MIBs Depot

LIEBERT-GP-NOTIFICATIONS-MIB

Registered at
1.3.6.1.4.1.476.1.42.1.4.1
1.3.6.1.4.1.476.1.42.3.3.0
1.3.6.1.4.1.476.1.42.3.3.10
Last updated
2008-07-02 00:00
Organization
Liebert Corporation
Revisions
2008-07-02 00:00, 2008-05-15 00:00, 2008-01-10 00:00, 2006-08-15 00:00, 2006-02-22 00:00
Namespace
liebert
Source file
LIEBERT-GP-NOTIFICATIONS-MIB
Digest
sha256:71d84167c25407f1104ccf7c6c6872908f506cd220aff8c8181b0f1ebfac69f3

Description

The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.

Contact

Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com Author: Craig S. Ward

Imports

FromSymbols
LIEBERT-GP-CONDITIONS-MIBlgpConditionDescr, lgpConditionId, lgpConditionTableRef, lgpConditionTableRowRef, lgpConditionTime
LIEBERT-GP-REGISTRATION-MIBlgpNotifications, liebertNotificationsModuleReg
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-MIBsysUpTime
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

LIEBERT-GP-CONDITIONS-MIB
LIEBERT-GP-NOTIFICATIONS-MIB
LIEBERT-GP-REGISTRATION-MIB
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
lgpEventNotifications
OBJECT-IDENTITY
Notifications for Liebert Global Products.
1.3.6.1.4.1.476.1.42.3.3.0current
lgpEventParameters
OBJECT-IDENTITY
This sub tree describes various parameters/data that are carried in the payload of some notifications.
1.3.6.1.4.1.476.1.42.3.3.10current
lgpEventParmTableRef
OBJECT-TYPE
This object will be included as a varbind in some lgpEventNotifications. It is a reference to a table object in the MIB. The value of this object will be the OID of a table that the object that the notification applies to is defined. The notification containing this object will also contain a varbind 'lgpEventParmTableRowRef' that will specify which instance (row) in the table the object is defined in. Example: NOTIFICATION: lgpEventConditionEntryAdded varbind: lgpConditionId 6 varbind: lgpConditionDescr lgpConditionRcpBranchBreakerOpen varbind: lgpConditionTime 393884848 varbind: lgpEventParmTableRef lgpPduRbTable varbind: lgpEventParmTableRowRef lgpPduRbEntryId.1.4 In the above example the breaker opened for a Receptacle branch. The specific receptacle branch is specified by the additional varbind (lgpEventParmTableRowRef). In this case the notification is for the 4th receptacle branch on the 1st PDU in the PDU cluster.
1.3.6.1.4.1.476.1.42.3.3.10.5OBJECT IDENTIFIERread-onlycurrent
lgpEventParmTableRowRef
OBJECT-TYPE
This is a reference to the intersection of a row and column (cell) in the table specified by the companion varbind (lgpEventParmTableRef) in this notification. The row in the table where this cell exists represents the object that this notification applies to. Example: NOTIFICATION: lgpEventRcpPowerStateChangeOff varbind: sysUpTime 393885975 varbind: lgpEventParmTableRef lgpPduRcpTable varbind: lgpEventParmTableRowRef lgpPduRcpEntryId.2.4.5 In the above example the power state changed for a Receptacle. The table containing the definition of the receptacle (lgpPduRcpTable) is given by the varbind (lgpEventParmTableRef) The specific receptacle is specified by the varbind (lgpEventParmTableRowRef). In this case the notification is for the 5th receptacle on the 4th receptacle branch on the 2nd PDU in the PDU cluster. If one wanted to retrieve the user assigned label for this receptacle the OID would be: lgpPduRcpEntryUsrLabel.2.4.5
1.3.6.1.4.1.476.1.42.3.3.10.6OBJECT IDENTIFIERread-onlycurrent

