Description

MIB module for Plug Power products.

Contact

Postal: Plug Power 15913 East Euclid Avenue Spokane, Wa 99216 Tel: +1 509-228-6500 24 Hour Support: +1 866-661-0020 Internet: www.plugpower.com E-mail: GenSureTechSupport@plugpower.com

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-SMIInteger32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCAutonomousType, DisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

PLUG-POWER-ESERIES-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Textual conventions

NameOIDSyntaxAccessStatus
FloatingPointNumber
TEXTUAL-CONVENTION
This data type is a floating point number.
current
NonNegativeInteger
TEXTUAL-CONVENTION
This data type is a non-negative value.
current
PositiveInteger
TEXTUAL-CONVENTION
This data type is a non-zero and non-negative value.
current

Objects

NameOIDSyntaxAccessStatus
fuelCellSys
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1
fcsTSeries
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.1
fcsESeries
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.2
fcsEObjects
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.2.1
fcsEMain
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.2.1.1
fcsEMainManufacturerModel
OBJECT-TYPE
Model designation.
1.3.6.1.4.1.17022.1.2.1.1.1DisplayString (SIZE(0..31))read-onlycurrent
fcsEMainMIBVersion010102
OBJECT-TYPE
The MIB version.
1.3.6.1.4.1.17022.1.2.1.1.2DisplayString (SIZE(0..31))read-onlycurrent
fcsEMainName
OBJECT-TYPE
A string displaying the system's name.
1.3.6.1.4.1.17022.1.2.1.1.3DisplayString (SIZE(0..15))read-writecurrent
fcsEMainLocation
OBJECT-TYPE
A string displaying the system's location.
1.3.6.1.4.1.17022.1.2.1.1.4DisplayString (SIZE(0..15))read-writecurrent
fcsEMainDate
OBJECT-TYPE
A string displaying the date in the format mm/dd/yy.
1.3.6.1.4.1.17022.1.2.1.1.5DisplayString (SIZE(0..11))read-writecurrent
fcsEMainTime
OBJECT-TYPE
A string displaying the time in the format hh:mm:ss. The hour is 24 hour time, 0->23.
1.3.6.1.4.1.17022.1.2.1.1.6DisplayString (SIZE(0..31))read-writecurrent
fcsEMainAlarms
OBJECT-TYPE
Indication of any alarms, will display None, Minor, Major, or Customer Attn.
1.3.6.1.4.1.17022.1.2.1.1.7DisplayString (SIZE(0..31))read-onlycurrent
fcsEMainSystemStatus
OBJECT-TYPE
The present System status. POWERUP, STANDBY, WARMUP, RUN, EXERCISE, COOLDOWN, ALARM
1.3.6.1.4.1.17022.1.2.1.1.8DisplayString (SIZE(0..30))read-onlycurrent
fcsEMainChassisSerNum
OBJECT-TYPE
The chassis serial number.
1.3.6.1.4.1.17022.1.2.1.1.9DisplayString (SIZE(0..15))read-onlycurrent
fcsEMainCommCardVersion
OBJECT-TYPE
The firmware/software version of CommCard.
1.3.6.1.4.1.17022.1.2.1.1.10DisplayString (SIZE(0..15))read-onlycurrent
fcsEMainConverterVersion
OBJECT-TYPE
The firmware/software version of Converter.
1.3.6.1.4.1.17022.1.2.1.1.11DisplayString (SIZE(0..15))read-onlycurrent
fcsEMainPower
OBJECT-TYPE
The voltage, current, and watts being produced by the fuel cell.
1.3.6.1.4.1.17022.1.2.1.1.12DisplayString (SIZE(0..36))read-onlycurrent
fcsEMainPressurePSI
OBJECT-TYPE
The H2 pressure.
1.3.6.1.4.1.17022.1.2.1.1.13DisplayString (SIZE(0..30))read-onlycurrent
fcsEMainHeater
OBJECT-TYPE
The main heater status, on/off.
1.3.6.1.4.1.17022.1.2.1.1.14DisplayString (SIZE(0..30))read-onlycurrent
fcsEMainLastRun
OBJECT-TYPE
The date of last run.
1.3.6.1.4.1.17022.1.2.1.1.15DisplayString (SIZE(0..30))read-onlycurrent
fcsEMainTotalTime
OBJECT-TYPE
The total run time (hh:mm).
