TRIPPLITE-PRODUCTS
- Registered at
- 1.3.6.1.4.1.850.1
- Last updated
- 2019-09-27 09:30
- Organization
- Tripp Lite
- Revisions
- 2019-09-27 09:30, 2019-06-18 09:30, 2019-05-07 12:50, 2019-05-06 10:30, 2019-01-17 10:30, 2018-07-13 14:30, 2018-05-10 14:30, 2018-05-08 13:30, 2018-04-30 15:30, 2018-04-25 13:30, 2018-03-19 07:30, 2018-01-15 11:30, 2017-12-29 13:30, 2017-11-30 11:30, 2017-09-29 08:00, 2017-08-30 09:00, 2017-07-31 09:00, 2017-05-23 14:23, 2017-04-19 22:30, 2017-04-03 15:33, 2017-02-28 16:00, 2017-01-17 12:50, 2016-07-11 12:15, 2016-06-22 11:15, 2016-03-16 12:10, 2016-02-02 11:15, 2016-01-25 12:30, 2016-01-20 12:00, 2016-01-08 11:40, 2015-11-25 13:00, 2015-11-10 13:00, 2015-10-16 12:30, 2015-08-19 12:00, 2014-12-04 10:00, 2014-04-14 09:00
- Namespace
- poweralert
- Source file
TRIPPLITE-PRODUCTS- Digest
sha256:22f1835a07a060b4d62184d65dc58d1dc3cdbaf2f8a2823a679950e5acdae511
Description
This MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripp Lite PowerAlert and related software.
Contact
Software Engineering Tripp Lite 1111 W. 35th St. Chicago, IL 60609
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-MIB | sysUpTime |
| SNMPv2-SMI | Gauge32, Integer32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, RowStatus, TEXTUAL-CONVENTION, TimeStamp, TruthValue |
| TRIPPLITE | tripplite |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC TRIPPLITE TRIPPLITE-PRODUCTS
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| tlpHardware OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1 | |||
| tlpDevice OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.1 | |||
| tlpDeviceNumDevices OBJECT-TYPE The number of devices that this agent is currently managing. | 1.3.6.1.4.1.850.1.1.1.1 | Unsigned32 | read-only | current |
| tlpDeviceTable OBJECT-TYPE A list of device table entries. The number of entries is given by the value of tlpDevicesNumDevices. | 1.3.6.1.4.1.850.1.1.1.2 | not-accessible | current | |
| tlpDeviceEntry OBJECT-TYPE An entry containing information applicable to a particular device managed by this agent. | 1.3.6.1.4.1.850.1.1.1.2.1 | not-accessible | current | |
| tlpDeviceIndex OBJECT-TYPE The table row index for the device. | 1.3.6.1.4.1.850.1.1.1.2.1.1 | Unsigned32 | read-only | current |
| tlpDeviceRowStatus OBJECT-TYPE Used with table edits to indicate the status of a given row in tlpDeviceTable. | 1.3.6.1.4.1.850.1.1.1.2.1.2 | RowStatus | read-only | current |
| tlpDeviceType OBJECT-TYPE The type of device. One of the appropriate hardware types: ups, pdu, envirosense, etc. | 1.3.6.1.4.1.850.1.1.1.2.1.3 | OBJECT IDENTIFIER | read-only | current |
| tlpDeviceManufacturer OBJECT-TYPE The name of the manufacturer. | 1.3.6.1.4.1.850.1.1.1.2.1.4 | DisplayString | read-only | current |
| tlpDeviceModel OBJECT-TYPE The model designation. | 1.3.6.1.4.1.850.1.1.1.2.1.5 | DisplayString | read-only | current |
| tlpDeviceName OBJECT-TYPE A user-supplied name for the device. | 1.3.6.1.4.1.850.1.1.1.2.1.6 | DisplayString | read-write | current |
| tlpDeviceID OBJECT-TYPE A user-supplied ID for the device. | 1.3.6.1.4.1.850.1.1.1.2.1.7 | INTEGER (0..65535) | read-write | current |
| tlpDeviceLocation OBJECT-TYPE A user-supplied location for the device. | 1.3.6.1.4.1.850.1.1.1.2.1.8 | DisplayString | read-write | current |
| tlpDeviceRegion OBJECT-TYPE A user-supplied region for the device. | 1.3.6.1.4.1.850.1.1.1.2.1.9 | DisplayString | read-write | current |
| tlpDeviceStatus OBJECT-TYPE The currently most critical alarm status for the device. | 1.3.6.1.4.1.850.1.1.1.2.1.10 | INTEGER {none(0), critical(1), warning(2), info(3), status(4), offline(5), custom(6), configuration(7)} | read-only | current |
| tlpDeviceDetail OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.2 | |||
| tlpDeviceIdentTable OBJECT-TYPE The identity details of each device in device table. The number of entries is given by the value of tlpDevicesNumDevices. | 1.3.6.1.4.1.850.1.1.2.1 | not-accessible | current | |
| tlpDeviceIdentEntry OBJECT-TYPE An entry containing details for a particular device. | 1.3.6.1.4.1.850.1.1.2.1.1 | not-accessible | current | |
| tlpDeviceIdentProtocol OBJECT-TYPE The Tripplite protocol used to communicate with the device. | 1.3.6.1.4.1.850.1.1.2.1.1.1 | DisplayString | read-only | current |
| tlpDeviceIdentCommPortType OBJECT-TYPE The type of communications port used to connect with the device. | 1.3.6.1.4.1.850.1.1.2.1.1.2 | INTEGER {unknown(0), serial(1), usb(2), hid(3), simulated(4), unittest(5)} | read-only | current |
| tlpDeviceIdentCommPortName OBJECT-TYPE The name of the communications port. | 1.3.6.1.4.1.850.1.1.2.1.1.3 | DisplayString | read-only | current |
| tlpDeviceIdentFirmwareVersion OBJECT-TYPE The firmware version of the device. | 1.3.6.1.4.1.850.1.1.2.1.1.4 | DisplayString | read-only | current |
| tlpDeviceIdentSerialNum OBJECT-TYPE The serial number of the device. | 1.3.6.1.4.1.850.1.1.2.1.1.5 | DisplayString | read-only | current |
| tlpDeviceIdentDateInstalled OBJECT-TYPE The installation date for this device in the format of mm/dd/yyyy. | 1.3.6.1.4.1.850.1.1.2.1.1.6 | DisplayString | read-write | current |
| tlpDeviceIdentHardwareVersion OBJECT-TYPE The hardware revision of the device. This value will return ERROR_NO_SUCH_NAME if not supported by the device. | 1.3.6.1.4.1.850.1.1.2.1.1.7 | DisplayString | read-only | current |
| tlpDeviceIdentCurrentUptime OBJECT-TYPE The device uptime since its last startup. This value will return ERROR_NO_SUCH_NAME if not supported by the device. | 1.3.6.1.4.1.850.1.1.2.1.1.8 | DisplayString | read-only | current |
| tlpDeviceIdentTotalUptime OBJECT-TYPE The cumulative (total) uptime for the device. This value will return ERROR_NO_SUCH_NAME if not supported by the device. | 1.3.6.1.4.1.850.1.1.2.1.1.9 | DisplayString | read-only | current |
| tlpDeviceIdentFirmwareVersion2 OBJECT-TYPE The firmware version of second IC on the device. This value will return ERROR_NO_SUCH_NAME if not supported by the device. | 1.3.6.1.4.1.850.1.1.2.1.1.10 | DisplayString | read-only | current |
| tlpDeviceIdentFirmwareVersion3 OBJECT-TYPE The firmware version of third IC on the device. This value will return ERROR_NO_SUCH_NAME if not supported by the device. | 1.3.6.1.4.1.850.1.1.2.1.1.11 | DisplayString | read-only | current |
| tlpDeviceIdentNvrID OBJECT-TYPE The id of NVRAM. This value will return ERROR_NO_SUCH_NAME if not supported by the device. | 1.3.6.1.4.1.850.1.1.2.1.1.12 | DisplayString | read-only | current |
| tlpDeviceTypes OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3 | |||
| tlpUps OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1 | |||
| tlpUpsIdent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.1 | |||
| tlpUpsIdentNumUps OBJECT-TYPE The number of ups devices that this agent is currently managing. | 1.3.6.1.4.1.850.1.1.3.1.1.1 | Unsigned32 | read-only | current |
| tlpUpsIdentTable OBJECT-TYPE The identity details of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. | 1.3.6.1.4.1.850.1.1.3.1.1.2 | not-accessible | current | |
| tlpUpsIdentEntry OBJECT-TYPE An entry containing details for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1 | not-accessible | current | |
| tlpUpsIdentNumInputs OBJECT-TYPE The number of input lines supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.1 | Unsigned32 | read-only | current |
| tlpUpsIdentNumOutputs OBJECT-TYPE The number of output lines supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.2 | Unsigned32 | read-only | current |
| tlpUpsIdentNumBypass OBJECT-TYPE The number of bypass lines supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.3 | Unsigned32 | read-only | current |
| tlpUpsIdentNumPhases OBJECT-TYPE The number of phases supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.4 | Unsigned32 | read-only | current |
| tlpUpsIdentNumOutlets OBJECT-TYPE The number of receptacles supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.5 | Unsigned32 | read-only | current |
| tlpUpsIdentNumOutletGroups OBJECT-TYPE The number of receptacle groups supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.6 | Unsigned32 | read-only | current |
| tlpUpsIdentNumBatteryPacks OBJECT-TYPE The number of battery packs, internal and external combined, supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.7 | Unsigned32 | read-only | current |
| tlpUpsIdentNumFans OBJECT-TYPE The number of fans supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.8 | Unsigned32 | read-only | current |
| tlpUpsIdentNumHeatsinks OBJECT-TYPE The number of heatsink thermistors supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.9 | Unsigned32 | read-only | current |
| tlpUpsIdentNumInputContacts OBJECT-TYPE The number of input contacts supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.10 | Unsigned32 | read-only | current |
| tlpUpsIdentNumOutputContacts OBJECT-TYPE The number of output contacts supported by the ups. | 1.3.6.1.4.1.850.1.1.3.1.1.2.1.11 | Unsigned32 | read-only | current |
| tlpUpsSupportsTable OBJECT-TYPE The supported details of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. | 1.3.6.1.4.1.850.1.1.3.1.1.3 | not-accessible | current | |
| tlpUpsSupportsEntry OBJECT-TYPE An entry containing supported details for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.1.3.1 | not-accessible | current | |
| tlpUpsSupportsEnergywise OBJECT-TYPE Indicates whether the ups supports Cisco EnergyWise. | 1.3.6.1.4.1.850.1.1.3.1.1.3.1.1 | TruthValue | read-only | current |
| tlpUpsSupportsRampShed OBJECT-TYPE Indicates whether the ups supports ramping and shedding. | 1.3.6.1.4.1.850.1.1.3.1.1.3.1.2 | TruthValue | read-only | current |
| tlpUpsSupportsOutletGroup OBJECT-TYPE Indicates whether the ups supports outlet groups. | 1.3.6.1.4.1.850.1.1.3.1.1.3.1.3 | TruthValue | read-only | current |
| tlpUpsSupportsOutletCurrentPower OBJECT-TYPE Indicates whether the ups reports individual receptacle current and power measurements. Devices that do not support individual receptacle measurements will always return ERROR_NO_SUCH_NAME for tlpUpsOutletCurrent and tlpUpsOutletPower. | 1.3.6.1.4.1.850.1.1.3.1.1.3.1.4 | TruthValue | read-only | current |
| tlpUpsSupportsOutletVoltage OBJECT-TYPE Indicates whether the ups reports individual receptacle voltage measurements. Devices that do not support individual receptacle measurements will always return ERROR_NO_SUCH_NAME for tlpUpsOutletVoltage. | 1.3.6.1.4.1.850.1.1.3.1.1.3.1.5 | TruthValue | read-only | current |
| tlpUpsDevice OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.2 | |||
| tlpUpsDeviceTable OBJECT-TYPE The device details of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. | 1.3.6.1.4.1.850.1.1.3.1.2.1 | not-accessible | current | |
| tlpUpsDeviceEntry OBJECT-TYPE An entry containing device details for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1 | not-accessible | current | |
| tlpUpsDeviceMainLoadState OBJECT-TYPE The current state of the main output of the device. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.1 | INTEGER {unknown(0), off(1), on(2)} | read-only | current |
| tlpUpsDeviceMainLoadControllable OBJECT-TYPE Indicates whether or not the main output is controllable, and whether the ups can be turned off and on. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.2 | TruthValue | read-only | current |
| tlpUpsDeviceMainLoadCommand OBJECT-TYPE Reading this value will always return 0. Setting this value to turnOff(1) will turn off the main output of the ups. Setting this value to turnOn(2) will turn on the main output of the ups. Setting this value to cycle(3) will turn off the main output, then turn it back on. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.3 | INTEGER {idle(0), turnOff(1), turnOn(2), cycle(3)} | read-write | current |
| tlpUpsDevicePowerOnDelay OBJECT-TYPE The configurable delay value, which sets the amount of additional time a given device will wait before it connects to a valid AC source. By default the delay value is set to 0. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.4 | Integer32 | read-write | current |
| tlpUpsDeviceTestDate OBJECT-TYPE The date of the last self-test run on the ups, in the format YYYY-MM-DD. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.5 | DisplayString | read-only | current |
| tlpUpsDeviceTestResultsStatus OBJECT-TYPE The result of the last self-test run on the ups. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.6 | INTEGER {noTest(0), doneAndPassed(1), doneAndWarning(2), doneAndError(3), aborted(4), inProgress(5), noTestInitiated(6), badBattery(7), overCurrent(8), batteryFailed(9)} | read-only | current |
| tlpUpsDeviceTemperatureC OBJECT-TYPE The ambient temperature at or near the ups casing. Temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.7 | Integer32 | read-only | current |
| tlpUpsDeviceTemperatureF OBJECT-TYPE The ambient temperature at or near the ups casing. Temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.8 | Integer32 | read-only | current |
| tlpUpsDeviceLastACFailureReason OBJECT-TYPE The last AC failure reason. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.9 | INTEGER {noACFailureSinceReset(0), blackout(1), instantaneousHighLineFrequency(2), highLineVoltage(3), lowLineVoltage(4), averageFrequencyFault(5), instantaneousLowLineFrequency(6), delayedBrownout(7)} | read-only | current |
| tlpUpsDeviceLastShutdownReason OBJECT-TYPE The last unit shut down reason. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.10 | INTEGER {noShutdownSinceReset(0), onOffButtonShutdown(1), averageVbattSmallerThenLVCShutdown(2), fastVbattKeepaliveVoltageFastShutdown(3), averageCurrentLimitShutdown(4), fastCurrentLimitShutdown(5), heavyLoadThermalTimeLimitShutdown(6), fixedInvertModeTimeLimitShutdown(7), highBatteryVoltageFault(8), averageVbattKeepaliveVoltageShutdown(9), shutdownCommandWithAutorestartEnabled(10), shutdownCommandWithoutAutorestartEnabled(11), lineConnectRelayFault(12), epoInvertMode(13), epoRebootMode(14), invalidLineStandbyMode(15), chargerLimitMinBatteryVoltage(16), chargerLimitMaxBatteryVoltage(17), invalidLineDelayedWakeupAutorestartEnabled(18), invalidLineDelayedWakeupAutorestartDisabled(19), minBatteryVoltagePriorDelayedWakeupAutorestartEnabled(20), minBatteryVoltagePriorDelayedWakeupAutorestartDisabled(21), lvcShutdownAutorestartEnabled(22), lvcShutdownAutorestartDisabled(23), overloadShutdownAutorestartEnabled(24), overloadShutdownAutorestartDisabled(25), overTemperatureShutdownAutorestartEnabled(26), overTemperatureShutdownAutorestartDisabled(27), onOffButtonShutdownAutorestartEnabled(28), onOffButtonShutdownAutorestartDisabled(29), batteryReportedFault(30), batteryCommunicationLost(31), batteryJumpStartChargerTimeoutError(32)} | read-only | current |
| tlpUpsDeviceOutputCurrentPrecision OBJECT-TYPE Output current is reported by tlpUpsOutputLineCurrent, tlpUpsOutputLineCurrentMin and tlpUpsOutputLineCurrentMax. These values are all reported in hundredths(0.01A),which accommodates all models; however, on any given device the actual precision may vary. This value describes the actual precision, which can be used as a divisor against the output current values to obtain the true output current measurement. For example, if tlpUpsOutputLineCurrent reports 530 and tlpUpsDeviceOutputCurrentPrecision is tenths(1), then the actual output current is 5.3. | 1.3.6.1.4.1.850.1.1.3.1.2.1.1.11 | INTEGER {wholeNumber(0), tenths(1), hundredths(2)} | read-only | current |
| tlpUpsDetail OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3 | |||
| tlpUpsBattery OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.1 | |||
| tlpUpsBatterySummaryTable OBJECT-TYPE The battery system summary of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps. | 1.3.6.1.4.1.850.1.1.3.1.3.1.1 | not-accessible | current | |
| tlpUpsBatterySummaryEntry OBJECT-TYPE An entry containing information applicable to a particular battery system managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1 | not-accessible | current | |
| tlpUpsBatteryStatus OBJECT-TYPE The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than tlpUpsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to tlpUpsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). | 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.1 | INTEGER {unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4)} | read-only | current |
| tlpUpsSecondsOnBattery OBJECT-TYPE If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power. | 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.2 | Unsigned32 | read-only | current |
| tlpUpsEstimatedMinutesRemaining OBJECT-TYPE An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. | 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.3 | Unsigned32 | read-only | current |
| tlpUpsEstimatedChargeRemaining OBJECT-TYPE An estimate of the battery charge remaining expressed as a percent of full charge. | 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.4 | INTEGER (0..100) | read-only | current |
| tlpUpsBatteryRunTimeRemaining OBJECT-TYPE The run time remaining before batteries are exhausted. If the device does not support run time remaining, then the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.5 | TimeTicks | read-only | current |
| tlpUpsBatteryTotalMinutesOnBattery OBJECT-TYPE The total accumulative minutes the ups has run on the battery. | 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.6 | Unsigned32 | read-only | current |
| tlpUpsBatteryDetailTable OBJECT-TYPE The battery detail of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps. | 1.3.6.1.4.1.850.1.1.3.1.3.1.2 | not-accessible | current | |
| tlpUpsBatteryDetailEntry OBJECT-TYPE An entry containing information applicable to a particular battery system managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1 | not-accessible | current | |
| tlpUpsBatteryDetailVoltage OBJECT-TYPE The magnitude of the present battery voltage. | 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.1 | Unsigned32 | read-only | current |
| tlpUpsBatteryDetailCurrent OBJECT-TYPE The present battery current. | 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.2 | Integer32 | read-only | current |
| tlpUpsBatteryDetailCapacity OBJECT-TYPE The estimated remaining battery capacity expressed as a percent of full capacity. | 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.3 | INTEGER (0..100) | read-only | current |
| tlpUpsBatteryDetailCharge OBJECT-TYPE Denotes the charge state of the battery. | 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.4 | INTEGER {floating(0), charging(1), resting(2), discharging(3), normal(4), standby(5)} | read-only | current |
| tlpUpsBatteryDetailChargerStatus OBJECT-TYPE The status of the battery charger. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.5 | INTEGER {ok(0), inFaultCondition(1)} | read-only | current |
| tlpUpsBatteryPackIdentTable OBJECT-TYPE The battery identification details for each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by upsIdentNumUps and the number of battery battery packs per each as reported by tlpUpsNumBatteryPacks. | 1.3.6.1.4.1.850.1.1.3.1.3.1.3 | not-accessible | current | |
| tlpUpsBatteryPackIdentEntry OBJECT-TYPE An entry containing information applicable to a particular battery pack managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.1.3.1 | not-accessible | current | |
| tlpUpsBatteryPackIdentIndex OBJECT-TYPE The table row index for the ups battery pack. | 1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.1 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackIdentManufacturer OBJECT-TYPE The manufacturer of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.2 | DisplayString | read-only | current |
| tlpUpsBatteryPackIdentModel OBJECT-TYPE The model or device name of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.3 | DisplayString | read-only | current |
| tlpUpsBatteryPackIdentSerialNum OBJECT-TYPE The serial number of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.4 | DisplayString | read-only | current |
| tlpUpsBatteryPackIdentFirmware OBJECT-TYPE The firmware of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.5 | DisplayString | read-only | current |
| tlpUpsBatteryPackIdentSKU OBJECT-TYPE The SKU of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.6 | DisplayString | read-only | current |
| tlpUpsBatteryPackConfigTable OBJECT-TYPE The battery configuration details for each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by upsIdentNumUps and the number of battery battery packs per each as reported by tlpUpsNumBatteryPacks. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4 | not-accessible | current | |
| tlpUpsBatteryPackConfigEntry OBJECT-TYPE An entry containing information applicable to a particular battery pack managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1 | not-accessible | current | |
| tlpUpsBatteryPackConfigChemistry OBJECT-TYPE The type of battery pack. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.1 | INTEGER {unknown(0), leadAcid(1), nickelCadmium(2), lithiumIon(3)} | read-only | current |
| tlpUpsBatteryPackConfigStyle OBJECT-TYPE The style of battery pack. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.2 | INTEGER {unknown(0), nonsmart(1), smart(2), bms(3)} | read-only | current |
| tlpUpsBatteryPackConfigLocation OBJECT-TYPE The location of the battery pack. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.3 | INTEGER {unknown(0), internal(1), external(2)} | read-only | current |
| tlpUpsBatteryPackConfigStrings OBJECT-TYPE The number of series strings in parallel contained in the battery pack. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.4 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackConfigBatteriesPerString OBJECT-TYPE The number of battery per each string in the battery pack. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.5 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackConfigCellsPerBattery OBJECT-TYPE The number of cells per battery.. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.6 | INTEGER {unknown(0), one(1), two(2), four(4), six(6)} | read-only | current |
| tlpUpsBatteryPackConfigNumBatteries OBJECT-TYPE The total number of batteries contained in the battery pack. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.7 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackConfigCapacityUnits OBJECT-TYPE The units of measurement used for tlpUpsBatteryPackConfigDesignCapacity and tlpUpsBatteryPackConfigCellCapacity. If supported, this value will report either mAHR(1), amps per hour, or mWhr(1), watts per hour. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.8 | INTEGER {mAHr(0), mWHr(1)} | read-only | current |
| tlpUpsBatteryPackConfigDesignCapacity OBJECT-TYPE The theoretical or nominal capacity of the battery pack in the measurement defined by tlpUpsBatteryPackConfigCapacityUnits. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.9 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackConfigCellCapacity OBJECT-TYPE The capacity of the batteries in the measurement defined by tlpUpsBatteryPackConfigCapacityUnits. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.10 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackConfigMinCellVoltage OBJECT-TYPE The minimum cell voltage for the batteries. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.11 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackConfigMaxCellVoltage OBJECT-TYPE The maximum cell voltage for the batteries. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.12 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackDetailTable OBJECT-TYPE The details of each battery pack for each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss and battery packs managed by the agent as reported by tlpUpsIdentNumUps and tlpUpsIdentNumBatteryPacks. | 1.3.6.1.4.1.850.1.1.3.1.3.1.5 | not-accessible | current | |
| tlpUpsBatteryPackDetailEntry OBJECT-TYPE An entry containing information applicable to a particular battery system managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1 | not-accessible | current | |
| tlpUpsBatteryPackDetailCondition OBJECT-TYPE The condition of the battery. A bad battery should be replaced. | 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.1 | INTEGER {unknown(0), good(1), weak(2), bad(3)} | read-only | current |
| tlpUpsBatteryPackDetailTemperatureC OBJECT-TYPE The ambient temperature at or near the UPS Battery casing. | 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.2 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackDetailTemperatureF OBJECT-TYPE The ambient temperature at or near the UPS Battery casing. | 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.3 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackDetailAge OBJECT-TYPE The age of the battery in years. This is equal to the current date minus tlpUpsBatteryPackIdentInstallDate. | 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.4 | Unsigned32 | read-only | current |
| tlpUpsBatteryPackDetailLastReplaceDate OBJECT-TYPE The date when the batteries were last replaced in YYYYMMDD format. | 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.5 | DisplayString | read-write | current |
| tlpUpsBatteryPackDetailNextReplaceDate OBJECT-TYPE The date when the batteries should next be replaced in YYYYMMDD format. | 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.6 | DisplayString | read-only | current |
| tlpUpsBatteryPackDetailCycleCount OBJECT-TYPE The number of times the battery went into invert mode. This number is incremented by 1 each time the unit goes on battery mode (with the exception of Self Test mode). If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.7 | Unsigned32 | read-only | current |
| tlpUpsInput OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.2 | |||
| tlpUpsInputTable OBJECT-TYPE The input details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1 | not-accessible | current | |
| tlpUpsInputEntry OBJECT-TYPE An entry containing information applicable to all input lines per each ups managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1 | not-accessible | current | |
| tlpUpsInputLineBads OBJECT-TYPE A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. This value is not supported on all units. If the ups does not support this value, then the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.1 | INTEGER | read-only | current |
| tlpUpsInputNominalVoltage OBJECT-TYPE The nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.2 | Unsigned32 | read-only | current |
| tlpUpsInputNominalFrequency OBJECT-TYPE The nominal value of the input line frequency. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.3 | Unsigned32 | read-only | current |
| tlpUpsInputLowTransferVoltage OBJECT-TYPE The minimum line voltage allowed before the ups system transfers to battery backup. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.4 | Unsigned32 | read-only | current |
| tlpUpsInputLowTransferVoltageLowerBound OBJECT-TYPE The lower boundary value of tlpUpsInputLowTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.5 | Unsigned32 | read-only | current |
| tlpUpsInputLowTransferVoltageUpperBound OBJECT-TYPE The upper boundary value of tlpUpsInputLowTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.6 | Unsigned32 | read-only | current |
| tlpUpsInputHighTransferVoltage OBJECT-TYPE The maximum line voltage allowed before the ups system transfers to battery backup. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.7 | Unsigned32 | read-only | current |
| tlpUpsInputHighTransferVoltageLowerBound OBJECT-TYPE The lower boundary value of tlpUpsInputHighTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.8 | Unsigned32 | read-only | current |
| tlpUpsInputHighTransferVoltageUpperBound OBJECT-TYPE The upper boundary value of tlpUpsInputHighTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.9 | Unsigned32 | read-only | current |
| tlpUpsInputWattHours OBJECT-TYPE The number of watt hours of energy utilized in the past 24 hours. Use tlpUpsControlResetWattHours to reset the watt hours calculation algorithm. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.10 | Unsigned32 | read-only | current |
| tlpUpsInputLowTransferVoltageResetTolerance OBJECT-TYPE If a unit is transferred to battery backup due to under-voltage, the line voltage has to rise above this value from tlpUpsConfigLowVoltageTransfer, before the unit switched back to the AC input. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.11 | Unsigned32 | read-only | current |
| tlpUpsInputHighTransferVoltageResetTolerance OBJECT-TYPE If an input transferred to battery backup due to over-voltage, the line voltage on the input source has to fall below this value from tlpUpsConfigHighVoltageTransfer, before the unit switched back to the AC input. | 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.12 | Unsigned32 | read-only | current |
| tlpUpsInputPhaseTable OBJECT-TYPE The input phase details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps and tlpUpsIdentNumPhases. | 1.3.6.1.4.1.850.1.1.3.1.3.2.2 | not-accessible | current | |
| tlpUpsInputPhaseEntry OBJECT-TYPE An entry containing information applicable to a particular input phase managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1 | not-accessible | current | |
| tlpUpsInputPhaseIndex OBJECT-TYPE The table row index for the ups input phase. | 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.1 | Unsigned32 | read-only | current |
| tlpUpsInputPhaseFrequency OBJECT-TYPE The present input frequency for a given input line. | 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.2 | Unsigned32 | read-only | current |
| tlpUpsInputPhaseVoltage OBJECT-TYPE The magnitude of the present input voltage for a given input line. | 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.3 | Unsigned32 | read-only | current |
| tlpUpsInputPhaseVoltageMin OBJECT-TYPE The minimum input voltage value since the last reset of this value for a given input line. If any value is written to either tlpUpsInputVoltageMin or tlpUpsInputVoltageMax, both will be reset to their appropriate minimum and maximum values. | 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.4 | Unsigned32 | read-write | current |
| tlpUpsInputPhaseVoltageMax OBJECT-TYPE The maximum input voltage value since the last reset of this value for a given input line. If any value is written to either tlpUpsInputVoltageMin or tlpUpsInputVoltageMax, both will be reset to their appropriate minimum and maximum values. | 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.5 | Unsigned32 | read-write | current |
| tlpUpsInputPhaseCurrent OBJECT-TYPE The magnitude of the present input current. | 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.6 | Unsigned32 | read-only | current |
| tlpUpsInputPhasePower OBJECT-TYPE The magnitude of the present input true power. | 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.7 | Unsigned32 | read-only | current |
| tlpUpsOutput OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.3 | |||
| tlpUpsOutputTable OBJECT-TYPE The output details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps. | 1.3.6.1.4.1.850.1.1.3.1.3.3.1 | not-accessible | current | |
| tlpUpsOutputEntry OBJECT-TYPE An entry containing information applicable to a particular output line managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1 | not-accessible | current | |
| tlpUpsOutputSource OBJECT-TYPE The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. | 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.1 | INTEGER {unknown(0), other(1), none(2), normal(3), bypass(4), battery(5), boosting(6), reducing(7), second(8), economy(9), testing(10)} | read-only | current |
| tlpUpsOutputNominalVoltage OBJECT-TYPE The nominal value of the output voltage. This value may not be supported on all models. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.2 | Unsigned32 | read-only | current |
| tlpUpsOutputFrequency OBJECT-TYPE The present output frequency. The output frequency on most ups devices is common across all output lines. Some ups devices, however, maintain the output frequency per each line. If a common frequency is supported by the ups, then this frequency will contain the common frequency value. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.3 | Unsigned32 | read-only | current |
| tlpUpsOutputVARating OBJECT-TYPE The VA Rating of the ups. This value may not be supported on all models. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.4 | Unsigned32 | read-only | current |
| tlpUpsOutputPowerFactor OBJECT-TYPE The percentage of output power factor. | 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.5 | Unsigned32 | read-only | current |
| tlpUpsOutputLineTable OBJECT-TYPE The output line details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps. | 1.3.6.1.4.1.850.1.1.3.1.3.3.2 | not-accessible | current | |
| tlpUpsOutputLineEntry OBJECT-TYPE An entry containing information applicable to a particular output line managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1 | not-accessible | current | |
| tlpUpsOutputLineIndex OBJECT-TYPE The table row index for the ups output line. | 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.1 | Unsigned32 | read-only | current |
| tlpUpsOutputLineVoltage OBJECT-TYPE The magnitude of the present output voltage for a given output line. | 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.2 | Unsigned32 | read-only | current |
| tlpUpsOutputLineCurrent OBJECT-TYPE The output current, in hundredths of amps, for a given line. The actual precision of this value, whether a whole number, tenths or hundredths, is returned by tlpUpsDeviceOutputCurrentPrecision. | 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.3 | Unsigned32 | read-only | current |
| tlpUpsOutputLinePower OBJECT-TYPE The present output true power. | 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.4 | Unsigned32 | read-only | current |
| tlpUpsOutputLinePercentLoad OBJECT-TYPE The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. | 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.5 | INTEGER (0..200) | read-only | current |
