HUAWEI-POWER-MIB
- Registered at
- 1.3.6.1.4.1.2011.6.2
- Last updated
- 2013-12-28 00:00
- Organization
- Huawei Technologies Co.,Ltd.
- Revisions
- 2013-12-28 00:00, 2013-11-16 00:00, 2012-12-28 00:00, 2012-12-14 00:00, 2012-07-24 00:00, 2012-06-25 00:00, 2012-01-09 00:00, 2011-12-17 00:00, 2011-12-08 00:00, 2011-08-17 00:00, 2011-03-16 00:00, 2010-12-17 00:00, 2010-11-10 00:00, 2010-07-18 09:00, 2010-06-12 09:00, 2010-04-21 09:00, 2010-04-08 09:00, 2010-03-09 09:00, 2010-02-06 09:00, 2010-01-29 09:00, 2006-11-10 09:00, 2006-10-25 09:00
- Namespace
- huawei
- Source file
HUAWEI-POWER-MIB- Digest
sha256:c67abe53fa1754b27a7f09d46314046d66065b7842c7dbae006bf3d7eb4ede63
Description
This MIB is used for defining Power Monitor management MIB objects.
Contact
Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China Website: http://www.huawei.com Email: support@huawei.com
Imports
| From | Symbols |
|---|---|
| HUAWEI-DEVICE-MIB | hwFrameIndex |
| HUAWEI-ENVIRONMENT-MIB | hwDigChannelIndex, hwEnvEmuIndex, hwEnvEmuType |
| HUAWEI-MIB | huaweiUtility |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso |
| SNMPv2-TC | DateAndTime, DisplayString, RowStatus, TEXTUAL-CONVENTION, TruthValue |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
HCNUM-TC HUAWEI-DEVICE-MIB HUAWEI-ENVIRONMENT-MIB HUAWEI-MIB HUAWEI-POWER-MIB HUAWEI-TC-MIB IANAifType-MIB IF-MIB INET-ADDRESS-MIB SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| MeasuresRange TEXTUAL-CONVENTION Basic unit of measure: 1.pressure:indicated by mV, 1V = 1000 mV 2.current:indicated by mA, 1A = 1000 mA 3.temperature: indicated by 1% degree centigrade | current |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| hwPowerMonObjects OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.1 | |||
| hwPowerSysInfoTable OBJECT-TYPE Power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.1 | not-accessible | current | |
| hwPowerSysInfoEntry OBJECT-TYPE Power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.1.1 | not-accessible | current | |
| hwPowerIndex OBJECT-TYPE Index of the power supply monitored by the monitoring unit | 1.3.6.1.4.1.2011.6.2.1.1.1.1 | Integer32 (0..255) | read-only | current |
| hwPowerType OBJECT-TYPE Type of the Power emu device. Options: 1.power4875(1) - Type of the Power emu device is power4875 2.power4810(2) - Type of the Power emu device is power4810 3.power48100(3) - Type of the Power emu device is power48100 4.power4850(4) - Type of the Power emu device is power4850 5.power48240(5) - Type of the Power emu device is power48240 6.power48120(6) - Type of the Power emu device is power48120 7.power48300(7) - Type of the Power emu device is power48300 8.power48240SinglePhase(8) - Type of the Power emu device is power48240SinglePhase 9.universalPower(9) - Type of the Power emu device is universalPower 10.power4845(10) - Type of the Power emu device is power4845 11.rpower(11) - Type of the Power emu device is rpower 12.power4805(15) - Type of the Power emu device is power4805 13.power4820(16) - Type of the Power emu device is power4820 14.onps(17) - Type of the Power emu device is onps 15.power4875l(18) - Type of the Power emu device is power4875l 16.psma(100) - Type of the Power emu device is psma 17.perm-al175nt(101) - Type of the Power emu device is perm-al175nt 18.mcs1800(102) - Type of the Power emu device is mcs1800 19.mcs1800A(103) - Type of the Power emu device is mcs1800A 20.mcs3000(104) - Type of the Power emu device is mcs3000 21.sm40sm60(105) - Type of the Power emu device is sm40sm60 22.scu(106) - Type of the Power emu device is scu 23.eltek(107) - Type of the Power emu device is eltek 24.dk04(108) - Type of the Power emu device is dk04 25.dk04C(109) - Type of the Power emu device is dk04C 26.dpc(110) - Type of the Power emu device is dpc 27.power4830(120) - Type of the Power emu device is power4830 28.h831pmua(121) - Type of the Power emu device is h831pmua 29.power3000(122) - Type of the Power emu device is power3000 30.liFeBattery(123) - Type of the Power emu device is LiFeBattery 31.etp4830(125), - Type of SMU Power emu device is etp4830 32.etp4890(126), - Type of SMU Power emu device is etp4890 33.h801pmu(127), - Type of the Power emu device is h801pmua 34.etp48150(128), - Type of SMU Power emu device is etp48150 35.other(255) - other Power Type | 1.3.6.1.4.1.2011.6.2.1.1.1.2 | INTEGER {power4875(1), power4810(2), power48100(3), power4850(4), power48240(5), power48120(6), power48300(7), power48240SinglePhase(8), universalPower(9), power4845(10), rpower(11), power4805(15), power4820(16), onps(17), power4875l(18), psma(100), perm-al175nt(101), mcs1800(102), mcs1800A(103), mcs3000(104), sm40sm60(105), scu(106), eltek(107), dk04(108), dk04C(109), dpc(110), power4830(120), h831pmua(121), power3000(122), liFeBattery(123), etp4830(125), etp4890(126), h801pmu(127), etp48150(128), other(255)} | read-write | current |
| hwPowerName OBJECT-TYPE Power name. | 1.3.6.1.4.1.2011.6.2.1.1.1.3 | DisplayString | read-write | current |
| hwPowerState OBJECT-TYPE Power board status: Refers to the status of communication between the internal monitor board of the power device and the external upper board. Options: 1.normal(1) - indicates the normal state 2.fault(2) - indicates the faulty state 3.protecting(3)- indicates that the backup power supply works in the protection state 4.switched(4) - indicates that the main power supply is faulty, and is protected by backup power supply 5.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.1.1.4 | INTEGER {invalid(-1), normal(1), fault(2), protecting(3), switched(4)} | read-only | current |
| hwPowerRowStatus OBJECT-TYPE RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status. | 1.3.6.1.4.1.2011.6.2.1.1.1.5 | RowStatus | read-write | current |
| hwPowerControlMode OBJECT-TYPE Control mode of the power monitor module. Options: 1.manualControl(1) - control by manual, the remote mode 2.autoControl(2) - auto control mode, the default is auto control mode 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.1.1.6 | INTEGER {invalid(-1), manualControl(1), autoControl(2)} | read-write | current |
| hwPowerRemoteFrameID OBJECT-TYPE Apply for remote power system. It is the frame ID that the remote unit exists in | 1.3.6.1.4.1.2011.6.2.1.1.1.7 | Integer32 (0..255) | read-write | current |
| hwPowerProtect OBJECT-TYPE Apply for remote power system. It is used to enable or disable N+1 protection function. Options: 1.protect(1) - enables the N+1 protection function 2.undoProtect(2) - disables the N+1 protection function | 1.3.6.1.4.1.2011.6.2.1.1.1.8 | INTEGER {protect(1), undoProtect(2)} | read-write | current |
| hwPowerVersion OBJECT-TYPE Version of power | 1.3.6.1.4.1.2011.6.2.1.1.1.9 | DisplayString | read-only | current |
| hwPowerSupplyState OBJECT-TYPE Power supply modes. Options: 1.ac(1) - indicates the AC power supply 2.battery(2) - indicates power supply by the batteries | 1.3.6.1.4.1.2011.6.2.1.1.1.10 | INTEGER {ac(1), battery(2)} | read-only | current |
| hwACInputTable OBJECT-TYPE AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.2 | not-accessible | current | |
| hwACInputEntry OBJECT-TYPE AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.2.1 | not-accessible | current | |
| hwACLoopIndex OBJECT-TYPE Input loop index. There are two channels of AC current input, which are the backup for each other. | 1.3.6.1.4.1.2011.6.2.1.2.1.1 | Integer32 (0..255) | read-only | current |
