PM-MIB
- Registered at
- 1.3.6.1.4.1.10418.17
- Last updated
- 2010-11-24 00:00
- Organization
- Avocent Corporation
- Revisions
- 2010-11-24 00:00, 2010-09-24 00:00, 2010-04-14 00:00, 2009-05-21 00:00
- Namespace
- avocent
- Source file
PM-MIB- Digest
sha256:ef247a2066101ef76b5a249e78c9573dab4dd99258168573df526cf8c42b279b
Description
This module defines the Avocent MIB extensions to PM-PDU products.
Contact
postal : Avocent Corporation 47281 Bayside Parkway Fremont, CA 94538, USA e-mail : Technical Support techsupport@avocent.com
Imports
| From | Symbols |
|---|---|
| IF-MIB | InterfaceIndex, InterfaceIndexOrZero |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
IANAifType-MIB IF-MIB PM-MIB SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| pmProducts OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1 | |||
| pm1024 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.1 | |||
| pm2003 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.2 | |||
| pm2006 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.3 | |||
| pm2024 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.4 | |||
| pm3003 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.5 | |||
| pm3006 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.6 | |||
| pm3024 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.7 | |||
| pm1010 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.8 | |||
| pm2010 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.9 | |||
| pm3010 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.10 | |||
| pm1020 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.11 | |||
| pm2020 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.12 | |||
| pm3020 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.1.13 | |||
| pmManagement OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.2 | |||
| pmAppliance OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.2.1 | |||
| pmHostName OBJECT-TYPE The appliance name | 1.3.6.1.4.1.10418.17.2.1.1 | DisplayString (SIZE(0..32)) | read-only | current |
| pmProductModel OBJECT-TYPE The appliance product model | 1.3.6.1.4.1.10418.17.2.1.2 | DisplayString (SIZE(0..50)) | read-only | current |
| pmPartNumber OBJECT-TYPE The part number of this appliance as shown on the label attached or imprinted on the appliance. | 1.3.6.1.4.1.10418.17.2.1.3 | DisplayString (SIZE(0..32)) | read-only | current |
| pmSerialNumber OBJECT-TYPE The serial number of this appliance as shown on the label attached or imprinted on the appliance. | 1.3.6.1.4.1.10418.17.2.1.4 | DisplayString (SIZE(0..32)) | read-only | current |
| pmEIDNumber OBJECT-TYPE The electronic ID number (EID) of this appliance as shown on the label attached or imprinted on the appliance. | 1.3.6.1.4.1.10418.17.2.1.5 | DisplayString (SIZE(0..32)) | read-only | current |
| pmBootcodeVersion OBJECT-TYPE The version of the bootcode of this appliance. | 1.3.6.1.4.1.10418.17.2.1.6 | DisplayString (SIZE(0..32)) | read-only | current |
| pmFirmwareVersion OBJECT-TYPE The version of the firmware of this appliance. | 1.3.6.1.4.1.10418.17.2.1.7 | DisplayString (SIZE(0..32)) | read-only | current |
| pmReboot OBJECT-TYPE A set value of reboot(2) will reboot the appliance. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the appliance immediately reboots. | 1.3.6.1.4.1.10418.17.2.1.9 | INTEGER {noAction(1), reboot(2)} | read-write | current |
| pmSessions OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.2.2 | |||
| pmActiveSessionsNumberOfSession OBJECT-TYPE Number of active sessions. | 1.3.6.1.4.1.10418.17.2.2.1 | Integer32 | read-only | current |
| pmActiveSessionsTable OBJECT-TYPE This table contains the list of active sessions. | 1.3.6.1.4.1.10418.17.2.2.2 | not-accessible | current | |
| pmActiveSessionsTableEntry OBJECT-TYPE each entry has the information about the active session | 1.3.6.1.4.1.10418.17.2.2.2.1 | not-accessible | current | |
| pmActiveSessionsTableIndex OBJECT-TYPE A unique index representing an entry in this table. | 1.3.6.1.4.1.10418.17.2.2.2.1.1 | InterfaceIndexOrZero | read-only | current |
| pmActiveSessionsTableUser OBJECT-TYPE The name of the user that opens this session. | 1.3.6.1.4.1.10418.17.2.2.2.1.2 | DisplayString (SIZE(0..32)) | read-only | current |
| pmActiveSessionsTableGroup OBJECT-TYPE The name of the group that the user belongs to. | 1.3.6.1.4.1.10418.17.2.2.2.1.3 | DisplayString (SIZE(0..32)) | read-only | current |
| pmActiveSessionsTableType OBJECT-TYPE The session type. | 1.3.6.1.4.1.10418.17.2.2.2.1.4 | DisplayString (SIZE(0..32)) | read-only | current |
| pmActiveSessionsTableConnection OBJECT-TYPE Connection type. | 1.3.6.1.4.1.10418.17.2.2.2.1.5 | DisplayString (SIZE(0..32)) | read-only | current |
| pmActiveSessionsTableSessionTime OBJECT-TYPE Time of the session | 1.3.6.1.4.1.10418.17.2.2.2.1.6 | DisplayString (SIZE(0..32)) | read-only | current |
| pmActiveSessionsTableFrom OBJECT-TYPE The source IP address of the session. | 1.3.6.1.4.1.10418.17.2.2.2.1.7 | DisplayString (SIZE(0..32)) | read-only | current |
| pmActiveSessionsTableKill OBJECT-TYPE A set value of killSession(2) will kill the session. noAction(1) = always returned in a GET. Does nothing if SET. killSession(2)= when SET the appliance immediately kills the session. | 1.3.6.1.4.1.10418.17.2.2.2.1.8 | INTEGER {noAction(1), killSession(2)} | read-write | current |
| pmPowerMgmt OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.2.5 | |||
| pmPowerMgmtNumSerialPorts OBJECT-TYPE The number of Serial Ports that has PDU connected on the appliance. | 1.3.6.1.4.1.10418.17.2.5.1 | Integer32 | read-only | current |
| pmPowerMgmtSerialTable OBJECT-TYPE Information about each serial port thas has PDU connect. | 1.3.6.1.4.1.10418.17.2.5.2 | not-accessible | current | |
| pmPowerMgmtSerialTableEntry OBJECT-TYPE Information about each serial port thas has PDU connect. | 1.3.6.1.4.1.10418.17.2.5.2.1 | not-accessible | current | |
| pmPowerMgmtSerialTableIndex OBJECT-TYPE The index of the register. | 1.3.6.1.4.1.10418.17.2.5.2.1.1 | InterfaceIndex | read-only | current |
| pmPowerMgmtSerialTablePortNumber OBJECT-TYPE The number of the serial port when the PDU is connected. | 1.3.6.1.4.1.10418.17.2.5.2.1.2 | Integer32 | read-only | current |
