MIBs Depot

RackMonitor-MIB

Registered at
1.3.6.1.4.1.534.6.7.1.1
1.3.6.1.4.1.534.6.7.1.2
Namespace
eaton
Source file
RackMonitor-MIB
Digest
sha256:697779da73d0df5ebe4d6d18d991f64f8f32ebc45c2e37a0259437e2e0447538

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

RackMonitor-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
powerware
OBJECT-IDENTITY
1.3.6.1.4.1.534
product
OBJECT-IDENTITY
1.3.6.1.4.1.534.6
dataCenter
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7
environmentalMonitor
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1
insObjects
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1
rmIdent
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.1
insIdentManufacturer
OBJECT-TYPE
The name of the RackMonitor manufacturer.
1.3.6.1.4.1.534.6.7.1.1.1.1DisplayString (SIZE(0..31))read-onlymandatory
insIdentModel
OBJECT-TYPE
The RackMonitor Model designation.
1.3.6.1.4.1.534.6.7.1.1.1.2DisplayString (SIZE(0..63))read-onlymandatory
insIdentAgentSoftwareVersion
OBJECT-TYPE
The RackMonitor software/firmware version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.534.6.7.1.1.1.3DisplayString (SIZE(0..31))read-onlymandatory
insIdentName
OBJECT-TYPE
A string identifying the RackMonitor. This object should be set by the administrator.
1.3.6.1.4.1.534.6.7.1.1.1.4DisplayString (SIZE(0..31))read-writemandatory
rmConfig
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.2
rmConfigMibVersion
OBJECT-TYPE
The version of MIB spec.
1.3.6.1.4.1.534.6.7.1.1.2.1INTEGERread-onlymandatory
rmConfigNetwork
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.2.2
rmConfigIpAddress
OBJECT-TYPE
The ip address that NMS can identify the managed device
1.3.6.1.4.1.534.6.7.1.1.2.2.1IpAddressread-writemandatory
rmConfigGateway
OBJECT-TYPE
The default gateway that allow device managed through routers
1.3.6.1.4.1.534.6.7.1.1.2.2.2IpAddressread-writemandatory
rmConfigSubnetMask
OBJECT-TYPE
Internet address subnet mask
1.3.6.1.4.1.534.6.7.1.1.2.2.3IpAddressread-writemandatory
rmConfigDateTime
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.2.3
rmConfigDate
OBJECT-TYPE
The date in Environmental Rack Monitor, format is (dd/mm/yyyy)
1.3.6.1.4.1.534.6.7.1.1.2.3.1DisplayString (SIZE(10))read-writemandatory
rmConfigTime
OBJECT-TYPE
The time in Environmental Rack Monitor, format is (hh:mm:ss)
1.3.6.1.4.1.534.6.7.1.1.2.3.2DisplayString (SIZE(8))read-writemandatory
rmConfigTimeFromNtp
OBJECT-TYPE
Enable/disable update of the date and time from the NTP server.
1.3.6.1.4.1.534.6.7.1.1.2.3.3INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigNtpIpAddress
OBJECT-TYPE
NTP IP address.
1.3.6.1.4.1.534.6.7.1.1.2.3.4IpAddressread-writemandatory
rmConfigNtpTimeZone
OBJECT-TYPE
Enable/disable update of the date and time from the NTP server.
1.3.6.1.4.1.534.6.7.1.1.2.3.5INTEGER {gMT-1200(1), gMT-1100(2), gMT-1000(3), gMT-0900(4), gMT-0800(5), gMT-0700(6), gMT-0600(7), gMT-0500(8), gMT-0400(9), gMT-0330(10), gMT-0300(11), gMT-0200(12), gMT-0100(13), gMT-0000(14), gMT0100(15), gMT0200(16), gMT0300(17), gMT0330(18), gMT0400(19), gMT0500(20), gMT0530(21), gMT0600(22), gMT0700(23), gMT0800(24), gMT0900(25), gMT1000(26), gMT1100(27), gMT1200(28)}read-writemandatory
rmConfigDayLightSaving
OBJECT-TYPE
Enable/disable daylight saving for NTP time, if enabled, the time obtained from the NTP will be set one hour in advance to reflect daylight saving status.
