VALERE-DC-POWER-MIB
- Registered at
- 1.3.6.1.4.1.13858
- Last updated
- 1905-12-02 00:00
- Organization
- Valere Power Inc.
- Namespace
- eltek
- Source file
VALERE-DC-POWER-MIB- Digest
sha256:8f13b5d5de9fd57b7b1d9120dfd81c2deba6727260fa862eeb2089a85d94f27a
Description
MIB Version 0.8 Need description here. History Add table to retrieve module inventory info MIB Version 0.7 Dec 1, 05 Fixed HP Openview error Fixed warnings generated by MG-SOFT Add table to retrieve rectifier inventory info MIB Version 0.6 Feb 10, 2004 Added additional traps. Defined Ringers and other modules. Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry This fixes errors generated by MG-SOFT mib compiler. Oct 30, 2002 initial release - version 0.4
Contact
Contact: Valere Customer Support Postal: 661 N. Plano Road, Suite 300 Richardson, TX-75081 Web: http://www.valerepower.com email: support@valerepower.com Phone 866-240-6614
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-MIB | sysUpTime |
| SNMPv2-SMI | Counter32, Gauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | AutonomousType, DisplayString, TEXTUAL-CONVENTION, TestAndIncr, TimeInterval, TimeStamp |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC VALERE-DC-POWER-MIB
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| NonNegativeInteger TEXTUAL-CONVENTION This data type is a non-negative value. | current | |||
| PositiveInteger TEXTUAL-CONVENTION This data type is a non-zero and non-negative value. | current |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| vpwrDcPowerProducts OBJECT-IDENTITY | 1.3.6.1.4.1.13858.1 | |||
| vpwrDcPowerSystem OBJECT-IDENTITY | 1.3.6.1.4.1.13858.2 | |||
| vpwrSystemIdentGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.2.1 | |||
| vpwrIdentManufacturer OBJECT-TYPE The name of the DC Power manufacturer. | 1.3.6.1.4.1.13858.2.1.1 | DisplayString (SIZE(0..31)) | read-only | current |
| vpwrIdentModel OBJECT-TYPE The DC Power Model designation. | 1.3.6.1.4.1.13858.2.1.2 | DisplayString (SIZE(0..15)) | read-only | current |
| vpwrIdentControllerVersion OBJECT-TYPE The hardware/firmware version(s). This variable may or may not have the same value as vpwrIdentAgentSoftwareVersion. | 1.3.6.1.4.1.13858.2.1.3 | DisplayString (SIZE(0..15)) | read-only | current |
| vpwrIdentAgentSoftwareVersion OBJECT-TYPE The SNMP agent software version. This variable may or may not have the same value as vpwrIdentControllerFirmwareVersion. | 1.3.6.1.4.1.13858.2.1.4 | DisplayString (SIZE(0..15)) | read-only | current |
| vpwrIdentName OBJECT-TYPE A string identifying the system. This object should be set by the administrator. | 1.3.6.1.4.1.13858.2.1.5 | DisplayString (SIZE(0..31)) | read-write | current |
| vpwrSystemIdentTable OBJECT-TYPE This table describes shelves and modules that make up the sysetm. | 1.3.6.1.4.1.13858.2.1.6 | not-accessible | current | |
| vpwrSystemIdentEntry OBJECT-TYPE An entry containing information applicable to a particular alarm. | 1.3.6.1.4.1.13858.2.1.6.1 | not-accessible | current | |
| vpwrBayIndex OBJECT-TYPE Identifies Bay number that this module belongs to. The possible values are 1 through 16 limited by vpwrSystemShelfCapacity. | 1.3.6.1.4.1.13858.2.1.6.1.1 | PositiveInteger | read-only | current |
| vpwrModuleIndex OBJECT-TYPE This object identifies the module by its position in the shelf. Module numbering is left to right starting with module 1. So, the module in the first slot has an index of 1, the next module is 2 and so on. | 1.3.6.1.4.1.13858.2.1.6.1.2 | PositiveInteger | read-only | current |
| vpwrModuleOID OBJECT-TYPE It indicates the type of the module by specifiying its OID | 1.3.6.1.4.1.13858.2.1.6.1.3 | OBJECT IDENTIFIER | read-only | current |
| vpwrModuleCurrent OBJECT-TYPE The meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Current for Rectifier module. - Not Applicable for LVD module | 1.3.6.1.4.1.13858.2.1.6.1.4 | INTEGER | read-only | current |
| vpwrModuleOperStatus OBJECT-TYPE This object indicates current over all status of the module. | 1.3.6.1.4.1.13858.2.1.6.1.5 | INTEGER {moduleStatusOK(0), moduleStatusAlarm(1), moduleStatusDisabled(2), moduleStatusRingerAOn(3), moduleStatusRingerBOn(4), moduleStatusUnknown(5)} | read-only | current |
| vpwrModuleCapacity OBJECT-TYPE The meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Capacity for Rectifier module. - Not Applicable for LVD module | 1.3.6.1.4.1.13858.2.1.6.1.6 | INTEGER | read-only | current |
| vpwrSystemConfigGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.2.2 | |||
| vpwrSystemTempCompensation OBJECT-TYPE This parameter enables/disables temperature compensation. | 1.3.6.1.4.1.13858.2.2.1 | INTEGER {tempCompDisabled(0), tempCompEnabled(1)} | read-write | current |
| vpwrSystemTempCompStartTemperature OBJECT-TYPE The temperature at which temperature compensation becomes active. | 1.3.6.1.4.1.13858.2.2.2 | INTEGER (25..60) | read-write | current |
| vpwrSystemTempCompStopVoltage OBJECT-TYPE When temperature compensation is active, vpwrSystemTempCompStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to 51.75 volts enter a value of 5175. | 1.3.6.1.4.1.13858.2.2.3 | INTEGER | read-write | current |
| vpwrSystemTempCompensationSlope OBJECT-TYPE The rate at which float voltage is changed, within the specified limits, when temperature compensation is active. | 1.3.6.1.4.1.13858.2.2.4 | INTEGER (0..250) | read-write | current |
