Sentry3-MIB
- Registered at
- 1.3.6.1.4.1.1718.3
- Last updated
- 2016-01-25 16:30
- Organization
- Server Technology, Inc.
- Revisions
- 2016-01-25 16:30, 2014-06-25 12:00, 2014-01-16 18:00, 2013-11-25 09:00, 2013-09-16 10:00, 2013-02-14 09:30, 2012-11-07 14:00, 2012-04-18 14:00, 2012-01-04 11:00, 2011-07-11 16:40, 2011-06-15 13:00, 2011-05-05 11:00, 2010-07-07 12:15, 2009-03-10 16:00, 2008-05-07 15:20, 2007-07-09 14:45, 2007-01-09 14:10, 2006-07-20 12:00, 2006-06-12 09:30, 2005-07-27 11:05, 2005-02-18 11:45, 2005-01-07 12:20, 2004-12-09 13:20, 2004-11-11 12:00, 2003-11-20 13:00, 2003-10-23 19:00, 2003-10-02 11:00, 2003-08-27 16:00, 2003-03-28 17:00, 2003-03-27 17:00
- Namespace
- sentry
- Source file
Sentry3-MIB- Digest
sha256:6c998f9f42ac4543626ea29fc34e341b17310cfb5286a2e0dd8154403dffb6f2
Description
This is the MIB module for the third generation of the Sentry product family. This includes the Sentry Remote Power Manager (RPM), Sentry Power Distribution Unit (PDU), Sentry Environmental Monitor (EM), Sentry Smart and Switched Cabinet Distribution Unit (CDU), and Sentry Switched -48 VDC.
Contact
Server Technology, Inc. 1040 Sandhill Road Reno, NV 89521 Tel: (775) 284-2000 Fax: (775) 284-2065 Email: mibmaster@servertech.com
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
SNMPv2-CONF SNMPv2-SMI SNMPv2-TC Sentry3-MIB
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| serverTech OBJECT-IDENTITY | 1.3.6.1.4.1.1718 | |||
| systemGroup OBJECT-IDENTITY | 1.3.6.1.4.1.1718.3.1 | |||
| systemVersion OBJECT-TYPE The firmware version of the system. | 1.3.6.1.4.1.1718.3.1.1 | DisplayString (SIZE(0..80)) | read-only | current |
| systemNICSerialNumber OBJECT-TYPE The serial number of the network interface card in the system. | 1.3.6.1.4.1.1718.3.1.2 | DisplayString (SIZE(0..8)) | read-only | current |
| systemLocation OBJECT-TYPE The location of the system. | 1.3.6.1.4.1.1718.3.1.3 | DisplayString (SIZE(0..32)) | read-write | current |
| systemTowerCount OBJECT-TYPE The number of towers in the system. | 1.3.6.1.4.1.1718.3.1.4 | INTEGER (0..4) | read-only | current |
| systemEnvMonCount OBJECT-TYPE The number of environmental monitors in the system. | 1.3.6.1.4.1.1718.3.1.5 | INTEGER (0..4) | read-only | current |
| systemTotalPower OBJECT-TYPE The total power consumption of all of the input feeds in the system. A non-negative value indicates the total power consumption in Watts. A negative value indicates that the total power consumption was not available. | 1.3.6.1.4.1.1718.3.1.6 | INTEGER (-1..150000) | read-only | current |
| systemArea OBJECT-TYPE The area that the footprint of the system occupies. A non-zero non-negative value indicates the area in tenths of area units as selected by the systemAreaUnit object. A zero or negative value indicates that the area was not available. | 1.3.6.1.4.1.1718.3.1.7 | INTEGER (0..1000) | read-write | current |
| systemWattsPerAreaUnit OBJECT-TYPE The system Watts per area unit. A non-negative value indicates the power consumption per area unit as selected by the systemAreaUnit object. A negative value indicates that the power consumption per area unit was not available. | 1.3.6.1.4.1.1718.3.1.8 | INTEGER (-1..1500000) | read-only | current |
| systemAreaUnit OBJECT-TYPE The unit of area for the systemArea and systemWattsPerAreaUnit objects. If the agent does not support this object, then the unit of area is a square foot. | 1.3.6.1.4.1.1718.3.1.9 | INTEGER {squareMeter(0), squareFoot(1)} | read-write | current |
| systemPowerFactor OBJECT-TYPE The power factor used in power calculations performed by the system. | 1.3.6.1.4.1.1718.3.1.10 | INTEGER (50..100) | read-write | current |
| systemFeatures OBJECT-TYPE The key-activated features enabled in the system. | 1.3.6.1.4.1.1718.3.1.11 | Bits {smartLoadShedding(0), snmpPOPS(1), outletControlInhibit(2)} | read-only | current |
| systemFeatureKey OBJECT-TYPE A valid feature key written to this object will enable a feature in the system. A valid feature key is in the form xxxx-xxxx-xxxx-xxxx. A read of this object returns an empty string. | 1.3.6.1.4.1.1718.3.1.12 | DisplayString (SIZE(0..19)) | read-write | current |
| systemOutletSeqInterval OBJECT-TYPE The power-on sequencing interval for all outlets. | 1.3.6.1.4.1.1718.3.1.13 | INTEGER (0..15) | read-write | current |
| systemOutletRebootDelay OBJECT-TYPE The reboot delay for all outlets. | 1.3.6.1.4.1.1718.3.1.14 | INTEGER (5..600) | read-write | current |
| systemConfigModifiedCount OBJECT-TYPE The total number of times the system configuration has changed. | 1.3.6.1.4.1.1718.3.1.15 | INTEGER (0..2147483647) | read-only | current |
