UPS2-MIB
- Registered at
- 1.3.6.1.4.1.52.4.1.1.10.11.3.6.1.4.1.52.4.1.1.10.21.3.6.1.4.1.52.4.1.1.10.31.3.6.1.4.1.52.4.1.1.10.41.3.6.1.4.1.52.4.1.1.10.51.3.6.1.4.1.52.4.1.1.10.61.3.6.1.4.1.52.4.1.1.10.71.3.6.1.4.1.52.4.1.1.10.81.3.6.1.4.1.52.4.1.1.10.9
- Namespace
- enterasys
- Source file
UPS2-MIB- Digest
sha256:760f376592f33f5b3a60a3476f74bb1d8c89eee15093341741256dda4affd60f
Imports
| From | Symbols |
|---|---|
| CTRON-MIB-NAMES | ctUPS |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
CTRON-MIB-NAMES CTRON-OIDS SNMPv2-CONF SNMPv2-SMI SNMPv2-TC UPS2-MIB
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| upsSystem OBJECT-IDENTITY | 1.3.6.1.4.1.52.4.1.1.10.1 | |||
| upsNumUPSs OBJECT-TYPE The number of UPSs available. | 1.3.6.1.4.1.52.4.1.1.10.1.1 | INTEGER (0..2) | read-only | mandatory |
| upsId OBJECT-IDENTITY | 1.3.6.1.4.1.52.4.1.1.10.2 | |||
| upsIdTable OBJECT-TYPE A list of identification table entries. The number of entries is given by the value of upsNumUPSs. | 1.3.6.1.4.1.52.4.1.1.10.2.1 | not-accessible | mandatory | |
| upsIdEntry OBJECT-TYPE An entry containing objects for a particular UPS. | 1.3.6.1.4.1.52.4.1.1.10.2.1.1 | not-accessible | mandatory | |
| upsIndex OBJECT-TYPE A unique value which identifies a particular UPS. | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.1 | INTEGER | read-only | mandatory |
| upsName OBJECT-TYPE The UPS's name. A maximum of 8 characters may be specified. This object is initialized to the UPS's model name. | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.2 | DisplayString (SIZE(0..8)) | read-write | mandatory |
| upsModelType OBJECT-TYPE The UPS's base model type. | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.3 | INTEGER {smartUps250(1), smartUps400(2), smartUps600(3), smartUps900(4), smartUps1250(5), smartUps2000(6), matrixUps3000(7), matrixUps5000(8), other(9)} | read-only | mandatory |
| upsFwVersion OBJECT-TYPE The UPS's firmware version. | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.4 | DisplayString (SIZE(0..8)) | read-only | mandatory |
| upsSerialNumber OBJECT-TYPE The UPS's serial number as set at the factory. | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.5 | DisplayString (SIZE(0..16)) | read-only | mandatory |
| upsManufDate OBJECT-TYPE The UPS's date of manufacture in the format mm/dd/yy. | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.6 | DisplayString (SIZE(0..8)) | read-only | mandatory |
| upsBattery OBJECT-IDENTITY | 1.3.6.1.4.1.52.4.1.1.10.3 | |||
| upsBatteryTable OBJECT-TYPE A list of battery table entries. The number of entries is given by the value of upsNumUPSs. | 1.3.6.1.4.1.52.4.1.1.10.3.1 | not-accessible | mandatory | |
| upsBatteryEntry OBJECT-TYPE An entry containing objects for a particular UPS. | 1.3.6.1.4.1.52.4.1.1.10.3.1.1 | not-accessible | mandatory | |
| upsBatteryCapacity OBJECT-TYPE The UPS's remaining battery capacity expressed as a percent of the fully charged condition. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10). | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.1 | INTEGER | read-only | mandatory |
| upsBatteryVoltage OBJECT-TYPE The UPS's present battery voltage. The value of this object is the actual voltage * 100 (that is, to determine the actual voltage, divide the value of this object by 100). | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.2 | INTEGER | read-only | mandatory |
| upsBatteryTest OBJECT-TYPE This object may be written to initiate testing of the UPS's battery packs. Reading this object will always return a 0. | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.3 | INTEGER {initiateTest(1)} | read-write | mandatory |
| upsBatteryTestResult OBJECT-TYPE The result of the last battery test performed. | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.4 | INTEGER {batteryOK(1), batteryBad(2), noRecentTest(3), invalidTestDueToOverload(4)} | read-only | mandatory |
| upsRunTimeCalibration OBJECT-TYPE This object may be written to initiate or terminate the test used to calibrate the returned run time value. This test will only run if battery capacity is 100%. Results of this test can be retrieved by upsEstimatedRunTimeRemaining. Valid values for writing are 1 (initiate test) and 2 (terminate test). In addition, this object may be read to determine whether the test is currently running. Valid values for reading are 3 (test is in progress) and 4 (test is not in progress). | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.5 | INTEGER {performTest(1), abortTest(2), testInProgress(3), testNotInProgress(4)} | read-write | mandatory |