| vpwrSystemThermalSenseType OBJECT-TYPE This parameter selects the temperature sensing point for temperature compensation (in)activation. | 1.3.6.1.4.1.13858.2.2.5 | INTEGER {external(0), internal(1)} | read-write | current |
| vpwrSystemHVAlarmSetpoint OBJECT-TYPE System High voltage alarm voltage setting. | 1.3.6.1.4.1.13858.2.2.6 | INTEGER | read-write | current |
| vpwrSystemBDAlarmSetpoint OBJECT-TYPE System Battery Discharge voltage setting. | 1.3.6.1.4.1.13858.2.2.7 | INTEGER | read-write | current |
| vpwrSystemInternalTempLThreshold OBJECT-TYPE Temperature value at which temperature compensation inactive (clear) trap would be sent if temperature compensation was active when this value is reached. | 1.3.6.1.4.1.13858.2.2.8 | INTEGER | read-write | current |
| vpwrSystemInternalTempUThreshold OBJECT-TYPE Temperature value at which temperature compensation active (set) trap would be sent. | 1.3.6.1.4.1.13858.2.2.9 | INTEGER | read-write | current |
| vpwrSystemParameterGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.2.3 | |||
| vpwrSystemShelfCapacity OBJECT-TYPE It describes the maximum number of shelves that can/are controlled by the controller. Each shelf is uniquely numbered in the range from 1 to vpwrShelfCapacity. | 1.3.6.1.4.1.13858.2.3.1 | INTEGER (1..16) | read-only | current |
| vpwrSystemVoltage OBJECT-TYPE The current system voltage. | 1.3.6.1.4.1.13858.2.3.2 | INTEGER | read-only | current |
| vpwrSystemCurrent OBJECT-TYPE The current system current. | 1.3.6.1.4.1.13858.2.3.3 | INTEGER | read-only | current |
| vpwrSystemControllerState OBJECT-TYPE Current System state as shown on the enhanced display. | 1.3.6.1.4.1.13858.2.3.4 | INTEGER {systemControllerStateUnknown(0), systemControllerStateNormal(1), systemControllerStateChange(2), systemControllerStateAlarm(3), systemControllerStateMenu(4), systemControllerStateIrActive(5)} | read-only | current |
| vpwrSystemInternalTemperature OBJECT-TYPE The current controller internal temperature. | 1.3.6.1.4.1.13858.2.3.5 | INTEGER | read-only | current |
| vpwrSystemTempCompensationState OBJECT-TYPE Active or Inactive. Applicable only if temperature compensation is enabled. This means that the controller is temperature compensating the float voltage. | 1.3.6.1.4.1.13858.2.3.6 | INTEGER {systemTempCompInactive(0), systemTempCompActive(1)} | read-only | current |
| vpwrSystemType OBJECT-TYPE This parameter describes the type of the system being managed. This object is set by Valere Power Inc. | 1.3.6.1.4.1.13858.2.3.7 | INTEGER {sysTypeUnknow(0), sysType48V(1), sysType24V(2), sysType12V(3)} | read-only | current |
| vpwrSystemPanelIdentGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.2.4 | |||
| vpwrPanelIdentTable OBJECT-TYPE This table describes shelves and modules that make up the panels. | 1.3.6.1.4.1.13858.2.4.1 | not-accessible | current | |
| vpwrPanelIdentEntry OBJECT-TYPE An entry containing information applicable to a particular panel making up the system. | 1.3.6.1.4.1.13858.2.4.1.1 | not-accessible | current | |
| vpwrPanelBayIndex OBJECT-TYPE Identifies bay number that this module belongs to. The possible values are 1 through 16, starting from the top. | 1.3.6.1.4.1.13858.2.4.1.1.1 | PositiveInteger | read-only | current |
| vpwrPanelModuleIndex OBJECT-TYPE This object identifies the module within the panel. The orentation of modules within the panel is mappable. | 1.3.6.1.4.1.13858.2.4.1.1.2 | PositiveInteger | read-only | current |
| vpwrPanelModuleOID OBJECT-TYPE It indicates the type of the module by specifiying its OID | 1.3.6.1.4.1.13858.2.4.1.1.3 | OBJECT IDENTIFIER | read-only | current |
| vpwrPanelModuleCurrent OBJECT-TYPE This is the Current of the first shunt of the module. | 1.3.6.1.4.1.13858.2.4.1.1.4 | INTEGER | read-only | current |
| vpwrPanelModuleOperStatus OBJECT-TYPE This object indicates over all status of the module. | 1.3.6.1.4.1.13858.2.4.1.1.5 | INTEGER {moduleStatusOK(0), moduleStatusAlarm(1)} | read-only | current |
| vpwrPanelModuleCapacity OBJECT-TYPE This is the overall Capacity of the module and is for reference only. | 1.3.6.1.4.1.13858.2.4.1.1.6 | INTEGER | read-only | current |
| vpwrSystemBayctrlIdentGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.2.5 | |||
| vpwrBayctrlIdentTable OBJECT-TYPE This table describes bay controllers that make up the system. | 1.3.6.1.4.1.13858.2.5.1 | not-accessible | current | |
| vpwrBayctrlIdentEntry OBJECT-TYPE An entry containing information applicable to a particular bay controller making up the system. | 1.3.6.1.4.1.13858.2.5.1.1 | not-accessible | current | |
| vpwrBayctrlIndex OBJECT-TYPE Identifies bay number that this module belongs to. The possible values are 0 through 15, starting from the top. | 1.3.6.1.4.1.13858.2.5.1.1.1 | PositiveInteger | read-only | current |
| vpwrBayctrlOID OBJECT-TYPE It indicates the type of the module by specifiying its OID | 1.3.6.1.4.1.13858.2.5.1.1.2 | OBJECT IDENTIFIER | read-only | current |
| vpwrBayctrlCurrent OBJECT-TYPE This is the total output Current of the bay | 1.3.6.1.4.1.13858.2.5.1.1.3 | INTEGER | read-only | current |
| vpwrBayctrlOperStatus OBJECT-TYPE This object indicates over all status of the bay | 1.3.6.1.4.1.13858.2.5.1.1.4 | INTEGER {moduleStatusOK(0), moduleStatusAlarm(1)} | read-only | current |
| vpwrBayctrlCapacity OBJECT-TYPE This is the overall Capacity of the bay and is for reference only. | 1.3.6.1.4.1.13858.2.5.1.1.5 | INTEGER | read-only | current |
