RITTAL-CMC-TC-MIB
- Registered at
- 1.3.6.1.4.1.2606.4
- Namespace
- rittal
- Source file
RITTAL-CMC-TC-MIB- Digest
sha256:b113e19d3fa6038bbd595e4b5ee992eee14893057f1d9961fe98117bae612f89
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-MIB | sysContact, sysDescr, sysLocation, sysName |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
RITTAL-CMC-TC-MIB SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| rittal OBJECT-IDENTITY | 1.3.6.1.4.1.2606 | |||
| cmcTc OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4 | |||
| cmcTcMibRev OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.1 | |||
| cmcTcMibMajRev OBJECT-TYPE The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level. | 1.3.6.1.4.1.2606.4.1.1 | INTEGER (1..65535) | read-only | mandatory |
| cmcTcMibMinRev OBJECT-TYPE The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred. | 1.3.6.1.4.1.2606.4.1.2 | INTEGER (0..65535) | read-only | mandatory |
| cmcTcMibCondition OBJECT-TYPE The overall condition (status) of the system represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on CMC) (4) a major problem (red LED on CMC) (5) configuration of sensor units changed or unit detected (red/yellow/green LED on CMC) | 1.3.6.1.4.1.2606.4.1.3 | INTEGER {other(1), ok(2), degraded(3), failed(4), configChanged(5)} | read-only | mandatory |
| cmcTcStatus OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2 | |||
| cmcTcStatusDeviceCMC OBJECT-TYPE General Status of CMC-TC unit itself (1) failed (2) OK | 1.3.6.1.4.1.2606.4.2.1 | INTEGER {failed(1), ok(2)} | read-only | mandatory |
| cmcTcUnitsConnected OBJECT-TYPE Number of sensor units connected to the CMC, Port 1 to 4 | 1.3.6.1.4.1.2606.4.2.2 | INTEGER | read-only | mandatory |
| cmcTcStatusSensorUnit1 OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.3 | |||
| cmcTcUnit1TypeOfDevice OBJECT-TYPE Type of sensor unit connected to port 1 | 1.3.6.1.4.1.2606.4.2.3.1 | INTEGER {notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13)} | read-only | mandatory |
| cmcTcUnit1Text OBJECT-TYPE Descriptional text for sensor unit connected to port 1 | 1.3.6.1.4.1.2606.4.2.3.2 | DisplayString (SIZE(0..10)) | read-write | mandatory |
| cmcTcUnit1Serial OBJECT-TYPE Serialnumber of sensor unit connected to port 1 | 1.3.6.1.4.1.2606.4.2.3.3 | INTEGER | read-only | mandatory |
| cmcTcUnit1Status OBJECT-TYPE General Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low | 1.3.6.1.4.1.2606.4.2.3.4 | INTEGER {ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8)} | read-only | mandatory |
| cmcTcStatusUnit1Sensors OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.3.5 | |||
| cmcTcUnit1NumberOfSensors OBJECT-TYPE Number of sensors connected to sensor unit 1 | 1.3.6.1.4.1.2606.4.2.3.5.1 | INTEGER | read-only | mandatory |
| cmcTcUnit1SensorTable OBJECT-TYPE Headline of sensor table | 1.3.6.1.4.1.2606.4.2.3.5.2 | not-accessible | mandatory | |
| cmcTcUnit1SensorEntry OBJECT-TYPE Entries of sensor table | 1.3.6.1.4.1.2606.4.2.3.5.2.1 | not-accessible | mandatory | |
| unit1SensorIndex OBJECT-TYPE Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfSensors. | 1.3.6.1.4.1.2606.4.2.3.5.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit1SensorType OBJECT-TYPE Type of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage (OK, NOK) 18: voltage value 19: fan status, from CMC-TC-FAS-Unit 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless | 1.3.6.1.4.1.2606.4.2.3.5.2.1.2 | INTEGER {notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)} | read-only | mandatory |
| unit1SensorText OBJECT-TYPE Descriptional text for each sensor (entry in the table) | 1.3.6.1.4.1.2606.4.2.3.5.2.1.3 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit1SensorStatus OBJECT-TYPE Actual status of the sensor | 1.3.6.1.4.1.2606.4.2.3.5.2.1.4 | INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)} | read-only | mandatory |
| unit1SensorValue OBJECT-TYPE Value of sensor | 1.3.6.1.4.1.2606.4.2.3.5.2.1.5 | INTEGER | read-only | mandatory |
| unit1SensorSetHigh OBJECT-TYPE Value for high setpoint of sensor | 1.3.6.1.4.1.2606.4.2.3.5.2.1.6 | INTEGER | read-write | mandatory |
| unit1SensorSetLow OBJECT-TYPE Value for low setpoint of sensor, also used as alarm delay | 1.3.6.1.4.1.2606.4.2.3.5.2.1.7 | INTEGER | read-write | mandatory |
| unit1SensorSetWarn OBJECT-TYPE Value for warning setpoint of sensor, also used as fan threshold | 1.3.6.1.4.1.2606.4.2.3.5.2.1.8 | INTEGER | read-write | mandatory |
| cmcTcStatusUnit1Outputs OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.3.6 | |||
| cmcTcUnit1NumberOfOutputs OBJECT-TYPE Number of outputs available on sensor unit 1 | 1.3.6.1.4.1.2606.4.2.3.6.1 | INTEGER | read-only | mandatory |
| cmcTcUnit1OutputTable OBJECT-TYPE Headline of output table | 1.3.6.1.4.1.2606.4.2.3.6.2 | not-accessible | mandatory | |
| cmcTcUnit1OutputEntry OBJECT-TYPE Entries of output table | 1.3.6.1.4.1.2606.4.2.3.6.2.1 | not-accessible | mandatory | |
