MIBs Depot

Sentry4-MIB

Registered at
1.3.6.1.4.1.1718
Last updated
2017-06-15 18:30
Organization
Server Technology, Inc.
Revisions
2017-06-15 18:30, 2016-11-18 23:40, 2016-09-21 23:00, 2016-04-25 21:40, 2015-02-19 10:00, 2014-12-23 11:30
Namespace
sentry
Source file
Sentry4-MIB
Digest
sha256:0121e46153b69a64278685825f46e98a9101bd337b53f054656bb073fc5827f3

Description

This is the MIB module for the fourth generation of the Sentry product family. This includes the PRO1 and PRO2 series of Smart and Switched Cabinet Distribution Unit (CDU) and Power Distribution Unit (PDU) products.

Contact

Server Technology, Inc. 1040 Sandhill Road Reno, NV 89521 Tel: (775) 284-2000 Fax: (775) 284-2065 Email: mibmaster@servertech.com

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-SMIInteger32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC
Sentry4-MIB

Under this module's arcs

Where the registration tree carries on below this module.

ArcNameModule
1.3.6.1.4.1.1718.3sentry3Sentry3-MIB

Textual conventions

NameOIDSyntaxAccessStatus
DeviceState
TEXTUAL-CONVENTION
On or off state of devices.
current
DeviceStatus
TEXTUAL-CONVENTION
Status returned by devices.
current
EventNotificationMethods
TEXTUAL-CONVENTION
Bits to enable event notification methods.
current

