SP2-MIB

Registered at
1.3.6.1.4.1.12148.10
Namespace
eltek
Source file
SP2-MIB
Digest
sha256:37557bca8c87c1cdcf1cb669c05d87fc1570ee25281aa44884bdb4dd78fa6f9a

Imports

FromSymbols
ELTEK-COMMON-MIBeltek
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMICounter32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDateAndTime, DisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

ELTEK-COMMON-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC
SP2-MIB

Objects

NameOIDSyntaxAccessStatus
eNexus
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10
eltekTraps
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.1
powerAlarmVars
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.1.1
alarmSubsysSourceDescr
OBJECT-TYPE
A description of the source generating the trap for the Alarm Condition. Used in alarmSubSystemTrap to describe the alarm source. Example: 'batteryVoltageDescription'
1.3.6.1.4.1.12148.10.1.1.1DisplayString (SIZE(0..32))accessible-for-notifycurrent
alarmSubsysStatusOid
OBJECT-TYPE
The OID (name) of the object indicating the alarm-status for which the alarm is generated. The Status must be an INTEGER type. Example: SP2-MIB::batteryVoltage.batteryVoltageStatus 1.3.6.1.4.1.12148.10.3.5.2: This object maybe polled by the SNMP management application, to monitor the current Status object.
1.3.6.1.4.1.12148.10.1.1.2OBJECT IDENTIFIERaccessible-for-notifycurrent
alarmSubsysStatusValue
OBJECT-TYPE
The value of the Status object of the subsystem for which the alarm-status is generated. The OID (name) of this object is indicated by alarmSubsysStatusOid above. Example: the value of SP2-MIB::batteryVoltage.batteryVoltageStatus one of: error (0), normal (1), minorAlarm (2), etc.
1.3.6.1.4.1.12148.10.1.1.3INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}accessible-for-notifycurrent
alarmSubsysStatusOnOff
OBJECT-TYPE
This indicates if the abnormal condition is on or goes off.
1.3.6.1.4.1.12148.10.1.1.4INTEGER {off(0), on(1)}accessible-for-notifycurrent
alarmMeasuredVarOid
OBJECT-TYPE
The OID (name) of the measured-object indicating some measurement (e.g voltage) for which the alarm is generated. Example: SP2-MIB::batteryVoltage.batteryVoltageValue 1.3.6.1.4.1.12148.10.3.5.1 This object maybe polled by the SNMP management application, to monitor the current measurement.
1.3.6.1.4.1.12148.10.1.1.5OBJECT IDENTIFIERaccessible-for-notifycurrent
alarmMeasuredVarValue
OBJECT-TYPE
The value of the measured-object for which the alarm-status is generated, for example 13 volt. The actual value is in units defined by the actual variable (e.g volts). The units must use INTEGER type. The OID (name) of this object is indicated by alarmMeasuredVarOid above. Example: Value of SP2-MIB::batteryVoltage.batteryVoltageValue 'The measured battery voltage'
1.3.6.1.4.1.12148.10.1.1.6Integer32accessible-for-notifycurrent
alarmTrapCounterVarValue
OBJECT-TYPE
1.3.6.1.4.1.12148.10.1.1.7Integer32accessible-for-notifycurrent
powerSystemTraps
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.1.2
powerSystem
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.2
powerSystemStatus
OBJECT-TYPE
A status value showing the overall condition of the power system.
1.3.6.1.4.1.12148.10.2.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
powerSystemType
OBJECT-TYPE
A value showing the type of the power system, which is named after the main controller.
1.3.6.1.4.1.12148.10.2.2INTEGER {smartpack2(1), smartpackS(2), compack(3)}read-onlycurrent
powerSystemMode
OBJECT-TYPE
A summary status showing if the system is in test, boost, float, equalize, emergency or start-up delay mode
1.3.6.1.4.1.12148.10.2.3INTEGER {off(0), test(1), boost(2), float(3), emergency(4), startupdelay(5), equalize(6)}read-onlycurrent
powerSystemCompany
OBJECT-TYPE
The Copmany name (as stored in the Control Unit).
1.3.6.1.4.1.12148.10.2.4DisplayString (SIZE(0..32))read-writecurrent
powerSystemSite
OBJECT-TYPE
The system/site Location details (as stored in the Control Unit).
1.3.6.1.4.1.12148.10.2.5DisplayString (SIZE(0..32))read-writecurrent
powerSystemModel
OBJECT-TYPE
The model/part number of the power system (as stored in the Control Unit).
1.3.6.1.4.1.12148.10.2.6DisplayString (SIZE(0..32))read-onlycurrent
powerSystemSerialNumber
OBJECT-TYPE
The serial number for the complete system.
1.3.6.1.4.1.12148.10.2.7DisplayString (SIZE(0..16))read-writecurrent
powerSystemInstallDate
OBJECT-TYPE
The system's Installation date (as stored in the Control Unit).
1.3.6.1.4.1.12148.10.2.8DateAndTimeread-writecurrent
powerSystemNominalVoltage
OBJECT-TYPE
The nominal voltage rating. 12V/24V/48V/60V/110V/220V/380V etc. systems.
1.3.6.1.4.1.12148.10.2.9Integer32read-onlycurrent
powerSystemLongitude
OBJECT-TYPE
A part of the systems global positioning data. The range +-180degrees Longitude lines are imaginary lines running from the north pole to the south pole. Longitudes are usually (WGS84) referenced from Greenwich, England where it has been established as Zero Degrees longitude. Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this.
1.3.6.1.4.1.12148.10.2.10Integer32 (-180..180)read-writecurrent
powerSystemLongitudeDecimal
OBJECT-TYPE
The decimal part of dcSystemLatitude contains up to 7digits. This number is in 1/1000000 degree fractions or 0,0000001 degree. A part of the systems global positioning data. Longitude lines are imaginary lines running from the north pole to the south pole. Longitudes are usually (WGS84) referenced from Greenwich, England where it has been established as Zero Degrees longitude. Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this.
1.3.6.1.4.1.12148.10.2.11Integer32read-writecurrent
powerSystemLatitude
OBJECT-TYPE
A part of the systems global positioning data. The latitude gives the location of a place on Earth (or other planetary body) north or south of the equator. Lines of Latitude has a range of +-90 degrees and are the imaginary horizontal lines shown running east-to-west (or west to east). Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this.
1.3.6.1.4.1.12148.10.2.12Integer32 (-90..90)read-writecurrent
powerSystemLatitudeDecimal
OBJECT-TYPE
The decimal part of dcSystemLatitude contains up to 7digits. This number is in 1/1000000 degree fractions or 0,0000001 degree. A part of the systems global positioning data. Lines of Latitude has a range of +-90 degrees and are the imaginary horizontal lines shown running east-to-west (or west to east). Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this. Longitude lines are imaginary lines running from the north pole to the south pole. Longitudes are usually (WGS84) referenced from Greenwich, England where it has been established as Zero Degrees longitude. Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this.
1.3.6.1.4.1.12148.10.2.13Integer32read-writecurrent
powerSystemElevation
OBJECT-TYPE
A part of the systems global positioning data. This is the sites height above sealevel in Meters. The Elevation together with Latituse and Longitude is used for automagically placing system icons on NMS/Sitemonitors system that support this.
1.3.6.1.4.1.12148.10.2.14Integer32read-writecurrent
powerSystemCurrentDecimalSetting
OBJECT-TYPE
A global flag telling if the current values in the system is Amperes or DeciAmpres
1.3.6.1.4.1.12148.10.2.15INTEGER {ampere(0), deciAmpere(1)}read-writecurrent
powerSystemTemperatureScale
OBJECT-TYPE
A flag telling if the temperatures values in the system is of Celcius or Fahrenheit type
1.3.6.1.4.1.12148.10.2.16INTEGER {celcius(0), fahrenheit(1)}read-writecurrent
powerSystemCapacityScale
OBJECT-TYPE
A flag telling if the system's battery capacity value is a percentage of a fully charged battery, or in AmpereHours
1.3.6.1.4.1.12148.10.2.17INTEGER {ah(0), percent(1)}read-writecurrent
mains
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.3
mainsStatus
OBJECT-TYPE
The overall status of mains/AC feed subsystem.
1.3.6.1.4.1.12148.10.3.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsMainsFailure
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.3.2
mainsMainsFailureStatus
OBJECT-TYPE
This status value shows if the number of failed phases is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.3.2.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsMainsFailureDescription
OBJECT-TYPE
A textual description of the mains phase failure monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.2.2DisplayString (SIZE(0..16))read-writecurrent
mainsMainsFailureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.3.2.3Integer32accessible-for-notifycurrent
mainsMainsFailureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.2.4INTEGER {disabled(0), enabled(1)}read-writecurrent
mainsMainsFailureValue
OBJECT-TYPE
The detected number of failed phases.
1.3.6.1.4.1.12148.10.3.2.5Integer32read-onlycurrent
mainsMainsFailureMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.3.2.6Integer32read-writecurrent
mainsMainsFailureMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.3.2.7Integer32read-writecurrent
mainsNumberOfPhases
OBJECT-TYPE
This value showing the number of phases of the mains subsystem.
1.3.6.1.4.1.12148.10.3.3Integer32read-writecurrent
mainsVoltageTable
OBJECT-TYPE
This table contains information about mains voltage monitor
1.3.6.1.4.1.12148.10.3.4not-accessiblecurrent
mainsVoltageEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.4.1not-accessiblecurrent
mainsVoltageIndex
OBJECT-TYPE
Index used for navigating the rows 1..12 of mainsVoltageTable
1.3.6.1.4.1.12148.10.3.4.1.1Integer32 (1..12)not-accessiblecurrent
mainsVoltageStatus
OBJECT-TYPE
The status of the measured mains voltage.
1.3.6.1.4.1.12148.10.3.4.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsVoltageDescription
OBJECT-TYPE
A textual description of the mains voltage monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.4.1.3DisplayString (SIZE(0..16))read-writecurrent
mainsVoltageTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.3.4.1.4Counter32accessible-for-notifycurrent
mainsVoltageAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.4.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
mainsVoltageValue
OBJECT-TYPE
The value of the measured mains voltage.
1.3.6.1.4.1.12148.10.3.4.1.6Integer32read-onlycurrent
mainsVoltageMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.3.4.1.7Integer32read-writecurrent
mainsVoltageMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.3.4.1.8Integer32read-writecurrent
mainsVoltageMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.3.4.1.9Integer32read-writecurrent
mainsVoltageMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.3.4.1.10Integer32read-writecurrent
mainsMonitors
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.3.5
mainsMonitorsNumberOfUnits
OBJECT-TYPE
This is the number of AC Mains Monitor CAN Nodes installed in the system.
1.3.6.1.4.1.12148.10.3.5.1Integer32 (0..14)read-writecurrent
mainsMonitorsTable
OBJECT-TYPE
This table contains the number of voltage, current and frequency measurements in each AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.2not-accessiblecurrent
mainsMonitorsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.5.2.1not-accessiblecurrent
mainsMonitorIndex
OBJECT-TYPE
Index used for navigating the rows of mainsMonitorsTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.3.5.2.1.1Integer32 (1..14)not-accessiblecurrent
mainsMonitorNumberOfVoltages
OBJECT-TYPE
The number of voltage measurements in the AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.2.1.2Integer32 (0..3)read-onlycurrent
mainsMonitorNumberOfCurrents
OBJECT-TYPE
The number of current measurements in the AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.2.1.3Integer32 (0..3)read-onlycurrent
mainsMonitorNumberOfFrequencies
OBJECT-TYPE
The number of frequency measurements in the AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.2.1.4Integer32 (0..3)read-onlycurrent
mainsMonitorVoltageTable
OBJECT-TYPE
This table contains information about mains voltage in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.3not-accessiblecurrent
mainsMonitorVoltageEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.5.3.1not-accessiblecurrent
mainsMonitorPhaseIndex
OBJECT-TYPE
Index used for navigating the rows 1..3 of mainsMonitorVolatgeTable
1.3.6.1.4.1.12148.10.3.5.3.1.1Integer32 (1..3)not-accessiblecurrent
mainsMonitorVoltageStatus
OBJECT-TYPE
The status of the measured mains voltage in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.3.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsMonitorVoltageDescription
OBJECT-TYPE
A textual description of the mains voltage in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.5.3.1.3DisplayString (SIZE(1..16))read-writecurrent
mainsMonitorVoltageTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.3.5.3.1.4Counter32accessible-for-notifycurrent
mainsMonitorVoltageAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.5.3.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
mainsMonitorVoltageValue
OBJECT-TYPE
The value of the measured mains voltage in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.3.1.6Integer32read-onlycurrent
mainsMonitorVoltageMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.3.5.3.1.7Integer32read-writecurrent
mainsMonitorVoltageMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.3.5.3.1.8Integer32read-writecurrent
mainsMonitorVoltageMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.3.5.3.1.9Integer32read-writecurrent
mainsMonitorVoltageMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.3.5.3.1.10Integer32read-writecurrent
mainsMonitorCurrentTable
OBJECT-TYPE
This table contains information about mains current in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.4not-accessiblecurrent
mainsMonitorCurrentEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.5.4.1not-accessiblecurrent
mainsMonitorCurrentStatus
OBJECT-TYPE
The status of the measured mains current in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.4.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsMonitorCurrentDescription
OBJECT-TYPE
A textual description of the mains current in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.5.4.1.2DisplayString (SIZE(1..16))read-writecurrent
mainsMonitorCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.3.5.4.1.3Counter32accessible-for-notifycurrent
mainsMonitorCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.5.4.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
mainsMonitorCurrentValue
OBJECT-TYPE
The value of the measured mains current in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.4.1.5Integer32read-onlycurrent
mainsMonitorCurrentMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.3.5.4.1.6Integer32read-writecurrent
mainsMonitorCurrentMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.3.5.4.1.7Integer32read-writecurrent
mainsMonitorFrequencyTable
OBJECT-TYPE
This table contains information about mains frequency in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.5not-accessiblecurrent
mainsMonitorFrequencyEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.5.5.1not-accessiblecurrent
mainsMonitorFrequencyStatus
OBJECT-TYPE
The status of the measured mains frequency in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.5.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsMonitorFrequencyDescription
OBJECT-TYPE
A textual description of the mains frequency in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.5.5.1.2DisplayString (SIZE(0..16))read-writecurrent
mainsMonitorFrequencyTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.3.5.5.1.3Counter32accessible-for-notifycurrent
mainsMonitorFrequencyAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.5.5.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
mainsMonitorFrequencyValue
OBJECT-TYPE
The value of the measured mains frequency in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.5.1.5Integer32read-onlycurrent
mainsMonitorFrequencyMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.3.5.5.1.6Integer32read-writecurrent
mainsMonitorFrequencyMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.3.5.5.1.7Integer32read-writecurrent
mainsMonitorFrequencyMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.3.5.5.1.8Integer32read-writecurrent
mainsMonitorFrequencyMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.3.5.5.1.9Integer32read-writecurrent
mainsMonitorEnergyLogAccumulatedTable
OBJECT-TYPE
This table contains the accumulated energy consumption measured in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.6not-accessiblecurrent
mainsMonitorEnergyLogAccumulatedEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.5.6.1not-accessiblecurrent
mainsMonitorEnergyLogAccumulated
OBJECT-TYPE
The accumulated energy consumption value
1.3.6.1.4.1.12148.10.3.5.6.1.1Integer32read-onlycurrent
mainsMonitorEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in hourly energy log
1.3.6.1.4.1.12148.10.3.5.7Integer32 (0..52)read-onlycurrent
mainsMonitorEnergyLogLastHoursTable
OBJECT-TYPE
This table contains energy consumption values logged every hour in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.8not-accessiblecurrent
mainsMonitorEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.5.8.1not-accessiblecurrent
mainsMonitorEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.3.5.8.1.1Integer32 (1..52)not-accessiblecurrent
mainsMonitorEnergyLogLastHoursValue
OBJECT-TYPE
Energy consumption value logged every hour in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.8.1.2Integer32read-onlycurrent
mainsMonitorEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in daily energy log
1.3.6.1.4.1.12148.10.3.5.9Integer32 (0..52)read-onlycurrent
mainsMonitorEnergyLogLastDaysTable
OBJECT-TYPE
This table contains energy consumption values logged every day in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.10not-accessiblecurrent
mainsMonitorEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.5.10.1not-accessiblecurrent
mainsMonitorEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.3.5.10.1.1Integer32 (1..52)not-accessiblecurrent
mainsMonitorEnergyLogLastDaysValue
OBJECT-TYPE
Energy consumption value logged every day in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.10.1.2Integer32read-onlycurrent
mainsMonitorEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in weekly energy log
1.3.6.1.4.1.12148.10.3.5.11Integer32 (0..52)read-onlycurrent
mainsMonitorEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains energy consumption values logged every week in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.12not-accessiblecurrent
mainsMonitorEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.5.12.1not-accessiblecurrent
mainsMonitorEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastWeeksTable
1.3.6.1.4.1.12148.10.3.5.12.1.1Integer32 (1..52)not-accessiblecurrent
mainsMonitorEnergyLogLastWeeksValue
OBJECT-TYPE
Energy consumption value logged every week in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.12.1.2Integer32read-onlycurrent
mainsOutageLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.3.6
mainsOutageTotal
OBJECT-TYPE
This is the total mains outage time measured in hours.
1.3.6.1.4.1.12148.10.3.6.1Integer32read-onlycurrent
mainsOutageLogDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in daily mains outage log.
1.3.6.1.4.1.12148.10.3.6.2Integer32 (0..52)read-onlycurrent
mainsOutageLogDaysTable
OBJECT-TYPE
This table contains daily mains outage time log.
1.3.6.1.4.1.12148.10.3.6.3not-accessiblecurrent
mainsOutageLogDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.6.3.1not-accessiblecurrent
mainsOutageLogDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of mainsOutageLogDaysTable
1.3.6.1.4.1.12148.10.3.6.3.1.1Integer32 (1..52)not-accessiblecurrent
mainsOutageLogDaysValue
OBJECT-TYPE
Mains outage time value in minutes, logged every day.
1.3.6.1.4.1.12148.10.3.6.3.1.2Integer32read-onlycurrent
mainsOutageLogWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in weekly mains outage time log.
1.3.6.1.4.1.12148.10.3.6.4Integer32 (0..52)read-onlycurrent
mainsOutageLogWeeksTable
OBJECT-TYPE
This table contains weekly mains outage time log.
1.3.6.1.4.1.12148.10.3.6.5not-accessiblecurrent
mainsOutageLogWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.6.5.1not-accessiblecurrent
mainsOutageLogWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of mainsOutageLogWeeksTable
1.3.6.1.4.1.12148.10.3.6.5.1.1Integer32 (1..52)not-accessiblecurrent
mainsOutageLogWeeksValue
OBJECT-TYPE
Mains outage time value in hours, logged every week.
1.3.6.1.4.1.12148.10.3.6.5.1.2Integer32read-onlycurrent
mainsOutageLogMonthsNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in monthly mains outage time log.
1.3.6.1.4.1.12148.10.3.6.6Integer32 (0..52)read-onlycurrent
mainsOutageLogMonthsTable
OBJECT-TYPE
This table contains monthly mains outage time log.
1.3.6.1.4.1.12148.10.3.6.7not-accessiblecurrent
mainsOutageLogMonthsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.6.7.1not-accessiblecurrent
mainsOutageLogMonthsIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of mainsOutageLogMonthsTable
1.3.6.1.4.1.12148.10.3.6.7.1.1Integer32 (1..52)not-accessiblecurrent
mainsOutageLogMonthsValue
OBJECT-TYPE
Mains outage time value in hours, logged every month.
1.3.6.1.4.1.12148.10.3.6.7.1.2Integer32read-onlycurrent
mainsNumberOfGroups
OBJECT-TYPE
This value showing the number of groups of the mains subsystem.
1.3.6.1.4.1.12148.10.3.7Integer32read-onlycurrent
mainsGroupsTable
OBJECT-TYPE
This table contains the status of mains group and number of phases in each group.
1.3.6.1.4.1.12148.10.3.8not-accessiblecurrent
mainsGroupsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.8.1not-accessiblecurrent
mainsGroupIndex
OBJECT-TYPE
Index used for navigating the rows 1..10 of mainsGroupTable
1.3.6.1.4.1.12148.10.3.8.1.1Integer32 (1..10)not-accessiblecurrent
mainsGroupStatus
OBJECT-TYPE
The status of mains group.
1.3.6.1.4.1.12148.10.3.8.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsGroupNumberOfPhases
OBJECT-TYPE
This value showing the number of phases of the mains group subsystem.
1.3.6.1.4.1.12148.10.3.8.1.3Integer32read-writecurrent
mainsGroupMainsFailureTable
OBJECT-TYPE
This table contains information about mains failure monitor of mains group
1.3.6.1.4.1.12148.10.3.9not-accessiblecurrent
mainsGroupMainsFailureEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.9.1not-accessiblecurrent
mainsGroupMainsFailureStatus
OBJECT-TYPE
This status value shows if the number of failed phases is higher than the defined alarm level for the mains group
1.3.6.1.4.1.12148.10.3.9.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsGroupMainsFailureDescription
OBJECT-TYPE
A textual description of the mains group phase failure monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.9.1.2DisplayString (SIZE(0..16))read-writecurrent
mainsGroupMainsFailureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.3.9.1.3Integer32accessible-for-notifycurrent
mainsGroupMainsFailureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.9.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
mainsGroupMainsFailureValue
OBJECT-TYPE
The detected number of failed phases in the mains group.
1.3.6.1.4.1.12148.10.3.9.1.5Integer32read-onlycurrent
mainsGroupMainsFailureMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.3.9.1.6Integer32read-writecurrent
mainsGroupMainsFailureMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.3.9.1.7Integer32read-writecurrent
mainsGroupVoltageTable
OBJECT-TYPE
This table contains information about mains voltage monitors for mains group
1.3.6.1.4.1.12148.10.3.10not-accessiblecurrent
mainsGroupVoltageEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.10.1not-accessiblecurrent
mainsGroupVoltageIndex
OBJECT-TYPE
Index used for navigating the rows 1..12 of mainsGroupVoltageTable
1.3.6.1.4.1.12148.10.3.10.1.1Integer32 (1..12)not-accessiblecurrent
mainsGroupVoltageStatus
OBJECT-TYPE
The status of the measured mains voltage of the mains group.
1.3.6.1.4.1.12148.10.3.10.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsGroupVoltageDescription
OBJECT-TYPE
A textual description of the mains voltage monitor of the mains group. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.10.1.3DisplayString (SIZE(0..16))read-writecurrent
mainsGroupVoltageTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.3.10.1.4Integer32accessible-for-notifycurrent
mainsGroupVoltageAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.10.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
mainsGroupVoltageValue
OBJECT-TYPE
The value of the measured mains voltage in the mains group.
1.3.6.1.4.1.12148.10.3.10.1.6Integer32read-onlycurrent
mainsGroupVoltageMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.3.10.1.7Integer32read-writecurrent
mainsGroupVoltageMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.3.10.1.8Integer32read-writecurrent
mainsGroupVoltageMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.3.10.1.9Integer32read-writecurrent
mainsGroupVoltageMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.3.10.1.10Integer32read-writecurrent
mainsGroupOutageLogTable
OBJECT-TYPE
This table contains total mains outage of the mains group and number of entries in each log table.
1.3.6.1.4.1.12148.10.3.11not-accessiblecurrent
mainsGroupOutageLogEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.11.1not-accessiblecurrent
mainsGroupOutageTotal
OBJECT-TYPE
This is the total mains outage time measured in hours in the mains group.
1.3.6.1.4.1.12148.10.3.11.1.1Integer32read-onlycurrent
mainsGroupOutageLogDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in daily mains outage log.
1.3.6.1.4.1.12148.10.3.11.1.2Integer32read-onlycurrent
mainsGroupOutageLogWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in weekly mains outage time log.
1.3.6.1.4.1.12148.10.3.11.1.3Integer32read-onlycurrent
mainsGroupOutageLogMonthsNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in monthly mains outage time log.
1.3.6.1.4.1.12148.10.3.11.1.4Integer32read-onlycurrent
mainsGroupOutageLogDaysTable
OBJECT-TYPE
This table contains daily mains outage time log of mains group.
1.3.6.1.4.1.12148.10.3.12not-accessiblecurrent
mainsGroupOutageLogDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.12.1not-accessiblecurrent
mainsGroupOutageLogDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of mainsGroupOutageLogDaysTable
1.3.6.1.4.1.12148.10.3.12.1.1Integer32 (1..52)not-accessiblecurrent
mainsGroupOutageLogDaysValue
OBJECT-TYPE
Mains outage time value in minutes of each mains group, logged every day.
1.3.6.1.4.1.12148.10.3.12.1.2Integer32read-onlycurrent
mainsGroupOutageLogWeeksTable
OBJECT-TYPE
This table contains weekly mains outage time log of mains group.