| tlpUpsOutputLineFrequency OBJECT-TYPE The present output frequency on this output line. The output frequency on most ups devices is common across all output lines. Some ups devices, however, maintain the output frequency per each line. If a per line frequency is supported by the ups, then this frequency value will reports the value of this line. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.6 | Unsigned32 | read-only | current |
| tlpUpsOutputLineApparentPower OBJECT-TYPE The present output apparent power. | 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.9 | Unsigned32 | read-only | current |
| tlpUpsBypass OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.4 | |||
| tlpUpsBypassTable OBJECT-TYPE The bypass details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps. | 1.3.6.1.4.1.850.1.1.3.1.3.4.1 | not-accessible | current | |
| tlpUpsBypassEntry OBJECT-TYPE An entry containing information applicable to all input lines per each ups managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.4.1.1 | not-accessible | current | |
| tlpUpsBypassFrequency OBJECT-TYPE The present bypass frequency. | 1.3.6.1.4.1.850.1.1.3.1.3.4.1.1.1 | Unsigned32 | read-only | current |
| tlpUpsBypassLineTable OBJECT-TYPE The bypass line details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps. | 1.3.6.1.4.1.850.1.1.3.1.3.4.2 | not-accessible | current | |
| tlpUpsBypassLineEntry OBJECT-TYPE An entry containing information applicable to a particular bypass line managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.4.2.1 | not-accessible | current | |
| tlpUpsBypassLineIndex OBJECT-TYPE The bypass line identifier. | 1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.1 | Unsigned32 | read-only | current |
| tlpUpsBypassLineVoltage OBJECT-TYPE The present bypass voltage. | 1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.2 | Unsigned32 | read-only | current |
| tlpUpsBypassLineCurrent OBJECT-TYPE The present bypass current. | 1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.3 | Unsigned32 | read-only | current |
| tlpUpsBypassLinePower OBJECT-TYPE The present true power conveyed by the bypass. | 1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.4 | Unsigned32 | read-only | current |
| tlpUpsOutlet OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.5 | |||
| tlpUpsOutletTable OBJECT-TYPE The details of each ups outlet in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1 | not-accessible | current | |
| tlpUpsOutletEntry OBJECT-TYPE An entry containing information applicable to a particular outlet managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1 | not-accessible | current | |
| tlpUpsOutletIndex OBJECT-TYPE The table row index for the ups outlet. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.1 | Unsigned32 | read-only | current |
| tlpUpsOutletName OBJECT-TYPE A user-definable string identifying the name of the outlet. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.2 | DisplayString | read-write | current |
| tlpUpsOutletDescription OBJECT-TYPE A user-definable string identifying the device(s) connected to the given outlet. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.3 | DisplayString | read-write | current |
| tlpUpsOutletState OBJECT-TYPE The current state of the outlet. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.4 | INTEGER {unknown(0), off(1), on(2)} | read-only | current |
| tlpUpsOutletControllable OBJECT-TYPE Denotes whether this outlet is controllable. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.5 | TruthValue | read-only | current |
| tlpUpsOutletCommand OBJECT-TYPE Reading this value will always return 0. Setting this value to turnOff(1) will turn off the outlet. Setting this value to turnOn(2) will turn on the outlet. Setting this value to cycle(3) will turn the outlet off, then turn it back on. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.6 | INTEGER {idle(0), turnOff(1), turnOn(2), cycle(3)} | read-write | current |
| tlpUpsOutletVoltage OBJECT-TYPE The magnitude of the present output voltage for a given outlet. If the voltage measurement is not supported for an individual receptacle regardless whether device-wide or just for this receptacle, then this value will always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle voltage measurements is denoted by tlpUpsSupportsOutletVoltage. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.7 | Unsigned32 | read-only | current |
| tlpUpsOutletCurrent OBJECT-TYPE The present output current, in hundredths of amps, of a given outlet. If the current measurement is not supported for an individual receptacle regardless whether device-wide or just for this receptacle, then this value will always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle current measurements is denoted by tlpUpsSupportsCurrentPower. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.8 | Unsigned32 | read-only | current |
| tlpUpsOutletPower OBJECT-TYPE The output power of a given outlet. If the power measurement is not supported for an individual receptacle regardless whether device-wide or just for this receptacle, then this value will always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle power measurements is denoted by tlpUpsSupportsCurrentPower. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.9 | Unsigned32 | read-only | current |
| tlpUpsOutletRampAction OBJECT-TYPE The ramp action to take on a given outlet when powering on the device. If this receptacle is not controllable, as denoted by tlpUpsOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.10 | INTEGER {remainOff(0), turnOnAfterDelay(1)} | read-write | current |
| tlpUpsOutletRampDelay OBJECT-TYPE The number of seconds to delay before powering on the given outlet. If this receptacle is not controllable, as denoted by tlpUpsOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.11 | Integer32 | read-write | current |
| tlpUpsOutletShedAction OBJECT-TYPE The shed action to take on a given outlet when powering off the device. If this receptacle is not controllable, as denoted by tlpUpsOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.12 | INTEGER {remainOn(0), turnOffAfterDelay(1)} | read-write | current |
| tlpUpsOutletShedDelay OBJECT-TYPE The number of seconds to delay before powering off the given outlet. If this receptacle is not controllable, as denoted by tlpUpsOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.13 | Integer32 | read-write | current |
| tlpUpsOutletGroup OBJECT-TYPE The tlpUpsOutletGroupIndex group index of the respective group to which the given outlet is assigned, or zero (0) if the given outlet is not grouped. | 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.14 | Integer32 | read-write | current |
| tlpUpsOutletGroupTable OBJECT-TYPE The receptacle grouping details of each ups in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpUpsIdentNumOutletGroups per each device. | 1.3.6.1.4.1.850.1.1.3.1.3.5.2 | not-accessible | current | |
| tlpUpsOutletGroupEntry OBJECT-TYPE An entry containing information applicable to a particular outlet group managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.5.2.1 | not-accessible | current | |
| tlpUpsOutletGroupIndex OBJECT-TYPE The table row index for the ups outlet group. | 1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.1 | Unsigned32 | read-only | current |
| tlpUpsOutletGroupRowStatus OBJECT-TYPE Row status for the tlpUpsOutletGroupTable | 1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.2 | RowStatus | read-write | current |
| tlpUpsOutletGroupName OBJECT-TYPE The name of this outlet group. | 1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.3 | DisplayString | read-write | current |
| tlpUpsOutletGroupDescription OBJECT-TYPE A description for this outlet group. | 1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.4 | DisplayString | read-write | current |
| tlpUpsOutletGroupState OBJECT-TYPE The current state of the outlet group. This value will report off(1) if all outlets in the group are off, on(2) if all outlets in the group are on, mixed(3) if some outlets in the group are off and others are on, or unknown(0) if the state of the outlets cannot be determined. | 1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.5 | INTEGER {unknown(0), off(1), on(2), mixed(3)} | read-only | current |
| tlpUpsOutletGroupCommand OBJECT-TYPE Reading this value will always return 0. Setting this value to turnOff(1) will turn off every outlet associated with the group. Setting this value to turnOn(2) will turn on every outlet associated with the group. Setting this value to cycle(3) will turn off every outlet associated with the group, then turn each outlet back on. | 1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.6 | INTEGER {idle(0), turnOff(1), turnOn(2), cycle(3)} | read-write | current |
| tlpUpsWatchdog OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.6 | |||
| tlpUpsWatchdogTable OBJECT-TYPE The watchdog details of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. | 1.3.6.1.4.1.850.1.1.3.1.3.6.1 | not-accessible | current | |
| tlpUpsWatchdogEntry OBJECT-TYPE An entry containing watchdog details for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.3.6.1.1 | not-accessible | current | |
| tlpUpsWatchdogSupported OBJECT-TYPE Indicates whether or not this ups supports a watchdog reboot. | 1.3.6.1.4.1.850.1.1.3.1.3.6.1.1.1 | TruthValue | read-only | current |
| tlpUpsWatchdogSecsBeforeReboot OBJECT-TYPE The maximum number of seconds that can expire between polls that the engine makes to the ups for data. If this time runs out, then the ups will cycle its outputs. Set this to zero to turns disable this feature. | 1.3.6.1.4.1.850.1.1.3.1.3.6.1.1.2 | Unsigned32 | read-write | current |
| tlpUpsFan OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.7 | |||
| tlpUpsFanTable OBJECT-TYPE The fan speed of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumFans. | 1.3.6.1.4.1.850.1.1.3.1.3.7.1 | not-accessible | current | |
| tlpUpsFanEntry OBJECT-TYPE An entry containing information applicable to a particular fan managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.7.1.1 | not-accessible | current | |
| tlpUpsFanIndex OBJECT-TYPE The table row index for the ups fan speed. | 1.3.6.1.4.1.850.1.1.3.1.3.7.1.1.1 | Unsigned32 | read-only | current |
| tlpUpsFanSpeed OBJECT-TYPE The fan speed in rotations per minute. | 1.3.6.1.4.1.850.1.1.3.1.3.7.1.1.2 | Unsigned32 | read-only | current |
| tlpUpsHeatsink OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.8 | |||
| tlpUpsHeatsinkTable OBJECT-TYPE A list of ups heatsink thermistor table entries. The number of entries is given by the value of tlpUpsIdentNumHeatsinks. | 1.3.6.1.4.1.850.1.1.3.1.3.8.1 | not-accessible | current | |
| tlpUpsHeatsinkEntry OBJECT-TYPE An entry containing information applicable to a particular heatsink managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.3.8.1.1 | not-accessible | current | |
| tlpUpsHeatsinkIndex OBJECT-TYPE The table row index for the ups heatsink. | 1.3.6.1.4.1.850.1.1.3.1.3.8.1.1.1 | Unsigned32 | read-only | current |
| tlpUpsHeatsinkTemperatureC OBJECT-TYPE The temperature at the heatsink thermistor in tenths degrees Celsius. Heatsink temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.8.1.1.2 | Integer32 | read-only | current |
| tlpUpsHeatsinkTemperatureF OBJECT-TYPE The temperature at the heatsink thermistor in tenths degrees Fahrenheit. Heatsink temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.8.1.1.3 | Integer32 | read-only | current |
| tlpUpsContact OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.9 | |||
| tlpUpsInputContact OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.9.1 | |||
| tlpUpsInputContactTable OBJECT-TYPE The input contact details of each ups in the device table. The number of entries is given by the value of tlpUpsIdentNumInputContacts. | 1.3.6.1.4.1.850.1.1.3.1.3.9.1.1 | not-accessible | current | |
| tlpUpsInputContactEntry OBJECT-TYPE An entry containing input contact details for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.3.9.1.1.1 | not-accessible | current | |
| tlpUpsInputContactIndex OBJECT-TYPE The table row index for the ups input contact details. | 1.3.6.1.4.1.850.1.1.3.1.3.9.1.1.1.1 | Unsigned32 | read-only | current |
| tlpUpsInputContactInAlarm OBJECT-TYPE The alarm status of the input contact. Input contacts are not supported on all models. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.9.1.1.1.2 | INTEGER {notInAlarm(0), inAlarm(1)} | read-only | current |
| tlpUpsOutputContact OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.3.9.2 | |||
| tlpUpsOutputContactTable OBJECT-TYPE The output contact details of each ups in the device table. The number of entries is given by the value of tlpUpsIdentNumOuputContacts. | 1.3.6.1.4.1.850.1.1.3.1.3.9.2.1 | not-accessible | current | |
| tlpUpsOutputContactEntry OBJECT-TYPE An entry containing output contact details for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.3.9.2.1.1 | not-accessible | current | |
| tlpUpsOutputContactIndex OBJECT-TYPE The table row index for the ups output contact details. | 1.3.6.1.4.1.850.1.1.3.1.3.9.2.1.1.1 | Unsigned32 | read-only | current |
| tlpUpsOutputContactInAlarm OBJECT-TYPE The alarm status of the output contact. Output contacts are not supported on all models. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.3.9.2.1.1.2 | INTEGER {notInAlarm(0), inAlarm(1)} | read-only | current |
| tlpUpsControl OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.4 | |||
| tlpUpsControlTable OBJECT-TYPE The actionable controls for each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. | 1.3.6.1.4.1.850.1.1.3.1.4.1 | not-accessible | current | |
| tlpUpsControlEntry OBJECT-TYPE An entry containing controls for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1 | not-accessible | current | |
| tlpUpsControlSelfTest OBJECT-TYPE Set to TRUE to initiate a self test on the ups. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.1 | TruthValue | read-write | current |
| tlpUpsControlRamp OBJECT-TYPE Set to TRUE to initiate the pre-designated ramp sequence on the ups. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.2 | TruthValue | read-write | current |
| tlpUpsControlShed OBJECT-TYPE Set to TRUE to initiate the pre-designated shed sequence on the ups. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.3 | TruthValue | read-write | current |
| tlpUpsControlUpsOn OBJECT-TYPE Set to TRUE to turn the ups on. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.4 | TruthValue | read-write | current |
| tlpUpsControlUpsOff OBJECT-TYPE Set to TRUE to turn the ups off. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.5 | TruthValue | read-write | current |
| tlpUpsControlUpsReboot OBJECT-TYPE Set to TRUE to reboot the ups. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.6 | TruthValue | read-write | current |
| tlpUpsControlBypass OBJECT-TYPE This switches the ups in and out of bypass mode. This value returns the current bypass mode: disable(0) if the ups is not in bypass mode, enable(1) if the ups is in bypass mode. Set to disable(0) to exit bypass mode, or enable(1) to enter bypass mode. If switching bypass mode is not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.7 | INTEGER {disable(0), enable(1)} | read-write | current |
| tlpUpsControlResetWattHours OBJECT-TYPE Set to TRUE to reset the tlpUpsInputWattHours calculation algorithm. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.8 | TruthValue | read-write | current |
| tlpUpsControlCancelSelfTest OBJECT-TYPE Set to TRUE to cancel the self test in progress. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.9 | TruthValue | read-write | current |
| tlpUpsControlResetAllParameters OBJECT-TYPE Set to TRUE to reset all configuration settings to the default values. | 1.3.6.1.4.1.850.1.1.3.1.4.1.1.10 | TruthValue | read-write | current |
| tlpUpsConfig OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.5 | |||
| tlpUpsConfigTable OBJECT-TYPE The configuration details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss managed by the agent as reported by tlpUpsIdentNumUps. | 1.3.6.1.4.1.850.1.1.3.1.5.1 | not-accessible | current | |
| tlpUpsConfigEntry OBJECT-TYPE An entry containing information applicable to all input lines per each ups managed by this agent. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1 | not-accessible | current | |
| tlpUpsConfigInputVoltage OBJECT-TYPE The nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. This value may not be writable on all models. If not writable, the value will be rejected and an appropriate error message will be returned. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.1 | Unsigned32 | read-write | current |
| tlpUpsConfigInputFrequency OBJECT-TYPE The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.2 | Unsigned32 | read-write | current |
| tlpUpsConfigOutputVoltage OBJECT-TYPE The nominal value of the output voltage. This value may not be supported on all models. If not supported, the agent reports ERROR_NO_SUCH_NAME. This value may not be writable on all models. If not writable, the value will be rejected and an appropriate error message will be returned. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.3 | Unsigned32 | read-write | current |
| tlpUpsConfigOutputFrequency OBJECT-TYPE The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request will be rejected and the agent will respond with an appropriate error message. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.4 | Unsigned32 | read-write | current |
| tlpUpsConfigAudibleStatus OBJECT-TYPE The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self- describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.5 | INTEGER {disabled(1), enabled(2), muted(3)} | read-write | current |
| tlpUpsConfigAutoBatteryTest OBJECT-TYPE When disabled(0), the ups will not perform an automatic battery selftest. When set to another value, the ups will perform an automatic selftest in the approximate period defined by each respective enumerated value. This feature is generally not recommended. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.6 | INTEGER {disabled(0), biweekly(1), monthly(2), quarterly(3), semiannually(4)} | read-write | current |
| tlpUpsConfigAutoRestartAfterShutdown OBJECT-TYPE When enabled(1), the ups should autorestart after a shutdown from battery mode if valid AC is applied. When disabled(0), the ups should not autorestart when AC is restored and instead power up into standby mode. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.7 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpUpsConfigAutoRampOnTransition OBJECT-TYPE When enabled(1), the ups should perform its preconfigured ramp sequence when valid AC is restored while in battery mode. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.8 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpUpsConfigAutoShedOnTransition OBJECT-TYPE When enabled(1), the ups should perform its preconfigured shed sequence when valid AC is lost causing the ups to enter battery mode. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.9 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpUpsConfigBypassLowerLimitPercent OBJECT-TYPE The lowest AC input voltage allowed to be output to the load while in bypass mode. This setting is expressed as a percentage from nominal voltage. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.10 | INTEGER (-20..-5) | read-write | current |
| tlpUpsConfigBypassUpperLimitPercent OBJECT-TYPE The highest AC input voltage allowed to be output to the load while in bypass mode. This setting is expressed as a percentage from nominal voltage. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.11 | INTEGER (5..20) | read-write | current |
| tlpUpsConfigBypassLowerLimitVoltage OBJECT-TYPE The lowest AC input voltage allowed to be output to the load while in bypass mode. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.12 | Unsigned32 | read-write | current |
| tlpUpsConfigBypassUpperLimitVoltage OBJECT-TYPE The highest AC input voltage allowed to be output to the load while in bypass mode. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.13 | Unsigned32 | read-write | current |
| tlpUpsConfigColdStart OBJECT-TYPE This option enables or disables the ability to turn the ups on without AC supplied. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.14 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpUpsConfigEconomicMode OBJECT-TYPE The configurable economic mode options for the ups. The online(0) mode is the default configuration of most upss, which is synonymous as having the economic mode disabled. The economy(1) mode is the typical configuration to run in economy mode, which is synonymous as having the economic mode enabled. Constant50Hz(2) is a power strategy, which fixes the output frequency at 50Hz. Constant60Hz(3) is a power strategy, which fixes the output frequency at 60Hz. ConstantAuto(4) regulates the output frequency at nominal input frequency. AutoAdaptive(5) mode will cause the ups to automatically switch between online(0), maximum quality, and economy(1), maximum efficiency, to improve efficiency during stable utility periods and improve output regulation during unstable utility periods. Not all values are supported by all upss. Most upss, if supportive of economic mode, only supports online(0) and economy(1). If the ups does not support economic mode, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.15 | INTEGER {online(0), economy(1), constant50Hz(2), constant60Hz(3), constantAuto(4), autoAdaptive(5)} | read-write | current |
| tlpUpsConfigFaultAction OBJECT-TYPE Determines the action to take if the output needs to be shut down due to a fault condition, limited by the type of fault incurred. When configured for bypass(0), the ups will go to bypass on a fault condition. When configured for standby(1), the ups will go to standby mode on a fault condition. Either configuration will be valid as long as AC input is within normal line voltage and frequency limits when the fault condition occurs. If the line is outside these limits, the ups will turn off. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.16 | INTEGER {bypass(0), standby(1)} | read-write | current |
| tlpUpsConfigOffMode OBJECT-TYPE This option governs what mode the ups should go into when AC input is available, but the load is either off or not battery backed up. If this setting is configured for bypass(1), the intention is that any time the ups would normally go into standby mode, it would instead go into bypass mode. Note that this setting does not dictate the mode for fault conditions, which is governed by tlpUpsConfigFaultAction. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.17 | INTEGER {standby(0), bypass(1)} | read-write | current |
| tlpUpsConfigLineSensitivity OBJECT-TYPE Adjusts the AC line voltage sensitivity setting. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.18 | INTEGER {normal(0), reduced(1), fullyReduced(2)} | read-write | current |
| tlpUpsConfigLineQualifyTime OBJECT-TYPE The amount of time the ups monitors line power quality for stability before ac power is restored. If there is an attempt to set this variable to a value that is not supported, the request will be rejected and the agent will respond with an appropriate error message. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.19 | Unsigned32 | read-write | current |
| tlpUpsConfigACPowerSenseType OBJECT-TYPE This option enables configuration of ups AC power sensing to maximize ups operation for standard line power AC and generator power applications. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.1.1.20 | INTEGER {generator(1), ups(2)} | read-write | current |
| tlpUpsConfigAutoRestartTable OBJECT-TYPE The configurable automatic restart options of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. Not all options are available on all upss. | 1.3.6.1.4.1.850.1.1.3.1.5.2 | not-accessible | current | |
| tlpUpsConfigAutoRestartEntry OBJECT-TYPE An entry containing configurable automatic restart options for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.5.2.1 | not-accessible | current | |
| tlpUpsConfigAutoRestartInverterShutdown OBJECT-TYPE If enabled(1) and the ups is turned off from invert mode (via user interaction), if line becomes valid, the ups will automatically go to line mode. If disabled(0), the ups will turn back on and go to standby mode instead. | 1.3.6.1.4.1.850.1.1.3.1.5.2.1.1 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpUpsConfigAutoRestartDelayedWakeup OBJECT-TYPE If enabled(1) and power fails during a DelayBeforeStartup and line remains invalid after the timeout expires, the ups will be set to turn back on automatically. If disabled(0), the ups will turn back on and go to standby mode instead. | 1.3.6.1.4.1.850.1.1.3.1.5.2.1.2 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpUpsConfigAutoRestartLowVoltageCutoff OBJECT-TYPE If enabled(1) and the ups is turned off from invert mode (via low voltage cutoff), if line becomes valid, the ups will automatically go to line mode. If disabled(0), the ups will turn back on and go to standby mode instead. | 1.3.6.1.4.1.850.1.1.3.1.5.2.1.3 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpUpsConfigAutoRestartOverLoad OBJECT-TYPE If enabled(1) and the ups is turned off from invert mode (via overload), if line becomes valid, the ups will automatically go to line mode. If disabled(0), the ups will turn back on and go to standby mode instead. | 1.3.6.1.4.1.850.1.1.3.1.5.2.1.4 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpUpsConfigAutoRestartOverTemperature OBJECT-TYPE If enabled(1) and the ups is turned off from invert mode (via over temperature), if line becomes valid, the ups will automatically go to line mode. If disabled(0), the ups will turn back on and go to standby mode instead. | 1.3.6.1.4.1.850.1.1.3.1.5.2.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpUpsConfigThresholdTable OBJECT-TYPE The configurable threshold options of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. Not all options are available on all upss. | 1.3.6.1.4.1.850.1.1.3.1.5.3 | not-accessible | current | |
| tlpUpsConfigThresholdEntry OBJECT-TYPE An entry containing configurable threshold options for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.5.3.1 | not-accessible | current | |
| tlpUpsConfigBatteryAgeThreshold OBJECT-TYPE The number of months for a battery to be in service. The battery age alarm, tlpUpsAlarmBatteryAgeAboveThreshold, is triggered when the current date exceeds tlpUpsBatteryPackIdentInstallDate by tlpUpsConfigBatteryAgeThreshold months. | 1.3.6.1.4.1.850.1.1.3.1.5.3.1.1 | Unsigned32 | read-write | current |
| tlpUpsConfigLowBatteryThreshold OBJECT-TYPE This value denotes the percentage of battery capacity remaining warning level. The low battery alarm, tlpUpsAlarmLowBattery, is triggered when tlpUpsEstimatedChargeRemaining drops below this value. | 1.3.6.1.4.1.850.1.1.3.1.5.3.1.2 | INTEGER (5..95) | read-write | current |
| tlpUpsConfigLowBatteryTime OBJECT-TYPE The value in seconds of tlpUpsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected. | 1.3.6.1.4.1.850.1.1.3.1.5.3.1.3 | Unsigned32 | read-write | current |
| tlpUpsConfigOverLoadThreshold OBJECT-TYPE This value denotes the percentage of load at which the overload condition occurs. The overload alarm, tlpUpsAlarmOutputOverload, is triggered when the percentage of output load exceeds this value. | 1.3.6.1.4.1.850.1.1.3.1.5.3.1.4 | INTEGER (5..105) | read-write | current |
| tlpUpsConfigVoltageTable OBJECT-TYPE The voltage configuration details for each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. Not all options are available on all upss. | 1.3.6.1.4.1.850.1.1.3.1.5.4 | not-accessible | current | |
| tlpUpsConfigVoltageEntry OBJECT-TYPE An entry containing voltage configuration options for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.5.4.1 | not-accessible | current | |
| tlpUpsConfigHighVoltageTransfer OBJECT-TYPE The maximum line voltage allowed on the input source before the unit disconnects the AC input connection. | 1.3.6.1.4.1.850.1.1.3.1.5.4.1.1 | Unsigned32 | read-write | current |
| tlpUpsConfigHighVoltageResetTolerance OBJECT-TYPE If an input connection is disconnected due to over-voltage, the line voltage on the input source has to fall below tlpUpsConfigHighVoltageTransfer less tlpUpsConfigHighVoltageTransferResetTolerance ` before the unit reconnects the AC input to input source. | 1.3.6.1.4.1.850.1.1.3.1.5.4.1.2 | Unsigned32 | read-write | current |
| tlpUpsConfigHighVoltageReset OBJECT-TYPE If an input connection is disconnected due to over-voltage, the line voltage on the input source has to fall below tlpUpsConfigHighVoltageReset before the unit reconnects the AC input to input source. | 1.3.6.1.4.1.850.1.1.3.1.5.4.1.3 | Unsigned32 | read-write | current |
| tlpUpsConfigLowVoltageTransfer OBJECT-TYPE The minimum line voltage allowed before the unit disconnects the AC input connection. | 1.3.6.1.4.1.850.1.1.3.1.5.4.1.4 | Unsigned32 | read-write | current |
| tlpUpsConfigLowVoltageResetTolerance OBJECT-TYPE If a unit is disconnected due to under-voltage or is not powered up yet, the line voltage has to rise above tlpUpsConfigLowVoltageTransfer plus tlpUpsConfigLowVoltageTransferResetTolerance before the unit reonnect the AC input to input source. | 1.3.6.1.4.1.850.1.1.3.1.5.4.1.5 | Unsigned32 | read-write | current |
| tlpUpsConfigLowVoltageReset OBJECT-TYPE If a unit is disconnected due to under-voltage or is not powered up yet, the line voltage has to rise above tlpUpsConfigLowVoltageReset before the unit reonnect the AC input to input source. | 1.3.6.1.4.1.850.1.1.3.1.5.4.1.6 | Unsigned32 | read-write | current |
| tlpUpsConfigContact OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.1.5.5 | |||
| tlpUpsConfigContactTable OBJECT-TYPE The configuration options of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. Not all options are available on all upss. | 1.3.6.1.4.1.850.1.1.3.1.5.5.1 | not-accessible | current | |
| tlpUpsConfigContactEntry OBJECT-TYPE An entry containing contact configuration options for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.5.5.1.1 | not-accessible | current | |
| tlpUpsConfigOutputContactBackupTimer OBJECT-TYPE This is the amount of runtime the UPS supports in battery mode before sending a configured output contact notification. Output contacts are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.5.1.1.1 | INTEGER | read-write | current |
| tlpUpsConfigInputContactTable OBJECT-TYPE The input contact details of each ups in device table. the number of entries is given by tlpUpsIdentNumInputContacts. This is a sparse dependent table, and will contain some subset of devices that are upss. Not all options are available on all upss. | 1.3.6.1.4.1.850.1.1.3.1.5.5.2 | not-accessible | current | |
| tlpUpsConfigInputContactEntry OBJECT-TYPE An entry containing input contact details for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.5.5.2.1 | not-accessible | current | |
| tlpUpsConfigInputContactIndex OBJECT-TYPE The table row index for the ups input contact details. | 1.3.6.1.4.1.850.1.1.3.1.5.5.2.1.1 | Unsigned32 | read-only | current |
| tlpUpsConfigInputContactSetup OBJECT-TYPE Input contact configuration options. Input contacts are not supported on all models. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.5.2.1.2 | INTEGER {userDefined(0), externalAlarm(1), externalBatteryAlarm(2), externalFanFailed(3), doorUnlock(4)} | read-write | current |
| tlpUpsConfigOutputContactTable OBJECT-TYPE Output contact details of each ups in device table. The number of entries is given by tlpUpsIdentNumOutputContacts. This is a sparse dependent table, and will contain some subset of devices that are upss. Not all options are available on all upss. | 1.3.6.1.4.1.850.1.1.3.1.5.5.3 | not-accessible | current | |
| tlpUpsConfigOutputContactEntry OBJECT-TYPE An entry containing output contact details for a particular ups. | 1.3.6.1.4.1.850.1.1.3.1.5.5.3.1 | not-accessible | current | |
| tlpUpsConfigOutputContactIndex OBJECT-TYPE The table row index for the ups output contact details. | 1.3.6.1.4.1.850.1.1.3.1.5.5.3.1.1 | Unsigned32 | read-only | current |
| tlpUpsConfigOutputContactSetup OBJECT-TYPE Output contact configuration options. Output contacts are not supported on all models. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.1.5.5.3.1.2 | INTEGER {disabled(0), onBattery(1), batteryLow(2), timer(3), alarm(4), fault(5), outputOff(6)} | read-write | current |
| tlpPdu OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2 | |||
| tlpPduIdent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.1 | |||
| tlpPduIdentNumPdu OBJECT-TYPE The number of pdu devices that this agent is currently managing. | 1.3.6.1.4.1.850.1.1.3.2.1.1 | Unsigned32 | read-only | current |
| tlpPduIdentTable OBJECT-TYPE The identity details of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus. | 1.3.6.1.4.1.850.1.1.3.2.1.2 | not-accessible | current | |
| tlpPduIdentEntry OBJECT-TYPE An entry containing details for a particular pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.2.1 | not-accessible | current | |
| tlpPduIdentNumInputs OBJECT-TYPE The number of input lines supported by the pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.2.1.1 | Unsigned32 | read-only | current |
| tlpPduIdentNumOutputs OBJECT-TYPE The number of output lines supported by the pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.2.1.2 | Unsigned32 | read-only | current |
| tlpPduIdentNumPhases OBJECT-TYPE The number of phases supported by the pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.2.1.3 | Unsigned32 | read-only | current |
| tlpPduIdentNumOutlets OBJECT-TYPE The number of receptacles supported by the pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.2.1.4 | Unsigned32 | read-only | current |
| tlpPduIdentNumOutletGroups OBJECT-TYPE The number of receptacle groups supported by the pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.2.1.5 | Unsigned32 | read-only | current |
