MIBs Depot

Sentry3-MIB

Registered at
1.3.6.1.4.1.1718.3
Last updated
2016-01-25 16:30
Organization
Server Technology, Inc.
Revisions
2016-01-25 16:30, 2014-06-25 12:00, 2014-01-16 18:00, 2013-11-25 09:00, 2013-09-16 10:00, 2013-02-14 09:30, 2012-11-07 14:00, 2012-04-18 14:00, 2012-01-04 11:00, 2011-07-11 16:40, 2011-06-15 13:00, 2011-05-05 11:00, 2010-07-07 12:15, 2009-03-10 16:00, 2008-05-07 15:20, 2007-07-09 14:45, 2007-01-09 14:10, 2006-07-20 12:00, 2006-06-12 09:30, 2005-07-27 11:05, 2005-02-18 11:45, 2005-01-07 12:20, 2004-12-09 13:20, 2004-11-11 12:00, 2003-11-20 13:00, 2003-10-23 19:00, 2003-10-02 11:00, 2003-08-27 16:00, 2003-03-28 17:00, 2003-03-27 17:00
Namespace
sentry
Source file
Sentry3-MIB
Digest
sha256:6c998f9f42ac4543626ea29fc34e341b17310cfb5286a2e0dd8154403dffb6f2

Description

This is the MIB module for the third generation of the Sentry product family. This includes the Sentry Remote Power Manager (RPM), Sentry Power Distribution Unit (PDU), Sentry Environmental Monitor (EM), Sentry Smart and Switched Cabinet Distribution Unit (CDU), and Sentry Switched -48 VDC.

Contact

Server Technology, Inc. 1040 Sandhill Road Reno, NV 89521 Tel: (775) 284-2000 Fax: (775) 284-2065 Email: mibmaster@servertech.com

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC
Sentry3-MIB

Objects

NameOIDSyntaxAccessStatus
serverTech
OBJECT-IDENTITY
1.3.6.1.4.1.1718
systemGroup
OBJECT-IDENTITY
1.3.6.1.4.1.1718.3.1
systemVersion
OBJECT-TYPE
The firmware version of the system.
1.3.6.1.4.1.1718.3.1.1DisplayString (SIZE(0..80))read-onlycurrent
systemNICSerialNumber
OBJECT-TYPE
The serial number of the network interface card in the system.
1.3.6.1.4.1.1718.3.1.2DisplayString (SIZE(0..8))read-onlycurrent
systemLocation
OBJECT-TYPE
The location of the system.
1.3.6.1.4.1.1718.3.1.3DisplayString (SIZE(0..32))read-writecurrent
systemTowerCount
OBJECT-TYPE
The number of towers in the system.
1.3.6.1.4.1.1718.3.1.4INTEGER (0..4)read-onlycurrent
systemEnvMonCount
OBJECT-TYPE
The number of environmental monitors in the system.
1.3.6.1.4.1.1718.3.1.5INTEGER (0..4)read-onlycurrent
systemTotalPower
OBJECT-TYPE
The total power consumption of all of the input feeds in the system. A non-negative value indicates the total power consumption in Watts. A negative value indicates that the total power consumption was not available.
1.3.6.1.4.1.1718.3.1.6INTEGER (-1..150000)read-onlycurrent
systemArea
OBJECT-TYPE
The area that the footprint of the system occupies. A non-zero non-negative value indicates the area in tenths of area units as selected by the systemAreaUnit object. A zero or negative value indicates that the area was not available.
1.3.6.1.4.1.1718.3.1.7INTEGER (0..1000)read-writecurrent
systemWattsPerAreaUnit
OBJECT-TYPE
The system Watts per area unit. A non-negative value indicates the power consumption per area unit as selected by the systemAreaUnit object. A negative value indicates that the power consumption per area unit was not available.
1.3.6.1.4.1.1718.3.1.8INTEGER (-1..1500000)read-onlycurrent
systemAreaUnit
OBJECT-TYPE
The unit of area for the systemArea and systemWattsPerAreaUnit objects. If the agent does not support this object, then the unit of area is a square foot.
1.3.6.1.4.1.1718.3.1.9INTEGER {squareMeter(0), squareFoot(1)}read-writecurrent
systemPowerFactor
OBJECT-TYPE
The power factor used in power calculations performed by the system.
1.3.6.1.4.1.1718.3.1.10INTEGER (50..100)read-writecurrent
systemFeatures
OBJECT-TYPE
The key-activated features enabled in the system.
1.3.6.1.4.1.1718.3.1.11Bits {smartLoadShedding(0), snmpPOPS(1), outletControlInhibit(2)}read-onlycurrent
systemFeatureKey
OBJECT-TYPE
A valid feature key written to this object will enable a feature in the system. A valid feature key is in the form xxxx-xxxx-xxxx-xxxx. A read of this object returns an empty string.
1.3.6.1.4.1.1718.3.1.12DisplayString (SIZE(0..19))read-writecurrent
systemOutletSeqInterval
OBJECT-TYPE
The power-on sequencing interval for all outlets.
