HPN-ICF-UPS-MIB
- Registered at
- 1.3.6.1.4.1.11.2.14.11.15.2.82
- Last updated
- 2007-09-04 14:52
- Namespace
- hp
- Source file
HPN-ICF-UPS-MIB- Digest
sha256:e5de2576ce4da53850620d9ad56f367b3cc971f91521ffdb45970aac52bea448
Description
This MIB describes the general information of UPS(Uninterrupted Power Supply) device.
Imports
| From | Symbols |
|---|---|
| ENTITY-MIB | entPhysicalIndex |
| HPN-ICF-OID-MIB | hpnicfCommon |
| INET-ADDRESS-MIB | InetAddress, InetAddressType |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Counter32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
ENTITY-MIB HPN-ICF-OID-MIB HPN-ICF-UPS-MIB IANA-ENTITY-MIB INET-ADDRESS-MIB SNMP-FRAMEWORK-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC UUID-TC-MIB
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| HpnicfActionType TEXTUAL-CONVENTION A control variable used to trigger an operator events, when read, always returns a value of invalid. | current |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| hpnicfUpsMibObjects OBJECT-IDENTITY | 1.3.6.1.4.1.11.2.14.11.15.2.82.1 | |||
| hpnicfUpsConfigEnable OBJECT-TYPE This object identifies the operation which will make the UPS(Uninterrupted Power Supply)'s new configure become effective. | 1.3.6.1.4.1.11.2.14.11.15.2.82.1.1 | HpnicfActionType | read-write | current |
| hpnicfUpsConfigTable OBJECT-TYPE This table contains an entry for user to get some information about the UPS device. | 1.3.6.1.4.1.11.2.14.11.15.2.82.1.2 | not-accessible | current | |
| hpnicfUpsConfigEntry OBJECT-TYPE An entry containing management information applicable to a particular UPS. | 1.3.6.1.4.1.11.2.14.11.15.2.82.1.2.1 | not-accessible | current | |
| hpnicfUpsIndex OBJECT-TYPE This object identifies the index of hpnicfUpsConfigTable. The object identified by this index is the same object as identified by the same value of entPhysicalIndex. | 1.3.6.1.4.1.11.2.14.11.15.2.82.1.2.1.1 | Integer32 | not-accessible | current |
| hpnicfUpsType OBJECT-TYPE This object identifies the type of UPS. The value 'emersonUart' means an EMERSON UPS support UART interface. The value 'mge' means a MGE UPS support ethernet interface. The value 'common' means a common UPS support standard UPSMIB. The value 'emersonEth' means an EMERSON UPS support ethernet interface. The value 'liebert' means a Liebert UPS support ethernet interface. | 1.3.6.1.4.1.11.2.14.11.15.2.82.1.2.1.2 | INTEGER {emersonUart(1), mge(2), common(3), emersonEth(4), liebert(5)} | read-only | current |
| hpnicfUpsIpAddress OBJECT-TYPE This object describes the address of UPS. The value of this object is invalid if the UPS do not support ethernet interface. | 1.3.6.1.4.1.11.2.14.11.15.2.82.1.2.1.3 | InetAddress | read-write | current |
| hpnicfUpsIpAddressType OBJECT-TYPE This object describes the address type of UPS. The value of this object is invalid if the UPS do not support ethernet interface. | 1.3.6.1.4.1.11.2.14.11.15.2.82.1.2.1.4 | InetAddressType | read-write | current |