ORION-BASE-MIB
- Registered at
- 1.3.6.1.4.1.20246.2.1.1.21.3.6.1.4.1.20246.2.3.1.1.1
- Last updated
- 2008-02-21 14:39
- Organization
- Delta Energy Systems (Switzerland) AG
- Revisions
- 2012-04-27 12:00, 2012-01-26 14:15, 2011-06-20 07:34, 2011-02-10 09:01, 2010-06-16 10:27, 2010-02-24 10:46, 2009-09-04 09:52, 2008-02-21 14:39, 2008-01-18 08:35, 2006-07-27 10:26, 2006-03-02 08:55, 2006-02-23 09:32, 2005-06-03 11:07
- Namespace
- delta
- Source file
ORION-BASE-MIB- Digest
sha256:a073e2d78f71bec0b56e80fd308b41d5706861cd7b586b723adda8fec9d2dd2a
Description
MIB for managing a DC power system with PSC 3.
Contact
postal: Delta Energy Systems (Switzerland) AG Freiburgstrasse 251, CH-3018 Bern-Buempliz web: www.deltapowersolutions.com email: patrick.camina@delta-es.com
Imports
| From | Symbols |
|---|---|
| GLOBAL-REG | modules, orion |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-SMI | Gauge32, Integer32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
GLOBAL-REG ORION-BASE-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| orionBaseMib OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1 | |||
| controllerConfs OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.1 | |||
| controllerGroups OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1 | |||
| controllerCompl OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.1.2 | |||
| controllerObjects OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2 | |||
| dcSystemInfo OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1 | |||
| dcSiteName OBJECT-TYPE An administratively-assigned site name for this DC-power system. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1 | DisplayString (SIZE(0..16)) | read-write | current |
| dcSystemName OBJECT-TYPE An administratively-assigned system name for this DC-power system. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2 | DisplayString (SIZE(0..16)) | read-write | current |
| dcSystemDateTime OBJECT-TYPE ISO 8601 representation of controller´s local date/time. The value is in the format YYYY-MM-DDThh:mm:ss. An example of a valid string is: '2004-10-04T13:45:00'. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3 | DisplayString (SIZE(19)) | read-write | current |
| dcSoftwareVersion OBJECT-TYPE The controller´s software version e.g V2.50Build1. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4 | DisplayString (SIZE(10..12)) | read-only | current |
| dcSystemAlarms OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2 | |||
| dcEventHistoryTable OBJECT-TYPE Controller´s event history table that shows the content of the default log file. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1 | not-accessible | current | |
| dcEventHistoryEntry OBJECT-TYPE A particular Event History entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1 | not-accessible | current | |
| dcEventHistoryIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1 | Integer32 (1..10000) | not-accessible | current |
| dcEventHistoryTimestamp OBJECT-TYPE ISO8601 timestamp representation of a particular entry in the form YYYY-MM-DDThh:mm:ss. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2 | DisplayString (SIZE(19)) | read-only | current |
| dcEventHistoryMessage OBJECT-TYPE Event message of a particular entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3 | DisplayString (SIZE(1..255)) | read-only | current |
| dcAlarmTable OBJECT-TYPE Table that shows all currently active alarm sources causing urgent or non-urgent alarm(s). | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2 | not-accessible | current | |
| dcAlarmEntry OBJECT-TYPE A particular active alarm source entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1 | not-accessible | current | |
| dcAlarmIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1 | Integer32 (1..16) | not-accessible | current |
| dcAlarmEventCategory OBJECT-TYPE Specifies the type of alarm source. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2 | INTEGER {unknown(1), urgent(2), nonUrgent(3), critical(4)} | read-only | current |
| dcAlarmEventName OBJECT-TYPE Name of a particular alarm source entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3 | DisplayString (SIZE(1..35)) | read-only | current |
| dcAlarmEventIdentifier OBJECT-TYPE Unique alarm event identifier. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4 | Gauge32 | read-only | current |
| dcAlarmEventValue OBJECT-TYPE Event status that corresponds to alarm event identifier. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5 | INTEGER {false(1), true(3)} | read-only | current |
| dcNumberUrgentAlarms OBJECT-TYPE Number of currently active urgent alarm sources. A zero value indicates that urgent alarm is not active. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3 | Gauge32 | read-only | current |
