HHMSAGENT-MIB
- Registered at
- 1.3.6.1.4.1.3854
- Namespace
- akcp
- Source file
HHMSAGENT-MIB- Digest
sha256:0a839d43d86893df3531ecff4c11361edb729429ade42ed6ead8b2cf579c4d93
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
HHMSAGENT-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Under this module's arcs
Where the registration tree carries on below this module.
| Arc | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.3854.1 | hhmsagent | |
| 1.3.6.1.4.1.3854.2 | securityProbe | SPAGENT-MIB |
| 1.3.6.1.4.1.3854.3 | plusSeries | SPAGENT-MIB |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| akcp OBJECT-IDENTITY | 1.3.6.1.4.1.3854 | |||
| hhmsagent OBJECT-IDENTITY | 1.3.6.1.4.1.3854.1 | |||
| hhmsAgentSummary OBJECT-IDENTITY | 1.3.6.1.4.1.3854.1.1 | |||
| hhmsAgentLocation OBJECT-TYPE The Agent location | 1.3.6.1.4.1.3854.1.1.1 | DisplayString | read-write | mandatory |
| hhmsAgentStatus OBJECT-TYPE The current status of this Agent. The status of the agent is the worst status of all the sensors usder the control of this agent. | 1.3.6.1.4.1.3854.1.1.2 | INTEGER {noStatus(1), normal(2), warning(3), critical(4), sensorError(5)} | read-only | mandatory |
| hhmsNumberBadSensors OBJECT-TYPE How many sensors controlled by this agent are not functioning properly | 1.3.6.1.4.1.3854.1.1.4 | INTEGER | read-only | mandatory |
| hhmsLocationBadSensor OBJECT-TYPE The Location of the first bad sensor controlled by this agent. | 1.3.6.1.4.1.3854.1.1.5 | DisplayString | read-only | mandatory |
| hhmsAgentManufName OBJECT-TYPE The manufacturers name | 1.3.6.1.4.1.3854.1.1.6 | DisplayString | read-only | mandatory |
| hhmsAgentHelpUrl OBJECT-TYPE The URL of the web based help | 1.3.6.1.4.1.3854.1.1.7 | DisplayString | read-only | mandatory |
| hhmsAgentHtmlView OBJECT-TYPE Which view of the sensors the user is served via the web server | 1.3.6.1.4.1.3854.1.1.8 | INTEGER {sensorArray(1), sensorArrayPro(2), advanced(3)} | read-write | mandatory |
| hhmsAgentHtmlStandardTitle OBJECT-TYPE The titles of the standard html view | 1.3.6.1.4.1.3854.1.1.9 | DisplayString | read-write | mandatory |
| hhmsAgentHtmlStandardButton OBJECT-TYPE The buttons of the standard html view | 1.3.6.1.4.1.3854.1.1.10 | DisplayString | read-write | mandatory |
| hhmsSensor OBJECT-IDENTITY | 1.3.6.1.4.1.3854.1.2 | |||
| hhmsSensorArrayTable OBJECT-IDENTITY | 1.3.6.1.4.1.3854.1.2.2 | |||
| hhmsSensorArrayEntry OBJECT-IDENTITY | 1.3.6.1.4.1.3854.1.2.2.1 | |||
| hhmsSensorArrayHost OBJECT-TYPE The Host of this sensor, this is the IP address | 1.3.6.1.4.1.3854.1.2.2.1.1 | IpAddress | read-write | mandatory |
| hhmsSensorArrayUseDHCP OBJECT-TYPE To use DHCP enter a 1, to use a static IP address enter a 2 | 1.3.6.1.4.1.3854.1.2.2.1.2 | INTEGER {yes(1), no(2)} | read-write | mandatory |
| hhmsSensorArrayMAC OBJECT-TYPE The MAC address of this sensor. | 1.3.6.1.4.1.3854.1.2.2.1.3 | DisplayString | read-only | mandatory |
| hhmsSensorArraySetCommunity OBJECT-TYPE The sensorArray community string used for snmp Sets | 1.3.6.1.4.1.3854.1.2.2.1.4 | DisplayString | read-write | mandatory |
| hhmsSensorArrayGetCommunity OBJECT-TYPE The sensorArray community string used for snmp Gets | 1.3.6.1.4.1.3854.1.2.2.1.5 | DisplayString | read-write | mandatory |
| hhmsSensorArrayDescription OBJECT-TYPE A Description of this sensorArray | 1.3.6.1.4.1.3854.1.2.2.1.6 | DisplayString | read-write | mandatory |
| hhmsSensorArrayLocation OBJECT-TYPE The description of the physical location of this sensorArray | 1.3.6.1.4.1.3854.1.2.2.1.7 | DisplayString | read-write | mandatory |
| hhmsSensorArrayLastUpdate OBJECT-TYPE The last time the sensorArray was read | 1.3.6.1.4.1.3854.1.2.2.1.8 | DisplayString | read-only | mandatory |
| hhmsSensorArrayStatus OBJECT-TYPE The current status of this sensorArray | 1.3.6.1.4.1.3854.1.2.2.1.9 | INTEGER {noStatus(1), normal(2), sensorError(7)} | read-only | mandatory |