| vpwrDcPowerRectifier OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3 | |||
| vpwrRectifierConfigGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.1 | |||
| vpwrRectifierFVSetpoint OBJECT-TYPE System Float Voltage setting | 1.3.6.1.4.1.13858.3.1.1 | INTEGER | read-write | current |
| vpwrRectifierHVSDSetpoint OBJECT-TYPE System High Voltage Shutdown voltage setting | 1.3.6.1.4.1.13858.3.1.2 | INTEGER | read-write | current |
| vpwrRectifierCurrentLimitAdminState OBJECT-TYPE This parameter allows enabling or disabling boost. | 1.3.6.1.4.1.13858.3.1.3 | INTEGER {rectCurrentLimitDisabled(0), rectCurrentLimitEnabled(1)} | read-write | current |
| vpwrRectifierCurrentLimit OBJECT-TYPE Rectifier current limit setpoint | 1.3.6.1.4.1.13858.3.1.4 | INTEGER (5..200) | read-write | current |
| vpwrRectifierAlarmGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2 | |||
| vpwrRectAlarmDCFail OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.1 | current | ||
| vpwrRectAlarmBoostFail OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.2 | current | ||
| vpwrRectAlarmACFail OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.3 | current | ||
| vpwrRectAlarmHVSD OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.4 | current | ||
| vpwrRectAlarmFanFail OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.5 | current | ||
| vpwrRectAlarmAmbTemp OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.6 | current | ||
| vpwrRectAlarmIntTemp OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.7 | current | ||
| vpwrRectAlarmIShare OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.8 | current | ||
| vpwrRectAlarmUV OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.9 | current | ||
| vpwrRectAlarmLowVoltage OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.10 | current | ||
| vpwrRectAlarmReserved OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.11 | current | ||
| vpwrRectAlarmDCEnable OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.12 | current | ||
| vpwrRectAlarmRemoteShutdown OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.13 | current | ||
| vpwrRectAlarmModDisableShutdown OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.14 | current | ||
| vpwrRectAlarmShortPinShutdown OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.15 | current | ||
| vpwrRectAlarmBoostComm OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.2.16 | current | ||
| vpwrRectifierTestGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.3.3 | |||
| vpwrDcPowerLvd OBJECT-IDENTITY | 1.3.6.1.4.1.13858.4 | |||
| vpwrLvdConfigGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.4.1 | |||
| vpwrLvdWarningSetpoint OBJECT-TYPE LVD Warning voltage setpoint. | 1.3.6.1.4.1.13858.4.1.1 | INTEGER | read-write | current |
| vpwrLvdDisconnectSetpoint OBJECT-TYPE LVD disconnect voltage setpoint. | 1.3.6.1.4.1.13858.4.1.2 | INTEGER | read-write | current |
| vpwrLvdReconnectSetpoint OBJECT-TYPE LVD Reconnect voltage setpoint. | 1.3.6.1.4.1.13858.4.1.3 | INTEGER | read-write | current |
| vpwrLvdReconnectDelayTimer OBJECT-TYPE The delay time, in seconds, before LVD is reconnected | 1.3.6.1.4.1.13858.4.1.4 | INTEGER (20..240) | read-write | current |
| vpwrLvdContactorConfigTable OBJECT-TYPE This table describes shelves and modules that make up the sysetm. | 1.3.6.1.4.1.13858.4.1.5 | not-accessible | current | |
| vpwrLvdContactorConfigEntry OBJECT-TYPE An entry containing information applicable to a particular module making up the system. | 1.3.6.1.4.1.13858.4.1.5.1 | not-accessible | current | |
| vpwrLvdContactorIndex OBJECT-TYPE contactor index | 1.3.6.1.4.1.13858.4.1.5.1.1 | PositiveInteger | read-only | current |
| vpwrLvdContactorWarningSetpoint OBJECT-TYPE LVD Warning voltage setpoint. | 1.3.6.1.4.1.13858.4.1.5.1.2 | PositiveInteger | read-write | current |
| vpwrLvdContactorDisconnectSetpoint OBJECT-TYPE LVD disconnect voltage setpoint. | 1.3.6.1.4.1.13858.4.1.5.1.3 | PositiveInteger | read-write | current |
| vpwrLvdContactorReconnectSetpoint OBJECT-TYPE LVD Reconnect voltage setpoint. | 1.3.6.1.4.1.13858.4.1.5.1.4 | PositiveInteger | read-write | current |
| vpwrLvdContactorReconnectDelayTimer OBJECT-TYPE The delay time, in seconds, before LVD is reconnected | 1.3.6.1.4.1.13858.4.1.5.1.5 | PositiveInteger (0..240) | read-write | current |
| vpwrLvdContactorState OBJECT-TYPE The delay time, in seconds, before LVD is reconnected | 1.3.6.1.4.1.13858.4.1.5.1.6 | INTEGER {contactorOpen(0), contactorClose(1)} | read-write | current |
| vpwrLvdAlarmGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.4.2 | |||
| vpwrLvdAlarmContactorOpen OBJECT-IDENTITY Contactor open | 1.3.6.1.4.1.13858.4.2.1 | current | ||
| vpwrLvdAlarmCBOpen OBJECT-IDENTITY Circuit Breaker open | 1.3.6.1.4.1.13858.4.2.2 | current | ||
| vpwrTrapLvdFuseOpen OBJECT-IDENTITY Fuse open | 1.3.6.1.4.1.13858.4.2.3 | current | ||
| vpwrLvdAlarmWarning OBJECT-IDENTITY Plant Voltage below warning threshold | 1.3.6.1.4.1.13858.4.2.4 | current | ||
| vpwrLvdTestGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.4.3 | |||
| vpwrDcPowerTest OBJECT-IDENTITY | 1.3.6.1.4.1.13858.5 | |||
| vpwrDcPowerModuleIdent OBJECT-IDENTITY | 1.3.6.1.4.1.13858.6 | |||
| vpwrModuleIdentTable OBJECT-TYPE This table describes shelves and modules that make up the sysetm. | 1.3.6.1.4.1.13858.6.1 | not-accessible | current | |
