MIBs Depot

SOCOMECUPS-MIB

Registered at
1.3.6.1.4.1.4555.1
Namespace
socomec
Source file
SOCOMECUPS-MIB
Digest
sha256:b662b0b8b4d5da0b69fdd5e10a5e342521c5bd2c64be89d6d4670f389b80978f

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso
SNMPv2-TCAutonomousType, DisplayString, TEXTUAL-CONVENTION, TestAndIncr, TimeInterval, TimeStamp

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC
SOCOMECUPS-MIB

Under this module's arcs

Where the registration tree carries on below this module.

ArcNameModule
1.3.6.1.4.1.4555.1.1network

Textual conventions

NameOIDSyntaxAccessStatus
NonNegativeInteger
type
PositiveInteger
type

Objects

NameOIDSyntaxAccessStatus
socomecSicon
OBJECT-IDENTITY
1.3.6.1.4.1.4555
software
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1
network
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1
netvision
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1
upsObjects
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1
upsIdent
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.1
upsIdentModel
OBJECT-TYPE
The UPS Model designation.
1.3.6.1.4.1.4555.1.1.1.1.1.1DisplayString (SIZE(0..63))read-onlymandatory
upsIdentUPSFirmwareVersion
OBJECT-TYPE
The UPS firmware version.
1.3.6.1.4.1.4555.1.1.1.1.1.2DisplayString (SIZE(0..63))read-onlymandatory
upsIdentAgentSoftwareVersion
OBJECT-TYPE
The UPS Net Vision software version.
1.3.6.1.4.1.4555.1.1.1.1.1.3DisplayString (SIZE(0..31))read-onlymandatory
upsIdentUpsSerialNumber
OBJECT-TYPE
The UPS serial no.
1.3.6.1.4.1.4555.1.1.1.1.1.4DisplayString (SIZE(0..15))read-onlymandatory
upsBattery
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.2
upsBatteryStatus
OBJECT-TYPE
The present battery status
1.3.6.1.4.1.4555.1.1.1.1.2.1INTEGER {unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6), upsOff(7)}read-onlymandatory
upsSecondsOnBattery
OBJECT-TYPE
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power.
1.3.6.1.4.1.4555.1.1.1.1.2.2INTEGERread-onlymandatory
upsEstimatedMinutesRemaining
OBJECT-TYPE
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
1.3.6.1.4.1.4555.1.1.1.1.2.3INTEGERread-onlymandatory
upsEstimatedChargeRemaining
OBJECT-TYPE
An estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.4555.1.1.1.1.2.4INTEGERread-onlymandatory
upsBatteryVoltage
OBJECT-TYPE
The magnitude of the present battery voltage in 0.1 Volt DC.
1.3.6.1.4.1.4555.1.1.1.1.2.5INTEGERread-onlymandatory
upsBatteryTemperature
OBJECT-TYPE
The ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.4555.1.1.1.1.2.6INTEGERread-onlymandatory
upsInput
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.3
upsInputNumLines
OBJECT-TYPE
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.4555.1.1.1.1.3.1INTEGERread-onlymandatory
upsInputFrequency
OBJECT-TYPE
The current input frequency to the UPS system in 0.1 HZ.
1.3.6.1.4.1.4555.1.1.1.1.3.2INTEGERread-onlymandatory
upsInputTable
OBJECT-TYPE
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
1.3.6.1.4.1.4555.1.1.1.1.3.3not-accessiblemandatory
upsInputEntry
OBJECT-TYPE
An entry containing information applicable to a particular input line.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1not-accessiblemandatory
upsInputLineIndex
OBJECT-TYPE
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1INTEGER (0..65535)read-onlymandatory
upsInputVoltage
OBJECT-TYPE
The input utility line voltage in 0.1 volts.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2INTEGERread-onlymandatory
upsInputCurrent
OBJECT-TYPE
The magnitude of the present input current in 0.1 A.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3INTEGERread-onlymandatory
upsInputVoltageMax
OBJECT-TYPE
The maximum utility line voltage in 0.1 VAC for last 1 minute.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4INTEGERread-onlymandatory
upsInputVoltageMin
OBJECT-TYPE
The minimum utility line voltage in 0.1 VAC for last 1 minute.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5INTEGERread-onlymandatory
upsOutput
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.4
upsOutputSource
OBJECT-TYPE
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
1.3.6.1.4.1.4555.1.1.1.1.4.1INTEGER {unknown(1), onInverter(2), onMains(3), ecoMode(4), onBypass(5), standby(6), onMaintenanceBypass(7), upsOff(8), normalMode(9)}read-onlymandatory
upsOutputFrequency
OBJECT-TYPE
The current output frequency of the UPS system in 0.1 of HZ.
1.3.6.1.4.1.4555.1.1.1.1.4.2INTEGERread-onlymandatory
upsOutputNumLines
OBJECT-TYPE
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.4555.1.1.1.1.4.3INTEGERread-onlymandatory
upsOutputTable
OBJECT-TYPE
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.4.1.4555.1.1.1.1.4.4not-accessiblemandatory
upsOutputEntry
OBJECT-TYPE
An entry containing information applicable to a particular output line.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1not-accessiblemandatory
upsOutputLineIndex
OBJECT-TYPE
The output line identifier.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1INTEGER (0..65535)read-onlymandatory
upsOutputVoltage
OBJECT-TYPE
The output voltage of the UPS system in 0.1 volts.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2INTEGERread-onlymandatory
upsOutputCurrent
OBJECT-TYPE
The output current of the UPS system in 0.1 Amps.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3INTEGERread-onlymandatory
upsOutputPercentLoad
OBJECT-TYPE
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4INTEGERread-onlymandatory
upsOutputKva
OBJECT-TYPE
Output KVA.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.5INTEGERread-onlymandatory
upsBypass
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.5
upsBypassFrequency
OBJECT-TYPE
The present bypass frequency.
