SITE-MONITORING-MIB
- Registered at
- 1.3.6.1.4.1.26854
- Last updated
- 2017-05-16 16:00
- Organization
- Alpha Innovations
- Revisions
- 2017-05-16 16:00
- Namespace
- alpha
- Source file
SITE-MONITORING-MIB- Digest
sha256:3079408802c166e45015608da9a2e8c22daaa174c4a9d8f351f8c2e64cd0daab
Description
Alpha Innovations SNMP corporate naming convention Organises the SNMP OIDs according to the design centres that generate the different MIBs
Contact
Jean-Philippe Vanhulst Postal: Alpha Innovations Rue Alexander Fleming 1 B-1348 Louvain-la-Neuve Belgium phone +32 10 438 382 e-mail mail@alphainnovations.eu
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-SMI | Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, RowStatus, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
SITE-MONITORING-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| atsa OBJECT-IDENTITY | 1.3.6.1.4.1.26854 | |||
| atsaCorporate OBJECT-IDENTITY | 1.3.6.1.4.1.26854.1 | |||
| atsaUs OBJECT-IDENTITY | 1.3.6.1.4.1.26854.2 | |||
| atsaEu OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3 | |||
| atsaEuDevices OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.1 | |||
| siteMonitoring OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2 | |||
| siteV1 OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1 | |||
| siteV1GlobalStatus OBJECT-TYPE A textual string (alarms, normal or unknown) containing the status of the Site | 1.3.6.1.4.1.26854.3.2.1.1 | DisplayString (SIZE(0..255)) | read-only | current |
| siteV1GlobalAlarmSeverityType OBJECT-TYPE The alarm severity type (critical, major, minor, warning, none, disabled) of the Site | 1.3.6.1.4.1.26854.3.2.1.2 | DisplayString | read-only | current |
| siteV1GlobalAlarmSeverityLevel OBJECT-TYPE The alarm severity level (0-9) of the Site | 1.3.6.1.4.1.26854.3.2.1.3 | Integer32 | read-only | current |
| siteV1GlobalAlarmSeverityTypeInt OBJECT-TYPE The alarm severity type as integer (critical=4, major=3, minor=2, warning=1, none=0) of the Site | 1.3.6.1.4.1.26854.3.2.1.4 | Integer32 | read-only | current |
| siteV1Description OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.10 | |||
| siteV1DescriptionNumber OBJECT-TYPE The number of entries in the Site Description table | 1.3.6.1.4.1.26854.3.2.1.10.1 | Integer32 | read-only | current |
| siteV1DescriptionTable OBJECT-TYPE The Description table of the Site | 1.3.6.1.4.1.26854.3.2.1.10.2 | not-accessible | current | |
| siteV1DescriptionEntry OBJECT-TYPE A Description entry | 1.3.6.1.4.1.26854.3.2.1.10.2.1 | not-accessible | current | |
| siteV1DescriptionIndex OBJECT-TYPE Description Index | 1.3.6.1.4.1.26854.3.2.1.10.2.1.1 | Unsigned32 | not-accessible | current |
| siteV1DescriptionName OBJECT-TYPE Description Name | 1.3.6.1.4.1.26854.3.2.1.10.2.1.2 | DisplayString | read-only | current |
| siteV1DescriptionValue OBJECT-TYPE Description Value | 1.3.6.1.4.1.26854.3.2.1.10.2.1.3 | DisplayString | read-create | current |
| siteV1DescriptionEntryStatus OBJECT-TYPE The status of this table entry | 1.3.6.1.4.1.26854.3.2.1.10.2.1.4 | RowStatus | read-create | current |
| siteV1DescriptionList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.10.3 | |||
| siteV1DescDescriptionSiteNumber OBJECT-TYPE The identification number of the site | 1.3.6.1.4.1.26854.3.2.1.10.3.1 | DisplayString | read-write | current |
| siteV1DescDescriptionSiteName OBJECT-TYPE The name of the site | 1.3.6.1.4.1.26854.3.2.1.10.3.2 | DisplayString | read-write | current |
| siteV1DescDescriptionShortDescription OBJECT-TYPE A short description of the site | 1.3.6.1.4.1.26854.3.2.1.10.3.3 | DisplayString | read-write | current |
| siteV1DescDescriptionInfo OBJECT-TYPE Some more information about the site | 1.3.6.1.4.1.26854.3.2.1.10.3.4 | DisplayString | read-write | current |
| siteV1DescDescriptionDescription OBJECT-TYPE A free text zone to write a system description | 1.3.6.1.4.1.26854.3.2.1.10.3.5 | DisplayString | read-write | current |
| siteV1DescDescriptionReference OBJECT-TYPE A free text zone to write the customer reference of the system | 1.3.6.1.4.1.26854.3.2.1.10.3.6 | DisplayString | read-write | current |
| siteV1DescDescriptionContactName OBJECT-TYPE Contact Name | 1.3.6.1.4.1.26854.3.2.1.10.3.7 | DisplayString | read-write | current |
| siteV1DescDescriptionPhoneNumber OBJECT-TYPE Phone Number | 1.3.6.1.4.1.26854.3.2.1.10.3.8 | DisplayString | read-write | current |
| siteV1DescDescriptionStreet OBJECT-TYPE Street part of the site address | 1.3.6.1.4.1.26854.3.2.1.10.3.11 | DisplayString | read-write | current |
| siteV1DescDescriptionCity OBJECT-TYPE City part of the site address | 1.3.6.1.4.1.26854.3.2.1.10.3.12 | DisplayString | read-write | current |
| siteV1DescDescriptionProvince OBJECT-TYPE Province part of the site address | 1.3.6.1.4.1.26854.3.2.1.10.3.13 | DisplayString | read-write | current |
| siteV1DescDescriptionPostalCode OBJECT-TYPE Postal Code part of the site address | 1.3.6.1.4.1.26854.3.2.1.10.3.14 | DisplayString | read-write | current |
| siteV1DescDescriptionRegion OBJECT-TYPE Region part of the site address | 1.3.6.1.4.1.26854.3.2.1.10.3.15 | DisplayString | read-write | current |
| siteV1DescDescriptionCountry OBJECT-TYPE Country part of the site address | 1.3.6.1.4.1.26854.3.2.1.10.3.16 | DisplayString | read-write | current |
| siteV1DescDescriptionGroup1 OBJECT-TYPE Group Level 1 (For Armada Clustering) | 1.3.6.1.4.1.26854.3.2.1.10.3.21 | DisplayString | read-write | current |
| siteV1DescDescriptionGroup2 OBJECT-TYPE Group Level 2 (For Armada Clustering) | 1.3.6.1.4.1.26854.3.2.1.10.3.22 | DisplayString | read-write | current |
| siteV1DescDescriptionGroup3 OBJECT-TYPE Group Level 3 (For Armada Clustering) | 1.3.6.1.4.1.26854.3.2.1.10.3.23 | DisplayString | read-write | current |
| siteV1DescDescriptionGroup4 OBJECT-TYPE Group Level 4 (For Armada Clustering) | 1.3.6.1.4.1.26854.3.2.1.10.3.24 | DisplayString | read-write | current |
| siteV1DescDescriptionGroup5 OBJECT-TYPE Group Level 5 (For Armada Clustering) | 1.3.6.1.4.1.26854.3.2.1.10.3.25 | DisplayString | read-write | current |
| siteV1DescDescriptionLatitude OBJECT-TYPE The latitude of the site | 1.3.6.1.4.1.26854.3.2.1.10.3.31 | DisplayString | read-write | current |
| siteV1DescDescriptionLongitude OBJECT-TYPE The longitude of the site | 1.3.6.1.4.1.26854.3.2.1.10.3.32 | DisplayString | read-write | current |
| siteV1DescDescriptionAltitude OBJECT-TYPE The altitude of the site | 1.3.6.1.4.1.26854.3.2.1.10.3.33 | DisplayString | read-write | current |
| siteV1DescControllerSoftwareRevision OBJECT-TYPE The software revision of Comp@s (read only) | 1.3.6.1.4.1.26854.3.2.1.10.3.91 | DisplayString | read-only | current |
| siteV1DescControllerOperatingSystemRevision OBJECT-TYPE The operating system of Comp@s (read only) | 1.3.6.1.4.1.26854.3.2.1.10.3.92 | DisplayString | read-only | current |
| siteV1DescControllerCPU OBJECT-TYPE Information about the CPU | 1.3.6.1.4.1.26854.3.2.1.10.3.93 | DisplayString | read-only | current |
| siteV1DescControllerCard OBJECT-TYPE Information about the hardware system containing Compas | 1.3.6.1.4.1.26854.3.2.1.10.3.94 | DisplayString | read-only | current |
| siteV1DescControllerStarterVersion OBJECT-TYPE Information about the starter component of Compas | 1.3.6.1.4.1.26854.3.2.1.10.3.100 | DisplayString | read-only | current |
| siteV1DescControllerFactoryCompasVersion OBJECT-TYPE Information about the revision of Compas in Factory folder | 1.3.6.1.4.1.26854.3.2.1.10.3.105 | DisplayString | read-only | current |
| siteV1DescControllerUserCompasVersion OBJECT-TYPE Information about the revision of Compas in user folder | 1.3.6.1.4.1.26854.3.2.1.10.3.106 | DisplayString | read-only | current |
| siteV1DescControllerFactoryFTPServerVersion OBJECT-TYPE Information about the revision of Ftp Server in Factory folder | 1.3.6.1.4.1.26854.3.2.1.10.3.110 | DisplayString | read-only | current |
| siteV1DescControllerUserFTPServerVersion OBJECT-TYPE Information about the revision of Ftp Server in Factory folder | 1.3.6.1.4.1.26854.3.2.1.10.3.111 | DisplayString | read-only | current |
| siteV1Alarm OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.11 | |||
| siteV1AlarmNumber OBJECT-TYPE The number of entries in the Site Alarm table | 1.3.6.1.4.1.26854.3.2.1.11.1 | Integer32 | read-only | current |
| siteV1AlarmTable OBJECT-TYPE The table of Alarm entries | 1.3.6.1.4.1.26854.3.2.1.11.2 | not-accessible | current | |
| siteV1AlarmEntry OBJECT-TYPE An alarm entry | 1.3.6.1.4.1.26854.3.2.1.11.2.1 | not-accessible | current | |
| siteV1AlarmIndex OBJECT-TYPE Alarm Index | 1.3.6.1.4.1.26854.3.2.1.11.2.1.1 | Unsigned32 | not-accessible | current |
| siteV1AlarmName OBJECT-TYPE Alarm Name | 1.3.6.1.4.1.26854.3.2.1.11.2.1.2 | DisplayString | read-only | current |
| siteV1AlarmActive OBJECT-TYPE Is the Alarm active ? 'true' for active, 'false' for not-active | 1.3.6.1.4.1.26854.3.2.1.11.2.1.3 | DisplayString | read-only | current |
| siteV1AlarmSeverityType OBJECT-TYPE The alarm severity type (major, minor, warning, none, disabled) of this alarm entry | 1.3.6.1.4.1.26854.3.2.1.11.2.1.4 | DisplayString | read-write | current |
| siteV1AlarmSeverityLevel OBJECT-TYPE The alarm severity level (0-9) of this alarm entry | 1.3.6.1.4.1.26854.3.2.1.11.2.1.5 | DisplayString | read-write | current |
| siteV1AlarmStartTime OBJECT-TYPE The last start time of this alarm entry (null if never active) | 1.3.6.1.4.1.26854.3.2.1.11.2.1.6 | DisplayString | read-only | current |
| siteV1AlarmStopTime OBJECT-TYPE The last stop time of this alarm entry (null if alarm active) | 1.3.6.1.4.1.26854.3.2.1.11.2.1.7 | DisplayString | read-only | current |
| siteV1AlarmEntryStatus OBJECT-TYPE The status of this table entry - not used, only for MIB compliance | 1.3.6.1.4.1.26854.3.2.1.11.2.1.8 | RowStatus | read-create | current |
| siteV1AlarmSummary OBJECT-TYPE Summary bit vector with all the alarms state of the Site. A '1' means alarm active, '0' means not active. Unimplemented alarms are always '0'. | 1.3.6.1.4.1.26854.3.2.1.11.3 | Bits {inventoryCANBusFail(0), inventoryCANBusAddressingError(1), inventoryMissingCANBusNodeIDs(2), inventoryRunningCANLSSDeviceDetection(3), inventoryRunningCANFirmwareUpgrade(4), controllerControllerRebootRequired(10), controllerLastConfChangesUnsaved(14), xMLXMLHeartbeatPostFail(20)} | read-only | current |
| siteV1Event OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.12 | |||
| siteV1EventNumber OBJECT-TYPE The number of entries in the Event Table related to the Site | 1.3.6.1.4.1.26854.3.2.1.12.1 | Integer32 | read-only | current |
| siteV1EventTable OBJECT-TYPE The Event table related to the Site | 1.3.6.1.4.1.26854.3.2.1.12.2 | not-accessible | current | |
| siteV1EventEntry OBJECT-TYPE . | 1.3.6.1.4.1.26854.3.2.1.12.2.1 | not-accessible | current | |
| siteV1EventIndex OBJECT-TYPE Event Index | 1.3.6.1.4.1.26854.3.2.1.12.2.1.1 | Unsigned32 | not-accessible | current |
| siteV1EventId OBJECT-TYPE Event Index | 1.3.6.1.4.1.26854.3.2.1.12.2.1.2 | Unsigned32 | read-only | current |
| siteV1EventName OBJECT-TYPE Event Name | 1.3.6.1.4.1.26854.3.2.1.12.2.1.3 | DisplayString | read-only | current |
| siteV1EventDateTime OBJECT-TYPE The date and time of the event | 1.3.6.1.4.1.26854.3.2.1.12.2.1.4 | DisplayString | read-only | current |
| siteV1EventSeverityType OBJECT-TYPE The event severity type ('major', 'minor', 'warning' or 'none') | 1.3.6.1.4.1.26854.3.2.1.12.2.1.5 | DisplayString | read-only | current |
| siteV1EventSeverityLevel OBJECT-TYPE The event severity level (0-9) | 1.3.6.1.4.1.26854.3.2.1.12.2.1.6 | DisplayString | read-only | current |
| siteV1EventEntryStatus OBJECT-TYPE The status of this table entry | 1.3.6.1.4.1.26854.3.2.1.12.2.1.7 | RowStatus | read-create | current |
| siteV1Data OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.13 | |||
| siteV1DataNumber OBJECT-TYPE The number of entries in the Data Table related to the Site | 1.3.6.1.4.1.26854.3.2.1.13.1 | Integer32 | read-only | current |
| siteV1DataTable OBJECT-TYPE The table of Data entries | 1.3.6.1.4.1.26854.3.2.1.13.2 | not-accessible | current | |
| siteV1DataEntry OBJECT-TYPE A data entry | 1.3.6.1.4.1.26854.3.2.1.13.2.1 | not-accessible | current | |
| siteV1DataIndex OBJECT-TYPE The data index | 1.3.6.1.4.1.26854.3.2.1.13.2.1.1 | Unsigned32 | not-accessible | current |
| siteV1DataName OBJECT-TYPE The data name | 1.3.6.1.4.1.26854.3.2.1.13.2.1.2 | DisplayString | read-only | current |
| siteV1DataValue OBJECT-TYPE The data value | 1.3.6.1.4.1.26854.3.2.1.13.2.1.3 | DisplayString | read-only | current |
| siteV1DataEntryStatus OBJECT-TYPE The status of this table entry - not used, only present for compliance | 1.3.6.1.4.1.26854.3.2.1.13.2.1.4 | RowStatus | read-create | current |
| siteV1DataList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.13.3 | |||
| siteV1DataNetworkCurrentIPAddress OBJECT-TYPE This is the actual IP address of the Comp@s platform. If the Ethernet cable is not correctly connected, the address will be 0.0.0.0. | 1.3.6.1.4.1.26854.3.2.1.13.3.1 | Integer32 | read-only | current |
| siteV1DataNetworkCurrentIPMask OBJECT-TYPE This is the actual IP address of the Comp@s platform. If the Ethernet cable is not correctly connected, the address will be 0.0.0.0. | 1.3.6.1.4.1.26854.3.2.1.13.3.2 | Integer32 | read-only | current |
