply.
1.3.6.1.4.1.476.1.42.3.2.1.143.6current
lgpConditionLowTemperatureSupplyAir
OBJECT-IDENTITY
The temperature is below the low temperature threshold for the supply air.
1.3.6.1.4.1.476.1.42.3.2.1.143.7current
lgpConditionHighHumidityGroup
OBJECT-IDENTITY
The system has detected a high humidity condition. This group contains various high humidity conditions.
1.3.6.1.4.1.476.1.42.3.2.1.144current
lgpConditionHighHumiditySensor1
OBJECT-IDENTITY
The humidity has exceeded the high humidity threshold for sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.144.1current
lgpConditionHighHumidityReturnAir
OBJECT-IDENTITY
The humidity has exceeded the high humidity threshold for the return air.
1.3.6.1.4.1.476.1.42.3.2.1.144.2current
lgpConditionLowHumidityGroup
OBJECT-IDENTITY
The system has detected a low humidity condition. This group contains various high humidity conditions.
1.3.6.1.4.1.476.1.42.3.2.1.145current
lgpConditionLowHumiditySensor1
OBJECT-IDENTITY
The humidity is below the low humidity threshold for sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.145.1current
lgpConditionLowHumidityReturnAir
OBJECT-IDENTITY
The humidity is below the low humidity threshold for the return air.
1.3.6.1.4.1.476.1.42.3.2.1.145.2current
lgpConditionPeerNetworkNoMaster
OBJECT-IDENTITY
The system is unable to communicate with the master on the peer to peer network.
1.3.6.1.4.1.476.1.42.3.2.1.146current
lgpConditionNoOnOffPermissions
OBJECT-IDENTITY
The system lacks the permissions to execute the on/off operation.
1.3.6.1.4.1.476.1.42.3.2.1.147current
lgpConditionPeerNetworkFailure
OBJECT-IDENTITY
The system has detected a communication failure on the peer to peer network.
1.3.6.1.4.1.476.1.42.3.2.1.148current
lgpConditionUnitDisabled
OBJECT-IDENTITY
The unit is disabled.
1.3.6.1.4.1.476.1.42.3.2.1.149current
lgpConditionUnitShutdown
OBJECT-IDENTITY
The system has shutdown.
1.3.6.1.4.1.476.1.42.3.2.1.150current
lgpConditionPeerNetworkDiscovered
OBJECT-IDENTITY
The system has established communications on the peer to peer network.
1.3.6.1.4.1.476.1.42.3.2.1.151current
lgpConditionLossOfWaterFlow
OBJECT-IDENTITY
The system has detected a loss of water flow condition.
1.3.6.1.4.1.476.1.42.3.2.1.152current
lgpConditionCondensatePumpHighWater
OBJECT-IDENTITY
The system has detected high water in the condensate pump.
1.3.6.1.4.1.476.1.42.3.2.1.153current
lgpConditionGeneralAlarm
OBJECT-IDENTITY
The system has detected a general alarm condition.
1.3.6.1.4.1.476.1.42.3.2.1.154current
lgpConditionProductSpecific
OBJECT-IDENTITY
The system has detected a product specific condition. This condition is not currently available via the agent card.
1.3.6.1.4.1.476.1.42.3.2.1.155current
lgpConditionReheatLockout
OBJECT-IDENTITY
The system has locked out the electrical reheat operation for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.156current
lgpConditionHumidifierLockout
OBJECT-IDENTITY
The system has locked out the humidifier operation for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.157current
lgpConditionCompressorsLockout
OBJECT-IDENTITY
The system has locked out compressor operation for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.158current
lgpConditionCallService
OBJECT-IDENTITY
The system has detected a condition that requires a service representative be contacted.
1.3.6.1.4.1.476.1.42.3.2.1.159current
lgpConditionLowMemoryGroup
OBJECT-IDENTITY
This group contains various low memory conditions.
1.3.6.1.4.1.476.1.42.3.2.1.160current
lgpConditionLowMemory1
OBJECT-IDENTITY
The system has detected a low memory condition. The control board is low in memory resources.
1.3.6.1.4.1.476.1.42.3.2.1.160.1current
lgpConditionMemoryFailureGroup
OBJECT-IDENTITY
This group contains various memory device failure conditions.
1.3.6.1.4.1.476.1.42.3.2.1.161current
lgpConditionMemory1Failure
OBJECT-IDENTITY
The system has detected a memory 1 module failure.
1.3.6.1.4.1.476.1.42.3.2.1.161.1current
lgpConditionMemory2Failure
OBJECT-IDENTITY
The system has detected a memory 2 module failure.
1.3.6.1.4.1.476.1.42.3.2.1.161.2current
lgpConditionUnitCodeErrorGroup
OBJECT-IDENTITY
This group contains various memory device failure conditions.
1.3.6.1.4.1.476.1.42.3.2.1.162current
lgpConditionUnitCodeNotConfigured
OBJECT-IDENTITY
The system has detected the unit code is not configured. The unit code must be configured before system start-up.
