MIBs Depot

HUAWEI-ENVIRONMENT-MIB

Registered at
1.3.6.1.4.1.2011.6.1
Last updated
2013-06-17 09:00
Organization
Fix-Net DepT, Huawei Technologies Co.,Ltd.
Revisions
2013-06-17 09:00, 2013-05-13 09:00, 2013-01-24 09:00, 2012-11-19 09:00, 2012-11-05 10:00, 2012-10-25 17:00, 2012-09-24 17:00, 2012-07-23 17:00, 2012-01-14 09:00, 2011-11-10 09:00, 2011-08-08 09:00, 2011-05-12 09:00, 2011-03-18 09:00, 2011-01-18 09:00, 2010-11-10 00:00, 2010-08-20 09:00, 2010-07-19 09:00, 2010-06-10 09:00, 2010-05-30 09:00, 2010-05-18 09:00, 2010-04-08 09:00, 2010-03-27 09:00, 2010-03-24 09:00, 2010-02-22 09:00, 2010-02-06 09:00, 2010-01-29 09:00, 2009-07-20 09:00, 2009-05-05 00:00, 2002-11-29 00:00
Namespace
huawei
Source file
HUAWEI-ENVIRONMENT-MIB
Digest
sha256:0a69a80d33f30157996774be6fe6c3bc0432aa15c19c5c3cad005e6203b3769f

Description

The MIB module defines MIB objects which include Environment Monitor Unit, Analog Environment data, Digital Environment data, Out data and Fan data Monitor management MIB interfaces.

Contact

Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China Website: http://www.huawei.com Email: support@huawei.com

Imports

FromSymbols
HUAWEI-DEVICE-MIBhwFrameIndex
HUAWEI-MIBhuaweiUtility
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIBITS, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso
SNMPv2-TCDisplayString, RowStatus, TEXTUAL-CONVENTION

Imported by

1 module(s) in this corpus import this one.

Load order

Every file a consumer needs in order to load this module, dependencies first.