| vpwrModuleIdentEntry OBJECT-TYPE An entry containing information applicable to a particular Module. | 1.3.6.1.4.1.13858.6.1.1 | not-accessible | current | |
| vpwrModuleSerialNumber OBJECT-TYPE Serial Number of the module | 1.3.6.1.4.1.13858.6.1.1.1 | DisplayString | read-only | current |
| vpwrModuleModelNumber OBJECT-TYPE Model Number of the module. | 1.3.6.1.4.1.13858.6.1.1.2 | DisplayString | read-only | current |
| vpwrModuleFwVersion OBJECT-TYPE Firmware version of the module. | 1.3.6.1.4.1.13858.6.1.1.3 | DisplayString | read-only | current |
| vpwrModuleTestDate OBJECT-TYPE Date when the module was last tested. | 1.3.6.1.4.1.13858.6.1.1.4 | DisplayString | read-only | current |
| vpwrModuleOperHours OBJECT-TYPE Cumulative Operating Hours. | 1.3.6.1.4.1.13858.6.1.1.5 | Counter32 | read-only | current |
| vpwrPanelModuleIdentTable OBJECT-TYPE This table describes shelves and modules that make up the sysetm. | 1.3.6.1.4.1.13858.6.2 | not-accessible | current | |
| vpwrPanelModuleIdentEntry OBJECT-TYPE An entry containing information applicable to a particular alarm. | 1.3.6.1.4.1.13858.6.2.1 | not-accessible | current | |
| vpwrPanelModuleSerialNumber OBJECT-TYPE Serial Number of the module | 1.3.6.1.4.1.13858.6.2.1.1 | DisplayString | read-only | current |
| vpwrPanelModuleModelNumber OBJECT-TYPE Model Number of the module. | 1.3.6.1.4.1.13858.6.2.1.2 | DisplayString | read-only | current |
| vpwrPanelModuleFwVersion OBJECT-TYPE Firmware version of the module. | 1.3.6.1.4.1.13858.6.2.1.3 | DisplayString | read-only | current |
| vpwrPanelModuleTestDate OBJECT-TYPE Date when the module was last tested. | 1.3.6.1.4.1.13858.6.2.1.4 | DisplayString | read-only | current |
| vpwrPanelModuleOperHours OBJECT-TYPE Cumulative Operating Hours. | 1.3.6.1.4.1.13858.6.2.1.5 | Counter32 | read-only | current |
| vpwrBayctrlModuleIdentTable OBJECT-TYPE This table describes bay controllers that make up the sysetm. | 1.3.6.1.4.1.13858.6.3 | not-accessible | current | |
| vpwrBayctrlModuleIdentEntry OBJECT-TYPE An entry containing information applicable to a particular bay controller. | 1.3.6.1.4.1.13858.6.3.1 | not-accessible | current | |
| vpwrBayctrlSerialNumber OBJECT-TYPE Serial Number of the bay controller | 1.3.6.1.4.1.13858.6.3.1.1 | DisplayString | read-only | current |
| vpwrBayctrlModelNumber OBJECT-TYPE Model Number of the bay controller. | 1.3.6.1.4.1.13858.6.3.1.2 | DisplayString | read-only | current |
| vpwrBayctrlFwVersion OBJECT-TYPE Firmware version of the bay controller. | 1.3.6.1.4.1.13858.6.3.1.3 | DisplayString | read-only | current |
| vpwrBayctrlTestDate OBJECT-TYPE Date when the bayctrl was last tested. | 1.3.6.1.4.1.13858.6.3.1.4 | DisplayString | read-only | current |
| vpwrBayctrlOperHours OBJECT-TYPE Cumulative Operating Hours. | 1.3.6.1.4.1.13858.6.3.1.5 | Counter32 | read-only | current |
| vpwrDcPowerBatteryGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.7 | |||
| vpwrBatteryTempGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.7.1 | |||
| vpwrBatteryTempTable OBJECT-TYPE This table describes battery temperature probes. | 1.3.6.1.4.1.13858.7.1.1 | not-accessible | current | |
| vpwrBatteryTempEntry OBJECT-TYPE An entry containing information applicable to a particular temperature probe. | 1.3.6.1.4.1.13858.7.1.1.1 | not-accessible | current | |
| vpwrBatteryTempIndex OBJECT-TYPE Index into temperature table | 1.3.6.1.4.1.13858.7.1.1.1.1 | INTEGER | read-only | current |
| vpwrBatteryTempName OBJECT-TYPE A string identifying probe location. | 1.3.6.1.4.1.13858.7.1.1.1.2 | DisplayString (SIZE(1..8)) | read-write | current |
| vpwrBatteryTemp OBJECT-TYPE Current temperature as recorded by the probe. | 1.3.6.1.4.1.13858.7.1.1.1.3 | INTEGER | read-only | current |
| vpwrBatteryTempLThreshold OBJECT-TYPE Temperature value at which a clear trap would be sent. All three battery temperature must be at or below this value to trigger this trap. | 1.3.6.1.4.1.13858.7.1.2 | INTEGER | read-write | current |
| vpwrBatteryTempUThreshold OBJECT-TYPE Temperature value at which a set trap would be sent. Any one of the three battery temperatures at or exceeding this limit would trigger the trap. | 1.3.6.1.4.1.13858.7.1.3 | INTEGER | read-write | current |
| batteryTempCompensation OBJECT-TYPE This parameter enables/disables temperature compensation. | 1.3.6.1.4.1.13858.7.1.4 | INTEGER {tempCompDisabled(0), tempCompEnabled(1)} | read-write | current |
| batteryTempCompHighStartTemperature OBJECT-TYPE The temperature at which temperature compensation becomes active. | 1.3.6.1.4.1.13858.7.1.5 | INTEGER (25..60) | read-write | current |
| batteryTempCompHighStopVoltage OBJECT-TYPE When temperature compensation is active, batteryTempCompHighStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to 51.75 volts enter a value of 5175. | 1.3.6.1.4.1.13858.7.1.6 | INTEGER | read-write | current |
| batteryTempCompHighSlope OBJECT-TYPE The rate at which float voltage is changed, within the specified limits, when temperature compensation is active. | 1.3.6.1.4.1.13858.7.1.7 | INTEGER (0..250) | read-write | current |
| batteryTempCompLowStartTemperature OBJECT-TYPE The temperature at which temperature compensation becomes active. | 1.3.6.1.4.1.13858.7.1.8 | INTEGER | read-write | current |
| batteryTempCompLowStopVoltage OBJECT-TYPE When temperature compensation is active, batteryTempCompLowStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to 51.75 volts enter a value of 5175. | 1.3.6.1.4.1.13858.7.1.9 | INTEGER | read-write | current |