1.3.6.1.4.1.17022.1.2.1.1.16DisplayString (SIZE(0..30))read-onlycurrent
fcsEMainKilowattHours
OBJECT-TYPE
The kilowatt hours (hh:mm).
1.3.6.1.4.1.17022.1.2.1.1.17DisplayString (SIZE(0..30))read-onlycurrent
fcsEMainSystemRuns
OBJECT-TYPE
The Number of System Runs.
1.3.6.1.4.1.17022.1.2.1.1.18DisplayString (SIZE(0..30))read-onlycurrent
fcsEMainChassisTemp
OBJECT-TYPE
The current chassis temperature, degrees C.
1.3.6.1.4.1.17022.1.2.1.1.19DisplayString (SIZE(0..30))read-onlycurrent
fcsEMainBleedTempSensor
OBJECT-TYPE
Indicates if the bleed temperature sensor is installed.
1.3.6.1.4.1.17022.1.2.1.1.20INTEGER {no(1), yes(2)}read-writecurrent
fcsEMainResetSystem
OBJECT-TYPE
Resets / Reboots the system.
1.3.6.1.4.1.17022.1.2.1.1.21INTEGER {no(1), yes(2)}read-writecurrent
fcsEMainVolts
OBJECT-TYPE
The voltage being produced by the fuel cell.
1.3.6.1.4.1.17022.1.2.1.1.22DisplayString (SIZE(0..36))read-onlycurrent
fcsEMainAmps
OBJECT-TYPE
The current being produced by the fuel cell.
1.3.6.1.4.1.17022.1.2.1.1.23DisplayString (SIZE(0..36))read-onlycurrent
fcsEMainWatts
OBJECT-TYPE
The watts being produced by the fuel cell.
1.3.6.1.4.1.17022.1.2.1.1.24DisplayString (SIZE(0..36))read-onlycurrent
fcsERun
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.2.1.2
fcsERunStartStop
OBJECT-TYPE
Manual Start and Stop.
1.3.6.1.4.1.17022.1.2.1.2.1INTEGER {start(1), stop(2), busy(3)}read-writecurrent
fcsERunSystemStatus
OBJECT-TYPE
The present System status.
1.3.6.1.4.1.17022.1.2.1.2.2DisplayString (SIZE(0..30))read-onlycurrent
fcsERunStartStatus
OBJECT-TYPE
The present Run status.
1.3.6.1.4.1.17022.1.2.1.2.3DisplayString (SIZE(0..30))read-onlycurrent
fcsERunFloatVolt
OBJECT-TYPE
The Float Voltage. The voltage to charge the batteries to when the system is running.
1.3.6.1.4.1.17022.1.2.1.2.4DisplayString (SIZE(0..12))read-writecurrent
fcsERunLowVoltThreshold
OBJECT-TYPE
The low voltage at which the system will start automatically if enabled.
1.3.6.1.4.1.17022.1.2.1.2.5DisplayString (SIZE(0..30))read-writecurrent
fcsERunLowVoltStartMode
OBJECT-TYPE
Disables low voltage start or Enables low voltage start in either float or maintain modes.
1.3.6.1.4.1.17022.1.2.1.2.6INTEGER {off(1), float(2), maintain(3)}read-writecurrent
fcsERunLowVoltTimer
OBJECT-TYPE
Number of minutes to maintain Float Voltage on the batteries before shutting down. Valid minutes are between 5 and 120 in 5 minute increments and 240. A value of 0 sets a 1/2 volt above the float voltage before the low volt start will end, this requires another voltage source to drive the 1/2 volt above. A value of 0 will continue to run on a low volt start until another voltage source picks up the load.
1.3.6.1.4.1.17022.1.2.1.2.7INTEGER {minutes005(5), minutes010(10), minutes015(15), minutes020(20), minutes025(25), minutes030(30), minutes035(35), minutes040(40), minutes045(45), minutes050(50), minutes055(55), minutes060(60), minutes065(65), minutes070(70), minutes075(75), minutes080(80), minutes085(85), minutes090(90), minutes095(95), minutes100(100), minutes105(105), minutes110(110), minutes115(115), minutes120(120), minutes240(240)}read-writecurrent
fcsERunLowVoltageFloatTimeOut
OBJECT-TYPE
The current time at float voltage, (mm:ss).