| systemTables OBJECT-IDENTITY | 1.3.6.1.4.1.1718.3.2 | |||
| towerTable OBJECT-TYPE A table of towers. | 1.3.6.1.4.1.1718.3.2.1 | not-accessible | current | |
| towerEntry OBJECT-TYPE Row definition for the tower table. | 1.3.6.1.4.1.1718.3.2.1.1 | not-accessible | current | |
| towerIndex OBJECT-TYPE Index for the tower table. | 1.3.6.1.4.1.1718.3.2.1.1.1 | INTEGER (0..4) | not-accessible | current |
| towerID OBJECT-TYPE The ID of the tower. | 1.3.6.1.4.1.1718.3.2.1.1.2 | DisplayString (SIZE(1)) | read-only | current |
| towerName OBJECT-TYPE The name of the tower. | 1.3.6.1.4.1.1718.3.2.1.1.3 | DisplayString (SIZE(0..24)) | read-write | current |
| towerStatus OBJECT-TYPE The operational status of the tower. | 1.3.6.1.4.1.1718.3.2.1.1.4 | INTEGER {normal(0), noComm(1), fanFail(2), overTemp(3), nvmFail(4), outOfBalance(5)} | read-only | current |
| towerInfeedCount OBJECT-TYPE The number of input feeds on the tower. | 1.3.6.1.4.1.1718.3.2.1.1.5 | INTEGER (0..4) | read-only | current |
| towerProductSN OBJECT-TYPE The product serial number of the tower. | 1.3.6.1.4.1.1718.3.2.1.1.6 | DisplayString (SIZE(0..16)) | read-only | current |
| towerModelNumber OBJECT-TYPE The model number of the tower. | 1.3.6.1.4.1.1718.3.2.1.1.7 | DisplayString (SIZE(0..24)) | read-only | current |
| towerCapabilities OBJECT-TYPE The capabilities of the tower. | 1.3.6.1.4.1.1718.3.2.1.1.8 | Bits {failSafe(0), fuseSense(1), directCurrent(2), threePhase(3), fanSense(4), tempSense(5)} | read-only | current |
| towerVACapacity OBJECT-TYPE The total apparent power capacity of the tower circuit. A non-negative value indicates the maximum total apparent power in Volt-Amps. A negative value indicates that the total apparent power capacity was not available. | 1.3.6.1.4.1.1718.3.2.1.1.9 | INTEGER (-1..50000) | read-only | current |
| towerVACapacityUsed OBJECT-TYPE The used percentage of the tower circuit total apparent power capacity (towerApparentPower / towerVACapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentage of capacity used was not available. | 1.3.6.1.4.1.1718.3.2.1.1.10 | INTEGER (-1..1500) | read-only | current |
| towerActivePower OBJECT-TYPE The total active power consumption of the tower circuit. A non-negative value indicates the total active power consumption in Watts. A negative value indicates that the total active power consumption was not available. | 1.3.6.1.4.1.1718.3.2.1.1.11 | INTEGER (-1..50000) | read-only | current |
| towerApparentPower OBJECT-TYPE The total apparent power consumption of the tower circuit. A non-negative value indicates the total apparent power consumption in Volt-Amps. A negative value indicates that the total apparent power consumption was not available. | 1.3.6.1.4.1.1718.3.2.1.1.12 | INTEGER (-1..50000) | read-only | current |
| towerPowerFactor OBJECT-TYPE The overall power factor of the tower circuit. A non- negative value indicates the overall power factor in hundredths. A negative value indicates that the overall power factor was not able to be measured. | 1.3.6.1.4.1.1718.3.2.1.1.13 | INTEGER (-1..100) | read-only | current |
| towerEnergy OBJECT-TYPE The total energy consumption of the tower circuit. A non- negative value indicates the total energy consumption in Kilowatt-Hours. A negative value indicates that the total energy consumption was not available. | 1.3.6.1.4.1.1718.3.2.1.1.14 | INTEGER (-1..2147483647) | read-only | current |
| towerLineFrequency OBJECT-TYPE The frequency of the input feed line voltage. A non- negative value indicates the frequency in Hertz. A negative value indicates that the frequency was not available. | 1.3.6.1.4.1.1718.3.2.1.1.15 | INTEGER (-1..60) | read-only | current |
| infeedTable OBJECT-TYPE A table of input feeds. | 1.3.6.1.4.1.1718.3.2.2 | not-accessible | current | |
| infeedEntry OBJECT-TYPE Row definition for the input feed table. | 1.3.6.1.4.1.1718.3.2.2.1 | not-accessible | current | |
| infeedIndex OBJECT-TYPE Index for the input feed table. | 1.3.6.1.4.1.1718.3.2.2.1.1 | INTEGER (0..4) | not-accessible | current |
| infeedID OBJECT-TYPE The ID of the input feed. | 1.3.6.1.4.1.1718.3.2.2.1.2 | DisplayString (SIZE(2)) | read-only | current |
| infeedName OBJECT-TYPE The name of the input feed. | 1.3.6.1.4.1.1718.3.2.2.1.3 | DisplayString (SIZE(0..24)) | read-write | current |
| infeedCapabilities OBJECT-TYPE The capabilities of the input feed. | 1.3.6.1.4.1.1718.3.2.2.1.4 | Bits {onSense(0), loadSense(1), powerControl(2), failSafe(3), defaultOff(4), voltageSense(5), powerSense(6), branchOnSense(7), branchLoadSense(8)} | read-only | current |