HCNUM-TC
HUAWEI-DEVICE-MIB
HUAWEI-ENVIRONMENT-MIB
HUAWEI-MIB
HUAWEI-TC-MIB
IANAifType-MIB
IF-MIB
INET-ADDRESS-MIB
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
hwEnvironmentMon
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.1
hwEnvironmentInfoTable
OBJECT-TYPE
Information table of Environment Monitor Unit. The Environment Monitor Unit is some kind of Environment monitoring device and is used to monitor many kinds of Environment data. The maximum number of Environment Monitor Units in one device node is 64. The index of this table is hwEnvEmuIndex. hwEnvEmuIndex is the index of one Environment Monitor Unit.
1.3.6.1.4.1.2011.6.1.1.1not-accessiblecurrent
hwEnvironmentInfoEntry
OBJECT-TYPE
Information table of Environment Monitor Unit. The Environment Monitor Unit is some kind of Environment monitoring device and is used to monitor many kinds of Environment data. The maximum number of Environment Monitor Units in one device node is 64. The index of this entry is hwEnvEmuIndex. hwEnvEmuIndex is the index of one Environment Monitor Unit.
1.3.6.1.4.1.2011.6.1.1.1.1not-accessiblecurrent
hwEnvEmuIndex
OBJECT-TYPE
hwEnvEmuIndex is the index of the Environment monitoring unit, used as the index of hwEnvironmentInfoTable. Range: 0 - 2048
1.3.6.1.4.1.2011.6.1.1.1.1.1Integer32 (0..2048)read-onlycurrent
hwEnvEmuType
OBJECT-TYPE
Type of the physical monitoring devices associated with the environment monitoring unit. Options: 1.h302ESC(1) -Type of the physical monitoring devices is H302ESC 2.h303ESC(2) -Type of the physical monitoring devices is H303ESC 3.h4875(3) -Type of the physical monitoring devices is 4875 power monitoring frame 4.h301ESC(4) -Type of the physical monitoring devices is H301ESC 5.switch(5) -Distribute monitoring frame 6.fanEscFrame(6) -ESC monitoring fan frame 7.fanFrame(7) -monitoring fan frame 8.h4845(8) -4845 power monitoring 9.fanFCBFrame(9) -FCB monitoring fan frame 10.fanFDMUFrame(10) -FDMU monitoring fan frame 11.h304ESC(11) -provides the management function of battery 12.pwma(12) -Type of the physical monitoring devices is pwma 13.h561esc(13) -H561ESC 14.h801esc(14) -H801Esc 15.h612pwbp(15) -H612pwbp 16.pse158(16) -pse158 17.h4805(19) -h4805 18.pdu(20) -pdu 19.acrmu(21) -ac_rmu 20.acfan(22) -ac_fan 21.dcfan(23) -dc_fan 22.rmun1509(24) -rmun1509 23.onps150(25) -onps150 24.h801pmix(26) -h801pmix 25.h4875L(27) -h4875L 26.miniESC(28) -miniESC 27.h831VESC(29) -H831VESC 28.h601VESC(30) -H601VESC 29.h4830L(31) -h4830L 30.h801citx(32) -h801citx 31.h801citd(33) -h801citd 32.h831ccuh(34) -h831ccuh 33.h831pmu(35) -h831pmu 34.pwr3000(36) -a type of power named power 3000, supports 12 rectifier modules 35.tcu(37) -tcu 36.liFeBattery(38) -liFeBattery 37.transemu(39) -a type of emu for transport environment information to managment center 38.smu(40) -site monitoring unit 39.vpea(41) -vector monitoring unit 40.h801VESC(42) -H801VESC 41.h801PMU(44) -H801PMU 42.other(255) -other
1.3.6.1.4.1.2011.6.1.1.1.1.2INTEGER {h302ESC(1), h303ESC(2), h4875(3), h301ESC(4), switch(5), fanEscFrame(6), fanFrame(7), h4845(8), fanFCBFrame(9), fanFDMUFrame(10), h304ESC(11), pwma(12), h561esc(13), h801esc(14), h612pwbp(15), pse158(16), h4805(19), pdu(20), acrmu(21), acfan(22), dcfan(23), rmun1509(24), onps150(25), h801pmix(26), h4875L(27), miniESC(28), h831VESC(29), h601VESC(30), h4830L(31), h801citx(32), h801citd(33), h831ccuh(34), h831pmu(35), pwr3000(36), tcu(37), liFeBattery(38), transemu(39), smu(40), vpea(41), h801VESC(42), leadAcidBattery(43), h801PMU(44), other(255)}read-writecurrent
hwEnvBoardName
OBJECT-TYPE
Name of the environment monitoring unit.
1.3.6.1.4.1.2011.6.1.1.1.1.3DisplayStringread-writecurrent
hwEnvCommState
OBJECT-TYPE
Status of the communication between the environment monitoring unit and the device. The environmental condition can be tested only when the communication is normal. Options: 1.normal(1) - indicates that communication state is normal 2.shutdown(2) - indicates that communication state is shutdown 3.fault(3) - indicates that communication state is fault 4.abnormal(4) - indicates that communication state is abnormal 5.config(5) - indicates that communication state is config
1.3.6.1.4.1.2011.6.1.1.1.1.4INTEGER {normal(1), shutdown(2), fault(3), abnormal(4), config(5)}read-onlycurrent
hwEnvRowStatus
OBJECT-TYPE
RowStatus standard operation. The creation and deletion operations are supported currently.
1.3.6.1.4.1.2011.6.1.1.1.1.5RowStatusread-writecurrent
hwEnvVersion
OBJECT-TYPE
Version information of the environment monitoring unit.
1.3.6.1.4.1.2011.6.1.1.1.1.6DisplayStringread-onlycurrent
hwEnvFrameId
OBJECT-TYPE
ID of the shelf housing the environment monitoring unit.
1.3.6.1.4.1.2011.6.1.1.1.1.7Integer32read-writecurrent
hwEnvAdminStatus
OBJECT-TYPE
The management status of the monitoring unit. Options: 1.noOperation(1) -no any operation 2.reset(2) -reset the monitoring board 3.manage(3) -manage the monitoring unit 4.unmanage(4) -undo manage the monitoring unit 5.clearsmokealarm(5) -clear the smoke alarm for miniEsc
1.3.6.1.4.1.2011.6.1.1.1.1.8INTEGER {noOperation(1), reset(2), manage(3), unmanage(4), clearsmokealarm(5)}read-writecurrent
hwEnvSlaveNodeId
OBJECT-TYPE
ID of the slave object that the environment monitoring unit belongs to. The environment monitoring unit uses the slave object ID to communicate with the upstream equipment.
