MIBs Depot

PDU2-MIB

Registered at
1.3.6.1.4.1.13742
Last updated
2017-11-13 00:00
Organization
Raritan
Revisions
2017-11-13 00:00, 2016-12-02 00:00, 2016-02-16 00:00, 2016-02-09 00:00, 2015-10-26 00:00, 2015-09-30 00:00, 2015-02-18 00:00, 2014-06-04 00:00, 2014-01-09 00:00, 2014-01-07 00:00, 2013-11-21 00:00, 2013-09-18 00:00, 2013-08-01 00:00, 2013-07-10 00:00, 2013-07-02 00:00, 2013-05-21 00:00, 2013-04-26 00:00, 2013-03-27 00:00, 2013-03-25 10:00, 2013-03-25 00:00, 2013-03-18 00:00, 2013-02-25 00:00, 2013-02-04 00:00, 2013-01-24 00:00, 2012-11-20 00:00, 2012-11-15 00:00, 2012-10-05 00:00, 2012-10-04 00:00, 2012-09-28 00:00, 2012-09-21 00:00, 2012-09-20 00:00, 2012-09-17 00:00, 2012-09-04 00:00, 2012-06-22 00:00, 2012-06-18 00:00, 2012-06-06 00:00, 2012-05-25 00:00, 2012-05-15 00:00, 2012-03-26 00:00, 2011-12-13 00:00, 2011-11-29 00:00, 2011-10-25 00:00, 2011-06-16 00:00, 2011-03-22 00:00, 2011-02-21 00:00, 2011-02-14 00:00, 2011-02-08 00:00, 2011-02-03 00:00, 2011-01-31 00:00, 2010-12-15 00:00, 2010-12-13 11:31, 2010-12-13 00:00, 2010-12-07 00:00, 2010-10-07 00:00, 2010-10-04 00:00, 2010-09-01 00:00, 2010-08-05 00:00, 2010-07-23 00:00, 2010-07-22 00:00, 2010-07-21 00:00, 2010-07-14 00:00, 2010-07-06 00:00, 2010-07-01 00:00, 2010-06-30 00:00, 2010-06-21 00:00, 2010-06-03 00:00, 2010-05-27 00:00, 2010-05-24 00:00, 2010-04-19 00:00, 2010-04-15 00:00, 2010-04-08 00:00, 2010-03-29 00:00, 2010-03-25 00:00, 2010-03-16 00:00, 2010-03-01 00:00, 2010-01-29 00:00
Namespace
raritan
Source file
PDU2-MIB
Digest
sha256:72d7020bc0ac06ffff55dd2ce6ad95f2beae07963f6328df6d8a098e1abe7ab6

Description

This MIB describes the SNMP functions of the Raritan PX2, PX3 and BCM2 series power distribution units by Raritan.

Contact

Author: Raritan Americas, Inc. postal: Raritan Americas, Inc. 400 Cottontail Lane Somerset, NJ 08873 email: tech@raritan.com phone: +1 732 764 8886

Imports

FromSymbols
INET-ADDRESS-MIBInetAddress, InetAddressType, InetPortNumber
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-MIBsysContact, sysLocation, sysName
SNMPv2-SMIInteger32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, enterprises, iso
SNMPv2-TCDisplayString, MacAddress, RowPointer, TEXTUAL-CONVENTION, TruthValue

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

INET-ADDRESS-MIB
PDU2-MIB
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC

Under this module's arcs

Where the registration tree carries on below this module.

ArcNameModule
1.3.6.1.4.1.13742.3remoteKVMDeviceRemoteKVMDevice-MIB
1.3.6.1.4.1.13742.4pduPDU-MIB
1.3.6.1.4.1.13742.9raritanMibConformanceRemoteKVMDevice-MIB

Textual conventions

NameOIDSyntaxAccessStatus
AddressSourceEnumeration
TEXTUAL-CONVENTION
How was the address obtained?
current
BoardTypeEnumeration
TEXTUAL-CONVENTION
The types of boards.
current
CircuitTypeEnumeration
TEXTUAL-CONVENTION
The panel circuit types.
current
DaisychainMemberTypeEnumeration
TEXTUAL-CONVENTION
The daisy chain member type.
current
DeviceCascadeTypeEnumeration
TEXTUAL-CONVENTION
The type of configured cascading on this device.
current
DeviceIdentificationParameterEnumeration
TEXTUAL-CONVENTION
The configurable parameters.
current
ExternalSensorsZCoordinateUnitsEnumeration
TEXTUAL-CONVENTION
The units of the external sensor Z coordinate. rackUnits implies that the Z coordinate for all external sensors is in rack units (U) text implies that the Z coordinate for all external sensors is a text string (label)
current
GlobalOutletStateOnStartupEnumeration
TEXTUAL-CONVENTION
The global outlet state on device start up; can be overridden per outlet.
current
HundredthsOfAPercentage
TEXTUAL-CONVENTION
Data type for reporting values in hundredths of percentage, i.e. 0.01 %.
current
LineEnumeration
TEXTUAL-CONVENTION
The Lines: L1, L2, L3, N.
current
NetworkInterfaceTypeEnumeration
TEXTUAL-CONVENTION
The type of network interface.
current
OutletStateOnStartupEnumeration
TEXTUAL-CONVENTION
The outlet state on device start up; this overrides the global value.
current
OutletSwitchingOperationsEnumeration
TEXTUAL-CONVENTION
The switching operations on an outlet.
current
OverCurrentProtectorTypeEnumeration
TEXTUAL-CONVENTION
The types of overcurrent protectors.
current
PanelLayoutEnumeration
TEXTUAL-CONVENTION
The panel circuit position layout.
current
PanelNumberingEnumeration
TEXTUAL-CONVENTION
The panel circuit position numbering scheme.
current
PeripheralDeviceFirmwareUpdateStateEnumeration
TEXTUAL-CONVENTION
The state of a peripheral device firmware update.
current
PhaseEnumeration
TEXTUAL-CONVENTION
The power phase.
current
PlugTypeEnumeration
TEXTUAL-CONVENTION
The types of inlet plug.
current
PowerMeterTypeEnumeration
TEXTUAL-CONVENTION
The power meter types
current
ProductTypeEnumeration
TEXTUAL-CONVENTION
The product types.
current
ReceptacleTypeEnumeration
TEXTUAL-CONVENTION
The types of outlet receptacle.
current
RelayPowerLossBehaviorEnumeration
TEXTUAL-CONVENTION
The type of relay behavior on power loss.
current
SensorStateEnumeration
TEXTUAL-CONVENTION
The states a sensor can be in.
current
SensorTypeEnumeration
TEXTUAL-CONVENTION
The types a sensor can be.
current
SensorUnitsEnumeration
TEXTUAL-CONVENTION
The sensor units.
current
TransferSwitchTransferReasonEnumeration
TEXTUAL-CONVENTION
Transfer Switch Transfer Reason
current
URL
TEXTUAL-CONVENTION
A Uniform Resource Locator (URL), as defined in RFC1738.
current

