MIBs Depot

RITTAL-CMC-III-MIB

Registered at
1.3.6.1.4.1.2606.7
Last updated
2016-02-02 00:00
Organization
RITTAL GmbH & Co. KG
Revisions
2016-02-02 00:00, 2015-10-27 00:00, 2015-01-23 00:00, 2014-07-10 00:00, 2013-11-10 00:00, 2013-05-01 00:00, 2012-08-30 00:00, 2011-09-02 00:00, 2011-04-11 00:00
Namespace
rittal
Source file
RITTAL-CMC-III-MIB
Digest
sha256:99d8678475ea8e1f54aa9d9946c60d87a83ec6f9392b57218a46ea9df74b1586

Description

The MIB module for representing cmcIII SNMP agent.

Contact

www.rittal.de RITTAL GmbH & Co. KG Forschung & Entwicklung Auf dem Stuetzelberg D-35745 Herborn Germany, Europe +49(0)2772 5050 info@rittal.de.

Imports

FromSymbols
RITTAL-SMI-MIBrittal
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-MIBsysObjectID
SNMPv2-SMIInteger32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

2 module(s) in this corpus import this one.

Load order

Every file a consumer needs in order to load this module, dependencies first.

RITTAL-CMC-III-MIB
RITTAL-SMI-MIB
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC

Under this module's arcs

Where the registration tree carries on below this module.

ArcNameModule
1.3.6.1.4.1.2606.7.7cmcIIIProductsRITTAL-CMC-III-PRODUCTS-MIB
1.3.6.1.4.1.2606.7.8cmcIIICapabilityRITTAL-CMC-III-CAPABILITY-MIB

