SP2-MIB
- Registered at
- 1.3.6.1.4.1.12148.10
- Namespace
- eltek
- Source file
SP2-MIB- Digest
sha256:37557bca8c87c1cdcf1cb669c05d87fc1570ee25281aa44884bdb4dd78fa6f9a
Imports
| From | Symbols |
|---|---|
| ELTEK-COMMON-MIB | eltek |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Counter32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | DateAndTime, DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
ELTEK-COMMON-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC SP2-MIB
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| eNexus OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10 | |||
| eltekTraps OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.1 | |||
| powerAlarmVars OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.1.1 | |||
| alarmSubsysSourceDescr OBJECT-TYPE A description of the source generating the trap for the Alarm Condition. Used in alarmSubSystemTrap to describe the alarm source. Example: 'batteryVoltageDescription' | 1.3.6.1.4.1.12148.10.1.1.1 | DisplayString (SIZE(0..32)) | accessible-for-notify | current |
| alarmSubsysStatusOid OBJECT-TYPE The OID (name) of the object indicating the alarm-status for which the alarm is generated. The Status must be an INTEGER type. Example: SP2-MIB::batteryVoltage.batteryVoltageStatus 1.3.6.1.4.1.12148.10.3.5.2: This object maybe polled by the SNMP management application, to monitor the current Status object. | 1.3.6.1.4.1.12148.10.1.1.2 | OBJECT IDENTIFIER | accessible-for-notify | current |
| alarmSubsysStatusValue OBJECT-TYPE The value of the Status object of the subsystem for which the alarm-status is generated. The OID (name) of this object is indicated by alarmSubsysStatusOid above. Example: the value of SP2-MIB::batteryVoltage.batteryVoltageStatus one of: error (0), normal (1), minorAlarm (2), etc. | 1.3.6.1.4.1.12148.10.1.1.3 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | accessible-for-notify | current |
| alarmSubsysStatusOnOff OBJECT-TYPE This indicates if the abnormal condition is on or goes off. | 1.3.6.1.4.1.12148.10.1.1.4 | INTEGER {off(0), on(1)} | accessible-for-notify | current |
| alarmMeasuredVarOid OBJECT-TYPE The OID (name) of the measured-object indicating some measurement (e.g voltage) for which the alarm is generated. Example: SP2-MIB::batteryVoltage.batteryVoltageValue 1.3.6.1.4.1.12148.10.3.5.1 This object maybe polled by the SNMP management application, to monitor the current measurement. | 1.3.6.1.4.1.12148.10.1.1.5 | OBJECT IDENTIFIER | accessible-for-notify | current |
| alarmMeasuredVarValue OBJECT-TYPE The value of the measured-object for which the alarm-status is generated, for example 13 volt. The actual value is in units defined by the actual variable (e.g volts). The units must use INTEGER type. The OID (name) of this object is indicated by alarmMeasuredVarOid above. Example: Value of SP2-MIB::batteryVoltage.batteryVoltageValue 'The measured battery voltage' | 1.3.6.1.4.1.12148.10.1.1.6 | Integer32 | accessible-for-notify | current |
| alarmTrapCounterVarValue OBJECT-TYPE | 1.3.6.1.4.1.12148.10.1.1.7 | Integer32 | accessible-for-notify | current |
| powerSystemTraps OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.1.2 | |||
| powerSystem OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.2 | |||
| powerSystemStatus OBJECT-TYPE A status value showing the overall condition of the power system. | 1.3.6.1.4.1.12148.10.2.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| powerSystemType OBJECT-TYPE A value showing the type of the power system, which is named after the main controller. | 1.3.6.1.4.1.12148.10.2.2 | INTEGER {smartpack2(1), smartpackS(2), compack(3)} | read-only | current |
| powerSystemMode OBJECT-TYPE A summary status showing if the system is in test, boost, float, equalize, emergency or start-up delay mode | 1.3.6.1.4.1.12148.10.2.3 | INTEGER {off(0), test(1), boost(2), float(3), emergency(4), startupdelay(5), equalize(6)} | read-only | current |
| powerSystemCompany OBJECT-TYPE The Copmany name (as stored in the Control Unit). | 1.3.6.1.4.1.12148.10.2.4 | DisplayString (SIZE(0..32)) | read-write | current |
| powerSystemSite OBJECT-TYPE The system/site Location details (as stored in the Control Unit). | 1.3.6.1.4.1.12148.10.2.5 | DisplayString (SIZE(0..32)) | read-write | current |
| powerSystemModel OBJECT-TYPE The model/part number of the power system (as stored in the Control Unit). | 1.3.6.1.4.1.12148.10.2.6 | DisplayString (SIZE(0..32)) | read-only | current |
| powerSystemSerialNumber OBJECT-TYPE The serial number for the complete system. | 1.3.6.1.4.1.12148.10.2.7 | DisplayString (SIZE(0..16)) | read-write | current |
| powerSystemInstallDate OBJECT-TYPE The system's Installation date (as stored in the Control Unit). | 1.3.6.1.4.1.12148.10.2.8 | DateAndTime | read-write | current |
| powerSystemNominalVoltage OBJECT-TYPE The nominal voltage rating. 12V/24V/48V/60V/110V/220V/380V etc. systems. | 1.3.6.1.4.1.12148.10.2.9 | Integer32 | read-only | current |
| powerSystemLongitude OBJECT-TYPE A part of the systems global positioning data. The range +-180degrees Longitude lines are imaginary lines running from the north pole to the south pole. Longitudes are usually (WGS84) referenced from Greenwich, England where it has been established as Zero Degrees longitude. Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this. | 1.3.6.1.4.1.12148.10.2.10 | Integer32 (-180..180) | read-write | current |
| powerSystemLongitudeDecimal OBJECT-TYPE The decimal part of dcSystemLatitude contains up to 7digits. This number is in 1/1000000 degree fractions or 0,0000001 degree. A part of the systems global positioning data. Longitude lines are imaginary lines running from the north pole to the south pole. Longitudes are usually (WGS84) referenced from Greenwich, England where it has been established as Zero Degrees longitude. Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this. | 1.3.6.1.4.1.12148.10.2.11 | Integer32 | read-write | current |
| powerSystemLatitude OBJECT-TYPE A part of the systems global positioning data. The latitude gives the location of a place on Earth (or other planetary body) north or south of the equator. Lines of Latitude has a range of +-90 degrees and are the imaginary horizontal lines shown running east-to-west (or west to east). Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this. | 1.3.6.1.4.1.12148.10.2.12 | Integer32 (-90..90) | read-write | current |
| powerSystemLatitudeDecimal OBJECT-TYPE The decimal part of dcSystemLatitude contains up to 7digits. This number is in 1/1000000 degree fractions or 0,0000001 degree. A part of the systems global positioning data. Lines of Latitude has a range of +-90 degrees and are the imaginary horizontal lines shown running east-to-west (or west to east). Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this. Longitude lines are imaginary lines running from the north pole to the south pole. Longitudes are usually (WGS84) referenced from Greenwich, England where it has been established as Zero Degrees longitude. Latitude and Longitude together with the Elevation can be used for automagically placing system icons on NMS/Sitemonitors system that support this. | 1.3.6.1.4.1.12148.10.2.13 | Integer32 | read-write | current |
| powerSystemElevation OBJECT-TYPE A part of the systems global positioning data. This is the sites height above sealevel in Meters. The Elevation together with Latituse and Longitude is used for automagically placing system icons on NMS/Sitemonitors system that support this. | 1.3.6.1.4.1.12148.10.2.14 | Integer32 | read-write | current |
| powerSystemCurrentDecimalSetting OBJECT-TYPE A global flag telling if the current values in the system is Amperes or DeciAmpres | 1.3.6.1.4.1.12148.10.2.15 | INTEGER {ampere(0), deciAmpere(1)} | read-write | current |
| powerSystemTemperatureScale OBJECT-TYPE A flag telling if the temperatures values in the system is of Celcius or Fahrenheit type | 1.3.6.1.4.1.12148.10.2.16 | INTEGER {celcius(0), fahrenheit(1)} | read-write | current |
| powerSystemCapacityScale OBJECT-TYPE A flag telling if the system's battery capacity value is a percentage of a fully charged battery, or in AmpereHours | 1.3.6.1.4.1.12148.10.2.17 | INTEGER {ah(0), percent(1)} | read-write | current |
| mains OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.3 | |||
| mainsStatus OBJECT-TYPE The overall status of mains/AC feed subsystem. | 1.3.6.1.4.1.12148.10.3.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsMainsFailure OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.3.2 | |||
| mainsMainsFailureStatus OBJECT-TYPE This status value shows if the number of failed phases is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.3.2.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsMainsFailureDescription OBJECT-TYPE A textual description of the mains phase failure monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.3.2.2 | DisplayString (SIZE(0..16)) | read-write | current |
| mainsMainsFailureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.3.2.3 | Integer32 | accessible-for-notify | current |
| mainsMainsFailureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.3.2.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainsMainsFailureValue OBJECT-TYPE The detected number of failed phases. | 1.3.6.1.4.1.12148.10.3.2.5 | Integer32 | read-only | current |
| mainsMainsFailureMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.3.2.6 | Integer32 | read-write | current |
| mainsMainsFailureMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.3.2.7 | Integer32 | read-write | current |
| mainsNumberOfPhases OBJECT-TYPE This value showing the number of phases of the mains subsystem. | 1.3.6.1.4.1.12148.10.3.3 | Integer32 | read-write | current |
| mainsVoltageTable OBJECT-TYPE This table contains information about mains voltage monitor | 1.3.6.1.4.1.12148.10.3.4 | not-accessible | current | |
| mainsVoltageEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.4.1 | not-accessible | current | |
| mainsVoltageIndex OBJECT-TYPE Index used for navigating the rows 1..12 of mainsVoltageTable | 1.3.6.1.4.1.12148.10.3.4.1.1 | Integer32 (1..12) | not-accessible | current |
| mainsVoltageStatus OBJECT-TYPE The status of the measured mains voltage. | 1.3.6.1.4.1.12148.10.3.4.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsVoltageDescription OBJECT-TYPE A textual description of the mains voltage monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.3.4.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| mainsVoltageTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.3.4.1.4 | Counter32 | accessible-for-notify | current |
| mainsVoltageAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.3.4.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainsVoltageValue OBJECT-TYPE The value of the measured mains voltage. | 1.3.6.1.4.1.12148.10.3.4.1.6 | Integer32 | read-only | current |
| mainsVoltageMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.3.4.1.7 | Integer32 | read-write | current |
| mainsVoltageMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.3.4.1.8 | Integer32 | read-write | current |
| mainsVoltageMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.3.4.1.9 | Integer32 | read-write | current |
| mainsVoltageMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.3.4.1.10 | Integer32 | read-write | current |
| mainsMonitors OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.3.5 | |||
| mainsMonitorsNumberOfUnits OBJECT-TYPE This is the number of AC Mains Monitor CAN Nodes installed in the system. | 1.3.6.1.4.1.12148.10.3.5.1 | Integer32 (0..14) | read-write | current |
| mainsMonitorsTable OBJECT-TYPE This table contains the number of voltage, current and frequency measurements in each AC Mains Monitor | 1.3.6.1.4.1.12148.10.3.5.2 | not-accessible | current | |
| mainsMonitorsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.5.2.1 | not-accessible | current | |
| mainsMonitorIndex OBJECT-TYPE Index used for navigating the rows of mainsMonitorsTable The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.3.5.2.1.1 | Integer32 (1..14) | not-accessible | current |
| mainsMonitorNumberOfVoltages OBJECT-TYPE The number of voltage measurements in the AC Mains Monitor | 1.3.6.1.4.1.12148.10.3.5.2.1.2 | Integer32 (0..3) | read-only | current |
| mainsMonitorNumberOfCurrents OBJECT-TYPE The number of current measurements in the AC Mains Monitor | 1.3.6.1.4.1.12148.10.3.5.2.1.3 | Integer32 (0..3) | read-only | current |
| mainsMonitorNumberOfFrequencies OBJECT-TYPE The number of frequency measurements in the AC Mains Monitor | 1.3.6.1.4.1.12148.10.3.5.2.1.4 | Integer32 (0..3) | read-only | current |
| mainsMonitorVoltageTable OBJECT-TYPE This table contains information about mains voltage in AC Mains Monitor | 1.3.6.1.4.1.12148.10.3.5.3 | not-accessible | current | |
| mainsMonitorVoltageEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.5.3.1 | not-accessible | current | |
| mainsMonitorPhaseIndex OBJECT-TYPE Index used for navigating the rows 1..3 of mainsMonitorVolatgeTable | 1.3.6.1.4.1.12148.10.3.5.3.1.1 | Integer32 (1..3) | not-accessible | current |
| mainsMonitorVoltageStatus OBJECT-TYPE The status of the measured mains voltage in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.3.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsMonitorVoltageDescription OBJECT-TYPE A textual description of the mains voltage in AC Mains Monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.3.5.3.1.3 | DisplayString (SIZE(1..16)) | read-write | current |
| mainsMonitorVoltageTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.3.5.3.1.4 | Counter32 | accessible-for-notify | current |
| mainsMonitorVoltageAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.3.5.3.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainsMonitorVoltageValue OBJECT-TYPE The value of the measured mains voltage in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.3.1.6 | Integer32 | read-only | current |
| mainsMonitorVoltageMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.3.5.3.1.7 | Integer32 | read-write | current |
| mainsMonitorVoltageMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.3.5.3.1.8 | Integer32 | read-write | current |
| mainsMonitorVoltageMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.3.5.3.1.9 | Integer32 | read-write | current |
| mainsMonitorVoltageMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.3.5.3.1.10 | Integer32 | read-write | current |
| mainsMonitorCurrentTable OBJECT-TYPE This table contains information about mains current in AC Mains Monitor | 1.3.6.1.4.1.12148.10.3.5.4 | not-accessible | current | |
| mainsMonitorCurrentEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.5.4.1 | not-accessible | current | |
| mainsMonitorCurrentStatus OBJECT-TYPE The status of the measured mains current in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.4.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsMonitorCurrentDescription OBJECT-TYPE A textual description of the mains current in AC Mains Monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.3.5.4.1.2 | DisplayString (SIZE(1..16)) | read-write | current |
| mainsMonitorCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.3.5.4.1.3 | Counter32 | accessible-for-notify | current |
| mainsMonitorCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.3.5.4.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainsMonitorCurrentValue OBJECT-TYPE The value of the measured mains current in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.4.1.5 | Integer32 | read-only | current |
| mainsMonitorCurrentMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.3.5.4.1.6 | Integer32 | read-write | current |
| mainsMonitorCurrentMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.3.5.4.1.7 | Integer32 | read-write | current |
| mainsMonitorFrequencyTable OBJECT-TYPE This table contains information about mains frequency in AC Mains Monitor | 1.3.6.1.4.1.12148.10.3.5.5 | not-accessible | current | |
| mainsMonitorFrequencyEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.5.5.1 | not-accessible | current | |
| mainsMonitorFrequencyStatus OBJECT-TYPE The status of the measured mains frequency in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.5.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsMonitorFrequencyDescription OBJECT-TYPE A textual description of the mains frequency in AC Mains Monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.3.5.5.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| mainsMonitorFrequencyTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.3.5.5.1.3 | Counter32 | accessible-for-notify | current |
| mainsMonitorFrequencyAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.3.5.5.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainsMonitorFrequencyValue OBJECT-TYPE The value of the measured mains frequency in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.5.1.5 | Integer32 | read-only | current |
| mainsMonitorFrequencyMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.3.5.5.1.6 | Integer32 | read-write | current |
| mainsMonitorFrequencyMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.3.5.5.1.7 | Integer32 | read-write | current |
| mainsMonitorFrequencyMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.3.5.5.1.8 | Integer32 | read-write | current |
| mainsMonitorFrequencyMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.3.5.5.1.9 | Integer32 | read-write | current |
| mainsMonitorEnergyLogAccumulatedTable OBJECT-TYPE This table contains the accumulated energy consumption measured in AC Mains Monitor | 1.3.6.1.4.1.12148.10.3.5.6 | not-accessible | current | |
| mainsMonitorEnergyLogAccumulatedEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.5.6.1 | not-accessible | current | |
| mainsMonitorEnergyLogAccumulated OBJECT-TYPE The accumulated energy consumption value | 1.3.6.1.4.1.12148.10.3.5.6.1.1 | Integer32 | read-only | current |
| mainsMonitorEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in hourly energy log | 1.3.6.1.4.1.12148.10.3.5.7 | Integer32 (0..52) | read-only | current |
| mainsMonitorEnergyLogLastHoursTable OBJECT-TYPE This table contains energy consumption values logged every hour in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.8 | not-accessible | current | |
| mainsMonitorEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.5.8.1 | not-accessible | current | |
| mainsMonitorEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.3.5.8.1.1 | Integer32 (1..52) | not-accessible | current |
| mainsMonitorEnergyLogLastHoursValue OBJECT-TYPE Energy consumption value logged every hour in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.8.1.2 | Integer32 | read-only | current |
| mainsMonitorEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in daily energy log | 1.3.6.1.4.1.12148.10.3.5.9 | Integer32 (0..52) | read-only | current |
| mainsMonitorEnergyLogLastDaysTable OBJECT-TYPE This table contains energy consumption values logged every day in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.10 | not-accessible | current | |
| mainsMonitorEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.5.10.1 | not-accessible | current | |
| mainsMonitorEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.3.5.10.1.1 | Integer32 (1..52) | not-accessible | current |
| mainsMonitorEnergyLogLastDaysValue OBJECT-TYPE Energy consumption value logged every day in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.10.1.2 | Integer32 | read-only | current |
| mainsMonitorEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in weekly energy log | 1.3.6.1.4.1.12148.10.3.5.11 | Integer32 (0..52) | read-only | current |
| mainsMonitorEnergyLogLastWeeksTable OBJECT-TYPE This table contains energy consumption values logged every week in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.12 | not-accessible | current | |
| mainsMonitorEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.5.12.1 | not-accessible | current | |
| mainsMonitorEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastWeeksTable | 1.3.6.1.4.1.12148.10.3.5.12.1.1 | Integer32 (1..52) | not-accessible | current |
| mainsMonitorEnergyLogLastWeeksValue OBJECT-TYPE Energy consumption value logged every week in AC Mains Monitor. | 1.3.6.1.4.1.12148.10.3.5.12.1.2 | Integer32 | read-only | current |
| mainsOutageLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.3.6 | |||
| mainsOutageTotal OBJECT-TYPE This is the total mains outage time measured in hours. | 1.3.6.1.4.1.12148.10.3.6.1 | Integer32 | read-only | current |
| mainsOutageLogDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in daily mains outage log. | 1.3.6.1.4.1.12148.10.3.6.2 | Integer32 (0..52) | read-only | current |
| mainsOutageLogDaysTable OBJECT-TYPE This table contains daily mains outage time log. | 1.3.6.1.4.1.12148.10.3.6.3 | not-accessible | current | |
| mainsOutageLogDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.6.3.1 | not-accessible | current | |
| mainsOutageLogDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of mainsOutageLogDaysTable | 1.3.6.1.4.1.12148.10.3.6.3.1.1 | Integer32 (1..52) | not-accessible | current |
| mainsOutageLogDaysValue OBJECT-TYPE Mains outage time value in minutes, logged every day. | 1.3.6.1.4.1.12148.10.3.6.3.1.2 | Integer32 | read-only | current |
| mainsOutageLogWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in weekly mains outage time log. | 1.3.6.1.4.1.12148.10.3.6.4 | Integer32 (0..52) | read-only | current |
| mainsOutageLogWeeksTable OBJECT-TYPE This table contains weekly mains outage time log. | 1.3.6.1.4.1.12148.10.3.6.5 | not-accessible | current | |
| mainsOutageLogWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.6.5.1 | not-accessible | current | |
| mainsOutageLogWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of mainsOutageLogWeeksTable | 1.3.6.1.4.1.12148.10.3.6.5.1.1 | Integer32 (1..52) | not-accessible | current |
| mainsOutageLogWeeksValue OBJECT-TYPE Mains outage time value in hours, logged every week. | 1.3.6.1.4.1.12148.10.3.6.5.1.2 | Integer32 | read-only | current |
| mainsOutageLogMonthsNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in monthly mains outage time log. | 1.3.6.1.4.1.12148.10.3.6.6 | Integer32 (0..52) | read-only | current |
| mainsOutageLogMonthsTable OBJECT-TYPE This table contains monthly mains outage time log. | 1.3.6.1.4.1.12148.10.3.6.7 | not-accessible | current | |
| mainsOutageLogMonthsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.6.7.1 | not-accessible | current | |
| mainsOutageLogMonthsIndex OBJECT-TYPE Index used for navigating the rows 1..52 of mainsOutageLogMonthsTable | 1.3.6.1.4.1.12148.10.3.6.7.1.1 | Integer32 (1..52) | not-accessible | current |
| mainsOutageLogMonthsValue OBJECT-TYPE Mains outage time value in hours, logged every month. | 1.3.6.1.4.1.12148.10.3.6.7.1.2 | Integer32 | read-only | current |
| mainsNumberOfGroups OBJECT-TYPE This value showing the number of groups of the mains subsystem. | 1.3.6.1.4.1.12148.10.3.7 | Integer32 | read-only | current |
| mainsGroupsTable OBJECT-TYPE This table contains the status of mains group and number of phases in each group. | 1.3.6.1.4.1.12148.10.3.8 | not-accessible | current | |
| mainsGroupsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.8.1 | not-accessible | current | |
| mainsGroupIndex OBJECT-TYPE Index used for navigating the rows 1..10 of mainsGroupTable | 1.3.6.1.4.1.12148.10.3.8.1.1 | Integer32 (1..10) | not-accessible | current |
| mainsGroupStatus OBJECT-TYPE The status of mains group. | 1.3.6.1.4.1.12148.10.3.8.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsGroupNumberOfPhases OBJECT-TYPE This value showing the number of phases of the mains group subsystem. | 1.3.6.1.4.1.12148.10.3.8.1.3 | Integer32 | read-write | current |
| mainsGroupMainsFailureTable OBJECT-TYPE This table contains information about mains failure monitor of mains group | 1.3.6.1.4.1.12148.10.3.9 | not-accessible | current | |
| mainsGroupMainsFailureEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.9.1 | not-accessible | current | |
| mainsGroupMainsFailureStatus OBJECT-TYPE This status value shows if the number of failed phases is higher than the defined alarm level for the mains group | 1.3.6.1.4.1.12148.10.3.9.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsGroupMainsFailureDescription OBJECT-TYPE A textual description of the mains group phase failure monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.3.9.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| mainsGroupMainsFailureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.3.9.1.3 | Integer32 | accessible-for-notify | current |
| mainsGroupMainsFailureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.3.9.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainsGroupMainsFailureValue OBJECT-TYPE The detected number of failed phases in the mains group. | 1.3.6.1.4.1.12148.10.3.9.1.5 | Integer32 | read-only | current |
| mainsGroupMainsFailureMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.3.9.1.6 | Integer32 | read-write | current |
| mainsGroupMainsFailureMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.3.9.1.7 | Integer32 | read-write | current |
| mainsGroupVoltageTable OBJECT-TYPE This table contains information about mains voltage monitors for mains group | 1.3.6.1.4.1.12148.10.3.10 | not-accessible | current | |
| mainsGroupVoltageEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.10.1 | not-accessible | current | |
| mainsGroupVoltageIndex OBJECT-TYPE Index used for navigating the rows 1..12 of mainsGroupVoltageTable | 1.3.6.1.4.1.12148.10.3.10.1.1 | Integer32 (1..12) | not-accessible | current |
| mainsGroupVoltageStatus OBJECT-TYPE The status of the measured mains voltage of the mains group. | 1.3.6.1.4.1.12148.10.3.10.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsGroupVoltageDescription OBJECT-TYPE A textual description of the mains voltage monitor of the mains group. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.3.10.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| mainsGroupVoltageTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.3.10.1.4 | Integer32 | accessible-for-notify | current |
| mainsGroupVoltageAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.3.10.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainsGroupVoltageValue OBJECT-TYPE The value of the measured mains voltage in the mains group. | 1.3.6.1.4.1.12148.10.3.10.1.6 | Integer32 | read-only | current |
| mainsGroupVoltageMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.3.10.1.7 | Integer32 | read-write | current |
| mainsGroupVoltageMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.3.10.1.8 | Integer32 | read-write | current |
| mainsGroupVoltageMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.3.10.1.9 | Integer32 | read-write | current |
| mainsGroupVoltageMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.3.10.1.10 | Integer32 | read-write | current |
| mainsGroupOutageLogTable OBJECT-TYPE This table contains total mains outage of the mains group and number of entries in each log table. | 1.3.6.1.4.1.12148.10.3.11 | not-accessible | current | |
| mainsGroupOutageLogEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.11.1 | not-accessible | current | |
| mainsGroupOutageTotal OBJECT-TYPE This is the total mains outage time measured in hours in the mains group. | 1.3.6.1.4.1.12148.10.3.11.1.1 | Integer32 | read-only | current |
| mainsGroupOutageLogDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in daily mains outage log. | 1.3.6.1.4.1.12148.10.3.11.1.2 | Integer32 | read-only | current |
| mainsGroupOutageLogWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in weekly mains outage time log. | 1.3.6.1.4.1.12148.10.3.11.1.3 | Integer32 | read-only | current |
| mainsGroupOutageLogMonthsNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in monthly mains outage time log. | 1.3.6.1.4.1.12148.10.3.11.1.4 | Integer32 | read-only | current |
| mainsGroupOutageLogDaysTable OBJECT-TYPE This table contains daily mains outage time log of mains group. | 1.3.6.1.4.1.12148.10.3.12 | not-accessible | current | |
| mainsGroupOutageLogDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.12.1 | not-accessible | current | |
| mainsGroupOutageLogDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of mainsGroupOutageLogDaysTable | 1.3.6.1.4.1.12148.10.3.12.1.1 | Integer32 (1..52) | not-accessible | current |
| mainsGroupOutageLogDaysValue OBJECT-TYPE Mains outage time value in minutes of each mains group, logged every day. | 1.3.6.1.4.1.12148.10.3.12.1.2 | Integer32 | read-only | current |
| mainsGroupOutageLogWeeksTable OBJECT-TYPE This table contains weekly mains outage time log of mains group. | 1.3.6.1.4.1.12148.10.3.13 | not-accessible | current | |
| mainsGroupOutageLogWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.13.1 | not-accessible | current | |
| mainsGroupOutageLogWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of mainsGroupOutageLogWeeksTable | 1.3.6.1.4.1.12148.10.3.13.1.1 | Integer32 (1..52) | not-accessible | current |
| mainsGroupOutageLogWeeksValue OBJECT-TYPE Mains outage time value in hours of each mains group, logged every week. | 1.3.6.1.4.1.12148.10.3.13.1.2 | Integer32 | read-only | current |
| mainsGroupOutageLogMonthsTable OBJECT-TYPE This table contains monthly mains outage time log of mains group. | 1.3.6.1.4.1.12148.10.3.14 | not-accessible | current | |
| mainsGroupOutageLogMonthsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.3.14.1 | not-accessible | current | |
| mainsGroupOutageLogMonthsIndex OBJECT-TYPE Index used for navigating the rows 1..52 of mainsGroupOutageLogMonthsTable | 1.3.6.1.4.1.12148.10.3.14.1.1 | Integer32 (1..52) | not-accessible | current |
| mainsGroupOutageLogMonthsValue OBJECT-TYPE Mains outage time value in hours of each mains group, logged every month. | 1.3.6.1.4.1.12148.10.3.14.1.2 | Integer32 | read-only | current |
| generator OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.4 | |||
| generatorStatus OBJECT-TYPE The overall status of generator subsystem. | 1.3.6.1.4.1.12148.10.4.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| generatorFailStatus OBJECT-TYPE The status of generator failure monitor. | 1.3.6.1.4.1.12148.10.4.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| generatorActivation OBJECT-TYPE Indicate if the generator run output signal is activated. | 1.3.6.1.4.1.12148.10.4.3 | Integer32 | read-only | current |
| generatorDischargeValue OBJECT-TYPE This is the present discharge value in percentage of total capacity. | 1.3.6.1.4.1.12148.10.4.4 | Integer32 | read-only | current |
| generatorMainsDelay OBJECT-TYPE Elapsing time of mains failure. | 1.3.6.1.4.1.12148.10.4.5 | Integer32 | read-only | current |
| generatorChargeTime OBJECT-TYPE Elapsing time of charging with generator running. | 1.3.6.1.4.1.12148.10.4.6 | Integer32 | read-only | current |
| generatorCapacityControlledStartStopEnable OBJECT-TYPE Battery charge/discharge level control of starting and stopping of generator | 1.3.6.1.4.1.12148.10.4.7 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| generatorCapacityStartOnDischargeLimit OBJECT-TYPE When the generatorCapacityControlled is enabled, the generator is started when the remaining battery capacity drops below this limit in percentage of the total capacity. | 1.3.6.1.4.1.12148.10.4.8 | Integer32 (0..100) | read-write | current |
| generatorCapacityStopOnChargeLimit OBJECT-TYPE When the generatorCapacityControlled is enabled, the generator is stopped when the remaining battery capacity is greater than this limit in percentage of the total capacity. | 1.3.6.1.4.1.12148.10.4.9 | Integer32 (0..100) | read-write | current |
| generatorCurrentLimitControlledStopEnable OBJECT-TYPE Enables the generator to stop when the charge current drops below generatorCurrentLimitControlledStopValue. | 1.3.6.1.4.1.12148.10.4.10 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| generatorCurrentLimitControlledStopValue OBJECT-TYPE Generator stops when the charge current drop drops below this level. | 1.3.6.1.4.1.12148.10.4.11 | Integer32 (0..100) | read-write | current |
| generatorVoltageControlledStartEnable OBJECT-TYPE Enable/disable voltage controlled generator activation. | 1.3.6.1.4.1.12148.10.4.12 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| generatorVoltageControlStartVoltage OBJECT-TYPE The voltage limit to start generator. | 1.3.6.1.4.1.12148.10.4.13 | Integer32 | read-write | current |
| generatorVoltageControlStopAfter OBJECT-TYPE A time delay for stopping generator when generator is activated by voltage. | 1.3.6.1.4.1.12148.10.4.14 | Integer32 | read-write | current |
| generatorDailyRunEnable OBJECT-TYPE Enable/disable generator daily run function. | 1.3.6.1.4.1.12148.10.4.15 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| generatorDailyRunSetupTable OBJECT-TYPE This table contains configurations of generator daily run. | 1.3.6.1.4.1.12148.10.4.16 | not-accessible | current | |
| generatorDailyRunSetupEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.16.1 | not-accessible | current | |
| generatorDailyRunDayIndex OBJECT-TYPE Index used for navigating the rows 1..7 of generatorDailyRunSetupTable | 1.3.6.1.4.1.12148.10.4.16.1.1 | INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7)} | not-accessible | current |
| generatorDailyRunStartHour OBJECT-TYPE Generator daily starting time. | 1.3.6.1.4.1.12148.10.4.16.1.2 | Integer32 (0..23) | read-write | current |
| generatorDailyRunStopHour OBJECT-TYPE Generator daily stopping time. | 1.3.6.1.4.1.12148.10.4.16.1.3 | Integer32 (0..23) | read-write | current |
| generatorMonthlyRunEnable OBJECT-TYPE Enable/disable generator monthly run function. | 1.3.6.1.4.1.12148.10.4.17 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| generatorMonthlyRunStartTime OBJECT-TYPE Generator monthly run starting time. | 1.3.6.1.4.1.12148.10.4.18 | Integer32 (0..23) | read-write | current |
| generatorMonthlyRunStartDayinMonth1 OBJECT-TYPE Generator monthly run starting day #1. | 1.3.6.1.4.1.12148.10.4.19 | Integer32 (1..32) | read-write | current |
| generatorMonthlyRunStartDayinMonth2 OBJECT-TYPE Generator monthly run starting day #2. | 1.3.6.1.4.1.12148.10.4.20 | Integer32 (1..32) | read-write | current |
| generatorTankNumberOfTanks OBJECT-TYPE Number of fuel tanks. | 1.3.6.1.4.1.12148.10.4.21 | Integer32 (0..2) | read-only | current |
| generatorTankTable OBJECT-TYPE This table contains information about generator fuel tanks. | 1.3.6.1.4.1.12148.10.4.22 | not-accessible | current | |
| generatorTankEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.22.1 | not-accessible | current | |
| generatorTankIndex OBJECT-TYPE Index used for navigating the rows 1..2 of generatorTankTable | 1.3.6.1.4.1.12148.10.4.22.1.1 | Integer32 (1..2) | not-accessible | current |
| generatorTankStatus OBJECT-TYPE The status of the measured fuel level in tank. | 1.3.6.1.4.1.12148.10.4.22.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| generatorTankDescription OBJECT-TYPE A textual description of the fuel level monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.4.22.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| generatorTankTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.4.22.1.4 | Counter32 | accessible-for-notify | current |
| generatorTankEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.4.22.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| generatorTankValue OBJECT-TYPE The value of the measured fuel level. | 1.3.6.1.4.1.12148.10.4.22.1.6 | Integer32 | read-only | current |
| generatorTankMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.4.22.1.7 | Integer32 | read-write | current |
| generatorTankMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.4.22.1.8 | Integer32 | read-write | current |
| generatorTankMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.4.22.1.9 | Integer32 | read-write | current |
| generatorTankMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.4.22.1.10 | Integer32 | read-write | current |
| generatorEnergyLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.4.23 | |||
| generatorEnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered through rectifiers from generator. | 1.3.6.1.4.1.12148.10.4.23.1 | Integer32 | read-only | current |
| generatorEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in generator hourly energy log. | 1.3.6.1.4.1.12148.10.4.23.2 | Integer32 (0..52) | read-only | current |
| generatorEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly energy log of generator. | 1.3.6.1.4.1.12148.10.4.23.3 | not-accessible | current | |
| generatorEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.23.3.1 | not-accessible | current | |
| generatorEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of generatorEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.4.23.3.1.1 | Integer32 (1..52) | not-accessible | current |
| generatorEnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.4.23.3.1.2 | Integer32 | read-only | current |
| generatorEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in generator daily energy log. | 1.3.6.1.4.1.12148.10.4.23.4 | Integer32 (0..52) | read-only | current |
| generatorEnergyLogLastDaysTable OBJECT-TYPE This table contains daily energy log of generator. | 1.3.6.1.4.1.12148.10.4.23.5 | not-accessible | current | |
| generatorEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.23.5.1 | not-accessible | current | |
| generatorEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of generatorEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.4.23.5.1.1 | Integer32 (1..52) | not-accessible | current |
| generatorEnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day | 1.3.6.1.4.1.12148.10.4.23.5.1.2 | Integer32 | read-only | current |
| generatorEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in generator weekly energy log. | 1.3.6.1.4.1.12148.10.4.23.6 | Integer32 (0..52) | read-only | current |
| generatorEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly energy log of generator. | 1.3.6.1.4.1.12148.10.4.23.7 | not-accessible | current | |
| generatorEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.23.7.1 | not-accessible | current | |
| generatorEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of generatorEnergyLogLastWeeksTable | 1.3.6.1.4.1.12148.10.4.23.7.1.1 | Integer32 (1..52) | not-accessible | current |
| generatorEnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.4.23.7.1.2 | Integer32 | read-only | current |
| generatorRunHoursLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.4.24 | |||
| generatorRunHoursTotalHours OBJECT-TYPE This is the total generator running hours. | 1.3.6.1.4.1.12148.10.4.24.1 | Integer32 | read-only | current |
| generatorRunHoursLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in generator daily running hours log. | 1.3.6.1.4.1.12148.10.4.24.2 | Integer32 (0..52) | read-only | current |
| generatorRunHoursLogLastDaysTable OBJECT-TYPE generator running time in minutes | 1.3.6.1.4.1.12148.10.4.24.3 | not-accessible | current | |
| generatorRunHoursLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.24.3.1 | not-accessible | current | |
| generatorRunHoursLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of generatorRunHoursLogLastDaysTable | 1.3.6.1.4.1.12148.10.4.24.3.1.1 | Integer32 (1..52) | not-accessible | current |
| generatorRunHoursLogLastDaysValue OBJECT-TYPE Generator running time in minutes, logged every day. | 1.3.6.1.4.1.12148.10.4.24.3.1.2 | Integer32 | read-only | current |
| generatorRunHoursLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in generator weekly running hours log. | 1.3.6.1.4.1.12148.10.4.24.4 | Integer32 (0..52) | read-only | current |
| generatorRunHoursLogLastWeeksTable OBJECT-TYPE generator running time in hours | 1.3.6.1.4.1.12148.10.4.24.5 | not-accessible | current | |
| generatorRunHoursLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.24.5.1 | not-accessible | current | |
| generatorRunHoursLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of generatorRunHoursLogLastWeeksTable | 1.3.6.1.4.1.12148.10.4.24.5.1.1 | Integer32 (1..52) | not-accessible | current |
| generatorRunHoursLogLastWeeksValue OBJECT-TYPE Generator running time in hours, logged every week. | 1.3.6.1.4.1.12148.10.4.24.5.1.2 | Integer32 | read-only | current |
| generatorRunHoursLogLastMonthsNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in generator monthly running hours log. | 1.3.6.1.4.1.12148.10.4.24.6 | Integer32 (0..52) | read-only | current |
| generatorRunHoursLogLastMonthsTable OBJECT-TYPE generator running time in hours | 1.3.6.1.4.1.12148.10.4.24.7 | not-accessible | current | |
| generatorRunHoursLogLastMonthsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.24.7.1 | not-accessible | current | |
| generatorRunHoursLogLastMonthsIndex OBJECT-TYPE Index used for navigating the rows 1..52 of generatorRunHoursLogLastMonthsTable | 1.3.6.1.4.1.12148.10.4.24.7.1.1 | Integer32 (1..52) | not-accessible | current |
| generatorRunHoursLogLastMonthsValue OBJECT-TYPE Generator running time in hours, logged every month. | 1.3.6.1.4.1.12148.10.4.24.7.1.2 | Integer32 | read-only | current |
| generatorFuelConsumptionLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.4.25 | |||
| generatorFuelConsumptionTotalUsedTable OBJECT-TYPE This table contains total fuel consumption for each tank. | 1.3.6.1.4.1.12148.10.4.25.1 | not-accessible | current | |
| generatorFuelConsumptionTotalUsedEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.25.1.1 | not-accessible | current | |
| generatorFuelConsumptionTotalUsed OBJECT-TYPE Total fuel consumption value. | 1.3.6.1.4.1.12148.10.4.25.1.1.1 | Integer32 | read-only | current |
| generatorFuelConsumptionLogLastDaysNoOfEntries OBJECT-TYPE This is the maximal number of entries stored in generator daily fuel consumption log. | 1.3.6.1.4.1.12148.10.4.25.2 | Integer32 (0..52) | read-only | current |
| generatorFuelConsumptionLogLastDaysTable OBJECT-TYPE This table contains generator daily fuel consumption log. | 1.3.6.1.4.1.12148.10.4.25.3 | not-accessible | current | |
| generatorFuelConsumptionLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.25.3.1 | not-accessible | current | |
| generatorFuelConsumptionLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastDaysTable | 1.3.6.1.4.1.12148.10.4.25.3.1.1 | Integer32 (1..52) | not-accessible | current |
| generatorFuelConsumptionLogLastDaysValue OBJECT-TYPE Generator fuel consumption value, logged every day. | 1.3.6.1.4.1.12148.10.4.25.3.1.2 | Integer32 | read-only | current |
| generatorFuelConsumptionLogLastWeeksNoOfEntries OBJECT-TYPE This is the maximal number of entries stored in generator weekly fuel consumption log. | 1.3.6.1.4.1.12148.10.4.25.4 | Integer32 (0..52) | read-only | current |
| generatorFuelConsumptionLogLastWeeksTable OBJECT-TYPE This table contains generator weekly fuel consumption log. | 1.3.6.1.4.1.12148.10.4.25.5 | not-accessible | current | |
| generatorFuelConsumptionLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.25.5.1 | not-accessible | current | |
| generatorFuelConsumptionLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastWeeksTable | 1.3.6.1.4.1.12148.10.4.25.5.1.1 | Integer32 (1..52) | not-accessible | current |
| generatorFuelConsumptionLogLastWeeksValue OBJECT-TYPE Generator fuel consumption value, logged every week. | 1.3.6.1.4.1.12148.10.4.25.5.1.2 | Integer32 | read-only | current |
| generatorFuelConsumptionLogLastMonthsNoOfEntries OBJECT-TYPE This is the maximal number of entries stored in generator hourly fuel consumption log. | 1.3.6.1.4.1.12148.10.4.25.6 | Integer32 (0..52) | read-only | current |
| generatorFuelConsumptionLogLastMonthsTable OBJECT-TYPE This table contains generator hourly fuel consumption log. | 1.3.6.1.4.1.12148.10.4.25.7 | not-accessible | current | |
| generatorFuelConsumptionLogLastMonthsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.4.25.7.1 | not-accessible | current | |
| generatorFuelConsumptionLogLastMonthsIndex OBJECT-TYPE Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastHoursTable | 1.3.6.1.4.1.12148.10.4.25.7.1.1 | Integer32 (1..52) | not-accessible | current |
| generatorFuelConsumptionLogLastMonthsValue OBJECT-TYPE Generator fuel consumption value, logged every hour. | 1.3.6.1.4.1.12148.10.4.25.7.1.2 | Integer32 | read-only | current |
| rectifiers OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.5 | |||
| rectifiersStatus OBJECT-TYPE The overall status of rectifier subsystem. | 1.3.6.1.4.1.12148.10.5.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifiersCurrent OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.5.2 | |||
| rectifiersCurrentStatus OBJECT-TYPE The status of the measured total rectifier current. | 1.3.6.1.4.1.12148.10.5.2.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifiersCurrentDescription OBJECT-TYPE A textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.5.2.2 | DisplayString (SIZE(0..16)) | read-write | current |
| rectifiersCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.5.2.3 | Counter32 | accessible-for-notify | current |
| rectifiersCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.5.2.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| rectifiersCurrentValue OBJECT-TYPE The value of the measured total rectifier current. | 1.3.6.1.4.1.12148.10.5.2.5 | Integer32 | read-only | current |
| rectifiersCurrentMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.5.2.6 | Integer32 | read-write | current |
| rectifiersCurrentMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.5.2.7 | Integer32 | read-write | current |
| rectifiersCapacity OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.5.3 | |||
| rectifiersCapacityStatus OBJECT-TYPE The status of the measured used rectifier capacity. | 1.3.6.1.4.1.12148.10.5.3.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifiersCapacityDescription OBJECT-TYPE A textual description of the used rectifier capacity monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.5.3.2 | DisplayString (SIZE(0..16)) | read-write | current |
| rectifiersCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.5.3.3 | Counter32 | accessible-for-notify | current |
| rectifiersCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.5.3.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| rectifiersCapacityValue OBJECT-TYPE The used rectifier capacity value presented in percentage of the total installed rectifier capacity. | 1.3.6.1.4.1.12148.10.5.3.5 | Integer32 | read-only | current |
| rectifiersCapacityMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.5.3.6 | Integer32 | read-write | current |
| rectifiersCapacityMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.5.3.7 | Integer32 | read-write | current |
| rectifiersError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.5.4 | |||
| rectifiersErrorStatus OBJECT-TYPE This status value shows if the number of failed units is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.5.4.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifiersErrorDescription OBJECT-TYPE A textual description of the rectifier error monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.5.4.2 | DisplayString (SIZE(0..16)) | read-write | current |
| rectifiersErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.5.4.3 | Counter32 | accessible-for-notify | current |
| rectifiersErrorEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.5.4.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| rectifiersErrorValue OBJECT-TYPE The number of failed rectifiers. | 1.3.6.1.4.1.12148.10.5.4.5 | Integer32 | read-only | current |
| rectifiersErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.5.4.6 | Integer32 | read-write | current |
| rectifiersErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.5.4.7 | Integer32 | read-write | current |
| rectifiersNumberOfRectifiers OBJECT-TYPE Number of installed rectifiers. | 1.3.6.1.4.1.12148.10.5.5 | Integer32 (0..100) | read-write | current |
| rectifierTable OBJECT-TYPE This table shows the information of each rectifier installed in the system. | 1.3.6.1.4.1.12148.10.5.6 | not-accessible | current | |
| rectifierEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.6.1 | not-accessible | current | |
| rectifierIndex OBJECT-TYPE Index used for navigating the rows 1..100 of rectifierTable | 1.3.6.1.4.1.12148.10.5.6.1.1 | Integer32 (1..100) | not-accessible | current |
| rectifierStatus OBJECT-TYPE The overall status of rectifier. | 1.3.6.1.4.1.12148.10.5.6.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifierOutputCurrentValue OBJECT-TYPE The output current value of rectifier. | 1.3.6.1.4.1.12148.10.5.6.1.3 | Integer32 | read-only | current |
| rectifierInputVoltageValue OBJECT-TYPE The input voltage value of rectifier. | 1.3.6.1.4.1.12148.10.5.6.1.4 | Integer32 | read-only | current |
| rectifierType OBJECT-TYPE Type of rectifier | 1.3.6.1.4.1.12148.10.5.6.1.5 | DisplayString (SIZE(0..27)) | read-only | current |
| rectifierHwPartNumber OBJECT-TYPE Hardware part number of rectifier | 1.3.6.1.4.1.12148.10.5.6.1.6 | DisplayString (SIZE(0..12)) | read-only | current |
| rectifierHwVersion OBJECT-TYPE Hardware version number of rectifier | 1.3.6.1.4.1.12148.10.5.6.1.7 | DisplayString (SIZE(0..6)) | read-only | current |
| rectifierSwPartNumber OBJECT-TYPE Part number of secondary software in rectifier | 1.3.6.1.4.1.12148.10.5.6.1.8 | DisplayString (SIZE(0..12)) | read-only | current |
| rectifierSwVersion OBJECT-TYPE Version number of secondary software in rectifier | 1.3.6.1.4.1.12148.10.5.6.1.9 | DisplayString (SIZE(0..6)) | read-only | current |
| rectifiersEnergyLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.5.7 | |||
| rectifiersEnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered from rectifiers. | 1.3.6.1.4.1.12148.10.5.7.1 | Integer32 | read-only | current |
| rectifiersEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in rectifier hourly energy log. | 1.3.6.1.4.1.12148.10.5.7.2 | Integer32 (0..52) | read-only | current |
| rectifiersEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly energy log of rectifiers. | 1.3.6.1.4.1.12148.10.5.7.3 | not-accessible | current | |
| rectifiersEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.7.3.1 | not-accessible | current | |
| rectifiersEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of rectifiersEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.5.7.3.1.1 | Integer32 (1..52) | not-accessible | current |
| rectifiersEnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.5.7.3.1.2 | Integer32 | read-only | current |
| rectifiersEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in rectifier daily energy log. | 1.3.6.1.4.1.12148.10.5.7.4 | Integer32 (0..52) | read-only | current |
| rectifiersEnergyLogLastDaysTable OBJECT-TYPE This table contains daily energy log of rectifiers. | 1.3.6.1.4.1.12148.10.5.7.5 | not-accessible | current | |
| rectifiersEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.7.5.1 | not-accessible | current | |
| rectifiersEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of rectifiersEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.5.7.5.1.1 | Integer32 (1..52) | not-accessible | current |
| rectifiersEnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day. | 1.3.6.1.4.1.12148.10.5.7.5.1.2 | Integer32 | read-only | current |
| rectifiersEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in rectifier weekly energy log. | 1.3.6.1.4.1.12148.10.5.7.6 | Integer32 (0..52) | read-only | current |
| rectifiersEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly energy log of rectifiers. | 1.3.6.1.4.1.12148.10.5.7.7 | not-accessible | current | |
| rectifiersEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.7.7.1 | not-accessible | current | |
| rectifiersEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of rectifiersEnergyLogLastWeekTable | 1.3.6.1.4.1.12148.10.5.7.7.1.1 | Integer32 (1..52) | not-accessible | current |
| rectifiersEnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.5.7.7.1.2 | Integer32 | read-only | current |
| rectifiersNumberOfGroups OBJECT-TYPE Number of rectifier groups | 1.3.6.1.4.1.12148.10.5.8 | Integer32 | read-only | current |
| rectifierGroupsTable OBJECT-TYPE This table contains status and the number of installed rectifiers of each rectifier groups. | 1.3.6.1.4.1.12148.10.5.9 | not-accessible | current | |
| rectifierGroupsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.9.1 | not-accessible | current | |
| rectifierGroupIndex OBJECT-TYPE Index used for navigating the rows 1..10 of rectifierGroupsTable | 1.3.6.1.4.1.12148.10.5.9.1.1 | Integer32 (1..10) | not-accessible | current |
| rectifierGroupStatus OBJECT-TYPE The status of each rectifier group. | 1.3.6.1.4.1.12148.10.5.9.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifierGroupNumberOfRectifiers OBJECT-TYPE Number of installed rectifiers in each rectifier groups | 1.3.6.1.4.1.12148.10.5.9.1.3 | Integer32 (0..100) | read-write | current |
| rectifierGroupCurrentTable OBJECT-TYPE This table contains information about the total rectifier current of each rectifier groups, which is calculated by summing up current from each rectifier in a rectifier group. | 1.3.6.1.4.1.12148.10.5.10 | not-accessible | current | |
| rectifierGroupCurrentEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.10.1 | not-accessible | current | |
| rectifierGroupCurrentStatus OBJECT-TYPE The status of the measured total rectifier current of the rectifier group | 1.3.6.1.4.1.12148.10.5.10.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifierGroupCurrentDescription OBJECT-TYPE A textual description of the total rectifier current monitor of a rectifier group. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.5.10.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| rectifierGroupCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.5.10.1.3 | Integer32 | accessible-for-notify | current |
| rectifierGroupCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.5.10.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| rectifierGroupCurrentValue OBJECT-TYPE The value of the measured total rectifier current of each rectifier group. | 1.3.6.1.4.1.12148.10.5.10.1.5 | Integer32 | read-only | current |
| rectifierGroupCurrentMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.5.10.1.6 | Integer32 | read-write | current |
| rectifierGroupCurrentMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.5.10.1.7 | Integer32 | read-write | current |
| rectifierGroupCapacityTable OBJECT-TYPE This table contains information about the used rectifier capacity of each rectifier group. | 1.3.6.1.4.1.12148.10.5.11 | not-accessible | current | |
| rectifierGroupCapacityEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.11.1 | not-accessible | current | |
| rectifierGroupCapacityStatus OBJECT-TYPE The status of the measured used rectifier capacity of each rectifier group | 1.3.6.1.4.1.12148.10.5.11.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifierGroupCapacityDescription OBJECT-TYPE A textual description of the used rectifier capacity monitor of each rectifier group. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.5.11.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| rectifierGroupCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.5.11.1.3 | Integer32 | accessible-for-notify | current |
| rectifierGroupCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.5.11.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| rectifierGroupCapacityValue OBJECT-TYPE The used rectifier capacity value presented in percentage of the total installed rectifier capacity of each rectifier group. | 1.3.6.1.4.1.12148.10.5.11.1.5 | Integer32 | read-only | current |
| rectifierGroupCapacityMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.5.11.1.6 | Integer32 | read-write | current |
| rectifierGroupCapacityMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.5.11.1.7 | Integer32 | read-write | current |
| rectifierGroupErrorTable OBJECT-TYPE This table contains information about the rectifier error monitor of each rectifier group. | 1.3.6.1.4.1.12148.10.5.12 | not-accessible | current | |
| rectifierGroupErrorEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.12.1 | not-accessible | current | |
| rectifierGroupErrorStatus OBJECT-TYPE This status value shows if the number of failed units is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.5.12.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifierGroupErrorDescription OBJECT-TYPE A textual description of the rectifier error monitor of each rectifier group. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.5.12.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| rectifierGroupErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.5.12.1.3 | Integer32 | accessible-for-notify | current |
| rectifierGroupErrorAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.5.12.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| rectifierGroupErrorValue OBJECT-TYPE The number of failed rectifiers of each rectifier group. | 1.3.6.1.4.1.12148.10.5.12.1.5 | Integer32 | read-only | current |
| rectifierGroupErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.5.12.1.6 | Integer32 | read-write | current |
| rectifierGroupErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.5.12.1.7 | Integer32 | read-write | current |
| rectifierGroupRectifierTable OBJECT-TYPE This table shows the information of each rectifier installed in each of the rectifier group in the system. | 1.3.6.1.4.1.12148.10.5.13 | not-accessible | current | |
| rectifierGroupRectifierEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.13.1 | not-accessible | current | |
| rectifierGroupRectifierIndex OBJECT-TYPE Index used for navigating the rows 1..100 of rectifierGroupRectifierTable | 1.3.6.1.4.1.12148.10.5.13.1.1 | Integer32 (1..100) | not-accessible | current |
| rectifierGroupRectifierStatus OBJECT-TYPE The overall status of rectifier. | 1.3.6.1.4.1.12148.10.5.13.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifierGroupRectifierOutputCurrentValue OBJECT-TYPE The output current value of rectifier. | 1.3.6.1.4.1.12148.10.5.13.1.3 | Integer32 | read-only | current |
| rectifierGroupRectifierInputVoltageValue OBJECT-TYPE The input voltage value of rectifier. | 1.3.6.1.4.1.12148.10.5.13.1.4 | Integer32 | read-only | current |
| rectifierGroupRectifierType OBJECT-TYPE Type of rectifier | 1.3.6.1.4.1.12148.10.5.13.1.5 | DisplayString (SIZE(0..27)) | read-only | current |
| rectifierGroupRectifierHwPartNumber OBJECT-TYPE Hardware part number of rectifier | 1.3.6.1.4.1.12148.10.5.13.1.6 | DisplayString (SIZE(0..12)) | read-only | current |
| rectifierGroupRectifierHwVersion OBJECT-TYPE Hardware version number of rectifier | 1.3.6.1.4.1.12148.10.5.13.1.7 | DisplayString (SIZE(0..6)) | read-only | current |
