MIBs Depot

TIC-RMTI4-G9000-G2020-MIB

Registered at
1.3.6.1.4.1.186
Namespace
toshiba
Source file
TIC-RMTI4-G9000-G2020-MIB
Digest
sha256:a9ad7b7b847a40d052b547e22971e9be8cb6dc26ee426fa7453981969c0055d5

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso
SNMPv2-TCAutonomousType, DisplayString, TEXTUAL-CONVENTION, TestAndIncr, TimeInterval, TimeStamp

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC
TIC-RMTI4-G9000-G2020-MIB

Textual conventions

NameOIDSyntaxAccessStatus
NonNegativeInteger
type
PositiveInteger
type

Objects

NameOIDSyntaxAccessStatus
toshiba
OBJECT-IDENTITY
1.3.6.1.4.1.186
equ
OBJECT-IDENTITY
1.3.6.1.4.1.186.1
equUPS
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19
ticUPS
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2
rmti4
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5
upsG9000_G2020
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1
upsIdent
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.1
upsIdentManufacturer
OBJECT-TYPE
The name of the UPS manufacturer.
1.3.6.1.4.1.186.1.19.2.5.1.1.1DisplayString (SIZE(0..31))read-onlymandatory
upsIdentTypeform
OBJECT-TYPE
The UPS Model designation.
1.3.6.1.4.1.186.1.19.2.5.1.1.2DisplayString (SIZE(0..127))read-onlymandatory
upsIdentUPSFirmwareVersion
OBJECT-TYPE
The UPS firmware version.
1.3.6.1.4.1.186.1.19.2.5.1.1.3DisplayString (SIZE(0..63))read-onlymandatory
upsIdentSysName
OBJECT-TYPE
A string identifying the UPS. This object is set by the administrator.
1.3.6.1.4.1.186.1.19.2.5.1.1.4DisplayString (SIZE(0..63))read-writemandatory
upsIdentAttachedDevices
OBJECT-TYPE
A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator.
1.3.6.1.4.1.186.1.19.2.5.1.1.5DisplayString (SIZE(0..63))read-writemandatory
upsInput
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.2
upsInputNumOfPhases
OBJECT-TYPE
Number of input lines. This data is used by upsInputNumLines.
1.3.6.1.4.1.186.1.19.2.5.1.2.1NonNegativeIntegerread-onlymandatory
upsInputLLVoltageAB
OBJECT-TYPE
The input line to line voltage for AB in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.2.2NonNegativeIntegerread-onlymandatory
upsInputLLVoltageBC
OBJECT-TYPE
The input line to line voltage for BC in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.2.3NonNegativeIntegerread-onlymandatory
upsInputLLVoltageCA
OBJECT-TYPE
The input line to line voltage for CA in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.2.4NonNegativeIntegerread-onlymandatory
upsInputLLVoltagePercentAB
OBJECT-TYPE
The input line to line voltage percent for AB.
1.3.6.1.4.1.186.1.19.2.5.1.2.5NonNegativeIntegerread-onlymandatory
upsInputLLVoltagePercentBC
OBJECT-TYPE
The input line to line voltage percent for BC.
1.3.6.1.4.1.186.1.19.2.5.1.2.6NonNegativeIntegerread-onlymandatory
upsInputLLVoltagePercentCA
OBJECT-TYPE
The input line to line voltage percent for CA.
1.3.6.1.4.1.186.1.19.2.5.1.2.7NonNegativeIntegerread-onlymandatory
upsInputCurrentPhaseA
OBJECT-TYPE
The input phase current for Phase A.
1.3.6.1.4.1.186.1.19.2.5.1.2.8NonNegativeIntegerread-onlymandatory
upsInputCurrentPhaseB
OBJECT-TYPE
The input phase current unit for Phase B.
1.3.6.1.4.1.186.1.19.2.5.1.2.9NonNegativeIntegerread-onlymandatory
upsInputCurrentPhaseC
OBJECT-TYPE
The input phase current unit for Phase C.
