RackMonitor-MIB
- Registered at
- 1.3.6.1.4.1.534.6.7.1.11.3.6.1.4.1.534.6.7.1.2
- Namespace
- eaton
- Source file
RackMonitor-MIB- Digest
sha256:697779da73d0df5ebe4d6d18d991f64f8f32ebc45c2e37a0259437e2e0447538
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
RackMonitor-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| powerware OBJECT-IDENTITY | 1.3.6.1.4.1.534 | |||
| product OBJECT-IDENTITY | 1.3.6.1.4.1.534.6 | |||
| dataCenter OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7 | |||
| environmentalMonitor OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1 | |||
| insObjects OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1 | |||
| rmIdent OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.1 | |||
| insIdentManufacturer OBJECT-TYPE The name of the RackMonitor manufacturer. | 1.3.6.1.4.1.534.6.7.1.1.1.1 | DisplayString (SIZE(0..31)) | read-only | mandatory |
| insIdentModel OBJECT-TYPE The RackMonitor Model designation. | 1.3.6.1.4.1.534.6.7.1.1.1.2 | DisplayString (SIZE(0..63)) | read-only | mandatory |
| insIdentAgentSoftwareVersion OBJECT-TYPE The RackMonitor software/firmware version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations. | 1.3.6.1.4.1.534.6.7.1.1.1.3 | DisplayString (SIZE(0..31)) | read-only | mandatory |
| insIdentName OBJECT-TYPE A string identifying the RackMonitor. This object should be set by the administrator. | 1.3.6.1.4.1.534.6.7.1.1.1.4 | DisplayString (SIZE(0..31)) | read-write | mandatory |
| rmConfig OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.2 | |||
| rmConfigMibVersion OBJECT-TYPE The version of MIB spec. | 1.3.6.1.4.1.534.6.7.1.1.2.1 | INTEGER | read-only | mandatory |
| rmConfigNetwork OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.2.2 | |||
| rmConfigIpAddress OBJECT-TYPE The ip address that NMS can identify the managed device | 1.3.6.1.4.1.534.6.7.1.1.2.2.1 | IpAddress | read-write | mandatory |
| rmConfigGateway OBJECT-TYPE The default gateway that allow device managed through routers | 1.3.6.1.4.1.534.6.7.1.1.2.2.2 | IpAddress | read-write | mandatory |
| rmConfigSubnetMask OBJECT-TYPE Internet address subnet mask | 1.3.6.1.4.1.534.6.7.1.1.2.2.3 | IpAddress | read-write | mandatory |
| rmConfigDateTime OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.2.3 | |||
| rmConfigDate OBJECT-TYPE The date in Environmental Rack Monitor, format is (dd/mm/yyyy) | 1.3.6.1.4.1.534.6.7.1.1.2.3.1 | DisplayString (SIZE(10)) | read-write | mandatory |
| rmConfigTime OBJECT-TYPE The time in Environmental Rack Monitor, format is (hh:mm:ss) | 1.3.6.1.4.1.534.6.7.1.1.2.3.2 | DisplayString (SIZE(8)) | read-write | mandatory |
| rmConfigTimeFromNtp OBJECT-TYPE Enable/disable update of the date and time from the NTP server. | 1.3.6.1.4.1.534.6.7.1.1.2.3.3 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigNtpIpAddress OBJECT-TYPE NTP IP address. | 1.3.6.1.4.1.534.6.7.1.1.2.3.4 | IpAddress | read-write | mandatory |
| rmConfigNtpTimeZone OBJECT-TYPE Enable/disable update of the date and time from the NTP server. | 1.3.6.1.4.1.534.6.7.1.1.2.3.5 | INTEGER {gMT-1200(1), gMT-1100(2), gMT-1000(3), gMT-0900(4), gMT-0800(5), gMT-0700(6), gMT-0600(7), gMT-0500(8), gMT-0400(9), gMT-0330(10), gMT-0300(11), gMT-0200(12), gMT-0100(13), gMT-0000(14), gMT0100(15), gMT0200(16), gMT0300(17), gMT0330(18), gMT0400(19), gMT0500(20), gMT0530(21), gMT0600(22), gMT0700(23), gMT0800(24), gMT0900(25), gMT1000(26), gMT1100(27), gMT1200(28)} | read-write | mandatory |
| rmConfigDayLightSaving OBJECT-TYPE Enable/disable daylight saving for NTP time, if enabled, the time obtained from the NTP will be set one hour in advance to reflect daylight saving status. | 1.3.6.1.4.1.534.6.7.1.1.2.3.6 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigLog OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.2.4 | |||
