Description

SmartZone G5 iPDU

Contact

Panduit Postal: Panduit 18900 Panduit Drive Tinley Park, IL 60487 USA Tel: +1 708 532-1800/888-506-5400 E-mail: systemsupport@panduit.com

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-MIBsysDescr
SNMPv2-SMIInteger32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

PANDUIT-MIB
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
panduit
OBJECT-IDENTITY
1.3.6.1.4.1.19536
pdug5
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1
pdug5Ident
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.1
pdug5NumberPDU
OBJECT-TYPE
The number of PDUs detected (in its daisy chain).
1.3.6.1.4.1.19536.10.1.1.1Integer32 (1..4)read-onlycurrent
pdug5IdentTable
OBJECT-TYPE
Aggregate Object with number of entries equal to pdug5NumberPDU .
1.3.6.1.4.1.19536.10.1.1.2not-accessiblecurrent
pdug5IdentEntry
OBJECT-TYPE
The Identity table entry containing the name, model, manufacturer, firmware version, part number, etc.
1.3.6.1.4.1.19536.10.1.1.2.1not-accessiblecurrent
pdug5IdentIndex
OBJECT-TYPE
Index for the pdug5IdentEntry table.
1.3.6.1.4.1.19536.10.1.1.2.1.1Integer32 (1..6)not-accessiblecurrent
pdug5Name
OBJECT-TYPE
The string identify the device in daisy chain. Example PDU A.
1.3.6.1.4.1.19536.10.1.1.2.1.2DisplayString (SIZE(0..63))read-writecurrent
pdug5Model
OBJECT-TYPE
The Device Model.
1.3.6.1.4.1.19536.10.1.1.2.1.3DisplayString (SIZE(0..63))read-onlycurrent
pdug5Manufacturer
OBJECT-TYPE
The Device Manufacturer Name.
1.3.6.1.4.1.19536.10.1.1.2.1.4DisplayString (SIZE(0..63))read-onlycurrent
pdug5FirmwareVersion
OBJECT-TYPE
The firmware revision level of the device.
1.3.6.1.4.1.19536.10.1.1.2.1.5DisplayString (SIZE(0..63))read-onlycurrent
pdug5FirmwareVersionTimeStamp
OBJECT-TYPE
Timestamp of when the PDU firmware was last updated
1.3.6.1.4.1.19536.10.1.1.2.1.6DisplayStringread-onlycurrent
pdug5PartNumber
OBJECT-TYPE
The device part number. Example P36E09M.
1.3.6.1.4.1.19536.10.1.1.2.1.7DisplayString (SIZE(0..63))read-onlycurrent
pdug5SerialNumber
OBJECT-TYPE
The device serial number, 10-digit.
1.3.6.1.4.1.19536.10.1.1.2.1.8DisplayString (SIZE(0..63))read-onlycurrent
pdug5Status
OBJECT-TYPE
The overall status of the device. A value of OK(2) indicates the device is operating normally. A value of degraded(3) indicates the device is operating with warning indicators. A value of failed(4) indicates the device is operating with critical indicators.
1.3.6.1.4.1.19536.10.1.1.2.1.9INTEGER {other(1), ok(2), degraded(3), failed(4)}read-onlycurrent
pdug5Controllable
OBJECT-TYPE
This object indicates whether or not the device is controllable.
1.3.6.1.4.1.19536.10.1.1.2.1.10INTEGER {yes(1), no(2)}read-onlycurrent
pdug5InputPhaseCount
OBJECT-TYPE
The number of input phase on this pdu 1 or 3.
1.3.6.1.4.1.19536.10.1.1.2.1.11Integer32 (1..3)read-onlycurrent
pdug5GroupCount
OBJECT-TYPE
The number of groups (breakers) on this pdu.
1.3.6.1.4.1.19536.10.1.1.2.1.12Integer32 (0..12)read-onlycurrent
pdug5OutletCount
OBJECT-TYPE
The number of outlets in this PDU.
1.3.6.1.4.1.19536.10.1.1.2.1.13Integer32 (1..48)read-onlycurrent
pdug5MACAddress
OBJECT-TYPE
The assigned MAC address for this PDU.
1.3.6.1.4.1.19536.10.1.1.2.1.14DisplayStringread-onlycurrent
pdug5IPv4Address
OBJECT-TYPE
The current IPv4 Address. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.19536.10.1.1.2.1.15IpAddressread-onlycurrent
pdug5IPv6Address
OBJECT-TYPE
The current IPv6 Address. A value of 0.0.0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.19536.10.1.1.2.1.16DisplayStringread-onlycurrent
pdug5HWVersion
OBJECT-TYPE
The current Hardware Version. 1.0 - G5 (STM) No Powershare, 1.5 - G5 (STM) with Powershare, 2.0 - G6 Processor
1.3.6.1.4.1.19536.10.1.1.2.1.17DisplayStringread-onlycurrent
pdug5ConfigTable
OBJECT-TYPE
Aggregate Object with number of entries equal to pdug5NumberPDU.
1.3.6.1.4.1.19536.10.1.1.3not-accessiblecurrent
pdug5ConfigEntry
OBJECT-TYPE
Read Configuration data from the PDU being queried.
1.3.6.1.4.1.19536.10.1.1.3.1not-accessiblecurrent
pdug5ConfigIndex
OBJECT-TYPE
The index of PDU configuration entry.
1.3.6.1.4.1.19536.10.1.1.3.1.1Integer32 (1..4)not-accessiblecurrent
pdug5ConfigSsh
OBJECT-TYPE
Setting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection. iNC reboot will be required for the settings to take effect.
1.3.6.1.4.1.19536.10.1.1.3.1.2INTEGER {off(0), on(1)}read-writecurrent
pdug5ConfigFtps
OBJECT-TYPE
Setting this OID to off(0) will disable the FTPS connection. Setting this OID to on(1) will enable the FTPS connection. iNC reboot will be required for the settings to take effect
1.3.6.1.4.1.19536.10.1.1.3.1.3INTEGER {off(0), on(1)}read-writecurrent
pdug5ConfigHttp
OBJECT-TYPE
Setting this OID to off(0) will disable the HTTP connection. Setting this OID to on(1) will enable the HTTP connection.iNC reboot will be required for the settings to take effect
1.3.6.1.4.1.19536.10.1.1.3.1.4INTEGER {off(0), on(1)}read-writecurrent
pdug5ConfigHttps
OBJECT-TYPE
Setting this OID to off(0) will disable the HTTPS connection. Setting this OID to on(1) will enable the HTTPS connection.iNC reboot will be required for the settings to take effect
1.3.6.1.4.1.19536.10.1.1.3.1.5INTEGER {off(0), on(1)}read-writecurrent
pdug5ConfigIPv4IPv6Switch
OBJECT-TYPE
Setting this OID to IPv4(1) will enable the IPv4 configuration. Setting this OID to IPv6(2) will enable the IPv6 configuration. Setting this OID to IPv4&IPv6(3) will enable both IPv4 and IPv6 configuration.iNC reboot will be required for the settings to take effect
1.3.6.1.4.1.19536.10.1.1.3.1.6INTEGER {iPv4(1), iPv6(2), iPv4IPv6(3)}read-writecurrent
pdug5ConfigRedfishAPI
OBJECT-TYPE
Setting this OID to off(0) will disable the Redfish API. Setting this OID to on(1) will enable the Redfish API.iNC reboot will be required for the settings to take effect
1.3.6.1.4.1.19536.10.1.1.3.1.7INTEGER {off(0), on(1)}read-writecurrent
pdug5ConfigOledDispalyOrientation
OBJECT-TYPE
Indicates the intended physical orientation of OLED display. displayNormal(1) indicates normal orientation. displayReverse(2) indicates upside down orientation.
1.3.6.1.4.1.19536.10.1.1.3.1.8INTEGER {displayNormal(1), displayReverse(2)}read-writecurrent
pdug5ConfigEnergyReset
OBJECT-TYPE
Setting this OID to reset(2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not supported this feature will respond to this OID with a value of notSupported(3). Attempts to set this OID in these models will fail.
