XUPS-MIB
- Registered at
- 1.3.6.1.4.1.534.1
- Last updated
- 2019-09-27 00:00
- Organization
- Eaton Corporation
- Revisions
- 2019-09-27 00:00, 2019-09-12 00:00, 2019-09-10 00:00, 2019-04-12 00:00, 2019-03-05 00:00, 2019-02-19 00:00, 2018-09-12 00:00, 2018-04-23 00:00, 2012-11-26 15:13, 2012-04-03 00:00, 2011-02-25 00:00, 2008-10-02 00:00, 2007-05-03 00:00, 2007-03-13 00:00
- Namespace
- eaton
- Source file
XUPS-MIB- Digest
sha256:e65256d748c7e13712c7ab1f3e0b71974de56b2e2382eca136323175ec30298b
Description
Defines Eaton's proprietary PowerMIB for UPS and related device data. Copyright (C) Exide Electronics 1992-98 Copyright (C) Powerware Corporation 1999-2004 Copyright (C) Eaton Corporation (2005-).
Contact
Eaton Power Quality Technical Support (PQTS) group www.eaton.com/powerxpert Technical Resource Center phone numbers United States: 1.800.843.9433 or 919.870.3028 Canada: 1.800.461.9166 ext. 260 All other countries: Call your local service representative.
Imports
| From | Symbols |
|---|---|
| EATON-EMP-MIB | xupsContactDescr, xupsContactIndex, xupsContactState, xupsContactType, xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit, xupsEnvRemoteHumidityUpperLimit, xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit, xupsEnvRemoteTempUpperLimit |
| EATON-OIDS | eaton, xupsEnvironment |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-MIB | sysName |
| SNMPv2-SMI | Counter32, Gauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
EATON-EMP-MIB EATON-OIDS SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC XUPS-MIB
Under this module's arcs
Where the registration tree carries on below this module.
| Arc | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.534.1.6 | xupsEnvironment |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| xupsIdent OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.1 | |||
| xupsIdentManufacturer OBJECT-TYPE The UPS Manufacturer Name (e.g. Eaton Corporation). | 1.3.6.1.4.1.534.1.1.1 | DisplayString (SIZE(0..31)) | read-only | current |
| xupsIdentModel OBJECT-TYPE The UPS Model (e.g. Powerware Plus Model 18). | 1.3.6.1.4.1.534.1.1.2 | DisplayString (SIZE(0..63)) | read-only | current |
| xupsIdentSoftwareVersion OBJECT-TYPE The firmware revision level(s) of the UPS microcontroller(s). | 1.3.6.1.4.1.534.1.1.3 | DisplayString (SIZE(0..63)) | read-only | current |
| xupsIdentOemCode OBJECT-TYPE A binary code indicating who the UPS was manufactured or labeled for. 0 or 255 indicates Eaton itself. | 1.3.6.1.4.1.534.1.1.4 | Integer32 (0..255) | read-only | current |
| xupsIdentPartNumber OBJECT-TYPE The catalog part number of the UPS device. | 1.3.6.1.4.1.534.1.1.5 | OCTET STRING (SIZE(1..31)) | read-only | current |
| xupsIdentSerialNumber OBJECT-TYPE The serial number of the UPS device. | 1.3.6.1.4.1.534.1.1.6 | OCTET STRING (SIZE(1..31)) | read-only | current |
| xupsBattery OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.2 | |||
| xupsBatTimeRemaining OBJECT-TYPE Battery run time in seconds before UPS turns off due to low battery. | 1.3.6.1.4.1.534.1.2.1 | Integer32 (0..2147483647) | read-only | current |
| xupsBatVoltage OBJECT-TYPE Battery voltage as reported by the UPS meters. | 1.3.6.1.4.1.534.1.2.2 | Integer32 (0..2147483647) | read-only | current |
| xupsBatCurrent OBJECT-TYPE Battery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery. | 1.3.6.1.4.1.534.1.2.3 | Integer32 (-2147483648..2147483647) | read-only | current |
| xupsBatCapacity OBJECT-TYPE Battery percent charge. | 1.3.6.1.4.1.534.1.2.4 | Integer32 (0..100) | read-only | current |
| xupsBatteryAbmStatus OBJECT-TYPE Gives the status of the Advanced Battery Management and Battery state; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage; batteryResting(4) is the state when the battery is fully charged and none of the other actions (charging/discharging/floating) is being done. checkBattery(8) indicates that the Battery state is uncertain following a poor battery test result. | 1.3.6.1.4.1.534.1.2.5 | INTEGER {batteryCharging(1), batteryDischarging(2), batteryFloating(3), batteryResting(4), unknown(5), batteryDisconnected(6), batteryUnderTest(7), checkBattery(8)} | read-only | current |
| xupsBatteryLastReplacedDate OBJECT-TYPE The date when the Batteries in this UPS were last replaced. Free text format, so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc). | 1.3.6.1.4.1.534.1.2.6 | DisplayString (SIZE(0..16)) | read-only | current |
| xupsBatteryFailure OBJECT-TYPE Indicates if a battery fault detected or battery tests failed. | 1.3.6.1.4.1.534.1.2.7 | INTEGER {yes(1), no(2)} | read-only | current |
| xupsBatteryNotPresent OBJECT-TYPE Indicates if the UPS has no battery either internal or external. | 1.3.6.1.4.1.534.1.2.8 | INTEGER {yes(1), no(2)} | read-only | current |
| xupsBatteryAged OBJECT-TYPE Indicates if the battery is over aged. | 1.3.6.1.4.1.534.1.2.9 | INTEGER {yes(1), no(2)} | read-only | current |
| xupsBatteryLowCapacity OBJECT-TYPE Indicates if the battery capacity is below the threshold set in the UPS. | 1.3.6.1.4.1.534.1.2.10 | INTEGER {yes(1), no(2)} | read-only | current |
| xupsInput OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.3 | |||
| xupsInputFrequency OBJECT-TYPE The utility line frequency in tenths of Hz. | 1.3.6.1.4.1.534.1.3.1 | Integer32 (0..2147483647) | read-only | current |
| xupsInputLineBads OBJECT-TYPE The number of times the Input was out of tolerance in voltage or frequency. | 1.3.6.1.4.1.534.1.3.2 | Counter32 | read-only | current |
| xupsInputNumPhases OBJECT-TYPE The number of input phases (normally 1 to 3). | 1.3.6.1.4.1.534.1.3.3 | Integer32 (0..6) | read-only | current |
| xupsInputTable OBJECT-TYPE A list of input table entries. The number of entries is given by the value of xupsInputNumPhases. | 1.3.6.1.4.1.534.1.3.4 | not-accessible | current | |
| xupsInputEntry OBJECT-TYPE The input table entry containing the current, voltage, etc. readings for one phase. | 1.3.6.1.4.1.534.1.3.4.1 | not-accessible | current | |
| xupsInputPhase OBJECT-TYPE The number of the phase. Serves as index for input table. | 1.3.6.1.4.1.534.1.3.4.1.1 | Integer32 (0..6) | read-only | current |
| xupsInputVoltage OBJECT-TYPE The measured input voltage from the UPS meters in volts. | 1.3.6.1.4.1.534.1.3.4.1.2 | Integer32 (0..2147483647) | read-only | current |
| xupsInputCurrent OBJECT-TYPE The measured input current from the UPS meters in amps. | 1.3.6.1.4.1.534.1.3.4.1.3 | Integer32 (0..2147483647) | read-only | current |
| xupsInputWatts OBJECT-TYPE The measured input real power in watts. | 1.3.6.1.4.1.534.1.3.4.1.4 | Integer32 (0..2147483647) | read-only | current |
| xupsInputId OBJECT-TYPE value indicates what measurement is being stored in this table row : phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1. | 1.3.6.1.4.1.534.1.3.4.1.5 | INTEGER {phase1toN(1), phase2toN(2), phase3toN(3), phase1to2(4), phase2to3(5), phase3to1(6)} | read-only | current |