| hwACPowerState OBJECT-TYPE Status of power supply. Options: 1.normal(1) - indicates that the power supply is normal 2.offline(2) - indicates that the power supply is offline 3.exceedVoltage(3) - indicates that the power supply is overvoltage 4.belowVoltage(4) - indicates that the power supply is undervoltage 5.backup(5) - indicates that the power supply is not supported currently 6.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.2.1.2 | INTEGER {invalid(-1), normal(1), offline(2), exceedVoltage(3), belowVoltage(4), backup(5)} | read-only | current |
| hwACVoltA OBJECT-TYPE AC Inuput voltage A. Unit: mV | 1.3.6.1.4.1.2011.6.2.1.2.1.3 | MeasuresRange | read-only | current |
| hwACCurrentA OBJECT-TYPE AC input Current A. Unit: mA | 1.3.6.1.4.1.2011.6.2.1.2.1.4 | MeasuresRange | read-only | current |
| hwACVoltB OBJECT-TYPE AC input voltage B. Unit: mv | 1.3.6.1.4.1.2011.6.2.1.2.1.5 | MeasuresRange | read-only | current |
| hwACCurrentB OBJECT-TYPE AC input current B. Unit: mA | 1.3.6.1.4.1.2011.6.2.1.2.1.6 | MeasuresRange | read-only | current |
| hwACVoltC OBJECT-TYPE AC input voltage C. Unit: mV | 1.3.6.1.4.1.2011.6.2.1.2.1.7 | MeasuresRange | read-only | current |
| hwACCurrentC OBJECT-TYPE AC input current C. Unit: mA | 1.3.6.1.4.1.2011.6.2.1.2.1.8 | MeasuresRange | read-only | current |
| hwACVoltageHigh OBJECT-TYPE AC input over-voltage alarm threshold. Unit: mV | 1.3.6.1.4.1.2011.6.2.1.2.1.9 | MeasuresRange | read-write | current |
| hwACVoltageLow OBJECT-TYPE AC input under-voltage alarm threshold. Unit: mV | 1.3.6.1.4.1.2011.6.2.1.2.1.10 | MeasuresRange | read-write | current |
| hwACRowStatus OBJECT-TYPE Only the add operation, delete operation, and status query operation are supported. | 1.3.6.1.4.1.2011.6.2.1.2.1.11 | RowStatus | read-write | current |
| hwACVoltageAState OBJECT-TYPE Phase AB/A of AC input state. Options: 1. normal(0) - indicates that the Phase AB/A of AC input state is normal 2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase AB/A of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase AB/A of AC input state is missing-phase | 1.3.6.1.4.1.2011.6.2.1.2.1.12 | INTEGER {normal(0), belowVoltage(1), exceedVoltage(2), missing-phase(3)} | read-only | current |
| hwACVoltageBState OBJECT-TYPE Phase BC/B of AC input state. Options: 1. normal(0) - indicates that the Phase BC/B of AC input state is normal 2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase BC/B of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase BC/B of AC input state is missing-phase | 1.3.6.1.4.1.2011.6.2.1.2.1.13 | INTEGER {normal(0), belowVoltage(1), exceedVoltage(2), missing-phase(3)} | read-only | current |
| hwACVoltageCState OBJECT-TYPE Phase CA/C of AC input state. Options: 1. normal(0) - indicates that the Phase CA/C of AC input state is normal 2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase CA/C of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase CA/C of AC input state is missing-phase | 1.3.6.1.4.1.2011.6.2.1.2.1.14 | INTEGER {normal(0), belowVoltage(1), exceedVoltage(2), missing-phase(3)} | read-only | current |
| hwDCOutTable OBJECT-TYPE DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.3 | not-accessible | current | |
| hwDCOutEntry OBJECT-TYPE DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.3.1 | not-accessible | current | |
| hwDCVoltageOut OBJECT-TYPE DC voltage output. Unit: mV | 1.3.6.1.4.1.2011.6.2.1.3.1.1 | MeasuresRange | read-only | current |
| hwDCCurrentOut OBJECT-TYPE DC current output. Unit: mA | 1.3.6.1.4.1.2011.6.2.1.3.1.2 | MeasuresRange | read-only | current |
| hwDCVoltageOutHigh OBJECT-TYPE Output DC exceed-voltage alarm point. Default: 58000 Unit: mV | 1.3.6.1.4.1.2011.6.2.1.3.1.3 | MeasuresRange | read-write | current |
| hwDCVoltageOutLow OBJECT-TYPE Output DC below-voltage alarm point . Default value is 45V. Unit: mV | 1.3.6.1.4.1.2011.6.2.1.3.1.4 | MeasuresRange | read-write | current |
| hwDCVoltageOutState OBJECT-TYPE DC output voltage status. Options: 1. normal(1) - indicates that the DC output voltage state is normal 2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage 3. belowVoltage(3) - indicates that the DC output voltage state is belowVoltage 4.invalid(-1) - indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.3.1.5 | INTEGER {invalid(-1), normal(1), exceedVoltage(2), belowVoltage(3)} | read-only | deprecated |
| hwDCCurrentOutHigh OBJECT-TYPE Output DC exceed-current alarm point . Unit: mA | 1.3.6.1.4.1.2011.6.2.1.3.1.6 | MeasuresRange | read-write | current |
| hwDCCurrentOutLow OBJECT-TYPE Output below-current alarm point . Unit: mA | 1.3.6.1.4.1.2011.6.2.1.3.1.7 | MeasuresRange | read-write | current |
| hwDCCurrentOutState OBJECT-TYPE DC output current status. Options: 1.normal(1) - indicates that the DC output current state is normal 2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage 3.belowVoltage(3) - indicates that the DC output current state is belowVoltage 4.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.3.1.8 | INTEGER {invalid(-1), normal(1), exceedVoltage(2), belowVoltage(3)} | read-only | deprecated |
| hwDCOutRowStatus OBJECT-TYPE RowStatus standard operation | 1.3.6.1.4.1.2011.6.2.1.3.1.9 | RowStatus | read-write | current |
| hwDCOutLoadCurrent OBJECT-TYPE Total load current of DC output . Unit: mA | 1.3.6.1.4.1.2011.6.2.1.3.1.10 | MeasuresRange | read-only | current |
| hwDCOutLoadTmpHigh OBJECT-TYPE The off protection point under the load temperature, by default, it is 65 degrees centigrade. Unit: 0.01 degree | 1.3.6.1.4.1.2011.6.2.1.3.1.11 | MeasuresRange | read-write | current |
| hwDCOutRunState OBJECT-TYPE DC output running status. Options: 1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current 2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current 3.batteryVoltageOver(2) - indicates output over-voltage 4.batteryVoltageLack(3) - indicates battery lack-voltage 5.loadOff(4) - indicates load off twice 6.batteryOff(5) - indictes battery protection (off once) 7.communicationFailure(6) - indicates that the communication fails 8.dcOutManual(7) - indicates DC by manual | 1.3.6.1.4.1.2011.6.2.1.3.1.12 | Bits {battery1ChargeCurOver(0), battery2ChargeCurOver(1), batteryVoltageOver(2), batteryVoltageLack(3), loadOff(4), batteryOff(5), communicationFailure(6), dcOutManual(7)} | read-only | current |
| hwDCCommunicationState OBJECT-TYPE DC communication status. Options: 1.normal(0) - indicates that the DC communication state is normal 2.fault(1) - indicates that the DC communication state is fault | 1.3.6.1.4.1.2011.6.2.1.3.1.13 | INTEGER {normal(0), fault(1)} | read-only | current |
| hwLoadinfoTable OBJECT-TYPE Load information table. Through this table, the load parameter can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load. | 1.3.6.1.4.1.2011.6.2.1.4 | not-accessible | current | |
| hwLoadinfoEntry OBJECT-TYPE Load information table. Through this table, the load parameter can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load. | 1.3.6.1.4.1.2011.6.2.1.4.1 | not-accessible | current | |
| hwLoadIndex OBJECT-TYPE Loop index: usually each DC output loop corresponds to a load. | 1.3.6.1.4.1.2011.6.2.1.4.1.1 | Integer32 (0..255) | read-only | current |