| unit1OutputIndex OBJECT-TYPE Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfOutputs. | 1.3.6.1.4.1.2606.4.2.3.6.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit1OutputType OBJECT-TYPE Type of output which is connected to sensor unit 1 to output[unit1OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, LCP) 15: setpoint temperature monitoring (LCP) 16: hysteresis of setpoint (LCP) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode, LCP 31: min fan speed (fan control), LCP 32: min delta T (fan control), LCP 33: max delta T (fan control), LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187), LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM | 1.3.6.1.4.1.2606.4.2.3.6.2.1.2 | INTEGER {notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)} | read-only | mandatory |
| unit1OutputText OBJECT-TYPE Descriptional text for each output (entry in the table) | 1.3.6.1.4.1.2606.4.2.3.6.2.1.3 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit1OutputStatus OBJECT-TYPE Actual status of the output | 1.3.6.1.4.1.2606.4.2.3.6.2.1.4 | INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)} | read-write | mandatory |
| unit1OutputValue OBJECT-TYPE Value for output | 1.3.6.1.4.1.2606.4.2.3.6.2.1.5 | INTEGER | read-write | mandatory |
| unit1OutputSet OBJECT-TYPE Command for output | 1.3.6.1.4.1.2606.4.2.3.6.2.1.6 | INTEGER {off(1), on(2), lock(3), unlock(4), unlockDelay(5)} | read-write | mandatory |
| unit1OutputConfig OBJECT-TYPE Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control | 1.3.6.1.4.1.2606.4.2.3.6.2.1.7 | INTEGER {disRemote(1), enRemote(2)} | read-write | mandatory |
| unit1OutputDelay OBJECT-TYPE Unsigned Value for delay, after this time the output will fall into the previous state | 1.3.6.1.4.1.2606.4.2.3.6.2.1.8 | INTEGER | read-write | mandatory |
| unit1OutputTimeoutAction OBJECT-TYPE State for output if timeout (RS422) occurs | 1.3.6.1.4.1.2606.4.2.3.6.2.1.9 | INTEGER {stay(1), off(2), on(3)} | read-write | mandatory |
| cmcTcStatusUnit1Msg OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.3.7 | |||
| cmcTcUnit1NumberOfMsgs OBJECT-TYPE Number of messages that can be created with sensor unit 1 | 1.3.6.1.4.1.2606.4.2.3.7.1 | INTEGER | read-only | mandatory |
| cmcTcUnit1MsgTable OBJECT-TYPE Headline of message table | 1.3.6.1.4.1.2606.4.2.3.7.2 | not-accessible | mandatory | |
| cmcTcUnit1MsgEntry OBJECT-TYPE Entries of message table | 1.3.6.1.4.1.2606.4.2.3.7.2.1 | not-accessible | mandatory | |
| unit1MsgIndex OBJECT-TYPE Index for the list of message entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfMsgs. | 1.3.6.1.4.1.2606.4.2.3.7.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit1MsgText OBJECT-TYPE Descriptional text for each message (entry in the table) | 1.3.6.1.4.1.2606.4.2.3.7.2.1.2 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit1MsgStatus OBJECT-TYPE Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor | 1.3.6.1.4.1.2606.4.2.3.7.2.1.3 | INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)} | read-only | mandatory |
| unit1MsgRelay OBJECT-TYPE Setup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay | 1.3.6.1.4.1.2606.4.2.3.7.2.1.4 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit1MsgBeeper OBJECT-TYPE Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm | 1.3.6.1.4.1.2606.4.2.3.7.2.1.5 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit1MsgTrap1 OBJECT-TYPE Trap receiver 1 activated | 1.3.6.1.4.1.2606.4.2.3.7.2.1.6 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit1MsgTrap2 OBJECT-TYPE Trap receiver 2 activated | 1.3.6.1.4.1.2606.4.2.3.7.2.1.7 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit1MsgTrap3 OBJECT-TYPE Trap receiver 3 activated | 1.3.6.1.4.1.2606.4.2.3.7.2.1.8 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit1MsgTrap4 OBJECT-TYPE Trap receiver 4 and Event Logging activated | 1.3.6.1.4.1.2606.4.2.3.7.2.1.9 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit1MsgQuit OBJECT-TYPE Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key | 1.3.6.1.4.1.2606.4.2.3.7.2.1.10 | INTEGER {auto(1), manual(2)} | read-write | mandatory |
| cmcTcStatusSensorUnit2 OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.4 | |||
| cmcTcUnit2TypeOfDevice OBJECT-TYPE Type of sensor unit connected to port 2 | 1.3.6.1.4.1.2606.4.2.4.1 | INTEGER {notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13)} | read-only | mandatory |
| cmcTcUnit2Text OBJECT-TYPE Descriptional text for sensor unit connected to port 2 | 1.3.6.1.4.1.2606.4.2.4.2 | DisplayString (SIZE(0..10)) | read-write | mandatory |
| cmcTcUnit2Serial OBJECT-TYPE Serialnumber of sensor unit connected to port 2 | 1.3.6.1.4.1.2606.4.2.4.3 | INTEGER | read-only | mandatory |
| cmcTcUnit2Status OBJECT-TYPE General Status sensor unit connected to port 2 (1) OK (2) error (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required (6) sensor unit detected, needs to be confirmed (8) supply voltage is too low | 1.3.6.1.4.1.2606.4.2.4.4 | INTEGER {ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8)} | read-only | mandatory |