| rectifierGroupRectifierSwPartNumber OBJECT-TYPE Part number of secondary software in rectifier | 1.3.6.1.4.1.12148.10.5.13.1.8 | DisplayString (SIZE(0..12)) | read-only | current |
| rectifierGroupRectifierSwVersion OBJECT-TYPE Version number of secondary software in rectifier | 1.3.6.1.4.1.12148.10.5.13.1.9 | DisplayString (SIZE(0..6)) | read-only | current |
| rectifierGroupEnergyLogTable OBJECT-TYPE This branch contains information about rectifiers' energy logs of each rectifier group. | 1.3.6.1.4.1.12148.10.5.14 | not-accessible | current | |
| rectifierGroupEnergyLogEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.14.1 | not-accessible | current | |
| rectifierGroupEnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered from rectifiers of each rectifier group. | 1.3.6.1.4.1.12148.10.5.14.1.1 | Integer32 | read-only | current |
| rectifierGroupEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in rectifier group hourly energy log. | 1.3.6.1.4.1.12148.10.5.14.1.2 | Integer32 | read-only | current |
| rectifierGroupEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in rectifier group daily energy log. | 1.3.6.1.4.1.12148.10.5.14.1.3 | Integer32 | read-only | current |
| rectifierGroupEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in rectifier group weekly energy log. | 1.3.6.1.4.1.12148.10.5.14.1.4 | Integer32 | read-only | current |
| rectifierGroupEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly energy log of each rectifier group | 1.3.6.1.4.1.12148.10.5.15 | not-accessible | current | |
| rectifierGroupEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.15.1 | not-accessible | current | |
| rectifierGroupEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.5.15.1.1 | Integer32 (1..52) | not-accessible | current |
| rectifierGroupEnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.5.15.1.2 | Integer32 | read-only | current |
| rectifierGroupEnergyLogLastDaysTable OBJECT-TYPE This table contains daily energy log of each rectifier group | 1.3.6.1.4.1.12148.10.5.16 | not-accessible | current | |
| rectifierGroupEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.16.1 | not-accessible | current | |
| rectifierGroupEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLasDaysTable | 1.3.6.1.4.1.12148.10.5.16.1.1 | Integer32 (1..52) | not-accessible | current |
| rectifierGroupEnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day. | 1.3.6.1.4.1.12148.10.5.16.1.2 | Integer32 | read-only | current |
| rectifierGroupEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly energy log of each rectifier group | 1.3.6.1.4.1.12148.10.5.17 | not-accessible | current | |
| rectifierGroupEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.17.1 | not-accessible | current | |
| rectifierGroupEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLastWeeksTable | 1.3.6.1.4.1.12148.10.5.17.1.1 | Integer32 (1..52) | not-accessible | current |
| rectifierGroupEnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.5.17.1.2 | Integer32 | read-only | current |
| rectifiersTemperature OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.5.18 | |||
| rectifiersTemperatureStatus OBJECT-TYPE The state of the rectifier temperature can be either one of the defined enumerated values | 1.3.6.1.4.1.12148.10.5.18.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifiersTemperatureDescription OBJECT-TYPE A textual description of the rectifier temperature monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.5.18.2 | DisplayString (SIZE(0..16)) | read-write | current |
| rectifiersTemperatureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.5.18.3 | Counter32 | accessible-for-notify | current |
| rectifiersTemperatureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.5.18.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| rectifiersTemperatureValue OBJECT-TYPE The highest value of the rectifier temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. | 1.3.6.1.4.1.12148.10.5.18.5 | Integer32 (0..9999) | read-only | current |
| rectifiersTemperatureMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.5.18.6 | Integer32 | read-write | current |
| rectifiersTemperatureMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.5.18.7 | Integer32 | read-write | current |
| rectifiersTemperatureMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.5.18.8 | Integer32 | read-write | current |
| rectifiersTemperatureMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.5.18.9 | Integer32 | read-write | current |
| rectifierGroupTemperatureTable OBJECT-TYPE This table contains information about the highest rectifier temperature of each rectifier groups, which is calculated by summing up current from each rectifier in a rectifier group. | 1.3.6.1.4.1.12148.10.5.19 | not-accessible | current | |
| rectifierGroupTemperatureEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.5.19.1 | not-accessible | current | |
| rectifierGroupTemperatureStatus OBJECT-TYPE The status of the measured highest rectifier temperature of the rectifier group | 1.3.6.1.4.1.12148.10.5.19.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| rectifierGroupTemperatureDescription OBJECT-TYPE A textual description of the highest rectifier temperature monitor of a rectifier group. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.5.19.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| rectifierGroupTemperatureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.5.19.1.3 | Integer32 | accessible-for-notify | current |
| rectifierGroupTemperatureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.5.19.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| rectifierGroupTemperatureValue OBJECT-TYPE The value of the measured highest rectifier temperature of each rectifier group. | 1.3.6.1.4.1.12148.10.5.19.1.5 | Integer32 | read-only | current |
| rectifierGroupTemperatureMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.5.19.1.6 | Integer32 | read-write | current |
| rectifierGroupTemperatureMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.5.19.1.7 | Integer32 | read-write | current |
| rectifierGroupTemperatureMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.5.19.1.8 | Integer32 | read-write | current |
| rectifierGroupTemperatureMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.5.19.1.9 | Integer32 | read-write | current |
| dcdc OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.6 | |||
| dcdcNumberOfGroups OBJECT-TYPE Number of dcdc groups | 1.3.6.1.4.1.12148.10.6.1 | Integer32 (0..5) | read-only | current |
| dcdcGroupsTable OBJECT-TYPE This table contains information about dcdc groups. | 1.3.6.1.4.1.12148.10.6.2 | not-accessible | current | |
| dcdcGroupsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.6.2.1 | not-accessible | current | |
| dcdcGroupIndex OBJECT-TYPE | 1.3.6.1.4.1.12148.10.6.2.1.1 | Integer32 (1..5) | not-accessible | current |
| dcdcGroupStatus OBJECT-TYPE The overall status of dcdc group. | 1.3.6.1.4.1.12148.10.6.2.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| dcdcGroupNumberOfDcdcConverters OBJECT-TYPE Number of installed dcdc converters. | 1.3.6.1.4.1.12148.10.6.2.1.3 | Integer32 | read-write | current |
| dcdcGroupOutputVoltage OBJECT-TYPE Output voltage of dcdc converters | 1.3.6.1.4.1.12148.10.6.2.1.4 | Integer32 | read-write | current |
| dcdcNumberOfCurrents OBJECT-TYPE Number of dcdc currents | 1.3.6.1.4.1.12148.10.6.2.1.5 | Integer32 (0..5) | read-only | current |
| dcdcNumberOfCapacities OBJECT-TYPE Number of dcdc capacities | 1.3.6.1.4.1.12148.10.6.2.1.6 | Integer32 (0..5) | read-only | current |
| dcdcNumberOfAlarms OBJECT-TYPE Number of dcdc alarms | 1.3.6.1.4.1.12148.10.6.2.1.7 | Integer32 (0..5) | read-only | current |
| dcdcCurrentTable OBJECT-TYPE This table contains information about the total dcdc current. | 1.3.6.1.4.1.12148.10.6.3 | not-accessible | current | |
| dcdcCurrentEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.6.3.1 | not-accessible | current | |
| dcdcCurrentStatus OBJECT-TYPE The status of the measured total dcdc current. | 1.3.6.1.4.1.12148.10.6.3.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| dcdcCurrentDescription OBJECT-TYPE A textual description of the total dcdc current monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.6.3.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| dcdcCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.6.3.1.3 | Counter32 | accessible-for-notify | current |
| dcdcCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.6.3.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| dcdcCurrentValue OBJECT-TYPE The value of the measured total dcdc current. | 1.3.6.1.4.1.12148.10.6.3.1.5 | Integer32 | read-only | current |
| dcdcCurrentMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.6.3.1.6 | Integer32 | read-write | current |
| dcdcCurrentMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.6.3.1.7 | Integer32 | read-write | current |
| dcdcCapacityTable OBJECT-TYPE This table contains information about the used dcdc capacity. | 1.3.6.1.4.1.12148.10.6.4 | not-accessible | current | |
| dcdcCapacityEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.6.4.1 | not-accessible | current | |
| dcdcCapacityStatus OBJECT-TYPE The status of the measured used dcdc capacity. | 1.3.6.1.4.1.12148.10.6.4.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| dcdcCapacityDescription OBJECT-TYPE A textual description of the used dcdc capacity monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.6.4.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| dcdcCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes of | 1.3.6.1.4.1.12148.10.6.4.1.3 | Counter32 | accessible-for-notify | current |
| dcdcCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.6.4.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| dcdcCapacityValue OBJECT-TYPE The used dcdc capacity value presented in percentage of the total installed dcdc capacity. | 1.3.6.1.4.1.12148.10.6.4.1.5 | Integer32 | read-only | current |
| dcdcCapacityMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.6.4.1.6 | Integer32 | read-write | current |
| dcdcCapacityMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.6.4.1.7 | Integer32 | read-write | current |
| dcdcTable OBJECT-TYPE This table shows the information of each dcdc converter installed in the system. | 1.3.6.1.4.1.12148.10.6.5 | not-accessible | current | |
| dcdcEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.6.5.1 | not-accessible | current | |
| dcdcIndex OBJECT-TYPE Index used for navigating the rows 1..100 of dcdcTable | 1.3.6.1.4.1.12148.10.6.5.1.1 | Integer32 (1..100) | not-accessible | current |
| dcdcStatus OBJECT-TYPE The overall status of dcdc converter | 1.3.6.1.4.1.12148.10.6.5.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| dcdcOutputCurrentValue OBJECT-TYPE The output current value of dcdc. | 1.3.6.1.4.1.12148.10.6.5.1.3 | Integer32 | read-only | current |
| dcdcInputVoltageValue OBJECT-TYPE The input voltage value of dcdc. | 1.3.6.1.4.1.12148.10.6.5.1.4 | Integer32 | read-only | current |
| dcdcType OBJECT-TYPE Type of dcdc converter | 1.3.6.1.4.1.12148.10.6.5.1.5 | DisplayString (SIZE(0..27)) | read-only | current |
| dcdcHwPartNumber OBJECT-TYPE Hardware part number of dcdc converter | 1.3.6.1.4.1.12148.10.6.5.1.6 | DisplayString (SIZE(0..12)) | read-only | current |
| dcdcHwVersion OBJECT-TYPE Hardware version number of dcdc converter | 1.3.6.1.4.1.12148.10.6.5.1.7 | DisplayString (SIZE(0..6)) | read-only | current |
| dcdcSwPartNumber OBJECT-TYPE Part number of secondary software in dcdc converter | 1.3.6.1.4.1.12148.10.6.5.1.8 | DisplayString (SIZE(0..12)) | read-only | current |
| dcdcSwVersion OBJECT-TYPE Version number of secondary software in dcdc converter | 1.3.6.1.4.1.12148.10.6.5.1.9 | DisplayString (SIZE(0..6)) | read-only | current |
| dcdcErrorTable OBJECT-TYPE This table contains information about the dcdc error monitor. | 1.3.6.1.4.1.12148.10.6.6 | not-accessible | current | |
| dcdcErrorEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.6.6.1 | not-accessible | current | |
| dcdcErrorStatus OBJECT-TYPE This status value shows if the number of failed units is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.6.6.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| dcdcErrorDescription OBJECT-TYPE A textual description of the dcdc error monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.6.6.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| dcdcErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.6.6.1.3 | Counter32 | accessible-for-notify | current |
| dcdcErrorEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.6.6.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| dcdcErrorValue OBJECT-TYPE The number of failed dcdc converters. | 1.3.6.1.4.1.12148.10.6.6.1.5 | Integer32 | read-only | current |
| dcdcErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.6.6.1.6 | Integer32 | read-write | current |
| dcdcErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.6.6.1.7 | Integer32 | read-write | current |
| dcdcObsolete OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.6.7 | |||
| solarChargers OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.7 | |||
| solarChargersStatus OBJECT-TYPE The overall status of solar charger subsystem. | 1.3.6.1.4.1.12148.10.7.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| solarChargersCurrent OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.7.2 | |||
| solarChargersCurrentStatus OBJECT-TYPE The status of the measured total solar current. | 1.3.6.1.4.1.12148.10.7.2.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| solarChargersCurrentDescription OBJECT-TYPE A textual description of the total solar current monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.7.2.2 | DisplayString (SIZE(0..16)) | read-write | current |
| solarChargersCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.7.2.3 | Counter32 | accessible-for-notify | current |
| solarChargersCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.7.2.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| solarChargersCurrentValue OBJECT-TYPE The value of the measured total solar current. | 1.3.6.1.4.1.12148.10.7.2.5 | Integer32 | read-only | current |
| solarChargersCurrentMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.7.2.6 | Integer32 | read-write | current |
| solarChargersCurrentMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.7.2.7 | Integer32 | read-write | current |
| solarChargersObsolete OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.7.3 | |||
| solarChargersError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.7.4 | |||
| solarChargersErrorStatus OBJECT-TYPE This status value shows if the number of failed units is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.7.4.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| solarChargersErrorDescription OBJECT-TYPE A textual description of the solar error monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.7.4.2 | DisplayString (SIZE(0..16)) | read-write | current |
| solarChargersErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.7.4.3 | Counter32 | accessible-for-notify | current |
| solarChargersErrorEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.7.4.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| solarChargersErrorValue OBJECT-TYPE The number of failed solar chargers. | 1.3.6.1.4.1.12148.10.7.4.5 | Integer32 | read-only | current |
| solarChargersErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.7.4.6 | Integer32 | read-write | current |
| solarChargersErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.7.4.7 | Integer32 | read-write | current |
| solarChargersNumberOfSolarChargers OBJECT-TYPE Number of installed solar chargers. | 1.3.6.1.4.1.12148.10.7.5 | Integer32 (0..100) | read-write | current |
| solarChargerTable OBJECT-TYPE This table shows the information of each solar charger installed in the system. | 1.3.6.1.4.1.12148.10.7.6 | not-accessible | current | |
| solarChargerEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.7.6.1 | not-accessible | current | |
| solarChargerIndex OBJECT-TYPE Index used for navigating the rows 1..100 of solarChargerTable | 1.3.6.1.4.1.12148.10.7.6.1.1 | Integer32 (1..100) | not-accessible | current |
| solarChargerStatus OBJECT-TYPE The overall status of solar charger. | 1.3.6.1.4.1.12148.10.7.6.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| solarChargerOutputCurrentValue OBJECT-TYPE The output current value of solar charger. | 1.3.6.1.4.1.12148.10.7.6.1.3 | Integer32 | read-only | current |
| solarChargerInputVoltageValue OBJECT-TYPE The input voltage value of solar charger. | 1.3.6.1.4.1.12148.10.7.6.1.4 | Integer32 | read-only | current |
| solarChargerType OBJECT-TYPE Type of solar charger | 1.3.6.1.4.1.12148.10.7.6.1.5 | DisplayString (SIZE(0..27)) | read-only | current |
| solarChargerHwPartNumber OBJECT-TYPE Hardware part number of solar charger | 1.3.6.1.4.1.12148.10.7.6.1.6 | DisplayString (SIZE(0..12)) | read-only | current |
| solarChargerHwVersion OBJECT-TYPE Hardware version number of solar charger | 1.3.6.1.4.1.12148.10.7.6.1.7 | DisplayString (SIZE(0..6)) | read-only | current |
| solarChargerSwPartNumber OBJECT-TYPE Part number of secondary software in solar charger | 1.3.6.1.4.1.12148.10.7.6.1.8 | DisplayString (SIZE(0..12)) | read-only | current |
| solarChargerSwVersion OBJECT-TYPE Version number of secondary software in solar charger | 1.3.6.1.4.1.12148.10.7.6.1.9 | DisplayString (SIZE(0..6)) | read-only | current |
| solarChargersEnergyLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.7.7 | |||
| solarChargersEnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered from solar chargers. | 1.3.6.1.4.1.12148.10.7.7.1 | Integer32 | read-only | current |
| solarChargersEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in solar charger hourly energy log. | 1.3.6.1.4.1.12148.10.7.7.2 | Integer32 | read-only | current |
| solarChargersEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly energy log of solar chargers. | 1.3.6.1.4.1.12148.10.7.7.3 | not-accessible | current | |
| solarChargersEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.7.7.3.1 | not-accessible | current | |
| solarChargersEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of solarChargersEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.7.7.3.1.1 | Integer32 (1..52) | not-accessible | current |
| solarChargersEnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.7.7.3.1.2 | Integer32 | read-only | current |
| solarChargersEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in solar charger daily energy log. | 1.3.6.1.4.1.12148.10.7.7.4 | Integer32 | read-only | current |
| solarChargersEnergyLogLastDaysTable OBJECT-TYPE This table contains daily energy log of solar chargers. | 1.3.6.1.4.1.12148.10.7.7.5 | not-accessible | current | |
| solarChargersEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.7.7.5.1 | not-accessible | current | |
| solarChargersEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of solarChargersEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.7.7.5.1.1 | Integer32 (1..52) | not-accessible | current |
| solarChargersEnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day. | 1.3.6.1.4.1.12148.10.7.7.5.1.2 | Integer32 | read-only | current |
| solarChargersEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in solar charger weekly energy log. | 1.3.6.1.4.1.12148.10.7.7.6 | Integer32 | read-only | current |
| solarChargersEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly energy log of solar chargers. | 1.3.6.1.4.1.12148.10.7.7.7 | not-accessible | current | |
| solarChargersEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.7.7.7.1 | not-accessible | current | |
| solarChargersEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of solarChargersEnergyLogLastWeekTable | 1.3.6.1.4.1.12148.10.7.7.7.1.1 | Integer32 (1..52) | not-accessible | current |
| solarChargersEnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.7.7.7.1.2 | Integer32 | read-only | current |
| windChargers OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.8 | |||
| windChargersStatus OBJECT-TYPE The overall status of wind charger subsystem. | 1.3.6.1.4.1.12148.10.8.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| windChargersCurrent OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.8.2 | |||
| windChargersCurrentStatus OBJECT-TYPE The status of the measured total wind current. | 1.3.6.1.4.1.12148.10.8.2.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| windChargersCurrentDescription OBJECT-TYPE A textual description of the total wind current monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.8.2.2 | DisplayString (SIZE(0..16)) | read-write | current |
| windChargersCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.8.2.3 | Counter32 | accessible-for-notify | current |
| windChargersCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.8.2.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| windChargersCurrentValue OBJECT-TYPE The value of the measured total wind current. | 1.3.6.1.4.1.12148.10.8.2.5 | Integer32 | read-only | current |
| windChargersCurrentMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.8.2.6 | Integer32 | read-write | current |
| windChargersCurrentMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.8.2.7 | Integer32 | read-write | current |
| windChargersObsolete OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.8.3 | |||
| windChargersError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.8.4 | |||
| windChargersErrorStatus OBJECT-TYPE This status value shows if the number of failed units is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.8.4.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| windChargersErrorDescription OBJECT-TYPE A textual description of the wind error monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.8.4.2 | DisplayString (SIZE(0..16)) | read-write | current |
| windChargersErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.8.4.3 | Counter32 | accessible-for-notify | current |
| windChargersErrorEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.8.4.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| windChargersErrorValue OBJECT-TYPE The number of failed wind chargers. | 1.3.6.1.4.1.12148.10.8.4.5 | Integer32 | read-only | current |
| windChargersErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.8.4.6 | Integer32 | read-write | current |
| windChargersErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.8.4.7 | Integer32 | read-write | current |
| windChargersNumberOfWindChargers OBJECT-TYPE Number of installed wind chargers. | 1.3.6.1.4.1.12148.10.8.5 | Integer32 (0..254) | read-write | current |
| windChargerTable OBJECT-TYPE This table shows the information of each wind charger installed in the system. | 1.3.6.1.4.1.12148.10.8.6 | not-accessible | current | |
| windChargerEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.8.6.1 | not-accessible | current | |
| windChargerIndex OBJECT-TYPE Index used for navigating the rows 1..100 of windChargerTable | 1.3.6.1.4.1.12148.10.8.6.1.1 | Integer32 (1..100) | not-accessible | current |
| windChargerStatus OBJECT-TYPE The overall status of wind charger. | 1.3.6.1.4.1.12148.10.8.6.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| windChargerOutputCurrentValue OBJECT-TYPE The output current value of wind charger. | 1.3.6.1.4.1.12148.10.8.6.1.3 | Integer32 | read-only | current |
| windChargerInputVoltageValue OBJECT-TYPE The input voltage value of wind charger. | 1.3.6.1.4.1.12148.10.8.6.1.4 | Integer32 | read-only | current |
| windChargerType OBJECT-TYPE Type of wind charger | 1.3.6.1.4.1.12148.10.8.6.1.5 | DisplayString (SIZE(0..27)) | read-only | current |
| windChargerHwPartNumber OBJECT-TYPE Hardware part number of wind charger | 1.3.6.1.4.1.12148.10.8.6.1.6 | DisplayString (SIZE(0..12)) | read-only | current |
| windChargerHwVersion OBJECT-TYPE Hardware version number of wind charger | 1.3.6.1.4.1.12148.10.8.6.1.7 | DisplayString (SIZE(0..6)) | read-only | current |
| windChargerSwPartNumber OBJECT-TYPE Part number of secondary software in wind charger | 1.3.6.1.4.1.12148.10.8.6.1.8 | DisplayString (SIZE(0..12)) | read-only | current |
| windChargerSwVersion OBJECT-TYPE Version number of secondary software in wind charger | 1.3.6.1.4.1.12148.10.8.6.1.9 | DisplayString (SIZE(0..6)) | read-only | current |
| windChargersEnergyLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.8.7 | |||
| windChargersEnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered to/from wind chargers. | 1.3.6.1.4.1.12148.10.8.7.1 | Integer32 | read-only | current |
| windChargersEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in wind charger hourly energy log. | 1.3.6.1.4.1.12148.10.8.7.2 | Integer32 (0..52) | read-only | current |
| windChargersEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly energy log of wind chargers. | 1.3.6.1.4.1.12148.10.8.7.3 | not-accessible | current | |
| windChargersEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.8.7.3.1 | not-accessible | current | |
| windChargersEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of windChargersEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.8.7.3.1.1 | Integer32 (1..52) | not-accessible | current |
| windChargersEnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.8.7.3.1.2 | Integer32 | read-only | current |
| windChargersEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in wind charger daily energy log. | 1.3.6.1.4.1.12148.10.8.7.4 | Integer32 (0..52) | read-only | current |
| windChargersEnergyLogLastDaysTable OBJECT-TYPE This table contains daily energy log of wind chargers. | 1.3.6.1.4.1.12148.10.8.7.5 | not-accessible | current | |
| windChargersEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.8.7.5.1 | not-accessible | current | |
| windChargersEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of windChargersEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.8.7.5.1.1 | Integer32 (1..52) | not-accessible | current |
| windChargersEnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day. | 1.3.6.1.4.1.12148.10.8.7.5.1.2 | Integer32 | read-only | current |
| windChargersEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in wind charger weekly energy log. | 1.3.6.1.4.1.12148.10.8.7.6 | Integer32 (0..52) | read-only | current |
| windChargersEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly energy log of wind chargers. | 1.3.6.1.4.1.12148.10.8.7.7 | not-accessible | current | |
| windChargersEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.8.7.7.1 | not-accessible | current | |
| windChargersEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of windChargersEnergyLogLastWeekTable | 1.3.6.1.4.1.12148.10.8.7.7.1.1 | Integer32 (1..52) | not-accessible | current |
| windChargersEnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.8.7.7.1.2 | Integer32 | read-only | current |
| load OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.9 | |||
| loadStatus OBJECT-TYPE The overall status of load subsystem. | 1.3.6.1.4.1.12148.10.9.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| loadCurrent OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.9.2 | |||
| loadCurrentStatus OBJECT-TYPE The status of the measured load current. | 1.3.6.1.4.1.12148.10.9.2.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| loadCurrentDescription OBJECT-TYPE A textual description of the load current monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.9.2.2 | DisplayString (SIZE(0..16)) | read-write | current |
| loadCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.9.2.3 | Counter32 | accessible-for-notify | current |
| loadCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.9.2.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| loadCurrentValue OBJECT-TYPE The value of the measured load current. | 1.3.6.1.4.1.12148.10.9.2.5 | Integer32 | read-only | current |
| loadCurrentMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.9.2.6 | Integer32 | read-write | current |
| loadCurrentMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.9.2.7 | Integer32 | read-write | current |
| loadFusesStatus OBJECT-TYPE The overall status of the load fuses. | 1.3.6.1.4.1.12148.10.9.3 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| loadNumberOfGroups OBJECT-TYPE Number of load groups | 1.3.6.1.4.1.12148.10.9.4 | Integer32 (1..8) | read-write | current |
| loadGroupTable OBJECT-TYPE This table contains information about load groups. | 1.3.6.1.4.1.12148.10.9.5 | not-accessible | current | |
| loadGroupEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.5.1 | not-accessible | current | |
| loadGroupIndex OBJECT-TYPE Index used for navigating the rows 1..8 of loadGroupTable | 1.3.6.1.4.1.12148.10.9.5.1.1 | Integer32 (1..8) | not-accessible | current |
| loadGroupStatus OBJECT-TYPE The status of load group | 1.3.6.1.4.1.12148.10.9.5.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| loadNumberOfLVLDs OBJECT-TYPE Number of LVLDs installed in load group | 1.3.6.1.4.1.12148.10.9.5.1.3 | Integer32 (0..4) | read-only | current |
| loadNumberOfVoltages OBJECT-TYPE Number of voltages in load group | 1.3.6.1.4.1.12148.10.9.5.1.4 | Integer32 (0..4) | read-only | current |
| loadLVLDTable OBJECT-TYPE This table contains information about LVLDs | 1.3.6.1.4.1.12148.10.9.6 | not-accessible | current | |
| loadLVLDEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.6.1 | not-accessible | current | |
