VERTIV-V5-MIB
- Registered at
- 1.3.6.1.4.1.21239
- Last updated
- 2020-01-07 00:00
- Organization
- Vertiv
- Revisions
- 2020-01-07 00:00, 2019-09-30 00:00, 2019-09-12 00:00, 2019-08-30 00:00, 2019-06-06 00:00, 2019-05-07 00:00, 2019-04-30 00:00, 2019-03-07 00:00, 2018-01-19 00:00, 2017-09-19 00:00, 2017-08-10 00:00, 2017-05-10 00:00, 2017-04-05 00:00, 2016-06-30 00:00, 2012-09-11 00:00
- Namespace
- vertiv
- Source file
VERTIV-V5-MIB- Digest
sha256:70c7fa0d3d8518af5717df78dc0702097776d790f964e5b8c82a6a5ec3f42d38
Description
The MIB for Vertiv products
Contact
support@geistglobal.com
Imports
| From | Symbols |
|---|---|
| SNMP-FRAMEWORK-MIB | SnmpAdminString |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-MIB | sysName |
| SNMPv2-SMI | Gauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, MacAddress, TEXTUAL-CONVENTION, TruthValue |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
SNMP-FRAMEWORK-MIB SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC VERTIV-V5-MIB
Under this module's arcs
Where the registration tree carries on below this module.
| Arc | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.21239.2 | geistV3 | GEIST-MIB-V3 |
| 1.3.6.1.4.1.21239.5 | blackbird |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| v5 OBJECT-IDENTITY | 1.3.6.1.4.1.21239.5 | |||
| imd OBJECT-IDENTITY | 1.3.6.1.4.1.21239.5.2 | |||
| deviceInfo OBJECT-IDENTITY | 1.3.6.1.4.1.21239.5.2.1 | |||
| productTitle OBJECT-TYPE Product name | 1.3.6.1.4.1.21239.5.2.1.1 | SnmpAdminString | read-only | current |
| productVersion OBJECT-TYPE Product version | 1.3.6.1.4.1.21239.5.2.1.2 | SnmpAdminString | read-only | current |
| productFriendlyName OBJECT-TYPE User-assigned name | 1.3.6.1.4.1.21239.5.2.1.3 | SnmpAdminString | read-only | current |
| productMacAddress OBJECT-TYPE Product's unique MAC address | 1.3.6.1.4.1.21239.5.2.1.4 | MacAddress | read-only | current |
| deviceCount OBJECT-TYPE Total number of devices on unit | 1.3.6.1.4.1.21239.5.2.1.6 | Integer32 (0..16) | read-only | current |
| temperatureUnits OBJECT-TYPE Current units for temperature/dewpoint values: 0 = Degrees Fahrenheit 1 = Degrees Celsius | 1.3.6.1.4.1.21239.5.2.1.7 | INTEGER {fahrenheit(0), celsius(1)} | read-write | current |
| productModelNumber OBJECT-TYPE Product model number (factory-assigned) | 1.3.6.1.4.1.21239.5.2.1.8 | SnmpAdminString | read-only | current |
| productPartNumber OBJECT-TYPE Product part number (factory-assigned) | 1.3.6.1.4.1.21239.5.2.1.9 | SnmpAdminString | read-only | current |
| productSerialNumber OBJECT-TYPE Product serial number (factory-assigned) | 1.3.6.1.4.1.21239.5.2.1.10 | SnmpAdminString | read-only | current |
| productPlatform OBJECT-TYPE Product platform | 1.3.6.1.4.1.21239.5.2.1.11 | SnmpAdminString | read-only | current |
| productHostname OBJECT-TYPE Product hostname | 1.3.6.1.4.1.21239.5.2.1.12 | SnmpAdminString | read-only | current |
| productAlarmCount OBJECT-TYPE Number of alarms currently tripped | 1.3.6.1.4.1.21239.5.2.1.13 | Integer32 | read-only | current |
| productWarnCount OBJECT-TYPE Number of warnings currently tripped | 1.3.6.1.4.1.21239.5.2.1.14 | Integer32 | read-only | current |
| productManufacturer OBJECT-TYPE Product manufacturer | 1.3.6.1.4.1.21239.5.2.1.15 | SnmpAdminString | read-only | current |
| pdu OBJECT-IDENTITY | 1.3.6.1.4.1.21239.5.2.3 | |||
| pduMainTable OBJECT-TYPE PDU general information | 1.3.6.1.4.1.21239.5.2.3.1 | not-accessible | current | |
| pduMainEntry OBJECT-TYPE Entry in the pduMainTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.3.1.1 | not-accessible | current | |
| pduMainIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.3.1.1.1 | Integer32 (1..100) | not-accessible | current |
| pduMainSerial OBJECT-TYPE Serial number | 1.3.6.1.4.1.21239.5.2.3.1.1.2 | DisplayString | read-only | current |
| pduMainName OBJECT-TYPE PDU name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.3.1.1.3 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| pduMainLabel OBJECT-TYPE PDU label (user-defined) | 1.3.6.1.4.1.21239.5.2.3.1.1.4 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| pduMainAvail OBJECT-TYPE Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable | 1.3.6.1.4.1.21239.5.2.3.1.1.5 | Gauge32 | read-only | current |
| pduMeterType OBJECT-TYPE Current meter type: 0 = Wye 1 = Delta | 1.3.6.1.4.1.21239.5.2.3.1.1.6 | INTEGER {wye(0), delta(1)} | read-only | current |
| pduTotalName OBJECT-TYPE Total name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.3.1.1.7 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| pduTotalLabel OBJECT-TYPE Total label (user-defined) | 1.3.6.1.4.1.21239.5.2.3.1.1.8 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| pduTotalRealPower OBJECT-TYPE PDU total real power | 1.3.6.1.4.1.21239.5.2.3.1.1.9 | Gauge32 (0..9999) | read-only | current |
| pduTotalApparentPower OBJECT-TYPE PDU total apparent power | 1.3.6.1.4.1.21239.5.2.3.1.1.10 | Gauge32 (0..9999) | read-only | current |
| pduTotalPowerFactor OBJECT-TYPE PDU total power factor | 1.3.6.1.4.1.21239.5.2.3.1.1.11 | Gauge32 (0..100) | read-only | current |
| pduTotalEnergy OBJECT-TYPE PDU total accumulated energy in watt-hours | 1.3.6.1.4.1.21239.5.2.3.1.1.12 | Gauge32 (0..9999000) | read-only | current |
| pduPhaseTable OBJECT-TYPE PDU phases information | 1.3.6.1.4.1.21239.5.2.3.2 | not-accessible | current | |
| pduPhaseEntry OBJECT-TYPE Entry in the pduPhaseTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.3.2.1 | not-accessible | current | |
| pduPhaseIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.3.2.1.1 | Integer32 (1..100) | not-accessible | current |
| pduPhaseName OBJECT-TYPE PDU phase name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.3.2.1.2 | SnmpAdminString (SIZE(0..25)) | read-only | current |
| pduPhaseLabel OBJECT-TYPE PDU phase label (user-defined) | 1.3.6.1.4.1.21239.5.2.3.2.1.3 | SnmpAdminString (SIZE(1..25)) | read-write | current |
| pduPhaseVoltage OBJECT-TYPE PDU phase voltage in tenths of a volt | 1.3.6.1.4.1.21239.5.2.3.2.1.4 | Gauge32 (0..3100) | read-only | current |
| pduPhaseCurrent OBJECT-TYPE PDU phase current reading in hundredths of an amp | 1.3.6.1.4.1.21239.5.2.3.2.1.8 | Gauge32 (0..9900) | read-only | current |
| pduPhaseRealPower OBJECT-TYPE Real power for phase in watts | 1.3.6.1.4.1.21239.5.2.3.2.1.12 | Gauge32 (0..9999) | read-only | current |
| pduPhaseApparentPower OBJECT-TYPE Apparent power for phase in volt-amps | 1.3.6.1.4.1.21239.5.2.3.2.1.13 | Gauge32 (0..9999) | read-only | current |
| pduPhasePowerFactor OBJECT-TYPE Power factor for phase | 1.3.6.1.4.1.21239.5.2.3.2.1.14 | Gauge32 (0..100) | read-only | current |
| pduPhaseEnergy OBJECT-TYPE Accumulated energy for phase in watt-hours | 1.3.6.1.4.1.21239.5.2.3.2.1.15 | Gauge32 (0..9999000) | read-only | current |
| pduPhaseBalance OBJECT-TYPE Phase balance as percent | 1.3.6.1.4.1.21239.5.2.3.2.1.17 | Gauge32 (0..100) | read-only | current |
| pduPhaseCurrentCrestFactor OBJECT-TYPE Current crest factor for phase, in hundredths | 1.3.6.1.4.1.21239.5.2.3.2.1.19 | Gauge32 (0..9999) | read-only | current |
| pduBreakerTable OBJECT-TYPE PDU breaker information | 1.3.6.1.4.1.21239.5.2.3.3 | not-accessible | current | |
| pduBreakerEntry OBJECT-TYPE Entry in the pduBreakerTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.3.3.1 | not-accessible | current | |
| pduBreakerIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.3.3.1.1 | Integer32 (1..100) | not-accessible | current |
| pduBreakerName OBJECT-TYPE PDU breaker name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.3.3.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| pduBreakerLabel OBJECT-TYPE PDU breaker label (user-defined) | 1.3.6.1.4.1.21239.5.2.3.3.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| pduBreakerCurrent OBJECT-TYPE PDU breaker current reading in hundredths of an amp | 1.3.6.1.4.1.21239.5.2.3.3.1.4 | Gauge32 (0..9900) | read-only | current |
| pduBreakerVoltage OBJECT-TYPE PDU breaker voltage in tenths of a volt. This object may not exist on all platforms, due to hardware differences. | 1.3.6.1.4.1.21239.5.2.3.3.1.8 | Gauge32 (0..3100) | read-only | current |
| pduBreakerRealPower OBJECT-TYPE Real power for breaker in watts. This object may not exist on all platforms, due to hardware differences. | 1.3.6.1.4.1.21239.5.2.3.3.1.12 | Gauge32 (0..9999) | read-only | current |
| pduBreakerApparentPower OBJECT-TYPE Apparent power for breaker in volt-amps. This object may not exist on all platforms, due to hardware differences. | 1.3.6.1.4.1.21239.5.2.3.3.1.13 | Gauge32 (0..9999) | read-only | current |
| pduBreakerPowerFactor OBJECT-TYPE Power factor for breaker. This object may not exist on all platforms, due to hardware differences. | 1.3.6.1.4.1.21239.5.2.3.3.1.14 | Gauge32 (0..100) | read-only | current |
| pduBreakerEnergy OBJECT-TYPE Accumulated energy for breaker in watt-hours. This object may not exist on all platforms, due to hardware differences. | 1.3.6.1.4.1.21239.5.2.3.3.1.15 | Gauge32 (0..9999000) | read-only | current |
| pduLineTable OBJECT-TYPE PDU line current information | 1.3.6.1.4.1.21239.5.2.3.4 | not-accessible | current | |
| pduLineEntry OBJECT-TYPE Entry in the pduLineTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.3.4.1 | not-accessible | current | |
| pduLineIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.3.4.1.1 | Integer32 (1..100) | not-accessible | current |
| pduLineName OBJECT-TYPE PDU line name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.3.4.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| pduLineLabel OBJECT-TYPE PDU line label (user-defined) | 1.3.6.1.4.1.21239.5.2.3.4.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| pduLineCurrent OBJECT-TYPE PDU line current reading in hundredths of an amp | 1.3.6.1.4.1.21239.5.2.3.4.1.4 | Gauge32 (0..9900) | read-only | current |
| pduOutletSwitchTable OBJECT-TYPE Data, config and control for outlets with switching | 1.3.6.1.4.1.21239.5.2.3.5 | not-accessible | current | |
| pduOutletSwitchEntry OBJECT-TYPE Entry in the pduOutletSwitchTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.3.5.1 | not-accessible | current | |
| pduOutletSwitchIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.3.5.1.1 | Integer32 (1..100) | not-accessible | current |
| pduOutletSwitchName OBJECT-TYPE PDU outlet name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.3.5.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| pduOutletSwitchLabel OBJECT-TYPE PDU outlet label (user-defined) | 1.3.6.1.4.1.21239.5.2.3.5.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| pduOutletSwitchState OBJECT-TYPE Switch state of the outlet: 1 = Outlet is on 2 = Outlet is off 3 = Outlet is on, but will turn off after a delay 4 = Outlet is off, but will turn on after a delay 5 = Starting reboot cycle, outlet is on, but will go to the rebootOff(6) state after a delay 6 = Rebooting, outlet is off, but it will turn on after a delay 7 = Cannot get outlet state | 1.3.6.1.4.1.21239.5.2.3.5.1.4 | INTEGER {on(1), off(2), on2off(3), off2on(4), rebootOn(5), rebootOff(6), unavailable(7)} | read-only | current |