| tlpPduIdentNumCircuits OBJECT-TYPE The number of circuits supported by the pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.2.1.6 | Unsigned32 | read-only | current |
| tlpPduIdentNumBreakers OBJECT-TYPE The number of monitored bank breakers supported by the pdu. If the pdu has breakers that are not monitored by the device, the value of zero(0) will be returned. | 1.3.6.1.4.1.850.1.1.3.2.1.2.1.7 | Unsigned32 | read-only | current |
| tlpPduIdentNumHeatsinks OBJECT-TYPE The number of heatsink thermistors supported by the pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.2.1.8 | Unsigned32 | read-only | current |
| tlpPduSupportsTable OBJECT-TYPE The supported details of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus. | 1.3.6.1.4.1.850.1.1.3.2.1.3 | not-accessible | current | |
| tlpPduSupportsEntry OBJECT-TYPE An entry containing supported details for a particular pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.3.1 | not-accessible | current | |
| tlpPduSupportsEnergywise OBJECT-TYPE Indicates whether the pdu supports Cisco EnergyWise. | 1.3.6.1.4.1.850.1.1.3.2.1.3.1.1 | TruthValue | read-only | current |
| tlpPduSupportsRampShed OBJECT-TYPE Indicates whether the pdu supports ramping and shedding. | 1.3.6.1.4.1.850.1.1.3.2.1.3.1.2 | TruthValue | read-only | current |
| tlpPduSupportsOutletGroup OBJECT-TYPE Indicates whether the pdu supports outlet groups. | 1.3.6.1.4.1.850.1.1.3.2.1.3.1.3 | TruthValue | read-only | current |
| tlpPduSupportsOutletCurrentPower OBJECT-TYPE Indicates whether the pdu reports individual receptacle current and power measurements. Devices that do not support individual receptacle measurements will always return ERROR_NO_SUCH_NAME for tlpPduOutletCurrent and tlpPduOutletPower. | 1.3.6.1.4.1.850.1.1.3.2.1.3.1.4 | TruthValue | read-only | current |
| tlpPduSupportsOutletVoltage OBJECT-TYPE Indicates whether the pdu reports individual receptacle voltage measurements. Devices that do not support individual receptacle measurements will always return ERROR_NO_SUCH_NAME for tlpPduOutletVoltage. | 1.3.6.1.4.1.850.1.1.3.2.1.3.1.5 | TruthValue | read-only | current |
| tlpPduDisplayTable OBJECT-TYPE The display details of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus. | 1.3.6.1.4.1.850.1.1.3.2.1.4 | not-accessible | current | |
| tlpPduDisplayEntry OBJECT-TYPE An entry containing display details for a particular pdu. | 1.3.6.1.4.1.850.1.1.3.2.1.4.1 | not-accessible | current | |
| tlpPduDisplayScheme OBJECT-TYPE Indicates the display scheme of the LED display. The value schemeReverse(0) indicates the tricolor LED indicator uses an alternate pattern. The value schemeNormal(1) indicates the LED indicator uses the standard pattern. This value may not be supported on all models. If not supported, the value will always return schemeNormal(1). | 1.3.6.1.4.1.850.1.1.3.2.1.4.1.1 | INTEGER {schemeReverse(0), schemeNormal(1)} | read-write | current |
| tlpPduDisplayOrientation OBJECT-TYPE Indicates the physical orientation of the LED display. The value displayNormal(0) indicates the display is right-side-up (normal). The value displayReverse(1) indicates the display is upside-down. This value may not be supported on all models. If not supported, the value will always return displayNormal(0). | 1.3.6.1.4.1.850.1.1.3.2.1.4.1.2 | INTEGER {displayNormal(0), displayReverse(1)} | read-write | current |
| tlpPduDisplayAutoScroll OBJECT-TYPE Indicates whether the LED display automatically scrolls through displaying status values. | 1.3.6.1.4.1.850.1.1.3.2.1.4.1.3 | INTEGER {scrollDisabled(0), scrollEnabled(1)} | read-write | current |
| tlpPduDisplayIntensity OBJECT-TYPE Indicates the intensity, as a percentage, of the LED display. The value intensity100(4) indicates the display is at 100% intensity. The other values indicate the display is at a lesser intensity based upon the respective percentage denoted. | 1.3.6.1.4.1.850.1.1.3.2.1.4.1.4 | INTEGER {intensity25(1), intensity50(2), intensity75(3), intensity100(4)} | read-write | current |
| tlpPduDisplayUnits OBJECT-TYPE Indicates the units of measurement displayed on the LED display. The value normal(0) indicates that a temperature value, for example, is displayed in degrees Fahrenheit. The value metric(1) indicates a temperature value is displayed in degrees Celsius. | 1.3.6.1.4.1.850.1.1.3.2.1.4.1.5 | INTEGER {normal(0), metric(1)} | read-write | current |
| tlpPduDevice OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.2 | |||
| tlpPduDeviceTable OBJECT-TYPE The device details of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus. | 1.3.6.1.4.1.850.1.1.3.2.2.1 | not-accessible | current | |
| tlpPduDeviceEntry OBJECT-TYPE An entry containing device details for a particular pdu. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1 | not-accessible | current | |
| tlpPduDeviceMainLoadState OBJECT-TYPE The current state of the main output of the device. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.1 | INTEGER {unknown(0), off(1), on(2)} | read-only | current |
| tlpPduDeviceMainLoadControllable OBJECT-TYPE Indicates whether or not the main output is controllable, and whether the ups can be turned off and on. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.2 | TruthValue | read-only | current |
| tlpPduDeviceMainLoadCommand OBJECT-TYPE Reading this value will always return 0. Setting this value to turnOff(1) will turn off the main output of the ups. Setting this value to turnOn(2) will turn on the main output of the ups. Setting this value to cycle(3) will turn off the main output, then turn it back on. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.3 | INTEGER {idle(0), turnOff(1), turnOn(2), cycle(3)} | read-write | current |
| tlpPduDevicePowerOnDelay OBJECT-TYPE The configurable delay value, which sets the amount of additional time a given device will wait before it connects to a valid AC source. By default the delay value is set to 0. For devices with multiple AC input sources, this delay only applies to the primary input source. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.4 | Integer32 | read-write | current |
| tlpPduDeviceTotalInputPowerRating OBJECT-TYPE The total input power rating of all phases on the device. This value may not be supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.5 | Integer32 | read-only | current |
| tlpPduDeviceTemperatureC OBJECT-TYPE The ambient temperature at or near the PDU casing. Temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.6 | Integer32 | read-only | current |
| tlpPduDeviceTemperatureF OBJECT-TYPE The ambient temperature at or near the PDU casing. Temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.7 | Integer32 | read-only | current |
| tlpPduDevicePhaseImbalance OBJECT-TYPE The percentage of imbalance of the three phases. This value is in the range from 0% imbalance to 100% imbalance. The lower the value, the better balanced the phases are. If all load is on a single phase, the imbalance is defined as 100%. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.8 | INTEGER (0..200) | read-only | current |
| tlpPduDeviceOutputPowerTotal OBJECT-TYPE The AC output total power for all circuits. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.9 | Unsigned32 | read-only | current |
| tlpPduDeviceAggregatePowerFactor OBJECT-TYPE The aggregate power factor of all phases. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.10 | Unsigned32 | read-only | current |
| tlpPduDeviceOutputCurrentPrecision OBJECT-TYPE Output current is reported by tlpPduOutputCurrent, tlpPduOutputCurrentMin and tlpPduOutputCurrentMax. These values are all reported in hundredths(0.01A), which accommodates all models; however, on any given device the actual precision may vary. All current values must be divided by 100 to obtain the actual value. For example, if tlpPduOutputCurrent reports 500, then the actual output current is 5.00. This tlpPduDeviceOutputCurrentPrecision defines the actual resolution of that value: wholeNumber(0) is 5, tenths(1) is 5.0 and hundredths(2) is 5.00. | 1.3.6.1.4.1.850.1.1.3.2.2.1.1.11 | INTEGER {wholeNumber(0), tenths(1), hundredths(2)} | read-only | current |
| tlpPduDetail OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.3 | |||
| tlpPduInput OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.3.1 | |||
| tlpPduInputTable OBJECT-TYPE The input details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of pdus managed by the agent as reported by tlpPduIdentNumPdus. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1 | not-accessible | current | |
| tlpPduInputEntry OBJECT-TYPE An entry containing information applicable to a particular pdu managed by this agent. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1 | not-accessible | current | |
| tlpPduInputNominalVoltage OBJECT-TYPE The nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.1 | Unsigned32 | read-only | current |
| tlpPduInputNominalVoltagePhaseToPhase OBJECT-TYPE The nominal value of the input line voltage as measured from phase to phase. This value may not be supported on all models. If not supported, this value will always return zero. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.2 | Unsigned32 | read-only | current |
| tlpPduInputNominalVoltagePhaseToNeutral OBJECT-TYPE The nominal value of the input line voltage as measured from phase to neutral. This value may not be supported on all models. If not supported, this value will always return zero. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.3 | Unsigned32 | read-only | current |
| tlpPduInputLowTransferVoltage OBJECT-TYPE The minimum line voltage allowed before the unit disconnects the AC input connection. This value may not be writable on all models. If not writable, the value will be rejected and an appropriate error message will be returned. When supported, the minimum and maximum values allowed are dictated by tlpPduInputLowTransferVoltageLowerBound and tlpPduInputLowTransferVoltageUpperBound respectively. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.4 | Unsigned32 | read-only | current |
| tlpPduInputLowTransferVoltageLowerBound OBJECT-TYPE The lower boundary value of tlpPduInputLowTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.5 | Unsigned32 | read-only | current |
| tlpPduInputLowTransferVoltageUpperBound OBJECT-TYPE The upper boundary value of tlpPduInputLowTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.6 | Unsigned32 | read-only | current |
| tlpPduInputHighTransferVoltage OBJECT-TYPE The maximum line voltage allowed before the unit disconnects the AC input connection. This value may not be writable on all models. If not writable, the value will be rejected and an appropriate error message will be returned. When supported, the minimum and maximum values allowed are dictated by tlpPduInputHighTransferVoltageLowerBound and tlpPduInputHighTransferVoltageUpperBound respectively. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.7 | Unsigned32 | read-only | current |
| tlpPduInputHighTransferVoltageLowerBound OBJECT-TYPE The lower boundary value of tlpPduInputHighTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.8 | Unsigned32 | read-only | current |
| tlpPduInputHighTransferVoltageUpperBound OBJECT-TYPE The upper boundary value of tlpPduInputHighTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.9 | Unsigned32 | read-only | current |
| tlpPduInputCurrentLimit OBJECT-TYPE The capacity of each phase conductor in the pdu limited by the AC input cord or any other potential limiting factors unique to a given unit. | 1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.10 | Unsigned32 | read-only | current |
| tlpPduInputPhaseTable OBJECT-TYPE The input phase details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpPduIdentNumInputs and tlpPduIdentNumPhases per each device. | 1.3.6.1.4.1.850.1.1.3.2.3.1.2 | not-accessible | current | |
| tlpPduInputPhaseEntry OBJECT-TYPE An entry containing information applicable to a particular input phase managed by this agent. | 1.3.6.1.4.1.850.1.1.3.2.3.1.2.1 | not-accessible | current | |
| tlpPduInputPhaseIndex OBJECT-TYPE The table row index for the pdu phase. | 1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.1 | Unsigned32 | read-only | current |
| tlpPduInputPhasePhaseType OBJECT-TYPE Denotes whether measurements are phase to neutral(0) or phase to phase(1). | 1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.2 | INTEGER {phaseToNeutral(0), phaseToPhase(1)} | read-only | current |
| tlpPduInputPhaseFrequency OBJECT-TYPE The present input frequency for a given phase. | 1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.3 | Unsigned32 | read-only | current |
| tlpPduInputPhaseVoltage OBJECT-TYPE The magnitude of the present input voltage for a given phase. | 1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.4 | Unsigned32 | read-only | current |
| tlpPduInputPhaseVoltageMin OBJECT-TYPE The minimum input voltage value since the last reset of this value for a given phase. If any value is written to either tlpPduInputVoltageMin or tlpPduInputVoltageMax, both will be reset to their appropriate minimum and maximum values. | 1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.5 | Unsigned32 | read-write | current |
| tlpPduInputPhaseVoltageMax OBJECT-TYPE The maximum input voltage value since the last reset of this value for a given phase. If any value is written to either tlpPduInputVoltageMin or tlpPduInputVoltageMax, both will be reset to their appropriate minimum and maximum values. | 1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.6 | Unsigned32 | read-write | current |
| tlpPduInputPhaseCurrent OBJECT-TYPE The magnitude of the present input current for a given phase. | 1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.7 | Unsigned32 | read-only | current |
| tlpPduOutput OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.3.2 | |||
| tlpPduOutputTable OBJECT-TYPE The output details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpPduIdentNumOutputs per each device. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1 | not-accessible | current | |
| tlpPduOutputEntry OBJECT-TYPE An entry containing output information applicable to a particular phase managed by this agent. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1 | not-accessible | current | |
| tlpPduOutputIndex OBJECT-TYPE The table row index for the pdu phase. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.1 | Unsigned32 | read-only | current |
| tlpPduOutputPhase OBJECT-TYPE Indicates the phase associated with the output line. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.2 | INTEGER {phase1(1), phase2(2), phase3(3)} | read-only | current |
| tlpPduOutputPhaseType OBJECT-TYPE Denotes whether measurements are phase to neutral(0) or phase to phase(1). | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.3 | INTEGER {phaseToNeutral(0), phaseToPhase(1)} | read-only | current |
| tlpPduOutputVoltage OBJECT-TYPE The magnitude of the present output voltage for a given output line. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.4 | Unsigned32 | read-only | current |
| tlpPduOutputCurrent OBJECT-TYPE The output current, in hundredths of amps, for a given phase. The actual precision of this value, whether a whole number, tenths or hundredths, is returned by tlpPduDeviceOutputCurrentPrecision. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.5 | Unsigned32 | read-only | current |
| tlpPduOutputCurrentMin OBJECT-TYPE The minimum current, in hundredths of amps, observed for a given phase since last reset. The actual precision of this value, whether a whole number, tenths or hundredths, is returned by tlpPduDeviceOutputCurrentPrecision. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.6 | Unsigned32 | read-only | current |
| tlpPduOutputCurrentMax OBJECT-TYPE The maximum current, in hundredths of amps, observed for a given phase since last reset. The actual precision of this value, whether a whole number, tenths or hundredths, is returned by tlpPduDeviceOutputCurrentPrecision. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.7 | Unsigned32 | read-only | current |
| tlpPduOutputActivePower OBJECT-TYPE The output power for a given phase. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.8 | Unsigned32 | read-only | current |
| tlpPduOutputPowerFactor OBJECT-TYPE The output power factor, in hundredths of a percent, for a given phase. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.9 | Unsigned32 | read-only | current |
| tlpPduOutputSource OBJECT-TYPE The present source of output power. The enumeration none(0) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.10 | INTEGER {none(0), normal(1)} | read-only | current |
| tlpPduOutputFrequency OBJECT-TYPE The present output frequency. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.11 | Unsigned32 | read-only | current |
| tlpPduOutputCalculatedPowerKVA OBJECT-TYPE The calculated amount of apparent power being used. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.12 | Unsigned32 | read-only | current |
| tlpPduOutputCalculatedPowerKW OBJECT-TYPE The calculated amount of active power being used. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.13 | Unsigned32 | read-only | current |
| tlpPduOutputCalculated24hrEnergy OBJECT-TYPE Estimated 24 hour power consumption using present value of tlpPduOutputCalculatedPowerKW. | 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.14 | Unsigned32 | read-only | current |
| tlpPduOutlet OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.3.3 | |||
| tlpPduOutletTable OBJECT-TYPE The receptacle status details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpPduIdentNumOutlets per each device. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1 | not-accessible | current | |
| tlpPduOutletEntry OBJECT-TYPE An entry containing information applicable to a particular outlet managed by this agent. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1 | not-accessible | current | |
| tlpPduOutletIndex OBJECT-TYPE The table row index for the pdu outlet. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.1 | Unsigned32 | read-only | current |
| tlpPduOutletName OBJECT-TYPE A user-definable string identifying the name of the outlet. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.2 | DisplayString | read-write | current |
| tlpPduOutletDescription OBJECT-TYPE A user-definable string identifying the device(s) connected to the given outlet. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.3 | DisplayString | read-write | current |
| tlpPduOutletState OBJECT-TYPE The current state of the outlet. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.4 | INTEGER {unknown(0), off(1), on(2)} | read-only | current |
| tlpPduOutletControllable OBJECT-TYPE Denotes whether this outlet is controllable. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.5 | TruthValue | read-only | current |
| tlpPduOutletCommand OBJECT-TYPE Reading this value will always return 0. Setting this value to turnOff(1) will turn off the outlet. Setting this value to turnOn(2) will turn on the outlet. Setting this value to cycle(3) will turn the outlet off, then turn it back on. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.6 | INTEGER {idle(0), turnOff(1), turnOn(2), cycle(3)} | read-write | current |
| tlpPduOutletVoltage OBJECT-TYPE The magnitude of the present output voltage for a given outlet. If the voltage measurement is not supported for an individual receptacle regardless whether device-wide or just for this receptacle, then this value will always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle voltage measurements is denoted by tlpPduSupportsOutletVoltage. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.7 | Unsigned32 | read-only | current |
| tlpPduOutletCurrent OBJECT-TYPE The present output current, in hundredths of amps, of a given outlet. If the current measurement is not supported for an individual receptacle regardless whether device-wide or just for this receptacle, then this value will always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle current measurements is denoted by tlpPduSupportsCurrentPower. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.8 | Unsigned32 | read-only | current |
| tlpPduOutletPower OBJECT-TYPE The output power of a given outlet. If the power measurement is not supported for an individual receptacle regardless whether device-wide or just for this receptacle, then this value will always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle power measurements is denoted by tlpPduSupportsCurrentPower. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.9 | Unsigned32 | read-only | current |
| tlpPduOutletRampAction OBJECT-TYPE The ramp action to take on a given outlet when powering on the device. If this receptacle is not controllable, as denoted by tlpPduOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.10 | INTEGER {remainOff(0), turnOnAfterDelay(1)} | read-write | current |
| tlpPduOutletRampDelay OBJECT-TYPE The number of seconds to delay before powering on the given outlet. If this receptacle is not controllable, as denoted by tlpPduOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.11 | Integer32 | read-write | current |
| tlpPduOutletShedAction OBJECT-TYPE The shed action to take on a given outlet when powering off the device. If this receptacle is not controllable, as denoted by tlpPduOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.12 | INTEGER {remainOn(0), turnOffAfterDelay(1)} | read-write | current |
| tlpPduOutletShedDelay OBJECT-TYPE The number of seconds to delay before powering off the given outlet. If this receptacle is not controllable, as denoted by tlpPduOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.13 | Integer32 | read-write | current |
| tlpPduOutletGroup OBJECT-TYPE The tlpPduOutletGroupIndex group index of the respective group to which the given outlet is assigned, or zero (0) if the given outlet is not grouped. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.14 | Integer32 | read-write | current |
| tlpPduOutletBank OBJECT-TYPE Indicates on which bank the given outlet is located. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.15 | Integer32 | read-only | current |
| tlpPduOutletCircuit OBJECT-TYPE Indicates on which circuit the given outlet is wired. | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.16 | Integer32 | read-only | current |
| tlpPduOutletPhase OBJECT-TYPE Indicates on which phase or phases the given outlet is associated. For single phase devices, this object will always return phase1(1). For 3-phase devices with outlets wired to a single phase, this object will return phase1(1), phase2(2) or phase3(3). For 3-phase devices with outlets wired to two phases, this object will return phase1-2(4) for phases 1 and 2, phase2-3(5) for phases 2 and 3, and phase3-1(6) for phases 3 and 1. Devices that do not report phase connections will return unknown(0). | 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.17 | INTEGER {unknown(0), phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | current |
| tlpPduOutletGroupTable OBJECT-TYPE The receptacle grouping details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpPduIdentNumOutletGroups per each device. | 1.3.6.1.4.1.850.1.1.3.2.3.3.2 | not-accessible | current | |
| tlpPduOutletGroupEntry OBJECT-TYPE An entry containing information applicable to a particular outlet group managed by this agent. | 1.3.6.1.4.1.850.1.1.3.2.3.3.2.1 | not-accessible | current | |
| tlpPduOutletGroupIndex OBJECT-TYPE The table row index for the pdu outlet group. | 1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.1 | Unsigned32 | read-only | current |
| tlpPduOutletGroupRowStatus OBJECT-TYPE Row status for the tlpPduOutletGroupTable | 1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.2 | RowStatus | read-write | current |
| tlpPduOutletGroupName OBJECT-TYPE The name of this outlet group. | 1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.3 | DisplayString | read-write | current |
| tlpPduOutletGroupDescription OBJECT-TYPE A description for this outlet group. | 1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.4 | DisplayString | read-write | current |
| tlpPduOutletGroupState OBJECT-TYPE The current state of the outlet group. This value will report off(1) if all outlets in the group are off, on(2) if all outlets in the group are on, mixed(3) if some outlets in the group are off and others are on, or unknown(0) if the state of the outlets cannot be determined. | 1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.5 | INTEGER {unknown(0), off(1), on(2), mixed(3)} | read-only | current |
| tlpPduOutletGroupCommand OBJECT-TYPE Reading this value will always return 0. Setting this value to turnOff(1) will turn off every outlet associated with the group. Setting this value to turnOn(2) will turn on every outlet associated with the group. Setting this value to cycle(3) will turn off every outlet associated with the group, then turn each outlet back on. | 1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.6 | INTEGER {turnOff(1), turnOn(2), cycle(3)} | read-write | current |
| tlpPduCircuit OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.3.4 | |||
| tlpPduCircuitTable OBJECT-TYPE A list of pdu circuit table entries. The number of entries is given by the value of tlpPduIdentNumCircuits. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1 | not-accessible | current | |
| tlpPduCircuitEntry OBJECT-TYPE An entry containing information applicable to a particular circuit managed by this agent. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1 | not-accessible | current | |
| tlpPduCircuitIndex OBJECT-TYPE The table row index for the pdu circuit. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.1 | Unsigned32 | read-only | current |
| tlpPduCircuitPhase OBJECT-TYPE Indicates on which phase or phases the given circuit is wired. For single phase devices, this object will always return phase1(1). For 3-phase devices with outlets wired to a single phase, this object will return phase1(1), phase2(2) or phase3(3). For 3-phase devices with outlets wired to two phases, this object will return phase1-2(4) for phases 1 and 2, phase2-3(5) for phases 2 and 3, and phase3-1(6) for phases 3 and 1. Devices that do not report phase connections will return unknown(0). | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.2 | INTEGER {unknown(0), phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | current |
| tlpPduCircuitInputVoltage OBJECT-TYPE The input voltage for a circuit. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.3 | Integer32 | read-only | current |
| tlpPduCircuitTotalCurrent OBJECT-TYPE The total current, in hundredths of amps, for all receptacles in a given circuit. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.4 | Integer32 | read-only | current |
| tlpPduCircuitCurrentLimit OBJECT-TYPE The current capacity, in hundredths of amps, of a circuit in the system limited by the circuit breaker or wiring used in a given unit. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.5 | Integer32 | read-only | current |
| tlpPduCircuitCurrentMin OBJECT-TYPE The minimum total current, in hundredths of amps, for all receptacles in a given circuit since last reset. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.6 | Integer32 | read-only | current |
| tlpPduCircuitCurrentMax OBJECT-TYPE The maximum total current, in hundredths of amps, for all receptacles in a given circuit since last reset. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.7 | Integer32 | read-only | current |
| tlpPduCircuitTotalPower OBJECT-TYPE The total power for all receptacles in a given circuit. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.8 | Integer32 | read-only | current |
| tlpPduCircuitPowerFactor OBJECT-TYPE The power factor for all receptacles in a given circuit. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.9 | INTEGER (0..200) | read-only | current |
| tlpPduCircuitUtilization OBJECT-TYPE The percentage of utilization of a given circuit. This is typically a calculation of tlpPduCircuitTotalCurrent / tlpPduCircuitCurrentLimit. | 1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.10 | Unsigned32 | read-only | current |
| tlpPduBreaker OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.3.5 | |||
| tlpPduBreakerTable OBJECT-TYPE A list of pdu bank breaker table entries. The number of entries is given by the value of tlpPduIdentNumBreakers. | 1.3.6.1.4.1.850.1.1.3.2.3.5.1 | not-accessible | current | |
| tlpPduBreakerEntry OBJECT-TYPE An entry containing information applicable to a particular bank breaker managed by this agent. | 1.3.6.1.4.1.850.1.1.3.2.3.5.1.1 | not-accessible | current | |
| tlpPduBreakerIndex OBJECT-TYPE The table row index for the pdu bank breaker. | 1.3.6.1.4.1.850.1.1.3.2.3.5.1.1.1 | Unsigned32 | read-only | current |
| tlpPduBreakerStatus OBJECT-TYPE Indicates whether the bank breaker is open(0), closed(1) or not installed(2). | 1.3.6.1.4.1.850.1.1.3.2.3.5.1.1.2 | INTEGER {open(0), closed(1), notInstalled(2)} | read-only | current |
| tlpPduHeatsink OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.3.6 | |||
| tlpPduHeatsinkTable OBJECT-TYPE A list of pdu heatsink thermistor table entries. The number of entries is given by the value of tlpPduIdentNumHeatsinks. | 1.3.6.1.4.1.850.1.1.3.2.3.6.1 | not-accessible | current | |
| tlpPduHeatsinkEntry OBJECT-TYPE An entry containing information applicable to a particular heatsink thermistor managed by this agent. | 1.3.6.1.4.1.850.1.1.3.2.3.6.1.1 | not-accessible | current | |
| tlpPduHeatsinkIndex OBJECT-TYPE The table row index for the pdu heatsink thermistor. | 1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.1 | Unsigned32 | read-only | current |
| tlpPduHeatsinkStatus OBJECT-TYPE Indicates whether the heatsink thermistor is available. The entry will return notAvailable(0) if a thermistor is either non-existent or disconnected, or available(1) when connected. | 1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.2 | INTEGER {notAvailable(0), available(1)} | read-only | current |
| tlpPduHeatsinkTemperatureC OBJECT-TYPE The temperature at the heatsink thermistor in tenths degrees Celsius. Heatsink temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.3 | Integer32 | read-only | current |
| tlpPduHeatsinkTemperatureF OBJECT-TYPE The temperature at the heatsink thermistor in tenths degrees Fahrenheit. Heatsink temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.4 | Integer32 | read-only | current |
| tlpPduControl OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.4 | |||
| tlpPduControlTable OBJECT-TYPE The actionable controls for each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus. | 1.3.6.1.4.1.850.1.1.3.2.4.1 | not-accessible | current | |
| tlpPduControlEntry OBJECT-TYPE An entry containing controls for a particular pdu. | 1.3.6.1.4.1.850.1.1.3.2.4.1.1 | not-accessible | current | |
| tlpPduControlRamp OBJECT-TYPE Set to TRUE to initiate the pre-designated ramp sequence on the pdu. | 1.3.6.1.4.1.850.1.1.3.2.4.1.1.1 | TruthValue | read-write | current |
| tlpPduControlShed OBJECT-TYPE Set to TRUE to initiate the pre-designated shed sequence on the pdu. | 1.3.6.1.4.1.850.1.1.3.2.4.1.1.2 | TruthValue | read-write | current |
| tlpPduControlPduOn OBJECT-TYPE Set to TRUE to turn the pdu on. | 1.3.6.1.4.1.850.1.1.3.2.4.1.1.3 | TruthValue | read-write | current |
| tlpPduControlPduOff OBJECT-TYPE Set to TRUE to turn the pdu off. | 1.3.6.1.4.1.850.1.1.3.2.4.1.1.4 | TruthValue | read-write | current |
| tlpPduControlPduReboot OBJECT-TYPE Set to TRUE to reboot the pdu. | 1.3.6.1.4.1.850.1.1.3.2.4.1.1.5 | TruthValue | read-write | current |
| tlpPduConfig OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.2.5 | |||
| tlpPduConfigTable OBJECT-TYPE The configuration options of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus. Not all options are available on all pdus. | 1.3.6.1.4.1.850.1.1.3.2.5.1 | not-accessible | current | |
| tlpPduConfigEntry OBJECT-TYPE An entry containing configuration options for a particular pdu. | 1.3.6.1.4.1.850.1.1.3.2.5.1.1 | not-accessible | current | |
| tlpPduConfigInputVoltage OBJECT-TYPE The nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. This value may not be writable on all models. If not writable, the value will be rejected and an appropriate error message will be returned. | 1.3.6.1.4.1.850.1.1.3.2.5.1.1.1 | Unsigned32 | read-write | current |
| tlpPduConfigPhaseThresholdTable OBJECT-TYPE The configuration options of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus. Not all options are available on all pdus. | 1.3.6.1.4.1.850.1.1.3.2.5.2 | not-accessible | current | |
| tlpPduConfigPhaseThresholdEntry OBJECT-TYPE An entry containing threshold configuration options for a particular pdu. | 1.3.6.1.4.1.850.1.1.3.2.5.2.1 | not-accessible | current | |
| tlpPduPhaseIndex OBJECT-TYPE The table row index for the pdu phase. | 1.3.6.1.4.1.850.1.1.3.2.5.2.1.1 | Unsigned32 | read-only | current |
| tlpPduConfigOutputCurrentThresholdTolerance OBJECT-TYPE The threshold tolerance value used together with output current high/low threshold to evaluate output current high/low condition. | 1.3.6.1.4.1.850.1.1.3.2.5.2.1.2 | Unsigned32 | read-write | current |
| tlpPduConfigOutputCurrentHighThreshold OBJECT-TYPE The value at which a output current high condition is declared. | 1.3.6.1.4.1.850.1.1.3.2.5.2.1.3 | Unsigned32 | read-write | current |
| tlpPduConfigOutputCurrentLowThreshold OBJECT-TYPE The value at which a output current low condition is declared. | 1.3.6.1.4.1.850.1.1.3.2.5.2.1.4 | Unsigned32 | read-write | current |
| tlpEnvirosense OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.3 | |||
| tlpEnvIdent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.3.1 | |||
| tlpEnvIdentNumEnvirosense OBJECT-TYPE The number of envirosense devices that this agent is currently managing. | 1.3.6.1.4.1.850.1.1.3.3.1.1 | Unsigned32 | read-only | current |
| tlpEnvIdentTable OBJECT-TYPE The identity details of each envirosense in device table. This is a sparse dependent table, and will contain some subset of devices that are envirosenses. | 1.3.6.1.4.1.850.1.1.3.3.1.2 | not-accessible | current | |