1.3.6.1.4.1.1718.3.1.13INTEGER (0..15)read-writecurrent
systemOutletRebootDelay
OBJECT-TYPE
The reboot delay for all outlets.
1.3.6.1.4.1.1718.3.1.14INTEGER (5..600)read-writecurrent
systemConfigModifiedCount
OBJECT-TYPE
The total number of times the system configuration has changed.
1.3.6.1.4.1.1718.3.1.15INTEGER (0..2147483647)read-onlycurrent
systemTables
OBJECT-IDENTITY
1.3.6.1.4.1.1718.3.2
towerTable
OBJECT-TYPE
A table of towers.
1.3.6.1.4.1.1718.3.2.1not-accessiblecurrent
towerEntry
OBJECT-TYPE
Row definition for the tower table.
1.3.6.1.4.1.1718.3.2.1.1not-accessiblecurrent
towerIndex
OBJECT-TYPE
Index for the tower table.
1.3.6.1.4.1.1718.3.2.1.1.1INTEGER (0..4)not-accessiblecurrent
towerID
OBJECT-TYPE
The ID of the tower.
1.3.6.1.4.1.1718.3.2.1.1.2DisplayString (SIZE(1))read-onlycurrent
towerName
OBJECT-TYPE
The name of the tower.
1.3.6.1.4.1.1718.3.2.1.1.3DisplayString (SIZE(0..24))read-writecurrent
towerStatus
OBJECT-TYPE
The operational status of the tower.
1.3.6.1.4.1.1718.3.2.1.1.4INTEGER {normal(0), noComm(1), fanFail(2), overTemp(3), nvmFail(4), outOfBalance(5)}read-onlycurrent
towerInfeedCount
OBJECT-TYPE
The number of input feeds on the tower.
1.3.6.1.4.1.1718.3.2.1.1.5INTEGER (0..4)read-onlycurrent
towerProductSN
OBJECT-TYPE
The product serial number of the tower.
1.3.6.1.4.1.1718.3.2.1.1.6DisplayString (SIZE(0..16))read-onlycurrent
towerModelNumber
OBJECT-TYPE
The model number of the tower.
1.3.6.1.4.1.1718.3.2.1.1.7DisplayString (SIZE(0..24))read-onlycurrent
towerCapabilities
OBJECT-TYPE
The capabilities of the tower.
1.3.6.1.4.1.1718.3.2.1.1.8Bits {failSafe(0), fuseSense(1), directCurrent(2), threePhase(3), fanSense(4), tempSense(5)}read-onlycurrent
towerVACapacity
OBJECT-TYPE
The total apparent power capacity of the tower circuit. A non-negative value indicates the maximum total apparent power in Volt-Amps. A negative value indicates that the total apparent power capacity was not available.
1.3.6.1.4.1.1718.3.2.1.1.9INTEGER (-1..50000)read-onlycurrent
towerVACapacityUsed
OBJECT-TYPE
The used percentage of the tower circuit total apparent power capacity (towerApparentPower / towerVACapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentage of capacity used was not available.
1.3.6.1.4.1.1718.3.2.1.1.10INTEGER (-1..1500)read-onlycurrent
towerActivePower
OBJECT-TYPE
The total active power consumption of the tower circuit. A non-negative value indicates the total active power consumption in Watts. A negative value indicates that the total active power consumption was not available.
1.3.6.1.4.1.1718.3.2.1.1.11INTEGER (-1..50000)read-onlycurrent
towerApparentPower
OBJECT-TYPE
The total apparent power consumption of the tower circuit. A non-negative value indicates the total apparent power consumption in Volt-Amps. A negative value indicates that the total apparent power consumption was not available.
1.3.6.1.4.1.1718.3.2.1.1.12INTEGER (-1..50000)read-onlycurrent
towerPowerFactor
OBJECT-TYPE
The overall power factor of the tower circuit. A non- negative value indicates the overall power factor in hundredths. A negative value indicates that the overall power factor was not able to be measured.
1.3.6.1.4.1.1718.3.2.1.1.13INTEGER (-1..100)read-onlycurrent
towerEnergy
OBJECT-TYPE
The total energy consumption of the tower circuit. A non- negative value indicates the total energy consumption in Kilowatt-Hours. A negative value indicates that the total energy consumption was not available.
1.3.6.1.4.1.1718.3.2.1.1.14INTEGER (-1..2147483647)read-onlycurrent
towerLineFrequency
OBJECT-TYPE
The frequency of the input feed line voltage. A non- negative value indicates the frequency in Hertz. A negative value indicates that the frequency was not available.
1.3.6.1.4.1.1718.3.2.1.1.15INTEGER (-1..60)read-onlycurrent
infeedTable
OBJECT-TYPE
A table of input feeds.
1.3.6.1.4.1.1718.3.2.2not-accessiblecurrent
infeedEntry
OBJECT-TYPE
Row definition for the input feed table.
1.3.6.1.4.1.1718.3.2.2.1not-accessiblecurrent
infeedIndex
OBJECT-TYPE
Index for the input feed table.