1.3.6.1.4.1.4555.1.1.1.1.5.1INTEGERread-onlymandatory
upsBypassNumLines
OBJECT-TYPE
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
1.3.6.1.4.1.4555.1.1.1.1.5.2INTEGERread-onlymandatory
upsBypassTable
OBJECT-TYPE
A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
1.3.6.1.4.1.4555.1.1.1.1.5.3not-accessiblemandatory
upsBypassEntry
OBJECT-TYPE
An entry containing information applicable to a particular bypass input.
1.3.6.1.4.1.4555.1.1.1.1.5.3.1not-accessiblemandatory
upsBypassLineIndex
OBJECT-TYPE
The bypass line identifier.
1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1INTEGER (0..65535)read-onlymandatory
upsBypassVoltage
OBJECT-TYPE
The present bypass voltage.
1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2INTEGERread-onlymandatory
upsBypassCurrent
OBJECT-TYPE
The present bypass current.
1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3INTEGERread-onlymandatory
upsAlarm
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.6
upsAlarmsPresent
OBJECT-TYPE
The present number of active alarm conditions.
1.3.6.1.4.1.4555.1.1.1.1.6.1INTEGERread-onlymandatory
upsAlarmTable
OBJECT-TYPE
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.
1.3.6.1.4.1.4555.1.1.1.1.6.2not-accessiblemandatory
upsAlarmEntry
OBJECT-TYPE
An entry containing information applicable to a particular alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.2.1not-accessiblemandatory
upsAlarmId
OBJECT-TYPE
A unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.4555.1.1.1.1.6.2.1.1PositiveIntegerread-onlymandatory
upsAlarmDescr
OBJECT-TYPE
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
1.3.6.1.4.1.4555.1.1.1.1.6.2.1.2AutonomousTyperead-onlymandatory
upsAlarmTime
OBJECT-TYPE
The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.
1.3.6.1.4.1.4555.1.1.1.1.6.2.1.3TimeStampread-onlymandatory
upsAlarmExtDes
OBJECT-TYPE
Extra description.
1.3.6.1.4.1.4555.1.1.1.1.6.2.1.4DisplayStringread-onlymandatory
upsWellKnownAlarms
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.6.3
upsAlarmBatteryBad
OBJECT-TYPE
One or more batteries have been determined to require replacement.
1.3.6.1.4.1.4555.1.1.1.1.6.3.1INTEGERread-onlymandatory
upsAlarmOnBattery
OBJECT-TYPE
The UPS is drawing power from the batteries.
1.3.6.1.4.1.4555.1.1.1.1.6.3.2INTEGERread-onlymandatory
upsAlarmLowBattery
OBJECT-TYPE
The remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.4555.1.1.1.1.6.3.3INTEGERread-onlymandatory
upsAlarmDepletedBattery
OBJECT-TYPE
The UPS will be unable to sustain the present load when and if the utility power is lost.
1.3.6.1.4.1.4555.1.1.1.1.6.3.4INTEGERread-onlymandatory
upsAlarmTempBad
OBJECT-TYPE
A temperature is out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.5INTEGERread-onlymandatory
upsAlarmInputBad
OBJECT-TYPE
An input condition is out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.6INTEGERread-onlymandatory
upsAlarmOutputBad
OBJECT-TYPE
An output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.7INTEGERread-onlymandatory
upsAlarmOutputOverload
OBJECT-TYPE
The output load exceeds the UPS output capacity.
1.3.6.1.4.1.4555.1.1.1.1.6.3.8INTEGERread-onlymandatory
upsAlarmOnBypass
OBJECT-TYPE
The Bypass is presently engaged on the UPS.
1.3.6.1.4.1.4555.1.1.1.1.6.3.9INTEGERread-onlymandatory
upsAlarmBypassBad
OBJECT-TYPE
The Bypass is out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.10INTEGERread-onlymandatory
upsAlarmOutputOffAsRequested
OBJECT-TYPE
The UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.4555.1.1.1.1.6.3.11INTEGERread-onlymandatory
upsAlarmUpsOffAsRequested
OBJECT-TYPE
The entire UPS has shutdown as commanded.
1.3.6.1.4.1.4555.1.1.1.1.6.3.12INTEGERread-onlymandatory
upsAlarmChargerFailed
OBJECT-TYPE
An uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.4555.1.1.1.1.6.3.13INTEGERread-onlymandatory
upsAlarmUpsOutputOff
OBJECT-TYPE
The output of the UPS is in the off state.
1.3.6.1.4.1.4555.1.1.1.1.6.3.14INTEGERread-onlymandatory
upsAlarmUpsSystemOff
OBJECT-TYPE
The UPS system is in the off state.
1.3.6.1.4.1.4555.1.1.1.1.6.3.15INTEGERread-onlymandatory
upsAlarmFanFailure
OBJECT-TYPE
The failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.4555.1.1.1.1.6.3.16INTEGERread-onlymandatory
upsAlarmFuseFailure
OBJECT-TYPE
The failure of one or more fuses has been detected.
1.3.6.1.4.1.4555.1.1.1.1.6.3.17INTEGERread-onlymandatory
upsAlarmGeneralFault
OBJECT-TYPE
A general fault in the UPS has been detected.
