MIBs Depot

PM8ECCMIB

Registered at
1.3.6.1.4.1.3833
Namespace
schneider
Source file
PM8ECCMIB
Digest
sha256:e381414a375eb840a498a70ffb8ce5774a4edaae364dbf2afebc0d673a67ae06

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

PM8ECCMIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Textual conventions

NameOIDSyntaxAccessStatus
AlarmLabel
type
AlarmType
type
IOPointLabel
type
IOPointType
type

Objects

NameOIDSyntaxAccessStatus
schneiderElectric
OBJECT-IDENTITY
1.3.6.1.4.1.3833
transparentFactoryEthernet
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1
equipmentProfile
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1.7
tfProducts
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1.7.255
ecc
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1.7.255.15
pm8ecc
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1.7.255.15.1
metering
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1.7.255.15.1.1
systemWiringTypeTable
OBJECT-TYPE
The wiring system type of the host meter.
1.3.6.1.4.1.3833.1.7.255.15.1.1.1not-accessiblemandatory
systemWiringTypeEntry
OBJECT-TYPE
Host Meter System Wiring Type
1.3.6.1.4.1.3833.1.7.255.15.1.1.1.1not-accessiblemandatory
swtIndex
OBJECT-TYPE
System Wiring Type Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.1.1.1.1INTEGER (1..255)read-onlymandatory
swtWiringType
OBJECT-TYPE
Single Phase Line to Neutral 2 Wire 1CT 1PT is '10' Single Phase Line to Line 2 Wire 1CT 1PT is '11' Single Phase 3-Wire 3 wire 2CT 2PT is '12' Three Phase 3 Wire 2CT 2PT is '30' Three Phase 3 Wire 3CT 2PT is '31' Three Phase 3 Wire 1CT 2PT is '32' Three Phase 4 Wire 3CT 3PT is '40' Three Phase 4 Wire 3CT 2PT is '42' Three Phase 4 Wire 1CT 3PT is '44'
1.3.6.1.4.1.3833.1.7.255.15.1.1.1.1.2INTEGER (10 | 11 | 12 | 30 | 31 | 32 | 40 | 42 | 44)read-onlymandatory
loadCurrentTable
OBJECT-TYPE
Host Meter Load Current Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.2not-accessiblemandatory
loadCurrentEntry
OBJECT-TYPE
Host Meter Load Current Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.2.1not-accessiblemandatory
lcIndex
OBJECT-TYPE
Load Current Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.1.2.1.1INTEGER (1..255)read-onlymandatory
lcIa
OBJECT-TYPE
Host Meter Load Current Phase A Units = A (Amps)
1.3.6.1.4.1.3833.1.7.255.15.1.1.2.1.2OCTET STRINGread-onlymandatory
lcIb
OBJECT-TYPE
Host Meter Load Current Phase B Units = A (Amps)
1.3.6.1.4.1.3833.1.7.255.15.1.1.2.1.3OCTET STRINGread-onlymandatory
lcIc
OBJECT-TYPE
Host Meter Load Current Phase C Units = A (Amps)
1.3.6.1.4.1.3833.1.7.255.15.1.1.2.1.4OCTET STRINGread-onlymandatory
lcIAvg
OBJECT-TYPE
Host Meter Load Current 3 Phase Average Units = A (Amps)
1.3.6.1.4.1.3833.1.7.255.15.1.1.2.1.5OCTET STRINGread-onlymandatory
powerTable
OBJECT-TYPE
Host Meter Power Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.3not-accessiblemandatory
powerEntry
OBJECT-TYPE
Host Meter Power Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.3.1not-accessiblemandatory
pIndex
OBJECT-TYPE
Power Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.1.3.1.1INTEGER (1..255)read-onlymandatory
pReal
OBJECT-TYPE
Host Meter Real Power Units = kW
1.3.6.1.4.1.3833.1.7.255.15.1.1.3.1.2OCTET STRINGread-onlymandatory
pReactive
OBJECT-TYPE
