WebGraph-Thermo-Hygrometer-US-MIB
- Registered at
- 1.3.6.1.4.1.5040.1.2.42
- Namespace
- wut
- Source file
WebGraph-Thermo-Hygrometer-US-MIB- Digest
sha256:28a9f566b4dfc4c0c56b188af3c86b79f463be591e126f5bbead6a549cd7253f
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
SNMPv2-CONF SNMPv2-SMI SNMPv2-TC WebGraph-Thermo-Hygrometer-US-MIB
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| wut OBJECT-IDENTITY | 1.3.6.1.4.1.5040 | |||
| wtComServer OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1 | |||
| wtWebio OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2 | |||
| wtWebGraphThermoHygro OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42 | |||
| wtWebGraphThermoHygroTemp OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.1 | |||
| wtWebGraphThermoHygroSensors OBJECT-TYPE Number of sensors | 1.3.6.1.4.1.5040.1.2.42.1.1 | INTEGER (1..2) | read-only | mandatory |
| wtWebGraphThermoHygroSensorTable OBJECT-TYPE List of sensors. | 1.3.6.1.4.1.5040.1.2.42.1.2 | not-accessible | mandatory | |
| wtWebGraphThermoHygroSensorEntry OBJECT-TYPE List of sensor numbers. | 1.3.6.1.4.1.5040.1.2.42.1.2.1 | not-accessible | mandatory | |
| wtWebGraphThermoHygroSensorNo OBJECT-TYPE Sensor number. | 1.3.6.1.4.1.5040.1.2.42.1.2.1.1 | INTEGER (1..2) | read-only | mandatory |
| wtWebGraphThermoHygroTempValueTable OBJECT-TYPE List of measurement values corresponding to the channel numbers. | 1.3.6.1.4.1.5040.1.2.42.1.3 | not-accessible | mandatory | |
| wtWebGraphThermoHygroTempValueEntry OBJECT-TYPE Measurement values of the sensors. | 1.3.6.1.4.1.5040.1.2.42.1.3.1 | not-accessible | mandatory | |
| wtWebGraphThermoHygroTempValue OBJECT-TYPE Measurement value of the sensor, ASCII, 5 characters in length. | 1.3.6.1.4.1.5040.1.2.42.1.3.1.1 | OCTET STRING (SIZE(5)) | read-only | mandatory |
| wtWebGraphThermoHygroBinaryTempValueTable OBJECT-TYPE List of binary measurement values corresponding to the channel numbers. | 1.3.6.1.4.1.5040.1.2.42.1.4 | not-accessible | mandatory | |
| wtWebGraphThermoHygroBinaryTempValueEntry OBJECT-TYPE Binary measurement values of the sensors. | 1.3.6.1.4.1.5040.1.2.42.1.4.1 | not-accessible | mandatory | |
| wtWebGraphThermoHygroBinaryTempValue OBJECT-TYPE Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent, signed number, 0x4FFF6 indicates an invalid measured value. | 1.3.6.1.4.1.5040.1.2.42.1.4.1.1 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroTempValuePktTable OBJECT-TYPE List of measurement values corresponding to the channel numbers. | 1.3.6.1.4.1.5040.1.2.42.1.8 | not-accessible | mandatory | |
| wtWebGraphThermoHygroTempValuePktEntry OBJECT-TYPE Measurement values of the sensors. | 1.3.6.1.4.1.5040.1.2.42.1.8.1 | not-accessible | mandatory | |
| wtWebGraphThermoHygroTempValuePkt OBJECT-TYPE Measurement value of the sensor, ASCII, 5 characters in length, delimeter is decimal point. | 1.3.6.1.4.1.5040.1.2.42.1.8.1.1 | OCTET STRING (SIZE(5)) | read-only | mandatory |
| wtWebGraphThermoHygroSessCntrl OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.2 | |||
| wtWebGraphThermoHygroSessCntrlPassword OBJECT-TYPE Entering this password opens a session which is ended by writing a 1 to wtWebGraphThermoHygroSessCntrlLogout. When read this variable provides a string of length zero. | 1.3.6.1.4.1.5040.1.2.42.2.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSessCntrlConfigMode OBJECT-TYPE When the device is in SNMP configuration mode, the value 1 is returned, otherwise 0. If the read value is 0 even though the password was written, the device is already in config mode and the variables can only be read. | 1.3.6.1.4.1.5040.1.2.42.2.2 | INTEGER {wtWebGraphThermoHygroSessCntrl-NoSession(0), wtWebGraphThermoHygroSessCntrl-Session(1)} | read-only | mandatory |
| wtWebGraphThermoHygroSessCntrlLogout OBJECT-TYPE If the device is in configuration mode and the session was opened by this SNMP Manager, writing a 1 to this variable will end the session and all parameters are stored. Writing a 2 discards all entries again. When read this variable provides the value 0. | 1.3.6.1.4.1.5040.1.2.42.2.3 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroSessCntrlAdminPassword OBJECT-TYPE This password protects access to the variables with administrator rights. It can only be changed by the administrator. If no password was assigned, the valid password is public. | 1.3.6.1.4.1.5040.1.2.42.2.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSessCntrlConfigPassword OBJECT-TYPE This password protects access to the variables with configurator rights. It can be changed by the administrator and by the configurator. If no password was assigned, the valid password is public. When read this variable provides a null-pointer. | 1.3.6.1.4.1.5040.1.2.42.2.5 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroConfig OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3 | |||
| wtWebGraphThermoHygroDevice OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1 | |||
| wtWebGraphThermoHygroText OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.1 | |||
| wtWebGraphThermoHygroDeviceName OBJECT-TYPE Name of the Webio, which is user definable. | 1.3.6.1.4.1.5040.1.2.42.3.1.1.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroDeviceText OBJECT-TYPE Description of the Webio, which is user definable. | 1.3.6.1.4.1.5040.1.2.42.3.1.1.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroDeviceLocation OBJECT-TYPE Description of the location of the Webio, which is user definable. | 1.3.6.1.4.1.5040.1.2.42.3.1.1.3 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroDeviceContact OBJECT-TYPE Contact address of the system operator of the Webio, which is user definable. | 1.3.6.1.4.1.5040.1.2.42.3.1.1.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroTimeDate OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.2 | |||
| wtWebGraphThermoHygroTimeZone OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1 | |||