| dcNumberNonUrgentAlarms OBJECT-TYPE Number of currently active non urgent alarm sources. A zero value indicates that non urgent alarm is not active. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4 | Gauge32 | read-only | current |
| dcMainsFailureAlarm OBJECT-TYPE Mains failure alarm. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5 | INTEGER {inactive(1), active(2)} | read-only | current |
| dcUrgentAlarmIdentifier OBJECT-TYPE Current unique urgent alarm event identifier. A zero value indicates that urgent alarm is not active. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6 | Gauge32 | read-only | current |
| dcUrgentAlarmValue OBJECT-TYPE Current urgent alarm event status that corresponds to the urgent alarm identifier. If the urgent alarm identifier is zero then the alarm value is false. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7 | INTEGER {false(1), indeterminate(2), true(3)} | read-only | current |
| dcNonUrgentAlarmIdentifier OBJECT-TYPE Current unique non urgent alarm event identifier. A zero value indicates that non urgent alarm is not active. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8 | Gauge32 | read-only | current |
| dcNonUrgentAlarmValue OBJECT-TYPE Current non urgent alarm event status that corresponds to non urgent alarm identifier. If the non urgent alarm identifier is zero then the alarm value is false. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9 | INTEGER {false(1), indeterminate(2), true(3)} | read-only | current |
| dcUrgentAlarmName OBJECT-TYPE Current alarm name for urgent alarm that corresponds to urgent alarm identifier. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10 | DisplayString (SIZE(0..35)) | read-only | current |
| dcNonUrgentAlarmName OBJECT-TYPE Current alarm name for active non urgent alarm that corresponds to non urgent alarm identifier. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11 | DisplayString (SIZE(0..35)) | read-only | current |
| dcGenericAlarmTable OBJECT-TYPE Table that shows ten alarm event assignments that can be configured via WEB interface. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12 | not-accessible | current | |
| dcGenericAlarmEntry OBJECT-TYPE A particular generic alarm entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1 | not-accessible | current | |
| dcGenericAlarmIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1 | Integer32 (1..16) | not-accessible | current |
| dcGenericAlarmEventName OBJECT-TYPE Plain text name of the assigned alarm event. Empty if not configured. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2 | DisplayString (SIZE(0..35)) | read-only | current |
| dcGenericAlarmEventIdentifier OBJECT-TYPE Unique numeric identifier of the assigned alarm event. Zero if not configured. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3 | Gauge32 | read-only | current |
| dcGenericAlarmEventValue OBJECT-TYPE Current value of the assigned alarm event. Value is false if not configured. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4 | INTEGER {false(1), true(2)} | read-only | current |
| dcNumberCriticalAlarms OBJECT-TYPE Number of currently active critical alarm sources. A zero value indicates that critical alarm is not active. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.13 | Gauge32 | read-only | current |
| dcCriticalAlarmIdentifier OBJECT-TYPE Current unique critical alarm event identifier. A zero value indicates that critical alarm is not active. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.14 | Gauge32 | read-only | current |
| dcCriticalAlarmValue OBJECT-TYPE Current critical alarm event status that corresponds to the critical alarm identifier. If the critical alarm identifier is zero then the alarm value is false. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.15 | INTEGER {false(1), indeterminate(2), true(3)} | read-only | current |
| dcCriticalAlarmName OBJECT-TYPE Current alarm name for active critical alarm that corresponds to critical alarm identifier. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.16 | DisplayString (SIZE(0..35)) | read-only | current |
| dcSystemMonitor OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3 | |||
| dcSystemVoltage OBJECT-TYPE The measured system voltage. The max. value 2147483647 is used to indicate an invalid value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1 | Integer32 | read-only | current |
| dcLoadCurrent OBJECT-TYPE The measured load current. The max. value 2147483647 is used to indicate an invalid value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2 | Integer32 | read-only | current |
| dcBatteryCurrent OBJECT-TYPE The measured battery current. The max. value 2147483647 is used to indicate an invalid value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3 | Integer32 | read-only | current |