1.3.6.1.4.1.4555.1.1.1.1.6.3.18INTEGERread-onlymandatory
upsAlarmDiagnosticTestFailed
OBJECT-TYPE
The result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.4555.1.1.1.1.6.3.19INTEGERread-onlymandatory
upsAlarmCommunicationLost
OBJECT-TYPE
A problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.4.1.4555.1.1.1.1.6.3.20INTEGERread-onlymandatory
upsAlarmAwaitingPower
OBJECT-TYPE
The UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.4.1.4555.1.1.1.1.6.3.21INTEGERread-onlymandatory
upsAlarmShutdownPending
OBJECT-TYPE
A upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.4555.1.1.1.1.6.3.22INTEGERread-onlymandatory
upsAlarmShutdownImminent
OBJECT-TYPE
The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.4555.1.1.1.1.6.3.23INTEGERread-onlymandatory
upsAlarmTestInProgress
OBJECT-TYPE
A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-TYPE macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-TYPE.
1.3.6.1.4.1.4555.1.1.1.1.6.3.24INTEGERread-onlymandatory
upsAlarmPowerSupplyFault
OBJECT-TYPE
Digital power supply fault.
1.3.6.1.4.1.4555.1.1.1.1.6.3.25INTEGERread-onlymandatory
upsAlarmAuxMainFail
OBJECT-TYPE
Auxiliary mains out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.26INTEGERread-onlymandatory
upsAlarmManualBypassClose
OBJECT-TYPE
Manual By-pass closed
1.3.6.1.4.1.4555.1.1.1.1.6.3.27INTEGERread-onlymandatory
upsAlarmShortCircuit
OBJECT-TYPE
Short Circuit on UPS output.
1.3.6.1.4.1.4555.1.1.1.1.6.3.28INTEGERread-onlymandatory
upsAlarmBatteryChargerFailure
OBJECT-TYPE
Battery charger failure.
1.3.6.1.4.1.4555.1.1.1.1.6.3.29INTEGERread-onlymandatory
upsAlarmInverterOverCurrent
OBJECT-TYPE
Inverter Over-current.
1.3.6.1.4.1.4555.1.1.1.1.6.3.30INTEGERread-onlymandatory
upsAlarmInverterDistorsion
OBJECT-TYPE
Excessive Inverter Distorsion.
1.3.6.1.4.1.4555.1.1.1.1.6.3.31INTEGERread-onlymandatory
upsAlarmPrechargeVoltageFail
OBJECT-TYPE
Precharge voltage out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.32INTEGERread-onlymandatory
upsAlarmBoostTooLow
OBJECT-TYPE
Boost output voltage too low.
1.3.6.1.4.1.4555.1.1.1.1.6.3.33INTEGERread-onlymandatory
upsAlarmBoostTooHigh
OBJECT-TYPE
Boost output voltage too high.
1.3.6.1.4.1.4555.1.1.1.1.6.3.34INTEGERread-onlymandatory
upsAlarmBatteryTooHigh
OBJECT-TYPE
Battery voltage too high.
1.3.6.1.4.1.4555.1.1.1.1.6.3.35INTEGERread-onlymandatory
upsAlarmImproperCondition
OBJECT-TYPE
Improper condition of use
1.3.6.1.4.1.4555.1.1.1.1.6.3.36INTEGERread-onlymandatory
upsAlarmOverloadTimeout
OBJECT-TYPE
Overload timeout blocking Inverter.
1.3.6.1.4.1.4555.1.1.1.1.6.3.37INTEGERread-onlymandatory
upsAlarmControlSystemFailure
OBJECT-TYPE
Microprocessor control system failure
1.3.6.1.4.1.4555.1.1.1.1.6.3.38INTEGERread-onlymandatory
upsAlarmDataCorrupted
OBJECT-TYPE
Configuration data map corrupted.
1.3.6.1.4.1.4555.1.1.1.1.6.3.39INTEGERread-onlymandatory
upsAlarmPllFault
OBJECT-TYPE
Pll fault.
1.3.6.1.4.1.4555.1.1.1.1.6.3.40INTEGERread-onlymandatory
upsAlarmInputGeneralAlarm
OBJECT-TYPE
Input mains general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.41INTEGERread-onlymandatory
upsAlarmRectifierGeneralAlarm
OBJECT-TYPE
Rectifier general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.42INTEGERread-onlymandatory
upsAlarmBoostGeneralAlarm
OBJECT-TYPE
Boost general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.43INTEGERread-onlymandatory
upsAlarmInverterGeneralAlarm
OBJECT-TYPE
Inverter general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.44INTEGERread-onlymandatory
upsAlarmBatteryGeneralAlarm
OBJECT-TYPE
Bettery charger general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.45INTEGERread-onlymandatory
upsAlarmOutputOver
OBJECT-TYPE
Output voltage over limit.
1.3.6.1.4.1.4555.1.1.1.1.6.3.46INTEGERread-onlymandatory
upsAlarmOutputUnder
OBJECT-TYPE
Output voltage under limit.
1.3.6.1.4.1.4555.1.1.1.1.6.3.47INTEGERread-onlymandatory
upsAlarmBypassGeneralAlarm
OBJECT-TYPE
Bypass charger general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.48INTEGERread-onlymandatory
upsAlarmStopForOverload
OBJECT-TYPE
Stop for overload.
1.3.6.1.4.1.4555.1.1.1.1.6.3.49INTEGERread-onlymandatory
upsAlarmImminentStop
OBJECT-TYPE
UPS imminent stop
1.3.6.1.4.1.4555.1.1.1.1.6.3.50INTEGERread-onlymandatory
upsAlarmModule1Alarm
OBJECT-TYPE
Module 1 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.51INTEGERread-onlymandatory
upsAlarmModule2Alarm
OBJECT-TYPE
Module 2 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.52INTEGERread-onlymandatory
upsAlarmModule3Alarm
OBJECT-TYPE
Module 3 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.53INTEGERread-onlymandatory
upsAlarmModule4Alarm
OBJECT-TYPE
Module 4 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.54INTEGERread-onlymandatory
upsAlarmModule5Alarm
OBJECT-TYPE
Module 5 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.55INTEGERread-onlymandatory
upsAlarmModule6Alarm
OBJECT-TYPE
Module 6 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.56INTEGERread-onlymandatory
upsAlarmExternalAlarm1
OBJECT-TYPE
External Alarm 1.