| tlpEnvIdentEntry OBJECT-TYPE An entry containing details for a particular envirosense. | 1.3.6.1.4.1.850.1.1.3.3.1.2.1 | not-accessible | current | |
| tlpEnvIdentTempSupported OBJECT-TYPE Indicates whether or not temperature is supported. | 1.3.6.1.4.1.850.1.1.3.3.1.2.1.1 | TruthValue | read-only | current |
| tlpEnvIdentHumiditySupported OBJECT-TYPE Indicates whether or not temperature is supported. | 1.3.6.1.4.1.850.1.1.3.3.1.2.1.2 | TruthValue | read-only | current |
| tlpEnvNumInputContacts OBJECT-TYPE The number of input contacts supported by the envirosense. | 1.3.6.1.4.1.850.1.1.3.3.1.2.1.3 | Unsigned32 | read-only | current |
| tlpEnvNumOutputContacts OBJECT-TYPE The number of output contacts supported by the envirosense. | 1.3.6.1.4.1.850.1.1.3.3.1.2.1.4 | Unsigned32 | read-only | current |
| tlpEnvDetail OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.3.3 | |||
| tlpEnvTemperatureTable OBJECT-TYPE The temperature details of each envirosense in device table. The number of entries is given by the value of tlpDevicesNumDevices. | 1.3.6.1.4.1.850.1.1.3.3.3.1 | not-accessible | current | |
| tlpEnvTemperatureEntry OBJECT-TYPE An entry containing temperature details for a particular envirosense. | 1.3.6.1.4.1.850.1.1.3.3.3.1.1 | not-accessible | current | |
| tlpEnvTemperatureC OBJECT-TYPE The ambient temperature. | 1.3.6.1.4.1.850.1.1.3.3.3.1.1.1 | Integer32 | read-only | current |
| tlpEnvTemperatureF OBJECT-TYPE The ambient temperature. | 1.3.6.1.4.1.850.1.1.3.3.3.1.1.2 | Integer32 | read-only | current |
| tlpEnvTemperatureInAlarm OBJECT-TYPE Indicates whether or not temperature is in alarm. | 1.3.6.1.4.1.850.1.1.3.3.3.1.1.3 | TruthValue | read-only | current |
| tlpEnvHumidityTable OBJECT-TYPE The humidity details of each envirosense in device table. The number of entries is given by the value of tlpDevicesNumDevices. | 1.3.6.1.4.1.850.1.1.3.3.3.2 | not-accessible | current | |
| tlpEnvHumidityEntry OBJECT-TYPE An entry containing humidity details for a particular envirosense. | 1.3.6.1.4.1.850.1.1.3.3.3.2.1 | not-accessible | current | |
| tlpEnvHumidityHumidity OBJECT-TYPE The ambient humidity. | 1.3.6.1.4.1.850.1.1.3.3.3.2.1.1 | INTEGER (0..100) | read-only | current |
| tlpEnvHumidityInAlarm OBJECT-TYPE Indicates whether or not humidity is in alarm. | 1.3.6.1.4.1.850.1.1.3.3.3.2.1.2 | TruthValue | read-only | current |
| tlpEnvInputContactTable OBJECT-TYPE The input contact details of each envirosense in device table. The number of entries is given by the value of tlpDevicesNumDevices. | 1.3.6.1.4.1.850.1.1.3.3.3.3 | not-accessible | current | |
| tlpEnvInputContactEntry OBJECT-TYPE An entry containing input contact details for a particular envirosense. | 1.3.6.1.4.1.850.1.1.3.3.3.3.1 | not-accessible | current | |
| tlpEnvInputContactIndex OBJECT-TYPE The table row index for the envirosense input contact details. | 1.3.6.1.4.1.850.1.1.3.3.3.3.1.1 | Unsigned32 | read-only | current |
| tlpEnvInputContactName OBJECT-TYPE The name or description of the contact. | 1.3.6.1.4.1.850.1.1.3.3.3.3.1.2 | DisplayString | read-write | current |
| tlpEnvInputContactNormalState OBJECT-TYPE The normal operating position of the contact. | 1.3.6.1.4.1.850.1.1.3.3.3.3.1.3 | INTEGER {open(0), closed(1)} | read-write | current |
| tlpEnvInputContactCurrentState OBJECT-TYPE The current state of the contact. | 1.3.6.1.4.1.850.1.1.3.3.3.3.1.4 | INTEGER {open(0), closed(1)} | read-only | current |
| tlpEnvInputContactInAlarm OBJECT-TYPE Indicates whether or not the contact is in alarm. | 1.3.6.1.4.1.850.1.1.3.3.3.3.1.5 | TruthValue | read-only | current |
| tlpEnvOutputContactTable OBJECT-TYPE The output contact details of each envirosense in device table. The number of entries is given by the value of tlpDevicesNumDevices. | 1.3.6.1.4.1.850.1.1.3.3.3.4 | not-accessible | current | |
| tlpEnvOutputContactEntry OBJECT-TYPE An entry containing output contact details for a particular envirosense. | 1.3.6.1.4.1.850.1.1.3.3.3.4.1 | not-accessible | current | |
| tlpEnvOutputContactIndex OBJECT-TYPE The table row index for the envirosense output contact details. | 1.3.6.1.4.1.850.1.1.3.3.3.4.1.1 | Unsigned32 | read-only | current |
| tlpEnvOutputContactName OBJECT-TYPE The name or description of the contact. | 1.3.6.1.4.1.850.1.1.3.3.3.4.1.2 | DisplayString | read-write | current |
| tlpEnvOutputContactNormalState OBJECT-TYPE The normal operating position of the contact. | 1.3.6.1.4.1.850.1.1.3.3.3.4.1.3 | INTEGER {open(0), closed(1)} | read-write | current |
| tlpEnvOutputContactCurrentState OBJECT-TYPE The current state of the contact. | 1.3.6.1.4.1.850.1.1.3.3.3.4.1.4 | INTEGER {open(0), closed(1)} | read-write | current |
| tlpEnvOutputContactInAlarm OBJECT-TYPE Indicates whether or not the contact is in alarm. | 1.3.6.1.4.1.850.1.1.3.3.3.4.1.5 | TruthValue | read-only | current |
| tlpEnvConfig OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.3.5 | |||
| tlpEnvConfigTable OBJECT-TYPE The configuration options of each envirosense in device table. This is a sparse dependent table, and will contain some subset of devices that are envirosenses. Not all options are available on all envirosenses. | 1.3.6.1.4.1.850.1.1.3.3.5.1 | not-accessible | current | |
| tlpEnvConfigEntry OBJECT-TYPE An entry containing configuration options for a particular envirosenses. | 1.3.6.1.4.1.850.1.1.3.3.5.1.1 | not-accessible | current | |
| tlpEnvTemperatureLowLimit OBJECT-TYPE The lower alarm limit for ambient temperature. | 1.3.6.1.4.1.850.1.1.3.3.5.1.1.1 | Integer32 | read-write | current |
| tlpEnvTemperatureHighLimit OBJECT-TYPE The upper alarm limit for ambient temperature. | 1.3.6.1.4.1.850.1.1.3.3.5.1.1.2 | Integer32 | read-write | current |
| tlpEnvHumidityLowLimit OBJECT-TYPE The lower alarm limit for ambient humidity. | 1.3.6.1.4.1.850.1.1.3.3.5.1.1.3 | INTEGER (0..100) | read-write | current |
| tlpEnvHumidityHighLimit OBJECT-TYPE The upper alarm limit for ambient humidity. | 1.3.6.1.4.1.850.1.1.3.3.5.1.1.4 | INTEGER (0..100) | read-write | current |
| tlpAts OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4 | |||
| tlpAtsIdent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.1 | |||
| tlpAtsIdentNumAts OBJECT-TYPE The number of ats devices that this agent is currently managing. | 1.3.6.1.4.1.850.1.1.3.4.1.1 | Unsigned32 | read-only | current |
| tlpAtsIdentTable OBJECT-TYPE The identity details of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss. | 1.3.6.1.4.1.850.1.1.3.4.1.2 | not-accessible | current | |
| tlpAtsIdentEntry OBJECT-TYPE An entry containing details for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.1.2.1 | not-accessible | current | |
| tlpAtsIdentNumInputs OBJECT-TYPE The number of inputs supported by the ats. | 1.3.6.1.4.1.850.1.1.3.4.1.2.1.1 | Unsigned32 | read-only | current |
| tlpAtsIdentNumOutputs OBJECT-TYPE The number of outputs supported by the ats. | 1.3.6.1.4.1.850.1.1.3.4.1.2.1.2 | Unsigned32 | read-only | current |
| tlpAtsIdentNumPhases OBJECT-TYPE The number of phases per input supported by the ats. | 1.3.6.1.4.1.850.1.1.3.4.1.2.1.3 | Unsigned32 | read-only | current |
| tlpAtsIdentNumOutlets OBJECT-TYPE The number of receptacles supported by the ats. | 1.3.6.1.4.1.850.1.1.3.4.1.2.1.4 | Unsigned32 | read-only | current |
| tlpAtsIdentNumOutletGroups OBJECT-TYPE The number of receptacle groups supported by the ats. | 1.3.6.1.4.1.850.1.1.3.4.1.2.1.5 | Unsigned32 | read-only | current |
| tlpAtsIdentNumCircuits OBJECT-TYPE The number of circuits supported by the ats. | 1.3.6.1.4.1.850.1.1.3.4.1.2.1.6 | Unsigned32 | read-only | current |
| tlpAtsIdentNumBreakers OBJECT-TYPE The number of monitored bank breakers supported by the ats. If the ats has breakers that are not monitored by the device, the value of zero(0) will be returned. | 1.3.6.1.4.1.850.1.1.3.4.1.2.1.7 | Unsigned32 | read-only | current |
| tlpAtsIdentNumHeatsinks OBJECT-TYPE The number of heatsink thermistors supported by the ats. | 1.3.6.1.4.1.850.1.1.3.4.1.2.1.8 | Unsigned32 | read-only | current |
| tlpAtsSupportsTable OBJECT-TYPE The supported details of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss. | 1.3.6.1.4.1.850.1.1.3.4.1.3 | not-accessible | current | |
| tlpAtsSupportsEntry OBJECT-TYPE An entry containing supported details for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.1.3.1 | not-accessible | current | |
| tlpAtsSupportsEnergywise OBJECT-TYPE Indicates whether the ats supports Cisco EnergyWise. | 1.3.6.1.4.1.850.1.1.3.4.1.3.1.1 | TruthValue | read-only | current |
| tlpAtsSupportsRampShed OBJECT-TYPE Indicates whether the ats supports ramping and shedding. | 1.3.6.1.4.1.850.1.1.3.4.1.3.1.2 | TruthValue | read-only | current |
| tlpAtsSupportsOutletGroup OBJECT-TYPE Indicates whether the ats supports outlet groups. | 1.3.6.1.4.1.850.1.1.3.4.1.3.1.3 | TruthValue | read-only | current |
| tlpAtsSupportsOutletCurrentPower OBJECT-TYPE Indicates whether the ats reports individual receptacle current and power measurements. Devices that do not support individual receptacle measurements will always return ERROR_NO_SUCH_NAME for tlpAtsOutletCurrent and tlpAtsOutletPower. | 1.3.6.1.4.1.850.1.1.3.4.1.3.1.4 | TruthValue | read-only | current |
| tlpAtsSupportsOutletVoltage OBJECT-TYPE Indicates whether the ats reports individual receptacle voltage measurements. Devices that do not support individual receptacle measurements will always return ERROR_NO_SUCH_NAME for tlpAtsOutletVoltage. | 1.3.6.1.4.1.850.1.1.3.4.1.3.1.5 | TruthValue | read-only | current |
| tlpAtsDisplayTable OBJECT-TYPE The display details of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss. | 1.3.6.1.4.1.850.1.1.3.4.1.4 | not-accessible | current | |
| tlpAtsDisplayEntry OBJECT-TYPE An entry containing display details for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.1.4.1 | not-accessible | current | |
| tlpAtsDisplayScheme OBJECT-TYPE Indicates the display scheme of the LED display. The value schemeReverse(0) indicates the tricolor LED indicator uses an alternate pattern. The value schemeNormal(1) indicates the LED indicator uses the standard pattern. This value may not be supported on all models. If not supported, the value will always return schemeNormal(1). | 1.3.6.1.4.1.850.1.1.3.4.1.4.1.1 | INTEGER {schemeReverse(0), schemeNormal(1)} | read-write | current |
| tlpAtsDisplayOrientation OBJECT-TYPE Indicates the physical orientation of the LED display. The value displayNormal(0) indicates the display is right-side-up (normal). The value displayReverse(1) indicates the display is upside-down. This value may not be supported on all models. If not supported, the value will always return displayNormal(0). | 1.3.6.1.4.1.850.1.1.3.4.1.4.1.2 | INTEGER {displayNormal(0), displayReverse(1)} | read-write | current |
| tlpAtsDisplayAutoScroll OBJECT-TYPE Indicates whether the LED display automatically scrolls through displaying status values. | 1.3.6.1.4.1.850.1.1.3.4.1.4.1.3 | INTEGER {scrollDisabled(0), scrollEnabled(1)} | read-write | current |
| tlpAtsDisplayIntensity OBJECT-TYPE Indicates the intensity, as a percentage, of the LED display. The value intensity100(4) indicates the display is at 100% intensity. The other values indicate the display is at a lesser intensity based upon the respective percentage denoted. | 1.3.6.1.4.1.850.1.1.3.4.1.4.1.4 | INTEGER {intensity25(1), intensity50(2), intensity75(3), intensity100(4)} | read-write | current |
| tlpAtsDisplayUnits OBJECT-TYPE Indicates the units of measurement displayed on the LED display. The value normal(0) indicates that a temperature value, for example, is displayed in degrees Fahrenheit. The value metric(1) indicates a temperature value is displayed in degrees Celsius. | 1.3.6.1.4.1.850.1.1.3.4.1.4.1.5 | INTEGER {normal(0), metric(1)} | read-write | current |
| tlpAtsDevice OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.2 | |||
| tlpAtsDeviceTable OBJECT-TYPE The device details of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss. | 1.3.6.1.4.1.850.1.1.3.4.2.1 | not-accessible | current | |
| tlpAtsDeviceEntry OBJECT-TYPE An entry containing device details for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1 | not-accessible | current | |
| tlpAtsDeviceMainLoadState OBJECT-TYPE The current state of the main output of the device. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.1 | INTEGER {unknown(0), off(1), on(2)} | read-only | current |
| tlpAtsDeviceMainLoadControllable OBJECT-TYPE Indicates whether or not the main output is controllable, and whether the ups can be turned off and on. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.2 | TruthValue | read-only | current |
| tlpAtsDeviceMainLoadCommand OBJECT-TYPE Reading this value will always return 0. Setting this value to turnOff(1) will turn off the main output of the ups. Setting this value to turnOn(2) will turn on the main output of the ups. Setting this value to cycle(3) will turn off the main output, then turn it back on. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.3 | INTEGER {idle(0), turnOff(1), turnOn(2), cycle(3)} | read-write | current |
| tlpAtsDevicePowerOnDelay OBJECT-TYPE The configurable delay value, which sets the amount of additional time a given device will wait before it connects to a valid AC source. By default the delay value is set to 0. For devices with multiple AC input sources, this delay only applies to the primary input source. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.4 | Integer32 | read-write | current |
| tlpAtsDeviceTotalInputPowerRating OBJECT-TYPE The total input power rating of all phases on the device. This value may not be supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.5 | Integer32 | read-only | current |
| tlpAtsDeviceTemperatureC OBJECT-TYPE The ambient temperature at or near the ats casing. Temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.6 | Integer32 | read-only | current |
| tlpAtsDeviceTemperatureF OBJECT-TYPE The ambient temperature at or near the ats casing. Temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.7 | Integer32 | read-only | current |
| tlpAtsDevicePhaseImbalance OBJECT-TYPE The percentage of imbalance of the three phases. This value is in the range from 0% imbalance to 100% imbalance. The lower the value, the better balanced the phases are. If all load is on a single phase, the imbalance is defined as 100%. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.8 | INTEGER (0..200) | read-only | current |
| tlpAtsDeviceOutputPowerTotal OBJECT-TYPE The AC output total power for all circuits. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.9 | Unsigned32 | read-only | current |
| tlpAtsDeviceAggregatePowerFactor OBJECT-TYPE The aggregate power factor of all phases. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.10 | Unsigned32 | read-only | current |
| tlpAtsDeviceOutputCurrentPrecision OBJECT-TYPE Output current is reported by tlpAtsOutputCurrent, tlpAtsOutputCurrentMin and tlpAtsOutputCurrentMax. These values are all reported in hundredths (0.01A), which accommodates all models; however, on any given device the actual precision may vary. This value describes the actual precision, which can be used as a divisor against the output current values to obtain the true output current measurement. For example, if tlpAtsOutputCurrent reports 530 and tlpAtsDeviceOutputCurrentPrecision is tenths(1), then the actual output current is 5.3. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.11 | INTEGER {none(0), tenths(1), hundredths(2)} | read-only | current |
| tlpAtsDeviceGeneralFault OBJECT-TYPE Indicates whether or not the ats is in a system fault condition. When the ats is in such a fault condition, the condition can be cleared with tlpAtsControlResetGeneralFault. | 1.3.6.1.4.1.850.1.1.3.4.2.1.1.12 | TruthValue | read-only | current |
| tlpAtsDetail OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.3 | |||
| tlpAtsInput OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.3.1 | |||
| tlpAtsInputTable OBJECT-TYPE The input details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of atss managed by the agent as reported by tlpAtsIdentNumAts. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1 | not-accessible | current | |
| tlpAtsInputEntry OBJECT-TYPE An entry containing information applicable to a particular primary input phase managed by this agent. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1 | not-accessible | current | |
| tlpAtsInputNominalVoltage OBJECT-TYPE The nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.1 | Unsigned32 | read-only | current |
| tlpAtsInputNominalVoltagePhaseToPhase OBJECT-TYPE The nominal value of the input line voltage as measured from phase to phase. This value may not be supported on all models. If not supported, this value will always return zero. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.2 | Unsigned32 | read-only | current |
| tlpAtsInputNominalVoltagePhaseToNeutral OBJECT-TYPE The nominal value of the input line voltage as measured from phase to neutral. This value may not be supported on all models. If not supported, this value will always return zero. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.3 | Unsigned32 | read-only | current |
| tlpAtsInputBadTransferVoltage OBJECT-TYPE The minimum line voltage allowed before the unit disconnects the AC input connection. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.4 | Unsigned32 | read-only | current |
| tlpAtsInputBadTransferVoltageLowerBound OBJECT-TYPE The lower boundary value of tlpAtsInputBadTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.5 | Unsigned32 | read-only | current |
| tlpAtsInputBadTransferVoltageUpperBound OBJECT-TYPE The upper boundary value of tlpAtsInputBadTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.6 | Unsigned32 | read-only | current |
| tlpAtsInputHighTransferVoltage OBJECT-TYPE The maximum line voltage allowed before the unit disconnects the AC input connection. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.7 | Unsigned32 | read-only | current |
| tlpAtsInputHighTransferVoltageLowerBound OBJECT-TYPE The lower boundary value of tlpAtsInputHighTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.8 | Unsigned32 | read-only | current |
| tlpAtsInputHighTransferVoltageUpperBound OBJECT-TYPE The upper boundary value of tlpAtsInputHighTransferVoltage as dictated by the hardware of the unit. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.9 | Unsigned32 | read-only | current |
| tlpAtsInputFairVoltageThreshold OBJECT-TYPE The voltage level at which the device will transition between sources. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.10 | Unsigned32 | read-only | current |
| tlpAtsInputBadVoltageThreshold OBJECT-TYPE The minimum line voltage allowed before the device disconnects the AC input connection. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.11 | Unsigned32 | read-only | current |
| tlpAtsInputSourceAvailability OBJECT-TYPE The determination as to which of two AC input lines are available. The agent will return either inputSourceA(1) or inputSourceB(2) if only one line is available, or inputSourceAB(3) if both lines are available. The agent will never return none(0) since the device will be powered off if neither line is available. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.12 | INTEGER {none(0), inputSourceA(1), inputSourceB(2), inputSourceAB(3)} | read-only | current |
| tlpAtsInputSourceInUse OBJECT-TYPE The determination as to which one of two AC input lines is in use. Not all devices support the reporting of which source is currently in use. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.13 | INTEGER {inputSourceA(0), inputSourceB(1)} | read-only | current |
| tlpAtsInputSourceTransitionCount OBJECT-TYPE The number of times the device transitions between primary and secondary sources. Most devices are limited to 65533 transitions, after which the value will not increment. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.14 | Unsigned32 | read-only | current |
| tlpAtsInputCurrentLimit OBJECT-TYPE The capacity of each phase conductor in the ats limited by the AC input cord or any other potential limiting factors unique to a given unit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.15 | Unsigned32 | read-only | current |
| tlpAtsInputPhaseTable OBJECT-TYPE The input phase details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpAtsIdentNumInputs and tlpAtsIdentNumPhases per each device. | 1.3.6.1.4.1.850.1.1.3.4.3.1.2 | not-accessible | current | |
| tlpAtsInputPhaseEntry OBJECT-TYPE An entry containing information applicable to a particular primary input phase managed by this agent. | 1.3.6.1.4.1.850.1.1.3.4.3.1.2.1 | not-accessible | current | |
| tlpAtsInputLineIndex OBJECT-TYPE The table row index for the input line on the ats. | 1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.1 | Unsigned32 | read-only | current |
| tlpAtsInputPhaseIndex OBJECT-TYPE The table row index for the input phase for the input line. | 1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.2 | Unsigned32 | read-only | current |
| tlpAtsInputPhaseType OBJECT-TYPE Denotes whether measurements are phase to neutral(0) or phase to phase(1). | 1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.3 | INTEGER {phaseToNeutral(0), phaseToPhase(1)} | read-only | current |
| tlpAtsInputPhaseFrequency OBJECT-TYPE The present input frequency for a given phase. | 1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.4 | Unsigned32 | read-only | current |
| tlpAtsInputPhaseVoltage OBJECT-TYPE The magnitude of the present input voltage for a given phase. | 1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.5 | Unsigned32 | read-only | current |
| tlpAtsInputPhaseVoltageMin OBJECT-TYPE The minimum input voltage value since the last reset of this value for a given phase. If any value is written to either tlpAtsInputVoltageMin or tlpAtsInputVoltageMax, both will be reset to their appropriate minimum and maximum values. | 1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.6 | Unsigned32 | read-write | current |
| tlpAtsInputPhaseVoltageMax OBJECT-TYPE The maximum input voltage value since the last reset of this value for a given phase. If any value is written to either tlpAtsInputVoltageMin or tlpAtsInputVoltageMax, both will be reset to their appropriate minimum and maximum values. | 1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.7 | Unsigned32 | read-write | current |
| tlpAtsInputPhaseCurrent OBJECT-TYPE The magnitude of the present input current for a given phase. | 1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.8 | Unsigned32 | read-only | current |
| tlpAtsOutput OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.3.2 | |||
| tlpAtsOutputTable OBJECT-TYPE The output details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpAtsIdentNumOutputs per each device. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1 | not-accessible | current | |
| tlpAtsOutputEntry OBJECT-TYPE An entry containing output information applicable to a particular phase managed by this agent. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1 | not-accessible | current | |
| tlpAtsOutputIndex OBJECT-TYPE The table row index for the ats phase. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.1 | Unsigned32 | read-only | current |
| tlpAtsOutputPhase OBJECT-TYPE Indicates the phase associated with the output line. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.2 | INTEGER {phase1(1), phase2(2), phase3(3)} | read-only | current |
| tlpAtsOutputPhaseType OBJECT-TYPE Denotes whether measurements are phase to neutral(0) or phase to phase(1). | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.3 | INTEGER {phaseToNeutral(0), phaseToPhase(1)} | read-only | current |
| tlpAtsOutputVoltage OBJECT-TYPE The magnitude of the present output voltage for a given output line. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.4 | Unsigned32 | read-only | current |
| tlpAtsOutputCurrent OBJECT-TYPE The output current, in hundredths of amps, for a given phase. The actual precision of this value, whether a whole number, tenths or hundredths, is returned by tlpAtsDeviceOutputCurrentPrecision. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.5 | Unsigned32 | read-only | current |
| tlpAtsOutputCurrentMin OBJECT-TYPE The minimum current, in hundredths of amps, observed for a given phase since last reset. The actual precision of this value, whether a whole number, tenths or hundredths, is returned by tlpAtsDeviceOutputCurrentPrecision. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.6 | Unsigned32 | read-only | current |
| tlpAtsOutputCurrentMax OBJECT-TYPE The maximum current, in hundredths of amps, observed for a given phase since last reset. The actual precision of this value, whether a whole number, tenths or hundredths, is returned by tlpAtsDeviceOutputCurrentPrecision. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.7 | Unsigned32 | read-only | current |
| tlpAtsOutputActivePower OBJECT-TYPE The output power for a given phase. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.8 | Unsigned32 | read-only | current |
| tlpAtsOutputPowerFactor OBJECT-TYPE The output power factor, in hundredths of a percent, for a given phase. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.9 | Unsigned32 | read-only | current |
| tlpAtsOutputSource OBJECT-TYPE The present source of output power. The enumeration none(0) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.10 | INTEGER {none(0), normal(1)} | read-only | current |
| tlpAtsOutputFrequency OBJECT-TYPE The present output frequency. If not supported, the agent reports ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.11 | Unsigned32 | read-only | current |
| tlpAtsOutputCalculatedPowerKVA OBJECT-TYPE The calculated amount of apparent power being used. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.12 | Unsigned32 | read-only | current |
| tlpAtsOutputCalculatedPowerKW OBJECT-TYPE The calculated amount of active power being used. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.13 | Unsigned32 | read-only | current |
| tlpAtsOutputCalculated24hrEnergy OBJECT-TYPE Estimated 24 hour power consumption using present value of tlpAtsOutputCalculatedPowerKW. | 1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.14 | Unsigned32 | read-only | current |
| tlpAtsOutlet OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.3.3 | |||
| tlpAtsOutletTable OBJECT-TYPE The receptacle status details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpAtsIdentNumOutlets per each device. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1 | not-accessible | current | |
| tlpAtsOutletEntry OBJECT-TYPE An entry containing information applicable to a particular outlet managed by this agent. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1 | not-accessible | current | |
| tlpAtsOutletIndex OBJECT-TYPE The table row index for the ats outlet. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.1 | Unsigned32 | read-only | current |
| tlpAtsOutletName OBJECT-TYPE A user-definable string identifying the name of the outlet. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.2 | DisplayString | read-write | current |
| tlpAtsOutletDescription OBJECT-TYPE A user-definable string identifying the device(s) connected to the given outlet. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.3 | DisplayString | read-write | current |
| tlpAtsOutletState OBJECT-TYPE The current state of the outlet. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.4 | INTEGER {unknown(0), off(1), on(2)} | read-only | current |
| tlpAtsOutletControllable OBJECT-TYPE Denotes whether this outlet is controllable. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.5 | TruthValue | read-only | current |
| tlpAtsOutletCommand OBJECT-TYPE Reading this value will always return 0. Setting this value to turnOff(1) will turn off the outlet. Setting this value to turnOn(2) will turn on the outlet. Setting this value to cycle(3) will turn the outlet off, then turn it back on. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.6 | INTEGER {idle(0), turnOff(1), turnOn(2), cycle(3)} | read-write | current |
| tlpAtsOutletVoltage OBJECT-TYPE The magnitude of the present output voltage for a given outlet. If the voltage measurement is not supported for an individual receptacle regardless whether device-wide or just for this receptacle, then this value will always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle voltage measurements is denoted by tlpAtsSupportsOutletVoltage. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.7 | Unsigned32 | read-only | current |
| tlpAtsOutletCurrent OBJECT-TYPE The present output current, in hundredths of amps, of a given outlet. If the current measurement is not supported for an individual receptacle regardless whether device-wide or just for this receptacle, then this value will always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle current measurements is denoted by tlpAtsSupportsCurrentPower. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.8 | Unsigned32 | read-only | current |
| tlpAtsOutletPower OBJECT-TYPE The output power of a given outlet. If the power measurement is not supported for an individual receptacle regardless whether device-wide or just for this receptacle, then this value will always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle power measurements is denoted by tlpAtsSupportsCurrentPower. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.9 | Unsigned32 | read-only | current |
| tlpAtsOutletRampAction OBJECT-TYPE The ramp action to take on a given outlet when powering on the device. If this receptacle is not controllable, as denoted by tlpAtsOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.10 | INTEGER {remainOff(0), turnOnAfterDelay(1)} | read-write | current |
| tlpAtsOutletRampDelay OBJECT-TYPE The number of seconds to delay before powering on the given outlet. If this receptacle is not controllable, as denoted by tlpAtsOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.11 | Integer32 | read-write | current |
| tlpAtsOutletShedAction OBJECT-TYPE The shed action to take on a given outlet when powering off the device. If this receptacle is not controllable, as denoted by tlpAtsOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.12 | INTEGER {remainOn(0), turnOffAfterDelay(1)} | read-write | current |
| tlpAtsOutletShedDelay OBJECT-TYPE The number of seconds to delay before powering off the given outlet. If this receptacle is not controllable, as denoted by tlpAtsOutletControllable, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.13 | Integer32 | read-write | current |
| tlpAtsOutletGroup OBJECT-TYPE The tlpAtsOutletGroupIndex group index of the respective group to which the given outlet is assigned, or zero (0) if the given outlet is not grouped. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.14 | Integer32 | read-write | current |
| tlpAtsOutletBank OBJECT-TYPE Indicates on which bank the given outlet is located. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.15 | Integer32 | read-only | current |
| tlpAtsOutletCircuit OBJECT-TYPE Indicates on which circuit the given outlet is wired. | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.16 | Integer32 | read-only | current |
| tlpAtsOutletPhase OBJECT-TYPE Indicates on which phase or phases the given outlet is associated. For single phase devices, this object will always return phase1(1). For 3-phase devices with outlets wired to a single phase, this object will return phase1(1), phase2(2) or phase3(3). For 3-phase devices with outlets wired to two phases, this object will return phase1-2(4) for phases 1 and 2, phase2-3(5) for phases 2 and 3, and phase3-1(6) for phases 3 and 1. Devices that do not report phase connections will return unknown(0). | 1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.17 | INTEGER {unknown(0), phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | current |
| tlpAtsOutletGroupTable OBJECT-TYPE The receptacle grouping details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpAtsIdentNumOutletGroups per each device. | 1.3.6.1.4.1.850.1.1.3.4.3.3.2 | not-accessible | current | |
| tlpAtsOutletGroupEntry OBJECT-TYPE An entry containing information applicable to a particular outlet group managed by this agent. | 1.3.6.1.4.1.850.1.1.3.4.3.3.2.1 | not-accessible | current | |
| tlpAtsOutletGroupIndex OBJECT-TYPE The table row index for the ats outlet group. | 1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.1 | Unsigned32 | read-only | current |
| tlpAtsOutletGroupRowStatus OBJECT-TYPE Row status for the tlpAtsOutletGroupTable | 1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.2 | RowStatus | read-write | current |
| tlpAtsOutletGroupName OBJECT-TYPE The name of this outlet group. | 1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.3 | DisplayString | read-write | current |
| tlpAtsOutletGroupDescription OBJECT-TYPE A description for this outlet group. | 1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.4 | DisplayString | read-write | current |
| tlpAtsOutletGroupState OBJECT-TYPE The current state of the outlet group. This value will report off(1) if all outlets in the group are off, on(2) if all outlets in the group are on, mixed(3) if some outlets in the group are off and others are on, or unknown(0) if the state of the outlets cannot be determined. | 1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.5 | INTEGER {unknown(0), off(1), on(2), mixed(3)} | read-only | current |
| tlpAtsOutletGroupCommand OBJECT-TYPE Reading this value will always return 0. Setting this value to turnOff(1) will turn off every outlet associated with the group. Setting this value to turnOn(2) will turn on every outlet associated with the group. Setting this value to cycle(3) will turn off every outlet associated with the group, then turn each outlet back on. | 1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.6 | INTEGER {turnOff(1), turnOn(2), cycle(3)} | read-write | current |
| tlpAtsCircuit OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.3.4 | |||
