MIBs Depot

RITTAL-CMC-TC-MIB

Registered at
1.3.6.1.4.1.2606.4
Namespace
rittal
Source file
RITTAL-CMC-TC-MIB
Digest
sha256:b113e19d3fa6038bbd595e4b5ee992eee14893057f1d9961fe98117bae612f89

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-MIBsysContact, sysDescr, sysLocation, sysName
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

RITTAL-CMC-TC-MIB
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
rittal
OBJECT-IDENTITY
1.3.6.1.4.1.2606
cmcTc
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4
cmcTcMibRev
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.1
cmcTcMibMajRev
OBJECT-TYPE
The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level.
1.3.6.1.4.1.2606.4.1.1INTEGER (1..65535)read-onlymandatory
cmcTcMibMinRev
OBJECT-TYPE
The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.
1.3.6.1.4.1.2606.4.1.2INTEGER (0..65535)read-onlymandatory
cmcTcMibCondition
OBJECT-TYPE
The overall condition (status) of the system represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on CMC) (4) a major problem (red LED on CMC) (5) configuration of sensor units changed or unit detected (red/yellow/green LED on CMC)
1.3.6.1.4.1.2606.4.1.3INTEGER {other(1), ok(2), degraded(3), failed(4), configChanged(5)}read-onlymandatory
cmcTcStatus
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2
cmcTcStatusDeviceCMC
OBJECT-TYPE
General Status of CMC-TC unit itself (1) failed (2) OK
1.3.6.1.4.1.2606.4.2.1INTEGER {failed(1), ok(2)}read-onlymandatory
cmcTcUnitsConnected
OBJECT-TYPE
Number of sensor units connected to the CMC, Port 1 to 4
1.3.6.1.4.1.2606.4.2.2INTEGERread-onlymandatory
cmcTcStatusSensorUnit1
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.3
cmcTcUnit1TypeOfDevice
OBJECT-TYPE
Type of sensor unit connected to port 1
1.3.6.1.4.1.2606.4.2.3.1INTEGER {notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13)}read-onlymandatory
cmcTcUnit1Text
OBJECT-TYPE
Descriptional text for sensor unit connected to port 1
1.3.6.1.4.1.2606.4.2.3.2DisplayString (SIZE(0..10))read-writemandatory
cmcTcUnit1Serial
OBJECT-TYPE
Serialnumber of sensor unit connected to port 1
1.3.6.1.4.1.2606.4.2.3.3INTEGERread-onlymandatory
cmcTcUnit1Status
OBJECT-TYPE
General Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low
1.3.6.1.4.1.2606.4.2.3.4INTEGER {ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8)}read-onlymandatory
cmcTcStatusUnit1Sensors
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.3.5
cmcTcUnit1NumberOfSensors
OBJECT-TYPE
Number of sensors connected to sensor unit 1
1.3.6.1.4.1.2606.4.2.3.5.1INTEGERread-onlymandatory
cmcTcUnit1SensorTable
OBJECT-TYPE
Headline of sensor table
1.3.6.1.4.1.2606.4.2.3.5.2not-accessiblemandatory
cmcTcUnit1SensorEntry
OBJECT-TYPE
Entries of sensor table
1.3.6.1.4.1.2606.4.2.3.5.2.1not-accessiblemandatory
unit1SensorIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfSensors.
1.3.6.1.4.1.2606.4.2.3.5.2.1.1INTEGER (1..65535)read-onlymandatory
unit1SensorType
OBJECT-TYPE
Type of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage (OK, NOK) 18: voltage value 19: fan status, from CMC-TC-FAS-Unit 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless
1.3.6.1.4.1.2606.4.2.3.5.2.1.2INTEGER {notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)}read-onlymandatory
unit1SensorText
OBJECT-TYPE
Descriptional text for each sensor (entry in the table)
1.3.6.1.4.1.2606.4.2.3.5.2.1.3DisplayString (SIZE(0..20))read-writemandatory
unit1SensorStatus
OBJECT-TYPE
Actual status of the sensor
1.3.6.1.4.1.2606.4.2.3.5.2.1.4INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)}read-onlymandatory
unit1SensorValue
OBJECT-TYPE
Value of sensor
1.3.6.1.4.1.2606.4.2.3.5.2.1.5INTEGERread-onlymandatory
unit1SensorSetHigh
OBJECT-TYPE
Value for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.3.5.2.1.6INTEGERread-writemandatory
unit1SensorSetLow
OBJECT-TYPE
Value for low setpoint of sensor, also used as alarm delay
1.3.6.1.4.1.2606.4.2.3.5.2.1.7INTEGERread-writemandatory
unit1SensorSetWarn
OBJECT-TYPE
Value for warning setpoint of sensor, also used as fan threshold
1.3.6.1.4.1.2606.4.2.3.5.2.1.8INTEGERread-writemandatory
cmcTcStatusUnit1Outputs
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.3.6
cmcTcUnit1NumberOfOutputs
OBJECT-TYPE
Number of outputs available on sensor unit 1
1.3.6.1.4.1.2606.4.2.3.6.1INTEGERread-onlymandatory
cmcTcUnit1OutputTable
OBJECT-TYPE
Headline of output table
1.3.6.1.4.1.2606.4.2.3.6.2not-accessiblemandatory
cmcTcUnit1OutputEntry
OBJECT-TYPE
Entries of output table
1.3.6.1.4.1.2606.4.2.3.6.2.1not-accessiblemandatory
unit1OutputIndex
OBJECT-TYPE
Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfOutputs.