| rmConfigHistoryLogFrequency OBJECT-TYPE The frequency of the history log update. The value is in seconds | 1.3.6.1.4.1.534.6.7.1.1.2.4.1 | INTEGER (5..3600) | read-write | mandatory |
| rmConfigExtHistoryLogFrequency OBJECT-TYPE The frequency of the extended history log update. The value is in seconds | 1.3.6.1.4.1.534.6.7.1.1.2.4.2 | INTEGER (1..1440) | read-write | mandatory |
| rmConfigConfigurationLog OBJECT-TYPE Enable/Disable Environmental Rack Monitor parameters change logging. | 1.3.6.1.4.1.534.6.7.1.1.2.4.3 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigDhcpStatue OBJECT-TYPE Enable or Disable DHCP/BootP capability | 1.3.6.1.4.1.534.6.7.1.1.2.5 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigPingStatue OBJECT-TYPE Enable or Disable Ping Echo capability | 1.3.6.1.4.1.534.6.7.1.1.2.6 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigTftpStatue OBJECT-TYPE Enable or Disable TFTP network upgrade capability | 1.3.6.1.4.1.534.6.7.1.1.2.7 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigTelnet OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.2.8 | |||
| rmConfigTelnetStatue OBJECT-TYPE Enable or Disable telnet access | 1.3.6.1.4.1.534.6.7.1.1.2.8.1 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigTelnetPortNumber OBJECT-TYPE Setting the server port for telnet. | 1.3.6.1.4.1.534.6.7.1.1.2.8.2 | INTEGER (1..65535) | read-write | mandatory |
| rmConfigHttp OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.2.9 | |||
| rmConfigHttpStatue OBJECT-TYPE Enable or Disable HTTP access | 1.3.6.1.4.1.534.6.7.1.1.2.9.1 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigHttpPortNumber OBJECT-TYPE Setting the server port of HTTP. | 1.3.6.1.4.1.534.6.7.1.1.2.9.2 | INTEGER (1..65535) | read-write | mandatory |
| rmConfigHttpSecurity OBJECT-TYPE Enable/Disable HTTP access for read-only users | 1.3.6.1.4.1.534.6.7.1.1.2.9.3 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigSnmp OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.2.10 | |||
| rmConfigSnmpStatue OBJECT-TYPE Enable or Disable SNMP access | 1.3.6.1.4.1.534.6.7.1.1.2.10.1 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| rmConfigSnmpPortNumber OBJECT-TYPE Setting the server port for SNMP. | 1.3.6.1.4.1.534.6.7.1.1.2.10.2 | INTEGER (1..65535) | read-write | mandatory |
| rmConfigControl OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.2.11 | |||
| rmConfigResetToDefault OBJECT-TYPE Reset all parameters of Environmental Rack Monitor to default values | 1.3.6.1.4.1.534.6.7.1.1.2.11.1 | INTEGER {reset(1), nothing(2)} | read-write | mandatory |
| rmConfigRestart OBJECT-TYPE Restart rm | 1.3.6.1.4.1.534.6.7.1.1.2.11.2 | INTEGER {restart(1), nothing(2)} | read-write | mandatory |
| rmConfigTrap OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.2.12 | |||
| rmConfigTrapRetryCount OBJECT-TYPE The count of repeat traps to send to NMS before trap acknowledge received. | 1.3.6.1.4.1.534.6.7.1.1.2.12.1 | INTEGER | read-write | mandatory |
| rmConfigTrapRetryTime OBJECT-TYPE The time between retry traps sent to NMS. | 1.3.6.1.4.1.534.6.7.1.1.2.12.2 | INTEGER | read-write | mandatory |
| rmConfigTrapAckSignature OBJECT-TYPE The signature of trap acknowledge. | 1.3.6.1.4.1.534.6.7.1.1.2.12.3 | INTEGER | read-write | mandatory |
| rmConfigPollRate OBJECT-TYPE The frequency that the Rack Monitor will read from sensors (unit : second). | 1.3.6.1.4.1.534.6.7.1.1.2.13 | INTEGER (3..60) | read-write | mandatory |
| rmConfigTrapsReceiversTable OBJECT-TYPE A list of managers to send traps to. The number of entries is given by the value of rmConfigNumTrapReceivers | 1.3.6.1.4.1.534.6.7.1.1.2.14 | not-accessible | mandatory | |