Objects

NameOIDSyntaxAccessStatus
pdu2
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6
traps
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.0
trapInformation
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.0.0
trapInformationTable
OBJECT-TYPE
A group of objects used exclusively in traps. This is a table for historic reasons; it can't be queried from the SNMP agent.
1.3.6.1.4.1.13742.6.0.0.1not-accessiblecurrent
trapInformationEntry
OBJECT-TYPE
An entry containing objects used in traps.
1.3.6.1.4.1.13742.6.0.0.1.1not-accessiblecurrent
userName
OBJECT-TYPE
The user currently logged in.
1.3.6.1.4.1.13742.6.0.0.1.1.2DisplayStringread-onlycurrent
targetUser
OBJECT-TYPE
The user added, deleted, or modified.
1.3.6.1.4.1.13742.6.0.0.1.1.3DisplayStringread-onlycurrent
imageVersion
OBJECT-TYPE
The version of the upgrade image.
1.3.6.1.4.1.13742.6.0.0.1.1.5DisplayStringread-onlycurrent
roleName
OBJECT-TYPE
The role added, deleted, or modified.
1.3.6.1.4.1.13742.6.0.0.1.1.6DisplayStringread-onlycurrent
smtpMessageRecipients
OBJECT-TYPE
Comma separated list of SMTP message recipients
1.3.6.1.4.1.13742.6.0.0.1.1.7DisplayStringread-onlycurrent
smtpServer
OBJECT-TYPE
The IP address/host name of the SMTP server
1.3.6.1.4.1.13742.6.0.0.1.1.8DisplayStringread-onlycurrent
oldSensorState
OBJECT-TYPE
The old sensor state used in sensor state transition traps.
1.3.6.1.4.1.13742.6.0.0.2SensorStateEnumerationaccessible-for-notifycurrent
pduNumber
OBJECT-TYPE
A unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.13742.6.0.0.3Integer32 (1..256)accessible-for-notifycurrent
inletPoleNumber
OBJECT-TYPE
A unique value for each inlet pole. Its value ranges between 1 and the value of inletPoleCount.
1.3.6.1.4.1.13742.6.0.0.5Integer32 (1..256)accessible-for-notifycurrent
outletPoleNumber
OBJECT-TYPE
A unique value for each outlet pole. Its value ranges between 1 and the value of outletPoleCount.
1.3.6.1.4.1.13742.6.0.0.7Integer32 (1..256)accessible-for-notifycurrent
externalSensorNumber
OBJECT-TYPE
A unique value for each external sensor. Its value ranges between 1 and the value of externalSensorCount.
1.3.6.1.4.1.13742.6.0.0.8Integer32 (1..256)accessible-for-notifycurrent
typeOfSensor
OBJECT-TYPE
The type of sensor.
1.3.6.1.4.1.13742.6.0.0.10SensorTypeEnumerationaccessible-for-notifycurrent
errorDescription
OBJECT-TYPE
Description of the error
1.3.6.1.4.1.13742.6.0.0.11DisplayStringaccessible-for-notifycurrent
deviceChangedParameter
OBJECT-TYPE
Identifies the parameter that has changed.
1.3.6.1.4.1.13742.6.0.0.12DeviceIdentificationParameterEnumerationaccessible-for-notifycurrent
changedParameterNewValue
OBJECT-TYPE
The new value of the changed parameter
1.3.6.1.4.1.13742.6.0.0.13DisplayStringaccessible-for-notifycurrent
lhxSupportEnabled
OBJECT-TYPE
The new enabled state for Schroff LHX support.
1.3.6.1.4.1.13742.6.0.0.14TruthValueaccessible-for-notifycurrent
webcamModel
OBJECT-TYPE
The model of the webcam
1.3.6.1.4.1.13742.6.0.0.15DisplayStringaccessible-for-notifycurrent
webcamConnectionPort
OBJECT-TYPE
The port to which the webcam is connected
1.3.6.1.4.1.13742.6.0.0.16DisplayStringaccessible-for-notifycurrent
agentInetPortNumber
OBJECT-TYPE
The UDP port number used for accessing the SNMP agent on the device. This is necessary to identify the slave in a port forwarding cascade.
1.3.6.1.4.1.13742.6.0.0.18InetPortNumberaccessible-for-notifycurrent
peripheralDeviceRomcode
OBJECT-TYPE
The 1-wire romcode of a peripheral device
1.3.6.1.4.1.13742.6.0.0.19DisplayStringaccessible-for-notifycurrent
peripheralDeviceFirmwareUpdateState
OBJECT-TYPE
The firmware update state of a peripheral device
1.3.6.1.4.1.13742.6.0.0.20PeripheralDeviceFirmwareUpdateStateEnumerationaccessible-for-notifycurrent
circuitNumber
OBJECT-TYPE
A unique value for each circuit. Defined as follows: circuitNumber = 1000 * panelId + circuitPosition Examples: 1045 is the the circuit on panel 1 with lowest circuit position equal to 45 4067 is the the circuit on panel 4 with lowest circuit position equal to 67.
1.3.6.1.4.1.13742.6.0.0.21Integer32 (1..33000)accessible-for-notifycurrent
circuitPoleNumber
OBJECT-TYPE
A unique value for each circuit pole.
1.3.6.1.4.1.13742.6.0.0.22Integer32 (1..256)accessible-for-notifycurrent
phoneNumber
OBJECT-TYPE
The phone number of e.g. an SMS receiver.
1.3.6.1.4.1.13742.6.0.0.23DisplayStringaccessible-for-notifycurrent
smartCardReaderId
OBJECT-TYPE
The ID of a smartcard reader.
1.3.6.1.4.1.13742.6.0.0.24DisplayStringaccessible-for-notifycurrent
smartCardTimestamp
OBJECT-TYPE
The timestamp indicating when the smartcard was inserted or removed. It is measured in seconds since January 1, 1970 UTC
1.3.6.1.4.1.13742.6.0.0.25Unsigned32accessible-for-notifycurrent
smartCardType
OBJECT-TYPE
The type of a smartcard.
1.3.6.1.4.1.13742.6.0.0.26DisplayStringaccessible-for-notifycurrent
smartCardId
OBJECT-TYPE
The ID/serial number of a smartcard.
1.3.6.1.4.1.13742.6.0.0.27DisplayStringaccessible-for-notifycurrent
suspectedTripCauseLabel
OBJECT-TYPE
The label of the outlet that likely caused the OCP trip, if it can be determined.
1.3.6.1.4.1.13742.6.0.0.28DisplayStringaccessible-for-notifycurrent
board
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.1
environmental
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.2
configuration
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3
pduCount
OBJECT-TYPE
The number of PDUs managed by this MIB. For PX2, PX3 and PX3TS, pduCount is always 1 For BCM2, pduCount is the number of power meters plus 1 (for the main controller)
1.3.6.1.4.1.13742.6.3.1Integer32read-onlycurrent
unit
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.2
nameplateTable
OBJECT-TYPE
A list of PDU nameplate entries. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.3.2.1not-accessiblecurrent
nameplateEntry
OBJECT-TYPE
An entry providing PDU nameplate information.
1.3.6.1.4.1.13742.6.3.2.1.1not-accessiblecurrent
pduId
OBJECT-TYPE
A unique value for each PDU or power meter. For PX2, PX3 and PX3TS, pduId is always 1 For BCM2, pduId can be: - 0 for the main controller - The meter ID (rotary switch) for power meter
1.3.6.1.4.1.13742.6.3.2.1.1.1Integer32 (0..256)not-accessiblecurrent
pduManufacturer
OBJECT-TYPE
The PDU manufacturer.
1.3.6.1.4.1.13742.6.3.2.1.1.2DisplayStringread-onlycurrent
pduModel
OBJECT-TYPE
The PDU model name.
1.3.6.1.4.1.13742.6.3.2.1.1.3DisplayStringread-onlycurrent
pduSerialNumber
OBJECT-TYPE
The PDU serial number.
1.3.6.1.4.1.13742.6.3.2.1.1.4DisplayStringread-onlycurrent
pduRatedVoltage
OBJECT-TYPE
The PDU voltage rating.
1.3.6.1.4.1.13742.6.3.2.1.1.5DisplayStringread-onlycurrent
pduRatedCurrent
OBJECT-TYPE
The PDU current rating.
1.3.6.1.4.1.13742.6.3.2.1.1.6DisplayStringread-onlycurrent
pduRatedFrequency
OBJECT-TYPE
The PDU frequency rating.
1.3.6.1.4.1.13742.6.3.2.1.1.7DisplayStringread-onlycurrent
pduRatedVA
OBJECT-TYPE
The PDU VA (VoltAmps) rating.
1.3.6.1.4.1.13742.6.3.2.1.1.8DisplayStringread-onlycurrent
pduImage
OBJECT-TYPE
The URL of the wiring diagram for this PDU.
1.3.6.1.4.1.13742.6.3.2.1.1.9URLread-onlycurrent
unitConfigurationTable
OBJECT-TYPE
A list of PDU configuration entries. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.3.2.2not-accessiblecurrent
unitConfigurationEntry
OBJECT-TYPE
An entry containing configuration objects for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.2.1not-accessiblecurrent
inletCount
OBJECT-TYPE
The number of inlets.
1.3.6.1.4.1.13742.6.3.2.2.1.2Integer32 (1..256)read-onlycurrent
overCurrentProtectorCount
OBJECT-TYPE
The number of overcurrent protectors.
1.3.6.1.4.1.13742.6.3.2.2.1.3Integer32 (0..255)read-onlycurrent
outletCount
OBJECT-TYPE
The number of outlets.
1.3.6.1.4.1.13742.6.3.2.2.1.4Integer32 (1..256)read-onlycurrent
inletControllerCount
OBJECT-TYPE
The number of inlet controllers.
1.3.6.1.4.1.13742.6.3.2.2.1.5Integer32 (0..255)read-onlycurrent
outletControllerCount
OBJECT-TYPE
The number of outlet controllers.
1.3.6.1.4.1.13742.6.3.2.2.1.6Integer32 (0..255)read-onlycurrent
externalSensorCount
OBJECT-TYPE
The maximum supported number of external sensors. This value is fixed and does not reflect how many sensors are actually connected.
1.3.6.1.4.1.13742.6.3.2.2.1.7Integer32 (0..255)read-onlycurrent
pxIPAddress
OBJECT-TYPE
The current IP address. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.13742.6.3.2.2.1.8IpAddressread-onlydeprecated
netmask
OBJECT-TYPE
The current netmask. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.13742.6.3.2.2.1.9IpAddressread-onlydeprecated
gateway
OBJECT-TYPE
The current gateway. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.13742.6.3.2.2.1.10IpAddressread-onlydeprecated
pxMACAddress
OBJECT-TYPE
The current MAC address. If bridge interface is enabled, then equal to the MAC address of Ethernet 1 else if Ethernet 1 is enabled, then equal to the MAC address of Ethernet 1 else if Ethernet 2 is enabled, then equal to the MAC address of Ethernet 2 else if Wlan is enabled, then equal to the MAC address of Wlan else return SNMP_ERR_NOSUCHNAME
1.3.6.1.4.1.13742.6.3.2.2.1.11MacAddressread-onlydeprecated
utcOffset
OBJECT-TYPE
The current UTC offset.
1.3.6.1.4.1.13742.6.3.2.2.1.12DisplayStringread-onlycurrent
pduName
OBJECT-TYPE
The user-defined name for the PDU.
1.3.6.1.4.1.13742.6.3.2.2.1.13DisplayStringread-writecurrent
networkInterfaceType
OBJECT-TYPE
The network interface type: wired or wireless. If only the Wireless interface is enabled, then equal to wireless else equal to wired
1.3.6.1.4.1.13742.6.3.2.2.1.14NetworkInterfaceTypeEnumerationread-onlydeprecated
externalSensorsZCoordinateUnits
OBJECT-TYPE
External sensor Z coordinate units: freeform text or rack units (U) Default is U.
1.3.6.1.4.1.13742.6.3.2.2.1.34ExternalSensorsZCoordinateUnitsEnumerationread-writecurrent
unitDeviceCapabilities
OBJECT-TYPE
A bit string indicating which unit sensors are available.
1.3.6.1.4.1.13742.6.3.2.2.1.35Bits {i1smpsStatus(45), i2smpsStatus(46)}read-onlycurrent
outletSequencingDelay
OBJECT-TYPE
It is deprecated. This is an alias for inrushGuardDelay
1.3.6.1.4.1.13742.6.3.2.2.1.36Unsigned32read-writedeprecated
globalOutletPowerCyclingPowerOffPeriod
OBJECT-TYPE
The power-off period when an outlet is cycled; applies to all outlets unless overridden at the outlet level; specified in seconds; 1 <= value <= 3600 seconds.
1.3.6.1.4.1.13742.6.3.2.2.1.37Unsigned32read-writecurrent
globalOutletStateOnStartup
OBJECT-TYPE
The outlet state on device startup; applies to all outlets unless overridden at the outlet level. Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching.
1.3.6.1.4.1.13742.6.3.2.2.1.38GlobalOutletStateOnStartupEnumerationread-writecurrent
outletPowerupSequence
OBJECT-TYPE
The sequence in which will the outlets will be switched on under the following conditions. 1) Switch all outlets on operation is executed 2) Power to the PDU is cycled String must consist of a comma separated sequence of the outlet numbers and all outlet numbers must be included. The numbers entered must be a permutation of the numbers 1,2,3,-outletnumber. Example for a 12 outlet PDU: 1,12,3,5,6,7,10,2,4,11,9,8. The per outlet sequence delays are defined as outletSequenceDelay in the outletConfigurationTable
1.3.6.1.4.1.13742.6.3.2.2.1.39DisplayStringread-writecurrent
pduPowerCyclingPowerOffPeriod
OBJECT-TYPE
When power to the PX is cycled (either manually or because of a temporary power loss), this number determines how many seconds the PX will wait before it provides power to the outlets. specified in seconds: 1 <= value <= 3600 seconds. Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching.
1.3.6.1.4.1.13742.6.3.2.2.1.40Unsigned32read-writecurrent
pduDaisychainMemberType
OBJECT-TYPE
The daisy chain member type.
1.3.6.1.4.1.13742.6.3.2.2.1.41DaisychainMemberTypeEnumerationread-onlycurrent
managedExternalSensorCount
OBJECT-TYPE
The number of managed external sensors
1.3.6.1.4.1.13742.6.3.2.2.1.42Integer32 (0..255)read-onlycurrent
pxInetAddressType
OBJECT-TYPE
The type of address format This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293).
1.3.6.1.4.1.13742.6.3.2.2.1.50InetAddressTyperead-onlydeprecated
pxInetIPAddress
OBJECT-TYPE
The current IP address. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0
1.3.6.1.4.1.13742.6.3.2.2.1.51InetAddressread-onlydeprecated
pxInetNetmask
OBJECT-TYPE
The current netmask. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0
1.3.6.1.4.1.13742.6.3.2.2.1.52InetAddressread-onlydeprecated
pxInetGateway
OBJECT-TYPE
The current gateway. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0
1.3.6.1.4.1.13742.6.3.2.2.1.53InetAddressread-onlydeprecated
loadShedding
OBJECT-TYPE
Enter/Exit Load Shedding Mode
1.3.6.1.4.1.13742.6.3.2.2.1.55TruthValueread-writecurrent
serverCount
OBJECT-TYPE
The number of servers monitored with the server reachability feature
1.3.6.1.4.1.13742.6.3.2.2.1.56Integer32 (0..255)read-onlycurrent
inrushGuardDelay
OBJECT-TYPE
The time interval between switching on two outlets; specified in milliseconds; 100 <= value <= 100000 milliseconds.
1.3.6.1.4.1.13742.6.3.2.2.1.57Unsigned32read-writecurrent
cascadedDeviceConnected
OBJECT-TYPE
Indicates whether another PX2 is connected using an USB cable to the USB-A port of this PX2 in a cascaded configuration.
1.3.6.1.4.1.13742.6.3.2.2.1.58TruthValueread-onlycurrent
synchronizeWithNTPServer
OBJECT-TYPE
Indicates whether time is synchronized with an NTP server.
1.3.6.1.4.1.13742.6.3.2.2.1.59TruthValueread-writecurrent
useDHCPProvidedNTPServer
OBJECT-TYPE
**NOTE: This object is obsolete. Its functionality has been replaced by the following: - If at least one of firstNTPServerAddress and secondNTPServerAddress has been configured then use the static NTP servers - else use the DHCP-provided NTP servers
1.3.6.1.4.1.13742.6.3.2.2.1.60TruthValueread-writeobsolete
firstNTPServerAddressType
OBJECT-TYPE
Represents the type of the corresponding instance of firstNTPServerAddress object. When setting this value, be sure that firstNTPServerAddress is of this address type, e.g. by setting both of them.
1.3.6.1.4.1.13742.6.3.2.2.1.61InetAddressTyperead-writecurrent
firstNTPServerAddress
OBJECT-TYPE
The address of the primary NTP server. When setting this value, be sure that it is of the type specified in firstNTPServerAddressType, e.g. by setting both of them.
1.3.6.1.4.1.13742.6.3.2.2.1.62InetAddressread-writecurrent
secondNTPServerAddressType
OBJECT-TYPE
Represents the type of the corresponding instance of secondNTPServerAddress object. When setting this value, be sure that secondNTPServerAddress is of this address type, e.g. by setting both of them. Default is ipv4
1.3.6.1.4.1.13742.6.3.2.2.1.63InetAddressTyperead-writecurrent
secondNTPServerAddress
OBJECT-TYPE
The address of the second NTP server. When setting this value, be sure that it is of the type specified in secondNTPServerAddressType, e.g. by setting both of them.
1.3.6.1.4.1.13742.6.3.2.2.1.64InetAddressread-writecurrent
wireCount
OBJECT-TYPE
The number of wire objects in the PDU topology. This feature is no longer used, the returned value is always 0.
1.3.6.1.4.1.13742.6.3.2.2.1.65Integer32 (0..255)read-onlydeprecated
transferSwitchCount
OBJECT-TYPE
The number of transfer switches.
1.3.6.1.4.1.13742.6.3.2.2.1.66Integer32 (0..255)read-onlycurrent
productType
OBJECT-TYPE
The product type (PDU, BCM, transfer switch or power meter).
1.3.6.1.4.1.13742.6.3.2.2.1.67ProductTypeEnumerationread-onlycurrent
meteringControllerCount
OBJECT-TYPE
The number of metering controllers.
1.3.6.1.4.1.13742.6.3.2.2.1.68Integer32 (0..255)read-onlycurrent
relayBehaviorOnPowerLoss
OBJECT-TYPE
The relay behavior on power loss (latching or non-latching).
1.3.6.1.4.1.13742.6.3.2.2.1.69RelayPowerLossBehaviorEnumerationread-writecurrent
deviceCascadeType
OBJECT-TYPE
The type of network cascade this device is part of (none, bridging or port forwarding).
1.3.6.1.4.1.13742.6.3.2.2.1.70DeviceCascadeTypeEnumerationread-writecurrent
deviceCascadePosition
OBJECT-TYPE
The position of the device in the cascade chain. Only supported in port forwarding mode, 0 otherwise.
1.3.6.1.4.1.13742.6.3.2.2.1.71Integer32 (0..99)read-onlycurrent
peripheralDevicesAutoManagement
OBJECT-TYPE
Defines whether newly-connected peripheral devices are automatically assigned to an unused slot.
1.3.6.1.4.1.13742.6.3.2.2.1.72TruthValueread-writecurrent
frontPanelOutletSwitching
OBJECT-TYPE
Enables/disables switching of outlets using the PDU front panel.
1.3.6.1.4.1.13742.6.3.2.2.1.73TruthValueread-writecurrent
frontPanelRCMSelfTest
OBJECT-TYPE
Enables/disables front panel RCM self-test.
1.3.6.1.4.1.13742.6.3.2.2.1.74TruthValueread-writecurrent
frontPanelActuatorControl
OBJECT-TYPE
Enables/disables front panel peripheral actuator control.
1.3.6.1.4.1.13742.6.3.2.2.1.75TruthValueread-writecurrent
circuitCount
OBJECT-TYPE
The number of branch circuits in a panel.
1.3.6.1.4.1.13742.6.3.2.2.1.76Integer32read-onlycurrent
activeDNSServerCount
OBJECT-TYPE
The number of active DNS servers
1.3.6.1.4.1.13742.6.3.2.2.1.77Integer32 (0..16)read-onlycurrent
activeNTPServerCount
OBJECT-TYPE
The number of active NTP servers
1.3.6.1.4.1.13742.6.3.2.2.1.78Integer32 (0..16)read-onlycurrent
controllerConfigurationTable
OBJECT-TYPE
A list of entries for the boards in a PDU. The number of entries is one more than the sum of inletControllerCount, outletControllerCount and meterControllerCount.
1.3.6.1.4.1.13742.6.3.2.3not-accessiblecurrent
controllerConfigurationEntry
OBJECT-TYPE
An entry containing objects for a controller.
1.3.6.1.4.1.13742.6.3.2.3.1not-accessiblecurrent
boardType
OBJECT-TYPE
The type of board.
1.3.6.1.4.1.13742.6.3.2.3.1.1BoardTypeEnumerationnot-accessiblecurrent
boardIndex
OBJECT-TYPE
A unique value for each controller.
1.3.6.1.4.1.13742.6.3.2.3.1.2Integer32 (1..256)not-accessiblecurrent
boardVersion
OBJECT-TYPE
The board hardware version.
1.3.6.1.4.1.13742.6.3.2.3.1.4DisplayStringread-onlycurrent
boardFirmwareVersion
OBJECT-TYPE
The firmware version.
1.3.6.1.4.1.13742.6.3.2.3.1.6DisplayStringread-onlycurrent
boardFirmwareTimeStamp
OBJECT-TYPE
The time when the board firmware was updated as UNIX timestamp. It is measured in seconds since January 1, 1970 (midnight UTC/GMT)
1.3.6.1.4.1.13742.6.3.2.3.1.8Unsigned32read-onlycurrent
logConfigurationTable
OBJECT-TYPE
A table of parameters for the data logging feature. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.3.2.4not-accessiblecurrent
logConfigurationEntry
OBJECT-TYPE
An entry containing data logging parameters for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.4.1not-accessiblecurrent
dataLogging
OBJECT-TYPE
Defines whether sensor data logging is enabled.
1.3.6.1.4.1.13742.6.3.2.4.1.1TruthValueread-writecurrent
measurementPeriod
OBJECT-TYPE
Data collection periodicity. This is the periodicity of the data collected by the PDU. This value is fixed at 1 second.
1.3.6.1.4.1.13742.6.3.2.4.1.2Integer32read-onlycurrent
measurementsPerLogEntry
OBJECT-TYPE
The number of measurements aggregated into a data log entry.
1.3.6.1.4.1.13742.6.3.2.4.1.3Integer32read-writecurrent
logSize
OBJECT-TYPE
The capacity (number of entries) of the data log.
1.3.6.1.4.1.13742.6.3.2.4.1.4Integer32read-onlycurrent
dataLoggingEnableForAllSensors
OBJECT-TYPE
Operation to control data logging for all sensors: - when set to true, all *SensorLogAvailable OIDs are set to true - when set to false, all *SensorLogAvailable OIDs are set to false
1.3.6.1.4.1.13742.6.3.2.4.1.5TruthValueread-writecurrent
unitSensorConfigurationTable
OBJECT-TYPE
A list of unit-level sensors for a PDU.
1.3.6.1.4.1.13742.6.3.2.5not-accessiblecurrent
unitSensorConfigurationEntry
OBJECT-TYPE
An entry containing unit sensor parameters.
1.3.6.1.4.1.13742.6.3.2.5.1not-accessiblecurrent
sensorType
OBJECT-TYPE
The type of sensor.
1.3.6.1.4.1.13742.6.3.2.5.1.1SensorTypeEnumerationnot-accessiblecurrent
unitSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.2.5.1.4TruthValueread-writecurrent
unitSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.6SensorUnitsEnumerationread-onlycurrent
unitSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point.
1.3.6.1.4.1.13742.6.3.2.5.1.7Unsigned32read-onlycurrent
unitSensorAccuracy
OBJECT-TYPE
The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.8HundredthsOfAPercentageread-onlydeprecated
unitSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.9Unsigned32read-onlycurrent
unitSensorTolerance
OBJECT-TYPE
The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (unitSensorDecimalDigits + 1). For example, if the value is 50 and unitSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.10Unsigned32read-onlydeprecated
unitSensorMaximum
OBJECT-TYPE
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.11Unsigned32read-onlycurrent
unitSensorMinimum
OBJECT-TYPE
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.12Unsigned32read-onlycurrent
unitSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.13Unsigned32read-writecurrent
unitSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.14Unsigned32read-writecurrent
unitSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.21Unsigned32read-writecurrent
unitSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.22Unsigned32read-writecurrent
unitSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.23Unsigned32read-writecurrent
unitSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.24Unsigned32read-writecurrent
unitSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
unitSensorSignedMaximum
OBJECT-TYPE
The largest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.26Integer32read-onlycurrent
unitSensorSignedMinimum
OBJECT-TYPE
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.27Integer32read-onlycurrent
unitSensorSignedLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.28Integer32read-writecurrent
unitSensorSignedLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.29Integer32read-writecurrent
unitSensorSignedUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.30Integer32read-writecurrent
unitSensorSignedUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.31Integer32read-writecurrent
activeDNSServerTable
OBJECT-TYPE
A list of active DNS server entries. The number of rows in the table is given by the value of activeDNSServerCount in unitConfigurationTable.
1.3.6.1.4.1.13742.6.3.2.6not-accessiblecurrent
activeDNSServerEntry
OBJECT-TYPE
An entry containing an active DNS server for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.6.1not-accessiblecurrent
activeDNSServerIndex
OBJECT-TYPE
A unique value for a DNS server. Its value ranges between 1 and activeDNSServerCount.
1.3.6.1.4.1.13742.6.3.2.6.1.2Integer32 (1..16)not-accessiblecurrent
activeDNSServerAddressType
OBJECT-TYPE
Represents the type of the corresponding instance of activeDNSServerAddress object.
1.3.6.1.4.1.13742.6.3.2.6.1.3InetAddressTyperead-onlycurrent
activeDNSServerAddress
OBJECT-TYPE
The address of the DNS server.
1.3.6.1.4.1.13742.6.3.2.6.1.4InetAddressread-onlycurrent
activeDNSServerAddressSource
OBJECT-TYPE
How was the address obtained: static, DHCP, DHCPv6? No longer used, always set to static.
1.3.6.1.4.1.13742.6.3.2.6.1.5AddressSourceEnumerationread-onlydeprecated
activeNTPServerTable
OBJECT-TYPE
A list of active NTP server entries. The number of rows in the table is given by the value of activeNTPServerCount in unitConfigurationTable.
1.3.6.1.4.1.13742.6.3.2.7not-accessiblecurrent
activeNTPServerEntry
OBJECT-TYPE
An entry containing an active NTP server for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.7.1not-accessiblecurrent
activeNTPServerIndex
OBJECT-TYPE
A unique value for an NTP server. Its value ranges between 1 and activeNTPServerCount.
1.3.6.1.4.1.13742.6.3.2.7.1.2Integer32 (1..16)not-accessiblecurrent
activeNTPServerAddressType
OBJECT-TYPE
Represents the type of the corresponding instance of activeNTPServerAddress object, e.g. IPv4, IPv6, DNS Name
1.3.6.1.4.1.13742.6.3.2.7.1.3InetAddressTyperead-onlycurrent
activeNTPServerAddress
OBJECT-TYPE
The address of the NTP server.
1.3.6.1.4.1.13742.6.3.2.7.1.4InetAddressread-onlycurrent
activeNTPServerAddressSource
OBJECT-TYPE
How was the address obtained: static, DHCP, DHCPv6? No longer used, always set to static.
1.3.6.1.4.1.13742.6.3.2.7.1.5AddressSourceEnumerationread-onlydeprecated
inlets
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.3
inletConfigurationTable
OBJECT-TYPE
A list of inlet configuration entries. The number of entries is given by the value of inletCount for the PDU.
1.3.6.1.4.1.13742.6.3.3.3not-accessiblecurrent
inletConfigurationEntry
OBJECT-TYPE
An entry containing parametersfor a particular inlet.
1.3.6.1.4.1.13742.6.3.3.3.1not-accessiblecurrent
inletId
OBJECT-TYPE
A unique value for each inlet. Its value ranges between 1 and the value of inletCount.
1.3.6.1.4.1.13742.6.3.3.3.1.1Integer32 (1..256)not-accessiblecurrent
inletLabel
OBJECT-TYPE
The label on the PDU identifying the inlet.
1.3.6.1.4.1.13742.6.3.3.3.1.2DisplayStringread-onlycurrent
inletName
OBJECT-TYPE
The user-defined name.
1.3.6.1.4.1.13742.6.3.3.3.1.3DisplayStringread-writecurrent
inletPlug
OBJECT-TYPE
The type of plug/receptacle wired to the inlet. Note: PlugTypeEnumeration is no longer updated, unlisted plugs will be reported as plugOTHER. Use inletPlugDescriptor to reliably determine the plug type.
1.3.6.1.4.1.13742.6.3.3.3.1.4PlugTypeEnumerationread-onlycurrent
inletPoleCount
OBJECT-TYPE
The number of poles. PDU: 2 for 1-phase circuits 3 for 3-phase delta-wired models 4 for 3-phase wye-wired models, pole 4 is neutral Power Meter: 2 to 5 depending on the power meter type: Pole 1 is Phase A Pole 2 is Phase B Pole 3 is Phase C Pole 4 is Neutral Pole 5 is Earth
1.3.6.1.4.1.13742.6.3.3.3.1.5Integer32 (2..5)read-onlycurrent
inletRatedVoltage
OBJECT-TYPE
The inlet voltage rating.
1.3.6.1.4.1.13742.6.3.3.3.1.6DisplayStringread-onlycurrent
inletRatedCurrent
OBJECT-TYPE
The inlet current rating.
1.3.6.1.4.1.13742.6.3.3.3.1.7DisplayStringread-onlycurrent
inletRatedFrequency
OBJECT-TYPE
The inlet frequency rating. Deprecated: use pduRatedFrequency for unit nameplate information.
1.3.6.1.4.1.13742.6.3.3.3.1.8DisplayStringread-onlydeprecated
inletRatedVA
OBJECT-TYPE
The inlet VA (VoltAmps) rating. Deprecated: use pduRatedVA for unit nameplate information.
1.3.6.1.4.1.13742.6.3.3.3.1.9DisplayStringread-onlydeprecated
inletDeviceCapabilities
OBJECT-TYPE
A bit string indicating which inlet sensors are available.
1.3.6.1.4.1.13742.6.3.3.3.1.10Bits {rmsCurrent(0), peakCurrent(1), unbalancedCurrent(2), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), surgeProtectorStatus(21), frequency(22), phaseAngle(23), residualCurrent(25), rcmState(26), reactivePower(28), powerQuality(31)}read-onlycurrent
inletPoleCapabilities
OBJECT-TYPE
A bit string indicating which inlet pole sensors are available.
1.3.6.1.4.1.13742.6.3.3.3.1.11Bits {rmsCurrent(0), peakCurrent(1), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), phaseAngle(23), rmsVoltageLN(24), reactivePower(28), displacementPowerFactor(34)}read-onlycurrent
inletPlugDescriptor
OBJECT-TYPE
The inlet plug type as a string.
1.3.6.1.4.1.13742.6.3.3.3.1.12DisplayStringread-onlycurrent
inletEnableState
OBJECT-TYPE
Enable/disable PDU operation for this inlet. When PDU operation is disabled the sensors for this inlet and all children will no longer be updated, and outlet switching is no longer allowed. This is only meaningful for multi-inlet units if one inlet is temporarily expected to be powered down. Disabling the inlet of a single-inlet unit is forbidden and any attempt to do so will result in an error.
1.3.6.1.4.1.13742.6.3.3.3.1.13TruthValueread-writecurrent
inletRCMResidualOperatingCurrent
OBJECT-TYPE
**NOTE:This object is obsolete. Its functionality was implemented by existing RCM sensor thresholds. The Residual Operating Current (Threshold) for the RCM State sensor. For inlets without an RCM, any attempt to access this OID will return NoSuchInstance error. The value of this OID is in milliamps.
1.3.6.1.4.1.13742.6.3.3.3.1.14Unsigned32read-writeobsolete
inletSensorConfigurationTable
OBJECT-TYPE
A list of configuration entries for an inlet sensor.
1.3.6.1.4.1.13742.6.3.3.4not-accessiblecurrent
inletSensorConfigurationEntry
OBJECT-TYPE
An entry containing objects for configuring an inlet sensor.
1.3.6.1.4.1.13742.6.3.3.4.1not-accessiblecurrent
inletSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.3.4.1.4TruthValueread-writecurrent
inletSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.6SensorUnitsEnumerationread-onlycurrent
inletSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.7Unsigned32read-onlycurrent
inletSensorAccuracy
OBJECT-TYPE
The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.8HundredthsOfAPercentageread-onlydeprecated
inletSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.9Unsigned32read-onlycurrent
inletSensorTolerance
OBJECT-TYPE
The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (inletSensorDecimalDigits + 1). For example, if the value is 50 and inletSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.10Unsigned32read-onlydeprecated
inletSensorMaximum
OBJECT-TYPE
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.11Unsigned32read-onlycurrent
inletSensorMinimum
OBJECT-TYPE
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.12Unsigned32read-onlycurrent
inletSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.13Unsigned32read-writecurrent
inletSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.14Unsigned32read-writecurrent
inletSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.21Unsigned32read-writecurrent
inletSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.22Unsigned32read-writecurrent
inletSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.23Unsigned32read-writecurrent
inletSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.24Unsigned32read-writecurrent
inletSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
inletSensorSignedMaximum
OBJECT-TYPE
The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.26Integer32read-onlycurrent
inletSensorSignedMinimum
OBJECT-TYPE
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.27Integer32read-onlycurrent
inletSensorSignedLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.28Integer32read-writecurrent
inletSensorSignedLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.29Integer32read-writecurrent
inletSensorSignedUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.30Integer32read-writecurrent
inletSensorSignedUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.31Integer32read-writecurrent
inletPoleConfigurationTable
OBJECT-TYPE
A list of inlet pole configuration entries. The number of entries is given by the value of inletPoleCount for the inlet.
1.3.6.1.4.1.13742.6.3.3.5not-accessiblecurrent
inletPoleConfigurationEntry
OBJECT-TYPE
An entry containing parameters for a particular inlet pole.
1.3.6.1.4.1.13742.6.3.3.5.1not-accessiblecurrent
inletPoleLine
OBJECT-TYPE
The phase for this inlet pole.
1.3.6.1.4.1.13742.6.3.3.5.1.1LineEnumerationread-onlycurrent
inletPoleNode
OBJECT-TYPE
The node to which this inlet pole is connected
1.3.6.1.4.1.13742.6.3.3.5.1.2Integer32read-onlycurrent
inletPoleSensorConfigurationTable
OBJECT-TYPE
A list of configuration entries for an inlet pole sensor.
1.3.6.1.4.1.13742.6.3.3.6not-accessiblecurrent
inletPoleSensorConfigurationEntry
OBJECT-TYPE
An entry containing objects for configuring an inlet pole sensor.
1.3.6.1.4.1.13742.6.3.3.6.1not-accessiblecurrent
inletPoleIndex
OBJECT-TYPE
A unique value for each inlet pole. Its value ranges between 1 and the value of inletPoleCount.
1.3.6.1.4.1.13742.6.3.3.6.1.1Integer32 (1..256)not-accessiblecurrent
inletPoleSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.3.6.1.4TruthValueread-writecurrent
inletPoleSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.6SensorUnitsEnumerationread-onlycurrent
inletPoleSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.7Unsigned32read-onlycurrent
inletPoleSensorAccuracy
OBJECT-TYPE
The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.8HundredthsOfAPercentageread-onlydeprecated
inletPoleSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.9Unsigned32read-onlycurrent
inletPoleSensorTolerance
OBJECT-TYPE
The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (inletPoleSensorDecimalDigits + 1). For example, if the value is 50 and inletPoleSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.10Unsigned32read-onlydeprecated
inletPoleSensorMaximum
OBJECT-TYPE
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.11Unsigned32read-onlycurrent
inletPoleSensorMinimum
OBJECT-TYPE
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.12Unsigned32read-onlycurrent
inletPoleSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.13Unsigned32read-writecurrent
inletPoleSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.14Unsigned32read-writecurrent
inletPoleSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.21Unsigned32read-writecurrent
inletPoleSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.22Unsigned32read-writecurrent
inletPoleSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.23Unsigned32read-writecurrent
inletPoleSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.24Unsigned32read-writecurrent
inletPoleSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
inletPoleSensorSignedMaximum
OBJECT-TYPE
The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.26Integer32read-onlycurrent
inletPoleSensorSignedMinimum
OBJECT-TYPE
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.27Integer32read-onlycurrent
inletPoleSensorSignedLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.28Integer32read-writecurrent
inletPoleSensorSignedLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.29Integer32read-writecurrent
inletPoleSensorSignedUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.30Integer32read-writecurrent
inletPoleSensorSignedUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.31Integer32read-writecurrent
overCurrentProtector
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.4
overCurrentProtectorConfigurationTable
OBJECT-TYPE
A list of overcurrent protector configuration entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU.
1.3.6.1.4.1.13742.6.3.4.3not-accessiblecurrent
overCurrentProtectorConfigurationEntry
OBJECT-TYPE
An entry containing objects for a particular overcurrent protector.
1.3.6.1.4.1.13742.6.3.4.3.1not-accessiblecurrent
overCurrentProtectorIndex
OBJECT-TYPE
A unique value for each overcurrent protector. Its value ranges between 1 and the value of overCurrentProtectorCount.
1.3.6.1.4.1.13742.6.3.4.3.1.1Integer32 (1..256)not-accessiblecurrent
overCurrentProtectorLabel
OBJECT-TYPE
The label on the PDU identifying the overcurrent protector.
1.3.6.1.4.1.13742.6.3.4.3.1.2DisplayStringread-onlycurrent
overCurrentProtectorName
OBJECT-TYPE
The user-defined name.
1.3.6.1.4.1.13742.6.3.4.3.1.3DisplayStringread-writecurrent
overCurrentProtectorType
OBJECT-TYPE
The type of overcurrent protector.
1.3.6.1.4.1.13742.6.3.4.3.1.4OverCurrentProtectorTypeEnumerationread-onlycurrent
overCurrentProtectorRatedCurrent
OBJECT-TYPE
The current rating.
1.3.6.1.4.1.13742.6.3.4.3.1.5DisplayStringread-onlycurrent
overCurrentProtectorPoleCount
OBJECT-TYPE
The number of overcurrent protector poles.
1.3.6.1.4.1.13742.6.3.4.3.1.6Integer32 (1..3)read-onlycurrent
overCurrentProtectorCapabilities
OBJECT-TYPE
A bit string indicating which overcurrent protector sensors are available.
1.3.6.1.4.1.13742.6.3.4.3.1.9Bits {rmsCurrent(0), peakCurrent(1), trip(14)}read-onlycurrent
overCurrentProtectorPowerSource
OBJECT-TYPE
This object allows discovery of how the PDU is wired. It indicates the overcurrent protector's power source which can be one of the following: - an inlet - another overcurrent protector - a transfer switch If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet tables. If the power source is an overcurrent protector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfigurationTable. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. If the power source is a transfer switch, it contains the OID of a transferSwitchLabel in the transferSwitchConfigurationTable. The indices of the OID can then be used to reference other objects in the transfer switch tables.
1.3.6.1.4.1.13742.6.3.4.3.1.10RowPointerread-onlycurrent
overCurrentProtectorSensorConfigurationTable
OBJECT-TYPE
A list of overcurrent protector sensor configuration entries.
1.3.6.1.4.1.13742.6.3.4.4not-accessiblecurrent
overCurrentProtectorSensorConfigurationEntry
OBJECT-TYPE
An overcurrent protector sensor entry containing objects for a particular overcurrent protector sensor.
1.3.6.1.4.1.13742.6.3.4.4.1not-accessiblecurrent
overCurrentProtectorSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.4.4.1.4TruthValueread-writecurrent
overCurrentProtectorSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.6SensorUnitsEnumerationread-onlycurrent
overCurrentProtectorSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.7Unsigned32read-onlycurrent
overCurrentProtectorSensorAccuracy
OBJECT-TYPE
The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.8HundredthsOfAPercentageread-onlydeprecated
overCurrentProtectorSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.9Unsigned32read-onlycurrent
overCurrentProtectorSensorTolerance
OBJECT-TYPE
The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (overCurrentProtectorSensorDecimalDigits + 1). For example, if the value is 50 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.10Unsigned32read-onlydeprecated
overCurrentProtectorSensorMaximum
OBJECT-TYPE
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.11Unsigned32read-onlycurrent
overCurrentProtectorSensorMinimum
OBJECT-TYPE
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.12Unsigned32read-onlycurrent
overCurrentProtectorSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.13Unsigned32read-writecurrent
overCurrentProtectorSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.14Unsigned32read-writecurrent
overCurrentProtectorSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.21Unsigned32read-writecurrent
overCurrentProtectorSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.22Unsigned32read-writecurrent
overCurrentProtectorSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.23Unsigned32read-writecurrent
overCurrentProtectorSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.24Unsigned32read-writecurrent
overCurrentProtectorSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
overCurrentProtectorSensorSignedMaximum
OBJECT-TYPE
The largest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.26Integer32read-onlycurrent
overCurrentProtectorSensorSignedMinimum
OBJECT-TYPE
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.27Integer32read-onlycurrent
overCurrentProtectorSensorSignedLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.28Integer32read-writecurrent
overCurrentProtectorSensorSignedLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.29Integer32read-writecurrent
overCurrentProtectorSensorSignedUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.30Integer32read-writecurrent
overCurrentProtectorSensorSignedUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.31Integer32read-writecurrent
overCurrentProtectorPoleConfigurationTable
OBJECT-TYPE
A list of overcurrent protector pole configuration entries. The number of entries is given by the value of overCurrentProtectorPoleCount.
1.3.6.1.4.1.13742.6.3.4.5not-accessiblecurrent
overCurrentProtectorPoleConfigurationEntry
OBJECT-TYPE
An entry containing parameters for a particular overcurrent protector pole.
1.3.6.1.4.1.13742.6.3.4.5.1not-accessiblecurrent
overCurrentProtectorPoleIndex
OBJECT-TYPE
A unique value for each overcurrent protector pole. Its value ranges between 1 and the value of overCurrentProtectorPoleCount.
1.3.6.1.4.1.13742.6.3.4.5.1.1Integer32 (1..256)not-accessiblecurrent
overCurrentProtectorPoleLine
OBJECT-TYPE
The phase for this overcurrent protector pole.
1.3.6.1.4.1.13742.6.3.4.5.1.2LineEnumerationread-onlycurrent
overCurrentProtectorPoleInNode
OBJECT-TYPE
