LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB
- Registered at
- 1.3.6.1.4.1.476.1.42.1.11.11.3.6.1.4.1.476.1.42.3.2.7.1
- Last updated
- 2018-10-02 00:00
- Organization
- Liebert Corporation
- Revisions
- 2018-10-02 00:00
- Namespace
- liebert
- Source file
LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB- Digest
sha256:a01e6f3978df8f0ed4ebc36fbd217ebcf4a6214b3a8c7e67da053375266d9889
Description
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2018 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Contact
Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com
Imports
| From | Symbols |
|---|---|
| LIEBERT-GP-CONDITIONS-MIB | lgpFlexConditions |
| LIEBERT-GP-REGISTRATION-MIB | liebertFlexibleConditionsModuleReg |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
LIEBERT-GP-CONDITIONS-MIB LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB LIEBERT-GP-REGISTRATION-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| lgpFlexConditionsWellKnown OBJECT-IDENTITY | 1.3.6.1.4.1.476.1.42.3.2.7.1 | |||
| lgpCondId4122SystemInputPowerProblem OBJECT-IDENTITY The input is not qualified to provide power to the system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4122 | current | ||
| lgpCondId4132BypassOverloadPhaseA OBJECT-IDENTITY An overload exists on output phase A while operating on the bypass. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4132 | current | ||
| lgpCondId4133BypassOverloadPhaseB OBJECT-IDENTITY An overload exists on output phase B while operating on the bypass. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4133 | current | ||
| lgpCondId4134BypassOverloadPhaseC OBJECT-IDENTITY An overload exists on output phase C while operating on the bypass. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4134 | current | ||
| lgpCondId4135BypassNotAvailable OBJECT-IDENTITY A problem associated with the bypass has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4135 | current | ||
| lgpCondId4137BypassAutoRetransferPrimed OBJECT-IDENTITY Automatic retransfer from bypass to inverter is possible. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4137 | current | ||
| lgpCondId4138BypassAutoRetransferFailed OBJECT-IDENTITY After performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4138 | current | ||
| lgpCondId4139BypassExcessAutoRetransfers OBJECT-IDENTITY The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4139 | current | ||
| lgpCondId4140BypassRestartInhibitExternal OBJECT-IDENTITY Restart of the bypass is inhibited by the state of an external signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4140 | current | ||
| lgpCondId4141BypassBreakerClosed OBJECT-IDENTITY The bypass breaker is closed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4141 | current | ||
| lgpCondId4142BypassStaticSwitchOverload OBJECT-IDENTITY Bypass off due to static switch overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4142 | current | ||
| lgpCondId4143BypassStaticSwitchUnavailable OBJECT-IDENTITY The static bypass is unavailable to support the critical load. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4143 | current | ||
| lgpCondId4144BypassExcessivePulseParallel OBJECT-IDENTITY The system has performed too many pulse parallel operations within a specified time interval. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4144 | current | ||
| lgpCondId4145BypassAutoTransferFailed OBJECT-IDENTITY An automatic transfer to static bypass failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4145 | current | ||
| lgpCondId4146SystemInputPhsRotationError OBJECT-IDENTITY The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C). | 1.3.6.1.4.1.476.1.42.3.2.7.1.4146 | current | ||
| lgpCondId4147SystemInputCurrentLimit OBJECT-IDENTITY The RMS input current has reached the input current limit threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4147 | current | ||
| lgpCondId4162BatteryLow OBJECT-IDENTITY The calculated battery time remaining has reached the low battery threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4162 | current | ||
| lgpCondId4163OutputOffEndofDischarge OBJECT-IDENTITY Output turned off due to battery reaching end-of-discharge. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4163 | current | ||
| lgpCondId4164BatteryChargingError OBJECT-IDENTITY The battery is not charging properly. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4164 | current | ||
| lgpCondId4165BatteryChargingReducedExtrnl OBJECT-IDENTITY Using a reduced battery charging algorithm due to an external signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4165 | current | ||
| lgpCondId4166BatteryCapacityLow OBJECT-IDENTITY Battery capacity is low. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4166 | current | ||
| lgpCondId4167OutputOff OBJECT-IDENTITY Output is off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4167 | current | ||
| lgpCondId4168BatteryDischarging OBJECT-IDENTITY The battery is discharging. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4168 | current | ||
| lgpCondId4169BatteryTemperatureImbalance OBJECT-IDENTITY Excessive temperature differences between battery sensors detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4169 | current | ||
| lgpCondId4170BatteryEqualize OBJECT-IDENTITY The rectifier output voltage is increased to equalize the battery voltage level. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4170 | current | ||
| lgpCondId4171BatteryManualTestInProgress OBJECT-IDENTITY Manual battery test is in progress. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4171 | current | ||
| lgpCondId4172BatteryAutoTestInProgress OBJECT-IDENTITY Automatic battery test is in progress. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4172 | current | ||
| lgpCondId4173MainBatteryDisconnectOpen OBJECT-IDENTITY Main battery disconnect is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4173 | current | ||
| lgpCondId4174BatteryTemperatureSensorFault OBJECT-IDENTITY A battery temperature sensor fault has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4174 | current | ||
| lgpCondId4175BypassFrequencyError OBJECT-IDENTITY The bypass frequency is outside the inverter synchronization limits. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4175 | current | ||
| lgpCondId4176BatteryCircuitBreaker1Open OBJECT-IDENTITY Battery circuit breaker 1 is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4176 | current | ||
| lgpCondId4177BatteryBreaker1OpenFailure OBJECT-IDENTITY Battery circuit breaker 1 failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4177 | current | ||
| lgpCondId4178BatteryBreaker1CloseFailure OBJECT-IDENTITY Battery circuit breaker 1 failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4178 | current | ||
| lgpCondId4179BatteryCircuitBreaker2Open OBJECT-IDENTITY Battery circuit breaker 2 is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4179 | current | ||
| lgpCondId4180BatteryBreaker2OpenFailure OBJECT-IDENTITY Battery circuit breaker 2 failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4180 | current | ||
| lgpCondId4181BatteryBreaker2CloseFailure OBJECT-IDENTITY Battery circuit breaker 2 failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4181 | current | ||
| lgpCondId4182BatteryCircuitBreaker3Open OBJECT-IDENTITY Battery circuit breaker 3 is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4182 | current | ||
| lgpCondId4183BatteryBreaker3OpenFailure OBJECT-IDENTITY Battery circuit breaker 3 failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4183 | current | ||
| lgpCondId4184BatteryBreaker3CloseFailure OBJECT-IDENTITY Battery circuit breaker 3 failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4184 | current | ||
| lgpCondId4185BatteryCircuitBreaker4Open OBJECT-IDENTITY Battery circuit breaker 4 is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4185 | current | ||
| lgpCondId4186BatteryBreaker4OpenFailure OBJECT-IDENTITY Battery circuit breaker 4 failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4186 | current | ||
| lgpCondId4187BatteryBreaker4CloseFailure OBJECT-IDENTITY Battery circuit breaker 4 failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4187 | current | ||
| lgpCondId4188BatteryCircuitBreaker5Open OBJECT-IDENTITY Battery circuit breaker 5 is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4188 | current | ||
| lgpCondId4189BatteryBreaker5OpenFailure OBJECT-IDENTITY Battery circuit breaker 5 failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4189 | current | ||
| lgpCondId4190BatteryBreaker5CloseFailure OBJECT-IDENTITY Battery circuit breaker 5 failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4190 | current | ||
| lgpCondId4191BatteryCircuitBreaker6Open OBJECT-IDENTITY Battery circuit breaker 6 is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4191 | current | ||
| lgpCondId4192BatteryBreaker6OpenFailure OBJECT-IDENTITY Battery circuit breaker 6 failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4192 | current | ||
| lgpCondId4193BatteryBreaker6CloseFailure OBJECT-IDENTITY Battery circuit breaker 6 failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4193 | current | ||
| lgpCondId4194BatteryCircuitBreaker7Open OBJECT-IDENTITY Battery circuit breaker 7 is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4194 | current | ||
| lgpCondId4195BatteryBreaker7OpenFailure OBJECT-IDENTITY Battery circuit breaker 7 failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4195 | current | ||
| lgpCondId4196BatteryBreaker7CloseFailure OBJECT-IDENTITY Battery circuit breaker 7 failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4196 | current | ||
| lgpCondId4197BatteryCircuitBreaker8Open OBJECT-IDENTITY Battery circuit breaker 8 is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4197 | current | ||
| lgpCondId4198BatteryBreaker8OpenFailure OBJECT-IDENTITY Battery circuit breaker 8 failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4198 | current | ||
| lgpCondId4199BatteryBreaker8CloseFailure OBJECT-IDENTITY Battery circuit breaker 8 failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4199 | current | ||
| lgpCondId4200BatteryChargingInhibited OBJECT-IDENTITY Battery charging is inhibited due to an external inhibit signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4200 | current | ||
| lgpCondId4213SystemShutdownEPO OBJECT-IDENTITY System shutdown due to Emergency Power Off (EPO). | 1.3.6.1.4.1.476.1.42.3.2.7.1.4213 | current | ||
| lgpCondId4214SystemShutdownREPO OBJECT-IDENTITY System shutdown due to Remote Emergency Power Off (REPO). | 1.3.6.1.4.1.476.1.42.3.2.7.1.4214 | current | ||
| lgpCondId4215SystemOutputOff OBJECT-IDENTITY The system output is off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4215 | current | ||
| lgpCondId4216BypassBackfeedDetected OBJECT-IDENTITY The system detected a voltage on the bypass when none was expected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4216 | current | ||
| lgpCondId4217BypassManualXfrInhibited OBJECT-IDENTITY Manual transfer from inverter to bypass is inhibited - bypass not qualified. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4217 | current | ||
| lgpCondId4218BypassManualRexfrInhibited OBJECT-IDENTITY Manual transfer from bypass to inverter is inhibited - inverter output not qualified. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4218 | current | ||
| lgpCondId4219BatteryOverTemperature OBJECT-IDENTITY A battery temperature sensor is reporting a value above a threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4219 | current | ||
| lgpCondId4220BatteryExternalMonitor1 OBJECT-IDENTITY External battery monitor 1 - battery maintenance required. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4220 | current | ||
| lgpCondId4221BatteryExternalMonitor2 OBJECT-IDENTITY External battery monitor 2 - battery maintenance required. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4221 | current | ||
| lgpCondId4222BatteryGroundFault OBJECT-IDENTITY Battery system ground fault amperage exceeds the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4222 | current | ||
| lgpCondId4229EmergencyPowerOffLatched OBJECT-IDENTITY System output is off - 'Emergency Power Off (EPO) - latched' requires manual reset. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4229 | current | ||
| lgpCondId4230SystemOutputLowPowerFactor OBJECT-IDENTITY The system output power factor is low, resulting in reduced output capacity. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4230 | current | ||
| lgpCondId4231OutputCurrentExceedsThreshold OBJECT-IDENTITY Output current for one or more phases exceeds a threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4231 | current | ||
| lgpCondId4233InverterFailure OBJECT-IDENTITY Inverter failure - inverter output is off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4233 | current | ||
| lgpCondId4234InverterOverloadPhaseA OBJECT-IDENTITY Inverter is operating with an overload on phase A. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4234 | current | ||
| lgpCondId4235InverterOverloadPhaseB OBJECT-IDENTITY Inverter is operating with an overload on phase B. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4235 | current | ||
| lgpCondId4236InverterOverloadPhaseC OBJECT-IDENTITY Inverter is operating with an overload on phase C. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4236 | current | ||
| lgpCondId4237InverterInhibitExternal OBJECT-IDENTITY Restart of the inverter is inhibited by an external signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4237 | current | ||
| lgpCondId4238InverterOutBreakerOpenFail OBJECT-IDENTITY Inverter output breaker failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4238 | current | ||
| lgpCondId4239InverterOutBreakerCloseFail OBJECT-IDENTITY Inverter output breaker failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4239 | current | ||
| lgpCondId4270InputContact01 OBJECT-IDENTITY The external input contact 1. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4270 | current | ||
| lgpCondId4271InputContact02 OBJECT-IDENTITY The external input contact 2. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4271 | current | ||
| lgpCondId4272InputContact03 OBJECT-IDENTITY The external input contact 3. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4272 | current | ||
| lgpCondId4273InputContact04 OBJECT-IDENTITY The external input contact 4. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4273 | current | ||
| lgpCondId4274InputContact05 OBJECT-IDENTITY The external input contact 5. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4274 | current | ||
| lgpCondId4275InputContact06 OBJECT-IDENTITY The external input contact 6. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4275 | current | ||
| lgpCondId4276InputContact07 OBJECT-IDENTITY The external input contact 7. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4276 | current | ||
| lgpCondId4277InputContact08 OBJECT-IDENTITY The external input contact 8. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4277 | current | ||
| lgpCondId4278InputContact09 OBJECT-IDENTITY The external input contact 9. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4278 | current | ||
| lgpCondId4279InputContact10 OBJECT-IDENTITY The external input contact 10. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4279 | current | ||
| lgpCondId4280InputContact11 OBJECT-IDENTITY The external input contact 11. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4280 | current | ||
| lgpCondId4281InputContact12 OBJECT-IDENTITY The external input contact 12. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4281 | current | ||
| lgpCondId4282InputContact13 OBJECT-IDENTITY The external input contact 13. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4282 | current | ||
| lgpCondId4283InputContact14 OBJECT-IDENTITY The external input contact 14. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4283 | current | ||
| lgpCondId4284InputContact15 OBJECT-IDENTITY The external input contact 15. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4284 | current | ||
| lgpCondId4285InputContact16 OBJECT-IDENTITY The external input contact 16. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4285 | current | ||
| lgpCondId4286OutputAmpOverUserLimitPhsA OBJECT-IDENTITY The phase A output has exceeded the user amperage threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4286 | current | ||
| lgpCondId4287OutputAmpOverUserLimitPhsB OBJECT-IDENTITY The phase B output has exceeded the user amperage threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4287 | current | ||
| lgpCondId4288OutputAmpOverUserLimitPhsC OBJECT-IDENTITY The phase C output has exceeded the user amperage threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4288 | current | ||
| lgpCondId4289InverterTransferInhibitExt OBJECT-IDENTITY Transfer of critical bus source to inverter is inhibited by an external signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4289 | current | ||
| lgpCondId4290InverterShutdownOverload OBJECT-IDENTITY The inverter has shutdown due to a sustained overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4290 | current | ||
| lgpCondId4294InletAirOverTemperature OBJECT-IDENTITY The inlet air exceeds the maximum temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4294 | current | ||
| lgpCondId4295RectifierFailure OBJECT-IDENTITY Rectifier failure - rectifier is off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4295 | current | ||
| lgpCondId4296RectifierOperationInhibitExt OBJECT-IDENTITY The operation of the rectifier is inhibited by an external signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4296 | current | ||
| lgpCondId4297UPSOutputonInverter OBJECT-IDENTITY The output power is supplied by the inverter. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4297 | current | ||
| lgpCondId4298UPSOutputonBypass OBJECT-IDENTITY The output power is supplied by the bypass. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4298 | current | ||
| lgpCondId4299OutputLoadonMaintBypass OBJECT-IDENTITY The output power is supplied by the maintenance bypass. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4299 | current | ||
| lgpCondId4300InternalCommunicationsFailure OBJECT-IDENTITY The control has detected a communication failure of a component on the internal communication bus. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4300 | current | ||