| xupsInputName OBJECT-TYPE A descriptive name for the phase, example : L1/A for the phase 1. | 1.3.6.1.4.1.534.1.3.4.1.6 | OCTET STRING (SIZE(1..31)) | read-only | current |
| xupsInputCurrentHighPrecision OBJECT-TYPE The measured input current from the UPS meters in tenth of amps. | 1.3.6.1.4.1.534.1.3.4.1.7 | Integer32 (0..2147483647) | read-only | current |
| xupsInputSource OBJECT-TYPE The present external source of input power. The enumeration 'none(2)' indicates that there is no external source of power, for example, the UPS is On Battery (an internal source). 'primaryUtility' indicates the normal case of utility input power. The 'bypassFeed' can only be used when the Bypass source is known to be a separate utility feed than the primaryUtility(3). 'secondaryUtility' indicates that a secondary utility feed is supplying power (on a dual AC input UPS). 'generator' indicates that input power is provided by a generator. Note that the alternate energy sources of 'flywheel' and 'fuelcell' are not necessarily AC input sources. | 1.3.6.1.4.1.534.1.3.5 | INTEGER {other(1), none(2), primaryUtility(3), bypassFeed(4), secondaryUtility(5), generator(6), flywheel(7), fuelcell(8)} | read-only | current |
| xupsDualInputStatus OBJECT-TYPE The present status of the sources of input power in a dual source UPS. The enumeration primarySourceGood(2) indicates that the primary source of power is present and within 'normal' ranges for voltage and frequency, but the secondary source is either not present or not in an acceptable range. 'secondarySourceGood' indicates that only the Secondary power feed is available and within its limits. The enumeration bothSourcesGood(4) indicates that both sources are present and within their respective 'normal' ranges; bothSourcesBad(1) indicates that neither source is present, or, if present, is not within acceptable ranges. This object will only be implemented for UPSs with two sources of input power, e.g., redundant AC feeds or a separate Bypass or Generator source. The secondary source will not be an AC power source in all cases. | 1.3.6.1.4.1.534.1.3.6 | INTEGER {bothSourcesBad(1), primarySourceGood(2), secondarySourceGood(3), bothSourcesGood(4)} | read-only | current |
| xupsSecondaryInputWatch OBJECT-TYPE This object enables(2) or disables(1) the alarms and traps related to the availability and use of the secondary input of a dual-input UPS (i.e., OnAlternatePowerSource and AltPowerNotAvailable). To avoid nuisance alarms and traps, this object should be set to disabled(1) when the UPS is not wired to a secondary source of power. This object will only be implemented for UPSs with two sources of input power, i.e., redundant AC feeds or a separate Bypass or Generator source. | 1.3.6.1.4.1.534.1.3.7 | INTEGER {disabled(1), enabled(2)} | read-write | current |
| xupsInputTotal OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.3.8 | |||
| xupsInputAverageVoltage OBJECT-TYPE The measured input voltage from the UPS meters in volts. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase voltage. | 1.3.6.1.4.1.534.1.3.8.1 | Integer32 (0..2147483647) | read-only | current |
| xupsInputTotalCurrent OBJECT-TYPE The measured input current from the UPS meters in tenth of amps. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase current. | 1.3.6.1.4.1.534.1.3.8.2 | Integer32 (0..2147483647) | read-only | current |
| xupsInputTotalWatts OBJECT-TYPE The measured input active power in watts. Sum of all the simple phase watts. | 1.3.6.1.4.1.534.1.3.8.3 | Integer32 (0..2147483647) | read-only | current |
| xupsInputTotalVA OBJECT-TYPE The measured input apparent power in VA. Sum of all the simple phase VA. | 1.3.6.1.4.1.534.1.3.8.4 | Integer32 (0..2147483647) | read-only | current |
| xupsInputAveragePowerFactor OBJECT-TYPE Indicates the total power factor of the input in hundredths. 0.92 would be returned as 92. | 1.3.6.1.4.1.534.1.3.8.5 | Integer32 | read-only | current |
| xupsInputStatus OBJECT-TYPE The present status of the primary AC input of the UPS. The enumeration inputGood(2) indicates that the primary source of power is present and within 'normal' ranges for voltage and frequency. inputBad(1) indicates that neither source is present, or, if present, is not within acceptable ranges. | 1.3.6.1.4.1.534.1.3.9 | INTEGER {inputBad(1), inputGood(2)} | read-only | current |
| xupsOutput OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.4 | |||
| xupsOutputLoad OBJECT-TYPE The UPS output load in percent of rated capacity. | 1.3.6.1.4.1.534.1.4.1 | Integer32 (0..200) | read-only | current |
| xupsOutputFrequency OBJECT-TYPE The measured UPS output frequency in tenths of Hz. | 1.3.6.1.4.1.534.1.4.2 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputNumPhases OBJECT-TYPE The number of metered output phases. | 1.3.6.1.4.1.534.1.4.3 | Integer32 (0..6) | read-only | current |
| xupsOutputTable OBJECT-TYPE A list of output table entries. The number of entries is given by the value of xupsOutputNumPhases. | 1.3.6.1.4.1.534.1.4.4 | not-accessible | current | |
| xupsOutputEntry OBJECT-TYPE Output Table Entry containing voltage, current, etc. | 1.3.6.1.4.1.534.1.4.4.1 | not-accessible | current | |
| xupsOutputPhase OBJECT-TYPE The number of the phase. Serves as index for output table. | 1.3.6.1.4.1.534.1.4.4.1.1 | Integer32 (0..6) | read-only | current |
| xupsOutputVoltage OBJECT-TYPE The measured output voltage from the UPS metering in volts. | 1.3.6.1.4.1.534.1.4.4.1.2 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputCurrent OBJECT-TYPE The measured UPS output current in amps. | 1.3.6.1.4.1.534.1.4.4.1.3 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputWatts OBJECT-TYPE The measured real output power in watts. | 1.3.6.1.4.1.534.1.4.4.1.4 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputId OBJECT-TYPE value indicates what measurement is being stored in this table row : phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1. | 1.3.6.1.4.1.534.1.4.4.1.5 | INTEGER {phase1toN(1), phase2toN(2), phase3toN(3), phase1to2(4), phase2to3(5), phase3to1(6)} | read-only | current |
| xupsOutputName OBJECT-TYPE A descriptive name for the phase. | 1.3.6.1.4.1.534.1.4.4.1.6 | OCTET STRING (SIZE(1..31)) | read-only | current |
| xupsOutputCurrentHighPrecision OBJECT-TYPE The measured output current from the UPS meters in tenth of amps. | 1.3.6.1.4.1.534.1.4.4.1.7 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputPercentLoad OBJECT-TYPE The percentage of the UPS power capacity presently being used on this output line | 1.3.6.1.4.1.534.1.4.4.1.8 | Integer32 (0..200) | read-only | current |
