RIELLOUPS-MIB

Registered at
1.3.6.1.4.1.5491.10
Namespace
riello
Source file
RIELLOUPS-MIB
Digest
sha256:4a0bb369b210af99f132c204fd097cd3afec7533553570c4792d36f34a0cb25d

Imports

FromSymbols
RIELLO-MIBrielloMIB
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-SMICounter32, Gauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, iso
SNMPv2-TCAutonomousType, DisplayString, TEXTUAL-CONVENTION, TestAndIncr, TimeInterval, TimeStamp

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

RIELLO-MIB
RIELLOUPS-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Textual conventions

NameOIDSyntaxAccessStatus
NonNegativeInteger
TEXTUAL-CONVENTION
This data type is a non-negative value.
current
PositiveInteger
TEXTUAL-CONVENTION
This data type is a non-zero and non-negative value.
current

Objects

NameOIDSyntaxAccessStatus
rupsMIB
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10
rupsObjects
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1
rupsIdent
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.1
rupsIdentManufacturer
OBJECT-TYPE
The name of the UPS manufacturer.
1.3.6.1.4.1.5491.10.1.1.1DisplayStringread-onlymandatory
rupsIdentModel
OBJECT-TYPE
The UPS Model designation.
1.3.6.1.4.1.5491.10.1.1.2DisplayStringread-onlymandatory
rupsIdentUPSSoftwareVersion
OBJECT-TYPE
The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.
1.3.6.1.4.1.5491.10.1.1.3DisplayStringread-onlymandatory
rupsIdentAgentSoftwareVersion
OBJECT-TYPE
The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.5491.10.1.1.4DisplayStringread-onlymandatory
rupsIdentName
OBJECT-TYPE
A string identifying the UPS. This object should be set by the administrator.
1.3.6.1.4.1.5491.10.1.1.5DisplayStringread-writemandatory
rupsIdentAttachedDevices
OBJECT-TYPE
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
1.3.6.1.4.1.5491.10.1.1.6DisplayStringread-writemandatory
rupsIdentIOConfiguration
OBJECT-TYPE
The UPS IO configuration.
1.3.6.1.4.1.5491.10.1.1.7INTEGERread-onlymandatory
rupsIdentUpsType
OBJECT-TYPE
The UPS type.
1.3.6.1.4.1.5491.10.1.1.8INTEGERread-onlymandatory
rupsIdentNominalPowerVA
OBJECT-TYPE
The UPS nominal power VA.
1.3.6.1.4.1.5491.10.1.1.9INTEGERread-onlymandatory
rupsIdentNominalPowerW
OBJECT-TYPE
The UPS nominal power W.
1.3.6.1.4.1.5491.10.1.1.10INTEGERread-onlymandatory
rupsIdentBatteryVoltage
OBJECT-TYPE
The UPS nominal battery voltage.
1.3.6.1.4.1.5491.10.1.1.11INTEGERread-onlymandatory
rupsIdentBatteryCapacity
OBJECT-TYPE
The UPS nominal battery capacity.
1.3.6.1.4.1.5491.10.1.1.12INTEGERread-onlymandatory
rupsIdentOutputVoltage
OBJECT-TYPE
The UPS nominal output voltage.
1.3.6.1.4.1.5491.10.1.1.13INTEGERread-onlymandatory
rupsIdentOutputFrequency
OBJECT-TYPE
The UPS nominal output frequency.
1.3.6.1.4.1.5491.10.1.1.14INTEGERread-onlymandatory
rupsBattery
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.2
rupsBatteryStatus
OBJECT-TYPE
The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than rupsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to rupsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).
1.3.6.1.4.1.5491.10.1.2.1INTEGER {unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4)}read-onlymandatory
rupsSecondsOnBattery
OBJECT-TYPE
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
1.3.6.1.4.1.5491.10.1.2.2NonNegativeIntegerread-onlymandatory
rupsEstimatedMinutesRemaining
OBJECT-TYPE
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
1.3.6.1.4.1.5491.10.1.2.3PositiveIntegerread-onlymandatory
rupsEstimatedChargeRemaining
OBJECT-TYPE
An estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.5491.10.1.2.4INTEGERread-onlymandatory
rupsBatteryVoltage
OBJECT-TYPE
The magnitude of the present battery voltage.