1.3.6.1.4.1.534.6.7.1.1.2.3.6INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigLog
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.2.4
rmConfigHistoryLogFrequency
OBJECT-TYPE
The frequency of the history log update. The value is in seconds
1.3.6.1.4.1.534.6.7.1.1.2.4.1INTEGER (5..3600)read-writemandatory
rmConfigExtHistoryLogFrequency
OBJECT-TYPE
The frequency of the extended history log update. The value is in seconds
1.3.6.1.4.1.534.6.7.1.1.2.4.2INTEGER (1..1440)read-writemandatory
rmConfigConfigurationLog
OBJECT-TYPE
Enable/Disable Environmental Rack Monitor parameters change logging.
1.3.6.1.4.1.534.6.7.1.1.2.4.3INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigDhcpStatue
OBJECT-TYPE
Enable or Disable DHCP/BootP capability
1.3.6.1.4.1.534.6.7.1.1.2.5INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigPingStatue
OBJECT-TYPE
Enable or Disable Ping Echo capability
1.3.6.1.4.1.534.6.7.1.1.2.6INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigTftpStatue
OBJECT-TYPE
Enable or Disable TFTP network upgrade capability
1.3.6.1.4.1.534.6.7.1.1.2.7INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigTelnet
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.2.8
rmConfigTelnetStatue
OBJECT-TYPE
Enable or Disable telnet access
1.3.6.1.4.1.534.6.7.1.1.2.8.1INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigTelnetPortNumber
OBJECT-TYPE
Setting the server port for telnet.
1.3.6.1.4.1.534.6.7.1.1.2.8.2INTEGER (1..65535)read-writemandatory
rmConfigHttp
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.2.9
rmConfigHttpStatue
OBJECT-TYPE
Enable or Disable HTTP access
1.3.6.1.4.1.534.6.7.1.1.2.9.1INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigHttpPortNumber
OBJECT-TYPE
Setting the server port of HTTP.
1.3.6.1.4.1.534.6.7.1.1.2.9.2INTEGER (1..65535)read-writemandatory
rmConfigHttpSecurity
OBJECT-TYPE
Enable/Disable HTTP access for read-only users
1.3.6.1.4.1.534.6.7.1.1.2.9.3INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigSnmp
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.2.10
rmConfigSnmpStatue
OBJECT-TYPE
Enable or Disable SNMP access
1.3.6.1.4.1.534.6.7.1.1.2.10.1INTEGER {enabled(1), disabled(2)}read-writemandatory
rmConfigSnmpPortNumber
OBJECT-TYPE
Setting the server port for SNMP.
1.3.6.1.4.1.534.6.7.1.1.2.10.2INTEGER (1..65535)read-writemandatory
rmConfigControl
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.2.11
rmConfigResetToDefault
OBJECT-TYPE
Reset all parameters of Environmental Rack Monitor to default values
1.3.6.1.4.1.534.6.7.1.1.2.11.1INTEGER {reset(1), nothing(2)}read-writemandatory
rmConfigRestart
OBJECT-TYPE
Restart rm
1.3.6.1.4.1.534.6.7.1.1.2.11.2INTEGER {restart(1), nothing(2)}read-writemandatory
rmConfigTrap
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.2.12
rmConfigTrapRetryCount
OBJECT-TYPE
The count of repeat traps to send to NMS before trap acknowledge received.
1.3.6.1.4.1.534.6.7.1.1.2.12.1INTEGERread-writemandatory
rmConfigTrapRetryTime
OBJECT-TYPE
The time between retry traps sent to NMS.
1.3.6.1.4.1.534.6.7.1.1.2.12.2INTEGERread-writemandatory
rmConfigTrapAckSignature
OBJECT-TYPE
The signature of trap acknowledge.
1.3.6.1.4.1.534.6.7.1.1.2.12.3INTEGERread-writemandatory
rmConfigPollRate
OBJECT-TYPE
The frequency that the Rack Monitor will read from sensors (unit : second).
1.3.6.1.4.1.534.6.7.1.1.2.13INTEGER (3..60)read-writemandatory
rmConfigTrapsReceiversTable
OBJECT-TYPE
A list of managers to send traps to. The number of entries is given by the value of rmConfigNumTrapReceivers
1.3.6.1.4.1.534.6.7.1.1.2.14not-accessiblemandatory
rmConfigTrapsReceiversEntry
OBJECT-TYPE
The managers to send traps to.