| xupsOutputVA OBJECT-TYPE The measured apparent output power in VA. | 1.3.6.1.4.1.534.1.4.4.1.9 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputSource OBJECT-TYPE The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. 'normal', 'bypass', and 'battery' indicate those common UPS statuses. 'booster' and 'reducer' indicate boost or buck operation, for line-interactive UPSs only. 'parallelCapacity' and 'parallelRedundant' indicate a normal parallel UPS system, in either Parallel for Capacity or Redundancy configuration. 'highEfficiencyMode' is normal but enhanced by High Efficiency mode. 'maintenanceBypass' indicates that the UPS is in Maintenance/Manual Bypass mode. 'essMode' is normal but enhanced by Energy Saver System. 'other' covers any other, unusual conditions. | 1.3.6.1.4.1.534.1.4.5 | INTEGER {other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7), parallelCapacity(8), parallelRedundant(9), highEfficiencyMode(10), maintenanceBypass(11), essMode(12)} | read-only | current |
| xupsOutputHourlyPowerUsage OBJECT-TYPE Units are Watt-hours.This is the energy consumed during the last hour. | 1.3.6.1.4.1.534.1.4.6 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputCumulativePowerUsage OBJECT-TYPE Units are Watt-hours.This is the energy consumed since the last reset. This object is writable so that it can be reset to 0. When it is written to 0, the xupsOutputCumulativeWhTimer will be reset to 0 as well. | 1.3.6.1.4.1.534.1.4.7 | Integer32 (0..2147483647) | read-write | current |
| xupsOutputCumulativePowerUsageTimer OBJECT-TYPE Time in seconds since the cumulative power usage was last reset. | 1.3.6.1.4.1.534.1.4.8 | Counter32 | read-only | current |
| xupsOutputTotal OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.4.9 | |||
| xupsOutputAverageVoltage OBJECT-TYPE The measured output voltage from the UPS meters in volts. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase voltage. | 1.3.6.1.4.1.534.1.4.9.1 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputTotalCurrent OBJECT-TYPE The measured output current from the UPS meters in tenth of amps. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase current. | 1.3.6.1.4.1.534.1.4.9.2 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputTotalWatts OBJECT-TYPE The measured output active power in watts. Sum of all the simple phase watts. | 1.3.6.1.4.1.534.1.4.9.3 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputTotalVA OBJECT-TYPE The measured output apparent power in VA. Sum of all the simple phase VA. | 1.3.6.1.4.1.534.1.4.9.4 | Integer32 (0..2147483647) | read-only | current |
| xupsOutputAveragePowerFactor OBJECT-TYPE Indicates the total power factor of the output in hundredths. 0.92 would be returned as 92. | 1.3.6.1.4.1.534.1.4.9.5 | Integer32 | read-only | current |
| xupsOutputStatus OBJECT-TYPE The present status of the AC output of the UPS. The enumeration outputNotPowered(1) indicates that the output is not powered. outputNotProtected(2) indicates that the output is powered but not protected, due to following reasons : On bypass, battery fault, or UPS internal failure that makes the ups will be inoperant in case of AC input failure. outputProtected(3) indicates that the output is powered and protected. | 1.3.6.1.4.1.534.1.4.10 | INTEGER {outputNotPowered(1), outputNotProtected(2), outputProtected(3)} | read-only | current |
| xupsBypass OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.5 | |||
| xupsBypassFrequency OBJECT-TYPE The bypass frequency in tenths of Hz. | 1.3.6.1.4.1.534.1.5.1 | Integer32 (0..2147483647) | read-only | current |
| xupsBypassNumPhases OBJECT-TYPE The number of lines in the UPS bypass table. | 1.3.6.1.4.1.534.1.5.2 | Integer32 (0..6) | read-only | current |
| xupsBypassTable OBJECT-TYPE A list of bypass table entries. The number of entries is given by the value of xupsBypassNumPhases. | 1.3.6.1.4.1.534.1.5.3 | not-accessible | current | |
| xupsBypassEntry OBJECT-TYPE Bypass Table Entry containing voltage for each phase. | 1.3.6.1.4.1.534.1.5.3.1 | not-accessible | current | |
| xupsBypassPhase OBJECT-TYPE The Bypass Phase, index for the table. | 1.3.6.1.4.1.534.1.5.3.1.1 | Integer32 (0..6) | read-only | current |
| xupsBypassVoltage OBJECT-TYPE The measured UPS bypass voltage in volts. | 1.3.6.1.4.1.534.1.5.3.1.2 | Integer32 (0..2147483647) | read-only | current |
| xupsBypassId OBJECT-TYPE value indicates what measurement is being stored in this table row : phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1. | 1.3.6.1.4.1.534.1.5.3.1.3 | INTEGER {phase1toN(1), phase2toN(2), phase3toN(3), phase1to2(4), phase2to3(5), phase3to1(6)} | read-only | current |
| xupsBypassName OBJECT-TYPE A descriptive name for the phase. | 1.3.6.1.4.1.534.1.5.3.1.4 | OCTET STRING (SIZE(1..31)) | read-only | current |
| xupsBypassCurrentHighPrecision OBJECT-TYPE The measured bypass current from the UPS meters in tenth of amps. | 1.3.6.1.4.1.534.1.5.3.1.5 | Integer32 (0..2147483647) | read-only | current |
| xupsBypassWatts OBJECT-TYPE The measured real bypass power in watts. | 1.3.6.1.4.1.534.1.5.3.1.6 | Integer32 (0..2147483647) | read-only | current |
| xupsBypassTotal OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.5.4 | |||
| xupsBypassAverageVoltage OBJECT-TYPE The measured bypass voltage from the UPS meters in volts. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase voltage. | 1.3.6.1.4.1.534.1.5.4.1 | Integer32 (0..2147483647) | read-only | current |
| xupsBypassTotalCurrent OBJECT-TYPE The measured bypass current from the UPS meters in tenth of amps. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase current. | 1.3.6.1.4.1.534.1.5.4.2 | Integer32 (0..2147483647) | read-only | current |
| xupsBypassTotalWatts OBJECT-TYPE The measured bypass active power in watts. Sum of all the simple phase watts. | 1.3.6.1.4.1.534.1.5.4.3 | Integer32 (0..2147483647) | read-only | current |
| xupsBypassTotalVA OBJECT-TYPE The measured output apparent power in VA. Sum of all the simple phase VA. | 1.3.6.1.4.1.534.1.5.4.4 | Integer32 (0..2147483647) | read-only | current |
| xupsBypassAveragePowerFactor OBJECT-TYPE Indicates the total power factor of the input in hundredths. 0.92 would be returned as 92. | 1.3.6.1.4.1.534.1.5.4.5 | Integer32 | read-only | current |
| xupsEnvAmbientTemp OBJECT-TYPE The reading of the ambient temperature in the vicinity of the UPS or SNMP agent. | 1.3.6.1.4.1.534.1.6.1 | Integer32 (-100..200) | read-only | current |
| xupsEnvAmbientLowerLimit OBJECT-TYPE The Lower Limit of the ambient temperature; if xupsEnvAmbientTemp falls below this value, the xupsAmbientTempBad alarm will occur. | 1.3.6.1.4.1.534.1.6.2 | Integer32 (-100..200) | read-write | current |
| xupsEnvAmbientUpperLimit OBJECT-TYPE The Upper Limit of the ambient temperature; if xupsEnvAmbientTemp rises above this value, the xupsAmbientTempBad alarm will occur. This value should be greater than xupsEnvAmbientLowerLimit. | 1.3.6.1.4.1.534.1.6.3 | Integer32 (-100..200) | read-write | current |
| xupsEnvAmbientHumidity OBJECT-TYPE The reading of the ambient humidity in the vicinity of the UPS or SNMP agent. | 1.3.6.1.4.1.534.1.6.4 | Integer32 (0..100) | read-only | current |