| rmConfigTrapsReceiversEntry OBJECT-TYPE The managers to send traps to. | 1.3.6.1.4.1.534.6.7.1.1.2.14.1 | not-accessible | mandatory | |
| trapsIndex OBJECT-TYPE The index to a trap receiver entry. | 1.3.6.1.4.1.534.6.7.1.1.2.14.1.1 | INTEGER (1..2147483647) | read-only | mandatory |
| trapsReceiverAddr OBJECT-TYPE The IP address of the manager to send a trap to. | 1.3.6.1.4.1.534.6.7.1.1.2.14.1.2 | IpAddress | read-write | mandatory |
| receiverCommunityString OBJECT-TYPE The community name to use in the trap when sent to the manager. | 1.3.6.1.4.1.534.6.7.1.1.2.14.1.3 | DisplayString (SIZE(0..19)) | read-write | mandatory |
| receiverSeverityLevel OBJECT-TYPE The severity level of traps to be received by this manager. | 1.3.6.1.4.1.534.6.7.1.1.2.14.1.4 | INTEGER {informational(1), warning(2), severe(3)} | read-write | mandatory |
| receiverDescription OBJECT-TYPE Description of trap receivers | 1.3.6.1.4.1.534.6.7.1.1.2.14.1.5 | DisplayString (SIZE(0..31)) | read-write | mandatory |
| rmConfigAccessControlTable OBJECT-TYPE A list of managers which can access rm with private community string. | 1.3.6.1.4.1.534.6.7.1.1.2.15 | not-accessible | mandatory | |
| rmConfigAccessControlEntry OBJECT-TYPE The managers. | 1.3.6.1.4.1.534.6.7.1.1.2.15.1 | not-accessible | mandatory | |
| accessIndex OBJECT-TYPE The index to a access control entry. | 1.3.6.1.4.1.534.6.7.1.1.2.15.1.1 | INTEGER (1..2147483647) | read-only | mandatory |
| accessControlAddr OBJECT-TYPE The IP address of the manager to access RackMonitor | 1.3.6.1.4.1.534.6.7.1.1.2.15.1.2 | IpAddress | read-write | mandatory |
| accessCommunityString OBJECT-TYPE The community name to use in the manager when access RackMonitor | 1.3.6.1.4.1.534.6.7.1.1.2.15.1.3 | DisplayString (SIZE(0..19)) | read-write | mandatory |
| accessControlMode OBJECT-TYPE Access type, only read/Write access type can change parameter of RackMonitor | 1.3.6.1.4.1.534.6.7.1.1.2.15.1.4 | INTEGER {readOnly(1), read-write(2), notAccess(3)} | read-write | mandatory |
| rmConfigTemperatureUnit OBJECT-TYPE The temperature unit of the system, can be Celsius or Fahrenheit | 1.3.6.1.4.1.534.6.7.1.1.2.16 | INTEGER {celsius(1), fahrenheit(2)} | read-write | mandatory |
| rmConfigDateFormat OBJECT-TYPE The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy | 1.3.6.1.4.1.534.6.7.1.1.2.17 | INTEGER {mm-dd-yyyy(1), dd-mm-yyyy(2), yyyy-mm-dd(3), dd-mmm-yyyy(4)} | read-write | mandatory |
| sensorMonitor OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.3 | |||
| smSensorNumber OBJECT-TYPE The number of sensors that can be monitored. | 1.3.6.1.4.1.534.6.7.1.1.3.1 | INTEGER | read-only | mandatory |
| smSensorTable OBJECT-TYPE A list of sensor devices to be monitored. | 1.3.6.1.4.1.534.6.7.1.1.3.2 | not-accessible | mandatory | |
| smSensorEntry OBJECT-TYPE The sensor device. | 1.3.6.1.4.1.534.6.7.1.1.3.2.1 | not-accessible | mandatory | |
| smDeviceIndex OBJECT-TYPE The index to a sensor device entry. | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.1 | INTEGER (1..2147483647) | read-only | mandatory |
| smDeviceStatus OBJECT-TYPE The device type plugged into RackMonitor. | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.2 | INTEGER {unknow(1), disabled(2), eMD-HT(3), eMD-T(4)} | read-only | mandatory |
| smDeviceTemperature OBJECT-TYPE The temperature of sensor on device RackMonitor, the unit is 0.1 degree. | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.3 | INTEGER | read-only | mandatory |