| wtWebGraphThermoHygroTzOffsetHrs OBJECT-TYPE Offset hours for the time zone (winter time) with respect to UTC. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.1 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroTzOffsetMin OBJECT-TYPE Offset minutes for the time zone (winter time) with respect to UTC. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.2 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroTzEnable OBJECT-TYPE Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Timezone | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.3 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroStTzOffsetHrs OBJECT-TYPE Offset hours of the time zone (summer time) with respect to UTC. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.4 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroStTzOffsetMin OBJECT-TYPE Offset minutes of the time zone (summer time) with respect to UTC. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.5 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroStTzEnable OBJECT-TYPE Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Summertime | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.6 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroStTzStartMonth OBJECT-TYPE Month in which the change is made from winter time to summer time. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.7 | INTEGER {wtWebGraphThermoHygroStartMonth-January(1), wtWebGraphThermoHygroStartMonth-February(2), wtWebGraphThermoHygroStartMonth-March(3), wtWebGraphThermoHygroStartMonth-April(4), wtWebGraphThermoHygroStartMonth-May(5), wtWebGraphThermoHygroStartMonth-June(6), wtWebGraphThermoHygroStartMonth-July(7), wtWebGraphThermoHygroStartMonth-August(8), wtWebGraphThermoHygroStartMonth-September(9), wtWebGraphThermoHygroStartMonth-October(10), wtWebGraphThermoHygroStartMonth-November(11), wtWebGraphThermoHygroStartMonth-December(12)} | read-write | mandatory |
| wtWebGraphThermoHygroStTzStartMode OBJECT-TYPE Mode of the day of the week for which the change is made from winter time to summer time. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.8 | INTEGER {wtWebGraphThermoHygroStartMode-first(1), wtWebGraphThermoHygroStartMode-second(2), wtWebGraphThermoHygroStartMode-third(3), wtWebGraphThermoHygroStartMode-fourth(4), wtWebGraphThermoHygroStartMode-last(5)} | read-write | mandatory |
| wtWebGraphThermoHygroStTzStartWday OBJECT-TYPE Day of the week on which the change is made from winter time to summer time | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.9 | INTEGER {wtWebGraphThermoHygroStartWday-Sunday(1), wtWebGraphThermoHygroStartWday-Monday(2), wtWebGraphThermoHygroStartWday-Tuesday(3), wtWebGraphThermoHygroStartWday-Thursday(4), wtWebGraphThermoHygroStartWday-Wednesday(5), wtWebGraphThermoHygroStartWday-Friday(6), wtWebGraphThermoHygroStartWday-Saturday(7)} | read-write | mandatory |
| wtWebGraphThermoHygroStTzStartHrs OBJECT-TYPE Hour in which the time zone is changed from winter to summer time with respect to UTC. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.10 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroStTzStartMin OBJECT-TYPE Minute in which the time zone is changed from winter to summer time with respect to UTC. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.11 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroStTzStopMonth OBJECT-TYPE Month in which the change is made from summer time to winter time. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.12 | INTEGER {wtWebGraphThermoHygroStopMonth-January(1), wtWebGraphThermoHygroStopMonth-February(2), wtWebGraphThermoHygroStopMonth-March(3), wtWebGraphThermoHygroStopMonth-April(4), wtWebGraphThermoHygroStopMonth-May(5), wtWebGraphThermoHygroStopMonth-June(6), wtWebGraphThermoHygroStopMonth-July(7), wtWebGraphThermoHygroStopMonth-August(8), wtWebGraphThermoHygroStopMonth-September(9), wtWebGraphThermoHygroStopMonth-October(10), wtWebGraphThermoHygroStopMonth-November(11), wtWebGraphThermoHygroStopMonth-December(12)} | read-write | mandatory |
| wtWebGraphThermoHygroStTzStopMode OBJECT-TYPE Mode of the week day on which the change is made from summer time to winter time. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.13 | INTEGER {wtWebGraphThermoHygroStopMode-first(1), wtWebGraphThermoHygroStopMode-second(2), wtWebGraphThermoHygroStopMode-third(3), wtWebGraphThermoHygroStopMode-fourth(4), wtWebGraphThermoHygroStopMode-last(5)} | read-write | mandatory |
| wtWebGraphThermoHygroStTzStopWday OBJECT-TYPE Day of the week on which the change is made from summer time to winter time. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.14 | INTEGER {wtWebGraphThermoHygroStopWday-Sunday(1), wtWebGraphThermoHygroStopWday-Monday(2), wtWebGraphThermoHygroStopWday-Tuesday(3), wtWebGraphThermoHygroStopWday-Thursday(4), wtWebGraphThermoHygroStopWday-Wednesday(5), wtWebGraphThermoHygroStopWday-Friday(6), wtWebGraphThermoHygroStopWday-Saturday(7)} | read-write | mandatory |
| wtWebGraphThermoHygroStTzStopHrs OBJECT-TYPE Hour at which the time zone is changed from summer to winter time with respect to UTC. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.15 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroStTzStopMin OBJECT-TYPE Minute at which the time zone is changed from summer to winter time with respect to UTC. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.1.16 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroTimeServer OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.2.2 | |||
| wtWebGraphThermoHygroTimeServer1 OBJECT-TYPE IP address or name of the 1st time server in ASCII | 1.3.6.1.4.1.5040.1.2.42.3.1.2.2.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroTimeServer2 OBJECT-TYPE IP address or name of the 2nd time server in ASCII | 1.3.6.1.4.1.5040.1.2.42.3.1.2.2.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroTsEnable OBJECT-TYPE Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Time Server | 1.3.6.1.4.1.5040.1.2.42.3.1.2.2.3 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroTsSyncTime OBJECT-TYPE Daily synchronisation time with the time server (hour: 0-23). | 1.3.6.1.4.1.5040.1.2.42.3.1.2.2.4 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroDeviceClock OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.2.3 | |||
| wtWebGraphThermoHygroClockHrs OBJECT-TYPE Clock hours taking into account the time zone settings. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.3.1 | INTEGER (0..23) | read-write | mandatory |
| wtWebGraphThermoHygroClockMin OBJECT-TYPE Clock minutes taking into account the time zone settings. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.3.2 | INTEGER (0..59) | read-write | mandatory |
| wtWebGraphThermoHygroClockDay OBJECT-TYPE Date: Day of the month, taking into account the time zone settings. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.3.3 | INTEGER (1..31) | read-write | mandatory |