Objects

NameOIDSyntaxAccessStatus
serverTech
OBJECT-IDENTITY
1.3.6.1.4.1.1718
st4Objects
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1
st4System
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.1
st4SystemConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.1.1
st4SystemProductName
OBJECT-TYPE
The product name.
1.3.6.1.4.1.1718.4.1.1.1.1DisplayString (SIZE(0..63))read-onlycurrent
st4SystemLocation
OBJECT-TYPE
The location of the system.
1.3.6.1.4.1.1718.4.1.1.1.2DisplayString (SIZE(0..63))read-writecurrent
st4SystemFirmwareVersion
OBJECT-TYPE
The firmware version.
1.3.6.1.4.1.1718.4.1.1.1.3DisplayString (SIZE(0..63))read-onlycurrent
st4SystemFirmwareBuildInfo
OBJECT-TYPE
The firmware build information.
1.3.6.1.4.1.1718.4.1.1.1.4DisplayString (SIZE(0..63))read-onlycurrent
st4SystemNICSerialNumber
OBJECT-TYPE
The serial number of the network interface card.
1.3.6.1.4.1.1718.4.1.1.1.5DisplayString (SIZE(0..8))read-onlycurrent
st4SystemNICHardwareInfo
OBJECT-TYPE
Hardware information about the network interface card.
1.3.6.1.4.1.1718.4.1.1.1.6DisplayString (SIZE(0..63))read-onlycurrent
st4SystemProductSeries
OBJECT-TYPE
The product series.
1.3.6.1.4.1.1718.4.1.1.1.7INTEGER {pro1(0), pro2(1)}read-onlycurrent
st4SystemFeatures
OBJECT-TYPE
The key-activated features enabled in the system.
1.3.6.1.4.1.1718.4.1.1.1.10Bits {smartLoadShedding(0), reserved(1), outletControlInhibit(2)}read-onlycurrent
st4SystemFeatureKey
OBJECT-TYPE
A valid feature key written to this object will enable a feature in the system. A valid feature key is in the form xxxx-xxxx-xxxx-xxxx. A read of this object returns an empty string.
1.3.6.1.4.1.1718.4.1.1.1.11DisplayString (SIZE(0..19))read-writecurrent
st4SystemConfigModifiedCount
OBJECT-TYPE
The total number of times the system configuration has changed.
1.3.6.1.4.1.1718.4.1.1.1.20Integer32 (0..2147483647)read-onlycurrent
st4SystemUnitCount
OBJECT-TYPE
The number of units in the system.
1.3.6.1.4.1.1718.4.1.1.1.21Integer32 (0..8)read-onlycurrent
st4Units
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.2
st4UnitCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.2.1
st4UnitConfigTable
OBJECT-TYPE
Unit configuration table.
1.3.6.1.4.1.1718.4.1.2.2not-accessiblecurrent
st4UnitConfigEntry
OBJECT-TYPE
Configuration objects for a particular unit.
1.3.6.1.4.1.1718.4.1.2.2.1not-accessiblecurrent
st4UnitIndex
OBJECT-TYPE
Unit index. A=1, B=2, C=3, D=4, E=5, F=6.
1.3.6.1.4.1.1718.4.1.2.2.1.1Integer32 (1..6)not-accessiblecurrent
st4UnitID
OBJECT-TYPE
The internal ID of the unit. Format=A.
1.3.6.1.4.1.1718.4.1.2.2.1.2DisplayString (SIZE(1))read-onlycurrent
st4UnitName
OBJECT-TYPE
The name of the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.3DisplayString (SIZE(0..32))read-writecurrent
st4UnitProductSN
OBJECT-TYPE
The product serial number of the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.4DisplayString (SIZE(0..32))read-onlycurrent
st4UnitModel
OBJECT-TYPE
The model of the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.5DisplayString (SIZE(0..32))read-onlycurrent
st4UnitAssetTag
OBJECT-TYPE
The asset tag of the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.6DisplayString (SIZE(0..32))read-writecurrent
st4UnitType
OBJECT-TYPE
The type of the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.7INTEGER {masterPdu(0), linkPdu(1), controller(2), emcu(3)}read-onlycurrent
st4UnitCapabilities
OBJECT-TYPE
The capabilities of the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.8Bits {dc(0), phase3(1), wye(2), delta(3)}read-onlycurrent
st4UnitProductMfrDate
OBJECT-TYPE
The product manufacture date in YYYY-MM-DD (ISO 8601 format) of the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.9DisplayString (SIZE(0..10))read-onlycurrent
st4UnitDisplayOrientation
OBJECT-TYPE
The orientation of all displays in the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.20INTEGER {normal(0), inverted(1), auto(2)}read-writecurrent
st4UnitOutletSequenceOrder
OBJECT-TYPE
The sequencing order of all outlets in the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.21INTEGER {normal(0), reversed(1)}read-writecurrent
st4UnitOutletDisplayOrder
OBJECT-TYPE
The display order in the user interfaces of all outlets in the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.22INTEGER {normal(0), reversed(1)}read-writecurrent
st4UnitInputCordCount
OBJECT-TYPE
The number of power input cords into the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.30Integer32 (0..4)read-onlycurrent
st4UnitTempSensorCount
OBJECT-TYPE
The number of external temperature sensors supported by the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.31Integer32 (0..2)read-onlycurrent
st4UnitHumidSensorCount
OBJECT-TYPE
The number of external humidity sensors supported by the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.32Integer32 (0..2)read-onlycurrent
st4UnitWaterSensorCount
OBJECT-TYPE
The number of external water sensors supported by the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.33Integer32 (0..1)read-onlycurrent
st4UnitCcSensorCount
OBJECT-TYPE
The number of external contact closure sensors supported by the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.34Integer32 (0..4)read-onlycurrent
st4UnitAdcSensorCount
OBJECT-TYPE
The number of analog-to-digital converter sensors supported by the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.35Integer32 (0..1)read-onlycurrent
st4UnitFanSensorCount
OBJECT-TYPE
The number of fan sensors supported by the unit.
1.3.6.1.4.1.1718.4.1.2.2.1.36Integer32 (0..4)read-onlycurrent
st4UnitMonitorTable
OBJECT-TYPE
Unit monitor table.
1.3.6.1.4.1.1718.4.1.2.3not-accessiblecurrent
st4UnitMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular unit.
1.3.6.1.4.1.1718.4.1.2.3.1not-accessiblecurrent
st4UnitStatus
OBJECT-TYPE
The status of the unit.
1.3.6.1.4.1.1718.4.1.2.3.1.1DeviceStatusread-onlycurrent
st4UnitEventConfigTable
OBJECT-TYPE
Unit event configuration table.
1.3.6.1.4.1.1718.4.1.2.4not-accessiblecurrent
st4UnitEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular unit.
1.3.6.1.4.1.1718.4.1.2.4.1not-accessiblecurrent
st4UnitNotifications
OBJECT-TYPE
The notification methods enabled for unit events.
1.3.6.1.4.1.1718.4.1.2.4.1.1EventNotificationMethodsread-writecurrent
st4InputCords
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.3
st4InputCordCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.3.1
st4InputCordActivePowerHysteresis
OBJECT-TYPE
The active power hysteresis of the input cord in Watts.
1.3.6.1.4.1.1718.4.1.3.1.1Integer32 (0..1000)read-writecurrent
st4InputCordApparentPowerHysteresis
OBJECT-TYPE
The apparent power hysteresis of the input cord in Volt-Amps.
1.3.6.1.4.1.1718.4.1.3.1.2Integer32 (0..1000)read-writecurrent
st4InputCordPowerFactorHysteresis
OBJECT-TYPE
The power factor hysteresis of the input cord in hundredths.
1.3.6.1.4.1.1718.4.1.3.1.3Integer32 (0..20)read-writecurrent
st4InputCordOutOfBalanceHysteresis
OBJECT-TYPE
The 3 phase out-of-balance hysteresis of the input cord in percent.
1.3.6.1.4.1.1718.4.1.3.1.4Integer32 (0..10)read-writecurrent
st4InputCordConfigTable
OBJECT-TYPE
Input cord configuration table.
1.3.6.1.4.1.1718.4.1.3.2not-accessiblecurrent
st4InputCordConfigEntry
OBJECT-TYPE
Configuration objects for a particular input cord.
1.3.6.1.4.1.1718.4.1.3.2.1not-accessiblecurrent
st4InputCordIndex
OBJECT-TYPE
Input cord index. A=1, B=2, C=3, D=4.
1.3.6.1.4.1.1718.4.1.3.2.1.1Integer32 (1..4)not-accessiblecurrent
st4InputCordID
OBJECT-TYPE
The internal ID of the input cord. Format=AA.
1.3.6.1.4.1.1718.4.1.3.2.1.2DisplayString (SIZE(2))read-onlycurrent
st4InputCordName
OBJECT-TYPE
The name of the input cord.
1.3.6.1.4.1.1718.4.1.3.2.1.3DisplayString (SIZE(0..32))read-writecurrent
st4InputCordInletType
OBJECT-TYPE
The type of plug on the input cord, or socket for the input cord.
1.3.6.1.4.1.1718.4.1.3.2.1.6DisplayString (SIZE(0..32))read-onlycurrent
st4InputCordNominalVoltage
OBJECT-TYPE
The user-configured nominal voltage of the input cord in tenth Volts.
1.3.6.1.4.1.1718.4.1.3.2.1.7Integer32 (0..6000)read-writecurrent
st4InputCordNominalVoltageMin
OBJECT-TYPE
The factory-set minimum allowed for the user-configured nominal voltage of the input cord in Volts.
1.3.6.1.4.1.1718.4.1.3.2.1.8Integer32 (0..600)read-onlycurrent
st4InputCordNominalVoltageMax
OBJECT-TYPE
The factory-set maximum allowed for the user-configured nominal voltage of the input cord in Volts.
1.3.6.1.4.1.1718.4.1.3.2.1.9Integer32 (0..600)read-onlycurrent
st4InputCordCurrentCapacity
OBJECT-TYPE
The user-configured current capacity of the input cord in Amps.
1.3.6.1.4.1.1718.4.1.3.2.1.10Integer32 (0..600)read-writecurrent
st4InputCordCurrentCapacityMax
OBJECT-TYPE
The factory-set maximum allowed for the user-configured current capacity of the input cord in Amps.
1.3.6.1.4.1.1718.4.1.3.2.1.11Integer32 (0..600)read-onlycurrent
st4InputCordPowerCapacity
OBJECT-TYPE
The power capacity of the input cord in Volt-Amps. For DC products, this is identical to power capacity in Watts.
