ELTEK-DISTRIBUTED-MIB
- Registered at
- 1.3.6.1.4.1.12148
- Last updated
- 2015-01-03 08:25
- Organization
- ELTEK power System MIB Working Group
- Revisions
- 2016-02-18 14:16, 2015-01-03 08:25, 2011-06-05 14:44, 2011-03-22 14:41, 2010-10-29 08:29, 2009-03-12 15:15, 2008-01-30 11:49, 2007-06-22 11:27, 2005-09-07 12:38, 2005-06-28 11:30
- Namespace
- eltek
- Source file
ELTEK-DISTRIBUTED-MIB- Digest
sha256:89c4fcc9833152d81d067c6a92e060fb0bd5d35379f574cafa8777e141fe82f2
Description
Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5 and compack V1.0, V1.01, V1.02, V1.03) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack2 sw V1.1, V1.2, V1.3) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6, V4.7 and compack V1.04, V1.05) ELTEK Distributed V8 branch will be 9 (SmartPack w/WebPower sw V4.9, V4.10, ComPack V1.04, V1.05, Smartpack2 V1.1, V1.2) ELTEK Distributed V9 branch will be 9 (SmartPack w/WebPower sw V4.11) ELTEK eNexus MIB branch will be 10 (SmartPack2 V2.x, SmartPack S V2.x and Compack V2.x) ELTEK Brasil office will have branch 11 ELTEK BMS-EM MIB will have branch 12 ELTEK TELMEX MIB will have branch 13
Contact
Eltek R&D. Postal: Eltek AS P.O. Box 3043 N-3003 Drammen Norway Tel: +47-32 20 32 00 Fax: +47-32 20 31 20 web: www.eltek.com
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Counter32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
ELTEK-DISTRIBUTED-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Under this module's arcs
Where the registration tree carries on below this module.
| Arc | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.12148.10 | eNexus | SP2-MIB |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| eltekDistributedPlantV9 OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9 | |||
| controlSystem OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.1 | |||
| systemTime OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.1.1 | |||
| systemTimeTime OBJECT-TYPE The system date and time. Used for event timestamps and logging | 1.3.6.1.4.1.12148.9.1.1.1 | DisplayString (SIZE(0..255)) | read-only | current |
| systemInfoRefresh OBJECT-TYPE This is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make sure the tables are updated. | 1.3.6.1.4.1.12148.9.1.2 | INTEGER {pushbutton(0), refreshdata(1)} | read-write | current |
| systemTrapRepeatRate OBJECT-TYPE This object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event. | 1.3.6.1.4.1.12148.9.1.3 | Integer32 (0..1440) | read-write | current |
| systemSendOffTrap OBJECT-TYPE A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted. | 1.3.6.1.4.1.12148.9.1.4 | INTEGER {off(0), on(1)} | read-write | current |
| systemNumOfControlUnits OBJECT-TYPE The number of Control units in a distributed system. | 1.3.6.1.4.1.12148.9.1.5 | Integer32 (0..8) | read-only | current |
| systemControlUnitIndex OBJECT-TYPE Index used for navigating in the table for configurable inputs. | 1.3.6.1.4.1.12148.9.1.6 | Integer32 (0..7) | accessible-for-notify | current |
| systemControlUnitTable OBJECT-TYPE This table contains the status of the programmable inputs. There is one row for each Control unit. | 1.3.6.1.4.1.12148.9.1.7 | not-accessible | current | |
| systemControlUnitEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.9.1.7.1 | not-accessible | current | |
| inputControlUnitID OBJECT-TYPE The ID of which Control unit to be read. | 1.3.6.1.4.1.12148.9.1.7.1.1 | Integer32 (1..8) | read-only | current |
| inputUserConfigurable1 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.2 | INTEGER {normal(0), alarm(1)} | read-only | current |
| inputUserConfigurable2 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.3 | INTEGER {normal(0), alarm(1)} | read-only | current |
| inputUserConfigurable3 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.4 | INTEGER {normal(0), alarm(1)} | read-only | current |
| inputUserConfigurable4 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.5 | INTEGER {normal(0), alarm(1)} | read-only | current |
| inputUserConfigurable5 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.6 | INTEGER {normal(0), alarm(1)} | read-only | current |
| inputUserConfigurable6 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.7 | INTEGER {normal(0), alarm(1)} | read-only | current |
| inputUserConfigurable7 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.8 | INTEGER {normal(0), alarm(1)} | read-only | current |
| inputUserConfigurable8 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.9 | INTEGER {normal(0), alarm(1)} | read-only | current |
| inputUserConfigurable9 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.10 | INTEGER {normal(0), alarm(1)} | read-only | current |
| inputUserConfigurable10 OBJECT-TYPE Programmable input status. The description of the input is found in the systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.7.1.11 | INTEGER {normal(0), alarm(1)} | read-only | current |
| systemLinkStatus OBJECT-TYPE A flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Not applicable for ComPack control unit | 1.3.6.1.4.1.12148.9.1.8 | INTEGER {linkdown(0), linkup(1)} | read-only | current |
| systemInitiateEEPROM OBJECT-TYPE Pushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly. | 1.3.6.1.4.1.12148.9.1.9 | INTEGER {pushbutton(0), start(1)} | read-write | deprecated |
| systemLastDigInput OBJECT-TYPE The last Prog.Input that generated a trap. Used by Traps only. | 1.3.6.1.4.1.12148.9.1.10 | Integer32 (1..10) | accessible-for-notify | current |
| systemTrapCounter OBJECT-TYPE The number of times a trap has been repeated.. Only acessible for Traps. | 1.3.6.1.4.1.12148.9.1.11 | Counter32 | accessible-for-notify | current |
| systemHeartBeatTrapRepeatRate OBJECT-TYPE The repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap. | 1.3.6.1.4.1.12148.9.1.12 | Integer32 (0..1440) | read-write | current |
| systemResetManualAlarms OBJECT-TYPE A pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this. | 1.3.6.1.4.1.12148.9.1.13 | INTEGER {pushbutton(0), apply(1)} | read-write | current |
| systemControlUnitInputIndex OBJECT-TYPE Index used for navigating in the table for configurable inputs. | 1.3.6.1.4.1.12148.9.1.14 | Integer32 (0..7) | accessible-for-notify | current |
| systemControlUnitInputTable OBJECT-TYPE This table contains the description of the programmable inputs. There is one row for each Control unit. Programmable input alarms will have description attached to the traps that explains the alarm. Default description is: ProgInput <Control unit ID>.x | 1.3.6.1.4.1.12148.9.1.15 | not-accessible | current | |
| systemControlUnitInputEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.9.1.15.1 | not-accessible | current | |