1.3.6.1.4.1.476.1.42.3.2.1.162.1current
lgpConditionUnitCode01OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.2current
lgpConditionUnitCode02OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.3current
lgpConditionUnitCode03OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.4current
lgpConditionUnitCode04OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.5current
lgpConditionUnitCode05OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.6current
lgpConditionUnitCode06OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.7current
lgpConditionUnitCode07OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.8current
lgpConditionUnitCode08OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.9current
lgpConditionUnitCode09OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.10current
lgpConditionUnitCode10OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.11current
lgpConditionUnitCode11OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.12current
lgpConditionUnitCode12OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.13current
lgpConditionUnitCode13OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.14current
lgpConditionUnitCode14OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.15current
lgpConditionUnitCode15OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.16current
lgpConditionUnitCode16OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.17current
lgpConditionUnitCode17OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.18current
lgpConditionUnitCode18OutOfRange
OBJECT-IDENTITY
The system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.19current
lgpConditionHighExternalDewPoint
OBJECT-IDENTITY
The system has detected a high external dew point condition. The room dew point has exceeded the specified threshold.
1.3.6.1.4.1.476.1.42.3.2.1.163current
lgpConditionHcbDisconnected
OBJECT-IDENTITY
The system has detected the humidifier control board is disconnected or not installed.
1.3.6.1.4.1.476.1.42.3.2.1.164current
lgpConditionBmsResetTimerExpired
OBJECT-IDENTITY
The BMS fan speed control reset counter has timed out.
1.3.6.1.4.1.476.1.42.3.2.1.165current
lgpConditionAgentFirmwareCorrupt
OBJECT-IDENTITY
The firmware update to the agent card has failed and the firmware is now corrupt.
1.3.6.1.4.1.476.1.42.3.2.1.166current
lgpConditionSystemAccessGroup
OBJECT-IDENTITY
This group contains various system access conditions. An examples is an open access panel.
1.3.6.1.4.1.476.1.42.3.2.1.175current
lgpConditionFrontAccessOpen
OBJECT-IDENTITY
The system has detected the front access panel/door is open.
1.3.6.1.4.1.476.1.42.3.2.1.175.1current
lgpConditionRearAccessOpen
OBJECT-IDENTITY
The system has detected the rear access panel/door is open.
1.3.6.1.4.1.476.1.42.3.2.1.175.2current
lgpConditionsDamperFailure
OBJECT-IDENTITY
This group contains various damper failure conditions.
1.3.6.1.4.1.476.1.42.3.2.1.176current
lgpConditionEmergencyDamperFailure
OBJECT-IDENTITY
The system has detected an emergency damper failure. The damper is in the wrong position.
1.3.6.1.4.1.476.1.42.3.2.1.176.1current
lgpConditionRemoteShutdown
OBJECT-IDENTITY
A remote shutdown occurred.
1.3.6.1.4.1.476.1.42.3.2.1.177current
lgpConditionFireAlarm
OBJECT-IDENTITY
Fire Alarm.
1.3.6.1.4.1.476.1.42.3.2.1.178current
lgpConditionHeatersOverheated
OBJECT-IDENTITY
Heaters Overheated.
1.3.6.1.4.1.476.1.42.3.2.1.179current
lgpConditionCondenserFailureGroup
OBJECT-IDENTITY
This group contains condenser failure conditions.
1.3.6.1.4.1.476.1.42.3.2.1.180current
lgpConditionCondenser1Failure
OBJECT-IDENTITY
Condenser 1 Failure.
1.3.6.1.4.1.476.1.42.3.2.1.180.1current
lgpConditionCondenser2Failure
OBJECT-IDENTITY
Condenser 2 Failure.
1.3.6.1.4.1.476.1.42.3.2.1.180.2current
lgpConditionCondenserTVSSFailure
OBJECT-IDENTITY
The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed.
1.3.6.1.4.1.476.1.42.3.2.1.180.3current
lgpConditionHumidifierCyclinderWorn
OBJECT-IDENTITY
The system has detected the humidifier cylinder is worn.
1.3.6.1.4.1.476.1.42.3.2.1.181current
lgpConditionUnderCurrent
OBJECT-IDENTITY
The system has detected a low current condition. The current of one or more sources in the system has fallen below a threshold for a specified amount of time. The threshold and time that triggered this condition is system dependent.
1.3.6.1.4.1.476.1.42.3.2.1.182current
lgpConditionHumidifierUnderCurrent
OBJECT-IDENTITY
The system has detected a low current condition on the humidifier. The current of the humidifier has fallen below a pre-determined threshold for a defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.182.1current
lgpConditionInputUnderCurrent
OBJECT-IDENTITY
There is a low current condition on the input power source. The current of the input power source has fallen below a pre-determined threshold for a defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.182.2current
lgpConditionHeatRejectorGroup
OBJECT-IDENTITY
This group contains failure conditions for the heat rejection unit.
1.3.6.1.4.1.476.1.42.3.2.1.183current
lgpConditionHeatRejectorFanFailure
OBJECT-IDENTITY
The heat rejecter fan has failed.
1.3.6.1.4.1.476.1.42.3.2.1.183.1current
lgpConditionHeatRejectorVoltageSuppressionFailure
OBJECT-IDENTITY
The heat rejecter voltage suppression has failed and is no longer able to protect the unit from power fluctuations.