| smDeviceTemperatureAlarm OBJECT-TYPE The status of temperature sensor on device RackMonitor. | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.4 | INTEGER {unknow(1), disabled(2), normal(3), lowWarning(4), lowCritical(5), highWarning(6), highCritical(7)} | read-only | mandatory |
| smDeviceHumidity OBJECT-TYPE The humidity of sensor on device RackMonitor, the unit is 0.1%. | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.5 | INTEGER | read-only | mandatory |
| smDeviceHumidityAlarm OBJECT-TYPE The device type plugged into RackMonitor. | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.6 | INTEGER {unknow(1), disabled(2), normal(3), lowWarning(4), lowCritical(5), highWarning(6), highCritical(7)} | read-only | mandatory |
| smAlarm1 OBJECT-TYPE The device type plugged into RackMonitor. | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.7 | INTEGER {unknow(1), disabled(2), active(3), inactive(4)} | read-only | mandatory |
| smAlarm2 OBJECT-TYPE The device type plugged into RackMonitor. | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.8 | INTEGER {unknow(1), disabled(2), active(3), inactive(4)} | read-only | mandatory |
| sensorConfig OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4 | |||
| scSensorNumber OBJECT-TYPE The number of sensors that can be plugged into RackMonitor. | 1.3.6.1.4.1.534.6.7.1.1.4.1 | INTEGER | read-only | mandatory |
| scSensorTable OBJECT-TYPE A list of sensor devices to be configured. | 1.3.6.1.4.1.534.6.7.1.1.4.2 | not-accessible | mandatory | |
| scSensorEntry OBJECT-TYPE The sensor device. | 1.3.6.1.4.1.534.6.7.1.1.4.2.1 | not-accessible | mandatory | |
| scDeviceIndex OBJECT-TYPE The index to a sensor device entry. | 1.3.6.1.4.1.534.6.7.1.1.4.2.1.1 | INTEGER (1..2147483647) | read-only | mandatory |
| scDeviceName OBJECT-TYPE The name of the sensor device for identification. | 1.3.6.1.4.1.534.6.7.1.1.4.2.1.2 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scDeviceState OBJECT-TYPE The setup of sensor device type. | 1.3.6.1.4.1.534.6.7.1.1.4.2.1.3 | INTEGER {disabled(1), auto(2)} | read-write | mandatory |
| scSensor1 OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.3 | |||
| scSensor1DeviceName OBJECT-TYPE The name of sensor device. | 1.3.6.1.4.1.534.6.7.1.1.4.3.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor1DeviceState OBJECT-TYPE The setup of sensor device type. | 1.3.6.1.4.1.534.6.7.1.1.4.3.2 | INTEGER {disabled(1), auto(2)} | read-write | mandatory |
| scSensor1Temperature OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.3.3 | |||
| scSensor1TemperatureName OBJECT-TYPE The temperature sensor name. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor1TemperatureLowWarning OBJECT-TYPE The set point to trigger low warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.2 | INTEGER | read-write | mandatory |
| scSensor1TemperatureLowCritical OBJECT-TYPE The threshold to trigger low critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.3 | INTEGER | read-write | mandatory |
| scSensor1TemperatureHighWarning OBJECT-TYPE The threshold to trigger high warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.4 | INTEGER | read-write | mandatory |
| scSensor1TemperatureHighCritical OBJECT-TYPE The threshold to trigger high critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.5 | INTEGER | read-write | mandatory |
| scSensor1TemperatureHysteresis OBJECT-TYPE The set value to prevent too many alarms when temperature is hovering around the set threshold. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.6 | INTEGER | read-write | mandatory |
