2013-12-28 00:00, 2013-11-16 00:00, 2012-12-28 00:00, 2012-12-14 00:00, 2012-07-24 00:00, 2012-06-25 00:00, 2012-01-09 00:00, 2011-12-17 00:00, 2011-12-08 00:00, 2011-08-17 00:00, 2011-03-16 00:00, 2010-12-17 00:00, 2010-11-10 00:00, 2010-07-18 09:00, 2010-06-12 09:00, 2010-04-21 09:00, 2010-04-08 09:00, 2010-03-09 09:00, 2010-02-06 09:00, 2010-01-29 09:00, 2006-11-10 09:00, 2006-10-25 09:00
Namespace
huawei
Source file
HUAWEI-POWER-MIB
Digest
sha256:c67abe53fa1754b27a7f09d46314046d66065b7842c7dbae006bf3d7eb4ede63

Description

This MIB is used for defining Power Monitor management MIB objects.

Contact

Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China Website: http://www.huawei.com Email: support@huawei.com

Imports

FromSymbols
HUAWEI-DEVICE-MIBhwFrameIndex
HUAWEI-ENVIRONMENT-MIBhwDigChannelIndex, hwEnvEmuIndex, hwEnvEmuType
HUAWEI-MIBhuaweiUtility
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIInteger32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso
SNMPv2-TCDateAndTime, DisplayString, RowStatus, TEXTUAL-CONVENTION, TruthValue

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

HCNUM-TC
HUAWEI-DEVICE-MIB
HUAWEI-ENVIRONMENT-MIB
HUAWEI-MIB
HUAWEI-POWER-MIB
HUAWEI-TC-MIB
IANAifType-MIB
IF-MIB
INET-ADDRESS-MIB
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC

Textual conventions

NameOIDSyntaxAccessStatus
MeasuresRange
TEXTUAL-CONVENTION
Basic unit of measure: 1.pressure:indicated by mV, 1V = 1000 mV 2.current:indicated by mA, 1A = 1000 mA 3.temperature: indicated by 1% degree centigrade
current

Objects

NameOIDSyntaxAccessStatus
hwPowerMonObjects
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.1
hwPowerSysInfoTable
OBJECT-TYPE
Power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.1not-accessiblecurrent
hwPowerSysInfoEntry
OBJECT-TYPE
Power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.1.1not-accessiblecurrent
hwPowerIndex
OBJECT-TYPE
Index of the power supply monitored by the monitoring unit
1.3.6.1.4.1.2011.6.2.1.1.1.1Integer32 (0..255)read-onlycurrent
hwPowerType
OBJECT-TYPE
Type of the Power emu device. Options: 1.power4875(1) - Type of the Power emu device is power4875 2.power4810(2) - Type of the Power emu device is power4810 3.power48100(3) - Type of the Power emu device is power48100 4.power4850(4) - Type of the Power emu device is power4850 5.power48240(5) - Type of the Power emu device is power48240 6.power48120(6) - Type of the Power emu device is power48120 7.power48300(7) - Type of the Power emu device is power48300 8.power48240SinglePhase(8) - Type of the Power emu device is power48240SinglePhase 9.universalPower(9) - Type of the Power emu device is universalPower 10.power4845(10) - Type of the Power emu device is power4845 11.rpower(11) - Type of the Power emu device is rpower 12.power4805(15) - Type of the Power emu device is power4805 13.power4820(16) - Type of the Power emu device is power4820 14.onps(17) - Type of the Power emu device is onps 15.power4875l(18) - Type of the Power emu device is power4875l 16.psma(100) - Type of the Power emu device is psma 17.perm-al175nt(101) - Type of the Power emu device is perm-al175nt 18.mcs1800(102) - Type of the Power emu device is mcs1800 19.mcs1800A(103) - Type of the Power emu device is mcs1800A 20.mcs3000(104) - Type of the Power emu device is mcs3000 21.sm40sm60(105) - Type of the Power emu device is sm40sm60 22.scu(106) - Type of the Power emu device is scu 23.eltek(107) - Type of the Power emu device is eltek 24.dk04(108) - Type of the Power emu device is dk04 25.dk04C(109) - Type of the Power emu device is dk04C 26.dpc(110) - Type of the Power emu device is dpc 27.power4830(120) - Type of the Power emu device is power4830 28.h831pmua(121) - Type of the Power emu device is h831pmua 29.power3000(122) - Type of the Power emu device is power3000 30.liFeBattery(123) - Type of the Power emu device is LiFeBattery 31.etp4830(125), - Type of SMU Power emu device is etp4830 32.etp4890(126), - Type of SMU Power emu device is etp4890 33.h801pmu(127), - Type of the Power emu device is h801pmua 34.etp48150(128), - Type of SMU Power emu device is etp48150 35.other(255) - other Power Type
1.3.6.1.4.1.2011.6.2.1.1.1.2INTEGER {power4875(1), power4810(2), power48100(3), power4850(4), power48240(5), power48120(6), power48300(7), power48240SinglePhase(8), universalPower(9), power4845(10), rpower(11), power4805(15), power4820(16), onps(17), power4875l(18), psma(100), perm-al175nt(101), mcs1800(102), mcs1800A(103), mcs3000(104), sm40sm60(105), scu(106), eltek(107), dk04(108), dk04C(109), dpc(110), power4830(120), h831pmua(121), power3000(122), liFeBattery(123), etp4830(125), etp4890(126), h801pmu(127), etp48150(128), other(255)}read-writecurrent
hwPowerName
OBJECT-TYPE
Power name.
1.3.6.1.4.1.2011.6.2.1.1.1.3DisplayStringread-writecurrent
hwPowerState
OBJECT-TYPE
Power board status: Refers to the status of communication between the internal monitor board of the power device and the external upper board. Options: 1.normal(1) - indicates the normal state 2.fault(2) - indicates the faulty state 3.protecting(3)- indicates that the backup power supply works in the protection state 4.switched(4) - indicates that the main power supply is faulty, and is protected by backup power supply 5.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.1.1.4INTEGER {invalid(-1), normal(1), fault(2), protecting(3), switched(4)}read-onlycurrent
hwPowerRowStatus
OBJECT-TYPE
RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
1.3.6.1.4.1.2011.6.2.1.1.1.5RowStatusread-writecurrent
hwPowerControlMode
OBJECT-TYPE
Control mode of the power monitor module. Options: 1.manualControl(1) - control by manual, the remote mode 2.autoControl(2) - auto control mode, the default is auto control mode 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.1.1.6INTEGER {invalid(-1), manualControl(1), autoControl(2)}read-writecurrent
hwPowerRemoteFrameID
OBJECT-TYPE
Apply for remote power system. It is the frame ID that the remote unit exists in
1.3.6.1.4.1.2011.6.2.1.1.1.7Integer32 (0..255)read-writecurrent
hwPowerProtect
OBJECT-TYPE
Apply for remote power system. It is used to enable or disable N+1 protection function. Options: 1.protect(1) - enables the N+1 protection function 2.undoProtect(2) - disables the N+1 protection function
1.3.6.1.4.1.2011.6.2.1.1.1.8INTEGER {protect(1), undoProtect(2)}read-writecurrent
hwPowerVersion
OBJECT-TYPE
Version of power
1.3.6.1.4.1.2011.6.2.1.1.1.9DisplayStringread-onlycurrent
hwPowerSupplyState
OBJECT-TYPE
Power supply modes. Options: 1.ac(1) - indicates the AC power supply 2.battery(2) - indicates power supply by the batteries
1.3.6.1.4.1.2011.6.2.1.1.1.10INTEGER {ac(1), battery(2)}read-onlycurrent
hwACInputTable
OBJECT-TYPE
AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.2not-accessiblecurrent
hwACInputEntry
OBJECT-TYPE
AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.2.1not-accessiblecurrent
hwACLoopIndex
OBJECT-TYPE
Input loop index. There are two channels of AC current input, which are the backup for each other.