1.3.6.1.4.1.2606.4.2.3.6.2.1.1INTEGER (1..65535)read-onlymandatory
unit1OutputType
OBJECT-TYPE
Type of output which is connected to sensor unit 1 to output[unit1OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, LCP) 15: setpoint temperature monitoring (LCP) 16: hysteresis of setpoint (LCP) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode, LCP 31: min fan speed (fan control), LCP 32: min delta T (fan control), LCP 33: max delta T (fan control), LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187), LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
1.3.6.1.4.1.2606.4.2.3.6.2.1.2INTEGER {notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)}read-onlymandatory
unit1OutputText
OBJECT-TYPE
Descriptional text for each output (entry in the table)
1.3.6.1.4.1.2606.4.2.3.6.2.1.3DisplayString (SIZE(0..20))read-writemandatory
unit1OutputStatus
OBJECT-TYPE
Actual status of the output
1.3.6.1.4.1.2606.4.2.3.6.2.1.4INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)}read-writemandatory
unit1OutputValue
OBJECT-TYPE
Value for output
1.3.6.1.4.1.2606.4.2.3.6.2.1.5INTEGERread-writemandatory
unit1OutputSet
OBJECT-TYPE
Command for output
1.3.6.1.4.1.2606.4.2.3.6.2.1.6INTEGER {off(1), on(2), lock(3), unlock(4), unlockDelay(5)}read-writemandatory
unit1OutputConfig
OBJECT-TYPE
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
1.3.6.1.4.1.2606.4.2.3.6.2.1.7INTEGER {disRemote(1), enRemote(2)}read-writemandatory
unit1OutputDelay
OBJECT-TYPE
Unsigned Value for delay, after this time the output will fall into the previous state
1.3.6.1.4.1.2606.4.2.3.6.2.1.8INTEGERread-writemandatory
unit1OutputTimeoutAction
OBJECT-TYPE
State for output if timeout (RS422) occurs
1.3.6.1.4.1.2606.4.2.3.6.2.1.9INTEGER {stay(1), off(2), on(3)}read-writemandatory
cmcTcStatusUnit1Msg
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.3.7
cmcTcUnit1NumberOfMsgs
OBJECT-TYPE
Number of messages that can be created with sensor unit 1
1.3.6.1.4.1.2606.4.2.3.7.1INTEGERread-onlymandatory
cmcTcUnit1MsgTable
OBJECT-TYPE
Headline of message table
1.3.6.1.4.1.2606.4.2.3.7.2not-accessiblemandatory
cmcTcUnit1MsgEntry
OBJECT-TYPE
Entries of message table
1.3.6.1.4.1.2606.4.2.3.7.2.1not-accessiblemandatory
unit1MsgIndex
OBJECT-TYPE
Index for the list of message entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfMsgs.
1.3.6.1.4.1.2606.4.2.3.7.2.1.1INTEGER (1..65535)read-onlymandatory
unit1MsgText
OBJECT-TYPE
Descriptional text for each message (entry in the table)
1.3.6.1.4.1.2606.4.2.3.7.2.1.2DisplayString (SIZE(0..20))read-writemandatory
unit1MsgStatus
OBJECT-TYPE
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
1.3.6.1.4.1.2606.4.2.3.7.2.1.3INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)}read-onlymandatory
unit1MsgRelay
OBJECT-TYPE
Setup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay
1.3.6.1.4.1.2606.4.2.3.7.2.1.4INTEGER {disable(1), enable(2)}read-writemandatory
unit1MsgBeeper
OBJECT-TYPE
Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
1.3.6.1.4.1.2606.4.2.3.7.2.1.5INTEGER {disable(1), enable(2)}read-writemandatory
unit1MsgTrap1
OBJECT-TYPE
Trap receiver 1 activated
1.3.6.1.4.1.2606.4.2.3.7.2.1.6INTEGER {disable(1), enable(2)}read-writemandatory
unit1MsgTrap2
OBJECT-TYPE
Trap receiver 2 activated
1.3.6.1.4.1.2606.4.2.3.7.2.1.7INTEGER {disable(1), enable(2)}read-writemandatory
unit1MsgTrap3
OBJECT-TYPE
Trap receiver 3 activated
1.3.6.1.4.1.2606.4.2.3.7.2.1.8INTEGER {disable(1), enable(2)}read-writemandatory
unit1MsgTrap4
OBJECT-TYPE
Trap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.3.7.2.1.9INTEGER {disable(1), enable(2)}read-writemandatory
unit1MsgQuit
OBJECT-TYPE
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
1.3.6.1.4.1.2606.4.2.3.7.2.1.10INTEGER {auto(1), manual(2)}read-writemandatory
cmcTcStatusSensorUnit2
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.4
cmcTcUnit2TypeOfDevice
OBJECT-TYPE
Type of sensor unit connected to port 2
1.3.6.1.4.1.2606.4.2.4.1INTEGER {notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13)}read-onlymandatory
cmcTcUnit2Text
OBJECT-TYPE
Descriptional text for sensor unit connected to port 2
1.3.6.1.4.1.2606.4.2.4.2DisplayString (SIZE(0..10))read-writemandatory
cmcTcUnit2Serial
OBJECT-TYPE
Serialnumber of sensor unit connected to port 2
1.3.6.1.4.1.2606.4.2.4.3INTEGERread-onlymandatory
cmcTcUnit2Status
OBJECT-TYPE
General Status sensor unit connected to port 2 (1) OK (2) error (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required (6) sensor unit detected, needs to be confirmed (8) supply voltage is too low
1.3.6.1.4.1.2606.4.2.4.4INTEGER {ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8)}read-onlymandatory
cmcTcStatusUnit2Sensors
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.4.5
cmcTcUnit2NumberOfSensors
OBJECT-TYPE
Number of sensors connected to sensor unit 2
1.3.6.1.4.1.2606.4.2.4.5.1INTEGERread-onlymandatory
cmcTcUnit2SensorTable
OBJECT-TYPE
Headline of sensor table
1.3.6.1.4.1.2606.4.2.4.5.2not-accessiblemandatory
cmcTcUnit2SensorEntry
OBJECT-TYPE
Entries of sensor table
1.3.6.1.4.1.2606.4.2.4.5.2.1not-accessiblemandatory
unit2SensorIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfSensors.