1.3.6.1.4.1.12148.10.3.13not-accessiblecurrent
mainsGroupOutageLogWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.13.1not-accessiblecurrent
mainsGroupOutageLogWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of mainsGroupOutageLogWeeksTable
1.3.6.1.4.1.12148.10.3.13.1.1Integer32 (1..52)not-accessiblecurrent
mainsGroupOutageLogWeeksValue
OBJECT-TYPE
Mains outage time value in hours of each mains group, logged every week.
1.3.6.1.4.1.12148.10.3.13.1.2Integer32read-onlycurrent
mainsGroupOutageLogMonthsTable
OBJECT-TYPE
This table contains monthly mains outage time log of mains group.
1.3.6.1.4.1.12148.10.3.14not-accessiblecurrent
mainsGroupOutageLogMonthsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.3.14.1not-accessiblecurrent
mainsGroupOutageLogMonthsIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of mainsGroupOutageLogMonthsTable
1.3.6.1.4.1.12148.10.3.14.1.1Integer32 (1..52)not-accessiblecurrent
mainsGroupOutageLogMonthsValue
OBJECT-TYPE
Mains outage time value in hours of each mains group, logged every month.
1.3.6.1.4.1.12148.10.3.14.1.2Integer32read-onlycurrent
generator
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.4
generatorStatus
OBJECT-TYPE
The overall status of generator subsystem.
1.3.6.1.4.1.12148.10.4.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
generatorFailStatus
OBJECT-TYPE
The status of generator failure monitor.
1.3.6.1.4.1.12148.10.4.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
generatorActivation
OBJECT-TYPE
Indicate if the generator run output signal is activated.
1.3.6.1.4.1.12148.10.4.3Integer32read-onlycurrent
generatorDischargeValue
OBJECT-TYPE
This is the present discharge value in percentage of total capacity.
1.3.6.1.4.1.12148.10.4.4Integer32read-onlycurrent
generatorMainsDelay
OBJECT-TYPE
Elapsing time of mains failure.
1.3.6.1.4.1.12148.10.4.5Integer32read-onlycurrent
generatorChargeTime
OBJECT-TYPE
Elapsing time of charging with generator running.
1.3.6.1.4.1.12148.10.4.6Integer32read-onlycurrent
generatorCapacityControlledStartStopEnable
OBJECT-TYPE
Battery charge/discharge level control of starting and stopping of generator
1.3.6.1.4.1.12148.10.4.7INTEGER {disabled(0), enabled(1)}read-writecurrent
generatorCapacityStartOnDischargeLimit
OBJECT-TYPE
When the generatorCapacityControlled is enabled, the generator is started when the remaining battery capacity drops below this limit in percentage of the total capacity.
1.3.6.1.4.1.12148.10.4.8Integer32 (0..100)read-writecurrent
generatorCapacityStopOnChargeLimit
OBJECT-TYPE
When the generatorCapacityControlled is enabled, the generator is stopped when the remaining battery capacity is greater than this limit in percentage of the total capacity.
1.3.6.1.4.1.12148.10.4.9Integer32 (0..100)read-writecurrent
generatorCurrentLimitControlledStopEnable
OBJECT-TYPE
Enables the generator to stop when the charge current drops below generatorCurrentLimitControlledStopValue.
1.3.6.1.4.1.12148.10.4.10INTEGER {disabled(0), enabled(1)}read-writecurrent
generatorCurrentLimitControlledStopValue
OBJECT-TYPE
Generator stops when the charge current drop drops below this level.
1.3.6.1.4.1.12148.10.4.11Integer32 (0..100)read-writecurrent
generatorVoltageControlledStartEnable
OBJECT-TYPE
Enable/disable voltage controlled generator activation.
1.3.6.1.4.1.12148.10.4.12INTEGER {disabled(0), enabled(1)}read-writecurrent
generatorVoltageControlStartVoltage
OBJECT-TYPE
The voltage limit to start generator.
1.3.6.1.4.1.12148.10.4.13Integer32read-writecurrent
generatorVoltageControlStopAfter
OBJECT-TYPE
A time delay for stopping generator when generator is activated by voltage.
1.3.6.1.4.1.12148.10.4.14Integer32read-writecurrent
generatorDailyRunEnable
OBJECT-TYPE
Enable/disable generator daily run function.
1.3.6.1.4.1.12148.10.4.15INTEGER {disabled(0), enabled(1)}read-writecurrent
generatorDailyRunSetupTable
OBJECT-TYPE
This table contains configurations of generator daily run.
1.3.6.1.4.1.12148.10.4.16not-accessiblecurrent
generatorDailyRunSetupEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.16.1not-accessiblecurrent
generatorDailyRunDayIndex
OBJECT-TYPE
Index used for navigating the rows 1..7 of generatorDailyRunSetupTable
1.3.6.1.4.1.12148.10.4.16.1.1INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7)}not-accessiblecurrent
generatorDailyRunStartHour
OBJECT-TYPE
Generator daily starting time.
1.3.6.1.4.1.12148.10.4.16.1.2Integer32 (0..23)read-writecurrent
generatorDailyRunStopHour
OBJECT-TYPE
Generator daily stopping time.
1.3.6.1.4.1.12148.10.4.16.1.3Integer32 (0..23)read-writecurrent
generatorMonthlyRunEnable
OBJECT-TYPE
Enable/disable generator monthly run function.
1.3.6.1.4.1.12148.10.4.17INTEGER {disabled(0), enabled(1)}read-writecurrent
generatorMonthlyRunStartTime
OBJECT-TYPE
Generator monthly run starting time.
1.3.6.1.4.1.12148.10.4.18Integer32 (0..23)read-writecurrent
generatorMonthlyRunStartDayinMonth1
OBJECT-TYPE
Generator monthly run starting day #1.
1.3.6.1.4.1.12148.10.4.19Integer32 (1..32)read-writecurrent
generatorMonthlyRunStartDayinMonth2
OBJECT-TYPE
Generator monthly run starting day #2.
1.3.6.1.4.1.12148.10.4.20Integer32 (1..32)read-writecurrent
generatorTankNumberOfTanks
OBJECT-TYPE
Number of fuel tanks.
1.3.6.1.4.1.12148.10.4.21Integer32 (0..2)read-onlycurrent
generatorTankTable
OBJECT-TYPE
This table contains information about generator fuel tanks.
1.3.6.1.4.1.12148.10.4.22not-accessiblecurrent
generatorTankEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.22.1not-accessiblecurrent
generatorTankIndex
OBJECT-TYPE
Index used for navigating the rows 1..2 of generatorTankTable
1.3.6.1.4.1.12148.10.4.22.1.1Integer32 (1..2)not-accessiblecurrent
generatorTankStatus
OBJECT-TYPE
The status of the measured fuel level in tank.
1.3.6.1.4.1.12148.10.4.22.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
generatorTankDescription
OBJECT-TYPE
A textual description of the fuel level monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.4.22.1.3DisplayString (SIZE(0..16))read-writecurrent
generatorTankTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.4.22.1.4Counter32accessible-for-notifycurrent
generatorTankEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.4.22.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
generatorTankValue
OBJECT-TYPE
The value of the measured fuel level.
1.3.6.1.4.1.12148.10.4.22.1.6Integer32read-onlycurrent
generatorTankMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.4.22.1.7Integer32read-writecurrent
generatorTankMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.4.22.1.8Integer32read-writecurrent
generatorTankMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.4.22.1.9Integer32read-writecurrent
generatorTankMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.4.22.1.10Integer32read-writecurrent
generatorEnergyLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.4.23
generatorEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered through rectifiers from generator.
1.3.6.1.4.1.12148.10.4.23.1Integer32read-onlycurrent
generatorEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in generator hourly energy log.
1.3.6.1.4.1.12148.10.4.23.2Integer32 (0..52)read-onlycurrent
generatorEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly energy log of generator.
1.3.6.1.4.1.12148.10.4.23.3not-accessiblecurrent
generatorEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.23.3.1not-accessiblecurrent
generatorEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of generatorEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.4.23.3.1.1Integer32 (1..52)not-accessiblecurrent
generatorEnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.4.23.3.1.2Integer32read-onlycurrent
generatorEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in generator daily energy log.
1.3.6.1.4.1.12148.10.4.23.4Integer32 (0..52)read-onlycurrent
generatorEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily energy log of generator.
1.3.6.1.4.1.12148.10.4.23.5not-accessiblecurrent
generatorEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.23.5.1not-accessiblecurrent
generatorEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of generatorEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.4.23.5.1.1Integer32 (1..52)not-accessiblecurrent
generatorEnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day
1.3.6.1.4.1.12148.10.4.23.5.1.2Integer32read-onlycurrent
generatorEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in generator weekly energy log.
1.3.6.1.4.1.12148.10.4.23.6Integer32 (0..52)read-onlycurrent
generatorEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly energy log of generator.
1.3.6.1.4.1.12148.10.4.23.7not-accessiblecurrent
generatorEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.23.7.1not-accessiblecurrent
generatorEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of generatorEnergyLogLastWeeksTable
1.3.6.1.4.1.12148.10.4.23.7.1.1Integer32 (1..52)not-accessiblecurrent
generatorEnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.4.23.7.1.2Integer32read-onlycurrent
generatorRunHoursLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.4.24
generatorRunHoursTotalHours
OBJECT-TYPE
This is the total generator running hours.
1.3.6.1.4.1.12148.10.4.24.1Integer32read-onlycurrent
generatorRunHoursLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in generator daily running hours log.
1.3.6.1.4.1.12148.10.4.24.2Integer32 (0..52)read-onlycurrent
generatorRunHoursLogLastDaysTable
OBJECT-TYPE
generator running time in minutes
1.3.6.1.4.1.12148.10.4.24.3not-accessiblecurrent
generatorRunHoursLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.24.3.1not-accessiblecurrent
generatorRunHoursLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of generatorRunHoursLogLastDaysTable
1.3.6.1.4.1.12148.10.4.24.3.1.1Integer32 (1..52)not-accessiblecurrent
generatorRunHoursLogLastDaysValue
OBJECT-TYPE
Generator running time in minutes, logged every day.
1.3.6.1.4.1.12148.10.4.24.3.1.2Integer32read-onlycurrent
generatorRunHoursLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in generator weekly running hours log.
1.3.6.1.4.1.12148.10.4.24.4Integer32 (0..52)read-onlycurrent
generatorRunHoursLogLastWeeksTable
OBJECT-TYPE
generator running time in hours
1.3.6.1.4.1.12148.10.4.24.5not-accessiblecurrent
generatorRunHoursLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.24.5.1not-accessiblecurrent
generatorRunHoursLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of generatorRunHoursLogLastWeeksTable
1.3.6.1.4.1.12148.10.4.24.5.1.1Integer32 (1..52)not-accessiblecurrent
generatorRunHoursLogLastWeeksValue
OBJECT-TYPE
Generator running time in hours, logged every week.
1.3.6.1.4.1.12148.10.4.24.5.1.2Integer32read-onlycurrent
generatorRunHoursLogLastMonthsNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in generator monthly running hours log.
1.3.6.1.4.1.12148.10.4.24.6Integer32 (0..52)read-onlycurrent
generatorRunHoursLogLastMonthsTable
OBJECT-TYPE
generator running time in hours
1.3.6.1.4.1.12148.10.4.24.7not-accessiblecurrent
generatorRunHoursLogLastMonthsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.24.7.1not-accessiblecurrent
generatorRunHoursLogLastMonthsIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of generatorRunHoursLogLastMonthsTable
1.3.6.1.4.1.12148.10.4.24.7.1.1Integer32 (1..52)not-accessiblecurrent
generatorRunHoursLogLastMonthsValue
OBJECT-TYPE
Generator running time in hours, logged every month.
1.3.6.1.4.1.12148.10.4.24.7.1.2Integer32read-onlycurrent
generatorFuelConsumptionLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.4.25
generatorFuelConsumptionTotalUsedTable
OBJECT-TYPE
This table contains total fuel consumption for each tank.
1.3.6.1.4.1.12148.10.4.25.1not-accessiblecurrent
generatorFuelConsumptionTotalUsedEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.25.1.1not-accessiblecurrent
generatorFuelConsumptionTotalUsed
OBJECT-TYPE
Total fuel consumption value.
1.3.6.1.4.1.12148.10.4.25.1.1.1Integer32read-onlycurrent
generatorFuelConsumptionLogLastDaysNoOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in generator daily fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.2Integer32 (0..52)read-onlycurrent
generatorFuelConsumptionLogLastDaysTable
OBJECT-TYPE
This table contains generator daily fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.3not-accessiblecurrent
generatorFuelConsumptionLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.25.3.1not-accessiblecurrent
generatorFuelConsumptionLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastDaysTable
1.3.6.1.4.1.12148.10.4.25.3.1.1Integer32 (1..52)not-accessiblecurrent
generatorFuelConsumptionLogLastDaysValue
OBJECT-TYPE
Generator fuel consumption value, logged every day.
1.3.6.1.4.1.12148.10.4.25.3.1.2Integer32read-onlycurrent
generatorFuelConsumptionLogLastWeeksNoOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in generator weekly fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.4Integer32 (0..52)read-onlycurrent
generatorFuelConsumptionLogLastWeeksTable
OBJECT-TYPE
This table contains generator weekly fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.5not-accessiblecurrent
generatorFuelConsumptionLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.25.5.1not-accessiblecurrent
generatorFuelConsumptionLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastWeeksTable
1.3.6.1.4.1.12148.10.4.25.5.1.1Integer32 (1..52)not-accessiblecurrent
generatorFuelConsumptionLogLastWeeksValue
OBJECT-TYPE
Generator fuel consumption value, logged every week.
1.3.6.1.4.1.12148.10.4.25.5.1.2Integer32read-onlycurrent
generatorFuelConsumptionLogLastMonthsNoOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in generator hourly fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.6Integer32 (0..52)read-onlycurrent
generatorFuelConsumptionLogLastMonthsTable
OBJECT-TYPE
This table contains generator hourly fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.7not-accessiblecurrent
generatorFuelConsumptionLogLastMonthsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.4.25.7.1not-accessiblecurrent
generatorFuelConsumptionLogLastMonthsIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastHoursTable
1.3.6.1.4.1.12148.10.4.25.7.1.1Integer32 (1..52)not-accessiblecurrent
generatorFuelConsumptionLogLastMonthsValue
OBJECT-TYPE
Generator fuel consumption value, logged every hour.
1.3.6.1.4.1.12148.10.4.25.7.1.2Integer32read-onlycurrent
rectifiers
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.5
rectifiersStatus
OBJECT-TYPE
The overall status of rectifier subsystem.
1.3.6.1.4.1.12148.10.5.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifiersCurrent
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.5.2
rectifiersCurrentStatus
OBJECT-TYPE
The status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.5.2.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifiersCurrentDescription
OBJECT-TYPE
A textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.2.2DisplayString (SIZE(0..16))read-writecurrent
rectifiersCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.5.2.3Counter32accessible-for-notifycurrent
rectifiersCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.2.4INTEGER {disabled(0), enabled(1)}read-writecurrent
rectifiersCurrentValue
OBJECT-TYPE
The value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.5.2.5Integer32read-onlycurrent
rectifiersCurrentMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.5.2.6Integer32read-writecurrent
rectifiersCurrentMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.5.2.7Integer32read-writecurrent
rectifiersCapacity
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.5.3
rectifiersCapacityStatus
OBJECT-TYPE
The status of the measured used rectifier capacity.
1.3.6.1.4.1.12148.10.5.3.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifiersCapacityDescription
OBJECT-TYPE
A textual description of the used rectifier capacity monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.3.2DisplayString (SIZE(0..16))read-writecurrent
rectifiersCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.5.3.3Counter32accessible-for-notifycurrent
rectifiersCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.3.4INTEGER {disabled(0), enabled(1)}read-writecurrent
rectifiersCapacityValue
OBJECT-TYPE
The used rectifier capacity value presented in percentage of the total installed rectifier capacity.
1.3.6.1.4.1.12148.10.5.3.5Integer32read-onlycurrent
rectifiersCapacityMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.5.3.6Integer32read-writecurrent
rectifiersCapacityMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.5.3.7Integer32read-writecurrent
rectifiersError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.5.4
rectifiersErrorStatus
OBJECT-TYPE
This status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.5.4.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifiersErrorDescription
OBJECT-TYPE
A textual description of the rectifier error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.4.2DisplayString (SIZE(0..16))read-writecurrent
rectifiersErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.5.4.3Counter32accessible-for-notifycurrent
rectifiersErrorEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.4.4INTEGER {disabled(0), enabled(1)}read-writecurrent
rectifiersErrorValue
OBJECT-TYPE
The number of failed rectifiers.
1.3.6.1.4.1.12148.10.5.4.5Integer32read-onlycurrent
rectifiersErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.5.4.6Integer32read-writecurrent
rectifiersErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.5.4.7Integer32read-writecurrent
rectifiersNumberOfRectifiers
OBJECT-TYPE
Number of installed rectifiers.
1.3.6.1.4.1.12148.10.5.5Integer32 (0..100)read-writecurrent
rectifierTable
OBJECT-TYPE
This table shows the information of each rectifier installed in the system.
1.3.6.1.4.1.12148.10.5.6not-accessiblecurrent
rectifierEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.6.1not-accessiblecurrent
rectifierIndex
OBJECT-TYPE
Index used for navigating the rows 1..100 of rectifierTable
1.3.6.1.4.1.12148.10.5.6.1.1Integer32 (1..100)not-accessiblecurrent
rectifierStatus
OBJECT-TYPE
The overall status of rectifier.
1.3.6.1.4.1.12148.10.5.6.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifierOutputCurrentValue
OBJECT-TYPE
The output current value of rectifier.
1.3.6.1.4.1.12148.10.5.6.1.3Integer32read-onlycurrent
rectifierInputVoltageValue
OBJECT-TYPE
The input voltage value of rectifier.
1.3.6.1.4.1.12148.10.5.6.1.4Integer32read-onlycurrent
rectifierType
OBJECT-TYPE
Type of rectifier
1.3.6.1.4.1.12148.10.5.6.1.5DisplayString (SIZE(0..27))read-onlycurrent
rectifierHwPartNumber
OBJECT-TYPE
Hardware part number of rectifier
1.3.6.1.4.1.12148.10.5.6.1.6DisplayString (SIZE(0..12))read-onlycurrent
rectifierHwVersion
OBJECT-TYPE
Hardware version number of rectifier
1.3.6.1.4.1.12148.10.5.6.1.7DisplayString (SIZE(0..6))read-onlycurrent
rectifierSwPartNumber
OBJECT-TYPE
Part number of secondary software in rectifier
1.3.6.1.4.1.12148.10.5.6.1.8DisplayString (SIZE(0..12))read-onlycurrent
rectifierSwVersion
OBJECT-TYPE
Version number of secondary software in rectifier
1.3.6.1.4.1.12148.10.5.6.1.9DisplayString (SIZE(0..6))read-onlycurrent
rectifiersEnergyLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.5.7
rectifiersEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered from rectifiers.
1.3.6.1.4.1.12148.10.5.7.1Integer32read-onlycurrent
rectifiersEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in rectifier hourly energy log.
1.3.6.1.4.1.12148.10.5.7.2Integer32 (0..52)read-onlycurrent
rectifiersEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly energy log of rectifiers.
1.3.6.1.4.1.12148.10.5.7.3not-accessiblecurrent
rectifiersEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.7.3.1not-accessiblecurrent
rectifiersEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.5.7.3.1.1Integer32 (1..52)not-accessiblecurrent
rectifiersEnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.5.7.3.1.2Integer32read-onlycurrent
rectifiersEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in rectifier daily energy log.
1.3.6.1.4.1.12148.10.5.7.4Integer32 (0..52)read-onlycurrent
rectifiersEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily energy log of rectifiers.
1.3.6.1.4.1.12148.10.5.7.5not-accessiblecurrent
rectifiersEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.7.5.1not-accessiblecurrent
rectifiersEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.5.7.5.1.1Integer32 (1..52)not-accessiblecurrent
rectifiersEnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day.
1.3.6.1.4.1.12148.10.5.7.5.1.2Integer32read-onlycurrent
rectifiersEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in rectifier weekly energy log.
1.3.6.1.4.1.12148.10.5.7.6Integer32 (0..52)read-onlycurrent
rectifiersEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly energy log of rectifiers.
1.3.6.1.4.1.12148.10.5.7.7not-accessiblecurrent
rectifiersEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.7.7.1not-accessiblecurrent
rectifiersEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.5.7.7.1.1Integer32 (1..52)not-accessiblecurrent
rectifiersEnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.5.7.7.1.2Integer32read-onlycurrent
rectifiersNumberOfGroups
OBJECT-TYPE
Number of rectifier groups
1.3.6.1.4.1.12148.10.5.8Integer32read-onlycurrent
rectifierGroupsTable
OBJECT-TYPE
This table contains status and the number of installed rectifiers of each rectifier groups.
1.3.6.1.4.1.12148.10.5.9not-accessiblecurrent
rectifierGroupsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.9.1not-accessiblecurrent
rectifierGroupIndex
OBJECT-TYPE
Index used for navigating the rows 1..10 of rectifierGroupsTable
1.3.6.1.4.1.12148.10.5.9.1.1Integer32 (1..10)not-accessiblecurrent
rectifierGroupStatus
OBJECT-TYPE
The status of each rectifier group.
1.3.6.1.4.1.12148.10.5.9.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifierGroupNumberOfRectifiers
OBJECT-TYPE
Number of installed rectifiers in each rectifier groups
1.3.6.1.4.1.12148.10.5.9.1.3Integer32 (0..100)read-writecurrent
rectifierGroupCurrentTable
OBJECT-TYPE
This table contains information about the total rectifier current of each rectifier groups, which is calculated by summing up current from each rectifier in a rectifier group.
1.3.6.1.4.1.12148.10.5.10not-accessiblecurrent
rectifierGroupCurrentEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.10.1not-accessiblecurrent
rectifierGroupCurrentStatus
OBJECT-TYPE
The status of the measured total rectifier current of the rectifier group
1.3.6.1.4.1.12148.10.5.10.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifierGroupCurrentDescription
OBJECT-TYPE
A textual description of the total rectifier current monitor of a rectifier group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.10.1.2DisplayString (SIZE(0..16))read-writecurrent
rectifierGroupCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.5.10.1.3Integer32accessible-for-notifycurrent
rectifierGroupCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.10.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
rectifierGroupCurrentValue
OBJECT-TYPE
The value of the measured total rectifier current of each rectifier group.
1.3.6.1.4.1.12148.10.5.10.1.5Integer32read-onlycurrent
rectifierGroupCurrentMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.5.10.1.6Integer32read-writecurrent
rectifierGroupCurrentMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.5.10.1.7Integer32read-writecurrent
rectifierGroupCapacityTable
OBJECT-TYPE
This table contains information about the used rectifier capacity of each rectifier group.
1.3.6.1.4.1.12148.10.5.11not-accessiblecurrent
rectifierGroupCapacityEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.11.1not-accessiblecurrent
rectifierGroupCapacityStatus
OBJECT-TYPE
The status of the measured used rectifier capacity of each rectifier group
1.3.6.1.4.1.12148.10.5.11.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifierGroupCapacityDescription
OBJECT-TYPE
A textual description of the used rectifier capacity monitor of each rectifier group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.11.1.2DisplayString (SIZE(0..16))read-writecurrent
rectifierGroupCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.5.11.1.3Integer32accessible-for-notifycurrent
rectifierGroupCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.11.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
rectifierGroupCapacityValue
OBJECT-TYPE
The used rectifier capacity value presented in percentage of the total installed rectifier capacity of each rectifier group.
1.3.6.1.4.1.12148.10.5.11.1.5Integer32read-onlycurrent
rectifierGroupCapacityMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.5.11.1.6Integer32read-writecurrent
rectifierGroupCapacityMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.5.11.1.7Integer32read-writecurrent
rectifierGroupErrorTable
OBJECT-TYPE
This table contains information about the rectifier error monitor of each rectifier group.
1.3.6.1.4.1.12148.10.5.12not-accessiblecurrent
rectifierGroupErrorEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.12.1not-accessiblecurrent
rectifierGroupErrorStatus
OBJECT-TYPE
This status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.5.12.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifierGroupErrorDescription
OBJECT-TYPE
A textual description of the rectifier error monitor of each rectifier group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.12.1.2DisplayString (SIZE(0..16))read-writecurrent
rectifierGroupErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.5.12.1.3Integer32accessible-for-notifycurrent
rectifierGroupErrorAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.12.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
rectifierGroupErrorValue
OBJECT-TYPE
The number of failed rectifiers of each rectifier group.