Objects

NameOIDSyntaxAccessStatus
cmcIIINotifications
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.0
cmcIIIMibRev
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.1
cmcIIIMibMajRev
OBJECT-TYPE
The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level.
1.3.6.1.4.1.2606.7.1.1Unsigned32 (1..65535)read-onlycurrent
cmcIIIMibMinRev
OBJECT-TYPE
The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.
1.3.6.1.4.1.2606.7.1.2Unsigned32 (0..65535)read-onlycurrent
cmcIIIAgentRev
OBJECT-TYPE
The SNMP Agent Revision level.
1.3.6.1.4.1.2606.7.1.3DisplayString (SIZE(0..20))read-onlycurrent
cmcIIICapabilityRev
OBJECT-TYPE
This agents capabilities as used in RITTAL-CMC-III-CAPABILITY-MIB.
1.3.6.1.4.1.2606.7.1.4Unsigned32 (30000..39999)read-onlycurrent
cmcIIIUnit
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.2
cmcIIIUnitStatus
OBJECT-TYPE
General Status of CMCIII PU unit itself (1) OK (2) failed (3) overload (current too high).
1.3.6.1.4.1.2606.7.2.1INTEGER {ok(1), failed(2), overload(3)}read-onlycurrent
cmcIIIUnitURL
OBJECT-TYPE
URL of CMCIII PU.
1.3.6.1.4.1.2606.7.2.2DisplayString (SIZE(0..30))read-onlycurrent
cmcIIIUnitHWRev
OBJECT-TYPE
Hardware Revision of CMCIII PU.
1.3.6.1.4.1.2606.7.2.3DisplayString (SIZE(0..24))read-onlycurrent
cmcIIIUnitFWRev
OBJECT-TYPE
Firmware Revision of CMCIII PU.
1.3.6.1.4.1.2606.7.2.4DisplayString (SIZE(0..24))read-onlycurrent
cmcIIIUnitOSRev
OBJECT-TYPE
Linux Revision of CMCIII PU.
1.3.6.1.4.1.2606.7.2.5DisplayString (SIZE(0..20))read-onlycurrent
cmcIIIUnitSerial
OBJECT-TYPE
Serial Number of CMCIII PU.
1.3.6.1.4.1.2606.7.2.6DisplayString (SIZE(0..10))read-onlycurrent
cmcIIIUnitProd
OBJECT-TYPE
Production Code of CMCIII PU.
1.3.6.1.4.1.2606.7.2.7DisplayString (SIZE(0..24))read-onlycurrent
cmcIIIUnitType
OBJECT-TYPE
Type of CMCIII (1) Unit unknown (2) Processing Unit (3) Processing Unit Compact (4) LCP (5) PDU (6) RiMatrix S.
1.3.6.1.4.1.2606.7.2.8INTEGER {unknown(1), pu(2), compact(3), lcp(4), pdu(5), rms(6)}read-onlycurrent
cmcIIIUnitCurrentSource
OBJECT-TYPE
Current source of CMCIII PU (1) unknown (2) AC Adapter Power Supply (3) Terminal Strip (4) poe: Power Over Ethernet (5) usb: Universal Serial Bus.
1.3.6.1.4.1.2606.7.2.9INTEGER {unknown(1), acAdapter(2), terminalStrip(3), poe(4), usb(5)}read-onlycurrent
cmcIIICan0CurrentConsumption
OBJECT-TYPE
Maximal current consumption required by CANopen fieldbus 1.
1.3.6.1.4.1.2606.7.2.10Integer32read-onlycurrent
cmcIIICan1CurrentConsumption
OBJECT-TYPE
Maximal current consumption required by CANopen fieldbus 2.
1.3.6.1.4.1.2606.7.2.11Integer32read-onlycurrent
cmcIIIUnitUpTime
OBJECT-TYPE
Operating time of CMCIII PU in seconds since an epoch.
1.3.6.1.4.1.2606.7.2.12Unsigned32read-onlycurrent
cmcIIIUnitMode
OBJECT-TYPE
Current status mode of CMCIII PU and all subsystems (1) local init ini progress (2) start local system first time (3) first start delay (4) restart bus system, reread configuration (5) locally online (6) collect all slaves at the bus (7) reorganize bus (8) up and running (9) prepare for sensor upgrade (10) upgrade sensors (11) gentle termination.
1.3.6.1.4.1.2606.7.2.13INTEGER {localInit(1), start(2), pwrDelay(3), restartBus(4), localOnline(5), collectSlaves(6), reorganizeBus(7), online(8), prepareUpgrade(9), upgradeSensor(10), terminate(11)}read-onlycurrent
cmcIIIUnitLoadTable
OBJECT-TYPE
A list of system load entries.
1.3.6.1.4.1.2606.7.2.14not-accessiblecurrent
cmcIIIUnitLoadEntry
OBJECT-TYPE
Entries of system load table.
1.3.6.1.4.1.2606.7.2.14.1not-accessiblecurrent
cmcIIIUnitLoadIndex
OBJECT-TYPE
Index for the system load table. These are the past minutes the load is given for.
1.3.6.1.4.1.2606.7.2.14.1.1Unsigned32 (1..10)not-accessiblecurrent
cmcIIIUnitLoadAverage
OBJECT-TYPE
System load average multiplied by 100.
1.3.6.1.4.1.2606.7.2.14.1.2Unsigned32read-onlycurrent
cmcIIISetup
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3
cmcIIILastChangeSetup
OBJECT-TYPE
Last change of configuration according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.3.1Unsigned32read-onlycurrent
cmcIIISetupGeneral
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.2
cmcIIISetTempUnit
OBJECT-TYPE
Unit of all temperature values and setpoints.
1.3.6.1.4.1.2606.7.3.2.1INTEGER {celsius(1), fahrenheit(2)}read-writecurrent
cmcIIISetBeeper
OBJECT-TYPE
Audible alarm in CMCIII unit: (1) beeper is off (general) (2) beeper is on.
1.3.6.1.4.1.2606.7.3.2.2INTEGER {off(1), on(2)}read-writecurrent
cmcIIIQuitRelay
OBJECT-TYPE
Enable or disable acknowledging currently active alarm relay (with 'C' on CMCIII).
1.3.6.1.4.1.2606.7.3.2.3INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIILogicRelay
OBJECT-TYPE
Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay disabled.
1.3.6.1.4.1.2606.7.3.2.4INTEGER {closeAtAlarm(1), openAtAlarm(2), disabled(3)}read-writecurrent
cmcIIIUnitMsgRelay
OBJECT-TYPE
Alarm relay in case of Device Messages (detect, lost, changed..): (1) Relay disabled, relay will not switch in case of a device message (2) Relay enabled, relay will switch in case of a unit message.
1.3.6.1.4.1.2606.7.3.2.5INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIIFunctionRelay
OBJECT-TYPE
Logic of alarm relay: (1) Relay will switch in case of a warning only (2) Relay will switch in case of an alarm only (3) Relay will switch in case of an alarm or warning.
1.3.6.1.4.1.2606.7.3.2.6INTEGER {warningOnly(1), alarmOnly(2), warningOrAlarm(3)}read-writecurrent
cmcIIITimeZone
OBJECT-TYPE
Time Zone 0 : (GMT-12:00) International Date Line West 1 : (GMT-11:00) Midway Island, Samoa 2 : (GMT-10:00) Hawaii 3 : (GMT-09:00) Alaska 4 : (GMT-08:00) Pacific Time (US and Canada), Tijuana 5 : (GMT-07:00) Arizona 6 : (GMT-07:00) Chihuahua, La Paz, Mazatlan 7 : (GMT-07:00) Mountain Time (US & Canada) 8 : (GMT-06:00) Central America 9 : (GMT-06:00) Central Time (US and Canada) 10 : (GMT-06:00) Guadalajara, Mexico City, Monterrey 11 : (GMT-06:00) Saskatchewan 12 : (GMT-05:00) Bogota, Lima, Quito 13 : (GMT-05:00) Eastern Time (Us and Canada) 14 : (GMT-05:00) Indiana (East) 15 : (GMT-04:00) Atlantic Time (Canada) 16 : (GMT-04:00) Caracas, La Paz 17 : (GMT-04:00) Santiago 18 : (GMT-03:30) Newfoundland 19 : (GMT-03:00) Brasilia 20 : (GMT-03:00) Buenos Aires, Georgetown 21 : (GMT-03:00) Greenland 22 : (GMT-02:00) Mid-Atlantic 23 : (GMT-01:00) Azores 24 : (GMT-01:00) Cape Verde Is. 25 : (GMT) Casablanca, Monrovia 26 : (GMT) Greenwich Mean Time : Dublin, Lisbon, London 27 : (GMT+01:00) Amsterdam, Berlin, Bern, Rome, Vienna 28 : (GMT+01:00) Belgrade, Bratislava, Budapest, Prague 29 : (GMT+01:00) Brussels, Copenhagen, Madrid, Paris 30 : (GMT+01:00) Sarajevo, Skopje, Warsaw, Zagreb 31 : (GMT+01:00) West Central Africa 32 : (GMT+02:00) Athens, Istanbul, Minsk 33 : (GMT+02:00) Bucharest 34 : (GMT+02:00) Harare, Pretoria 35 : (GMT+02:00) Helsinki, Kyiv, Sofia 36 : (GMT+02:00) Riga, Tallinn, Vilnius 37 : (GMT+02:00) Jerusalem 38 : (GMT+03:00) Baghdad 39 : (GMT+03:00) Kuwait, Riyadh 40 : (GMT+03:00) Moscow, St. Petersburg, Volgograd 41 : (GMT+03:00) Nairobi 42 : (GMT+03:30) Tehran 43 : (GMT+04:00) Abu Dhabi, Muscat 44 : (GMT+04:00) Baku, Tbilisi, Yerevan 45 : (GMT+04:30) Kabul 46 : (GMT+05:00) Ekaterinburg 47 : (GMT+05:00) Islamabad, Karachi, Tashkent 48 : (GMT+05:30) Chennai, Kolkata, Mumbai, New Delhi 49 : (GMT+05:45) Kathmandu 50 : (GMT+06:00) Almaty, Novosibirsk 51 : (GMT+06:00) Astana, Dhaka 52 : (GMT+06:00) Sri Jayawardenepura 53 : (GMT+06:30) Rangoon 54 : (GMT+07:00) Bangkok, Hanoi, Jakarta 55 : (GMT+07:00) Krasnoyarsk 56 : (GMT+08:00) Beijing, Chongqing, Hong Kong, Urumqi 57 : (GMT+08:00) Irkutsk, Ulaan Bataar 58 : (GMT+08:00) Kuala Lumpur, Singapore 59 : (GMT+08:00) Perth 60 : (GMT+08:00) Taipei 61 : (GMT+09:00) Osaka, Sapporo, Tokyo 62 : (GMT+09:00) Seoul 63 : (GMT+09:00) Yakutsk 64 : (GMT+09:30) Adelaide 65 : (GMT+09:30) Darwin 66 : (GMT+10:00) Brisbane 67 : (GMT+10:00) Canberra, Melbourne, Sydney 68 : (GMT+10:00) Guam, Port Moresby 69 : (GMT+10:00) Hobart 70 : (GMT+10:00) Vladivostok 71 : (GMT+11:00) Magadan, Solomon Is., New Caledonia 72 : (GMT+12:00) Auckland, Wellington 73 : (GMT+12:00) Fiji, Kamchatka, Marshall Is. 74 : (GMT+13:00) Nukualofa.
1.3.6.1.4.1.2606.7.3.2.7Integer32 (0..74)read-writecurrent
cmcIIISetupDate
OBJECT-TYPE
Actual date in format DD.MM.YYYY Use UTC date to set date.
1.3.6.1.4.1.2606.7.3.2.8DisplayString (SIZE(10))read-writecurrent
cmcIIISetupTime
OBJECT-TYPE
Actual time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59). Use UTC time to set time.
1.3.6.1.4.1.2606.7.3.2.9DisplayString (SIZE(8))read-writecurrent
cmcIIIWebAccess
OBJECT-TYPE
Web access status: (0) httpEnabled : http protocol is enabled (1) httpsEnabled : https protocol is enabled.
1.3.6.1.4.1.2606.7.3.2.10Bits {httpEnabled(0), httpsEnabled(1)}read-writecurrent
cmcIIIHttpPort
OBJECT-TYPE
TCP/IP port of HTTP daemon.
1.3.6.1.4.1.2606.7.3.2.11Unsigned32 (1..65535)read-writecurrent
cmcIIIHttpsPort
OBJECT-TYPE
TCP/IP port of HTTPS daemon.
1.3.6.1.4.1.2606.7.3.2.12Unsigned32 (1..65535)read-writecurrent
cmcIIIFtpAccess
OBJECT-TYPE
Ftp access: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.2.13INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIIFtpPort
OBJECT-TYPE
TCP/IP port of FTP daemon.
1.3.6.1.4.1.2606.7.3.2.14Unsigned32 (1..65535)read-writecurrent
cmcIIISshAccess
OBJECT-TYPE
Ssh access: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.2.15INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIISshPort
OBJECT-TYPE
TCP/IP port of SSH daemon.
1.3.6.1.4.1.2606.7.3.2.16Unsigned32 (1..65535)read-writecurrent
cmcIIITelnetAccess
OBJECT-TYPE
Telnet access: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.2.17INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIITelnetPort
OBJECT-TYPE
TCP/IP port of telnet daemon.
1.3.6.1.4.1.2606.7.3.2.18Unsigned32 (1..65535)read-writecurrent
cmcIIILanguage
OBJECT-TYPE
Language: (1) English. (2) German, (3) French, (4) Spanish, (5) Portuguese, (6) Russian, (7) Chinese (8) Japanese.
1.3.6.1.4.1.2606.7.3.2.19INTEGER {english(1), german(2), french(3), spanish(4), portuguese(5), russian(6), chinese(7), japanese(8)}read-writecurrent
cmcIIIOpcUaAccess
OBJECT-TYPE
OPC UA access: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.2.20INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIIOpcUaPort
