MIBs Depot

EATON-EMP-MIB

Registered at
1.3.6.1.4.1.534.1.6.0
Last updated
2007-03-12 00:00
Organization
Eaton Corporation
Revisions
2007-03-12 00:00
Namespace
eaton
Source file
EATON-EMP-MIB
Digest
sha256:a3071c053b7216e267e95f17adba1f7cdbc8ba6efdbc55f59e8bbb6fb3db52de

Description

The MIB module for Eaton Environment Monitoring Probes (EMP). The elements of this MIB have been extracted from the Eaton PowerMIB and placed in this separate MIB file for convenience. Copyright (C) Eaton Corporation (2007).

Contact

Eaton Power Quality Technical Support (PQTS) group www.eaton.com/powerxpert Technical Resource Center phone numbers United States: 1.800.843.9433 or 919.870.3028 Canada: 1.800.461.9166 ext. 260 All other countries: Call your local service representative.

Imports

FromSymbols
EATON-OIDSxupsEnvironment
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-SMIInteger32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

1 module(s) in this corpus import this one.

Load order

Every file a consumer needs in order to load this module, dependencies first.

EATON-EMP-MIB
EATON-OIDS
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
eatonEMPConformance
OBJECT-IDENTITY
1.3.6.1.4.1.534.1.6.0.2
xupsEnvRemoteTemp
OBJECT-TYPE
The reading of an EMP's temperature sensor.
1.3.6.1.4.1.534.1.6.5Integer32 (-100..200)read-onlycurrent
xupsEnvRemoteHumidity
OBJECT-TYPE
The reading of an EMP's humidity sensor.
1.3.6.1.4.1.534.1.6.6Integer32 (0..100)read-onlycurrent
xupsEnvNumContacts
OBJECT-TYPE
The number of Contacts in the xupsContactSenseTable. This object indicates the number of rows in the xupsContactSenseTable.
1.3.6.1.4.1.534.1.6.7Integer32 (1..1024)read-onlycurrent
xupsContactSenseTable
OBJECT-TYPE
A list of Contact Sensing table entries. The number of entries is given by the value of xupsEnvNumContacts.
1.3.6.1.4.1.534.1.6.8not-accessiblecurrent
xupsContactsTableEntry
OBJECT-TYPE
An entry containing information applicable to a particular Contact input.
1.3.6.1.4.1.534.1.6.8.1not-accessiblecurrent
xupsContactIndex
OBJECT-TYPE
The Contact identifier; identical to the Contact Number. This object is not-accessible to MIB browsers, but had to be changed to read-only to satisfy SMIv2 syntax checkers if it is included in traps.
1.3.6.1.4.1.534.1.6.8.1.1Integer32 (1..1024)read-onlycurrent
xupsContactType
OBJECT-TYPE
The normal state for this contact. The 'other' (not 'Normally') state is the Active state for generating the xupstdContactActiveNotice trap. If anyChange(3) is selected, then this trap is sent any time the contact changes to either Open or Closed. No traps are sent if the Contact is set to notUsed(4). In many cases, the configuration for Contacts may be done by other means, so this object may be read-only.
1.3.6.1.4.1.534.1.6.8.1.2INTEGER {normallyOpen(1), normallyClosed(2), anyChange(3), notUsed(4)}read-writecurrent
xupsContactState
OBJECT-TYPE
The current state of the Contact input; the value is based on the open/closed input state and the setting for xupsContactType. When entering the openWithNotice(3) and closedWithNotice(4) states, no entries added to the xupsAlarmTable, but the xupstdContactActiveNotice trap is sent.
1.3.6.1.4.1.534.1.6.8.1.3INTEGER {open(1), closed(2), openWithNotice(3), closedWithNotice(4)}read-onlycurrent
xupsContactDescr
OBJECT-TYPE
A label identifying the Contact. This object should be set by the administrator.
1.3.6.1.4.1.534.1.6.8.1.4DisplayString (SIZE(0..63))read-writecurrent
xupsEnvRemoteTempLowerLimit
OBJECT-TYPE
The Lower Limit of the EMP temperature; if xupsEnvRemoteTemp falls below this value, the xupsRemoteTempBad alarm will occur.
1.3.6.1.4.1.534.1.6.9Integer32 (-100..200)read-writecurrent
xupsEnvRemoteTempUpperLimit
OBJECT-TYPE
The Upper Limit of the EMP temperature; if xupsEnvRemoteTemp rises above this value, the xupsRemoteTempBad alarm will occur. This value should be greater than xupsEnvRemoteTempLowerLimit.
1.3.6.1.4.1.534.1.6.10Integer32 (-100..200)read-writecurrent
xupsEnvRemoteHumidityLowerLimit
OBJECT-TYPE
The Lower Limit of the EMP humidity reading; if xupsEnvRemoteHumidity falls below this value, the xupsRemoteHumidityBad alarm will occur.
1.3.6.1.4.1.534.1.6.11Integer32 (0..100)read-writecurrent
xupsEnvRemoteHumidityUpperLimit
OBJECT-TYPE
The Upper Limit of the EMP humidity reading; if xupsEnvRemoteHumidity rises above this value, the xupsRemoteHumidityBad alarm will occur. This value should be greater than xupsEnvRemoteHumidityLowerLimit.
1.3.6.1.4.1.534.1.6.12Integer32 (0..100)read-writecurrent

Conformance

NameOIDStatus
eatonEMPGroup
OBJECT-GROUP
The EMP scalar objects.
1.3.6.1.4.1.534.1.6.0.2.1current
eatonEMPTableGroup
OBJECT-GROUP
The EMP Contacts Table objects.
1.3.6.1.4.1.534.1.6.0.2.2current
eatonEMPSimpleCompliance
MODULE-COMPLIANCE
The compliance statement for a normal EMP.
1.3.6.1.4.1.534.1.6.0.2.4current