MIBs Depot

ELTEK-DISTRIBUTED-MIB

Registered at
1.3.6.1.4.1.12148
Last updated
2015-01-03 08:25
Organization
ELTEK power System MIB Working Group
Revisions
2016-02-18 14:16, 2015-01-03 08:25, 2011-06-05 14:44, 2011-03-22 14:41, 2010-10-29 08:29, 2009-03-12 15:15, 2008-01-30 11:49, 2007-06-22 11:27, 2005-09-07 12:38, 2005-06-28 11:30
Namespace
eltek
Source file
ELTEK-DISTRIBUTED-MIB
Digest
sha256:89c4fcc9833152d81d067c6a92e060fb0bd5d35379f574cafa8777e141fe82f2

Description

Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5 and compack V1.0, V1.01, V1.02, V1.03) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack2 sw V1.1, V1.2, V1.3) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6, V4.7 and compack V1.04, V1.05) ELTEK Distributed V8 branch will be 9 (SmartPack w/WebPower sw V4.9, V4.10, ComPack V1.04, V1.05, Smartpack2 V1.1, V1.2) ELTEK Distributed V9 branch will be 9 (SmartPack w/WebPower sw V4.11) ELTEK eNexus MIB branch will be 10 (SmartPack2 V2.x, SmartPack S V2.x and Compack V2.x) ELTEK Brasil office will have branch 11 ELTEK BMS-EM MIB will have branch 12 ELTEK TELMEX MIB will have branch 13

Contact

Eltek R&D. Postal: Eltek AS P.O. Box 3043 N-3003 Drammen Norway Tel: +47-32 20 32 00 Fax: +47-32 20 31 20 web: www.eltek.com

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMICounter32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

ELTEK-DISTRIBUTED-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Under this module's arcs

Where the registration tree carries on below this module.