1.3.6.1.4.1.2011.6.2.1.2.1.1Integer32 (0..255)read-onlycurrent
hwACPowerState
OBJECT-TYPE
Status of power supply. Options: 1.normal(1) - indicates that the power supply is normal 2.offline(2) - indicates that the power supply is offline 3.exceedVoltage(3) - indicates that the power supply is overvoltage 4.belowVoltage(4) - indicates that the power supply is undervoltage 5.backup(5) - indicates that the power supply is not supported currently 6.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.2.1.2INTEGER {invalid(-1), normal(1), offline(2), exceedVoltage(3), belowVoltage(4), backup(5)}read-onlycurrent
hwACVoltA
OBJECT-TYPE
AC Inuput voltage A. Unit: mV
1.3.6.1.4.1.2011.6.2.1.2.1.3MeasuresRangeread-onlycurrent
hwACCurrentA
OBJECT-TYPE
AC input Current A. Unit: mA
1.3.6.1.4.1.2011.6.2.1.2.1.4MeasuresRangeread-onlycurrent
hwACVoltB
OBJECT-TYPE
AC input voltage B. Unit: mv
1.3.6.1.4.1.2011.6.2.1.2.1.5MeasuresRangeread-onlycurrent
hwACCurrentB
OBJECT-TYPE
AC input current B. Unit: mA
1.3.6.1.4.1.2011.6.2.1.2.1.6MeasuresRangeread-onlycurrent
hwACVoltC
OBJECT-TYPE
AC input voltage C. Unit: mV
1.3.6.1.4.1.2011.6.2.1.2.1.7MeasuresRangeread-onlycurrent
hwACCurrentC
OBJECT-TYPE
AC input current C. Unit: mA
1.3.6.1.4.1.2011.6.2.1.2.1.8MeasuresRangeread-onlycurrent
hwACVoltageHigh
OBJECT-TYPE
AC input over-voltage alarm threshold. Unit: mV
1.3.6.1.4.1.2011.6.2.1.2.1.9MeasuresRangeread-writecurrent
hwACVoltageLow
OBJECT-TYPE
AC input under-voltage alarm threshold. Unit: mV
1.3.6.1.4.1.2011.6.2.1.2.1.10MeasuresRangeread-writecurrent
hwACRowStatus
OBJECT-TYPE
Only the add operation, delete operation, and status query operation are supported.
1.3.6.1.4.1.2011.6.2.1.2.1.11RowStatusread-writecurrent
hwACVoltageAState
OBJECT-TYPE
Phase AB/A of AC input state. Options: 1. normal(0) - indicates that the Phase AB/A of AC input state is normal 2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase AB/A of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase AB/A of AC input state is missing-phase
1.3.6.1.4.1.2011.6.2.1.2.1.12INTEGER {normal(0), belowVoltage(1), exceedVoltage(2), missing-phase(3)}read-onlycurrent
hwACVoltageBState
OBJECT-TYPE
Phase BC/B of AC input state. Options: 1. normal(0) - indicates that the Phase BC/B of AC input state is normal 2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase BC/B of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase BC/B of AC input state is missing-phase
1.3.6.1.4.1.2011.6.2.1.2.1.13INTEGER {normal(0), belowVoltage(1), exceedVoltage(2), missing-phase(3)}read-onlycurrent
hwACVoltageCState
OBJECT-TYPE
Phase CA/C of AC input state. Options: 1. normal(0) - indicates that the Phase CA/C of AC input state is normal 2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase CA/C of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase CA/C of AC input state is missing-phase
1.3.6.1.4.1.2011.6.2.1.2.1.14INTEGER {normal(0), belowVoltage(1), exceedVoltage(2), missing-phase(3)}read-onlycurrent
hwDCOutTable
OBJECT-TYPE
DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.3not-accessiblecurrent
hwDCOutEntry
OBJECT-TYPE
DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.3.1not-accessiblecurrent
hwDCVoltageOut
OBJECT-TYPE
DC voltage output. Unit: mV
1.3.6.1.4.1.2011.6.2.1.3.1.1MeasuresRangeread-onlycurrent
hwDCCurrentOut
OBJECT-TYPE
DC current output. Unit: mA
1.3.6.1.4.1.2011.6.2.1.3.1.2MeasuresRangeread-onlycurrent
hwDCVoltageOutHigh
OBJECT-TYPE
Output DC exceed-voltage alarm point. Default: 58000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.3.1.3MeasuresRangeread-writecurrent
hwDCVoltageOutLow
OBJECT-TYPE
Output DC below-voltage alarm point . Default value is 45V. Unit: mV
1.3.6.1.4.1.2011.6.2.1.3.1.4MeasuresRangeread-writecurrent
hwDCVoltageOutState
OBJECT-TYPE
DC output voltage status. Options: 1. normal(1) - indicates that the DC output voltage state is normal 2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage 3. belowVoltage(3) - indicates that the DC output voltage state is belowVoltage 4.invalid(-1) - indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.3.1.5INTEGER {invalid(-1), normal(1), exceedVoltage(2), belowVoltage(3)}read-onlydeprecated
hwDCCurrentOutHigh
OBJECT-TYPE
Output DC exceed-current alarm point . Unit: mA
1.3.6.1.4.1.2011.6.2.1.3.1.6MeasuresRangeread-writecurrent
hwDCCurrentOutLow
OBJECT-TYPE
Output below-current alarm point . Unit: mA
1.3.6.1.4.1.2011.6.2.1.3.1.7MeasuresRangeread-writecurrent
hwDCCurrentOutState
OBJECT-TYPE
DC output current status. Options: 1.normal(1) - indicates that the DC output current state is normal 2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage 3.belowVoltage(3) - indicates that the DC output current state is belowVoltage 4.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.3.1.8INTEGER {invalid(-1), normal(1), exceedVoltage(2), belowVoltage(3)}read-onlydeprecated
hwDCOutRowStatus
OBJECT-TYPE
RowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.3.1.9RowStatusread-writecurrent
hwDCOutLoadCurrent
OBJECT-TYPE
Total load current of DC output . Unit: mA
1.3.6.1.4.1.2011.6.2.1.3.1.10MeasuresRangeread-onlycurrent
hwDCOutLoadTmpHigh
OBJECT-TYPE
The off protection point under the load temperature, by default, it is 65 degrees centigrade. Unit: 0.01 degree
1.3.6.1.4.1.2011.6.2.1.3.1.11MeasuresRangeread-writecurrent
hwDCOutRunState
OBJECT-TYPE
DC output running status. Options: 1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current 2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current 3.batteryVoltageOver(2) - indicates output over-voltage 4.batteryVoltageLack(3) - indicates battery lack-voltage 5.loadOff(4) - indicates load off twice 6.batteryOff(5) - indictes battery protection (off once) 7.communicationFailure(6) - indicates that the communication fails 8.dcOutManual(7) - indicates DC by manual
1.3.6.1.4.1.2011.6.2.1.3.1.12Bits {battery1ChargeCurOver(0), battery2ChargeCurOver(1), batteryVoltageOver(2), batteryVoltageLack(3), loadOff(4), batteryOff(5), communicationFailure(6), dcOutManual(7)}read-onlycurrent
hwDCCommunicationState
OBJECT-TYPE
DC communication status. Options: 1.normal(0) - indicates that the DC communication state is normal 2.fault(1) - indicates that the DC communication state is fault
1.3.6.1.4.1.2011.6.2.1.3.1.13INTEGER {normal(0), fault(1)}read-onlycurrent
hwLoadinfoTable
OBJECT-TYPE
Load information table. Through this table, the load parameter can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load.