| infeedStatus OBJECT-TYPE The status of the input feed line. If the infeedCapabilities 'onSense' bit is TRUE, then all of the states are supported and indicate the sensed state of the input feed. If the infeedCapabilities 'onSense' bit is FALSE, then only the 'on' and 'noComm' states are supported, and 'on' indicates a derived state, not a sensed state. | 1.3.6.1.4.1.1718.3.2.2.1.5 | INTEGER {off(0), on(1), offWait(2), onWait(3), offError(4), onError(5), noComm(6), reading(7), offFuse(8), onFuse(9)} | read-only | current |
| infeedLoadStatus OBJECT-TYPE The status of the load measured on the input feed line. If the infeedCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the infeedCapabilities 'loadSense' bit is FALSE, then only the 'normal' and 'noComm' states are supported. | 1.3.6.1.4.1.1718.3.2.2.1.6 | INTEGER {normal(0), notOn(1), reading(2), loadLow(3), loadHigh(4), overLoad(5), readError(6), noComm(7)} | read-only | current |
| infeedLoadValue OBJECT-TYPE The load measured on the input feed line. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured. | 1.3.6.1.4.1.1718.3.2.2.1.7 | INTEGER (-1..60000) | read-only | current |
| infeedLoadHighThresh OBJECT-TYPE The load high threshold value of the input feed line in Amps. | 1.3.6.1.4.1.1718.3.2.2.1.8 | INTEGER (0..600) | read-write | current |
| infeedOutletCount OBJECT-TYPE The number of controlled and/or monitored outlets on the input feed. | 1.3.6.1.4.1.1718.3.2.2.1.9 | INTEGER (0..64) | read-only | current |
| infeedCapacity OBJECT-TYPE The load capacity of the input feed line. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available. | 1.3.6.1.4.1.1718.3.2.2.1.10 | INTEGER (-1..600) | read-only | current |
| infeedVoltage OBJECT-TYPE The line-to-line voltage of the input feed. A non-negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available. | 1.3.6.1.4.1.1718.3.2.2.1.11 | INTEGER (-1..4800) | read-only | current |
| infeedPower OBJECT-TYPE The active power consumption of the input feed phase. A non- negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available. | 1.3.6.1.4.1.1718.3.2.2.1.12 | INTEGER (-1..25000) | read-only | current |
| infeedApparentPower OBJECT-TYPE The apparent power consumption of the input feed phase. A non-negative value indicates the apparent power consumption in Volt-Amps. A negative value indicates that the apparent power consumption was not available. | 1.3.6.1.4.1.1718.3.2.2.1.13 | INTEGER (-1..25000) | read-only | current |
| infeedPowerFactor OBJECT-TYPE The power factor of the input feed phase. A non-negative value indicates the power factor in hundredths. A negative value indicates that the power factor was not able to be measured. | 1.3.6.1.4.1.1718.3.2.2.1.14 | INTEGER (-1..100) | read-only | current |
| infeedCrestFactor OBJECT-TYPE The crest factor for the load of the input feed phase. A non-negative value indicates the crest factor in tenths. A negative value indicates that the crest factor was not able to be measured. | 1.3.6.1.4.1.1718.3.2.2.1.15 | INTEGER (-1..1000) | read-only | current |
| infeedEnergy OBJECT-TYPE The energy consumption of the input feed phase. A non- negative value indicates the energy consumption in tenths of Kilowatt-Hours. A negative value indicates that the energy consumption was not available. | 1.3.6.1.4.1.1718.3.2.2.1.16 | INTEGER (-1..2147483647) | read-only | current |
| infeedReactance OBJECT-TYPE The characterization of the phase relation between the voltage and current of the input feed phase. | 1.3.6.1.4.1.1718.3.2.2.1.17 | INTEGER {unknown(0), capacitive(1), inductive(2), resistive(3)} | read-only | current |
| infeedPhaseVoltage OBJECT-TYPE The voltage measured for the input feed phase. A non- negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available. | 1.3.6.1.4.1.1718.3.2.2.1.18 | INTEGER (-1..2640) | read-only | current |
| infeedPhaseCurrent OBJECT-TYPE The current measured for the input feed phase. A non- negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured. | 1.3.6.1.4.1.1718.3.2.2.1.19 | INTEGER (-1..25500) | read-only | current |
| infeedCapacityUsed OBJECT-TYPE The used percentage of the input feed line load capacity (infeedLoadValue / infeedCapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentage of capacity used was not available. | 1.3.6.1.4.1.1718.3.2.2.1.20 | INTEGER (-1..1500) | read-only | current |
| infeedLineID OBJECT-TYPE The ID of the input feed line. | 1.3.6.1.4.1.1718.3.2.2.1.21 | DisplayString (SIZE(0..4)) | read-only | current |
| infeedLineToLineID OBJECT-TYPE The line-to-line ID of the input feed. | 1.3.6.1.4.1.1718.3.2.2.1.22 | DisplayString (SIZE(0..7)) | read-only | current |
