Description

Defines Eaton's proprietary PowerMIB for UPS and related device data. Copyright (C) Exide Electronics 1992-98 Copyright (C) Powerware Corporation 1999-2004 Copyright (C) Eaton Corporation (2005-).

Contact

Eaton Power Quality Technical Support (PQTS) group www.eaton.com/powerxpert Technical Resource Center phone numbers United States: 1.800.843.9433 or 919.870.3028 Canada: 1.800.461.9166 ext. 260 All other countries: Call your local service representative.

Imports

FromSymbols
EATON-EMP-MIBxupsContactDescr, xupsContactIndex, xupsContactState, xupsContactType, xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit, xupsEnvRemoteHumidityUpperLimit, xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit, xupsEnvRemoteTempUpperLimit
EATON-OIDSeaton, xupsEnvironment
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-MIBsysName
SNMPv2-SMICounter32, Gauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

EATON-EMP-MIB
EATON-OIDS
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC
XUPS-MIB

Under this module's arcs

Where the registration tree carries on below this module.

ArcNameModule
1.3.6.1.4.1.534.1.6xupsEnvironment

Objects

NameOIDSyntaxAccessStatus
xupsIdent
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.1
xupsIdentManufacturer
OBJECT-TYPE
The UPS Manufacturer Name (e.g. Eaton Corporation).
1.3.6.1.4.1.534.1.1.1DisplayString (SIZE(0..31))read-onlycurrent
xupsIdentModel
OBJECT-TYPE
The UPS Model (e.g. Powerware Plus Model 18).
1.3.6.1.4.1.534.1.1.2DisplayString (SIZE(0..63))read-onlycurrent
xupsIdentSoftwareVersion
OBJECT-TYPE
The firmware revision level(s) of the UPS microcontroller(s).
1.3.6.1.4.1.534.1.1.3DisplayString (SIZE(0..63))read-onlycurrent
xupsIdentOemCode
OBJECT-TYPE
A binary code indicating who the UPS was manufactured or labeled for. 0 or 255 indicates Eaton itself.
1.3.6.1.4.1.534.1.1.4Integer32 (0..255)read-onlycurrent
xupsIdentPartNumber
OBJECT-TYPE
The catalog part number of the UPS device.
1.3.6.1.4.1.534.1.1.5OCTET STRING (SIZE(1..31))read-onlycurrent
xupsIdentSerialNumber
OBJECT-TYPE
The serial number of the UPS device.
1.3.6.1.4.1.534.1.1.6OCTET STRING (SIZE(1..31))read-onlycurrent
xupsBattery
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.2
xupsBatTimeRemaining
OBJECT-TYPE
Battery run time in seconds before UPS turns off due to low battery.
1.3.6.1.4.1.534.1.2.1Integer32 (0..2147483647)read-onlycurrent
xupsBatVoltage
OBJECT-TYPE
Battery voltage as reported by the UPS meters.
1.3.6.1.4.1.534.1.2.2Integer32 (0..2147483647)read-onlycurrent
xupsBatCurrent
OBJECT-TYPE
Battery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery.
1.3.6.1.4.1.534.1.2.3Integer32 (-2147483648..2147483647)read-onlycurrent
xupsBatCapacity
OBJECT-TYPE
Battery percent charge.
1.3.6.1.4.1.534.1.2.4Integer32 (0..100)read-onlycurrent
xupsBatteryAbmStatus
OBJECT-TYPE
Gives the status of the Advanced Battery Management and Battery state; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage; batteryResting(4) is the state when the battery is fully charged and none of the other actions (charging/discharging/floating) is being done. checkBattery(8) indicates that the Battery state is uncertain following a poor battery test result.
1.3.6.1.4.1.534.1.2.5INTEGER {batteryCharging(1), batteryDischarging(2), batteryFloating(3), batteryResting(4), unknown(5), batteryDisconnected(6), batteryUnderTest(7), checkBattery(8)}read-onlycurrent
xupsBatteryLastReplacedDate
OBJECT-TYPE
The date when the Batteries in this UPS were last replaced. Free text format, so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc).
1.3.6.1.4.1.534.1.2.6DisplayString (SIZE(0..16))read-onlycurrent
xupsBatteryFailure
OBJECT-TYPE
Indicates if a battery fault detected or battery tests failed.
1.3.6.1.4.1.534.1.2.7INTEGER {yes(1), no(2)}read-onlycurrent
xupsBatteryNotPresent
OBJECT-TYPE
Indicates if the UPS has no battery either internal or external.
1.3.6.1.4.1.534.1.2.8INTEGER {yes(1), no(2)}read-onlycurrent
xupsBatteryAged
OBJECT-TYPE
Indicates if the battery is over aged.
1.3.6.1.4.1.534.1.2.9INTEGER {yes(1), no(2)}read-onlycurrent
xupsBatteryLowCapacity
OBJECT-TYPE
Indicates if the battery capacity is below the threshold set in the UPS.
1.3.6.1.4.1.534.1.2.10INTEGER {yes(1), no(2)}read-onlycurrent
xupsInput
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.3
xupsInputFrequency
OBJECT-TYPE
The utility line frequency in tenths of Hz.
1.3.6.1.4.1.534.1.3.1Integer32 (0..2147483647)read-onlycurrent
xupsInputLineBads
OBJECT-TYPE
The number of times the Input was out of tolerance in voltage or frequency.
1.3.6.1.4.1.534.1.3.2Counter32read-onlycurrent
xupsInputNumPhases
OBJECT-TYPE
The number of input phases (normally 1 to 3).
1.3.6.1.4.1.534.1.3.3Integer32 (0..6)read-onlycurrent
xupsInputTable
OBJECT-TYPE
A list of input table entries. The number of entries is given by the value of xupsInputNumPhases.
1.3.6.1.4.1.534.1.3.4not-accessiblecurrent
xupsInputEntry
OBJECT-TYPE
The input table entry containing the current, voltage, etc. readings for one phase.
1.3.6.1.4.1.534.1.3.4.1not-accessiblecurrent
xupsInputPhase
OBJECT-TYPE
The number of the phase. Serves as index for input table.
1.3.6.1.4.1.534.1.3.4.1.1Integer32 (0..6)read-onlycurrent
xupsInputVoltage
OBJECT-TYPE
The measured input voltage from the UPS meters in volts.
1.3.6.1.4.1.534.1.3.4.1.2Integer32 (0..2147483647)read-onlycurrent
xupsInputCurrent
OBJECT-TYPE
The measured input current from the UPS meters in amps.
1.3.6.1.4.1.534.1.3.4.1.3Integer32 (0..2147483647)read-onlycurrent
xupsInputWatts
OBJECT-TYPE
The measured input real power in watts.
1.3.6.1.4.1.534.1.3.4.1.4Integer32 (0..2147483647)read-onlycurrent
xupsInputId
OBJECT-TYPE
value indicates what measurement is being stored in this table row : phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1.
1.3.6.1.4.1.534.1.3.4.1.5INTEGER {phase1toN(1), phase2toN(2), phase3toN(3), phase1to2(4), phase2to3(5), phase3to1(6)}read-onlycurrent
xupsInputName
OBJECT-TYPE
A descriptive name for the phase, example : L1/A for the phase 1.
1.3.6.1.4.1.534.1.3.4.1.6OCTET STRING (SIZE(1..31))read-onlycurrent
xupsInputCurrentHighPrecision
OBJECT-TYPE
The measured input current from the UPS meters in tenth of amps.
1.3.6.1.4.1.534.1.3.4.1.7Integer32 (0..2147483647)read-onlycurrent
xupsInputSource
OBJECT-TYPE