1.3.6.1.4.1.12148.10.5.12.1.5Integer32read-onlycurrent
rectifierGroupErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.5.12.1.6Integer32read-writecurrent
rectifierGroupErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.5.12.1.7Integer32read-writecurrent
rectifierGroupRectifierTable
OBJECT-TYPE
This table shows the information of each rectifier installed in each of the rectifier group in the system.
1.3.6.1.4.1.12148.10.5.13not-accessiblecurrent
rectifierGroupRectifierEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.13.1not-accessiblecurrent
rectifierGroupRectifierIndex
OBJECT-TYPE
Index used for navigating the rows 1..100 of rectifierGroupRectifierTable
1.3.6.1.4.1.12148.10.5.13.1.1Integer32 (1..100)not-accessiblecurrent
rectifierGroupRectifierStatus
OBJECT-TYPE
The overall status of rectifier.
1.3.6.1.4.1.12148.10.5.13.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifierGroupRectifierOutputCurrentValue
OBJECT-TYPE
The output current value of rectifier.
1.3.6.1.4.1.12148.10.5.13.1.3Integer32read-onlycurrent
rectifierGroupRectifierInputVoltageValue
OBJECT-TYPE
The input voltage value of rectifier.
1.3.6.1.4.1.12148.10.5.13.1.4Integer32read-onlycurrent
rectifierGroupRectifierType
OBJECT-TYPE
Type of rectifier
1.3.6.1.4.1.12148.10.5.13.1.5DisplayString (SIZE(0..27))read-onlycurrent
rectifierGroupRectifierHwPartNumber
OBJECT-TYPE
Hardware part number of rectifier
1.3.6.1.4.1.12148.10.5.13.1.6DisplayString (SIZE(0..12))read-onlycurrent
rectifierGroupRectifierHwVersion
OBJECT-TYPE
Hardware version number of rectifier
1.3.6.1.4.1.12148.10.5.13.1.7DisplayString (SIZE(0..6))read-onlycurrent
rectifierGroupRectifierSwPartNumber
OBJECT-TYPE
Part number of secondary software in rectifier
1.3.6.1.4.1.12148.10.5.13.1.8DisplayString (SIZE(0..12))read-onlycurrent
rectifierGroupRectifierSwVersion
OBJECT-TYPE
Version number of secondary software in rectifier
1.3.6.1.4.1.12148.10.5.13.1.9DisplayString (SIZE(0..6))read-onlycurrent
rectifierGroupEnergyLogTable
OBJECT-TYPE
This branch contains information about rectifiers' energy logs of each rectifier group.
1.3.6.1.4.1.12148.10.5.14not-accessiblecurrent
rectifierGroupEnergyLogEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.14.1not-accessiblecurrent
rectifierGroupEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered from rectifiers of each rectifier group.
1.3.6.1.4.1.12148.10.5.14.1.1Integer32read-onlycurrent
rectifierGroupEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in rectifier group hourly energy log.
1.3.6.1.4.1.12148.10.5.14.1.2Integer32read-onlycurrent
rectifierGroupEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in rectifier group daily energy log.
1.3.6.1.4.1.12148.10.5.14.1.3Integer32read-onlycurrent
rectifierGroupEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in rectifier group weekly energy log.
1.3.6.1.4.1.12148.10.5.14.1.4Integer32read-onlycurrent
rectifierGroupEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly energy log of each rectifier group
1.3.6.1.4.1.12148.10.5.15not-accessiblecurrent
rectifierGroupEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.15.1not-accessiblecurrent
rectifierGroupEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.5.15.1.1Integer32 (1..52)not-accessiblecurrent
rectifierGroupEnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.5.15.1.2Integer32read-onlycurrent
rectifierGroupEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily energy log of each rectifier group
1.3.6.1.4.1.12148.10.5.16not-accessiblecurrent
rectifierGroupEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.16.1not-accessiblecurrent
rectifierGroupEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLasDaysTable
1.3.6.1.4.1.12148.10.5.16.1.1Integer32 (1..52)not-accessiblecurrent
rectifierGroupEnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day.
1.3.6.1.4.1.12148.10.5.16.1.2Integer32read-onlycurrent
rectifierGroupEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly energy log of each rectifier group
1.3.6.1.4.1.12148.10.5.17not-accessiblecurrent
rectifierGroupEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.17.1not-accessiblecurrent
rectifierGroupEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLastWeeksTable
1.3.6.1.4.1.12148.10.5.17.1.1Integer32 (1..52)not-accessiblecurrent
rectifierGroupEnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.5.17.1.2Integer32read-onlycurrent
rectifiersTemperature
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.5.18
rectifiersTemperatureStatus
OBJECT-TYPE
The state of the rectifier temperature can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.5.18.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifiersTemperatureDescription
OBJECT-TYPE
A textual description of the rectifier temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.5.18.2DisplayString (SIZE(0..16))read-writecurrent
rectifiersTemperatureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.5.18.3Counter32accessible-for-notifycurrent
rectifiersTemperatureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.18.4INTEGER {disabled(0), enabled(1)}read-writecurrent
rectifiersTemperatureValue
OBJECT-TYPE
The highest value of the rectifier temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.10.5.18.5Integer32 (0..9999)read-onlycurrent
rectifiersTemperatureMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.5.18.6Integer32read-writecurrent
rectifiersTemperatureMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.5.18.7Integer32read-writecurrent
rectifiersTemperatureMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.5.18.8Integer32read-writecurrent
rectifiersTemperatureMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.5.18.9Integer32read-writecurrent
rectifierGroupTemperatureTable
OBJECT-TYPE
This table contains information about the highest rectifier temperature of each rectifier groups, which is calculated by summing up current from each rectifier in a rectifier group.
1.3.6.1.4.1.12148.10.5.19not-accessiblecurrent
rectifierGroupTemperatureEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.5.19.1not-accessiblecurrent
rectifierGroupTemperatureStatus
OBJECT-TYPE
The status of the measured highest rectifier temperature of the rectifier group
1.3.6.1.4.1.12148.10.5.19.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
rectifierGroupTemperatureDescription
OBJECT-TYPE
A textual description of the highest rectifier temperature monitor of a rectifier group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.19.1.2DisplayString (SIZE(0..16))read-writecurrent
rectifierGroupTemperatureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.5.19.1.3Integer32accessible-for-notifycurrent
rectifierGroupTemperatureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.19.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
rectifierGroupTemperatureValue
OBJECT-TYPE
The value of the measured highest rectifier temperature of each rectifier group.
1.3.6.1.4.1.12148.10.5.19.1.5Integer32read-onlycurrent
rectifierGroupTemperatureMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.5.19.1.6Integer32read-writecurrent
rectifierGroupTemperatureMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.5.19.1.7Integer32read-writecurrent
rectifierGroupTemperatureMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.5.19.1.8Integer32read-writecurrent
rectifierGroupTemperatureMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.5.19.1.9Integer32read-writecurrent
dcdc
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.6
dcdcNumberOfGroups
OBJECT-TYPE
Number of dcdc groups
1.3.6.1.4.1.12148.10.6.1Integer32 (0..5)read-onlycurrent
dcdcGroupsTable
OBJECT-TYPE
This table contains information about dcdc groups.
1.3.6.1.4.1.12148.10.6.2not-accessiblecurrent
dcdcGroupsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.6.2.1not-accessiblecurrent
dcdcGroupIndex
OBJECT-TYPE
1.3.6.1.4.1.12148.10.6.2.1.1Integer32 (1..5)not-accessiblecurrent
dcdcGroupStatus
OBJECT-TYPE
The overall status of dcdc group.
1.3.6.1.4.1.12148.10.6.2.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
dcdcGroupNumberOfDcdcConverters
OBJECT-TYPE
Number of installed dcdc converters.
1.3.6.1.4.1.12148.10.6.2.1.3Integer32read-writecurrent
dcdcGroupOutputVoltage
OBJECT-TYPE
Output voltage of dcdc converters
1.3.6.1.4.1.12148.10.6.2.1.4Integer32read-writecurrent
dcdcNumberOfCurrents
OBJECT-TYPE
Number of dcdc currents
1.3.6.1.4.1.12148.10.6.2.1.5Integer32 (0..5)read-onlycurrent
dcdcNumberOfCapacities
OBJECT-TYPE
Number of dcdc capacities
1.3.6.1.4.1.12148.10.6.2.1.6Integer32 (0..5)read-onlycurrent
dcdcNumberOfAlarms
OBJECT-TYPE
Number of dcdc alarms
1.3.6.1.4.1.12148.10.6.2.1.7Integer32 (0..5)read-onlycurrent
dcdcCurrentTable
OBJECT-TYPE
This table contains information about the total dcdc current.
1.3.6.1.4.1.12148.10.6.3not-accessiblecurrent
dcdcCurrentEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.6.3.1not-accessiblecurrent
dcdcCurrentStatus
OBJECT-TYPE
The status of the measured total dcdc current.
1.3.6.1.4.1.12148.10.6.3.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
dcdcCurrentDescription
OBJECT-TYPE
A textual description of the total dcdc current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.6.3.1.2DisplayString (SIZE(0..16))read-writecurrent
dcdcCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.6.3.1.3Counter32accessible-for-notifycurrent
dcdcCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.6.3.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
dcdcCurrentValue
OBJECT-TYPE
The value of the measured total dcdc current.
1.3.6.1.4.1.12148.10.6.3.1.5Integer32read-onlycurrent
dcdcCurrentMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.6.3.1.6Integer32read-writecurrent
dcdcCurrentMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.6.3.1.7Integer32read-writecurrent
dcdcCapacityTable
OBJECT-TYPE
This table contains information about the used dcdc capacity.
1.3.6.1.4.1.12148.10.6.4not-accessiblecurrent
dcdcCapacityEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.6.4.1not-accessiblecurrent
dcdcCapacityStatus
OBJECT-TYPE
The status of the measured used dcdc capacity.
1.3.6.1.4.1.12148.10.6.4.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
dcdcCapacityDescription
OBJECT-TYPE
A textual description of the used dcdc capacity monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.6.4.1.2DisplayString (SIZE(0..16))read-writecurrent
dcdcCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes of
1.3.6.1.4.1.12148.10.6.4.1.3Counter32accessible-for-notifycurrent
dcdcCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.6.4.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
dcdcCapacityValue
OBJECT-TYPE
The used dcdc capacity value presented in percentage of the total installed dcdc capacity.
1.3.6.1.4.1.12148.10.6.4.1.5Integer32read-onlycurrent
dcdcCapacityMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.6.4.1.6Integer32read-writecurrent
dcdcCapacityMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.6.4.1.7Integer32read-writecurrent
dcdcTable
OBJECT-TYPE
This table shows the information of each dcdc converter installed in the system.
1.3.6.1.4.1.12148.10.6.5not-accessiblecurrent
dcdcEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.6.5.1not-accessiblecurrent
dcdcIndex
OBJECT-TYPE
Index used for navigating the rows 1..100 of dcdcTable
1.3.6.1.4.1.12148.10.6.5.1.1Integer32 (1..100)not-accessiblecurrent
dcdcStatus
OBJECT-TYPE
The overall status of dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
dcdcOutputCurrentValue
OBJECT-TYPE
The output current value of dcdc.
1.3.6.1.4.1.12148.10.6.5.1.3Integer32read-onlycurrent
dcdcInputVoltageValue
OBJECT-TYPE
The input voltage value of dcdc.
1.3.6.1.4.1.12148.10.6.5.1.4Integer32read-onlycurrent
dcdcType
OBJECT-TYPE
Type of dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.5DisplayString (SIZE(0..27))read-onlycurrent
dcdcHwPartNumber
OBJECT-TYPE
Hardware part number of dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.6DisplayString (SIZE(0..12))read-onlycurrent
dcdcHwVersion
OBJECT-TYPE
Hardware version number of dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.7DisplayString (SIZE(0..6))read-onlycurrent
dcdcSwPartNumber
OBJECT-TYPE
Part number of secondary software in dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.8DisplayString (SIZE(0..12))read-onlycurrent
dcdcSwVersion
OBJECT-TYPE
Version number of secondary software in dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.9DisplayString (SIZE(0..6))read-onlycurrent
dcdcErrorTable
OBJECT-TYPE
This table contains information about the dcdc error monitor.
1.3.6.1.4.1.12148.10.6.6not-accessiblecurrent
dcdcErrorEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.6.6.1not-accessiblecurrent
dcdcErrorStatus
OBJECT-TYPE
This status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.6.6.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
dcdcErrorDescription
OBJECT-TYPE
A textual description of the dcdc error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.6.6.1.2DisplayString (SIZE(0..16))read-writecurrent
dcdcErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.6.6.1.3Counter32accessible-for-notifycurrent
dcdcErrorEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.6.6.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
dcdcErrorValue
OBJECT-TYPE
The number of failed dcdc converters.
1.3.6.1.4.1.12148.10.6.6.1.5Integer32read-onlycurrent
dcdcErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.6.6.1.6Integer32read-writecurrent
dcdcErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.6.6.1.7Integer32read-writecurrent
dcdcObsolete
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.6.7
solarChargers
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.7
solarChargersStatus
OBJECT-TYPE
The overall status of solar charger subsystem.
1.3.6.1.4.1.12148.10.7.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
solarChargersCurrent
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.7.2
solarChargersCurrentStatus
OBJECT-TYPE
The status of the measured total solar current.
1.3.6.1.4.1.12148.10.7.2.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
solarChargersCurrentDescription
OBJECT-TYPE
A textual description of the total solar current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.7.2.2DisplayString (SIZE(0..16))read-writecurrent
solarChargersCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.7.2.3Counter32accessible-for-notifycurrent
solarChargersCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.7.2.4INTEGER {disabled(0), enabled(1)}read-writecurrent
solarChargersCurrentValue
OBJECT-TYPE
The value of the measured total solar current.
1.3.6.1.4.1.12148.10.7.2.5Integer32read-onlycurrent
solarChargersCurrentMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.7.2.6Integer32read-writecurrent
solarChargersCurrentMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.7.2.7Integer32read-writecurrent
solarChargersObsolete
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.7.3
solarChargersError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.7.4
solarChargersErrorStatus
OBJECT-TYPE
This status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.7.4.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
solarChargersErrorDescription
OBJECT-TYPE
A textual description of the solar error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.7.4.2DisplayString (SIZE(0..16))read-writecurrent
solarChargersErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.7.4.3Counter32accessible-for-notifycurrent
solarChargersErrorEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.7.4.4INTEGER {disabled(0), enabled(1)}read-writecurrent
solarChargersErrorValue
OBJECT-TYPE
The number of failed solar chargers.
1.3.6.1.4.1.12148.10.7.4.5Integer32read-onlycurrent
solarChargersErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.7.4.6Integer32read-writecurrent
solarChargersErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.7.4.7Integer32read-writecurrent
solarChargersNumberOfSolarChargers
OBJECT-TYPE
Number of installed solar chargers.
1.3.6.1.4.1.12148.10.7.5Integer32 (0..100)read-writecurrent
solarChargerTable
OBJECT-TYPE
This table shows the information of each solar charger installed in the system.
1.3.6.1.4.1.12148.10.7.6not-accessiblecurrent
solarChargerEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.7.6.1not-accessiblecurrent
solarChargerIndex
OBJECT-TYPE
Index used for navigating the rows 1..100 of solarChargerTable
1.3.6.1.4.1.12148.10.7.6.1.1Integer32 (1..100)not-accessiblecurrent
solarChargerStatus
OBJECT-TYPE
The overall status of solar charger.
1.3.6.1.4.1.12148.10.7.6.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
solarChargerOutputCurrentValue
OBJECT-TYPE
The output current value of solar charger.
1.3.6.1.4.1.12148.10.7.6.1.3Integer32read-onlycurrent
solarChargerInputVoltageValue
OBJECT-TYPE
The input voltage value of solar charger.
1.3.6.1.4.1.12148.10.7.6.1.4Integer32read-onlycurrent
solarChargerType
OBJECT-TYPE
Type of solar charger
1.3.6.1.4.1.12148.10.7.6.1.5DisplayString (SIZE(0..27))read-onlycurrent
solarChargerHwPartNumber
OBJECT-TYPE
Hardware part number of solar charger
1.3.6.1.4.1.12148.10.7.6.1.6DisplayString (SIZE(0..12))read-onlycurrent
solarChargerHwVersion
OBJECT-TYPE
Hardware version number of solar charger
1.3.6.1.4.1.12148.10.7.6.1.7DisplayString (SIZE(0..6))read-onlycurrent
solarChargerSwPartNumber
OBJECT-TYPE
Part number of secondary software in solar charger
1.3.6.1.4.1.12148.10.7.6.1.8DisplayString (SIZE(0..12))read-onlycurrent
solarChargerSwVersion
OBJECT-TYPE
Version number of secondary software in solar charger
1.3.6.1.4.1.12148.10.7.6.1.9DisplayString (SIZE(0..6))read-onlycurrent
solarChargersEnergyLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.7.7
solarChargersEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered from solar chargers.
1.3.6.1.4.1.12148.10.7.7.1Integer32read-onlycurrent
solarChargersEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in solar charger hourly energy log.
1.3.6.1.4.1.12148.10.7.7.2Integer32read-onlycurrent
solarChargersEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly energy log of solar chargers.
1.3.6.1.4.1.12148.10.7.7.3not-accessiblecurrent
solarChargersEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.7.7.3.1not-accessiblecurrent
solarChargersEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.7.7.3.1.1Integer32 (1..52)not-accessiblecurrent
solarChargersEnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.7.7.3.1.2Integer32read-onlycurrent
solarChargersEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in solar charger daily energy log.
1.3.6.1.4.1.12148.10.7.7.4Integer32read-onlycurrent
solarChargersEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily energy log of solar chargers.
1.3.6.1.4.1.12148.10.7.7.5not-accessiblecurrent
solarChargersEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.7.7.5.1not-accessiblecurrent
solarChargersEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.7.7.5.1.1Integer32 (1..52)not-accessiblecurrent
solarChargersEnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day.
1.3.6.1.4.1.12148.10.7.7.5.1.2Integer32read-onlycurrent
solarChargersEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in solar charger weekly energy log.
1.3.6.1.4.1.12148.10.7.7.6Integer32read-onlycurrent
solarChargersEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly energy log of solar chargers.
1.3.6.1.4.1.12148.10.7.7.7not-accessiblecurrent
solarChargersEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.7.7.7.1not-accessiblecurrent
solarChargersEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.7.7.7.1.1Integer32 (1..52)not-accessiblecurrent
solarChargersEnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.7.7.7.1.2Integer32read-onlycurrent
windChargers
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.8
windChargersStatus
OBJECT-TYPE
The overall status of wind charger subsystem.
1.3.6.1.4.1.12148.10.8.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
windChargersCurrent
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.8.2
windChargersCurrentStatus
OBJECT-TYPE
The status of the measured total wind current.
1.3.6.1.4.1.12148.10.8.2.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
windChargersCurrentDescription
OBJECT-TYPE
A textual description of the total wind current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.8.2.2DisplayString (SIZE(0..16))read-writecurrent
windChargersCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.8.2.3Counter32accessible-for-notifycurrent
windChargersCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.8.2.4INTEGER {disabled(0), enabled(1)}read-writecurrent
windChargersCurrentValue
OBJECT-TYPE
The value of the measured total wind current.
1.3.6.1.4.1.12148.10.8.2.5Integer32read-onlycurrent
windChargersCurrentMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.8.2.6Integer32read-writecurrent
windChargersCurrentMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.8.2.7Integer32read-writecurrent
windChargersObsolete
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.8.3
windChargersError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.8.4
windChargersErrorStatus
OBJECT-TYPE
This status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.8.4.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
windChargersErrorDescription
OBJECT-TYPE
A textual description of the wind error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.8.4.2DisplayString (SIZE(0..16))read-writecurrent
windChargersErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.8.4.3Counter32accessible-for-notifycurrent
windChargersErrorEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.8.4.4INTEGER {disabled(0), enabled(1)}read-writecurrent
windChargersErrorValue
OBJECT-TYPE
The number of failed wind chargers.
1.3.6.1.4.1.12148.10.8.4.5Integer32read-onlycurrent
windChargersErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.8.4.6Integer32read-writecurrent
windChargersErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.8.4.7Integer32read-writecurrent
windChargersNumberOfWindChargers
OBJECT-TYPE
Number of installed wind chargers.
1.3.6.1.4.1.12148.10.8.5Integer32 (0..254)read-writecurrent
windChargerTable
OBJECT-TYPE
This table shows the information of each wind charger installed in the system.
1.3.6.1.4.1.12148.10.8.6not-accessiblecurrent
windChargerEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.8.6.1not-accessiblecurrent
windChargerIndex
OBJECT-TYPE
Index used for navigating the rows 1..100 of windChargerTable
1.3.6.1.4.1.12148.10.8.6.1.1Integer32 (1..100)not-accessiblecurrent
windChargerStatus
OBJECT-TYPE
The overall status of wind charger.
1.3.6.1.4.1.12148.10.8.6.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
windChargerOutputCurrentValue
OBJECT-TYPE
The output current value of wind charger.
1.3.6.1.4.1.12148.10.8.6.1.3Integer32read-onlycurrent
windChargerInputVoltageValue
OBJECT-TYPE
The input voltage value of wind charger.
1.3.6.1.4.1.12148.10.8.6.1.4Integer32read-onlycurrent
windChargerType
OBJECT-TYPE
Type of wind charger
1.3.6.1.4.1.12148.10.8.6.1.5DisplayString (SIZE(0..27))read-onlycurrent
windChargerHwPartNumber
OBJECT-TYPE
Hardware part number of wind charger
1.3.6.1.4.1.12148.10.8.6.1.6DisplayString (SIZE(0..12))read-onlycurrent
windChargerHwVersion
OBJECT-TYPE
Hardware version number of wind charger
1.3.6.1.4.1.12148.10.8.6.1.7DisplayString (SIZE(0..6))read-onlycurrent
windChargerSwPartNumber
OBJECT-TYPE
Part number of secondary software in wind charger
1.3.6.1.4.1.12148.10.8.6.1.8DisplayString (SIZE(0..12))read-onlycurrent
windChargerSwVersion
OBJECT-TYPE
Version number of secondary software in wind charger
1.3.6.1.4.1.12148.10.8.6.1.9DisplayString (SIZE(0..6))read-onlycurrent
windChargersEnergyLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.8.7
windChargersEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered to/from wind chargers.
1.3.6.1.4.1.12148.10.8.7.1Integer32read-onlycurrent
windChargersEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in wind charger hourly energy log.
1.3.6.1.4.1.12148.10.8.7.2Integer32 (0..52)read-onlycurrent
windChargersEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly energy log of wind chargers.
1.3.6.1.4.1.12148.10.8.7.3not-accessiblecurrent
windChargersEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.8.7.3.1not-accessiblecurrent
windChargersEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of windChargersEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.8.7.3.1.1Integer32 (1..52)not-accessiblecurrent
windChargersEnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.8.7.3.1.2Integer32read-onlycurrent
windChargersEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in wind charger daily energy log.
1.3.6.1.4.1.12148.10.8.7.4Integer32 (0..52)read-onlycurrent
windChargersEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily energy log of wind chargers.
1.3.6.1.4.1.12148.10.8.7.5not-accessiblecurrent
windChargersEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.8.7.5.1not-accessiblecurrent
windChargersEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of windChargersEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.8.7.5.1.1Integer32 (1..52)not-accessiblecurrent
windChargersEnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day.
1.3.6.1.4.1.12148.10.8.7.5.1.2Integer32read-onlycurrent
windChargersEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in wind charger weekly energy log.
1.3.6.1.4.1.12148.10.8.7.6Integer32 (0..52)read-onlycurrent
windChargersEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly energy log of wind chargers.
1.3.6.1.4.1.12148.10.8.7.7not-accessiblecurrent
windChargersEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.8.7.7.1not-accessiblecurrent
windChargersEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of windChargersEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.8.7.7.1.1Integer32 (1..52)not-accessiblecurrent
windChargersEnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.8.7.7.1.2Integer32read-onlycurrent
load
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.9
loadStatus
OBJECT-TYPE
The overall status of load subsystem.
1.3.6.1.4.1.12148.10.9.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
loadCurrent
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.9.2
loadCurrentStatus
OBJECT-TYPE
The status of the measured load current.
1.3.6.1.4.1.12148.10.9.2.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
loadCurrentDescription
OBJECT-TYPE
A textual description of the load current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.9.2.2DisplayString (SIZE(0..16))read-writecurrent
loadCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.9.2.3Counter32accessible-for-notifycurrent
loadCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.9.2.4INTEGER {disabled(0), enabled(1)}read-writecurrent
loadCurrentValue
OBJECT-TYPE
The value of the measured load current.
1.3.6.1.4.1.12148.10.9.2.5Integer32read-onlycurrent
loadCurrentMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.9.2.6Integer32read-writecurrent
loadCurrentMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.9.2.7Integer32read-writecurrent
loadFusesStatus
OBJECT-TYPE
The overall status of the load fuses.