1.3.6.1.4.1.534.6.7.1.1.2.14.1not-accessiblemandatory
trapsIndex
OBJECT-TYPE
The index to a trap receiver entry.
1.3.6.1.4.1.534.6.7.1.1.2.14.1.1INTEGER (1..2147483647)read-onlymandatory
trapsReceiverAddr
OBJECT-TYPE
The IP address of the manager to send a trap to.
1.3.6.1.4.1.534.6.7.1.1.2.14.1.2IpAddressread-writemandatory
receiverCommunityString
OBJECT-TYPE
The community name to use in the trap when sent to the manager.
1.3.6.1.4.1.534.6.7.1.1.2.14.1.3DisplayString (SIZE(0..19))read-writemandatory
receiverSeverityLevel
OBJECT-TYPE
The severity level of traps to be received by this manager.
1.3.6.1.4.1.534.6.7.1.1.2.14.1.4INTEGER {informational(1), warning(2), severe(3)}read-writemandatory
receiverDescription
OBJECT-TYPE
Description of trap receivers
1.3.6.1.4.1.534.6.7.1.1.2.14.1.5DisplayString (SIZE(0..31))read-writemandatory
rmConfigAccessControlTable
OBJECT-TYPE
A list of managers which can access rm with private community string.
1.3.6.1.4.1.534.6.7.1.1.2.15not-accessiblemandatory
rmConfigAccessControlEntry
OBJECT-TYPE
The managers.
1.3.6.1.4.1.534.6.7.1.1.2.15.1not-accessiblemandatory
accessIndex
OBJECT-TYPE
The index to a access control entry.
1.3.6.1.4.1.534.6.7.1.1.2.15.1.1INTEGER (1..2147483647)read-onlymandatory
accessControlAddr
OBJECT-TYPE
The IP address of the manager to access RackMonitor
1.3.6.1.4.1.534.6.7.1.1.2.15.1.2IpAddressread-writemandatory
accessCommunityString
OBJECT-TYPE
The community name to use in the manager when access RackMonitor
1.3.6.1.4.1.534.6.7.1.1.2.15.1.3DisplayString (SIZE(0..19))read-writemandatory
accessControlMode
OBJECT-TYPE
Access type, only read/Write access type can change parameter of RackMonitor
1.3.6.1.4.1.534.6.7.1.1.2.15.1.4INTEGER {readOnly(1), read-write(2), notAccess(3)}read-writemandatory
rmConfigTemperatureUnit
OBJECT-TYPE
The temperature unit of the system, can be Celsius or Fahrenheit
1.3.6.1.4.1.534.6.7.1.1.2.16INTEGER {celsius(1), fahrenheit(2)}read-writemandatory
rmConfigDateFormat
OBJECT-TYPE
The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy
1.3.6.1.4.1.534.6.7.1.1.2.17INTEGER {mm-dd-yyyy(1), dd-mm-yyyy(2), yyyy-mm-dd(3), dd-mmm-yyyy(4)}read-writemandatory
sensorMonitor
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.3
smSensorNumber
OBJECT-TYPE
The number of sensors that can be monitored.
1.3.6.1.4.1.534.6.7.1.1.3.1INTEGERread-onlymandatory
smSensorTable
OBJECT-TYPE
A list of sensor devices to be monitored.
1.3.6.1.4.1.534.6.7.1.1.3.2not-accessiblemandatory
smSensorEntry
OBJECT-TYPE
The sensor device.
