LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB

Registered at
1.3.6.1.4.1.476.1.42.1.11.1
1.3.6.1.4.1.476.1.42.3.2.7.1
Last updated
2018-10-02 00:00
Organization
Liebert Corporation
Revisions
2018-10-02 00:00
Namespace
liebert
Source file
LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB
Digest
sha256:a01e6f3978df8f0ed4ebc36fbd217ebcf4a6214b3a8c7e67da053375266d9889

Description

The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2018 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.

Contact

Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com

Imports

FromSymbols
LIEBERT-GP-CONDITIONS-MIBlgpFlexConditions
LIEBERT-GP-REGISTRATION-MIBliebertFlexibleConditionsModuleReg
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

LIEBERT-GP-CONDITIONS-MIB
LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB
LIEBERT-GP-REGISTRATION-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
lgpFlexConditionsWellKnown
OBJECT-IDENTITY
1.3.6.1.4.1.476.1.42.3.2.7.1
lgpCondId4122SystemInputPowerProblem
OBJECT-IDENTITY
The input is not qualified to provide power to the system.
1.3.6.1.4.1.476.1.42.3.2.7.1.4122current
lgpCondId4132BypassOverloadPhaseA
OBJECT-IDENTITY
An overload exists on output phase A while operating on the bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4132current
lgpCondId4133BypassOverloadPhaseB
OBJECT-IDENTITY
An overload exists on output phase B while operating on the bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4133current
lgpCondId4134BypassOverloadPhaseC
OBJECT-IDENTITY
An overload exists on output phase C while operating on the bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4134current
lgpCondId4135BypassNotAvailable
OBJECT-IDENTITY
A problem associated with the bypass has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4135current
lgpCondId4137BypassAutoRetransferPrimed
OBJECT-IDENTITY
Automatic retransfer from bypass to inverter is possible.
1.3.6.1.4.1.476.1.42.3.2.7.1.4137current
lgpCondId4138BypassAutoRetransferFailed
OBJECT-IDENTITY
After performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4138current
lgpCondId4139BypassExcessAutoRetransfers
OBJECT-IDENTITY
The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval.
1.3.6.1.4.1.476.1.42.3.2.7.1.4139current
lgpCondId4140BypassRestartInhibitExternal
OBJECT-IDENTITY
Restart of the bypass is inhibited by the state of an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4140current
lgpCondId4141BypassBreakerClosed
OBJECT-IDENTITY
The bypass breaker is closed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4141current
lgpCondId4142BypassStaticSwitchOverload
OBJECT-IDENTITY
Bypass off due to static switch overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.4142current
lgpCondId4143BypassStaticSwitchUnavailable
OBJECT-IDENTITY
The static bypass is unavailable to support the critical load.
1.3.6.1.4.1.476.1.42.3.2.7.1.4143current
lgpCondId4144BypassExcessivePulseParallel
OBJECT-IDENTITY
The system has performed too many pulse parallel operations within a specified time interval.
1.3.6.1.4.1.476.1.42.3.2.7.1.4144current
lgpCondId4145BypassAutoTransferFailed
OBJECT-IDENTITY
An automatic transfer to static bypass failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4145current
lgpCondId4146SystemInputPhsRotationError
OBJECT-IDENTITY
The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C).
1.3.6.1.4.1.476.1.42.3.2.7.1.4146current
lgpCondId4147SystemInputCurrentLimit
OBJECT-IDENTITY
The RMS input current has reached the input current limit threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4147current
lgpCondId4162BatteryLow
OBJECT-IDENTITY
The calculated battery time remaining has reached the low battery threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4162current
lgpCondId4163OutputOffEndofDischarge
OBJECT-IDENTITY
Output turned off due to battery reaching end-of-discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4163current
lgpCondId4164BatteryChargingError
OBJECT-IDENTITY
The battery is not charging properly.
1.3.6.1.4.1.476.1.42.3.2.7.1.4164current
lgpCondId4165BatteryChargingReducedExtrnl
OBJECT-IDENTITY
Using a reduced battery charging algorithm due to an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4165current
lgpCondId4166BatteryCapacityLow
OBJECT-IDENTITY
Battery capacity is low.
1.3.6.1.4.1.476.1.42.3.2.7.1.4166current
lgpCondId4167OutputOff
OBJECT-IDENTITY
Output is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.4167current
lgpCondId4168BatteryDischarging
OBJECT-IDENTITY
The battery is discharging.
1.3.6.1.4.1.476.1.42.3.2.7.1.4168current
lgpCondId4169BatteryTemperatureImbalance
OBJECT-IDENTITY
Excessive temperature differences between battery sensors detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4169current
lgpCondId4170BatteryEqualize
OBJECT-IDENTITY
The rectifier output voltage is increased to equalize the battery voltage level.
1.3.6.1.4.1.476.1.42.3.2.7.1.4170current
lgpCondId4171BatteryManualTestInProgress
OBJECT-IDENTITY
Manual battery test is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.4171current
lgpCondId4172BatteryAutoTestInProgress
OBJECT-IDENTITY
Automatic battery test is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.4172current
lgpCondId4173MainBatteryDisconnectOpen
OBJECT-IDENTITY
Main battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4173current
lgpCondId4174BatteryTemperatureSensorFault
OBJECT-IDENTITY
A battery temperature sensor fault has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4174current
lgpCondId4175BypassFrequencyError
OBJECT-IDENTITY
The bypass frequency is outside the inverter synchronization limits.
1.3.6.1.4.1.476.1.42.3.2.7.1.4175current
lgpCondId4176BatteryCircuitBreaker1Open
OBJECT-IDENTITY
Battery circuit breaker 1 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4176current
lgpCondId4177BatteryBreaker1OpenFailure
OBJECT-IDENTITY
Battery circuit breaker 1 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4177current
lgpCondId4178BatteryBreaker1CloseFailure
OBJECT-IDENTITY
Battery circuit breaker 1 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4178current
lgpCondId4179BatteryCircuitBreaker2Open
OBJECT-IDENTITY
Battery circuit breaker 2 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4179current
lgpCondId4180BatteryBreaker2OpenFailure
OBJECT-IDENTITY
Battery circuit breaker 2 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4180current
lgpCondId4181BatteryBreaker2CloseFailure
OBJECT-IDENTITY
Battery circuit breaker 2 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4181current
lgpCondId4182BatteryCircuitBreaker3Open
OBJECT-IDENTITY
Battery circuit breaker 3 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4182current
lgpCondId4183BatteryBreaker3OpenFailure
OBJECT-IDENTITY
Battery circuit breaker 3 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4183current
lgpCondId4184BatteryBreaker3CloseFailure
OBJECT-IDENTITY
Battery circuit breaker 3 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4184current
lgpCondId4185BatteryCircuitBreaker4Open
OBJECT-IDENTITY
Battery circuit breaker 4 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4185current
lgpCondId4186BatteryBreaker4OpenFailure
OBJECT-IDENTITY
Battery circuit breaker 4 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4186current
lgpCondId4187BatteryBreaker4CloseFailure
OBJECT-IDENTITY
Battery circuit breaker 4 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4187current
lgpCondId4188BatteryCircuitBreaker5Open
OBJECT-IDENTITY
Battery circuit breaker 5 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4188current
lgpCondId4189BatteryBreaker5OpenFailure
OBJECT-IDENTITY
Battery circuit breaker 5 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4189current
lgpCondId4190BatteryBreaker5CloseFailure
OBJECT-IDENTITY
Battery circuit breaker 5 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4190current
lgpCondId4191BatteryCircuitBreaker6Open
OBJECT-IDENTITY
Battery circuit breaker 6 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4191current
lgpCondId4192BatteryBreaker6OpenFailure
OBJECT-IDENTITY
Battery circuit breaker 6 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4192current
lgpCondId4193BatteryBreaker6CloseFailure
OBJECT-IDENTITY
Battery circuit breaker 6 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4193current
lgpCondId4194BatteryCircuitBreaker7Open
OBJECT-IDENTITY
Battery circuit breaker 7 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4194current
lgpCondId4195BatteryBreaker7OpenFailure
OBJECT-IDENTITY
Battery circuit breaker 7 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4195current
lgpCondId4196BatteryBreaker7CloseFailure
OBJECT-IDENTITY
Battery circuit breaker 7 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4196current
lgpCondId4197BatteryCircuitBreaker8Open
OBJECT-IDENTITY
Battery circuit breaker 8 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4197current
lgpCondId4198BatteryBreaker8OpenFailure
OBJECT-IDENTITY
Battery circuit breaker 8 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4198current
lgpCondId4199BatteryBreaker8CloseFailure
OBJECT-IDENTITY
Battery circuit breaker 8 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4199current
lgpCondId4200BatteryChargingInhibited
OBJECT-IDENTITY
Battery charging is inhibited due to an external inhibit signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4200current
lgpCondId4213SystemShutdownEPO
OBJECT-IDENTITY
System shutdown due to Emergency Power Off (EPO).
1.3.6.1.4.1.476.1.42.3.2.7.1.4213current
lgpCondId4214SystemShutdownREPO
OBJECT-IDENTITY
System shutdown due to Remote Emergency Power Off (REPO).
1.3.6.1.4.1.476.1.42.3.2.7.1.4214current
lgpCondId4215SystemOutputOff
OBJECT-IDENTITY
The system output is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.4215current
lgpCondId4216BypassBackfeedDetected
OBJECT-IDENTITY
The system detected a voltage on the bypass when none was expected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4216current
lgpCondId4217BypassManualXfrInhibited
OBJECT-IDENTITY
Manual transfer from inverter to bypass is inhibited - bypass not qualified.
1.3.6.1.4.1.476.1.42.3.2.7.1.4217current
lgpCondId4218BypassManualRexfrInhibited
OBJECT-IDENTITY
Manual transfer from bypass to inverter is inhibited - inverter output not qualified.
1.3.6.1.4.1.476.1.42.3.2.7.1.4218current
lgpCondId4219BatteryOverTemperature
OBJECT-IDENTITY
A battery temperature sensor is reporting a value above a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4219current
lgpCondId4220BatteryExternalMonitor1
OBJECT-IDENTITY
External battery monitor 1 - battery maintenance required.
1.3.6.1.4.1.476.1.42.3.2.7.1.4220current
lgpCondId4221BatteryExternalMonitor2
OBJECT-IDENTITY
External battery monitor 2 - battery maintenance required.
1.3.6.1.4.1.476.1.42.3.2.7.1.4221current
lgpCondId4222BatteryGroundFault
OBJECT-IDENTITY
Battery system ground fault amperage exceeds the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4222current
lgpCondId4229EmergencyPowerOffLatched
OBJECT-IDENTITY
System output is off - 'Emergency Power Off (EPO) - latched' requires manual reset.
1.3.6.1.4.1.476.1.42.3.2.7.1.4229current
lgpCondId4230SystemOutputLowPowerFactor
OBJECT-IDENTITY
The system output power factor is low, resulting in reduced output capacity.
1.3.6.1.4.1.476.1.42.3.2.7.1.4230current
lgpCondId4231OutputCurrentExceedsThreshold
OBJECT-IDENTITY
Output current for one or more phases exceeds a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4231current
lgpCondId4233InverterFailure
OBJECT-IDENTITY
Inverter failure - inverter output is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.4233current
lgpCondId4234InverterOverloadPhaseA
OBJECT-IDENTITY
Inverter is operating with an overload on phase A.
1.3.6.1.4.1.476.1.42.3.2.7.1.4234current
lgpCondId4235InverterOverloadPhaseB
OBJECT-IDENTITY
Inverter is operating with an overload on phase B.
1.3.6.1.4.1.476.1.42.3.2.7.1.4235current
lgpCondId4236InverterOverloadPhaseC
OBJECT-IDENTITY
Inverter is operating with an overload on phase C.
1.3.6.1.4.1.476.1.42.3.2.7.1.4236current
lgpCondId4237InverterInhibitExternal
OBJECT-IDENTITY
Restart of the inverter is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4237current
lgpCondId4238InverterOutBreakerOpenFail
OBJECT-IDENTITY
Inverter output breaker failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4238current
lgpCondId4239InverterOutBreakerCloseFail
OBJECT-IDENTITY
Inverter output breaker failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4239current
lgpCondId4270InputContact01
OBJECT-IDENTITY
The external input contact 1.
1.3.6.1.4.1.476.1.42.3.2.7.1.4270current
lgpCondId4271InputContact02
OBJECT-IDENTITY
The external input contact 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.4271current
lgpCondId4272InputContact03
OBJECT-IDENTITY
The external input contact 3.
1.3.6.1.4.1.476.1.42.3.2.7.1.4272current
lgpCondId4273InputContact04
OBJECT-IDENTITY
The external input contact 4.
1.3.6.1.4.1.476.1.42.3.2.7.1.4273current
lgpCondId4274InputContact05
OBJECT-IDENTITY
The external input contact 5.
1.3.6.1.4.1.476.1.42.3.2.7.1.4274current
lgpCondId4275InputContact06
OBJECT-IDENTITY
The external input contact 6.
1.3.6.1.4.1.476.1.42.3.2.7.1.4275current
lgpCondId4276InputContact07
OBJECT-IDENTITY
The external input contact 7.
1.3.6.1.4.1.476.1.42.3.2.7.1.4276current
lgpCondId4277InputContact08
OBJECT-IDENTITY
The external input contact 8.
1.3.6.1.4.1.476.1.42.3.2.7.1.4277current
lgpCondId4278InputContact09
OBJECT-IDENTITY
The external input contact 9.
1.3.6.1.4.1.476.1.42.3.2.7.1.4278current
lgpCondId4279InputContact10
OBJECT-IDENTITY
The external input contact 10.
1.3.6.1.4.1.476.1.42.3.2.7.1.4279current
lgpCondId4280InputContact11
OBJECT-IDENTITY
The external input contact 11.
1.3.6.1.4.1.476.1.42.3.2.7.1.4280current
lgpCondId4281InputContact12
OBJECT-IDENTITY
The external input contact 12.
1.3.6.1.4.1.476.1.42.3.2.7.1.4281current
lgpCondId4282InputContact13
OBJECT-IDENTITY
The external input contact 13.
1.3.6.1.4.1.476.1.42.3.2.7.1.4282current
lgpCondId4283InputContact14
OBJECT-IDENTITY
The external input contact 14.
1.3.6.1.4.1.476.1.42.3.2.7.1.4283current
lgpCondId4284InputContact15
OBJECT-IDENTITY
The external input contact 15.
1.3.6.1.4.1.476.1.42.3.2.7.1.4284current
lgpCondId4285InputContact16
OBJECT-IDENTITY
The external input contact 16.
1.3.6.1.4.1.476.1.42.3.2.7.1.4285current
lgpCondId4286OutputAmpOverUserLimitPhsA
OBJECT-IDENTITY
The phase A output has exceeded the user amperage threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4286current
lgpCondId4287OutputAmpOverUserLimitPhsB
OBJECT-IDENTITY
The phase B output has exceeded the user amperage threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4287current
lgpCondId4288OutputAmpOverUserLimitPhsC
OBJECT-IDENTITY
The phase C output has exceeded the user amperage threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4288current
lgpCondId4289InverterTransferInhibitExt
OBJECT-IDENTITY
Transfer of critical bus source to inverter is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4289current
lgpCondId4290InverterShutdownOverload
OBJECT-IDENTITY
The inverter has shutdown due to a sustained overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.4290current
lgpCondId4294InletAirOverTemperature
OBJECT-IDENTITY
The inlet air exceeds the maximum temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4294current
lgpCondId4295RectifierFailure
OBJECT-IDENTITY
Rectifier failure - rectifier is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.4295current
lgpCondId4296RectifierOperationInhibitExt
OBJECT-IDENTITY
The operation of the rectifier is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4296current
lgpCondId4297UPSOutputonInverter
OBJECT-IDENTITY
The output power is supplied by the inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.4297current
lgpCondId4298UPSOutputonBypass
OBJECT-IDENTITY
The output power is supplied by the bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4298current
lgpCondId4299OutputLoadonMaintBypass
OBJECT-IDENTITY
The output power is supplied by the maintenance bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4299current
lgpCondId4300InternalCommunicationsFailure
OBJECT-IDENTITY
The control has detected a communication failure of a component on the internal communication bus.
