SOCOMECUPS-MIB
- Registered at
- 1.3.6.1.4.1.4555.1
- Namespace
- socomec
- Source file
SOCOMECUPS-MIB- Digest
sha256:b662b0b8b4d5da0b69fdd5e10a5e342521c5bd2c64be89d6d4670f389b80978f
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso |
| SNMPv2-TC | AutonomousType, DisplayString, TEXTUAL-CONVENTION, TestAndIncr, TimeInterval, TimeStamp |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
SNMPv2-CONF SNMPv2-SMI SNMPv2-TC SOCOMECUPS-MIB
Under this module's arcs
Where the registration tree carries on below this module.
| Arc | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.4555.1.1 | network |
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| NonNegativeInteger type | ||||
| PositiveInteger type |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| socomecSicon OBJECT-IDENTITY | 1.3.6.1.4.1.4555 | |||
| software OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1 | |||
| network OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1 | |||
| netvision OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1 | |||
| upsObjects OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1 | |||
| upsIdent OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.1 | |||
| upsIdentModel OBJECT-TYPE The UPS Model designation. | 1.3.6.1.4.1.4555.1.1.1.1.1.1 | DisplayString (SIZE(0..63)) | read-only | mandatory |
| upsIdentUPSFirmwareVersion OBJECT-TYPE The UPS firmware version. | 1.3.6.1.4.1.4555.1.1.1.1.1.2 | DisplayString (SIZE(0..63)) | read-only | mandatory |
| upsIdentAgentSoftwareVersion OBJECT-TYPE The UPS Net Vision software version. | 1.3.6.1.4.1.4555.1.1.1.1.1.3 | DisplayString (SIZE(0..31)) | read-only | mandatory |
| upsIdentUpsSerialNumber OBJECT-TYPE The UPS serial no. | 1.3.6.1.4.1.4555.1.1.1.1.1.4 | DisplayString (SIZE(0..15)) | read-only | mandatory |
| upsBattery OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.2 | |||
| upsBatteryStatus OBJECT-TYPE The present battery status | 1.3.6.1.4.1.4555.1.1.1.1.2.1 | INTEGER {unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6), upsOff(7)} | read-only | mandatory |
| upsSecondsOnBattery OBJECT-TYPE If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power. | 1.3.6.1.4.1.4555.1.1.1.1.2.2 | INTEGER | read-only | mandatory |
| upsEstimatedMinutesRemaining OBJECT-TYPE An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. | 1.3.6.1.4.1.4555.1.1.1.1.2.3 | INTEGER | read-only | mandatory |
| upsEstimatedChargeRemaining OBJECT-TYPE An estimate of the battery charge remaining expressed as a percent of full charge. | 1.3.6.1.4.1.4555.1.1.1.1.2.4 | INTEGER | read-only | mandatory |
| upsBatteryVoltage OBJECT-TYPE The magnitude of the present battery voltage in 0.1 Volt DC. | 1.3.6.1.4.1.4555.1.1.1.1.2.5 | INTEGER | read-only | mandatory |
| upsBatteryTemperature OBJECT-TYPE The ambient temperature at or near the UPS Battery casing. | 1.3.6.1.4.1.4555.1.1.1.1.2.6 | INTEGER | read-only | mandatory |
| upsInput OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.3 | |||
| upsInputNumLines OBJECT-TYPE The number of input lines utilized in this device. This variable indicates the number of rows in the input table. | 1.3.6.1.4.1.4555.1.1.1.1.3.1 | INTEGER | read-only | mandatory |
| upsInputFrequency OBJECT-TYPE The current input frequency to the UPS system in 0.1 HZ. | 1.3.6.1.4.1.4555.1.1.1.1.3.2 | INTEGER | read-only | mandatory |
| upsInputTable OBJECT-TYPE A list of input table entries. The number of entries is given by the value of upsInputNumLines. | 1.3.6.1.4.1.4555.1.1.1.1.3.3 | not-accessible | mandatory | |
| upsInputEntry OBJECT-TYPE An entry containing information applicable to a particular input line. | 1.3.6.1.4.1.4555.1.1.1.1.3.3.1 | not-accessible | mandatory | |
| upsInputLineIndex OBJECT-TYPE | 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1 | INTEGER (0..65535) | read-only | mandatory |
| upsInputVoltage OBJECT-TYPE The input utility line voltage in 0.1 volts. | 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2 | INTEGER | read-only | mandatory |
| upsInputCurrent OBJECT-TYPE The magnitude of the present input current in 0.1 A. | 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3 | INTEGER | read-only | mandatory |
| upsInputVoltageMax OBJECT-TYPE The maximum utility line voltage in 0.1 VAC for last 1 minute. | 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4 | INTEGER | read-only | mandatory |
| upsInputVoltageMin OBJECT-TYPE The minimum utility line voltage in 0.1 VAC for last 1 minute. | 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5 | INTEGER | read-only | mandatory |
| upsOutput OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.4 | |||
| upsOutputSource OBJECT-TYPE The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. | 1.3.6.1.4.1.4555.1.1.1.1.4.1 | INTEGER {unknown(1), onInverter(2), onMains(3), ecoMode(4), onBypass(5), standby(6), onMaintenanceBypass(7), upsOff(8), normalMode(9)} | read-only | mandatory |
| upsOutputFrequency OBJECT-TYPE The current output frequency of the UPS system in 0.1 of HZ. | 1.3.6.1.4.1.4555.1.1.1.1.4.2 | INTEGER | read-only | mandatory |
| upsOutputNumLines OBJECT-TYPE The number of output lines utilized in this device. This variable indicates the number of rows in the output table. | 1.3.6.1.4.1.4555.1.1.1.1.4.3 | INTEGER | read-only | mandatory |
| upsOutputTable OBJECT-TYPE A list of output table entries. The number of entries is given by the value of upsOutputNumLines. | 1.3.6.1.4.1.4555.1.1.1.1.4.4 | not-accessible | mandatory | |
