MIBs Depot

VERTIV-V5-MIB

Registered at
1.3.6.1.4.1.21239
Last updated
2020-01-07 00:00
Organization
Vertiv
Revisions
2020-01-07 00:00, 2019-09-30 00:00, 2019-09-12 00:00, 2019-08-30 00:00, 2019-06-06 00:00, 2019-05-07 00:00, 2019-04-30 00:00, 2019-03-07 00:00, 2018-01-19 00:00, 2017-09-19 00:00, 2017-08-10 00:00, 2017-05-10 00:00, 2017-04-05 00:00, 2016-06-30 00:00, 2012-09-11 00:00
Namespace
vertiv
Source file
VERTIV-V5-MIB
Digest
sha256:70c7fa0d3d8518af5717df78dc0702097776d790f964e5b8c82a6a5ec3f42d38

Description

The MIB for Vertiv products

Contact

support@geistglobal.com

Imports

FromSymbols
SNMP-FRAMEWORK-MIBSnmpAdminString
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-MIBsysName
SNMPv2-SMIGauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDisplayString, MacAddress, TEXTUAL-CONVENTION, TruthValue

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

SNMP-FRAMEWORK-MIB
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC
VERTIV-V5-MIB

Under this module's arcs

Where the registration tree carries on below this module.

ArcNameModule
1.3.6.1.4.1.21239.2geistV3GEIST-MIB-V3
1.3.6.1.4.1.21239.5blackbird