OBJECT-TYPE
TCP/IP port of OPC UA daemon.
1.3.6.1.4.1.2606.7.3.2.21Unsigned32 (1..65535)read-writecurrent
cmcIIISetupTimer
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.3
cmcIIINumberOfTimers
OBJECT-TYPE
Number of value table entries=number of outlets available on this unit.
1.3.6.1.4.1.2606.7.3.3.1Integer32read-onlycurrent
cmcIIITimerTable
OBJECT-TYPE
Headline of Timer Table.
1.3.6.1.4.1.2606.7.3.3.2not-accessiblecurrent
cmcIIITimerEntry
OBJECT-TYPE
Entries of Timer Table.
1.3.6.1.4.1.2606.7.3.3.2.1not-accessiblecurrent
cmcIIITimerIndex
OBJECT-TYPE
Index for the list of timer entries. Its value ranges between 1 and the value of cmcIIINumberOfTimers.
1.3.6.1.4.1.2606.7.3.3.2.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIITimerStatus
OBJECT-TYPE
Actual status of the timer.
1.3.6.1.4.1.2606.7.3.3.2.1.2INTEGER {switchedOff(1), switchedOn(2), noTime(3)}read-onlycurrent
cmcIIITimerDayOfWeek
OBJECT-TYPE
Selection of day of week for timer to switch.
1.3.6.1.4.1.2606.7.3.3.2.1.3INTEGER {sun(1), mon(2), tue(3), wed(4), thu(5), fri(6), sat(7), sat2sun(8), mon2fri(9), mon2sun(10)}read-writecurrent
cmcIIITimeOn
OBJECT-TYPE
Time to switch on current function, Format: HH:MM.
1.3.6.1.4.1.2606.7.3.3.2.1.4DisplayString (SIZE(5))read-writecurrent
cmcIIITimeOff
OBJECT-TYPE
Time to switch off current function, Format: HH:MM.
1.3.6.1.4.1.2606.7.3.3.2.1.5DisplayString (SIZE(5))read-writecurrent
cmcIIITimeControl
OBJECT-TYPE
Control via RTC.
1.3.6.1.4.1.2606.7.3.3.2.1.6INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIITimerFunction
OBJECT-TYPE
Function which is controlled via timer 1: Unlock of doors via keypad is disabled 2: Doors will be unlocked 3-6: sending traps to this trap receiver will be disabled 7-10: sending SMS to phone number 1..4 will be disabled 11-18: Scheduled alarm off.
1.3.6.1.4.1.2606.7.3.3.2.1.7INTEGER {disKeypads(1), unlDoors(2), disTrapRec1(3), disTrapRec2(4), disTrapRec3(5), disTrapRec4(6), disSMS1(7), disSMS2(8), disSMS3(9), disSMS4(10), schedule1(11), schedule2(12), schedule3(13), schedule4(14), schedule5(15), schedule6(16), schedule7(17), schedule8(18)}read-writecurrent
cmcIIISetupTrap
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.4
cmcIIINumberOfTrapReceivers
OBJECT-TYPE
Number of TrapReceiverTable entries. The number of trap receivers.
1.3.6.1.4.1.2606.7.3.4.1Integer32read-onlycurrent
cmcIIITrapReceiverTable
OBJECT-TYPE
A list of trap receiver entries.
1.3.6.1.4.1.2606.7.3.4.2not-accessiblecurrent
cmcIIITrapReceiverEntry
OBJECT-TYPE
Entries of trapTable.
1.3.6.1.4.1.2606.7.3.4.2.1not-accessiblecurrent
cmcIIITrapReceiverIndex
OBJECT-TYPE
Index for the trap receiver table. Its value ranges between 1 and the value of NumberOfTrapReceivers.
1.3.6.1.4.1.2606.7.3.4.2.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIITrapReceiverStatus
OBJECT-TYPE
Enable SNMP version and trap/inform type or disable trap receiver. Enumeration type snmpv3Inform(6) is not yet supported.
1.3.6.1.4.1.2606.7.3.4.2.1.2INTEGER {disabled(1), snmpv1Trap(2), snmpv2cTrap(3), snmpv2cInform(4), snmpv3Trap(5), snmpv3Inform(6)}read-writecurrent
cmcIIITrapReceiverIpAddress
OBJECT-TYPE
IP address of trap receiver.
1.3.6.1.4.1.2606.7.3.4.2.1.3DisplayString (SIZE(0..64))read-writecurrent
cmcIIISetupSMTP
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.5
cmcIIISmtpStatus
OBJECT-TYPE
SMTP (email) usage: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.5.1INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIISmtpServer
OBJECT-TYPE
IP address of SMTP server.
1.3.6.1.4.1.2606.7.3.5.2DisplayString (SIZE(0..64))read-writecurrent
cmcIIISmtpPort
OBJECT-TYPE
TCP/IP port of SMTP server.
1.3.6.1.4.1.2606.7.3.5.3Unsigned32 (1..65535)read-writecurrent
cmcIIISmtpAuth
OBJECT-TYPE
SMTP authentication usage: (1) disabled (2) enabled (3) enabled with TLS support.
1.3.6.1.4.1.2606.7.3.5.4INTEGER {disabled(1), enabled(2), enabledTls(3)}read-writecurrent
cmcIIISmtpUsername
OBJECT-TYPE
Username required to authenticate at the SMTP server.
1.3.6.1.4.1.2606.7.3.5.5DisplayString (SIZE(0..50))read-writecurrent
cmcIIISmtpPassword
OBJECT-TYPE
Password required to authenticate at the SMTP server.
1.3.6.1.4.1.2606.7.3.5.6DisplayString (SIZE(0..50))read-writecurrent
cmcIIISmtpSender
OBJECT-TYPE
Sender address (FROM:) of the SMTP message.
1.3.6.1.4.1.2606.7.3.5.7DisplayString (SIZE(0..50))read-writecurrent
cmcIIISmtpReply
OBJECT-TYPE
Reply address (REPLY:) of the SMTP message.
1.3.6.1.4.1.2606.7.3.5.8DisplayString (SIZE(0..50))read-writecurrent
cmcIIINumberOfSmtpReceivers
OBJECT-TYPE
Number of SmtpReceiverTable entries. The number of SMTP receivers.
1.3.6.1.4.1.2606.7.3.5.9Integer32read-onlycurrent
cmcIIISmtpReceiverTable
OBJECT-TYPE
A list of SMTP receiver entries.
1.3.6.1.4.1.2606.7.3.5.10not-accessiblecurrent
cmcIIISmtpReceiverEntry
OBJECT-TYPE
Entries of SMTPTable.
1.3.6.1.4.1.2606.7.3.5.10.1not-accessiblecurrent
cmcIIISmtpReceiverIndex
OBJECT-TYPE
Index for the SMTP receiver table. Its value ranges between 1 and the value of NumberOfSmtpReceivers.
1.3.6.1.4.1.2606.7.3.5.10.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIISmtpReceiverStatus
OBJECT-TYPE
Enable or disable SMTP receiver.
1.3.6.1.4.1.2606.7.3.5.10.1.2INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIISmtpReceiverAddress
OBJECT-TYPE
IP address of SMTP receiver.
1.3.6.1.4.1.2606.7.3.5.10.1.3DisplayString (SIZE(0..50))read-writecurrent
cmcIIISetupSMS
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.6
cmcIIISmsStatus
OBJECT-TYPE
SMS usage: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.6.1INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIISmsPIN
OBJECT-TYPE
SMS PIN number.
1.3.6.1.4.1.2606.7.3.6.2DisplayString (SIZE(0..10))read-writecurrent
cmcIIISmsService
OBJECT-TYPE
SMS service number.
1.3.6.1.4.1.2606.7.3.6.3DisplayString (SIZE(0..30))read-writecurrent
cmcIIISmsMSN
OBJECT-TYPE
SMS MSN for ISDN.
1.3.6.1.4.1.2606.7.3.6.4DisplayString (SIZE(0..30))read-writecurrent
cmcIIISmsPreDial
OBJECT-TYPE
SMS PreDial number.
1.3.6.1.4.1.2606.7.3.6.5DisplayString (SIZE(0..2))read-writecurrent
cmcIIINumberOfSmsReceivers
OBJECT-TYPE
Number of SmsReceiverTable entries. The number of SMS receivers.
1.3.6.1.4.1.2606.7.3.6.6Integer32read-onlycurrent
cmcIIISmsReceiverTable
OBJECT-TYPE
A list of SMS receiver entries.
1.3.6.1.4.1.2606.7.3.6.7not-accessiblecurrent
cmcIIISmsReceiverEntry
OBJECT-TYPE
Entries of SMSTable.
1.3.6.1.4.1.2606.7.3.6.7.1not-accessiblecurrent
cmcIIISmsReceiverIndex
OBJECT-TYPE
Index for the SMS receiver table. Its value ranges between 1 and the value of NumberOfSmsReceivers.
1.3.6.1.4.1.2606.7.3.6.7.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIISmsReceiverStatus
OBJECT-TYPE
Enable or disable SMS receiver.
1.3.6.1.4.1.2606.7.3.6.7.1.2INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIISmsReceiverNumber
OBJECT-TYPE
Phone number of SMS receiver.
1.3.6.1.4.1.2606.7.3.6.7.1.3DisplayString (SIZE(0..30))read-writecurrent
cmcIIISetupSysLog
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.7
cmcIIISysLogStatus
OBJECT-TYPE
SysLog usage: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.7.1INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIISysLogFacility
OBJECT-TYPE
SysLog facility local0..7.
1.3.6.1.4.1.2606.7.3.7.2INTEGER {local0(1), local1(2), local2(3), local3(4), local4(5), local5(6), local6(7), local7(8)}read-writecurrent
cmcIIISysLogServer1
OBJECT-TYPE
IP address of first SysLog server.
1.3.6.1.4.1.2606.7.3.7.3DisplayString (SIZE(0..64))read-writecurrent
cmcIIISysLogServer2
OBJECT-TYPE
IP address of second SysLog server.
1.3.6.1.4.1.2606.7.3.7.4DisplayString (SIZE(0..64))read-writecurrent
cmcIIISetupNTP
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.8
cmcIIINtpStatus
OBJECT-TYPE
NTP usage: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.8.1INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIINtpTimeZone
OBJECT-TYPE
NTP time zone, see cmcIIITimeZone for valid time zones.
1.3.6.1.4.1.2606.7.3.8.2Integer32 (0..74)read-writecurrent
cmcIIINtpServer1
OBJECT-TYPE
IP address of first NTP server.
1.3.6.1.4.1.2606.7.3.8.3DisplayString (SIZE(0..64))read-writecurrent
cmcIIINtpServer2
OBJECT-TYPE
IP address of second NTP server.
1.3.6.1.4.1.2606.7.3.8.4DisplayString (SIZE(0..64))read-writecurrent
cmcIIISetupLDAP
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.9
cmcIIILdapStatus
OBJECT-TYPE
LDAP usage: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.9.1INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIILdapServer
OBJECT-TYPE
IP address of LDAP server.
1.3.6.1.4.1.2606.7.3.9.2DisplayString (SIZE(0..64))read-writecurrent
cmcIIILdapBindDN
OBJECT-TYPE
LDAP user name.
1.3.6.1.4.1.2606.7.3.9.3DisplayString (SIZE(0..100))read-writecurrent
cmcIIILdapBindPW
OBJECT-TYPE
LDAP user password.
1.3.6.1.4.1.2606.7.3.9.4DisplayString (SIZE(0..64))read-writecurrent
cmcIIILdapUserBase
OBJECT-TYPE
LDAP base user.
1.3.6.1.4.1.2606.7.3.9.5DisplayString (SIZE(0..64))read-writecurrent
cmcIIILdapUserSearch
OBJECT-TYPE
LDAP searchpath user.
1.3.6.1.4.1.2606.7.3.9.6DisplayString (SIZE(0..200))read-writecurrent
cmcIIILdapUserAttrib
OBJECT-TYPE
LDAP attribute user.
1.3.6.1.4.1.2606.7.3.9.7DisplayString (SIZE(0..20))read-writecurrent
cmcIIILdapGroupBase
OBJECT-TYPE
LDAP base group.
1.3.6.1.4.1.2606.7.3.9.8DisplayString (SIZE(0..64))read-writecurrent
cmcIIILdapGroupSearch
OBJECT-TYPE
LDAP searchpath group.
1.3.6.1.4.1.2606.7.3.9.9DisplayString (SIZE(0..200))read-writecurrent
cmcIIILdapGroupAttrib
OBJECT-TYPE
LDAP attribute group.
1.3.6.1.4.1.2606.7.3.9.10DisplayString (SIZE(0..20))read-writecurrent
cmcIIISetupShutdown
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.10
cmcIIINumberOfShutdowns
OBJECT-TYPE
Number of cmcIIIShutdownTable entries. The number of shutdown servers.
1.3.6.1.4.1.2606.7.3.10.1Integer32read-onlycurrent
cmcIIIShutdownTable
OBJECT-TYPE
A list of shutdown entries.
1.3.6.1.4.1.2606.7.3.10.2not-accessiblecurrent
cmcIIIShutdownEntry
OBJECT-TYPE
Entries of Shutdown table.
1.3.6.1.4.1.2606.7.3.10.2.1not-accessiblecurrent
cmcIIIShutdownIndex
OBJECT-TYPE
Index for the shutdown server table. Its value ranges between 1 and the value of cmcIIINumberOfShutdowns.
