TSL-MIB
- Registered at
- 1.3.6.1.4.1.6853
- Namespace
- tsl
- Source file
TSL-MIB- Digest
sha256:39321a0055548d36b05ab312ea473186590920d2a294da0320a3a2adc200bdbc
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Opaque, TRAP-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
SNMPv2-CONF SNMPv2-SMI SNMPv2-TC TSL-MIB
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| DisplayString type |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| tslMIB OBJECT-IDENTITY | 1.3.6.1.4.1.6853 | |||
| alarm OBJECT-IDENTITY | 1.3.6.1.4.1.6853.2 | |||
| alarmIdent OBJECT-TYPE Equipment alarms description and version | 1.3.6.1.4.1.6853.2.1 | DisplayString | read-only | mandatory |
| alarmTable OBJECT-TYPE The table of alarm entries | 1.3.6.1.4.1.6853.2.2 | not-accessible | mandatory | |
| alarmEntry OBJECT-TYPE An alarm entry in the table | 1.3.6.1.4.1.6853.2.2.1 | not-accessible | mandatory | |
| alarmTableIndex OBJECT-TYPE The index into the table | 1.3.6.1.4.1.6853.2.2.1.1 | INTEGER (1..28) | read-only | mandatory |
| alarmType OBJECT-TYPE Alarm type | 1.3.6.1.4.1.6853.2.2.1.2 | INTEGER {internal(1), gpi(2), outputFail(3), psuFail(4), currentAlarm(5)} | read-only | mandatory |
| alarmIndex OBJECT-TYPE Alarm type number | 1.3.6.1.4.1.6853.2.2.1.3 | INTEGER | read-only | mandatory |
| alarmText OBJECT-TYPE Alarm description | 1.3.6.1.4.1.6853.2.2.1.4 | DisplayString | read-write | mandatory |
| alarmState OBJECT-TYPE Alarm state | 1.3.6.1.4.1.6853.2.2.1.5 | INTEGER {inactive(1), active(2)} | read-only | mandatory |
| alarmPolarity OBJECT-TYPE Alarm active polarity (notApplicable for non-gpi alarms) | 1.3.6.1.4.1.6853.2.2.1.6 | INTEGER {notApplicable(1), normallyOpen(2), normallyClosed(3)} | read-write | mandatory |
| alarmData OBJECT-TYPE Additional alarm data of variable length, according to alarm type. | 1.3.6.1.4.1.6853.2.2.1.7 | Opaque | read-only | optional |
| alarmTotal OBJECT-TYPE The total number of alarms in the table | 1.3.6.1.4.1.6853.2.3 | INTEGER | read-only | mandatory |
| alarmLocation OBJECT-TYPE The physical location of the equipment generating the alarm | 1.3.6.1.4.1.6853.2.4 | DisplayString | read-write | mandatory |
| alarmEqptTemp OBJECT-TYPE Equipment temperature (in degrees Centigrade) | 1.3.6.1.4.1.6853.2.5 | INTEGER | read-only | optional |
| alarmEqptTempHi OBJECT-TYPE Equipment temperature alarm point (degrees Centigrade) | 1.3.6.1.4.1.6853.2.6 | INTEGER | read-write | optional |
| mdu12 OBJECT-IDENTITY | 1.3.6.1.4.1.6853.3 | |||
| mdu12Ident OBJECT-TYPE Equipment description and version | 1.3.6.1.4.1.6853.3.1 | DisplayString | read-only | mandatory |
| mduPowerOn OBJECT-TYPE MDU power-on output sequence | 1.3.6.1.4.1.6853.3.2 | INTEGER {simultaneous(1), sequential(2), delayed(3)} | read-write | mandatory |
| mduSeqDelay OBJECT-TYPE Sequential mode delay between outputs | 1.3.6.1.4.1.6853.3.3 | INTEGER | read-write | mandatory |
| mduOutputTable OBJECT-TYPE Table of output controls | 1.3.6.1.4.1.6853.3.4 | not-accessible | mandatory | |
| mduOutputEntry OBJECT-TYPE An entry in the output table | 1.3.6.1.4.1.6853.3.4.1 | not-accessible | mandatory | |