| loadLVLDIndex OBJECT-TYPE Index used for navigating the rows 1..8 of loadLVLDTable | 1.3.6.1.4.1.12148.10.9.6.1.1 | Integer32 (1..8) | not-accessible | current |
| loadLVLDStatus OBJECT-TYPE The status of LVLD | 1.3.6.1.4.1.12148.10.9.6.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| loadLVLDDescription OBJECT-TYPE A textual description of the LVLD. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.9.6.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| loadLVLDTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.9.6.1.4 | Counter32 | accessible-for-notify | current |
| loadLVLDEnable OBJECT-TYPE This value once enabled, the alarm condition of the LVLD will be reported. | 1.3.6.1.4.1.12148.10.9.6.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| loadLVLDValue OBJECT-TYPE The measured value of the LVLD. | 1.3.6.1.4.1.12148.10.9.6.1.6 | Integer32 | read-only | current |
| loadLVLDConnectVoltage OBJECT-TYPE The load Contactor's Reconnect Voltage | 1.3.6.1.4.1.12148.10.9.6.1.7 | Integer32 | read-write | current |
| loadLVLDDisconnectVoltage OBJECT-TYPE The load Contactor's Disconnect Voltage | 1.3.6.1.4.1.12148.10.9.6.1.8 | Integer32 | read-write | current |
| loadFuseTable OBJECT-TYPE This table contains information about load fuse | 1.3.6.1.4.1.12148.10.9.7 | not-accessible | current | |
| loadFuseEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.7.1 | not-accessible | current | |
| loadFuseStatus OBJECT-TYPE The status of load fuse | 1.3.6.1.4.1.12148.10.9.7.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11)} | read-only | current |
| loadFuseDescription OBJECT-TYPE A textual description of the load fuse monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.9.7.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| loadFuseTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.9.7.1.3 | Counter32 | accessible-for-notify | current |
| loadFuseAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.9.7.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| loadFuseValue OBJECT-TYPE The measured value of the load fuse. | 1.3.6.1.4.1.12148.10.9.7.1.5 | Integer32 | read-write | current |
| loadEnergyLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.9.8 | |||
| loadEnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered to load. | 1.3.6.1.4.1.12148.10.9.8.1 | Integer32 | read-only | current |
| loadEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in load hourly energy log. | 1.3.6.1.4.1.12148.10.9.8.2 | Integer32 (0..52) | read-only | current |
| loadEnergyLogLastHoursTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.8.3 | not-accessible | current | |
| loadEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.8.3.1 | not-accessible | current | |
| loadEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of loadEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.9.8.3.1.1 | Integer32 (1..52) | not-accessible | current |
| loadEnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.9.8.3.1.2 | Integer32 | read-only | current |
| loadEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in load daily energy log. | 1.3.6.1.4.1.12148.10.9.8.4 | Integer32 (0..52) | read-only | current |
| loadEnergyLogLastDaysTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.8.5 | not-accessible | current | |
| loadEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.8.5.1 | not-accessible | current | |
| loadEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of loadEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.9.8.5.1.1 | Integer32 (1..52) | not-accessible | current |
| loadEnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day. | 1.3.6.1.4.1.12148.10.9.8.5.1.2 | Integer32 | read-only | current |
| loadEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in load weekly energy log. | 1.3.6.1.4.1.12148.10.9.8.6 | Integer32 (0..52) | read-only | current |
| loadEnergyLogLastWeeksTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.8.7 | not-accessible | current | |
| loadEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.8.7.1 | not-accessible | current | |
| loadEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of loadEnergyLogLastWeekTable | 1.3.6.1.4.1.12148.10.9.8.7.1.1 | Integer32 (1..52) | not-accessible | current |
| loadEnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.9.8.7.1.2 | Integer32 | read-only | current |
| loadVoltageTable OBJECT-TYPE This table contains information about voltages | 1.3.6.1.4.1.12148.10.9.9 | not-accessible | current | |
| loadVoltageEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.9.9.1 | not-accessible | current | |
| loadVoltageIndex OBJECT-TYPE Index used for navigating the rows 1..3 of loadVoltageTable | 1.3.6.1.4.1.12148.10.9.9.1.1 | Integer32 (1..3) | not-accessible | current |
| loadVoltageStatus OBJECT-TYPE The status of voltage | 1.3.6.1.4.1.12148.10.9.9.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| loadVoltageDescription OBJECT-TYPE A textual description of the voltage. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.9.9.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| loadVoltageTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.9.9.1.4 | Counter32 | accessible-for-notify | current |
| loadVoltageEnable OBJECT-TYPE This value once enabled, the alarm condition of the LVLD will be reported. | 1.3.6.1.4.1.12148.10.9.9.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| loadVoltageValue OBJECT-TYPE The measured value of the voltage. | 1.3.6.1.4.1.12148.10.9.9.1.6 | Integer32 | read-only | current |
| battery OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10 | |||
| batteryStatus OBJECT-TYPE A toplevel status for the battery subsystem. The state of this reflects the status of all underlying statuses for the battery. Any change in one of the 'data monitors' in the battery subsystem will propagate up to this status indicator. | 1.3.6.1.4.1.12148.10.10.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryDescription OBJECT-TYPE A descriptive name of the battery installed in the system. | 1.3.6.1.4.1.12148.10.10.2 | DisplayString (SIZE(0..32)) | read-write | current |
| batteryReferenceVoltage OBJECT-TYPE The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging. | 1.3.6.1.4.1.12148.10.10.3 | Integer32 (840..60417) | read-write | current |
| batteryFusesStatus OBJECT-TYPE The state of the battery fuses/breakers can mainly be normal(1) or majorAlarm(3) and some other rarely used values . | 1.3.6.1.4.1.12148.10.10.4 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryVoltage OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.5 | |||
| batteryVoltageStatus OBJECT-TYPE The status of the measured battery voltage. | 1.3.6.1.4.1.12148.10.10.5.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryVoltageDescription OBJECT-TYPE A textual description of the battery voltage monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.5.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryVoltageTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.5.3 | Counter32 | accessible-for-notify | current |
| batteryVoltageAlarmEnable OBJECT-TYPE The measured battery voltage alarm enable/disable control | 1.3.6.1.4.1.12148.10.10.5.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryVoltageValue OBJECT-TYPE The value of the measured battery voltage. | 1.3.6.1.4.1.12148.10.10.5.5 | Integer32 (0..7500) | read-only | current |
| batteryVoltageMajorHighLevel OBJECT-TYPE The Major High Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.10.10.5.6 | Integer32 | read-write | current |
| batteryVoltageMinorHighLevel OBJECT-TYPE The Minor High Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.10.10.5.7 | Integer32 | read-write | current |
| batteryVoltageMinorLowLevel OBJECT-TYPE The Minor Low Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.10.10.5.8 | Integer32 | read-write | current |
| batteryVoltageMajorLowLevel OBJECT-TYPE The Major Low Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.10.10.5.9 | Integer32 | read-write | current |
| batteryCurrents OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.6 | |||
| batteryCurrentsStatus OBJECT-TYPE The status of the measured battery current | 1.3.6.1.4.1.12148.10.10.6.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryCurrentsDescription OBJECT-TYPE A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.6.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryCurrentsTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.10.6.3 | Counter32 | accessible-for-notify | current |
| batteryCurrentsAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.6.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryCurrentsValue OBJECT-TYPE The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.10.10.6.5 | Integer32 | read-only | current |
| batteryCurrentsMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.10.6.6 | Integer32 | read-write | current |
| batteryCurrentsMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.10.6.7 | Integer32 | read-write | current |
| batteryCurrentsMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.10.6.8 | Integer32 | read-write | current |
| batteryCurrentsMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.10.6.9 | Integer32 | read-write | current |
| batteryTemperatures OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.7 | |||
| batteryTemperaturesStatus OBJECT-TYPE The state of the battery fuses/breakers can be either one of the defined enumerated values | 1.3.6.1.4.1.12148.10.10.7.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryTemperaturesDescription OBJECT-TYPE A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.7.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryTemperaturesTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.7.3 | Counter32 | accessible-for-notify | current |
| batteryTemperaturesAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.7.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryTemperaturesValue OBJECT-TYPE The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. | 1.3.6.1.4.1.12148.10.10.7.5 | Integer32 (0..9999) | read-only | current |
| batteryTemperaturesMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.10.7.6 | Integer32 | read-write | current |
| batteryTemperaturesMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.10.7.7 | Integer32 | read-write | current |
| batteryTemperaturesMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.10.7.8 | Integer32 | read-write | current |
| batteryTemperaturesMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.10.7.9 | Integer32 | read-write | current |
| batteryTimeLeft OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.8 | |||
| batteryTimeLeftStatus OBJECT-TYPE The status of the estimated battery remaining backup time. | 1.3.6.1.4.1.12148.10.10.8.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryTimeLeftDescription OBJECT-TYPE A textual description of the battery discharge time monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.8.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryTimeLeftTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.10.8.3 | Counter32 | accessible-for-notify | current |
| batteryTimeLeftAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.8.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryTimeLeftValue OBJECT-TYPE The estimated value of battery remaining backup time. | 1.3.6.1.4.1.12148.10.10.8.5 | Integer32 | read-only | current |
| batteryTimeLeftMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.10.8.6 | Integer32 | read-write | current |
| batteryTimeLeftMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.10.8.7 | Integer32 | read-write | current |
| batteryRemainingCapacity OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.9 | |||
| batteryRemainingCapacityStatus OBJECT-TYPE The status of the battery remaining capacity monitor. | 1.3.6.1.4.1.12148.10.10.9.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryRemainingCapacityDescription OBJECT-TYPE A textual description of the battery remaining capacity monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.9.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryRemainingCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.10.9.3 | Counter32 | accessible-for-notify | current |
| batteryRemainingCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.9.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryRemainingCapacityValue OBJECT-TYPE Battery remaining capacity (SOC) value estimated from the latest battery test result. | 1.3.6.1.4.1.12148.10.10.9.5 | Integer32 | read-only | current |
| batteryRemainingCapacityMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.10.9.6 | Integer32 | read-write | current |
| batteryRemainingCapacityMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.10.9.7 | Integer32 | read-write | current |
| batteryUsedCapacity OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.10 | |||
| batteryUsedCapacityStatus OBJECT-TYPE The status of the battery used capacity (DoD) monitor | 1.3.6.1.4.1.12148.10.10.10.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryUsedCapacityDescription OBJECT-TYPE A textual description of the battery used capacity (DoD) monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.10.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryUsedCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.10.10.3 | Counter32 | accessible-for-notify | current |
| batteryUsedCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.10.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryUsedCapacityValue OBJECT-TYPE This is the estimated battery used capacity (DoD). | 1.3.6.1.4.1.12148.10.10.10.5 | Integer32 | read-only | current |
| batteryUsedCapacityMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.10.10.6 | Integer32 | read-write | current |
| batteryUsedCapacityMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.10.10.7 | Integer32 | read-write | current |
| batteryTotalCapacity OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.11 | |||
| batteryTotalCapacityStatus OBJECT-TYPE The status of the total capacity monitor. | 1.3.6.1.4.1.12148.10.10.11.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryTotalCapacityDescription OBJECT-TYPE A textual description of the battery total capacity monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.10.11.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryTotalCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.10.11.3 | Counter32 | accessible-for-notify | current |
| batteryTotalCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.11.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryTotalCapacityValue OBJECT-TYPE This is the estimated total battery capacity (installed Ah - SoH) value. | 1.3.6.1.4.1.12148.10.10.11.5 | Integer32 | read-only | current |
| batteryTotalCapacityMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.10.11.6 | Integer32 | read-write | current |
| batteryTotalCapacityMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.10.11.7 | Integer32 | read-write | current |
| batteryQuality OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.12 | |||
| batteryQualityStatus OBJECT-TYPE The status of the battery quality (SoH) monitor. | 1.3.6.1.4.1.12148.10.10.12.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryQualityDescription OBJECT-TYPE A textual description of the battery quality (SoH) monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.10.12.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryQualityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.12.3 | Counter32 | accessible-for-notify | current |
| batteryQualityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.12.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryQualityValue OBJECT-TYPE The calculated battery quality (SoH) based on the latest battery test | 1.3.6.1.4.1.12148.10.10.12.5 | Integer32 | read-only | current |
| batteryQualityMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.10.12.6 | Integer32 | read-write | current |
| batteryQualityMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.10.12.7 | Integer32 | read-write | current |
| batteryLVBD OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.13 | |||
| batteryLVBDStatus OBJECT-TYPE The Battery Contactor is connected, disconnected, disabled or in any other alarm condition | 1.3.6.1.4.1.12148.10.10.13.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryLVBDDescription OBJECT-TYPE A textual description of the battery LVBD monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.13.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryLVBDTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.10.13.3 | Counter32 | accessible-for-notify | current |
| batteryLVBDEnable OBJECT-TYPE This value once enabled, the alarm condition of the LVBD will be reported. | 1.3.6.1.4.1.12148.10.10.13.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryLVBDValue OBJECT-TYPE The measured value of the LVBD. | 1.3.6.1.4.1.12148.10.10.13.5 | Integer32 | read-only | current |
| batteryLVBDConnectVoltage OBJECT-TYPE The Battery Contactor's Reconnect Voltage | 1.3.6.1.4.1.12148.10.10.13.6 | Integer32 | read-write | current |
| batteryLVBDDisconnectVoltage OBJECT-TYPE The Battery Contactor's Disconnect Voltage | 1.3.6.1.4.1.12148.10.10.13.7 | Integer32 | read-write | current |
| batteryChargeCurrentLimit OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.14 | |||
| batteryChargeCurrentLimitEnable OBJECT-TYPE Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable. | 1.3.6.1.4.1.12148.10.10.14.1 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryChargeCurrentLimitValue OBJECT-TYPE Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.10.10.14.2 | Integer32 (0..32767) | read-write | current |
| batteryBoost OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.15 | |||
| batteryBoostVoltage OBJECT-TYPE The Voltage at which the DC System boost charges the batteries. | 1.3.6.1.4.1.12148.10.10.15.1 | Integer32 (870..60418) | read-write | current |
| batteryBoostCommand OBJECT-TYPE This pushbutton will start or stop a manual battery boost if the system allows it. | 1.3.6.1.4.1.12148.10.10.15.2 | INTEGER {pushbutton(0), startboost(1), stopboost(2)} | read-write | current |
| batteryBoostCurrentThreshold OBJECT-TYPE The boosting will terminate when the charge current drops below the BoostCurrentThreshold limit. | 1.3.6.1.4.1.12148.10.10.15.3 | Integer32 | read-write | current |
| batteryBoostManualMaxDuration OBJECT-TYPE A protection against overcharging. When running manual boost, the boosting will always terminate at this point. | 1.3.6.1.4.1.12148.10.10.15.4 | Integer32 (0..1440) | read-write | current |
| batteryTest OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.16 | |||
| batteryTestVoltage OBJECT-TYPE This is the battery test end voltage. The battery test will be terminated when the voltage drops below the end voltage. | 1.3.6.1.4.1.12148.10.10.16.1 | Integer32 | read-write | current |
| batteryTestCommand OBJECT-TYPE This pushbutton will start or stop a manual battery test if the system allows it. | 1.3.6.1.4.1.12148.10.10.16.2 | INTEGER {pushbutton(0), starttest(1), stoptest(2)} | read-write | current |
| batteryTestNumberOfResults OBJECT-TYPE This is the number of valid battery test results stored in controller. | 1.3.6.1.4.1.12148.10.10.16.3 | Integer32 (0..10) | read-only | current |
| batteryTestResultTable OBJECT-TYPE This table contains the battery test results stored in controller. | 1.3.6.1.4.1.12148.10.10.16.4 | not-accessible | current | |
| batteryTestResultEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.16.4.1 | not-accessible | current | |
| batteryTestResultIndex OBJECT-TYPE A index pointing to one of ten possible battery test results | 1.3.6.1.4.1.12148.10.10.16.4.1.1 | Integer32 (1..10) | not-accessible | current |
| batteryTestResultStartDateTime OBJECT-TYPE This is the time and date when the test started. | 1.3.6.1.4.1.12148.10.10.16.4.1.2 | DateAndTime | read-only | current |
| batteryTestResultDuration OBJECT-TYPE This is the test duration in minutes. | 1.3.6.1.4.1.12148.10.10.16.4.1.3 | Integer32 | read-only | current |
| batteryTestResultDischarged OBJECT-TYPE This is the discharged Ah during test. | 1.3.6.1.4.1.12148.10.10.16.4.1.4 | Integer32 | read-only | current |
| batteryTestResultQuality OBJECT-TYPE This is the calculated battery quality (SoH)in percentage. | 1.3.6.1.4.1.12148.10.10.16.4.1.5 | Integer32 | read-only | current |
| batteryTempComp OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.17 | |||
| batteryTempCompEnable OBJECT-TYPE Enable (1) or Disable (0) of Battery Temperature Compensated output regulation mode | 1.3.6.1.4.1.12148.10.10.17.1 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryBank OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.18 | |||
| batteryBankNumberOfBanks OBJECT-TYPE Number of battery banks installed in system. | 1.3.6.1.4.1.12148.10.10.18.1 | Integer32 (0..8) | read-write | current |
| batteryBankTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.2 | not-accessible | current | |
| batteryBankEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.2.1 | not-accessible | current | |
| batteryBankIndex OBJECT-TYPE Index used for navigating the rows 1..8 of batteryBankTable | 1.3.6.1.4.1.12148.10.10.18.2.1.1 | Integer32 (1..8) | not-accessible | current |
| batteryBankStatus OBJECT-TYPE The overall status of battery bank | 1.3.6.1.4.1.12148.10.10.18.2.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryBankNumberOfTemperatures OBJECT-TYPE Number of temperature measurements in battery bank. | 1.3.6.1.4.1.12148.10.10.18.2.1.3 | Integer32 (0..4) | read-only | current |
| batteryBankNumberOfCurrents OBJECT-TYPE Number of current measurements in battery bank. | 1.3.6.1.4.1.12148.10.10.18.2.1.4 | Integer32 (0..4) | read-only | current |
| batteryBankNumberOfFuses OBJECT-TYPE Number of fuses installed in battery bank. | 1.3.6.1.4.1.12148.10.10.18.2.1.5 | Integer32 (0..4) | read-only | current |
| batteryBankNumberOfSymmetries OBJECT-TYPE Number of symmetry measurements available in battery bank. | 1.3.6.1.4.1.12148.10.10.18.2.1.6 | Integer32 (0..4) | read-only | current |
| batteryBankTemperatureTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.3 | not-accessible | current | |
| batteryBankTemperatureEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.3.1 | not-accessible | current | |
| batteryTemperatureIndex OBJECT-TYPE This index denotes which row in the temperature input table. The size of the table is defined by the batteryBankNumberOfTemp | 1.3.6.1.4.1.12148.10.10.18.3.1.1 | Integer32 (1..4) | not-accessible | current |
| batteryTemperatureStatus OBJECT-TYPE The status of battery temperature monitor | 1.3.6.1.4.1.12148.10.10.18.3.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryTemperatureDescription OBJECT-TYPE A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.18.3.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryTemperatureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.10.18.3.1.4 | Counter32 | accessible-for-notify | current |
| batteryTemperatureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.18.3.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryTemperatureValue OBJECT-TYPE The measured battery temperature. | 1.3.6.1.4.1.12148.10.10.18.3.1.6 | Integer32 | read-only | current |
| batteryTemperatureMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.10.18.3.1.7 | Integer32 | read-write | current |
| batteryTemperatureMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.10.18.3.1.8 | Integer32 | read-write | current |
| batteryTemperatureMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.10.18.3.1.9 | Integer32 | read-write | current |
| batteryTemperatureMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.10.18.3.1.10 | Integer32 | read-write | current |
| batteryBankCurrentTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.4 | not-accessible | current | |
| batteryBankCurrentEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.4.1 | not-accessible | current | |
| batteryCurrentIndex OBJECT-TYPE This index denotes which row in the current input table. The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.10.18.4.1.1 | Integer32 (1..4) | not-accessible | current |
| batteryCurrentStatus OBJECT-TYPE The status of battery current monitor | 1.3.6.1.4.1.12148.10.10.18.4.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryCurrentDescription OBJECT-TYPE A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.18.4.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.10.18.4.1.4 | Counter32 | accessible-for-notify | current |
| batteryCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.18.4.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryCurrentValue OBJECT-TYPE The measured battery current | 1.3.6.1.4.1.12148.10.10.18.4.1.6 | Integer32 | read-only | current |
| batteryCurrentMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.10.18.4.1.7 | Integer32 | read-write | current |
| batteryCurrentMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.10.18.4.1.8 | Integer32 | read-write | current |
| batteryCurrentMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.10.18.4.1.9 | Integer32 | read-write | current |
| batteryCurrentMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.10.18.4.1.10 | Integer32 | read-write | current |
| batteryBankFuseTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.5 | not-accessible | current | |
| batteryBankFuseEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.5.1 | not-accessible | current | |
| batteryFuseIndex OBJECT-TYPE This index denotes which row in the fuse table. The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.10.18.5.1.1 | Integer32 (1..4) | not-accessible | current |
| batteryFuseStatus OBJECT-TYPE The status of battery fuse monitor | 1.3.6.1.4.1.12148.10.10.18.5.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryFuseDescription OBJECT-TYPE A textual description of the battery fuse monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.18.5.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryFuseTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.10.18.5.1.4 | Counter32 | accessible-for-notify | current |
| batteryFuseAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.18.5.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryFuseValue OBJECT-TYPE The measured value of battery fuse input. | 1.3.6.1.4.1.12148.10.10.18.5.1.6 | Integer32 | read-only | current |
| batteryBankSymmetryTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.6 | not-accessible | current | |
| batteryBankSymmetryEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.18.6.1 | not-accessible | current | |
| batteryBankSymmetryIndex OBJECT-TYPE This index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries | 1.3.6.1.4.1.12148.10.10.18.6.1.1 | Integer32 (1..8) | not-accessible | current |
| batteryBankSymmetryStatus OBJECT-TYPE The status of battery symmetry monitor | 1.3.6.1.4.1.12148.10.10.18.6.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryBankSymmetryDescription OBJECT-TYPE A textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.18.6.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryBankSymmetryTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.18.6.1.4 | Counter32 | accessible-for-notify | current |
| batteryBankSymmetryAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.18.6.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryBankSymmetryMeasureValue OBJECT-TYPE The measured battery symmetry voltage in battery monitor. | 1.3.6.1.4.1.12148.10.10.18.6.1.6 | Integer32 | read-only | current |
| batteryBankSymmetryDeltaValue OBJECT-TYPE The measured battery symmetry delta voltage in battery monitor. | 1.3.6.1.4.1.12148.10.10.18.6.1.7 | Integer32 | read-only | current |
| batteryBankSymmetryMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.10.18.6.1.8 | Integer32 | read-write | current |
| batteryBankSymmetryMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.10.18.6.1.9 | Integer32 | read-write | current |
| batteryMonitors OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.19 | |||
| batteryMonitorsNumberOfUnits OBJECT-TYPE The number of battery monitor installed in system. | 1.3.6.1.4.1.12148.10.10.19.1 | Integer32 | read-write | current |
| batteryMonitorsTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.2 | not-accessible | current | |
| batteryMonitorsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.2.1 | not-accessible | current | |
| batteryMonitorIndex OBJECT-TYPE Index used for navigating the rows 1..8 of batteryMonitorsTable | 1.3.6.1.4.1.12148.10.10.19.2.1.1 | Integer32 (1..8) | not-accessible | current |
| batteryMonitorNumberOfTemperatures OBJECT-TYPE The number of temperature measurements in battery monitor. | 1.3.6.1.4.1.12148.10.10.19.2.1.2 | Integer32 (0..4) | read-only | current |
| batteryMonitorNumberOfCurrents OBJECT-TYPE The number of current measurements in battery monitor. | 1.3.6.1.4.1.12148.10.10.19.2.1.3 | Integer32 (0..4) | read-only | current |
| batteryMonitorNumberOfFuses OBJECT-TYPE The number of fuse measurements in battery monitor. | 1.3.6.1.4.1.12148.10.10.19.2.1.4 | Integer32 (0..4) | read-only | current |
| batteryMonitorNumberOfSymmetries OBJECT-TYPE The number of symmetry measurements in battery monitor. | 1.3.6.1.4.1.12148.10.10.19.2.1.5 | Integer32 (0..4) | read-only | current |
| batteryMonitorTemperatureTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.3 | not-accessible | current | |
| batteryMonitorTemperatureEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.3.1 | not-accessible | current | |
| batteryMonitorTemperatureIndex OBJECT-TYPE This index denotes which row in the temperature input table. The size of the table is defined by the batteryMonitorNumberOfTemperatures | 1.3.6.1.4.1.12148.10.10.19.3.1.1 | Integer32 (1..4) | not-accessible | current |
| batteryMonitorTemperatureStatus OBJECT-TYPE The status of battery temperature monitor | 1.3.6.1.4.1.12148.10.10.19.3.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryMonitorTemperatureDescription OBJECT-TYPE A textual description of the battery monitor temperature. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.19.3.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryMonitorTemperatureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.19.3.1.4 | Counter32 | accessible-for-notify | current |
| batteryMonitorTemperatureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.19.3.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryMonitorTemperatureValue OBJECT-TYPE The measured battery temperature in battery monitor. | 1.3.6.1.4.1.12148.10.10.19.3.1.6 | Integer32 | read-only | current |
| batteryMonitorTemperatureMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.10.19.3.1.7 | Integer32 | read-write | current |
| batteryMonitorTemperatureMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.10.19.3.1.8 | Integer32 | read-write | current |
| batteryMonitorTemperatureMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.10.19.3.1.9 | Integer32 | read-write | current |
| batteryMonitorTemperatureMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.10.19.3.1.10 | Integer32 | read-write | current |
| batteryMonitorCurrentTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.4 | not-accessible | current | |
| batteryMonitorCurrentEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.4.1 | not-accessible | current | |
| batteryMonitorCurrentIndex OBJECT-TYPE This index denotes which row in the current input table. The size of the table is defined by the batteryMonitorNumberOfCurrents | 1.3.6.1.4.1.12148.10.10.19.4.1.1 | Integer32 (1..4) | not-accessible | current |
| batteryMonitorCurrentStatus OBJECT-TYPE The status of battery current monitor | 1.3.6.1.4.1.12148.10.10.19.4.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryMonitorCurrentDescription OBJECT-TYPE A textual description of the battery monitor current. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.19.4.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryMonitorCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.19.4.1.4 | Counter32 | accessible-for-notify | current |
| batteryMonitorCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.19.4.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryMonitorCurrentValue OBJECT-TYPE The measured battery current in battery monitor. | 1.3.6.1.4.1.12148.10.10.19.4.1.6 | Integer32 | read-only | current |
| batteryMonitorCurrentMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.10.19.4.1.7 | Integer32 | read-write | current |
| batteryMonitorCurrentMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.10.19.4.1.8 | Integer32 | read-write | current |
| batteryMonitorCurrentMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.10.19.4.1.9 | Integer32 | read-write | current |
| batteryMonitorCurrentMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.10.19.4.1.10 | Integer32 | read-write | current |
| batteryMonitorFuseTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.5 | not-accessible | current | |
| batteryMonitorFuseEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.5.1 | not-accessible | current | |
| batteryMonitorFuseIndex OBJECT-TYPE This index denotes which row in the fuse table. The size of the table is defined by the batteryMonitorNumberOfFuses | 1.3.6.1.4.1.12148.10.10.19.5.1.1 | Integer32 (1..4) | not-accessible | current |
| batteryMonitorFuseStatus OBJECT-TYPE The status of battery fuse monitor | 1.3.6.1.4.1.12148.10.10.19.5.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryMonitorFuseDescription OBJECT-TYPE A textual description of the battery monitor fuse. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.19.5.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryMonitorFuseTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.19.5.1.4 | Counter32 | accessible-for-notify | current |
| batteryMonitorFuseAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.19.5.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryMonitorFuseValue OBJECT-TYPE The measured value of battery fuse in battery monitor. | 1.3.6.1.4.1.12148.10.10.19.5.1.6 | Integer32 | read-only | current |
| batteryMonitorSymmetryTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.6 | not-accessible | current | |
| batteryMonitorSymmetryEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.19.6.1 | not-accessible | current | |
| batteryMonitorSymmetryIndex OBJECT-TYPE This index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries | 1.3.6.1.4.1.12148.10.10.19.6.1.1 | Integer32 (1..8) | not-accessible | current |
| batteryMonitorSymmetryStatus OBJECT-TYPE The status of battery symmetry monitor | 1.3.6.1.4.1.12148.10.10.19.6.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryMonitorSymmetryDescription OBJECT-TYPE A textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.10.19.6.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryMonitorSymmetryTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.19.6.1.4 | Counter32 | accessible-for-notify | current |
| batteryMonitorSymmetryAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.19.6.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryMonitorSymmetryMeasureValue OBJECT-TYPE The measured battery symmetry voltage in battery monitor. | 1.3.6.1.4.1.12148.10.10.19.6.1.6 | Integer32 | read-only | current |
| batteryMonitorSymmetryDeltaValue OBJECT-TYPE The measured battery symmetry delta voltage in battery monitor. | 1.3.6.1.4.1.12148.10.10.19.6.1.7 | Integer32 | read-only | current |
| batteryMonitorSymmetryMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.10.19.6.1.8 | Integer32 | read-write | current |
| batteryMonitorSymmetryMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.10.19.6.1.9 | Integer32 | read-write | current |
| batteryEnergyLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.20 | |||
| batteryEnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered to/from battery. | 1.3.6.1.4.1.12148.10.10.20.1 | Integer32 | read-only | current |
| batteryEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in battery hourly energy log. | 1.3.6.1.4.1.12148.10.10.20.2 | Integer32 (0..52) | read-only | current |
| batteryEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly energy log of battery. | 1.3.6.1.4.1.12148.10.10.20.3 | not-accessible | current | |
| batteryEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.20.3.1 | not-accessible | current | |
| batteryEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.10.20.3.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryEnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.10.20.3.1.2 | Integer32 | read-only | current |
| batteryEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in battery daily energy log. | 1.3.6.1.4.1.12148.10.10.20.4 | Integer32 (0..52) | read-only | current |
| batteryEnergyLogLastDaysTable OBJECT-TYPE This table contains daily energy log of battery. | 1.3.6.1.4.1.12148.10.10.20.5 | not-accessible | current | |
| batteryEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.20.5.1 | not-accessible | current | |
| batteryEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.10.20.5.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryEnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day. | 1.3.6.1.4.1.12148.10.10.20.5.1.2 | Integer32 | read-only | current |
| batteryEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in battery weekly energy log. | 1.3.6.1.4.1.12148.10.10.20.6 | Integer32 (0..52) | read-only | current |
| batteryEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly energy log of battery. | 1.3.6.1.4.1.12148.10.10.20.7 | not-accessible | current | |
| batteryEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.20.7.1 | not-accessible | current | |
| batteryEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable | 1.3.6.1.4.1.12148.10.10.20.7.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryEnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.10.20.7.1.2 | Integer32 | read-only | current |
| batteryCycleLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.21 | |||
| batteryCycleLogTotalCycles OBJECT-TYPE This is the total number of battery discharge cycles. | 1.3.6.1.4.1.12148.10.10.21.1 | Integer32 | read-only | current |
| batteryCycleLogDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in daily battery discharge cycle log. | 1.3.6.1.4.1.12148.10.10.21.2 | Integer32 (0..52) | read-only | current |
| batteryCycleLogDaysTable OBJECT-TYPE This table contains daily battery discharge cycle log. | 1.3.6.1.4.1.12148.10.10.21.3 | not-accessible | current | |
| batteryCycleLogDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.21.3.1 | not-accessible | current | |
| batteryCycleLogDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryCycleLogLastDaysTable | 1.3.6.1.4.1.12148.10.10.21.3.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryCycleLogDaysValue OBJECT-TYPE Number of discharge cycles logged every day. | 1.3.6.1.4.1.12148.10.10.21.3.1.2 | Integer32 | read-only | current |
| batteryCycleLogWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in weeky battery discharge cycle log. | 1.3.6.1.4.1.12148.10.10.21.4 | Integer32 (0..52) | read-only | current |
| batteryCycleLogWeeksTable OBJECT-TYPE This table contains weekly battery discharge cycle log. | 1.3.6.1.4.1.12148.10.10.21.5 | not-accessible | current | |
| batteryCycleLogWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.21.5.1 | not-accessible | current | |
| batteryCycleLogWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable | 1.3.6.1.4.1.12148.10.10.21.5.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryCycleLogWeeksValue OBJECT-TYPE Number of discharge cycles logged every week. | 1.3.6.1.4.1.12148.10.10.21.5.1.2 | Integer32 | read-only | current |
| batteryCycleLogMonthsNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in monthly battery discharge cycle log. | 1.3.6.1.4.1.12148.10.10.21.6 | Integer32 (0..52) | read-only | current |
| batteryCycleLogMonthsTable OBJECT-TYPE This table contains monthly battery discharge cycle log. | 1.3.6.1.4.1.12148.10.10.21.7 | not-accessible | current | |
| batteryCycleLogMonthsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.10.21.7.1 | not-accessible | current | |
| batteryCycleLogMonthsIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryCycleLogLastMonthTable | 1.3.6.1.4.1.12148.10.10.21.7.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryCycleLogMonthsValue OBJECT-TYPE Number of discharge cycles logged every month. | 1.3.6.1.4.1.12148.10.10.21.7.1.2 | Integer32 | read-only | current |
| batteryEqualize OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.22 | |||
| batteryEqualizeVoltage OBJECT-TYPE The Voltage at which the DC System equalize charges the batteries. | 1.3.6.1.4.1.12148.10.10.22.1 | Integer32 (870..60418) | read-write | current |
| batteryEqualizeCommand OBJECT-TYPE This pushbutton will start or stop a manual battery equalize if the system allows it. | 1.3.6.1.4.1.12148.10.10.22.2 | INTEGER {pushbutton(0), startequalize(1), stopequalize(2)} | read-write | current |
| batteryEqualizeCurrentThreshold OBJECT-TYPE The equalizing will terminate when the charge current drops below the EqualizeCurrentThreshold limit. | 1.3.6.1.4.1.12148.10.10.22.3 | Integer32 | read-write | current |
| batteryEqualizeManualMaxDuration OBJECT-TYPE A protection against overcharging. When running manual equalize, the boosting will always terminate at this point. | 1.3.6.1.4.1.12148.10.10.22.4 | Integer32 (0..1440) | read-write | current |
| batteryAhCharged OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.23 | |||
| batteryAhChargedStatus OBJECT-TYPE The status of the battery ah charged monitor. | 1.3.6.1.4.1.12148.10.10.23.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryAhChargedDescription OBJECT-TYPE A textual description of the battery ah charged monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.10.23.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryAhChargedTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.23.3 | Counter32 | accessible-for-notify | current |
| batteryAhChargedAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.23.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryAhChargedValue OBJECT-TYPE The calculated battery ah (x100) charged value. | 1.3.6.1.4.1.12148.10.10.23.5 | Integer32 | read-only | current |
| batteryAhChargedMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.10.23.6 | Integer32 | read-write | current |
| batteryAhChargedMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.10.23.7 | Integer32 | read-write | current |
| batteryAhDischarged OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.10.24 | |||
| batteryAhDischargedStatus OBJECT-TYPE The status of the battery ah discharged monitor. | 1.3.6.1.4.1.12148.10.10.24.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryAhDischargedDescription OBJECT-TYPE A textual description of the battery ah discharged monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.10.24.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryAhDischargedTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.10.24.3 | Counter32 | accessible-for-notify | current |
| batteryAhDischargedAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.10.24.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryAhDischargedValue OBJECT-TYPE The calculated battery ah (x100) discharged value. | 1.3.6.1.4.1.12148.10.10.24.5 | Integer32 | read-only | current |
| batteryAhDischargedMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.10.24.6 | Integer32 | read-write | current |
| batteryAhDischargedMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.10.24.7 | Integer32 | read-write | current |
| inputs OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.11 | |||
| inputControlUnitsTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.11.1 | not-accessible | current | |
| inputControlUnitsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.11.1.1 | not-accessible | current | |
| inputControlUnitIndex OBJECT-TYPE Index used for navigating the rows of inputControlUnitTable The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.11.1.1.1 | Integer32 (1..14) | not-accessible | current |
| inputControlUnitNumberOfInputs OBJECT-TYPE Number of programmable inputs available in controller. | 1.3.6.1.4.1.12148.10.11.1.1.2 | Integer32 (0..8) | read-only | current |
| inputControlUnitInputTable OBJECT-TYPE This table contains the status of the programmable inputs for Control Units. | 1.3.6.1.4.1.12148.10.11.2 | not-accessible | current | |
| inputControlUnitInputEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.11.2.1 | not-accessible | current | |
| inputControlUnitInputIndex OBJECT-TYPE Index used for navigating the rows of inputControlUnitInputTable The size of the table is defined by the inputControlUnitNumberOfInputs | 1.3.6.1.4.1.12148.10.11.2.1.1 | Integer32 (1..10) | not-accessible | current |
| inputControlUnitInputStatus OBJECT-TYPE Programmable input status. | 1.3.6.1.4.1.12148.10.11.2.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| inputControlUnitInputDescription OBJECT-TYPE A textual description of the programmable input. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.11.2.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| inputControlUnitInputTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.11.2.1.4 | Counter32 | accessible-for-notify | current |
| inputControlUnitInputAlarmEnable OBJECT-TYPE This will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state | 1.3.6.1.4.1.12148.10.11.2.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| inputControlUnitInputValue OBJECT-TYPE The inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current or a Boolean value. Note: This value can only be set for virtual input on SP2 master or Smartpack S. When this value is set to '0', the input is deactivated; When this value is set to '1', the input is activated; if set to any other value, an Inconsistent Value error will be generated. | 1.3.6.1.4.1.12148.10.11.2.1.6 | Integer32 | read-write | current |
| inputControlUnitInputConfiguration OBJECT-TYPE Configuration of the input type. Configurations available for different controllers are as follows: SP2 Master(clock, virtual), SP2 Basic(normally open, normally closed),Compack(normally open, normally closed, diode matrix, voltage, clock), SmartpackS(normally open, normally closed,voltage) | 1.3.6.1.4.1.12148.10.11.2.1.7 | INTEGER {normallyOpen(1), normallyClosed(2), diodeMatrix(3), voltage(4), clock(5), virtual(6)} | read-write | current |
| inputIoUnitsTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.11.3 | not-accessible | current | |
| inputIoUnitsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.11.3.1 | not-accessible | current | |
| inputIoUnitIndex OBJECT-TYPE Index used for navigating the rows of inputIoUnitsTable The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.11.3.1.1 | Integer32 (1..14) | not-accessible | current |
| inputIoUnitNumberOfInputs OBJECT-TYPE Number of programmable inputs available in IO unit. | 1.3.6.1.4.1.12148.10.11.3.1.2 | Integer32 (0..8) | read-only | current |
| inputIoUnitProgInputTable OBJECT-TYPE This table contains the status of the programmable inputs for I/O monitor units. . | 1.3.6.1.4.1.12148.10.11.4 | not-accessible | current | |
| inputIoUnitProgInputEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.11.4.1 | not-accessible | current | |
| inputIoUnitProgInputIndex OBJECT-TYPE The Index to the Input of the selected I/O monitor unit. Or the input number if you like. | 1.3.6.1.4.1.12148.10.11.4.1.1 | Integer32 (1..6) | not-accessible | current |
| inputIoUnitProgInputStatus OBJECT-TYPE Programmable input status. | 1.3.6.1.4.1.12148.10.11.4.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| inputIoUnitProgInputDescription OBJECT-TYPE A textual description of the programmable input in IO unit. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.11.4.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| inputIoUnitProgInputTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.11.4.1.4 | Counter32 | accessible-for-notify | current |
| inputIoUnitProgInputAlarmEnable OBJECT-TYPE This will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state | 1.3.6.1.4.1.12148.10.11.4.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| inputIoUnitProgInputValue OBJECT-TYPE The inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current or a Boolean value. | 1.3.6.1.4.1.12148.10.11.4.1.6 | Integer32 | read-only | current |
| inputIoUnitProgInputConfiguration OBJECT-TYPE Configuration of the input type. Configurations available for IO unit are normally open, normally closed, diode matrix, voltage and clock. Note: If an input is set to 'clock', it can not be configurated to 'normally open', 'normally closed' and 'diode matrix' directly, it has to be configurated to 'voltage' first. | 1.3.6.1.4.1.12148.10.11.4.1.7 | INTEGER {normallyOpen(1), normallyClosed(2), diodeMatrix(3), voltage(4), clock(5)} | read-write | current |
| outputs OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.12 | |||
| outputControlUnitTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.12.1 | not-accessible | current | |
| outputControlUnitEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.12.1.1 | not-accessible | current | |
| outputControlUnitIndex OBJECT-TYPE Index used for navigating the rows of outputControlUnitTable The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.12.1.1.1 | Integer32 (1..14) | not-accessible | current |
| outputControlUnitNumberOfOutputs OBJECT-TYPE Number of outputs available in controller. | 1.3.6.1.4.1.12148.10.12.1.1.2 | Integer32 (0..8) | read-only | current |
| outputControlUnitOutputTable OBJECT-TYPE This table contains the status of the outputs for Control Units. | 1.3.6.1.4.1.12148.10.12.2 | not-accessible | current | |
| outputControlUnitOutputEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.12.2.1 | not-accessible | current | |
| outputControlUnitOutputIndex OBJECT-TYPE Index used for navigating the rows of outputControlUnitoutputTable The size of the table is defined by the outputControlUnitNumberOfOutputs | 1.3.6.1.4.1.12148.10.12.2.1.1 | Integer32 (1..16) | not-accessible | current |
| outputControlUnitOutputStatus OBJECT-TYPE General output relays may be 'energized' or 'not energized'. 'energized' and 'not energized' correspond to normal and alarm condition respectively for normally activated configuration. Latched contactors may have values 'disconnected' or 'connected' | 1.3.6.1.4.1.12148.10.12.2.1.2 | INTEGER {notenergized(0), energized(1), disconnected(2), connected(3)} | read-only | current |
| outputControlUnitOutputDescription OBJECT-TYPE A textual description of the output. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.12.2.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| outputIoUnitTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.12.3 | not-accessible | current | |
| outputIoUnitEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.12.3.1 | not-accessible | current | |
| outputIoUnitIndex OBJECT-TYPE Index used for navigating the rows of outputIoUnitTable The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.12.3.1.1 | Integer32 (1..14) | not-accessible | current |
| outputIoUnitNumberOfOutputs OBJECT-TYPE Number of outputs available in IO unit. | 1.3.6.1.4.1.12148.10.12.3.1.2 | Integer32 (0..8) | read-only | current |
| outputIoUnitOutputTable OBJECT-TYPE This table contains the status of the outputs for IO Units. | 1.3.6.1.4.1.12148.10.12.4 | not-accessible | current | |
| outputIoUnitOutputEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.12.4.1 | not-accessible | current | |
| outputIoUnitOutputIndex OBJECT-TYPE Index used for navigating the rows of outputIOUnitOutputTable The size of the table is defined by the outputIOUnitNumberOfOutputs | 1.3.6.1.4.1.12148.10.12.4.1.1 | Integer32 (1..14) | not-accessible | current |
| outputIoUnitOutputStatus OBJECT-TYPE General output relays may be 'energized' or 'not energized'. Latched contactors may have values 'disconnected' or 'connected' | 1.3.6.1.4.1.12148.10.12.4.1.2 | INTEGER {notenergized(0), energized(1), disconnected(2), connected(3)} | read-only | current |
| outputIoUnitOutputDescription OBJECT-TYPE A textual description of the output in IO unit. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.12.4.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| controlSystem OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13 | |||
| controlSystemStatus OBJECT-TYPE The overall status of control system subsystem | 1.3.6.1.4.1.12148.10.13.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| controlSystemClock OBJECT-TYPE This is the system time. | 1.3.6.1.4.1.12148.10.13.2 | DateAndTime (SIZE(8..11)) | read-write | current |
| controlSystemNumberOfControlUnits OBJECT-TYPE Total number of main controllers (SP2 Master, SP2 Basic Ind, SP2 Basic, Compack, Smartpack S, Smartpack) | 1.3.6.1.4.1.12148.10.13.3 | Integer32 (1..14) | read-write | current |
| snmp OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.4 | |||
| snmpSendOffTraps OBJECT-TYPE When this is enabled, a trap is sent when a alarm condition goes off . | 1.3.6.1.4.1.12148.10.13.4.1 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| snmpTrapRepeatRate OBJECT-TYPE The time between every repeated trap when an alarm condition is on. To turn repetetive traps off, set to zero. Can be 0 to 1440 minutes i.e 24 hours. | 1.3.6.1.4.1.12148.10.13.4.2 | Integer32 (0..1440) | read-write | current |
| snmpHeartBeatTrapRepeatRate OBJECT-TYPE The time between every heartbeat trap when an alarm condition is on. To turn heartbeat traps off, set to zero. Can be 0 to 1440 minutes i.e 24 hours. | 1.3.6.1.4.1.12148.10.13.4.3 | Integer32 (0..1440) | read-write | current |
| snmpInhibitTraps OBJECT-TYPE When this is enabled, no trap is sent regardless of alarm conditions. | 1.3.6.1.4.1.12148.10.13.4.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| controlSystemResetManualAlarms OBJECT-TYPE Reset manual alarms and put buzzer into silence. | 1.3.6.1.4.1.12148.10.13.5 | INTEGER {pushbutton(0), resetalarm(1)} | read-write | current |
| controlSystemResetNumberOfModules OBJECT-TYPE If set to '1', the number of modules (rectifier, solar charger, wind charger, control units, etc.) will be reset, and only those modules communicating are counted. | 1.3.6.1.4.1.12148.10.13.6 | INTEGER {pushbutton(0), resetnumber(1)} | read-write | current |
| controlSystemIoUnits OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.7 | |||
| controlSystemIoUnitsNumberOfUnits OBJECT-TYPE This is the number of IO units installed in the system. | 1.3.6.1.4.1.12148.10.13.7.1 | Integer32 (0..14) | read-write | current |
| controlSystemIoUnitsTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.7.2 | not-accessible | current | |
| controlSystemIoUnitsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.7.2.1 | not-accessible | current | |
| controlSystemIoUnitIndex OBJECT-TYPE Index used for navigating the rows of controlSystemIoUnitTable The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.13.7.2.1.1 | Integer32 (1..14) | not-accessible | current |
| controlSystemIoUnitNumberOfTemperatures OBJECT-TYPE Number of temperature measurements available in IO unit | 1.3.6.1.4.1.12148.10.13.7.2.1.2 | Integer32 (0..4) | read-only | current |
| controlSystemIoUnitNumberOfFans OBJECT-TYPE Number of fan measurements available in IO unit | 1.3.6.1.4.1.12148.10.13.7.2.1.3 | Integer32 (0..4) | read-only | current |
| controlSystemIoUnitTemperatureTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.7.3 | not-accessible | current | |
| controlSystemIoUnitTemperatureEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.7.3.1 | not-accessible | current | |
| controlSystemIoUnitTemperatureIndex OBJECT-TYPE Index used for navigating the rows of controlSystemIoUnitTemperatureTable The size of the table is defined by the controlSystemIoUnitNumberOfTemperatures | 1.3.6.1.4.1.12148.10.13.7.3.1.1 | Integer32 (1..2) | not-accessible | current |
| controlSystemIoUnitTemperatureStatus OBJECT-TYPE The status of temperature monitor | 1.3.6.1.4.1.12148.10.13.7.3.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| controlSystemIoUnitTemperatureDescription OBJECT-TYPE A textual description of the temperature monitor in control system. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.7.3.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| controlSystemIoUnitTemperatureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.13.7.3.1.4 | Counter32 | accessible-for-notify | current |
| controlSystemIoUnitTemperatureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.7.3.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| controlSystemIoUnitTemperatureValue OBJECT-TYPE The measured temperature value. | 1.3.6.1.4.1.12148.10.13.7.3.1.6 | Integer32 | read-only | current |
| controlSystemIoUnitTemperatureMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.13.7.3.1.7 | Integer32 | read-write | current |
| controlSystemIoUnitTemperatureMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.13.7.3.1.8 | Integer32 | read-write | current |
| controlSystemIoUnitTemperatureMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.13.7.3.1.9 | Integer32 | read-write | current |
| controlSystemIoUnitTemperatureMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.13.7.3.1.10 | Integer32 | read-write | current |
| controlSystemIoUnitFanTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.7.4 | not-accessible | current | |
| controlSystemIoUnitFanEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.7.4.1 | not-accessible | current | |
| controlSystemIoUnitFanIndex OBJECT-TYPE Index used for navigating the rows 1..2 of ioUnitFan Table | 1.3.6.1.4.1.12148.10.13.7.4.1.1 | Integer32 (1..2) | not-accessible | current |
| controlSystemIoUnitFanSpeedValue OBJECT-TYPE The measured fan speed | 1.3.6.1.4.1.12148.10.13.7.4.1.2 | Integer32 | read-only | current |
| controlSystemIoUnitFanSpeedDeviation OBJECT-TYPE The measured fan speed deviation | 1.3.6.1.4.1.12148.10.13.7.4.1.3 | Integer32 | read-only | current |
| controlSystemIoUnitFanControl OBJECT-TYPE Fan speed control value in percentage | 1.3.6.1.4.1.12148.10.13.7.4.1.4 | Integer32 | read-only | current |
| controlSystemInventory OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.8 | |||
| controlUnitNumberOfUnits OBJECT-TYPE Total number of control units installed in system. | 1.3.6.1.4.1.12148.10.13.8.1 | Integer32 (1..254) | read-only | current |
| controlUnitTable OBJECT-TYPE A table containing an inventory listing. Each row represent one of the system hardware unit that is connected to the can bus. These units are system controllers, battery monitors, I/O units, AC Mains Monitor boxes and load monitors. Due to the system architechture the tables index are not contiguous. Each unit type har its own address range on the can bus. All unit types except the system controller may contain from 0 to 14 units. The system controlller can never be zero. Then there is no powersystem. | 1.3.6.1.4.1.12148.10.13.8.2 | not-accessible | current | |