1.3.6.1.4.1.1718.3.2.2.1.1INTEGER (0..4)not-accessiblecurrent
infeedID
OBJECT-TYPE
The ID of the input feed.
1.3.6.1.4.1.1718.3.2.2.1.2DisplayString (SIZE(2))read-onlycurrent
infeedName
OBJECT-TYPE
The name of the input feed.
1.3.6.1.4.1.1718.3.2.2.1.3DisplayString (SIZE(0..24))read-writecurrent
infeedCapabilities
OBJECT-TYPE
The capabilities of the input feed.
1.3.6.1.4.1.1718.3.2.2.1.4Bits {onSense(0), loadSense(1), powerControl(2), failSafe(3), defaultOff(4), voltageSense(5), powerSense(6), branchOnSense(7), branchLoadSense(8)}read-onlycurrent
infeedStatus
OBJECT-TYPE
The status of the input feed line. If the infeedCapabilities 'onSense' bit is TRUE, then all of the states are supported and indicate the sensed state of the input feed. If the infeedCapabilities 'onSense' bit is FALSE, then only the 'on' and 'noComm' states are supported, and 'on' indicates a derived state, not a sensed state.
1.3.6.1.4.1.1718.3.2.2.1.5INTEGER {off(0), on(1), offWait(2), onWait(3), offError(4), onError(5), noComm(6), reading(7), offFuse(8), onFuse(9)}read-onlycurrent
infeedLoadStatus
OBJECT-TYPE
The status of the load measured on the input feed line. If the infeedCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the infeedCapabilities 'loadSense' bit is FALSE, then only the 'normal' and 'noComm' states are supported.
1.3.6.1.4.1.1718.3.2.2.1.6INTEGER {normal(0), notOn(1), reading(2), loadLow(3), loadHigh(4), overLoad(5), readError(6), noComm(7)}read-onlycurrent
infeedLoadValue
OBJECT-TYPE
The load measured on the input feed line. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.
1.3.6.1.4.1.1718.3.2.2.1.7INTEGER (-1..60000)read-onlycurrent
infeedLoadHighThresh
OBJECT-TYPE
The load high threshold value of the input feed line in Amps.
1.3.6.1.4.1.1718.3.2.2.1.8INTEGER (0..600)read-writecurrent
infeedOutletCount
OBJECT-TYPE
The number of controlled and/or monitored outlets on the input feed.
1.3.6.1.4.1.1718.3.2.2.1.9INTEGER (0..64)read-onlycurrent
infeedCapacity
OBJECT-TYPE
The load capacity of the input feed line. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available.
1.3.6.1.4.1.1718.3.2.2.1.10INTEGER (-1..600)read-onlycurrent
infeedVoltage
OBJECT-TYPE
The line-to-line voltage of the input feed. A non-negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available.
1.3.6.1.4.1.1718.3.2.2.1.11INTEGER (-1..4800)read-onlycurrent
infeedPower
OBJECT-TYPE
The active power consumption of the input feed phase. A non- negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available.
1.3.6.1.4.1.1718.3.2.2.1.12INTEGER (-1..25000)read-onlycurrent
infeedApparentPower
OBJECT-TYPE
The apparent power consumption of the input feed phase. A non-negative value indicates the apparent power consumption in Volt-Amps. A negative value indicates that the apparent power consumption was not available.
1.3.6.1.4.1.1718.3.2.2.1.13INTEGER (-1..25000)read-onlycurrent
infeedPowerFactor
OBJECT-TYPE
The power factor of the input feed phase. A non-negative value indicates the power factor in hundredths. A negative value indicates that the power factor was not able to be measured.
1.3.6.1.4.1.1718.3.2.2.1.14INTEGER (-1..100)read-onlycurrent
infeedCrestFactor
OBJECT-TYPE
The crest factor for the load of the input feed phase. A non-negative value indicates the crest factor in tenths. A negative value indicates that the crest factor was not able to be measured.
1.3.6.1.4.1.1718.3.2.2.1.15INTEGER (-1..1000)read-onlycurrent
infeedEnergy
OBJECT-TYPE
The energy consumption of the input feed phase. A non- negative value indicates the energy consumption in tenths of Kilowatt-Hours. A negative value indicates that the energy consumption was not available.
1.3.6.1.4.1.1718.3.2.2.1.16INTEGER (-1..2147483647)read-onlycurrent
infeedReactance
OBJECT-TYPE
The characterization of the phase relation between the voltage and current of the input feed phase.
1.3.6.1.4.1.1718.3.2.2.1.17INTEGER {unknown(0), capacitive(1), inductive(2), resistive(3)}read-onlycurrent
infeedPhaseVoltage
OBJECT-TYPE
The voltage measured for the input feed phase. A non- negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available.
1.3.6.1.4.1.1718.3.2.2.1.18INTEGER (-1..2640)read-onlycurrent
infeedPhaseCurrent
OBJECT-TYPE
The current measured for the input feed phase. A non- negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.
1.3.6.1.4.1.1718.3.2.2.1.19INTEGER (-1..25500)read-onlycurrent
infeedCapacityUsed
OBJECT-TYPE
The used percentage of the input feed line load capacity (infeedLoadValue / infeedCapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentage of capacity used was not available.