1.3.6.1.4.1.2011.6.2.1.4not-accessiblecurrent
hwLoadinfoEntry
OBJECT-TYPE
Load information table. Through this table, the load parameter can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load.
1.3.6.1.4.1.2011.6.2.1.4.1not-accessiblecurrent
hwLoadIndex
OBJECT-TYPE
Loop index: usually each DC output loop corresponds to a load.
1.3.6.1.4.1.2011.6.2.1.4.1.1Integer32 (0..255)read-onlycurrent
hwLoadInfoAdminState
OBJECT-TYPE
Load operation. Options: 1. on(1) - indicates that the Load is enabled 2. off(2) - indicates that the Load is disabled 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.4.1.2INTEGER {invalid(-1), on(1), off(2)}read-writecurrent
hwLoadInfoOperStatus
OBJECT-TYPE
Status of power supply. Options: 1. normal(1) - indicates that the state of power supply is normal 2. abnormal(2) - indicates that the state of power supply is abnormal 3. stop(3) - indicates that the state of power supply is stopping power supply 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.4.1.3INTEGER {invalid(-1), normal(1), abnormal(2), stop(3)}read-onlycurrent
hwLoadCurrent
OBJECT-TYPE
Present current . Unit: mA
1.3.6.1.4.1.2011.6.2.1.4.1.4MeasuresRangeread-onlycurrent
hwLoadVoltage
OBJECT-TYPE
Present voltage . Unit: mV
1.3.6.1.4.1.2011.6.2.1.4.1.5MeasuresRangeread-onlycurrent
hwLoadVoltageHigh
OBJECT-TYPE
Off voltage (Stop external voltage), in unit of mV, When DC output voltage exceeds the value, the load will be automatically cut off. Default: 43500 Unit: mV
1.3.6.1.4.1.2011.6.2.1.4.1.6MeasuresRangeread-writecurrent
hwLoadLoadName
OBJECT-TYPE
Load name: usually each DC output loop corresponds to a load.
1.3.6.1.4.1.2011.6.2.1.4.1.7DisplayStringread-writecurrent
hwLoadInfoRowStatus
OBJECT-TYPE
RowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.4.1.8RowStatusread-writecurrent
hwLoadFuseState
OBJECT-TYPE
Load fuse state, including the auxiliary load fuse. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.4.1.9INTEGER {invalid(-1), on(1), off(2)}read-onlycurrent
hwLoadHoreIndex
OBJECT-TYPE
load hore index
1.3.6.1.4.1.2011.6.2.1.4.1.10Integer32 (0..255)read-writecurrent
hwRectifierTable
OBJECT-TYPE
Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply.
1.3.6.1.4.1.2011.6.2.1.5not-accessiblecurrent
hwRectifierEntry
OBJECT-TYPE
Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply.
1.3.6.1.4.1.2011.6.2.1.5.1not-accessiblecurrent
hwRectifierIndex
OBJECT-TYPE
Rectifier Module index. There are multiple rectifier modules to a power source.
1.3.6.1.4.1.2011.6.2.1.5.1.1Integer32 (0..255)read-onlycurrent
hwRectifierAdminState
OBJECT-TYPE
Switch operation of rectifier module. Options: 1.on(1) - indicates that the Rectifier module is enabled 2.off(2) - indicates that the Rectifier module is disabled 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.5.1.2INTEGER {invalid(-1), on(1), off(2)}read-writecurrent
hwRectifierOperState
OBJECT-TYPE
Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device. Options: 1. normal(1) - indicates that the Rectifier operation state is normal 2. fault(2) - indicates that the Rectifier operation state is fault 3. protect(3) - indicates that the Rectifier operation state is protect 4. communicationFailure(4) - indicates that the Rectifier operation state is communicationFailure 5. on(5) - indicates that the Rectifier operation state is on 6. noConfig(6) - indicates that the Rectifier operation state is not Configured 7. offline(7) - indicates that the Rectifier operation state is offline 8. close(8) - indicates that the Rectifier operation state is closed 9. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.5.1.3INTEGER {invalid(-1), normal(1), fault(2), protect(3), communicationFailure(4), on(5), noConfig(6), offline(7), close(8)}read-onlycurrent
hwRectifierVoltage
OBJECT-TYPE
Output voltage . Unit: mV
1.3.6.1.4.1.2011.6.2.1.5.1.4MeasuresRangeread-onlycurrent
hwRectifierCurrent
OBJECT-TYPE
Output current . Unit: mA
1.3.6.1.4.1.2011.6.2.1.5.1.5MeasuresRangeread-onlycurrent
hwRectifierRowStatus
OBJECT-TYPE
RowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.5.1.6RowStatusread-writecurrent
hwRectifierCurrentLimit
OBJECT-TYPE
current limit switch
1.3.6.1.4.1.2011.6.2.1.5.1.7TruthValueread-writecurrent
hwRectifierRunState
OBJECT-TYPE
Running state of rectifier module. Options: 1.rectifierOn(0) - indicates that the module is on 2.averageCharge(1) - indicates that the module is being averagely charged. 3.output(2) - indicates that the module has output 4. isLimit(3) - indicates the current limit switch
1.3.6.1.4.1.2011.6.2.1.5.1.8Bits {rectifierOn(0), averageCharge(1), output(2), isLimit(3)}read-onlycurrent
hwRectifierChargeState
OBJECT-TYPE
Charging state of rectifier. Options: 1. float(0) - indicates that the Charge state of Rectifier is float 2. average(1) - indicates that the Charge state of Rectifier is average 3. test(2) - indicates that the Charge state of Rectifier is test
1.3.6.1.4.1.2011.6.2.1.5.1.9INTEGER {float(0), average(1), test(2)}read-onlycurrent
hwBatteryGroup
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.1.6
hwBatteryGroupTable
OBJECT-TYPE
Basic information table of battery group. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.6.1not-accessiblecurrent
hwBatteryGroupEntry
OBJECT-TYPE
Basic information table of battery group. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.6.1.1not-accessiblecurrent
hwBatteryGroupCapacity
OBJECT-TYPE
Total capacity of the present battery group. Unit: Ah
1.3.6.1.4.1.2011.6.2.1.6.1.1.1Integer32read-onlycurrent
hwBatteryGroupCapcaityRemain
OBJECT-TYPE
Total remain capacity of the present battery group . invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. Unit: Ah
1.3.6.1.4.1.2011.6.2.1.6.1.1.2Integer32 (-1..100)read-onlycurrent
hwBatteryGroups
OBJECT-TYPE
Number of battery group
1.3.6.1.4.1.2011.6.2.1.6.1.1.3Integer32 (0..255)read-writecurrent
hwBatteryGroupVoltageLow
OBJECT-TYPE
When the voltage of the battery group is lower than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.1.1.4MeasuresRangeread-writecurrent
hwBatteryGroupChargeLimit
OBJECT-TYPE
Charge limit point quotient, the product of which and the max capacity of the battery group is the max charge current allowed. Default: 15 Unit: percent
1.3.6.1.4.1.2011.6.2.1.6.1.1.5MeasuresRangeread-writecurrent
hwBatteryGroupRowStatus
OBJECT-TYPE
RowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.6.1.1.6RowStatusread-writecurrent
hwBatteryGroupOperStatus
OBJECT-TYPE
The State of the battery supply which was connected with Power EMU. To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal. When the mains supply is abnormal, the battery group usually supplies power in an emergency. Options: 1.on(1) - indicates that the state of the battery power supply is on 2.off(2) - indicates that the state of the battery power supply is off 3.invalid(-1) - indicates that the device can not get the value,e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.6.1.1.7INTEGER {invalid(-1), on(1), off(2)}read-onlycurrent
hwBatteryGroupVoltageHigh
OBJECT-TYPE
When the voltage of the battery group is higher than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.1.1.8MeasuresRangeread-writecurrent
hwBatteryGroupTwiceOffVoltage
OBJECT-TYPE
The twice off protection voltage of the battery group. Its unit is mV. Default: 44000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.1.1.9MeasuresRangeread-writecurrent
hwBatteryGroupProtectVoltage
OBJECT-TYPE
The first off protection voltage of the battery, whose default is 43V. Default: 43000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.1.1.10MeasuresRangeread-writecurrent
hwBatteryGroupTmpOffHigh
OBJECT-TYPE
The high temperature off protection point of the battery group, whose default is 50 degrees centigrade. Unit: 0.01 degree
1.3.6.1.4.1.2011.6.2.1.6.1.1.11MeasuresRangeread-writecurrent
hwBatteryInstallTime
OBJECT-TYPE
The installing date of battery group.