| siteV1DataNetworkCurrentMACAddress OBJECT-TYPE This is the MAC address of IP interface. | 1.3.6.1.4.1.26854.3.2.1.13.3.3 | Integer32 | read-only | current |
| siteV1DataControllerLicensedOptions OBJECT-TYPE This is the options of the actual license. | 1.3.6.1.4.1.26854.3.2.1.13.3.11 | Integer32 | read-only | current |
| siteV1DataTimeDateAndTimeLocal OBJECT-TYPE This is the local time of the monitoring. | 1.3.6.1.4.1.26854.3.2.1.13.3.21 | DisplayString | read-only | current |
| siteV1DataTimeDateAndTimeUTC OBJECT-TYPE This is the UTC time of the monitoring. | 1.3.6.1.4.1.26854.3.2.1.13.3.22 | DisplayString | read-only | current |
| siteV1DataControllerMonitoringMemoryUsed OBJECT-TYPE This is actual amount of RAM memory used by the application. | 1.3.6.1.4.1.26854.3.2.1.13.3.31 | Integer32 | read-only | current |
| siteV1DataControllerCPUPercentageUsage OBJECT-TYPE This is actual percentage of CPU used | 1.3.6.1.4.1.26854.3.2.1.13.3.32 | Integer32 | read-only | current |
| siteV1DataControllerFreeFlashMemorySpace OBJECT-TYPE This is free flash memory available on the Comp@s card, in Megabytes | 1.3.6.1.4.1.26854.3.2.1.13.3.33 | Integer32 | read-only | current |
| siteV1DataControllerFTPServerStatus OBJECT-TYPE Status of the FTP Server. Compatible only with version >= 2.26.X.X. The configuration is available at controller -> FTP Server page. | 1.3.6.1.4.1.26854.3.2.1.13.3.35 | DisplayString | read-only | current |
| siteV1DataDataRecordsTotalFifoSizeOfSecondRecords OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.13.3.41 | Integer32 | read-only | current |
| siteV1DataDataRecordsTotalFifoSizeOfMinuteRecords OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.13.3.42 | Integer32 | read-only | current |
| siteV1DataDataRecordsTotalFifoSizeOfHourRecords OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.13.3.43 | Integer32 | read-only | current |
| siteV1DataDataRecordsTotalFifoSizeOfDayRecords OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.13.3.44 | Integer32 | read-only | current |
| siteV1DataInventoryCANBusNodeIDs OBJECT-TYPE The coma separated list of the node ids present on the CAN bus. | 1.3.6.1.4.1.26854.3.2.1.13.3.51 | Integer32 | read-only | current |
| siteV1DataCloudLinkCloudLinkState OBJECT-TYPE Cloud Link State | 1.3.6.1.4.1.26854.3.2.1.13.3.166 | DisplayString | read-only | current |
| siteV1Config OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.15 | |||
| siteV1ConfigNumber OBJECT-TYPE The number of entries in the Config table related to the Site | 1.3.6.1.4.1.26854.3.2.1.15.1 | Integer32 | read-only | current |
| siteV1ConfigTable OBJECT-TYPE The table of Config entries related to the Site | 1.3.6.1.4.1.26854.3.2.1.15.2 | not-accessible | current | |
| siteV1ConfigEntry OBJECT-TYPE A Config entry | 1.3.6.1.4.1.26854.3.2.1.15.2.1 | not-accessible | current | |
| siteV1ConfigIndex OBJECT-TYPE The Config entry Index | 1.3.6.1.4.1.26854.3.2.1.15.2.1.1 | Unsigned32 | not-accessible | current |
| siteV1ConfigName OBJECT-TYPE The Config entry name | 1.3.6.1.4.1.26854.3.2.1.15.2.1.2 | DisplayString | read-only | current |
| siteV1ConfigValue OBJECT-TYPE The Config entry value | 1.3.6.1.4.1.26854.3.2.1.15.2.1.3 | DisplayString | read-write | current |
| siteV1ConfigEntryStatus OBJECT-TYPE The status of this table entry - not used, only for compliance | 1.3.6.1.4.1.26854.3.2.1.15.2.1.4 | RowStatus | read-create | current |
| siteV1ConfigList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.15.3 | |||
| siteV1CfgNetworkDHCPEnabled OBJECT-TYPE The monitoring will try to get an IP with the DHCP protocol if this parameter is set to True. By default, this parameter is set to False. | 1.3.6.1.4.1.26854.3.2.1.15.3.1 | DisplayString | read-write | current |
| siteV1CfgNetworkIPAddressIfStatic OBJECT-TYPE The static IP address of the monitoring. This configuration parameter is not used if the DHCP is enabled. The default IP is 192.168.45.2. | 1.3.6.1.4.1.26854.3.2.1.15.3.2 | DisplayString | read-write | current |
| siteV1CfgNetworkSubnetMaskIfStatic OBJECT-TYPE The static Subnet Mask of the monitoring. This configuration parameter is not used if the DHCP is enabled. The default mask is 255.255.255.0. | 1.3.6.1.4.1.26854.3.2.1.15.3.3 | DisplayString | read-write | current |
| siteV1CfgNetworkDefaultGatewayIfStatic OBJECT-TYPE The static Default Gateway of the monitoring. This configuration parameter is not used if DHCP is enabled. This is only useful if the monitoring have to use a gateway, this is generally not necessary. The default gateway is 192.168.45.1. | 1.3.6.1.4.1.26854.3.2.1.15.3.4 | DisplayString | read-write | current |
| siteV1CfgNetworkDNSIfStatic OBJECT-TYPE The static DNS of the monitoring. This configuration parameter is used to resolve URI and server name. This is not necessary if you are only IP address as target server. The default DNS server is 192.168.45.1. | 1.3.6.1.4.1.26854.3.2.1.15.3.5 | DisplayString | read-write | current |
| siteV1CfgNetworkMaxTransmissionUnit OBJECT-TYPE Specifies the TCP/IP MTU for the network interface | 1.3.6.1.4.1.26854.3.2.1.15.3.8 | DisplayString | read-write | current |
| siteV1CfgTimeSNTPTimeServer OBJECT-TYPE The address of the server acting as SNTP timer server. If this server is not valid, the monitoring cannot update automatically his time. You can use several time server by usin a coma separator without space. | 1.3.6.1.4.1.26854.3.2.1.15.3.11 | DisplayString | read-write | current |
| siteV1CfgTimeTimeZoneName OBJECT-TYPE The Time Zone of the site | 1.3.6.1.4.1.26854.3.2.1.15.3.14 | DisplayString | read-write | current |
| siteV1CfgTimeSNTPTimeRefresh OBJECT-TYPE Set the time between synchronisation with the SNTP server (max 1000 hours, by default 178) | 1.3.6.1.4.1.26854.3.2.1.15.3.15 | DisplayString | read-write | current |
| siteV1CfgTimeSNTPTimeRecoveryRefresh OBJECT-TYPE Set the time to wait before retry if a synchronisation fail (max 1000 hours, by default 24) | 1.3.6.1.4.1.26854.3.2.1.15.3.16 | DisplayString | read-write | current |
| siteV1CfgWebServerWebServerSecurityEnabled OBJECT-TYPE This is a True/False parameter used to activate or deactivate the access control to the web server. | 1.3.6.1.4.1.26854.3.2.1.15.3.22 | DisplayString | read-write | current |
| siteV1CfgWebServerWebServerPort OBJECT-TYPE This is an unsigned integer parameter used to configure the port at which the web server is accessible. By default, the port is 80. If you change this port, you must be sure that the traffic is allowed by your switches and routers on this port. | 1.3.6.1.4.1.26854.3.2.1.15.3.23 | DisplayString | read-write | current |
| siteV1CfgWebServerWebAuthenticationMethod OBJECT-TYPE The web access security can be managed with 3 authentication methods: Basic Access, Digest Access or Basic with Radius. | 1.3.6.1.4.1.26854.3.2.1.15.3.24 | DisplayString | read-write | current |
| siteV1CfgWebServerHttpsWebServerPort OBJECT-TYPE This is a port number to activate or deactivate the https web server - 0 or 443 by default | 1.3.6.1.4.1.26854.3.2.1.15.3.26 | DisplayString | read-write | current |
| siteV1CfgWebServerDefaultPage OBJECT-TYPE The default page displayed on logon (dashboard, site, summary, alarm_event, ...) | 1.3.6.1.4.1.26854.3.2.1.15.3.31 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventPostingActivated OBJECT-TYPE This is a True/False parameter used to activate or deactivate the XML event posting. | 1.3.6.1.4.1.26854.3.2.1.15.3.41 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventPostingRefreshTime OBJECT-TYPE The minimal time in second between to calculation of the XML events to send. By default, this is done every two seconds. | 1.3.6.1.4.1.26854.3.2.1.15.3.42 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventPostingTimeout OBJECT-TYPE The timeout in millisecond when trying to post XML data to a Web Server. | 1.3.6.1.4.1.26854.3.2.1.15.3.43 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventPostingToSecOnlyIfPrimFail OBJECT-TYPE If this parameter is set to true, the events will be sent to secondary only if primary server is not available. If this parameter is set to false, all the events will be sent to primary and secondary server | 1.3.6.1.4.1.26854.3.2.1.15.3.45 | DisplayString | read-write | current |
| siteV1CfgXMLXMLTablesToPostOnXMLEvent OBJECT-TYPE The list of the tables to send when an event is generated. (description,alarm,data,config,control). This allows to have armada database updated on event. | 1.3.6.1.4.1.26854.3.2.1.15.3.46 | DisplayString | read-write | current |
| siteV1CfgXMLXMLHeartbeatTime OBJECT-TYPE This is the time between 2 XML Post of heartbeat. If set to 0, no heartbeat. | 1.3.6.1.4.1.26854.3.2.1.15.3.51 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPActivated OBJECT-TYPE This is a True/False parameter used to activate or deactivate the SNMP agent. | 1.3.6.1.4.1.26854.3.2.1.15.3.61 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPTrapVersion OBJECT-TYPE Traps/Notification can be sent with SNMP V1, V2c or V3 format. | 1.3.6.1.4.1.26854.3.2.1.15.3.63 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPGETMinSecurityLevel OBJECT-TYPE 4 choices are available: No Authentication, V1 Community, V2c Community or V3. | 1.3.6.1.4.1.26854.3.2.1.15.3.64 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPSETMinSecurityLevel OBJECT-TYPE 4 choices are available: No Authentication, V1 Community, V2c Community or V3. | 1.3.6.1.4.1.26854.3.2.1.15.3.65 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPV3AuthAlgorithm OBJECT-TYPE 3 choices are available: MD5, SHA, Any | 1.3.6.1.4.1.26854.3.2.1.15.3.66 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPV3PrivacyAlgorithm OBJECT-TYPE 3 choices are available: DES, AES, 3DES | 1.3.6.1.4.1.26854.3.2.1.15.3.67 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPV3PrivacyPassword OBJECT-TYPE The global SNMP V3 Encryption Password. This one is common for all the users to avoid complexity | 1.3.6.1.4.1.26854.3.2.1.15.3.68 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPV3EngineID OBJECT-TYPE The SNMP V3 Local Engine ID string | 1.3.6.1.4.1.26854.3.2.1.15.3.69 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPV3TrapAuthAlgorithm OBJECT-TYPE 2 choices are available: MD5, SHA | 1.3.6.1.4.1.26854.3.2.1.15.3.72 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPV3TrapPrivacyAlgorithm OBJECT-TYPE 3 choices are available: DES, AES, 3DES | 1.3.6.1.4.1.26854.3.2.1.15.3.73 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPV3TrapUsername OBJECT-TYPE The SNMP V3 Trap UserName used for all the SNMP V3 traps | 1.3.6.1.4.1.26854.3.2.1.15.3.74 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPV3TrapAuthPassword OBJECT-TYPE The SNMP V3 Trap Authentication Password | 1.3.6.1.4.1.26854.3.2.1.15.3.75 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPV3TrapPrivacyPassword OBJECT-TYPE The SNMP V3 Trap Privacy Password | 1.3.6.1.4.1.26854.3.2.1.15.3.76 | DisplayString | read-write | current |
| siteV1CfgSNMPSiteDescriptionIdsIncludedInTraps OBJECT-TYPE List of site Description Elements to send on traps. (to have the site reference and the city in each trap for example). The list is separated with ';' | 1.3.6.1.4.1.26854.3.2.1.15.3.77 | DisplayString | read-write | current |
| siteV1CfgGenericGenerateEventOnConfChanges OBJECT-TYPE This is a True/False parameter used to activate or deactivate the tracking of configuration changes | 1.3.6.1.4.1.26854.3.2.1.15.3.81 | DisplayString | read-write | current |
| siteV1CfgDataRecordsAutoArchivePeriodDataRecord OBJECT-TYPE Period in hour to auto save records (when detailled and long duration records are needed). 0 means disabled. | 1.3.6.1.4.1.26854.3.2.1.15.3.82 | DisplayString | read-write | current |
| siteV1CfgGenericGenerateEventOnControlExecution OBJECT-TYPE This is a True/False parameter used to activate or deactivate the tracking of control execution | 1.3.6.1.4.1.26854.3.2.1.15.3.83 | DisplayString | read-write | current |
| siteV1CfgGenericGenerateEventOnAlarmAcknowledge OBJECT-TYPE This is a True/False parameter used to activate or deactivate the tracking of alarm acknowledgment | 1.3.6.1.4.1.26854.3.2.1.15.3.84 | DisplayString | read-write | current |
| siteV1CfgInventoryRequiredCANBusNodeIDs OBJECT-TYPE This is a coma separated list with the required CAN bus node ids | 1.3.6.1.4.1.26854.3.2.1.15.3.91 | DisplayString | read-write | current |
| siteV1CfgInventoryLSSCANidrange OBJECT-TYPE By default 50-80, means up to 50 Can Nodes like rectifiers with CAN Id 50 to 80. To support up to 100 rectifiers, change it to 1-100. | 1.3.6.1.4.1.26854.3.2.1.15.3.92 | DisplayString | read-write | current |
| siteV1CfgInventorySystemNodesDefinition OBJECT-TYPE dc3(30-100) | 1.3.6.1.4.1.26854.3.2.1.15.3.93 | DisplayString | read-write | current |
| siteV1CfgInventoryLSSCANOpenSavedConf OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.15.3.95 | DisplayString | read-write | current |
| siteV1CfgUsersAdministratorLoginPassword OBJECT-TYPE This is the login and the password of the administrator. It is saved with a special syntax. First the login in clear, followed of 2 points, followed of the MD5 hashed password. If you change the login:password by entering a non hashed password, this last is automatically hashed. | 1.3.6.1.4.1.26854.3.2.1.15.3.101 | DisplayString | read-write | current |