The node to which this overcurrent protector pole input is connected
1.3.6.1.4.1.13742.6.3.4.5.1.3Integer32read-onlycurrent
overCurrentProtectorPoleOutNode
OBJECT-TYPE
The node to which this overcurrent protector pole output is connected
1.3.6.1.4.1.13742.6.3.4.5.1.4Integer32read-onlycurrent
outlets
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.5
outletConfigurationTable
OBJECT-TYPE
A list of outlet configuration entries. The number of entries is given by the value of outletCount for the PDU.
1.3.6.1.4.1.13742.6.3.5.3not-accessiblecurrent
outletConfigurationEntry
OBJECT-TYPE
An outlet entry containing parameters for a particular outlet.
1.3.6.1.4.1.13742.6.3.5.3.1not-accessiblecurrent
outletId
OBJECT-TYPE
A unique value for each outlet. Its value ranges between 1 and the value of outletCount.
1.3.6.1.4.1.13742.6.3.5.3.1.1Integer32 (1..256)not-accessiblecurrent
outletLabel
OBJECT-TYPE
The label on the PDU identifying the outlet.
1.3.6.1.4.1.13742.6.3.5.3.1.2DisplayStringread-onlycurrent
outletName
OBJECT-TYPE
The user-defined name.
1.3.6.1.4.1.13742.6.3.5.3.1.3DisplayStringread-writecurrent
outletReceptacle
OBJECT-TYPE
The receptacle type. Note: ReceptacleTypeEnumeration is no longer updated, unlisted receptacles will be listed as receptacleOTHER. Use outletReceptacleDescriptor to reliably determine the receptacle type.
1.3.6.1.4.1.13742.6.3.5.3.1.4ReceptacleTypeEnumerationread-onlycurrent
outletPoleCount
OBJECT-TYPE
The number of poles.
1.3.6.1.4.1.13742.6.3.5.3.1.5Integer32 (2..4)read-onlycurrent
outletRatedVoltage
OBJECT-TYPE
The outlet voltage rating.
1.3.6.1.4.1.13742.6.3.5.3.1.6DisplayStringread-onlycurrent
outletRatedCurrent
OBJECT-TYPE
The outlet current rating.
1.3.6.1.4.1.13742.6.3.5.3.1.7DisplayStringread-onlycurrent
outletRatedVA
OBJECT-TYPE
The outlet VA (VoltAmps) rating.
1.3.6.1.4.1.13742.6.3.5.3.1.8DisplayStringread-onlycurrent
outletDeviceCapabilities
OBJECT-TYPE
A bit string indicating which outlet sensors are available.
1.3.6.1.4.1.13742.6.3.5.3.1.10Bits {rmsCurrent(0), peakCurrent(1), unbalancedCurrent(2), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), onOff(13), frequency(22), phaseAngle(23)}read-onlycurrent
outletPoleCapabilities
OBJECT-TYPE
A bit string indicating which outlet pole sensors are available.
1.3.6.1.4.1.13742.6.3.5.3.1.11Bits {rmsCurrent(0), peakCurrent(1), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), rmsVoltageLN(24)}read-onlycurrent
outletPowerCyclingPowerOffPeriod
OBJECT-TYPE
The power-off period when an outlet is cycled. Overrides the global value if outletUseGlobalPowerCyclingPowerOffPeriod is false. Specified in seconds, 1 <= value <= 3600.
1.3.6.1.4.1.13742.6.3.5.3.1.12Unsigned32read-writecurrent
outletStateOnStartup
OBJECT-TYPE
The outlet state on device startup. This value is ignored if relayBehaviorOnPowerLoss is set to latching.
1.3.6.1.4.1.13742.6.3.5.3.1.13OutletStateOnStartupEnumerationread-writecurrent
outletUseGlobalPowerCyclingPowerOffPeriod
OBJECT-TYPE
Indicates which power-off period to use when the outlet is cycled: - true: use globalOutletPowerCyclingPowerOffPeriod - false: use outletPowerCyclingPowerOffPeriod
1.3.6.1.4.1.13742.6.3.5.3.1.14TruthValueread-writecurrent
outletSwitchable
OBJECT-TYPE
Is this outlet switchable?
1.3.6.1.4.1.13742.6.3.5.3.1.28TruthValueread-onlycurrent
outletReceptacleDescriptor
OBJECT-TYPE
The outlet receptacle type as a string.
1.3.6.1.4.1.13742.6.3.5.3.1.29DisplayStringread-onlycurrent
outletNonCritical
OBJECT-TYPE
Is this outlet non-critical? Non-critical outlets will be switched off when load shedding is enabled.
1.3.6.1.4.1.13742.6.3.5.3.1.30TruthValueread-writecurrent
outletSequenceDelay
OBJECT-TYPE
The time interval between switching on this outlet and the next outlet in the outlet sequence. This applies to the following operations. 1) Switch all outlets on operation is executed 2) Power to the PDU is cycled It is specified in seconds, 0 <= value <= 3600 seconds. The effective time interval used can never be less than the inrushGuardDelay defined in the unitConfigurationTable.
1.3.6.1.4.1.13742.6.3.5.3.1.32Unsigned32read-writecurrent
outletPowerSource
OBJECT-TYPE
This object allows discovery of how the PDU is wired. It indicates the outlet's power source which can one of the following: - an inlet - an overcurrent protector - a transfer switch If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet tables. If the power source is an overcurrent protector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfigurationTable. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. If the power source is a transfer switch, it contains the OID of a transferSwitchLabel in the transferSwitchConfigurationTable. The indices of the OID can then be used to reference other objects in the transfer switch tables.
1.3.6.1.4.1.13742.6.3.5.3.1.33RowPointerread-onlycurrent
outletSensorConfigurationTable
OBJECT-TYPE
A list of outlet sensor configuration entries.
1.3.6.1.4.1.13742.6.3.5.4not-accessiblecurrent
outletSensorConfigurationEntry
OBJECT-TYPE
An entry containing parameters for an outlet sensor.
1.3.6.1.4.1.13742.6.3.5.4.1not-accessiblecurrent
outletSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.5.4.1.4TruthValueread-writecurrent
outletSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.6SensorUnitsEnumerationread-onlycurrent
outletSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.7Unsigned32read-onlycurrent
outletSensorAccuracy
OBJECT-TYPE
The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.8HundredthsOfAPercentageread-onlydeprecated
outletSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.9Unsigned32read-onlycurrent
outletSensorTolerance
OBJECT-TYPE
The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (outletSensorDecimalDigits + 1). For example, if the value is 50 and outletSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.10Unsigned32read-onlydeprecated
outletSensorMaximum
OBJECT-TYPE
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.11Unsigned32read-onlycurrent
outletSensorMinimum
OBJECT-TYPE
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.12Unsigned32read-onlycurrent
outletSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.13Unsigned32read-writecurrent
outletSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.14Unsigned32read-writecurrent
outletSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.21Unsigned32read-writecurrent
outletSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.22Unsigned32read-writecurrent
outletSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.23Unsigned32read-writecurrent
outletSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.24Unsigned32read-writecurrent
outletSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
outletSensorSignedMaximum
OBJECT-TYPE
The largest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.26Integer32read-onlycurrent
outletSensorSignedMinimum
OBJECT-TYPE
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.27Integer32read-onlycurrent
outletSensorSignedLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.28Integer32read-writecurrent
outletSensorSignedLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.29Integer32read-writecurrent
outletSensorSignedUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.30Integer32read-writecurrent
outletSensorSignedUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.31Integer32read-writecurrent
outletPoleConfigurationTable
OBJECT-TYPE
A list of outlet pole configuration entries. The number of entries is given by the value of outletPoleCount for the PDU.
1.3.6.1.4.1.13742.6.3.5.5not-accessiblecurrent
outletPoleConfigurationEntry
OBJECT-TYPE
An entry containing parameters for a particular outlet pole.
1.3.6.1.4.1.13742.6.3.5.5.1not-accessiblecurrent
outletPoleLine
OBJECT-TYPE
The phase for this outlet pole.
1.3.6.1.4.1.13742.6.3.5.5.1.1LineEnumerationread-onlycurrent
outletPoleNode
OBJECT-TYPE
The node to which this outlet pole is connected
1.3.6.1.4.1.13742.6.3.5.5.1.2Integer32read-onlycurrent
outletPoleSensorConfigurationTable
OBJECT-TYPE
A list of outlet pole sensor configuration entries.
1.3.6.1.4.1.13742.6.3.5.6not-accessiblecurrent
outletPoleSensorConfigurationEntry
OBJECT-TYPE
An entry containing objects for configuring an outlet pole sensor.
1.3.6.1.4.1.13742.6.3.5.6.1not-accessiblecurrent
outletPoleIndex
OBJECT-TYPE
A unique value for each outlet pole. Its value ranges between 1 and the value of outletPoleCount.
1.3.6.1.4.1.13742.6.3.5.6.1.1Integer32 (1..256)not-accessiblecurrent
outletPoleSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.5.6.1.4TruthValueread-writecurrent
outletPoleSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.6SensorUnitsEnumerationread-onlycurrent
outletPoleSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.7Unsigned32read-onlycurrent
outletPoleSensorAccuracy
OBJECT-TYPE
The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.8HundredthsOfAPercentageread-onlydeprecated
outletPoleSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.9Unsigned32read-onlycurrent
outletPoleSensorTolerance
OBJECT-TYPE
The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (outletPoleSensorDecimalDigits + 1). For example, if the value is 50 and outletPoleSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.10Unsigned32read-onlydeprecated
outletPoleSensorMaximum
OBJECT-TYPE
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.11Unsigned32read-onlycurrent
outletPoleSensorMinimum
OBJECT-TYPE
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.12Unsigned32read-onlycurrent
outletPoleSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.13Unsigned32read-writecurrent
outletPoleSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.14Unsigned32read-writecurrent
outletPoleSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.21Unsigned32read-writecurrent
outletPoleSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.22Unsigned32read-writecurrent
outletPoleSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.23Unsigned32read-writecurrent
outletPoleSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.24Unsigned32read-writecurrent
outletPoleSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
outletPoleSensorSignedMaximum
OBJECT-TYPE
The largest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.26Integer32read-onlycurrent
outletPoleSensorSignedMinimum
OBJECT-TYPE
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.27Integer32read-onlycurrent
outletPoleSensorSignedLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.28Integer32read-writecurrent
outletPoleSensorSignedLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.29Integer32read-writecurrent
outletPoleSensorSignedUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.30Integer32read-writecurrent
outletPoleSensorSignedUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.31Integer32read-writecurrent
externalSensors
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.6
externalSensorConfigurationTable
OBJECT-TYPE
A list of external sensor configuration entries. The number of entries is given by the value of externalSensorCount for the PDU.
1.3.6.1.4.1.13742.6.3.6.3not-accessiblecurrent
externalSensorConfigurationEntry
OBJECT-TYPE
An entry containing parameters for an external sensor.
1.3.6.1.4.1.13742.6.3.6.3.1not-accessiblecurrent
sensorID
OBJECT-TYPE
A unique value for each sensor. Its value ranges between 1 and the value of externalSensorCount.
1.3.6.1.4.1.13742.6.3.6.3.1.1Integer32 (1..256)not-accessiblecurrent
externalSensorType
OBJECT-TYPE
The type of sensor.
1.3.6.1.4.1.13742.6.3.6.3.1.2SensorTypeEnumerationread-onlycurrent
externalSensorSerialNumber
OBJECT-TYPE
The sensor serial number.
1.3.6.1.4.1.13742.6.3.6.3.1.3DisplayStringread-onlycurrent
externalSensorName
OBJECT-TYPE
The user-defined name.
1.3.6.1.4.1.13742.6.3.6.3.1.4DisplayStringread-writecurrent
externalSensorDescription
OBJECT-TYPE
The user-defined description.
1.3.6.1.4.1.13742.6.3.6.3.1.5DisplayStringread-writecurrent
externalSensorXCoordinate
OBJECT-TYPE
The X coordinate.
1.3.6.1.4.1.13742.6.3.6.3.1.6DisplayStringread-writecurrent
externalSensorYCoordinate
OBJECT-TYPE
The Y coordinate.
1.3.6.1.4.1.13742.6.3.6.3.1.7DisplayStringread-writecurrent
externalSensorZCoordinate
OBJECT-TYPE
The Z coordinate. The value must be a number if externalSensorsZCoordinateUnits is rackUnits.
1.3.6.1.4.1.13742.6.3.6.3.1.8DisplayStringread-writecurrent
externalSensorChannelNumber
OBJECT-TYPE
The channel number. This applies only to contact sensors, -1 for other sensors.
1.3.6.1.4.1.13742.6.3.6.3.1.9Integer32read-onlycurrent
externalOnOffSensorSubtype
OBJECT-TYPE
The subtype of the binary sensor.
1.3.6.1.4.1.13742.6.3.6.3.1.10SensorTypeEnumerationread-writecurrent
externalSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.6.3.1.14TruthValueread-writecurrent
externalSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.16SensorUnitsEnumerationread-onlycurrent
externalSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.17Unsigned32read-onlycurrent
externalSensorAccuracy
OBJECT-TYPE
The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.18HundredthsOfAPercentageread-onlydeprecated
externalSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.19Unsigned32read-onlycurrent
externalSensorTolerance
OBJECT-TYPE
The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (externalSensorDecimalDigits + 1). For example, if the value is 50 and externalSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.20Unsigned32read-onlydeprecated
externalSensorMaximum
OBJECT-TYPE
The largest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.21Integer32read-onlycurrent
externalSensorMinimum
OBJECT-TYPE
The smallest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.22Integer32read-onlycurrent
externalSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.23Unsigned32read-writecurrent
externalSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.24Unsigned32read-writecurrent
externalSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.31Integer32read-writecurrent
externalSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.32Integer32read-writecurrent
externalSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.33Integer32read-writecurrent
externalSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.34Integer32read-writecurrent
externalSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.35Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
externalSensorIsActuator
OBJECT-TYPE
Indicates whether the sensor is an actuator.
1.3.6.1.4.1.13742.6.3.6.3.1.36TruthValueread-onlycurrent
externalSensorPosition
OBJECT-TYPE
The position of the sensor in the bus topology. The format is a semicolon separated list of Keyword:value pairs. Keyword can be one of the following: ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION Examples: 1) Onboard sensor ONBOARD:CC1 2) Old sensor connected to device 1-wire port DEVICE-1WIREPORT:2 3) New-style sensor connected to device 1-wire port DEVICE-1WIREPORT:2;CHAIN-POSITION:3 4) New-style sensor connected to hub port 3 DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1 5) Old-style sensor connected to end of new-style sensor chain DEVICE-1WIREPORT:2;
1.3.6.1.4.1.13742.6.3.6.3.1.37DisplayStringread-onlycurrent
externalSensorUseDefaultThresholds
OBJECT-TYPE
Use default thresholds for this sensor? True: Use default thresholds from externalSensorTypeDefaultThresholdsTable False: Use sensor-specific thresholds from this table
1.3.6.1.4.1.13742.6.3.6.3.1.38TruthValueread-writecurrent
externalSensorAlarmedToNormalDelay
OBJECT-TYPE
The delay (in seconds) before the sensor returns from alarmed to normal. This is supported for motion detectors only. For all other sensors the value is 0 and cannot be set to any other value.
1.3.6.1.4.1.13742.6.3.6.3.1.39Integer32read-writecurrent
externalSensorTypeDefaultThresholdsTable
OBJECT-TYPE
A table listing the default thresholds for each sensor type. The table contains a row for each supported type of external sensor with a numeric reading.
1.3.6.1.4.1.13742.6.3.6.4not-accessiblecurrent
externalSensorTypeDefaultThresholdsEntry
OBJECT-TYPE
An entry containing default thresholds for a sensor type.
1.3.6.1.4.1.13742.6.3.6.4.1not-accessiblecurrent
externalSensorTypeDefaultHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01.
1.3.6.1.4.1.13742.6.3.6.4.1.3Unsigned32read-writecurrent
externalSensorTypeDefaultStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported.
1.3.6.1.4.1.13742.6.3.6.4.1.4Unsigned32read-writecurrent
externalSensorTypeDefaultLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01.
1.3.6.1.4.1.13742.6.3.6.4.1.5Integer32read-writecurrent
externalSensorTypeDefaultLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01.
1.3.6.1.4.1.13742.6.3.6.4.1.6Integer32read-writecurrent
externalSensorTypeDefaultUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01.
1.3.6.1.4.1.13742.6.3.6.4.1.7Integer32read-writecurrent
externalSensorTypeDefaultUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01.
1.3.6.1.4.1.13742.6.3.6.4.1.8Integer32read-writecurrent
externalSensorTypeDefaultEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled.
1.3.6.1.4.1.13742.6.3.6.4.1.9Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
peripheralDevicePackageTable
OBJECT-TYPE
A list of entries for the peripheral device packages connected to a PDU. The number of entries is given by the value of peripheralDevicePackagesCount. A peripheral device package contains one or more sensors or actuators in a single enclosure.
1.3.6.1.4.1.13742.6.3.6.5not-accessiblecurrent
peripheralDevicePackageEntry
OBJECT-TYPE
An entry containing objects for a peripheral device package.
1.3.6.1.4.1.13742.6.3.6.5.1not-accessiblecurrent
peripheralDevicePackageId
OBJECT-TYPE
A unique value for each peripheral device package.
1.3.6.1.4.1.13742.6.3.6.5.1.1Integer32 (1..256)not-accessiblecurrent
peripheralDevicePackageSerialNumber
OBJECT-TYPE
The peripheral device package serial number.
1.3.6.1.4.1.13742.6.3.6.5.1.3DisplayStringread-onlycurrent
peripheralDevicePackageModel
OBJECT-TYPE
The peripheral device package model. Examples are DX-D2C6, DPX2-T1, DPX2-T1H1, DPX2-T2H1, DPX2-T3H1
1.3.6.1.4.1.13742.6.3.6.5.1.4DisplayStringread-onlycurrent
peripheralDevicePackageFirmwareVersion
OBJECT-TYPE
The peripheral device package firmware version.
1.3.6.1.4.1.13742.6.3.6.5.1.5DisplayStringread-onlycurrent
peripheralDevicePackageMinFirmwareVersion
OBJECT-TYPE
The peripheral device package minimum firmware version. This field may be empty. If it is not empty, then it shall not be possible to downgrade the peripheral device firmware to an older version.
1.3.6.1.4.1.13742.6.3.6.5.1.6DisplayStringread-onlycurrent
peripheralDevicePackageFirmwareTimeStamp
OBJECT-TYPE
The time when the peripheral device package firmware was last updated. It is measured in seconds since January 1, 1970 (midnight UTC/GMT).
1.3.6.1.4.1.13742.6.3.6.5.1.7Unsigned32read-onlycurrent
peripheralDevicePackagePosition
OBJECT-TYPE
The position of the package in the bus topology. The format is a semicolon separated list of Keyword:value pairs. Keyword can be one of the following: ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION Examples: 1) Onboard Sensor ONBOARD:CC1 2) Old sensor connected to device 1-wire port DEVICE-1WIREPORT:2 3) New-style sensor connected to device 1-wire port DEVICE-1WIREPORT:2;CHAIN-POSITION:3 4) New-style sensor connected to hub port 3 DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1 5) Old-style sensor connected to end of new-style sensor chain DEVICE-1WIREPORT:2;
1.3.6.1.4.1.13742.6.3.6.5.1.8DisplayStringread-onlycurrent
peripheralDevicePackageState
OBJECT-TYPE
The state of the package.
1.3.6.1.4.1.13742.6.3.6.5.1.9DisplayStringread-onlycurrent
serverReachability
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.7
serverReachabilityTable
OBJECT-TYPE
A list of server entries. The number of entries is given by the value of serverCount for the PDU.
1.3.6.1.4.1.13742.6.3.7.3not-accessiblecurrent
serverReachabilityEntry
OBJECT-TYPE
An entry containing parameters for a server.
