sha256:8f13b5d5de9fd57b7b1d9120dfd81c2deba6727260fa862eeb2089a85d94f27a

Description

MIB Version 0.8 Need description here. History Add table to retrieve module inventory info MIB Version 0.7 Dec 1, 05 Fixed HP Openview error Fixed warnings generated by MG-SOFT Add table to retrieve rectifier inventory info MIB Version 0.6 Feb 10, 2004 Added additional traps. Defined Ringers and other modules. Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry This fixes errors generated by MG-SOFT mib compiler. Oct 30, 2002 initial release - version 0.4

Contact

Contact: Valere Customer Support Postal: 661 N. Plano Road, Suite 300 Richardson, TX-75081 Web: http://www.valerepower.com email: support@valerepower.com Phone 866-240-6614

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-MIBsysUpTime
SNMPv2-SMICounter32, Gauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCAutonomousType, DisplayString, TEXTUAL-CONVENTION, TestAndIncr, TimeInterval, TimeStamp

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC
VALERE-DC-POWER-MIB

Textual conventions

NameOIDSyntaxAccessStatus
NonNegativeInteger
TEXTUAL-CONVENTION
This data type is a non-negative value.
current
PositiveInteger
TEXTUAL-CONVENTION
This data type is a non-zero and non-negative value.
current

Objects

NameOIDSyntaxAccessStatus
vpwrDcPowerProducts
OBJECT-IDENTITY
1.3.6.1.4.1.13858.1
vpwrDcPowerSystem
OBJECT-IDENTITY
1.3.6.1.4.1.13858.2
vpwrSystemIdentGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.2.1
vpwrIdentManufacturer
OBJECT-TYPE
The name of the DC Power manufacturer.
1.3.6.1.4.1.13858.2.1.1DisplayString (SIZE(0..31))read-onlycurrent
vpwrIdentModel
OBJECT-TYPE
The DC Power Model designation.
1.3.6.1.4.1.13858.2.1.2DisplayString (SIZE(0..15))read-onlycurrent
vpwrIdentControllerVersion
OBJECT-TYPE
The hardware/firmware version(s). This variable may or may not have the same value as vpwrIdentAgentSoftwareVersion.
1.3.6.1.4.1.13858.2.1.3DisplayString (SIZE(0..15))read-onlycurrent
vpwrIdentAgentSoftwareVersion
OBJECT-TYPE
The SNMP agent software version. This variable may or may not have the same value as vpwrIdentControllerFirmwareVersion.
1.3.6.1.4.1.13858.2.1.4DisplayString (SIZE(0..15))read-onlycurrent
vpwrIdentName
OBJECT-TYPE
A string identifying the system. This object should be set by the administrator.
1.3.6.1.4.1.13858.2.1.5DisplayString (SIZE(0..31))read-writecurrent
vpwrSystemIdentTable
OBJECT-TYPE
This table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.2.1.6not-accessiblecurrent
vpwrSystemIdentEntry
OBJECT-TYPE
An entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.2.1.6.1not-accessiblecurrent
vpwrBayIndex
OBJECT-TYPE
Identifies Bay number that this module belongs to. The possible values are 1 through 16 limited by vpwrSystemShelfCapacity.
1.3.6.1.4.1.13858.2.1.6.1.1PositiveIntegerread-onlycurrent
vpwrModuleIndex
OBJECT-TYPE
This object identifies the module by its position in the shelf. Module numbering is left to right starting with module 1. So, the module in the first slot has an index of 1, the next module is 2 and so on.
1.3.6.1.4.1.13858.2.1.6.1.2PositiveIntegerread-onlycurrent
vpwrModuleOID
OBJECT-TYPE
It indicates the type of the module by specifiying its OID
1.3.6.1.4.1.13858.2.1.6.1.3OBJECT IDENTIFIERread-onlycurrent
vpwrModuleCurrent
OBJECT-TYPE
The meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Current for Rectifier module. - Not Applicable for LVD module
1.3.6.1.4.1.13858.2.1.6.1.4INTEGERread-onlycurrent
vpwrModuleOperStatus
OBJECT-TYPE
This object indicates current over all status of the module.
1.3.6.1.4.1.13858.2.1.6.1.5INTEGER {moduleStatusOK(0), moduleStatusAlarm(1), moduleStatusDisabled(2), moduleStatusRingerAOn(3), moduleStatusRingerBOn(4), moduleStatusUnknown(5)}read-onlycurrent
vpwrModuleCapacity
OBJECT-TYPE
The meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Capacity for Rectifier module. - Not Applicable for LVD module
1.3.6.1.4.1.13858.2.1.6.1.6INTEGERread-onlycurrent
vpwrSystemConfigGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.2.2
vpwrSystemTempCompensation
OBJECT-TYPE
This parameter enables/disables temperature compensation.
1.3.6.1.4.1.13858.2.2.1INTEGER {tempCompDisabled(0), tempCompEnabled(1)}read-writecurrent
vpwrSystemTempCompStartTemperature
OBJECT-TYPE
The temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.2.2.2INTEGER (25..60)read-writecurrent
vpwrSystemTempCompStopVoltage
OBJECT-TYPE
When temperature compensation is active, vpwrSystemTempCompStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to 51.75 volts enter a value of 5175.
1.3.6.1.4.1.13858.2.2.3INTEGERread-writecurrent
vpwrSystemTempCompensationSlope
OBJECT-TYPE
The rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.2.2.4INTEGER (0..250)read-writecurrent
vpwrSystemThermalSenseType
OBJECT-TYPE
This parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.2.2.5INTEGER {external(0), internal(1)}read-writecurrent
vpwrSystemHVAlarmSetpoint
OBJECT-TYPE
System High voltage alarm voltage setting.
1.3.6.1.4.1.13858.2.2.6INTEGERread-writecurrent
vpwrSystemBDAlarmSetpoint
OBJECT-TYPE
System Battery Discharge voltage setting.
1.3.6.1.4.1.13858.2.2.7INTEGERread-writecurrent
vpwrSystemInternalTempLThreshold
OBJECT-TYPE
Temperature value at which temperature compensation inactive (clear) trap would be sent if temperature compensation was active when this value is reached.