1.3.6.1.4.1.1718.4.1.3.2.1.12Integer32 (0..50000)read-onlycurrent
st4InputCordNominalPowerFactor
OBJECT-TYPE
The user-configured estimated nominal power factor of the input cord in hundredths.
1.3.6.1.4.1.1718.4.1.3.2.1.13Integer32 (0..100)read-writecurrent
st4InputCordLineCount
OBJECT-TYPE
The number of current-carrying lines in the input cord.
1.3.6.1.4.1.1718.4.1.3.2.1.20Integer32 (0..4)read-onlycurrent
st4InputCordPhaseCount
OBJECT-TYPE
The number of active phases from the lines in the input cord.
1.3.6.1.4.1.1718.4.1.3.2.1.21Integer32 (0..6)read-onlycurrent
st4InputCordOcpCount
OBJECT-TYPE
The number of over-current protectors downstream from the input cord.
1.3.6.1.4.1.1718.4.1.3.2.1.22Integer32 (0..12)read-onlycurrent
st4InputCordBranchCount
OBJECT-TYPE
The number of branches downstream from the input cord.
1.3.6.1.4.1.1718.4.1.3.2.1.23Integer32 (0..12)read-onlycurrent
st4InputCordOutletCount
OBJECT-TYPE
The number of outlets powered from the input cord.
1.3.6.1.4.1.1718.4.1.3.2.1.24Integer32 (0..128)read-onlycurrent
st4InputCordMonitorTable
OBJECT-TYPE
Input cord monitor table.
1.3.6.1.4.1.1718.4.1.3.3not-accessiblecurrent
st4InputCordMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular input cord.
1.3.6.1.4.1.1718.4.1.3.3.1not-accessiblecurrent
st4InputCordState
OBJECT-TYPE
The on/off state of the input cord.
1.3.6.1.4.1.1718.4.1.3.3.1.1DeviceStateread-onlycurrent
st4InputCordStatus
OBJECT-TYPE
The status of the input cord.
1.3.6.1.4.1.1718.4.1.3.3.1.2DeviceStatusread-onlycurrent
st4InputCordActivePower
OBJECT-TYPE
The measured active power of the input cord in Watts.
1.3.6.1.4.1.1718.4.1.3.3.1.3Integer32 (-1..50000)read-onlycurrent
st4InputCordActivePowerStatus
OBJECT-TYPE
The status of the measured active power of the input cord.
1.3.6.1.4.1.1718.4.1.3.3.1.4DeviceStatusread-onlycurrent
st4InputCordApparentPower
OBJECT-TYPE
The measured apparent power of the input cord in Volt-Amps.
1.3.6.1.4.1.1718.4.1.3.3.1.5Integer32 (-1..50000)read-onlycurrent
st4InputCordApparentPowerStatus
OBJECT-TYPE
The status of the measured apparent power of the input cord.
1.3.6.1.4.1.1718.4.1.3.3.1.6DeviceStatusread-onlycurrent
st4InputCordPowerUtilized
OBJECT-TYPE
The amount of the input cord power capacity used in tenth percent. For AC products, this is the ratio of the apparent power to the power capacity. For DC products, this is the ratio of the active power to the power capacity.
1.3.6.1.4.1.1718.4.1.3.3.1.7Integer32 (-1..1200)read-onlycurrent
st4InputCordPowerFactor
OBJECT-TYPE
The measured power factor of the input cord in hundredths.
1.3.6.1.4.1.1718.4.1.3.3.1.8Integer32 (-1..100)read-onlycurrent
st4InputCordPowerFactorStatus
OBJECT-TYPE
The status of the measured power factor of the input cord.
1.3.6.1.4.1.1718.4.1.3.3.1.9DeviceStatusread-onlycurrent
st4InputCordEnergy
OBJECT-TYPE
The total energy consumption of loads through the input cord in tenth Kilowatt-Hours.
1.3.6.1.4.1.1718.4.1.3.3.1.10Integer32 (-1..2147483647)read-onlycurrent
st4InputCordFrequency
OBJECT-TYPE
The frequency of the input cord voltage in tenth Hertz.
1.3.6.1.4.1.1718.4.1.3.3.1.11Integer32 (-1..1000)read-onlycurrent
st4InputCordOutOfBalance
OBJECT-TYPE
The current imbalance on the lines of the input cord in tenth percent.
1.3.6.1.4.1.1718.4.1.3.3.1.12Integer32 (-1..2000)read-onlycurrent
st4InputCordOutOfBalanceStatus
OBJECT-TYPE
The status of the current imbalance on the lines of the input cord.
1.3.6.1.4.1.1718.4.1.3.3.1.13DeviceStatusread-onlycurrent
st4InputCordEventConfigTable
OBJECT-TYPE
Input cord event configuration table.
1.3.6.1.4.1.1718.4.1.3.4not-accessiblecurrent
st4InputCordEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular input cord.
1.3.6.1.4.1.1718.4.1.3.4.1not-accessiblecurrent
st4InputCordNotifications
OBJECT-TYPE
The notification methods enabled for input cord events.
1.3.6.1.4.1.1718.4.1.3.4.1.1EventNotificationMethodsread-writecurrent
st4InputCordActivePowerLowAlarm
OBJECT-TYPE
The active power low alarm threshold of the input cord in Watts.
1.3.6.1.4.1.1718.4.1.3.4.1.2Integer32 (0..50000)read-writecurrent
st4InputCordActivePowerLowWarning
OBJECT-TYPE
The active power low warning threshold of the input cord in Watts.
1.3.6.1.4.1.1718.4.1.3.4.1.3Integer32 (0..50000)read-writecurrent
st4InputCordActivePowerHighWarning
OBJECT-TYPE
The active power high warning threshold of the input cord in Watts.
1.3.6.1.4.1.1718.4.1.3.4.1.4Integer32 (0..50000)read-writecurrent
st4InputCordActivePowerHighAlarm
OBJECT-TYPE
The active power high alarm threshold of the input cord in Watts.
1.3.6.1.4.1.1718.4.1.3.4.1.5Integer32 (0..50000)read-writecurrent
st4InputCordApparentPowerLowAlarm
OBJECT-TYPE
The apparent power low alarm threshold of the input cord in Volt-Amps.
1.3.6.1.4.1.1718.4.1.3.4.1.6Integer32 (0..50000)read-writecurrent
st4InputCordApparentPowerLowWarning
OBJECT-TYPE
The apparent power low warning threshold of the input cord in Volt-Amps.
1.3.6.1.4.1.1718.4.1.3.4.1.7Integer32 (0..50000)read-writecurrent
st4InputCordApparentPowerHighWarning
OBJECT-TYPE
The apparent power high warning threshold of the input cord in Volt-Amps.
1.3.6.1.4.1.1718.4.1.3.4.1.8Integer32 (0..50000)read-writecurrent
st4InputCordApparentPowerHighAlarm
OBJECT-TYPE
The apparent power high alarm threshold of the input cord in Volt-Amps.
1.3.6.1.4.1.1718.4.1.3.4.1.9Integer32 (0..50000)read-writecurrent
st4InputCordPowerFactorLowAlarm
OBJECT-TYPE
The power factor low alarm threshold of the input cord in hundredths.
1.3.6.1.4.1.1718.4.1.3.4.1.10Integer32 (0..100)read-writecurrent
st4InputCordPowerFactorLowWarning
OBJECT-TYPE
The power factor low warning threshold of the input cord in hundredths.
1.3.6.1.4.1.1718.4.1.3.4.1.11Integer32 (0..100)read-writecurrent
st4InputCordOutOfBalanceHighWarning
OBJECT-TYPE
The 3 phase out-of-balance high warning threshold of the input cord in percent.
1.3.6.1.4.1.1718.4.1.3.4.1.12Integer32 (0..100)read-writecurrent
st4InputCordOutOfBalanceHighAlarm
OBJECT-TYPE
The 3 phase out-of-balance high alarm threshold of the input cord in percent.
1.3.6.1.4.1.1718.4.1.3.4.1.13Integer32 (0..100)read-writecurrent
st4Lines
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.4
st4LineCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.4.1
st4LineCurrentHysteresis
OBJECT-TYPE
The current hysteresis of the line in tenth Amps.
1.3.6.1.4.1.1718.4.1.4.1.1Integer32 (0..100)read-writecurrent
st4LineConfigTable
OBJECT-TYPE
Line configuration table.
1.3.6.1.4.1.1718.4.1.4.2not-accessiblecurrent
st4LineConfigEntry
OBJECT-TYPE
Configuration objects for a particular line.
1.3.6.1.4.1.1718.4.1.4.2.1not-accessiblecurrent
st4LineIndex
OBJECT-TYPE
Line index. L1=1, L2=2, L3=3, N=4.
1.3.6.1.4.1.1718.4.1.4.2.1.1Integer32 (1..4)not-accessiblecurrent
st4LineID
OBJECT-TYPE
The internal ID of the line. Format=AAN.
1.3.6.1.4.1.1718.4.1.4.2.1.2DisplayString (SIZE(3))read-onlycurrent
st4LineLabel
OBJECT-TYPE
The system label assigned to the line for identification.
1.3.6.1.4.1.1718.4.1.4.2.1.4DisplayString (SIZE(0..32))read-onlycurrent
st4LineCurrentCapacity
OBJECT-TYPE
The current capacity of the line in Amps.
1.3.6.1.4.1.1718.4.1.4.2.1.6Integer32 (0..600)read-onlycurrent
st4LineMonitorTable
OBJECT-TYPE
Line monitor table.
1.3.6.1.4.1.1718.4.1.4.3not-accessiblecurrent
st4LineMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular line.
1.3.6.1.4.1.1718.4.1.4.3.1not-accessiblecurrent
st4LineState
OBJECT-TYPE
The on/off state of the line.
1.3.6.1.4.1.1718.4.1.4.3.1.1DeviceStateread-onlycurrent
st4LineStatus
OBJECT-TYPE
The status of the line.
1.3.6.1.4.1.1718.4.1.4.3.1.2DeviceStatusread-onlycurrent
st4LineCurrent
OBJECT-TYPE
The measured current on the line in hundredth Amps.
1.3.6.1.4.1.1718.4.1.4.3.1.3Integer32 (-1..60000)read-onlycurrent
st4LineCurrentStatus
OBJECT-TYPE
The status of the measured current on the line.
1.3.6.1.4.1.1718.4.1.4.3.1.4DeviceStatusread-onlycurrent
st4LineCurrentUtilized
OBJECT-TYPE
The amount of the line current capacity used in tenth percent.
1.3.6.1.4.1.1718.4.1.4.3.1.5Integer32 (-1..1200)read-onlycurrent
st4LineEventConfigTable
OBJECT-TYPE
Line event configuration table.
1.3.6.1.4.1.1718.4.1.4.4not-accessiblecurrent
st4LineEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular line.
1.3.6.1.4.1.1718.4.1.4.4.1not-accessiblecurrent
st4LineNotifications
OBJECT-TYPE
The notification methods enabled for line events.
1.3.6.1.4.1.1718.4.1.4.4.1.1EventNotificationMethodsread-writecurrent
st4LineCurrentLowAlarm
OBJECT-TYPE
The current low alarm threshold of the line in tenth Amps.
1.3.6.1.4.1.1718.4.1.4.4.1.2Integer32 (0..6000)read-writecurrent
st4LineCurrentLowWarning
OBJECT-TYPE
The current low warning threshold of the line in tenth Amps.
1.3.6.1.4.1.1718.4.1.4.4.1.3Integer32 (0..6000)read-writecurrent
st4LineCurrentHighWarning
OBJECT-TYPE
The current high warning threshold of the line in tenth Amps.
1.3.6.1.4.1.1718.4.1.4.4.1.4Integer32 (0..6000)read-writecurrent