| tlpAtsCircuitTable OBJECT-TYPE A list of ats circuit table entries. The number of entries is given by the value of tlpAtsIdentNumCircuits. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1 | not-accessible | current | |
| tlpAtsCircuitEntry OBJECT-TYPE An entry containing information applicable to a particular circuit managed by this agent. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1 | not-accessible | current | |
| tlpAtsCircuitIndex OBJECT-TYPE The table row index for the ats circuit. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.1 | Unsigned32 | read-only | current |
| tlpAtsCircuitPhase OBJECT-TYPE Indicates on which phase or phases the given circuit is wired. For single phase devices, this object will always return phase1(1). For 3-phase devices with outlets wired to a single phase, this object will return phase1(1), phase2(2) or phase3(3). For 3-phase devices with outlets wired to two phases, this object will return phase1-2(4) for phases 1 and 2, phase2-3(5) for phases 2 and 3, and phase3-1(6) for phases 3 and 1. Devices that do not report phase connections will return unknown(0). | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.2 | INTEGER {unknown(0), phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | current |
| tlpAtsCircuitInputVoltage OBJECT-TYPE The input voltage for a circuit. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.3 | Integer32 | read-only | current |
| tlpAtsCircuitTotalCurrent OBJECT-TYPE The total current for all receptacles in a given circuit. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.4 | Integer32 | read-only | current |
| tlpAtsCircuitCurrentLimit OBJECT-TYPE The current capacity of a circuit in the system limited by the circuit breaker or wiring used in a given unit. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.5 | Integer32 | read-only | current |
| tlpAtsCircuitCurrentMin OBJECT-TYPE The minimum total current for all receptacles in a given circuit since last reset. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.6 | Integer32 | read-only | current |
| tlpAtsCircuitCurrentMax OBJECT-TYPE The maximum total current for all receptacles in a given circuit since last reset. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.7 | Integer32 | read-only | current |
| tlpAtsCircuitTotalPower OBJECT-TYPE The total power for all receptacles in a given circuit. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.8 | Integer32 | read-only | current |
| tlpAtsCircuitPowerFactor OBJECT-TYPE The power factor for all receptacles in a given circuit. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.9 | INTEGER (0..200) | read-only | current |
| tlpAtsCircuitUtilization OBJECT-TYPE The percentage of utilization of a given circuit. This is typically a calculation of tlpAtsCircuitTotalCurrent / tlpAtsCircuitCurrentLimit. | 1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.10 | Unsigned32 | read-only | current |
| tlpAtsBreaker OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.3.5 | |||
| tlpAtsBreakerTable OBJECT-TYPE A list of ats bank breaker table entries. The number of entries is given by the value of tlpAtsIdentNumBreakers. | 1.3.6.1.4.1.850.1.1.3.4.3.5.1 | not-accessible | current | |
| tlpAtsBreakerEntry OBJECT-TYPE An entry containing information applicable to a particular bank breaker managed by this agent. | 1.3.6.1.4.1.850.1.1.3.4.3.5.1.1 | not-accessible | current | |
| tlpAtsBreakerIndex OBJECT-TYPE The table row index for the ats bank breaker. | 1.3.6.1.4.1.850.1.1.3.4.3.5.1.1.1 | Unsigned32 | read-only | current |
| tlpAtsBreakerStatus OBJECT-TYPE Indicates whether the bank breaker is open(0), closed(1) or not installed(2). | 1.3.6.1.4.1.850.1.1.3.4.3.5.1.1.2 | INTEGER {open(0), closed(1), notInstalled(2)} | read-only | current |
| tlpAtsHeatsink OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.3.6 | |||
| tlpAtsHeatsinkTable OBJECT-TYPE A list of ats heatsink thermistor table entries. The number of entries is given by the value of tlpAtsIdentNumHeatsinks. | 1.3.6.1.4.1.850.1.1.3.4.3.6.1 | not-accessible | current | |
| tlpAtsHeatsinkEntry OBJECT-TYPE An entry containing information applicable to a particular heatsink thermistor managed by this agent. | 1.3.6.1.4.1.850.1.1.3.4.3.6.1.1 | not-accessible | current | |
| tlpAtsHeatsinkIndex OBJECT-TYPE The table row index for the ats heatsink thermistor. | 1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.1 | Unsigned32 | read-only | current |
| tlpAtsHeatsinkStatus OBJECT-TYPE Indicates whether the heatsink thermistor is available. The entry will return notAvailable(0) if a thermistor is either non-existent or disconnected, or available(1) when connected. | 1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.2 | INTEGER {notAvailable(0), available(1)} | read-only | current |
| tlpAtsHeatsinkTemperatureC OBJECT-TYPE The temperature at the heatsink thermistor in tenths degrees Celsius. Heatsink temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.3 | Integer32 | read-only | current |
| tlpAtsHeatsinkTemperatureF OBJECT-TYPE The temperature at the heatsink thermistor in tenths degrees Fahrenheit. Heatsink temperature measurements are not supported on all models. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.4 | Integer32 | read-only | current |
| tlpAtsControl OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.4 | |||
| tlpAtsControlTable OBJECT-TYPE The actionable controls for each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss. | 1.3.6.1.4.1.850.1.1.3.4.4.1 | not-accessible | current | |
| tlpAtsControlEntry OBJECT-TYPE An entry containing controls for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.4.1.1 | not-accessible | current | |
| tlpAtsControlRamp OBJECT-TYPE Set to TRUE to initiate the pre-designated ramp sequence on the ats. | 1.3.6.1.4.1.850.1.1.3.4.4.1.1.1 | TruthValue | read-write | current |
| tlpAtsControlShed OBJECT-TYPE Set to TRUE to initiate the pre-designated shed sequence on the ats. | 1.3.6.1.4.1.850.1.1.3.4.4.1.1.2 | TruthValue | read-write | current |
| tlpAtsControlAtsOn OBJECT-TYPE Set to TRUE to turn the ats on. | 1.3.6.1.4.1.850.1.1.3.4.4.1.1.3 | TruthValue | read-write | current |
| tlpAtsControlAtsOff OBJECT-TYPE Set to TRUE to turn the ats off. | 1.3.6.1.4.1.850.1.1.3.4.4.1.1.4 | TruthValue | read-write | current |
| tlpAtsControlAtsReboot OBJECT-TYPE Set to TRUE to reboot the ats. | 1.3.6.1.4.1.850.1.1.3.4.4.1.1.5 | TruthValue | read-write | current |
| tlpAtsControlResetGeneralFault OBJECT-TYPE Set to TRUE to reset the general fault alarm indicated by tlpAtsDeviceGeneralFault. | 1.3.6.1.4.1.850.1.1.3.4.4.1.1.6 | TruthValue | read-write | current |
| tlpAtsConfig OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.4.5 | |||
| tlpAtsConfigTable OBJECT-TYPE The configuration options of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss. Not all options are available on all atss. | 1.3.6.1.4.1.850.1.1.3.4.5.1 | not-accessible | current | |
| tlpAtsConfigEntry OBJECT-TYPE An entry containing configuration options for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.5.1.1 | not-accessible | current | |
| tlpAtsConfigInputVoltage OBJECT-TYPE The nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. This value may not be writable on all models. If not writable, the value will be rejected and an appropriate error message will be returned. | 1.3.6.1.4.1.850.1.1.3.4.5.1.1.1 | Unsigned32 | read-write | current |
| tlpAtsConfigSourceSelect OBJECT-TYPE The determination as to which of two AC input lines is designated as the primary input source. The other is designated as the secondary input source. This value will always return inputSourceA(1) for devices with a single input source. Setting this value is supported only on selected models. | 1.3.6.1.4.1.850.1.1.3.4.5.1.1.2 | INTEGER {inputSourceA(1), inputSourceB(2)} | read-write | current |
| tlpAtsConfigSource1ReturnTime OBJECT-TYPE The nominal time to delay a transition to Source 1, if it is the preferred source. | 1.3.6.1.4.1.850.1.1.3.4.5.1.1.3 | Unsigned32 | read-write | current |
| tlpAtsConfigSource2ReturnTime OBJECT-TYPE The nominal time to delay a transition to Source 2, if it is the preferred source. | 1.3.6.1.4.1.850.1.1.3.4.5.1.1.4 | Unsigned32 | read-write | current |
| tlpAtsConfigAutoRampOnTransition OBJECT-TYPE When enabled(1), the ats should perform its preconfigured ramp sequence when the input source transfers from its designated secondary source to its designated primary source. This value not supported on all ats devices. If not supported, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.1.1.5 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpAtsConfigAutoShedOnTransition OBJECT-TYPE When enabled(1), the ats should perform its preconfigured shed sequence when the input source transfers from its designated primary source to its designated secondary source. This value not supported on all ats devices. If not supported, then this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.1.1.6 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpAtsConfigVoltageRangeOldTable OBJECT-TYPE The voltage range options in this table is intended to configure the operating voltages of an ats. This is a sparse dependent table, and will contain some subset of devices that are atss. All voltage points defined in this table are listed in a specific order from high to low. All voltage points must satisfy the conditions and ranges defined for each point. Any point violating any of the relative limits will be rejected. For optimal operation, it is recommended that tlpAtsConfigHighVoltageReset be set lower than tlpAtsConfigHighVoltageTransfer by a margin no less than 1% of tlpAtsConfigHighVoltageTransfer; and that tlpAtsConfigSource1TransferReset (tlpAtsConfigSource2TransferReset) be set higher than tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet) by a margin no less than 1% of tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet). *The upper limit of line voltage is tlpAtsInputHighTransferVoltageUpperBound. The lower limit of line voltage is tlpAtsInputBadTransferVoltageLowerBound. All minimum and maximum limits for each voltage point are all exclusive unless indicated otherwise. This table in its entirety is obsolete and replaced by tlpAtsConfigVoltageRangeTable. | 1.3.6.1.4.1.850.1.1.3.4.5.2 | not-accessible | obsolete | |
| tlpAtsConfigVoltageRangeOldEntry OBJECT-TYPE An entry containing voltage range configuration options for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1 | not-accessible | obsolete | |
| tlpAtsConfigHighVoltageTransferOld OBJECT-TYPE The maximum line voltage allowed before the unit disconnects the AC input connection. The maximum value allowed is dictated by tlpAtsInputHighTransferVoltageUpperBound (inclusively). The minimum value allowed is dictated by tlpAtsConfigHighVoltageResetOld. This value may not be configurable on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.1 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigHighVoltageResetOld OBJECT-TYPE If a unit is disconnected due to over-voltage, the line voltage has to fall below this value before the unit re-connects the AC input connection. The maximum value allowed is dictated by tlpAtsConfigHighVoltageTransferOld. The minimum value allowed is dictated by the greater of tlpAtsConfigSource1TransferResetOld and tlpAtsConfigSource2TransferResetOld. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.2 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigSource1TransferResetOld OBJECT-TYPE If input source 1 voltage level is above this value, a unit connected to source 2 will transition to source 1 (if it is the preferred source). The maximum value allowed is dictated by tlpAtsConfigHighVoltageResetOld. The minimum value allowed is dictated by tlpAtsConfigSource1BrownoutSetOld. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.3 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigSource1BrownoutSetOld OBJECT-TYPE This value dictates the voltage level below which source 1 goes into a brown out condition. The maximum value allowed is dictated by tlpAtsConfigSource1TransferResetOld. The minimum value allowed is dictated by tlpAtsConfigSource1TransferSetOld. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.4 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigSource1TransferSetOld OBJECT-TYPE If input source 1 voltage level falls below this value, a unit connected to source 1 will transition to source 2 (if it is in fair condition as denoted by tlpAtsConfigSource2TransferSetOld). The maximum value allowed is dictated by tlpAtsConfigSource1BrownoutSetOld. The minimum value allowed is dictated by tlpAtsConfigLowVoltageResetOld. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.5 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigSource2TransferResetOld OBJECT-TYPE If input source 2 voltage level is above this value, a unit connected to source 1 will transition to source 2 (if it is the preferred source). The maximum value allowed is dictated by tlpAtsConfigHighVoltageResetOld. The minimum value allowed is dictated by tlpAtsConfigSource2BrownoutSetOld. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.6 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigSource2BrownoutSetOld OBJECT-TYPE This value dictates the voltage level below which source 2 goes into a brown out condition. The maximum value allowed is dictated by tlpAtsConfigSource2TransferResetOld. The minimum value allowed is dictated by tlpAtsConfigSource2TransferSetOld. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.7 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigSource2TransferSetOld OBJECT-TYPE If input source 2 voltage level falls below this value, a unit connected to source 2 will transition to source 1 (if it is in fair condition as denoted by tlpAtsConfigSource1TransferSetOld). The maximum value allowed is dictated by tlpAtsConfigSource2BrownoutSetOld. The minimum value allowed is dictated by tlpAtsConfigLowVoltageResetOld. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.8 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigLowVoltageResetOld OBJECT-TYPE If a unit is disconnected due to under-voltage or is not powered up yet, the line voltage has to rise above this value before the unit gets connected to the AC input connection. The maximum value allowed is dictated by the lesser value of tlpAtsConfigSource1TransferSetOld and tlpAtsConfigSource2TransferSetOld. The minimum value allowed is dictated by tlpAtsConfigLowVoltageTransferOld. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.9 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigLowVoltageTransferOld OBJECT-TYPE The minimum line voltage allowed before the unit disconnects the AC input connection. The maximum value allowed is dictated by tlpAtsConfigLowVoltageResetOld. The minimum value allowed is dictated by tlpAtsInputBadTransferVoltageLowerBound (inclusively). If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.2.1.10 | Unsigned32 | read-write | obsolete |
| tlpAtsConfigVoltageRangeLimitsTable OBJECT-TYPE The voltage range table, as documented by tlpAtsConfigVoltageRangeTable requires that all changes adhere with stack order, from high transfer voltage down to low transfer voltage. In addition to stack order, certain voltage range values have limits defining the absolute minimum and absolute maximum for such values. Any voltage value violating any respective limit defined herein will be rejected. | 1.3.6.1.4.1.850.1.1.3.4.5.3 | not-accessible | current | |
| tlpAtsConfigVoltageRangeLimitsEntry OBJECT-TYPE An entry containing voltage range limits configuration options for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.5.3.1 | not-accessible | current | |
| tlpAtsConfigSourceBrownoutSetMinimum OBJECT-TYPE This value dictates the absolute lower limit by which tlpAtsConfigSource1BrownoutSet and tlpAtsConfigSource2BrownoutSet can be set. tlpAtsConfigSource1TransferSet and tlpAtsConfigSource2TransferSet, respectively, are also used when determining the lowest value a brownout value can be set at any given time. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.3.1.1 | Unsigned32 | read-write | current |
| tlpAtsConfigSourceBrownoutSetMaximum OBJECT-TYPE This value dictates the absolute upper limit by which tlpAtsConfigSource1BrownoutSet and tlpAtsConfigSource2BrownoutSet can be set. tlpAtsConfigSource1TransferReset and tlpAtsConfigSource2TransferReset, respectively, are also used when determining the greatest value a brownout value can be set at any given time. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.3.1.2 | Unsigned32 | read-write | current |
| tlpAtsConfigSourceTransferSetMinimum OBJECT-TYPE This value dictates the absolute lower limit by which tlpAtsConfigSource1TransferSet and tlpAtsConfigSource2TransferSet can be set. tlpAtsConfigLowVoltageReset is also used when determining the lowest value a transferset value can be set at any given time. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.3.1.3 | Unsigned32 | read-write | current |
| tlpAtsConfigSourceTransferSetMaximum OBJECT-TYPE This value dictates the absolute upper limit by which tlpAtsConfigSource1TransferSet and tlpAtsConfigSource2TransferSet can be set. tlpAtsConfigSource1BrownoutSet and tlpAtsConfigSource2BrownoutSet, respectively, are also used when determining the greatest value a transferset value can be set at any given time. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.3.1.4 | Unsigned32 | read-write | current |
| tlpAtsConfigThresholdTable OBJECT-TYPE The configurable threshold options of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss. Not all options are available on all atss. | 1.3.6.1.4.1.850.1.1.3.4.5.4 | not-accessible | current | |
| tlpAtsConfigThresholdEntry OBJECT-TYPE An entry containing configurable threshold options for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.5.4.1 | not-accessible | current | |
| tlpAtsConfigOutputCurrentThreshold OBJECT-TYPE The output current measurement at which an over current condition is reported. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.4.1.1 | Unsigned32 | read-write | current |
| tlpAtsConfigOverTemperatureThreshold OBJECT-TYPE The system temperature at which an over temperature condition is reported. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.4.1.2 | Unsigned32 | read-write | current |
| tlpAtsConfigOverVoltageThreshold OBJECT-TYPE The input voltage measurement at which an over voltage condition is reported. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.4.1.3 | Unsigned32 | read-write | current |
| tlpAtsConfigOverLoadThreshold OBJECT-TYPE The system load at which an overload condition is reported. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.4.1.4 | Unsigned32 | read-write | current |
| tlpAtsConfigVoltageRangeTable OBJECT-TYPE The voltage range options in this table is intended to configure the operating voltages of an ats. This is a sparse dependent table, and will contain some subset of devices that are atss. All voltage points defined in this table are listed in a specific order from high to low. All voltage points must satisfy the conditions and ranges defined for each point. Any point violating any of the relative limits will be rejected. For optimal operation, it is recommended that tlpAtsConfigHighVoltageReset be set lower than tlpAtsConfigHighVoltageTransfer by a margin no less than 1% of tlpAtsConfigHighVoltageTransfer; and that tlpAtsConfigSource1TransferReset (tlpAtsConfigSource2TransferReset) be set higher than tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet) by a margin no less than 1% of tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet). *The upper limit of line voltage is tlpAtsInputHighTransferVoltageUpperBound. The lower limit of line voltage is tlpAtsInputBadTransferVoltageLowerBound. All minimum and maximum limits for each voltage point are all exclusive unless indicated otherwise. | 1.3.6.1.4.1.850.1.1.3.4.5.5 | not-accessible | current | |
| tlpAtsConfigVoltageRangeEntry OBJECT-TYPE An entry containing voltage range configuration options for a particular ats. | 1.3.6.1.4.1.850.1.1.3.4.5.5.1 | not-accessible | current | |
| tlpAtsConfigHighVoltageTransfer OBJECT-TYPE The maximum line voltage allowed on the input source before the unit disconnects the AC input connection. tlpAtsConfigHighVoltageTransfer is the same value for both input sources on some units. On such units, changing this value on one source will change the value on the other source. The maximum value allowed is dictated by tlpAtsInputHighTransferVoltageUpperBound (inclusively). The minimum value allowed is dictated by tlpAtsConfigHighVoltageReset. This value may not be configurable on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.5.1.1 | Unsigned32 | read-write | current |
| tlpAtsConfigHighVoltageReset OBJECT-TYPE If an input connection is disconnected due to over-voltage, the line voltage on the input source has to fall below this value before the unit re-connects the AC input connection for the input source. tlpAtsConfigHighVoltageReset is the same value for both input sources on some units. On such units, changing this value on one source will change the value on the other source. The maximum value allowed is dictated by tlpAtsConfigHighVoltageTransfer. On units where this is the same value for both sources, the minimum value allowed is dictated by the greater of tlpAtsConfigTransferReset.1 and tlpAtsConfigTransferReset.2. On units where the value is distinct for each source, the minimum value allowed is dictated solely by this source's tlpAtsConfigTransferReset. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.5.1.2 | Unsigned32 | read-write | current |
| tlpAtsConfigTransferReset OBJECT-TYPE If input source voltage level is above this value, a unit connected to this other input source will transition to this input source (if it is the preferred source). The maximum value allowed is dictated by tlpAtsConfigHighVoltageReset. The minimum value allowed is dictated by tlpAtsConfigBrownoutSet. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.5.1.3 | Unsigned32 | read-write | current |
| tlpAtsConfigBrownoutSet OBJECT-TYPE This value dictates the voltage level below which the input source goes into a brown out condition. The maximum value allowed is dictated by tlpAtsConfigTransferReset. The minimum value allowed is dictated by tlpAtsConfigTransferSet. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.5.1.4 | Unsigned32 | read-write | current |
| tlpAtsConfigTransferSet OBJECT-TYPE If input source voltage level falls below this value, a unit connected to this input source will transition to other input source (if it is in fair condition as denoted by tlpAtsConfigTransferSet). The maximum value allowed is dictated by tlpAtsConfigBrownoutSet. The minimum value allowed is dictated by tlpAtsConfigLowVoltageReset. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.5.1.5 | Unsigned32 | read-write | current |
| tlpAtsConfigLowVoltageReset OBJECT-TYPE If a unit is disconnected due to under-voltage or is not powered up yet, the line voltage has to rise above this value before the unit gets connected to the AC input connection. tlpAtsConfigLowVoltageReset is the same value for both input sources. As such, changing this value on one source will change the value on the other source. The maximum value allowed is dictated by the lesser value of tlpAtsConfigTransferSet.1 and tlpAtsConfigTransferSet.2. The minimum value allowed is dictated by tlpAtsConfigLowVoltageTransfer. If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.5.1.6 | Unsigned32 | read-write | current |
| tlpAtsConfigLowVoltageTransfer OBJECT-TYPE The minimum line voltage allowed before the unit disconnects the AC input connection. tlpAtsConfigLowVoltageTransfer is the same value for both input sources. As such, changing this value on one source will change the value on the other source. The maximum value allowed is dictated by tlpAtsConfigLowVoltageReset. The minimum value allowed is dictated by tlpAtsInputBadTransferVoltageLowerBound (inclusively). If not supported, this value will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.4.5.5.1.7 | Unsigned32 | read-write | current |
| tlpAtsConfigPhaseThresholdTable OBJECT-TYPE The configuration options of each Ats in device table. This is a sparse dependent table, and will contain some subset of devices that are Atss. Not all options are available on all Atss. | 1.3.6.1.4.1.850.1.1.3.4.5.6 | not-accessible | current | |
| tlpAtsConfigPhaseThresholdEntry OBJECT-TYPE An entry containing threshold configuration options for a particular Ats. | 1.3.6.1.4.1.850.1.1.3.4.5.6.1 | not-accessible | current | |
| tlpAtsPhaseIndex OBJECT-TYPE The table row index for the Ats phase. | 1.3.6.1.4.1.850.1.1.3.4.5.6.1.1 | Unsigned32 | read-only | current |
| tlpAtsConfigOutputCurrentThresholdTolerance OBJECT-TYPE The threshold tolerance value used together with output current high/low threshold to evaluate output current high/low condition. | 1.3.6.1.4.1.850.1.1.3.4.5.6.1.2 | Unsigned32 | read-write | current |
| tlpAtsConfigOutputCurrentHighThreshold OBJECT-TYPE The value at which a output current high condition is declared. | 1.3.6.1.4.1.850.1.1.3.4.5.6.1.3 | Unsigned32 | read-write | current |
| tlpAtsConfigOutputCurrentLowThreshold OBJECT-TYPE The value at which a output current low condition is declared. | 1.3.6.1.4.1.850.1.1.3.4.5.6.1.4 | Unsigned32 | read-write | current |
| tlpCooling OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.5 | |||
| tlpCoolingIdent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.5.1 | |||
| tlpCoolingIdentNumCooling OBJECT-TYPE The number of cooling devices that this agent is currently managing. | 1.3.6.1.4.1.850.1.1.3.5.1.1 | Unsigned32 | read-only | current |
| tlpCoolingDevice OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.5.2 | |||
| tlpCoolingDetail OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.5.3 | |||
| tlpCoolingTemperature OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.5.3.1 | |||
| tlpCoolingTemperatureFahrenheitTable OBJECT-TYPE The temperature details for each cooling device in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1 | not-accessible | current | |
| tlpCoolingTemperatureFahrenheitEntry OBJECT-TYPE An entry containing temperature details for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1.1 | not-accessible | current | |
| tlpCoolingAmbientDegF OBJECT-TYPE The ambient temperature in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.1 | Integer32 | read-only | current |
| tlpCoolingSupplyAirDegF OBJECT-TYPE The temperature of the air entering the cooling unit in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.2 | Integer32 | read-only | current |
| tlpCoolingReturnAirDegF OBJECT-TYPE The temperature of the air entering the cooling unit in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.3 | Integer32 | read-only | current |
| tlpCoolingCondenserInletDegF OBJECT-TYPE The temperature of the air entering the condenser in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.4 | Integer32 | read-only | current |
| tlpCoolingEvaporatorDegF OBJECT-TYPE The temperature of the evaporator surface in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.5 | Integer32 | read-only | current |
| tlpCoolingSuctionDegF OBJECT-TYPE The temperature of the low pressure refrigerant line in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.6 | Integer32 | read-only | current |
| tlpCoolingRemoteDegF OBJECT-TYPE The external remote temperature in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.7 | Integer32 | read-only | current |
| tlpCoolingCondenserOutletDegF OBJECT-TYPE The temperature of the air leaving the condenser in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.8 | Integer32 | read-only | current |
| tlpCoolingTemperatureCelsiusTable OBJECT-TYPE The temperature details for each cooling device in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2 | not-accessible | current | |
| tlpCoolingTemperatureCelsiusEntry OBJECT-TYPE An entry containing temperature details for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2.1 | not-accessible | current | |
| tlpCoolingAmbientDegC OBJECT-TYPE The ambient temperature in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.1 | Integer32 | read-only | current |
| tlpCoolingSupplyAirDegC OBJECT-TYPE The temperature of the air entering the cooling unit in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.2 | Integer32 | read-only | current |
| tlpCoolingReturnAirDegC OBJECT-TYPE The temperature of the air entering the cooling unit in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.3 | Integer32 | read-only | current |
| tlpCoolingCondenserInletDegC OBJECT-TYPE The temperature of the air entering the condenser in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.4 | Integer32 | read-only | current |
| tlpCoolingEvaporatorDegC OBJECT-TYPE The temperature of the evaporator surface in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.5 | Integer32 | read-only | current |
| tlpCoolingSuctionDegC OBJECT-TYPE The temperature of the low pressure refrigerant line in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.6 | Integer32 | read-only | current |
| tlpCoolingRemoteDegC OBJECT-TYPE The external remote temperature in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.7 | Integer32 | read-only | current |
| tlpCoolingCondenserOutletDegC OBJECT-TYPE The temperature of the air leaving the condenser in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.8 | Integer32 | read-only | current |
| tlpCoolingPressure OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.5.3.2 | |||
| tlpCoolingPressureMpaTable OBJECT-TYPE The pressure detail for each cooling device in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling. | 1.3.6.1.4.1.850.1.1.3.5.3.2.1 | not-accessible | current | |
| tlpCoolingPressureMpaEntry OBJECT-TYPE An entry containing pressure details for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.3.2.1.1 | not-accessible | current | |
| tlpCoolingSuctionPressureMpa OBJECT-TYPE The pressure of the compressor discharge line in tenths of Mpa. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.2.1.1.1 | Unsigned32 | read-only | current |
| tlpCoolingDischargePressureMpa OBJECT-TYPE The pressure of the compressor discharge line in tenths of Mpa. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.2.1.1.2 | Unsigned32 | read-only | current |
| tlpCoolingPressurePsiTable OBJECT-TYPE The pressure detail for each cooling device in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling. | 1.3.6.1.4.1.850.1.1.3.5.3.2.2 | not-accessible | current | |
| tlpCoolingPressurePsiEntry OBJECT-TYPE An entry containing pressure details for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.3.2.2.1 | not-accessible | current | |
| tlpCoolingSuctionPressurePsi OBJECT-TYPE The pressure of the compressor discharge line in tenths of Psi. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.2.2.1.1 | Unsigned32 | read-only | current |
| tlpCoolingDischargePressurePsi OBJECT-TYPE The pressure of the compressor discharge line in tenths of Psi. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.2.2.1.2 | Unsigned32 | read-only | current |
| tlpCoolingCurrentTable OBJECT-TYPE The input current for each cooling device in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling. | 1.3.6.1.4.1.850.1.1.3.5.3.3 | not-accessible | current | |
| tlpCoolingCurrentEntry OBJECT-TYPE An entry containing input current for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.3.3.1 | not-accessible | current | |
| tlpCoolingUnitCurrent OBJECT-TYPE The total current draw of the unit in tenths of Amps. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.3.1.1 | Unsigned32 | read-only | current |
| tlpCoolingCompressorCurrent OBJECT-TYPE The compressor current draw of the unit in tenths of Amps. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.3.1.2 | Unsigned32 | read-only | current |
| tlpCoolingEvaporatorFanCurrent OBJECT-TYPE The current draw of the evaporator fan in tenths of Amps. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.3.1.3 | Unsigned32 | read-only | current |
| tlpCoolingCondenserFanCurrent OBJECT-TYPE The current draw of the condenser fan in tenths of Amps. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.3.1.4 | Unsigned32 | read-only | current |
| tlpCoolingDynamicTable OBJECT-TYPE The dynamic detail for each cooling device in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling. | 1.3.6.1.4.1.850.1.1.3.5.3.4 | not-accessible | current | |
| tlpCoolingDynamicEntry OBJECT-TYPE An entry dynamic details for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.3.4.1 | not-accessible | current | |
| tlpCoolingEvaporatorFanSpeed OBJECT-TYPE The current speed of the evaporator fan. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.4.1.1 | INTEGER {off(0), low(1), mediumLow(2), medium(3), mediumHigh(4), high(5), auto(6)} | read-only | current |
| tlpCoolingCondenserFanSpeed OBJECT-TYPE The current speed of the condenser fan. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.4.1.2 | INTEGER {off(0), low(1), mediumLow(2), medium(3), mediumHigh(4), high(5), auto(6)} | read-only | current |
| tlpCoolingCompressorFrequency OBJECT-TYPE The operating mechanical frequency(Hz) of the compressor. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.4.1.3 | Unsigned32 | read-only | current |
| tlpCoolingEEVSteps OBJECT-TYPE The current EEV steps. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.4.1.4 | INTEGER | read-only | current |
| tlpCoolingRuntimeTable OBJECT-TYPE The runtime detail for each cooling device in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling. | 1.3.6.1.4.1.850.1.1.3.5.3.5 | not-accessible | current | |
| tlpCoolingRuntimeEntry OBJECT-TYPE An entry containing runtime for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.3.5.1 | not-accessible | current | |
| tlpCoolingCompressorRunDays OBJECT-TYPE Total days the compressor has been under operation. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.5.1.1 | Unsigned32 | read-only | current |