1.3.6.1.4.1.186.1.19.2.5.1.2.10NonNegativeIntegerread-onlymandatory
upsInputFrequency
OBJECT-TYPE
The input frequency unit 0.1 Hertz.
1.3.6.1.4.1.186.1.19.2.5.1.2.11NonNegativeIntegerread-onlymandatory
upsInputActivePowerA
OBJECT-TYPE
The magnitude of the present input true power for phase A.
1.3.6.1.4.1.186.1.19.2.5.1.2.12NonNegativeIntegerread-onlymandatory
upsInputActivePowerB
OBJECT-TYPE
The magnitude of the present input true power for phase B.
1.3.6.1.4.1.186.1.19.2.5.1.2.13NonNegativeIntegerread-onlymandatory
upsInputActivePowerC
OBJECT-TYPE
The magnitude of the present input true power for phase C.
1.3.6.1.4.1.186.1.19.2.5.1.2.14NonNegativeIntegerread-onlymandatory
upsInputTotalActivePower
OBJECT-TYPE
The magnitude of the total input true power.
1.3.6.1.4.1.186.1.19.2.5.1.2.15NonNegativeIntegerread-onlymandatory
upsInputRatedLLVoltage
OBJECT-TYPE
The input line to line rated voltage in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.2.16NonNegativeIntegerread-onlymandatory
upsOutput
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.3
upsOutputSource
OBJECT-TYPE
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
1.3.6.1.4.1.186.1.19.2.5.1.3.1INTEGER {other(1), none(2), normal(3), bypass(4), battery(5)}read-onlymandatory
upsOutputNumOfPhases
OBJECT-TYPE
The number of output lines utilized in this device.
1.3.6.1.4.1.186.1.19.2.5.1.3.2NonNegativeIntegerread-onlymandatory
upsOutputLLVoltageAB
OBJECT-TYPE
The output line to line voltage for AB in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.3.3NonNegativeIntegerread-onlymandatory
upsOutputLLVoltageBC
OBJECT-TYPE
The output line to line voltage for BC in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.3.4NonNegativeIntegerread-onlymandatory
upsOutputLLVoltageCA
OBJECT-TYPE
The output line to line voltage for CA in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.3.5NonNegativeIntegerread-onlymandatory
upsOutputCurrentPhaseA
OBJECT-TYPE
The Output phase current for phase A in amps.
1.3.6.1.4.1.186.1.19.2.5.1.3.6NonNegativeIntegerread-onlymandatory
upsOutputCurrentPhaseB
OBJECT-TYPE
The Output phase current for phase B in amps.
1.3.6.1.4.1.186.1.19.2.5.1.3.7NonNegativeIntegerread-onlymandatory
upsOutputCurrentPhaseC
OBJECT-TYPE
The Output phase current for phase C in amps.
1.3.6.1.4.1.186.1.19.2.5.1.3.8NonNegativeIntegerread-onlymandatory
upsOutputFrequency
OBJECT-TYPE
The Output Frequency for phase A in 1/10 of HZ.
1.3.6.1.4.1.186.1.19.2.5.1.3.9NonNegativeIntegerread-onlymandatory
upsOutputCurrentPercentA
OBJECT-TYPE
The output current for phase A in percent.
1.3.6.1.4.1.186.1.19.2.5.1.3.10INTEGERread-onlymandatory
upsOutputCurrentPercentB
OBJECT-TYPE
The output current for phase B in percent.
1.3.6.1.4.1.186.1.19.2.5.1.3.11INTEGERread-onlymandatory
upsOutputCurrentPercentC
OBJECT-TYPE
The output current for phase C in percent.
1.3.6.1.4.1.186.1.19.2.5.1.3.12INTEGERread-onlymandatory
upsOutputTotalActivePower
OBJECT-TYPE
The output active power.