Objects

NameOIDSyntaxAccessStatus
v5
OBJECT-IDENTITY
1.3.6.1.4.1.21239.5
imd
OBJECT-IDENTITY
1.3.6.1.4.1.21239.5.2
deviceInfo
OBJECT-IDENTITY
1.3.6.1.4.1.21239.5.2.1
productTitle
OBJECT-TYPE
Product name
1.3.6.1.4.1.21239.5.2.1.1SnmpAdminStringread-onlycurrent
productVersion
OBJECT-TYPE
Product version
1.3.6.1.4.1.21239.5.2.1.2SnmpAdminStringread-onlycurrent
productFriendlyName
OBJECT-TYPE
User-assigned name
1.3.6.1.4.1.21239.5.2.1.3SnmpAdminStringread-onlycurrent
productMacAddress
OBJECT-TYPE
Product's unique MAC address
1.3.6.1.4.1.21239.5.2.1.4MacAddressread-onlycurrent
deviceCount
OBJECT-TYPE
Total number of devices on unit
1.3.6.1.4.1.21239.5.2.1.6Integer32 (0..16)read-onlycurrent
temperatureUnits
OBJECT-TYPE
Current units for temperature/dewpoint values: 0 = Degrees Fahrenheit 1 = Degrees Celsius
1.3.6.1.4.1.21239.5.2.1.7INTEGER {fahrenheit(0), celsius(1)}read-writecurrent
productModelNumber
OBJECT-TYPE
Product model number (factory-assigned)
1.3.6.1.4.1.21239.5.2.1.8SnmpAdminStringread-onlycurrent
productPartNumber
OBJECT-TYPE
Product part number (factory-assigned)
1.3.6.1.4.1.21239.5.2.1.9SnmpAdminStringread-onlycurrent
productSerialNumber
OBJECT-TYPE
Product serial number (factory-assigned)
1.3.6.1.4.1.21239.5.2.1.10SnmpAdminStringread-onlycurrent
productPlatform
OBJECT-TYPE
Product platform
1.3.6.1.4.1.21239.5.2.1.11SnmpAdminStringread-onlycurrent
productHostname
OBJECT-TYPE
Product hostname
1.3.6.1.4.1.21239.5.2.1.12SnmpAdminStringread-onlycurrent
productAlarmCount
OBJECT-TYPE
Number of alarms currently tripped
1.3.6.1.4.1.21239.5.2.1.13Integer32read-onlycurrent
productWarnCount
OBJECT-TYPE
Number of warnings currently tripped
1.3.6.1.4.1.21239.5.2.1.14Integer32read-onlycurrent
productManufacturer
OBJECT-TYPE
Product manufacturer
1.3.6.1.4.1.21239.5.2.1.15SnmpAdminStringread-onlycurrent
pdu
OBJECT-IDENTITY
1.3.6.1.4.1.21239.5.2.3
pduMainTable
OBJECT-TYPE
PDU general information
1.3.6.1.4.1.21239.5.2.3.1not-accessiblecurrent
pduMainEntry
OBJECT-TYPE
Entry in the pduMainTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.3.1.1not-accessiblecurrent
pduMainIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.3.1.1.1Integer32 (1..100)not-accessiblecurrent
pduMainSerial
OBJECT-TYPE
Serial number
1.3.6.1.4.1.21239.5.2.3.1.1.2DisplayStringread-onlycurrent
pduMainName
OBJECT-TYPE
PDU name (factory-assigned)
1.3.6.1.4.1.21239.5.2.3.1.1.3SnmpAdminString (SIZE(1..25))read-onlycurrent
pduMainLabel
OBJECT-TYPE
PDU label (user-defined)
1.3.6.1.4.1.21239.5.2.3.1.1.4SnmpAdminString (SIZE(0..25))read-writecurrent
pduMainAvail
OBJECT-TYPE
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
1.3.6.1.4.1.21239.5.2.3.1.1.5Gauge32read-onlycurrent
pduMeterType
OBJECT-TYPE
Current meter type: 0 = Wye 1 = Delta
1.3.6.1.4.1.21239.5.2.3.1.1.6INTEGER {wye(0), delta(1)}read-onlycurrent
pduTotalName
OBJECT-TYPE
Total name (factory-assigned)
1.3.6.1.4.1.21239.5.2.3.1.1.7SnmpAdminString (SIZE(1..25))read-onlycurrent
pduTotalLabel
OBJECT-TYPE
Total label (user-defined)
1.3.6.1.4.1.21239.5.2.3.1.1.8SnmpAdminString (SIZE(0..25))read-writecurrent
pduTotalRealPower
OBJECT-TYPE
PDU total real power
1.3.6.1.4.1.21239.5.2.3.1.1.9Gauge32 (0..9999)read-onlycurrent
pduTotalApparentPower
OBJECT-TYPE
PDU total apparent power
1.3.6.1.4.1.21239.5.2.3.1.1.10Gauge32 (0..9999)read-onlycurrent
pduTotalPowerFactor
OBJECT-TYPE
PDU total power factor
1.3.6.1.4.1.21239.5.2.3.1.1.11Gauge32 (0..100)read-onlycurrent
pduTotalEnergy
OBJECT-TYPE
PDU total accumulated energy in watt-hours
1.3.6.1.4.1.21239.5.2.3.1.1.12Gauge32 (0..9999000)read-onlycurrent
pduPhaseTable
OBJECT-TYPE
PDU phases information
1.3.6.1.4.1.21239.5.2.3.2not-accessiblecurrent
pduPhaseEntry
OBJECT-TYPE
Entry in the pduPhaseTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.3.2.1not-accessiblecurrent
pduPhaseIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.3.2.1.1Integer32 (1..100)not-accessiblecurrent
pduPhaseName
OBJECT-TYPE
PDU phase name (factory-assigned)
1.3.6.1.4.1.21239.5.2.3.2.1.2SnmpAdminString (SIZE(0..25))read-onlycurrent
pduPhaseLabel
OBJECT-TYPE
PDU phase label (user-defined)
1.3.6.1.4.1.21239.5.2.3.2.1.3SnmpAdminString (SIZE(1..25))read-writecurrent
pduPhaseVoltage
OBJECT-TYPE
PDU phase voltage in tenths of a volt
1.3.6.1.4.1.21239.5.2.3.2.1.4Gauge32 (0..3100)read-onlycurrent
pduPhaseCurrent
OBJECT-TYPE
PDU phase current reading in hundredths of an amp
1.3.6.1.4.1.21239.5.2.3.2.1.8Gauge32 (0..9900)read-onlycurrent
pduPhaseRealPower
OBJECT-TYPE
Real power for phase in watts
1.3.6.1.4.1.21239.5.2.3.2.1.12Gauge32 (0..9999)read-onlycurrent
pduPhaseApparentPower
OBJECT-TYPE
Apparent power for phase in volt-amps
1.3.6.1.4.1.21239.5.2.3.2.1.13Gauge32 (0..9999)read-onlycurrent
pduPhasePowerFactor
OBJECT-TYPE
Power factor for phase
1.3.6.1.4.1.21239.5.2.3.2.1.14Gauge32 (0..100)read-onlycurrent
pduPhaseEnergy
OBJECT-TYPE
Accumulated energy for phase in watt-hours
1.3.6.1.4.1.21239.5.2.3.2.1.15Gauge32 (0..9999000)read-onlycurrent
pduPhaseBalance
OBJECT-TYPE
Phase balance as percent
1.3.6.1.4.1.21239.5.2.3.2.1.17Gauge32 (0..100)read-onlycurrent
pduPhaseCurrentCrestFactor
OBJECT-TYPE
Current crest factor for phase, in hundredths
1.3.6.1.4.1.21239.5.2.3.2.1.19Gauge32 (0..9999)read-onlycurrent
pduBreakerTable
OBJECT-TYPE
PDU breaker information
1.3.6.1.4.1.21239.5.2.3.3not-accessiblecurrent
pduBreakerEntry
OBJECT-TYPE
Entry in the pduBreakerTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.3.3.1not-accessiblecurrent
pduBreakerIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.3.3.1.1Integer32 (1..100)not-accessiblecurrent
pduBreakerName
OBJECT-TYPE
PDU breaker name (factory-assigned)
1.3.6.1.4.1.21239.5.2.3.3.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
pduBreakerLabel
OBJECT-TYPE
PDU breaker label (user-defined)
1.3.6.1.4.1.21239.5.2.3.3.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
pduBreakerCurrent
OBJECT-TYPE
PDU breaker current reading in hundredths of an amp
1.3.6.1.4.1.21239.5.2.3.3.1.4Gauge32 (0..9900)read-onlycurrent
pduBreakerVoltage
OBJECT-TYPE
PDU breaker voltage in tenths of a volt. This object may not exist on all platforms, due to hardware differences.
1.3.6.1.4.1.21239.5.2.3.3.1.8Gauge32 (0..3100)read-onlycurrent
pduBreakerRealPower
OBJECT-TYPE
Real power for breaker in watts. This object may not exist on all platforms, due to hardware differences.
1.3.6.1.4.1.21239.5.2.3.3.1.12Gauge32 (0..9999)read-onlycurrent
pduBreakerApparentPower
OBJECT-TYPE
Apparent power for breaker in volt-amps. This object may not exist on all platforms, due to hardware differences.
1.3.6.1.4.1.21239.5.2.3.3.1.13Gauge32 (0..9999)read-onlycurrent
pduBreakerPowerFactor
OBJECT-TYPE
Power factor for breaker. This object may not exist on all platforms, due to hardware differences.
1.3.6.1.4.1.21239.5.2.3.3.1.14Gauge32 (0..100)read-onlycurrent
pduBreakerEnergy
OBJECT-TYPE
Accumulated energy for breaker in watt-hours. This object may not exist on all platforms, due to hardware differences.
1.3.6.1.4.1.21239.5.2.3.3.1.15Gauge32 (0..9999000)read-onlycurrent
pduLineTable
OBJECT-TYPE
PDU line current information
1.3.6.1.4.1.21239.5.2.3.4not-accessiblecurrent
pduLineEntry
OBJECT-TYPE
Entry in the pduLineTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.3.4.1not-accessiblecurrent
pduLineIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.3.4.1.1Integer32 (1..100)not-accessiblecurrent
pduLineName
OBJECT-TYPE
PDU line name (factory-assigned)
1.3.6.1.4.1.21239.5.2.3.4.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
pduLineLabel
OBJECT-TYPE
PDU line label (user-defined)
1.3.6.1.4.1.21239.5.2.3.4.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
pduLineCurrent
OBJECT-TYPE
PDU line current reading in hundredths of an amp
1.3.6.1.4.1.21239.5.2.3.4.1.4Gauge32 (0..9900)read-onlycurrent
pduOutletSwitchTable
OBJECT-TYPE
Data, config and control for outlets with switching
1.3.6.1.4.1.21239.5.2.3.5not-accessiblecurrent
pduOutletSwitchEntry
OBJECT-TYPE
Entry in the pduOutletSwitchTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.3.5.1not-accessiblecurrent
pduOutletSwitchIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.3.5.1.1Integer32 (1..100)not-accessiblecurrent
pduOutletSwitchName
OBJECT-TYPE
PDU outlet name (factory-assigned)
1.3.6.1.4.1.21239.5.2.3.5.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
pduOutletSwitchLabel
OBJECT-TYPE
PDU outlet label (user-defined)
1.3.6.1.4.1.21239.5.2.3.5.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
pduOutletSwitchState
OBJECT-TYPE
Switch state of the outlet: 1 = Outlet is on 2 = Outlet is off 3 = Outlet is on, but will turn off after a delay 4 = Outlet is off, but will turn on after a delay 5 = Starting reboot cycle, outlet is on, but will go to the rebootOff(6) state after a delay 6 = Rebooting, outlet is off, but it will turn on after a delay 7 = Cannot get outlet state
1.3.6.1.4.1.21239.5.2.3.5.1.4INTEGER {on(1), off(2), on2off(3), off2on(4), rebootOn(5), rebootOff(6), unavailable(7)}read-onlycurrent
pduOutletSwitchRelayFailure
OBJECT-TYPE
Tells if the outlet relay has failed. In normal operation, the value will be false(2).
1.3.6.1.4.1.21239.5.2.3.5.1.5TruthValueread-onlycurrent
pduOutletSwitchControl
OBJECT-TYPE
Used for manual control of the outlet. If the outlet is in manual mode, this field can be set to one of the following values: 1 = Cancel pending operation 2 = Turn outlet on 3 = After delay (pduOutletSwitchOnDelay), turn outlet on 4 = Turn outlet off 5 = After delay (pduOutletSwitchOffDelay), turn outlet off 6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn outlet back on 7 = After delay (pduOutletSwitchRebootDelay), reboot outlet When not in manual mode, setting this field will give an inconsistentValue error. Returns none(8) for all get requests.
1.3.6.1.4.1.21239.5.2.3.5.1.6INTEGER {cancel(1), on(2), onAfterDelay(3), off(4), offAfterDelay(5), reboot(6), rebootAfterDelay(7), none(8)}read-writecurrent
pduOutletSwitchTimeToAction
OBJECT-TYPE
Seconds until an outlet state change. The value of pduOutletSwitchState tells what state the outlet will be set, after the delay.
1.3.6.1.4.1.21239.5.2.3.5.1.7Integer32 (0..600)read-onlycurrent
pduOutletSwitchOnDelay
OBJECT-TYPE
Seconds to wait before powering on the outlet, during onAfterDelay(3) operation. Changing this value has no effect on pending actions.
1.3.6.1.4.1.21239.5.2.3.5.1.8Integer32 (0..600)read-writecurrent
pduOutletSwitchOffDelay
OBJECT-TYPE
Seconds to wait before powering off the outlet, during offAfterDelay(5) operation. Changing this value has no effect on pending actions.