| scSensor1TemperatureCalibration OBJECT-TYPE The set value to get the correct temperature according to the reference temperature. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.7 | INTEGER {temperatureIncrease0Point0(1), temperatureIncrease0Point5(2), temperatureIncrease1Point0(3), temperatureIncrease1Point5(4), temperatureIncrease2Point0(5), temperatureIncrease2Point5(6), temperatureIncrease3Point0(7), temperatureMinus0Point5(8), temperatureMinus1Point0(9), temperatureMinus1Point5(10), temperatureMinus2Point0(11), temperatureMinus2Point5(12), temperatureMinusPoint0(13)} | read-write | mandatory |
| scSensor1TemperatureLowWarningStatus OBJECT-TYPE Enable/Disable the set point to trigger low warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.8 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor1TemperatureLowCriticalStatus OBJECT-TYPE Enable/Disable the set point to trigger low critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.9 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor1TemperatureHighWarningStatus OBJECT-TYPE Enable/Disable the set point to trigger high warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.10 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor1TemperatureHighCriticalStatus OBJECT-TYPE Enable/disable the set point to trigger high critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.11 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor1Humidity OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.3.4 | |||
| scSensor1HumdityName OBJECT-TYPE The humidity sensor name. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor1HumidityLowWarning OBJECT-TYPE The set point to trigger low warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.2 | INTEGER | read-write | mandatory |
| scSensor1HumidityLowCritical OBJECT-TYPE The threshold to trigger low critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.3 | INTEGER | read-write | mandatory |
| scSensor1HumidityHighWarning OBJECT-TYPE The threshold to trigger high warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.4 | INTEGER | read-write | mandatory |
| scSensor1HumidityHighCritical OBJECT-TYPE The threshold to trigger high critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.5 | INTEGER | read-write | mandatory |
| scSensor1HumidityHysteresis OBJECT-TYPE The set value to prevent too many alarms when Humidity is hovering around the set threshold. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.6 | INTEGER | read-write | mandatory |
| scSensor1HumidityCalibration OBJECT-TYPE The set value to get the correct temperature according to your reference temperature. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.7 | INTEGER {humidityIncrease0Point0(1), humidityIncrease1Point0(2), humidityIncrease2Point0(3), humidityIncrease3Point0(4), humidityIncrease4Point0(5), humidityIncrease5Point0(6), humidityIncrease6Point0(7), humidityMinus1Point0(8), humidityMinus2Point0(9), humidityMinus3Point0(10), humidityMinus4Point0(11), humidityMinus5Point0(12), humidityMinus6Point0(13)} | read-write | mandatory |
| scSensor1HumidityLowWarningStatus OBJECT-TYPE Enable/Disable the set point to trigger low warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.8 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor1HumidityLowCriticalStatus OBJECT-TYPE Enable/Disable the set point to trigger low critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.9 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor1HumidityHighWarningStatus OBJECT-TYPE Enable/Disable the set point to trigger high warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.10 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor1HumidityHighCriticalStatus OBJECT-TYPE Enable/Disable the set point to trigger high critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.11 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor1Alarm1 OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.3.5 | |||