1.3.6.1.4.1.19536.10.1.1.3.1.9INTEGER {noOperation(1), reset(2), notSupported(3)}read-writecurrent
pdug5ConfigNetworkManagementCardReset
OBJECT-TYPE
Getting this OID will return noOperation(0). Getting this OID to reset(1) will reset iNC.
1.3.6.1.4.1.19536.10.1.1.3.1.10INTEGER {noOperation(0), reset(1)}read-writecurrent
pdug5ConfigDaisyChainStatus
OBJECT-TYPE
Setting this OID will change daisychain mode. 0:QNA,1:DNA.
1.3.6.1.4.1.19536.10.1.1.3.1.11INTEGER {daisychain(0), rna(1)}read-writecurrent
pdug5PowershareTable
OBJECT-TYPE
Aggregate Object with number of entries equal to number of PDUs and Power share
1.3.6.1.4.1.19536.10.1.1.4not-accessiblecurrent
pdug5PowershareEntry
OBJECT-TYPE
The Power share entry containing the available, input, output etc.
1.3.6.1.4.1.19536.10.1.1.4.1not-accessiblecurrent
pdug5PowershareIndex
OBJECT-TYPE
The index of the PDU Power share table entry
1.3.6.1.4.1.19536.10.1.1.4.1.1Integer32 (1..4)not-accessiblecurrent
pdug5PowershareFunctionStatus
OBJECT-TYPE
Power share function status on PDU.
1.3.6.1.4.1.19536.10.1.1.4.1.2INTEGER {notAvailable(0), available(1)}read-onlycurrent
pdug5PowershareFunctionUpstreamStatus
OBJECT-TYPE
Power share function status on upstream PDU
1.3.6.1.4.1.19536.10.1.1.4.1.3INTEGER {notAvailable(0), available(1)}read-onlycurrent
pdug5PowershareOutput
OBJECT-TYPE
Power share output status.
1.3.6.1.4.1.19536.10.1.1.4.1.4INTEGER {off(0), on(1)}read-onlycurrent
pdug5PowershareInput
OBJECT-TYPE
Power share input status.
1.3.6.1.4.1.19536.10.1.1.4.1.5INTEGER {off(0), on(1)}read-onlycurrent
pdug5PowershareOptMode
OBJECT-TYPE
Power share operation status of PDU. 0 meaning pdu is using powershare to power the NMC, 1 meaning pdu is using mains power to power the NMC
1.3.6.1.4.1.19536.10.1.1.4.1.6INTEGER {powerByPowershare(0), powerByMains(1)}read-onlycurrent
pdug5PowershareFunc
OBJECT-TYPE
Enable/Disable Powershare function of PDU. Set 1 to enable powershare. Set 0 to disable powershare
1.3.6.1.4.1.19536.10.1.1.4.1.7INTEGER {disablePowershare(0), enablePowershare(1)}read-writecurrent
pdug5Input
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.2
pdug5InputTable
OBJECT-TYPE
Aggregate Object with number of entries equal to pdug5NumberPDU .
1.3.6.1.4.1.19536.10.1.2.1not-accessiblecurrent
pdug5InputEntry
OBJECT-TYPE
The ident table entry containing the VA, Watts, WH, etc.
1.3.6.1.4.1.19536.10.1.2.1.1not-accessiblecurrent
pdug5InputType
OBJECT-TYPE
Type of input - single phase, split phase, three phase delta, or three phase wye.
1.3.6.1.4.1.19536.10.1.2.1.1.1INTEGER {singlePhase(1), splitPhase(2), threePhaseDelta(3), threePhaseWye(4)}read-onlycurrent
pdug5InputFrequency
OBJECT-TYPE
The measured input frequency from the PDU meters in tenths of Hz.
1.3.6.1.4.1.19536.10.1.2.1.1.2Integer32 (0..2147483647)read-onlycurrent
pdug5InputFrequencyStatus
OBJECT-TYPE
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
1.3.6.1.4.1.19536.10.1.2.1.1.3INTEGER {good(1), outOfRange(2)}read-onlycurrent
pdug5InputPowerVA
OBJECT-TYPE
A total input VA of all phases. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.1.1.4Integer32read-onlycurrent
pdug5InputPowerWatts
OBJECT-TYPE
A total input Watts of all phases. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.1.1.5Integer32read-onlycurrent
pdug5InputTotalEnergy
OBJECT-TYPE
A total input Watt-Hour value for all phases. Units are KWh. This value is accumulated since PDU in service. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.1.1.6Integer32read-onlycurrent
pdug5InputPowerWattHourTimer
OBJECT-TYPE
A Timestamp of when the Total Input WH was last reset.
1.3.6.1.4.1.19536.10.1.2.1.1.7DisplayString (SIZE(0..22))read-onlycurrent
pdug5InputResettableEnergy
OBJECT-TYPE
A total input Watt-Hour value for all phases. Units are Wh. This value can be reset to 0 using GUI. In that case, the pdug5InputPowerWattHourTimer will be reset as well A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.1.1.8Integer32read-onlycurrent
pdug5InputPowerFactor
OBJECT-TYPE
An input PF value. Units are in hundredths, for example a power factor of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.1.1.9Integer32read-onlycurrent
pdug5InputPowerVAR
OBJECT-TYPE
An input VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.1.1.10Integer32read-onlycurrent
pdug5InputTotalCurrent
OBJECT-TYPE
All phases total current value. Units are 0.01 amps. For 3 phase, mathematically add totally 3 phase current together.
1.3.6.1.4.1.19536.10.1.2.1.1.11Integer32read-onlycurrent
pdug5InputPhaseTable
OBJECT-TYPE
Aggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and number of input phase (pdug5InputPhaseCount).
1.3.6.1.4.1.19536.10.1.2.2not-accessiblecurrent
pdug5InputPhaseEntry
OBJECT-TYPE
The input table entry containing the voltage, current, frequency, power for each phase. Entries are given with number of pdu and number of input phase 1, 2, or 3.
1.3.6.1.4.1.19536.10.1.2.2.1not-accessiblecurrent
pdug5InputPhaseIndex
OBJECT-TYPE
Index for the pdug5InputEntry table.
1.3.6.1.4.1.19536.10.1.2.2.1.1Integer32 (1..3)not-accessiblecurrent
pdug5InputPhaseVoltageMeasType
OBJECT-TYPE
Value indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1.
1.3.6.1.4.1.19536.10.1.2.2.1.2INTEGER {singlePhase(1), phase1toN(2), phase2toN(3), phase3toN(4), phase1to2(5), phase2to3(6), phase3to1(7)}read-onlycurrent
pdug5InputPhaseVoltage
OBJECT-TYPE
An input voltage measurement value. Values is in 0.1 V.
1.3.6.1.4.1.19536.10.1.2.2.1.3Integer32read-onlycurrent
pdug5InputPhaseVoltageThStatus
OBJECT-TYPE
Status of the measured input voltage relative to the configured thresholds.
1.3.6.1.4.1.19536.10.1.2.2.1.4INTEGER {good(1), lowWarning(2), lowCritical(3), highWarning(4), highCritical(5)}read-onlycurrent
pdug5InputPhaseVoltageThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are 0.1 volts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.5Integer32 (-1..500000)read-writecurrent
pdug5InputPhaseVoltageThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are 0.1 volts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.6Integer32 (-1..500000)read-writecurrent
pdug5InputPhaseVoltageThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are 0.1 volts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.7Integer32 (-1..500000)read-writecurrent
pdug5InputPhaseVoltageThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are 0.1 volts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.8Integer32 (-1..500000)read-writecurrent
pdug5InputPhaseCurrentMeasType
OBJECT-TYPE
Which input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.
1.3.6.1.4.1.19536.10.1.2.2.1.9INTEGER {singlePhase(1), neutral(2), phase1(3), phase2(4), phase3(5)}read-onlycurrent
pdug5InputPhaseCurrentRating
OBJECT-TYPE
Rated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Units are 0.01 amps.