| hwLoadInfoAdminState OBJECT-TYPE Load operation. Options: 1. on(1) - indicates that the Load is enabled 2. off(2) - indicates that the Load is disabled 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.4.1.2 | INTEGER {invalid(-1), on(1), off(2)} | read-write | current |
| hwLoadInfoOperStatus OBJECT-TYPE Status of power supply. Options: 1. normal(1) - indicates that the state of power supply is normal 2. abnormal(2) - indicates that the state of power supply is abnormal 3. stop(3) - indicates that the state of power supply is stopping power supply 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.4.1.3 | INTEGER {invalid(-1), normal(1), abnormal(2), stop(3)} | read-only | current |
| hwLoadCurrent OBJECT-TYPE Present current . Unit: mA | 1.3.6.1.4.1.2011.6.2.1.4.1.4 | MeasuresRange | read-only | current |
| hwLoadVoltage OBJECT-TYPE Present voltage . Unit: mV | 1.3.6.1.4.1.2011.6.2.1.4.1.5 | MeasuresRange | read-only | current |
| hwLoadVoltageHigh OBJECT-TYPE Off voltage (Stop external voltage), in unit of mV, When DC output voltage exceeds the value, the load will be automatically cut off. Default: 43500 Unit: mV | 1.3.6.1.4.1.2011.6.2.1.4.1.6 | MeasuresRange | read-write | current |
| hwLoadLoadName OBJECT-TYPE Load name: usually each DC output loop corresponds to a load. | 1.3.6.1.4.1.2011.6.2.1.4.1.7 | DisplayString | read-write | current |
| hwLoadInfoRowStatus OBJECT-TYPE RowStatus standard operation | 1.3.6.1.4.1.2011.6.2.1.4.1.8 | RowStatus | read-write | current |
| hwLoadFuseState OBJECT-TYPE Load fuse state, including the auxiliary load fuse. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.4.1.9 | INTEGER {invalid(-1), on(1), off(2)} | read-only | current |
| hwLoadHoreIndex OBJECT-TYPE load hore index | 1.3.6.1.4.1.2011.6.2.1.4.1.10 | Integer32 (0..255) | read-write | current |
| hwRectifierTable OBJECT-TYPE Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply. | 1.3.6.1.4.1.2011.6.2.1.5 | not-accessible | current | |
| hwRectifierEntry OBJECT-TYPE Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply. | 1.3.6.1.4.1.2011.6.2.1.5.1 | not-accessible | current | |
| hwRectifierIndex OBJECT-TYPE Rectifier Module index. There are multiple rectifier modules to a power source. | 1.3.6.1.4.1.2011.6.2.1.5.1.1 | Integer32 (0..255) | read-only | current |
| hwRectifierAdminState OBJECT-TYPE Switch operation of rectifier module. Options: 1.on(1) - indicates that the Rectifier module is enabled 2.off(2) - indicates that the Rectifier module is disabled 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.5.1.2 | INTEGER {invalid(-1), on(1), off(2)} | read-write | current |
| hwRectifierOperState OBJECT-TYPE Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device. Options: 1. normal(1) - indicates that the Rectifier operation state is normal 2. fault(2) - indicates that the Rectifier operation state is fault 3. protect(3) - indicates that the Rectifier operation state is protect 4. communicationFailure(4) - indicates that the Rectifier operation state is communicationFailure 5. on(5) - indicates that the Rectifier operation state is on 6. noConfig(6) - indicates that the Rectifier operation state is not Configured 7. offline(7) - indicates that the Rectifier operation state is offline 8. close(8) - indicates that the Rectifier operation state is closed 9. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.5.1.3 | INTEGER {invalid(-1), normal(1), fault(2), protect(3), communicationFailure(4), on(5), noConfig(6), offline(7), close(8)} | read-only | current |
| hwRectifierVoltage OBJECT-TYPE Output voltage . Unit: mV | 1.3.6.1.4.1.2011.6.2.1.5.1.4 | MeasuresRange | read-only | current |
| hwRectifierCurrent OBJECT-TYPE Output current . Unit: mA | 1.3.6.1.4.1.2011.6.2.1.5.1.5 | MeasuresRange | read-only | current |
| hwRectifierRowStatus OBJECT-TYPE RowStatus standard operation | 1.3.6.1.4.1.2011.6.2.1.5.1.6 | RowStatus | read-write | current |
| hwRectifierCurrentLimit OBJECT-TYPE current limit switch | 1.3.6.1.4.1.2011.6.2.1.5.1.7 | TruthValue | read-write | current |
| hwRectifierRunState OBJECT-TYPE Running state of rectifier module. Options: 1.rectifierOn(0) - indicates that the module is on 2.averageCharge(1) - indicates that the module is being averagely charged. 3.output(2) - indicates that the module has output 4. isLimit(3) - indicates the current limit switch | 1.3.6.1.4.1.2011.6.2.1.5.1.8 | Bits {rectifierOn(0), averageCharge(1), output(2), isLimit(3)} | read-only | current |
| hwRectifierChargeState OBJECT-TYPE Charging state of rectifier. Options: 1. float(0) - indicates that the Charge state of Rectifier is float 2. average(1) - indicates that the Charge state of Rectifier is average 3. test(2) - indicates that the Charge state of Rectifier is test | 1.3.6.1.4.1.2011.6.2.1.5.1.9 | INTEGER {float(0), average(1), test(2)} | read-only | current |
| hwBatteryGroup OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.1.6 | |||
| hwBatteryGroupTable OBJECT-TYPE Basic information table of battery group. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.6.1 | not-accessible | current | |
| hwBatteryGroupEntry OBJECT-TYPE Basic information table of battery group. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.6.1.1 | not-accessible | current | |
| hwBatteryGroupCapacity OBJECT-TYPE Total capacity of the present battery group. Unit: Ah | 1.3.6.1.4.1.2011.6.2.1.6.1.1.1 | Integer32 | read-only | current |
| hwBatteryGroupCapcaityRemain OBJECT-TYPE Total remain capacity of the present battery group . invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. Unit: Ah | 1.3.6.1.4.1.2011.6.2.1.6.1.1.2 | Integer32 (-1..100) | read-only | current |
| hwBatteryGroups OBJECT-TYPE Number of battery group | 1.3.6.1.4.1.2011.6.2.1.6.1.1.3 | Integer32 (0..255) | read-write | current |
| hwBatteryGroupVoltageLow OBJECT-TYPE When the voltage of the battery group is lower than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV | 1.3.6.1.4.1.2011.6.2.1.6.1.1.4 | MeasuresRange | read-write | current |
| hwBatteryGroupChargeLimit OBJECT-TYPE Charge limit point quotient, the product of which and the max capacity of the battery group is the max charge current allowed. Default: 15 Unit: percent | 1.3.6.1.4.1.2011.6.2.1.6.1.1.5 | MeasuresRange | read-write | current |
| hwBatteryGroupRowStatus OBJECT-TYPE RowStatus standard operation | 1.3.6.1.4.1.2011.6.2.1.6.1.1.6 | RowStatus | read-write | current |
| hwBatteryGroupOperStatus OBJECT-TYPE The State of the battery supply which was connected with Power EMU. To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal. When the mains supply is abnormal, the battery group usually supplies power in an emergency. Options: 1.on(1) - indicates that the state of the battery power supply is on 2.off(2) - indicates that the state of the battery power supply is off 3.invalid(-1) - indicates that the device can not get the value,e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.6.1.1.7 | INTEGER {invalid(-1), on(1), off(2)} | read-only | current |
| hwBatteryGroupVoltageHigh OBJECT-TYPE When the voltage of the battery group is higher than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV | 1.3.6.1.4.1.2011.6.2.1.6.1.1.8 | MeasuresRange | read-write | current |
| hwBatteryGroupTwiceOffVoltage OBJECT-TYPE The twice off protection voltage of the battery group. Its unit is mV. Default: 44000 Unit: mV | 1.3.6.1.4.1.2011.6.2.1.6.1.1.9 | MeasuresRange | read-write | current |