1.3.6.1.4.1.186.1.19.2.5.1.3.13NonNegativeIntegerread-onlymandatory
upsOutputTotalActivePowerPercent
OBJECT-TYPE
The output active power in percent.
1.3.6.1.4.1.186.1.19.2.5.1.3.14NonNegativeIntegerread-onlymandatory
upsOutputPowerFactor
OBJECT-TYPE
The UPS output power factor.
1.3.6.1.4.1.186.1.19.2.5.1.3.15NonNegativeIntegerread-onlymandatory
upsOutputRatedActivePower
OBJECT-TYPE
The output rated active power for the UPS.
1.3.6.1.4.1.186.1.19.2.5.1.3.16NonNegativeIntegerread-onlymandatory
upsOutputRatedApparentPower
OBJECT-TYPE
The output rated apparent power for the UPS.
1.3.6.1.4.1.186.1.19.2.5.1.3.17NonNegativeIntegerread-onlymandatory
upsOutputRatedLLVoltage
OBJECT-TYPE
The output rated line to line voltage for the UPS.
1.3.6.1.4.1.186.1.19.2.5.1.3.18NonNegativeIntegerread-onlymandatory
upsBypass
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.4
upsBypassNumOfPhases
OBJECT-TYPE
The number of bypass lines utilized.
1.3.6.1.4.1.186.1.19.2.5.1.4.1NonNegativeIntegerread-onlymandatory
upsBypassLLVoltageAB
OBJECT-TYPE
The Bypass line to line voltage for AB in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.4.2NonNegativeIntegerread-onlymandatory
upsBypassLLVoltageBC
OBJECT-TYPE
The Bypass line to line voltage for BC in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.4.3NonNegativeIntegerread-onlymandatory
upsBypassLLVoltageCA
OBJECT-TYPE
The Bypass line to line voltage for CA in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.4.4NonNegativeIntegerread-onlymandatory
upsBypassFrequency
OBJECT-TYPE
The Bypass frequency in 0.1 Hertz.
1.3.6.1.4.1.186.1.19.2.5.1.4.5NonNegativeIntegerread-onlymandatory
upsBattery
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.5
upsBatteryStatus
OBJECT-TYPE
The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run time sufficient to handle the load. A value of batteryLow indicates the battery level is low. Continued operation in battery mode will deplate batteries. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). A value of batteryDischarging indicates UPS system is in Battery power.
1.3.6.1.4.1.186.1.19.2.5.1.5.1INTEGER {unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6)}read-onlymandatory
upsElapsedTimeOnBatteryPower
OBJECT-TYPE
If the unit is on battery power, the elapsed time since the UPS on battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
1.3.6.1.4.1.186.1.19.2.5.1.5.2NonNegativeIntegerread-onlymandatory
upsEstimatedBatteryRuntime
OBJECT-TYPE
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
1.3.6.1.4.1.186.1.19.2.5.1.5.3PositiveIntegerread-onlymandatory
upsBatteryVoltage
OBJECT-TYPE
The battery voltage DC.
1.3.6.1.4.1.186.1.19.2.5.1.5.4NonNegativeIntegerread-onlymandatory
upsBatteryVoltagePercent
OBJECT-TYPE
Battery voltage in percent.
1.3.6.1.4.1.186.1.19.2.5.1.5.5NonNegativeIntegerread-onlymandatory
upsBatteryEstimatedCharge
OBJECT-TYPE
An estimate of the charge to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
1.3.6.1.4.1.186.1.19.2.5.1.5.6INTEGER (0..100)read-onlymandatory
upsBatteryDischargeCurrent
OBJECT-TYPE
The present battery discharge Current in percent.
1.3.6.1.4.1.186.1.19.2.5.1.5.7Integer32read-onlymandatory
upsBatteryChargeCurrent
OBJECT-TYPE
The present battery charge Current in percent.
1.3.6.1.4.1.186.1.19.2.5.1.5.8Integer32read-onlymandatory
upsBatteryModel
OBJECT-TYPE
The Battery manufacturer.