1.3.6.1.4.1.12148.10.9.3INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
loadNumberOfGroups
OBJECT-TYPE
Number of load groups
1.3.6.1.4.1.12148.10.9.4Integer32 (1..8)read-writecurrent
loadGroupTable
OBJECT-TYPE
This table contains information about load groups.
1.3.6.1.4.1.12148.10.9.5not-accessiblecurrent
loadGroupEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.5.1not-accessiblecurrent
loadGroupIndex
OBJECT-TYPE
Index used for navigating the rows 1..8 of loadGroupTable
1.3.6.1.4.1.12148.10.9.5.1.1Integer32 (1..8)not-accessiblecurrent
loadGroupStatus
OBJECT-TYPE
The status of load group
1.3.6.1.4.1.12148.10.9.5.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
loadNumberOfLVLDs
OBJECT-TYPE
Number of LVLDs installed in load group
1.3.6.1.4.1.12148.10.9.5.1.3Integer32 (0..4)read-onlycurrent
loadNumberOfVoltages
OBJECT-TYPE
Number of voltages in load group
1.3.6.1.4.1.12148.10.9.5.1.4Integer32 (0..4)read-onlycurrent
loadLVLDTable
OBJECT-TYPE
This table contains information about LVLDs
1.3.6.1.4.1.12148.10.9.6not-accessiblecurrent
loadLVLDEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.6.1not-accessiblecurrent
loadLVLDIndex
OBJECT-TYPE
Index used for navigating the rows 1..8 of loadLVLDTable
1.3.6.1.4.1.12148.10.9.6.1.1Integer32 (1..8)not-accessiblecurrent
loadLVLDStatus
OBJECT-TYPE
The status of LVLD
1.3.6.1.4.1.12148.10.9.6.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
loadLVLDDescription
OBJECT-TYPE
A textual description of the LVLD. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.9.6.1.3DisplayString (SIZE(0..16))read-writecurrent
loadLVLDTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.9.6.1.4Counter32accessible-for-notifycurrent
loadLVLDEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the LVLD will be reported.
1.3.6.1.4.1.12148.10.9.6.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
loadLVLDValue
OBJECT-TYPE
The measured value of the LVLD.
1.3.6.1.4.1.12148.10.9.6.1.6Integer32read-onlycurrent
loadLVLDConnectVoltage
OBJECT-TYPE
The load Contactor's Reconnect Voltage
1.3.6.1.4.1.12148.10.9.6.1.7Integer32read-writecurrent
loadLVLDDisconnectVoltage
OBJECT-TYPE
The load Contactor's Disconnect Voltage
1.3.6.1.4.1.12148.10.9.6.1.8Integer32read-writecurrent
loadFuseTable
OBJECT-TYPE
This table contains information about load fuse
1.3.6.1.4.1.12148.10.9.7not-accessiblecurrent
loadFuseEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.7.1not-accessiblecurrent
loadFuseStatus
OBJECT-TYPE
The status of load fuse
1.3.6.1.4.1.12148.10.9.7.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11)}read-onlycurrent
loadFuseDescription
OBJECT-TYPE
A textual description of the load fuse monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.9.7.1.2DisplayString (SIZE(0..16))read-writecurrent
loadFuseTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.9.7.1.3Counter32accessible-for-notifycurrent
loadFuseAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.9.7.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
loadFuseValue
OBJECT-TYPE
The measured value of the load fuse.
1.3.6.1.4.1.12148.10.9.7.1.5Integer32read-writecurrent
loadEnergyLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.9.8
loadEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered to load.
1.3.6.1.4.1.12148.10.9.8.1Integer32read-onlycurrent
loadEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in load hourly energy log.
1.3.6.1.4.1.12148.10.9.8.2Integer32 (0..52)read-onlycurrent
loadEnergyLogLastHoursTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.8.3not-accessiblecurrent
loadEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.8.3.1not-accessiblecurrent
loadEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of loadEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.9.8.3.1.1Integer32 (1..52)not-accessiblecurrent
loadEnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.9.8.3.1.2Integer32read-onlycurrent
loadEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in load daily energy log.
1.3.6.1.4.1.12148.10.9.8.4Integer32 (0..52)read-onlycurrent
loadEnergyLogLastDaysTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.8.5not-accessiblecurrent
loadEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.8.5.1not-accessiblecurrent
loadEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of loadEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.9.8.5.1.1Integer32 (1..52)not-accessiblecurrent
loadEnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day.
1.3.6.1.4.1.12148.10.9.8.5.1.2Integer32read-onlycurrent
loadEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in load weekly energy log.
1.3.6.1.4.1.12148.10.9.8.6Integer32 (0..52)read-onlycurrent
loadEnergyLogLastWeeksTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.8.7not-accessiblecurrent
loadEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.8.7.1not-accessiblecurrent
loadEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of loadEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.9.8.7.1.1Integer32 (1..52)not-accessiblecurrent
loadEnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.9.8.7.1.2Integer32read-onlycurrent
loadVoltageTable
OBJECT-TYPE
This table contains information about voltages
1.3.6.1.4.1.12148.10.9.9not-accessiblecurrent
loadVoltageEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.9.9.1not-accessiblecurrent
loadVoltageIndex
OBJECT-TYPE
Index used for navigating the rows 1..3 of loadVoltageTable
1.3.6.1.4.1.12148.10.9.9.1.1Integer32 (1..3)not-accessiblecurrent
loadVoltageStatus
OBJECT-TYPE
The status of voltage
1.3.6.1.4.1.12148.10.9.9.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
loadVoltageDescription
OBJECT-TYPE
A textual description of the voltage. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.9.9.1.3DisplayString (SIZE(0..16))read-writecurrent
loadVoltageTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.9.9.1.4Counter32accessible-for-notifycurrent
loadVoltageEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the LVLD will be reported.
1.3.6.1.4.1.12148.10.9.9.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
loadVoltageValue
OBJECT-TYPE
The measured value of the voltage.
1.3.6.1.4.1.12148.10.9.9.1.6Integer32read-onlycurrent
battery
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10
batteryStatus
OBJECT-TYPE
A toplevel status for the battery subsystem. The state of this reflects the status of all underlying statuses for the battery. Any change in one of the 'data monitors' in the battery subsystem will propagate up to this status indicator.
1.3.6.1.4.1.12148.10.10.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryDescription
OBJECT-TYPE
A descriptive name of the battery installed in the system.
1.3.6.1.4.1.12148.10.10.2DisplayString (SIZE(0..32))read-writecurrent
batteryReferenceVoltage
OBJECT-TYPE
The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
1.3.6.1.4.1.12148.10.10.3Integer32 (840..60417)read-writecurrent
batteryFusesStatus
OBJECT-TYPE
The state of the battery fuses/breakers can mainly be normal(1) or majorAlarm(3) and some other rarely used values .
1.3.6.1.4.1.12148.10.10.4INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryVoltage
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.5
batteryVoltageStatus
OBJECT-TYPE
The status of the measured battery voltage.
1.3.6.1.4.1.12148.10.10.5.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryVoltageDescription
OBJECT-TYPE
A textual description of the battery voltage monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.5.2DisplayString (SIZE(0..16))read-writecurrent
batteryVoltageTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.5.3Counter32accessible-for-notifycurrent
batteryVoltageAlarmEnable
OBJECT-TYPE
The measured battery voltage alarm enable/disable control
1.3.6.1.4.1.12148.10.10.5.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryVoltageValue
OBJECT-TYPE
The value of the measured battery voltage.
1.3.6.1.4.1.12148.10.10.5.5Integer32 (0..7500)read-onlycurrent
batteryVoltageMajorHighLevel
OBJECT-TYPE
The Major High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.10.10.5.6Integer32read-writecurrent
batteryVoltageMinorHighLevel
OBJECT-TYPE
The Minor High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.10.10.5.7Integer32read-writecurrent
batteryVoltageMinorLowLevel
OBJECT-TYPE
The Minor Low Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.10.10.5.8Integer32read-writecurrent
batteryVoltageMajorLowLevel
OBJECT-TYPE
The Major Low Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.10.10.5.9Integer32read-writecurrent
batteryCurrents
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.6
batteryCurrentsStatus
OBJECT-TYPE
The status of the measured battery current
1.3.6.1.4.1.12148.10.10.6.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryCurrentsDescription
OBJECT-TYPE
A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.6.2DisplayString (SIZE(0..16))read-writecurrent
batteryCurrentsTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.10.6.3Counter32accessible-for-notifycurrent
batteryCurrentsAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.6.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryCurrentsValue
OBJECT-TYPE
The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.10.10.6.5Integer32read-onlycurrent
batteryCurrentsMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.10.6.6Integer32read-writecurrent
batteryCurrentsMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.10.6.7Integer32read-writecurrent
batteryCurrentsMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.10.6.8Integer32read-writecurrent
batteryCurrentsMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.10.6.9Integer32read-writecurrent
batteryTemperatures
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.7
batteryTemperaturesStatus
OBJECT-TYPE
The state of the battery fuses/breakers can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.10.7.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryTemperaturesDescription
OBJECT-TYPE
A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.7.2DisplayString (SIZE(0..16))read-writecurrent
batteryTemperaturesTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.7.3Counter32accessible-for-notifycurrent
batteryTemperaturesAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.7.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryTemperaturesValue
OBJECT-TYPE
The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.10.10.7.5Integer32 (0..9999)read-onlycurrent
batteryTemperaturesMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.10.7.6Integer32read-writecurrent
batteryTemperaturesMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.10.7.7Integer32read-writecurrent
batteryTemperaturesMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.10.7.8Integer32read-writecurrent
batteryTemperaturesMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.10.7.9Integer32read-writecurrent
batteryTimeLeft
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.8
batteryTimeLeftStatus
OBJECT-TYPE
The status of the estimated battery remaining backup time.
1.3.6.1.4.1.12148.10.10.8.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryTimeLeftDescription
OBJECT-TYPE
A textual description of the battery discharge time monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.8.2DisplayString (SIZE(0..16))read-writecurrent
batteryTimeLeftTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.10.8.3Counter32accessible-for-notifycurrent
batteryTimeLeftAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.8.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryTimeLeftValue
OBJECT-TYPE
The estimated value of battery remaining backup time.
1.3.6.1.4.1.12148.10.10.8.5Integer32read-onlycurrent
batteryTimeLeftMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.10.8.6Integer32read-writecurrent
batteryTimeLeftMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.10.8.7Integer32read-writecurrent
batteryRemainingCapacity
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.9
batteryRemainingCapacityStatus
OBJECT-TYPE
The status of the battery remaining capacity monitor.
1.3.6.1.4.1.12148.10.10.9.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryRemainingCapacityDescription
OBJECT-TYPE
A textual description of the battery remaining capacity monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.9.2DisplayString (SIZE(0..16))read-writecurrent
batteryRemainingCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.10.9.3Counter32accessible-for-notifycurrent
batteryRemainingCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.9.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryRemainingCapacityValue
OBJECT-TYPE
Battery remaining capacity (SOC) value estimated from the latest battery test result.
1.3.6.1.4.1.12148.10.10.9.5Integer32read-onlycurrent
batteryRemainingCapacityMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.10.9.6Integer32read-writecurrent
batteryRemainingCapacityMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.10.9.7Integer32read-writecurrent
batteryUsedCapacity
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.10
batteryUsedCapacityStatus
OBJECT-TYPE
The status of the battery used capacity (DoD) monitor
1.3.6.1.4.1.12148.10.10.10.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryUsedCapacityDescription
OBJECT-TYPE
A textual description of the battery used capacity (DoD) monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.10.2DisplayString (SIZE(0..16))read-writecurrent
batteryUsedCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.10.10.3Counter32accessible-for-notifycurrent
batteryUsedCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.10.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryUsedCapacityValue
OBJECT-TYPE
This is the estimated battery used capacity (DoD).
1.3.6.1.4.1.12148.10.10.10.5Integer32read-onlycurrent
batteryUsedCapacityMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.10.10.6Integer32read-writecurrent
batteryUsedCapacityMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.10.10.7Integer32read-writecurrent
batteryTotalCapacity
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.11
batteryTotalCapacityStatus
OBJECT-TYPE
The status of the total capacity monitor.
1.3.6.1.4.1.12148.10.10.11.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryTotalCapacityDescription
OBJECT-TYPE
A textual description of the battery total capacity monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.11.2DisplayString (SIZE(0..16))read-writecurrent
batteryTotalCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.10.11.3Counter32accessible-for-notifycurrent
batteryTotalCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.11.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryTotalCapacityValue
OBJECT-TYPE
This is the estimated total battery capacity (installed Ah - SoH) value.
1.3.6.1.4.1.12148.10.10.11.5Integer32read-onlycurrent
batteryTotalCapacityMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.10.11.6Integer32read-writecurrent
batteryTotalCapacityMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.10.11.7Integer32read-writecurrent
batteryQuality
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.12
batteryQualityStatus
OBJECT-TYPE
The status of the battery quality (SoH) monitor.
1.3.6.1.4.1.12148.10.10.12.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryQualityDescription
OBJECT-TYPE
A textual description of the battery quality (SoH) monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.12.2DisplayString (SIZE(0..16))read-writecurrent
batteryQualityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.12.3Counter32accessible-for-notifycurrent
batteryQualityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.12.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryQualityValue
OBJECT-TYPE
The calculated battery quality (SoH) based on the latest battery test
1.3.6.1.4.1.12148.10.10.12.5Integer32read-onlycurrent
batteryQualityMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.10.12.6Integer32read-writecurrent
batteryQualityMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.10.12.7Integer32read-writecurrent
batteryLVBD
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.13
batteryLVBDStatus
OBJECT-TYPE
The Battery Contactor is connected, disconnected, disabled or in any other alarm condition
1.3.6.1.4.1.12148.10.10.13.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryLVBDDescription
OBJECT-TYPE
A textual description of the battery LVBD monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.13.2DisplayString (SIZE(0..16))read-writecurrent
batteryLVBDTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.10.13.3Counter32accessible-for-notifycurrent
batteryLVBDEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the LVBD will be reported.
1.3.6.1.4.1.12148.10.10.13.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryLVBDValue
OBJECT-TYPE
The measured value of the LVBD.
1.3.6.1.4.1.12148.10.10.13.5Integer32read-onlycurrent
batteryLVBDConnectVoltage
OBJECT-TYPE
The Battery Contactor's Reconnect Voltage
1.3.6.1.4.1.12148.10.10.13.6Integer32read-writecurrent
batteryLVBDDisconnectVoltage
OBJECT-TYPE
The Battery Contactor's Disconnect Voltage
1.3.6.1.4.1.12148.10.10.13.7Integer32read-writecurrent
batteryChargeCurrentLimit
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.14
batteryChargeCurrentLimitEnable
OBJECT-TYPE
Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
1.3.6.1.4.1.12148.10.10.14.1INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryChargeCurrentLimitValue
OBJECT-TYPE
Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.10.10.14.2Integer32 (0..32767)read-writecurrent
batteryBoost
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.15
batteryBoostVoltage
OBJECT-TYPE
The Voltage at which the DC System boost charges the batteries.
1.3.6.1.4.1.12148.10.10.15.1Integer32 (870..60418)read-writecurrent
batteryBoostCommand
OBJECT-TYPE
This pushbutton will start or stop a manual battery boost if the system allows it.
1.3.6.1.4.1.12148.10.10.15.2INTEGER {pushbutton(0), startboost(1), stopboost(2)}read-writecurrent
batteryBoostCurrentThreshold
OBJECT-TYPE
The boosting will terminate when the charge current drops below the BoostCurrentThreshold limit.
1.3.6.1.4.1.12148.10.10.15.3Integer32read-writecurrent
batteryBoostManualMaxDuration
OBJECT-TYPE
A protection against overcharging. When running manual boost, the boosting will always terminate at this point.
1.3.6.1.4.1.12148.10.10.15.4Integer32 (0..1440)read-writecurrent
batteryTest
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.16
batteryTestVoltage
OBJECT-TYPE
This is the battery test end voltage. The battery test will be terminated when the voltage drops below the end voltage.
1.3.6.1.4.1.12148.10.10.16.1Integer32read-writecurrent
batteryTestCommand
OBJECT-TYPE
This pushbutton will start or stop a manual battery test if the system allows it.
1.3.6.1.4.1.12148.10.10.16.2INTEGER {pushbutton(0), starttest(1), stoptest(2)}read-writecurrent
batteryTestNumberOfResults
OBJECT-TYPE
This is the number of valid battery test results stored in controller.
1.3.6.1.4.1.12148.10.10.16.3Integer32 (0..10)read-onlycurrent
batteryTestResultTable
OBJECT-TYPE
This table contains the battery test results stored in controller.
1.3.6.1.4.1.12148.10.10.16.4not-accessiblecurrent
batteryTestResultEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.16.4.1not-accessiblecurrent
batteryTestResultIndex
OBJECT-TYPE
A index pointing to one of ten possible battery test results
1.3.6.1.4.1.12148.10.10.16.4.1.1Integer32 (1..10)not-accessiblecurrent
batteryTestResultStartDateTime
OBJECT-TYPE
This is the time and date when the test started.
1.3.6.1.4.1.12148.10.10.16.4.1.2DateAndTimeread-onlycurrent
batteryTestResultDuration
OBJECT-TYPE
This is the test duration in minutes.
1.3.6.1.4.1.12148.10.10.16.4.1.3Integer32read-onlycurrent
batteryTestResultDischarged
OBJECT-TYPE
This is the discharged Ah during test.
1.3.6.1.4.1.12148.10.10.16.4.1.4Integer32read-onlycurrent
batteryTestResultQuality
OBJECT-TYPE
This is the calculated battery quality (SoH)in percentage.
1.3.6.1.4.1.12148.10.10.16.4.1.5Integer32read-onlycurrent
batteryTempComp
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.17
batteryTempCompEnable
OBJECT-TYPE
Enable (1) or Disable (0) of Battery Temperature Compensated output regulation mode
1.3.6.1.4.1.12148.10.10.17.1INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryBank
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.18
batteryBankNumberOfBanks
OBJECT-TYPE
Number of battery banks installed in system.
1.3.6.1.4.1.12148.10.10.18.1Integer32 (0..8)read-writecurrent
batteryBankTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.2not-accessiblecurrent
batteryBankEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.2.1not-accessiblecurrent
batteryBankIndex
OBJECT-TYPE
Index used for navigating the rows 1..8 of batteryBankTable
1.3.6.1.4.1.12148.10.10.18.2.1.1Integer32 (1..8)not-accessiblecurrent
batteryBankStatus
OBJECT-TYPE
The overall status of battery bank
1.3.6.1.4.1.12148.10.10.18.2.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryBankNumberOfTemperatures
OBJECT-TYPE
Number of temperature measurements in battery bank.
1.3.6.1.4.1.12148.10.10.18.2.1.3Integer32 (0..4)read-onlycurrent
batteryBankNumberOfCurrents
OBJECT-TYPE
Number of current measurements in battery bank.
1.3.6.1.4.1.12148.10.10.18.2.1.4Integer32 (0..4)read-onlycurrent
batteryBankNumberOfFuses
OBJECT-TYPE
Number of fuses installed in battery bank.
1.3.6.1.4.1.12148.10.10.18.2.1.5Integer32 (0..4)read-onlycurrent
batteryBankNumberOfSymmetries
OBJECT-TYPE
Number of symmetry measurements available in battery bank.
1.3.6.1.4.1.12148.10.10.18.2.1.6Integer32 (0..4)read-onlycurrent
batteryBankTemperatureTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.3not-accessiblecurrent
batteryBankTemperatureEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.3.1not-accessiblecurrent
batteryTemperatureIndex
OBJECT-TYPE
This index denotes which row in the temperature input table. The size of the table is defined by the batteryBankNumberOfTemp
1.3.6.1.4.1.12148.10.10.18.3.1.1Integer32 (1..4)not-accessiblecurrent
batteryTemperatureStatus
OBJECT-TYPE
The status of battery temperature monitor
1.3.6.1.4.1.12148.10.10.18.3.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryTemperatureDescription
OBJECT-TYPE
A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.18.3.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryTemperatureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.10.18.3.1.4Counter32accessible-for-notifycurrent
batteryTemperatureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.18.3.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryTemperatureValue
OBJECT-TYPE
The measured battery temperature.
1.3.6.1.4.1.12148.10.10.18.3.1.6Integer32read-onlycurrent
batteryTemperatureMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.10.18.3.1.7Integer32read-writecurrent
batteryTemperatureMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.10.18.3.1.8Integer32read-writecurrent
batteryTemperatureMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.10.18.3.1.9Integer32read-writecurrent
batteryTemperatureMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.10.18.3.1.10Integer32read-writecurrent
batteryBankCurrentTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.4not-accessiblecurrent
batteryBankCurrentEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.4.1not-accessiblecurrent
batteryCurrentIndex
OBJECT-TYPE
This index denotes which row in the current input table. The size of the table is defined by the system
1.3.6.1.4.1.12148.10.10.18.4.1.1Integer32 (1..4)not-accessiblecurrent
batteryCurrentStatus
OBJECT-TYPE
The status of battery current monitor
1.3.6.1.4.1.12148.10.10.18.4.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryCurrentDescription
OBJECT-TYPE
A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.18.4.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.10.18.4.1.4Counter32accessible-for-notifycurrent
batteryCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.18.4.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryCurrentValue
OBJECT-TYPE
The measured battery current
1.3.6.1.4.1.12148.10.10.18.4.1.6Integer32read-onlycurrent
batteryCurrentMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.10.18.4.1.7Integer32read-writecurrent
batteryCurrentMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.10.18.4.1.8Integer32read-writecurrent
batteryCurrentMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.10.18.4.1.9Integer32read-writecurrent
batteryCurrentMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.10.18.4.1.10Integer32read-writecurrent
batteryBankFuseTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.5not-accessiblecurrent
batteryBankFuseEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.5.1not-accessiblecurrent
batteryFuseIndex
OBJECT-TYPE
This index denotes which row in the fuse table. The size of the table is defined by the system
1.3.6.1.4.1.12148.10.10.18.5.1.1Integer32 (1..4)not-accessiblecurrent
batteryFuseStatus
OBJECT-TYPE
The status of battery fuse monitor
1.3.6.1.4.1.12148.10.10.18.5.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryFuseDescription
OBJECT-TYPE
A textual description of the battery fuse monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.18.5.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryFuseTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.10.18.5.1.4Counter32accessible-for-notifycurrent
batteryFuseAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.18.5.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryFuseValue
OBJECT-TYPE
The measured value of battery fuse input.
1.3.6.1.4.1.12148.10.10.18.5.1.6Integer32read-onlycurrent
batteryBankSymmetryTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.6not-accessiblecurrent
batteryBankSymmetryEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.18.6.1not-accessiblecurrent
batteryBankSymmetryIndex
OBJECT-TYPE
This index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries
1.3.6.1.4.1.12148.10.10.18.6.1.1Integer32 (1..8)not-accessiblecurrent
batteryBankSymmetryStatus
OBJECT-TYPE
The status of battery symmetry monitor
1.3.6.1.4.1.12148.10.10.18.6.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryBankSymmetryDescription
OBJECT-TYPE
A textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.18.6.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryBankSymmetryTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.18.6.1.4Counter32accessible-for-notifycurrent
batteryBankSymmetryAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.18.6.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryBankSymmetryMeasureValue
OBJECT-TYPE
The measured battery symmetry voltage in battery monitor.
1.3.6.1.4.1.12148.10.10.18.6.1.6Integer32read-onlycurrent
batteryBankSymmetryDeltaValue
OBJECT-TYPE
The measured battery symmetry delta voltage in battery monitor.
1.3.6.1.4.1.12148.10.10.18.6.1.7Integer32read-onlycurrent
batteryBankSymmetryMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.10.18.6.1.8Integer32read-writecurrent
batteryBankSymmetryMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.10.18.6.1.9Integer32read-writecurrent
batteryMonitors
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.19
batteryMonitorsNumberOfUnits
OBJECT-TYPE
The number of battery monitor installed in system.
1.3.6.1.4.1.12148.10.10.19.1Integer32read-writecurrent
batteryMonitorsTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.2not-accessiblecurrent
batteryMonitorsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.2.1not-accessiblecurrent
batteryMonitorIndex
OBJECT-TYPE
Index used for navigating the rows 1..8 of batteryMonitorsTable
1.3.6.1.4.1.12148.10.10.19.2.1.1Integer32 (1..8)not-accessiblecurrent
batteryMonitorNumberOfTemperatures
OBJECT-TYPE
The number of temperature measurements in battery monitor.
1.3.6.1.4.1.12148.10.10.19.2.1.2Integer32 (0..4)read-onlycurrent
batteryMonitorNumberOfCurrents
OBJECT-TYPE
The number of current measurements in battery monitor.
