MIBs Depot

SITE-MONITORING-MIB

Registered at
1.3.6.1.4.1.26854
Last updated
2017-05-16 16:00
Organization
Alpha Innovations
Revisions
2017-05-16 16:00
Namespace
alpha
Source file
SITE-MONITORING-MIB
Digest
sha256:3079408802c166e45015608da9a2e8c22daaa174c4a9d8f351f8c2e64cd0daab

Description

Alpha Innovations SNMP corporate naming convention Organises the SNMP OIDs according to the design centres that generate the different MIBs

Contact

Jean-Philippe Vanhulst Postal: Alpha Innovations Rue Alexander Fleming 1 B-1348 Louvain-la-Neuve Belgium phone +32 10 438 382 e-mail mail@alphainnovations.eu

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-SMIInteger32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, enterprises, iso
SNMPv2-TCDisplayString, RowStatus, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

SITE-MONITORING-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
atsa
OBJECT-IDENTITY
1.3.6.1.4.1.26854
atsaCorporate
OBJECT-IDENTITY
1.3.6.1.4.1.26854.1
atsaUs
OBJECT-IDENTITY
1.3.6.1.4.1.26854.2
atsaEu
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3
atsaEuDevices
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.1
siteMonitoring
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2
siteV1
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1
siteV1GlobalStatus
OBJECT-TYPE
A textual string (alarms, normal or unknown) containing the status of the Site
1.3.6.1.4.1.26854.3.2.1.1DisplayString (SIZE(0..255))read-onlycurrent
siteV1GlobalAlarmSeverityType
OBJECT-TYPE
The alarm severity type (critical, major, minor, warning, none, disabled) of the Site
1.3.6.1.4.1.26854.3.2.1.2DisplayStringread-onlycurrent
siteV1GlobalAlarmSeverityLevel
OBJECT-TYPE
The alarm severity level (0-9) of the Site
1.3.6.1.4.1.26854.3.2.1.3Integer32read-onlycurrent
siteV1GlobalAlarmSeverityTypeInt
OBJECT-TYPE
The alarm severity type as integer (critical=4, major=3, minor=2, warning=1, none=0) of the Site
1.3.6.1.4.1.26854.3.2.1.4Integer32read-onlycurrent
siteV1Description
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.10
siteV1DescriptionNumber
OBJECT-TYPE
The number of entries in the Site Description table
1.3.6.1.4.1.26854.3.2.1.10.1Integer32read-onlycurrent
siteV1DescriptionTable
OBJECT-TYPE
The Description table of the Site
1.3.6.1.4.1.26854.3.2.1.10.2not-accessiblecurrent
siteV1DescriptionEntry
OBJECT-TYPE
A Description entry
1.3.6.1.4.1.26854.3.2.1.10.2.1not-accessiblecurrent
siteV1DescriptionIndex
OBJECT-TYPE
Description Index
1.3.6.1.4.1.26854.3.2.1.10.2.1.1Unsigned32not-accessiblecurrent
siteV1DescriptionName
OBJECT-TYPE
Description Name
1.3.6.1.4.1.26854.3.2.1.10.2.1.2DisplayStringread-onlycurrent
siteV1DescriptionValue
OBJECT-TYPE
Description Value
1.3.6.1.4.1.26854.3.2.1.10.2.1.3DisplayStringread-createcurrent
siteV1DescriptionEntryStatus
OBJECT-TYPE
The status of this table entry
1.3.6.1.4.1.26854.3.2.1.10.2.1.4RowStatusread-createcurrent
siteV1DescriptionList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.10.3
siteV1DescDescriptionSiteNumber
OBJECT-TYPE
The identification number of the site
1.3.6.1.4.1.26854.3.2.1.10.3.1DisplayStringread-writecurrent
siteV1DescDescriptionSiteName
OBJECT-TYPE
The name of the site
1.3.6.1.4.1.26854.3.2.1.10.3.2DisplayStringread-writecurrent
siteV1DescDescriptionShortDescription
OBJECT-TYPE
A short description of the site
1.3.6.1.4.1.26854.3.2.1.10.3.3DisplayStringread-writecurrent
siteV1DescDescriptionInfo
OBJECT-TYPE
Some more information about the site
1.3.6.1.4.1.26854.3.2.1.10.3.4DisplayStringread-writecurrent
siteV1DescDescriptionDescription
OBJECT-TYPE
A free text zone to write a system description
1.3.6.1.4.1.26854.3.2.1.10.3.5DisplayStringread-writecurrent
siteV1DescDescriptionReference
OBJECT-TYPE
A free text zone to write the customer reference of the system
1.3.6.1.4.1.26854.3.2.1.10.3.6DisplayStringread-writecurrent
siteV1DescDescriptionContactName
OBJECT-TYPE
Contact Name
1.3.6.1.4.1.26854.3.2.1.10.3.7DisplayStringread-writecurrent
siteV1DescDescriptionPhoneNumber
OBJECT-TYPE
Phone Number
1.3.6.1.4.1.26854.3.2.1.10.3.8DisplayStringread-writecurrent
siteV1DescDescriptionStreet
OBJECT-TYPE
Street part of the site address
1.3.6.1.4.1.26854.3.2.1.10.3.11DisplayStringread-writecurrent
siteV1DescDescriptionCity
OBJECT-TYPE
City part of the site address
1.3.6.1.4.1.26854.3.2.1.10.3.12DisplayStringread-writecurrent
siteV1DescDescriptionProvince
OBJECT-TYPE
Province part of the site address
1.3.6.1.4.1.26854.3.2.1.10.3.13DisplayStringread-writecurrent
siteV1DescDescriptionPostalCode
OBJECT-TYPE
Postal Code part of the site address
1.3.6.1.4.1.26854.3.2.1.10.3.14DisplayStringread-writecurrent
siteV1DescDescriptionRegion
OBJECT-TYPE
Region part of the site address
1.3.6.1.4.1.26854.3.2.1.10.3.15DisplayStringread-writecurrent
siteV1DescDescriptionCountry
OBJECT-TYPE
Country part of the site address
1.3.6.1.4.1.26854.3.2.1.10.3.16DisplayStringread-writecurrent
siteV1DescDescriptionGroup1
OBJECT-TYPE
Group Level 1 (For Armada Clustering)
1.3.6.1.4.1.26854.3.2.1.10.3.21DisplayStringread-writecurrent
siteV1DescDescriptionGroup2
OBJECT-TYPE
Group Level 2 (For Armada Clustering)
1.3.6.1.4.1.26854.3.2.1.10.3.22DisplayStringread-writecurrent
siteV1DescDescriptionGroup3
OBJECT-TYPE
Group Level 3 (For Armada Clustering)
1.3.6.1.4.1.26854.3.2.1.10.3.23DisplayStringread-writecurrent
siteV1DescDescriptionGroup4
OBJECT-TYPE
Group Level 4 (For Armada Clustering)
1.3.6.1.4.1.26854.3.2.1.10.3.24DisplayStringread-writecurrent
siteV1DescDescriptionGroup5
OBJECT-TYPE
Group Level 5 (For Armada Clustering)
1.3.6.1.4.1.26854.3.2.1.10.3.25DisplayStringread-writecurrent
siteV1DescDescriptionLatitude
OBJECT-TYPE
The latitude of the site
1.3.6.1.4.1.26854.3.2.1.10.3.31DisplayStringread-writecurrent
siteV1DescDescriptionLongitude
OBJECT-TYPE
The longitude of the site
1.3.6.1.4.1.26854.3.2.1.10.3.32DisplayStringread-writecurrent
siteV1DescDescriptionAltitude
OBJECT-TYPE
The altitude of the site
1.3.6.1.4.1.26854.3.2.1.10.3.33DisplayStringread-writecurrent
siteV1DescControllerSoftwareRevision
OBJECT-TYPE
The software revision of Comp@s (read only)
1.3.6.1.4.1.26854.3.2.1.10.3.91DisplayStringread-onlycurrent
siteV1DescControllerOperatingSystemRevision
OBJECT-TYPE
The operating system of Comp@s (read only)
1.3.6.1.4.1.26854.3.2.1.10.3.92DisplayStringread-onlycurrent
siteV1DescControllerCPU
OBJECT-TYPE
Information about the CPU
1.3.6.1.4.1.26854.3.2.1.10.3.93DisplayStringread-onlycurrent
siteV1DescControllerCard
OBJECT-TYPE
Information about the hardware system containing Compas
1.3.6.1.4.1.26854.3.2.1.10.3.94DisplayStringread-onlycurrent
siteV1DescControllerStarterVersion
OBJECT-TYPE
Information about the starter component of Compas
1.3.6.1.4.1.26854.3.2.1.10.3.100DisplayStringread-onlycurrent
siteV1DescControllerFactoryCompasVersion
OBJECT-TYPE
Information about the revision of Compas in Factory folder
1.3.6.1.4.1.26854.3.2.1.10.3.105DisplayStringread-onlycurrent
siteV1DescControllerUserCompasVersion
OBJECT-TYPE
Information about the revision of Compas in user folder
1.3.6.1.4.1.26854.3.2.1.10.3.106DisplayStringread-onlycurrent
siteV1DescControllerFactoryFTPServerVersion
OBJECT-TYPE
Information about the revision of Ftp Server in Factory folder
1.3.6.1.4.1.26854.3.2.1.10.3.110DisplayStringread-onlycurrent
siteV1DescControllerUserFTPServerVersion
OBJECT-TYPE
Information about the revision of Ftp Server in Factory folder
1.3.6.1.4.1.26854.3.2.1.10.3.111DisplayStringread-onlycurrent
siteV1Alarm
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.11
siteV1AlarmNumber
OBJECT-TYPE
The number of entries in the Site Alarm table
1.3.6.1.4.1.26854.3.2.1.11.1Integer32read-onlycurrent
siteV1AlarmTable
OBJECT-TYPE
The table of Alarm entries
1.3.6.1.4.1.26854.3.2.1.11.2not-accessiblecurrent
siteV1AlarmEntry
OBJECT-TYPE
An alarm entry
1.3.6.1.4.1.26854.3.2.1.11.2.1not-accessiblecurrent
siteV1AlarmIndex
OBJECT-TYPE
Alarm Index
1.3.6.1.4.1.26854.3.2.1.11.2.1.1Unsigned32not-accessiblecurrent
siteV1AlarmName
OBJECT-TYPE
Alarm Name
1.3.6.1.4.1.26854.3.2.1.11.2.1.2DisplayStringread-onlycurrent
siteV1AlarmActive
OBJECT-TYPE
Is the Alarm active ? 'true' for active, 'false' for not-active
1.3.6.1.4.1.26854.3.2.1.11.2.1.3DisplayStringread-onlycurrent
siteV1AlarmSeverityType
OBJECT-TYPE
The alarm severity type (major, minor, warning, none, disabled) of this alarm entry
1.3.6.1.4.1.26854.3.2.1.11.2.1.4DisplayStringread-writecurrent
siteV1AlarmSeverityLevel
OBJECT-TYPE
The alarm severity level (0-9) of this alarm entry
1.3.6.1.4.1.26854.3.2.1.11.2.1.5DisplayStringread-writecurrent
siteV1AlarmStartTime
OBJECT-TYPE
The last start time of this alarm entry (null if never active)
1.3.6.1.4.1.26854.3.2.1.11.2.1.6DisplayStringread-onlycurrent
siteV1AlarmStopTime
OBJECT-TYPE
The last stop time of this alarm entry (null if alarm active)
1.3.6.1.4.1.26854.3.2.1.11.2.1.7DisplayStringread-onlycurrent
siteV1AlarmEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only for MIB compliance
1.3.6.1.4.1.26854.3.2.1.11.2.1.8RowStatusread-createcurrent
siteV1AlarmSummary
OBJECT-TYPE
Summary bit vector with all the alarms state of the Site. A '1' means alarm active, '0' means not active. Unimplemented alarms are always '0'.
1.3.6.1.4.1.26854.3.2.1.11.3Bits {inventoryCANBusFail(0), inventoryCANBusAddressingError(1), inventoryMissingCANBusNodeIDs(2), inventoryRunningCANLSSDeviceDetection(3), inventoryRunningCANFirmwareUpgrade(4), controllerControllerRebootRequired(10), controllerLastConfChangesUnsaved(14), xMLXMLHeartbeatPostFail(20)}read-onlycurrent
siteV1Event
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.12
siteV1EventNumber
OBJECT-TYPE
The number of entries in the Event Table related to the Site
1.3.6.1.4.1.26854.3.2.1.12.1Integer32read-onlycurrent
siteV1EventTable
OBJECT-TYPE
The Event table related to the Site
1.3.6.1.4.1.26854.3.2.1.12.2not-accessiblecurrent
siteV1EventEntry
OBJECT-TYPE
.