| xupsAlarm OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7 | |||
| xupsAlarms OBJECT-TYPE The current number of alarm conditions. | 1.3.6.1.4.1.534.1.7.1 | Gauge32 | read-only | current |
| xupsAlarmTable OBJECT-TYPE A list of alarm table entries. The number of entries is given by the value of xupsAlarms. Note that this table is sparsely (non-consecutively) numbered and will be empty if there are no active alarms. | 1.3.6.1.4.1.534.1.7.2 | not-accessible | current | |
| xupsAlarmEntry OBJECT-TYPE Alarm Table Entry containing descriptive information for one alarm entry. | 1.3.6.1.4.1.534.1.7.2.1 | not-accessible | current | |
| xupsAlarmID OBJECT-TYPE A unique identifier for an alarm condition. | 1.3.6.1.4.1.534.1.7.2.1.1 | Integer32 (1..2147483647) | read-only | current |
| xupsAlarmDescr OBJECT-TYPE A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. | 1.3.6.1.4.1.534.1.7.2.1.2 | OBJECT IDENTIFIER | read-only | current |
| xupsAlarmTime OBJECT-TYPE The value of the MIB-II variable sysUpTime when the alarm condition occurred. | 1.3.6.1.4.1.534.1.7.2.1.3 | TimeTicks | read-only | current |
| xupsOnBattery OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.3 | |||
| xupsLowBattery OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.4 | |||
| xupsUtilityPowerRestored OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.5 | |||
| xupsReturnFromLowBattery OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.6 | |||
| xupsOutputOverload OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.7 | |||
| xupsInternalFailure OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.8 | |||
| xupsBatteryDischarged OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.9 | |||
| xupsInverterFailure OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.10 | |||
| xupsOnBypass OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.11 | |||
| xupsBypassNotAvailable OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.12 | |||
| xupsOutputOff OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.13 | |||
| xupsInputFailure OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.14 | |||
| xupsBuildingAlarm OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.15 | |||
| xupsShutdownImminent OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.16 | |||
| xupsOnInverter OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.17 | |||
| xupsAlarmNumEvents OBJECT-TYPE The number of entries in the UPS event history queue. | 1.3.6.1.4.1.534.1.7.18 | Gauge32 | read-only | current |
| xupsAlarmEventTable OBJECT-TYPE A table of the UPS internal event history queue. | 1.3.6.1.4.1.534.1.7.19 | not-accessible | current | |
| xupsAlarmEventEntry OBJECT-TYPE One of the entries in the UPS event history queue. | 1.3.6.1.4.1.534.1.7.19.1 | not-accessible | current | |
| xupsAlarmEventID OBJECT-TYPE A unique number that reflects the order in which the event occurred. The oldest event in the queue will be number 1. Subsequent events will be numbered 2, 3, 4, etc. | 1.3.6.1.4.1.534.1.7.19.1.1 | Integer32 (1..400) | not-accessible | current |
| xupsAlarmEventDateAndTime OBJECT-TYPE The time and date that an event occurred as recorded in the UPS internal event queue. This string will reflect the time and date as set in the UPS itself and will not be referenced to sysUpTime. The format is MM/DD/YYYY:HH:MM:SS. Time is 24 hour standard. | 1.3.6.1.4.1.534.1.7.19.1.2 | DisplayString (SIZE(0..22)) | read-only | deprecated |
| xupsAlarmEventKind OBJECT-TYPE Enumerated value that tells whether the event is an occurrence of an alarm condition or a clearing of an alarm condition. | 1.3.6.1.4.1.534.1.7.19.1.3 | INTEGER {occurred(1), cleared(2), unknown(3)} | read-only | deprecated |
| xupsAlarmEventDescr OBJECT-TYPE A description of the event stored in the UPS event queue. This description will be a sixteen bit integer value representing one of the defined alarms in the Powerware Binary Computer Mode communication specification; for example, a value of 0 represents the 'Inverter AC Over Voltage' alarm (byte 1, bit 0 in the BCM Alarm Map). | 1.3.6.1.4.1.534.1.7.19.1.4 | Integer32 (0..2147483647) | read-only | deprecated |
| xupsAlarmEventMsg OBJECT-TYPE A text string describing each entry in the Event Log. The format of this text message is free (not fixed) for the operator to read; good contents would be a time & date stamp, the event type, and a description of the event. | 1.3.6.1.4.1.534.1.7.19.1.5 | DisplayString (SIZE(0..80)) | read-only | current |
| xupsBreakerOpen OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.20 | |||
| xupsAlarmEntryAdded OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.21 | |||
| xupsAlarmEntryRemoved OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.22 | |||
| xupsAlarmBatteryBad OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.23 | |||
| xupsOutputOffAsRequested OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.24 | |||
| xupsDiagnosticTestFailed OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.25 | |||
| xupsCommunicationsLost OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.26 | |||
| xupsUpsShutdownPending OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.27 | |||
| xupsAlarmTestInProgress OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.28 | |||
| xupsAmbientTempBad OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.29 | |||
| xupsLossOfRedundancy OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.30 | |||
| xupsAlarmTempBad OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.31 | |||
| xupsAlarmChargerFailed OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.32 | |||
| xupsAlarmFanFailure OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.33 | |||
| xupsAlarmFuseFailure OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.34 | |||
| xupsPowerSwitchBad OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.35 | |||
| xupsModuleFailure OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.36 | |||
| xupsOnAlternatePowerSource OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.37 | |||
| xupsAltPowerNotAvailable OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.38 | |||
| xupsNoticeCondition OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.39 | |||
| xupsRemoteTempBad OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.40 | |||
| xupsRemoteHumidityBad OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.41 | |||
| xupsAlarmOutputBad OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.42 | |||
| xupsAlarmAwaitingPower OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.43 | |||
| xupsOnMaintenanceBypass OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.44 | |||
| xupsOutputNotProtected OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.7.51 | |||
| xupsTest OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.8 | |||