| pmPowerMgmtSerialTableDeviceName OBJECT-TYPE The device name of this serial port. | 1.3.6.1.4.1.10418.17.2.5.2.1.3 | DisplayString | read-only | current |
| pmPowerMgmtSerialTableNumberPDUs OBJECT-TYPE Total number of units connected in this serial port. | 1.3.6.1.4.1.10418.17.2.5.2.1.4 | Integer32 | read-only | current |
| pmPowerMgmtSerialTableBuzzer OBJECT-TYPE set/get buzzer(s) on or off for the chain. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.2.1.10 | Integer32 | read-write | current |
| pmPowerMgmtSerialTableSyslog OBJECT-TYPE set/get syslog on or off for the chain. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.2.1.11 | Integer32 | read-write | current |
| pmPowerMgmtSerialTableOverCurrent OBJECT-TYPE set/get over current proctection on or off for the chain. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.2.1.12 | Integer32 | read-write | current |
| pmPowerMgmtSerialTableCycleInterval OBJECT-TYPE set/get cycle interval for the chain in whole seconds. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.2.1.13 | Integer32 | read-write | current |
| pmPowerMgmtSerialTablePollRate OBJECT-TYPE set/get the poll rate for the chain in whole seconds. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.2.1.14 | Integer32 | read-write | current |
| pmPowerMgmtSerialTablePassWord OBJECT-TYPE set the global password for admin user | 1.3.6.1.4.1.10418.17.2.5.2.1.15 | DisplayString | read-write | current |
| pmPowerMgmtSerialTableSave OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. save(2) = when SET the save command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.2.1.20 | INTEGER {noAction(1), save(2)} | read-write | current |
| pmPowerMgmtSerialTableRestore OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. restore(2) = when SET the restore command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.2.1.21 | INTEGER {noAction(1), restore(2)} | read-write | current |
| pmPowerMgmtPDUTable OBJECT-TYPE This table contains the list of detected PDUs. | 1.3.6.1.4.1.10418.17.2.5.3 | not-accessible | current | |
| pmPowerMgmtPDUTableEntry OBJECT-TYPE each entry has the information about the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1 | not-accessible | current | |
| pmPowerMgmtPDUTablePortNumber OBJECT-TYPE Number of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.17.2.5.3.1.1 | InterfaceIndex | read-only | current |
| pmPowerMgmtPDUTablePduIndex OBJECT-TYPE A PDU position in the chain. | 1.3.6.1.4.1.10418.17.2.5.3.1.2 | InterfaceIndexOrZero | read-only | current |
| pmPowerMgmtPDUTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.17.2.5.3.1.3 | DisplayString | read-write | current |
| pmPowerMgmtPDUTablePortName OBJECT-TYPE Name of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.17.2.5.3.1.4 | DisplayString | read-only | current |
| pmPowerMgmtPDUTableModel OBJECT-TYPE Model of the PDU. Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.3.1.5 | DisplayString | read-only | current |
| pmPowerMgmtPDUTableVendor OBJECT-TYPE Vendor of the PDU. Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.3.1.6 | DisplayString | read-only | current |
| pmPowerMgmtPDUTableFirmwareVersion OBJECT-TYPE Version of the PDU firmware. Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.3.1.7 | DisplayString | read-only | current |
| pmPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE Number of outlets of the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.8 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableCurrentNOS OBJECT-TYPE Number of current sensors in the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.9 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableCurrent1Value OBJECT-TYPE Current of the sensor 1 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.). This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentValue, pmPowerMgmtPhasesTableCurrentValue, or pmPowerMgmtOutletsTableCurrentValue | 1.3.6.1.4.1.10418.17.2.5.3.1.10 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableCurrent1Max OBJECT-TYPE Maximum current of the sensor 1 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentMax, pmPowerMgmtPhasesTableCurrentMax, or pmPowerMgmtOutletsTableCurrentMax | 1.3.6.1.4.1.10418.17.2.5.3.1.11 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableCurrent2Value OBJECT-TYPE Current of the sensor 2 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.). This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentValue, pmPowerMgmtPhasesTableCurrentValue, or pmPowerMgmtOutletsTableCurrentValue | 1.3.6.1.4.1.10418.17.2.5.3.1.12 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableCurrent2Max OBJECT-TYPE Maximum current of the sensor 2 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentMax, pmPowerMgmtPhasesTableCurrentMax, or pmPowerMgmtOutletsTableCurrentMax | 1.3.6.1.4.1.10418.17.2.5.3.1.13 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableCurrent3Value OBJECT-TYPE Current of the sensor 3 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentValue, pmPowerMgmtPhasesTableCurrentValue, or pmPowerMgmtOutletsTableCurrentValue | 1.3.6.1.4.1.10418.17.2.5.3.1.14 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableCurrent3Max OBJECT-TYPE Maximum current of the sensor 3 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableCurrentMax, pmPowerMgmtPhasesTableCurrentMax, or pmPowerMgmtOutletsTableCurrentMax | 1.3.6.1.4.1.10418.17.2.5.3.1.15 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE Number of temperature sensors in the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.16 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableTemperature1Value OBJECT-TYPE Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | 1.3.6.1.4.1.10418.17.2.5.3.1.17 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableTemperature1Max OBJECT-TYPE Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.17.2.5.3.1.18 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableTemperature2Value OBJECT-TYPE Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | 1.3.6.1.4.1.10418.17.2.5.3.1.19 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableTemperature2Max OBJECT-TYPE Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.17.2.5.3.1.20 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableTemperature3Value