| hhmsSensorArrayOnline OBJECT-TYPE If this sensorArray is currently online | 1.3.6.1.4.1.3854.1.2.2.1.10 | INTEGER {online(1), offline(2)} | read-only | mandatory |
| hhmsSensorArrayGoOnline OBJECT-TYPE To put online enter a 1, to take offline enter a 2 | 1.3.6.1.4.1.3854.1.2.2.1.11 | INTEGER {goOnline(1), goOffline(2)} | read-write | mandatory |
| hhmsSensorArrayReadInterval OBJECT-TYPE How many seconds between readings of this sensor | 1.3.6.1.4.1.3854.1.2.2.1.12 | INTEGER | read-write | mandatory |
| hhmsSensorArrayReceiveTimeout OBJECT-TYPE How many seconds to wait to receive data from the sensor | 1.3.6.1.4.1.3854.1.2.2.1.13 | INTEGER | read-write | mandatory |
| hhmsSensorArrayReceiveRetries OBJECT-TYPE How many times to retry to receive data before giving up. A -1 means never give up trying | 1.3.6.1.4.1.3854.1.2.2.1.14 | INTEGER | read-write | mandatory |
| hhmsSensorArrayVersion OBJECT-TYPE The version of this SensorArray | 1.3.6.1.4.1.3854.1.2.2.1.15 | INTEGER | read-only | mandatory |
| hhmsSensorArrayTempTable OBJECT-TYPE This table contains the data for every Temperature Sensor in the SensorArray. Each row in the table contains data for a different Temperature Sensor. | 1.3.6.1.4.1.3854.1.2.2.1.16 | not-accessible | mandatory | |
| hhmsSensorArrayTempEntry OBJECT-TYPE This is an entry in the hhmsSensorArrayTempEntry Table | 1.3.6.1.4.1.3854.1.2.2.1.16.1 | not-accessible | mandatory | |
| hhmsSensorArrayTempDescription OBJECT-TYPE A Description of this sensor | 1.3.6.1.4.1.3854.1.2.2.1.16.1.1 | DisplayString | read-write | mandatory |
| hhmsSensorArrayTempLocation OBJECT-TYPE The physical location of this sensor | 1.3.6.1.4.1.3854.1.2.2.1.16.1.2 | DisplayString | read-write | mandatory |
| hhmsSensorArrayTempDegree OBJECT-TYPE The degrees in this sensor | 1.3.6.1.4.1.3854.1.2.2.1.16.1.3 | INTEGER | read-only | mandatory |
| hhmsSensorArrayTempStatus OBJECT-TYPE The current status of this Sensor | 1.3.6.1.4.1.3854.1.2.2.1.16.1.4 | INTEGER {noStatus(1), normal(2), highWarning(3), highCritical(4), lowWarning(5), lowCritical(6), sensorError(7)} | read-only | mandatory |
| hhmsSensorArrayTempOnline OBJECT-TYPE If this Sensor is currently online | 1.3.6.1.4.1.3854.1.2.2.1.16.1.5 | INTEGER {online(1), offline(2)} | read-only | mandatory |
| hhmsSensorArrayTempGoOnline OBJECT-TYPE To put online enter a 1, to take offline enter a 2 | 1.3.6.1.4.1.3854.1.2.2.1.16.1.6 | INTEGER {goOnline(1), goOffline(2)} | read-write | mandatory |
| hhmsSensorArrayTempHighWarning OBJECT-TYPE How hot this sensor gets before it sends a warning | 1.3.6.1.4.1.3854.1.2.2.1.16.1.7 | INTEGER | read-write | mandatory |
| hhmsSensorArrayTempHighCritical OBJECT-TYPE How hot this sensor gets before it sends a critical event | 1.3.6.1.4.1.3854.1.2.2.1.16.1.8 | INTEGER | read-write | mandatory |
| hhmsSensorArrayTempLowWarning OBJECT-TYPE How cold this sensor gets before it sends a warning | 1.3.6.1.4.1.3854.1.2.2.1.16.1.9 | INTEGER | read-write | mandatory |
| hhmsSensorArrayTempLowCritical OBJECT-TYPE How cold this sensor gets before it sends a critical event | 1.3.6.1.4.1.3854.1.2.2.1.16.1.10 | INTEGER | read-write | mandatory |
| hhmsSensorArrayTempRearm OBJECT-TYPE The number of degrees to rearm the status. For example if status goes from normal to warning, the temp must go down hhmsTempRearm degrees below warning before the status goes to normal | 1.3.6.1.4.1.3854.1.2.2.1.16.1.11 | INTEGER | read-write | mandatory |
| hhmsSensorArrayTempDegreeType OBJECT-TYPE The degrees are in fahrenheit(0) or in celsius(1) | 1.3.6.1.4.1.3854.1.2.2.1.16.1.12 | INTEGER {fahr(0), celsius(1)} | read-write | mandatory |
| hhmsSensorArrayTempSensorType OBJECT-TYPE The type of temperture sensor | 1.3.6.1.4.1.3854.1.2.2.1.16.1.13 | INTEGER {type1(0), type2(1)} | read-write | mandatory |
| hhmsSensorArrayTempTestStatus OBJECT-TYPE Set the status for test purposes | 1.3.6.1.4.1.3854.1.2.2.1.16.1.14 | INTEGER {testNoStatus(1), testNormal(2), testHighWarning(3), testHighCritical(4), testLowWarning(5), testLowCritical(6), sensorError(7)} | read-write | mandatory |