| controlUnitEntry OBJECT-TYPE One row in the table containing all hardware units connected to the canbus. | 1.3.6.1.4.1.12148.10.13.8.2.1 | not-accessible | current | |
| controlUnitIndex OBJECT-TYPE Index used for navigating the rows of controlUnitTable The size of the table is defined by the controlUnitNumberOfUnits | 1.3.6.1.4.1.12148.10.13.8.2.1.1 | Integer32 (1..254) | not-accessible | current |
| controlUnitDescription OBJECT-TYPE A textual description of the control unit | 1.3.6.1.4.1.12148.10.13.8.2.1.2 | DisplayString (SIZE(0..32)) | read-only | current |
| controlUnitStatus OBJECT-TYPE The overall status of the control unit. | 1.3.6.1.4.1.12148.10.13.8.2.1.3 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| controlUnitSerialNumber OBJECT-TYPE Serial number of the control unit. | 1.3.6.1.4.1.12148.10.13.8.2.1.4 | DisplayString (SIZE(0..12)) | read-only | current |
| controlUnitHwPartNumber OBJECT-TYPE Hardware part number of the control unit. | 1.3.6.1.4.1.12148.10.13.8.2.1.5 | DisplayString (SIZE(0..12)) | read-only | current |
| controlUnitHwVersion OBJECT-TYPE Hardware version of the control unit. | 1.3.6.1.4.1.12148.10.13.8.2.1.6 | DisplayString (SIZE(0..20)) | read-only | current |
| controlUnitSwPartNumber OBJECT-TYPE Software part number of the control unit. | 1.3.6.1.4.1.12148.10.13.8.2.1.7 | DisplayString (SIZE(0..12)) | read-only | current |
| controlUnitSwVersion OBJECT-TYPE Software version of the control unit. | 1.3.6.1.4.1.12148.10.13.8.2.1.8 | DisplayString (SIZE(0..20)) | read-only | current |
| currentMonitors OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.9 | |||
| currentMonitorsNumberOfUnits OBJECT-TYPE This is the number of current monitors installed in the system. | 1.3.6.1.4.1.12148.10.13.9.1 | Integer32 (0..14) | read-write | current |
| currentMonitorsTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.2 | not-accessible | current | |
| currentMonitorsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.2.1 | not-accessible | current | |
| currentMonitorIndex OBJECT-TYPE Index used for navigating the rows of currentMonitorsTable The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.13.9.2.1.1 | Integer32 (1..14) | not-accessible | current |
| currentMonitorType OBJECT-TYPE This shows if the current monitor is configured as standard load monitor (1), load current monitor (2), rectifier current monitor (3), dcdc current monitor (4), solar current monitor (5), wind current monitor (6) or fuel cell current monitor (7). | 1.3.6.1.4.1.12148.10.13.9.2.1.2 | INTEGER {stdLoadMonitor(1), loadCurrMonitor(2), rectCurrMonitor(3), dcdcCurrMonitor(4), solarCurrMonitor(5), windCurrMonitor(6), fuelcellCurrMonitor(7)} | read-only | current |
| currentMonitorId OBJECT-TYPE This is the unit index for each current monitor type. | 1.3.6.1.4.1.12148.10.13.9.2.1.3 | Integer32 | read-only | current |
| currentMonitorNumberOfFuses OBJECT-TYPE Number of fuse measurements in current monitor. | 1.3.6.1.4.1.12148.10.13.9.2.1.4 | Integer32 (0..8) | read-only | current |
| currentMonitorNumberOfCurrents OBJECT-TYPE Number of current measurements in current monitor. | 1.3.6.1.4.1.12148.10.13.9.2.1.5 | Integer32 (0..8) | read-only | current |
| currentMonitorFuseTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.3 | not-accessible | current | |
| currentMonitorFuseEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.3.1 | not-accessible | current | |
| currentMonitorFuseIndex OBJECT-TYPE Index used for navigating the rows of currentMonitorFuseTable The size of the table is defined by the currentMonitorNumberOfFuses | 1.3.6.1.4.1.12148.10.13.9.3.1.1 | Integer32 (1..8) | not-accessible | current |
| currentMonitorFuseStatus OBJECT-TYPE The status of fuse in current monitor | 1.3.6.1.4.1.12148.10.13.9.3.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| currentMonitorFuseDescription OBJECT-TYPE A textual description of the fuse monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.9.3.1.3 | DisplayString (SIZE(1..16)) | read-write | current |
| currentMonitorFuseTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.13.9.3.1.4 | Counter32 | accessible-for-notify | current |
| currentMonitorFuseAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.9.3.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| currentMonitorFuseValue OBJECT-TYPE The measured fuse value. | 1.3.6.1.4.1.12148.10.13.9.3.1.6 | Integer32 | read-only | current |
| currentMonitorCurrentTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.4 | not-accessible | current | |
| currentMonitorCurrentEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.4.1 | not-accessible | current | |
| currentMonitorCurrentIndex OBJECT-TYPE Index used for navigating the rows of currentMonitorCurrentTable The size of the table is defined by the currentMonitorNumberOfCurrents | 1.3.6.1.4.1.12148.10.13.9.4.1.1 | Integer32 (1..8) | not-accessible | current |
| currentMonitorCurrentStatus OBJECT-TYPE The status of current in current monitor | 1.3.6.1.4.1.12148.10.13.9.4.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| currentMonitorCurrentDescription OBJECT-TYPE A textual description of the current monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.9.4.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| currentMonitorCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.13.9.4.1.4 | Counter32 | accessible-for-notify | current |
| currentMonitorCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.9.4.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| currentMonitorCurrentValue OBJECT-TYPE The measured current value. | 1.3.6.1.4.1.12148.10.13.9.4.1.6 | Integer32 | read-only | current |
| currentMonitorCurrentMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.9.4.1.7 | Integer32 | read-write | current |
| currentMonitorCurrentMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.13.9.4.1.8 | Integer32 | read-write | current |
| currentMonitorEnergyLogAccumulatedTable OBJECT-TYPE This table contains the accumulated energy consumption measured in current monitor | 1.3.6.1.4.1.12148.10.13.9.5 | not-accessible | current | |
| currentMonitorEnergyLogAccumulatedEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.5.1 | not-accessible | current | |
| currentMonitorEnergyLogAccumulated OBJECT-TYPE The accumulated energy consumption value | 1.3.6.1.4.1.12148.10.13.9.5.1.1 | Integer32 | read-only | current |
| currentMonitorEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in hourly energy log | 1.3.6.1.4.1.12148.10.13.9.6 | Integer32 (0..52) | read-only | current |
| currentMonitorEnergyLogLastHoursTable OBJECT-TYPE This table contains energy consumption values logged every hour in current monitor. | 1.3.6.1.4.1.12148.10.13.9.7 | not-accessible | current | |
| currentMonitorEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.7.1 | not-accessible | current | |
| currentMonitorEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.13.9.7.1.1 | Integer32 (1..52) | not-accessible | current |
| currentMonitorEnergyLogLastHoursValue OBJECT-TYPE Energy consumption value logged every hour in current monitor. | 1.3.6.1.4.1.12148.10.13.9.7.1.2 | Integer32 | read-only | current |
| currentMonitorEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in daily energy log | 1.3.6.1.4.1.12148.10.13.9.8 | Integer32 (0..52) | read-only | current |
| currentMonitorEnergyLogLastDaysTable OBJECT-TYPE This table contains energy consumption values logged every day in current monitor. | 1.3.6.1.4.1.12148.10.13.9.9 | not-accessible | current | |
| currentMonitorEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.9.1 | not-accessible | current | |
| currentMonitorEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.13.9.9.1.1 | Integer32 (1..52) | not-accessible | current |
| currentMonitorEnergyLogLastDaysValue OBJECT-TYPE Energy consumption value logged every day in current monitor. | 1.3.6.1.4.1.12148.10.13.9.9.1.2 | Integer32 | read-only | current |
| currentMonitorEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in weekly energy log | 1.3.6.1.4.1.12148.10.13.9.10 | Integer32 (0..52) | read-only | current |
| currentMonitorEnergyLogLastWeeksTable OBJECT-TYPE This table contains energy consumption values logged every week in current monitor. | 1.3.6.1.4.1.12148.10.13.9.11 | not-accessible | current | |
| currentMonitorEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.9.11.1 | not-accessible | current | |
| currentMonitorEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastWeekTable | 1.3.6.1.4.1.12148.10.13.9.11.1.1 | Integer32 (1..52) | not-accessible | current |
| currentMonitorEnergyLogLastWeeksValue OBJECT-TYPE Energy consumption value logged every week in current monitor. | 1.3.6.1.4.1.12148.10.13.9.11.1.2 | Integer32 | read-only | current |
| flexiMonitors OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.10 | |||
| flexiMonitorsNumberOfUnits OBJECT-TYPE This is the number of fleximonitors installed in the system. | 1.3.6.1.4.1.12148.10.13.10.1 | Integer32 (0..14) | read-write | current |
| flexiMonitorsTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.10.2 | not-accessible | current | |
| flexiMonitorsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.10.2.1 | not-accessible | current | |
| flexiMonitorIndex OBJECT-TYPE Index used for navigating the rows of flexiMonitorsTable The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.13.10.2.1.1 | Integer32 (1..14) | not-accessible | current |
| flexiMonitorType OBJECT-TYPE This shows if the fleximonitor is configured as battery monitor (1), load monitor (2), rectifier monitor (3), controller monitor(4), dcdc monitor (5), solar monitor (6), wind monitor (7) or fuel cell monitor 8). | 1.3.6.1.4.1.12148.10.13.10.2.1.2 | INTEGER {battFlexiMonitor(1), loadFlexiMonitor(2), rectFlexiMonitor(3), contrFlexiMonitor(4), dcdcFlexiMonitor(5), solarFlexiMonitor(6), windFlexiMonitor(7), fuelcFlexiMonitor(8)} | read-only | current |
| flexiMonitorId OBJECT-TYPE This is the unit index for each fleximonitor type. | 1.3.6.1.4.1.12148.10.13.10.2.1.3 | Integer32 | read-only | current |
| flexiMonitorNumberOfInputs OBJECT-TYPE Number of inputs in fleximonitor. | 1.3.6.1.4.1.12148.10.13.10.2.1.4 | Integer32 (0..8) | read-only | current |
| flexiMonitorNumberOfOutputs OBJECT-TYPE Number of outputs in fleximonitor. | 1.3.6.1.4.1.12148.10.13.10.2.1.5 | Integer32 | read-only | current |
| flexiMonitorInputTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.10.3 | not-accessible | current | |
| flexiMonitorInputEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.10.3.1 | not-accessible | current | |
| flexiMonitorInputIndex OBJECT-TYPE Index used for navigating the rows of flexiMonitorInputTable The size of the table is defined by the flexiMonitorNumberOfInputs | 1.3.6.1.4.1.12148.10.13.10.3.1.1 | Integer32 (1..16) | not-accessible | current |
| flexiMonitorInputStatus OBJECT-TYPE Programmable input status. | 1.3.6.1.4.1.12148.10.13.10.3.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| flexiMonitorInputDescription OBJECT-TYPE A textual description of the programmable input. This is stored in the system controller and can be changed by the user. . | 1.3.6.1.4.1.12148.10.13.10.3.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| flexiMonitorInputTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.13.10.3.1.4 | Counter32 | accessible-for-notify | current |
| flexiMonitorInputAlarmEnable OBJECT-TYPE This will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state | 1.3.6.1.4.1.12148.10.13.10.3.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| flexiMonitorInputValue OBJECT-TYPE The inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current, a Speed or a Boolean value. | 1.3.6.1.4.1.12148.10.13.10.3.1.6 | Integer32 | read-only | current |
| flexiMonitorInputConfiguration OBJECT-TYPE Configuration of the input type. Available configurations are: ProgIn-Normally Open(1), ProgIn-Normally Closed(2), Voltage(3), Temperature(4),Current(5),Speed(6),Fuse-Normally Open(7),Fuse-Normally Closed(8), Fuse-Diode Matrix(9). | 1.3.6.1.4.1.12148.10.13.10.3.1.7 | INTEGER {progIn-NormallyOpen(1), progIn-NormallyClosed(2), voltage(3), temperature(4), current(5), speed(6), fuse-NormallyOpen(7), fuse-NormallyClosed(8), fuse-DiodeMatrix(9)} | read-write | current |
| flexiMonitorOutputTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.10.4 | not-accessible | current | |
| flexiMonitorOutputEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.10.4.1 | not-accessible | current | |
| flexiMonitorOutputIndex OBJECT-TYPE Index used for navigating the rows of flexiMonitorOutputTable The size of the table is defined by the flexiMonitorNumberOfOutputs | 1.3.6.1.4.1.12148.10.13.10.4.1.1 | Integer32 (1..16) | not-accessible | current |
| flexiMonitorOutputStatus OBJECT-TYPE General output relays may be 'energized' or 'not energized'. 'energized' and 'not energized' correspond to normal and alarm condition respectively for normally activated configuration. Latched contactors may have values 'disconnected' or 'connected' | 1.3.6.1.4.1.12148.10.13.10.4.1.2 | INTEGER {notenergized(0), energized(1), disconnected(2), connected(3)} | read-only | current |
| flexiMonitorOutputDescription OBJECT-TYPE A textual description of the output. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.10.4.1.3 | DisplayString | read-write | current |
| mainControlUnits OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.11 | |||
| mainControlUnitsTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.11.1 | not-accessible | current | |
| mainControlUnitsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.11.1.1 | not-accessible | current | |
| mainControlUnitIndex OBJECT-TYPE Index used for navigating the rows of controlUnitTable The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.13.11.1.1.1 | Integer32 (1..14) | not-accessible | current |
| mainControlUnitNumberOfTemperatures OBJECT-TYPE Total number of temperature measurements in main controller | 1.3.6.1.4.1.12148.10.13.11.1.1.2 | Integer32 (1..14) | read-only | current |
| mainControlUnitTemperatureTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.11.2 | not-accessible | current | |
| mainControlUnitTemperatureEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.11.2.1 | not-accessible | current | |
| mainControlUnitTemperatureIndex OBJECT-TYPE This index denotes which row in the temperature input table. The size of the table is defined by the batteryBankNumberOfTemp | 1.3.6.1.4.1.12148.10.13.11.2.1.1 | Integer32 (1..4) | not-accessible | current |
| mainControlUnitTemperatureStatus OBJECT-TYPE The status of battery temperature monitor | 1.3.6.1.4.1.12148.10.13.11.2.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainControlUnitTemperatureDescription OBJECT-TYPE A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.11.2.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| mainControlUnitTemperatureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.11.2.1.4 | Counter32 | accessible-for-notify | current |
| mainControlUnitTemperatureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.11.2.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainControlUnitTemperatureValue OBJECT-TYPE The measured battery temperature. | 1.3.6.1.4.1.12148.10.13.11.2.1.6 | Integer32 | read-only | current |
| mainControlUnitTemperatureMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.13.11.2.1.7 | Integer32 | read-write | current |
| mainControlUnitTemperatureMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.13.11.2.1.8 | Integer32 | read-write | current |
| mainControlUnitTemperatureMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.13.11.2.1.9 | Integer32 | read-write | current |
| mainControlUnitTemperatureMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.13.11.2.1.10 | Integer32 | read-write | current |
| mainControlUnitEarthFaultTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.11.3 | not-accessible | current | |
| mainControlUnitEarthFaultEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.13.11.3.1 | not-accessible | current | |
| mainControlUnitEarthFaultStatus OBJECT-TYPE This status value shows if the earth resistance is lower than the defined alarm level. | 1.3.6.1.4.1.12148.10.13.11.3.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainControlUnitEarthFaultDescription OBJECT-TYPE A textual description of the earth fault monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.11.3.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| mainControlUnitEarthFaultTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.11.3.1.3 | Integer32 | accessible-for-notify | current |
| mainControlUnitEarthFaultAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.11.3.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainControlUnitEarthFaultValue OBJECT-TYPE The measured value of the earth resistance in kOhm. | 1.3.6.1.4.1.12148.10.13.11.3.1.5 | Integer32 | read-only | current |
| mainControlUnitEarthFaultMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.11.3.1.6 | Integer32 | read-write | current |
| controlSystemSummary OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.12 | |||
| mainControlUnitsError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.12.1 | |||
| mainControlUnitsErrorStatus OBJECT-TYPE This status value shows if the number of failed main controllers is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.13.12.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainControlUnitsErrorDescription OBJECT-TYPE A textual description of the main control units error monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.12.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| mainControlUnitsErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.12.1.3 | Integer32 | accessible-for-notify | current |
| mainControlUnitsErrorAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.12.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainControlUnitsErrorValue OBJECT-TYPE The detected number of failed main controllers. | 1.3.6.1.4.1.12148.10.13.12.1.5 | Integer32 | read-only | current |
| mainControlUnitsErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.12.1.6 | Integer32 | read-write | current |
| mainControlUnitsErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.13.12.1.7 | Integer32 | read-write | current |
| smartNodeError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.12.2 | |||
| smartNodeErrorStatus OBJECT-TYPE This status value shows if the number of failed smartnodes is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.13.12.2.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| smartNodeErrorDescription OBJECT-TYPE A textual description of the smartnode error monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.12.2.2 | DisplayString (SIZE(0..16)) | read-write | current |
| smartNodeErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.12.2.3 | Integer32 | accessible-for-notify | current |
| smartNodeErrorAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.12.2.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| smartNodeErrorValue OBJECT-TYPE The detected number of failed smartnodes. | 1.3.6.1.4.1.12148.10.13.12.2.5 | Integer32 | read-only | current |
| smartNodeErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.12.2.6 | Integer32 | read-write | current |
| smartNodeErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.13.12.2.7 | Integer32 | read-write | current |
| batteryMonitorError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.12.3 | |||
| batteryMonitorErrorStatus OBJECT-TYPE This status value shows if the number of failed battery monitors is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.13.12.3.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryMonitorErrorDescription OBJECT-TYPE A textual description of the battery monitor error monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.12.3.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryMonitorErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.12.3.3 | Integer32 | accessible-for-notify | current |
| batteryMonitorErrorAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.12.3.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryMonitorErrorValue OBJECT-TYPE The detected number of failed battery monitors. | 1.3.6.1.4.1.12148.10.13.12.3.5 | Integer32 | read-only | current |
| batteryMonitorErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.12.3.6 | Integer32 | read-write | current |
| batteryMonitorErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.13.12.3.7 | Integer32 | read-write | current |
| loadMonitorError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.12.4 | |||
| loadMonitorErrorStatus OBJECT-TYPE This status value shows if the number of failed load monitors is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.13.12.4.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| loadMonitorErrorDescription OBJECT-TYPE A textual description of the load monitor error monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.12.4.2 | DisplayString (SIZE(0..16)) | read-write | current |
| loadMonitorErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.12.4.3 | Integer32 | accessible-for-notify | current |
| loadMonitorErrorAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.12.4.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| loadMonitorErrorValue OBJECT-TYPE The detected number of failed load monitors. | 1.3.6.1.4.1.12148.10.13.12.4.5 | Integer32 | read-only | current |
| loadMonitorErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.12.4.6 | Integer32 | read-write | current |
| loadMonitorErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.13.12.4.7 | Integer32 | read-write | current |
| ioUnitError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.12.5 | |||
| ioUnitErrorStatus OBJECT-TYPE This status value shows if the number of failed IO units is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.13.12.5.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| ioUnitErrorDescription OBJECT-TYPE A textual description of the IO unit error monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.12.5.2 | DisplayString (SIZE(0..16)) | read-write | current |
| ioUnitErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.12.5.3 | Integer32 | accessible-for-notify | current |
| ioUnitErrorAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.12.5.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| ioUnitErrorValue OBJECT-TYPE The detected number of failed IO units. | 1.3.6.1.4.1.12148.10.13.12.5.5 | Integer32 | read-only | current |
| ioUnitErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.12.5.6 | Integer32 | read-write | current |
| ioUnitErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.13.12.5.7 | Integer32 | read-write | current |
| mainsMonitorError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.12.6 | |||
| mainsMonitorErrorStatus OBJECT-TYPE This status value shows if the number of failed mains monitors is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.13.12.6.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| mainsMonitorErrorDescription OBJECT-TYPE A textual description of the mains monitor error monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.12.6.2 | DisplayString (SIZE(0..16)) | read-write | current |
| mainsMonitorErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.12.6.3 | Integer32 | accessible-for-notify | current |
| mainsMonitorErrorAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.12.6.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| mainsMonitorErrorValue OBJECT-TYPE The detected number of failed mains monitors. | 1.3.6.1.4.1.12148.10.13.12.6.5 | Integer32 | read-only | current |
| mainsMonitorErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.12.6.6 | Integer32 | read-write | current |
| mainsMonitorErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.13.12.6.7 | Integer32 | read-write | current |
| flexiMonitorError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.12.7 | |||
| flexiMonitorErrorStatus OBJECT-TYPE This status value shows if the number of failed flexi monitors is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.13.12.7.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| flexiMonitorErrorDescription OBJECT-TYPE A textual description of the flexi monitor error monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.12.7.2 | DisplayString (SIZE(0..16)) | read-write | current |
| flexiMonitorErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.12.7.3 | Integer32 | accessible-for-notify | current |
| flexiMonitorErrorAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.12.7.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| flexiMonitorErrorValue OBJECT-TYPE The detected number of failed flexi monitors. | 1.3.6.1.4.1.12148.10.13.12.7.5 | Integer32 | read-only | current |
| flexiMonitorErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.12.7.6 | Integer32 | read-write | current |
| flexiMonitorErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.13.12.7.7 | Integer32 | read-write | current |
| ambientTemperature OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.13 | |||
| ambientTemperatureStatus OBJECT-TYPE The state of the ambient temperature can be either one of the defined enumerated values | 1.3.6.1.4.1.12148.10.13.13.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| ambientTemperatureDescription OBJECT-TYPE A textual description of the ambient temperature monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.13.2 | DisplayString (SIZE(0..16)) | read-write | current |
| ambientTemperatureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.13.13.3 | Counter32 | accessible-for-notify | current |
| ambientTemperatureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.13.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| ambientTemperatureValue OBJECT-TYPE The highest value of the enabled ambient temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. | 1.3.6.1.4.1.12148.10.13.13.5 | Integer32 (0..9999) | read-only | current |
| ambientTemperatureMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.13.13.6 | Integer32 | read-write | current |
| ambientTemperatureMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.13.13.7 | Integer32 | read-write | current |
| ambientTemperatureMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.13.13.8 | Integer32 | read-write | current |
| ambientTemperatureMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.13.13.9 | Integer32 | read-write | current |
| deltaTemperature OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.14 | |||
| deltaTemperatureStatus OBJECT-TYPE The state of the delta temperature can be either one of the defined enumerated values | 1.3.6.1.4.1.12148.10.13.14.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| deltaTemperatureDescription OBJECT-TYPE A textual description of the delta temperature monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.14.2 | DisplayString (SIZE(0..16)) | read-write | current |
| deltaTemperatureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.13.14.3 | Counter32 | accessible-for-notify | current |
| deltaTemperatureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.14.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| deltaTemperatureValue OBJECT-TYPE The delta temperature value. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. | 1.3.6.1.4.1.12148.10.13.14.5 | Integer32 (0..9999) | read-only | current |
| deltaTemperatureMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.13.14.6 | Integer32 | read-write | current |
| deltaTemperatureMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.13.14.7 | Integer32 | read-write | current |
| deltaTemperatureMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.13.14.8 | Integer32 | read-write | current |
| deltaTemperatureMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.13.14.9 | Integer32 | read-write | current |
| userSuspended OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.13.15 | |||
| userSuspendedStatus OBJECT-TYPE This status value shows if the number of failed attempts is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.13.15.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| userSuspendedDescription OBJECT-TYPE A textual description of the login failure monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.13.15.2 | DisplayString (SIZE(0..16)) | read-write | current |
| userSuspendedTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.13.15.3 | Integer32 | accessible-for-notify | current |
| userSuspendedAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.13.15.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| userSuspendedValue OBJECT-TYPE The detected number of failed attempts. | 1.3.6.1.4.1.12148.10.13.15.5 | Integer32 | read-only | current |
| userSuspendedMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.13.15.6 | Integer32 | read-write | current |
| alarmGroups OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.14 | |||
| alarmGroupTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.14.1 | not-accessible | current | |
| alarmGroupEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.14.1.1 | not-accessible | current | |
| alarmGroupIndex OBJECT-TYPE Index used for navigating the rows 1..49 of alarmGroupTable | 1.3.6.1.4.1.12148.10.14.1.1.1 | Integer32 (1..49) | not-accessible | current |