| cmcTcStatusUnit2Sensors OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.4.5 | |||
| cmcTcUnit2NumberOfSensors OBJECT-TYPE Number of sensors connected to sensor unit 2 | 1.3.6.1.4.1.2606.4.2.4.5.1 | INTEGER | read-only | mandatory |
| cmcTcUnit2SensorTable OBJECT-TYPE Headline of sensor table | 1.3.6.1.4.1.2606.4.2.4.5.2 | not-accessible | mandatory | |
| cmcTcUnit2SensorEntry OBJECT-TYPE Entries of sensor table | 1.3.6.1.4.1.2606.4.2.4.5.2.1 | not-accessible | mandatory | |
| unit2SensorIndex OBJECT-TYPE Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfSensors. | 1.3.6.1.4.1.2606.4.2.4.5.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit2SensorType OBJECT-TYPE Type of sensor which is connected to sensor unit 2 to sensor[unit2SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless | 1.3.6.1.4.1.2606.4.2.4.5.2.1.2 | INTEGER {notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)} | read-only | mandatory |
| unit2SensorText OBJECT-TYPE Descriptional text for each sensor (entry in the table) | 1.3.6.1.4.1.2606.4.2.4.5.2.1.3 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit2SensorStatus OBJECT-TYPE Actual status of the sensor | 1.3.6.1.4.1.2606.4.2.4.5.2.1.4 | INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)} | read-only | mandatory |
| unit2SensorValue OBJECT-TYPE Value of sensor | 1.3.6.1.4.1.2606.4.2.4.5.2.1.5 | INTEGER | read-only | mandatory |
| unit2SensorSetHigh OBJECT-TYPE Value for high setpoint of sensor | 1.3.6.1.4.1.2606.4.2.4.5.2.1.6 | INTEGER | read-write | mandatory |
| unit2SensorSetLow OBJECT-TYPE Value for low setpoint of sensor, also used as alarm delay | 1.3.6.1.4.1.2606.4.2.4.5.2.1.7 | INTEGER | read-write | mandatory |
| unit2SensorSetWarn OBJECT-TYPE Value for warning setpoint of sensor, also used as fan threshold | 1.3.6.1.4.1.2606.4.2.4.5.2.1.8 | INTEGER | read-write | mandatory |
| cmcTcStatusUnit2Outputs OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.4.6 | |||
| cmcTcUnit2NumberOfOutputs OBJECT-TYPE Number of outputs available on sensor unit 2 | 1.3.6.1.4.1.2606.4.2.4.6.1 | INTEGER | read-only | mandatory |
| cmcTcUnit2OutputTable OBJECT-TYPE Headline of output table | 1.3.6.1.4.1.2606.4.2.4.6.2 | not-accessible | mandatory | |
| cmcTcUnit2OutputEntry OBJECT-TYPE Entries of output table | 1.3.6.1.4.1.2606.4.2.4.6.2.1 | not-accessible | mandatory | |
| unit2OutputIndex OBJECT-TYPE Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfOutputs. | 1.3.6.1.4.1.2606.4.2.4.6.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit2OutputType OBJECT-TYPE Type of output which is connected to sensor unit 2 to output[unit2OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM | 1.3.6.1.4.1.2606.4.2.4.6.2.1.2 | INTEGER {notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)} | read-only | mandatory |
| unit2OutputText OBJECT-TYPE Descriptional text for each output (entry in the table) | 1.3.6.1.4.1.2606.4.2.4.6.2.1.3 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit2OutputStatus OBJECT-TYPE Actual status of the output | 1.3.6.1.4.1.2606.4.2.4.6.2.1.4 | INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)} | read-write | mandatory |
| unit2OutputValue OBJECT-TYPE Signed value for output | 1.3.6.1.4.1.2606.4.2.4.6.2.1.5 | INTEGER | read-write | mandatory |
| unit2OutputSet OBJECT-TYPE Command for output | 1.3.6.1.4.1.2606.4.2.4.6.2.1.6 | INTEGER {off(1), on(2), lock(3), unlock(4), unlockDelay(5)} | read-write | mandatory |
| unit2OutputConfig OBJECT-TYPE Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control | 1.3.6.1.4.1.2606.4.2.4.6.2.1.7 | INTEGER {disRemote(1), enRemote(2)} | read-write | mandatory |
| unit2OutputDelay OBJECT-TYPE Unsigned Value for delay, after this time the output will fall into the previous state | 1.3.6.1.4.1.2606.4.2.4.6.2.1.8 | INTEGER | read-write | mandatory |
| unit2OutputTimeoutAction OBJECT-TYPE State for output if timeout (RS422) occurs | 1.3.6.1.4.1.2606.4.2.4.6.2.1.9 | INTEGER {stay(1), off(2), on(3)} | read-write | mandatory |
| cmcTcStatusUnit2Msg OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.4.7 | |||
| cmcTcUnit2NumberOfMsgs OBJECT-TYPE Number of alarms that can be created with sensor unit 2 | 1.3.6.1.4.1.2606.4.2.4.7.1 | INTEGER | read-only | mandatory |
| cmcTcUnit2MsgTable OBJECT-TYPE Headline of message table | 1.3.6.1.4.1.2606.4.2.4.7.2 | not-accessible | mandatory | |
| cmcTcUnit2MsgEntry OBJECT-TYPE Entries of message table | 1.3.6.1.4.1.2606.4.2.4.7.2.1 | not-accessible | mandatory | |
| unit2MsgIndex OBJECT-TYPE Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfMsgs. | 1.3.6.1.4.1.2606.4.2.4.7.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit2MsgText OBJECT-TYPE Descriptional text for each message (entry in the table) | 1.3.6.1.4.1.2606.4.2.4.7.2.1.2 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit2MsgStatus OBJECT-TYPE Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor | 1.3.6.1.4.1.2606.4.2.4.7.2.1.3 | INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)} | read-only | mandatory |