The present external source of input power. The enumeration 'none(2)' indicates that there is no external source of power, for example, the UPS is On Battery (an internal source). 'primaryUtility' indicates the normal case of utility input power. The 'bypassFeed' can only be used when the Bypass source is known to be a separate utility feed than the primaryUtility(3). 'secondaryUtility' indicates that a secondary utility feed is supplying power (on a dual AC input UPS). 'generator' indicates that input power is provided by a generator. Note that the alternate energy sources of 'flywheel' and 'fuelcell' are not necessarily AC input sources.
1.3.6.1.4.1.534.1.3.5INTEGER {other(1), none(2), primaryUtility(3), bypassFeed(4), secondaryUtility(5), generator(6), flywheel(7), fuelcell(8)}read-onlycurrent
xupsDualInputStatus
OBJECT-TYPE
The present status of the sources of input power in a dual source UPS. The enumeration primarySourceGood(2) indicates that the primary source of power is present and within 'normal' ranges for voltage and frequency, but the secondary source is either not present or not in an acceptable range. 'secondarySourceGood' indicates that only the Secondary power feed is available and within its limits. The enumeration bothSourcesGood(4) indicates that both sources are present and within their respective 'normal' ranges; bothSourcesBad(1) indicates that neither source is present, or, if present, is not within acceptable ranges. This object will only be implemented for UPSs with two sources of input power, e.g., redundant AC feeds or a separate Bypass or Generator source. The secondary source will not be an AC power source in all cases.
1.3.6.1.4.1.534.1.3.6INTEGER {bothSourcesBad(1), primarySourceGood(2), secondarySourceGood(3), bothSourcesGood(4)}read-onlycurrent
xupsSecondaryInputWatch
OBJECT-TYPE
This object enables(2) or disables(1) the alarms and traps related to the availability and use of the secondary input of a dual-input UPS (i.e., OnAlternatePowerSource and AltPowerNotAvailable). To avoid nuisance alarms and traps, this object should be set to disabled(1) when the UPS is not wired to a secondary source of power. This object will only be implemented for UPSs with two sources of input power, i.e., redundant AC feeds or a separate Bypass or Generator source.
1.3.6.1.4.1.534.1.3.7INTEGER {disabled(1), enabled(2)}read-writecurrent
xupsInputTotal
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.3.8
xupsInputAverageVoltage
OBJECT-TYPE
The measured input voltage from the UPS meters in volts. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase voltage.
1.3.6.1.4.1.534.1.3.8.1Integer32 (0..2147483647)read-onlycurrent
xupsInputTotalCurrent
OBJECT-TYPE
The measured input current from the UPS meters in tenth of amps. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase current.
1.3.6.1.4.1.534.1.3.8.2Integer32 (0..2147483647)read-onlycurrent
xupsInputTotalWatts
OBJECT-TYPE
The measured input active power in watts. Sum of all the simple phase watts.
1.3.6.1.4.1.534.1.3.8.3Integer32 (0..2147483647)read-onlycurrent
xupsInputTotalVA
OBJECT-TYPE
The measured input apparent power in VA. Sum of all the simple phase VA.
1.3.6.1.4.1.534.1.3.8.4Integer32 (0..2147483647)read-onlycurrent
xupsInputAveragePowerFactor
OBJECT-TYPE
Indicates the total power factor of the input in hundredths. 0.92 would be returned as 92.
1.3.6.1.4.1.534.1.3.8.5Integer32read-onlycurrent
xupsInputStatus
OBJECT-TYPE
The present status of the primary AC input of the UPS. The enumeration inputGood(2) indicates that the primary source of power is present and within 'normal' ranges for voltage and frequency. inputBad(1) indicates that neither source is present, or, if present, is not within acceptable ranges.
1.3.6.1.4.1.534.1.3.9INTEGER {inputBad(1), inputGood(2)}read-onlycurrent
xupsOutput
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.4
xupsOutputLoad
OBJECT-TYPE
The UPS output load in percent of rated capacity.
1.3.6.1.4.1.534.1.4.1Integer32 (0..200)read-onlycurrent
xupsOutputFrequency
OBJECT-TYPE
The measured UPS output frequency in tenths of Hz.
1.3.6.1.4.1.534.1.4.2Integer32 (0..2147483647)read-onlycurrent
xupsOutputNumPhases
OBJECT-TYPE
The number of metered output phases.
1.3.6.1.4.1.534.1.4.3Integer32 (0..6)read-onlycurrent
xupsOutputTable
OBJECT-TYPE
A list of output table entries. The number of entries is given by the value of xupsOutputNumPhases.
1.3.6.1.4.1.534.1.4.4not-accessiblecurrent
xupsOutputEntry
OBJECT-TYPE
Output Table Entry containing voltage, current, etc.
1.3.6.1.4.1.534.1.4.4.1not-accessiblecurrent
xupsOutputPhase
OBJECT-TYPE
The number of the phase. Serves as index for output table.
1.3.6.1.4.1.534.1.4.4.1.1Integer32 (0..6)read-onlycurrent
xupsOutputVoltage
OBJECT-TYPE
The measured output voltage from the UPS metering in volts.
1.3.6.1.4.1.534.1.4.4.1.2Integer32 (0..2147483647)read-onlycurrent
xupsOutputCurrent
OBJECT-TYPE
The measured UPS output current in amps.
1.3.6.1.4.1.534.1.4.4.1.3Integer32 (0..2147483647)read-onlycurrent
xupsOutputWatts
OBJECT-TYPE
The measured real output power in watts.
1.3.6.1.4.1.534.1.4.4.1.4Integer32 (0..2147483647)read-onlycurrent
xupsOutputId
OBJECT-TYPE
value indicates what measurement is being stored in this table row : phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1.
1.3.6.1.4.1.534.1.4.4.1.5INTEGER {phase1toN(1), phase2toN(2), phase3toN(3), phase1to2(4), phase2to3(5), phase3to1(6)}read-onlycurrent
xupsOutputName
OBJECT-TYPE
A descriptive name for the phase.
1.3.6.1.4.1.534.1.4.4.1.6OCTET STRING (SIZE(1..31))read-onlycurrent
xupsOutputCurrentHighPrecision
OBJECT-TYPE
The measured output current from the UPS meters in tenth of amps.
1.3.6.1.4.1.534.1.4.4.1.7Integer32 (0..2147483647)read-onlycurrent
xupsOutputPercentLoad
OBJECT-TYPE
The percentage of the UPS power capacity presently being used on this output line
1.3.6.1.4.1.534.1.4.4.1.8Integer32 (0..200)read-onlycurrent
xupsOutputVA
OBJECT-TYPE
The measured apparent output power in VA.
1.3.6.1.4.1.534.1.4.4.1.9Integer32 (0..2147483647)read-onlycurrent
xupsOutputSource
OBJECT-TYPE
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. 'normal', 'bypass', and 'battery' indicate those common UPS statuses. 'booster' and 'reducer' indicate boost or buck operation, for line-interactive UPSs only. 'parallelCapacity' and 'parallelRedundant' indicate a normal parallel UPS system, in either Parallel for Capacity or Redundancy configuration. 'highEfficiencyMode' is normal but enhanced by High Efficiency mode. 'maintenanceBypass' indicates that the UPS is in Maintenance/Manual Bypass mode. 'essMode' is normal but enhanced by Energy Saver System. 'other' covers any other, unusual conditions.
1.3.6.1.4.1.534.1.4.5INTEGER {other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7), parallelCapacity(8), parallelRedundant(9), highEfficiencyMode(10), maintenanceBypass(11), essMode(12)}read-onlycurrent