1.3.6.1.4.1.5491.10.1.2.5NonNegativeIntegerread-onlymandatory
rupsBatteryCurrent
OBJECT-TYPE
The present battery current.
1.3.6.1.4.1.5491.10.1.2.6INTEGER (-2147483648..2147483647)read-onlymandatory
rupsBatteryTemperature
OBJECT-TYPE
The ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.5491.10.1.2.7INTEGER (-2147483648..2147483647)read-onlymandatory
rupsBatteryPositiveVoltage
OBJECT-TYPE
The UPS Battery positive voltage.
1.3.6.1.4.1.5491.10.1.2.8INTEGER (-2147483648..2147483647)read-onlymandatory
rupsBatteryNegativeVoltage
OBJECT-TYPE
The UPS Battery negative voltage.
1.3.6.1.4.1.5491.10.1.2.9INTEGER (-2147483648..2147483647)read-onlymandatory
rupsBatteryPositiveCurrent
OBJECT-TYPE
The UPS Battery positive current.
1.3.6.1.4.1.5491.10.1.2.10INTEGER (-2147483648..2147483647)read-onlymandatory
rupsBatteryNegativeCurrent
OBJECT-TYPE
The UPS Battery positive current.
1.3.6.1.4.1.5491.10.1.2.11INTEGER (-2147483648..2147483647)read-onlymandatory
rupsIsCharging
OBJECT-TYPE
The charging/discharging status of the battery
1.3.6.1.4.1.5491.10.1.2.12INTEGER {discharging(0), charging(1)}read-onlymandatory
rupsInput
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.3
rupsInputLineBads
OBJECT-TYPE
A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.
1.3.6.1.4.1.5491.10.1.3.1Counterread-onlymandatory
rupsInputNumLines
OBJECT-TYPE
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.5491.10.1.3.2NonNegativeIntegerread-onlymandatory
rupsInputTable
OBJECT-TYPE
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
1.3.6.1.4.1.5491.10.1.3.3not-accessiblemandatory
rupsInputEntry
OBJECT-TYPE
An entry containing information applicable to a particular input line.
1.3.6.1.4.1.5491.10.1.3.3.1not-accessiblemandatory
rupsInputLineIndex
OBJECT-TYPE
The input line identifier.
1.3.6.1.4.1.5491.10.1.3.3.1.1PositiveIntegernot-accessiblemandatory
rupsInputFrequency
OBJECT-TYPE
The present input frequency.
1.3.6.1.4.1.5491.10.1.3.3.1.2NonNegativeIntegerread-onlymandatory
rupsInputVoltage
OBJECT-TYPE
The magnitude of the present input voltage.
1.3.6.1.4.1.5491.10.1.3.3.1.3NonNegativeIntegerread-onlymandatory
rupsInputCurrent
OBJECT-TYPE
The magnitude of the present input current.
1.3.6.1.4.1.5491.10.1.3.3.1.4NonNegativeIntegerread-onlymandatory
rupsInputTruePower
OBJECT-TYPE
The magnitude of the present input true power.
1.3.6.1.4.1.5491.10.1.3.3.1.5NonNegativeIntegerread-onlymandatory
rupsOutput
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.4
rupsOutputSource
OBJECT-TYPE
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
1.3.6.1.4.1.5491.10.1.4.1INTEGER {other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7)}read-onlymandatory
rupsOutputFrequency
OBJECT-TYPE
The present output frequency.
1.3.6.1.4.1.5491.10.1.4.2NonNegativeIntegerread-onlymandatory
rupsOutputNumLines
OBJECT-TYPE
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.5491.10.1.4.3NonNegativeIntegerread-onlymandatory
rupsOutputTable
OBJECT-TYPE
A list of output table entries. The number of entries is given by the value of rupsOutputNumLines.
1.3.6.1.4.1.5491.10.1.4.4not-accessiblemandatory
rupsOutputEntry
OBJECT-TYPE
An entry containing information applicable to a particular output line.
1.3.6.1.4.1.5491.10.1.4.4.1not-accessiblemandatory
rupsOutputLineIndex
OBJECT-TYPE
The output line identifier.
1.3.6.1.4.1.5491.10.1.4.4.1.1PositiveIntegernot-accessiblemandatory
rupsOutputVoltage
OBJECT-TYPE
The present output voltage.