1.3.6.1.4.1.4555.1.1.1.1.6.3.57INTEGERread-onlymandatory
upsAlarmExternalAlarm2
OBJECT-TYPE
External Alarm 2.
1.3.6.1.4.1.4555.1.1.1.1.6.3.58INTEGERread-onlymandatory
upsAlarmExternalAlarm3
OBJECT-TYPE
External Alarm 3.
1.3.6.1.4.1.4555.1.1.1.1.6.3.59INTEGERread-onlymandatory
upsAlarmExternalAlarm4
OBJECT-TYPE
External Alarm 4.
1.3.6.1.4.1.4555.1.1.1.1.6.3.60INTEGERread-onlymandatory
upsAlarmEService
OBJECT-TYPE
E-Service General Alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.61INTEGERread-onlymandatory
upsAlarmRedundancyLost
OBJECT-TYPE
Redundancy lost
1.3.6.1.4.1.4555.1.1.1.1.6.3.62INTEGERread-onlymandatory
upsAlarmPeriodicServiceCheck
OBJECT-TYPE
Periodic service check up.
1.3.6.1.4.1.4555.1.1.1.1.6.3.63INTEGERread-onlymandatory
upsAlarmAllTransferDisabled
OBJECT-TYPE
Automatic and manual transfer disabled
1.3.6.1.4.1.4555.1.1.1.1.6.3.64INTEGERread-onlymandatory
upsAlarmAutoTransferDisabled
OBJECT-TYPE
Automatic transfer disabled
1.3.6.1.4.1.4555.1.1.1.1.6.3.65INTEGERread-onlymandatory
upsAlarmBatteryRoom
OBJECT-TYPE
Battery room alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.66INTEGERread-onlymandatory
upsAlarmManualBypass
OBJECT-TYPE
Manual bypass alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.67INTEGERread-onlymandatory
upsAlarmBatteryDischarged
OBJECT-TYPE
Battery Discharged
1.3.6.1.4.1.4555.1.1.1.1.6.3.68INTEGERread-onlymandatory
upsAlarmInsufficientResources
OBJECT-TYPE
Insufficient resources
1.3.6.1.4.1.4555.1.1.1.1.6.3.69INTEGERread-onlymandatory
upsAlarmOptionalBoards
OBJECT-TYPE
Optional boards general alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.70INTEGERread-onlymandatory
upsAlarmRectifierFault
OBJECT-TYPE
Rectifier fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.71INTEGERread-onlymandatory
upsAlarmBoostFault
OBJECT-TYPE
Boost fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.72INTEGERread-onlymandatory
upsAlarmInverterFault
OBJECT-TYPE
Inverter fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.73INTEGERread-onlymandatory
upsAlarmParallelModuleFault
OBJECT-TYPE
Parallel module fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.74INTEGERread-onlymandatory
upsAlarmGenSetGeneral
OBJECT-TYPE
Gen-set general alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.75INTEGERread-onlymandatory
upsAlarmGenSetFault
OBJECT-TYPE
Gen-set fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.76INTEGERread-onlymandatory
upsAlarmEmergencyStopActive
OBJECT-TYPE
Emergency stop active
1.3.6.1.4.1.4555.1.1.1.1.6.3.77INTEGERread-onlymandatory
upsAlarmBatteryCircuitOpen
OBJECT-TYPE
Battery circuit open
1.3.6.1.4.1.4555.1.1.1.1.6.3.78INTEGERread-onlymandatory
upsAlarmFansFailure
OBJECT-TYPE
Fans failure
1.3.6.1.4.1.4555.1.1.1.1.6.3.79INTEGERread-onlymandatory
upsAlarmPhaseRotationFault
OBJECT-TYPE
Phase rotation fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.80INTEGERread-onlymandatory
upsAlarmA62
OBJECT-TYPE
A62.
1.3.6.1.4.1.4555.1.1.1.1.6.3.81INTEGERread-onlymandatory
upsAlarmA63
OBJECT-TYPE
A63.
1.3.6.1.4.1.4555.1.1.1.1.6.3.82INTEGERread-onlymandatory
upsTest
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.7
upsTestId
OBJECT-TYPE
The test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of test, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. Tests in progress may be aborted by setting this variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has bee run, in which case the well known value upsTestNoTestsInitiated is returned.
1.3.6.1.4.1.4555.1.1.1.1.7.1OBJECT IDENTIFIERread-writemandatory
upsTestSpinLock
OBJECT-TYPE
A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: try_again: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lock_value = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lock_value, upsTestId = requested_test) if (error_index == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto try_again } if (error_index == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lock_value + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.
1.3.6.1.4.1.4555.1.1.1.1.7.2TestAndIncrread-writemandatory
upsTestResultsSummary
OBJECT-TYPE
The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
1.3.6.1.4.1.4555.1.1.1.1.7.3INTEGER {notActive(1), inProgress(2), byPass(3), failed(4)}read-onlymandatory
upsTestResultsDetail
OBJECT-TYPE
Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
1.3.6.1.4.1.4555.1.1.1.1.7.4DisplayStringread-onlymandatory
upsTestStartTime
OBJECT-TYPE
The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.
1.3.6.1.4.1.4555.1.1.1.1.7.5TimeStampread-onlymandatory
upsTestElapsedTime
OBJECT-TYPE
The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.