1.3.6.1.4.1.17022.1.2.1.2.8DisplayString (SIZE(0..30))read-onlycurrent
fcsERunContactStartDelay
OBJECT-TYPE
Number of minutes to wait on a contact start condition before the system starts.
1.3.6.1.4.1.17022.1.2.1.2.9Integer32 (0..60)read-writecurrent
fcsERunContactStartTimeOut
OBJECT-TYPE
The current time at contact start delay, (mm:ss).
1.3.6.1.4.1.17022.1.2.1.2.10DisplayString (SIZE(0..30))read-onlycurrent
fcsERunPower
OBJECT-TYPE
The voltage, current, and watts being produced by the fuel cell.
1.3.6.1.4.1.17022.1.2.1.2.11DisplayString (SIZE(0..36))read-onlycurrent
fcsERunPressurePSI
OBJECT-TYPE
The H2 pressure.
1.3.6.1.4.1.17022.1.2.1.2.12DisplayString (SIZE(0..30))read-onlycurrent
fcsERunLowH2PressureAlarm
OBJECT-TYPE
The Low H2 Pressure Alarm setting.
1.3.6.1.4.1.17022.1.2.1.2.13DisplayString (SIZE(0..30))read-writecurrent
fcsERunLowH2PressureAlert
OBJECT-TYPE
The Low H2 Pressure Alert setting.
1.3.6.1.4.1.17022.1.2.1.2.14DisplayString (SIZE(0..30))read-writecurrent
fcsERunLowH2PressureAlertStatus
OBJECT-TYPE
The Low H2 Pressure Alert current status.
1.3.6.1.4.1.17022.1.2.1.2.15DisplayString (SIZE(0..30))read-onlycurrent
fcsERunAuxOutAssigned
OBJECT-TYPE
Aux Out assigned to.
1.3.6.1.4.1.17022.1.2.1.2.16INTEGER {lowH2Alert(1), auxInput(2), exercise(3)}read-writecurrent
fcsERunPowerLimiting
OBJECT-TYPE
Percentage of rated power to limit the output power to.
1.3.6.1.4.1.17022.1.2.1.2.17INTEGER {percent020(2), percent030(3), percent040(4), percent050(5), percent060(6), percent070(7), percent080(8), percent090(9), percent100(10)}read-writecurrent
fcsERunClearNoPressureAlarm
OBJECT-TYPE
Clears the No Pressure / No H2 Fuel Major alarm.
1.3.6.1.4.1.17022.1.2.1.2.18INTEGER {no(1), yes(2)}read-writecurrent
fcsERunSystemLockTime
OBJECT-TYPE
Number of minutes to lock the system.
1.3.6.1.4.1.17022.1.2.1.2.19Integer32 (5..120)read-writecurrent
fcsERunSystemLockTimeOut
OBJECT-TYPE
Time left that the system will be locked, (mm:ss).
1.3.6.1.4.1.17022.1.2.1.2.20DisplayString (SIZE(0..30))read-onlycurrent
fcsERunLockSystem
OBJECT-TYPE
Lock the system.
1.3.6.1.4.1.17022.1.2.1.2.21INTEGER {lock(1), unlock(2), locked(3)}read-writecurrent
fcsERunAuxInAssigned
OBJECT-TYPE
Aux Out assigned to.
1.3.6.1.4.1.17022.1.2.1.2.22INTEGER {nothing(1), lock(2), door(3), extLd1-2k(4), extLd1-3k(5), extLd2(6)}read-writecurrent
fcsERunVolts
OBJECT-TYPE
The voltage being produced by the fuel cell.
1.3.6.1.4.1.17022.1.2.1.2.23DisplayString (SIZE(0..36))read-onlycurrent
fcsERunAmps
OBJECT-TYPE
The current being produced by the fuel cell.
1.3.6.1.4.1.17022.1.2.1.2.24DisplayString (SIZE(0..36))read-onlycurrent
fcsERunWatts
OBJECT-TYPE
The watts being produced by the fuel cell.
1.3.6.1.4.1.17022.1.2.1.2.25DisplayString (SIZE(0..36))read-onlycurrent
fcsEExercise
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.2.1.3
fcsEExerciseManualExercise
OBJECT-TYPE
Manual Start and Stop.