1.3.6.1.4.1.2606.4.2.4.5.2.1.1INTEGER (1..65535)read-onlymandatory
unit2SensorType
OBJECT-TYPE
Type of sensor which is connected to sensor unit 2 to sensor[unit2SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless
1.3.6.1.4.1.2606.4.2.4.5.2.1.2INTEGER {notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)}read-onlymandatory
unit2SensorText
OBJECT-TYPE
Descriptional text for each sensor (entry in the table)
1.3.6.1.4.1.2606.4.2.4.5.2.1.3DisplayString (SIZE(0..20))read-writemandatory
unit2SensorStatus
OBJECT-TYPE
Actual status of the sensor
1.3.6.1.4.1.2606.4.2.4.5.2.1.4INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)}read-onlymandatory
unit2SensorValue
OBJECT-TYPE
Value of sensor
1.3.6.1.4.1.2606.4.2.4.5.2.1.5INTEGERread-onlymandatory
unit2SensorSetHigh
OBJECT-TYPE
Value for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.4.5.2.1.6INTEGERread-writemandatory
unit2SensorSetLow
OBJECT-TYPE
Value for low setpoint of sensor, also used as alarm delay
1.3.6.1.4.1.2606.4.2.4.5.2.1.7INTEGERread-writemandatory
unit2SensorSetWarn
OBJECT-TYPE
Value for warning setpoint of sensor, also used as fan threshold
1.3.6.1.4.1.2606.4.2.4.5.2.1.8INTEGERread-writemandatory
cmcTcStatusUnit2Outputs
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.4.6
cmcTcUnit2NumberOfOutputs
OBJECT-TYPE
Number of outputs available on sensor unit 2
1.3.6.1.4.1.2606.4.2.4.6.1INTEGERread-onlymandatory
cmcTcUnit2OutputTable
OBJECT-TYPE
Headline of output table
1.3.6.1.4.1.2606.4.2.4.6.2not-accessiblemandatory
cmcTcUnit2OutputEntry
OBJECT-TYPE
Entries of output table
1.3.6.1.4.1.2606.4.2.4.6.2.1not-accessiblemandatory
unit2OutputIndex
OBJECT-TYPE
Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfOutputs.
1.3.6.1.4.1.2606.4.2.4.6.2.1.1INTEGER (1..65535)read-onlymandatory
unit2OutputType
OBJECT-TYPE
Type of output which is connected to sensor unit 2 to output[unit2OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
1.3.6.1.4.1.2606.4.2.4.6.2.1.2INTEGER {notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)}read-onlymandatory
unit2OutputText
OBJECT-TYPE
Descriptional text for each output (entry in the table)
1.3.6.1.4.1.2606.4.2.4.6.2.1.3DisplayString (SIZE(0..20))read-writemandatory
unit2OutputStatus
OBJECT-TYPE
Actual status of the output
1.3.6.1.4.1.2606.4.2.4.6.2.1.4INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)}read-writemandatory
unit2OutputValue
OBJECT-TYPE
Signed value for output
1.3.6.1.4.1.2606.4.2.4.6.2.1.5INTEGERread-writemandatory
unit2OutputSet
OBJECT-TYPE
Command for output
1.3.6.1.4.1.2606.4.2.4.6.2.1.6INTEGER {off(1), on(2), lock(3), unlock(4), unlockDelay(5)}read-writemandatory
unit2OutputConfig
OBJECT-TYPE
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
1.3.6.1.4.1.2606.4.2.4.6.2.1.7INTEGER {disRemote(1), enRemote(2)}read-writemandatory
unit2OutputDelay
OBJECT-TYPE
Unsigned Value for delay, after this time the output will fall into the previous state
1.3.6.1.4.1.2606.4.2.4.6.2.1.8INTEGERread-writemandatory
unit2OutputTimeoutAction
OBJECT-TYPE
State for output if timeout (RS422) occurs
1.3.6.1.4.1.2606.4.2.4.6.2.1.9INTEGER {stay(1), off(2), on(3)}read-writemandatory
cmcTcStatusUnit2Msg
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.4.7
cmcTcUnit2NumberOfMsgs
OBJECT-TYPE
Number of alarms that can be created with sensor unit 2
1.3.6.1.4.1.2606.4.2.4.7.1INTEGERread-onlymandatory
cmcTcUnit2MsgTable
OBJECT-TYPE
Headline of message table
1.3.6.1.4.1.2606.4.2.4.7.2not-accessiblemandatory
cmcTcUnit2MsgEntry
OBJECT-TYPE
Entries of message table
1.3.6.1.4.1.2606.4.2.4.7.2.1not-accessiblemandatory
unit2MsgIndex
OBJECT-TYPE
Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfMsgs.
1.3.6.1.4.1.2606.4.2.4.7.2.1.1INTEGER (1..65535)read-onlymandatory
unit2MsgText
OBJECT-TYPE
Descriptional text for each message (entry in the table)
1.3.6.1.4.1.2606.4.2.4.7.2.1.2DisplayString (SIZE(0..20))read-writemandatory
unit2MsgStatus
OBJECT-TYPE
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
1.3.6.1.4.1.2606.4.2.4.7.2.1.3INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)}read-onlymandatory
unit2MsgRelay
OBJECT-TYPE
Setup of Alarm relay for this alarm 2: no switching of alarm relay 1: switching of alarm relay
1.3.6.1.4.1.2606.4.2.4.7.2.1.4INTEGER {disable(1), enable(2)}read-writemandatory
unit2MsgBeeper
OBJECT-TYPE
Setup of Alarm beeper for this alarm 2: no audible alarm 1: audible alarm
1.3.6.1.4.1.2606.4.2.4.7.2.1.5INTEGER {disable(1), enable(2)}read-writemandatory
unit2MsgTrap1
OBJECT-TYPE
Trap receiver 1 activated
1.3.6.1.4.1.2606.4.2.4.7.2.1.6INTEGER {disable(1), enable(2)}read-writemandatory
unit2MsgTrap2
OBJECT-TYPE
Trap receiver 2 activated
1.3.6.1.4.1.2606.4.2.4.7.2.1.7INTEGER {disable(1), enable(2)}read-writemandatory
unit2MsgTrap3
OBJECT-TYPE
Trap receiver 3 activated
1.3.6.1.4.1.2606.4.2.4.7.2.1.8INTEGER {disable(1), enable(2)}read-writemandatory
unit2MsgTrap4
OBJECT-TYPE
Trap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.4.7.2.1.9INTEGER {disable(1), enable(2)}read-writemandatory
unit2MsgQuit
OBJECT-TYPE
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
1.3.6.1.4.1.2606.4.2.4.7.2.1.10INTEGER {auto(1), manual(2)}read-writemandatory
cmcTcStatusSensorUnit3
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.5
cmcTcUnit3TypeOfDevice
OBJECT-TYPE
Type of sensor unit connected to port 3
1.3.6.1.4.1.2606.4.2.5.1INTEGER {notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13)}read-onlymandatory
cmcTcUnit3Text
OBJECT-TYPE
Descriptional text for sensor unit connected to port 3
1.3.6.1.4.1.2606.4.2.5.2DisplayString (SIZE(0..10))read-writemandatory
cmcTcUnit3Serial
OBJECT-TYPE
Serialnumber of sensor unit connected to port 3
1.3.6.1.4.1.2606.4.2.5.3INTEGERread-onlymandatory
cmcTcUnit3Status
OBJECT-TYPE
General Status sensor unit connected to port 3 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low
1.3.6.1.4.1.2606.4.2.5.4INTEGER {ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8)}read-onlymandatory
cmcTcStatusUnit3Sensors
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.5.5
cmcTcUnit3NumberOfSensors
OBJECT-TYPE
Number of sensors connected to sensor unit 3
1.3.6.1.4.1.2606.4.2.5.5.1INTEGERread-onlymandatory
cmcTcUnit3SensorTable
OBJECT-TYPE
Headline of sensor table
1.3.6.1.4.1.2606.4.2.5.5.2not-accessiblemandatory
cmcTcUnit3SensorEntry
OBJECT-TYPE
Entries of sensor table
1.3.6.1.4.1.2606.4.2.5.5.2.1not-accessiblemandatory
unit3SensorIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfSensors.