| siteV1CfgUsersUser1LoginPassword OBJECT-TYPE This is the login and the password of the user number 1. | 1.3.6.1.4.1.26854.3.2.1.15.3.102 | DisplayString | read-write | current |
| siteV1CfgUsersUser2LoginPassword OBJECT-TYPE This is the login and the password of the user number 2. | 1.3.6.1.4.1.26854.3.2.1.15.3.103 | DisplayString | read-write | current |
| siteV1CfgUsersUser3LoginPassword OBJECT-TYPE This is the login and the password of the user number 3. | 1.3.6.1.4.1.26854.3.2.1.15.3.104 | DisplayString | read-write | current |
| siteV1CfgUsersUser4LoginPassword OBJECT-TYPE This is the login and the password of the user number 4. | 1.3.6.1.4.1.26854.3.2.1.15.3.105 | DisplayString | read-write | current |
| siteV1CfgUsersUser5LoginPassword OBJECT-TYPE This is the login and the password of the user number 5. | 1.3.6.1.4.1.26854.3.2.1.15.3.106 | DisplayString | read-write | current |
| siteV1CfgRadiusAuthenticationRadiusServer OBJECT-TYPE Radius Server address. If you have a secondary server, you could use a coma to separate it. | 1.3.6.1.4.1.26854.3.2.1.15.3.111 | DisplayString | read-write | current |
| siteV1CfgRadiusAuthenticationRadiusPort OBJECT-TYPE Radius Port. If you have a secondary server, you could use a coma to separate it. | 1.3.6.1.4.1.26854.3.2.1.15.3.112 | DisplayString | read-write | current |
| siteV1CfgRadiusAuthenticationRadiusSecret OBJECT-TYPE Radius PassPhrase | 1.3.6.1.4.1.26854.3.2.1.15.3.113 | DisplayString | read-write | current |
| siteV1CfgEmailEnableEmailFeature OBJECT-TYPE Enable/Disable the email feature | 1.3.6.1.4.1.26854.3.2.1.15.3.120 | DisplayString | read-write | current |
| siteV1CfgEmailSmtpServer OBJECT-TYPE Smtp Server. If you are using a domain name, make sure you configured the network Dns (CF5) | 1.3.6.1.4.1.26854.3.2.1.15.3.121 | DisplayString | read-write | current |
| siteV1CfgEmailSmtpDomain OBJECT-TYPE Smtp Domain. (Required by some servers.) | 1.3.6.1.4.1.26854.3.2.1.15.3.122 | DisplayString | read-write | current |
| siteV1CfgEmailSmtpUserLoginPassword OBJECT-TYPE Smtp Login and Password. The password is encrypted. To enter a new login and password, enter login:password and validate, the password will be encrypted. | 1.3.6.1.4.1.26854.3.2.1.15.3.123 | DisplayString | read-write | current |
| siteV1CfgEmailMailSender OBJECT-TYPE Mail Sender (The 'From' of the emails you will receive) | 1.3.6.1.4.1.26854.3.2.1.15.3.130 | DisplayString | read-write | current |
| siteV1CfgEmailMailRecipients OBJECT-TYPE Mail Recipients, separated with semicolon ';' | 1.3.6.1.4.1.26854.3.2.1.15.3.131 | DisplayString | read-write | current |
| siteV1CfgEmailMinimalSeverityTypeToSendMail OBJECT-TYPE This is the minimal severity of the event to send a Summary Mail | 1.3.6.1.4.1.26854.3.2.1.15.3.135 | DisplayString | read-write | current |
| siteV1CfgControllerAutomaticReboot OBJECT-TYPE Cron rules used in order to restart automatically the controller. Before rebooting configuration, events and data records are saved. | 1.3.6.1.4.1.26854.3.2.1.15.3.150 | DisplayString | read-write | current |
| siteV1CfgCloudLinkCloudEnabled OBJECT-TYPE Enable Cloud Connection | 1.3.6.1.4.1.26854.3.2.1.15.3.161 | DisplayString | read-write | current |
| siteV1CfgCloudLinkCloudServer OBJECT-TYPE Cloud Server | 1.3.6.1.4.1.26854.3.2.1.15.3.162 | DisplayString | read-write | current |
| siteV1CfgCloudLinkCloudPort OBJECT-TYPE Cloud Port | 1.3.6.1.4.1.26854.3.2.1.15.3.163 | DisplayString | read-write | current |
| siteV1CfgCloudLinkCloudCredential OBJECT-TYPE Enter Credential of your AlphaCloud account in order to connect. You have to enter username:password in order to save your credential. | 1.3.6.1.4.1.26854.3.2.1.15.3.164 | DisplayString | read-write | current |
| siteV1CfgCloudLinkCloudCluster OBJECT-TYPE Cloud Cluster | 1.3.6.1.4.1.26854.3.2.1.15.3.165 | DisplayString | read-write | current |
| siteV1CfgInventoryRS485ExtensionsConf OBJECT-TYPE The configuration string for RS485 Extensions | 1.3.6.1.4.1.26854.3.2.1.15.3.210 | DisplayString | read-write | current |
| siteV1CfgInventoryEthernetExtensionsConf OBJECT-TYPE The configuration string for Ethernet Extensions | 1.3.6.1.4.1.26854.3.2.1.15.3.220 | DisplayString | read-write | current |
| siteV1CfgScriptingEnabledscripts OBJECT-TYPE This parameter enable all CompasLua Scripting capabilities. You can control scripts in Files -> Files manager > scripting tab. | 1.3.6.1.4.1.26854.3.2.1.15.3.250 | DisplayString | read-write | current |
| siteV1CfgScriptingNumberofErrorsbeforetriggeringalarm OBJECT-TYPE Number of errors before triggering the scripting error alarm. When number of error is higher than this parameter, the alarm is triggered. If 0 is set, the alarm is deactivated | 1.3.6.1.4.1.26854.3.2.1.15.3.251 | DisplayString | read-write | current |
| siteV1CfgGenericReadAccessUserNumbers OBJECT-TYPE The list of the user numbers which have read access to this equipment. The user numbers are coma separated. The accepted user id are 1,2,3,4 and 5. Ex: 1,3,4 | 1.3.6.1.4.1.26854.3.2.1.15.3.521 | DisplayString | read-write | current |
| siteV1CfgGenericWriteAccessUserNumbers OBJECT-TYPE The list of the user numbers which have write access to this equipment. This means that these users can modify the configuration element, the alarm settings and use the control elements. The user numbers are coma separated. The accepted user ids are 1,2,3,4 and 5. Ex: 1,3,4 | 1.3.6.1.4.1.26854.3.2.1.15.3.522 | DisplayString | read-write | current |
| siteV1CfgGenericEventTableLength OBJECT-TYPE The maximum length of the table. The value must be comprised between 10 and 4000 | 1.3.6.1.4.1.26854.3.2.1.15.3.601 | DisplayString | read-write | current |
| siteV1CfgSNMPSNMPTrapTargetsIP OBJECT-TYPE One or multiple target IP to send traps, coma separated. Ex: 130.145.23.1, 130.23.12.45 | 1.3.6.1.4.1.26854.3.2.1.15.3.611 | DisplayString | read-write | current |
| siteV1CfgSNMPMinimalEventSeverityForTraps OBJECT-TYPE This is the minimal severity of the event to send a SNMP trap | 1.3.6.1.4.1.26854.3.2.1.15.3.612 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventsPrimPostURL OBJECT-TYPE This is the first URL at which the events related to this equipment must be posted. The XML ETSI standard is used in the posted data content. | 1.3.6.1.4.1.26854.3.2.1.15.3.651 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventsPrimPostLogin OBJECT-TYPE The login which must be used when posting events to the primary server | 1.3.6.1.4.1.26854.3.2.1.15.3.652 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventsPrimPostPassword OBJECT-TYPE The password which must be used when posting events to the primary server | 1.3.6.1.4.1.26854.3.2.1.15.3.653 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventsSecPostURL OBJECT-TYPE This is the second URL at which the events related to this equipment must be posted. The XML ETSI standard is used in the posted data content. This allows having redundancy with the management server. | 1.3.6.1.4.1.26854.3.2.1.15.3.661 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventsSecPostLogin OBJECT-TYPE The login which must be used when posting events to the secondary server | 1.3.6.1.4.1.26854.3.2.1.15.3.662 | DisplayString | read-write | current |
| siteV1CfgXMLXMLEventsSecPostPassword OBJECT-TYPE The password which must be used when posting events to the secondary server | 1.3.6.1.4.1.26854.3.2.1.15.3.663 | DisplayString | read-write | current |
| siteV1CfgPLCNumberOfPLCData OBJECT-TYPE The number of PLC data. Every equipment can manage up to 30 user programmable data. Data elements are automatically added in the data table. Configuration parameters are added to set the PLC Data Name and the PLC Data Mathematical calculation. In order to use these functionalities, you need a license with the 'PLC' module | 1.3.6.1.4.1.26854.3.2.1.15.3.901 | DisplayString | read-write | current |
| siteV1CfgPLCNumberOfPLCAlarm OBJECT-TYPE The number of PLC alarm. Every equipment can manage up to 30 user programmable alarms. Alarm elements are automatically added in the alarm table. The alarm parameters are added to set the PLC Alarm Name and the PLC Alarm Boolean condition. In order to use these functionalities, you need a licence with the 'PLC' module | 1.3.6.1.4.1.26854.3.2.1.15.3.902 | DisplayString | read-write | current |
| siteV1Control OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.16 | |||
| siteV1ControlNumber OBJECT-TYPE The number of entries in the Control table related to the Site | 1.3.6.1.4.1.26854.3.2.1.16.1 | Integer32 | read-only | current |
| siteV1ControlTable OBJECT-TYPE The table of Control entries related to the Site | 1.3.6.1.4.1.26854.3.2.1.16.2 | not-accessible | current | |
| siteV1ControlEntry OBJECT-TYPE A Control entry | 1.3.6.1.4.1.26854.3.2.1.16.2.1 | not-accessible | current | |
| siteV1ControlIndex OBJECT-TYPE The Control entry Index | 1.3.6.1.4.1.26854.3.2.1.16.2.1.1 | Unsigned32 | not-accessible | current |
| siteV1ControlName OBJECT-TYPE The Control entry name | 1.3.6.1.4.1.26854.3.2.1.16.2.1.2 | DisplayString | read-only | current |
| siteV1ControlValue OBJECT-TYPE The Control entry value | 1.3.6.1.4.1.26854.3.2.1.16.2.1.3 | DisplayString | read-write | current |
| siteV1ControlEntryStatus OBJECT-TYPE The status of this table entry - not used, only for compliance | 1.3.6.1.4.1.26854.3.2.1.16.2.1.4 | RowStatus | read-create | current |
| siteV1ControlList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.16.3 | |||
| siteV1CtrlControllerRebootController OBJECT-TYPE Writing a '1' to this control element will reboot the monitoring. Events and Records will be saved. | 1.3.6.1.4.1.26854.3.2.1.16.3.1 | DisplayString | read-write | current |
| siteV1CtrlControllerSaveConfAndRebootController OBJECT-TYPE Writing a '1' to this control element will first save the actual configuration and will reboot the monitoring after. | 1.3.6.1.4.1.26854.3.2.1.16.3.2 | DisplayString | read-write | current |
| siteV1CtrlControllerRebootControllerWithoutSavingRecords OBJECT-TYPE Writing a '1' to this control element will reboot the monitoring without saving records | 1.3.6.1.4.1.26854.3.2.1.16.3.3 | DisplayString | read-write | current |
| siteV1CtrlNetworkApplyNetworkConf OBJECT-TYPE Writing a '1' to this control element will reconfigure the ethernet according to the Network Configuration. If you change the IP address in the config table without using this command after, the configuration is not applied. | 1.3.6.1.4.1.26854.3.2.1.16.3.6 | DisplayString | read-write | current |
| siteV1CtrlTimeForceSNTPTimeRefresh OBJECT-TYPE Writing a '1' to this control element will force the monitoring to try to refresh his time with the configured SNTP Time Server. | 1.3.6.1.4.1.26854.3.2.1.16.3.11 | DisplayString | read-write | current |
| siteV1CtrlTimeSetLocalTime OBJECT-TYPE Writing a date and time to this control element allows to manually change the local time of the monitoring. The syntax of the date and the time is: 2007-11-19T13:02:34 | 1.3.6.1.4.1.26854.3.2.1.16.3.12 | DisplayString | read-write | current |
| siteV1CtrlTimeSetUTCTime OBJECT-TYPE Writing a date and time to this control element allows to manually change the UTC time of the monitoring. The syntax of the date and the time is: 2007-11-19T13:02:34 | 1.3.6.1.4.1.26854.3.2.1.16.3.13 | DisplayString | read-write | current |
| siteV1CtrlTimeResetUptime OBJECT-TYPE Writing a '1' to this control element will reset the uptime of the monitoring. | 1.3.6.1.4.1.26854.3.2.1.16.3.14 | DisplayString | read-write | current |
| siteV1CtrlControllerCleanandSaveXMLUserConf OBJECT-TYPE Writing a '1' to this control element will remove the configuration sections related to missing equipments, than save all the configuration of all the connected equipment in a XML format. This file is read when the monitoring is starting in order to configure the monitoring. This file is also accessible trough the FTP server or can be downloaded trough the web interface. | 1.3.6.1.4.1.26854.3.2.1.16.3.20 | DisplayString | read-write | current |
| siteV1CtrlControllerSaveXMLUserConf OBJECT-TYPE Writing a '1' to this control element will save all the configuration of all the connected (or previously connected) equipment in a XML format. This file is read when the monitoring is starting in order to configure the monitoring. This file is also accessible trough the FTP server or can be downloaded trough the web interface. | 1.3.6.1.4.1.26854.3.2.1.16.3.21 | DisplayString | read-write | current |
| siteV1CtrlControllerSaveInventory OBJECT-TYPE Writing a '1' to this control element will save save the inventory in a XML format. This file is read when the monitoring is starting in order to configure the monitoring. This file is also accessible trough the FTP server or can be downloaded trough the web interface. | 1.3.6.1.4.1.26854.3.2.1.16.3.22 | DisplayString | read-write | current |
| siteV1CtrlDataRecordsSaveDataRecords OBJECT-TYPE Writing a '1' to this control element will force the monitoring to save all the data records. This is useful if you want to unpower the Comp@s monitoring. This function is called automatically everyday. | 1.3.6.1.4.1.26854.3.2.1.16.3.33 | DisplayString | read-write | current |
| siteV1CtrlDataRecordsExportDataRecordsinCSV OBJECT-TYPE Writing a '1' to this control element will force the monitoring to save all the CVS records files. The CSV files are stored in the records folder. | 1.3.6.1.4.1.26854.3.2.1.16.3.34 | DisplayString | read-write | current |