| inputUnitID OBJECT-TYPE The ID of which Control unit to be read. | 1.3.6.1.4.1.12148.9.1.15.1.1 | Integer32 | read-only | current |
| inputUserConfigurableText1 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.1. | 1.3.6.1.4.1.12148.9.1.15.1.2 | DisplayString | read-only | current |
| inputUserConfigurableText2 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.2. | 1.3.6.1.4.1.12148.9.1.15.1.3 | DisplayString | read-only | current |
| inputUserConfigurableText3 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.3. | 1.3.6.1.4.1.12148.9.1.15.1.4 | DisplayString | read-only | current |
| inputUserConfigurableText4 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.4. | 1.3.6.1.4.1.12148.9.1.15.1.5 | DisplayString | read-only | current |
| inputUserConfigurableText5 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.5. | 1.3.6.1.4.1.12148.9.1.15.1.6 | DisplayString | read-only | current |
| inputUserConfigurableText6 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.6. | 1.3.6.1.4.1.12148.9.1.15.1.7 | DisplayString | read-only | current |
| inputUserConfigurableText7 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.7. | 1.3.6.1.4.1.12148.9.1.15.1.8 | DisplayString | read-only | current |
| inputUserConfigurableText8 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.8. | 1.3.6.1.4.1.12148.9.1.15.1.9 | DisplayString | read-only | current |
| inputUserConfigurableText9 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.9. | 1.3.6.1.4.1.12148.9.1.15.1.10 | DisplayString | read-only | current |
| inputUserConfigurableText10 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.10. | 1.3.6.1.4.1.12148.9.1.15.1.11 | DisplayString | read-only | current |
| systemResetCtrlSystem OBJECT-TYPE A pushbutton function that resets the control system. Configuration data will be kept. | 1.3.6.1.4.1.12148.9.1.16 | INTEGER {pushbutton(0), reboot(1)} | read-write | deprecated |
| ioUnits OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.1.17 | |||
| ioUnitNumberOfUnits OBJECT-TYPE | 1.3.6.1.4.1.12148.9.1.17.1 | Integer32 | read-only | current |
| ioUnitsIndex OBJECT-TYPE | 1.3.6.1.4.1.12148.9.1.17.2 | Integer32 (0..13) | accessible-for-notify | current |
| ioUnitsTable OBJECT-TYPE | 1.3.6.1.4.1.12148.9.1.17.3 | not-accessible | current | |
| ioUnitsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.9.1.17.3.1 | not-accessible | current | |
| ioUnitID OBJECT-TYPE | 1.3.6.1.4.1.12148.9.1.17.3.1.1 | Integer32 | read-only | current |
| ioUnitOutDoorTemp1 OBJECT-TYPE The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. | 1.3.6.1.4.1.12148.9.1.17.3.1.2 | Integer32 | read-only | current |
| ioUnitOutDoorTemp2 OBJECT-TYPE The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. | 1.3.6.1.4.1.12148.9.1.17.3.1.3 | Integer32 | read-only | current |
| ioUnitFanSpeed1 OBJECT-TYPE The speed of the cooling/ circulation fan. The speed is a percentage of max RPM. | 1.3.6.1.4.1.12148.9.1.17.3.1.4 | Integer32 | read-only | current |
| ioUnitFanSpeedDeltaValue1 OBJECT-TYPE The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value. | 1.3.6.1.4.1.12148.9.1.17.3.1.5 | Integer32 | read-only | current |
| ioUnitFanSpeed2 OBJECT-TYPE The speed of the cooling/ circulation fan. The speed is a percentage of max RPM. | 1.3.6.1.4.1.12148.9.1.17.3.1.6 | Integer32 | read-only | current |
| ioUnitFanSpeedDeltaValue2 OBJECT-TYPE The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value. | 1.3.6.1.4.1.12148.9.1.17.3.1.7 | Integer32 | read-only | current |
| ioUnitProgInputText1 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.1 | 1.3.6.1.4.1.12148.9.1.17.3.1.8 | DisplayString (SIZE(0..32)) | read-only | current |
| ioUnitProgInputStatus1 OBJECT-TYPE Programmable input status. | 1.3.6.1.4.1.12148.9.1.17.3.1.9 | INTEGER {normal(0), alarm(1)} | read-only | current |
| ioUnitProgInputText2 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.2 | 1.3.6.1.4.1.12148.9.1.17.3.1.10 | DisplayString (SIZE(0..32)) | read-only | current |
| ioUnitProgInputStatus2 OBJECT-TYPE Programmable input status. | 1.3.6.1.4.1.12148.9.1.17.3.1.11 | INTEGER {normal(0), alarm(1)} | read-only | current |
| ioUnitProgInputText3 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.3 | 1.3.6.1.4.1.12148.9.1.17.3.1.12 | DisplayString (SIZE(0..32)) | read-only | current |
| ioUnitProgInputStatus3 OBJECT-TYPE Programmable input status. | 1.3.6.1.4.1.12148.9.1.17.3.1.13 | INTEGER {normal(0), alarm(1)} | read-only | current |
| ioUnitProgInputText4 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.4 | 1.3.6.1.4.1.12148.9.1.17.3.1.14 | DisplayString (SIZE(0..32)) | read-only | current |
| ioUnitProgInputStatus4 OBJECT-TYPE Programmable input status. | 1.3.6.1.4.1.12148.9.1.17.3.1.15 | INTEGER {normal(0), alarm(1)} | read-only | current |
| ioUnitProgInputText5 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.5 | 1.3.6.1.4.1.12148.9.1.17.3.1.16 | DisplayString (SIZE(0..32)) | read-only | current |
| ioUnitProgInputStatus5 OBJECT-TYPE Programmable input status. | 1.3.6.1.4.1.12148.9.1.17.3.1.17 | INTEGER {normal(0), alarm(1)} | read-only | current |
| ioUnitProgInputText6 OBJECT-TYPE Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.6 | 1.3.6.1.4.1.12148.9.1.17.3.1.18 | DisplayString (SIZE(0..32)) | read-only | current |
| ioUnitProgInputStatus6 OBJECT-TYPE Programmable input status. | 1.3.6.1.4.1.12148.9.1.17.3.1.19 | INTEGER {normal(0), alarm(1)} | read-only | current |
| ioUnitProgInputValue1 OBJECT-TYPE The value read on input. | 1.3.6.1.4.1.12148.9.1.17.3.1.20 | Integer32 | read-only | current |
| ioUnitProgInputValue2 OBJECT-TYPE The value read on input. | 1.3.6.1.4.1.12148.9.1.17.3.1.21 | Integer32 | read-only | current |
| ioUnitProgInputValue3 OBJECT-TYPE The value read on input. | 1.3.6.1.4.1.12148.9.1.17.3.1.22 | Integer32 | read-only | current |
| ioUnitProgInputValue4 OBJECT-TYPE The value read on input. | 1.3.6.1.4.1.12148.9.1.17.3.1.23 | Integer32 | read-only | current |
| ioUnitProgInputValue5 OBJECT-TYPE The value read on input. | 1.3.6.1.4.1.12148.9.1.17.3.1.24 | Integer32 | read-only | current |
| ioUnitProgInputValue6 OBJECT-TYPE The value read on input. | 1.3.6.1.4.1.12148.9.1.17.3.1.25 | Integer32 | read-only | current |
| systemServiceMode OBJECT-TYPE This is a switch function to activate (1) or deactivate (0) servicemode. Status can also be read. Servicemode prevent the system to operate relays or send traps or mail. | 1.3.6.1.4.1.12148.9.1.18 | INTEGER {deactivate(0), activate(1)} | read-write | deprecated |
| dcSystem OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.2 | |||
| dcPlant OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.2.1 | |||
| systemSiteInfo OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.2.1.3 | |||