1.3.6.1.4.1.13858.2.2.8INTEGERread-writecurrent
vpwrSystemInternalTempUThreshold
OBJECT-TYPE
Temperature value at which temperature compensation active (set) trap would be sent.
1.3.6.1.4.1.13858.2.2.9INTEGERread-writecurrent
vpwrSystemParameterGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.2.3
vpwrSystemShelfCapacity
OBJECT-TYPE
It describes the maximum number of shelves that can/are controlled by the controller. Each shelf is uniquely numbered in the range from 1 to vpwrShelfCapacity.
1.3.6.1.4.1.13858.2.3.1INTEGER (1..16)read-onlycurrent
vpwrSystemVoltage
OBJECT-TYPE
The current system voltage.
1.3.6.1.4.1.13858.2.3.2INTEGERread-onlycurrent
vpwrSystemCurrent
OBJECT-TYPE
The current system current.
1.3.6.1.4.1.13858.2.3.3INTEGERread-onlycurrent
vpwrSystemControllerState
OBJECT-TYPE
Current System state as shown on the enhanced display.
1.3.6.1.4.1.13858.2.3.4INTEGER {systemControllerStateUnknown(0), systemControllerStateNormal(1), systemControllerStateChange(2), systemControllerStateAlarm(3), systemControllerStateMenu(4), systemControllerStateIrActive(5)}read-onlycurrent
vpwrSystemInternalTemperature
OBJECT-TYPE
The current controller internal temperature.
1.3.6.1.4.1.13858.2.3.5INTEGERread-onlycurrent
vpwrSystemTempCompensationState
OBJECT-TYPE
Active or Inactive. Applicable only if temperature compensation is enabled. This means that the controller is temperature compensating the float voltage.
1.3.6.1.4.1.13858.2.3.6INTEGER {systemTempCompInactive(0), systemTempCompActive(1)}read-onlycurrent
vpwrSystemType
OBJECT-TYPE
This parameter describes the type of the system being managed. This object is set by Valere Power Inc.
1.3.6.1.4.1.13858.2.3.7INTEGER {sysTypeUnknow(0), sysType48V(1), sysType24V(2), sysType12V(3)}read-onlycurrent
vpwrSystemPanelIdentGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.2.4
vpwrPanelIdentTable
OBJECT-TYPE
This table describes shelves and modules that make up the panels.
1.3.6.1.4.1.13858.2.4.1not-accessiblecurrent
vpwrPanelIdentEntry
OBJECT-TYPE
An entry containing information applicable to a particular panel making up the system.
1.3.6.1.4.1.13858.2.4.1.1not-accessiblecurrent
vpwrPanelBayIndex
OBJECT-TYPE
Identifies bay number that this module belongs to. The possible values are 1 through 16, starting from the top.
1.3.6.1.4.1.13858.2.4.1.1.1PositiveIntegerread-onlycurrent
vpwrPanelModuleIndex
OBJECT-TYPE
This object identifies the module within the panel. The orentation of modules within the panel is mappable.
1.3.6.1.4.1.13858.2.4.1.1.2PositiveIntegerread-onlycurrent
vpwrPanelModuleOID
OBJECT-TYPE
It indicates the type of the module by specifiying its OID
1.3.6.1.4.1.13858.2.4.1.1.3OBJECT IDENTIFIERread-onlycurrent
vpwrPanelModuleCurrent
OBJECT-TYPE
This is the Current of the first shunt of the module.
1.3.6.1.4.1.13858.2.4.1.1.4INTEGERread-onlycurrent
vpwrPanelModuleOperStatus
OBJECT-TYPE
This object indicates over all status of the module.
1.3.6.1.4.1.13858.2.4.1.1.5INTEGER {moduleStatusOK(0), moduleStatusAlarm(1)}read-onlycurrent
vpwrPanelModuleCapacity
OBJECT-TYPE
This is the overall Capacity of the module and is for reference only.
1.3.6.1.4.1.13858.2.4.1.1.6INTEGERread-onlycurrent
vpwrSystemBayctrlIdentGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.2.5
vpwrBayctrlIdentTable
OBJECT-TYPE
This table describes bay controllers that make up the system.
1.3.6.1.4.1.13858.2.5.1not-accessiblecurrent
vpwrBayctrlIdentEntry
OBJECT-TYPE
An entry containing information applicable to a particular bay controller making up the system.
1.3.6.1.4.1.13858.2.5.1.1not-accessiblecurrent
vpwrBayctrlIndex
OBJECT-TYPE
Identifies bay number that this module belongs to. The possible values are 0 through 15, starting from the top.
1.3.6.1.4.1.13858.2.5.1.1.1PositiveIntegerread-onlycurrent
vpwrBayctrlOID
OBJECT-TYPE
It indicates the type of the module by specifiying its OID
1.3.6.1.4.1.13858.2.5.1.1.2OBJECT IDENTIFIERread-onlycurrent
vpwrBayctrlCurrent
OBJECT-TYPE
This is the total output Current of the bay
1.3.6.1.4.1.13858.2.5.1.1.3INTEGERread-onlycurrent
vpwrBayctrlOperStatus
OBJECT-TYPE
This object indicates over all status of the bay
1.3.6.1.4.1.13858.2.5.1.1.4INTEGER {moduleStatusOK(0), moduleStatusAlarm(1)}read-onlycurrent
vpwrBayctrlCapacity
OBJECT-TYPE
This is the overall Capacity of the bay and is for reference only.
1.3.6.1.4.1.13858.2.5.1.1.5INTEGERread-onlycurrent
vpwrDcPowerRectifier
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3
vpwrRectifierConfigGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.1
vpwrRectifierFVSetpoint
OBJECT-TYPE
System Float Voltage setting
1.3.6.1.4.1.13858.3.1.1INTEGERread-writecurrent
vpwrRectifierHVSDSetpoint
OBJECT-TYPE
System High Voltage Shutdown voltage setting
1.3.6.1.4.1.13858.3.1.2INTEGERread-writecurrent
vpwrRectifierCurrentLimitAdminState
OBJECT-TYPE
This parameter allows enabling or disabling boost.