| lgpCondId4308DCBusGroundFaultPositive OBJECT-IDENTITY A ground fault has been detected on the positive DC Bus link. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4308 | current | ||
| lgpCondId4309DCBusGroundFaultNegative OBJECT-IDENTITY A ground fault has been detected on the negative DC Bus link. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4309 | current | ||
| lgpCondId4310EquipmentOverTemperature OBJECT-IDENTITY Equipment over temperature summary event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4310 | current | ||
| lgpCondId4311SystemFanFailure OBJECT-IDENTITY System fan failure - one or more fans have failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4311 | current | ||
| lgpCondId4313PasswordChanged OBJECT-IDENTITY Password changed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4313 | current | ||
| lgpCondId4314PowerSupplyFailure OBJECT-IDENTITY Power supply failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4314 | current | ||
| lgpCondId4315OnGenerator OBJECT-IDENTITY A generator is supplying the power to the system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4315 | current | ||
| lgpCondId4316AutoRestartInProgress OBJECT-IDENTITY Auto restart is in progress. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4316 | current | ||
| lgpCondId4317AutoRestartInhibitedExt OBJECT-IDENTITY Auto restart inhibited due to an external signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4317 | current | ||
| lgpCondId4320InitiatedTransfertoBypass OBJECT-IDENTITY User initiated manual transfer to bypass. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4320 | current | ||
| lgpCondId4321InitiatedTransfertoInverter OBJECT-IDENTITY User initiated manual transfer to inverter. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4321 | current | ||
| lgpCondId4322BatteryTestPassed OBJECT-IDENTITY Battery test passed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4322 | current | ||
| lgpCondId4323BatteryTestFailed OBJECT-IDENTITY Battery test failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4323 | current | ||
| lgpCondId4324BatteryTestManuallyStopped OBJECT-IDENTITY The battery test was manually stopped prior to completion. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4324 | current | ||
| lgpCondId4325BackfeedBreakerOpen OBJECT-IDENTITY The backfeed breaker is in the open position. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4325 | current | ||
| lgpCondId4341VelocityAuthenticationFailure OBJECT-IDENTITY Notification of a message rejected by Velocity due to an authentication failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4341 | current | ||
| lgpCondId4360ReceptacleOverCurrent OBJECT-IDENTITY The system has detected a receptacle over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4360 | current | ||
| lgpCondId4361ReceptacleUnderCurrent OBJECT-IDENTITY The system has detected a receptacle under current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4361 | current | ||
| lgpCondId4382SystemInputCurrentImbalance OBJECT-IDENTITY System Input Currents are Imbalanced. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4382 | current | ||
| lgpCondId4383BypassStaticSwitchOffExtrnl OBJECT-IDENTITY Bypass static switch is off due to the state of an external signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4383 | current | ||
| lgpCondId4384BatteryEoDDisconnect OBJECT-IDENTITY Battery disconnect due to end-of-discharge. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4384 | current | ||
| lgpCondId4389SystemOutputFault OBJECT-IDENTITY A fault has been detected in the system output. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4389 | current | ||
| lgpCondId4390InverterOffExternal OBJECT-IDENTITY Inverter is off (operation is inhibited) due to external signal state. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4390 | current | ||
| lgpCondId4391InverterStaticSwitchSCRShort OBJECT-IDENTITY The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR). | 1.3.6.1.4.1.476.1.42.3.2.7.1.4391 | current | ||
| lgpCondId4392TemperatureSensorError OBJECT-IDENTITY One or more temperature sensors cannot provide a valid temperature reading (i.e. sensor failure, wiring failure, sense circuit failure, etc). | 1.3.6.1.4.1.476.1.42.3.2.7.1.4392 | current | ||
| lgpCondId4406BranchOverCurrent OBJECT-IDENTITY The system has detected a module over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4406 | current | ||
| lgpCondId4407BranchUnderCurrent OBJECT-IDENTITY The system has detected a module under current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4407 | current | ||
| lgpCondId4416BranchOverCurrent OBJECT-IDENTITY The system has detected a module over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4416 | current | ||
| lgpCondId4417BranchUnderCurrent OBJECT-IDENTITY The system has detected a module under current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4417 | current | ||
| lgpCondId4421BranchFailure OBJECT-IDENTITY One or more conditions indicate a Branch Receptacle Module failure , service is required. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4421 | current | ||
| lgpCondId4436PDUOverCurrent OBJECT-IDENTITY The system has detected a module over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4436 | current | ||
| lgpCondId4437PDUUnderCurrent OBJECT-IDENTITY The system has detected a module under current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4437 | current | ||
| lgpCondId4438SystemInternalTemperatureRise OBJECT-IDENTITY Excessive temperature rise internal to the system (i.e. difference between the output versus input temperature is too large). | 1.3.6.1.4.1.476.1.42.3.2.7.1.4438 | current | ||
| lgpCondId4439AutomaticRestartFailed OBJECT-IDENTITY Automatic restart failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4439 | current | ||
| lgpCondId4440FuseFailure OBJECT-IDENTITY A summary event indicating one or more fuse failures. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4440 | current | ||
| lgpCondId4441SystemControllerError OBJECT-IDENTITY System controller internal error. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4441 | current | ||
| lgpCondId4442SystemBreakersOpenFailure OBJECT-IDENTITY One or more breakers in the system failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4442 | current | ||
| lgpCondId4448PDUOverCurrent OBJECT-IDENTITY The system has detected a module over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4448 | current | ||
| lgpCondId4449PDUUnderCurrent OBJECT-IDENTITY The system has detected a module under current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4449 | current | ||
| lgpCondId4468PDUOverCurrentL1 OBJECT-IDENTITY The system has detected a module over current condition on line 1. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4468 | current | ||
| lgpCondId4469PDUOverCurrentL2 OBJECT-IDENTITY The system has detected a module over current condition on line 2. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4469 | current | ||
| lgpCondId4470PDUOverCurrentL3 OBJECT-IDENTITY The system has detected a module over current condition on line 3. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4470 | current | ||
| lgpCondId4471PDUUnderCurrentL1 OBJECT-IDENTITY The system has detected a module under current condition on line 1. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4471 | current | ||
| lgpCondId4472PDUUnderCurrentL2 OBJECT-IDENTITY The system has detected a module under current condition on line 2. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4472 | current | ||
| lgpCondId4473PDUUnderCurrentL3 OBJECT-IDENTITY The system has detected a module under current condition on line 3. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4473 | current | ||
| lgpCondId4492ReceptaclePowerStateOn OBJECT-IDENTITY The receptacle power state changed to the ON state. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4492 | current | ||
| lgpCondId4493ReceptaclePowerStateOff OBJECT-IDENTITY The receptacle power state changed to the OFF state. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4493 | current | ||
| lgpCondId4494BranchBreakerOpen OBJECT-IDENTITY The Branch Receptacle Module's input breaker is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4494 | current | ||
| lgpCondId4495DeviceConfigurationChange OBJECT-IDENTITY Device Configuration Change. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4495 | current | ||
| lgpCondId4496BasicDisplayModuleRemoved OBJECT-IDENTITY Basic Display Module Removed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4496 | current | ||
| lgpCondId4497BasicDisplayModuleDiscovered OBJECT-IDENTITY Basic Display Module Discovered. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4497 | current | ||
| lgpCondId4500PDUOverCurrent OBJECT-IDENTITY The system has detected a power module over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4500 | current | ||
| lgpCondId4501PDUUnderCurrent OBJECT-IDENTITY The system has detected a power module under current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4501 | current | ||
| lgpCondId4502PDUFailure OBJECT-IDENTITY One or more conditions indicate a power module failure, service is required. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4502 | current | ||
| lgpCondId4503PDUCommunicationFail OBJECT-IDENTITY Internal communications failure with the Power Module. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4503 | current | ||
| lgpCondId4504BranchRemoved OBJECT-IDENTITY Branch Receptacle Module Removed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4504 | current | ||
| lgpCondId4505BranchDiscovered OBJECT-IDENTITY Branch Receptacle Module Discovered. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4505 | current | ||
| lgpCondId4506BranchOverCurrent OBJECT-IDENTITY The system has detected a Branch Receptacle Module over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4506 | current | ||
| lgpCondId4507BranchCurrent OBJECT-IDENTITY The system has detected a Branch Receptacle Module under current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4507 | current | ||
| lgpCondId4508ReceptacleLoadRemoved OBJECT-IDENTITY The receptacle's load stopped drawing power. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4508 | current | ||
| lgpCondId4509ReceptacleLoadAdded OBJECT-IDENTITY The receptacle's load started to draw power. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4509 | current | ||
| lgpCondId4523ModuleRemoved OBJECT-IDENTITY Module Removed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4523 | current | ||
| lgpCondId4524ModuleAdded OBJECT-IDENTITY Module Added. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4524 | current | ||
| lgpCondId4550FirmwareUpdateRequired OBJECT-IDENTITY Module compatibility error requires a system firmware update to resolve. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4550 | current | ||
| lgpCondId4551GenericTestEvent OBJECT-IDENTITY A generic test event designed to evaluate system handling of events. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4551 | current | ||
| lgpCondId4580OverTemperature OBJECT-IDENTITY An over temperature condition was detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4580 | current | ||
| lgpCondId4581UnderTemperature OBJECT-IDENTITY An under temperature condition was detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4581 | current | ||
| lgpCondId4588OverRelativeHumidity OBJECT-IDENTITY An over relative humidity condition was detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4588 | current | ||
| lgpCondId4589UnderRelativeHumidity OBJECT-IDENTITY An under relative humidity condition was detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4589 | current | ||
| lgpCondId4601ExternalAirSensorAOverTemperature OBJECT-IDENTITY [Ext Air Sensor A Temperature] has exceeded [External Air Over Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4601 | current | ||
| lgpCondId4604ExternalAirSensorBOverTemperature OBJECT-IDENTITY [Ext Air Sensor B Temperature] has exceeded [External Air Over Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4604 | current | ||
| lgpCondId4608ExtAirSensorAUnderTemperature OBJECT-IDENTITY [Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4608 | current | ||
| lgpCondId4611ExtAirSensorBUnderTemperature OBJECT-IDENTITY [Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4611 | current | ||
| lgpCondId4615ExtDewPointOverTemperature OBJECT-IDENTITY At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4615 | current | ||
| lgpCondId4618ExternalAirSensorAIssue OBJECT-IDENTITY The external air sensor A is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4618 | current | ||
| lgpCondId4621ExternalAirSensorBIssue OBJECT-IDENTITY The external air sensor B is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4621 | current | ||
| lgpCondId4626SupplyChilledWaterOverTemp OBJECT-IDENTITY [Supply Fluid Temperature] has exceeded [High Supply Fluid Temperature Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4626 | current | ||
| lgpCondId4629SupplyChilledWaterTempSensorIssue OBJECT-IDENTITY The supply chilled water temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4629 | current | ||
| lgpCondId4634SupplyRefrigerantOverTemp OBJECT-IDENTITY Event that is activated when [Supply Refrigerant Temperature] exceeds [Supply Refrig Over Temp Threshold]. The event is deactivated when the temperature drops below the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4634 | current | ||
| lgpCondId4637SupplyRefrigerantUnderTemp OBJECT-IDENTITY [Supply Refrigerant Temperature] has dropped below a specified threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4637 | current | ||
| lgpCondId4640SupplyRefrigerantTempSensorIssue OBJECT-IDENTITY The supply refrigeramt temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4640 | current | ||
| lgpCondId4645SupplyFluidOverTemp OBJECT-IDENTITY [Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4645 | current | ||
| lgpCondId4648SupplyFluidUnderTemp OBJECT-IDENTITY [Supply Fluid Temperature] has dropped below a specified threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4648 | current | ||
| lgpCondId4651SupplyFluidTempSensorIssue OBJECT-IDENTITY The supply fluid temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4651 | current | ||
| lgpCondId4656Pump1LossofFlow OBJECT-IDENTITY Loss of flow is detected in pump 1. The loss of flow condition occurs when no differential pressure is detected across the pump. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4656 | current | ||
| lgpCondId4659Pump2LossofFlow OBJECT-IDENTITY Loss of flow is detected in pump 2. The loss of flow condition occurs when no differential pressure is detected across the pump. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4659 | current | ||
| lgpCondId4662PumpShortCycle OBJECT-IDENTITY Pumps have short cycled. A short cycle is defined as turning on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4662 | current | ||
| lgpCondId4669Compressor1AHighHeadPressure OBJECT-IDENTITY Compressor 1A high head pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4669 | current | ||
| lgpCondId4672Compressor1BHighHeadPressure OBJECT-IDENTITY Compressor 1B high head pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4672 | current | ||
| lgpCondId4675Compressor2AHighHeadPressure OBJECT-IDENTITY Compressor 2A high head pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4675 | current | ||
| lgpCondId4678Compressor2BHighHeadPressure OBJECT-IDENTITY Compressor 2B high head pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4678 | current | ||
| lgpCondId4681Compressor1AShortCycle OBJECT-IDENTITY Compressor 1A short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4681 | current | ||
| lgpCondId4684Compressor1BShortCycle OBJECT-IDENTITY Compressor 1B short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4684 | current | ||
| lgpCondId4687Compressor2AShortCycle OBJECT-IDENTITY Compressor 2A short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4687 | current | ||
| lgpCondId4690Compressor2BShortCycle OBJECT-IDENTITY Compressor 2B short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4690 | current | ||
| lgpCondId4693Tandem1LowSuctionPressure OBJECT-IDENTITY 'Tandem compressors' 1 low suction pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4693 | current | ||
| lgpCondId4696Tandem2LowSuctionPressure OBJECT-IDENTITY 'Tandem compressors' 2 low suction pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4696 | current | ||
| lgpCondId4703ChilledWaterControlValvePosition OBJECT-IDENTITY Chilled water valve out of position. Chilled water control valve position does not match expected value. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4703 | current | ||
| lgpCondId4711SystemCondensationDetected OBJECT-IDENTITY System condensation detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4711 | current | ||
| lgpCondId4714ShutdownLossOfPower OBJECT-IDENTITY System lost power. This event becomes active when the unit is powered on following an unexpected loss of power. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4714 | current | ||
| lgpCondId4720SmokeDetected OBJECT-IDENTITY Smoke detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4720 | current | ||
| lgpCondId4723WaterUnderFloor OBJECT-IDENTITY Water under the floor is detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4723 | current | ||
| lgpCondId4726ServiceRequired OBJECT-IDENTITY Unit requires servicing. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4726 | current | ||
| lgpCondId4729FanIssue OBJECT-IDENTITY One or more fans are not operating within their operational parameters. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4729 | current | ||
| lgpCondId4732ReceptacleLoadDropped OBJECT-IDENTITY The receptacle's load is not drawing power. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4732 | current | ||
| lgpCondId4740BatteryAutomaticTestInhibited OBJECT-IDENTITY Automatic (scheduled) battery tests are inhibited. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4740 | current | ||
| lgpCondId4741BatterySelfTest OBJECT-IDENTITY Battery self test is in progress. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4741 | current | ||
| lgpCondId4742BatteryLowShutdown OBJECT-IDENTITY Battery disconnect due to end-of-discharge. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4742 | current | ||