1.3.6.1.4.1.2606.7.3.10.2.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIShutdownServer
OBJECT-TYPE
IP address or name of server to shutdown.
1.3.6.1.4.1.2606.7.3.10.2.1.2DisplayString (SIZE(0..64))read-writecurrent
cmcIIIShutdownName
OBJECT-TYPE
Name of server to shutdown.
1.3.6.1.4.1.2606.7.3.10.2.1.3DisplayString (SIZE(0..20))read-writecurrent
cmcIIIShutdownPort
OBJECT-TYPE
Port used to shutdown server.
1.3.6.1.4.1.2606.7.3.10.2.1.4Unsigned32 (1..65535)read-writecurrent
cmcIIIShutdownDelay
OBJECT-TYPE
Delay of server shutdown.
1.3.6.1.4.1.2606.7.3.10.2.1.5Unsigned32 (0..999)read-writecurrent
cmcIIIShutdownEnabled
OBJECT-TYPE
Enable or disable this server shutdown entry.
1.3.6.1.4.1.2606.7.3.10.2.1.6INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIISetupModbus
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.11
cmcIIIModbusStatus
OBJECT-TYPE
Modbus daemon running status: (1) shutdown (2) readonly (3) writeonly (4) readwrite.
1.3.6.1.4.1.2606.7.3.11.1INTEGER {shutdown(1), readonly(2), writeonly(3), readwrite(4)}read-writecurrent
cmcIIIModbusPort
OBJECT-TYPE
TCP/IP port of Modbus daemon.
1.3.6.1.4.1.2606.7.3.11.2Unsigned32 (1..65535)read-writecurrent
cmcIIINumberOfModbusSources
OBJECT-TYPE
Number of cmcIIIModbusTable entries. The number of Modbus access settings.
1.3.6.1.4.1.2606.7.3.11.3Unsigned32read-onlycurrent
cmcIIIModbusTable
OBJECT-TYPE
A list of Modbus entries.
1.3.6.1.4.1.2606.7.3.11.4not-accessiblecurrent
cmcIIIModbusEntry
OBJECT-TYPE
Entries of Modbus table.
1.3.6.1.4.1.2606.7.3.11.4.1not-accessiblecurrent
cmcIIIModbusIndex
OBJECT-TYPE
Index for the Modbus access table. Its value ranges between 1 and the value of cmcIIINumberOfModbusSources.
1.3.6.1.4.1.2606.7.3.11.4.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIModbusAccess
OBJECT-TYPE
Modbus access for this source entry: (1) noaccess (2) readonly (3) writeonly (4) readwrite This access is inferior to cmcIIIModbusStatus, e.g. readwrite access also requires readwrite status.
1.3.6.1.4.1.2606.7.3.11.4.1.2INTEGER {noaccess(1), readonly(2), writeonly(3), readwrite(4)}read-writecurrent
cmcIIIModbusSource
OBJECT-TYPE
Source to restrict Modbus access. It can either be a specific hostname, IP address, or a subnet represented as IP/MASK (e.g. 10.10.10.0/255.255.255.0), or IP/BITS (e.g. 10.10.10.0/24), or the IPv6 equivalents. The same source can be specified in several separate entries (presumably with different access tokens), and the first combination that matches the incoming request will be selected.
1.3.6.1.4.1.2606.7.3.11.4.1.3DisplayString (SIZE(0..64))read-writecurrent
cmcIIISetupRadius
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.12
cmcIIIRadiusStatus
OBJECT-TYPE
Radius usage: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.12.1INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIIRadiusServer
OBJECT-TYPE
IP address of Radius server.
1.3.6.1.4.1.2606.7.3.12.2DisplayString (SIZE(0..64))read-writecurrent
cmcIIIRadiusPort
OBJECT-TYPE
TCP/IP port of Radius server.
1.3.6.1.4.1.2606.7.3.12.3Unsigned32 (1..65535)read-writecurrent
cmcIIIRadiusPassword
OBJECT-TYPE
Password required to authenticate at the Radius server.
1.3.6.1.4.1.2606.7.3.12.4DisplayString (SIZE(0..20))read-writecurrent
cmcIIIRadiusGroupMode
OBJECT-TYPE
Radius group method: (1) manual (2) byAttribute.
1.3.6.1.4.1.2606.7.3.12.5INTEGER {manual(1), byAttribute(2)}read-writecurrent
cmcIIIRadiusGroupId
OBJECT-TYPE
Radius group id.
1.3.6.1.4.1.2606.7.3.12.6Unsigned32 (1..32)read-writecurrent
cmcIIIRadiusAuth
OBJECT-TYPE
Radius authentification method: (1) auto - not supported (2) pap (3) chap (4) mschap (5) md5.
1.3.6.1.4.1.2606.7.3.12.7INTEGER {auto(1), pap(2), chap(3), mschap(4), md5(5)}read-writecurrent
cmcIIISetupWebCam
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.3.13
cmcIIIWebCamStatus
OBJECT-TYPE
WebCam usage: (1) disabled (2) enabled.
1.3.6.1.4.1.2606.7.3.13.1INTEGER {disabled(1), enabled(2)}read-writecurrent
cmcIIIWebCamServer
OBJECT-TYPE
IP address of WebCam.
1.3.6.1.4.1.2606.7.3.13.2DisplayString (SIZE(0..64))read-writecurrent
cmcIIIWebCamUsername
OBJECT-TYPE
Username required to authenticate at the WebCam server.
1.3.6.1.4.1.2606.7.3.13.3DisplayString (SIZE(0..30))read-writecurrent
cmcIIIWebCamPassword
OBJECT-TYPE
Password required to authenticate at the WebCam server.
1.3.6.1.4.1.2606.7.3.13.4DisplayString (SIZE(0..20))read-writecurrent
cmcIIIWebCamIntervall
OBJECT-TYPE
WebCam snapshot intervall in 1/10 seconds.
1.3.6.1.4.1.2606.7.3.13.5Unsigned32 (5..100)read-writecurrent
cmcIIIWebCamNumberofImages
OBJECT-TYPE
WebCam number of images per event.
1.3.6.1.4.1.2606.7.3.13.6Unsigned32 (1..16)read-writecurrent
cmcIIIWebCamDestination
OBJECT-TYPE
WebCam storage destination: (1) usb (2) sd.
1.3.6.1.4.1.2606.7.3.13.7INTEGER {usb(1), sd(2)}read-writecurrent
cmcIIIDevice
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4
cmcIIIDevs
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.1
cmcIIIDevInfo
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.1.1
cmcIIIOverallDevStatus
OBJECT-TYPE
Overall status of all devices.
1.3.6.1.4.1.2606.7.4.1.1.1INTEGER {ok(1), warning(2), alarm(3), detected(4), lost(5), changed(6), update(7)}read-onlycurrent
cmcIIINumberOfDevs
OBJECT-TYPE
Number of devices available.
1.3.6.1.4.1.2606.7.4.1.1.2Integer32read-onlycurrent
cmcIIILastChangeOverallDevStatus
OBJECT-TYPE
Timestamp of last status change of any device connected to CMCIII PU according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.1.1.3Unsigned32read-onlycurrent
cmcIIILastChangeNumberOfDevs
OBJECT-TYPE
Timestamp of last device number change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.1.1.4Unsigned32read-onlycurrent
cmcIIILastChangeDevSettings
OBJECT-TYPE
Timestamp of last setting change of any device connected to CMCIII PU according to operating time cmcIIIUnitUpTime. This timestamp will be affected by SNMP settings only!
1.3.6.1.4.1.2606.7.4.1.1.5Unsigned32read-onlycurrent
cmcIIILastChangeDevs
OBJECT-TYPE
Timestamp of last device change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.1.1.6Unsigned32read-onlycurrent
cmcIIIDevTable
OBJECT-TYPE
Headline of device table.
1.3.6.1.4.1.2606.7.4.1.2not-accessiblecurrent
cmcIIIDevEntry
OBJECT-TYPE
Entries of device table.
1.3.6.1.4.1.2606.7.4.1.2.1not-accessiblecurrent
cmcIIIDevIndex
OBJECT-TYPE
Index of device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.1Unsigned32 (1..126)not-accessiblecurrent
cmcIIIDevName
OBJECT-TYPE
Name of the device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
cmcIIIDevAlias
OBJECT-TYPE
Descriptional text for device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.3DisplayString (SIZE(0..40))read-writecurrent
cmcIIIDevType
OBJECT-TYPE
Type of device chassis connected to CMCIII PU. The authoritative identification of the device contained in the entity is allocated within the SMI cmcIIIProducts subtree (1.3.6.1.4.1.2606.7.7) and provides an easy and unambiguous means for determining `what kind of box' is connected. E.g.: in cmcIIIProductChassis (1.3.6.1.4.1.2606.7.7.4.x) the placeholder x is used for 1 : Not Available 2 : Internal Device of Processing Unit 3 : Virtual Device 4 : Temperature Sensor 7030.110 5 : Temp/Humidity Sensor 7030.111 6 : Vandalism Sensor 7030.130 7 : Access Sensor 7030.120 8 : Door Lock Device 7030.200, .210 9 : Universal Sensor 7030.190 10: Sensor Gateway 7030.100 11: Power Unit 7030.050 12: Pressure Sensor 7030.150 20-25: Gateways to RS422, RS485.
1.3.6.1.4.1.2606.7.4.1.2.1.4OBJECT IDENTIFIERread-onlycurrent
cmcIIIDevNodeID
OBJECT-TYPE
Node ID of device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.5Integer32read-onlycurrent
cmcIIIDevStatus
OBJECT-TYPE
General Status of device connected to CMCIII PU (1) Device not available (2) OK (3) Device detected, confirmation required (4) Device lost (disconnected), confirmation required (5) Device changed (6) Error (7) Firmware Update pending (8) Firmware Update running.
1.3.6.1.4.1.2606.7.4.1.2.1.6INTEGER {notAvail(1), ok(2), detect(3), lost(4), changed(5), error(6), fwUpdate(7), fwUpdateRun(8)}read-onlycurrent
cmcIIIDevArtNr
OBJECT-TYPE
Article number of device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.7DisplayString (SIZE(0..10))read-onlycurrent
cmcIIIDevLocation
OBJECT-TYPE
Location of device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.8DisplayString (SIZE(0..40))read-writecurrent
cmcIIIDevBus
OBJECT-TYPE
CAN bus of device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.9INTEGER {canBus1(1), canBus2(2), virtual(3)}read-onlycurrent
cmcIIIDevPos
OBJECT-TYPE
Position (order) of device in CAN bus connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.10Integer32read-onlycurrent
cmcIIIDevFW
OBJECT-TYPE
FW version of device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.11DisplayString (SIZE(0..12))read-onlycurrent
cmcIIIDevHW
OBJECT-TYPE
HW version of device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.12DisplayString (SIZE(0..12))read-onlycurrent
cmcIIIDevSerial
OBJECT-TYPE
Serial number of device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.13DisplayString (SIZE(8))read-onlycurrent
cmcIIIDevProductWeek
OBJECT-TYPE
Production week of device connected to CMCIII PU.
1.3.6.1.4.1.2606.7.4.1.2.1.14DisplayString (SIZE(8))read-onlycurrent
cmcIIIDevLastChange
OBJECT-TYPE
Timestamp of last change of device connected to CMCIII PU according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.1.2.1.15Unsigned32read-onlycurrent
cmcIIIDevURL
OBJECT-TYPE
URL to device page of CMCIII PU (if available).
1.3.6.1.4.1.2606.7.4.1.2.1.16DisplayString (SIZE(0..30))read-onlycurrent
cmcIIIDevNumberOfVars
OBJECT-TYPE
Number of variables available on this device. This variable will give the number of rows of the variable table cmcIIIVarTable belonging to this device.
1.3.6.1.4.1.2606.7.4.1.2.1.17Integer32read-onlycurrent
cmcIIIDevNumberOfMsgs
OBJECT-TYPE
Number of messages available in this device. This variable will give the number of rows of the message table cmcIIIMsgTable belonging to this device.
1.3.6.1.4.1.2606.7.4.1.2.1.18Integer32read-onlycurrent
cmcIIIDevStatusText
OBJECT-TYPE
Latest status of this device.
1.3.6.1.4.1.2606.7.4.1.2.1.19DisplayString (SIZE(0..160))read-onlycurrent