| hhmsSensorArrayTempTestDegree OBJECT-TYPE Enter the degrees in this sensor for test purposes | 1.3.6.1.4.1.3854.1.2.2.1.16.1.15 | INTEGER | read-write | mandatory |
| hhmsSensorArrayTempIndex OBJECT-TYPE The index into the temperature sensor table | 1.3.6.1.4.1.3854.1.2.2.1.16.1.16 | INTEGER (0..3) | read-only | mandatory |
| hhmsSensorArrayHumidityTable OBJECT-TYPE This table contains the data for every Humidity Sensor in the SensorArray. Each row in the table contains data for a different Humidity Sensor. | 1.3.6.1.4.1.3854.1.2.2.1.17 | not-accessible | mandatory | |
| hhmsSensorArrayHumidityEntry OBJECT-TYPE This is an entry in the hhmsSensorArrayHumidityEntry Table | 1.3.6.1.4.1.3854.1.2.2.1.17.1 | not-accessible | mandatory | |
| hhmsSensorArrayHumidityDescription OBJECT-TYPE A Description of this sensor | 1.3.6.1.4.1.3854.1.2.2.1.17.1.1 | DisplayString | read-write | mandatory |
| hhmsSensorArrayHumidityLocation OBJECT-TYPE The physical location of this sensor | 1.3.6.1.4.1.3854.1.2.2.1.17.1.2 | DisplayString | read-write | mandatory |
| hhmsSensorArrayHumidityPercent OBJECT-TYPE The relative humidity percentage measured by this sensor | 1.3.6.1.4.1.3854.1.2.2.1.17.1.3 | INTEGER | read-only | mandatory |
| hhmsSensorArrayHumidityStatus OBJECT-TYPE The current status of this Sensor | 1.3.6.1.4.1.3854.1.2.2.1.17.1.4 | INTEGER {noStatus(1), normal(2), highWarning(3), highCritical(4), lowWarning(5), lowCritical(6), sensorError(7)} | read-only | mandatory |
| hhmsSensorArrayHumidityOnline OBJECT-TYPE If this Sensor is currently online | 1.3.6.1.4.1.3854.1.2.2.1.17.1.5 | INTEGER {online(1), offline(2)} | read-only | mandatory |
| hhmsSensorArrayHumidityGoOnline OBJECT-TYPE To put online enter a 1, to take offline enter a 2 | 1.3.6.1.4.1.3854.1.2.2.1.17.1.6 | INTEGER {goOnline(1), goOffline(2)} | read-write | mandatory |
| hhmsSensorArrayHumidityHighWarning OBJECT-TYPE How high the relative humidity this sensor measures before it sends a warning | 1.3.6.1.4.1.3854.1.2.2.1.17.1.7 | INTEGER | read-write | mandatory |
| hhmsSensorArrayHumidityHighCritical OBJECT-TYPE How high the relative humidity this sensor measures before it becomes critical | 1.3.6.1.4.1.3854.1.2.2.1.17.1.8 | INTEGER | read-write | mandatory |
| hhmsSensorArrayHumidityLowWarning OBJECT-TYPE How low the relative humidity this sensor measures before it sends a warning | 1.3.6.1.4.1.3854.1.2.2.1.17.1.9 | INTEGER | read-write | mandatory |
| hhmsSensorArrayHumidityLowCritical OBJECT-TYPE How low the relative humidity this sensor measures before it becomes critical | 1.3.6.1.4.1.3854.1.2.2.1.17.1.10 | INTEGER | read-write | mandatory |
| hhmsSensorArrayHumidityRearm OBJECT-TYPE The percent relative humidity to rearm the status. For example if status goes from normal to warning, the humidity must go down hhmsHumidityRearm below warning before the status goes to normal | 1.3.6.1.4.1.3854.1.2.2.1.17.1.11 | INTEGER | read-write | mandatory |
| hhmsSensorArrayHumidityTestStatus OBJECT-TYPE Set the status for test purposes | 1.3.6.1.4.1.3854.1.2.2.1.17.1.12 | INTEGER {testNoStatus(1), testNormal(2), testHighWarning(3), testHighCritical(4), testLowWarning(5), testLowCritical(6), sensorError(7)} | read-write | mandatory |
| hhmsSensorArrayHumidityTestPercent OBJECT-TYPE Enter the percent of relative humidity in this sensor for test purposes | 1.3.6.1.4.1.3854.1.2.2.1.17.1.13 | INTEGER | read-write | mandatory |
| hhmsSensorArrayHumidityIndex OBJECT-TYPE The index into the Humidity sensor table | 1.3.6.1.4.1.3854.1.2.2.1.17.1.14 | INTEGER (0..2) | read-only | mandatory |
| hhmsSensorArraySwitchTable OBJECT-TYPE This table contains the data for every Switch Sensor in the SensorArray. Each row in the table contains data for a different Switch Sensor. | 1.3.6.1.4.1.3854.1.2.2.1.18 | not-accessible | mandatory | |
| hhmsSensorArraySwitchEntry OBJECT-TYPE This is an entry in the hhmsSensorArraySwitchEntry Table | 1.3.6.1.4.1.3854.1.2.2.1.18.1 | not-accessible | mandatory | |