ArcNameModule
1.3.6.1.4.1.12148.10eNexusSP2-MIB

Objects

NameOIDSyntaxAccessStatus
eltekDistributedPlantV9
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9
controlSystem
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.1
systemTime
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.1.1
systemTimeTime
OBJECT-TYPE
The system date and time. Used for event timestamps and logging
1.3.6.1.4.1.12148.9.1.1.1DisplayString (SIZE(0..255))read-onlycurrent
systemInfoRefresh
OBJECT-TYPE
This is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make sure the tables are updated.
1.3.6.1.4.1.12148.9.1.2INTEGER {pushbutton(0), refreshdata(1)}read-writecurrent
systemTrapRepeatRate
OBJECT-TYPE
This object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.
1.3.6.1.4.1.12148.9.1.3Integer32 (0..1440)read-writecurrent
systemSendOffTrap
OBJECT-TYPE
A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted.
1.3.6.1.4.1.12148.9.1.4INTEGER {off(0), on(1)}read-writecurrent
systemNumOfControlUnits
OBJECT-TYPE
The number of Control units in a distributed system.
1.3.6.1.4.1.12148.9.1.5Integer32 (0..8)read-onlycurrent
systemControlUnitIndex
OBJECT-TYPE
Index used for navigating in the table for configurable inputs.
1.3.6.1.4.1.12148.9.1.6Integer32 (0..7)accessible-for-notifycurrent
systemControlUnitTable
OBJECT-TYPE
This table contains the status of the programmable inputs. There is one row for each Control unit.
1.3.6.1.4.1.12148.9.1.7not-accessiblecurrent
systemControlUnitEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.9.1.7.1not-accessiblecurrent
inputControlUnitID
OBJECT-TYPE
The ID of which Control unit to be read.
1.3.6.1.4.1.12148.9.1.7.1.1Integer32 (1..8)read-onlycurrent
inputUserConfigurable1
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.2INTEGER {normal(0), alarm(1)}read-onlycurrent
inputUserConfigurable2
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.3INTEGER {normal(0), alarm(1)}read-onlycurrent
inputUserConfigurable3
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.4INTEGER {normal(0), alarm(1)}read-onlycurrent
inputUserConfigurable4
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.5INTEGER {normal(0), alarm(1)}read-onlycurrent
inputUserConfigurable5
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.6INTEGER {normal(0), alarm(1)}read-onlycurrent
inputUserConfigurable6
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.7INTEGER {normal(0), alarm(1)}read-onlycurrent
inputUserConfigurable7
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.8INTEGER {normal(0), alarm(1)}read-onlycurrent
inputUserConfigurable8
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.9INTEGER {normal(0), alarm(1)}read-onlycurrent
inputUserConfigurable9
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.10INTEGER {normal(0), alarm(1)}read-onlycurrent
inputUserConfigurable10
OBJECT-TYPE
Programmable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.11INTEGER {normal(0), alarm(1)}read-onlycurrent
systemLinkStatus
OBJECT-TYPE
A flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Not applicable for ComPack control unit
1.3.6.1.4.1.12148.9.1.8INTEGER {linkdown(0), linkup(1)}read-onlycurrent
systemInitiateEEPROM
OBJECT-TYPE
Pushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly.
1.3.6.1.4.1.12148.9.1.9INTEGER {pushbutton(0), start(1)}read-writedeprecated
systemLastDigInput
OBJECT-TYPE
The last Prog.Input that generated a trap. Used by Traps only.
1.3.6.1.4.1.12148.9.1.10Integer32 (1..10)accessible-for-notifycurrent
systemTrapCounter
OBJECT-TYPE
The number of times a trap has been repeated.. Only acessible for Traps.
1.3.6.1.4.1.12148.9.1.11Counter32accessible-for-notifycurrent
systemHeartBeatTrapRepeatRate
OBJECT-TYPE
The repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap.
1.3.6.1.4.1.12148.9.1.12Integer32 (0..1440)read-writecurrent
systemResetManualAlarms
OBJECT-TYPE
A pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this.
1.3.6.1.4.1.12148.9.1.13INTEGER {pushbutton(0), apply(1)}read-writecurrent
systemControlUnitInputIndex
OBJECT-TYPE
Index used for navigating in the table for configurable inputs.
1.3.6.1.4.1.12148.9.1.14Integer32 (0..7)accessible-for-notifycurrent
systemControlUnitInputTable
OBJECT-TYPE
This table contains the description of the programmable inputs. There is one row for each Control unit. Programmable input alarms will have description attached to the traps that explains the alarm. Default description is: ProgInput <Control unit ID>.x
1.3.6.1.4.1.12148.9.1.15not-accessiblecurrent
systemControlUnitInputEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.9.1.15.1not-accessiblecurrent
inputUnitID
OBJECT-TYPE
The ID of which Control unit to be read.
1.3.6.1.4.1.12148.9.1.15.1.1Integer32read-onlycurrent
inputUserConfigurableText1
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.1.
1.3.6.1.4.1.12148.9.1.15.1.2DisplayStringread-onlycurrent
inputUserConfigurableText2
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.2.
1.3.6.1.4.1.12148.9.1.15.1.3DisplayStringread-onlycurrent
inputUserConfigurableText3
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.3.
1.3.6.1.4.1.12148.9.1.15.1.4DisplayStringread-onlycurrent
inputUserConfigurableText4
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.4.
1.3.6.1.4.1.12148.9.1.15.1.5DisplayStringread-onlycurrent
inputUserConfigurableText5
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.5.
1.3.6.1.4.1.12148.9.1.15.1.6DisplayStringread-onlycurrent
inputUserConfigurableText6
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.6.
1.3.6.1.4.1.12148.9.1.15.1.7DisplayStringread-onlycurrent
inputUserConfigurableText7
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.7.
1.3.6.1.4.1.12148.9.1.15.1.8DisplayStringread-onlycurrent
inputUserConfigurableText8
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.8.
1.3.6.1.4.1.12148.9.1.15.1.9DisplayStringread-onlycurrent
inputUserConfigurableText9
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.9.
1.3.6.1.4.1.12148.9.1.15.1.10DisplayStringread-onlycurrent
inputUserConfigurableText10
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.10.
1.3.6.1.4.1.12148.9.1.15.1.11DisplayStringread-onlycurrent
systemResetCtrlSystem
OBJECT-TYPE
A pushbutton function that resets the control system. Configuration data will be kept.
1.3.6.1.4.1.12148.9.1.16INTEGER {pushbutton(0), reboot(1)}read-writedeprecated
ioUnits
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.1.17
ioUnitNumberOfUnits
OBJECT-TYPE
1.3.6.1.4.1.12148.9.1.17.1Integer32read-onlycurrent
ioUnitsIndex
OBJECT-TYPE
1.3.6.1.4.1.12148.9.1.17.2Integer32 (0..13)accessible-for-notifycurrent
ioUnitsTable
OBJECT-TYPE
1.3.6.1.4.1.12148.9.1.17.3not-accessiblecurrent
ioUnitsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.9.1.17.3.1not-accessiblecurrent
ioUnitID
OBJECT-TYPE
1.3.6.1.4.1.12148.9.1.17.3.1.1Integer32read-onlycurrent