Host Meter Reactive Power Units = kVAR
1.3.6.1.4.1.3833.1.7.255.15.1.1.3.1.3OCTET STRINGread-onlymandatory
pApparent
OBJECT-TYPE
Host Meter Apparent Power Units = kVA
1.3.6.1.4.1.3833.1.7.255.15.1.1.3.1.4OCTET STRINGread-onlymandatory
powerFactorTable
OBJECT-TYPE
Host Meter Power Factor Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.4not-accessiblemandatory
powerFactorEntry
OBJECT-TYPE
Host Meter Power Factor Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.4.1not-accessiblemandatory
pfIndex
OBJECT-TYPE
Power Factor Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.1.4.1.1INTEGER (1..255)read-onlymandatory
pfPowerFactorTotal
OBJECT-TYPE
Host Meter 3 Phase Total Power Factor
1.3.6.1.4.1.3833.1.7.255.15.1.1.4.1.2OCTET STRINGread-onlymandatory
pfPowerFactorDescription
OBJECT-TYPE
Describes the current power factor Lead/Lag for IEEE mode Cap/Ind for IEC mode
1.3.6.1.4.1.3833.1.7.255.15.1.1.4.1.3OCTET STRINGread-onlymandatory
voltageTable
OBJECT-TYPE
Host Meter Voltage Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.5not-accessiblemandatory
voltageEntry
OBJECT-TYPE
Host Meter Voltage Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1not-accessiblemandatory
vIndex
OBJECT-TYPE
Voltage Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1.1INTEGER (1..255)read-onlymandatory
vVab
OBJECT-TYPE
Host Meter Voltage Line A to Line B Units = V (Volts)
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1.2OCTET STRINGread-onlymandatory
vVbc
OBJECT-TYPE
Host Meter Voltage Line B to Line C Units = V (Volts)
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1.3OCTET STRINGread-onlymandatory
vVca
OBJECT-TYPE
Host Meter Voltage Line C to Line A Units = V (Volts)
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1.4OCTET STRINGread-onlymandatory
vVllAvg
OBJECT-TYPE
Host Meter Voltage Line to Line Average Voltage Units = V (Volts)
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1.5OCTET STRINGread-onlymandatory
vVan
OBJECT-TYPE
Host Meter Voltage Line A to Neutral Units = V (Volts)
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1.6OCTET STRINGread-onlymandatory
vVbn
OBJECT-TYPE
Host Meter Voltage Line B to Neutral Units = V (Volts)
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1.7OCTET STRINGread-onlymandatory
vVcn
OBJECT-TYPE
Host Meter Voltage Line C to Neutral Units = V (Volts)
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1.8OCTET STRINGread-onlymandatory
vVlnAvg
OBJECT-TYPE
Host Meter Voltage Line to Neutral 3 Phase Average Units = V (Volts)
1.3.6.1.4.1.3833.1.7.255.15.1.1.5.1.9OCTET STRINGread-onlymandatory
frequencyTable
OBJECT-TYPE
Host Meter Frequency Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.6not-accessiblemandatory
frequencyEntry
OBJECT-TYPE
Host Meter Frequency Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.6.1not-accessiblemandatory
fIndex
OBJECT-TYPE
Frequency Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.1.6.1.1INTEGER (1..255)read-onlymandatory
fFrequency
OBJECT-TYPE
Host Meter Frequency Units = Hz
1.3.6.1.4.1.3833.1.7.255.15.1.1.6.1.2OCTET STRINGread-onlymandatory
currentDemandTable
OBJECT-TYPE
Host Meter Current Demand Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.7not-accessiblemandatory
currentDemandEntry
OBJECT-TYPE