OBJECT-TYPE Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | 1.3.6.1.4.1.10418.17.2.5.3.1.21 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableTemperature3Max OBJECT-TYPE Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.17.2.5.3.1.22 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableHumidityNOS OBJECT-TYPE Number of humidity sensors in the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.23 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableHumidity1Value OBJECT-TYPE Humidity of this PM unit . If the humidity measurement is not installed this value will be 0. | 1.3.6.1.4.1.10418.17.2.5.3.1.24 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableHumidity1Max OBJECT-TYPE Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.17.2.5.3.1.25 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableHumidity2Value OBJECT-TYPE Humidity of this PM unit . If the humidity measurement is not installed this value will be 0. | 1.3.6.1.4.1.10418.17.2.5.3.1.26 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableHumidity2Max OBJECT-TYPE Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.17.2.5.3.1.27 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableHumidity3Value OBJECT-TYPE Humidity of this PM unit . If the humidity measurement is not installed this value will be 0. | 1.3.6.1.4.1.10418.17.2.5.3.1.28 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableHumidity3Max OBJECT-TYPE Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.17.2.5.3.1.29 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableVoltageNOS OBJECT-TYPE Number of voltage sensors in the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.30 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableVoltage1Value OBJECT-TYPE Voltage of this sensor in this PDU unit. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageValue, pmPowerMgmtPhasesTableVoltageValue, or pmPowerMgmtOutletsTableVoltageValue | 1.3.6.1.4.1.10418.17.2.5.3.1.31 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableVoltage1Max OBJECT-TYPE Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageMax, pmPowerMgmtPhasesTableVoltageMax, or pmPowerMgmtOutletsTableVoltageMax | 1.3.6.1.4.1.10418.17.2.5.3.1.32 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableVoltage2Value OBJECT-TYPE Voltage of this sensor in this PDU unit. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageValue, pmPowerMgmtPhasesTableVoltageValue, or pmPowerMgmtOutletsTableVoltageValue | 1.3.6.1.4.1.10418.17.2.5.3.1.33 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableVoltage2Max OBJECT-TYPE Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageMax, pmPowerMgmtPhasesTableVoltageMax, or pmPowerMgmtOutletsTableVoltageMax | 1.3.6.1.4.1.10418.17.2.5.3.1.34 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableVoltage3Value OBJECT-TYPE Voltage of this sensor in this PDU unit. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageValue, pmPowerMgmtPhasesTableVoltageValue, or pmPowerMgmtOutletsTableVoltageValue | 1.3.6.1.4.1.10418.17.2.5.3.1.35 | Integer32 | read-only | obsolete |
| pmPowerMgmtPDUTableVoltage3Max OBJECT-TYPE Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageMax, pmPowerMgmtPhasesTableVoltageMax, or pmPowerMgmtOutletsTableVoltageMax | 1.3.6.1.4.1.10418.17.2.5.3.1.36 | Integer32 | read-write | obsolete |
| pmPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE Number of phases of the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.37 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE Number of banks in the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.38 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableNumberOfSensors OBJECT-TYPE Number of sensors in the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.40 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableFactoryDefault OBJECT-TYPE A set value of 2 will set the PDU to factory default settings. noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the factory default command is sent to the PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.41 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPDUTableColdStartDelay OBJECT-TYPE PDUs cold start delay in whole seconds (0-60). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.42 | Integer32 | read-write | current |
| pmPowerMgmtPDUTableReboot OBJECT-TYPE A set value of power*(2) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the reboot command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.43 | INTEGER {noAction(1), reboot(2)} | read-write | current |
| pmPowerMgmtPDUTableMaxCurrent OBJECT-TYPE Maximum value of current allowed in the PDU (A x 10). | 1.3.6.1.4.1.10418.17.2.5.3.1.44 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableAlarm OBJECT-TYPE Show the PDU alarm status. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.45 | INTEGER {normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)} | read-only | current |
| pmPowerMgmtPDUTableCurrentValue OBJECT-TYPE Actual value of current in the PDU (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.50 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableCurrentMax OBJECT-TYPE Maximum value of current in the PDU (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.51 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableCurrentMin OBJECT-TYPE Minimum value of current in the PDU (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.52 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableCurrentAvg OBJECT-TYPE Average value of current in the PDU (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.53 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableCurrentReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.54 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPDUTablePowerValue OBJECT-TYPE Actual value of power in the PDU (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.60 | Integer32 | read-only | current |
| pmPowerMgmtPDUTablePowerMax OBJECT-TYPE Maximum value of power in the PDU (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.61 | Integer32 | read-only | current |
| pmPowerMgmtPDUTablePowerMin OBJECT-TYPE Minimum value of power in the PDU (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.62 | Integer32 | read-only | current |