1.3.6.1.4.1.19536.10.1.2.2.1.10Integer32read-onlycurrent
pdug5InputPhaseCurrent
OBJECT-TYPE
An input current measurement value. Units are 0.01 amps.
1.3.6.1.4.1.19536.10.1.2.2.1.11Integer32read-onlycurrent
pdug5InputPhaseCurrentThStatus
OBJECT-TYPE
Status of the measured input current relative to the configured thresholds.
1.3.6.1.4.1.19536.10.1.2.2.1.12INTEGER {good(1), lowWarning(2), lowCritical(3), highWarning(4), highCritical(5)}read-onlycurrent
pdug5InputPhaseCurrentThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.13Integer32 (-1..100000)read-writecurrent
pdug5InputPhaseCurrentThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.14Integer32 (-1..100000)read-writecurrent
pdug5InputPhaseCurrentThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.15Integer32 (-1..100000)read-writecurrent
pdug5InputPhaseCurrentThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.16Integer32 (-1..100000)read-writecurrent
pdug5InputPhaseCurrentPercentLoad
OBJECT-TYPE
Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.17Integer32read-onlycurrent
pdug5InputPhasePowerMeasType
OBJECT-TYPE
Which input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.
1.3.6.1.4.1.19536.10.1.2.2.1.18INTEGER {singlePhase(1), neutral(2), phase1(3), phase2(4), phase3(5)}read-onlycurrent
pdug5InputPhasePowerVA
OBJECT-TYPE
An input VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.19Integer32read-onlycurrent
pdug5InputPhasePowerWatts
OBJECT-TYPE
An input Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.20Integer32read-onlycurrent
pdug5InputPhasePowerWattHour
OBJECT-TYPE
A Watt-Hour value for each Input phase. Units are WH. This value can be reset to 0 using GUI. In that case, the pdug5InputPhasePowerWattHourTimer will be reset as well A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.21Integer32read-onlycurrent
pdug5InputPhasePowerWattHourTimer
OBJECT-TYPE
Timestamp of when input Watt-hours (inputWh) was last reset.
1.3.6.1.4.1.19536.10.1.2.2.1.22DisplayString (SIZE(0..22))read-onlycurrent
pdug5InputPhasePowerFactor
OBJECT-TYPE
An input PF value. Units are in hundredths, for example a power factor of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.23Integer32read-onlycurrent
pdug5InputPhasePowerVAR
OBJECT-TYPE
An input VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.24Integer32read-onlycurrent
pdug5InputPhaseVoltageThResetThld
OBJECT-TYPE
The Reset threshold is the number of volts the reading needs to fall below the threshold setting for the condition to be cleared. Units are 0.1 volts.
1.3.6.1.4.1.19536.10.1.2.2.1.25Integer32read-writecurrent
pdug5InputPhaseVoltageThChangeDelay
OBJECT-TYPE
The number of consecutive sample that the condition is present before an alarm is raised.
1.3.6.1.4.1.19536.10.1.2.2.1.26Integer32 (0..100)read-writecurrent
pdug5InputPhaseVoltageThCtrl
OBJECT-TYPE
Input phase voltage alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disable
1.3.6.1.4.1.19536.10.1.2.2.1.27Integer32read-writecurrent
pdug5InputPhaseCurrentThResetThld
OBJECT-TYPE
The Reset threshold is the number of amps the reading needs to fall below the threshold setting for the condition to be cleared. Units are 0.01 amps.
1.3.6.1.4.1.19536.10.1.2.2.1.28Integer32read-writecurrent
pdug5InputPhaseCurrentThChangeDelay
OBJECT-TYPE
The number of consecutive sample that the condition is present before an alarm is raised.
1.3.6.1.4.1.19536.10.1.2.2.1.29Integer32 (0..100)read-writecurrent
pdug5InputPhaseCurrentThCtrl
OBJECT-TYPE
Input phase current alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disable
1.3.6.1.4.1.19536.10.1.2.2.1.30Integer32read-writecurrent
pdug5InputPowerThresholdThLowerWarning
OBJECT-TYPE
Lower warning Power threshold. Units are in Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.31Integer32 (-1..500000)read-writecurrent
pdug5InputPowerThresholdThLowerCritical
OBJECT-TYPE
Lower critical Power threshold. Units are in Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.32Integer32 (-1..500000)read-writecurrent
pdug5InputPowerThresholdThUpperWarning
OBJECT-TYPE
Upper warning Power threshold. Units are in Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.33Integer32 (-1..500000)read-writecurrent
pdug5InputPowerThresholdThUpperCritical
OBJECT-TYPE
Upper critical Power threshold. Units are in Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.34Integer32 (-1..500000)read-writecurrent
pdug5InputPowerThresholdThResetThld
OBJECT-TYPE
The Reset threshold is the number of watts the reading needs to fall below the threshold setting for the condition to be cleared. Units are watts.
1.3.6.1.4.1.19536.10.1.2.2.1.35Integer32read-writecurrent
pdug5InputPowerThresholdThChangeDelay
OBJECT-TYPE
The number of consecutive sample that the condition is present before an alarm is raised.
1.3.6.1.4.1.19536.10.1.2.2.1.36Integer32 (0..100)read-writecurrent
pdug5InputPowerThresholdThCtrl
OBJECT-TYPE
Power alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disable
1.3.6.1.4.1.19536.10.1.2.2.1.37Integer32read-writecurrent
pdug5InputEnergyThresholdThUpperWarning
OBJECT-TYPE
Upper warning Energy threshold. Units are in Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.38Integer32 (-1..500000)read-writecurrent
pdug5InputEnergyThresholdThUpperCritical
OBJECT-TYPE
Upper critical Energy threshold. Units are in Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.2.1.39Integer32 (-1..500000)read-writecurrent
pdug5InputEnergyThresholdThResetThld
OBJECT-TYPE
The Reset threshold is the number of watts the reading needs to fall below the threshold setting for the condition to be cleared. Units are watts.
1.3.6.1.4.1.19536.10.1.2.2.1.40Integer32read-writecurrent
pdug5InputEnergyThresholdThChangeDelay
OBJECT-TYPE
The number of consecutive sample that the condition is present before an alarm is raised.
1.3.6.1.4.1.19536.10.1.2.2.1.41Integer32 (0..100)read-writecurrent
pdug5InputEnergyThresholdThCtrl
OBJECT-TYPE
Energy alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disable
1.3.6.1.4.1.19536.10.1.2.2.1.42Integer32read-writecurrent
pdug5InputPhasePowerThStatus
OBJECT-TYPE
Status of the measured input current relative to the configured thresholds.
1.3.6.1.4.1.19536.10.1.2.2.1.43INTEGER {good(1), lowWarning(2), lowCritical(3), highWarning(4), highCritical(5)}read-onlycurrent
pdug5InputRcmTable
OBJECT-TYPE
Aggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and number of RCM modules per PDU.
1.3.6.1.4.1.19536.10.1.2.3not-accessiblecurrent
pdug5InputRcmEntry
OBJECT-TYPE
The ident table entry containing the RCM Module status, RCM current, RCM module threshold settings, etc.
1.3.6.1.4.1.19536.10.1.2.3.1not-accessiblecurrent
pdug5InputRcmEnabled
OBJECT-TYPE
RCM configuration value off(0) if the PDU doesn't have RCM, on(1) if the PDU has RCM.
1.3.6.1.4.1.19536.10.1.2.3.1.1INTEGER {featureNotAvailable(-1), off(0), on(1)}read-onlycurrent
pdug5InputRcmModStatus
OBJECT-TYPE
RCM module status ok(2) if the PDU can communicate with the RCM module, failed(4) if the PDU cannot communicate with the RCM module, degraded(3) if the PDU can communicate with the RCM module and the last self-test failed.
