RIELLOMDU-MIB
- Registered at
- 1.3.6.1.4.1.5491.11
- Namespace
- riello
- Source file
RIELLOMDU-MIB- Digest
sha256:57f7174784b849370a24a437330b9108543f8c6646ad6754fde6f9c7b21bc812
Imports
| From | Symbols |
|---|---|
| RIELLO-MIB | rielloMIB |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
RIELLO-MIB RIELLOMDU-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| mduMIB OBJECT-IDENTITY | 1.3.6.1.4.1.5491.11 | |||
| mduIdent OBJECT-IDENTITY | 1.3.6.1.4.1.5491.11.1 | |||
| mduIdentManufacturer OBJECT-TYPE The name of the mdu manufacturer. | 1.3.6.1.4.1.5491.11.1.1 | DisplayString | read-only | mandatory |
| mduIdentModel OBJECT-TYPE The mdu Model designation. | 1.3.6.1.4.1.5491.11.1.2 | DisplayString | read-only | mandatory |
| mduIdentSoftwareVersion OBJECT-TYPE The mdu Software version. | 1.3.6.1.4.1.5491.11.1.3 | DisplayString | read-only | mandatory |
| mduIdentIOConfiguration OBJECT-TYPE The mdu input/output configuration (1 for Mono/mono, 4 for Tri/tri). | 1.3.6.1.4.1.5491.11.1.4 | INTEGER | read-only | mandatory |
| mduIdentInputSockets OBJECT-TYPE The number of mdu input sockets. | 1.3.6.1.4.1.5491.11.1.5 | INTEGER | read-only | mandatory |
| mduIdentOutputSockets OBJECT-TYPE The number of mdu output sockets. | 1.3.6.1.4.1.5491.11.1.6 | INTEGER | read-only | mandatory |
| mduIdentNominalCurrent OBJECT-TYPE The mdu nominal current (A). | 1.3.6.1.4.1.5491.11.1.7 | INTEGER | read-only | mandatory |
| mduIdentNominalVoltage OBJECT-TYPE The mdu nominal voltage (V). | 1.3.6.1.4.1.5491.11.1.8 | INTEGER | read-only | mandatory |
| mduIdentNominalFrequency OBJECT-TYPE The mdu nominal frequency (0.1 Hz). | 1.3.6.1.4.1.5491.11.1.9 | INTEGER | read-only | mandatory |
| mduStatus OBJECT-IDENTITY | 1.3.6.1.4.1.5491.11.2 | |||
| mduLineAFrequency OBJECT-TYPE The frequency of source A (0.1 Hz). | 1.3.6.1.4.1.5491.11.2.1 | INTEGER | read-only | mandatory |
| mduLineAVoltage OBJECT-TYPE The voltage of source 1 (V). | 1.3.6.1.4.1.5491.11.2.2 | INTEGER | read-only | mandatory |
| mduLineACurrent OBJECT-TYPE The current of line A (0.1 A). | 1.3.6.1.4.1.5491.11.2.3 | INTEGER | read-only | mandatory |
| mduOutput OBJECT-TYPE A list of output table entries. | 1.3.6.1.4.1.5491.11.2.4 | not-accessible | mandatory | |
| mduOutputSockets OBJECT-TYPE An entry containing information applicable to a particular output line. | 1.3.6.1.4.1.5491.11.2.4.1 | not-accessible | mandatory | |
| mduOutputLineIndex OBJECT-TYPE The line identifier. | 1.3.6.1.4.1.5491.11.2.4.1.1 | INTEGER (1..2147483647) | not-accessible | mandatory |
| mduOutputCurrent OBJECT-TYPE Output current (0.1 A) | 1.3.6.1.4.1.5491.11.2.4.1.2 | INTEGER | read-only | mandatory |
| mduOutputDisabled OBJECT-TYPE 1->line active, 2->line deactivated | 1.3.6.1.4.1.5491.11.2.4.1.3 | INTEGER {no(1), yes(2)} | read-only | mandatory |
| mduOutputOverload OBJECT-TYPE 1->line ok, 2->line deactivated for overload | 1.3.6.1.4.1.5491.11.2.4.1.4 | INTEGER | read-only | mandatory |
| mduOutputStatus OBJECT-TYPE 0=OFF 1=ON 2= Shutdown active (when a CS or a CR command is received but shutdown is not yet been executed and the Imminent time is not reached) 3= Shutdown imminent (S01 ÷ S08 code) 4= Restore active (when after that a CR command is received and the shutdown has been acted but the restore delay time is not expired) 5= Overload alarm (F01 ÷ F08 code) 6= Locked: OFF for overload (L01 ÷ L08 code) | 1.3.6.1.4.1.5491.11.2.4.1.5 | INTEGER {off(0), on(1), shutdownActive(2), shutdownImminent(3), restoreActive(4), overload(5), locked(6)} | read-only | mandatory |