| unit2MsgRelay OBJECT-TYPE Setup of Alarm relay for this alarm 2: no switching of alarm relay 1: switching of alarm relay | 1.3.6.1.4.1.2606.4.2.4.7.2.1.4 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit2MsgBeeper OBJECT-TYPE Setup of Alarm beeper for this alarm 2: no audible alarm 1: audible alarm | 1.3.6.1.4.1.2606.4.2.4.7.2.1.5 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit2MsgTrap1 OBJECT-TYPE Trap receiver 1 activated | 1.3.6.1.4.1.2606.4.2.4.7.2.1.6 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit2MsgTrap2 OBJECT-TYPE Trap receiver 2 activated | 1.3.6.1.4.1.2606.4.2.4.7.2.1.7 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit2MsgTrap3 OBJECT-TYPE Trap receiver 3 activated | 1.3.6.1.4.1.2606.4.2.4.7.2.1.8 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit2MsgTrap4 OBJECT-TYPE Trap receiver 4 and Event Logging activated | 1.3.6.1.4.1.2606.4.2.4.7.2.1.9 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit2MsgQuit OBJECT-TYPE Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key | 1.3.6.1.4.1.2606.4.2.4.7.2.1.10 | INTEGER {auto(1), manual(2)} | read-write | mandatory |
| cmcTcStatusSensorUnit3 OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.5 | |||
| cmcTcUnit3TypeOfDevice OBJECT-TYPE Type of sensor unit connected to port 3 | 1.3.6.1.4.1.2606.4.2.5.1 | INTEGER {notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13)} | read-only | mandatory |
| cmcTcUnit3Text OBJECT-TYPE Descriptional text for sensor unit connected to port 3 | 1.3.6.1.4.1.2606.4.2.5.2 | DisplayString (SIZE(0..10)) | read-write | mandatory |
| cmcTcUnit3Serial OBJECT-TYPE Serialnumber of sensor unit connected to port 3 | 1.3.6.1.4.1.2606.4.2.5.3 | INTEGER | read-only | mandatory |
| cmcTcUnit3Status OBJECT-TYPE General Status sensor unit connected to port 3 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low | 1.3.6.1.4.1.2606.4.2.5.4 | INTEGER {ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8)} | read-only | mandatory |
| cmcTcStatusUnit3Sensors OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.5.5 | |||
| cmcTcUnit3NumberOfSensors OBJECT-TYPE Number of sensors connected to sensor unit 3 | 1.3.6.1.4.1.2606.4.2.5.5.1 | INTEGER | read-only | mandatory |
| cmcTcUnit3SensorTable OBJECT-TYPE Headline of sensor table | 1.3.6.1.4.1.2606.4.2.5.5.2 | not-accessible | mandatory | |
| cmcTcUnit3SensorEntry OBJECT-TYPE Entries of sensor table | 1.3.6.1.4.1.2606.4.2.5.5.2.1 | not-accessible | mandatory | |
| unit3SensorIndex OBJECT-TYPE Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfSensors. | 1.3.6.1.4.1.2606.4.2.5.5.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit3SensorType OBJECT-TYPE Type of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless | 1.3.6.1.4.1.2606.4.2.5.5.2.1.2 | INTEGER {notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)} | read-only | mandatory |
| unit3SensorText OBJECT-TYPE Descriptional text for each sensor (entry in the table) | 1.3.6.1.4.1.2606.4.2.5.5.2.1.3 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit3SensorStatus OBJECT-TYPE Actual status of the sensor | 1.3.6.1.4.1.2606.4.2.5.5.2.1.4 | INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)} | read-only | mandatory |
| unit3SensorValue OBJECT-TYPE Value of sensor | 1.3.6.1.4.1.2606.4.2.5.5.2.1.5 | INTEGER | read-only | mandatory |
| unit3SensorSetHigh OBJECT-TYPE Value for high setpoint of sensor | 1.3.6.1.4.1.2606.4.2.5.5.2.1.6 | INTEGER | read-write | mandatory |
| unit3SensorSetLow OBJECT-TYPE Value for low setpoint of sensor | 1.3.6.1.4.1.2606.4.2.5.5.2.1.7 | INTEGER | read-write | mandatory |
| unit3SensorSetWarn OBJECT-TYPE Value for warning setpoint of sensor, also used as fan threshold | 1.3.6.1.4.1.2606.4.2.5.5.2.1.8 | INTEGER | read-write | mandatory |
| cmcTcStatusUnit3Outputs OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.5.6 | |||
| cmcTcUnit3NumberOfOutputs OBJECT-TYPE Number of outputs available on sensor unit 3 | 1.3.6.1.4.1.2606.4.2.5.6.1 | INTEGER | read-only | mandatory |
| cmcTcUnit3OutputTable OBJECT-TYPE Headline of output table | 1.3.6.1.4.1.2606.4.2.5.6.2 | not-accessible | mandatory | |
| cmcTcUnit3OutputEntry OBJECT-TYPE Entries of output table | 1.3.6.1.4.1.2606.4.2.5.6.2.1 | not-accessible | mandatory | |
| unit3OutputIndex OBJECT-TYPE Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfOutputs. | 1.3.6.1.4.1.2606.4.2.5.6.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit3OutputType OBJECT-TYPE Type of output which is connected to sensor unit 3 to output[unit3OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM | 1.3.6.1.4.1.2606.4.2.5.6.2.1.2 | INTEGER {notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)} | read-only | mandatory |