ioUnitOutDoorTemp1
OBJECT-TYPE
The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.9.1.17.3.1.2Integer32read-onlycurrent
ioUnitOutDoorTemp2
OBJECT-TYPE
The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.9.1.17.3.1.3Integer32read-onlycurrent
ioUnitFanSpeed1
OBJECT-TYPE
The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
1.3.6.1.4.1.12148.9.1.17.3.1.4Integer32read-onlycurrent
ioUnitFanSpeedDeltaValue1
OBJECT-TYPE
The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
1.3.6.1.4.1.12148.9.1.17.3.1.5Integer32read-onlycurrent
ioUnitFanSpeed2
OBJECT-TYPE
The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
1.3.6.1.4.1.12148.9.1.17.3.1.6Integer32read-onlycurrent
ioUnitFanSpeedDeltaValue2
OBJECT-TYPE
The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
1.3.6.1.4.1.12148.9.1.17.3.1.7Integer32read-onlycurrent
ioUnitProgInputText1
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.1
1.3.6.1.4.1.12148.9.1.17.3.1.8DisplayString (SIZE(0..32))read-onlycurrent
ioUnitProgInputStatus1
OBJECT-TYPE
Programmable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.9INTEGER {normal(0), alarm(1)}read-onlycurrent
ioUnitProgInputText2
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.2
1.3.6.1.4.1.12148.9.1.17.3.1.10DisplayString (SIZE(0..32))read-onlycurrent
ioUnitProgInputStatus2
OBJECT-TYPE
Programmable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.11INTEGER {normal(0), alarm(1)}read-onlycurrent
ioUnitProgInputText3
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.3
1.3.6.1.4.1.12148.9.1.17.3.1.12DisplayString (SIZE(0..32))read-onlycurrent
ioUnitProgInputStatus3
OBJECT-TYPE
Programmable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.13INTEGER {normal(0), alarm(1)}read-onlycurrent
ioUnitProgInputText4
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.4
1.3.6.1.4.1.12148.9.1.17.3.1.14DisplayString (SIZE(0..32))read-onlycurrent
ioUnitProgInputStatus4
OBJECT-TYPE
Programmable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.15INTEGER {normal(0), alarm(1)}read-onlycurrent
ioUnitProgInputText5
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.5
1.3.6.1.4.1.12148.9.1.17.3.1.16DisplayString (SIZE(0..32))read-onlycurrent
ioUnitProgInputStatus5
OBJECT-TYPE
Programmable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.17INTEGER {normal(0), alarm(1)}read-onlycurrent
ioUnitProgInputText6
OBJECT-TYPE
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.6
1.3.6.1.4.1.12148.9.1.17.3.1.18DisplayString (SIZE(0..32))read-onlycurrent
ioUnitProgInputStatus6
OBJECT-TYPE
Programmable input status.
1.3.6.1.4.1.12148.9.1.17.3.1.19INTEGER {normal(0), alarm(1)}read-onlycurrent
ioUnitProgInputValue1
OBJECT-TYPE
The value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.20Integer32read-onlycurrent
ioUnitProgInputValue2
OBJECT-TYPE
The value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.21Integer32read-onlycurrent
ioUnitProgInputValue3
OBJECT-TYPE
The value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.22Integer32read-onlycurrent
ioUnitProgInputValue4
OBJECT-TYPE
The value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.23Integer32read-onlycurrent
ioUnitProgInputValue5
OBJECT-TYPE
The value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.24Integer32read-onlycurrent
ioUnitProgInputValue6
OBJECT-TYPE
The value read on input.
1.3.6.1.4.1.12148.9.1.17.3.1.25Integer32read-onlycurrent
systemServiceMode
OBJECT-TYPE
This is a switch function to activate (1) or deactivate (0) servicemode. Status can also be read. Servicemode prevent the system to operate relays or send traps or mail.
1.3.6.1.4.1.12148.9.1.18INTEGER {deactivate(0), activate(1)}read-writedeprecated
dcSystem
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.2
dcPlant
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.2.1
systemSiteInfo
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.2.1.3
systemSiteInfoCustomer
OBJECT-TYPE
The Customer name (as stored in the Control Unit).
1.3.6.1.4.1.12148.9.2.1.3.1DisplayString (SIZE(0..32))read-onlycurrent
systemSiteInfoLocation
OBJECT-TYPE
The system/site Location details (as stored in the Control Unit).
1.3.6.1.4.1.12148.9.2.1.3.2DisplayString (SIZE(0..32))read-onlycurrent
systemSiteInfoMessage1
OBJECT-TYPE
The system/site Info Message record #1 (as stored in the Control Unit). 31 Bytes.
1.3.6.1.4.1.12148.9.2.1.3.3DisplayString (SIZE(0..32))read-onlycurrent
systemSiteInfoMessage2
OBJECT-TYPE
The system/site Info Message record #2 (as stored in the Control Unit). 31 Bytes.
1.3.6.1.4.1.12148.9.2.1.3.4DisplayString (SIZE(0..32))read-onlycurrent
systemSiteInfoInstalledDate
OBJECT-TYPE
The system's Installed Date text string (as stored in the Control Unit) 16bytes.
1.3.6.1.4.1.12148.9.2.1.3.5DisplayString (SIZE(0..16))read-onlycurrent
systemSiteInfoControllerType
OBJECT-TYPE
The system Controller Module currently connected. 0 = AL175 1 = AL4000 (Aeon Gold) 2 = AL6000 3 = AL175OEM 4 = MCU 5 = SmartPack 6 = ComPack
1.3.6.1.4.1.12148.9.2.1.3.6INTEGER {al175(0), al4000(1), al6000(2), al175oem(3), mcu(4), smartpack(5), compack(6), smartpack2(7)}read-onlycurrent
systemSiteInfoSystemSeriaNum
OBJECT-TYPE
The serial number for the complete system.
1.3.6.1.4.1.12148.9.2.1.3.7DisplayString (SIZE(0..16))read-onlycurrent
systemSiteInfoControllerSeriaNum
OBJECT-TYPE
The serial number for Control unit 1.
1.3.6.1.4.1.12148.9.2.1.3.8DisplayString (SIZE(0..16))read-onlycurrent
systemNominalVoltage
OBJECT-TYPE
The nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60V
1.3.6.1.4.1.12148.9.2.1.4INTEGER {prs48v(0), prs24v(1), prs12v(2), prs26v(3), prs60v(4)}read-onlycurrent
systemOperationalStatus
OBJECT-TYPE
A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery test
1.3.6.1.4.1.12148.9.2.2INTEGER {floatvoltreg(0), floattempcomp(1), batteryboost(2), batterytest(3)}read-onlycurrent
battery
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.3
batteryName
OBJECT-TYPE
A descriptive name of the battery installed in the system.
1.3.6.1.4.1.12148.9.3.1DisplayString (SIZE(0..31))read-onlycurrent
batteryVoltage
OBJECT-TYPE
The measured battery voltage.
1.3.6.1.4.1.12148.9.3.2Integer32 (0..7500)read-onlycurrent
batteryCurrent
OBJECT-TYPE
The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.3.3Integer32read-onlycurrent
batteryTemp
OBJECT-TYPE
The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.9.3.4Integer32 (0..9999)read-onlycurrent
batteryBreakerStatus
OBJECT-TYPE
The state of the battery fuses/breakers can be either normal(0) or alarm(1).
1.3.6.1.4.1.12148.9.3.5INTEGER {normal(0), alarm(1)}read-onlycurrent
batteryChargeCurrentLimitCtrl
OBJECT-TYPE
Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
1.3.6.1.4.1.12148.9.3.6INTEGER {disable(0), enable(1)}read-writecurrent
batteryChargeCurrentLimitValue
OBJECT-TYPE
Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.3.7Integer32 (0..32000)read-writecurrent