1.3.6.1.4.1.2011.6.2.1.6.1.1.12DisplayStringread-onlycurrent
hwBatteryGroupBomCode
OBJECT-TYPE
The BOM code of battery.
1.3.6.1.4.1.2011.6.2.1.6.1.1.13DisplayString (SIZE(0..32))read-writecurrent
hwChargeTable
OBJECT-TYPE
Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.6.2not-accessiblecurrent
hwChargeEntry
OBJECT-TYPE
Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.6.2.1not-accessiblecurrent
hwChargeAdminStatus
OBJECT-TYPE
Charge management mode. Options: 1. average(1) - indicates that the charge management mode is average charge 2. float(2) - indicates that the charge management mode is float charge 3. auto(3) - indicates that the charge management mode is auto-control charge 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.6.2.1.1INTEGER {invalid(-1), average(1), float(2), auto(3)}read-writecurrent
hwChargeOperStatus
OBJECT-TYPE
Charge operation status. Options: 1. average(1) - indicates that the charge operation state is average charge 2. float(2) - indicates that the charge operation state is float charge 3. full(3) - indicates that the charge operation state is full 4. noCharge(4) - indicates that there is no charge in operation 5. discharge(5) - indicates that there is discharge in operation 6. sleep(6) - indicates that the charge operation state is sleep 7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.6.2.1.2INTEGER {invalid(-1), average(1), float(2), full(3), noCharge(4), discharge(5), sleep(6)}read-onlycurrent
hwAverageChargeVoltage
OBJECT-TYPE
Voltage value of average charge, in unit of mV. Default: 56500 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.2.1.3MeasuresRangeread-writecurrent
hwFloatChargeVoltage
OBJECT-TYPE
Voltage value of float charge . Default: 53500 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.2.1.4MeasuresRangeread-writecurrent
hwChargeControlRowStatus
OBJECT-TYPE
RowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.6.2.1.5RowStatusread-writecurrent
hwAverageChargeTime
OBJECT-TYPE
Timing average charge time interval, effective range is 190 days. Default :value is 60 days Unit: day
1.3.6.1.4.1.2011.6.2.1.6.2.1.6Integer32read-writecurrent
hwBatteryTmpRedeemingQuotiety
OBJECT-TYPE
Temperature redeeming quotient, used to set the co-relation between the float charge voltage and the battery temperature. It means How much will the float charge voltage decrease with the increasing of every degree centigrade of the battery temperature. The unit is mV. Specific value is determined by the redeem feature curve of floating charge for the battery group used. Default value is 100mV
1.3.6.1.4.1.2011.6.2.1.6.2.1.7Integer32read-writecurrent
hwBatteryTable
OBJECT-TYPE
Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group.
1.3.6.1.4.1.2011.6.2.1.6.3not-accessiblecurrent
hwBatteryEntry
OBJECT-TYPE
Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group.
1.3.6.1.4.1.2011.6.2.1.6.3.1not-accessiblecurrent
hwBatteryIndex
OBJECT-TYPE
Battery group loop index
1.3.6.1.4.1.2011.6.2.1.6.3.1.1Integer32 (0..255)read-onlycurrent
hwBatteryCapacity
OBJECT-TYPE
The permitted max battery capacity of the battery group loop charge. Unit: Ah
1.3.6.1.4.1.2011.6.2.1.6.3.1.2Integer32read-writecurrent
hwBatteryLoopState
OBJECT-TYPE
The battery group present status. Options: 1. on(1) - indicates that the present state of battery group is on 2. off(2) - indicates that the present state of battery group is off 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.6.3.1.3INTEGER {invalid(-1), on(1), off(2)}read-onlycurrent
hwBatteryVoltage
OBJECT-TYPE
The loop voltage of the battery group. Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.3.1.4MeasuresRangeread-onlycurrent
hwBatteryState
OBJECT-TYPE
The present state of the battery group loop. Options: 1. charge(1) - indicates that the present state of the battery group loop is charge 2. discharge(2) - indicates that the present state of the battery group loop is discharge 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.6.3.1.5INTEGER {invalid(-1), charge(1), discharge(2)}read-onlycurrent
hwBatteryCurrent
OBJECT-TYPE
Present current . Unit: mA
1.3.6.1.4.1.2011.6.2.1.6.3.1.6MeasuresRangeread-onlycurrent
hwBatteryTemperature
OBJECT-TYPE
The loop temperature of the battery group. Unit: degree
1.3.6.1.4.1.2011.6.2.1.6.3.1.7Integer32read-onlycurrent
hwBatteryRowStatus
OBJECT-TYPE
RowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.6.3.1.8RowStatusread-writecurrent
hwBatteryCurrentHigh
OBJECT-TYPE
The over-current alarm point of the battery group. Unit: mA
1.3.6.1.4.1.2011.6.2.1.6.3.1.9MeasuresRangeread-writecurrent
hwBatteryFuseState
OBJECT-TYPE
Battery fuse state. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.6.3.1.10INTEGER {invalid(-1), on(1), off(2)}read-onlycurrent
hwBatteryContactState
OBJECT-TYPE
The state of the battery contactor. Options: 1. on(1) - indicates that the contactor is connected 2. off(2) - indicates that the contactor is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.2.1.6.3.1.11INTEGER {invalid(-1), on(1), off(2)}read-onlycurrent
hwBatteryRemainCapacity
OBJECT-TYPE
Remain capacity of the battery
1.3.6.1.4.1.2011.6.2.1.6.3.1.12Integer32read-onlycurrent
hwBatteryProtectState
OBJECT-TYPE
Protection status of the battery. Options: 1. normal(1) - indicates that the Protection status of the battery is normal 2. overtemperature(2) - indicates that the Protection status of the battery is overtemperature 3. overCurrent(3) - indicates that the Protection status of the battery is overCurrent
1.3.6.1.4.1.2011.6.2.1.6.3.1.13INTEGER {normal(1), overtemperature(2), overCurrent(3)}read-onlycurrent
hwBatteryVoltageState
OBJECT-TYPE
Voltage state of Battery. Options: 1. normal(1) - indicates that Voltage state of Battery is normal 2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage 3. belowVoltage(3) - indicates that Voltage state of Battery is belowVoltage
1.3.6.1.4.1.2011.6.2.1.6.3.1.14INTEGER {normal(1), exceedVoltage(2), belowVoltage(3)}read-onlycurrent
hwBatteryHardwareState
OBJECT-TYPE
Hardware State of Battery. Options: 1. normal(1) - indicates that the hardware state of Battery is normal 2. fault(2) - indicates that the hardware state of Battery is fault
1.3.6.1.4.1.2011.6.2.1.6.3.1.15INTEGER {normal(1), fault(2)}read-onlycurrent