| siteV1CtrlDataRecordsArchiveDataRecords OBJECT-TYPE Writing a '1' to this control element will force the monitoring to save all the data records. This is useful if you want to unpower the Comp@s monitoring. This function is called automatically everyday. | 1.3.6.1.4.1.26854.3.2.1.16.3.35 | DisplayString | read-write | current |
| siteV1CtrlDataRecordsDeleteAllDataRecords OBJECT-TYPE Writing a '1' to this control element will force the monitoring to save all the data records. This is useful if you want to unpower the Comp@s monitoring. This function is called automatically everyday. | 1.3.6.1.4.1.26854.3.2.1.16.3.36 | DisplayString | read-write | current |
| siteV1CtrlControllerEmulateRecords OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.16.3.40 | DisplayString | read-write | current |
| siteV1CtrlControllerReloadTranslations OBJECT-TYPE Writing a '1' to this control element will reload all the csv translation files | 1.3.6.1.4.1.26854.3.2.1.16.3.41 | DisplayString | read-write | current |
| siteV1CtrlControllerReloadLicense OBJECT-TYPE Writing a '1' to this control element will reload the license file | 1.3.6.1.4.1.26854.3.2.1.16.3.51 | DisplayString | read-write | current |
| siteV1CtrlControllerManageFTPServer OBJECT-TYPE This Control is used to manage the FTP Server | 1.3.6.1.4.1.26854.3.2.1.16.3.55 | DisplayString | read-write | current |
| siteV1CtrlInventoryRemoveAbsentEquipments OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.16.3.61 | DisplayString | read-write | current |
| siteV1CtrlInventoryResetCANBusNode OBJECT-TYPE Writing a valid CAN bus node id to this control element will reset the correspondent device. | 1.3.6.1.4.1.26854.3.2.1.16.3.81 | DisplayString | read-write | current |
| siteV1CtrlInventorySaveCANOpenLSSConf OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.16.3.82 | DisplayString | read-write | current |
| siteV1CtrlInventoryStartNewInventory OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.16.3.83 | DisplayString | read-write | current |
| siteV1CtrlInventoryUpgradeNodeFirmware OBJECT-TYPE This control element is used to start the firmware upgrade of a CAN bus Node. You need to upload first the firmware trough ftp in the /user/firmware path. Then you need to write the id number of the CAN Node, followed by a coma, followed by the file name. Example : '101,SOFT_0000030_01.txt'. | 1.3.6.1.4.1.26854.3.2.1.16.3.91 | DisplayString | read-write | current |
| siteV1CtrlInventoryCancelFirmwareUpgrade OBJECT-TYPE This control element is used to cancel the running firmware upgrade of a CAN bus Node. | 1.3.6.1.4.1.26854.3.2.1.16.3.92 | DisplayString | read-write | current |
| siteV1CtrlFilesFlashBinary OBJECT-TYPE This control element is used to start a binary flash update. You need to upload first the firmware trough ftp in the /user/firmware path. | 1.3.6.1.4.1.26854.3.2.1.16.3.103 | DisplayString | read-write | current |
| siteV1CtrlFilesDownloadFileFromUrl OBJECT-TYPE This control element is used to download a file wiht HTTP get, the argument is an url. The file is saved in the upload folder | 1.3.6.1.4.1.26854.3.2.1.16.3.110 | DisplayString | read-write | current |
| siteV1CtrlFilesDeleteUserUploadedFile OBJECT-TYPE This control element is used to delete a file in the user-upload folder. This is riskless as these files are not used, they are temporary files. | 1.3.6.1.4.1.26854.3.2.1.16.3.111 | DisplayString | read-write | current |
| siteV1CtrlFilesMoveUserUploadedFile OBJECT-TYPE This control element is used to copy a file from the user-upload folder to another one. Be aware of what your are doing ! | 1.3.6.1.4.1.26854.3.2.1.16.3.112 | DisplayString | read-write | current |
| siteV1CtrlFilesExtractZipFileinuserupload OBJECT-TYPE This control element is used to delete a file in the user-upload folder. This is riskless as these files are not used, they are temporary files. | 1.3.6.1.4.1.26854.3.2.1.16.3.113 | DisplayString | read-write | current |
| siteV1CtrlEmailSendSummaryEmail OBJECT-TYPE This control element is used to force the sending of a summary to the configured mail address | 1.3.6.1.4.1.26854.3.2.1.16.3.120 | DisplayString | read-write | current |
| siteV1CtrlScriptingControlLuaScript OBJECT-TYPE This control element is used to control the lua scripting system. Available command are: enable[Enable Lua Capabilities], disable[Disable Lua Capabilities], restart[Restart All Lua Capabilities], refresh[Read the folder script (if you added a file when system is running)], enable filename[enable filename.lua located in folder user/scripts], disable filename[disable filename.lua located in folder user/scripts], restart filename : Restart fileName[file must be enabled], reseterrors[Reset all errors counters], reseterrors filename[Reset errors from filename | 1.3.6.1.4.1.26854.3.2.1.16.3.250 | DisplayString | read-write | current |
| siteV1CtrlControllerAdvancedFunctionGenericCommandExecution OBJECT-TYPE This control is used to perform advanced operation. | 1.3.6.1.4.1.26854.3.2.1.16.3.300 | DisplayString | read-write | current |
| siteV1CtrlGenericClearMyEvents OBJECT-TYPE By writing '1' to this control element, all the events of this equipment will be cleared. | 1.3.6.1.4.1.26854.3.2.1.16.3.501 | DisplayString | read-write | current |
| siteV1CtrlGenericClearAllEvents OBJECT-TYPE By writing '1' to this control element, all the events of this equipment and all the events of all the sub-equipments will be cleared. | 1.3.6.1.4.1.26854.3.2.1.16.3.502 | DisplayString | read-write | current |
| siteV1CtrlGenericAddEvent OBJECT-TYPE This control element adds an event of severity none. The event name is the text written to this control element | 1.3.6.1.4.1.26854.3.2.1.16.3.511 | DisplayString | read-write | current |
| siteV1CtrlGenericAddMajorEvent OBJECT-TYPE This control element adds an event of severity major. The event name is the text written to this control element | 1.3.6.1.4.1.26854.3.2.1.16.3.512 | DisplayString | read-write | current |
| siteV1CtrlGenericResetDefaultNamesAndGroups OBJECT-TYPE This control element resets all the element Names, Groups and Subgroups to default values for this equipment | 1.3.6.1.4.1.26854.3.2.1.16.3.521 | DisplayString | read-write | current |
| siteV1CtrlGenericResetDefaultNamesAndGroupsRecursive OBJECT-TYPE This control element resets all the element Names, Groups and Subgroups to default values for this equipment and all sub equipments | 1.3.6.1.4.1.26854.3.2.1.16.3.522 | DisplayString | read-write | current |
| siteV1Notifications OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.18 | |||
| siteV1NotificationPrefix OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.18.0 | |||
| siteV1Compliance OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.19 | |||
| siteV1ComplianceGroups OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.19.1 | |||
| energySystems OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20 | |||
| es1 OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1 | |||
| es1GlobalStatus OBJECT-TYPE A textual string (alarms, normal or unknown) containing the status of the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.1 | DisplayString (SIZE(0..255)) | read-only | current |
| es1GlobalAlarmSeverityType OBJECT-TYPE The alarm severity type (critical, major, minor, warning, none, disabled) of the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.2 | DisplayString | read-only | current |
| es1GlobalAlarmSeverityLevel OBJECT-TYPE The alarm severity level (0-9) of the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.3 | Integer32 | read-only | current |
| es1GlobalAlarmSeverityTypeInt OBJECT-TYPE The alarm severity type as integer (critical=4, major=3, minor=2, warning=1, none=0) of the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.4 | Integer32 | read-only | current |
| es1Description OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.10 | |||
| es1DescriptionNumber OBJECT-TYPE The number of entries in the Energy System Description table | 1.3.6.1.4.1.26854.3.2.1.20.1.10.1 | Integer32 | read-only | current |
| es1DescriptionTable OBJECT-TYPE The Description table of the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.10.2 | not-accessible | current | |
| es1DescriptionEntry OBJECT-TYPE A Description entry | 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1 | not-accessible | current | |
| es1DescriptionIndex OBJECT-TYPE Description Index | 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.1 | Unsigned32 | not-accessible | current |
| es1DescriptionName OBJECT-TYPE Description Name | 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.2 | DisplayString | read-only | current |
| es1DescriptionValue OBJECT-TYPE Description Value | 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.3 | DisplayString | read-create | current |
| es1DescriptionEntryStatus OBJECT-TYPE The status of this table entry | 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.4 | RowStatus | read-create | current |
| es1DescriptionList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.10.3 | |||
| es1DescDescriptionDescription OBJECT-TYPE A free text zone to write a system description | 1.3.6.1.4.1.26854.3.2.1.20.1.10.3.1 | DisplayString | read-write | current |
| es1DescDescriptionReference OBJECT-TYPE A free text zone to write the customer reference of the system | 1.3.6.1.4.1.26854.3.2.1.20.1.10.3.2 | DisplayString | read-write | current |
| es1Alarm OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.11 | |||
| es1AlarmNumber OBJECT-TYPE The number of entries in the Energy System Alarm table | 1.3.6.1.4.1.26854.3.2.1.20.1.11.1 | Integer32 | read-only | current |
| es1AlarmTable OBJECT-TYPE The table of Alarm entries | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2 | not-accessible | current | |
| es1AlarmEntry OBJECT-TYPE An alarm entry | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1 | not-accessible | current | |
| es1AlarmIndex OBJECT-TYPE Alarm Index | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.1 | Unsigned32 | not-accessible | current |
| es1AlarmName OBJECT-TYPE Alarm Name | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.2 | DisplayString | read-only | current |
| es1AlarmActive OBJECT-TYPE Is the Alarm active ? 'true' for active, 'false' for not-active | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.3 | DisplayString | read-only | current |
| es1AlarmSeverityType OBJECT-TYPE The alarm severity type (major, minor, warning, none, disabled) of this alarm entry | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.4 | DisplayString | read-write | current |
| es1AlarmSeverityLevel OBJECT-TYPE The alarm severity level (0-9) of this alarm entry | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.5 | DisplayString | read-write | current |
| es1AlarmStartTime OBJECT-TYPE The last start time of this alarm entry (null if never active) | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.6 | DisplayString | read-only | current |
| es1AlarmStopTime OBJECT-TYPE The last stop time of this alarm entry (null if alarm active) | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.7 | DisplayString | read-only | current |
| es1AlarmEntryStatus OBJECT-TYPE The status of this table entry - not used, only for MIB compliance | 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.8 | RowStatus | read-create | current |
| es1AlarmSummary OBJECT-TYPE Summary bit vector with all the alarms state of the Energy System. A '1' means alarm active, '0' means not active. Unimplemented alarms are always '0'. | 1.3.6.1.4.1.26854.3.2.1.20.1.11.3 | Bits {none(0)} | read-only | current |
| es1Event OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.12 | |||
| es1EventNumber OBJECT-TYPE The number of entries in the Event Table related to the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.12.1 | Integer32 | read-only | current |
| es1EventTable OBJECT-TYPE The Event table related to the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.12.2 | not-accessible | current | |
| es1EventEntry OBJECT-TYPE . | 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1 | not-accessible | current | |
| es1EventIndex OBJECT-TYPE Event Index | 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.1 | Unsigned32 | not-accessible | current |
| es1EventId OBJECT-TYPE Event Index | 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.2 | Unsigned32 | read-only | current |
| es1EventName OBJECT-TYPE Event Name | 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.3 | DisplayString | read-only | current |
| es1EventDateTime OBJECT-TYPE The date and time of the event | 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.4 | DisplayString | read-only | current |
| es1EventSeverityType OBJECT-TYPE The event severity type ('major', 'minor', 'warning' or 'none') | 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.5 | DisplayString | read-only | current |
| es1EventSeverityLevel OBJECT-TYPE The event severity level (0-9) | 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.6 | DisplayString | read-only | current |
| es1EventEntryStatus OBJECT-TYPE The status of this table entry | 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.7 | RowStatus | read-create | current |