| hwBatteryGroupProtectVoltage OBJECT-TYPE The first off protection voltage of the battery, whose default is 43V. Default: 43000 Unit: mV | 1.3.6.1.4.1.2011.6.2.1.6.1.1.10 | MeasuresRange | read-write | current |
| hwBatteryGroupTmpOffHigh OBJECT-TYPE The high temperature off protection point of the battery group, whose default is 50 degrees centigrade. Unit: 0.01 degree | 1.3.6.1.4.1.2011.6.2.1.6.1.1.11 | MeasuresRange | read-write | current |
| hwBatteryInstallTime OBJECT-TYPE The installing date of battery group. | 1.3.6.1.4.1.2011.6.2.1.6.1.1.12 | DisplayString | read-only | current |
| hwBatteryGroupBomCode OBJECT-TYPE The BOM code of battery. | 1.3.6.1.4.1.2011.6.2.1.6.1.1.13 | DisplayString (SIZE(0..32)) | read-write | current |
| hwChargeTable OBJECT-TYPE Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.6.2 | not-accessible | current | |
| hwChargeEntry OBJECT-TYPE Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.6.2.1 | not-accessible | current | |
| hwChargeAdminStatus OBJECT-TYPE Charge management mode. Options: 1. average(1) - indicates that the charge management mode is average charge 2. float(2) - indicates that the charge management mode is float charge 3. auto(3) - indicates that the charge management mode is auto-control charge 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.6.2.1.1 | INTEGER {invalid(-1), average(1), float(2), auto(3)} | read-write | current |
| hwChargeOperStatus OBJECT-TYPE Charge operation status. Options: 1. average(1) - indicates that the charge operation state is average charge 2. float(2) - indicates that the charge operation state is float charge 3. full(3) - indicates that the charge operation state is full 4. noCharge(4) - indicates that there is no charge in operation 5. discharge(5) - indicates that there is discharge in operation 6. sleep(6) - indicates that the charge operation state is sleep 7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.6.2.1.2 | INTEGER {invalid(-1), average(1), float(2), full(3), noCharge(4), discharge(5), sleep(6)} | read-only | current |
| hwAverageChargeVoltage OBJECT-TYPE Voltage value of average charge, in unit of mV. Default: 56500 Unit: mV | 1.3.6.1.4.1.2011.6.2.1.6.2.1.3 | MeasuresRange | read-write | current |
| hwFloatChargeVoltage OBJECT-TYPE Voltage value of float charge . Default: 53500 Unit: mV | 1.3.6.1.4.1.2011.6.2.1.6.2.1.4 | MeasuresRange | read-write | current |
| hwChargeControlRowStatus OBJECT-TYPE RowStatus standard operation | 1.3.6.1.4.1.2011.6.2.1.6.2.1.5 | RowStatus | read-write | current |
| hwAverageChargeTime OBJECT-TYPE Timing average charge time interval, effective range is 190 days. Default :value is 60 days Unit: day | 1.3.6.1.4.1.2011.6.2.1.6.2.1.6 | Integer32 | read-write | current |
| hwBatteryTmpRedeemingQuotiety OBJECT-TYPE Temperature redeeming quotient, used to set the co-relation between the float charge voltage and the battery temperature. It means How much will the float charge voltage decrease with the increasing of every degree centigrade of the battery temperature. The unit is mV. Specific value is determined by the redeem feature curve of floating charge for the battery group used. Default value is 100mV | 1.3.6.1.4.1.2011.6.2.1.6.2.1.7 | Integer32 | read-write | current |
| hwBatteryTable OBJECT-TYPE Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group. | 1.3.6.1.4.1.2011.6.2.1.6.3 | not-accessible | current | |
| hwBatteryEntry OBJECT-TYPE Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group. | 1.3.6.1.4.1.2011.6.2.1.6.3.1 | not-accessible | current | |
| hwBatteryIndex OBJECT-TYPE Battery group loop index | 1.3.6.1.4.1.2011.6.2.1.6.3.1.1 | Integer32 (0..255) | read-only | current |
| hwBatteryCapacity OBJECT-TYPE The permitted max battery capacity of the battery group loop charge. Unit: Ah | 1.3.6.1.4.1.2011.6.2.1.6.3.1.2 | Integer32 | read-write | current |
| hwBatteryLoopState OBJECT-TYPE The battery group present status. Options: 1. on(1) - indicates that the present state of battery group is on 2. off(2) - indicates that the present state of battery group is off 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.6.3.1.3 | INTEGER {invalid(-1), on(1), off(2)} | read-only | current |
| hwBatteryVoltage OBJECT-TYPE The loop voltage of the battery group. Unit: mV | 1.3.6.1.4.1.2011.6.2.1.6.3.1.4 | MeasuresRange | read-only | current |
| hwBatteryState OBJECT-TYPE The present state of the battery group loop. Options: 1. charge(1) - indicates that the present state of the battery group loop is charge 2. discharge(2) - indicates that the present state of the battery group loop is discharge 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.6.3.1.5 | INTEGER {invalid(-1), charge(1), discharge(2)} | read-only | current |
| hwBatteryCurrent OBJECT-TYPE Present current . Unit: mA | 1.3.6.1.4.1.2011.6.2.1.6.3.1.6 | MeasuresRange | read-only | current |
| hwBatteryTemperature OBJECT-TYPE The loop temperature of the battery group. Unit: degree | 1.3.6.1.4.1.2011.6.2.1.6.3.1.7 | Integer32 | read-only | current |
| hwBatteryRowStatus OBJECT-TYPE RowStatus standard operation | 1.3.6.1.4.1.2011.6.2.1.6.3.1.8 | RowStatus | read-write | current |
| hwBatteryCurrentHigh OBJECT-TYPE The over-current alarm point of the battery group. Unit: mA | 1.3.6.1.4.1.2011.6.2.1.6.3.1.9 | MeasuresRange | read-write | current |
| hwBatteryFuseState OBJECT-TYPE Battery fuse state. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.6.3.1.10 | INTEGER {invalid(-1), on(1), off(2)} | read-only | current |
| hwBatteryContactState OBJECT-TYPE The state of the battery contactor. Options: 1. on(1) - indicates that the contactor is connected 2. off(2) - indicates that the contactor is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | 1.3.6.1.4.1.2011.6.2.1.6.3.1.11 | INTEGER {invalid(-1), on(1), off(2)} | read-only | current |
| hwBatteryRemainCapacity OBJECT-TYPE Remain capacity of the battery | 1.3.6.1.4.1.2011.6.2.1.6.3.1.12 | Integer32 | read-only | current |
| hwBatteryProtectState OBJECT-TYPE Protection status of the battery. Options: 1. normal(1) - indicates that the Protection status of the battery is normal 2. overtemperature(2) - indicates that the Protection status of the battery is overtemperature 3. overCurrent(3) - indicates that the Protection status of the battery is overCurrent | 1.3.6.1.4.1.2011.6.2.1.6.3.1.13 | INTEGER {normal(1), overtemperature(2), overCurrent(3)} | read-only | current |
| hwBatteryVoltageState OBJECT-TYPE Voltage state of Battery. Options: 1. normal(1) - indicates that Voltage state of Battery is normal 2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage 3. belowVoltage(3) - indicates that Voltage state of Battery is belowVoltage | 1.3.6.1.4.1.2011.6.2.1.6.3.1.14 | INTEGER {normal(1), exceedVoltage(2), belowVoltage(3)} | read-only | current |
| hwBatteryHardwareState OBJECT-TYPE Hardware State of Battery. Options: 1. normal(1) - indicates that the hardware state of Battery is normal 2. fault(2) - indicates that the hardware state of Battery is fault | 1.3.6.1.4.1.2011.6.2.1.6.3.1.15 | INTEGER {normal(1), fault(2)} | read-only | current |
| hwBatteryTestTable OBJECT-TYPE Battery test table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.6.4 | not-accessible | current | |
| hwBatteryTestEntry OBJECT-TYPE Battery test table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.6.4.1 | not-accessible | current | |