1.3.6.1.4.1.1718.3.2.2.1.20INTEGER (-1..1500)read-onlycurrent
infeedLineID
OBJECT-TYPE
The ID of the input feed line.
1.3.6.1.4.1.1718.3.2.2.1.21DisplayString (SIZE(0..4))read-onlycurrent
infeedLineToLineID
OBJECT-TYPE
The line-to-line ID of the input feed.
1.3.6.1.4.1.1718.3.2.2.1.22DisplayString (SIZE(0..7))read-onlycurrent
infeedPhaseID
OBJECT-TYPE
The ID of the input feed phase.
1.3.6.1.4.1.1718.3.2.2.1.23DisplayString (SIZE(0..6))read-onlycurrent
infeedVACapacity
OBJECT-TYPE
The apparent power capacity of the input feed circuit. A non-negative value indicates the maximum apparent power in Volt-Amps. A negative value indicates that the apparent power capacity was not available.
1.3.6.1.4.1.1718.3.2.2.1.24INTEGER (-1..25000)read-onlycurrent
infeedVACapacityUsed
OBJECT-TYPE
The used percentage of the input feed circuit apparent power capacity (infeedApparentPower / infeedVACapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentage of capacity used was not available.
1.3.6.1.4.1.1718.3.2.2.1.25INTEGER (-1..1500)read-onlycurrent
outletTable
OBJECT-TYPE
A table of outlets.
1.3.6.1.4.1.1718.3.2.3not-accessiblecurrent
outletEntry
OBJECT-TYPE
Row definition for the outlet table.
1.3.6.1.4.1.1718.3.2.3.1not-accessiblecurrent
outletIndex
OBJECT-TYPE
Index for the outlet table.
1.3.6.1.4.1.1718.3.2.3.1.1INTEGER (0..64)not-accessiblecurrent
outletID
OBJECT-TYPE
The ID of the outlet.
1.3.6.1.4.1.1718.3.2.3.1.2DisplayString (SIZE(2..4))read-onlycurrent
outletName
OBJECT-TYPE
The name of the outlet.
1.3.6.1.4.1.1718.3.2.3.1.3DisplayString (SIZE(0..24))read-writecurrent
outletCapabilities
OBJECT-TYPE
The capabilities of the outlet.
1.3.6.1.4.1.1718.3.2.3.1.4Bits {onSense(0), loadSense(1), powerControl(2), shutdown(3), defaultOn(4), ownInfeed(5), fusedBranch(6), voltageSense(7), powerSense(8)}read-onlycurrent
outletStatus
OBJECT-TYPE
The status of the outlet. If the outletCapabilities 'onSense' bit is TRUE, then the state indicates the sensed state of the outlet, not a derived state, and 'offError' and 'onError' are supported to indicate a mismatch between the control and sensed state. If the outletCapabilities 'fusedBranch' bit is TRUE, then the outlet is on a fused branch circuit that can detect the fuse state, and 'offFuse' and 'onFuse' are supported to indicate a fuse error.
1.3.6.1.4.1.1718.3.2.3.1.5INTEGER {off(0), on(1), offWait(2), onWait(3), offError(4), onError(5), noComm(6), reading(7), offFuse(8), onFuse(9)}read-onlycurrent
outletLoadStatus
OBJECT-TYPE
The status of the load measured on the outlet. If the outletCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the outletCapabilities 'loadSense' bit is FALSE, then only the 'normal' and 'noComm' states are supported.
1.3.6.1.4.1.1718.3.2.3.1.6INTEGER {normal(0), notOn(1), reading(2), loadLow(3), loadHigh(4), overLoad(5), readError(6), noComm(7)}read-onlycurrent
outletLoadValue
OBJECT-TYPE
The load measured on the outlet. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.
1.3.6.1.4.1.1718.3.2.3.1.7INTEGER (-1..25500)read-onlycurrent
outletLoadLowThresh
OBJECT-TYPE
The load low threshold value of the outlet in Amps.
1.3.6.1.4.1.1718.3.2.3.1.8INTEGER (0..255)read-writecurrent
outletLoadHighThresh
OBJECT-TYPE
The load high threshold value of the outlet in Amps.
1.3.6.1.4.1.1718.3.2.3.1.9INTEGER (0..255)read-writecurrent
outletControlState
OBJECT-TYPE
The control state of the outlet. The supported states are dependent upon the outletCapabilities 'powerControl' and 'shutdown' bits, as well as the supported features of the firmware version.
1.3.6.1.4.1.1718.3.2.3.1.10INTEGER {idleOff(0), idleOn(1), wakeOff(2), wakeOn(3), off(4), on(5), lockedOff(6), lockedOn(7), reboot(8), shutdown(9), pendOn(10), pendOff(11), minimumOff(12), minimumOn(13), eventOff(14), eventOn(15), eventReboot(16), eventShutdown(17)}read-onlycurrent
outletControlAction
OBJECT-TYPE
An action to change the control state of the outlet. If the outletCapabilities 'powerControl' bit is TRUE, then the 'on', 'off', and 'reboot' actions can be used to change the control state of the outlet. If the outletCapabilities 'powerControl' bit is FALSE, then the actions have no effect.