1.3.6.1.4.1.12148.10.10.19.2.1.3Integer32 (0..4)read-onlycurrent
batteryMonitorNumberOfFuses
OBJECT-TYPE
The number of fuse measurements in battery monitor.
1.3.6.1.4.1.12148.10.10.19.2.1.4Integer32 (0..4)read-onlycurrent
batteryMonitorNumberOfSymmetries
OBJECT-TYPE
The number of symmetry measurements in battery monitor.
1.3.6.1.4.1.12148.10.10.19.2.1.5Integer32 (0..4)read-onlycurrent
batteryMonitorTemperatureTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.3not-accessiblecurrent
batteryMonitorTemperatureEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.3.1not-accessiblecurrent
batteryMonitorTemperatureIndex
OBJECT-TYPE
This index denotes which row in the temperature input table. The size of the table is defined by the batteryMonitorNumberOfTemperatures
1.3.6.1.4.1.12148.10.10.19.3.1.1Integer32 (1..4)not-accessiblecurrent
batteryMonitorTemperatureStatus
OBJECT-TYPE
The status of battery temperature monitor
1.3.6.1.4.1.12148.10.10.19.3.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryMonitorTemperatureDescription
OBJECT-TYPE
A textual description of the battery monitor temperature. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.19.3.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryMonitorTemperatureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.19.3.1.4Counter32accessible-for-notifycurrent
batteryMonitorTemperatureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.19.3.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryMonitorTemperatureValue
OBJECT-TYPE
The measured battery temperature in battery monitor.
1.3.6.1.4.1.12148.10.10.19.3.1.6Integer32read-onlycurrent
batteryMonitorTemperatureMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.10.19.3.1.7Integer32read-writecurrent
batteryMonitorTemperatureMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.10.19.3.1.8Integer32read-writecurrent
batteryMonitorTemperatureMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.10.19.3.1.9Integer32read-writecurrent
batteryMonitorTemperatureMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.10.19.3.1.10Integer32read-writecurrent
batteryMonitorCurrentTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.4not-accessiblecurrent
batteryMonitorCurrentEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.4.1not-accessiblecurrent
batteryMonitorCurrentIndex
OBJECT-TYPE
This index denotes which row in the current input table. The size of the table is defined by the batteryMonitorNumberOfCurrents
1.3.6.1.4.1.12148.10.10.19.4.1.1Integer32 (1..4)not-accessiblecurrent
batteryMonitorCurrentStatus
OBJECT-TYPE
The status of battery current monitor
1.3.6.1.4.1.12148.10.10.19.4.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryMonitorCurrentDescription
OBJECT-TYPE
A textual description of the battery monitor current. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.19.4.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryMonitorCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.19.4.1.4Counter32accessible-for-notifycurrent
batteryMonitorCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.19.4.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryMonitorCurrentValue
OBJECT-TYPE
The measured battery current in battery monitor.
1.3.6.1.4.1.12148.10.10.19.4.1.6Integer32read-onlycurrent
batteryMonitorCurrentMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.10.19.4.1.7Integer32read-writecurrent
batteryMonitorCurrentMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.10.19.4.1.8Integer32read-writecurrent
batteryMonitorCurrentMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.10.19.4.1.9Integer32read-writecurrent
batteryMonitorCurrentMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.10.19.4.1.10Integer32read-writecurrent
batteryMonitorFuseTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.5not-accessiblecurrent
batteryMonitorFuseEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.5.1not-accessiblecurrent
batteryMonitorFuseIndex
OBJECT-TYPE
This index denotes which row in the fuse table. The size of the table is defined by the batteryMonitorNumberOfFuses
1.3.6.1.4.1.12148.10.10.19.5.1.1Integer32 (1..4)not-accessiblecurrent
batteryMonitorFuseStatus
OBJECT-TYPE
The status of battery fuse monitor
1.3.6.1.4.1.12148.10.10.19.5.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryMonitorFuseDescription
OBJECT-TYPE
A textual description of the battery monitor fuse. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.19.5.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryMonitorFuseTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.19.5.1.4Counter32accessible-for-notifycurrent
batteryMonitorFuseAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.19.5.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryMonitorFuseValue
OBJECT-TYPE
The measured value of battery fuse in battery monitor.
1.3.6.1.4.1.12148.10.10.19.5.1.6Integer32read-onlycurrent
batteryMonitorSymmetryTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.6not-accessiblecurrent
batteryMonitorSymmetryEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.19.6.1not-accessiblecurrent
batteryMonitorSymmetryIndex
OBJECT-TYPE
This index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries
1.3.6.1.4.1.12148.10.10.19.6.1.1Integer32 (1..8)not-accessiblecurrent
batteryMonitorSymmetryStatus
OBJECT-TYPE
The status of battery symmetry monitor
1.3.6.1.4.1.12148.10.10.19.6.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryMonitorSymmetryDescription
OBJECT-TYPE
A textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.19.6.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryMonitorSymmetryTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.19.6.1.4Counter32accessible-for-notifycurrent
batteryMonitorSymmetryAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.19.6.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryMonitorSymmetryMeasureValue
OBJECT-TYPE
The measured battery symmetry voltage in battery monitor.
1.3.6.1.4.1.12148.10.10.19.6.1.6Integer32read-onlycurrent
batteryMonitorSymmetryDeltaValue
OBJECT-TYPE
The measured battery symmetry delta voltage in battery monitor.
1.3.6.1.4.1.12148.10.10.19.6.1.7Integer32read-onlycurrent
batteryMonitorSymmetryMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.10.19.6.1.8Integer32read-writecurrent
batteryMonitorSymmetryMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.10.19.6.1.9Integer32read-writecurrent
batteryEnergyLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.20
batteryEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered to/from battery.
1.3.6.1.4.1.12148.10.10.20.1Integer32read-onlycurrent
batteryEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in battery hourly energy log.
1.3.6.1.4.1.12148.10.10.20.2Integer32 (0..52)read-onlycurrent
batteryEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly energy log of battery.
1.3.6.1.4.1.12148.10.10.20.3not-accessiblecurrent
batteryEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.20.3.1not-accessiblecurrent
batteryEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.10.20.3.1.1Integer32 (1..52)not-accessiblecurrent
batteryEnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.10.20.3.1.2Integer32read-onlycurrent
batteryEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in battery daily energy log.
1.3.6.1.4.1.12148.10.10.20.4Integer32 (0..52)read-onlycurrent
batteryEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily energy log of battery.
1.3.6.1.4.1.12148.10.10.20.5not-accessiblecurrent
batteryEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.20.5.1not-accessiblecurrent
batteryEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.10.20.5.1.1Integer32 (1..52)not-accessiblecurrent
batteryEnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day.
1.3.6.1.4.1.12148.10.10.20.5.1.2Integer32read-onlycurrent
batteryEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in battery weekly energy log.
1.3.6.1.4.1.12148.10.10.20.6Integer32 (0..52)read-onlycurrent
batteryEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly energy log of battery.
1.3.6.1.4.1.12148.10.10.20.7not-accessiblecurrent
batteryEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.20.7.1not-accessiblecurrent
batteryEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.10.20.7.1.1Integer32 (1..52)not-accessiblecurrent
batteryEnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.10.20.7.1.2Integer32read-onlycurrent
batteryCycleLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.21
batteryCycleLogTotalCycles
OBJECT-TYPE
This is the total number of battery discharge cycles.
1.3.6.1.4.1.12148.10.10.21.1Integer32read-onlycurrent
batteryCycleLogDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in daily battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.2Integer32 (0..52)read-onlycurrent
batteryCycleLogDaysTable
OBJECT-TYPE
This table contains daily battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.3not-accessiblecurrent
batteryCycleLogDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.21.3.1not-accessiblecurrent
batteryCycleLogDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryCycleLogLastDaysTable
1.3.6.1.4.1.12148.10.10.21.3.1.1Integer32 (1..52)not-accessiblecurrent
batteryCycleLogDaysValue
OBJECT-TYPE
Number of discharge cycles logged every day.
1.3.6.1.4.1.12148.10.10.21.3.1.2Integer32read-onlycurrent
batteryCycleLogWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in weeky battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.4Integer32 (0..52)read-onlycurrent
batteryCycleLogWeeksTable
OBJECT-TYPE
This table contains weekly battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.5not-accessiblecurrent
batteryCycleLogWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.21.5.1not-accessiblecurrent
batteryCycleLogWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable
1.3.6.1.4.1.12148.10.10.21.5.1.1Integer32 (1..52)not-accessiblecurrent
batteryCycleLogWeeksValue
OBJECT-TYPE
Number of discharge cycles logged every week.
1.3.6.1.4.1.12148.10.10.21.5.1.2Integer32read-onlycurrent
batteryCycleLogMonthsNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in monthly battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.6Integer32 (0..52)read-onlycurrent
batteryCycleLogMonthsTable
OBJECT-TYPE
This table contains monthly battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.7not-accessiblecurrent
batteryCycleLogMonthsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.10.21.7.1not-accessiblecurrent
batteryCycleLogMonthsIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryCycleLogLastMonthTable
1.3.6.1.4.1.12148.10.10.21.7.1.1Integer32 (1..52)not-accessiblecurrent
batteryCycleLogMonthsValue
OBJECT-TYPE
Number of discharge cycles logged every month.
1.3.6.1.4.1.12148.10.10.21.7.1.2Integer32read-onlycurrent
batteryEqualize
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.22
batteryEqualizeVoltage
OBJECT-TYPE
The Voltage at which the DC System equalize charges the batteries.
1.3.6.1.4.1.12148.10.10.22.1Integer32 (870..60418)read-writecurrent
batteryEqualizeCommand
OBJECT-TYPE
This pushbutton will start or stop a manual battery equalize if the system allows it.
1.3.6.1.4.1.12148.10.10.22.2INTEGER {pushbutton(0), startequalize(1), stopequalize(2)}read-writecurrent
batteryEqualizeCurrentThreshold
OBJECT-TYPE
The equalizing will terminate when the charge current drops below the EqualizeCurrentThreshold limit.
1.3.6.1.4.1.12148.10.10.22.3Integer32read-writecurrent
batteryEqualizeManualMaxDuration
OBJECT-TYPE
A protection against overcharging. When running manual equalize, the boosting will always terminate at this point.
1.3.6.1.4.1.12148.10.10.22.4Integer32 (0..1440)read-writecurrent
batteryAhCharged
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.23
batteryAhChargedStatus
OBJECT-TYPE
The status of the battery ah charged monitor.
1.3.6.1.4.1.12148.10.10.23.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryAhChargedDescription
OBJECT-TYPE
A textual description of the battery ah charged monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.23.2DisplayString (SIZE(0..16))read-writecurrent
batteryAhChargedTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.23.3Counter32accessible-for-notifycurrent
batteryAhChargedAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.23.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryAhChargedValue
OBJECT-TYPE
The calculated battery ah (x100) charged value.
1.3.6.1.4.1.12148.10.10.23.5Integer32read-onlycurrent
batteryAhChargedMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.10.23.6Integer32read-writecurrent
batteryAhChargedMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.10.23.7Integer32read-writecurrent
batteryAhDischarged
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.10.24
batteryAhDischargedStatus
OBJECT-TYPE
The status of the battery ah discharged monitor.
1.3.6.1.4.1.12148.10.10.24.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryAhDischargedDescription
OBJECT-TYPE
A textual description of the battery ah discharged monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.24.2DisplayString (SIZE(0..16))read-writecurrent
batteryAhDischargedTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.10.24.3Counter32accessible-for-notifycurrent
batteryAhDischargedAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.24.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryAhDischargedValue
OBJECT-TYPE
The calculated battery ah (x100) discharged value.
1.3.6.1.4.1.12148.10.10.24.5Integer32read-onlycurrent
batteryAhDischargedMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.10.24.6Integer32read-writecurrent
batteryAhDischargedMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.10.24.7Integer32read-writecurrent
inputs
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.11
inputControlUnitsTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.11.1not-accessiblecurrent
inputControlUnitsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.11.1.1not-accessiblecurrent
inputControlUnitIndex
OBJECT-TYPE
Index used for navigating the rows of inputControlUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.11.1.1.1Integer32 (1..14)not-accessiblecurrent
inputControlUnitNumberOfInputs
OBJECT-TYPE
Number of programmable inputs available in controller.
1.3.6.1.4.1.12148.10.11.1.1.2Integer32 (0..8)read-onlycurrent
inputControlUnitInputTable
OBJECT-TYPE
This table contains the status of the programmable inputs for Control Units.
1.3.6.1.4.1.12148.10.11.2not-accessiblecurrent
inputControlUnitInputEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.11.2.1not-accessiblecurrent
inputControlUnitInputIndex
OBJECT-TYPE
Index used for navigating the rows of inputControlUnitInputTable The size of the table is defined by the inputControlUnitNumberOfInputs
1.3.6.1.4.1.12148.10.11.2.1.1Integer32 (1..10)not-accessiblecurrent
inputControlUnitInputStatus
OBJECT-TYPE
Programmable input status.
1.3.6.1.4.1.12148.10.11.2.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
inputControlUnitInputDescription
OBJECT-TYPE
A textual description of the programmable input. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.11.2.1.3DisplayString (SIZE(0..16))read-writecurrent
inputControlUnitInputTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.11.2.1.4Counter32accessible-for-notifycurrent
inputControlUnitInputAlarmEnable
OBJECT-TYPE
This will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state
1.3.6.1.4.1.12148.10.11.2.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
inputControlUnitInputValue
OBJECT-TYPE
The inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current or a Boolean value. Note: This value can only be set for virtual input on SP2 master or Smartpack S. When this value is set to '0', the input is deactivated; When this value is set to '1', the input is activated; if set to any other value, an Inconsistent Value error will be generated.
1.3.6.1.4.1.12148.10.11.2.1.6Integer32read-writecurrent
inputControlUnitInputConfiguration
OBJECT-TYPE
Configuration of the input type. Configurations available for different controllers are as follows: SP2 Master(clock, virtual), SP2 Basic(normally open, normally closed),Compack(normally open, normally closed, diode matrix, voltage, clock), SmartpackS(normally open, normally closed,voltage)
1.3.6.1.4.1.12148.10.11.2.1.7INTEGER {normallyOpen(1), normallyClosed(2), diodeMatrix(3), voltage(4), clock(5), virtual(6)}read-writecurrent
inputIoUnitsTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.11.3not-accessiblecurrent
inputIoUnitsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.11.3.1not-accessiblecurrent
inputIoUnitIndex
OBJECT-TYPE
Index used for navigating the rows of inputIoUnitsTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.11.3.1.1Integer32 (1..14)not-accessiblecurrent
inputIoUnitNumberOfInputs
OBJECT-TYPE
Number of programmable inputs available in IO unit.
1.3.6.1.4.1.12148.10.11.3.1.2Integer32 (0..8)read-onlycurrent
inputIoUnitProgInputTable
OBJECT-TYPE
This table contains the status of the programmable inputs for I/O monitor units. .
1.3.6.1.4.1.12148.10.11.4not-accessiblecurrent
inputIoUnitProgInputEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.11.4.1not-accessiblecurrent
inputIoUnitProgInputIndex
OBJECT-TYPE
The Index to the Input of the selected I/O monitor unit. Or the input number if you like.
1.3.6.1.4.1.12148.10.11.4.1.1Integer32 (1..6)not-accessiblecurrent
inputIoUnitProgInputStatus
OBJECT-TYPE
Programmable input status.
1.3.6.1.4.1.12148.10.11.4.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
inputIoUnitProgInputDescription
OBJECT-TYPE
A textual description of the programmable input in IO unit. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.11.4.1.3DisplayString (SIZE(0..16))read-writecurrent
inputIoUnitProgInputTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.11.4.1.4Counter32accessible-for-notifycurrent
inputIoUnitProgInputAlarmEnable
OBJECT-TYPE
This will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state
1.3.6.1.4.1.12148.10.11.4.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
inputIoUnitProgInputValue
OBJECT-TYPE
The inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current or a Boolean value.
1.3.6.1.4.1.12148.10.11.4.1.6Integer32read-onlycurrent
inputIoUnitProgInputConfiguration
OBJECT-TYPE
Configuration of the input type. Configurations available for IO unit are normally open, normally closed, diode matrix, voltage and clock. Note: If an input is set to 'clock', it can not be configurated to 'normally open', 'normally closed' and 'diode matrix' directly, it has to be configurated to 'voltage' first.
1.3.6.1.4.1.12148.10.11.4.1.7INTEGER {normallyOpen(1), normallyClosed(2), diodeMatrix(3), voltage(4), clock(5)}read-writecurrent
outputs
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.12
outputControlUnitTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.12.1not-accessiblecurrent
outputControlUnitEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.12.1.1not-accessiblecurrent
outputControlUnitIndex
OBJECT-TYPE
Index used for navigating the rows of outputControlUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.12.1.1.1Integer32 (1..14)not-accessiblecurrent
outputControlUnitNumberOfOutputs
OBJECT-TYPE
Number of outputs available in controller.
1.3.6.1.4.1.12148.10.12.1.1.2Integer32 (0..8)read-onlycurrent
outputControlUnitOutputTable
OBJECT-TYPE
This table contains the status of the outputs for Control Units.
1.3.6.1.4.1.12148.10.12.2not-accessiblecurrent
outputControlUnitOutputEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.12.2.1not-accessiblecurrent
outputControlUnitOutputIndex
OBJECT-TYPE
Index used for navigating the rows of outputControlUnitoutputTable The size of the table is defined by the outputControlUnitNumberOfOutputs
1.3.6.1.4.1.12148.10.12.2.1.1Integer32 (1..16)not-accessiblecurrent
outputControlUnitOutputStatus
OBJECT-TYPE
General output relays may be 'energized' or 'not energized'. 'energized' and 'not energized' correspond to normal and alarm condition respectively for normally activated configuration. Latched contactors may have values 'disconnected' or 'connected'
1.3.6.1.4.1.12148.10.12.2.1.2INTEGER {notenergized(0), energized(1), disconnected(2), connected(3)}read-onlycurrent
outputControlUnitOutputDescription
OBJECT-TYPE
A textual description of the output. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.12.2.1.3DisplayString (SIZE(0..16))read-writecurrent
outputIoUnitTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.12.3not-accessiblecurrent
outputIoUnitEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.12.3.1not-accessiblecurrent
outputIoUnitIndex
OBJECT-TYPE
Index used for navigating the rows of outputIoUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.12.3.1.1Integer32 (1..14)not-accessiblecurrent
outputIoUnitNumberOfOutputs
OBJECT-TYPE
Number of outputs available in IO unit.
1.3.6.1.4.1.12148.10.12.3.1.2Integer32 (0..8)read-onlycurrent
outputIoUnitOutputTable
OBJECT-TYPE
This table contains the status of the outputs for IO Units.
1.3.6.1.4.1.12148.10.12.4not-accessiblecurrent
outputIoUnitOutputEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.12.4.1not-accessiblecurrent
outputIoUnitOutputIndex
OBJECT-TYPE
Index used for navigating the rows of outputIOUnitOutputTable The size of the table is defined by the outputIOUnitNumberOfOutputs
1.3.6.1.4.1.12148.10.12.4.1.1Integer32 (1..14)not-accessiblecurrent
outputIoUnitOutputStatus
OBJECT-TYPE
General output relays may be 'energized' or 'not energized'. Latched contactors may have values 'disconnected' or 'connected'
1.3.6.1.4.1.12148.10.12.4.1.2INTEGER {notenergized(0), energized(1), disconnected(2), connected(3)}read-onlycurrent
outputIoUnitOutputDescription
OBJECT-TYPE
A textual description of the output in IO unit. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.12.4.1.3DisplayString (SIZE(0..16))read-writecurrent
controlSystem
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13
controlSystemStatus
OBJECT-TYPE
The overall status of control system subsystem
1.3.6.1.4.1.12148.10.13.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
controlSystemClock
OBJECT-TYPE
This is the system time.
1.3.6.1.4.1.12148.10.13.2DateAndTime (SIZE(8..11))read-writecurrent
controlSystemNumberOfControlUnits
OBJECT-TYPE
Total number of main controllers (SP2 Master, SP2 Basic Ind, SP2 Basic, Compack, Smartpack S, Smartpack)
1.3.6.1.4.1.12148.10.13.3Integer32 (1..14)read-writecurrent
snmp
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.4
snmpSendOffTraps
OBJECT-TYPE
When this is enabled, a trap is sent when a alarm condition goes off .
1.3.6.1.4.1.12148.10.13.4.1INTEGER {disabled(0), enabled(1)}read-writecurrent
snmpTrapRepeatRate
OBJECT-TYPE
The time between every repeated trap when an alarm condition is on. To turn repetetive traps off, set to zero. Can be 0 to 1440 minutes i.e 24 hours.
1.3.6.1.4.1.12148.10.13.4.2Integer32 (0..1440)read-writecurrent
snmpHeartBeatTrapRepeatRate
OBJECT-TYPE
The time between every heartbeat trap when an alarm condition is on. To turn heartbeat traps off, set to zero. Can be 0 to 1440 minutes i.e 24 hours.
1.3.6.1.4.1.12148.10.13.4.3Integer32 (0..1440)read-writecurrent
snmpInhibitTraps
OBJECT-TYPE
When this is enabled, no trap is sent regardless of alarm conditions.
1.3.6.1.4.1.12148.10.13.4.4INTEGER {disabled(0), enabled(1)}read-writecurrent
controlSystemResetManualAlarms
OBJECT-TYPE
Reset manual alarms and put buzzer into silence.
1.3.6.1.4.1.12148.10.13.5INTEGER {pushbutton(0), resetalarm(1)}read-writecurrent
controlSystemResetNumberOfModules
OBJECT-TYPE
If set to '1', the number of modules (rectifier, solar charger, wind charger, control units, etc.) will be reset, and only those modules communicating are counted.
1.3.6.1.4.1.12148.10.13.6INTEGER {pushbutton(0), resetnumber(1)}read-writecurrent
controlSystemIoUnits
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.7
controlSystemIoUnitsNumberOfUnits
OBJECT-TYPE
This is the number of IO units installed in the system.
1.3.6.1.4.1.12148.10.13.7.1Integer32 (0..14)read-writecurrent
controlSystemIoUnitsTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.7.2not-accessiblecurrent
controlSystemIoUnitsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.7.2.1not-accessiblecurrent
controlSystemIoUnitIndex
OBJECT-TYPE
Index used for navigating the rows of controlSystemIoUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.13.7.2.1.1Integer32 (1..14)not-accessiblecurrent
controlSystemIoUnitNumberOfTemperatures
OBJECT-TYPE
Number of temperature measurements available in IO unit
1.3.6.1.4.1.12148.10.13.7.2.1.2Integer32 (0..4)read-onlycurrent
controlSystemIoUnitNumberOfFans
OBJECT-TYPE
Number of fan measurements available in IO unit
1.3.6.1.4.1.12148.10.13.7.2.1.3Integer32 (0..4)read-onlycurrent
controlSystemIoUnitTemperatureTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.7.3not-accessiblecurrent
controlSystemIoUnitTemperatureEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.7.3.1not-accessiblecurrent
controlSystemIoUnitTemperatureIndex
OBJECT-TYPE
Index used for navigating the rows of controlSystemIoUnitTemperatureTable The size of the table is defined by the controlSystemIoUnitNumberOfTemperatures
1.3.6.1.4.1.12148.10.13.7.3.1.1Integer32 (1..2)not-accessiblecurrent
controlSystemIoUnitTemperatureStatus
OBJECT-TYPE
The status of temperature monitor
1.3.6.1.4.1.12148.10.13.7.3.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
controlSystemIoUnitTemperatureDescription
OBJECT-TYPE
A textual description of the temperature monitor in control system. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.7.3.1.3DisplayString (SIZE(0..16))read-writecurrent
controlSystemIoUnitTemperatureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.13.7.3.1.4Counter32accessible-for-notifycurrent
controlSystemIoUnitTemperatureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.7.3.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
controlSystemIoUnitTemperatureValue
OBJECT-TYPE
The measured temperature value.
1.3.6.1.4.1.12148.10.13.7.3.1.6Integer32read-onlycurrent
controlSystemIoUnitTemperatureMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.13.7.3.1.7Integer32read-writecurrent
controlSystemIoUnitTemperatureMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.13.7.3.1.8Integer32read-writecurrent
controlSystemIoUnitTemperatureMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.13.7.3.1.9Integer32read-writecurrent
controlSystemIoUnitTemperatureMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.13.7.3.1.10Integer32read-writecurrent
controlSystemIoUnitFanTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.7.4not-accessiblecurrent
controlSystemIoUnitFanEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.7.4.1not-accessiblecurrent
controlSystemIoUnitFanIndex
OBJECT-TYPE
Index used for navigating the rows 1..2 of ioUnitFan Table
1.3.6.1.4.1.12148.10.13.7.4.1.1Integer32 (1..2)not-accessiblecurrent
controlSystemIoUnitFanSpeedValue
OBJECT-TYPE
The measured fan speed
1.3.6.1.4.1.12148.10.13.7.4.1.2Integer32read-onlycurrent
controlSystemIoUnitFanSpeedDeviation
OBJECT-TYPE
The measured fan speed deviation
1.3.6.1.4.1.12148.10.13.7.4.1.3Integer32read-onlycurrent
controlSystemIoUnitFanControl
OBJECT-TYPE
Fan speed control value in percentage
1.3.6.1.4.1.12148.10.13.7.4.1.4Integer32read-onlycurrent
controlSystemInventory
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.8
controlUnitNumberOfUnits
OBJECT-TYPE
Total number of control units installed in system.