| dcBatteryTemperature OBJECT-TYPE The measured battery temperature. The max. value 2147483647 is used to indicate an invalid value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4 | Integer32 | read-only | current |
| dcChargeState OBJECT-TYPE Battery charge state. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5 | INTEGER {float(1), discharge(2), equalize(3), boost(4), battTest(5), recharge(6), sepCharge(7), evCtrlCharge(8)} | read-only | current |
| dcCurrentLimit OBJECT-TYPE Battery current limit. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6 | INTEGER {inactive(1), active(2)} | read-only | current |
| dcRectifierCurrent OBJECT-TYPE Total current of all working rectifier modules. The maximum value 2147483647 is used to indicate an invalid value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7 | Integer32 | read-only | current |
| dcSystemPower OBJECT-TYPE Calculated system power. The maximum value 2147483647 is used to indicate an invalid value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8 | Integer32 | read-only | current |
| dcRectifier OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4 | |||
| dcNumberRectifiers OBJECT-TYPE The configured number of rectifiers plugged into the system. The maximum number of rectifiersi is 128. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1 | Gauge32 (0..128) | read-only | current |
| dcNumberRectifiersFailure OBJECT-TYPE Number of rectifiers that are not properly working. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2 | Gauge32 (0..128) | read-only | current |
| dcNumberRectifiersOkay OBJECT-TYPE Number of rectifiers that are properly working. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3 | Gauge32 (0..128) | read-only | current |
| dcRectifierTable OBJECT-TYPE Table that shows all currently active rectifier modules. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4 | not-accessible | current | |
| dcRectifierEntry OBJECT-TYPE A particular rectifier entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1 | not-accessible | current | |
| dcRectifierIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1 | Integer32 (1..128) | not-accessible | current |
| dcRectifierIdentifier OBJECT-TYPE Unique rectifier identifier. If positioning active the position number scheme is used otherwise the rectifier instance is used to identify a rectifier. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2 | DisplayString (SIZE(1..16)) | read-only | current |
| dcRectifierStatus OBJECT-TYPE Specifies status of rectifiers. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3 | INTEGER {unknown(1), off(2), on(3)} | read-only | current |
| dcRectifierGroupTable OBJECT-TYPE Table that shows all available rectifier groups. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5 | not-accessible | current | |
| dcRectifierGroupEntry OBJECT-TYPE A particular rectifier group entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1 | not-accessible | current | |
| dcRectifierGroupIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.1 | Integer32 (1) | not-accessible | current |
| dcRectifierGroupName OBJECT-TYPE Rectifier group name to identify an individual device parameter set. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.2 | DisplayString (SIZE(1..16)) | read-only | current |
| dcRectifierGroupRectifierType OBJECT-TYPE Rectifier type defined for this group. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.3 | INTEGER {unknown48V(1), fR48V2000W(2), dPR1200B48(3), dPR1500B48(4), dPR600B48(5), dPR7200B48(6), fR48to60V2000W(7), unknown24V(8), unknown60V(9), dPR600B60(10), dPR3500B48(11), dPR3500B24(12), dPR300B48(13), dPR1600B48(14), dPR2700B48(15), dPR2400B48(16), dPR4000B48(17), dPR2900B48(18), dPR4000B48to60(19), dPR850B48(20), dPR2000B48(21)} | read-only | current |
| dcRectifierGroupDefaultVoltage OBJECT-TYPE This default voltage is used by rectifiers when there is no connection to PSC 3. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.4 | Integer32 | read-write | current |
| dcRectifierGroupDefaultCurrentLimit OBJECT-TYPE This default current limit is used by rectifiers when there is no connection to PSC 3. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.5 | Integer32 | read-write | current |
| dcRectifierGroupDefaultPowerLimit OBJECT-TYPE This default power limit is used by rectifiers when there is no connection to PSC 3. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.6 | Integer32 | read-write | current |
| dcRectifierGroupInputLowOff OBJECT-TYPE Threshold for low AC input voltage. It can is used to adjust the behaviour of the power system to the available AC network limitation. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.7 | Integer32 | read-write | current |