| hwBatteryTestAdminStatus OBJECT-TYPE Battery test admin status. Options: 1. start(1) - indicates that the Battery starts testing 2. terminate(2) - indicates that the Battery terminates testing 3. enableAutoTest(3) - indicates that the Battery enables auto test function 4. disableAutoTest(4) - indicates that the Battery disables auto test function 5. timeautoTest(5) - indicates that the Battery enable timing auto test function 6. offautoTest(6) - indicates that the Battery enable off auto test function 7. timeoffautoTest(7) - indicates that the Battery enable timing+off auto test | 1.3.6.1.4.1.2011.6.2.1.6.4.1.1 | INTEGER {start(1), terminate(2), enableAutoTest(3), disableAutoTest(4), timeautoTest(5), offautoTest(6), timeoffautoTest(7)} | read-write | current |
| hwBatteryTestAutoDischargePeriod OBJECT-TYPE Auto discharge test period. Effective range is 30 -240 days. Default: 120 Unit: day | 1.3.6.1.4.1.2011.6.2.1.6.4.1.2 | Integer32 | read-write | current |
| hwBatteryTestResult OBJECT-TYPE Test result: Options: 1. testing(1) - indicates that the Battery test is in operation 2. complete(2) - indicates that the Battery test is completed normally 3. alarmTerminated(3) - indicates that the Battery test is stopped by alarms 4. hostTerminated(4) - indicates that the Battery test is stopped by the host 5. overtimeTerminated(5) - indicates that the Battery test is stopped because of over time 6. normal(6) - indicates that the Battery test is not started 7. supplyRecoverAutotestTerminated(7) - indicates that the Battery test is stopped because of supply recover | 1.3.6.1.4.1.2011.6.2.1.6.4.1.3 | INTEGER {testing(1), complete(2), alarmTerminated(3), hostTerminated(4), overtimeTerminated(5), normal(6), supplyRecoverAutotestTerminated(7)} | read-only | obsolete |
| hwBatteryTestStartTime OBJECT-TYPE Time of starting test | 1.3.6.1.4.1.2011.6.2.1.6.4.1.4 | DateAndTime | read-only | obsolete |
| hwBatteryTestDuration OBJECT-TYPE Battery discharge test duration . Effective range is 1C100 hours. Default :value is 10 hours Unit: hour | 1.3.6.1.4.1.2011.6.2.1.6.4.1.5 | Integer32 | read-write | current |
| hwBatteryTestTerminateVoltage OBJECT-TYPE Battery discharge test end voltage. Effective range (DC lack alarm voltage+0.5VCvoltage of floating charge). Default: 45600 Unit: mV | 1.3.6.1.4.1.2011.6.2.1.6.4.1.6 | Integer32 | read-write | current |
| hwBatteryTestTotalDischargeAH OBJECT-TYPE Total discharge AH. Unit: mAH | 1.3.6.1.4.1.2011.6.2.1.6.4.1.7 | Integer32 | read-only | obsolete |
| hwBatteryTestOperStatus OBJECT-TYPE Battery discharge test operate status. Options: 1. autoTestPermit(1) - indicates that auto discharge test is enabled 2. autoTestForbid(2) - indicates that auto discharge test is disabled 3. timeautoTestPermit(3) - indicates that timing auto discharge test is enabled 4. offautoTestPermit(4) - indicates that off auto discharge test is enabled 5. timeoffautoTestPermit(5) - indicates that timing-off auto discharge test is enabled | 1.3.6.1.4.1.2011.6.2.1.6.4.1.8 | INTEGER {autoTestPermit(1), autoTestForbid(2), timeautoTestPermit(3), offautoTestPermit(4), timeoffautoTestPermit(5)} | read-only | current |
| hwBatteryTestPhase OBJECT-TYPE Battery test phase. Options: 1. charge(1) - indicates the batter test phase is charge 2. discharge(2) - indicates the batter test phase is discharge 3. record(3) - indicates the power equipment recording test result 4. finish(4) - indicates that the discharge is complete 5.waitingfordischarge(5) - indicates that preparation is ready for discharge command | 1.3.6.1.4.1.2011.6.2.1.6.4.1.9 | INTEGER {charge(1), discharge(2), record(3), finish(4), waitingfordischarge(5)} | read-only | current |
| hwBatteryTestStartHour OBJECT-TYPE Discharge start time. Effective range is 0 23 Default: 0 Unit: hour | 1.3.6.1.4.1.2011.6.2.1.6.4.1.10 | Integer32 | read-write | current |
| hwBatteryTestAlarmThreshold OBJECT-TYPE The battery discharge test alarm threshold in ratio of the range:1~79. | 1.3.6.1.4.1.2011.6.2.1.6.4.1.11 | Integer32 | read-write | current |
| hwBatteryLogTestTable OBJECT-TYPE Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery. | 1.3.6.1.4.1.2011.6.2.1.6.5 | not-accessible | current | |
| hwBatteryLogTestEntry OBJECT-TYPE Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery. | 1.3.6.1.4.1.2011.6.2.1.6.5.1 | not-accessible | current | |
| hwBatteryLogTestIndex OBJECT-TYPE Battery discharge test result index | 1.3.6.1.4.1.2011.6.2.1.6.5.1.1 | Integer32 (0..255) | read-only | current |
| hwBatteryLogTestStartTime OBJECT-TYPE Battery discharge test start time | 1.3.6.1.4.1.2011.6.2.1.6.5.1.2 | DateAndTime | read-only | current |
| hwBatteryLogTestDischargeDuration OBJECT-TYPE Duration of discharge. Unit: minute | 1.3.6.1.4.1.2011.6.2.1.6.5.1.3 | Integer32 | read-only | current |
| hwBatteryLogTestTerminateVoltage OBJECT-TYPE End voltage of battery discharge test . Unit: mV | 1.3.6.1.4.1.2011.6.2.1.6.5.1.4 | Integer32 | read-only | current |
| hwBatteryLogTestBatteryStatus OBJECT-TYPE Battery status. Options: 1. expectant(1) - indicates the batter test state is expectant 2. unexpected(2) - indicates the batter test state is unexpected 3. unknown(3) - indicates the batter test state is unknown | 1.3.6.1.4.1.2011.6.2.1.6.5.1.5 | INTEGER {expectant(1), unexpected(2), unknown(3)} | read-only | current |
| hwBatteryLogTestTotalDischargeAH OBJECT-TYPE Discharge cumulate AH. Unit: mAH | 1.3.6.1.4.1.2011.6.2.1.6.5.1.6 | Integer32 | read-only | current |
| hwBatteryLogTestFinish OBJECT-TYPE Battery Test result. Options: 1. testing(1) - indicates that it is during testing 2. completed(2) - indicates that the test is completed normally 3. alarmTerminated(3) - indicates that the test is stopped by alarms 4. hostTerminated(4) - indicates that the test is stopped by the host 5. overtimeTerminated(5) - indicates that the test is stopped because of over 100 hours 6. notTest(6) - indicates that the test is not started | 1.3.6.1.4.1.2011.6.2.1.6.5.1.7 | INTEGER {testing(1), completed(2), alarmTerminated(3), hostTerminated(4), overtimeTerminated(5), notTest(6)} | read-only | current |
| hwBatteryLogTestEfficiency OBJECT-TYPE The information of battery test efficiency. | 1.3.6.1.4.1.2011.6.2.1.6.5.1.8 | Integer32 | read-only | current |
| hwBatteryLogTestBatteryTemperature OBJECT-TYPE Battery discharge test end Temperature. Unit: 0.01 Degree | 1.3.6.1.4.1.2011.6.2.1.6.5.1.9 | Integer32 | read-only | current |
| hwBatteryLogTestBatteryCurrent OBJECT-TYPE Battery discharge test average Current. Unit: mA | 1.3.6.1.4.1.2011.6.2.1.6.5.1.10 | Integer32 | read-only | current |
| hwRemoteProvidePowerInfoTable OBJECT-TYPE Remote provide power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.7 | not-accessible | current | |
| hwRemoteProvidePowerInfoEntry OBJECT-TYPE Remote provide power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | 1.3.6.1.4.1.2011.6.2.1.7.1 | not-accessible | current | |
| hwPowerCentralState OBJECT-TYPE State of the central module. Options: 1. normal(1) - indicates the normal state 2. temOver(2) - indicates the over-temperature | 1.3.6.1.4.1.2011.6.2.1.7.1.1 | INTEGER {normal(1), temOver(2)} | read-only | current |