1.3.6.1.4.1.476.1.42.3.2.7.1.4300current
lgpCondId4308DCBusGroundFaultPositive
OBJECT-IDENTITY
A ground fault has been detected on the positive DC Bus link.
1.3.6.1.4.1.476.1.42.3.2.7.1.4308current
lgpCondId4309DCBusGroundFaultNegative
OBJECT-IDENTITY
A ground fault has been detected on the negative DC Bus link.
1.3.6.1.4.1.476.1.42.3.2.7.1.4309current
lgpCondId4310EquipmentOverTemperature
OBJECT-IDENTITY
Equipment over temperature summary event.
1.3.6.1.4.1.476.1.42.3.2.7.1.4310current
lgpCondId4311SystemFanFailure
OBJECT-IDENTITY
System fan failure - one or more fans have failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4311current
lgpCondId4313PasswordChanged
OBJECT-IDENTITY
Password changed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4313current
lgpCondId4314PowerSupplyFailure
OBJECT-IDENTITY
Power supply failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4314current
lgpCondId4315OnGenerator
OBJECT-IDENTITY
A generator is supplying the power to the system.
1.3.6.1.4.1.476.1.42.3.2.7.1.4315current
lgpCondId4316AutoRestartInProgress
OBJECT-IDENTITY
Auto restart is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.4316current
lgpCondId4317AutoRestartInhibitedExt
OBJECT-IDENTITY
Auto restart inhibited due to an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4317current
lgpCondId4320InitiatedTransfertoBypass
OBJECT-IDENTITY
User initiated manual transfer to bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4320current
lgpCondId4321InitiatedTransfertoInverter
OBJECT-IDENTITY
User initiated manual transfer to inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.4321current
lgpCondId4322BatteryTestPassed
OBJECT-IDENTITY
Battery test passed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4322current
lgpCondId4323BatteryTestFailed
OBJECT-IDENTITY
Battery test failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4323current
lgpCondId4324BatteryTestManuallyStopped
OBJECT-IDENTITY
The battery test was manually stopped prior to completion.
1.3.6.1.4.1.476.1.42.3.2.7.1.4324current
lgpCondId4325BackfeedBreakerOpen
OBJECT-IDENTITY
The backfeed breaker is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.4325current
lgpCondId4341VelocityAuthenticationFailure
OBJECT-IDENTITY
Notification of a message rejected by Velocity due to an authentication failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4341current
lgpCondId4360ReceptacleOverCurrent
OBJECT-IDENTITY
The system has detected a receptacle over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4360current
lgpCondId4361ReceptacleUnderCurrent
OBJECT-IDENTITY
The system has detected a receptacle under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4361current
lgpCondId4382SystemInputCurrentImbalance
OBJECT-IDENTITY
System Input Currents are Imbalanced.
1.3.6.1.4.1.476.1.42.3.2.7.1.4382current
lgpCondId4383BypassStaticSwitchOffExtrnl
OBJECT-IDENTITY
Bypass static switch is off due to the state of an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4383current
lgpCondId4384BatteryEoDDisconnect
OBJECT-IDENTITY
Battery disconnect due to end-of-discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4384current
lgpCondId4389SystemOutputFault
OBJECT-IDENTITY
A fault has been detected in the system output.
1.3.6.1.4.1.476.1.42.3.2.7.1.4389current
lgpCondId4390InverterOffExternal
OBJECT-IDENTITY
Inverter is off (operation is inhibited) due to external signal state.
1.3.6.1.4.1.476.1.42.3.2.7.1.4390current
lgpCondId4391InverterStaticSwitchSCRShort
OBJECT-IDENTITY
The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR).
1.3.6.1.4.1.476.1.42.3.2.7.1.4391current
lgpCondId4392TemperatureSensorError
OBJECT-IDENTITY
One or more temperature sensors cannot provide a valid temperature reading (i.e. sensor failure, wiring failure, sense circuit failure, etc).
1.3.6.1.4.1.476.1.42.3.2.7.1.4392current
lgpCondId4406BranchOverCurrent
OBJECT-IDENTITY
The system has detected a module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4406current
lgpCondId4407BranchUnderCurrent
OBJECT-IDENTITY
The system has detected a module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4407current
lgpCondId4416BranchOverCurrent
OBJECT-IDENTITY
The system has detected a module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4416current
lgpCondId4417BranchUnderCurrent
OBJECT-IDENTITY
The system has detected a module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4417current
lgpCondId4421BranchFailure
OBJECT-IDENTITY
One or more conditions indicate a Branch Receptacle Module failure , service is required.
1.3.6.1.4.1.476.1.42.3.2.7.1.4421current
lgpCondId4436PDUOverCurrent
OBJECT-IDENTITY
The system has detected a module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4436current
lgpCondId4437PDUUnderCurrent
OBJECT-IDENTITY
The system has detected a module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4437current
lgpCondId4438SystemInternalTemperatureRise
OBJECT-IDENTITY
Excessive temperature rise internal to the system (i.e. difference between the output versus input temperature is too large).
1.3.6.1.4.1.476.1.42.3.2.7.1.4438current
lgpCondId4439AutomaticRestartFailed
OBJECT-IDENTITY
Automatic restart failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4439current
lgpCondId4440FuseFailure
OBJECT-IDENTITY
A summary event indicating one or more fuse failures.
1.3.6.1.4.1.476.1.42.3.2.7.1.4440current
lgpCondId4441SystemControllerError
OBJECT-IDENTITY
System controller internal error.
1.3.6.1.4.1.476.1.42.3.2.7.1.4441current
lgpCondId4442SystemBreakersOpenFailure
OBJECT-IDENTITY
One or more breakers in the system failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4442current
lgpCondId4448PDUOverCurrent
OBJECT-IDENTITY
The system has detected a module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4448current
lgpCondId4449PDUUnderCurrent
OBJECT-IDENTITY
The system has detected a module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4449current
lgpCondId4468PDUOverCurrentL1
OBJECT-IDENTITY
The system has detected a module over current condition on line 1.
1.3.6.1.4.1.476.1.42.3.2.7.1.4468current
lgpCondId4469PDUOverCurrentL2
OBJECT-IDENTITY
The system has detected a module over current condition on line 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.4469current
lgpCondId4470PDUOverCurrentL3
OBJECT-IDENTITY
The system has detected a module over current condition on line 3.
1.3.6.1.4.1.476.1.42.3.2.7.1.4470current
lgpCondId4471PDUUnderCurrentL1
OBJECT-IDENTITY
The system has detected a module under current condition on line 1.
1.3.6.1.4.1.476.1.42.3.2.7.1.4471current
lgpCondId4472PDUUnderCurrentL2
OBJECT-IDENTITY
The system has detected a module under current condition on line 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.4472current
lgpCondId4473PDUUnderCurrentL3
OBJECT-IDENTITY
The system has detected a module under current condition on line 3.
1.3.6.1.4.1.476.1.42.3.2.7.1.4473current
lgpCondId4492ReceptaclePowerStateOn
OBJECT-IDENTITY
The receptacle power state changed to the ON state.
1.3.6.1.4.1.476.1.42.3.2.7.1.4492current
lgpCondId4493ReceptaclePowerStateOff
OBJECT-IDENTITY
The receptacle power state changed to the OFF state.
1.3.6.1.4.1.476.1.42.3.2.7.1.4493current
lgpCondId4494BranchBreakerOpen
OBJECT-IDENTITY
The Branch Receptacle Module's input breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4494current
lgpCondId4495DeviceConfigurationChange
OBJECT-IDENTITY
Device Configuration Change.
1.3.6.1.4.1.476.1.42.3.2.7.1.4495current
lgpCondId4496BasicDisplayModuleRemoved
OBJECT-IDENTITY
Basic Display Module Removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4496current
lgpCondId4497BasicDisplayModuleDiscovered
OBJECT-IDENTITY
Basic Display Module Discovered.
1.3.6.1.4.1.476.1.42.3.2.7.1.4497current
lgpCondId4500PDUOverCurrent
OBJECT-IDENTITY
The system has detected a power module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4500current
lgpCondId4501PDUUnderCurrent
OBJECT-IDENTITY
The system has detected a power module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4501current
lgpCondId4502PDUFailure
OBJECT-IDENTITY
One or more conditions indicate a power module failure, service is required.
1.3.6.1.4.1.476.1.42.3.2.7.1.4502current
lgpCondId4503PDUCommunicationFail
OBJECT-IDENTITY
Internal communications failure with the Power Module.
1.3.6.1.4.1.476.1.42.3.2.7.1.4503current
lgpCondId4504BranchRemoved
OBJECT-IDENTITY
Branch Receptacle Module Removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4504current
lgpCondId4505BranchDiscovered
OBJECT-IDENTITY
Branch Receptacle Module Discovered.
1.3.6.1.4.1.476.1.42.3.2.7.1.4505current
lgpCondId4506BranchOverCurrent
OBJECT-IDENTITY
The system has detected a Branch Receptacle Module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4506current
lgpCondId4507BranchCurrent
OBJECT-IDENTITY
The system has detected a Branch Receptacle Module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4507current
lgpCondId4508ReceptacleLoadRemoved
OBJECT-IDENTITY
The receptacle's load stopped drawing power.
1.3.6.1.4.1.476.1.42.3.2.7.1.4508current
lgpCondId4509ReceptacleLoadAdded
OBJECT-IDENTITY
The receptacle's load started to draw power.
1.3.6.1.4.1.476.1.42.3.2.7.1.4509current
lgpCondId4523ModuleRemoved
OBJECT-IDENTITY
Module Removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4523current
lgpCondId4524ModuleAdded
OBJECT-IDENTITY
Module Added.
1.3.6.1.4.1.476.1.42.3.2.7.1.4524current
lgpCondId4550FirmwareUpdateRequired
OBJECT-IDENTITY
Module compatibility error requires a system firmware update to resolve.
1.3.6.1.4.1.476.1.42.3.2.7.1.4550current
lgpCondId4551GenericTestEvent
OBJECT-IDENTITY
A generic test event designed to evaluate system handling of events.
1.3.6.1.4.1.476.1.42.3.2.7.1.4551current
lgpCondId4580OverTemperature
OBJECT-IDENTITY
An over temperature condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4580current
lgpCondId4581UnderTemperature
OBJECT-IDENTITY
An under temperature condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4581current
lgpCondId4588OverRelativeHumidity
OBJECT-IDENTITY
An over relative humidity condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4588current
lgpCondId4589UnderRelativeHumidity
OBJECT-IDENTITY
An under relative humidity condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4589current
lgpCondId4601ExternalAirSensorAOverTemperature
OBJECT-IDENTITY
[Ext Air Sensor A Temperature] has exceeded [External Air Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4601current
lgpCondId4604ExternalAirSensorBOverTemperature
OBJECT-IDENTITY
[Ext Air Sensor B Temperature] has exceeded [External Air Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4604current
lgpCondId4608ExtAirSensorAUnderTemperature
OBJECT-IDENTITY
[Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4608current
lgpCondId4611ExtAirSensorBUnderTemperature
OBJECT-IDENTITY
[Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4611current
lgpCondId4615ExtDewPointOverTemperature
OBJECT-IDENTITY
At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4615current
lgpCondId4618ExternalAirSensorAIssue
OBJECT-IDENTITY
The external air sensor A is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4618current
lgpCondId4621ExternalAirSensorBIssue
OBJECT-IDENTITY
The external air sensor B is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4621current
lgpCondId4626SupplyChilledWaterOverTemp
OBJECT-IDENTITY
[Supply Fluid Temperature] has exceeded [High Supply Fluid Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4626current
lgpCondId4629SupplyChilledWaterTempSensorIssue
OBJECT-IDENTITY
The supply chilled water temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4629current
lgpCondId4634SupplyRefrigerantOverTemp
OBJECT-IDENTITY
Event that is activated when [Supply Refrigerant Temperature] exceeds [Supply Refrig Over Temp Threshold]. The event is deactivated when the temperature drops below the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4634current
lgpCondId4637SupplyRefrigerantUnderTemp
OBJECT-IDENTITY
[Supply Refrigerant Temperature] has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4637current
lgpCondId4640SupplyRefrigerantTempSensorIssue
OBJECT-IDENTITY
The supply refrigeramt temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4640current
lgpCondId4645SupplyFluidOverTemp
OBJECT-IDENTITY
[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4645current
lgpCondId4648SupplyFluidUnderTemp
OBJECT-IDENTITY
[Supply Fluid Temperature] has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4648current
lgpCondId4651SupplyFluidTempSensorIssue
OBJECT-IDENTITY
The supply fluid temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4651current
lgpCondId4656Pump1LossofFlow
OBJECT-IDENTITY
Loss of flow is detected in pump 1. The loss of flow condition occurs when no differential pressure is detected across the pump.
1.3.6.1.4.1.476.1.42.3.2.7.1.4656current
lgpCondId4659Pump2LossofFlow
OBJECT-IDENTITY
Loss of flow is detected in pump 2. The loss of flow condition occurs when no differential pressure is detected across the pump.
1.3.6.1.4.1.476.1.42.3.2.7.1.4659current
lgpCondId4662PumpShortCycle
OBJECT-IDENTITY
Pumps have short cycled. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4662current
lgpCondId4669Compressor1AHighHeadPressure
OBJECT-IDENTITY
Compressor 1A high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4669current
lgpCondId4672Compressor1BHighHeadPressure
OBJECT-IDENTITY
Compressor 1B high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4672current
lgpCondId4675Compressor2AHighHeadPressure
OBJECT-IDENTITY
Compressor 2A high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4675current
lgpCondId4678Compressor2BHighHeadPressure
OBJECT-IDENTITY
Compressor 2B high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4678current
lgpCondId4681Compressor1AShortCycle
OBJECT-IDENTITY
Compressor 1A short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4681current
lgpCondId4684Compressor1BShortCycle
OBJECT-IDENTITY
Compressor 1B short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4684current
lgpCondId4687Compressor2AShortCycle
OBJECT-IDENTITY
Compressor 2A short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4687current
lgpCondId4690Compressor2BShortCycle
OBJECT-IDENTITY
Compressor 2B short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4690current
lgpCondId4693Tandem1LowSuctionPressure
OBJECT-IDENTITY
'Tandem compressors' 1 low suction pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4693current
lgpCondId4696Tandem2LowSuctionPressure
OBJECT-IDENTITY
'Tandem compressors' 2 low suction pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4696current
lgpCondId4703ChilledWaterControlValvePosition
OBJECT-IDENTITY
Chilled water valve out of position. Chilled water control valve position does not match expected value.
1.3.6.1.4.1.476.1.42.3.2.7.1.4703current
lgpCondId4711SystemCondensationDetected
OBJECT-IDENTITY
System condensation detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4711current
lgpCondId4714ShutdownLossOfPower
OBJECT-IDENTITY
System lost power. This event becomes active when the unit is powered on following an unexpected loss of power.