| lgpCondId4747EquipmentTemperatureSensorFail OBJECT-IDENTITY One or more temperature sensors report a temperature outside of the range of expected operation. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4747 | current | ||
| lgpCondId4749SystemFanFailureRedundant OBJECT-IDENTITY Redundant system fan failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4749 | current | ||
| lgpCondId4750MultipleFanFailure OBJECT-IDENTITY Multiple fan failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4750 | current | ||
| lgpCondId4753MainControllerFault OBJECT-IDENTITY A Main Controller fault has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4753 | current | ||
| lgpCondId4754SystemBreakersCloseFailure OBJECT-IDENTITY One or more breakers in the system failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4754 | current | ||
| lgpCondId4755InputFilterCycleLock OBJECT-IDENTITY The input filter disconnect is open due to exceeding the maximum number of cycles. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4755 | current | ||
| lgpCondId4756ServiceCodeActive OBJECT-IDENTITY Service code is running. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4756 | current | ||
| lgpCondId4757LBSActive OBJECT-IDENTITY The Load Bus Sync option is active. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4757 | current | ||
| lgpCondId4758LBSInhibited OBJECT-IDENTITY The system has detected that conditions to perform Load Bus Sync are not satisfied. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4758 | current | ||
| lgpCondId4759LeadingPowerFactor OBJECT-IDENTITY The leading output Power Factor has fallen below a specified value. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4759 | current | ||
| lgpCondId4760ControlsResetRequired OBJECT-IDENTITY A controls reset is required due to one or more critical settings changing. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4760 | current | ||
| lgpCondId4823ParallelCommWarning OBJECT-IDENTITY Parallel communication bus warning. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4823 | current | ||
| lgpCondId4824SystemCommFail OBJECT-IDENTITY Failure of a device on the multi-module system communication bus. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4824 | current | ||
| lgpCondId4825LossofRedundancy OBJECT-IDENTITY The multi-module collection doesn't have enough modules to satisfy the redundancy configuration. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4825 | current | ||
| lgpCondId4826BPSSStartupInhibit OBJECT-IDENTITY The Bypass Static Switch startup is inhibited. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4826 | current | ||
| lgpCondId4827MMSTransferInhibit OBJECT-IDENTITY The critical load can not be manually transferred from inverter to bypass. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4827 | current | ||
| lgpCondId4828MMSRetransferInhibit OBJECT-IDENTITY The critical load can not be manually retransferred from bypass to inverter. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4828 | current | ||
| lgpCondId4830MMSLossofSyncPulse OBJECT-IDENTITY Multi-module system loss of sync pulse. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4830 | current | ||
| lgpCondId4831MMSOverload OBJECT-IDENTITY Multi-module system overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4831 | current | ||
| lgpCondId4834MMSOnBattery OBJECT-IDENTITY The multi-module system is on battery. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4834 | current | ||
| lgpCondId4835MMSLowBatteryWarning OBJECT-IDENTITY Multi-module system low battery warning. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4835 | current | ||
| lgpCondId4906LowAmbientTemperature OBJECT-IDENTITY The system has detected a low ambient temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4906 | current | ||
| lgpCondId4907HighAmbientTemperature OBJECT-IDENTITY The system has detected a high ambient temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4907 | current | ||
| lgpCondId4908LowOverallVoltage OBJECT-IDENTITY The system has detected a low battery string overall voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4908 | current | ||
| lgpCondId4909HighOverallVoltage OBJECT-IDENTITY The system has detected a high battery string overall voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4909 | current | ||
| lgpCondId4910HighBatteryStringCurrent OBJECT-IDENTITY The system has detected a high battery string current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4910 | current | ||
| lgpCondId4911LowBatteryStringFloatCurrent OBJECT-IDENTITY The system has detected a low battery string float current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4911 | current | ||
| lgpCondId4912HighBatteryStringFloatCurrent OBJECT-IDENTITY The system has detected a high battery string float current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4912 | current | ||
| lgpCondId4913HighBatteryStringRippleCurrent OBJECT-IDENTITY The system has detected a high battery string ripple current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4913 | current | ||
| lgpCondId4914BatteryStringDischargeDetected OBJECT-IDENTITY The system has detected a battery string discharge condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4914 | current | ||
| lgpCondId4915MaximumDischargeTimeExceeded OBJECT-IDENTITY The system has detected an excessive discharge time condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4915 | current | ||
| lgpCondId4916DischargeLowOverallVoltage OBJECT-IDENTITY The system has detected a low battery string overall voltage condition during a discharge. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4916 | current | ||
| lgpCondId4917DischargeLowCellVoltage OBJECT-IDENTITY The system has detected a low cell voltage condition during a discharge. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4917 | current | ||
| lgpCondId4918DischargeHighBatteryStringCurrent OBJECT-IDENTITY The system has detected a high battery string current condition during a discharge. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4918 | current | ||
| lgpCondId4919ExcessiveCelltoCellTemperatureDeviation OBJECT-IDENTITY The system has detected an excessive cell to cell temperature deviation condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4919 | current | ||
| lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation OBJECT-IDENTITY The system has detected an excessive cell to ambient temperature deviation condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4920 | current | ||
| lgpCondId4964LowCellVoltage OBJECT-IDENTITY The system has detected a low cell voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4964 | current | ||
| lgpCondId4965HighCellVoltage OBJECT-IDENTITY The system has detected a high cell voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4965 | current | ||
| lgpCondId4966LowCellTemperature OBJECT-IDENTITY The system has detected a low cell temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4966 | current | ||
| lgpCondId4967HighCellTemperature OBJECT-IDENTITY The system has detected a high cell temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4967 | current | ||
| lgpCondId4968LowInternalResistance OBJECT-IDENTITY The system has detected a low internal resistance condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4968 | current | ||
| lgpCondId4969HighInternalResistance OBJECT-IDENTITY The system has detected a high internal resistance condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4969 | current | ||
| lgpCondId4970HighIntercellResistance OBJECT-IDENTITY The system has detected a high intercell resistance condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4970 | current | ||
| lgpCondId4978IntertierResistanceHigh OBJECT-IDENTITY The system has detected a high intertier resistance condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4978 | current | ||
| lgpCondId4980SupplyChilledWaterLossofFlow OBJECT-IDENTITY Supply chilled water or glycol flow is too low. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4980 | current | ||
| lgpCondId4983SupplyRefrigOverTempBand1 OBJECT-IDENTITY [Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 1]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4983 | current | ||
| lgpCondId4986SupplyRefrigUnderTempBand1 OBJECT-IDENTITY [Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 1]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4986 | current | ||
| lgpCondId4990SupplyRefrigOverTempBand2 OBJECT-IDENTITY [Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 2]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4990 | current | ||
| lgpCondId4993SupplyRefrigUnderTempBand2 OBJECT-IDENTITY [Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 2]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4993 | current | ||
| lgpCondId4996Inverter1ShortCycle OBJECT-IDENTITY Inverter for pump 1 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4996 | current | ||
| lgpCondId4999Inverter2ShortCycle OBJECT-IDENTITY Inverter for pump 2 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.7.1.4999 | current | ||
| lgpCondId5015SupplyAirOverTemperature OBJECT-IDENTITY [Supply Air Temperature] has exceeded [High Supply Air Temperature Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5015 | current | ||
| lgpCondId5019SupplyAirUnderTemperature OBJECT-IDENTITY [Supply Air Temperature] has dropped below [Low Supply Air Temperature Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5019 | current | ||
| lgpCondId5023ReturnAirOverTemperature OBJECT-IDENTITY [Return Air Temperature] has exceeded [High Return Air Temperature Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5023 | current | ||
| lgpCondId5026SupplyAirSensorIssue OBJECT-IDENTITY The air sensor at the outlet of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5026 | current | ||
| lgpCondId5034HighReturnHumidity OBJECT-IDENTITY [Return Humidity] has exceeded [High Return Humidity Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5034 | current | ||
| lgpCondId5036LowReturnHumidity OBJECT-IDENTITY [Return Humidity] has dropped below [Low Return Humidity Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5036 | current | ||
| lgpCondId5037HumidifierHoursExceeded OBJECT-IDENTITY Operating hours for the humidifier have exceeded the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5037 | current | ||
| lgpCondId5038DehumidifierHoursExceeded OBJECT-IDENTITY Operating hours for the dehumidifier have exceeded the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5038 | current | ||
| lgpCondId5039HumidifierUnderCurrent OBJECT-IDENTITY The electrical current to the humidifier has dropped below its lower threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5039 | current | ||
| lgpCondId5040HumidifierOverCurrent OBJECT-IDENTITY The electrical current to the humidifier has exceeded its upper threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5040 | current | ||
| lgpCondId5041HumidifierLowWater OBJECT-IDENTITY The water level in the humidifier has dropped below its threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5041 | current | ||
| lgpCondId5042HumidifierCylinderWorn OBJECT-IDENTITY Humidifier cylinder is not operating properly and needs to be replaced. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5042 | current | ||
| lgpCondId5043HumidifierIssue OBJECT-IDENTITY Humidifier issue detected, causing it to be locked out. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5043 | current | ||
| lgpCondId5044ExtHumidifierLockout OBJECT-IDENTITY The humidifier is shut down and disabled by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5044 | current | ||
| lgpCondId5045HumidifierControlBoardNotDetected OBJECT-IDENTITY Humidifier control board is required to be connected, but no signal is detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5045 | current | ||
| lgpCondId5046ReturnHumidityOutOfProportionalBand OBJECT-IDENTITY [Return Humidity] has exceeded the upper limit of [Dehumidification Proportional Band], or has dropped below the lower limit of [Humidification Proportional Band] ], for an extended period of time. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5046 | current | ||
| lgpCondId5053LossofAirFlow OBJECT-IDENTITY No air flow through the unit due to failure of all fans. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5053 | current | ||
| lgpCondId5054FanHoursExceeded OBJECT-IDENTITY Operating hours for the unit blower fan have exceeded the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5054 | current | ||
| lgpCondId5055TopFanIssue OBJECT-IDENTITY The top fan is not operating within its normal parameters. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5055 | current | ||
| lgpCondId5056BottomFanIssue OBJECT-IDENTITY The bottom fan is not operating within its normal parameters. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5056 | current | ||
| lgpCondId5060RemoteSensorIssue OBJECT-IDENTITY Remote sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5060 | current | ||
| lgpCondId5062Compressor1LowSuctionPressure OBJECT-IDENTITY Compressor 1 low suction pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5062 | current | ||
| lgpCondId5063Compressor1HoursExceeded OBJECT-IDENTITY Operating hours for compressor 1 have exceeded the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5063 | current | ||
| lgpCondId5064DigScrollComp1TempSensorIssue OBJECT-IDENTITY Digital scroll compressor 1 temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5064 | current | ||
| lgpCondId5065DigScrollComp1OverTemp OBJECT-IDENTITY Digital scroll compressor 1 shut off because its head temperature has exceeded the upper threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5065 | current | ||
| lgpCondId5066Compressor1LowPressureTransducerIssue OBJECT-IDENTITY Compressor 1 low pressure transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5066 | current | ||
| lgpCondId5067ExtCompressorLockout OBJECT-IDENTITY The compressor is shut down and disabled by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5067 | current | ||
| lgpCondId5068ReheaterOverTemperature OBJECT-IDENTITY The temperature of the reheater has exceeded its threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5068 | current | ||
| lgpCondId5069ElectricReheater1HoursExceeded OBJECT-IDENTITY Operating hours for electric reheater 1 have exceeded the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5069 | current | ||
| lgpCondId5070ExtReheatLockout OBJECT-IDENTITY The reheater is shut down and disabled by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5070 | current | ||
| lgpCondId5071Condenser1Issue OBJECT-IDENTITY Condenser 1 is not operating within its normal parameters. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5071 | current | ||
| lgpCondId5072CondenserVFDIssue OBJECT-IDENTITY The condenser fan Variable Frequency Drive is offline. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5072 | current | ||
| lgpCondId5073CondenserTVSSIssue OBJECT-IDENTITY The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5073 | current | ||
| lgpCondId5104ExtOverTemperature OBJECT-IDENTITY A temperature has exceeded its threshold, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5104 | current | ||
| lgpCondId5105ExtLossofFlow OBJECT-IDENTITY Loss of flow is detected, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5105 | current | ||
| lgpCondId5106ExtCondenserPumpHighWater OBJECT-IDENTITY High water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5106 | current | ||
| lgpCondId5107ExtStandbyGlycolPumpOn OBJECT-IDENTITY The standby glycol pump is on, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5107 | current | ||
| lgpCondId5108ExternalFireDetected OBJECT-IDENTITY Fire detected, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5108 | current | ||
| lgpCondId5109UnitOn OBJECT-IDENTITY Unit was turned on. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5109 | current | ||
| lgpCondId5110UnitOff OBJECT-IDENTITY Unit was turned off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5110 | current | ||
| lgpCondId5111UnitStandby OBJECT-IDENTITY Unit was placed in standby mode. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5111 | current | ||
| lgpCondId5112UnitPartialShutdown OBJECT-IDENTITY An event has occurred requiring some system components to be shutdown and disabled. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5112 | current | ||
| lgpCondId5113UnitShutdown OBJECT-IDENTITY An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5113 | current | ||
| lgpCondId5114WaterLeakageDetectorSensorIssue OBJECT-IDENTITY The water leakage detector sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5114 | current | ||
| lgpCondId5115BMSCommunicationsTimeout OBJECT-IDENTITY Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5115 | current | ||
| lgpCondId5116MaintenanceDue OBJECT-IDENTITY The calculated maintenance date has been reached. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5116 | current | ||
| lgpCondId5117MaintenanceCompleted OBJECT-IDENTITY Maintenance has been completed on the unit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5117 | current | ||
| lgpCondId5118CloggedAirFilter OBJECT-IDENTITY Air filter is dirty and needs to be (cleaned or) replaced. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5118 | current | ||
| lgpCondId5119RAMBatteryIssue OBJECT-IDENTITY RAM or RAM backup battery is not operating correctly. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5119 | current | ||
| lgpCondId5120MasterUnitCommunicationLost OBJECT-IDENTITY Communication with master unit has been lost. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5120 | current | ||
| lgpCondId5121HighPowerShutdown OBJECT-IDENTITY Supply to high power components has been shutdown. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5121 | current | ||
| lgpCondId5126DigScrollComp2OverTemp OBJECT-IDENTITY Digital scroll compressor 2 shut off because its head temperature has exceeded the upper threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5126 | current | ||
| lgpCondId5144OutputOfUf OBJECT-IDENTITY The output frequency has exceeded a specified range for a specified period of time. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5144 | current | ||
| lgpCondId5145MMSModuleAlarmActive OBJECT-IDENTITY Active alarm or fault of any module in a multi-module system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5145 | current | ||