1.3.6.1.4.1.2011.6.1.1.1.1.9Integer32read-writecurrent
hwEnvComType
OBJECT-TYPE
The serial communication protocol type between the monitoring unit and the upstream equipment. The protocol types used are as follows: Options: 1.unknown(1) -The protocol types is unknown 2.serialRS485(2) -The protocol types is serialRS485 3.serialRS232(3) -The protocol types is serialRS232 4.serialRS422(4) -The protocol types is serialRS422
1.3.6.1.4.1.2011.6.1.1.1.1.10INTEGER {unknown(1), serialRS485(2), serialRS232(3), serialRS422(4)}read-writecurrent
hwEnvCLEICode
OBJECT-TYPE
Environment CLEI Code.
1.3.6.1.4.1.2011.6.1.1.1.1.11OCTET STRING (SIZE(0..640))read-onlycurrent
hwEnvEmuPower
OBJECT-TYPE
Power of the environment monitoring equipment associated with the environment monitoring unit. Unit: Watt.
1.3.6.1.4.1.2011.6.1.1.1.1.12Integer32 (0..255)read-onlycurrent
hwEnvEmuTypeName
OBJECT-TYPE
Name of the environment type.
1.3.6.1.4.1.2011.6.1.1.1.1.13DisplayStringread-onlycurrent
hwAnaChannelTable
OBJECT-TYPE
Information table of the analog parameters monitored. The indexes of this table are hwEnvEmuIndex or hwAnaChannelIndex. hwEnvEmuIndex is the index of the environment monitoring unit, and hwAnaChannelIndex is the index of the analog parameter that is monitored by a monitoring unit.
1.3.6.1.4.1.2011.6.1.1.2not-accessiblecurrent
hwAnaChannelEntry
OBJECT-TYPE
Information table of the analog parameters monitored. The indexes of this entry are hwEnvEmuIndex or hwAnaChannelIndex. hwEnvEmuIndex is the index of the environment monitoring unit, and hwAnaChannelIndex is the index of the analog parameter that is monitored by a monitoring unit.
1.3.6.1.4.1.2011.6.1.1.2.1not-accessiblecurrent
hwAnaChannelIndex
OBJECT-TYPE
Index of the analog parameter that is monitored by the monitoring unit. Range: 0 - 255
1.3.6.1.4.1.2011.6.1.1.2.1.1Integer32 (0..255)read-onlycurrent
hwAnaName
OBJECT-TYPE
Name of the analog parameter that is monitored by a monitoring unit.
1.3.6.1.4.1.2011.6.1.1.2.1.2DisplayStringread-writecurrent
hwAnaType
OBJECT-TYPE
This object indicates the type of the sensor that is used to test the Analog parameter. Options: 1.invalid(-1) -there is no valid sensor 2.voltage(1) -voltage sensor currently 3.current(2) -current sensor currently
1.3.6.1.4.1.2011.6.1.1.2.1.3INTEGER {invalid(-1), voltage(1), current(2)}read-writecurrent
hwAnaMeasureType
OBJECT-TYPE
This object indicates the unit of the analog parameter that is tested.
1.3.6.1.4.1.2011.6.1.1.2.1.4DisplayStringread-writecurrent
hwAnaWorkHigh
OBJECT-TYPE
High limit of the analog normal work
1.3.6.1.4.1.2011.6.1.1.2.1.5Integer32read-writecurrent
hwAnaWorkLow
OBJECT-TYPE
Low limit of the analog normal work
1.3.6.1.4.1.2011.6.1.1.2.1.6Integer32read-writecurrent
hwAnaAlmHigh
OBJECT-TYPE
High limit of the analog alarm. The alarm is produced when the measurement value is higher than this value
1.3.6.1.4.1.2011.6.1.1.2.1.7Integer32read-writecurrent
hwAnaAlmLow
OBJECT-TYPE
The low limit of the analog alarm. The alarm is produced when the measurement value is lower than this value.
1.3.6.1.4.1.2011.6.1.1.2.1.8Integer32read-writecurrent
hwAnaCurrentValue
OBJECT-TYPE
The actual measurement value of the present analog. Unit: milli
1.3.6.1.4.1.2011.6.1.1.2.1.9Integer32read-onlycurrent
hwAnaAlarmState
OBJECT-TYPE
The status of the present monitored. Options: 1.normal(1) -indicates that the measurement value is lower than the set high limit of the alarm, and higher than the low limit 2.overWorkHigh(2) -indicates that the measurement value is higher than the high limit of the alarm 3.belowWorkLow(3) -indicates that the measurement value is lower than the low limit of the alarm 4.abnormal(4) -indicates that the measurement value is outside the scope of limit of the alarm 5.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.1.1.2.1.10INTEGER {invalid(-1), normal(1), overWorkHigh(2), belowWorkLow(3), abnormal(4)}read-onlycurrent
hwAnaRowStatus
OBJECT-TYPE
RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
1.3.6.1.4.1.2011.6.1.1.2.1.11RowStatusread-writecurrent
hwAnaAlarmID
OBJECT-TYPE
Analog alarm definition. Options: 1.temperature(1) -temperature alarm 2.humidity(2) -humidity alarm 3.voltage(3) -voltage alarm 4.current(4) -current alarm 5.userDefinedAlarm0(100) -analog user-defined alarm 0 6.userDefinedAlarm1(101) -analog user-defined alarm 1 7.userDefinedAlarm2(102) -analog user-defined alarm 2 8.userDefinedAlarm3(103) -analog user-defined alarm 3 9.userDefinedAlarm4(104) -analog user-defined alarm 4 10.userDefinedAlarm5(105) -analog user-defined alarm 5 11.userDefinedAlarm6(106) -analog user-defined alarm 6 12.userDefinedAlarm7(107) -analog user-defined alarm 7 13.userDefinedAlarm8(108) -analog user-defined alarm 8 14.userDefinedAlarm9(109) -analog user-defined alarm 9 15.userDefinedAlarm10(110) -analog user-defined alarm 10 16.userDefinedAlarm11(111) -analog user-defined alarm 11 17.userDefinedAlarm12(112) -analog user-defined alarm 12 18.userDefinedAlarm13(113) -analog user-defined alarm 13 19.userDefinedAlarm14(114) -analog user-defined alarm 14 20.userDefinedAlarm15(115) -analog user-defined alarm 15 21.default(65535) -default analog alarm