1.3.6.1.4.1.2606.4.2.5.5.2.1.1INTEGER (1..65535)read-onlymandatory
unit3SensorType
OBJECT-TYPE
Type of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless
1.3.6.1.4.1.2606.4.2.5.5.2.1.2INTEGER {notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)}read-onlymandatory
unit3SensorText
OBJECT-TYPE
Descriptional text for each sensor (entry in the table)
1.3.6.1.4.1.2606.4.2.5.5.2.1.3DisplayString (SIZE(0..20))read-writemandatory
unit3SensorStatus
OBJECT-TYPE
Actual status of the sensor
1.3.6.1.4.1.2606.4.2.5.5.2.1.4INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)}read-onlymandatory
unit3SensorValue
OBJECT-TYPE
Value of sensor
1.3.6.1.4.1.2606.4.2.5.5.2.1.5INTEGERread-onlymandatory
unit3SensorSetHigh
OBJECT-TYPE
Value for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.5.5.2.1.6INTEGERread-writemandatory
unit3SensorSetLow
OBJECT-TYPE
Value for low setpoint of sensor
1.3.6.1.4.1.2606.4.2.5.5.2.1.7INTEGERread-writemandatory
unit3SensorSetWarn
OBJECT-TYPE
Value for warning setpoint of sensor, also used as fan threshold
1.3.6.1.4.1.2606.4.2.5.5.2.1.8INTEGERread-writemandatory
cmcTcStatusUnit3Outputs
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.5.6
cmcTcUnit3NumberOfOutputs
OBJECT-TYPE
Number of outputs available on sensor unit 3
1.3.6.1.4.1.2606.4.2.5.6.1INTEGERread-onlymandatory
cmcTcUnit3OutputTable
OBJECT-TYPE
Headline of output table
1.3.6.1.4.1.2606.4.2.5.6.2not-accessiblemandatory
cmcTcUnit3OutputEntry
OBJECT-TYPE
Entries of output table
1.3.6.1.4.1.2606.4.2.5.6.2.1not-accessiblemandatory
unit3OutputIndex
OBJECT-TYPE
Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfOutputs.
1.3.6.1.4.1.2606.4.2.5.6.2.1.1INTEGER (1..65535)read-onlymandatory
unit3OutputType
OBJECT-TYPE
Type of output which is connected to sensor unit 3 to output[unit3OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
1.3.6.1.4.1.2606.4.2.5.6.2.1.2INTEGER {notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)}read-onlymandatory
unit3OutputText
OBJECT-TYPE
Descriptional text for each output (entry in the table)
1.3.6.1.4.1.2606.4.2.5.6.2.1.3DisplayString (SIZE(0..20))read-writemandatory
unit3OutputStatus
OBJECT-TYPE
Actual status of the output
1.3.6.1.4.1.2606.4.2.5.6.2.1.4INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)}read-writemandatory
unit3OutputValue
OBJECT-TYPE
Value for output
1.3.6.1.4.1.2606.4.2.5.6.2.1.5INTEGERread-writemandatory
unit3OutputSet
OBJECT-TYPE
Command for output
1.3.6.1.4.1.2606.4.2.5.6.2.1.6INTEGER {off(1), on(2), lock(3), unlock(4), unlockDelay(5)}read-writemandatory
unit3OutputConfig
OBJECT-TYPE
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
1.3.6.1.4.1.2606.4.2.5.6.2.1.7INTEGER {disRemote(1), enRemote(2)}read-writemandatory
unit3OutputDelay
OBJECT-TYPE
Unsigned Value for delay, after this time the output will fall into the previous state
1.3.6.1.4.1.2606.4.2.5.6.2.1.8INTEGERread-writemandatory
unit3OutputTimeoutAction
OBJECT-TYPE
State for output if timeout (RS422) occurs
1.3.6.1.4.1.2606.4.2.5.6.2.1.9INTEGER {stay(1), off(2), on(3)}read-writemandatory
cmcTcStatusUnit3Msg
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.5.7
cmcTcUnit3NumberOfMsgs
OBJECT-TYPE
Number of alarms that can be created with sensor unit 3
1.3.6.1.4.1.2606.4.2.5.7.1INTEGERread-onlymandatory
cmcTcUnit3MsgTable
OBJECT-TYPE
Headline of message table
1.3.6.1.4.1.2606.4.2.5.7.2not-accessiblemandatory
cmcTcUnit3MsgEntry
OBJECT-TYPE
Entries of message table
1.3.6.1.4.1.2606.4.2.5.7.2.1not-accessiblemandatory
unit3MsgIndex
OBJECT-TYPE
Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfMsgs.