batteryTempCompEnable
OBJECT-TYPE
Enable (0) or Disable (1) of Battery Temperature Compensated output regulation mode
1.3.6.1.4.1.12148.9.3.8INTEGER {disable(0), enable(1)}read-writecurrent
batteryFloatVoltConfig
OBJECT-TYPE
The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
1.3.6.1.4.1.12148.9.3.9Integer32 (4300..6000)read-writecurrent
batteryBoostVoltConfig
OBJECT-TYPE
The Voltage at which the DC System boost charges the batteries.
1.3.6.1.4.1.12148.9.3.10Integer32 (4300..6000)read-writecurrent
batteryHighMajorAlarmVoltageConfig
OBJECT-TYPE
The Major High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.9.3.11Integer32read-writecurrent
batteryHighMinorAlarmVoltageConfig
OBJECT-TYPE
The Minor High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.9.3.12Integer32read-writecurrent
batteryLowMajorAlarmVoltageConfig
OBJECT-TYPE
The Major Low Battery Voltage Alarm limit set voltage
1.3.6.1.4.1.12148.9.3.13Integer32read-writecurrent
batteryLowMinorAlarmVoltageConfig
OBJECT-TYPE
The Minor Low Battery Voltage Alarm limit set voltage
1.3.6.1.4.1.12148.9.3.14Integer32read-writecurrent
batteryStartManualTest
OBJECT-TYPE
This pushbutton will start or stop a manual battery test if the system allows it.
1.3.6.1.4.1.12148.9.3.15INTEGER {pushbutton(0), starttest(1), stoptest(2)}read-writecurrent
batteryStartManualBoost
OBJECT-TYPE
This pushbutton will start or stop a manual battery boost if the system allows it.
1.3.6.1.4.1.12148.9.3.16INTEGER {pushbutton(0), startboost(1), stopboost(2)}read-writecurrent
batteryLVD
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.3.17
batteryLVDStatus
OBJECT-TYPE
The Battery Contactor is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.3.17.1INTEGER {connected(0), disconnected(1), disabled(2)}read-onlycurrent
batteryLVDDisconnectVoltage
OBJECT-TYPE
The Battery Contactors Disconnect Voltage
1.3.6.1.4.1.12148.9.3.17.2Integer32 (0..7200)read-writecurrent
batteryLVDConnectVoltage
OBJECT-TYPE
The Battery Contactors Reconnect Voltage
1.3.6.1.4.1.12148.9.3.17.3Integer32 (0..7200)read-writecurrent
batteryBanksNumofBanks
OBJECT-TYPE
The number of Control units that is used to measure battery parameters.
1.3.6.1.4.1.12148.9.3.18Integer32 (1..8)read-onlycurrent
batteryBanks
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.3.19
batterySymmetryDeltaLimitVoltage
OBJECT-TYPE
The allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state.
1.3.6.1.4.1.12148.9.3.19.1Integer32read-writecurrent
batteryBanksIndex
OBJECT-TYPE
Index used for navigating the rows 1..8 of batteryBanksTable
1.3.6.1.4.1.12148.9.3.19.2Integer32 (0..7)accessible-for-notifycurrent
batteryBanksTable
OBJECT-TYPE
A table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments.
1.3.6.1.4.1.12148.9.3.19.3not-accessiblecurrent
batteryBanksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.9.3.19.3.1not-accessiblecurrent
batteryBankID
OBJECT-TYPE
The ID of the selected row in the table. i.e. the battery bank.
1.3.6.1.4.1.12148.9.3.19.3.1.1Integer32 (1..8)read-onlycurrent
batteryBanksSymmetry1enable
OBJECT-TYPE
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.2INTEGER {disable(0), enable(1)}read-writecurrent
batteryBanksSymmetry1status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.3INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryBanksSymmetry1deltaVoltage
OBJECT-TYPE
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
1.3.6.1.4.1.12148.9.3.19.3.1.4Integer32read-onlycurrent
batteryBanksSymmetry2enable
OBJECT-TYPE
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.5INTEGER {disable(0), enable(1)}read-writecurrent
batteryBanksSymmetry2status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.6INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryBanksSymmetry2deltaVoltage
OBJECT-TYPE
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
1.3.6.1.4.1.12148.9.3.19.3.1.7Integer32read-onlycurrent
batteryBanksSymmetry3enable
OBJECT-TYPE
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.8INTEGER {disable(0), enable(1)}read-writecurrent
batteryBanksSymmetry3status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.9INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryBanksSymmetry3deltaVoltage
OBJECT-TYPE
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
1.3.6.1.4.1.12148.9.3.19.3.1.10Integer32read-onlycurrent
batteryBanksSymmetry4enable
OBJECT-TYPE
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.11INTEGER {disable(0), enable(1)}read-writecurrent
batteryBanksSymmetry4status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.12INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryBanksSymmetry4deltaVoltage
OBJECT-TYPE
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
1.3.6.1.4.1.12148.9.3.19.3.1.13Integer32read-onlycurrent
batteryBanksSymmetry5enable
OBJECT-TYPE
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.14INTEGER {disable(0), enable(1)}read-writecurrent
batteryBanksSymmetry5status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.15INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryBanksSymmetry5deltaVoltage
OBJECT-TYPE
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
1.3.6.1.4.1.12148.9.3.19.3.1.16Integer32read-onlycurrent
batteryBanksSymmetry6enable
OBJECT-TYPE
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.17INTEGER {disable(0), enable(1)}read-writecurrent
batteryBanksSymmetry6status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.18INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryBanksSymmetry6deltaVoltage
OBJECT-TYPE
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
1.3.6.1.4.1.12148.9.3.19.3.1.19Integer32read-onlycurrent
batteryBanksSymmetry7enable
OBJECT-TYPE
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.20INTEGER {disable(0), enable(1)}read-writecurrent
batteryBanksSymmetry7status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.21INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryBanksSymmetry7deltaVoltage
OBJECT-TYPE
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
1.3.6.1.4.1.12148.9.3.19.3.1.22Integer32read-onlycurrent
batteryBanksSymmetry8enable
OBJECT-TYPE
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.23INTEGER {disable(0), enable(1)}read-writecurrent
batteryBanksSymmetry8status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.24INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryBanksSymmetry8deltaVoltage
OBJECT-TYPE
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
1.3.6.1.4.1.12148.9.3.19.3.1.25Integer32read-onlycurrent
batteryBanksNumberOfStrings
OBJECT-TYPE
Number of strings in the power system.
1.3.6.1.4.1.12148.9.3.19.4Integer32read-onlycurrent
batteryBanksExtensionIndex
OBJECT-TYPE
Index used for navigating the rows 1..14 of batteryBanksExtensionTable
1.3.6.1.4.1.12148.9.3.19.5Integer32 (0..7)accessible-for-notifycurrent