Host Meter Current Demand Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.7.1not-accessiblemandatory
cdIndex
OBJECT-TYPE
Demand Current Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.1.7.1.1INTEGER (1..255)read-onlymandatory
cdPhase
OBJECT-TYPE
Host Meter Current Demand Phase Name
1.3.6.1.4.1.3833.1.7.255.15.1.1.7.1.2OCTET STRING (SIZE(2))read-onlymandatory
cdPresentCurrentDemand
OBJECT-TYPE
Host Meter Present Demand Current Units = A (Amps)
1.3.6.1.4.1.3833.1.7.255.15.1.1.7.1.3OCTET STRINGread-onlymandatory
cdPeakCurrentDemand
OBJECT-TYPE
Host Meter Peak Current Demand Units = A (Amps)
1.3.6.1.4.1.3833.1.7.255.15.1.1.7.1.4OCTET STRINGread-onlymandatory
cdLastCurrentDemand
OBJECT-TYPE
Host Meter Current Demand Last Interval Units = A (Amps)
1.3.6.1.4.1.3833.1.7.255.15.1.1.7.1.5OCTET STRINGread-onlymandatory
cdPeakDateTime
OBJECT-TYPE
Host Meter Peak Current Demand Date and Time
1.3.6.1.4.1.3833.1.7.255.15.1.1.7.1.6OCTET STRINGread-onlymandatory
cdResetDateTime
OBJECT-TYPE
Host Meter Date and Time of Demand Current Reset
1.3.6.1.4.1.3833.1.7.255.15.1.1.7.1.7OCTET STRINGread-onlymandatory
cdPhaseEnum
OBJECT-TYPE
Host Meter Current Demand Phase
1.3.6.1.4.1.3833.1.7.255.15.1.1.7.1.8INTEGER {currentPhaseA(1), currentPhaseB(2), currentPhaseC(3)}read-onlymandatory
powerDemandTable
OBJECT-TYPE
Host Meter Power Demand
1.3.6.1.4.1.3833.1.7.255.15.1.1.8not-accessiblemandatory
powerDemandEntry
OBJECT-TYPE
Host Meter Power Demand Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.8.1not-accessiblemandatory
pdIndex
OBJECT-TYPE
Power Demand Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.1.8.1.1INTEGER (1..255)read-onlymandatory
pdComponent
OBJECT-TYPE
Host Meter Power Demand Component Units: Real = kW Reacitve = kVAR Apparent = kVA
1.3.6.1.4.1.3833.1.7.255.15.1.1.8.1.2OCTET STRING (SIZE(4..8))read-onlymandatory
pdPresentPowerDemand
OBJECT-TYPE
Host Meter Present Demand Power
1.3.6.1.4.1.3833.1.7.255.15.1.1.8.1.3OCTET STRINGread-onlymandatory
pdPeakPowerDemand
OBJECT-TYPE
Host Meter Peak Power Demand
1.3.6.1.4.1.3833.1.7.255.15.1.1.8.1.4OCTET STRINGread-onlymandatory
pdLastPowerDemand
OBJECT-TYPE
Host Meter Power Demand Last Interval
1.3.6.1.4.1.3833.1.7.255.15.1.1.8.1.5OCTET STRINGread-onlymandatory
pdPeakDateTime
OBJECT-TYPE
Host Meter Peak Power Demand Date and Time
1.3.6.1.4.1.3833.1.7.255.15.1.1.8.1.6OCTET STRINGread-onlymandatory
pdResetDateTime
OBJECT-TYPE
Host Meter Date and Time of Power Demand Reset
1.3.6.1.4.1.3833.1.7.255.15.1.1.8.1.7OCTET STRINGread-onlymandatory
pdComponentEnum
OBJECT-TYPE
Host Meter Power Demand Component
1.3.6.1.4.1.3833.1.7.255.15.1.1.8.1.8INTEGER {realPower(1), reactivePower(2), apparentPower(3)}read-onlymandatory
energyTable
OBJECT-TYPE
Host Meter Energy Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.9not-accessiblemandatory
energyEntry
OBJECT-TYPE
Host Meter Energy Table
1.3.6.1.4.1.3833.1.7.255.15.1.1.9.1not-accessiblemandatory
eIndex
OBJECT-TYPE
Energy Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.1.9.1.1INTEGER (1..255)read-onlymandatory
eRealEnergy
OBJECT-TYPE
Host Meter Real Energy Units = Wh
1.3.6.1.4.1.3833.1.7.255.15.1.1.9.1.2OCTET STRINGread-onlymandatory
eDateTimeRealEnergyReset
OBJECT-TYPE
Host Meter Date and Time Real Energy Accumulation was reset