| systemSiteInfoCustomer OBJECT-TYPE The Customer name (as stored in the Control Unit). | 1.3.6.1.4.1.12148.9.2.1.3.1 | DisplayString (SIZE(0..32)) | read-only | current |
| systemSiteInfoLocation OBJECT-TYPE The system/site Location details (as stored in the Control Unit). | 1.3.6.1.4.1.12148.9.2.1.3.2 | DisplayString (SIZE(0..32)) | read-only | current |
| systemSiteInfoMessage1 OBJECT-TYPE The system/site Info Message record #1 (as stored in the Control Unit). 31 Bytes. | 1.3.6.1.4.1.12148.9.2.1.3.3 | DisplayString (SIZE(0..32)) | read-only | current |
| systemSiteInfoMessage2 OBJECT-TYPE The system/site Info Message record #2 (as stored in the Control Unit). 31 Bytes. | 1.3.6.1.4.1.12148.9.2.1.3.4 | DisplayString (SIZE(0..32)) | read-only | current |
| systemSiteInfoInstalledDate OBJECT-TYPE The system's Installed Date text string (as stored in the Control Unit) 16bytes. | 1.3.6.1.4.1.12148.9.2.1.3.5 | DisplayString (SIZE(0..16)) | read-only | current |
| systemSiteInfoControllerType OBJECT-TYPE The system Controller Module currently connected. 0 = AL175 1 = AL4000 (Aeon Gold) 2 = AL6000 3 = AL175OEM 4 = MCU 5 = SmartPack 6 = ComPack | 1.3.6.1.4.1.12148.9.2.1.3.6 | INTEGER {al175(0), al4000(1), al6000(2), al175oem(3), mcu(4), smartpack(5), compack(6), smartpack2(7)} | read-only | current |
| systemSiteInfoSystemSeriaNum OBJECT-TYPE The serial number for the complete system. | 1.3.6.1.4.1.12148.9.2.1.3.7 | DisplayString (SIZE(0..16)) | read-only | current |
| systemSiteInfoControllerSeriaNum OBJECT-TYPE The serial number for Control unit 1. | 1.3.6.1.4.1.12148.9.2.1.3.8 | DisplayString (SIZE(0..16)) | read-only | current |
| systemNominalVoltage OBJECT-TYPE The nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60V | 1.3.6.1.4.1.12148.9.2.1.4 | INTEGER {prs48v(0), prs24v(1), prs12v(2), prs26v(3), prs60v(4)} | read-only | current |
| systemOperationalStatus OBJECT-TYPE A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery test | 1.3.6.1.4.1.12148.9.2.2 | INTEGER {floatvoltreg(0), floattempcomp(1), batteryboost(2), batterytest(3)} | read-only | current |
| battery OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.3 | |||
| batteryName OBJECT-TYPE A descriptive name of the battery installed in the system. | 1.3.6.1.4.1.12148.9.3.1 | DisplayString (SIZE(0..31)) | read-only | current |
| batteryVoltage OBJECT-TYPE The measured battery voltage. | 1.3.6.1.4.1.12148.9.3.2 | Integer32 (0..7500) | read-only | current |
| batteryCurrent OBJECT-TYPE The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.3.3 | Integer32 | read-only | current |
| batteryTemp OBJECT-TYPE The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. | 1.3.6.1.4.1.12148.9.3.4 | Integer32 (0..9999) | read-only | current |
| batteryBreakerStatus OBJECT-TYPE The state of the battery fuses/breakers can be either normal(0) or alarm(1). | 1.3.6.1.4.1.12148.9.3.5 | INTEGER {normal(0), alarm(1)} | read-only | current |
| batteryChargeCurrentLimitCtrl OBJECT-TYPE Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable. | 1.3.6.1.4.1.12148.9.3.6 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryChargeCurrentLimitValue OBJECT-TYPE Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.3.7 | Integer32 (0..32000) | read-write | current |
| batteryTempCompEnable OBJECT-TYPE Enable (0) or Disable (1) of Battery Temperature Compensated output regulation mode | 1.3.6.1.4.1.12148.9.3.8 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryFloatVoltConfig OBJECT-TYPE The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging. | 1.3.6.1.4.1.12148.9.3.9 | Integer32 (4300..6000) | read-write | current |
| batteryBoostVoltConfig OBJECT-TYPE The Voltage at which the DC System boost charges the batteries. | 1.3.6.1.4.1.12148.9.3.10 | Integer32 (4300..6000) | read-write | current |
| batteryHighMajorAlarmVoltageConfig OBJECT-TYPE The Major High Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.9.3.11 | Integer32 | read-write | current |
| batteryHighMinorAlarmVoltageConfig OBJECT-TYPE The Minor High Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.9.3.12 | Integer32 | read-write | current |
| batteryLowMajorAlarmVoltageConfig OBJECT-TYPE The Major Low Battery Voltage Alarm limit set voltage | 1.3.6.1.4.1.12148.9.3.13 | Integer32 | read-write | current |
| batteryLowMinorAlarmVoltageConfig OBJECT-TYPE The Minor Low Battery Voltage Alarm limit set voltage | 1.3.6.1.4.1.12148.9.3.14 | Integer32 | read-write | current |
| batteryStartManualTest OBJECT-TYPE This pushbutton will start or stop a manual battery test if the system allows it. | 1.3.6.1.4.1.12148.9.3.15 | INTEGER {pushbutton(0), starttest(1), stoptest(2)} | read-write | current |
| batteryStartManualBoost OBJECT-TYPE This pushbutton will start or stop a manual battery boost if the system allows it. | 1.3.6.1.4.1.12148.9.3.16 | INTEGER {pushbutton(0), startboost(1), stopboost(2)} | read-write | current |
| batteryLVD OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.3.17 | |||
| batteryLVDStatus OBJECT-TYPE The Battery Contactor is connected(0), disconnected(1) or disabled(2) | 1.3.6.1.4.1.12148.9.3.17.1 | INTEGER {connected(0), disconnected(1), disabled(2)} | read-only | current |
| batteryLVDDisconnectVoltage OBJECT-TYPE The Battery Contactors Disconnect Voltage | 1.3.6.1.4.1.12148.9.3.17.2 | Integer32 (0..7200) | read-write | current |
| batteryLVDConnectVoltage OBJECT-TYPE The Battery Contactors Reconnect Voltage | 1.3.6.1.4.1.12148.9.3.17.3 | Integer32 (0..7200) | read-write | current |
| batteryBanksNumofBanks OBJECT-TYPE The number of Control units that is used to measure battery parameters. | 1.3.6.1.4.1.12148.9.3.18 | Integer32 (1..8) | read-only | current |
| batteryBanks OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.3.19 | |||
| batterySymmetryDeltaLimitVoltage OBJECT-TYPE The allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state. | 1.3.6.1.4.1.12148.9.3.19.1 | Integer32 | read-write | current |
| batteryBanksIndex OBJECT-TYPE Index used for navigating the rows 1..8 of batteryBanksTable | 1.3.6.1.4.1.12148.9.3.19.2 | Integer32 (0..7) | accessible-for-notify | current |
| batteryBanksTable OBJECT-TYPE A table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments. | 1.3.6.1.4.1.12148.9.3.19.3 | not-accessible | current | |
| batteryBanksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.9.3.19.3.1 | not-accessible | current | |
| batteryBankID OBJECT-TYPE The ID of the selected row in the table. i.e. the battery bank. | 1.3.6.1.4.1.12148.9.3.19.3.1.1 | Integer32 (1..8) | read-only | current |
| batteryBanksSymmetry1enable OBJECT-TYPE Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. | 1.3.6.1.4.1.12148.9.3.19.3.1.2 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryBanksSymmetry1status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.19.3.1.3 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryBanksSymmetry1deltaVoltage OBJECT-TYPE The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. | 1.3.6.1.4.1.12148.9.3.19.3.1.4 | Integer32 | read-only | current |