1.3.6.1.4.1.13858.3.1.3INTEGER {rectCurrentLimitDisabled(0), rectCurrentLimitEnabled(1)}read-writecurrent
vpwrRectifierCurrentLimit
OBJECT-TYPE
Rectifier current limit setpoint
1.3.6.1.4.1.13858.3.1.4INTEGER (5..200)read-writecurrent
vpwrRectifierAlarmGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2
vpwrRectAlarmDCFail
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.1current
vpwrRectAlarmBoostFail
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.2current
vpwrRectAlarmACFail
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.3current
vpwrRectAlarmHVSD
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.4current
vpwrRectAlarmFanFail
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.5current
vpwrRectAlarmAmbTemp
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.6current
vpwrRectAlarmIntTemp
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.7current
vpwrRectAlarmIShare
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.8current
vpwrRectAlarmUV
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.9current
vpwrRectAlarmLowVoltage
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.10current
vpwrRectAlarmReserved
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.11current
vpwrRectAlarmDCEnable
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.12current
vpwrRectAlarmRemoteShutdown
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.13current
vpwrRectAlarmModDisableShutdown
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.14current
vpwrRectAlarmShortPinShutdown
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.15current
vpwrRectAlarmBoostComm
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.2.16current
vpwrRectifierTestGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.3.3
vpwrDcPowerLvd
OBJECT-IDENTITY
1.3.6.1.4.1.13858.4
vpwrLvdConfigGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.4.1
vpwrLvdWarningSetpoint
OBJECT-TYPE
LVD Warning voltage setpoint.
1.3.6.1.4.1.13858.4.1.1INTEGERread-writecurrent
vpwrLvdDisconnectSetpoint
OBJECT-TYPE
LVD disconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.2INTEGERread-writecurrent
vpwrLvdReconnectSetpoint
OBJECT-TYPE
LVD Reconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.3INTEGERread-writecurrent
vpwrLvdReconnectDelayTimer
OBJECT-TYPE
The delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.1.4INTEGER (20..240)read-writecurrent
vpwrLvdContactorConfigTable
OBJECT-TYPE
This table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.4.1.5not-accessiblecurrent
vpwrLvdContactorConfigEntry
OBJECT-TYPE
An entry containing information applicable to a particular module making up the system.
1.3.6.1.4.1.13858.4.1.5.1not-accessiblecurrent
vpwrLvdContactorIndex
OBJECT-TYPE
contactor index
1.3.6.1.4.1.13858.4.1.5.1.1PositiveIntegerread-onlycurrent
vpwrLvdContactorWarningSetpoint
OBJECT-TYPE
LVD Warning voltage setpoint.
1.3.6.1.4.1.13858.4.1.5.1.2PositiveIntegerread-writecurrent
vpwrLvdContactorDisconnectSetpoint
OBJECT-TYPE
LVD disconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.5.1.3PositiveIntegerread-writecurrent
vpwrLvdContactorReconnectSetpoint
OBJECT-TYPE
LVD Reconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.5.1.4PositiveIntegerread-writecurrent
vpwrLvdContactorReconnectDelayTimer
OBJECT-TYPE
The delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.1.5.1.5PositiveInteger (0..240)read-writecurrent
vpwrLvdContactorState
OBJECT-TYPE
The delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.1.5.1.6INTEGER {contactorOpen(0), contactorClose(1)}read-writecurrent
vpwrLvdAlarmGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.4.2
vpwrLvdAlarmContactorOpen
OBJECT-IDENTITY
Contactor open
1.3.6.1.4.1.13858.4.2.1current
vpwrLvdAlarmCBOpen
OBJECT-IDENTITY
Circuit Breaker open
1.3.6.1.4.1.13858.4.2.2current
vpwrTrapLvdFuseOpen
OBJECT-IDENTITY
Fuse open
1.3.6.1.4.1.13858.4.2.3current
vpwrLvdAlarmWarning
OBJECT-IDENTITY
Plant Voltage below warning threshold
1.3.6.1.4.1.13858.4.2.4current
vpwrLvdTestGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.4.3
vpwrDcPowerTest
OBJECT-IDENTITY
1.3.6.1.4.1.13858.5
vpwrDcPowerModuleIdent
OBJECT-IDENTITY
1.3.6.1.4.1.13858.6
vpwrModuleIdentTable
OBJECT-TYPE
This table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.6.1not-accessiblecurrent
vpwrModuleIdentEntry
OBJECT-TYPE
An entry containing information applicable to a particular Module.
1.3.6.1.4.1.13858.6.1.1not-accessiblecurrent
vpwrModuleSerialNumber
OBJECT-TYPE
Serial Number of the module
1.3.6.1.4.1.13858.6.1.1.1DisplayStringread-onlycurrent
vpwrModuleModelNumber
OBJECT-TYPE
Model Number of the module.
1.3.6.1.4.1.13858.6.1.1.2DisplayStringread-onlycurrent
vpwrModuleFwVersion
OBJECT-TYPE
Firmware version of the module.
1.3.6.1.4.1.13858.6.1.1.3DisplayStringread-onlycurrent
vpwrModuleTestDate
OBJECT-TYPE
Date when the module was last tested.
1.3.6.1.4.1.13858.6.1.1.4DisplayStringread-onlycurrent
vpwrModuleOperHours
OBJECT-TYPE
Cumulative Operating Hours.
1.3.6.1.4.1.13858.6.1.1.5Counter32read-onlycurrent
vpwrPanelModuleIdentTable
OBJECT-TYPE
This table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.6.2not-accessiblecurrent
vpwrPanelModuleIdentEntry
OBJECT-TYPE
An entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.6.2.1not-accessiblecurrent
vpwrPanelModuleSerialNumber
OBJECT-TYPE
Serial Number of the module
1.3.6.1.4.1.13858.6.2.1.1DisplayStringread-onlycurrent
vpwrPanelModuleModelNumber
OBJECT-TYPE
Model Number of the module.
1.3.6.1.4.1.13858.6.2.1.2DisplayStringread-onlycurrent
vpwrPanelModuleFwVersion
OBJECT-TYPE
Firmware version of the module.
1.3.6.1.4.1.13858.6.2.1.3DisplayStringread-onlycurrent
vpwrPanelModuleTestDate
OBJECT-TYPE
Date when the module was last tested.