1.3.6.1.4.1.476.1.42.3.2.1.183.2current
lgpConditionFreeCoolLockout
OBJECT-IDENTITY
The free cooling capability has been disabled.
1.3.6.1.4.1.476.1.42.3.2.1.184current
lgpConditionWaterLeakSensorFailure
OBJECT-IDENTITY
The sensor used to detect water leaks is not connected or has failed.
1.3.6.1.4.1.476.1.42.3.2.1.185current
lgpConditionNoLoadDetectedWarning
OBJECT-IDENTITY
There is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been left on external bypass. This warning is triggered after a delay. The delay is specified by the object 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output current falls below a certain threshold specified by the object 'lgpPwrNoLoadWarningLimit'
1.3.6.1.4.1.476.1.42.3.2.1.186current
lgpConditionFirmwareGroup
OBJECT-IDENTITY
Grouping level for firmware related conditions.
1.3.6.1.4.1.476.1.42.3.2.1.187current
lgpConditionFirmwareUpdateRequired
OBJECT-IDENTITY
The firmware on the system or one or more components of the system must be updated. This typically indicates that one or more components of the system contain corrupted firmware or the firmware on one or more components are incompatible with one another. When this condition is active the system may not be able to function to its full capacity or may not be able to function at all.
1.3.6.1.4.1.476.1.42.3.2.1.187.3current
lgpConditionTestGroup
OBJECT-IDENTITY
Objects in this group of conditions are related to testing or test events. This object is never active.
1.3.6.1.4.1.476.1.42.3.2.1.188current
lgpConditionTest01
OBJECT-IDENTITY
This is a 'test' condition. It is a generic test event that can be utilized to evaluate system handling of events. Some products will support the activation of this event upon user request so that user management stations can execute end-to-end event handling tests.
1.3.6.1.4.1.476.1.42.3.2.1.188.5current
lgpConditionReceptacleBranchGroup
OBJECT-IDENTITY
Grouping level for receptacle branch conditions.
1.3.6.1.4.1.476.1.42.3.2.1.190current
lgpConditionRcpBranchFailure
OBJECT-IDENTITY
The receptacle branch module or control system has failed. Service is required.
1.3.6.1.4.1.476.1.42.3.2.1.190.5current
lgpConditionRcpBranchBreakerOpen
OBJECT-IDENTITY
The receptacle branch breaker is open.
1.3.6.1.4.1.476.1.42.3.2.1.190.10current
lgpConditionInputUnqualified
OBJECT-IDENTITY
The input is not qualified to provide power to the system. This may be due to system input over-voltage, system input under-voltage, system input frequency out of range, or other similar issues.
1.3.6.1.4.1.476.1.42.3.2.1.192current
lgpConditionBypassUnavailable
OBJECT-IDENTITY
This summary event is asserted when the bypass is not available. Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass Overvoltage, Bypass Undervoltage, Bypass Phase Rotation Error, or other similar causes.
1.3.6.1.4.1.476.1.42.3.2.1.193current
lgpConditionAutoTransferFailed
OBJECT-IDENTITY
The system is failing to automatically transfer the load to the alternate source.
1.3.6.1.4.1.476.1.42.3.2.1.194current
lgpConditionSBSUnavailable
OBJECT-IDENTITY
A Static Bypass Switch (SBS) Failure has been detected. Possible causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier) Shorted, SBS Overload Exceeded, Bypass Power Supply Fail, Static Bypass Switch Fuse Failure, or other similar causes.
1.3.6.1.4.1.476.1.42.3.2.1.195current
lgpConditionSBSOverload
OBJECT-IDENTITY
On at least one phase of the static bypass switch (SBS), the power dissipation limit has been exceeded.
1.3.6.1.4.1.476.1.42.3.2.1.196current
lgpConditionExcessPulseParallel
OBJECT-IDENTITY
The system has performed too many pulse parallel operations within the specified time interval. A pulse parallel operation is a momentary operation of the static bypass switch (SBS) in parallel with the inverter.
1.3.6.1.4.1.476.1.42.3.2.1.197current
lgpConditionRemoteBypassSwitchOffExt
OBJECT-IDENTITY
The static bypass switch is off due to the state of an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.198current
lgpConditionManTransferInhibited
OBJECT-IDENTITY
Manual transfer from inverter to bypass is inhibited. Bypass is not qualified.
1.3.6.1.4.1.476.1.42.3.2.1.199current
lgpConditionManReTransferInhibited
OBJECT-IDENTITY
Manual retransfer from bypass to inverter is inhibited.
1.3.6.1.4.1.476.1.42.3.2.1.200current
lgpConditionBatteryChargeError
OBJECT-IDENTITY
The battery is not charging properly. Some reasons for this condition include, but are not limited to: battery charger failure, battery failure, etc.
1.3.6.1.4.1.476.1.42.3.2.1.201current
lgpConditionBatteryAutoTestInhibited
OBJECT-IDENTITY
Automatic (scheduled) battery tests are inhibited.