| lgpCondId5146CompressorPumpDownIssue OBJECT-IDENTITY Unable to pump down suction-side pressure during compressor shutdown. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5146 | current | ||
| lgpCondId5147ReturnAirSensorIssue OBJECT-IDENTITY The air sensor at the inlet of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5147 | current | ||
| lgpCondId5148CompressorHighPressureTransducerIssue OBJECT-IDENTITY Compressor high pressure transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5148 | current | ||
| lgpCondId5149BatteryNotQualified OBJECT-IDENTITY The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5149 | current | ||
| lgpCondId5150BatteryTerminalsReversed OBJECT-IDENTITY The measured battery voltage is a negative value due to reverse battery terminal connections. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5150 | current | ||
| lgpCondId5151BatteryConverterFailure OBJECT-IDENTITY Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5151 | current | ||
| lgpCondId5152InverterSCROpen OBJECT-IDENTITY The system has detected an open across one or more inverter static switch Silicon Controlled Rectifiers. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5152 | current | ||
| lgpCondId5153LoadSharingFault OBJECT-IDENTITY Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5153 | current | ||
| lgpCondId5154DCBusAbnormal OBJECT-IDENTITY The system has detected an abnormal DC Bus Voltage. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5154 | current | ||
| lgpCondId5155MainsInputNeutralLost OBJECT-IDENTITY Loss of neutral in the input source is detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5155 | current | ||
| lgpCondId5156LoadImpactTransfer OBJECT-IDENTITY On bypass as result of load impact. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5156 | current | ||
| lgpCondId5157UserOperationInvalid OBJECT-IDENTITY User attempted an invalid operation. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5157 | current | ||
| lgpCondId5158PowerSubModuleFault OBJECT-IDENTITY One or more failures detected in power module, inverter or rectifier. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5158 | current | ||
| lgpCondId5178OutputOvervoltage OBJECT-IDENTITY One or more of the output phase voltages has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5178 | current | ||
| lgpCondId5179OutputUndervoltage OBJECT-IDENTITY One or more of the output phase voltages has dropped below the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5179 | current | ||
| lgpCondId5180OutputOvercurrent OBJECT-IDENTITY One or more of the phase currents has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5180 | current | ||
| lgpCondId5181NeutralOvercurrent OBJECT-IDENTITY The system's neutral current has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5181 | current | ||
| lgpCondId5182GroundOvercurrent OBJECT-IDENTITY System ground current has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5182 | current | ||
| lgpCondId5183OutputVoltageTHD OBJECT-IDENTITY The Total Harmonic Distortion of the voltage on one or more of the output phases has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5183 | current | ||
| lgpCondId5184OutputFrequencyError OBJECT-IDENTITY The output frequency is outside a specified range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5184 | current | ||
| lgpCondId5185TransformerOvertemperature OBJECT-IDENTITY Indicates a unit transformer overtemperature condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5185 | current | ||
| lgpCondId5212PanelSummaryStatus OBJECT-IDENTITY The status for the panel. Detects and annunciates upon occurrence of any branch or panelboard main breaker active event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5212 | current | ||
| lgpCondId5213PanelOvervoltage OBJECT-IDENTITY One or more of the phase voltages of this panel has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5213 | current | ||
| lgpCondId5214PanelUndervoltage OBJECT-IDENTITY One or more of the phase voltages of this panel is less than the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5214 | current | ||
| lgpCondId5215PanelOvercurrent OBJECT-IDENTITY One or more of the phase currents of this panel has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5215 | current | ||
| lgpCondId5216PanelNeutralOvercurrent OBJECT-IDENTITY The Neutral current of this panel has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5216 | current | ||
| lgpCondId5217PanelGroundOvercurrent OBJECT-IDENTITY The Ground current of this panel has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5217 | current | ||
| lgpCondId5226BranchOvercurrent OBJECT-IDENTITY The current in one or more phases of this branch exceeds the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5226 | current | ||
| lgpCondId5227BranchUndercurrent OBJECT-IDENTITY The current in one or more phases of this branch is less than the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5227 | current | ||
| lgpCondId5245SubfeedPhaseOvercurrent OBJECT-IDENTITY One or more of the phase currents in this subfeed has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5245 | current | ||
| lgpCondId5246SubfeedNeutralOvercurrent OBJECT-IDENTITY The Neutral current in this subfeed has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5246 | current | ||
| lgpCondId5247SubfeedGroundOvercurrent OBJECT-IDENTITY The Ground current of this subfeed has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5247 | current | ||
| lgpCondId5249EventState OBJECT-IDENTITY The present state of this digital event input. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5249 | current | ||
| lgpCondId5263CompressorNotStopping OBJECT-IDENTITY Compressor commanded to stop, but continues to run. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5263 | current | ||
| lgpCondId5269CompressorHoursExceeded OBJECT-IDENTITY [Compressor Hours] has exceeded [Compressor Hours Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5269 | current | ||
| lgpCondId5270CompressorHighHeadPressure OBJECT-IDENTITY Compressor is shut down due to high head pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5270 | current | ||
| lgpCondId5271CompressorLowSuctionPressure OBJECT-IDENTITY Compressor is shut down due to low suction pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5271 | current | ||
| lgpCondId5272CompressorThermalOverload OBJECT-IDENTITY Compressor is shut down due to thermal overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5272 | current | ||
| lgpCondId5273CompressorLowOilPressure OBJECT-IDENTITY Compressor low oil pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5273 | current | ||
| lgpCondId5274CompressorHeadPressureOverThreshold OBJECT-IDENTITY Compressor head pressure has exceeded an upper threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5274 | current | ||
| lgpCondId5275CompressorLossofDifferentialPressure OBJECT-IDENTITY Compressor is shut down due to low differential pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5275 | current | ||
| lgpCondId5277CondenserFanIssue OBJECT-IDENTITY Condenser fan is not operating within its operational parameters. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5277 | current | ||
| lgpCondId5278LowCondenserRefrigerantPressure OBJECT-IDENTITY Refrigerant pressure in condenser coil is too low. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5278 | current | ||
| lgpCondId5280LowFluidPressure OBJECT-IDENTITY [Fluid Pressure] has dropped below a specified threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5280 | current | ||
| lgpCondId5293ReturnFluidOverTemp OBJECT-IDENTITY [Return Fluid Temperature] has exceeded a specified threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5293 | current | ||
| lgpCondId5294ReturnFluidUnderTemp OBJECT-IDENTITY [Return Fluid Temperature] has dropped below a specified threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5294 | current | ||
| lgpCondId5295ReturnFluidTempSensorIssue OBJECT-IDENTITY The return fluid temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5295 | current | ||
| lgpCondId5296TeamworkReturnFluidTempSensorIssue OBJECT-IDENTITY The return fluid temperature sensors for all Teamwork units are disconnected or the signals are out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5296 | current | ||
| lgpCondId5297AllPumpsLossofFlow OBJECT-IDENTITY System is shut down due to loss of flow in all available pumps. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5297 | current | ||
| lgpCondId5300PumpHoursExceeded OBJECT-IDENTITY [Pump Hours] has exceeded [Pump Hours Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5300 | current | ||
| lgpCondId5306FreeCoolingValveHoursExceeded OBJECT-IDENTITY [Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5306 | current | ||
| lgpCondId5308EvaporatorInletTempSensorIssue OBJECT-IDENTITY The evaporator inlet temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5308 | current | ||
| lgpCondId5309TeamworkEvaporatorInletTempSensorIssue OBJECT-IDENTITY The evaporator inlet temperature sensors for all Teamwork units are disconnected or the signals are out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5309 | current | ||
| lgpCondId5310EvaporatorFluidFreezeAutoReset OBJECT-IDENTITY Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down, but will restart when the temperature rises above the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5310 | current | ||
| lgpCondId5311EvaporatorFluidFreezeManualResetRequired OBJECT-IDENTITY Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down and requires a manual reset. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5311 | current | ||
| lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss OBJECT-IDENTITY While subgroup unit communication was lost, an event occurred on the subgroup unit. Please check subgroup unit event log. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5315 | current | ||
| lgpCondId5335ReturnAirUnderTemperature OBJECT-IDENTITY [Return Air Temperature] has dropped below [Low Return Air Temperature Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5335 | current | ||
| lgpCondId5349ExtAirSensorAHighHumidity OBJECT-IDENTITY [Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5349 | current | ||
| lgpCondId5351ExtAirSensorALowHumidity OBJECT-IDENTITY [Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5351 | current | ||
| lgpCondId5352CompressorShortCycle OBJECT-IDENTITY Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5352 | current | ||
| lgpCondId5354DigScrollCompDischargeTempSensorIssue OBJECT-IDENTITY Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5354 | current | ||
| lgpCondId5355DigScrollCompOverTemp OBJECT-IDENTITY Digital scroll compressor is shut down due to head temperature exceeding an upper threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5355 | current | ||
| lgpCondId5361ExtFreeCoolingLockout OBJECT-IDENTITY Free cooling is disabled by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5361 | current | ||
| lgpCondId5362FreeCoolingTempSensorIssue OBJECT-IDENTITY The free cooling fluid temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5362 | current | ||
| lgpCondId5365HotWaterHotGasValveHoursExceeded OBJECT-IDENTITY [Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5365 | current | ||
| lgpCondId5368ElectricReheaterHoursExceeded OBJECT-IDENTITY [Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5368 | current | ||
| lgpCondId5376MainFanOverload OBJECT-IDENTITY Main fan is shut down due to thermal overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5376 | current | ||
| lgpCondId5377Condenser OBJECT-IDENTITY Condenser is not operating within its operational parameters. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5377 | current | ||
| lgpCondId5415ExtLossofAirBlower OBJECT-IDENTITY Loss of air blower is detected, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5415 | current | ||
| lgpCondId5416ExtStandbyUnitOn OBJECT-IDENTITY Standby unit is on, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5416 | current | ||
| lgpCondId5417DigitalOutputBoardNotDetected OBJECT-IDENTITY Digital output board is required to be connected, but no signal is detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5417 | current | ||
| lgpCondId5418UnitCodeMissing OBJECT-IDENTITY Unit code has not been entered and saved. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5418 | current | ||
| lgpCondId5419UnitCommunicationLost OBJECT-IDENTITY Master has lost communication with one or more networked units. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5419 | current | ||
| lgpCondId5422OvertemperaturePowerOff OBJECT-IDENTITY Power turned off because equipment over temperature limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5422 | current | ||
| lgpCondId5423TooManySensors OBJECT-IDENTITY The number of sensors connected to the PDU exceeds the allowable limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5423 | current | ||
| lgpCondId5432TransformerOvertemperaturePowerOff OBJECT-IDENTITY Output power shutdown due to high transformer temperature. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5432 | current | ||
| lgpCondId5433TransformerOvertemperature OBJECT-IDENTITY Transformer temperature has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5433 | current | ||
| lgpCondId5434TransformerTemperatureSensorFail OBJECT-IDENTITY Transformer temperature sensor has failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5434 | current | ||
| lgpCondId5436LowAmbientTemperatureProbeTwo OBJECT-IDENTITY The system has detected a low ambient temperature condition on temperature probe 2. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5436 | current | ||
| lgpCondId5437HighAmbientTemperatureProbeTwo OBJECT-IDENTITY The system has detected a high ambient temperature condition on temperature probe 2. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5437 | current | ||
| lgpCondId5438ThermalRunawayDetected OBJECT-IDENTITY The system has detected a thermal runaway condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5438 | current | ||
| lgpCondId5439BatteryStringEqualize OBJECT-IDENTITY The system has detected a battery string equalize condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5439 | current | ||
| lgpCondId5440BatteryStringOffline OBJECT-IDENTITY The system has detected the battery string is offline. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5440 | current | ||
| lgpCondId5442DischargeLowCellVoltage OBJECT-IDENTITY The system has detected a low cell voltage condition during a discharge. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5442 | current | ||
| lgpCondId5447MMSPowerSharing OBJECT-IDENTITY A module is not sharing power with the other modules in a multi -module system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5447 | current | ||
| lgpCondId5453ModuleInStandbyIntelligentParalleling OBJECT-IDENTITY Module is placed into standby operation per Intelligent Paralleling. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5453 | current | ||
| lgpCondId5456ECOModeActive OBJECT-IDENTITY Conditions for Activation or Automatic Reactivation have been satisfied. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5456 | current | ||
| lgpCondId5457ECOModeSuspended OBJECT-IDENTITY ECO Mode session is suspended. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5457 | current | ||
| lgpCondId5458ExcessECOSuspends OBJECT-IDENTITY Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5458 | current | ||
| lgpCondId5471DoorOpen OBJECT-IDENTITY An open door was detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5471 | current | ||
| lgpCondId5472DoorSensorDisconnected OBJECT-IDENTITY Door sensor disconnect detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5472 | current | ||
| lgpCondId5479ContactClosureOpen OBJECT-IDENTITY An open circuit was detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5479 | current | ||
| lgpCondId5480ContactClosureClosed OBJECT-IDENTITY A closed circuit was detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5480 | current | ||
| lgpCondId5492ExtSystemCondensationDetected OBJECT-IDENTITY External system condensation detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5492 | current | ||
| lgpCondId5495ExtFanIssue OBJECT-IDENTITY One or more fans are not operating within their operational parameters. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5495 | current | ||
| lgpCondId5500ExtRemoteShutdown OBJECT-IDENTITY Unit is shut down by a remote signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5500 | current | ||
| lgpCondId5505HotAisleTempOutofRange OBJECT-IDENTITY The air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5505 | current | ||
| lgpCondId5508ColdAisleTempOutofRange OBJECT-IDENTITY The air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5508 | current | ||
| lgpCondId5512RemoteShutdown OBJECT-IDENTITY Unit is shut down by a remote signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5512 | current | ||
| lgpCondId5513CompressorCapacityReduced OBJECT-IDENTITY Compressor capacity has been reduced. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5513 | current | ||
| lgpCondId5514CompressorLowPressureTransducerIssue OBJECT-IDENTITY Compressor low pressure transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5514 | current | ||
| lgpCondId5524PDUNeutralOverCurrent OBJECT-IDENTITY The system has detected a neutral over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5524 | current | ||
| lgpCondId5531CondenserCommunicationLost OBJECT-IDENTITY Communication with condenser unit has been lost. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5531 | current | ||
| lgpCondId5535CondenserOutsideAirTempSensorIssue OBJECT-IDENTITY Condenser outside air temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5535 | current | ||
| lgpCondId5536CondenserOutsideAirTempOutofOperatingRange OBJECT-IDENTITY [Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5536 | current | ||
| lgpCondId5537CondenserControlBoardIssue OBJECT-IDENTITY The condenser control board is reporting an issue. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5537 | current | ||
| lgpCondId5539CondenserRefrigerantPressureOverThreshold OBJECT-IDENTITY Condenser refrigerant pressure has exceeded a threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5539 | current | ||