| wtWebGraphThermoHygroClockMonth OBJECT-TYPE Date: Month, taking into account the time zone settings. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.3.4 | INTEGER {wtWebGraphThermoHygroClockMonth-January(1), wtWebGraphThermoHygroClockMonth-February(2), wtWebGraphThermoHygroClockMonth-March(3), wtWebGraphThermoHygroClockMonth-April(4), wtWebGraphThermoHygroClockMonth-May(5), wtWebGraphThermoHygroClockMonth-June(6), wtWebGraphThermoHygroClockMonth-July(7), wtWebGraphThermoHygroClockMonth-August(8), wtWebGraphThermoHygroClockMonth-September(9), wtWebGraphThermoHygroClockMonth-October(10), wtWebGraphThermoHygroClockMonth-November(11), wtWebGraphThermoHygroClockMonth-December(12)} | read-write | mandatory |
| wtWebGraphThermoHygroClockYear OBJECT-TYPE Date: Year, taking into account the time zone settings. | 1.3.6.1.4.1.5040.1.2.42.3.1.2.3.5 | INTEGER (0..65535) | read-write | mandatory |
| wtWebGraphThermoHygroBasic OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3 | |||
| wtWebGraphThermoHygroNetwork OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.1 | |||
| wtWebGraphThermoHygroIpAddress OBJECT-TYPE IP address of the Webio | 1.3.6.1.4.1.5040.1.2.42.3.1.3.1.1 | IpAddress | read-write | mandatory |
| wtWebGraphThermoHygroSubnetMask OBJECT-TYPE Subnet mask of the Webio | 1.3.6.1.4.1.5040.1.2.42.3.1.3.1.2 | IpAddress | read-write | mandatory |
| wtWebGraphThermoHygroGateway OBJECT-TYPE Gateway of the Webio | 1.3.6.1.4.1.5040.1.2.42.3.1.3.1.3 | IpAddress | read-write | mandatory |
| wtWebGraphThermoHygroDnsServer1 OBJECT-TYPE IP address of the 1st DNS server in ASCII | 1.3.6.1.4.1.5040.1.2.42.3.1.3.1.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroDnsServer2 OBJECT-TYPE IP address of the 2nd DNS server in ASCII | 1.3.6.1.4.1.5040.1.2.42.3.1.3.1.5 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAddConfig OBJECT-TYPE Additional configuration (1=ON): Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1: DHCP disable Bit 0: BOOTP disable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.1.6 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroHTTP OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.2 | |||
| wtWebGraphThermoHygroStartup OBJECT-TYPE Binary coded start page: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1: Index.htm Bit 2: Home.htm Bit 3: User.htm Only one page may be selected at a time. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.2.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroGetHeaderEnable OBJECT-TYPE If these bits are set, every answer of a short form GET question will be lead by the IP-address and name of the device and/or a HTTP header: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-6: unused Bit 1 : GET HTTP enable Bit 0 : GET Header enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.2.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroHttpPort OBJECT-TYPE Definition of the standard HTML port (Default: 80). | 1.3.6.1.4.1.5040.1.2.42.3.1.3.2.3 | INTEGER (1..65535) | read-write | mandatory |
| wtWebGraphThermoHygroMail OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.3 | |||
| wtWebGraphThermoHygroMailAdName OBJECT-TYPE Device name for mail administration. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.3.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMailReply OBJECT-TYPE Reply address for the mail server. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.3.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMailServer OBJECT-TYPE Name or IP address of the mail server. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.3.3 | OCTET STRING | read-write | mandatory |
| wtWebioAn1MailEnable OBJECT-TYPE Set this bit to enable the sending of mails: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Mail enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.3.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMailAuthentication OBJECT-TYPE Selection of the authentication modi: The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : POP3 before SMTP Bit 1 : ESMTP, authentication Bit 0 : SMTP, no authentication | 1.3.6.1.4.1.5040.1.2.42.3.1.3.3.5 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroMailAuthUser OBJECT-TYPE Name of the user to be authenticated. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.3.6 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMailAuthPassword OBJECT-TYPE Authentication password. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.3.7 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMailPop3Server OBJECT-TYPE Name or Ip-address of the POP3 Servers. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.3.8 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSNMP OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.4 | |||
| wtWebGraphThermoHygroSnmpCommunityStringRead OBJECT-TYPE Community string read only | 1.3.6.1.4.1.5040.1.2.42.3.1.3.4.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSnmpCommunityStringReadWrite OBJECT-TYPE Community string read / write | 1.3.6.1.4.1.5040.1.2.42.3.1.3.4.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSystemTrapManagerIP OBJECT-TYPE Name or IP address of the TCP server which accepts the system trap. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.4.3 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSystemTrapEnable OBJECT-TYPE Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.3.4.4 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroSnmpEnable OBJECT-TYPE Set bit 0 to enable SNMP. If disabled, the device did not respond to any SNMP requests. Bit 1 decided wether the community string of read operations is compared with the system password or not: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : SNMP enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.4.5 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSnmpCommunityStringTrap OBJECT-TYPE Community string send within traps. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.4.6 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSnmpSystemTrapManagerPort OBJECT-TYPE Port number of the TCP server which accepts the system trap. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.4.7 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroUDP OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.5 | |||