| es1Data OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.13 | |||
| es1DataNumber OBJECT-TYPE The number of entries in the Data Table related to the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.13.1 | Integer32 | read-only | current |
| es1Config OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.15 | |||
| es1ConfigNumber OBJECT-TYPE The number of entries in the Config table related to the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.15.1 | Integer32 | read-only | current |
| es1ConfigTable OBJECT-TYPE The table of Config entries related to the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.15.2 | not-accessible | current | |
| es1ConfigEntry OBJECT-TYPE A Config entry | 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1 | not-accessible | current | |
| es1ConfigIndex OBJECT-TYPE The Config entry Index | 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.1 | Unsigned32 | not-accessible | current |
| es1ConfigName OBJECT-TYPE The Config entry name | 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.2 | DisplayString | read-only | current |
| es1ConfigValue OBJECT-TYPE The Config entry value | 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.3 | DisplayString | read-write | current |
| es1ConfigEntryStatus OBJECT-TYPE The status of this table entry - not used, only for compliance | 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.4 | RowStatus | read-create | current |
| es1ConfigList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.15.3 | |||
| es1CfgEnergyMeterNumberOfGenericPulseEnergyCounter OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.20.1.15.3.100 | DisplayString | read-write | current |
| es1Control OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.16 | |||
| es1ControlNumber OBJECT-TYPE The number of entries in the Control table related to the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.16.1 | Integer32 | read-only | current |
| es1ControlTable OBJECT-TYPE The table of Control entries related to the Energy System | 1.3.6.1.4.1.26854.3.2.1.20.1.16.2 | not-accessible | current | |
| es1ControlEntry OBJECT-TYPE A Control entry | 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1 | not-accessible | current | |
| es1ControlIndex OBJECT-TYPE The Control entry Index | 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.1 | Unsigned32 | not-accessible | current |
| es1ControlName OBJECT-TYPE The Control entry name | 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.2 | DisplayString | read-only | current |
| es1ControlValue OBJECT-TYPE The Control entry value | 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.3 | DisplayString | read-write | current |
| es1ControlEntryStatus OBJECT-TYPE The status of this table entry - not used, only for compliance | 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.4 | RowStatus | read-create | current |
| es1ControlList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.16.3 | |||
| es1CtrlGenericClearMyEvents OBJECT-TYPE By writing '1' to this control element, all the events of this equipment will be cleared. | 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.501 | DisplayString | read-write | current |
| es1CtrlGenericClearAllEvents OBJECT-TYPE By writing '1' to this control element, all the events of this equipment and all the events of all the sub-equipments will be cleared. | 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.502 | DisplayString | read-write | current |
| es1CtrlGenericAddEvent OBJECT-TYPE This control element adds an event of severity none. The event name is the text written to this control element | 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.511 | DisplayString | read-write | current |
| es1CtrlGenericAddMajorEvent OBJECT-TYPE This control element adds an event of severity major. The event name is the text written to this control element | 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.512 | DisplayString | read-write | current |
| es1CtrlGenericResetDefaultNamesAndGroups OBJECT-TYPE This control element resets all the element Names, Groups and Subgroups to default values for this equipment | 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.521 | DisplayString | read-write | current |
| es1CtrlGenericResetDefaultNamesAndGroupsRecursive OBJECT-TYPE This control element resets all the element Names, Groups and Subgroups to default values for this equipment and all sub equipments | 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.522 | DisplayString | read-write | current |
| es1Notifications OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.18 | |||
| es1NotificationPrefix OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.18.0 | |||
| es1Compliance OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.19 | |||
| es1ComplianceGroups OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.19.1 | |||
| es1DCSystems OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20 | |||
| es1dc1 OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1 | |||
| es1dc1GlobalStatus OBJECT-TYPE A textual string (alarms, normal or unknown) containing the status of the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.1 | DisplayString (SIZE(0..255)) | read-only | current |
| es1dc1GlobalAlarmSeverityType OBJECT-TYPE The alarm severity type (critical, major, minor, warning, none, disabled) of the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.2 | DisplayString | read-only | current |
| es1dc1GlobalAlarmSeverityLevel OBJECT-TYPE The alarm severity level (0-9) of the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.3 | Integer32 | read-only | current |
| es1dc1GlobalAlarmSeverityTypeInt OBJECT-TYPE The alarm severity type as integer (critical=4, major=3, minor=2, warning=1, none=0) of the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.4 | Integer32 | read-only | current |
| es1dc1Description OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10 | |||
| es1dc1DescriptionNumber OBJECT-TYPE The number of entries in the DC System Description table | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.1 | Integer32 | read-only | current |
| es1dc1DescriptionTable OBJECT-TYPE The Description table of the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2 | not-accessible | current | |
| es1dc1DescriptionEntry OBJECT-TYPE A Description entry | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1 | not-accessible | current | |
| es1dc1DescriptionIndex OBJECT-TYPE Description Index | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.1 | Unsigned32 | not-accessible | current |
| es1dc1DescriptionName OBJECT-TYPE Description Name | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.2 | DisplayString | read-only | current |
| es1dc1DescriptionValue OBJECT-TYPE Description Value | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.3 | DisplayString | read-create | current |
| es1dc1DescriptionEntryStatus OBJECT-TYPE The status of this table entry | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.4 | RowStatus | read-create | current |
| es1dc1DescriptionList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3 | |||
| es1dc1DescDescriptionDescription OBJECT-TYPE A free text zone to write a system description | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.1 | DisplayString | read-write | current |
| es1dc1DescDescriptionReference OBJECT-TYPE A free text zone to write the customer reference of the system | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.2 | DisplayString | read-write | current |
| es1dc1DescDescriptionProductName OBJECT-TYPE The product name of the DC system monitoring | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.11 | DisplayString | read-only | current |
| es1dc1DescDescriptionHardwareReference OBJECT-TYPE The hardware reference of the DC system monitoring | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.12 | DisplayString | read-only | current |
| es1dc1DescDescriptionSoftwareReference OBJECT-TYPE The software reference of the DC system monitoring | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.14 | DisplayString | read-only | current |
| es1dc1DescDescriptionSerialNumber OBJECT-TYPE The serial number of the DC system monitoring | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.16 | DisplayString | read-only | current |
| es1dc1DescDescriptionManufacturingDate OBJECT-TYPE The production date of the DC system monitoring | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.18 | DisplayString | read-only | current |
| es1dc1DescDescriptionDistributionModuleProductName OBJECT-TYPE The product name of the Electronic Distribution/LVD Module | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.31 | DisplayString | read-only | current |
| es1dc1DescDescriptionDistributionModuleHardwareReference OBJECT-TYPE The hardware reference of the Electronic Distribution/LVD Module | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.32 | DisplayString | read-only | current |
| es1dc1DescDescriptionDistributionModuleSoftwareReference OBJECT-TYPE The software reference of the Electronic Distribution/LVD Module | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.34 | DisplayString | read-only | current |
| es1dc1DescDescriptionDistributionModuleSerialNumber OBJECT-TYPE The serial number of the Electronic Distribution/LVD Module | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.36 | DisplayString | read-only | current |
| es1dc1DescDescriptionDistributionModuleManufacturingDate OBJECT-TYPE The manufacturing date of the Electronic Distribution/LVD Module | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.38 | DisplayString | read-only | current |
| es1dc1Alarm OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11 | |||
| es1dc1AlarmNumber OBJECT-TYPE The number of entries in the DC System Alarm table | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.1 | Integer32 | read-only | current |
| es1dc1AlarmTable OBJECT-TYPE The table of Alarm entries | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2 | not-accessible | current | |
| es1dc1AlarmEntry OBJECT-TYPE An alarm entry | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1 | not-accessible | current | |
| es1dc1AlarmIndex OBJECT-TYPE Alarm Index | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.1 | Unsigned32 | not-accessible | current |
| es1dc1AlarmName OBJECT-TYPE Alarm Name | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.2 | DisplayString | read-only | current |
| es1dc1AlarmActive OBJECT-TYPE Is the Alarm active ? 'true' for active, 'false' for not-active | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.3 | DisplayString | read-only | current |
| es1dc1AlarmSeverityType OBJECT-TYPE The alarm severity type (major, minor, warning, none, disabled) of this alarm entry | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.4 | DisplayString | read-write | current |
| es1dc1AlarmSeverityLevel OBJECT-TYPE The alarm severity level (0-9) of this alarm entry | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.5 | DisplayString | read-write | current |
| es1dc1AlarmStartTime OBJECT-TYPE The last start time of this alarm entry (null if never active) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.6 | DisplayString | read-only | current |
| es1dc1AlarmStopTime OBJECT-TYPE The last stop time of this alarm entry (null if alarm active) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.7 | DisplayString | read-only | current |
| es1dc1AlarmEntryStatus OBJECT-TYPE The status of this table entry - not used, only for MIB compliance | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.8 | RowStatus | read-create | current |
| es1dc1AlarmSummary OBJECT-TYPE Summary bit vector with all the alarms state of the DC System. A '1' means alarm active, '0' means not active. Unimplemented alarms are always '0'. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.3 | Bits {dCBusDCBusExtraLow(0), dCBusDCBusLow(1), dCBusDCBusHigh(2), dCBusDCBusExtraHigh(3), dCBusDCBusVoltageSenseFail(4), aCBusMainsFail(5), aCBusMainsPartialFail(6), aCBusMainsLow(7), rectifiersOneRectifierFail(9), rectifiersMoreThanOneRectifierFail(10), rectifiersMissingRectifiers(11), batBatLastTestFailed(12), batBatOnDischarge(13), lVDBatLVDRelOpen(16), batBatTempTooHigh(17), batBatTempTooLow(18), batBatTempSensorFail(19), sensorsAmbientTempTooHigh(20), sensorsAmbientTempTooLow(21), sensorsAmbientTempSensorFail(22), digInputsDistributionBreakerOpen(24), digInputsBatBreakerOpen(25), digInputsDigInput1(26), digInputsDigInput2(27), digInputsDigInput3(28), digInputsDigInput4(29)} | read-only | current |
| es1dc1Event OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12 | |||
| es1dc1EventNumber OBJECT-TYPE The number of entries in the Event Table related to the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.1 | Integer32 | read-only | current |
| es1dc1EventTable OBJECT-TYPE The Event table related to the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2 | not-accessible | current | |
| es1dc1EventEntry OBJECT-TYPE . | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1 | not-accessible | current | |
| es1dc1EventIndex OBJECT-TYPE Event Index | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.1 | Unsigned32 | not-accessible | current |