1.3.6.1.4.1.2011.6.1.1.2.1.12INTEGER {temperature(1), humidity(2), voltage(3), current(4), userDefinedAlarm0(100), userDefinedAlarm1(101), userDefinedAlarm2(102), userDefinedAlarm3(103), userDefinedAlarm4(104), userDefinedAlarm5(105), userDefinedAlarm6(106), userDefinedAlarm7(107), userDefinedAlarm8(108), userDefinedAlarm9(109), userDefinedAlarm10(110), userDefinedAlarm11(111), userDefinedAlarm12(112), userDefinedAlarm13(113), userDefinedAlarm14(114), userDefinedAlarm15(115), default(65535)}read-writecurrent
hwDigChannelTable
OBJECT-TYPE
Information table of the digital parameters monitored. The indexes of this table are hwEnvEmuIndex and hwDigChannelIndex. hwEnvEmuIndex is the index of the environment monitoring unit, and hwDigChannelIndex is the index of the digital parameter that is monitored by a monitoring unit.
1.3.6.1.4.1.2011.6.1.1.3not-accessiblecurrent
hwDigChannelEntry
OBJECT-TYPE
Information table of the digital parameters monitored. The indexes of this entry are hwEnvEmuIndex and hwDigChannelIndex. hwEnvEmuIndex is the index of the environment monitoring unit, and hwDigChannelIndex is the index of the digital parameter that is monitored by a monitoring unit.
1.3.6.1.4.1.2011.6.1.1.3.1not-accessiblecurrent
hwDigChannelIndex
OBJECT-TYPE
Index of the digital parameter that is monitored by a monitoring unit. Range: 0 - 255
1.3.6.1.4.1.2011.6.1.1.3.1.1Integer32 (0..255)read-onlycurrent
hwDigChannelName
OBJECT-TYPE
Name of the digital parameter that is monitored by a monitoring unit.
1.3.6.1.4.1.2011.6.1.1.3.1.2DisplayStringread-writecurrent
hwAlmCondition
OBJECT-TYPE
Alarm conditions. Options: 1.lowLevelAlarm(1) -refers to the alarm produced when the digital sensor detects the low level 2.highLevelAlarm(2) -refers to the alarm produced when the digital sensor detects the high level 3.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.1.1.3.1.3INTEGER {invalid(-1), lowLevelAlarm(1), highLevelAlarm(2)}read-writecurrent
hwDigChannelState
OBJECT-TYPE
The status of the present monitored digital sensor Options: 1.normal(1) -indicates that the digital sensor works normally 2.alarm(2) -indicates that the digital sensor produces the alarm signal 3.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.1.1.3.1.4INTEGER {invalid(-1), normal(1), alarm(2)}read-onlycurrent
hwDigRowStatus
OBJECT-TYPE
RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
1.3.6.1.4.1.2011.6.1.1.3.1.5RowStatusread-writecurrent
hwDigAlarmID
OBJECT-TYPE
Digital alarm definition. Options: 1.acvoltage(1) -ac voltage alarm 2.acswitch(2) -ac switch alarm 3.batteryvoltage(3) -battery voltage alarm 4.batteryfuse(4) -battery fuse alarm 5.loadfuse(5) -load fuse alarm 6.rectifier(6) -rectifier alarm 7.dcpower(7) -dc power alarm 8.cupboarddoor(8) -cupboard alarm 9.roomdoor(9) -room door alarm 10.window(10) -window alarm 11.thief(11) -thief alarm 12.wiring(12) -wiring alarm 13.fan(13) -fan alarm 14.fire(14) -fire alarm 15.fog(15) -fog alarm 16.water(16) -water alarm 17.diesel(17) -diesel alarm 18.smell(18) -smell alarm 19.aircondition(19) -air-condition alarm 20.arrester(20) -arrester alarm 21.dcvoltage(21) -dc voltage 22.outputswitch(22) -output swith 23.hard-fault(23) -hard-fault 24.userDefinedAlarm0(100) -digital user-defined alarm 0 25.userDefinedAlarm1(101) -digital user-defined alarm 1 26.userDefinedAlarm2(102) -digital user-defined alarm 2 27.userDefinedAlarm3(103) -digital user-defined alarm 3 28.userDefinedAlarm4(104) -digital user-defined alarm 4 29.userDefinedAlarm5(105) -digital user-defined alarm 5 30.userDefinedAlarm6(106) -digital user-defined alarm 6 31.userDefinedAlarm7(107) -digital user-defined alarm 7 32.userDefinedAlarm8(108) -digital user-defined alarm 8 33.userDefinedAlarm9(109) -digital user-defined alarm 9 34.userDefinedAlarm10(110) -digital user-defined alarm 10 35.userDefinedAlarm11(111) -digital user-defined alarm 11 36.userDefinedAlarm12(112) -digital user-defined alarm 12 37.userDefinedAlarm13(113) -digital user-defined alarm 13 38.userDefinedAlarm14(114) -digital user-defined alarm 14 39.userDefinedAlarm15(115) -digital user-defined alarm 15 40.userDefinedAlarm16(116) -digital user-defined alarm 16 41.userDefinedAlarm17(117) -digital user-defined alarm 17 42.userDefinedAlarm18(118) -digital user-defined alarm 18 43.userDefinedAlarm19(119) -digital user-defined alarm 19 44.userDefinedAlarm20(120) -digital user-defined alarm 20 45.userDefinedAlarm21(121) -digital user-defined alarm 21 46.userDefinedAlarm22(122) -digital user-defined alarm 22 47.userDefinedAlarm23(123) -digital user-defined alarm 23 48.userDefinedAlarm24(124) -digital user-defined alarm 24 49.userDefinedAlarm25(125) -digital user-defined alarm 25 50.userDefinedAlarm26(126) -digital user-defined alarm 26 51.userDefinedAlarm27(127) -digital user-defined alarm 27 52.userDefinedAlarm28(128) -digital user-defined alarm 28 53.userDefinedAlarm29(129) -digital user-defined alarm 29 54.userDefinedAlarm30(130) -digital user-defined alarm 30 55.userDefinedAlarm31(131) -digital user-defined alarm 31 56.default(65535) -digital alarm