1.3.6.1.4.1.4555.1.1.1.1.7.6TimeIntervalread-onlymandatory
upsWellKnownTests
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.7.7
upsTestNoTestsInitiated
OBJECT-TYPE
No tests have been initiated and no test is in progress.
1.3.6.1.4.1.4555.1.1.1.1.7.7.1INTEGERread-onlymandatory
upsTestAbortTestInProgress
OBJECT-TYPE
The test in progress is to be aborted / the test in progress was aborted.
1.3.6.1.4.1.4555.1.1.1.1.7.7.2INTEGERread-onlymandatory
upsTestGeneralSystemsTest
OBJECT-TYPE
The manufacturer's standard test of UPS device systems.
1.3.6.1.4.1.4555.1.1.1.1.7.7.3INTEGERread-onlymandatory
upsTestQuickBatteryTest
OBJECT-TYPE
A test that is sufficient to determine if the battery needs replacement.
1.3.6.1.4.1.4555.1.1.1.1.7.7.4INTEGERread-onlymandatory
upsDeepBatteryCalibration
OBJECT-TYPE
The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.
1.3.6.1.4.1.4555.1.1.1.1.7.7.5INTEGERread-onlymandatory
upsControl
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.8
upsControlStatusControl
OBJECT-TYPE
This object Control UPS status
1.3.6.1.4.1.4555.1.1.1.1.8.1INTEGER {upsStandbyOn(1), upsStandbyOff(2), upsEcoMode(3), upsNormalMode(4), upsAlarmReset(5), upsCommandReset(6), upsBuzzerOff(7), upsOnBypass(8), upsOnInverter(9)}read-writemandatory
upsShutdownDelay
OBJECT-TYPE
This object set the delay time (in seconds) to turn UPS off after Net Vision broadcast shutdown request to connected clients
1.3.6.1.4.1.4555.1.1.1.1.8.2INTEGERread-writemandatory
upsTurnOffAfterShutdown
OBJECT-TYPE
This object enable/disable UPS turn off function after shutdown process complete
1.3.6.1.4.1.4555.1.1.1.1.8.3INTEGER {enable(1), disable(2)}read-writemandatory
upsControlShutdownParametersTable
OBJECT-TYPE
Table which describes the parametes for shutdown process when shutdown event occurs
1.3.6.1.4.1.4555.1.1.1.1.8.4not-accessiblemandatory
shutdownParametersEntry
OBJECT-TYPE
1.3.6.1.4.1.4555.1.1.1.1.8.4.1not-accessiblemandatory
upsControlEventDescr
OBJECT-TYPE
The shutdown event identification
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.1DisplayStringread-onlymandatory
upsControlEventStatus
OBJECT-TYPE
Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured.
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.2INTEGER {enable(1), disable(2)}read-writemandatory
upsControlDelay
OBJECT-TYPE
The Delay after the occurance of the curresponding shutdown event that Net Vision should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before the configured Shutdowntime when Net Vision will start sending the warning message to the connected clients. The value is in units of minutes.
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.3INTEGER (0..32767)read-writemandatory
upsControlFirstWarning
OBJECT-TYPE
The delay after the occurance of the curresponding shutdown event that the Net Vision will start sending the warning message to the connected clients. The value is in units of seconds
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.4INTEGER (0..32767)read-writemandatory
upsControlWarningInterval
OBJECT-TYPE
The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.5INTEGER (0..32767)read-writemandatory
upsControlSeverity
OBJECT-TYPE
Shutdown daemon severity.
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.6INTEGER (0..2)read-writemandatory
upsControlWeeklyScheduleTable
OBJECT-TYPE
The table to schedule shutting down the ups by weekly.
1.3.6.1.4.1.4555.1.1.1.1.8.5not-accessiblemandatory
upsControlWeeklyScheduleEntry
OBJECT-TYPE
The entries for each day.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1not-accessiblemandatory
upsControlWeeklyIndex
OBJECT-TYPE
The index of scheduled events.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.1INTEGER (1..7)read-onlymandatory
upsControlWeeklyShutdownDay
OBJECT-TYPE
The weekday on which the UPS should shut down.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.2INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)}read-writemandatory
upsControlWeeklyShutdownTime
OBJECT-TYPE
The time that the process of shutting down the UPS will be initiated in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.3DisplayString (SIZE(5))read-writemandatory
upsControlWeeklyRestartDay
OBJECT-TYPE
The weekday on which the UPS should restart
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.4INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)}read-writemandatory
upsControlWeeklyRestartTime
OBJECT-TYPE
The time the UPS will restart in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.5DisplayString (SIZE(5))read-writemandatory
upsControlSpecialScheduleTable
OBJECT-TYPE
The table to schedule shutting down the ups.
1.3.6.1.4.1.4555.1.1.1.1.8.6not-accessiblemandatory
upsControlSpecialScheduleEntry
OBJECT-TYPE
The entries for each day.
1.3.6.1.4.1.4555.1.1.1.1.8.6.1not-accessiblemandatory
upsControlSpecialIndex
OBJECT-TYPE
The index of scheduled events.
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.1INTEGER (1..8)read-onlymandatory
upsControlSpecialShutdownDay
OBJECT-TYPE
The date on which the UPS should shut down in dd/mm/yyyy format.
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.2DisplayString (SIZE(10))read-writemandatory
upsControlSpecialShutdownTime
OBJECT-TYPE
The time that the process of shutting down the UPS will be initiated in hh:mm:ss format
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.3DisplayString (SIZE(5))read-writemandatory
upsControlSpecialRestartDay
OBJECT-TYPE
The date on which the UPS should restart in dd/mm/yyyy format
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.4DisplayString (SIZE(10))read-writemandatory
upsControlSpecialRestartTime
OBJECT-TYPE
The time the UPS will restart in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.5DisplayString (SIZE(5))read-writemandatory
upsControlEcoModeScheduleTable
OBJECT-TYPE
The table to schedule enable/disable ups eco/mode by weekly.