1.3.6.1.4.1.3833.1.7.255.15.1.1.9.1.3OCTET STRINGread-onlymandatory
eReactiveEnergy
OBJECT-TYPE
Host Meter Reactive Energy Units = VARh
1.3.6.1.4.1.3833.1.7.255.15.1.1.9.1.4OCTET STRINGread-onlymandatory
eDateTimeReactiveEnergyReset
OBJECT-TYPE
Host Meter Date and Time Reative Energy Accumulation was reset
1.3.6.1.4.1.3833.1.7.255.15.1.1.9.1.5OCTET STRINGread-onlymandatory
eApparentEnergy
OBJECT-TYPE
Host Meter Apparent Energy Units = VAh
1.3.6.1.4.1.3833.1.7.255.15.1.1.9.1.6OCTET STRINGread-onlymandatory
eDateTimeApparentEnergyReset
OBJECT-TYPE
Host Meter Date and Time Reactive Energy Accumulation was reset
1.3.6.1.4.1.3833.1.7.255.15.1.1.9.1.7OCTET STRINGread-onlymandatory
alarms
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1.7.255.15.1.2
alarmConfigurationTable
OBJECT-TYPE
Displays the current configuration of the Host Meter On-board alarms
1.3.6.1.4.1.3833.1.7.255.15.1.2.1not-accessiblemandatory
alarmConfigurationEntry
OBJECT-TYPE
Contains configuration information for the Host Meter On-board Alarms
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1not-accessiblemandatory
acIndex
OBJECT-TYPE
Alarm Configuration Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.1INTEGER (1..255)read-onlymandatory
acPosition
OBJECT-TYPE
Indicates the position of the alarm. 1 - 74
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.2INTEGER (1..74)read-onlymandatory
acAlarmLabel
OBJECT-TYPE
The name of the alarm (user configurable)
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.3AlarmLabelread-onlymandatory
acEnabled
OBJECT-TYPE
Indicates whether the alarm is enabled or not. 0 = Disabled 255 = Enabled
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.4INTEGER (0 | 255)read-onlymandatory
acStatus
OBJECT-TYPE
Indicates whether the alarm is active. 0 = Inactive 1 = Active
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.5INTEGER (0..1)read-onlymandatory
acCounter
OBJECT-TYPE
Indicates the number of times the alarm has been activated. Note: This counter resets at 32767
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.6INTEGER (0..32767)read-onlymandatory
acPriority
OBJECT-TYPE
The priority of the alarm. 0 = No Priority 1 = Low Priority 2 = Medium Priority 3 = High Priority
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.7INTEGER (0..3)read-onlymandatory
acType
OBJECT-TYPE
Indicates the type of the alarm.
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.8AlarmTyperead-onlymandatory
acAlarmList1
OBJECT-TYPE
Used for combinatorial type alarms - The position of the first alarm that is used to evaluate the alarm state.
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.9INTEGERread-onlymandatory
acAlarmList2
OBJECT-TYPE
Used for combinatorial type alarms - The position of the second alarm that is used to evaluate the alarm state.
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.10INTEGERread-onlymandatory
acAlarmList3
OBJECT-TYPE
Used for combinatorial type alarms - The position of the third alarm that is used to evaluate the alarm state.
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.11INTEGERread-onlymandatory
acAlarmList4
OBJECT-TYPE
Used for combinatorial type alarms - The position of the fourth alarm that is used to evaluate the alarm state.