1.3.6.1.4.1.186.1.19.2.5.1.5.9DisplayString (SIZE(0..15))read-writemandatory
upsBatteryInSeries
OBJECT-TYPE
The Battery rated holding time in minutes.
1.3.6.1.4.1.186.1.19.2.5.1.5.10NonNegativeIntegerread-writemandatory
upsBatteryNumStrings
OBJECT-TYPE
The Battery rated holding time in minutes.
1.3.6.1.4.1.186.1.19.2.5.1.5.11NonNegativeIntegerread-writemandatory
upsBatteryRatedAmpereHour
OBJECT-TYPE
The Battery rated holding time in minutes.
1.3.6.1.4.1.186.1.19.2.5.1.5.12NonNegativeIntegerread-writemandatory
upsBatteryRatedBackupTime
OBJECT-TYPE
The Battery rated holding time in minutes.
1.3.6.1.4.1.186.1.19.2.5.1.5.13DisplayString (SIZE(0..8))read-writemandatory
upsBatteryInstallationDate
OBJECT-TYPE
The battery install date.
1.3.6.1.4.1.186.1.19.2.5.1.5.14DisplayString (SIZE(10))read-onlymandatory
upsAlarm
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.6
upsAlarmsPresent
OBJECT-TYPE
The present number of active alarm conditions.
1.3.6.1.4.1.186.1.19.2.5.1.6.1Gauge32read-onlymandatory
upsAlarmTable
OBJECT-TYPE
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.
1.3.6.1.4.1.186.1.19.2.5.1.6.2not-accessiblemandatory
upsAlarmEntry
OBJECT-TYPE
An entry containing information applicable to a particular alarm.
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1not-accessiblemandatory
upsAlarmId
OBJECT-TYPE
A unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.1PositiveIntegernot-accessiblemandatory
upsAlarmDescr
OBJECT-TYPE
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.2AutonomousTyperead-onlymandatory
upsAlarmTime
OBJECT-TYPE
The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.3TimeStampread-onlymandatory
upsWellKnownAlarms
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.6.3
upsAlarmFault
OBJECT-TYPE
Fault: A UPS fault/Alarm condition exists.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.1INTEGERread-onlymandatory
upsAlarmOnBattery
OBJECT-TYPE
Info: The UPS is on Battery mode; it is supplying output power from its batteries.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.2INTEGERread-onlymandatory
upsAlarmBatteryLow
OBJECT-TYPE
Warning: The battery level is low. It has dropped to less than 90% of its nominal value. Continued operation in Battery Mode will deplete Batteries and result in UPS output shut down. Reduce critical load to increase battery runtime.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.3INTEGERread-onlymandatory
upsAlarmBatteryDepleted
OBJECT-TYPE
Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shut down excess equipment to reduce Load.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.4INTEGERread-onlymandatory
upsAlarmBatteryOverheat
OBJECT-TYPE
Fault: Detection of over temperature at the batteries.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.5INTEGERread-onlymandatory
upsAlarmBatteryVoltageAbnormal
OBJECT-TYPE
Fault: Battery voltage is abnormality.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.6INTEGERread-onlymandatory
upsAlarmUPSOverheat
OBJECT-TYPE
Fault: The UPS is overheating (warning is given when the internal temperature reaches and exceeds 50?C rise @ 40?C ambient). Check to see if the ambient temperature is abnormally high (40?C or more). If so, turn on air conditioning. Also, check ventilation fan at the back of the UPS for operation or obstructions. Otherwise, shut down the UPS and contact your Toshiba authorized service center.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.7INTEGERread-onlymandatory
upsAlarmPowerFailure
OBJECT-TYPE
Info: Power Failure.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.8INTEGERread-onlymandatory
upsAlarmUPSOverload
OBJECT-TYPE
Fault: The UPS is overloaded. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.9INTEGERread-onlymandatory
upsAlarmUserDefinedOverloadWarning
OBJECT-TYPE
Warning: The inverter output load % is greater than the user defined overload set point (default: 110%).