1.3.6.1.4.1.13858.6.2.1.4DisplayStringread-onlycurrent
vpwrPanelModuleOperHours
OBJECT-TYPE
Cumulative Operating Hours.
1.3.6.1.4.1.13858.6.2.1.5Counter32read-onlycurrent
vpwrBayctrlModuleIdentTable
OBJECT-TYPE
This table describes bay controllers that make up the sysetm.
1.3.6.1.4.1.13858.6.3not-accessiblecurrent
vpwrBayctrlModuleIdentEntry
OBJECT-TYPE
An entry containing information applicable to a particular bay controller.
1.3.6.1.4.1.13858.6.3.1not-accessiblecurrent
vpwrBayctrlSerialNumber
OBJECT-TYPE
Serial Number of the bay controller
1.3.6.1.4.1.13858.6.3.1.1DisplayStringread-onlycurrent
vpwrBayctrlModelNumber
OBJECT-TYPE
Model Number of the bay controller.
1.3.6.1.4.1.13858.6.3.1.2DisplayStringread-onlycurrent
vpwrBayctrlFwVersion
OBJECT-TYPE
Firmware version of the bay controller.
1.3.6.1.4.1.13858.6.3.1.3DisplayStringread-onlycurrent
vpwrBayctrlTestDate
OBJECT-TYPE
Date when the bayctrl was last tested.
1.3.6.1.4.1.13858.6.3.1.4DisplayStringread-onlycurrent
vpwrBayctrlOperHours
OBJECT-TYPE
Cumulative Operating Hours.
1.3.6.1.4.1.13858.6.3.1.5Counter32read-onlycurrent
vpwrDcPowerBatteryGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.7
vpwrBatteryTempGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.7.1
vpwrBatteryTempTable
OBJECT-TYPE
This table describes battery temperature probes.
1.3.6.1.4.1.13858.7.1.1not-accessiblecurrent
vpwrBatteryTempEntry
OBJECT-TYPE
An entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.7.1.1.1not-accessiblecurrent
vpwrBatteryTempIndex
OBJECT-TYPE
Index into temperature table
1.3.6.1.4.1.13858.7.1.1.1.1INTEGERread-onlycurrent
vpwrBatteryTempName
OBJECT-TYPE
A string identifying probe location.
1.3.6.1.4.1.13858.7.1.1.1.2DisplayString (SIZE(1..8))read-writecurrent
vpwrBatteryTemp
OBJECT-TYPE
Current temperature as recorded by the probe.
1.3.6.1.4.1.13858.7.1.1.1.3INTEGERread-onlycurrent
vpwrBatteryTempLThreshold
OBJECT-TYPE
Temperature value at which a clear trap would be sent. All three battery temperature must be at or below this value to trigger this trap.
1.3.6.1.4.1.13858.7.1.2INTEGERread-writecurrent
vpwrBatteryTempUThreshold
OBJECT-TYPE
Temperature value at which a set trap would be sent. Any one of the three battery temperatures at or exceeding this limit would trigger the trap.
1.3.6.1.4.1.13858.7.1.3INTEGERread-writecurrent
batteryTempCompensation
OBJECT-TYPE
This parameter enables/disables temperature compensation.
1.3.6.1.4.1.13858.7.1.4INTEGER {tempCompDisabled(0), tempCompEnabled(1)}read-writecurrent
batteryTempCompHighStartTemperature
OBJECT-TYPE
The temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.7.1.5INTEGER (25..60)read-writecurrent
batteryTempCompHighStopVoltage
OBJECT-TYPE
When temperature compensation is active, batteryTempCompHighStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to 51.75 volts enter a value of 5175.
1.3.6.1.4.1.13858.7.1.6INTEGERread-writecurrent
batteryTempCompHighSlope
OBJECT-TYPE
The rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.7.1.7INTEGER (0..250)read-writecurrent
batteryTempCompLowStartTemperature
OBJECT-TYPE
The temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.7.1.8INTEGERread-writecurrent
batteryTempCompLowStopVoltage
OBJECT-TYPE
When temperature compensation is active, batteryTempCompLowStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to 51.75 volts enter a value of 5175.
1.3.6.1.4.1.13858.7.1.9INTEGERread-writecurrent
batteryTempCompLowSlope
OBJECT-TYPE
The rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.7.1.10INTEGER (0..250)read-writecurrent
batteryTempCompRunawayTemperature
OBJECT-TYPE
The temperature at which system voltage will be set to batteryTempCompRunawayStopVoltage.
1.3.6.1.4.1.13858.7.1.11INTEGER (25..60)read-writecurrent
batteryTempCompRunawayStopVoltage
OBJECT-TYPE
When temperature compensation is enabled, float voltage will be reduced to batteryTempCompRunawayStopVoltage if temperature reaches batteryTempCompRunawayTemperature.
1.3.6.1.4.1.13858.7.1.12INTEGERread-writecurrent
batteryTempCompSenseSource
OBJECT-TYPE
This parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.7.1.13INTEGER {external(0), internal(1)}read-writecurrent
batteryTempCompRunawayState
OBJECT-TYPE
This parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.7.1.14INTEGER {inactive(0), active(1)}read-onlycurrent
thermalProbeTable
OBJECT-TYPE
This table describes battery temperature probes.
1.3.6.1.4.1.13858.7.1.15not-accessiblecurrent
thermalProbeEntry
OBJECT-TYPE
An entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.7.1.15.1not-accessiblecurrent
thermalProbeState
OBJECT-TYPE
State of thermal probe.
1.3.6.1.4.1.13858.7.1.15.1.1INTEGER {notPresent(0), present(1), removed(2), shorted(3)}read-onlycurrent
vpwrBatteryCurrentGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.7.2
vpwrBatteryCurrentLimitAdminState
OBJECT-TYPE
This parameter allows enabling or disabling battery current limit.
1.3.6.1.4.1.13858.7.2.1INTEGER {battetyCurrentLimitDisabled(0), battetyCurrentLimitEnabled(1)}read-writecurrent
vpwrBattetyCurrentLimitValue
OBJECT-TYPE
1.3.6.1.4.1.13858.7.2.2INTEGER (5..40)read-writecurrent
vpwrBattetyCurrentValue
OBJECT-TYPE
1.3.6.1.4.1.13858.7.2.3INTEGER (5..40)read-onlycurrent
vpwrBatteryBoostGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.7.3
vpwrBoostAdminState
OBJECT-TYPE
This parameter allows enabling or disabling boost.