1.3.6.1.4.1.4555.1.1.1.1.8.7not-accessiblemandatory
upsControlEcoModeScheduleEntry
OBJECT-TYPE
The entries for each day.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1not-accessiblemandatory
upsControlEcoModeIndex
OBJECT-TYPE
The index of scheduled events.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.1INTEGER (1..7)read-onlymandatory
upsControlEcoModeStartDay
OBJECT-TYPE
The weekday on which the UPS Eco/Mode should enable.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.2INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)}read-writemandatory
upsControlEcoModeStartTime
OBJECT-TYPE
The time that the UPS Eco/Mode will be enabled, in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.3DisplayString (SIZE(5))read-writemandatory
upsControlEcoModeEndDay
OBJECT-TYPE
The weekday on which the UPS Eco/Mode should disable
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.4INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)}read-writemandatory
upsControlEcoModeEndTime
OBJECT-TYPE
The time the UPS Eco/Mode will disabled, in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.5DisplayString (SIZE(5))read-writemandatory
upsConfig
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.9
upsConfigInputVoltage
OBJECT-TYPE
The magnitude of the nominal input voltage.
1.3.6.1.4.1.4555.1.1.1.1.9.1INTEGERread-onlymandatory
upsConfigInputFreq
OBJECT-TYPE
The nominal input frequency.
1.3.6.1.4.1.4555.1.1.1.1.9.2INTEGERread-onlymandatory
upsConfigOutputVoltage
OBJECT-TYPE
The magnitude of the nominal output voltage.
1.3.6.1.4.1.4555.1.1.1.1.9.3INTEGERread-onlymandatory
upsConfigOutputFreq
OBJECT-TYPE
The nominal output frequency.
1.3.6.1.4.1.4555.1.1.1.1.9.4INTEGERread-onlymandatory
upsDevicesTable
OBJECT-TYPE
The devices powered by UPS and registered to Net Vision
1.3.6.1.4.1.4555.1.1.1.1.9.5not-accessiblemandatory
upsDevicesEntry
OBJECT-TYPE
The devices protected by Net Vision
1.3.6.1.4.1.4555.1.1.1.1.9.5.1not-accessiblemandatory
indexOfDevice
OBJECT-TYPE
The index of the device that is plugged into the UPS.
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.1INTEGER (1..255)read-onlymandatory
addrOfDevice
OBJECT-TYPE
The ip address of the device.
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.2IpAddressread-onlymandatory
nameOfDevice
OBJECT-TYPE
The name/description of the device plugged into the UPS.
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.3DisplayString (SIZE(0..31))read-onlymandatory
timeOfConnection
OBJECT-TYPE
The that device registered to Net Vision
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.4DisplayStringread-onlymandatory
statusOfConnection
OBJECT-TYPE
status
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.5INTEGERread-onlymandatory
severityOfConnection
OBJECT-TYPE
severity
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.6INTEGERread-onlymandatory
upsAgent
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.10
upsAgentIpaddress
OBJECT-TYPE
The ip address that NMS can identify the managed device
1.3.6.1.4.1.4555.1.1.1.1.10.1IpAddressread-writemandatory
upsAgentGateway
OBJECT-TYPE
The default gateway that allow device managed through routers
1.3.6.1.4.1.4555.1.1.1.1.10.2IpAddressread-writemandatory
upsAgentSubnetMask
OBJECT-TYPE
Internet address subnet mask
1.3.6.1.4.1.4555.1.1.1.1.10.3IpAddressread-writemandatory
upsAgentDate
OBJECT-TYPE
The date in agent, format is (dd/mm/yyyy)
1.3.6.1.4.1.4555.1.1.1.1.10.4DisplayString (SIZE(10))read-writemandatory
upsAgentTime
OBJECT-TYPE
The time in agent, format is (hh:mm:ss)
1.3.6.1.4.1.4555.1.1.1.1.10.5DisplayString (SIZE(8))read-writemandatory
upsAgentNtpTimeServer
OBJECT-TYPE
1.3.6.1.4.1.4555.1.1.1.1.10.6DisplayStringread-writemandatory
upsAgentNtpTimeZone
OBJECT-TYPE
1.3.6.1.4.1.4555.1.1.1.1.10.7INTEGER {gmt1200dateLineWest(1), gmt1200kwajalein(2), gmt1100samoa(3), gmt1000hawaii(4), gmt0900alaska(5), gmt0800tijuana(6), gmt0700arizona(7), gmt0700chihuahua(8), gmt0700mountain(9), gmt0600camerica(10), gmt0600ctime(11), gmt0600guadalajara(12), gmt0600saskatchewan(13), gmt0500quito(14), gmt0500etime(15), gmt0500indiana(16), gmt0400atime(17), gmt0400caracas(18), gmt0400santiago(19), gmt0300newfoundland(20), gmt0300brasilia(21), gmt0300georgetown(22), gmt0300greenland(23), gmt0200atlantic(24), gmt0100azores(25), gmt0100cvi(26), gmt0000monrovia(27), gmt0000london(28), gmt0100vienna(29), gmt0100prague(30), gmt0100paris(31), gmt0100zagreb(32), gmt0100wcafrica(33), gmt0200minsk(34), gmt0200bucharest(35), gmt0200cairo(36), gmt0200pretoria(37), gmt0200vilnius(38), gmt0200jerusalem(39), gmt0300maghdad(40), gmt0300riyadh(41), gmt0300volgograd(42), gmt0300nairobi(43), gmt0300tehran(44), gmt0400muscat(45), gmt0400yerevan(46), gmt0400kabul(47), gmt0500ekaterinburg(48), gmt0500tashkent(49), gmt0500calcutta(50), gmt0500mumbai(51), gmt0500kathmandu(52), gmt0600novosibirsk(53), gmt0600dhaka(54), gmt0600jayawardenepura(55), gmt0600rangoon(56), gmt0700bangkok(57), gmt0700krasnoyarsk(58), gmt0800beijing(59), gmt0800irkutsk(60), gmt0800singapore(61), gmt0800perth(62), gmt0800taipei(63), gmt0900tokyo(64), gmt0900seoul(65), gmt0900yakutsk(66), gmt0900adelaide(67), gmt0900darwin(68), gmt1000brisbane(69), gmt1000canberra(70), gmt1000guam(71), gmt1000hobart(72), gmt1000vladivostok(73), gmt1100magadan(74), gmt1200auckland(75), gmt1200fiji(76), gmt1300alofa(77)}read-writemandatory
upsAgentHistoryLogFrequency
OBJECT-TYPE
The frequency of the updation of the history log. The value is in seconds
1.3.6.1.4.1.4555.1.1.1.1.10.8INTEGER (5..21600)read-writemandatory
upsAgentExtHistoryLogFrequency
OBJECT-TYPE
The ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which is determined by this object.