| batteryBanksSymmetry2enable OBJECT-TYPE Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. | 1.3.6.1.4.1.12148.9.3.19.3.1.5 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryBanksSymmetry2status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.19.3.1.6 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryBanksSymmetry2deltaVoltage OBJECT-TYPE The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. | 1.3.6.1.4.1.12148.9.3.19.3.1.7 | Integer32 | read-only | current |
| batteryBanksSymmetry3enable OBJECT-TYPE Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. | 1.3.6.1.4.1.12148.9.3.19.3.1.8 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryBanksSymmetry3status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.19.3.1.9 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryBanksSymmetry3deltaVoltage OBJECT-TYPE The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. | 1.3.6.1.4.1.12148.9.3.19.3.1.10 | Integer32 | read-only | current |
| batteryBanksSymmetry4enable OBJECT-TYPE Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. | 1.3.6.1.4.1.12148.9.3.19.3.1.11 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryBanksSymmetry4status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.19.3.1.12 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryBanksSymmetry4deltaVoltage OBJECT-TYPE The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. | 1.3.6.1.4.1.12148.9.3.19.3.1.13 | Integer32 | read-only | current |
| batteryBanksSymmetry5enable OBJECT-TYPE Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. | 1.3.6.1.4.1.12148.9.3.19.3.1.14 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryBanksSymmetry5status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.19.3.1.15 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryBanksSymmetry5deltaVoltage OBJECT-TYPE The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. | 1.3.6.1.4.1.12148.9.3.19.3.1.16 | Integer32 | read-only | current |
| batteryBanksSymmetry6enable OBJECT-TYPE Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. | 1.3.6.1.4.1.12148.9.3.19.3.1.17 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryBanksSymmetry6status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.19.3.1.18 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryBanksSymmetry6deltaVoltage OBJECT-TYPE The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. | 1.3.6.1.4.1.12148.9.3.19.3.1.19 | Integer32 | read-only | current |
| batteryBanksSymmetry7enable OBJECT-TYPE Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. | 1.3.6.1.4.1.12148.9.3.19.3.1.20 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryBanksSymmetry7status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.19.3.1.21 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryBanksSymmetry7deltaVoltage OBJECT-TYPE The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. | 1.3.6.1.4.1.12148.9.3.19.3.1.22 | Integer32 | read-only | current |
| batteryBanksSymmetry8enable OBJECT-TYPE Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. | 1.3.6.1.4.1.12148.9.3.19.3.1.23 | INTEGER {disable(0), enable(1)} | read-write | current |
| batteryBanksSymmetry8status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.19.3.1.24 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryBanksSymmetry8deltaVoltage OBJECT-TYPE The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. | 1.3.6.1.4.1.12148.9.3.19.3.1.25 | Integer32 | read-only | current |
| batteryBanksNumberOfStrings OBJECT-TYPE Number of strings in the power system. | 1.3.6.1.4.1.12148.9.3.19.4 | Integer32 | read-only | current |
| batteryBanksExtensionIndex OBJECT-TYPE Index used for navigating the rows 1..14 of batteryBanksExtensionTable | 1.3.6.1.4.1.12148.9.3.19.5 | Integer32 (0..7) | accessible-for-notify | current |
| batteryBanksExtensionTable OBJECT-TYPE This table shows the measured value on the symmetry inputs. | 1.3.6.1.4.1.12148.9.3.19.6 | not-accessible | current | |
| batteryBanksExtensionEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.9.3.19.6.1 | not-accessible | current | |
| batteryBanksExtensionID OBJECT-TYPE The ID of the selected row in the table. i.e. the battery bank. | 1.3.6.1.4.1.12148.9.3.19.6.1.1 | Integer32 | read-only | current |
| batteryBanksExtensionSymmetryInputValue1 OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.19.6.1.2 | Integer32 | read-only | current |
| batteryBanksExtensionSymmetryInputValue2 OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.19.6.1.3 | Integer32 | read-only | current |
| batteryBanksExtensionSymmetryInputValue3 OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.19.6.1.4 | Integer32 | read-only | current |
| batteryBanksExtensionSymmetryInputValue4 OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.19.6.1.5 | Integer32 | read-only | current |
| batteryBanksExtensionSymmetryInputValue5 OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.19.6.1.6 | Integer32 | read-only | current |
| batteryBanksExtensionSymmetryInputValue6 OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.19.6.1.7 | Integer32 | read-only | current |
| batteryBanksExtensionSymmetryInputValue7 OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.19.6.1.8 | Integer32 | read-only | current |
| batteryBanksExtensionSymmetryInputValue8 OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.19.6.1.9 | Integer32 | read-only | current |
| batteryCapacityData OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.3.20 | |||
| batteryTimeToDisconnect OBJECT-TYPE Remaining time to low voltage battery disconnect. | 1.3.6.1.4.1.12148.9.3.20.1 | Integer32 | read-only | current |
| batteryCapacityLeft OBJECT-TYPE Capacity left in the battery. | 1.3.6.1.4.1.12148.9.3.20.2 | Integer32 | read-only | current |
| batteryCapacityUsed OBJECT-TYPE Capacity consumed. | 1.3.6.1.4.1.12148.9.3.20.3 | Integer32 | read-only | current |
| batteryCapacityTotal OBJECT-TYPE This is the total Capacity of the battery. This value is the installed capacity compensated with the last battery tests quality level | 1.3.6.1.4.1.12148.9.3.20.4 | Integer32 | read-only | current |
| batteryQuality OBJECT-TYPE This is the battery quality (%) of the latest battery test. | 1.3.6.1.4.1.12148.9.3.20.5 | Integer32 | read-only | current |
| batteryMonitorUnits OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.3.21 | |||
| battmonNumberOfUnits OBJECT-TYPE Number of battery monitor units in the power system. | 1.3.6.1.4.1.12148.9.3.21.1 | Integer32 | read-only | current |