1.3.6.1.4.1.13858.7.3.1INTEGER {boostDisabled(0), boostEnabled(1)}read-writecurrent
vpwrBoostVoltage
OBJECT-TYPE
1.3.6.1.4.1.13858.7.3.2INTEGER (7000..11000)read-writecurrent
vpwrBoostDuration
OBJECT-TYPE
1.3.6.1.4.1.13858.7.3.3INTEGER (0..100)read-writecurrent
vpwrBoostOperState
OBJECT-TYPE
This parameter allows starting or stoping boost if it is enabled.
1.3.6.1.4.1.13858.7.3.4INTEGER {boostInactive(0), boostActive(1)}read-writecurrent
vpwrBatteryDischargeTestGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.7.4
vpwrBDTAdminState
OBJECT-TYPE
Enable /Disable Battery Discharge Test execution.
1.3.6.1.4.1.13858.7.4.1INTEGER {bdtDisabled(0), bdtEnabled(1)}read-writecurrent
vpwrBDTDuration
OBJECT-TYPE
1.3.6.1.4.1.13858.7.4.2INTEGER (17..50)read-writecurrent
vpwrBDTAlarmVoltage
OBJECT-TYPE
1.3.6.1.4.1.13858.7.4.3INTEGER (7000..11000)read-writecurrent
vpwrBDTAbortVoltage
OBJECT-TYPE
1.3.6.1.4.1.13858.7.4.4INTEGER (0..5600)read-writecurrent
vpwrBDTAlarmCoefficient
OBJECT-TYPE
1.3.6.1.4.1.13858.7.4.5INTEGER (0..1)read-writecurrent
vpwrBDTOperState
OBJECT-TYPE
Start/Stop Battery Discharge Test execution.
1.3.6.1.4.1.13858.7.4.6INTEGER {bdtInactive(0), bdtActive(1)}read-writecurrent
vpwrBDTClearAlarm
OBJECT-TYPE
Clears any active bdt alarm.
1.3.6.1.4.1.13858.7.4.7INTEGER {bdtNoAlarm(0), bdtAlarmPresent(1)}read-writecurrent
vpwrDcPowerAlarmGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.8
vpwrAlarmsPresent
OBJECT-TYPE
The present number of active alarm conditions.
1.3.6.1.4.1.13858.8.1Gauge32read-onlycurrent
vpwrAlarmTable
OBJECT-TYPE
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The vpwrAlarmIndex, for each type of module starts at 1 and is limited by the total number of alarams that can be generated by the module. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), vpwrAlarmDescr, to allow a single table to reflect alarms for different type of modules. The number of rows in the table at any given time is reflected by the value of vpwrAlarmsPresent.
1.3.6.1.4.1.13858.8.2not-accessiblecurrent
vpwrAlarmEntry
OBJECT-TYPE
An entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.8.2.1not-accessiblecurrent
vpwrAlarmIndex
OBJECT-TYPE
Identifies the alarm associated with the module. It is unique on per module type basis. For example, multiple rectifiers can have the same alarm and therefore same vpwrAlarmIndex active at any one time.
1.3.6.1.4.1.13858.8.2.1.1PositiveIntegerread-onlycurrent
vpwrAlarmDescr
OBJECT-TYPE
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
1.3.6.1.4.1.13858.8.2.1.2AutonomousTyperead-onlycurrent
vpwrAlarmTime
OBJECT-TYPE
The value of sysUpTime when the alarm condition was detected.
1.3.6.1.4.1.13858.8.2.1.3TimeStampread-onlycurrent
sysRelayConfigTable
OBJECT-TYPE
This table describes battery temperature probes.
1.3.6.1.4.1.13858.8.3not-accessiblecurrent
sysRelayConfigEntry
OBJECT-TYPE
An entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.8.3.1not-accessiblecurrent
sysRelayIndex
OBJECT-TYPE
Index into temperature table
1.3.6.1.4.1.13858.8.3.1.1INTEGERread-onlycurrent
sysRelayDefaultName
OBJECT-TYPE
A string identifying probe location.
1.3.6.1.4.1.13858.8.3.1.2DisplayString (SIZE(1..8))read-onlycurrent
sysRelayCustomName
OBJECT-TYPE
A string identifying probe location.
1.3.6.1.4.1.13858.8.3.1.3DisplayString (SIZE(1..8))read-writecurrent
sysRelayAlarmSeverity
OBJECT-TYPE
Current temperature as recorded by the probe.
1.3.6.1.4.1.13858.8.3.1.4INTEGER {alarmNone(0), alarmMajor(1), alarmMinor(2), alarmMajorAndMinor(3)}read-writecurrent
sysAlarmConfigTable
OBJECT-TYPE
This table describes battery temperature probes.
1.3.6.1.4.1.13858.8.4not-accessiblecurrent
sysAlarmConfigEntry
OBJECT-TYPE
An entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.8.4.1not-accessiblecurrent
sysAlarmIndex
OBJECT-TYPE
Index into temperature table
1.3.6.1.4.1.13858.8.4.1.1INTEGERread-onlycurrent
sysAlarmDefaultName
OBJECT-TYPE
A string identifying probe location.
1.3.6.1.4.1.13858.8.4.1.2DisplayString (SIZE(1..8))read-onlycurrent
sysAlarmCustomName
OBJECT-TYPE
A string identifying probe location.
1.3.6.1.4.1.13858.8.4.1.3DisplayString (SIZE(1..8))read-writecurrent
sysAlarmSeverity
OBJECT-TYPE
Alarm Severity as denoted by Major and Minor Alarm Mask
1.3.6.1.4.1.13858.8.4.1.4INTEGER {none(0), major(1), minor(2), majorAndMinor(3)}read-writecurrent
sysAlarmToRelayMapping
OBJECT-TYPE
No additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A and B = (1 + 2) and so on The major/minor classification of alarms automatically associates it with Major/Minor relay. Assigning a null mapping here does not override sysRelayAlarmSeverity for the alarm. It should be used to define mapping to additional relays.