| infeedPhaseID OBJECT-TYPE The ID of the input feed phase. | 1.3.6.1.4.1.1718.3.2.2.1.23 | DisplayString (SIZE(0..6)) | read-only | current |
| infeedVACapacity OBJECT-TYPE The apparent power capacity of the input feed circuit. A non-negative value indicates the maximum apparent power in Volt-Amps. A negative value indicates that the apparent power capacity was not available. | 1.3.6.1.4.1.1718.3.2.2.1.24 | INTEGER (-1..25000) | read-only | current |
| infeedVACapacityUsed OBJECT-TYPE The used percentage of the input feed circuit apparent power capacity (infeedApparentPower / infeedVACapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentage of capacity used was not available. | 1.3.6.1.4.1.1718.3.2.2.1.25 | INTEGER (-1..1500) | read-only | current |
| outletTable OBJECT-TYPE A table of outlets. | 1.3.6.1.4.1.1718.3.2.3 | not-accessible | current | |
| outletEntry OBJECT-TYPE Row definition for the outlet table. | 1.3.6.1.4.1.1718.3.2.3.1 | not-accessible | current | |
| outletIndex OBJECT-TYPE Index for the outlet table. | 1.3.6.1.4.1.1718.3.2.3.1.1 | INTEGER (0..64) | not-accessible | current |
| outletID OBJECT-TYPE The ID of the outlet. | 1.3.6.1.4.1.1718.3.2.3.1.2 | DisplayString (SIZE(2..4)) | read-only | current |
| outletName OBJECT-TYPE The name of the outlet. | 1.3.6.1.4.1.1718.3.2.3.1.3 | DisplayString (SIZE(0..24)) | read-write | current |
| outletCapabilities OBJECT-TYPE The capabilities of the outlet. | 1.3.6.1.4.1.1718.3.2.3.1.4 | Bits {onSense(0), loadSense(1), powerControl(2), shutdown(3), defaultOn(4), ownInfeed(5), fusedBranch(6), voltageSense(7), powerSense(8)} | read-only | current |
| outletStatus OBJECT-TYPE The status of the outlet. If the outletCapabilities 'onSense' bit is TRUE, then the state indicates the sensed state of the outlet, not a derived state, and 'offError' and 'onError' are supported to indicate a mismatch between the control and sensed state. If the outletCapabilities 'fusedBranch' bit is TRUE, then the outlet is on a fused branch circuit that can detect the fuse state, and 'offFuse' and 'onFuse' are supported to indicate a fuse error. | 1.3.6.1.4.1.1718.3.2.3.1.5 | INTEGER {off(0), on(1), offWait(2), onWait(3), offError(4), onError(5), noComm(6), reading(7), offFuse(8), onFuse(9)} | read-only | current |
| outletLoadStatus OBJECT-TYPE The status of the load measured on the outlet. If the outletCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the outletCapabilities 'loadSense' bit is FALSE, then only the 'normal' and 'noComm' states are supported. | 1.3.6.1.4.1.1718.3.2.3.1.6 | INTEGER {normal(0), notOn(1), reading(2), loadLow(3), loadHigh(4), overLoad(5), readError(6), noComm(7)} | read-only | current |
| outletLoadValue OBJECT-TYPE The load measured on the outlet. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured. | 1.3.6.1.4.1.1718.3.2.3.1.7 | INTEGER (-1..25500) | read-only | current |
| outletLoadLowThresh OBJECT-TYPE The load low threshold value of the outlet in Amps. | 1.3.6.1.4.1.1718.3.2.3.1.8 | INTEGER (0..255) | read-write | current |
| outletLoadHighThresh OBJECT-TYPE The load high threshold value of the outlet in Amps. | 1.3.6.1.4.1.1718.3.2.3.1.9 | INTEGER (0..255) | read-write | current |
| outletControlState OBJECT-TYPE The control state of the outlet. The supported states are dependent upon the outletCapabilities 'powerControl' and 'shutdown' bits, as well as the supported features of the firmware version. | 1.3.6.1.4.1.1718.3.2.3.1.10 | INTEGER {idleOff(0), idleOn(1), wakeOff(2), wakeOn(3), off(4), on(5), lockedOff(6), lockedOn(7), reboot(8), shutdown(9), pendOn(10), pendOff(11), minimumOff(12), minimumOn(13), eventOff(14), eventOn(15), eventReboot(16), eventShutdown(17)} | read-only | current |
| outletControlAction OBJECT-TYPE An action to change the control state of the outlet. If the outletCapabilities 'powerControl' bit is TRUE, then the 'on', 'off', and 'reboot' actions can be used to change the control state of the outlet. If the outletCapabilities 'powerControl' bit is FALSE, then the actions have no effect. | 1.3.6.1.4.1.1718.3.2.3.1.11 | INTEGER {none(0), on(1), off(2), reboot(3)} | read-write | current |
| outletCapacity OBJECT-TYPE The load capacity of the outlet. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available. | 1.3.6.1.4.1.1718.3.2.3.1.12 | INTEGER (-1..255) | read-only | current |
| outletVoltage OBJECT-TYPE The voltage of the outlet. A non-negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available. | 1.3.6.1.4.1.1718.3.2.3.1.13 | INTEGER (-1..2640) | read-only | current |