| unit3OutputText OBJECT-TYPE Descriptional text for each output (entry in the table) | 1.3.6.1.4.1.2606.4.2.5.6.2.1.3 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit3OutputStatus OBJECT-TYPE Actual status of the output | 1.3.6.1.4.1.2606.4.2.5.6.2.1.4 | INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)} | read-write | mandatory |
| unit3OutputValue OBJECT-TYPE Value for output | 1.3.6.1.4.1.2606.4.2.5.6.2.1.5 | INTEGER | read-write | mandatory |
| unit3OutputSet OBJECT-TYPE Command for output | 1.3.6.1.4.1.2606.4.2.5.6.2.1.6 | INTEGER {off(1), on(2), lock(3), unlock(4), unlockDelay(5)} | read-write | mandatory |
| unit3OutputConfig OBJECT-TYPE Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control | 1.3.6.1.4.1.2606.4.2.5.6.2.1.7 | INTEGER {disRemote(1), enRemote(2)} | read-write | mandatory |
| unit3OutputDelay OBJECT-TYPE Unsigned Value for delay, after this time the output will fall into the previous state | 1.3.6.1.4.1.2606.4.2.5.6.2.1.8 | INTEGER | read-write | mandatory |
| unit3OutputTimeoutAction OBJECT-TYPE State for output if timeout (RS422) occurs | 1.3.6.1.4.1.2606.4.2.5.6.2.1.9 | INTEGER {stay(1), off(2), on(3)} | read-write | mandatory |
| cmcTcStatusUnit3Msg OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.5.7 | |||
| cmcTcUnit3NumberOfMsgs OBJECT-TYPE Number of alarms that can be created with sensor unit 3 | 1.3.6.1.4.1.2606.4.2.5.7.1 | INTEGER | read-only | mandatory |
| cmcTcUnit3MsgTable OBJECT-TYPE Headline of message table | 1.3.6.1.4.1.2606.4.2.5.7.2 | not-accessible | mandatory | |
| cmcTcUnit3MsgEntry OBJECT-TYPE Entries of message table | 1.3.6.1.4.1.2606.4.2.5.7.2.1 | not-accessible | mandatory | |
| unit3MsgIndex OBJECT-TYPE Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfMsgs. | 1.3.6.1.4.1.2606.4.2.5.7.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit3MsgText OBJECT-TYPE Descriptional text for each message (entry in the table) | 1.3.6.1.4.1.2606.4.2.5.7.2.1.2 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit3MsgStatus OBJECT-TYPE Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor | 1.3.6.1.4.1.2606.4.2.5.7.2.1.3 | INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)} | read-only | mandatory |
| unit3MsgRelay OBJECT-TYPE Setup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay | 1.3.6.1.4.1.2606.4.2.5.7.2.1.4 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit3MsgBeeper OBJECT-TYPE Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm | 1.3.6.1.4.1.2606.4.2.5.7.2.1.5 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit3MsgTrap1 OBJECT-TYPE Trap receiver 1 activated | 1.3.6.1.4.1.2606.4.2.5.7.2.1.6 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit3MsgTrap2 OBJECT-TYPE Trap receiver 2 activated | 1.3.6.1.4.1.2606.4.2.5.7.2.1.7 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit3MsgTrap3 OBJECT-TYPE Trap receiver 3 activated | 1.3.6.1.4.1.2606.4.2.5.7.2.1.8 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit3MsgTrap4 OBJECT-TYPE Trap receiver 4 and Event Logging activated | 1.3.6.1.4.1.2606.4.2.5.7.2.1.9 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit3MsgQuit OBJECT-TYPE Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key | 1.3.6.1.4.1.2606.4.2.5.7.2.1.10 | INTEGER {auto(1), manual(2)} | read-write | mandatory |
| cmcTcStatusSensorUnit4 OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.6 | |||
| cmcTcUnit4TypeOfDevice OBJECT-TYPE Type of sensor unit connected to port 4 | 1.3.6.1.4.1.2606.4.2.6.1 | INTEGER {notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13)} | read-only | mandatory |
| cmcTcUnit4Text OBJECT-TYPE Descriptional text for sensor unit connected to port 4 | 1.3.6.1.4.1.2606.4.2.6.2 | DisplayString (SIZE(0..10)) | read-write | mandatory |
| cmcTcUnit4Serial OBJECT-TYPE Serialnumber of sensor unit connected to port 4 | 1.3.6.1.4.1.2606.4.2.6.3 | INTEGER | read-only | mandatory |
| cmcTcUnit4Status OBJECT-TYPE General Status sensor unit connected to port 4 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low | 1.3.6.1.4.1.2606.4.2.6.4 | INTEGER {ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8)} | read-only | mandatory |
| cmcTcStatusUnit4Sensors OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.6.5 | |||
| cmcTcUnit4NumberOfSensors OBJECT-TYPE Number of sensors connected to sensor unit 4 | 1.3.6.1.4.1.2606.4.2.6.5.1 | INTEGER | read-only | mandatory |
| cmcTcUnit4SensorTable OBJECT-TYPE Headline of sensor table | 1.3.6.1.4.1.2606.4.2.6.5.2 | not-accessible | mandatory | |
| cmcTcUnit4SensorEntry OBJECT-TYPE Entries of sensor table | 1.3.6.1.4.1.2606.4.2.6.5.2.1 | not-accessible | mandatory | |
| unit4SensorIndex OBJECT-TYPE Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfSensors. | 1.3.6.1.4.1.2606.4.2.6.5.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit4SensorType OBJECT-TYPE Type of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless | 1.3.6.1.4.1.2606.4.2.6.5.2.1.2 | INTEGER {notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)} | read-only | mandatory |
