MIBs Depot

TSL-MIB

Registered at
1.3.6.1.4.1.6853
Namespace
tsl
Source file
TSL-MIB
Digest
sha256:39321a0055548d36b05ab312ea473186590920d2a294da0320a3a2adc200bdbc

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Opaque, TRAP-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC
TSL-MIB

Textual conventions

NameOIDSyntaxAccessStatus
DisplayString
type

Objects

NameOIDSyntaxAccessStatus
tslMIB
OBJECT-IDENTITY
1.3.6.1.4.1.6853
alarm
OBJECT-IDENTITY
1.3.6.1.4.1.6853.2
alarmIdent
OBJECT-TYPE
Equipment alarms description and version
1.3.6.1.4.1.6853.2.1DisplayStringread-onlymandatory
alarmTable
OBJECT-TYPE
The table of alarm entries
1.3.6.1.4.1.6853.2.2not-accessiblemandatory
alarmEntry
OBJECT-TYPE
An alarm entry in the table
1.3.6.1.4.1.6853.2.2.1not-accessiblemandatory
alarmTableIndex
OBJECT-TYPE
The index into the table
1.3.6.1.4.1.6853.2.2.1.1INTEGER (1..28)read-onlymandatory
alarmType
OBJECT-TYPE
Alarm type
1.3.6.1.4.1.6853.2.2.1.2INTEGER {internal(1), gpi(2), outputFail(3), psuFail(4), currentAlarm(5)}read-onlymandatory
alarmIndex
OBJECT-TYPE
Alarm type number
1.3.6.1.4.1.6853.2.2.1.3INTEGERread-onlymandatory
alarmText
OBJECT-TYPE
Alarm description
1.3.6.1.4.1.6853.2.2.1.4DisplayStringread-writemandatory
alarmState
OBJECT-TYPE
Alarm state
1.3.6.1.4.1.6853.2.2.1.5INTEGER {inactive(1), active(2)}read-onlymandatory
alarmPolarity
OBJECT-TYPE
Alarm active polarity (notApplicable for non-gpi alarms)
1.3.6.1.4.1.6853.2.2.1.6INTEGER {notApplicable(1), normallyOpen(2), normallyClosed(3)}read-writemandatory
alarmData
OBJECT-TYPE
Additional alarm data of variable length, according to alarm type.
1.3.6.1.4.1.6853.2.2.1.7Opaqueread-onlyoptional
alarmTotal
OBJECT-TYPE
The total number of alarms in the table
1.3.6.1.4.1.6853.2.3INTEGERread-onlymandatory
alarmLocation
OBJECT-TYPE
The physical location of the equipment generating the alarm
1.3.6.1.4.1.6853.2.4DisplayStringread-writemandatory
alarmEqptTemp
OBJECT-TYPE
Equipment temperature (in degrees Centigrade)
1.3.6.1.4.1.6853.2.5INTEGERread-onlyoptional
alarmEqptTempHi
OBJECT-TYPE
Equipment temperature alarm point (degrees Centigrade)
1.3.6.1.4.1.6853.2.6INTEGERread-writeoptional
mdu12
OBJECT-IDENTITY
1.3.6.1.4.1.6853.3
mdu12Ident
OBJECT-TYPE
Equipment description and version
1.3.6.1.4.1.6853.3.1DisplayStringread-onlymandatory
mduPowerOn
OBJECT-TYPE
MDU power-on output sequence
1.3.6.1.4.1.6853.3.2INTEGER {simultaneous(1), sequential(2), delayed(3)}read-writemandatory
mduSeqDelay
OBJECT-TYPE
Sequential mode delay between outputs
1.3.6.1.4.1.6853.3.3INTEGERread-writemandatory
mduOutputTable
OBJECT-TYPE
Table of output controls
1.3.6.1.4.1.6853.3.4not-accessiblemandatory
mduOutputEntry
OBJECT-TYPE
An entry in the output table
1.3.6.1.4.1.6853.3.4.1not-accessiblemandatory