1.3.6.1.4.1.21239.5.2.3.5.1.9Integer32 (0..600)read-writecurrent
pduOutletSwitchRebootDelay
OBJECT-TYPE
Seconds to wait before powering off the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info.
1.3.6.1.4.1.21239.5.2.3.5.1.10Integer32 (0..600)read-writecurrent
pduOutletSwitchRebootHoldDelay
OBJECT-TYPE
Seconds to hold the outlet off, before powering on the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info.
1.3.6.1.4.1.21239.5.2.3.5.1.11Integer32 (0..600)read-writecurrent
pduOutletSwitchPoaAction
OBJECT-TYPE
The outlet is set to this state during power-up. The action can be have one the following values: 1 = Outlet will be turned on 2 = Outlet will stay off 3 = Outlet will be set to last known state
1.3.6.1.4.1.21239.5.2.3.5.1.12INTEGER {on(1), off(2), last(3)}read-writecurrent
pduOutletSwitchPoaDelay
OBJECT-TYPE
Seconds to wait before setting the outlet to the pduOutletSwitchPoaAction state. The delay starts at power-up.
1.3.6.1.4.1.21239.5.2.3.5.1.13Integer32 (0..600)read-writecurrent
pduOutletMeterTable
OBJECT-TYPE
Metering data for outlets that support this feature
1.3.6.1.4.1.21239.5.2.3.6not-accessiblecurrent
pduOutletMeterEntry
OBJECT-TYPE
Entry in the pduOutletMeterTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.3.6.1not-accessiblecurrent
pduOutletMeterIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.3.6.1.1Integer32 (1..100)not-accessiblecurrent
pduOutletMeterName
OBJECT-TYPE
PDU outlet name (factory-assigned)
1.3.6.1.4.1.21239.5.2.3.6.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
pduOutletMeterLabel
OBJECT-TYPE
PDU outlet label (user-defined)
1.3.6.1.4.1.21239.5.2.3.6.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
pduOutletMeterVoltage
OBJECT-TYPE
PDU outlet voltage in tenths of a volt
1.3.6.1.4.1.21239.5.2.3.6.1.4Gauge32 (0..3100)read-onlycurrent
pduOutletMeterCurrent
OBJECT-TYPE
PDU outlet current reading in hundredths of an amp
1.3.6.1.4.1.21239.5.2.3.6.1.8Gauge32 (0..9900)read-onlycurrent
pduOutletMeterRealPower
OBJECT-TYPE
Real power for outlet in watts
1.3.6.1.4.1.21239.5.2.3.6.1.12Gauge32 (0..9999)read-onlycurrent
pduOutletMeterApparentPower
OBJECT-TYPE
Apparent power for outlet in volt-amps
1.3.6.1.4.1.21239.5.2.3.6.1.13Gauge32 (0..9999)read-onlycurrent
pduOutletMeterPowerFactor
OBJECT-TYPE
Power factor for outlet
1.3.6.1.4.1.21239.5.2.3.6.1.14Gauge32 (0..100)read-onlycurrent
pduOutletMeterEnergy
OBJECT-TYPE
Accumulated energy for outlet in watt-hours
1.3.6.1.4.1.21239.5.2.3.6.1.15Gauge32 (0..9999000)read-onlycurrent
pduOutletMeterReset
OBJECT-TYPE
Used to reset energy. If read, the value is none(8). It can be set to resetEnergy(1), which sets outlet energy to 0
1.3.6.1.4.1.21239.5.2.3.6.1.16INTEGER {resetEnergy(1), none(8)}read-writecurrent
pduOutletCurrentCrestFactor
OBJECT-TYPE
Current crest factor for outlet, in hundredths
1.3.6.1.4.1.21239.5.2.3.6.1.19Gauge32 (0..9999)read-onlycurrent
tempSensorTable
OBJECT-TYPE
Remote Temperature (RT) sensor
1.3.6.1.4.1.21239.5.2.4not-accessiblecurrent
tempSensorEntry
OBJECT-TYPE
Entry in the tempSensorTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.4.1not-accessiblecurrent
tempSensorIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.4.1.1Integer32 (1..100)not-accessiblecurrent
tempSensorSerial
OBJECT-TYPE
Serial number
1.3.6.1.4.1.21239.5.2.4.1.2DisplayStringread-onlycurrent
tempSensorLabel
OBJECT-TYPE
User-defined label
1.3.6.1.4.1.21239.5.2.4.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
tempSensorAvail
OBJECT-TYPE
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
1.3.6.1.4.1.21239.5.2.4.1.4Gauge32read-onlycurrent
tempSensorTemp
OBJECT-TYPE
Temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.4.1.5Integer32 (-400..2540)read-onlycurrent
airFlowSensorTable
OBJECT-TYPE
Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor
1.3.6.1.4.1.21239.5.2.5not-accessiblecurrent
airFlowSensorEntry
OBJECT-TYPE
Entry in the airFlowSensorTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.5.1not-accessiblecurrent
airFlowSensorIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.5.1.1Integer32 (1..100)not-accessiblecurrent
airFlowSensorSerial
OBJECT-TYPE
Serial number
1.3.6.1.4.1.21239.5.2.5.1.2DisplayStringread-onlycurrent
airFlowSensorLabel
OBJECT-TYPE
User-defined label
1.3.6.1.4.1.21239.5.2.5.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
airFlowSensorAvail
OBJECT-TYPE
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
1.3.6.1.4.1.21239.5.2.5.1.4Gauge32read-onlycurrent
airFlowSensorTemp
OBJECT-TYPE
Temperature reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.5.1.5Integer32 (-400..2540)read-onlycurrent
airFlowSensorFlow
OBJECT-TYPE
Airflow reading. Still air will be less than 20, while rushing air will be around 100.
1.3.6.1.4.1.21239.5.2.5.1.6Integer32 (0..100)read-onlycurrent
airFlowSensorHumidity
OBJECT-TYPE
Humidity reading
1.3.6.1.4.1.21239.5.2.5.1.7Integer32 (0..100)read-onlycurrent
airFlowSensorDewPoint
OBJECT-TYPE
Dewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.5.1.8Integer32 (-400..2540)read-onlycurrent
t3hdSensorTable
OBJECT-TYPE
Remote Temperature x 3, Humidity and Dewpoint Sensor
1.3.6.1.4.1.21239.5.2.8not-accessiblecurrent
t3hdSensorEntry
OBJECT-TYPE
Entry in the t3hdSensorTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.8.1not-accessiblecurrent
t3hdSensorIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.8.1.1Integer32 (1..100)not-accessiblecurrent
t3hdSensorSerial
OBJECT-TYPE
Serial number
1.3.6.1.4.1.21239.5.2.8.1.2DisplayStringread-onlycurrent
t3hdSensorLabel
OBJECT-TYPE
User-defined label
1.3.6.1.4.1.21239.5.2.8.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
t3hdSensorAvail
OBJECT-TYPE
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
1.3.6.1.4.1.21239.5.2.8.1.4Gauge32read-onlycurrent
t3hdSensorIntLabel
OBJECT-TYPE
Internal label (user-defined)
1.3.6.1.4.1.21239.5.2.8.1.5SnmpAdminString (SIZE(0..25))read-writecurrent
t3hdSensorIntTemp
OBJECT-TYPE
Internal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.8.1.6Integer32 (-400..2540)read-onlycurrent
t3hdSensorIntHumidity
OBJECT-TYPE
Internal humidity
1.3.6.1.4.1.21239.5.2.8.1.7Integer32 (0..100)read-onlycurrent
t3hdSensorIntDewPoint
OBJECT-TYPE
Internal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.8.1.8Integer32 (-400..2540)read-onlycurrent
t3hdSensorExtAAvail
OBJECT-TYPE
External A status: 0 = Unavailable 1 = Available
1.3.6.1.4.1.21239.5.2.8.1.9Gauge32read-onlycurrent
t3hdSensorExtALabel
OBJECT-TYPE
External A label (user-defined)
1.3.6.1.4.1.21239.5.2.8.1.10SnmpAdminString (SIZE(0..25))read-writecurrent
t3hdSensorExtATemp
OBJECT-TYPE
External A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.8.1.11Integer32 (-400..2540)read-onlycurrent
t3hdSensorExtBAvail
OBJECT-TYPE
External B status: 0 = Unavailable 1 = Available
1.3.6.1.4.1.21239.5.2.8.1.12Gauge32read-onlycurrent
t3hdSensorExtBLabel
OBJECT-TYPE
External B label (user-defined)
1.3.6.1.4.1.21239.5.2.8.1.13SnmpAdminString (SIZE(0..25))read-writecurrent
t3hdSensorExtBTemp
OBJECT-TYPE
External B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.8.1.14Integer32 (-400..2540)read-onlycurrent
thdSensorTable
OBJECT-TYPE
Remote Temperature, Humidity, and Dewpoint (THD) Sensor
1.3.6.1.4.1.21239.5.2.9not-accessiblecurrent
thdSensorEntry
OBJECT-TYPE
Entry in the thdSensorTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.9.1not-accessiblecurrent
thdSensorIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.9.1.1Integer32 (1..100)not-accessiblecurrent
thdSensorSerial
OBJECT-TYPE
Serial number
1.3.6.1.4.1.21239.5.2.9.1.2DisplayStringread-onlycurrent
thdSensorLabel
OBJECT-TYPE
User-defined label
1.3.6.1.4.1.21239.5.2.9.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
thdSensorAvail
OBJECT-TYPE
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
1.3.6.1.4.1.21239.5.2.9.1.4Gauge32read-onlycurrent
thdSensorTemp
OBJECT-TYPE
Temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.9.1.5Integer32 (-400..2540)read-onlycurrent
thdSensorHumidity
OBJECT-TYPE
Humidity value
1.3.6.1.4.1.21239.5.2.9.1.6Integer32 (0..100)read-onlycurrent
thdSensorDewPoint
OBJECT-TYPE
Dewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.9.1.7Integer32 (-400..2540)read-onlycurrent
a2dSensorTable
OBJECT-TYPE
Analog measurement (A2D) sensor (voltage, current, or dry-contact)
1.3.6.1.4.1.21239.5.2.11not-accessiblecurrent
a2dSensorEntry
OBJECT-TYPE
Entry in the a2dSensorTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.11.1not-accessiblecurrent
a2dSensorIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.11.1.1Integer32 (1..100)not-accessiblecurrent
a2dSensorSerial
OBJECT-TYPE
Serial number
1.3.6.1.4.1.21239.5.2.11.1.2DisplayStringread-onlycurrent
a2dSensorLabel
OBJECT-TYPE
User-defined label
1.3.6.1.4.1.21239.5.2.11.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
a2dSensorAvail
OBJECT-TYPE
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
1.3.6.1.4.1.21239.5.2.11.1.4Gauge32read-onlycurrent
a2dSensorValue
OBJECT-TYPE
Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode.
1.3.6.1.4.1.21239.5.2.11.1.5Integer32 (-1000000..1000000)read-onlycurrent
a2dSensorDisplayValue
OBJECT-TYPE
For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue.
1.3.6.1.4.1.21239.5.2.11.1.6SnmpAdminString (SIZE(0..25))read-onlycurrent
a2dSensorMode
OBJECT-TYPE
Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMax. Analog modes: 1 = Door (binary) 2 = Power failure (binary) 3 = Flood (binary) 4 = Water-sensing cable leak (binary) 5 = Water-sensing cable fault (binary) 6 = Smoke alarm (binary) 7 = Isolated voltage negative ground (voltage) 8 = Isolated voltage positive ground (voltage) 9 = Custom voltage (voltage) 10 = Custom binary (binary) 11 = Custom current (current)
1.3.6.1.4.1.21239.5.2.11.1.7INTEGER {door(1), powerFailure(2), flood(3), wscLeak(4), wscFault(5), smoke(6), ivsNegGnd(7), ivsPosGnd(8), customVoltage(9), customBinary(10), customCurrent(11)}read-writecurrent
a2dSensorUnits
OBJECT-TYPE
The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode.
1.3.6.1.4.1.21239.5.2.11.1.8SnmpAdminString (SIZE(0..7))read-writecurrent
a2dSensorMin
OBJECT-TYPE
Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode.
1.3.6.1.4.1.21239.5.2.11.1.9Integer32 (-1000000..1000000)read-writecurrent
a2dSensorMax
OBJECT-TYPE
Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode.
1.3.6.1.4.1.21239.5.2.11.1.10Integer32 (-1000000..1000000)read-writecurrent
a2dSensorLowLabel
OBJECT-TYPE
Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode.