1.3.6.1.4.1.13742.6.3.7.3.1not-accessiblecurrent
serverID
OBJECT-TYPE
A unique value for each server. Its value ranges between 1 and the value of serverCount for that PDU
1.3.6.1.4.1.13742.6.3.7.3.1.1Integer32 (1..256)not-accessiblecurrent
serverIPAddress
OBJECT-TYPE
The IP Address/host name of the server
1.3.6.1.4.1.13742.6.3.7.3.1.3DisplayStringread-onlycurrent
serverPingEnabled
OBJECT-TYPE
Is ping enabled for this server?
1.3.6.1.4.1.13742.6.3.7.3.1.4TruthValueread-writecurrent
wires
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.8
wireConfigurationTable
OBJECT-TYPE
A list of wire configuration entries. The number of entries is given by the value of wireCount for the PDU. Note: This feature is no longer used, the table is always empty.
1.3.6.1.4.1.13742.6.3.8.3not-accessibledeprecated
wireConfigurationEntry
OBJECT-TYPE
An entry containing objects for a particular wire.
1.3.6.1.4.1.13742.6.3.8.3.1not-accessibledeprecated
wireId
OBJECT-TYPE
A unique value for each wire. Its value ranges between 1 and the value of wireCount.
1.3.6.1.4.1.13742.6.3.8.3.1.1Integer32 (1..256)not-accessibledeprecated
wireLabel
OBJECT-TYPE
The label on the PDU identifying the wire.
1.3.6.1.4.1.13742.6.3.8.3.1.2DisplayStringread-onlydeprecated
wireCapabilities
OBJECT-TYPE
A bit string indicating which wire sensors are available.
1.3.6.1.4.1.13742.6.3.8.3.1.3Bits {rmsCurrent(0), peakCurrent(1), unbalancedCurrent(2), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8)}read-onlydeprecated
wirePowerSource
OBJECT-TYPE
This object allows discovery of how the PDU is wired. It indicates the wire's power source which can one of the following: - an inlet - an overcurrent protector - a transfer switch If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet tables. If the power source is an overcurrent protector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfigurationTable. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. If the power source is a transfer switch, it contains the OID of a transferSwitchLabel in the transferSwitchConfigurationTable. The indices of the OID can then be used to reference other objects in the transfer switch tables.
1.3.6.1.4.1.13742.6.3.8.3.1.4RowPointerread-onlydeprecated
wireSensorConfigurationTable
OBJECT-TYPE
A list of wire sensor configuration entries. Note: This feature is no longer used, the table is always empty.
1.3.6.1.4.1.13742.6.3.8.4not-accessibledeprecated
wireSensorConfigurationEntry
OBJECT-TYPE
An wireSensor entry containing objects for a particular wire Sensor.
1.3.6.1.4.1.13742.6.3.8.4.1not-accessibledeprecated
wireSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.8.4.1.4TruthValueread-writedeprecated
wireSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.6SensorUnitsEnumerationread-onlydeprecated
wireSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.7Unsigned32read-onlydeprecated
wireSensorAccuracy
OBJECT-TYPE
The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.8HundredthsOfAPercentageread-onlydeprecated
wireSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.9Unsigned32read-onlydeprecated
wireSensorTolerance
OBJECT-TYPE
The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (wireSensorDecimalDigits + 1). For example, if the value is 50 and wireSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.10Unsigned32read-onlydeprecated
wireSensorMaximum
OBJECT-TYPE
The largest possible value The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.11Unsigned32read-onlydeprecated
wireSensorMinimum
OBJECT-TYPE
The smallest possible value The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.12Unsigned32read-onlydeprecated
wireSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.13Unsigned32read-writedeprecated
wireSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.14Unsigned32read-writedeprecated
wireSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.21Unsigned32read-writedeprecated
wireSensorLowerWarningThreshold
OBJECT-TYPE
The lower non-critical (warning) threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.22Unsigned32read-writedeprecated
wireSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.23Unsigned32read-writedeprecated
wireSensorUpperWarningThreshold
OBJECT-TYPE
The upper non-critical (warning) threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.24Unsigned32read-writedeprecated
wireSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writedeprecated
transferSwitch
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.9
transferSwitchConfigurationTable
OBJECT-TYPE
A list of transfer switch configuration entries. The number of entries is given by the value of transferSwitchCount.
1.3.6.1.4.1.13742.6.3.9.3not-accessiblecurrent
transferSwitchConfigurationEntry
OBJECT-TYPE
An entry containing objects for a particular transfer switch.
1.3.6.1.4.1.13742.6.3.9.3.1not-accessiblecurrent
transferSwitchId
OBJECT-TYPE
A unique value for each transfer switch. Its value ranges between 1 and the value of transferSwitchCount.
1.3.6.1.4.1.13742.6.3.9.3.1.1Integer32 (1..256)not-accessiblecurrent
transferSwitchLabel
OBJECT-TYPE
The label on the PDU identifying the transfer switch.
1.3.6.1.4.1.13742.6.3.9.3.1.2DisplayStringread-onlycurrent
transferSwitchName
OBJECT-TYPE
The user-defined name of the transfer switch.
1.3.6.1.4.1.13742.6.3.9.3.1.3DisplayStringread-writecurrent
transferSwitchPreferredInlet
OBJECT-TYPE
The preferred inlet. This is the inlet to be selected in case both inlets have acceptable power.
1.3.6.1.4.1.13742.6.3.9.3.1.4Integer32 (1..64)read-onlycurrent
transferSwitchPoleCount
OBJECT-TYPE
The number of poles.
1.3.6.1.4.1.13742.6.3.9.3.1.5Integer32 (2..4)read-onlycurrent
transferSwitchAutoReTransferEnabled
OBJECT-TYPE
Enables or disables automatic retransfer from the standby inlet to the preferred inlet after power has been restored.
1.3.6.1.4.1.13742.6.3.9.3.1.20TruthValueread-writecurrent
transferSwitchAutoReTransferWaitTime
OBJECT-TYPE
The delay for automatic retransfers. Retransfer occurs this many seconds after the condition causing the original transfer has been corrected.
1.3.6.1.4.1.13742.6.3.9.3.1.21Unsigned32read-writecurrent
transferSwitchAutoReTransferRequiresPhaseSync
OBJECT-TYPE
Enables or disables automatic retransfer in case the two inlets are not synchronized. If set to True, automatic retransfer is inhibited while a phase sync alarm is present, i.e. the phase difference between the two inlets is too large.
1.3.6.1.4.1.13742.6.3.9.3.1.22TruthValueread-writecurrent
transferSwitchFrontPanelManualTransferButtonEnabled
OBJECT-TYPE
Enables or disables the Manual Transfer button on the unit's front panel.
1.3.6.1.4.1.13742.6.3.9.3.1.23TruthValueread-writecurrent
transferSwitchCapabilities
OBJECT-TYPE
A bit string indicating which sensors are available for the transfer switch.
1.3.6.1.4.1.13742.6.3.9.3.1.24Bits {overloadStatus(32), inletPhaseSyncAngle(37), inletPhaseSync(38), operatingState(39), activeInlet(40), switchStatus(47)}read-onlycurrent
transferSwitchPowerSource1
OBJECT-TYPE
This object allows discovery of how the PDU is wired. It indicates the transfer switch's first power source, typically a fuse. It contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfiguration Table. The indices of the OID can then be used to reference other objects in the overcurrent protector tables.
1.3.6.1.4.1.13742.6.3.9.3.1.31RowPointerread-onlycurrent
transferSwitchPowerSource2
OBJECT-TYPE
This object allows discovery of how the PDU is wired. It indicates the transfer switch's second power source, typically a fuse. It contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfiguration Table. The indices of the OID can then be used to reference other objects in the overcurrent protector tables.
1.3.6.1.4.1.13742.6.3.9.3.1.32RowPointerread-onlycurrent
transferSwitchSensorConfigurationTable
OBJECT-TYPE
A list of transfer switch sensor configuration entries.
1.3.6.1.4.1.13742.6.3.9.4not-accessiblecurrent
transferSwitchSensorConfigurationEntry
OBJECT-TYPE
An entry containing parameters for a transfer switch sensor.
1.3.6.1.4.1.13742.6.3.9.4.1not-accessiblecurrent
transferSwitchSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.9.4.1.4TruthValueread-writecurrent
transferSwitchSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.6SensorUnitsEnumerationread-onlycurrent
transferSwitchSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.7Unsigned32read-onlycurrent
transferSwitchSensorAccuracy
OBJECT-TYPE
The accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.8HundredthsOfAPercentageread-onlydeprecated
transferSwitchSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.9Unsigned32read-onlycurrent
transferSwitchSensorTolerance
OBJECT-TYPE
The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (transferSwitchSensorDecimalDigits + 1). For example, if the value is 50 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.10Unsigned32read-onlydeprecated
transferSwitchSensorMaximum
OBJECT-TYPE
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.11Unsigned32read-onlycurrent
transferSwitchSensorMinimum
OBJECT-TYPE
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.12Unsigned32read-onlycurrent
transferSwitchSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.13Unsigned32read-writecurrent
transferSwitchSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.14Unsigned32read-writecurrent
transferSwitchSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.21Unsigned32read-writecurrent
transferSwitchSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.22Unsigned32read-writecurrent
transferSwitchSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.23Unsigned32read-writecurrent
transferSwitchSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.24Unsigned32read-writecurrent
transferSwitchSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
transferSwitchSensorSignedMaximum
OBJECT-TYPE
The largest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.26Integer32read-onlycurrent
transferSwitchSensorSignedMinimum
OBJECT-TYPE
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.27Integer32read-onlycurrent
transferSwitchSensorSignedLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.28Integer32read-writecurrent
transferSwitchSensorSignedLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.29Integer32read-writecurrent
transferSwitchSensorSignedUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.30Integer32read-writecurrent
transferSwitchSensorSignedUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.31Integer32read-writecurrent
transferSwitchPoleConfigurationTable
OBJECT-TYPE
A list of transfer switch pole configuration entries. The number of entries is given by the value of transferSwitchPoleCount.
1.3.6.1.4.1.13742.6.3.9.5not-accessiblecurrent
transferSwitchPoleConfigurationEntry
OBJECT-TYPE
An entry containing parameters for a particular transfer switch pole.
1.3.6.1.4.1.13742.6.3.9.5.1not-accessiblecurrent
transferSwitchPoleIndex
OBJECT-TYPE
A unique value for each transfer switch pole. Its value ranges between 1 and the value of transferSwitchPoleCount.
1.3.6.1.4.1.13742.6.3.9.5.1.1Integer32 (1..256)not-accessiblecurrent
transferSwitchPoleLine
OBJECT-TYPE
The phase for this transfer switch pole.
1.3.6.1.4.1.13742.6.3.9.5.1.2LineEnumerationread-onlycurrent
transferSwitchPoleIn1Node
OBJECT-TYPE
The node to which this transfer switch pole input 1 is connected
1.3.6.1.4.1.13742.6.3.9.5.1.3Integer32read-onlycurrent
transferSwitchPoleIn2Node
OBJECT-TYPE
The node to which this transfer switch pole input 2 is connected
1.3.6.1.4.1.13742.6.3.9.5.1.4Integer32read-onlycurrent
transferSwitchPoleOutNode
OBJECT-TYPE
The node to which this transfer switch pole output is connected
1.3.6.1.4.1.13742.6.3.9.5.1.5Integer32read-onlycurrent
powerMeter
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.10
powerMeterConfigurationTable
OBJECT-TYPE
A list of power meter and panel configuration entries. Note: Also see inlet tables for settings and sensor information.
1.3.6.1.4.1.13742.6.3.10.2not-accessiblecurrent
powerMeterConfigurationEntry
OBJECT-TYPE
An entry containing configuration objects for power meters and panels.
1.3.6.1.4.1.13742.6.3.10.2.1not-accessiblecurrent
powerMeterPhaseCTRating
OBJECT-TYPE
The rating of the phase CT in Amps, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.10.2.1.2Unsigned32read-writecurrent
powerMeterNeutralCTRating
OBJECT-TYPE
The rating of the neutral CT in Amps, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.10.2.1.3Unsigned32read-writecurrent
powerMeterEarthCTRating
OBJECT-TYPE
The rating of the earth CT in Amps, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.10.2.1.4Unsigned32read-writecurrent
powerMeterBranchCount
OBJECT-TYPE
The maximum number of circuits supported by the panel. This can be used to distinguish between panels (>0) and power meters (0). See circuitCount for the number of currently defined circuits.
1.3.6.1.4.1.13742.6.3.10.2.1.5Unsigned32read-onlycurrent
powerMeterPanelPositions
OBJECT-TYPE
The number of circuit positions in the panel. Its value is specified by the user when configuring a panel
1.3.6.1.4.1.13742.6.3.10.2.1.6Integer32 (1..256)read-onlycurrent
powerMeterPanelLayout
OBJECT-TYPE
The panel circuit position layout: one or two columns. This is valid only for panels, the value is -1 for power meters.
1.3.6.1.4.1.13742.6.3.10.2.1.7PanelLayoutEnumerationread-onlycurrent
powerMeterPanelNumbering
OBJECT-TYPE
The panel circuit position numbering scheme: odd/even or sequential. This is valid only for panels, the value is -1 for power meters.
1.3.6.1.4.1.13742.6.3.10.2.1.8PanelNumberingEnumerationread-onlycurrent
powerMeterType
OBJECT-TYPE
The power meter type: 3-phase, single-phase or split-phase.
1.3.6.1.4.1.13742.6.3.10.2.1.9PowerMeterTypeEnumerationread-onlycurrent
circuit
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.3.11
circuitConfigurationTable
OBJECT-TYPE
A list of circuit configuration entries. The number of entries is given by the value of panelCircuitPositionCount.
1.3.6.1.4.1.13742.6.3.11.2not-accessiblecurrent
circuitConfigurationEntry
OBJECT-TYPE
An entry containing configuration objects for the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1not-accessiblecurrent
circuitId
OBJECT-TYPE
A unique value for each circuit. Its value is the smallest panel position occupied by the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.1Integer32 (1..1024)not-accessiblecurrent
circuitPoleCount
OBJECT-TYPE
The number of panel positions occupied by the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.2Integer32 (1..256)read-onlycurrent
circuitName
OBJECT-TYPE
The user-defined name for the circuit. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.2.1.3DisplayStringread-writecurrent
circuitType
OBJECT-TYPE
The circuit type: line-line, line-neutral, line-line-neutral or 3-phase
1.3.6.1.4.1.13742.6.3.11.2.1.4CircuitTypeEnumerationread-onlycurrent
circuitRatedCurrent
OBJECT-TYPE
The rating of the breaker for the circuit in Amps. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.2.1.5Unsigned32read-writecurrent
circuitCTRating
OBJECT-TYPE
The rating of the CTs metering this circuit in Amps. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.2.1.6Unsigned32read-writecurrent
circuitCapabilities
OBJECT-TYPE
A bit string indicating which sensors are available for the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.7Bits {rmsCurrent(0), peakCurrent(1), unbalancedCurrent(2), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), surgeProtectorStatus(21), frequency(22), phaseAngle(23), residualCurrent(25), rcmState(26), reactivePower(28), powerQuality(31), displacementPowerFactor(34)}read-onlycurrent
circuitPoleCapabilities
OBJECT-TYPE
A bit string indicating which sensors are available for each circuit pole.
1.3.6.1.4.1.13742.6.3.11.2.1.8Bits {rmsCurrent(0), peakCurrent(1), rmsVoltage(3), activePower(4), apparentPower(5), powerFactor(6), activeEnergy(7), apparentEnergy(8), phaseAngle(23), rmsVoltageLN(24), reactivePower(28), displacementPowerFactor(34)}read-onlycurrent
circuitPowerSource
OBJECT-TYPE
This object allows discovery of how the circuit is wired. It indicates the circuit's power source, typically an inlet. It contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet and power meter tables.
1.3.6.1.4.1.13742.6.3.11.2.1.9RowPointerread-onlycurrent
circuitPoleConfigurationTable
OBJECT-TYPE
A list of branch circuit pole configuration entries. The number of entries is given by the value of circuitPoleCount for the circuit.
1.3.6.1.4.1.13742.6.3.11.3not-accessiblecurrent
circuitPoleConfigurationEntry
OBJECT-TYPE
An entry containing configuration objects for the circuit poles.
1.3.6.1.4.1.13742.6.3.11.3.1not-accessiblecurrent
circuitPoleId
OBJECT-TYPE
A unique value for each circuit pole. Its value ranges between 1 and the value of circuitPoleCount.
1.3.6.1.4.1.13742.6.3.11.3.1.1Integer32 (1..256)not-accessiblecurrent
circuitPolePanelPosition
OBJECT-TYPE
The panel position for this pole.
1.3.6.1.4.1.13742.6.3.11.3.1.2Integer32 (1..256)read-onlycurrent
circuitPoleCTNumber
OBJECT-TYPE
The CT number for this circuit pole, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.3.1.3Integer32 (0..256)read-writecurrent
circuitPolePhase
OBJECT-TYPE
The phase for this circuit pole. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.3.1.4PhaseEnumerationread-writecurrent
circuitSensorConfigurationTable
OBJECT-TYPE
A list of configuration entries for branch circuit sensor.
1.3.6.1.4.1.13742.6.3.11.4not-accessiblecurrent
circuitSensorConfigurationEntry
OBJECT-TYPE
An entry containing objects for configuring a branch circuit sensor.
1.3.6.1.4.1.13742.6.3.11.4.1not-accessiblecurrent
circuitSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.11.4.1.4TruthValueread-writecurrent
circuitSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.6SensorUnitsEnumerationread-onlycurrent
circuitSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.7Unsigned32read-onlycurrent
circuitSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.9Unsigned32read-onlycurrent
circuitSensorMaximum
OBJECT-TYPE
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.11Unsigned32read-onlycurrent
circuitSensorMinimum
OBJECT-TYPE
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.12Unsigned32read-onlycurrent
circuitSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.13Unsigned32read-writecurrent
circuitSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.14Unsigned32read-writecurrent
circuitSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.21Unsigned32read-writecurrent
circuitSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.22Unsigned32read-writecurrent
circuitSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.23Unsigned32read-writecurrent
circuitSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.24Unsigned32read-writecurrent
circuitSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
circuitSensorSignedMaximum
OBJECT-TYPE
The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.26Integer32read-onlycurrent
circuitSensorSignedMinimum
OBJECT-TYPE
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.27Integer32read-onlycurrent
circuitSensorSignedLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.28Integer32read-writecurrent
circuitSensorSignedLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.29Integer32read-writecurrent
circuitSensorSignedUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.30Integer32read-writecurrent
circuitSensorSignedUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.31Integer32read-writecurrent
circuitPoleSensorConfigurationTable
OBJECT-TYPE
A list of configuration entries for a circuit's pole sensors.
1.3.6.1.4.1.13742.6.3.11.6not-accessiblecurrent
circuitPoleSensorConfigurationEntry
OBJECT-TYPE
An entry containing objects for configuring a circuit pole sensor.
1.3.6.1.4.1.13742.6.3.11.6.1not-accessiblecurrent
circuitPoleSensorLogAvailable
OBJECT-TYPE
Is data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.11.6.1.4TruthValueread-writecurrent
circuitPoleSensorUnits