| hhmsSensorArraySwitchDescription OBJECT-TYPE A Description of this sensor Switch | 1.3.6.1.4.1.3854.1.2.2.1.18.1.1 | DisplayString | read-write | mandatory |
| hhmsSensorArraySwitchLocation OBJECT-TYPE The physical location of this sensor Switch | 1.3.6.1.4.1.3854.1.2.2.1.18.1.2 | DisplayString | read-write | mandatory |
| hhmsSensorArraySwitchStatus OBJECT-TYPE The current status of this Sensor, only input switches have a status | 1.3.6.1.4.1.3854.1.2.2.1.18.1.3 | INTEGER {noStatus(1), normal(2), critical(4), sensorError(7)} | read-only | mandatory |
| hhmsSensorArraySwitchOnline OBJECT-TYPE If this Sensor is currently online | 1.3.6.1.4.1.3854.1.2.2.1.18.1.4 | INTEGER {online(1), offline(2)} | read-only | mandatory |
| hhmsSensorArraySwitchGoOnline OBJECT-TYPE To put online enter a 1, to take offline enter a 2 | 1.3.6.1.4.1.3854.1.2.2.1.18.1.5 | INTEGER {goOnline(1), goOffline(2)} | read-write | mandatory |
| hhmsSensorArraySwitchDirection OBJECT-TYPE To set a switch to input enter 0. To set a switch to output enter 1 | 1.3.6.1.4.1.3854.1.2.2.1.18.1.6 | INTEGER {input(0), output(1)} | read-write | mandatory |
| hhmsSensorArraySwitchNormalState OBJECT-TYPE The normal state of an input switch. If an input switch is in this state it is normal, else it is critical. An open switch senses +5 volts. A closed switch senses 0 volts. | 1.3.6.1.4.1.3854.1.2.2.1.18.1.7 | INTEGER {closed(0), open(1)} | read-write | mandatory |
| hhmsSensorArraySwitchOutputLevel OBJECT-TYPE An output swith can be set to this level | 1.3.6.1.4.1.3854.1.2.2.1.18.1.8 | INTEGER {low(0), high(1)} | read-write | mandatory |
| hhmsSensorArraySwitchTestState OBJECT-TYPE Enter the status of this Sensor for test purposes | 1.3.6.1.4.1.3854.1.2.2.1.18.1.9 | INTEGER {noStatus(1), normal(2), critical(4), sensorError(7)} | read-only | mandatory |
| hhmsSensorArraySwitchIndex OBJECT-TYPE The index into the Switch sensor table | 1.3.6.1.4.1.3854.1.2.2.1.18.1.10 | INTEGER (0..24) | read-only | mandatory |
| hhmsSensorArraySerialTable OBJECT-TYPE This table contains the data for every Serial Port in the SensorArray. Each row in the table contains data for a different Serial Port. | 1.3.6.1.4.1.3854.1.2.2.1.19 | not-accessible | mandatory | |
| hhmsSensorArraySerialEntry OBJECT-TYPE This is an entry in the hhmsSensorArraySerialEntry Table | 1.3.6.1.4.1.3854.1.2.2.1.19.1 | not-accessible | mandatory | |
| hhmsSensorArraySerialDescription OBJECT-TYPE A Description of this Serial Port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.1 | DisplayString | read-write | mandatory |
| hhmsSensorArraySerialLocation OBJECT-TYPE The physical location of this Serial Port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.2 | DisplayString | read-write | mandatory |
| hhmsSensorArraySerialStatus OBJECT-TYPE The current status of this Serial Port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.3 | INTEGER {noStatus(1), normal(2), critical(4), sensorError(7)} | read-only | mandatory |
| hhmsSensorArraySerialOnline OBJECT-TYPE If this Serial Port is currently online | 1.3.6.1.4.1.3854.1.2.2.1.19.1.4 | INTEGER {online(1), offline(2)} | read-only | mandatory |
| hhmsSensorArraySerialGoOnline OBJECT-TYPE To put online enter a 1, to take offline enter a 2 | 1.3.6.1.4.1.3854.1.2.2.1.19.1.5 | INTEGER {goOnline(1), goOffline(2)} | read-write | mandatory |
| hhmsSensorArraySerialData OBJECT-TYPE Write sends data, read gets data from this Serial Port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.6 | DisplayString | read-write | mandatory |
| hhmsSensorArraySerialBaud OBJECT-TYPE Choose the baud rate for this serial port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.7 | INTEGER {baud115200(2), baud57600(4), baud38400(7), baud28800(10), baud19200(15), baud9600(32), baud4800(64), baud2400(129), baud1200(255)} | read-write | mandatory |