st4LineCurrentHighAlarm
OBJECT-TYPE
The current high alarm threshold of the line in tenth Amps.
1.3.6.1.4.1.1718.4.1.4.4.1.5Integer32 (0..6000)read-writecurrent
st4Phases
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.5
st4PhaseCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.5.1
st4PhaseVoltageHysteresis
OBJECT-TYPE
The voltage hysteresis of the phase in tenth Volts.
1.3.6.1.4.1.1718.4.1.5.1.1Integer32 (0..200)read-writecurrent
st4PhasePowerFactorHysteresis
OBJECT-TYPE
The power factor hysteresis of the phase in hundredths.
1.3.6.1.4.1.1718.4.1.5.1.2Integer32 (0..20)read-writecurrent
st4PhaseConfigTable
OBJECT-TYPE
Phase configuration table.
1.3.6.1.4.1.1718.4.1.5.2not-accessiblecurrent
st4PhaseConfigEntry
OBJECT-TYPE
Configuration objects for a particular phase.
1.3.6.1.4.1.1718.4.1.5.2.1not-accessiblecurrent
st4PhaseIndex
OBJECT-TYPE
Phase index. Three-phase AC Wye: L1-N=1, L2-N=2, L3-N=3; Three-phase AC Delta: L1-L2=1, L2-L3=2, L3-L1=3; Single Phase: L1-R=1; DC: L1-R=1; Three-phase AC Wye & Delta: L1-N=1, L2-N=2, L3-N=3, L1-L2=4, L2-L3=5; L3-L1=6.
1.3.6.1.4.1.1718.4.1.5.2.1.1Integer32 (1..6)not-accessiblecurrent
st4PhaseID
OBJECT-TYPE
The internal ID of the phase. Format=AAN.
1.3.6.1.4.1.1718.4.1.5.2.1.2DisplayString (SIZE(3))read-onlycurrent
st4PhaseLabel
OBJECT-TYPE
The system label assigned to the phase for identification.
1.3.6.1.4.1.1718.4.1.5.2.1.4DisplayString (SIZE(0..32))read-onlycurrent
st4PhaseNominalVoltage
OBJECT-TYPE
The nominal voltage of the phase in tenth Volts.
1.3.6.1.4.1.1718.4.1.5.2.1.6Integer32 (0..6000)read-onlycurrent
st4PhaseBranchCount
OBJECT-TYPE
The number of branches downstream from the phase.
1.3.6.1.4.1.1718.4.1.5.2.1.20Integer32 (0..12)read-onlycurrent
st4PhaseOutletCount
OBJECT-TYPE
The number of outlets powered from the phase.
1.3.6.1.4.1.1718.4.1.5.2.1.21Integer32 (0..128)read-onlycurrent
st4PhaseMonitorTable
OBJECT-TYPE
Phase monitor table.
1.3.6.1.4.1.1718.4.1.5.3not-accessiblecurrent
st4PhaseMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular phase.
1.3.6.1.4.1.1718.4.1.5.3.1not-accessiblecurrent
st4PhaseState
OBJECT-TYPE
The on/off state of the phase.
1.3.6.1.4.1.1718.4.1.5.3.1.1DeviceStateread-onlycurrent
st4PhaseStatus
OBJECT-TYPE
The status of the phase.
1.3.6.1.4.1.1718.4.1.5.3.1.2DeviceStatusread-onlycurrent
st4PhaseVoltage
OBJECT-TYPE
The measured voltage on the phase in tenth Volts.
1.3.6.1.4.1.1718.4.1.5.3.1.3Integer32 (-1..6000)read-onlycurrent
st4PhaseVoltageStatus
OBJECT-TYPE
The status of the measured voltage on the phase.
1.3.6.1.4.1.1718.4.1.5.3.1.4DeviceStatusread-onlycurrent
st4PhaseVoltageDeviation
OBJECT-TYPE
The deviation from the nominal voltage on the phase in tenth percent.
1.3.6.1.4.1.1718.4.1.5.3.1.5Integer32 (-1000..1000)read-onlycurrent
st4PhaseCurrent
OBJECT-TYPE
The measured current on the phase in hundredth Amps.
1.3.6.1.4.1.1718.4.1.5.3.1.6Integer32 (-1..30000)read-onlycurrent
st4PhaseCurrentCrestFactor
OBJECT-TYPE
The measured crest factor of the current waveform on the phase in tenths.
1.3.6.1.4.1.1718.4.1.5.3.1.7Integer32 (-1..250)read-onlycurrent
st4PhaseActivePower
OBJECT-TYPE
The measured active power on the phase in Watts.
1.3.6.1.4.1.1718.4.1.5.3.1.8Integer32 (-1..25000)read-onlycurrent
st4PhaseApparentPower
OBJECT-TYPE
The measured apparent power on the phase in Volt-Amps.
1.3.6.1.4.1.1718.4.1.5.3.1.9Integer32 (-1..25000)read-onlycurrent
st4PhasePowerFactor
OBJECT-TYPE
The measured power factor on the phase in hundredths.
1.3.6.1.4.1.1718.4.1.5.3.1.10Integer32 (-1..100)read-onlycurrent
st4PhasePowerFactorStatus
OBJECT-TYPE
The status of the measured power factor on the phase.
1.3.6.1.4.1.1718.4.1.5.3.1.11DeviceStatusread-onlycurrent
st4PhaseReactance
OBJECT-TYPE
The status of the measured reactance of the phase.
1.3.6.1.4.1.1718.4.1.5.3.1.12INTEGER {unknown(0), capacitive(1), inductive(2), resistive(3)}read-onlycurrent
st4PhaseEnergy
OBJECT-TYPE
The total energy consumption of loads through the phase in tenth Kilowatt-Hours.
1.3.6.1.4.1.1718.4.1.5.3.1.13Integer32 (-1..2147483647)read-onlycurrent
st4PhaseEventConfigTable
OBJECT-TYPE
Phase event configuration table.
1.3.6.1.4.1.1718.4.1.5.4not-accessiblecurrent
st4PhaseEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular phase.
1.3.6.1.4.1.1718.4.1.5.4.1not-accessiblecurrent
st4PhaseNotifications
OBJECT-TYPE
The notification methods enabled for phase events.
1.3.6.1.4.1.1718.4.1.5.4.1.1EventNotificationMethodsread-writecurrent
st4PhaseVoltageLowAlarm
OBJECT-TYPE
The current low alarm threshold of the phase in tenth Volts.
1.3.6.1.4.1.1718.4.1.5.4.1.2Integer32 (0..6000)read-writecurrent
st4PhaseVoltageLowWarning
OBJECT-TYPE
The current low warning threshold of the phase in tenth Volts.
1.3.6.1.4.1.1718.4.1.5.4.1.3Integer32 (0..6000)read-writecurrent
st4PhaseVoltageHighWarning
OBJECT-TYPE
The current high warning threshold of the phase in tenth Volts.
1.3.6.1.4.1.1718.4.1.5.4.1.4Integer32 (0..6000)read-writecurrent
st4PhaseVoltageHighAlarm
OBJECT-TYPE
The current high alarm threshold of the phase in tenth Volts.
1.3.6.1.4.1.1718.4.1.5.4.1.5Integer32 (0..6000)read-writecurrent
st4PhasePowerFactorLowAlarm
OBJECT-TYPE
The low power factor alarm threshold of the phase in hundredths.
1.3.6.1.4.1.1718.4.1.5.4.1.6Integer32 (0..100)read-writecurrent
st4PhasePowerFactorLowWarning
OBJECT-TYPE
The low power factor warning threshold of the phase in hundredths.
1.3.6.1.4.1.1718.4.1.5.4.1.7Integer32 (0..100)read-writecurrent
st4OverCurrentProtectors
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.6
st4OcpCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.6.1
st4OcpConfigTable
OBJECT-TYPE
Over-current protector configuration table.
1.3.6.1.4.1.1718.4.1.6.2not-accessiblecurrent
st4OcpConfigEntry
OBJECT-TYPE
Configuration objects for a particular over-current protector.
1.3.6.1.4.1.1718.4.1.6.2.1not-accessiblecurrent
st4OcpIndex
OBJECT-TYPE
Over-current protector index.
1.3.6.1.4.1.1718.4.1.6.2.1.1Integer32 (1..64)not-accessiblecurrent
st4OcpID
OBJECT-TYPE
The internal ID of the over-current protector. Format=AAN[N].
1.3.6.1.4.1.1718.4.1.6.2.1.2DisplayString (SIZE(3..4))read-onlycurrent
st4OcpLabel
OBJECT-TYPE
The system label assigned to the over-current protector for identification.
1.3.6.1.4.1.1718.4.1.6.2.1.4DisplayString (SIZE(0..32))read-onlycurrent
st4OcpType
OBJECT-TYPE
The type of over-current protector.
1.3.6.1.4.1.1718.4.1.6.2.1.6INTEGER {fuse(0), breaker(1)}read-onlycurrent
st4OcpCurrentCapacity
OBJECT-TYPE
The user-configured current capacity of the over-current protector in Amps.
1.3.6.1.4.1.1718.4.1.6.2.1.7Integer32 (0..125)read-writecurrent
st4OcpCurrentCapacityMax
OBJECT-TYPE
The factory-set maximum allowed for the user-configured current capacity of the over-current protector in Amps.
1.3.6.1.4.1.1718.4.1.6.2.1.8Integer32 (0..125)read-onlycurrent
st4OcpBranchCount
OBJECT-TYPE
The number of branches downstream from the over-current protector.
1.3.6.1.4.1.1718.4.1.6.2.1.20Integer32 (0..12)read-onlycurrent
st4OcpOutletCount
OBJECT-TYPE
The number of outlets powered from the over-current protector.
1.3.6.1.4.1.1718.4.1.6.2.1.21Integer32 (0..128)read-onlycurrent
st4OcpMonitorTable
OBJECT-TYPE
Over-current protector monitor table.
1.3.6.1.4.1.1718.4.1.6.3not-accessiblecurrent
st4OcpMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular over-current protector.
1.3.6.1.4.1.1718.4.1.6.3.1not-accessiblecurrent
st4OcpStatus
OBJECT-TYPE
The status of the over-current protector.
1.3.6.1.4.1.1718.4.1.6.3.1.1DeviceStatusread-onlycurrent
st4OcpEventConfigTable
OBJECT-TYPE
Over-current protector event configuration table.
1.3.6.1.4.1.1718.4.1.6.4not-accessiblecurrent
st4OcpEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular over-current protector.
1.3.6.1.4.1.1718.4.1.6.4.1not-accessiblecurrent
st4OcpNotifications
OBJECT-TYPE
The notification methods enabled for over-current protector events.
1.3.6.1.4.1.1718.4.1.6.4.1.1EventNotificationMethodsread-writecurrent
st4Branches
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.7
st4BranchCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.7.1
st4BranchCurrentHysteresis
OBJECT-TYPE
The current hysteresis of the branch in tenth Amps.
1.3.6.1.4.1.1718.4.1.7.1.1Integer32 (0..100)read-writecurrent
st4BranchConfigTable
OBJECT-TYPE
Branch configuration table.
1.3.6.1.4.1.1718.4.1.7.2not-accessiblecurrent
st4BranchConfigEntry
OBJECT-TYPE
Configuration objects for a particular branch.
1.3.6.1.4.1.1718.4.1.7.2.1not-accessiblecurrent
st4BranchIndex
OBJECT-TYPE
Branch index.
1.3.6.1.4.1.1718.4.1.7.2.1.1Integer32 (1..64)not-accessiblecurrent
st4BranchID
OBJECT-TYPE
The internal ID of the branch. Format=AAN[N].
1.3.6.1.4.1.1718.4.1.7.2.1.2DisplayString (SIZE(3..4))read-onlycurrent
st4BranchLabel
OBJECT-TYPE
The system label assigned to the branch for identification.
1.3.6.1.4.1.1718.4.1.7.2.1.4DisplayString (SIZE(0..32))read-onlycurrent
st4BranchCurrentCapacity
OBJECT-TYPE
The current capacity of the branch in Amps.