| batteryTempCompLowSlope OBJECT-TYPE The rate at which float voltage is changed, within the specified limits, when temperature compensation is active. | 1.3.6.1.4.1.13858.7.1.10 | INTEGER (0..250) | read-write | current |
| batteryTempCompRunawayTemperature OBJECT-TYPE The temperature at which system voltage will be set to batteryTempCompRunawayStopVoltage. | 1.3.6.1.4.1.13858.7.1.11 | INTEGER (25..60) | read-write | current |
| batteryTempCompRunawayStopVoltage OBJECT-TYPE When temperature compensation is enabled, float voltage will be reduced to batteryTempCompRunawayStopVoltage if temperature reaches batteryTempCompRunawayTemperature. | 1.3.6.1.4.1.13858.7.1.12 | INTEGER | read-write | current |
| batteryTempCompSenseSource OBJECT-TYPE This parameter selects the temperature sensing point for temperature compensation (in)activation. | 1.3.6.1.4.1.13858.7.1.13 | INTEGER {external(0), internal(1)} | read-write | current |
| batteryTempCompRunawayState OBJECT-TYPE This parameter selects the temperature sensing point for temperature compensation (in)activation. | 1.3.6.1.4.1.13858.7.1.14 | INTEGER {inactive(0), active(1)} | read-only | current |
| thermalProbeTable OBJECT-TYPE This table describes battery temperature probes. | 1.3.6.1.4.1.13858.7.1.15 | not-accessible | current | |
| thermalProbeEntry OBJECT-TYPE An entry containing information applicable to a particular temperature probe. | 1.3.6.1.4.1.13858.7.1.15.1 | not-accessible | current | |
| thermalProbeState OBJECT-TYPE State of thermal probe. | 1.3.6.1.4.1.13858.7.1.15.1.1 | INTEGER {notPresent(0), present(1), removed(2), shorted(3)} | read-only | current |
| vpwrBatteryCurrentGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.7.2 | |||
| vpwrBatteryCurrentLimitAdminState OBJECT-TYPE This parameter allows enabling or disabling battery current limit. | 1.3.6.1.4.1.13858.7.2.1 | INTEGER {battetyCurrentLimitDisabled(0), battetyCurrentLimitEnabled(1)} | read-write | current |
| vpwrBattetyCurrentLimitValue OBJECT-TYPE | 1.3.6.1.4.1.13858.7.2.2 | INTEGER (5..40) | read-write | current |
| vpwrBattetyCurrentValue OBJECT-TYPE | 1.3.6.1.4.1.13858.7.2.3 | INTEGER (5..40) | read-only | current |
| vpwrBatteryBoostGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.7.3 | |||
| vpwrBoostAdminState OBJECT-TYPE This parameter allows enabling or disabling boost. | 1.3.6.1.4.1.13858.7.3.1 | INTEGER {boostDisabled(0), boostEnabled(1)} | read-write | current |
| vpwrBoostVoltage OBJECT-TYPE | 1.3.6.1.4.1.13858.7.3.2 | INTEGER (7000..11000) | read-write | current |
| vpwrBoostDuration OBJECT-TYPE | 1.3.6.1.4.1.13858.7.3.3 | INTEGER (0..100) | read-write | current |
| vpwrBoostOperState OBJECT-TYPE This parameter allows starting or stoping boost if it is enabled. | 1.3.6.1.4.1.13858.7.3.4 | INTEGER {boostInactive(0), boostActive(1)} | read-write | current |
| vpwrBatteryDischargeTestGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.7.4 | |||
| vpwrBDTAdminState OBJECT-TYPE Enable /Disable Battery Discharge Test execution. | 1.3.6.1.4.1.13858.7.4.1 | INTEGER {bdtDisabled(0), bdtEnabled(1)} | read-write | current |
| vpwrBDTDuration OBJECT-TYPE | 1.3.6.1.4.1.13858.7.4.2 | INTEGER (17..50) | read-write | current |
| vpwrBDTAlarmVoltage OBJECT-TYPE | 1.3.6.1.4.1.13858.7.4.3 | INTEGER (7000..11000) | read-write | current |
| vpwrBDTAbortVoltage OBJECT-TYPE | 1.3.6.1.4.1.13858.7.4.4 | INTEGER (0..5600) | read-write | current |
| vpwrBDTAlarmCoefficient OBJECT-TYPE | 1.3.6.1.4.1.13858.7.4.5 | INTEGER (0..1) | read-write | current |
| vpwrBDTOperState OBJECT-TYPE Start/Stop Battery Discharge Test execution. | 1.3.6.1.4.1.13858.7.4.6 | INTEGER {bdtInactive(0), bdtActive(1)} | read-write | current |
| vpwrBDTClearAlarm OBJECT-TYPE Clears any active bdt alarm. | 1.3.6.1.4.1.13858.7.4.7 | INTEGER {bdtNoAlarm(0), bdtAlarmPresent(1)} | read-write | current |
| vpwrDcPowerAlarmGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.8 | |||
| vpwrAlarmsPresent OBJECT-TYPE The present number of active alarm conditions. | 1.3.6.1.4.1.13858.8.1 | Gauge32 | read-only | current |
| vpwrAlarmTable OBJECT-TYPE A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The vpwrAlarmIndex, for each type of module starts at 1 and is limited by the total number of alarams that can be generated by the module. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), vpwrAlarmDescr, to allow a single table to reflect alarms for different type of modules. The number of rows in the table at any given time is reflected by the value of vpwrAlarmsPresent. | 1.3.6.1.4.1.13858.8.2 | not-accessible | current | |
| vpwrAlarmEntry OBJECT-TYPE An entry containing information applicable to a particular alarm. | 1.3.6.1.4.1.13858.8.2.1 | not-accessible | current | |
| vpwrAlarmIndex OBJECT-TYPE Identifies the alarm associated with the module. It is unique on per module type basis. For example, multiple rectifiers can have the same alarm and therefore same vpwrAlarmIndex active at any one time. | 1.3.6.1.4.1.13858.8.2.1.1 | PositiveInteger | read-only | current |
| vpwrAlarmDescr OBJECT-TYPE A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. | 1.3.6.1.4.1.13858.8.2.1.2 | AutonomousType | read-only | current |
| vpwrAlarmTime OBJECT-TYPE The value of sysUpTime when the alarm condition was detected. | 1.3.6.1.4.1.13858.8.2.1.3 | TimeStamp | read-only | current |