| upsOutputEntry OBJECT-TYPE An entry containing information applicable to a particular output line. | 1.3.6.1.4.1.4555.1.1.1.1.4.4.1 | not-accessible | mandatory | |
| upsOutputLineIndex OBJECT-TYPE The output line identifier. | 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1 | INTEGER (0..65535) | read-only | mandatory |
| upsOutputVoltage OBJECT-TYPE The output voltage of the UPS system in 0.1 volts. | 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2 | INTEGER | read-only | mandatory |
| upsOutputCurrent OBJECT-TYPE The output current of the UPS system in 0.1 Amps. | 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3 | INTEGER | read-only | mandatory |
| upsOutputPercentLoad OBJECT-TYPE The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. | 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4 | INTEGER | read-only | mandatory |
| upsOutputKva OBJECT-TYPE Output KVA. | 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.5 | INTEGER | read-only | mandatory |
| upsBypass OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.5 | |||
| upsBypassFrequency OBJECT-TYPE The present bypass frequency. | 1.3.6.1.4.1.4555.1.1.1.1.5.1 | INTEGER | read-only | mandatory |
| upsBypassNumLines OBJECT-TYPE The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. | 1.3.6.1.4.1.4555.1.1.1.1.5.2 | INTEGER | read-only | mandatory |
| upsBypassTable OBJECT-TYPE A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines. | 1.3.6.1.4.1.4555.1.1.1.1.5.3 | not-accessible | mandatory | |
| upsBypassEntry OBJECT-TYPE An entry containing information applicable to a particular bypass input. | 1.3.6.1.4.1.4555.1.1.1.1.5.3.1 | not-accessible | mandatory | |
| upsBypassLineIndex OBJECT-TYPE The bypass line identifier. | 1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1 | INTEGER (0..65535) | read-only | mandatory |
| upsBypassVoltage OBJECT-TYPE The present bypass voltage. | 1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2 | INTEGER | read-only | mandatory |
| upsBypassCurrent OBJECT-TYPE The present bypass current. | 1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3 | INTEGER | read-only | mandatory |
| upsAlarm OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.6 | |||
| upsAlarmsPresent OBJECT-TYPE The present number of active alarm conditions. | 1.3.6.1.4.1.4555.1.1.1.1.6.1 | INTEGER | read-only | mandatory |
| upsAlarmTable OBJECT-TYPE A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent. | 1.3.6.1.4.1.4555.1.1.1.1.6.2 | not-accessible | mandatory | |
| upsAlarmEntry OBJECT-TYPE An entry containing information applicable to a particular alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.2.1 | not-accessible | mandatory | |
| upsAlarmId OBJECT-TYPE A unique identifier for an alarm condition. This value must remain constant. | 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.1 | PositiveInteger | read-only | mandatory |
| upsAlarmDescr OBJECT-TYPE A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. | 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.2 | AutonomousType | read-only | mandatory |
| upsAlarmTime OBJECT-TYPE The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0. | 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.3 | TimeStamp | read-only | mandatory |
| upsAlarmExtDes OBJECT-TYPE Extra description. | 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.4 | DisplayString | read-only | mandatory |
| upsWellKnownAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.6.3 | |||
| upsAlarmBatteryBad OBJECT-TYPE One or more batteries have been determined to require replacement. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.1 | INTEGER | read-only | mandatory |
| upsAlarmOnBattery OBJECT-TYPE The UPS is drawing power from the batteries. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.2 | INTEGER | read-only | mandatory |
| upsAlarmLowBattery OBJECT-TYPE The remaining battery run-time is less than or equal to upsConfigLowBattTime. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.3 | INTEGER | read-only | mandatory |
| upsAlarmDepletedBattery OBJECT-TYPE The UPS will be unable to sustain the present load when and if the utility power is lost. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.4 | INTEGER | read-only | mandatory |
| upsAlarmTempBad OBJECT-TYPE A temperature is out of tolerance. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.5 | INTEGER | read-only | mandatory |
| upsAlarmInputBad OBJECT-TYPE An input condition is out of tolerance. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.6 | INTEGER | read-only | mandatory |
| upsAlarmOutputBad OBJECT-TYPE An output condition (other than OutputOverload) is out of tolerance. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.7 | INTEGER | read-only | mandatory |
| upsAlarmOutputOverload OBJECT-TYPE The output load exceeds the UPS output capacity. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.8 | INTEGER | read-only | mandatory |
| upsAlarmOnBypass OBJECT-TYPE The Bypass is presently engaged on the UPS. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.9 | INTEGER | read-only | mandatory |
| upsAlarmBypassBad OBJECT-TYPE The Bypass is out of tolerance. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.10 | INTEGER | read-only | mandatory |
| upsAlarmOutputOffAsRequested OBJECT-TYPE The UPS has shutdown as requested, i.e., the output is off. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.11 | INTEGER | read-only | mandatory |