1.3.6.1.4.1.19536.10.1.2.3.1.2INTEGER {featureNotAvailable(-1), ok(2), degraded(3), failed(4)}read-onlycurrent
pdug5InputRcmThUpperWarning
OBJECT-TYPE
RCM Current Upper warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.3.1.3Integer32 (15..300)read-writecurrent
pdug5InputRcmThUpperCritical
OBJECT-TYPE
RCM Current Upper critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.2.3.1.4Integer32 (15..300)read-writecurrent
pdug5InputRcmThResetThld
OBJECT-TYPE
The Reset threshold is the number of amps the reading needs to fall below the threshold setting for the condition to be cleared. Units are 0.01 amps.
1.3.6.1.4.1.19536.10.1.2.3.1.5Integer32 (0..16)read-writecurrent
pdug5InputRcmThChangeDelay
OBJECT-TYPE
The number of consecutive sample that the condition is present before an alarm is raised.
1.3.6.1.4.1.19536.10.1.2.3.1.6Integer32 (0..100)read-writecurrent
pdug5InputRcmThCtrl
OBJECT-TYPE
Rcm current alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable.
1.3.6.1.4.1.19536.10.1.2.3.1.7Integer32read-writecurrent
pdug5InputRcmThStatus
OBJECT-TYPE
Status of the measured Rcm current relative to the configured thresholds.
1.3.6.1.4.1.19536.10.1.2.3.1.8INTEGER {featureNotAvailable(-1), good(1), highWarning(4), highCritical(5)}read-onlycurrent
pdug5InputRcmCurrent
OBJECT-TYPE
Rcm module current reading. Units are milliAmps.
1.3.6.1.4.1.19536.10.1.2.3.1.9Integer32read-onlycurrent
pdug5InputRcmSelfTestTable
OBJECT-TYPE
Aggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and number of Rcm modules per PDU.
1.3.6.1.4.1.19536.10.1.2.4not-accessiblecurrent
pdug5InputRcmSelfTestEntry
OBJECT-TYPE
The ident table entry containing the Rcm Module Self Test Enable, Schedule, LastRunTime,LastRunStatus etc.
1.3.6.1.4.1.19536.10.1.2.4.1not-accessiblecurrent
pdug5InputRcmSelfTestEnable
OBJECT-TYPE
Rcm Self Test configuration value Disable(0) if the self test is disabled on the PDU, Enable(1) if self test is enabled on the PDU .
1.3.6.1.4.1.19536.10.1.2.4.1.1INTEGER {featureNotAvailable(-1), disable(0), enable(1)}read-writecurrent
pdug5InputRcmSelfTestFreq
OBJECT-TYPE
Rcm module self test run frequency , the time for the test is set from Pdug5RcmSelfTestNextRunTime, the self test will be repeated based on the setting as Daily(1),Weekly(2),First Day Of Month(3),Yearly(4)
1.3.6.1.4.1.19536.10.1.2.4.1.2INTEGER {featureNotAvailable(-1), daily(1), weekly(2), monthly(3), yearly(4)}read-writecurrent
pdug5InputRcmSelfTestHour
OBJECT-TYPE
Rcm module self test schedule hour setting,-1 means feature not available
1.3.6.1.4.1.19536.10.1.2.4.1.3Integer32 (-1..23)read-writecurrent
pdug5InputRcmSelfTestMinute
OBJECT-TYPE
Rcm module self test schedule minute setting,-1 means feature not available
1.3.6.1.4.1.19536.10.1.2.4.1.4Integer32 (-1..59)read-writecurrent
pdug5InputRcmSelfTestDay
OBJECT-TYPE
Rcm module self test schedule day setting,-1 means feature not available
1.3.6.1.4.1.19536.10.1.2.4.1.5INTEGER {featureNotAvailable(-1), sunday(0), monday(1), tuesday(2), wednesday(3), thursday(4), friday(5), saturday(6)}read-writecurrent
pdug5InputRcmSelfTestMonth
OBJECT-TYPE
Rcm module self test schedule month setting,-1 means feature not available
1.3.6.1.4.1.19536.10.1.2.4.1.6INTEGER {featureNotAvailable(-1), january(0), february(1), march(2), april(3), may(4), june(5), july(6), august(7), september(8), october(9), november(10), december(11)}read-writecurrent
pdug5InputRcmSelfTestNextRunTime
OBJECT-TYPE
next run date and Time for self test.
1.3.6.1.4.1.19536.10.1.2.4.1.7DisplayStringread-onlycurrent
pdug5InputRcmSelfTestLastRunTime
OBJECT-TYPE
Date and Time when the self test run previously
1.3.6.1.4.1.19536.10.1.2.4.1.8DisplayStringread-onlycurrent
pdug5InputRcmSelfTestLastRunStatus
OBJECT-TYPE
Status of the lastest self test run
1.3.6.1.4.1.19536.10.1.2.4.1.9INTEGER {featureNotAvailable(-1), passed(1), failed(2), pending(3)}read-onlycurrent
pdug5Group
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.3
pdug5GroupTable
OBJECT-TYPE
Aggregate Object with number of entries equal to number of PDUs and number of breakers (pdug5GroupCount).
1.3.6.1.4.1.19536.10.1.3.1not-accessiblecurrent
pdug5GroupEntry
OBJECT-TYPE
The input table entry containing the name, voltages, currents, power, etc.
1.3.6.1.4.1.19536.10.1.3.1.1not-accessiblecurrent
pdug5GroupIndex
OBJECT-TYPE
Index for the pdug5GroupEntry table.
1.3.6.1.4.1.19536.10.1.3.1.1.1Integer32 (0..12)not-accessiblecurrent
pdug5GroupName
OBJECT-TYPE
A descriptive name for the group.
1.3.6.1.4.1.19536.10.1.3.1.1.2DisplayString (SIZE(1..31))read-writecurrent
pdug5GroupType
OBJECT-TYPE
The type of the group. (5) has no breaker
1.3.6.1.4.1.19536.10.1.3.1.1.3INTEGER {breaker1pole(2), breaker2pole(3), breaker3pole(4), outletSection(5)}read-onlycurrent
pdug5GroupVoltageMeasType
OBJECT-TYPE
Value indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1.
1.3.6.1.4.1.19536.10.1.3.1.1.4INTEGER {singlePhase(1), phase1toN(2), phase2toN(3), phase3toN(4), phase1to2(5), phase2to3(6), phase3to1(7)}read-onlycurrent
pdug5GroupVoltage
OBJECT-TYPE
Units are 0.1 volts.
1.3.6.1.4.1.19536.10.1.3.1.1.5Integer32read-onlycurrent
pdug5GroupVoltageThStatus
OBJECT-TYPE
Status of the measured group voltage relative to the configured thresholds.
1.3.6.1.4.1.19536.10.1.3.1.1.6INTEGER {good(1), lowWarning(2), lowCritical(3), highWarning(4), highCritical(5)}read-onlycurrent
pdug5GroupVoltageThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are 0.1 volts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.7Integer32 (-1..500000)read-onlycurrent
pdug5GroupVoltageThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are 0.1 volts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.8Integer32 (-1..500000)read-onlycurrent
pdug5GroupVoltageThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are 0.1 volts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.9Integer32 (-1..500000)read-onlycurrent
pdug5GroupVoltageThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are 0.1 volts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.10Integer32 (-1..500000)read-onlycurrent
pdug5groupCurrentRating
OBJECT-TYPE
Rated current capacity of the group. Units are 0.01 amps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups).
1.3.6.1.4.1.19536.10.1.3.1.1.11Integer32read-onlycurrent
pdug5GroupCurrent
OBJECT-TYPE
A group current measurement value. Units are 0.01 amps.
1.3.6.1.4.1.19536.10.1.3.1.1.12Integer32read-onlycurrent
pdug5GroupCurrentThStatus
OBJECT-TYPE
Status of the measured group current relative to the configured thresholds.