1.3.6.1.4.1.476.1.42.3.2.1.202current
lgpConditionBatteryChargeReducedExt
OBJECT-IDENTITY
A reduced battery charging algorithm is being used due to an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.203current
lgpConditionBatteryCapacityLow
OBJECT-IDENTITY
The battery capacity is low. Some reasons for this condition include, but are not limited to: a battery is offline, the battery age has reduced its capabilities, etc.
1.3.6.1.4.1.476.1.42.3.2.1.204current
lgpConditionBatteryTempImbalance
OBJECT-IDENTITY
The temperature difference between two batteries in the system exceeds the predefined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.205current
lgpConditionBatteryEqualize
OBJECT-IDENTITY
The rectifier output voltage has been increased to equalize the battery voltage level.
1.3.6.1.4.1.476.1.42.3.2.1.206current
lgpConditionBatteryChargeInhibitedExt
OBJECT-IDENTITY
Battery charging is inhibited due to an external inhibit signal.
1.3.6.1.4.1.476.1.42.3.2.1.207current
lgpConditionServiceExtBatteryMonitorGroup
OBJECT-IDENTITY
This group contains battery monitor service conditions.
1.3.6.1.4.1.476.1.42.3.2.1.208current
lgpConditionServiceExtBatteryMonitor1
OBJECT-IDENTITY
External battery monitor 1 indicates battery maintenance is required.
1.3.6.1.4.1.476.1.42.3.2.1.208.1current
lgpConditionServiceExtBatteryMonitor2
OBJECT-IDENTITY
External battery monitor 2 indicates battery maintenance is required.
1.3.6.1.4.1.476.1.42.3.2.1.208.2current
lgpConditionBatteryGroundFault
OBJECT-IDENTITY
Battery system ground fault amperage exceeds the threshold.
1.3.6.1.4.1.476.1.42.3.2.1.209current
lgpConditionBatteryLowShutdown
OBJECT-IDENTITY
With the battery breaker closed, the battery voltage has dropped below the calculated End-Of-Discharge (EOD) limit.
1.3.6.1.4.1.476.1.42.3.2.1.210current
lgpConditionEmergencyPowerOffLocal
OBJECT-IDENTITY
The system has detected an Emergency Power Off (EPO) condition. The local EPO switch has cut off the power source to the system.
1.3.6.1.4.1.476.1.42.3.2.1.211current
lgpConditionOutputLowPFLagging
OBJECT-IDENTITY
The system has detected a lagging output power factor below the threshold, resulting in reduced load capacity.
1.3.6.1.4.1.476.1.42.3.2.1.212current
lgpConditionOutputLowPFLeading
OBJECT-IDENTITY
The system has detected a leading output power factor below the threshold, resulting in reduced load capacity.
1.3.6.1.4.1.476.1.42.3.2.1.213current
lgpConditionOutputToLoadFault
OBJECT-IDENTITY
The system has detected an output to load fault. This could be caused by over or under voltage, or by over or under frequency.
1.3.6.1.4.1.476.1.42.3.2.1.214current
lgpConditionInvRestartInhibitedExt
OBJECT-IDENTITY
Restart of the inverter is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.215current
lgpConditionInverterShutdownOverload
OBJECT-IDENTITY
The system has shutdown the inverter due to a sustained overload. This event does not indicate if the load has been dropped or transferred to bypass. At least one phase of the inverter power dissipation limit has been exceeded.
1.3.6.1.4.1.476.1.42.3.2.1.216current
lgpConditionInverterOffExt
OBJECT-IDENTITY
The inverter is off due to the state of an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.217current
lgpConditionInputContactGroup
OBJECT-IDENTITY
The system has detected an active input contact.
1.3.6.1.4.1.476.1.42.3.2.1.218current
lgpConditionInputContact01
OBJECT-IDENTITY
The system has detected that input contact 1 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.1current
lgpConditionInputContact02
OBJECT-IDENTITY
The system has detected that input contact 2 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.2current
lgpConditionInputContact03
OBJECT-IDENTITY
The system has detected that input contact 3 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.3current
lgpConditionInputContact04
OBJECT-IDENTITY
The system has detected that input contact 4 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.4current
lgpConditionInputContact05
OBJECT-IDENTITY
The system has detected that input contact 5 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.5current
lgpConditionInputContact06
OBJECT-IDENTITY
The system has detected that input contact 6 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.6current
lgpConditionInputContact07
OBJECT-IDENTITY
The system has detected that input contact 7 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.7current
lgpConditionInputContact08
OBJECT-IDENTITY
The system has detected that input contact 8 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.8current
lgpConditionInputContact09
OBJECT-IDENTITY
The system has detected that input contact 9 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.9current
lgpConditionInputContact10
OBJECT-IDENTITY
The system has detected that input contact 10 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.10current
lgpConditionInputContact11
OBJECT-IDENTITY
The system has detected that input contact 11 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.11current
lgpConditionInputContact12
OBJECT-IDENTITY
The system has detected that input contact 12 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.12current
lgpConditionInputContact13
OBJECT-IDENTITY
The system has detected that input contact 13 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.13current
lgpConditionInputContact14
OBJECT-IDENTITY
The system has detected that input contact 14 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.14current
lgpConditionInputContact15
OBJECT-IDENTITY
The system has detected that input contact 15 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.15current
lgpConditionInputContact16
OBJECT-IDENTITY
The system has detected that input contact 16 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.16current
lgpConditionRectifierOperInhibited
OBJECT-IDENTITY
The operation of the rectifier is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.219current
lgpConditionBypassBackFeedBrkrOpen
OBJECT-IDENTITY
The bypass backfeed breaker is in the open position.