1.3.6.1.4.1.5491.10.1.4.4.1.2NonNegativeIntegerread-onlymandatory
rupsOutputCurrent
OBJECT-TYPE
The present output current.
1.3.6.1.4.1.5491.10.1.4.4.1.3NonNegativeIntegerread-onlymandatory
rupsOutputPower
OBJECT-TYPE
The present output true power.
1.3.6.1.4.1.5491.10.1.4.4.1.4NonNegativeIntegerread-onlymandatory
rupsOutputPercentLoad
OBJECT-TYPE
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
1.3.6.1.4.1.5491.10.1.4.4.1.5INTEGERread-onlymandatory
rupsOutputPeakCurrent
OBJECT-TYPE
The present output peak current.
1.3.6.1.4.1.5491.10.1.4.4.1.6NonNegativeIntegerread-onlymandatory
rupsBypass
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.5
rupsBypassFrequency
OBJECT-TYPE
The present bypass frequency.
1.3.6.1.4.1.5491.10.1.5.1NonNegativeIntegerread-onlymandatory
rupsBypassNumLines
OBJECT-TYPE
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
1.3.6.1.4.1.5491.10.1.5.2NonNegativeIntegerread-onlymandatory
rupsBypassTable
OBJECT-TYPE
A list of bypass table entries. The number of entries is given by the value of rupsBypassNumLines.
1.3.6.1.4.1.5491.10.1.5.3not-accessiblemandatory
rupsBypassEntry
OBJECT-TYPE
An entry containing information applicable to a particular bypass input.
1.3.6.1.4.1.5491.10.1.5.3.1not-accessiblemandatory
rupsBypassLineIndex
OBJECT-TYPE
The bypass line identifier.
1.3.6.1.4.1.5491.10.1.5.3.1.1PositiveIntegernot-accessiblemandatory
rupsBypassVoltage
OBJECT-TYPE
The present bypass voltage.
1.3.6.1.4.1.5491.10.1.5.3.1.2NonNegativeIntegerread-onlymandatory
rupsBypassCurrent
OBJECT-TYPE
The present bypass current.
1.3.6.1.4.1.5491.10.1.5.3.1.3NonNegativeIntegerread-onlymandatory
rupsBypassPower
OBJECT-TYPE
The present true power conveyed by the bypass.
1.3.6.1.4.1.5491.10.1.5.3.1.4NonNegativeIntegerread-onlymandatory
rupsAlarm
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6
rupsAlarmsPresent
OBJECT-TYPE
The present number of active alarm conditions.
1.3.6.1.4.1.5491.10.1.6.1Gaugeread-onlymandatory
rupsAlarmTable
OBJECT-TYPE
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with rupsAlarmId equal to 1, and increments the value of rupsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of rupsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because rupsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), rupsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of rupsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of rupsAlarmsPresent.
1.3.6.1.4.1.5491.10.1.6.2not-accessiblemandatory
rupsAlarmEntry
OBJECT-TYPE
An entry containing information applicable to a particular alarm.
1.3.6.1.4.1.5491.10.1.6.2.1not-accessiblemandatory
rupsAlarmId
OBJECT-TYPE
A unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.5491.10.1.6.2.1.1PositiveIntegernot-accessiblemandatory
rupsAlarmDescr
OBJECT-TYPE
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
1.3.6.1.4.1.5491.10.1.6.2.1.2OBJECT IDENTIFIERread-onlymandatory
rupsAlarmTime
OBJECT-TYPE
The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of rupsAlarmTime shall equal 0.
1.3.6.1.4.1.5491.10.1.6.2.1.3PositiveIntegerread-onlymandatory
rupsWellKnownAlarms
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3
rupsAlarmBatteryBad
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.1
rupsAlarmOnBattery
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.2
rupsAlarmLowBattery
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.3
rupsAlarmShutdownImminent
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.4
rupsAlarmTempBad
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.5
rupsAlarmFault
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.6
rupsAlarmInternal
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.7
rupsAlarmOutputOverload
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.8
rupsAlarmOnBypass
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.9
rupsAlarmBypassBad
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.6.3.10
rupsTest
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.7
rupsTestId
OBJECT-TYPE
The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the rupsTestId variable to rupsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.