| outletPower OBJECT-TYPE The active power consumption of the device plugged into the outlet. A non-negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available. | 1.3.6.1.4.1.1718.3.2.3.1.14 | INTEGER (-1..10000) | read-only | current |
| outletApparentPower OBJECT-TYPE The apparent power consumption of the device plugged into the outlet. A non-negative value indicates the apparent power consumption in Volt-Amps. A negative value indicates that the apparent power consumption was not available. | 1.3.6.1.4.1.1718.3.2.3.1.15 | INTEGER (-1..10000) | read-only | current |
| outletPowerFactor OBJECT-TYPE The power factor of the device plugged into the outlet. A non-negative value indicates the power factor in hundredths. A negative value indicates that the power factor was not able to be measured. | 1.3.6.1.4.1.1718.3.2.3.1.16 | INTEGER (-1..100) | read-only | current |
| outletCrestFactor OBJECT-TYPE The crest factor for the load of the device plugged into the outlet. A non-negative value indicates the crest factor in tenths. A negative value indicates that the crest factor was not able to be measured. | 1.3.6.1.4.1.1718.3.2.3.1.17 | INTEGER (-1..1000) | read-only | current |
| outletEnergy OBJECT-TYPE The energy consumption of the device plugged into the outlet. A non-negative value indicates the energy consumption in Watt-Hours. A negative value indicates that the energy consumption was not available. | 1.3.6.1.4.1.1718.3.2.3.1.18 | INTEGER (-1..2147483647) | read-only | current |
| outletWakeupState OBJECT-TYPE The wakeup state of the outlet. | 1.3.6.1.4.1.1718.3.2.3.1.19 | INTEGER {last(1), off(2), on(3)} | read-write | current |
| outletPostOnDelay OBJECT-TYPE The post-on delay of the outlet. | 1.3.6.1.4.1.1718.3.2.3.1.20 | INTEGER (0..900) | read-write | current |
| envMonTable OBJECT-TYPE A table of environmental monitors. | 1.3.6.1.4.1.1718.3.2.4 | not-accessible | current | |
| envMonEntry OBJECT-TYPE Row definition for the environmental monitor table. | 1.3.6.1.4.1.1718.3.2.4.1 | not-accessible | current | |
| envMonIndex OBJECT-TYPE Index for the environmental monitor table. | 1.3.6.1.4.1.1718.3.2.4.1.1 | INTEGER (0..4) | not-accessible | current |
| envMonID OBJECT-TYPE The ID of the environmental monitor. | 1.3.6.1.4.1.1718.3.2.4.1.2 | DisplayString (SIZE(1)) | read-only | current |
| envMonName OBJECT-TYPE The name of the environmental monitor. | 1.3.6.1.4.1.1718.3.2.4.1.3 | DisplayString (SIZE(0..24)) | read-write | current |
| envMonStatus OBJECT-TYPE The operational status of the environmental monitor. | 1.3.6.1.4.1.1718.3.2.4.1.4 | INTEGER {normal(0), noComm(1)} | read-only | current |
| envMonWaterSensorName OBJECT-TYPE The name of the water sensor. | 1.3.6.1.4.1.1718.3.2.4.1.5 | DisplayString (SIZE(0..24)) | read-write | current |
| envMonWaterSensorStatus OBJECT-TYPE The status of the water sensor. | 1.3.6.1.4.1.1718.3.2.4.1.6 | INTEGER {normal(0), alarm(1), noComm(2)} | read-only | current |
| envMonADCName OBJECT-TYPE The name of the analog-to-digital converter. | 1.3.6.1.4.1.1718.3.2.4.1.7 | DisplayString (SIZE(0..24)) | read-write | current |
| envMonADCStatus OBJECT-TYPE The status of the analog-to-digital converter. | 1.3.6.1.4.1.1718.3.2.4.1.8 | INTEGER {normal(0), reading(1), countLow(2), countHigh(3), readError(4), noComm(5)} | read-only | current |
| envMonADCCount OBJECT-TYPE The 8-bit count value from the analog-to-digital converter. A non-negative value indicates the digital value retrieved from the ADC. A negative value indicates that a digital value was not able to be retrieved. | 1.3.6.1.4.1.1718.3.2.4.1.9 | INTEGER (-1..255) | read-only | current |
| envMonADCLowThresh OBJECT-TYPE The 8-bit count low threshold value of the analog-to-digital converter. | 1.3.6.1.4.1.1718.3.2.4.1.10 | INTEGER (0..255) | read-write | current |
| envMonADCHighThresh OBJECT-TYPE The 8-bit count high threshold value of the analog-to-digital converter. | 1.3.6.1.4.1.1718.3.2.4.1.11 | INTEGER (0..255) | read-write | current |
| envMonTempHumidSensorCount OBJECT-TYPE The number of temperature/humidity sensors on the environmental monitor. | 1.3.6.1.4.1.1718.3.2.4.1.12 | INTEGER (0..2) | read-only | current |
| envMonContactClosureCount OBJECT-TYPE The number of contact closures on the environmental monitor. | 1.3.6.1.4.1.1718.3.2.4.1.13 | INTEGER (0..4) | read-only | current |
| tempHumidSensorTable OBJECT-TYPE A table of temperature/humidity sensors. | 1.3.6.1.4.1.1718.3.2.5 | not-accessible | current | |
| tempHumidSensorEntry OBJECT-TYPE Row definition for the temperature/humidity sensor table. | 1.3.6.1.4.1.1718.3.2.5.1 | not-accessible | current | |