| battmonUnitsIndex OBJECT-TYPE Index used for navigating the rows 1..14 of battmonUnitsTable | 1.3.6.1.4.1.12148.9.3.21.2 | Integer32 | accessible-for-notify | current |
| battmonUnitsTable OBJECT-TYPE A table of up to 14 battery monitor control units. | 1.3.6.1.4.1.12148.9.3.21.3 | not-accessible | current | |
| battmonUnitsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.9.3.21.3.1 | not-accessible | current | |
| batteryMonitorID OBJECT-TYPE The ID of the selected row | 1.3.6.1.4.1.12148.9.3.21.3.1.1 | Integer32 (1..14) | read-only | current |
| batteryMonitorSymmetry1status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.21.3.1.2 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryMonitorSymmetry1InputValue OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.21.3.1.3 | Integer32 | read-only | current |
| batteryMonitorSymmetry2status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.21.3.1.4 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryMonitorSymmetry2InputValue OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.21.3.1.5 | Integer32 | read-only | current |
| batteryMonitorSymmetry3status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.21.3.1.6 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryMonitorSymmetry3InputValue OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.21.3.1.7 | Integer32 | read-only | current |
| batteryMonitorSymmetry4status OBJECT-TYPE Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error | 1.3.6.1.4.1.12148.9.3.21.3.1.8 | INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)} | read-only | current |
| batteryMonitorSymmetry4InputValue OBJECT-TYPE The measured voltage on the symmetry input. | 1.3.6.1.4.1.12148.9.3.21.3.1.9 | Integer32 | read-only | current |
| batteryMonitorCurrentValue OBJECT-TYPE The measured current to/from the battery. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.3.21.3.1.10 | Integer32 | read-only | current |
| batteryMonitorFuseStatus OBJECT-TYPE The state of the battery fuse/breaker can be either normal(0) or alarm(1). | 1.3.6.1.4.1.12148.9.3.21.3.1.11 | INTEGER {normal(0), alarm(1)} | read-only | current |
| batteryMonitorTemperature OBJECT-TYPE The battery temperature. | 1.3.6.1.4.1.12148.9.3.21.3.1.12 | Integer32 | read-only | current |
| batteryHighMajorTempAlarmLevel OBJECT-TYPE This is the Major High Temperature Alarm level. | 1.3.6.1.4.1.12148.9.3.22 | Integer32 | read-write | current |
| batteryHighMinorTempAlarmLevel OBJECT-TYPE This is the Minor High Temperature Alarm level. | 1.3.6.1.4.1.12148.9.3.23 | Integer32 | read-write | current |
| batteryTest OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.3.24 | |||
| batteryTestEndVoltage OBJECT-TYPE The end voltage for standard battery test (V/cell) 1/100 Volt; i.e. 190 = 1.90V | 1.3.6.1.4.1.12148.9.3.24.1 | Integer32 | read-write | current |
| batteryTestMaximumDischargeTime OBJECT-TYPE The maximum allowed run time for the battery test (Minutes) | 1.3.6.1.4.1.12148.9.3.24.2 | Integer32 | read-write | current |
| batteryTestMaximumDischargeAh OBJECT-TYPE The maximum allowed discharge for the batteries during a battery test (Ah) | 1.3.6.1.4.1.12148.9.3.24.3 | Integer32 | read-write | current |
| loadDistribution OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.4 | |||
| loadDistributionCurrent OBJECT-TYPE The total load current Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.4.1 | Integer32 | read-only | current |
| loadDistributionBreakerStatus OBJECT-TYPE The state of the load fuses/breakers can be either normal(0) or alarm(1) | 1.3.6.1.4.1.12148.9.4.2 | INTEGER {normal(0), alarm(1)} | read-only | current |
| loadDistributionLVDStatus OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.4.3 | |||
| loadLVD1Enable OBJECT-TYPE The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. | 1.3.6.1.4.1.12148.9.4.3.1 | INTEGER {disabled(0), enabled(1)} | read-only | current |
| loadLVD1Status OBJECT-TYPE The load Contactor 1 is connected(0), disconnected(1) or disabled(2) | 1.3.6.1.4.1.12148.9.4.3.2 | INTEGER {connected(0), disconnected(1), disabled(2)} | read-only | current |
| loadLVD1ConnectVoltage OBJECT-TYPE LVLD1 Connect Voltage | 1.3.6.1.4.1.12148.9.4.3.3 | Integer32 (0..7200) | read-write | current |
| loadLVD1DisconnectVoltage OBJECT-TYPE LVLD1 Disconnect Voltage | 1.3.6.1.4.1.12148.9.4.3.4 | Integer32 (0..7200) | read-write | current |
| loadLVD2Enable OBJECT-TYPE The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. | 1.3.6.1.4.1.12148.9.4.3.5 | INTEGER {disabled(0), enabled(1)} | read-only | current |
| loadLVD2Status OBJECT-TYPE The load Contactor 2 is connected(0), disconnected(1) or disabled(2) | 1.3.6.1.4.1.12148.9.4.3.6 | INTEGER {connected(0), disconnected(1), disabled(2)} | read-only | current |
| loadLVD2ConnectVoltage OBJECT-TYPE LVLD2 Connect Voltage | 1.3.6.1.4.1.12148.9.4.3.7 | Integer32 (0..7200) | read-write | current |
| loadLVD2DisconnectVoltage OBJECT-TYPE LVLD2 Disconnect Voltage | 1.3.6.1.4.1.12148.9.4.3.8 | Integer32 (0..7200) | read-write | current |
| loadLVD3Enable OBJECT-TYPE The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. | 1.3.6.1.4.1.12148.9.4.3.9 | INTEGER {disabled(0), enabled(1)} | read-only | current |
| loadLVD3Status OBJECT-TYPE The load Contactor 3 is connected(0), disconnected(1) or disabled(2) | 1.3.6.1.4.1.12148.9.4.3.10 | INTEGER {connected(0), disconnected(1), disabled(2)} | read-only | current |
| loadLVD3ConnectVoltage OBJECT-TYPE LVLD3 Connect Voltage | 1.3.6.1.4.1.12148.9.4.3.11 | Integer32 (0..7200) | read-write | current |
| loadLVD3DisconnectVoltage OBJECT-TYPE LVLD3 Disconnect Voltage | 1.3.6.1.4.1.12148.9.4.3.12 | Integer32 (0..7200) | read-write | current |
| loadMonitorUnits OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.4.4 | |||
| loadmonitorNumberOfUnits OBJECT-TYPE | 1.3.6.1.4.1.12148.9.4.4.1 | Integer32 | read-only | current |
| loadMonitorUnitsIndex OBJECT-TYPE | 1.3.6.1.4.1.12148.9.4.4.2 | Integer32 (0..13) | accessible-for-notify | current |
| loadMonitorUnitsTable OBJECT-TYPE | 1.3.6.1.4.1.12148.9.4.4.3 | not-accessible | current | |
| loadMonitorUnitsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.9.4.4.3.1 | not-accessible | current | |
| loadMonitorID OBJECT-TYPE | 1.3.6.1.4.1.12148.9.4.4.3.1.1 | Integer32 | read-only | current |
| loadMonitorFuseStatus1 OBJECT-TYPE The state of the load fuses/breakers can be either normal(0) or alarm(1) | 1.3.6.1.4.1.12148.9.4.4.3.1.2 | INTEGER {normal(0), alarm(1)} | read-only | current |
| loadMonitorCurrent1 OBJECT-TYPE The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.4.4.3.1.3 | Integer32 | read-only | current |
| loadMonitorFuseStatus2 OBJECT-TYPE The state of the load fuses/breakers can be either normal(0) or alarm(1) | 1.3.6.1.4.1.12148.9.4.4.3.1.4 | INTEGER {normal(0), alarm(1)} | read-only | current |