| dcRectifierGroupInputLowOn OBJECT-TYPE For details see dcRectifierGroupInputLowOff. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.8 | Integer32 | read-write | current |
| dcRectifierGroupStartupVoltage OBJECT-TYPE Startup parameters are the values that rectifiers use during the start-up phase. These parameters allow starting the system smoothly after a mains failure even on a discharged battery and even without PSC 3. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.9 | Integer32 | read-write | current |
| dcRectifierGroupStartupCurrentLimit OBJECT-TYPE For details see dcRectifierGroupStartupVoltage. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.10 | Integer32 | read-write | current |
| dcRectifierGroupStartupPowerLimit OBJECT-TYPE For details see dcRectifierGroupStartupVoltage. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.11 | Integer32 | read-write | current |
| dcRectifierGroupStartupTimeLimit OBJECT-TYPE For details see dcRectifierGroupStartupVoltage. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.12 | Gauge32 | read-write | current |
| dcRectifierGroupPowerupDelay OBJECT-TYPE This parameter is used after a mains failure to delay the start-up of all rectifiers. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.13 | Gauge32 | read-write | current |
| dcRectifierGroupPowerupTime OBJECT-TYPE This parameter used after a mains failure and allows defining a time within all rectifiers needs to start-up one after another. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.14 | Gauge32 | read-write | current |
| dcRectifierGroupUmaxOff OBJECT-TYPE Overvoltage protection value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.15 | Integer32 | read-write | current |
| dcRectifierFunctions OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6 | |||
| dcEfficiencyCycling OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1 | |||
| dcEfficiencyCyclingEnabled OBJECT-TYPE Enable/disable efficiency cycling. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.1 | INTEGER {no(1), yes(2)} | read-write | current |
| dcLimitSwitchingTimes OBJECT-TYPE Enable/disable limit switching times. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.2 | INTEGER {no(1), yes(2)} | read-write | current |
| dcForceSwitchingOncePerMonth OBJECT-TYPE Enable/disable force switching once per month. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.3 | INTEGER {no(1), yes(2)} | read-write | current |
| dcMaximumLoadStep OBJECT-TYPE Maximum load setup. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.4 | Integer32 | read-write | current |
| dcMinimumLoadStep OBJECT-TYPE Minimum load setup. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.5 | Integer32 | read-write | current |
| dcPowerLimitation OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2 | |||
| dcPowerLimitationTable OBJECT-TYPE Table that shows parameters of the available power limitation functions. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1 | not-accessible | current | |
| dcPowerLimitationEntry OBJECT-TYPE A particular power limitation entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1 | not-accessible | current | |
| dcPowerLimitationIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.1 | Integer32 (1..16) | not-accessible | current |
| dcPowerLimitationEventName OBJECT-TYPE Name of the power limitation event. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.2 | DisplayString (SIZE(1..35)) | read-only | current |
| dcPowerLimitationStatus OBJECT-TYPE Status of power limitation. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.3 | INTEGER {disabled(1), inactive(2), powerLimit(3)} | read-only | current |
| dcPowerLimitationType OBJECT-TYPE Power limitation type. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.4 | INTEGER {dynamic(1), fixedLimit(2)} | read-only | current |
| dcPowerLimitationLimit OBJECT-TYPE Limit used for power limitation. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.5 | Integer32 | read-write | current |
| dcPowerLimitationNoBatteryDischarge OBJECT-TYPE Enable/disable no battery discharge during power limitation. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.6 | INTEGER {no(1), yes(2)} | read-write | current |
| dcBattery OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5 | |||
| dcFloatCharge OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1 | |||
| dcUsys20 OBJECT-TYPE Voltage to regulate to at 20°C. If temperature compensation is used, this voltage will vary. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1 | Integer32 | read-write | current |
| dcBatteryTest OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2 | |||
| dcBatteryTestParameter OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1 | |||