| pduOutletSwitchRelayFailure OBJECT-TYPE Tells if the outlet relay has failed. In normal operation, the value will be false(2). | 1.3.6.1.4.1.21239.5.2.3.5.1.5 | TruthValue | read-only | current |
| pduOutletSwitchControl OBJECT-TYPE Used for manual control of the outlet. If the outlet is in manual mode, this field can be set to one of the following values: 1 = Cancel pending operation 2 = Turn outlet on 3 = After delay (pduOutletSwitchOnDelay), turn outlet on 4 = Turn outlet off 5 = After delay (pduOutletSwitchOffDelay), turn outlet off 6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn outlet back on 7 = After delay (pduOutletSwitchRebootDelay), reboot outlet When not in manual mode, setting this field will give an inconsistentValue error. Returns none(8) for all get requests. | 1.3.6.1.4.1.21239.5.2.3.5.1.6 | INTEGER {cancel(1), on(2), onAfterDelay(3), off(4), offAfterDelay(5), reboot(6), rebootAfterDelay(7), none(8)} | read-write | current |
| pduOutletSwitchTimeToAction OBJECT-TYPE Seconds until an outlet state change. The value of pduOutletSwitchState tells what state the outlet will be set, after the delay. | 1.3.6.1.4.1.21239.5.2.3.5.1.7 | Integer32 (0..600) | read-only | current |
| pduOutletSwitchOnDelay OBJECT-TYPE Seconds to wait before powering on the outlet, during onAfterDelay(3) operation. Changing this value has no effect on pending actions. | 1.3.6.1.4.1.21239.5.2.3.5.1.8 | Integer32 (0..600) | read-write | current |
| pduOutletSwitchOffDelay OBJECT-TYPE Seconds to wait before powering off the outlet, during offAfterDelay(5) operation. Changing this value has no effect on pending actions. | 1.3.6.1.4.1.21239.5.2.3.5.1.9 | Integer32 (0..600) | read-write | current |
| pduOutletSwitchRebootDelay OBJECT-TYPE Seconds to wait before powering off the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info. | 1.3.6.1.4.1.21239.5.2.3.5.1.10 | Integer32 (0..600) | read-write | current |
| pduOutletSwitchRebootHoldDelay OBJECT-TYPE Seconds to hold the outlet off, before powering on the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info. | 1.3.6.1.4.1.21239.5.2.3.5.1.11 | Integer32 (0..600) | read-write | current |
| pduOutletSwitchPoaAction OBJECT-TYPE The outlet is set to this state during power-up. The action can be have one the following values: 1 = Outlet will be turned on 2 = Outlet will stay off 3 = Outlet will be set to last known state | 1.3.6.1.4.1.21239.5.2.3.5.1.12 | INTEGER {on(1), off(2), last(3)} | read-write | current |
| pduOutletSwitchPoaDelay OBJECT-TYPE Seconds to wait before setting the outlet to the pduOutletSwitchPoaAction state. The delay starts at power-up. | 1.3.6.1.4.1.21239.5.2.3.5.1.13 | Integer32 (0..600) | read-write | current |
| pduOutletMeterTable OBJECT-TYPE Metering data for outlets that support this feature | 1.3.6.1.4.1.21239.5.2.3.6 | not-accessible | current | |
| pduOutletMeterEntry OBJECT-TYPE Entry in the pduOutletMeterTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.3.6.1 | not-accessible | current | |
| pduOutletMeterIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.3.6.1.1 | Integer32 (1..100) | not-accessible | current |
| pduOutletMeterName OBJECT-TYPE PDU outlet name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.3.6.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| pduOutletMeterLabel OBJECT-TYPE PDU outlet label (user-defined) | 1.3.6.1.4.1.21239.5.2.3.6.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| pduOutletMeterVoltage OBJECT-TYPE PDU outlet voltage in tenths of a volt | 1.3.6.1.4.1.21239.5.2.3.6.1.4 | Gauge32 (0..3100) | read-only | current |
| pduOutletMeterCurrent OBJECT-TYPE PDU outlet current reading in hundredths of an amp | 1.3.6.1.4.1.21239.5.2.3.6.1.8 | Gauge32 (0..9900) | read-only | current |
| pduOutletMeterRealPower OBJECT-TYPE Real power for outlet in watts | 1.3.6.1.4.1.21239.5.2.3.6.1.12 | Gauge32 (0..9999) | read-only | current |
| pduOutletMeterApparentPower OBJECT-TYPE Apparent power for outlet in volt-amps | 1.3.6.1.4.1.21239.5.2.3.6.1.13 | Gauge32 (0..9999) | read-only | current |
| pduOutletMeterPowerFactor OBJECT-TYPE Power factor for outlet | 1.3.6.1.4.1.21239.5.2.3.6.1.14 | Gauge32 (0..100) | read-only | current |
| pduOutletMeterEnergy OBJECT-TYPE Accumulated energy for outlet in watt-hours | 1.3.6.1.4.1.21239.5.2.3.6.1.15 | Gauge32 (0..9999000) | read-only | current |
| pduOutletMeterReset OBJECT-TYPE Used to reset energy. If read, the value is none(8). It can be set to resetEnergy(1), which sets outlet energy to 0 | 1.3.6.1.4.1.21239.5.2.3.6.1.16 | INTEGER {resetEnergy(1), none(8)} | read-write | current |
| pduOutletCurrentCrestFactor OBJECT-TYPE Current crest factor for outlet, in hundredths | 1.3.6.1.4.1.21239.5.2.3.6.1.19 | Gauge32 (0..9999) | read-only | current |
| tempSensorTable OBJECT-TYPE Remote Temperature (RT) sensor | 1.3.6.1.4.1.21239.5.2.4 | not-accessible | current | |
| tempSensorEntry OBJECT-TYPE Entry in the tempSensorTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.4.1 | not-accessible | current | |
| tempSensorIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.4.1.1 | Integer32 (1..100) | not-accessible | current |
| tempSensorSerial OBJECT-TYPE Serial number | 1.3.6.1.4.1.21239.5.2.4.1.2 | DisplayString | read-only | current |
| tempSensorLabel OBJECT-TYPE User-defined label | 1.3.6.1.4.1.21239.5.2.4.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| tempSensorAvail OBJECT-TYPE Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable | 1.3.6.1.4.1.21239.5.2.4.1.4 | Gauge32 | read-only | current |
| tempSensorTemp OBJECT-TYPE Temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.4.1.5 | Integer32 (-400..2540) | read-only | current |
| airFlowSensorTable OBJECT-TYPE Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor | 1.3.6.1.4.1.21239.5.2.5 | not-accessible | current | |
| airFlowSensorEntry OBJECT-TYPE Entry in the airFlowSensorTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.5.1 | not-accessible | current | |
| airFlowSensorIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.5.1.1 | Integer32 (1..100) | not-accessible | current |
| airFlowSensorSerial OBJECT-TYPE Serial number | 1.3.6.1.4.1.21239.5.2.5.1.2 | DisplayString | read-only | current |
| airFlowSensorLabel OBJECT-TYPE User-defined label | 1.3.6.1.4.1.21239.5.2.5.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| airFlowSensorAvail OBJECT-TYPE Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable | 1.3.6.1.4.1.21239.5.2.5.1.4 | Gauge32 | read-only | current |
| airFlowSensorTemp OBJECT-TYPE Temperature reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.5.1.5 | Integer32 (-400..2540) | read-only | current |
| airFlowSensorFlow OBJECT-TYPE Airflow reading. Still air will be less than 20, while rushing air will be around 100. | 1.3.6.1.4.1.21239.5.2.5.1.6 | Integer32 (0..100) | read-only | current |
| airFlowSensorHumidity OBJECT-TYPE Humidity reading | 1.3.6.1.4.1.21239.5.2.5.1.7 | Integer32 (0..100) | read-only | current |
| airFlowSensorDewPoint OBJECT-TYPE Dewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.5.1.8 | Integer32 (-400..2540) | read-only | current |
| t3hdSensorTable OBJECT-TYPE Remote Temperature x 3, Humidity and Dewpoint Sensor | 1.3.6.1.4.1.21239.5.2.8 | not-accessible | current | |
| t3hdSensorEntry OBJECT-TYPE Entry in the t3hdSensorTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.8.1 | not-accessible | current | |
| t3hdSensorIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.8.1.1 | Integer32 (1..100) | not-accessible | current |
| t3hdSensorSerial OBJECT-TYPE Serial number | 1.3.6.1.4.1.21239.5.2.8.1.2 | DisplayString | read-only | current |
| t3hdSensorLabel OBJECT-TYPE User-defined label | 1.3.6.1.4.1.21239.5.2.8.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| t3hdSensorAvail OBJECT-TYPE Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable | 1.3.6.1.4.1.21239.5.2.8.1.4 | Gauge32 | read-only | current |
| t3hdSensorIntLabel OBJECT-TYPE Internal label (user-defined) | 1.3.6.1.4.1.21239.5.2.8.1.5 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| t3hdSensorIntTemp OBJECT-TYPE Internal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.8.1.6 | Integer32 (-400..2540) | read-only | current |
| t3hdSensorIntHumidity OBJECT-TYPE Internal humidity | 1.3.6.1.4.1.21239.5.2.8.1.7 | Integer32 (0..100) | read-only | current |
| t3hdSensorIntDewPoint OBJECT-TYPE Internal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.8.1.8 | Integer32 (-400..2540) | read-only | current |
| t3hdSensorExtAAvail OBJECT-TYPE External A status: 0 = Unavailable 1 = Available | 1.3.6.1.4.1.21239.5.2.8.1.9 | Gauge32 | read-only | current |
| t3hdSensorExtALabel OBJECT-TYPE External A label (user-defined) | 1.3.6.1.4.1.21239.5.2.8.1.10 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| t3hdSensorExtATemp OBJECT-TYPE External A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.8.1.11 | Integer32 (-400..2540) | read-only | current |
| t3hdSensorExtBAvail OBJECT-TYPE External B status: 0 = Unavailable 1 = Available | 1.3.6.1.4.1.21239.5.2.8.1.12 | Gauge32 | read-only | current |
| t3hdSensorExtBLabel OBJECT-TYPE External B label (user-defined) | 1.3.6.1.4.1.21239.5.2.8.1.13 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| t3hdSensorExtBTemp OBJECT-TYPE External B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.8.1.14 | Integer32 (-400..2540) | read-only | current |
| thdSensorTable OBJECT-TYPE Remote Temperature, Humidity, and Dewpoint (THD) Sensor | 1.3.6.1.4.1.21239.5.2.9 | not-accessible | current | |
| thdSensorEntry OBJECT-TYPE Entry in the thdSensorTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.9.1 | not-accessible | current | |
| thdSensorIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.9.1.1 | Integer32 (1..100) | not-accessible | current |
| thdSensorSerial OBJECT-TYPE Serial number | 1.3.6.1.4.1.21239.5.2.9.1.2 | DisplayString | read-only | current |
| thdSensorLabel OBJECT-TYPE User-defined label | 1.3.6.1.4.1.21239.5.2.9.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| thdSensorAvail OBJECT-TYPE Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable | 1.3.6.1.4.1.21239.5.2.9.1.4 | Gauge32 | read-only | current |
| thdSensorTemp OBJECT-TYPE Temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.9.1.5 | Integer32 (-400..2540) | read-only | current |
| thdSensorHumidity OBJECT-TYPE Humidity value | 1.3.6.1.4.1.21239.5.2.9.1.6 | Integer32 (0..100) | read-only | current |