| sysRelayConfigTable OBJECT-TYPE This table describes battery temperature probes. | 1.3.6.1.4.1.13858.8.3 | not-accessible | current | |
| sysRelayConfigEntry OBJECT-TYPE An entry containing information applicable to a particular temperature probe. | 1.3.6.1.4.1.13858.8.3.1 | not-accessible | current | |
| sysRelayIndex OBJECT-TYPE Index into temperature table | 1.3.6.1.4.1.13858.8.3.1.1 | INTEGER | read-only | current |
| sysRelayDefaultName OBJECT-TYPE A string identifying probe location. | 1.3.6.1.4.1.13858.8.3.1.2 | DisplayString (SIZE(1..8)) | read-only | current |
| sysRelayCustomName OBJECT-TYPE A string identifying probe location. | 1.3.6.1.4.1.13858.8.3.1.3 | DisplayString (SIZE(1..8)) | read-write | current |
| sysRelayAlarmSeverity OBJECT-TYPE Current temperature as recorded by the probe. | 1.3.6.1.4.1.13858.8.3.1.4 | INTEGER {alarmNone(0), alarmMajor(1), alarmMinor(2), alarmMajorAndMinor(3)} | read-write | current |
| sysAlarmConfigTable OBJECT-TYPE This table describes battery temperature probes. | 1.3.6.1.4.1.13858.8.4 | not-accessible | current | |
| sysAlarmConfigEntry OBJECT-TYPE An entry containing information applicable to a particular temperature probe. | 1.3.6.1.4.1.13858.8.4.1 | not-accessible | current | |
| sysAlarmIndex OBJECT-TYPE Index into temperature table | 1.3.6.1.4.1.13858.8.4.1.1 | INTEGER | read-only | current |
| sysAlarmDefaultName OBJECT-TYPE A string identifying probe location. | 1.3.6.1.4.1.13858.8.4.1.2 | DisplayString (SIZE(1..8)) | read-only | current |
| sysAlarmCustomName OBJECT-TYPE A string identifying probe location. | 1.3.6.1.4.1.13858.8.4.1.3 | DisplayString (SIZE(1..8)) | read-write | current |
| sysAlarmSeverity OBJECT-TYPE Alarm Severity as denoted by Major and Minor Alarm Mask | 1.3.6.1.4.1.13858.8.4.1.4 | INTEGER {none(0), major(1), minor(2), majorAndMinor(3)} | read-write | current |
| sysAlarmToRelayMapping OBJECT-TYPE No additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A and B = (1 + 2) and so on The major/minor classification of alarms automatically associates it with Major/Minor relay. Assigning a null mapping here does not override sysRelayAlarmSeverity for the alarm. It should be used to define mapping to additional relays. | 1.3.6.1.4.1.13858.8.4.1.5 | DisplayString (SIZE(1..8)) | read-write | current |
| sysAlarmOperStatus OBJECT-TYPE Indicates current alarm status | 1.3.6.1.4.1.13858.8.4.1.6 | INTEGER {inactive(0), active(1)} | read-only | current |
| sysAuxAlarmConfigTable OBJECT-TYPE This table describes battery temperature probes. | 1.3.6.1.4.1.13858.8.5 | not-accessible | current | |
| sysAuxAlarmConfigEntry OBJECT-TYPE An entry containing information applicable to a particular temperature probe. | 1.3.6.1.4.1.13858.8.5.1 | not-accessible | current | |
| sysAuxAlarmIndex OBJECT-TYPE Index into temperature table | 1.3.6.1.4.1.13858.8.5.1.1 | INTEGER | read-only | current |
| sysAuxAlarmDefaultName OBJECT-TYPE A string identifying probe location. | 1.3.6.1.4.1.13858.8.5.1.2 | DisplayString (SIZE(1..8)) | read-only | current |
| sysAuxAlarmCustomName OBJECT-TYPE A string identifying probe location. | 1.3.6.1.4.1.13858.8.5.1.3 | DisplayString (SIZE(1..8)) | read-write | current |
| sysAuxAlarmSeverity OBJECT-TYPE Aux Alarm Severity | 1.3.6.1.4.1.13858.8.5.1.4 | INTEGER {none(0), major(1), minor(2), majorAndMinor(3)} | read-write | current |
| sysAuxAlarmToRelayMapping OBJECT-TYPE No additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A and B = (1 + 2) and so on The major/minor classification of alarms automatically associates it with Major/Minor relay. Assigning a null mapping here does not override sysRelayAlarmSeverity for the alarm. It should be used to define mapping to additional relays. | 1.3.6.1.4.1.13858.8.5.1.5 | DisplayString (SIZE(1..8)) | read-write | current |
| sysAuxAlarmPolarity OBJECT-TYPE Current temperature as recorded by the probe. | 1.3.6.1.4.1.13858.8.5.1.6 | INTEGER {alarmOnOpen(0), alarmOnClose(1)} | read-write | current |
| sysAuxAlarmOperStatus OBJECT-TYPE Indicates current alarm status | 1.3.6.1.4.1.13858.8.5.1.7 | INTEGER {inactive(0), active(1)} | read-only | current |
| sysAlarmComFailState OBJECT-TYPE Enable/Disable generation of comm fail alarm. | 1.3.6.1.4.1.13858.8.6 | INTEGER {disabled(0), enabled(1), other(2)} | read-write | current |
| sysAlarmIShareState OBJECT-TYPE Enable/Disable generation of current share alarm. | 1.3.6.1.4.1.13858.8.7 | INTEGER {disabled(0), enabled(1), other(2)} | read-write | current |
| sysAlarmRedundancyState OBJECT-TYPE Enable/Disable generation of redundancy alarm. | 1.3.6.1.4.1.13858.8.8 | INTEGER {disabled(0), nPlus1(1), nPlus2(2)} | read-write | current |
| vpwrDcPowerSnmpConfig OBJECT-IDENTITY | 1.3.6.1.4.1.13858.9 | |||
| vpwrTrapTable OBJECT-TYPE A list of possible trap destinations depending upon the criticality of the trap. | 1.3.6.1.4.1.13858.9.1 | not-accessible | current | |
| vpwrTrapEntry OBJECT-TYPE An entry containing information applicable to a particular trap destination. | 1.3.6.1.4.1.13858.9.1.1 | not-accessible | current | |
| vpwrTrapIpIndex OBJECT-TYPE Trap Entry Index | 1.3.6.1.4.1.13858.9.1.1.1 | INTEGER | read-only | current |
| vpwrTrapIpAddress OBJECT-TYPE Trap destination IP Address | 1.3.6.1.4.1.13858.9.1.1.2 | IpAddress | read-write | current |
| vpwrTrapCriticality OBJECT-TYPE Criticality of traps sent to this IP Address | 1.3.6.1.4.1.13858.9.1.1.3 | INTEGER | read-write | current |