1.3.6.1.4.1.5491.10.1.7.1OBJECT IDENTIFIERread-writeoptional
rupsTestSpinLock
OBJECT-TYPE
A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: try_again: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lock_value = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lock_value, upsTestId = requested_test) if (error_index == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto try_again } if (error_index == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lock_value + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.
1.3.6.1.4.1.5491.10.1.7.2TestAndIncrread-writeoptional
rupsTestResultsSummary
OBJECT-TYPE
The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
1.3.6.1.4.1.5491.10.1.7.3INTEGER {donePass(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6)}read-onlyoptional
rupsTestResultsDetail
OBJECT-TYPE
Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
1.3.6.1.4.1.5491.10.1.7.4DisplayString (SIZE(0..255))read-onlyoptional
rupsTestStartTime
OBJECT-TYPE
The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.
1.3.6.1.4.1.5491.10.1.7.5TimeStampread-onlyoptional
rupsTestElapsedTime
OBJECT-TYPE
The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.
1.3.6.1.4.1.5491.10.1.7.6TimeIntervalread-onlyoptional
rupsWellKnownTests
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.7.7
rupsTestNoTestsInitiated
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.7.7.1
rupsTestAbortTestInProgress
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.7.7.2
rupsTestGeneralSystemsTest
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.7.7.3
rupsTestQuickBatteryTest
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.7.7.4
rupsTestDeepBatteryCalibration
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.7.7.5
rupsControl
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.8
rupsShutdownType
OBJECT-TYPE
This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.
1.3.6.1.4.1.5491.10.1.8.1INTEGER {output(1), system(2)}read-writemandatory
rupsShutdownAfterDelay
OBJECT-TYPE
Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.
1.3.6.1.4.1.5491.10.1.8.2INTEGERread-writemandatory
rupsStartupAfterDelay
OBJECT-TYPE
Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.
1.3.6.1.4.1.5491.10.1.8.3INTEGERread-writemandatory
rupsRebootWithDuration
OBJECT-TYPE
Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.
1.3.6.1.4.1.5491.10.1.8.4INTEGERread-writemandatory
rupsAutoRestart
OBJECT-TYPE
Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.
1.3.6.1.4.1.5491.10.1.8.5INTEGER {on(1), off(2)}read-writemandatory
rupsTemperature
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.10
rupsSystemTemperature
OBJECT-TYPE
The present temperature.
1.3.6.1.4.1.5491.10.1.10.1INTEGERread-onlymandatory
rupsPowerTemperature1
OBJECT-TYPE
The present temperature.
1.3.6.1.4.1.5491.10.1.10.2INTEGERread-onlymandatory
rupsPowerTemperature2
OBJECT-TYPE
The present temperature.
1.3.6.1.4.1.5491.10.1.10.3INTEGERread-onlymandatory
rupsPowerTemperature3
OBJECT-TYPE
The present temperature.
1.3.6.1.4.1.5491.10.1.10.4INTEGERread-onlymandatory
rupsChargerTemperature
OBJECT-TYPE
The present temperature.
1.3.6.1.4.1.5491.10.1.10.5INTEGERread-onlymandatory
rupsBatteryPositiveTemperature
OBJECT-TYPE
The present temperature.
1.3.6.1.4.1.5491.10.1.10.6INTEGERread-onlymandatory
rupsBatteryNegativeTemperature
OBJECT-TYPE
The present temperature.
1.3.6.1.4.1.5491.10.1.10.7INTEGERread-onlymandatory
rupsBatteryExternalTemperature
OBJECT-TYPE
The present temperature.
1.3.6.1.4.1.5491.10.1.10.8INTEGERread-onlymandatory
rupsMPS
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.20
mpsAlarmGroupS
OBJECT-TYPE
The alarm group s.
1.3.6.1.4.1.5491.10.1.20.1INTEGERread-onlymandatory
mpsAlarmGroupC
OBJECT-TYPE
The alarm group c.
1.3.6.1.4.1.5491.10.1.20.2INTEGERread-onlymandatory
mpsAlarmGroupB
OBJECT-TYPE
The alarm group b.
1.3.6.1.4.1.5491.10.1.20.3INTEGERread-onlymandatory
mpsAlarmGroupR
OBJECT-TYPE
The alarm group r.