| pmPowerMgmtPDUTablePowerAvg OBJECT-TYPE Average value of power in the PDU (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.63 | Integer32 | read-only | current |
| pmPowerMgmtPDUTablePowerReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.64 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPDUTablePowerType OBJECT-TYPE Type of power values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.65 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtPDUTableVoltageValue OBJECT-TYPE Actual value of voltage in the PDU (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.70 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableVoltageMax OBJECT-TYPE Maximum value of voltage in the PDU (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.71 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableVoltageMin OBJECT-TYPE Minimum value of voltage in the PDU (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.72 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableVoltageAvg OBJECT-TYPE Average value of voltage in the PDU (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.73 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableVoltageReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.74 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPDUTableVoltageType OBJECT-TYPE Type of voltage values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.75 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE Actual value of power factor in the PDU (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.80 | Integer32 | read-only | current |
| pmPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE Maximum value of power factor in the PDU (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.81 | Integer32 | read-only | current |
| pmPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE Minimum value of power factor in the PDU (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.82 | Integer32 | read-only | current |
| pmPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE Average value of power factor in the PDU (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.83 | Integer32 | read-only | current |
| pmPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.84 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPDUTablePowerFactorType OBJECT-TYPE Type of power values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.85 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtPDUTablePowerControl OBJECT-TYPE A set value of power*(2-4) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.90 | INTEGER {noAction(1), powerOn(2), powerOff(3), powerCycle(4)} | read-write | current |
| pmPowerMgmtPDUTableResetOCP OBJECT-TYPE A set value of power*(2) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.91 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPDUTableCurrentHighCritical OBJECT-TYPE outlet high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.100 | Integer32 | read-write | current |
| pmPowerMgmtPDUTableCurrentHighWarning OBJECT-TYPE outlet high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.101 | Integer32 | read-write | current |
| pmPowerMgmtPDUTableCurrentLowWarning OBJECT-TYPE outlet low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.102 | Integer32 | read-write | current |
| pmPowerMgmtPDUTableCurrentLowCritical OBJECT-TYPE outlet low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.103 | Integer32 | read-write | current |
| pmPowerMgmtPDUTableEnergyValue OBJECT-TYPE pdu energy value (Wh). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.3.1.105 | Integer32 | read-only | current |
| pmPowerMgmtPDUTableEnergyStartTime OBJECT-TYPE time at which energy calculation commenced (ISO8601 format). Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.3.1.106 | DisplayString | read-only | current |
| pmPowerMgmtPDUTableEnergyReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.3.1.107 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtTotalNumberOfOutlets OBJECT-TYPE Number of outlets managed by the appliance. | 1.3.6.1.4.1.10418.17.2.5.4 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTable OBJECT-TYPE This table contains the information about outlets. | 1.3.6.1.4.1.10418.17.2.5.5 | not-accessible | current | |
| pmPowerMgmtOutletsTableEntry OBJECT-TYPE each entry has the information about the outlet. | 1.3.6.1.4.1.10418.17.2.5.5.1 | not-accessible | current | |
| pmPowerMgmtOutletsTablePortNumber OBJECT-TYPE Serial Port number. | 1.3.6.1.4.1.10418.17.2.5.5.1.1 | InterfaceIndex | read-only | current |
| pmPowerMgmtOutletsTablePduNumber OBJECT-TYPE Index. | 1.3.6.1.4.1.10418.17.2.5.5.1.2 | InterfaceIndex | read-only | current |
| pmPowerMgmtOutletsTableNumber OBJECT-TYPE Number of the outlet in the PDU. | 1.3.6.1.4.1.10418.17.2.5.5.1.3 | InterfaceIndex | read-only | current |
| pmPowerMgmtOutletsTableName OBJECT-TYPE Name of the outlet. | 1.3.6.1.4.1.10418.17.2.5.5.1.4 | DisplayString | read-write | current |
| pmPowerMgmtOutletsTableStatus OBJECT-TYPE Status of the outlet. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.5 | INTEGER {off(1), on(2), offLocked(3), onLocked(4), offCycle(5), onPendingOff(6), offPendingOn(7), onPendingCycle(8), notSet(9), onFixed(10), offShutdown(11), tripped(12)} | read-only | current |
| pmPowerMgmtOutletsTablePowerControl OBJECT-TYPE A set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. powerLock(5)= when SET the power lock command is sent to PDU. powerUnlock(6)=when SET the power unlock command is sent to PDU. The powerLock and powerUnlock are valid only for Cyclades-PM PDUs | 1.3.6.1.4.1.10418.17.2.5.5.1.6 | INTEGER {noAction(1), powerOn(2), powerOff(3), powerCycle(4), powerLock(5), powerUnlock(6)} | read-write | current |
| pmPowerMgmtOutletsTablePortName OBJECT-TYPE Serial Port Name where the PDU is connected. | 1.3.6.1.4.1.10418.17.2.5.5.1.7 | DisplayString | read-only | current |
| pmPowerMgmtOutletsTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.17.2.5.5.1.8 | DisplayString | read-only | current |
| pmPowerMgmtOutletsTablePostOnDelay OBJECT-TYPE post on delay for the outlet (seconds x 10) Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.9 | Integer32 | read-write | current |