| thdSensorDewPoint OBJECT-TYPE Dewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.9.1.7 | Integer32 (-400..2540) | read-only | current |
| a2dSensorTable OBJECT-TYPE Analog measurement (A2D) sensor (voltage, current, or dry-contact) | 1.3.6.1.4.1.21239.5.2.11 | not-accessible | current | |
| a2dSensorEntry OBJECT-TYPE Entry in the a2dSensorTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.11.1 | not-accessible | current | |
| a2dSensorIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.11.1.1 | Integer32 (1..100) | not-accessible | current |
| a2dSensorSerial OBJECT-TYPE Serial number | 1.3.6.1.4.1.21239.5.2.11.1.2 | DisplayString | read-only | current |
| a2dSensorLabel OBJECT-TYPE User-defined label | 1.3.6.1.4.1.21239.5.2.11.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| a2dSensorAvail OBJECT-TYPE Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable | 1.3.6.1.4.1.21239.5.2.11.1.4 | Gauge32 | read-only | current |
| a2dSensorValue OBJECT-TYPE Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode. | 1.3.6.1.4.1.21239.5.2.11.1.5 | Integer32 (-1000000..1000000) | read-only | current |
| a2dSensorDisplayValue OBJECT-TYPE For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue. | 1.3.6.1.4.1.21239.5.2.11.1.6 | SnmpAdminString (SIZE(0..25)) | read-only | current |
| a2dSensorMode OBJECT-TYPE Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMax. Analog modes: 1 = Door (binary) 2 = Power failure (binary) 3 = Flood (binary) 4 = Water-sensing cable leak (binary) 5 = Water-sensing cable fault (binary) 6 = Smoke alarm (binary) 7 = Isolated voltage negative ground (voltage) 8 = Isolated voltage positive ground (voltage) 9 = Custom voltage (voltage) 10 = Custom binary (binary) 11 = Custom current (current) | 1.3.6.1.4.1.21239.5.2.11.1.7 | INTEGER {door(1), powerFailure(2), flood(3), wscLeak(4), wscFault(5), smoke(6), ivsNegGnd(7), ivsPosGnd(8), customVoltage(9), customBinary(10), customCurrent(11)} | read-write | current |
| a2dSensorUnits OBJECT-TYPE The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode. | 1.3.6.1.4.1.21239.5.2.11.1.8 | SnmpAdminString (SIZE(0..7)) | read-write | current |
| a2dSensorMin OBJECT-TYPE Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode. | 1.3.6.1.4.1.21239.5.2.11.1.9 | Integer32 (-1000000..1000000) | read-write | current |
| a2dSensorMax OBJECT-TYPE Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode. | 1.3.6.1.4.1.21239.5.2.11.1.10 | Integer32 (-1000000..1000000) | read-write | current |
| a2dSensorLowLabel OBJECT-TYPE Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode. | 1.3.6.1.4.1.21239.5.2.11.1.11 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| a2dSensorHighLabel OBJECT-TYPE Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode. | 1.3.6.1.4.1.21239.5.2.11.1.12 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| a2dSensorAnalogLabel OBJECT-TYPE Label for the analog measurement | 1.3.6.1.4.1.21239.5.2.11.1.13 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| humiditySensorTable OBJECT-TYPE Remote humidity sensor | 1.3.6.1.4.1.21239.5.2.12 | not-accessible | current | |
| humiditySensorEntry OBJECT-TYPE Entry in the humiditySensorTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.12.1 | not-accessible | current | |
| humiditySensorIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.12.1.1 | Integer32 (1..100) | not-accessible | current |
| humiditySensorSerial OBJECT-TYPE Serial number | 1.3.6.1.4.1.21239.5.2.12.1.2 | DisplayString | read-only | current |
| humiditySensorLabel OBJECT-TYPE User-defined label | 1.3.6.1.4.1.21239.5.2.12.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| humiditySensorAvail OBJECT-TYPE Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable | 1.3.6.1.4.1.21239.5.2.12.1.4 | Gauge32 | read-only | current |
| humiditySensorValue OBJECT-TYPE Humidity value | 1.3.6.1.4.1.21239.5.2.12.1.5 | Integer32 (0..100) | read-only | current |
| sn2dSensorTable OBJECT-TYPE 2 Door Switch Sensor (SN-2D) | 1.3.6.1.4.1.21239.5.2.13 | not-accessible | current | |
| sn2dSensorEntry OBJECT-TYPE Entry in the sn2dSensorTable table: each entry contains an index and other sensor details | 1.3.6.1.4.1.21239.5.2.13.1 | not-accessible | current | |
| sn2dSensorIndex OBJECT-TYPE Table entry index value | 1.3.6.1.4.1.21239.5.2.13.1.1 | Integer32 (1..100) | not-accessible | current |
| sn2dSensorSerial OBJECT-TYPE Serial number | 1.3.6.1.4.1.21239.5.2.13.1.2 | DisplayString | read-only | current |
| sn2dSensorLabel OBJECT-TYPE User-defined label | 1.3.6.1.4.1.21239.5.2.13.1.3 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| sn2dSensorAvail OBJECT-TYPE Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable | 1.3.6.1.4.1.21239.5.2.13.1.4 | Gauge32 | read-only | current |
| sn2dSensorDoor1Label OBJECT-TYPE Door switch 1 label | 1.3.6.1.4.1.21239.5.2.13.1.5 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| sn2dSensorDoor1State OBJECT-TYPE Door switch 1 state: 1 = open 2 = closed | 1.3.6.1.4.1.21239.5.2.13.1.6 | INTEGER {open(1), closed(2)} | read-only | current |
| sn2dSensorDoor1DisplayState OBJECT-TYPE Door switch 1 state given as a string | 1.3.6.1.4.1.21239.5.2.13.1.7 | SnmpAdminString (SIZE(0..25)) | read-only | current |
| sn2dSensorDoor2Label OBJECT-TYPE Door switch 2 label | 1.3.6.1.4.1.21239.5.2.13.1.8 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| sn2dSensorDoor2State OBJECT-TYPE Door switch 2 state: 1 = open 2 = closed | 1.3.6.1.4.1.21239.5.2.13.1.9 | INTEGER {open(1), closed(2)} | read-only | current |
| sn2dSensorDoor2DisplayState OBJECT-TYPE Door switch 2 state given as a string | 1.3.6.1.4.1.21239.5.2.13.1.10 | SnmpAdminString (SIZE(0..25)) | read-only | current |
| cooling OBJECT-IDENTITY | 1.3.6.1.4.1.21239.5.2.30 | |||
| vrc OBJECT-IDENTITY | 1.3.6.1.4.1.21239.5.2.30.1 | |||
| vrcMainTable OBJECT-TYPE Table that contains general VRC information | 1.3.6.1.4.1.21239.5.2.30.1.1 | not-accessible | current | |
| vrcMainEntry OBJECT-TYPE Entry in the vrcMainTable: each entry represents a VRC device | 1.3.6.1.4.1.21239.5.2.30.1.1.1 | not-accessible | current | |
| vrcMainIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.1.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcMainSerial OBJECT-TYPE Serial number | 1.3.6.1.4.1.21239.5.2.30.1.1.1.2 | DisplayString | read-only | current |
| vrcMainName OBJECT-TYPE VRC name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.1.1.3 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcMainLabel OBJECT-TYPE VRC label (user-defined) | 1.3.6.1.4.1.21239.5.2.30.1.1.1.4 | SnmpAdminString (SIZE(0..25)) | read-write | current |
| vrcMainAvail OBJECT-TYPE Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable | 1.3.6.1.4.1.21239.5.2.30.1.1.1.5 | Gauge32 | read-only | current |
| vrcMainPtTable OBJECT-TYPE Table that contains general VRC status | 1.3.6.1.4.1.21239.5.2.30.1.2 | not-accessible | current | |
| vrcMainPtEntry OBJECT-TYPE Entry in the vrcMainPtTable: each entry contains status data for a VRC device | 1.3.6.1.4.1.21239.5.2.30.1.2.1 | not-accessible | current | |
| vrcMainPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.2.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcMainPtRunState OBJECT-TYPE VRC run state: 1 = on 2 = off | 1.3.6.1.4.1.21239.5.2.30.1.2.1.2 | INTEGER {on(1), off(2)} | read-only | current |
| vrcMainPtEevOpened OBJECT-TYPE Eev opened value (percent) | 1.3.6.1.4.1.21239.5.2.30.1.2.1.3 | Integer32 (0..100) | read-only | current |
| vrcMainPtAlarmNumbers OBJECT-TYPE Alarm numbers value | 1.3.6.1.4.1.21239.5.2.30.1.2.1.4 | Integer32 (-32768..32767) | read-only | current |
| vrcMainPtHistoryAlarmNumbers OBJECT-TYPE History alarm numbers value | 1.3.6.1.4.1.21239.5.2.30.1.2.1.5 | Integer32 (-32768..32767) | read-only | current |
| vrcMainPtHpAbnRecordCnt OBJECT-TYPE Hp Abnormal record count | 1.3.6.1.4.1.21239.5.2.30.1.2.1.6 | Integer32 (-32768..32767) | read-only | current |
| vrcMainPtMonitorBaudrate OBJECT-TYPE Monitor baud rate: 1 = error 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200 | 1.3.6.1.4.1.21239.5.2.30.1.2.1.7 | INTEGER {error(1), baud1200(2), baud2400(3), baud4800(4), baud9600(5), baud19200(6)} | read-only | current |
| vrcMainPtMonitorAddress OBJECT-TYPE Monitor address | 1.3.6.1.4.1.21239.5.2.30.1.2.1.8 | Integer32 (1..247) | read-only | current |
| vrcMainPtLp OBJECT-TYPE Lp status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.9 | TruthValue | read-only | current |
| vrcMainPtFilterMaintRemind OBJECT-TYPE Filter maintenance reminder status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.10 | TruthValue | read-only | current |
| vrcMainPtCoolingFlag OBJECT-TYPE Cooling flag | 1.3.6.1.4.1.21239.5.2.30.1.2.1.11 | TruthValue | read-only | current |
| vrcMainPtFirstOnFlag OBJECT-TYPE First on flag | 1.3.6.1.4.1.21239.5.2.30.1.2.1.12 | TruthValue | read-only | current |
| vrcMainPtNewAlarmFlag OBJECT-TYPE New alarm flag | 1.3.6.1.4.1.21239.5.2.30.1.2.1.13 | TruthValue | read-only | current |
| vrcMainPtComAlarmOutState OBJECT-TYPE Common alarm output state | 1.3.6.1.4.1.21239.5.2.30.1.2.1.14 | TruthValue | read-only | current |
| vrcMainPtHighWaterInput OBJECT-TYPE High water input | 1.3.6.1.4.1.21239.5.2.30.1.2.1.15 | TruthValue | read-only | current |
| vrcMainPtHighWaterAlarm OBJECT-TYPE High water alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.16 | TruthValue | read-only | current |
| vrcMainPtWaterUnderFloorAlarm OBJECT-TYPE Water under floor alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.17 | TruthValue | read-only | current |
| vrcMainPtSwShutDownStatus OBJECT-TYPE Software shutdown status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.18 | TruthValue | read-only | current |
| vrcMainPtRemoteShutdown OBJECT-TYPE Remote shutdown status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.19 | TruthValue | read-only | current |
| vrcMainPtRemoteShutDownFlag OBJECT-TYPE Remote shutdown flag | 1.3.6.1.4.1.21239.5.2.30.1.2.1.20 | TruthValue | read-only | current |
| vrcMainPtRemoteShutDownAlarm OBJECT-TYPE Remote shutdown alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.21 | TruthValue | read-only | current |
| vrcMainPtHmiShutDownFlag OBJECT-TYPE Hmi shutdown flag | 1.3.6.1.4.1.21239.5.2.30.1.2.1.22 | TruthValue | read-only | current |
| vrcMainPtLpAlarm OBJECT-TYPE Low pressure alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.23 | TruthValue | read-only | current |
| vrcMainPtHpAlarm OBJECT-TYPE High pressure alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.24 | TruthValue | read-only | current |
| vrcMainPtLpFreqAlarm OBJECT-TYPE Low pressure frequently alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.25 | TruthValue | read-only | current |