1.3.6.1.4.1.13858.8.4.1.5DisplayString (SIZE(1..8))read-writecurrent
sysAlarmOperStatus
OBJECT-TYPE
Indicates current alarm status
1.3.6.1.4.1.13858.8.4.1.6INTEGER {inactive(0), active(1)}read-onlycurrent
sysAuxAlarmConfigTable
OBJECT-TYPE
This table describes battery temperature probes.
1.3.6.1.4.1.13858.8.5not-accessiblecurrent
sysAuxAlarmConfigEntry
OBJECT-TYPE
An entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.8.5.1not-accessiblecurrent
sysAuxAlarmIndex
OBJECT-TYPE
Index into temperature table
1.3.6.1.4.1.13858.8.5.1.1INTEGERread-onlycurrent
sysAuxAlarmDefaultName
OBJECT-TYPE
A string identifying probe location.
1.3.6.1.4.1.13858.8.5.1.2DisplayString (SIZE(1..8))read-onlycurrent
sysAuxAlarmCustomName
OBJECT-TYPE
A string identifying probe location.
1.3.6.1.4.1.13858.8.5.1.3DisplayString (SIZE(1..8))read-writecurrent
sysAuxAlarmSeverity
OBJECT-TYPE
Aux Alarm Severity
1.3.6.1.4.1.13858.8.5.1.4INTEGER {none(0), major(1), minor(2), majorAndMinor(3)}read-writecurrent
sysAuxAlarmToRelayMapping
OBJECT-TYPE
No additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A and B = (1 + 2) and so on The major/minor classification of alarms automatically associates it with Major/Minor relay. Assigning a null mapping here does not override sysRelayAlarmSeverity for the alarm. It should be used to define mapping to additional relays.
1.3.6.1.4.1.13858.8.5.1.5DisplayString (SIZE(1..8))read-writecurrent
sysAuxAlarmPolarity
OBJECT-TYPE
Current temperature as recorded by the probe.
1.3.6.1.4.1.13858.8.5.1.6INTEGER {alarmOnOpen(0), alarmOnClose(1)}read-writecurrent
sysAuxAlarmOperStatus
OBJECT-TYPE
Indicates current alarm status
1.3.6.1.4.1.13858.8.5.1.7INTEGER {inactive(0), active(1)}read-onlycurrent
sysAlarmComFailState
OBJECT-TYPE
Enable/Disable generation of comm fail alarm.
1.3.6.1.4.1.13858.8.6INTEGER {disabled(0), enabled(1), other(2)}read-writecurrent
sysAlarmIShareState
OBJECT-TYPE
Enable/Disable generation of current share alarm.
1.3.6.1.4.1.13858.8.7INTEGER {disabled(0), enabled(1), other(2)}read-writecurrent
sysAlarmRedundancyState
OBJECT-TYPE
Enable/Disable generation of redundancy alarm.
1.3.6.1.4.1.13858.8.8INTEGER {disabled(0), nPlus1(1), nPlus2(2)}read-writecurrent
vpwrDcPowerSnmpConfig
OBJECT-IDENTITY
1.3.6.1.4.1.13858.9
vpwrTrapTable
OBJECT-TYPE
A list of possible trap destinations depending upon the criticality of the trap.
1.3.6.1.4.1.13858.9.1not-accessiblecurrent
vpwrTrapEntry
OBJECT-TYPE
An entry containing information applicable to a particular trap destination.
1.3.6.1.4.1.13858.9.1.1not-accessiblecurrent
vpwrTrapIpIndex
OBJECT-TYPE
Trap Entry Index
1.3.6.1.4.1.13858.9.1.1.1INTEGERread-onlycurrent
vpwrTrapIpAddress
OBJECT-TYPE
Trap destination IP Address
1.3.6.1.4.1.13858.9.1.1.2IpAddressread-writecurrent
vpwrTrapCriticality
OBJECT-TYPE
Criticality of traps sent to this IP Address
1.3.6.1.4.1.13858.9.1.1.3INTEGERread-writecurrent
vpwrReadCommunityString
OBJECT-TYPE
This allows setting password to be able to do Get operations
1.3.6.1.4.1.13858.9.2DisplayString (SIZE(3..8))read-writecurrent
vpwrWriteCommunityString
OBJECT-TYPE
This allows setting password to be able to do Get and Set operations. The read-access is not allowed in the actual implementation.
1.3.6.1.4.1.13858.9.3DisplayString (SIZE(3..8))read-writecurrent
vpwrTrapCommunityString
OBJECT-TYPE
This allows setting community string required for the trap to be accepted at the destination.
1.3.6.1.4.1.13858.9.4DisplayString (SIZE(3..8))read-writecurrent
vpwrDcPowerTraps
OBJECT-IDENTITY
1.3.6.1.4.1.13858.10
vpwrDcPowerTrapsMsgString
OBJECT-IDENTITY
1.3.6.1.4.1.13858.11
vpwrTrapsMsgString
OBJECT-TYPE
Place holder for trap notification message string
1.3.6.1.4.1.13858.11.1DisplayString (SIZE(0..127))not-accessiblecurrent
vpwrTrapUserIpAddress
OBJECT-TYPE
Place holder for IP address of the user accessing the system
1.3.6.1.4.1.13858.11.2IpAddressnot-accessiblecurrent
vpwrTrapEventTimeStamp
OBJECT-TYPE
Place holder for time-stamp.
1.3.6.1.4.1.13858.11.3IpAddressnot-accessiblecurrent
vpwrDcPowerRinger
OBJECT-IDENTITY
1.3.6.1.4.1.13858.12
vpwrRingerConfigGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.12.1
vpwrRingerParameterTable
OBJECT-TYPE
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The vpwrAlarmIndex, for each type of module starts at 1 and is limited by the total number of alarams that can be generated by the module. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), vpwrAlarmDescr, to allow a single table to reflect alarms for different type of modules. The number of rows in the table at any given time is reflected by the value of vpwrAlarmsPresent.