| upsAlarmUpsOffAsRequested OBJECT-TYPE The entire UPS has shutdown as commanded. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.12 | INTEGER | read-only | mandatory |
| upsAlarmChargerFailed OBJECT-TYPE An uncorrected problem has been detected within the UPS charger subsystem. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.13 | INTEGER | read-only | mandatory |
| upsAlarmUpsOutputOff OBJECT-TYPE The output of the UPS is in the off state. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.14 | INTEGER | read-only | mandatory |
| upsAlarmUpsSystemOff OBJECT-TYPE The UPS system is in the off state. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.15 | INTEGER | read-only | mandatory |
| upsAlarmFanFailure OBJECT-TYPE The failure of one or more fans in the UPS has been detected. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.16 | INTEGER | read-only | mandatory |
| upsAlarmFuseFailure OBJECT-TYPE The failure of one or more fuses has been detected. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.17 | INTEGER | read-only | mandatory |
| upsAlarmGeneralFault OBJECT-TYPE A general fault in the UPS has been detected. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.18 | INTEGER | read-only | mandatory |
| upsAlarmDiagnosticTestFailed OBJECT-TYPE The result of the last diagnostic test indicates a failure. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.19 | INTEGER | read-only | mandatory |
| upsAlarmCommunicationLost OBJECT-TYPE A problem has been encountered in the communications between the agent and the UPS. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.20 | INTEGER | read-only | mandatory |
| upsAlarmAwaitingPower OBJECT-TYPE The UPS output is off and the UPS is awaiting the return of input power. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.21 | INTEGER | read-only | mandatory |
| upsAlarmShutdownPending OBJECT-TYPE A upsShutdownAfterDelay countdown is underway. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.22 | INTEGER | read-only | mandatory |
| upsAlarmShutdownImminent OBJECT-TYPE The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.23 | INTEGER | read-only | mandatory |
| upsAlarmTestInProgress OBJECT-TYPE A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-TYPE macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-TYPE. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.24 | INTEGER | read-only | mandatory |
| upsAlarmPowerSupplyFault OBJECT-TYPE Digital power supply fault. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.25 | INTEGER | read-only | mandatory |
| upsAlarmAuxMainFail OBJECT-TYPE Auxiliary mains out of tolerance. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.26 | INTEGER | read-only | mandatory |
| upsAlarmManualBypassClose OBJECT-TYPE Manual By-pass closed | 1.3.6.1.4.1.4555.1.1.1.1.6.3.27 | INTEGER | read-only | mandatory |
| upsAlarmShortCircuit OBJECT-TYPE Short Circuit on UPS output. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.28 | INTEGER | read-only | mandatory |
| upsAlarmBatteryChargerFailure OBJECT-TYPE Battery charger failure. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.29 | INTEGER | read-only | mandatory |
| upsAlarmInverterOverCurrent OBJECT-TYPE Inverter Over-current. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.30 | INTEGER | read-only | mandatory |
| upsAlarmInverterDistorsion OBJECT-TYPE Excessive Inverter Distorsion. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.31 | INTEGER | read-only | mandatory |
| upsAlarmPrechargeVoltageFail OBJECT-TYPE Precharge voltage out of tolerance. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.32 | INTEGER | read-only | mandatory |
| upsAlarmBoostTooLow OBJECT-TYPE Boost output voltage too low. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.33 | INTEGER | read-only | mandatory |
| upsAlarmBoostTooHigh OBJECT-TYPE Boost output voltage too high. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.34 | INTEGER | read-only | mandatory |
| upsAlarmBatteryTooHigh OBJECT-TYPE Battery voltage too high. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.35 | INTEGER | read-only | mandatory |
| upsAlarmImproperCondition OBJECT-TYPE Improper condition of use | 1.3.6.1.4.1.4555.1.1.1.1.6.3.36 | INTEGER | read-only | mandatory |
| upsAlarmOverloadTimeout OBJECT-TYPE Overload timeout blocking Inverter. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.37 | INTEGER | read-only | mandatory |
| upsAlarmControlSystemFailure OBJECT-TYPE Microprocessor control system failure | 1.3.6.1.4.1.4555.1.1.1.1.6.3.38 | INTEGER | read-only | mandatory |
| upsAlarmDataCorrupted OBJECT-TYPE Configuration data map corrupted. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.39 | INTEGER | read-only | mandatory |
| upsAlarmPllFault OBJECT-TYPE Pll fault. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.40 | INTEGER | read-only | mandatory |
| upsAlarmInputGeneralAlarm OBJECT-TYPE Input mains general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.41 | INTEGER | read-only | mandatory |
| upsAlarmRectifierGeneralAlarm OBJECT-TYPE Rectifier general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.42 | INTEGER | read-only | mandatory |
| upsAlarmBoostGeneralAlarm OBJECT-TYPE Boost general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.43 | INTEGER | read-only | mandatory |
| upsAlarmInverterGeneralAlarm OBJECT-TYPE Inverter general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.44 | INTEGER | read-only | mandatory |