1.3.6.1.4.1.476.1.42.3.2.1.220current
lgpConditionAutoRestartInProgress
OBJECT-IDENTITY
Auto restart is in progress. Becomes inactive when auto restart completes or fails.
1.3.6.1.4.1.476.1.42.3.2.1.221current
lgpConditionAutoRestartInhibitedExt
OBJECT-IDENTITY
Auto restart is inhibited due to an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.222current
lgpConditionAutoRestartFailed
OBJECT-IDENTITY
Auto restart has failed.
1.3.6.1.4.1.476.1.42.3.2.1.223current
lgpConditionInputOnGenerator
OBJECT-IDENTITY
A generator is supplying the power to the system.
1.3.6.1.4.1.476.1.42.3.2.1.224current
lgpConditionInputFilterCycleLock
OBJECT-IDENTITY
The input filter disconnect has opened too many times within a given period of time.
1.3.6.1.4.1.476.1.42.3.2.1.225current
lgpConditionServiceCodeActive
OBJECT-IDENTITY
The system is in an operational mode intended for testing. In normal operating conditions, the system should not be in this state.
1.3.6.1.4.1.476.1.42.3.2.1.226current
lgpConditionLoadBusSyncActive
OBJECT-IDENTITY
Load Bus Sync Operation is active. This synchronizes the UPS output with the output of another UPS.
1.3.6.1.4.1.476.1.42.3.2.1.227current
lgpConditionLoadBusSyncInhibited
OBJECT-IDENTITY
The system has detected that conditions to perform Load Bus Sync Operation are not satisfied.
1.3.6.1.4.1.476.1.42.3.2.1.228current
lgpConditionControlsResetRequired
OBJECT-IDENTITY
A controls reset is required because one or more critical settings have changed.
1.3.6.1.4.1.476.1.42.3.2.1.229current
lgpConditionEquipTempSensorFailed
OBJECT-IDENTITY
A temperature sensor is reporting a value outside the bounds of a properly operating sensor.
1.3.6.1.4.1.476.1.42.3.2.1.230current
lgpConditionInputCurrentImbalance
OBJECT-IDENTITY
The current on one input phase is much greater or lower than the average current of all the phases. This may indicate improper operation of the rectifier or input filter.
1.3.6.1.4.1.476.1.42.3.2.1.231current
lgpConditionPumpGroup
OBJECT-IDENTITY
The system has detected an alarm with one of the pumps.
1.3.6.1.4.1.476.1.42.3.2.1.232current
lgpConditionPumpFlowLoss
OBJECT-IDENTITY
The system has detected a loss of flow with one or more pumps.
1.3.6.1.4.1.476.1.42.3.2.1.232.1current
lgpConditionPump1FlowLoss
OBJECT-IDENTITY
The system has detected a loss of flow with pump 1.
1.3.6.1.4.1.476.1.42.3.2.1.232.1.1current
lgpConditionPump2FlowLoss
OBJECT-IDENTITY
The system has detected a loss of flow with pump 2.
1.3.6.1.4.1.476.1.42.3.2.1.232.1.2current
lgpConditionPumpShortCycle
OBJECT-IDENTITY
The system has detected a short cycling of the pumps. One or more of the pumps has been turned on and off a number of times within a specified time period.
1.3.6.1.4.1.476.1.42.3.2.1.232.2current
lgpConditionPumpInverterShortCycle
OBJECT-IDENTITY
The system has detected a short cycling of one or more pump inverters and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.1.232.3current
lgpConditionPump1InverterShortCycle
OBJECT-IDENTITY
The system has detected a short cycling of the inverter for pump 1 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.1.232.3.1current
lgpConditionPump2InverterShortCycle
OBJECT-IDENTITY
The system has detected a short cycling of the inverter for pump 2 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.1.232.3.2current
lgpConditionValveGroup
OBJECT-IDENTITY
The system has detected an alarm with one of the valves.
1.3.6.1.4.1.476.1.42.3.2.1.233current
lgpConditionChilledWaterValvePosition
OBJECT-IDENTITY
The system has detected a problem with the chilled water valve position. The position of the chilled water control valve does not match an expected value.
1.3.6.1.4.1.476.1.42.3.2.1.233.1current
lgpConditionCondensationDetected
OBJECT-IDENTITY
The system has detected condensation.
1.3.6.1.4.1.476.1.42.3.2.1.234current
lgpConditionMaintenanceGroup
OBJECT-IDENTITY
The system has detected a maintenance condition. This group contains various maintenance conditions.
1.3.6.1.4.1.476.1.42.3.2.1.235current
lgpConditionMaintenanceDue
OBJECT-IDENTITY
System is due for maintenance.
1.3.6.1.4.1.476.1.42.3.2.1.235.1current
lgpConditionMaintenanceComplete
OBJECT-IDENTITY
The system maintenance has been completed.