1.3.6.1.4.1.1718.3.2.3.1.11INTEGER {none(0), on(1), off(2), reboot(3)}read-writecurrent
outletCapacity
OBJECT-TYPE
The load capacity of the outlet. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available.
1.3.6.1.4.1.1718.3.2.3.1.12INTEGER (-1..255)read-onlycurrent
outletVoltage
OBJECT-TYPE
The voltage of the outlet. A non-negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available.
1.3.6.1.4.1.1718.3.2.3.1.13INTEGER (-1..2640)read-onlycurrent
outletPower
OBJECT-TYPE
The active power consumption of the device plugged into the outlet. A non-negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available.
1.3.6.1.4.1.1718.3.2.3.1.14INTEGER (-1..10000)read-onlycurrent
outletApparentPower
OBJECT-TYPE
The apparent power consumption of the device plugged into the outlet. A non-negative value indicates the apparent power consumption in Volt-Amps. A negative value indicates that the apparent power consumption was not available.
1.3.6.1.4.1.1718.3.2.3.1.15INTEGER (-1..10000)read-onlycurrent
outletPowerFactor
OBJECT-TYPE
The power factor of the device plugged into the outlet. A non-negative value indicates the power factor in hundredths. A negative value indicates that the power factor was not able to be measured.
1.3.6.1.4.1.1718.3.2.3.1.16INTEGER (-1..100)read-onlycurrent
outletCrestFactor
OBJECT-TYPE
The crest factor for the load of the device plugged into the outlet. A non-negative value indicates the crest factor in tenths. A negative value indicates that the crest factor was not able to be measured.
1.3.6.1.4.1.1718.3.2.3.1.17INTEGER (-1..1000)read-onlycurrent
outletEnergy
OBJECT-TYPE
The energy consumption of the device plugged into the outlet. A non-negative value indicates the energy consumption in Watt-Hours. A negative value indicates that the energy consumption was not available.
1.3.6.1.4.1.1718.3.2.3.1.18INTEGER (-1..2147483647)read-onlycurrent
outletWakeupState
OBJECT-TYPE
The wakeup state of the outlet.
1.3.6.1.4.1.1718.3.2.3.1.19INTEGER {last(1), off(2), on(3)}read-writecurrent
outletPostOnDelay
OBJECT-TYPE
The post-on delay of the outlet.
1.3.6.1.4.1.1718.3.2.3.1.20INTEGER (0..900)read-writecurrent
envMonTable
OBJECT-TYPE
A table of environmental monitors.
1.3.6.1.4.1.1718.3.2.4not-accessiblecurrent
envMonEntry
OBJECT-TYPE
Row definition for the environmental monitor table.
1.3.6.1.4.1.1718.3.2.4.1not-accessiblecurrent
envMonIndex
OBJECT-TYPE
Index for the environmental monitor table.
1.3.6.1.4.1.1718.3.2.4.1.1INTEGER (0..4)not-accessiblecurrent
envMonID
OBJECT-TYPE
The ID of the environmental monitor.
1.3.6.1.4.1.1718.3.2.4.1.2DisplayString (SIZE(1))read-onlycurrent
envMonName
OBJECT-TYPE
The name of the environmental monitor.
1.3.6.1.4.1.1718.3.2.4.1.3DisplayString (SIZE(0..24))read-writecurrent
envMonStatus
OBJECT-TYPE
The operational status of the environmental monitor.
1.3.6.1.4.1.1718.3.2.4.1.4INTEGER {normal(0), noComm(1)}read-onlycurrent
envMonWaterSensorName
OBJECT-TYPE
The name of the water sensor.
1.3.6.1.4.1.1718.3.2.4.1.5DisplayString (SIZE(0..24))read-writecurrent
envMonWaterSensorStatus
OBJECT-TYPE
The status of the water sensor.
1.3.6.1.4.1.1718.3.2.4.1.6INTEGER {normal(0), alarm(1), noComm(2)}read-onlycurrent
envMonADCName
OBJECT-TYPE
The name of the analog-to-digital converter.
1.3.6.1.4.1.1718.3.2.4.1.7DisplayString (SIZE(0..24))read-writecurrent
envMonADCStatus
OBJECT-TYPE
The status of the analog-to-digital converter.
1.3.6.1.4.1.1718.3.2.4.1.8INTEGER {normal(0), reading(1), countLow(2), countHigh(3), readError(4), noComm(5)}read-onlycurrent
envMonADCCount
OBJECT-TYPE
The 8-bit count value from the analog-to-digital converter. A non-negative value indicates the digital value retrieved from the ADC. A negative value indicates that a digital value was not able to be retrieved.
1.3.6.1.4.1.1718.3.2.4.1.9INTEGER (-1..255)read-onlycurrent
envMonADCLowThresh
OBJECT-TYPE
The 8-bit count low threshold value of the analog-to-digital converter.