1.3.6.1.4.1.186.1.19.2.5.1.6.3.10INTEGERread-onlymandatory
upsAlarmOnBypass
OBJECT-TYPE
Warning: The UPS is in Stop (Bypass) mode.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.11INTEGERread-onlymandatory
upsAlarmOutputOff
OBJECT-TYPE
Info: The UPS output is off.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.12INTEGERread-onlymandatory
upsAlarmAsyncOperation
OBJECT-TYPE
Warning: Async Operation
1.3.6.1.4.1.186.1.19.2.5.1.6.3.13INTEGERread-onlymandatory
upsAlarmDCBusOverCurrent
OBJECT-TYPE
Fault: UPS is reporting a DC bus overcurrent condition. Contact your Toshiba authorized service center for examination of a DCOC fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.14INTEGERread-onlymandatory
upsAlarmDCBusOverVoltage
OBJECT-TYPE
Fault: UPS is reporting a DC bus overvoltage condition. Contact your Toshiba authorized service center for examination of a DCOV fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.15INTEGERread-onlymandatory
upsAlarmDCBusUnderVoltage
OBJECT-TYPE
Fault: UPS is reporting a DC bus undervoltage condition. Contact your Toshiba authorized service center for examination of a DCUV fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.16INTEGERread-onlymandatory
upsAlarmDCBusImbalanced
OBJECT-TYPE
Fault: The DC imbalanced alarm detection.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.17INTEGERread-onlymandatory
upsAlarmOutputUnderVoltage
OBJECT-TYPE
Fault: UPS is reporting an output undervoltage condition. Contact your Toshiba authorized service center for examination of a INVUV fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.18INTEGERread-onlymandatory
upsAlarmOutputOverVoltage
OBJECT-TYPE
Fault: UPS is reporting an output overvoltage condition. Contact your Toshiba authorized service center for examination of a INVOV fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.19INTEGERread-onlymandatory
upsAlarmInverterOverload
OBJECT-TYPE
Fault: Short time over-current has been detected.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.20INTEGERread-onlymandatory
upsAlarmInverterOvercurrent
OBJECT-TYPE
Fault: Detection of inverter overcurrent.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.21INTEGERread-onlymandatory
upsAlarmRemotEyeCommError
OBJECT-TYPE
Warning: Communication error between the RemotEye 4 and the UPS.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.22INTEGERread-onlymandatory
upsConfig
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.7
upsConfigModelIDString
OBJECT-TYPE
UPS Model ID string. This string contains codes for the UPS series,input voltage, output voltage, output VA, and addition option.
1.3.6.1.4.1.186.1.19.2.5.1.7.1DisplayString (SIZE(0..63))read-onlymandatory
upsConfigUPSFirmwareVersion
OBJECT-TYPE
The G9000 software version.
1.3.6.1.4.1.186.1.19.2.5.1.7.2DisplayString (SIZE(0..63))read-onlymandatory
upsConfigInputNumOfPhases
OBJECT-TYPE
Number of input lines. This data is used by upsInputNumLines.
1.3.6.1.4.1.186.1.19.2.5.1.7.3NonNegativeIntegerread-onlymandatory
upsConfigRatedInputFrequency
OBJECT-TYPE
The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
1.3.6.1.4.1.186.1.19.2.5.1.7.4NonNegativeIntegerread-onlymandatory
upsConfigRatedInputLLVoltage
OBJECT-TYPE
The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
1.3.6.1.4.1.186.1.19.2.5.1.7.5NonNegativeIntegerread-writemandatory
upsConfigRatedInputPowerFactor
OBJECT-TYPE
UNITS are in hundredths. For 0.95 = 95.
1.3.6.1.4.1.186.1.19.2.5.1.7.6PositiveIntegerread-onlymandatory
upsConfigOutputNumOfPhases
OBJECT-TYPE
Number of output lines. This data is used by upsOutputNumLines.