1.3.6.1.4.1.2011.6.1.1.3.1.6INTEGER {acvoltage(1), acswitch(2), batteryvoltage(3), batteryfuse(4), loadfuse(5), rectifier(6), dcpower(7), cupboarddoor(8), roomdoor(9), window(10), thief(11), wiring(12), fan(13), fire(14), fog(15), water(16), diesel(17), smell(18), aircondition(19), arrester(20), dcvoltage(21), outputswitch(22), hard-fault(23), userDefinedAlarm0(100), userDefinedAlarm1(101), userDefinedAlarm2(102), userDefinedAlarm3(103), userDefinedAlarm4(104), userDefinedAlarm5(105), userDefinedAlarm6(106), userDefinedAlarm7(107), userDefinedAlarm8(108), userDefinedAlarm9(109), userDefinedAlarm10(110), userDefinedAlarm11(111), userDefinedAlarm12(112), userDefinedAlarm13(113), userDefinedAlarm14(114), userDefinedAlarm15(115), userDefinedAlarm16(116), userDefinedAlarm17(117), userDefinedAlarm18(118), userDefinedAlarm19(119), userDefinedAlarm20(120), userDefinedAlarm21(121), userDefinedAlarm22(122), userDefinedAlarm23(123), userDefinedAlarm24(124), userDefinedAlarm25(125), userDefinedAlarm26(126), userDefinedAlarm27(127), userDefinedAlarm28(128), userDefinedAlarm29(129), userDefinedAlarm30(130), userDefinedAlarm31(131), default(65535)}read-writecurrent
hwControlOutTable
OBJECT-TYPE
Monitored digital out table. This table indicates information about whether digital parameter is monitored. The indexes of this table are hwEnvEmuIndex and hwControlOutIndex. hwEnvEmuIndex is the index of the monitoring unit, and hwControlOutIndex is the index of the digital out table monitored in the monitoring unit.
1.3.6.1.4.1.2011.6.1.1.4not-accessiblecurrent
hwControlOutEntry
OBJECT-TYPE
Monitored digital out table. This table indicates information about whether digital parameter is monitored. The indexes of this entry are hwEnvEmuIndex and hwControlOutIndex. hwEnvEmuIndex is the index of the monitoring unit, and hwControlOutIndex is the index of the digital out table monitored in the monitoring unit.
1.3.6.1.4.1.2011.6.1.1.4.1not-accessiblecurrent
hwControlOutIndex
OBJECT-TYPE
Index of the digital out table monitored in the monitoring unit Range: 0 - 255
1.3.6.1.4.1.2011.6.1.1.4.1.1Integer32 (0..255)read-onlycurrent
hwControlOutName
OBJECT-TYPE
Name of the monitored digital out table
1.3.6.1.4.1.2011.6.1.1.4.1.2DisplayStringread-writecurrent
hwControlOutAdminStatus
OBJECT-TYPE
Control Out administration: executes the on/off operation. Options: 1. on(1) - trun on 2. off(2) - trun off
1.3.6.1.4.1.2011.6.1.1.4.1.3INTEGER {on(1), off(2)}read-writecurrent
hwControlOutRowStatus
OBJECT-TYPE
RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
1.3.6.1.4.1.2011.6.1.1.4.1.4RowStatusread-writecurrent
hwFanTable
OBJECT-TYPE
Information table of fan monitoring. The index of this table is hwEnvEmuIndex that comes from hwEnvironmentInfoTable. hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is fan.
1.3.6.1.4.1.2011.6.1.1.5not-accessiblecurrent
hwFanEntry
OBJECT-TYPE
Information table of fan monitoring. The index of this entry is hwEnvEmuIndex that comes from hwEnvironmentInfoTable. hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is fan.
1.3.6.1.4.1.2011.6.1.1.5.1not-accessiblecurrent
hwFanName
OBJECT-TYPE
Fan name
1.3.6.1.4.1.2011.6.1.1.5.1.1DisplayStringread-writecurrent
hwFanControlMode
OBJECT-TYPE
The fan control modes of the fan frame. Options: 1.manual(1) -indicates that the fan is always on, and the fan speed can be manually adjusted 2.emuAuto(2) -indicates that the fan is in the automatic mode, and can be automatically controlled depending on the temperature of the fan 3.fixed(3) -indicates that the fan is in the fixed mode, and adjusting its speed is not allowed 4.mainboardAuto(4) -indicates that the fan is in the automatic mode, and can be automatically controlled depending on the temperature of the boards in the frame
1.3.6.1.4.1.2011.6.1.1.5.1.2INTEGER {manual(1), emuAuto(2), fixed(3), mainboardAuto(4)}read-writecurrent
hwFanControlState
OBJECT-TYPE
For ESC fan, all should be checked to turn on the fan, while all should not be checked to turn off the fan. Options: 1.fan1(0) -indicates that the first fan needs to be opened 2.fan2(1) -indicates that the second fan needs to be opened 3.fan3(2) -indicates that the third fan needs to be opened 4.fan4(3) -indicates that the fourth fan needs to be opened 5.fan5(4) -indicates that the fifth fan needs to be opened 6.fan6(5) -indicates that the sixth fan needs to be opened
1.3.6.1.4.1.2011.6.1.1.5.1.3Bits {fan1(0), fan2(1), fan3(2), fan4(3), fan5(4), fan6(5)}read-writecurrent
hwESCFanTempAutoOn
OBJECT-TYPE
The fan temperature set, in unit of centigrade. The MIB object only functions for the fan monitoring board of ESC and is not applicable to the type of fan monitoring board. Only when the fan control mode of the fan frame is hwFanControl =auto (3), the temperature control mode will take effect. When detecting the environment temperature higher than the set value, the fan will be on (or increase its rotation).
1.3.6.1.4.1.2011.6.1.1.5.1.4Integer32read-writecurrent
hwESCFanTempAutoOff
OBJECT-TYPE
The fan temperature set, in unit of centigrade. The MIB object only functions for the fan monitoring board of ESC and is not applicable to the type of fan monitoring board. Only when the fan control mode of the fan frame is hwFanControl =auto (3), the temperature control mode will take effect. When detecting the environment temperature is lower than the set value, the fan will be turned off (decrease its rotation).
1.3.6.1.4.1.2011.6.1.1.5.1.5Integer32read-writecurrent
hwFanRowStatus