| xupsTestStart OBJECT-TYPE Setting this object initiates the requested Test. The test types which a UPS might support are 'testBattery', 'testSystem' (a UPS General Systems test, however defined by the UPS), 'testSecondarySource' (test if the Secondary power source is good on a dual input UPS), and 'flashLightsTest' (start a test which flashes the UPS lights, and if available, sounds the horn to help locate the UPS). If a UPS does not support the requested test, the set operation may succeed but the xupsTestBatteryStatus will end up as notSupported. When read, this object indicates the last test requested via this object, if any; 'noTestStarted' could be the initial value. Currently only the 'flashLightsTest' can be canceled with 'cancelTest'. | 1.3.6.1.4.1.534.1.8.1 | INTEGER {testBattery(1), noTestStarted(2), testSystem(3), testSecondarySource(4), flashLightsTest(5), cancelTest(6)} | read-write | current |
| xupsTestBatteryStatus OBJECT-TYPE Reading this enumerated value gives an indication of the (last) UPS Battery test status. 'inhibited' means that the battery test could not be run. 'scheduled' means that the battery test could not be run at the time of request, but will be run at some later (UPS-determined) time. | 1.3.6.1.4.1.534.1.8.2 | INTEGER {unknown(1), passed(2), failed(3), inProgress(4), notSupported(5), inhibited(6), scheduled(7)} | read-only | current |
| xupsLastGeneralTest OBJECT-TYPE Indicates the last UPS test requested via xupsTestStart or by other non-SNMP means, other than for the testBattery (1) case. The results of the test indicated by this object are reported in xupsLastGeneralTestResult. | 1.3.6.1.4.1.534.1.8.3 | INTEGER {noTestStarted(2), testSystem(3), testSecondarySource(4), flashLightsTest(5)} | read-only | current |
| xupsLastGeneralTestResult OBJECT-TYPE Reading this enumerated value gives the result of the test indicated in xupsLastGeneralTest. | 1.3.6.1.4.1.534.1.8.4 | INTEGER {unknown(1), passed(2), failed(3), inProgress(4), notSupported(5), inhibited(6), scheduled(7)} | read-only | current |
| xupsTestTrap OBJECT-TYPE Setting startTestTrap to 1 will initiate a test trap to be sent out from the agent. All other set values are invalid. | 1.3.6.1.4.1.534.1.8.5 | INTEGER {startTestTrap(1)} | read-write | current |
| xupsControl OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.9 | |||
| xupsControlOutputOffDelay OBJECT-TYPE Setting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pending shutdown. | 1.3.6.1.4.1.534.1.9.1 | Integer32 (0..2147483647) | read-write | current |
| xupsControlOutputOnDelay OBJECT-TYPE Setting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pending startup. | 1.3.6.1.4.1.534.1.9.2 | Integer32 (0..2147483647) | read-write | current |
| xupsControlOutputOffTrapDelay OBJECT-TYPE When xupsControlOutputOffDelay reaches this value, a trap will be sent. | 1.3.6.1.4.1.534.1.9.3 | Integer32 (0..2147483647) | read-write | current |
| xupsControlOutputOnTrapDelay OBJECT-TYPE When xupsControlOutputOnDelay reaches this value, a xupsOutputOff trap will be sent. | 1.3.6.1.4.1.534.1.9.4 | Integer32 (0..2147483647) | read-write | deprecated |
| xupsControlToBypassDelay OBJECT-TYPE Setting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the UPS to not supply power to the load. Setting it to 0 will cause an attempt to abort a pending shutdown. | 1.3.6.1.4.1.534.1.9.5 | Integer32 (0..2147483647) | read-write | current |
| xupsLoadShedSecsWithRestart OBJECT-TYPE Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsControlOutputOffDelay, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted. This is the preferred Control object to use when performing an On Battery OS Shutdown. | 1.3.6.1.4.1.534.1.9.6 | Integer32 (0..2147483647) | read-write | current |
| xupsSwitchable OBJECT-TYPE Parameter which indicates whether UPS commands received via any communication path (aside from manual controls) are able (switchable) or not able (notSwitchable) to control the UPS. | 1.3.6.1.4.1.534.1.9.7 | INTEGER {switchable(1), notSwitchable(2)} | read-only | current |
| xupsConfig OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.10 | |||
| xupsConfigOutputVoltage OBJECT-TYPE The nominal UPS Output voltage per phase in volts. | 1.3.6.1.4.1.534.1.10.1 | Integer32 (0..2147483647) | read-only | current |
| xupsConfigInputVoltage OBJECT-TYPE The nominal UPS Input voltage per phase in volts. | 1.3.6.1.4.1.534.1.10.2 | Integer32 (0..2147483647) | read-only | current |
| xupsConfigOutputWatts OBJECT-TYPE The nominal UPS available real power output in watts. | 1.3.6.1.4.1.534.1.10.3 | Integer32 (0..2147483647) | read-only | current |
| xupsConfigOutputFreq OBJECT-TYPE The nominal output frequency in tenths of Hz. | 1.3.6.1.4.1.534.1.10.4 | Integer32 (0..2147483647) | read-only | current |
| xupsConfigDateAndTime OBJECT-TYPE Date and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS time and date. This value is not referenced to sysUpTime. It is simply the clock value from the UPS real time clock. Format is as follows: MM/DD/YYYY:HH:MM:SS. | 1.3.6.1.4.1.534.1.10.5 | DisplayString (SIZE(0..22)) | read-write | current |
| xupsConfigLowOutputVoltageLimit OBJECT-TYPE The Lower limit for acceptable Output Voltage, per the UPS specifications. | 1.3.6.1.4.1.534.1.10.6 | Integer32 (0..2147483647) | read-only | current |
| xupsConfigHighOutputVoltageLimit OBJECT-TYPE The Upper limit for acceptable Output Voltage, per the UPS specifications. | 1.3.6.1.4.1.534.1.10.7 | Integer32 (0..2147483647) | read-only | current |
| xupsConfigInstallDate OBJECT-TYPE The date when this UPS was installed. Free text format, so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc). | 1.3.6.1.4.1.534.1.10.8 | DisplayString (SIZE(0..16)) | read-write | current |
| xupsTrapControl OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.11 | |||
| xupsMaxTrapLevel OBJECT-TYPE The level of severity of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. Values are: (1) none: no traps will be sent to this host; (2) critical: only traps for Critical alarm conditions will be sent to this host; (3) major: Critical and Major traps will be sent; (4) minor: All levels of alarming traps will be sent: Critical, Major, and Minor (This level was added in PowerMIB v3.11) (5) allTraps: all Traps will be sent to this host (Critical, Major, Minor, Informational). | 1.3.6.1.4.1.534.1.11.1 | INTEGER {none(1), critical(2), major(3), minor(4), allTraps(5)} | read-write | current |