1.3.6.1.4.1.2606.4.2.5.7.2.1.1INTEGER (1..65535)read-onlymandatory
unit3MsgText
OBJECT-TYPE
Descriptional text for each message (entry in the table)
1.3.6.1.4.1.2606.4.2.5.7.2.1.2DisplayString (SIZE(0..20))read-writemandatory
unit3MsgStatus
OBJECT-TYPE
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
1.3.6.1.4.1.2606.4.2.5.7.2.1.3INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)}read-onlymandatory
unit3MsgRelay
OBJECT-TYPE
Setup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay
1.3.6.1.4.1.2606.4.2.5.7.2.1.4INTEGER {disable(1), enable(2)}read-writemandatory
unit3MsgBeeper
OBJECT-TYPE
Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
1.3.6.1.4.1.2606.4.2.5.7.2.1.5INTEGER {disable(1), enable(2)}read-writemandatory
unit3MsgTrap1
OBJECT-TYPE
Trap receiver 1 activated
1.3.6.1.4.1.2606.4.2.5.7.2.1.6INTEGER {disable(1), enable(2)}read-writemandatory
unit3MsgTrap2
OBJECT-TYPE
Trap receiver 2 activated
1.3.6.1.4.1.2606.4.2.5.7.2.1.7INTEGER {disable(1), enable(2)}read-writemandatory
unit3MsgTrap3
OBJECT-TYPE
Trap receiver 3 activated
1.3.6.1.4.1.2606.4.2.5.7.2.1.8INTEGER {disable(1), enable(2)}read-writemandatory
unit3MsgTrap4
OBJECT-TYPE
Trap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.5.7.2.1.9INTEGER {disable(1), enable(2)}read-writemandatory
unit3MsgQuit
OBJECT-TYPE
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
1.3.6.1.4.1.2606.4.2.5.7.2.1.10INTEGER {auto(1), manual(2)}read-writemandatory
cmcTcStatusSensorUnit4
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.6
cmcTcUnit4TypeOfDevice
OBJECT-TYPE
Type of sensor unit connected to port 4
1.3.6.1.4.1.2606.4.2.6.1INTEGER {notAvail(1), unitIO(2), unitAccess(3), unitClimate(4), unitFCS(5), unitRTT(6), unitRCT(7), unitPSM(8), unitPSM8(9), unitPSMMetered(10), unitIOWireless(11), unitPSM6Schuko(12), unitPSM6C19(13)}read-onlymandatory
cmcTcUnit4Text
OBJECT-TYPE
Descriptional text for sensor unit connected to port 4
1.3.6.1.4.1.2606.4.2.6.2DisplayString (SIZE(0..10))read-writemandatory
cmcTcUnit4Serial
OBJECT-TYPE
Serialnumber of sensor unit connected to port 4
1.3.6.1.4.1.2606.4.2.6.3INTEGERread-onlymandatory
cmcTcUnit4Status
OBJECT-TYPE
General Status sensor unit connected to port 4 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low
1.3.6.1.4.1.2606.4.2.6.4INTEGER {ok(1), error(2), changed(3), quit(4), timeout(5), detected(6), notAvail(7), lowPower(8)}read-onlymandatory
cmcTcStatusUnit4Sensors
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.6.5
cmcTcUnit4NumberOfSensors
OBJECT-TYPE
Number of sensors connected to sensor unit 4
1.3.6.1.4.1.2606.4.2.6.5.1INTEGERread-onlymandatory
cmcTcUnit4SensorTable
OBJECT-TYPE
Headline of sensor table
1.3.6.1.4.1.2606.4.2.6.5.2not-accessiblemandatory
cmcTcUnit4SensorEntry
OBJECT-TYPE
Entries of sensor table
1.3.6.1.4.1.2606.4.2.6.5.2.1not-accessiblemandatory
unit4SensorIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfSensors.
1.3.6.1.4.1.2606.4.2.6.5.2.1.1INTEGER (1..65535)read-onlymandatory
unit4SensorType
OBJECT-TYPE
Type of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless
1.3.6.1.4.1.2606.4.2.6.5.2.1.2INTEGER {notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), lock(15), unlock(16), voltOK(17), voltage(18), fanOK(19), readerKeypad(20), dutyPWM(21), fanStatus(22), leakage(23), warningRTT(24), alarmRTT(25), filterRTT(26), heatflowRCT(27), alarmRCT(28), warningRCT(29), currentPSM(30), statusPSM(31), positionPSM(32), airFlap(33), acoustic(34), detACfault(35), detACfirstAlarm(36), detACmainAlarm(37), rpm11LCP(40), rpm12LCP(41), rpm21LCP(42), rpm22LCP(43), rpm31LCP(44), rpm32LCP(45), rpm41LCP(46), rpm42LCP(47), airTemp11LCP(48), airTemp12LCP(49), airTemp21LCP(50), airTemp22LCP(51), airTemp31LCP(52), airTemp32LCP(53), airTemp41LCP(54), airTemp42LCP(55), temp1LCP(56), temp2LCP(57), waterInTemp(58), waterOutTemp(59), waterFlow(60), fanSpeed(61), valve(62), statusLCP(63), waterDelta(64), valveActual(65), contrTemp2(66), condensateDuration(67), condensateCycles(68), totalKWhPSM(72), totalKWPSM(73), frequencyPSM(74), voltagePSM(75), voltStatusPSM(76), amperePSM(77), ampStatusPSM(78), kWPSM(79), kWhPSM(80), kWhTempPSM(81), temperatureWL(100), temperature1WL(101), humidityWL(102), accessWL(103), userNOWL(104), userNCWL(105), analogWL(106)}read-onlymandatory
unit4SensorText
OBJECT-TYPE
Descriptional text for each sensor (entry in the table)
1.3.6.1.4.1.2606.4.2.6.5.2.1.3DisplayString (SIZE(0..20))read-writemandatory
unit4SensorStatus
OBJECT-TYPE
Actual status of the sensor
1.3.6.1.4.1.2606.4.2.6.5.2.1.4INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)}read-onlymandatory
unit4SensorValue
OBJECT-TYPE
Value of sensor
1.3.6.1.4.1.2606.4.2.6.5.2.1.5INTEGERread-onlymandatory
unit4SensorSetHigh
OBJECT-TYPE
Value for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.6.5.2.1.6INTEGERread-writemandatory
unit4SensorSetLow
OBJECT-TYPE
Value for low setpoint of sensor
1.3.6.1.4.1.2606.4.2.6.5.2.1.7INTEGERread-writemandatory
unit4SensorSetWarn
OBJECT-TYPE
Value for warning setpoint of sensor, also used as fan threshold
1.3.6.1.4.1.2606.4.2.6.5.2.1.8INTEGERread-writemandatory
cmcTcStatusUnit4Outputs
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.6.6
cmcTcUnit4NumberOfOutputs
OBJECT-TYPE
Number of outputs available on sensor unit 4
1.3.6.1.4.1.2606.4.2.6.6.1INTEGERread-onlymandatory
cmcTcUnit4OutputTable
OBJECT-TYPE
Headline of output table
1.3.6.1.4.1.2606.4.2.6.6.2not-accessiblemandatory
cmcTcUnit4OutputEntry
OBJECT-TYPE
Entries of output table
1.3.6.1.4.1.2606.4.2.6.6.2.1not-accessiblemandatory
unit4OutputIndex
OBJECT-TYPE
Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfOutputs.