| upsAlarmBatteryGeneralAlarm OBJECT-TYPE Bettery charger general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.45 | INTEGER | read-only | mandatory |
| upsAlarmOutputOver OBJECT-TYPE Output voltage over limit. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.46 | INTEGER | read-only | mandatory |
| upsAlarmOutputUnder OBJECT-TYPE Output voltage under limit. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.47 | INTEGER | read-only | mandatory |
| upsAlarmBypassGeneralAlarm OBJECT-TYPE Bypass charger general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.48 | INTEGER | read-only | mandatory |
| upsAlarmStopForOverload OBJECT-TYPE Stop for overload. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.49 | INTEGER | read-only | mandatory |
| upsAlarmImminentStop OBJECT-TYPE UPS imminent stop | 1.3.6.1.4.1.4555.1.1.1.1.6.3.50 | INTEGER | read-only | mandatory |
| upsAlarmModule1Alarm OBJECT-TYPE Module 1 in parallel general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.51 | INTEGER | read-only | mandatory |
| upsAlarmModule2Alarm OBJECT-TYPE Module 2 in parallel general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.52 | INTEGER | read-only | mandatory |
| upsAlarmModule3Alarm OBJECT-TYPE Module 3 in parallel general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.53 | INTEGER | read-only | mandatory |
| upsAlarmModule4Alarm OBJECT-TYPE Module 4 in parallel general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.54 | INTEGER | read-only | mandatory |
| upsAlarmModule5Alarm OBJECT-TYPE Module 5 in parallel general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.55 | INTEGER | read-only | mandatory |
| upsAlarmModule6Alarm OBJECT-TYPE Module 6 in parallel general alarm. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.56 | INTEGER | read-only | mandatory |
| upsAlarmExternalAlarm1 OBJECT-TYPE External Alarm 1. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.57 | INTEGER | read-only | mandatory |
| upsAlarmExternalAlarm2 OBJECT-TYPE External Alarm 2. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.58 | INTEGER | read-only | mandatory |
| upsAlarmExternalAlarm3 OBJECT-TYPE External Alarm 3. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.59 | INTEGER | read-only | mandatory |
| upsAlarmExternalAlarm4 OBJECT-TYPE External Alarm 4. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.60 | INTEGER | read-only | mandatory |
| upsAlarmEService OBJECT-TYPE E-Service General Alarm | 1.3.6.1.4.1.4555.1.1.1.1.6.3.61 | INTEGER | read-only | mandatory |
| upsAlarmRedundancyLost OBJECT-TYPE Redundancy lost | 1.3.6.1.4.1.4555.1.1.1.1.6.3.62 | INTEGER | read-only | mandatory |
| upsAlarmPeriodicServiceCheck OBJECT-TYPE Periodic service check up. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.63 | INTEGER | read-only | mandatory |
| upsAlarmAllTransferDisabled OBJECT-TYPE Automatic and manual transfer disabled | 1.3.6.1.4.1.4555.1.1.1.1.6.3.64 | INTEGER | read-only | mandatory |
| upsAlarmAutoTransferDisabled OBJECT-TYPE Automatic transfer disabled | 1.3.6.1.4.1.4555.1.1.1.1.6.3.65 | INTEGER | read-only | mandatory |
| upsAlarmBatteryRoom OBJECT-TYPE Battery room alarm | 1.3.6.1.4.1.4555.1.1.1.1.6.3.66 | INTEGER | read-only | mandatory |
| upsAlarmManualBypass OBJECT-TYPE Manual bypass alarm | 1.3.6.1.4.1.4555.1.1.1.1.6.3.67 | INTEGER | read-only | mandatory |
| upsAlarmBatteryDischarged OBJECT-TYPE Battery Discharged | 1.3.6.1.4.1.4555.1.1.1.1.6.3.68 | INTEGER | read-only | mandatory |
| upsAlarmInsufficientResources OBJECT-TYPE Insufficient resources | 1.3.6.1.4.1.4555.1.1.1.1.6.3.69 | INTEGER | read-only | mandatory |
| upsAlarmOptionalBoards OBJECT-TYPE Optional boards general alarm | 1.3.6.1.4.1.4555.1.1.1.1.6.3.70 | INTEGER | read-only | mandatory |
| upsAlarmRectifierFault OBJECT-TYPE Rectifier fault | 1.3.6.1.4.1.4555.1.1.1.1.6.3.71 | INTEGER | read-only | mandatory |
| upsAlarmBoostFault OBJECT-TYPE Boost fault | 1.3.6.1.4.1.4555.1.1.1.1.6.3.72 | INTEGER | read-only | mandatory |
| upsAlarmInverterFault OBJECT-TYPE Inverter fault | 1.3.6.1.4.1.4555.1.1.1.1.6.3.73 | INTEGER | read-only | mandatory |
| upsAlarmParallelModuleFault OBJECT-TYPE Parallel module fault | 1.3.6.1.4.1.4555.1.1.1.1.6.3.74 | INTEGER | read-only | mandatory |
| upsAlarmGenSetGeneral OBJECT-TYPE Gen-set general alarm | 1.3.6.1.4.1.4555.1.1.1.1.6.3.75 | INTEGER | read-only | mandatory |
| upsAlarmGenSetFault OBJECT-TYPE Gen-set fault | 1.3.6.1.4.1.4555.1.1.1.1.6.3.76 | INTEGER | read-only | mandatory |
| upsAlarmEmergencyStopActive OBJECT-TYPE Emergency stop active | 1.3.6.1.4.1.4555.1.1.1.1.6.3.77 | INTEGER | read-only | mandatory |
| upsAlarmBatteryCircuitOpen OBJECT-TYPE Battery circuit open | 1.3.6.1.4.1.4555.1.1.1.1.6.3.78 | INTEGER | read-only | mandatory |
| upsAlarmFansFailure OBJECT-TYPE Fans failure | 1.3.6.1.4.1.4555.1.1.1.1.6.3.79 | INTEGER | read-only | mandatory |
| upsAlarmPhaseRotationFault OBJECT-TYPE Phase rotation fault | 1.3.6.1.4.1.4555.1.1.1.1.6.3.80 | INTEGER | read-only | mandatory |
| upsAlarmA62 OBJECT-TYPE A62. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.81 | INTEGER | read-only | mandatory |
| upsAlarmA63 OBJECT-TYPE A63. | 1.3.6.1.4.1.4555.1.1.1.1.6.3.82 | INTEGER | read-only | mandatory |
| upsTest OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.7 | |||