1.3.6.1.4.1.26854.3.2.1.12.2.1not-accessiblecurrent
siteV1EventIndex
OBJECT-TYPE
Event Index
1.3.6.1.4.1.26854.3.2.1.12.2.1.1Unsigned32not-accessiblecurrent
siteV1EventId
OBJECT-TYPE
Event Index
1.3.6.1.4.1.26854.3.2.1.12.2.1.2Unsigned32read-onlycurrent
siteV1EventName
OBJECT-TYPE
Event Name
1.3.6.1.4.1.26854.3.2.1.12.2.1.3DisplayStringread-onlycurrent
siteV1EventDateTime
OBJECT-TYPE
The date and time of the event
1.3.6.1.4.1.26854.3.2.1.12.2.1.4DisplayStringread-onlycurrent
siteV1EventSeverityType
OBJECT-TYPE
The event severity type ('major', 'minor', 'warning' or 'none')
1.3.6.1.4.1.26854.3.2.1.12.2.1.5DisplayStringread-onlycurrent
siteV1EventSeverityLevel
OBJECT-TYPE
The event severity level (0-9)
1.3.6.1.4.1.26854.3.2.1.12.2.1.6DisplayStringread-onlycurrent
siteV1EventEntryStatus
OBJECT-TYPE
The status of this table entry
1.3.6.1.4.1.26854.3.2.1.12.2.1.7RowStatusread-createcurrent
siteV1Data
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.13
siteV1DataNumber
OBJECT-TYPE
The number of entries in the Data Table related to the Site
1.3.6.1.4.1.26854.3.2.1.13.1Integer32read-onlycurrent
siteV1DataTable
OBJECT-TYPE
The table of Data entries
1.3.6.1.4.1.26854.3.2.1.13.2not-accessiblecurrent
siteV1DataEntry
OBJECT-TYPE
A data entry
1.3.6.1.4.1.26854.3.2.1.13.2.1not-accessiblecurrent
siteV1DataIndex
OBJECT-TYPE
The data index
1.3.6.1.4.1.26854.3.2.1.13.2.1.1Unsigned32not-accessiblecurrent
siteV1DataName
OBJECT-TYPE
The data name
1.3.6.1.4.1.26854.3.2.1.13.2.1.2DisplayStringread-onlycurrent
siteV1DataValue
OBJECT-TYPE
The data value
1.3.6.1.4.1.26854.3.2.1.13.2.1.3DisplayStringread-onlycurrent
siteV1DataEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only present for compliance
1.3.6.1.4.1.26854.3.2.1.13.2.1.4RowStatusread-createcurrent
siteV1DataList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.13.3
siteV1DataNetworkCurrentIPAddress
OBJECT-TYPE
This is the actual IP address of the Comp@s platform. If the Ethernet cable is not correctly connected, the address will be 0.0.0.0.
1.3.6.1.4.1.26854.3.2.1.13.3.1Integer32read-onlycurrent
siteV1DataNetworkCurrentIPMask
OBJECT-TYPE
This is the actual IP address of the Comp@s platform. If the Ethernet cable is not correctly connected, the address will be 0.0.0.0.
1.3.6.1.4.1.26854.3.2.1.13.3.2Integer32read-onlycurrent
siteV1DataNetworkCurrentMACAddress
OBJECT-TYPE
This is the MAC address of IP interface.
1.3.6.1.4.1.26854.3.2.1.13.3.3Integer32read-onlycurrent
siteV1DataControllerLicensedOptions
OBJECT-TYPE
This is the options of the actual license.
1.3.6.1.4.1.26854.3.2.1.13.3.11Integer32read-onlycurrent
siteV1DataTimeDateAndTimeLocal
OBJECT-TYPE
This is the local time of the monitoring.
1.3.6.1.4.1.26854.3.2.1.13.3.21DisplayStringread-onlycurrent
siteV1DataTimeDateAndTimeUTC
OBJECT-TYPE
This is the UTC time of the monitoring.
1.3.6.1.4.1.26854.3.2.1.13.3.22DisplayStringread-onlycurrent
siteV1DataControllerMonitoringMemoryUsed
OBJECT-TYPE
This is actual amount of RAM memory used by the application.
1.3.6.1.4.1.26854.3.2.1.13.3.31Integer32read-onlycurrent
siteV1DataControllerCPUPercentageUsage
OBJECT-TYPE
This is actual percentage of CPU used
1.3.6.1.4.1.26854.3.2.1.13.3.32Integer32read-onlycurrent
siteV1DataControllerFreeFlashMemorySpace
OBJECT-TYPE
This is free flash memory available on the Comp@s card, in Megabytes
1.3.6.1.4.1.26854.3.2.1.13.3.33Integer32read-onlycurrent
siteV1DataControllerFTPServerStatus
OBJECT-TYPE
Status of the FTP Server. Compatible only with version >= 2.26.X.X. The configuration is available at controller -> FTP Server page.
1.3.6.1.4.1.26854.3.2.1.13.3.35DisplayStringread-onlycurrent
siteV1DataDataRecordsTotalFifoSizeOfSecondRecords
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.13.3.41Integer32read-onlycurrent
siteV1DataDataRecordsTotalFifoSizeOfMinuteRecords
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.13.3.42Integer32read-onlycurrent
siteV1DataDataRecordsTotalFifoSizeOfHourRecords
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.13.3.43Integer32read-onlycurrent
siteV1DataDataRecordsTotalFifoSizeOfDayRecords
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.13.3.44Integer32read-onlycurrent
siteV1DataInventoryCANBusNodeIDs
OBJECT-TYPE
The coma separated list of the node ids present on the CAN bus.
1.3.6.1.4.1.26854.3.2.1.13.3.51Integer32read-onlycurrent
siteV1DataCloudLinkCloudLinkState
OBJECT-TYPE
Cloud Link State
1.3.6.1.4.1.26854.3.2.1.13.3.166DisplayStringread-onlycurrent
siteV1Config
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.15
siteV1ConfigNumber
OBJECT-TYPE
The number of entries in the Config table related to the Site
1.3.6.1.4.1.26854.3.2.1.15.1Integer32read-onlycurrent
siteV1ConfigTable
OBJECT-TYPE
The table of Config entries related to the Site
1.3.6.1.4.1.26854.3.2.1.15.2not-accessiblecurrent
siteV1ConfigEntry
OBJECT-TYPE
A Config entry
1.3.6.1.4.1.26854.3.2.1.15.2.1not-accessiblecurrent
siteV1ConfigIndex
OBJECT-TYPE
The Config entry Index
1.3.6.1.4.1.26854.3.2.1.15.2.1.1Unsigned32not-accessiblecurrent
siteV1ConfigName
OBJECT-TYPE
The Config entry name
1.3.6.1.4.1.26854.3.2.1.15.2.1.2DisplayStringread-onlycurrent
siteV1ConfigValue
OBJECT-TYPE
The Config entry value
1.3.6.1.4.1.26854.3.2.1.15.2.1.3DisplayStringread-writecurrent
siteV1ConfigEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only for compliance
1.3.6.1.4.1.26854.3.2.1.15.2.1.4RowStatusread-createcurrent
siteV1ConfigList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.15.3
siteV1CfgNetworkDHCPEnabled
OBJECT-TYPE
The monitoring will try to get an IP with the DHCP protocol if this parameter is set to True. By default, this parameter is set to False.
1.3.6.1.4.1.26854.3.2.1.15.3.1DisplayStringread-writecurrent
siteV1CfgNetworkIPAddressIfStatic
OBJECT-TYPE
The static IP address of the monitoring. This configuration parameter is not used if the DHCP is enabled. The default IP is 192.168.45.2.
1.3.6.1.4.1.26854.3.2.1.15.3.2DisplayStringread-writecurrent
siteV1CfgNetworkSubnetMaskIfStatic
OBJECT-TYPE
The static Subnet Mask of the monitoring. This configuration parameter is not used if the DHCP is enabled. The default mask is 255.255.255.0.
1.3.6.1.4.1.26854.3.2.1.15.3.3DisplayStringread-writecurrent
siteV1CfgNetworkDefaultGatewayIfStatic
OBJECT-TYPE
The static Default Gateway of the monitoring. This configuration parameter is not used if DHCP is enabled. This is only useful if the monitoring have to use a gateway, this is generally not necessary. The default gateway is 192.168.45.1.
1.3.6.1.4.1.26854.3.2.1.15.3.4DisplayStringread-writecurrent
siteV1CfgNetworkDNSIfStatic
OBJECT-TYPE
The static DNS of the monitoring. This configuration parameter is used to resolve URI and server name. This is not necessary if you are only IP address as target server. The default DNS server is 192.168.45.1.
1.3.6.1.4.1.26854.3.2.1.15.3.5DisplayStringread-writecurrent
siteV1CfgNetworkMaxTransmissionUnit
OBJECT-TYPE
Specifies the TCP/IP MTU for the network interface
1.3.6.1.4.1.26854.3.2.1.15.3.8DisplayStringread-writecurrent
siteV1CfgTimeSNTPTimeServer
OBJECT-TYPE
The address of the server acting as SNTP timer server. If this server is not valid, the monitoring cannot update automatically his time. You can use several time server by usin a coma separator without space.
1.3.6.1.4.1.26854.3.2.1.15.3.11DisplayStringread-writecurrent
siteV1CfgTimeTimeZoneName
OBJECT-TYPE
The Time Zone of the site
1.3.6.1.4.1.26854.3.2.1.15.3.14DisplayStringread-writecurrent
siteV1CfgTimeSNTPTimeRefresh
OBJECT-TYPE
Set the time between synchronisation with the SNTP server (max 1000 hours, by default 178)
1.3.6.1.4.1.26854.3.2.1.15.3.15DisplayStringread-writecurrent
siteV1CfgTimeSNTPTimeRecoveryRefresh
OBJECT-TYPE
Set the time to wait before retry if a synchronisation fail (max 1000 hours, by default 24)
1.3.6.1.4.1.26854.3.2.1.15.3.16DisplayStringread-writecurrent
siteV1CfgWebServerWebServerSecurityEnabled
OBJECT-TYPE
This is a True/False parameter used to activate or deactivate the access control to the web server.
1.3.6.1.4.1.26854.3.2.1.15.3.22DisplayStringread-writecurrent
siteV1CfgWebServerWebServerPort
OBJECT-TYPE
This is an unsigned integer parameter used to configure the port at which the web server is accessible. By default, the port is 80. If you change this port, you must be sure that the traffic is allowed by your switches and routers on this port.
1.3.6.1.4.1.26854.3.2.1.15.3.23DisplayStringread-writecurrent
siteV1CfgWebServerWebAuthenticationMethod
OBJECT-TYPE
The web access security can be managed with 3 authentication methods: Basic Access, Digest Access or Basic with Radius.
1.3.6.1.4.1.26854.3.2.1.15.3.24DisplayStringread-writecurrent
siteV1CfgWebServerHttpsWebServerPort
OBJECT-TYPE
This is a port number to activate or deactivate the https web server - 0 or 443 by default
1.3.6.1.4.1.26854.3.2.1.15.3.26DisplayStringread-writecurrent
siteV1CfgWebServerDefaultPage
OBJECT-TYPE
The default page displayed on logon (dashboard, site, summary, alarm_event, ...)
1.3.6.1.4.1.26854.3.2.1.15.3.31DisplayStringread-writecurrent
siteV1CfgXMLXMLEventPostingActivated
OBJECT-TYPE
This is a True/False parameter used to activate or deactivate the XML event posting.
1.3.6.1.4.1.26854.3.2.1.15.3.41DisplayStringread-writecurrent
siteV1CfgXMLXMLEventPostingRefreshTime
OBJECT-TYPE
The minimal time in second between to calculation of the XML events to send. By default, this is done every two seconds.
1.3.6.1.4.1.26854.3.2.1.15.3.42DisplayStringread-writecurrent
siteV1CfgXMLXMLEventPostingTimeout
OBJECT-TYPE
The timeout in millisecond when trying to post XML data to a Web Server.
1.3.6.1.4.1.26854.3.2.1.15.3.43DisplayStringread-writecurrent
siteV1CfgXMLXMLEventPostingToSecOnlyIfPrimFail
OBJECT-TYPE
If this parameter is set to true, the events will be sent to secondary only if primary server is not available. If this parameter is set to false, all the events will be sent to primary and secondary server
1.3.6.1.4.1.26854.3.2.1.15.3.45DisplayStringread-writecurrent
siteV1CfgXMLXMLTablesToPostOnXMLEvent
OBJECT-TYPE
The list of the tables to send when an event is generated. (description,alarm,data,config,control). This allows to have armada database updated on event.