1.3.6.1.4.1.4555.1.1.1.1.10.9INTEGER (1..10080)read-writemandatory
upsAgentPollRate
OBJECT-TYPE
The frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second)
1.3.6.1.4.1.4555.1.1.1.1.10.10INTEGER (3..60)read-writemandatory
upsAgentBaudRate
OBJECT-TYPE
The serial port communication speed (2400/9600 allowed).
1.3.6.1.4.1.4555.1.1.1.1.10.11INTEGER {br2400(1), br9600(2), br19200(3)}read-writemandatory
upsAgentDhcpStatus
OBJECT-TYPE
Enable or disable DHCP-BootP capability
1.3.6.1.4.1.4555.1.1.1.1.10.12INTEGER {enabled(1), disabled(2)}read-writemandatory
upsAgentTelnetStatus
OBJECT-TYPE
Enable or disable telnet access
1.3.6.1.4.1.4555.1.1.1.1.10.13INTEGER {enabled(1), disabled(2)}read-writemandatory
upsAgentTftpStatus
OBJECT-TYPE
Enable or disable network upgrade capability
1.3.6.1.4.1.4555.1.1.1.1.10.14INTEGER {enabled(1), disabled(2)}read-writemandatory
upsAgentResetToDefault
OBJECT-TYPE
Reset all parameters of Net Vision to default value
1.3.6.1.4.1.4555.1.1.1.1.10.15INTEGER {reset(1), nothing(2)}read-writemandatory
upsAgentRestart
OBJECT-TYPE
Restart Net Vision
1.3.6.1.4.1.4555.1.1.1.1.10.16INTEGER {restart(1), nothing(2)}read-writemandatory
upsAgentClearAgentLog
OBJECT-TYPE
Clear agent log data
1.3.6.1.4.1.4555.1.1.1.1.10.17INTEGER {clear(1), nothing(2)}read-writemandatory
upsAgentClearEventLog
OBJECT-TYPE
Clear event log data
1.3.6.1.4.1.4555.1.1.1.1.10.18INTEGER {clear(1), nothing(2)}read-writemandatory
upsAgentClearExtHistoryLog
OBJECT-TYPE
Clear extented history log data
1.3.6.1.4.1.4555.1.1.1.1.10.19INTEGER {clear(1), nothing(2)}read-writemandatory
upsAgentClearHistoryLog
OBJECT-TYPE
Clear history log data
1.3.6.1.4.1.4555.1.1.1.1.10.20INTEGER {clear(1), nothing(2)}read-writemandatory
upsAgentTrapsReceiversTable
OBJECT-TYPE
A list of managers to send traps to. The number of entries is given by the value of upsAgentNumTrapReceivers
1.3.6.1.4.1.4555.1.1.1.1.10.21not-accessiblemandatory
upsAgentTrapsReceiversEntry
OBJECT-TYPE
The managers to send traps to.
1.3.6.1.4.1.4555.1.1.1.1.10.21.1not-accessiblemandatory
trapsIndex
OBJECT-TYPE
The index to a trap receiver entry.
1.3.6.1.4.1.4555.1.1.1.1.10.21.1.1INTEGER (1..8)read-onlymandatory
trapsReceiverAddr
OBJECT-TYPE
The IP address of the manager to send a trap to.
1.3.6.1.4.1.4555.1.1.1.1.10.21.1.2DisplayStringread-writemandatory
receiverCommunityString
OBJECT-TYPE
The community name to use in the trap when sent to the manager.
1.3.6.1.4.1.4555.1.1.1.1.10.21.1.3DisplayString (SIZE(0..15))read-writemandatory
receiverDescription
OBJECT-TYPE
Description of trap receivers
1.3.6.1.4.1.4555.1.1.1.1.10.21.1.4DisplayString (SIZE(0..31))read-writemandatory
upsAgentAccessControlTable
OBJECT-TYPE
A list of managers which can access Net Vision with private community string.
1.3.6.1.4.1.4555.1.1.1.1.10.22not-accessiblemandatory
upsAgentAccessControlEntry
OBJECT-TYPE
The managers.
1.3.6.1.4.1.4555.1.1.1.1.10.22.1not-accessiblemandatory
accessIndex
OBJECT-TYPE
The index to a access control entry.