1.3.6.1.4.1.476.1.42.3.2.7.1.4714current
lgpCondId4720SmokeDetected
OBJECT-IDENTITY
Smoke detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4720current
lgpCondId4723WaterUnderFloor
OBJECT-IDENTITY
Water under the floor is detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4723current
lgpCondId4726ServiceRequired
OBJECT-IDENTITY
Unit requires servicing.
1.3.6.1.4.1.476.1.42.3.2.7.1.4726current
lgpCondId4729FanIssue
OBJECT-IDENTITY
One or more fans are not operating within their operational parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.4729current
lgpCondId4732ReceptacleLoadDropped
OBJECT-IDENTITY
The receptacle's load is not drawing power.
1.3.6.1.4.1.476.1.42.3.2.7.1.4732current
lgpCondId4740BatteryAutomaticTestInhibited
OBJECT-IDENTITY
Automatic (scheduled) battery tests are inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.4740current
lgpCondId4741BatterySelfTest
OBJECT-IDENTITY
Battery self test is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.4741current
lgpCondId4742BatteryLowShutdown
OBJECT-IDENTITY
Battery disconnect due to end-of-discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4742current
lgpCondId4747EquipmentTemperatureSensorFail
OBJECT-IDENTITY
One or more temperature sensors report a temperature outside of the range of expected operation.
1.3.6.1.4.1.476.1.42.3.2.7.1.4747current
lgpCondId4749SystemFanFailureRedundant
OBJECT-IDENTITY
Redundant system fan failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4749current
lgpCondId4750MultipleFanFailure
OBJECT-IDENTITY
Multiple fan failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4750current
lgpCondId4753MainControllerFault
OBJECT-IDENTITY
A Main Controller fault has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4753current
lgpCondId4754SystemBreakersCloseFailure
OBJECT-IDENTITY
One or more breakers in the system failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4754current
lgpCondId4755InputFilterCycleLock
OBJECT-IDENTITY
The input filter disconnect is open due to exceeding the maximum number of cycles.
1.3.6.1.4.1.476.1.42.3.2.7.1.4755current
lgpCondId4756ServiceCodeActive
OBJECT-IDENTITY
Service code is running.
1.3.6.1.4.1.476.1.42.3.2.7.1.4756current
lgpCondId4757LBSActive
OBJECT-IDENTITY
The Load Bus Sync option is active.
1.3.6.1.4.1.476.1.42.3.2.7.1.4757current
lgpCondId4758LBSInhibited
OBJECT-IDENTITY
The system has detected that conditions to perform Load Bus Sync are not satisfied.
1.3.6.1.4.1.476.1.42.3.2.7.1.4758current
lgpCondId4759LeadingPowerFactor
OBJECT-IDENTITY
The leading output Power Factor has fallen below a specified value.
1.3.6.1.4.1.476.1.42.3.2.7.1.4759current
lgpCondId4760ControlsResetRequired
OBJECT-IDENTITY
A controls reset is required due to one or more critical settings changing.
1.3.6.1.4.1.476.1.42.3.2.7.1.4760current
lgpCondId4823ParallelCommWarning
OBJECT-IDENTITY
Parallel communication bus warning.
1.3.6.1.4.1.476.1.42.3.2.7.1.4823current
lgpCondId4824SystemCommFail
OBJECT-IDENTITY
Failure of a device on the multi-module system communication bus.
1.3.6.1.4.1.476.1.42.3.2.7.1.4824current
lgpCondId4825LossofRedundancy
OBJECT-IDENTITY
The multi-module collection doesn't have enough modules to satisfy the redundancy configuration.
1.3.6.1.4.1.476.1.42.3.2.7.1.4825current
lgpCondId4826BPSSStartupInhibit
OBJECT-IDENTITY
The Bypass Static Switch startup is inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.4826current
lgpCondId4827MMSTransferInhibit
OBJECT-IDENTITY
The critical load can not be manually transferred from inverter to bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4827current
lgpCondId4828MMSRetransferInhibit
OBJECT-IDENTITY
The critical load can not be manually retransferred from bypass to inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.4828current
lgpCondId4830MMSLossofSyncPulse
OBJECT-IDENTITY
Multi-module system loss of sync pulse.
1.3.6.1.4.1.476.1.42.3.2.7.1.4830current
lgpCondId4831MMSOverload
OBJECT-IDENTITY
Multi-module system overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.4831current
lgpCondId4834MMSOnBattery
OBJECT-IDENTITY
The multi-module system is on battery.
1.3.6.1.4.1.476.1.42.3.2.7.1.4834current
lgpCondId4835MMSLowBatteryWarning
OBJECT-IDENTITY
Multi-module system low battery warning.
1.3.6.1.4.1.476.1.42.3.2.7.1.4835current
lgpCondId4906LowAmbientTemperature
OBJECT-IDENTITY
The system has detected a low ambient temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4906current
lgpCondId4907HighAmbientTemperature
OBJECT-IDENTITY
The system has detected a high ambient temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4907current
lgpCondId4908LowOverallVoltage
OBJECT-IDENTITY
The system has detected a low battery string overall voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4908current
lgpCondId4909HighOverallVoltage
OBJECT-IDENTITY
The system has detected a high battery string overall voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4909current
lgpCondId4910HighBatteryStringCurrent
OBJECT-IDENTITY
The system has detected a high battery string current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4910current
lgpCondId4911LowBatteryStringFloatCurrent
OBJECT-IDENTITY
The system has detected a low battery string float current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4911current
lgpCondId4912HighBatteryStringFloatCurrent
OBJECT-IDENTITY
The system has detected a high battery string float current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4912current
lgpCondId4913HighBatteryStringRippleCurrent
OBJECT-IDENTITY
The system has detected a high battery string ripple current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4913current
lgpCondId4914BatteryStringDischargeDetected
OBJECT-IDENTITY
The system has detected a battery string discharge condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4914current
lgpCondId4915MaximumDischargeTimeExceeded
OBJECT-IDENTITY
The system has detected an excessive discharge time condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4915current
lgpCondId4916DischargeLowOverallVoltage
OBJECT-IDENTITY
The system has detected a low battery string overall voltage condition during a discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4916current
lgpCondId4917DischargeLowCellVoltage
OBJECT-IDENTITY
The system has detected a low cell voltage condition during a discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4917current
lgpCondId4918DischargeHighBatteryStringCurrent
OBJECT-IDENTITY
The system has detected a high battery string current condition during a discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4918current
lgpCondId4919ExcessiveCelltoCellTemperatureDeviation
OBJECT-IDENTITY
The system has detected an excessive cell to cell temperature deviation condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4919current
lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation
OBJECT-IDENTITY
The system has detected an excessive cell to ambient temperature deviation condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4920current
lgpCondId4964LowCellVoltage
OBJECT-IDENTITY
The system has detected a low cell voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4964current
lgpCondId4965HighCellVoltage
OBJECT-IDENTITY
The system has detected a high cell voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4965current
lgpCondId4966LowCellTemperature
OBJECT-IDENTITY
The system has detected a low cell temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4966current
lgpCondId4967HighCellTemperature
OBJECT-IDENTITY
The system has detected a high cell temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4967current
lgpCondId4968LowInternalResistance
OBJECT-IDENTITY
The system has detected a low internal resistance condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4968current
lgpCondId4969HighInternalResistance
OBJECT-IDENTITY
The system has detected a high internal resistance condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4969current
lgpCondId4970HighIntercellResistance
OBJECT-IDENTITY
The system has detected a high intercell resistance condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4970current
lgpCondId4978IntertierResistanceHigh
OBJECT-IDENTITY
The system has detected a high intertier resistance condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4978current
lgpCondId4980SupplyChilledWaterLossofFlow
OBJECT-IDENTITY
Supply chilled water or glycol flow is too low.
1.3.6.1.4.1.476.1.42.3.2.7.1.4980current
lgpCondId4983SupplyRefrigOverTempBand1
OBJECT-IDENTITY
[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 1].
1.3.6.1.4.1.476.1.42.3.2.7.1.4983current
lgpCondId4986SupplyRefrigUnderTempBand1
OBJECT-IDENTITY
[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 1].
1.3.6.1.4.1.476.1.42.3.2.7.1.4986current
lgpCondId4990SupplyRefrigOverTempBand2
OBJECT-IDENTITY
[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 2].
1.3.6.1.4.1.476.1.42.3.2.7.1.4990current
lgpCondId4993SupplyRefrigUnderTempBand2
OBJECT-IDENTITY
[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 2].
1.3.6.1.4.1.476.1.42.3.2.7.1.4993current
lgpCondId4996Inverter1ShortCycle
OBJECT-IDENTITY
Inverter for pump 1 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4996current
lgpCondId4999Inverter2ShortCycle
OBJECT-IDENTITY
Inverter for pump 2 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4999current
lgpCondId5015SupplyAirOverTemperature
OBJECT-IDENTITY
[Supply Air Temperature] has exceeded [High Supply Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5015current
lgpCondId5019SupplyAirUnderTemperature
OBJECT-IDENTITY
[Supply Air Temperature] has dropped below [Low Supply Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5019current
lgpCondId5023ReturnAirOverTemperature
OBJECT-IDENTITY
[Return Air Temperature] has exceeded [High Return Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5023current
lgpCondId5026SupplyAirSensorIssue
OBJECT-IDENTITY
The air sensor at the outlet of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5026current
lgpCondId5034HighReturnHumidity
OBJECT-IDENTITY
[Return Humidity] has exceeded [High Return Humidity Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5034current
lgpCondId5036LowReturnHumidity
OBJECT-IDENTITY
[Return Humidity] has dropped below [Low Return Humidity Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5036current
lgpCondId5037HumidifierHoursExceeded
OBJECT-IDENTITY
Operating hours for the humidifier have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5037current
lgpCondId5038DehumidifierHoursExceeded
OBJECT-IDENTITY
Operating hours for the dehumidifier have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5038current
lgpCondId5039HumidifierUnderCurrent
OBJECT-IDENTITY
The electrical current to the humidifier has dropped below its lower threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5039current
lgpCondId5040HumidifierOverCurrent
OBJECT-IDENTITY
The electrical current to the humidifier has exceeded its upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5040current
lgpCondId5041HumidifierLowWater
OBJECT-IDENTITY
The water level in the humidifier has dropped below its threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5041current
lgpCondId5042HumidifierCylinderWorn
OBJECT-IDENTITY
Humidifier cylinder is not operating properly and needs to be replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5042current
lgpCondId5043HumidifierIssue
OBJECT-IDENTITY
Humidifier issue detected, causing it to be locked out.
1.3.6.1.4.1.476.1.42.3.2.7.1.5043current
lgpCondId5044ExtHumidifierLockout
OBJECT-IDENTITY
The humidifier is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5044current
lgpCondId5045HumidifierControlBoardNotDetected
OBJECT-IDENTITY
Humidifier control board is required to be connected, but no signal is detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5045current
lgpCondId5046ReturnHumidityOutOfProportionalBand
OBJECT-IDENTITY
[Return Humidity] has exceeded the upper limit of [Dehumidification Proportional Band], or has dropped below the lower limit of [Humidification Proportional Band] ], for an extended period of time.
1.3.6.1.4.1.476.1.42.3.2.7.1.5046current
lgpCondId5053LossofAirFlow
OBJECT-IDENTITY
No air flow through the unit due to failure of all fans.
1.3.6.1.4.1.476.1.42.3.2.7.1.5053current
lgpCondId5054FanHoursExceeded
OBJECT-IDENTITY
Operating hours for the unit blower fan have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5054current
lgpCondId5055TopFanIssue
OBJECT-IDENTITY
The top fan is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5055current
lgpCondId5056BottomFanIssue
OBJECT-IDENTITY
The bottom fan is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5056current
lgpCondId5060RemoteSensorIssue
OBJECT-IDENTITY
Remote sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5060current
lgpCondId5062Compressor1LowSuctionPressure
OBJECT-IDENTITY
Compressor 1 low suction pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5062current
lgpCondId5063Compressor1HoursExceeded
OBJECT-IDENTITY
Operating hours for compressor 1 have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5063current
lgpCondId5064DigScrollComp1TempSensorIssue
OBJECT-IDENTITY
Digital scroll compressor 1 temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5064current
lgpCondId5065DigScrollComp1OverTemp
OBJECT-IDENTITY
Digital scroll compressor 1 shut off because its head temperature has exceeded the upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5065current
lgpCondId5066Compressor1LowPressureTransducerIssue
OBJECT-IDENTITY
Compressor 1 low pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5066current
lgpCondId5067ExtCompressorLockout
OBJECT-IDENTITY
The compressor is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5067current
lgpCondId5068ReheaterOverTemperature
OBJECT-IDENTITY
The temperature of the reheater has exceeded its threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5068current
lgpCondId5069ElectricReheater1HoursExceeded
OBJECT-IDENTITY
Operating hours for electric reheater 1 have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5069current
lgpCondId5070ExtReheatLockout
OBJECT-IDENTITY
The reheater is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5070current
lgpCondId5071Condenser1Issue
OBJECT-IDENTITY
Condenser 1 is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5071current
lgpCondId5072CondenserVFDIssue
OBJECT-IDENTITY
The condenser fan Variable Frequency Drive is offline.
1.3.6.1.4.1.476.1.42.3.2.7.1.5072current
lgpCondId5073CondenserTVSSIssue
OBJECT-IDENTITY
The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5073current
lgpCondId5104ExtOverTemperature
OBJECT-IDENTITY
A temperature has exceeded its threshold, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5104current
lgpCondId5105ExtLossofFlow
OBJECT-IDENTITY
Loss of flow is detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5105current
lgpCondId5106ExtCondenserPumpHighWater
OBJECT-IDENTITY
High water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5106current
lgpCondId5107ExtStandbyGlycolPumpOn
OBJECT-IDENTITY
The standby glycol pump is on, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5107current
lgpCondId5108ExternalFireDetected
OBJECT-IDENTITY
Fire detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5108current
lgpCondId5109UnitOn
OBJECT-IDENTITY
Unit was turned on.
1.3.6.1.4.1.476.1.42.3.2.7.1.5109current
lgpCondId5110UnitOff
OBJECT-IDENTITY
Unit was turned off.
1.3.6.1.4.1.476.1.42.3.2.7.1.5110current
lgpCondId5111UnitStandby
OBJECT-IDENTITY
Unit was placed in standby mode.
1.3.6.1.4.1.476.1.42.3.2.7.1.5111current
lgpCondId5112UnitPartialShutdown
OBJECT-IDENTITY
An event has occurred requiring some system components to be shutdown and disabled.
1.3.6.1.4.1.476.1.42.3.2.7.1.5112current
lgpCondId5113UnitShutdown
OBJECT-IDENTITY
An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5113current
lgpCondId5114WaterLeakageDetectorSensorIssue
OBJECT-IDENTITY
The water leakage detector sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5114current
lgpCondId5115BMSCommunicationsTimeout
OBJECT-IDENTITY
Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe.
1.3.6.1.4.1.476.1.42.3.2.7.1.5115current
lgpCondId5116MaintenanceDue
OBJECT-IDENTITY
The calculated maintenance date has been reached.
1.3.6.1.4.1.476.1.42.3.2.7.1.5116current
lgpCondId5117MaintenanceCompleted
OBJECT-IDENTITY
Maintenance has been completed on the unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5117current
lgpCondId5118CloggedAirFilter
OBJECT-IDENTITY
Air filter is dirty and needs to be (cleaned or) replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5118current
lgpCondId5119RAMBatteryIssue
OBJECT-IDENTITY
RAM or RAM backup battery is not operating correctly.