cmcIIIDevCurrentMinConsumption
OBJECT-TYPE
Standby power consumption of device in mA.
1.3.6.1.4.1.2606.7.4.1.2.1.20Integer32read-onlycurrent
cmcIIIDevCurrentMaxConsumption
OBJECT-TYPE
Maximal power consumption of device in mA.
1.3.6.1.4.1.2606.7.4.1.2.1.21Integer32read-onlycurrent
cmcIIIDevEntPhysicalIndex
OBJECT-TYPE
Corresponding entPhysicalIndex of this device. 0 if none exists.
1.3.6.1.4.1.2606.7.4.1.2.1.22Integer32read-onlycurrent
cmcIIIDevAssembly
OBJECT-TYPE
Assembly of this device.
1.3.6.1.4.1.2606.7.4.1.2.1.23DisplayString (SIZE(0..100))read-onlycurrent
cmcIIIVars
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.2
cmcIIIVarInfo
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.2.1
cmcIIINumberOfVars
OBJECT-TYPE
Total number of variables available.
1.3.6.1.4.1.2606.7.4.2.1.1Integer32read-onlycurrent
cmcIIILastChangeNumberOfVars
OBJECT-TYPE
Timestamp of last change number of variables according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.2.1.2Unsigned32read-onlycurrent
cmcIIILastChangeVarSettings
OBJECT-TYPE
Timestamp of last setting change according to operating time cmcIIIUnitUpTime This timestamp will be affected by SNMP settings only!
1.3.6.1.4.1.2606.7.4.2.1.3Unsigned32read-onlycurrent
cmcIIILastChangeVars
OBJECT-TYPE
Timestamp of last variable change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.2.1.4Unsigned32read-onlycurrent
cmcIIIVarByQualityHide
OBJECT-TYPE
Hide entries in cmcIIIVarByQualityTable to reduce table size.
1.3.6.1.4.1.2606.7.4.2.1.5Bits {notInUse(0), undefined(1), ok(2), warning(3), alarm(4), info(5), undefinedNoValue(21), okNoValue(22), warningNoValue(23), alarmNoValue(24), infoNoValue(25)}read-writecurrent
cmcIIIDynUpdateRate
OBJECT-TYPE
Update rate in seconds to add/remove entries from cmcIIIVarIntDynTable and cmcIIIVarStrDynTable. Note: cmcIIIDynUpdateHistory (>0) has to be at least twice cmcIIIDynUpdateRate.
1.3.6.1.4.1.2606.7.4.2.1.6Unsigned32 (5..86400)read-writecurrent
cmcIIIDynUpdateHistory
OBJECT-TYPE
History range in seconds to restrict data view in cmcIIIVarIntDynTable and cmcIIIVarStrDynTable. The value 0 will disable the history range restriction completly. Note: cmcIIIDynUpdateHistory (>0) has to be at least twice cmcIIIDynUpdateRate.
1.3.6.1.4.1.2606.7.4.2.1.7Unsigned32 (0 | 10..2419200)read-writecurrent
cmcIIIVarTable
OBJECT-TYPE
Headline of variable table.
1.3.6.1.4.1.2606.7.4.2.2not-accessiblecurrent
cmcIIIVarEntry
OBJECT-TYPE
Entries of variable table.
1.3.6.1.4.1.2606.7.4.2.2.1not-accessiblecurrent
cmcIIIVarDeviceIndex
OBJECT-TYPE
Index for the device. Its value ranges between 1 and the value of cmcIIINumberOfDevs.
1.3.6.1.4.1.2606.7.4.2.2.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcIIINumberOfVars.
1.3.6.1.4.1.2606.7.4.2.2.1.2Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarName
OBJECT-TYPE
Clear name of variable.
1.3.6.1.4.1.2606.7.4.2.2.1.3DisplayString (SIZE(0..50))read-onlycurrent
cmcIIIVarType
OBJECT-TYPE
Type of variable.
1.3.6.1.4.1.2606.7.4.2.2.1.4INTEGER {description(1), value(2), setHigh(3), setWarn(4), setLow(5), hysteresis(6), status(7), statusEnum(8), setWarnLow(9), unit(10), alarmDur(11), steps(12), configPar(13), category(14), logic(15), logicEnum(16), setCntrl(17), offset(18), type(19), output(20), outputdelay(21), outputaction(22), outdelayExec(23), outputEnum(24), config(25), configNum(26), configLcpFcs(27), assembly(28), configWiring(29), sensitivity(30), accessTime(31), accessLogic(32), position(33), positionEnum(34), pin(35), sequence(36), outputPWM(40), rotation(41), circuit(42), rizoneArray(43), socketType(44), customValue(45), productDate(50), orderNr(51), devName(52), devLocation(53), currentMin(54), currentMax(55), keycode(80), command(81), commandEnum(82), commandKeypad(83), commandService(84), commandRack(85), unitType(90), swVersion(91), serialNumber(92), mountPos(93), mountPosEnum(94), gsmStatus(95), connected(96), connectedEnum(97), grouping(100), scaleValue(110), scaleUnit(111), scaleStart(112), scaleEnd(113), commandCtrl(120), commandCtrlDP(121), commandCtrlWdt(122), fanAffect(123), waterAffect(124), location(130), building(131), level(132), room(133), row(134), rack(135), operatingTime(136), numberOfRU(137), tagsQuit(138), tagsChanged(139), uid(140), ignore(254), illegal(255)}read-onlycurrent
cmcIIIVarUnit
OBJECT-TYPE
Unit of variable e. g. degree C.
1.3.6.1.4.1.2606.7.4.2.2.1.5DisplayString (SIZE(0..12))read-onlycurrent
cmcIIIVarDataType
OBJECT-TYPE
Datatype of variable.
1.3.6.1.4.1.2606.7.4.2.2.1.6INTEGER {notAvail(1), int(2), string(3), enum(4)}read-onlycurrent
cmcIIIVarScale
OBJECT-TYPE
Scaling factor of variable value, e. g. -100 -> value has to be divided by 100 +100 -> value has to be multiplied by 100.
1.3.6.1.4.1.2606.7.4.2.2.1.7Integer32read-onlycurrent
cmcIIIVarConstraints
OBJECT-TYPE
Constraints of value, e. g. [-_ a-zA-Z0-9]+ (if VariableDatatype is 'string').
1.3.6.1.4.1.2606.7.4.2.2.1.8DisplayString (SIZE(0..64))read-onlycurrent
cmcIIIVarSteps
OBJECT-TYPE
Steps of variable value (resolution).
1.3.6.1.4.1.2606.7.4.2.2.1.9Integer32read-onlycurrent
cmcIIIVarValueStr
OBJECT-TYPE
Value as string, including sign (+/-) and unit (degree C).
1.3.6.1.4.1.2606.7.4.2.2.1.10DisplayString (SIZE(0..40))read-writecurrent
cmcIIIVarValueInt
OBJECT-TYPE
Value as integer.
1.3.6.1.4.1.2606.7.4.2.2.1.11Integer32read-writecurrent
cmcIIIVarLastChange
OBJECT-TYPE
Timestamp of last update or change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.2.2.1.12Unsigned32read-onlycurrent
cmcIIIVarAccess
OBJECT-TYPE
Access for value.
1.3.6.1.4.1.2606.7.4.2.2.1.13INTEGER {none(1), readonly(2), readwrite(3), readwriteswitch(4), readwriteextended(5)}read-onlycurrent
cmcIIIVarQuality
OBJECT-TYPE
Quality of variable.
1.3.6.1.4.1.2606.7.4.2.2.1.14INTEGER {undefined(1), ok(2), warning(3), alarm(4), info(5), undefinedNoValue(21), okNoValue(22), warningNoValue(23), alarmNoValue(24), infoNoValue(25)}read-onlycurrent
cmcIIIVarEntPhysicalIndex
OBJECT-TYPE
Corresponding entPhysicalIndex of this variable. 0 if none exists.
1.3.6.1.4.1.2606.7.4.2.2.1.15Integer32read-onlycurrent
cmcIIIVarByTypeTable
OBJECT-TYPE
Headline of variable by type table.
1.3.6.1.4.1.2606.7.4.2.3not-accessiblecurrent
cmcIIIVarByTypeEntry
OBJECT-TYPE
Entries of variable by type table.
1.3.6.1.4.1.2606.7.4.2.3.1not-accessiblecurrent
cmcIIIVarByTypeType
OBJECT-TYPE
Type of variable.
1.3.6.1.4.1.2606.7.4.2.3.1.1INTEGER {description(1), value(2), setHigh(3), setWarn(4), setLow(5), hysteresis(6), status(7), statusEnum(8), setWarnLow(9), unit(10), alarmDur(11), steps(12), configPar(13), category(14), logic(15), logicEnum(16), setCntrl(17), offset(18), type(19), output(20), outputdelay(21), outputaction(22), outdelayExec(23), outputEnum(24), config(25), configNum(26), configLcpFcs(27), assembly(28), configWiring(29), sensitivity(30), accessTime(31), accessLogic(32), position(33), positionEnum(34), pin(35), sequence(36), outputPWM(40), rotation(41), circuit(42), rizoneArray(43), socketType(44), customValue(45), productDate(50), orderNr(51), devName(52), devLocation(53), currentMin(54), currentMax(55), keycode(80), command(81), commandEnum(82), commandKeypad(83), commandService(84), commandRack(85), unitType(90), swVersion(91), serialNumber(92), mountPos(93), mountPosEnum(94), gsmStatus(95), connected(96), connectedEnum(97), grouping(100), scaleValue(110), scaleUnit(111), scaleStart(112), scaleEnd(113), commandCtrl(120), commandCtrlDP(121), location(130), building(131), level(132), room(133), row(134), rack(135), operatingTime(136), numberOfRU(137), tagsQuit(138), tagsChanged(139), uid(140), ignore(254), illegal(255)}not-accessiblecurrent
cmcIIIVarByTypeDeviceIndex
OBJECT-TYPE
Index for the device. Its value ranges between 1 and the value of cmcIIINumberOfDevs.
1.3.6.1.4.1.2606.7.4.2.3.1.2Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarByTypeIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcIIINumberOfVars.
1.3.6.1.4.1.2606.7.4.2.3.1.3Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarByTypeValueStr
OBJECT-TYPE
Value as string, including sign (+/-) and unit (degree C).
1.3.6.1.4.1.2606.7.4.2.3.1.4DisplayString (SIZE(0..40))read-onlycurrent
cmcIIIVarByTypeValueInt
OBJECT-TYPE
Value as integer.
1.3.6.1.4.1.2606.7.4.2.3.1.5Integer32read-onlycurrent
cmcIIIVarByTypeLastChange
OBJECT-TYPE
Timestamp of last update or change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.2.3.1.6Unsigned32read-onlycurrent
cmcIIIVarByQualityTable
OBJECT-TYPE
Headline of variable by quality table.
1.3.6.1.4.1.2606.7.4.2.4not-accessiblecurrent
cmcIIIVarByQualityEntry
OBJECT-TYPE
Entries of variable by quality table. The view of this table may be reduced using the bits of cmcIIIVarByQualityHide.
1.3.6.1.4.1.2606.7.4.2.4.1not-accessiblecurrent
cmcIIIVarByQualityQuality
OBJECT-TYPE
Quality of variable.
1.3.6.1.4.1.2606.7.4.2.4.1.1INTEGER {undefined(1), ok(2), warning(3), alarm(4), info(5), undefinedNoValue(21), okNoValue(22), warningNoValue(23), alarmNoValue(24), infoNoValue(25)}not-accessiblecurrent
cmcIIIVarByQualityDeviceIndex
OBJECT-TYPE
Index for the device. Its value ranges between 1 and the value of cmcIIINumberOfDevs.
1.3.6.1.4.1.2606.7.4.2.4.1.2Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarByQualityIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcIIINumberOfVars.
1.3.6.1.4.1.2606.7.4.2.4.1.3Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarByQualityValueStr
OBJECT-TYPE
Value as string, including sign (+/-) and unit (degree C).
1.3.6.1.4.1.2606.7.4.2.4.1.4DisplayString (SIZE(0..40))read-onlycurrent
cmcIIIVarByQualityValueInt
OBJECT-TYPE
Value as integer.
1.3.6.1.4.1.2606.7.4.2.4.1.5Integer32read-onlycurrent
cmcIIIVarByQualityLastChange
OBJECT-TYPE
Timestamp of last update or change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.2.4.1.6Unsigned32read-onlycurrent
cmcIIIVarIntDynTable
OBJECT-TYPE
Headline of dynamically changed variable table of cmcIIIVarDatatype int(2) or enum(4). This table is updated each cmcIIIVarDynUpdateRate seconds only. This table has variables updated/changed within the last cmcIIIVarDynUpdateHistory seconds only. This table has dynamic integer variables (cmcIIIVarDataType = int(2) or enum(4)) only.
1.3.6.1.4.1.2606.7.4.2.5not-accessiblecurrent