| wtWebGraphThermoHygroUdpPort OBJECT-TYPE Udp port to which the Udp queries ( short form GET requests) can be sent. This port number must be unique within the device. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.5.1 | INTEGER (1..65535) | read-write | mandatory |
| wtWebGraphThermoHygroUdpEnable OBJECT-TYPE Set this bit to enable UDP support: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : UDP enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.5.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSyslog OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.6 | |||
| wtWebGraphThermoHygroSyslogServerIP OBJECT-TYPE Name or IP address of the Syslog server, which accepts the Syslog messgaes. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.6.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroSyslogServerPort OBJECT-TYPE Portnumber of the Syslog servers, default 514. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.6.2 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroSyslogSystemMessagesEnable OBJECT-TYPE Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2: Diag Messages Bit 3-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.3.6.3 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroSyslogEnable OBJECT-TYPE Set bit 0to enable Syslog: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Syslog enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.6.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroFTP OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.7 | |||
| wtWebGraphThermoHygroFTPServerIP OBJECT-TYPE Name or IP address of the FTP server, which accepts the FTP messages. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.7.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroFTPServerControlPort OBJECT-TYPE Portnumber of the control port of the FTP server, default 21. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.7.2 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroFTPUserName OBJECT-TYPE FTP Loggin: user name. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.7.3 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroFTPPassword OBJECT-TYPE FTP Loggin: user password. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.7.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroFTPAccount OBJECT-TYPE FTP Loggin: name of account. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.7.5 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroFTPOption OBJECT-TYPE Bit 0 switches the FTP Server in Passiv-Mode, the Client controls the data connection on its own: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : PASV enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.7.6 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroFTPEnable OBJECT-TYPE Set Bit 0 to enable FTP: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : FTP enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.7.7 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSS OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8 | |||
| wtWebGraphThermoHygroRSSChannelTitle OBJECT-TYPE Name of the RSS Feed. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSSChannelLink OBJECT-TYPE Link of the RSS Feed. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSSChannelDescription OBJECT-TYPE Description of the RSS Feed. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.3 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSSChannelImage OBJECT-TYPE Link of a picture, which will be shown at the headline of the output window. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSSChannelImageTitle OBJECT-TYPE Alias Name of the picture. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.5 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSSChannelImageLink OBJECT-TYPE Link, which can be selected by clicking on the picture. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.6 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSSChannelItemTitle OBJECT-TYPE Title of the RSS Feed. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.7 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSSChannelItemLink OBJECT-TYPE Link of the RSS Feed. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.8 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSSChannelItemDescription OBJECT-TYPE Text of the RSS Feed. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.9 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRSSChannelItemQuantity OBJECT-TYPE Number of lines. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.8.10 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroLanguage OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.9 | |||
| wtWebGraphThermoHygroLanguageSelect OBJECT-TYPE Sprachauswahl: Octet 1: ungenutzt Octet 2: ungenutzt Octet 3: ungenutzt Octet 4: Bit 2-7: ungenutzt Bit 1 : Englisch Bit 0 : Deutsch | 1.3.6.1.4.1.5040.1.2.42.3.1.3.9.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMQTT OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12 | |||
| wtWebGraphThermoHygroMQTTEnable OBJECT-TYPE Bit 7 schaltet MQTT frei: Octet 1: ungenutzt Octet 2: ungenutzt Octet 3: ungenutzt Octet 4: Bit 0-6: ungenutzt Bit 7 : MQTT enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMQTTBrockerIP OBJECT-TYPE Name or IP-address of the MQTT-Server. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMQTTUserName OBJECT-TYPE MQTT login user name. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.3 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMQTTPassword OBJECT-TYPE MQTT login password. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMQTTLocalPort OBJECT-TYPE Local port number. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.5 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroMQTTBrokerServerPort OBJECT-TYPE MQTT Server port number. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.6 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroMQTTInterval OBJECT-TYPE Ping intervall, if no data has to be send: time in seconds. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.7 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroMQTTLastWillEnable OBJECT-TYPE Bit 0 activate MQTT LastWill message: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : MQTT Last will enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.8 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMQTTLastWillTopic OBJECT-TYPE MQTT Last Will Topic. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.9 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMQTTLastWillMsg OBJECT-TYPE MQTT Last Will message. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.10 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMQTTLastWillQoS OBJECT-TYPE Binary coded MQTT Publish QoS: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: QoS 0 Bit 1: QoS 1 Bit 2: QoS 2 Bit 3-7:unused | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.11 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroMQTTLastWillRetain OBJECT-TYPE Binary coded MQTT Publish Retain properties: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : retain enable Bit 1-7 : unused | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.12 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroMQTTLastWillConnectEnable OBJECT-TYPE Bit 0 activate MQTT LastWill Connect message: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : MQTT Last will connect message enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.13 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMQTTLastWillConnectMsg OBJECT-TYPE MQTT Last Will Connect message will be send with the QoS and Retain settings of the LastWill message. | 1.3.6.1.4.1.5040.1.2.42.3.1.3.12.14 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroREST OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.3.13 | |||
| wtWebGraphThermoHygroRESTEnable OBJECT-TYPE Bit 0 activates REST : Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : REST enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.13.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroRESTDigestAuthEnable OBJECT-TYPE Bit 0 activates Digest-Authentification: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Digest Auth enable | 1.3.6.1.4.1.5040.1.2.42.3.1.3.13.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroDatalogger OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.4 | |||
| wtWebGraphThermoHygroLoggerTimebase OBJECT-TYPE Time base of the data logger | 1.3.6.1.4.1.5040.1.2.42.3.1.4.1 | INTEGER {wtWebGraphThermoHygroDatalogger-1Min(1), wtWebGraphThermoHygroDatalogger-5Min(2), wtWebGraphThermoHygroDatalogger-15Min(3), wtWebGraphThermoHygroDatalogger-60Min(4)} | read-write | mandatory |
| wtWebGraphThermoHygroLoggerSensorSel OBJECT-TYPE Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.4.2 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroAlarm OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.5 | |||
| wtWebGraphThermoHygroAlarmCount OBJECT-TYPE Number of independent alarms. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.1 | INTEGER (1..8) | read-only | mandatory |
| wtWebGraphThermoHygroAlarmIfTable OBJECT-TYPE List of alarm indices. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.2 | not-accessible | mandatory | |
| wtWebGraphThermoHygroAlarmIfEntry OBJECT-TYPE Numbers of the alarms. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.2.1 | not-accessible | mandatory | |
| wtWebGraphThermoHygroAlarmNo OBJECT-TYPE Alarm number. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.2.1.1 | INTEGER (1..8) | read-only | mandatory |
| wtWebGraphThermoHygroAlarmTable OBJECT-TYPE List of settings depending on the alarm number. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3 | not-accessible | mandatory | |
| wtWebGraphThermoHygroAlarmEntry OBJECT-TYPE Alarm parameters of the individual alarms. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1 | not-accessible | mandatory | |
| wtWebGraphThermoHygroAlarmTrigger OBJECT-TYPE Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.1 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMin OBJECT-TYPE Minimum temperature in degrees with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMax OBJECT-TYPE Maximum temperature in degrees with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.3 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmHysteresis OBJECT-TYPE Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.) , in degrees with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmDelay OBJECT-TYPE Alarm will be delayed by setting this time while stable alarm condition occur (time in minutes). | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.5 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmInterval OBJECT-TYPE Send interval for alarm messages. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.6 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmEnable OBJECT-TYPE Binary coded alarm enable: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.7 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroAlarmEMailAddr OBJECT-TYPE E-Mail address for sending the alarm mail to. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.8 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMailSubject OBJECT-TYPE Subject line for alarm mail. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.9 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMailText OBJECT-TYPE Alarm mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.10 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmManagerIP OBJECT-TYPE Name or IP address of the SNMP Manager which accepts the trap. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.11 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmTrapText OBJECT-TYPE This text is sent in the trap body. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.12 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMailOptions OBJECT-TYPE Binary coded options: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.13 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroAlarmTcpIpAddr OBJECT-TYPE Name or IP address of the TCP server which accepts the trap. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.14 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmTcpPort OBJECT-TYPE Port number of the TCP server which accepts the trap. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.15 | INTEGER (1..65535) | read-write | mandatory |
