ROOMALERT12E-MIB
- Registered at
- 1.3.6.1.4.1.20916.1.9
- Namespace
- avtech
- Source file
ROOMALERT12E-MIB- Digest
sha256:62478bcdb8e6b0d283b91c3da705769dcb32451f5f10311baf1a115e39c06f06
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Counter32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
ROOMALERT12E-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Under this module's arcs
Where the registration tree carries on below this module.
| Arc | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.20916.1.9.1 | sensors |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| avtech OBJECT-IDENTITY | 1.3.6.1.4.1.20916 | |||
| products OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1 | |||
| roomalert12E OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9 | |||
| sensors OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1 | |||
| internal_sen OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.1 | |||
| internal_sen_1 OBJECT-TYPE If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. | 1.3.6.1.4.1.20916.1.9.1.1.1 | INTEGER (0..65535) | read-only | mandatory |
| internal_sen_2 OBJECT-TYPE If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. | 1.3.6.1.4.1.20916.1.9.1.1.2 | INTEGER (0..65535) | read-only | mandatory |
| internal_sen_3 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. | 1.3.6.1.4.1.20916.1.9.1.1.3 | INTEGER (0..65535) | read-only | mandatory |
| internal_sen_4 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. | 1.3.6.1.4.1.20916.1.9.1.1.4 | INTEGER (0..65535) | read-only | mandatory |
| internal_sen_5 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. | 1.3.6.1.4.1.20916.1.9.1.1.5 | INTEGER (0..65535) | read-only | mandatory |
| internal_sen_6 OBJECT-TYPE Represents the sensor's label/ | 1.3.6.1.4.1.20916.1.9.1.1.6 | OCTET STRING | read-only | mandatory |
| digital_sen1 OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.2 | |||
| digital_sen1_1 OBJECT-TYPE If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. | 1.3.6.1.4.1.20916.1.9.1.2.1 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen1_2 OBJECT-TYPE If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. | 1.3.6.1.4.1.20916.1.9.1.2.2 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen1_3 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. | 1.3.6.1.4.1.20916.1.9.1.2.3 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen1_4 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. | 1.3.6.1.4.1.20916.1.9.1.2.4 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen1_5 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. | 1.3.6.1.4.1.20916.1.9.1.2.5 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen1_6 OBJECT-TYPE Represents the sensor's label/ | 1.3.6.1.4.1.20916.1.9.1.2.6 | OCTET STRING | read-only | mandatory |
| digital_sen2 OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.3 | |||
| digital_sen2_1 OBJECT-TYPE If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. | 1.3.6.1.4.1.20916.1.9.1.3.1 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen2_2 OBJECT-TYPE If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. | 1.3.6.1.4.1.20916.1.9.1.3.2 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen2_3 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. | 1.3.6.1.4.1.20916.1.9.1.3.3 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen2_4 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. | 1.3.6.1.4.1.20916.1.9.1.3.4 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen2_5 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. | 1.3.6.1.4.1.20916.1.9.1.3.5 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen2_6 OBJECT-TYPE Represents the sensor's label/ | 1.3.6.1.4.1.20916.1.9.1.3.6 | OCTET STRING | read-only | mandatory |
| digital_sen3 OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.4 | |||