1.3.6.1.4.1.3833.1.7.255.15.1.2.1.1.12INTEGERread-onlymandatory
alarmSummaryBitmapsTable
OBJECT-TYPE
Indicates the state of the Host Meter On-Board Alarms
1.3.6.1.4.1.3833.1.7.255.15.1.2.2not-accessiblemandatory
alarmSummaryBitmapsEntry
OBJECT-TYPE
Indicates the status of the Host Meter On-Board Alarms
1.3.6.1.4.1.3833.1.7.255.15.1.2.2.1not-accessiblemandatory
alSumIndex
OBJECT-TYPE
Alarm Summary Bitmap Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.2.2.1.1INTEGER (1..255)read-onlymandatory
alSumAlarms1to16
OBJECT-TYPE
Indicates the status of Alarms 1 - 16 (16-bits, bit-0 = Alarm 1)
1.3.6.1.4.1.3833.1.7.255.15.1.2.2.1.2OCTET STRING (SIZE(16))read-onlymandatory
alSumAlarms17to32
OBJECT-TYPE
Indicates the status of Alarms 17 - 32 (16-bits, bit-0 = Alarm 17)
1.3.6.1.4.1.3833.1.7.255.15.1.2.2.1.3OCTET STRING (SIZE(16))read-onlymandatory
alSumAlarms33to48
OBJECT-TYPE
Indicates the status of Alarms 33 - 48 (16-bits, bit-0 = Alarm 33)
1.3.6.1.4.1.3833.1.7.255.15.1.2.2.1.4OCTET STRING (SIZE(16))read-onlymandatory
alSumAlarms49to64
OBJECT-TYPE
Indicates the status of Alarms 49 - 64 (16-bits, bit-0 = Alarm 49)
1.3.6.1.4.1.3833.1.7.255.15.1.2.2.1.5OCTET STRING (SIZE(16))read-onlymandatory
alSumAlarms65to74
OBJECT-TYPE
Indicates the status of Alarms 65 - 74 (16-bits, bit-0 = Alarm 65, bit-9 = Alarm 74)
1.3.6.1.4.1.3833.1.7.255.15.1.2.2.1.6OCTET STRING (SIZE(16))read-onlymandatory
alarmCountersTable
OBJECT-TYPE
Host Meter On-Board Alarm Counters
1.3.6.1.4.1.3833.1.7.255.15.1.2.3not-accessiblemandatory
alarmCountersEntry
OBJECT-TYPE
Host Meter On-Board Alarm Counters
1.3.6.1.4.1.3833.1.7.255.15.1.2.3.1not-accessiblemandatory
alCntIndex
OBJECT-TYPE
Alarm Counters Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.2.3.1.1INTEGER (1..255)read-onlymandatory
alCntAlarmPosition
OBJECT-TYPE
The Host Meter Alarm Position
1.3.6.1.4.1.3833.1.7.255.15.1.2.3.1.2INTEGER (1..74)read-onlymandatory
alCntCount
OBJECT-TYPE
The number of times the Host Meter On-Board alarm has transitioned from an inactive state to an active state
1.3.6.1.4.1.3833.1.7.255.15.1.2.3.1.3INTEGER (0..65535)read-onlymandatory
io
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1.7.255.15.1.3
ioOptionIDTable
OBJECT-TYPE
I/O Option Module Installed on the Host Meter
1.3.6.1.4.1.3833.1.7.255.15.1.3.1not-accessiblemandatory
ioOptionIDEntry
OBJECT-TYPE
I/O Option Card Installed On-board the Host Meter
1.3.6.1.4.1.3833.1.7.255.15.1.3.1.1not-accessiblemandatory
ioIDIndex
OBJECT-TYPE
I/O Installed Option ID Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.3.1.1.1INTEGER (1..255)read-onlymandatory
ioIDInstalledOptionSlot1
OBJECT-TYPE
0 = Not Installed 1 = Unused 2 = IO22 3 = IO26 4 = IO 2222
1.3.6.1.4.1.3833.1.7.255.15.1.3.1.1.2INTEGER {unused(1), io-22(2), io-26(3), io-2222(4)}read-onlymandatory