1.3.6.1.4.1.13858.12.1.1not-accessiblecurrent
vpwrRingerParameterEntry
OBJECT-TYPE
An entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.12.1.1.1not-accessiblecurrent
vpwrRingerIndex
OBJECT-TYPE
This parameter allows selecting ringer A or Ringer B as the active ringer.
1.3.6.1.4.1.13858.12.1.1.1.1INTEGERread-onlycurrent
vpwrRingerParameterAdminState
OBJECT-TYPE
This parameter allows selecting ringer A or Ringer B as the active ringer.
1.3.6.1.4.1.13858.12.1.1.1.2INTEGER {ringerDisabled(0), ringerAOn(1), ringerBOn(2)}read-writecurrent
vpwrRingerParameterAcVoltage
OBJECT-TYPE
1.3.6.1.4.1.13858.12.1.1.1.3INTEGER (7000..11000)read-writecurrent
vpwrRingerParameterDcVoltage
OBJECT-TYPE
1.3.6.1.4.1.13858.12.1.1.1.4INTEGER (0..5600)read-writecurrent
vpwrRingerParameterFrequency
OBJECT-TYPE
1.3.6.1.4.1.13858.12.1.1.1.5INTEGER (17..50)read-writecurrent
vpwrRingerNumberPresent
OBJECT-TYPE
The present number of active alarm conditions.
1.3.6.1.4.1.13858.12.1.2Gauge32read-onlycurrent
vpwrRingerAlarmGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.12.2
vpwrRingerAlarmaAFailed
OBJECT-IDENTITY
Ringer A Failed
1.3.6.1.4.1.13858.12.2.1current
vpwrRingerAlarmAOTemp
OBJECT-IDENTITY
Ringer A Heatsink Over-Temperature
1.3.6.1.4.1.13858.12.2.2current
vpwrRingerAlarmAOCurrent
OBJECT-IDENTITY
Ringer A Over-Current protection
1.3.6.1.4.1.13858.12.2.3current
vpwrRingerAlarmaBFailed
OBJECT-IDENTITY
Ringer A Failed
1.3.6.1.4.1.13858.12.2.4current
vpwrRingerAlarmBOverTemp
OBJECT-IDENTITY
Ringer A Heatsink Over-Temperature
1.3.6.1.4.1.13858.12.2.5current
vpwrRingerAlarmBOverCurrent
OBJECT-IDENTITY
Ringer A Over-Current protection
1.3.6.1.4.1.13858.12.2.6current
vpwrRingerTestGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.12.3
vpwrDcPowerDcDcConverter
OBJECT-IDENTITY
1.3.6.1.4.1.13858.13
vpwrDcDcConverterConfigGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.13.1
vpwrDcDcConverterAlarmGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.13.2
vpwrDcDcConverterTestGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.13.3
vpwrDcPowerDcAcInverter
OBJECT-IDENTITY
1.3.6.1.4.1.13858.14
vpwrDcAcInverterConfigGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.14.1
vpwrDcAcInverterAlarmGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.14.2
vpwrDcAcInverterTestGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.14.3
vpwrDcPowerBayController
OBJECT-IDENTITY
1.3.6.1.4.1.13858.15
vpwrDcPowerIoModule
OBJECT-IDENTITY
1.3.6.1.4.1.13858.16
vpwrIoModuleConfigGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.16.1
vpwrIoModuleAlarmGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.16.2
vpwrIoModuleTestGroup
OBJECT-IDENTITY
1.3.6.1.4.1.13858.16.3
vpwrDcPowerDist
OBJECT-IDENTITY
1.3.6.1.4.1.13858.17
vpwrDcPowerTrio
OBJECT-IDENTITY
1.3.6.1.4.1.13858.18

Notifications

NameOIDStatus
vpwrTrapPowerMajorAlarm
NOTIFICATION-TYPE
Major Alarm
1.3.6.1.4.1.13858.10.0.1
vpwrTrapPowerMinorAlarm
NOTIFICATION-TYPE
Minor Alarm
1.3.6.1.4.1.13858.10.0.2
vpwrTrapACFAlarm
NOTIFICATION-TYPE
AC Fail Alarm
1.3.6.1.4.1.13858.10.0.3
vpwrTrapHVAlarm
NOTIFICATION-TYPE
High Voltage Warning Alarm
1.3.6.1.4.1.13858.10.0.4
vpwrTrapHVSDAlarm
NOTIFICATION-TYPE
High Voltage Shutdown Alarm
1.3.6.1.4.1.13858.10.0.5
vpwrTrapBDAlarm
NOTIFICATION-TYPE
Battery on Discharge Alarm
1.3.6.1.4.1.13858.10.0.6
vpwrTrapLVDWarningAlarm
NOTIFICATION-TYPE
LVD Warning Alarm
1.3.6.1.4.1.13858.10.0.7
vpwrTrapLVDOpenAlarm
NOTIFICATION-TYPE
LVD Open Alarm
1.3.6.1.4.1.13858.10.0.8
vpwrTrapDistAlarm
NOTIFICATION-TYPE
Distribution Open Alarm
1.3.6.1.4.1.13858.10.0.9
vpwrTrapAuxAlarm
NOTIFICATION-TYPE
Auxiliary System Alarm
1.3.6.1.4.1.13858.10.0.10
vpwrTrapSystemRedundancyAlarm
NOTIFICATION-TYPE
System Redundant Capacity Alarm
1.3.6.1.4.1.13858.10.0.11
vpwrTrapIShareAlarm
NOTIFICATION-TYPE
Rectifier Current Share Alarm
1.3.6.1.4.1.13858.10.0.12
vpwrTrapModuleFailAlarm
NOTIFICATION-TYPE
Single Rectifier Fail Alarm
1.3.6.1.4.1.13858.10.0.13
vpwrTrapMultipleModuleFailAlarm
NOTIFICATION-TYPE
Multiple Rectifier Fail Alarm
1.3.6.1.4.1.13858.10.0.14
vpwrTrapModuleCommAlarm
NOTIFICATION-TYPE
Module Communication Alarm
1.3.6.1.4.1.13858.10.0.15
vpwrTrapSystemOverTemperatureAlarm
NOTIFICATION-TYPE
System Over Temperature Alarm
1.3.6.1.4.1.13858.10.0.16
vpwrTrapSystemOK
NOTIFICATION-TYPE
SYSTEM OK - No Active Alarms
1.3.6.1.4.1.13858.10.0.17
vpwrTrapModuleInserted
NOTIFICATION-TYPE
A new module has been inserted into the system.