| upsEstimatedRunTimeRemaining OBJECT-TYPE The UPS's estimated remaining run time in minutes. The UPS may be queried when operating in the on-line, bypass, or on-battery modes of operation. The run time estimate is based on available battery capacity and output load. | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.6 | INTEGER | read-only | mandatory |
| upsTransferCause OBJECT-TYPE The reason for the most recent transfer to on-battery operation. | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.7 | INTEGER {noTransfer(1), selfTest(2), inputLineSpike(3), inputLowVoltage(4), inputHighVoltage(5), inputLineFrequencyBad(6)} | read-only | mandatory |
| upsBatteryTestTime OBJECT-TYPE The frequency of execution of the UPS's automatic battery test. The test may be run immediately upon startup, upon startup and every 7 days thereafter, upon startup and every 14 days thereafter, or never. | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.8 | INTEGER {twoWeeks(1), oneWeek(2), startupOnly(3), off(4)} | read-write | mandatory |
| upsLowBatteryWarning OBJECT-TYPE The interval between activation of the UPS's low battery alarm warnings and shutdown of the UPS. | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.9 | INTEGER {twoMinutes(1), fiveMinutes(2), sevenMinutes(3), tenMinutes(4)} | read-write | mandatory |
| upsInput OBJECT-IDENTITY | 1.3.6.1.4.1.52.4.1.1.10.4 | |||
| upsInputTable OBJECT-TYPE A list of input table entries. The number of entries is given by the value of upsNumUPSs. | 1.3.6.1.4.1.52.4.1.1.10.4.1 | not-accessible | mandatory | |
| upsInputEntry OBJECT-TYPE An entry containing objects for a particular UPS. | 1.3.6.1.4.1.52.4.1.1.10.4.1.1 | not-accessible | mandatory | |
| upsInputUtilityVoltage OBJECT-TYPE The UPS's utility voltage version. | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.1 | INTEGER {vac100(1), vac120(2), vac208(3), vac220(4)} | read-only | mandatory |
| upsInputVoltage OBJECT-TYPE The UPS's measured utility input voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.2 | INTEGER | read-only | mandatory |
| upsInputFailureSensitivity OBJECT-TYPE The sensitivity of the UPS to rapid changes in utility voltage (e.g., blackouts, spikes, or notches) or abnormal changes in utility frequency. | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.3 | INTEGER {high(1), medium(2), low(3), auto(4)} | read-write | mandatory |
| upsInputMaxVoltage OBJECT-TYPE The UPS's maximum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.4 | INTEGER | read-only | mandatory |
| upsInputMinVoltage OBJECT-TYPE The UPS's minimum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.5 | INTEGER | read-only | mandatory |
| upsInputFrequency OBJECT-TYPE The UPS's present internal operating frequency in Hz. The value of this object is the actual frequency * 100 (that is, to determine the actual frequency, divide the value of this object by 100). | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.6 | INTEGER | read-only | mandatory |
| upsOutput OBJECT-IDENTITY | 1.3.6.1.4.1.52.4.1.1.10.5 | |||
| upsOutputTable OBJECT-TYPE A list of output table entries. The number of entries is given by the value of upsNumUPSs. | 1.3.6.1.4.1.52.4.1.1.10.5.1 | not-accessible | mandatory | |
| upsOutputEntry OBJECT-TYPE An entry containing objects for a particular UPS. | 1.3.6.1.4.1.52.4.1.1.10.5.1.1 | not-accessible | mandatory | |
| upsOutputVoltage OBJECT-TYPE The measured UPS output voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). | 1.3.6.1.4.1.52.4.1.1.10.5.1.1.1 | INTEGER | read-only | mandatory |
| upsOutputUtilityVoltage OBJECT-TYPE The UPS's current on-battery output voltage setting (valid for 220/230/240 Vac version UPSs only). For other version UPSs, reading this object will always return a 0 and writing this object will have no effect. | 1.3.6.1.4.1.52.4.1.1.10.5.1.1.2 | INTEGER {vac225(1), vac230(2), vac240(3), vac220(4)} | read-write | mandatory |