1.3.6.1.4.1.476.1.42.3.2.7.1.5119current
lgpCondId5120MasterUnitCommunicationLost
OBJECT-IDENTITY
Communication with master unit has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.5120current
lgpCondId5121HighPowerShutdown
OBJECT-IDENTITY
Supply to high power components has been shutdown.
1.3.6.1.4.1.476.1.42.3.2.7.1.5121current
lgpCondId5126DigScrollComp2OverTemp
OBJECT-IDENTITY
Digital scroll compressor 2 shut off because its head temperature has exceeded the upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5126current
lgpCondId5144OutputOfUf
OBJECT-IDENTITY
The output frequency has exceeded a specified range for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.7.1.5144current
lgpCondId5145MMSModuleAlarmActive
OBJECT-IDENTITY
Active alarm or fault of any module in a multi-module system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5145current
lgpCondId5146CompressorPumpDownIssue
OBJECT-IDENTITY
Unable to pump down suction-side pressure during compressor shutdown.
1.3.6.1.4.1.476.1.42.3.2.7.1.5146current
lgpCondId5147ReturnAirSensorIssue
OBJECT-IDENTITY
The air sensor at the inlet of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5147current
lgpCondId5148CompressorHighPressureTransducerIssue
OBJECT-IDENTITY
Compressor high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5148current
lgpCondId5149BatteryNotQualified
OBJECT-IDENTITY
The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5149current
lgpCondId5150BatteryTerminalsReversed
OBJECT-IDENTITY
The measured battery voltage is a negative value due to reverse battery terminal connections.
1.3.6.1.4.1.476.1.42.3.2.7.1.5150current
lgpCondId5151BatteryConverterFailure
OBJECT-IDENTITY
Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module.
1.3.6.1.4.1.476.1.42.3.2.7.1.5151current
lgpCondId5152InverterSCROpen
OBJECT-IDENTITY
The system has detected an open across one or more inverter static switch Silicon Controlled Rectifiers.
1.3.6.1.4.1.476.1.42.3.2.7.1.5152current
lgpCondId5153LoadSharingFault
OBJECT-IDENTITY
Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current.
1.3.6.1.4.1.476.1.42.3.2.7.1.5153current
lgpCondId5154DCBusAbnormal
OBJECT-IDENTITY
The system has detected an abnormal DC Bus Voltage.
1.3.6.1.4.1.476.1.42.3.2.7.1.5154current
lgpCondId5155MainsInputNeutralLost
OBJECT-IDENTITY
Loss of neutral in the input source is detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5155current
lgpCondId5156LoadImpactTransfer
OBJECT-IDENTITY
On bypass as result of load impact.
1.3.6.1.4.1.476.1.42.3.2.7.1.5156current
lgpCondId5157UserOperationInvalid
OBJECT-IDENTITY
User attempted an invalid operation.
1.3.6.1.4.1.476.1.42.3.2.7.1.5157current
lgpCondId5158PowerSubModuleFault
OBJECT-IDENTITY
One or more failures detected in power module, inverter or rectifier.
1.3.6.1.4.1.476.1.42.3.2.7.1.5158current
lgpCondId5178OutputOvervoltage
OBJECT-IDENTITY
One or more of the output phase voltages has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5178current
lgpCondId5179OutputUndervoltage
OBJECT-IDENTITY
One or more of the output phase voltages has dropped below the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5179current
lgpCondId5180OutputOvercurrent
OBJECT-IDENTITY
One or more of the phase currents has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5180current
lgpCondId5181NeutralOvercurrent
OBJECT-IDENTITY
The system's neutral current has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5181current
lgpCondId5182GroundOvercurrent
OBJECT-IDENTITY
System ground current has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5182current
lgpCondId5183OutputVoltageTHD
OBJECT-IDENTITY
The Total Harmonic Distortion of the voltage on one or more of the output phases has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5183current
lgpCondId5184OutputFrequencyError
OBJECT-IDENTITY
The output frequency is outside a specified range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5184current
lgpCondId5185TransformerOvertemperature
OBJECT-IDENTITY
Indicates a unit transformer overtemperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5185current
lgpCondId5212PanelSummaryStatus
OBJECT-IDENTITY
The status for the panel. Detects and annunciates upon occurrence of any branch or panelboard main breaker active event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5212current
lgpCondId5213PanelOvervoltage
OBJECT-IDENTITY
One or more of the phase voltages of this panel has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5213current
lgpCondId5214PanelUndervoltage
OBJECT-IDENTITY
One or more of the phase voltages of this panel is less than the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5214current
lgpCondId5215PanelOvercurrent
OBJECT-IDENTITY
One or more of the phase currents of this panel has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5215current
lgpCondId5216PanelNeutralOvercurrent
OBJECT-IDENTITY
The Neutral current of this panel has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5216current
lgpCondId5217PanelGroundOvercurrent
OBJECT-IDENTITY
The Ground current of this panel has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5217current
lgpCondId5226BranchOvercurrent
OBJECT-IDENTITY
The current in one or more phases of this branch exceeds the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5226current
lgpCondId5227BranchUndercurrent
OBJECT-IDENTITY
The current in one or more phases of this branch is less than the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5227current
lgpCondId5245SubfeedPhaseOvercurrent
OBJECT-IDENTITY
One or more of the phase currents in this subfeed has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5245current
lgpCondId5246SubfeedNeutralOvercurrent
OBJECT-IDENTITY
The Neutral current in this subfeed has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5246current
lgpCondId5247SubfeedGroundOvercurrent
OBJECT-IDENTITY
The Ground current of this subfeed has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5247current
lgpCondId5249EventState
OBJECT-IDENTITY
The present state of this digital event input.
1.3.6.1.4.1.476.1.42.3.2.7.1.5249current
lgpCondId5263CompressorNotStopping
OBJECT-IDENTITY
Compressor commanded to stop, but continues to run.
1.3.6.1.4.1.476.1.42.3.2.7.1.5263current
lgpCondId5269CompressorHoursExceeded
OBJECT-IDENTITY
[Compressor Hours] has exceeded [Compressor Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5269current
lgpCondId5270CompressorHighHeadPressure
OBJECT-IDENTITY
Compressor is shut down due to high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5270current
lgpCondId5271CompressorLowSuctionPressure
OBJECT-IDENTITY
Compressor is shut down due to low suction pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5271current
lgpCondId5272CompressorThermalOverload
OBJECT-IDENTITY
Compressor is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.5272current
lgpCondId5273CompressorLowOilPressure
OBJECT-IDENTITY
Compressor low oil pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5273current
lgpCondId5274CompressorHeadPressureOverThreshold
OBJECT-IDENTITY
Compressor head pressure has exceeded an upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5274current
lgpCondId5275CompressorLossofDifferentialPressure
OBJECT-IDENTITY
Compressor is shut down due to low differential pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5275current
lgpCondId5277CondenserFanIssue
OBJECT-IDENTITY
Condenser fan is not operating within its operational parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5277current
lgpCondId5278LowCondenserRefrigerantPressure
OBJECT-IDENTITY
Refrigerant pressure in condenser coil is too low.
1.3.6.1.4.1.476.1.42.3.2.7.1.5278current
lgpCondId5280LowFluidPressure
OBJECT-IDENTITY
[Fluid Pressure] has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5280current
lgpCondId5293ReturnFluidOverTemp
OBJECT-IDENTITY
[Return Fluid Temperature] has exceeded a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5293current
lgpCondId5294ReturnFluidUnderTemp
OBJECT-IDENTITY
[Return Fluid Temperature] has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5294current
lgpCondId5295ReturnFluidTempSensorIssue
OBJECT-IDENTITY
The return fluid temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5295current
lgpCondId5296TeamworkReturnFluidTempSensorIssue
OBJECT-IDENTITY
The return fluid temperature sensors for all Teamwork units are disconnected or the signals are out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5296current
lgpCondId5297AllPumpsLossofFlow
OBJECT-IDENTITY
System is shut down due to loss of flow in all available pumps.
1.3.6.1.4.1.476.1.42.3.2.7.1.5297current
lgpCondId5300PumpHoursExceeded
OBJECT-IDENTITY
[Pump Hours] has exceeded [Pump Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5300current
lgpCondId5306FreeCoolingValveHoursExceeded
OBJECT-IDENTITY
[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5306current
lgpCondId5308EvaporatorInletTempSensorIssue
OBJECT-IDENTITY
The evaporator inlet temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5308current
lgpCondId5309TeamworkEvaporatorInletTempSensorIssue
OBJECT-IDENTITY
The evaporator inlet temperature sensors for all Teamwork units are disconnected or the signals are out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5309current
lgpCondId5310EvaporatorFluidFreezeAutoReset
OBJECT-IDENTITY
Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down, but will restart when the temperature rises above the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5310current
lgpCondId5311EvaporatorFluidFreezeManualResetRequired
OBJECT-IDENTITY
Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down and requires a manual reset.
1.3.6.1.4.1.476.1.42.3.2.7.1.5311current
lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss
OBJECT-IDENTITY
While subgroup unit communication was lost, an event occurred on the subgroup unit. Please check subgroup unit event log.
1.3.6.1.4.1.476.1.42.3.2.7.1.5315current
lgpCondId5335ReturnAirUnderTemperature
OBJECT-IDENTITY
[Return Air Temperature] has dropped below [Low Return Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5335current
lgpCondId5349ExtAirSensorAHighHumidity
OBJECT-IDENTITY
[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5349current
lgpCondId5351ExtAirSensorALowHumidity
OBJECT-IDENTITY
[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5351current
lgpCondId5352CompressorShortCycle
OBJECT-IDENTITY
Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.5352current
lgpCondId5354DigScrollCompDischargeTempSensorIssue
OBJECT-IDENTITY
Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5354current
lgpCondId5355DigScrollCompOverTemp
OBJECT-IDENTITY
Digital scroll compressor is shut down due to head temperature exceeding an upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5355current
lgpCondId5361ExtFreeCoolingLockout
OBJECT-IDENTITY
Free cooling is disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5361current
lgpCondId5362FreeCoolingTempSensorIssue
OBJECT-IDENTITY
The free cooling fluid temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5362current
lgpCondId5365HotWaterHotGasValveHoursExceeded
OBJECT-IDENTITY
[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5365current
lgpCondId5368ElectricReheaterHoursExceeded
OBJECT-IDENTITY
[Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5368current
lgpCondId5376MainFanOverload
OBJECT-IDENTITY
Main fan is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.5376current
lgpCondId5377Condenser
OBJECT-IDENTITY
Condenser is not operating within its operational parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5377current
lgpCondId5415ExtLossofAirBlower
OBJECT-IDENTITY
Loss of air blower is detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5415current
lgpCondId5416ExtStandbyUnitOn
OBJECT-IDENTITY
Standby unit is on, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5416current
lgpCondId5417DigitalOutputBoardNotDetected
OBJECT-IDENTITY
Digital output board is required to be connected, but no signal is detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5417current
lgpCondId5418UnitCodeMissing
OBJECT-IDENTITY
Unit code has not been entered and saved.
1.3.6.1.4.1.476.1.42.3.2.7.1.5418current
lgpCondId5419UnitCommunicationLost
OBJECT-IDENTITY
Master has lost communication with one or more networked units.
1.3.6.1.4.1.476.1.42.3.2.7.1.5419current
lgpCondId5422OvertemperaturePowerOff
OBJECT-IDENTITY
Power turned off because equipment over temperature limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5422current
lgpCondId5423TooManySensors
OBJECT-IDENTITY
The number of sensors connected to the PDU exceeds the allowable limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5423current
lgpCondId5432TransformerOvertemperaturePowerOff
OBJECT-IDENTITY
Output power shutdown due to high transformer temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.5432current
lgpCondId5433TransformerOvertemperature
OBJECT-IDENTITY
Transformer temperature has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5433current
lgpCondId5434TransformerTemperatureSensorFail
OBJECT-IDENTITY
Transformer temperature sensor has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5434current
lgpCondId5436LowAmbientTemperatureProbeTwo
OBJECT-IDENTITY
The system has detected a low ambient temperature condition on temperature probe 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.5436current
lgpCondId5437HighAmbientTemperatureProbeTwo
OBJECT-IDENTITY
The system has detected a high ambient temperature condition on temperature probe 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.5437current
lgpCondId5438ThermalRunawayDetected
OBJECT-IDENTITY
The system has detected a thermal runaway condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5438current
lgpCondId5439BatteryStringEqualize
OBJECT-IDENTITY
The system has detected a battery string equalize condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5439current
lgpCondId5440BatteryStringOffline
OBJECT-IDENTITY
The system has detected the battery string is offline.
1.3.6.1.4.1.476.1.42.3.2.7.1.5440current
lgpCondId5442DischargeLowCellVoltage
OBJECT-IDENTITY
The system has detected a low cell voltage condition during a discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.5442current
lgpCondId5447MMSPowerSharing
OBJECT-IDENTITY
A module is not sharing power with the other modules in a multi -module system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5447current
lgpCondId5453ModuleInStandbyIntelligentParalleling
OBJECT-IDENTITY
Module is placed into standby operation per Intelligent Paralleling.
1.3.6.1.4.1.476.1.42.3.2.7.1.5453current
lgpCondId5456ECOModeActive
OBJECT-IDENTITY
Conditions for Activation or Automatic Reactivation have been satisfied.
1.3.6.1.4.1.476.1.42.3.2.7.1.5456current
lgpCondId5457ECOModeSuspended
OBJECT-IDENTITY
ECO Mode session is suspended.
1.3.6.1.4.1.476.1.42.3.2.7.1.5457current
lgpCondId5458ExcessECOSuspends
OBJECT-IDENTITY
Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting.
1.3.6.1.4.1.476.1.42.3.2.7.1.5458current
lgpCondId5471DoorOpen
OBJECT-IDENTITY
An open door was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5471current
lgpCondId5472DoorSensorDisconnected
OBJECT-IDENTITY
Door sensor disconnect detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5472current
lgpCondId5479ContactClosureOpen
OBJECT-IDENTITY
An open circuit was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5479current
lgpCondId5480ContactClosureClosed
OBJECT-IDENTITY
A closed circuit was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5480current
lgpCondId5492ExtSystemCondensationDetected
OBJECT-IDENTITY
External system condensation detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5492current
lgpCondId5495ExtFanIssue
OBJECT-IDENTITY
One or more fans are not operating within their operational parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5495current
lgpCondId5500ExtRemoteShutdown
OBJECT-IDENTITY
Unit is shut down by a remote signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5500current
lgpCondId5505HotAisleTempOutofRange
OBJECT-IDENTITY
The air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold] or below [Hot Aisle Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5505current
lgpCondId5508ColdAisleTempOutofRange
OBJECT-IDENTITY
The air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold] or below [Cold Aisle Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5508current
lgpCondId5512RemoteShutdown
OBJECT-IDENTITY
Unit is shut down by a remote signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5512current
lgpCondId5513CompressorCapacityReduced
OBJECT-IDENTITY
Compressor capacity has been reduced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5513current
lgpCondId5514CompressorLowPressureTransducerIssue
OBJECT-IDENTITY
Compressor low pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5514current
lgpCondId5524PDUNeutralOverCurrent
OBJECT-IDENTITY
The system has detected a neutral over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5524current
lgpCondId5531CondenserCommunicationLost
OBJECT-IDENTITY
Communication with condenser unit has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.5531current
lgpCondId5535CondenserOutsideAirTempSensorIssue
OBJECT-IDENTITY
Condenser outside air temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5535current
lgpCondId5536CondenserOutsideAirTempOutofOperatingRange
OBJECT-IDENTITY
[Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5536current
lgpCondId5537CondenserControlBoardIssue
OBJECT-IDENTITY
The condenser control board is reporting an issue.