hwBatteryTestTable
OBJECT-TYPE
Battery test table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.6.4not-accessiblecurrent
hwBatteryTestEntry
OBJECT-TYPE
Battery test table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.6.4.1not-accessiblecurrent
hwBatteryTestAdminStatus
OBJECT-TYPE
Battery test admin status. Options: 1. start(1) - indicates that the Battery starts testing 2. terminate(2) - indicates that the Battery terminates testing 3. enableAutoTest(3) - indicates that the Battery enables auto test function 4. disableAutoTest(4) - indicates that the Battery disables auto test function 5. timeautoTest(5) - indicates that the Battery enable timing auto test function 6. offautoTest(6) - indicates that the Battery enable off auto test function 7. timeoffautoTest(7) - indicates that the Battery enable timing+off auto test
1.3.6.1.4.1.2011.6.2.1.6.4.1.1INTEGER {start(1), terminate(2), enableAutoTest(3), disableAutoTest(4), timeautoTest(5), offautoTest(6), timeoffautoTest(7)}read-writecurrent
hwBatteryTestAutoDischargePeriod
OBJECT-TYPE
Auto discharge test period. Effective range is 30 -240 days. Default: 120 Unit: day
1.3.6.1.4.1.2011.6.2.1.6.4.1.2Integer32read-writecurrent
hwBatteryTestResult
OBJECT-TYPE
Test result: Options: 1. testing(1) - indicates that the Battery test is in operation 2. complete(2) - indicates that the Battery test is completed normally 3. alarmTerminated(3) - indicates that the Battery test is stopped by alarms 4. hostTerminated(4) - indicates that the Battery test is stopped by the host 5. overtimeTerminated(5) - indicates that the Battery test is stopped because of over time 6. normal(6) - indicates that the Battery test is not started 7. supplyRecoverAutotestTerminated(7) - indicates that the Battery test is stopped because of supply recover
1.3.6.1.4.1.2011.6.2.1.6.4.1.3INTEGER {testing(1), complete(2), alarmTerminated(3), hostTerminated(4), overtimeTerminated(5), normal(6), supplyRecoverAutotestTerminated(7)}read-onlyobsolete
hwBatteryTestStartTime
OBJECT-TYPE
Time of starting test
1.3.6.1.4.1.2011.6.2.1.6.4.1.4DateAndTimeread-onlyobsolete
hwBatteryTestDuration
OBJECT-TYPE
Battery discharge test duration . Effective range is 1C100 hours. Default :value is 10 hours Unit: hour
1.3.6.1.4.1.2011.6.2.1.6.4.1.5Integer32read-writecurrent
hwBatteryTestTerminateVoltage
OBJECT-TYPE
Battery discharge test end voltage. Effective range (DC lack alarm voltage+0.5VCvoltage of floating charge). Default: 45600 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.4.1.6Integer32read-writecurrent
hwBatteryTestTotalDischargeAH
OBJECT-TYPE
Total discharge AH. Unit: mAH
1.3.6.1.4.1.2011.6.2.1.6.4.1.7Integer32read-onlyobsolete
hwBatteryTestOperStatus
OBJECT-TYPE
Battery discharge test operate status. Options: 1. autoTestPermit(1) - indicates that auto discharge test is enabled 2. autoTestForbid(2) - indicates that auto discharge test is disabled 3. timeautoTestPermit(3) - indicates that timing auto discharge test is enabled 4. offautoTestPermit(4) - indicates that off auto discharge test is enabled 5. timeoffautoTestPermit(5) - indicates that timing-off auto discharge test is enabled
1.3.6.1.4.1.2011.6.2.1.6.4.1.8INTEGER {autoTestPermit(1), autoTestForbid(2), timeautoTestPermit(3), offautoTestPermit(4), timeoffautoTestPermit(5)}read-onlycurrent
hwBatteryTestPhase
OBJECT-TYPE
Battery test phase. Options: 1. charge(1) - indicates the batter test phase is charge 2. discharge(2) - indicates the batter test phase is discharge 3. record(3) - indicates the power equipment recording test result 4. finish(4) - indicates that the discharge is complete 5.waitingfordischarge(5) - indicates that preparation is ready for discharge command
1.3.6.1.4.1.2011.6.2.1.6.4.1.9INTEGER {charge(1), discharge(2), record(3), finish(4), waitingfordischarge(5)}read-onlycurrent
hwBatteryTestStartHour
OBJECT-TYPE
Discharge start time. Effective range is 0 23 Default: 0 Unit: hour
1.3.6.1.4.1.2011.6.2.1.6.4.1.10Integer32read-writecurrent
hwBatteryTestAlarmThreshold
OBJECT-TYPE
The battery discharge test alarm threshold in ratio of the range:1~79.
1.3.6.1.4.1.2011.6.2.1.6.4.1.11Integer32read-writecurrent
hwBatteryLogTestTable
OBJECT-TYPE
Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery.
1.3.6.1.4.1.2011.6.2.1.6.5not-accessiblecurrent
hwBatteryLogTestEntry
OBJECT-TYPE
Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery.
1.3.6.1.4.1.2011.6.2.1.6.5.1not-accessiblecurrent
hwBatteryLogTestIndex
OBJECT-TYPE
Battery discharge test result index
1.3.6.1.4.1.2011.6.2.1.6.5.1.1Integer32 (0..255)read-onlycurrent
hwBatteryLogTestStartTime
OBJECT-TYPE
Battery discharge test start time
1.3.6.1.4.1.2011.6.2.1.6.5.1.2DateAndTimeread-onlycurrent
hwBatteryLogTestDischargeDuration
OBJECT-TYPE
Duration of discharge. Unit: minute
1.3.6.1.4.1.2011.6.2.1.6.5.1.3Integer32read-onlycurrent
hwBatteryLogTestTerminateVoltage
OBJECT-TYPE
End voltage of battery discharge test . Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.5.1.4Integer32read-onlycurrent
hwBatteryLogTestBatteryStatus
OBJECT-TYPE
Battery status. Options: 1. expectant(1) - indicates the batter test state is expectant 2. unexpected(2) - indicates the batter test state is unexpected 3. unknown(3) - indicates the batter test state is unknown
1.3.6.1.4.1.2011.6.2.1.6.5.1.5INTEGER {expectant(1), unexpected(2), unknown(3)}read-onlycurrent
hwBatteryLogTestTotalDischargeAH
OBJECT-TYPE
Discharge cumulate AH. Unit: mAH
1.3.6.1.4.1.2011.6.2.1.6.5.1.6Integer32read-onlycurrent
hwBatteryLogTestFinish
OBJECT-TYPE
Battery Test result. Options: 1. testing(1) - indicates that it is during testing 2. completed(2) - indicates that the test is completed normally 3. alarmTerminated(3) - indicates that the test is stopped by alarms 4. hostTerminated(4) - indicates that the test is stopped by the host 5. overtimeTerminated(5) - indicates that the test is stopped because of over 100 hours 6. notTest(6) - indicates that the test is not started
1.3.6.1.4.1.2011.6.2.1.6.5.1.7INTEGER {testing(1), completed(2), alarmTerminated(3), hostTerminated(4), overtimeTerminated(5), notTest(6)}read-onlycurrent
hwBatteryLogTestEfficiency
OBJECT-TYPE
The information of battery test efficiency.