| mduOutputIndex OBJECT-TYPE Output number | 1.3.6.1.4.1.6853.3.4.1.1 | INTEGER (1..12) | read-only | mandatory |
| mduOutputState OBJECT-TYPE MDU Output status | 1.3.6.1.4.1.6853.3.4.1.2 | INTEGER {off(1), on(2), locked-Off(3), locked-On(4)} | read-write | mandatory |
| mduOutputDelay OBJECT-TYPE Output on delay from power on (Delay mode only) | 1.3.6.1.4.1.6853.3.4.1.3 | INTEGER | read-write | mandatory |
| mduOutputlowerCurrent OBJECT-TYPE Lower current limit for output | 1.3.6.1.4.1.6853.3.4.1.4 | INTEGER | read-write | mandatory |
| mduOutputupperCurrent OBJECT-TYPE Upper current limit for output | 1.3.6.1.4.1.6853.3.4.1.5 | INTEGER | read-write | mandatory |
| mduOutputCurrent OBJECT-TYPE Output current | 1.3.6.1.4.1.6853.3.4.1.6 | INTEGER | read-only | mandatory |
| mduOutputpowerFactor OBJECT-TYPE Output power factor | 1.3.6.1.4.1.6853.3.4.1.7 | INTEGER | read-only | mandatory |
| mduOutputVA OBJECT-TYPE Output apparent power | 1.3.6.1.4.1.6853.3.4.1.8 | INTEGER | read-only | mandatory |
| mduOutputWatts OBJECT-TYPE Output real power | 1.3.6.1.4.1.6853.3.4.1.9 | INTEGER | read-only | mandatory |
| mduOutputCal OBJECT-TYPE Output current measure calibration data | 1.3.6.1.4.1.6853.3.4.1.10 | INTEGER | read-write | mandatory |
| mduPowerStatus OBJECT-TYPE Status of MDU power inlets | 1.3.6.1.4.1.6853.3.5 | INTEGER {totalLoss(1), input1OK(2), input2OK(3), allOk(4)} | read-only | mandatory |
| mduVoltageCal OBJECT-TYPE Voltage measure calibration data | 1.3.6.1.4.1.6853.3.6 | INTEGER | read-write | mandatory |
| mduVoltage OBJECT-TYPE Voltage measurement | 1.3.6.1.4.1.6853.3.7 | INTEGER | read-only | mandatory |
| mduVoltageFloor OBJECT-TYPE Voltage lower limit | 1.3.6.1.4.1.6853.3.8 | INTEGER | read-write | mandatory |
| mduVoltageLimit OBJECT-TYPE Voltage upper limit | 1.3.6.1.4.1.6853.3.9 | INTEGER | read-write | mandatory |
| mduTotalCurrent OBJECT-TYPE Total current measurement | 1.3.6.1.4.1.6853.3.10 | INTEGER | read-write | mandatory |
| mduCurrentLimit OBJECT-TYPE Current total limit | 1.3.6.1.4.1.6853.3.11 | INTEGER | read-write | mandatory |
| mduAuxRly1 OBJECT-TYPE Auxiliary Relay 1 state | 1.3.6.1.4.1.6853.3.12 | INTEGER {off(1), on(2)} | read-write | mandatory |
| mduAuxRly2 OBJECT-TYPE Auxiliary Relay 2 state | 1.3.6.1.4.1.6853.3.13 | INTEGER {off(1), on(2)} | read-write | mandatory |
Notifications
| Name | OID | Status |
|---|---|---|
| alarmTrap NOTIFICATION-TYPE An entry in the alarm table has changed state | 1.3.6.1.4.1.6853.0.4 | |
| alarmEqptTempHiTrap NOTIFICATION-TYPE The equipment temperature has exceeded the maximum allowed | 1.3.6.1.4.1.6853.0.5 | |
| alarmEqptTempOkTrap NOTIFICATION-TYPE The equipment temperature is now within limits | 1.3.6.1.4.1.6853.0.6 | |
| mduPowerStatusTrap NOTIFICATION-TYPE The power input to the MDU has changed state | 1.3.6.1.4.1.6853.0.7 | |
| mduVoltageStatusTrap NOTIFICATION-TYPE The voltage to the MDU has traversed a limit | 1.3.6.1.4.1.6853.0.8 | |
| mduTotalCurrentStatusTrap NOTIFICATION-TYPE The total current through the MDU has traversed a limit | 1.3.6.1.4.1.6853.0.9 |