| digital_sen3_1 OBJECT-TYPE If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. | 1.3.6.1.4.1.20916.1.9.1.4.1 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen3_2 OBJECT-TYPE If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. | 1.3.6.1.4.1.20916.1.9.1.4.2 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen3_3 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. | 1.3.6.1.4.1.20916.1.9.1.4.3 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen3_4 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. | 1.3.6.1.4.1.20916.1.9.1.4.4 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen3_5 OBJECT-TYPE If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. | 1.3.6.1.4.1.20916.1.9.1.4.5 | INTEGER (0..65535) | read-only | mandatory |
| digital_sen3_6 OBJECT-TYPE Represents the sensor's label/ | 1.3.6.1.4.1.20916.1.9.1.4.6 | OCTET STRING | read-only | mandatory |
| switch1 OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.5 | |||
| switch_sen1_1 OBJECT-TYPE The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED). | 1.3.6.1.4.1.20916.1.9.1.5.1 | INTEGER (0..1) | read-only | mandatory |
| switch_sen1_2 OBJECT-TYPE The label for switch sensor 1. | 1.3.6.1.4.1.20916.1.9.1.5.2 | OCTET STRING | read-only | mandatory |
| switch2 OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.6 | |||
| switch_sen2 OBJECT-TYPE The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED). | 1.3.6.1.4.1.20916.1.9.1.6.1 | INTEGER (0..1) | read-only | mandatory |
| switch_sen2_2 OBJECT-TYPE The label for switch sensor 2. | 1.3.6.1.4.1.20916.1.9.1.6.2 | OCTET STRING | read-only | mandatory |
| switch3 OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.7 | |||
| switch_sen3 OBJECT-TYPE The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED). | 1.3.6.1.4.1.20916.1.9.1.7.1 | INTEGER (0..1) | read-only | mandatory |
| switch_sen3_2 OBJECT-TYPE The label for switch sensor 3. | 1.3.6.1.4.1.20916.1.9.1.7.2 | OCTET STRING | read-only | mandatory |
| switch4 OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.8 | |||
| switch_sen4 OBJECT-TYPE The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED). | 1.3.6.1.4.1.20916.1.9.1.8.1 | INTEGER (0..1) | read-only | mandatory |
| switch_sen4_2 OBJECT-TYPE The label for switch sensor 4. | 1.3.6.1.4.1.20916.1.9.1.8.2 | OCTET STRING | read-only | mandatory |
| analog OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.9 | |||
| analog_1 OBJECT-TYPE The current status of the Room Alert 12E analog input (0-5VDC). | 1.3.6.1.4.1.20916.1.9.1.9.1 | INTEGER (0..65535) | read-only | mandatory |
| analog_2 OBJECT-TYPE The analog sensor's label. | 1.3.6.1.4.1.20916.1.9.1.9.2 | OCTET STRING | read-only | mandatory |
| relay OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.1.10 | |||
| relay_1 OBJECT-TYPE The current status of the Room Alert 12E relay output. | 1.3.6.1.4.1.20916.1.9.1.10.1 | INTEGER (0..1) | read-write | mandatory |
| relay_2 OBJECT-TYPE The relay output's label. | 1.3.6.1.4.1.20916.1.9.1.10.2 | OCTET STRING | read-only | mandatory |
| lightTower OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.2 | |||
| lightTower_RE OBJECT-TYPE The status of the red LED on the Light Tower. | 1.3.6.1.4.1.20916.1.9.2.1 | INTEGER (0..1) | read-write | mandatory |
| lightTower_OR OBJECT-TYPE The status of the orange LED on the Light Tower. | 1.3.6.1.4.1.20916.1.9.2.2 | INTEGER (0..1) | read-write | mandatory |
| lightTower_GR OBJECT-TYPE The status of the green LED on the Light Tower. | 1.3.6.1.4.1.20916.1.9.2.3 | INTEGER (0..1) | read-write | mandatory |
| lightTower_WH OBJECT-TYPE The status of the white LED on the Light Tower. | 1.3.6.1.4.1.20916.1.9.2.4 | INTEGER (0..1) | read-write | mandatory |
| lightTower_BL OBJECT-TYPE The status of the blue LED on the Light Tower. | 1.3.6.1.4.1.20916.1.9.2.5 | INTEGER (0..1) | read-write | mandatory |
| lightTower_A1 OBJECT-TYPE The status of the 1st audio alarm on the Light Tower. | 1.3.6.1.4.1.20916.1.9.2.6 | INTEGER (0..1) | read-write | mandatory |
| lightTower_A2 OBJECT-TYPE The status of the 2nd audio alarm on the Light Tower. | 1.3.6.1.4.1.20916.1.9.2.7 | INTEGER (0..1) | read-write | mandatory |