| scSensor1Alarm1Name OBJECT-TYPE The name of alarm-1. | 1.3.6.1.4.1.534.6.7.1.1.4.3.5.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor1Alarm1State OBJECT-TYPE Setup the signal type to trigger alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.5.2 | INTEGER {disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)} | read-write | mandatory |
| scSensor1Alarm1Hysteresis OBJECT-TYPE The set value to delay the alarm triggered when event occurs. | 1.3.6.1.4.1.534.6.7.1.1.4.3.5.3 | INTEGER | read-write | mandatory |
| scSensor1Alarm2 OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.3.6 | |||
| scSensor1Alarm2Name OBJECT-TYPE The name of alarm-1. | 1.3.6.1.4.1.534.6.7.1.1.4.3.6.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor1Alarm2State OBJECT-TYPE Setup the signal type to trigger alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.3.6.2 | INTEGER {disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)} | read-write | mandatory |
| scSensor1Alarm2Hysteresis OBJECT-TYPE The set value to delay the alarm triggered when event occurs. | 1.3.6.1.4.1.534.6.7.1.1.4.3.6.3 | INTEGER | read-write | mandatory |
| scSensor2 OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.4 | |||
| scSensor2DeviceName OBJECT-TYPE The name of sensor device. | 1.3.6.1.4.1.534.6.7.1.1.4.4.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor2DeviceState OBJECT-TYPE The setup of sensor device type. | 1.3.6.1.4.1.534.6.7.1.1.4.4.2 | INTEGER {disabled(1), auto(2)} | read-write | mandatory |
| scSensor2Temperature OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.4.3 | |||
| scSensor2TemperatureName OBJECT-TYPE The temperature sensor name. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor2TemperatureLowWarning OBJECT-TYPE The set point to trigger low warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.2 | INTEGER | read-write | mandatory |
| scSensor2TemperatureLowCritical OBJECT-TYPE The threshold to trigger low critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.3 | INTEGER | read-write | mandatory |
| scSensor2TemperatureHighWarning OBJECT-TYPE The threshold to trigger high warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.4 | INTEGER | read-write | mandatory |
| scSensor2TemperatureHighCritical OBJECT-TYPE The threshold to trigger high critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.5 | INTEGER | read-write | mandatory |
| scSensor2TemperatureHysteresis OBJECT-TYPE The set value to prevent too many alarms when temperature is hovering around the set threshold. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.6 | INTEGER | read-write | mandatory |
| scSensor2TemperatureCalibration OBJECT-TYPE The set value to get the correct temperature according to your reference temperature. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.7 | INTEGER {temperatureIncrease0Point0(1), temperatureIncrease0Point5(2), temperatureIncrease1Point0(3), temperatureIncrease1Point5(4), temperatureIncrease2Point0(5), temperatureIncrease2Point5(6), temperatureIncrease3Point0(7), temperatureMinus0Point5(8), temperatureMinus1Point0(9), temperatureMinus1Point5(10), temperatureMinus2Point0(11), temperatureMinus2Point5(12), temperatureMinusPoint0(13)} | read-write | mandatory |
| scSensor2TemperatureLowWarningStatus OBJECT-TYPE Enable/Disable the set point to trigger low warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.8 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor2TemperatureLowCriticalStatus OBJECT-TYPE Enable/Disable the set point to trigger low critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.9 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor2TemperatureHighWarningStatus OBJECT-TYPE Enable/Disable the set point to trigger high warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.10 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor2TemperatureHighCriticalStatus OBJECT-TYPE Enable/Disable the set point to trigger high critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.11 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor2Humidity OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.4.4 | |||