1.3.6.1.4.1.186.1.19.2.5.1.7.7NonNegativeIntegerread-onlymandatory
upsConfigRatedOutputFrequency
OBJECT-TYPE
The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., bad Value for SNMPv1, or inconsistent Value for SNMPv2.
1.3.6.1.4.1.186.1.19.2.5.1.7.8NonNegativeIntegerread-onlymandatory
upsConfigRatedOutputLLVoltage
OBJECT-TYPE
The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., bad Value for SNMPv1, or inconsistent Value for SNMPv2.
1.3.6.1.4.1.186.1.19.2.5.1.7.9NonNegativeIntegerread-writemandatory
upsConfigRatedOutputApperentPower
OBJECT-TYPE
The magnitude of the nominal Volt-Amp rating.
1.3.6.1.4.1.186.1.19.2.5.1.7.10NonNegativeIntegerread-onlymandatory
upsConfigRatedOutputActivePower
OBJECT-TYPE
The magnitude of the nominal true power rating.
1.3.6.1.4.1.186.1.19.2.5.1.7.11NonNegativeIntegerread-onlymandatory
upsConfigRatedOutputPowerFactor
OBJECT-TYPE
UNITS are in hundredths. For 0.70 = 70.
1.3.6.1.4.1.186.1.19.2.5.1.7.12NonNegativeIntegerread-onlymandatory
upsConfigBypassNumOfPhases
OBJECT-TYPE
The number of bypass lines utilized.
1.3.6.1.4.1.186.1.19.2.5.1.7.13NonNegativeIntegerread-onlymandatory
upsConfigLowVoltageTransferPoint
OBJECT-TYPE
The minimum input line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.4.1.186.1.19.2.5.1.7.14NonNegativeIntegerread-writemandatory
upsConfigHighVoltageTransferPoint
OBJECT-TYPE
The maximum line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.4.1.186.1.19.2.5.1.7.15NonNegativeIntegerread-writemandatory
upsConfigBatteryInSeries
OBJECT-TYPE
The number of batteries in each string connected in series.
1.3.6.1.4.1.186.1.19.2.5.1.7.16NonNegativeIntegerread-writemandatory
upsConfigBatteryNumStrings
OBJECT-TYPE
The number of parallel battery strings.
1.3.6.1.4.1.186.1.19.2.5.1.7.17NonNegativeIntegerread-writemandatory
upsConfigRatedBatteryVoltage
OBJECT-TYPE
Rated voltage of a single battery.
1.3.6.1.4.1.186.1.19.2.5.1.7.18NonNegativeIntegerread-writemandatory
upsConfigRatedBatteryAmpereHour
OBJECT-TYPE
The rated battery in ampere hour.
1.3.6.1.4.1.186.1.19.2.5.1.7.19INTEGERread-writemandatory
upsConfigBatteryModel
OBJECT-TYPE
The manufacturer of the battery.
1.3.6.1.4.1.186.1.19.2.5.1.7.20DisplayString (SIZE(0..31))read-writemandatory
upsConfigBatteryRatedBackupTime
OBJECT-TYPE
The rated duration batteries can hold when unit is in backup mode with full load.
1.3.6.1.4.1.186.1.19.2.5.1.7.21NonNegativeIntegerread-writemandatory
upsConfigUserDefinedOverloadSetPoint
OBJECT-TYPE
The maximum output load % defined by the user.
1.3.6.1.4.1.186.1.19.2.5.1.7.22INTEGERread-writemandatory
upsConfigBatteryInstallationDate
OBJECT-TYPE
The battery install date.
1.3.6.1.4.1.186.1.19.2.5.1.7.23DisplayString (SIZE(10))read-writemandatory
upsConfigSysName
OBJECT-TYPE
A string identifying the UPS. This object is set by the administrator.