1.3.6.1.4.1.4555.1.1.1.1.10.22.1.1INTEGERread-onlymandatory
accessControlAddr
OBJECT-TYPE
The IP address of the manager to access Net Vision
1.3.6.1.4.1.4555.1.1.1.1.10.22.1.2DisplayStringread-writemandatory
accessCommunityString
OBJECT-TYPE
The community name to use in the manager when access Net Vision
1.3.6.1.4.1.4555.1.1.1.1.10.22.1.3DisplayString (SIZE(0..15))read-writemandatory
accessControlMode
OBJECT-TYPE
Access type, only read-Write access type can change parameter of Net Vision
1.3.6.1.4.1.4555.1.1.1.1.10.22.1.4INTEGER {readOnly(1), readWrite(2), notAccess(3)}read-writemandatory
upsAgentMibVersion
OBJECT-TYPE
The version of MIB spec.
1.3.6.1.4.1.4555.1.1.1.1.10.23INTEGERread-onlymandatory
upsAgentTrapString
OBJECT-TYPE
This OID allows traps to be sent with an octet string argument that my not be defined in the. A get of this OID will return error or NULL string.
1.3.6.1.4.1.4555.1.1.1.1.10.50DisplayStringread-onlymandatory
emdStatus
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.1.11
emdSatatusTemperature
OBJECT-TYPE
The measurement of EMD temperature, in 0.1 degree
1.3.6.1.4.1.4555.1.1.1.1.11.1INTEGERread-onlymandatory
emdSatatusHumidity
OBJECT-TYPE
The measurement of EMD humidity, in 0.1 degree
1.3.6.1.4.1.4555.1.1.1.1.11.2INTEGERread-onlymandatory
upsTraps
OBJECT-IDENTITY
1.3.6.1.4.1.4555.1.1.1.2

Notifications

NameOIDStatus
upsTrapOnBattery
NOTIFICATION-TYPE
The UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery.
1.3.6.1.4.1.4555.1.1.1.2.0.1
upsTrapTestCompleted
NOTIFICATION-TYPE
This trap is sent upon completion of a UPS diagnostic test.
1.3.6.1.4.1.4555.1.1.1.2.0.2
upsTrapAlarmEntryAdded
NOTIFICATION-TYPE
This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and upsAlarmTestInProgress.
1.3.6.1.4.1.4555.1.1.1.2.0.3
upsTrapAlarmEntryRemoved
NOTIFICATION-TYPE
This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress.
1.3.6.1.4.1.4555.1.1.1.2.0.4
upsTrapUpsNormal
NOTIFICATION-TYPE
INFORMATION: The UPS status is normal.
1.3.6.1.4.1.4555.1.1.1.2.0.5
upsTrapUpsBattTestFailed
NOTIFICATION-TYPE
SEVERE: UPS failed the last test of battery.
1.3.6.1.4.1.4555.1.1.1.2.0.6
upsTrapOnBatteryPower
NOTIFICATION-TYPE
WARNING: The UPS has switched to battery backup power.
1.3.6.1.4.1.4555.1.1.1.2.0.7
upsTrapBatteryLow
NOTIFICATION-TYPE
SEVERE: Battery is near to be discharged.
1.3.6.1.4.1.4555.1.1.1.2.0.8
upsTrapPowerRestored
NOTIFICATION-TYPE
INFORMATION: Input power has been restored.
1.3.6.1.4.1.4555.1.1.1.2.0.9
upsTrapImminentStop
NOTIFICATION-TYPE
SEVERE: The UPS is near to switch off the output power.
1.3.6.1.4.1.4555.1.1.1.2.0.10
upsTrapTurnedOff
NOTIFICATION-TYPE
WARNING: The UPS has been turned off by the management station.
1.3.6.1.4.1.4555.1.1.1.2.0.11
upsTrapOverTemperature
NOTIFICATION-TYPE
SEVERE: The UPS has sensed a temperature greater than its limit.
1.3.6.1.4.1.4555.1.1.1.2.0.12
upsTrapOverload
NOTIFICATION-TYPE
SEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
1.3.6.1.4.1.4555.1.1.1.2.0.13
upsTrapOnMains
NOTIFICATION-TYPE
SEVERE: The UPS output is on mains.
1.3.6.1.4.1.4555.1.1.1.2.0.14
upsTrapRedoundancyLost
NOTIFICATION-TYPE
SEVERE: Redoundancy is lost.
1.3.6.1.4.1.4555.1.1.1.2.0.15
upsTrapEmdTempLow
NOTIFICATION-TYPE
SEVERE: EMD Sensor detected low temperature.
1.3.6.1.4.1.4555.1.1.1.2.0.16
upsTrapEmdTempHigh
NOTIFICATION-TYPE
SEVERE: EMD Sensor detected high temperature.
1.3.6.1.4.1.4555.1.1.1.2.0.17
upsTrapEmdHumidityLow
NOTIFICATION-TYPE
SEVERE: EMD Sensor detected low humidity.
1.3.6.1.4.1.4555.1.1.1.2.0.18
upsTrapEmdHumidityHigh
NOTIFICATION-TYPE
SEVERE: EMD Sensor detected high humidity.
1.3.6.1.4.1.4555.1.1.1.2.0.19
upsTrapEmdFirstInputActive
NOTIFICATION-TYPE
SEVERE: The <customized string_1> input is active.
1.3.6.1.4.1.4555.1.1.1.2.0.20
upsTrapEmdFirstInputRestored
NOTIFICATION-TYPE
INFORMATION: The <customized string_1> input is restored.
1.3.6.1.4.1.4555.1.1.1.2.0.21
upsTrapEmdSecondInputActive
NOTIFICATION-TYPE
SEVERE: The <customized string_2> input is active.
1.3.6.1.4.1.4555.1.1.1.2.0.22
upsTrapEmdSecondInputRestored
NOTIFICATION-TYPE
INFORMATION: The <customized string_2> input is restored.
1.3.6.1.4.1.4555.1.1.1.2.0.23