1.3.6.1.4.1.26854.3.2.1.15.3.46DisplayStringread-writecurrent
siteV1CfgXMLXMLHeartbeatTime
OBJECT-TYPE
This is the time between 2 XML Post of heartbeat. If set to 0, no heartbeat.
1.3.6.1.4.1.26854.3.2.1.15.3.51DisplayStringread-writecurrent
siteV1CfgSNMPSNMPActivated
OBJECT-TYPE
This is a True/False parameter used to activate or deactivate the SNMP agent.
1.3.6.1.4.1.26854.3.2.1.15.3.61DisplayStringread-writecurrent
siteV1CfgSNMPSNMPTrapVersion
OBJECT-TYPE
Traps/Notification can be sent with SNMP V1, V2c or V3 format.
1.3.6.1.4.1.26854.3.2.1.15.3.63DisplayStringread-writecurrent
siteV1CfgSNMPSNMPGETMinSecurityLevel
OBJECT-TYPE
4 choices are available: No Authentication, V1 Community, V2c Community or V3.
1.3.6.1.4.1.26854.3.2.1.15.3.64DisplayStringread-writecurrent
siteV1CfgSNMPSNMPSETMinSecurityLevel
OBJECT-TYPE
4 choices are available: No Authentication, V1 Community, V2c Community or V3.
1.3.6.1.4.1.26854.3.2.1.15.3.65DisplayStringread-writecurrent
siteV1CfgSNMPSNMPV3AuthAlgorithm
OBJECT-TYPE
3 choices are available: MD5, SHA, Any
1.3.6.1.4.1.26854.3.2.1.15.3.66DisplayStringread-writecurrent
siteV1CfgSNMPSNMPV3PrivacyAlgorithm
OBJECT-TYPE
3 choices are available: DES, AES, 3DES
1.3.6.1.4.1.26854.3.2.1.15.3.67DisplayStringread-writecurrent
siteV1CfgSNMPSNMPV3PrivacyPassword
OBJECT-TYPE
The global SNMP V3 Encryption Password. This one is common for all the users to avoid complexity
1.3.6.1.4.1.26854.3.2.1.15.3.68DisplayStringread-writecurrent
siteV1CfgSNMPSNMPV3EngineID
OBJECT-TYPE
The SNMP V3 Local Engine ID string
1.3.6.1.4.1.26854.3.2.1.15.3.69DisplayStringread-writecurrent
siteV1CfgSNMPSNMPV3TrapAuthAlgorithm
OBJECT-TYPE
2 choices are available: MD5, SHA
1.3.6.1.4.1.26854.3.2.1.15.3.72DisplayStringread-writecurrent
siteV1CfgSNMPSNMPV3TrapPrivacyAlgorithm
OBJECT-TYPE
3 choices are available: DES, AES, 3DES
1.3.6.1.4.1.26854.3.2.1.15.3.73DisplayStringread-writecurrent
siteV1CfgSNMPSNMPV3TrapUsername
OBJECT-TYPE
The SNMP V3 Trap UserName used for all the SNMP V3 traps
1.3.6.1.4.1.26854.3.2.1.15.3.74DisplayStringread-writecurrent
siteV1CfgSNMPSNMPV3TrapAuthPassword
OBJECT-TYPE
The SNMP V3 Trap Authentication Password
1.3.6.1.4.1.26854.3.2.1.15.3.75DisplayStringread-writecurrent
siteV1CfgSNMPSNMPV3TrapPrivacyPassword
OBJECT-TYPE
The SNMP V3 Trap Privacy Password
1.3.6.1.4.1.26854.3.2.1.15.3.76DisplayStringread-writecurrent
siteV1CfgSNMPSiteDescriptionIdsIncludedInTraps
OBJECT-TYPE
List of site Description Elements to send on traps. (to have the site reference and the city in each trap for example). The list is separated with ';'
1.3.6.1.4.1.26854.3.2.1.15.3.77DisplayStringread-writecurrent
siteV1CfgGenericGenerateEventOnConfChanges
OBJECT-TYPE
This is a True/False parameter used to activate or deactivate the tracking of configuration changes
1.3.6.1.4.1.26854.3.2.1.15.3.81DisplayStringread-writecurrent
siteV1CfgDataRecordsAutoArchivePeriodDataRecord
OBJECT-TYPE
Period in hour to auto save records (when detailled and long duration records are needed). 0 means disabled.
1.3.6.1.4.1.26854.3.2.1.15.3.82DisplayStringread-writecurrent
siteV1CfgGenericGenerateEventOnControlExecution
OBJECT-TYPE
This is a True/False parameter used to activate or deactivate the tracking of control execution
1.3.6.1.4.1.26854.3.2.1.15.3.83DisplayStringread-writecurrent
siteV1CfgGenericGenerateEventOnAlarmAcknowledge
OBJECT-TYPE
This is a True/False parameter used to activate or deactivate the tracking of alarm acknowledgment
1.3.6.1.4.1.26854.3.2.1.15.3.84DisplayStringread-writecurrent
siteV1CfgInventoryRequiredCANBusNodeIDs
OBJECT-TYPE
This is a coma separated list with the required CAN bus node ids
1.3.6.1.4.1.26854.3.2.1.15.3.91DisplayStringread-writecurrent
siteV1CfgInventoryLSSCANidrange
OBJECT-TYPE
By default 50-80, means up to 50 Can Nodes like rectifiers with CAN Id 50 to 80. To support up to 100 rectifiers, change it to 1-100.
1.3.6.1.4.1.26854.3.2.1.15.3.92DisplayStringread-writecurrent
siteV1CfgInventorySystemNodesDefinition
OBJECT-TYPE
dc3(30-100)
1.3.6.1.4.1.26854.3.2.1.15.3.93DisplayStringread-writecurrent
siteV1CfgInventoryLSSCANOpenSavedConf
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.15.3.95DisplayStringread-writecurrent
siteV1CfgUsersAdministratorLoginPassword
OBJECT-TYPE
This is the login and the password of the administrator. It is saved with a special syntax. First the login in clear, followed of 2 points, followed of the MD5 hashed password. If you change the login:password by entering a non hashed password, this last is automatically hashed.
1.3.6.1.4.1.26854.3.2.1.15.3.101DisplayStringread-writecurrent
siteV1CfgUsersUser1LoginPassword
OBJECT-TYPE
This is the login and the password of the user number 1.
1.3.6.1.4.1.26854.3.2.1.15.3.102DisplayStringread-writecurrent
siteV1CfgUsersUser2LoginPassword
OBJECT-TYPE
This is the login and the password of the user number 2.
1.3.6.1.4.1.26854.3.2.1.15.3.103DisplayStringread-writecurrent
siteV1CfgUsersUser3LoginPassword
OBJECT-TYPE
This is the login and the password of the user number 3.
1.3.6.1.4.1.26854.3.2.1.15.3.104DisplayStringread-writecurrent
siteV1CfgUsersUser4LoginPassword
OBJECT-TYPE
This is the login and the password of the user number 4.
1.3.6.1.4.1.26854.3.2.1.15.3.105DisplayStringread-writecurrent
siteV1CfgUsersUser5LoginPassword
OBJECT-TYPE
This is the login and the password of the user number 5.
1.3.6.1.4.1.26854.3.2.1.15.3.106DisplayStringread-writecurrent
siteV1CfgRadiusAuthenticationRadiusServer
OBJECT-TYPE
Radius Server address. If you have a secondary server, you could use a coma to separate it.
1.3.6.1.4.1.26854.3.2.1.15.3.111DisplayStringread-writecurrent
siteV1CfgRadiusAuthenticationRadiusPort
OBJECT-TYPE
Radius Port. If you have a secondary server, you could use a coma to separate it.
1.3.6.1.4.1.26854.3.2.1.15.3.112DisplayStringread-writecurrent
siteV1CfgRadiusAuthenticationRadiusSecret
OBJECT-TYPE
Radius PassPhrase
1.3.6.1.4.1.26854.3.2.1.15.3.113DisplayStringread-writecurrent
siteV1CfgEmailEnableEmailFeature
OBJECT-TYPE
Enable/Disable the email feature
1.3.6.1.4.1.26854.3.2.1.15.3.120DisplayStringread-writecurrent
siteV1CfgEmailSmtpServer
OBJECT-TYPE
Smtp Server. If you are using a domain name, make sure you configured the network Dns (CF5)
1.3.6.1.4.1.26854.3.2.1.15.3.121DisplayStringread-writecurrent
siteV1CfgEmailSmtpDomain
OBJECT-TYPE
Smtp Domain. (Required by some servers.)
1.3.6.1.4.1.26854.3.2.1.15.3.122DisplayStringread-writecurrent
siteV1CfgEmailSmtpUserLoginPassword
OBJECT-TYPE
Smtp Login and Password. The password is encrypted. To enter a new login and password, enter login:password and validate, the password will be encrypted.
1.3.6.1.4.1.26854.3.2.1.15.3.123DisplayStringread-writecurrent
siteV1CfgEmailMailSender
OBJECT-TYPE
Mail Sender (The 'From' of the emails you will receive)
1.3.6.1.4.1.26854.3.2.1.15.3.130DisplayStringread-writecurrent
siteV1CfgEmailMailRecipients
OBJECT-TYPE
Mail Recipients, separated with semicolon ';'
1.3.6.1.4.1.26854.3.2.1.15.3.131DisplayStringread-writecurrent
siteV1CfgEmailMinimalSeverityTypeToSendMail
OBJECT-TYPE
This is the minimal severity of the event to send a Summary Mail
1.3.6.1.4.1.26854.3.2.1.15.3.135DisplayStringread-writecurrent
siteV1CfgControllerAutomaticReboot
OBJECT-TYPE
Cron rules used in order to restart automatically the controller. Before rebooting configuration, events and data records are saved.
1.3.6.1.4.1.26854.3.2.1.15.3.150DisplayStringread-writecurrent
siteV1CfgCloudLinkCloudEnabled
OBJECT-TYPE
Enable Cloud Connection
1.3.6.1.4.1.26854.3.2.1.15.3.161DisplayStringread-writecurrent
siteV1CfgCloudLinkCloudServer
OBJECT-TYPE
Cloud Server
1.3.6.1.4.1.26854.3.2.1.15.3.162DisplayStringread-writecurrent
siteV1CfgCloudLinkCloudPort
OBJECT-TYPE
Cloud Port
1.3.6.1.4.1.26854.3.2.1.15.3.163DisplayStringread-writecurrent
siteV1CfgCloudLinkCloudCredential
OBJECT-TYPE
Enter Credential of your AlphaCloud account in order to connect. You have to enter username:password in order to save your credential.
1.3.6.1.4.1.26854.3.2.1.15.3.164DisplayStringread-writecurrent
siteV1CfgCloudLinkCloudCluster
OBJECT-TYPE
Cloud Cluster
1.3.6.1.4.1.26854.3.2.1.15.3.165DisplayStringread-writecurrent
siteV1CfgInventoryRS485ExtensionsConf
OBJECT-TYPE
The configuration string for RS485 Extensions
1.3.6.1.4.1.26854.3.2.1.15.3.210DisplayStringread-writecurrent
siteV1CfgInventoryEthernetExtensionsConf
OBJECT-TYPE
The configuration string for Ethernet Extensions
1.3.6.1.4.1.26854.3.2.1.15.3.220DisplayStringread-writecurrent
siteV1CfgScriptingEnabledscripts
OBJECT-TYPE
This parameter enable all CompasLua Scripting capabilities. You can control scripts in Files -> Files manager > scripting tab.
1.3.6.1.4.1.26854.3.2.1.15.3.250DisplayStringread-writecurrent
siteV1CfgScriptingNumberofErrorsbeforetriggeringalarm
OBJECT-TYPE
Number of errors before triggering the scripting error alarm. When number of error is higher than this parameter, the alarm is triggered. If 0 is set, the alarm is deactivated
1.3.6.1.4.1.26854.3.2.1.15.3.251DisplayStringread-writecurrent
siteV1CfgGenericReadAccessUserNumbers
OBJECT-TYPE
The list of the user numbers which have read access to this equipment. The user numbers are coma separated. The accepted user id are 1,2,3,4 and 5. Ex: 1,3,4
1.3.6.1.4.1.26854.3.2.1.15.3.521DisplayStringread-writecurrent
siteV1CfgGenericWriteAccessUserNumbers
OBJECT-TYPE
The list of the user numbers which have write access to this equipment. This means that these users can modify the configuration element, the alarm settings and use the control elements. The user numbers are coma separated. The accepted user ids are 1,2,3,4 and 5. Ex: 1,3,4
1.3.6.1.4.1.26854.3.2.1.15.3.522DisplayStringread-writecurrent
siteV1CfgGenericEventTableLength
OBJECT-TYPE
The maximum length of the table. The value must be comprised between 10 and 4000
1.3.6.1.4.1.26854.3.2.1.15.3.601DisplayStringread-writecurrent
siteV1CfgSNMPSNMPTrapTargetsIP
OBJECT-TYPE
One or multiple target IP to send traps, coma separated. Ex: 130.145.23.1, 130.23.12.45
1.3.6.1.4.1.26854.3.2.1.15.3.611DisplayStringread-writecurrent
siteV1CfgSNMPMinimalEventSeverityForTraps
OBJECT-TYPE
This is the minimal severity of the event to send a SNMP trap
1.3.6.1.4.1.26854.3.2.1.15.3.612DisplayStringread-writecurrent
siteV1CfgXMLXMLEventsPrimPostURL
OBJECT-TYPE
This is the first URL at which the events related to this equipment must be posted. The XML ETSI standard is used in the posted data content.