| tempHumidSensorIndex OBJECT-TYPE Index for the temperature/humidity sensor table. | 1.3.6.1.4.1.1718.3.2.5.1.1 | INTEGER (0..2) | not-accessible | current |
| tempHumidSensorID OBJECT-TYPE The ID of the temperature/humidity sensor. | 1.3.6.1.4.1.1718.3.2.5.1.2 | DisplayString (SIZE(2)) | read-only | current |
| tempHumidSensorName OBJECT-TYPE The name of the temperature/humidity sensor. | 1.3.6.1.4.1.1718.3.2.5.1.3 | DisplayString (SIZE(0..24)) | read-write | current |
| tempHumidSensorStatus OBJECT-TYPE The operational status of the temperature/humidity sensor. | 1.3.6.1.4.1.1718.3.2.5.1.4 | INTEGER {found(0), notFound(1), lost(2), noComm(3)} | read-only | current |
| tempHumidSensorTempStatus OBJECT-TYPE The status of the temperature sensor. | 1.3.6.1.4.1.1718.3.2.5.1.5 | INTEGER {normal(0), notFound(1), reading(2), tempLow(3), tempHigh(4), readError(5), lost(6), noComm(7)} | read-only | current |
| tempHumidSensorTempValue OBJECT-TYPE The temperature measured by the sensor. A non-negative value indicates the measured temperature in tenths of degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is Celsius. A negative value indicates that a temperature value was not able to be measured. | 1.3.6.1.4.1.1718.3.2.5.1.6 | INTEGER (-1..2540) | read-only | current |
| tempHumidSensorTempLowThresh OBJECT-TYPE The temperature low threshold value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is Celsius. | 1.3.6.1.4.1.1718.3.2.5.1.7 | INTEGER (0..254) | read-write | current |
| tempHumidSensorTempHighThresh OBJECT-TYPE The temperature high threshold value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is Celsius. | 1.3.6.1.4.1.1718.3.2.5.1.8 | INTEGER (0..254) | read-write | current |
| tempHumidSensorHumidStatus OBJECT-TYPE The status of the humidity sensor. | 1.3.6.1.4.1.1718.3.2.5.1.9 | INTEGER {normal(0), notFound(1), reading(2), humidLow(3), humidHigh(4), readError(5), lost(6), noComm(7)} | read-only | current |
| tempHumidSensorHumidValue OBJECT-TYPE The humidity measured by the sensor. A non-negative value indicates the measured humidity in percentage relative humidity. A negative value indicates that a humidity value was not able to be measured. | 1.3.6.1.4.1.1718.3.2.5.1.10 | INTEGER (-1..100) | read-only | current |
| tempHumidSensorHumidLowThresh OBJECT-TYPE The humidity low threshold value of the sensor in percentage relative humidity. | 1.3.6.1.4.1.1718.3.2.5.1.11 | INTEGER (0..100) | read-write | current |
| tempHumidSensorHumidHighThresh OBJECT-TYPE The humidity low threshold value of the sensor in percentage relative humidity. | 1.3.6.1.4.1.1718.3.2.5.1.12 | INTEGER (0..100) | read-write | current |
| tempHumidSensorTempScale OBJECT-TYPE The scale used for temperature values. This is a global setting for all temperature values in the system. If the agent does not support this object, then the temperature scale used is Celsius. | 1.3.6.1.4.1.1718.3.2.5.1.13 | INTEGER {celsius(0), fahrenheit(1)} | read-write | current |
| tempHumidSensorTempRecDelta OBJECT-TYPE The temperature recovery delta (hysteresis) value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale. | 1.3.6.1.4.1.1718.3.2.5.1.14 | INTEGER (0..54) | read-write | current |
| tempHumidSensorHumidRecDelta OBJECT-TYPE The humidity recovery delta (hysteresis) value of the sensor in percentage relative humidity. | 1.3.6.1.4.1.1718.3.2.5.1.15 | INTEGER (0..20) | read-write | current |
| contactClosureTable OBJECT-TYPE A table of contact closures. | 1.3.6.1.4.1.1718.3.2.6 | not-accessible | current | |
| contactClosureEntry OBJECT-TYPE Row definition for the contact closure table. | 1.3.6.1.4.1.1718.3.2.6.1 | not-accessible | current | |
| contactClosureIndex OBJECT-TYPE Index for the contact closure table. | 1.3.6.1.4.1.1718.3.2.6.1.1 | INTEGER (0..4) | not-accessible | current |
| contactClosureID OBJECT-TYPE The ID of the contact closure. | 1.3.6.1.4.1.1718.3.2.6.1.2 | DisplayString (SIZE(2)) | read-only | current |
| contactClosureName OBJECT-TYPE The name of the contact closure. | 1.3.6.1.4.1.1718.3.2.6.1.3 | DisplayString (SIZE(0..24)) | read-write | current |
| contactClosureStatus OBJECT-TYPE The status of the contact closure. | 1.3.6.1.4.1.1718.3.2.6.1.4 | INTEGER {normal(0), alarm(1), noComm(2)} | read-only | current |
| branchTable OBJECT-TYPE A table of branches. | 1.3.6.1.4.1.1718.3.2.7 | not-accessible | current | |
| branchEntry OBJECT-TYPE Row definition for the branch table. | 1.3.6.1.4.1.1718.3.2.7.1 | not-accessible | current | |
| branchIndex OBJECT-TYPE Index for the branch table. | 1.3.6.1.4.1.1718.3.2.7.1.1 | INTEGER (0..4) | not-accessible | current |