| upsTestId OBJECT-TYPE The test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of test, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. Tests in progress may be aborted by setting this variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has bee run, in which case the well known value upsTestNoTestsInitiated is returned. | 1.3.6.1.4.1.4555.1.1.1.1.7.1 | OBJECT IDENTIFIER | read-write | mandatory |
| upsTestSpinLock OBJECT-TYPE A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: try_again: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lock_value = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lock_value, upsTestId = requested_test) if (error_index == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto try_again } if (error_index == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lock_value + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1. | 1.3.6.1.4.1.4555.1.1.1.1.7.2 | TestAndIncr | read-write | mandatory |
| upsTestResultsSummary OBJECT-TYPE The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results. | 1.3.6.1.4.1.4555.1.1.1.1.7.3 | INTEGER {notActive(1), inProgress(2), byPass(3), failed(4)} | read-only | mandatory |
| upsTestResultsDetail OBJECT-TYPE Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned. | 1.3.6.1.4.1.4555.1.1.1.1.7.4 | DisplayString | read-only | mandatory |
| upsTestStartTime OBJECT-TYPE The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0. | 1.3.6.1.4.1.4555.1.1.1.1.7.5 | TimeStamp | read-only | mandatory |
| upsTestElapsedTime OBJECT-TYPE The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0. | 1.3.6.1.4.1.4555.1.1.1.1.7.6 | TimeInterval | read-only | mandatory |
| upsWellKnownTests OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.7.7 | |||
| upsTestNoTestsInitiated OBJECT-TYPE No tests have been initiated and no test is in progress. | 1.3.6.1.4.1.4555.1.1.1.1.7.7.1 | INTEGER | read-only | mandatory |
| upsTestAbortTestInProgress OBJECT-TYPE The test in progress is to be aborted / the test in progress was aborted. | 1.3.6.1.4.1.4555.1.1.1.1.7.7.2 | INTEGER | read-only | mandatory |
| upsTestGeneralSystemsTest OBJECT-TYPE The manufacturer's standard test of UPS device systems. | 1.3.6.1.4.1.4555.1.1.1.1.7.7.3 | INTEGER | read-only | mandatory |
| upsTestQuickBatteryTest OBJECT-TYPE A test that is sufficient to determine if the battery needs replacement. | 1.3.6.1.4.1.4555.1.1.1.1.7.7.4 | INTEGER | read-only | mandatory |
| upsDeepBatteryCalibration OBJECT-TYPE The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load. | 1.3.6.1.4.1.4555.1.1.1.1.7.7.5 | INTEGER | read-only | mandatory |
| upsControl OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.8 | |||
| upsControlStatusControl OBJECT-TYPE This object Control UPS status | 1.3.6.1.4.1.4555.1.1.1.1.8.1 | INTEGER {upsStandbyOn(1), upsStandbyOff(2), upsEcoMode(3), upsNormalMode(4), upsAlarmReset(5), upsCommandReset(6), upsBuzzerOff(7), upsOnBypass(8), upsOnInverter(9)} | read-write | mandatory |
| upsShutdownDelay OBJECT-TYPE This object set the delay time (in seconds) to turn UPS off after Net Vision broadcast shutdown request to connected clients | 1.3.6.1.4.1.4555.1.1.1.1.8.2 | INTEGER | read-write | mandatory |
| upsTurnOffAfterShutdown OBJECT-TYPE This object enable/disable UPS turn off function after shutdown process complete | 1.3.6.1.4.1.4555.1.1.1.1.8.3 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsControlShutdownParametersTable OBJECT-TYPE Table which describes the parametes for shutdown process when shutdown event occurs | 1.3.6.1.4.1.4555.1.1.1.1.8.4 | not-accessible | mandatory | |
| shutdownParametersEntry OBJECT-TYPE | 1.3.6.1.4.1.4555.1.1.1.1.8.4.1 | not-accessible | mandatory | |
| upsControlEventDescr OBJECT-TYPE The shutdown event identification | 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.1 | DisplayString | read-only | mandatory |
| upsControlEventStatus OBJECT-TYPE Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured. | 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.2 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| upsControlDelay OBJECT-TYPE The Delay after the occurance of the curresponding shutdown event that Net Vision should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before the configured Shutdowntime when Net Vision will start sending the warning message to the connected clients. The value is in units of minutes. | 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.3 | INTEGER (0..32767) | read-write | mandatory |
| upsControlFirstWarning OBJECT-TYPE The delay after the occurance of the curresponding shutdown event that the Net Vision will start sending the warning message to the connected clients. The value is in units of seconds | 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.4 | INTEGER (0..32767) | read-write | mandatory |
| upsControlWarningInterval OBJECT-TYPE The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds. | 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.5 | INTEGER (0..32767) | read-write | mandatory |
| upsControlSeverity OBJECT-TYPE Shutdown daemon severity. | 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.6 | INTEGER (0..2) | read-write | mandatory |
| upsControlWeeklyScheduleTable OBJECT-TYPE The table to schedule shutting down the ups by weekly. | 1.3.6.1.4.1.4555.1.1.1.1.8.5 | not-accessible | mandatory | |
| upsControlWeeklyScheduleEntry OBJECT-TYPE The entries for each day. | 1.3.6.1.4.1.4555.1.1.1.1.8.5.1 | not-accessible | mandatory | |
| upsControlWeeklyIndex OBJECT-TYPE The index of scheduled events. | 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.1 | INTEGER (1..7) | read-only | mandatory |