xupsOutputHourlyPowerUsage
OBJECT-TYPE
Units are Watt-hours.This is the energy consumed during the last hour.
1.3.6.1.4.1.534.1.4.6Integer32 (0..2147483647)read-onlycurrent
xupsOutputCumulativePowerUsage
OBJECT-TYPE
Units are Watt-hours.This is the energy consumed since the last reset. This object is writable so that it can be reset to 0. When it is written to 0, the xupsOutputCumulativeWhTimer will be reset to 0 as well.
1.3.6.1.4.1.534.1.4.7Integer32 (0..2147483647)read-writecurrent
xupsOutputCumulativePowerUsageTimer
OBJECT-TYPE
Time in seconds since the cumulative power usage was last reset.
1.3.6.1.4.1.534.1.4.8Counter32read-onlycurrent
xupsOutputTotal
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.4.9
xupsOutputAverageVoltage
OBJECT-TYPE
The measured output voltage from the UPS meters in volts. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase voltage.
1.3.6.1.4.1.534.1.4.9.1Integer32 (0..2147483647)read-onlycurrent
xupsOutputTotalCurrent
OBJECT-TYPE
The measured output current from the UPS meters in tenth of amps. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase current.
1.3.6.1.4.1.534.1.4.9.2Integer32 (0..2147483647)read-onlycurrent
xupsOutputTotalWatts
OBJECT-TYPE
The measured output active power in watts. Sum of all the simple phase watts.
1.3.6.1.4.1.534.1.4.9.3Integer32 (0..2147483647)read-onlycurrent
xupsOutputTotalVA
OBJECT-TYPE
The measured output apparent power in VA. Sum of all the simple phase VA.
1.3.6.1.4.1.534.1.4.9.4Integer32 (0..2147483647)read-onlycurrent
xupsOutputAveragePowerFactor
OBJECT-TYPE
Indicates the total power factor of the output in hundredths. 0.92 would be returned as 92.
1.3.6.1.4.1.534.1.4.9.5Integer32read-onlycurrent
xupsOutputStatus
OBJECT-TYPE
The present status of the AC output of the UPS. The enumeration outputNotPowered(1) indicates that the output is not powered. outputNotProtected(2) indicates that the output is powered but not protected, due to following reasons : On bypass, battery fault, or UPS internal failure that makes the ups will be inoperant in case of AC input failure. outputProtected(3) indicates that the output is powered and protected.
1.3.6.1.4.1.534.1.4.10INTEGER {outputNotPowered(1), outputNotProtected(2), outputProtected(3)}read-onlycurrent
xupsBypass
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.5
xupsBypassFrequency
OBJECT-TYPE
The bypass frequency in tenths of Hz.
1.3.6.1.4.1.534.1.5.1Integer32 (0..2147483647)read-onlycurrent
xupsBypassNumPhases
OBJECT-TYPE
The number of lines in the UPS bypass table.
1.3.6.1.4.1.534.1.5.2Integer32 (0..6)read-onlycurrent
xupsBypassTable
OBJECT-TYPE
A list of bypass table entries. The number of entries is given by the value of xupsBypassNumPhases.
1.3.6.1.4.1.534.1.5.3not-accessiblecurrent
xupsBypassEntry
OBJECT-TYPE
Bypass Table Entry containing voltage for each phase.
1.3.6.1.4.1.534.1.5.3.1not-accessiblecurrent
xupsBypassPhase
OBJECT-TYPE
The Bypass Phase, index for the table.
1.3.6.1.4.1.534.1.5.3.1.1Integer32 (0..6)read-onlycurrent
xupsBypassVoltage
OBJECT-TYPE
The measured UPS bypass voltage in volts.
1.3.6.1.4.1.534.1.5.3.1.2Integer32 (0..2147483647)read-onlycurrent
xupsBypassId
OBJECT-TYPE
value indicates what measurement is being stored in this table row : phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1.
1.3.6.1.4.1.534.1.5.3.1.3INTEGER {phase1toN(1), phase2toN(2), phase3toN(3), phase1to2(4), phase2to3(5), phase3to1(6)}read-onlycurrent
xupsBypassName
OBJECT-TYPE
A descriptive name for the phase.
1.3.6.1.4.1.534.1.5.3.1.4OCTET STRING (SIZE(1..31))read-onlycurrent
xupsBypassCurrentHighPrecision
OBJECT-TYPE
The measured bypass current from the UPS meters in tenth of amps.
1.3.6.1.4.1.534.1.5.3.1.5Integer32 (0..2147483647)read-onlycurrent
xupsBypassWatts
OBJECT-TYPE
The measured real bypass power in watts.
1.3.6.1.4.1.534.1.5.3.1.6Integer32 (0..2147483647)read-onlycurrent
xupsBypassTotal
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.5.4
xupsBypassAverageVoltage
OBJECT-TYPE
The measured bypass voltage from the UPS meters in volts. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase voltage.
1.3.6.1.4.1.534.1.5.4.1Integer32 (0..2147483647)read-onlycurrent
xupsBypassTotalCurrent
OBJECT-TYPE
The measured bypass current from the UPS meters in tenth of amps. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase current.
1.3.6.1.4.1.534.1.5.4.2Integer32 (0..2147483647)read-onlycurrent
xupsBypassTotalWatts
OBJECT-TYPE
The measured bypass active power in watts. Sum of all the simple phase watts.
1.3.6.1.4.1.534.1.5.4.3Integer32 (0..2147483647)read-onlycurrent
xupsBypassTotalVA
OBJECT-TYPE
The measured output apparent power in VA. Sum of all the simple phase VA.
1.3.6.1.4.1.534.1.5.4.4Integer32 (0..2147483647)read-onlycurrent
xupsBypassAveragePowerFactor
OBJECT-TYPE
Indicates the total power factor of the input in hundredths. 0.92 would be returned as 92.
1.3.6.1.4.1.534.1.5.4.5Integer32read-onlycurrent
xupsEnvAmbientTemp
OBJECT-TYPE
The reading of the ambient temperature in the vicinity of the UPS or SNMP agent.
1.3.6.1.4.1.534.1.6.1Integer32 (-100..200)read-onlycurrent
xupsEnvAmbientLowerLimit
OBJECT-TYPE
The Lower Limit of the ambient temperature; if xupsEnvAmbientTemp falls below this value, the xupsAmbientTempBad alarm will occur.
1.3.6.1.4.1.534.1.6.2Integer32 (-100..200)read-writecurrent
xupsEnvAmbientUpperLimit
OBJECT-TYPE
The Upper Limit of the ambient temperature; if xupsEnvAmbientTemp rises above this value, the xupsAmbientTempBad alarm will occur. This value should be greater than xupsEnvAmbientLowerLimit.
1.3.6.1.4.1.534.1.6.3Integer32 (-100..200)read-writecurrent
xupsEnvAmbientHumidity
OBJECT-TYPE
The reading of the ambient humidity in the vicinity of the UPS or SNMP agent.
1.3.6.1.4.1.534.1.6.4Integer32 (0..100)read-onlycurrent
xupsAlarm
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7
xupsAlarms
OBJECT-TYPE
The current number of alarm conditions.
1.3.6.1.4.1.534.1.7.1Gauge32read-onlycurrent
xupsAlarmTable
OBJECT-TYPE
A list of alarm table entries. The number of entries is given by the value of xupsAlarms. Note that this table is sparsely (non-consecutively) numbered and will be empty if there are no active alarms.
1.3.6.1.4.1.534.1.7.2not-accessiblecurrent
xupsAlarmEntry
OBJECT-TYPE
Alarm Table Entry containing descriptive information for one alarm entry.
1.3.6.1.4.1.534.1.7.2.1not-accessiblecurrent
xupsAlarmID
OBJECT-TYPE
A unique identifier for an alarm condition.
1.3.6.1.4.1.534.1.7.2.1.1Integer32 (1..2147483647)read-onlycurrent
xupsAlarmDescr
OBJECT-TYPE