| xupsSendTrapType OBJECT-TYPE The type of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. The additional variables in types (3) and (4) are useful for determining which UPS is the source on multi-port network adapters, and for getting additional descriptive information. Types (1) through (4) are all SNMP version 1 trap PDUs. Values are: (1) stnd: Traps as defined in the Standard UPS MIB (RFC1628) and Generic (MIB II) traps as defined in RFC 1215. (2) xups: xupsTrapDefined Traps as defined in the PowerMIB and Generic (MIB II) traps as defined in RFC 1215. (3 Deprecated) stndPlus: same as stnd plus variables from the interface group and, where appropriate, xupsTrapMessage. (4 Deprecated) xupsPlus: xupsTrapPortN Traps (same as xups plus variables from the interface group) and, for authFail, xupsTrapMessage. (5 pxg: Traps as defined in the Power Xpert Gateway MIB (PXG-MIB). | 1.3.6.1.4.1.534.1.11.2 | INTEGER {stnd(1), xups(2), stndPlus(3), xupsPlus(4), pxg(5)} | read-write | current |
| xupsTrapMessage OBJECT-TYPE A descriptive text message which may be sent with traps to further explain the reason for the trap. This object is not-accessible to MIB browsers, but had to be changed to read-only to satisfy SMIv2 syntax checkers since it is included in traps. | 1.3.6.1.4.1.534.1.11.3 | DisplayString (SIZE(0..79)) | read-only | current |
| xupsTrapSource OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.11.4 | |||
| xupsTrapDefined OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.11.4.1 | |||
| xupsTrapOidDefined OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.11.4.1.0 | |||
| xupsHeartbeatMinsInterval OBJECT-TYPE How often to send the xupstdHeartbeat trap, in units of minutes. A setting of 0 disables the Heartbeat function. | 1.3.6.1.4.1.534.1.11.5 | Integer32 (0..2147483647) | read-write | current |
| xupsRecep OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.12 | |||
| xupsNumReceptacles OBJECT-TYPE The number of independently controllable Receptacles, as described in the xupsRecepTable. | 1.3.6.1.4.1.534.1.12.1 | Integer32 (0..64) | read-only | current |
| xupsRecepTable OBJECT-TYPE A list of receptacle table entries. The number of entries is given by the value of xupsNumReceptacles. | 1.3.6.1.4.1.534.1.12.2 | not-accessible | current | |
| xupsRecepEntry OBJECT-TYPE A receptacle table entry containing the status and control values for one receptacle. | 1.3.6.1.4.1.534.1.12.2.1 | not-accessible | current | |
| xupsRecepIndex OBJECT-TYPE The number of the Receptacle. Serves as index for Receptacle table. | 1.3.6.1.4.1.534.1.12.2.1.1 | Integer32 (1..64) | read-only | current |
| xupsRecepStatus OBJECT-TYPE The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 4=Off w/Pending ON, 5=Unknown, 6=Reserved for future, 7=Failed in Closed position, 8=Failed in Open position. | 1.3.6.1.4.1.534.1.12.2.1.2 | INTEGER {on(1), off(2), pendingOff(3), pendingOn(4), unknown(5), reserved(6), failedClosed(7), failedOpen(8)} | read-only | current |
| xupsRecepOffDelaySecs OBJECT-TYPE The Delay until the Receptacle is turned Off. Setting this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending shutdown. When this object is set while the UPS is On Battery, it is not necessary to set xupsRecepOnDelaySecs, since the outlet will turn back on automatically when power is available again. | 1.3.6.1.4.1.534.1.12.2.1.3 | Integer32 (-1..2147483647) | read-write | current |
| xupsRecepOnDelaySecs OBJECT-TYPE The Delay until the Receptacle is turned On. Setting this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending restart. | 1.3.6.1.4.1.534.1.12.2.1.4 | Integer32 (-1..2147483647) | read-write | current |
| xupsRecepAutoOffDelay OBJECT-TYPE The delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappropriate. The AutoOffDelay can be used to prioritize loads in the event of a prolonged power outage; less critical loads will turn off earlier to extend battery time for the more critical loads. If the utility power is restored before the AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off. | 1.3.6.1.4.1.534.1.12.2.1.5 | Integer32 (-1..32767) | read-write | current |
| xupsRecepAutoOnDelay OBJECT-TYPE Seconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to do so. A value of 0 means that the Receptacle should come On immediately at power-up or for an On command. | 1.3.6.1.4.1.534.1.12.2.1.6 | Integer32 (-1..32767) | read-write | current |
| xupsRecepShedSecsWithRestart OBJECT-TYPE Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsRecepOffDelaySecs, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted. | 1.3.6.1.4.1.534.1.12.2.1.7 | Integer32 (0..2147483647) | read-write | current |
| xupsRecepHourlyPowerUsage OBJECT-TYPE Units are Watt-hours.This is the energy consumed during the last hour. | 1.3.6.1.4.1.534.1.12.2.1.8 | Integer32 (0..2147483647) | read-only | current |
| xupsRecepCumulativePowerUsage OBJECT-TYPE Units are Watt-hours.This is the energy consumed since the last reset. This object is writable so that it can be reset to 0. When it is written to 0, the xupsRecepCumulativePowerUsageTimer will be reset to 0 as well. | 1.3.6.1.4.1.534.1.12.2.1.9 | Integer32 (0..2147483647) | read-write | current |
| xupsRecepCumulativePowerUsageTimer OBJECT-TYPE Time in seconds since the cumulative power usage was last reset. | 1.3.6.1.4.1.534.1.12.2.1.10 | Counter32 | read-only | current |
| xupsTopology OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.13 | |||
| xupsTopologyType OBJECT-TYPE Value which denotes the type of UPS by its power topology. Values are the same as those described in the XCP Topology block's Overall Topology field. | 1.3.6.1.4.1.534.1.13.1 | Integer32 (0..32767) | read-only | current |
| xupsTopoMachineCode OBJECT-TYPE ID Value which denotes the Powerware model of the UPS for software. Values are the same as those described in the XCP Configuration block's Machine Code field. | 1.3.6.1.4.1.534.1.13.2 | Integer32 (0..32767) | read-only | current |
| xupsTopoUnitNumber OBJECT-TYPE Identifies which unit and what type of data is being reported. A value of 0 means that this MIB information comes from the top-level system view (eg, manifold module or system bypass cabinet reporting total system output). Standalone units also use a value of 0, since they are the 'full system' view. A value of 1 or higher indicates the number of the module in the system which is reporting only its own data in the PowerMIB objects. | 1.3.6.1.4.1.534.1.13.3 | Integer32 (0..64) | read-only | current |
| xupsTopoPowerStrategy OBJECT-TYPE Value which denotes which Power Strategy is currently set for the UPS. The values are: highAlert(1) - The UPS shall optimize its operating state to maximize its power-protection levels. This mode will be held for at most 24 hours. standard(2) - Balanced, normal power protection strategy. UPS will not enter HE operating mode from this setting. enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to optimize its operating state to maximize its efficiency, when conditions change to permit it (as determined by the UPS). forceHighEfficiency(4) - If this value is permitted to be Set for this UPS, and if conditions permit, requires the UPS to enter High Efficiency mode now, without delay (for as long as utility conditions permit). After successfully set to forceHighEfficiency(4), xupsTopoPowerStrategy changes to value enableHighEfficiency(3). xupsOutputSource will indicate if the UPS status is actually operating in High Efficiency mode. | 1.3.6.1.4.1.534.1.13.4 | INTEGER {highAlert(1), standard(2), enableHighEfficiency(3), immediateHighEfficiency(4)} | read-write | current |