1.3.6.1.4.1.2011.6.2.1.6.5.1.8Integer32read-onlycurrent
hwBatteryLogTestBatteryTemperature
OBJECT-TYPE
Battery discharge test end Temperature. Unit: 0.01 Degree
1.3.6.1.4.1.2011.6.2.1.6.5.1.9Integer32read-onlycurrent
hwBatteryLogTestBatteryCurrent
OBJECT-TYPE
Battery discharge test average Current. Unit: mA
1.3.6.1.4.1.2011.6.2.1.6.5.1.10Integer32read-onlycurrent
hwRemoteProvidePowerInfoTable
OBJECT-TYPE
Remote provide power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.7not-accessiblecurrent
hwRemoteProvidePowerInfoEntry
OBJECT-TYPE
Remote provide power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
1.3.6.1.4.1.2011.6.2.1.7.1not-accessiblecurrent
hwPowerCentralState
OBJECT-TYPE
State of the central module. Options: 1. normal(1) - indicates the normal state 2. temOver(2) - indicates the over-temperature
1.3.6.1.4.1.2011.6.2.1.7.1.1INTEGER {normal(1), temOver(2)}read-onlycurrent
hwPowerCentralDCInPutState
OBJECT-TYPE
State of central module DC input: Options: 1.normal(1) - indicates the normal state 2.lack(2) - indicates the voltage underflow 3.over(3) - indicates the voltage overflow
1.3.6.1.4.1.2011.6.2.1.7.1.2INTEGER {normal(1), lack(2), over(3)}read-onlycurrent
hwPowerCentralDCOutputState
OBJECT-TYPE
State of central module DC output. Options: 1. normal(1) - indicates the normal state 2. volLack(2) - indicates the voltage underflow 3. volOver(3) - indicates the voltage overflow 4. loadOver(4) - indicates the over-loading 5. shortCircuit(5) - indicates the short circuit 6. noLoad(6) - indicates no load
1.3.6.1.4.1.2011.6.2.1.7.1.3INTEGER {normal(1), volLack(2), volOver(3), loadOver(4), shortCircuit(5), noLoad(6)}read-onlycurrent
hwPowerCentralDCOutputMode
OBJECT-TYPE
Mode of central module DC output. Options: 1. highVolMode(1) - indicates the high voltage output mode 2. lowVolMode(2) - indicates the low voltage output mode
1.3.6.1.4.1.2011.6.2.1.7.1.4INTEGER {highVolMode(1), lowVolMode(2)}read-onlycurrent
hwPowerRemoteCommState
OBJECT-TYPE
Remote power module communications state. Options: 1. normal(1) - indicates the normal state 2. revfault(2) - indicates the receiving of fault 3. sendfault(3) - indicates the sending of fault
1.3.6.1.4.1.2011.6.2.1.7.1.5INTEGER {normal(1), revfault(2), sendfault(3)}read-writecurrent
hwPowerRemoteDCInputState
OBJECT-TYPE
State of remote module DC input. Options: 1. normal(1) - indicates the normal state 2. lack(2) - indicates that the voltage is underflow
1.3.6.1.4.1.2011.6.2.1.7.1.6INTEGER {normal(1), lack(2)}read-writecurrent
hwPowerRemoteLineCurState
OBJECT-TYPE
state of line between central and remote module. Options: 1.normal(1) - indicates the normal state 2.cablejoining(2) - indicates the cable joining 3.curLeakage(3) - indicates the cur Leakage 4.curOver(4) - indicates the cur Over
1.3.6.1.4.1.2011.6.2.1.7.1.7INTEGER {normal(1), cablejoining(2), curLeakage(3), curOver(4)}read-writecurrent
hwPowerRemotePowerState
OBJECT-TYPE
state of remote UA60 power. Options: 1. normal(1) - indicates the normal state 2. fault(2) - indicates the faulty state
1.3.6.1.4.1.2011.6.2.1.7.1.8INTEGER {normal(1), fault(2)}read-writecurrent
hwPowerRemoteLineState
OBJECT-TYPE
State of line U1. Options: 1. u1state(0) - indicates the power remote line state is u1 state 2. u2state(1) - indicates the power remote line state is u2 state 3. u3state(2) - indicates the power remote line state is u3 state 4. u4state(3) - indicates the power remote line state is u4 state 5. a1state(4) - indicates the power remote line state is a1 state 6. a2state(5) - indicates the power remote line state is a2 state 7. a3state(6) - indicates the power remote line state is a3 state 8. a4state(7) - indicates the power remote line state is a4 state
1.3.6.1.4.1.2011.6.2.1.7.1.9Bits {u1state(0), u2state(1), u3state(2), u4state(3), a1state(4), a2state(5), a3state(6), a4state(7)}read-writecurrent
hwPowerCentralLoadState
OBJECT-TYPE
state of central load. Options: 1. normal(1) - indicates the normal state 2. overload(2) - indicates overload 3. nonload(3) - indicates non-load
1.3.6.1.4.1.2011.6.2.1.7.1.10INTEGER {normal(1), overload(2), nonload(3)}read-writecurrent
hwACInfomationTable
OBJECT-TYPE
AC infomation table. The table is not supported. The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
1.3.6.1.4.1.2011.6.2.1.8not-accessiblecurrent
hwACInfomationEntry
OBJECT-TYPE
AC infomation table. The table is not supported. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
1.3.6.1.4.1.2011.6.2.1.8.1not-accessiblecurrent
hwACInfoCommState
OBJECT-TYPE
communication state of AC input module. The node is not supported. Options: 1. normal(0) - indicates the communication state of AC is normal 2. fault(1) - indicates the communication state of AC is fault
1.3.6.1.4.1.2011.6.2.1.8.1.1INTEGER {normal(0), fault(1)}read-onlycurrent
hwACInfoThunderState
OBJECT-TYPE
Thunder's state. The node is not supported. Options: 1. normal(0) - indicates the state of Thunder is normal 2. fault(1) - indicates the state of Thunder is fault
1.3.6.1.4.1.2011.6.2.1.8.1.2INTEGER {normal(0), fault(1)}read-onlycurrent
hwACInfoCurrentLoop
OBJECT-TYPE
Current AC input working loop. The leaf is not supported.