1.3.6.1.4.1.534.6.7.1.1.3.2.1not-accessiblemandatory
smDeviceIndex
OBJECT-TYPE
The index to a sensor device entry.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.1INTEGER (1..2147483647)read-onlymandatory
smDeviceStatus
OBJECT-TYPE
The device type plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.2INTEGER {unknow(1), disabled(2), eMD-HT(3), eMD-T(4)}read-onlymandatory
smDeviceTemperature
OBJECT-TYPE
The temperature of sensor on device RackMonitor, the unit is 0.1 degree.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.3INTEGERread-onlymandatory
smDeviceTemperatureAlarm
OBJECT-TYPE
The status of temperature sensor on device RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.4INTEGER {unknow(1), disabled(2), normal(3), lowWarning(4), lowCritical(5), highWarning(6), highCritical(7)}read-onlymandatory
smDeviceHumidity
OBJECT-TYPE
The humidity of sensor on device RackMonitor, the unit is 0.1%.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.5INTEGERread-onlymandatory
smDeviceHumidityAlarm
OBJECT-TYPE
The device type plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.6INTEGER {unknow(1), disabled(2), normal(3), lowWarning(4), lowCritical(5), highWarning(6), highCritical(7)}read-onlymandatory
smAlarm1
OBJECT-TYPE
The device type plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.7INTEGER {unknow(1), disabled(2), active(3), inactive(4)}read-onlymandatory
smAlarm2
OBJECT-TYPE
The device type plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.8INTEGER {unknow(1), disabled(2), active(3), inactive(4)}read-onlymandatory
sensorConfig
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4
scSensorNumber
OBJECT-TYPE
The number of sensors that can be plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.4.1INTEGERread-onlymandatory
scSensorTable
OBJECT-TYPE
A list of sensor devices to be configured.
1.3.6.1.4.1.534.6.7.1.1.4.2not-accessiblemandatory
scSensorEntry
OBJECT-TYPE
The sensor device.
1.3.6.1.4.1.534.6.7.1.1.4.2.1not-accessiblemandatory
scDeviceIndex
OBJECT-TYPE
The index to a sensor device entry.
1.3.6.1.4.1.534.6.7.1.1.4.2.1.1INTEGER (1..2147483647)read-onlymandatory
scDeviceName
OBJECT-TYPE
The name of the sensor device for identification.
1.3.6.1.4.1.534.6.7.1.1.4.2.1.2DisplayString (SIZE(0..15))read-writemandatory
scDeviceState
OBJECT-TYPE
The setup of sensor device type.
1.3.6.1.4.1.534.6.7.1.1.4.2.1.3INTEGER {disabled(1), auto(2)}read-writemandatory
scSensor1
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.3
scSensor1DeviceName
OBJECT-TYPE
The name of sensor device.
1.3.6.1.4.1.534.6.7.1.1.4.3.1DisplayString (SIZE(0..15))read-writemandatory
scSensor1DeviceState
OBJECT-TYPE
The setup of sensor device type.
1.3.6.1.4.1.534.6.7.1.1.4.3.2INTEGER {disabled(1), auto(2)}read-writemandatory
scSensor1Temperature
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.3.3
scSensor1TemperatureName
OBJECT-TYPE
The temperature sensor name.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.1DisplayString (SIZE(0..15))read-writemandatory
scSensor1TemperatureLowWarning
OBJECT-TYPE
The set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.2INTEGERread-writemandatory
scSensor1TemperatureLowCritical
OBJECT-TYPE
The threshold to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.3INTEGERread-writemandatory
scSensor1TemperatureHighWarning
OBJECT-TYPE
The threshold to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.4INTEGERread-writemandatory
scSensor1TemperatureHighCritical
OBJECT-TYPE
The threshold to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.5INTEGERread-writemandatory
scSensor1TemperatureHysteresis
OBJECT-TYPE
The set value to prevent too many alarms when temperature is hovering around the set threshold.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.6INTEGERread-writemandatory
scSensor1TemperatureCalibration
OBJECT-TYPE
The set value to get the correct temperature according to the reference temperature.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.7INTEGER {temperatureIncrease0Point0(1), temperatureIncrease0Point5(2), temperatureIncrease1Point0(3), temperatureIncrease1Point5(4), temperatureIncrease2Point0(5), temperatureIncrease2Point5(6), temperatureIncrease3Point0(7), temperatureMinus0Point5(8), temperatureMinus1Point0(9), temperatureMinus1Point5(10), temperatureMinus2Point0(11), temperatureMinus2Point5(12), temperatureMinusPoint0(13)}read-writemandatory