1.3.6.1.4.1.21239.5.2.11.1.11SnmpAdminString (SIZE(0..25))read-writecurrent
a2dSensorHighLabel
OBJECT-TYPE
Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode.
1.3.6.1.4.1.21239.5.2.11.1.12SnmpAdminString (SIZE(0..25))read-writecurrent
a2dSensorAnalogLabel
OBJECT-TYPE
Label for the analog measurement
1.3.6.1.4.1.21239.5.2.11.1.13SnmpAdminString (SIZE(0..25))read-writecurrent
humiditySensorTable
OBJECT-TYPE
Remote humidity sensor
1.3.6.1.4.1.21239.5.2.12not-accessiblecurrent
humiditySensorEntry
OBJECT-TYPE
Entry in the humiditySensorTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.12.1not-accessiblecurrent
humiditySensorIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.12.1.1Integer32 (1..100)not-accessiblecurrent
humiditySensorSerial
OBJECT-TYPE
Serial number
1.3.6.1.4.1.21239.5.2.12.1.2DisplayStringread-onlycurrent
humiditySensorLabel
OBJECT-TYPE
User-defined label
1.3.6.1.4.1.21239.5.2.12.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
humiditySensorAvail
OBJECT-TYPE
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
1.3.6.1.4.1.21239.5.2.12.1.4Gauge32read-onlycurrent
humiditySensorValue
OBJECT-TYPE
Humidity value
1.3.6.1.4.1.21239.5.2.12.1.5Integer32 (0..100)read-onlycurrent
sn2dSensorTable
OBJECT-TYPE
2 Door Switch Sensor (SN-2D)
1.3.6.1.4.1.21239.5.2.13not-accessiblecurrent
sn2dSensorEntry
OBJECT-TYPE
Entry in the sn2dSensorTable table: each entry contains an index and other sensor details
1.3.6.1.4.1.21239.5.2.13.1not-accessiblecurrent
sn2dSensorIndex
OBJECT-TYPE
Table entry index value
1.3.6.1.4.1.21239.5.2.13.1.1Integer32 (1..100)not-accessiblecurrent
sn2dSensorSerial
OBJECT-TYPE
Serial number
1.3.6.1.4.1.21239.5.2.13.1.2DisplayStringread-onlycurrent
sn2dSensorLabel
OBJECT-TYPE
User-defined label
1.3.6.1.4.1.21239.5.2.13.1.3SnmpAdminString (SIZE(0..25))read-writecurrent
sn2dSensorAvail
OBJECT-TYPE
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
1.3.6.1.4.1.21239.5.2.13.1.4Gauge32read-onlycurrent
sn2dSensorDoor1Label
OBJECT-TYPE
Door switch 1 label
1.3.6.1.4.1.21239.5.2.13.1.5SnmpAdminString (SIZE(0..25))read-writecurrent
sn2dSensorDoor1State
OBJECT-TYPE
Door switch 1 state: 1 = open 2 = closed
1.3.6.1.4.1.21239.5.2.13.1.6INTEGER {open(1), closed(2)}read-onlycurrent
sn2dSensorDoor1DisplayState
OBJECT-TYPE
Door switch 1 state given as a string
1.3.6.1.4.1.21239.5.2.13.1.7SnmpAdminString (SIZE(0..25))read-onlycurrent
sn2dSensorDoor2Label
OBJECT-TYPE
Door switch 2 label
1.3.6.1.4.1.21239.5.2.13.1.8SnmpAdminString (SIZE(0..25))read-writecurrent
sn2dSensorDoor2State
OBJECT-TYPE
Door switch 2 state: 1 = open 2 = closed
1.3.6.1.4.1.21239.5.2.13.1.9INTEGER {open(1), closed(2)}read-onlycurrent
sn2dSensorDoor2DisplayState
OBJECT-TYPE
Door switch 2 state given as a string
1.3.6.1.4.1.21239.5.2.13.1.10SnmpAdminString (SIZE(0..25))read-onlycurrent
cooling
OBJECT-IDENTITY
1.3.6.1.4.1.21239.5.2.30
vrc
OBJECT-IDENTITY
1.3.6.1.4.1.21239.5.2.30.1
vrcMainTable
OBJECT-TYPE
Table that contains general VRC information
1.3.6.1.4.1.21239.5.2.30.1.1not-accessiblecurrent
vrcMainEntry
OBJECT-TYPE
Entry in the vrcMainTable: each entry represents a VRC device
1.3.6.1.4.1.21239.5.2.30.1.1.1not-accessiblecurrent
vrcMainIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.1.1.1Integer32 (1..100)not-accessiblecurrent
vrcMainSerial
OBJECT-TYPE
Serial number
1.3.6.1.4.1.21239.5.2.30.1.1.1.2DisplayStringread-onlycurrent
vrcMainName
OBJECT-TYPE
VRC name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.1.1.3SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcMainLabel
OBJECT-TYPE
VRC label (user-defined)
1.3.6.1.4.1.21239.5.2.30.1.1.1.4SnmpAdminString (SIZE(0..25))read-writecurrent
vrcMainAvail
OBJECT-TYPE
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
1.3.6.1.4.1.21239.5.2.30.1.1.1.5Gauge32read-onlycurrent
vrcMainPtTable
OBJECT-TYPE
Table that contains general VRC status
1.3.6.1.4.1.21239.5.2.30.1.2not-accessiblecurrent
vrcMainPtEntry
OBJECT-TYPE
Entry in the vrcMainPtTable: each entry contains status data for a VRC device
1.3.6.1.4.1.21239.5.2.30.1.2.1not-accessiblecurrent
vrcMainPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.2.1.1Integer32 (1..100)not-accessiblecurrent
vrcMainPtRunState
OBJECT-TYPE
VRC run state: 1 = on 2 = off
1.3.6.1.4.1.21239.5.2.30.1.2.1.2INTEGER {on(1), off(2)}read-onlycurrent
vrcMainPtEevOpened
OBJECT-TYPE
Eev opened value (percent)
1.3.6.1.4.1.21239.5.2.30.1.2.1.3Integer32 (0..100)read-onlycurrent
vrcMainPtAlarmNumbers
OBJECT-TYPE
Alarm numbers value
1.3.6.1.4.1.21239.5.2.30.1.2.1.4Integer32 (-32768..32767)read-onlycurrent
vrcMainPtHistoryAlarmNumbers
OBJECT-TYPE
History alarm numbers value
1.3.6.1.4.1.21239.5.2.30.1.2.1.5Integer32 (-32768..32767)read-onlycurrent
vrcMainPtHpAbnRecordCnt
OBJECT-TYPE
Hp Abnormal record count
1.3.6.1.4.1.21239.5.2.30.1.2.1.6Integer32 (-32768..32767)read-onlycurrent
vrcMainPtMonitorBaudrate
OBJECT-TYPE
Monitor baud rate: 1 = error 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200
1.3.6.1.4.1.21239.5.2.30.1.2.1.7INTEGER {error(1), baud1200(2), baud2400(3), baud4800(4), baud9600(5), baud19200(6)}read-onlycurrent
vrcMainPtMonitorAddress
OBJECT-TYPE
Monitor address
1.3.6.1.4.1.21239.5.2.30.1.2.1.8Integer32 (1..247)read-onlycurrent
vrcMainPtLp
OBJECT-TYPE
Lp status
1.3.6.1.4.1.21239.5.2.30.1.2.1.9TruthValueread-onlycurrent
vrcMainPtFilterMaintRemind
OBJECT-TYPE
Filter maintenance reminder status
1.3.6.1.4.1.21239.5.2.30.1.2.1.10TruthValueread-onlycurrent
vrcMainPtCoolingFlag
OBJECT-TYPE
Cooling flag
1.3.6.1.4.1.21239.5.2.30.1.2.1.11TruthValueread-onlycurrent
vrcMainPtFirstOnFlag
OBJECT-TYPE
First on flag
1.3.6.1.4.1.21239.5.2.30.1.2.1.12TruthValueread-onlycurrent
vrcMainPtNewAlarmFlag
OBJECT-TYPE
New alarm flag
1.3.6.1.4.1.21239.5.2.30.1.2.1.13TruthValueread-onlycurrent
vrcMainPtComAlarmOutState
OBJECT-TYPE
Common alarm output state
1.3.6.1.4.1.21239.5.2.30.1.2.1.14TruthValueread-onlycurrent
vrcMainPtHighWaterInput
OBJECT-TYPE
High water input
1.3.6.1.4.1.21239.5.2.30.1.2.1.15TruthValueread-onlycurrent
vrcMainPtHighWaterAlarm
OBJECT-TYPE
High water alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.16TruthValueread-onlycurrent
vrcMainPtWaterUnderFloorAlarm
OBJECT-TYPE
Water under floor alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.17TruthValueread-onlycurrent
vrcMainPtSwShutDownStatus
OBJECT-TYPE
Software shutdown status
1.3.6.1.4.1.21239.5.2.30.1.2.1.18TruthValueread-onlycurrent
vrcMainPtRemoteShutdown
OBJECT-TYPE
Remote shutdown status
1.3.6.1.4.1.21239.5.2.30.1.2.1.19TruthValueread-onlycurrent
vrcMainPtRemoteShutDownFlag
OBJECT-TYPE
Remote shutdown flag
1.3.6.1.4.1.21239.5.2.30.1.2.1.20TruthValueread-onlycurrent
vrcMainPtRemoteShutDownAlarm
OBJECT-TYPE
Remote shutdown alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.21TruthValueread-onlycurrent
vrcMainPtHmiShutDownFlag
OBJECT-TYPE
Hmi shutdown flag
1.3.6.1.4.1.21239.5.2.30.1.2.1.22TruthValueread-onlycurrent
vrcMainPtLpAlarm
OBJECT-TYPE
Low pressure alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.23TruthValueread-onlycurrent
vrcMainPtHpAlarm
OBJECT-TYPE
High pressure alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.24TruthValueread-onlycurrent
vrcMainPtLpFreqAlarm
OBJECT-TYPE
Low pressure frequently alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.25TruthValueread-onlycurrent
vrcMainPtHpFreqAlarm
OBJECT-TYPE
High pressure frequently alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.26TruthValueread-onlycurrent
vrcMainPtLpSensorFailAlarm
OBJECT-TYPE
Low pressure sensor failure alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.27TruthValueread-onlycurrent
vrcMainPtHpSensorFailAlarm
OBJECT-TYPE
High pressure sensor failure alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.28TruthValueread-onlycurrent
vrcMainPtEevCommFailAlarm
OBJECT-TYPE
Eev communication failure alarm status
1.3.6.1.4.1.21239.5.2.30.1.2.1.29TruthValueread-onlycurrent
vrcMainCfgTable
OBJECT-TYPE
Table that contains general VRC configuration
1.3.6.1.4.1.21239.5.2.30.1.3not-accessiblecurrent
vrcMainCfgEntry
OBJECT-TYPE
Entry in the vrcMainCfgTable: each entry contains general config fields for a VRC device
1.3.6.1.4.1.21239.5.2.30.1.3.1not-accessiblecurrent
vrcMainCfgIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.3.1.1Integer32 (1..100)not-accessiblecurrent
vrcMainCfgModelSelect
OBJECT-TYPE
Model Selection: 1 = TMM-Local 220V 50/60HZ 2 = TMM-Global 208/230V 50/60HZ 3 = TMM-Global 120V 50/60HZ 4 = SC 220V 50/60HZ 5 = 0U 220V 50/60HZ 6 = SS 208/230V 50/60HZ 7 = SS 120V 50/60HZ
1.3.6.1.4.1.21239.5.2.30.1.3.1.2INTEGER {tmLoc(1), r035Ap(2), r035Ak(3), scLoc(4), zeroULoc(5), r035Ep(6), r035Ek(7)}read-writecurrent
vrcMainCfgSystemTimeYear
OBJECT-TYPE
System time - year
1.3.6.1.4.1.21239.5.2.30.1.3.1.3Integer32 (2000..2099)read-writecurrent
vrcMainCfgSystemTimeMonth
OBJECT-TYPE
System time - month
1.3.6.1.4.1.21239.5.2.30.1.3.1.4Integer32 (1..12)read-writecurrent
vrcMainCfgSystemTimeDay
OBJECT-TYPE
System time - day
1.3.6.1.4.1.21239.5.2.30.1.3.1.5Integer32 (1..31)read-writecurrent
vrcMainCfgSystemTimeHour
OBJECT-TYPE
System time - hour
1.3.6.1.4.1.21239.5.2.30.1.3.1.6Integer32 (0..23)read-writecurrent
vrcMainCfgSystemTimeMin
OBJECT-TYPE
System time - minutes
1.3.6.1.4.1.21239.5.2.30.1.3.1.7Integer32 (0..59)read-writecurrent
vrcMainCfgSystemTimeSec
OBJECT-TYPE
System time - seconds
1.3.6.1.4.1.21239.5.2.30.1.3.1.8Integer32 (0..59)read-writecurrent
vrcMainCfgEevShtSettingMin
OBJECT-TYPE
Min Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359
1.3.6.1.4.1.21239.5.2.30.1.3.1.9Integer32read-writecurrent
vrcMainCfgEevShtSettingMax
OBJECT-TYPE
Max Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359
1.3.6.1.4.1.21239.5.2.30.1.3.1.10Integer32read-writecurrent
vrcMainCfgEevValveCloseSht
OBJECT-TYPE
Eev valve close sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 100 Fahrenheit: 0 to 179
1.3.6.1.4.1.21239.5.2.30.1.3.1.11Integer32read-writecurrent
vrcMainCfgEevMopPressSetting
OBJECT-TYPE
Eev mop pressure setting in tenths of a bar.
1.3.6.1.4.1.21239.5.2.30.1.3.1.12Integer32 (0..200)read-writecurrent
vrcMainCfgLpdt
OBJECT-TYPE
Low pressure dt in seconds
1.3.6.1.4.1.21239.5.2.30.1.3.1.13Integer32 (30..600)read-writecurrent
vrcMainCfgDeadBand
OBJECT-TYPE
Dead band in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 20 Fahrenheit: 0 to 35
1.3.6.1.4.1.21239.5.2.30.1.3.1.14Integer32read-writecurrent
vrcMainCfgOnOffSwitch
OBJECT-TYPE
On-off switch
1.3.6.1.4.1.21239.5.2.30.1.3.1.15TruthValueread-writecurrent
vrcMainCfgVacuumState
OBJECT-TYPE