| xupsAgent OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.14 | |||
| xupsAgentManufacturer OBJECT-TYPE The card agent Manufacturer Name (e.g. Eaton Corporation). | 1.3.6.1.4.1.534.1.14.1 | DisplayString (SIZE(0..31)) | read-only | current |
| xupsAgentModel OBJECT-TYPE The card agent model | 1.3.6.1.4.1.534.1.14.2 | DisplayString (SIZE(0..63)) | read-only | current |
| xupsAgentSoftwareVersion OBJECT-TYPE The agent firmware version. | 1.3.6.1.4.1.534.1.14.3 | DisplayString (SIZE(0..63)) | read-only | current |
| xupsAgentPartNumber OBJECT-TYPE The card agent catalog part number. | 1.3.6.1.4.1.534.1.14.4 | OCTET STRING (SIZE(1..31)) | read-only | current |
| xupsAgentSerialNumber OBJECT-TYPE The card agent catalog serial number. | 1.3.6.1.4.1.534.1.14.5 | OCTET STRING (SIZE(1..31)) | read-only | current |
| xupsConformance OBJECT-IDENTITY | 1.3.6.1.4.1.534.1.100 |
Notifications
| Name | OID | Status |
|---|---|---|
| xupstdControlOff NOTIFICATION-TYPE The UPS output power will turn off in a number of seconds equal to upsControlOutputOffTrapDelay. | 1.3.6.1.4.1.534.1.11.4.1.0.1 | current |
| xupstdControlOn NOTIFICATION-TYPE The UPS output power will turn on in a number of seconds equal to upsControlOutputOnTrapDelay. | 1.3.6.1.4.1.534.1.11.4.1.0.2 | current |
| xupstdOnBattery NOTIFICATION-TYPE The UPS has no AC input power and is running on battery. | 1.3.6.1.4.1.534.1.11.4.1.0.3 | current |
| xupstdLowBattery NOTIFICATION-TYPE The UPS batteries are low. Tied to low battery alarm condition. | 1.3.6.1.4.1.534.1.11.4.1.0.4 | current |
| xupstdUtilityPowerRestored NOTIFICATION-TYPE Input power has been restored after running on battery. | 1.3.6.1.4.1.534.1.11.4.1.0.5 | current |
| xupstdReturnFromLowBattery NOTIFICATION-TYPE The battery has recovered from a low battery condition. | 1.3.6.1.4.1.534.1.11.4.1.0.6 | current |
| xupstdOutputOverload NOTIFICATION-TYPE The ups has sensed an overload of greater than 106 percent. Tied to the 106% overload alarm. | 1.3.6.1.4.1.534.1.11.4.1.0.7 | current |
| xupstdInternalFailure NOTIFICATION-TYPE Some component of the ups - rectifier, inverter, control panel has failed. Tied to alarms indi- cating failure. | 1.3.6.1.4.1.534.1.11.4.1.0.8 | current |
| xupstdBatteryDischarged NOTIFICATION-TYPE The Battery Totally Discharged Alarm has occurred. | 1.3.6.1.4.1.534.1.11.4.1.0.9 | current |
| xupstdInverterFailure NOTIFICATION-TYPE The ups inverter is unavailable or malfunctioning due to an internal failure. | 1.3.6.1.4.1.534.1.11.4.1.0.10 | current |
| xupstdOnBypass NOTIFICATION-TYPE The ups has gone on bypass for some reason. | 1.3.6.1.4.1.534.1.11.4.1.0.11 | current |
| xupstdBypassNotAvailable NOTIFICATION-TYPE The ups bypass is unavailable | 1.3.6.1.4.1.534.1.11.4.1.0.12 | current |
| xupstdOutputOff NOTIFICATION-TYPE The ups output is switched off. | 1.3.6.1.4.1.534.1.11.4.1.0.13 | current |
| xupstdInputFailure NOTIFICATION-TYPE The ups input power is incorrect in voltage, frequency, or phase rotation. | 1.3.6.1.4.1.534.1.11.4.1.0.14 | current |
| xupstdBuildingAlarm NOTIFICATION-TYPE One of the defined building alarms has occurred. | 1.3.6.1.4.1.534.1.11.4.1.0.15 | current |
| xupstdShutdownImminent NOTIFICATION-TYPE The ups shutdown imminent alarm has occurred. | 1.3.6.1.4.1.534.1.11.4.1.0.16 | current |
| xupstdOnInverter NOTIFICATION-TYPE The ups is returned to utility power running the inverter after either a transfer to bypass or a run on battery. | 1.3.6.1.4.1.534.1.11.4.1.0.17 | current |
| xupstdBreakerOpen NOTIFICATION-TYPE One of the UPS breakers or contactors has been opened. | 1.3.6.1.4.1.534.1.11.4.1.0.20 | current |
| xupstdAlarmEntryAdded NOTIFICATION-TYPE An alarm not defined in the xups Well Known Alarms (eg, an alarm defined in RFC1628) has been added to the Alarm Table. | 1.3.6.1.4.1.534.1.11.4.1.0.21 | current |
| xupstdAlarmEntryRemoved NOTIFICATION-TYPE An alarm not defined in the xups Well Known Alarms has been removed from the Alarm Table. | 1.3.6.1.4.1.534.1.11.4.1.0.22 | current |
| xupstdAlarmBatteryBad NOTIFICATION-TYPE One or more batteries have been determined to require replacement. | 1.3.6.1.4.1.534.1.11.4.1.0.23 | current |
| xupstdOutputOffAsRequested NOTIFICATION-TYPE The UPS has shutdown as requested, i.e., the output is off. | 1.3.6.1.4.1.534.1.11.4.1.0.24 | current |
| xupstdDiagnosticTestFailed NOTIFICATION-TYPE The result of the last diagnostic test indicates a failure. | 1.3.6.1.4.1.534.1.11.4.1.0.25 | current |
| xupstdCommunicationsLost NOTIFICATION-TYPE A problem has been encountered in the communications between the agent and the UPS. | 1.3.6.1.4.1.534.1.11.4.1.0.26 | current |
| xupstdUpsShutdownPending NOTIFICATION-TYPE An xupsControlOutputOffDelay countdown is underway. | 1.3.6.1.4.1.534.1.11.4.1.0.27 | current |
| xupstdAlarmTestInProgress NOTIFICATION-TYPE A test is in progress, as initiated and indicated by the xupsTest Group. When the test is complete, one of the following traps will be sent: - xupstdDiagnosticTestFailed if the test fails, - xupstdDiagnosticTestPassed on success, or - xupstdAlarmEntryRemoved in other cases (e.g., Test Canceled). | 1.3.6.1.4.1.534.1.11.4.1.0.28 | current |
| xupstdAmbientTempBad NOTIFICATION-TYPE The ambient temperature, xupsEnvAmbientTemp, has fallen below the set lower limit, xupsEnvAmbientLowerLimit, or has risen above the set upper limit, xupsEnvAmbientUpperLimit. | 1.3.6.1.4.1.534.1.11.4.1.0.29 | current |
| xupstdContactActiveNotice NOTIFICATION-TYPE The Contact indicated by xupsContactIndex is in its Active state. The following are the situations that generate this trap: For xupsContactType: and xupsContactState: normallyOpen(1) and closedWithNotice(4) normallyClosed(2) and openWithNotice(3) anyChange(3) and openWithNotice(3) or closedWithNotice(4) | 1.3.6.1.4.1.534.1.11.4.1.0.30 | current |
| xupstdContactInactiveNotice NOTIFICATION-TYPE The Contact indicated by xupsContactIndex has changed to its Inactive state. | 1.3.6.1.4.1.534.1.11.4.1.0.31 | current |
| xupstdLossOfRedundancy NOTIFICATION-TYPE A parallel UPS system is no longer operating in N+1 redundant mode; this may be due to module failure or removal, or due to overloading. | 1.3.6.1.4.1.534.1.11.4.1.0.32 | current |
| xupstdAlarmTempBad NOTIFICATION-TYPE An internal temperature is out of tolerance. | 1.3.6.1.4.1.534.1.11.4.1.0.33 | current |
| xupstdAlarmChargerFailed NOTIFICATION-TYPE An uncorrected problem has been detected within the UPS charger subsystem. | 1.3.6.1.4.1.534.1.11.4.1.0.34 | current |