scSensor1TemperatureLowWarningStatus
OBJECT-TYPE
Enable/Disable the set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.8INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor1TemperatureLowCriticalStatus
OBJECT-TYPE
Enable/Disable the set point to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.9INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor1TemperatureHighWarningStatus
OBJECT-TYPE
Enable/Disable the set point to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.10INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor1TemperatureHighCriticalStatus
OBJECT-TYPE
Enable/disable the set point to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.11INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor1Humidity
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.3.4
scSensor1HumdityName
OBJECT-TYPE
The humidity sensor name.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.1DisplayString (SIZE(0..15))read-writemandatory
scSensor1HumidityLowWarning
OBJECT-TYPE
The set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.2INTEGERread-writemandatory
scSensor1HumidityLowCritical
OBJECT-TYPE
The threshold to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.3INTEGERread-writemandatory
scSensor1HumidityHighWarning
OBJECT-TYPE
The threshold to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.4INTEGERread-writemandatory
scSensor1HumidityHighCritical
OBJECT-TYPE
The threshold to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.5INTEGERread-writemandatory
scSensor1HumidityHysteresis
OBJECT-TYPE
The set value to prevent too many alarms when Humidity is hovering around the set threshold.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.6INTEGERread-writemandatory
scSensor1HumidityCalibration
OBJECT-TYPE
The set value to get the correct temperature according to your reference temperature.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.7INTEGER {humidityIncrease0Point0(1), humidityIncrease1Point0(2), humidityIncrease2Point0(3), humidityIncrease3Point0(4), humidityIncrease4Point0(5), humidityIncrease5Point0(6), humidityIncrease6Point0(7), humidityMinus1Point0(8), humidityMinus2Point0(9), humidityMinus3Point0(10), humidityMinus4Point0(11), humidityMinus5Point0(12), humidityMinus6Point0(13)}read-writemandatory
scSensor1HumidityLowWarningStatus
OBJECT-TYPE
Enable/Disable the set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.8INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor1HumidityLowCriticalStatus
OBJECT-TYPE
Enable/Disable the set point to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.9INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor1HumidityHighWarningStatus
OBJECT-TYPE
Enable/Disable the set point to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.10INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor1HumidityHighCriticalStatus
OBJECT-TYPE
Enable/Disable the set point to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.11INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor1Alarm1
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.3.5
scSensor1Alarm1Name
OBJECT-TYPE
The name of alarm-1.
1.3.6.1.4.1.534.6.7.1.1.4.3.5.1DisplayString (SIZE(0..15))read-writemandatory
scSensor1Alarm1State
OBJECT-TYPE
Setup the signal type to trigger alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.5.2INTEGER {disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)}read-writemandatory
scSensor1Alarm1Hysteresis
OBJECT-TYPE
The set value to delay the alarm triggered when event occurs.
1.3.6.1.4.1.534.6.7.1.1.4.3.5.3INTEGERread-writemandatory
scSensor1Alarm2
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.3.6
scSensor1Alarm2Name
OBJECT-TYPE
The name of alarm-1.
1.3.6.1.4.1.534.6.7.1.1.4.3.6.1DisplayString (SIZE(0..15))read-writemandatory
scSensor1Alarm2State
OBJECT-TYPE
Setup the signal type to trigger alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.6.2INTEGER {disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)}read-writemandatory
scSensor1Alarm2Hysteresis
OBJECT-TYPE
The set value to delay the alarm triggered when event occurs.
1.3.6.1.4.1.534.6.7.1.1.4.3.6.3INTEGERread-writemandatory
scSensor2
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.4
scSensor2DeviceName
OBJECT-TYPE
The name of sensor device.
1.3.6.1.4.1.534.6.7.1.1.4.4.1DisplayString (SIZE(0..15))read-writemandatory
scSensor2DeviceState
OBJECT-TYPE
The setup of sensor device type.