| lgpCondId5540CondenserRefrigerantPressureUnderThreshold OBJECT-IDENTITY Condenser refrigerant pressure has dropped below a threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5540 | current | ||
| lgpCondId5541CondenserRefrigerantPressureSensorIssue OBJECT-IDENTITY Condenser refrigerant pressure sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5541 | current | ||
| lgpCondId5542CondenserSupplyRefrigerantOverTemp OBJECT-IDENTITY Condenser supply refrigerant temperature has exceeded a threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5542 | current | ||
| lgpCondId5543CondenserSupplyRefrigerantUnderTemp OBJECT-IDENTITY Condenser supply refrigerant temperature has dropped below a specified threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5543 | current | ||
| lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue OBJECT-IDENTITY Condenser supply refrigerant temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5544 | current | ||
| lgpCondId5545CondenserMaxFanSpeedOverride OBJECT-IDENTITY Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5545 | current | ||
| lgpCondId5559EvaporatorReturnFluidOverTemp OBJECT-IDENTITY [Evaporator Return Fluid Temperature] has exceeded a threshold. The event is deactivated when the temperature drops below the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5559 | current | ||
| lgpCondId5560EvaporatorReturnFluidUnderTemp OBJECT-IDENTITY [Evaporator Return Fluid Temperature] has dropped below a threshold. The event is deactivated when the temperature rises above the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5560 | current | ||
| lgpCondId5561LBSActiveMaster OBJECT-IDENTITY This UPS system has been selected as the functional Master Load Bus Synchronization (LBS) system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5561 | current | ||
| lgpCondId5562LBSActiveSlave OBJECT-IDENTITY This UPS system is synchronized to the output bus of the UPS system that has been selected as the Master Load Bus Synchronization (LBS) system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5562 | current | ||
| lgpCondId5563DCBusLowFault OBJECT-IDENTITY The DC Bus voltage has reached a critical low level. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5563 | current | ||
| lgpCondId5564FanContactorOpen OBJECT-IDENTITY The fan contactor is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5564 | current | ||
| lgpCondId5565FanContactorOpenFail OBJECT-IDENTITY The fan contactor failed to open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5565 | current | ||
| lgpCondId5566FanContactorCloseFail OBJECT-IDENTITY The fan contactor failed to close. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5566 | current | ||
| lgpCondId5567IPInhibit OBJECT-IDENTITY The intelligent paralleling operation is inhibited. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5567 | current | ||
| lgpCondId5568InputUndervoltage OBJECT-IDENTITY One or more of the input phase voltages has dropped below the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5568 | current | ||
| lgpCondId5569InputOvervoltage OBJECT-IDENTITY One or more of the input phase voltages has exceeded the limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5569 | current | ||
| lgpCondId5573AmbientAirSensorIssue OBJECT-IDENTITY Ambient air sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5573 | current | ||
| lgpCondId5577ExtDewPointUnderTemperature OBJECT-IDENTITY At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5577 | current | ||
| lgpCondId5578DewPointOverTemperature OBJECT-IDENTITY Dew point temperature reading has exceeded the upper threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5578 | current | ||
| lgpCondId5579DewPointUnderTemperature OBJECT-IDENTITY Dew point temperature reading has dropped below the lower threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5579 | current | ||
| lgpCondId5588UnspecifiedGeneralEvent OBJECT-IDENTITY One or more unspecified events active. See local unit display for further details. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5588 | current | ||
| lgpCondId5593RemoteSensorAverageOverTemperature OBJECT-IDENTITY [Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5593 | current | ||
| lgpCondId5594RemoteSensorAverageUnderTemperature OBJECT-IDENTITY [Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5594 | current | ||
| lgpCondId5595RemoteSensorSystemAverageOverTemperature OBJECT-IDENTITY [Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5595 | current | ||
| lgpCondId5596RemoteSensorSystemAverageUnderTemperature OBJECT-IDENTITY [Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5596 | current | ||
| lgpCondId5597RemoteSensorOverTemperature OBJECT-IDENTITY [Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5597 | current | ||
| lgpCondId5598RemoteSensorUnderTemperature OBJECT-IDENTITY [Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5598 | current | ||
| lgpCondId5600AirEconomizerEmergencyOverride OBJECT-IDENTITY Indoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5600 | current | ||
| lgpCondId5601AirEconomizerReducedAirflow OBJECT-IDENTITY Air economizer filter is dirty and needs to be cleaned or replaced. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5601 | current | ||
| lgpCondId5604CompressorSuperheatOverThreshold OBJECT-IDENTITY Compressor discharge refrigerant superheat temperature has exceeded an upper threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5604 | current | ||
| lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent OBJECT-IDENTITY The delta temperature between a cell temperature and the ambient temperature has exceeded the thermal runaway cell to ambient temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5609 | current | ||
| lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent OBJECT-IDENTITY The delta temperature between two cells has exceeded the thermal runaway cell to cell temperature threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5610 | current | ||
| lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent OBJECT-IDENTITY The Battery-String charger current has exceeded the thermal runaway charger current level one threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5611 | current | ||
| lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent OBJECT-IDENTITY The Battery-String charger current has exceeded the thermal runaway charger current level two threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5612 | current | ||
| lgpCondId5617TemperatureControlSensorIssue OBJECT-IDENTITY The air sensor selected for cooling control is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5617 | current | ||
| lgpCondId5621EEVSuperheatBelowThreshold OBJECT-IDENTITY Electronic expansion valve refrigerant low superheat event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5621 | current | ||
| lgpCondId5622EEVDischargeTempAboveThreshold OBJECT-IDENTITY Electronic expansion valve refrigerant high discharge temperature event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5622 | current | ||
| lgpCondId5623EEVBatteryIssue OBJECT-IDENTITY Electronic expansion valve battery cannot be recharged and needs to be replaced. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5623 | current | ||
| lgpCondId5624EEVPowerIssue OBJECT-IDENTITY Electronic expansion valve lost power and is running on battery backup. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5624 | current | ||
| lgpCondId5625EEVUnspecifiedGeneralEvent OBJECT-IDENTITY One or more unspecified electronic expansion valve events active. See local unit display for further details. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5625 | current | ||
| lgpCondId5629StaticPressureSensorIssue OBJECT-IDENTITY The static pressure sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5629 | current | ||
| lgpCondId5630HighStaticPressure OBJECT-IDENTITY High static pressure event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5630 | current | ||
| lgpCondId5631LowStaticPressure OBJECT-IDENTITY Low static pressure event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5631 | current | ||
| lgpCondId5636PumpUnspecifiedGeneralEvent OBJECT-IDENTITY One or more unspecified pump events active. See local unit display for further details. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5636 | current | ||
| lgpCondId5637CondenserUnitUnspecifiedGeneralEvent OBJECT-IDENTITY One or more unspecified condenser unit events active. See local unit display for further details. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5637 | current | ||
| lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent OBJECT-IDENTITY One or more unspecified condenser circuit events active. See local unit display for further details. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5638 | current | ||
| lgpCondId5642SFAReservedEvent1 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5642 | current | ||
| lgpCondId5643SFAReservedEvent2 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5643 | current | ||
| lgpCondId5644SFAReservedEvent3 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5644 | current | ||
| lgpCondId5645SFAReservedEvent4 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5645 | current | ||
| lgpCondId5646SFAReservedEvent5 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5646 | current | ||
| lgpCondId5647SFAReservedEvent6 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5647 | current | ||
| lgpCondId5648SFAReservedEvent7 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5648 | current | ||
| lgpCondId5649SFAReservedEvent8 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5649 | current | ||
| lgpCondId5650SFAReservedEvent9 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5650 | current | ||
| lgpCondId5651SFAReservedEvent10 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5651 | current | ||
| lgpCondId5652SFAReservedEvent11 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5652 | current | ||
| lgpCondId5653SFAReservedEvent12 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5653 | current | ||
| lgpCondId5654SFAReservedEvent13 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5654 | current | ||
| lgpCondId5655SFAReservedEvent14 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5655 | current | ||
| lgpCondId5656SFAReservedEvent15 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5656 | current | ||
| lgpCondId5657SFAReservedEvent16 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5657 | current | ||
| lgpCondId5658SFAReservedEvent17 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5658 | current | ||
| lgpCondId5659SFAReservedEvent18 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5659 | current | ||
| lgpCondId5660SFAReservedEvent19 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5660 | current | ||
| lgpCondId5661SFAReservedEvent20 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5661 | current | ||
| lgpCondId5662SFAReservedEvent21 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5662 | current | ||
| lgpCondId5663SFAReservedEvent22 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5663 | current | ||
| lgpCondId5664SFAReservedEvent23 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5664 | current | ||
| lgpCondId5665SFAReservedEvent24 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5665 | current | ||
| lgpCondId5666SFAReservedEvent25 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5666 | current | ||
| lgpCondId5768OutletAirOvertemperatureLimit OBJECT-IDENTITY The difference between the outlet air temperature and inlet air temperature exceeds a specified maximum temperature. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5768 | current | ||
| lgpCondId5769EMOShutdown OBJECT-IDENTITY An Emergency Module Off command has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5769 | current | ||
| lgpCondId5770TopOutletFanFault OBJECT-IDENTITY Top outlet fan fault - one or more top outlet fans have failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5770 | current | ||
| lgpCondId5771MMSOverCapacity OBJECT-IDENTITY The multi-module system load is larger than the apparent power limit setting. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5771 | current | ||
| lgpCondId5773CompressorCapacityNormal OBJECT-IDENTITY Compressor has returned to normal load capacity. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5773 | current | ||
| lgpCondId5774CompressorContactorIssue OBJECT-IDENTITY Compressor contactor is not closing during compressor startup or is not opening during compressor shutdown. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5774 | current | ||
| lgpCondId5775UnitShutdownUnspecifiedGeneralEvent OBJECT-IDENTITY One or more unspecified unit shutdown events active. See local unit display for further details. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5775 | current | ||
| lgpCondId5776PDULowVoltageLN OBJECT-IDENTITY The system has detected a module under voltage condition (LN). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5776 | current | ||
| lgpCondId5777PDULowVoltageLL OBJECT-IDENTITY The system has detected a module under voltage condition (LL). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5777 | current | ||
| lgpCondId5778PDULowVoltageL1L2 OBJECT-IDENTITY The system has detected a line-to-line under voltage condition (L1 -L2). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5778 | current | ||
| lgpCondId5779PDULowVoltageL2L3 OBJECT-IDENTITY The system has detected a line-to-line under voltage condition (L2 -L3). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5779 | current | ||
| lgpCondId5780PDULowVoltageL3L1 OBJECT-IDENTITY The system has detected a line-to-line under voltage condition (L3 -L1). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5780 | current | ||
| lgpCondId5781PDULowVoltageL1N OBJECT-IDENTITY The system has detected a line to neutral under voltage condition (L1-N). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5781 | current | ||
| lgpCondId5782PDULowVoltageL2N OBJECT-IDENTITY The system has detected a line to neutral under voltage condition (L2-N). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5782 | current | ||
| lgpCondId5783PDULowVoltageL3N OBJECT-IDENTITY The system has detected a line to neutral under voltage condition (L3-N). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5783 | current | ||
| lgpCondId5784BranchLowVoltageLN OBJECT-IDENTITY The system has detected a module under voltage condition (LN). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5784 | current | ||
| lgpCondId5785BranchLowVoltageLL OBJECT-IDENTITY The system has detected a module under voltage condition (LL). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5785 | current | ||
| lgpCondId5786BranchLowVoltage OBJECT-IDENTITY The system has detected a module under voltage condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5786 | current | ||
| lgpCondId5788ContTieActive OBJECT-IDENTITY Continuous Power Tie Active. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5788 | current | ||
| lgpCondId5792UserkWhReset OBJECT-IDENTITY The user kWh accumulator was reset to zero by the operator. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5792 | current | ||
| lgpCondId5796PeakkWReset OBJECT-IDENTITY The Peak kW was reset. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5796 | current | ||
| lgpCondId5798BypassOverload OBJECT-IDENTITY Bypass overloaded, reduce load immediately. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5798 | current | ||
| lgpCondId5801LowBatteryShutdownImminent OBJECT-IDENTITY If active and guaranteed shutdown is enabled, a low battery reserve condition exists that will shutdown the UPS. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5801 | current | ||
| lgpCondId5806OutputOverload OBJECT-IDENTITY An overload exists on the output. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5806 | current | ||
| lgpCondId5807OutputOffPending OBJECT-IDENTITY Output off pending - shutdown imminent. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5807 | current | ||
| lgpCondId5808SystemShutdownOutputShort OBJECT-IDENTITY Shutdown was due to a short on the output. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5808 | current | ||
| lgpCondId5809SystemShutdownLowBattery OBJECT-IDENTITY Shutdown was due to a low battery condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5809 | current | ||
| lgpCondId5810SystemShutdownRemoteShutdown OBJECT-IDENTITY Shutdown was due to a remote communications shutdown command. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5810 | current | ||
| lgpCondId5811SystemShutdownHardwareFault OBJECT-IDENTITY Shutdown was due to an externally applied hardware control signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5811 | current | ||
| lgpCondId5817LossofRedundancy OBJECT-IDENTITY The system has an insufficient number of power modules to provide redundancy. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5817 | current | ||
| lgpCondId5818PowerModuleFailure OBJECT-IDENTITY One or more conditions indicate a power module failure, service is required. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5818 | current | ||
| lgpCondId5819PowerModuleWarning OBJECT-IDENTITY One or more power modules is reporting a warning condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5819 | current | ||
| lgpCondId5838PowerModuleFanFault OBJECT-IDENTITY The Power Module has detected a fan fault. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5838 | current | ||
| lgpCondId5839PowerModuleOverTemperature OBJECT-IDENTITY The Power Module has detected an over temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5839 | current | ||
| lgpCondId5840PowerModuleShutdownOverTemperature OBJECT-IDENTITY Power Module has shutdown due to over temperature. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5840 | current | ||
| lgpCondId5842ChargerModuleFanFault OBJECT-IDENTITY The Charger Module has detected a fan fault. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5842 | current | ||
| lgpCondId5847BatteryModuleTemperatureSensorFault OBJECT-IDENTITY A Battery Module temperature sensor fault has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5847 | current | ||
| lgpCondId5848BatteryModuleOverTemperature OBJECT-IDENTITY The Battery Module has detected an over temperature condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5848 | current | ||