| xupstdAlarmFanFailure NOTIFICATION-TYPE The failure of one or more fans in the UPS has been detected. | 1.3.6.1.4.1.534.1.11.4.1.0.35 | current |
| xupstdAlarmFuseFailure NOTIFICATION-TYPE The failure of one or more fuses has been detected. | 1.3.6.1.4.1.534.1.11.4.1.0.36 | current |
| xupstdPowerSwitchBad NOTIFICATION-TYPE A Relay, Contactor, or Breaker has failed. | 1.3.6.1.4.1.534.1.11.4.1.0.37 | current |
| xupstdModuleFailure NOTIFICATION-TYPE One module in a parallel or composite system has failed. | 1.3.6.1.4.1.534.1.11.4.1.0.38 | current |
| xupstdOnAlternatePowerSource NOTIFICATION-TYPE The system is being powered by its Alternate Power Source, such as a Secondary utility feed (on a dual AC input UPS), generator, flywheel, or fuel cell. | 1.3.6.1.4.1.534.1.11.4.1.0.39 | current |
| xupstdAltPowerNotAvailable NOTIFICATION-TYPE On systems with a separate alternate power source (eg, dual AC inputs), that alternate power source is currently not available. This could be a problem if the primary power source (eg, utility) fails for a period of time longer than that for which the internal batteries can supply power. | 1.3.6.1.4.1.534.1.11.4.1.0.40 | current |
| xupstdNoticeCondition NOTIFICATION-TYPE Some Notice condition exists which is not covered by the other traps. This is like an xupstdInternalFailure, but at a lower severity level. | 1.3.6.1.4.1.534.1.11.4.1.0.41 | current |
| xupstdRemoteTempBad NOTIFICATION-TYPE The remote temperature, xupsEnvRemoteTemp, has fallen below the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above the set upper limit, xupsEnvRemoteTempUpperLimit. | 1.3.6.1.4.1.534.1.11.4.1.0.42 | current |
| xupstdRemoteHumidityBad NOTIFICATION-TYPE The remote temperature, xupsEnvRemoteHumidity, has fallen below the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above the set upper limit, xupsEnvRemoteHumidityUpperLimit. | 1.3.6.1.4.1.534.1.11.4.1.0.43 | current |
| xupstdHeartbeat NOTIFICATION-TYPE A periodic status trap message. It is sent at an interval set by object xupsHeartbeatMinsInterval. The included variables provide a brief statement of the UPS status. | 1.3.6.1.4.1.534.1.11.4.1.0.44 | current |
| xupstdDiagnosticTestPassed NOTIFICATION-TYPE A diagnostic test just completed, and its result is Passed. The included variables provide additional information on the test. | 1.3.6.1.4.1.534.1.11.4.1.0.45 | current |
| xupstdOutputBad NOTIFICATION-TYPE The output condition (other than OutputOverload) is out of tolerance. | 1.3.6.1.4.1.534.1.11.4.1.0.46 | current |
| xupstdAwaitingPower NOTIFICATION-TYPE The UPS output is off and the UPS is awaiting the return of input power. | 1.3.6.1.4.1.534.1.11.4.1.0.47 | current |
| xupstdOnMaintenanceBypass NOTIFICATION-TYPE The UPS has been placed on Maintenance / Manual Bypass by an operator. | 1.3.6.1.4.1.534.1.11.4.1.0.48 | current |
| xupstdCommEstablished NOTIFICATION-TYPE This trap is sent when the SNMP agent first establishes a communication link with the UPS. The included variables provide identification and UPS status information. | 1.3.6.1.4.1.534.1.11.4.1.0.49 | current |
| xupstdAgentDown NOTIFICATION-TYPE This trap is sent when the SNMP agent is exiting or closing down gracefully. This may be triggered by a signal from the OS to stop this process. In many implementations, it will be followed quickly by a restart of this vital process. | 1.3.6.1.4.1.534.1.11.4.1.0.50 | current |
| xupstdOutputNotProtected NOTIFICATION-TYPE The ups output is not protectet for any reason in the UPS. | 1.3.6.1.4.1.534.1.11.4.1.0.51 | current |
| xupstdTestTrap NOTIFICATION-TYPE This trap is sent to the trap receivers to check proper reception of traps. | 1.3.6.1.4.1.534.1.11.4.1.0.100 | current |
Conformance
| Name | OID | Status |
|---|---|---|
| xupsIdentFullGroup OBJECT-GROUP The Full set of xupsIdent subgroup objects. | 1.3.6.1.4.1.534.1.100.2 | current |
| xupsBatteryFullGroup OBJECT-GROUP The Full set of xupsBattery subgroup objects. | 1.3.6.1.4.1.534.1.100.3 | current |
| xupsInputFullGroup OBJECT-GROUP The Full set of xupsInput subgroup objects. | 1.3.6.1.4.1.534.1.100.4 | current |
| xupsInputTableFullGroup OBJECT-GROUP The Full set of xupsInputTable subgroup objects. | 1.3.6.1.4.1.534.1.100.5 | current |
| xupsOutputFullGroup OBJECT-GROUP The Full set of xupsOutput subgroup objects. | 1.3.6.1.4.1.534.1.100.6 | current |
| xupsOutputTableFullGroup OBJECT-GROUP The Full set of xupsOutputTable subgroup objects. | 1.3.6.1.4.1.534.1.100.7 | current |
| xupsBypassFullGroup OBJECT-GROUP The Full set of xupsBypass subgroup objects. | 1.3.6.1.4.1.534.1.100.8 | current |
| xupsEnvironmentFullGroup OBJECT-GROUP The Full set of xupsEnvironment subgroup objects. | 1.3.6.1.4.1.534.1.100.9 | current |
| xupsAlarmFullGroup OBJECT-GROUP The Full set of xupsAlarm subgroup objects. | 1.3.6.1.4.1.534.1.100.10 | current |
| xupsAlarmEventsFullGroup OBJECT-GROUP The Full set of Alarm/Event history subgroup objects. | 1.3.6.1.4.1.534.1.100.11 | current |
| xupsTestFullGroup OBJECT-GROUP The Full set of xupsTest subgroup objects. | 1.3.6.1.4.1.534.1.100.12 | current |
| xupsControlFullGroup OBJECT-GROUP The Full set of xupsControl subgroup objects. | 1.3.6.1.4.1.534.1.100.13 | current |
| xupsConfigFullGroup OBJECT-GROUP The Full set of xupsConfig subgroup objects. | 1.3.6.1.4.1.534.1.100.14 | current |
| xupsTrapControlFullGroup OBJECT-GROUP The Full set of xupsTrapControl subgroup objects. | 1.3.6.1.4.1.534.1.100.15 | current |
| xupsRecepFullGroup OBJECT-GROUP The Full set of xupsRecep subgroup objects. | 1.3.6.1.4.1.534.1.100.16 | current |
| xupsTopologyFullGroup OBJECT-GROUP The Full set of xupsTopology subgroup objects. | 1.3.6.1.4.1.534.1.100.17 | current |
| xupstdNotifyGroup NOTIFICATION-GROUP The Alarm and Event notifications from the xupsTrapDefined source (xupstd). | 1.3.6.1.4.1.534.1.100.18 | current |
| xupstdEMPNotifyGroup NOTIFICATION-GROUP The EMP's Alarm and Event notifications from the xupsTrapDefined source (xupstd). | 1.3.6.1.4.1.534.1.100.19 | current |
| xupsMibFullCompliance MODULE-COMPLIANCE A compliance statement for all of everything in this MIB. | 1.3.6.1.4.1.534.1.100.20 | current |
| xupsDeprecatedGroup OBJECT-GROUP Contains objects which are now deprecated. | 1.3.6.1.4.1.534.1.100.21 | deprecated |
| xupsBypassTableFullGroup OBJECT-GROUP The Full set of xupsBypassTable subgroup objects. | 1.3.6.1.4.1.534.1.100.22 | current |
| xupsInputTotalFullGroup OBJECT-GROUP The Full set of xupsInputTotal subgroup objects. | 1.3.6.1.4.1.534.1.100.23 | current |
| xupsOutputTotalFullGroup OBJECT-GROUP The Full set of xupsOutputTotal subgroup objects. | 1.3.6.1.4.1.534.1.100.24 | current |
| xupsBypassTotalFullGroup OBJECT-GROUP The Full set of xupsOutputTotal subgroup objects. | 1.3.6.1.4.1.534.1.100.25 | current |
| xupsAgentFullGroup OBJECT-GROUP The Full set of xupsAgent subgroup objects. | 1.3.6.1.4.1.534.1.100.26 | current |