| wtWebGraphThermoHygroAlarmTcpText OBJECT-TYPE This text is sent in the TCP trap body. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.16 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmClearMailSubject OBJECT-TYPE Subject line for alarm clear mail. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.17 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmClearMailText OBJECT-TYPE Alarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.18 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmClearTrapText OBJECT-TYPE This text is sent in the trap body. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.19 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmClearTcpText OBJECT-TYPE This text is sent in the TCP trap body. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.20 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmDeltaTemp OBJECT-TYPE Maximum rate of change degrees/min with maximum 2 decimal places. Compared with the average of a period of 5 minutes. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.21 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmRHMin OBJECT-TYPE Minimum rel. Humidity in percent with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.22 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmRHMax OBJECT-TYPE Maximum rel.Humidity in percent with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.23 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmRHHysteresis OBJECT-TYPE Hysterese rel. Humidity in percent with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.24 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmAHMin OBJECT-TYPE Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.25 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmAHMax OBJECT-TYPE Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.26 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmSyslogIpAddr OBJECT-TYPE IP address of the syslog server to which the Webio device should send syslog messages. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.27 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmSyslogPort OBJECT-TYPE Port number of the syslog server to which the Webio device should send syslog messages. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.28 | INTEGER (1..65535) | read-write | mandatory |
| wtWebGraphThermoHygroAlarmSyslogText OBJECT-TYPE Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.29 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmSyslogClearText OBJECT-TYPE Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.30 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmFtpDataPort OBJECT-TYPE Local data port: 1..65535 or AUTO: the next free port will be assigned. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.31 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmFtpFileName OBJECT-TYPE Name of the file including path informations. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.32 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmFtpText OBJECT-TYPE Message text to store on the FTP server. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.33 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmFtpClearText OBJECT-TYPE Alarm clear message to store on the FTP server. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.34 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmFtpOption OBJECT-TYPE Binary coded options, select only one option at the same time: STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STORE Bit 1 : APPEND Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.35 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroAlarmTimerCron OBJECT-TYPE This entry contains 5 space or tab seperated text fields for time trigger definition. Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Range 0-59 2. Hours Range 0-23, 0 is midnight 3: Day of month Range 1-31 4: Month Range 1-12 5: Weekday Range 0-6, 0 is sunday Syntax for every field: - an asterix (*) enables every possible setting of a field - single numbers seperated by commas - a partition within the allowed range (1-5) - step size within an partition of the allowed range (0-59/2: every second minute). | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.36 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmName OBJECT-TYPE Alert name | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.39 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmActive OBJECT-TYPE Alert active 1 = ON 0 = OFF | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.40 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmHttpReqAuthEnable OBJECT-TYPE Binary coded options, select only one option at the same time: OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : HHTP Request Authentication enable | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.61 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmHttpReqAuthUser OBJECT-TYPE HTTP Request: User | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.62 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmHttpReqAuthPassword OBJECT-TYPE HTTP Request: Password | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.63 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmHttpReqSetUrl OBJECT-TYPE HTTP Request: Set URL | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.64 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmHttpReqClearUrl OBJECT-TYPE HTTP Request: Clear URL | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.65 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmHttpReqServerPort OBJECT-TYPE HTTP Request: Server Port | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.66 | INTEGER (1..65535) | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMqttTopicPath OBJECT-TYPE MQTT Publish: Topic path | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.67 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMqttTopicSetTopic OBJECT-TYPE MQTT Publish: Topic SET message | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.68 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMqttTopicClear OBJECT-TYPE MQTT Publish: Topic CLEAR message | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.69 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmSensorLostSelection OBJECT-TYPE Binary coded options: OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : Sensor 1 Bit 0 : Sensor 0 | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.70 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmLimitWindow OBJECT-TYPE If window type is INSIDE the alarm is genereted when the temperature is greater minumum value and lower than maximum value. If window type is OUTSIDE the alarm is generated when the measured value is lower than the minimum value or greater than the maximum value. Binary coded options, select only one option at the same time: OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : inside window Bit 0 : outside window | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.71 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroAlarmSnmpManagerPort OBJECT-TYPE Port number of the SNMP Manager to which the Webio device should send SNMP traps. | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.76 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMqttQoS OBJECT-TYPE Binary coded value: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: QoS 0 Bit 1: QoS 1 Bit 2: QoS 2 Bit 3-7:unused | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.77 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroAlarmMqttRetain OBJECT-TYPE Binary coded value: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : retain enable Bit 1-7 : unused | 1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.78 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroGraphics OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.6 | |||