| lgpCondId5849ReplaceBatteryModule OBJECT-IDENTITY The Battery Module needs to be replaced. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5849 | current | ||
| lgpCondId5850SystemShutdownTransformerOverTemperature OBJECT-IDENTITY System shutdown due to transformer over temperature. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5850 | current | ||
| lgpCondId5851MaximumLoadAlarm OBJECT-IDENTITY Maximum load alarm indicating load setting has been exceeded. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5851 | current | ||
| lgpCondId5856BatteryModuleFault OBJECT-IDENTITY One or more battery modules are reporting a fault condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5856 | current | ||
| lgpCondId5857BatteryModuleWarning OBJECT-IDENTITY One or more battery modules are reporting a warning condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5857 | current | ||
| lgpCondId5862CheckAirFilter OBJECT-IDENTITY Please check air filter, it may need to be cleaned or replaced. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5862 | current | ||
| lgpCondId5863TransformerFanFault OBJECT-IDENTITY The transformer fan has failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5863 | current | ||
| lgpCondId5865NoLoadWarning OBJECT-IDENTITY Indicates the UPS has output voltage but the output current is below a set threshold [No Load Warning Current Threshold] for a set period of time [No Load Warning Delay]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5865 | current | ||
| lgpCondId5871BatteryOverTemperatureLimit OBJECT-IDENTITY A battery temperature sensor is reporting a value above a predetermined limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5871 | current | ||
| lgpCondId5873UnexpectedMainBatteryDisconnectClosure OBJECT-IDENTITY The main battery disconnect has closed unexpectedly. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5873 | current | ||
| lgpCondId5874BatteryOverVoltage OBJECT-IDENTITY The system has detected that the battery voltage has exceeded a predetermined limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5874 | current | ||
| lgpCondId5875BatteryFuseFault OBJECT-IDENTITY One or more battery fuse faults has occurred. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5875 | current | ||
| lgpCondId5878MainBatteryDisconnectForcedToUnlock OBJECT-IDENTITY The main battery disconnect is forced to the unlocked state. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5878 | current | ||
| lgpCondId5879VdcBackfeed OBJECT-IDENTITY The voltage between battery and DC bus measurements is out of tolerance. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5879 | current | ||
| lgpCondId5880RectifierConfigurationChangeRequest OBJECT-IDENTITY This event indicates that the battery is not configured and PFC is not enabled. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5880 | current | ||
| lgpCondId5881RegenerationActive OBJECT-IDENTITY Regeneration operation is active. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5881 | current | ||
| lgpCondId5882RegenerationOperationTerminated OBJECT-IDENTITY Regeneration operation is not active. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5882 | current | ||
| lgpCondId5883RegenerationOperationFailure OBJECT-IDENTITY Regeneration operation has been terminated due to bypass source instability or unit misoperation. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5883 | current | ||
| lgpCondId5884ProgramInputContact01 OBJECT-IDENTITY When the signal from [Program Input Contact 01] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5884 | current | ||
| lgpCondId5885ProgramInputContact02 OBJECT-IDENTITY When the signal from [Program Input Contact 02] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5885 | current | ||
| lgpCondId5886ProgramInputContact03 OBJECT-IDENTITY When the signal from [Program Input Contact 03] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5886 | current | ||
| lgpCondId5887ProgramInputContact04 OBJECT-IDENTITY When the signal from [Program Input Contact 04] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5887 | current | ||
| lgpCondId5888ProgramInputContact05 OBJECT-IDENTITY When the signal from [Program Input Contact 05] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5888 | current | ||
| lgpCondId5889ProgramInputContact06 OBJECT-IDENTITY When the signal from [Program Input Contact 06] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5889 | current | ||
| lgpCondId5890ProgramInputContact07 OBJECT-IDENTITY When the signal from [Program Input Contact 07] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5890 | current | ||
| lgpCondId5891ProgramInputContact08 OBJECT-IDENTITY When the signal from [Program Input Contact 08] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5891 | current | ||
| lgpCondId5892ProgramInputContact09 OBJECT-IDENTITY When the signal from [Program Input Contact 09] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5892 | current | ||
| lgpCondId5893ProgramInputContact10 OBJECT-IDENTITY When the signal from [Program Input Contact 10] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5893 | current | ||
| lgpCondId5894ProgramInputContact11 OBJECT-IDENTITY When the signal from [Program Input Contact 11] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5894 | current | ||
| lgpCondId5895ProgramInputContact12 OBJECT-IDENTITY When the signal from [Program Input Contact 12] is active the function assigned to this contact is executed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5895 | current | ||
| lgpCondId5896GroundFaultDetected OBJECT-IDENTITY The system has detected a ground fault on a Battery-String. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5896 | current | ||
| lgpCondId5902ReturnHumiditySensorIssue OBJECT-IDENTITY The humidity sensor at the inlet of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5902 | current | ||
| lgpCondId5903CompressorLowDifferentialPressureLockout OBJECT-IDENTITY Compressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5903 | current | ||
| lgpCondId5906AirflowSensorIssue OBJECT-IDENTITY Airflow sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5906 | current | ||
| lgpCondId5907ExtAirDamperPositionIssue OBJECT-IDENTITY Air damper position does not match expected value, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5907 | current | ||
| lgpCondId5908ExtPowerSourceAFailure OBJECT-IDENTITY Unit main power source A failure, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5908 | current | ||
| lgpCondId5909ExtPowerSourceBFailure OBJECT-IDENTITY Unit main power source B failure, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5909 | current | ||
| lgpCondId5910StaticPressureSensorOutofRange OBJECT-IDENTITY Static pressure sensor signal is out of its configured range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5910 | current | ||
| lgpCondId5911FluidTemperatureSensorIssue OBJECT-IDENTITY The fluid temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5911 | current | ||
| lgpCondId5912FluidFlowSensorIssue OBJECT-IDENTITY The fluid flow sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5912 | current | ||
| lgpCondId5914OverDifferentialPressure OBJECT-IDENTITY An over differential pressure condition was detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5914 | current | ||
| lgpCondId5915UnderDifferentialPressure OBJECT-IDENTITY An under differential pressure condition was detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5915 | current | ||
| lgpCondId5924MixedModeLockout OBJECT-IDENTITY Mixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on one refrigeration circuit and the use of a refrigerant pump on the other circuit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5924 | current | ||
| lgpCondId5928UnbalancedLoadCondition OBJECT-IDENTITY The system has detected a line-to-line unbalanced load condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5928 | current | ||
| lgpCondId5939BranchOverCurrentProtection OBJECT-IDENTITY The Branch Receptacle Module's over current protection is triggered. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5939 | current | ||
| lgpCondId5948BranchLowVoltageLL OBJECT-IDENTITY The system has detected a module under voltage condition (LL). | 1.3.6.1.4.1.476.1.42.3.2.7.1.5948 | current | ||
| lgpCondId5957BypassInputVoltageFault OBJECT-IDENTITY The system has detected the bypass voltage is unqualified. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5957 | current | ||
| lgpCondId5958BatteryTemperatureOutofRange OBJECT-IDENTITY Battery temperature is outside of acceptable range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5958 | current | ||
| lgpCondId5960InverterOverload OBJECT-IDENTITY Inverter in overload fault. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5960 | current | ||
| lgpCondId5966AuxAirTempDeviceCommunicationLost OBJECT-IDENTITY Communication with external auxiliary device providing an air temperature value has been lost. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5966 | current | ||
| lgpCondId5967ModbusPowerMeterCommunicationLost OBJECT-IDENTITY Communication with Modbus power meter has been lost. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5967 | current | ||
| lgpCondId5968InverterDesaturation OBJECT-IDENTITY Inverter Desaturation. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5968 | current | ||
| lgpCondId5969GenericDICFault OBJECT-IDENTITY The control board reports a fault - Service required. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5969 | current | ||
| lgpCondId5970GroundFault OBJECT-IDENTITY An AC phase to ground fault or three phase fault to ground exists on the output of the UPS. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5970 | current | ||
| lgpCondId5973InputBreakerOpen OBJECT-IDENTITY The main input breaker is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5973 | current | ||
| lgpCondId5974NeutralBreakerOpen OBJECT-IDENTITY The neutral breaker is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5974 | current | ||
| lgpCondId5975OutputBreakerOpen OBJECT-IDENTITY The output breaker is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5975 | current | ||
| lgpCondId5976MaintenanceBypassBreakerClosed OBJECT-IDENTITY The maintenance bypass breaker is closed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5976 | current | ||
| lgpCondId5977BatteryBreakerOpen OBJECT-IDENTITY The battery circuit is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5977 | current | ||
| lgpCondId5978RectifierIsolationBreakerRFBOpen OBJECT-IDENTITY The rectifier isolation breaker (RFB) indicates that it is in the open position. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5978 | current | ||
| lgpCondId5982BypassBreakerSBBOpen OBJECT-IDENTITY The bypass circuit breaker (SBB) indicates that it is in the open position. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5982 | current | ||
| lgpCondId5983BypassIsolationBreakerBIBOpen OBJECT-IDENTITY The bypass isolation breaker (BIB) indicates that it is in the open position. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5983 | current | ||
| lgpCondId5984BypassUndervoltageWarning OBJECT-IDENTITY The voltage on one or more bypass phases is less than a specified percentage of the nominal voltage. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5984 | current | ||
| lgpCondId5985BypassStaticSwitchBPSSOn OBJECT-IDENTITY The Bypass Static Switch has been turned on. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5985 | current | ||
| lgpCondId5998BattOvtempWarning OBJECT-IDENTITY A battery temperature sensor is reporting a value above the setpoint. | 1.3.6.1.4.1.476.1.42.3.2.7.1.5998 | current | ||
| lgpCondId6009InverterOutputBreakerOpen OBJECT-IDENTITY The inverter output breaker indicates that it is in the open position. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6009 | current | ||
| lgpCondId6011EquipmentOverTempWarning OBJECT-IDENTITY Equipment over temperature warning is a summary event based on the detection of at least one measured temperature exceeding a threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6011 | current | ||
| lgpCondId6012EquipmentOvertemperatureLimit OBJECT-IDENTITY The equipment air temperature has exceeded its maximum set point. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6012 | current | ||
| lgpCondId6045RectifierInputBreakerOpen OBJECT-IDENTITY The rectifier isolation breaker indicates that it is in the open position. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6045 | current | ||
| lgpCondId6046LoadonUPS OBJECT-IDENTITY The output is being supplied power from the inverter. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6046 | current | ||
| lgpCondId6047Core2CoreFuseFailure OBJECT-IDENTITY Core-2-core fuse failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6047 | current | ||
| lgpCondId6052SystemOutputBreakerOpen OBJECT-IDENTITY The system output breaker is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6052 | current | ||
| lgpCondId6059InverterRelayFault OBJECT-IDENTITY The inverter relay has malfunctioned. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6059 | current | ||
| lgpCondId6060TransfertoBypassSystemOverload OBJECT-IDENTITY The UPS System has transferred to bypass because the active power modules cannot support the critical load. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6060 | current | ||
| lgpCondId6061InputSourceBackfeed OBJECT-IDENTITY The battery is backfeeding the input source. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6061 | current | ||
| lgpCondId6062LossofSynchronization OBJECT-IDENTITY The inverter and bypass are no longer synchronized. . | 1.3.6.1.4.1.476.1.42.3.2.7.1.6062 | current | ||
| lgpCondId6063BatteryConverterCurrentLimit OBJECT-IDENTITY The battery converter has reached is maximum current limit. . | 1.3.6.1.4.1.476.1.42.3.2.7.1.6063 | current | ||
| lgpCondId6064LBSCableFailure OBJECT-IDENTITY Load Bus Sync communications is abnormal. A problem with the LBS cable may exist. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6064 | current | ||
| lgpCondId6065BatteryChargeEqualizationTimeout OBJECT-IDENTITY The battery equalizing is time out. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6065 | current | ||
| lgpCondId6066ParallelCableFailure OBJECT-IDENTITY The UPS parallel system communications is abnormal. A problem with the parallel cable may exist. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6066 | current | ||
| lgpCondId6067BatteryFault OBJECT-IDENTITY A short circuit exists in the battery system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6067 | current | ||
| lgpCondId6068BatteryRoomAlarm OBJECT-IDENTITY The ambient temperature of the battery room is abnormal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6068 | current | ||
| lgpCondId6080UPSCCommunicationFailure OBJECT-IDENTITY The UPSC has failed to communicate in a designated time period. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6080 | current | ||
| lgpCondId6092Compressor1BThermalOverload OBJECT-IDENTITY Fixed compressor 1B is shut down due to thermal overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6092 | current | ||
| lgpCondId6093Compressor2BThermalOverload OBJECT-IDENTITY Fixed compressor 2B is shut down due to thermal overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6093 | current | ||
| lgpCondId6094Compressor1BHoursExceeded OBJECT-IDENTITY Fixed compressor 1B run hours have exceeded the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6094 | current | ||
| lgpCondId6095Compressor2BHoursExceeded OBJECT-IDENTITY Fixed compressor 2B run hours have exceeded the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6095 | current | ||
| lgpCondId6100CondenserRemoteShutdown OBJECT-IDENTITY Condenser is shut down by a remote signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6100 | current | ||
| lgpCondId6105ExternalCondenserTVSSIssue OBJECT-IDENTITY The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6105 | current | ||
| lgpCondId6106ExternalCondenserVFDIssue OBJECT-IDENTITY The condenser fan Variable Frequency Drive is offline, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6106 | current | ||
| lgpCondId6107ExternalCondenserIssue OBJECT-IDENTITY Condenser is not operating within its operational parameters, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6107 | current | ||
| lgpCondId6119Slotsnotavailable OBJECT-IDENTITY The number of sensors exceeds the number of allocated slots and cannot be displayed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6119 | current | ||
| lgpCondId6180BatteryUnderVoltage OBJECT-IDENTITY Battery voltage is too low. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6180 | current | ||
| lgpCondId6182ReplaceBattery OBJECT-IDENTITY The battery is due for replacement. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6182 | current | ||
| lgpCondId6186InputFrequencyDeviation OBJECT-IDENTITY The input frequency is outside of the normal range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6186 | current | ||
| lgpCondId6187ShutdownPending OBJECT-IDENTITY Shutdown is pending. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6187 | current | ||
| lgpCondId6194SystemRebootCommandIssued OBJECT-IDENTITY Reboot command issued to the system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6194 | current | ||
| lgpCondId6203SensorAdded OBJECT-IDENTITY Sensor Added. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6203 | current | ||
| lgpCondId6204SensorRemoved OBJECT-IDENTITY Sensor Removed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6204 | current | ||
| lgpCondId6205WaterLeakDetected OBJECT-IDENTITY Water leak detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6205 | current | ||
| lgpCondId6210FirmwareUpdateInProgress OBJECT-IDENTITY Firmware update has started and is in progress. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6210 | current | ||
| lgpCondId6211FirmwareUpdateCompletedSuccessfully OBJECT-IDENTITY Firmware update has completed successfully. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6211 | current | ||
| lgpCondId6212FirmwareUpdateCompletedUnsuccessfully OBJECT-IDENTITY Firmware update has completed, but was not successful. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6212 | current | ||