Vacuum state
1.3.6.1.4.1.21239.5.2.30.1.3.1.16TruthValueread-writecurrent
vrcMainCfgControlMode
OBJECT-TYPE
Control mode: 1 = supply 2 = return
1.3.6.1.4.1.21239.5.2.30.1.3.1.17INTEGER {supply(1), return(2)}read-writecurrent
vrcMainCfgManualRunEnable
OBJECT-TYPE
Manual run enable
1.3.6.1.4.1.21239.5.2.30.1.3.1.18TruthValueread-writecurrent
vrcMainCfgRemShutdownInput
OBJECT-TYPE
Remote shutdown input
1.3.6.1.4.1.21239.5.2.30.1.3.1.19TruthValueread-writecurrent
vrcMainCfgMonitorShutDownFlag
OBJECT-TYPE
Monitor shutdown flag
1.3.6.1.4.1.21239.5.2.30.1.3.1.20TruthValueread-writecurrent
vrcMainCfgFirstOnPassword
OBJECT-TYPE
First on password value
1.3.6.1.4.1.21239.5.2.30.1.3.1.21Integer32 (-32768..32767)read-writecurrent
vrcMainCfgFilterMaintSetting
OBJECT-TYPE
Filter maintenance setting
1.3.6.1.4.1.21239.5.2.30.1.3.1.22TruthValueread-writecurrent
vrcMainCfgFilterMaintRemindTime
OBJECT-TYPE
Time between filter maintenance reminders in days
1.3.6.1.4.1.21239.5.2.30.1.3.1.23Integer32 (30..360)read-writecurrent
vrcMainCfgFilterMaintRemindCtrl
OBJECT-TYPE
Filter maintenance reminder: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.24INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcMainCfgCommonAlarmOutputDir
OBJECT-TYPE
Common alarm output direction
1.3.6.1.4.1.21239.5.2.30.1.3.1.25TruthValueread-writecurrent
vrcMainCfgHpAbnAlarmSetting
OBJECT-TYPE
Abnormal high pressure alarm value in tenths of a bar
1.3.6.1.4.1.21239.5.2.30.1.3.1.26Integer32 (300..360)read-writecurrent
vrcMainCfgLpAlarmCtrl
OBJECT-TYPE
Low pressure alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.27INTEGER {suspend(2), open(3)}read-writecurrent
vrcMainCfgHpAlarmCtrl
OBJECT-TYPE
High pressure alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.28INTEGER {suspend(2), open(3)}read-writecurrent
vrcMainCfgLpFreqAlarmCtrl
OBJECT-TYPE
Low pressure frequently alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.29INTEGER {suspend(2), open(3)}read-writecurrent
vrcMainCfgHpFreqAlarmCtrl
OBJECT-TYPE
High pressure frequently alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.30INTEGER {suspend(2), open(3)}read-writecurrent
vrcMainCfgLpSensorFailAlarmCtrl
OBJECT-TYPE
Low pressure sensor failure alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.31INTEGER {suspend(2), open(3)}read-writecurrent
vrcMainCfgHpSensorFailAlarmCtrl
OBJECT-TYPE
High pressure sensor failure alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.32INTEGER {suspend(2), open(3)}read-writecurrent
vrcMainCfgHighWaterAlarmCtrl
OBJECT-TYPE
High water alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.33INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcMainCfgRemShutdownAlarmCtrl
OBJECT-TYPE
Remote shutdown alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.34INTEGER {suspend(2), open(3)}read-writecurrent
vrcMainCfgEevCommFailAlarmCtrl
OBJECT-TYPE
Eev communication failure alarm: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.3.1.35INTEGER {suspend(2), open(3)}read-writecurrent
vrcOutFanPtTable
OBJECT-TYPE
Table that contains VRC out-fan status
1.3.6.1.4.1.21239.5.2.30.1.4not-accessiblecurrent
vrcOutFanPtEntry
OBJECT-TYPE
Entry in the vrcOutFanPtTable: each entry represents data for a VRC out-fan
1.3.6.1.4.1.21239.5.2.30.1.4.1not-accessiblecurrent
vrcOutFanPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.4.1.1Integer32 (1..100)not-accessiblecurrent
vrcOutFanPtName
OBJECT-TYPE
Out-fan name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.4.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcOutFanPtSpeed
OBJECT-TYPE
Fan speed (percent)
1.3.6.1.4.1.21239.5.2.30.1.4.1.3Integer32 (0..100)read-onlycurrent
vrcOutFanCfgTable
OBJECT-TYPE
Table used for VRC out-fan configuration
1.3.6.1.4.1.21239.5.2.30.1.5not-accessiblecurrent
vrcOutFanCfgEntry
OBJECT-TYPE
Entry in the vrcOutFanCfgTable: each entry contains config fields for a VRC out-fan
1.3.6.1.4.1.21239.5.2.30.1.5.1not-accessiblecurrent
vrcOutFanCfgIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.5.1.1Integer32 (1..100)not-accessiblecurrent
vrcOutFanCfgStartPress
OBJECT-TYPE
Out-fan start pressure in tenths of a bar
1.3.6.1.4.1.21239.5.2.30.1.5.1.2Integer32 (190..250)read-writecurrent
vrcOutFanCfgPressSetting
OBJECT-TYPE
Out-fan pressure setting in tenths of a bar
1.3.6.1.4.1.21239.5.2.30.1.5.1.3Integer32 (50..80)read-writecurrent
vrcOutFanCfgMinPowerVoltage
OBJECT-TYPE
Min out-fan voltage (percent)
1.3.6.1.4.1.21239.5.2.30.1.5.1.4Integer32 (30..50)read-writecurrent
vrcOutFanCfgMaxPowerVoltage
OBJECT-TYPE
Max out-fan voltage (percent)
1.3.6.1.4.1.21239.5.2.30.1.5.1.5Integer32 (60..100)read-writecurrent
vrcOutFanCfgSpeed
OBJECT-TYPE
Out-fan speed (percent)
1.3.6.1.4.1.21239.5.2.30.1.5.1.6Integer32 (0..100)read-writecurrent
vrcInFanPtTable
OBJECT-TYPE
Table that contains VRC in-fan status
1.3.6.1.4.1.21239.5.2.30.1.6not-accessiblecurrent
vrcInFanPtEntry
OBJECT-TYPE
Entry in the vrcInFanPtTable: each entry represents data for a VRC in- fan
1.3.6.1.4.1.21239.5.2.30.1.6.1not-accessiblecurrent
vrcInFanPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.6.1.1Integer32 (1..100)not-accessiblecurrent
vrcInFanPtName
OBJECT-TYPE
In-fan name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.6.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcInFanPtRunTimeHours
OBJECT-TYPE
In-fan run time in hours
1.3.6.1.4.1.21239.5.2.30.1.6.1.3Integer32 (-32768..32767)read-onlycurrent
vrcInFanPtStartStopCount
OBJECT-TYPE
In-fan start/stop count
1.3.6.1.4.1.21239.5.2.30.1.6.1.4Integer32 (-32768..32767)read-onlycurrent
vrcInFanCfgTable
OBJECT-TYPE
Table used for VRC in-fan configuration
1.3.6.1.4.1.21239.5.2.30.1.7not-accessiblecurrent
vrcInFanCfgEntry
OBJECT-TYPE
Entry in the vrcInFanCfgTable: each entry contains config fields for a VRC in-fan
1.3.6.1.4.1.21239.5.2.30.1.7.1not-accessiblecurrent
vrcInFanCfgIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.7.1.1Integer32 (1..100)not-accessiblecurrent
vrcInFanCfgOutputStatus
OBJECT-TYPE
In-fan output status
1.3.6.1.4.1.21239.5.2.30.1.7.1.2TruthValueread-writecurrent
vrcInFanCfgLowSpeedStep
OBJECT-TYPE
In-fan low speed step in tenths of a percent per second
1.3.6.1.4.1.21239.5.2.30.1.7.1.3Integer32 (1..20)read-writecurrent
vrcInFanCfgHighSpeedStep
OBJECT-TYPE
In-fan high speed step in tenths of a percent per second
1.3.6.1.4.1.21239.5.2.30.1.7.1.4Integer32 (1..50)read-writecurrent
vrcInFanCfgMinSpeed
OBJECT-TYPE
Min in-fan speed (percent)
1.3.6.1.4.1.21239.5.2.30.1.7.1.5Integer32 (30..80)read-writecurrent
vrcInFanCfgStandardSpeed
OBJECT-TYPE
Standard in-fan speed (percent)
1.3.6.1.4.1.21239.5.2.30.1.7.1.6Integer32 (80..100)read-writecurrent
vrcInFanCfgMinCfc
OBJECT-TYPE
Min in-fan cfc (percent)
1.3.6.1.4.1.21239.5.2.30.1.7.1.7Integer32 (0..30)read-writecurrent
vrcInFanCfgStandardCfc
OBJECT-TYPE
Standard in-fan cfc (percent)
1.3.6.1.4.1.21239.5.2.30.1.7.1.8Integer32 (85..100)read-writecurrent
vrcInFanCfgStartDelay
OBJECT-TYPE
In-fan start delay in seconds
1.3.6.1.4.1.21239.5.2.30.1.7.1.9Integer32 (10..600)read-writecurrent
vrcInFanCfgStopDelay
OBJECT-TYPE
In-fan stop delay in seconds
1.3.6.1.4.1.21239.5.2.30.1.7.1.10Integer32 (10..300)read-writecurrent
vrcInFanCfgReduceSpeedDelay
OBJECT-TYPE
In-fan reduce speed delay in seconds
1.3.6.1.4.1.21239.5.2.30.1.7.1.11Integer32 (0..300)read-writecurrent
vrcInFanCfgJumpBand1
OBJECT-TYPE
In-fan jump band 1 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.12Integer32 (0..100)read-writecurrent
vrcInFanCfgJumpBand2
OBJECT-TYPE
In-fan jump band 2 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.13Integer32 (0..100)read-writecurrent
vrcInFanCfgJumpBand3
OBJECT-TYPE
In-fan jump band 3 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.14Integer32 (0..100)read-writecurrent
vrcInFanCfgJumpBand4
OBJECT-TYPE
In-fan jump band 4 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.15Integer32 (0..100)read-writecurrent
vrcInFanCfgJumpBand5
OBJECT-TYPE
In-fan jump band 5 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.16Integer32 (0..100)read-writecurrent
vrcInFanCfgJumpFreq1
OBJECT-TYPE
In-fan jump frequency 1 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.17Integer32 (0..1000)read-writecurrent
vrcInFanCfgJumpFreq2
OBJECT-TYPE
In-fan jump frequency 2 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.18Integer32 (0..1000)read-writecurrent
vrcInFanCfgJumpFreq3
OBJECT-TYPE
In-fan jump frequency 3 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.19Integer32 (0..1000)read-writecurrent
vrcInFanCfgJumpFreq4
OBJECT-TYPE
In-fan jump frequency 4 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.20Integer32 (0..1000)read-writecurrent
vrcInFanCfgJumpFreq5
OBJECT-TYPE
In-fan jump frequency 5 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.7.1.21Integer32 (0..1000)read-writecurrent
vrcInFanCfgTempP
OBJECT-TYPE
In-fan temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
1.3.6.1.4.1.21239.5.2.30.1.7.1.22Integer32 (10..150)read-writecurrent
vrcInFanCfgTempI
OBJECT-TYPE
In-fan temperature I in seconds
1.3.6.1.4.1.21239.5.2.30.1.7.1.23Integer32 (0..900)read-writecurrent
vrcInFanCfgTempD
OBJECT-TYPE
In-fan temperature D in seconds
1.3.6.1.4.1.21239.5.2.30.1.7.1.24Integer32 (0..900)read-writecurrent
vrcCompPtTable
OBJECT-TYPE
Table that contains VRC compressor status
1.3.6.1.4.1.21239.5.2.30.1.8not-accessiblecurrent
vrcCompPtEntry
OBJECT-TYPE
Entry in the vrcCompPtTable: each entry represents data for a VRC compressor
1.3.6.1.4.1.21239.5.2.30.1.8.1not-accessiblecurrent
vrcCompPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.8.1.1Integer32 (1..100)not-accessiblecurrent
vrcCompPtName
OBJECT-TYPE
Compressor name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.8.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcCompPtCapacity
OBJECT-TYPE
Compressor capacity value (percent)
1.3.6.1.4.1.21239.5.2.30.1.8.1.3Integer32 (0..100)read-onlycurrent
vrcCompPtRunTimeHours
OBJECT-TYPE
Compressor run time in hours
1.3.6.1.4.1.21239.5.2.30.1.8.1.4Integer32 (-32768..32767)read-onlycurrent
vrcCompPtStartStopCount
OBJECT-TYPE
Compressor start/stop count
1.3.6.1.4.1.21239.5.2.30.1.8.1.5Integer32 (-32768..32767)read-onlycurrent
vrcCompPtDriverFaultU00
OBJECT-TYPE
Compressor driver fault alarm U00 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.6TruthValueread-onlycurrent
vrcCompPtDriverFaultU01
OBJECT-TYPE
Compressor driver fault alarm U01 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.7TruthValueread-onlycurrent
vrcCompPtDriverFaultU02
OBJECT-TYPE