| unit4SensorText OBJECT-TYPE Descriptional text for each sensor (entry in the table) | 1.3.6.1.4.1.2606.4.2.6.5.2.1.3 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit4SensorStatus OBJECT-TYPE Actual status of the sensor | 1.3.6.1.4.1.2606.4.2.6.5.2.1.4 | INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)} | read-only | mandatory |
| unit4SensorValue OBJECT-TYPE Value of sensor | 1.3.6.1.4.1.2606.4.2.6.5.2.1.5 | INTEGER | read-only | mandatory |
| unit4SensorSetHigh OBJECT-TYPE Value for high setpoint of sensor | 1.3.6.1.4.1.2606.4.2.6.5.2.1.6 | INTEGER | read-write | mandatory |
| unit4SensorSetLow OBJECT-TYPE Value for low setpoint of sensor | 1.3.6.1.4.1.2606.4.2.6.5.2.1.7 | INTEGER | read-write | mandatory |
| unit4SensorSetWarn OBJECT-TYPE Value for warning setpoint of sensor, also used as fan threshold | 1.3.6.1.4.1.2606.4.2.6.5.2.1.8 | INTEGER | read-write | mandatory |
| cmcTcStatusUnit4Outputs OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.6.6 | |||
| cmcTcUnit4NumberOfOutputs OBJECT-TYPE Number of outputs available on sensor unit 4 | 1.3.6.1.4.1.2606.4.2.6.6.1 | INTEGER | read-only | mandatory |
| cmcTcUnit4OutputTable OBJECT-TYPE Headline of output table | 1.3.6.1.4.1.2606.4.2.6.6.2 | not-accessible | mandatory | |
| cmcTcUnit4OutputEntry OBJECT-TYPE Entries of output table | 1.3.6.1.4.1.2606.4.2.6.6.2.1 | not-accessible | mandatory | |
| unit4OutputIndex OBJECT-TYPE Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfOutputs. | 1.3.6.1.4.1.2606.4.2.6.6.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit4OutputType OBJECT-TYPE Type of output which is connected to sensor unit 4 to output[unit4OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM | 1.3.6.1.4.1.2606.4.2.6.6.2.1.2 | INTEGER {notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)} | read-only | mandatory |
| unit4OutputText OBJECT-TYPE Descriptional text for each output (entry in the table) | 1.3.6.1.4.1.2606.4.2.6.6.2.1.3 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit4OutputStatus OBJECT-TYPE Actual status of the output | 1.3.6.1.4.1.2606.4.2.6.6.2.1.4 | INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)} | read-write | mandatory |
| unit4OutputValue OBJECT-TYPE Value for output | 1.3.6.1.4.1.2606.4.2.6.6.2.1.5 | INTEGER | read-write | mandatory |
| unit4OutputSet OBJECT-TYPE Command for output | 1.3.6.1.4.1.2606.4.2.6.6.2.1.6 | INTEGER {off(1), on(2), lock(3), unlock(4), unlockDelay(5)} | read-write | mandatory |
| unit4OutputConfig OBJECT-TYPE Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control | 1.3.6.1.4.1.2606.4.2.6.6.2.1.7 | INTEGER {disRemote(1), enRemote(2)} | read-write | mandatory |
| unit4OutputDelay OBJECT-TYPE Unsigned Value for delay, after this time the output will fall into the previous state | 1.3.6.1.4.1.2606.4.2.6.6.2.1.8 | INTEGER | read-write | mandatory |
| unit4OutputTimeoutAction OBJECT-TYPE State for output if timeout (RS422) occurs | 1.3.6.1.4.1.2606.4.2.6.6.2.1.9 | INTEGER {stay(1), off(2), on(3)} | read-write | mandatory |
| cmcTcStatusUnit4Msg OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.6.7 | |||
| cmcTcUnit4NumberOfMsgs OBJECT-TYPE Number of alarms that can be created with sensor unit 4 | 1.3.6.1.4.1.2606.4.2.6.7.1 | INTEGER | read-only | mandatory |
| cmcTcUnit4MsgTable OBJECT-TYPE Headline of message table | 1.3.6.1.4.1.2606.4.2.6.7.2 | not-accessible | mandatory | |
| cmcTcUnit4MsgEntry OBJECT-TYPE Entries of message table | 1.3.6.1.4.1.2606.4.2.6.7.2.1 | not-accessible | mandatory | |
| unit4MsgIndex OBJECT-TYPE Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfMsgs. | 1.3.6.1.4.1.2606.4.2.6.7.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| unit4MsgText OBJECT-TYPE Descriptional text for each message (entry in the table) | 1.3.6.1.4.1.2606.4.2.6.7.2.1.2 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| unit4MsgStatus OBJECT-TYPE Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor | 1.3.6.1.4.1.2606.4.2.6.7.2.1.3 | INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)} | read-only | mandatory |
| unit4MsgRelay OBJECT-TYPE Setup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay | 1.3.6.1.4.1.2606.4.2.6.7.2.1.4 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit4MsgBeeper OBJECT-TYPE Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm | 1.3.6.1.4.1.2606.4.2.6.7.2.1.5 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit4MsgTrap1 OBJECT-TYPE Trap receiver 1 activated | 1.3.6.1.4.1.2606.4.2.6.7.2.1.6 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit4MsgTrap2 OBJECT-TYPE Trap receiver 2 activated | 1.3.6.1.4.1.2606.4.2.6.7.2.1.7 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit4MsgTrap3 OBJECT-TYPE Trap receiver 3 activated | 1.3.6.1.4.1.2606.4.2.6.7.2.1.8 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit4MsgTrap4 OBJECT-TYPE Trap receiver 4 and Event Logging activated | 1.3.6.1.4.1.2606.4.2.6.7.2.1.9 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| unit4MsgQuit OBJECT-TYPE Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key | 1.3.6.1.4.1.2606.4.2.6.7.2.1.10 | INTEGER {auto(1), manual(2)} | read-write | mandatory |