| tlpCoolingCondensatePumpRunDays OBJECT-TYPE Total days the condensate pump has been under operation. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.5.1.2 | Unsigned32 | read-only | current |
| tlpCoolingAirFilterRunHours OBJECT-TYPE Total hours the air filter has been under operation. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.5.1.3 | Unsigned32 | read-only | current |
| tlpCoolingEvaporatorFanRunDays OBJECT-TYPE Total days the evaporator fan has been under operation. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.5.1.4 | Unsigned32 | read-only | current |
| tlpCoolingCondenserFanRunDays OBJECT-TYPE Total days the condenser fan has been under operation. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.5.1.5 | Unsigned32 | read-only | current |
| tlpCoolingAtomizerRunDays OBJECT-TYPE Total days the atomizer has been under operation. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.5.1.6 | Unsigned32 | read-only | current |
| tlpCoolingStatusTable OBJECT-TYPE The status detail for each cooling device in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling. | 1.3.6.1.4.1.850.1.1.3.5.3.6 | not-accessible | current | |
| tlpCoolingStatusEntry OBJECT-TYPE An entry containing status for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.3.6.1 | not-accessible | current | |
| tlpCoolingOperatingMode OBJECT-TYPE The current operating mode. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.6.1.1 | INTEGER {off(0), idle(1), cooling(2), shuttingDown(3), dehumidifying(4), defrosting(5), notConnected(6)} | read-only | current |
| tlpCoolingCoolOutput OBJECT-TYPE The current cooling output of the cooling device in tenth of kilowatt. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.6.1.2 | Unsigned32 | read-only | current |
| tlpCoolingAlarmStatus OBJECT-TYPE The current alarm status of the cooling device. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.6.1.3 | INTEGER {noAlarm(0), warning(1), critical(2)} | read-only | current |
| tlpCoolingCompressorStatus OBJECT-TYPE The current operating status of compressor. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.6.1.4 | INTEGER {off(0), on(1)} | read-only | current |
| tlpCoolingWaterStatus OBJECT-TYPE The current water status of cooling unit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.3.6.1.5 | INTEGER {notFull(0), full(1)} | read-only | current |
| tlpCoolingControl OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.5.4 | |||
| tlpCoolingControlTable OBJECT-TYPE The actionable controls for each cooling device in device table. This is a sparse dependent table, and will contain some subset of devices that are cooling device. | 1.3.6.1.4.1.850.1.1.3.5.4.1 | not-accessible | current | |
| tlpCoolingControlEntry OBJECT-TYPE An entry containing controls for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.4.1.1 | not-accessible | current | |
| tlpCoolingOnOff OBJECT-TYPE Turn the unit on or off. | 1.3.6.1.4.1.850.1.1.3.5.4.1.1.1 | INTEGER {turnOffUnit(0), turnOnUnit(1)} | read-write | current |
| tlpCoolingConfig OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.5.5 | |||
| tlpCoolingConfigTable OBJECT-TYPE The configuration details for each each cooling device in device table. This is a sparse dependent table, and will contain some subset of devices that are cooling device. Not all options are available on all cooling devices. | 1.3.6.1.4.1.850.1.1.3.5.5.1 | not-accessible | current | |
| tlpCoolingConfigEntry OBJECT-TYPE An entry configuration details for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1 | not-accessible | current | |
| tlpCoolingAutoStart OBJECT-TYPE Specifies if the unit should start automatically on power up. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.1 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpCoolingFanSpeed OBJECT-TYPE Specifies the actual speed of the evaporator fan. Setting the fan speed to auto(6) will enable tlpCoolingAutoFanSpeed; however, on most units getting the fan speed will return the actual fan speed regardless whether auto fan speed is enabled or disabled. The value auto(6) is returned only on units that do not report the actual fan speed when auto fan speed is enabled. Not all values are supported on all cooling units. Invalid values will return an appropriate error when accessed. If not supported, this value will always return ERROR_NO_SUCH_NAME | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.2 | INTEGER {off(0), low(1), mediumLow(2), medium(3), mediumHigh(4), high(5), auto(6)} | read-write | current |
| tlpCoolingControlType OBJECT-TYPE Specifies which temperature is used as a control point. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.3 | INTEGER {returnAirTemperature(0), remoteTemperature(1)} | read-write | current |
| tlpCoolingDisplayUnits OBJECT-TYPE Specifies whether displays output values in Metric or English formats. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.4 | INTEGER {metric(0), english(1)} | read-write | current |
| tlpCoolingBeepOnKey OBJECT-TYPE Specifies whether a beep is emitted when a key is pressed on the unit's display panel. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.5 | INTEGER {noBeep(0), beepOn(1)} | read-write | current |
| tlpCoolingInputContactType OBJECT-TYPE The input contact type. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.6 | INTEGER {normallyClosed(0), normallyOpen(1)} | read-write | current |
| tlpCoolingOutputContactType OBJECT-TYPE The output contact type. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.7 | INTEGER {normallyClosed(0), normallyOpen(1)} | read-write | current |
| tlpCoolingOutputRelaySource OBJECT-TYPE The alarm level that causes the output relay to activate. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.8 | INTEGER {disabled(0), allAlarmsAndWarnings(1), criticalAlarmsOnly(2)} | read-write | current |
| tlpCoolingOutputRelayDefault OBJECT-TYPE Type of contact to make when output relay is activated. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.9 | INTEGER {normallyClosed(0), normallyOpen(1)} | read-write | current |
| tlpCoolingOffOnInputContact OBJECT-TYPE Indicates if the unit should stop cooling when input contact is activated. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.10 | INTEGER {turnOff(0), alarmOnly(1)} | read-write | current |
| tlpCoolingOffOnLeak OBJECT-TYPE Indicates if the unit should stop cooling when leak input is activated. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.11 | INTEGER {turnOff(0), alarmOnly(1)} | read-write | current |
| tlpCoolingWaterLeakContactType OBJECT-TYPE The water leak contact type. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.12 | INTEGER {normallyClosed(0), normallyOpen(1)} | read-write | current |
| tlpCoolingAirFilterInterval OBJECT-TYPE The number of weeks before the air filter needs to be changed. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.13 | Unsigned32 | read-write | current |
| tlpCoolingAirFilterAlarm OBJECT-TYPE When enabled, an alarm should occur when the maximum number of air filter run hours has been exceeded. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.14 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpCoolingMaxAirFilterRunHours OBJECT-TYPE The maximum interval for air filter run hours before warning is annunciated. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.15 | Unsigned32 | read-write | current |
| tlpCoolingStartTimer OBJECT-TYPE The unit will start operate after the specified timer elapsed. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.16 | Unsigned32 | read-write | current |
| tlpCoolingStopTimer OBJECT-TYPE The unit will switch to standby mode after the specified timer elapsed. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.17 | Unsigned32 | read-write | current |
| tlpCoolingEnergyMode OBJECT-TYPE This option enables or disables the energy saving mode. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.18 | INTEGER {normalCooling(0), energySaving(1)} | read-write | current |
| tlpCoolingDefrostMode OBJECT-TYPE This option enables or disables the defrost mode. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.19 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpCoolingRemoteTemperatureSensor OBJECT-TYPE This option enables or disables the remote temperature sensor. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.20 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpCoolingDehumidifyingMode OBJECT-TYPE This option enables or disables the dehumidifying mode. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.21 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpCoolingFanAlwaysOn OBJECT-TYPE This option enables or disables the fan always on. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.22 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpCoolingQuietMode OBJECT-TYPE This option enables or disables the quiet mode. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.23 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpCoolingHotGasBypass OBJECT-TYPE This option enables or disables the hot gas bypass. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.24 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpCoolingAutoFanSpeed OBJECT-TYPE This option enables or disables the auto fan speed. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.1.1.25 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| tlpCoolingConfigTemperatureFahrenheitTable OBJECT-TYPE The configuration details for each each cooling device in device table. This is a sparse dependent table, and will contain some subset of devices that are cooling device. Not all options are available on all cooling devices. | 1.3.6.1.4.1.850.1.1.3.5.5.2 | not-accessible | current | |
| tlpCoolingConfigTemperatureFahrenheitEntry OBJECT-TYPE An entry configuration details for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.5.2.1 | not-accessible | current | |
| tlpCoolingSetPointDegF OBJECT-TYPE The set point temperature the unit will control the temperature in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.2.1.1 | Integer32 | read-write | current |
| tlpCoolingSupplyAirHighLimitDegF OBJECT-TYPE Maximum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.2.1.2 | Integer32 | read-write | current |
| tlpCoolingSupplyAirLowLimitDegF OBJECT-TYPE Minimum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.2.1.3 | Integer32 | read-write | current |
| tlpCoolingMaxDeviationLimitDegF OBJECT-TYPE Maximum allowed air temperature deviation from set temperature before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.2.1.4 | Integer32 | read-write | current |
| tlpCoolingReturnAirHighLimitDegF OBJECT-TYPE Maximum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.2.1.5 | Integer32 | read-write | current |
| tlpCoolingReturnAirLowLimitDegF OBJECT-TYPE Minimum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.2.1.6 | Integer32 | read-write | current |
| tlpCoolingRemoteSetPointDegF OBJECT-TYPE The remote set point temperature the unit will control the temperature in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.2.1.7 | Integer32 | read-write | current |
| tlpCoolingConfigTemperatureCelsiusTable OBJECT-TYPE The configuration details for each cooling device in device table. This is a sparse dependent table, and will contain some subset of devices that are cooling device. Not all options are available on all cooling devices. | 1.3.6.1.4.1.850.1.1.3.5.5.3 | not-accessible | current | |
| tlpCoolingConfigTemperatureCelsiusEntry OBJECT-TYPE An entry configuration details for a particular cooling device. | 1.3.6.1.4.1.850.1.1.3.5.5.3.1 | not-accessible | current | |
| tlpCoolingSetPointDegC OBJECT-TYPE The set point temperature the unit will control the temperature in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.3.1.1 | Integer32 | read-write | current |
| tlpCoolingSupplyAirHighLimitDegC OBJECT-TYPE Maximum allowed supply air temperature in tenths degrees Celsius before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.3.1.2 | Integer32 | read-write | current |
| tlpCoolingSupplyAirLowLimitDegC OBJECT-TYPE Minimum allowed supply air temperature in tenths degrees Celsius before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.3.1.3 | Integer32 | read-write | current |
| tlpCoolingMaxDeviationLimitDegC OBJECT-TYPE Maximum allowed air temperature deviation from set temperature before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.3.1.4 | Integer32 | read-write | current |
| tlpCoolingReturnAirHighLimitDegC OBJECT-TYPE Maximum allowed return air temperature in tenths degrees Celsius before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.3.1.5 | Integer32 | read-write | current |
| tlpCoolingReturnAirLowLimitDegC OBJECT-TYPE Minimum allowed return air temperature in tenths degrees Celsius before firing an alarm. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.3.1.6 | Integer32 | read-write | current |
| tlpCoolingRemoteSetPointDegC OBJECT-TYPE The remote set point temperature the unit will control the temperature in tenths degrees Celsius. If not supported, this value will always return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.1.3.5.5.3.1.7 | Integer32 | read-write | current |
| tlpKvm OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.6 | |||
| tlpKvmIdent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.6.1 | |||
| tlpKvmIdentNumKvm OBJECT-TYPE The number of kvm devices that this agent is currently managing. | 1.3.6.1.4.1.850.1.1.3.6.1.1 | Unsigned32 | read-only | current |
| tlpKvmDevice OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.6.2 | |||
| tlpKvmDetail OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.6.3 | |||
| tlpKvmControl OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.6.4 | |||
| tlpKvmConfig OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.6.5 | |||
| tlpRackTrack OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.7 | |||
| tlpRackTrackIdent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.7.1 | |||
| tlpRackTrackIdentNumRackTrack OBJECT-TYPE The number of rack track devices that this agent is currently managing. | 1.3.6.1.4.1.850.1.1.3.7.1.1 | Unsigned32 | read-only | current |
| tlpRackTrackDevice OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.7.2 | |||
| tlpRackTrackDetail OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.7.3 | |||
| tlpRackTrackControl OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.7.4 | |||
| tlpRackTrackConfig OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.7.5 | |||
| tlpSwitch OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.8 | |||
| tlpSwitchIdent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.8.1 | |||
| tlpSwitchIdentNumSwitch OBJECT-TYPE The number of switch devices that this agent is currently managing. | 1.3.6.1.4.1.850.1.1.3.8.1.1 | Unsigned32 | read-only | current |
| tlpSwitchDevice OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.8.2 | |||
| tlpSwitchDetail OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.8.3 | |||
| tlpSwitchControl OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.8.4 | |||
| tlpSwitchConfig OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.1.3.8.5 | |||
| tlpSoftware OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2 | |||
| tlpAgentDetails OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.1 | |||
| tlpAgentIdent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.1.1 | |||
| tlpAgentType OBJECT-TYPE The type of PowerAlert engine providing this data. | 1.3.6.1.4.1.850.1.2.1.1.1 | INTEGER {unknown(0), pal(1), pansa(2), delta(3), sinetica(4), netos6(5), netos7(6), panms(7), nmc5(8)} | read-only | current |
| tlpAgentVersion OBJECT-TYPE The version of the agent software. | 1.3.6.1.4.1.850.1.2.1.1.2 | DisplayString | read-only | current |
| tlpAgentDriverVersion OBJECT-TYPE The driver version of the agent software. | 1.3.6.1.4.1.850.1.2.1.1.3 | DisplayString | read-only | current |
| tlpAgentMAC OBJECT-TYPE The MAC Address of the agent. | 1.3.6.1.4.1.850.1.2.1.1.4 | DisplayString | read-only | current |
| tlpAgentSerialNum OBJECT-TYPE Serial number of the web card providing the agent data. This value is only supported by a web card agent. PowerAlert for PC (PAL) agents do not support this value and will return ERROR_NO_SUCH_NAME. | 1.3.6.1.4.1.850.1.2.1.1.5 | DisplayString | read-only | current |
| tlpAgentUuid OBJECT-TYPE Universally unique identifier for this host in the form 8-4-4-4-12 for a total of 36 characters (32 alphanumeric characters and four hyphens). For example: 550e8400-e29b-41d4-a716-446655440000. | 1.3.6.1.4.1.850.1.2.1.1.6 | DisplayString | read-only | current |
| tlpAgentAttributes OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.1.2 | |||
| tlpAgentAttributesSupports OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.1.2.1 | |||
| tlpAgentAttributesSupportsHTTP OBJECT-TYPE Indicates whether the agent supports HTTP connections. | 1.3.6.1.4.1.850.1.2.1.2.1.1 | TruthValue | read-only | current |
| tlpAgentAttributesSupportsHTTPS OBJECT-TYPE Indicates whether the agent supports HTTPS connections. | 1.3.6.1.4.1.850.1.2.1.2.1.2 | TruthValue | read-only | current |
| tlpAgentAttributesSupportsFTP OBJECT-TYPE Indicates whether the agent supports FTP connections. | 1.3.6.1.4.1.850.1.2.1.2.1.3 | TruthValue | read-only | current |
| tlpAgentAttributesSupportsTelnetMenu OBJECT-TYPE Indicates whether the agent supports Telnet menu connections. | 1.3.6.1.4.1.850.1.2.1.2.1.4 | TruthValue | read-only | current |
| tlpAgentAttributesSupportsTelnetCLI OBJECT-TYPE Indicates whether the agent supports Telnet CLI connections. | 1.3.6.1.4.1.850.1.2.1.2.1.5 | TruthValue | read-only | current |
| tlpAgentAttributesSupportsSSHMenu OBJECT-TYPE Indicates whether the agent supports SSH menu connections. | 1.3.6.1.4.1.850.1.2.1.2.1.6 | TruthValue | read-only | current |
| tlpAgentAttributesSupportsSSHCLI OBJECT-TYPE Indicates whether the agent supports SSH CLI connections. | 1.3.6.1.4.1.850.1.2.1.2.1.7 | TruthValue | read-only | current |
| tlpAgentAttributesSupportsSNMP OBJECT-TYPE Indicates whether the agent supports SNMP connections. | 1.3.6.1.4.1.850.1.2.1.2.1.8 | TruthValue | read-only | current |
| tlpAgentAttributesSupportsSNMPTrap OBJECT-TYPE Indicates whether the agent supports listening for SNMP traps. This is only applicable for network monitoring applications, PowerAlert Shutdown Agent for an example, that connect to a web card or PowerAlert Local and listen for outbound traps. As such, this value is not supported and will always return 2(false) for a web card or PowerAlert Local. | 1.3.6.1.4.1.850.1.2.1.2.1.9 | TruthValue | read-only | current |
| tlpAgentAttributesAutostart OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.1.2.2 | |||
| tlpAgentAttributesAutostartHTTP OBJECT-TYPE Indicates whether the agent autostarts HTTP services. | 1.3.6.1.4.1.850.1.2.1.2.2.1 | TruthValue | read-only | current |
| tlpAgentAttributesAutostartHTTPS OBJECT-TYPE Indicates whether the agent autostarts HTTPS services. | 1.3.6.1.4.1.850.1.2.1.2.2.2 | TruthValue | read-only | current |
| tlpAgentAttributesAutostartFTP OBJECT-TYPE Indicates whether the agent autostarts FTP services. | 1.3.6.1.4.1.850.1.2.1.2.2.3 | TruthValue | read-only | current |
| tlpAgentAttributesAutostartTelnetMenu OBJECT-TYPE Indicates whether the agent autostarts Telnet menu services. | 1.3.6.1.4.1.850.1.2.1.2.2.4 | TruthValue | read-only | current |
| tlpAgentAttributesAutostartTelnetCLI OBJECT-TYPE Indicates whether the agent autostarts Telnet CLI services. | 1.3.6.1.4.1.850.1.2.1.2.2.5 | TruthValue | read-only | current |
| tlpAgentAttributesAutostartSSHMenu OBJECT-TYPE Indicates whether the agent autostarts SSH menu services. | 1.3.6.1.4.1.850.1.2.1.2.2.6 | TruthValue | read-only | current |
| tlpAgentAttributesAutostartSSHCLI OBJECT-TYPE Indicates whether the agent autostarts SSH CLI services. | 1.3.6.1.4.1.850.1.2.1.2.2.7 | TruthValue | read-only | current |
| tlpAgentAttributesAutostartSNMP OBJECT-TYPE Indicates whether the agent autostarts SNMP services. | 1.3.6.1.4.1.850.1.2.1.2.2.8 | TruthValue | read-only | current |
| tlpAgentAttributesSnmp OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.1.2.3 | |||
| tlpAgentAttributesSNMPv1Enabled OBJECT-TYPE Indicates whether the agent will allow SNMPv1 connections. | 1.3.6.1.4.1.850.1.2.1.2.3.1 | TruthValue | read-only | current |
| tlpAgentAttributesSNMPv2cEnabled OBJECT-TYPE Indicates whether the agent will allow SNMPv2c connections. | 1.3.6.1.4.1.850.1.2.1.2.3.2 | TruthValue | read-only | current |
| tlpAgentAttributesSNMPv3Enabled OBJECT-TYPE Indicates whether the agent will allow SNMPv3 connections. | 1.3.6.1.4.1.850.1.2.1.2.3.3 | TruthValue | read-only | current |
| tlpAgentAttributesPorts OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.1.2.4 | |||
| tlpAgentAttributesHTTPPort OBJECT-TYPE The port used for HTTP communications. | 1.3.6.1.4.1.850.1.2.1.2.4.1 | Unsigned32 | read-only | current |
| tlpAgentAttributesHTTPSPort OBJECT-TYPE The port used for HTTPS communications. | 1.3.6.1.4.1.850.1.2.1.2.4.2 | Unsigned32 | read-only | current |
| tlpAgentAttributesFTPPort OBJECT-TYPE The port used for FTP communications. | 1.3.6.1.4.1.850.1.2.1.2.4.3 | Unsigned32 | read-only | current |
| tlpAgentAttributesTelnetMenuPort OBJECT-TYPE The port used for Telnet Menu communications. | 1.3.6.1.4.1.850.1.2.1.2.4.4 | Unsigned32 | read-only | current |
| tlpAgentAttributesTelnetCLIPort OBJECT-TYPE The port used for Telnet CLI communications. | 1.3.6.1.4.1.850.1.2.1.2.4.5 | Unsigned32 | read-only | current |
| tlpAgentAttributesSSHMenuPort OBJECT-TYPE The port used for SSH Menu communications. | 1.3.6.1.4.1.850.1.2.1.2.4.6 | Unsigned32 | read-only | current |
| tlpAgentAttributesSSHCLIPort OBJECT-TYPE The port used for SSH CLI communications. | 1.3.6.1.4.1.850.1.2.1.2.4.7 | Unsigned32 | read-only | current |
| tlpAgentAttributesSNMPPort OBJECT-TYPE The port used for SNMP communications. | 1.3.6.1.4.1.850.1.2.1.2.4.8 | Unsigned32 | read-only | current |
| tlpAgentAttributesSNMPTrapPort OBJECT-TYPE The port used for SNMP trap and notifications. | 1.3.6.1.4.1.850.1.2.1.2.4.9 | Unsigned32 | read-only | current |
| tlpAgentSettings OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.2 | |||
| tlpAgentConfig OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.2.1 | |||
| tlpAgentConfigRemoteRegistration OBJECT-TYPE Registers an SNMP contact's IP address and the port on which the contact is listening for SNMP traps. Setting this value is used to CREATE a table entry in a non-standard way. Getting this value will return a string INADDR_ANY and any port number. The port number should always be included. When unregistering an SNMP contact, the requester's IP address should be provided with a port number of 0. When setting or unsetting this OID, the IP address string should never be 0 nor should it be empty. The registration uses its default community string to register each contact. To use a community other than the default, then it must be appended to the end of the string delimited with a comma. The address should be of the format 0.0.0.0:00000 for IPv4. If IPv6 is supported, use the bracket-enclosed format given in IETF RFC 2732 Section 2, with the following examples: [FEDC:BA98:7654:3210:FEDC:BA98:7654:3210]:80 [1080:0:0:0:8:800:200C:417A]:162 [3ffe:2a00:100:7031::1]:162 [1080::8:800:200C:417A]:162,myCommunity [::192.9.5.5]:162,myCommunity [::FFFF:129.144.52.38]:80 [2010:836B:4179::836B:4179]:162 | 1.3.6.1.4.1.850.1.2.2.1.1 | DisplayString | read-write | current |
| tlpAgentConfigCurrentTime OBJECT-TYPE The current date and time of the system. | 1.3.6.1.4.1.850.1.2.2.1.2 | DisplayString | read-write | current |
| tlpAgentContacts OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.3 | |||
| tlpAgentEmailContacts OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.3.1 | |||
| tlpAgentNumEmailContacts OBJECT-TYPE The number of email contacts currently defined in the agent. | 1.3.6.1.4.1.850.1.2.3.1.1 | Unsigned32 | read-only | current |
| tlpAgentEmailContactTable OBJECT-TYPE A list of email contact entries. The number of entries is given by the value of tlpAgentNumEmailContacts. | 1.3.6.1.4.1.850.1.2.3.1.2 | not-accessible | current | |
| tlpAgentEmailContactEntry OBJECT-TYPE An entry containing the details of an email contact. | 1.3.6.1.4.1.850.1.2.3.1.2.1 | not-accessible | current | |
| tlpAgentEmailContactIndex OBJECT-TYPE The table row index for the email contact. | 1.3.6.1.4.1.850.1.2.3.1.2.1.1 | Unsigned32 | read-only | current |
| tlpAgentEmailContactRowStatus OBJECT-TYPE Row status for the tlpAgentEmailContactTable. | 1.3.6.1.4.1.850.1.2.3.1.2.1.2 | RowStatus | read-write | current |
| tlpAgentEmailContactName OBJECT-TYPE The name of the email contact. | 1.3.6.1.4.1.850.1.2.3.1.2.1.3 | DisplayString | read-write | current |
| tlpAgentEmailContactAddress OBJECT-TYPE The address of the email contact. | 1.3.6.1.4.1.850.1.2.3.1.2.1.4 | DisplayString | read-write | current |
| tlpAgentSnmpContacts OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.2.3.2 | |||
| tlpAgentNumSnmpContacts OBJECT-TYPE The number of SNMP contacts currently defined in the agent. | 1.3.6.1.4.1.850.1.2.3.2.1 | Unsigned32 | read-only | current |
| tlpAgentSnmpContactTable OBJECT-TYPE A list of SNMP contact entries. The number of entries is given by the value of tlpAgentNumSnmpContacts. | 1.3.6.1.4.1.850.1.2.3.2.2 | not-accessible | current | |
| tlpAgentSnmpContactEntry OBJECT-TYPE An entry containing the details of an SNMP contact. | 1.3.6.1.4.1.850.1.2.3.2.2.1 | not-accessible | current | |
| tlpAgentSnmpContactIndex OBJECT-TYPE The table row index for the SNMP contact. | 1.3.6.1.4.1.850.1.2.3.2.2.1.1 | Unsigned32 | read-only | current |
| tlpAgentSnmpContactRowStatus OBJECT-TYPE Row status for the tlpAgentSnmpContactTable. | 1.3.6.1.4.1.850.1.2.3.2.2.1.2 | RowStatus | read-write | current |
| tlpAgentSnmpContactName OBJECT-TYPE The name of the SNMP contact. | 1.3.6.1.4.1.850.1.2.3.2.2.1.3 | DisplayString | read-write | current |
| tlpAgentSnmpContactIpAddress OBJECT-TYPE The IP address of the SNMP contact. | 1.3.6.1.4.1.850.1.2.3.2.2.1.4 | DisplayString | read-write | current |
| tlpAgentSnmpContactPort OBJECT-TYPE The port of the SNMP contact. | 1.3.6.1.4.1.850.1.2.3.2.2.1.5 | Unsigned32 | read-write | current |
| tlpAgentSnmpContactSnmpVersion OBJECT-TYPE The SNMP contact version to use for sending traps. | 1.3.6.1.4.1.850.1.2.3.2.2.1.6 | INTEGER {snmpv1(1), snmpv2c(2), snmpv3(3)} | read-write | current |
| tlpAgentSnmpContactSecurityName OBJECT-TYPE The security name for the SNMP contact. | 1.3.6.1.4.1.850.1.2.3.2.2.1.7 | DisplayString | read-write | current |
| tlpAgentSnmpContactPrivPassword OBJECT-TYPE The privacy password to use for sending V3 traps to the SNMP contact. | 1.3.6.1.4.1.850.1.2.3.2.2.1.8 | DisplayString | read-write | obsolete |
| tlpAgentSnmpContactAuthPassword OBJECT-TYPE The authentication password to use for sending V3 traps to the SNMP contact. | 1.3.6.1.4.1.850.1.2.3.2.2.1.9 | DisplayString | read-write | obsolete |
| tlpAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3 | |||
| tlpAlarmsPresent OBJECT-TYPE The present number of active alarm conditions. | 1.3.6.1.4.1.850.1.3.1 | Unsigned32 | read-only | current |
| tlpAlarmTable OBJECT-TYPE A list of alarm conditions for all devices managed by this agent. This table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect or conditions not acknowledged. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains (becomes inactive and is acknowledged). The agent creates the first row with tlpAlarmId equal to 1, and increments the value of tlpAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of tlpAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse (e.g., containing entries for rows 95, 100, 101, and 203) and the entries should not be assumed to be in chronological order because tlpAlarmId might have wrapped. The number of rows in the table at any given time is reflected by the value of tlpAlarmsPresent. | 1.3.6.1.4.1.850.1.3.2 | not-accessible | current | |
| tlpAlarmEntry OBJECT-TYPE An entry containing information application to a particular alarm. | 1.3.6.1.4.1.850.1.3.2.1 | not-accessible | current | |
| tlpAlarmId OBJECT-TYPE A unique identifier for an alarm condition. This value will remain constant for the duration of the alarm condition. | 1.3.6.1.4.1.850.1.3.2.1.1 | Unsigned32 | read-only | current |
| tlpAlarmDescr OBJECT-TYPE A reference of the alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description for the alarm condition. The object referenced will be a well known alarm object associated with the device on which the alarm condition is active. | 1.3.6.1.4.1.850.1.3.2.1.2 | OBJECT IDENTIFIER | read-only | current |
| tlpAlarmTime OBJECT-TYPE The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of tlpAlarmsTime shall equal 0. | 1.3.6.1.4.1.850.1.3.2.1.3 | TimeStamp | read-only | current |
| tlpAlarmTableRef OBJECT-TYPE This value references the OID of a table object applicable to the alarm condition. This, in conjunction with the table row as defined by tlpAlarmTableRowRef, specifies the object/row within this table to which the alarm condition applies. Example 1 -- The following sample values will be returned for a UPS on battery: tlpAlarmId 28 tlpAlarmDescr tlpUpsAlarmOnBattery tlpAlarmTime 12345678 tlpAlarmTableRef tlpDeviceTable tlpAlarmTableRowRef tlpDeviceIndex.2 tlpAlarmDetail On Battery tlpAlarmType warning tlpAlarmState active tlpAlarmAcknowledged notAcknowledged In the above example, tlpAlarmTableRef references the device table and tlpAlarmTableRowRef references the 2nd managed device in that table. Example 2 -- The following sample values will be returned for a PDU with a load turned off: tlpAlarmId 46 tlpAlarmDescr tlpPduAlarmLoadOff tlpAlarmTime 12345678 tlpAlarmTableRef tlpPduOutletTable tlpAlarmTableRowRef tlpOutletIndex.1.4 tlpAlarmDetail Load Off tlpAlarmType warning tlpAlarmState active tlpAlarmAcknowledged acknowledged In the above example, tlpAlarmTableRef references the pdu outlet table and tlpAlarmTableRowRef references the 4th outlet on the 1st managed device. | 1.3.6.1.4.1.850.1.3.2.1.4 | OBJECT IDENTIFIER | read-only | current |
| tlpAlarmTableRowRef OBJECT-TYPE This value is used in conjunction with tlpAlarmTableRef to define the object associated with this alarm condition. See the description of tlpAlarmTableRef for more information. | 1.3.6.1.4.1.850.1.3.2.1.5 | OBJECT IDENTIFIER | read-only | current |
| tlpAlarmDetail OBJECT-TYPE A textual description of the alarm condition. | 1.3.6.1.4.1.850.1.3.2.1.6 | DisplayString | read-only | current |
| tlpAlarmType OBJECT-TYPE The category/group of this alarm. | 1.3.6.1.4.1.850.1.3.2.1.7 | INTEGER {critical(1), warning(2), info(3), status(4), offline(5), custom(6)} | read-only | current |
| tlpAlarmState OBJECT-TYPE The current state of this alarm condition. An active(1) alarm is a condition that currently exists. An inactive(2) alarm is a condition that no longer exists because the alarm either cleared or was resolved. Each alarm condition must be cleared and acknowledged before it is removed from this table (see tlpAlarmAcknowledged). | 1.3.6.1.4.1.850.1.3.2.1.8 | INTEGER {active(1), inactive(2)} | read-only | current |
| tlpAlarmAcknowledged OBJECT-TYPE Denotes whether the alarm condition has been acknowledged. The agent will return notAcknowledged(1) if the condition has not been acknowledged, or acknowledged(2) when acknowledged. Writing the value acknowledged(2) for an alarm acknowledges the alarm condition. Each alarm condition must be cleared and acknowledged before it is removed from this table; therefore, even if acknowledged, the alarm will remain in this table until the alarm becomes inactive as denoted by tlpAlarmState. | 1.3.6.1.4.1.850.1.3.2.1.9 | INTEGER {notAcknowledged(1), acknowledged(2)} | read-write | current |
| tlpAlarmsWellKnown OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3 | |||
| tlpAgentAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.1 | |||
| tlpAutoProbeAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.1.1 | |||
| tlpAutoProbeAlarm01 OBJECT-IDENTITY Auto Probe 1 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.1 | current | ||
| tlpAutoProbeAlarm02 OBJECT-IDENTITY Auto Probe 2 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.2 | current | ||
| tlpAutoProbeAlarm03 OBJECT-IDENTITY Auto Probe 3 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.3 | current | ||
| tlpAutoProbeAlarm04 OBJECT-IDENTITY Auto Probe 4 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.4 | current | ||
| tlpAutoProbeAlarm05 OBJECT-IDENTITY Auto Probe 5 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.5 | current | ||
| tlpAutoProbeAlarm06 OBJECT-IDENTITY Auto Probe 6 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.6 | current | ||
| tlpAutoProbeAlarm07 OBJECT-IDENTITY Auto Probe 7 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.7 | current | ||
| tlpAutoProbeAlarm08 OBJECT-IDENTITY Auto Probe 8 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.8 | current | ||
| tlpAutoProbeAlarm09 OBJECT-IDENTITY Auto Probe 9 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.9 | current | ||
| tlpAutoProbeAlarm10 OBJECT-IDENTITY Auto Probe 10 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.10 | current | ||
| tlpAutoProbeAlarm11 OBJECT-IDENTITY Auto Probe 11 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.11 | current | ||
| tlpAutoProbeAlarm12 OBJECT-IDENTITY Auto Probe 12 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.12 | current | ||
| tlpAutoProbeAlarm13 OBJECT-IDENTITY Auto Probe 13 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.13 | current | ||
| tlpAutoProbeAlarm14 OBJECT-IDENTITY Auto Probe 14 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.14 | current | ||
| tlpAutoProbeAlarm15 OBJECT-IDENTITY Auto Probe 15 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.15 | current | ||
| tlpAutoProbeAlarm16 OBJECT-IDENTITY Auto Probe 16 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.16 | current | ||
| tlpAutoProbeAlarm17 OBJECT-IDENTITY Auto Probe 17 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.17 | current | ||