1.3.6.1.4.1.12148.10.13.8.1Integer32 (1..254)read-onlycurrent
controlUnitTable
OBJECT-TYPE
A table containing an inventory listing. Each row represent one of the system hardware unit that is connected to the can bus. These units are system controllers, battery monitors, I/O units, AC Mains Monitor boxes and load monitors. Due to the system architechture the tables index are not contiguous. Each unit type har its own address range on the can bus. All unit types except the system controller may contain from 0 to 14 units. The system controlller can never be zero. Then there is no powersystem.
1.3.6.1.4.1.12148.10.13.8.2not-accessiblecurrent
controlUnitEntry
OBJECT-TYPE
One row in the table containing all hardware units connected to the canbus.
1.3.6.1.4.1.12148.10.13.8.2.1not-accessiblecurrent
controlUnitIndex
OBJECT-TYPE
Index used for navigating the rows of controlUnitTable The size of the table is defined by the controlUnitNumberOfUnits
1.3.6.1.4.1.12148.10.13.8.2.1.1Integer32 (1..254)not-accessiblecurrent
controlUnitDescription
OBJECT-TYPE
A textual description of the control unit
1.3.6.1.4.1.12148.10.13.8.2.1.2DisplayString (SIZE(0..32))read-onlycurrent
controlUnitStatus
OBJECT-TYPE
The overall status of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.3INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
controlUnitSerialNumber
OBJECT-TYPE
Serial number of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.4DisplayString (SIZE(0..12))read-onlycurrent
controlUnitHwPartNumber
OBJECT-TYPE
Hardware part number of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.5DisplayString (SIZE(0..12))read-onlycurrent
controlUnitHwVersion
OBJECT-TYPE
Hardware version of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.6DisplayString (SIZE(0..20))read-onlycurrent
controlUnitSwPartNumber
OBJECT-TYPE
Software part number of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.7DisplayString (SIZE(0..12))read-onlycurrent
controlUnitSwVersion
OBJECT-TYPE
Software version of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.8DisplayString (SIZE(0..20))read-onlycurrent
currentMonitors
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.9
currentMonitorsNumberOfUnits
OBJECT-TYPE
This is the number of current monitors installed in the system.
1.3.6.1.4.1.12148.10.13.9.1Integer32 (0..14)read-writecurrent
currentMonitorsTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.2not-accessiblecurrent
currentMonitorsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.2.1not-accessiblecurrent
currentMonitorIndex
OBJECT-TYPE
Index used for navigating the rows of currentMonitorsTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.13.9.2.1.1Integer32 (1..14)not-accessiblecurrent
currentMonitorType
OBJECT-TYPE
This shows if the current monitor is configured as standard load monitor (1), load current monitor (2), rectifier current monitor (3), dcdc current monitor (4), solar current monitor (5), wind current monitor (6) or fuel cell current monitor (7).
1.3.6.1.4.1.12148.10.13.9.2.1.2INTEGER {stdLoadMonitor(1), loadCurrMonitor(2), rectCurrMonitor(3), dcdcCurrMonitor(4), solarCurrMonitor(5), windCurrMonitor(6), fuelcellCurrMonitor(7)}read-onlycurrent
currentMonitorId
OBJECT-TYPE
This is the unit index for each current monitor type.
1.3.6.1.4.1.12148.10.13.9.2.1.3Integer32read-onlycurrent
currentMonitorNumberOfFuses
OBJECT-TYPE
Number of fuse measurements in current monitor.
1.3.6.1.4.1.12148.10.13.9.2.1.4Integer32 (0..8)read-onlycurrent
currentMonitorNumberOfCurrents
OBJECT-TYPE
Number of current measurements in current monitor.
1.3.6.1.4.1.12148.10.13.9.2.1.5Integer32 (0..8)read-onlycurrent
currentMonitorFuseTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.3not-accessiblecurrent
currentMonitorFuseEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.3.1not-accessiblecurrent
currentMonitorFuseIndex
OBJECT-TYPE
Index used for navigating the rows of currentMonitorFuseTable The size of the table is defined by the currentMonitorNumberOfFuses
1.3.6.1.4.1.12148.10.13.9.3.1.1Integer32 (1..8)not-accessiblecurrent
currentMonitorFuseStatus
OBJECT-TYPE
The status of fuse in current monitor
1.3.6.1.4.1.12148.10.13.9.3.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
currentMonitorFuseDescription
OBJECT-TYPE
A textual description of the fuse monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.9.3.1.3DisplayString (SIZE(1..16))read-writecurrent
currentMonitorFuseTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.13.9.3.1.4Counter32accessible-for-notifycurrent
currentMonitorFuseAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.9.3.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
currentMonitorFuseValue
OBJECT-TYPE
The measured fuse value.
1.3.6.1.4.1.12148.10.13.9.3.1.6Integer32read-onlycurrent
currentMonitorCurrentTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.4not-accessiblecurrent
currentMonitorCurrentEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.4.1not-accessiblecurrent
currentMonitorCurrentIndex
OBJECT-TYPE
Index used for navigating the rows of currentMonitorCurrentTable The size of the table is defined by the currentMonitorNumberOfCurrents
1.3.6.1.4.1.12148.10.13.9.4.1.1Integer32 (1..8)not-accessiblecurrent
currentMonitorCurrentStatus
OBJECT-TYPE
The status of current in current monitor
1.3.6.1.4.1.12148.10.13.9.4.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
currentMonitorCurrentDescription
OBJECT-TYPE
A textual description of the current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.9.4.1.3DisplayString (SIZE(0..16))read-writecurrent
currentMonitorCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.13.9.4.1.4Counter32accessible-for-notifycurrent
currentMonitorCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.9.4.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
currentMonitorCurrentValue
OBJECT-TYPE
The measured current value.
1.3.6.1.4.1.12148.10.13.9.4.1.6Integer32read-onlycurrent
currentMonitorCurrentMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.9.4.1.7Integer32read-writecurrent
currentMonitorCurrentMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.13.9.4.1.8Integer32read-writecurrent
currentMonitorEnergyLogAccumulatedTable
OBJECT-TYPE
This table contains the accumulated energy consumption measured in current monitor
1.3.6.1.4.1.12148.10.13.9.5not-accessiblecurrent
currentMonitorEnergyLogAccumulatedEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.5.1not-accessiblecurrent
currentMonitorEnergyLogAccumulated
OBJECT-TYPE
The accumulated energy consumption value
1.3.6.1.4.1.12148.10.13.9.5.1.1Integer32read-onlycurrent
currentMonitorEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in hourly energy log
1.3.6.1.4.1.12148.10.13.9.6Integer32 (0..52)read-onlycurrent
currentMonitorEnergyLogLastHoursTable
OBJECT-TYPE
This table contains energy consumption values logged every hour in current monitor.
1.3.6.1.4.1.12148.10.13.9.7not-accessiblecurrent
currentMonitorEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.7.1not-accessiblecurrent
currentMonitorEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.13.9.7.1.1Integer32 (1..52)not-accessiblecurrent
currentMonitorEnergyLogLastHoursValue
OBJECT-TYPE
Energy consumption value logged every hour in current monitor.
1.3.6.1.4.1.12148.10.13.9.7.1.2Integer32read-onlycurrent
currentMonitorEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in daily energy log
1.3.6.1.4.1.12148.10.13.9.8Integer32 (0..52)read-onlycurrent
currentMonitorEnergyLogLastDaysTable
OBJECT-TYPE
This table contains energy consumption values logged every day in current monitor.
1.3.6.1.4.1.12148.10.13.9.9not-accessiblecurrent
currentMonitorEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.9.1not-accessiblecurrent
currentMonitorEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.13.9.9.1.1Integer32 (1..52)not-accessiblecurrent
currentMonitorEnergyLogLastDaysValue
OBJECT-TYPE
Energy consumption value logged every day in current monitor.
1.3.6.1.4.1.12148.10.13.9.9.1.2Integer32read-onlycurrent
currentMonitorEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in weekly energy log
1.3.6.1.4.1.12148.10.13.9.10Integer32 (0..52)read-onlycurrent
currentMonitorEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains energy consumption values logged every week in current monitor.
1.3.6.1.4.1.12148.10.13.9.11not-accessiblecurrent
currentMonitorEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.9.11.1not-accessiblecurrent
currentMonitorEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.13.9.11.1.1Integer32 (1..52)not-accessiblecurrent
currentMonitorEnergyLogLastWeeksValue
OBJECT-TYPE
Energy consumption value logged every week in current monitor.
1.3.6.1.4.1.12148.10.13.9.11.1.2Integer32read-onlycurrent
flexiMonitors
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.10
flexiMonitorsNumberOfUnits
OBJECT-TYPE
This is the number of fleximonitors installed in the system.
1.3.6.1.4.1.12148.10.13.10.1Integer32 (0..14)read-writecurrent
flexiMonitorsTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.10.2not-accessiblecurrent
flexiMonitorsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.10.2.1not-accessiblecurrent
flexiMonitorIndex
OBJECT-TYPE
Index used for navigating the rows of flexiMonitorsTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.13.10.2.1.1Integer32 (1..14)not-accessiblecurrent
flexiMonitorType
OBJECT-TYPE
This shows if the fleximonitor is configured as battery monitor (1), load monitor (2), rectifier monitor (3), controller monitor(4), dcdc monitor (5), solar monitor (6), wind monitor (7) or fuel cell monitor 8).
1.3.6.1.4.1.12148.10.13.10.2.1.2INTEGER {battFlexiMonitor(1), loadFlexiMonitor(2), rectFlexiMonitor(3), contrFlexiMonitor(4), dcdcFlexiMonitor(5), solarFlexiMonitor(6), windFlexiMonitor(7), fuelcFlexiMonitor(8)}read-onlycurrent
flexiMonitorId
OBJECT-TYPE
This is the unit index for each fleximonitor type.
1.3.6.1.4.1.12148.10.13.10.2.1.3Integer32read-onlycurrent
flexiMonitorNumberOfInputs
OBJECT-TYPE
Number of inputs in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.2.1.4Integer32 (0..8)read-onlycurrent
flexiMonitorNumberOfOutputs
OBJECT-TYPE
Number of outputs in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.2.1.5Integer32read-onlycurrent
flexiMonitorInputTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.10.3not-accessiblecurrent
flexiMonitorInputEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.10.3.1not-accessiblecurrent
flexiMonitorInputIndex
OBJECT-TYPE
Index used for navigating the rows of flexiMonitorInputTable The size of the table is defined by the flexiMonitorNumberOfInputs
1.3.6.1.4.1.12148.10.13.10.3.1.1Integer32 (1..16)not-accessiblecurrent
flexiMonitorInputStatus
OBJECT-TYPE
Programmable input status.
1.3.6.1.4.1.12148.10.13.10.3.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
flexiMonitorInputDescription
OBJECT-TYPE
A textual description of the programmable input. This is stored in the system controller and can be changed by the user. .
1.3.6.1.4.1.12148.10.13.10.3.1.3DisplayString (SIZE(0..16))read-writecurrent
flexiMonitorInputTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.13.10.3.1.4Counter32accessible-for-notifycurrent
flexiMonitorInputAlarmEnable
OBJECT-TYPE
This will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state
1.3.6.1.4.1.12148.10.13.10.3.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
flexiMonitorInputValue
OBJECT-TYPE
The inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current, a Speed or a Boolean value.
1.3.6.1.4.1.12148.10.13.10.3.1.6Integer32read-onlycurrent
flexiMonitorInputConfiguration
OBJECT-TYPE
Configuration of the input type. Available configurations are: ProgIn-Normally Open(1), ProgIn-Normally Closed(2), Voltage(3), Temperature(4),Current(5),Speed(6),Fuse-Normally Open(7),Fuse-Normally Closed(8), Fuse-Diode Matrix(9).
1.3.6.1.4.1.12148.10.13.10.3.1.7INTEGER {progIn-NormallyOpen(1), progIn-NormallyClosed(2), voltage(3), temperature(4), current(5), speed(6), fuse-NormallyOpen(7), fuse-NormallyClosed(8), fuse-DiodeMatrix(9)}read-writecurrent
flexiMonitorOutputTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.10.4not-accessiblecurrent
flexiMonitorOutputEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.10.4.1not-accessiblecurrent
flexiMonitorOutputIndex
OBJECT-TYPE
Index used for navigating the rows of flexiMonitorOutputTable The size of the table is defined by the flexiMonitorNumberOfOutputs
1.3.6.1.4.1.12148.10.13.10.4.1.1Integer32 (1..16)not-accessiblecurrent
flexiMonitorOutputStatus
OBJECT-TYPE
General output relays may be 'energized' or 'not energized'. 'energized' and 'not energized' correspond to normal and alarm condition respectively for normally activated configuration. Latched contactors may have values 'disconnected' or 'connected'
1.3.6.1.4.1.12148.10.13.10.4.1.2INTEGER {notenergized(0), energized(1), disconnected(2), connected(3)}read-onlycurrent
flexiMonitorOutputDescription
OBJECT-TYPE
A textual description of the output. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.10.4.1.3DisplayStringread-writecurrent
mainControlUnits
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.11
mainControlUnitsTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.11.1not-accessiblecurrent
mainControlUnitsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.11.1.1not-accessiblecurrent
mainControlUnitIndex
OBJECT-TYPE
Index used for navigating the rows of controlUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.13.11.1.1.1Integer32 (1..14)not-accessiblecurrent
mainControlUnitNumberOfTemperatures
OBJECT-TYPE
Total number of temperature measurements in main controller
1.3.6.1.4.1.12148.10.13.11.1.1.2Integer32 (1..14)read-onlycurrent
mainControlUnitTemperatureTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.11.2not-accessiblecurrent
mainControlUnitTemperatureEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.11.2.1not-accessiblecurrent
mainControlUnitTemperatureIndex
OBJECT-TYPE
This index denotes which row in the temperature input table. The size of the table is defined by the batteryBankNumberOfTemp
1.3.6.1.4.1.12148.10.13.11.2.1.1Integer32 (1..4)not-accessiblecurrent
mainControlUnitTemperatureStatus
OBJECT-TYPE
The status of battery temperature monitor
1.3.6.1.4.1.12148.10.13.11.2.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainControlUnitTemperatureDescription
OBJECT-TYPE
A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.11.2.1.3DisplayString (SIZE(0..16))read-writecurrent
mainControlUnitTemperatureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.11.2.1.4Counter32accessible-for-notifycurrent
mainControlUnitTemperatureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.11.2.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
mainControlUnitTemperatureValue
OBJECT-TYPE
The measured battery temperature.
1.3.6.1.4.1.12148.10.13.11.2.1.6Integer32read-onlycurrent
mainControlUnitTemperatureMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.13.11.2.1.7Integer32read-writecurrent
mainControlUnitTemperatureMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.13.11.2.1.8Integer32read-writecurrent
mainControlUnitTemperatureMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.13.11.2.1.9Integer32read-writecurrent
mainControlUnitTemperatureMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.13.11.2.1.10Integer32read-writecurrent
mainControlUnitEarthFaultTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.11.3not-accessiblecurrent
mainControlUnitEarthFaultEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.13.11.3.1not-accessiblecurrent
mainControlUnitEarthFaultStatus
OBJECT-TYPE
This status value shows if the earth resistance is lower than the defined alarm level.
1.3.6.1.4.1.12148.10.13.11.3.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainControlUnitEarthFaultDescription
OBJECT-TYPE
A textual description of the earth fault monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.11.3.1.2DisplayString (SIZE(0..16))read-writecurrent
mainControlUnitEarthFaultTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.11.3.1.3Integer32accessible-for-notifycurrent
mainControlUnitEarthFaultAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.11.3.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
mainControlUnitEarthFaultValue
OBJECT-TYPE
The measured value of the earth resistance in kOhm.
1.3.6.1.4.1.12148.10.13.11.3.1.5Integer32read-onlycurrent
mainControlUnitEarthFaultMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.11.3.1.6Integer32read-writecurrent
controlSystemSummary
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.12
mainControlUnitsError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.12.1
mainControlUnitsErrorStatus
OBJECT-TYPE
This status value shows if the number of failed main controllers is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainControlUnitsErrorDescription
OBJECT-TYPE
A textual description of the main control units error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.1.2DisplayString (SIZE(0..16))read-writecurrent
mainControlUnitsErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.12.1.3Integer32accessible-for-notifycurrent
mainControlUnitsErrorAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
mainControlUnitsErrorValue
OBJECT-TYPE
The detected number of failed main controllers.
1.3.6.1.4.1.12148.10.13.12.1.5Integer32read-onlycurrent
mainControlUnitsErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.12.1.6Integer32read-writecurrent
mainControlUnitsErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.13.12.1.7Integer32read-writecurrent
smartNodeError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.12.2
smartNodeErrorStatus
OBJECT-TYPE
This status value shows if the number of failed smartnodes is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.2.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
smartNodeErrorDescription
OBJECT-TYPE
A textual description of the smartnode error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.2.2DisplayString (SIZE(0..16))read-writecurrent
smartNodeErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.12.2.3Integer32accessible-for-notifycurrent
smartNodeErrorAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.2.4INTEGER {disabled(0), enabled(1)}read-writecurrent
smartNodeErrorValue
OBJECT-TYPE
The detected number of failed smartnodes.
1.3.6.1.4.1.12148.10.13.12.2.5Integer32read-onlycurrent
smartNodeErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.12.2.6Integer32read-writecurrent
smartNodeErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.13.12.2.7Integer32read-writecurrent
batteryMonitorError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.12.3
batteryMonitorErrorStatus
OBJECT-TYPE
This status value shows if the number of failed battery monitors is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.3.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryMonitorErrorDescription
OBJECT-TYPE
A textual description of the battery monitor error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.3.2DisplayString (SIZE(0..16))read-writecurrent
batteryMonitorErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.12.3.3Integer32accessible-for-notifycurrent
batteryMonitorErrorAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.3.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryMonitorErrorValue
OBJECT-TYPE
The detected number of failed battery monitors.
1.3.6.1.4.1.12148.10.13.12.3.5Integer32read-onlycurrent
batteryMonitorErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.12.3.6Integer32read-writecurrent
batteryMonitorErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.13.12.3.7Integer32read-writecurrent
loadMonitorError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.12.4
loadMonitorErrorStatus
OBJECT-TYPE
This status value shows if the number of failed load monitors is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.4.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
loadMonitorErrorDescription
OBJECT-TYPE
A textual description of the load monitor error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.4.2DisplayString (SIZE(0..16))read-writecurrent
loadMonitorErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.12.4.3Integer32accessible-for-notifycurrent
loadMonitorErrorAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.4.4INTEGER {disabled(0), enabled(1)}read-writecurrent
loadMonitorErrorValue
OBJECT-TYPE
The detected number of failed load monitors.
1.3.6.1.4.1.12148.10.13.12.4.5Integer32read-onlycurrent
loadMonitorErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.12.4.6Integer32read-writecurrent
loadMonitorErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.13.12.4.7Integer32read-writecurrent
ioUnitError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.12.5
ioUnitErrorStatus
OBJECT-TYPE
This status value shows if the number of failed IO units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.5.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
ioUnitErrorDescription
OBJECT-TYPE
A textual description of the IO unit error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.5.2DisplayString (SIZE(0..16))read-writecurrent
ioUnitErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.12.5.3Integer32accessible-for-notifycurrent
ioUnitErrorAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.5.4INTEGER {disabled(0), enabled(1)}read-writecurrent
ioUnitErrorValue
OBJECT-TYPE
The detected number of failed IO units.
1.3.6.1.4.1.12148.10.13.12.5.5Integer32read-onlycurrent
ioUnitErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.12.5.6Integer32read-writecurrent
ioUnitErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.13.12.5.7Integer32read-writecurrent
mainsMonitorError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.12.6
mainsMonitorErrorStatus
OBJECT-TYPE
This status value shows if the number of failed mains monitors is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.6.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
mainsMonitorErrorDescription
OBJECT-TYPE
A textual description of the mains monitor error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.6.2DisplayString (SIZE(0..16))read-writecurrent
mainsMonitorErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.12.6.3Integer32accessible-for-notifycurrent
mainsMonitorErrorAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.6.4INTEGER {disabled(0), enabled(1)}read-writecurrent
mainsMonitorErrorValue
OBJECT-TYPE
The detected number of failed mains monitors.
1.3.6.1.4.1.12148.10.13.12.6.5Integer32read-onlycurrent
mainsMonitorErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.12.6.6Integer32read-writecurrent
mainsMonitorErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.13.12.6.7Integer32read-writecurrent
flexiMonitorError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.12.7
flexiMonitorErrorStatus
OBJECT-TYPE
This status value shows if the number of failed flexi monitors is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.7.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
flexiMonitorErrorDescription
OBJECT-TYPE
A textual description of the flexi monitor error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.7.2DisplayString (SIZE(0..16))read-writecurrent
flexiMonitorErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.12.7.3Integer32accessible-for-notifycurrent
flexiMonitorErrorAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.7.4INTEGER {disabled(0), enabled(1)}read-writecurrent
flexiMonitorErrorValue
OBJECT-TYPE
The detected number of failed flexi monitors.
1.3.6.1.4.1.12148.10.13.12.7.5Integer32read-onlycurrent
flexiMonitorErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.12.7.6Integer32read-writecurrent
flexiMonitorErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.13.12.7.7Integer32read-writecurrent
ambientTemperature
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.13
ambientTemperatureStatus
OBJECT-TYPE
The state of the ambient temperature can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.13.13.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
ambientTemperatureDescription
OBJECT-TYPE
A textual description of the ambient temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.13.2DisplayString (SIZE(0..16))read-writecurrent
ambientTemperatureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.13.13.3Counter32accessible-for-notifycurrent
ambientTemperatureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.13.4INTEGER {disabled(0), enabled(1)}read-writecurrent
ambientTemperatureValue
OBJECT-TYPE
The highest value of the enabled ambient temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.10.13.13.5Integer32 (0..9999)read-onlycurrent
ambientTemperatureMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.13.13.6Integer32read-writecurrent
ambientTemperatureMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.13.13.7Integer32read-writecurrent
ambientTemperatureMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.13.13.8Integer32read-writecurrent
ambientTemperatureMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.13.13.9Integer32read-writecurrent
deltaTemperature
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.14
deltaTemperatureStatus
OBJECT-TYPE
The state of the delta temperature can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.13.14.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
deltaTemperatureDescription
OBJECT-TYPE
A textual description of the delta temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.14.2DisplayString (SIZE(0..16))read-writecurrent
deltaTemperatureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.13.14.3Counter32accessible-for-notifycurrent
deltaTemperatureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.14.4INTEGER {disabled(0), enabled(1)}read-writecurrent
deltaTemperatureValue
OBJECT-TYPE
The delta temperature value. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.10.13.14.5Integer32 (0..9999)read-onlycurrent
deltaTemperatureMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.13.14.6Integer32read-writecurrent
deltaTemperatureMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.13.14.7Integer32read-writecurrent
deltaTemperatureMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.13.14.8Integer32read-writecurrent
deltaTemperatureMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.13.14.9Integer32read-writecurrent
userSuspended
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.13.15
userSuspendedStatus
OBJECT-TYPE
This status value shows if the number of failed attempts is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.15.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
userSuspendedDescription
OBJECT-TYPE
A textual description of the login failure monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.15.2DisplayString (SIZE(0..16))read-writecurrent
userSuspendedTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.13.15.3Integer32accessible-for-notifycurrent
userSuspendedAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.15.4INTEGER {disabled(0), enabled(1)}read-writecurrent
userSuspendedValue
OBJECT-TYPE
The detected number of failed attempts.