cmcIIIVarIntDynEntry
OBJECT-TYPE
Entries of dynamically changed table.
1.3.6.1.4.1.2606.7.4.2.5.1not-accessiblecurrent
cmcIIIVarIntDynDeviceIndex
OBJECT-TYPE
Index for the device. Its value ranges between 1 and the value of cmcIIINumberOfDevs.
1.3.6.1.4.1.2606.7.4.2.5.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarIntDynIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcIIINumberOfVars.
1.3.6.1.4.1.2606.7.4.2.5.1.2Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarIntDynLastChange
OBJECT-TYPE
Timestamp of last update or change according to operating time cmcIIIUnitUpTime. Entries may be restricted by cmcIIIDynUpdateHistory.
1.3.6.1.4.1.2606.7.4.2.5.1.3Unsigned32 (0..2147483647)not-accessiblecurrent
cmcIIIVarIntDynValue
OBJECT-TYPE
Value as integer.
1.3.6.1.4.1.2606.7.4.2.5.1.4Integer32read-onlycurrent
cmcIIIVarStrDynTable
OBJECT-TYPE
Headline of dynamically changed variable table of cmcIIIVarDataType string(3). This table is updated each cmcIIIVarDynUpdateRate seconds only. This table has variables updated/changed within the last cmcIIIVarDynUpdateHistory seconds only. This table has dynamic string variables (cmcIIIVarDataType = string(3)) only. Please note, this table will be empty in most cases as strings are rarely changing.
1.3.6.1.4.1.2606.7.4.2.6not-accessiblecurrent
cmcIIIVarStrDynEntry
OBJECT-TYPE
Entries of dynamically changed table.
1.3.6.1.4.1.2606.7.4.2.6.1not-accessiblecurrent
cmcIIIVarStrDynDeviceIndex
OBJECT-TYPE
Index for the device. Its value ranges between 1 and the value of cmcIIINumberOfDevs.
1.3.6.1.4.1.2606.7.4.2.6.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarStrDynIndex
OBJECT-TYPE
Index for the list of value entries. Its value ranges between 1 and the value of cmcIIINumberOfVars.
1.3.6.1.4.1.2606.7.4.2.6.1.2Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIVarStrDynLastChange
OBJECT-TYPE
Timestamp of last update or change according to operating time cmcIIIUnitUpTime. Entries may be restricted by cmcIIIDynUpdateHistory.
1.3.6.1.4.1.2606.7.4.2.6.1.3Unsigned32 (0..2147483647)not-accessiblecurrent
cmcIIIVarStrDynValue
OBJECT-TYPE
Value as string.
1.3.6.1.4.1.2606.7.4.2.6.1.4DisplayString (SIZE(0..40))read-onlycurrent
cmcIIIMsgs
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.3
cmcIIIMsgInfo
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.3.1
cmcIIIOverallMsgStatus
OBJECT-TYPE
Overall message status of device.
1.3.6.1.4.1.2606.7.4.3.1.1INTEGER {ok(1), warning(2), alarm(3)}read-onlycurrent
cmcIIINumberOfMsgs
OBJECT-TYPE
Number of messages. All status vars available in cmcIIIVarTable will cause a message in cmcIIIMsgTable.
1.3.6.1.4.1.2606.7.4.3.1.2Integer32read-onlycurrent
cmcIIILastChangeOverallMsgStatus
OBJECT-TYPE
Timestamp of last status change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.3.1.3Unsigned32read-onlycurrent
cmcIIILastChangeNumberOfMsgs
OBJECT-TYPE
Timestamp of last message number change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.3.1.4Unsigned32read-onlycurrent
cmcIIILastChangeMsgSettings
OBJECT-TYPE
Timestamp of last setting change according to operating time cmcIIIUnitUpTime This timestamp will be affected by SNMP settings only!
1.3.6.1.4.1.2606.7.4.3.1.5Unsigned32read-onlycurrent
cmcIIIMsgTable
OBJECT-TYPE
Headline of message table.
1.3.6.1.4.1.2606.7.4.3.2not-accessiblecurrent
cmcIIIMsgEntry
OBJECT-TYPE
Entries of message table.
1.3.6.1.4.1.2606.7.4.3.2.1not-accessiblecurrent
cmcIIIMsgDeviceIndex
OBJECT-TYPE
Index for the device. Its value ranges between 1 and the value of cmcIIINumberOfDevs.
1.3.6.1.4.1.2606.7.4.3.2.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIMsgIndex
OBJECT-TYPE
Index for the list of message entries. Its value ranges between 1 and the value of cmcIIINumberOfMsgs.
1.3.6.1.4.1.2606.7.4.3.2.1.2Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIMsgText
OBJECT-TYPE
Text for each message (entry in the table).
1.3.6.1.4.1.2606.7.4.3.2.1.3DisplayString (SIZE(0..40))read-onlycurrent
cmcIIIMsgStatus
OBJECT-TYPE
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached high warning threshold 7: analog value too low, value reached low threshold (Alarm) 8: analog value too high, value reached high threshold (Alarm) 9: warning of analog value, value reached low warning threshold 10: output is set to OFF 11: output is set to ON 12: door is open 13: door is closed 14: door is locked 15: door is unlocked by remote input, e.g. external card reader 16: door is unlocked by reader or keypad connected 17: door is unlocked by SNMP set command 18: door is unlocked by WEB 19: door is unlocked by timer 20: no access, wrong key code or card number 21: lost 22: detected 23: battery low, wireless sensor 24: sensor cable broken 25: sensor cable short 26: sensor calibration in progress 27: sensor is inactive 28: sensor is active 29: no Power (PSM) 30: read only (SD, USB-Stick) 31: control boards of LCP exchanged.
1.3.6.1.4.1.2606.7.4.3.2.1.4INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), highWarn(6), lowAlarm(7), highAlarm(8), lowWarn(9), setOff(10), setOn(11), open(12), closed(13), locked(14), unlRemote(15), doorOpen(16), service(17), standby(18), busy(19), noAccess(20), lost(21), detected(22), lowVoltage(23), probeopen(24), probeshort(25), calibration(26), inactive(27), active(28), noPower(29), readOnly(30), exchanged(31)}read-onlycurrent
cmcIIIMsgRelay
OBJECT-TYPE
Setup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay.
1.3.6.1.4.1.2606.7.4.3.2.1.5INTEGER {disable(1), enable(2)}read-writecurrent
cmcIIIMsgBeeper
OBJECT-TYPE
Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm.
1.3.6.1.4.1.2606.7.4.3.2.1.6INTEGER {disable(1), enable(2)}read-writecurrent
cmcIIIMsgTrap
OBJECT-TYPE
Each bit is representing an entry of cmcIIITrapReceiverTable. If the corresponding cmcIIITrapReceiverStatus is enabled setting this bit enables sending messages to this receiver.
1.3.6.1.4.1.2606.7.4.3.2.1.7Bits {receiver1(0), receiver2(1), receiver3(2), receiver4(3), receiver5(4), receiver6(5), receiver7(6), receiver8(7), receiver9(8), receiver10(9), receiver11(10), receiver12(11), receiver13(12), receiver14(13), receiver15(14), receiver16(15)}read-writecurrent
cmcIIIMsgSMTP
OBJECT-TYPE
Each bit is representing an entry of cmcIIISmtpReceiverTable. If the corresponding cmcIIISmtpReceiverStatus is enabled setting this bit enables sending messages to this receiver.
1.3.6.1.4.1.2606.7.4.3.2.1.8Bits {receiver1(0), receiver2(1), receiver3(2), receiver4(3), receiver5(4), receiver6(5), receiver7(6), receiver8(7), receiver9(8), receiver10(9), receiver11(10), receiver12(11), receiver13(12), receiver14(13), receiver15(14), receiver16(15)}read-writecurrent
cmcIIIMsgSMS
OBJECT-TYPE
Each bit is representing an entry of cmcIIISmsReceiverTable. If the corresponding cmcIIISmsReceiverStatus is enabled setting this bit enables sending messages to this receiver.
1.3.6.1.4.1.2606.7.4.3.2.1.9Bits {receiver1(0), receiver2(1), receiver3(2), receiver4(3), receiver5(4), receiver6(5), receiver7(6), receiver8(7), receiver9(8), receiver10(9), receiver11(10), receiver12(11), receiver13(12), receiver14(13), receiver15(14), receiver16(15)}read-writecurrent
cmcIIIMsgQuit
OBJECT-TYPE
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key.
1.3.6.1.4.1.2606.7.4.3.2.1.10INTEGER {auto(1), manual(2)}read-writecurrent
cmcIIIMsgDelay
OBJECT-TYPE
Delay of alarm condition.
1.3.6.1.4.1.2606.7.4.3.2.1.11Unsigned32read-writecurrent
cmcIIIMsgSchedAlarmOff
OBJECT-TYPE
Alarm condition disabled by scheduler.
1.3.6.1.4.1.2606.7.4.3.2.1.12Integer32read-writecurrent
cmcIIIMsgQuality
OBJECT-TYPE
Quality of variable.
1.3.6.1.4.1.2606.7.4.3.2.1.13INTEGER {undefined(1), ok(2), warning(3), alarm(4), info(5), undefinedNoValue(21), okNoValue(22), warningNoValue(23), alarmNoValue(24), infoNoValue(25)}read-onlycurrent
cmcIIIMsgVarIdx
OBJECT-TYPE
Index of variable 'Status' in variable table generating this message.
1.3.6.1.4.1.2606.7.4.3.2.1.14Integer32read-onlycurrent
cmcIIIMsgVarValueIdx
OBJECT-TYPE
Index of variable 'Value' in the variable table.
1.3.6.1.4.1.2606.7.4.3.2.1.15Integer32read-writecurrent
cmcIIIMsgStatusText
OBJECT-TYPE
Message status text.
1.3.6.1.4.1.2606.7.4.3.2.1.16DisplayString (SIZE(0..160))read-onlycurrent
cmcIIIDrcs
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.4
cmcIIIDrcInfo
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.4.1
cmcIIIOverallDrcStatus
OBJECT-TYPE
Overall DRC status of devices.
1.3.6.1.4.1.2606.7.4.4.1.1INTEGER {ok(1), warning(2), alarm(3)}read-onlycurrent
cmcIIINumberOfDrcs
OBJECT-TYPE
Number of DRCs available.
1.3.6.1.4.1.2606.7.4.4.1.2Unsigned32read-onlycurrent
cmcIIIOverallLastChangeDrcStatus
OBJECT-TYPE
Overall timestamp of last DRC change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.4.1.3Unsigned32read-onlycurrent
cmcIIILastChangeNumberOfDrcs
OBJECT-TYPE
Overall timestamp of last DRC number change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.4.1.4Unsigned32read-onlycurrent
cmcIIIOverallDrcUtilization
OBJECT-TYPE
Percentage of occupied RUs.
1.3.6.1.4.1.2606.7.4.4.1.5Unsigned32 (0..100)read-onlycurrent
cmcIIIOverallDrcPower
OBJECT-TYPE
Total Power in Watts, calculated from all cmcIIITotalDrcPower -values.
1.3.6.1.4.1.2606.7.4.4.1.6Unsigned32read-onlycurrent
cmcIIIDrcTable
OBJECT-TYPE
Headline of DRC table.
1.3.6.1.4.1.2606.7.4.4.2not-accessiblecurrent
cmcIIIDrcEntry
OBJECT-TYPE
Entries of DRC table.
1.3.6.1.4.1.2606.7.4.4.2.1not-accessiblecurrent
cmcIIIDrcIndex
OBJECT-TYPE
Index for the DRC. Its value ranges between 1 and the value of cmcIIINumberOfDrcs.
1.3.6.1.4.1.2606.7.4.4.2.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIIDrcStatus
OBJECT-TYPE
DRC status of device.
1.3.6.1.4.1.2606.7.4.4.2.1.2INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), service(17), lost(21), detected(22)}read-onlycurrent
cmcIIILastChangeDrcStatus
OBJECT-TYPE
Timestamp of last DRC change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.4.2.1.3Unsigned32read-onlycurrent
cmcIIIDrcUnitName
OBJECT-TYPE
Unit of Installation of DRC.
1.3.6.1.4.1.2606.7.4.4.2.1.4DisplayString (SIZE(0..10))read-writecurrent
cmcIIIDrcLocation
OBJECT-TYPE
Location of Installation of DRC.
1.3.6.1.4.1.2606.7.4.4.2.1.5DisplayString (SIZE(0..32))read-writecurrent