| tlpAutoProbeAlarm18 OBJECT-IDENTITY Auto Probe 18 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.18 | current | ||
| tlpAutoProbeAlarm19 OBJECT-IDENTITY Auto Probe 19 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.19 | current | ||
| tlpAutoProbeAlarm20 OBJECT-IDENTITY Auto Probe 20 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.20 | current | ||
| tlpAutoProbeAlarm21 OBJECT-IDENTITY Auto Probe 21 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.21 | current | ||
| tlpAutoProbeAlarm22 OBJECT-IDENTITY Auto Probe 22 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.22 | current | ||
| tlpAutoProbeAlarm23 OBJECT-IDENTITY Auto Probe 23 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.23 | current | ||
| tlpAutoProbeAlarm24 OBJECT-IDENTITY Auto Probe 24 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.24 | current | ||
| tlpAutoProbeAlarm25 OBJECT-IDENTITY Auto Probe 25 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.25 | current | ||
| tlpAutoProbeAlarm26 OBJECT-IDENTITY Auto Probe 26 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.26 | current | ||
| tlpAutoProbeAlarm27 OBJECT-IDENTITY Auto Probe 27 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.27 | current | ||
| tlpAutoProbeAlarm28 OBJECT-IDENTITY Auto Probe 28 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.28 | current | ||
| tlpAutoProbeAlarm29 OBJECT-IDENTITY Auto Probe 29 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.29 | current | ||
| tlpAutoProbeAlarm30 OBJECT-IDENTITY Auto Probe 30 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.30 | current | ||
| tlpAutoProbeAlarm31 OBJECT-IDENTITY Auto Probe 31 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.31 | current | ||
| tlpAutoProbeAlarm32 OBJECT-IDENTITY Auto Probe 32 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.32 | current | ||
| tlpAutoProbeAlarm33 OBJECT-IDENTITY Auto Probe 33 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.33 | current | ||
| tlpAutoProbeAlarm34 OBJECT-IDENTITY Auto Probe 34 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.34 | current | ||
| tlpAutoProbeAlarm35 OBJECT-IDENTITY Auto Probe 35 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.35 | current | ||
| tlpAutoProbeAlarm36 OBJECT-IDENTITY Auto Probe 36 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.36 | current | ||
| tlpAutoProbeAlarm37 OBJECT-IDENTITY Auto Probe 37 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.37 | current | ||
| tlpAutoProbeAlarm38 OBJECT-IDENTITY Auto Probe 38 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.38 | current | ||
| tlpAutoProbeAlarm39 OBJECT-IDENTITY Auto Probe 39 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.39 | current | ||
| tlpAutoProbeAlarm40 OBJECT-IDENTITY Auto Probe 40 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.40 | current | ||
| tlpAutoProbeAlarm41 OBJECT-IDENTITY Auto Probe 41 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.41 | current | ||
| tlpAutoProbeAlarm42 OBJECT-IDENTITY Auto Probe 42 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.42 | current | ||
| tlpAutoProbeAlarm43 OBJECT-IDENTITY Auto Probe 43 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.43 | current | ||
| tlpAutoProbeAlarm44 OBJECT-IDENTITY Auto Probe 44 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.44 | current | ||
| tlpAutoProbeAlarm45 OBJECT-IDENTITY Auto Probe 45 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.45 | current | ||
| tlpAutoProbeAlarm46 OBJECT-IDENTITY Auto Probe 46 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.46 | current | ||
| tlpAutoProbeAlarm47 OBJECT-IDENTITY Auto Probe 47 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.47 | current | ||
| tlpAutoProbeAlarm48 OBJECT-IDENTITY Auto Probe 48 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.48 | current | ||
| tlpAutoProbeAlarm49 OBJECT-IDENTITY Auto Probe 49 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.49 | current | ||
| tlpAutoProbeAlarm50 OBJECT-IDENTITY Auto Probe 50 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.50 | current | ||
| tlpAutoProbeAlarm51 OBJECT-IDENTITY Auto Probe 51 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.51 | current | ||
| tlpAutoProbeAlarm52 OBJECT-IDENTITY Auto Probe 52 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.52 | current | ||
| tlpAutoProbeAlarm53 OBJECT-IDENTITY Auto Probe 53 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.53 | current | ||
| tlpAutoProbeAlarm54 OBJECT-IDENTITY Auto Probe 54 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.54 | current | ||
| tlpAutoProbeAlarm55 OBJECT-IDENTITY Auto Probe 55 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.55 | current | ||
| tlpAutoProbeAlarm56 OBJECT-IDENTITY Auto Probe 56 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.56 | current | ||
| tlpAutoProbeAlarm57 OBJECT-IDENTITY Auto Probe 57 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.57 | current | ||
| tlpAutoProbeAlarm58 OBJECT-IDENTITY Auto Probe 58 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.58 | current | ||
| tlpAutoProbeAlarm59 OBJECT-IDENTITY Auto Probe 59 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.59 | current | ||
| tlpAutoProbeAlarm60 OBJECT-IDENTITY Auto Probe 60 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.60 | current | ||
| tlpAutoProbeAlarm61 OBJECT-IDENTITY Auto Probe 61 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.61 | current | ||
| tlpAutoProbeAlarm62 OBJECT-IDENTITY Auto Probe 62 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.62 | current | ||
| tlpAutoProbeAlarm63 OBJECT-IDENTITY Auto Probe 63 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.63 | current | ||
| tlpAutoProbeAlarm64 OBJECT-IDENTITY Auto Probe 64 had failed | 1.3.6.1.4.1.850.1.3.3.1.1.64 | current | ||
| tlpDeviceAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.2 | |||
| tlpAlarmCommunicationsLost OBJECT-IDENTITY A problem has been encountered in the communications between the agent and the device. | 1.3.6.1.4.1.850.1.3.3.2.1 | current | ||
| tlpAlarmUserDefined OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.2.2 | |||
| tlpAlarmUserDefined01 OBJECT-IDENTITY User-defined event 1 is in alarm. | 1.3.6.1.4.1.850.1.3.3.2.2.1 | current | ||
| tlpAlarmUserDefined02 OBJECT-IDENTITY User-defined event 2 is in alarm. | 1.3.6.1.4.1.850.1.3.3.2.2.2 | current | ||
| tlpAlarmUserDefined03 OBJECT-IDENTITY User-defined event 3 is in alarm. | 1.3.6.1.4.1.850.1.3.3.2.2.3 | current | ||
| tlpAlarmUserDefined04 OBJECT-IDENTITY User-defined event 4 is in alarm. | 1.3.6.1.4.1.850.1.3.3.2.2.4 | current | ||
| tlpAlarmUserDefined05 OBJECT-IDENTITY User-defined event 5 is in alarm. | 1.3.6.1.4.1.850.1.3.3.2.2.5 | current | ||
| tlpAlarmUserDefined06 OBJECT-IDENTITY User-defined event 6 is in alarm. | 1.3.6.1.4.1.850.1.3.3.2.2.6 | current | ||
| tlpAlarmUserDefined07 OBJECT-IDENTITY User-defined event 7 is in alarm. | 1.3.6.1.4.1.850.1.3.3.2.2.7 | current | ||
| tlpAlarmUserDefined08 OBJECT-IDENTITY User-defined event 8 is in alarm. | 1.3.6.1.4.1.850.1.3.3.2.2.8 | current | ||
| tlpAlarmUserDefined09 OBJECT-IDENTITY User-defined event 9 is in alarm. | 1.3.6.1.4.1.850.1.3.3.2.2.9 | current | ||
| tlpAlarmInternalFirmwareError OBJECT-IDENTITY A problem has been encountered with the device firmware. | 1.3.6.1.4.1.850.1.3.3.2.3 | current | ||
| tlpAlarmDeviceEEPROMFault OBJECT-IDENTITY A problem has been encountered with the device EEPROM. | 1.3.6.1.4.1.850.1.3.3.2.4 | current | ||
| tlpUpsAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.3 | |||
| tlpUpsAlarmBatteryBad OBJECT-IDENTITY One or more batteries have been determined to require replacement. | 1.3.6.1.4.1.850.1.3.3.3.1 | current | ||
| tlpUpsAlarmOnBattery OBJECT-IDENTITY The UPS is drawing power from the batteries. | 1.3.6.1.4.1.850.1.3.3.3.2 | current | ||
| tlpUpsAlarmLowBattery OBJECT-IDENTITY The remaining battery charge is less than or equal to the percentage of capacity warning specified by tlpUpsConfigBatteryCapacityThreshold. | 1.3.6.1.4.1.850.1.3.3.3.3 | current | ||
| tlpUpsAlarmDepletedBattery OBJECT-IDENTITY The UPS will be unable to sustain the present load when and if the utility power is lost. | 1.3.6.1.4.1.850.1.3.3.3.4 | current | ||
| tlpUpsAlarmTempBad OBJECT-IDENTITY A temperature is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.3.5 | current | ||
| tlpUpsAlarmInputBad OBJECT-IDENTITY An input condition is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.3.6 | current | ||
| tlpUpsAlarmOutputBad OBJECT-IDENTITY An output condition (other than OutputOverload) is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.3.7 | current | ||
| tlpUpsAlarmOutputOverload OBJECT-IDENTITY The output load exceeds the UPS output capacity. | 1.3.6.1.4.1.850.1.3.3.3.8 | current | ||
| tlpUpsAlarmOnBypass OBJECT-IDENTITY The Bypass is presently engaged on the UPS. | 1.3.6.1.4.1.850.1.3.3.3.9 | current | ||
| tlpUpsAlarmBypassBad OBJECT-IDENTITY The Bypass is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.3.10 | current | ||
| tlpUpsAlarmOutputOffAsRequested OBJECT-IDENTITY The UPS has shutdown as requested, i.e., the output is off. | 1.3.6.1.4.1.850.1.3.3.3.11 | current | ||
| tlpUpsAlarmUpsOffAsRequested OBJECT-IDENTITY The entire UPS has shutdown as commanded. | 1.3.6.1.4.1.850.1.3.3.3.12 | current | ||
| tlpUpsAlarmChargerFailed OBJECT-IDENTITY An uncorrected problem has been detected within the UPS charger subsystem. | 1.3.6.1.4.1.850.1.3.3.3.13 | current | ||
| tlpUpsAlarmUpsOutputOff OBJECT-IDENTITY The output of the UPS is in the off state. | 1.3.6.1.4.1.850.1.3.3.3.14 | current | ||
| tlpUpsAlarmUpsSystemOff OBJECT-IDENTITY The UPS system is in the off state. | 1.3.6.1.4.1.850.1.3.3.3.15 | current | ||
| tlpUpsAlarmFanFailure OBJECT-IDENTITY The failure of one or more fans in the UPS has been detected. | 1.3.6.1.4.1.850.1.3.3.3.16 | current | ||
| tlpUpsAlarmFuseFailure OBJECT-IDENTITY The failure of one or more fuses has been detected. | 1.3.6.1.4.1.850.1.3.3.3.17 | current | ||
| tlpUpsAlarmGeneralFault OBJECT-IDENTITY A general fault in the UPS has been detected. | 1.3.6.1.4.1.850.1.3.3.3.18 | current | ||
| tlpUpsAlarmDiagnosticTestFailed OBJECT-IDENTITY The result of the last diagnostic test indicates a failure. | 1.3.6.1.4.1.850.1.3.3.3.19 | current | ||
| tlpUpsAlarmAwaitingPower OBJECT-IDENTITY The UPS output is off and the UPS is awaiting the return of input power. | 1.3.6.1.4.1.850.1.3.3.3.20 | current | ||
| tlpUpsAlarmShutdownPending OBJECT-IDENTITY A tlpUpsShutdownAfterDelay countdown is underway. | 1.3.6.1.4.1.850.1.3.3.3.21 | current | ||
| tlpUpsAlarmShutdownImminent OBJECT-IDENTITY The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. | 1.3.6.1.4.1.850.1.3.3.3.22 | current | ||
| tlpUpsAlarmLoadLevelAboveThreshold OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.3.23 | |||
| tlpUpsAlarmLoadLevelAboveThresholdTotal OBJECT-IDENTITY The total load level is above the designated threshold. | 1.3.6.1.4.1.850.1.3.3.3.23.1 | current | ||
| tlpUpsAlarmLoadLevelAboveThresholdPhase1 OBJECT-IDENTITY The load level on phase 1 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.3.23.2 | current | ||
| tlpUpsAlarmLoadLevelAboveThresholdPhase2 OBJECT-IDENTITY The load level on phase 2 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.3.23.3 | current | ||
| tlpUpsAlarmLoadLevelAboveThresholdPhase3 OBJECT-IDENTITY The load level on phase 3 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.3.23.4 | current | ||
| tlpUpsAlarmOutputCurrentChanged OBJECT-IDENTITY The output current changed from its last known value. | 1.3.6.1.4.1.850.1.3.3.3.24 | current | ||
| tlpUpsAlarmBatteryAgeAboveThreshold OBJECT-IDENTITY One or more batteries have been determined to require replacement. | 1.3.6.1.4.1.850.1.3.3.3.25 | current | ||
| tlpUpsAlarmLoadOff OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.3.26 | |||
| tlpUpsAlarmLoadOff01 OBJECT-IDENTITY Load 1 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.1 | current | ||
| tlpUpsAlarmLoadOff02 OBJECT-IDENTITY Load 2 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.2 | current | ||
| tlpUpsAlarmLoadOff03 OBJECT-IDENTITY Load 3 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.3 | current | ||
| tlpUpsAlarmLoadOff04 OBJECT-IDENTITY Load 4 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.4 | current | ||
| tlpUpsAlarmLoadOff05 OBJECT-IDENTITY Load 5 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.5 | current | ||
| tlpUpsAlarmLoadOff06 OBJECT-IDENTITY Load 6 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.6 | current | ||
| tlpUpsAlarmLoadOff07 OBJECT-IDENTITY Load 7 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.7 | current | ||
| tlpUpsAlarmLoadOff08 OBJECT-IDENTITY Load 8 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.8 | current | ||
| tlpUpsAlarmLoadOff09 OBJECT-IDENTITY Load 9 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.9 | current | ||
| tlpUpsAlarmLoadOff10 OBJECT-IDENTITY Load 10 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.10 | current | ||
| tlpUpsAlarmLoadOff11 OBJECT-IDENTITY Load 11 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.11 | current | ||
| tlpUpsAlarmLoadOff12 OBJECT-IDENTITY Load 12 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.12 | current | ||
| tlpUpsAlarmLoadOff13 OBJECT-IDENTITY Load 13 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.13 | current | ||
| tlpUpsAlarmLoadOff14 OBJECT-IDENTITY Load 14 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.14 | current | ||
| tlpUpsAlarmLoadOff15 OBJECT-IDENTITY Load 15 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.15 | current | ||
| tlpUpsAlarmLoadOff16 OBJECT-IDENTITY Load 16 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.16 | current | ||
| tlpUpsAlarmLoadOff17 OBJECT-IDENTITY Load 17 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.17 | current | ||
| tlpUpsAlarmLoadOff18 OBJECT-IDENTITY Load 18 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.18 | current | ||
| tlpUpsAlarmLoadOff19 OBJECT-IDENTITY Load 19 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.19 | current | ||
| tlpUpsAlarmLoadOff20 OBJECT-IDENTITY Load 20 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.20 | current | ||
| tlpUpsAlarmLoadOff21 OBJECT-IDENTITY Load 21 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.21 | current | ||
| tlpUpsAlarmLoadOff22 OBJECT-IDENTITY Load 22 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.22 | current | ||
| tlpUpsAlarmLoadOff23 OBJECT-IDENTITY Load 23 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.23 | current | ||
| tlpUpsAlarmLoadOff24 OBJECT-IDENTITY Load 24 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.24 | current | ||
| tlpUpsAlarmLoadOff25 OBJECT-IDENTITY Load 25 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.25 | current | ||
| tlpUpsAlarmLoadOff26 OBJECT-IDENTITY Load 26 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.26 | current | ||
| tlpUpsAlarmLoadOff27 OBJECT-IDENTITY Load 27 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.27 | current | ||
| tlpUpsAlarmLoadOff28 OBJECT-IDENTITY Load 28 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.28 | current | ||
| tlpUpsAlarmLoadOff29 OBJECT-IDENTITY Load 29 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.29 | current | ||
| tlpUpsAlarmLoadOff30 OBJECT-IDENTITY Load 30 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.30 | current | ||
| tlpUpsAlarmLoadOff31 OBJECT-IDENTITY Load 31 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.31 | current | ||
| tlpUpsAlarmLoadOff32 OBJECT-IDENTITY Load 32 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.32 | current | ||
| tlpUpsAlarmLoadOff33 OBJECT-IDENTITY Load 33 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.33 | current | ||
| tlpUpsAlarmLoadOff34 OBJECT-IDENTITY Load 34 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.34 | current | ||
| tlpUpsAlarmLoadOff35 OBJECT-IDENTITY Load 35 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.35 | current | ||
| tlpUpsAlarmLoadOff36 OBJECT-IDENTITY Load 36 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.36 | current | ||
| tlpUpsAlarmLoadOff37 OBJECT-IDENTITY Load 37 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.37 | current | ||
| tlpUpsAlarmLoadOff38 OBJECT-IDENTITY Load 38 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.38 | current | ||
| tlpUpsAlarmLoadOff39 OBJECT-IDENTITY Load 39 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.39 | current | ||
| tlpUpsAlarmLoadOff40 OBJECT-IDENTITY Load 40 is off. | 1.3.6.1.4.1.850.1.3.3.3.26.40 | current | ||
| tlpUpsAlarmCurrentAboveThreshold OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.3.27 | |||
| tlpUpsAlarmCurrentAboveThreshold1 OBJECT-IDENTITY The output current on phase 1 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.3.27.1 | current | ||
| tlpUpsAlarmCurrentAboveThreshold2 OBJECT-IDENTITY The output current on phase 2 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.3.27.2 | current | ||
| tlpUpsAlarmCurrentAboveThreshold3 OBJECT-IDENTITY The output current on phase 3 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.3.27.3 | current | ||
| tlpUpsAlarmRuntimeBelowWarningLevel OBJECT-IDENTITY The battery seconds remaining is below warning level. | 1.3.6.1.4.1.850.1.3.3.3.28 | current | ||
| tlpUpsAlarmBusStartVoltageLow OBJECT-IDENTITY The inverter start up bus voltage is too low. | 1.3.6.1.4.1.850.1.3.3.3.29 | current | ||
| tlpUpsAlarmBusOverVoltage OBJECT-IDENTITY The inverter bus voltage is too high. | 1.3.6.1.4.1.850.1.3.3.3.30 | current | ||
| tlpUpsAlarmBusUnderVoltage OBJECT-IDENTITY The inverter bus voltage is too low. | 1.3.6.1.4.1.850.1.3.3.3.31 | current | ||
| tlpUpsAlarmBusVoltageUnbalanced OBJECT-IDENTITY The inverter bus voltage is not balanced. | 1.3.6.1.4.1.850.1.3.3.3.32 | current | ||
| tlpUpsAlarmInverterSoftStartBad OBJECT-IDENTITY The inverter bus voltage cannot reach desired voltage within a specified duration. | 1.3.6.1.4.1.850.1.3.3.3.33 | current | ||
| tlpUpsAlarmInverterOverVoltage OBJECT-IDENTITY The inverter voltage is too high. | 1.3.6.1.4.1.850.1.3.3.3.34 | current | ||
| tlpUpsAlarmInverterUnderVoltage OBJECT-IDENTITY The inverter voltage is too low. | 1.3.6.1.4.1.850.1.3.3.3.35 | current | ||
| tlpUpsAlarmInverterCircuitBad OBJECT-IDENTITY The inverter output is shorted. | 1.3.6.1.4.1.850.1.3.3.3.36 | current | ||
| tlpUpsAlarmBatteryOverVoltage OBJECT-IDENTITY The battery voltage is too high. | 1.3.6.1.4.1.850.1.3.3.3.37 | current | ||
| tlpUpsAlarmBatteryUnderVoltage OBJECT-IDENTITY The battery voltage is too low. | 1.3.6.1.4.1.850.1.3.3.3.38 | current | ||
| tlpUpsAlarmSiteWiringFault OBJECT-IDENTITY The utility input wiring is faulty. | 1.3.6.1.4.1.850.1.3.3.3.39 | current | ||
| tlpUpsAlarmOverTemperatureProtection OBJECT-IDENTITY The over temperature protection is activated. | 1.3.6.1.4.1.850.1.3.3.3.40 | current | ||
| tlpUpsAlarmOverCharged OBJECT-IDENTITY The UPS is over charged. | 1.3.6.1.4.1.850.1.3.3.3.41 | current | ||
| tlpUpsAlarmEPOActive OBJECT-IDENTITY The EPO is currently activated. | 1.3.6.1.4.1.850.1.3.3.3.42 | current | ||
| tlpUpsAlarmBypassFrequencyBad OBJECT-IDENTITY The bypass frequency is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.3.43 | current | ||
| tlpUpsAlarmExternalSmartBatteryAgeAboveThreshold OBJECT-IDENTITY One or more external smart batteries have been determined to require replacement. | 1.3.6.1.4.1.850.1.3.3.3.44 | current | ||
| tlpUpsAlarmExternalNonSmartBatteryAgeAboveThreshold OBJECT-IDENTITY One or more external non-smart batteries have been determined to require replacement. | 1.3.6.1.4.1.850.1.3.3.3.45 | current | ||
| tlpUpsAlarmSmartBatteryCommLost OBJECT-IDENTITY Communications with the smart batteries was lost. | 1.3.6.1.4.1.850.1.3.3.3.46 | current | ||
| tlpUpsAlarmLoadsNotAllOn OBJECT-IDENTITY One of more loads are not on. | 1.3.6.1.4.1.850.1.3.3.3.47 | current | ||
| tlpUpsAlarmBatteryTemperatureHigh OBJECT-IDENTITY The battery temperature is high. | 1.3.6.1.4.1.850.1.3.3.3.48 | current | ||
| tlpUpsAlarmBatteryTemperatureLow OBJECT-IDENTITY The battery temperature is low. | 1.3.6.1.4.1.850.1.3.3.3.49 | current | ||
| tlpUpsAlarmBatteryDisconnected OBJECT-IDENTITY The battery disconnected. | 1.3.6.1.4.1.850.1.3.3.3.50 | current | ||
| tlpUpsAlarmBatteryTemperatureSensorDisconnected OBJECT-IDENTITY The battery temperature sensor disconnected. | 1.3.6.1.4.1.850.1.3.3.3.51 | current | ||
| tlpUpsAlarmTemperatureDerating OBJECT-IDENTITY Power derating due to high environment temperature. | 1.3.6.1.4.1.850.1.3.3.3.52 | current | ||
| tlpUpsAlarmInputContact OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.3.53 | |||
| tlpUpsAlarmInputContact1 OBJECT-IDENTITY Input contact 1 in alarm. | 1.3.6.1.4.1.850.1.3.3.3.53.1 | current | ||
| tlpUpsAlarmOutputContact OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.3.54 | |||
| tlpUpsAlarmOutputContact1 OBJECT-IDENTITY Output contact 1 in alarm. | 1.3.6.1.4.1.850.1.3.3.3.54.1 | current | ||
| tlpUpsAlarmOutputContact2 OBJECT-IDENTITY Output contact 2 in alarm. | 1.3.6.1.4.1.850.1.3.3.3.54.2 | current | ||
| tlpUpsAlarmOutputContact3 OBJECT-IDENTITY Output contact 3 in alarm. | 1.3.6.1.4.1.850.1.3.3.3.54.3 | current | ||
| tlpUpsAlarmOutputContact4 OBJECT-IDENTITY Output contact 4 in alarm. | 1.3.6.1.4.1.850.1.3.3.3.54.4 | current | ||
| tlpUpsAlarmOutputContact5 OBJECT-IDENTITY Output contact 5 in alarm. | 1.3.6.1.4.1.850.1.3.3.3.54.5 | current | ||
| tlpUpsAlarmOutputContact6 OBJECT-IDENTITY Output contact 6 in alarm. | 1.3.6.1.4.1.850.1.3.3.3.54.6 | current | ||
| tlpPduAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.4 | |||
| tlpPduAlarmLoadLevelAboveThreshold OBJECT-IDENTITY The load level is above the designated threshold. | 1.3.6.1.4.1.850.1.3.3.4.1 | current | ||
| tlpPduAlarmInputBad OBJECT-IDENTITY An input condition is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.4.2 | current | ||
| tlpPduAlarmOutputBad OBJECT-IDENTITY An output condition (other than OutputOverload) is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.4.3 | current | ||
| tlpPduAlarmOutputOverload OBJECT-IDENTITY The output load exceeds the pdu output capacity. | 1.3.6.1.4.1.850.1.3.3.4.4 | current | ||
| tlpPduAlarmOutputOff OBJECT-IDENTITY The output of the pdu is in the off state. | 1.3.6.1.4.1.850.1.3.3.4.5 | current | ||
| tlpPduAlarmLoadOff OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.4.6 | |||
| tlpPduAlarmLoadOff01 OBJECT-IDENTITY Load 1 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.1 | current | ||
| tlpPduAlarmLoadOff02 OBJECT-IDENTITY Load 2 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.2 | current | ||
| tlpPduAlarmLoadOff03 OBJECT-IDENTITY Load 3 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.3 | current | ||
| tlpPduAlarmLoadOff04 OBJECT-IDENTITY Load 4 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.4 | current | ||
| tlpPduAlarmLoadOff05 OBJECT-IDENTITY Load 5 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.5 | current | ||
| tlpPduAlarmLoadOff06 OBJECT-IDENTITY Load 6 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.6 | current | ||
| tlpPduAlarmLoadOff07 OBJECT-IDENTITY Load 7 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.7 | current | ||
| tlpPduAlarmLoadOff08 OBJECT-IDENTITY Load 8 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.8 | current | ||
| tlpPduAlarmLoadOff09 OBJECT-IDENTITY Load 9 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.9 | current | ||
| tlpPduAlarmLoadOff10 OBJECT-IDENTITY Load 10 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.10 | current | ||
| tlpPduAlarmLoadOff11 OBJECT-IDENTITY Load 11 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.11 | current | ||
| tlpPduAlarmLoadOff12 OBJECT-IDENTITY Load 12 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.12 | current | ||
| tlpPduAlarmLoadOff13 OBJECT-IDENTITY Load 13 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.13 | current | ||
| tlpPduAlarmLoadOff14 OBJECT-IDENTITY Load 14 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.14 | current | ||
| tlpPduAlarmLoadOff15 OBJECT-IDENTITY Load 15 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.15 | current | ||
| tlpPduAlarmLoadOff16 OBJECT-IDENTITY Load 16 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.16 | current | ||
| tlpPduAlarmLoadOff17 OBJECT-IDENTITY Load 17 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.17 | current | ||
| tlpPduAlarmLoadOff18 OBJECT-IDENTITY Load 18 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.18 | current | ||
| tlpPduAlarmLoadOff19 OBJECT-IDENTITY Load 19 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.19 | current | ||
| tlpPduAlarmLoadOff20 OBJECT-IDENTITY Load 20 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.20 | current | ||
| tlpPduAlarmLoadOff21 OBJECT-IDENTITY Load 21 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.21 | current | ||
| tlpPduAlarmLoadOff22 OBJECT-IDENTITY Load 22 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.22 | current | ||
| tlpPduAlarmLoadOff23 OBJECT-IDENTITY Load 23 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.23 | current | ||
| tlpPduAlarmLoadOff24 OBJECT-IDENTITY Load 24 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.24 | current | ||
| tlpPduAlarmLoadOff25 OBJECT-IDENTITY Load 25 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.25 | current | ||
| tlpPduAlarmLoadOff26 OBJECT-IDENTITY Load 26 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.26 | current | ||
| tlpPduAlarmLoadOff27 OBJECT-IDENTITY Load 27 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.27 | current | ||
| tlpPduAlarmLoadOff28 OBJECT-IDENTITY Load 28 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.28 | current | ||
| tlpPduAlarmLoadOff29 OBJECT-IDENTITY Load 29 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.29 | current | ||
| tlpPduAlarmLoadOff30 OBJECT-IDENTITY Load 30 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.30 | current | ||
| tlpPduAlarmLoadOff31 OBJECT-IDENTITY Load 31 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.31 | current | ||
| tlpPduAlarmLoadOff32 OBJECT-IDENTITY Load 32 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.32 | current | ||
| tlpPduAlarmLoadOff33 OBJECT-IDENTITY Load 33 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.33 | current | ||
| tlpPduAlarmLoadOff34 OBJECT-IDENTITY Load 34 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.34 | current | ||
| tlpPduAlarmLoadOff35 OBJECT-IDENTITY Load 35 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.35 | current | ||
| tlpPduAlarmLoadOff36 OBJECT-IDENTITY Load 36 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.36 | current | ||
| tlpPduAlarmLoadOff37 OBJECT-IDENTITY Load 37 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.37 | current | ||
| tlpPduAlarmLoadOff38 OBJECT-IDENTITY Load 38 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.38 | current | ||
| tlpPduAlarmLoadOff39 OBJECT-IDENTITY Load 39 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.39 | current | ||
| tlpPduAlarmLoadOff40 OBJECT-IDENTITY Load 40 is off. | 1.3.6.1.4.1.850.1.3.3.4.6.40 | current | ||
| tlpPduAlarmCircuitBreakerOpen OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.4.7 | |||
| tlpPduAlarmCircuitBreakerOpen01 OBJECT-IDENTITY Circuit breaker 1 is open. | 1.3.6.1.4.1.850.1.3.3.4.7.1 | current | ||
| tlpPduAlarmCircuitBreakerOpen02 OBJECT-IDENTITY Circuit breaker 2 is open. | 1.3.6.1.4.1.850.1.3.3.4.7.2 | current | ||
| tlpPduAlarmCircuitBreakerOpen03 OBJECT-IDENTITY Circuit breaker 3 is open. | 1.3.6.1.4.1.850.1.3.3.4.7.3 | current | ||
| tlpPduAlarmCircuitBreakerOpen04 OBJECT-IDENTITY Circuit breaker 4 is open. | 1.3.6.1.4.1.850.1.3.3.4.7.4 | current | ||
| tlpPduAlarmCircuitBreakerOpen05 OBJECT-IDENTITY Circuit breaker 5 is open. | 1.3.6.1.4.1.850.1.3.3.4.7.5 | current | ||
| tlpPduAlarmCircuitBreakerOpen06 OBJECT-IDENTITY Circuit breaker 6 is open. | 1.3.6.1.4.1.850.1.3.3.4.7.6 | current | ||
| tlpPduAlarmCurrentAboveThreshold OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.4.8 | |||
| tlpPduAlarmCurrentAboveThreshold1 OBJECT-IDENTITY The output current on phase 1 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.4.8.1 | current | ||
| tlpPduAlarmCurrentAboveThreshold2 OBJECT-IDENTITY The output current on phase 2 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.4.8.2 | current | ||
| tlpPduAlarmCurrentAboveThreshold3 OBJECT-IDENTITY The output current on phase 3 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.4.8.3 | current | ||
| tlpPduAlarmLoadsNotAllOn OBJECT-IDENTITY One of more loads are not on. | 1.3.6.1.4.1.850.1.3.3.4.9 | current | ||
| tlpPduAlarmLoadLevelBelowThreshold OBJECT-IDENTITY The load level is below the designated threshold. | 1.3.6.1.4.1.850.1.3.3.4.10 | current | ||
| tlpPduAlarmCurrentBelowThreshold OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.4.11 | |||
| tlpPduAlarmCurrentBelowThreshold1 OBJECT-IDENTITY The output current on phase 1 below load limits. | 1.3.6.1.4.1.850.1.3.3.4.11.1 | current | ||
| tlpPduAlarmCurrentBelowThreshold2 OBJECT-IDENTITY The output current on phase 2 below load limits. | 1.3.6.1.4.1.850.1.3.3.4.11.2 | current | ||
| tlpPduAlarmCurrentBelowThreshold3 OBJECT-IDENTITY The output current on phase 3 below load limits. | 1.3.6.1.4.1.850.1.3.3.4.11.3 | current | ||
| tlpEnvAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.5 | |||
| tlpEnvAlarmTemperatureBeyondLimits OBJECT-IDENTITY The temperature exceeds limits. | 1.3.6.1.4.1.850.1.3.3.5.1 | current | ||
| tlpEnvAlarmHumidityBeyondLimits OBJECT-IDENTITY The humidity exceeds limits. | 1.3.6.1.4.1.850.1.3.3.5.2 | current | ||
| tlpEnvAlarmInputContact OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.5.3 | |||
| tlpEnvAlarmInputContact01 OBJECT-IDENTITY Input contact 1 is in alarm. | 1.3.6.1.4.1.850.1.3.3.5.3.1 | current | ||
| tlpEnvAlarmInputContact02 OBJECT-IDENTITY Input contact 2 is in alarm. | 1.3.6.1.4.1.850.1.3.3.5.3.2 | current | ||
| tlpEnvAlarmInputContact03 OBJECT-IDENTITY Input contact 3 is in alarm. | 1.3.6.1.4.1.850.1.3.3.5.3.3 | current | ||
| tlpEnvAlarmInputContact04 OBJECT-IDENTITY Input contact 4 is in alarm. | 1.3.6.1.4.1.850.1.3.3.5.3.4 | current | ||
| tlpEnvAlarmOutputContact OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.5.4 | |||
| tlpEnvAlarmOutputContact01 OBJECT-IDENTITY Output contact 1 is in alarm. | 1.3.6.1.4.1.850.1.3.3.5.4.1 | current | ||
| tlpEnvAlarmOutputContact02 OBJECT-IDENTITY Output contact 2 is in alarm. | 1.3.6.1.4.1.850.1.3.3.5.4.2 | current | ||
| tlpEnvAlarmOutputContact03 OBJECT-IDENTITY Output contact 3 is in alarm. | 1.3.6.1.4.1.850.1.3.3.5.4.3 | current | ||
| tlpEnvAlarmOutputContact04 OBJECT-IDENTITY Output contact 4 is in alarm. | 1.3.6.1.4.1.850.1.3.3.5.4.4 | current | ||
| tlpAtsAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.6 | |||
| tlpAtsAlarmOutage OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.6.1 | |||
| tlpAtsAlarmSource1Outage OBJECT-IDENTITY Input on source 1 is not present. For atss with the designation of primary and secondary, this alarm denotes input on the primary source is not present. | 1.3.6.1.4.1.850.1.3.3.6.1.1 | current | ||
| tlpAtsAlarmSource2Outage OBJECT-IDENTITY Input on source 2 is not present. For atss with the designation of primary and secondary, this alarm denotes input on the secondary source is not present. | 1.3.6.1.4.1.850.1.3.3.6.1.2 | current | ||
| tlpAtsAlarmTemperature OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.6.2 | |||
| tlpAtsAlarmSystemTemperature OBJECT-IDENTITY The system temperature is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.2.1 | current | ||
| tlpAtsAlarmSource1Temperature OBJECT-IDENTITY The source 1 temperature is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.2.2 | current | ||
| tlpAtsAlarmSource2Temperature OBJECT-IDENTITY The source 2 temperature is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.2.3 | current | ||
| tlpAtsAlarmLoadLevelAboveThreshold OBJECT-IDENTITY The load level is above the designated threshold. | 1.3.6.1.4.1.850.1.3.3.6.3 | current | ||
| tlpAtsAlarmInputBad OBJECT-IDENTITY An input condition is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.4 | current | ||
| tlpAtsAlarmOutputBad OBJECT-IDENTITY An output condition (other than OutputOverload) is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.5 | current | ||
| tlpAtsAlarmOutputOverload OBJECT-IDENTITY The output load exceeds the ats output capacity. | 1.3.6.1.4.1.850.1.3.3.6.6 | current | ||
| tlpAtsAlarmOutputOff OBJECT-IDENTITY The output of the ats is in the off state. | 1.3.6.1.4.1.850.1.3.3.6.7 | current | ||
| tlpAtsAlarmLoadOff OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.6.8 | |||
| tlpAtsAlarmLoadOff01 OBJECT-IDENTITY Load 1 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.1 | current | ||
| tlpAtsAlarmLoadOff02 OBJECT-IDENTITY Load 2 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.2 | current | ||
| tlpAtsAlarmLoadOff03 OBJECT-IDENTITY Load 3 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.3 | current | ||
| tlpAtsAlarmLoadOff04 OBJECT-IDENTITY Load 4 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.4 | current | ||
| tlpAtsAlarmLoadOff05 OBJECT-IDENTITY Load 5 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.5 | current | ||
| tlpAtsAlarmLoadOff06 OBJECT-IDENTITY Load 6 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.6 | current | ||
| tlpAtsAlarmLoadOff07 OBJECT-IDENTITY Load 7 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.7 | current | ||
| tlpAtsAlarmLoadOff08 OBJECT-IDENTITY Load 8 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.8 | current | ||
| tlpAtsAlarmLoadOff09 OBJECT-IDENTITY Load 9 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.9 | current | ||
| tlpAtsAlarmLoadOff10 OBJECT-IDENTITY Load 10 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.10 | current | ||
| tlpAtsAlarmLoadOff11 OBJECT-IDENTITY Load 11 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.11 | current | ||
| tlpAtsAlarmLoadOff12 OBJECT-IDENTITY Load 12 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.12 | current | ||