1.3.6.1.4.1.19536.10.1.3.1.1.13INTEGER {good(1), lowWarning(2), lowCritical(3), highWarning(4), highCritical(5), cbOff(6)}read-onlycurrent
pdug5GroupCurrentThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.14Integer32 (-1..100000)read-writecurrent
pdug5GroupCurrentThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.15Integer32 (-1..100000)read-writecurrent
pdug5GroupCurrentThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.16Integer32 (-1..100000)read-writecurrent
pdug5GroupCurrentThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.17Integer32 (-1..100000)read-writecurrent
pdug5GroupCurrentPercentLoad
OBJECT-TYPE
Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.18Integer32read-onlycurrent
pdug5GroupPowerVA
OBJECT-TYPE
A group VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.19Integer32read-onlycurrent
pdug5GroupPowerWatts
OBJECT-TYPE
A group power value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.20Integer32read-onlycurrent
pdug5GroupPowerWattHour
OBJECT-TYPE
A Watt-Hour value for each section. Units are WH. This value can be reset to 0 using GUI. In that case, the pdug5GroupPowerWattHourTimer will be reset as well. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.21Integer32read-onlycurrent
pdug5GroupPowerWattHourTimer
OBJECT-TYPE
Timestamp of when group Watt-hours (groupWh) was last reset.
1.3.6.1.4.1.19536.10.1.3.1.1.22DisplayString (SIZE(0..22))read-onlycurrent
pdug5GroupPowerFactor
OBJECT-TYPE
A group PF value. Units are in hundredths, for example a power factor of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.23Integer32read-onlycurrent
pdug5GroupPowerVAR
OBJECT-TYPE
A group VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.3.1.1.24Integer32read-onlycurrent
pdug5GroupOutletCount
OBJECT-TYPE
The number of outlets in each group (breaker).
1.3.6.1.4.1.19536.10.1.3.1.1.25Integer32 (0..48)read-onlycurrent
pdug5GroupBreakerStatus
OBJECT-TYPE
Only applicable to groups with breaker. Indicates whether a breaker is turned off or on.
1.3.6.1.4.1.19536.10.1.3.1.1.26INTEGER {notApplicable(1), breakerOn(2), breakerOff(3)}read-onlycurrent
pdug5GroupVoltageThCtrl
OBJECT-TYPE
Circuit Breaker voltage alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disable
1.3.6.1.4.1.19536.10.1.3.1.1.27Integer32read-onlycurrent
pdug5GroupCurrentThCtrl
OBJECT-TYPE
Circuit Breaker current alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disable
1.3.6.1.4.1.19536.10.1.3.1.1.28Integer32read-writecurrent
pdug5Environment
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.4
pdug5EnvProbeTable
OBJECT-TYPE
A list of environment probe (1 per PDU) for temperature, humidity, and contacts. The number of entries is given by number of PDUs in daisy chain.
1.3.6.1.4.1.19536.10.1.4.1not-accessiblecurrent
pdug5EnvProbeEntry
OBJECT-TYPE
Aggregate entries equal to number of PDUs.
1.3.6.1.4.1.19536.10.1.4.1.1not-accessiblecurrent
pdug5TemperatureScale
OBJECT-TYPE
Scale used to return temperature objects.
1.3.6.1.4.1.19536.10.1.4.1.1.1INTEGER {celsius(1), fahrenheit(2)}read-writecurrent
pdug5TemperatureCount
OBJECT-TYPE
The number of temperature measurements.The MAX is 6 (1 per probe).
1.3.6.1.4.1.19536.10.1.4.1.1.2Integer32read-onlycurrent
pdug5HumidityCount
OBJECT-TYPE
The number of humidity measurements.The MAX is 6(1 per probe).
1.3.6.1.4.1.19536.10.1.4.1.1.3Integer32read-onlycurrent
pdug5DoorCount
OBJECT-TYPE
The number of door sensors.The MAX is 6(1 per probe).
1.3.6.1.4.1.19536.10.1.4.1.1.4Integer32read-onlycurrent
pdug5DryCount
OBJECT-TYPE
The number of dry sensors.The MAX is 2(1 per probe).
1.3.6.1.4.1.19536.10.1.4.1.1.5Integer32read-onlycurrent
pdug5SpotCount
OBJECT-TYPE
The number of spot sensors.The MAX is 2(1 per probe).
1.3.6.1.4.1.19536.10.1.4.1.1.6Integer32read-onlycurrent
pdug5RopeCount
OBJECT-TYPE
The number of rope sensors.The MAX is 2(1 per probe).
1.3.6.1.4.1.19536.10.1.4.1.1.7Integer32read-onlycurrent
pdug5HidCount
OBJECT-TYPE
The number of hid sensors. The MAX is 2(1 per probe).
1.3.6.1.4.1.19536.10.1.4.1.1.10Integer32read-onlycurrent
pdug5TemperatureTable
OBJECT-TYPE
A list of temperature probe measurements. The number of entries are given by number of pdu and pdug5TemperatureCount.
1.3.6.1.4.1.19536.10.1.4.2not-accessiblecurrent
pdug5TemperatureEntry
OBJECT-TYPE
An entry for a temperature measurement.
1.3.6.1.4.1.19536.10.1.4.2.1not-accessiblecurrent
pdug5TemperatureIndex
OBJECT-TYPE
A unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount.
1.3.6.1.4.1.19536.10.1.4.2.1.1Integer32 (1..6)not-accessiblecurrent
pdug5TemperatureName
OBJECT-TYPE
A descriptive name for the temperature probe.
1.3.6.1.4.1.19536.10.1.4.2.1.2DisplayString (SIZE(1..15))read-writecurrent
pdug5TemperatureProbeStatus
OBJECT-TYPE
Indicates whether a probe is connected or not.
1.3.6.1.4.1.19536.10.1.4.2.1.3INTEGER {disconnected(1), connected(2), bad(3)}read-onlycurrent
pdug5TemperatureValue
OBJECT-TYPE
Units are degree(either Fahrenheit or Celsius).
1.3.6.1.4.1.19536.10.1.4.2.1.4Integer32read-onlycurrent
pdug5TemperatureThStatus
OBJECT-TYPE
Status of the measured temperature relative to the configured thresholds.
1.3.6.1.4.1.19536.10.1.4.2.1.5INTEGER {good(1), lowWarning(2), lowCritical(3), highWarning(4), highCritical(5)}read-onlycurrent
pdug5TemperatureThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are degrees. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.4.2.1.6Integer32 (-1..150000)read-writecurrent
pdug5TemperatureThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are degrees. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.4.2.1.7Integer32 (-1..150000)read-writecurrent
pdug5TemperatureThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are degrees. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.4.2.1.8Integer32 (-1..150000)read-writecurrent
pdug5TemperatureThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are degrees. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.4.2.1.9Integer32 (-1..150000)read-writecurrent
pdug5TemperatureThCtrl
OBJECT-TYPE
Temperature alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disable
1.3.6.1.4.1.19536.10.1.4.2.1.10Integer32read-writecurrent
pdug5HumidityTable
OBJECT-TYPE
A list of humidity probe measurements. The number of entries are given by number of pdu and pdug5HumidityCount.
1.3.6.1.4.1.19536.10.1.4.3not-accessiblecurrent
pdug5HumidityEntry
OBJECT-TYPE
An entry for a humidity measurement.
1.3.6.1.4.1.19536.10.1.4.3.1not-accessiblecurrent
pdug5HumidityIndex
OBJECT-TYPE
A unique value for each humidity probe measurement. Its value ranges from 1 to pdug5HumidityCount per PDU.
1.3.6.1.4.1.19536.10.1.4.3.1.1Integer32 (1..6)not-accessiblecurrent
pdug5HumidityName
OBJECT-TYPE
A descriptive name for the humidity probe.
1.3.6.1.4.1.19536.10.1.4.3.1.2DisplayString (SIZE(1..15))read-writecurrent
pdug5HumidityProbeStatus
OBJECT-TYPE
Indicates whether a probe is connected or not.
1.3.6.1.4.1.19536.10.1.4.3.1.3INTEGER {disconnected(1), connected(2), bad(3)}read-onlycurrent
pdug5HumidityValue
OBJECT-TYPE
Units are %RH.
1.3.6.1.4.1.19536.10.1.4.3.1.4Integer32read-onlycurrent
pdug5HumidityThStatus
OBJECT-TYPE
Status of the measured humidity relative to the configured thresholds.