1.3.6.1.4.1.5491.10.1.20.4INTEGERread-onlymandatory
mpsAlarmGroupRI
OBJECT-TYPE
The alarm group RI.
1.3.6.1.4.1.5491.10.1.20.5INTEGERread-onlymandatory
mpsAlarmGroupI
OBJECT-TYPE
The alarm group I.
1.3.6.1.4.1.5491.10.1.20.6INTEGERread-onlymandatory
mpsAlarmGroupA0
OBJECT-TYPE
The alarm group A0.
1.3.6.1.4.1.5491.10.1.20.7INTEGERread-onlymandatory
mpsAlarmGroupA1
OBJECT-TYPE
The alarm group A1.
1.3.6.1.4.1.5491.10.1.20.8INTEGERread-onlymandatory
mpsAlarmGroupA2
OBJECT-TYPE
The alarm group A2.
1.3.6.1.4.1.5491.10.1.20.9INTEGERread-onlymandatory
mpsAlarmGroupA3
OBJECT-TYPE
The alarm group A3.
1.3.6.1.4.1.5491.10.1.20.10INTEGERread-onlymandatory
mpsAlarmGroupA4
OBJECT-TYPE
The alarm group A4.
1.3.6.1.4.1.5491.10.1.20.11INTEGERread-onlymandatory
mpsAlarmGroupA5
OBJECT-TYPE
The alarm group A5.
1.3.6.1.4.1.5491.10.1.20.12INTEGERread-onlymandatory
rupsMST
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.21
mstWarningGroupW0W1
OBJECT-TYPE
The anomaly group W0W1.
1.3.6.1.4.1.5491.10.1.21.1INTEGERread-onlymandatory
mstAnomalyGroupA0A1
OBJECT-TYPE
The anomaly group A0A1.
1.3.6.1.4.1.5491.10.1.21.2INTEGERread-onlymandatory
mstAnomalyGroupA2A3
OBJECT-TYPE
The anomaly group A2A3.
1.3.6.1.4.1.5491.10.1.21.3INTEGERread-onlymandatory
mstAnomalyGroupA4A5
OBJECT-TYPE
The anomaly group A4A5.
1.3.6.1.4.1.5491.10.1.21.4INTEGERread-onlymandatory
mstFaultGroupF0F1
OBJECT-TYPE
The fault group F0F1.
1.3.6.1.4.1.5491.10.1.21.5INTEGERread-onlymandatory
mstFaultGroupF2F3
OBJECT-TYPE
The fault group F2F3.
1.3.6.1.4.1.5491.10.1.21.6INTEGERread-onlymandatory
mstFaultGroupF4F5
OBJECT-TYPE
The fault group F4F5.
1.3.6.1.4.1.5491.10.1.21.7INTEGERread-onlymandatory
mstLockGroupL0L1
OBJECT-TYPE
The lock group L0L1.
1.3.6.1.4.1.5491.10.1.21.8INTEGERread-onlymandatory
mstLockGroupL2L3
OBJECT-TYPE
The lock group L2L3.
1.3.6.1.4.1.5491.10.1.21.9INTEGERread-onlymandatory
mstLockGroupL4L5
OBJECT-TYPE
The lock group L4L5.
1.3.6.1.4.1.5491.10.1.21.10INTEGERread-onlymandatory
mstEventGroupE0E1
OBJECT-TYPE
The event group E0E1.
1.3.6.1.4.1.5491.10.1.21.11INTEGERread-onlymandatory
rupsMPW
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.22
mpwSystemStatusGroup1
OBJECT-TYPE
The system status group 1.
1.3.6.1.4.1.5491.10.1.22.1INTEGERread-onlymandatory
mpwSystemStatusGroup2
OBJECT-TYPE
The system status group 2.
1.3.6.1.4.1.5491.10.1.22.2INTEGERread-onlymandatory
mpwSystemStatusGroup3
OBJECT-TYPE
The system status group 3.
1.3.6.1.4.1.5491.10.1.22.3INTEGERread-onlymandatory
mpwBypassModuleAlarmGroup
OBJECT-TYPE
The bypass module alarm group.
1.3.6.1.4.1.5491.10.1.22.4INTEGERread-onlymandatory
mpwPowerModule1AlarmGroup
OBJECT-TYPE
The power module 1 alarm group.