1.3.6.1.4.1.12148.10.13.15.5Integer32read-onlycurrent
userSuspendedMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.13.15.6Integer32read-writecurrent
alarmGroups
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.14
alarmGroupTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.14.1not-accessiblecurrent
alarmGroupEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.14.1.1not-accessiblecurrent
alarmGroupIndex
OBJECT-TYPE
Index used for navigating the rows 1..49 of alarmGroupTable
1.3.6.1.4.1.12148.10.14.1.1.1Integer32 (1..49)not-accessiblecurrent
alarmGroupStatus
OBJECT-TYPE
The status of alarm group
1.3.6.1.4.1.12148.10.14.1.1.2INTEGER {normal(0), alarm(1)}read-onlycurrent
alarmGroupDescription
OBJECT-TYPE
A textual description of the alarm group. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.14.1.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15
batteryGroup2Status
OBJECT-TYPE
A toplevel status for the battery group 2.The state of this reflects the status of all underlying statuses for the battery. Any change in one of the 'data monitors' in the battery subsystem will propagate up to this status indicator.
1.3.6.1.4.1.12148.10.15.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2Description
OBJECT-TYPE
A descriptive name of the battery installed in the battery group 2.
1.3.6.1.4.1.12148.10.15.2DisplayString (SIZE(0..32))read-writecurrent
batteryGroup2ReferenceVoltage
OBJECT-TYPE
The reference voltage of battery group 2.
1.3.6.1.4.1.12148.10.15.3Integer32 (840..60417)read-writecurrent
batteryGroup2FusesStatus
OBJECT-TYPE
The state of the battery fuses/breakers can mainly be normal(1) or majorAlarm(3) and some other rarely used values .
1.3.6.1.4.1.12148.10.15.4INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2Voltage
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.5
batteryGroup2VoltageStatus
OBJECT-TYPE
The status of the measured battery voltage.
1.3.6.1.4.1.12148.10.15.5.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2VoltageDescription
OBJECT-TYPE
A textual description of the battery voltage monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.5.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2VoltageTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.15.5.3Counter32accessible-for-notifycurrent
batteryGroup2VoltageAlarmEnable
OBJECT-TYPE
The measured battery voltage alarm enable/disable control
1.3.6.1.4.1.12148.10.15.5.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2VoltageValue
OBJECT-TYPE
The value of the measured battery voltage.
1.3.6.1.4.1.12148.10.15.5.5Integer32 (0..7500)read-onlycurrent
batteryGroup2VoltageMajorHighLevel
OBJECT-TYPE
The Major High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.10.15.5.6Integer32read-writecurrent
batteryGroup2VoltageMinorHighLevel
OBJECT-TYPE
The Minor High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.10.15.5.7Integer32read-writecurrent
batteryGroup2VoltageMinorLowLevel
OBJECT-TYPE
The Minor Low Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.10.15.5.8Integer32read-writecurrent
batteryGroup2VoltageMajorLowLevel
OBJECT-TYPE
The Major Low Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.10.15.5.9Integer32read-writecurrent
batteryGroup2Currents
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.6
batteryGroup2CurrentsStatus
OBJECT-TYPE
The status of the measured battery current
1.3.6.1.4.1.12148.10.15.6.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2CurrentsDescription
OBJECT-TYPE
A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.6.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2CurrentsTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.15.6.3Counter32accessible-for-notifycurrent
batteryGroup2CurrentsAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.6.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2CurrentsValue
OBJECT-TYPE
The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.10.15.6.5Integer32read-onlycurrent
batteryGroup2CurrentsMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.15.6.6Integer32read-writecurrent
batteryGroup2CurrentsMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.15.6.7Integer32read-writecurrent
batteryGroup2CurrentsMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.15.6.8Integer32read-writecurrent
batteryGroup2CurrentsMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.15.6.9Integer32read-writecurrent
batteryGroup2Temperatures
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.7
batteryGroup2TemperaturesStatus
OBJECT-TYPE
The state of the battery fuses/breakers can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.15.7.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2TemperaturesDescription
OBJECT-TYPE
A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.7.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2TemperaturesTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.15.7.3Counter32accessible-for-notifycurrent
batteryGroup2TemperaturesAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.7.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2TemperaturesValue
OBJECT-TYPE
The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.10.15.7.5Integer32 (0..9999)read-onlycurrent
batteryGroup2TemperaturesMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.15.7.6Integer32read-writecurrent
batteryGroup2TemperaturesMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.15.7.7Integer32read-writecurrent
batteryGroup2TemperaturesMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.15.7.8Integer32read-writecurrent
batteryGroup2TemperaturesMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.15.7.9Integer32read-writecurrent
batteryGroup2TimeLeft
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.8
batteryGroup2TimeLeftStatus
OBJECT-TYPE
The status of the estimated battery remaining backup time.
1.3.6.1.4.1.12148.10.15.8.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2TimeLeftDescription
OBJECT-TYPE
A textual description of the battery discharge time monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.8.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2TimeLeftTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.15.8.3Counter32accessible-for-notifycurrent
batteryGroup2TimeLeftAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.8.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2TimeLeftValue
OBJECT-TYPE
The estimated value of battery remaining backup time.
1.3.6.1.4.1.12148.10.15.8.5Integer32read-onlycurrent
batteryGroup2TimeLeftMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.15.8.6Integer32read-writecurrent
batteryGroup2TimeLeftMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.15.8.7Integer32read-writecurrent
batteryGroup2RemainingCapacity
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.9
batteryGroup2RemainingCapacityStatus
OBJECT-TYPE
The status of the battery remaining capacity monitor.
1.3.6.1.4.1.12148.10.15.9.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2RemainingCapacityDescription
OBJECT-TYPE
A textual description of the battery remaining capacity monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.9.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2RemainingCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.15.9.3Counter32accessible-for-notifycurrent
batteryGroup2RemainingCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.9.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2RemainingCapacityValue
OBJECT-TYPE
Battery remaining capacity (SOC) value estimated from the latest battery test result.
1.3.6.1.4.1.12148.10.15.9.5Integer32read-onlycurrent
batteryGroup2RemainingCapacityMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.15.9.6Integer32read-writecurrent
batteryGroup2RemainingCapacityMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.15.9.7Integer32read-writecurrent
batteryGroup2UsedCapacity
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.10
batteryGroup2UsedCapacityStatus
OBJECT-TYPE
The status of the battery used capacity (DoD) monitor
1.3.6.1.4.1.12148.10.15.10.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2UsedCapacityDescription
OBJECT-TYPE
A textual description of the battery used capacity (DoD) monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.10.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2UsedCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.15.10.3Counter32accessible-for-notifycurrent
batteryGroup2UsedCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.10.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2UsedCapacityValue
OBJECT-TYPE
This is the estimated battery used capacity (DoD).
1.3.6.1.4.1.12148.10.15.10.5Integer32read-onlycurrent
batteryGroup2UsedCapacityMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.15.10.6Integer32read-writecurrent
batteryGroup2UsedCapacityMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.15.10.7Integer32read-writecurrent
batteryGroup2TotalCapacity
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.11
batteryGroup2TotalCapacityStatus
OBJECT-TYPE
The status of the total capacity monitor.
1.3.6.1.4.1.12148.10.15.11.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2TotalCapacityDescription
OBJECT-TYPE
A textual description of the battery total capacity monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.15.11.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2TotalCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.15.11.3Counter32accessible-for-notifycurrent
batteryGroup2TotalCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.11.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2TotalCapacityValue
OBJECT-TYPE
This is the estimated total battery capacity (installed Ah - SoH) value.
1.3.6.1.4.1.12148.10.15.11.5Integer32read-onlycurrent
batteryGroup2TotalCapacityMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.15.11.6Integer32read-writecurrent
batteryGroup2TotalCapacityMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.15.11.7Integer32read-writecurrent
batteryGroup2Quality
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.12
batteryGroup2QualityStatus
OBJECT-TYPE
The status of the battery quality (SoH) monitor.
1.3.6.1.4.1.12148.10.15.12.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2QualityDescription
OBJECT-TYPE
A textual description of the battery quality (SoH) monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.15.12.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2QualityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.15.12.3Counter32accessible-for-notifycurrent
batteryGroup2QualityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.12.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2QualityValue
OBJECT-TYPE
The calculated battery quality (SoH) based on the latest battery test
1.3.6.1.4.1.12148.10.15.12.5Integer32read-onlycurrent
batteryGroup2QualityMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.15.12.6Integer32read-writecurrent
batteryGroup2QualityMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.15.12.7Integer32read-writecurrent
batteryGroup2LVBD
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.13
batteryGroup2LVBDStatus
OBJECT-TYPE
The Battery Contactor is connected, disconnected, disabled or in any other alarm condition
1.3.6.1.4.1.12148.10.15.13.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2LVBDDescription
OBJECT-TYPE
A textual description of the battery LVBD monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.13.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2LVBDTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.15.13.3Counter32accessible-for-notifycurrent
batteryGroup2LVBDEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the LVBD will be reported.
1.3.6.1.4.1.12148.10.15.13.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2LVBDValue
OBJECT-TYPE
The measured value of the LVBD.
1.3.6.1.4.1.12148.10.15.13.5Integer32read-onlycurrent
batteryGroup2LVBDConnectVoltage
OBJECT-TYPE
The Battery Contactor's Reconnect Voltage
1.3.6.1.4.1.12148.10.15.13.6Integer32read-writecurrent
batteryGroup2LVBDDisconnectVoltage
OBJECT-TYPE
The Battery Contactor's Disconnect Voltage
1.3.6.1.4.1.12148.10.15.13.7Integer32read-writecurrent
batteryGroup2ChargeCurrentLimit
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.14
batteryGroup2ChargeCurrentLimitEnable
OBJECT-TYPE
Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
1.3.6.1.4.1.12148.10.15.14.1INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2ChargeCurrentLimitValue
OBJECT-TYPE
Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
1.3.6.1.4.1.12148.10.15.14.2Integer32 (0..32767)read-writecurrent
batteryGroup2Boost
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.15
batteryGroup2BoostVoltage
OBJECT-TYPE
The Voltage at which the DC System boost charges the batteries.
1.3.6.1.4.1.12148.10.15.15.1Integer32 (870..60418)read-writecurrent
batteryGroup2BoostCommand
OBJECT-TYPE
This pushbutton will start or stop a manual battery boost if the system allows it.
1.3.6.1.4.1.12148.10.15.15.2INTEGER {pushbutton(0), startboost(1), stopboost(2)}read-writecurrent
batteryGroup2BoostCurrentThreshold
OBJECT-TYPE
The boosting will terminate when the charge current drops below the BoostCurrentThreshold limit.
1.3.6.1.4.1.12148.10.15.15.3Integer32read-writecurrent
batteryGroup2BoostManualMaxDuration
OBJECT-TYPE
A protection against overcharging. When running manual boost, the boosting will always terminate at this point.
1.3.6.1.4.1.12148.10.15.15.4Integer32 (0..1440)read-writecurrent
batteryGroup2Test
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.16
batteryGroup2TestVoltage
OBJECT-TYPE
This is the battery test end voltage. The battery test will be terminated when the voltage drops below the end voltage.
1.3.6.1.4.1.12148.10.15.16.1Integer32read-writecurrent
batteryGroup2TestCommand
OBJECT-TYPE
This pushbutton will start or stop a manual battery test if the system allows it.
1.3.6.1.4.1.12148.10.15.16.2INTEGER {pushbutton(0), starttest(1), stoptest(2)}read-writecurrent
batteryGroup2TestNumberOfResults
OBJECT-TYPE
This is the number of valid battery test results stored in controller.
1.3.6.1.4.1.12148.10.15.16.3Integer32 (0..10)read-onlycurrent
batteryGroup2TestResultTable
OBJECT-TYPE
This table contains the battery test results stored in controller.
1.3.6.1.4.1.12148.10.15.16.4not-accessiblecurrent
batteryGroup2TestResultEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.16.4.1not-accessiblecurrent
batteryGroup2TestResultIndex
OBJECT-TYPE
A index pointing to one of ten possible battery test results
1.3.6.1.4.1.12148.10.15.16.4.1.1Integer32 (1..10)not-accessiblecurrent
batteryGroup2TestResultStartDateTime
OBJECT-TYPE
This is the time and date when the test started.
1.3.6.1.4.1.12148.10.15.16.4.1.2DateAndTimeread-onlycurrent
batteryGroup2TestResultDuration
OBJECT-TYPE
This is the test duration in minutes.
1.3.6.1.4.1.12148.10.15.16.4.1.3Integer32read-onlycurrent
batteryGroup2TestResultDischarged
OBJECT-TYPE
This is the discharged Ah during test.
1.3.6.1.4.1.12148.10.15.16.4.1.4Integer32read-onlycurrent
batteryGroup2TestResultQuality
OBJECT-TYPE
This is the calculated battery quality (SoH)in percentage.
1.3.6.1.4.1.12148.10.15.16.4.1.5Integer32read-onlycurrent
batteryGroup2TempComp
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.17
batteryGroup2TempCompEnable
OBJECT-TYPE
Enable (1) or Disable (0) of Battery Temperature Compensated output regulation mode
1.3.6.1.4.1.12148.10.15.17.1INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2Bank
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.18
batteryGroup2BankStatus
OBJECT-TYPE
The overall status of battery bank
1.3.6.1.4.1.12148.10.15.18.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2BankNumberOfTemperatures
OBJECT-TYPE
Number of temperature measurements in battery bank.
1.3.6.1.4.1.12148.10.15.18.2Integer32read-onlycurrent
batteryGroup2BankNumberOfCurrents
OBJECT-TYPE
Number of current measurements in battery bank.
1.3.6.1.4.1.12148.10.15.18.3Integer32read-onlycurrent
batteryGroup2BankNumberOfFuses
OBJECT-TYPE
Number of fuses installed in battery bank.
1.3.6.1.4.1.12148.10.15.18.4Integer32read-onlycurrent
batteryGroup2BankNumberOfSymmetries
OBJECT-TYPE
Number of fuses installed in battery bank.
1.3.6.1.4.1.12148.10.15.18.5Integer32read-onlycurrent
batteryGroup2BankTemperatureTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.18.6not-accessiblecurrent
batteryGroup2BankTemperatureEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.18.6.1not-accessiblecurrent
batteryGroup2TemperatureIndex
OBJECT-TYPE
This index denotes which row in the temperature input table. The size of the table is defined by the batteryGroup2BankNumberOfTemperatures
1.3.6.1.4.1.12148.10.15.18.6.1.1Integer32 (1..4)not-accessiblecurrent
batteryGroup2TemperatureStatus
OBJECT-TYPE
The status of battery temperature monitor
1.3.6.1.4.1.12148.10.15.18.6.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2TemperatureDescription
OBJECT-TYPE
A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.18.6.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2TemperatureTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.15.18.6.1.4Counter32accessible-for-notifycurrent
batteryGroup2TemperatureAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.18.6.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2TemperatureValue
OBJECT-TYPE
The measured battery temperature.
1.3.6.1.4.1.12148.10.15.18.6.1.6Integer32read-onlycurrent
batteryGroup2TemperatureMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.15.18.6.1.7Integer32read-writecurrent
batteryGroup2TemperatureMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.15.18.6.1.8Integer32read-writecurrent
batteryGroup2TemperatureMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.15.18.6.1.9Integer32read-writecurrent
batteryGroup2TemperatureMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.15.18.6.1.10Integer32read-writecurrent
batteryGroup2BankCurrentTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.18.7not-accessiblecurrent
batteryGroup2BankCurrentEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.18.7.1not-accessiblecurrent
batteryGroup2CurrentIndex
OBJECT-TYPE
This index denotes which row in the current input table. The size of the table is defined by the system
1.3.6.1.4.1.12148.10.15.18.7.1.1Integer32 (1..4)not-accessiblecurrent
batteryGroup2CurrentStatus
OBJECT-TYPE
The status of battery current monitor
1.3.6.1.4.1.12148.10.15.18.7.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2CurrentDescription
OBJECT-TYPE
A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.18.7.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2CurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.15.18.7.1.4Counter32accessible-for-notifycurrent
batteryGroup2CurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.18.7.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2CurrentValue
OBJECT-TYPE
The measured battery current
1.3.6.1.4.1.12148.10.15.18.7.1.6Integer32read-onlycurrent
batteryGroup2CurrentMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.15.18.7.1.7Integer32read-writecurrent
batteryGroup2CurrentMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.15.18.7.1.8Integer32read-writecurrent
batteryGroup2CurrentMinorLowLevel
OBJECT-TYPE
The minor low alarm limit
1.3.6.1.4.1.12148.10.15.18.7.1.9Integer32read-writecurrent
batteryGroup2CurrentMajorLowLevel
OBJECT-TYPE
The major low alarm limit
1.3.6.1.4.1.12148.10.15.18.7.1.10Integer32read-writecurrent
batteryGroup2BankFuseTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.18.8not-accessiblecurrent
batteryGroup2BankFuseEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.18.8.1not-accessiblecurrent
batteryGroup2FuseIndex
OBJECT-TYPE
This index denotes which row in the fuse table. The size of the table is defined by the system
1.3.6.1.4.1.12148.10.15.18.8.1.1Integer32 (1..4)not-accessiblecurrent
batteryGroup2FuseStatus
OBJECT-TYPE
The status of battery fuse monitor
1.3.6.1.4.1.12148.10.15.18.8.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2FuseDescription
OBJECT-TYPE
A textual description of the battery fuse monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.18.8.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2FuseTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off.
1.3.6.1.4.1.12148.10.15.18.8.1.4Counter32accessible-for-notifycurrent
batteryGroup2FuseAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.18.8.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2FuseValue
OBJECT-TYPE
The measured value of battery fuse input.
1.3.6.1.4.1.12148.10.15.18.8.1.6Integer32read-onlycurrent
batteryGroup2BankSymmetryTable
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.18.9not-accessiblecurrent
batteryGroup2BankSymmetryEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.18.9.1not-accessiblecurrent
batteryGroup2BankSymmetryIndex
OBJECT-TYPE
This index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries
1.3.6.1.4.1.12148.10.15.18.9.1.1Integer32 (1..8)not-accessiblecurrent
batteryGroup2BankSymmetryStatus
OBJECT-TYPE
The status of battery symmetry monitor
1.3.6.1.4.1.12148.10.15.18.9.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2BankSymmetryDescription
OBJECT-TYPE
A textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.18.9.1.3DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2BankSymmetryTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.15.18.9.1.4Counter32accessible-for-notifycurrent
batteryGroup2BankSymmetryAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.18.9.1.5INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2BankSymmetryMeasureValue
OBJECT-TYPE
The measured battery symmetry voltage in battery monitor.
1.3.6.1.4.1.12148.10.15.18.9.1.6Integer32read-onlycurrent
batteryGroup2BankSymmetryDeltaValue
OBJECT-TYPE
The measured battery symmetry delta voltage in battery monitor.
1.3.6.1.4.1.12148.10.15.18.9.1.7Integer32read-onlycurrent
batteryGroup2BankSymmetryMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.15.18.9.1.8Integer32read-writecurrent
batteryGroup2BankSymmetryMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.15.18.9.1.9Integer32read-writecurrent
batteryGroup2EnergyLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.19
batteryGroup2EnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered to/from battery.
1.3.6.1.4.1.12148.10.15.19.1Integer32read-onlycurrent
batteryGroup2EnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in battery hourly energy log.
1.3.6.1.4.1.12148.10.15.19.2Integer32 (0..52)read-onlycurrent
batteryGroup2EnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly energy log of battery.
1.3.6.1.4.1.12148.10.15.19.3not-accessiblecurrent
batteryGroup2EnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.19.3.1not-accessiblecurrent
batteryGroup2EnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.15.19.3.1.1Integer32 (1..52)not-accessiblecurrent
batteryGroup2EnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.15.19.3.1.2Integer32read-onlycurrent
batteryGroup2EnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in battery daily energy log.
1.3.6.1.4.1.12148.10.15.19.4Integer32 (0..52)read-onlycurrent
batteryGroup2EnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily energy log of battery.
1.3.6.1.4.1.12148.10.15.19.5not-accessiblecurrent
batteryGroup2EnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.19.5.1not-accessiblecurrent
batteryGroup2EnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.15.19.5.1.1Integer32 (1..52)not-accessiblecurrent
batteryGroup2EnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day.
1.3.6.1.4.1.12148.10.15.19.5.1.2Integer32read-onlycurrent
batteryGroup2EnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in battery weekly energy log.
1.3.6.1.4.1.12148.10.15.19.6Integer32 (0..52)read-onlycurrent
batteryGroup2EnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly energy log of battery.
1.3.6.1.4.1.12148.10.15.19.7not-accessiblecurrent
batteryGroup2EnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.19.7.1not-accessiblecurrent
batteryGroup2EnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.15.19.7.1.1Integer32 (1..52)not-accessiblecurrent
batteryGroup2EnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.15.19.7.1.2Integer32read-onlycurrent
batteryGroup2CycleLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.20
batteryGroup2CycleLogTotalCycles
OBJECT-TYPE
This is the total number of battery discharge cycles.
1.3.6.1.4.1.12148.10.15.20.1Integer32read-onlycurrent
batteryGroup2CycleLogDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in daily battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.2Integer32 (0..52)read-onlycurrent
batteryGroup2CycleLogDaysTable
OBJECT-TYPE
This table contains daily battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.3not-accessiblecurrent
batteryGroup2CycleLogDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.20.3.1not-accessiblecurrent
batteryGroup2CycleLogDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryCycleLogLastDaysTable
1.3.6.1.4.1.12148.10.15.20.3.1.1Integer32 (1..52)not-accessiblecurrent
batteryGroup2CycleLogDaysValue
OBJECT-TYPE
Number of discharge cycles logged every day.
1.3.6.1.4.1.12148.10.15.20.3.1.2Integer32read-onlycurrent
batteryGroup2CycleLogWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in weeky battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.4Integer32 (0..52)read-onlycurrent
batteryGroup2CycleLogWeeksTable
OBJECT-TYPE
This table contains weekly battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.5not-accessiblecurrent
batteryGroup2CycleLogWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.20.5.1not-accessiblecurrent
batteryGroup2CycleLogWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable
1.3.6.1.4.1.12148.10.15.20.5.1.1Integer32 (1..52)not-accessiblecurrent
batteryGroup2CycleLogWeeksValue
OBJECT-TYPE
Number of discharge cycles logged every week.
1.3.6.1.4.1.12148.10.15.20.5.1.2Integer32read-onlycurrent
batteryGroup2CycleLogMonthsNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in monthly battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.6Integer32 (0..52)read-onlycurrent
batteryGroup2CycleLogMonthsTable
OBJECT-TYPE
This table contains monthly battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.7not-accessiblecurrent
batteryGroup2CycleLogMonthsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.15.20.7.1not-accessiblecurrent
batteryGroup2CycleLogMonthsIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of batteryCycleLogLastMonthTable
1.3.6.1.4.1.12148.10.15.20.7.1.1Integer32 (1..52)not-accessiblecurrent
batteryGroup2CycleLogMonthsValue
OBJECT-TYPE
Number of discharge cycles logged every month.
1.3.6.1.4.1.12148.10.15.20.7.1.2Integer32read-onlycurrent
batteryGroup2Equalize
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.21
batteryGroup2EqualizeVoltage
OBJECT-TYPE
The Voltage at which the DC System equalize charges the batteries.
1.3.6.1.4.1.12148.10.15.21.1Integer32 (870..60418)read-writecurrent
batteryGroup2EqualizeCommand
OBJECT-TYPE
This pushbutton will start or stop a manual battery equalize if the system allows it.
1.3.6.1.4.1.12148.10.15.21.2INTEGER {pushbutton(0), startequalize(1), stopequalize(2)}read-writecurrent
batteryGroup2EqualizeCurrentThreshold
OBJECT-TYPE
The equalizing will terminate when the charge current drops below the EqualizeCurrentThreshold limit.
1.3.6.1.4.1.12148.10.15.21.3Integer32read-writecurrent
batteryGroup2EqualizeManualMaxDuration
OBJECT-TYPE
A protection against overcharging. When running manual equalize, the boosting will always terminate at this point.
1.3.6.1.4.1.12148.10.15.21.4Integer32 (0..1440)read-writecurrent
batteryGroup2AhCharged
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.22
batteryGroup2AhChargedStatus
OBJECT-TYPE
The status of the battery ah charged monitor.
1.3.6.1.4.1.12148.10.15.22.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2AhChargedDescription
OBJECT-TYPE
A textual description of the battery ah charged monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.15.22.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2AhChargedTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.15.22.3Counter32accessible-for-notifycurrent
batteryGroup2AhChargedAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.22.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2AhChargedValue
OBJECT-TYPE
The calculated battery ah (x100) charged value.
1.3.6.1.4.1.12148.10.15.22.5Integer32read-onlycurrent
batteryGroup2AhChargedMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.15.22.6Integer32read-writecurrent
batteryGroup2AhChargedMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.15.22.7Integer32read-writecurrent
batteryGroup2AhDischarged
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.15.23
batteryGroup2AhDischargedStatus
OBJECT-TYPE
The status of the battery ah discharged monitor.