1.3.6.1.4.1.2011.6.2.1.8.1.3Integer32read-onlycurrent
hwACInfoMCBTrigger
OBJECT-TYPE
AC input MCB trigger state. The leaf is not supported. Options: 1. normal(0) - indicates the AC input MCB trigger state is normal 2. break-down(1)- indicates the AC input MCB trigger state is break-down
1.3.6.1.4.1.2011.6.2.1.8.1.4INTEGER {normal(0), break-down(1)}read-onlycurrent
hwACInfoFrequency
OBJECT-TYPE
The infomation of AC input frequency. This leaf is not supported. Unit: HZ
1.3.6.1.4.1.2011.6.2.1.8.1.5Integer32read-onlycurrent
hwACInfoRowStatus
OBJECT-TYPE
RowStatus standard operation The leaf is not supported.
1.3.6.1.4.1.2011.6.2.1.8.1.6RowStatusread-writecurrent
hwPowerMibTrap
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.2
hwPowerTrapOid
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.2.1
hwPowerTrapsDefine
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.2.2
hwPowerTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.2.2.0
powerConformance
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.3
powerCompliances
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.3.1
powerGroups
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.3.2
hwEnvironPowerTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.4
hwEnvironPowerCommonTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.4.1
hwEnvironPowerAlarmTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.4.2
hwEnvironPowerAlarmTrapsPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.2.4.2.0

Notifications

NameOIDStatus
powerConnFaultAlarm
NOTIFICATION-TYPE
This trap message is reported when the communication between the power module and the monitoring board is fault.
1.3.6.1.4.1.2011.6.2.2.2.0.1current
powerConnFaultAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the communication between the power module and the monitoring board resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.2current
acInputVoltageAlarm
NOTIFICATION-TYPE
This trap message is reported when there is a exception of AC input voltage.
1.3.6.1.4.1.2011.6.2.2.2.0.3current
acInputVoltageAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the state of AC input voltage resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.4current
acInputVoltageHighAlarm
NOTIFICATION-TYPE
This trap message is reported when the input voltage is too high.
1.3.6.1.4.1.2011.6.2.2.2.0.5current
acInputVoltageHighAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the input voltage resumes to the normal range from a high value.
1.3.6.1.4.1.2011.6.2.2.2.0.6current
acInputVoltageLowAlarm
NOTIFICATION-TYPE
This trap message is reported when the input voltage is too low.
1.3.6.1.4.1.2011.6.2.2.2.0.7current
acInputVoltageLowAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the input voltage resumes to the normal range from a low value.
1.3.6.1.4.1.2011.6.2.2.2.0.8current
dcOutputVoltageHighAlarm
NOTIFICATION-TYPE
This trap message is reported when the output voltage is too high.
1.3.6.1.4.1.2011.6.2.2.2.0.9current
dcOutputVoltageHighAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the output voltage resumes to the normal range from a high value.
1.3.6.1.4.1.2011.6.2.2.2.0.10current
dcOutputCurrentHighAlarm
NOTIFICATION-TYPE
This trap message is reported when the output current is too high.
1.3.6.1.4.1.2011.6.2.2.2.0.11current
dcOutputCurrentHighAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the output current resumes to the normal range from a high value.
1.3.6.1.4.1.2011.6.2.2.2.0.12current
dcOutputVoltageLowAlarm
NOTIFICATION-TYPE
This trap message is reported when the output voltage is too low.
1.3.6.1.4.1.2011.6.2.2.2.0.13current
dcOutputVoltageLowAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the output voltage resumes to the normal range from a low value.
1.3.6.1.4.1.2011.6.2.2.2.0.14current
dcOutputCurrentLowAlarm
NOTIFICATION-TYPE
This trap message is reported when the output current is too low.
1.3.6.1.4.1.2011.6.2.2.2.0.15current
dcOutputCurrentLowAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the output current resumes to the normal range from a low value.
1.3.6.1.4.1.2011.6.2.2.2.0.16current
overLoadPowerAbnormalAlarm
NOTIFICATION-TYPE
This trap message is reported when the state of load power is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.17current
overLoadPowerAbnormalAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the state of load power recovers to normal.
1.3.6.1.4.1.2011.6.2.2.2.0.18current
overBattPowerOffAlarm
NOTIFICATION-TYPE
This trap message is reported when the battery is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.19current
overBattPowerOffAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the battery is powered on.
1.3.6.1.4.1.2011.6.2.2.2.0.20current
overLoadPowerOffAlarm
NOTIFICATION-TYPE
This trap message is reported when the loadpower is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.21current
overLoadPowerOffAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the loadpower is powered on.
1.3.6.1.4.1.2011.6.2.2.2.0.22current
acMainsSupplyAlarm
NOTIFICATION-TYPE
This trap message is reported when the AC mains supply is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.23current
acMainsSupplyAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the AC mains supply recovers to normal.
1.3.6.1.4.1.2011.6.2.2.2.0.24current
batteryLoopAlarm
NOTIFICATION-TYPE
This trap message is reported when the loop of battery group disconnects.
1.3.6.1.4.1.2011.6.2.2.2.0.25current
batteryLoopAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the loop of battery group connects.
1.3.6.1.4.1.2011.6.2.2.2.0.26current
batteryFuseAlarm
NOTIFICATION-TYPE
This trap message is reported when the fuse of battery group disconnects.
1.3.6.1.4.1.2011.6.2.2.2.0.27current
batteryFuseAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the fuse of battery group connects.
1.3.6.1.4.1.2011.6.2.2.2.0.28current
batteryContachAlarm
NOTIFICATION-TYPE
This trap message is reported when the contactor of battery group disconnects.
1.3.6.1.4.1.2011.6.2.2.2.0.29current
batteryContachAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the contactor of battery group connects.
1.3.6.1.4.1.2011.6.2.2.2.0.30current
userModuleOffAlarm
NOTIFICATION-TYPE
This trap message is reported when the user module is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.31current
userModuleOffAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the user module is powered on.
1.3.6.1.4.1.2011.6.2.2.2.0.32current
transferModuleOffAlarm
NOTIFICATION-TYPE
This trap message is reported when the transfer module is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.33current
transferModuleOffAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the transfer module is powered on.
1.3.6.1.4.1.2011.6.2.2.2.0.34current
userModuleSwitchAlarm
NOTIFICATION-TYPE
This trap message is reported when the user module is switched off.
1.3.6.1.4.1.2011.6.2.2.2.0.35current
transferModuleSwitchAlarm
NOTIFICATION-TYPE
This trap message is reported when the transfer module is switched off.
1.3.6.1.4.1.2011.6.2.2.2.0.37current
loadFuseAlarm
NOTIFICATION-TYPE
This trap message is reported when the load fuse is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.39current
loadFuseAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the load fuse resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.40current
chargeCtrlStateAlarm
NOTIFICATION-TYPE
This trap message is reported when the control state of average or floating charge converts.
1.3.6.1.4.1.2011.6.2.2.2.0.41current
chargeModeAlarm
NOTIFICATION-TYPE
This trap message is reported when the charge state converts.
1.3.6.1.4.1.2011.6.2.2.2.0.42current
acCommFailAlarm
NOTIFICATION-TYPE
This trap message is reported when the AC panel communication fails.
1.3.6.1.4.1.2011.6.2.2.2.0.43current
acCommFailAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the AC panel communication resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.44current
batteryChargeOverAlarm
NOTIFICATION-TYPE
This trap message is reported when the Over-current of battery group happens.
1.3.6.1.4.1.2011.6.2.2.2.0.45current
batteryChargeOverAlarmResume
NOTIFICATION-TYPE
OThis trap message is reported when the Over-current of battery group resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.46current
batteryVoltageLackAlarm
NOTIFICATION-TYPE
This trap message is reported when the voltage of battery group lacks.