Compressor driver fault alarm U02 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.8TruthValueread-onlycurrent
vrcCompPtDriverFaultU03
OBJECT-TYPE
Compressor driver fault alarm U03 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.9TruthValueread-onlycurrent
vrcCompPtDriverFaultU04
OBJECT-TYPE
Compressor driver fault alarm U04 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.10TruthValueread-onlycurrent
vrcCompPtDriverFaultU05
OBJECT-TYPE
Compressor driver fault alarm U05 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.11TruthValueread-onlycurrent
vrcCompPtDriverFaultU06
OBJECT-TYPE
Compressor driver fault alarm U06 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.12TruthValueread-onlycurrent
vrcCompPtDriverFaultU07
OBJECT-TYPE
Compressor driver fault alarm U07 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.13TruthValueread-onlycurrent
vrcCompPtDriverFaultU08
OBJECT-TYPE
Compressor driver fault alarm U08 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.14TruthValueread-onlycurrent
vrcCompPtDriverFaultU09
OBJECT-TYPE
Compressor driver fault alarm U09 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.15TruthValueread-onlycurrent
vrcCompPtDriverFaultU10
OBJECT-TYPE
Compressor driver fault alarm U10 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.16TruthValueread-onlycurrent
vrcCompPtDriverFaultU11
OBJECT-TYPE
Compressor driver fault alarm U11 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.17TruthValueread-onlycurrent
vrcCompPtDriverFaultU12
OBJECT-TYPE
Compressor driver fault alarm U12 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.18TruthValueread-onlycurrent
vrcCompPtDriverFaultU13
OBJECT-TYPE
Compressor driver fault alarm U13 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.19TruthValueread-onlycurrent
vrcCompPtDriverFaultU14
OBJECT-TYPE
Compressor driver fault alarm U14 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.20TruthValueread-onlycurrent
vrcCompPtDriverFaultU15
OBJECT-TYPE
Compressor driver fault alarm U15 state
1.3.6.1.4.1.21239.5.2.30.1.8.1.21TruthValueread-onlycurrent
vrcCompPtDriverCommFailAlarm
OBJECT-TYPE
Compressor driver communication failure alarm state
1.3.6.1.4.1.21239.5.2.30.1.8.1.22TruthValueread-onlycurrent
vrcCompPtFaultLockAlarm
OBJECT-TYPE
Compressor fault lock alarm state
1.3.6.1.4.1.21239.5.2.30.1.8.1.23TruthValueread-onlycurrent
vrcCompCfgTable
OBJECT-TYPE
Table used for VRC compressor configuration
1.3.6.1.4.1.21239.5.2.30.1.9not-accessiblecurrent
vrcCompCfgEntry
OBJECT-TYPE
Entry in the vrcCompCfgTable: each entry contains config fields for a VRC compressor
1.3.6.1.4.1.21239.5.2.30.1.9.1not-accessiblecurrent
vrcCompCfgIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.9.1.1Integer32 (1..100)not-accessiblecurrent
vrcCompCfgOutputStatus
OBJECT-TYPE
Compressor output status
1.3.6.1.4.1.21239.5.2.30.1.9.1.2TruthValueread-writecurrent
vrcCompCfgOutputDeadBand
OBJECT-TYPE
Compressor output dead band in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.3Integer32 (0..50)read-writecurrent
vrcCompCfgCapacityOutputValue
OBJECT-TYPE
Compressor capacity output (percent)
1.3.6.1.4.1.21239.5.2.30.1.9.1.4Integer32 (0..100)read-writecurrent
vrcCompCfgMinCapacity
OBJECT-TYPE
Compressor min capacity (percent)
1.3.6.1.4.1.21239.5.2.30.1.9.1.5Integer32 (15..50)read-writecurrent
vrcCompCfgStartCapacity
OBJECT-TYPE
Compressor start capacity (percent)
1.3.6.1.4.1.21239.5.2.30.1.9.1.6Integer32 (40..100)read-writecurrent
vrcCompCfgStandardCapacity
OBJECT-TYPE
Compressor standard capacity (percent)
1.3.6.1.4.1.21239.5.2.30.1.9.1.7Integer32 (80..100)read-writecurrent
vrcCompCfgStartCfc
OBJECT-TYPE
Compressor start cfc (percent)
1.3.6.1.4.1.21239.5.2.30.1.9.1.8Integer32 (1..100)read-writecurrent
vrcCompCfgStopCfc
OBJECT-TYPE
Compressor stop cfc (percent)
1.3.6.1.4.1.21239.5.2.30.1.9.1.9Integer32 (-200..-50)read-writecurrent
vrcCompCfgMinRunTime
OBJECT-TYPE
Compressor min run time in minutes
1.3.6.1.4.1.21239.5.2.30.1.9.1.10Integer32 (0..30)read-writecurrent
vrcCompCfgMinStopTime
OBJECT-TYPE
Compressor min stop time in minutes
1.3.6.1.4.1.21239.5.2.30.1.9.1.11Integer32 (0..10)read-writecurrent
vrcCompCfgJumpBand1
OBJECT-TYPE
Compressor jump band 1 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.12Integer32 (0..100)read-writecurrent
vrcCompCfgJumpBand2
OBJECT-TYPE
Compressor jump band 2 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.13Integer32 (0..100)read-writecurrent
vrcCompCfgJumpBand3
OBJECT-TYPE
Compressor jump band 3 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.14Integer32 (0..100)read-writecurrent
vrcCompCfgJumpBand4
OBJECT-TYPE
Compressor jump band 4 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.15Integer32 (0..100)read-writecurrent
vrcCompCfgJumpBand5
OBJECT-TYPE
Compressor jump band 5 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.16Integer32 (0..100)read-writecurrent
vrcCompCfgJumpFreq1
OBJECT-TYPE
Compressor jump frequency 1 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.17Integer32 (0..1000)read-writecurrent
vrcCompCfgJumpFreq2
OBJECT-TYPE
Compressor jump frequency 2 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.18Integer32 (0..1000)read-writecurrent
vrcCompCfgJumpFreq3
OBJECT-TYPE
Compressor jump frequency 3 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.19Integer32 (0..1000)read-writecurrent
vrcCompCfgJumpFreq4
OBJECT-TYPE
Compressor jump frequency 4 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.20Integer32 (0..1000)read-writecurrent
vrcCompCfgJumpFreq5
OBJECT-TYPE
Compressor jump frequency 5 in tenths of a percent
1.3.6.1.4.1.21239.5.2.30.1.9.1.21Integer32 (0..1000)read-writecurrent
vrcCompCfgTempP
OBJECT-TYPE
Compressor temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 10 to 150 Fahrenheit: 18 to 269
1.3.6.1.4.1.21239.5.2.30.1.9.1.22Integer32read-writecurrent
vrcCompCfgTempI
OBJECT-TYPE
Compressor temperature I in seconds
1.3.6.1.4.1.21239.5.2.30.1.9.1.23Integer32 (0..900)read-writecurrent
vrcCompCfgTempD
OBJECT-TYPE
Compressor temperature D in seconds
1.3.6.1.4.1.21239.5.2.30.1.9.1.24Integer32 (0..900)read-writecurrent
vrcCompCfgDriverFaultAlmCtrl
OBJECT-TYPE
Compressor driver fault alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.9.1.25INTEGER {suspend(2), open(3)}read-writecurrent
vrcCompCfgDriverCommFailAlmCtrl
OBJECT-TYPE
Compressor driver communication failure alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.9.1.26INTEGER {suspend(2), open(3)}read-writecurrent
vrcCompCfgFaultLockAlmCtrl
OBJECT-TYPE
Compressor fault lock alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.9.1.27INTEGER {suspend(2), open(3)}read-writecurrent
vrcReturnPtTable
OBJECT-TYPE
Table that contains VRC return status
1.3.6.1.4.1.21239.5.2.30.1.10not-accessiblecurrent
vrcReturnPtEntry
OBJECT-TYPE
Entry in the vrcReturnPtTable: each entry represents return data for a VRC
1.3.6.1.4.1.21239.5.2.30.1.10.1not-accessiblecurrent
vrcReturnPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.10.1.1Integer32 (1..100)not-accessiblecurrent
vrcReturnPtName
OBJECT-TYPE
Return name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.10.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcReturnPtTemp
OBJECT-TYPE
Return temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
1.3.6.1.4.1.21239.5.2.30.1.10.1.3Integer32read-onlycurrent
vrcReturnPtHighTempAlarm
OBJECT-TYPE
Return high temperature alarm state
1.3.6.1.4.1.21239.5.2.30.1.10.1.4TruthValueread-onlycurrent
vrcReturnPtTempSensorFailAlarm
OBJECT-TYPE
Return temperature sensor failure alarm state
1.3.6.1.4.1.21239.5.2.30.1.10.1.5TruthValueread-onlycurrent
vrcReturnCfgTable
OBJECT-TYPE
Table used for VRC return configuration
1.3.6.1.4.1.21239.5.2.30.1.11not-accessiblecurrent
vrcReturnCfgEntry
OBJECT-TYPE
Entry in the vrcReturnCfgTable: each entry contains config fields for VRC return
1.3.6.1.4.1.21239.5.2.30.1.11.1not-accessiblecurrent
vrcReturnCfgIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.11.1.1Integer32 (1..100)not-accessiblecurrent
vrcReturnCfgOilCycle
OBJECT-TYPE
Return oil cycle in tenths of an hour
1.3.6.1.4.1.21239.5.2.30.1.11.1.2Integer32 (5..50)read-writecurrent
vrcReturnCfgOilRunCapacity
OBJECT-TYPE
Return Oil run capacity (percent)
1.3.6.1.4.1.21239.5.2.30.1.11.1.3Integer32 (50..100)read-writecurrent
vrcReturnCfgOilRunTime
OBJECT-TYPE
Return oil run time in minutes
1.3.6.1.4.1.21239.5.2.30.1.11.1.4Integer32 (0..10)read-writecurrent
vrcReturnCfgTempCalValue
OBJECT-TYPE
Return temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179
1.3.6.1.4.1.21239.5.2.30.1.11.1.5Integer32read-writecurrent
vrcReturnCfgTempSetting
OBJECT-TYPE
Return temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 250 to 350 Fahrenheit: 770 to 949
1.3.6.1.4.1.21239.5.2.30.1.11.1.6Integer32read-writecurrent
vrcReturnCfgHighTempAlarmValue
OBJECT-TYPE
Return high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 300 to 450 Fahrenheit: 860 to 1129
1.3.6.1.4.1.21239.5.2.30.1.11.1.7Integer32read-writecurrent
vrcReturnCfgHighTempAlarmCtrl
OBJECT-TYPE
Return high temperature alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.11.1.8INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcReturnCfgTempSensFailAlmCtrl
OBJECT-TYPE
Return temperature sensor failure alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.11.1.9INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcSupplyPtTable
OBJECT-TYPE
Table that contains VRC supply status
1.3.6.1.4.1.21239.5.2.30.1.12not-accessiblecurrent
vrcSupplyPtEntry
OBJECT-TYPE
Entry in the vrcSupplyPtTable: each entry represents supply data for a VRC
1.3.6.1.4.1.21239.5.2.30.1.12.1not-accessiblecurrent
vrcSupplyPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.12.1.1Integer32 (1..100)not-accessiblecurrent
vrcSupplyPtName
OBJECT-TYPE
Supply name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.12.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcSupplyPtTemp
OBJECT-TYPE
Supply temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
1.3.6.1.4.1.21239.5.2.30.1.12.1.3Integer32read-onlycurrent
vrcSupplyPtLowTempAlarm
OBJECT-TYPE
Supply low temperature alarm state
1.3.6.1.4.1.21239.5.2.30.1.12.1.4TruthValueread-onlycurrent
vrcSupplyPtHighTempAlarm
OBJECT-TYPE
Supply high temperature alarm state
1.3.6.1.4.1.21239.5.2.30.1.12.1.5TruthValueread-onlycurrent
vrcSupplyPtTempSensorFailAlarm
OBJECT-TYPE
Supply temperature sensor failure alarm state
1.3.6.1.4.1.21239.5.2.30.1.12.1.6TruthValueread-onlycurrent
vrcSupplyCfgTable
OBJECT-TYPE
Table used for VRC supply configuration
1.3.6.1.4.1.21239.5.2.30.1.13not-accessiblecurrent