1.3.6.1.4.1.476.1.42.3.2.1.235.2current
lgpConditionExternalEventSignalGroup
OBJECT-IDENTITY
This group contains various conditions signalled by external inputs. Each event is deactivated when the signal is inactive.
1.3.6.1.4.1.476.1.42.3.2.1.236current
lgpConditionExternalFireDetect
OBJECT-IDENTITY
Fire detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.1current
lgpConditionExternalFlowLoss
OBJECT-IDENTITY
Loss of flow is detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.2current
lgpConditionExternalReheatLockout
OBJECT-IDENTITY
The reheater is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.3current
lgpConditionExternalOverTemp
OBJECT-IDENTITY
A temperature has exceeded its threshold, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.4current
lgpConditionExternalCompLockout
OBJECT-IDENTITY
The compressor is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.5current
lgpConditionExternalHumidifierLockout
OBJECT-IDENTITY
The humidifier is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.6current
lgpConditionComponentShutdownGroup
OBJECT-IDENTITY
This group contains conditions signaling shutdown of various system components.
1.3.6.1.4.1.476.1.42.3.2.1.237current
lgpConditionComponentShutdownPartial
OBJECT-IDENTITY
An event has occurred requiring some system components to be shutdown and disabled.
1.3.6.1.4.1.476.1.42.3.2.1.237.1current
lgpConditionComponentShutdownHighPower
OBJECT-IDENTITY
Supply to high power components has been shutdown.
1.3.6.1.4.1.476.1.42.3.2.1.237.2current
lgpConditionCondenserProblemGroup
OBJECT-IDENTITY
This group contains condenser conditions.
1.3.6.1.4.1.476.1.42.3.2.1.238current
lgpConditionCondenser1Problem
OBJECT-IDENTITY
Condenser 1 is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.1.238.1current
lgpConditionHumidityOutOfPropBand
OBJECT-IDENTITY
The system has detected a humidity reading that remained outside of the proportional control band for an extended period of time.
1.3.6.1.4.1.476.1.42.3.2.1.239current
lgpConditionEnvRemoteSensorGroup
OBJECT-IDENTITY
This group contains remote sensors.
1.3.6.1.4.1.476.1.42.3.2.1.240current
lgpConditionEnvRemoteSensor1Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.1current
lgpConditionEnvRemoteSensor2Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.2current
lgpConditionEnvRemoteSensor3Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.3current
lgpConditionEnvRemoteSensor4Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.4current
lgpConditionEnvRemoteSensor5Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.5current
lgpConditionEnvRemoteSensor6Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.6current
lgpConditionEnvRemoteSensor7Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.7current
lgpConditionEnvRemoteSensor8Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.8current
lgpConditionEnvRemoteSensor9Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.9current
lgpConditionEnvRemoteSensor10Issue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.10current
lgpConditionNeutralSnubberBoardCommFailure
OBJECT-IDENTITY
The Neutral Snubber board has stopped communicating.
1.3.6.1.4.1.476.1.42.3.2.1.241current
lgpConditionRedundantChargerFailure
OBJECT-IDENTITY
The redundant charger has failed.
1.3.6.1.4.1.476.1.42.3.2.1.242current
lgpConditionBoardInputContactorPowerFailure
OBJECT-IDENTITY
Board input contactor power failure.
1.3.6.1.4.1.476.1.42.3.2.1.243current
lgpConditionBoard1InputContactorPowerFailure
OBJECT-IDENTITY
Board1 input contactor power failure.
1.3.6.1.4.1.476.1.42.3.2.1.243.1current
lgpConditionBoard2InputContactorPowerFailure
OBJECT-IDENTITY
Board2 input contactor power failure.
1.3.6.1.4.1.476.1.42.3.2.1.243.2current
lgpConditionTooManySensors
OBJECT-IDENTITY
The number of sensors installed on the device has exceeded the pre-determined limit.
1.3.6.1.4.1.476.1.42.3.2.1.5423current
lgpConditionDoorSwitchOpen
OBJECT-IDENTITY
An open door has been detected.
1.3.6.1.4.1.476.1.42.3.2.1.5471current
lgpConditionContactClosureOpen
OBJECT-IDENTITY
An open circuit has been detected.
1.3.6.1.4.1.476.1.42.3.2.1.5479current
lgpConditionContactClosureClosed
OBJECT-IDENTITY
A closed circuit has been detected.
1.3.6.1.4.1.476.1.42.3.2.1.5480current
lgpConditionSensorsNotDisplayed
OBJECT-IDENTITY
The number of sensors that can be displayed (monitored) on the device has exceeded the pre-determined limit. Note this condition differs from the lgpConditionTooManySensors in that the system may currently have less than the maximum of installed sensors present but one or more of those sensors can not be displayed because the display order table (lgpPduAuxMeasOrderTable) contains entries for sensors that are not currently installed. This condition effectively prevents one or more installed sensors from being presented in the lgpPduAuxMeasTable. It is possible for both this condition and the lgpConditionTooManySensors condition to be active at the same time.
1.3.6.1.4.1.476.1.42.3.2.1.6119current
lgpConditionsPresent
OBJECT-TYPE
The present number of conditions (rows) in the lgpConditionsTable.