1.3.6.1.4.1.19536.10.1.4.3.1.5INTEGER {good(1), lowWarning(2), lowCritical(3), highWarning(4), highCritical(5)}read-onlycurrent
pdug5HumidityThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.4.3.1.6Integer32 (-1..1000)read-writecurrent
pdug5HumidityThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.4.3.1.7Integer32 (-1..1000)read-writecurrent
pdug5HumidityThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.4.3.1.8Integer32 (-1..1000)read-writecurrent
pdug5HumidityThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.4.3.1.9Integer32 (-1..1000)read-writecurrent
pdug5HumidityThCtrl
OBJECT-TYPE
Humidity alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disable
1.3.6.1.4.1.19536.10.1.4.3.1.10Integer32read-writecurrent
pdug5DoorTable
OBJECT-TYPE
A list of door sensors. The number of entries are given by number of PDU and pdug5DoorCount.
1.3.6.1.4.1.19536.10.1.4.4not-accessiblecurrent
pdug5DoorEntry
OBJECT-TYPE
An entry for a door sensor
1.3.6.1.4.1.19536.10.1.4.4.1not-accessiblecurrent
pdug5DoorIndex
OBJECT-TYPE
A unique value for each door sensor. Its value ranges from 1 to doorCount.
1.3.6.1.4.1.19536.10.1.4.4.1.1Integer32 (1..2)not-accessiblecurrent
pdug5DoorName
OBJECT-TYPE
A descriptive name for the door sensor.
1.3.6.1.4.1.19536.10.1.4.4.1.2DisplayString (SIZE(1..15))read-writecurrent
pdug5DoorProbeStatus
OBJECT-TYPE
Indicates whether a probe is connected or not. Will not be returned if the door sensor is internal to the ePDU, in that case only doorState should be read.
1.3.6.1.4.1.19536.10.1.4.4.1.3INTEGER {disconnected(1), connected(2), bad(3)}read-onlycurrent
pdug5DoorState
OBJECT-TYPE
The state of the door sensor.
1.3.6.1.4.1.19536.10.1.4.4.1.4INTEGER {doorOpen(1), doorClosed(2), badDoorSensor(3)}read-onlycurrent
pdug5DryTable
OBJECT-TYPE
A list of dry sensors. The number of entries are given by number of pdu and pdug5DryCount.
1.3.6.1.4.1.19536.10.1.4.5not-accessiblecurrent
pdug5DryEntry
OBJECT-TYPE
An entry for a contact sensor
1.3.6.1.4.1.19536.10.1.4.5.1not-accessiblecurrent
pdug5DryIndex
OBJECT-TYPE
A unique value for each dry sensor. Its value ranges from 1 to dryCount.
1.3.6.1.4.1.19536.10.1.4.5.1.1Integer32 (1..2)not-accessiblecurrent
pdug5DryName
OBJECT-TYPE
A descriptive name for the dry sensor.
1.3.6.1.4.1.19536.10.1.4.5.1.2DisplayString (SIZE(1..15))read-writecurrent
pdug5DryProbeStatus
OBJECT-TYPE
Indicates whether a probe is connected or not.
1.3.6.1.4.1.19536.10.1.4.5.1.3INTEGER {disconnected(1), connected(2), bad(3)}read-onlycurrent
pdug5DryState
OBJECT-TYPE
The state of the dry sensor.
1.3.6.1.4.1.19536.10.1.4.5.1.4INTEGER {good(1), alarmed(2)}read-onlycurrent
pdug5SpotTable
OBJECT-TYPE
A list of contact sensors. The number of entries are given by number of pdu and pdug5SpotCount.
1.3.6.1.4.1.19536.10.1.4.6not-accessiblecurrent
pdug5SpotEntry
OBJECT-TYPE
An entry for a contact sensor
1.3.6.1.4.1.19536.10.1.4.6.1not-accessiblecurrent
pdug5SpotIndex
OBJECT-TYPE
A unique value for each spot sensor. Its value ranges from 1 to spotCount.
1.3.6.1.4.1.19536.10.1.4.6.1.1Integer32 (1..3)not-accessiblecurrent
pdug5SpotName
OBJECT-TYPE
A descriptive name for the spot sensor.
1.3.6.1.4.1.19536.10.1.4.6.1.2DisplayString (SIZE(1..15))read-writecurrent
pdug5SpotProbeStatus
OBJECT-TYPE
Indicates whether a probe is connected or not.
1.3.6.1.4.1.19536.10.1.4.6.1.3INTEGER {disconnected(1), connected(2), bad(3)}read-onlycurrent
pdug5SpotState
OBJECT-TYPE
The state of the spot sensor.
1.3.6.1.4.1.19536.10.1.4.6.1.4INTEGER {noleak(1), leak(2)}read-onlycurrent
pdug5RopeTable
OBJECT-TYPE
A list of rope sensors. The number of entries are given by number of pdu and pdug5RopeCount.
1.3.6.1.4.1.19536.10.1.4.7not-accessiblecurrent
pdug5RopeEntry
OBJECT-TYPE
An entry for a contact sensor
1.3.6.1.4.1.19536.10.1.4.7.1not-accessiblecurrent
pdug5RopeIndex
OBJECT-TYPE
A unique value for each rope sensor. Its value ranges from 1 to ropeCount.
1.3.6.1.4.1.19536.10.1.4.7.1.1Integer32 (1..3)not-accessiblecurrent
pdug5RopeName
OBJECT-TYPE
A descriptive name for the rope sensor.
1.3.6.1.4.1.19536.10.1.4.7.1.2DisplayString (SIZE(1..15))read-writecurrent
pdug5RopeProbeStatus
OBJECT-TYPE
Indicates whether a probe is connected or not.
1.3.6.1.4.1.19536.10.1.4.7.1.3INTEGER {disconnected(1), connected(2), bad(3)}read-onlycurrent
pdug5RopeState
OBJECT-TYPE
The state of the rope sensor.
1.3.6.1.4.1.19536.10.1.4.7.1.4INTEGER {noleak(1), leak(2)}read-onlycurrent
pdug5EnvHID
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.4.10
pdug5EnvHidTable
OBJECT-TYPE
A list of contact sensors. The number of entries are given by number of pdu and pdug5HidCount.
1.3.6.1.4.1.19536.10.1.4.10.1not-accessiblecurrent
pdug5EnvHidEntry
OBJECT-TYPE
An entry for a contact sensor
1.3.6.1.4.1.19536.10.1.4.10.1.1not-accessiblecurrent
pdug5HIDIndex
OBJECT-TYPE
The index of the PDU HID table entry
1.3.6.1.4.1.19536.10.1.4.10.1.1.1Integer32 (1..2)not-accessiblecurrent
pdug5HidAisle
OBJECT-TYPE
Aisle of HID handle.