1.3.6.1.4.1.2606.4.2.6.6.2.1.1INTEGER (1..65535)read-onlymandatory
unit4OutputType
OBJECT-TYPE
Type of output which is connected to sensor unit 4 to output[unit4OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
1.3.6.1.4.1.2606.4.2.6.6.2.1.2INTEGER {notAvail(1), failure(2), overflow(3), doorLock(4), univLock1(5), univLock2(6), fan(7), fanSpeedContr(8), universalOut(9), roomLock(10), powerOut(11), doorLockMaster(12), doorLockFRi(13), setpoint(14), setpointTimax(15), hysteresisRCT(16), commandRCT(17), relayPSM(18), setHighPSM(19), setLowPSM(20), setpointRTT(21), setTimaxRTT(22), powerOut1(23), controlModeLCP(30), minFanSpeedLCP(31), minDeltaTLCP(32), maxDeltaTLCP(33), kPLCP(34), kILCP(35), kDLCP(36), flowRateLCP(37), cwValueLCP(38), deltaTLCP(39), ctrModLCP(40), voltHighPSM(42), voltLowPSM(43), ampHighPSM(44), ampLowPSM(45), commandPSM(46)}read-onlymandatory
unit4OutputText
OBJECT-TYPE
Descriptional text for each output (entry in the table)
1.3.6.1.4.1.2606.4.2.6.6.2.1.3DisplayString (SIZE(0..20))read-writemandatory
unit4OutputStatus
OBJECT-TYPE
Actual status of the output
1.3.6.1.4.1.2606.4.2.6.6.2.1.4INTEGER {notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)}read-writemandatory
unit4OutputValue
OBJECT-TYPE
Value for output
1.3.6.1.4.1.2606.4.2.6.6.2.1.5INTEGERread-writemandatory
unit4OutputSet
OBJECT-TYPE
Command for output
1.3.6.1.4.1.2606.4.2.6.6.2.1.6INTEGER {off(1), on(2), lock(3), unlock(4), unlockDelay(5)}read-writemandatory
unit4OutputConfig
OBJECT-TYPE
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
1.3.6.1.4.1.2606.4.2.6.6.2.1.7INTEGER {disRemote(1), enRemote(2)}read-writemandatory
unit4OutputDelay
OBJECT-TYPE
Unsigned Value for delay, after this time the output will fall into the previous state
1.3.6.1.4.1.2606.4.2.6.6.2.1.8INTEGERread-writemandatory
unit4OutputTimeoutAction
OBJECT-TYPE
State for output if timeout (RS422) occurs
1.3.6.1.4.1.2606.4.2.6.6.2.1.9INTEGER {stay(1), off(2), on(3)}read-writemandatory
cmcTcStatusUnit4Msg
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.6.7
cmcTcUnit4NumberOfMsgs
OBJECT-TYPE
Number of alarms that can be created with sensor unit 4
1.3.6.1.4.1.2606.4.2.6.7.1INTEGERread-onlymandatory
cmcTcUnit4MsgTable
OBJECT-TYPE
Headline of message table
1.3.6.1.4.1.2606.4.2.6.7.2not-accessiblemandatory
cmcTcUnit4MsgEntry
OBJECT-TYPE
Entries of message table
1.3.6.1.4.1.2606.4.2.6.7.2.1not-accessiblemandatory
unit4MsgIndex
OBJECT-TYPE
Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfMsgs.
1.3.6.1.4.1.2606.4.2.6.7.2.1.1INTEGER (1..65535)read-onlymandatory
unit4MsgText
OBJECT-TYPE
Descriptional text for each message (entry in the table)
1.3.6.1.4.1.2606.4.2.6.7.2.1.2DisplayString (SIZE(0..20))read-writemandatory
unit4MsgStatus
OBJECT-TYPE
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
1.3.6.1.4.1.2606.4.2.6.7.2.1.3INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10), open(11), closed(12), locked(13), unlRemote(14), unlReaderKeypad(15), unlSNMP(16), unlWEB(17), unlTimer(18), noAccess(19), circuit1(20), circuit2(21), lowBatt(22)}read-onlymandatory
unit4MsgRelay
OBJECT-TYPE
Setup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay
1.3.6.1.4.1.2606.4.2.6.7.2.1.4INTEGER {disable(1), enable(2)}read-writemandatory
unit4MsgBeeper
OBJECT-TYPE
Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
1.3.6.1.4.1.2606.4.2.6.7.2.1.5INTEGER {disable(1), enable(2)}read-writemandatory
unit4MsgTrap1
OBJECT-TYPE
Trap receiver 1 activated
1.3.6.1.4.1.2606.4.2.6.7.2.1.6INTEGER {disable(1), enable(2)}read-writemandatory
unit4MsgTrap2
OBJECT-TYPE
Trap receiver 2 activated
1.3.6.1.4.1.2606.4.2.6.7.2.1.7INTEGER {disable(1), enable(2)}read-writemandatory
unit4MsgTrap3
OBJECT-TYPE
Trap receiver 3 activated
1.3.6.1.4.1.2606.4.2.6.7.2.1.8INTEGER {disable(1), enable(2)}read-writemandatory
unit4MsgTrap4
OBJECT-TYPE
Trap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.6.7.2.1.9INTEGER {disable(1), enable(2)}read-writemandatory
unit4MsgQuit
OBJECT-TYPE
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
1.3.6.1.4.1.2606.4.2.6.7.2.1.10INTEGER {auto(1), manual(2)}read-writemandatory
cmcTcStatusExtUnit