1.3.6.1.4.1.12148.10.15.23.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
batteryGroup2AhDischargedDescription
OBJECT-TYPE
A textual description of the battery ah discharged monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.15.23.2DisplayString (SIZE(0..16))read-writecurrent
batteryGroup2AhDischargedTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.15.23.3Counter32accessible-for-notifycurrent
batteryGroup2AhDischargedAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.23.4INTEGER {disabled(0), enabled(1)}read-writecurrent
batteryGroup2AhDischargedValue
OBJECT-TYPE
The calculated battery ah (x100) discharged value.
1.3.6.1.4.1.12148.10.15.23.5Integer32read-onlycurrent
batteryGroup2AhDischargedMinorHighLevel
OBJECT-TYPE
The minor high alarm limit
1.3.6.1.4.1.12148.10.15.23.6Integer32read-writecurrent
batteryGroup2AhDischargedMajorHighLevel
OBJECT-TYPE
The major high alarm limit
1.3.6.1.4.1.12148.10.15.23.7Integer32read-writecurrent
inverters
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.16
invertersStatus
OBJECT-TYPE
The overall status of inverter subsystem.
1.3.6.1.4.1.12148.10.16.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
invertersCurrent
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.16.2
invertersCurrentStatus
OBJECT-TYPE
The status of the measured total inverter current.
1.3.6.1.4.1.12148.10.16.2.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
invertersCurrentDescription
OBJECT-TYPE
A textual description of the total inverter current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.2.2DisplayString (SIZE(0..16))read-writecurrent
invertersCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.16.2.3Counter32accessible-for-notifycurrent
invertersCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.2.4INTEGER {disabled(0), enabled(1)}read-writecurrent
invertersCurrentValue
OBJECT-TYPE
The value of the measured total inverter current.
1.3.6.1.4.1.12148.10.16.2.5Integer32read-onlycurrent
invertersCurrentMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.16.2.6Integer32read-writecurrent
invertersCurrentMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.16.2.7Integer32read-writecurrent
invertersCapacity
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.16.3
invertersCapacityStatus
OBJECT-TYPE
The status of the measured used inverter capacity.
1.3.6.1.4.1.12148.10.16.3.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
invertersCapacityDescription
OBJECT-TYPE
A textual description of the used inverter capacity monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.3.2DisplayString (SIZE(0..16))read-writecurrent
invertersCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.16.3.3Counter32accessible-for-notifycurrent
invertersCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.3.4INTEGER {disabled(0), enabled(1)}read-writecurrent
invertersCapacityValue
OBJECT-TYPE
The used inverter capacity value presented in percentage of the total installed inverter capacity.
1.3.6.1.4.1.12148.10.16.3.5Integer32read-onlycurrent
invertersCapacityMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.16.3.6Integer32read-writecurrent
invertersCapacityMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.16.3.7Integer32read-writecurrent
invertersError
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.16.4
invertersErrorStatus
OBJECT-TYPE
This status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.16.4.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
invertersErrorDescription
OBJECT-TYPE
A textual description of the inverter error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.4.2DisplayString (SIZE(0..16))read-writecurrent
invertersErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.16.4.3Counter32accessible-for-notifycurrent
invertersErrorEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.4.4INTEGER {disabled(0), enabled(1)}read-writecurrent
invertersErrorValue
OBJECT-TYPE
The number of failed inverters.
1.3.6.1.4.1.12148.10.16.4.5Integer32read-onlycurrent
invertersErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.16.4.6Integer32read-writecurrent
invertersErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.16.4.7Integer32read-writecurrent
invertersNumberOfInverters
OBJECT-TYPE
Number of installed inverters.
1.3.6.1.4.1.12148.10.16.5Integer32 (0..100)read-writecurrent
inverterTable
OBJECT-TYPE
This table shows the information of each inverter installed in the system.
1.3.6.1.4.1.12148.10.16.6not-accessiblecurrent
inverterEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.6.1not-accessiblecurrent
inverterIndex
OBJECT-TYPE
Index used for navigating the rows 1..100 of inverterTable
1.3.6.1.4.1.12148.10.16.6.1.1Integer32 (1..100)not-accessiblecurrent
inverterStatus
OBJECT-TYPE
The overall status of inverter.
1.3.6.1.4.1.12148.10.16.6.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
inverterOutputCurrentValue
OBJECT-TYPE
The output current value of inverter.
1.3.6.1.4.1.12148.10.16.6.1.3Integer32read-onlycurrent
inverterOutputVoltageValue
OBJECT-TYPE
The output voltage value of inverter.
1.3.6.1.4.1.12148.10.16.6.1.4Integer32read-onlycurrent
inverterType
OBJECT-TYPE
Type of inverter
1.3.6.1.4.1.12148.10.16.6.1.5DisplayString (SIZE(0..27))read-onlycurrent
inverterHwPartNumber
OBJECT-TYPE
Hardware part number of inverter
1.3.6.1.4.1.12148.10.16.6.1.6DisplayString (SIZE(0..12))read-onlycurrent
inverterHwVersion
OBJECT-TYPE
Hardware version number of inverter
1.3.6.1.4.1.12148.10.16.6.1.7DisplayString (SIZE(0..6))read-onlycurrent
inverterSwPartNumber
OBJECT-TYPE
Part number of secondary software in inverter
1.3.6.1.4.1.12148.10.16.6.1.8DisplayString (SIZE(0..12))read-onlycurrent
inverterSwVersion
OBJECT-TYPE
Version number of secondary software in inverter
1.3.6.1.4.1.12148.10.16.6.1.9DisplayString (SIZE(0..6))read-onlycurrent
inverterOutputFrequencyValue
OBJECT-TYPE
The output frequency value of inverter.
1.3.6.1.4.1.12148.10.16.6.1.10Integer32read-onlycurrent
inverterOutputPowerValue
OBJECT-TYPE
The output power value of inverter.
1.3.6.1.4.1.12148.10.16.6.1.11Integer32read-onlycurrent
inverterOutputReactivePowerValue
OBJECT-TYPE
The output reactive power value of inverter.
1.3.6.1.4.1.12148.10.16.6.1.12Integer32read-onlycurrent
invertersNumberOfGroups
OBJECT-TYPE
Number of inverter groups
1.3.6.1.4.1.12148.10.16.7Integer32read-onlycurrent
inverterGroupsTable
OBJECT-TYPE
This table contains status and the number of installed inverters of each inverter groups.
1.3.6.1.4.1.12148.10.16.8not-accessiblecurrent
inverterGroupsEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.8.1not-accessiblecurrent
inverterGroupIndex
OBJECT-TYPE
Index used for navigating the rows 1..10 of inverterGroupsTable
1.3.6.1.4.1.12148.10.16.8.1.1Integer32 (1..10)not-accessiblecurrent
inverterGroupStatus
OBJECT-TYPE
The status of each inverter group.
1.3.6.1.4.1.12148.10.16.8.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
inverterGroupNumberOfInverters
OBJECT-TYPE
Number of installed inverters in each inverter groups
1.3.6.1.4.1.12148.10.16.8.1.3Integer32 (0..100)read-writecurrent
inverterGroupCurrentTable
OBJECT-TYPE
This table contains information about the total inverter current of each inverter groups, which is calculated by summing up current from each inverter in a inverter group.
1.3.6.1.4.1.12148.10.16.9not-accessiblecurrent
inverterGroupCurrentEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.9.1not-accessiblecurrent
inverterGroupCurrentStatus
OBJECT-TYPE
The status of the measured total inverter current of the inverter group
1.3.6.1.4.1.12148.10.16.9.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
inverterGroupCurrentDescription
OBJECT-TYPE
A textual description of the total inverter current monitor of a inverter group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.9.1.2DisplayString (SIZE(0..16))read-writecurrent
inverterGroupCurrentTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.16.9.1.3Integer32accessible-for-notifycurrent
inverterGroupCurrentAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.9.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
inverterGroupCurrentValue
OBJECT-TYPE
The value of the measured total inverter current of each inverter group.
1.3.6.1.4.1.12148.10.16.9.1.5Integer32read-onlycurrent
inverterGroupCurrentMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.16.9.1.6Integer32read-writecurrent
inverterGroupCurrentMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.16.9.1.7Integer32read-writecurrent
inverterGroupCapacityTable
OBJECT-TYPE
This table contains information about the used inverter capacity of each inverter group.
1.3.6.1.4.1.12148.10.16.10not-accessiblecurrent
inverterGroupCapacityEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.10.1not-accessiblecurrent
inverterGroupCapacityStatus
OBJECT-TYPE
The status of the measured used inverter capacity of each inverter group
1.3.6.1.4.1.12148.10.16.10.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
inverterGroupCapacityDescription
OBJECT-TYPE
A textual description of the used inverter capacity monitor of each inverter group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.10.1.2DisplayString (SIZE(0..16))read-writecurrent
inverterGroupCapacityTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.16.10.1.3Integer32accessible-for-notifycurrent
inverterGroupCapacityAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.10.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
inverterGroupCapacityValue
OBJECT-TYPE
The used inverter capacity value presented in percentage of the total installed inverter capacity of each inverter group.
1.3.6.1.4.1.12148.10.16.10.1.5Integer32read-onlycurrent
inverterGroupCapacityMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.16.10.1.6Integer32read-writecurrent
inverterGroupCapacityMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.16.10.1.7Integer32read-writecurrent
inverterGroupErrorTable
OBJECT-TYPE
This table contains information about the inverter error monitor of each inverter group.
1.3.6.1.4.1.12148.10.16.11not-accessiblecurrent
inverterGroupErrorEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.11.1not-accessiblecurrent
inverterGroupErrorStatus
OBJECT-TYPE
This status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.16.11.1.1INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
inverterGroupErrorDescription
OBJECT-TYPE
A textual description of the inverter error monitor of each inverter group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.11.1.2DisplayString (SIZE(0..16))read-writecurrent
inverterGroupErrorTrapRepeatCounter
OBJECT-TYPE
The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off
1.3.6.1.4.1.12148.10.16.11.1.3Integer32accessible-for-notifycurrent
inverterGroupErrorAlarmEnable
OBJECT-TYPE
This value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.11.1.4INTEGER {disabled(0), enabled(1)}read-writecurrent
inverterGroupErrorValue
OBJECT-TYPE
The number of failed inverters of each inverter group.
1.3.6.1.4.1.12148.10.16.11.1.5Integer32read-onlycurrent
inverterGroupErrorMajorAlarmLevel
OBJECT-TYPE
The major alarm limit
1.3.6.1.4.1.12148.10.16.11.1.6Integer32read-writecurrent
inverterGroupErrorMinorAlarmLevel
OBJECT-TYPE
The minor alarm limit
1.3.6.1.4.1.12148.10.16.11.1.7Integer32read-writecurrent
inverterGroupInverterTable
OBJECT-TYPE
This table shows the information of each inverter installed in each of the inverter group in the system.
1.3.6.1.4.1.12148.10.16.12not-accessiblecurrent
inverterGroupInverterEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.12.1not-accessiblecurrent
inverterGroupInverterIndex
OBJECT-TYPE
Index used for navigating the rows 1..100 of inverterGroupinverterTable
1.3.6.1.4.1.12148.10.16.12.1.1Integer32 (1..100)not-accessiblecurrent
inverterGroupInverterStatus
OBJECT-TYPE
The overall status of inverter.
1.3.6.1.4.1.12148.10.16.12.1.2INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)}read-onlycurrent
inverterGroupInverterOutputCurrentValue
OBJECT-TYPE
The output current value of inverter.
1.3.6.1.4.1.12148.10.16.12.1.3Integer32read-onlycurrent
inverterGroupInverterOutputVoltageValue
OBJECT-TYPE
The output voltage value of inverter.
1.3.6.1.4.1.12148.10.16.12.1.4Integer32read-onlycurrent
inverterGroupInverterType
OBJECT-TYPE
Type of inverter
1.3.6.1.4.1.12148.10.16.12.1.5DisplayString (SIZE(0..27))read-onlycurrent
inverterGroupInverterHwPartNumber
OBJECT-TYPE
Hardware part number of inverter
1.3.6.1.4.1.12148.10.16.12.1.6DisplayString (SIZE(0..12))read-onlycurrent
inverterGroupInverterHwVersion
OBJECT-TYPE
Hardware version number of inverter
1.3.6.1.4.1.12148.10.16.12.1.7DisplayString (SIZE(0..6))read-onlycurrent
inverterGroupInverterSwPartNumber
OBJECT-TYPE
Part number of secondary software in inverter
1.3.6.1.4.1.12148.10.16.12.1.8DisplayString (SIZE(0..12))read-onlycurrent
inverterGroupInverterSwVersion
OBJECT-TYPE
Version number of secondary software in inverter
1.3.6.1.4.1.12148.10.16.12.1.9DisplayString (SIZE(0..6))read-onlycurrent
inverterGroupInverterOutputFrequencyValue
OBJECT-TYPE
The output frequency value of inverter.
1.3.6.1.4.1.12148.10.16.12.1.10Integer32read-onlycurrent
inverterGroupInverterOutputPowerValue
OBJECT-TYPE
The output power value of inverter.
1.3.6.1.4.1.12148.10.16.12.1.11Integer32read-onlycurrent
inverterGroupInverterOutputReactivePowerValue
OBJECT-TYPE
The output reactive power value of inverter.
1.3.6.1.4.1.12148.10.16.12.1.12Integer32read-onlycurrent
invertersEnergyLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.16.13
invertersEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered from inverters.
1.3.6.1.4.1.12148.10.16.13.1Integer32read-onlycurrent
invertersEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter hourly energy log.
1.3.6.1.4.1.12148.10.16.13.2Integer32 (0..52)read-onlycurrent
invertersEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly energy log of inverters.
1.3.6.1.4.1.12148.10.16.13.3not-accessiblecurrent
invertersEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.13.3.1not-accessiblecurrent
invertersEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of invertersEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.16.13.3.1.1Integer32 (1..52)not-accessiblecurrent
invertersEnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.16.13.3.1.2Integer32read-onlycurrent
invertersEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter daily energy log.
1.3.6.1.4.1.12148.10.16.13.4Integer32 (0..52)read-onlycurrent
invertersEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily energy log of inverters.
1.3.6.1.4.1.12148.10.16.13.5not-accessiblecurrent
invertersEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.13.5.1not-accessiblecurrent
invertersEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of invertersEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.16.13.5.1.1Integer32 (1..52)not-accessiblecurrent
invertersEnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day.
1.3.6.1.4.1.12148.10.16.13.5.1.2Integer32read-onlycurrent
invertersEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter weekly energy log.
1.3.6.1.4.1.12148.10.16.13.6Integer32 (0..52)read-onlycurrent
invertersEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly energy log of inverters.
1.3.6.1.4.1.12148.10.16.13.7not-accessiblecurrent
invertersEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.13.7.1not-accessiblecurrent
invertersEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of invertersEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.16.13.7.1.1Integer32 (1..52)not-accessiblecurrent
invertersEnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.16.13.7.1.2Integer32read-onlycurrent
inverterGroupEnergyLogTable
OBJECT-TYPE
This branch contains information about inverters' energy logs of each inverter group.
1.3.6.1.4.1.12148.10.16.14not-accessiblecurrent
inverterGroupEnergyLogEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.14.1not-accessiblecurrent
inverterGroupEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated energy delivered from inverters of each inverter group.
1.3.6.1.4.1.12148.10.16.14.1.1Integer32read-onlycurrent
inverterGroupEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter group hourly energy log.
1.3.6.1.4.1.12148.10.16.14.1.2Integer32read-onlycurrent
inverterGroupEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter group daily energy log.
1.3.6.1.4.1.12148.10.16.14.1.3Integer32read-onlycurrent
inverterGroupEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter group weekly energy log.
1.3.6.1.4.1.12148.10.16.14.1.4Integer32read-onlycurrent
inverterGroupEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly energy log of each inverter group
1.3.6.1.4.1.12148.10.16.15not-accessiblecurrent
inverterGroupEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.15.1not-accessiblecurrent
inverterGroupEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of inverterGroupEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.16.15.1.1Integer32 (1..52)not-accessiblecurrent
inverterGroupEnergyLogLastHoursValue
OBJECT-TYPE
Energy value logged every hour.
1.3.6.1.4.1.12148.10.16.15.1.2Integer32read-onlycurrent
inverterGroupEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily energy log of each inverter group
1.3.6.1.4.1.12148.10.16.16not-accessiblecurrent
inverterGroupEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.16.1not-accessiblecurrent
inverterGroupEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of inverterGroupEnergyLogLasDaysTable
1.3.6.1.4.1.12148.10.16.16.1.1Integer32 (1..52)not-accessiblecurrent
inverterGroupEnergyLogLastDaysValue
OBJECT-TYPE
Energy value logged every day.
1.3.6.1.4.1.12148.10.16.16.1.2Integer32read-onlycurrent
inverterGroupEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly energy log of each inverter group
1.3.6.1.4.1.12148.10.16.17not-accessiblecurrent
inverterGroupEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.17.1not-accessiblecurrent
inverterGroupEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of inverterGroupEnergyLogLastWeeksTable
1.3.6.1.4.1.12148.10.16.17.1.1Integer32 (1..52)not-accessiblecurrent
inverterGroupEnergyLogLastWeeksValue
OBJECT-TYPE
Energy value logged every week.
1.3.6.1.4.1.12148.10.16.17.1.2Integer32read-onlycurrent
invertersReactiveEnergyLog
OBJECT-IDENTITY
1.3.6.1.4.1.12148.10.16.18
invertersReactiveEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated reactive energy delivered from inverters.
1.3.6.1.4.1.12148.10.16.18.1Integer32read-onlycurrent
invertersReactiveEnergyLogLastHoursNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter hourly reactive energy log.
1.3.6.1.4.1.12148.10.16.18.2Integer32 (0..52)read-onlycurrent
invertersReactiveEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly reactive energy log of inverters.
1.3.6.1.4.1.12148.10.16.18.3not-accessiblecurrent
invertersReactiveEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.18.3.1not-accessiblecurrent
invertersReactiveEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of invertersReactiveEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.16.18.3.1.1Integer32 (1..52)not-accessiblecurrent
invertersReactiveEnergyLogLastHoursValue
OBJECT-TYPE
Reactive energy value logged every hour.
1.3.6.1.4.1.12148.10.16.18.3.1.2Integer32read-onlycurrent
invertersReactiveEnergyLogLastDaysNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter daily reactive energy log.
1.3.6.1.4.1.12148.10.16.18.4Integer32 (0..52)read-onlycurrent
invertersReactiveEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily reactive energy log of inverters.
1.3.6.1.4.1.12148.10.16.18.5not-accessiblecurrent
invertersReactiveEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.18.5.1not-accessiblecurrent
invertersReactiveEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of invertersReactiveEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.16.18.5.1.1Integer32 (1..52)not-accessiblecurrent
invertersReactiveEnergyLogLastDaysValue
OBJECT-TYPE
Reactive energy value logged every day.
1.3.6.1.4.1.12148.10.16.18.5.1.2Integer32read-onlycurrent
invertersReactiveEnergyLogLastWeeksNumberOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter weekly reactive energy log.
1.3.6.1.4.1.12148.10.16.18.6Integer32 (0..52)read-onlycurrent
invertersReactiveEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly reactive energy log of inverters.
1.3.6.1.4.1.12148.10.16.18.7not-accessiblecurrent
invertersReactiveEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.18.7.1not-accessiblecurrent
invertersReactiveEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of invertersReactiveEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.16.18.7.1.1Integer32 (1..52)not-accessiblecurrent
invertersReactiveEnergyLogLastWeeksValue
OBJECT-TYPE
Reactive energy value logged every week.
1.3.6.1.4.1.12148.10.16.18.7.1.2Integer32read-onlycurrent
inverterGroupReactiveEnergyLogTable
OBJECT-TYPE
This branch contains information about inverters' reactive energy logs of each inverter group.
1.3.6.1.4.1.12148.10.16.19not-accessiblecurrent
inverterGroupReactiveEnergyLogEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.19.1not-accessiblecurrent
inverterGroupReactiveEnergyLogAccumulated
OBJECT-TYPE
This is the accumulated reactive energy delivered from inverters of each inverter group.
1.3.6.1.4.1.12148.10.16.19.1.1Integer32read-onlycurrent
inverterGroupReactiveEnergyLogLastHoursNoOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter group hourly reactive energy log.
1.3.6.1.4.1.12148.10.16.19.1.2Integer32read-onlycurrent
inverterGroupReactiveEnergyLogLastDaysNoOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter group daily reactive energy log.
1.3.6.1.4.1.12148.10.16.19.1.3Integer32read-onlycurrent
inverterGroupReactiveEnergyLogLastWeeksNoOfEntries
OBJECT-TYPE
This is the maximal number of entries stored in inverter group weekly reactive energy log.
1.3.6.1.4.1.12148.10.16.19.1.4Integer32read-onlycurrent
inverterGroupReactiveEnergyLogLastHoursTable
OBJECT-TYPE
This table contains hourly reactive energy log of each inverter group
1.3.6.1.4.1.12148.10.16.20not-accessiblecurrent
inverterGroupReactiveEnergyLogLastHoursEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.20.1not-accessiblecurrent
inverterGroupReactiveEnergyLogLastHoursIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of inverterGroupReactiveEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.16.20.1.1Integer32 (1..52)not-accessiblecurrent
inverterGroupReactiveEnergyLogLastHoursValue
OBJECT-TYPE
Reactive energy value logged every hour.
1.3.6.1.4.1.12148.10.16.20.1.2Integer32read-onlycurrent
inverterGroupReactiveEnergyLogLastDaysTable
OBJECT-TYPE
This table contains daily reactive energy log of each inverter group
1.3.6.1.4.1.12148.10.16.21not-accessiblecurrent
inverterGroupReactiveEnergyLogLastDaysEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.21.1not-accessiblecurrent
inverterGroupReactiveEnergyLogLastDaysIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of inverterGroupReactiveEnergyLogLasDaysTable
1.3.6.1.4.1.12148.10.16.21.1.1Integer32 (1..52)not-accessiblecurrent
inverterGroupReactiveEnergyLogLastDaysValue
OBJECT-TYPE
Reactive energy value logged every day.
1.3.6.1.4.1.12148.10.16.21.1.2Integer32read-onlycurrent
inverterGroupReactiveEnergyLogLastWeeksTable
OBJECT-TYPE
This table contains weekly reactive energy log of each inverter group
1.3.6.1.4.1.12148.10.16.22not-accessiblecurrent
inverterGroupReactiveEnergyLogLastWeeksEntry
OBJECT-TYPE
1.3.6.1.4.1.12148.10.16.22.1not-accessiblecurrent
inverterGroupReactiveEnergyLogLastWeeksIndex
OBJECT-TYPE
Index used for navigating the rows 1..52 of inverterGroupReactiveEnergyLogLastWeeksTable
1.3.6.1.4.1.12148.10.16.22.1.1Integer32 (1..52)not-accessiblecurrent
inverterGroupReactiveEnergyLogLastWeeksValue
OBJECT-TYPE
Reactive energy value logged every week.
1.3.6.1.4.1.12148.10.16.22.1.2Integer32read-onlycurrent

Notifications

NameOIDStatus
alarmPowerSystemTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the power system.
1.3.6.1.4.1.12148.10.1.2.1current
alarmBatteryTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the battery subsystem.
1.3.6.1.4.1.12148.10.1.2.2current
alarmLoadGroupTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the Load subsystem.
1.3.6.1.4.1.12148.10.1.2.3current
alarmMainsTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the Mains subsystem.
1.3.6.1.4.1.12148.10.1.2.4current
alarmRectifierTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the Rectifier subsystem.
1.3.6.1.4.1.12148.10.1.2.5current
alarmControlSystemTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the Control-system subsystem.
1.3.6.1.4.1.12148.10.1.2.6current
alarmDcDcTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the DCDC converter subsystem.
1.3.6.1.4.1.12148.10.1.2.7current
alarmInputsTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the Inputs subsystem.
1.3.6.1.4.1.12148.10.1.2.8current
alarmOutputsTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the Outputs subsystem.
1.3.6.1.4.1.12148.10.1.2.9current
alarmGeneratorTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the Generator subsystem.
1.3.6.1.4.1.12148.10.1.2.10current
alarmSolarChargerTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the SolarCharger subsystem.
1.3.6.1.4.1.12148.10.1.2.11current
alarmWindChargerTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the WindCharger subsystem.
1.3.6.1.4.1.12148.10.1.2.12current
infoHeartBeatTrap
NOTIFICATION-TYPE
When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up.
1.3.6.1.4.1.12148.10.1.2.13current
alarmInverterTrap
NOTIFICATION-TYPE
This Trap is sent when an alarm condition occurs in the Rectifier subsystem.
1.3.6.1.4.1.12148.10.1.2.14current

Conformance

NameOIDStatus
powerSystemTrapsGroup
NOTIFICATION-GROUP
The powerSystem Trap goup. Entry point for the trap list.
1.3.6.1.4.1.12148.10.1.3current