| dcBatteryTestUsupport OBJECT-TYPE Support charge voltage for the battery. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1 | Integer32 | read-write | current |
| dcBatteryTestDuration OBJECT-TYPE Battery test duration. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2 | Gauge32 | read-write | current |
| dcBatteryTestInterval OBJECT-TYPE Minimal time between programmed battery tests as start condition. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3 | Gauge32 | read-write | current |
| dcBatteryTestDischargeCurrent OBJECT-TYPE Battery discharge current. The maximum value 2147483647 is used to indicate an invalid value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4 | Integer32 | read-write | current |
| dcBatteryTestMinDuration OBJECT-TYPE Minimum battery test duration during which time a battery test is not stopped in case of a voltage below the support voltage or a current difference higher than the specified value defined in Idiff measurement is detected. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5 | Gauge32 | read-write | current |
| dcBatteryTestVoltageWithinUfloat OBJECT-TYPE Battery voltage must be within Ufloat +/- set voltage for a given time (see also dcBatteryTestVoltageWithinUfloatPeriod) in order to start a battery test. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.6 | Integer32 | read-write | current |
| dcBatteryTestVoltageWithinUfloatPeriod OBJECT-TYPE For details see dcBatteryTestVoltageWithinUfloat parameter. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.7 | Gauge32 | read-write | current |
| dcBatteryTestTempFrom OBJECT-TYPE Battery temperature must be within temperature range given by dcBatteryTestTempFrom and dcBatteryTestTempTo, so that a battery test can be started. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.8 | Integer32 | read-write | current |
| dcBatteryTestTempTo OBJECT-TYPE For details see dcBatteryTestTempFrom parameter. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.9 | Integer32 | read-write | current |
| dcBatteryTestIntervalEnabled OBJECT-TYPE Enable/disable interval. For more details see dcBatteryTestInterval. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.10 | INTEGER {no(1), yes(2)} | read-write | current |
| dcBatteryTestStartTimeFrom OBJECT-TYPE Defines start time window for battery test. The possible time window is defined as the range between dcBatteryTestStartTimeFrom and dcBatteryTestStartTimeTo. The value is in the format 'hh:mm:ss'. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.11 | DisplayString (SIZE(8)) | read-write | current |
| dcBatteryTestStartTimeTo OBJECT-TYPE For details see dcBatteryTestStartTimeFrom. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.12 | DisplayString (SIZE(8)) | read-write | current |
| dcBatteryTestResults OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2 | |||
| dcBatteryTestDateTime OBJECT-TYPE ISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test result available. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1 | DisplayString (SIZE(19)) | read-only | current |
| dcBatteryTestResult OBJECT-TYPE Result of last performed battery test. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2 | INTEGER {none(1), failed(2), aborted(3), loadFailure(4), okay(5), abortedManual(6), abortedEvCtrlCharge(7), abortedInhibitEv(8)} | read-only | current |
| dcBatteryTestEndVoltage OBJECT-TYPE System voltage at the end of the last performed battery test. The maximum value 2147483647 is used to indicate an invalid value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3 | Integer32 | read-only | current |
| dcBatteryTestControl OBJECT-TYPE Start/stop of battery test. This special charge mode is used to check the capacity of a battery. Please note that a battery test can be started even if the battery is not fully charged. In this case the test result is ambiguous and the set failure event will become active. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3 | INTEGER {start(1), stop(2)} | read-write | current |
| dcBatteryTestStatus OBJECT-TYPE Status of battery test. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4 | INTEGER {inactive(1), starting(2), stopping(3), constantCurrent(4), timeBased(5), energyBased(6), recovery(7), realLoad(8), stop(9)} | read-only | current |
| dcBatteryTestFailureEvent OBJECT-TYPE Reset battery test failure event. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5 | INTEGER {reset(1)} | read-write | current |
| dcBatteryTestType OBJECT-TYPE Battery test type used. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.6 | INTEGER {none(1), constantCurrent(2), realLoad(5)} | read-write | current |
| dcBatteryParameter OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3 | |||