| cmcTcStatusExtUnit OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.2.7 | |||
| cmcTcValuesRelay OBJECT-TYPE Setup of Alarm relay for alarm ext. unit(s) 1: no switching of alarm relay 2: switching of alarm relay | 1.3.6.1.4.1.2606.4.2.7.1 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| cmcTcValuesBeeper OBJECT-TYPE Setup of Alarm beeper for alarm ext. unit(s) 1: no audible alarm 2: audible alarm | 1.3.6.1.4.1.2606.4.2.7.2 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| cmcTcValuesTrap1 OBJECT-TYPE Trap receiver 1 activated | 1.3.6.1.4.1.2606.4.2.7.3 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| cmcTcValuesTrap2 OBJECT-TYPE Trap receiver 2 activated | 1.3.6.1.4.1.2606.4.2.7.4 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| cmcTcValuesTrap3 OBJECT-TYPE Trap receiver 3 activated | 1.3.6.1.4.1.2606.4.2.7.5 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| cmcTcValuesTrap4 OBJECT-TYPE Trap receiver 4 and Event Logging activated | 1.3.6.1.4.1.2606.4.2.7.6 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| cmcTcNumberOfValues OBJECT-TYPE Number of values availabel on extension units connected to the CMC | 1.3.6.1.4.1.2606.4.2.7.7 | INTEGER | read-only | mandatory |
| cmcTcValuesTable OBJECT-TYPE Headline of values-table | 1.3.6.1.4.1.2606.4.2.7.8 | not-accessible | mandatory | |
| cmcTcValuesEntry OBJECT-TYPE Entries of values-table | 1.3.6.1.4.1.2606.4.2.7.8.1 | not-accessible | mandatory | |
| valuesIndex OBJECT-TYPE Index for the list of value entries. Its value ranges between 1 and the value of cmcTcNumberOfValues. | 1.3.6.1.4.1.2606.4.2.7.8.1.1 | INTEGER (1..65535) | read-only | mandatory |
| valuesText OBJECT-TYPE Descriptional text for each value (entry in the table) of the extension card | 1.3.6.1.4.1.2606.4.2.7.8.1.2 | DisplayString (SIZE(0..20)) | read-write | mandatory |
| valuesStatus OBJECT-TYPE Actual status of the value of the extension card | 1.3.6.1.4.1.2606.4.2.7.8.1.3 | INTEGER {notAvail(1), lost(2), changed(3), ok(4), tooLow(5), tooHigh(6), error(7)} | read-only | mandatory |
| valuesValue OBJECT-TYPE Value of sensor | 1.3.6.1.4.1.2606.4.2.7.8.1.4 | INTEGER | read-only | mandatory |
| valuesSetHigh OBJECT-TYPE Value for high setpoint of sensor | 1.3.6.1.4.1.2606.4.2.7.8.1.5 | INTEGER | read-write | mandatory |
| valuesSetLow OBJECT-TYPE Value for low setpoint of sensor | 1.3.6.1.4.1.2606.4.2.7.8.1.6 | INTEGER | read-write | mandatory |
| cmcTcSetup OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.3 | |||
| cmcTcSetupGeneral OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.3.1 | |||
| cmcTcSetTempUnit OBJECT-TYPE Unit of all temperature values and setpoints, Celsius or Fahrenheit | 1.3.6.1.4.1.2606.4.3.1.1 | INTEGER {celsius(1), fahrenheit(2)} | read-write | mandatory |
| cmcTcSetBeeper OBJECT-TYPE Audible alarm in CMC-TC unit: (2): beeper is on (1): beeper is off (general) | 1.3.6.1.4.1.2606.4.3.1.2 | INTEGER {off(1), on(2)} | read-write | mandatory |
| cmcTcQuitRelay OBJECT-TYPE Enable or disable acknowledging currently active alarm relay (with 'C' on CMC-TC). | 1.3.6.1.4.1.2606.4.3.1.3 | INTEGER {disabled(1), enabled(2)} | read-write | mandatory |
| cmcTcLogicRelay OBJECT-TYPE Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay off (general) | 1.3.6.1.4.1.2606.4.3.1.4 | INTEGER {closeAtAlarm(1), openAtAlarm(2), off(3)} | read-write | mandatory |
| cmcTcWebAccess OBJECT-TYPE Web access via HTTP: (1) view only (2) full Access, read and set (3) Web disabled (general) | 1.3.6.1.4.1.2606.4.3.1.5 | INTEGER {viewOnly(1), fullAccess(2), off(3)} | read-write | mandatory |
| cmcTcSetupDate OBJECT-TYPE actual Date in format DD.MM.YYYY | 1.3.6.1.4.1.2606.4.3.1.6 | DisplayString (SIZE(0..10)) | read-write | mandatory |
| cmcTcSetupTime OBJECT-TYPE actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59) | 1.3.6.1.4.1.2606.4.3.1.7 | DisplayString (SIZE(0..8)) | read-write | mandatory |
| cmcTcTimerTable1 OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.3.1.8 | |||
| cmcTcTimerNumber OBJECT-TYPE Number of value-table entries=number of outlets available on this unit | 1.3.6.1.4.1.2606.4.3.1.8.1 | INTEGER | read-only | mandatory |
| cmcTcTimerTable OBJECT-TYPE Headline of status-table | 1.3.6.1.4.1.2606.4.3.1.8.2 | not-accessible | mandatory | |
| cmcTcTimerEntry OBJECT-TYPE Entries of timer-table | 1.3.6.1.4.1.2606.4.3.1.8.2.1 | not-accessible | mandatory | |
| cmcTcTimerIndex OBJECT-TYPE Index for the list of timer entries. Its value ranges between 1 and the value of cmcTcTimerNumber. | 1.3.6.1.4.1.2606.4.3.1.8.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| cmcTcTimerStatus OBJECT-TYPE Actual status of the timer | 1.3.6.1.4.1.2606.4.3.1.8.2.1.2 | INTEGER {switchedOff(1), switchedOn(2), noTime(3)} | read-only | mandatory |