OBJECT-TYPE
RowStatus standard operation.
1.3.6.1.4.1.2011.6.1.1.5.1.6RowStatusread-writecurrent
hwCurrentTemp
OBJECT-TYPE
The present temperature value, in unit of cent-centigrade
1.3.6.1.4.1.2011.6.1.1.5.1.7Integer32read-onlycurrent
hwFanSpeedMode
OBJECT-TYPE
The adjusting rotation mode of the fan. Options: 1.continue(1) -continuous control 2.discontinue(2) -discrete control 3.percent(3) -duty ratio control 4.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
1.3.6.1.4.1.2011.6.1.1.5.1.8INTEGER {invalid(-1), continue(1), discontinue(2), percent(3)}read-writecurrent
hwFanSpeed
OBJECT-TYPE
When hwFanSpeedMode is the continue mode, 0 indicates the present wind speed +1, while 1 indicates the present wind speed -1. When hwFanSpeedMode is discontinuous, 0 indicates fixed high speed, while 1 indicates fixed low speed. When hwFanSpeedMode is percent, the value delivered by the main control is the percent value, ranging from 35 to 100, used to initialize the rotation of fan for various device main controls. invalid(-1) indicates that the fan tray does not work normally. For example, the fan tray is disconnected from the control board, or some of the fans in the fan tray are blocked.
1.3.6.1.4.1.2011.6.1.1.5.1.9Integer32read-writecurrent
hwFanTypeDescription
OBJECT-TYPE
Fan Type Description. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
1.3.6.1.4.1.2011.6.1.1.5.1.10DisplayStringread-onlycurrent
hwTcuTable
OBJECT-TYPE
Information table of temperature control unit. The index of this table is hwEnvEmuIndex that comes from hwEnvironmentInfoTable. hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is temperature control unit.
1.3.6.1.4.1.2011.6.1.1.6not-accessiblecurrent
hwTcuEntry
OBJECT-TYPE
Information table of temperature control unit. The index of this entry is hwEnvEmuIndex that comes from hwEnvironmentInfoTable. hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is temperature control unit.
1.3.6.1.4.1.2011.6.1.1.6.1not-accessiblecurrent
hwTcuHeatExchangerType
OBJECT-TYPE
Heat Exchanger Type Description.
1.3.6.1.4.1.2011.6.1.1.6.1.1DisplayStringread-onlycurrent
hwTcuExternalFanRev
OBJECT-TYPE
The rev of Heat Exchanger outer fan, in unit of RMP (rotate per minite)
1.3.6.1.4.1.2011.6.1.1.6.1.2Integer32read-onlycurrent
hwTcuInternalFanRev
OBJECT-TYPE
The rev of Heat Exchanger inner fan, in unit of RMP (rotate per minite)
1.3.6.1.4.1.2011.6.1.1.6.1.3Integer32read-onlycurrent
hwTcuStartHeatTemp
OBJECT-TYPE
The temperature of Heat Exchanger starts to heat up, in unit of Celsius
1.3.6.1.4.1.2011.6.1.1.6.1.4Integer32read-writecurrent
hwTcuStopHeatTemp
OBJECT-TYPE
The temperature of Heat Exchanger stops heating, in unit of Celsius
1.3.6.1.4.1.2011.6.1.1.6.1.5Integer32read-writecurrent
hwOpticalreceiverTable
OBJECT-TYPE
Information table of optical receiver unit. The index of this table is hwFrameIndex that comes from hwFrameTable. hwFrameIndex is the index of the optical receiver unit whose optical receiver type is optical receiver unit.
1.3.6.1.4.1.2011.6.1.1.7not-accessiblecurrent
hwOpticalreceiverEntry
OBJECT-TYPE
Information table of optical receiver unit. interface optical receiver config mode.
1.3.6.1.4.1.2011.6.1.1.7.1not-accessiblecurrent
hwORCOMState
OBJECT-TYPE
The state of Optical receiver The Optical receiver can be used only when it is online. Options: 1.online(1) - indicates that Optical state is online 2.offline(2) - indicates that Optical state is offline
1.3.6.1.4.1.2011.6.1.1.7.1.1INTEGER {online(1), offline(2)}read-onlycurrent
hwORModelNumber
OBJECT-TYPE
The model number of Optical receiver
1.3.6.1.4.1.2011.6.1.1.7.1.2DisplayStringread-onlycurrent
hwORHardwareVer
OBJECT-TYPE
The hard version of Optical receiver
1.3.6.1.4.1.2011.6.1.1.7.1.3DisplayStringread-onlycurrent
hwORSoftwareVer
OBJECT-TYPE
The software version of Optical receiver
1.3.6.1.4.1.2011.6.1.1.7.1.4DisplayStringread-onlycurrent
hwORProductDate
OBJECT-TYPE
The product date of Optical receiver field octets contents range ----- ------ -------- ----- 1 1-2 year 0..65536 2 3 month 1..12 3 4 day 1..31
1.3.6.1.4.1.2011.6.1.1.7.1.5OCTET STRING (SIZE(4))read-onlycurrent
hwOROpticalPowerValue
OBJECT-TYPE
The optical power value of Optical receiver Its unit is dbm,its real accuracy is 0.01. SNMP uses it which has been enlarged 100 by host. user uses it which has been lessened 100 by SNMP.
1.3.6.1.4.1.2011.6.1.1.7.1.6Integer32read-onlycurrent
hwOROpticalPowerAlarmState
OBJECT-TYPE
The optical power alarm state of Optical receiver The Optical receiver can be used only when it is normal. Options: 1.normal(1) - indicates that Optical power alarm state is normal 2.low(2) - indicates that Optical power alarm state is low 3.high(3) - indicates that Optical power alarm state is high
1.3.6.1.4.1.2011.6.1.1.7.1.7INTEGER {normal(1), low(2), high(3)}read-onlycurrent
hwOROpticalPowerLowThreshold
OBJECT-TYPE
The optical power low threshold of Optical receiver Its unit is dbm,its real accuracy is 0.01. SNMP uses it which has been enlarged 100 by host. user uses it which has been lessened 100 by SNMP. Its real range is -10dbm~3dbm,mib range is -1000dbm~300dbm.
1.3.6.1.4.1.2011.6.1.1.7.1.8Integer32read-writecurrent
hwOROpticalPowerHighThreshold
OBJECT-TYPE