Notifications

NameOIDStatus
lgpEventConditionEntryAdded
NOTIFICATION-TYPE
This notification is sent each time a condition is inserted into the conditions table.
1.3.6.1.4.1.476.1.42.3.3.0.1current
lgpEventConditionEntryRemoved
NOTIFICATION-TYPE
This notification is sent each time a condition is removed from the conditions table.
1.3.6.1.4.1.476.1.42.3.3.0.2current
lgpEventLowBatteryWarning
NOTIFICATION-TYPE
The battery's remaining charge is less than or equal to the agent's configured low threshold 'lgpPwrConfigLowBatteryWarningTime'.
1.3.6.1.4.1.476.1.42.3.3.0.3current
lgpEventLoadTransferedToBypass
NOTIFICATION-TYPE
The device has transferred the load to the bypass source.
1.3.6.1.4.1.476.1.42.3.3.0.4current
lgpEventInternalFault
NOTIFICATION-TYPE
The device has reported an internal fault.
1.3.6.1.4.1.476.1.42.3.3.0.5current
lgpEventBatteryTestFailed
NOTIFICATION-TYPE
The device has reported a battery self-test failure.
1.3.6.1.4.1.476.1.42.3.3.0.6current
lgpEventOutputOverload
NOTIFICATION-TYPE
The device has reported an output overload condition.
1.3.6.1.4.1.476.1.42.3.3.0.7current
lgpEventEstablishedPowerRedundancy
NOTIFICATION-TYPE
The device has transitioned to the user defined redundant state.
1.3.6.1.4.1.476.1.42.3.3.0.8current
lgpEventLostPowerRedundancy
NOTIFICATION-TYPE
The device as transitioned to a non-redundant power state as defined by the user configured threshold.
1.3.6.1.4.1.476.1.42.3.3.0.9current
lgpEventPowerModuleFailure
NOTIFICATION-TYPE
Device power module failure.
1.3.6.1.4.1.476.1.42.3.3.0.10current
lgpEventBatteryModuleFailure
NOTIFICATION-TYPE
Device battery module failure.
1.3.6.1.4.1.476.1.42.3.3.0.11current
lgpEventControlModuleFailure
NOTIFICATION-TYPE
Device control module failure.
1.3.6.1.4.1.476.1.42.3.3.0.12current
lgpEventPowerModuleWarning
NOTIFICATION-TYPE
Device power module warning.
1.3.6.1.4.1.476.1.42.3.3.0.13current
lgpEventBatteryModuleWarning
NOTIFICATION-TYPE
Device battery module warning.
1.3.6.1.4.1.476.1.42.3.3.0.14current
lgpEventControlModuleWarning
NOTIFICATION-TYPE
Device control module warning.
1.3.6.1.4.1.476.1.42.3.3.0.15current
lgpEventAgentFirmwareUpdateSuccessful
NOTIFICATION-TYPE
The firmware update to the agent card has completed successfully. This element has been relocated to lgpAgentFirmwareUpdateSuccessful in the LIEBERT-GP-AGENT-MIB document.
1.3.6.1.4.1.476.1.42.3.3.0.16deprecated
lgpEventAgentFirmwareCorrupt
NOTIFICATION-TYPE
The firmware update to the agent card has failed and the firmware is now corrupt. This element has been relocated to lgpAgentFirmwareCorrupt in the LIEBERT-GP-AGENT-MIB document.
1.3.6.1.4.1.476.1.42.3.3.0.17deprecated
lgpEventConfigModified
NOTIFICATION-TYPE
Configuration for the referenced PDU has been modified.
1.3.6.1.4.1.476.1.42.3.3.0.18current
lgpEventModuleAdded
NOTIFICATION-TYPE
A hot-swappable module has been added to the object specified by the lgpEventParmTableRef and lgpEventParmTableRowRef.
1.3.6.1.4.1.476.1.42.3.3.0.19current
lgpEventModuleRemoved
NOTIFICATION-TYPE
A hot-swappable module has been removed from the object specified by the lgpEventParmTableRef and lgpEventParmTableRowRef.
1.3.6.1.4.1.476.1.42.3.3.0.20current
lgpEventRcpPowerStateChangeOn
NOTIFICATION-TYPE
Receptacle's power state has been changed from OFF to ON.
1.3.6.1.4.1.476.1.42.3.3.0.21current
lgpEventRcpPowerStateChangeOff
NOTIFICATION-TYPE
Receptacle's power state has been changed from ON to OFF.
1.3.6.1.4.1.476.1.42.3.3.0.22current
lgpEventRcpLoadAdded
NOTIFICATION-TYPE
The receptacle's load started drawing power. This notification is asserted when the receptacle power is ON and the associated load was previously not drawing power but is now drawing power. This event is not asserted as a result of turning the receptacle power ON.
1.3.6.1.4.1.476.1.42.3.3.0.23current
lgpEventRcpLoadRemoved
NOTIFICATION-TYPE
The receptacle's load stopped drawing power. This notification is asserted when the receptacle power is ON and the associated load was previously drawing power but is now no longer drawing power. This event is not asserted as a result of turning the receptacle power OFF.
1.3.6.1.4.1.476.1.42.3.3.0.24current