1.3.6.1.4.1.476.1.42.3.2.2Gauge32read-onlycurrent
lgpConditionsTable
OBJECT-TYPE
A list of condition table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions in effect. The number of rows in the table is given by (lgpConditionsPresent). The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row subject to the following rules: Rows are removed from the table based on the following rules: 1. If a condition does not require acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState'). 2. If a condition requires acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState') AND the condition is acknowledged (see 'lgpConditionAcknowledged'). 3. If the columns 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are not present for the condition then the condition will be removed as soon as the issue causing the condition clears. The agent creates the first row with lgpConditionId equal to 1, and increments the value of 'lgpConditionId' each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of lgpConditionId would otherwise be exceeded. The number of rows in the table at any given time is reflected by the value of 'lgpConditionsPresent'.
1.3.6.1.4.1.476.1.42.3.2.3not-accessiblecurrent
lgpConditionEntry
OBJECT-TYPE
This entry defines the contents of the rows for the table 'lgpConditionsTable'. A row in this table cannot be created or deleted by SNMP operations on columns of the table.
1.3.6.1.4.1.476.1.42.3.2.3.1not-accessiblecurrent
lgpConditionId
OBJECT-TYPE
A unique identifier for a condition. This value must remain constant between agent initializations. This OID is used as an index to identify a row in the table 'lgpConditionsTable'.
1.3.6.1.4.1.476.1.42.3.2.3.1.1Unsigned32read-onlycurrent
lgpConditionDescr
OBJECT-TYPE
A reference to a condition description object. The object referenced should not be accessible, but rather be used to provide a unique description.
1.3.6.1.4.1.476.1.42.3.2.3.1.2OBJECT IDENTIFIERread-onlycurrent
lgpConditionTime
OBJECT-TYPE
The value of sysUpTime when the condition occurred (became active).
1.3.6.1.4.1.476.1.42.3.2.3.1.3TimeTicksread-onlycurrent
lgpConditionTableRef
OBJECT-TYPE
This object will be included as a varbind in some rows of the table. It is a reference to a table object in the MIB. The value of this object will be the OID of a table that the object that the condition applies to is defined. The table row corresponding to this object will also contain a varbind 'lgpConditionTableRowRef' that will specify which instance (row) in the referenced table the object is defined in. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType alarm lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required In the above example the breaker opened for a Receptacle branch. The specific receptacle branch is specified by the additional varbind (lgpEventParmTableRowRef). In this case the notification is for the 4th receptacle branch on the 1st PDU in the cluster.
1.3.6.1.4.1.476.1.42.3.2.3.1.5OBJECT IDENTIFIERread-onlycurrent
lgpConditionTableRowRef
OBJECT-TYPE
This is a reference to the (cell) in the table specified by the companion varbind (lgpConditionTableRef) in this condition. The row in the table where this cell exists represents the object that this condition applies to. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required The table containing the definition of the receptacle branch (lgpPduRbTable) is given by the varbind (lgpConditionTableRef) The specific receptacle branch (instance) is specified by the varbind (lgpConditionTableRowRef). In this case the condition is for the 4th receptacle branch on the 1st PDU in the PDU cluster. If one wanted to retrieve the serial number for this receptacle branch the OID would be: lgpPduRbEntrySerialNum.1.4.
1.3.6.1.4.1.476.1.42.3.2.3.1.6OBJECT IDENTIFIERread-onlycurrent
lgpConditionType
OBJECT-TYPE
The type of condition in this row in the table.
1.3.6.1.4.1.476.1.42.3.2.3.1.10INTEGER {not-specified(0), message(2), warning(4), alarm(6), fault(8)}read-onlycurrent
lgpConditionCurrentState
OBJECT-TYPE
Indication of the current state of the event. If the state is 'active' then the condition currently exists. If the state is 'inactive' then the condition no longer exists (i.e. the situation causing the condition has cleared or been resolved). The behavior of some devices is to remove the condition from this table when the condition clears. The behavior of other devices is to leave the condition entry in the table until the condition is acknowledged ( see lgpConditionAcknowledged and lgpConditionAckReq).
1.3.6.1.4.1.476.1.42.3.2.3.1.12INTEGER {active(1), inactive(2)}read-onlycurrent
lgpConditionSeverity
OBJECT-TYPE
This represents the relative severity of the condition.
1.3.6.1.4.1.476.1.42.3.2.3.1.14INTEGER {not-applicable(0), minor(3), major(6), critical(9)}read-onlycurrent
lgpConditionAcknowledged
OBJECT-TYPE
This indicates if the condition has been acknowledged. If the value is 'notAcknowledged' then the condition has not been acknowledged. If the value is 'acknowledged' then the condition has been acknowledged. Writing a value of 'acknowledged' to this object acknowledges the condition and the value will be changed to 'acknowledged'. If the current state of the condition is 'active' (see lgpConditionCurrentState) the condition will, for all devices remain in the table regardless of the state of the 'lgpConditionAcknowledged' object. If the 'lgpConditionAckReq' is 'notRequired' or this column does not exist for the row then this object has no affect on the duration the condition stays in the lgpConditionsTable. If the 'lgpConditionAckReq' is 'required' then the condition will remain in the condition table until both the 'lgpConditionCurrentState' is 'inactive' AND 'lgpConditionAcknowledged' is 'acknowledged'.