OBJECT-TYPE
The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.6SensorUnitsEnumerationread-onlycurrent
circuitPoleSensorDecimalDigits
OBJECT-TYPE
The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.7Unsigned32read-onlycurrent
circuitPoleSensorResolution
OBJECT-TYPE
The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.9Unsigned32read-onlycurrent
circuitPoleSensorMaximum
OBJECT-TYPE
The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.11Unsigned32read-onlycurrent
circuitPoleSensorMinimum
OBJECT-TYPE
The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.12Unsigned32read-onlycurrent
circuitPoleSensorHysteresis
OBJECT-TYPE
The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.13Unsigned32read-writecurrent
circuitPoleSensorStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.14Unsigned32read-writecurrent
circuitPoleSensorLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.21Unsigned32read-writecurrent
circuitPoleSensorLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.22Unsigned32read-writecurrent
circuitPoleSensorUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.23Unsigned32read-writecurrent
circuitPoleSensorUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.24Unsigned32read-writecurrent
circuitPoleSensorEnabledThresholds
OBJECT-TYPE
A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.25Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
circuitPoleSensorSignedMaximum
OBJECT-TYPE
The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.26Integer32read-onlycurrent
circuitPoleSensorSignedMinimum
OBJECT-TYPE
The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.27Integer32read-onlycurrent
circuitPoleSensorSignedLowerCriticalThreshold
OBJECT-TYPE
The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.28Integer32read-writecurrent
circuitPoleSensorSignedLowerWarningThreshold
OBJECT-TYPE
The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.29Integer32read-writecurrent
circuitPoleSensorSignedUpperCriticalThreshold
OBJECT-TYPE
The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.30Integer32read-writecurrent
circuitPoleSensorSignedUpperWarningThreshold
OBJECT-TYPE
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.31Integer32read-writecurrent
control
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4
outletControl
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4.1
outletSwitchControlTable
OBJECT-TYPE
A list of outlets for a PDU. The number of entries is given by the value of outletCount.
1.3.6.1.4.1.13742.6.4.1.2not-accessiblecurrent
outletSwitchControlEntry
OBJECT-TYPE
An entry for implementing switching operations on an outlet.
1.3.6.1.4.1.13742.6.4.1.2.1not-accessiblecurrent
switchingOperation
OBJECT-TYPE
The switching operation: switch on, switch off or power-cycle.
1.3.6.1.4.1.13742.6.4.1.2.1.2OutletSwitchingOperationsEnumerationread-writecurrent
outletSwitchingState
OBJECT-TYPE
The outlet state at present
1.3.6.1.4.1.13742.6.4.1.2.1.3SensorStateEnumerationread-onlycurrent
outletSwitchingTimeStamp
OBJECT-TYPE
The timestamp indicating when the outlet was last switched
1.3.6.1.4.1.13742.6.4.1.2.1.4Unsigned32read-onlycurrent
externalSensorControl
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4.2
transferSwitchControl
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4.3
transferSwitchControlTable
OBJECT-TYPE
A list of transfer switches for a PDU. The number of entries is given by the value of transferSwitchCount.
1.3.6.1.4.1.13742.6.4.3.1not-accessiblecurrent
transferSwitchControlEntry
OBJECT-TYPE
An entry for implementing switching operations on a transfer switch.
1.3.6.1.4.1.13742.6.4.3.1.1not-accessiblecurrent
transferSwitchActiveInlet
OBJECT-TYPE
The index of the currently active inlet.
1.3.6.1.4.1.13742.6.4.3.1.1.1Integer32 (1..64)read-onlycurrent
transferSwitchTransferToInlet
OBJECT-TYPE
Select the active inlet. If the new inlet is available, it will become both active and preferred, otherwise an inconsistentValue error will be returned. By default the switching operation will fail if the phase difference between the inlets is too large. In this case the switch can be forced by writing transferSwitchAlarmOverride as True in the same request. This variable will always read as 0.
1.3.6.1.4.1.13742.6.4.3.1.1.2Integer32 (1..64)read-writecurrent
transferSwitchAlarmOverride
OBJECT-TYPE
Force transfer even if the phase difference between the inlets is too large. This may only be written together with transferSwitchTransferToInlet, otherwise an inconsistentValue error will be returned. Always reads as false.
1.3.6.1.4.1.13742.6.4.3.1.1.3TruthValueread-writecurrent
transferSwitchLastTransferReason
OBJECT-TYPE
The reason for the most recent transfer
1.3.6.1.4.1.13742.6.4.3.1.1.4TransferSwitchTransferReasonEnumerationread-onlycurrent
actuatorControl
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4.4
actuatorControlTable
OBJECT-TYPE
A list of actuators for a PDU.
1.3.6.1.4.1.13742.6.4.4.2not-accessiblecurrent
actuatorControlEntry
OBJECT-TYPE
An entry for implementing user-initiated state changes for an actuator.
1.3.6.1.4.1.13742.6.4.4.2.1not-accessiblecurrent
actuatorState
OBJECT-TYPE
The actuator state. A get operation retrieves the state of the actuator. A set operation changes the state of the sensor. The valid states for set operations are on(7) and off(8). Attempting to set the state to any other value will generate an error.
1.3.6.1.4.1.13742.6.4.4.2.1.2SensorStateEnumerationread-writecurrent
rcmControl
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4.5
rcmSelfTestTable
OBJECT-TYPE
A list of RCMs.
1.3.6.1.4.1.13742.6.4.5.2not-accessiblecurrent
rcmSelfTestEntry
OBJECT-TYPE
An entry for initiating the self test of an RCM.
1.3.6.1.4.1.13742.6.4.5.2.1not-accessiblecurrent
rcmState
OBJECT-TYPE
The rcm state. A Get operation retrieves the state of the RCM State Sensor. A Set operation changes the state of the sensor. The only valid state for set operations is selfTest(29). When rcmState is set to selfTest, self test of the RCM starts. Attempting to set the state to any other value will generate an error. If the current state is selfTest, then an attempt to set the value to selfTest will be ignored.
1.3.6.1.4.1.13742.6.4.5.2.1.2SensorStateEnumerationread-writecurrent
inletSensorControl
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4.6
inletSensorControlTable
OBJECT-TYPE
A list of control entries for the inlet sensors of a PDU. The set of valid indices is defined by the value of inletCount and the inletDeviceCapabilities entry for the selected inlet.
1.3.6.1.4.1.13742.6.4.6.1not-accessiblecurrent
inletSensorControlEntry
OBJECT-TYPE
An entry used for controlling an inlet sensor.
1.3.6.1.4.1.13742.6.4.6.1.1not-accessiblecurrent
inletSensorResetValue
OBJECT-TYPE
Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0.
1.3.6.1.4.1.13742.6.4.6.1.1.1Integer32read-writecurrent
outletSensorControl
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4.7
outletSensorControlTable
OBJECT-TYPE
A list of control entries for the outlet sensors of a PDU. The set of valid indices is defined by the value of outletCount and the outletDeviceCapabilities entry for the selected outlet.
1.3.6.1.4.1.13742.6.4.7.1not-accessiblecurrent
outletSensorControlEntry
OBJECT-TYPE
An entry used for controlling an outlet sensor.
1.3.6.1.4.1.13742.6.4.7.1.1not-accessiblecurrent
outletSensorResetValue
OBJECT-TYPE
Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0.
1.3.6.1.4.1.13742.6.4.7.1.1.1Integer32read-writecurrent
unitSensorControl
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4.8
unitSensorControlTable
OBJECT-TYPE
A list of control entries for the global sensors of a PDU. The set of valid indices is defined by the value of pduCount and the pduDeviceCapabilities entry.
1.3.6.1.4.1.13742.6.4.8.1not-accessiblecurrent
unitSensorControlEntry
OBJECT-TYPE
An entry used for controlling an global sensor.
1.3.6.1.4.1.13742.6.4.8.1.1not-accessiblecurrent
unitSensorResetValue
OBJECT-TYPE
Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0. This object applies only to multi-inlet PDUs.
1.3.6.1.4.1.13742.6.4.8.1.1.1Integer32read-writecurrent
circuitSensorControl
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.4.9
circuitSensorControlTable
OBJECT-TYPE
A list of control entries for the circuit sensors of a BCM2. The maximum number of entries is given by the value of panelCircuitPositionCount.
1.3.6.1.4.1.13742.6.4.9.1not-accessiblecurrent
circuitSensorControlEntry
OBJECT-TYPE
An entry used for controlling an circuit sensor.
1.3.6.1.4.1.13742.6.4.9.1.1not-accessiblecurrent
circuitSensorResetValue
OBJECT-TYPE
Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0.
1.3.6.1.4.1.13742.6.4.9.1.1.1Integer32read-writecurrent
measurements
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.5
measurementsUnit
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.5.1
unitSensorMeasurementsTable
OBJECT-TYPE
A list of unit sensor entries.
1.3.6.1.4.1.13742.6.5.1.3not-accessiblecurrent
unitSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for an unit sensor.
1.3.6.1.4.1.13742.6.5.1.3.1not-accessiblecurrent
measurementsUnitSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.1.3.1.2TruthValueread-onlycurrent
measurementsUnitSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.1.3.1.3SensorStateEnumerationread-onlycurrent
measurementsUnitSensorValue
OBJECT-TYPE
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.1.3.1.4Unsigned32read-onlycurrent
measurementsUnitSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.1.3.1.5Unsigned32read-onlycurrent
measurementsUnitSensorSignedValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.1.3.1.6Integer32read-onlycurrent
measurementsInlet
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.5.2
inletSensorMeasurementsTable
OBJECT-TYPE
A list of inlet sensor entries.
1.3.6.1.4.1.13742.6.5.2.3not-accessiblecurrent
inletSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for an inlet sensor.
1.3.6.1.4.1.13742.6.5.2.3.1not-accessiblecurrent
measurementsInletSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.2.3.1.2TruthValueread-onlycurrent
measurementsInletSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.2.3.1.3SensorStateEnumerationread-onlycurrent
measurementsInletSensorValue
OBJECT-TYPE
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.2.3.1.4Unsigned32read-onlycurrent
measurementsInletSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.2.3.1.5Unsigned32read-onlycurrent
measurementsInletSensorSignedValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.2.3.1.6Integer32read-onlycurrent
inletPoleSensorMeasurementsTable
OBJECT-TYPE
A list of inlet pole sensor entries.
1.3.6.1.4.1.13742.6.5.2.4not-accessiblecurrent
inletPoleSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for an inlet pole sensor.
1.3.6.1.4.1.13742.6.5.2.4.1not-accessiblecurrent
measurementsInletPoleSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.2.4.1.2TruthValueread-onlycurrent
measurementsInletPoleSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.2.4.1.3SensorStateEnumerationread-onlycurrent
measurementsInletPoleSensorValue
OBJECT-TYPE
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.2.4.1.4Unsigned32read-onlycurrent
measurementsInletPoleSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.2.4.1.5Unsigned32read-onlycurrent
measurementsInletPoleSensorSignedValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.2.4.1.6Integer32read-onlycurrent
measurementsOverCurrentProtector
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.5.3
overCurrentProtectorSensorMeasurementsTable
OBJECT-TYPE
A list of overcurrent protector sensor entries.
1.3.6.1.4.1.13742.6.5.3.3not-accessiblecurrent
overCurrentProtectorSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for an overcurrent protector sensor.
1.3.6.1.4.1.13742.6.5.3.3.1not-accessiblecurrent
measurementsOverCurrentProtectorSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.3.3.1.2TruthValueread-onlycurrent
measurementsOverCurrentProtectorSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.3.3.1.3SensorStateEnumerationread-onlycurrent
measurementsOverCurrentProtectorSensorValue
OBJECT-TYPE
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.3.3.1.4Unsigned32read-onlycurrent
measurementsOverCurrentProtectorSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.3.3.1.5Unsigned32read-onlycurrent
measurementsOverCurrentProtectorSensorSignedValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.3.3.1.6Integer32read-onlycurrent
measurementsOutlet
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.5.4
outletSensorMeasurementsTable
OBJECT-TYPE
A list of outlet sensor entries.
1.3.6.1.4.1.13742.6.5.4.3not-accessiblecurrent
outletSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for an outlet sensor.
1.3.6.1.4.1.13742.6.5.4.3.1not-accessiblecurrent
measurementsOutletSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.4.3.1.2TruthValueread-onlycurrent
measurementsOutletSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.4.3.1.3SensorStateEnumerationread-onlycurrent
measurementsOutletSensorValue
OBJECT-TYPE
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.4.3.1.4Unsigned32read-onlycurrent
measurementsOutletSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.4.3.1.5Unsigned32read-onlycurrent
measurementsOutletSensorSignedValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.4.3.1.6Integer32read-onlycurrent
outletPoleSensorMeasurementsTable
OBJECT-TYPE
A list of outlet pole sensor entries.
1.3.6.1.4.1.13742.6.5.4.4not-accessiblecurrent
outletPoleSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for an outlet pole sensor.
1.3.6.1.4.1.13742.6.5.4.4.1not-accessiblecurrent
measurementsOutletPoleSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.4.4.1.2TruthValueread-onlycurrent
measurementsOutletPoleSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.4.4.1.3SensorStateEnumerationread-onlycurrent
measurementsOutletPoleSensorValue
OBJECT-TYPE
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.4.4.1.4Unsigned32read-onlycurrent
measurementsOutletPoleSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.4.4.1.5Unsigned32read-onlycurrent
measurementsOutletPoleSensorSignedValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.4.4.1.6Integer32read-onlycurrent
measurementsExternalSensor
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.5.5
externalSensorMeasurementsTable
OBJECT-TYPE
A list of external sensor entries. The number of entries is given by the value of externalSensorCount for the PDU.
1.3.6.1.4.1.13742.6.5.5.3not-accessiblecurrent
externalSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for an external sensor.
1.3.6.1.4.1.13742.6.5.5.3.1not-accessiblecurrent
measurementsExternalSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.5.3.1.2TruthValueread-onlycurrent
measurementsExternalSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.5.3.1.3SensorStateEnumerationread-onlycurrent
measurementsExternalSensorValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.5.3.1.4Integer32read-onlycurrent
measurementsExternalSensorTimeStamp
OBJECT-TYPE
The sensor reading timestamp.
1.3.6.1.4.1.13742.6.5.5.3.1.5Unsigned32read-onlycurrent
measurementsWire
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.5.6
wireSensorMeasurementsTable
OBJECT-TYPE
A list of wire sensor entries. Note: This feature is no longer used, the table is always empty.
1.3.6.1.4.1.13742.6.5.6.3not-accessibledeprecated
wireSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for a wire.
1.3.6.1.4.1.13742.6.5.6.3.1not-accessibledeprecated
measurementsWireSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.6.3.1.2TruthValueread-onlydeprecated
measurementsWireSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.6.3.1.3SensorStateEnumerationread-onlydeprecated
measurementsWireSensorValue
OBJECT-TYPE
The sensor value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the value exceeds 4294967295 This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.6.3.1.4Unsigned32read-onlydeprecated
measurementsWireSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.6.3.1.5Unsigned32read-onlydeprecated
measurementsTransferSwitch
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.5.7
transferSwitchSensorMeasurementsTable
OBJECT-TYPE
A list of transfer switch sensor entries.
1.3.6.1.4.1.13742.6.5.7.3not-accessiblecurrent
transferSwitchSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for a transfer switch sensor.
1.3.6.1.4.1.13742.6.5.7.3.1not-accessiblecurrent
measurementsTransferSwitchSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.7.3.1.2TruthValueread-onlycurrent
measurementsTransferSwitchSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.7.3.1.3SensorStateEnumerationread-onlycurrent
measurementsTransferSwitchSensorValue
OBJECT-TYPE
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.7.3.1.4Unsigned32read-onlycurrent
measurementsTransferSwitchSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.7.3.1.5Unsigned32read-onlycurrent
measurementsTransferSwitchSensorSignedValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.7.3.1.6Integer32read-onlycurrent
measurementsCircuit
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.5.8
circuitSensorMeasurementsTable
OBJECT-TYPE
A list of circuit sensor entries.
1.3.6.1.4.1.13742.6.5.8.3not-accessiblecurrent
circuitSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for a circuit sensor.
1.3.6.1.4.1.13742.6.5.8.3.1not-accessiblecurrent
measurementsCircuitSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.8.3.1.2TruthValueread-onlycurrent
measurementsCircuitSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.8.3.1.3SensorStateEnumerationread-onlycurrent
measurementsCircuitSensorValue
OBJECT-TYPE
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.8.3.1.4Unsigned32read-onlycurrent
measurementsCircuitSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.8.3.1.5Unsigned32read-onlycurrent
measurementsCircuitSensorSignedValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.8.3.1.6Integer32read-onlycurrent
circuitPoleSensorMeasurementsTable
OBJECT-TYPE
A list of panel circuit pole sensor entries.
1.3.6.1.4.1.13742.6.5.8.4not-accessiblecurrent
circuitPoleSensorMeasurementsEntry
OBJECT-TYPE
An entry containing measurement objects for a circuit pole sensor.
1.3.6.1.4.1.13742.6.5.8.4.1not-accessiblecurrent
measurementsCircuitPoleSensorIsAvailable
OBJECT-TYPE
Is the sensor available?
1.3.6.1.4.1.13742.6.5.8.4.1.2TruthValueread-onlycurrent
measurementsCircuitPoleSensorState
OBJECT-TYPE
The sensor state.
1.3.6.1.4.1.13742.6.5.8.4.1.3SensorStateEnumerationread-onlycurrent
measurementsCircuitPoleSensorValue
OBJECT-TYPE
The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.8.4.1.4Unsigned32read-onlycurrent
measurementsCircuitPoleSensorTimeStamp
OBJECT-TYPE
The timestamp.
1.3.6.1.4.1.13742.6.5.8.4.1.5Unsigned32read-onlycurrent
measurementsCircuitPoleSensorSignedValue
OBJECT-TYPE
The sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.5.8.4.1.6Integer32read-onlycurrent
log
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.6
logUnit
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.6.1
logIndexTable
OBJECT-TYPE
A table containing current indices for the data log buffer.
1.3.6.1.4.1.13742.6.6.1.1not-accessiblecurrent
logIndexEntry
OBJECT-TYPE
An entry containing the current indices for a PDU's data log buffer.
1.3.6.1.4.1.13742.6.6.1.1.1not-accessiblecurrent
oldestLogID
OBJECT-TYPE
The index of the oldest data in the buffer for this PDU.
1.3.6.1.4.1.13742.6.6.1.1.1.2Integer32read-onlycurrent
newestLogID
OBJECT-TYPE
The index of the newest data in the buffer for this PDU.
1.3.6.1.4.1.13742.6.6.1.1.1.3Integer32read-onlycurrent
logTimeStampTable
OBJECT-TYPE
A list of entries containing the timestamps of the entries in the log.
1.3.6.1.4.1.13742.6.6.1.2not-accessiblecurrent
logTimeStampEntry
OBJECT-TYPE
An entry containing the timestamp for log entries.
1.3.6.1.4.1.13742.6.6.1.2.1not-accessiblecurrent
logIndex
OBJECT-TYPE