| dcTotalBatteryCapacity OBJECT-TYPE Total battery capacity for all available batteries. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1 | Gauge32 | read-only | current |
| dcBatteryStringTable OBJECT-TYPE Table that shows parameters of the available battery strings. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2 | not-accessible | current | |
| dcBatteryStringEntry OBJECT-TYPE A particular battery string entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1 | not-accessible | current | |
| dcBatteryStringIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.1 | Integer32 (1..16) | not-accessible | current |
| dcBatteryStringName OBJECT-TYPE Name of the battery string. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.2 | DisplayString (SIZE(1..16)) | read-only | current |
| dcBatteryStringMaxIBatt OBJECT-TYPE Maximum battery charging current for this string. This parameter can be set individually for each battery. PSC 3 then regulates the system voltage such that the maximum battery charging current of each battery is respected. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.3 | Integer32 | read-write | current |
| dcBatteryStringCapacity OBJECT-TYPE Capacity of battery can be defined individually. It is used to calculate the expected backup time of the system. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.4 | Gauge32 | read-write | current |
| dcLossOfBackupTime OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3 | |||
| dcLossOfBackupTimeEnabled OBJECT-TYPE Enable/disable loss of backup time functionality. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.1 | INTEGER {no(1), yes(2)} | read-write | current |
| dcLossOfBackupTimeStatus OBJECT-TYPE Status of loss of backup time functionality. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.2 | INTEGER {inactive(1), ok(2), occured(3), fail(4)} | read-only | current |
| dcExpectedBackupTime OBJECT-TYPE Expected backup time value. Based on the given value for the parameter expected backup time, the corresponding maximum discharge current is calculated. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.3 | Gauge32 | read-write | current |
| dcEqualize OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4 | |||
| dcEqualizeControl OBJECT-TYPE Start/stop of battery equalize which is a special charge mode that applies a higher voltage to the batteries than the float charge. This ensures that the cells are all equally charged. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1 | INTEGER {start(1), stop(2)} | read-write | current |
| dcEqualizeStatus OBJECT-TYPE Current status of battery equalize. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2 | INTEGER {inactive(1), starting(2), stopping(3), preparing(4), cooking(5), recovering(6)} | read-only | current |
| dcEqualizeEnabled OBJECT-TYPE Enable/disable equalize. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.3 | INTEGER {no(1), yes(2)} | read-write | current |
| dcEqualizeParameter OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4 | |||
| dcEqualizeVoltage OBJECT-TYPE Voltage used for equalize. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.1 | Integer32 | read-write | current |
| dcEqualizeDuration OBJECT-TYPE Duration of equalize. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.2 | Gauge32 | read-write | current |
| dcEqualizeUseBattRoomFanEnabled OBJECT-TYPE Enable/disable battery room fan during equalize. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.3 | INTEGER {no(1), yes(2)} | read-write | current |
| dcEqualizeLeadTime OBJECT-TYPE Lead time for equalize. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.4 | Gauge32 | read-write | current |
| dcEqualizeTimeLag OBJECT-TYPE Time lag for equalize. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.5 | Gauge32 | read-write | current |
| dcEqualizeInterval OBJECT-TYPE Interval for equalize as start condition. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.6 | Gauge32 | read-write | current |
| dcEqualizeStartTimeIntervalFrom OBJECT-TYPE Defines start time window for equqlize. The possible time window is defined as the range between dcEqualizeStartTimeIntervalFrom and dcEqualizeStartTimeIntervalTo. The value is in the format 'hh:mm:ss'. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.7 | DisplayString (SIZE(8)) | read-write | current |
| dcEqualizeStartTimeIntervalTo OBJECT-TYPE For detail see dcEqualizeStartTimeIntervalFrom. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.8 | DisplayString (SIZE(8)) | read-write | current |
| dcEqualizeInhibitAfterBoost OBJECT-TYPE Inhibit after boost as start condition. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.9 | Gauge32 | read-write | current |
| dcBoostCharge OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5 | |||