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.2.7
cmcTcValuesRelay
OBJECT-TYPE
Setup of Alarm relay for alarm ext. unit(s) 1: no switching of alarm relay 2: switching of alarm relay
1.3.6.1.4.1.2606.4.2.7.1INTEGER {disable(1), enable(2)}read-writemandatory
cmcTcValuesBeeper
OBJECT-TYPE
Setup of Alarm beeper for alarm ext. unit(s) 1: no audible alarm 2: audible alarm
1.3.6.1.4.1.2606.4.2.7.2INTEGER {disable(1), enable(2)}read-writemandatory
cmcTcValuesTrap1
OBJECT-TYPE
Trap receiver 1 activated
1.3.6.1.4.1.2606.4.2.7.3INTEGER {disable(1), enable(2)}read-writemandatory
cmcTcValuesTrap2
OBJECT-TYPE
Trap receiver 2 activated
1.3.6.1.4.1.2606.4.2.7.4INTEGER {disable(1), enable(2)}read-writemandatory
cmcTcValuesTrap3
OBJECT-TYPE
Trap receiver 3 activated
1.3.6.1.4.1.2606.4.2.7.5INTEGER {disable(1), enable(2)}read-writemandatory
cmcTcValuesTrap4
OBJECT-TYPE
Trap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.7.6INTEGER {disable(1), enable(2)}read-writemandatory
cmcTcNumberOfValues
OBJECT-TYPE
Number of values availabel on extension units connected to the CMC
1.3.6.1.4.1.2606.4.2.7.7INTEGERread-onlymandatory
cmcTcValuesTable
OBJECT-TYPE
Headline of values-table
1.3.6.1.4.1.2606.4.2.7.8not-accessiblemandatory
cmcTcValuesEntry
OBJECT-TYPE
Entries of values-table
1.3.6.1.4.1.2606.4.2.7.8.1not-accessiblemandatory
valuesIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcTcNumberOfValues.
1.3.6.1.4.1.2606.4.2.7.8.1.1INTEGER (1..65535)read-onlymandatory
valuesText
OBJECT-TYPE
Descriptional text for each value (entry in the table) of the extension card
1.3.6.1.4.1.2606.4.2.7.8.1.2DisplayString (SIZE(0..20))read-writemandatory
valuesStatus
OBJECT-TYPE
Actual status of the value of the extension card
1.3.6.1.4.1.2606.4.2.7.8.1.3INTEGER {notAvail(1), lost(2), changed(3), ok(4), tooLow(5), tooHigh(6), error(7)}read-onlymandatory
valuesValue
OBJECT-TYPE
Value of sensor
1.3.6.1.4.1.2606.4.2.7.8.1.4INTEGERread-onlymandatory
valuesSetHigh
OBJECT-TYPE
Value for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.7.8.1.5INTEGERread-writemandatory
valuesSetLow
OBJECT-TYPE
Value for low setpoint of sensor
1.3.6.1.4.1.2606.4.2.7.8.1.6INTEGERread-writemandatory
cmcTcSetup
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.3
cmcTcSetupGeneral
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.3.1
cmcTcSetTempUnit
OBJECT-TYPE
Unit of all temperature values and setpoints, Celsius or Fahrenheit
1.3.6.1.4.1.2606.4.3.1.1INTEGER {celsius(1), fahrenheit(2)}read-writemandatory
cmcTcSetBeeper
OBJECT-TYPE
Audible alarm in CMC-TC unit: (2): beeper is on (1): beeper is off (general)
1.3.6.1.4.1.2606.4.3.1.2INTEGER {off(1), on(2)}read-writemandatory
cmcTcQuitRelay
OBJECT-TYPE
Enable or disable acknowledging currently active alarm relay (with 'C' on CMC-TC).
1.3.6.1.4.1.2606.4.3.1.3INTEGER {disabled(1), enabled(2)}read-writemandatory
cmcTcLogicRelay
OBJECT-TYPE
Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay off (general)
1.3.6.1.4.1.2606.4.3.1.4INTEGER {closeAtAlarm(1), openAtAlarm(2), off(3)}read-writemandatory
cmcTcWebAccess
OBJECT-TYPE
Web access via HTTP: (1) view only (2) full Access, read and set (3) Web disabled (general)
1.3.6.1.4.1.2606.4.3.1.5INTEGER {viewOnly(1), fullAccess(2), off(3)}read-writemandatory
cmcTcSetupDate
OBJECT-TYPE
actual Date in format DD.MM.YYYY
1.3.6.1.4.1.2606.4.3.1.6DisplayString (SIZE(0..10))read-writemandatory
cmcTcSetupTime
OBJECT-TYPE
actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)
1.3.6.1.4.1.2606.4.3.1.7DisplayString (SIZE(0..8))read-writemandatory
cmcTcTimerTable1
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.3.1.8
cmcTcTimerNumber
OBJECT-TYPE
Number of value-table entries=number of outlets available on this unit
1.3.6.1.4.1.2606.4.3.1.8.1INTEGERread-onlymandatory
cmcTcTimerTable
OBJECT-TYPE
Headline of status-table
1.3.6.1.4.1.2606.4.3.1.8.2not-accessiblemandatory
cmcTcTimerEntry
OBJECT-TYPE
Entries of timer-table
1.3.6.1.4.1.2606.4.3.1.8.2.1not-accessiblemandatory
cmcTcTimerIndex
OBJECT-TYPE
Index for the list of timer entries. Its value ranges between 1 and the value of cmcTcTimerNumber.