1.3.6.1.4.1.1718.4.1.7.2.1.6Integer32 (0..125)read-onlycurrent
st4BranchPhaseID
OBJECT-TYPE
The internal ID of the phase powering this branch. Format=AAN.
1.3.6.1.4.1.1718.4.1.7.2.1.20DisplayString (SIZE(3))read-onlycurrent
st4BranchOcpID
OBJECT-TYPE
The internal ID of the over-current protector powering this outlet. Format=AAN[N].
1.3.6.1.4.1.1718.4.1.7.2.1.21DisplayString (SIZE(3..4))read-onlycurrent
st4BranchOutletCount
OBJECT-TYPE
The number of outlets powered from the branch.
1.3.6.1.4.1.1718.4.1.7.2.1.30Integer32 (0..128)read-onlycurrent
st4BranchMonitorTable
OBJECT-TYPE
Branch monitor table.
1.3.6.1.4.1.1718.4.1.7.3not-accessiblecurrent
st4BranchMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular branch.
1.3.6.1.4.1.1718.4.1.7.3.1not-accessiblecurrent
st4BranchState
OBJECT-TYPE
The on/off state of the branch.
1.3.6.1.4.1.1718.4.1.7.3.1.1DeviceStateread-onlycurrent
st4BranchStatus
OBJECT-TYPE
The status of the branch.
1.3.6.1.4.1.1718.4.1.7.3.1.2DeviceStatusread-onlycurrent
st4BranchCurrent
OBJECT-TYPE
The measured current on the branch in hundredth Amps.
1.3.6.1.4.1.1718.4.1.7.3.1.3Integer32 (-1..12500)read-onlycurrent
st4BranchCurrentStatus
OBJECT-TYPE
The status of the measured current on the branch.
1.3.6.1.4.1.1718.4.1.7.3.1.4DeviceStatusread-onlycurrent
st4BranchCurrentUtilized
OBJECT-TYPE
The amount of the branch current capacity used in tenth percent.
1.3.6.1.4.1.1718.4.1.7.3.1.5Integer32 (-1..1200)read-onlycurrent
st4BranchEventConfigTable
OBJECT-TYPE
Branch event configuration table.
1.3.6.1.4.1.1718.4.1.7.4not-accessiblecurrent
st4BranchEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular branch.
1.3.6.1.4.1.1718.4.1.7.4.1not-accessiblecurrent
st4BranchNotifications
OBJECT-TYPE
The notification methods enabled for branch events.
1.3.6.1.4.1.1718.4.1.7.4.1.1EventNotificationMethodsread-writecurrent
st4BranchCurrentLowAlarm
OBJECT-TYPE
The current low alarm threshold of the branch in tenth Amps.
1.3.6.1.4.1.1718.4.1.7.4.1.2Integer32 (0..1250)read-writecurrent
st4BranchCurrentLowWarning
OBJECT-TYPE
The current low warning threshold of the branch in tenth Amps.
1.3.6.1.4.1.1718.4.1.7.4.1.3Integer32 (0..1250)read-writecurrent
st4BranchCurrentHighWarning
OBJECT-TYPE
The current high warning threshold of the branch in tenth Amps.
1.3.6.1.4.1.1718.4.1.7.4.1.4Integer32 (0..1250)read-writecurrent
st4BranchCurrentHighAlarm
OBJECT-TYPE
The current high alarm threshold of the branch in tenth Amps.
1.3.6.1.4.1.1718.4.1.7.4.1.5Integer32 (0..1250)read-writecurrent
st4Outlets
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.8
st4OutletCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.8.1
st4OutletCurrentHysteresis
OBJECT-TYPE
The current hysteresis of the outlet in tenth Amps.
1.3.6.1.4.1.1718.4.1.8.1.1Integer32 (0..100)read-writecurrent
st4OutletActivePowerHysteresis
OBJECT-TYPE
The power hysteresis of the outlet in Watts.
1.3.6.1.4.1.1718.4.1.8.1.2Integer32 (0..1000)read-writecurrent
st4OutletPowerFactorHysteresis
OBJECT-TYPE
The power factor hysteresis of the outlet in hundredths.
1.3.6.1.4.1.1718.4.1.8.1.3Integer32 (0..20)read-writecurrent
st4OutletSequenceInterval
OBJECT-TYPE
The power-on sequencing interval for all outlets in seconds.
1.3.6.1.4.1.1718.4.1.8.1.10Integer32 (0..15)read-writecurrent
st4OutletRebootDelay
OBJECT-TYPE
The reboot delay for all outlets in seconds.
1.3.6.1.4.1.1718.4.1.8.1.11Integer32 (5..600)read-writecurrent
st4OutletStateChangeLogging
OBJECT-TYPE
Enables or disables informational Outlet State Change event logging.
1.3.6.1.4.1.1718.4.1.8.1.12INTEGER {disabled(0), enabled(1)}read-writecurrent
st4OutletConfigTable
OBJECT-TYPE
Outlet configuration table.
1.3.6.1.4.1.1718.4.1.8.2not-accessiblecurrent
st4OutletConfigEntry
OBJECT-TYPE
Configuration objects for a particular outlet.
1.3.6.1.4.1.1718.4.1.8.2.1not-accessiblecurrent
st4OutletIndex
OBJECT-TYPE
Outlet index.
1.3.6.1.4.1.1718.4.1.8.2.1.1Integer32 (1..128)not-accessiblecurrent
st4OutletID
OBJECT-TYPE
The internal ID of the outlet. Format=AAN[N[N]].
1.3.6.1.4.1.1718.4.1.8.2.1.2DisplayString (SIZE(3..5))read-onlycurrent
st4OutletName
OBJECT-TYPE
The name of the outlet.
1.3.6.1.4.1.1718.4.1.8.2.1.3DisplayString (SIZE(0..32))read-writecurrent
st4OutletCapabilities
OBJECT-TYPE
The capabilities of the outlet.
1.3.6.1.4.1.1718.4.1.8.2.1.5Bits {switched(0), pops(1)}read-onlycurrent
st4OutletSocketType
OBJECT-TYPE
The socket type of the outlet.
1.3.6.1.4.1.1718.4.1.8.2.1.6DisplayString (SIZE(0..32))read-onlycurrent
st4OutletCurrentCapacity
OBJECT-TYPE
The current capacity of the outlet in Amps.
1.3.6.1.4.1.1718.4.1.8.2.1.7Integer32 (0..125)read-onlycurrent
st4OutletPowerCapacity
OBJECT-TYPE
The power capacity of the outlet in Volt-Amps. For DC products, this is identical to power capacity in Watts.
1.3.6.1.4.1.1718.4.1.8.2.1.8Integer32 (0..10000)read-onlycurrent
st4OutletWakeupState
OBJECT-TYPE
The wakeup state of the outlet.
1.3.6.1.4.1.1718.4.1.8.2.1.20INTEGER {on(0), off(1), last(2)}read-writecurrent
st4OutletPostOnDelay
OBJECT-TYPE
The post-on delay of the outlet in seconds.
1.3.6.1.4.1.1718.4.1.8.2.1.21Integer32 (0..900)read-writecurrent
st4OutletPhaseID
OBJECT-TYPE
The internal ID of the phase powering this outlet. Format=AAN.
1.3.6.1.4.1.1718.4.1.8.2.1.30DisplayString (SIZE(3))read-onlycurrent
st4OutletOcpID
OBJECT-TYPE
The internal ID of the over-current protector powering this outlet. Format=AAN[N].
1.3.6.1.4.1.1718.4.1.8.2.1.31DisplayString (SIZE(3..4))read-onlycurrent
st4OutletBranchID
OBJECT-TYPE
The internal ID of the branch powering this outlet. Format=AAN[N].
1.3.6.1.4.1.1718.4.1.8.2.1.32DisplayString (SIZE(3..4))read-onlycurrent
st4OutletMonitorTable
OBJECT-TYPE
Outlet monitor table.
1.3.6.1.4.1.1718.4.1.8.3not-accessiblecurrent
st4OutletMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular outlet.
1.3.6.1.4.1.1718.4.1.8.3.1not-accessiblecurrent
st4OutletState
OBJECT-TYPE
The on/off state of the outlet.
1.3.6.1.4.1.1718.4.1.8.3.1.1DeviceStateread-onlycurrent
st4OutletStatus
OBJECT-TYPE
The status of the outlet.
1.3.6.1.4.1.1718.4.1.8.3.1.2DeviceStatusread-onlycurrent
st4OutletCurrent
OBJECT-TYPE
The measured current on the outlet in hundredth Amps.
1.3.6.1.4.1.1718.4.1.8.3.1.3Integer32 (-1..12500)read-onlycurrent
st4OutletCurrentStatus
OBJECT-TYPE
The status of the measured current on the outlet.
1.3.6.1.4.1.1718.4.1.8.3.1.4DeviceStatusread-onlycurrent
st4OutletCurrentUtilized
OBJECT-TYPE
The amount of the outlet current capacity used in tenth percent.
1.3.6.1.4.1.1718.4.1.8.3.1.5Integer32 (-1..1200)read-onlycurrent
st4OutletVoltage
OBJECT-TYPE
The measured voltage of the outlet in tenth Volts.
1.3.6.1.4.1.1718.4.1.8.3.1.6Integer32 (-1..6000)read-onlycurrent
st4OutletActivePower
OBJECT-TYPE
The measured active power of the outlet in Watts.
1.3.6.1.4.1.1718.4.1.8.3.1.7Integer32 (-1..10000)read-onlycurrent
st4OutletActivePowerStatus
OBJECT-TYPE
The status of the measured active power of the outlet.
1.3.6.1.4.1.1718.4.1.8.3.1.8DeviceStatusread-onlycurrent
st4OutletApparentPower
OBJECT-TYPE
The measured apparent power of the outlet in Volt-Amps.
1.3.6.1.4.1.1718.4.1.8.3.1.9Integer32 (-1..10000)read-onlycurrent
st4OutletPowerFactor
OBJECT-TYPE
The measured power factor of the outlet in hundredths.
1.3.6.1.4.1.1718.4.1.8.3.1.10Integer32 (-1..100)read-onlycurrent
st4OutletPowerFactorStatus
OBJECT-TYPE
The status of the measured power factor of the outlet.
1.3.6.1.4.1.1718.4.1.8.3.1.11DeviceStatusread-onlycurrent
st4OutletCurrentCrestFactor
OBJECT-TYPE
The measured crest factor of the outlet in tenths.
1.3.6.1.4.1.1718.4.1.8.3.1.12Integer32 (-1..250)read-onlycurrent
st4OutletReactance
OBJECT-TYPE
The status of the measured reactance of the outlet.
1.3.6.1.4.1.1718.4.1.8.3.1.13INTEGER {unknown(0), capacitive(1), inductive(2), resistive(3)}read-onlycurrent
st4OutletEnergy
OBJECT-TYPE
The total energy consumption of the device plugged into the outlet in Watt-Hours.
1.3.6.1.4.1.1718.4.1.8.3.1.14Integer32 (-1..2147483647)read-onlycurrent
st4OutletEventConfigTable
OBJECT-TYPE
Outlet event configuration table.
1.3.6.1.4.1.1718.4.1.8.4not-accessiblecurrent
st4OutletEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular outlet.
1.3.6.1.4.1.1718.4.1.8.4.1not-accessiblecurrent
st4OutletNotifications
OBJECT-TYPE
The notification methods enabled for outlet events.
1.3.6.1.4.1.1718.4.1.8.4.1.1EventNotificationMethodsread-writecurrent
st4OutletCurrentLowAlarm
OBJECT-TYPE
The current low alarm threshold of the outlet in tenth Amps.
1.3.6.1.4.1.1718.4.1.8.4.1.2Integer32 (0..1250)read-writecurrent
st4OutletCurrentLowWarning
OBJECT-TYPE
The current low warning threshold of the outlet in tenth Amps.
1.3.6.1.4.1.1718.4.1.8.4.1.3Integer32 (0..1250)read-writecurrent
st4OutletCurrentHighWarning
OBJECT-TYPE
The current high warning threshold of the outlet in tenth Amps.
1.3.6.1.4.1.1718.4.1.8.4.1.4Integer32 (0..1250)read-writecurrent
st4OutletCurrentHighAlarm
OBJECT-TYPE
The current high alarm threshold of the outlet in tenth Amps.