1.3.6.1.4.1.17022.1.2.1.3.1INTEGER {start(1), stop(2), busy(3)}read-writecurrent
fcsEExerciseExerciseMode
OBJECT-TYPE
Auto Schedule mode, number of day mode, day of the month mode, or disabled.
1.3.6.1.4.1.17022.1.2.1.3.2INTEGER {autoSchedule(1), numOfDays(2), dayOfMonth(3), disabled(4)}read-writecurrent
fcsEExerciseNumOfDaysOrDayOfMonth
OBJECT-TYPE
Number of days between Auto exercising, or day of the month that system will auto exercise depending on ExerciseType setting.
1.3.6.1.4.1.17022.1.2.1.3.3Integer32 (1..45)read-writecurrent
fcsEExerciseTimeOfDay
OBJECT-TYPE
Time of day for Auto exercising, on the hour between midnight and 6 AM.
1.3.6.1.4.1.17022.1.2.1.3.4INTEGER {at-0-AM(1), at-1-AM(2), at-2-AM(3), at-3-AM(4), at-4-AM(5), at-5-AM(6), at-6-AM(7)}read-writecurrent
fcsEExerciseSetNextExerciseDate
OBJECT-TYPE
Set the next date for auto exercising to be done.
1.3.6.1.4.1.17022.1.2.1.3.5DisplayString (SIZE(0..30))read-writecurrent
fcsEExerciseNextExerciseDate
OBJECT-TYPE
Displays date and time of when the next scheduled auto exercise is to run.
1.3.6.1.4.1.17022.1.2.1.3.6DisplayString (SIZE(0..30))read-onlycurrent
fcsEExerciseCond1StartStop
OBJECT-TYPE
Conditioning 1 Run, Start and Stop
1.3.6.1.4.1.17022.1.2.1.3.7INTEGER {start(1), stop(2), busy(3)}read-writecurrent
fcsEAlarm
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.2.1.4
fcsEAlarms
OBJECT-TYPE
The present number of Major and Minor alarms.
1.3.6.1.4.1.17022.1.2.1.4.1DisplayString (SIZE(0..31))read-onlycurrent
fcsEAlarmTable
OBJECT-TYPE
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The fcsEAlarmId that indexes the table is the index into the products alarm table. Consequently the table is sparse, e.g., containing entries for alarm indices 5, 10, 11, and 20 and the entries should not be assumed to be in chronological or alarm severity order. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), fcsEAlarmDescr. No two rows will have the same value of fcsEAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of fcsEAlarmsPresent.
1.3.6.1.4.1.17022.1.2.1.4.2not-accessiblecurrent
fcsEAlarmEntry
OBJECT-TYPE
An entry containing information applicable to a particular alarm.
1.3.6.1.4.1.17022.1.2.1.4.2.1not-accessiblecurrent
fcsEAlarmId
OBJECT-TYPE
A unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.17022.1.2.1.4.2.1.1PositiveIntegernot-accessiblecurrent
fcsEAlarmDescr
OBJECT-TYPE
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
1.3.6.1.4.1.17022.1.2.1.4.2.1.2AutonomousTyperead-onlycurrent
fcsEAlarmType
OBJECT-TYPE
The type of alarm, Major or Minor.
1.3.6.1.4.1.17022.1.2.1.4.2.1.3INTEGER {major(1), minor(2)}read-onlycurrent
fcsEAlarmTime
OBJECT-TYPE
The date and time of when the alarm became active in the format mm/dd/yy hh:mm:ss
1.3.6.1.4.1.17022.1.2.1.4.2.1.4DisplayString (SIZE(0..31))read-onlycurrent
fcsESystemAlarms
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.2.1.5
fcsEAlarmNoCurrentAlarms
OBJECT-IDENTITY
No current alarms. Not used.
1.3.6.1.4.1.17022.1.2.1.5.0current
fcsMJAlarmVerMismatch
OBJECT-IDENTITY
Major Alarm: Comm Card running an incompatible version to the Controller running version.
1.3.6.1.4.1.17022.1.2.1.5.1current
fcsMJAlarmTermVoltsLow
OBJECT-IDENTITY
Major Alarm: The System's Terminal voltage is so low that there isn't enough power for the fuel cell system to start.