The optical power high threshold of Optical receiver Its unit is dbm,its real accuracy is 0.01. SNMP uses it which has been enlarged 100 by host. user uses it which has been lessened 100 by SNMP. Its real range is -10dbm~3dbm,mib range is -1000dbm~300dbm.
1.3.6.1.4.1.2011.6.1.1.7.1.9Integer32read-writecurrent
hwOROpticalAGCStart
OBJECT-TYPE
The optical AGC start of Optical receiver Its unit is dBm,its real range is -4dBm~3dBm.
1.3.6.1.4.1.2011.6.1.1.7.1.10Integer32read-writecurrent
hwORRFPowerValue
OBJECT-TYPE
The RF power value of Optical receiver Its unit is dBuV,its real accuracy is 0.1. SNMP uses it which has been enlarged 10 by host. user uses it which has been lessened 10 by SNMP.
1.3.6.1.4.1.2011.6.1.1.7.1.11Integer32read-onlycurrent
hwORRFPowerAlarmState
OBJECT-TYPE
The RF power alarm state of Optical receiver The Optical receiver can be used only when it is normal. Options: 1.normal(1) - indicates that RF power alarm state is normal 2.low(2) - indicates that RF power alarm state is low 3.high(3) - indicates that RF power alarm state is high
1.3.6.1.4.1.2011.6.1.1.7.1.12INTEGER {normal(1), low(2), high(3)}read-onlycurrent
hwORRFPowerLowThreshold
OBJECT-TYPE
The RF power low threshold of Optical receiver Its unit is dBuV,its real accuracy is 0.1. SNMP uses it which has been enlarged 10 by host. user uses it which has been lessened 10 by SNMP. Its real range is 85dBuV~130dBuV,mib range is 850dBuV~1300dBuV.
1.3.6.1.4.1.2011.6.1.1.7.1.13Integer32read-writecurrent
hwORRFPowerHighThreshold
OBJECT-TYPE
The RF power high threshold of Optical receiver Its unit is dBuV,its real accuracy is 0.1. SNMP uses it which has been enlarged 10 by host. user uses it which has been lessened 10 by SNMP. Its real range is 85dBuV~130dBuV,mib range is 850dBuV~1300dBuV.
1.3.6.1.4.1.2011.6.1.1.7.1.14Integer32read-writecurrent
hwORRFAttValue
OBJECT-TYPE
The RF ATT value of Optical receiver Its unit is db. Its range is 0db~20db.
1.3.6.1.4.1.2011.6.1.1.7.1.15Integer32read-writecurrent
hwORRFSwitch
OBJECT-TYPE
The RF switch of Optical receiver The Optical receiver can be used only when it is on. Options: 1.off(1) - indicates that RF Switch state is off 2.on(2) - indicates that RF Switch state is on
1.3.6.1.4.1.2011.6.1.1.7.1.16INTEGER {off(1), on(2)}read-writecurrent
hwORBarcode
OBJECT-TYPE
The barcode of Optical receiver
1.3.6.1.4.1.2011.6.1.1.7.1.17DisplayStringread-onlycurrent
hwOR5VVoltage
OBJECT-TYPE
The current input voltage of Optical receiver. Its unit is V,its real accuracy is 0.1. SNMP uses it which has been enlarged 10 by host. user uses it which has been lessened 10 by SNMP. +5V is positive voltage.
1.3.6.1.4.1.2011.6.1.1.7.1.18Integer32read-onlycurrent
hwOR24VVoltage
OBJECT-TYPE
The current input voltage of Optical receiver. Its unit is V,its real accuracy is 0.1. SNMP uses it which has been enlarged 10 by host. user uses it which has been lessened 10 by SNMP. +24V is positive voltage.
1.3.6.1.4.1.2011.6.1.1.7.1.19Integer32read-onlycurrent
hwORAGCRange
OBJECT-TYPE
Start value of the AGC range for optical paths of Optical receiver.
1.3.6.1.4.1.2011.6.1.1.7.1.20DisplayStringread-onlycurrent
snmpTrapsDef
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.2
emmsnmpTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.2.0
envConformance
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.3
envCompliances
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.3.1
envGroups
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.3.2
hwEnvironTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4
hwEnvironCommonTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4.1
hwEnvironCommonTrapsPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4.1.0
hwEnvironAlarmTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4.2
hwEnvironEmuAlarmTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4.2.1
hwEnvironEmuAlarmTrapsPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4.2.1.0
hwEnvironAnaAlarmTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4.2.2
hwEnvironAnaAlarmTrapsPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4.2.2.0
hwEnvironDigAlarmTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4.2.3
hwEnvironDigAlarmTrapsPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.4.2.3.0
hwEmmTrapVbOids
OBJECT-IDENTITY
1.3.6.1.4.1.2011.6.1.5
hwFanStatus
OBJECT-TYPE
The status of the fan. Options: 1.notconfig(1) -The status of the fan is notconfig 2.failure(2) -The status of the fan is fail
1.3.6.1.4.1.2011.6.1.5.1INTEGER {notconfig(1), failure(2)}accessible-for-notifycurrent
hwFailureCause
OBJECT-TYPE
The reason of the auto-finding failure: Options: 1.fullemu(1) -No enough EMU IDs are available 2.shelfnotsupport(2) -The EMU does not support the auto discovery function 3.emunotsupportautofind(3) -The shelf does not support the EMU of this type
1.3.6.1.4.1.2011.6.1.5.2INTEGER {fullemu(1), shelfnotsupport(2), emunotsupportautofind(3)}accessible-for-notifycurrent
hwEnvAutofindNodeId
OBJECT-TYPE
The NodeId of the auto-found EMU.
1.3.6.1.4.1.2011.6.1.5.3Integer32accessible-for-notifycurrent
hwEnvAutofindEmuType
OBJECT-TYPE
The type of the auto-found EMU.
1.3.6.1.4.1.2011.6.1.5.4OCTET STRINGaccessible-for-notifycurrent
hwEnvAutofindBoardName
OBJECT-TYPE
The board name of the auto-found EMU.
1.3.6.1.4.1.2011.6.1.5.5OCTET STRINGaccessible-for-notifycurrent