| upsOutputPower OBJECT-TYPE The UPS's output load represented as a percentage of full rated load in Watts. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10). | 1.3.6.1.4.1.52.4.1.1.10.5.1.1.3 | INTEGER | read-only | mandatory |
| upsStatus OBJECT-IDENTITY | 1.3.6.1.4.1.52.4.1.1.10.6 | |||
| upsStatusTable OBJECT-TYPE A list of status table entries. The number of entries is given by the value of upsNumUPSs. | 1.3.6.1.4.1.52.4.1.1.10.6.1 | not-accessible | mandatory | |
| upsStatusEntry OBJECT-TYPE An entry containing objects for a particular UPS. | 1.3.6.1.4.1.52.4.1.1.10.6.1.1 | not-accessible | mandatory | |
| upsStatusOperational OBJECT-TYPE This object contains 8 bits of information about the current operational status of the UPS. The bits are encoded as follows: BIT 7: 1=replace battery condition BIT 6: 1=low battery condition BIT 5: 1=overloaded output condition BIT 4: 1=on-battery mode of operation BIT 3: 1=on-line mode of operation BIT 2: 1=Smart Boost mode of operation (where applicable) BIT 1: 1=UPS shut down due to low battery, overload, or `sleep' mode BIT 0: 1=run time calibration running Note that bit 0 is the low-order bit. | 1.3.6.1.4.1.52.4.1.1.10.6.1.1.1 | INTEGER | read-only | mandatory |
| upsStatusFault OBJECT-TYPE This object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows: BIT 7: 1=UPS fault - internal temperature has exceeded nominal limits BIT 6: 1=UPS fault - bypass relay (where applicable) malfunction BIT 5: 1=UPS fault - battery charger failure BIT 4: 1=UPS in shut down mode via `S' command BIT 3: 1=UPS in `sleep' mode via `@ddd' command BIT 2: 1=UPS fault - main relay malfunction BIT 1: 1=UPS unable to transfer to on-battery operation due to overload BIT 0: 1=UPS's output unpowered due to low battery shut down Note that bit 0 is the low-order bit. | 1.3.6.1.4.1.52.4.1.1.10.6.1.1.2 | INTEGER | read-only | mandatory |
| upsStatusTemp OBJECT-TYPE The UPS's present internal operating temperature in degrees Fahrenheit. The value of this object is the actual temperature * 10 (that is, to determine the actual temperature, divide the value of this object by 10). | 1.3.6.1.4.1.52.4.1.1.10.6.1.1.3 | INTEGER | read-only | mandatory |
| upsConfig OBJECT-IDENTITY | 1.3.6.1.4.1.52.4.1.1.10.7 | |||
| upsConfigTable OBJECT-TYPE A list of configuration table entries. The number of entries is given by the value of upsNumUPSs. | 1.3.6.1.4.1.52.4.1.1.10.7.1 | not-accessible | mandatory | |
| upsConfigEntry OBJECT-TYPE An entry containing objects for a particular UPS. | 1.3.6.1.4.1.52.4.1.1.10.7.1.1 | not-accessible | mandatory | |
| upsConfigAlarm OBJECT-TYPE The UPS's current audible alarm setting. The alarm may be set to activate immediately upon utility failure and for low battery condition, to activate 30 seconds after utility failure and immediately upon low battery condition, to activate upon low battery condition only, or to not activate under any conditions. | 1.3.6.1.4.1.52.4.1.1.10.7.1.1.1 | INTEGER {uponUtilityFailure(1), thirtySecondsAfterUtilityFailure(2), lowBatteryOnly(3), noAudibleAlarm(4)} | read-write | mandatory |
| upsConfigRestoreDefaults OBJECT-TYPE This object may be written to force the UPS to restore the factory default settings for most of the UPS's customizable parameters. Reading this object will always return a 0. | 1.3.6.1.4.1.52.4.1.1.10.7.1.1.2 | INTEGER {restoreDefaults(1)} | read-write | mandatory |
| upsExtMeas OBJECT-IDENTITY | 1.3.6.1.4.1.52.4.1.1.10.8 | |||
| upsExtMeasTable OBJECT-TYPE A list of external measurement table entries. The number of entries is the number of available UPSs to which External Measurement Units are attached. | 1.3.6.1.4.1.52.4.1.1.10.8.1 | not-accessible | mandatory | |
| upsExtMeasEntry OBJECT-TYPE An entry containing objects for a particular UPS. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1 | not-accessible | mandatory | |
| upsExtMeasFwVersion OBJECT-TYPE The External Measurement Unit's firmware version letter. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.1 | DisplayString (SIZE(0..1)) | read-only | mandatory |
| upsExtMeasTemp OBJECT-TYPE The local ambient temperature in degrees Fahrenheit as measured by the External Measurement Unit. The value of this object is the actual temperature * 100 (that is, to determine the actual temperature, divide the value of this object by 100). | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.2 | INTEGER | read-only | mandatory |