1.3.6.1.4.1.17022.1.2.1.5.2current
fcsMJAlarmTermVoltsHigh
OBJECT-IDENTITY
Major Alarm: High Terminal Voltage. System will not start.
1.3.6.1.4.1.17022.1.2.1.5.3current
fcsMJAlarmNoH2Pressure
OBJECT-IDENTITY
Major Alarm: No H2 Pressure. System will not run.
1.3.6.1.4.1.17022.1.2.1.5.4current
fcsMJAlarmCommLinkDown
OBJECT-IDENTITY
Major Alarm: CommCard and Converter communications link is down. System will not start.
1.3.6.1.4.1.17022.1.2.1.5.5current
fcsMJAlarmSafetyCheckFail
OBJECT-IDENTITY
Major Alarm: Safety Check Failed. System will not start.
1.3.6.1.4.1.17022.1.2.1.5.6current
fcsMJAlarmH2SensorTopLtHigh
OBJECT-IDENTITY
Major Alarm: H2 Sensor is detecting a high concentration of H2. Top sensor on E2500, Left sensor on E1100.
1.3.6.1.4.1.17022.1.2.1.5.7current
fcsMJAlarmH2SensorBotRtHigh
OBJECT-IDENTITY
Major Alarm: H2 Sensor is detecting a high concentration of H2. Bot sensor on E2500, Right sensor on E1100.
1.3.6.1.4.1.17022.1.2.1.5.8current
fcsMJAlarmH2SensorTopLtFail
OBJECT-IDENTITY
Major Alarm: H2 Sensor has failed. Top sensor on E2500, Left sensor on E1100.
1.3.6.1.4.1.17022.1.2.1.5.9current
fcsMJAlarmH2SensorBotRtFail
OBJECT-IDENTITY
Major Alarm: H2 Sensor 2 has failed. Bot sensor on E2500, Right sensor on E1100.
1.3.6.1.4.1.17022.1.2.1.5.10current
fcsMJAlarmSafetyFanFail
OBJECT-IDENTITY
Major Alarm: Safety Circuit Fan has failed.
1.3.6.1.4.1.17022.1.2.1.5.11current
fcsMJAlarmSafetyTempFail
OBJECT-IDENTITY
Major Alarm: System is too hot to run.
1.3.6.1.4.1.17022.1.2.1.5.12current
fcsMJAlarmModOpenCircuitVoltage
OBJECT-IDENTITY
Major Alarm: Fuel Cell Module did not have high enough voltage on startup to run.
1.3.6.1.4.1.17022.1.2.1.5.13current
fcsMJAlarmModShortedCircuitVoltage
OBJECT-IDENTITY
Major Alarm: While running the Fuel Cell Module voltage got too low to continue to run.
1.3.6.1.4.1.17022.1.2.1.5.14current
fcsMJAlarmModTooHighVoltage
OBJECT-IDENTITY
Major Alarm: While running the Fuel Cell Module voltage got too high to continue to run.
1.3.6.1.4.1.17022.1.2.1.5.15current
fcsMJAlarmConverterID
OBJECT-IDENTITY
Major Alarm: The Comm Card does not know what the Converter is. System will not run.
1.3.6.1.4.1.17022.1.2.1.5.16current
fcsMJAllModTempSensorsFailed
OBJECT-IDENTITY
Major Alarm: All Fuel Cell Modules temperature sensors have failed. System will not run.
1.3.6.1.4.1.17022.1.2.1.5.17current
fcsMJAlarmSystemIsDown
OBJECT-IDENTITY
Major Alarm: The System is down. It cannot run.
1.3.6.1.4.1.17022.1.2.1.5.18current
fcsMJAlarmModsTooCold
OBJECT-IDENTITY
Major Alarm: Modules are TOO cold to run.
1.3.6.1.4.1.17022.1.2.1.5.19current
fcsMNAlarmModTopFailed
OBJECT-IDENTITY
Minor Alarm: Top Module did not reach Open Circuit voltage when starting up. System will run on bottom module(s) at half power.
1.3.6.1.4.1.17022.1.2.1.5.20current
fcsMNAlarmMod2Failed
OBJECT-IDENTITY
Minor Alarm: E2500 Module 2 did not reach Open Circuit voltage when starting up. System will run on bottom modules at half power.