| scSensor2HumdityName OBJECT-TYPE The humidity sensor name. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor2HumidityLowWarning OBJECT-TYPE The set point to trigger low warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.2 | INTEGER | read-write | mandatory |
| scSensor2HumidityLowCritical OBJECT-TYPE The threshold to trigger low critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.3 | INTEGER | read-write | mandatory |
| scSensor2HumidityHighWarning OBJECT-TYPE The threshold to trigger high warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.4 | INTEGER | read-write | mandatory |
| scSensor2HumidityHighCritical OBJECT-TYPE The threshold to trigger high critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.5 | INTEGER | read-write | mandatory |
| scSensor2HumidityHysteresis OBJECT-TYPE The set value to prevent too many alarms when Humidity is hovering around the set threshold. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.6 | INTEGER | read-write | mandatory |
| scSensor2HumidityCalibration OBJECT-TYPE The set value to get the correct temperature according to the reference temperature. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.7 | INTEGER {humidityIncrease0Point0(1), humidityIncrease1Point0(2), humidityIncrease2Point0(3), humidityIncrease3Point0(4), humidityIncrease4Point0(5), humidityIncrease5Point0(6), humidityIncrease6Point0(7), humidityMinus1Point0(8), humidityMinus2Point0(9), humidityMinus3Point0(10), humidityMinus4Point0(11), humidityMinus5Point0(12), humidityMinus6Point0(13)} | read-write | mandatory |
| scSensor2HumidityLowWarningStatus OBJECT-TYPE Enable/Disable the set point to trigger low warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.8 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor2HumidityLowCriticalStatus OBJECT-TYPE Enable/Disable the set point to trigger low critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.9 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor2HumidityHighWarningStatus OBJECT-TYPE Enable/Disable the set point to trigger high warning alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.10 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor2HumidityHighCriticalStatus OBJECT-TYPE Enable/Disable the set point to trigger high critical alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.11 | INTEGER {enabled(1), disabled(2)} | read-write | mandatory |
| scSensor2Alarm1 OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.4.5 | |||
| scSensor2Alarm1Name OBJECT-TYPE The name of alarm-1. | 1.3.6.1.4.1.534.6.7.1.1.4.4.5.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor2Alarm1State OBJECT-TYPE Setup the signal type to trigger alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.5.2 | INTEGER {disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)} | read-write | mandatory |
| scSensor2Alarm1Hysteresis OBJECT-TYPE The set value to delay the alarm triggered when event occurs. | 1.3.6.1.4.1.534.6.7.1.1.4.4.5.3 | INTEGER | read-write | mandatory |
| scSensor2Alarm2 OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.1.4.4.6 | |||