| vrcMainPtHpFreqAlarm OBJECT-TYPE High pressure frequently alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.26 | TruthValue | read-only | current |
| vrcMainPtLpSensorFailAlarm OBJECT-TYPE Low pressure sensor failure alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.27 | TruthValue | read-only | current |
| vrcMainPtHpSensorFailAlarm OBJECT-TYPE High pressure sensor failure alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.28 | TruthValue | read-only | current |
| vrcMainPtEevCommFailAlarm OBJECT-TYPE Eev communication failure alarm status | 1.3.6.1.4.1.21239.5.2.30.1.2.1.29 | TruthValue | read-only | current |
| vrcMainCfgTable OBJECT-TYPE Table that contains general VRC configuration | 1.3.6.1.4.1.21239.5.2.30.1.3 | not-accessible | current | |
| vrcMainCfgEntry OBJECT-TYPE Entry in the vrcMainCfgTable: each entry contains general config fields for a VRC device | 1.3.6.1.4.1.21239.5.2.30.1.3.1 | not-accessible | current | |
| vrcMainCfgIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.3.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcMainCfgModelSelect OBJECT-TYPE Model Selection: 1 = TMM-Local 220V 50/60HZ 2 = TMM-Global 208/230V 50/60HZ 3 = TMM-Global 120V 50/60HZ 4 = SC 220V 50/60HZ 5 = 0U 220V 50/60HZ 6 = SS 208/230V 50/60HZ 7 = SS 120V 50/60HZ | 1.3.6.1.4.1.21239.5.2.30.1.3.1.2 | INTEGER {tmLoc(1), r035Ap(2), r035Ak(3), scLoc(4), zeroULoc(5), r035Ep(6), r035Ek(7)} | read-write | current |
| vrcMainCfgSystemTimeYear OBJECT-TYPE System time - year | 1.3.6.1.4.1.21239.5.2.30.1.3.1.3 | Integer32 (2000..2099) | read-write | current |
| vrcMainCfgSystemTimeMonth OBJECT-TYPE System time - month | 1.3.6.1.4.1.21239.5.2.30.1.3.1.4 | Integer32 (1..12) | read-write | current |
| vrcMainCfgSystemTimeDay OBJECT-TYPE System time - day | 1.3.6.1.4.1.21239.5.2.30.1.3.1.5 | Integer32 (1..31) | read-write | current |
| vrcMainCfgSystemTimeHour OBJECT-TYPE System time - hour | 1.3.6.1.4.1.21239.5.2.30.1.3.1.6 | Integer32 (0..23) | read-write | current |
| vrcMainCfgSystemTimeMin OBJECT-TYPE System time - minutes | 1.3.6.1.4.1.21239.5.2.30.1.3.1.7 | Integer32 (0..59) | read-write | current |
| vrcMainCfgSystemTimeSec OBJECT-TYPE System time - seconds | 1.3.6.1.4.1.21239.5.2.30.1.3.1.8 | Integer32 (0..59) | read-write | current |
| vrcMainCfgEevShtSettingMin OBJECT-TYPE Min Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359 | 1.3.6.1.4.1.21239.5.2.30.1.3.1.9 | Integer32 | read-write | current |
| vrcMainCfgEevShtSettingMax OBJECT-TYPE Max Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359 | 1.3.6.1.4.1.21239.5.2.30.1.3.1.10 | Integer32 | read-write | current |
| vrcMainCfgEevValveCloseSht OBJECT-TYPE Eev valve close sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 100 Fahrenheit: 0 to 179 | 1.3.6.1.4.1.21239.5.2.30.1.3.1.11 | Integer32 | read-write | current |
| vrcMainCfgEevMopPressSetting OBJECT-TYPE Eev mop pressure setting in tenths of a bar. | 1.3.6.1.4.1.21239.5.2.30.1.3.1.12 | Integer32 (0..200) | read-write | current |
| vrcMainCfgLpdt OBJECT-TYPE Low pressure dt in seconds | 1.3.6.1.4.1.21239.5.2.30.1.3.1.13 | Integer32 (30..600) | read-write | current |
| vrcMainCfgDeadBand OBJECT-TYPE Dead band in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 20 Fahrenheit: 0 to 35 | 1.3.6.1.4.1.21239.5.2.30.1.3.1.14 | Integer32 | read-write | current |
| vrcMainCfgOnOffSwitch OBJECT-TYPE On-off switch | 1.3.6.1.4.1.21239.5.2.30.1.3.1.15 | TruthValue | read-write | current |
| vrcMainCfgVacuumState OBJECT-TYPE Vacuum state | 1.3.6.1.4.1.21239.5.2.30.1.3.1.16 | TruthValue | read-write | current |
| vrcMainCfgControlMode OBJECT-TYPE Control mode: 1 = supply 2 = return | 1.3.6.1.4.1.21239.5.2.30.1.3.1.17 | INTEGER {supply(1), return(2)} | read-write | current |
| vrcMainCfgManualRunEnable OBJECT-TYPE Manual run enable | 1.3.6.1.4.1.21239.5.2.30.1.3.1.18 | TruthValue | read-write | current |
| vrcMainCfgRemShutdownInput OBJECT-TYPE Remote shutdown input | 1.3.6.1.4.1.21239.5.2.30.1.3.1.19 | TruthValue | read-write | current |
| vrcMainCfgMonitorShutDownFlag OBJECT-TYPE Monitor shutdown flag | 1.3.6.1.4.1.21239.5.2.30.1.3.1.20 | TruthValue | read-write | current |
| vrcMainCfgFirstOnPassword OBJECT-TYPE First on password value | 1.3.6.1.4.1.21239.5.2.30.1.3.1.21 | Integer32 (-32768..32767) | read-write | current |
| vrcMainCfgFilterMaintSetting OBJECT-TYPE Filter maintenance setting | 1.3.6.1.4.1.21239.5.2.30.1.3.1.22 | TruthValue | read-write | current |
| vrcMainCfgFilterMaintRemindTime OBJECT-TYPE Time between filter maintenance reminders in days | 1.3.6.1.4.1.21239.5.2.30.1.3.1.23 | Integer32 (30..360) | read-write | current |
| vrcMainCfgFilterMaintRemindCtrl OBJECT-TYPE Filter maintenance reminder: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.24 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcMainCfgCommonAlarmOutputDir OBJECT-TYPE Common alarm output direction | 1.3.6.1.4.1.21239.5.2.30.1.3.1.25 | TruthValue | read-write | current |
| vrcMainCfgHpAbnAlarmSetting OBJECT-TYPE Abnormal high pressure alarm value in tenths of a bar | 1.3.6.1.4.1.21239.5.2.30.1.3.1.26 | Integer32 (300..360) | read-write | current |
| vrcMainCfgLpAlarmCtrl OBJECT-TYPE Low pressure alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.27 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcMainCfgHpAlarmCtrl OBJECT-TYPE High pressure alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.28 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcMainCfgLpFreqAlarmCtrl OBJECT-TYPE Low pressure frequently alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.29 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcMainCfgHpFreqAlarmCtrl OBJECT-TYPE High pressure frequently alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.30 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcMainCfgLpSensorFailAlarmCtrl OBJECT-TYPE Low pressure sensor failure alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.31 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcMainCfgHpSensorFailAlarmCtrl OBJECT-TYPE High pressure sensor failure alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.32 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcMainCfgHighWaterAlarmCtrl OBJECT-TYPE High water alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.33 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcMainCfgRemShutdownAlarmCtrl OBJECT-TYPE Remote shutdown alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.34 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcMainCfgEevCommFailAlarmCtrl OBJECT-TYPE Eev communication failure alarm: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.3.1.35 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcOutFanPtTable OBJECT-TYPE Table that contains VRC out-fan status | 1.3.6.1.4.1.21239.5.2.30.1.4 | not-accessible | current | |
| vrcOutFanPtEntry OBJECT-TYPE Entry in the vrcOutFanPtTable: each entry represents data for a VRC out-fan | 1.3.6.1.4.1.21239.5.2.30.1.4.1 | not-accessible | current | |
| vrcOutFanPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.4.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcOutFanPtName OBJECT-TYPE Out-fan name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.4.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcOutFanPtSpeed OBJECT-TYPE Fan speed (percent) | 1.3.6.1.4.1.21239.5.2.30.1.4.1.3 | Integer32 (0..100) | read-only | current |
| vrcOutFanCfgTable OBJECT-TYPE Table used for VRC out-fan configuration | 1.3.6.1.4.1.21239.5.2.30.1.5 | not-accessible | current | |
| vrcOutFanCfgEntry OBJECT-TYPE Entry in the vrcOutFanCfgTable: each entry contains config fields for a VRC out-fan | 1.3.6.1.4.1.21239.5.2.30.1.5.1 | not-accessible | current | |
| vrcOutFanCfgIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.5.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcOutFanCfgStartPress OBJECT-TYPE Out-fan start pressure in tenths of a bar | 1.3.6.1.4.1.21239.5.2.30.1.5.1.2 | Integer32 (190..250) | read-write | current |
| vrcOutFanCfgPressSetting OBJECT-TYPE Out-fan pressure setting in tenths of a bar | 1.3.6.1.4.1.21239.5.2.30.1.5.1.3 | Integer32 (50..80) | read-write | current |
| vrcOutFanCfgMinPowerVoltage OBJECT-TYPE Min out-fan voltage (percent) | 1.3.6.1.4.1.21239.5.2.30.1.5.1.4 | Integer32 (30..50) | read-write | current |
| vrcOutFanCfgMaxPowerVoltage OBJECT-TYPE Max out-fan voltage (percent) | 1.3.6.1.4.1.21239.5.2.30.1.5.1.5 | Integer32 (60..100) | read-write | current |
| vrcOutFanCfgSpeed OBJECT-TYPE Out-fan speed (percent) | 1.3.6.1.4.1.21239.5.2.30.1.5.1.6 | Integer32 (0..100) | read-write | current |
| vrcInFanPtTable OBJECT-TYPE Table that contains VRC in-fan status | 1.3.6.1.4.1.21239.5.2.30.1.6 | not-accessible | current | |
| vrcInFanPtEntry OBJECT-TYPE Entry in the vrcInFanPtTable: each entry represents data for a VRC in- fan | 1.3.6.1.4.1.21239.5.2.30.1.6.1 | not-accessible | current | |
| vrcInFanPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.6.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcInFanPtName OBJECT-TYPE In-fan name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.6.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcInFanPtRunTimeHours OBJECT-TYPE In-fan run time in hours | 1.3.6.1.4.1.21239.5.2.30.1.6.1.3 | Integer32 (-32768..32767) | read-only | current |
| vrcInFanPtStartStopCount OBJECT-TYPE In-fan start/stop count | 1.3.6.1.4.1.21239.5.2.30.1.6.1.4 | Integer32 (-32768..32767) | read-only | current |
| vrcInFanCfgTable OBJECT-TYPE Table used for VRC in-fan configuration | 1.3.6.1.4.1.21239.5.2.30.1.7 | not-accessible | current | |
| vrcInFanCfgEntry OBJECT-TYPE Entry in the vrcInFanCfgTable: each entry contains config fields for a VRC in-fan | 1.3.6.1.4.1.21239.5.2.30.1.7.1 | not-accessible | current | |
| vrcInFanCfgIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.7.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcInFanCfgOutputStatus OBJECT-TYPE In-fan output status | 1.3.6.1.4.1.21239.5.2.30.1.7.1.2 | TruthValue | read-write | current |
| vrcInFanCfgLowSpeedStep OBJECT-TYPE In-fan low speed step in tenths of a percent per second | 1.3.6.1.4.1.21239.5.2.30.1.7.1.3 | Integer32 (1..20) | read-write | current |
| vrcInFanCfgHighSpeedStep OBJECT-TYPE In-fan high speed step in tenths of a percent per second | 1.3.6.1.4.1.21239.5.2.30.1.7.1.4 | Integer32 (1..50) | read-write | current |
| vrcInFanCfgMinSpeed OBJECT-TYPE Min in-fan speed (percent) | 1.3.6.1.4.1.21239.5.2.30.1.7.1.5 | Integer32 (30..80) | read-write | current |
| vrcInFanCfgStandardSpeed OBJECT-TYPE Standard in-fan speed (percent) | 1.3.6.1.4.1.21239.5.2.30.1.7.1.6 | Integer32 (80..100) | read-write | current |
| vrcInFanCfgMinCfc OBJECT-TYPE Min in-fan cfc (percent) | 1.3.6.1.4.1.21239.5.2.30.1.7.1.7 | Integer32 (0..30) | read-write | current |