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
1.3.6.1.4.1.534.1.7.2.1.2OBJECT IDENTIFIERread-onlycurrent
xupsAlarmTime
OBJECT-TYPE
The value of the MIB-II variable sysUpTime when the alarm condition occurred.
1.3.6.1.4.1.534.1.7.2.1.3TimeTicksread-onlycurrent
xupsOnBattery
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.3
xupsLowBattery
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.4
xupsUtilityPowerRestored
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.5
xupsReturnFromLowBattery
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.6
xupsOutputOverload
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.7
xupsInternalFailure
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.8
xupsBatteryDischarged
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.9
xupsInverterFailure
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.10
xupsOnBypass
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.11
xupsBypassNotAvailable
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.12
xupsOutputOff
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.13
xupsInputFailure
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.14
xupsBuildingAlarm
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.15
xupsShutdownImminent
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.16
xupsOnInverter
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.17
xupsAlarmNumEvents
OBJECT-TYPE
The number of entries in the UPS event history queue.
1.3.6.1.4.1.534.1.7.18Gauge32read-onlycurrent
xupsAlarmEventTable
OBJECT-TYPE
A table of the UPS internal event history queue.
1.3.6.1.4.1.534.1.7.19not-accessiblecurrent
xupsAlarmEventEntry
OBJECT-TYPE
One of the entries in the UPS event history queue.
1.3.6.1.4.1.534.1.7.19.1not-accessiblecurrent
xupsAlarmEventID
OBJECT-TYPE
A unique number that reflects the order in which the event occurred. The oldest event in the queue will be number 1. Subsequent events will be numbered 2, 3, 4, etc.
1.3.6.1.4.1.534.1.7.19.1.1Integer32 (1..400)not-accessiblecurrent
xupsAlarmEventDateAndTime
OBJECT-TYPE
The time and date that an event occurred as recorded in the UPS internal event queue. This string will reflect the time and date as set in the UPS itself and will not be referenced to sysUpTime. The format is MM/DD/YYYY:HH:MM:SS. Time is 24 hour standard.
1.3.6.1.4.1.534.1.7.19.1.2DisplayString (SIZE(0..22))read-onlydeprecated
xupsAlarmEventKind
OBJECT-TYPE
Enumerated value that tells whether the event is an occurrence of an alarm condition or a clearing of an alarm condition.
1.3.6.1.4.1.534.1.7.19.1.3INTEGER {occurred(1), cleared(2), unknown(3)}read-onlydeprecated
xupsAlarmEventDescr
OBJECT-TYPE
A description of the event stored in the UPS event queue. This description will be a sixteen bit integer value representing one of the defined alarms in the Powerware Binary Computer Mode communication specification; for example, a value of 0 represents the 'Inverter AC Over Voltage' alarm (byte 1, bit 0 in the BCM Alarm Map).
1.3.6.1.4.1.534.1.7.19.1.4Integer32 (0..2147483647)read-onlydeprecated
xupsAlarmEventMsg
OBJECT-TYPE
A text string describing each entry in the Event Log. The format of this text message is free (not fixed) for the operator to read; good contents would be a time & date stamp, the event type, and a description of the event.
1.3.6.1.4.1.534.1.7.19.1.5DisplayString (SIZE(0..80))read-onlycurrent
xupsBreakerOpen
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.20
xupsAlarmEntryAdded
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.21
xupsAlarmEntryRemoved
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.22
xupsAlarmBatteryBad
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.23
xupsOutputOffAsRequested
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.24
xupsDiagnosticTestFailed
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.25
xupsCommunicationsLost
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.26
xupsUpsShutdownPending
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.27
xupsAlarmTestInProgress
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.28
xupsAmbientTempBad
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.29
xupsLossOfRedundancy
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.30
xupsAlarmTempBad
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.31
xupsAlarmChargerFailed
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.32
xupsAlarmFanFailure
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.33
xupsAlarmFuseFailure
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.34
xupsPowerSwitchBad
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.35
xupsModuleFailure
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.36
xupsOnAlternatePowerSource
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.37
xupsAltPowerNotAvailable
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.38
xupsNoticeCondition
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.39
xupsRemoteTempBad
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.40
xupsRemoteHumidityBad
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.41
xupsAlarmOutputBad
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.42
xupsAlarmAwaitingPower
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.43
xupsOnMaintenanceBypass
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.44
xupsOutputNotProtected
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.7.51
xupsTest
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.8
xupsTestStart
OBJECT-TYPE
Setting this object initiates the requested Test. The test types which a UPS might support are 'testBattery', 'testSystem' (a UPS General Systems test, however defined by the UPS), 'testSecondarySource' (test if the Secondary power source is good on a dual input UPS), and 'flashLightsTest' (start a test which flashes the UPS lights, and if available, sounds the horn to help locate the UPS). If a UPS does not support the requested test, the set operation may succeed but the xupsTestBatteryStatus will end up as notSupported. When read, this object indicates the last test requested via this object, if any; 'noTestStarted' could be the initial value. Currently only the 'flashLightsTest' can be canceled with 'cancelTest'.
1.3.6.1.4.1.534.1.8.1INTEGER {testBattery(1), noTestStarted(2), testSystem(3), testSecondarySource(4), flashLightsTest(5), cancelTest(6)}read-writecurrent
xupsTestBatteryStatus
OBJECT-TYPE
Reading this enumerated value gives an indication of the (last) UPS Battery test status. 'inhibited' means that the battery test could not be run. 'scheduled' means that the battery test could not be run at the time of request, but will be run at some later (UPS-determined) time.