1.3.6.1.4.1.19536.10.1.4.10.1.1.2INTEGER {cold(1), hot(2)}read-onlycurrent
pdug5HidHandleOperation
OBJECT-TYPE
HID handle control operations
1.3.6.1.4.1.19536.10.1.4.10.1.1.3INTEGER {unlock(1), lock(2)}read-writecurrent
pduHIDVer
OBJECT-TYPE
The firmware revision level of the HID
1.3.6.1.4.1.19536.10.1.4.10.1.1.4DisplayString (SIZE(0..63))read-onlycurrent
pdug5MechanicalLock
OBJECT-TYPE
HID Mechanical operations
1.3.6.1.4.1.19536.10.1.4.10.1.1.5INTEGER {unlock(1), lock(2)}read-onlycurrent
pduHIDSerial
OBJECT-TYPE
The Serial Number of the HID
1.3.6.1.4.1.19536.10.1.4.10.1.1.6DisplayString (SIZE(0..63))read-onlycurrent
pduHIDHwVer
OBJECT-TYPE
The hardware revision level of the HID
1.3.6.1.4.1.19536.10.1.4.10.1.1.7DisplayString (SIZE(0..63))read-onlycurrent
pdug5HIDAutoLockTime
OBJECT-TYPE
HID Electronic Latch Autolock Time in seconds, Value ranges (0-999)
1.3.6.1.4.1.19536.10.1.4.10.1.1.8Integer32read-writecurrent
pdug5HIDDoorOpenTime
OBJECT-TYPE
HID Door Open Time in seconds, Value ranges (0-999)
1.3.6.1.4.1.19536.10.1.4.10.1.1.9Integer32read-writecurrent
pdug5HIDMaxDoorOpenTime
OBJECT-TYPE
HID Max Door Open Time in seconds, Value ranges (0-32400), critical alarm will be raised if door is left open past this time
1.3.6.1.4.1.19536.10.1.4.10.1.1.10Integer32read-writecurrent
pdug5HIDUserPinLength
OBJECT-TYPE
Rack Access User minimum PIN Length, value ranges(0-16)
1.3.6.1.4.1.19536.10.1.4.10.1.1.11Integer32read-writecurrent
pdug5HIDUserPinMode
OBJECT-TYPE
Rack Access User PIN mode setting
1.3.6.1.4.1.19536.10.1.4.10.1.1.12INTEGER {visible(1), hidden(2)}read-writecurrent
pdug5HIDAisleControl
OBJECT-TYPE
Rack Access Aisle Control setting, when set to standalone each aisle will controlled separately, when set to combined opposite aisle can be controlled with authenticated control action on either aisle
1.3.6.1.4.1.19536.10.1.4.10.1.1.13INTEGER {combined(1), standalone(2)}read-writecurrent
pdug5HIDBeaconFuncControl
OBJECT-TYPE
Beacon Function Control
1.3.6.1.4.1.19536.10.1.4.10.1.1.14INTEGER {locate(0), standby(1)}read-writecurrent
pdug5HidBeaconColorControl
OBJECT-TYPE
Beacon Color Control
1.3.6.1.4.1.19536.10.1.4.10.1.1.15INTEGER {red(0), green(1), blue(2), yellow(3), magenta(4), aqua(5), white(6), beaconoff(7)}read-writecurrent
pdug5EnvHidControlTable
OBJECT-TYPE
A list of smartcard. The number of entries are given by number of pdu and pdug5HidCount.
1.3.6.1.4.1.19536.10.1.4.10.2not-accessiblecurrent
pdug5EnvHidControlEntry
OBJECT-TYPE
The smart card table entry containing the username, cardid, cardaisle etc.
1.3.6.1.4.1.19536.10.1.4.10.2.1not-accessiblecurrent
pdug5HidControlIndex
OBJECT-TYPE
The index of the PDU smartcard table entry
1.3.6.1.4.1.19536.10.1.4.10.2.1.1Integer32 (1..200)not-accessiblecurrent
pdug5HidControlUserName
OBJECT-TYPE
User name of smartcard. Use #delete# to delete the HID user
1.3.6.1.4.1.19536.10.1.4.10.2.1.2DisplayStringread-writecurrent
pdug5HidControlCardID
OBJECT-TYPE
HID smartcard ID.
1.3.6.1.4.1.19536.10.1.4.10.2.1.3Integer32read-writecurrent
pdug5HidControlTimestamp
OBJECT-TYPE
Indicates the date and time of accessing
1.3.6.1.4.1.19536.10.1.4.10.2.1.4DisplayStringread-onlycurrent
pdug5HidControlCardAisle
OBJECT-TYPE
Aisle of authorized card
1.3.6.1.4.1.19536.10.1.4.10.2.1.5INTEGER {cold(1), hot(2), both(3)}read-writecurrent
pdug5HidControlStartTime
OBJECT-TYPE
Indicates the start date and time Rack access user is given access
1.3.6.1.4.1.19536.10.1.4.10.2.1.6DisplayStringread-writecurrent
pdug5HidControlExpireTime
OBJECT-TYPE
Indicates the date and time when the access of user card will expire, To set expire time first set user as temporary user
1.3.6.1.4.1.19536.10.1.4.10.2.1.7DisplayStringread-writecurrent
pdug5HidControlTempUser
OBJECT-TYPE
Indicates if the card user has temporary access
1.3.6.1.4.1.19536.10.1.4.10.2.1.8INTEGER {no(1), yes(2)}read-writecurrent
pdug5HidControlPin
OBJECT-TYPE
Rack access control entry keypad PIN
1.3.6.1.4.1.19536.10.1.4.10.2.1.9DisplayStringread-writecurrent
pdug5HidControlCardIdStr
OBJECT-TYPE
Smartrack Access Card ID String
1.3.6.1.4.1.19536.10.1.4.10.2.1.10DisplayStringread-writecurrent
pdug5Outlet
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.5
pdug5OutletTable
OBJECT-TYPE
Aggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex) and Number of outlet per PDU (pdug5OutletIndex).
1.3.6.1.4.1.19536.10.1.5.1not-accessiblecurrent
pdug5OutletEntry
OBJECT-TYPE
The Outlet table entry containing the type, voltage, current etc.
1.3.6.1.4.1.19536.10.1.5.1.1not-accessiblecurrent
pdug5OutletIndex
OBJECT-TYPE
Index for each outlet, value from 1 to the number of outlets per PDU.
1.3.6.1.4.1.19536.10.1.5.1.1.1Integer32 (0..48)not-accessiblecurrent
pdug5OutletName
OBJECT-TYPE
A descriptive name for the outlet.
1.3.6.1.4.1.19536.10.1.5.1.1.2DisplayString (SIZE(1..31))read-writecurrent
pdug5OutletType
OBJECT-TYPE
Type of this outlet - C13, C19, 5-20R, iecC13/C15 COMBO, iecC13/C15/C19 COMBO...
1.3.6.1.4.1.19536.10.1.5.1.1.3INTEGER {iecC13(1), iecC19(2), nema5-20R(3), iecC13iecC15combo(4), iecC13iecC15iec19combo(5), uk(10), french(11), schuko(12), nema515(20), nema51520(21), nema520(22), nemaL520(23), nemaL530(24), nema615(25), nema620(26), nemaL620(27), nemaL630(28), nemaL715(29), rf203p277(30)}read-onlycurrent
pdug5OutletCurrentRating
OBJECT-TYPE
Rated current capacity of this outlet. Units are 0.01 amps. A negative value indicates that the hardware current capacity is unknown.
1.3.6.1.4.1.19536.10.1.5.1.1.4Integer32read-onlycurrent
pdug5OutletCurrent
OBJECT-TYPE
A outlet current measurement value. Units are 0.01 amps.
1.3.6.1.4.1.19536.10.1.5.1.1.5Integer32read-onlycurrent
pdug5OutletActivePowerThStatus
OBJECT-TYPE
Status of the measured outlet active power relative to the configured thresholds.
1.3.6.1.4.1.19536.10.1.5.1.1.6INTEGER {good(1), lowWarning(2), lowCritical(3), highWarning(4), highCritical(5)}read-onlycurrent
pdug5OutletActivePowerThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are Watts(W). A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.7Integer32 (-1..10000)read-writecurrent
pdug5OutletActivePowerThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are Watts(W). A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.8Integer32 (-1..10000)read-writecurrent
pdug5OutletActivePowerThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are Watts(W). A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.9Integer32 (-1..10000)read-writecurrent
pdug5OutletActivePowerThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are Watts(W). A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.10Integer32 (-1..10000)read-writecurrent
pdug5OutletCurrentPercentLoad
OBJECT-TYPE
Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.11Integer32read-onlycurrent
pdug5OutletVA
OBJECT-TYPE
A outlet VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.12Integer32read-onlycurrent
pdug5OutletWatts
OBJECT-TYPE
A outlet Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.13Integer32read-onlycurrent
pdug5OutletWh
OBJECT-TYPE
A Watt-Hour value for each outlet. Units are WH. This object is writable so that it can be reset to 0. When it is written to, the pdug5OutletWhTimer will be reset updated as well A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.14Integer32read-onlycurrent
pdug5OutletWhTimer
OBJECT-TYPE
Timestamp (date and time) of outlet Watt-hours was last reset.