| branchID OBJECT-TYPE The ID of the branch. | 1.3.6.1.4.1.1718.3.2.7.1.2 | DisplayString (SIZE(3)) | read-only | current |
| branchName OBJECT-TYPE The name of the branch. | 1.3.6.1.4.1.1718.3.2.7.1.3 | DisplayString (SIZE(0..24)) | read-write | current |
| branchCapabilities OBJECT-TYPE The capabilities of the branch. | 1.3.6.1.4.1.1718.3.2.7.1.4 | Bits {onSense(0), loadSense(1)} | read-only | current |
| branchStatus OBJECT-TYPE The status of the branch. | 1.3.6.1.4.1.1718.3.2.7.1.5 | INTEGER {off(0), on(1), offWait(2), onWait(3), offError(4), onError(5), noComm(6), reading(7), offFuse(8), onFuse(9)} | read-only | current |
| branchLoadStatus OBJECT-TYPE The status of the load measured on the branch. | 1.3.6.1.4.1.1718.3.2.7.1.6 | INTEGER {normal(0), notOn(1), reading(2), loadLow(3), loadHigh(4), overLoad(5), readError(6), noComm(7)} | read-only | current |
| branchLoadValue OBJECT-TYPE The load measured on the branch. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured. | 1.3.6.1.4.1.1718.3.2.7.1.7 | INTEGER (-1..4000) | read-only | current |
| branchLoadHighThresh OBJECT-TYPE The load high threshold value of the branch in Amps. | 1.3.6.1.4.1.1718.3.2.7.1.8 | INTEGER (0..40) | read-write | current |
| branchCapacity OBJECT-TYPE The load capacity of the branch. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available. | 1.3.6.1.4.1.1718.3.2.7.1.9 | INTEGER (-1..40) | read-only | current |
| eventInformationGroup OBJECT-IDENTITY | 1.3.6.1.4.1.1718.3.99 | |||
| eventStatusText OBJECT-TYPE The text representation of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A get of this object will return a NULL string. | 1.3.6.1.4.1.1718.3.99.1 | DisplayString (SIZE(0..20)) | read-only | current |
| eventStatusCondition OBJECT-TYPE The condition of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A get of this object will return zero. | 1.3.6.1.4.1.1718.3.99.2 | INTEGER {nonError(0), error(1)} | read-only | current |
| sentry3Traps OBJECT-IDENTITY | 1.3.6.1.4.1.1718.3.100 | |||
| events OBJECT-IDENTITY | 1.3.6.1.4.1.1718.3.100.0 |
Notifications
| Name | OID | Status |
|---|---|---|
| towerStatusEvent NOTIFICATION-TYPE Tower status event. If enabled, this trap is sent when the towerStatus indicates an error state ('noComm', 'fanFail', 'overTemp', 'nvmFail', or 'outOfBalance'). This trap is repeated periodically while the towerStatus remains in an error state. If the towerStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error towerStatus, and then stops being repeated. While the towerStatus indicates a 'noComm' error state, all status and load traps are suppressed for input feeds and outlets on the tower. | 1.3.6.1.4.1.1718.3.100.0.1 | current |
| infeedStatusEvent NOTIFICATION-TYPE Input feed status event. If enabled, this trap is sent when the infeedStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is repeated periodically while the infeedStatus remains in an error state. If the infeedStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error infeedStatus, and then stops being repeated. While the infeedStatus indicates an error state, load traps are suppressed for the input feed, and, if the infeedCapabilities 'failSafe' bit is FALSE, all status and load traps are suppressed for outlets on the input feed. | 1.3.6.1.4.1.1718.3.100.0.2 | current |
| infeedLoadEvent NOTIFICATION-TYPE Input feed load event. If enabled, this trap is sent when the infeedLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the infeedLoadStatus remains in an error state. If the infeedLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error infeedLoadStatus, and then stops being repeated. | 1.3.6.1.4.1.1718.3.100.0.3 | current |
| outletStatusEvent NOTIFICATION-TYPE Outlet status event. If enabled, this trap is sent when the outletStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is repeated periodically while the outletStatus remains in an error state. If the outletStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error outletStatus, and then stops being repeated. While the outletStatus indicates an error state, load traps are suppressed for the outlet. | 1.3.6.1.4.1.1718.3.100.0.4 | current |
| outletLoadEvent NOTIFICATION-TYPE Outlet load event. If enabled, this trap is sent when the outletLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the outletLoadStatus remains in an error state. If the outletLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error outletLoadStatus, and then stops being repeated. | 1.3.6.1.4.1.1718.3.100.0.5 | current |