1.3.6.1.4.1.534.1.8.2INTEGER {unknown(1), passed(2), failed(3), inProgress(4), notSupported(5), inhibited(6), scheduled(7)}read-onlycurrent
xupsLastGeneralTest
OBJECT-TYPE
Indicates the last UPS test requested via xupsTestStart or by other non-SNMP means, other than for the testBattery (1) case. The results of the test indicated by this object are reported in xupsLastGeneralTestResult.
1.3.6.1.4.1.534.1.8.3INTEGER {noTestStarted(2), testSystem(3), testSecondarySource(4), flashLightsTest(5)}read-onlycurrent
xupsLastGeneralTestResult
OBJECT-TYPE
Reading this enumerated value gives the result of the test indicated in xupsLastGeneralTest.
1.3.6.1.4.1.534.1.8.4INTEGER {unknown(1), passed(2), failed(3), inProgress(4), notSupported(5), inhibited(6), scheduled(7)}read-onlycurrent
xupsTestTrap
OBJECT-TYPE
Setting startTestTrap to 1 will initiate a test trap to be sent out from the agent. All other set values are invalid.
1.3.6.1.4.1.534.1.8.5INTEGER {startTestTrap(1)}read-writecurrent
xupsControl
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.9
xupsControlOutputOffDelay
OBJECT-TYPE
Setting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pending shutdown.
1.3.6.1.4.1.534.1.9.1Integer32 (0..2147483647)read-writecurrent
xupsControlOutputOnDelay
OBJECT-TYPE
Setting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pending startup.
1.3.6.1.4.1.534.1.9.2Integer32 (0..2147483647)read-writecurrent
xupsControlOutputOffTrapDelay
OBJECT-TYPE
When xupsControlOutputOffDelay reaches this value, a trap will be sent.
1.3.6.1.4.1.534.1.9.3Integer32 (0..2147483647)read-writecurrent
xupsControlOutputOnTrapDelay
OBJECT-TYPE
When xupsControlOutputOnDelay reaches this value, a xupsOutputOff trap will be sent.
1.3.6.1.4.1.534.1.9.4Integer32 (0..2147483647)read-writedeprecated
xupsControlToBypassDelay
OBJECT-TYPE
Setting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the UPS to not supply power to the load. Setting it to 0 will cause an attempt to abort a pending shutdown.
1.3.6.1.4.1.534.1.9.5Integer32 (0..2147483647)read-writecurrent
xupsLoadShedSecsWithRestart
OBJECT-TYPE
Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsControlOutputOffDelay, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted. This is the preferred Control object to use when performing an On Battery OS Shutdown.
1.3.6.1.4.1.534.1.9.6Integer32 (0..2147483647)read-writecurrent
xupsSwitchable
OBJECT-TYPE
Parameter which indicates whether UPS commands received via any communication path (aside from manual controls) are able (switchable) or not able (notSwitchable) to control the UPS.
1.3.6.1.4.1.534.1.9.7INTEGER {switchable(1), notSwitchable(2)}read-onlycurrent
xupsConfig
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.10
xupsConfigOutputVoltage
OBJECT-TYPE
The nominal UPS Output voltage per phase in volts.
1.3.6.1.4.1.534.1.10.1Integer32 (0..2147483647)read-onlycurrent
xupsConfigInputVoltage
OBJECT-TYPE
The nominal UPS Input voltage per phase in volts.
1.3.6.1.4.1.534.1.10.2Integer32 (0..2147483647)read-onlycurrent
xupsConfigOutputWatts
OBJECT-TYPE
The nominal UPS available real power output in watts.
1.3.6.1.4.1.534.1.10.3Integer32 (0..2147483647)read-onlycurrent
xupsConfigOutputFreq
OBJECT-TYPE
The nominal output frequency in tenths of Hz.
1.3.6.1.4.1.534.1.10.4Integer32 (0..2147483647)read-onlycurrent
xupsConfigDateAndTime
OBJECT-TYPE
Date and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS time and date. This value is not referenced to sysUpTime. It is simply the clock value from the UPS real time clock. Format is as follows: MM/DD/YYYY:HH:MM:SS.
1.3.6.1.4.1.534.1.10.5DisplayString (SIZE(0..22))read-writecurrent
xupsConfigLowOutputVoltageLimit
OBJECT-TYPE
The Lower limit for acceptable Output Voltage, per the UPS specifications.
1.3.6.1.4.1.534.1.10.6Integer32 (0..2147483647)read-onlycurrent
xupsConfigHighOutputVoltageLimit
OBJECT-TYPE
The Upper limit for acceptable Output Voltage, per the UPS specifications.
1.3.6.1.4.1.534.1.10.7Integer32 (0..2147483647)read-onlycurrent
xupsConfigInstallDate
OBJECT-TYPE
The date when this UPS was installed. Free text format, so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc).
1.3.6.1.4.1.534.1.10.8DisplayString (SIZE(0..16))read-writecurrent
xupsTrapControl
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.11
xupsMaxTrapLevel
OBJECT-TYPE
The level of severity of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. Values are: (1) none: no traps will be sent to this host; (2) critical: only traps for Critical alarm conditions will be sent to this host; (3) major: Critical and Major traps will be sent; (4) minor: All levels of alarming traps will be sent: Critical, Major, and Minor (This level was added in PowerMIB v3.11) (5) allTraps: all Traps will be sent to this host (Critical, Major, Minor, Informational).
1.3.6.1.4.1.534.1.11.1INTEGER {none(1), critical(2), major(3), minor(4), allTraps(5)}read-writecurrent
xupsSendTrapType
OBJECT-TYPE
The type of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. The additional variables in types (3) and (4) are useful for determining which UPS is the source on multi-port network adapters, and for getting additional descriptive information. Types (1) through (4) are all SNMP version 1 trap PDUs. Values are: (1) stnd: Traps as defined in the Standard UPS MIB (RFC1628) and Generic (MIB II) traps as defined in RFC 1215. (2) xups: xupsTrapDefined Traps as defined in the PowerMIB and Generic (MIB II) traps as defined in RFC 1215. (3 Deprecated) stndPlus: same as stnd plus variables from the interface group and, where appropriate, xupsTrapMessage. (4 Deprecated) xupsPlus: xupsTrapPortN Traps (same as xups plus variables from the interface group) and, for authFail, xupsTrapMessage. (5 pxg: Traps as defined in the Power Xpert Gateway MIB (PXG-MIB).
1.3.6.1.4.1.534.1.11.2INTEGER {stnd(1), xups(2), stndPlus(3), xupsPlus(4), pxg(5)}read-writecurrent
xupsTrapMessage
OBJECT-TYPE
A descriptive text message which may be sent with traps to further explain the reason for the trap. This object is not-accessible to MIB browsers, but had to be changed to read-only to satisfy SMIv2 syntax checkers since it is included in traps.
1.3.6.1.4.1.534.1.11.3DisplayString (SIZE(0..79))read-onlycurrent
xupsTrapSource
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.11.4
xupsTrapDefined
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.11.4.1
xupsTrapOidDefined
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.11.4.1.0