| upsControlWeeklyShutdownDay OBJECT-TYPE The weekday on which the UPS should shut down. | 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.2 | INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)} | read-write | mandatory |
| upsControlWeeklyShutdownTime OBJECT-TYPE The time that the process of shutting down the UPS will be initiated in hh:mm:ss format. | 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.3 | DisplayString (SIZE(5)) | read-write | mandatory |
| upsControlWeeklyRestartDay OBJECT-TYPE The weekday on which the UPS should restart | 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.4 | INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)} | read-write | mandatory |
| upsControlWeeklyRestartTime OBJECT-TYPE The time the UPS will restart in hh:mm:ss format. | 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.5 | DisplayString (SIZE(5)) | read-write | mandatory |
| upsControlSpecialScheduleTable OBJECT-TYPE The table to schedule shutting down the ups. | 1.3.6.1.4.1.4555.1.1.1.1.8.6 | not-accessible | mandatory | |
| upsControlSpecialScheduleEntry OBJECT-TYPE The entries for each day. | 1.3.6.1.4.1.4555.1.1.1.1.8.6.1 | not-accessible | mandatory | |
| upsControlSpecialIndex OBJECT-TYPE The index of scheduled events. | 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.1 | INTEGER (1..8) | read-only | mandatory |
| upsControlSpecialShutdownDay OBJECT-TYPE The date on which the UPS should shut down in dd/mm/yyyy format. | 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.2 | DisplayString (SIZE(10)) | read-write | mandatory |
| upsControlSpecialShutdownTime OBJECT-TYPE The time that the process of shutting down the UPS will be initiated in hh:mm:ss format | 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.3 | DisplayString (SIZE(5)) | read-write | mandatory |
| upsControlSpecialRestartDay OBJECT-TYPE The date on which the UPS should restart in dd/mm/yyyy format | 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.4 | DisplayString (SIZE(10)) | read-write | mandatory |
| upsControlSpecialRestartTime OBJECT-TYPE The time the UPS will restart in hh:mm:ss format. | 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.5 | DisplayString (SIZE(5)) | read-write | mandatory |
| upsControlEcoModeScheduleTable OBJECT-TYPE The table to schedule enable/disable ups eco/mode by weekly. | 1.3.6.1.4.1.4555.1.1.1.1.8.7 | not-accessible | mandatory | |
| upsControlEcoModeScheduleEntry OBJECT-TYPE The entries for each day. | 1.3.6.1.4.1.4555.1.1.1.1.8.7.1 | not-accessible | mandatory | |
| upsControlEcoModeIndex OBJECT-TYPE The index of scheduled events. | 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.1 | INTEGER (1..7) | read-only | mandatory |
| upsControlEcoModeStartDay OBJECT-TYPE The weekday on which the UPS Eco/Mode should enable. | 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.2 | INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)} | read-write | mandatory |
| upsControlEcoModeStartTime OBJECT-TYPE The time that the UPS Eco/Mode will be enabled, in hh:mm:ss format. | 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.3 | DisplayString (SIZE(5)) | read-write | mandatory |
| upsControlEcoModeEndDay OBJECT-TYPE The weekday on which the UPS Eco/Mode should disable | 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.4 | INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7), none(8)} | read-write | mandatory |
| upsControlEcoModeEndTime OBJECT-TYPE The time the UPS Eco/Mode will disabled, in hh:mm:ss format. | 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.5 | DisplayString (SIZE(5)) | read-write | mandatory |
| upsConfig OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.9 | |||
| upsConfigInputVoltage OBJECT-TYPE The magnitude of the nominal input voltage. | 1.3.6.1.4.1.4555.1.1.1.1.9.1 | INTEGER | read-only | mandatory |
| upsConfigInputFreq OBJECT-TYPE The nominal input frequency. | 1.3.6.1.4.1.4555.1.1.1.1.9.2 | INTEGER | read-only | mandatory |
| upsConfigOutputVoltage OBJECT-TYPE The magnitude of the nominal output voltage. | 1.3.6.1.4.1.4555.1.1.1.1.9.3 | INTEGER | read-only | mandatory |
| upsConfigOutputFreq OBJECT-TYPE The nominal output frequency. | 1.3.6.1.4.1.4555.1.1.1.1.9.4 | INTEGER | read-only | mandatory |
| upsDevicesTable OBJECT-TYPE The devices powered by UPS and registered to Net Vision | 1.3.6.1.4.1.4555.1.1.1.1.9.5 | not-accessible | mandatory | |
| upsDevicesEntry OBJECT-TYPE The devices protected by Net Vision | 1.3.6.1.4.1.4555.1.1.1.1.9.5.1 | not-accessible | mandatory | |
| indexOfDevice OBJECT-TYPE The index of the device that is plugged into the UPS. | 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.1 | INTEGER (1..255) | read-only | mandatory |
| addrOfDevice OBJECT-TYPE The ip address of the device. | 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.2 | IpAddress | read-only | mandatory |
| nameOfDevice OBJECT-TYPE The name/description of the device plugged into the UPS. | 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.3 | DisplayString (SIZE(0..31)) | read-only | mandatory |
| timeOfConnection OBJECT-TYPE The that device registered to Net Vision | 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.4 | DisplayString | read-only | mandatory |
| statusOfConnection OBJECT-TYPE status | 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.5 | INTEGER | read-only | mandatory |