1.3.6.1.4.1.476.1.42.3.2.3.1.18INTEGER {notAcknowledged(1), acknowledged(2)}read-writecurrent
lgpConditionAckReq
OBJECT-TYPE
This indicates if the corresponding condition does or does not require user acknowledgement. Conditions that require user acknowledgement will have a value of 'required'. Those conditions that do not require user acknowledgement will have a value of 'notRequired' or in some devices the column may not be present at all. If a condition requires acknowledgement it will remain in the table until both the 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are 'inactive' and 'acknowledged' respectively (see lgpConditionAcknowledged). If a condition does not require acknowledgement it will be removed from the table as soon as its 'lgpConditionCurrentState' is 'inactive'.
1.3.6.1.4.1.476.1.42.3.2.3.1.19INTEGER {required(1), notRequired(2)}read-onlycurrent
lgpConditionControl
OBJECT-IDENTITY
1.3.6.1.4.1.476.1.42.3.2.4
lgpConditionControlEventReset
OBJECT-TYPE
Event Reset Command. This command will reset all of the device's events. On some units, when an event is activated, a 'set' field is also marked and maintained even when the event has become inactive. The 'set' field is only cleared when the user clears it and the event is no longer active. This item will clear the 'set' field for all events that are not active.
1.3.6.1.4.1.476.1.42.3.2.4.1INTEGER {noAction(1), resetAll(2)}read-writecurrent
lgpConditionControlEventAck
OBJECT-TYPE
Event Acknowledge Command. This command will acknowledge all of the device's events.
1.3.6.1.4.1.476.1.42.3.2.4.2INTEGER {noAction(1), ackAll(2)}read-writecurrent
lgpConditionControlTable
OBJECT-TYPE
A list of condition control table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions that are controllable by the unit. This table does not necessarily contain all conditions supported by the unit. This table only contains conditions that are end-user modifiable.
1.3.6.1.4.1.476.1.42.3.2.4.20not-accessiblecurrent
lgpConditionControlEntry
OBJECT-TYPE
This entry defines the contents of the rows for the table 'lgpConditionControlTable'. A row in this table cannot be created or deleted by user initiated SNMP operations on columns of the table.
1.3.6.1.4.1.476.1.42.3.2.4.20.1not-accessiblecurrent
lgpConditionControlIndex
OBJECT-TYPE
This is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.2.4.20.1.1Unsigned32not-accessiblecurrent
lgpConditionControlDescr
OBJECT-TYPE
A reference to an Object Identifier (OID) representing a unique condition. The referenced OID is used solely for identification purposes. The object identifier referenced here will be the same object identifier referenced in the lgpConditionsTable (column: lgpConditionDescr) when the condition is activated.
1.3.6.1.4.1.476.1.42.3.2.4.20.1.2OBJECT IDENTIFIERread-onlycurrent
lgpConditionControlEnableStatus
OBJECT-TYPE
The value in this column determines if the device is currently capable of generating this event. If the value is 'enabled' then the event will be generated if the condition indicated by lgpConditionControlDescr becomes active. If the value is 'disabled' the device will never generate the event. This value is stored on the managed device. Some devices do not allow write access to some entries in this column. The 'lgpConditionControlEnableCapability' column indicates whether this entry can be written.
1.3.6.1.4.1.476.1.42.3.2.4.20.1.3INTEGER {not-specified(0), enabled(1), disabled(2)}read-writecurrent
lgpConditionControlType
OBJECT-TYPE
The 'type' assigned or configured for this condition. The value assigned to the condition here is displayed in the lgpConditionsTable (column: lgpConditionType). For some units this is user configurable. This value is stored on the managed device.
1.3.6.1.4.1.476.1.42.3.2.4.20.1.4INTEGER {not-specified(0), message(2), warning(4), alarm(6), fault(8)}read-writecurrent
lgpConditionControlEnableCapability
OBJECT-TYPE
Some devices do not allow write access to some entries in the 'lgpConditionControlEnableStatus' column. This column indicates whether the 'lgpConditionControlEnableStatus' entry for this row can be written.
1.3.6.1.4.1.476.1.42.3.2.4.20.1.5INTEGER {not-specified(0), readonly(1), readwrite(2)}read-onlycurrent
lgpConditionDescription
OBJECT-TYPE
The ASCII text description for the condition.
1.3.6.1.4.1.476.1.42.3.2.5DisplayString (SIZE(255))read-onlycurrent
lgpNetworkName
OBJECT-TYPE
The network name in a node.domain.com like format. This object is intended to be used as a varbind object by other notifications that have a context of a network address. As an example the lgpAgentDnsLookupFailure trap which describes a network name that is failing or has failed to be resolved from a Domain Name Service (DNS) lookup. Refer to RFC 952 for further information.
1.3.6.1.4.1.476.1.42.3.2.6DisplayString (SIZE(255))read-onlycurrent
lgpFlexConditions
OBJECT-IDENTITY
1.3.6.1.4.1.476.1.42.3.2.7