xupsHeartbeatMinsInterval
OBJECT-TYPE
How often to send the xupstdHeartbeat trap, in units of minutes. A setting of 0 disables the Heartbeat function.
1.3.6.1.4.1.534.1.11.5Integer32 (0..2147483647)read-writecurrent
xupsRecep
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.12
xupsNumReceptacles
OBJECT-TYPE
The number of independently controllable Receptacles, as described in the xupsRecepTable.
1.3.6.1.4.1.534.1.12.1Integer32 (0..64)read-onlycurrent
xupsRecepTable
OBJECT-TYPE
A list of receptacle table entries. The number of entries is given by the value of xupsNumReceptacles.
1.3.6.1.4.1.534.1.12.2not-accessiblecurrent
xupsRecepEntry
OBJECT-TYPE
A receptacle table entry containing the status and control values for one receptacle.
1.3.6.1.4.1.534.1.12.2.1not-accessiblecurrent
xupsRecepIndex
OBJECT-TYPE
The number of the Receptacle. Serves as index for Receptacle table.
1.3.6.1.4.1.534.1.12.2.1.1Integer32 (1..64)read-onlycurrent
xupsRecepStatus
OBJECT-TYPE
The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 4=Off w/Pending ON, 5=Unknown, 6=Reserved for future, 7=Failed in Closed position, 8=Failed in Open position.
1.3.6.1.4.1.534.1.12.2.1.2INTEGER {on(1), off(2), pendingOff(3), pendingOn(4), unknown(5), reserved(6), failedClosed(7), failedOpen(8)}read-onlycurrent
xupsRecepOffDelaySecs
OBJECT-TYPE
The Delay until the Receptacle is turned Off. Setting this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending shutdown. When this object is set while the UPS is On Battery, it is not necessary to set xupsRecepOnDelaySecs, since the outlet will turn back on automatically when power is available again.
1.3.6.1.4.1.534.1.12.2.1.3Integer32 (-1..2147483647)read-writecurrent
xupsRecepOnDelaySecs
OBJECT-TYPE
The Delay until the Receptacle is turned On. Setting this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending restart.
1.3.6.1.4.1.534.1.12.2.1.4Integer32 (-1..2147483647)read-writecurrent
xupsRecepAutoOffDelay
OBJECT-TYPE
The delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappropriate. The AutoOffDelay can be used to prioritize loads in the event of a prolonged power outage; less critical loads will turn off earlier to extend battery time for the more critical loads. If the utility power is restored before the AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.
1.3.6.1.4.1.534.1.12.2.1.5Integer32 (-1..32767)read-writecurrent
xupsRecepAutoOnDelay
OBJECT-TYPE
Seconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to do so. A value of 0 means that the Receptacle should come On immediately at power-up or for an On command.
1.3.6.1.4.1.534.1.12.2.1.6Integer32 (-1..32767)read-writecurrent
xupsRecepShedSecsWithRestart
OBJECT-TYPE
Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsRecepOffDelaySecs, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted.
1.3.6.1.4.1.534.1.12.2.1.7Integer32 (0..2147483647)read-writecurrent
xupsRecepHourlyPowerUsage
OBJECT-TYPE
Units are Watt-hours.This is the energy consumed during the last hour.
1.3.6.1.4.1.534.1.12.2.1.8Integer32 (0..2147483647)read-onlycurrent
xupsRecepCumulativePowerUsage
OBJECT-TYPE
Units are Watt-hours.This is the energy consumed since the last reset. This object is writable so that it can be reset to 0. When it is written to 0, the xupsRecepCumulativePowerUsageTimer will be reset to 0 as well.
1.3.6.1.4.1.534.1.12.2.1.9Integer32 (0..2147483647)read-writecurrent
xupsRecepCumulativePowerUsageTimer
OBJECT-TYPE
Time in seconds since the cumulative power usage was last reset.
1.3.6.1.4.1.534.1.12.2.1.10Counter32read-onlycurrent
xupsTopology
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.13
xupsTopologyType
OBJECT-TYPE
Value which denotes the type of UPS by its power topology. Values are the same as those described in the XCP Topology block's Overall Topology field.
1.3.6.1.4.1.534.1.13.1Integer32 (0..32767)read-onlycurrent
xupsTopoMachineCode
OBJECT-TYPE
ID Value which denotes the Powerware model of the UPS for software. Values are the same as those described in the XCP Configuration block's Machine Code field.
1.3.6.1.4.1.534.1.13.2Integer32 (0..32767)read-onlycurrent
xupsTopoUnitNumber
OBJECT-TYPE
Identifies which unit and what type of data is being reported. A value of 0 means that this MIB information comes from the top-level system view (eg, manifold module or system bypass cabinet reporting total system output). Standalone units also use a value of 0, since they are the 'full system' view. A value of 1 or higher indicates the number of the module in the system which is reporting only its own data in the PowerMIB objects.
1.3.6.1.4.1.534.1.13.3Integer32 (0..64)read-onlycurrent
xupsTopoPowerStrategy
OBJECT-TYPE
Value which denotes which Power Strategy is currently set for the UPS. The values are: highAlert(1) - The UPS shall optimize its operating state to maximize its power-protection levels. This mode will be held for at most 24 hours. standard(2) - Balanced, normal power protection strategy. UPS will not enter HE operating mode from this setting. enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to optimize its operating state to maximize its efficiency, when conditions change to permit it (as determined by the UPS). forceHighEfficiency(4) - If this value is permitted to be Set for this UPS, and if conditions permit, requires the UPS to enter High Efficiency mode now, without delay (for as long as utility conditions permit). After successfully set to forceHighEfficiency(4), xupsTopoPowerStrategy changes to value enableHighEfficiency(3). xupsOutputSource will indicate if the UPS status is actually operating in High Efficiency mode.
1.3.6.1.4.1.534.1.13.4INTEGER {highAlert(1), standard(2), enableHighEfficiency(3), immediateHighEfficiency(4)}read-writecurrent
xupsAgent
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.14
xupsAgentManufacturer
OBJECT-TYPE
The card agent Manufacturer Name (e.g. Eaton Corporation).
1.3.6.1.4.1.534.1.14.1DisplayString (SIZE(0..31))read-onlycurrent
xupsAgentModel
OBJECT-TYPE
The card agent model
1.3.6.1.4.1.534.1.14.2DisplayString (SIZE(0..63))read-onlycurrent
xupsAgentSoftwareVersion
OBJECT-TYPE
The agent firmware version.
1.3.6.1.4.1.534.1.14.3DisplayString (SIZE(0..63))read-onlycurrent
xupsAgentPartNumber
OBJECT-TYPE
The card agent catalog part number.
1.3.6.1.4.1.534.1.14.4OCTET STRING (SIZE(1..31))read-onlycurrent
xupsAgentSerialNumber
OBJECT-TYPE
The card agent catalog serial number.
1.3.6.1.4.1.534.1.14.5OCTET STRING (SIZE(1..31))read-onlycurrent
xupsConformance
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.100