| loadMonitorCurrent2 OBJECT-TYPE The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.4.4.3.1.5 | Integer32 | read-only | current |
| loadMonitorFuseStatus3 OBJECT-TYPE The state of the load fuses/breakers can be either normal(0) or alarm(1) | 1.3.6.1.4.1.12148.9.4.4.3.1.6 | INTEGER {normal(0), alarm(1)} | read-only | current |
| loadMonitorCurrent3 OBJECT-TYPE The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.4.4.3.1.7 | Integer32 | read-only | current |
| loadMonitorFuseStatus4 OBJECT-TYPE The state of the load fuses/breakers can be either normal(0) or alarm(1) | 1.3.6.1.4.1.12148.9.4.4.3.1.8 | INTEGER {normal(0), alarm(1)} | read-only | current |
| loadMonitorCurrent4 OBJECT-TYPE The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.4.4.3.1.9 | Integer32 | read-only | current |
| loadMonitorFuseStatus5 OBJECT-TYPE The state of the load fuses/breakers can be either normal(0) or alarm(1) | 1.3.6.1.4.1.12148.9.4.4.3.1.10 | INTEGER {normal(0), alarm(1)} | read-only | current |
| loadMonitorCurrent5 OBJECT-TYPE The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.4.4.3.1.11 | Integer32 | read-only | current |
| loadMonitorFuseStatus6 OBJECT-TYPE The state of the load fuses/breakers can be either normal(0) or alarm(1) | 1.3.6.1.4.1.12148.9.4.4.3.1.12 | INTEGER {normal(0), alarm(1)} | read-only | current |
| loadMonitorCurrent6 OBJECT-TYPE The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.4.4.3.1.13 | Integer32 | read-only | current |
| loadMonitorFuseStatus7 OBJECT-TYPE The state of the load fuses/breakers can be either normal(0) or alarm(1) | 1.3.6.1.4.1.12148.9.4.4.3.1.14 | INTEGER {normal(0), alarm(1)} | read-only | current |
| loadMonitorCurrent7 OBJECT-TYPE The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.4.4.3.1.15 | Integer32 | read-only | current |
| loadMonitorFuseStatus8 OBJECT-TYPE The state of the load fuses/breakers can be either normal(0) or alarm(1) | 1.3.6.1.4.1.12148.9.4.4.3.1.16 | INTEGER {normal(0), alarm(1)} | read-only | current |
| loadMonitorCurrent8 OBJECT-TYPE The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.9.4.4.3.1.17 | Integer32 | read-only | current |
| rectifier OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.5 | |||
| rectifierInstalledRectifiers OBJECT-TYPE The number of installed rectifiers for this DC Power System. | 1.3.6.1.4.1.12148.9.5.1 | Integer32 (1..101) | read-only | current |
| rectifierRectifiersActive OBJECT-TYPE Not Used! | 1.3.6.1.4.1.12148.9.5.2 | Integer32 (1..101) | read-only | current |
| rectifierTotalCurrent OBJECT-TYPE The DC system's total delivered rectifier current | 1.3.6.1.4.1.12148.9.5.3 | Integer32 | read-only | current |
| rectifierUtilization OBJECT-TYPE Utilization in % of available rectifier capacity | 1.3.6.1.4.1.12148.9.5.4 | Integer32 (0..100) | read-only | current |
| rectifierStatus OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.5.5 | |||
| rectifierStatusNoIndex OBJECT-TYPE An offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first row i.e. setting the index to 11 will give a range from rectifier ID12 to ID31. Setting the index to 0 will give a range from rectifier ID1 to ID20. | 1.3.6.1.4.1.12148.9.5.5.1 | Integer32 (0..95) | read-write | current |
| rectifierStatusTable OBJECT-TYPE A table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex | 1.3.6.1.4.1.12148.9.5.5.2 | not-accessible | current | |
| rectifierStatusEntry OBJECT-TYPE A row of rectifier status data corresponding to the rectifierStatusNoIndex value | 1.3.6.1.4.1.12148.9.5.5.2.1 | not-accessible | current | |
| rectifierStatusID OBJECT-TYPE The rectifier ID number of the rectifier. | 1.3.6.1.4.1.12148.9.5.5.2.1.1 | Integer32 (1..100) | read-only | current |
| rectifierStatusStatus OBJECT-TYPE The operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4) | 1.3.6.1.4.1.12148.9.5.5.2.1.2 | INTEGER {notPresent(0), normal(1), alarm(2), notUsed(3), disabled(4)} | read-only | current |
| rectifierStatusOutputCurrent OBJECT-TYPE The output current of the rectifier. | 1.3.6.1.4.1.12148.9.5.5.2.1.3 | Integer32 (0..65535) | read-only | current |
| rectifierStatusOutputVoltage OBJECT-TYPE The rectifier voltage of the rectifier record. | 1.3.6.1.4.1.12148.9.5.5.2.1.4 | Integer32 (0..65535) | read-only | current |
| rectifierStatusTemp OBJECT-TYPE The input air temperature of the rectifier. | 1.3.6.1.4.1.12148.9.5.5.2.1.5 | Integer32 (0..65535) | read-only | current |
| rectifierStatusType OBJECT-TYPE The rectifier article number string of the rectifier record. | 1.3.6.1.4.1.12148.9.5.5.2.1.6 | DisplayString (SIZE(0..32)) | read-only | current |
| rectifierStatusSKU OBJECT-TYPE The rectifier part number. | 1.3.6.1.4.1.12148.9.5.5.2.1.7 | DisplayString (SIZE(1..32)) | read-only | current |
| rectifierStatusSerialNo OBJECT-TYPE The rectifier serial number string of the rectifier record. | 1.3.6.1.4.1.12148.9.5.5.2.1.8 | DisplayString (SIZE(0..16)) | read-only | current |
| rectifierStatusRevisionLevel OBJECT-TYPE The rectifier HW revision number string of the rectifier record. | 1.3.6.1.4.1.12148.9.5.5.2.1.9 | DisplayString (SIZE(0..16)) | read-only | current |
| acDistribution OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.6 | |||
| acVoltage1 OBJECT-TYPE The AC Voltage of phase 1 | 1.3.6.1.4.1.12148.9.6.1 | Integer32 | read-only | current |
| acVoltage2 OBJECT-TYPE The AC Voltage of phase 2 | 1.3.6.1.4.1.12148.9.6.2 | Integer32 | read-only | current |
| acVoltage3 OBJECT-TYPE The AC Voltage of phase 3 | 1.3.6.1.4.1.12148.9.6.3 | Integer32 | read-only | current |
| alarmGroup OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.7 | |||
| alarmWellknownAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.7.1 | |||
| alarmMajorHighBattVolt OBJECT-TYPE The Major High Battery Voltage Alarm | 1.3.6.1.4.1.12148.9.7.1.1 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMinorHighBattVolt OBJECT-TYPE The Minor High Battery Voltage alarm | 1.3.6.1.4.1.12148.9.7.1.2 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMajorLowBattVolt OBJECT-TYPE The Major Low Battery Voltage Alarm | 1.3.6.1.4.1.12148.9.7.1.3 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMinorLowBattVolt OBJECT-TYPE The Minor Low Battery Voltage Alarm | 1.3.6.1.4.1.12148.9.7.1.4 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMajorBatteryHighTemp OBJECT-TYPE The Major High Battery Temperature alarm. | 1.3.6.1.4.1.12148.9.7.1.5 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMinorBatteryHighTemp OBJECT-TYPE The Minor High Battery Temperature alarm. | 1.3.6.1.4.1.12148.9.7.1.6 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmBatteryDisconnectOpen OBJECT-TYPE The Battery Disconnect Contactor alarm | 1.3.6.1.4.1.12148.9.7.1.7 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmLVD1open