1.3.6.1.4.1.186.1.19.2.5.1.7.24DisplayString (SIZE(0..31))read-writemandatory
upsConfigAttachedDevices
OBJECT-TYPE
A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator.
1.3.6.1.4.1.186.1.19.2.5.1.7.25DisplayString (SIZE(0..31))read-writemandatory
upsConfigPassword
OBJECT-TYPE
Password.
1.3.6.1.4.1.186.1.19.2.5.1.7.26DisplayString (SIZE(0..31))read-writemandatory
upsTime
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.8
upsTimeRealDate
OBJECT-TYPE
Present date: year-month-date-day of the week.
1.3.6.1.4.1.186.1.19.2.5.1.8.1DisplayString (SIZE(0..31))read-writemandatory
upsTimeRealTime
OBJECT-TYPE
Present time (military format): hour-minute-second. For example,2:00pm would be 14:00:00.
1.3.6.1.4.1.186.1.19.2.5.1.8.2DisplayString (SIZE(0..31))read-writemandatory
upsTrap
OBJECT-IDENTITY
1.3.6.1.4.1.186.1.19.2.5.1.9

Notifications

NameOIDStatus
upsTrapFault
NOTIFICATION-TYPE
Alarm: One or more fault/status alarm(s) reported.
1.3.6.1.4.1.186.1.19.2.5.1.0.1
upsTrapFaultClear
NOTIFICATION-TYPE
Alarm Clear: One or more fault/status reported.
1.3.6.1.4.1.186.1.19.2.5.1.0.2
upsTrapOnBattery
NOTIFICATION-TYPE
Info: The UPS is on Battery Mode.
1.3.6.1.4.1.186.1.19.2.5.1.0.3
upsTrapOnBatteryClear
NOTIFICATION-TYPE
Info Clear: The UPS is on Battery Mode.
1.3.6.1.4.1.186.1.19.2.5.1.0.4
upsTrapBatteryLow
NOTIFICATION-TYPE
Warning: Battery Low Voltage.
1.3.6.1.4.1.186.1.19.2.5.1.0.5
upsTrapBatteryLowClear
NOTIFICATION-TYPE
Warning Clear: Battery Low Voltage.
1.3.6.1.4.1.186.1.19.2.5.1.0.6
upsTrapBatteryDepleted
NOTIFICATION-TYPE
Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load.
1.3.6.1.4.1.186.1.19.2.5.1.0.7
upsTrapBatteryDepletedClear
NOTIFICATION-TYPE
Warning Clear: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load..
1.3.6.1.4.1.186.1.19.2.5.1.0.8
upsTrapBatteryOverheat
NOTIFICATION-TYPE
Fault: Battery Overheat.
1.3.6.1.4.1.186.1.19.2.5.1.0.9
upsTrapBatteryOverheatClear
NOTIFICATION-TYPE
Fault Clear: Battery Overheat.
1.3.6.1.4.1.186.1.19.2.5.1.0.10
upsTrapBatteryVoltageAbnormal
NOTIFICATION-TYPE
Fault: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.11
upsTrapBatteryVoltageAbnormalClear
NOTIFICATION-TYPE
Fault Clear: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.12
upsTrapUPSOverheat
NOTIFICATION-TYPE
Fault: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.13
upsTrapUPSOverheatClear
NOTIFICATION-TYPE
Fault Clear: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.14
upsTrapPowerFailure
NOTIFICATION-TYPE
Info: Power Failure.
1.3.6.1.4.1.186.1.19.2.5.1.0.15
upsTrapPowerFailureClear
NOTIFICATION-TYPE
Info Clear: PowerFailure.
1.3.6.1.4.1.186.1.19.2.5.1.0.16
upsTrapUPSOverload
NOTIFICATION-TYPE
Fault: UPS Overload (OL), the output load exceeds the rated current. Decrease load.
1.3.6.1.4.1.186.1.19.2.5.1.0.17
upsTrapUPSOverloadClear
NOTIFICATION-TYPE
Fault Clear: UPS Overload (OL), the output load exceeds the rated current. Decrease load.