cmcIIIDrcBuilding
OBJECT-TYPE
Building of Installation of DRC.
1.3.6.1.4.1.2606.7.4.4.2.1.6DisplayString (SIZE(0..32))read-writecurrent
cmcIIIDrcLevel
OBJECT-TYPE
Level of Installation of DRC.
1.3.6.1.4.1.2606.7.4.4.2.1.7DisplayString (SIZE(0..32))read-writecurrent
cmcIIIDrcRoom
OBJECT-TYPE
Room of Installation of DRC.
1.3.6.1.4.1.2606.7.4.4.2.1.8DisplayString (SIZE(0..32))read-writecurrent
cmcIIIDrcRow
OBJECT-TYPE
Row of Installation of DRC.
1.3.6.1.4.1.2606.7.4.4.2.1.9DisplayString (SIZE(0..16))read-writecurrent
cmcIIIDrcRackNr
OBJECT-TYPE
Rack number of Installation of DRC.
1.3.6.1.4.1.2606.7.4.4.2.1.10DisplayString (SIZE(0..8))read-writecurrent
cmcIIIDrcMfgDate
OBJECT-TYPE
Manufacture date of DRC, format DD.MM.YYYY.
1.3.6.1.4.1.2606.7.4.4.2.1.11DisplayString (SIZE(0..10))read-onlycurrent
cmcIIIDrcSerialNr
OBJECT-TYPE
Serial number of DRC.
1.3.6.1.4.1.2606.7.4.4.2.1.12Unsigned32read-onlycurrent
cmcIIIDrcOpHours
OBJECT-TYPE
Operational hours of DRC.
1.3.6.1.4.1.2606.7.4.4.2.1.13Unsigned32read-onlycurrent
cmcIIIDrcNumberOfRU
OBJECT-TYPE
Number of RUs.
1.3.6.1.4.1.2606.7.4.4.2.1.14Unsigned32read-onlycurrent
cmcIIIDrcUtilization
OBJECT-TYPE
Percentage of occupied RUs.
1.3.6.1.4.1.2606.7.4.4.2.1.15Unsigned32 (0..100)read-onlycurrent
cmcIIITotalDrcPower
OBJECT-TYPE
Total Power in Watts, calculated from all cmcIIIDrcPower -values.
1.3.6.1.4.1.2606.7.4.4.2.1.16Unsigned32read-onlycurrent
cmcIIIDrcSwController
OBJECT-TYPE
Software version of controller.
1.3.6.1.4.1.2606.7.4.4.2.1.17DisplayString (SIZE(0..8))read-onlycurrent
cmcIIIDrcSwBootloader
OBJECT-TYPE
Software version of controller bootloader.
1.3.6.1.4.1.2606.7.4.4.2.1.18DisplayString (SIZE(0..8))read-onlycurrent
cmcIIIDrcFwController
OBJECT-TYPE
Firmware version of controller.
1.3.6.1.4.1.2606.7.4.4.2.1.19DisplayString (SIZE(0..8))read-onlycurrent
cmcIIIDrcSwAntenna
OBJECT-TYPE
Software version of antenna module.
1.3.6.1.4.1.2606.7.4.4.2.1.20DisplayString (SIZE(0..8))read-onlycurrent
cmcIIIDrcSwAntennaBL
OBJECT-TYPE
Software version of antenna modul bootloader.
1.3.6.1.4.1.2606.7.4.4.2.1.21DisplayString (SIZE(0..8))read-onlycurrent
cmcIIIDrcCommand
OBJECT-TYPE
Command (to) send to the DRC 1: no Quit command 2: Quit command 3: LED auto, LED will show status of TAG (detected, lost..) 4: LEDs of occupied RUs will be switched on 5: LEDs of free RUs will be switched on.
1.3.6.1.4.1.2606.7.4.4.2.1.22INTEGER {noQuit(1), quit(2), ledAuto(3), ledOnOccupied(4), ledOnFreeRU(5)}read-writecurrent
cmcIIITagTable
OBJECT-TYPE
Headline of DRC Tag table.
1.3.6.1.4.1.2606.7.4.4.3not-accessiblecurrent
cmcIIITagEntry
OBJECT-TYPE
Entries of tag table.
1.3.6.1.4.1.2606.7.4.4.3.1not-accessiblecurrent
cmcIIITagDrcIndex
OBJECT-TYPE
Index for the DRC. Its value ranges between 1 and the value of cmcIIINumberOfDrcs.
1.3.6.1.4.1.2606.7.4.4.3.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIITagRuIndex
OBJECT-TYPE
Index for the RU of this DRC. This is the RU for this tag.
1.3.6.1.4.1.2606.7.4.4.3.1.2Unsigned32 (1..65535)not-accessiblecurrent
cmcIIITagStatus
OBJECT-TYPE
Status of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.3INTEGER {notAvail(1), configChanged(2), error(3), ok(4), alarm(5), service(17), lost(21), detected(22)}read-onlycurrent
cmcIIITagUID
OBJECT-TYPE
UID of the tag of the unit mounted at this position (RU).
1.3.6.1.4.1.2606.7.4.4.3.1.4DisplayString (SIZE(0..16))read-onlycurrent
cmcIIITagPosition
OBJECT-TYPE
Tag position within this RU, 0,1 or 2. 0: topmost position 1: middle position 2: lowermost position.
1.3.6.1.4.1.2606.7.4.4.3.1.5Unsigned32 (0..9999)read-onlycurrent
cmcIIITagUnitFormfactor
OBJECT-TYPE
Formfactor of the chassis (number of RUs).
1.3.6.1.4.1.2606.7.4.4.3.1.6Unsigned32 (0..9999)read-writecurrent
cmcIIITagOffset
OBJECT-TYPE
Tag offset. Offset of the tag related to the topmost position (in one-third of a RU).
1.3.6.1.4.1.2606.7.4.4.3.1.7Unsigned32 (0..9999)read-writecurrent
cmcIIITagRuPosition
OBJECT-TYPE
Position (RU) of the chassis.
1.3.6.1.4.1.2606.7.4.4.3.1.8Unsigned32 (0..9999)read-onlycurrent
cmcIIITagDeviceClass
OBJECT-TYPE
Class of the device.
1.3.6.1.4.1.2606.7.4.4.3.1.9INTEGER {notDefined(1), blankingPlate(2), componentShelf(3), cableRouting(4), patchPanelCatX(5), patchPanelFibreOptic(6), ups(7), powerSupply(8), kvm(9), switch(10), monitorKeyboardDrawer(11), monitor(12), server(13), storage(14)}read-writecurrent
cmcIIITagDescName
OBJECT-TYPE
Description name of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.10DisplayString (SIZE(0..20))read-writecurrent
cmcIIITagManufacturer
OBJECT-TYPE
Manufacturer of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.11DisplayString (SIZE(0..16))read-writecurrent
cmcIIITagType
OBJECT-TYPE
Type Name of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.12DisplayString (SIZE(0..16))read-writecurrent
cmcIIITagSerialNumber
OBJECT-TYPE
Serial number of the Unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.13DisplayString (SIZE(0..16))read-writecurrent
cmcIIITagVendor
OBJECT-TYPE
Vendor of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.14DisplayString (SIZE(0..16))read-writecurrent
cmcIIITagMac1
OBJECT-TYPE
MAC address 1 of the Unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.15DisplayString (SIZE(0..17))read-writecurrent
cmcIIITagMac2
OBJECT-TYPE
MAC address 2 of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.16DisplayString (SIZE(0..17))read-writecurrent
cmcIIITagService
OBJECT-TYPE
Vendor contact of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.17DisplayString (SIZE(0..64))read-writecurrent
cmcIIITagDeviceName
OBJECT-TYPE
Name of Unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.18DisplayString (SIZE(0..32))read-writecurrent
cmcIIITagInventoryCode
OBJECT-TYPE
Inventory code of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.19DisplayString (SIZE(0..200))read-writecurrent
cmcIIITagPower
OBJECT-TYPE
Power in Watts of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.20Unsigned32read-writecurrent
cmcIIITagCurrent
OBJECT-TYPE
Current in Amperes*10 of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.21Unsigned32read-writecurrent
cmcIIITagVoltage
OBJECT-TYPE
Voltage in Volts of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.22Unsigned32read-writecurrent
cmcIIITagLastService
OBJECT-TYPE
Last service of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.23DisplayString (SIZE(0..40))read-writecurrent
cmcIIITagNextService
OBJECT-TYPE
Next service of the Unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.24DisplayString (SIZE(0..40))read-writecurrent
cmcIIITagLastUpdate
OBJECT-TYPE
Last update of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.25DisplayString (SIZE(0..20))read-writecurrent
cmcIIITagNextUpdate
OBJECT-TYPE
Next update of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.26DisplayString (SIZE(0..20))read-writecurrent
cmcIIITagInitialStart
OBJECT-TYPE
Initial start (YYYYMMDD) of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.27DisplayString (SIZE(0..8))read-writecurrent
cmcIIITagCustom
OBJECT-TYPE
Custom field of the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.28DisplayString (SIZE(0..40))read-writecurrent
cmcIIITagCommand
OBJECT-TYPE
Command (to) send to the unit at this RU.
1.3.6.1.4.1.2606.7.4.4.3.1.29INTEGER {noQuit(1), quit(2), ledAuto(3), ledOn(4)}read-writecurrent
cmcIIITagStart
OBJECT-TYPE
Start position (bottom) of the chassis of this tag. The resolution is one-third of a RU.
1.3.6.1.4.1.2606.7.4.4.3.1.30Unsigned32read-onlycurrent
cmcIIITagEnd
OBJECT-TYPE
End position (top) of the chassis of this tag. The resolution is one-third of a RU.
1.3.6.1.4.1.2606.7.4.4.3.1.31Unsigned32read-onlycurrent
cmcIIITagAntennaMap
OBJECT-TYPE
Tag position mapping to the antennas. The resolution is one-third of a RU, one RU has three antennas. Position 1 is at the bottom of the rack. This value ranges from 1 to cmcIIIDrcNumberOfRU*3.
1.3.6.1.4.1.2606.7.4.4.3.1.32Unsigned32read-onlycurrent
cmcIIIFiles
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.5
cmcIIIFileInfo
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.4.5.1
cmcIIINumberOfFiles
OBJECT-TYPE
Number of Files available.
1.3.6.1.4.1.2606.7.4.5.1.1Unsigned32read-onlycurrent
cmcIIILastChangeFiles
OBJECT-TYPE
Overall timestamp of last file change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.5.1.2Unsigned32read-onlycurrent
cmcIIILastChangeNumberOfFiles
OBJECT-TYPE
Overall timestamp of last file number change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.5.1.3Unsigned32read-onlycurrent
cmcIIIFileTable
OBJECT-TYPE
Headline of file table.
1.3.6.1.4.1.2606.7.4.5.2not-accessiblecurrent
cmcIIIFileEntry
OBJECT-TYPE
Entries of file table.
1.3.6.1.4.1.2606.7.4.5.2.1not-accessiblecurrent
cmcIIIFileIndex
OBJECT-TYPE
Index for the file. Its value ranges between 1 and the value of cmcIIINumberOfFiles.
1.3.6.1.4.1.2606.7.4.5.2.1.1Unsigned32 (1..65535)not-accessiblecurrent
cmcIIILastChangeFile
OBJECT-TYPE
Timestamp of last file change according to operating time cmcIIIUnitUpTime.
1.3.6.1.4.1.2606.7.4.5.2.1.2Unsigned32read-onlycurrent
cmcIIIFileSize
OBJECT-TYPE
Size of the file in bytes.
1.3.6.1.4.1.2606.7.4.5.2.1.3Unsigned32read-onlycurrent
cmcIIIFileChecksum
OBJECT-TYPE
Checksum of the file.
1.3.6.1.4.1.2606.7.4.5.2.1.4Unsigned32read-onlycurrent
cmcIIIFileName
OBJECT-TYPE
Name of the file.
1.3.6.1.4.1.2606.7.4.5.2.1.5DisplayString (SIZE(0..40))read-onlycurrent
cmcIIIControl
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.5
cmcIIIQuitUnit
OBJECT-TYPE
Command to quit (acknowledge) alarms of CMCIII unit. Setting to 'quit' (2) will have same result as pressing 'C' on CMCIII. Variable is automatically set back to 'noQuit' (1).
1.3.6.1.4.1.2606.7.5.1INTEGER {noQuit(1), quit(2)}read-writecurrent
cmcIIISmsQueue
OBJECT-TYPE
Fast track to send a SMS message based on configuration of cmcIIISetupSMS. Message format: MessageText TabulatorAsSeparator ReceiverPhoneNumber e.g.: Hello World!\t0123456789
1.3.6.1.4.1.2606.7.5.2DisplayString (SIZE(0..180))read-writecurrent
cmcIIIConformance
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.6
cmcIIIMibCompliances
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.6.1
cmcIIIMibGroups
OBJECT-IDENTITY
1.3.6.1.4.1.2606.7.6.2