batteryBanksExtensionTable
OBJECT-TYPE
This table shows the measured value on the symmetry inputs.
1.3.6.1.4.1.12148.9.3.19.6not-accessiblecurrent
batteryBanksExtensionEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.9.3.19.6.1not-accessiblecurrent
batteryBanksExtensionID
OBJECT-TYPE
The ID of the selected row in the table. i.e. the battery bank.
1.3.6.1.4.1.12148.9.3.19.6.1.1Integer32read-onlycurrent
batteryBanksExtensionSymmetryInputValue1
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.2Integer32read-onlycurrent
batteryBanksExtensionSymmetryInputValue2
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.3Integer32read-onlycurrent
batteryBanksExtensionSymmetryInputValue3
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.4Integer32read-onlycurrent
batteryBanksExtensionSymmetryInputValue4
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.5Integer32read-onlycurrent
batteryBanksExtensionSymmetryInputValue5
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.6Integer32read-onlycurrent
batteryBanksExtensionSymmetryInputValue6
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.7Integer32read-onlycurrent
batteryBanksExtensionSymmetryInputValue7
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.8Integer32read-onlycurrent
batteryBanksExtensionSymmetryInputValue8
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.9Integer32read-onlycurrent
batteryCapacityData
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.3.20
batteryTimeToDisconnect
OBJECT-TYPE
Remaining time to low voltage battery disconnect.
1.3.6.1.4.1.12148.9.3.20.1Integer32read-onlycurrent
batteryCapacityLeft
OBJECT-TYPE
Capacity left in the battery.
1.3.6.1.4.1.12148.9.3.20.2Integer32read-onlycurrent
batteryCapacityUsed
OBJECT-TYPE
Capacity consumed.
1.3.6.1.4.1.12148.9.3.20.3Integer32read-onlycurrent
batteryCapacityTotal
OBJECT-TYPE
This is the total Capacity of the battery. This value is the installed capacity compensated with the last battery tests quality level
1.3.6.1.4.1.12148.9.3.20.4Integer32read-onlycurrent
batteryQuality
OBJECT-TYPE
This is the battery quality (%) of the latest battery test.
1.3.6.1.4.1.12148.9.3.20.5Integer32read-onlycurrent
batteryMonitorUnits
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.3.21
battmonNumberOfUnits
OBJECT-TYPE
Number of battery monitor units in the power system.
1.3.6.1.4.1.12148.9.3.21.1Integer32read-onlycurrent
battmonUnitsIndex
OBJECT-TYPE
Index used for navigating the rows 1..14 of battmonUnitsTable
1.3.6.1.4.1.12148.9.3.21.2Integer32accessible-for-notifycurrent
battmonUnitsTable
OBJECT-TYPE
A table of up to 14 battery monitor control units.
1.3.6.1.4.1.12148.9.3.21.3not-accessiblecurrent
battmonUnitsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.9.3.21.3.1not-accessiblecurrent
batteryMonitorID
OBJECT-TYPE
The ID of the selected row
1.3.6.1.4.1.12148.9.3.21.3.1.1Integer32 (1..14)read-onlycurrent
batteryMonitorSymmetry1status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.2INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryMonitorSymmetry1InputValue
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.3Integer32read-onlycurrent
batteryMonitorSymmetry2status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.4INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryMonitorSymmetry2InputValue
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.5Integer32read-onlycurrent
batteryMonitorSymmetry3status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.6INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryMonitorSymmetry3InputValue
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.7Integer32read-onlycurrent
batteryMonitorSymmetry4status
OBJECT-TYPE
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.8INTEGER {ok(0), minorAlarm(1), majorAlarm(2), disabled(3), error(4)}read-onlycurrent
batteryMonitorSymmetry4InputValue
OBJECT-TYPE
The measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.9Integer32read-onlycurrent
batteryMonitorCurrentValue
OBJECT-TYPE
The measured current to/from the battery. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.3.21.3.1.10Integer32read-onlycurrent
batteryMonitorFuseStatus
OBJECT-TYPE
The state of the battery fuse/breaker can be either normal(0) or alarm(1).
1.3.6.1.4.1.12148.9.3.21.3.1.11INTEGER {normal(0), alarm(1)}read-onlycurrent
batteryMonitorTemperature
OBJECT-TYPE
The battery temperature.
1.3.6.1.4.1.12148.9.3.21.3.1.12Integer32read-onlycurrent
batteryHighMajorTempAlarmLevel
OBJECT-TYPE
This is the Major High Temperature Alarm level.
1.3.6.1.4.1.12148.9.3.22Integer32read-writecurrent
batteryHighMinorTempAlarmLevel
OBJECT-TYPE
This is the Minor High Temperature Alarm level.
1.3.6.1.4.1.12148.9.3.23Integer32read-writecurrent
batteryTest
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.3.24
batteryTestEndVoltage
OBJECT-TYPE
The end voltage for standard battery test (V/cell) 1/100 Volt; i.e. 190 = 1.90V
1.3.6.1.4.1.12148.9.3.24.1Integer32read-writecurrent
batteryTestMaximumDischargeTime
OBJECT-TYPE
The maximum allowed run time for the battery test (Minutes)
1.3.6.1.4.1.12148.9.3.24.2Integer32read-writecurrent
batteryTestMaximumDischargeAh
OBJECT-TYPE
The maximum allowed discharge for the batteries during a battery test (Ah)
1.3.6.1.4.1.12148.9.3.24.3Integer32read-writecurrent
loadDistribution
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.4
loadDistributionCurrent
OBJECT-TYPE
The total load current Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.1Integer32read-onlycurrent
loadDistributionBreakerStatus
OBJECT-TYPE
The state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.2INTEGER {normal(0), alarm(1)}read-onlycurrent
loadDistributionLVDStatus
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.4.3
loadLVD1Enable
OBJECT-TYPE
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.9.4.3.1INTEGER {disabled(0), enabled(1)}read-onlycurrent
loadLVD1Status
OBJECT-TYPE
The load Contactor 1 is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.4.3.2INTEGER {connected(0), disconnected(1), disabled(2)}read-onlycurrent
loadLVD1ConnectVoltage
OBJECT-TYPE
LVLD1 Connect Voltage
1.3.6.1.4.1.12148.9.4.3.3Integer32 (0..7200)read-writecurrent
loadLVD1DisconnectVoltage
OBJECT-TYPE
LVLD1 Disconnect Voltage
1.3.6.1.4.1.12148.9.4.3.4Integer32 (0..7200)read-writecurrent
loadLVD2Enable
OBJECT-TYPE
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.9.4.3.5INTEGER {disabled(0), enabled(1)}read-onlycurrent
loadLVD2Status
OBJECT-TYPE
The load Contactor 2 is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.4.3.6INTEGER {connected(0), disconnected(1), disabled(2)}read-onlycurrent
loadLVD2ConnectVoltage
OBJECT-TYPE
LVLD2 Connect Voltage
1.3.6.1.4.1.12148.9.4.3.7Integer32 (0..7200)read-writecurrent
loadLVD2DisconnectVoltage
OBJECT-TYPE
LVLD2 Disconnect Voltage