| es1dc1EventId OBJECT-TYPE Event Index | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.2 | Unsigned32 | read-only | current |
| es1dc1EventName OBJECT-TYPE Event Name | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.3 | DisplayString | read-only | current |
| es1dc1EventDateTime OBJECT-TYPE The date and time of the event | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.4 | DisplayString | read-only | current |
| es1dc1EventSeverityType OBJECT-TYPE The event severity type ('major', 'minor', 'warning' or 'none') | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.5 | DisplayString | read-only | current |
| es1dc1EventSeverityLevel OBJECT-TYPE The event severity level (0-9) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.6 | DisplayString | read-only | current |
| es1dc1EventEntryStatus OBJECT-TYPE The status of this table entry | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.7 | RowStatus | read-create | current |
| es1dc1Data OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13 | |||
| es1dc1DataNumber OBJECT-TYPE The number of entries in the Data Table related to the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.1 | Integer32 | read-only | current |
| es1dc1DataTable OBJECT-TYPE The table of Data entries | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2 | not-accessible | current | |
| es1dc1DataEntry OBJECT-TYPE A data entry | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1 | not-accessible | current | |
| es1dc1DataIndex OBJECT-TYPE The data index | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.1 | Unsigned32 | not-accessible | current |
| es1dc1DataName OBJECT-TYPE The data name | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.2 | DisplayString | read-only | current |
| es1dc1DataValue OBJECT-TYPE The data value | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.3 | DisplayString | read-only | current |
| es1dc1DataEntryStatus OBJECT-TYPE The status of this table entry - not used, only present for compliance | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.4 | RowStatus | read-create | current |
| es1dc1DataList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3 | |||
| es1dc1DataSystemDCMode OBJECT-TYPE The DC system can have 5 values: 'Float'(0), 'Equalize'(1), 'Battery Test'(2), 'Ac Failure'(3) or 'Safe'(5) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.1 | Integer32 | read-only | current |
| es1dc1DataSystemPreviousDCMode OBJECT-TYPE The previous value of the DC Mode : 'Float'(0), 'Equalize'(1), 'Battery Test'(2), 'Ac Failure'(3) or 'Safe'(5) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.2 | Integer32 | read-only | current |
| es1dc1DataSystemNiMHChargeMode OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.5 | Integer32 | read-only | current |
| es1dc1DataDCBusBusVoltage OBJECT-TYPE The DC bus voltage in volt. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.11 | Integer32 | read-only | current |
| es1dc1DataSystemRatioDeliveredOnAvailablePower OBJECT-TYPE This is the ratio of the delivered power divided by the installed power, in %. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.12 | Integer32 | read-only | current |
| es1dc1DataACBusMinutesSinceLastACFailBegin OBJECT-TYPE The number of minute since the last AC Failure begin | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.13 | Integer32 | read-only | current |
| es1dc1DataACBusMinutesSinceLastACFailEnd OBJECT-TYPE The number of minute since the last AC Failure end | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.14 | Integer32 | read-only | current |
| es1dc1DataRectifiersRectifiersOutPower OBJECT-TYPE The sum of the delivered rectifier power | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.21 | Integer32 | read-only | current |
| es1dc1DataRectifiersRectifiersOutCurrent OBJECT-TYPE The sum of the delivered rectifier current | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.22 | Integer32 | read-only | current |
| es1dc1DataRectifiersRectifiersOutPowerMax OBJECT-TYPE The sum of the deliverable rectifier power | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.23 | Integer32 | read-only | current |
| es1dc1DataRectifiersRectifiersOutCurrentMax OBJECT-TYPE The sum of the deliverable rectifier current | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.24 | Integer32 | read-only | current |
| es1dc1DataRectifiersNumberOfRectifierMax OBJECT-TYPE The maximum possible number of rectifier in this dc system | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.31 | Integer32 | read-only | current |
| es1dc1DataRectifiersNumberOfPresentRectifier OBJECT-TYPE The actual number of present rectifier in this dc system | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.32 | Integer32 | read-only | current |
| es1dc1DataRectifiersNumberOfAbsentRectifier OBJECT-TYPE The actual number of absent rectifier in this dc system | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.33 | Integer32 | read-only | current |
| es1dc1DataRectifiersNumberOfActiveRectifier OBJECT-TYPE The actual number of active rectifier in this dc system. An active rectifier is a rectifier which is present, DC OK, AC OK and not in remote off. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.34 | Integer32 | read-only | current |
| es1dc1DataRectifiersNumberOfACFailRectifier OBJECT-TYPE The actual number or rectifier in AC Failure. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.35 | Integer32 | read-only | current |
| es1dc1DataRectifiersNumberOfDCFailRectifier OBJECT-TYPE The actual number or rectifier with DC Failure. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.36 | Integer32 | read-only | current |
| es1dc1DataRectifiersNumberOfRemoteOffRectifier OBJECT-TYPE The actual number or rectifier in remote off. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.37 | Integer32 | read-only | current |
| es1dc1DataRectifiersNumberOfOverTempRectifier OBJECT-TYPE The actual number or rectifier in Over Temperature. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.38 | Integer32 | read-only | current |
| es1dc1DataLoadLoadPower OBJECT-TYPE Estimation of the load power consumption | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.51 | Integer32 | read-only | current |
| es1dc1DataLoadLoadCurrent OBJECT-TYPE Estimation of the load current consumption | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.52 | Integer32 | read-only | current |
| es1dc1DataBatBatInputCurrent OBJECT-TYPE Measurement of the battery input current. A negative value means that the battery is discharging | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.61 | Integer32 | read-only | current |
| es1dc1DataBatBatInputPower OBJECT-TYPE Measurement of the battery input power. A negative value means that the battery is discharging | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.62 | Integer32 | read-only | current |
| es1dc1DataBatBatTemp OBJECT-TYPE The battery temperature | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.71 | Integer32 | read-only | current |
| es1dc1DataBatBatTestState OBJECT-TYPE This is about the result of the last battery test. 10 values are possible : 'Never Tested'(0), 'Success'(1), 'On Going'(2), 'Failed: Timeout'(3), 'Failed: Vbus Too Low'(4), 'Failed: Load Too Low'(5), 'Failed: Ac Failure'(6), 'Failed: Canceled' (7), 'Failed: Lvd Opened'(8), 'Failed: No Battery'(9) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.72 | Integer32 | read-only | current |
| es1dc1DataBatLastBatTestDischargedCapacityRatio OBJECT-TYPE This is the battery capacity, in percent, discharged during the last battery test. This value is updated at the end of the battery test. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.73 | Integer32 | read-only | current |
| es1dc1DataBatLastBatTestDischargedCapacity OBJECT-TYPE This is the battery capacity, in ampere hour, discharged during the last battery test. This value is updated at the end of the battery test. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.74 | Integer32 | read-only | current |
| es1dc1DataBatLastBatTestFinalVoltage OBJECT-TYPE This is the bus voltage at the end of the last battery test. This value is updated at the end of the battery test. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.75 | Integer32 | read-only | current |
| es1dc1DataBatBatTestDuration OBJECT-TYPE The duration of the last battery test. This value is updated at the end of the battery test. This value can't be higher than 1440 minutes (24 hours). | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.76 | Integer32 | read-only | current |
| es1dc1DataBatPreviousBatTestDischargedCapacityRatio OBJECT-TYPE This is the battery capacity, in percent, discharged during the previous battery test. This value is shifted at the end of the battery test. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.77 | Integer32 | read-only | current |
| es1dc1DataBatPreviousBatTestDischargedCapacity OBJECT-TYPE This is the battery capacity, in ampere hour, discharged during the previous battery test. This value is shifted at the end of the battery test. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.78 | Integer32 | read-only | current |
| es1dc1DataBatPreviousBatTestFinalVoltage OBJECT-TYPE This is the bus voltage at the end of the previous battery test. This value is shifted at the end of the battery test. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.79 | Integer32 | read-only | current |
| es1dc1DataBatPreviousBatTestDuration OBJECT-TYPE The duration of the previous battery test. This value is shifted at the end of the battery test. This value can't be higher than 1440 minutes (24 hours). | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.80 | Integer32 | read-only | current |
| es1dc1DataBatPreviousBatTestState OBJECT-TYPE The result of the previous battery test - 10 values are possible: 'Never Tested'(0), 'Success'(1), 'On Going'(2), 'Failed: Timeout'(3), 'Failed: Vbus Too Low'(4), 'Failed: Load Too Low'(5), 'Failed: Ac Failure'(6), 'Failed: Canceled', 'Failed: Lvd Opened'(8), 'Failed: No Battery'(9) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.81 | Integer32 | read-only | current |
| es1dc1DataBatMinutesSinceLastTestBat OBJECT-TYPE The number of minute since the end of last battery test | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.82 | Integer32 | read-only | current |
| es1dc1DataBatNextScheduledBatTest OBJECT-TYPE The date and time of the next time the scheduled battery test will run | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.84 | Integer32 | read-only | current |
| es1dc1DataBatBatChargeCapacity OBJECT-TYPE The battery charge capacity, calculated by integration of the current. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.91 | Integer32 | read-only | current |
| es1dc1DataBatCalculatedAutonomy OBJECT-TYPE Calculation of the remaining autonomy. This value can change following the load of your system and the maximal depth of dicharge configuration (CF39). | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.92 | Integer32 | read-only | current |
| es1dc1DataBatBatCurrentIntegration OBJECT-TYPE Actual value of the integration of the current, in Ampere * hour | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.94 | Integer32 | read-only | current |
| es1dc1DataLVDLVDState OBJECT-TYPE Actual state of the LVD | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.101 | Integer32 | read-only | current |
| es1dc1DataRelsRel1State OBJECT-TYPE Actual state of the Relay 1 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.111 | Integer32 | read-only | current |
| es1dc1DataRelsRel2State OBJECT-TYPE Actual state of the Relay 2 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.112 | Integer32 | read-only | current |
| es1dc1DataRelsRel3State OBJECT-TYPE Actual state of the Relay 3 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.113 | Integer32 | read-only | current |
| es1dc1DataRelsRel4State OBJECT-TYPE Actual state of the Relay 3 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.114 | Integer32 | read-only | current |
| es1dc1DataSmartEnergyEfficiencyOptimizedNumberOfRectifier OBJECT-TYPE The optimal number of ON rectifier for Efficiency Optimization | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.121 | Integer32 | read-only | current |
| es1dc1DataSmartEnergySystemLossWithoutOptimisation OBJECT-TYPE Estimation of the losses without optimisation | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.122 | Integer32 | read-only | current |
| es1dc1DataSmartEnergySystemLossWithOptimisation OBJECT-TYPE Estimation of the losses with optimisation | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.123 | Integer32 | read-only | current |
| es1dc1DataSmartEnergyRectifierModelUsedForCalculation OBJECT-TYPE The rectifier model used | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.124 | Integer32 | read-only | current |
| es1dc1DataSmartEnergySmartEnergySavings OBJECT-TYPE Estimation of the losses with optimisation | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.125 | Integer32 | read-only | current |
| es1dc1DataSensorsAmbientTemp OBJECT-TYPE The ambiant temperature (second temperature sense) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.151 | Integer32 | read-only | current |
| es1dc1DataSensorsPulseCounter4 OBJECT-TYPE The counter value of the digital input 4. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.204 | Integer32 | read-only | current |