| pmPowerMgmtOutletsTablePostOffDelay OBJECT-TYPE post off delay for the outlet (seconds x 10) Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.10 | Integer32 | read-write | current |
| pmPowerMgmtOutletsTableAlarm OBJECT-TYPE Show the outlet alarm status. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.45 | INTEGER {normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)} | read-only | current |
| pmPowerMgmtOutletsTableCurrentValue OBJECT-TYPE Actual value of current in the outlet (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.50 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTableCurrentMax OBJECT-TYPE Maximum value of current in the outlet (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.51 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTableCurrentMin OBJECT-TYPE Minimum value of current in the outlet (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.52 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTableCurrentAvg OBJECT-TYPE Average value of current in the outlet (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.53 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTableCurrentReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.5.1.54 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtOutletsTablePowerValue OBJECT-TYPE Actual value of power in the outlet (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.60 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTablePowerMax OBJECT-TYPE Maximum value of power in the outlet (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.61 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTablePowerMin OBJECT-TYPE Minimum value of power in the outlet (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.62 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTablePowerAvg OBJECT-TYPE Average value of power in the outlet (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.63 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTablePowerReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.5.1.64 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtOutletsTablePowerType OBJECT-TYPE Type of power values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.65 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtOutletsTableVoltageValue OBJECT-TYPE Actual value of voltage in the outlet (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.70 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTableVoltageMax OBJECT-TYPE Maximum value of voltage in the outlet (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.71 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTableVoltageMin OBJECT-TYPE Minimum value of voltage in the outlet (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.72 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTableVoltageAvg OBJECT-TYPE Average value of voltage in the outlet (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.73 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTableVoltageReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.5.1.74 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtOutletsTableVoltageType OBJECT-TYPE Type of voltage values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.75 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtOutletsTablePowerFactorValue OBJECT-TYPE Actual value of power factor in the outlet (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.80 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTablePowerFactorMax OBJECT-TYPE Maximum value of power factor in the outlet (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.81 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTablePowerFactorMin OBJECT-TYPE Minimum value of power factor in the outlet (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.82 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTablePowerFactorAvg OBJECT-TYPE Average value of power factor in the outlet (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.83 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTablePowerFactorReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.5.1.84 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtOutletsTablePowerFactorType OBJECT-TYPE Type of power factor values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.85 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtOutletsTableCurrentHighCritical OBJECT-TYPE outlet high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.100 | Integer32 | read-write | current |
| pmPowerMgmtOutletsTableCurrentHighWarning OBJECT-TYPE outlet high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.101 | Integer32 | read-write | current |
| pmPowerMgmtOutletsTableCurrentLowWarning OBJECT-TYPE outlet low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.102 | Integer32 | read-write | current |
| pmPowerMgmtOutletsTableCurrentLowCritical OBJECT-TYPE outlet low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.103 | Integer32 | read-write | current |
| pmPowerMgmtOutletsTableEnergyValue OBJECT-TYPE outlet energy value (Wh). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.5.1.105 | Integer32 | read-only | current |
| pmPowerMgmtOutletsTableEnergyStartTime OBJECT-TYPE time at which energy calculation commenced (ISO8601 format). Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.5.1.106 | DisplayString | read-only | current |
| pmPowerMgmtOutletsTableEnergyReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.5.1.107 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtNumberOfOutletGroup OBJECT-TYPE Number of configured group of outlets. | 1.3.6.1.4.1.10418.17.2.5.6 | Integer32 | read-only | current |
| pmPowerMgmtGroupTable OBJECT-TYPE This table contains the information about group of outlets. | 1.3.6.1.4.1.10418.17.2.5.7 | not-accessible | current | |
| pmPowerMgmtGroupTableEntry OBJECT-TYPE each entry has the information about group of outlets. | 1.3.6.1.4.1.10418.17.2.5.7.1 | not-accessible | current | |
| pmPowerMgmtGroupTableIndex OBJECT-TYPE Index of the group. | 1.3.6.1.4.1.10418.17.2.5.7.1.1 | InterfaceIndexOrZero | read-only | current |
| pmPowerMgmtGroupTableName OBJECT-TYPE Name of the group of outlets. | 1.3.6.1.4.1.10418.17.2.5.7.1.2 | DisplayString | read-only | current |