OBJECT-TYPE The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. | 1.3.6.1.4.1.12148.9.7.1.8 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmLVD2open OBJECT-TYPE The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. | 1.3.6.1.4.1.12148.9.7.1.9 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmLVD3open OBJECT-TYPE The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. | 1.3.6.1.4.1.12148.9.7.1.10 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmACmains OBJECT-TYPE The AC voltage has dropped below critical level, or one or more AC input phases was lost. | 1.3.6.1.4.1.12148.9.7.1.11 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmBatteryBreakerOpen OBJECT-TYPE A battery breaker/fuse alarm. | 1.3.6.1.4.1.12148.9.7.1.12 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmDistributionBreakerOpen OBJECT-TYPE A Load Distribution breaker/fuse alarm. | 1.3.6.1.4.1.12148.9.7.1.13 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMajorRectifier OBJECT-TYPE This is a Major Rectifier alarm. | 1.3.6.1.4.1.12148.9.7.1.14 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMinorRectifier OBJECT-TYPE This is a Minor Rectifier alarm. | 1.3.6.1.4.1.12148.9.7.1.15 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMajorBatterySymmetry OBJECT-TYPE Battery Symmetry Delta Voltage Major alarm. | 1.3.6.1.4.1.12148.9.7.1.16 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMinorBatterySymmetry OBJECT-TYPE Battery Symmetry Delta Voltage Minor alarm | 1.3.6.1.4.1.12148.9.7.1.17 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmBatteryLifeEnded OBJECT-TYPE The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. | 1.3.6.1.4.1.12148.9.7.1.18 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmBatteryTestmodeEntered OBJECT-TYPE The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. | 1.3.6.1.4.1.12148.9.7.1.19 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmBatteryBoostmodeEntered OBJECT-TYPE The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging. | 1.3.6.1.4.1.12148.9.7.1.20 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmIoUnitTemp1 OBJECT-TYPE High or low temperature alarm 1 from any of the IO units. | 1.3.6.1.4.1.12148.9.7.1.21 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmIoUnitTemp2 OBJECT-TYPE High or low temperature alarm 2 from any of the IO units. | 1.3.6.1.4.1.12148.9.7.1.22 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmIoUnitDeltaFanSpeed1 OBJECT-TYPE Delta fan speed 1 from any of the IO units. | 1.3.6.1.4.1.12148.9.7.1.23 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmIoUnitDeltaFanSpeed2 OBJECT-TYPE Delta fan speed 2 from any of the IO units. | 1.3.6.1.4.1.12148.9.7.1.24 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMajorSolar OBJECT-TYPE This is a Major Solar alarm. | 1.3.6.1.4.1.12148.9.7.1.25 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMinorSolar OBJECT-TYPE This is a Major Solar alarm. | 1.3.6.1.4.1.12148.9.7.1.26 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMajorRectifierCapacity OBJECT-TYPE This is a Major Rectifier Capacity alarm. | 1.3.6.1.4.1.12148.9.7.1.27 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmMinorRectifierCapacity OBJECT-TYPE This is a Minor Rectifier Capacity alarm. | 1.3.6.1.4.1.12148.9.7.1.28 | INTEGER {normal(0), alarm(1)} | read-only | current |
| solarCharger OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.9 | |||
| solarChargerInstalledsolarChargers OBJECT-TYPE The number of installed solar chargers for this DC Power System. | 1.3.6.1.4.1.12148.9.9.1 | Integer32 (1..101) | read-only | current |
| solarChargersActive OBJECT-TYPE Not Used! | 1.3.6.1.4.1.12148.9.9.2 | Integer32 (1..101) | read-only | current |
| solarChargerTotalCurrent OBJECT-TYPE The DC system's total delivered solar current | 1.3.6.1.4.1.12148.9.9.3 | Integer32 | read-only | current |
| solarChargerUtilization OBJECT-TYPE Utilization in % of available solar capacity | 1.3.6.1.4.1.12148.9.9.4 | Integer32 (0..100) | read-only | current |
| solarChargerStatus OBJECT-IDENTITY | 1.3.6.1.4.1.12148.9.9.5 | |||
| solarChargerStatusNoIndex OBJECT-TYPE An offset for the solarStatusTable array. The solar status table has a fixed number of 20 rows. This OID sets the offset for the solarcharger in the first row i.e. setting the index to 11 will give a range from solarcharger ID12 to ID31. Setting the index to 0 will give a range from solarcharger ID1 to ID20. | 1.3.6.1.4.1.12148.9.9.5.1 | Integer32 (0..95) | read-write | current |
| solarChargerStatusTable OBJECT-TYPE A table listing up to 20 solarchargers, starting from the solarcharger number specified by solarStatusNoIndex | 1.3.6.1.4.1.12148.9.9.5.2 | not-accessible | current | |
| solarChargerStatusEntry OBJECT-TYPE A row of rectifier status data corresponding to the rectifierStatusNoIndex value | 1.3.6.1.4.1.12148.9.9.5.2.1 | not-accessible | current | |
| solarChargerStatusID OBJECT-TYPE The ID number of the solarcharger. | 1.3.6.1.4.1.12148.9.9.5.2.1.1 | Integer32 (1..100) | read-only | current |
| solarChargerStatusStatus OBJECT-TYPE The operational status of the solarcharger record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4) | 1.3.6.1.4.1.12148.9.9.5.2.1.2 | INTEGER {notPresent(0), normal(1), alarm(2), notUsed(3), disabled(4)} | read-only | current |
| solarChargerOutputCurrent OBJECT-TYPE The output current of the solarcharger. | 1.3.6.1.4.1.12148.9.9.5.2.1.3 | Integer32 (0..65535) | read-only | current |
| solarChargerOutputVoltage OBJECT-TYPE The output voltage of the solarcharger. | 1.3.6.1.4.1.12148.9.9.5.2.1.4 | Integer32 (0..65535) | read-only | current |
| solarChargerTemp OBJECT-TYPE The input air temperature of the solarcharger. | 1.3.6.1.4.1.12148.9.9.5.2.1.5 | Integer32 (0..65535) | read-only | current |
| solarChargerType OBJECT-TYPE The article number string of the solarcharger. | 1.3.6.1.4.1.12148.9.9.5.2.1.6 | DisplayString (SIZE(0..32)) | read-only | current |
| solarChargerSKU OBJECT-TYPE The solarcharger part number. | 1.3.6.1.4.1.12148.9.9.5.2.1.7 | DisplayString (SIZE(1..32)) | read-only | current |
| solarChargerSerialNo OBJECT-TYPE The serial number string of the solarcharger. | 1.3.6.1.4.1.12148.9.9.5.2.1.8 | DisplayString (SIZE(0..16)) | read-only | current |
| solarChargerRevisionLevel OBJECT-TYPE The HW revision number string of the solarcharger. | 1.3.6.1.4.1.12148.9.9.5.2.1.9 | DisplayString (SIZE(0..16)) | read-only | current |
Notifications
| Name | OID | Status |
|---|---|---|
| alarmMajorHighBattVoltTrap NOTIFICATION-TYPE The Major High Battery Voltage alarm | 1.3.6.1.4.1.12148.9.8.1 | current |
| alarmMinorHighBattVoltTrap NOTIFICATION-TYPE The Minor High Battery Voltage alarm | 1.3.6.1.4.1.12148.9.8.2 | current |