1.3.6.1.4.1.12148.9.4.3.8Integer32 (0..7200)read-writecurrent
loadLVD3Enable
OBJECT-TYPE
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.9.4.3.9INTEGER {disabled(0), enabled(1)}read-onlycurrent
loadLVD3Status
OBJECT-TYPE
The load Contactor 3 is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.4.3.10INTEGER {connected(0), disconnected(1), disabled(2)}read-onlycurrent
loadLVD3ConnectVoltage
OBJECT-TYPE
LVLD3 Connect Voltage
1.3.6.1.4.1.12148.9.4.3.11Integer32 (0..7200)read-writecurrent
loadLVD3DisconnectVoltage
OBJECT-TYPE
LVLD3 Disconnect Voltage
1.3.6.1.4.1.12148.9.4.3.12Integer32 (0..7200)read-writecurrent
loadMonitorUnits
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.4.4
loadmonitorNumberOfUnits
OBJECT-TYPE
1.3.6.1.4.1.12148.9.4.4.1Integer32read-onlycurrent
loadMonitorUnitsIndex
OBJECT-TYPE
1.3.6.1.4.1.12148.9.4.4.2Integer32 (0..13)accessible-for-notifycurrent
loadMonitorUnitsTable
OBJECT-TYPE
1.3.6.1.4.1.12148.9.4.4.3not-accessiblecurrent
loadMonitorUnitsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.9.4.4.3.1not-accessiblecurrent
loadMonitorID
OBJECT-TYPE
1.3.6.1.4.1.12148.9.4.4.3.1.1Integer32read-onlycurrent
loadMonitorFuseStatus1
OBJECT-TYPE
The state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.2INTEGER {normal(0), alarm(1)}read-onlycurrent
loadMonitorCurrent1
OBJECT-TYPE
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.3Integer32read-onlycurrent
loadMonitorFuseStatus2
OBJECT-TYPE
The state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.4INTEGER {normal(0), alarm(1)}read-onlycurrent
loadMonitorCurrent2
OBJECT-TYPE
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.5Integer32read-onlycurrent
loadMonitorFuseStatus3
OBJECT-TYPE
The state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.6INTEGER {normal(0), alarm(1)}read-onlycurrent
loadMonitorCurrent3
OBJECT-TYPE
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.7Integer32read-onlycurrent
loadMonitorFuseStatus4
OBJECT-TYPE
The state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.8INTEGER {normal(0), alarm(1)}read-onlycurrent
loadMonitorCurrent4
OBJECT-TYPE
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.9Integer32read-onlycurrent
loadMonitorFuseStatus5
OBJECT-TYPE
The state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.10INTEGER {normal(0), alarm(1)}read-onlycurrent
loadMonitorCurrent5
OBJECT-TYPE
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.11Integer32read-onlycurrent
loadMonitorFuseStatus6
OBJECT-TYPE
The state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.12INTEGER {normal(0), alarm(1)}read-onlycurrent
loadMonitorCurrent6
OBJECT-TYPE
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.13Integer32read-onlycurrent
loadMonitorFuseStatus7
OBJECT-TYPE
The state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.14INTEGER {normal(0), alarm(1)}read-onlycurrent
loadMonitorCurrent7
OBJECT-TYPE
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.15Integer32read-onlycurrent
loadMonitorFuseStatus8
OBJECT-TYPE
The state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.4.3.1.16INTEGER {normal(0), alarm(1)}read-onlycurrent
loadMonitorCurrent8
OBJECT-TYPE
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.9.4.4.3.1.17Integer32read-onlycurrent
rectifier
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.5
rectifierInstalledRectifiers
OBJECT-TYPE
The number of installed rectifiers for this DC Power System.
1.3.6.1.4.1.12148.9.5.1Integer32 (1..101)read-onlycurrent
rectifierRectifiersActive
OBJECT-TYPE
Not Used!
1.3.6.1.4.1.12148.9.5.2Integer32 (1..101)read-onlycurrent
rectifierTotalCurrent
OBJECT-TYPE
The DC system's total delivered rectifier current
1.3.6.1.4.1.12148.9.5.3Integer32read-onlycurrent
rectifierUtilization
OBJECT-TYPE
Utilization in % of available rectifier capacity
1.3.6.1.4.1.12148.9.5.4Integer32 (0..100)read-onlycurrent
rectifierStatus
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.5.5
rectifierStatusNoIndex
OBJECT-TYPE
An offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first row i.e. setting the index to 11 will give a range from rectifier ID12 to ID31. Setting the index to 0 will give a range from rectifier ID1 to ID20.
1.3.6.1.4.1.12148.9.5.5.1Integer32 (0..95)read-writecurrent
rectifierStatusTable
OBJECT-TYPE
A table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex
1.3.6.1.4.1.12148.9.5.5.2not-accessiblecurrent
rectifierStatusEntry
OBJECT-TYPE
A row of rectifier status data corresponding to the rectifierStatusNoIndex value
1.3.6.1.4.1.12148.9.5.5.2.1not-accessiblecurrent
rectifierStatusID
OBJECT-TYPE
The rectifier ID number of the rectifier.
1.3.6.1.4.1.12148.9.5.5.2.1.1Integer32 (1..100)read-onlycurrent
rectifierStatusStatus
OBJECT-TYPE
The operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)
1.3.6.1.4.1.12148.9.5.5.2.1.2INTEGER {notPresent(0), normal(1), alarm(2), notUsed(3), disabled(4)}read-onlycurrent
rectifierStatusOutputCurrent
OBJECT-TYPE
The output current of the rectifier.
1.3.6.1.4.1.12148.9.5.5.2.1.3Integer32 (0..65535)read-onlycurrent
rectifierStatusOutputVoltage
OBJECT-TYPE
The rectifier voltage of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.4Integer32 (0..65535)read-onlycurrent
rectifierStatusTemp
OBJECT-TYPE
The input air temperature of the rectifier.
1.3.6.1.4.1.12148.9.5.5.2.1.5Integer32 (0..65535)read-onlycurrent
rectifierStatusType
OBJECT-TYPE
The rectifier article number string of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.6DisplayString (SIZE(0..32))read-onlycurrent
rectifierStatusSKU
OBJECT-TYPE
The rectifier part number.
1.3.6.1.4.1.12148.9.5.5.2.1.7DisplayString (SIZE(1..32))read-onlycurrent
rectifierStatusSerialNo
OBJECT-TYPE
The rectifier serial number string of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.8DisplayString (SIZE(0..16))read-onlycurrent
rectifierStatusRevisionLevel
OBJECT-TYPE
The rectifier HW revision number string of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.9DisplayString (SIZE(0..16))read-onlycurrent
acDistribution
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.6
acVoltage1
OBJECT-TYPE
The AC Voltage of phase 1
1.3.6.1.4.1.12148.9.6.1Integer32read-onlycurrent
acVoltage2
OBJECT-TYPE
The AC Voltage of phase 2
1.3.6.1.4.1.12148.9.6.2Integer32read-onlycurrent
acVoltage3
OBJECT-TYPE
The AC Voltage of phase 3
1.3.6.1.4.1.12148.9.6.3Integer32read-onlycurrent
alarmGroup
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.7
alarmWellknownAlarms
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.7.1
alarmMajorHighBattVolt
OBJECT-TYPE
The Major High Battery Voltage Alarm
1.3.6.1.4.1.12148.9.7.1.1INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMinorHighBattVolt
OBJECT-TYPE
The Minor High Battery Voltage alarm
1.3.6.1.4.1.12148.9.7.1.2INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMajorLowBattVolt
OBJECT-TYPE