| hhmsSensorArraySerialDataBits OBJECT-TYPE Parity bit for this serial port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.8 | INTEGER {eight(8)} | read-write | mandatory |
| hhmsSensorArraySerialParity OBJECT-TYPE Parity bit for this serial port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.9 | INTEGER {none(1)} | read-write | mandatory |
| hhmsSensorArraySerialStop OBJECT-TYPE Stop bits for this serial port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.10 | INTEGER {one(1)} | read-write | mandatory |
| hhmsSensorArraySerialCTS OBJECT-TYPE Turn CTS on or off for this serial port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.11 | INTEGER {on(1), off(2)} | read-write | mandatory |
| hhmsSensorArraySerialRTS OBJECT-TYPE Turn RTS on or off for this serial port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.12 | INTEGER {on(1), off(2)} | read-write | mandatory |
| hhmsSensorArraySerialConfig OBJECT-TYPE A Description of this Serial Port | 1.3.6.1.4.1.3854.1.2.2.1.19.1.13 | DisplayString | read-write | mandatory |
| hhmsSensorArraySerialIndex OBJECT-TYPE The index into the Serial table | 1.3.6.1.4.1.3854.1.2.2.1.19.1.14 | INTEGER (0..1) | read-only | mandatory |
| hhmsSensorArrayDebug OBJECT-TYPE Turn on or off debug messages | 1.3.6.1.4.1.3854.1.2.2.1.20 | INTEGER {off(0), on(1)} | read-write | mandatory |
| hhmsSensorArrayDebugIP OBJECT-TYPE The IP address to send debug messages to | 1.3.6.1.4.1.3854.1.2.2.1.21 | DisplayString | read-write | mandatory |
| hhmsSensorArrayTrapResend OBJECT-TYPE If traps for Warning or Error should be resent. Traps for Normal status are sent once | 1.3.6.1.4.1.3854.1.2.2.1.22 | INTEGER {off(0), on(1)} | read-write | mandatory |
| hhmsSensorArrayTrapResendInterval OBJECT-TYPE How often to resend mail or Traps. Enter the number of seconds from 15 to 65535. Mail for WARNING and ERROR are resent at this interval. Traps for Normal status are sent once | 1.3.6.1.4.1.3854.1.2.2.1.23 | INTEGER | read-write | mandatory |
| hhmsSensorArraySendTraps OBJECT-TYPE Turn on or off the sending of traps | 1.3.6.1.4.1.3854.1.2.2.1.24 | INTEGER {on(1), off(2)} | read-write | mandatory |
| hhmsSensorArrayTrapDestination OBJECT-TYPE The IP address of the trap destination | 1.3.6.1.4.1.3854.1.2.2.1.25 | IpAddress | read-write | mandatory |
| hhmsSensorArrayTrapCommunity OBJECT-TYPE The community string of the trap destination | 1.3.6.1.4.1.3854.1.2.2.1.26 | DisplayString | read-write | mandatory |
| hhmsSensorArrayTrapDefaultGateway OBJECT-TYPE If the trap destination is on another network, enter the IP address of the router | 1.3.6.1.4.1.3854.1.2.2.1.27 | IpAddress | read-write | mandatory |
| hhmsSensorArrayTrapUseDefaultGateway OBJECT-TYPE If the trap destination uses the default gateway | 1.3.6.1.4.1.3854.1.2.2.1.28 | INTEGER {on(1), off(2)} | read-write | mandatory |
| hhmsSensorArrayTrapDestinationMac OBJECT-TYPE If the trap destination MAC address | 1.3.6.1.4.1.3854.1.2.2.1.29 | DisplayString | read-write | mandatory |
| hhmsSensorArraySendMail OBJECT-TYPE Turn on or off the sending of Mail | 1.3.6.1.4.1.3854.1.2.2.1.30 | INTEGER {on(1), off(2)} | read-write | mandatory |
| hhmsSensorArrayMailRecpt OBJECT-TYPE The email address of the Recipient | 1.3.6.1.4.1.3854.1.2.2.1.31 | DisplayString | read-write | mandatory |
| hhmsSensorArrayMailFrom OBJECT-TYPE The email address of the Sender | 1.3.6.1.4.1.3854.1.2.2.1.32 | DisplayString | read-write | mandatory |
| hhmsSensorArrayMailSmpt OBJECT-TYPE The IP Address of the SMPT server. Note: This must be in dotted decimal form | 1.3.6.1.4.1.3854.1.2.2.1.33 | IpAddress | read-write | mandatory |
| hhmsSensorArrayMailGateway OBJECT-TYPE If the smpt server is on another network, enter the IP address of the router | 1.3.6.1.4.1.3854.1.2.2.1.34 | IpAddress | read-write | mandatory |
| hhmsSensorArrayMailUseGateway OBJECT-TYPE If the mail uses the default gateway | 1.3.6.1.4.1.3854.1.2.2.1.35 | INTEGER {on(1), off(2)} | read-write | mandatory |