| pmPowerMgmtGroupTableStatus OBJECT-TYPE Status of the group of outlet. | 1.3.6.1.4.1.10418.17.2.5.7.1.3 | INTEGER {off(1), on(2)} | read-only | current |
| pmPowerMgmtGroupTablePowerControl OBJECT-TYPE A set value of power*(2-4) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.7.1.4 | INTEGER {noAction(1), powerOn(2), powerOff(3), powerCycle(4)} | read-write | current |
| pmPowerMgmtTotalNumberOfPhases OBJECT-TYPE Number of phases managed by the appliance. | 1.3.6.1.4.1.10418.17.2.5.8 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTable OBJECT-TYPE This table contains the information about phases. | 1.3.6.1.4.1.10418.17.2.5.9 | not-accessible | current | |
| pmPowerMgmtPhasesTableEntry OBJECT-TYPE each entry has the information about the phases. | 1.3.6.1.4.1.10418.17.2.5.9.1 | not-accessible | current | |
| pmPowerMgmtPhasesTablePortNumber OBJECT-TYPE Serial Port number. | 1.3.6.1.4.1.10418.17.2.5.9.1.1 | InterfaceIndex | read-only | current |
| pmPowerMgmtPhasesTablePduNumber OBJECT-TYPE Index. | 1.3.6.1.4.1.10418.17.2.5.9.1.2 | InterfaceIndex | read-only | current |
| pmPowerMgmtPhasesTableNumber OBJECT-TYPE Number of the phase in the PDU. | 1.3.6.1.4.1.10418.17.2.5.9.1.3 | InterfaceIndex | read-only | current |
| pmPowerMgmtPhasesTableName OBJECT-TYPE Name of the phase. Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.9.1.4 | DisplayString | read-only | current |
| pmPowerMgmtPhasesTablePortName OBJECT-TYPE Serial Port Name where the PDU is connected. | 1.3.6.1.4.1.10418.17.2.5.9.1.5 | DisplayString | read-only | current |
| pmPowerMgmtPhasesTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.17.2.5.9.1.6 | DisplayString | read-only | current |
| pmPowerMgmtPhasesTableAlarm OBJECT-TYPE Show the phase alarm status. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.45 | INTEGER {normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)} | read-only | current |
| pmPowerMgmtPhasesTableCurrentValue OBJECT-TYPE Actual value of current in the phase (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.50 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTableCurrentMax OBJECT-TYPE Maximum value of current in the phase (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.51 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTableCurrentMin OBJECT-TYPE Minimum value of current in the phase (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.52 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE Average value of current in the phase (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.53 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTableCurrentReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.9.1.54 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPhasesTablePowerValue OBJECT-TYPE Actual value of power in the phase (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.60 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTablePowerMax OBJECT-TYPE Maximum value of power in the phase (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.61 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTablePowerMin OBJECT-TYPE Minimum value of power in the phase (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.62 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTablePowerAvg OBJECT-TYPE Average value of power in the phase (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.63 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTablePowerReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.9.1.64 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPhasesTablePowerType OBJECT-TYPE Type of power values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.65 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtPhasesTableVoltageValue OBJECT-TYPE Actual value of voltage in the phase (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.70 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTableVoltageMax OBJECT-TYPE Maximum value of voltage in the phase (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.71 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTableVoltageMin OBJECT-TYPE Minimum value of voltage in the phase (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.72 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE Average value of voltage in the phase (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.73 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTableVoltageReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.9.1.74 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPhasesTableVoltageType OBJECT-TYPE Type of voltage values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.75 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE Actual value of power factor in the phase (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.80 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE Maximum value of power factor in the phase (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.81 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE Minimum value of power factor in the phase (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.82 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE Average value of power factor in the phase (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.83 | Integer32 | read-only | current |
| pmPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.9.1.84 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE Type of power factor values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.85 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtPhasesTableCurrentHighCritical OBJECT-TYPE phase high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.100 | Integer32 | read-write | current |
| pmPowerMgmtPhasesTableCurrentHighWarning OBJECT-TYPE phase high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.101 | Integer32 | read-write | current |
| pmPowerMgmtPhasesTableCurrentLowWarning OBJECT-TYPE phase low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.102 | Integer32 | read-write | current |
| pmPowerMgmtPhasesTableCurrentLowCritical OBJECT-TYPE phase low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.9.1.103 | Integer32 | read-write | current |