vrcSupplyCfgEntry
OBJECT-TYPE
Entry in the vrcSupplyCfgTable: each entry contains config fields for a VRC supply
1.3.6.1.4.1.21239.5.2.30.1.13.1not-accessiblecurrent
vrcSupplyCfgIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.13.1.1Integer32 (1..100)not-accessiblecurrent
vrcSupplyCfgTempCalValue
OBJECT-TYPE
Supply temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179
1.3.6.1.4.1.21239.5.2.30.1.13.1.2Integer32read-writecurrent
vrcSupplyCfgTempSetting
OBJECT-TYPE
Supply temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 130 to 280 Fahrenheit: 554 to 823
1.3.6.1.4.1.21239.5.2.30.1.13.1.3Integer32read-writecurrent
vrcSupplyCfgLowTempAlarmValue
OBJECT-TYPE
Supply low temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 410 to 679
1.3.6.1.4.1.21239.5.2.30.1.13.1.4Integer32read-writecurrent
vrcSupplyCfgHighTempAlarmValue
OBJECT-TYPE
Supply high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 200 to 350 Fahrenheit: 680 to 949
1.3.6.1.4.1.21239.5.2.30.1.13.1.5Integer32read-writecurrent
vrcSupplyCfgLowTempAlmCtrl
OBJECT-TYPE
Supply low temperature alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.13.1.6INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcSupplyCfgHighTempAlmCtrl
OBJECT-TYPE
Supply high temperature alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.13.1.7INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcSupplyCfgTempSensFailAlmCtrl
OBJECT-TYPE
Supply temperature sensor failure alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.13.1.8INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcPowerPtTable
OBJECT-TYPE
Table that contains VRC power status
1.3.6.1.4.1.21239.5.2.30.1.14not-accessiblecurrent
vrcPowerPtEntry
OBJECT-TYPE
Entry in the vrcPowerPtTable: each entry represents power data for a VRC
1.3.6.1.4.1.21239.5.2.30.1.14.1not-accessiblecurrent
vrcPowerPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.14.1.1Integer32 (1..100)not-accessiblecurrent
vrcPowerPtName
OBJECT-TYPE
Power name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.14.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcPowerPtVoltage
OBJECT-TYPE
Power voltage measurement in tenths of a volt
1.3.6.1.4.1.21239.5.2.30.1.14.1.3Integer32 (-32768..32767)read-onlycurrent
vrcPowerPtFrequency
OBJECT-TYPE
Power frequency measurement in tenths of hertz
1.3.6.1.4.1.21239.5.2.30.1.14.1.4Integer32 (-32768..32767)read-onlycurrent
vrcPowerPtLowVoltageAlarm
OBJECT-TYPE
Power low voltage alarm state
1.3.6.1.4.1.21239.5.2.30.1.14.1.5TruthValueread-onlycurrent
vrcPowerPtHighVoltageAlarm
OBJECT-TYPE
Power high voltage alarm state
1.3.6.1.4.1.21239.5.2.30.1.14.1.6TruthValueread-onlycurrent
vrcPowerPtLossOfPhasePowerAlarm
OBJECT-TYPE
Phase power loss alarm state
1.3.6.1.4.1.21239.5.2.30.1.14.1.7TruthValueread-onlycurrent
vrcPowerPtLossOfPowerAlarm
OBJECT-TYPE
Power loss alarm state
1.3.6.1.4.1.21239.5.2.30.1.14.1.8TruthValueread-onlycurrent
vrcPowerPtFrequencyErrorAlarm
OBJECT-TYPE
Power frequency error alarm state
1.3.6.1.4.1.21239.5.2.30.1.14.1.9TruthValueread-onlycurrent
vrcPowerCfgTable
OBJECT-TYPE
Table used for VRC power configuration
1.3.6.1.4.1.21239.5.2.30.1.15not-accessiblecurrent
vrcPowerCfgEntry
OBJECT-TYPE
Entry in the vrcPowerCfgTable: each entry contains config fields for VRC power
1.3.6.1.4.1.21239.5.2.30.1.15.1not-accessiblecurrent
vrcPowerCfgIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.15.1.1Integer32 (1..100)not-accessiblecurrent
vrcPowerCfgLowVoltageSetting
OBJECT-TYPE
Power low voltage setting in volts
1.3.6.1.4.1.21239.5.2.30.1.15.1.2Integer32 (100..230)read-writecurrent
vrcPowerCfgHighVoltageSetting
OBJECT-TYPE
Power high voltage setting in volts
1.3.6.1.4.1.21239.5.2.30.1.15.1.3Integer32 (100..300)read-writecurrent
vrcPowerCfgLowVoltageAlarmCtrl
OBJECT-TYPE
Power low voltage alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.15.1.4INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcPowerCfgHighVoltageAlarmCtrl
OBJECT-TYPE
Power high voltage alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.15.1.5INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcPowerCfgLossOfPowerAlarmCtrl
OBJECT-TYPE
Power loss alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.15.1.6INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcPowerCfgFreqErrorAlarmCtrl
OBJECT-TYPE
Power frequency error alarm control: 1 = close 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.15.1.7INTEGER {close(1), suspend(2), open(3)}read-writecurrent
vrcOutdoorPtTable
OBJECT-TYPE
Table that contains VRC outdoor status
1.3.6.1.4.1.21239.5.2.30.1.16not-accessiblecurrent
vrcOutdoorPtEntry
OBJECT-TYPE
Entry in the vrcOutdoorPtTable: each entry represents data for a VRC outdoor
1.3.6.1.4.1.21239.5.2.30.1.16.1not-accessiblecurrent
vrcOutdoorPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.16.1.1Integer32 (1..100)not-accessiblecurrent
vrcOutdoorPtName
OBJECT-TYPE
Outdoor name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.16.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcOutdoorPtTemp
OBJECT-TYPE
Outdoor temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
1.3.6.1.4.1.21239.5.2.30.1.16.1.3Integer32read-onlycurrent
vrcDischPtTable
OBJECT-TYPE
Table that contains VRC discharge status
1.3.6.1.4.1.21239.5.2.30.1.18not-accessiblecurrent
vrcDischPtEntry
OBJECT-TYPE
Entry in the vrcDischPtTable: each entry represents discharge data for a VRC
1.3.6.1.4.1.21239.5.2.30.1.18.1not-accessiblecurrent
vrcDischPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.18.1.1Integer32 (1..100)not-accessiblecurrent
vrcDischPtName
OBJECT-TYPE
Discharge name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.18.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcDischPtTemp
OBJECT-TYPE
Discharge temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1560 Fahrenheit: -400 to 3128
1.3.6.1.4.1.21239.5.2.30.1.18.1.3Integer32read-writecurrent
vrcDischPtPressure
OBJECT-TYPE
Discharge air pressure value in tenths of a bar
1.3.6.1.4.1.21239.5.2.30.1.18.1.4Integer32 (0..460)read-writecurrent
vrcDischPtHighTempAlarm
OBJECT-TYPE
Discharge high temperature alarm state
1.3.6.1.4.1.21239.5.2.30.1.18.1.5TruthValueread-onlycurrent
vrcDischPtHighTempFreqAlarm
OBJECT-TYPE
Discharge high temperature frequently alarm state
1.3.6.1.4.1.21239.5.2.30.1.18.1.6TruthValueread-onlycurrent
vrcDischPtTempSensorFailAlarm
OBJECT-TYPE
Discharge temperature sensor failure alarm state
1.3.6.1.4.1.21239.5.2.30.1.18.1.7TruthValueread-onlycurrent
vrcDischCfgTable
OBJECT-TYPE
Table used for VRC discharge configuration
1.3.6.1.4.1.21239.5.2.30.1.19not-accessiblecurrent
vrcDischCfgEntry
OBJECT-TYPE
Entry in the vrcDischCfgTable: each entry contains config fields for VRC discharge
1.3.6.1.4.1.21239.5.2.30.1.19.1not-accessiblecurrent
vrcDischCfgIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.19.1.1Integer32 (1..100)not-accessiblecurrent
vrcDischCfgTempCalValue
OBJECT-TYPE
Discharge temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179
1.3.6.1.4.1.21239.5.2.30.1.19.1.2Integer32read-writecurrent
vrcDischCfgPressCalValue
OBJECT-TYPE
Discharge pressure calibration value in tenths of a bar
1.3.6.1.4.1.21239.5.2.30.1.19.1.3Integer32 (-100..100)read-writecurrent
vrcDischCfgHighTempAlmCtrl
OBJECT-TYPE
Discharge high temperature alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.19.1.4INTEGER {suspend(2), open(3)}read-writecurrent
vrcDischCfgHighTempFreqAlmCtrl
OBJECT-TYPE
Discharge high temperature frequenctly alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.19.1.5INTEGER {suspend(2), open(3)}read-writecurrent
vrcDischCfgTempSensFailAlmCtrl
OBJECT-TYPE
Discharge temperature sensor failure alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.19.1.6INTEGER {suspend(2), open(3)}read-writecurrent
vrcSuctPtTable
OBJECT-TYPE
Table that contains VRC suction status
1.3.6.1.4.1.21239.5.2.30.1.20not-accessiblecurrent
vrcSuctPtEntry
OBJECT-TYPE
Entry in the vrcSuctPtTable: each entry represents suction data for a VRC
1.3.6.1.4.1.21239.5.2.30.1.20.1not-accessiblecurrent
vrcSuctPtIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.20.1.1Integer32 (1..100)not-accessiblecurrent
vrcSuctPtName
OBJECT-TYPE
Suction name (factory-assigned)
1.3.6.1.4.1.21239.5.2.30.1.20.1.2SnmpAdminString (SIZE(1..25))read-onlycurrent
vrcSuctPtTemp
OBJECT-TYPE
Suction temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
1.3.6.1.4.1.21239.5.2.30.1.20.1.3Integer32read-onlycurrent
vrcSuctPtPressure
OBJECT-TYPE
Suction air pressure in tenths of a bar
1.3.6.1.4.1.21239.5.2.30.1.20.1.4Integer32 (0..173)read-onlycurrent
vrcSuctPtSuperHeatTemp
OBJECT-TYPE
Suction super heat temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
1.3.6.1.4.1.21239.5.2.30.1.20.1.5Integer32read-onlycurrent
vrcSuctPtTempSensorFailAlarm
OBJECT-TYPE
Suction temperature sensor failure alarm state
1.3.6.1.4.1.21239.5.2.30.1.20.1.6TruthValueread-onlycurrent
vrcSuctCfgTable
OBJECT-TYPE
Table used for VRC suction configuration
1.3.6.1.4.1.21239.5.2.30.1.21not-accessiblecurrent
vrcSuctCfgEntry
OBJECT-TYPE
Entry in the vrcSuctCfgTable: each entry contains config fields for VRC suction
1.3.6.1.4.1.21239.5.2.30.1.21.1not-accessiblecurrent
vrcSuctCfgIndex
OBJECT-TYPE
Unique id for each entry in the table
1.3.6.1.4.1.21239.5.2.30.1.21.1.1Integer32 (1..100)not-accessiblecurrent
vrcSuctCfgPressCalValue
OBJECT-TYPE
Suction pressure calibration value in tenths of a bar
1.3.6.1.4.1.21239.5.2.30.1.21.1.2Integer32 (-100..100)read-writecurrent
vrcSuctCfgTempSensFailAlmCtrl
OBJECT-TYPE
Suction temperature sensor failure alarm control: 2 = suspend 3 = open
1.3.6.1.4.1.21239.5.2.30.1.21.1.3INTEGER {suspend(2), open(3)}read-writecurrent
trap
OBJECT-IDENTITY
1.3.6.1.4.1.21239.5.2.32767
trapPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.21239.5.2.32767.0
trapObj
OBJECT-IDENTITY
1.3.6.1.4.1.21239.5.2.32767.1
trapSeverity
OBJECT-TYPE
Indicates the severity of the trap: 0 = None 1 = Warning 2 = Alarm
1.3.6.1.4.1.21239.5.2.32767.1.1INTEGER {none(0), warning(1), alarm(2)}accessible-for-notifycurrent
trapThreshType
OBJECT-TYPE
Only sent for threshold alarms. Identifies the threshold type: 1 = Low 2 = High
1.3.6.1.4.1.21239.5.2.32767.1.2INTEGER {low(1), high(2)}accessible-for-notifycurrent
common
OBJECT-IDENTITY
1.3.6.1.4.1.21239.42
identity
OBJECT-IDENTITY
1.3.6.1.4.1.21239.42.1
r05
OBJECT-IDENTITY
Value given for sysObjectID on R-Series units
1.3.6.1.4.1.21239.42.1.15current
i03
OBJECT-IDENTITY
Value given for sysObjectID on IMD3 units
1.3.6.1.4.1.21239.42.1.53current