Notifications

NameOIDStatus
alarmSensorDevice
NOTIFICATION-TYPE
Alarm of sensors of device.
1.3.6.1.4.1.2606.7.0.1current
alarmDevice
NOTIFICATION-TYPE
Alarm of device.
1.3.6.1.4.1.2606.7.0.2current
reConfigAgent
NOTIFICATION-TYPE
Agent reconfiguration.
1.3.6.1.4.1.2606.7.0.3current
shutdownAgent
NOTIFICATION-TYPE
Agent shutdown.
1.3.6.1.4.1.2606.7.0.4current

Conformance

NameOIDStatus
cmcIIIMibCompliance
MODULE-COMPLIANCE
The core compliance statement for all cmcIII implementations.
1.3.6.1.4.1.2606.7.6.1.1current
cmcIIITrapGroup
OBJECT-GROUP
Conformance group for objects contained in cmcIII notifications.
1.3.6.1.4.1.2606.7.6.2.1current
cmcIIINotificationGroup
NOTIFICATION-GROUP
The cmcIII MIB notification group.
1.3.6.1.4.1.2606.7.6.2.2current
cmcIIIInfoMibGroup
OBJECT-GROUP
Conformance group for all cmcIII base information.
1.3.6.1.4.1.2606.7.6.2.3current
cmcIIISetupMibGroup
OBJECT-GROUP
Conformance group for default cmcIII setup operations.
1.3.6.1.4.1.2606.7.6.2.4current
cmcIIIDeviceMibGroup
OBJECT-GROUP
Conformance group for all cmcIII device information.
1.3.6.1.4.1.2606.7.6.2.5current
cmcIIIControlMibGroup
OBJECT-GROUP
Conformance group for all cmcIII control operations.
1.3.6.1.4.1.2606.7.6.2.6current
cmcIIIRelayMibGroup
OBJECT-GROUP
Conformance group for cmcIII relay and beeper operations.
1.3.6.1.4.1.2606.7.6.2.7current
cmcIIISmsMibGroup
OBJECT-GROUP
Conformance group for cmcIII SMS operations.
1.3.6.1.4.1.2606.7.6.2.8current
cmcIIISmtpMibGroup
OBJECT-GROUP
Conformance group for cmcIII SMTP operations.
1.3.6.1.4.1.2606.7.6.2.9current
cmcIIISyslogMibGroup
OBJECT-GROUP
Conformance group for cmcIII syslog operations.
1.3.6.1.4.1.2606.7.6.2.10current
cmcIIITimerMibGroup
OBJECT-GROUP
Conformance group for cmcIII timer operations.
1.3.6.1.4.1.2606.7.6.2.11current
cmcIIILdapMibGroup
OBJECT-GROUP
Conformance group for cmcIII LDAP operations.
1.3.6.1.4.1.2606.7.6.2.12current
cmcIIINtpMibGroup
OBJECT-GROUP
Conformance group for cmcIII NTP operations.
1.3.6.1.4.1.2606.7.6.2.13current
cmcIIIShutdownMibGroup
OBJECT-GROUP
Conformance group for cmcIII shutdown server operations.
1.3.6.1.4.1.2606.7.6.2.14current
cmcIIIModbusMibGroup
OBJECT-GROUP
Conformance group for cmcIII modbus operations.
1.3.6.1.4.1.2606.7.6.2.15current
cmcIIIDrcMibGroup
OBJECT-GROUP
Conformance group for cmcIII Drc operations.
1.3.6.1.4.1.2606.7.6.2.16current
cmcIIIFileMibGroup
OBJECT-GROUP
Conformance group for cmcIII files.
1.3.6.1.4.1.2606.7.6.2.17current
cmcIIIRadiusMibGroup
OBJECT-GROUP
Conformance group for cmcIII Radius operations.
1.3.6.1.4.1.2606.7.6.2.18current
cmcIIIWebCamMibGroup
OBJECT-GROUP
Conformance group for cmcIII WebCam operations.
1.3.6.1.4.1.2606.7.6.2.19current