| pmPowerMgmtTotalNumberOfBanks OBJECT-TYPE Number of banks managed by the appliance. | 1.3.6.1.4.1.10418.17.2.5.10 | Integer32 | read-only | current |
| pmPowerMgmtBanksTable OBJECT-TYPE This table contains the information about banks. | 1.3.6.1.4.1.10418.17.2.5.11 | not-accessible | current | |
| pmPowerMgmtBanksTableEntry OBJECT-TYPE each entry has the information about the banks. | 1.3.6.1.4.1.10418.17.2.5.11.1 | not-accessible | current | |
| pmPowerMgmtBanksTablePortNumber OBJECT-TYPE Serial Port number. | 1.3.6.1.4.1.10418.17.2.5.11.1.1 | InterfaceIndex | read-only | current |
| pmPowerMgmtBanksTablePduNumber OBJECT-TYPE Index. | 1.3.6.1.4.1.10418.17.2.5.11.1.2 | InterfaceIndex | read-only | current |
| pmPowerMgmtBanksTableNumber OBJECT-TYPE Number of the bank in the PDU. | 1.3.6.1.4.1.10418.17.2.5.11.1.3 | InterfaceIndex | read-only | current |
| pmPowerMgmtBanksTableName OBJECT-TYPE Name of the bank. | 1.3.6.1.4.1.10418.17.2.5.11.1.4 | DisplayString | read-only | current |
| pmPowerMgmtBanksTablePortName OBJECT-TYPE Serial Port Name where the PDU is connected. | 1.3.6.1.4.1.10418.17.2.5.11.1.5 | DisplayString | read-only | current |
| pmPowerMgmtBanksTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.17.2.5.11.1.6 | DisplayString | read-only | current |
| pmPowerMgmtBanksTableAlarm OBJECT-TYPE Show the bank alarm status. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.45 | INTEGER {normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)} | read-only | current |
| pmPowerMgmtBanksTableCurrentValue OBJECT-TYPE Actual value of current in the bank (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.50 | Integer32 | read-only | current |
| pmPowerMgmtBanksTableCurrentMax OBJECT-TYPE Maximum value of current in the bank (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.51 | Integer32 | read-only | current |
| pmPowerMgmtBanksTableCurrentMin OBJECT-TYPE Minimum value of current in the bank (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.52 | Integer32 | read-only | current |
| pmPowerMgmtBanksTableCurrentAvg OBJECT-TYPE Average value of current in the bank (A x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.53 | Integer32 | read-only | current |
| pmPowerMgmtBanksTableCurrentReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.11.1.54 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtBanksTablePowerValue OBJECT-TYPE Actual value of power in the bank (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.60 | Integer32 | read-only | current |
| pmPowerMgmtBanksTablePowerMax OBJECT-TYPE Maximum value of power in the bank (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.61 | Integer32 | read-only | current |
| pmPowerMgmtBanksTablePowerMin OBJECT-TYPE Minimum value of power in the bank (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.62 | Integer32 | read-only | current |
| pmPowerMgmtBanksTablePowerAvg OBJECT-TYPE Average value of power in the bank (W x 10). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.63 | Integer32 | read-only | current |
| pmPowerMgmtBanksTablePowerReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.11.1.64 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtBanksTablePowerType OBJECT-TYPE Type of power values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.65 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtBanksTableVoltageValue OBJECT-TYPE Actual value of voltage in the bank (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.70 | Integer32 | read-only | current |
| pmPowerMgmtBanksTableVoltageMax OBJECT-TYPE Maximum value of voltage in the bank (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.71 | Integer32 | read-only | current |
| pmPowerMgmtBanksTableVoltageMin OBJECT-TYPE Minimum value of voltage in the bank (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.72 | Integer32 | read-only | current |
| pmPowerMgmtBanksTableVoltageAvg OBJECT-TYPE Average value of voltage in the bank (V). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.73 | Integer32 | read-only | current |
| pmPowerMgmtBanksTableVoltageReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.11.1.74 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtBanksTableVoltageType OBJECT-TYPE Type of voltage values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.75 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE Actual value of power factor in the bank (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.80 | Integer32 | read-only | current |
| pmPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE Maximum value of power factor in the bank (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.81 | Integer32 | read-only | current |
| pmPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE Minimum value of power factor in the bank (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.82 | Integer32 | read-only | current |
| pmPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE Average value of power factor in the bank (Pf x 100). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.83 | Integer32 | read-only | current |
| pmPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.11.1.84 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtBanksTablePowerFactorType OBJECT-TYPE Type of power factor values. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.85 | INTEGER {none-sensor(0), estimated(1), measured(2)} | read-only | current |
| pmPowerMgmtBanksTableCurrentHighCritical OBJECT-TYPE bank high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.100 | Integer32 | read-write | current |
| pmPowerMgmtBanksTableCurrentHighWarning OBJECT-TYPE bank high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.101 | Integer32 | read-write | current |
| pmPowerMgmtBanksTableCurrentLowWarning OBJECT-TYPE bank low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.102 | Integer32 | read-write | current |
| pmPowerMgmtBanksTableCurrentLowCritical OBJECT-TYPE bank low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.103 | Integer32 | read-write | current |
| pmPowerMgmtBanksTableEnergyValue OBJECT-TYPE bank energy value (Wh). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.11.1.105 | Integer32 | read-only | current |