mduOutputIndex
OBJECT-TYPE
Output number
1.3.6.1.4.1.6853.3.4.1.1INTEGER (1..12)read-onlymandatory
mduOutputState
OBJECT-TYPE
MDU Output status
1.3.6.1.4.1.6853.3.4.1.2INTEGER {off(1), on(2), locked-Off(3), locked-On(4)}read-writemandatory
mduOutputDelay
OBJECT-TYPE
Output on delay from power on (Delay mode only)
1.3.6.1.4.1.6853.3.4.1.3INTEGERread-writemandatory
mduOutputlowerCurrent
OBJECT-TYPE
Lower current limit for output
1.3.6.1.4.1.6853.3.4.1.4INTEGERread-writemandatory
mduOutputupperCurrent
OBJECT-TYPE
Upper current limit for output
1.3.6.1.4.1.6853.3.4.1.5INTEGERread-writemandatory
mduOutputCurrent
OBJECT-TYPE
Output current
1.3.6.1.4.1.6853.3.4.1.6INTEGERread-onlymandatory
mduOutputpowerFactor
OBJECT-TYPE
Output power factor
1.3.6.1.4.1.6853.3.4.1.7INTEGERread-onlymandatory
mduOutputVA
OBJECT-TYPE
Output apparent power
1.3.6.1.4.1.6853.3.4.1.8INTEGERread-onlymandatory
mduOutputWatts
OBJECT-TYPE
Output real power
1.3.6.1.4.1.6853.3.4.1.9INTEGERread-onlymandatory
mduOutputCal
OBJECT-TYPE
Output current measure calibration data
1.3.6.1.4.1.6853.3.4.1.10INTEGERread-writemandatory
mduPowerStatus
OBJECT-TYPE
Status of MDU power inlets
1.3.6.1.4.1.6853.3.5INTEGER {totalLoss(1), input1OK(2), input2OK(3), allOk(4)}read-onlymandatory
mduVoltageCal
OBJECT-TYPE
Voltage measure calibration data
1.3.6.1.4.1.6853.3.6INTEGERread-writemandatory
mduVoltage
OBJECT-TYPE
Voltage measurement
1.3.6.1.4.1.6853.3.7INTEGERread-onlymandatory
mduVoltageFloor
OBJECT-TYPE
Voltage lower limit
1.3.6.1.4.1.6853.3.8INTEGERread-writemandatory
mduVoltageLimit
OBJECT-TYPE
Voltage upper limit
1.3.6.1.4.1.6853.3.9INTEGERread-writemandatory
mduTotalCurrent
OBJECT-TYPE
Total current measurement
1.3.6.1.4.1.6853.3.10INTEGERread-writemandatory
mduCurrentLimit
OBJECT-TYPE
Current total limit
1.3.6.1.4.1.6853.3.11INTEGERread-writemandatory
mduAuxRly1
OBJECT-TYPE
Auxiliary Relay 1 state
1.3.6.1.4.1.6853.3.12INTEGER {off(1), on(2)}read-writemandatory
mduAuxRly2
OBJECT-TYPE
Auxiliary Relay 2 state
1.3.6.1.4.1.6853.3.13INTEGER {off(1), on(2)}read-writemandatory

Notifications

NameOIDStatus
alarmTrap
NOTIFICATION-TYPE
An entry in the alarm table has changed state
1.3.6.1.4.1.6853.0.4
alarmEqptTempHiTrap
NOTIFICATION-TYPE
The equipment temperature has exceeded the maximum allowed
1.3.6.1.4.1.6853.0.5
alarmEqptTempOkTrap
NOTIFICATION-TYPE
The equipment temperature is now within limits
1.3.6.1.4.1.6853.0.6
mduPowerStatusTrap
NOTIFICATION-TYPE
The power input to the MDU has changed state
1.3.6.1.4.1.6853.0.7
mduVoltageStatusTrap
NOTIFICATION-TYPE
The voltage to the MDU has traversed a limit
1.3.6.1.4.1.6853.0.8
mduTotalCurrentStatusTrap
NOTIFICATION-TYPE
The total current through the MDU has traversed a limit
1.3.6.1.4.1.6853.0.9