| vrcInFanCfgStandardCfc OBJECT-TYPE Standard in-fan cfc (percent) | 1.3.6.1.4.1.21239.5.2.30.1.7.1.8 | Integer32 (85..100) | read-write | current |
| vrcInFanCfgStartDelay OBJECT-TYPE In-fan start delay in seconds | 1.3.6.1.4.1.21239.5.2.30.1.7.1.9 | Integer32 (10..600) | read-write | current |
| vrcInFanCfgStopDelay OBJECT-TYPE In-fan stop delay in seconds | 1.3.6.1.4.1.21239.5.2.30.1.7.1.10 | Integer32 (10..300) | read-write | current |
| vrcInFanCfgReduceSpeedDelay OBJECT-TYPE In-fan reduce speed delay in seconds | 1.3.6.1.4.1.21239.5.2.30.1.7.1.11 | Integer32 (0..300) | read-write | current |
| vrcInFanCfgJumpBand1 OBJECT-TYPE In-fan jump band 1 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.12 | Integer32 (0..100) | read-write | current |
| vrcInFanCfgJumpBand2 OBJECT-TYPE In-fan jump band 2 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.13 | Integer32 (0..100) | read-write | current |
| vrcInFanCfgJumpBand3 OBJECT-TYPE In-fan jump band 3 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.14 | Integer32 (0..100) | read-write | current |
| vrcInFanCfgJumpBand4 OBJECT-TYPE In-fan jump band 4 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.15 | Integer32 (0..100) | read-write | current |
| vrcInFanCfgJumpBand5 OBJECT-TYPE In-fan jump band 5 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.16 | Integer32 (0..100) | read-write | current |
| vrcInFanCfgJumpFreq1 OBJECT-TYPE In-fan jump frequency 1 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.17 | Integer32 (0..1000) | read-write | current |
| vrcInFanCfgJumpFreq2 OBJECT-TYPE In-fan jump frequency 2 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.18 | Integer32 (0..1000) | read-write | current |
| vrcInFanCfgJumpFreq3 OBJECT-TYPE In-fan jump frequency 3 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.19 | Integer32 (0..1000) | read-write | current |
| vrcInFanCfgJumpFreq4 OBJECT-TYPE In-fan jump frequency 4 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.20 | Integer32 (0..1000) | read-write | current |
| vrcInFanCfgJumpFreq5 OBJECT-TYPE In-fan jump frequency 5 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.7.1.21 | Integer32 (0..1000) | read-write | current |
| vrcInFanCfgTempP OBJECT-TYPE In-fan temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. | 1.3.6.1.4.1.21239.5.2.30.1.7.1.22 | Integer32 (10..150) | read-write | current |
| vrcInFanCfgTempI OBJECT-TYPE In-fan temperature I in seconds | 1.3.6.1.4.1.21239.5.2.30.1.7.1.23 | Integer32 (0..900) | read-write | current |
| vrcInFanCfgTempD OBJECT-TYPE In-fan temperature D in seconds | 1.3.6.1.4.1.21239.5.2.30.1.7.1.24 | Integer32 (0..900) | read-write | current |
| vrcCompPtTable OBJECT-TYPE Table that contains VRC compressor status | 1.3.6.1.4.1.21239.5.2.30.1.8 | not-accessible | current | |
| vrcCompPtEntry OBJECT-TYPE Entry in the vrcCompPtTable: each entry represents data for a VRC compressor | 1.3.6.1.4.1.21239.5.2.30.1.8.1 | not-accessible | current | |
| vrcCompPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.8.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcCompPtName OBJECT-TYPE Compressor name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.8.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcCompPtCapacity OBJECT-TYPE Compressor capacity value (percent) | 1.3.6.1.4.1.21239.5.2.30.1.8.1.3 | Integer32 (0..100) | read-only | current |
| vrcCompPtRunTimeHours OBJECT-TYPE Compressor run time in hours | 1.3.6.1.4.1.21239.5.2.30.1.8.1.4 | Integer32 (-32768..32767) | read-only | current |
| vrcCompPtStartStopCount OBJECT-TYPE Compressor start/stop count | 1.3.6.1.4.1.21239.5.2.30.1.8.1.5 | Integer32 (-32768..32767) | read-only | current |
| vrcCompPtDriverFaultU00 OBJECT-TYPE Compressor driver fault alarm U00 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.6 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU01 OBJECT-TYPE Compressor driver fault alarm U01 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.7 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU02 OBJECT-TYPE Compressor driver fault alarm U02 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.8 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU03 OBJECT-TYPE Compressor driver fault alarm U03 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.9 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU04 OBJECT-TYPE Compressor driver fault alarm U04 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.10 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU05 OBJECT-TYPE Compressor driver fault alarm U05 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.11 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU06 OBJECT-TYPE Compressor driver fault alarm U06 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.12 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU07 OBJECT-TYPE Compressor driver fault alarm U07 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.13 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU08 OBJECT-TYPE Compressor driver fault alarm U08 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.14 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU09 OBJECT-TYPE Compressor driver fault alarm U09 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.15 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU10 OBJECT-TYPE Compressor driver fault alarm U10 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.16 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU11 OBJECT-TYPE Compressor driver fault alarm U11 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.17 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU12 OBJECT-TYPE Compressor driver fault alarm U12 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.18 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU13 OBJECT-TYPE Compressor driver fault alarm U13 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.19 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU14 OBJECT-TYPE Compressor driver fault alarm U14 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.20 | TruthValue | read-only | current |
| vrcCompPtDriverFaultU15 OBJECT-TYPE Compressor driver fault alarm U15 state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.21 | TruthValue | read-only | current |
| vrcCompPtDriverCommFailAlarm OBJECT-TYPE Compressor driver communication failure alarm state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.22 | TruthValue | read-only | current |
| vrcCompPtFaultLockAlarm OBJECT-TYPE Compressor fault lock alarm state | 1.3.6.1.4.1.21239.5.2.30.1.8.1.23 | TruthValue | read-only | current |
| vrcCompCfgTable OBJECT-TYPE Table used for VRC compressor configuration | 1.3.6.1.4.1.21239.5.2.30.1.9 | not-accessible | current | |
| vrcCompCfgEntry OBJECT-TYPE Entry in the vrcCompCfgTable: each entry contains config fields for a VRC compressor | 1.3.6.1.4.1.21239.5.2.30.1.9.1 | not-accessible | current | |
| vrcCompCfgIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.9.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcCompCfgOutputStatus OBJECT-TYPE Compressor output status | 1.3.6.1.4.1.21239.5.2.30.1.9.1.2 | TruthValue | read-write | current |
| vrcCompCfgOutputDeadBand OBJECT-TYPE Compressor output dead band in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.3 | Integer32 (0..50) | read-write | current |
| vrcCompCfgCapacityOutputValue OBJECT-TYPE Compressor capacity output (percent) | 1.3.6.1.4.1.21239.5.2.30.1.9.1.4 | Integer32 (0..100) | read-write | current |
| vrcCompCfgMinCapacity OBJECT-TYPE Compressor min capacity (percent) | 1.3.6.1.4.1.21239.5.2.30.1.9.1.5 | Integer32 (15..50) | read-write | current |
| vrcCompCfgStartCapacity OBJECT-TYPE Compressor start capacity (percent) | 1.3.6.1.4.1.21239.5.2.30.1.9.1.6 | Integer32 (40..100) | read-write | current |
| vrcCompCfgStandardCapacity OBJECT-TYPE Compressor standard capacity (percent) | 1.3.6.1.4.1.21239.5.2.30.1.9.1.7 | Integer32 (80..100) | read-write | current |
| vrcCompCfgStartCfc OBJECT-TYPE Compressor start cfc (percent) | 1.3.6.1.4.1.21239.5.2.30.1.9.1.8 | Integer32 (1..100) | read-write | current |
| vrcCompCfgStopCfc OBJECT-TYPE Compressor stop cfc (percent) | 1.3.6.1.4.1.21239.5.2.30.1.9.1.9 | Integer32 (-200..-50) | read-write | current |
| vrcCompCfgMinRunTime OBJECT-TYPE Compressor min run time in minutes | 1.3.6.1.4.1.21239.5.2.30.1.9.1.10 | Integer32 (0..30) | read-write | current |
| vrcCompCfgMinStopTime OBJECT-TYPE Compressor min stop time in minutes | 1.3.6.1.4.1.21239.5.2.30.1.9.1.11 | Integer32 (0..10) | read-write | current |
| vrcCompCfgJumpBand1 OBJECT-TYPE Compressor jump band 1 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.12 | Integer32 (0..100) | read-write | current |
| vrcCompCfgJumpBand2 OBJECT-TYPE Compressor jump band 2 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.13 | Integer32 (0..100) | read-write | current |
| vrcCompCfgJumpBand3 OBJECT-TYPE Compressor jump band 3 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.14 | Integer32 (0..100) | read-write | current |
| vrcCompCfgJumpBand4 OBJECT-TYPE Compressor jump band 4 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.15 | Integer32 (0..100) | read-write | current |
| vrcCompCfgJumpBand5 OBJECT-TYPE Compressor jump band 5 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.16 | Integer32 (0..100) | read-write | current |
| vrcCompCfgJumpFreq1 OBJECT-TYPE Compressor jump frequency 1 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.17 | Integer32 (0..1000) | read-write | current |
| vrcCompCfgJumpFreq2 OBJECT-TYPE Compressor jump frequency 2 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.18 | Integer32 (0..1000) | read-write | current |
| vrcCompCfgJumpFreq3 OBJECT-TYPE Compressor jump frequency 3 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.19 | Integer32 (0..1000) | read-write | current |
| vrcCompCfgJumpFreq4 OBJECT-TYPE Compressor jump frequency 4 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.20 | Integer32 (0..1000) | read-write | current |
| vrcCompCfgJumpFreq5 OBJECT-TYPE Compressor jump frequency 5 in tenths of a percent | 1.3.6.1.4.1.21239.5.2.30.1.9.1.21 | Integer32 (0..1000) | read-write | current |
| vrcCompCfgTempP OBJECT-TYPE Compressor temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 10 to 150 Fahrenheit: 18 to 269 | 1.3.6.1.4.1.21239.5.2.30.1.9.1.22 | Integer32 | read-write | current |
| vrcCompCfgTempI OBJECT-TYPE Compressor temperature I in seconds | 1.3.6.1.4.1.21239.5.2.30.1.9.1.23 | Integer32 (0..900) | read-write | current |
| vrcCompCfgTempD OBJECT-TYPE Compressor temperature D in seconds | 1.3.6.1.4.1.21239.5.2.30.1.9.1.24 | Integer32 (0..900) | read-write | current |