| lgpCondId6216PrechargeCircuitFailed OBJECT-IDENTITY DC Bus precharge/discharge didn't reach specified level within a specified time. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6216 | current | ||
| lgpCondId6217MemoryCardRemoved OBJECT-IDENTITY The memory card on the control board has been removed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6217 | current | ||
| lgpCondId6218AutoCalibrationActive OBJECT-IDENTITY The system is automatically calibrating ADC channels. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6218 | current | ||
| lgpCondId6219AutoCalibrationFailed OBJECT-IDENTITY ADC channel calibration has failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6219 | current | ||
| lgpCondId6220ModuleOutputBreakerOpen OBJECT-IDENTITY The module output breaker is open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6220 | current | ||
| lgpCondId6221NeutralVoltageFault OBJECT-IDENTITY Voltage observed on neutral line. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6221 | current | ||
| lgpCondId6222BranchLoadLoss OBJECT-IDENTITY Loss of load on branch detected. Branch circuit breaker might be open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6222 | current | ||
| lgpCondId6225RemoteSensorLowHumidity OBJECT-IDENTITY Remote sensor humidity has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6225 | current | ||
| lgpCondId6226RemoteSensorHighHumidity OBJECT-IDENTITY Remote sensor humidity has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6226 | current | ||
| lgpCondId6227RemoteSensorAverageLowHumidity OBJECT-IDENTITY The average humidity of multiple remote sensors on the cooling unit has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6227 | current | ||
| lgpCondId6228RemoteSensorAverageHighHumidity OBJECT-IDENTITY The average humidity of multiple remote sensors on the cooling unit has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6228 | current | ||
| lgpCondId6229RemoteSensorSystemAverageLowHumidity OBJECT-IDENTITY The average humidity of multiple remote sensors on interconnected cooling units in a single system has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6229 | current | ||
| lgpCondId6230RemoteSensorSystemAverageHighHumidity OBJECT-IDENTITY The average humidity of multiple remote sensors on interconnected cooling units in a single system has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6230 | current | ||
| lgpCondId6231LowCompressorSuperheat OBJECT-IDENTITY Compressor suction superheat has dropped below a lower threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6231 | current | ||
| lgpCondId6232SECUnspecifiedGeneralEvent OBJECT-IDENTITY One or more unspecified events active for the Superheat and Envelope Controller. See local unit display for further details. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6232 | current | ||
| lgpCondId6233SECCommunicationLost OBJECT-IDENTITY Communication with the Superheat and Envelope Controller has been lost. The event is deactivated when communication is re -established. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6233 | current | ||
| lgpCondId6236PowerSourceAIssue OBJECT-IDENTITY No power is detected at power source input 'A'. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6236 | current | ||
| lgpCondId6237PowerSourceBIssue OBJECT-IDENTITY No power is detected at power source input 'B'. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6237 | current | ||
| lgpCondId6239FluidValveHoursExceeded OBJECT-IDENTITY Operating hours for the fluid valve have exceeded the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6239 | current | ||
| lgpCondId6253BoosterFailure OBJECT-IDENTITY Booster failure - boost is off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6253 | current | ||
| lgpCondId6254ChargerFailure OBJECT-IDENTITY Charger Failure - Charger is off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6254 | current | ||
| lgpCondId6274UnitTopReturnAirSensorFailure OBJECT-IDENTITY Return air sensor at the top of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6274 | current | ||
| lgpCondId6275UnitMiddleReturnAirSensorFailure OBJECT-IDENTITY Return air sensor in the middle of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6275 | current | ||
| lgpCondId6276UnitBottomReturnAirSensorFailure OBJECT-IDENTITY Return air sensor at the bottom of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6276 | current | ||
| lgpCondId6277UnitTopSupplyAirSensorFailure OBJECT-IDENTITY Supply air sensor at the top of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6277 | current | ||
| lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure OBJECT-IDENTITY First supply air sensor in the middle of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6278 | current | ||
| lgpCondId6279UnitBottomSupplyAirSensorFailure OBJECT-IDENTITY Supply air sensor at the bottom of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6279 | current | ||
| lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure OBJECT-IDENTITY Second supply air sensor in the middle of the unit is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6284 | current | ||
| lgpCondId6293ChilledWaterControlActive OBJECT-IDENTITY Chilled water inlet temperature control function is enabled due to 'bad' water. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6293 | current | ||
| lgpCondId6294ChilledWaterFlowTransducerFailure OBJECT-IDENTITY Chilled water flow transducer is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6294 | current | ||
| lgpCondId6295ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY Chilled water inlet temperature sensor is disconnected or the signal is out of range. The sensor is mandatory for the chilled water flow function. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6295 | current | ||
| lgpCondId6296ChilledWaterHighInletTemperature OBJECT-IDENTITY Chilled water inlet temperature has exceeded an upper threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6296 | current | ||
| lgpCondId6297Modbus010VModuleCommunicationFailure OBJECT-IDENTITY Modbus 0-10V module for managing the second Chilled Water circuit valve is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6297 | current | ||
| lgpCondId6299RackDoorsOpen OBJECT-IDENTITY Rack doors opened due to supply air temperature exceeding the [Rack Door Open High Supply Air Temperature Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6299 | current | ||
| lgpCondId6303TeamStaticPressureSensorFailure OBJECT-IDENTITY The team static pressure sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6303 | current | ||
| lgpCondId6304HeatingLockout OBJECT-IDENTITY Heating is shut down and disabled. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6304 | current | ||
| lgpCondId6305FreeCoolingStoppedHighRoomTemp OBJECT-IDENTITY Free cooling is temporarily disabled due to room temperature exceeding a preset delta above the the set point. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6305 | current | ||
| lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure OBJECT-IDENTITY Cold aisle team sensor measuring air temperature and humidity is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6306 | current | ||
| lgpCondId6309ColdAisleAirSensorFailure OBJECT-IDENTITY Cold aisle sensor measuring air temperature and humidity is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6309 | current | ||
| lgpCondId6310ChilledWaterInletTemperatureControlActive OBJECT-IDENTITY Chilled water inlet temperature control is active. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6310 | current | ||
| lgpCondId6313ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY Chilled water inlet temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6313 | current | ||
| lgpCondId6314ChilledWaterOutletTemperatureSensorFailure OBJECT-IDENTITY Chilled water outlet temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6314 | current | ||
| lgpCondId6315ChilledWaterFlowMeterSensorFailure OBJECT-IDENTITY Chilled water flow meter sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6315 | current | ||
| lgpCondId6333Bypassoutofsync OBJECT-IDENTITY Bypass and Inverter inputs are not in sync. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6333 | current | ||
| lgpCondId6348SystemOutputoffasrequested OBJECT-IDENTITY The UPS has shutdown as requested, i.e., the output is off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6348 | current | ||
| lgpCondId6349SystemOffasrequested OBJECT-IDENTITY The entire UPS has shutdown as commanded. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6349 | current | ||
| lgpCondId6350GeneralFault OBJECT-IDENTITY A general fault in the UPS has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6350 | current | ||
| lgpCondId6351UPSAwaitingPower OBJECT-IDENTITY The UPS output is off and the UPS is awaiting the return of input power. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6351 | current | ||
| lgpCondId6352AutonomyCalibration OBJECT-IDENTITY Calibration test occurred. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6352 | current | ||
| lgpCondId6353GeneralWarning OBJECT-IDENTITY A warning in the UPS has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6353 | current | ||
| lgpCondId6354BatteryCharging OBJECT-IDENTITY The UPS battery is charging (battery charge percentage lower than 98). | 1.3.6.1.4.1.476.1.42.3.2.7.1.6354 | current | ||
| lgpCondId6355BackfeedRelayFailure OBJECT-IDENTITY Bypass SCR is wrongly on or commutated. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6355 | current | ||
| lgpCondId6356BatteryCircuitOpen OBJECT-IDENTITY Battery Circuit Open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6356 | current | ||
| lgpCondId6357SystemRestartPending OBJECT-IDENTITY A request for UPS restart has been received. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6357 | current | ||
| lgpCondId6358PipeTemperatureSensorFailure OBJECT-IDENTITY Air temperature sensor located in the pipe is not sending a valid value. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6358 | current | ||
| lgpCondId6362SFAReservedEvent26 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6362 | current | ||
| lgpCondId6363SFAReservedEvent27 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6363 | current | ||
| lgpCondId6364SFAReservedEvent28 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6364 | current | ||
| lgpCondId6365SFAReservedEvent29 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6365 | current | ||
| lgpCondId6366SFAReservedEvent30 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6366 | current | ||
| lgpCondId6367SFAReservedEvent31 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6367 | current | ||
| lgpCondId6368SFAReservedEvent32 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6368 | current | ||
| lgpCondId6369SFAReservedEvent33 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6369 | current | ||
| lgpCondId6370SFAReservedEvent34 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6370 | current | ||
| lgpCondId6371SFAReservedEvent35 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6371 | current | ||
| lgpCondId6372SFAReservedEvent36 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6372 | current | ||
| lgpCondId6373SFAReservedEvent37 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6373 | current | ||
| lgpCondId6374SFAReservedEvent38 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6374 | current | ||
| lgpCondId6375SFAReservedEvent39 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6375 | current | ||
| lgpCondId6376SFAReservedEvent40 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6376 | current | ||
| lgpCondId6377SFAReservedEvent41 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6377 | current | ||
| lgpCondId6378SFAReservedEvent42 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6378 | current | ||
| lgpCondId6379SFAReservedEvent43 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6379 | current | ||
| lgpCondId6380SFAReservedEvent44 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6380 | current | ||
| lgpCondId6381SFAReservedEvent45 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6381 | current | ||
| lgpCondId6382SFAReservedEvent46 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6382 | current | ||
| lgpCondId6383SFAReservedEvent47 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6383 | current | ||
| lgpCondId6384SFAReservedEvent48 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6384 | current | ||
| lgpCondId6385SFAReservedEvent49 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6385 | current | ||
| lgpCondId6386SFAReservedEvent50 OBJECT-IDENTITY Reserved event for SFA use. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6386 | current | ||
| lgpCondId6438PowerModuleInputCurrentAbnormal OBJECT-IDENTITY Input current of the power module is abnormal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6438 | current | ||
| lgpCondId6439PowerModuleBalancerofDCBusFailure OBJECT-IDENTITY Balancer of DC Bus in the power module has failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6439 | current | ||
| lgpCondId6440PowerModuleFuseFailure OBJECT-IDENTITY A summary event indicating one or more fuse failures in the power module. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6440 | current | ||
| lgpCondId6441PowerModulePowerSupplyFailure OBJECT-IDENTITY Power module power supply failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6441 | current | ||
| lgpCondId6450PDUPoweredOn OBJECT-IDENTITY The PDU was powered on. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6450 | current | ||
| lgpCondId6453InputWiringFault OBJECT-IDENTITY The neutral/ground conductors on the input wiring are not properly bonded, or the line/neutral conductors have been swapped. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6453 | current | ||
| lgpCondId6454DCtoDCConverterFault OBJECT-IDENTITY A failure has occurred in the battery discharge circuit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6454 | current | ||
| lgpCondId6455LeakSensorCableFault OBJECT-IDENTITY A fault is detected in the 'Leak Sensor' cable. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6455 | current | ||
| lgpCondId6518StandbyUnitActivatedDuetoChillerFailure OBJECT-IDENTITY External chiller unit has failed for this unit, so the standby cooling unit has been activated. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6518 | current | ||
| lgpCondId6522PDUResidualOverCurrent OBJECT-IDENTITY The system has detected a PDU residual over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6522 | current | ||
| lgpCondId6527PDUOverCurrentProtection OBJECT-IDENTITY The PDU over current protection is triggered. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6527 | current | ||
| lgpCondId6528PowerModuleLeverUnlocked OBJECT-IDENTITY The power module is inactive because the lever is in the unlocked position. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6528 | current | ||
| lgpCondId6529HardwareMismatch OBJECT-IDENTITY The assigned system model settings do not match the actual installed hardware. The module count is wrong, or a module of the wrong type is installed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6529 | current | ||
| lgpCondId6530SupplyNTCAirSensorIssue OBJECT-IDENTITY The supply NTC air sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6530 | current | ||
| lgpCondId6531ExternalAirSensorCIssue OBJECT-IDENTITY The external air sensor C is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6531 | current | ||
| lgpCondId6532ExternalAirSensorDIssue OBJECT-IDENTITY The external air sensor D is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6532 | current | ||
| lgpCondId6533ExternalAirSensorEIssue OBJECT-IDENTITY The external air sensor E is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6533 | current | ||
| lgpCondId6534PumpThermalOverload OBJECT-IDENTITY Pump is shut down due to thermal overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6534 | current | ||
| lgpCondId6535XDModuleCommunicationLost OBJECT-IDENTITY Communication with XD Module has been lost. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6535 | current | ||
| lgpCondId6536MMSCapacityExceeded OBJECT-IDENTITY The critical load is larger than the redundant rating of a 1+N redundant multi-module system. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6536 | current | ||
| lgpCondId6538TSAControlInputIssue OBJECT-IDENTITY The analog input used to set the air temperature set point for cooling control is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6538 | current | ||
| lgpCondId6539ChilledWaterValveHoursExceeded OBJECT-IDENTITY [Chilled Water Valve Hours] has exceeded [Chilled Water Valve Operating Hours Threshold]. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6539 | current | ||
| lgpCondId6540FSAControlInputIssue OBJECT-IDENTITY The analog input used to set the air temperature set point for fan speed control is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6540 | current | ||
| lgpCondId6541AutoTuneLicenseExpiring OBJECT-IDENTITY License for the AutoTune feature has not been refreshed in 30 days and will be expiring soon. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6541 | current | ||
| lgpCondId6542AutoTuneLicenseExpired OBJECT-IDENTITY License for the AutoTune feature has expired. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6542 | current | ||
| lgpCondId6543UnitInStandbyDueToCoolingLoss OBJECT-IDENTITY Unit forced into standby because it is unable to provide any cooling. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6543 | current | ||
| lgpCondId6544ControlUnitsRemoteShutdownMismatch OBJECT-IDENTITY The remote shutdown status of the primary control unit does not match the remote shutdown status of the secondary control unit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6544 | current | ||
| lgpCondId6545SecondaryControlUnitCommunicationLost OBJECT-IDENTITY The primary control unit has lost Ethernet communications with the secondary control unit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6545 | current | ||
| lgpCondId6546ControlUnitsUnitCodeMismatch OBJECT-IDENTITY Unit codes for the primary and secondary control units do not match. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6546 | current | ||
| lgpCondId6547SSAControlInputIssue OBJECT-IDENTITY The analog input used to set the static pressure set point for fan speed control is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6547 | current | ||