| severityOfConnection OBJECT-TYPE severity | 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.6 | INTEGER | read-only | mandatory |
| upsAgent OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.10 | |||
| upsAgentIpaddress OBJECT-TYPE The ip address that NMS can identify the managed device | 1.3.6.1.4.1.4555.1.1.1.1.10.1 | IpAddress | read-write | mandatory |
| upsAgentGateway OBJECT-TYPE The default gateway that allow device managed through routers | 1.3.6.1.4.1.4555.1.1.1.1.10.2 | IpAddress | read-write | mandatory |
| upsAgentSubnetMask OBJECT-TYPE Internet address subnet mask | 1.3.6.1.4.1.4555.1.1.1.1.10.3 | IpAddress | read-write | mandatory |
| upsAgentDate OBJECT-TYPE The date in agent, format is (dd/mm/yyyy) | 1.3.6.1.4.1.4555.1.1.1.1.10.4 | DisplayString (SIZE(10)) | read-write | mandatory |
| upsAgentTime OBJECT-TYPE The time in agent, format is (hh:mm:ss) | 1.3.6.1.4.1.4555.1.1.1.1.10.5 | DisplayString (SIZE(8)) | read-write | mandatory |
| upsAgentNtpTimeServer OBJECT-TYPE | 1.3.6.1.4.1.4555.1.1.1.1.10.6 | DisplayString | read-write | mandatory |
| upsAgentNtpTimeZone OBJECT-TYPE | 1.3.6.1.4.1.4555.1.1.1.1.10.7 | INTEGER {gmt1200dateLineWest(1), gmt1200kwajalein(2), gmt1100samoa(3), gmt1000hawaii(4), gmt0900alaska(5), gmt0800tijuana(6), gmt0700arizona(7), gmt0700chihuahua(8), gmt0700mountain(9), gmt0600camerica(10), gmt0600ctime(11), gmt0600guadalajara(12), gmt0600saskatchewan(13), gmt0500quito(14), gmt0500etime(15), gmt0500indiana(16), gmt0400atime(17), gmt0400caracas(18), gmt0400santiago(19), gmt0300newfoundland(20), gmt0300brasilia(21), gmt0300georgetown(22), gmt0300greenland(23), gmt0200atlantic(24), gmt0100azores(25), gmt0100cvi(26), gmt0000monrovia(27), gmt0000london(28), gmt0100vienna(29), gmt0100prague(30), gmt0100paris(31), gmt0100zagreb(32), gmt0100wcafrica(33), gmt0200minsk(34), gmt0200bucharest(35), gmt0200cairo(36), gmt0200pretoria(37), gmt0200vilnius(38), gmt0200jerusalem(39), gmt0300maghdad(40), gmt0300riyadh(41), gmt0300volgograd(42), gmt0300nairobi(43), gmt0300tehran(44), gmt0400muscat(45), gmt0400yerevan(46), gmt0400kabul(47), gmt0500ekaterinburg(48), gmt0500tashkent(49), gmt0500calcutta(50), gmt0500mumbai(51), gmt0500kathmandu(52), gmt0600novosibirsk(53), gmt0600dhaka(54), gmt0600jayawardenepura(55), gmt0600rangoon(56), gmt0700bangkok(57), gmt0700krasnoyarsk(58), gmt0800beijing(59), gmt0800irkutsk(60), gmt0800singapore(61), gmt0800perth(62), gmt0800taipei(63), gmt0900tokyo(64), gmt0900seoul(65), gmt0900yakutsk(66), gmt0900adelaide(67), gmt0900darwin(68), gmt1000brisbane(69), gmt1000canberra(70), gmt1000guam(71), gmt1000hobart(72), gmt1000vladivostok(73), gmt1100magadan(74), gmt1200auckland(75), gmt1200fiji(76), gmt1300alofa(77)} | read-write | mandatory |
| upsAgentHistoryLogFrequency OBJECT-TYPE The frequency of the updation of the history log. The value is in seconds | 1.3.6.1.4.1.4555.1.1.1.1.10.8 | INTEGER (5..21600) | read-write | mandatory |
| upsAgentExtHistoryLogFrequency OBJECT-TYPE The ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which is determined by this object. | 1.3.6.1.4.1.4555.1.1.1.1.10.9 | INTEGER (1..10080) | read-write | mandatory |
| upsAgentPollRate OBJECT-TYPE The frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second) | 1.3.6.1.4.1.4555.1.1.1.1.10.10 | INTEGER (3..60) | read-write | mandatory |
| upsAgentBaudRate OBJECT-TYPE The serial port communication speed (2400/9600 allowed). | 1.3.6.1.4.1.4555.1.1.1.1.10.11 | INTEGER {br2400(1), br9600(2), br19200(3)} | read-write | mandatory |
| upsAgentDhcpStatus OBJECT-TYPE Enable or disable DHCP-BootP capability | 1.3.6.1.4.1.4555.1.1.1.1.10.12 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| upsAgentTelnetStatus OBJECT-TYPE Enable or disable telnet access | 1.3.6.1.4.1.4555.1.1.1.1.10.13 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| upsAgentTftpStatus OBJECT-TYPE Enable or disable network upgrade capability | 1.3.6.1.4.1.4555.1.1.1.1.10.14 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| upsAgentResetToDefault OBJECT-TYPE Reset all parameters of Net Vision to default value | 1.3.6.1.4.1.4555.1.1.1.1.10.15 | INTEGER {reset(1), nothing(2)} | read-write | mandatory |
| upsAgentRestart OBJECT-TYPE Restart Net Vision | 1.3.6.1.4.1.4555.1.1.1.1.10.16 | INTEGER {restart(1), nothing(2)} | read-write | mandatory |
| upsAgentClearAgentLog OBJECT-TYPE Clear agent log data | 1.3.6.1.4.1.4555.1.1.1.1.10.17 | INTEGER {clear(1), nothing(2)} | read-write | mandatory |
| upsAgentClearEventLog OBJECT-TYPE Clear event log data | 1.3.6.1.4.1.4555.1.1.1.1.10.18 | INTEGER {clear(1), nothing(2)} | read-write | mandatory |
| upsAgentClearExtHistoryLog OBJECT-TYPE Clear extented history log data | 1.3.6.1.4.1.4555.1.1.1.1.10.19 | INTEGER {clear(1), nothing(2)} | read-write | mandatory |
| upsAgentClearHistoryLog OBJECT-TYPE Clear history log data | 1.3.6.1.4.1.4555.1.1.1.1.10.20 | INTEGER {clear(1), nothing(2)} | read-write | mandatory |
| upsAgentTrapsReceiversTable OBJECT-TYPE A list of managers to send traps to. The number of entries is given by the value of upsAgentNumTrapReceivers | 1.3.6.1.4.1.4555.1.1.1.1.10.21 | not-accessible | mandatory | |
| upsAgentTrapsReceiversEntry OBJECT-TYPE The managers to send traps to. | 1.3.6.1.4.1.4555.1.1.1.1.10.21.1 | not-accessible | mandatory | |
| trapsIndex OBJECT-TYPE The index to a trap receiver entry. | 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.1 | INTEGER (1..8) | read-only | mandatory |