ioIDInstalledOptionSlot2
OBJECT-TYPE
0 = Not Installed 1 = Unused 2 = IO22 3 = IO26 4 = IO 2222
1.3.6.1.4.1.3833.1.7.255.15.1.3.1.1.3INTEGER {unused(1), io-22(2), io-26(3), io-2222(4)}read-onlymandatory
ioConfigurationTable
OBJECT-TYPE
Displays the current I/O configuration for each I/O point
1.3.6.1.4.1.3833.1.7.255.15.1.3.2not-accessiblemandatory
ioConfigurationEntry
OBJECT-TYPE
Contains configuration information for the Host Meter On-board I/O
1.3.6.1.4.1.3833.1.7.255.15.1.3.2.1not-accessiblemandatory
iocIndex
OBJECT-TYPE
I/O Configuration Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.3.2.1.1INTEGER (1..255)read-onlymandatory
iocPointNumber
OBJECT-TYPE
The point number for this I/O Point
1.3.6.1.4.1.3833.1.7.255.15.1.3.2.1.2INTEGER (1..18)read-onlymandatory
iocLabel
OBJECT-TYPE
The name of the I/O Point (user configurable)
1.3.6.1.4.1.3833.1.7.255.15.1.3.2.1.3IOPointLabelread-onlymandatory
iocStateOrValue
OBJECT-TYPE
Displays the current value for the I/O Point Digial I/O: 1 = Active or 0 = Inactive Analog I/O: Scaled input/output value
1.3.6.1.4.1.3833.1.7.255.15.1.3.2.1.4OCTET STRINGread-onlymandatory
iocPointType
OBJECT-TYPE
The type of I/O at this point
1.3.6.1.4.1.3833.1.7.255.15.1.3.2.1.5IOPointTyperead-onlymandatory
iocMode
OBJECT-TYPE
For Digital Inputs and Outputs this object is always 0 indicating “Discrete”. For Analog Inputs and Outputs this object indicates the range of analog I/O values (used without units) 0 = 0 – 1 1 = 0 – 5 2 = 0 – 10 3 = 0 – 20 4 = 1 – 5 5 = 4 – 20 6 = -5 – 5 7 = -10 – 10 8 = -100 – 100 9 = User defined (values default to 0)
1.3.6.1.4.1.3833.1.7.255.15.1.3.2.1.6INTEGER (0..9)read-onlymandatory
iocType
OBJECT-TYPE
For Digital Inputs this object indicates input type 1 = Unused 2 = AC/DC For Digital Outputs this object indicates output type 1 = solid state relay 2 = electromechanical relay For Analog Inputs and Outputs this object indicates the digital resolution of the I/O hardware. 0 = 8-Bit, unipolar 1 = 10-Bit, unipolar 2 = 12-Bit, unipolar 3 = 14-Bit, unipolar 4 = 16-Bit, unipolar 5 = 16-Bit, bipolar with sign 6 = reserved 7 = reserved 8 = Resolution for IO2222 Voltage range 0 - 4000 9 = Resolution for IO2222 Current range 800 - 4000
1.3.6.1.4.1.3833.1.7.255.15.1.3.2.1.7INTEGERread-onlymandatory
iocCount
OBJECT-TYPE
Number of times digital I/O point has transitioned from OFF to ON
1.3.6.1.4.1.3833.1.7.255.15.1.3.2.1.8OCTET STRING (SIZE(8))read-onlymandatory
ioStatusBitmapsTable
OBJECT-TYPE
Host Meter I/O Status Bitmaps
1.3.6.1.4.1.3833.1.7.255.15.1.3.3not-accessiblemandatory
ioStatusBitmapsEntry
OBJECT-TYPE
Host Meter On-Board I/O Status Bitmaps
1.3.6.1.4.1.3833.1.7.255.15.1.3.3.1not-accessiblemandatory
ioStatIndex
OBJECT-TYPE