1.3.6.1.4.1.534.6.7.1.1.4.4.2INTEGER {disabled(1), auto(2)}read-writemandatory
scSensor2Temperature
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.4.3
scSensor2TemperatureName
OBJECT-TYPE
The temperature sensor name.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.1DisplayString (SIZE(0..15))read-writemandatory
scSensor2TemperatureLowWarning
OBJECT-TYPE
The set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.2INTEGERread-writemandatory
scSensor2TemperatureLowCritical
OBJECT-TYPE
The threshold to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.3INTEGERread-writemandatory
scSensor2TemperatureHighWarning
OBJECT-TYPE
The threshold to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.4INTEGERread-writemandatory
scSensor2TemperatureHighCritical
OBJECT-TYPE
The threshold to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.5INTEGERread-writemandatory
scSensor2TemperatureHysteresis
OBJECT-TYPE
The set value to prevent too many alarms when temperature is hovering around the set threshold.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.6INTEGERread-writemandatory
scSensor2TemperatureCalibration
OBJECT-TYPE
The set value to get the correct temperature according to your reference temperature.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.7INTEGER {temperatureIncrease0Point0(1), temperatureIncrease0Point5(2), temperatureIncrease1Point0(3), temperatureIncrease1Point5(4), temperatureIncrease2Point0(5), temperatureIncrease2Point5(6), temperatureIncrease3Point0(7), temperatureMinus0Point5(8), temperatureMinus1Point0(9), temperatureMinus1Point5(10), temperatureMinus2Point0(11), temperatureMinus2Point5(12), temperatureMinusPoint0(13)}read-writemandatory
scSensor2TemperatureLowWarningStatus
OBJECT-TYPE
Enable/Disable the set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.8INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor2TemperatureLowCriticalStatus
OBJECT-TYPE
Enable/Disable the set point to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.9INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor2TemperatureHighWarningStatus
OBJECT-TYPE
Enable/Disable the set point to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.10INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor2TemperatureHighCriticalStatus
OBJECT-TYPE
Enable/Disable the set point to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.11INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor2Humidity
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.4.4
scSensor2HumdityName
OBJECT-TYPE
The humidity sensor name.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.1DisplayString (SIZE(0..15))read-writemandatory
scSensor2HumidityLowWarning
OBJECT-TYPE
The set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.2INTEGERread-writemandatory
scSensor2HumidityLowCritical
OBJECT-TYPE
The threshold to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.3INTEGERread-writemandatory
scSensor2HumidityHighWarning
OBJECT-TYPE
The threshold to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.4INTEGERread-writemandatory
scSensor2HumidityHighCritical
OBJECT-TYPE
The threshold to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.5INTEGERread-writemandatory
scSensor2HumidityHysteresis
OBJECT-TYPE
The set value to prevent too many alarms when Humidity is hovering around the set threshold.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.6INTEGERread-writemandatory
scSensor2HumidityCalibration
OBJECT-TYPE
The set value to get the correct temperature according to the reference temperature.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.7INTEGER {humidityIncrease0Point0(1), humidityIncrease1Point0(2), humidityIncrease2Point0(3), humidityIncrease3Point0(4), humidityIncrease4Point0(5), humidityIncrease5Point0(6), humidityIncrease6Point0(7), humidityMinus1Point0(8), humidityMinus2Point0(9), humidityMinus3Point0(10), humidityMinus4Point0(11), humidityMinus5Point0(12), humidityMinus6Point0(13)}read-writemandatory
scSensor2HumidityLowWarningStatus
OBJECT-TYPE
Enable/Disable the set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.8INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor2HumidityLowCriticalStatus
OBJECT-TYPE
Enable/Disable the set point to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.9INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor2HumidityHighWarningStatus
OBJECT-TYPE
Enable/Disable the set point to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.10INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor2HumidityHighCriticalStatus
OBJECT-TYPE
Enable/Disable the set point to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.11INTEGER {enabled(1), disabled(2)}read-writemandatory
scSensor2Alarm1
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.4.5
scSensor2Alarm1Name
OBJECT-TYPE
The name of alarm-1.
1.3.6.1.4.1.534.6.7.1.1.4.4.5.1DisplayString (SIZE(0..15))read-writemandatory
scSensor2Alarm1State
OBJECT-TYPE
Setup the signal type to trigger alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.5.2INTEGER {disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)}read-writemandatory
scSensor2Alarm1Hysteresis
OBJECT-TYPE
The set value to delay the alarm triggered when event occurs.
1.3.6.1.4.1.534.6.7.1.1.4.4.5.3INTEGERread-writemandatory
scSensor2Alarm2
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.1.4.4.6
scSensor2Alarm2Name
OBJECT-TYPE
The name of alarm-1.
1.3.6.1.4.1.534.6.7.1.1.4.4.6.1DisplayString (SIZE(0..15))read-writemandatory
scSensor2Alarm2State
OBJECT-TYPE
Setup the signal type to trigger alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.6.2INTEGER {disabled(1), normalOpen(2), normalClose(3), highActive(4), lowActive(5)}read-writemandatory
scSensor2Alarm2Hysteresis
OBJECT-TYPE
The set value to delay the alarm triggered when event occurs.