1.3.6.1.4.1.26854.3.2.1.15.3.651DisplayStringread-writecurrent
siteV1CfgXMLXMLEventsPrimPostLogin
OBJECT-TYPE
The login which must be used when posting events to the primary server
1.3.6.1.4.1.26854.3.2.1.15.3.652DisplayStringread-writecurrent
siteV1CfgXMLXMLEventsPrimPostPassword
OBJECT-TYPE
The password which must be used when posting events to the primary server
1.3.6.1.4.1.26854.3.2.1.15.3.653DisplayStringread-writecurrent
siteV1CfgXMLXMLEventsSecPostURL
OBJECT-TYPE
This is the second URL at which the events related to this equipment must be posted. The XML ETSI standard is used in the posted data content. This allows having redundancy with the management server.
1.3.6.1.4.1.26854.3.2.1.15.3.661DisplayStringread-writecurrent
siteV1CfgXMLXMLEventsSecPostLogin
OBJECT-TYPE
The login which must be used when posting events to the secondary server
1.3.6.1.4.1.26854.3.2.1.15.3.662DisplayStringread-writecurrent
siteV1CfgXMLXMLEventsSecPostPassword
OBJECT-TYPE
The password which must be used when posting events to the secondary server
1.3.6.1.4.1.26854.3.2.1.15.3.663DisplayStringread-writecurrent
siteV1CfgPLCNumberOfPLCData
OBJECT-TYPE
The number of PLC data. Every equipment can manage up to 30 user programmable data. Data elements are automatically added in the data table. Configuration parameters are added to set the PLC Data Name and the PLC Data Mathematical calculation. In order to use these functionalities, you need a license with the 'PLC' module
1.3.6.1.4.1.26854.3.2.1.15.3.901DisplayStringread-writecurrent
siteV1CfgPLCNumberOfPLCAlarm
OBJECT-TYPE
The number of PLC alarm. Every equipment can manage up to 30 user programmable alarms. Alarm elements are automatically added in the alarm table. The alarm parameters are added to set the PLC Alarm Name and the PLC Alarm Boolean condition. In order to use these functionalities, you need a licence with the 'PLC' module
1.3.6.1.4.1.26854.3.2.1.15.3.902DisplayStringread-writecurrent
siteV1Control
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.16
siteV1ControlNumber
OBJECT-TYPE
The number of entries in the Control table related to the Site
1.3.6.1.4.1.26854.3.2.1.16.1Integer32read-onlycurrent
siteV1ControlTable
OBJECT-TYPE
The table of Control entries related to the Site
1.3.6.1.4.1.26854.3.2.1.16.2not-accessiblecurrent
siteV1ControlEntry
OBJECT-TYPE
A Control entry
1.3.6.1.4.1.26854.3.2.1.16.2.1not-accessiblecurrent
siteV1ControlIndex
OBJECT-TYPE
The Control entry Index
1.3.6.1.4.1.26854.3.2.1.16.2.1.1Unsigned32not-accessiblecurrent
siteV1ControlName
OBJECT-TYPE
The Control entry name
1.3.6.1.4.1.26854.3.2.1.16.2.1.2DisplayStringread-onlycurrent
siteV1ControlValue
OBJECT-TYPE
The Control entry value
1.3.6.1.4.1.26854.3.2.1.16.2.1.3DisplayStringread-writecurrent
siteV1ControlEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only for compliance
1.3.6.1.4.1.26854.3.2.1.16.2.1.4RowStatusread-createcurrent
siteV1ControlList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.16.3
siteV1CtrlControllerRebootController
OBJECT-TYPE
Writing a '1' to this control element will reboot the monitoring. Events and Records will be saved.
1.3.6.1.4.1.26854.3.2.1.16.3.1DisplayStringread-writecurrent
siteV1CtrlControllerSaveConfAndRebootController
OBJECT-TYPE
Writing a '1' to this control element will first save the actual configuration and will reboot the monitoring after.
1.3.6.1.4.1.26854.3.2.1.16.3.2DisplayStringread-writecurrent
siteV1CtrlControllerRebootControllerWithoutSavingRecords
OBJECT-TYPE
Writing a '1' to this control element will reboot the monitoring without saving records
1.3.6.1.4.1.26854.3.2.1.16.3.3DisplayStringread-writecurrent
siteV1CtrlNetworkApplyNetworkConf
OBJECT-TYPE
Writing a '1' to this control element will reconfigure the ethernet according to the Network Configuration. If you change the IP address in the config table without using this command after, the configuration is not applied.
1.3.6.1.4.1.26854.3.2.1.16.3.6DisplayStringread-writecurrent
siteV1CtrlTimeForceSNTPTimeRefresh
OBJECT-TYPE
Writing a '1' to this control element will force the monitoring to try to refresh his time with the configured SNTP Time Server.
1.3.6.1.4.1.26854.3.2.1.16.3.11DisplayStringread-writecurrent
siteV1CtrlTimeSetLocalTime
OBJECT-TYPE
Writing a date and time to this control element allows to manually change the local time of the monitoring. The syntax of the date and the time is: 2007-11-19T13:02:34
1.3.6.1.4.1.26854.3.2.1.16.3.12DisplayStringread-writecurrent
siteV1CtrlTimeSetUTCTime
OBJECT-TYPE
Writing a date and time to this control element allows to manually change the UTC time of the monitoring. The syntax of the date and the time is: 2007-11-19T13:02:34
1.3.6.1.4.1.26854.3.2.1.16.3.13DisplayStringread-writecurrent
siteV1CtrlTimeResetUptime
OBJECT-TYPE
Writing a '1' to this control element will reset the uptime of the monitoring.
1.3.6.1.4.1.26854.3.2.1.16.3.14DisplayStringread-writecurrent
siteV1CtrlControllerCleanandSaveXMLUserConf
OBJECT-TYPE
Writing a '1' to this control element will remove the configuration sections related to missing equipments, than save all the configuration of all the connected equipment in a XML format. This file is read when the monitoring is starting in order to configure the monitoring. This file is also accessible trough the FTP server or can be downloaded trough the web interface.
1.3.6.1.4.1.26854.3.2.1.16.3.20DisplayStringread-writecurrent
siteV1CtrlControllerSaveXMLUserConf
OBJECT-TYPE
Writing a '1' to this control element will save all the configuration of all the connected (or previously connected) equipment in a XML format. This file is read when the monitoring is starting in order to configure the monitoring. This file is also accessible trough the FTP server or can be downloaded trough the web interface.
1.3.6.1.4.1.26854.3.2.1.16.3.21DisplayStringread-writecurrent
siteV1CtrlControllerSaveInventory
OBJECT-TYPE
Writing a '1' to this control element will save save the inventory in a XML format. This file is read when the monitoring is starting in order to configure the monitoring. This file is also accessible trough the FTP server or can be downloaded trough the web interface.
1.3.6.1.4.1.26854.3.2.1.16.3.22DisplayStringread-writecurrent
siteV1CtrlDataRecordsSaveDataRecords
OBJECT-TYPE
Writing a '1' to this control element will force the monitoring to save all the data records. This is useful if you want to unpower the Comp@s monitoring. This function is called automatically everyday.
1.3.6.1.4.1.26854.3.2.1.16.3.33DisplayStringread-writecurrent
siteV1CtrlDataRecordsExportDataRecordsinCSV
OBJECT-TYPE
Writing a '1' to this control element will force the monitoring to save all the CVS records files. The CSV files are stored in the records folder.
1.3.6.1.4.1.26854.3.2.1.16.3.34DisplayStringread-writecurrent
siteV1CtrlDataRecordsArchiveDataRecords
OBJECT-TYPE
Writing a '1' to this control element will force the monitoring to save all the data records. This is useful if you want to unpower the Comp@s monitoring. This function is called automatically everyday.
1.3.6.1.4.1.26854.3.2.1.16.3.35DisplayStringread-writecurrent
siteV1CtrlDataRecordsDeleteAllDataRecords
OBJECT-TYPE
Writing a '1' to this control element will force the monitoring to save all the data records. This is useful if you want to unpower the Comp@s monitoring. This function is called automatically everyday.
1.3.6.1.4.1.26854.3.2.1.16.3.36DisplayStringread-writecurrent
siteV1CtrlControllerEmulateRecords
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.16.3.40DisplayStringread-writecurrent
siteV1CtrlControllerReloadTranslations
OBJECT-TYPE
Writing a '1' to this control element will reload all the csv translation files
1.3.6.1.4.1.26854.3.2.1.16.3.41DisplayStringread-writecurrent
siteV1CtrlControllerReloadLicense
OBJECT-TYPE
Writing a '1' to this control element will reload the license file
1.3.6.1.4.1.26854.3.2.1.16.3.51DisplayStringread-writecurrent
siteV1CtrlControllerManageFTPServer
OBJECT-TYPE
This Control is used to manage the FTP Server
1.3.6.1.4.1.26854.3.2.1.16.3.55DisplayStringread-writecurrent
siteV1CtrlInventoryRemoveAbsentEquipments
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.16.3.61DisplayStringread-writecurrent
siteV1CtrlInventoryResetCANBusNode
OBJECT-TYPE
Writing a valid CAN bus node id to this control element will reset the correspondent device.
1.3.6.1.4.1.26854.3.2.1.16.3.81DisplayStringread-writecurrent
siteV1CtrlInventorySaveCANOpenLSSConf
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.16.3.82DisplayStringread-writecurrent
siteV1CtrlInventoryStartNewInventory
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.16.3.83DisplayStringread-writecurrent
siteV1CtrlInventoryUpgradeNodeFirmware
OBJECT-TYPE
This control element is used to start the firmware upgrade of a CAN bus Node. You need to upload first the firmware trough ftp in the /user/firmware path. Then you need to write the id number of the CAN Node, followed by a coma, followed by the file name. Example : '101,SOFT_0000030_01.txt'.
1.3.6.1.4.1.26854.3.2.1.16.3.91DisplayStringread-writecurrent
siteV1CtrlInventoryCancelFirmwareUpgrade
OBJECT-TYPE
This control element is used to cancel the running firmware upgrade of a CAN bus Node.
1.3.6.1.4.1.26854.3.2.1.16.3.92DisplayStringread-writecurrent
siteV1CtrlFilesFlashBinary
OBJECT-TYPE
This control element is used to start a binary flash update. You need to upload first the firmware trough ftp in the /user/firmware path.
1.3.6.1.4.1.26854.3.2.1.16.3.103DisplayStringread-writecurrent
siteV1CtrlFilesDownloadFileFromUrl
OBJECT-TYPE
This control element is used to download a file wiht HTTP get, the argument is an url. The file is saved in the upload folder
1.3.6.1.4.1.26854.3.2.1.16.3.110DisplayStringread-writecurrent
siteV1CtrlFilesDeleteUserUploadedFile
OBJECT-TYPE
This control element is used to delete a file in the user-upload folder. This is riskless as these files are not used, they are temporary files.
1.3.6.1.4.1.26854.3.2.1.16.3.111DisplayStringread-writecurrent
siteV1CtrlFilesMoveUserUploadedFile
OBJECT-TYPE
This control element is used to copy a file from the user-upload folder to another one. Be aware of what your are doing !
1.3.6.1.4.1.26854.3.2.1.16.3.112DisplayStringread-writecurrent
siteV1CtrlFilesExtractZipFileinuserupload
OBJECT-TYPE
This control element is used to delete a file in the user-upload folder. This is riskless as these files are not used, they are temporary files.