| scSensor2Alarm2Name OBJECT-TYPE The name of alarm-1. | 1.3.6.1.4.1.534.6.7.1.1.4.4.6.1 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| scSensor2Alarm2State OBJECT-TYPE Setup the signal type to trigger alarm. | 1.3.6.1.4.1.534.6.7.1.1.4.4.6.2 | INTEGER {disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)} | read-write | mandatory |
| scSensor2Alarm2Hysteresis OBJECT-TYPE The set value to delay the alarm triggered when event occurs. | 1.3.6.1.4.1.534.6.7.1.1.4.4.6.3 | INTEGER | read-write | mandatory |
| rmTraps OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.7.1.2 |
Notifications
| Name | OID | Status |
|---|---|---|
| rmCommunicationRestored NOTIFICATION-TYPE INFORMATION: Communication between RackMonitor and sensor had established. | 1.3.6.1.4.1.534.6.7.1.2.0.1 | |
| rmCommunicationLost NOTIFICATION-TYPE WARNING: Communication between RackMonitor and sensor had lost. | 1.3.6.1.4.1.534.6.7.1.2.0.2 | |
| rmAlarm1Inactive NOTIFICATION-TYPE INFORMATION: Alarm1 of sensor had return from active state. | 1.3.6.1.4.1.534.6.7.1.2.0.3 | |
| rmAlarm1Active NOTIFICATION-TYPE WARNING: Alarm1 has become active. | 1.3.6.1.4.1.534.6.7.1.2.0.4 | |
| rmAlarm2Inactive NOTIFICATION-TYPE INFORMATION: Alarm2 of sensor has returned to normal state. | 1.3.6.1.4.1.534.6.7.1.2.0.5 | |
| rmAlarm2Active NOTIFICATION-TYPE WARNING: Alarm2 had became active. | 1.3.6.1.4.1.534.6.7.1.2.0.6 | |
| rmTemperatureNotHighWarning NOTIFICATION-TYPE INFORMATION: The temperature of sensor had return from High warning to normal. | 1.3.6.1.4.1.534.6.7.1.2.0.7 | |
| rmTemperatureHighWarning NOTIFICATION-TYPE WARNING: The temperature of sensor was higher than High warning set point. | 1.3.6.1.4.1.534.6.7.1.2.0.8 | |
| rmTemperatureNotLowWarning NOTIFICATION-TYPE INFORMATION: The temperature of sensor had return from low warning to normal. | 1.3.6.1.4.1.534.6.7.1.2.0.9 | |
| rmTemperatureLowWarning NOTIFICATION-TYPE WARNING: The temperature of sensor was lower than low warning set point. | 1.3.6.1.4.1.534.6.7.1.2.0.10 | |
| rmTemperatureNotHighCritical NOTIFICATION-TYPE INFORMATION: The temperature of sensor lower than high critical set point. | 1.3.6.1.4.1.534.6.7.1.2.0.11 | |
| rmTemperatureHighCritical NOTIFICATION-TYPE CRITICAL: The temperature of sensor was higher than high critical set point. | 1.3.6.1.4.1.534.6.7.1.2.0.12 | |
| rmTemperatureNotLowCritical NOTIFICATION-TYPE INFORMATION: The temperature of sensor was higher than low critical set point. | 1.3.6.1.4.1.534.6.7.1.2.0.13 | |
| rmTemperatureLowCritical NOTIFICATION-TYPE CRITICAL: The temperature of sensor was lower than low critical set point. | 1.3.6.1.4.1.534.6.7.1.2.0.14 | |
| rmHumidityNotHighWarning NOTIFICATION-TYPE INFORMATION: The humidity of sensor had return from High warning to normal. | 1.3.6.1.4.1.534.6.7.1.2.0.15 | |
| rmHumidityHighWarning NOTIFICATION-TYPE WARNING: The humidity of sensor was higher than High warning set point. | 1.3.6.1.4.1.534.6.7.1.2.0.16 | |
| rmHumidityNotLowWarning NOTIFICATION-TYPE INFORMATION: The humidity of sensor had return from low warning to normal. | 1.3.6.1.4.1.534.6.7.1.2.0.17 | |
| rmHumidityLowWarning NOTIFICATION-TYPE WARNING: The humidity of sensor was lower than low warning set point. | 1.3.6.1.4.1.534.6.7.1.2.0.18 | |
| rmHumidityNotHighCritical NOTIFICATION-TYPE INFORMATION: The humidity of sensor lower than high critical set point. | 1.3.6.1.4.1.534.6.7.1.2.0.19 | |
| rmHumidityHighCritical NOTIFICATION-TYPE CRITICAL: The humidity of sensor was higher than high critical set point. | 1.3.6.1.4.1.534.6.7.1.2.0.20 | |
| rmHumidityNotLowCritical NOTIFICATION-TYPE INFORMATION: The humidity of sensor was higher than low critical set point. | 1.3.6.1.4.1.534.6.7.1.2.0.21 | |
| rmHumidityLowCritical NOTIFICATION-TYPE CRITICAL: The humidity of sensor was lower than low critical set point. | 1.3.6.1.4.1.534.6.7.1.2.0.22 |