| cmcTcTimerDayOfWeek OBJECT-TYPE Selection of day of week for timer to switch | 1.3.6.1.4.1.2606.4.3.1.8.2.1.3 | INTEGER {sun(1), mon(2), tue(3), wed(4), thu(5), fri(6), sat(7), sat-sun(8), mon-fri(9), mon-sun(10)} | read-write | mandatory |
| cmcTcTimeOn OBJECT-TYPE Time to switch on current function, Format: HH:MM | 1.3.6.1.4.1.2606.4.3.1.8.2.1.4 | DisplayString (SIZE(0..5)) | read-write | mandatory |
| cmcTcTimeOff OBJECT-TYPE Time to switch off current function, Format: HH:MM | 1.3.6.1.4.1.2606.4.3.1.8.2.1.5 | DisplayString (SIZE(0..5)) | read-write | mandatory |
| cmcTcTimeControl OBJECT-TYPE Control via RTC | 1.3.6.1.4.1.2606.4.3.1.8.2.1.6 | INTEGER {disabled(1), enabled(2)} | read-write | mandatory |
| cmcTcTimerFunction OBJECT-TYPE Function which is controlled via timer 1: unlock via keypad 1 on unit 1 or remote input lock 1 is disabled 2: unlock via keypad 2 on unit 1 or remote input lock 2 is disabled 3 unlock via keypad 1 on unit 2 or remote input lock 1 is disabled 4: unlock via keypad 2 on unit 2 or remote input lock 2 is disabled 5: unlock via keypad 1 on unit 3 or remote input lock 1 is disabled 6: unlock via keypad 2 on unit 3 or remote input lock 2 is disabled 7: unlock via keypad 1 on unit 4 or remote input lock 1 is disabled 8: unlock via keypad 2 on unit 4 or remote input lock 2 is disabled 9: Lock of door 1 on unit 1 will be unlocked 10: Lock of door 2 on unit 1 will be unlocked 11: Lock of door 1 on unit 2 will be unlocked 12: Lock of door 2 on unit 2 will be unlocked 13: Lock of door 1 on unit 3 will be unlocked 14: Lock of door 2 on unit 3 will be unlocked 15: Lock of door 1 on unit 4 will be unlocked 16: Lock of door 2 on unit 4 will be unlocked 17-20: sending Traps to this Trap receiver will be disabled 21: sending SMS will be disabled generally 22-25: Scheduled alarm off 26-29: sending SMS to phone number 1..4 will be disabled | 1.3.6.1.4.1.2606.4.3.1.8.2.1.7 | INTEGER {disKeypad1-1(1), disKeypad2-1(2), disKeypad1-2(3), disKeypad2-2(4), disKeypad1-3(5), disKeypad2-3(6), disKeypad1-4(7), disKeypad2-4(8), unlDoor1-1(9), unlDoor2-1(10), unlDoor1-2(11), unlDoor2-2(12), unlDoor1-3(13), unlDoor2-3(14), unlDoor1-4(15), unlDoor2-5(16), disTrapRec1(17), disTrapRec2(18), disTrapRec3(19), disTrapRec4(20), disSMS(21), schedule1(22), schedule2(23), schedule3(24), schedule4(25), disSMS1(26), disSMS2(27), disSMS3(28), disSMS4(29)} | read-write | mandatory |
| cmcTcTrapControl OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.4 | |||
| cmcTcTraps OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.4.7 | |||
| cmcTcTraptableNumber OBJECT-TYPE Number of trapTable entries. The number of trap-receiver | 1.3.6.1.4.1.2606.4.4.7.1 | INTEGER | read-only | mandatory |
| cmcTcTrapTableTable OBJECT-TYPE A list of trap-receiver entries | 1.3.6.1.4.1.2606.4.4.7.2 | not-accessible | mandatory | |
| cmcTcTrapTableEntry OBJECT-TYPE Entries of trapTable | 1.3.6.1.4.1.2606.4.4.7.2.1 | not-accessible | mandatory | |
| trapIndex OBJECT-TYPE Index for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumber | 1.3.6.1.4.1.2606.4.4.7.2.1.1 | INTEGER (1..65535) | read-only | mandatory |
| trapStatus OBJECT-TYPE Enable or disable trap receiver | 1.3.6.1.4.1.2606.4.4.7.2.1.2 | INTEGER {disabled(1), enabled(2)} | read-write | mandatory |
| trapIPaddress OBJECT-TYPE IP-address of trap-receiver | 1.3.6.1.4.1.2606.4.4.7.2.1.3 | DisplayString (SIZE(0..15)) | read-write | mandatory |
| cmcTcControl OBJECT-IDENTITY | 1.3.6.1.4.1.2606.4.5 | |||
| cmcTcQuitUnit OBJECT-TYPE Command to quit (acknowledge) alarms of CMC-TC unit. Setting to 'quit' (2) will have same result as pressing 'C' on Units. Variable is automatically set back to 'noQuit' (1). | 1.3.6.1.4.1.2606.4.5.1 | INTEGER {noQuit(1), quit(2)} | read-write | mandatory |
Notifications
| Name | OID | Status |
|---|---|---|
| alarmSensorUnit1 NOTIFICATION-TYPE Alarm of sensor unit 1 | 1.3.6.1.4.1.2606.4.0.1 | |
| alarmSensorUnit2 NOTIFICATION-TYPE Alarm of sensor unit 2 | 1.3.6.1.4.1.2606.4.0.2 | |
| alarmSensorUnit3 NOTIFICATION-TYPE Alarm of sensor unit 3 | 1.3.6.1.4.1.2606.4.0.3 | |
| alarmSensorUnit4 NOTIFICATION-TYPE Alarm of sensor unit 4 | 1.3.6.1.4.1.2606.4.0.4 | |
| alarmUnit1 NOTIFICATION-TYPE Alarm of unit 1 | 1.3.6.1.4.1.2606.4.0.5 | |
| alarmUnit2 NOTIFICATION-TYPE Alarm of unit 2 | 1.3.6.1.4.1.2606.4.0.6 | |
| alarmUnit3 NOTIFICATION-TYPE Alarm of unit 3 | 1.3.6.1.4.1.2606.4.0.7 | |
| alarmUnit4 NOTIFICATION-TYPE Alarm of unit 4 | 1.3.6.1.4.1.2606.4.0.8 | |
| alarmValues NOTIFICATION-TYPE Alarm of values measured by external card | 1.3.6.1.4.1.2606.4.0.9 | |
| configChanged NOTIFICATION-TYPE The configuration of the cmc has changed, this trap is send if new setup is saved. Configuration can be changed by Terminal, Telnet, Web or SNMP *** NOT IMPLEMENTED *** | 1.3.6.1.4.1.2606.4.0.10 |