1.3.6.1.4.1.2606.4.3.1.8.2.1.1INTEGER (1..65535)read-onlymandatory
cmcTcTimerStatus
OBJECT-TYPE
Actual status of the timer
1.3.6.1.4.1.2606.4.3.1.8.2.1.2INTEGER {switchedOff(1), switchedOn(2), noTime(3)}read-onlymandatory
cmcTcTimerDayOfWeek
OBJECT-TYPE
Selection of day of week for timer to switch
1.3.6.1.4.1.2606.4.3.1.8.2.1.3INTEGER {sun(1), mon(2), tue(3), wed(4), thu(5), fri(6), sat(7), sat-sun(8), mon-fri(9), mon-sun(10)}read-writemandatory
cmcTcTimeOn
OBJECT-TYPE
Time to switch on current function, Format: HH:MM
1.3.6.1.4.1.2606.4.3.1.8.2.1.4DisplayString (SIZE(0..5))read-writemandatory
cmcTcTimeOff
OBJECT-TYPE
Time to switch off current function, Format: HH:MM
1.3.6.1.4.1.2606.4.3.1.8.2.1.5DisplayString (SIZE(0..5))read-writemandatory
cmcTcTimeControl
OBJECT-TYPE
Control via RTC
1.3.6.1.4.1.2606.4.3.1.8.2.1.6INTEGER {disabled(1), enabled(2)}read-writemandatory
cmcTcTimerFunction
OBJECT-TYPE
Function which is controlled via timer 1: unlock via keypad 1 on unit 1 or remote input lock 1 is disabled 2: unlock via keypad 2 on unit 1 or remote input lock 2 is disabled 3 unlock via keypad 1 on unit 2 or remote input lock 1 is disabled 4: unlock via keypad 2 on unit 2 or remote input lock 2 is disabled 5: unlock via keypad 1 on unit 3 or remote input lock 1 is disabled 6: unlock via keypad 2 on unit 3 or remote input lock 2 is disabled 7: unlock via keypad 1 on unit 4 or remote input lock 1 is disabled 8: unlock via keypad 2 on unit 4 or remote input lock 2 is disabled 9: Lock of door 1 on unit 1 will be unlocked 10: Lock of door 2 on unit 1 will be unlocked 11: Lock of door 1 on unit 2 will be unlocked 12: Lock of door 2 on unit 2 will be unlocked 13: Lock of door 1 on unit 3 will be unlocked 14: Lock of door 2 on unit 3 will be unlocked 15: Lock of door 1 on unit 4 will be unlocked 16: Lock of door 2 on unit 4 will be unlocked 17-20: sending Traps to this Trap receiver will be disabled 21: sending SMS will be disabled generally 22-25: Scheduled alarm off 26-29: sending SMS to phone number 1..4 will be disabled
1.3.6.1.4.1.2606.4.3.1.8.2.1.7INTEGER {disKeypad1-1(1), disKeypad2-1(2), disKeypad1-2(3), disKeypad2-2(4), disKeypad1-3(5), disKeypad2-3(6), disKeypad1-4(7), disKeypad2-4(8), unlDoor1-1(9), unlDoor2-1(10), unlDoor1-2(11), unlDoor2-2(12), unlDoor1-3(13), unlDoor2-3(14), unlDoor1-4(15), unlDoor2-5(16), disTrapRec1(17), disTrapRec2(18), disTrapRec3(19), disTrapRec4(20), disSMS(21), schedule1(22), schedule2(23), schedule3(24), schedule4(25), disSMS1(26), disSMS2(27), disSMS3(28), disSMS4(29)}read-writemandatory
cmcTcTrapControl
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.4
cmcTcTraps
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.4.7
cmcTcTraptableNumber
OBJECT-TYPE
Number of trapTable entries. The number of trap-receiver
1.3.6.1.4.1.2606.4.4.7.1INTEGERread-onlymandatory
cmcTcTrapTableTable
OBJECT-TYPE
A list of trap-receiver entries
1.3.6.1.4.1.2606.4.4.7.2not-accessiblemandatory
cmcTcTrapTableEntry
OBJECT-TYPE
Entries of trapTable
1.3.6.1.4.1.2606.4.4.7.2.1not-accessiblemandatory
trapIndex
OBJECT-TYPE
Index for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumber
1.3.6.1.4.1.2606.4.4.7.2.1.1INTEGER (1..65535)read-onlymandatory
trapStatus
OBJECT-TYPE
Enable or disable trap receiver
1.3.6.1.4.1.2606.4.4.7.2.1.2INTEGER {disabled(1), enabled(2)}read-writemandatory
trapIPaddress
OBJECT-TYPE
IP-address of trap-receiver
1.3.6.1.4.1.2606.4.4.7.2.1.3DisplayString (SIZE(0..15))read-writemandatory
cmcTcControl
OBJECT-IDENTITY
1.3.6.1.4.1.2606.4.5
cmcTcQuitUnit
OBJECT-TYPE
Command to quit (acknowledge) alarms of CMC-TC unit. Setting to 'quit' (2) will have same result as pressing 'C' on Units. Variable is automatically set back to 'noQuit' (1).
1.3.6.1.4.1.2606.4.5.1INTEGER {noQuit(1), quit(2)}read-writemandatory

Notifications

NameOIDStatus
alarmSensorUnit1
NOTIFICATION-TYPE
Alarm of sensor unit 1
1.3.6.1.4.1.2606.4.0.1
alarmSensorUnit2
NOTIFICATION-TYPE
Alarm of sensor unit 2
1.3.6.1.4.1.2606.4.0.2
alarmSensorUnit3
NOTIFICATION-TYPE
Alarm of sensor unit 3
1.3.6.1.4.1.2606.4.0.3
alarmSensorUnit4
NOTIFICATION-TYPE
Alarm of sensor unit 4
1.3.6.1.4.1.2606.4.0.4
alarmUnit1
NOTIFICATION-TYPE
Alarm of unit 1
1.3.6.1.4.1.2606.4.0.5
alarmUnit2
NOTIFICATION-TYPE
Alarm of unit 2
1.3.6.1.4.1.2606.4.0.6
alarmUnit3
NOTIFICATION-TYPE
Alarm of unit 3
1.3.6.1.4.1.2606.4.0.7
alarmUnit4
NOTIFICATION-TYPE
Alarm of unit 4
1.3.6.1.4.1.2606.4.0.8
alarmValues
NOTIFICATION-TYPE
Alarm of values measured by external card
1.3.6.1.4.1.2606.4.0.9
configChanged
NOTIFICATION-TYPE
The configuration of the cmc has changed, this trap is send if new setup is saved. Configuration can be changed by Terminal, Telnet, Web or SNMP *** NOT IMPLEMENTED ***
1.3.6.1.4.1.2606.4.0.10