1.3.6.1.4.1.26854.3.2.1.16.3.113DisplayStringread-writecurrent
siteV1CtrlEmailSendSummaryEmail
OBJECT-TYPE
This control element is used to force the sending of a summary to the configured mail address
1.3.6.1.4.1.26854.3.2.1.16.3.120DisplayStringread-writecurrent
siteV1CtrlScriptingControlLuaScript
OBJECT-TYPE
This control element is used to control the lua scripting system. Available command are: enable[Enable Lua Capabilities], disable[Disable Lua Capabilities], restart[Restart All Lua Capabilities], refresh[Read the folder script (if you added a file when system is running)], enable filename[enable filename.lua located in folder user/scripts], disable filename[disable filename.lua located in folder user/scripts], restart filename : Restart fileName[file must be enabled], reseterrors[Reset all errors counters], reseterrors filename[Reset errors from filename
1.3.6.1.4.1.26854.3.2.1.16.3.250DisplayStringread-writecurrent
siteV1CtrlControllerAdvancedFunctionGenericCommandExecution
OBJECT-TYPE
This control is used to perform advanced operation.
1.3.6.1.4.1.26854.3.2.1.16.3.300DisplayStringread-writecurrent
siteV1CtrlGenericClearMyEvents
OBJECT-TYPE
By writing '1' to this control element, all the events of this equipment will be cleared.
1.3.6.1.4.1.26854.3.2.1.16.3.501DisplayStringread-writecurrent
siteV1CtrlGenericClearAllEvents
OBJECT-TYPE
By writing '1' to this control element, all the events of this equipment and all the events of all the sub-equipments will be cleared.
1.3.6.1.4.1.26854.3.2.1.16.3.502DisplayStringread-writecurrent
siteV1CtrlGenericAddEvent
OBJECT-TYPE
This control element adds an event of severity none. The event name is the text written to this control element
1.3.6.1.4.1.26854.3.2.1.16.3.511DisplayStringread-writecurrent
siteV1CtrlGenericAddMajorEvent
OBJECT-TYPE
This control element adds an event of severity major. The event name is the text written to this control element
1.3.6.1.4.1.26854.3.2.1.16.3.512DisplayStringread-writecurrent
siteV1CtrlGenericResetDefaultNamesAndGroups
OBJECT-TYPE
This control element resets all the element Names, Groups and Subgroups to default values for this equipment
1.3.6.1.4.1.26854.3.2.1.16.3.521DisplayStringread-writecurrent
siteV1CtrlGenericResetDefaultNamesAndGroupsRecursive
OBJECT-TYPE
This control element resets all the element Names, Groups and Subgroups to default values for this equipment and all sub equipments
1.3.6.1.4.1.26854.3.2.1.16.3.522DisplayStringread-writecurrent
siteV1Notifications
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.18
siteV1NotificationPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.18.0
siteV1Compliance
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.19
siteV1ComplianceGroups
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.19.1
energySystems
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20
es1
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1
es1GlobalStatus
OBJECT-TYPE
A textual string (alarms, normal or unknown) containing the status of the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.1DisplayString (SIZE(0..255))read-onlycurrent
es1GlobalAlarmSeverityType
OBJECT-TYPE
The alarm severity type (critical, major, minor, warning, none, disabled) of the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.2DisplayStringread-onlycurrent
es1GlobalAlarmSeverityLevel
OBJECT-TYPE
The alarm severity level (0-9) of the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.3Integer32read-onlycurrent
es1GlobalAlarmSeverityTypeInt
OBJECT-TYPE
The alarm severity type as integer (critical=4, major=3, minor=2, warning=1, none=0) of the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.4Integer32read-onlycurrent
es1Description
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.10
es1DescriptionNumber
OBJECT-TYPE
The number of entries in the Energy System Description table
1.3.6.1.4.1.26854.3.2.1.20.1.10.1Integer32read-onlycurrent
es1DescriptionTable
OBJECT-TYPE
The Description table of the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.10.2not-accessiblecurrent
es1DescriptionEntry
OBJECT-TYPE
A Description entry
1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1not-accessiblecurrent
es1DescriptionIndex
OBJECT-TYPE
Description Index
1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.1Unsigned32not-accessiblecurrent
es1DescriptionName
OBJECT-TYPE
Description Name
1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.2DisplayStringread-onlycurrent
es1DescriptionValue
OBJECT-TYPE
Description Value
1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.3DisplayStringread-createcurrent
es1DescriptionEntryStatus
OBJECT-TYPE
The status of this table entry
1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.4RowStatusread-createcurrent
es1DescriptionList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.10.3
es1DescDescriptionDescription
OBJECT-TYPE
A free text zone to write a system description
1.3.6.1.4.1.26854.3.2.1.20.1.10.3.1DisplayStringread-writecurrent
es1DescDescriptionReference
OBJECT-TYPE
A free text zone to write the customer reference of the system
1.3.6.1.4.1.26854.3.2.1.20.1.10.3.2DisplayStringread-writecurrent
es1Alarm
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.11
es1AlarmNumber
OBJECT-TYPE
The number of entries in the Energy System Alarm table
1.3.6.1.4.1.26854.3.2.1.20.1.11.1Integer32read-onlycurrent
es1AlarmTable
OBJECT-TYPE
The table of Alarm entries
1.3.6.1.4.1.26854.3.2.1.20.1.11.2not-accessiblecurrent
es1AlarmEntry
OBJECT-TYPE
An alarm entry
1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1not-accessiblecurrent
es1AlarmIndex
OBJECT-TYPE
Alarm Index
1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.1Unsigned32not-accessiblecurrent
es1AlarmName
OBJECT-TYPE
Alarm Name
1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.2DisplayStringread-onlycurrent
es1AlarmActive
OBJECT-TYPE
Is the Alarm active ? 'true' for active, 'false' for not-active
1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.3DisplayStringread-onlycurrent
es1AlarmSeverityType
OBJECT-TYPE
The alarm severity type (major, minor, warning, none, disabled) of this alarm entry
1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.4DisplayStringread-writecurrent
es1AlarmSeverityLevel
OBJECT-TYPE
The alarm severity level (0-9) of this alarm entry
1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.5DisplayStringread-writecurrent
es1AlarmStartTime
OBJECT-TYPE
The last start time of this alarm entry (null if never active)
1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.6DisplayStringread-onlycurrent
es1AlarmStopTime
OBJECT-TYPE
The last stop time of this alarm entry (null if alarm active)
1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.7DisplayStringread-onlycurrent
es1AlarmEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only for MIB compliance
1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.8RowStatusread-createcurrent
es1AlarmSummary
OBJECT-TYPE
Summary bit vector with all the alarms state of the Energy System. A '1' means alarm active, '0' means not active. Unimplemented alarms are always '0'.
1.3.6.1.4.1.26854.3.2.1.20.1.11.3Bits {none(0)}read-onlycurrent
es1Event
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.12
es1EventNumber
OBJECT-TYPE
The number of entries in the Event Table related to the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.12.1Integer32read-onlycurrent
es1EventTable
OBJECT-TYPE
The Event table related to the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.12.2not-accessiblecurrent
es1EventEntry
OBJECT-TYPE
.
1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1not-accessiblecurrent
es1EventIndex
OBJECT-TYPE
Event Index
1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.1Unsigned32not-accessiblecurrent
es1EventId
OBJECT-TYPE
Event Index
1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.2Unsigned32read-onlycurrent
es1EventName
OBJECT-TYPE
Event Name
1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.3DisplayStringread-onlycurrent
es1EventDateTime
OBJECT-TYPE
The date and time of the event
1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.4DisplayStringread-onlycurrent
es1EventSeverityType
OBJECT-TYPE
The event severity type ('major', 'minor', 'warning' or 'none')
1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.5DisplayStringread-onlycurrent
es1EventSeverityLevel
OBJECT-TYPE
The event severity level (0-9)
1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.6DisplayStringread-onlycurrent
es1EventEntryStatus
OBJECT-TYPE
The status of this table entry
1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.7RowStatusread-createcurrent
es1Data
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.13
es1DataNumber
OBJECT-TYPE
The number of entries in the Data Table related to the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.13.1Integer32read-onlycurrent
es1Config
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.15
es1ConfigNumber
OBJECT-TYPE
The number of entries in the Config table related to the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.15.1Integer32read-onlycurrent
es1ConfigTable
OBJECT-TYPE
The table of Config entries related to the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.15.2not-accessiblecurrent
es1ConfigEntry
OBJECT-TYPE
A Config entry
1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1not-accessiblecurrent
es1ConfigIndex
OBJECT-TYPE
The Config entry Index
1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.1Unsigned32not-accessiblecurrent
es1ConfigName
OBJECT-TYPE
The Config entry name
1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.2DisplayStringread-onlycurrent
es1ConfigValue
OBJECT-TYPE
The Config entry value
1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.3DisplayStringread-writecurrent
es1ConfigEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only for compliance
1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.4RowStatusread-createcurrent
es1ConfigList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.15.3
es1CfgEnergyMeterNumberOfGenericPulseEnergyCounter
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.20.1.15.3.100DisplayStringread-writecurrent
es1Control
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.16
es1ControlNumber
OBJECT-TYPE
The number of entries in the Control table related to the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.16.1Integer32read-onlycurrent
es1ControlTable
OBJECT-TYPE
The table of Control entries related to the Energy System
1.3.6.1.4.1.26854.3.2.1.20.1.16.2not-accessiblecurrent
es1ControlEntry
OBJECT-TYPE
A Control entry
1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1not-accessiblecurrent
es1ControlIndex
OBJECT-TYPE
The Control entry Index
1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.1Unsigned32not-accessiblecurrent
es1ControlName
OBJECT-TYPE
The Control entry name
1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.2DisplayStringread-onlycurrent
es1ControlValue
OBJECT-TYPE
The Control entry value
1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.3DisplayStringread-writecurrent
es1ControlEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only for compliance
1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.4RowStatusread-createcurrent
es1ControlList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.16.3
es1CtrlGenericClearMyEvents
OBJECT-TYPE
By writing '1' to this control element, all the events of this equipment will be cleared.
1.3.6.1.4.1.26854.3.2.1.20.1.16.3.501DisplayStringread-writecurrent
es1CtrlGenericClearAllEvents
OBJECT-TYPE
By writing '1' to this control element, all the events of this equipment and all the events of all the sub-equipments will be cleared.