| hhmsSensorArrayMailResendInterval OBJECT-TYPE How often to resend mail or Traps. Enter the number of seconds from 10 to 65535. Mail for WARNING and ERROR are resent at this interval. Mail for Normal status are sent once | 1.3.6.1.4.1.3854.1.2.2.1.36 | INTEGER | read-write | mandatory |
| hhmsSensorArrayMailMaxResend OBJECT-TYPE The maximum number of times to resend mail. If set to 0 only send once. The maximum value is 25 | 1.3.6.1.4.1.3854.1.2.2.1.37 | INTEGER | read-write | mandatory |
| hhmsSensorArrayMailDestinationMac OBJECT-TYPE If the mail destination MAC address, either the smpt server or the gateway | 1.3.6.1.4.1.3854.1.2.2.1.38 | DisplayString | read-write | mandatory |
| hhmsSensorArrayMailLastStatus OBJECT-TYPE The status of the most recent attempt to send an email | 1.3.6.1.4.1.3854.1.2.2.1.39 | DisplayString | read-only | mandatory |
| hhmsSensorArrayPowerControlTable OBJECT-TYPE This table contains the Power Control features in the sensorArray. | 1.3.6.1.4.1.3854.1.2.2.1.40 | not-accessible | mandatory | |
| hhmsSensorArrayPowerControlEntry OBJECT-TYPE This is an entry in the hhmsSensorArrayPowerControlEntry Table | 1.3.6.1.4.1.3854.1.2.2.1.40.1 | not-accessible | mandatory | |
| hhmsSensorArrayPowerModuleDescription OBJECT-TYPE A Description of this Power Module | 1.3.6.1.4.1.3854.1.2.2.1.40.1.1 | DisplayString | read-write | mandatory |
| hhmsSensorArrayPowerModuleStatus OBJECT-TYPE The current status of this Sensor | 1.3.6.1.4.1.3854.1.2.2.1.40.1.2 | INTEGER {noStatus(1), normal(2), sensorError(7)} | read-only | mandatory |
| hhmsSensorArrayPowerModuleOnline OBJECT-TYPE If this Sensor is currently online | 1.3.6.1.4.1.3854.1.2.2.1.40.1.3 | INTEGER {online(1), offline(2)} | read-only | mandatory |
| hhmsSensorArrayPowerModuleGoOnline OBJECT-TYPE To put online enter a 1, to take offline enter a 2 | 1.3.6.1.4.1.3854.1.2.2.1.40.1.4 | INTEGER {goOnline(1), goOffline(2)} | read-write | mandatory |
| hhmsSensorArrayPowerOutletDescription OBJECT-TYPE A Description of this Power Port | 1.3.6.1.4.1.3854.1.2.2.1.40.1.5 | DisplayString | read-write | mandatory |
| hhmsSensorArrayPowerOutletStatus OBJECT-TYPE The current status of this Sensor | 1.3.6.1.4.1.3854.1.2.2.1.40.1.6 | INTEGER {noStatus(1), on(2), off(3), sensorError(7)} | read-only | mandatory |
| hhmsSensorArrayPowerOutletSet OBJECT-TYPE The current status of this Sensor | 1.3.6.1.4.1.3854.1.2.2.1.40.1.7 | INTEGER {noStatus(1), on(2), off(3), reboot(4), sensorError(7)} | read-write | mandatory |
| hhmsSensorArrayPowerControlIndex OBJECT-TYPE The index into the Power Control table | 1.3.6.1.4.1.3854.1.2.2.1.40.1.8 | INTEGER (0..1) | read-only | mandatory |
| hhmsSensorArrayPowerMonitorTable OBJECT-TYPE This table contains the Power Monitor features in the sensorArray. | 1.3.6.1.4.1.3854.1.2.2.1.41 | not-accessible | mandatory | |
| hhmsSensorArrayPowerMonitorEntry OBJECT-TYPE This is an entry in the hhmsSensorArrayPowerMonitorEntry Table | 1.3.6.1.4.1.3854.1.2.2.1.41.1 | not-accessible | mandatory | |
| hhmsSensorArrayPowerMonitorDescription OBJECT-TYPE A Description of this Power Monitor | 1.3.6.1.4.1.3854.1.2.2.1.41.1.1 | DisplayString | read-write | mandatory |
| hhmsSensorArrayPowerMonitorCurrent OBJECT-TYPE The current in this sensor | 1.3.6.1.4.1.3854.1.2.2.1.41.1.2 | INTEGER | read-write | mandatory |
| hhmsSensorArrayPowerMonitorVoltage OBJECT-TYPE The voltage in this sensor | 1.3.6.1.4.1.3854.1.2.2.1.41.1.3 | INTEGER | read-write | mandatory |
| hhmsSensorArrayPowerMonitorPower OBJECT-TYPE The total energy measured so far by this sensor | 1.3.6.1.4.1.3854.1.2.2.1.41.1.4 | DisplayString | read-write | mandatory |
| hhmsSensorArrayPowerMonitorStatus OBJECT-TYPE The current status of this Sensor | 1.3.6.1.4.1.3854.1.2.2.1.41.1.5 | INTEGER {noStatus(1), normal(2), highWarning(3), highCritical(4), lowWarning(5), lowCritical(6), sensorError(7)} | read-only | mandatory |
| hhmsSensorArrayPowerMonitorOnline OBJECT-TYPE If this Sensor is currently online | 1.3.6.1.4.1.3854.1.2.2.1.41.1.6 | INTEGER {online(1), offline(2)} | read-only | mandatory |