| wtWebGraphThermoHygroGraphicsBase OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.6.1 | |||
| wtWebGraphThermoHygroGraphicsBaseEnable OBJECT-TYPE Defines the viewing options of the graphic: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Auto scroll enable Bit 1 : Show table Bit 2 : Show graph Bit 3 : Show control buttons Bit 4 : Show config menu Bit 5-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.6.1.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsBaseWidth OBJECT-TYPE Defines the width of the graphic in pixels. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.1.2 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsBaseHeight OBJECT-TYPE Defines the height of the graphic in pixels. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.1.3 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsBaseFrameColor OBJECT-TYPE Frame color definition in RGB. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.1.4 | OCTET STRING (SIZE(3)) | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsBaseBackgroundColor OBJECT-TYPE Background color definition in RGB. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.1.5 | OCTET STRING (SIZE(3)) | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsBasePollingrate OBJECT-TYPE Defines the pollingrate in seconds, which defines the refreshing intervall of the graphic. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.1.6 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsSelect OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.6.2 | |||
| wtWebGraphThermoHygroGraphicsSelectDisplaySensorSel OBJECT-TYPE Binary coded sensor selection: only selected sensors will be shown in the graphical presentation: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.6.2.1 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsSelectDisplayShowExtrem OBJECT-TYPE Binary coded sensor selection: only selected sensors will be shown with minima and maxima: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.6.2.2 | OCTET STRING (SIZE(4)) | read-write | mandatory |
| wtWebGraphThermoHygroSensorColorTable OBJECT-TYPE List of sensor colors for the praphical presentation. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3 | not-accessible | mandatory | |
| wtWebGraphThermoHygroSensorColorEntry OBJECT-TYPE Numbers of the sensors. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3.1 | not-accessible | mandatory | |
| wtWebGraphThermoHygroGraphicsSensorColor OBJECT-TYPE Color of the sensors at the praphical presention. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3.1.1 | OCTET STRING (SIZE(3)) | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsSelectScale OBJECT-TYPE Assignes one of 4 scales to a sensor: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Use Scale 1 Bit 1 : Use Scale 2 Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3.1.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsScale OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3 | |||
| wtWebGraphThermoHygroGraphicsScaleAutoScaleEnable OBJECT-TYPE Select the Auto Scale Mode: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Scale 1 Auto scale enable Bit 1 : Scale 2 Auto scale enable Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsScaleAutoFitEnable OBJECT-TYPE Select the Auto Fit Mode:: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Scale 1 Auto fit enable Bit 1 : Scale 2 Auto fit enable Bit 2-7: unused | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroGraphicsScale1Min OBJECT-TYPE Scale 1: Minimum. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.3 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale2Min OBJECT-TYPE Scale 2: Minimum. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.4 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale3Min OBJECT-TYPE Scale 3: Minimum. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.5 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale4Min OBJECT-TYPE Scale 4: Minimum. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.6 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale1Max OBJECT-TYPE Scale 1: Maximum. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.7 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale2Max OBJECT-TYPE Scale 2: Maximum. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.8 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale3Max OBJECT-TYPE Scale 3: Maximum. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.9 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale4Max OBJECT-TYPE Scale 4: Maximum. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.10 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale1Unit OBJECT-TYPE Scale 1: Unit. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.11 | OCTET STRING | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale2Unit OBJECT-TYPE Scale 2: Unit. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.12 | OCTET STRING | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale3Unit OBJECT-TYPE Scale 3: Unit. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.13 | OCTET STRING | read-only | mandatory |
| wtWebGraphThermoHygroGraphicsScale4Unit OBJECT-TYPE Scale 4: Unit. | 1.3.6.1.4.1.5040.1.2.42.3.1.6.3.14 | OCTET STRING | read-only | mandatory |
| wtWebGraphThermoHygroPorts OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.2 | |||
| wtWebGraphThermoHygroPortTable OBJECT-TYPE List of settings depending on the sensor number. | 1.3.6.1.4.1.5040.1.2.42.3.2.1 | not-accessible | mandatory | |