| hwPowerCentralDCInPutState OBJECT-TYPE State of central module DC input: Options: 1.normal(1) - indicates the normal state 2.lack(2) - indicates the voltage underflow 3.over(3) - indicates the voltage overflow | 1.3.6.1.4.1.2011.6.2.1.7.1.2 | INTEGER {normal(1), lack(2), over(3)} | read-only | current |
| hwPowerCentralDCOutputState OBJECT-TYPE State of central module DC output. Options: 1. normal(1) - indicates the normal state 2. volLack(2) - indicates the voltage underflow 3. volOver(3) - indicates the voltage overflow 4. loadOver(4) - indicates the over-loading 5. shortCircuit(5) - indicates the short circuit 6. noLoad(6) - indicates no load | 1.3.6.1.4.1.2011.6.2.1.7.1.3 | INTEGER {normal(1), volLack(2), volOver(3), loadOver(4), shortCircuit(5), noLoad(6)} | read-only | current |
| hwPowerCentralDCOutputMode OBJECT-TYPE Mode of central module DC output. Options: 1. highVolMode(1) - indicates the high voltage output mode 2. lowVolMode(2) - indicates the low voltage output mode | 1.3.6.1.4.1.2011.6.2.1.7.1.4 | INTEGER {highVolMode(1), lowVolMode(2)} | read-only | current |
| hwPowerRemoteCommState OBJECT-TYPE Remote power module communications state. Options: 1. normal(1) - indicates the normal state 2. revfault(2) - indicates the receiving of fault 3. sendfault(3) - indicates the sending of fault | 1.3.6.1.4.1.2011.6.2.1.7.1.5 | INTEGER {normal(1), revfault(2), sendfault(3)} | read-write | current |
| hwPowerRemoteDCInputState OBJECT-TYPE State of remote module DC input. Options: 1. normal(1) - indicates the normal state 2. lack(2) - indicates that the voltage is underflow | 1.3.6.1.4.1.2011.6.2.1.7.1.6 | INTEGER {normal(1), lack(2)} | read-write | current |
| hwPowerRemoteLineCurState OBJECT-TYPE state of line between central and remote module. Options: 1.normal(1) - indicates the normal state 2.cablejoining(2) - indicates the cable joining 3.curLeakage(3) - indicates the cur Leakage 4.curOver(4) - indicates the cur Over | 1.3.6.1.4.1.2011.6.2.1.7.1.7 | INTEGER {normal(1), cablejoining(2), curLeakage(3), curOver(4)} | read-write | current |
| hwPowerRemotePowerState OBJECT-TYPE state of remote UA60 power. Options: 1. normal(1) - indicates the normal state 2. fault(2) - indicates the faulty state | 1.3.6.1.4.1.2011.6.2.1.7.1.8 | INTEGER {normal(1), fault(2)} | read-write | current |
| hwPowerRemoteLineState OBJECT-TYPE State of line U1. Options: 1. u1state(0) - indicates the power remote line state is u1 state 2. u2state(1) - indicates the power remote line state is u2 state 3. u3state(2) - indicates the power remote line state is u3 state 4. u4state(3) - indicates the power remote line state is u4 state 5. a1state(4) - indicates the power remote line state is a1 state 6. a2state(5) - indicates the power remote line state is a2 state 7. a3state(6) - indicates the power remote line state is a3 state 8. a4state(7) - indicates the power remote line state is a4 state | 1.3.6.1.4.1.2011.6.2.1.7.1.9 | Bits {u1state(0), u2state(1), u3state(2), u4state(3), a1state(4), a2state(5), a3state(6), a4state(7)} | read-write | current |
| hwPowerCentralLoadState OBJECT-TYPE state of central load. Options: 1. normal(1) - indicates the normal state 2. overload(2) - indicates overload 3. nonload(3) - indicates non-load | 1.3.6.1.4.1.2011.6.2.1.7.1.10 | INTEGER {normal(1), overload(2), nonload(3)} | read-write | current |
| hwACInfomationTable OBJECT-TYPE AC infomation table. The table is not supported. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. | 1.3.6.1.4.1.2011.6.2.1.8 | not-accessible | current | |
| hwACInfomationEntry OBJECT-TYPE AC infomation table. The table is not supported. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. | 1.3.6.1.4.1.2011.6.2.1.8.1 | not-accessible | current | |
| hwACInfoCommState OBJECT-TYPE communication state of AC input module. The node is not supported. Options: 1. normal(0) - indicates the communication state of AC is normal 2. fault(1) - indicates the communication state of AC is fault | 1.3.6.1.4.1.2011.6.2.1.8.1.1 | INTEGER {normal(0), fault(1)} | read-only | current |
| hwACInfoThunderState OBJECT-TYPE Thunder's state. The node is not supported. Options: 1. normal(0) - indicates the state of Thunder is normal 2. fault(1) - indicates the state of Thunder is fault | 1.3.6.1.4.1.2011.6.2.1.8.1.2 | INTEGER {normal(0), fault(1)} | read-only | current |
| hwACInfoCurrentLoop OBJECT-TYPE Current AC input working loop. The leaf is not supported. | 1.3.6.1.4.1.2011.6.2.1.8.1.3 | Integer32 | read-only | current |
| hwACInfoMCBTrigger OBJECT-TYPE AC input MCB trigger state. The leaf is not supported. Options: 1. normal(0) - indicates the AC input MCB trigger state is normal 2. break-down(1)- indicates the AC input MCB trigger state is break-down | 1.3.6.1.4.1.2011.6.2.1.8.1.4 | INTEGER {normal(0), break-down(1)} | read-only | current |
| hwACInfoFrequency OBJECT-TYPE The infomation of AC input frequency. This leaf is not supported. Unit: HZ | 1.3.6.1.4.1.2011.6.2.1.8.1.5 | Integer32 | read-only | current |
| hwACInfoRowStatus OBJECT-TYPE RowStatus standard operation The leaf is not supported. | 1.3.6.1.4.1.2011.6.2.1.8.1.6 | RowStatus | read-write | current |
| hwPowerMibTrap OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.2 | |||
| hwPowerTrapOid OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.2.1 | |||
| hwPowerTrapsDefine OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.2.2 | |||
| hwPowerTraps OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.2.2.0 | |||
| powerConformance OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.3 | |||
| powerCompliances OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.3.1 | |||
| powerGroups OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.3.2 | |||
| hwEnvironPowerTraps OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.4 | |||
| hwEnvironPowerCommonTraps OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.4.1 | |||
| hwEnvironPowerAlarmTraps OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.4.2 | |||
| hwEnvironPowerAlarmTrapsPrefix OBJECT-IDENTITY | 1.3.6.1.4.1.2011.6.2.4.2.0 |
Notifications
| Name | OID | Status |
|---|---|---|
| powerConnFaultAlarm NOTIFICATION-TYPE This trap message is reported when the communication between the power module and the monitoring board is fault. | 1.3.6.1.4.1.2011.6.2.2.2.0.1 | current |
| powerConnFaultAlarmResume NOTIFICATION-TYPE This trap message is reported when the communication between the power module and the monitoring board resumes. | 1.3.6.1.4.1.2011.6.2.2.2.0.2 | current |
| acInputVoltageAlarm NOTIFICATION-TYPE This trap message is reported when there is a exception of AC input voltage. | 1.3.6.1.4.1.2011.6.2.2.2.0.3 | current |
| acInputVoltageAlarmResume NOTIFICATION-TYPE This trap message is reported when the state of AC input voltage resumes. | 1.3.6.1.4.1.2011.6.2.2.2.0.4 | current |
| acInputVoltageHighAlarm NOTIFICATION-TYPE This trap message is reported when the input voltage is too high. | 1.3.6.1.4.1.2011.6.2.2.2.0.5 | current |
| acInputVoltageHighAlarmResume NOTIFICATION-TYPE This trap message is reported when the input voltage resumes to the normal range from a high value. | 1.3.6.1.4.1.2011.6.2.2.2.0.6 | current |
| acInputVoltageLowAlarm NOTIFICATION-TYPE This trap message is reported when the input voltage is too low. | 1.3.6.1.4.1.2011.6.2.2.2.0.7 | current |
| acInputVoltageLowAlarmResume NOTIFICATION-TYPE This trap message is reported when the input voltage resumes to the normal range from a low value. | 1.3.6.1.4.1.2011.6.2.2.2.0.8 | current |