| hhmsSensorArrayPowerMonitorGoOnline OBJECT-TYPE To put online enter a 1, to take offline enter a 2 | 1.3.6.1.4.1.3854.1.2.2.1.41.1.7 | INTEGER {goOnline(1), goOffline(2)} | read-write | mandatory |
| hhmsSensorArrayPowerMonitorHighWarning OBJECT-TYPE How many watts of power this sensor detects before the sensor status is set to warning | 1.3.6.1.4.1.3854.1.2.2.1.41.1.8 | INTEGER | read-write | mandatory |
| hhmsSensorArrayPowerMonitorHighCritical OBJECT-TYPE How many watts of power this sensor detects before the sensor status is set to critical | 1.3.6.1.4.1.3854.1.2.2.1.41.1.9 | INTEGER | read-write | mandatory |
| hhmsSensorArrayPowerMonitorLowWarning OBJECT-TYPE How many watts of power this sensor detects before the sensor status is set to warning | 1.3.6.1.4.1.3854.1.2.2.1.41.1.10 | INTEGER | read-write | mandatory |
| hhmsSensorArrayPowerMonitorLowCritical OBJECT-TYPE How many watts of power this sensor detects before the sensor status is set to critical | 1.3.6.1.4.1.3854.1.2.2.1.41.1.11 | INTEGER | read-write | mandatory |
| hhmsSensorArrayPowerMonitorRearm OBJECT-TYPE How many watts of power this sensor detects to rearm the status. For example if status goes from normal to warning, the temp must go down hhmsTempRearm degrees below warning before the status goes to normal | 1.3.6.1.4.1.3854.1.2.2.1.41.1.12 | INTEGER | read-write | mandatory |
| hhmsSensorArrayPowerMonitorIndex OBJECT-TYPE The index into the Power table | 1.3.6.1.4.1.3854.1.2.2.1.41.1.13 | INTEGER (0..4) | read-only | mandatory |
| hhmsSensorArrayHighDriveTable OBJECT-TYPE This table contains the High Current Drivers in the sensorArray. | 1.3.6.1.4.1.3854.1.2.2.1.42 | not-accessible | mandatory | |
| hhmsSensorArrayHighDriveEntry OBJECT-TYPE This is an entry in the hhmsSensorArrayHighDriveEntry Table | 1.3.6.1.4.1.3854.1.2.2.1.42.1 | not-accessible | mandatory | |
| hhmsSensorArrayHighDriveDescription OBJECT-TYPE A Description of this Power Monitor | 1.3.6.1.4.1.3854.1.2.2.1.42.1.1 | DisplayString | read-write | mandatory |
| hhmsSensorArrayHighDriveOutputLevel OBJECT-TYPE The Driver can be on or off. If closed the Open Collector will sink current. If open the Open Collector will tri state | 1.3.6.1.4.1.3854.1.2.2.1.42.1.2 | INTEGER {closed(0), open(1)} | read-write | mandatory |
| hhmsSensorArrayHighDriveIndex OBJECT-TYPE The index into the HighDrive table | 1.3.6.1.4.1.3854.1.2.2.1.42.1.3 | INTEGER (0..3) | read-only | mandatory |
| hhmsSensorArrayCameraTable OBJECT-TYPE This table contains the Camera features in the sensorArray. | 1.3.6.1.4.1.3854.1.2.2.1.43 | not-accessible | mandatory | |
| hhmsSensorArrayCameraEntry OBJECT-TYPE This is an entry in the hhmsSensorArrayCameraEntry Table | 1.3.6.1.4.1.3854.1.2.2.1.43.1 | not-accessible | mandatory | |
| hhmsSensorArrayCameraDescription OBJECT-TYPE A Description of this Camera | 1.3.6.1.4.1.3854.1.2.2.1.43.1.1 | DisplayString | read-write | mandatory |
| hhmsSensorArrayCameraOnline OBJECT-TYPE If this Sensor is currently online | 1.3.6.1.4.1.3854.1.2.2.1.43.1.2 | INTEGER {online(1), offline(2)} | read-only | mandatory |
| hhmsSensorArrayCameraGoOnline OBJECT-TYPE To put online enter a 1, to take offline enter a 2 | 1.3.6.1.4.1.3854.1.2.2.1.43.1.3 | INTEGER {goOnline(1), goOffline(2)} | read-write | mandatory |
| hhmsSensorArrayCameraUrlMain OBJECT-TYPE The URL of the Camera, for example http://10.1.1.7 | 1.3.6.1.4.1.3854.1.2.2.1.43.1.4 | DisplayString | read-write | mandatory |
| hhmsSensorArrayCameraUrlExtension OBJECT-TYPE The cgi extension for the Picture from this Camera for example /webcam/server.jpg | 1.3.6.1.4.1.3854.1.2.2.1.43.1.5 | DisplayString | read-write | mandatory |
| hhmsSensorArrayCameraRefreshRate OBJECT-TYPE How often to refresh the image on the browser in seconds from 5 to 254 | 1.3.6.1.4.1.3854.1.2.2.1.43.1.6 | INTEGER | read-write | mandatory |
| hhmsSensorArrayCameraIndex OBJECT-TYPE The index into the Camera table | 1.3.6.1.4.1.3854.1.2.2.1.43.1.7 | INTEGER (0..3) | read-only | mandatory |