A unique value for each entry in the log. Its value ranges between 1 and the value of logSize.
1.3.6.1.4.1.13742.6.6.1.2.1.1Integer32 (1..256)not-accessiblecurrent
logTimeStamp
OBJECT-TYPE
The time when the data was collected. It is measured in seconds since January 1, 1970 (midnight UTC/GMT).
1.3.6.1.4.1.13742.6.6.1.2.1.2Unsigned32read-onlycurrent
unitSensorLogTable
OBJECT-TYPE
A list of unit sensor entries in the log.
1.3.6.1.4.1.13742.6.6.1.3not-accessiblecurrent
unitSensorLogEntry
OBJECT-TYPE
An entry containing log objects for a unit sensor.
1.3.6.1.4.1.13742.6.6.1.3.1not-accessiblecurrent
logUnitSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.1.3.1.2TruthValueread-onlycurrent
logUnitSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.1.3.1.3SensorStateEnumerationread-onlycurrent
logUnitSensorAvgValue
OBJECT-TYPE
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.1.3.1.4Unsigned32read-onlycurrent
logUnitSensorMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.1.3.1.5Unsigned32read-onlycurrent
logUnitSensorMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.1.3.1.6Unsigned32read-onlycurrent
logUnitSensorSignedAvgValue
OBJECT-TYPE
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.1.3.1.7Integer32read-onlycurrent
logUnitSensorSignedMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.1.3.1.8Integer32read-onlycurrent
logUnitSensorSignedMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.1.3.1.9Integer32read-onlycurrent
logInlet
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.6.2
inletSensorLogTable
OBJECT-TYPE
A list of inlet sensor entries in the log.
1.3.6.1.4.1.13742.6.6.2.3not-accessiblecurrent
inletSensorLogEntry
OBJECT-TYPE
An entry containing log objects for an inlet sensor.
1.3.6.1.4.1.13742.6.6.2.3.1not-accessiblecurrent
logInletSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.2.3.1.2TruthValueread-onlycurrent
logInletSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.2.3.1.3SensorStateEnumerationread-onlycurrent
logInletSensorAvgValue
OBJECT-TYPE
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.3.1.4Unsigned32read-onlycurrent
logInletSensorMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.3.1.5Unsigned32read-onlycurrent
logInletSensorMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.3.1.6Unsigned32read-onlycurrent
logInletSensorSignedAvgValue
OBJECT-TYPE
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.3.1.7Integer32read-onlycurrent
logInletSensorSignedMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.3.1.8Integer32read-onlycurrent
logInletSensorSignedMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.3.1.9Integer32read-onlycurrent
inletPoleSensorLogTable
OBJECT-TYPE
A list of inletPole sensor entries in the log.
1.3.6.1.4.1.13742.6.6.2.4not-accessiblecurrent
inletPoleSensorLogEntry
OBJECT-TYPE
An entry containing log objects for an inlet pole sensor.
1.3.6.1.4.1.13742.6.6.2.4.1not-accessiblecurrent
logInletPoleSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.2.4.1.2TruthValueread-onlycurrent
logInletPoleSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.2.4.1.3SensorStateEnumerationread-onlycurrent
logInletPoleSensorAvgValue
OBJECT-TYPE
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.4.1.4Unsigned32read-onlycurrent
logInletPoleSensorMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.4.1.5Unsigned32read-onlycurrent
logInletPoleSensorMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.4.1.6Unsigned32read-onlycurrent
logInletPoleSensorSignedAvgValue
OBJECT-TYPE
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.4.1.7Integer32read-onlycurrent
logInletPoleSensorSignedMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.4.1.8Integer32read-onlycurrent
logInletPoleSensorSignedMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.2.4.1.9Integer32read-onlycurrent
logOverCurrentProtector
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.6.3
overCurrentProtectorSensorLogTable
OBJECT-TYPE
A list of overcurrent protector sensor entries in the log.
1.3.6.1.4.1.13742.6.6.3.3not-accessiblecurrent
overCurrentProtectorSensorLogEntry
OBJECT-TYPE
An entry containing log objects for an overcurrent protector sensor.
1.3.6.1.4.1.13742.6.6.3.3.1not-accessiblecurrent
logOverCurrentProtectorSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.3.3.1.2TruthValueread-onlycurrent
logOverCurrentProtectorSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.3.3.1.3SensorStateEnumerationread-onlycurrent
logOverCurrentProtectorSensorAvgValue
OBJECT-TYPE
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.3.3.1.4Unsigned32read-onlycurrent
logOverCurrentProtectorSensorMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.3.3.1.5Unsigned32read-onlycurrent
logOverCurrentProtectorSensorMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.3.3.1.6Unsigned32read-onlycurrent
logOverCurrentProtectorSensorSignedAvgValue
OBJECT-TYPE
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.3.3.1.7Integer32read-onlycurrent
logOverCurrentProtectorSensorSignedMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.3.3.1.8Integer32read-onlycurrent
logOverCurrentProtectorSensorSignedMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.3.3.1.9Integer32read-onlycurrent
logOutlet
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.6.4
outletSensorLogTable
OBJECT-TYPE
A list of outlet sensor entries in the log.
1.3.6.1.4.1.13742.6.6.4.3not-accessiblecurrent
outletSensorLogEntry
OBJECT-TYPE
An entry containing log objects for an outlet sensor.
1.3.6.1.4.1.13742.6.6.4.3.1not-accessiblecurrent
logOutletSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.4.3.1.2TruthValueread-onlycurrent
logOutletSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.4.3.1.3SensorStateEnumerationread-onlycurrent
logOutletSensorAvgValue
OBJECT-TYPE
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.3.1.4Unsigned32read-onlycurrent
logOutletSensorMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.3.1.5Unsigned32read-onlycurrent
logOutletSensorMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.3.1.6Unsigned32read-onlycurrent
logOutletSensorSignedAvgValue
OBJECT-TYPE
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.3.1.7Integer32read-onlycurrent
logOutletSensorSignedMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.3.1.8Integer32read-onlycurrent
logOutletSensorSignedMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.3.1.9Integer32read-onlycurrent
outletPoleSensorLogTable
OBJECT-TYPE
A list of outlet pole sensor entries in the log.
1.3.6.1.4.1.13742.6.6.4.4not-accessiblecurrent
outletPoleSensorLogEntry
OBJECT-TYPE
An entry containing log objects for an outlet pole sensor.
1.3.6.1.4.1.13742.6.6.4.4.1not-accessiblecurrent
logOutletPoleSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.4.4.1.2TruthValueread-onlycurrent
logOutletPoleSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.4.4.1.3SensorStateEnumerationread-onlycurrent
logOutletPoleSensorAvgValue
OBJECT-TYPE
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.4.1.4Unsigned32read-onlycurrent
logOutletPoleSensorMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.4.1.5Unsigned32read-onlycurrent
logOutletPoleSensorMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.4.1.6Unsigned32read-onlycurrent
logOutletPoleSensorSignedAvgValue
OBJECT-TYPE
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.4.1.7Integer32read-onlycurrent
logOutletPoleSensorSignedMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.4.1.8Integer32read-onlycurrent
logOutletPoleSensorSignedMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.4.4.1.9Integer32read-onlycurrent
logExternalSensor
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.6.5
externalSensorLogTable
OBJECT-TYPE
A list of external sensor entries in the log.
1.3.6.1.4.1.13742.6.6.5.3not-accessiblecurrent
externalSensorLogEntry
OBJECT-TYPE
An entry containing log objects for an external sensor.
1.3.6.1.4.1.13742.6.6.5.3.1not-accessiblecurrent
logExternalSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.5.3.1.2TruthValueread-onlycurrent
logExternalSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.5.3.1.3SensorStateEnumerationread-onlycurrent
logExternalSensorAvgValue
OBJECT-TYPE
The sensor reading average value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.5.3.1.4Integer32read-onlycurrent
logExternalSensorMaxValue
OBJECT-TYPE
The sensor reading maximum value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.5.3.1.5Integer32read-onlycurrent
logExternalSensorMinValue
OBJECT-TYPE
The sensor reading minimum value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.5.3.1.6Integer32read-onlycurrent
logWire
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.6.6
wireSensorLogTable
OBJECT-TYPE
A list of wire sensor entries in the log. Note: This feature is no longer used, the table is always empty.
1.3.6.1.4.1.13742.6.6.6.3not-accessibledeprecated
wireSensorLogEntry
OBJECT-TYPE
An entry containing log objects for a wire sensor.
1.3.6.1.4.1.13742.6.6.6.3.1not-accessibledeprecated
logWireSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.6.3.1.2TruthValueread-onlydeprecated
logWireSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.6.3.1.3SensorStateEnumerationread-onlydeprecated
logWireSensorAvgValue
OBJECT-TYPE
The sensor reading average value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the value exceeds 4294967295. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.6.3.1.4Unsigned32read-onlydeprecated
logWireSensorMaxValue
OBJECT-TYPE
The sensor reading maximum value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the value exceeds 4294967295. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.6.3.1.5Unsigned32read-onlydeprecated
logWireSensorMinValue
OBJECT-TYPE
The sensor reading minimum value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the value exceeds 4294967295. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.6.3.1.6Unsigned32read-onlydeprecated
logTransferSwitch
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.6.7
transferSwitchSensorLogTable
OBJECT-TYPE
A list of transfer switch sensor entries in the log.
1.3.6.1.4.1.13742.6.6.7.3not-accessiblecurrent
transferSwitchSensorLogEntry
OBJECT-TYPE
An entry containing log objects for a transfer switch sensor.
1.3.6.1.4.1.13742.6.6.7.3.1not-accessiblecurrent
logTransferSwitchSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.7.3.1.2TruthValueread-onlycurrent
logTransferSwitchSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.7.3.1.3SensorStateEnumerationread-onlycurrent
logTransferSwitchSensorAvgValue
OBJECT-TYPE
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.7.3.1.4Unsigned32read-onlycurrent
logTransferSwitchSensorMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.7.3.1.5Unsigned32read-onlycurrent
logTransferSwitchSensorMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.7.3.1.6Unsigned32read-onlycurrent
logTransferSwitchSensorSignedAvgValue
OBJECT-TYPE
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.7.3.1.7Integer32read-onlycurrent
logTransferSwitchSensorSignedMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.7.3.1.8Integer32read-onlycurrent
logTransferSwitchSensorSignedMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.7.3.1.9Integer32read-onlycurrent
logCircuit
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.6.8
circuitSensorLogTable
OBJECT-TYPE
A list of circuit sensor entries in the log.
1.3.6.1.4.1.13742.6.6.8.3not-accessiblecurrent
circuitSensorLogEntry
OBJECT-TYPE
An entry containing log objects for a circuit sensor.
1.3.6.1.4.1.13742.6.6.8.3.1not-accessiblecurrent
logCircuitSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.8.3.1.2TruthValueread-onlycurrent
logCircuitSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.8.3.1.3SensorStateEnumerationread-onlycurrent
logCircuitSensorAvgValue
OBJECT-TYPE
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.3.1.4Unsigned32read-onlycurrent
logCircuitSensorMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.3.1.5Unsigned32read-onlycurrent
logCircuitSensorMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.3.1.6Unsigned32read-onlycurrent
logCircuitSensorSignedAvgValue
OBJECT-TYPE
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.3.1.7Integer32read-onlycurrent
logCircuitSensorSignedMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.3.1.8Integer32read-onlycurrent
logCircuitSensorSignedMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.3.1.9Integer32read-onlycurrent
circuitPoleSensorLogTable
OBJECT-TYPE
A list of circuit pole sensor entries in the log.
1.3.6.1.4.1.13742.6.6.8.5not-accessiblecurrent
circuitPoleSensorLogEntry
OBJECT-TYPE
An entry containing log objects for a circuit pole sensor.
1.3.6.1.4.1.13742.6.6.8.5.1not-accessiblecurrent
logCircuitPoleSensorDataAvailable
OBJECT-TYPE
Is data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.8.5.1.2TruthValueread-onlycurrent
logCircuitPoleSensorState
OBJECT-TYPE
The most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.8.5.1.3SensorStateEnumerationread-onlycurrent
logCircuitPoleSensorAvgValue
OBJECT-TYPE
The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.5.1.4Unsigned32read-onlycurrent
logCircuitPoleSensorMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.5.1.5Unsigned32read-onlycurrent
logCircuitPoleSensorMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.5.1.6Unsigned32read-onlycurrent
logCircuitPoleSensorSignedAvgValue
OBJECT-TYPE
The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.5.1.7Integer32read-onlycurrent
logCircuitPoleSensorSignedMaxValue
OBJECT-TYPE
The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.5.1.8Integer32read-onlycurrent
logCircuitPoleSensorSignedMinValue
OBJECT-TYPE
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.6.8.5.1.9Integer32read-onlycurrent
conformance
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.9
compliances
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.9.1
groups
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.9.2
reliability
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.10
reliabilityData
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.10.1
reliabilityDataTableSequenceNumber
OBJECT-TYPE
The sequence number for updates to the reliability data table
1.3.6.1.4.1.13742.6.10.1.1Integer32 (1..2147483647)read-onlycurrent
reliabilityDataTable
OBJECT-TYPE
A list of PDU reliability data entries.
1.3.6.1.4.1.13742.6.10.1.2not-accessiblecurrent
reliabilityDataEntry
OBJECT-TYPE
An entry containing reliability data for a particular PDU.
1.3.6.1.4.1.13742.6.10.1.2.1not-accessiblecurrent
reliabilityIndex
OBJECT-TYPE
Index of the entry in the reliability data table.
1.3.6.1.4.1.13742.6.10.1.2.1.1Integer32 (1..4096)not-accessiblecurrent
reliabilityId
OBJECT-TYPE
Unique ID of the entry. POH Power on hours. CB.<label>.TRIPCNT Trip count of circuit breaker with label <label>. CTRL.<serial>.<addr>.MASTER.CSUMERRLASTHOUR Number of checksum errors in slave (controller board) to master (CPU board) communication in the last hour on controller with serial number <serial> and bus address <addr>. CTRL.<serial>.<addr>.SLAVE.CSUMERRLASTHOUR Number of checksum errors in master (CPU board) to slave (controller board) communication in the last hour on controller with serial number <serial> and bus address <addr>. CTRL.<serial>.<addr>.TOUTLASTHOUR Number of communication timeouts to controller with serial number <serial> and bus address <addr> in the last hour. CTRL.<serial>.<addr>.RLY.<num>.CYCLECNT Number of cycles the relay <num> on the controller board with serial number <serial> and bus address <addr> has made. A cycle is an off->on followed by an on->off event later. The count is increased on the off->on transition. CTRL.<serial>.<addr>.RLY.<num>.FAILLASTHOUR Number of failed switching operations on relay <num> on the controller board with serial number <serial> and bus address <addr> in the last hour. It depends on the specific controller board hardware and what error conditions are detected.
1.3.6.1.4.1.13742.6.10.1.2.1.2DisplayStringread-onlycurrent
reliabilityDataValue
OBJECT-TYPE
The normalized value
1.3.6.1.4.1.13742.6.10.1.2.1.3Unsigned32read-onlycurrent
reliabilityDataMaxPossible
OBJECT-TYPE
The maximum possible normalized value
1.3.6.1.4.1.13742.6.10.1.2.1.4Unsigned32read-onlycurrent
reliabilityDataWorstValue
OBJECT-TYPE
The worst normalized value seen so far
1.3.6.1.4.1.13742.6.10.1.2.1.5Unsigned32read-onlycurrent
reliabilityDataThreshold
OBJECT-TYPE
The normalized Threshold value
1.3.6.1.4.1.13742.6.10.1.2.1.6Unsigned32read-onlycurrent
reliabilityDataRawUpperBytes
OBJECT-TYPE
The upper 4 bytes of the raw (not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value
1.3.6.1.4.1.13742.6.10.1.2.1.7Unsigned32read-onlycurrent
reliabilityDataRawLowerBytes
OBJECT-TYPE
The lower 4 bytes of the raw (not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value
1.3.6.1.4.1.13742.6.10.1.2.1.8Unsigned32read-onlycurrent
reliabilityDataFlags
OBJECT-TYPE
Flags
1.3.6.1.4.1.13742.6.10.1.2.1.9Bits {invalidFlag(0), oldValue(1), criticalEntry(2)}read-onlycurrent
reliabilityErrorLog
OBJECT-IDENTITY
1.3.6.1.4.1.13742.6.10.2
reliabilityErrorLogTable
OBJECT-TYPE
A list of PDU reliability error log entries.
1.3.6.1.4.1.13742.6.10.2.2not-accessiblecurrent
reliabilityErrorLogEntry
OBJECT-TYPE
An entry containing reliability error log data for a particular PDU.
1.3.6.1.4.1.13742.6.10.2.2.1not-accessiblecurrent
reliabilityErrorLogIndex
OBJECT-TYPE
Index of the entry in the reliability error log table.
1.3.6.1.4.1.13742.6.10.2.2.1.1Integer32 (1..2147483647)not-accessiblecurrent
reliabilityErrorLogId
OBJECT-TYPE
Unique ID of the entry. POH Power on hours. CB.<label>.TRIPCNT Trip count of circuit breaker with label <label>. CTRL.<serial>.<addr>.MASTER.CSUMERRLASTHOUR Number of checksum errors in slave (controller board) to master (CPU board) communication in the last hour on controller with serial number <serial> and bus address <addr>. CTRL.<serial>.<addr>.SLAVE.CSUMERRLASTHOUR Number of checksum errors in master (CPU board) to slave (controller board) communication in the last hour on controller with serial number <serial> and bus address <addr>. CTRL.<serial>.<addr>.TOUTLASTHOUR Number of communication timeouts to controller with serial number <serial> and bus address <addr> in the last hour. CTRL.<serial>.<addr>.RLY.<num>.CYCLECNT Number of cycles the relay <num> on the controller board with serial number <serial> and bus address <addr> has made. A cycle is an off->on followed by an on->off event later. The count is increased on the off->on transition. CTRL.<serial>.<addr>.RLY.<num>.FAILLASTHOUR Number of failed switching operations on relay <num> on the controller board with serial number <serial> and bus address <addr> in the last hour. It depends on the specific controller board hardware and what error conditions are detected.
1.3.6.1.4.1.13742.6.10.2.2.1.2DisplayStringread-onlycurrent
reliabilityErrorLogValue
OBJECT-TYPE
The normalized value
1.3.6.1.4.1.13742.6.10.2.2.1.3Unsigned32read-onlycurrent
reliabilityErrorLogThreshold
OBJECT-TYPE
The normalized threshold value
1.3.6.1.4.1.13742.6.10.2.2.1.6Unsigned32read-onlycurrent
reliabilityErrorLogRawUpperBytes
OBJECT-TYPE
The upper 4 bytes of the raw (not normalized) data. reliabilityErrorLogRawUpperBytes and reliabilityErrorLogRawLowerBytes should be combined and interpreted as a signed 64-bit value
1.3.6.1.4.1.13742.6.10.2.2.1.7Unsigned32read-onlycurrent
reliabilityErrorLogRawLowerBytes
OBJECT-TYPE
The lower 4 bytes of the raw (not normalized) data. reliabilityErrorLogRawUpperBytes and reliabilityErrorLogRawLowerBytes should be combined and interpreted as a signed 64-bit value
1.3.6.1.4.1.13742.6.10.2.2.1.8Unsigned32read-onlycurrent
reliabilityErrorLogPOH
OBJECT-TYPE
The time of occurrence of the event measured from the last time the PDU was powered on
1.3.6.1.4.1.13742.6.10.2.2.1.9Unsigned32read-onlycurrent
reliabilityErrorLogTime
OBJECT-TYPE
The UTC time of occurrence of the event
1.3.6.1.4.1.13742.6.10.2.2.1.10Unsigned32read-onlycurrent