| lightTower_RL OBJECT-TYPE The status of the LTA's on-board relay output | 1.3.6.1.4.1.20916.1.9.2.8 | INTEGER (0..1) | read-write | mandatory |
| traps OBJECT-IDENTITY | 1.3.6.1.4.1.20916.1.9.3 | |||
| alarmmessage OBJECT-TYPE Last Alarm Message | 1.3.6.1.4.1.20916.1.9.3.1 | OCTET STRING | read-only | mandatory |
Notifications
| Name | OID | Status |
|---|---|---|
| tempalarm1_12E NOTIFICATION-TYPE A tempalarm1 trap signifies that the current temperature on external sensor 1 is outside the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.1 | |
| room_alert_12E_snmp_trap NOTIFICATION-TYPE A room-alert-12E-snmp-trap indicates that an alarm condition has occurred on the sensor inidcated by the alarmMessage variable. | 1.3.6.1.4.1.20916.1.9.0.2 | |
| tempalarm2_12E NOTIFICATION-TYPE A tempalarm2 trap signifies that the current temperature on external sensor 2 is outside the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.3 | |
| tempclear2_12E NOTIFICATION-TYPE A tempclear2 trap signifies that the current temperature on external sensor 2 has returned to a normal condition and is within the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.4 | |
| tempalarm3_12E NOTIFICATION-TYPE A tempalarm3 trap signifies that the current temperature on external sensor 3 is outside the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.5 | |
| tempclear3_12E NOTIFICATION-TYPE A tempclear3 trap signifies that the current temperature on external sensor 3 has returned to a normal condition and is within the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.6 | |
| humidityalarm1_12E NOTIFICATION-TYPE A humidityalarm1 trap signifies that the current humidity on external sensor 1 is outside the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.7 | |
| humidityclear1_12E NOTIFICATION-TYPE A humidityclear1 trap signifies that the current humidity on external sensor 1 has returned to a normal condition and is within the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.8 | |
| humidityalarm2_12E NOTIFICATION-TYPE A humidityalarm2 trap signifies that the current humidity on external sensor 2 is outside the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.9 | |
| humidityclear2_12E NOTIFICATION-TYPE A humidityclear2 trap signifies that the current humidity on external sensor 2 has returned to a normal condition and is within the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.10 | |
| humidityalarm3_12E NOTIFICATION-TYPE A humidityalarm3 trap signifies that the current humidity on external sensor 3 is outside the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.11 | |
| humidityclear3_12E NOTIFICATION-TYPE A humidityclear3 trap signifies that the current humidity on external sensor 3 has returned to a normal condition and is within the defined high or low threshold. | 1.3.6.1.4.1.20916.1.9.0.12 | |
| switchalarm1_12E NOTIFICATION-TYPE A switchalarm1 trap signifies that switch sensor 1 is in an alarm state. | 1.3.6.1.4.1.20916.1.9.0.13 | |
| switchclear1_12E NOTIFICATION-TYPE A switchclear1 trap signifies that the switch sensor 1 has returned to a normal state. | 1.3.6.1.4.1.20916.1.9.0.14 | |
| switchalarm2_12E NOTIFICATION-TYPE A switchalarm2 trap signifies that switch sensor 2 is in an alarm state. | 1.3.6.1.4.1.20916.1.9.0.15 | |
| switchclear2_12E NOTIFICATION-TYPE A switchclear2 trap signifies that the switch sensor 2 has returned to a normal state. | 1.3.6.1.4.1.20916.1.9.0.16 | |
| switchalarm3_12E NOTIFICATION-TYPE A switchalarm3 trap signifies that switch sensor 3 is in an alarm state. | 1.3.6.1.4.1.20916.1.9.0.17 | |
| switchclear3_12E NOTIFICATION-TYPE A switchclear3 trap signifies that the switch sensor 3 has returned to a normal state. | 1.3.6.1.4.1.20916.1.9.0.18 | |
| switchalarm4_12E NOTIFICATION-TYPE A switchalarm4 trap signifies that switch sensor 4 is in an alarm state. | 1.3.6.1.4.1.20916.1.9.0.19 | |
| switchclear4_12E NOTIFICATION-TYPE A switchclear4 trap signifies that the switch sensor 4 has returned to a normal state. | 1.3.6.1.4.1.20916.1.9.0.20 |