1.3.6.1.4.1.26854.3.2.1.20.1.16.3.502DisplayStringread-writecurrent
es1CtrlGenericAddEvent
OBJECT-TYPE
This control element adds an event of severity none. The event name is the text written to this control element
1.3.6.1.4.1.26854.3.2.1.20.1.16.3.511DisplayStringread-writecurrent
es1CtrlGenericAddMajorEvent
OBJECT-TYPE
This control element adds an event of severity major. The event name is the text written to this control element
1.3.6.1.4.1.26854.3.2.1.20.1.16.3.512DisplayStringread-writecurrent
es1CtrlGenericResetDefaultNamesAndGroups
OBJECT-TYPE
This control element resets all the element Names, Groups and Subgroups to default values for this equipment
1.3.6.1.4.1.26854.3.2.1.20.1.16.3.521DisplayStringread-writecurrent
es1CtrlGenericResetDefaultNamesAndGroupsRecursive
OBJECT-TYPE
This control element resets all the element Names, Groups and Subgroups to default values for this equipment and all sub equipments
1.3.6.1.4.1.26854.3.2.1.20.1.16.3.522DisplayStringread-writecurrent
es1Notifications
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.18
es1NotificationPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.18.0
es1Compliance
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.19
es1ComplianceGroups
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.19.1
es1DCSystems
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20
es1dc1
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1
es1dc1GlobalStatus
OBJECT-TYPE
A textual string (alarms, normal or unknown) containing the status of the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.1DisplayString (SIZE(0..255))read-onlycurrent
es1dc1GlobalAlarmSeverityType
OBJECT-TYPE
The alarm severity type (critical, major, minor, warning, none, disabled) of the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.2DisplayStringread-onlycurrent
es1dc1GlobalAlarmSeverityLevel
OBJECT-TYPE
The alarm severity level (0-9) of the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.3Integer32read-onlycurrent
es1dc1GlobalAlarmSeverityTypeInt
OBJECT-TYPE
The alarm severity type as integer (critical=4, major=3, minor=2, warning=1, none=0) of the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.4Integer32read-onlycurrent
es1dc1Description
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10
es1dc1DescriptionNumber
OBJECT-TYPE
The number of entries in the DC System Description table
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.1Integer32read-onlycurrent
es1dc1DescriptionTable
OBJECT-TYPE
The Description table of the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2not-accessiblecurrent
es1dc1DescriptionEntry
OBJECT-TYPE
A Description entry
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1not-accessiblecurrent
es1dc1DescriptionIndex
OBJECT-TYPE
Description Index
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.1Unsigned32not-accessiblecurrent
es1dc1DescriptionName
OBJECT-TYPE
Description Name
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.2DisplayStringread-onlycurrent
es1dc1DescriptionValue
OBJECT-TYPE
Description Value
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.3DisplayStringread-createcurrent
es1dc1DescriptionEntryStatus
OBJECT-TYPE
The status of this table entry
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.4RowStatusread-createcurrent
es1dc1DescriptionList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3
es1dc1DescDescriptionDescription
OBJECT-TYPE
A free text zone to write a system description
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.1DisplayStringread-writecurrent
es1dc1DescDescriptionReference
OBJECT-TYPE
A free text zone to write the customer reference of the system
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.2DisplayStringread-writecurrent
es1dc1DescDescriptionProductName
OBJECT-TYPE
The product name of the DC system monitoring
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.11DisplayStringread-onlycurrent
es1dc1DescDescriptionHardwareReference
OBJECT-TYPE
The hardware reference of the DC system monitoring
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.12DisplayStringread-onlycurrent
es1dc1DescDescriptionSoftwareReference
OBJECT-TYPE
The software reference of the DC system monitoring
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.14DisplayStringread-onlycurrent
es1dc1DescDescriptionSerialNumber
OBJECT-TYPE
The serial number of the DC system monitoring
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.16DisplayStringread-onlycurrent
es1dc1DescDescriptionManufacturingDate
OBJECT-TYPE
The production date of the DC system monitoring
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.18DisplayStringread-onlycurrent
es1dc1DescDescriptionDistributionModuleProductName
OBJECT-TYPE
The product name of the Electronic Distribution/LVD Module
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.31DisplayStringread-onlycurrent
es1dc1DescDescriptionDistributionModuleHardwareReference
OBJECT-TYPE
The hardware reference of the Electronic Distribution/LVD Module
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.32DisplayStringread-onlycurrent
es1dc1DescDescriptionDistributionModuleSoftwareReference
OBJECT-TYPE
The software reference of the Electronic Distribution/LVD Module
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.34DisplayStringread-onlycurrent
es1dc1DescDescriptionDistributionModuleSerialNumber
OBJECT-TYPE
The serial number of the Electronic Distribution/LVD Module
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.36DisplayStringread-onlycurrent
es1dc1DescDescriptionDistributionModuleManufacturingDate
OBJECT-TYPE
The manufacturing date of the Electronic Distribution/LVD Module
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.38DisplayStringread-onlycurrent
es1dc1Alarm
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11
es1dc1AlarmNumber
OBJECT-TYPE
The number of entries in the DC System Alarm table
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.1Integer32read-onlycurrent
es1dc1AlarmTable
OBJECT-TYPE
The table of Alarm entries
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2not-accessiblecurrent
es1dc1AlarmEntry
OBJECT-TYPE
An alarm entry
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1not-accessiblecurrent
es1dc1AlarmIndex
OBJECT-TYPE
Alarm Index
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.1Unsigned32not-accessiblecurrent
es1dc1AlarmName
OBJECT-TYPE
Alarm Name
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.2DisplayStringread-onlycurrent
es1dc1AlarmActive
OBJECT-TYPE
Is the Alarm active ? 'true' for active, 'false' for not-active
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.3DisplayStringread-onlycurrent
es1dc1AlarmSeverityType
OBJECT-TYPE
The alarm severity type (major, minor, warning, none, disabled) of this alarm entry
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.4DisplayStringread-writecurrent
es1dc1AlarmSeverityLevel
OBJECT-TYPE
The alarm severity level (0-9) of this alarm entry
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.5DisplayStringread-writecurrent
es1dc1AlarmStartTime
OBJECT-TYPE
The last start time of this alarm entry (null if never active)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.6DisplayStringread-onlycurrent
es1dc1AlarmStopTime
OBJECT-TYPE
The last stop time of this alarm entry (null if alarm active)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.7DisplayStringread-onlycurrent
es1dc1AlarmEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only for MIB compliance
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.8RowStatusread-createcurrent
es1dc1AlarmSummary
OBJECT-TYPE
Summary bit vector with all the alarms state of the DC System. A '1' means alarm active, '0' means not active. Unimplemented alarms are always '0'.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.3Bits {dCBusDCBusExtraLow(0), dCBusDCBusLow(1), dCBusDCBusHigh(2), dCBusDCBusExtraHigh(3), dCBusDCBusVoltageSenseFail(4), aCBusMainsFail(5), aCBusMainsPartialFail(6), aCBusMainsLow(7), rectifiersOneRectifierFail(9), rectifiersMoreThanOneRectifierFail(10), rectifiersMissingRectifiers(11), batBatLastTestFailed(12), batBatOnDischarge(13), lVDBatLVDRelOpen(16), batBatTempTooHigh(17), batBatTempTooLow(18), batBatTempSensorFail(19), sensorsAmbientTempTooHigh(20), sensorsAmbientTempTooLow(21), sensorsAmbientTempSensorFail(22), digInputsDistributionBreakerOpen(24), digInputsBatBreakerOpen(25), digInputsDigInput1(26), digInputsDigInput2(27), digInputsDigInput3(28), digInputsDigInput4(29)}read-onlycurrent
es1dc1Event
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12
es1dc1EventNumber
OBJECT-TYPE
The number of entries in the Event Table related to the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.1Integer32read-onlycurrent
es1dc1EventTable
OBJECT-TYPE
The Event table related to the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2not-accessiblecurrent
es1dc1EventEntry
OBJECT-TYPE
.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1not-accessiblecurrent
es1dc1EventIndex
OBJECT-TYPE
Event Index
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.1Unsigned32not-accessiblecurrent
es1dc1EventId
OBJECT-TYPE
Event Index
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.2Unsigned32read-onlycurrent
es1dc1EventName
OBJECT-TYPE
Event Name
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.3DisplayStringread-onlycurrent
es1dc1EventDateTime
OBJECT-TYPE
The date and time of the event
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.4DisplayStringread-onlycurrent
es1dc1EventSeverityType
OBJECT-TYPE
The event severity type ('major', 'minor', 'warning' or 'none')
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.5DisplayStringread-onlycurrent
es1dc1EventSeverityLevel
OBJECT-TYPE
The event severity level (0-9)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.6DisplayStringread-onlycurrent
es1dc1EventEntryStatus
OBJECT-TYPE
The status of this table entry
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.7RowStatusread-createcurrent
es1dc1Data
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13
es1dc1DataNumber
OBJECT-TYPE
The number of entries in the Data Table related to the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.1Integer32read-onlycurrent
es1dc1DataTable
OBJECT-TYPE
The table of Data entries
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2not-accessiblecurrent
es1dc1DataEntry
OBJECT-TYPE
A data entry
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1not-accessiblecurrent
es1dc1DataIndex
OBJECT-TYPE
The data index
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.1Unsigned32not-accessiblecurrent
es1dc1DataName
OBJECT-TYPE
The data name
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.2DisplayStringread-onlycurrent
es1dc1DataValue
OBJECT-TYPE
The data value
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.3DisplayStringread-onlycurrent
es1dc1DataEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only present for compliance
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.4RowStatusread-createcurrent
es1dc1DataList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3
es1dc1DataSystemDCMode
OBJECT-TYPE
The DC system can have 5 values: 'Float'(0), 'Equalize'(1), 'Battery Test'(2), 'Ac Failure'(3) or 'Safe'(5)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.1Integer32read-onlycurrent
es1dc1DataSystemPreviousDCMode
OBJECT-TYPE
The previous value of the DC Mode : 'Float'(0), 'Equalize'(1), 'Battery Test'(2), 'Ac Failure'(3) or 'Safe'(5)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.2Integer32read-onlycurrent
es1dc1DataSystemNiMHChargeMode
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.5Integer32read-onlycurrent
es1dc1DataDCBusBusVoltage
OBJECT-TYPE
The DC bus voltage in volt.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.11Integer32read-onlycurrent
es1dc1DataSystemRatioDeliveredOnAvailablePower
OBJECT-TYPE
This is the ratio of the delivered power divided by the installed power, in %.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.12Integer32read-onlycurrent
es1dc1DataACBusMinutesSinceLastACFailBegin
OBJECT-TYPE
The number of minute since the last AC Failure begin
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.13Integer32read-onlycurrent
es1dc1DataACBusMinutesSinceLastACFailEnd
OBJECT-TYPE
The number of minute since the last AC Failure end
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.14Integer32read-onlycurrent
es1dc1DataRectifiersRectifiersOutPower
OBJECT-TYPE
The sum of the delivered rectifier power
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.21Integer32read-onlycurrent
es1dc1DataRectifiersRectifiersOutCurrent
OBJECT-TYPE
The sum of the delivered rectifier current
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.22Integer32read-onlycurrent
es1dc1DataRectifiersRectifiersOutPowerMax
OBJECT-TYPE
The sum of the deliverable rectifier power
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.23Integer32read-onlycurrent
es1dc1DataRectifiersRectifiersOutCurrentMax
OBJECT-TYPE
The sum of the deliverable rectifier current
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.24Integer32read-onlycurrent
es1dc1DataRectifiersNumberOfRectifierMax
OBJECT-TYPE
The maximum possible number of rectifier in this dc system
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.31Integer32read-onlycurrent
es1dc1DataRectifiersNumberOfPresentRectifier
OBJECT-TYPE
The actual number of present rectifier in this dc system
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.32Integer32read-onlycurrent
es1dc1DataRectifiersNumberOfAbsentRectifier
OBJECT-TYPE
The actual number of absent rectifier in this dc system
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.33Integer32read-onlycurrent
es1dc1DataRectifiersNumberOfActiveRectifier
OBJECT-TYPE
The actual number of active rectifier in this dc system. An active rectifier is a rectifier which is present, DC OK, AC OK and not in remote off.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.34Integer32read-onlycurrent
es1dc1DataRectifiersNumberOfACFailRectifier
OBJECT-TYPE
The actual number or rectifier in AC Failure.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.35Integer32read-onlycurrent
es1dc1DataRectifiersNumberOfDCFailRectifier
OBJECT-TYPE
The actual number or rectifier with DC Failure.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.36Integer32read-onlycurrent
es1dc1DataRectifiersNumberOfRemoteOffRectifier
OBJECT-TYPE
The actual number or rectifier in remote off.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.37Integer32read-onlycurrent
es1dc1DataRectifiersNumberOfOverTempRectifier
OBJECT-TYPE
The actual number or rectifier in Over Temperature.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.38Integer32read-onlycurrent
es1dc1DataLoadLoadPower
OBJECT-TYPE
Estimation of the load power consumption
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.51Integer32read-onlycurrent
es1dc1DataLoadLoadCurrent
OBJECT-TYPE
Estimation of the load current consumption
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.52Integer32read-onlycurrent
es1dc1DataBatBatInputCurrent
OBJECT-TYPE
Measurement of the battery input current. A negative value means that the battery is discharging
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.61Integer32read-onlycurrent
es1dc1DataBatBatInputPower
OBJECT-TYPE
Measurement of the battery input power. A negative value means that the battery is discharging
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.62Integer32read-onlycurrent
es1dc1DataBatBatTemp
OBJECT-TYPE
The battery temperature
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.71Integer32read-onlycurrent
es1dc1DataBatBatTestState
OBJECT-TYPE
This is about the result of the last battery test. 10 values are possible : 'Never Tested'(0), 'Success'(1), 'On Going'(2), 'Failed: Timeout'(3), 'Failed: Vbus Too Low'(4), 'Failed: Load Too Low'(5), 'Failed: Ac Failure'(6), 'Failed: Canceled' (7), 'Failed: Lvd Opened'(8), 'Failed: No Battery'(9)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.72Integer32read-onlycurrent
es1dc1DataBatLastBatTestDischargedCapacityRatio
OBJECT-TYPE
This is the battery capacity, in percent, discharged during the last battery test. This value is updated at the end of the battery test.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.73Integer32read-onlycurrent
es1dc1DataBatLastBatTestDischargedCapacity
OBJECT-TYPE
This is the battery capacity, in ampere hour, discharged during the last battery test. This value is updated at the end of the battery test.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.74Integer32read-onlycurrent
es1dc1DataBatLastBatTestFinalVoltage
OBJECT-TYPE
This is the bus voltage at the end of the last battery test. This value is updated at the end of the battery test.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.75Integer32read-onlycurrent
es1dc1DataBatBatTestDuration
OBJECT-TYPE
The duration of the last battery test. This value is updated at the end of the battery test. This value can't be higher than 1440 minutes (24 hours).