1.3.6.1.4.1.1718.3.2.4.1.10INTEGER (0..255)read-writecurrent
envMonADCHighThresh
OBJECT-TYPE
The 8-bit count high threshold value of the analog-to-digital converter.
1.3.6.1.4.1.1718.3.2.4.1.11INTEGER (0..255)read-writecurrent
envMonTempHumidSensorCount
OBJECT-TYPE
The number of temperature/humidity sensors on the environmental monitor.
1.3.6.1.4.1.1718.3.2.4.1.12INTEGER (0..2)read-onlycurrent
envMonContactClosureCount
OBJECT-TYPE
The number of contact closures on the environmental monitor.
1.3.6.1.4.1.1718.3.2.4.1.13INTEGER (0..4)read-onlycurrent
tempHumidSensorTable
OBJECT-TYPE
A table of temperature/humidity sensors.
1.3.6.1.4.1.1718.3.2.5not-accessiblecurrent
tempHumidSensorEntry
OBJECT-TYPE
Row definition for the temperature/humidity sensor table.
1.3.6.1.4.1.1718.3.2.5.1not-accessiblecurrent
tempHumidSensorIndex
OBJECT-TYPE
Index for the temperature/humidity sensor table.
1.3.6.1.4.1.1718.3.2.5.1.1INTEGER (0..2)not-accessiblecurrent
tempHumidSensorID
OBJECT-TYPE
The ID of the temperature/humidity sensor.
1.3.6.1.4.1.1718.3.2.5.1.2DisplayString (SIZE(2))read-onlycurrent
tempHumidSensorName
OBJECT-TYPE
The name of the temperature/humidity sensor.
1.3.6.1.4.1.1718.3.2.5.1.3DisplayString (SIZE(0..24))read-writecurrent
tempHumidSensorStatus
OBJECT-TYPE
The operational status of the temperature/humidity sensor.
1.3.6.1.4.1.1718.3.2.5.1.4INTEGER {found(0), notFound(1), lost(2), noComm(3)}read-onlycurrent
tempHumidSensorTempStatus
OBJECT-TYPE
The status of the temperature sensor.
1.3.6.1.4.1.1718.3.2.5.1.5INTEGER {normal(0), notFound(1), reading(2), tempLow(3), tempHigh(4), readError(5), lost(6), noComm(7)}read-onlycurrent
tempHumidSensorTempValue
OBJECT-TYPE
The temperature measured by the sensor. A non-negative value indicates the measured temperature in tenths of degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is Celsius. A negative value indicates that a temperature value was not able to be measured.
1.3.6.1.4.1.1718.3.2.5.1.6INTEGER (-1..2540)read-onlycurrent
tempHumidSensorTempLowThresh
OBJECT-TYPE
The temperature low threshold value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is Celsius.
1.3.6.1.4.1.1718.3.2.5.1.7INTEGER (0..254)read-writecurrent
tempHumidSensorTempHighThresh
OBJECT-TYPE
The temperature high threshold value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is Celsius.
1.3.6.1.4.1.1718.3.2.5.1.8INTEGER (0..254)read-writecurrent
tempHumidSensorHumidStatus
OBJECT-TYPE
The status of the humidity sensor.
1.3.6.1.4.1.1718.3.2.5.1.9INTEGER {normal(0), notFound(1), reading(2), humidLow(3), humidHigh(4), readError(5), lost(6), noComm(7)}read-onlycurrent
tempHumidSensorHumidValue
OBJECT-TYPE
The humidity measured by the sensor. A non-negative value indicates the measured humidity in percentage relative humidity. A negative value indicates that a humidity value was not able to be measured.
1.3.6.1.4.1.1718.3.2.5.1.10INTEGER (-1..100)read-onlycurrent
tempHumidSensorHumidLowThresh
OBJECT-TYPE
The humidity low threshold value of the sensor in percentage relative humidity.
1.3.6.1.4.1.1718.3.2.5.1.11INTEGER (0..100)read-writecurrent
tempHumidSensorHumidHighThresh
OBJECT-TYPE
The humidity low threshold value of the sensor in percentage relative humidity.
1.3.6.1.4.1.1718.3.2.5.1.12INTEGER (0..100)read-writecurrent
tempHumidSensorTempScale
OBJECT-TYPE
The scale used for temperature values. This is a global setting for all temperature values in the system. If the agent does not support this object, then the temperature scale used is Celsius.
1.3.6.1.4.1.1718.3.2.5.1.13INTEGER {celsius(0), fahrenheit(1)}read-writecurrent
tempHumidSensorTempRecDelta
OBJECT-TYPE
The temperature recovery delta (hysteresis) value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale.
1.3.6.1.4.1.1718.3.2.5.1.14INTEGER (0..54)read-writecurrent
tempHumidSensorHumidRecDelta
OBJECT-TYPE
The humidity recovery delta (hysteresis) value of the sensor in percentage relative humidity.
1.3.6.1.4.1.1718.3.2.5.1.15INTEGER (0..20)read-writecurrent
contactClosureTable
OBJECT-TYPE
A table of contact closures.