The Major Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.7.1.3INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMinorLowBattVolt
OBJECT-TYPE
The Minor Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.7.1.4INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMajorBatteryHighTemp
OBJECT-TYPE
The Major High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.7.1.5INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMinorBatteryHighTemp
OBJECT-TYPE
The Minor High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.7.1.6INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmBatteryDisconnectOpen
OBJECT-TYPE
The Battery Disconnect Contactor alarm
1.3.6.1.4.1.12148.9.7.1.7INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmLVD1open
OBJECT-TYPE
The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.7.1.8INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmLVD2open
OBJECT-TYPE
The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.7.1.9INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmLVD3open
OBJECT-TYPE
The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.7.1.10INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmACmains
OBJECT-TYPE
The AC voltage has dropped below critical level, or one or more AC input phases was lost.
1.3.6.1.4.1.12148.9.7.1.11INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmBatteryBreakerOpen
OBJECT-TYPE
A battery breaker/fuse alarm.
1.3.6.1.4.1.12148.9.7.1.12INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmDistributionBreakerOpen
OBJECT-TYPE
A Load Distribution breaker/fuse alarm.
1.3.6.1.4.1.12148.9.7.1.13INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMajorRectifier
OBJECT-TYPE
This is a Major Rectifier alarm.
1.3.6.1.4.1.12148.9.7.1.14INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMinorRectifier
OBJECT-TYPE
This is a Minor Rectifier alarm.
1.3.6.1.4.1.12148.9.7.1.15INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMajorBatterySymmetry
OBJECT-TYPE
Battery Symmetry Delta Voltage Major alarm.
1.3.6.1.4.1.12148.9.7.1.16INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMinorBatterySymmetry
OBJECT-TYPE
Battery Symmetry Delta Voltage Minor alarm
1.3.6.1.4.1.12148.9.7.1.17INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmBatteryLifeEnded
OBJECT-TYPE
The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
1.3.6.1.4.1.12148.9.7.1.18INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmBatteryTestmodeEntered
OBJECT-TYPE
The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
1.3.6.1.4.1.12148.9.7.1.19INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmBatteryBoostmodeEntered
OBJECT-TYPE
The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging.
1.3.6.1.4.1.12148.9.7.1.20INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmIoUnitTemp1
OBJECT-TYPE
High or low temperature alarm 1 from any of the IO units.
1.3.6.1.4.1.12148.9.7.1.21INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmIoUnitTemp2
OBJECT-TYPE
High or low temperature alarm 2 from any of the IO units.
1.3.6.1.4.1.12148.9.7.1.22INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmIoUnitDeltaFanSpeed1
OBJECT-TYPE
Delta fan speed 1 from any of the IO units.
1.3.6.1.4.1.12148.9.7.1.23INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmIoUnitDeltaFanSpeed2
OBJECT-TYPE
Delta fan speed 2 from any of the IO units.
1.3.6.1.4.1.12148.9.7.1.24INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMajorSolar
OBJECT-TYPE
This is a Major Solar alarm.
1.3.6.1.4.1.12148.9.7.1.25INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMinorSolar
OBJECT-TYPE
This is a Major Solar alarm.
1.3.6.1.4.1.12148.9.7.1.26INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMajorRectifierCapacity
OBJECT-TYPE
This is a Major Rectifier Capacity alarm.
1.3.6.1.4.1.12148.9.7.1.27INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmMinorRectifierCapacity
OBJECT-TYPE
This is a Minor Rectifier Capacity alarm.
1.3.6.1.4.1.12148.9.7.1.28INTEGER {normal(0), alarm(1)}read-onlycurrent
solarCharger
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.9
solarChargerInstalledsolarChargers
OBJECT-TYPE
The number of installed solar chargers for this DC Power System.
1.3.6.1.4.1.12148.9.9.1Integer32 (1..101)read-onlycurrent
solarChargersActive
OBJECT-TYPE
Not Used!
1.3.6.1.4.1.12148.9.9.2Integer32 (1..101)read-onlycurrent
solarChargerTotalCurrent
OBJECT-TYPE
The DC system's total delivered solar current
1.3.6.1.4.1.12148.9.9.3Integer32read-onlycurrent
solarChargerUtilization
OBJECT-TYPE
Utilization in % of available solar capacity
1.3.6.1.4.1.12148.9.9.4Integer32 (0..100)read-onlycurrent
solarChargerStatus
OBJECT-IDENTITY
1.3.6.1.4.1.12148.9.9.5
solarChargerStatusNoIndex
OBJECT-TYPE
An offset for the solarStatusTable array. The solar status table has a fixed number of 20 rows. This OID sets the offset for the solarcharger in the first row i.e. setting the index to 11 will give a range from solarcharger ID12 to ID31. Setting the index to 0 will give a range from solarcharger ID1 to ID20.
1.3.6.1.4.1.12148.9.9.5.1Integer32 (0..95)read-writecurrent
solarChargerStatusTable
OBJECT-TYPE
A table listing up to 20 solarchargers, starting from the solarcharger number specified by solarStatusNoIndex
1.3.6.1.4.1.12148.9.9.5.2not-accessiblecurrent
solarChargerStatusEntry
OBJECT-TYPE
A row of rectifier status data corresponding to the rectifierStatusNoIndex value
1.3.6.1.4.1.12148.9.9.5.2.1not-accessiblecurrent
solarChargerStatusID
OBJECT-TYPE
The ID number of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.1Integer32 (1..100)read-onlycurrent
solarChargerStatusStatus
OBJECT-TYPE
The operational status of the solarcharger record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)
1.3.6.1.4.1.12148.9.9.5.2.1.2INTEGER {notPresent(0), normal(1), alarm(2), notUsed(3), disabled(4)}read-onlycurrent
solarChargerOutputCurrent
OBJECT-TYPE
The output current of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.3Integer32 (0..65535)read-onlycurrent
solarChargerOutputVoltage
OBJECT-TYPE
The output voltage of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.4Integer32 (0..65535)read-onlycurrent
solarChargerTemp
OBJECT-TYPE
The input air temperature of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.5Integer32 (0..65535)read-onlycurrent
solarChargerType
OBJECT-TYPE
The article number string of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.6DisplayString (SIZE(0..32))read-onlycurrent
solarChargerSKU
OBJECT-TYPE
The solarcharger part number.
1.3.6.1.4.1.12148.9.9.5.2.1.7DisplayString (SIZE(1..32))read-onlycurrent
solarChargerSerialNo
OBJECT-TYPE
The serial number string of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.8DisplayString (SIZE(0..16))read-onlycurrent
solarChargerRevisionLevel
OBJECT-TYPE
The HW revision number string of the solarcharger.
1.3.6.1.4.1.12148.9.9.5.2.1.9DisplayString (SIZE(0..16))read-onlycurrent