| vrcCompCfgDriverFaultAlmCtrl OBJECT-TYPE Compressor driver fault alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.9.1.25 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcCompCfgDriverCommFailAlmCtrl OBJECT-TYPE Compressor driver communication failure alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.9.1.26 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcCompCfgFaultLockAlmCtrl OBJECT-TYPE Compressor fault lock alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.9.1.27 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcReturnPtTable OBJECT-TYPE Table that contains VRC return status | 1.3.6.1.4.1.21239.5.2.30.1.10 | not-accessible | current | |
| vrcReturnPtEntry OBJECT-TYPE Entry in the vrcReturnPtTable: each entry represents return data for a VRC | 1.3.6.1.4.1.21239.5.2.30.1.10.1 | not-accessible | current | |
| vrcReturnPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.10.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcReturnPtName OBJECT-TYPE Return name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.10.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcReturnPtTemp OBJECT-TYPE Return temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120 | 1.3.6.1.4.1.21239.5.2.30.1.10.1.3 | Integer32 | read-only | current |
| vrcReturnPtHighTempAlarm OBJECT-TYPE Return high temperature alarm state | 1.3.6.1.4.1.21239.5.2.30.1.10.1.4 | TruthValue | read-only | current |
| vrcReturnPtTempSensorFailAlarm OBJECT-TYPE Return temperature sensor failure alarm state | 1.3.6.1.4.1.21239.5.2.30.1.10.1.5 | TruthValue | read-only | current |
| vrcReturnCfgTable OBJECT-TYPE Table used for VRC return configuration | 1.3.6.1.4.1.21239.5.2.30.1.11 | not-accessible | current | |
| vrcReturnCfgEntry OBJECT-TYPE Entry in the vrcReturnCfgTable: each entry contains config fields for VRC return | 1.3.6.1.4.1.21239.5.2.30.1.11.1 | not-accessible | current | |
| vrcReturnCfgIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.11.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcReturnCfgOilCycle OBJECT-TYPE Return oil cycle in tenths of an hour | 1.3.6.1.4.1.21239.5.2.30.1.11.1.2 | Integer32 (5..50) | read-write | current |
| vrcReturnCfgOilRunCapacity OBJECT-TYPE Return Oil run capacity (percent) | 1.3.6.1.4.1.21239.5.2.30.1.11.1.3 | Integer32 (50..100) | read-write | current |
| vrcReturnCfgOilRunTime OBJECT-TYPE Return oil run time in minutes | 1.3.6.1.4.1.21239.5.2.30.1.11.1.4 | Integer32 (0..10) | read-write | current |
| vrcReturnCfgTempCalValue OBJECT-TYPE Return temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179 | 1.3.6.1.4.1.21239.5.2.30.1.11.1.5 | Integer32 | read-write | current |
| vrcReturnCfgTempSetting OBJECT-TYPE Return temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 250 to 350 Fahrenheit: 770 to 949 | 1.3.6.1.4.1.21239.5.2.30.1.11.1.6 | Integer32 | read-write | current |
| vrcReturnCfgHighTempAlarmValue OBJECT-TYPE Return high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 300 to 450 Fahrenheit: 860 to 1129 | 1.3.6.1.4.1.21239.5.2.30.1.11.1.7 | Integer32 | read-write | current |
| vrcReturnCfgHighTempAlarmCtrl OBJECT-TYPE Return high temperature alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.11.1.8 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcReturnCfgTempSensFailAlmCtrl OBJECT-TYPE Return temperature sensor failure alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.11.1.9 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcSupplyPtTable OBJECT-TYPE Table that contains VRC supply status | 1.3.6.1.4.1.21239.5.2.30.1.12 | not-accessible | current | |
| vrcSupplyPtEntry OBJECT-TYPE Entry in the vrcSupplyPtTable: each entry represents supply data for a VRC | 1.3.6.1.4.1.21239.5.2.30.1.12.1 | not-accessible | current | |
| vrcSupplyPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.12.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcSupplyPtName OBJECT-TYPE Supply name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.12.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcSupplyPtTemp OBJECT-TYPE Supply temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120 | 1.3.6.1.4.1.21239.5.2.30.1.12.1.3 | Integer32 | read-only | current |
| vrcSupplyPtLowTempAlarm OBJECT-TYPE Supply low temperature alarm state | 1.3.6.1.4.1.21239.5.2.30.1.12.1.4 | TruthValue | read-only | current |
| vrcSupplyPtHighTempAlarm OBJECT-TYPE Supply high temperature alarm state | 1.3.6.1.4.1.21239.5.2.30.1.12.1.5 | TruthValue | read-only | current |
| vrcSupplyPtTempSensorFailAlarm OBJECT-TYPE Supply temperature sensor failure alarm state | 1.3.6.1.4.1.21239.5.2.30.1.12.1.6 | TruthValue | read-only | current |
| vrcSupplyCfgTable OBJECT-TYPE Table used for VRC supply configuration | 1.3.6.1.4.1.21239.5.2.30.1.13 | not-accessible | current | |
| vrcSupplyCfgEntry OBJECT-TYPE Entry in the vrcSupplyCfgTable: each entry contains config fields for a VRC supply | 1.3.6.1.4.1.21239.5.2.30.1.13.1 | not-accessible | current | |
| vrcSupplyCfgIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.13.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcSupplyCfgTempCalValue OBJECT-TYPE Supply temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179 | 1.3.6.1.4.1.21239.5.2.30.1.13.1.2 | Integer32 | read-write | current |
| vrcSupplyCfgTempSetting OBJECT-TYPE Supply temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 130 to 280 Fahrenheit: 554 to 823 | 1.3.6.1.4.1.21239.5.2.30.1.13.1.3 | Integer32 | read-write | current |
| vrcSupplyCfgLowTempAlarmValue OBJECT-TYPE Supply low temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 410 to 679 | 1.3.6.1.4.1.21239.5.2.30.1.13.1.4 | Integer32 | read-write | current |
| vrcSupplyCfgHighTempAlarmValue OBJECT-TYPE Supply high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 200 to 350 Fahrenheit: 680 to 949 | 1.3.6.1.4.1.21239.5.2.30.1.13.1.5 | Integer32 | read-write | current |
| vrcSupplyCfgLowTempAlmCtrl OBJECT-TYPE Supply low temperature alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.13.1.6 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcSupplyCfgHighTempAlmCtrl OBJECT-TYPE Supply high temperature alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.13.1.7 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcSupplyCfgTempSensFailAlmCtrl OBJECT-TYPE Supply temperature sensor failure alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.13.1.8 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcPowerPtTable OBJECT-TYPE Table that contains VRC power status | 1.3.6.1.4.1.21239.5.2.30.1.14 | not-accessible | current | |
| vrcPowerPtEntry OBJECT-TYPE Entry in the vrcPowerPtTable: each entry represents power data for a VRC | 1.3.6.1.4.1.21239.5.2.30.1.14.1 | not-accessible | current | |
| vrcPowerPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.14.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcPowerPtName OBJECT-TYPE Power name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.14.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcPowerPtVoltage OBJECT-TYPE Power voltage measurement in tenths of a volt | 1.3.6.1.4.1.21239.5.2.30.1.14.1.3 | Integer32 (-32768..32767) | read-only | current |
| vrcPowerPtFrequency OBJECT-TYPE Power frequency measurement in tenths of hertz | 1.3.6.1.4.1.21239.5.2.30.1.14.1.4 | Integer32 (-32768..32767) | read-only | current |
| vrcPowerPtLowVoltageAlarm OBJECT-TYPE Power low voltage alarm state | 1.3.6.1.4.1.21239.5.2.30.1.14.1.5 | TruthValue | read-only | current |
| vrcPowerPtHighVoltageAlarm OBJECT-TYPE Power high voltage alarm state | 1.3.6.1.4.1.21239.5.2.30.1.14.1.6 | TruthValue | read-only | current |
| vrcPowerPtLossOfPhasePowerAlarm OBJECT-TYPE Phase power loss alarm state | 1.3.6.1.4.1.21239.5.2.30.1.14.1.7 | TruthValue | read-only | current |
| vrcPowerPtLossOfPowerAlarm OBJECT-TYPE Power loss alarm state | 1.3.6.1.4.1.21239.5.2.30.1.14.1.8 | TruthValue | read-only | current |
| vrcPowerPtFrequencyErrorAlarm OBJECT-TYPE Power frequency error alarm state | 1.3.6.1.4.1.21239.5.2.30.1.14.1.9 | TruthValue | read-only | current |
| vrcPowerCfgTable OBJECT-TYPE Table used for VRC power configuration | 1.3.6.1.4.1.21239.5.2.30.1.15 | not-accessible | current | |
| vrcPowerCfgEntry OBJECT-TYPE Entry in the vrcPowerCfgTable: each entry contains config fields for VRC power | 1.3.6.1.4.1.21239.5.2.30.1.15.1 | not-accessible | current | |
| vrcPowerCfgIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.15.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcPowerCfgLowVoltageSetting OBJECT-TYPE Power low voltage setting in volts | 1.3.6.1.4.1.21239.5.2.30.1.15.1.2 | Integer32 (100..230) | read-write | current |
| vrcPowerCfgHighVoltageSetting OBJECT-TYPE Power high voltage setting in volts | 1.3.6.1.4.1.21239.5.2.30.1.15.1.3 | Integer32 (100..300) | read-write | current |
| vrcPowerCfgLowVoltageAlarmCtrl OBJECT-TYPE Power low voltage alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.15.1.4 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcPowerCfgHighVoltageAlarmCtrl OBJECT-TYPE Power high voltage alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.15.1.5 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcPowerCfgLossOfPowerAlarmCtrl OBJECT-TYPE Power loss alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.15.1.6 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcPowerCfgFreqErrorAlarmCtrl OBJECT-TYPE Power frequency error alarm control: 1 = close 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.15.1.7 | INTEGER {close(1), suspend(2), open(3)} | read-write | current |
| vrcOutdoorPtTable OBJECT-TYPE Table that contains VRC outdoor status | 1.3.6.1.4.1.21239.5.2.30.1.16 | not-accessible | current | |
| vrcOutdoorPtEntry OBJECT-TYPE Entry in the vrcOutdoorPtTable: each entry represents data for a VRC outdoor | 1.3.6.1.4.1.21239.5.2.30.1.16.1 | not-accessible | current | |
| vrcOutdoorPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.16.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcOutdoorPtName OBJECT-TYPE Outdoor name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.16.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcOutdoorPtTemp OBJECT-TYPE Outdoor temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120 | 1.3.6.1.4.1.21239.5.2.30.1.16.1.3 | Integer32 | read-only | current |
| vrcDischPtTable OBJECT-TYPE Table that contains VRC discharge status | 1.3.6.1.4.1.21239.5.2.30.1.18 | not-accessible | current | |
| vrcDischPtEntry OBJECT-TYPE Entry in the vrcDischPtTable: each entry represents discharge data for a VRC | 1.3.6.1.4.1.21239.5.2.30.1.18.1 | not-accessible | current | |
| vrcDischPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.18.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcDischPtName OBJECT-TYPE Discharge name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.18.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcDischPtTemp OBJECT-TYPE Discharge temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1560 Fahrenheit: -400 to 3128 | 1.3.6.1.4.1.21239.5.2.30.1.18.1.3 | Integer32 | read-write | current |