Notifications

NameOIDStatus
internalTestNOTIFY
NOTIFICATION-TYPE
Test SNMP Trap
1.3.6.1.4.1.21239.5.2.32767.0.10101current
pduMainAvailNOTIFY
NOTIFICATION-TYPE
PDU availability trap
1.3.6.1.4.1.21239.5.2.32767.0.10305current
pduTotalRealPowerNOTIFY
NOTIFICATION-TYPE
PDU total real power trap
1.3.6.1.4.1.21239.5.2.32767.0.10309current
pduTotalApparentPowerNOTIFY
NOTIFICATION-TYPE
PDU total apparent power trap
1.3.6.1.4.1.21239.5.2.32767.0.10310current
pduTotalPowerFactorNOTIFY
NOTIFICATION-TYPE
PDU total power factor trap
1.3.6.1.4.1.21239.5.2.32767.0.10311current
pduTotalEnergyNOTIFY
NOTIFICATION-TYPE
PDU total energy trap
1.3.6.1.4.1.21239.5.2.32767.0.10312current
pduPhaseVoltageNOTIFY
NOTIFICATION-TYPE
PDU phase voltage trap
1.3.6.1.4.1.21239.5.2.32767.0.10324current
pduPhaseCurrentNOTIFY
NOTIFICATION-TYPE
PDU phase current trap
1.3.6.1.4.1.21239.5.2.32767.0.10328current
pduPhaseRealPowerNOTIFY
NOTIFICATION-TYPE
PDU phase real power trap
1.3.6.1.4.1.21239.5.2.32767.0.10332current
pduPhaseApparentPowerNOTIFY
NOTIFICATION-TYPE
PDU phase apparent power trap
1.3.6.1.4.1.21239.5.2.32767.0.10333current
pduPhasePowerFactorNOTIFY
NOTIFICATION-TYPE
PDU phase power factor trap
1.3.6.1.4.1.21239.5.2.32767.0.10334current
pduPhaseEnergyNOTIFY
NOTIFICATION-TYPE
PDU phase energy trap
1.3.6.1.4.1.21239.5.2.32767.0.10335current
pduPhaseBalanceNOTIFY
NOTIFICATION-TYPE
PDU phase balance trap
1.3.6.1.4.1.21239.5.2.32767.0.10337current
pduPhaseCurrentCrestFactorNOTIFY
NOTIFICATION-TYPE
PDU phase current crest factor trap
1.3.6.1.4.1.21239.5.2.32767.0.10339current
pduBreakerCurrentNOTIFY
NOTIFICATION-TYPE
PDU breaker current trap
1.3.6.1.4.1.21239.5.2.32767.0.10354current
pduBreakerVoltageNOTIFY
NOTIFICATION-TYPE
PDU breaker voltage trap
1.3.6.1.4.1.21239.5.2.32767.0.10358current
pduBreakerRealPowerNOTIFY
NOTIFICATION-TYPE
PDU breaker real power trap
1.3.6.1.4.1.21239.5.2.32767.0.10362current
pduBreakerApparentPowerNOTIFY
NOTIFICATION-TYPE
PDU breaker apparent power trap
1.3.6.1.4.1.21239.5.2.32767.0.10363current
pduBreakerPowerFactorNOTIFY
NOTIFICATION-TYPE
PDU breaker power factor trap
1.3.6.1.4.1.21239.5.2.32767.0.10364current
pduBreakerEnergyNOTIFY
NOTIFICATION-TYPE
PDU breaker energy trap
1.3.6.1.4.1.21239.5.2.32767.0.10365current
pduLineCurrentNOTIFY
NOTIFICATION-TYPE
PDU line current trap
1.3.6.1.4.1.21239.5.2.32767.0.10374current
pduOutletMeterVoltageNOTIFY
NOTIFICATION-TYPE
PDU outlet voltage trap
1.3.6.1.4.1.21239.5.2.32767.0.10385current
pduOutletMeterCurrentNOTIFY
NOTIFICATION-TYPE
PDU outlet current trap
1.3.6.1.4.1.21239.5.2.32767.0.10389current
pduOutletMeterRealPowerNOTIFY
NOTIFICATION-TYPE
PDU outlet real power trap
1.3.6.1.4.1.21239.5.2.32767.0.10393current
pduOutletMeterApparentPowerNOTIFY
NOTIFICATION-TYPE
PDU outlet apparent power trap
1.3.6.1.4.1.21239.5.2.32767.0.10394current
pduOutletMeterPowerFactorNOTIFY
NOTIFICATION-TYPE
PDU outlet power factor trap
1.3.6.1.4.1.21239.5.2.32767.0.10395current
pduOutletMeterEnergyNOTIFY
NOTIFICATION-TYPE
PDU outlet energy trap
1.3.6.1.4.1.21239.5.2.32767.0.10396current
pduOutletCurrentCrestFactorNOTIFY
NOTIFICATION-TYPE
PDU outlet current crest factor trap
1.3.6.1.4.1.21239.5.2.32767.0.10400current
tempSensorAvailNOTIFY
NOTIFICATION-TYPE
RT availability trap
1.3.6.1.4.1.21239.5.2.32767.0.10404current
tempSensorTempNOTIFY
NOTIFICATION-TYPE
RT temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.10405current
airFlowSensorAvailNOTIFY
NOTIFICATION-TYPE
AFHT3 availability trap
1.3.6.1.4.1.21239.5.2.32767.0.10504current
airFlowSensorTempNOTIFY
NOTIFICATION-TYPE
AFHT3 temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.10505current
airFlowSensorFlowNOTIFY
NOTIFICATION-TYPE
AFHT3 airflow trap
1.3.6.1.4.1.21239.5.2.32767.0.10506current
airFlowSensorHumidityNOTIFY
NOTIFICATION-TYPE
AFHT3 humidity trap
1.3.6.1.4.1.21239.5.2.32767.0.10507current
airFlowSensorDewPointNOTIFY
NOTIFICATION-TYPE
AFHT3 dewpoint trap
1.3.6.1.4.1.21239.5.2.32767.0.10508current
t3hdSensorAvailNOTIFY
NOTIFICATION-TYPE
T3HD availability trap
1.3.6.1.4.1.21239.5.2.32767.0.10804current
t3hdSensorIntTempNOTIFY
NOTIFICATION-TYPE
T3HD Internal temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.10806current
t3hdSensorIntHumidityNOTIFY
NOTIFICATION-TYPE
T3HD Internal humidity trap
1.3.6.1.4.1.21239.5.2.32767.0.10807current
t3hdSensorIntDewPointNOTIFY
NOTIFICATION-TYPE
T3HD Internal dewpoint trap
1.3.6.1.4.1.21239.5.2.32767.0.10808current
t3hdSensorExtATempNOTIFY
NOTIFICATION-TYPE
T3HD External A temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.10811current
t3hdSensorExtBTempNOTIFY
NOTIFICATION-TYPE
T3HD External B temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.10814current
thdSensorAvailNOTIFY
NOTIFICATION-TYPE
THD availability trap
1.3.6.1.4.1.21239.5.2.32767.0.10904current
thdSensorTempNOTIFY
NOTIFICATION-TYPE
THD temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.10905current
thdSensorHumidityNOTIFY
NOTIFICATION-TYPE
THD humidity trap
1.3.6.1.4.1.21239.5.2.32767.0.10906current
thdSensorDewPointNOTIFY
NOTIFICATION-TYPE
THD dewpoint trap
1.3.6.1.4.1.21239.5.2.32767.0.10907current
a2dSensorAvailNOTIFY
NOTIFICATION-TYPE
A2D availability trap
1.3.6.1.4.1.21239.5.2.32767.0.11104current
a2dSensorValueNOTIFY
NOTIFICATION-TYPE
A2D measurement trap
1.3.6.1.4.1.21239.5.2.32767.0.11105current
humiditySensorAvailNOTIFY
NOTIFICATION-TYPE
Remote humidity availability trap
1.3.6.1.4.1.21239.5.2.32767.0.11204current
humiditySensorValueNOTIFY
NOTIFICATION-TYPE
Remote humidity value trap
1.3.6.1.4.1.21239.5.2.32767.0.11205current
sn2dSensorAvailNOTIFY
NOTIFICATION-TYPE
SN-2D availability trap
1.3.6.1.4.1.21239.5.2.32767.0.11304current
sn2dSensorDoor1StateNOTIFY
NOTIFICATION-TYPE
SN-2D Door switch 1 state trap
1.3.6.1.4.1.21239.5.2.32767.0.11306current
sn2dSensorDoor2StateNOTIFY
NOTIFICATION-TYPE
SN-2D Door switch 2 state trap
1.3.6.1.4.1.21239.5.2.32767.0.11309current
vrcMainAvailNOTIFY
NOTIFICATION-TYPE
VRC availability trap
1.3.6.1.4.1.21239.5.2.32767.0.13001current
vrcOutFanPtSpeedNOTIFY
NOTIFICATION-TYPE
VRC out-fan speed trap
1.3.6.1.4.1.21239.5.2.32767.0.13002current
vrcCompPtCapacityNOTIFY
NOTIFICATION-TYPE
VRC compressor capacity trap
1.3.6.1.4.1.21239.5.2.32767.0.13003current
vrcReturnPtTempNOTIFY
NOTIFICATION-TYPE
VRC return temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.13004current
vrcSupplyPtTempNOTIFY
NOTIFICATION-TYPE
VRC supply temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.13005current
vrcPowerPtVoltageNOTIFY
NOTIFICATION-TYPE
VRC power voltage trap
1.3.6.1.4.1.21239.5.2.32767.0.13006current
vrcPowerPtFrequencyNOTIFY
NOTIFICATION-TYPE
VRC power frequency trap
1.3.6.1.4.1.21239.5.2.32767.0.13007current
vrcOutdoorPtTempNOTIFY
NOTIFICATION-TYPE
VRC outdoor temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.13008current
vrcDischPtTempNOTIFY
NOTIFICATION-TYPE
VRC discharge temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.13009current
vrcDischPtPressureNOTIFY
NOTIFICATION-TYPE
VRC discharge pressure trap
1.3.6.1.4.1.21239.5.2.32767.0.13010current
vrcSuctPtTempNOTIFY
NOTIFICATION-TYPE
VRC suction temperature trap
1.3.6.1.4.1.21239.5.2.32767.0.13011current
vrcSuctPtPressureNOTIFY
NOTIFICATION-TYPE
VRC suction pressure trap
1.3.6.1.4.1.21239.5.2.32767.0.13012current
pduMainAvailCLEAR
NOTIFICATION-TYPE
PDU availability clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20305current
pduTotalRealPowerCLEAR
NOTIFICATION-TYPE
PDU total real power clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20309current
pduTotalApparentPowerCLEAR
NOTIFICATION-TYPE
PDU total apparent power clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20310current
pduTotalPowerFactorCLEAR
NOTIFICATION-TYPE
PDU total power factor clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20311current
pduTotalEnergyCLEAR
NOTIFICATION-TYPE
PDU total energy clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20312current
pduPhaseVoltageCLEAR
NOTIFICATION-TYPE
PDU phase voltage clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20324current
pduPhaseCurrentCLEAR
NOTIFICATION-TYPE
PDU phase current clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20328current
pduPhaseRealPowerCLEAR
NOTIFICATION-TYPE
PDU phase real power clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20332current
pduPhaseApparentPowerCLEAR
NOTIFICATION-TYPE
PDU phase apparent power clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20333current
pduPhasePowerFactorCLEAR
NOTIFICATION-TYPE
PDU phase power factor clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20334current
pduPhaseEnergyCLEAR
NOTIFICATION-TYPE
PDU phase energy clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20335current
pduPhaseBalanceCLEAR
NOTIFICATION-TYPE
PDU phase balance clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20337current
pduPhaseCurrentCrestFactorCLEAR
NOTIFICATION-TYPE
PDU phase current crest factor clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20339current
pduBreakerCurrentCLEAR
NOTIFICATION-TYPE
PDU breaker current clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20354current
pduBreakerVoltageCLEAR
NOTIFICATION-TYPE
PDU breaker voltage clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20358current
pduBreakerRealPowerCLEAR
NOTIFICATION-TYPE
PDU breaker real power clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20362current
pduBreakerApparentPowerCLEAR
NOTIFICATION-TYPE
PDU breaker apparent power clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20363current
pduBreakerPowerFactorCLEAR
NOTIFICATION-TYPE
PDU breaker power factor clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20364current
pduBreakerEnergyCLEAR
NOTIFICATION-TYPE
PDU breaker energy clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20365current
pduLineCurrentCLEAR
NOTIFICATION-TYPE
PDU line current clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20374current
pduOutletMeterVoltageCLEAR
NOTIFICATION-TYPE
PDU outlet voltage clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20385current
pduOutletMeterCurrentCLEAR
NOTIFICATION-TYPE
PDU outlet current clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20389current
pduOutletMeterRealPowerCLEAR
NOTIFICATION-TYPE
PDU outlet real power clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20393current
pduOutletMeterApparentPowerCLEAR
NOTIFICATION-TYPE
PDU outlet apparent power clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20394current
pduOutletMeterPowerFactorCLEAR
NOTIFICATION-TYPE
PDU outlet power factor clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20395current
pduOutletMeterEnergyCLEAR
NOTIFICATION-TYPE
PDU outlet energy clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20396current
pduOutletCurrentCrestFactorCLEAR
NOTIFICATION-TYPE
PDU outlet current crest factor clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20400current
tempSensorAvailCLEAR
NOTIFICATION-TYPE
RT availability clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20404current
tempSensorTempCLEAR
NOTIFICATION-TYPE
RT temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20405current
airFlowSensorAvailCLEAR
NOTIFICATION-TYPE
AFHT3 availability clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20504current
airFlowSensorTempCLEAR
NOTIFICATION-TYPE
AFHT3 temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20505current
airFlowSensorFlowCLEAR
NOTIFICATION-TYPE
AFHT3 airflow clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20506current
airFlowSensorHumidityCLEAR
NOTIFICATION-TYPE
AFHT3 humidity clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20507current
airFlowSensorDewPointCLEAR
NOTIFICATION-TYPE
AFHT3 dewpoint clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20508current
t3hdSensorAvailCLEAR
NOTIFICATION-TYPE
T3HD availability clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20804current
t3hdSensorIntTempCLEAR
NOTIFICATION-TYPE
T3HD Internal temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20806current
t3hdSensorIntHumidityCLEAR
NOTIFICATION-TYPE
T3HD Internal humidity clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20807current
t3hdSensorIntDewPointCLEAR
NOTIFICATION-TYPE
T3HD Internal dewpoint clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20808current
t3hdSensorExtATempCLEAR
NOTIFICATION-TYPE
T3HD External A temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20811current
t3hdSensorExtBTempCLEAR
NOTIFICATION-TYPE
T3HD External B temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20814current
thdSensorAvailCLEAR
NOTIFICATION-TYPE
THD availability clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20904current
thdSensorTempCLEAR
NOTIFICATION-TYPE
THD temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20905current
thdSensorHumidityCLEAR
NOTIFICATION-TYPE
THD humidity clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20906current
thdSensorDewPointCLEAR
NOTIFICATION-TYPE
THD dewpoint clear trap
1.3.6.1.4.1.21239.5.2.32767.0.20907current
a2dSensorAvailCLEAR
NOTIFICATION-TYPE
A2D availability clear trap
1.3.6.1.4.1.21239.5.2.32767.0.21104current
a2dSensorValueCLEAR
NOTIFICATION-TYPE
A2D measurement clear trap
1.3.6.1.4.1.21239.5.2.32767.0.21105current
humiditySensorAvailCLEAR
NOTIFICATION-TYPE
Remote humidity availability clear trap
1.3.6.1.4.1.21239.5.2.32767.0.21204current
humiditySensorValueCLEAR
NOTIFICATION-TYPE
Remote humidity value clear trap
1.3.6.1.4.1.21239.5.2.32767.0.21205current
sn2dSensorAvailCLEAR
NOTIFICATION-TYPE
SN-2D availability clear trap
1.3.6.1.4.1.21239.5.2.32767.0.21304current
sn2dSensorDoor1StateCLEAR
NOTIFICATION-TYPE
SN-2D Door switch 1 state clear trap
1.3.6.1.4.1.21239.5.2.32767.0.21306current
sn2dSensorDoor2StateCLEAR
NOTIFICATION-TYPE
SN-2D Door switch 2 state clear trap
1.3.6.1.4.1.21239.5.2.32767.0.21309current
vrcMainAvailCLEAR
NOTIFICATION-TYPE
VRC availability clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23001current
vrcOutFanPtSpeedCLEAR
NOTIFICATION-TYPE
VRC out-fan speed clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23002current
vrcCompPtCapacityCLEAR
NOTIFICATION-TYPE
VRC compressor capacity clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23003current
vrcReturnPtTempCLEAR
NOTIFICATION-TYPE
VRC return temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23004current
vrcSupplyPtTempCLEAR
NOTIFICATION-TYPE
VRC supply temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23005current
vrcPowerPtVoltageCLEAR
NOTIFICATION-TYPE
VRC power voltage clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23006current
vrcPowerPtFrequencyCLEAR
NOTIFICATION-TYPE
VRC power frequency clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23007current
vrcOutdoorPtTempCLEAR
NOTIFICATION-TYPE
VRC outdoor temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23008current
vrcDischPtTempCLEAR
NOTIFICATION-TYPE
VRC discharge temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23009current
vrcDischPtPressureCLEAR
NOTIFICATION-TYPE
VRC discharge pressure clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23010current
vrcSuctPtTempCLEAR
NOTIFICATION-TYPE
VRC suction temperature clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23011current
vrcSuctPtPressureCLEAR
NOTIFICATION-TYPE
VRC suction pressure clear trap
1.3.6.1.4.1.21239.5.2.32767.0.23012current