| vpwrReadCommunityString OBJECT-TYPE This allows setting password to be able to do Get operations | 1.3.6.1.4.1.13858.9.2 | DisplayString (SIZE(3..8)) | read-write | current |
| vpwrWriteCommunityString OBJECT-TYPE This allows setting password to be able to do Get and Set operations. The read-access is not allowed in the actual implementation. | 1.3.6.1.4.1.13858.9.3 | DisplayString (SIZE(3..8)) | read-write | current |
| vpwrTrapCommunityString OBJECT-TYPE This allows setting community string required for the trap to be accepted at the destination. | 1.3.6.1.4.1.13858.9.4 | DisplayString (SIZE(3..8)) | read-write | current |
| vpwrDcPowerTraps OBJECT-IDENTITY | 1.3.6.1.4.1.13858.10 | |||
| vpwrDcPowerTrapsMsgString OBJECT-IDENTITY | 1.3.6.1.4.1.13858.11 | |||
| vpwrTrapsMsgString OBJECT-TYPE Place holder for trap notification message string | 1.3.6.1.4.1.13858.11.1 | DisplayString (SIZE(0..127)) | not-accessible | current |
| vpwrTrapUserIpAddress OBJECT-TYPE Place holder for IP address of the user accessing the system | 1.3.6.1.4.1.13858.11.2 | IpAddress | not-accessible | current |
| vpwrTrapEventTimeStamp OBJECT-TYPE Place holder for time-stamp. | 1.3.6.1.4.1.13858.11.3 | IpAddress | not-accessible | current |
| vpwrDcPowerRinger OBJECT-IDENTITY | 1.3.6.1.4.1.13858.12 | |||
| vpwrRingerConfigGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.12.1 | |||
| vpwrRingerParameterTable OBJECT-TYPE A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The vpwrAlarmIndex, for each type of module starts at 1 and is limited by the total number of alarams that can be generated by the module. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), vpwrAlarmDescr, to allow a single table to reflect alarms for different type of modules. The number of rows in the table at any given time is reflected by the value of vpwrAlarmsPresent. | 1.3.6.1.4.1.13858.12.1.1 | not-accessible | current | |
| vpwrRingerParameterEntry OBJECT-TYPE An entry containing information applicable to a particular alarm. | 1.3.6.1.4.1.13858.12.1.1.1 | not-accessible | current | |
| vpwrRingerIndex OBJECT-TYPE This parameter allows selecting ringer A or Ringer B as the active ringer. | 1.3.6.1.4.1.13858.12.1.1.1.1 | INTEGER | read-only | current |
| vpwrRingerParameterAdminState OBJECT-TYPE This parameter allows selecting ringer A or Ringer B as the active ringer. | 1.3.6.1.4.1.13858.12.1.1.1.2 | INTEGER {ringerDisabled(0), ringerAOn(1), ringerBOn(2)} | read-write | current |
| vpwrRingerParameterAcVoltage OBJECT-TYPE | 1.3.6.1.4.1.13858.12.1.1.1.3 | INTEGER (7000..11000) | read-write | current |
| vpwrRingerParameterDcVoltage OBJECT-TYPE | 1.3.6.1.4.1.13858.12.1.1.1.4 | INTEGER (0..5600) | read-write | current |
| vpwrRingerParameterFrequency OBJECT-TYPE | 1.3.6.1.4.1.13858.12.1.1.1.5 | INTEGER (17..50) | read-write | current |
| vpwrRingerNumberPresent OBJECT-TYPE The present number of active alarm conditions. | 1.3.6.1.4.1.13858.12.1.2 | Gauge32 | read-only | current |
| vpwrRingerAlarmGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.12.2 | |||
| vpwrRingerAlarmaAFailed OBJECT-IDENTITY Ringer A Failed | 1.3.6.1.4.1.13858.12.2.1 | current | ||
| vpwrRingerAlarmAOTemp OBJECT-IDENTITY Ringer A Heatsink Over-Temperature | 1.3.6.1.4.1.13858.12.2.2 | current | ||
| vpwrRingerAlarmAOCurrent OBJECT-IDENTITY Ringer A Over-Current protection | 1.3.6.1.4.1.13858.12.2.3 | current | ||
| vpwrRingerAlarmaBFailed OBJECT-IDENTITY Ringer A Failed | 1.3.6.1.4.1.13858.12.2.4 | current | ||
| vpwrRingerAlarmBOverTemp OBJECT-IDENTITY Ringer A Heatsink Over-Temperature | 1.3.6.1.4.1.13858.12.2.5 | current | ||
| vpwrRingerAlarmBOverCurrent OBJECT-IDENTITY Ringer A Over-Current protection | 1.3.6.1.4.1.13858.12.2.6 | current | ||
| vpwrRingerTestGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.12.3 | |||
| vpwrDcPowerDcDcConverter OBJECT-IDENTITY | 1.3.6.1.4.1.13858.13 | |||
| vpwrDcDcConverterConfigGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.13.1 | |||
| vpwrDcDcConverterAlarmGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.13.2 | |||
| vpwrDcDcConverterTestGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.13.3 | |||
| vpwrDcPowerDcAcInverter OBJECT-IDENTITY | 1.3.6.1.4.1.13858.14 | |||
| vpwrDcAcInverterConfigGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.14.1 | |||
| vpwrDcAcInverterAlarmGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.14.2 | |||
| vpwrDcAcInverterTestGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.14.3 | |||
| vpwrDcPowerBayController OBJECT-IDENTITY | 1.3.6.1.4.1.13858.15 | |||
| vpwrDcPowerIoModule OBJECT-IDENTITY | 1.3.6.1.4.1.13858.16 | |||
| vpwrIoModuleConfigGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.16.1 | |||
| vpwrIoModuleAlarmGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.16.2 | |||
| vpwrIoModuleTestGroup OBJECT-IDENTITY | 1.3.6.1.4.1.13858.16.3 | |||
| vpwrDcPowerDist OBJECT-IDENTITY | 1.3.6.1.4.1.13858.17 | |||
| vpwrDcPowerTrio OBJECT-IDENTITY | 1.3.6.1.4.1.13858.18 |
Notifications
| Name | OID | Status |
|---|---|---|
| vpwrTrapPowerMajorAlarm NOTIFICATION-TYPE Major Alarm | 1.3.6.1.4.1.13858.10.0.1 | |
| vpwrTrapPowerMinorAlarm NOTIFICATION-TYPE Minor Alarm | 1.3.6.1.4.1.13858.10.0.2 | |
| vpwrTrapACFAlarm NOTIFICATION-TYPE AC Fail Alarm | 1.3.6.1.4.1.13858.10.0.3 | |
| vpwrTrapHVAlarm NOTIFICATION-TYPE High Voltage Warning Alarm | 1.3.6.1.4.1.13858.10.0.4 | |