1.3.6.1.4.1.1718.4.1.8.4.1.5Integer32 (0..1250)read-writecurrent
st4OutletActivePowerLowAlarm
OBJECT-TYPE
The active power low alarm threshold of the outlet in Watts.
1.3.6.1.4.1.1718.4.1.8.4.1.6Integer32 (0..10000)read-writecurrent
st4OutletActivePowerLowWarning
OBJECT-TYPE
The active power low warning threshold of the outlet in Watts.
1.3.6.1.4.1.1718.4.1.8.4.1.7Integer32 (0..10000)read-writecurrent
st4OutletActivePowerHighWarning
OBJECT-TYPE
The active power high warning threshold of the outlet in Watts.
1.3.6.1.4.1.1718.4.1.8.4.1.8Integer32 (0..10000)read-writecurrent
st4OutletActivePowerHighAlarm
OBJECT-TYPE
The active power high alarm threshold of the outlet in Watts.
1.3.6.1.4.1.1718.4.1.8.4.1.9Integer32 (0..10000)read-writecurrent
st4OutletPowerFactorLowAlarm
OBJECT-TYPE
The low power factor alarm threshold of the outlet in hundredths.
1.3.6.1.4.1.1718.4.1.8.4.1.10Integer32 (0..100)read-writecurrent
st4OutletPowerFactorLowWarning
OBJECT-TYPE
The low power factor warning threshold of the outlet in hundredths.
1.3.6.1.4.1.1718.4.1.8.4.1.11Integer32 (0..100)read-writecurrent
st4OutletControlTable
OBJECT-TYPE
Outlet control table.
1.3.6.1.4.1.1718.4.1.8.5not-accessiblecurrent
st4OutletControlEntry
OBJECT-TYPE
Objects for control of a particular outlet.
1.3.6.1.4.1.1718.4.1.8.5.1not-accessiblecurrent
st4OutletControlState
OBJECT-TYPE
The control state of the outlet.
1.3.6.1.4.1.1718.4.1.8.5.1.1INTEGER {notSet(0), fixedOn(1), idleOff(2), idleOn(3), wakeOff(4), wakeOn(5), ocpOff(6), ocpOn(7), pendOn(8), pendOff(9), off(10), on(11), reboot(12), shutdown(13), lockedOff(14), lockedOn(15), eventOff(16), eventOn(17), eventReboot(18), eventShutdown(19)}read-onlycurrent
st4OutletControlAction
OBJECT-TYPE
An action to change the control state of the outlet, or to queue an action.
1.3.6.1.4.1.1718.4.1.8.5.1.2INTEGER {none(0), on(1), off(2), reboot(3), queueOn(4), queueOff(5), queueReboot(6)}read-writecurrent
st4OutletCommonControl
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.8.6
st4OutletQueueControl
OBJECT-TYPE
An action to clear or commit queued outlet control actions. A read of this object returns clear(0) if queue is empty, and commit(1) if the queue is not empty.
1.3.6.1.4.1.1718.4.1.8.6.1INTEGER {clear(0), commit(1)}read-writecurrent
st4TemperatureSensors
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.9
st4TempSensorCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.9.1
st4TempSensorHysteresis
OBJECT-TYPE
The temperature hysteresis of the sensor in degrees, using the scale selected by st4TempSensorScale.
1.3.6.1.4.1.1718.4.1.9.1.1Integer32 (0..54)read-writecurrent
st4TempSensorScale
OBJECT-TYPE
The current scale used for all temperature values.
1.3.6.1.4.1.1718.4.1.9.1.10INTEGER {celsius(0), fahrenheit(1)}read-writecurrent
st4TempSensorConfigTable
OBJECT-TYPE
Temperature sensor configuration table.
1.3.6.1.4.1.1718.4.1.9.2not-accessiblecurrent
st4TempSensorConfigEntry
OBJECT-TYPE
Configuration objects for a particular temperature sensor.
1.3.6.1.4.1.1718.4.1.9.2.1not-accessiblecurrent
st4TempSensorIndex
OBJECT-TYPE
Temperature sensor index.
1.3.6.1.4.1.1718.4.1.9.2.1.1Integer32 (0..2)not-accessiblecurrent
st4TempSensorID
OBJECT-TYPE
The internal ID of the temperature sensor. Format=AN.
1.3.6.1.4.1.1718.4.1.9.2.1.2DisplayString (SIZE(2))read-onlycurrent
st4TempSensorName
OBJECT-TYPE
The name of the temperature sensor.
1.3.6.1.4.1.1718.4.1.9.2.1.3DisplayString (SIZE(0..32))read-writecurrent
st4TempSensorValueMin
OBJECT-TYPE
The minimum temperature limit of the sensor in degrees, using the scale selected by st4TempSensorScale.
1.3.6.1.4.1.1718.4.1.9.2.1.4Integer32 (-40..253)read-onlycurrent
st4TempSensorValueMax
OBJECT-TYPE
The maximum temperature limit of the sensor in degrees, using the scale selected by st4TempSensorScale.
1.3.6.1.4.1.1718.4.1.9.2.1.5Integer32 (-40..253)read-onlycurrent
st4TempSensorMonitorTable
OBJECT-TYPE
Temperature sensor monitor table.
1.3.6.1.4.1.1718.4.1.9.3not-accessiblecurrent
st4TempSensorMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular temperature sensor.
1.3.6.1.4.1.1718.4.1.9.3.1not-accessiblecurrent
st4TempSensorValue
OBJECT-TYPE
The measured temperature on the sensor in tenth degrees using the scale selected by st4TempSensorScale. -410 means the temperature reading is invalid.
1.3.6.1.4.1.1718.4.1.9.3.1.1Integer32 (-410..2540)read-onlycurrent
st4TempSensorStatus
OBJECT-TYPE
The status of the temperature sensor.
1.3.6.1.4.1.1718.4.1.9.3.1.2DeviceStatusread-onlycurrent
st4TempSensorEventConfigTable
OBJECT-TYPE
Temperature sensor event configuration table.
1.3.6.1.4.1.1718.4.1.9.4not-accessiblecurrent
st4TempSensorEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular temperature sensor.
1.3.6.1.4.1.1718.4.1.9.4.1not-accessiblecurrent
st4TempSensorNotifications
OBJECT-TYPE
The notification methods enabled for temperature sensor events.
1.3.6.1.4.1.1718.4.1.9.4.1.1EventNotificationMethodsread-writecurrent
st4TempSensorLowAlarm
OBJECT-TYPE
The low alarm threshold of the temperature sensor in degrees.
1.3.6.1.4.1.1718.4.1.9.4.1.2Integer32 (-40..253)read-writecurrent
st4TempSensorLowWarning
OBJECT-TYPE
The low warning threshold of the temperature sensor in degrees.
1.3.6.1.4.1.1718.4.1.9.4.1.3Integer32 (-40..253)read-writecurrent
st4TempSensorHighWarning
OBJECT-TYPE
The high warning threshold of the temperature sensor in degrees.
1.3.6.1.4.1.1718.4.1.9.4.1.4Integer32 (-40..253)read-writecurrent
st4TempSensorHighAlarm
OBJECT-TYPE
The high alarm threshold of the temperature sensor in degrees.
1.3.6.1.4.1.1718.4.1.9.4.1.5Integer32 (-40..253)read-writecurrent
st4HumiditySensors
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.10
st4HumidSensorCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.10.1
st4HumidSensorHysteresis
OBJECT-TYPE
The humidity hysteresis of the sensor in percent relative humidity.
1.3.6.1.4.1.1718.4.1.10.1.1Integer32 (0..20)read-writecurrent
st4HumidSensorConfigTable
OBJECT-TYPE
Humidity sensor configuration table.
1.3.6.1.4.1.1718.4.1.10.2not-accessiblecurrent
st4HumidSensorConfigEntry
OBJECT-TYPE
Configuration objects for a particular humidity sensor.
1.3.6.1.4.1.1718.4.1.10.2.1not-accessiblecurrent
st4HumidSensorIndex
OBJECT-TYPE
Humidity sensor index.
1.3.6.1.4.1.1718.4.1.10.2.1.1Integer32 (0..2)not-accessiblecurrent
st4HumidSensorID
OBJECT-TYPE
The internal ID of the humidity sensor. Format=AN.
1.3.6.1.4.1.1718.4.1.10.2.1.2DisplayString (SIZE(2))read-onlycurrent
st4HumidSensorName
OBJECT-TYPE
The name of the humidity sensor.
1.3.6.1.4.1.1718.4.1.10.2.1.3DisplayString (SIZE(0..32))read-writecurrent
st4HumidSensorMonitorTable
OBJECT-TYPE
Humidity sensor monitor table.
1.3.6.1.4.1.1718.4.1.10.3not-accessiblecurrent
st4HumidSensorMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular humidity sensor.
1.3.6.1.4.1.1718.4.1.10.3.1not-accessiblecurrent
st4HumidSensorValue
OBJECT-TYPE
The measured humidity on the sensor in percentage relative humidity.
1.3.6.1.4.1.1718.4.1.10.3.1.1Integer32 (-1..100)read-onlycurrent
st4HumidSensorStatus
OBJECT-TYPE
The status of the humidity sensor.
1.3.6.1.4.1.1718.4.1.10.3.1.2DeviceStatusread-onlycurrent
st4HumidSensorEventConfigTable
OBJECT-TYPE
Humidity sensor event configuration table.
1.3.6.1.4.1.1718.4.1.10.4not-accessiblecurrent
st4HumidSensorEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular humidity sensor.
1.3.6.1.4.1.1718.4.1.10.4.1not-accessiblecurrent
st4HumidSensorNotifications
OBJECT-TYPE
The notification methods enabled for humidity sensor events.
1.3.6.1.4.1.1718.4.1.10.4.1.1EventNotificationMethodsread-writecurrent
st4HumidSensorLowAlarm
OBJECT-TYPE
The low alarm threshold of the humidity sensor in percentage relative humidity.
1.3.6.1.4.1.1718.4.1.10.4.1.2Integer32 (0..100)read-writecurrent
st4HumidSensorLowWarning
OBJECT-TYPE
The low warning threshold of the humidity sensor in percentage relative humidity.
1.3.6.1.4.1.1718.4.1.10.4.1.3Integer32 (0..100)read-writecurrent
st4HumidSensorHighWarning
OBJECT-TYPE
The high warning threshold of the humidity sensor in percentage relative humidity.
1.3.6.1.4.1.1718.4.1.10.4.1.4Integer32 (0..100)read-writecurrent
st4HumidSensorHighAlarm
OBJECT-TYPE
The high alarm threshold of the humidity sensor in percentage relative humidity.
1.3.6.1.4.1.1718.4.1.10.4.1.5Integer32 (0..100)read-writecurrent
st4WaterSensors
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.11
st4WaterSensorCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.11.1
st4WaterSensorConfigTable
OBJECT-TYPE
Water sensor configuration table.
1.3.6.1.4.1.1718.4.1.11.2not-accessiblecurrent
st4WaterSensorConfigEntry
OBJECT-TYPE
Configuration objects for a particular water sensor.
1.3.6.1.4.1.1718.4.1.11.2.1not-accessiblecurrent
st4WaterSensorIndex
OBJECT-TYPE
Water sensor index.
1.3.6.1.4.1.1718.4.1.11.2.1.1Integer32 (0..1)not-accessiblecurrent
st4WaterSensorID
OBJECT-TYPE
The internal ID of the water sensor. Format=AN.
1.3.6.1.4.1.1718.4.1.11.2.1.2DisplayString (SIZE(2))read-onlycurrent