| alarmGroupStatus OBJECT-TYPE The status of alarm group | 1.3.6.1.4.1.12148.10.14.1.1.2 | INTEGER {normal(0), alarm(1)} | read-only | current |
| alarmGroupDescription OBJECT-TYPE A textual description of the alarm group. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.14.1.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2 OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15 | |||
| batteryGroup2Status OBJECT-TYPE A toplevel status for the battery group 2.The state of this reflects the status of all underlying statuses for the battery. Any change in one of the 'data monitors' in the battery subsystem will propagate up to this status indicator. | 1.3.6.1.4.1.12148.10.15.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2Description OBJECT-TYPE A descriptive name of the battery installed in the battery group 2. | 1.3.6.1.4.1.12148.10.15.2 | DisplayString (SIZE(0..32)) | read-write | current |
| batteryGroup2ReferenceVoltage OBJECT-TYPE The reference voltage of battery group 2. | 1.3.6.1.4.1.12148.10.15.3 | Integer32 (840..60417) | read-write | current |
| batteryGroup2FusesStatus OBJECT-TYPE The state of the battery fuses/breakers can mainly be normal(1) or majorAlarm(3) and some other rarely used values . | 1.3.6.1.4.1.12148.10.15.4 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2Voltage OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.5 | |||
| batteryGroup2VoltageStatus OBJECT-TYPE The status of the measured battery voltage. | 1.3.6.1.4.1.12148.10.15.5.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2VoltageDescription OBJECT-TYPE A textual description of the battery voltage monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.5.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2VoltageTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.15.5.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2VoltageAlarmEnable OBJECT-TYPE The measured battery voltage alarm enable/disable control | 1.3.6.1.4.1.12148.10.15.5.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2VoltageValue OBJECT-TYPE The value of the measured battery voltage. | 1.3.6.1.4.1.12148.10.15.5.5 | Integer32 (0..7500) | read-only | current |
| batteryGroup2VoltageMajorHighLevel OBJECT-TYPE The Major High Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.10.15.5.6 | Integer32 | read-write | current |
| batteryGroup2VoltageMinorHighLevel OBJECT-TYPE The Minor High Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.10.15.5.7 | Integer32 | read-write | current |
| batteryGroup2VoltageMinorLowLevel OBJECT-TYPE The Minor Low Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.10.15.5.8 | Integer32 | read-write | current |
| batteryGroup2VoltageMajorLowLevel OBJECT-TYPE The Major Low Battery Voltage alarm limit set voltage | 1.3.6.1.4.1.12148.10.15.5.9 | Integer32 | read-write | current |
| batteryGroup2Currents OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.6 | |||
| batteryGroup2CurrentsStatus OBJECT-TYPE The status of the measured battery current | 1.3.6.1.4.1.12148.10.15.6.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2CurrentsDescription OBJECT-TYPE A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.6.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2CurrentsTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.15.6.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2CurrentsAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.6.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2CurrentsValue OBJECT-TYPE The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.10.15.6.5 | Integer32 | read-only | current |
| batteryGroup2CurrentsMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.15.6.6 | Integer32 | read-write | current |
| batteryGroup2CurrentsMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.15.6.7 | Integer32 | read-write | current |
| batteryGroup2CurrentsMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.15.6.8 | Integer32 | read-write | current |
| batteryGroup2CurrentsMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.15.6.9 | Integer32 | read-write | current |
| batteryGroup2Temperatures OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.7 | |||
| batteryGroup2TemperaturesStatus OBJECT-TYPE The state of the battery fuses/breakers can be either one of the defined enumerated values | 1.3.6.1.4.1.12148.10.15.7.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2TemperaturesDescription OBJECT-TYPE A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.7.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2TemperaturesTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.15.7.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2TemperaturesAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.7.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2TemperaturesValue OBJECT-TYPE The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. | 1.3.6.1.4.1.12148.10.15.7.5 | Integer32 (0..9999) | read-only | current |
| batteryGroup2TemperaturesMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.15.7.6 | Integer32 | read-write | current |
| batteryGroup2TemperaturesMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.15.7.7 | Integer32 | read-write | current |
| batteryGroup2TemperaturesMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.15.7.8 | Integer32 | read-write | current |
| batteryGroup2TemperaturesMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.15.7.9 | Integer32 | read-write | current |
| batteryGroup2TimeLeft OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.8 | |||
| batteryGroup2TimeLeftStatus OBJECT-TYPE The status of the estimated battery remaining backup time. | 1.3.6.1.4.1.12148.10.15.8.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2TimeLeftDescription OBJECT-TYPE A textual description of the battery discharge time monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.8.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2TimeLeftTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.15.8.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2TimeLeftAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.8.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2TimeLeftValue OBJECT-TYPE The estimated value of battery remaining backup time. | 1.3.6.1.4.1.12148.10.15.8.5 | Integer32 | read-only | current |
| batteryGroup2TimeLeftMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.15.8.6 | Integer32 | read-write | current |
| batteryGroup2TimeLeftMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.15.8.7 | Integer32 | read-write | current |
| batteryGroup2RemainingCapacity OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.9 | |||
| batteryGroup2RemainingCapacityStatus OBJECT-TYPE The status of the battery remaining capacity monitor. | 1.3.6.1.4.1.12148.10.15.9.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2RemainingCapacityDescription OBJECT-TYPE A textual description of the battery remaining capacity monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.9.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2RemainingCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.15.9.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2RemainingCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.9.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2RemainingCapacityValue OBJECT-TYPE Battery remaining capacity (SOC) value estimated from the latest battery test result. | 1.3.6.1.4.1.12148.10.15.9.5 | Integer32 | read-only | current |
| batteryGroup2RemainingCapacityMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.15.9.6 | Integer32 | read-write | current |
| batteryGroup2RemainingCapacityMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.15.9.7 | Integer32 | read-write | current |
| batteryGroup2UsedCapacity OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.10 | |||
| batteryGroup2UsedCapacityStatus OBJECT-TYPE The status of the battery used capacity (DoD) monitor | 1.3.6.1.4.1.12148.10.15.10.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2UsedCapacityDescription OBJECT-TYPE A textual description of the battery used capacity (DoD) monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.10.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2UsedCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.15.10.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2UsedCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.10.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2UsedCapacityValue OBJECT-TYPE This is the estimated battery used capacity (DoD). | 1.3.6.1.4.1.12148.10.15.10.5 | Integer32 | read-only | current |
| batteryGroup2UsedCapacityMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.15.10.6 | Integer32 | read-write | current |
| batteryGroup2UsedCapacityMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.15.10.7 | Integer32 | read-write | current |
| batteryGroup2TotalCapacity OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.11 | |||
| batteryGroup2TotalCapacityStatus OBJECT-TYPE The status of the total capacity monitor. | 1.3.6.1.4.1.12148.10.15.11.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2TotalCapacityDescription OBJECT-TYPE A textual description of the battery total capacity monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.15.11.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2TotalCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.15.11.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2TotalCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.11.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2TotalCapacityValue OBJECT-TYPE This is the estimated total battery capacity (installed Ah - SoH) value. | 1.3.6.1.4.1.12148.10.15.11.5 | Integer32 | read-only | current |
| batteryGroup2TotalCapacityMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.15.11.6 | Integer32 | read-write | current |
| batteryGroup2TotalCapacityMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.15.11.7 | Integer32 | read-write | current |
| batteryGroup2Quality OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.12 | |||
| batteryGroup2QualityStatus OBJECT-TYPE The status of the battery quality (SoH) monitor. | 1.3.6.1.4.1.12148.10.15.12.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2QualityDescription OBJECT-TYPE A textual description of the battery quality (SoH) monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.15.12.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2QualityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.15.12.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2QualityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.12.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2QualityValue OBJECT-TYPE The calculated battery quality (SoH) based on the latest battery test | 1.3.6.1.4.1.12148.10.15.12.5 | Integer32 | read-only | current |
| batteryGroup2QualityMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.15.12.6 | Integer32 | read-write | current |
| batteryGroup2QualityMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.15.12.7 | Integer32 | read-write | current |
| batteryGroup2LVBD OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.13 | |||
| batteryGroup2LVBDStatus OBJECT-TYPE The Battery Contactor is connected, disconnected, disabled or in any other alarm condition | 1.3.6.1.4.1.12148.10.15.13.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2LVBDDescription OBJECT-TYPE A textual description of the battery LVBD monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.13.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2LVBDTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.15.13.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2LVBDEnable OBJECT-TYPE This value once enabled, the alarm condition of the LVBD will be reported. | 1.3.6.1.4.1.12148.10.15.13.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2LVBDValue OBJECT-TYPE The measured value of the LVBD. | 1.3.6.1.4.1.12148.10.15.13.5 | Integer32 | read-only | current |
| batteryGroup2LVBDConnectVoltage OBJECT-TYPE The Battery Contactor's Reconnect Voltage | 1.3.6.1.4.1.12148.10.15.13.6 | Integer32 | read-write | current |
| batteryGroup2LVBDDisconnectVoltage OBJECT-TYPE The Battery Contactor's Disconnect Voltage | 1.3.6.1.4.1.12148.10.15.13.7 | Integer32 | read-write | current |
| batteryGroup2ChargeCurrentLimit OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.14 | |||
| batteryGroup2ChargeCurrentLimitEnable OBJECT-TYPE Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable. | 1.3.6.1.4.1.12148.10.15.14.1 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2ChargeCurrentLimitValue OBJECT-TYPE Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings | 1.3.6.1.4.1.12148.10.15.14.2 | Integer32 (0..32767) | read-write | current |
| batteryGroup2Boost OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.15 | |||
| batteryGroup2BoostVoltage OBJECT-TYPE The Voltage at which the DC System boost charges the batteries. | 1.3.6.1.4.1.12148.10.15.15.1 | Integer32 (870..60418) | read-write | current |
| batteryGroup2BoostCommand OBJECT-TYPE This pushbutton will start or stop a manual battery boost if the system allows it. | 1.3.6.1.4.1.12148.10.15.15.2 | INTEGER {pushbutton(0), startboost(1), stopboost(2)} | read-write | current |
| batteryGroup2BoostCurrentThreshold OBJECT-TYPE The boosting will terminate when the charge current drops below the BoostCurrentThreshold limit. | 1.3.6.1.4.1.12148.10.15.15.3 | Integer32 | read-write | current |
| batteryGroup2BoostManualMaxDuration OBJECT-TYPE A protection against overcharging. When running manual boost, the boosting will always terminate at this point. | 1.3.6.1.4.1.12148.10.15.15.4 | Integer32 (0..1440) | read-write | current |
| batteryGroup2Test OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.16 | |||
| batteryGroup2TestVoltage OBJECT-TYPE This is the battery test end voltage. The battery test will be terminated when the voltage drops below the end voltage. | 1.3.6.1.4.1.12148.10.15.16.1 | Integer32 | read-write | current |
| batteryGroup2TestCommand OBJECT-TYPE This pushbutton will start or stop a manual battery test if the system allows it. | 1.3.6.1.4.1.12148.10.15.16.2 | INTEGER {pushbutton(0), starttest(1), stoptest(2)} | read-write | current |
| batteryGroup2TestNumberOfResults OBJECT-TYPE This is the number of valid battery test results stored in controller. | 1.3.6.1.4.1.12148.10.15.16.3 | Integer32 (0..10) | read-only | current |
| batteryGroup2TestResultTable OBJECT-TYPE This table contains the battery test results stored in controller. | 1.3.6.1.4.1.12148.10.15.16.4 | not-accessible | current | |
| batteryGroup2TestResultEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.16.4.1 | not-accessible | current | |
| batteryGroup2TestResultIndex OBJECT-TYPE A index pointing to one of ten possible battery test results | 1.3.6.1.4.1.12148.10.15.16.4.1.1 | Integer32 (1..10) | not-accessible | current |
| batteryGroup2TestResultStartDateTime OBJECT-TYPE This is the time and date when the test started. | 1.3.6.1.4.1.12148.10.15.16.4.1.2 | DateAndTime | read-only | current |
| batteryGroup2TestResultDuration OBJECT-TYPE This is the test duration in minutes. | 1.3.6.1.4.1.12148.10.15.16.4.1.3 | Integer32 | read-only | current |
| batteryGroup2TestResultDischarged OBJECT-TYPE This is the discharged Ah during test. | 1.3.6.1.4.1.12148.10.15.16.4.1.4 | Integer32 | read-only | current |
| batteryGroup2TestResultQuality OBJECT-TYPE This is the calculated battery quality (SoH)in percentage. | 1.3.6.1.4.1.12148.10.15.16.4.1.5 | Integer32 | read-only | current |
| batteryGroup2TempComp OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.17 | |||
| batteryGroup2TempCompEnable OBJECT-TYPE Enable (1) or Disable (0) of Battery Temperature Compensated output regulation mode | 1.3.6.1.4.1.12148.10.15.17.1 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2Bank OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.18 | |||
| batteryGroup2BankStatus OBJECT-TYPE The overall status of battery bank | 1.3.6.1.4.1.12148.10.15.18.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2BankNumberOfTemperatures OBJECT-TYPE Number of temperature measurements in battery bank. | 1.3.6.1.4.1.12148.10.15.18.2 | Integer32 | read-only | current |
| batteryGroup2BankNumberOfCurrents OBJECT-TYPE Number of current measurements in battery bank. | 1.3.6.1.4.1.12148.10.15.18.3 | Integer32 | read-only | current |
| batteryGroup2BankNumberOfFuses OBJECT-TYPE Number of fuses installed in battery bank. | 1.3.6.1.4.1.12148.10.15.18.4 | Integer32 | read-only | current |
| batteryGroup2BankNumberOfSymmetries OBJECT-TYPE Number of fuses installed in battery bank. | 1.3.6.1.4.1.12148.10.15.18.5 | Integer32 | read-only | current |
| batteryGroup2BankTemperatureTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.18.6 | not-accessible | current | |
| batteryGroup2BankTemperatureEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.18.6.1 | not-accessible | current | |
| batteryGroup2TemperatureIndex OBJECT-TYPE This index denotes which row in the temperature input table. The size of the table is defined by the batteryGroup2BankNumberOfTemperatures | 1.3.6.1.4.1.12148.10.15.18.6.1.1 | Integer32 (1..4) | not-accessible | current |
| batteryGroup2TemperatureStatus OBJECT-TYPE The status of battery temperature monitor | 1.3.6.1.4.1.12148.10.15.18.6.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2TemperatureDescription OBJECT-TYPE A textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.18.6.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2TemperatureTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.15.18.6.1.4 | Counter32 | accessible-for-notify | current |
| batteryGroup2TemperatureAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.18.6.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2TemperatureValue OBJECT-TYPE The measured battery temperature. | 1.3.6.1.4.1.12148.10.15.18.6.1.6 | Integer32 | read-only | current |
| batteryGroup2TemperatureMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.15.18.6.1.7 | Integer32 | read-write | current |
| batteryGroup2TemperatureMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.15.18.6.1.8 | Integer32 | read-write | current |
| batteryGroup2TemperatureMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.15.18.6.1.9 | Integer32 | read-write | current |
| batteryGroup2TemperatureMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.15.18.6.1.10 | Integer32 | read-write | current |
| batteryGroup2BankCurrentTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.18.7 | not-accessible | current | |
| batteryGroup2BankCurrentEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.18.7.1 | not-accessible | current | |
| batteryGroup2CurrentIndex OBJECT-TYPE This index denotes which row in the current input table. The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.15.18.7.1.1 | Integer32 (1..4) | not-accessible | current |
| batteryGroup2CurrentStatus OBJECT-TYPE The status of battery current monitor | 1.3.6.1.4.1.12148.10.15.18.7.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2CurrentDescription OBJECT-TYPE A textual description of the battery current monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.18.7.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2CurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.15.18.7.1.4 | Counter32 | accessible-for-notify | current |
| batteryGroup2CurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.18.7.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2CurrentValue OBJECT-TYPE The measured battery current | 1.3.6.1.4.1.12148.10.15.18.7.1.6 | Integer32 | read-only | current |
| batteryGroup2CurrentMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.15.18.7.1.7 | Integer32 | read-write | current |
| batteryGroup2CurrentMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.15.18.7.1.8 | Integer32 | read-write | current |
| batteryGroup2CurrentMinorLowLevel OBJECT-TYPE The minor low alarm limit | 1.3.6.1.4.1.12148.10.15.18.7.1.9 | Integer32 | read-write | current |
| batteryGroup2CurrentMajorLowLevel OBJECT-TYPE The major low alarm limit | 1.3.6.1.4.1.12148.10.15.18.7.1.10 | Integer32 | read-write | current |
| batteryGroup2BankFuseTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.18.8 | not-accessible | current | |
| batteryGroup2BankFuseEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.18.8.1 | not-accessible | current | |
| batteryGroup2FuseIndex OBJECT-TYPE This index denotes which row in the fuse table. The size of the table is defined by the system | 1.3.6.1.4.1.12148.10.15.18.8.1.1 | Integer32 (1..4) | not-accessible | current |
| batteryGroup2FuseStatus OBJECT-TYPE The status of battery fuse monitor | 1.3.6.1.4.1.12148.10.15.18.8.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2FuseDescription OBJECT-TYPE A textual description of the battery fuse monitor. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.18.8.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2FuseTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off. | 1.3.6.1.4.1.12148.10.15.18.8.1.4 | Counter32 | accessible-for-notify | current |
| batteryGroup2FuseAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.18.8.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2FuseValue OBJECT-TYPE The measured value of battery fuse input. | 1.3.6.1.4.1.12148.10.15.18.8.1.6 | Integer32 | read-only | current |
| batteryGroup2BankSymmetryTable OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.18.9 | not-accessible | current | |
| batteryGroup2BankSymmetryEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.18.9.1 | not-accessible | current | |
| batteryGroup2BankSymmetryIndex OBJECT-TYPE This index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries | 1.3.6.1.4.1.12148.10.15.18.9.1.1 | Integer32 (1..8) | not-accessible | current |
| batteryGroup2BankSymmetryStatus OBJECT-TYPE The status of battery symmetry monitor | 1.3.6.1.4.1.12148.10.15.18.9.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2BankSymmetryDescription OBJECT-TYPE A textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user. | 1.3.6.1.4.1.12148.10.15.18.9.1.3 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2BankSymmetryTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.15.18.9.1.4 | Counter32 | accessible-for-notify | current |
| batteryGroup2BankSymmetryAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.18.9.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2BankSymmetryMeasureValue OBJECT-TYPE The measured battery symmetry voltage in battery monitor. | 1.3.6.1.4.1.12148.10.15.18.9.1.6 | Integer32 | read-only | current |
| batteryGroup2BankSymmetryDeltaValue OBJECT-TYPE The measured battery symmetry delta voltage in battery monitor. | 1.3.6.1.4.1.12148.10.15.18.9.1.7 | Integer32 | read-only | current |
| batteryGroup2BankSymmetryMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.15.18.9.1.8 | Integer32 | read-write | current |
| batteryGroup2BankSymmetryMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.15.18.9.1.9 | Integer32 | read-write | current |
| batteryGroup2EnergyLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.19 | |||
| batteryGroup2EnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered to/from battery. | 1.3.6.1.4.1.12148.10.15.19.1 | Integer32 | read-only | current |
| batteryGroup2EnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in battery hourly energy log. | 1.3.6.1.4.1.12148.10.15.19.2 | Integer32 (0..52) | read-only | current |
| batteryGroup2EnergyLogLastHoursTable OBJECT-TYPE This table contains hourly energy log of battery. | 1.3.6.1.4.1.12148.10.15.19.3 | not-accessible | current | |
| batteryGroup2EnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.19.3.1 | not-accessible | current | |
| batteryGroup2EnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.15.19.3.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryGroup2EnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.15.19.3.1.2 | Integer32 | read-only | current |
| batteryGroup2EnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in battery daily energy log. | 1.3.6.1.4.1.12148.10.15.19.4 | Integer32 (0..52) | read-only | current |
| batteryGroup2EnergyLogLastDaysTable OBJECT-TYPE This table contains daily energy log of battery. | 1.3.6.1.4.1.12148.10.15.19.5 | not-accessible | current | |
| batteryGroup2EnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.19.5.1 | not-accessible | current | |
| batteryGroup2EnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.15.19.5.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryGroup2EnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day. | 1.3.6.1.4.1.12148.10.15.19.5.1.2 | Integer32 | read-only | current |
| batteryGroup2EnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in battery weekly energy log. | 1.3.6.1.4.1.12148.10.15.19.6 | Integer32 (0..52) | read-only | current |
| batteryGroup2EnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly energy log of battery. | 1.3.6.1.4.1.12148.10.15.19.7 | not-accessible | current | |
| batteryGroup2EnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.19.7.1 | not-accessible | current | |
| batteryGroup2EnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable | 1.3.6.1.4.1.12148.10.15.19.7.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryGroup2EnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.15.19.7.1.2 | Integer32 | read-only | current |
| batteryGroup2CycleLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.20 | |||
| batteryGroup2CycleLogTotalCycles OBJECT-TYPE This is the total number of battery discharge cycles. | 1.3.6.1.4.1.12148.10.15.20.1 | Integer32 | read-only | current |
| batteryGroup2CycleLogDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in daily battery discharge cycle log. | 1.3.6.1.4.1.12148.10.15.20.2 | Integer32 (0..52) | read-only | current |
| batteryGroup2CycleLogDaysTable OBJECT-TYPE This table contains daily battery discharge cycle log. | 1.3.6.1.4.1.12148.10.15.20.3 | not-accessible | current | |
| batteryGroup2CycleLogDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.20.3.1 | not-accessible | current | |
| batteryGroup2CycleLogDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryCycleLogLastDaysTable | 1.3.6.1.4.1.12148.10.15.20.3.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryGroup2CycleLogDaysValue OBJECT-TYPE Number of discharge cycles logged every day. | 1.3.6.1.4.1.12148.10.15.20.3.1.2 | Integer32 | read-only | current |
| batteryGroup2CycleLogWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in weeky battery discharge cycle log. | 1.3.6.1.4.1.12148.10.15.20.4 | Integer32 (0..52) | read-only | current |
| batteryGroup2CycleLogWeeksTable OBJECT-TYPE This table contains weekly battery discharge cycle log. | 1.3.6.1.4.1.12148.10.15.20.5 | not-accessible | current | |
| batteryGroup2CycleLogWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.20.5.1 | not-accessible | current | |
| batteryGroup2CycleLogWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable | 1.3.6.1.4.1.12148.10.15.20.5.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryGroup2CycleLogWeeksValue OBJECT-TYPE Number of discharge cycles logged every week. | 1.3.6.1.4.1.12148.10.15.20.5.1.2 | Integer32 | read-only | current |
| batteryGroup2CycleLogMonthsNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in monthly battery discharge cycle log. | 1.3.6.1.4.1.12148.10.15.20.6 | Integer32 (0..52) | read-only | current |
| batteryGroup2CycleLogMonthsTable OBJECT-TYPE This table contains monthly battery discharge cycle log. | 1.3.6.1.4.1.12148.10.15.20.7 | not-accessible | current | |
| batteryGroup2CycleLogMonthsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.15.20.7.1 | not-accessible | current | |
| batteryGroup2CycleLogMonthsIndex OBJECT-TYPE Index used for navigating the rows 1..52 of batteryCycleLogLastMonthTable | 1.3.6.1.4.1.12148.10.15.20.7.1.1 | Integer32 (1..52) | not-accessible | current |
| batteryGroup2CycleLogMonthsValue OBJECT-TYPE Number of discharge cycles logged every month. | 1.3.6.1.4.1.12148.10.15.20.7.1.2 | Integer32 | read-only | current |
| batteryGroup2Equalize OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.21 | |||
| batteryGroup2EqualizeVoltage OBJECT-TYPE The Voltage at which the DC System equalize charges the batteries. | 1.3.6.1.4.1.12148.10.15.21.1 | Integer32 (870..60418) | read-write | current |
| batteryGroup2EqualizeCommand OBJECT-TYPE This pushbutton will start or stop a manual battery equalize if the system allows it. | 1.3.6.1.4.1.12148.10.15.21.2 | INTEGER {pushbutton(0), startequalize(1), stopequalize(2)} | read-write | current |
| batteryGroup2EqualizeCurrentThreshold OBJECT-TYPE The equalizing will terminate when the charge current drops below the EqualizeCurrentThreshold limit. | 1.3.6.1.4.1.12148.10.15.21.3 | Integer32 | read-write | current |
| batteryGroup2EqualizeManualMaxDuration OBJECT-TYPE A protection against overcharging. When running manual equalize, the boosting will always terminate at this point. | 1.3.6.1.4.1.12148.10.15.21.4 | Integer32 (0..1440) | read-write | current |
| batteryGroup2AhCharged OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.22 | |||