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.76Integer32read-onlycurrent
es1dc1DataBatPreviousBatTestDischargedCapacityRatio
OBJECT-TYPE
This is the battery capacity, in percent, discharged during the previous battery test. This value is shifted at the end of the battery test.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.77Integer32read-onlycurrent
es1dc1DataBatPreviousBatTestDischargedCapacity
OBJECT-TYPE
This is the battery capacity, in ampere hour, discharged during the previous battery test. This value is shifted at the end of the battery test.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.78Integer32read-onlycurrent
es1dc1DataBatPreviousBatTestFinalVoltage
OBJECT-TYPE
This is the bus voltage at the end of the previous battery test. This value is shifted at the end of the battery test.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.79Integer32read-onlycurrent
es1dc1DataBatPreviousBatTestDuration
OBJECT-TYPE
The duration of the previous battery test. This value is shifted at the end of the battery test. This value can't be higher than 1440 minutes (24 hours).
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.80Integer32read-onlycurrent
es1dc1DataBatPreviousBatTestState
OBJECT-TYPE
The result of the previous battery test - 10 values are possible: 'Never Tested'(0), 'Success'(1), 'On Going'(2), 'Failed: Timeout'(3), 'Failed: Vbus Too Low'(4), 'Failed: Load Too Low'(5), 'Failed: Ac Failure'(6), 'Failed: Canceled', 'Failed: Lvd Opened'(8), 'Failed: No Battery'(9)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.81Integer32read-onlycurrent
es1dc1DataBatMinutesSinceLastTestBat
OBJECT-TYPE
The number of minute since the end of last battery test
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.82Integer32read-onlycurrent
es1dc1DataBatNextScheduledBatTest
OBJECT-TYPE
The date and time of the next time the scheduled battery test will run
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.84Integer32read-onlycurrent
es1dc1DataBatBatChargeCapacity
OBJECT-TYPE
The battery charge capacity, calculated by integration of the current.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.91Integer32read-onlycurrent
es1dc1DataBatCalculatedAutonomy
OBJECT-TYPE
Calculation of the remaining autonomy. This value can change following the load of your system and the maximal depth of dicharge configuration (CF39).
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.92Integer32read-onlycurrent
es1dc1DataBatBatCurrentIntegration
OBJECT-TYPE
Actual value of the integration of the current, in Ampere * hour
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.94Integer32read-onlycurrent
es1dc1DataLVDLVDState
OBJECT-TYPE
Actual state of the LVD
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.101Integer32read-onlycurrent
es1dc1DataRelsRel1State
OBJECT-TYPE
Actual state of the Relay 1
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.111Integer32read-onlycurrent
es1dc1DataRelsRel2State
OBJECT-TYPE
Actual state of the Relay 2
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.112Integer32read-onlycurrent
es1dc1DataRelsRel3State
OBJECT-TYPE
Actual state of the Relay 3
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.113Integer32read-onlycurrent
es1dc1DataRelsRel4State
OBJECT-TYPE
Actual state of the Relay 3
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.114Integer32read-onlycurrent
es1dc1DataSmartEnergyEfficiencyOptimizedNumberOfRectifier
OBJECT-TYPE
The optimal number of ON rectifier for Efficiency Optimization
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.121Integer32read-onlycurrent
es1dc1DataSmartEnergySystemLossWithoutOptimisation
OBJECT-TYPE
Estimation of the losses without optimisation
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.122Integer32read-onlycurrent
es1dc1DataSmartEnergySystemLossWithOptimisation
OBJECT-TYPE
Estimation of the losses with optimisation
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.123Integer32read-onlycurrent
es1dc1DataSmartEnergyRectifierModelUsedForCalculation
OBJECT-TYPE
The rectifier model used
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.124Integer32read-onlycurrent
es1dc1DataSmartEnergySmartEnergySavings
OBJECT-TYPE
Estimation of the losses with optimisation
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.125Integer32read-onlycurrent
es1dc1DataSensorsAmbientTemp
OBJECT-TYPE
The ambiant temperature (second temperature sense)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.151Integer32read-onlycurrent
es1dc1DataSensorsPulseCounter4
OBJECT-TYPE
The counter value of the digital input 4.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.204Integer32read-onlycurrent
es1dc1Config
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15
es1dc1ConfigNumber
OBJECT-TYPE
The number of entries in the Config table related to the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.1Integer32read-onlycurrent
es1dc1ConfigTable
OBJECT-TYPE
The table of Config entries related to the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2not-accessiblecurrent
es1dc1ConfigEntry
OBJECT-TYPE
A Config entry
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1not-accessiblecurrent
es1dc1ConfigIndex
OBJECT-TYPE
The Config entry Index
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.1Unsigned32not-accessiblecurrent
es1dc1ConfigName
OBJECT-TYPE
The Config entry name
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.2DisplayStringread-onlycurrent
es1dc1ConfigValue
OBJECT-TYPE
The Config entry value
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.3DisplayStringread-writecurrent
es1dc1ConfigEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only for compliance
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.4RowStatusread-createcurrent
es1dc1ConfigList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3
es1dc1CfgDCBusDCBusFloatVoltageat25degC
OBJECT-TYPE
The floating dc bus voltage of the system at 25 Celsius degree
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.1DisplayStringread-writecurrent
es1dc1CfgDCBusDCBusVoltageExtraLow
OBJECT-TYPE
The bus voltage under which the alarm 'DC Bus Voltage Extra Low' is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.2DisplayStringread-writecurrent
es1dc1CfgDCBusDCBusVoltageExtraLowHysteresis
OBJECT-TYPE
The voltage hysteresis on the alarm 'DC Bus Voltage Extra Low'.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.3DisplayStringread-writecurrent
es1dc1CfgDCBusDCBusVoltageLow
OBJECT-TYPE
The bus voltage under which the alarm 'DC Bus Voltage Low' is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.4DisplayStringread-writecurrent
es1dc1CfgDCBusDCBusVoltageLowHysteresis
OBJECT-TYPE
The voltage hysteresis on the alarm 'DC Bus Voltage Low
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.5DisplayStringread-writecurrent
es1dc1CfgDCBusDCBusVoltageHigh
OBJECT-TYPE
The bus voltage over which the alarm 'DC Bus Voltage High' is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.6DisplayStringread-writecurrent
es1dc1CfgDCBusDCBusVoltageHighHysteresis
OBJECT-TYPE
The voltage hysteresis on the alarm 'DC Bus Voltage High
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.7DisplayStringread-writecurrent
es1dc1CfgDCBusDCBusVoltageExtraHigh
OBJECT-TYPE
The bus voltage over which the alarm 'DC Bus Voltage Extra High' is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.8DisplayStringread-writecurrent
es1dc1CfgDCBusDCBusVoltageExtraHighHysteresis
OBJECT-TYPE
The voltage hysteresis on the alarm 'DC Bus Voltage Extra High
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.9DisplayStringread-writecurrent
es1dc1CfgLVDLVDDisconnectVoltage
OBJECT-TYPE
The dc bus voltage under which the battery must be disconnected of the bus. This allows preserving the battery life. The load will be unpowered. This value has to be lower than the Battery test end voltage (CF70)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.10DisplayStringread-writecurrent
es1dc1CfgLVDLVDDisconnectDelay
OBJECT-TYPE
The delay in second before disconnecting the battery if the dc bus voltage is under the configured disconnected voltage. This avoids disconnection during a low bus transient.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.11DisplayStringread-writecurrent
es1dc1CfgBatTempCompensationSlope
OBJECT-TYPE
The slope of the battery temperature compensation in mv/degree. For a 48V system, -72mV/degree is often used.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.21DisplayStringread-writecurrent
es1dc1CfgBatMaxPosTempCompensation
OBJECT-TYPE
The maximal allowed positive compensation.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.22DisplayStringread-writecurrent
es1dc1CfgBatMaxNegTempCompensation
OBJECT-TYPE
The maximal allowed negative compensation.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.23DisplayStringread-writecurrent
es1dc1CfgRectifiersMinimalNumberOfPresentRectifiers
OBJECT-TYPE
The minimal number of rectifier which must be present. If there is less present rectifiers, the alarm 'Missing Rectifiers' is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.25DisplayStringread-writecurrent
es1dc1CfgRectifiersRectifierModel
OBJECT-TYPE
The rectifier model
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.26DisplayStringread-writecurrent
es1dc1CfgRectifiersForcedRemoteOffRectifers
OBJECT-TYPE
A list of rectifier which are forced in remote off. The id of the rectifier must be coma separated. Ex: 1,3 will maintain rectifier 1 and 3 off.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.27DisplayStringread-writecurrent
es1dc1CfgBatBatChargeCurrentLimit
OBJECT-TYPE
The maximal battery current when the battery is charging. The monitoring regulates the bus voltage in order to satisfy this condition. This parameter is often equal to the nominal battery capacity divided by 10.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.31DisplayStringread-writecurrent
es1dc1CfgBatBatStringCapacity
OBJECT-TYPE
The battery capacity in Ah.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.32DisplayStringread-writecurrent
es1dc1CfgBatBatTempLow
OBJECT-TYPE
The temperature under which the alarm 'Battery Temperature Too Low' must be set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.33DisplayStringread-writecurrent
es1dc1CfgBatBatTempHigh
OBJECT-TYPE
The temperature over which the alarm 'Battery Temperature Too High' must be set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.34DisplayStringread-writecurrent
es1dc1CfgBatBatTempHysteresis
OBJECT-TYPE
The hysteresis on the 'Battery Temperature Too High' and 'Battery Temperature Too Low' alarms.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.35DisplayStringread-writecurrent
es1dc1CfgBatMinimalCurrentForDischargingAlarm
OBJECT-TYPE
The minimal discharging current to set the 'Battery On Discharge' alarm.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.36DisplayStringread-writecurrent
es1dc1CfgBatCurrentHysteresisForDischargingAlarm
OBJECT-TYPE
The hysteresis on the 'Battery On Discharge' alarm.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.37DisplayStringread-writecurrent
es1dc1CfgBatPeukertNumber
OBJECT-TYPE
The Peukert number relates to the internal resistance of a battery and provides an indication of the excpected capacity. The ideal number is 1. This value can be calculated with the formula: (ln(t2)-ln(t1))/(ln(i1)-ln(i2)) where tx is the autonomy in hours at a constant discharge current of ix Amps. Often, we use t1 = 1h and t2 = 10h
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.38DisplayStringread-writecurrent
es1dc1CfgBatMaxDepthOfDischargeforAutonomyEstimation
OBJECT-TYPE
It is generally recommended to discharge maximum 60% of the battery capacity to enhance battery lifetime. By default, 100% is used for autonomy calculation. This parameter can also be used to take into account the age of the battery
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.39DisplayStringread-writecurrent
es1dc1CfgBatBoostAutomatic
OBJECT-TYPE
The boost mode must be automatically after the fact that during a mains failure, the bus voltage went under the configured 'Boost Activation Low Voltage'. This allows charging the battery faster.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.51DisplayStringread-writecurrent
es1dc1CfgBatBoostActivationLowVoltage
OBJECT-TYPE
The voltage under which the boost mode can be activated.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.52DisplayStringread-writecurrent
es1dc1CfgBatBoostTerminationVoltage
OBJECT-TYPE
The voltage over which the system must go back to floating mode.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.53DisplayStringread-writecurrent
es1dc1CfgBatBoostTerminationCurrent
OBJECT-TYPE
The battery charging current under which the system must go back to floating mode.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.54DisplayStringread-writecurrent
es1dc1CfgBatBoostTerminationTime
OBJECT-TYPE
The time in minute after which the system must go back in floating mode.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.55DisplayStringread-writecurrent
es1dc1CfgBatBatTestType
OBJECT-TYPE
Type of the battery test: <br> Capacity based: The battery must give the requested capacity before falling lower than a value <br>Time Based: The battery must sustain a defined load during a defined time.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.69DisplayStringread-writecurrent
es1dc1CfgBatBatTestEndVoltage
OBJECT-TYPE
The voltage at which any battery test must be stopped. This value has to be higher than the LVD Disconnect voltage (CF10)
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.70DisplayStringread-writecurrent
es1dc1CfgBatBatTestDischargeRatio
OBJECT-TYPE
The ratio of the battery capacity to discharge. If 30 is set, 30% of the battery will be discharged during the test
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.71DisplayStringread-writecurrent
es1dc1CfgBatBatTestInterval
OBJECT-TYPE
The number of days between two automatically started battery test. If this parameter is set to 0, the battery test is not started automatically. The user can remotely or locally start or force this test.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.72DisplayStringread-writecurrent
es1dc1CfgBatBatTestDischargeCurrent
OBJECT-TYPE
The current at which the battery must be discharged during a battery test. The monitoring regulates the bus voltage in order to satisfy this condition. The load current must be of course higher than this parameter.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.73DisplayStringread-writecurrent
es1dc1CfgBatBatTestMinimalDischargeCurrent
OBJECT-TYPE
The battery current under which the battery test must be stopped because the load is too low.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.74DisplayStringread-writecurrent
es1dc1CfgBatBatTestDuration
OBJECT-TYPE