1.3.6.1.4.1.19536.10.1.5.1.1.15DisplayString (SIZE(0..22))read-onlycurrent
pdug5OutletPowerFactor
OBJECT-TYPE
An outlet PF value. Units are in hundredths, for example a power factor of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.16Integer32read-onlycurrent
pdug5OutletVAR
OBJECT-TYPE
An outlet VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.19536.10.1.5.1.1.17Integer32read-onlycurrent
pdug5OutletBranch
OBJECT-TYPE
The branch number outlet located.
1.3.6.1.4.1.19536.10.1.5.1.1.18Integer32read-onlycurrent
pdug5OutletActivePowerThResetThld
OBJECT-TYPE
The Reset threshold is the number of watss the reading needs to fall below the threshold setting for the condition to be cleared. Units are watts.
1.3.6.1.4.1.19536.10.1.5.1.1.19Integer32 (-1..10000)read-writecurrent
pdug5OutletActivePowerThChangeDelay
OBJECT-TYPE
The number of consecutive sample that the condition is present before an alarm is raised.
1.3.6.1.4.1.19536.10.1.5.1.1.20Integer32 (0..100)read-writecurrent
pdug5OutletActivePowerThCtrl
OBJECT-TYPE
Outlet Active Power alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disable
1.3.6.1.4.1.19536.10.1.5.1.1.21Integer32read-writecurrent
pdug5OutletControlTable
OBJECT-TYPE
Aggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex) and Number of outlets per PDU (pdug5OutletIndex).
1.3.6.1.4.1.19536.10.1.5.2not-accessiblecurrent
pdug5OutletControlEntry
OBJECT-TYPE
The Outlet table entry containing the type, voltage, current etc.
1.3.6.1.4.1.19536.10.1.5.2.1not-accessiblecurrent
pdug5OutletControlStatus
OBJECT-TYPE
current state of a control outlet.
1.3.6.1.4.1.19536.10.1.5.2.1.1INTEGER {off(1), on(2), pendingOff(3), pendingOn(4)}read-onlycurrent
pdug5OutletControlOffCmd
OBJECT-TYPE
When write, once issued, the outlet will turn Off immediately. 0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
1.3.6.1.4.1.19536.10.1.5.2.1.2Integer32 (-1..99999)read-writecurrent
pdug5OutletControlOnCmd
OBJECT-TYPE
When write, once issued, the outlet will turn On immediately. 0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet On command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
1.3.6.1.4.1.19536.10.1.5.2.1.3Integer32 (-1..99999)read-writecurrent
pdug5OutletControlRebootCmd
OBJECT-TYPE
When write, for outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn back On. For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime seconds from when the command is issued. 0-n : Time in seconds until the Reboot command is issued -1 : Cancel a pending outlet Reboot command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
1.3.6.1.4.1.19536.10.1.5.2.1.4Integer32 (-1..99999)read-writecurrent
pdug5OutletControlPowerOnState
OBJECT-TYPE
Determines the outlet state when power is applied to the unit. 1 : not restart at device startup 2 : should sequence back ON in line with outletControlSequenceTime 3 : should take the state the outlet had when power was lost. If the state was ON, should sequence back ON in line with outletControlSequenceTime.
1.3.6.1.4.1.19536.10.1.5.2.1.5INTEGER {off(1), on(2), lastState(3)}read-writecurrent
pdug5OutletControlSequenceDelay
OBJECT-TYPE
Time delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on delay.
1.3.6.1.4.1.19536.10.1.5.2.1.6Integer32 (-1..7200)read-writecurrent
pdug5OutletControlRebootOffTime
OBJECT-TYPE
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
1.3.6.1.4.1.19536.10.1.5.2.1.7Integer32 (5..60)read-writecurrent
pdug5OutletControlSwitchable
OBJECT-TYPE
Determines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled.
1.3.6.1.4.1.19536.10.1.5.2.1.8INTEGER {switchable(1), notSwitchable(2)}read-writecurrent
pdug5OutletControlShutoffDelay
OBJECT-TYPE
Time delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this parameter first then write it to the command pdug5OutletControlOffCmd.
1.3.6.1.4.1.19536.10.1.5.2.1.9Integer32 (-1..7200)read-writecurrent
pdug5OutletControlCommand
OBJECT-TYPE
Getting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (1) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (7) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (1) will immediately turn the outlet off. Setting this variable to immediateReboot (5) will cause the Switched PDU to perform an immediateOff command, wait the pdug5OutletControlRebootOffTime OID time, and then perform an immediateOn command. Setting this variable to delayedOn (4) will turn the outlet on after the pdug5OutletControlSequenceDelay OID time has elapsed. Setting this variable to delayedOff (3) will turn the outlet off after the pdug5OutletControlShutoffDelay OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched PDU to perform a delayedOff command, wait the pdug5OutletControlRebootOffTime OID time, and then perform a delayedOn command.
1.3.6.1.4.1.19536.10.1.5.2.1.10INTEGER {immediateOff(1), immediateOn(2), delayedOff(3), delayedOn(4), immediateReboot(5), delayedReboot(6), outletUnknown(7)}read-writecurrent
pdug5Traps
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.6
pdug5TrapInfo
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.7
pdug5TrapInfoEntry
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.7.1
trapCode
OBJECT-TYPE
A number identifying the event for the trap that was sent.
1.3.6.1.4.1.19536.10.1.7.1.1Integer32read-onlycurrent
trapDescription
OBJECT-TYPE
A string identifying the event for that last trap that was sent.
1.3.6.1.4.1.19536.10.1.7.1.2DisplayString (SIZE(0..255))read-onlycurrent
pdug5Conformance
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.8
pdug5Compliances
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.8.1
pdug5Groups
OBJECT-IDENTITY
1.3.6.1.4.1.19536.10.1.8.2

Notifications

NameOIDStatus
trapCritical
NOTIFICATION-TYPE
A critical alarm has occurred.
1.3.6.1.4.1.19536.10.1.6.1current
trapWarning
NOTIFICATION-TYPE
A warning alarm has occurred.
1.3.6.1.4.1.19536.10.1.6.2current
trapInformation
NOTIFICATION-TYPE
An informational alarm has occurred.
1.3.6.1.4.1.19536.10.1.6.3current
trapCleared
NOTIFICATION-TYPE
An alarm has cleared.
1.3.6.1.4.1.19536.10.1.6.4current
trapTest
NOTIFICATION-TYPE
Test trap sent to a trap receiver to check proper reception of traps
1.3.6.1.4.1.19536.10.1.6.5current

Conformance

NameOIDStatus
pdug5FullCompliance
MODULE-COMPLIANCE
Compliance statement
1.3.6.1.4.1.19536.10.1.8.1.1current
pdug5IdentGroup
OBJECT-GROUP
the pdug5Identity defines objects which aid PDU system level configuration
1.3.6.1.4.1.19536.10.1.8.2.1current
pdug5InputGroup
OBJECT-GROUP
the pdug5InputGroup defines objects which aid Input level configuration and monitoring
1.3.6.1.4.1.19536.10.1.8.2.2current
pdug5GroupGroup
OBJECT-GROUP
the pdug5GroupGroup defines objects which aid Breaker level configuration and monitoring
1.3.6.1.4.1.19536.10.1.8.2.3current
pdug5EnvironmentGroup
OBJECT-GROUP
the pdug5Environmental defines objects which aid Environmental level configuration and monitoring
1.3.6.1.4.1.19536.10.1.8.2.4current
pdug5OutletGroup
OBJECT-GROUP
the pdug5OutletGroup defines objects which aid Outlet level configuration and monitoring
1.3.6.1.4.1.19536.10.1.8.2.5current
pdug5TrapGroup
NOTIFICATION-GROUP
the pdug5TrapGroup defines Traps.
1.3.6.1.4.1.19536.10.1.8.2.6current
pdug5TrapInfoGroup
OBJECT-GROUP
the pdug5TrapInfoGroup defines Traps Information.
1.3.6.1.4.1.19536.10.1.8.2.7current