1.3.6.1.4.1.476.1.42.3.2.7.1.5537current
lgpCondId5539CondenserRefrigerantPressureOverThreshold
OBJECT-IDENTITY
Condenser refrigerant pressure has exceeded a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5539current
lgpCondId5540CondenserRefrigerantPressureUnderThreshold
OBJECT-IDENTITY
Condenser refrigerant pressure has dropped below a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5540current
lgpCondId5541CondenserRefrigerantPressureSensorIssue
OBJECT-IDENTITY
Condenser refrigerant pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5541current
lgpCondId5542CondenserSupplyRefrigerantOverTemp
OBJECT-IDENTITY
Condenser supply refrigerant temperature has exceeded a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5542current
lgpCondId5543CondenserSupplyRefrigerantUnderTemp
OBJECT-IDENTITY
Condenser supply refrigerant temperature has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5543current
lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue
OBJECT-IDENTITY
Condenser supply refrigerant temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5544current
lgpCondId5545CondenserMaxFanSpeedOverride
OBJECT-IDENTITY
Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5545current
lgpCondId5559EvaporatorReturnFluidOverTemp
OBJECT-IDENTITY
[Evaporator Return Fluid Temperature] has exceeded a threshold. The event is deactivated when the temperature drops below the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5559current
lgpCondId5560EvaporatorReturnFluidUnderTemp
OBJECT-IDENTITY
[Evaporator Return Fluid Temperature] has dropped below a threshold. The event is deactivated when the temperature rises above the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5560current
lgpCondId5561LBSActiveMaster
OBJECT-IDENTITY
This UPS system has been selected as the functional Master Load Bus Synchronization (LBS) system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5561current
lgpCondId5562LBSActiveSlave
OBJECT-IDENTITY
This UPS system is synchronized to the output bus of the UPS system that has been selected as the Master Load Bus Synchronization (LBS) system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5562current
lgpCondId5563DCBusLowFault
OBJECT-IDENTITY
The DC Bus voltage has reached a critical low level.
1.3.6.1.4.1.476.1.42.3.2.7.1.5563current
lgpCondId5564FanContactorOpen
OBJECT-IDENTITY
The fan contactor is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5564current
lgpCondId5565FanContactorOpenFail
OBJECT-IDENTITY
The fan contactor failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5565current
lgpCondId5566FanContactorCloseFail
OBJECT-IDENTITY
The fan contactor failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.5566current
lgpCondId5567IPInhibit
OBJECT-IDENTITY
The intelligent paralleling operation is inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.5567current
lgpCondId5568InputUndervoltage
OBJECT-IDENTITY
One or more of the input phase voltages has dropped below the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5568current
lgpCondId5569InputOvervoltage
OBJECT-IDENTITY
One or more of the input phase voltages has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5569current
lgpCondId5573AmbientAirSensorIssue
OBJECT-IDENTITY
Ambient air sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5573current
lgpCondId5577ExtDewPointUnderTemperature
OBJECT-IDENTITY
At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5577current
lgpCondId5578DewPointOverTemperature
OBJECT-IDENTITY
Dew point temperature reading has exceeded the upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5578current
lgpCondId5579DewPointUnderTemperature
OBJECT-IDENTITY
Dew point temperature reading has dropped below the lower threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5579current
lgpCondId5588UnspecifiedGeneralEvent
OBJECT-IDENTITY
One or more unspecified events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5588current
lgpCondId5593RemoteSensorAverageOverTemperature
OBJECT-IDENTITY
[Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5593current
lgpCondId5594RemoteSensorAverageUnderTemperature
OBJECT-IDENTITY
[Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5594current
lgpCondId5595RemoteSensorSystemAverageOverTemperature
OBJECT-IDENTITY
[Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5595current
lgpCondId5596RemoteSensorSystemAverageUnderTemperature
OBJECT-IDENTITY
[Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5596current
lgpCondId5597RemoteSensorOverTemperature
OBJECT-IDENTITY
[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5597current
lgpCondId5598RemoteSensorUnderTemperature
OBJECT-IDENTITY
[Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5598current
lgpCondId5600AirEconomizerEmergencyOverride
OBJECT-IDENTITY
Indoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling.
1.3.6.1.4.1.476.1.42.3.2.7.1.5600current
lgpCondId5601AirEconomizerReducedAirflow
OBJECT-IDENTITY
Air economizer filter is dirty and needs to be cleaned or replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5601current
lgpCondId5604CompressorSuperheatOverThreshold
OBJECT-IDENTITY
Compressor discharge refrigerant superheat temperature has exceeded an upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5604current
lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent
OBJECT-IDENTITY
The delta temperature between a cell temperature and the ambient temperature has exceeded the thermal runaway cell to ambient temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5609current
lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent
OBJECT-IDENTITY
The delta temperature between two cells has exceeded the thermal runaway cell to cell temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5610current
lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent
OBJECT-IDENTITY
The Battery-String charger current has exceeded the thermal runaway charger current level one threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5611current
lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent
OBJECT-IDENTITY
The Battery-String charger current has exceeded the thermal runaway charger current level two threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5612current
lgpCondId5617TemperatureControlSensorIssue
OBJECT-IDENTITY
The air sensor selected for cooling control is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5617current
lgpCondId5621EEVSuperheatBelowThreshold
OBJECT-IDENTITY
Electronic expansion valve refrigerant low superheat event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5621current
lgpCondId5622EEVDischargeTempAboveThreshold
OBJECT-IDENTITY
Electronic expansion valve refrigerant high discharge temperature event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5622current
lgpCondId5623EEVBatteryIssue
OBJECT-IDENTITY
Electronic expansion valve battery cannot be recharged and needs to be replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5623current
lgpCondId5624EEVPowerIssue
OBJECT-IDENTITY
Electronic expansion valve lost power and is running on battery backup.
1.3.6.1.4.1.476.1.42.3.2.7.1.5624current
lgpCondId5625EEVUnspecifiedGeneralEvent
OBJECT-IDENTITY
One or more unspecified electronic expansion valve events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5625current
lgpCondId5629StaticPressureSensorIssue
OBJECT-IDENTITY
The static pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5629current
lgpCondId5630HighStaticPressure
OBJECT-IDENTITY
High static pressure event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5630current
lgpCondId5631LowStaticPressure
OBJECT-IDENTITY
Low static pressure event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5631current
lgpCondId5636PumpUnspecifiedGeneralEvent
OBJECT-IDENTITY
One or more unspecified pump events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5636current
lgpCondId5637CondenserUnitUnspecifiedGeneralEvent
OBJECT-IDENTITY
One or more unspecified condenser unit events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5637current
lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent
OBJECT-IDENTITY
One or more unspecified condenser circuit events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5638current
lgpCondId5642SFAReservedEvent1
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5642current
lgpCondId5643SFAReservedEvent2
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5643current
lgpCondId5644SFAReservedEvent3
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5644current
lgpCondId5645SFAReservedEvent4
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5645current
lgpCondId5646SFAReservedEvent5
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5646current
lgpCondId5647SFAReservedEvent6
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5647current
lgpCondId5648SFAReservedEvent7
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5648current
lgpCondId5649SFAReservedEvent8
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5649current
lgpCondId5650SFAReservedEvent9
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5650current
lgpCondId5651SFAReservedEvent10
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5651current
lgpCondId5652SFAReservedEvent11
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5652current
lgpCondId5653SFAReservedEvent12
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5653current
lgpCondId5654SFAReservedEvent13
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5654current
lgpCondId5655SFAReservedEvent14
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5655current
lgpCondId5656SFAReservedEvent15
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5656current
lgpCondId5657SFAReservedEvent16
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5657current
lgpCondId5658SFAReservedEvent17
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5658current
lgpCondId5659SFAReservedEvent18
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5659current
lgpCondId5660SFAReservedEvent19
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5660current
lgpCondId5661SFAReservedEvent20
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5661current
lgpCondId5662SFAReservedEvent21
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5662current
lgpCondId5663SFAReservedEvent22
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5663current
lgpCondId5664SFAReservedEvent23
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5664current
lgpCondId5665SFAReservedEvent24
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5665current
lgpCondId5666SFAReservedEvent25
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5666current
lgpCondId5768OutletAirOvertemperatureLimit
OBJECT-IDENTITY
The difference between the outlet air temperature and inlet air temperature exceeds a specified maximum temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.5768current
lgpCondId5769EMOShutdown
OBJECT-IDENTITY
An Emergency Module Off command has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5769current
lgpCondId5770TopOutletFanFault
OBJECT-IDENTITY
Top outlet fan fault - one or more top outlet fans have failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5770current
lgpCondId5771MMSOverCapacity
OBJECT-IDENTITY
The multi-module system load is larger than the apparent power limit setting.
1.3.6.1.4.1.476.1.42.3.2.7.1.5771current
lgpCondId5773CompressorCapacityNormal
OBJECT-IDENTITY
Compressor has returned to normal load capacity.
1.3.6.1.4.1.476.1.42.3.2.7.1.5773current
lgpCondId5774CompressorContactorIssue
OBJECT-IDENTITY
Compressor contactor is not closing during compressor startup or is not opening during compressor shutdown.
1.3.6.1.4.1.476.1.42.3.2.7.1.5774current
lgpCondId5775UnitShutdownUnspecifiedGeneralEvent
OBJECT-IDENTITY
One or more unspecified unit shutdown events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5775current
lgpCondId5776PDULowVoltageLN
OBJECT-IDENTITY
The system has detected a module under voltage condition (LN).
1.3.6.1.4.1.476.1.42.3.2.7.1.5776current
lgpCondId5777PDULowVoltageLL
OBJECT-IDENTITY
The system has detected a module under voltage condition (LL).
1.3.6.1.4.1.476.1.42.3.2.7.1.5777current
lgpCondId5778PDULowVoltageL1L2
OBJECT-IDENTITY
The system has detected a line-to-line under voltage condition (L1 -L2).
1.3.6.1.4.1.476.1.42.3.2.7.1.5778current
lgpCondId5779PDULowVoltageL2L3
OBJECT-IDENTITY
The system has detected a line-to-line under voltage condition (L2 -L3).
1.3.6.1.4.1.476.1.42.3.2.7.1.5779current
lgpCondId5780PDULowVoltageL3L1
OBJECT-IDENTITY
The system has detected a line-to-line under voltage condition (L3 -L1).
1.3.6.1.4.1.476.1.42.3.2.7.1.5780current
lgpCondId5781PDULowVoltageL1N
OBJECT-IDENTITY
The system has detected a line to neutral under voltage condition (L1-N).
1.3.6.1.4.1.476.1.42.3.2.7.1.5781current
lgpCondId5782PDULowVoltageL2N
OBJECT-IDENTITY
The system has detected a line to neutral under voltage condition (L2-N).
1.3.6.1.4.1.476.1.42.3.2.7.1.5782current
lgpCondId5783PDULowVoltageL3N
OBJECT-IDENTITY
The system has detected a line to neutral under voltage condition (L3-N).
1.3.6.1.4.1.476.1.42.3.2.7.1.5783current
lgpCondId5784BranchLowVoltageLN
OBJECT-IDENTITY
The system has detected a module under voltage condition (LN).
1.3.6.1.4.1.476.1.42.3.2.7.1.5784current
lgpCondId5785BranchLowVoltageLL
OBJECT-IDENTITY
The system has detected a module under voltage condition (LL).
1.3.6.1.4.1.476.1.42.3.2.7.1.5785current
lgpCondId5786BranchLowVoltage
OBJECT-IDENTITY
The system has detected a module under voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5786current
lgpCondId5788ContTieActive
OBJECT-IDENTITY
Continuous Power Tie Active.
1.3.6.1.4.1.476.1.42.3.2.7.1.5788current
lgpCondId5792UserkWhReset
OBJECT-IDENTITY
The user kWh accumulator was reset to zero by the operator.
1.3.6.1.4.1.476.1.42.3.2.7.1.5792current
lgpCondId5796PeakkWReset
OBJECT-IDENTITY
The Peak kW was reset.
1.3.6.1.4.1.476.1.42.3.2.7.1.5796current
lgpCondId5798BypassOverload
OBJECT-IDENTITY
Bypass overloaded, reduce load immediately.
1.3.6.1.4.1.476.1.42.3.2.7.1.5798current
lgpCondId5801LowBatteryShutdownImminent
OBJECT-IDENTITY
If active and guaranteed shutdown is enabled, a low battery reserve condition exists that will shutdown the UPS.
1.3.6.1.4.1.476.1.42.3.2.7.1.5801current
lgpCondId5806OutputOverload
OBJECT-IDENTITY
An overload exists on the output.
1.3.6.1.4.1.476.1.42.3.2.7.1.5806current
lgpCondId5807OutputOffPending
OBJECT-IDENTITY
Output off pending - shutdown imminent.
1.3.6.1.4.1.476.1.42.3.2.7.1.5807current
lgpCondId5808SystemShutdownOutputShort
OBJECT-IDENTITY
Shutdown was due to a short on the output.
1.3.6.1.4.1.476.1.42.3.2.7.1.5808current
lgpCondId5809SystemShutdownLowBattery
OBJECT-IDENTITY
Shutdown was due to a low battery condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5809current
lgpCondId5810SystemShutdownRemoteShutdown
OBJECT-IDENTITY
Shutdown was due to a remote communications shutdown command.
1.3.6.1.4.1.476.1.42.3.2.7.1.5810current
lgpCondId5811SystemShutdownHardwareFault
OBJECT-IDENTITY
Shutdown was due to an externally applied hardware control signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5811current
lgpCondId5817LossofRedundancy
OBJECT-IDENTITY
The system has an insufficient number of power modules to provide redundancy.
1.3.6.1.4.1.476.1.42.3.2.7.1.5817current
lgpCondId5818PowerModuleFailure
OBJECT-IDENTITY
One or more conditions indicate a power module failure, service is required.
1.3.6.1.4.1.476.1.42.3.2.7.1.5818current
lgpCondId5819PowerModuleWarning
OBJECT-IDENTITY
One or more power modules is reporting a warning condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5819current
lgpCondId5838PowerModuleFanFault
OBJECT-IDENTITY
The Power Module has detected a fan fault.
1.3.6.1.4.1.476.1.42.3.2.7.1.5838current
lgpCondId5839PowerModuleOverTemperature
OBJECT-IDENTITY
The Power Module has detected an over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5839current
lgpCondId5840PowerModuleShutdownOverTemperature
OBJECT-IDENTITY
Power Module has shutdown due to over temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.5840current
lgpCondId5842ChargerModuleFanFault
OBJECT-IDENTITY
The Charger Module has detected a fan fault.
1.3.6.1.4.1.476.1.42.3.2.7.1.5842current
lgpCondId5847BatteryModuleTemperatureSensorFault
OBJECT-IDENTITY
A Battery Module temperature sensor fault has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5847current
lgpCondId5848BatteryModuleOverTemperature
OBJECT-IDENTITY
The Battery Module has detected an over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5848current
lgpCondId5849ReplaceBatteryModule
OBJECT-IDENTITY
The Battery Module needs to be replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5849current
lgpCondId5850SystemShutdownTransformerOverTemperature
OBJECT-IDENTITY
System shutdown due to transformer over temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.5850current
lgpCondId5851MaximumLoadAlarm
OBJECT-IDENTITY
Maximum load alarm indicating load setting has been exceeded.