1.3.6.1.4.1.1718.3.2.6not-accessiblecurrent
contactClosureEntry
OBJECT-TYPE
Row definition for the contact closure table.
1.3.6.1.4.1.1718.3.2.6.1not-accessiblecurrent
contactClosureIndex
OBJECT-TYPE
Index for the contact closure table.
1.3.6.1.4.1.1718.3.2.6.1.1INTEGER (0..4)not-accessiblecurrent
contactClosureID
OBJECT-TYPE
The ID of the contact closure.
1.3.6.1.4.1.1718.3.2.6.1.2DisplayString (SIZE(2))read-onlycurrent
contactClosureName
OBJECT-TYPE
The name of the contact closure.
1.3.6.1.4.1.1718.3.2.6.1.3DisplayString (SIZE(0..24))read-writecurrent
contactClosureStatus
OBJECT-TYPE
The status of the contact closure.
1.3.6.1.4.1.1718.3.2.6.1.4INTEGER {normal(0), alarm(1), noComm(2)}read-onlycurrent
branchTable
OBJECT-TYPE
A table of branches.
1.3.6.1.4.1.1718.3.2.7not-accessiblecurrent
branchEntry
OBJECT-TYPE
Row definition for the branch table.
1.3.6.1.4.1.1718.3.2.7.1not-accessiblecurrent
branchIndex
OBJECT-TYPE
Index for the branch table.
1.3.6.1.4.1.1718.3.2.7.1.1INTEGER (0..4)not-accessiblecurrent
branchID
OBJECT-TYPE
The ID of the branch.
1.3.6.1.4.1.1718.3.2.7.1.2DisplayString (SIZE(3))read-onlycurrent
branchName
OBJECT-TYPE
The name of the branch.
1.3.6.1.4.1.1718.3.2.7.1.3DisplayString (SIZE(0..24))read-writecurrent
branchCapabilities
OBJECT-TYPE
The capabilities of the branch.
1.3.6.1.4.1.1718.3.2.7.1.4Bits {onSense(0), loadSense(1)}read-onlycurrent
branchStatus
OBJECT-TYPE
The status of the branch.
1.3.6.1.4.1.1718.3.2.7.1.5INTEGER {off(0), on(1), offWait(2), onWait(3), offError(4), onError(5), noComm(6), reading(7), offFuse(8), onFuse(9)}read-onlycurrent
branchLoadStatus
OBJECT-TYPE
The status of the load measured on the branch.
1.3.6.1.4.1.1718.3.2.7.1.6INTEGER {normal(0), notOn(1), reading(2), loadLow(3), loadHigh(4), overLoad(5), readError(6), noComm(7)}read-onlycurrent
branchLoadValue
OBJECT-TYPE
The load measured on the branch. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.
1.3.6.1.4.1.1718.3.2.7.1.7INTEGER (-1..4000)read-onlycurrent
branchLoadHighThresh
OBJECT-TYPE
The load high threshold value of the branch in Amps.
1.3.6.1.4.1.1718.3.2.7.1.8INTEGER (0..40)read-writecurrent
branchCapacity
OBJECT-TYPE
The load capacity of the branch. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available.
1.3.6.1.4.1.1718.3.2.7.1.9INTEGER (-1..40)read-onlycurrent
eventInformationGroup
OBJECT-IDENTITY
1.3.6.1.4.1.1718.3.99
eventStatusText
OBJECT-TYPE
The text representation of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A get of this object will return a NULL string.
1.3.6.1.4.1.1718.3.99.1DisplayString (SIZE(0..20))read-onlycurrent
eventStatusCondition
OBJECT-TYPE
The condition of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A get of this object will return zero.
1.3.6.1.4.1.1718.3.99.2INTEGER {nonError(0), error(1)}read-onlycurrent
sentry3Traps
OBJECT-IDENTITY
1.3.6.1.4.1.1718.3.100
events
OBJECT-IDENTITY
1.3.6.1.4.1.1718.3.100.0

Notifications

NameOIDStatus
towerStatusEvent
NOTIFICATION-TYPE
Tower status event. If enabled, this trap is sent when the towerStatus indicates an error state ('noComm', 'fanFail', 'overTemp', 'nvmFail', or 'outOfBalance'). This trap is repeated periodically while the towerStatus remains in an error state. If the towerStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error towerStatus, and then stops being repeated. While the towerStatus indicates a 'noComm' error state, all status and load traps are suppressed for input feeds and outlets on the tower.
1.3.6.1.4.1.1718.3.100.0.1current
infeedStatusEvent
NOTIFICATION-TYPE
Input feed status event. If enabled, this trap is sent when the infeedStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is repeated periodically while the infeedStatus remains in an error state. If the infeedStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error infeedStatus, and then stops being repeated. While the infeedStatus indicates an error state, load traps are suppressed for the input feed, and, if the infeedCapabilities 'failSafe' bit is FALSE, all status and load traps are suppressed for outlets on the input feed.
1.3.6.1.4.1.1718.3.100.0.2current
infeedLoadEvent
NOTIFICATION-TYPE
Input feed load event. If enabled, this trap is sent when the infeedLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the infeedLoadStatus remains in an error state. If the infeedLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error infeedLoadStatus, and then stops being repeated.