| es1dc1Config OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15 | |||
| es1dc1ConfigNumber OBJECT-TYPE The number of entries in the Config table related to the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.1 | Integer32 | read-only | current |
| es1dc1ConfigTable OBJECT-TYPE The table of Config entries related to the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2 | not-accessible | current | |
| es1dc1ConfigEntry OBJECT-TYPE A Config entry | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1 | not-accessible | current | |
| es1dc1ConfigIndex OBJECT-TYPE The Config entry Index | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.1 | Unsigned32 | not-accessible | current |
| es1dc1ConfigName OBJECT-TYPE The Config entry name | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.2 | DisplayString | read-only | current |
| es1dc1ConfigValue OBJECT-TYPE The Config entry value | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.3 | DisplayString | read-write | current |
| es1dc1ConfigEntryStatus OBJECT-TYPE The status of this table entry - not used, only for compliance | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.4 | RowStatus | read-create | current |
| es1dc1ConfigList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3 | |||
| es1dc1CfgDCBusDCBusFloatVoltageat25degC OBJECT-TYPE The floating dc bus voltage of the system at 25 Celsius degree | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.1 | DisplayString | read-write | current |
| es1dc1CfgDCBusDCBusVoltageExtraLow OBJECT-TYPE The bus voltage under which the alarm 'DC Bus Voltage Extra Low' is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.2 | DisplayString | read-write | current |
| es1dc1CfgDCBusDCBusVoltageExtraLowHysteresis OBJECT-TYPE The voltage hysteresis on the alarm 'DC Bus Voltage Extra Low'. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.3 | DisplayString | read-write | current |
| es1dc1CfgDCBusDCBusVoltageLow OBJECT-TYPE The bus voltage under which the alarm 'DC Bus Voltage Low' is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.4 | DisplayString | read-write | current |
| es1dc1CfgDCBusDCBusVoltageLowHysteresis OBJECT-TYPE The voltage hysteresis on the alarm 'DC Bus Voltage Low | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.5 | DisplayString | read-write | current |
| es1dc1CfgDCBusDCBusVoltageHigh OBJECT-TYPE The bus voltage over which the alarm 'DC Bus Voltage High' is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.6 | DisplayString | read-write | current |
| es1dc1CfgDCBusDCBusVoltageHighHysteresis OBJECT-TYPE The voltage hysteresis on the alarm 'DC Bus Voltage High | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.7 | DisplayString | read-write | current |
| es1dc1CfgDCBusDCBusVoltageExtraHigh OBJECT-TYPE The bus voltage over which the alarm 'DC Bus Voltage Extra High' is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.8 | DisplayString | read-write | current |
| es1dc1CfgDCBusDCBusVoltageExtraHighHysteresis OBJECT-TYPE The voltage hysteresis on the alarm 'DC Bus Voltage Extra High | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.9 | DisplayString | read-write | current |
| es1dc1CfgLVDLVDDisconnectVoltage OBJECT-TYPE The dc bus voltage under which the battery must be disconnected of the bus. This allows preserving the battery life. The load will be unpowered. This value has to be lower than the Battery test end voltage (CF70) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.10 | DisplayString | read-write | current |
| es1dc1CfgLVDLVDDisconnectDelay OBJECT-TYPE The delay in second before disconnecting the battery if the dc bus voltage is under the configured disconnected voltage. This avoids disconnection during a low bus transient. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.11 | DisplayString | read-write | current |
| es1dc1CfgBatTempCompensationSlope OBJECT-TYPE The slope of the battery temperature compensation in mv/degree. For a 48V system, -72mV/degree is often used. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.21 | DisplayString | read-write | current |
| es1dc1CfgBatMaxPosTempCompensation OBJECT-TYPE The maximal allowed positive compensation. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.22 | DisplayString | read-write | current |
| es1dc1CfgBatMaxNegTempCompensation OBJECT-TYPE The maximal allowed negative compensation. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.23 | DisplayString | read-write | current |
| es1dc1CfgRectifiersMinimalNumberOfPresentRectifiers OBJECT-TYPE The minimal number of rectifier which must be present. If there is less present rectifiers, the alarm 'Missing Rectifiers' is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.25 | DisplayString | read-write | current |
| es1dc1CfgRectifiersRectifierModel OBJECT-TYPE The rectifier model | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.26 | DisplayString | read-write | current |
| es1dc1CfgRectifiersForcedRemoteOffRectifers OBJECT-TYPE A list of rectifier which are forced in remote off. The id of the rectifier must be coma separated. Ex: 1,3 will maintain rectifier 1 and 3 off. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.27 | DisplayString | read-write | current |
| es1dc1CfgBatBatChargeCurrentLimit OBJECT-TYPE The maximal battery current when the battery is charging. The monitoring regulates the bus voltage in order to satisfy this condition. This parameter is often equal to the nominal battery capacity divided by 10. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.31 | DisplayString | read-write | current |
| es1dc1CfgBatBatStringCapacity OBJECT-TYPE The battery capacity in Ah. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.32 | DisplayString | read-write | current |
| es1dc1CfgBatBatTempLow OBJECT-TYPE The temperature under which the alarm 'Battery Temperature Too Low' must be set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.33 | DisplayString | read-write | current |
| es1dc1CfgBatBatTempHigh OBJECT-TYPE The temperature over which the alarm 'Battery Temperature Too High' must be set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.34 | DisplayString | read-write | current |
| es1dc1CfgBatBatTempHysteresis OBJECT-TYPE The hysteresis on the 'Battery Temperature Too High' and 'Battery Temperature Too Low' alarms. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.35 | DisplayString | read-write | current |
| es1dc1CfgBatMinimalCurrentForDischargingAlarm OBJECT-TYPE The minimal discharging current to set the 'Battery On Discharge' alarm. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.36 | DisplayString | read-write | current |
| es1dc1CfgBatCurrentHysteresisForDischargingAlarm OBJECT-TYPE The hysteresis on the 'Battery On Discharge' alarm. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.37 | DisplayString | read-write | current |
| es1dc1CfgBatPeukertNumber OBJECT-TYPE The Peukert number relates to the internal resistance of a battery and provides an indication of the excpected capacity. The ideal number is 1. This value can be calculated with the formula: (ln(t2)-ln(t1))/(ln(i1)-ln(i2)) where tx is the autonomy in hours at a constant discharge current of ix Amps. Often, we use t1 = 1h and t2 = 10h | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.38 | DisplayString | read-write | current |
| es1dc1CfgBatMaxDepthOfDischargeforAutonomyEstimation OBJECT-TYPE It is generally recommended to discharge maximum 60% of the battery capacity to enhance battery lifetime. By default, 100% is used for autonomy calculation. This parameter can also be used to take into account the age of the battery | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.39 | DisplayString | read-write | current |
| es1dc1CfgBatBoostAutomatic OBJECT-TYPE The boost mode must be automatically after the fact that during a mains failure, the bus voltage went under the configured 'Boost Activation Low Voltage'. This allows charging the battery faster. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.51 | DisplayString | read-write | current |
| es1dc1CfgBatBoostActivationLowVoltage OBJECT-TYPE The voltage under which the boost mode can be activated. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.52 | DisplayString | read-write | current |
| es1dc1CfgBatBoostTerminationVoltage OBJECT-TYPE The voltage over which the system must go back to floating mode. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.53 | DisplayString | read-write | current |
| es1dc1CfgBatBoostTerminationCurrent OBJECT-TYPE The battery charging current under which the system must go back to floating mode. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.54 | DisplayString | read-write | current |
| es1dc1CfgBatBoostTerminationTime OBJECT-TYPE The time in minute after which the system must go back in floating mode. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.55 | DisplayString | read-write | current |
| es1dc1CfgBatBatTestType OBJECT-TYPE Type of the battery test: <br> Capacity based: The battery must give the requested capacity before falling lower than a value <br>Time Based: The battery must sustain a defined load during a defined time. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.69 | DisplayString | read-write | current |
| es1dc1CfgBatBatTestEndVoltage OBJECT-TYPE The voltage at which any battery test must be stopped. This value has to be higher than the LVD Disconnect voltage (CF10) | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.70 | DisplayString | read-write | current |
| es1dc1CfgBatBatTestDischargeRatio OBJECT-TYPE The ratio of the battery capacity to discharge. If 30 is set, 30% of the battery will be discharged during the test | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.71 | DisplayString | read-write | current |
| es1dc1CfgBatBatTestInterval OBJECT-TYPE The number of days between two automatically started battery test. If this parameter is set to 0, the battery test is not started automatically. The user can remotely or locally start or force this test. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.72 | DisplayString | read-write | current |
| es1dc1CfgBatBatTestDischargeCurrent OBJECT-TYPE The current at which the battery must be discharged during a battery test. The monitoring regulates the bus voltage in order to satisfy this condition. The load current must be of course higher than this parameter. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.73 | DisplayString | read-write | current |
| es1dc1CfgBatBatTestMinimalDischargeCurrent OBJECT-TYPE The battery current under which the battery test must be stopped because the load is too low. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.74 | DisplayString | read-write | current |
| es1dc1CfgBatBatTestDuration OBJECT-TYPE The timeout in minute after which the battery test must be stopped. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.75 | DisplayString | read-write | current |
| es1dc1CfgBatBatTestRequMinutesWithoutMainsFail OBJECT-TYPE The minimal time in minute without mains failure in order to allow a battery start. This parameter is not taken into account when the battery test is forced. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.76 | DisplayString | read-write | current |
| es1dc1CfgBatBatTestSchedulerCronRule OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.77 | DisplayString | read-write | current |
| es1dc1CfgSmartEnergySmartEnergyBooleanCond OBJECT-TYPE This is the boolean condition which allows or not to automatically optimize the number of rectifier in remote off. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.83 | DisplayString | read-write | current |
| es1dc1CfgLVDBatLVDNodeId OBJECT-TYPE This is a list of the node id of the Smart Electronic LVDs, coma separated | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.86 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput1Name OBJECT-TYPE The name of the digital input 1 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.91 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput1NormallyClosed OBJECT-TYPE True/False value defining if the digital input 1 is normally closed. If this digital input is not in this default state, the related alarm is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.92 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput2Name OBJECT-TYPE The name of the digital input 2 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.93 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput2NormallyClosed OBJECT-TYPE True/False value defining if the digital input 2 is normally closed. If this digital input is not in this default state, the related alarm is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.94 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput3Name OBJECT-TYPE The name of the digital input 3 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.95 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput3NormallyClosed OBJECT-TYPE True/False value defining if the digital input 3 is normally closed. If this digital input is not in this default state, the related alarm is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.96 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput4Name OBJECT-TYPE The name of the digital input 4 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.97 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput4NormallyClosed OBJECT-TYPE True/False value defining if the digital input 4 is normally closed. If this digital input is not in this default state, the related alarm is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.98 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput5Name OBJECT-TYPE The name of the digital input 5 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.99 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput5NormallyClosed OBJECT-TYPE True/False value defining if the digital input 5 is normally closed. If this digital input is not in this default state, the related alarm is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.100 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput6Name OBJECT-TYPE The name of the digital input 6 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.101 | DisplayString | read-write | current |