Notifications

NameOIDStatus
xupstdControlOff
NOTIFICATION-TYPE
The UPS output power will turn off in a number of seconds equal to upsControlOutputOffTrapDelay.
1.3.6.1.4.1.534.1.11.4.1.0.1current
xupstdControlOn
NOTIFICATION-TYPE
The UPS output power will turn on in a number of seconds equal to upsControlOutputOnTrapDelay.
1.3.6.1.4.1.534.1.11.4.1.0.2current
xupstdOnBattery
NOTIFICATION-TYPE
The UPS has no AC input power and is running on battery.
1.3.6.1.4.1.534.1.11.4.1.0.3current
xupstdLowBattery
NOTIFICATION-TYPE
The UPS batteries are low. Tied to low battery alarm condition.
1.3.6.1.4.1.534.1.11.4.1.0.4current
xupstdUtilityPowerRestored
NOTIFICATION-TYPE
Input power has been restored after running on battery.
1.3.6.1.4.1.534.1.11.4.1.0.5current
xupstdReturnFromLowBattery
NOTIFICATION-TYPE
The battery has recovered from a low battery condition.
1.3.6.1.4.1.534.1.11.4.1.0.6current
xupstdOutputOverload
NOTIFICATION-TYPE
The ups has sensed an overload of greater than 106 percent. Tied to the 106% overload alarm.
1.3.6.1.4.1.534.1.11.4.1.0.7current
xupstdInternalFailure
NOTIFICATION-TYPE
Some component of the ups - rectifier, inverter, control panel has failed. Tied to alarms indi- cating failure.
1.3.6.1.4.1.534.1.11.4.1.0.8current
xupstdBatteryDischarged
NOTIFICATION-TYPE
The Battery Totally Discharged Alarm has occurred.
1.3.6.1.4.1.534.1.11.4.1.0.9current
xupstdInverterFailure
NOTIFICATION-TYPE
The ups inverter is unavailable or malfunctioning due to an internal failure.
1.3.6.1.4.1.534.1.11.4.1.0.10current
xupstdOnBypass
NOTIFICATION-TYPE
The ups has gone on bypass for some reason.
1.3.6.1.4.1.534.1.11.4.1.0.11current
xupstdBypassNotAvailable
NOTIFICATION-TYPE
The ups bypass is unavailable
1.3.6.1.4.1.534.1.11.4.1.0.12current
xupstdOutputOff
NOTIFICATION-TYPE
The ups output is switched off.
1.3.6.1.4.1.534.1.11.4.1.0.13current
xupstdInputFailure
NOTIFICATION-TYPE
The ups input power is incorrect in voltage, frequency, or phase rotation.
1.3.6.1.4.1.534.1.11.4.1.0.14current
xupstdBuildingAlarm
NOTIFICATION-TYPE
One of the defined building alarms has occurred.
1.3.6.1.4.1.534.1.11.4.1.0.15current
xupstdShutdownImminent
NOTIFICATION-TYPE
The ups shutdown imminent alarm has occurred.
1.3.6.1.4.1.534.1.11.4.1.0.16current
xupstdOnInverter
NOTIFICATION-TYPE
The ups is returned to utility power running the inverter after either a transfer to bypass or a run on battery.
1.3.6.1.4.1.534.1.11.4.1.0.17current
xupstdBreakerOpen
NOTIFICATION-TYPE
One of the UPS breakers or contactors has been opened.
1.3.6.1.4.1.534.1.11.4.1.0.20current
xupstdAlarmEntryAdded
NOTIFICATION-TYPE
An alarm not defined in the xups Well Known Alarms (eg, an alarm defined in RFC1628) has been added to the Alarm Table.
1.3.6.1.4.1.534.1.11.4.1.0.21current
xupstdAlarmEntryRemoved
NOTIFICATION-TYPE
An alarm not defined in the xups Well Known Alarms has been removed from the Alarm Table.
1.3.6.1.4.1.534.1.11.4.1.0.22current
xupstdAlarmBatteryBad
NOTIFICATION-TYPE
One or more batteries have been determined to require replacement.
1.3.6.1.4.1.534.1.11.4.1.0.23current
xupstdOutputOffAsRequested
NOTIFICATION-TYPE
The UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.534.1.11.4.1.0.24current
xupstdDiagnosticTestFailed
NOTIFICATION-TYPE
The result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.534.1.11.4.1.0.25current
xupstdCommunicationsLost
NOTIFICATION-TYPE
A problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.4.1.534.1.11.4.1.0.26current
xupstdUpsShutdownPending
NOTIFICATION-TYPE
An xupsControlOutputOffDelay countdown is underway.
1.3.6.1.4.1.534.1.11.4.1.0.27current
xupstdAlarmTestInProgress
NOTIFICATION-TYPE
A test is in progress, as initiated and indicated by the xupsTest Group. When the test is complete, one of the following traps will be sent: - xupstdDiagnosticTestFailed if the test fails, - xupstdDiagnosticTestPassed on success, or - xupstdAlarmEntryRemoved in other cases (e.g., Test Canceled).
1.3.6.1.4.1.534.1.11.4.1.0.28current
xupstdAmbientTempBad
NOTIFICATION-TYPE
The ambient temperature, xupsEnvAmbientTemp, has fallen below the set lower limit, xupsEnvAmbientLowerLimit, or has risen above the set upper limit, xupsEnvAmbientUpperLimit.
1.3.6.1.4.1.534.1.11.4.1.0.29current
xupstdContactActiveNotice
NOTIFICATION-TYPE
The Contact indicated by xupsContactIndex is in its Active state. The following are the situations that generate this trap: For xupsContactType: and xupsContactState: normallyOpen(1) and closedWithNotice(4) normallyClosed(2) and openWithNotice(3) anyChange(3) and openWithNotice(3) or closedWithNotice(4)
1.3.6.1.4.1.534.1.11.4.1.0.30current
xupstdContactInactiveNotice
NOTIFICATION-TYPE
The Contact indicated by xupsContactIndex has changed to its Inactive state.
1.3.6.1.4.1.534.1.11.4.1.0.31current
xupstdLossOfRedundancy
NOTIFICATION-TYPE
A parallel UPS system is no longer operating in N+1 redundant mode; this may be due to module failure or removal, or due to overloading.
1.3.6.1.4.1.534.1.11.4.1.0.32current
xupstdAlarmTempBad
NOTIFICATION-TYPE
An internal temperature is out of tolerance.
1.3.6.1.4.1.534.1.11.4.1.0.33current
xupstdAlarmChargerFailed
NOTIFICATION-TYPE
An uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.534.1.11.4.1.0.34current
xupstdAlarmFanFailure
NOTIFICATION-TYPE
The failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.534.1.11.4.1.0.35current
xupstdAlarmFuseFailure
NOTIFICATION-TYPE
The failure of one or more fuses has been detected.
1.3.6.1.4.1.534.1.11.4.1.0.36current
xupstdPowerSwitchBad
NOTIFICATION-TYPE
A Relay, Contactor, or Breaker has failed.
1.3.6.1.4.1.534.1.11.4.1.0.37current
xupstdModuleFailure
NOTIFICATION-TYPE
One module in a parallel or composite system has failed.
1.3.6.1.4.1.534.1.11.4.1.0.38current
xupstdOnAlternatePowerSource
NOTIFICATION-TYPE
The system is being powered by its Alternate Power Source, such as a Secondary utility feed (on a dual AC input UPS), generator, flywheel, or fuel cell.
1.3.6.1.4.1.534.1.11.4.1.0.39current
xupstdAltPowerNotAvailable
NOTIFICATION-TYPE
On systems with a separate alternate power source (eg, dual AC inputs), that alternate power source is currently not available. This could be a problem if the primary power source (eg, utility) fails for a period of time longer than that for which the internal batteries can supply power.
1.3.6.1.4.1.534.1.11.4.1.0.40current
xupstdNoticeCondition
NOTIFICATION-TYPE
Some Notice condition exists which is not covered by the other traps. This is like an xupstdInternalFailure, but at a lower severity level.
1.3.6.1.4.1.534.1.11.4.1.0.41current
xupstdRemoteTempBad
NOTIFICATION-TYPE
The remote temperature, xupsEnvRemoteTemp, has fallen below the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above the set upper limit, xupsEnvRemoteTempUpperLimit.
1.3.6.1.4.1.534.1.11.4.1.0.42current
xupstdRemoteHumidityBad
NOTIFICATION-TYPE
The remote temperature, xupsEnvRemoteHumidity, has fallen below the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above the set upper limit, xupsEnvRemoteHumidityUpperLimit.
1.3.6.1.4.1.534.1.11.4.1.0.43current
xupstdHeartbeat
NOTIFICATION-TYPE
A periodic status trap message. It is sent at an interval set by object xupsHeartbeatMinsInterval. The included variables provide a brief statement of the UPS status.
1.3.6.1.4.1.534.1.11.4.1.0.44current
xupstdDiagnosticTestPassed
NOTIFICATION-TYPE
A diagnostic test just completed, and its result is Passed. The included variables provide additional information on the test.
1.3.6.1.4.1.534.1.11.4.1.0.45current
xupstdOutputBad
NOTIFICATION-TYPE
The output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.534.1.11.4.1.0.46current
xupstdAwaitingPower
NOTIFICATION-TYPE
The UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.4.1.534.1.11.4.1.0.47current
xupstdOnMaintenanceBypass
NOTIFICATION-TYPE
The UPS has been placed on Maintenance / Manual Bypass by an operator.
1.3.6.1.4.1.534.1.11.4.1.0.48current
xupstdCommEstablished
NOTIFICATION-TYPE
This trap is sent when the SNMP agent first establishes a communication link with the UPS. The included variables provide identification and UPS status information.
1.3.6.1.4.1.534.1.11.4.1.0.49current
xupstdAgentDown
NOTIFICATION-TYPE
This trap is sent when the SNMP agent is exiting or closing down gracefully. This may be triggered by a signal from the OS to stop this process. In many implementations, it will be followed quickly by a restart of this vital process.
1.3.6.1.4.1.534.1.11.4.1.0.50current
xupstdOutputNotProtected
NOTIFICATION-TYPE
The ups output is not protectet for any reason in the UPS.
1.3.6.1.4.1.534.1.11.4.1.0.51current
xupstdTestTrap
NOTIFICATION-TYPE
This trap is sent to the trap receivers to check proper reception of traps.
1.3.6.1.4.1.534.1.11.4.1.0.100current