1.3.6.1.4.1.17022.1.2.1.5.21current
fcsMNAlarmMod3Failed
OBJECT-IDENTITY
Minor Alarm: E2500 Module 3 did not reach Open Circuit voltage when starting up. System will run on top modules at half power.
1.3.6.1.4.1.17022.1.2.1.5.22current
fcsMNAlarmModBotFailed
OBJECT-IDENTITY
Minor Alarm: Bottom Module did not reach Open Circuit voltage when starting up. System will run on top module(s) at half power.
1.3.6.1.4.1.17022.1.2.1.5.23current
fcsMNAlarmH2SensorTopLtLow
OBJECT-IDENTITY
Minor Alarm: H2 Sensor is detecting a low concentration of H2. Top sensor on E2500, Left sensor on E1100.
1.3.6.1.4.1.17022.1.2.1.5.24current
fcsMNAlarmH2SensorBotRtLow
OBJECT-IDENTITY
Minor Alarm: H2 Sensor is detecting a low concentration of H2. Bottom sensor on E2500, Right sensor on E1100.
1.3.6.1.4.1.17022.1.2.1.5.25current
fcsMNAlarmBleedTempSensor
OBJECT-IDENTITY
Minor Alarm: Bleed temperature sensor has failed.
1.3.6.1.4.1.17022.1.2.1.5.26current
fcsMNAlarmModTopLtTempSensor
OBJECT-IDENTITY
Minor Alarm: Top Module Left temperature sensor has failed.
1.3.6.1.4.1.17022.1.2.1.5.27current
fcsMNAlarmModTopRtTempSensor
OBJECT-IDENTITY
Minor Alarm: Top Module Right temperature sensor has failed.
1.3.6.1.4.1.17022.1.2.1.5.28current
fcsMNAlarmModTwoLtTempSensor
OBJECT-IDENTITY
Minor Alarm: Module two Left temperature sensor has failed. Only E2500 alarm.
1.3.6.1.4.1.17022.1.2.1.5.29current
fcsMNAlarmModTwoRtTempSensor
OBJECT-IDENTITY
Minor Alarm: Module two Right temperature sensor has failed. Only E2500 alarm.
1.3.6.1.4.1.17022.1.2.1.5.30current
fcsMNAlarmModThreeLtTempSensor
OBJECT-IDENTITY
Minor Alarm: Module three Left temperature sensor has failed. Only E2500 alarm.
1.3.6.1.4.1.17022.1.2.1.5.31current
fcsMNAlarmModThreeRtTempSensor
OBJECT-IDENTITY
Minor Alarm: Module three Right temperature sensor has failed. Only E2500 alarm.
1.3.6.1.4.1.17022.1.2.1.5.32current
fcsMNAlarmModBotLtTempSensor
OBJECT-IDENTITY
Minor Alarm: Bottom Module Left temperature sensor has failed.
1.3.6.1.4.1.17022.1.2.1.5.33current
fcsMNAlarmModBotRtTempSensor
OBJECT-IDENTITY
Minor Alarm: Bottom Module Right temperature sensor has failed.
1.3.6.1.4.1.17022.1.2.1.5.34current
fcsMNAlarmExtFan1Failed
OBJECT-IDENTITY
Minor Alarm: Exhaust Fan 1 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.35current
fcsMNAlarmExtFan2Failed
OBJECT-IDENTITY
Minor Alarm: Exhaust Fan 2 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.36current
fcsMNAlarmExtFan3Failed
OBJECT-IDENTITY
Minor Alarm: Exhaust Fan 3 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.37current
fcsMNAlarmExtFan4Failed
OBJECT-IDENTITY
Minor Alarm: Exhaust Fan 4 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.38current
fcsMNAlarmExtFan5Failed
OBJECT-IDENTITY
Minor Alarm: Exhaust Fan 5 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.39current
fcsMNAlarmExtFan6Failed
OBJECT-IDENTITY
Minor Alarm: Exhaust Fan 6 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.40current
fcsMNAlarmRecFan1Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 1 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.41current
fcsMNAlarmRecFan2Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 2 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.42current
fcsMNAlarmRecFan3Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 3 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.43current
fcsMNAlarmRecFan4Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 4 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.44current
fcsMNAlarmRecFan5Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 5 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.45current
fcsMNAlarmRecFan6Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 6 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.46current
fcsMNAlarmRecFan7Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 7 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.47current
fcsMNAlarmRecFan8Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 8 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.48current
fcsMNAlarmRecFan9Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 9 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.49current
fcsMNAlarmRecFan10Failed
OBJECT-IDENTITY
Minor Alarm: Recirculation Fan 10 has Failed.