| tlpAtsAlarmLoadOff13 OBJECT-IDENTITY Load 13 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.13 | current | ||
| tlpAtsAlarmLoadOff14 OBJECT-IDENTITY Load 14 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.14 | current | ||
| tlpAtsAlarmLoadOff15 OBJECT-IDENTITY Load 15 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.15 | current | ||
| tlpAtsAlarmLoadOff16 OBJECT-IDENTITY Load 16 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.16 | current | ||
| tlpAtsAlarmLoadOff17 OBJECT-IDENTITY Load 17 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.17 | current | ||
| tlpAtsAlarmLoadOff18 OBJECT-IDENTITY Load 18 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.18 | current | ||
| tlpAtsAlarmLoadOff19 OBJECT-IDENTITY Load 19 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.19 | current | ||
| tlpAtsAlarmLoadOff20 OBJECT-IDENTITY Load 20 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.20 | current | ||
| tlpAtsAlarmLoadOff21 OBJECT-IDENTITY Load 21 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.21 | current | ||
| tlpAtsAlarmLoadOff22 OBJECT-IDENTITY Load 22 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.22 | current | ||
| tlpAtsAlarmLoadOff23 OBJECT-IDENTITY Load 23 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.23 | current | ||
| tlpAtsAlarmLoadOff24 OBJECT-IDENTITY Load 24 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.24 | current | ||
| tlpAtsAlarmLoadOff25 OBJECT-IDENTITY Load 25 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.25 | current | ||
| tlpAtsAlarmLoadOff26 OBJECT-IDENTITY Load 26 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.26 | current | ||
| tlpAtsAlarmLoadOff27 OBJECT-IDENTITY Load 27 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.27 | current | ||
| tlpAtsAlarmLoadOff28 OBJECT-IDENTITY Load 28 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.28 | current | ||
| tlpAtsAlarmLoadOff29 OBJECT-IDENTITY Load 29 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.29 | current | ||
| tlpAtsAlarmLoadOff30 OBJECT-IDENTITY Load 30 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.30 | current | ||
| tlpAtsAlarmLoadOff31 OBJECT-IDENTITY Load 31 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.31 | current | ||
| tlpAtsAlarmLoadOff32 OBJECT-IDENTITY Load 32 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.32 | current | ||
| tlpAtsAlarmLoadOff33 OBJECT-IDENTITY Load 33 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.33 | current | ||
| tlpAtsAlarmLoadOff34 OBJECT-IDENTITY Load 34 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.34 | current | ||
| tlpAtsAlarmLoadOff35 OBJECT-IDENTITY Load 35 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.35 | current | ||
| tlpAtsAlarmLoadOff36 OBJECT-IDENTITY Load 36 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.36 | current | ||
| tlpAtsAlarmLoadOff37 OBJECT-IDENTITY Load 37 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.37 | current | ||
| tlpAtsAlarmLoadOff38 OBJECT-IDENTITY Load 38 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.38 | current | ||
| tlpAtsAlarmLoadOff39 OBJECT-IDENTITY Load 39 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.39 | current | ||
| tlpAtsAlarmLoadOff40 OBJECT-IDENTITY Load 40 is off. | 1.3.6.1.4.1.850.1.3.3.6.8.40 | current | ||
| tlpAtsAlarmCircuitBreakerOpen OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.6.9 | |||
| tlpAtsAlarmCircuitBreakerOpen01 OBJECT-IDENTITY Circuit breaker 1 is open. | 1.3.6.1.4.1.850.1.3.3.6.9.1 | current | ||
| tlpAtsAlarmCircuitBreakerOpen02 OBJECT-IDENTITY Circuit breaker 2 is open. | 1.3.6.1.4.1.850.1.3.3.6.9.2 | current | ||
| tlpAtsAlarmCircuitBreakerOpen03 OBJECT-IDENTITY Circuit breaker 3 is open. | 1.3.6.1.4.1.850.1.3.3.6.9.3 | current | ||
| tlpAtsAlarmCircuitBreakerOpen04 OBJECT-IDENTITY Circuit breaker 4 is open. | 1.3.6.1.4.1.850.1.3.3.6.9.4 | current | ||
| tlpAtsAlarmCircuitBreakerOpen05 OBJECT-IDENTITY Circuit breaker 5 is open. | 1.3.6.1.4.1.850.1.3.3.6.9.5 | current | ||
| tlpAtsAlarmCircuitBreakerOpen06 OBJECT-IDENTITY Circuit breaker 6 is open. | 1.3.6.1.4.1.850.1.3.3.6.9.6 | current | ||
| tlpAtsAlarmCurrentAboveThreshold OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.6.10 | |||
| tlpAtsAlarmCurrentAboveThresholdA1 OBJECT-IDENTITY The output current on input source 1 phase 1 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.6.10.1 | current | ||
| tlpAtsAlarmCurrentAboveThresholdA2 OBJECT-IDENTITY The output current on input source 1 phase 2 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.6.10.2 | current | ||
| tlpAtsAlarmCurrentAboveThresholdA3 OBJECT-IDENTITY The output current on input source 1 phase 3 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.6.10.3 | current | ||
| tlpAtsAlarmCurrentAboveThresholdB1 OBJECT-IDENTITY The output current on input source 2 phase 1 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.6.10.4 | current | ||
| tlpAtsAlarmCurrentAboveThresholdB2 OBJECT-IDENTITY The output current on input source 2 phase 2 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.6.10.5 | current | ||
| tlpAtsAlarmCurrentAboveThresholdB3 OBJECT-IDENTITY The output current on input source 2 phase 3 exceeds load limits. | 1.3.6.1.4.1.850.1.3.3.6.10.6 | current | ||
| tlpAtsAlarmLoadsNotAllOn OBJECT-IDENTITY One of more loads are not on. | 1.3.6.1.4.1.850.1.3.3.6.11 | current | ||
| tlpAtsAlarmGeneralFault OBJECT-IDENTITY A general fault in the ats has been detected. | 1.3.6.1.4.1.850.1.3.3.6.12 | current | ||
| tlpAtsAlarmVoltage OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.6.13 | |||
| tlpAtsAlarmOverVoltage OBJECT-IDENTITY The input voltage is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.13.1 | current | ||
| tlpAtsAlarmSource1OverVoltage OBJECT-IDENTITY The voltage on source 1 is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.13.2 | current | ||
| tlpAtsAlarmSource2OverVoltage OBJECT-IDENTITY The voltage on source 2 is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.13.3 | current | ||
| tlpAtsAlarmFrequency OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.6.14 | |||
| tlpAtsAlarmSource1InvalidFrequency OBJECT-IDENTITY The voltage on source 1 is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.14.1 | current | ||
| tlpAtsAlarmSource2InvalidFrequency OBJECT-IDENTITY The voltage on source 2 is out of tolerance. | 1.3.6.1.4.1.850.1.3.3.6.14.2 | current | ||
| tlpAtsAlarmLoadLevelBelowThreshold OBJECT-IDENTITY The load level is below the designated threshold. | 1.3.6.1.4.1.850.1.3.3.6.15 | current | ||
| tlpAtsAlarmCurrentBelowThreshold OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.6.16 | |||
| tlpAtsAlarmCurrentBelowThresholdA1 OBJECT-IDENTITY The output current on input source 1 phase 1 below load limits. | 1.3.6.1.4.1.850.1.3.3.6.16.1 | current | ||
| tlpAtsAlarmCurrentBelowThresholdA2 OBJECT-IDENTITY The output current on input source 1 phase 2 below load limits. | 1.3.6.1.4.1.850.1.3.3.6.16.2 | current | ||
| tlpAtsAlarmCurrentBelowThresholdA3 OBJECT-IDENTITY The output current on input source 1 phase 3 below load limits. | 1.3.6.1.4.1.850.1.3.3.6.16.3 | current | ||
| tlpAtsAlarmCurrentBelowThresholdB1 OBJECT-IDENTITY The output current on input source 2 phase 1 below load limits. | 1.3.6.1.4.1.850.1.3.3.6.16.4 | current | ||
| tlpAtsAlarmCurrentBelowThresholdB2 OBJECT-IDENTITY The output current on input source 2 phase 2 below load limits. | 1.3.6.1.4.1.850.1.3.3.6.16.5 | current | ||
| tlpAtsAlarmCurrentBelowThresholdB3 OBJECT-IDENTITY The output current on input source 2 phase 3 below load limits. | 1.3.6.1.4.1.850.1.3.3.6.16.6 | current | ||
| tlpCoolingAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.7 | |||
| tlpCoolingAlarmSupplyAirSensorFault OBJECT-IDENTITY The supply air sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.1 | current | ||
| tlpCoolingAlarmReturnAirSensorFault OBJECT-IDENTITY The return air sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.2 | current | ||
| tlpCoolingAlarmCondenserInletAirSensorFault OBJECT-IDENTITY The condenser inlet air sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.3 | current | ||
| tlpCoolingAlarmCondenserOutletAirSensorFault OBJECT-IDENTITY The condenser outlet air sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.4 | current | ||
| tlpCoolingAlarmSuctionTemperatureSensorFault OBJECT-IDENTITY The suction temperature sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.5 | current | ||
| tlpCoolingAlarmEvaporatorTemperatureSensorFault OBJECT-IDENTITY The evaporator temperature sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.6 | current | ||
| tlpCoolingAlarmAirFilterClogged OBJECT-IDENTITY The air filter is clogged. | 1.3.6.1.4.1.850.1.3.3.7.7 | current | ||
| tlpCoolingAlarmAirFilterRunHoursViolation OBJECT-IDENTITY The air filter run hours was violated. | 1.3.6.1.4.1.850.1.3.3.7.8 | current | ||
| tlpCoolingAlarmSuctionPressureSensorFault OBJECT-IDENTITY The suction pressure sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.9 | current | ||
| tlpCoolingAlarmInverterCommunicationsFault OBJECT-IDENTITY The inverter communications is in fault. | 1.3.6.1.4.1.850.1.3.3.7.10 | current | ||
| tlpCoolingAlarmRemoteShutdownViaInputContact OBJECT-IDENTITY A remote shutdown was triggerd by an input contact. | 1.3.6.1.4.1.850.1.3.3.7.11 | current | ||
| tlpCoolingAlarmCondensatePumpFault OBJECT-IDENTITY The condensate pump is in fault. | 1.3.6.1.4.1.850.1.3.3.7.12 | current | ||
| tlpCoolingAlarmLowRefrigerantStartupFault OBJECT-IDENTITY The low refrigerant startup is in fault. | 1.3.6.1.4.1.850.1.3.3.7.13 | current | ||
| tlpCoolingAlarmCondenserFanFault OBJECT-IDENTITY The condenser fan is in fault. | 1.3.6.1.4.1.850.1.3.3.7.14 | current | ||
| tlpCoolingAlarmCondenserFailure OBJECT-IDENTITY The condenser has failed. | 1.3.6.1.4.1.850.1.3.3.7.15 | current | ||
| tlpCoolingAlarmEvaporatorCoolingFailure OBJECT-IDENTITY The evaporator cooling is in fault. | 1.3.6.1.4.1.850.1.3.3.7.16 | current | ||
| tlpCoolingAlarmReturnAirTempHigh OBJECT-IDENTITY The return air temperature is high. | 1.3.6.1.4.1.850.1.3.3.7.17 | current | ||
| tlpCoolingAlarmSupplyAirTempHigh OBJECT-IDENTITY The supply air temperature is high. | 1.3.6.1.4.1.850.1.3.3.7.18 | current | ||
| tlpCoolingAlarmEvaporatorFailure OBJECT-IDENTITY The evaporator has failed. | 1.3.6.1.4.1.850.1.3.3.7.19 | current | ||
| tlpCoolingAlarmEvaporatorFreezeUp OBJECT-IDENTITY The evaporator is frozen. | 1.3.6.1.4.1.850.1.3.3.7.20 | current | ||
| tlpCoolingAlarmDischargePressureHigh OBJECT-IDENTITY The discharge pressure is high. | 1.3.6.1.4.1.850.1.3.3.7.21 | current | ||
| tlpCoolingAlarmPressureGaugeFailure OBJECT-IDENTITY The pressure gauge has failed. | 1.3.6.1.4.1.850.1.3.3.7.22 | current | ||
| tlpCoolingAlarmDischargePressurePersistentHigh OBJECT-IDENTITY The discharge pressure is persistently high. | 1.3.6.1.4.1.850.1.3.3.7.23 | current | ||
| tlpCoolingAlarmSuctionPressureLowStartFailure OBJECT-IDENTITY Cannot start due to low suction pressure. | 1.3.6.1.4.1.850.1.3.3.7.24 | current | ||
| tlpCoolingAlarmSuctionPressureLow OBJECT-IDENTITY The suction pressure is low. | 1.3.6.1.4.1.850.1.3.3.7.25 | current | ||
| tlpCoolingAlarmSuctionPressurePersistentLow OBJECT-IDENTITY The suction pressure is persistently low. | 1.3.6.1.4.1.850.1.3.3.7.26 | current | ||
| tlpCoolingAlarmStartupLinePressureImbalance OBJECT-IDENTITY The startup line pressure is in imbalance. | 1.3.6.1.4.1.850.1.3.3.7.27 | current | ||
| tlpCoolingAlarmCompressorFailure OBJECT-IDENTITY The compressor has failed. | 1.3.6.1.4.1.850.1.3.3.7.28 | current | ||
| tlpCoolingAlarmCurrentLimit OBJECT-IDENTITY The current is out of range. | 1.3.6.1.4.1.850.1.3.3.7.29 | current | ||
| tlpCoolingAlarmWaterLeak OBJECT-IDENTITY Water is leaking. | 1.3.6.1.4.1.850.1.3.3.7.30 | current | ||
| tlpCoolingAlarmFanUnderCurrent OBJECT-IDENTITY The fan is under current. | 1.3.6.1.4.1.850.1.3.3.7.31 | current | ||
| tlpCoolingAlarmFanOverCurrent OBJECT-IDENTITY The fan is over current. | 1.3.6.1.4.1.850.1.3.3.7.32 | current | ||
| tlpCoolingAlarmDischargePressureSensorFault OBJECT-IDENTITY The discharge pressure sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.33 | current | ||
| tlpCoolingAlarmWaterFull OBJECT-IDENTITY Water is Full. | 1.3.6.1.4.1.850.1.3.3.7.34 | current | ||
| tlpCoolingAlarmAutoCoolingOn OBJECT-IDENTITY Automatic cooling was activated to lower the temperature below the remote set point. | 1.3.6.1.4.1.850.1.3.3.7.35 | current | ||
| tlpCoolingAlarmPowerButtonPressed OBJECT-IDENTITY Power button was pressed on the front panel. | 1.3.6.1.4.1.850.1.3.3.7.36 | current | ||
| tlpCoolingAlarmDisconnectedFromDevice OBJECT-IDENTITY The device communications is disconnected. | 1.3.6.1.4.1.850.1.3.3.7.37 | current | ||
| tlpCoolingAlarmAmbientTemperatureSensorFault OBJECT-IDENTITY Ambient temperature sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.38 | current | ||
| tlpCoolingAlarmRemoteTemperatureSensorFault OBJECT-IDENTITY Remote temperature sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.39 | current | ||
| tlpCoolingAlarmLowPressureSensorFault OBJECT-IDENTITY Low pressure sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.40 | current | ||
| tlpCoolingAlarmHighPressureSensorFault OBJECT-IDENTITY High pressure sensor is in fault. | 1.3.6.1.4.1.850.1.3.3.7.41 | current | ||
| tlpCoolingAlarmSentrytimerTimeout OBJECT-IDENTITY Sentry timer time out. | 1.3.6.1.4.1.850.1.3.3.7.42 | current | ||
| tlpKvmAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.8 | |||
| tlpRackTrackAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.9 | |||
| tlpSwitchAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.3.10 | |||
| tlpAlarmControl OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.3.4 | |||
| tlpAlarmControlTable OBJECT-TYPE A list of alarm conditions supported for each device managed by this agent. This table contains zero, one, or many rows depending upon the number of available alarms managed by each device. | 1.3.6.1.4.1.850.1.3.4.1 | not-accessible | current | |
| tlpAlarmControlEntry OBJECT-TYPE An entry containing details for a particular alarm condition. | 1.3.6.1.4.1.850.1.3.4.1.1 | not-accessible | current | |
| tlpAlarmControlIndex OBJECT-TYPE The table row index for this alarm control entry for this device. The index of any one row represents the index of the alarm entry within the agent system. As such, the index values for any one device is not guaranteed to start with 1 or be numerically sequential. | 1.3.6.1.4.1.850.1.3.4.1.1.1 | Unsigned32 | read-only | current |
| tlpAlarmControlDescr OBJECT-TYPE A reference of the alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description for the alarm condition. The object referenced will be a well known alarm object associated with the device on which the alarm condition is active. This will be the same object description of an alarm when in alarm as referenced by tlpAlarmDescr. | 1.3.6.1.4.1.850.1.3.4.1.1.2 | OBJECT IDENTIFIER | read-only | current |
| tlpAlarmControlDetail OBJECT-TYPE A textual description of the alarm condition. This will be the same textual description of an alarm when in alarm as referenced by tlpAlarmDetail. | 1.3.6.1.4.1.850.1.3.4.1.1.3 | DisplayString | read-only | current |
| tlpAlarmControlSeverity OBJECT-TYPE The severity of this alarm, which can be configured as desired for each alarm condition. This will be the same severity used when in alarm as referenced by tlpAlarmType. | 1.3.6.1.4.1.850.1.3.4.1.1.4 | INTEGER {critical(1), warning(2), info(3)} | read-write | current |
| tlpNotify OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4 | |||
| tlpNotifications OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.1 | |||
| tlpNotificationsEvent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2 | |||
| tlpNotificationsAgent OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.1 | |||
| tlpNotificationsDevice OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.2 | |||
| tlpNotificationsUps OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.3 | |||
| tlpNotificationsPdu OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.4 | |||
| tlpNotificationsEnvirosense OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.5 | |||
| tlpNotificationsAts OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.6 | |||
| tlpNotificationsCooling OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.7 | |||
| tlpNotificationsKvm OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.8 | |||
| tlpNotificationsRackTrack OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.9 | |||
| tlpNotificationsSwitch OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.2.10 | |||
| tlpNotificationsEventParameters OBJECT-IDENTITY | 1.3.6.1.4.1.850.1.4.3 | |||
| tlpNotifyEventTableRef OBJECT-TYPE This value references the OID of a table object applicable to the event condition. This, in conjunction with the table row as defined by tlpAlarmTableRowRef, specifies the object/row within this table to which the event condition applies. Refer to tlpAlarmTableRef for more information. | 1.3.6.1.4.1.850.1.4.3.1 | OBJECT IDENTIFIER | read-only | current |
| tlpNotifyEventTableRowRef OBJECT-TYPE This value is used in conjunction with tlpNotifyEventTableRef to define the object associated with this event condition. See the description of tlpNotifyEventTableRef for more information. | 1.3.6.1.4.1.850.1.4.3.2 | OBJECT IDENTIFIER | read-only | current |
Notifications
| Name | OID | Status |
|---|---|---|
| tlpNotificationsAlarmEntryAdded NOTIFICATION-TYPE This notification is sent each time an alarm condition is inserted into the device alarm table, tlpAlarmTable. | 1.3.6.1.4.1.850.1.4.1.1 | current |
| tlpNotificationsAlarmEntryRemoved NOTIFICATION-TYPE This notification is sent each time an alarm condition is removed from the device alarm table, tlpAlarmTable. | 1.3.6.1.4.1.850.1.4.1.2 | current |
| tlpNotifySystemStartup NOTIFICATION-TYPE Used to inform another entity of an agent's startup. The varbinds that follow are: OBJ1 = tlpAgentType Obj1Value = The type of engine providing this data OBJ2 = tlpAgentVersion Obj2Value = The current version of the engine OBJ3 = tlpAgentMAC Obj3Value = The MAC address of the engine OBJ4 = tlpAgentSerialNum Obj4Value = The serial number of the web card [should be 0 on PC] --- if this trap is extended, place all static OIDs above this mark. all objects below --- the number of devices (tlpDeviceNumDevices) is explicit as per device for enumeration by --- the target receiver OBJ5 = tlpDeviceNumDevices Obj5Value = The number of devices attached --- The following objects will be replicated per each device: OBJ6 = The OID for an entry of tlpDeviceManufacturer, indexed by device Obj6Value = The device's manufacturer OBJ7 = The OID for an entry of tlpDeviceModel, indexed by device Obj7Value = The device's model name OBJ8 = The OID for an entry of tlpDeviceName, indexed by device Obj8Value = The device's display name OBJ9 = The OID for an entry of tlpDeviceLocation, indexed by device Obj9Value = The device's location OBJ10 = The OID for an entry of tlpDeviceRegion, indexed by device Obj10Value= The device's region OBJ11 = The OID for an entry of tlpDeviceProtocol, indexed by device Obj11Value= The device's protocol (display string format) | 1.3.6.1.4.1.850.1.4.1.3 | current |
| tlpNotifySystemShutdown NOTIFICATION-TYPE Used to inform another entity of an agent's shutdown. The varbinds that follow are: OBJ1 = tlpAgentType Obj1Value = The type of engine providing this data OBJ2 = tlpAgentVersion Obj2Value = The current version of the engine OBJ3 = tlpAgentMAC Obj3Value = The MAC address of the engine OBJ4 = tlpAgentSerialNum Obj4Value = The serial number of the web card [should be 0 on PC] --- if this trap is extended, place all static OIDs above this mark. all objects below --- the number of devices (tlpDeviceNumDevices) is explicit as per device for enumeration by --- the target receiver OBJ5 = tlpDeviceNumDevices Obj5Value = The number of devices attached --- The following objects will be replicated per each device: OBJ6 = The OID for an entry of tlpDeviceManufacturer, indexed by device Obj6Value = The device's manufacturer OBJ7 = The OID for an entry of tlpDeviceModel, indexed by device Obj7Value = The device's model name OBJ8 = The OID for an entry of tlpDeviceName, indexed by device Obj8Value = The device's display name OBJ9 = The OID for an entry of tlpDeviceLocation, indexed by device Obj9Value = The device's location OBJ10 = The OID for an entry of tlpDeviceRegion, indexed by device Obj10Value= The device's region OBJ11 = The OID for an entry of tlpDeviceProtocol, indexed by device Obj11Value= The device's protocol (display string format) | 1.3.6.1.4.1.850.1.4.1.4 | current |
| tlpNotifySystemUpdate NOTIFICATION-TYPE Used to inform another entity of an engine's startup. The varbinds that follow are: OBJ1 = tlpAgentType Obj1Value = The type of engine providing this data OBJ2 = tlpAgentVersion Obj2Value = The current version of the engine OBJ3 = tlpAgentMAC Obj3Value = The MAC address of the engine OBJ4 = tlpAgentSerialNum Obj4Value = The serial number of the web card [should be 0 on PC] --- if this trap is extended, place all static OIDs above this mark. all objects below --- the number of devices (tlpDeviceNumDevices) is explicit as per device for enumeration by --- the target receiver OBJ5 = tlpDeviceNumDevices Obj5Value = The number of devices attached --- The following objects will be replicated per each device: OBJ6 = The OID for an entry of tlpDeviceManufacturer, indexed by device Obj6Value = The device's manufacturer OBJ7 = The OID for an entry of tlpDeviceModel, indexed by device Obj7Value = The device's model name OBJ8 = The OID for an entry of tlpDeviceName, indexed by device Obj8Value = The device's display name OBJ9 = The OID for an entry of tlpDeviceLocation, indexed by device Obj9Value = The device's location OBJ10 = The OID for an entry of tlpDeviceRegion, indexed by device Obj10Value= The device's region OBJ11 = The OID for an entry of tlpDeviceProtocol, indexed by device Obj11Value= The device's protocol (display string format) | 1.3.6.1.4.1.850.1.4.1.5 | current |
| tlpNotifyTest NOTIFICATION-TYPE Used when performing a test of the system or an alert notification contact. The varbinds that follow are: OBJ1 = tlpAgentType Obj1Value = The type of engine providing this data OBJ2 = tlpAgentVersion Obj2Value = The current version of the engine OBJ3 = tlpAgentMAC Obj3Value = The MAC address of the engine OBJ4 = tlpAgentSerialNum Obj4Value = The serial number of the web card [should be 0 on PC] | 1.3.6.1.4.1.850.1.4.1.6 | current |
| tlpNotificationsDeviceInternalFirmwareFault NOTIFICATION-TYPE This notification is sent when the device experiences an internal firmware failure. | 1.3.6.1.4.1.850.1.4.2.2.1 | current |
| tlpNotificationsDeviceInternalHardwareFault NOTIFICATION-TYPE This notification is sent when the device experiences an internal hardware failure. | 1.3.6.1.4.1.850.1.4.2.2.2 | current |
| tlpNotificationsDeviceConfigurationChange NOTIFICATION-TYPE This notification is sent when the device configuration changes. | 1.3.6.1.4.1.850.1.4.2.2.3 | current |
| tlpNotificationsDeviceFirmwareUpdate NOTIFICATION-TYPE This notification is sent when the device firmware is updated. | 1.3.6.1.4.1.850.1.4.2.2.4 | current |
| tlpNotificationsDeviceMicrocontrollerReset NOTIFICATION-TYPE This notification is sent when the device microcontroller resets. | 1.3.6.1.4.1.850.1.4.2.2.5 | current |
| tlpNotificationsDeviceSystemInformation NOTIFICATION-TYPE This notification is sent when the device sysytem information changes. | 1.3.6.1.4.1.850.1.4.2.2.6 | current |
| tlpNotificationsDeviceNvrChecksumMismatch NOTIFICATION-TYPE This notification is sent when the NVR is corrupted. | 1.3.6.1.4.1.850.1.4.2.2.7 | current |
| tlpNotificationsDeviceUsbCommunicationsEstablished NOTIFICATION-TYPE This notification is sent when the device USB communications is established. | 1.3.6.1.4.1.850.1.4.2.2.8 | current |
| tlpNotificationsDeviceUsbCommunicationsLost NOTIFICATION-TYPE This notification is sent when the device USB communications is lost. | 1.3.6.1.4.1.850.1.4.2.2.9 | current |
| tlpNotificationsDevicePowerSupplyShutdown NOTIFICATION-TYPE This notification is sent when the device reports a shutdown occurred due to a power supply fault. | 1.3.6.1.4.1.850.1.4.2.2.10 | current |
| tlpNotificationsDeviceOverLoadShutdown NOTIFICATION-TYPE This notification is sent when the device reports a shutdown occurred due to an over load fault. | 1.3.6.1.4.1.850.1.4.2.2.11 | current |
| tlpNotificationsDeviceCurrentLimitShutdown NOTIFICATION-TYPE This notification is sent when the device reports a shutdown occurred due to a current limit fault. | 1.3.6.1.4.1.850.1.4.2.2.12 | current |
| tlpNotificationsDeviceOverTemperatureShutdown NOTIFICATION-TYPE This notification is sent when the device reports a shutdown occurred due to an over temperature fault. | 1.3.6.1.4.1.850.1.4.2.2.13 | current |
| tlpNotificationsDeviceModeTransitionTimeout NOTIFICATION-TYPE This notification is sent when the device timed out transitioning to a mode. | 1.3.6.1.4.1.850.1.4.2.2.14 | current |
| tlpNotificationsDeviceFailedModeTransitionToIdle NOTIFICATION-TYPE This notification is sent when the device failed a transition to idle mode. | 1.3.6.1.4.1.850.1.4.2.2.15 | current |
| tlpNotificationsDeviceInternalCommunicationsLost NOTIFICATION-TYPE This notification is sent when the device lost internal communications. | 1.3.6.1.4.1.850.1.4.2.2.16 | current |
| tlpNotificationsDeviceAcknowledgeFaults NOTIFICATION-TYPE This notification is sent when device faults are acknowledged. | 1.3.6.1.4.1.850.1.4.2.2.17 | current |
| tlpNotificationsDeviceTransferToReboot NOTIFICATION-TYPE This notification is sent when a device reboot occurred. | 1.3.6.1.4.1.850.1.4.2.2.18 | current |
| tlpNotificationsDeviceTransferToWatchdogReboot NOTIFICATION-TYPE This notification is sent when a device reboot occurred due to a watchdog fault. | 1.3.6.1.4.1.850.1.4.2.2.19 | current |
| tlpNotificationsDeviceTransferToLatchedIdle NOTIFICATION-TYPE This notification is sent when the device transferred to latched idle mode. | 1.3.6.1.4.1.850.1.4.2.2.20 | current |
| tlpNotificationsDeviceTransferToLatchedStandby NOTIFICATION-TYPE This notification is sent when the device transferred to latched standby mode. | 1.3.6.1.4.1.850.1.4.2.2.21 | current |
| tlpNotificationsDeviceTransferToLatchedLine NOTIFICATION-TYPE This notification is sent when the device transferred to latched line mode. | 1.3.6.1.4.1.850.1.4.2.2.22 | current |
| tlpNotificationsDeviceFailSafeClockMonitorEngaged NOTIFICATION-TYPE This notification is sent when the fail safe clock monitor is engaged. | 1.3.6.1.4.1.850.1.4.2.2.23 | current |
| tlpNotificationsDeviceTransferToIdle NOTIFICATION-TYPE This notification is sent when the device transferred to idle mode. | 1.3.6.1.4.1.850.1.4.2.2.24 | current |
| tlpNotificationsDeviceVoutUnderVoltageShutdown NOTIFICATION-TYPE This notification is sent when the device reports a shutdown occurred due to a vout under voltage fault. | 1.3.6.1.4.1.850.1.4.2.2.25 | current |
| tlpNotificationsDeviceVoutOverVoltageShutdown NOTIFICATION-TYPE This notification is sent when the device reports a shutdown occurred due to a vout over voltage fault. | 1.3.6.1.4.1.850.1.4.2.2.26 | current |
| tlpNotificationsDeviceUnhandledFault NOTIFICATION-TYPE This notification is sent when the device reports an unhandled fault. | 1.3.6.1.4.1.850.1.4.2.2.27 | current |
| tlpNotificationsUpsBatteryLowVoltageShutdown NOTIFICATION-TYPE This notification is sent when the ups reports a shutdown occurred due to a low battery voltage fault. | 1.3.6.1.4.1.850.1.4.2.3.1 | current |
| tlpNotificationsUpsBatteryLowPercentageShutdown NOTIFICATION-TYPE This notification is sent when the ups reports a shutdown occurred due to a low battery percentage fault. | 1.3.6.1.4.1.850.1.4.2.3.2 | current |
| tlpNotificationsUpsBatteryOverVoltageShutdown NOTIFICATION-TYPE This notification is sent when the ups reports a shutdown occurred due to a battery over voltage fault. | 1.3.6.1.4.1.850.1.4.2.3.3 | current |
| tlpNotificationsUpsBatteryOverCurrentShutdown NOTIFICATION-TYPE This notification is sent when the ups reports a shutdown occurred due to a battery over current fault. | 1.3.6.1.4.1.850.1.4.2.3.4 | current |
| tlpNotificationsUpsBatteryUnknownTypeShutdown NOTIFICATION-TYPE This notification is sent when the ups reports a shutdown occurred due to an unknown battery type fault. | 1.3.6.1.4.1.850.1.4.2.3.5 | current |
| tlpNotificationsUpsBatteryConfigurationMismatch NOTIFICATION-TYPE This notification is sent when the ups battery configuration is mismatched. | 1.3.6.1.4.1.850.1.4.2.3.6 | current |
| tlpNotificationsUpsBatteryUnderVoltageShutdown NOTIFICATION-TYPE This notification is sent when the ups reports a shutdown occurred due to a battery under voltage fault. | 1.3.6.1.4.1.850.1.4.2.3.7 | current |
| tlpNotificationsUpsSlaBatteryOverTemperatureShutdown NOTIFICATION-TYPE This notification is sent when the ups reports a shutdown occurred due to an SLA battery over temperature fault. | 1.3.6.1.4.1.850.1.4.2.3.8 | current |
| tlpNotificationsUpsBatteryInstallation NOTIFICATION-TYPE This notification is sent when a battery installation occurs. | 1.3.6.1.4.1.850.1.4.2.3.9 | current |
| tlpNotificationsUpsChargerBulkToAcceptance NOTIFICATION-TYPE This notification is sent when ups battery charging. | 1.3.6.1.4.1.850.1.4.2.3.10 | current |
| tlpNotificationsUpsChargerAcceptanceToFloat NOTIFICATION-TYPE This notification is sent when ups battery fully charged. | 1.3.6.1.4.1.850.1.4.2.3.11 | current |
| tlpNotificationsUpsChargerFloatToBulk NOTIFICATION-TYPE This notification is sent when ups battery not fully charged. | 1.3.6.1.4.1.850.1.4.2.3.12 | current |
| tlpNotificationsUpsTransferToSelftest NOTIFICATION-TYPE This notification is sent when a self test is initiated. | 1.3.6.1.4.1.850.1.4.2.3.13 | current |
| tlpNotificationsUpsTransferToEconomy NOTIFICATION-TYPE This notification is sent when the device transferred to economy mode. | 1.3.6.1.4.1.850.1.4.2.3.14 | current |
| tlpNotificationsUpsLineConnectRelayFaultShutdown NOTIFICATION-TYPE This notification is sent when the device reports a shutdown occurred due to line connect relay fault. | 1.3.6.1.4.1.850.1.4.2.3.15 | current |
| tlpNotificationsUpsTransferToFaultBypass NOTIFICATION-TYPE This notification is sent when the device transferred to fault bypass mode. | 1.3.6.1.4.1.850.1.4.2.3.16 | current |
| tlpNotificationsUpsBypassPowerDistributionModuleDisconnected NOTIFICATION-TYPE This notification is sent when bypass power distribution module is disconnected. | 1.3.6.1.4.1.850.1.4.2.3.17 | current |
| tlpNotificationsUpsManualBypassActivatedFromUnsupportedMode NOTIFICATION-TYPE This notification is sent when manual bypass activated from an unsupported UPS mode. | 1.3.6.1.4.1.850.1.4.2.3.18 | current |
| tlpNotificationsUpsOnBatteryTimeoutShutdown NOTIFICATION-TYPE This notification is sent when the device reports a shutdown occurred due to on battery timeout. | 1.3.6.1.4.1.850.1.4.2.3.19 | current |
| tlpNotificationsUpsLowBatteryPercentageShutdown NOTIFICATION-TYPE This notification is sent when the device reports a shutdown occurred due to low battery percentage. | 1.3.6.1.4.1.850.1.4.2.3.20 | current |
| tlpNotificationsAtsSource1NotAvailable NOTIFICATION-TYPE This notification is sent when input on source one is not available. For atss with the designation of primary and secondary, this notification denotes input on the primary source is not available. | 1.3.6.1.4.1.850.1.4.2.6.1 | current |
| tlpNotificationsAtsSource2NotAvailable NOTIFICATION-TYPE This notification is sent when input on source two is not available. For atss with the designation of primary and secondary, this notification denotes input on the secondary source is not available. | 1.3.6.1.4.1.850.1.4.2.6.2 | current |
| tlpNotificationsAtsLockdownToSource1 NOTIFICATION-TYPE This notification is sent upon a transfer circuit fault causing the device to be locked on source 1. | 1.3.6.1.4.1.850.1.4.2.6.3 | current |
| tlpNotificationsAtsLockdownToSource2 NOTIFICATION-TYPE This notification is sent upon a transfer circuit fault causing the device to be locked on source 2. | 1.3.6.1.4.1.850.1.4.2.6.4 | current |
| tlpNotificationsAtsSource1Available NOTIFICATION-TYPE This notification is sent when source 1 is available and ready for use. | 1.3.6.1.4.1.850.1.4.2.6.5 | current |
| tlpNotificationsAtsSource2Available NOTIFICATION-TYPE This notification is sent when source 2 is available and ready for use. | 1.3.6.1.4.1.850.1.4.2.6.6 | current |
| tlpNotificationsAtsSource1Brownout NOTIFICATION-TYPE This notification is sent when a brownout condition occurred on source 1. | 1.3.6.1.4.1.850.1.4.2.6.7 | current |
| tlpNotificationsAtsSource2Brownout NOTIFICATION-TYPE This notification is sent when a brownout condition occurred on source 2. | 1.3.6.1.4.1.850.1.4.2.6.8 | current |
| tlpNotificationsAtsSource1VoltageDrop NOTIFICATION-TYPE This notification is sent when the voltage on source 1 drops below a usable state. | 1.3.6.1.4.1.850.1.4.2.6.9 | current |
| tlpNotificationsAtsSource2VoltageDrop NOTIFICATION-TYPE This notification is sent when the voltage on source 2 drops below a usable state. | 1.3.6.1.4.1.850.1.4.2.6.10 | current |
| tlpNotificationsAtsTimedReturnToSource1 NOTIFICATION-TYPE This notification is sent when the active input source returns to source 1 from source 2 after a delay time expires. | 1.3.6.1.4.1.850.1.4.2.6.11 | current |
| tlpNotificationsAtsTimedReturnToSource2 NOTIFICATION-TYPE This notification is sent when the active input source returns to source 2 from source 1 after a delay time expires. | 1.3.6.1.4.1.850.1.4.2.6.12 | current |
| tlpNotificationsAtsTransferToSource1 NOTIFICATION-TYPE This notification is sent when the active input source transfers from source 2 to source 1. | 1.3.6.1.4.1.850.1.4.2.6.13 | current |
| tlpNotificationsAtsTransferToSource2 NOTIFICATION-TYPE This notification is sent when the active input source transfers from source 1 to source 2. | 1.3.6.1.4.1.850.1.4.2.6.14 | current |