1.3.6.1.4.1.13858.10.0.18
vpwrTrapModuleRemoved
NOTIFICATION-TYPE
A module has been removed from the system.
1.3.6.1.4.1.13858.10.0.19
vpwrTrapThermalCompActive
NOTIFICATION-TYPE
Thermal compensation has become active.
1.3.6.1.4.1.13858.10.0.20
vpwrTrapThermalCompInactive
NOTIFICATION-TYPE
Thermal compensation has been de-activated.
1.3.6.1.4.1.13858.10.0.21
vpwrTrapInternalTempAlarmSet
NOTIFICATION-TYPE
Internal Temperature upper threshold exceeded.
1.3.6.1.4.1.13858.10.0.22
vpwrTrapInternalTempAlarmCleared
NOTIFICATION-TYPE
Internal Temperature within limits
1.3.6.1.4.1.13858.10.0.23
vpwrTrapBatteryTempAlarmSet
NOTIFICATION-TYPE
At least one Battery Temperature exceeded upper threshold.
1.3.6.1.4.1.13858.10.0.24
vpwrTrapBatteryTempAlarmCleared
NOTIFICATION-TYPE
All Battery Temperatures within limits.
1.3.6.1.4.1.13858.10.0.25
vpwrTrapLoginFail
NOTIFICATION-TYPE
Admin login failed due to wrong username/password.
1.3.6.1.4.1.13858.10.0.26
vpwrTrapLoginSuccess
NOTIFICATION-TYPE
Admin login successful.
1.3.6.1.4.1.13858.10.0.27
vpwrTrapLogout
NOTIFICATION-TYPE
Admin logout.
1.3.6.1.4.1.13858.10.0.28
vpwrTrapAdminPwdChange
NOTIFICATION-TYPE
Config change submitted with invalid access.
1.3.6.1.4.1.13858.10.0.29
vpwrTrapIllegalConfigSubmit
NOTIFICATION-TYPE
Config change submitted with invalid access.
1.3.6.1.4.1.13858.10.0.30
vpwrTrapCfgChange
NOTIFICATION-TYPE
Config change submitted.
1.3.6.1.4.1.13858.10.0.31
vpwrTrapClearEventHistory
NOTIFICATION-TYPE
Clear Event history buffer clear request.
1.3.6.1.4.1.13858.10.0.32
vpwrTrapSwDownloadNoReboot
NOTIFICATION-TYPE
System software upgrade without reboot.
1.3.6.1.4.1.13858.10.0.33
vpwrTrapSwDownloadAndReboot
NOTIFICATION-TYPE
System reboot due to software upgrade.
1.3.6.1.4.1.13858.10.0.34
vpwrTrapSystemClockChange
NOTIFICATION-TYPE
System clock updated.
1.3.6.1.4.1.13858.10.0.35
vpwrTrapModuleAlarm
NOTIFICATION-TYPE
Module Alarm.
1.3.6.1.4.1.13858.10.0.36
vpwrTrapOIDChange
NOTIFICATION-TYPE
Change in OID.
1.3.6.1.4.1.13858.10.0.37
vpwrTrapThermalRunaway
NOTIFICATION-TYPE
Thermal Runaway Alarm.
1.3.6.1.4.1.13858.10.0.38
vpwrTrapBatteryDischargeTestAlarm
NOTIFICATION-TYPE
System Voltage dropped to BDT Alarm Setpoint.
1.3.6.1.4.1.13858.10.0.39
vpwrTrapRingerAAlarm
NOTIFICATION-TYPE
Ringer A Fail Alarm.
1.3.6.1.4.1.13858.10.0.40
vpwrTrapRingerBAlarm
NOTIFICATION-TYPE
Ringer B Fail Alarm.
1.3.6.1.4.1.13858.10.0.41
vpwrTrapSingleRingerAlarm
NOTIFICATION-TYPE
Single Ringer Fail Alarm.
1.3.6.1.4.1.13858.10.0.42
vpwrTrapMultipleRingerAlarm
NOTIFICATION-TYPE
Multiple Ringer Fail Alarm.
1.3.6.1.4.1.13858.10.0.43
vpwrTrapThermalProbeAlarm
NOTIFICATION-TYPE
Thermal Probe Missing Alarm.
1.3.6.1.4.1.13858.10.0.44
vpwrTrapRingerCommAlarm
NOTIFICATION-TYPE
Ringer Communication Alarm.
1.3.6.1.4.1.13858.10.0.45
vpwrTrapDistributionCommAlarm
NOTIFICATION-TYPE
Distribution Communication Alarm.
1.3.6.1.4.1.13858.10.0.46
vpwrTrapConverterAlarm
NOTIFICATION-TYPE
Single Converter Fail Alarm.
1.3.6.1.4.1.13858.10.0.47
vpwrTrapMultipleConvFailAlarm
NOTIFICATION-TYPE
Multiple Converter Fail Alarm.
1.3.6.1.4.1.13858.10.0.48
vpwrTrapUnmappedAddressAlarm
NOTIFICATION-TYPE
Unmapped I2C Address.
1.3.6.1.4.1.13858.10.0.49
vpwrTrapConfigErrorAlarm
NOTIFICATION-TYPE
Configuration Error.
1.3.6.1.4.1.13858.10.0.50
vpwrTrapDisplayFirmwareMismatchAlarm
NOTIFICATION-TYPE
Display Firmware Mismatch.
1.3.6.1.4.1.13858.10.0.51
vpwrTrapConverterInputFailAlarm
NOTIFICATION-TYPE
Converter Input Fail Alarm.
1.3.6.1.4.1.13858.10.0.52
vpwrTrapBatteryRechgIlimitFailAlarm
NOTIFICATION-TYPE
Battery Recharge Current Limit Fail.
1.3.6.1.4.1.13858.10.0.53
vpwrTrapSystemAlive
NOTIFICATION-TYPE
Periodic Keepalive trap.
1.3.6.1.4.1.13858.10.0.54