1.3.6.1.4.1.2011.6.2.2.2.0.47current
batteryVoltageLackAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the voltage of battery group recovers from lack.
1.3.6.1.4.1.2011.6.2.2.2.0.48current
loadTwiceOffAlarm
NOTIFICATION-TYPE
This trap message is reported when the load is powered off twice.
1.3.6.1.4.1.2011.6.2.2.2.0.49current
loadTwiceOffAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the load recovers from powering off twice.
1.3.6.1.4.1.2011.6.2.2.2.0.50current
loadOnceOffAlarm
NOTIFICATION-TYPE
This trap message is reported when the load is powered off once.
1.3.6.1.4.1.2011.6.2.2.2.0.51current
loadOnceOffAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the load recovers from powering off once.
1.3.6.1.4.1.2011.6.2.2.2.0.52current
acInputPowerOffAlarm
NOTIFICATION-TYPE
This trap message is reported when the AC input is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.53current
acInputPowerOffAlarmResume
NOTIFICATION-TYPE
This trap message is reported when the AC input power is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.54current
acInputLoopSwtichAlarm
NOTIFICATION-TYPE
This trap message is reported when the AC input loop switches to another one.
1.3.6.1.4.1.2011.6.2.2.2.0.55current
batteryDischargeTestStartAlarm
NOTIFICATION-TYPE
This trap message is reported when the battery discharge test starts.
1.3.6.1.4.1.2011.6.2.2.2.0.56current
batteryDischargeTestStopAlarm
NOTIFICATION-TYPE
This trap message is reported when the battery discharge test stops.
1.3.6.1.4.1.2011.6.2.2.2.0.57current
powerProtectAlarm
NOTIFICATION-TYPE
This trap message is reported when the power protection function is enbaled.
1.3.6.1.4.1.2011.6.2.2.2.0.58current
powerUndoProtectAlarm
NOTIFICATION-TYPE
This trap message is reported when the power protection function is disabled.
1.3.6.1.4.1.2011.6.2.2.2.0.59current
powerCentralOutputModeSwtichAlarm
NOTIFICATION-TYPE
This trap message is reported when the central output mode swtiches to another one.
1.3.6.1.4.1.2011.6.2.2.2.0.60current
powerCentralTempretaureAlarm
NOTIFICATION-TYPE
This trap message is reported when the central tempretaure is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.61current
powerCentralInputAlarm
NOTIFICATION-TYPE
This trap message is reported when the central input voltage is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.62current
powerCentralOutputAlarm
NOTIFICATION-TYPE
This trap message is reported when the central output voltage is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.63current
powerRemoteCommFaultAlarm
NOTIFICATION-TYPE
This trap message is reported when the communiction between the remote and central fails.
1.3.6.1.4.1.2011.6.2.2.2.0.64current
powerRemoteVoltageAlarm
NOTIFICATION-TYPE
This trap message is reported when the remote voltage is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.65current
powerLineAlarm
NOTIFICATION-TYPE
This trap message is reported when the power line is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.66current
powerRemotePowerAlarm1
NOTIFICATION-TYPE
This trap message is reported when the remote power is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.67current
powerRemotePowerAlarm2
NOTIFICATION-TYPE
This trap message is reported when the Line UA is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.68current
powerRemotePowerAlarm3
NOTIFICATION-TYPE
This trap message is reported when the Central load is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.69current
hwEmmPowerBattaryTestStartTrap
NOTIFICATION-TYPE
The agent generates this trap when the power device battary discharge test starts.
1.3.6.1.4.1.2011.6.2.4.2.0.1current
hwEmmPowerBattaryTestStopTrap
NOTIFICATION-TYPE
The agent generates this trap when the power device battary discharge test ends.
1.3.6.1.4.1.2011.6.2.4.2.0.2current
hwEmmPowerAcvolFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the power device AC input voltage is abnormal.
1.3.6.1.4.1.2011.6.2.4.2.0.3current
hwEmmPowerAcvolRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the power device AC input voltage recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.4current
hwEmmPowerDcvolFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the power device DC output voltage is abnormal.
1.3.6.1.4.1.2011.6.2.4.2.0.5current
hwEmmPowerDcvolRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the power device DC output voltage recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.6current
hwEmmPowerBattloopFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the power device the battery loop is broken. In this case, the function of he backup power is lost.
1.3.6.1.4.1.2011.6.2.4.2.0.7current
hwEmmPowerBattloopRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the power device battery loop recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.8current
hwEmmPowerLoadfuseFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the fuse of the power device is broken. In this case, the device is powered off.
1.3.6.1.4.1.2011.6.2.4.2.0.9current
hwEmmPowerLoadfuseRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the fuse of the power device recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.10current
hwEmmPowerRectifierFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the rectifier module of the power device is abnormal and the spully power may decrease.
1.3.6.1.4.1.2011.6.2.4.2.0.11current
hwEmmPowerRectifierRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the rectifier module of the power device recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.12current
hwEmmDigMainsupplyFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the main supply digital is faulty.
1.3.6.1.4.1.2011.6.2.4.2.0.13current
hwEmmDigMainsupplyRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the main supply digital recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.14current
hwEmmPowerBatteryOffTrap
NOTIFICATION-TYPE
The agent generates this trap when the power of battary is off.
1.3.6.1.4.1.2011.6.2.4.2.0.15current
hwEmmBatt1TempFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the battery group 1 temperature sensor fault occurs.
1.3.6.1.4.1.2011.6.2.4.2.0.16current
hwEmmBatt1TempRestoreTrap
NOTIFICATION-TYPE
The agent generates this trap when the battery group 1 temperature sensor fault recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.17current
hwEmmEnviHumFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the environment humidity sensor fault occurs.
1.3.6.1.4.1.2011.6.2.4.2.0.18current
hwEmmEnviHumRestoreTrap
NOTIFICATION-TYPE
The agent generates this trap when the environment humidity sensor fault recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.19current
hwEmmEnvi1TempFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the environment 1 temperature sensor fault occurs.
1.3.6.1.4.1.2011.6.2.4.2.0.20current
hwEmmEnvi1TempRestoreTrap
NOTIFICATION-TYPE
The agent generates this trap when the environment 1 temperature sensor fault recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.21current
hwEmmBattTemFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the battery temperature out of normal range.
1.3.6.1.4.1.2011.6.2.4.2.0.22current
hwEmmBattTemRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the battery temperature recovers to normal range.
1.3.6.1.4.1.2011.6.2.4.2.0.23current
hwEmmPowerBatteryOffRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the power of battary recovers to on state.
1.3.6.1.4.1.2011.6.2.4.2.0.24current
hwEmmPowerBatteryUnDetectTrap
NOTIFICATION-TYPE
The agent generates this trap when the one or more batteries are not detected.
1.3.6.1.4.1.2011.6.2.4.2.0.25current
hwEmmPowerBatteryDetectRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the batteries recover.
1.3.6.1.4.1.2011.6.2.4.2.0.26current
hwPowerModuleMismatchTrap
NOTIFICATION-TYPE
The agent generates this trap when the the power supply system detects mismatched power module .
1.3.6.1.4.1.2011.6.2.4.2.0.27current
hwPowerModuleRestoreTrap
NOTIFICATION-TYPE
The agent generates this trap when the power module recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.28current