| dcOutputVoltageHighAlarm NOTIFICATION-TYPE This trap message is reported when the output voltage is too high. | 1.3.6.1.4.1.2011.6.2.2.2.0.9 | current |
| dcOutputVoltageHighAlarmResume NOTIFICATION-TYPE This trap message is reported when the output voltage resumes to the normal range from a high value. | 1.3.6.1.4.1.2011.6.2.2.2.0.10 | current |
| dcOutputCurrentHighAlarm NOTIFICATION-TYPE This trap message is reported when the output current is too high. | 1.3.6.1.4.1.2011.6.2.2.2.0.11 | current |
| dcOutputCurrentHighAlarmResume NOTIFICATION-TYPE This trap message is reported when the output current resumes to the normal range from a high value. | 1.3.6.1.4.1.2011.6.2.2.2.0.12 | current |
| dcOutputVoltageLowAlarm NOTIFICATION-TYPE This trap message is reported when the output voltage is too low. | 1.3.6.1.4.1.2011.6.2.2.2.0.13 | current |
| dcOutputVoltageLowAlarmResume NOTIFICATION-TYPE This trap message is reported when the output voltage resumes to the normal range from a low value. | 1.3.6.1.4.1.2011.6.2.2.2.0.14 | current |
| dcOutputCurrentLowAlarm NOTIFICATION-TYPE This trap message is reported when the output current is too low. | 1.3.6.1.4.1.2011.6.2.2.2.0.15 | current |
| dcOutputCurrentLowAlarmResume NOTIFICATION-TYPE This trap message is reported when the output current resumes to the normal range from a low value. | 1.3.6.1.4.1.2011.6.2.2.2.0.16 | current |
| overLoadPowerAbnormalAlarm NOTIFICATION-TYPE This trap message is reported when the state of load power is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.17 | current |
| overLoadPowerAbnormalAlarmResume NOTIFICATION-TYPE This trap message is reported when the state of load power recovers to normal. | 1.3.6.1.4.1.2011.6.2.2.2.0.18 | current |
| overBattPowerOffAlarm NOTIFICATION-TYPE This trap message is reported when the battery is powered off. | 1.3.6.1.4.1.2011.6.2.2.2.0.19 | current |
| overBattPowerOffAlarmResume NOTIFICATION-TYPE This trap message is reported when the battery is powered on. | 1.3.6.1.4.1.2011.6.2.2.2.0.20 | current |
| overLoadPowerOffAlarm NOTIFICATION-TYPE This trap message is reported when the loadpower is powered off. | 1.3.6.1.4.1.2011.6.2.2.2.0.21 | current |
| overLoadPowerOffAlarmResume NOTIFICATION-TYPE This trap message is reported when the loadpower is powered on. | 1.3.6.1.4.1.2011.6.2.2.2.0.22 | current |
| acMainsSupplyAlarm NOTIFICATION-TYPE This trap message is reported when the AC mains supply is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.23 | current |
| acMainsSupplyAlarmResume NOTIFICATION-TYPE This trap message is reported when the AC mains supply recovers to normal. | 1.3.6.1.4.1.2011.6.2.2.2.0.24 | current |
| batteryLoopAlarm NOTIFICATION-TYPE This trap message is reported when the loop of battery group disconnects. | 1.3.6.1.4.1.2011.6.2.2.2.0.25 | current |
| batteryLoopAlarmResume NOTIFICATION-TYPE This trap message is reported when the loop of battery group connects. | 1.3.6.1.4.1.2011.6.2.2.2.0.26 | current |
| batteryFuseAlarm NOTIFICATION-TYPE This trap message is reported when the fuse of battery group disconnects. | 1.3.6.1.4.1.2011.6.2.2.2.0.27 | current |
| batteryFuseAlarmResume NOTIFICATION-TYPE This trap message is reported when the fuse of battery group connects. | 1.3.6.1.4.1.2011.6.2.2.2.0.28 | current |
| batteryContachAlarm NOTIFICATION-TYPE This trap message is reported when the contactor of battery group disconnects. | 1.3.6.1.4.1.2011.6.2.2.2.0.29 | current |
| batteryContachAlarmResume NOTIFICATION-TYPE This trap message is reported when the contactor of battery group connects. | 1.3.6.1.4.1.2011.6.2.2.2.0.30 | current |
| userModuleOffAlarm NOTIFICATION-TYPE This trap message is reported when the user module is powered off. | 1.3.6.1.4.1.2011.6.2.2.2.0.31 | current |
| userModuleOffAlarmResume NOTIFICATION-TYPE This trap message is reported when the user module is powered on. | 1.3.6.1.4.1.2011.6.2.2.2.0.32 | current |
| transferModuleOffAlarm NOTIFICATION-TYPE This trap message is reported when the transfer module is powered off. | 1.3.6.1.4.1.2011.6.2.2.2.0.33 | current |
| transferModuleOffAlarmResume NOTIFICATION-TYPE This trap message is reported when the transfer module is powered on. | 1.3.6.1.4.1.2011.6.2.2.2.0.34 | current |
| userModuleSwitchAlarm NOTIFICATION-TYPE This trap message is reported when the user module is switched off. | 1.3.6.1.4.1.2011.6.2.2.2.0.35 | current |
| transferModuleSwitchAlarm NOTIFICATION-TYPE This trap message is reported when the transfer module is switched off. | 1.3.6.1.4.1.2011.6.2.2.2.0.37 | current |
| loadFuseAlarm NOTIFICATION-TYPE This trap message is reported when the load fuse is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.39 | current |
| loadFuseAlarmResume NOTIFICATION-TYPE This trap message is reported when the load fuse resumes. | 1.3.6.1.4.1.2011.6.2.2.2.0.40 | current |
| chargeCtrlStateAlarm NOTIFICATION-TYPE This trap message is reported when the control state of average or floating charge converts. | 1.3.6.1.4.1.2011.6.2.2.2.0.41 | current |
| chargeModeAlarm NOTIFICATION-TYPE This trap message is reported when the charge state converts. | 1.3.6.1.4.1.2011.6.2.2.2.0.42 | current |
| acCommFailAlarm NOTIFICATION-TYPE This trap message is reported when the AC panel communication fails. | 1.3.6.1.4.1.2011.6.2.2.2.0.43 | current |
| acCommFailAlarmResume NOTIFICATION-TYPE This trap message is reported when the AC panel communication resumes. | 1.3.6.1.4.1.2011.6.2.2.2.0.44 | current |
| batteryChargeOverAlarm NOTIFICATION-TYPE This trap message is reported when the Over-current of battery group happens. | 1.3.6.1.4.1.2011.6.2.2.2.0.45 | current |
| batteryChargeOverAlarmResume NOTIFICATION-TYPE OThis trap message is reported when the Over-current of battery group resumes. | 1.3.6.1.4.1.2011.6.2.2.2.0.46 | current |
| batteryVoltageLackAlarm NOTIFICATION-TYPE This trap message is reported when the voltage of battery group lacks. | 1.3.6.1.4.1.2011.6.2.2.2.0.47 | current |
| batteryVoltageLackAlarmResume NOTIFICATION-TYPE This trap message is reported when the voltage of battery group recovers from lack. | 1.3.6.1.4.1.2011.6.2.2.2.0.48 | current |
| loadTwiceOffAlarm NOTIFICATION-TYPE This trap message is reported when the load is powered off twice. | 1.3.6.1.4.1.2011.6.2.2.2.0.49 | current |
| loadTwiceOffAlarmResume NOTIFICATION-TYPE This trap message is reported when the load recovers from powering off twice. | 1.3.6.1.4.1.2011.6.2.2.2.0.50 | current |
| loadOnceOffAlarm NOTIFICATION-TYPE This trap message is reported when the load is powered off once. | 1.3.6.1.4.1.2011.6.2.2.2.0.51 | current |
| loadOnceOffAlarmResume NOTIFICATION-TYPE This trap message is reported when the load recovers from powering off once. | 1.3.6.1.4.1.2011.6.2.2.2.0.52 | current |
| acInputPowerOffAlarm NOTIFICATION-TYPE This trap message is reported when the AC input is powered off. | 1.3.6.1.4.1.2011.6.2.2.2.0.53 | current |
| acInputPowerOffAlarmResume NOTIFICATION-TYPE This trap message is reported when the AC input power is powered off. | 1.3.6.1.4.1.2011.6.2.2.2.0.54 | current |
| acInputLoopSwtichAlarm NOTIFICATION-TYPE This trap message is reported when the AC input loop switches to another one. | 1.3.6.1.4.1.2011.6.2.2.2.0.55 | current |