| lgpCondId6574SubfeedPhaseUndercurrent OBJECT-IDENTITY Subfeed breaker phase current has dropped below the threshold. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6574 | current | ||
| lgpCondId6587TransferCountCleared OBJECT-IDENTITY A system event indicating the transfer count has been cleared. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6587 | current | ||
| lgpCondId6588EnergyCounterCleared OBJECT-IDENTITY A system event indicating the energy counter (e.g. KWH) has been cleared. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6588 | current | ||
| lgpCondId6589HistoryLogsFull OBJECT-IDENTITY The history logs are full. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6589 | current | ||
| lgpCondId6590HistoryLogsCleared OBJECT-IDENTITY History logs have been cleared. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6590 | current | ||
| lgpCondId6591EventLogCleared OBJECT-IDENTITY All past alarms and faults have been cleared. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6591 | current | ||
| lgpCondId6592SystemDateChanged OBJECT-IDENTITY The system date has been updated. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6592 | current | ||
| lgpCondId6593SystemTimeChanged OBJECT-IDENTITY The system time has been updated. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6593 | current | ||
| lgpCondId6594AccessPasswordChanged OBJECT-IDENTITY The access password has been changed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6594 | current | ||
| lgpCondId6595ConfigModified OBJECT-IDENTITY A setpoint has been updated. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6595 | current | ||
| lgpCondId6612SCRShort OBJECT-IDENTITY The SCR is in a short condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6612 | current | ||
| lgpCondId6613SCROpen OBJECT-IDENTITY The SCR is in an open condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6613 | current | ||
| lgpCondId6614ACPowerSupplyFail OBJECT-IDENTITY A failure of the AC Power Supply has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6614 | current | ||
| lgpCondId6615DCPowerSupplyFail OBJECT-IDENTITY A failure of the DC Power Supply has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6615 | current | ||
| lgpCondId6616VoltageSensorFail OBJECT-IDENTITY A voltage sensor failure has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6616 | current | ||
| lgpCondId6617SCRSensorFail OBJECT-IDENTITY The SCR sensor module failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6617 | current | ||
| lgpCondId6618CurrentSensorFail OBJECT-IDENTITY The current sensor module failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6618 | current | ||
| lgpCondId6619GateDriveFail OBJECT-IDENTITY The Gate Drive module failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6619 | current | ||
| lgpCondId6620SurgeFail OBJECT-IDENTITY The surge module failed for the input source. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6620 | current | ||
| lgpCondId6621FastUnderVoltage OBJECT-IDENTITY Fast under voltage detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6621 | current | ||
| lgpCondId6622SlowUnderVoltage OBJECT-IDENTITY Slow under voltage detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6622 | current | ||
| lgpCondId6623OverVoltage OBJECT-IDENTITY Over voltage detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6623 | current | ||
| lgpCondId6624OverUnderFrequencyFail OBJECT-IDENTITY An over or under frequency condition has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6624 | current | ||
| lgpCondId6625GeneralSourceFailure OBJECT-IDENTITY A non-specific failure has been detected in the source. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6625 | current | ||
| lgpCondId6626OverCurrent OBJECT-IDENTITY An over current has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6626 | current | ||
| lgpCondId6627PeakCurrentOffLimit OBJECT-IDENTITY The peak current has exceeded the setpoint defined by I-PK Xfer Lockout. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6627 | current | ||
| lgpCondId6628SyncFail OBJECT-IDENTITY A phase rotation/out of synchronization failure has been detected. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6628 | current | ||
| lgpCondId6629InputOverVoltage OBJECT-IDENTITY Input over voltage. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6629 | current | ||
| lgpCondId6630InputUnderVoltage OBJECT-IDENTITY Input under voltage. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6630 | current | ||
| lgpCondId6631InputOverUnderFrequency OBJECT-IDENTITY Input over/under frequency. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6631 | current | ||
| lgpCondId6635VoltageSenseFail OBJECT-IDENTITY Output voltage sense failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6635 | current | ||
| lgpCondId6636LoadonAlternateSource OBJECT-IDENTITY The load is on the alternate source. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6636 | current | ||
| lgpCondId6637UnderVoltageFail OBJECT-IDENTITY Output under voltage failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6637 | current | ||
| lgpCondId6638OutputOverCurrent OBJECT-IDENTITY Output is over current. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6638 | current | ||
| lgpCondId6639GroundOverCurrent OBJECT-IDENTITY Ground is over current. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6639 | current | ||
| lgpCondId6640NeutralOverCurrent OBJECT-IDENTITY Neutral is over current. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6640 | current | ||
| lgpCondId6641LoadVoltageTHD OBJECT-IDENTITY Load voltage THD has exceeded the set limit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6641 | current | ||
| lgpCondId6662ControlLogicFail OBJECT-IDENTITY A control logic module has failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6662 | current | ||
| lgpCondId6663PowerSupplyLogicFail OBJECT-IDENTITY A power supply module has failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6663 | current | ||
| lgpCondId6664ExternalCommsFailure OBJECT-IDENTITY External communications failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6664 | current | ||
| lgpCondId6665HeatSinkOverTemp OBJECT-IDENTITY The system heat sink temperature has exceeded design limits. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6665 | current | ||
| lgpCondId6666AutomaticTransferInhibited OBJECT-IDENTITY Automatic transfer is inhibited. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6666 | current | ||
| lgpCondId6667InputSourceTransferInhibited OBJECT-IDENTITY Input source transfer is inhibited. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6667 | current | ||
| lgpCondId6676CB1ShuntTrip OBJECT-IDENTITY CB1 Shunt Trip event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6676 | current | ||
| lgpCondId6677CB2ShuntTrip OBJECT-IDENTITY CB2 Shunt Trip event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6677 | current | ||
| lgpCondId6678CB6NeutralOpen OBJECT-IDENTITY CB6 neutral open event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6678 | current | ||
| lgpCondId6679ContactorNeutralFail OBJECT-IDENTITY Contactor Neutral Fail event. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6679 | current | ||
| lgpCondId6680CB1BreakerOpen OBJECT-IDENTITY CB1 Breaker open event. Normal state is breaker closed. Latched state is breaker open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6680 | current | ||
| lgpCondId6681CB2BreakerOpen OBJECT-IDENTITY CB2 Breaker open event. Normal state is breaker closed. Latched state is breaker open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6681 | current | ||
| lgpCondId6682CB4BreakerClosed OBJECT-IDENTITY CB4 breaker closed event. Normal state is breaker open. Latched state is breaker closed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6682 | current | ||
| lgpCondId6683CB5BreakerClosed OBJECT-IDENTITY CB5 breaker closed event. Normal state is breaker open. Latched state is breaker closed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6683 | current | ||
| lgpCondId6684CB3BreakerOpen OBJECT-IDENTITY CB3 breaker open event. Normal state is breaker closed. Latched state is breaker open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6684 | current | ||
| lgpCondId6685CB3ABreakerOpen OBJECT-IDENTITY CB3A breaker open event. Normal state is breaker closed. Latched state is breaker open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6685 | current | ||
| lgpCondId6686CB6BreakerOpen OBJECT-IDENTITY CB6 breaker open event. Normal state is breaker closed. Latched state is breaker open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6686 | current | ||
| lgpCondId6687CB7BreakerOpen OBJECT-IDENTITY CB7 breaker open event. Normal state is breaker closed. Latched state is breaker open. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6687 | current | ||
| lgpCondId6691GroupIndependentOn OBJECT-IDENTITY The group standby/cascade state for this unit has been overridden. The unit has been forced on. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6691 | current | ||
| lgpCondId6692GroupIndependentOff OBJECT-IDENTITY The group standby/cascade state for this unit has been overridden. The unit has been forced off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6692 | current | ||
| lgpCondId6693BranchResidualOverCurrent OBJECT-IDENTITY The system has detected a branch residual over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6693 | current | ||
| lgpCondId6694ReceptacleResidualOverCurrent OBJECT-IDENTITY The system has detected a receptacle residual over current condition. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6694 | current | ||
| lgpCondId6728BuckOn OBJECT-IDENTITY The input voltage is currently being bucked (lowered) by the inverter. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6728 | current | ||
| lgpCondId6729BoostOn OBJECT-IDENTITY The input voltage is currently being boosted (raised) by the inverter. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6729 | current | ||
| lgpCondId6739Compressor1HighPressure OBJECT-IDENTITY Compressor 1 High Pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6739 | current | ||
| lgpCondId6740Compressor2HighPressure OBJECT-IDENTITY Compressor 2 High Pressure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6740 | current | ||
| lgpCondId6741Compressor1ThermalOverload OBJECT-IDENTITY Compressor 1 Thermal Overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6741 | current | ||
| lgpCondId6742Compressor2ThermalOverload OBJECT-IDENTITY Compressor 2 Thermal Overload. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6742 | current | ||
| lgpCondId6758CompressorFreezeProtection OBJECT-IDENTITY Compressor has entered the freeze protection phase. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6758 | current | ||
| lgpCondId6773FanTemperatureCompensationLimitReached OBJECT-IDENTITY Unit is configured for fan temperature compensation, and the fan control set point cannot be reduced any further due to high remote air temperature sensor readings. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6773 | current | ||
| lgpCondId6774ModbusECFanCommunicationLost OBJECT-IDENTITY Communication with Modbus EC fan has been lost. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6774 | current | ||
| lgpCondId6785AnalogTemperatureControlIssue OBJECT-IDENTITY Analog input used for creating the control temperature (instead of reading a sensor) is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6785 | current | ||
| lgpCondId6786SubgroupFirmwareUpdateRequired OBJECT-IDENTITY Mismatch of subgroup firmware. Both the primary and secondary control boards must be running the same firmware version. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6786 | current | ||
| lgpCondId6787SubgroupSecondaryControlUnitIssue OBJECT-IDENTITY Subgroup secondary control unit is reporting an unspecified issue. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6787 | current | ||
| lgpCondId6788EEVCommunicationLost OBJECT-IDENTITY Communication with Electronic Expansion Valve unit has been lost. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6788 | current | ||
| lgpCondId6789EEVMotorIssue OBJECT-IDENTITY Electronic Expansion Valve stepper motor issue. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6789 | current | ||
| lgpCondId6790EEVFeedbackIssue OBJECT-IDENTITY Electronic Expansion Valve feedback error. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6790 | current | ||
| lgpCondId6791EEVPressureSensorIssue OBJECT-IDENTITY Electronic Expansion Valve refrigerant pressure sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6791 | current | ||
| lgpCondId6792EEVCoilTemperatureSensorIssue OBJECT-IDENTITY Electronic Expansion Valve coil temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6792 | current | ||
| lgpCondId6793EEVDischargeTemperatureSensorIssue OBJECT-IDENTITY Electronic Expansion Valve discharge temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6793 | current | ||
| lgpCondId6794EEVSumpTemperatureSensorIssue OBJECT-IDENTITY Electronic Expansion Valve sump temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6794 | current | ||
| lgpCondId6795EEVBatteryTestIssue OBJECT-IDENTITY Electronic Expansion Valve battery state cannot be determined. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6795 | current | ||
| lgpCondId6796EEVBatteryPersistentIssue OBJECT-IDENTITY Electronic Expansion Valve has continuously detected a 'bad' battery condition for an extended period of time. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6796 | current | ||
| lgpCondId6798PumpCycleLockOut OBJECT-IDENTITY Pump is locked out due to multiple pump-to-compressor transitions at cold ambient air temperature. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6798 | current | ||
| lgpCondId6799PumpBoardFirmwareUpdateRequired OBJECT-IDENTITY Mismatch of pump board firmware. All pump boards must be running the same firmware version. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6799 | current | ||
| lgpCondId6800PumpControlBoardIssue OBJECT-IDENTITY Pump is shut down due to a pump control board issue. Control board must be rebooted. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6800 | current | ||
| lgpCondId6801PumpInvalidDataShutdown OBJECT-IDENTITY Pump is shut down due to invalid data. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6801 | current | ||
| lgpCondId6802PumpInputPressureSensorIssue OBJECT-IDENTITY Pump input refrigerant pressure sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6802 | current | ||
| lgpCondId6803PumpInputTemperatureSensorIssue OBJECT-IDENTITY Pump input refrigerant temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6803 | current | ||
| lgpCondId6804PumpOutputPressureSensorIssue OBJECT-IDENTITY Pump output refrigerant pressure sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6804 | current | ||
| lgpCondId6805PumpOutputTemperatureSensorIssue OBJECT-IDENTITY Pump output refrigerant temperature sensor is disconnected or the signal is out of range. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6805 | current | ||
| lgpCondId6806PumpCommunicationLost OBJECT-IDENTITY Communication with pump unit has been lost. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6806 | current | ||
| lgpCondId6807PumpRemoteShutdown OBJECT-IDENTITY Pump is shut down by a remote signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6807 | current | ||
| lgpCondId6808PumpUSBEthernetPortIssue OBJECT-IDENTITY Pump control board USB or Ethernet interface has failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6808 | current | ||
| lgpCondId6809PumpStartupFailure OBJECT-IDENTITY Multiple attempts to start the pump have failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6809 | current | ||
| lgpCondId6810PumpInverterFailure OBJECT-IDENTITY Pump inverter is reporting a failure. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6810 | current | ||
| lgpCondId6811PumpTVSSIssue OBJECT-IDENTITY Pump Transient Voltage Surge Suppressor or Surge Protection Device has failed. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6811 | current | ||
| lgpCondId6812PumpHighSuperheat OBJECT-IDENTITY Pump inlet refrigerant superheat temperature is too high, or the pump has been running too long with the condenser fan off. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6812 | current | ||
| lgpCondId6813CondenserHighAmbientAirTempDelta OBJECT-IDENTITY The difference between condenser measured ambient air temperatures has been too large for an extended period of time. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6813 | current | ||
| lgpCondId6814CondenserLeeTempOptionMismatch OBJECT-IDENTITY Lee-Temp option configured at a condenser unit does not match Lee -Temp option configured at the control unit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6814 | current | ||
| lgpCondId6815CondenserBoardFirmwareUpdateRequired OBJECT-IDENTITY Mismatch of condenser board firmware. All condenser boards must be running the same firmware version. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6815 | current | ||
| lgpCondId6816CondenserToPumpHighRefrigerantTempDelta OBJECT-IDENTITY Temperature delta between the condenser output refrigerant and pump inlet refrigerant is too large. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6816 | current | ||
| lgpCondId6817CondenserRefrigerantTypeMismatch OBJECT-IDENTITY Refrigerant type configured at condenser unit does not match refrigerant type configured at the control unit. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6817 | current | ||
| lgpCondId6818ExternalSupplyFluidHighTemperature OBJECT-IDENTITY Supply fluid temperature has exceeded a threshold, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6818 | current | ||
| lgpCondId6819ExternalSupplyFluidTempSensorIssue OBJECT-IDENTITY Supply fluid temperature sensor is disconnected or the signal is out of range, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6819 | current | ||
| lgpCondId6822AuditLogUpdate OBJECT-IDENTITY Audit log has been updated. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6822 | current | ||
| lgpCondId6824ExternalSupplyFluidFlowIssue OBJECT-IDENTITY Supply fluid flow issue, as indicated by an external input signal. | 1.3.6.1.4.1.476.1.42.3.2.7.1.6824 | current |