| pmPowerMgmtBanksTableEnergyStartTime OBJECT-TYPE time at which energy calculation commenced (ISO8601 format). Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.11.1.106 | DisplayString | read-only | current |
| pmPowerMgmtBanksTableEnergyReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU. | 1.3.6.1.4.1.10418.17.2.5.11.1.107 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtTotalNumberOfSensors OBJECT-TYPE Number of Sensors managed by the appliance. | 1.3.6.1.4.1.10418.17.2.5.12 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTable OBJECT-TYPE This table contains the information about sensors. | 1.3.6.1.4.1.10418.17.2.5.13 | not-accessible | current | |
| pmPowerMgmtSensorsTableEntry OBJECT-TYPE each entry has the information about the sensors. | 1.3.6.1.4.1.10418.17.2.5.13.1 | not-accessible | current | |
| pmPowerMgmtSensorsTablePortNumber OBJECT-TYPE Serial Port number. | 1.3.6.1.4.1.10418.17.2.5.13.1.1 | InterfaceIndex | read-only | current |
| pmPowerMgmtSensorsTablePduNumber OBJECT-TYPE Index. | 1.3.6.1.4.1.10418.17.2.5.13.1.2 | InterfaceIndex | read-only | current |
| pmPowerMgmtSensorsTableNumber OBJECT-TYPE Number of the sensor in the PDU. | 1.3.6.1.4.1.10418.17.2.5.13.1.3 | InterfaceIndex | read-only | current |
| pmPowerMgmtSensorsTableName OBJECT-TYPE Name of the sensor. | 1.3.6.1.4.1.10418.17.2.5.13.1.4 | DisplayString | read-write | current |
| pmPowerMgmtSensorsTablePortName OBJECT-TYPE Serial Port Name where the PDU is connected. | 1.3.6.1.4.1.10418.17.2.5.13.1.5 | DisplayString | read-only | current |
| pmPowerMgmtSensorsTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.17.2.5.13.1.6 | DisplayString | read-only | current |
| pmPowerMgmtSensorsTableType OBJECT-TYPE The type of environmental monitor. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.7 | INTEGER {temp-internal(1), temperature(2), humidity(3), air-flow(4), smoke(5), dry-concact(6), water-level(7), motion(8), unplugged(9), unknown(10)} | read-only | current |
| pmPowerMgmtSensorsTableStatus OBJECT-TYPE Status of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.8 | INTEGER {normal(1), triggered(2), not-applicable(3), opened(4), closed(5)} | read-only | current |
| pmPowerMgmtSensorsTableValue OBJECT-TYPE Actual value of the sensor. Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.13.1.20 | DisplayString | read-only | current |
| pmPowerMgmtSensorsTableValueMax OBJECT-TYPE Maximum value of the sensor. Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.13.1.21 | DisplayString | read-only | current |
| pmPowerMgmtSensorsTableValueMin OBJECT-TYPE Minimum value of the sensor. Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.13.1.22 | DisplayString | read-only | current |
| pmPowerMgmtSensorsTableValueAvg OBJECT-TYPE Average value of the sensor. Returns N/A if not applicable. | 1.3.6.1.4.1.10418.17.2.5.13.1.23 | DisplayString | read-only | current |
| pmPowerMgmtSensorsTableValueInt OBJECT-TYPE Actual value of the sensor. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.25 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableValueMaxInt OBJECT-TYPE Maximum value of the sensor. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.26 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableValueMinInt OBJECT-TYPE Minimum value of the sensor. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.27 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableValueAvgInt OBJECT-TYPE Average value of the sensor. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.28 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableValueReset OBJECT-TYPE noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to sensor. | 1.3.6.1.4.1.10418.17.2.5.13.1.30 | INTEGER {noAction(1), reset(2)} | read-write | current |
| pmPowerMgmtSensorsTableHighCritical OBJECT-TYPE sensor high critical (alarm) threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.40 | Integer32 | read-write | current |
| pmPowerMgmtSensorsTableHighWarning OBJECT-TYPE sensor high warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is higher than HighCritical or lower than LowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.41 | Integer32 | read-write | current |
| pmPowerMgmtSensorsTableLowWarning OBJECT-TYPE sensor low warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is higher than HighWarning or lower than LowCritical. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.42 | Integer32 | read-write | current |
| pmPowerMgmtSensorsTableLowCritical OBJECT-TYPE sensor low critical threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is higher than LowWarning. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.43 | Integer32 | read-write | current |
| pmPowerMgmtSensorsTableUnit OBJECT-TYPE sensor unit. Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.45 | INTEGER {undefined(1), fahrenheit(2), celsius(3), percent(4), afu(5)} | read-write | current |
| pmPowerMgmtSensorsTableHighCriticalC OBJECT-TYPE sensor high critical (alarm) threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.50 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableHighWarningC OBJECT-TYPE sensor high warning threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.51 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableLowWarningC OBJECT-TYPE sensor low warning threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.52 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableLowCriticalC OBJECT-TYPE sensor low critical threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.53 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableHighCriticalF OBJECT-TYPE sensor high critical (alarm) threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.60 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableHighWarningF OBJECT-TYPE sensor high warning threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.61 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableLowWarningF OBJECT-TYPE sensor low warning threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.62 | Integer32 | read-only | current |
| pmPowerMgmtSensorsTableLowCriticalF OBJECT-TYPE sensor low critical threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supported. | 1.3.6.1.4.1.10418.17.2.5.13.1.63 | Integer32 | read-only | current |
| pmTrapObject OBJECT-IDENTITY | 1.3.6.1.4.1.10418.17.2.6 |