| mduLowInputVoltage OBJECT-TYPE 1= yes, 0= no. | 1.3.6.1.4.1.5491.11.2.5 | INTEGER | read-only | mandatory |
| mduHighInputVoltage OBJECT-TYPE 1= yes, 0= no. | 1.3.6.1.4.1.5491.11.2.6 | INTEGER | read-only | mandatory |
| mduLowInputCurrent OBJECT-TYPE 1= yes, 0= no. | 1.3.6.1.4.1.5491.11.2.7 | INTEGER | read-only | mandatory |
| mduHighInputCurrent OBJECT-TYPE 1= yes, 0= no. | 1.3.6.1.4.1.5491.11.2.8 | INTEGER | read-only | mandatory |
| mduPowerFailAux1 OBJECT-TYPE 1= yes, 0= no. | 1.3.6.1.4.1.5491.11.2.9 | INTEGER | read-only | mandatory |
| mduPowerFailAux2 OBJECT-TYPE 1= yes, 0= no. | 1.3.6.1.4.1.5491.11.2.10 | INTEGER | read-only | mandatory |
| mduManualBypass OBJECT-TYPE 1= on manual bypass, 0= no. | 1.3.6.1.4.1.5491.11.2.11 | INTEGER | read-only | mandatory |
| mduTemperature OBJECT-TYPE The temperature (°C). | 1.3.6.1.4.1.5491.11.2.12 | INTEGER | read-only | mandatory |
| mduCommand OBJECT-IDENTITY | 1.3.6.1.4.1.5491.11.3 | |||
| mduCommandCode OBJECT-TYPE This object determines the nature of the action to be taken at the time when the countdown of the mduShutdownDelay and mduRestoreDelay objects reaches zero. Setting this object to shutdown(1) indicates that the specified sockets mduOutputSocketApplyCommand will yurn off. Setting this object to restore(2) indicates that the specified output sockets will turn on. command delete(3) will delete the applied command, test panel will perform a test of LCD panel and audible alarm | 1.3.6.1.4.1.5491.11.3.1 | INTEGER {shutdown(1), restore(2), commandDelete(3), testPanel(22)} | read-write | mandatory |
| mduShutdownDelay OBJECT-TYPE Setting this object will shutdown (i.e., turn off) either the MDU output socket by the value of mduCommandCode at the time of shutdown after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately | 1.3.6.1.4.1.5491.11.3.2 | INTEGER | read-write | mandatory |
| mduRestoreDelay OBJECT-TYPE The restore delay. | 1.3.6.1.4.1.5491.11.3.3 | INTEGER | read-write | mandatory |
| mduOutputSocketApplyCommand OBJECT-TYPE Specify the socket to apply the command, the value 0 apply to all sockets. | 1.3.6.1.4.1.5491.11.3.4 | INTEGER | read-write | mandatory |
| mduCommandResult OBJECT-TYPE The command result, refer to the follow codes: 0+mduCommandCode Command in progress 256+mduCommandCode Wrong Command code 512+mduCommandCode Command is not handled 768+mduCommandCode Parameter out of range 3584+mduCommandCode Command sent to MDU 3840+mduCommandCode Command executed | 1.3.6.1.4.1.5491.11.3.5 | INTEGER | read-only | mandatory |
| mduTraps OBJECT-IDENTITY | 1.3.6.1.4.1.5491.11.4 |
Notifications
| Name | OID | Status |
|---|---|---|
| mduNormal NOTIFICATION-TYPE This trap is sent when MDU is on normal status | 1.3.6.1.4.1.5491.11.4.0.1 | |
| mduAnomaly NOTIFICATION-TYPE This trap is sent when MDU is has some anomaly and is resent every minute | 1.3.6.1.4.1.5491.11.4.0.2 | |
| mduFault NOTIFICATION-TYPE This trap is sent when MDU is has some fault and is resent every minute | 1.3.6.1.4.1.5491.11.4.0.3 | |
| mduLock NOTIFICATION-TYPE This trap is sent when MDU is locked and is resent every minute | 1.3.6.1.4.1.5491.11.4.0.4 | |
| mduManualBypassEnabled NOTIFICATION-TYPE This trap is sent when MDU is on manual bypass and is resent every minute | 1.3.6.1.4.1.5491.11.4.0.5 |