| batteryDischargeTestStartAlarm NOTIFICATION-TYPE This trap message is reported when the battery discharge test starts. | 1.3.6.1.4.1.2011.6.2.2.2.0.56 | current |
| batteryDischargeTestStopAlarm NOTIFICATION-TYPE This trap message is reported when the battery discharge test stops. | 1.3.6.1.4.1.2011.6.2.2.2.0.57 | current |
| powerProtectAlarm NOTIFICATION-TYPE This trap message is reported when the power protection function is enbaled. | 1.3.6.1.4.1.2011.6.2.2.2.0.58 | current |
| powerUndoProtectAlarm NOTIFICATION-TYPE This trap message is reported when the power protection function is disabled. | 1.3.6.1.4.1.2011.6.2.2.2.0.59 | current |
| powerCentralOutputModeSwtichAlarm NOTIFICATION-TYPE This trap message is reported when the central output mode swtiches to another one. | 1.3.6.1.4.1.2011.6.2.2.2.0.60 | current |
| powerCentralTempretaureAlarm NOTIFICATION-TYPE This trap message is reported when the central tempretaure is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.61 | current |
| powerCentralInputAlarm NOTIFICATION-TYPE This trap message is reported when the central input voltage is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.62 | current |
| powerCentralOutputAlarm NOTIFICATION-TYPE This trap message is reported when the central output voltage is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.63 | current |
| powerRemoteCommFaultAlarm NOTIFICATION-TYPE This trap message is reported when the communiction between the remote and central fails. | 1.3.6.1.4.1.2011.6.2.2.2.0.64 | current |
| powerRemoteVoltageAlarm NOTIFICATION-TYPE This trap message is reported when the remote voltage is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.65 | current |
| powerLineAlarm NOTIFICATION-TYPE This trap message is reported when the power line is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.66 | current |
| powerRemotePowerAlarm1 NOTIFICATION-TYPE This trap message is reported when the remote power is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.67 | current |
| powerRemotePowerAlarm2 NOTIFICATION-TYPE This trap message is reported when the Line UA is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.68 | current |
| powerRemotePowerAlarm3 NOTIFICATION-TYPE This trap message is reported when the Central load is abnormal. | 1.3.6.1.4.1.2011.6.2.2.2.0.69 | current |
| hwEmmPowerBattaryTestStartTrap NOTIFICATION-TYPE The agent generates this trap when the power device battary discharge test starts. | 1.3.6.1.4.1.2011.6.2.4.2.0.1 | current |
| hwEmmPowerBattaryTestStopTrap NOTIFICATION-TYPE The agent generates this trap when the power device battary discharge test ends. | 1.3.6.1.4.1.2011.6.2.4.2.0.2 | current |
| hwEmmPowerAcvolFaultTrap NOTIFICATION-TYPE The agent generates this trap when the power device AC input voltage is abnormal. | 1.3.6.1.4.1.2011.6.2.4.2.0.3 | current |
| hwEmmPowerAcvolRecoverTrap NOTIFICATION-TYPE The agent generates this trap when the power device AC input voltage recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.4 | current |
| hwEmmPowerDcvolFaultTrap NOTIFICATION-TYPE The agent generates this trap when the power device DC output voltage is abnormal. | 1.3.6.1.4.1.2011.6.2.4.2.0.5 | current |
| hwEmmPowerDcvolRecoverTrap NOTIFICATION-TYPE The agent generates this trap when the power device DC output voltage recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.6 | current |
| hwEmmPowerBattloopFaultTrap NOTIFICATION-TYPE The agent generates this trap when the power device the battery loop is broken. In this case, the function of he backup power is lost. | 1.3.6.1.4.1.2011.6.2.4.2.0.7 | current |
| hwEmmPowerBattloopRecoverTrap NOTIFICATION-TYPE The agent generates this trap when the power device battery loop recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.8 | current |
| hwEmmPowerLoadfuseFaultTrap NOTIFICATION-TYPE The agent generates this trap when the fuse of the power device is broken. In this case, the device is powered off. | 1.3.6.1.4.1.2011.6.2.4.2.0.9 | current |
| hwEmmPowerLoadfuseRecoverTrap NOTIFICATION-TYPE The agent generates this trap when the fuse of the power device recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.10 | current |
| hwEmmPowerRectifierFaultTrap NOTIFICATION-TYPE The agent generates this trap when the rectifier module of the power device is abnormal and the spully power may decrease. | 1.3.6.1.4.1.2011.6.2.4.2.0.11 | current |
| hwEmmPowerRectifierRecoverTrap NOTIFICATION-TYPE The agent generates this trap when the rectifier module of the power device recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.12 | current |
| hwEmmDigMainsupplyFaultTrap NOTIFICATION-TYPE The agent generates this trap when the main supply digital is faulty. | 1.3.6.1.4.1.2011.6.2.4.2.0.13 | current |
| hwEmmDigMainsupplyRecoverTrap NOTIFICATION-TYPE The agent generates this trap when the main supply digital recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.14 | current |
| hwEmmPowerBatteryOffTrap NOTIFICATION-TYPE The agent generates this trap when the power of battary is off. | 1.3.6.1.4.1.2011.6.2.4.2.0.15 | current |
| hwEmmBatt1TempFaultTrap NOTIFICATION-TYPE The agent generates this trap when the battery group 1 temperature sensor fault occurs. | 1.3.6.1.4.1.2011.6.2.4.2.0.16 | current |
| hwEmmBatt1TempRestoreTrap NOTIFICATION-TYPE The agent generates this trap when the battery group 1 temperature sensor fault recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.17 | current |
| hwEmmEnviHumFaultTrap NOTIFICATION-TYPE The agent generates this trap when the environment humidity sensor fault occurs. | 1.3.6.1.4.1.2011.6.2.4.2.0.18 | current |
| hwEmmEnviHumRestoreTrap NOTIFICATION-TYPE The agent generates this trap when the environment humidity sensor fault recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.19 | current |
| hwEmmEnvi1TempFaultTrap NOTIFICATION-TYPE The agent generates this trap when the environment 1 temperature sensor fault occurs. | 1.3.6.1.4.1.2011.6.2.4.2.0.20 | current |
| hwEmmEnvi1TempRestoreTrap NOTIFICATION-TYPE The agent generates this trap when the environment 1 temperature sensor fault recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.21 | current |
| hwEmmBattTemFaultTrap NOTIFICATION-TYPE The agent generates this trap when the battery temperature out of normal range. | 1.3.6.1.4.1.2011.6.2.4.2.0.22 | current |
| hwEmmBattTemRecoverTrap NOTIFICATION-TYPE The agent generates this trap when the battery temperature recovers to normal range. | 1.3.6.1.4.1.2011.6.2.4.2.0.23 | current |
| hwEmmPowerBatteryOffRecoverTrap NOTIFICATION-TYPE The agent generates this trap when the power of battary recovers to on state. | 1.3.6.1.4.1.2011.6.2.4.2.0.24 | current |
| hwEmmPowerBatteryUnDetectTrap NOTIFICATION-TYPE The agent generates this trap when the one or more batteries are not detected. | 1.3.6.1.4.1.2011.6.2.4.2.0.25 | current |
| hwEmmPowerBatteryDetectRecoverTrap NOTIFICATION-TYPE The agent generates this trap when the batteries recover. | 1.3.6.1.4.1.2011.6.2.4.2.0.26 | current |
| hwPowerModuleMismatchTrap NOTIFICATION-TYPE The agent generates this trap when the the power supply system detects mismatched power module . | 1.3.6.1.4.1.2011.6.2.4.2.0.27 | current |
| hwPowerModuleRestoreTrap NOTIFICATION-TYPE The agent generates this trap when the power module recovers. | 1.3.6.1.4.1.2011.6.2.4.2.0.28 | current |