| hhmsSensorArrayTrapMailPollInterval OBJECT-TYPE How often the sensor thresholds are tested before sending traps or mail. This can vary from 3 to 15 seconds | 1.3.6.1.4.1.3854.1.2.2.1.50 | INTEGER | read-write | mandatory |
| hhmsSensorArraySendTestMail OBJECT-TYPE Send out an email test message | 1.3.6.1.4.1.3854.1.2.2.1.51 | INTEGER | read-write | mandatory |
| hhmsSensorArrayLastSystemError OBJECT-TYPE A text string containing the description of the last system error | 1.3.6.1.4.1.3854.1.2.2.1.52 | DisplayString | read-only | mandatory |
| hhmsSensorArrayDataCollectionPeriod OBJECT-TYPE The number of minutes between collections of the data logger. This can vary from 1 to 60 minutes | 1.3.6.1.4.1.3854.1.2.2.1.53 | INTEGER | read-write | mandatory |
| hhmsSensorArrayMailTimeout OBJECT-TYPE The number of seconds to wait for a timeout while sending email This can vary from 10 to 60 seconds | 1.3.6.1.4.1.3854.1.2.2.1.54 | INTEGER | read-write | mandatory |
| hhmsAgentConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3854.1.5 | |||
| hhmsAgentVersion OBJECT-TYPE The hhms agent release version number | 1.3.6.1.4.1.3854.1.5.1 | DisplayString | read-only | mandatory |
| hhmsCompressedSummaryTable OBJECT-TYPE This table contains a way to get summary info to the browser using minimum communication. One get contains a PDU info from multiple sensorArrays | 1.3.6.1.4.1.3854.1.5.7 | not-accessible | mandatory | |
| hhmsCompressedSummaryEntry OBJECT-TYPE This is an entry in the hhmsCompressedSummary Table | 1.3.6.1.4.1.3854.1.5.7.1 | not-accessible | mandatory | |
| hhmsCompressedSummaryGet OBJECT-TYPE Get multiple compressed summary PDU | 1.3.6.1.4.1.3854.1.5.7.1.1 | DisplayString | read-only | mandatory |
| hhmsCompressedSummaryIndex OBJECT-TYPE The index into the compressed summary table | 1.3.6.1.4.1.3854.1.5.7.1.2 | INTEGER (0..1) | read-only | mandatory |
| hhmsAgentTraps OBJECT-IDENTITY | 1.3.6.1.4.1.3854.1.7 | |||
| hhmsSensorStatus OBJECT-TYPE The current integer status of the sensor causing this trap to be sent | 1.3.6.1.4.1.3854.1.7.1 | INTEGER {noStatus(1), normal(2), highWarning(3), highCritical(4), lowWarning(5), lowCritical(6), sensorError(7)} | read-only | mandatory |
| hhmsSensorValue OBJECT-TYPE The current integer value of the sensor causing this trap to be sent | 1.3.6.1.4.1.3854.1.7.2 | INTEGER | read-only | mandatory |
| hhmsSensorLevelExceeded OBJECT-TYPE The integer level that was exceeded causing this trap to be sent | 1.3.6.1.4.1.3854.1.7.3 | INTEGER | read-only | mandatory |
| hhmsSensorIndex OBJECT-TYPE The integer index of the sensor causing this trap to be sent | 1.3.6.1.4.1.3854.1.7.4 | INTEGER | read-only | mandatory |
| hhmsSensorName OBJECT-TYPE The name of the sensor causing this trap to be sent | 1.3.6.1.4.1.3854.1.7.5 | DisplayString | read-only | mandatory |
| hhmsSensorDescription OBJECT-TYPE The description of the sensor causing this trap to be sent | 1.3.6.1.4.1.3854.1.7.6 | DisplayString | read-only | mandatory |
Notifications
| Name | OID | Status |
|---|---|---|
| hhmsUnknownStatus NOTIFICATION-TYPE hhmsagent status went to Unknown | 1.3.6.1.4.1.3854.1.0.0 | |
| hhmsNormalStatus NOTIFICATION-TYPE hhmsagent status is Normal | 1.3.6.1.4.1.3854.1.0.1 | |
| hhmsWarningStatus NOTIFICATION-TYPE hhmsagent status went to Warning | 1.3.6.1.4.1.3854.1.0.2 | |
| hhmsCriticalStatus NOTIFICATION-TYPE hhmsagent status went to Critical | 1.3.6.1.4.1.3854.1.0.3 | |
| hhmsDownStatus NOTIFICATION-TYPE hhmsagent status went to Disabled | 1.3.6.1.4.1.3854.1.0.4 | |
| hhmsTemperatureStatus NOTIFICATION-TYPE Temperature sensor trap | 1.3.6.1.4.1.3854.1.0.10 | |
| hhmsHumidityStatus NOTIFICATION-TYPE Humidity sensor trap | 1.3.6.1.4.1.3854.1.0.20 | |
| hhmsSwitchStatus NOTIFICATION-TYPE Switch sensor trap | 1.3.6.1.4.1.3854.1.0.30 | |
| hhmsPowerMonitorStatus NOTIFICATION-TYPE Power Monitor sensor trap | 1.3.6.1.4.1.3854.1.0.40 |