Notifications

NameOIDStatus
alarmMajorHighBattVoltTrap
NOTIFICATION-TYPE
The Major High Battery Voltage alarm
1.3.6.1.4.1.12148.9.8.1current
alarmMinorHighBattVoltTrap
NOTIFICATION-TYPE
The Minor High Battery Voltage alarm
1.3.6.1.4.1.12148.9.8.2current
alarmMajorLowBattVoltTrap
NOTIFICATION-TYPE
The Major Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.8.3current
alarmMinorLowBattVoltTrap
NOTIFICATION-TYPE
The Minor Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.8.4current
alarmMajorBatteryHighTempTrap
NOTIFICATION-TYPE
The Major High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.8.5current
alarmMinorBatteryHighTempTrap
NOTIFICATION-TYPE
The Minor High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.8.6current
alarmBatteryDisconnectOpenTrap
NOTIFICATION-TYPE
The Battery Disconnect Contactor alarm
1.3.6.1.4.1.12148.9.8.7current
alarmLVD1openTrap
NOTIFICATION-TYPE
The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.8.8current
alarmLVD2openTrap
NOTIFICATION-TYPE
The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.8.9current
alarmLVD3openTrap
NOTIFICATION-TYPE
The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.8.10current
alarmACmainsTrap
NOTIFICATION-TYPE
The AC voltage has dropped below critical level, or one or more AC input phases was lost.
1.3.6.1.4.1.12148.9.8.11current
alarmBatteryBreakerOpenTrap
NOTIFICATION-TYPE
A battery breaker/fuse alarm.
1.3.6.1.4.1.12148.9.8.12current
alarmDistributionBreakerOpenTrap
NOTIFICATION-TYPE
A Load Distribution breaker/fuse alarm.
1.3.6.1.4.1.12148.9.8.13current
alarmMajorRectifierTrap
NOTIFICATION-TYPE
This is a Major Rectifier alarm.
1.3.6.1.4.1.12148.9.8.14current
alarmMinorRectifierTrap
NOTIFICATION-TYPE
This is a Minor Rectifier alarm.
1.3.6.1.4.1.12148.9.8.15current
alarmMajorBatterySymmetryTrap
NOTIFICATION-TYPE
Battery Symmetry Delta Voltage Major alarm
1.3.6.1.4.1.12148.9.8.16current
alarmMinorBatterySymmetryTrap
NOTIFICATION-TYPE
Battery Symmetry Delta Voltage Minor alarm
1.3.6.1.4.1.12148.9.8.17current
alarmBatteryLifeEndedTrap
NOTIFICATION-TYPE
The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
1.3.6.1.4.1.12148.9.8.18current
alarmBatteryTestmodeEnteredTrap
NOTIFICATION-TYPE
The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
1.3.6.1.4.1.12148.9.8.19current
alarmBatteryBoostmodeEnteredTrap
NOTIFICATION-TYPE
The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging.
1.3.6.1.4.1.12148.9.8.20current
alarmController1proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for Control unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
1.3.6.1.4.1.12148.9.8.21current
alarmController2proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for Control unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
1.3.6.1.4.1.12148.9.8.22current
alarmController3proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for Control unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
1.3.6.1.4.1.12148.9.8.23current
alarmController4proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for Control unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
1.3.6.1.4.1.12148.9.8.24current
alarmController5proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for Control unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
1.3.6.1.4.1.12148.9.8.25current
alarmController6proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for Control unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
1.3.6.1.4.1.12148.9.8.26current
alarmController7proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for Control unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
1.3.6.1.4.1.12148.9.8.27current
alarmController8proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for Control unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
1.3.6.1.4.1.12148.9.8.28current
infoHeartBeatTrap
NOTIFICATION-TYPE
When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up.
1.3.6.1.4.1.12148.9.8.29current
alarmIoUnitTemp1Trap
NOTIFICATION-TYPE
High or low temperature alarm 1 from any of the IO units.
1.3.6.1.4.1.12148.9.8.30current
alarmIoUnitTemp2Trap
NOTIFICATION-TYPE
High or low temperature alarm 2 from any of the IO units.
1.3.6.1.4.1.12148.9.8.31current
alarmIoUnitDeltaFanSpeed1Trap
NOTIFICATION-TYPE
Delta fan speed 1 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
1.3.6.1.4.1.12148.9.8.32current
alarmIoUnitDeltaFanSpeed2Trap
NOTIFICATION-TYPE
Delta fan speed 2 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
1.3.6.1.4.1.12148.9.8.33current
alarmIoUnit1proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.34current
alarmIoUnit2proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.35current
alarmIoUnit3proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.36current
alarmIoUnit4proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.37current
alarmIoUnit5proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.38current
alarmIoUnit6proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.39current
alarmIoUnit7proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.40current
alarmIoUnit8proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.41current
alarmIoUnit9proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 9. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.42current
alarmIoUnit10proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 10. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.43current
alarmIoUnit11proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 11. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.44current
alarmIoUnit12proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 12. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.45current
alarmIoUnit13proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 13. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.46current
alarmIoUnit14proginputTrap
NOTIFICATION-TYPE
Programmable input alarm for IO Unit 14. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
1.3.6.1.4.1.12148.9.8.47current
alarmMajorSolarChargerTrap
NOTIFICATION-TYPE
The Major Solar Charger alarm
1.3.6.1.4.1.12148.9.8.48current
alarmMinorSolarChargerTrap
NOTIFICATION-TYPE
The Minor Solar Charger alarm
1.3.6.1.4.1.12148.9.8.49current
alarmMajorRectifierCapacityTrap
NOTIFICATION-TYPE
The Major Rectifier Capacity alarm
1.3.6.1.4.1.12148.9.8.50current
alarmMinorRectifierCapacityTrap
NOTIFICATION-TYPE
The Minor Rectifier Capacity alarm
1.3.6.1.4.1.12148.9.8.51current

Conformance

NameOIDStatus
dcSystemTraps
NOTIFICATION-GROUP
This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap
1.3.6.1.4.1.12148.9.8current