| vpwrTrapHVSDAlarm NOTIFICATION-TYPE High Voltage Shutdown Alarm | 1.3.6.1.4.1.13858.10.0.5 | |
| vpwrTrapBDAlarm NOTIFICATION-TYPE Battery on Discharge Alarm | 1.3.6.1.4.1.13858.10.0.6 | |
| vpwrTrapLVDWarningAlarm NOTIFICATION-TYPE LVD Warning Alarm | 1.3.6.1.4.1.13858.10.0.7 | |
| vpwrTrapLVDOpenAlarm NOTIFICATION-TYPE LVD Open Alarm | 1.3.6.1.4.1.13858.10.0.8 | |
| vpwrTrapDistAlarm NOTIFICATION-TYPE Distribution Open Alarm | 1.3.6.1.4.1.13858.10.0.9 | |
| vpwrTrapAuxAlarm NOTIFICATION-TYPE Auxiliary System Alarm | 1.3.6.1.4.1.13858.10.0.10 | |
| vpwrTrapSystemRedundancyAlarm NOTIFICATION-TYPE System Redundant Capacity Alarm | 1.3.6.1.4.1.13858.10.0.11 | |
| vpwrTrapIShareAlarm NOTIFICATION-TYPE Rectifier Current Share Alarm | 1.3.6.1.4.1.13858.10.0.12 | |
| vpwrTrapModuleFailAlarm NOTIFICATION-TYPE Single Rectifier Fail Alarm | 1.3.6.1.4.1.13858.10.0.13 | |
| vpwrTrapMultipleModuleFailAlarm NOTIFICATION-TYPE Multiple Rectifier Fail Alarm | 1.3.6.1.4.1.13858.10.0.14 | |
| vpwrTrapModuleCommAlarm NOTIFICATION-TYPE Module Communication Alarm | 1.3.6.1.4.1.13858.10.0.15 | |
| vpwrTrapSystemOverTemperatureAlarm NOTIFICATION-TYPE System Over Temperature Alarm | 1.3.6.1.4.1.13858.10.0.16 | |
| vpwrTrapSystemOK NOTIFICATION-TYPE SYSTEM OK - No Active Alarms | 1.3.6.1.4.1.13858.10.0.17 | |
| vpwrTrapModuleInserted NOTIFICATION-TYPE A new module has been inserted into the system. | 1.3.6.1.4.1.13858.10.0.18 | |
| vpwrTrapModuleRemoved NOTIFICATION-TYPE A module has been removed from the system. | 1.3.6.1.4.1.13858.10.0.19 | |
| vpwrTrapThermalCompActive NOTIFICATION-TYPE Thermal compensation has become active. | 1.3.6.1.4.1.13858.10.0.20 | |
| vpwrTrapThermalCompInactive NOTIFICATION-TYPE Thermal compensation has been de-activated. | 1.3.6.1.4.1.13858.10.0.21 | |
| vpwrTrapInternalTempAlarmSet NOTIFICATION-TYPE Internal Temperature upper threshold exceeded. | 1.3.6.1.4.1.13858.10.0.22 | |
| vpwrTrapInternalTempAlarmCleared NOTIFICATION-TYPE Internal Temperature within limits | 1.3.6.1.4.1.13858.10.0.23 | |
| vpwrTrapBatteryTempAlarmSet NOTIFICATION-TYPE At least one Battery Temperature exceeded upper threshold. | 1.3.6.1.4.1.13858.10.0.24 | |
| vpwrTrapBatteryTempAlarmCleared NOTIFICATION-TYPE All Battery Temperatures within limits. | 1.3.6.1.4.1.13858.10.0.25 | |
| vpwrTrapLoginFail NOTIFICATION-TYPE Admin login failed due to wrong username/password. | 1.3.6.1.4.1.13858.10.0.26 | |
| vpwrTrapLoginSuccess NOTIFICATION-TYPE Admin login successful. | 1.3.6.1.4.1.13858.10.0.27 | |
| vpwrTrapLogout NOTIFICATION-TYPE Admin logout. | 1.3.6.1.4.1.13858.10.0.28 | |
| vpwrTrapAdminPwdChange NOTIFICATION-TYPE Config change submitted with invalid access. | 1.3.6.1.4.1.13858.10.0.29 | |
| vpwrTrapIllegalConfigSubmit NOTIFICATION-TYPE Config change submitted with invalid access. | 1.3.6.1.4.1.13858.10.0.30 | |
| vpwrTrapCfgChange NOTIFICATION-TYPE Config change submitted. | 1.3.6.1.4.1.13858.10.0.31 | |
| vpwrTrapClearEventHistory NOTIFICATION-TYPE Clear Event history buffer clear request. | 1.3.6.1.4.1.13858.10.0.32 | |
| vpwrTrapSwDownloadNoReboot NOTIFICATION-TYPE System software upgrade without reboot. | 1.3.6.1.4.1.13858.10.0.33 | |
| vpwrTrapSwDownloadAndReboot NOTIFICATION-TYPE System reboot due to software upgrade. | 1.3.6.1.4.1.13858.10.0.34 | |
| vpwrTrapSystemClockChange NOTIFICATION-TYPE System clock updated. | 1.3.6.1.4.1.13858.10.0.35 | |
| vpwrTrapModuleAlarm NOTIFICATION-TYPE Module Alarm. | 1.3.6.1.4.1.13858.10.0.36 | |
| vpwrTrapOIDChange NOTIFICATION-TYPE Change in OID. | 1.3.6.1.4.1.13858.10.0.37 | |
| vpwrTrapThermalRunaway NOTIFICATION-TYPE Thermal Runaway Alarm. | 1.3.6.1.4.1.13858.10.0.38 | |
| vpwrTrapBatteryDischargeTestAlarm NOTIFICATION-TYPE System Voltage dropped to BDT Alarm Setpoint. | 1.3.6.1.4.1.13858.10.0.39 | |
| vpwrTrapRingerAAlarm NOTIFICATION-TYPE Ringer A Fail Alarm. | 1.3.6.1.4.1.13858.10.0.40 | |
| vpwrTrapRingerBAlarm NOTIFICATION-TYPE Ringer B Fail Alarm. | 1.3.6.1.4.1.13858.10.0.41 | |
| vpwrTrapSingleRingerAlarm NOTIFICATION-TYPE Single Ringer Fail Alarm. | 1.3.6.1.4.1.13858.10.0.42 | |
| vpwrTrapMultipleRingerAlarm NOTIFICATION-TYPE Multiple Ringer Fail Alarm. | 1.3.6.1.4.1.13858.10.0.43 | |
| vpwrTrapThermalProbeAlarm NOTIFICATION-TYPE Thermal Probe Missing Alarm. | 1.3.6.1.4.1.13858.10.0.44 | |
| vpwrTrapRingerCommAlarm NOTIFICATION-TYPE Ringer Communication Alarm. | 1.3.6.1.4.1.13858.10.0.45 | |
| vpwrTrapDistributionCommAlarm NOTIFICATION-TYPE Distribution Communication Alarm. | 1.3.6.1.4.1.13858.10.0.46 | |
| vpwrTrapConverterAlarm NOTIFICATION-TYPE Single Converter Fail Alarm. | 1.3.6.1.4.1.13858.10.0.47 | |
| vpwrTrapMultipleConvFailAlarm NOTIFICATION-TYPE Multiple Converter Fail Alarm. | 1.3.6.1.4.1.13858.10.0.48 | |
| vpwrTrapUnmappedAddressAlarm NOTIFICATION-TYPE Unmapped I2C Address. | 1.3.6.1.4.1.13858.10.0.49 | |
| vpwrTrapConfigErrorAlarm NOTIFICATION-TYPE Configuration Error. | 1.3.6.1.4.1.13858.10.0.50 | |
| vpwrTrapDisplayFirmwareMismatchAlarm NOTIFICATION-TYPE Display Firmware Mismatch. | 1.3.6.1.4.1.13858.10.0.51 | |
| vpwrTrapConverterInputFailAlarm NOTIFICATION-TYPE Converter Input Fail Alarm. | 1.3.6.1.4.1.13858.10.0.52 | |
| vpwrTrapBatteryRechgIlimitFailAlarm NOTIFICATION-TYPE Battery Recharge Current Limit Fail. | 1.3.6.1.4.1.13858.10.0.53 | |
| vpwrTrapSystemAlive NOTIFICATION-TYPE Periodic Keepalive trap. | 1.3.6.1.4.1.13858.10.0.54 |