| wtWebGraphThermoHygroPortEntry OBJECT-TYPE Sensor parameters for the individual sensors. | 1.3.6.1.4.1.5040.1.2.42.3.2.1.1 | not-accessible | mandatory | |
| wtWebGraphThermoHygroPortName OBJECT-TYPE Name of the sensor. | 1.3.6.1.4.1.5040.1.2.42.3.2.1.1.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroPortText OBJECT-TYPE Description of the sensor. | 1.3.6.1.4.1.5040.1.2.42.3.2.1.1.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroPortOffset1 OBJECT-TYPE Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1. | 1.3.6.1.4.1.5040.1.2.42.3.2.1.1.3 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroPortTemperature1 OBJECT-TYPE Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.2.1.1.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroPortOffset2 OBJECT-TYPE Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2. | 1.3.6.1.4.1.5040.1.2.42.3.2.1.1.5 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroPortTemperature2 OBJECT-TYPE Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. | 1.3.6.1.4.1.5040.1.2.42.3.2.1.1.6 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroPortComment OBJECT-TYPE Offset calibration: informations of date, name of operator, reference devices. | 1.3.6.1.4.1.5040.1.2.42.3.2.1.1.7 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroPortAltidude OBJECT-TYPE Altidude oh the Sensor over mean sea level (MSL). | 1.3.6.1.4.1.5040.1.2.42.3.2.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroManufact OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.3.3 | |||
| wtWebGraphThermoHygroMfName OBJECT-TYPE Manufacturer company name | 1.3.6.1.4.1.5040.1.2.42.3.3.1 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMfAddr OBJECT-TYPE Manufacturer address. | 1.3.6.1.4.1.5040.1.2.42.3.3.2 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMfHotline OBJECT-TYPE Manufacturer hotline. | 1.3.6.1.4.1.5040.1.2.42.3.3.3 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMfInternet OBJECT-TYPE Manufacturer Internet address. | 1.3.6.1.4.1.5040.1.2.42.3.3.4 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMfDeviceTyp OBJECT-TYPE Manufacturer device name (model number). | 1.3.6.1.4.1.5040.1.2.42.3.3.5 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroMfOrderNo OBJECT-TYPE Manufacturer part number. | 1.3.6.1.4.1.5040.1.2.42.3.3.6 | OCTET STRING | read-write | mandatory |
| wtWebGraphThermoHygroDiag OBJECT-IDENTITY | 1.3.6.1.4.1.5040.1.2.42.4 | |||
| wtWebGraphThermoHygroDiagErrorCount OBJECT-TYPE Number of entries in the error memory. | 1.3.6.1.4.1.5040.1.2.42.4.1 | INTEGER | read-only | mandatory |
| wtWebGraphThermoHygroDiagBinaryError OBJECT-TYPE Error causes coded bit-by-bit. | 1.3.6.1.4.1.5040.1.2.42.4.2 | OCTET STRING | read-only | mandatory |
| wtWebGraphThermoHygroDiagErrorIndex OBJECT-TYPE The value of this variable is used as an index to read an error massege from wtWebGraphThermoHygroDiagErrorMessage. Errors are numbered from 1 to wtWebGraphThermoHygroDiagErrorCount. Writing a valid value into this variable, making the appropriate message readable from wtWebGraphThermoHygroDiagErrorMessage. | 1.3.6.1.4.1.5040.1.2.42.4.3 | INTEGER | read-write | mandatory |
| wtWebGraphThermoHygroDiagErrorMessage OBJECT-TYPE Using wtWebGraphThermoHygroDiagErrorIndex as an index, the appropriate message is available. | 1.3.6.1.4.1.5040.1.2.42.4.4 | OCTET STRING | read-only | mandatory |
| wtWebGraphThermoHygroDiagErrorClear OBJECT-TYPE Writing 1 into this variable clears all diagnosis messages. | 1.3.6.1.4.1.5040.1.2.42.4.5 | INTEGER | write-only | mandatory |
Notifications
| Name | OID | Status |
|---|---|---|
| wtWebGraphThermoHygroAlert1 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 1 was triggered, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.31 | |
| wtWebGraphThermoHygroAlert2 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 2 was triggered, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.32 | |
| wtWebGraphThermoHygroAlert3 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 3 was triggered, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.33 | |
| wtWebGraphThermoHygroAlert4 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 4 was triggered, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.34 | |
| wtWebGraphThermoHygroAlert5 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 5 was triggered, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.35 | |
| wtWebGraphThermoHygroAlert6 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 6 was triggered, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.36 | |
| wtWebGraphThermoHygroAlert7 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 7 was triggered, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.37 | |
| wtWebGraphThermoHygroAlert8 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 8 was triggered, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.38 | |
| wtWebGraphThermoHygroAlert9 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 1 was cleared, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.91 | |
| wtWebGraphThermoHygroAlert10 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 2 was cleared, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.92 | |
| wtWebGraphThermoHygroAlert11 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 3 was cleared, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.93 | |
| wtWebGraphThermoHygroAlert12 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 4 was cleared, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.94 | |
| wtWebGraphThermoHygroAlert13 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 5 was cleared, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.95 | |
| wtWebGraphThermoHygroAlert14 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 6 was cleared, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.96 | |
| wtWebGraphThermoHygroAlert15 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 7 was cleared, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.97 | |
| wtWebGraphThermoHygroAlert16 NOTIFICATION-TYPE This SNMP trap is generated when Alarm 8 was cleared, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.98 | |
| wtWebGraphThermoHygroAlertDiag NOTIFICATION-TYPE This SNMP trap is generated when a diagnosis/error message was triggered, SNMP trap enable is set and SNMP is enabled. | 1.3.6.1.4.1.5040.1.2.42.0.110 |