1.3.6.1.4.1.534.6.7.1.1.4.4.6.3INTEGERread-writemandatory
rmTraps
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.7.1.2

Notifications

NameOIDStatus
rmCommunicationRestored
NOTIFICATION-TYPE
INFORMATION: Communication between RackMonitor and sensor had established.
1.3.6.1.4.1.534.6.7.1.2.0.1
rmCommunicationLost
NOTIFICATION-TYPE
WARNING: Communication between RackMonitor and sensor had lost.
1.3.6.1.4.1.534.6.7.1.2.0.2
rmAlarm1Inactive
NOTIFICATION-TYPE
INFORMATION: Alarm1 of sensor had return from active state.
1.3.6.1.4.1.534.6.7.1.2.0.3
rmAlarm1Active
NOTIFICATION-TYPE
WARNING: Alarm1 has become active.
1.3.6.1.4.1.534.6.7.1.2.0.4
rmAlarm2Inactive
NOTIFICATION-TYPE
INFORMATION: Alarm2 of sensor has returned to normal state.
1.3.6.1.4.1.534.6.7.1.2.0.5
rmAlarm2Active
NOTIFICATION-TYPE
WARNING: Alarm2 had became active.
1.3.6.1.4.1.534.6.7.1.2.0.6
rmTemperatureNotHighWarning
NOTIFICATION-TYPE
INFORMATION: The temperature of sensor had return from High warning to normal.
1.3.6.1.4.1.534.6.7.1.2.0.7
rmTemperatureHighWarning
NOTIFICATION-TYPE
WARNING: The temperature of sensor was higher than High warning set point.
1.3.6.1.4.1.534.6.7.1.2.0.8
rmTemperatureNotLowWarning
NOTIFICATION-TYPE
INFORMATION: The temperature of sensor had return from low warning to normal.
1.3.6.1.4.1.534.6.7.1.2.0.9
rmTemperatureLowWarning
NOTIFICATION-TYPE
WARNING: The temperature of sensor was lower than low warning set point.
1.3.6.1.4.1.534.6.7.1.2.0.10
rmTemperatureNotHighCritical
NOTIFICATION-TYPE
INFORMATION: The temperature of sensor lower than high critical set point.
1.3.6.1.4.1.534.6.7.1.2.0.11
rmTemperatureHighCritical
NOTIFICATION-TYPE
CRITICAL: The temperature of sensor was higher than high critical set point.
1.3.6.1.4.1.534.6.7.1.2.0.12
rmTemperatureNotLowCritical
NOTIFICATION-TYPE
INFORMATION: The temperature of sensor was higher than low critical set point.
1.3.6.1.4.1.534.6.7.1.2.0.13
rmTemperatureLowCritical
NOTIFICATION-TYPE
CRITICAL: The temperature of sensor was lower than low critical set point.
1.3.6.1.4.1.534.6.7.1.2.0.14
rmHumidityNotHighWarning
NOTIFICATION-TYPE
INFORMATION: The humidity of sensor had return from High warning to normal.
1.3.6.1.4.1.534.6.7.1.2.0.15
rmHumidityHighWarning
NOTIFICATION-TYPE
WARNING: The humidity of sensor was higher than High warning set point.
1.3.6.1.4.1.534.6.7.1.2.0.16
rmHumidityNotLowWarning
NOTIFICATION-TYPE
INFORMATION: The humidity of sensor had return from low warning to normal.
1.3.6.1.4.1.534.6.7.1.2.0.17
rmHumidityLowWarning
NOTIFICATION-TYPE
WARNING: The humidity of sensor was lower than low warning set point.
1.3.6.1.4.1.534.6.7.1.2.0.18
rmHumidityNotHighCritical
NOTIFICATION-TYPE
INFORMATION: The humidity of sensor lower than high critical set point.
1.3.6.1.4.1.534.6.7.1.2.0.19
rmHumidityHighCritical
NOTIFICATION-TYPE
CRITICAL: The humidity of sensor was higher than high critical set point.
1.3.6.1.4.1.534.6.7.1.2.0.20
rmHumidityNotLowCritical
NOTIFICATION-TYPE
INFORMATION: The humidity of sensor was higher than low critical set point.
1.3.6.1.4.1.534.6.7.1.2.0.21
rmHumidityLowCritical
NOTIFICATION-TYPE
CRITICAL: The humidity of sensor was lower than low critical set point.
1.3.6.1.4.1.534.6.7.1.2.0.22