1.3.6.1.4.1.476.1.42.3.2.7.1.5851current
lgpCondId5856BatteryModuleFault
OBJECT-IDENTITY
One or more battery modules are reporting a fault condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5856current
lgpCondId5857BatteryModuleWarning
OBJECT-IDENTITY
One or more battery modules are reporting a warning condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5857current
lgpCondId5862CheckAirFilter
OBJECT-IDENTITY
Please check air filter, it may need to be cleaned or replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5862current
lgpCondId5863TransformerFanFault
OBJECT-IDENTITY
The transformer fan has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5863current
lgpCondId5865NoLoadWarning
OBJECT-IDENTITY
Indicates the UPS has output voltage but the output current is below a set threshold [No Load Warning Current Threshold] for a set period of time [No Load Warning Delay].
1.3.6.1.4.1.476.1.42.3.2.7.1.5865current
lgpCondId5871BatteryOverTemperatureLimit
OBJECT-IDENTITY
A battery temperature sensor is reporting a value above a predetermined limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5871current
lgpCondId5873UnexpectedMainBatteryDisconnectClosure
OBJECT-IDENTITY
The main battery disconnect has closed unexpectedly.
1.3.6.1.4.1.476.1.42.3.2.7.1.5873current
lgpCondId5874BatteryOverVoltage
OBJECT-IDENTITY
The system has detected that the battery voltage has exceeded a predetermined limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5874current
lgpCondId5875BatteryFuseFault
OBJECT-IDENTITY
One or more battery fuse faults has occurred.
1.3.6.1.4.1.476.1.42.3.2.7.1.5875current
lgpCondId5878MainBatteryDisconnectForcedToUnlock
OBJECT-IDENTITY
The main battery disconnect is forced to the unlocked state.
1.3.6.1.4.1.476.1.42.3.2.7.1.5878current
lgpCondId5879VdcBackfeed
OBJECT-IDENTITY
The voltage between battery and DC bus measurements is out of tolerance.
1.3.6.1.4.1.476.1.42.3.2.7.1.5879current
lgpCondId5880RectifierConfigurationChangeRequest
OBJECT-IDENTITY
This event indicates that the battery is not configured and PFC is not enabled.
1.3.6.1.4.1.476.1.42.3.2.7.1.5880current
lgpCondId5881RegenerationActive
OBJECT-IDENTITY
Regeneration operation is active.
1.3.6.1.4.1.476.1.42.3.2.7.1.5881current
lgpCondId5882RegenerationOperationTerminated
OBJECT-IDENTITY
Regeneration operation is not active.
1.3.6.1.4.1.476.1.42.3.2.7.1.5882current
lgpCondId5883RegenerationOperationFailure
OBJECT-IDENTITY
Regeneration operation has been terminated due to bypass source instability or unit misoperation.
1.3.6.1.4.1.476.1.42.3.2.7.1.5883current
lgpCondId5884ProgramInputContact01
OBJECT-IDENTITY
When the signal from [Program Input Contact 01] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5884current
lgpCondId5885ProgramInputContact02
OBJECT-IDENTITY
When the signal from [Program Input Contact 02] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5885current
lgpCondId5886ProgramInputContact03
OBJECT-IDENTITY
When the signal from [Program Input Contact 03] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5886current
lgpCondId5887ProgramInputContact04
OBJECT-IDENTITY
When the signal from [Program Input Contact 04] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5887current
lgpCondId5888ProgramInputContact05
OBJECT-IDENTITY
When the signal from [Program Input Contact 05] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5888current
lgpCondId5889ProgramInputContact06
OBJECT-IDENTITY
When the signal from [Program Input Contact 06] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5889current
lgpCondId5890ProgramInputContact07
OBJECT-IDENTITY
When the signal from [Program Input Contact 07] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5890current
lgpCondId5891ProgramInputContact08
OBJECT-IDENTITY
When the signal from [Program Input Contact 08] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5891current
lgpCondId5892ProgramInputContact09
OBJECT-IDENTITY
When the signal from [Program Input Contact 09] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5892current
lgpCondId5893ProgramInputContact10
OBJECT-IDENTITY
When the signal from [Program Input Contact 10] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5893current
lgpCondId5894ProgramInputContact11
OBJECT-IDENTITY
When the signal from [Program Input Contact 11] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5894current
lgpCondId5895ProgramInputContact12
OBJECT-IDENTITY
When the signal from [Program Input Contact 12] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5895current
lgpCondId5896GroundFaultDetected
OBJECT-IDENTITY
The system has detected a ground fault on a Battery-String.
1.3.6.1.4.1.476.1.42.3.2.7.1.5896current
lgpCondId5902ReturnHumiditySensorIssue
OBJECT-IDENTITY
The humidity sensor at the inlet of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5902current
lgpCondId5903CompressorLowDifferentialPressureLockout
OBJECT-IDENTITY
Compressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled.
1.3.6.1.4.1.476.1.42.3.2.7.1.5903current
lgpCondId5906AirflowSensorIssue
OBJECT-IDENTITY
Airflow sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5906current
lgpCondId5907ExtAirDamperPositionIssue
OBJECT-IDENTITY
Air damper position does not match expected value, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5907current
lgpCondId5908ExtPowerSourceAFailure
OBJECT-IDENTITY
Unit main power source A failure, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5908current
lgpCondId5909ExtPowerSourceBFailure
OBJECT-IDENTITY
Unit main power source B failure, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5909current
lgpCondId5910StaticPressureSensorOutofRange
OBJECT-IDENTITY
Static pressure sensor signal is out of its configured range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5910current
lgpCondId5911FluidTemperatureSensorIssue
OBJECT-IDENTITY
The fluid temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5911current
lgpCondId5912FluidFlowSensorIssue
OBJECT-IDENTITY
The fluid flow sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5912current
lgpCondId5914OverDifferentialPressure
OBJECT-IDENTITY
An over differential pressure condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5914current
lgpCondId5915UnderDifferentialPressure
OBJECT-IDENTITY
An under differential pressure condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5915current
lgpCondId5924MixedModeLockout
OBJECT-IDENTITY
Mixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on one refrigeration circuit and the use of a refrigerant pump on the other circuit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5924current
lgpCondId5928UnbalancedLoadCondition
OBJECT-IDENTITY
The system has detected a line-to-line unbalanced load condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5928current
lgpCondId5939BranchOverCurrentProtection
OBJECT-IDENTITY
The Branch Receptacle Module's over current protection is triggered.
1.3.6.1.4.1.476.1.42.3.2.7.1.5939current
lgpCondId5948BranchLowVoltageLL
OBJECT-IDENTITY
The system has detected a module under voltage condition (LL).
1.3.6.1.4.1.476.1.42.3.2.7.1.5948current
lgpCondId5957BypassInputVoltageFault
OBJECT-IDENTITY
The system has detected the bypass voltage is unqualified.
1.3.6.1.4.1.476.1.42.3.2.7.1.5957current
lgpCondId5958BatteryTemperatureOutofRange
OBJECT-IDENTITY
Battery temperature is outside of acceptable range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5958current
lgpCondId5960InverterOverload
OBJECT-IDENTITY
Inverter in overload fault.
1.3.6.1.4.1.476.1.42.3.2.7.1.5960current
lgpCondId5966AuxAirTempDeviceCommunicationLost
OBJECT-IDENTITY
Communication with external auxiliary device providing an air temperature value has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.5966current
lgpCondId5967ModbusPowerMeterCommunicationLost
OBJECT-IDENTITY
Communication with Modbus power meter has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.5967current
lgpCondId5968InverterDesaturation
OBJECT-IDENTITY
Inverter Desaturation.
1.3.6.1.4.1.476.1.42.3.2.7.1.5968current
lgpCondId5969GenericDICFault
OBJECT-IDENTITY
The control board reports a fault - Service required.
1.3.6.1.4.1.476.1.42.3.2.7.1.5969current
lgpCondId5970GroundFault
OBJECT-IDENTITY
An AC phase to ground fault or three phase fault to ground exists on the output of the UPS.
1.3.6.1.4.1.476.1.42.3.2.7.1.5970current
lgpCondId5973InputBreakerOpen
OBJECT-IDENTITY
The main input breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5973current
lgpCondId5974NeutralBreakerOpen
OBJECT-IDENTITY
The neutral breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5974current
lgpCondId5975OutputBreakerOpen
OBJECT-IDENTITY
The output breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5975current
lgpCondId5976MaintenanceBypassBreakerClosed
OBJECT-IDENTITY
The maintenance bypass breaker is closed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5976current
lgpCondId5977BatteryBreakerOpen
OBJECT-IDENTITY
The battery circuit is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5977current
lgpCondId5978RectifierIsolationBreakerRFBOpen
OBJECT-IDENTITY
The rectifier isolation breaker (RFB) indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.5978current
lgpCondId5982BypassBreakerSBBOpen
OBJECT-IDENTITY
The bypass circuit breaker (SBB) indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.5982current
lgpCondId5983BypassIsolationBreakerBIBOpen
OBJECT-IDENTITY
The bypass isolation breaker (BIB) indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.5983current
lgpCondId5984BypassUndervoltageWarning
OBJECT-IDENTITY
The voltage on one or more bypass phases is less than a specified percentage of the nominal voltage.
1.3.6.1.4.1.476.1.42.3.2.7.1.5984current
lgpCondId5985BypassStaticSwitchBPSSOn
OBJECT-IDENTITY
The Bypass Static Switch has been turned on.
1.3.6.1.4.1.476.1.42.3.2.7.1.5985current
lgpCondId5998BattOvtempWarning
OBJECT-IDENTITY
A battery temperature sensor is reporting a value above the setpoint.
1.3.6.1.4.1.476.1.42.3.2.7.1.5998current
lgpCondId6009InverterOutputBreakerOpen
OBJECT-IDENTITY
The inverter output breaker indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.6009current
lgpCondId6011EquipmentOverTempWarning
OBJECT-IDENTITY
Equipment over temperature warning is a summary event based on the detection of at least one measured temperature exceeding a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6011current
lgpCondId6012EquipmentOvertemperatureLimit
OBJECT-IDENTITY
The equipment air temperature has exceeded its maximum set point.
1.3.6.1.4.1.476.1.42.3.2.7.1.6012current
lgpCondId6045RectifierInputBreakerOpen
OBJECT-IDENTITY
The rectifier isolation breaker indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.6045current
lgpCondId6046LoadonUPS
OBJECT-IDENTITY
The output is being supplied power from the inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.6046current
lgpCondId6047Core2CoreFuseFailure
OBJECT-IDENTITY
Core-2-core fuse failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6047current
lgpCondId6052SystemOutputBreakerOpen
OBJECT-IDENTITY
The system output breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6052current
lgpCondId6059InverterRelayFault
OBJECT-IDENTITY
The inverter relay has malfunctioned.
1.3.6.1.4.1.476.1.42.3.2.7.1.6059current
lgpCondId6060TransfertoBypassSystemOverload
OBJECT-IDENTITY
The UPS System has transferred to bypass because the active power modules cannot support the critical load.
1.3.6.1.4.1.476.1.42.3.2.7.1.6060current
lgpCondId6061InputSourceBackfeed
OBJECT-IDENTITY
The battery is backfeeding the input source.
1.3.6.1.4.1.476.1.42.3.2.7.1.6061current
lgpCondId6062LossofSynchronization
OBJECT-IDENTITY
The inverter and bypass are no longer synchronized. .
1.3.6.1.4.1.476.1.42.3.2.7.1.6062current
lgpCondId6063BatteryConverterCurrentLimit
OBJECT-IDENTITY
The battery converter has reached is maximum current limit. .
1.3.6.1.4.1.476.1.42.3.2.7.1.6063current
lgpCondId6064LBSCableFailure
OBJECT-IDENTITY
Load Bus Sync communications is abnormal. A problem with the LBS cable may exist.
1.3.6.1.4.1.476.1.42.3.2.7.1.6064current
lgpCondId6065BatteryChargeEqualizationTimeout
OBJECT-IDENTITY
The battery equalizing is time out.
1.3.6.1.4.1.476.1.42.3.2.7.1.6065current
lgpCondId6066ParallelCableFailure
OBJECT-IDENTITY
The UPS parallel system communications is abnormal. A problem with the parallel cable may exist.
1.3.6.1.4.1.476.1.42.3.2.7.1.6066current
lgpCondId6067BatteryFault
OBJECT-IDENTITY
A short circuit exists in the battery system.
1.3.6.1.4.1.476.1.42.3.2.7.1.6067current
lgpCondId6068BatteryRoomAlarm
OBJECT-IDENTITY
The ambient temperature of the battery room is abnormal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6068current
lgpCondId6080UPSCCommunicationFailure
OBJECT-IDENTITY
The UPSC has failed to communicate in a designated time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.6080current
lgpCondId6092Compressor1BThermalOverload
OBJECT-IDENTITY
Fixed compressor 1B is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6092current
lgpCondId6093Compressor2BThermalOverload
OBJECT-IDENTITY
Fixed compressor 2B is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6093current
lgpCondId6094Compressor1BHoursExceeded
OBJECT-IDENTITY
Fixed compressor 1B run hours have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6094current
lgpCondId6095Compressor2BHoursExceeded
OBJECT-IDENTITY
Fixed compressor 2B run hours have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6095current
lgpCondId6100CondenserRemoteShutdown
OBJECT-IDENTITY
Condenser is shut down by a remote signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6100current
lgpCondId6105ExternalCondenserTVSSIssue
OBJECT-IDENTITY
The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6105current
lgpCondId6106ExternalCondenserVFDIssue
OBJECT-IDENTITY
The condenser fan Variable Frequency Drive is offline, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6106current
lgpCondId6107ExternalCondenserIssue
OBJECT-IDENTITY
Condenser is not operating within its operational parameters, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6107current
lgpCondId6119Slotsnotavailable
OBJECT-IDENTITY
The number of sensors exceeds the number of allocated slots and cannot be displayed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6119current
lgpCondId6180BatteryUnderVoltage
OBJECT-IDENTITY
Battery voltage is too low.
1.3.6.1.4.1.476.1.42.3.2.7.1.6180current
lgpCondId6182ReplaceBattery
OBJECT-IDENTITY
The battery is due for replacement.
1.3.6.1.4.1.476.1.42.3.2.7.1.6182current
lgpCondId6186InputFrequencyDeviation
OBJECT-IDENTITY
The input frequency is outside of the normal range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6186current
lgpCondId6187ShutdownPending
OBJECT-IDENTITY
Shutdown is pending.
1.3.6.1.4.1.476.1.42.3.2.7.1.6187current
lgpCondId6194SystemRebootCommandIssued
OBJECT-IDENTITY
Reboot command issued to the system.
1.3.6.1.4.1.476.1.42.3.2.7.1.6194current
lgpCondId6203SensorAdded
OBJECT-IDENTITY
Sensor Added.
1.3.6.1.4.1.476.1.42.3.2.7.1.6203current
lgpCondId6204SensorRemoved
OBJECT-IDENTITY
Sensor Removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6204current
lgpCondId6205WaterLeakDetected
OBJECT-IDENTITY
Water leak detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6205current
lgpCondId6210FirmwareUpdateInProgress
OBJECT-IDENTITY
Firmware update has started and is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.6210current
lgpCondId6211FirmwareUpdateCompletedSuccessfully
OBJECT-IDENTITY
Firmware update has completed successfully.
1.3.6.1.4.1.476.1.42.3.2.7.1.6211current
lgpCondId6212FirmwareUpdateCompletedUnsuccessfully
OBJECT-IDENTITY
Firmware update has completed, but was not successful.