| trapsReceiverAddr OBJECT-TYPE The IP address of the manager to send a trap to. | 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.2 | DisplayString | read-write | mandatory |
| receiverCommunityString OBJECT-TYPE The community name to use in the trap when sent to the manager. | 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.3 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| receiverDescription OBJECT-TYPE Description of trap receivers | 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.4 | DisplayString (SIZE(0..31)) | read-write | mandatory |
| upsAgentAccessControlTable OBJECT-TYPE A list of managers which can access Net Vision with private community string. | 1.3.6.1.4.1.4555.1.1.1.1.10.22 | not-accessible | mandatory | |
| upsAgentAccessControlEntry OBJECT-TYPE The managers. | 1.3.6.1.4.1.4555.1.1.1.1.10.22.1 | not-accessible | mandatory | |
| accessIndex OBJECT-TYPE The index to a access control entry. | 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.1 | INTEGER | read-only | mandatory |
| accessControlAddr OBJECT-TYPE The IP address of the manager to access Net Vision | 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.2 | DisplayString | read-write | mandatory |
| accessCommunityString OBJECT-TYPE The community name to use in the manager when access Net Vision | 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.3 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| accessControlMode OBJECT-TYPE Access type, only read-Write access type can change parameter of Net Vision | 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.4 | INTEGER {readOnly(1), readWrite(2), notAccess(3)} | read-write | mandatory |
| upsAgentMibVersion OBJECT-TYPE The version of MIB spec. | 1.3.6.1.4.1.4555.1.1.1.1.10.23 | INTEGER | read-only | mandatory |
| upsAgentTrapString OBJECT-TYPE This OID allows traps to be sent with an octet string argument that my not be defined in the. A get of this OID will return error or NULL string. | 1.3.6.1.4.1.4555.1.1.1.1.10.50 | DisplayString | read-only | mandatory |
| emdStatus OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.1.11 | |||
| emdSatatusTemperature OBJECT-TYPE The measurement of EMD temperature, in 0.1 degree | 1.3.6.1.4.1.4555.1.1.1.1.11.1 | INTEGER | read-only | mandatory |
| emdSatatusHumidity OBJECT-TYPE The measurement of EMD humidity, in 0.1 degree | 1.3.6.1.4.1.4555.1.1.1.1.11.2 | INTEGER | read-only | mandatory |
| upsTraps OBJECT-IDENTITY | 1.3.6.1.4.1.4555.1.1.1.2 |
Notifications
| Name | OID | Status |
|---|---|---|
| upsTrapOnBattery NOTIFICATION-TYPE The UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery. | 1.3.6.1.4.1.4555.1.1.1.2.0.1 | |
| upsTrapTestCompleted NOTIFICATION-TYPE This trap is sent upon completion of a UPS diagnostic test. | 1.3.6.1.4.1.4555.1.1.1.2.0.2 | |
| upsTrapAlarmEntryAdded NOTIFICATION-TYPE This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and upsAlarmTestInProgress. | 1.3.6.1.4.1.4555.1.1.1.2.0.3 | |
| upsTrapAlarmEntryRemoved NOTIFICATION-TYPE This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress. | 1.3.6.1.4.1.4555.1.1.1.2.0.4 | |
| upsTrapUpsNormal NOTIFICATION-TYPE INFORMATION: The UPS status is normal. | 1.3.6.1.4.1.4555.1.1.1.2.0.5 | |
| upsTrapUpsBattTestFailed NOTIFICATION-TYPE SEVERE: UPS failed the last test of battery. | 1.3.6.1.4.1.4555.1.1.1.2.0.6 | |
| upsTrapOnBatteryPower NOTIFICATION-TYPE WARNING: The UPS has switched to battery backup power. | 1.3.6.1.4.1.4555.1.1.1.2.0.7 | |
| upsTrapBatteryLow NOTIFICATION-TYPE SEVERE: Battery is near to be discharged. | 1.3.6.1.4.1.4555.1.1.1.2.0.8 | |
| upsTrapPowerRestored NOTIFICATION-TYPE INFORMATION: Input power has been restored. | 1.3.6.1.4.1.4555.1.1.1.2.0.9 | |
| upsTrapImminentStop NOTIFICATION-TYPE SEVERE: The UPS is near to switch off the output power. | 1.3.6.1.4.1.4555.1.1.1.2.0.10 | |
| upsTrapTurnedOff NOTIFICATION-TYPE WARNING: The UPS has been turned off by the management station. | 1.3.6.1.4.1.4555.1.1.1.2.0.11 | |
| upsTrapOverTemperature NOTIFICATION-TYPE SEVERE: The UPS has sensed a temperature greater than its limit. | 1.3.6.1.4.1.4555.1.1.1.2.0.12 | |
| upsTrapOverload NOTIFICATION-TYPE SEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity. | 1.3.6.1.4.1.4555.1.1.1.2.0.13 | |
| upsTrapOnMains NOTIFICATION-TYPE SEVERE: The UPS output is on mains. | 1.3.6.1.4.1.4555.1.1.1.2.0.14 | |
| upsTrapRedoundancyLost NOTIFICATION-TYPE SEVERE: Redoundancy is lost. | 1.3.6.1.4.1.4555.1.1.1.2.0.15 | |
| upsTrapEmdTempLow NOTIFICATION-TYPE SEVERE: EMD Sensor detected low temperature. | 1.3.6.1.4.1.4555.1.1.1.2.0.16 | |
| upsTrapEmdTempHigh NOTIFICATION-TYPE SEVERE: EMD Sensor detected high temperature. | 1.3.6.1.4.1.4555.1.1.1.2.0.17 | |
| upsTrapEmdHumidityLow NOTIFICATION-TYPE SEVERE: EMD Sensor detected low humidity. | 1.3.6.1.4.1.4555.1.1.1.2.0.18 | |
| upsTrapEmdHumidityHigh NOTIFICATION-TYPE SEVERE: EMD Sensor detected high humidity. | 1.3.6.1.4.1.4555.1.1.1.2.0.19 | |
| upsTrapEmdFirstInputActive NOTIFICATION-TYPE SEVERE: The <customized string_1> input is active. | 1.3.6.1.4.1.4555.1.1.1.2.0.20 | |
| upsTrapEmdFirstInputRestored NOTIFICATION-TYPE INFORMATION: The <customized string_1> input is restored. | 1.3.6.1.4.1.4555.1.1.1.2.0.21 | |
| upsTrapEmdSecondInputActive NOTIFICATION-TYPE SEVERE: The <customized string_2> input is active. | 1.3.6.1.4.1.4555.1.1.1.2.0.22 | |
| upsTrapEmdSecondInputRestored NOTIFICATION-TYPE INFORMATION: The <customized string_2> input is restored. | 1.3.6.1.4.1.4555.1.1.1.2.0.23 |