The timeout in minute after which the battery test must be stopped.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.75DisplayStringread-writecurrent
es1dc1CfgBatBatTestRequMinutesWithoutMainsFail
OBJECT-TYPE
The minimal time in minute without mains failure in order to allow a battery start. This parameter is not taken into account when the battery test is forced.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.76DisplayStringread-writecurrent
es1dc1CfgBatBatTestSchedulerCronRule
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.77DisplayStringread-writecurrent
es1dc1CfgSmartEnergySmartEnergyBooleanCond
OBJECT-TYPE
This is the boolean condition which allows or not to automatically optimize the number of rectifier in remote off.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.83DisplayStringread-writecurrent
es1dc1CfgLVDBatLVDNodeId
OBJECT-TYPE
This is a list of the node id of the Smart Electronic LVDs, coma separated
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.86DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput1Name
OBJECT-TYPE
The name of the digital input 1
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.91DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput1NormallyClosed
OBJECT-TYPE
True/False value defining if the digital input 1 is normally closed. If this digital input is not in this default state, the related alarm is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.92DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput2Name
OBJECT-TYPE
The name of the digital input 2
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.93DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput2NormallyClosed
OBJECT-TYPE
True/False value defining if the digital input 2 is normally closed. If this digital input is not in this default state, the related alarm is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.94DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput3Name
OBJECT-TYPE
The name of the digital input 3
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.95DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput3NormallyClosed
OBJECT-TYPE
True/False value defining if the digital input 3 is normally closed. If this digital input is not in this default state, the related alarm is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.96DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput4Name
OBJECT-TYPE
The name of the digital input 4
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.97DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput4NormallyClosed
OBJECT-TYPE
True/False value defining if the digital input 4 is normally closed. If this digital input is not in this default state, the related alarm is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.98DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput5Name
OBJECT-TYPE
The name of the digital input 5
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.99DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput5NormallyClosed
OBJECT-TYPE
True/False value defining if the digital input 5 is normally closed. If this digital input is not in this default state, the related alarm is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.100DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput6Name
OBJECT-TYPE
The name of the digital input 6
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.101DisplayStringread-writecurrent
es1dc1CfgDigInputsDigInput6NormallyClosed
OBJECT-TYPE
True/False value defining if the digital input 6 is normally closed. If this digital input is not in this default state, the related alarm is set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.102DisplayStringread-writecurrent
es1dc1CfgRelsDryAlarm1AlternativeBooleanCond
OBJECT-TYPE
Another Boolean condition to activate the dry alarm relay 1. The way to define boolean condition is detailed in the PLC chapter.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.111DisplayStringread-writecurrent
es1dc1CfgRelsDryAlarm2AlternativeBooleanCond
OBJECT-TYPE
Another Boolean condition to activate the dry alarm relay 2. The way to define boolean condition is detailed in the PLC chapter.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.112DisplayStringread-writecurrent
es1dc1CfgRelsDryAlarm3AlternativeBooleanCond
OBJECT-TYPE
Another Boolean condition to activate the dry alarm relay 3. The way to define boolean condition is detailed in the PLC chapter.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.113DisplayStringread-writecurrent
es1dc1CfgRelsDryAlarm4AlternativeBooleanCond
OBJECT-TYPE
Another Boolean condition to activate the dry alarm relay 4. The way to define boolean condition is detailed in the PLC chapter.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.114DisplayStringread-writecurrent
es1dc1CfgSensorsAmbientTempLow
OBJECT-TYPE
The temperature under which the alarm 'Ambiant Temperature Too Low' must be set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.131DisplayStringread-writecurrent
es1dc1CfgSensorsAmbientTempHigh
OBJECT-TYPE
The temperature under which the alarm 'Ambiant Temperature Too Low' must be set.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.132DisplayStringread-writecurrent
es1dc1CfgSensorsAmbientTempHysteresis
OBJECT-TYPE
The hysteresis on the 'Battery Temperature Too High' and 'Battery Temperature Too Low' alarms.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.133DisplayStringread-writecurrent
es1dc1CfgGenericReadAccessUserNumbers
OBJECT-TYPE
The list of the user numbers which have read access to this equipment. The user numbers are coma separated. The accepted user id are 1,2,3,4 and 5. Ex: 1,3,4
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.521DisplayStringread-writecurrent
es1dc1CfgGenericWriteAccessUserNumbers
OBJECT-TYPE
The list of the user numbers which have write access to this equipment. This means that these users can modify the configuration element, the alarm settings and use the control elements. The user numbers are coma separated. The accepted user ids are 1,2,3,4 and 5. Ex: 1,3,4
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.522DisplayStringread-writecurrent
es1dc1CfgGenericEventTableLength
OBJECT-TYPE
The maximum length of the table. The value must be comprised between 10 and 4000
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.601DisplayStringread-writecurrent
es1dc1CfgGenericEventTableLengthByRectifier
OBJECT-TYPE
The maximum length of the table. The value must be comprised between 10 and 4000
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.602DisplayStringread-writecurrent
es1dc1CfgPLCNumberOfPLCData
OBJECT-TYPE
The number of PLC data. Every equipment can manage up to 30 user programmable data. Data elements are automatically added in the data table. Configuration parameters are added to set the PLC Data Name and the PLC Data Mathematical calculation. In order to use these functionalities, you need a license with the 'PLC' module
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.901DisplayStringread-writecurrent
es1dc1CfgPLCNumberOfPLCAlarm
OBJECT-TYPE
The number of PLC alarm. Every equipment can manage up to 30 user programmable alarms. Alarm elements are automatically added in the alarm table. The alarm parameters are added to set the PLC Alarm Name and the PLC Alarm Boolean condition. In order to use these functionalities, you need a licence with the 'PLC' module
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.902DisplayStringread-writecurrent
es1dc1Control
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16
es1dc1ControlNumber
OBJECT-TYPE
The number of entries in the Control table related to the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.1Integer32read-onlycurrent
es1dc1ControlTable
OBJECT-TYPE
The table of Control entries related to the DC System
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2not-accessiblecurrent
es1dc1ControlEntry
OBJECT-TYPE
A Control entry
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1not-accessiblecurrent
es1dc1ControlIndex
OBJECT-TYPE
The Control entry Index
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.1Unsigned32not-accessiblecurrent
es1dc1ControlName
OBJECT-TYPE
The Control entry name
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.2DisplayStringread-onlycurrent
es1dc1ControlValue
OBJECT-TYPE
The Control entry value
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.3DisplayStringread-writecurrent
es1dc1ControlEntryStatus
OBJECT-TYPE
The status of this table entry - not used, only for compliance
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.4RowStatusread-createcurrent
es1dc1ControlList
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3
es1dc1CtrlSystemBackToFloat
OBJECT-TYPE
The dc system must go back in floating mode.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.1DisplayStringread-writecurrent
es1dc1CtrlSystemStartBatTest
OBJECT-TYPE
The dc system must start a battery test.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.2DisplayStringread-writecurrent
es1dc1CtrlSystemForceBatTest
OBJECT-TYPE
The dc system must force a battery test.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.3DisplayStringread-writecurrent
es1dc1CtrlSystemStartBoostMode
OBJECT-TYPE
The dc system must go in boost mode.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.4DisplayStringread-writecurrent
es1dc1CtrlLVDOpenTheLVD
OBJECT-TYPE
Try to open the LVD. It could not work if the LVD is electronic, and the request will be canceled after 15 sec.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.11DisplayStringread-writecurrent
es1dc1CtrlLVDCloseTheLVD
OBJECT-TYPE
The LVD must be closed
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.12DisplayStringread-writecurrent
es1dc1CtrlBatCorrectBatCurrentOffset
OBJECT-TYPE
NA
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.21DisplayStringread-writecurrent
es1dc1CtrlBatResetLastBatTestState
OBJECT-TYPE
Reset the state of the last battery test. If an alarm 'Battery Last Test Failed' is set, the alarm will be cleared.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.41DisplayStringread-writecurrent
es1dc1CtrlSaveSaveConfInMCU
OBJECT-TYPE
Save configuration parameters in the MCU microcontroller. If comp@s is not present, the system will be correctly managed.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.51DisplayStringread-writecurrent
es1dc1CtrlAdvancedSetMCUSpecificConfId
OBJECT-TYPE
This control allows to reconfigure the MCU to support specific hardware configuration, with embedded distribution for example
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.55DisplayStringread-writecurrent
es1dc1CtrlDigInputsSetDigInput4CounterValue
OBJECT-TYPE
Set Counter Value
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.61DisplayStringread-writecurrent
es1dc1CtrlRelsInvertRel1StateForXSeconds
OBJECT-TYPE
Generate Pulse on relay 1
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.111DisplayStringread-writecurrent
es1dc1CtrlRelsInvertRel2StateForXSeconds
OBJECT-TYPE
Generate Pulse on relay 2
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.112DisplayStringread-writecurrent
es1dc1CtrlRelsInvertRel3StateForXSeconds
OBJECT-TYPE
Generate Pulse on relay 3
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.113DisplayStringread-writecurrent
es1dc1CtrlRelsInvertRel4StateForXSeconds
OBJECT-TYPE
Generate Pulse on relay 4
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.114DisplayStringread-writecurrent
es1dc1CtrlGenericClearMyEvents
OBJECT-TYPE
By writing '1' to this control element, all the events of this equipment will be cleared.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.501DisplayStringread-writecurrent
es1dc1CtrlGenericClearAllEvents
OBJECT-TYPE
By writing '1' to this control element, all the events of this equipment and all the events of all the sub-equipments will be cleared.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.502DisplayStringread-writecurrent
es1dc1CtrlGenericAddEvent
OBJECT-TYPE
This control element adds an event of severity none. The event name is the text written to this control element
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.511DisplayStringread-writecurrent
es1dc1CtrlGenericAddMajorEvent
OBJECT-TYPE
This control element adds an event of severity major. The event name is the text written to this control element
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.512DisplayStringread-writecurrent
es1dc1CtrlGenericResetDefaultNamesAndGroups
OBJECT-TYPE
This control element resets all the element Names, Groups and Subgroups to default values for this equipment
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.521DisplayStringread-writecurrent
es1dc1CtrlGenericResetDefaultNamesAndGroupsRecursive
OBJECT-TYPE
This control element resets all the element Names, Groups and Subgroups to default values for this equipment and all sub equipments
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.522DisplayStringread-writecurrent
es1dc1Notifications
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.18
es1dc1NotificationPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.18.0
es1dc1Compliance
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19
es1dc1ComplianceGroups
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.1
es1InverterSystems
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.25
es1RemotePowerFeedingSystems
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.20.1.28
extensions
OBJECT-IDENTITY
1.3.6.1.4.1.26854.3.2.1.21

Notifications

NameOIDStatus
siteV1NotificationOfEvent
NOTIFICATION-TYPE
Notification generated when a new event appears
1.3.6.1.4.1.26854.3.2.1.18.0.1current
es1NotificationOfEvent
NOTIFICATION-TYPE
Notification generated when a new event appears
1.3.6.1.4.1.26854.3.2.1.20.1.18.0.1current
es1dc1NotificationOfEvent
NOTIFICATION-TYPE
Notification generated when a new event appears
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.18.0.1current

Conformance

NameOIDStatus
siteV1GlobalGroup
OBJECT-GROUP
text
1.3.6.1.4.1.26854.3.2.1.19.1.1current
siteV1NotificationGroup
NOTIFICATION-GROUP
text
1.3.6.1.4.1.26854.3.2.1.19.1.2current
siteV1FullCompliance
MODULE-COMPLIANCE
The compliance statement for SNMPV2 entities which implement the SNMPV2 MIB.
1.3.6.1.4.1.26854.3.2.1.19.2current
es1GlobalGroup
OBJECT-GROUP
text
1.3.6.1.4.1.26854.3.2.1.20.1.19.1.1current
es1NotificationGroup
NOTIFICATION-GROUP
text
1.3.6.1.4.1.26854.3.2.1.20.1.19.1.2current
es1FullCompliance
MODULE-COMPLIANCE
The compliance statement for SNMPV2 entities which implement the SNMPV2 MIB.
1.3.6.1.4.1.26854.3.2.1.20.1.19.2current
es1dc1GlobalGroup
OBJECT-GROUP
text
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.1.1current
es1dc1NotificationGroup
NOTIFICATION-GROUP
text
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.1.2current
es1dc1FullCompliance
MODULE-COMPLIANCE
The compliance statement for SNMPV2 entities which implement the SNMPV2 MIB.
1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.2current