1.3.6.1.4.1.17022.1.2.1.5.50current
fcsMNAlarmConverterCheckSumError
OBJECT-IDENTITY
Minor Alarm: Converter Code Checksum Error.
1.3.6.1.4.1.17022.1.2.1.5.51current
fcsMJAlarmModsTooHotToRun
OBJECT-IDENTITY
Major Alarm: Modules Too Hot to Run.
1.3.6.1.4.1.17022.1.2.1.5.52current
fcsMJAlarmSystemLocked
OBJECT-IDENTITY
Major Alarm: User has locked the system.
1.3.6.1.4.1.17022.1.2.1.5.53current
fcsMNAlarmCommCardCheckSumError
OBJECT-IDENTITY
Minor Alarm: Comm Card Code Checksum Error.
1.3.6.1.4.1.17022.1.2.1.5.54current
fcsMNAlarmWebPagesCheckSumError
OBJECT-IDENTITY
Minor Alarm: Web Pages Checksum Error.
1.3.6.1.4.1.17022.1.2.1.5.55current
fcsMJAlarmTesting
OBJECT-IDENTITY
Major Alarm: Testing the Major alarm funtion.
1.3.6.1.4.1.17022.1.2.1.5.56current
fcsMNAlarmTesting
OBJECT-IDENTITY
Minor Alarm: Testing the Minor alarm funtion.
1.3.6.1.4.1.17022.1.2.1.5.57current
fcsMNAlarmLowH2Pressure
OBJECT-IDENTITY
Minor Alarm: Low H2 Pressure.
1.3.6.1.4.1.17022.1.2.1.5.58current
fcsMNAlarmDoorOpen
OBJECT-IDENTITY
Minor Alarm: Cabinet Door is Open.
1.3.6.1.4.1.17022.1.2.1.5.59current
fcsMNAlarmSystemDateInvalid
OBJECT-IDENTITY
Minor Alarm: System Date is Invalid.
1.3.6.1.4.1.17022.1.2.1.5.60current
fcsETraps
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.2.2
fcsE2Gen2
OBJECT-IDENTITY
1.3.6.1.4.1.17022.1.3

Notifications

NameOIDStatus
fcsETrapMJAlarmEntryAdded
NOTIFICATION-TYPE
This trap is sent each time a major alarm is inserted into the alarm table.
1.3.6.1.4.1.17022.1.2.2.1current
fcsETrapMJAlarmEntryRemoved
NOTIFICATION-TYPE
This trap is sent each time a major alarm is removed from the alarm table.
1.3.6.1.4.1.17022.1.2.2.2current
fcsETrapMNAlarmEntryAdded
NOTIFICATION-TYPE
This trap is sent each time a minor alarm is inserted into the alarm table.
1.3.6.1.4.1.17022.1.2.2.3current
fcsETrapMNAlarmEntryRemoved
NOTIFICATION-TYPE
This trap is sent each time a minor alarm is removed from the alarm table.
1.3.6.1.4.1.17022.1.2.2.4current
fcsETrapRunning
NOTIFICATION-TYPE
The Fuel Cell System is running. This trap gets sent when the system goes into run mode. The fcsETrapRunEnded trap will be sent when the system exits run mode.
1.3.6.1.4.1.17022.1.2.2.5current
fcsETrapExercising
NOTIFICATION-TYPE
The Fuel Cell System is exercising. This trap gets sent when the system goes into exercise mode. The fcsETrapRunEnded trap will be sent when the system exits exercise mode.
1.3.6.1.4.1.17022.1.2.2.6current
fcsETrapRunEnded
NOTIFICATION-TYPE
The Fuel Cell System just shut down from either exercising or running.
1.3.6.1.4.1.17022.1.2.2.7current
fcsETrapLowH2FuelAlertOn
NOTIFICATION-TYPE
Low H2 Fuel alert is on.
1.3.6.1.4.1.17022.1.2.2.8current
fcsETrapLowH2FuelAlertOff
NOTIFICATION-TYPE
Low H2 Fuel alert is off.
1.3.6.1.4.1.17022.1.2.2.9current