| vrcDischPtPressure OBJECT-TYPE Discharge air pressure value in tenths of a bar | 1.3.6.1.4.1.21239.5.2.30.1.18.1.4 | Integer32 (0..460) | read-write | current |
| vrcDischPtHighTempAlarm OBJECT-TYPE Discharge high temperature alarm state | 1.3.6.1.4.1.21239.5.2.30.1.18.1.5 | TruthValue | read-only | current |
| vrcDischPtHighTempFreqAlarm OBJECT-TYPE Discharge high temperature frequently alarm state | 1.3.6.1.4.1.21239.5.2.30.1.18.1.6 | TruthValue | read-only | current |
| vrcDischPtTempSensorFailAlarm OBJECT-TYPE Discharge temperature sensor failure alarm state | 1.3.6.1.4.1.21239.5.2.30.1.18.1.7 | TruthValue | read-only | current |
| vrcDischCfgTable OBJECT-TYPE Table used for VRC discharge configuration | 1.3.6.1.4.1.21239.5.2.30.1.19 | not-accessible | current | |
| vrcDischCfgEntry OBJECT-TYPE Entry in the vrcDischCfgTable: each entry contains config fields for VRC discharge | 1.3.6.1.4.1.21239.5.2.30.1.19.1 | not-accessible | current | |
| vrcDischCfgIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.19.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcDischCfgTempCalValue OBJECT-TYPE Discharge temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179 | 1.3.6.1.4.1.21239.5.2.30.1.19.1.2 | Integer32 | read-write | current |
| vrcDischCfgPressCalValue OBJECT-TYPE Discharge pressure calibration value in tenths of a bar | 1.3.6.1.4.1.21239.5.2.30.1.19.1.3 | Integer32 (-100..100) | read-write | current |
| vrcDischCfgHighTempAlmCtrl OBJECT-TYPE Discharge high temperature alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.19.1.4 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcDischCfgHighTempFreqAlmCtrl OBJECT-TYPE Discharge high temperature frequenctly alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.19.1.5 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcDischCfgTempSensFailAlmCtrl OBJECT-TYPE Discharge temperature sensor failure alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.19.1.6 | INTEGER {suspend(2), open(3)} | read-write | current |
| vrcSuctPtTable OBJECT-TYPE Table that contains VRC suction status | 1.3.6.1.4.1.21239.5.2.30.1.20 | not-accessible | current | |
| vrcSuctPtEntry OBJECT-TYPE Entry in the vrcSuctPtTable: each entry represents suction data for a VRC | 1.3.6.1.4.1.21239.5.2.30.1.20.1 | not-accessible | current | |
| vrcSuctPtIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.20.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcSuctPtName OBJECT-TYPE Suction name (factory-assigned) | 1.3.6.1.4.1.21239.5.2.30.1.20.1.2 | SnmpAdminString (SIZE(1..25)) | read-only | current |
| vrcSuctPtTemp OBJECT-TYPE Suction temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120 | 1.3.6.1.4.1.21239.5.2.30.1.20.1.3 | Integer32 | read-only | current |
| vrcSuctPtPressure OBJECT-TYPE Suction air pressure in tenths of a bar | 1.3.6.1.4.1.21239.5.2.30.1.20.1.4 | Integer32 (0..173) | read-only | current |
| vrcSuctPtSuperHeatTemp OBJECT-TYPE Suction super heat temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120 | 1.3.6.1.4.1.21239.5.2.30.1.20.1.5 | Integer32 | read-only | current |
| vrcSuctPtTempSensorFailAlarm OBJECT-TYPE Suction temperature sensor failure alarm state | 1.3.6.1.4.1.21239.5.2.30.1.20.1.6 | TruthValue | read-only | current |
| vrcSuctCfgTable OBJECT-TYPE Table used for VRC suction configuration | 1.3.6.1.4.1.21239.5.2.30.1.21 | not-accessible | current | |
| vrcSuctCfgEntry OBJECT-TYPE Entry in the vrcSuctCfgTable: each entry contains config fields for VRC suction | 1.3.6.1.4.1.21239.5.2.30.1.21.1 | not-accessible | current | |
| vrcSuctCfgIndex OBJECT-TYPE Unique id for each entry in the table | 1.3.6.1.4.1.21239.5.2.30.1.21.1.1 | Integer32 (1..100) | not-accessible | current |
| vrcSuctCfgPressCalValue OBJECT-TYPE Suction pressure calibration value in tenths of a bar | 1.3.6.1.4.1.21239.5.2.30.1.21.1.2 | Integer32 (-100..100) | read-write | current |
| vrcSuctCfgTempSensFailAlmCtrl OBJECT-TYPE Suction temperature sensor failure alarm control: 2 = suspend 3 = open | 1.3.6.1.4.1.21239.5.2.30.1.21.1.3 | INTEGER {suspend(2), open(3)} | read-write | current |
| trap OBJECT-IDENTITY | 1.3.6.1.4.1.21239.5.2.32767 | |||
| trapPrefix OBJECT-IDENTITY | 1.3.6.1.4.1.21239.5.2.32767.0 | |||
| trapObj OBJECT-IDENTITY | 1.3.6.1.4.1.21239.5.2.32767.1 | |||
| trapSeverity OBJECT-TYPE Indicates the severity of the trap: 0 = None 1 = Warning 2 = Alarm | 1.3.6.1.4.1.21239.5.2.32767.1.1 | INTEGER {none(0), warning(1), alarm(2)} | accessible-for-notify | current |
| trapThreshType OBJECT-TYPE Only sent for threshold alarms. Identifies the threshold type: 1 = Low 2 = High | 1.3.6.1.4.1.21239.5.2.32767.1.2 | INTEGER {low(1), high(2)} | accessible-for-notify | current |
| common OBJECT-IDENTITY | 1.3.6.1.4.1.21239.42 | |||
| identity OBJECT-IDENTITY | 1.3.6.1.4.1.21239.42.1 | |||
| r05 OBJECT-IDENTITY Value given for sysObjectID on R-Series units | 1.3.6.1.4.1.21239.42.1.15 | current | ||
| i03 OBJECT-IDENTITY Value given for sysObjectID on IMD3 units | 1.3.6.1.4.1.21239.42.1.53 | current |
Notifications
| Name | OID | Status |
|---|---|---|
| internalTestNOTIFY NOTIFICATION-TYPE Test SNMP Trap | 1.3.6.1.4.1.21239.5.2.32767.0.10101 | current |
| pduMainAvailNOTIFY NOTIFICATION-TYPE PDU availability trap | 1.3.6.1.4.1.21239.5.2.32767.0.10305 | current |
| pduTotalRealPowerNOTIFY NOTIFICATION-TYPE PDU total real power trap | 1.3.6.1.4.1.21239.5.2.32767.0.10309 | current |
| pduTotalApparentPowerNOTIFY NOTIFICATION-TYPE PDU total apparent power trap | 1.3.6.1.4.1.21239.5.2.32767.0.10310 | current |
| pduTotalPowerFactorNOTIFY NOTIFICATION-TYPE PDU total power factor trap | 1.3.6.1.4.1.21239.5.2.32767.0.10311 | current |
| pduTotalEnergyNOTIFY NOTIFICATION-TYPE PDU total energy trap | 1.3.6.1.4.1.21239.5.2.32767.0.10312 | current |
| pduPhaseVoltageNOTIFY NOTIFICATION-TYPE PDU phase voltage trap | 1.3.6.1.4.1.21239.5.2.32767.0.10324 | current |
| pduPhaseCurrentNOTIFY NOTIFICATION-TYPE PDU phase current trap | 1.3.6.1.4.1.21239.5.2.32767.0.10328 | current |
| pduPhaseRealPowerNOTIFY NOTIFICATION-TYPE PDU phase real power trap | 1.3.6.1.4.1.21239.5.2.32767.0.10332 | current |
| pduPhaseApparentPowerNOTIFY NOTIFICATION-TYPE PDU phase apparent power trap | 1.3.6.1.4.1.21239.5.2.32767.0.10333 | current |
| pduPhasePowerFactorNOTIFY NOTIFICATION-TYPE PDU phase power factor trap | 1.3.6.1.4.1.21239.5.2.32767.0.10334 | current |
| pduPhaseEnergyNOTIFY NOTIFICATION-TYPE PDU phase energy trap | 1.3.6.1.4.1.21239.5.2.32767.0.10335 | current |
| pduPhaseBalanceNOTIFY NOTIFICATION-TYPE PDU phase balance trap | 1.3.6.1.4.1.21239.5.2.32767.0.10337 | current |
| pduPhaseCurrentCrestFactorNOTIFY NOTIFICATION-TYPE PDU phase current crest factor trap | 1.3.6.1.4.1.21239.5.2.32767.0.10339 | current |
| pduBreakerCurrentNOTIFY NOTIFICATION-TYPE PDU breaker current trap | 1.3.6.1.4.1.21239.5.2.32767.0.10354 | current |
| pduBreakerVoltageNOTIFY NOTIFICATION-TYPE PDU breaker voltage trap | 1.3.6.1.4.1.21239.5.2.32767.0.10358 | current |
| pduBreakerRealPowerNOTIFY NOTIFICATION-TYPE PDU breaker real power trap | 1.3.6.1.4.1.21239.5.2.32767.0.10362 | current |
| pduBreakerApparentPowerNOTIFY NOTIFICATION-TYPE PDU breaker apparent power trap | 1.3.6.1.4.1.21239.5.2.32767.0.10363 | current |
| pduBreakerPowerFactorNOTIFY NOTIFICATION-TYPE PDU breaker power factor trap | 1.3.6.1.4.1.21239.5.2.32767.0.10364 | current |
| pduBreakerEnergyNOTIFY NOTIFICATION-TYPE PDU breaker energy trap | 1.3.6.1.4.1.21239.5.2.32767.0.10365 | current |
| pduLineCurrentNOTIFY NOTIFICATION-TYPE PDU line current trap | 1.3.6.1.4.1.21239.5.2.32767.0.10374 | current |
| pduOutletMeterVoltageNOTIFY NOTIFICATION-TYPE PDU outlet voltage trap | 1.3.6.1.4.1.21239.5.2.32767.0.10385 | current |
| pduOutletMeterCurrentNOTIFY NOTIFICATION-TYPE PDU outlet current trap | 1.3.6.1.4.1.21239.5.2.32767.0.10389 | current |
| pduOutletMeterRealPowerNOTIFY NOTIFICATION-TYPE PDU outlet real power trap | 1.3.6.1.4.1.21239.5.2.32767.0.10393 | current |
| pduOutletMeterApparentPowerNOTIFY NOTIFICATION-TYPE PDU outlet apparent power trap | 1.3.6.1.4.1.21239.5.2.32767.0.10394 | current |
| pduOutletMeterPowerFactorNOTIFY NOTIFICATION-TYPE PDU outlet power factor trap | 1.3.6.1.4.1.21239.5.2.32767.0.10395 | current |
| pduOutletMeterEnergyNOTIFY NOTIFICATION-TYPE PDU outlet energy trap | 1.3.6.1.4.1.21239.5.2.32767.0.10396 | current |
| pduOutletCurrentCrestFactorNOTIFY NOTIFICATION-TYPE PDU outlet current crest factor trap | 1.3.6.1.4.1.21239.5.2.32767.0.10400 | current |
| tempSensorAvailNOTIFY NOTIFICATION-TYPE RT availability trap | 1.3.6.1.4.1.21239.5.2.32767.0.10404 | current |
| tempSensorTempNOTIFY NOTIFICATION-TYPE RT temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.10405 | current |
| airFlowSensorAvailNOTIFY NOTIFICATION-TYPE AFHT3 availability trap | 1.3.6.1.4.1.21239.5.2.32767.0.10504 | current |
| airFlowSensorTempNOTIFY NOTIFICATION-TYPE AFHT3 temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.10505 | current |
| airFlowSensorFlowNOTIFY NOTIFICATION-TYPE AFHT3 airflow trap | 1.3.6.1.4.1.21239.5.2.32767.0.10506 | current |
| airFlowSensorHumidityNOTIFY NOTIFICATION-TYPE AFHT3 humidity trap | 1.3.6.1.4.1.21239.5.2.32767.0.10507 | current |
| airFlowSensorDewPointNOTIFY NOTIFICATION-TYPE AFHT3 dewpoint trap | 1.3.6.1.4.1.21239.5.2.32767.0.10508 | current |
| t3hdSensorAvailNOTIFY NOTIFICATION-TYPE T3HD availability trap | 1.3.6.1.4.1.21239.5.2.32767.0.10804 | current |
| t3hdSensorIntTempNOTIFY NOTIFICATION-TYPE T3HD Internal temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.10806 | current |
| t3hdSensorIntHumidityNOTIFY NOTIFICATION-TYPE T3HD Internal humidity trap | 1.3.6.1.4.1.21239.5.2.32767.0.10807 | current |
| t3hdSensorIntDewPointNOTIFY NOTIFICATION-TYPE T3HD Internal dewpoint trap | 1.3.6.1.4.1.21239.5.2.32767.0.10808 | current |
| t3hdSensorExtATempNOTIFY NOTIFICATION-TYPE T3HD External A temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.10811 | current |
| t3hdSensorExtBTempNOTIFY NOTIFICATION-TYPE T3HD External B temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.10814 | current |
| thdSensorAvailNOTIFY NOTIFICATION-TYPE THD availability trap | 1.3.6.1.4.1.21239.5.2.32767.0.10904 | current |
| thdSensorTempNOTIFY NOTIFICATION-TYPE THD temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.10905 | current |
| thdSensorHumidityNOTIFY NOTIFICATION-TYPE THD humidity trap | 1.3.6.1.4.1.21239.5.2.32767.0.10906 | current |
| thdSensorDewPointNOTIFY NOTIFICATION-TYPE THD dewpoint trap | 1.3.6.1.4.1.21239.5.2.32767.0.10907 | current |
| a2dSensorAvailNOTIFY NOTIFICATION-TYPE A2D availability trap | 1.3.6.1.4.1.21239.5.2.32767.0.11104 | current |