1.3.6.1.4.1.186.1.19.2.5.1.0.18
upsTrapUserDefinedOverloadWarning
NOTIFICATION-TYPE
Warning: The inverter output load % is greater than the user defined overload set point (default: 110%).
1.3.6.1.4.1.186.1.19.2.5.1.0.19
upsTrapUserDefinedOverloadWarningClear
NOTIFICATION-TYPE
Warning Clear: The inverter output load % is greater than the user defined overload set point (default: 110%).
1.3.6.1.4.1.186.1.19.2.5.1.0.20
upsTrapOnBypass
NOTIFICATION-TYPE
Warning:On Bypass.
1.3.6.1.4.1.186.1.19.2.5.1.0.21
upsTrapOnBypassClear
NOTIFICATION-TYPE
Warning Clear: On Bypass.
1.3.6.1.4.1.186.1.19.2.5.1.0.22
upsTrapOutputOff
NOTIFICATION-TYPE
Info: The UPS output is off.
1.3.6.1.4.1.186.1.19.2.5.1.0.23
upsTrapOutputOffClear
NOTIFICATION-TYPE
Info Clear: The UPS output is off.
1.3.6.1.4.1.186.1.19.2.5.1.0.24
upsTrapAsyncOperation
NOTIFICATION-TYPE
Warning: Inverter Synchronous.
1.3.6.1.4.1.186.1.19.2.5.1.0.25
upsTrapAsyncOperationClear
NOTIFICATION-TYPE
Warning Clear: Inverter Synchronous.
1.3.6.1.4.1.186.1.19.2.5.1.0.26
upsTrapDCBusOverCurrent
NOTIFICATION-TYPE
Fault: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.27
upsTrapDCBusOverCurrentClear
NOTIFICATION-TYPE
Fault Clear: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.28
upsTrapDCBusOverVoltage
NOTIFICATION-TYPE
Fault: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.29
upsTrapDCBusOverVoltageClear
NOTIFICATION-TYPE
Fault Clear: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.30
upsTrapDCBusUnderVoltage
NOTIFICATION-TYPE
Fault: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.31
upsTrapDCBusUnderVoltageClear
NOTIFICATION-TYPE
Fault Clear: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.32
upsTrapDCBusImbalance
NOTIFICATION-TYPE
Fault: DC Unbalance. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.33
upsTrapDCBusImbalanceClear
NOTIFICATION-TYPE
Fault Clear: DC Unbalance. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.34
upsTrapOutputUnderVoltage
NOTIFICATION-TYPE
Fault: Output Undervoltage. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.35
upsTrapOutputUnderVoltageClear
NOTIFICATION-TYPE
Fault Clear: Output Undervoltage. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.36
upsTrapOutputOverVoltage
NOTIFICATION-TYPE
Fault: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.37
upsTrapOutputOverVoltageClear
NOTIFICATION-TYPE
Fault Clear: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.38
upsTrapInverterOverload
NOTIFICATION-TYPE
Fault: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load.
1.3.6.1.4.1.186.1.19.2.5.1.0.39
upsTrapInverterOverloadClear
NOTIFICATION-TYPE
Fault Clear: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load.
1.3.6.1.4.1.186.1.19.2.5.1.0.40
upsTrapInverterOvercurrent
NOTIFICATION-TYPE
Fault: Inverter Overcurrent. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.41
upsTrapInverterOvercurrentClear
NOTIFICATION-TYPE
Fault Clear: Inverter Overcurrent. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.0.42
upsTrapRemotEyeCommError
NOTIFICATION-TYPE
Warning: RemotEye UPS communication error.
1.3.6.1.4.1.186.1.19.2.5.1.0.43
upsTrapRemotEyeCommErrorClear
NOTIFICATION-TYPE
Warning Clear:RemotEye UPS communication error.
1.3.6.1.4.1.186.1.19.2.5.1.0.44