Conformance

NameOIDStatus
xupsIdentFullGroup
OBJECT-GROUP
The Full set of xupsIdent subgroup objects.
1.3.6.1.4.1.534.1.100.2current
xupsBatteryFullGroup
OBJECT-GROUP
The Full set of xupsBattery subgroup objects.
1.3.6.1.4.1.534.1.100.3current
xupsInputFullGroup
OBJECT-GROUP
The Full set of xupsInput subgroup objects.
1.3.6.1.4.1.534.1.100.4current
xupsInputTableFullGroup
OBJECT-GROUP
The Full set of xupsInputTable subgroup objects.
1.3.6.1.4.1.534.1.100.5current
xupsOutputFullGroup
OBJECT-GROUP
The Full set of xupsOutput subgroup objects.
1.3.6.1.4.1.534.1.100.6current
xupsOutputTableFullGroup
OBJECT-GROUP
The Full set of xupsOutputTable subgroup objects.
1.3.6.1.4.1.534.1.100.7current
xupsBypassFullGroup
OBJECT-GROUP
The Full set of xupsBypass subgroup objects.
1.3.6.1.4.1.534.1.100.8current
xupsEnvironmentFullGroup
OBJECT-GROUP
The Full set of xupsEnvironment subgroup objects.
1.3.6.1.4.1.534.1.100.9current
xupsAlarmFullGroup
OBJECT-GROUP
The Full set of xupsAlarm subgroup objects.
1.3.6.1.4.1.534.1.100.10current
xupsAlarmEventsFullGroup
OBJECT-GROUP
The Full set of Alarm/Event history subgroup objects.
1.3.6.1.4.1.534.1.100.11current
xupsTestFullGroup
OBJECT-GROUP
The Full set of xupsTest subgroup objects.
1.3.6.1.4.1.534.1.100.12current
xupsControlFullGroup
OBJECT-GROUP
The Full set of xupsControl subgroup objects.
1.3.6.1.4.1.534.1.100.13current
xupsConfigFullGroup
OBJECT-GROUP
The Full set of xupsConfig subgroup objects.
1.3.6.1.4.1.534.1.100.14current
xupsTrapControlFullGroup
OBJECT-GROUP
The Full set of xupsTrapControl subgroup objects.
1.3.6.1.4.1.534.1.100.15current
xupsRecepFullGroup
OBJECT-GROUP
The Full set of xupsRecep subgroup objects.
1.3.6.1.4.1.534.1.100.16current
xupsTopologyFullGroup
OBJECT-GROUP
The Full set of xupsTopology subgroup objects.
1.3.6.1.4.1.534.1.100.17current
xupstdNotifyGroup
NOTIFICATION-GROUP
The Alarm and Event notifications from the xupsTrapDefined source (xupstd).
1.3.6.1.4.1.534.1.100.18current
xupstdEMPNotifyGroup
NOTIFICATION-GROUP
The EMP's Alarm and Event notifications from the xupsTrapDefined source (xupstd).
1.3.6.1.4.1.534.1.100.19current
xupsMibFullCompliance
MODULE-COMPLIANCE
A compliance statement for all of everything in this MIB.
1.3.6.1.4.1.534.1.100.20current
xupsDeprecatedGroup
OBJECT-GROUP
Contains objects which are now deprecated.
1.3.6.1.4.1.534.1.100.21deprecated
xupsBypassTableFullGroup
OBJECT-GROUP
The Full set of xupsBypassTable subgroup objects.
1.3.6.1.4.1.534.1.100.22current
xupsInputTotalFullGroup
OBJECT-GROUP
The Full set of xupsInputTotal subgroup objects.
1.3.6.1.4.1.534.1.100.23current
xupsOutputTotalFullGroup
OBJECT-GROUP
The Full set of xupsOutputTotal subgroup objects.
1.3.6.1.4.1.534.1.100.24current
xupsBypassTotalFullGroup
OBJECT-GROUP
The Full set of xupsOutputTotal subgroup objects.
1.3.6.1.4.1.534.1.100.25current
xupsAgentFullGroup
OBJECT-GROUP
The Full set of xupsAgent subgroup objects.
1.3.6.1.4.1.534.1.100.26current