| alarmMajorLowBattVoltTrap NOTIFICATION-TYPE The Major Low Battery Voltage Alarm | 1.3.6.1.4.1.12148.9.8.3 | current |
| alarmMinorLowBattVoltTrap NOTIFICATION-TYPE The Minor Low Battery Voltage Alarm | 1.3.6.1.4.1.12148.9.8.4 | current |
| alarmMajorBatteryHighTempTrap NOTIFICATION-TYPE The Major High Battery Temperature alarm. | 1.3.6.1.4.1.12148.9.8.5 | current |
| alarmMinorBatteryHighTempTrap NOTIFICATION-TYPE The Minor High Battery Temperature alarm. | 1.3.6.1.4.1.12148.9.8.6 | current |
| alarmBatteryDisconnectOpenTrap NOTIFICATION-TYPE The Battery Disconnect Contactor alarm | 1.3.6.1.4.1.12148.9.8.7 | current |
| alarmLVD1openTrap NOTIFICATION-TYPE The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. | 1.3.6.1.4.1.12148.9.8.8 | current |
| alarmLVD2openTrap NOTIFICATION-TYPE The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. | 1.3.6.1.4.1.12148.9.8.9 | current |
| alarmLVD3openTrap NOTIFICATION-TYPE The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. | 1.3.6.1.4.1.12148.9.8.10 | current |
| alarmACmainsTrap NOTIFICATION-TYPE The AC voltage has dropped below critical level, or one or more AC input phases was lost. | 1.3.6.1.4.1.12148.9.8.11 | current |
| alarmBatteryBreakerOpenTrap NOTIFICATION-TYPE A battery breaker/fuse alarm. | 1.3.6.1.4.1.12148.9.8.12 | current |
| alarmDistributionBreakerOpenTrap NOTIFICATION-TYPE A Load Distribution breaker/fuse alarm. | 1.3.6.1.4.1.12148.9.8.13 | current |
| alarmMajorRectifierTrap NOTIFICATION-TYPE This is a Major Rectifier alarm. | 1.3.6.1.4.1.12148.9.8.14 | current |
| alarmMinorRectifierTrap NOTIFICATION-TYPE This is a Minor Rectifier alarm. | 1.3.6.1.4.1.12148.9.8.15 | current |
| alarmMajorBatterySymmetryTrap NOTIFICATION-TYPE Battery Symmetry Delta Voltage Major alarm | 1.3.6.1.4.1.12148.9.8.16 | current |
| alarmMinorBatterySymmetryTrap NOTIFICATION-TYPE Battery Symmetry Delta Voltage Minor alarm | 1.3.6.1.4.1.12148.9.8.17 | current |
| alarmBatteryLifeEndedTrap NOTIFICATION-TYPE The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. | 1.3.6.1.4.1.12148.9.8.18 | current |
| alarmBatteryTestmodeEnteredTrap NOTIFICATION-TYPE The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. | 1.3.6.1.4.1.12148.9.8.19 | current |
| alarmBatteryBoostmodeEnteredTrap NOTIFICATION-TYPE The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging. | 1.3.6.1.4.1.12148.9.8.20 | current |
| alarmController1proginputTrap NOTIFICATION-TYPE Programmable input alarm for Control unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | 1.3.6.1.4.1.12148.9.8.21 | current |
| alarmController2proginputTrap NOTIFICATION-TYPE Programmable input alarm for Control unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | 1.3.6.1.4.1.12148.9.8.22 | current |
| alarmController3proginputTrap NOTIFICATION-TYPE Programmable input alarm for Control unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | 1.3.6.1.4.1.12148.9.8.23 | current |
| alarmController4proginputTrap NOTIFICATION-TYPE Programmable input alarm for Control unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | 1.3.6.1.4.1.12148.9.8.24 | current |
| alarmController5proginputTrap NOTIFICATION-TYPE Programmable input alarm for Control unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | 1.3.6.1.4.1.12148.9.8.25 | current |
| alarmController6proginputTrap NOTIFICATION-TYPE Programmable input alarm for Control unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | 1.3.6.1.4.1.12148.9.8.26 | current |
| alarmController7proginputTrap NOTIFICATION-TYPE Programmable input alarm for Control unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | 1.3.6.1.4.1.12148.9.8.27 | current |
| alarmController8proginputTrap NOTIFICATION-TYPE Programmable input alarm for Control unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | 1.3.6.1.4.1.12148.9.8.28 | current |
| infoHeartBeatTrap NOTIFICATION-TYPE When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up. | 1.3.6.1.4.1.12148.9.8.29 | current |
| alarmIoUnitTemp1Trap NOTIFICATION-TYPE High or low temperature alarm 1 from any of the IO units. | 1.3.6.1.4.1.12148.9.8.30 | current |
| alarmIoUnitTemp2Trap NOTIFICATION-TYPE High or low temperature alarm 2 from any of the IO units. | 1.3.6.1.4.1.12148.9.8.31 | current |
| alarmIoUnitDeltaFanSpeed1Trap NOTIFICATION-TYPE Delta fan speed 1 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level. | 1.3.6.1.4.1.12148.9.8.32 | current |
| alarmIoUnitDeltaFanSpeed2Trap NOTIFICATION-TYPE Delta fan speed 2 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level. | 1.3.6.1.4.1.12148.9.8.33 | current |
| alarmIoUnit1proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.34 | current |
| alarmIoUnit2proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.35 | current |
| alarmIoUnit3proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.36 | current |
| alarmIoUnit4proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.37 | current |
| alarmIoUnit5proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.38 | current |
| alarmIoUnit6proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.39 | current |
| alarmIoUnit7proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.40 | current |
| alarmIoUnit8proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.41 | current |
| alarmIoUnit9proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 9. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.42 | current |
| alarmIoUnit10proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 10. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.43 | current |
| alarmIoUnit11proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 11. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.44 | current |
| alarmIoUnit12proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 12. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.45 | current |
| alarmIoUnit13proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 13. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.46 | current |
| alarmIoUnit14proginputTrap NOTIFICATION-TYPE Programmable input alarm for IO Unit 14. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | 1.3.6.1.4.1.12148.9.8.47 | current |
| alarmMajorSolarChargerTrap NOTIFICATION-TYPE The Major Solar Charger alarm | 1.3.6.1.4.1.12148.9.8.48 | current |
| alarmMinorSolarChargerTrap NOTIFICATION-TYPE The Minor Solar Charger alarm | 1.3.6.1.4.1.12148.9.8.49 | current |
| alarmMajorRectifierCapacityTrap NOTIFICATION-TYPE The Major Rectifier Capacity alarm | 1.3.6.1.4.1.12148.9.8.50 | current |
| alarmMinorRectifierCapacityTrap NOTIFICATION-TYPE The Minor Rectifier Capacity alarm | 1.3.6.1.4.1.12148.9.8.51 | current |
Conformance
| Name | OID | Status |
|---|---|---|
| dcSystemTraps NOTIFICATION-GROUP This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap | 1.3.6.1.4.1.12148.9.8 | current |