| es1dc1CfgDigInputsDigInput6NormallyClosed OBJECT-TYPE True/False value defining if the digital input 6 is normally closed. If this digital input is not in this default state, the related alarm is set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.102 | DisplayString | read-write | current |
| es1dc1CfgRelsDryAlarm1AlternativeBooleanCond OBJECT-TYPE Another Boolean condition to activate the dry alarm relay 1. The way to define boolean condition is detailed in the PLC chapter. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.111 | DisplayString | read-write | current |
| es1dc1CfgRelsDryAlarm2AlternativeBooleanCond OBJECT-TYPE Another Boolean condition to activate the dry alarm relay 2. The way to define boolean condition is detailed in the PLC chapter. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.112 | DisplayString | read-write | current |
| es1dc1CfgRelsDryAlarm3AlternativeBooleanCond OBJECT-TYPE Another Boolean condition to activate the dry alarm relay 3. The way to define boolean condition is detailed in the PLC chapter. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.113 | DisplayString | read-write | current |
| es1dc1CfgRelsDryAlarm4AlternativeBooleanCond OBJECT-TYPE Another Boolean condition to activate the dry alarm relay 4. The way to define boolean condition is detailed in the PLC chapter. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.114 | DisplayString | read-write | current |
| es1dc1CfgSensorsAmbientTempLow OBJECT-TYPE The temperature under which the alarm 'Ambiant Temperature Too Low' must be set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.131 | DisplayString | read-write | current |
| es1dc1CfgSensorsAmbientTempHigh OBJECT-TYPE The temperature under which the alarm 'Ambiant Temperature Too Low' must be set. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.132 | DisplayString | read-write | current |
| es1dc1CfgSensorsAmbientTempHysteresis OBJECT-TYPE The hysteresis on the 'Battery Temperature Too High' and 'Battery Temperature Too Low' alarms. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.133 | DisplayString | read-write | current |
| es1dc1CfgGenericReadAccessUserNumbers OBJECT-TYPE The list of the user numbers which have read access to this equipment. The user numbers are coma separated. The accepted user id are 1,2,3,4 and 5. Ex: 1,3,4 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.521 | DisplayString | read-write | current |
| es1dc1CfgGenericWriteAccessUserNumbers OBJECT-TYPE The list of the user numbers which have write access to this equipment. This means that these users can modify the configuration element, the alarm settings and use the control elements. The user numbers are coma separated. The accepted user ids are 1,2,3,4 and 5. Ex: 1,3,4 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.522 | DisplayString | read-write | current |
| es1dc1CfgGenericEventTableLength OBJECT-TYPE The maximum length of the table. The value must be comprised between 10 and 4000 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.601 | DisplayString | read-write | current |
| es1dc1CfgGenericEventTableLengthByRectifier OBJECT-TYPE The maximum length of the table. The value must be comprised between 10 and 4000 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.602 | DisplayString | read-write | current |
| es1dc1CfgPLCNumberOfPLCData OBJECT-TYPE The number of PLC data. Every equipment can manage up to 30 user programmable data. Data elements are automatically added in the data table. Configuration parameters are added to set the PLC Data Name and the PLC Data Mathematical calculation. In order to use these functionalities, you need a license with the 'PLC' module | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.901 | DisplayString | read-write | current |
| es1dc1CfgPLCNumberOfPLCAlarm OBJECT-TYPE The number of PLC alarm. Every equipment can manage up to 30 user programmable alarms. Alarm elements are automatically added in the alarm table. The alarm parameters are added to set the PLC Alarm Name and the PLC Alarm Boolean condition. In order to use these functionalities, you need a licence with the 'PLC' module | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.902 | DisplayString | read-write | current |
| es1dc1Control OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16 | |||
| es1dc1ControlNumber OBJECT-TYPE The number of entries in the Control table related to the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.1 | Integer32 | read-only | current |
| es1dc1ControlTable OBJECT-TYPE The table of Control entries related to the DC System | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2 | not-accessible | current | |
| es1dc1ControlEntry OBJECT-TYPE A Control entry | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1 | not-accessible | current | |
| es1dc1ControlIndex OBJECT-TYPE The Control entry Index | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.1 | Unsigned32 | not-accessible | current |
| es1dc1ControlName OBJECT-TYPE The Control entry name | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.2 | DisplayString | read-only | current |
| es1dc1ControlValue OBJECT-TYPE The Control entry value | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.3 | DisplayString | read-write | current |
| es1dc1ControlEntryStatus OBJECT-TYPE The status of this table entry - not used, only for compliance | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.4 | RowStatus | read-create | current |
| es1dc1ControlList OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3 | |||
| es1dc1CtrlSystemBackToFloat OBJECT-TYPE The dc system must go back in floating mode. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.1 | DisplayString | read-write | current |
| es1dc1CtrlSystemStartBatTest OBJECT-TYPE The dc system must start a battery test. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.2 | DisplayString | read-write | current |
| es1dc1CtrlSystemForceBatTest OBJECT-TYPE The dc system must force a battery test. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.3 | DisplayString | read-write | current |
| es1dc1CtrlSystemStartBoostMode OBJECT-TYPE The dc system must go in boost mode. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.4 | DisplayString | read-write | current |
| es1dc1CtrlLVDOpenTheLVD OBJECT-TYPE Try to open the LVD. It could not work if the LVD is electronic, and the request will be canceled after 15 sec. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.11 | DisplayString | read-write | current |
| es1dc1CtrlLVDCloseTheLVD OBJECT-TYPE The LVD must be closed | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.12 | DisplayString | read-write | current |
| es1dc1CtrlBatCorrectBatCurrentOffset OBJECT-TYPE NA | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.21 | DisplayString | read-write | current |
| es1dc1CtrlBatResetLastBatTestState OBJECT-TYPE Reset the state of the last battery test. If an alarm 'Battery Last Test Failed' is set, the alarm will be cleared. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.41 | DisplayString | read-write | current |
| es1dc1CtrlSaveSaveConfInMCU OBJECT-TYPE Save configuration parameters in the MCU microcontroller. If comp@s is not present, the system will be correctly managed. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.51 | DisplayString | read-write | current |
| es1dc1CtrlAdvancedSetMCUSpecificConfId OBJECT-TYPE This control allows to reconfigure the MCU to support specific hardware configuration, with embedded distribution for example | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.55 | DisplayString | read-write | current |
| es1dc1CtrlDigInputsSetDigInput4CounterValue OBJECT-TYPE Set Counter Value | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.61 | DisplayString | read-write | current |
| es1dc1CtrlRelsInvertRel1StateForXSeconds OBJECT-TYPE Generate Pulse on relay 1 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.111 | DisplayString | read-write | current |
| es1dc1CtrlRelsInvertRel2StateForXSeconds OBJECT-TYPE Generate Pulse on relay 2 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.112 | DisplayString | read-write | current |
| es1dc1CtrlRelsInvertRel3StateForXSeconds OBJECT-TYPE Generate Pulse on relay 3 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.113 | DisplayString | read-write | current |
| es1dc1CtrlRelsInvertRel4StateForXSeconds OBJECT-TYPE Generate Pulse on relay 4 | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.114 | DisplayString | read-write | current |
| es1dc1CtrlGenericClearMyEvents OBJECT-TYPE By writing '1' to this control element, all the events of this equipment will be cleared. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.501 | DisplayString | read-write | current |
| es1dc1CtrlGenericClearAllEvents OBJECT-TYPE By writing '1' to this control element, all the events of this equipment and all the events of all the sub-equipments will be cleared. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.502 | DisplayString | read-write | current |
| es1dc1CtrlGenericAddEvent OBJECT-TYPE This control element adds an event of severity none. The event name is the text written to this control element | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.511 | DisplayString | read-write | current |
| es1dc1CtrlGenericAddMajorEvent OBJECT-TYPE This control element adds an event of severity major. The event name is the text written to this control element | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.512 | DisplayString | read-write | current |
| es1dc1CtrlGenericResetDefaultNamesAndGroups OBJECT-TYPE This control element resets all the element Names, Groups and Subgroups to default values for this equipment | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.521 | DisplayString | read-write | current |
| es1dc1CtrlGenericResetDefaultNamesAndGroupsRecursive OBJECT-TYPE This control element resets all the element Names, Groups and Subgroups to default values for this equipment and all sub equipments | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.522 | DisplayString | read-write | current |
| es1dc1Notifications OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.18 | |||
| es1dc1NotificationPrefix OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.18.0 | |||
| es1dc1Compliance OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19 | |||
| es1dc1ComplianceGroups OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.1 | |||
| es1InverterSystems OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.25 | |||
| es1RemotePowerFeedingSystems OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.20.1.28 | |||
| extensions OBJECT-IDENTITY | 1.3.6.1.4.1.26854.3.2.1.21 |
Notifications
| Name | OID | Status |
|---|---|---|
| siteV1NotificationOfEvent NOTIFICATION-TYPE Notification generated when a new event appears | 1.3.6.1.4.1.26854.3.2.1.18.0.1 | current |
| es1NotificationOfEvent NOTIFICATION-TYPE Notification generated when a new event appears | 1.3.6.1.4.1.26854.3.2.1.20.1.18.0.1 | current |
| es1dc1NotificationOfEvent NOTIFICATION-TYPE Notification generated when a new event appears | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.18.0.1 | current |
Conformance
| Name | OID | Status |
|---|---|---|
| siteV1GlobalGroup OBJECT-GROUP text | 1.3.6.1.4.1.26854.3.2.1.19.1.1 | current |
| siteV1NotificationGroup NOTIFICATION-GROUP text | 1.3.6.1.4.1.26854.3.2.1.19.1.2 | current |
| siteV1FullCompliance MODULE-COMPLIANCE The compliance statement for SNMPV2 entities which implement the SNMPV2 MIB. | 1.3.6.1.4.1.26854.3.2.1.19.2 | current |
| es1GlobalGroup OBJECT-GROUP text | 1.3.6.1.4.1.26854.3.2.1.20.1.19.1.1 | current |
| es1NotificationGroup NOTIFICATION-GROUP text | 1.3.6.1.4.1.26854.3.2.1.20.1.19.1.2 | current |
| es1FullCompliance MODULE-COMPLIANCE The compliance statement for SNMPV2 entities which implement the SNMPV2 MIB. | 1.3.6.1.4.1.26854.3.2.1.20.1.19.2 | current |
| es1dc1GlobalGroup OBJECT-GROUP text | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.1.1 | current |
| es1dc1NotificationGroup NOTIFICATION-GROUP text | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.1.2 | current |
| es1dc1FullCompliance MODULE-COMPLIANCE The compliance statement for SNMPV2 entities which implement the SNMPV2 MIB. | 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.2 | current |