| upsExtMeasHumidity OBJECT-TYPE The local ambient relative humidity in percent as measured by the External Measurement Unit. The value of this object is the actual humidity * 10 (that is, to determine the actual humidity, divide the value of this object by 10). | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.3 | INTEGER | read-only | mandatory |
| upsExtMeasAlarmStatus OBJECT-TYPE This object contains 8 bits of information about the current alarm status of the External Measurement Unit. The bits are encoded as follows: BIT 7: 1=Upper temperature limit exceeded BIT 6: 1=Lower temperature limit exceeded BIT 5: 1=Upper relative humidity limit exceeded BIT 4: 1=Lower relative humidity limit exceeded BIT 3: 1=Contact input channel #4 alarm state BIT 2: 1=Contact input channel #3 alarm state BIT 1: 1=Contact input channel #2 alarm state BIT 0: 1=Contact input channel #1 alarm state Note that bit 0 is the low-order bit. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.4 | INTEGER | read-only | mandatory |
| upsExtMeasMaxTemp OBJECT-TYPE The upper temperature limit at which an alarm will be sent. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.5 | INTEGER {ninetyDegreesF(1), oneHundredFifteenDegreesF(2), oneHundredThirtyDegreesF(3), oneHundredSeventyFiveDegreesF(4)} | read-write | mandatory |
| upsExtMeasMinTemp OBJECT-TYPE The lower temperature limit at which an alarm will be sent. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.6 | INTEGER {fortyDegreesF(1), fiftyDegreesF(2), fiftyEightDegreesF(3), sixtyFiveDegreesF(4)} | read-write | mandatory |
| upsExtMeasMaxHumidity OBJECT-TYPE The upper humidity limit at which an alarm will be sent. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.7 | INTEGER {seventyPercent(1), eightyPercent(2), eightyFivePercent(3), ninetyPercent(4)} | read-write | mandatory |
| upsExtMeasMinHumidity OBJECT-TYPE The lower humidity limit at which an alarm will be sent. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.8 | INTEGER {tenPercent(1), twentyPercent(2), thirtyPercent(3), fortyPercent(4)} | read-write | mandatory |
| upsExtMeasContact1AlarmControl OBJECT-TYPE The alarm enable state for the External Measurement Unit's contact input channel #1. If enabled, an alarm will be sent when contact input channel #1 has changed to abnormal state. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.9 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsExtMeasContact2AlarmControl OBJECT-TYPE The alarm enable state for the External Measurement Unit's contact input channel #2. If enabled, an alarm will be sent when contact input channel #2 has changed to abnormal state. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.10 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsExtMeasContact3AlarmControl OBJECT-TYPE The alarm enable state for the External Measurement Unit's contact input channel #3. If enabled, an alarm will be sent when contact input channel #3 has changed to abnormal state. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.11 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsExtMeasContact4AlarmControl OBJECT-TYPE The alarm enable state for the External Measurement Unit's contact input channel #4. If enabled, an alarm will be sent when contact input channel #4 has changed to abnormal state. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.12 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsExtMeasMaxTempAlarmControl OBJECT-TYPE The alarm enable state for the External Measurement Unit's upper temperature limit. If enabled, an alarm will be sent when the ambient temperature rises above the upper temperature limit. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.13 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsExtMeasMinTempAlarmControl OBJECT-TYPE The alarm enable state for the External Measurement Unit's lower temperature limit. If enabled, an alarm will be sent when the ambient temperature falls below the lower temperature limit. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.14 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsExtMeasMaxHumidityAlarmControl OBJECT-TYPE The alarm enable state for the External Measurement Unit's upper humidity limit. If enabled, an alarm will be sent when the ambient relative humidity rises above the upper humidity limit. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.15 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsExtMeasMinHumidityAlarmControl OBJECT-TYPE The alarm enable state for the External Measurement Unit's lower humidity limit. If enabled, an alarm will be sent when the ambient relative humidity falls below the lower humidity limit. | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.16 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsAddlFuncs OBJECT-IDENTITY | 1.3.6.1.4.1.52.4.1.1.10.9 | |||
| upsAddlFuncsTable OBJECT-TYPE A list of additional functions table entries. The number of entries is the number of available UPSs which are capable of supporting these additional functions. | 1.3.6.1.4.1.52.4.1.1.10.9.1 | not-accessible | mandatory | |
| upsAddlFuncsEntry OBJECT-TYPE An entry containing objects for a particular UPS. | 1.3.6.1.4.1.52.4.1.1.10.9.1.1 | not-accessible | mandatory | |
| upsAddlFuncsNumBatteryPacks OBJECT-TYPE The number of battery pack units connected to the UPS. | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.1 | INTEGER | read-only | mandatory |
| upsAddlFuncsNumBadBatteryPacks OBJECT-TYPE The number of bad (faulty) battery pack units connected to the UPS. | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.2 | INTEGER | read-only | mandatory |
| upsAddlFuncsOutputCurrent OBJECT-TYPE The true rms load current drawn from the UPS. The value of this object is the actual amperage * 100 (that is, to determine the actual amperage, divide the value of this object by 100). | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.3 | INTEGER | read-only | mandatory |
| upsAddlFuncsOutputApparentPower OBJECT-TYPE The UPS's output load represented as a percentage of full rated load in Volt-Amps. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10). | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.4 | INTEGER | read-only | mandatory |
| upsAddlFuncsStatusOperational OBJECT-TYPE This object contains 8 bits of information about the current operational status of the UPS. The bits are encoded as follows: BIT 7: 1=UPS ready to power load upon return of normal line or upon user command BIT 6: 1=UPS ready to power load upon user command BIT 5: 1=UPS in bypass mode as a result of manual bypass control BIT 4: 1=UPS is returning from bypass mode BIT 3: 1=UPS in bypass mode as a result of UPS-Link or key command BIT 2: 1=UPS going to bypass mode as a result of UPS-Link or key command BIT 1: 1=not defined BIT 0: 1=wakeup mode - startup test lasting < 2 sec Note that bit 0 is the low-order bit. | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.5 | INTEGER | read-only | mandatory |
| upsAddlFuncsStatusFault OBJECT-TYPE This object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows: BIT 7: reserved for future use BIT 6: reserved for future use BIT 5: reserved for future use BIT 4: 1=UPS fault - DC imbalance, UPS in bypass BIT 3: 1=UPS fault - output voltage select failure, UPS in bypass BIT 2: 1=UPS fault - bypass supply failure BIT 1: 1=UPS fault - Isolation Unit fan failure BIT 0: 1=UPS fault - Electronics Unit fan failure, UPS in bypass Note that bit 0 is the low-order bit. | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6 | INTEGER | read-only | mandatory |
| upsAddlFuncsConfigPassword OBJECT-TYPE The password that controls access to the UPS's LCD display. A maximum of 4 characters may be entered. | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.7 | OCTET STRING | read-write | mandatory |
| upsAddlFuncsConfigDisable OBJECT-TYPE This object may be written to immediately shut down the UPS, requiring a manual reset. Reading this object will always return a 0. | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.8 | INTEGER {disableUps(1)} | read-write | mandatory |
| upsAddlFuncsConfigBypass OBJECT-TYPE This object may be written to cause the UPS to transfer to or from the bypass mode. Reading this object will always return a 0. | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.9 | INTEGER {bypassMode(1), exitBypassMode(2)} | read-write | mandatory |