| outletChangeEvent NOTIFICATION-TYPE Outlet on/off change event. If enabled, this trap is sent when the outletStatus changes from any 'on' state ('on', 'onWait', 'onError', or 'onFuse') to any 'off' state ('off', 'offWait', 'offError', or 'offFuse'), and vice-versa. | 1.3.6.1.4.1.1718.3.100.0.6 | current |
| envMonStatusEvent NOTIFICATION-TYPE Environmental monitor status event. If enabled, this trap is sent when the envMonStatus indicates an error state ('noComm'). This trap is repeated periodically while the envMonStatus remains in an error state. If the envMonStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonStatus, and then stops being repeated. While the envMonStatus indicates an error state, all status traps are suppressed for the water sensor, ADC, temperature/ humidity sensors, and contact closures on the environmental monitor. | 1.3.6.1.4.1.1718.3.100.0.7 | current |
| envMonWaterSensorEvent NOTIFICATION-TYPE Environmental monitor water sensor event. If enabled, this trap is sent when the envMonWaterSensorStatus indicates an error state ('alarm'). This trap is repeated periodically while the envMonWaterSensorStatus remains in an error state. If the envMonWaterSensorStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonWaterSensorStatus, and then stops being repeated. | 1.3.6.1.4.1.1718.3.100.0.8 | current |
| envMonADCEvent NOTIFICATION-TYPE Environmental monitor analog-to-digital converter event. If enabled, this trap is sent when the envMonADCStatus indicates an error state ('countLow' or 'countHigh'). This trap is repeated periodically while the envMonADCStatus remains in an error state. If the envMonADCStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonADCStatus, and then stops being repeated. | 1.3.6.1.4.1.1718.3.100.0.9 | current |
| tempHumidSensorStatusEvent NOTIFICATION-TYPE Temperature/humidity sensor status event. If enabled, this trap is sent when the tempHumidSensorStatus indicates an error state ('lost'). This trap is repeated periodically while the tempHumidSensorStatus remains in an error state. If the tempHumidSensorStatus returns to a non-error state ('found'), this trap is sent once more with the non-error tempHumidSensorStatus, and then stops being repeated. While the tempHumidSensorStatus indicates an error state, all temperature and humidity status traps are suppressed for the temperature/humidity sensor. | 1.3.6.1.4.1.1718.3.100.0.10 | current |
| tempHumidSensorTempEvent NOTIFICATION-TYPE Temperature/humidity sensor temperature event. If enabled, this trap is sent when the tempHumidSensorTempStatus indicates an error state ('tempLow' or 'tempHigh'). This trap is repeated periodically while the tempHumidSensorTempStatus remains in an error state. If the tempHumidSensorTempStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error tempHumidSensorTempStatus, and then stops being repeated. | 1.3.6.1.4.1.1718.3.100.0.11 | current |
| tempHumidSensorHumidEvent NOTIFICATION-TYPE Temperature/humidity sensor humidity event. If enabled, this trap is sent when the tempHumidSensorHumidStatus indicates an error state ('humidLow' or 'humidHigh'). This trap is repeated periodically while the tempHumidSensorHumidStatus remains in an error state. If the tempHumidSensorHumidStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error tempHumidSensorHumidStatus, and then stops being repeated. | 1.3.6.1.4.1.1718.3.100.0.12 | current |
| contactClosureEvent NOTIFICATION-TYPE Contact closure event. If enabled, this trap is sent when the contactClosureStatus indicates an error state ('alarm'). This trap is repeated periodically while the contactClosureStatus remains in an error state. If the contactClosureStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error contactClosureStatus, and then stops being repeated. | 1.3.6.1.4.1.1718.3.100.0.13 | current |
| branchStatusEvent NOTIFICATION-TYPE Branch status event. If enabled, this trap is sent when the branchStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is repeated periodically while the branchStatus remains in an error state. If the branchStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error branchStatus, and then stops being repeated. While the branchStatus indicates an error state, load traps are suppressed for the branch. | 1.3.6.1.4.1.1718.3.100.0.14 | current |
| branchLoadEvent NOTIFICATION-TYPE Branch load event. If enabled, this trap is sent when the branchLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the branchLoadStatus remains in an error state. If the branchLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error branchLoadStatus, and then stops being repeated. | 1.3.6.1.4.1.1718.3.100.0.15 | current |