st4WaterSensorName
OBJECT-TYPE
The name of the water sensor.
1.3.6.1.4.1.1718.4.1.11.2.1.3DisplayString (SIZE(0..32))read-writecurrent
st4WaterSensorMonitorTable
OBJECT-TYPE
Water sensor monitor table.
1.3.6.1.4.1.1718.4.1.11.3not-accessiblecurrent
st4WaterSensorMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular water sensor.
1.3.6.1.4.1.1718.4.1.11.3.1not-accessiblecurrent
st4WaterSensorStatus
OBJECT-TYPE
The status of the water sensor.
1.3.6.1.4.1.1718.4.1.11.3.1.1DeviceStatusread-onlycurrent
st4WaterSensorEventConfigTable
OBJECT-TYPE
Water sensor event configuration table.
1.3.6.1.4.1.1718.4.1.11.4not-accessiblecurrent
st4WaterSensorEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular water sensor.
1.3.6.1.4.1.1718.4.1.11.4.1not-accessiblecurrent
st4WaterSensorNotifications
OBJECT-TYPE
The notification methods enabled for water sensor events.
1.3.6.1.4.1.1718.4.1.11.4.1.1EventNotificationMethodsread-writecurrent
st4ContactClosureSensors
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.12
st4CcSensorCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.12.1
st4CcSensorConfigTable
OBJECT-TYPE
Contact closure sensor configuration table.
1.3.6.1.4.1.1718.4.1.12.2not-accessiblecurrent
st4CcSensorConfigEntry
OBJECT-TYPE
Configuration objects for a particular contact closure sensor.
1.3.6.1.4.1.1718.4.1.12.2.1not-accessiblecurrent
st4CcSensorIndex
OBJECT-TYPE
Contact closure sensor index.
1.3.6.1.4.1.1718.4.1.12.2.1.1Integer32 (0..4)not-accessiblecurrent
st4CcSensorID
OBJECT-TYPE
The internal ID of the contact closure sensor. Format=AN.
1.3.6.1.4.1.1718.4.1.12.2.1.2DisplayString (SIZE(2))read-onlycurrent
st4CcSensorName
OBJECT-TYPE
The name of the contact closure sensor.
1.3.6.1.4.1.1718.4.1.12.2.1.3DisplayString (SIZE(0..32))read-writecurrent
st4CcSensorMonitorTable
OBJECT-TYPE
Contact closure sensor monitor table.
1.3.6.1.4.1.1718.4.1.12.3not-accessiblecurrent
st4CcSensorMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular contact closure sensor.
1.3.6.1.4.1.1718.4.1.12.3.1not-accessiblecurrent
st4CcSensorStatus
OBJECT-TYPE
The status of the contact closure.
1.3.6.1.4.1.1718.4.1.12.3.1.1DeviceStatusread-onlycurrent
st4CcSensorEventConfigTable
OBJECT-TYPE
Contact closure sensor event configuration table.
1.3.6.1.4.1.1718.4.1.12.4not-accessiblecurrent
st4CcSensorEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular contact closure sensor.
1.3.6.1.4.1.1718.4.1.12.4.1not-accessiblecurrent
st4CcSensorNotifications
OBJECT-TYPE
The notification methods enabled for contact closure sensor events.
1.3.6.1.4.1.1718.4.1.12.4.1.1EventNotificationMethodsread-writecurrent
st4AnalogToDigitalConvSensors
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.13
st4AdcSensorCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.13.1
st4AdcSensorHysteresis
OBJECT-TYPE
The 8-bit count hysteresis of the analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.1.1Integer32 (0..20)read-writecurrent
st4AdcSensorConfigTable
OBJECT-TYPE
Analog-to-digital converter sensor configuration table.
1.3.6.1.4.1.1718.4.1.13.2not-accessiblecurrent
st4AdcSensorConfigEntry
OBJECT-TYPE
Configuration objects for a particular analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.2.1not-accessiblecurrent
st4AdcSensorIndex
OBJECT-TYPE
Analog-to-digital converter sensor index.
1.3.6.1.4.1.1718.4.1.13.2.1.1Integer32 (0..1)not-accessiblecurrent
st4AdcSensorID
OBJECT-TYPE
The internal ID of the analog-to-digital converter sensor. Format=AN.
1.3.6.1.4.1.1718.4.1.13.2.1.2DisplayString (SIZE(2))read-onlycurrent
st4AdcSensorName
OBJECT-TYPE
The name of the analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.2.1.3DisplayString (SIZE(0..32))read-writecurrent
st4AdcSensorMonitorTable
OBJECT-TYPE
Analog-to-digital converter sensor monitor table.
1.3.6.1.4.1.1718.4.1.13.3not-accessiblecurrent
st4AdcSensorMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.3.1not-accessiblecurrent
st4AdcSensorValue
OBJECT-TYPE
The 8-bit value from the analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.3.1.1Integer32 (-1..255)read-onlycurrent
st4AdcSensorStatus
OBJECT-TYPE
The status of the analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.3.1.2DeviceStatusread-onlycurrent
st4AdcSensorEventConfigTable
OBJECT-TYPE
Analog-to-digital converter sensor event configuration table.
1.3.6.1.4.1.1718.4.1.13.4not-accessiblecurrent
st4AdcSensorEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.4.1not-accessiblecurrent
st4AdcSensorNotifications
OBJECT-TYPE
The notification methods enabled for analog-to-digital converter sensor events.
1.3.6.1.4.1.1718.4.1.13.4.1.1EventNotificationMethodsread-writecurrent
st4AdcSensorLowAlarm
OBJECT-TYPE
The 8-bit value for the low alarm threshold of the analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.4.1.2Integer32 (0..255)read-writecurrent
st4AdcSensorLowWarning
OBJECT-TYPE
The 8-bit value for the low warning threshold of the analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.4.1.3Integer32 (0..255)read-writecurrent
st4AdcSensorHighWarning
OBJECT-TYPE
The 8-bit value for the high warning threshold of the analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.4.1.4Integer32 (0..255)read-writecurrent
st4AdcSensorHighAlarm
OBJECT-TYPE
The 8-bit value for the high alarm threshold of the analog-to-digital converter sensor.
1.3.6.1.4.1.1718.4.1.13.4.1.5Integer32 (0..255)read-writecurrent
st4FanSensors
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.14
st4FanSensorCommonConfig
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.14.1
st4FanSensorHysteresis
OBJECT-TYPE
The fan speed hysteresis of the sensor in rotations per minute.
1.3.6.1.4.1.1718.4.1.14.1.1Integer32 (0..1200)read-writecurrent
st4FanSensorConfigTable
OBJECT-TYPE
Fan sensor configuration table.
1.3.6.1.4.1.1718.4.1.14.2not-accessiblecurrent
st4FanSensorConfigEntry
OBJECT-TYPE
Configuration objects for a particular fan sensor.
1.3.6.1.4.1.1718.4.1.14.2.1not-accessiblecurrent
st4FanSensorIndex
OBJECT-TYPE
Fan sensor index.
1.3.6.1.4.1.1718.4.1.14.2.1.1Integer32 (0..4)not-accessiblecurrent
st4FanSensorID
OBJECT-TYPE
The internal ID of the fan sensor. Format=AN.
1.3.6.1.4.1.1718.4.1.14.2.1.2DisplayString (SIZE(2))read-onlycurrent
st4FanSensorName
OBJECT-TYPE
The name of the fan sensor.
1.3.6.1.4.1.1718.4.1.14.2.1.3DisplayString (SIZE(0..32))read-writecurrent
st4FanSensorMonitorTable
OBJECT-TYPE
Fan sensor monitor table.
1.3.6.1.4.1.1718.4.1.14.3not-accessiblecurrent
st4FanSensorMonitorEntry
OBJECT-TYPE
Objects to monitor for a particular fan sensor.
1.3.6.1.4.1.1718.4.1.14.3.1not-accessiblecurrent
st4FanSensorValue
OBJECT-TYPE
The measured fan speed of the sensor in rotations per minute.
1.3.6.1.4.1.1718.4.1.14.3.1.1Integer32 (-1..15300)read-onlycurrent
st4FanSensorStatus
OBJECT-TYPE
The status of the fan sensor.
1.3.6.1.4.1.1718.4.1.14.3.1.2DeviceStatusread-onlycurrent
st4FanSensorEventConfigTable
OBJECT-TYPE
Fan sensor event configuration table.
1.3.6.1.4.1.1718.4.1.14.4not-accessiblecurrent
st4FanSensorEventConfigEntry
OBJECT-TYPE
Event configuration objects for a particular fan sensor.
1.3.6.1.4.1.1718.4.1.14.4.1not-accessiblecurrent
st4FanSensorNotifications
OBJECT-TYPE
The notification methods enabled for fan sensor events.
1.3.6.1.4.1.1718.4.1.14.4.1.1EventNotificationMethodsread-writecurrent
st4FanSensorLowAlarm
OBJECT-TYPE
The low alarm threshold of the fan sensor in rotations per minute.
1.3.6.1.4.1.1718.4.1.14.4.1.2Integer32 (0..15300)read-writecurrent
st4FanSensorLowWarning
OBJECT-TYPE
The low warning threshold of the fan sensor in rotations per minute.
1.3.6.1.4.1.1718.4.1.14.4.1.3Integer32 (0..15300)read-writecurrent
st4FanSensorHighWarning
OBJECT-TYPE
The high warning threshold of the fan sensor in rotations per minute.
1.3.6.1.4.1.1718.4.1.14.4.1.4Integer32 (0..15300)read-writecurrent
st4FanSensorHighAlarm
OBJECT-TYPE
The high alarm threshold of the fan sensor in rotations per minute.
1.3.6.1.4.1.1718.4.1.14.4.1.5Integer32 (0..15300)read-writecurrent
st4EventInformation
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.1.99
st4EventStatusText
OBJECT-TYPE
The text representation of the enumerated integer value of the most-relevant status or state object included in a trap. The value of this object is set only when sent with a trap. A read of this object will return a NULL string.
1.3.6.1.4.1.1718.4.1.99.1DisplayString (SIZE(0..20))read-onlycurrent
st4EventStatusCondition
OBJECT-TYPE
The condition of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A read of this object will return zero.
1.3.6.1.4.1.1718.4.1.99.2INTEGER {nonError(0), error(1)}read-onlycurrent
st4Notifications
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.100
st4Events
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.100.0
st4Conformance
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.200
st4Groups
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.200.1
st4Compliances
OBJECT-IDENTITY
1.3.6.1.4.1.1718.4.200.2