Notifications

NameOIDStatus
envCommAlarm
NOTIFICATION-TYPE
The communication alarm of environment monitoring board, reporting the environment monitoring unit ID. This trap message is reported when the communication between the emu and control board is fault.
1.3.6.1.4.1.2011.6.1.2.0.1current
envCommAlarmResume
NOTIFICATION-TYPE
The communication alarm recovery of the environment monitoring, reporting the environment monitoring unit ID. This trap message is reported when the communication between the emu and control board resumes.
1.3.6.1.4.1.2011.6.1.2.0.2current
anaFaultAlarm
NOTIFICATION-TYPE
The alarm recovery of the analog exception, reporting the environment monitoring unit ID. This trap message is reported when there is an analog exception in emu.
1.3.6.1.4.1.2011.6.1.2.0.3current
anaFaultAlarmResume
NOTIFICATION-TYPE
The alarm recovery of the analog exception, reporting the environment monitoring unit ID. This trap message is reported when the analog exception recovery in emu.
1.3.6.1.4.1.2011.6.1.2.0.4current
anaTooHighAlarm
NOTIFICATION-TYPE
The alarm of too high an analog, reporting the environment monitoring unit ID and the channel ID of the analog sensor. This trap message is reported when an analog value is too high.
1.3.6.1.4.1.2011.6.1.2.0.5current
anaTooHighAlarmResume
NOTIFICATION-TYPE
The alarm of too high analog resume, reporting the environment monitoring unit ID. This trap message is reported when an analog value returns to normal range from the high value.
1.3.6.1.4.1.2011.6.1.2.0.6current
anaTooLowAlarm
NOTIFICATION-TYPE
The alarm of too low an analog, reporting the environment monitoring unit ID and the channel ID of the analog sensor. This trap message is reported when an analog value is too low.
1.3.6.1.4.1.2011.6.1.2.0.7current
anaTooLowAlarmResume
NOTIFICATION-TYPE
The alarm of too low an analog, reporting the environment monitoring unit ID. This trap message is reported when an analog value returns to normal range from the low value.
1.3.6.1.4.1.2011.6.1.2.0.8current
controlAlarm
NOTIFICATION-TYPE
The control alarm, reporting the environment monitoring unit ID. This trap message is reported when emu control operation fails.
1.3.6.1.4.1.2011.6.1.2.0.9current
controlAlarmResume
NOTIFICATION-TYPE
The control alarm, reporting the environment monitoring unit ID. This trap message is reported when emu control operation resumes.
1.3.6.1.4.1.2011.6.1.2.0.10current
digtalMeasureAlarm
NOTIFICATION-TYPE
The digital measure alarm, reporting the environment monitoring unit ID and the channel ID of the digital sensor. This trap message is reported when emu measure operation fails.
1.3.6.1.4.1.2011.6.1.2.0.11current
digtaleasureAlarmResume
NOTIFICATION-TYPE
The digital measure alarm recovery, reporting the environment monitoring unit ID and the channel ID of the digital sensor. This trap message is reported when emu measure operation resumes.
1.3.6.1.4.1.2011.6.1.2.0.12current
fanExistsAlarm
NOTIFICATION-TYPE
Fan nonexistance alarm. This trap message is reported when there is no fan device connected to control board.
1.3.6.1.4.1.2011.6.1.2.0.13current
fanExistsAlarmResume
NOTIFICATION-TYPE
Fan nonexistance alarm recovery. This trap message is reported when there is a fan device connected to control board.
1.3.6.1.4.1.2011.6.1.2.0.14current
fanRunStateAlarm
NOTIFICATION-TYPE
Fan running status alarm. This trap message is reported when the fan run state gets abnormal.
1.3.6.1.4.1.2011.6.1.2.0.15current
hwEmmEmuAutofindTrap
NOTIFICATION-TYPE
The agent generates this trap when a new EMU autofind.
1.3.6.1.4.1.2011.6.1.4.1.0.1current
hwEmmEmufailTrap
NOTIFICATION-TYPE
The agent generates this trap when the communication of the EMU with the host is abnormal.
1.3.6.1.4.1.2011.6.1.4.2.1.0.1current
hwEmmEmuRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the communication of the EMU with the host recovers.
1.3.6.1.4.1.2011.6.1.4.2.1.0.2current
hwEmmEmuHardwareFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the a Hardware exception occurs.
1.3.6.1.4.1.2011.6.1.4.2.1.0.3current
hwEmmEmuHardwareRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the a Hardware exception Recover
1.3.6.1.4.1.2011.6.1.4.2.1.0.4current
hwEmmEmuAutofindFailTrap
NOTIFICATION-TYPE
The agent generates this trap when the emu autofind fail.
1.3.6.1.4.1.2011.6.1.4.2.1.0.5current
hwEmmEmuFanStateTrap
NOTIFICATION-TYPE
The agent generates this trap when the fan is not configured or fails.
1.3.6.1.4.1.2011.6.1.4.2.1.0.6current
hwOpticalReceiverFailTrap
NOTIFICATION-TYPE
The agent generates this trap when the communication of the OpticalReceiver with the host is abnormal.
1.3.6.1.4.1.2011.6.1.4.2.1.0.7current
hwOpticalReceiverRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the communication of the OpticalReceiver with the host recovers.
1.3.6.1.4.1.2011.6.1.4.2.1.0.8current
hwOpticalReceiverPowerFailTrap
NOTIFICATION-TYPE
The agent generates this trap when the optical power of OpticalReceiver is abnormal.
1.3.6.1.4.1.2011.6.1.4.2.1.0.9current
hwOpticalReceiverPowerRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the optical power of OpticalReceiver recovers to normal rage.
1.3.6.1.4.1.2011.6.1.4.2.1.0.10current
hwOpticalReceiverRFPowerFailTrap
NOTIFICATION-TYPE
The agent generates this trap when the RF power of OpticalReceiver is abnormal.
1.3.6.1.4.1.2011.6.1.4.2.1.0.11current
hwOpticalReceiverRFPowerRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the RF power of OpticalReceiver recovers to normal rage.
1.3.6.1.4.1.2011.6.1.4.2.1.0.12current
hwEmmAnaUnnamedFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when an unnamed analog alarm occurs.
1.3.6.1.4.1.2011.6.1.4.2.2.0.1current
hwEmmAnaUnnamedRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when an unnamed analog alarm recovers.
1.3.6.1.4.1.2011.6.1.4.2.2.0.2current
hwEmmAnaTempFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the analog temperature alarm occurs.
1.3.6.1.4.1.2011.6.1.4.2.2.0.3current
hwEmmAnaTempRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the analog temperature alarm recovers.
1.3.6.1.4.1.2011.6.1.4.2.2.0.4current
hwEmmAnaHumyFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the analog humidity alarm occurs.
1.3.6.1.4.1.2011.6.1.4.2.2.0.5current
hwEmmAnaHumyRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the analog humidity alarm recovers.
1.3.6.1.4.1.2011.6.1.4.2.2.0.6current
hwEmmAnaVoltFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the analog voltage alarm occurs.
1.3.6.1.4.1.2011.6.1.4.2.2.0.7current
hwEmmAnaVoltRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the analog voltage alarm recovers.
1.3.6.1.4.1.2011.6.1.4.2.2.0.8current
hwEmmAnaCurrentFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the analog current alarm occurs.
1.3.6.1.4.1.2011.6.1.4.2.2.0.9current
hwEmmAnaCurrentRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the analog current alarm recovers.
1.3.6.1.4.1.2011.6.1.4.2.2.0.10current
hwEmmDigFanBlockFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the fan is blocked.
1.3.6.1.4.1.2011.6.1.4.2.3.0.1current
hwEmmDigFanBlockRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the fan is recovered from block.
1.3.6.1.4.1.2011.6.1.4.2.3.0.2current
hwEmmDigFanTempHighFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when the temperature of fan is too high.
1.3.6.1.4.1.2011.6.1.4.2.3.0.3current
hwEmmDigFanTempHighRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the temperature of fan recover from too high.
1.3.6.1.4.1.2011.6.1.4.2.3.0.4current
hwEmmDigUnnamedFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when a unnamed digital fault occurs.
1.3.6.1.4.1.2011.6.1.4.2.3.0.5current
hwEmmDigUnnamedRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when a unnamed digital recovers.
1.3.6.1.4.1.2011.6.1.4.2.3.0.6current
hwEmmDigOutputswitchFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when Output switch digital fault occurs.
1.3.6.1.4.1.2011.6.1.4.2.3.0.7current
hwEmmDigOutputswitchRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when Output switch digital recovers.
1.3.6.1.4.1.2011.6.1.4.2.3.0.8current
hwEmmDigAcvolFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The AC voltage is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.11current
hwEmmDigAcvolRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The AC voltage recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.12current
hwEmmDigAcswitchFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The AC switch is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.13current
hwEmmDigAcswitchRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The AC switch recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.14current
hwEmmDigBattvolFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The batt vol is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.15current
hwEmmDigBattvolRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The batt vol recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.16current
hwEmmDigBattfuseFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The battery fuse is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.17current
hwEmmDigBattfuseRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The battery fuse recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.18current
hwEmmDigLoadfuseFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The load fuse is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.19current
hwEmmDigLoadfuseRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The load fuse recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.20current
hwEmmDigRectifierFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The Rectifier is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.21current
hwEmmDigRectifierRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The Rectifier recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.22current
hwEmmDigDcpowerFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The dc-power is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.23current
hwEmmDigDcpowerRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The dc-power recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.24current
hwEmmDigRoomdoorFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The Roomdoor is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.25current
hwEmmDigRoomdoorRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The Roomdoor recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.26current
hwEmmDigTheftFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The Roomdoor is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.27current
hwEmmDigTheftRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The Roomdoor recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.28current
hwEmmDigWiringFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The WIRING is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.29current
hwEmmDigWiringRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The WIRING recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.30current
hwEmmDigFanFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The FAN is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.31current
hwEmmDigFanRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The FAN recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.32current
hwEmmDigFireFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The Fire is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.33current
hwEmmDigFireRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The Fire recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.34current
hwEmmDigFogFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The Fog is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.35current
hwEmmDigFogRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The Fog recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.36current
hwEmmDigWaterFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The Water is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.37current
hwEmmDigWaterRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The Water recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.38current
hwEmmDigDieselFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The Diesel is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.39current
hwEmmDigDieselRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The Diesel recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.40current
hwEmmDigSmellFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The Smell is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.41current
hwEmmDigSmellRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The Smell recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.42current
hwEmmDigAirconditionFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The Air condition is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.43current
hwEmmDigAirconditionRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The Air condition recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.44current
hwEmmDigArrsterFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The arrester is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.45current
hwEmmDigArrsterRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The arrester recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.46current
hwEmmDigDcvolFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when The DC VOL is out of the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.47current
hwEmmDigDcvolRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when The DC VOL recovers to the normal range.
1.3.6.1.4.1.2011.6.1.4.2.3.0.48current
hwEmmFanCriticalBlockFaultTrap
NOTIFICATION-TYPE
The agent generates this trap when more than two fans are blocked.
1.3.6.1.4.1.2011.6.1.4.2.3.0.49current
hwEmmFanCriticalBlockRecoverTrap
NOTIFICATION-TYPE
The agent generates this trap when the critical multi-fan blocking recovers.
1.3.6.1.4.1.2011.6.1.4.2.3.0.50current
hwEmmDigitalSwitchOpenTrap
NOTIFICATION-TYPE
The agent generates this trap when the 48V input switch is closed.
1.3.6.1.4.1.2011.6.1.4.2.3.0.51current
hwEmmDigitalSwitchCloseTrap
NOTIFICATION-TYPE
The agent generates this trap when the 48V input switch is opened.
1.3.6.1.4.1.2011.6.1.4.2.3.0.52current