1.3.6.1.4.1.476.1.42.3.2.7.1.6212current
lgpCondId6216PrechargeCircuitFailed
OBJECT-IDENTITY
DC Bus precharge/discharge didn't reach specified level within a specified time.
1.3.6.1.4.1.476.1.42.3.2.7.1.6216current
lgpCondId6217MemoryCardRemoved
OBJECT-IDENTITY
The memory card on the control board has been removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6217current
lgpCondId6218AutoCalibrationActive
OBJECT-IDENTITY
The system is automatically calibrating ADC channels.
1.3.6.1.4.1.476.1.42.3.2.7.1.6218current
lgpCondId6219AutoCalibrationFailed
OBJECT-IDENTITY
ADC channel calibration has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6219current
lgpCondId6220ModuleOutputBreakerOpen
OBJECT-IDENTITY
The module output breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6220current
lgpCondId6221NeutralVoltageFault
OBJECT-IDENTITY
Voltage observed on neutral line.
1.3.6.1.4.1.476.1.42.3.2.7.1.6221current
lgpCondId6222BranchLoadLoss
OBJECT-IDENTITY
Loss of load on branch detected. Branch circuit breaker might be open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6222current
lgpCondId6225RemoteSensorLowHumidity
OBJECT-IDENTITY
Remote sensor humidity has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6225current
lgpCondId6226RemoteSensorHighHumidity
OBJECT-IDENTITY
Remote sensor humidity has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6226current
lgpCondId6227RemoteSensorAverageLowHumidity
OBJECT-IDENTITY
The average humidity of multiple remote sensors on the cooling unit has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6227current
lgpCondId6228RemoteSensorAverageHighHumidity
OBJECT-IDENTITY
The average humidity of multiple remote sensors on the cooling unit has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6228current
lgpCondId6229RemoteSensorSystemAverageLowHumidity
OBJECT-IDENTITY
The average humidity of multiple remote sensors on interconnected cooling units in a single system has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6229current
lgpCondId6230RemoteSensorSystemAverageHighHumidity
OBJECT-IDENTITY
The average humidity of multiple remote sensors on interconnected cooling units in a single system has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6230current
lgpCondId6231LowCompressorSuperheat
OBJECT-IDENTITY
Compressor suction superheat has dropped below a lower threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6231current
lgpCondId6232SECUnspecifiedGeneralEvent
OBJECT-IDENTITY
One or more unspecified events active for the Superheat and Envelope Controller. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.6232current
lgpCondId6233SECCommunicationLost
OBJECT-IDENTITY
Communication with the Superheat and Envelope Controller has been lost. The event is deactivated when communication is re -established.
1.3.6.1.4.1.476.1.42.3.2.7.1.6233current
lgpCondId6236PowerSourceAIssue
OBJECT-IDENTITY
No power is detected at power source input 'A'.
1.3.6.1.4.1.476.1.42.3.2.7.1.6236current
lgpCondId6237PowerSourceBIssue
OBJECT-IDENTITY
No power is detected at power source input 'B'.
1.3.6.1.4.1.476.1.42.3.2.7.1.6237current
lgpCondId6239FluidValveHoursExceeded
OBJECT-IDENTITY
Operating hours for the fluid valve have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6239current
lgpCondId6253BoosterFailure
OBJECT-IDENTITY
Booster failure - boost is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6253current
lgpCondId6254ChargerFailure
OBJECT-IDENTITY
Charger Failure - Charger is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6254current
lgpCondId6274UnitTopReturnAirSensorFailure
OBJECT-IDENTITY
Return air sensor at the top of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6274current
lgpCondId6275UnitMiddleReturnAirSensorFailure
OBJECT-IDENTITY
Return air sensor in the middle of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6275current
lgpCondId6276UnitBottomReturnAirSensorFailure
OBJECT-IDENTITY
Return air sensor at the bottom of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6276current
lgpCondId6277UnitTopSupplyAirSensorFailure
OBJECT-IDENTITY
Supply air sensor at the top of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6277current
lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure
OBJECT-IDENTITY
First supply air sensor in the middle of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6278current
lgpCondId6279UnitBottomSupplyAirSensorFailure
OBJECT-IDENTITY
Supply air sensor at the bottom of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6279current
lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure
OBJECT-IDENTITY
Second supply air sensor in the middle of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6284current
lgpCondId6293ChilledWaterControlActive
OBJECT-IDENTITY
Chilled water inlet temperature control function is enabled due to 'bad' water.
1.3.6.1.4.1.476.1.42.3.2.7.1.6293current
lgpCondId6294ChilledWaterFlowTransducerFailure
OBJECT-IDENTITY
Chilled water flow transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6294current
lgpCondId6295ChilledWaterInletTemperatureSensorFailure
OBJECT-IDENTITY
Chilled water inlet temperature sensor is disconnected or the signal is out of range. The sensor is mandatory for the chilled water flow function.
1.3.6.1.4.1.476.1.42.3.2.7.1.6295current
lgpCondId6296ChilledWaterHighInletTemperature
OBJECT-IDENTITY
Chilled water inlet temperature has exceeded an upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6296current
lgpCondId6297Modbus010VModuleCommunicationFailure
OBJECT-IDENTITY
Modbus 0-10V module for managing the second Chilled Water circuit valve is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6297current
lgpCondId6299RackDoorsOpen
OBJECT-IDENTITY
Rack doors opened due to supply air temperature exceeding the [Rack Door Open High Supply Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.6299current
lgpCondId6303TeamStaticPressureSensorFailure
OBJECT-IDENTITY
The team static pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6303current
lgpCondId6304HeatingLockout
OBJECT-IDENTITY
Heating is shut down and disabled.
1.3.6.1.4.1.476.1.42.3.2.7.1.6304current
lgpCondId6305FreeCoolingStoppedHighRoomTemp
OBJECT-IDENTITY
Free cooling is temporarily disabled due to room temperature exceeding a preset delta above the the set point.
1.3.6.1.4.1.476.1.42.3.2.7.1.6305current
lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure
OBJECT-IDENTITY
Cold aisle team sensor measuring air temperature and humidity is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6306current
lgpCondId6309ColdAisleAirSensorFailure
OBJECT-IDENTITY
Cold aisle sensor measuring air temperature and humidity is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6309current
lgpCondId6310ChilledWaterInletTemperatureControlActive
OBJECT-IDENTITY
Chilled water inlet temperature control is active.
1.3.6.1.4.1.476.1.42.3.2.7.1.6310current
lgpCondId6313ChilledWaterInletTemperatureSensorFailure
OBJECT-IDENTITY
Chilled water inlet temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6313current
lgpCondId6314ChilledWaterOutletTemperatureSensorFailure
OBJECT-IDENTITY
Chilled water outlet temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6314current
lgpCondId6315ChilledWaterFlowMeterSensorFailure
OBJECT-IDENTITY
Chilled water flow meter sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6315current
lgpCondId6333Bypassoutofsync
OBJECT-IDENTITY
Bypass and Inverter inputs are not in sync.
1.3.6.1.4.1.476.1.42.3.2.7.1.6333current
lgpCondId6348SystemOutputoffasrequested
OBJECT-IDENTITY
The UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6348current
lgpCondId6349SystemOffasrequested
OBJECT-IDENTITY
The entire UPS has shutdown as commanded.
1.3.6.1.4.1.476.1.42.3.2.7.1.6349current
lgpCondId6350GeneralFault
OBJECT-IDENTITY
A general fault in the UPS has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6350current
lgpCondId6351UPSAwaitingPower
OBJECT-IDENTITY
The UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.4.1.476.1.42.3.2.7.1.6351current
lgpCondId6352AutonomyCalibration
OBJECT-IDENTITY
Calibration test occurred.
1.3.6.1.4.1.476.1.42.3.2.7.1.6352current
lgpCondId6353GeneralWarning
OBJECT-IDENTITY
A warning in the UPS has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6353current
lgpCondId6354BatteryCharging
OBJECT-IDENTITY
The UPS battery is charging (battery charge percentage lower than 98).
1.3.6.1.4.1.476.1.42.3.2.7.1.6354current
lgpCondId6355BackfeedRelayFailure
OBJECT-IDENTITY
Bypass SCR is wrongly on or commutated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6355current
lgpCondId6356BatteryCircuitOpen
OBJECT-IDENTITY
Battery Circuit Open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6356current
lgpCondId6357SystemRestartPending
OBJECT-IDENTITY
A request for UPS restart has been received.
1.3.6.1.4.1.476.1.42.3.2.7.1.6357current
lgpCondId6358PipeTemperatureSensorFailure
OBJECT-IDENTITY
Air temperature sensor located in the pipe is not sending a valid value.
1.3.6.1.4.1.476.1.42.3.2.7.1.6358current
lgpCondId6362SFAReservedEvent26
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6362current
lgpCondId6363SFAReservedEvent27
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6363current
lgpCondId6364SFAReservedEvent28
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6364current
lgpCondId6365SFAReservedEvent29
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6365current
lgpCondId6366SFAReservedEvent30
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6366current
lgpCondId6367SFAReservedEvent31
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6367current
lgpCondId6368SFAReservedEvent32
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6368current
lgpCondId6369SFAReservedEvent33
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6369current
lgpCondId6370SFAReservedEvent34
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6370current
lgpCondId6371SFAReservedEvent35
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6371current
lgpCondId6372SFAReservedEvent36
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6372current
lgpCondId6373SFAReservedEvent37
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6373current
lgpCondId6374SFAReservedEvent38
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6374current
lgpCondId6375SFAReservedEvent39
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6375current
lgpCondId6376SFAReservedEvent40
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6376current
lgpCondId6377SFAReservedEvent41
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6377current
lgpCondId6378SFAReservedEvent42
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6378current
lgpCondId6379SFAReservedEvent43
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6379current
lgpCondId6380SFAReservedEvent44
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6380current
lgpCondId6381SFAReservedEvent45
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6381current
lgpCondId6382SFAReservedEvent46
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6382current
lgpCondId6383SFAReservedEvent47
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6383current
lgpCondId6384SFAReservedEvent48
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6384current
lgpCondId6385SFAReservedEvent49
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6385current
lgpCondId6386SFAReservedEvent50
OBJECT-IDENTITY
Reserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6386current
lgpCondId6438PowerModuleInputCurrentAbnormal
OBJECT-IDENTITY
Input current of the power module is abnormal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6438current
lgpCondId6439PowerModuleBalancerofDCBusFailure
OBJECT-IDENTITY
Balancer of DC Bus in the power module has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6439current
lgpCondId6440PowerModuleFuseFailure
OBJECT-IDENTITY
A summary event indicating one or more fuse failures in the power module.
1.3.6.1.4.1.476.1.42.3.2.7.1.6440current
lgpCondId6441PowerModulePowerSupplyFailure
OBJECT-IDENTITY
Power module power supply failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6441current
lgpCondId6450PDUPoweredOn
OBJECT-IDENTITY
The PDU was powered on.
1.3.6.1.4.1.476.1.42.3.2.7.1.6450current
lgpCondId6453InputWiringFault
OBJECT-IDENTITY
The neutral/ground conductors on the input wiring are not properly bonded, or the line/neutral conductors have been swapped.
1.3.6.1.4.1.476.1.42.3.2.7.1.6453current
lgpCondId6454DCtoDCConverterFault
OBJECT-IDENTITY
A failure has occurred in the battery discharge circuit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6454current
lgpCondId6455LeakSensorCableFault
OBJECT-IDENTITY
A fault is detected in the 'Leak Sensor' cable.
1.3.6.1.4.1.476.1.42.3.2.7.1.6455current
lgpCondId6518StandbyUnitActivatedDuetoChillerFailure
OBJECT-IDENTITY
External chiller unit has failed for this unit, so the standby cooling unit has been activated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6518current
lgpCondId6522PDUResidualOverCurrent
OBJECT-IDENTITY
The system has detected a PDU residual over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6522current
lgpCondId6527PDUOverCurrentProtection
OBJECT-IDENTITY
The PDU over current protection is triggered.
1.3.6.1.4.1.476.1.42.3.2.7.1.6527current
lgpCondId6528PowerModuleLeverUnlocked
OBJECT-IDENTITY
The power module is inactive because the lever is in the unlocked position.
1.3.6.1.4.1.476.1.42.3.2.7.1.6528current
lgpCondId6529HardwareMismatch
OBJECT-IDENTITY
The assigned system model settings do not match the actual installed hardware. The module count is wrong, or a module of the wrong type is installed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6529current
lgpCondId6530SupplyNTCAirSensorIssue
OBJECT-IDENTITY
The supply NTC air sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6530current
lgpCondId6531ExternalAirSensorCIssue
OBJECT-IDENTITY
The external air sensor C is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6531current
lgpCondId6532ExternalAirSensorDIssue
OBJECT-IDENTITY
The external air sensor D is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6532current
lgpCondId6533ExternalAirSensorEIssue
OBJECT-IDENTITY
The external air sensor E is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6533current
lgpCondId6534PumpThermalOverload
OBJECT-IDENTITY
Pump is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6534current
lgpCondId6535XDModuleCommunicationLost
OBJECT-IDENTITY
Communication with XD Module has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.6535current
lgpCondId6536MMSCapacityExceeded
OBJECT-IDENTITY
The critical load is larger than the redundant rating of a 1+N redundant multi-module system.
1.3.6.1.4.1.476.1.42.3.2.7.1.6536current
lgpCondId6538TSAControlInputIssue
OBJECT-IDENTITY
The analog input used to set the air temperature set point for cooling control is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6538current
lgpCondId6539ChilledWaterValveHoursExceeded
OBJECT-IDENTITY
[Chilled Water Valve Hours] has exceeded [Chilled Water Valve Operating Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.6539current
lgpCondId6540FSAControlInputIssue
OBJECT-IDENTITY
The analog input used to set the air temperature set point for fan speed control is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6540current
lgpCondId6541AutoTuneLicenseExpiring
OBJECT-IDENTITY
License for the AutoTune feature has not been refreshed in 30 days and will be expiring soon.
1.3.6.1.4.1.476.1.42.3.2.7.1.6541current
lgpCondId6542AutoTuneLicenseExpired
OBJECT-IDENTITY
License for the AutoTune feature has expired.
1.3.6.1.4.1.476.1.42.3.2.7.1.6542current
lgpCondId6543UnitInStandbyDueToCoolingLoss
OBJECT-IDENTITY
Unit forced into standby because it is unable to provide any cooling.
1.3.6.1.4.1.476.1.42.3.2.7.1.6543current
lgpCondId6544ControlUnitsRemoteShutdownMismatch
OBJECT-IDENTITY
The remote shutdown status of the primary control unit does not match the remote shutdown status of the secondary control unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6544current
lgpCondId6545SecondaryControlUnitCommunicationLost
OBJECT-IDENTITY
The primary control unit has lost Ethernet communications with the secondary control unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6545current
lgpCondId6546ControlUnitsUnitCodeMismatch
OBJECT-IDENTITY
Unit codes for the primary and secondary control units do not match.
1.3.6.1.4.1.476.1.42.3.2.7.1.6546current
lgpCondId6547SSAControlInputIssue
OBJECT-IDENTITY
The analog input used to set the static pressure set point for fan speed control is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6547current
lgpCondId6574SubfeedPhaseUndercurrent
OBJECT-IDENTITY
Subfeed breaker phase current has dropped below the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6574current
lgpCondId6587TransferCountCleared
OBJECT-IDENTITY
A system event indicating the transfer count has been cleared.