1.3.6.1.4.1.5491.10.1.22.5INTEGERread-onlymandatory
mpwPowerModule2AlarmGroup
OBJECT-TYPE
The power module 2 alarm group.
1.3.6.1.4.1.5491.10.1.22.6INTEGERread-onlymandatory
mpwPowerModule3AlarmGroup
OBJECT-TYPE
The power module 3 alarm group.
1.3.6.1.4.1.5491.10.1.22.7INTEGERread-onlymandatory
mpwPowerModule4AlarmGroup
OBJECT-TYPE
The power module 4 alarm group.
1.3.6.1.4.1.5491.10.1.22.8INTEGERread-onlymandatory
mpwPowerModule5AlarmGroup
OBJECT-TYPE
The power module 5 alarm group.
1.3.6.1.4.1.5491.10.1.22.9INTEGERread-onlymandatory
mpwPowerModule6AlarmGroup
OBJECT-TYPE
The power module 6 alarm group.
1.3.6.1.4.1.5491.10.1.22.10INTEGERread-onlymandatory
mpwPowerModule7AlarmGroup
OBJECT-TYPE
The power module 7 alarm group.
1.3.6.1.4.1.5491.10.1.22.11INTEGERread-onlymandatory
mpwBypassModuleStatus
OBJECT-TYPE
The bypass module status.
1.3.6.1.4.1.5491.10.1.22.12INTEGERread-onlymandatory
mpwPowerModule1Status
OBJECT-TYPE
The status of power module 1.
1.3.6.1.4.1.5491.10.1.22.13INTEGERread-onlymandatory
mpwPowerModule2Status
OBJECT-TYPE
The status of power module 2.
1.3.6.1.4.1.5491.10.1.22.14INTEGERread-onlymandatory
mpwPowerModule3Status
OBJECT-TYPE
The status of power module 3.
1.3.6.1.4.1.5491.10.1.22.15INTEGERread-onlymandatory
mpwPowerModule4Status
OBJECT-TYPE
The status of power module 4.
1.3.6.1.4.1.5491.10.1.22.16INTEGERread-onlymandatory
mpwPowerModule5Status
OBJECT-TYPE
The status of power module 5.
1.3.6.1.4.1.5491.10.1.22.17INTEGERread-onlymandatory
mpwPowerModule6Status
OBJECT-TYPE
The status of power module 6.
1.3.6.1.4.1.5491.10.1.22.18INTEGERread-onlymandatory
mpwPowerModule7Status
OBJECT-TYPE
The status of power module 7.
1.3.6.1.4.1.5491.10.1.22.19INTEGERread-onlymandatory
mpwControl
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.1.22.20
mpwCommandCode
OBJECT-TYPE
Command code.
1.3.6.1.4.1.5491.10.1.22.20.1INTEGERread-writemandatory
mpwShutdownDelay
OBJECT-TYPE
Shutdown delay.
1.3.6.1.4.1.5491.10.1.22.20.2INTEGERread-writemandatory
mpwRestoreDelay
OBJECT-TYPE
Restore delay.
1.3.6.1.4.1.5491.10.1.22.20.3INTEGERread-writemandatory
mpwModuleApplyCommand
OBJECT-TYPE
Module apply command
1.3.6.1.4.1.5491.10.1.22.20.4INTEGERread-writemandatory
mpwCommandResult
OBJECT-TYPE
Result of command.
1.3.6.1.4.1.5491.10.1.22.20.5INTEGERread-onlymandatory
rupsTraps
OBJECT-IDENTITY
1.3.6.1.4.1.5491.10.2

Notifications

NameOIDStatus
rupsTrapOnBattery
NOTIFICATION-TYPE
The UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery.
1.3.6.1.4.1.5491.10.2.0.1
rupsTrapTestCompleted
NOTIFICATION-TYPE
This trap is sent upon completion of a UPS diagnostic test.
1.3.6.1.4.1.5491.10.2.0.2
rupsTrapAlarmEntryAdded
NOTIFICATION-TYPE
This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for rupsAlarmOnBattery and rupsAlarmTestInProgress.
1.3.6.1.4.1.5491.10.2.0.3
rupsTrapAlarmEntryRemoved
NOTIFICATION-TYPE
This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for rupsAlarmTestInProgress.
1.3.6.1.4.1.5491.10.2.0.4