I/O Summary Bitmaps Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.3.3.1.1INTEGER (1..255)read-onlymandatory
ioStatSummaryBitmap
OBJECT-TYPE
Indicates the Status of the Host Meter I/O Points Bit-0 = I/O Point 1 Bit-1 = I/O Point 2 ... Bit-17 = I/O Point 18
1.3.6.1.4.1.3833.1.7.255.15.1.3.3.1.2OCTET STRING (SIZE(18))read-onlymandatory
meterSystem
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1.7.255.15.1.4
meterIdentificationTable
OBJECT-TYPE
Host Meter Identification
1.3.6.1.4.1.3833.1.7.255.15.1.4.1not-accessiblemandatory
meterIdentificationEntry
OBJECT-TYPE
Host Meter Identification
1.3.6.1.4.1.3833.1.7.255.15.1.4.1.1not-accessiblemandatory
midIndex
OBJECT-TYPE
Meter Identification Table Index
1.3.6.1.4.1.3833.1.7.255.15.1.4.1.1.1INTEGER (1..255)read-onlymandatory
midSerialNumber
OBJECT-TYPE
Host meter 32 bit Serial Number
1.3.6.1.4.1.3833.1.7.255.15.1.4.1.1.2INTEGERread-onlymandatory
midFirmwareVersion
OBJECT-TYPE
Host Meter Firmware Version
1.3.6.1.4.1.3833.1.7.255.15.1.4.1.1.3OCTET STRINGread-onlymandatory
midModelNumber
OBJECT-TYPE
Host Meter Model Number
1.3.6.1.4.1.3833.1.7.255.15.1.4.1.1.4OCTET STRINGread-onlymandatory
midDeviceName
OBJECT-TYPE
Host Meter Label plus Nameplate
1.3.6.1.4.1.3833.1.7.255.15.1.4.1.1.5OCTET STRINGread-onlymandatory
trapVariables
OBJECT-IDENTITY
1.3.6.1.4.1.3833.1.7.255.15.1.5
alarmDateAndTime
OBJECT-TYPE
The Date and Time of the alarm state change.
1.3.6.1.4.1.3833.1.7.255.15.1.5.1OCTET STRINGread-onlymandatory
alarmLabel
OBJECT-TYPE
The Descriptive Label given to the alarm
1.3.6.1.4.1.3833.1.7.255.15.1.5.2OCTET STRINGread-onlymandatory
alarmState
OBJECT-TYPE
The state of the Alarm - pickup, dropout, unary, diagnostic
1.3.6.1.4.1.3833.1.7.255.15.1.5.3OCTET STRINGread-onlymandatory
alarmValue
OBJECT-TYPE
The value of the alarm when it changed state.
1.3.6.1.4.1.3833.1.7.255.15.1.5.4INTEGERread-onlymandatory
alarmPriority
OBJECT-TYPE
The priority defined for the alarm.
1.3.6.1.4.1.3833.1.7.255.15.1.5.5INTEGER {highPriority(1), mediumPriority(2), lowPriority(3)}read-onlymandatory
mibVersion
OBJECT-TYPE
This is the current version of the MIB
1.3.6.1.4.1.3833.1.7.255.15.1.6OCTET STRINGread-onlymandatory

Notifications

NameOIDStatus
pm8OnBoardAlarmP1
NOTIFICATION-TYPE
Indicates the Host Meter On-Board Alarm system has detected a state change of an enabled alarm with a priority of 1
1.3.6.1.4.1.3833.1.7.255.15.1.0.1
pm8OnBoardAlarmP2
NOTIFICATION-TYPE
Indicates the Host Meter On-Board Alarm system has detected a state change of an enabled alarm with a priority of 2
1.3.6.1.4.1.3833.1.7.255.15.1.0.2
pm8OnBoardAlarmP3
NOTIFICATION-TYPE
Indicates the Host Meter On-Board Alarm system has detected a state change of an enabled alarm with a priority of 3
1.3.6.1.4.1.3833.1.7.255.15.1.0.3