| a2dSensorValueNOTIFY NOTIFICATION-TYPE A2D measurement trap | 1.3.6.1.4.1.21239.5.2.32767.0.11105 | current |
| humiditySensorAvailNOTIFY NOTIFICATION-TYPE Remote humidity availability trap | 1.3.6.1.4.1.21239.5.2.32767.0.11204 | current |
| humiditySensorValueNOTIFY NOTIFICATION-TYPE Remote humidity value trap | 1.3.6.1.4.1.21239.5.2.32767.0.11205 | current |
| sn2dSensorAvailNOTIFY NOTIFICATION-TYPE SN-2D availability trap | 1.3.6.1.4.1.21239.5.2.32767.0.11304 | current |
| sn2dSensorDoor1StateNOTIFY NOTIFICATION-TYPE SN-2D Door switch 1 state trap | 1.3.6.1.4.1.21239.5.2.32767.0.11306 | current |
| sn2dSensorDoor2StateNOTIFY NOTIFICATION-TYPE SN-2D Door switch 2 state trap | 1.3.6.1.4.1.21239.5.2.32767.0.11309 | current |
| vrcMainAvailNOTIFY NOTIFICATION-TYPE VRC availability trap | 1.3.6.1.4.1.21239.5.2.32767.0.13001 | current |
| vrcOutFanPtSpeedNOTIFY NOTIFICATION-TYPE VRC out-fan speed trap | 1.3.6.1.4.1.21239.5.2.32767.0.13002 | current |
| vrcCompPtCapacityNOTIFY NOTIFICATION-TYPE VRC compressor capacity trap | 1.3.6.1.4.1.21239.5.2.32767.0.13003 | current |
| vrcReturnPtTempNOTIFY NOTIFICATION-TYPE VRC return temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.13004 | current |
| vrcSupplyPtTempNOTIFY NOTIFICATION-TYPE VRC supply temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.13005 | current |
| vrcPowerPtVoltageNOTIFY NOTIFICATION-TYPE VRC power voltage trap | 1.3.6.1.4.1.21239.5.2.32767.0.13006 | current |
| vrcPowerPtFrequencyNOTIFY NOTIFICATION-TYPE VRC power frequency trap | 1.3.6.1.4.1.21239.5.2.32767.0.13007 | current |
| vrcOutdoorPtTempNOTIFY NOTIFICATION-TYPE VRC outdoor temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.13008 | current |
| vrcDischPtTempNOTIFY NOTIFICATION-TYPE VRC discharge temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.13009 | current |
| vrcDischPtPressureNOTIFY NOTIFICATION-TYPE VRC discharge pressure trap | 1.3.6.1.4.1.21239.5.2.32767.0.13010 | current |
| vrcSuctPtTempNOTIFY NOTIFICATION-TYPE VRC suction temperature trap | 1.3.6.1.4.1.21239.5.2.32767.0.13011 | current |
| vrcSuctPtPressureNOTIFY NOTIFICATION-TYPE VRC suction pressure trap | 1.3.6.1.4.1.21239.5.2.32767.0.13012 | current |
| pduMainAvailCLEAR NOTIFICATION-TYPE PDU availability clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20305 | current |
| pduTotalRealPowerCLEAR NOTIFICATION-TYPE PDU total real power clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20309 | current |
| pduTotalApparentPowerCLEAR NOTIFICATION-TYPE PDU total apparent power clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20310 | current |
| pduTotalPowerFactorCLEAR NOTIFICATION-TYPE PDU total power factor clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20311 | current |
| pduTotalEnergyCLEAR NOTIFICATION-TYPE PDU total energy clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20312 | current |
| pduPhaseVoltageCLEAR NOTIFICATION-TYPE PDU phase voltage clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20324 | current |
| pduPhaseCurrentCLEAR NOTIFICATION-TYPE PDU phase current clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20328 | current |
| pduPhaseRealPowerCLEAR NOTIFICATION-TYPE PDU phase real power clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20332 | current |
| pduPhaseApparentPowerCLEAR NOTIFICATION-TYPE PDU phase apparent power clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20333 | current |
| pduPhasePowerFactorCLEAR NOTIFICATION-TYPE PDU phase power factor clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20334 | current |
| pduPhaseEnergyCLEAR NOTIFICATION-TYPE PDU phase energy clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20335 | current |
| pduPhaseBalanceCLEAR NOTIFICATION-TYPE PDU phase balance clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20337 | current |
| pduPhaseCurrentCrestFactorCLEAR NOTIFICATION-TYPE PDU phase current crest factor clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20339 | current |
| pduBreakerCurrentCLEAR NOTIFICATION-TYPE PDU breaker current clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20354 | current |
| pduBreakerVoltageCLEAR NOTIFICATION-TYPE PDU breaker voltage clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20358 | current |
| pduBreakerRealPowerCLEAR NOTIFICATION-TYPE PDU breaker real power clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20362 | current |
| pduBreakerApparentPowerCLEAR NOTIFICATION-TYPE PDU breaker apparent power clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20363 | current |
| pduBreakerPowerFactorCLEAR NOTIFICATION-TYPE PDU breaker power factor clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20364 | current |
| pduBreakerEnergyCLEAR NOTIFICATION-TYPE PDU breaker energy clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20365 | current |
| pduLineCurrentCLEAR NOTIFICATION-TYPE PDU line current clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20374 | current |
| pduOutletMeterVoltageCLEAR NOTIFICATION-TYPE PDU outlet voltage clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20385 | current |
| pduOutletMeterCurrentCLEAR NOTIFICATION-TYPE PDU outlet current clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20389 | current |
| pduOutletMeterRealPowerCLEAR NOTIFICATION-TYPE PDU outlet real power clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20393 | current |
| pduOutletMeterApparentPowerCLEAR NOTIFICATION-TYPE PDU outlet apparent power clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20394 | current |
| pduOutletMeterPowerFactorCLEAR NOTIFICATION-TYPE PDU outlet power factor clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20395 | current |
| pduOutletMeterEnergyCLEAR NOTIFICATION-TYPE PDU outlet energy clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20396 | current |
| pduOutletCurrentCrestFactorCLEAR NOTIFICATION-TYPE PDU outlet current crest factor clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20400 | current |
| tempSensorAvailCLEAR NOTIFICATION-TYPE RT availability clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20404 | current |
| tempSensorTempCLEAR NOTIFICATION-TYPE RT temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20405 | current |
| airFlowSensorAvailCLEAR NOTIFICATION-TYPE AFHT3 availability clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20504 | current |
| airFlowSensorTempCLEAR NOTIFICATION-TYPE AFHT3 temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20505 | current |
| airFlowSensorFlowCLEAR NOTIFICATION-TYPE AFHT3 airflow clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20506 | current |
| airFlowSensorHumidityCLEAR NOTIFICATION-TYPE AFHT3 humidity clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20507 | current |
| airFlowSensorDewPointCLEAR NOTIFICATION-TYPE AFHT3 dewpoint clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20508 | current |
| t3hdSensorAvailCLEAR NOTIFICATION-TYPE T3HD availability clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20804 | current |
| t3hdSensorIntTempCLEAR NOTIFICATION-TYPE T3HD Internal temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20806 | current |
| t3hdSensorIntHumidityCLEAR NOTIFICATION-TYPE T3HD Internal humidity clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20807 | current |
| t3hdSensorIntDewPointCLEAR NOTIFICATION-TYPE T3HD Internal dewpoint clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20808 | current |
| t3hdSensorExtATempCLEAR NOTIFICATION-TYPE T3HD External A temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20811 | current |
| t3hdSensorExtBTempCLEAR NOTIFICATION-TYPE T3HD External B temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20814 | current |
| thdSensorAvailCLEAR NOTIFICATION-TYPE THD availability clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20904 | current |
| thdSensorTempCLEAR NOTIFICATION-TYPE THD temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20905 | current |
| thdSensorHumidityCLEAR NOTIFICATION-TYPE THD humidity clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20906 | current |
| thdSensorDewPointCLEAR NOTIFICATION-TYPE THD dewpoint clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.20907 | current |
| a2dSensorAvailCLEAR NOTIFICATION-TYPE A2D availability clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.21104 | current |
| a2dSensorValueCLEAR NOTIFICATION-TYPE A2D measurement clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.21105 | current |
| humiditySensorAvailCLEAR NOTIFICATION-TYPE Remote humidity availability clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.21204 | current |
| humiditySensorValueCLEAR NOTIFICATION-TYPE Remote humidity value clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.21205 | current |
| sn2dSensorAvailCLEAR NOTIFICATION-TYPE SN-2D availability clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.21304 | current |
| sn2dSensorDoor1StateCLEAR NOTIFICATION-TYPE SN-2D Door switch 1 state clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.21306 | current |
| sn2dSensorDoor2StateCLEAR NOTIFICATION-TYPE SN-2D Door switch 2 state clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.21309 | current |
| vrcMainAvailCLEAR NOTIFICATION-TYPE VRC availability clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23001 | current |
| vrcOutFanPtSpeedCLEAR NOTIFICATION-TYPE VRC out-fan speed clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23002 | current |
| vrcCompPtCapacityCLEAR NOTIFICATION-TYPE VRC compressor capacity clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23003 | current |
| vrcReturnPtTempCLEAR NOTIFICATION-TYPE VRC return temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23004 | current |
| vrcSupplyPtTempCLEAR NOTIFICATION-TYPE VRC supply temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23005 | current |
| vrcPowerPtVoltageCLEAR NOTIFICATION-TYPE VRC power voltage clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23006 | current |
| vrcPowerPtFrequencyCLEAR NOTIFICATION-TYPE VRC power frequency clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23007 | current |
| vrcOutdoorPtTempCLEAR NOTIFICATION-TYPE VRC outdoor temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23008 | current |
| vrcDischPtTempCLEAR NOTIFICATION-TYPE VRC discharge temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23009 | current |
| vrcDischPtPressureCLEAR NOTIFICATION-TYPE VRC discharge pressure clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23010 | current |
| vrcSuctPtTempCLEAR NOTIFICATION-TYPE VRC suction temperature clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23011 | current |
| vrcSuctPtPressureCLEAR NOTIFICATION-TYPE VRC suction pressure clear trap | 1.3.6.1.4.1.21239.5.2.32767.0.23012 | current |