1.3.6.1.4.1.476.1.42.3.2.7.1.6587current
lgpCondId6588EnergyCounterCleared
OBJECT-IDENTITY
A system event indicating the energy counter (e.g. KWH) has been cleared.
1.3.6.1.4.1.476.1.42.3.2.7.1.6588current
lgpCondId6589HistoryLogsFull
OBJECT-IDENTITY
The history logs are full.
1.3.6.1.4.1.476.1.42.3.2.7.1.6589current
lgpCondId6590HistoryLogsCleared
OBJECT-IDENTITY
History logs have been cleared.
1.3.6.1.4.1.476.1.42.3.2.7.1.6590current
lgpCondId6591EventLogCleared
OBJECT-IDENTITY
All past alarms and faults have been cleared.
1.3.6.1.4.1.476.1.42.3.2.7.1.6591current
lgpCondId6592SystemDateChanged
OBJECT-IDENTITY
The system date has been updated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6592current
lgpCondId6593SystemTimeChanged
OBJECT-IDENTITY
The system time has been updated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6593current
lgpCondId6594AccessPasswordChanged
OBJECT-IDENTITY
The access password has been changed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6594current
lgpCondId6595ConfigModified
OBJECT-IDENTITY
A setpoint has been updated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6595current
lgpCondId6612SCRShort
OBJECT-IDENTITY
The SCR is in a short condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6612current
lgpCondId6613SCROpen
OBJECT-IDENTITY
The SCR is in an open condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6613current
lgpCondId6614ACPowerSupplyFail
OBJECT-IDENTITY
A failure of the AC Power Supply has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6614current
lgpCondId6615DCPowerSupplyFail
OBJECT-IDENTITY
A failure of the DC Power Supply has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6615current
lgpCondId6616VoltageSensorFail
OBJECT-IDENTITY
A voltage sensor failure has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6616current
lgpCondId6617SCRSensorFail
OBJECT-IDENTITY
The SCR sensor module failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6617current
lgpCondId6618CurrentSensorFail
OBJECT-IDENTITY
The current sensor module failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6618current
lgpCondId6619GateDriveFail
OBJECT-IDENTITY
The Gate Drive module failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6619current
lgpCondId6620SurgeFail
OBJECT-IDENTITY
The surge module failed for the input source.
1.3.6.1.4.1.476.1.42.3.2.7.1.6620current
lgpCondId6621FastUnderVoltage
OBJECT-IDENTITY
Fast under voltage detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6621current
lgpCondId6622SlowUnderVoltage
OBJECT-IDENTITY
Slow under voltage detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6622current
lgpCondId6623OverVoltage
OBJECT-IDENTITY
Over voltage detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6623current
lgpCondId6624OverUnderFrequencyFail
OBJECT-IDENTITY
An over or under frequency condition has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6624current
lgpCondId6625GeneralSourceFailure
OBJECT-IDENTITY
A non-specific failure has been detected in the source.
1.3.6.1.4.1.476.1.42.3.2.7.1.6625current
lgpCondId6626OverCurrent
OBJECT-IDENTITY
An over current has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6626current
lgpCondId6627PeakCurrentOffLimit
OBJECT-IDENTITY
The peak current has exceeded the setpoint defined by I-PK Xfer Lockout.
1.3.6.1.4.1.476.1.42.3.2.7.1.6627current
lgpCondId6628SyncFail
OBJECT-IDENTITY
A phase rotation/out of synchronization failure has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6628current
lgpCondId6629InputOverVoltage
OBJECT-IDENTITY
Input over voltage.
1.3.6.1.4.1.476.1.42.3.2.7.1.6629current
lgpCondId6630InputUnderVoltage
OBJECT-IDENTITY
Input under voltage.
1.3.6.1.4.1.476.1.42.3.2.7.1.6630current
lgpCondId6631InputOverUnderFrequency
OBJECT-IDENTITY
Input over/under frequency.
1.3.6.1.4.1.476.1.42.3.2.7.1.6631current
lgpCondId6635VoltageSenseFail
OBJECT-IDENTITY
Output voltage sense failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6635current
lgpCondId6636LoadonAlternateSource
OBJECT-IDENTITY
The load is on the alternate source.
1.3.6.1.4.1.476.1.42.3.2.7.1.6636current
lgpCondId6637UnderVoltageFail
OBJECT-IDENTITY
Output under voltage failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6637current
lgpCondId6638OutputOverCurrent
OBJECT-IDENTITY
Output is over current.
1.3.6.1.4.1.476.1.42.3.2.7.1.6638current
lgpCondId6639GroundOverCurrent
OBJECT-IDENTITY
Ground is over current.
1.3.6.1.4.1.476.1.42.3.2.7.1.6639current
lgpCondId6640NeutralOverCurrent
OBJECT-IDENTITY
Neutral is over current.
1.3.6.1.4.1.476.1.42.3.2.7.1.6640current
lgpCondId6641LoadVoltageTHD
OBJECT-IDENTITY
Load voltage THD has exceeded the set limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6641current
lgpCondId6662ControlLogicFail
OBJECT-IDENTITY
A control logic module has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6662current
lgpCondId6663PowerSupplyLogicFail
OBJECT-IDENTITY
A power supply module has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6663current
lgpCondId6664ExternalCommsFailure
OBJECT-IDENTITY
External communications failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6664current
lgpCondId6665HeatSinkOverTemp
OBJECT-IDENTITY
The system heat sink temperature has exceeded design limits.
1.3.6.1.4.1.476.1.42.3.2.7.1.6665current
lgpCondId6666AutomaticTransferInhibited
OBJECT-IDENTITY
Automatic transfer is inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.6666current
lgpCondId6667InputSourceTransferInhibited
OBJECT-IDENTITY
Input source transfer is inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.6667current
lgpCondId6676CB1ShuntTrip
OBJECT-IDENTITY
CB1 Shunt Trip event.
1.3.6.1.4.1.476.1.42.3.2.7.1.6676current
lgpCondId6677CB2ShuntTrip
OBJECT-IDENTITY
CB2 Shunt Trip event.
1.3.6.1.4.1.476.1.42.3.2.7.1.6677current
lgpCondId6678CB6NeutralOpen
OBJECT-IDENTITY
CB6 neutral open event.
1.3.6.1.4.1.476.1.42.3.2.7.1.6678current
lgpCondId6679ContactorNeutralFail
OBJECT-IDENTITY
Contactor Neutral Fail event.
1.3.6.1.4.1.476.1.42.3.2.7.1.6679current
lgpCondId6680CB1BreakerOpen
OBJECT-IDENTITY
CB1 Breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6680current
lgpCondId6681CB2BreakerOpen
OBJECT-IDENTITY
CB2 Breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6681current
lgpCondId6682CB4BreakerClosed
OBJECT-IDENTITY
CB4 breaker closed event. Normal state is breaker open. Latched state is breaker closed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6682current
lgpCondId6683CB5BreakerClosed
OBJECT-IDENTITY
CB5 breaker closed event. Normal state is breaker open. Latched state is breaker closed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6683current
lgpCondId6684CB3BreakerOpen
OBJECT-IDENTITY
CB3 breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6684current
lgpCondId6685CB3ABreakerOpen
OBJECT-IDENTITY
CB3A breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6685current
lgpCondId6686CB6BreakerOpen
OBJECT-IDENTITY
CB6 breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6686current
lgpCondId6687CB7BreakerOpen
OBJECT-IDENTITY
CB7 breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6687current
lgpCondId6691GroupIndependentOn
OBJECT-IDENTITY
The group standby/cascade state for this unit has been overridden. The unit has been forced on.
1.3.6.1.4.1.476.1.42.3.2.7.1.6691current
lgpCondId6692GroupIndependentOff
OBJECT-IDENTITY
The group standby/cascade state for this unit has been overridden. The unit has been forced off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6692current
lgpCondId6693BranchResidualOverCurrent
OBJECT-IDENTITY
The system has detected a branch residual over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6693current
lgpCondId6694ReceptacleResidualOverCurrent
OBJECT-IDENTITY
The system has detected a receptacle residual over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6694current
lgpCondId6728BuckOn
OBJECT-IDENTITY
The input voltage is currently being bucked (lowered) by the inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.6728current
lgpCondId6729BoostOn
OBJECT-IDENTITY
The input voltage is currently being boosted (raised) by the inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.6729current
lgpCondId6739Compressor1HighPressure
OBJECT-IDENTITY
Compressor 1 High Pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6739current
lgpCondId6740Compressor2HighPressure
OBJECT-IDENTITY
Compressor 2 High Pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6740current
lgpCondId6741Compressor1ThermalOverload
OBJECT-IDENTITY
Compressor 1 Thermal Overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6741current
lgpCondId6742Compressor2ThermalOverload
OBJECT-IDENTITY
Compressor 2 Thermal Overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6742current
lgpCondId6758CompressorFreezeProtection
OBJECT-IDENTITY
Compressor has entered the freeze protection phase.
1.3.6.1.4.1.476.1.42.3.2.7.1.6758current
lgpCondId6773FanTemperatureCompensationLimitReached
OBJECT-IDENTITY
Unit is configured for fan temperature compensation, and the fan control set point cannot be reduced any further due to high remote air temperature sensor readings.
1.3.6.1.4.1.476.1.42.3.2.7.1.6773current
lgpCondId6774ModbusECFanCommunicationLost
OBJECT-IDENTITY
Communication with Modbus EC fan has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.6774current
lgpCondId6785AnalogTemperatureControlIssue
OBJECT-IDENTITY
Analog input used for creating the control temperature (instead of reading a sensor) is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6785current
lgpCondId6786SubgroupFirmwareUpdateRequired
OBJECT-IDENTITY
Mismatch of subgroup firmware. Both the primary and secondary control boards must be running the same firmware version.
1.3.6.1.4.1.476.1.42.3.2.7.1.6786current
lgpCondId6787SubgroupSecondaryControlUnitIssue
OBJECT-IDENTITY
Subgroup secondary control unit is reporting an unspecified issue.
1.3.6.1.4.1.476.1.42.3.2.7.1.6787current
lgpCondId6788EEVCommunicationLost
OBJECT-IDENTITY
Communication with Electronic Expansion Valve unit has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.6788current
lgpCondId6789EEVMotorIssue
OBJECT-IDENTITY
Electronic Expansion Valve stepper motor issue.
1.3.6.1.4.1.476.1.42.3.2.7.1.6789current
lgpCondId6790EEVFeedbackIssue
OBJECT-IDENTITY
Electronic Expansion Valve feedback error.
1.3.6.1.4.1.476.1.42.3.2.7.1.6790current
lgpCondId6791EEVPressureSensorIssue
OBJECT-IDENTITY
Electronic Expansion Valve refrigerant pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6791current
lgpCondId6792EEVCoilTemperatureSensorIssue
OBJECT-IDENTITY
Electronic Expansion Valve coil temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6792current
lgpCondId6793EEVDischargeTemperatureSensorIssue
OBJECT-IDENTITY
Electronic Expansion Valve discharge temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6793current
lgpCondId6794EEVSumpTemperatureSensorIssue
OBJECT-IDENTITY
Electronic Expansion Valve sump temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6794current
lgpCondId6795EEVBatteryTestIssue
OBJECT-IDENTITY
Electronic Expansion Valve battery state cannot be determined.
1.3.6.1.4.1.476.1.42.3.2.7.1.6795current
lgpCondId6796EEVBatteryPersistentIssue
OBJECT-IDENTITY
Electronic Expansion Valve has continuously detected a 'bad' battery condition for an extended period of time.
1.3.6.1.4.1.476.1.42.3.2.7.1.6796current
lgpCondId6798PumpCycleLockOut
OBJECT-IDENTITY
Pump is locked out due to multiple pump-to-compressor transitions at cold ambient air temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.6798current
lgpCondId6799PumpBoardFirmwareUpdateRequired
OBJECT-IDENTITY
Mismatch of pump board firmware. All pump boards must be running the same firmware version.
1.3.6.1.4.1.476.1.42.3.2.7.1.6799current
lgpCondId6800PumpControlBoardIssue
OBJECT-IDENTITY
Pump is shut down due to a pump control board issue. Control board must be rebooted.
1.3.6.1.4.1.476.1.42.3.2.7.1.6800current
lgpCondId6801PumpInvalidDataShutdown
OBJECT-IDENTITY
Pump is shut down due to invalid data.
1.3.6.1.4.1.476.1.42.3.2.7.1.6801current
lgpCondId6802PumpInputPressureSensorIssue
OBJECT-IDENTITY
Pump input refrigerant pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6802current
lgpCondId6803PumpInputTemperatureSensorIssue
OBJECT-IDENTITY
Pump input refrigerant temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6803current
lgpCondId6804PumpOutputPressureSensorIssue
OBJECT-IDENTITY
Pump output refrigerant pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6804current
lgpCondId6805PumpOutputTemperatureSensorIssue
OBJECT-IDENTITY
Pump output refrigerant temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6805current
lgpCondId6806PumpCommunicationLost
OBJECT-IDENTITY
Communication with pump unit has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.6806current
lgpCondId6807PumpRemoteShutdown
OBJECT-IDENTITY
Pump is shut down by a remote signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6807current
lgpCondId6808PumpUSBEthernetPortIssue
OBJECT-IDENTITY
Pump control board USB or Ethernet interface has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6808current
lgpCondId6809PumpStartupFailure
OBJECT-IDENTITY
Multiple attempts to start the pump have failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6809current
lgpCondId6810PumpInverterFailure
OBJECT-IDENTITY
Pump inverter is reporting a failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6810current
lgpCondId6811PumpTVSSIssue
OBJECT-IDENTITY
Pump Transient Voltage Surge Suppressor or Surge Protection Device has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6811current
lgpCondId6812PumpHighSuperheat
OBJECT-IDENTITY
Pump inlet refrigerant superheat temperature is too high, or the pump has been running too long with the condenser fan off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6812current
lgpCondId6813CondenserHighAmbientAirTempDelta
OBJECT-IDENTITY
The difference between condenser measured ambient air temperatures has been too large for an extended period of time.
1.3.6.1.4.1.476.1.42.3.2.7.1.6813current
lgpCondId6814CondenserLeeTempOptionMismatch
OBJECT-IDENTITY
Lee-Temp option configured at a condenser unit does not match Lee -Temp option configured at the control unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6814current
lgpCondId6815CondenserBoardFirmwareUpdateRequired
OBJECT-IDENTITY
Mismatch of condenser board firmware. All condenser boards must be running the same firmware version.
1.3.6.1.4.1.476.1.42.3.2.7.1.6815current
lgpCondId6816CondenserToPumpHighRefrigerantTempDelta
OBJECT-IDENTITY
Temperature delta between the condenser output refrigerant and pump inlet refrigerant is too large.
1.3.6.1.4.1.476.1.42.3.2.7.1.6816current
lgpCondId6817CondenserRefrigerantTypeMismatch
OBJECT-IDENTITY
Refrigerant type configured at condenser unit does not match refrigerant type configured at the control unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6817current
lgpCondId6818ExternalSupplyFluidHighTemperature
OBJECT-IDENTITY
Supply fluid temperature has exceeded a threshold, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6818current
lgpCondId6819ExternalSupplyFluidTempSensorIssue
OBJECT-IDENTITY
Supply fluid temperature sensor is disconnected or the signal is out of range, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6819current
lgpCondId6822AuditLogUpdate
OBJECT-IDENTITY
Audit log has been updated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6822current
lgpCondId6824ExternalSupplyFluidFlowIssue
OBJECT-IDENTITY
Supply fluid flow issue, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6824current