Notifications

NameOIDStatus
systemStarted
NOTIFICATION-TYPE
The system has started.
1.3.6.1.4.1.13742.6.0.1current
systemReset
NOTIFICATION-TYPE
The system was rebooted.
1.3.6.1.4.1.13742.6.0.2current
userLogin
NOTIFICATION-TYPE
A user logged in.
1.3.6.1.4.1.13742.6.0.3current
userLogout
NOTIFICATION-TYPE
A user logged out.
1.3.6.1.4.1.13742.6.0.4current
userAuthenticationFailure
NOTIFICATION-TYPE
A user authentication attempt failed.
1.3.6.1.4.1.13742.6.0.5current
userSessionTimeout
NOTIFICATION-TYPE
A user session timed out.
1.3.6.1.4.1.13742.6.0.8current
userAdded
NOTIFICATION-TYPE
A user account was added to the system.
1.3.6.1.4.1.13742.6.0.11current
userModified
NOTIFICATION-TYPE
A user account was modified.
1.3.6.1.4.1.13742.6.0.12current
userDeleted
NOTIFICATION-TYPE
A user account was deleted from the system.
1.3.6.1.4.1.13742.6.0.13current
roleAdded
NOTIFICATION-TYPE
A role was added to the system.
1.3.6.1.4.1.13742.6.0.14current
roleModified
NOTIFICATION-TYPE
A role was modified.
1.3.6.1.4.1.13742.6.0.15current
roleDeleted
NOTIFICATION-TYPE
A role was deleted from the system.
1.3.6.1.4.1.13742.6.0.16current
deviceUpdateStarted
NOTIFICATION-TYPE
The device firmware update has started.
1.3.6.1.4.1.13742.6.0.20current
deviceUpdateCompleted
NOTIFICATION-TYPE
The device firmware update has completed.
1.3.6.1.4.1.13742.6.0.21current
userBlocked
NOTIFICATION-TYPE
A blocked user tried to log in.
1.3.6.1.4.1.13742.6.0.22current
powerControl
NOTIFICATION-TYPE
An outlet switching operation has been performed. Note that measurementsOutletSensorState represents the state of the outlet at the time the trap was sent. This may be different from the final state of the outlet. For instance, if the outlet is cycled and the outlet cycle delay is 20 seconds, this variable will indicate OFF although the final state of the outlet will be ON. The final state of the outlet will be indicated in the outletSensorStateChange trap for the outlet onOff sensor.
1.3.6.1.4.1.13742.6.0.23current
userPasswordChanged
NOTIFICATION-TYPE
User password was changed.
1.3.6.1.4.1.13742.6.0.24current
passwordSettingsChanged
NOTIFICATION-TYPE
Strong password settings changed.
1.3.6.1.4.1.13742.6.0.28current
firmwareValidationFailed
NOTIFICATION-TYPE
Validation of an uploaded firmware image failed.
1.3.6.1.4.1.13742.6.0.38current
logFileCleared
NOTIFICATION-TYPE
The event log has been cleared.
1.3.6.1.4.1.13742.6.0.41current
bulkConfigurationSaved
NOTIFICATION-TYPE
A bulk configuration file was downloaded from the device.
1.3.6.1.4.1.13742.6.0.53current
bulkConfigurationCopied
NOTIFICATION-TYPE
A bulk configuration file was copied to the device.
1.3.6.1.4.1.13742.6.0.54current
pduSensorStateChange
NOTIFICATION-TYPE
Unit-level sensor state change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can have negative readings, measurementsUnitSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
1.3.6.1.4.1.13742.6.0.60deprecated
inletSensorStateChange
NOTIFICATION-TYPE
Inlet sensor state change. Which value field to use depends on the metadata of the sensor. measurementsInletSensorValue is undefined for sensors which can have negative readings, measurementsInletSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For an rcmState sensor transitioning to the fail state, the value is the residual current just before the sensor transitioned to the fail state i.e. if typeOfSensor = rcmState and measurementsInletSensorState = fail, then measurementsInletSensorValue = the residual current just before the sensor transitioned to the fail state
1.3.6.1.4.1.13742.6.0.61current
inletPoleSensorStateChange
NOTIFICATION-TYPE
Inlet pole sensor state change. Which value field to use depends on the metadata of the sensor. measurementsInletPoleSensorValue is undefined for sensors which can have negative readings, measurementsInletPoleSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
1.3.6.1.4.1.13742.6.0.62current
outletSensorStateChange
NOTIFICATION-TYPE
Outlet sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOutletSensorValue is undefined for sensors which can have negative readings, measurementsOutletSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
1.3.6.1.4.1.13742.6.0.63current
outletPoleSensorStateChange
NOTIFICATION-TYPE
Outlet pole sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOutletPoleSensorValue is undefined for sensors which can have negative readings, measurementsOutletPoleSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
1.3.6.1.4.1.13742.6.0.64current
overCurrentProtectorSensorStateChange
NOTIFICATION-TYPE
Overcurrent protector sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undefined for sensors which can have negative readings, measurementsOverCurrentProtectorSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For trip sensor state changes, if a particular outlet is determined to be likely to have caused the OCP trip, its label is passed in suspectedTripCauseLabel.
1.3.6.1.4.1.13742.6.0.65current
externalSensorStateChange
NOTIFICATION-TYPE
External sensor state change.
1.3.6.1.4.1.13742.6.0.66current
smtpMessageTransmissionFailure
NOTIFICATION-TYPE
SMTP message transmission failure
1.3.6.1.4.1.13742.6.0.67current
ldapError
NOTIFICATION-TYPE
An LDAP error occurred; errorDescription describes the error
1.3.6.1.4.1.13742.6.0.68current
deviceUpdateFailed
NOTIFICATION-TYPE
The device firmware update has failed.
1.3.6.1.4.1.13742.6.0.70current
loadSheddingModeEntered
NOTIFICATION-TYPE
The PDU has entered load shedding mode
1.3.6.1.4.1.13742.6.0.71current
loadSheddingModeExited
NOTIFICATION-TYPE
The PDU has exited load shedding mode
1.3.6.1.4.1.13742.6.0.72current
pingServerEnabled
NOTIFICATION-TYPE
The ping feature has been enabled for a server.
1.3.6.1.4.1.13742.6.0.73current
pingServerDisabled
NOTIFICATION-TYPE
The ping feature has been disabled for a server.
1.3.6.1.4.1.13742.6.0.74current
serverNotReachable
NOTIFICATION-TYPE
A monitored server has become unreachable.
1.3.6.1.4.1.13742.6.0.75current
serverReachable
NOTIFICATION-TYPE
A monitored server has become reachable.
1.3.6.1.4.1.13742.6.0.76current
rfCodeTagConnected
NOTIFICATION-TYPE
An RF-Code tag has been connected.
1.3.6.1.4.1.13742.6.0.77deprecated
rfCodeTagDisconnected
NOTIFICATION-TYPE
An RF-Code tag has been disconnected.
1.3.6.1.4.1.13742.6.0.78deprecated
deviceIdentificationChanged
NOTIFICATION-TYPE
A device identification parameter has been changed.
1.3.6.1.4.1.13742.6.0.79current
usbSlaveConnected
NOTIFICATION-TYPE
Connectivity to downstream slave has been established. It applies to the following interfaces: USB Ethernet This trap is sent only if deviceCascadeType is portForwarding
1.3.6.1.4.1.13742.6.0.80current
usbSlaveDisconnected
NOTIFICATION-TYPE
Connectivity to downstream slave has been lost It applies to the following interfaces: USB Ethernet This trap is sent only if deviceCascadeType is portForwarding
1.3.6.1.4.1.13742.6.0.81current
lhxSupportChanged
NOTIFICATION-TYPE
Schroff LHX support has been enabled or disabled.
1.3.6.1.4.1.13742.6.0.82current
userAcceptedRestrictedServiceAgreement
NOTIFICATION-TYPE
A user accepted the Restricted Service Agreement.
1.3.6.1.4.1.13742.6.0.83current
userDeclinedRestrictedServiceAgreement
NOTIFICATION-TYPE
A user declined the Restricted Service Agreement.
1.3.6.1.4.1.13742.6.0.84current
wireSensorStateChange
NOTIFICATION-TYPE
Wire sensor state change.
1.3.6.1.4.1.13742.6.0.85deprecated
transferSwitchSensorStateChange
NOTIFICATION-TYPE
Transfer switch sensor state change. Which value field to use depends on the metadata of the sensor. measurementsTransferSwitchSensorValue is undefined for sensors which can have negative readings, measurementsTransferSwitchSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
1.3.6.1.4.1.13742.6.0.86current
deviceSettingsSaved
NOTIFICATION-TYPE
A configuration backup has been downloaded from the device.
1.3.6.1.4.1.13742.6.0.88current
deviceSettingsRestored
NOTIFICATION-TYPE
A configuration backup has been restored to the device.
1.3.6.1.4.1.13742.6.0.89current
webcamInserted
NOTIFICATION-TYPE
A webcam has been connected.
1.3.6.1.4.1.13742.6.0.90current
webcamRemoved
NOTIFICATION-TYPE
A webcam has been disconnected.
1.3.6.1.4.1.13742.6.0.91current
inletEnabled
NOTIFICATION-TYPE
PDU operation has been enabled for an inlet
1.3.6.1.4.1.13742.6.0.92current
inletDisabled
NOTIFICATION-TYPE
PDU operation has been disabled for an inlet
1.3.6.1.4.1.13742.6.0.93current
serverConnectivityUnrecoverable
NOTIFICATION-TYPE
The connection to a monitored server could not be recovered.
1.3.6.1.4.1.13742.6.0.94current
radiusError
NOTIFICATION-TYPE
A Radius error occurred; errorDescription describes the error
1.3.6.1.4.1.13742.6.0.95current
serverReachabilityError
NOTIFICATION-TYPE
Server reachability error occurred; errorDescription describes the error. This trap is sent when the Error state is entered. Reasons for transitioning to the Error state include the following: Unable to resolve the server hostname.
1.3.6.1.4.1.13742.6.0.96current
inletSensorReset
NOTIFICATION-TYPE
An inlet sensor was reset.
1.3.6.1.4.1.13742.6.0.97current
outletSensorReset
NOTIFICATION-TYPE
An outlet sensor was reset.
1.3.6.1.4.1.13742.6.0.98current
unknownPeripheralDeviceAttached
NOTIFICATION-TYPE
An unsupported peripheral device was attached.
1.3.6.1.4.1.13742.6.0.99current
peripheralDeviceFirmwareUpdate
NOTIFICATION-TYPE
The firmware update state of a peripheral device changed while performing update to peripheralDevicePackageFirmwareVersion.
1.3.6.1.4.1.13742.6.0.100current
unitSensorReset
NOTIFICATION-TYPE
A unit-level sensor was reset.
1.3.6.1.4.1.13742.6.0.101current
unitSensorStateChange
NOTIFICATION-TYPE
Unit-level sensor state change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can have negative readings, measurementsUnitSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
1.3.6.1.4.1.13742.6.0.102current
circuitSensorStateChange
NOTIFICATION-TYPE
BCM2/PMC branch circuit sensor state change. Which value field to use depends on the metadata of the sensor. measurementsCircuitSensorValue is undefined for sensors which can have negative readings, measurementsCircuitSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
1.3.6.1.4.1.13742.6.0.103current
circuitPoleSensorStateChange
NOTIFICATION-TYPE
BCM2/PMC circuit pole sensor state change. Which value field to use depends on the metadata of the sensor. measurementsCircuitPoleSensorValue is undefined for sensors which can have negative readings, measurementsCircuitPoleSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
1.3.6.1.4.1.13742.6.0.104current
circuitAdded
NOTIFICATION-TYPE
A new branch circuit has been configured
1.3.6.1.4.1.13742.6.0.105current
circuitDeleted
NOTIFICATION-TYPE
A configured branch circuit has been deleted
1.3.6.1.4.1.13742.6.0.106current
circuitModified
NOTIFICATION-TYPE
A configured branch circuit has been modified
1.3.6.1.4.1.13742.6.0.107current
circuitSensorReset
NOTIFICATION-TYPE
An BCM2/PMC branch circuit sensor was reset.
1.3.6.1.4.1.13742.6.0.108current
powerMeterAdded
NOTIFICATION-TYPE
A new power meter or panel has been configured
1.3.6.1.4.1.13742.6.0.109current
powerMeterDeleted
NOTIFICATION-TYPE
A configured power meter has been deleted
1.3.6.1.4.1.13742.6.0.110current
powerMeterModified
NOTIFICATION-TYPE
A configured power meter has been modified
1.3.6.1.4.1.13742.6.0.111current
smsMessageTransmissionFailure
NOTIFICATION-TYPE
Sending an SMS message failed.
1.3.6.1.4.1.13742.6.0.112current
smartCardInserted
NOTIFICATION-TYPE
A smartcard was inserted into a card reader.
1.3.6.1.4.1.13742.6.0.113current
smartCardRemoved
NOTIFICATION-TYPE
A smartcard was removed from a card reader.
1.3.6.1.4.1.13742.6.0.114current

Conformance

NameOIDStatus
complianceRev1
MODULE-COMPLIANCE
The requirements for conformance to the PDU2-MIB.
1.3.6.1.4.1.13742.6.9.1.1deprecated
complianceRev2
MODULE-COMPLIANCE
The requirements for conformance to the PDU2-MIB.
1.3.6.1.4.1.13742.6.9.1.2current
configGroup
OBJECT-GROUP
A collection of objects representing configuration data.
1.3.6.1.4.1.13742.6.9.2.1current
logGroup
OBJECT-GROUP
A collection of objects providing logging (history of readings) capabilities about the PDU.
1.3.6.1.4.1.13742.6.9.2.2current
measurementsGroup
OBJECT-GROUP
A collection of objects providing measurements (most recent data) capabilities. about the PDU.
1.3.6.1.4.1.13742.6.9.2.3current
controlGroup
OBJECT-GROUP
A collection of objects providing the ability to control various components of a PDU.
1.3.6.1.4.1.13742.6.9.2.4current
trapInformationGroup
OBJECT-GROUP
A collection of objects providing information in the traps.
1.3.6.1.4.1.13742.6.9.2.5current
trapsGroup
NOTIFICATION-GROUP
A collection of traps.
1.3.6.1.4.1.13742.6.9.2.9current
reliabilityGroup
OBJECT-GROUP
A collection of objects providing reliability data.
1.3.6.1.4.1.13742.6.9.2.10current
ipAddressGroup
OBJECT-GROUP
A collection of objects representing configuration data.
1.3.6.1.4.1.13742.6.9.2.12deprecated
oldConfigGroup
OBJECT-GROUP
A collection of objects representing old (deprecated) configuration data.
1.3.6.1.4.1.13742.6.9.2.13deprecated
oldLogGroup
OBJECT-GROUP
A collection of objects representing old (deprecated) logging data.
1.3.6.1.4.1.13742.6.9.2.14deprecated
oldMeasurementsGroup
OBJECT-GROUP
A collection of objects representing old (deprecated) measurement data.
1.3.6.1.4.1.13742.6.9.2.15deprecated
oldTrapsGroup
NOTIFICATION-GROUP
A collection of objects representing old (deprecated) traps.
1.3.6.1.4.1.13742.6.9.2.16deprecated
obsoleteObjectsGroup
OBJECT-GROUP
A collection of obsolete objects.
1.3.6.1.4.1.13742.6.9.2.20obsolete