| batteryGroup2AhChargedStatus OBJECT-TYPE The status of the battery ah charged monitor. | 1.3.6.1.4.1.12148.10.15.22.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2AhChargedDescription OBJECT-TYPE A textual description of the battery ah charged monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.15.22.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2AhChargedTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.15.22.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2AhChargedAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.22.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2AhChargedValue OBJECT-TYPE The calculated battery ah (x100) charged value. | 1.3.6.1.4.1.12148.10.15.22.5 | Integer32 | read-only | current |
| batteryGroup2AhChargedMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.15.22.6 | Integer32 | read-write | current |
| batteryGroup2AhChargedMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.15.22.7 | Integer32 | read-write | current |
| batteryGroup2AhDischarged OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.15.23 | |||
| batteryGroup2AhDischargedStatus OBJECT-TYPE The status of the battery ah discharged monitor. | 1.3.6.1.4.1.12148.10.15.23.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| batteryGroup2AhDischargedDescription OBJECT-TYPE A textual description of the battery ah discharged monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.15.23.2 | DisplayString (SIZE(0..16)) | read-write | current |
| batteryGroup2AhDischargedTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.15.23.3 | Counter32 | accessible-for-notify | current |
| batteryGroup2AhDischargedAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.15.23.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| batteryGroup2AhDischargedValue OBJECT-TYPE The calculated battery ah (x100) discharged value. | 1.3.6.1.4.1.12148.10.15.23.5 | Integer32 | read-only | current |
| batteryGroup2AhDischargedMinorHighLevel OBJECT-TYPE The minor high alarm limit | 1.3.6.1.4.1.12148.10.15.23.6 | Integer32 | read-write | current |
| batteryGroup2AhDischargedMajorHighLevel OBJECT-TYPE The major high alarm limit | 1.3.6.1.4.1.12148.10.15.23.7 | Integer32 | read-write | current |
| inverters OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.16 | |||
| invertersStatus OBJECT-TYPE The overall status of inverter subsystem. | 1.3.6.1.4.1.12148.10.16.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| invertersCurrent OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.16.2 | |||
| invertersCurrentStatus OBJECT-TYPE The status of the measured total inverter current. | 1.3.6.1.4.1.12148.10.16.2.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| invertersCurrentDescription OBJECT-TYPE A textual description of the total inverter current monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.16.2.2 | DisplayString (SIZE(0..16)) | read-write | current |
| invertersCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.16.2.3 | Counter32 | accessible-for-notify | current |
| invertersCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.16.2.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| invertersCurrentValue OBJECT-TYPE The value of the measured total inverter current. | 1.3.6.1.4.1.12148.10.16.2.5 | Integer32 | read-only | current |
| invertersCurrentMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.16.2.6 | Integer32 | read-write | current |
| invertersCurrentMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.16.2.7 | Integer32 | read-write | current |
| invertersCapacity OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.16.3 | |||
| invertersCapacityStatus OBJECT-TYPE The status of the measured used inverter capacity. | 1.3.6.1.4.1.12148.10.16.3.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| invertersCapacityDescription OBJECT-TYPE A textual description of the used inverter capacity monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.16.3.2 | DisplayString (SIZE(0..16)) | read-write | current |
| invertersCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.16.3.3 | Counter32 | accessible-for-notify | current |
| invertersCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.16.3.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| invertersCapacityValue OBJECT-TYPE The used inverter capacity value presented in percentage of the total installed inverter capacity. | 1.3.6.1.4.1.12148.10.16.3.5 | Integer32 | read-only | current |
| invertersCapacityMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.16.3.6 | Integer32 | read-write | current |
| invertersCapacityMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.16.3.7 | Integer32 | read-write | current |
| invertersError OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.16.4 | |||
| invertersErrorStatus OBJECT-TYPE This status value shows if the number of failed units is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.16.4.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| invertersErrorDescription OBJECT-TYPE A textual description of the inverter error monitor. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.16.4.2 | DisplayString (SIZE(0..16)) | read-write | current |
| invertersErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.16.4.3 | Counter32 | accessible-for-notify | current |
| invertersErrorEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.16.4.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| invertersErrorValue OBJECT-TYPE The number of failed inverters. | 1.3.6.1.4.1.12148.10.16.4.5 | Integer32 | read-only | current |
| invertersErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.16.4.6 | Integer32 | read-write | current |
| invertersErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.16.4.7 | Integer32 | read-write | current |
| invertersNumberOfInverters OBJECT-TYPE Number of installed inverters. | 1.3.6.1.4.1.12148.10.16.5 | Integer32 (0..100) | read-write | current |
| inverterTable OBJECT-TYPE This table shows the information of each inverter installed in the system. | 1.3.6.1.4.1.12148.10.16.6 | not-accessible | current | |
| inverterEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.6.1 | not-accessible | current | |
| inverterIndex OBJECT-TYPE Index used for navigating the rows 1..100 of inverterTable | 1.3.6.1.4.1.12148.10.16.6.1.1 | Integer32 (1..100) | not-accessible | current |
| inverterStatus OBJECT-TYPE The overall status of inverter. | 1.3.6.1.4.1.12148.10.16.6.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| inverterOutputCurrentValue OBJECT-TYPE The output current value of inverter. | 1.3.6.1.4.1.12148.10.16.6.1.3 | Integer32 | read-only | current |
| inverterOutputVoltageValue OBJECT-TYPE The output voltage value of inverter. | 1.3.6.1.4.1.12148.10.16.6.1.4 | Integer32 | read-only | current |
| inverterType OBJECT-TYPE Type of inverter | 1.3.6.1.4.1.12148.10.16.6.1.5 | DisplayString (SIZE(0..27)) | read-only | current |
| inverterHwPartNumber OBJECT-TYPE Hardware part number of inverter | 1.3.6.1.4.1.12148.10.16.6.1.6 | DisplayString (SIZE(0..12)) | read-only | current |
| inverterHwVersion OBJECT-TYPE Hardware version number of inverter | 1.3.6.1.4.1.12148.10.16.6.1.7 | DisplayString (SIZE(0..6)) | read-only | current |
| inverterSwPartNumber OBJECT-TYPE Part number of secondary software in inverter | 1.3.6.1.4.1.12148.10.16.6.1.8 | DisplayString (SIZE(0..12)) | read-only | current |
| inverterSwVersion OBJECT-TYPE Version number of secondary software in inverter | 1.3.6.1.4.1.12148.10.16.6.1.9 | DisplayString (SIZE(0..6)) | read-only | current |
| inverterOutputFrequencyValue OBJECT-TYPE The output frequency value of inverter. | 1.3.6.1.4.1.12148.10.16.6.1.10 | Integer32 | read-only | current |
| inverterOutputPowerValue OBJECT-TYPE The output power value of inverter. | 1.3.6.1.4.1.12148.10.16.6.1.11 | Integer32 | read-only | current |
| inverterOutputReactivePowerValue OBJECT-TYPE The output reactive power value of inverter. | 1.3.6.1.4.1.12148.10.16.6.1.12 | Integer32 | read-only | current |
| invertersNumberOfGroups OBJECT-TYPE Number of inverter groups | 1.3.6.1.4.1.12148.10.16.7 | Integer32 | read-only | current |
| inverterGroupsTable OBJECT-TYPE This table contains status and the number of installed inverters of each inverter groups. | 1.3.6.1.4.1.12148.10.16.8 | not-accessible | current | |
| inverterGroupsEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.8.1 | not-accessible | current | |
| inverterGroupIndex OBJECT-TYPE Index used for navigating the rows 1..10 of inverterGroupsTable | 1.3.6.1.4.1.12148.10.16.8.1.1 | Integer32 (1..10) | not-accessible | current |
| inverterGroupStatus OBJECT-TYPE The status of each inverter group. | 1.3.6.1.4.1.12148.10.16.8.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| inverterGroupNumberOfInverters OBJECT-TYPE Number of installed inverters in each inverter groups | 1.3.6.1.4.1.12148.10.16.8.1.3 | Integer32 (0..100) | read-write | current |
| inverterGroupCurrentTable OBJECT-TYPE This table contains information about the total inverter current of each inverter groups, which is calculated by summing up current from each inverter in a inverter group. | 1.3.6.1.4.1.12148.10.16.9 | not-accessible | current | |
| inverterGroupCurrentEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.9.1 | not-accessible | current | |
| inverterGroupCurrentStatus OBJECT-TYPE The status of the measured total inverter current of the inverter group | 1.3.6.1.4.1.12148.10.16.9.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| inverterGroupCurrentDescription OBJECT-TYPE A textual description of the total inverter current monitor of a inverter group. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.16.9.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| inverterGroupCurrentTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.16.9.1.3 | Integer32 | accessible-for-notify | current |
| inverterGroupCurrentAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.16.9.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| inverterGroupCurrentValue OBJECT-TYPE The value of the measured total inverter current of each inverter group. | 1.3.6.1.4.1.12148.10.16.9.1.5 | Integer32 | read-only | current |
| inverterGroupCurrentMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.16.9.1.6 | Integer32 | read-write | current |
| inverterGroupCurrentMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.16.9.1.7 | Integer32 | read-write | current |
| inverterGroupCapacityTable OBJECT-TYPE This table contains information about the used inverter capacity of each inverter group. | 1.3.6.1.4.1.12148.10.16.10 | not-accessible | current | |
| inverterGroupCapacityEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.10.1 | not-accessible | current | |
| inverterGroupCapacityStatus OBJECT-TYPE The status of the measured used inverter capacity of each inverter group | 1.3.6.1.4.1.12148.10.16.10.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| inverterGroupCapacityDescription OBJECT-TYPE A textual description of the used inverter capacity monitor of each inverter group. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.16.10.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| inverterGroupCapacityTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.16.10.1.3 | Integer32 | accessible-for-notify | current |
| inverterGroupCapacityAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.16.10.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| inverterGroupCapacityValue OBJECT-TYPE The used inverter capacity value presented in percentage of the total installed inverter capacity of each inverter group. | 1.3.6.1.4.1.12148.10.16.10.1.5 | Integer32 | read-only | current |
| inverterGroupCapacityMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.16.10.1.6 | Integer32 | read-write | current |
| inverterGroupCapacityMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.16.10.1.7 | Integer32 | read-write | current |
| inverterGroupErrorTable OBJECT-TYPE This table contains information about the inverter error monitor of each inverter group. | 1.3.6.1.4.1.12148.10.16.11 | not-accessible | current | |
| inverterGroupErrorEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.11.1 | not-accessible | current | |
| inverterGroupErrorStatus OBJECT-TYPE This status value shows if the number of failed units is higher than the defined alarm level. | 1.3.6.1.4.1.12148.10.16.11.1.1 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| inverterGroupErrorDescription OBJECT-TYPE A textual description of the inverter error monitor of each inverter group. This is stored in the system controller and can be changed by the user | 1.3.6.1.4.1.12148.10.16.11.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| inverterGroupErrorTrapRepeatCounter OBJECT-TYPE The number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero when the alarm condition is reset and the alarm goes off | 1.3.6.1.4.1.12148.10.16.11.1.3 | Integer32 | accessible-for-notify | current |
| inverterGroupErrorAlarmEnable OBJECT-TYPE This value once enabled, the alarm condition of the monitor will be reported. | 1.3.6.1.4.1.12148.10.16.11.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| inverterGroupErrorValue OBJECT-TYPE The number of failed inverters of each inverter group. | 1.3.6.1.4.1.12148.10.16.11.1.5 | Integer32 | read-only | current |
| inverterGroupErrorMajorAlarmLevel OBJECT-TYPE The major alarm limit | 1.3.6.1.4.1.12148.10.16.11.1.6 | Integer32 | read-write | current |
| inverterGroupErrorMinorAlarmLevel OBJECT-TYPE The minor alarm limit | 1.3.6.1.4.1.12148.10.16.11.1.7 | Integer32 | read-write | current |
| inverterGroupInverterTable OBJECT-TYPE This table shows the information of each inverter installed in each of the inverter group in the system. | 1.3.6.1.4.1.12148.10.16.12 | not-accessible | current | |
| inverterGroupInverterEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.12.1 | not-accessible | current | |
| inverterGroupInverterIndex OBJECT-TYPE Index used for navigating the rows 1..100 of inverterGroupinverterTable | 1.3.6.1.4.1.12148.10.16.12.1.1 | Integer32 (1..100) | not-accessible | current |
| inverterGroupInverterStatus OBJECT-TYPE The overall status of inverter. | 1.3.6.1.4.1.12148.10.16.12.1.2 | INTEGER {error(0), normal(1), minorAlarm(2), majorAlarm(3), disabled(4), disconnected(5), notPresent(6), minorAndMajor(7), majorLow(8), minorLow(9), majorHigh(10), minorHigh(11), event(12), valueVolt(13), valueAmp(14), valueTemp(15), valueUnit(16), valuePerCent(17), critical(18), warning(19)} | read-only | current |
| inverterGroupInverterOutputCurrentValue OBJECT-TYPE The output current value of inverter. | 1.3.6.1.4.1.12148.10.16.12.1.3 | Integer32 | read-only | current |
| inverterGroupInverterOutputVoltageValue OBJECT-TYPE The output voltage value of inverter. | 1.3.6.1.4.1.12148.10.16.12.1.4 | Integer32 | read-only | current |
| inverterGroupInverterType OBJECT-TYPE Type of inverter | 1.3.6.1.4.1.12148.10.16.12.1.5 | DisplayString (SIZE(0..27)) | read-only | current |
| inverterGroupInverterHwPartNumber OBJECT-TYPE Hardware part number of inverter | 1.3.6.1.4.1.12148.10.16.12.1.6 | DisplayString (SIZE(0..12)) | read-only | current |
| inverterGroupInverterHwVersion OBJECT-TYPE Hardware version number of inverter | 1.3.6.1.4.1.12148.10.16.12.1.7 | DisplayString (SIZE(0..6)) | read-only | current |
| inverterGroupInverterSwPartNumber OBJECT-TYPE Part number of secondary software in inverter | 1.3.6.1.4.1.12148.10.16.12.1.8 | DisplayString (SIZE(0..12)) | read-only | current |
| inverterGroupInverterSwVersion OBJECT-TYPE Version number of secondary software in inverter | 1.3.6.1.4.1.12148.10.16.12.1.9 | DisplayString (SIZE(0..6)) | read-only | current |
| inverterGroupInverterOutputFrequencyValue OBJECT-TYPE The output frequency value of inverter. | 1.3.6.1.4.1.12148.10.16.12.1.10 | Integer32 | read-only | current |
| inverterGroupInverterOutputPowerValue OBJECT-TYPE The output power value of inverter. | 1.3.6.1.4.1.12148.10.16.12.1.11 | Integer32 | read-only | current |
| inverterGroupInverterOutputReactivePowerValue OBJECT-TYPE The output reactive power value of inverter. | 1.3.6.1.4.1.12148.10.16.12.1.12 | Integer32 | read-only | current |
| invertersEnergyLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.16.13 | |||
| invertersEnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered from inverters. | 1.3.6.1.4.1.12148.10.16.13.1 | Integer32 | read-only | current |
| invertersEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter hourly energy log. | 1.3.6.1.4.1.12148.10.16.13.2 | Integer32 (0..52) | read-only | current |
| invertersEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly energy log of inverters. | 1.3.6.1.4.1.12148.10.16.13.3 | not-accessible | current | |
| invertersEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.13.3.1 | not-accessible | current | |
| invertersEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of invertersEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.16.13.3.1.1 | Integer32 (1..52) | not-accessible | current |
| invertersEnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.16.13.3.1.2 | Integer32 | read-only | current |
| invertersEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter daily energy log. | 1.3.6.1.4.1.12148.10.16.13.4 | Integer32 (0..52) | read-only | current |
| invertersEnergyLogLastDaysTable OBJECT-TYPE This table contains daily energy log of inverters. | 1.3.6.1.4.1.12148.10.16.13.5 | not-accessible | current | |
| invertersEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.13.5.1 | not-accessible | current | |
| invertersEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of invertersEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.16.13.5.1.1 | Integer32 (1..52) | not-accessible | current |
| invertersEnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day. | 1.3.6.1.4.1.12148.10.16.13.5.1.2 | Integer32 | read-only | current |
| invertersEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter weekly energy log. | 1.3.6.1.4.1.12148.10.16.13.6 | Integer32 (0..52) | read-only | current |
| invertersEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly energy log of inverters. | 1.3.6.1.4.1.12148.10.16.13.7 | not-accessible | current | |
| invertersEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.13.7.1 | not-accessible | current | |
| invertersEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of invertersEnergyLogLastWeekTable | 1.3.6.1.4.1.12148.10.16.13.7.1.1 | Integer32 (1..52) | not-accessible | current |
| invertersEnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.16.13.7.1.2 | Integer32 | read-only | current |
| inverterGroupEnergyLogTable OBJECT-TYPE This branch contains information about inverters' energy logs of each inverter group. | 1.3.6.1.4.1.12148.10.16.14 | not-accessible | current | |
| inverterGroupEnergyLogEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.14.1 | not-accessible | current | |
| inverterGroupEnergyLogAccumulated OBJECT-TYPE This is the accumulated energy delivered from inverters of each inverter group. | 1.3.6.1.4.1.12148.10.16.14.1.1 | Integer32 | read-only | current |
| inverterGroupEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter group hourly energy log. | 1.3.6.1.4.1.12148.10.16.14.1.2 | Integer32 | read-only | current |
| inverterGroupEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter group daily energy log. | 1.3.6.1.4.1.12148.10.16.14.1.3 | Integer32 | read-only | current |
| inverterGroupEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter group weekly energy log. | 1.3.6.1.4.1.12148.10.16.14.1.4 | Integer32 | read-only | current |
| inverterGroupEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly energy log of each inverter group | 1.3.6.1.4.1.12148.10.16.15 | not-accessible | current | |
| inverterGroupEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.15.1 | not-accessible | current | |
| inverterGroupEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of inverterGroupEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.16.15.1.1 | Integer32 (1..52) | not-accessible | current |
| inverterGroupEnergyLogLastHoursValue OBJECT-TYPE Energy value logged every hour. | 1.3.6.1.4.1.12148.10.16.15.1.2 | Integer32 | read-only | current |
| inverterGroupEnergyLogLastDaysTable OBJECT-TYPE This table contains daily energy log of each inverter group | 1.3.6.1.4.1.12148.10.16.16 | not-accessible | current | |
| inverterGroupEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.16.1 | not-accessible | current | |
| inverterGroupEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of inverterGroupEnergyLogLasDaysTable | 1.3.6.1.4.1.12148.10.16.16.1.1 | Integer32 (1..52) | not-accessible | current |
| inverterGroupEnergyLogLastDaysValue OBJECT-TYPE Energy value logged every day. | 1.3.6.1.4.1.12148.10.16.16.1.2 | Integer32 | read-only | current |
| inverterGroupEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly energy log of each inverter group | 1.3.6.1.4.1.12148.10.16.17 | not-accessible | current | |
| inverterGroupEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.17.1 | not-accessible | current | |
| inverterGroupEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of inverterGroupEnergyLogLastWeeksTable | 1.3.6.1.4.1.12148.10.16.17.1.1 | Integer32 (1..52) | not-accessible | current |
| inverterGroupEnergyLogLastWeeksValue OBJECT-TYPE Energy value logged every week. | 1.3.6.1.4.1.12148.10.16.17.1.2 | Integer32 | read-only | current |
| invertersReactiveEnergyLog OBJECT-IDENTITY | 1.3.6.1.4.1.12148.10.16.18 | |||
| invertersReactiveEnergyLogAccumulated OBJECT-TYPE This is the accumulated reactive energy delivered from inverters. | 1.3.6.1.4.1.12148.10.16.18.1 | Integer32 | read-only | current |
| invertersReactiveEnergyLogLastHoursNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter hourly reactive energy log. | 1.3.6.1.4.1.12148.10.16.18.2 | Integer32 (0..52) | read-only | current |
| invertersReactiveEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly reactive energy log of inverters. | 1.3.6.1.4.1.12148.10.16.18.3 | not-accessible | current | |
| invertersReactiveEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.18.3.1 | not-accessible | current | |
| invertersReactiveEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of invertersReactiveEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.16.18.3.1.1 | Integer32 (1..52) | not-accessible | current |
| invertersReactiveEnergyLogLastHoursValue OBJECT-TYPE Reactive energy value logged every hour. | 1.3.6.1.4.1.12148.10.16.18.3.1.2 | Integer32 | read-only | current |
| invertersReactiveEnergyLogLastDaysNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter daily reactive energy log. | 1.3.6.1.4.1.12148.10.16.18.4 | Integer32 (0..52) | read-only | current |
| invertersReactiveEnergyLogLastDaysTable OBJECT-TYPE This table contains daily reactive energy log of inverters. | 1.3.6.1.4.1.12148.10.16.18.5 | not-accessible | current | |
| invertersReactiveEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.18.5.1 | not-accessible | current | |
| invertersReactiveEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of invertersReactiveEnergyLogLastDaysTable | 1.3.6.1.4.1.12148.10.16.18.5.1.1 | Integer32 (1..52) | not-accessible | current |
| invertersReactiveEnergyLogLastDaysValue OBJECT-TYPE Reactive energy value logged every day. | 1.3.6.1.4.1.12148.10.16.18.5.1.2 | Integer32 | read-only | current |
| invertersReactiveEnergyLogLastWeeksNumberOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter weekly reactive energy log. | 1.3.6.1.4.1.12148.10.16.18.6 | Integer32 (0..52) | read-only | current |
| invertersReactiveEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly reactive energy log of inverters. | 1.3.6.1.4.1.12148.10.16.18.7 | not-accessible | current | |
| invertersReactiveEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.18.7.1 | not-accessible | current | |
| invertersReactiveEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of invertersReactiveEnergyLogLastWeekTable | 1.3.6.1.4.1.12148.10.16.18.7.1.1 | Integer32 (1..52) | not-accessible | current |
| invertersReactiveEnergyLogLastWeeksValue OBJECT-TYPE Reactive energy value logged every week. | 1.3.6.1.4.1.12148.10.16.18.7.1.2 | Integer32 | read-only | current |
| inverterGroupReactiveEnergyLogTable OBJECT-TYPE This branch contains information about inverters' reactive energy logs of each inverter group. | 1.3.6.1.4.1.12148.10.16.19 | not-accessible | current | |
| inverterGroupReactiveEnergyLogEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.19.1 | not-accessible | current | |
| inverterGroupReactiveEnergyLogAccumulated OBJECT-TYPE This is the accumulated reactive energy delivered from inverters of each inverter group. | 1.3.6.1.4.1.12148.10.16.19.1.1 | Integer32 | read-only | current |
| inverterGroupReactiveEnergyLogLastHoursNoOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter group hourly reactive energy log. | 1.3.6.1.4.1.12148.10.16.19.1.2 | Integer32 | read-only | current |
| inverterGroupReactiveEnergyLogLastDaysNoOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter group daily reactive energy log. | 1.3.6.1.4.1.12148.10.16.19.1.3 | Integer32 | read-only | current |
| inverterGroupReactiveEnergyLogLastWeeksNoOfEntries OBJECT-TYPE This is the maximal number of entries stored in inverter group weekly reactive energy log. | 1.3.6.1.4.1.12148.10.16.19.1.4 | Integer32 | read-only | current |
| inverterGroupReactiveEnergyLogLastHoursTable OBJECT-TYPE This table contains hourly reactive energy log of each inverter group | 1.3.6.1.4.1.12148.10.16.20 | not-accessible | current | |
| inverterGroupReactiveEnergyLogLastHoursEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.20.1 | not-accessible | current | |
| inverterGroupReactiveEnergyLogLastHoursIndex OBJECT-TYPE Index used for navigating the rows 1..52 of inverterGroupReactiveEnergyLogLastHoursTable | 1.3.6.1.4.1.12148.10.16.20.1.1 | Integer32 (1..52) | not-accessible | current |
| inverterGroupReactiveEnergyLogLastHoursValue OBJECT-TYPE Reactive energy value logged every hour. | 1.3.6.1.4.1.12148.10.16.20.1.2 | Integer32 | read-only | current |
| inverterGroupReactiveEnergyLogLastDaysTable OBJECT-TYPE This table contains daily reactive energy log of each inverter group | 1.3.6.1.4.1.12148.10.16.21 | not-accessible | current | |
| inverterGroupReactiveEnergyLogLastDaysEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.21.1 | not-accessible | current | |
| inverterGroupReactiveEnergyLogLastDaysIndex OBJECT-TYPE Index used for navigating the rows 1..52 of inverterGroupReactiveEnergyLogLasDaysTable | 1.3.6.1.4.1.12148.10.16.21.1.1 | Integer32 (1..52) | not-accessible | current |
| inverterGroupReactiveEnergyLogLastDaysValue OBJECT-TYPE Reactive energy value logged every day. | 1.3.6.1.4.1.12148.10.16.21.1.2 | Integer32 | read-only | current |
| inverterGroupReactiveEnergyLogLastWeeksTable OBJECT-TYPE This table contains weekly reactive energy log of each inverter group | 1.3.6.1.4.1.12148.10.16.22 | not-accessible | current | |
| inverterGroupReactiveEnergyLogLastWeeksEntry OBJECT-TYPE | 1.3.6.1.4.1.12148.10.16.22.1 | not-accessible | current | |
| inverterGroupReactiveEnergyLogLastWeeksIndex OBJECT-TYPE Index used for navigating the rows 1..52 of inverterGroupReactiveEnergyLogLastWeeksTable | 1.3.6.1.4.1.12148.10.16.22.1.1 | Integer32 (1..52) | not-accessible | current |
| inverterGroupReactiveEnergyLogLastWeeksValue OBJECT-TYPE Reactive energy value logged every week. | 1.3.6.1.4.1.12148.10.16.22.1.2 | Integer32 | read-only | current |
Notifications
| Name | OID | Status |
|---|---|---|
| alarmPowerSystemTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the power system. | 1.3.6.1.4.1.12148.10.1.2.1 | current |
| alarmBatteryTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the battery subsystem. | 1.3.6.1.4.1.12148.10.1.2.2 | current |
| alarmLoadGroupTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the Load subsystem. | 1.3.6.1.4.1.12148.10.1.2.3 | current |
| alarmMainsTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the Mains subsystem. | 1.3.6.1.4.1.12148.10.1.2.4 | current |
| alarmRectifierTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the Rectifier subsystem. | 1.3.6.1.4.1.12148.10.1.2.5 | current |
| alarmControlSystemTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the Control-system subsystem. | 1.3.6.1.4.1.12148.10.1.2.6 | current |
| alarmDcDcTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the DCDC converter subsystem. | 1.3.6.1.4.1.12148.10.1.2.7 | current |
| alarmInputsTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the Inputs subsystem. | 1.3.6.1.4.1.12148.10.1.2.8 | current |
| alarmOutputsTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the Outputs subsystem. | 1.3.6.1.4.1.12148.10.1.2.9 | current |
| alarmGeneratorTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the Generator subsystem. | 1.3.6.1.4.1.12148.10.1.2.10 | current |
| alarmSolarChargerTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the SolarCharger subsystem. | 1.3.6.1.4.1.12148.10.1.2.11 | current |
| alarmWindChargerTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the WindCharger subsystem. | 1.3.6.1.4.1.12148.10.1.2.12 | current |
| infoHeartBeatTrap NOTIFICATION-TYPE When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up. | 1.3.6.1.4.1.12148.10.1.2.13 | current |
| alarmInverterTrap NOTIFICATION-TYPE This Trap is sent when an alarm condition occurs in the Rectifier subsystem. | 1.3.6.1.4.1.12148.10.1.2.14 | current |
Conformance
| Name | OID | Status |
|---|---|---|
| powerSystemTrapsGroup NOTIFICATION-GROUP The powerSystem Trap goup. Entry point for the trap list. | 1.3.6.1.4.1.12148.10.1.3 | current |