Notifications

NameOIDStatus
st4UnitStatusEvent
NOTIFICATION-TYPE
Unit status event.
1.3.6.1.4.1.1718.4.100.0.1current
st4InputCordStatusEvent
NOTIFICATION-TYPE
Input cord status event.
1.3.6.1.4.1.1718.4.100.0.2current
st4InputCordActivePowerEvent
NOTIFICATION-TYPE
Input cord active power event.
1.3.6.1.4.1.1718.4.100.0.3current
st4InputCordApparentPowerEvent
NOTIFICATION-TYPE
Input cord apparent power event.
1.3.6.1.4.1.1718.4.100.0.4current
st4InputCordPowerFactorEvent
NOTIFICATION-TYPE
Input cord power factor event.
1.3.6.1.4.1.1718.4.100.0.5current
st4InputCordOutOfBalanceEvent
NOTIFICATION-TYPE
Input cord out-of-balance event.
1.3.6.1.4.1.1718.4.100.0.6current
st4LineStatusEvent
NOTIFICATION-TYPE
Line status event.
1.3.6.1.4.1.1718.4.100.0.7current
st4LineCurrentEvent
NOTIFICATION-TYPE
Line current event.
1.3.6.1.4.1.1718.4.100.0.8current
st4PhaseStatusEvent
NOTIFICATION-TYPE
Phase status event.
1.3.6.1.4.1.1718.4.100.0.9current
st4PhaseVoltageEvent
NOTIFICATION-TYPE
Phase voltage event.
1.3.6.1.4.1.1718.4.100.0.10current
st4PhasePowerFactorEvent
NOTIFICATION-TYPE
Phase voltage event.
1.3.6.1.4.1.1718.4.100.0.11current
st4OcpStatusEvent
NOTIFICATION-TYPE
Over-current protector status event.
1.3.6.1.4.1.1718.4.100.0.12current
st4BranchStatusEvent
NOTIFICATION-TYPE
Branch status event.
1.3.6.1.4.1.1718.4.100.0.13current
st4BranchCurrentEvent
NOTIFICATION-TYPE
Branch current event.
1.3.6.1.4.1.1718.4.100.0.14current
st4OutletStatusEvent
NOTIFICATION-TYPE
Outlet status event.
1.3.6.1.4.1.1718.4.100.0.15current
st4OutletStateChangeEvent
NOTIFICATION-TYPE
Outlet state change event.
1.3.6.1.4.1.1718.4.100.0.16current
st4OutletCurrentEvent
NOTIFICATION-TYPE
Outlet current event.
1.3.6.1.4.1.1718.4.100.0.17current
st4OutletActivePowerEvent
NOTIFICATION-TYPE
Outlet active power event.
1.3.6.1.4.1.1718.4.100.0.18current
st4OutletPowerFactorEvent
NOTIFICATION-TYPE
Outlet power factor event.
1.3.6.1.4.1.1718.4.100.0.19current
st4TempSensorEvent
NOTIFICATION-TYPE
Temperature sensor event.
1.3.6.1.4.1.1718.4.100.0.20current
st4HumidSensorEvent
NOTIFICATION-TYPE
Humidity sensor event.
1.3.6.1.4.1.1718.4.100.0.21current
st4WaterSensorStatusEvent
NOTIFICATION-TYPE
Water sensor status event.
1.3.6.1.4.1.1718.4.100.0.22current
st4CcSensorStatusEvent
NOTIFICATION-TYPE
Contact closure sensor status event.
1.3.6.1.4.1.1718.4.100.0.23current
st4AdcSensorEvent
NOTIFICATION-TYPE
Analog-to-digital converter sensor event.
1.3.6.1.4.1.1718.4.100.0.24current
st4FanSensorEvent
NOTIFICATION-TYPE
Fan sensor event.
1.3.6.1.4.1.1718.4.100.0.25current

Conformance

NameOIDStatus
st4SystemObjectsGroup
OBJECT-GROUP
System objects group.
1.3.6.1.4.1.1718.4.200.1.1current
st4UnitObjectsGroup
OBJECT-GROUP
Unit objects group.
1.3.6.1.4.1.1718.4.200.1.2current
st4InputCordObjectsGroup
OBJECT-GROUP
Input cord objects group.
1.3.6.1.4.1.1718.4.200.1.3current
st4LineObjectsGroup
OBJECT-GROUP
Line objects group.
1.3.6.1.4.1.1718.4.200.1.4current
st4PhaseObjectsGroup
OBJECT-GROUP
Phase objects group.
1.3.6.1.4.1.1718.4.200.1.5current
st4OcpObjectsGroup
OBJECT-GROUP
Over-current protector objects group.
1.3.6.1.4.1.1718.4.200.1.6current
st4BranchObjectsGroup
OBJECT-GROUP
Branch objects group.
1.3.6.1.4.1.1718.4.200.1.7current
st4OutletObjectsGroup
OBJECT-GROUP
Outlet objects group.
1.3.6.1.4.1.1718.4.200.1.8current
st4TempSensorObjectsGroup
OBJECT-GROUP
Temperature sensor objects group.
1.3.6.1.4.1.1718.4.200.1.9current
st4HumidSensorObjectsGroup
OBJECT-GROUP
Humidity sensor objects group.
1.3.6.1.4.1.1718.4.200.1.10current
st4WaterSensorObjectsGroup
OBJECT-GROUP
Water sensor objects group.
1.3.6.1.4.1.1718.4.200.1.11current
st4CcSensorObjectsGroup
OBJECT-GROUP
Contact closure sensor objects group.
1.3.6.1.4.1.1718.4.200.1.12current
st4AdcSensorObjectsGroup
OBJECT-GROUP
Analog-to-digital converter sensor objects group.
1.3.6.1.4.1.1718.4.200.1.13current
st4FanSensorObjectsGroup
OBJECT-GROUP
Fan sensor objects group.
1.3.6.1.4.1.1718.4.200.1.14current
st4EventInfoObjectsGroup
OBJECT-GROUP
Event information objects group.
1.3.6.1.4.1.1718.4.200.1.99current
st4EventNotificationsGroup
NOTIFICATION-GROUP
Event notifications group.
1.3.6.1.4.1.1718.4.200.1.100current
st4ModuleCompliances
MODULE-COMPLIANCE
The requirements for conformance to the Sentry4-MIB.
1.3.6.1.4.1.1718.4.200.2.1current