1.3.6.1.4.1.1718.3.100.0.3current
outletStatusEvent
NOTIFICATION-TYPE
Outlet status event. If enabled, this trap is sent when the outletStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is repeated periodically while the outletStatus remains in an error state. If the outletStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error outletStatus, and then stops being repeated. While the outletStatus indicates an error state, load traps are suppressed for the outlet.
1.3.6.1.4.1.1718.3.100.0.4current
outletLoadEvent
NOTIFICATION-TYPE
Outlet load event. If enabled, this trap is sent when the outletLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the outletLoadStatus remains in an error state. If the outletLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error outletLoadStatus, and then stops being repeated.
1.3.6.1.4.1.1718.3.100.0.5current
outletChangeEvent
NOTIFICATION-TYPE
Outlet on/off change event. If enabled, this trap is sent when the outletStatus changes from any 'on' state ('on', 'onWait', 'onError', or 'onFuse') to any 'off' state ('off', 'offWait', 'offError', or 'offFuse'), and vice-versa.
1.3.6.1.4.1.1718.3.100.0.6current
envMonStatusEvent
NOTIFICATION-TYPE
Environmental monitor status event. If enabled, this trap is sent when the envMonStatus indicates an error state ('noComm'). This trap is repeated periodically while the envMonStatus remains in an error state. If the envMonStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonStatus, and then stops being repeated. While the envMonStatus indicates an error state, all status traps are suppressed for the water sensor, ADC, temperature/ humidity sensors, and contact closures on the environmental monitor.
1.3.6.1.4.1.1718.3.100.0.7current
envMonWaterSensorEvent
NOTIFICATION-TYPE
Environmental monitor water sensor event. If enabled, this trap is sent when the envMonWaterSensorStatus indicates an error state ('alarm'). This trap is repeated periodically while the envMonWaterSensorStatus remains in an error state. If the envMonWaterSensorStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonWaterSensorStatus, and then stops being repeated.
1.3.6.1.4.1.1718.3.100.0.8current
envMonADCEvent
NOTIFICATION-TYPE
Environmental monitor analog-to-digital converter event. If enabled, this trap is sent when the envMonADCStatus indicates an error state ('countLow' or 'countHigh'). This trap is repeated periodically while the envMonADCStatus remains in an error state. If the envMonADCStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonADCStatus, and then stops being repeated.
1.3.6.1.4.1.1718.3.100.0.9current
tempHumidSensorStatusEvent
NOTIFICATION-TYPE
Temperature/humidity sensor status event. If enabled, this trap is sent when the tempHumidSensorStatus indicates an error state ('lost'). This trap is repeated periodically while the tempHumidSensorStatus remains in an error state. If the tempHumidSensorStatus returns to a non-error state ('found'), this trap is sent once more with the non-error tempHumidSensorStatus, and then stops being repeated. While the tempHumidSensorStatus indicates an error state, all temperature and humidity status traps are suppressed for the temperature/humidity sensor.
1.3.6.1.4.1.1718.3.100.0.10current
tempHumidSensorTempEvent
NOTIFICATION-TYPE
Temperature/humidity sensor temperature event. If enabled, this trap is sent when the tempHumidSensorTempStatus indicates an error state ('tempLow' or 'tempHigh'). This trap is repeated periodically while the tempHumidSensorTempStatus remains in an error state. If the tempHumidSensorTempStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error tempHumidSensorTempStatus, and then stops being repeated.
1.3.6.1.4.1.1718.3.100.0.11current
tempHumidSensorHumidEvent
NOTIFICATION-TYPE
Temperature/humidity sensor humidity event. If enabled, this trap is sent when the tempHumidSensorHumidStatus indicates an error state ('humidLow' or 'humidHigh'). This trap is repeated periodically while the tempHumidSensorHumidStatus remains in an error state. If the tempHumidSensorHumidStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error tempHumidSensorHumidStatus, and then stops being repeated.
1.3.6.1.4.1.1718.3.100.0.12current
contactClosureEvent
NOTIFICATION-TYPE
Contact closure event. If enabled, this trap is sent when the contactClosureStatus indicates an error state ('alarm'). This trap is repeated periodically while the contactClosureStatus remains in an error state. If the contactClosureStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error contactClosureStatus, and then stops being repeated.
1.3.6.1.4.1.1718.3.100.0.13current
branchStatusEvent
NOTIFICATION-TYPE
Branch status event. If enabled, this trap is sent when the branchStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is repeated periodically while the branchStatus remains in an error state. If the branchStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error branchStatus, and then stops being repeated. While the branchStatus indicates an error state, load traps are suppressed for the branch.
1.3.6.1.4.1.1718.3.100.0.14current
branchLoadEvent
NOTIFICATION-TYPE
Branch load event. If enabled, this trap is sent when the branchLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the branchLoadStatus remains in an error state. If the branchLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error branchLoadStatus, and then stops being repeated.
1.3.6.1.4.1.1718.3.100.0.15current