| dcBoostChargeControl OBJECT-TYPE Start/stop of boost charge which is a special charge mode that applies a higher voltage to the batteries than the float charge. This mode is started after a discharge phase to recharge the batteries faster. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1 | INTEGER {start(1), stop(2)} | read-write | current |
| dcBoostChargeStatus OBJECT-TYPE Current status of boost charge. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2 | INTEGER {inactive(1), starting(2), stopping(3), cooking(4), recovering(5)} | read-only | current |
| dcBoostChargeType OBJECT-TYPE Boost charge type. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.3 | INTEGER {none(1), currentBased(2), timeBased(3), energyBased(4)} | read-write | current |
| dcBoostChargeParameter OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4 | |||
| dcBoostChargeVoltage OBJECT-TYPE Voltage used for boost charge. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.1 | Integer32 | read-write | current |
| dcBoostChargeMaxDuration OBJECT-TYPE Defines the maximum allowed time for boost charge to prevent that the battery is charged forever. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.2 | Gauge32 | read-write | current |
| dcBoostChargeUseBattRoomFanEnabled OBJECT-TYPE Enable/disable battery room fan during boost charge. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.3 | INTEGER {no(1), yes(2)} | read-write | current |
| dcBoostChargeTimeLag OBJECT-TYPE Time lag used for boost charge. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.4 | Gauge32 | read-write | current |
| dcBoostChargeIstart OBJECT-TYPE For current based boost charge, the parameters Istart and Istop are the battery current values at which boost charge starts or stops. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.5 | Integer32 | read-write | current |
| dcBoostChargeIstop OBJECT-TYPE For details see dcBoostChargeIstart. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.6 | Integer32 | read-write | current |
| dcBoostChargeInhibitTime OBJECT-TYPE A start condition for all types of boost charge. It defines the time from last boost charge stop to the next acceptable boost charge start. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.7 | Gauge32 | read-write | current |
| dcSystemVoltageSupervision OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6 | |||
| dcUaMax OBJECT-TYPE If the system voltage is outside the range specified by the values UaMin (lower alarm voltage)/UaMax (upper alarm voltage), the system event 'S Ua low'/'S Ua high' is activated. The values for the parameters UaMin and UaMax are not temperature compensated. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.1 | Integer32 | read-write | current |
| dcUaMin OBJECT-TYPE For details see dcUaMax. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.2 | Integer32 | read-write | current |
| dcUsMax OBJECT-TYPE If the voltage is outside the range defined by the parameters UsMin (lower safety voltage)/UsMax (upper safety voltage), the system event 'S Us low'/'S Us high' is activated. If temperature compensation is enabled, the levels for Us min and / Us max are automatically temperature compensated to correspond to the required system voltage. The parameters are defined at 20°C. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.3 | Integer32 | read-write | current |
| dcUsMin OBJECT-TYPE For details see dcUsMax. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.4 | Integer32 | read-write | current |
| dcBoD OBJECT-TYPE Voltage threshold for Battery on Discharge alarm. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.5 | Integer32 | read-write | current |
| dcHysteresis OBJECT-TYPE Hysteresis used for Ua and Us. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.6 | Integer32 | read-write | current |
| dcSuppressUaLowEnabled OBJECT-TYPE Suppress Ua Low alarm during mains failure. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.7 | INTEGER {no(1), yes(2)} | read-write | current |
| dcSuppressUsLowEnabled OBJECT-TYPE Suppress Us Low alarm during mains failure. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.8 | INTEGER {no(1), yes(2)} | read-write | current |
| dcEnableUsTempComp OBJECT-TYPE Checkbox to enable the automatic temperature compensation for the Us thresholds (Us min, Us max). | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.9 | INTEGER {no(1), yes(2)} | read-write | current |
| dcEvtCtrlCharge OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7 | |||
| dcEvtCtrlChargeStatus OBJECT-TYPE Event control charge status. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1 | INTEGER {inactive(1), voltageControlled(2), noBatteryCharge(3), currentLimitation(4)} | read-only | current |
| dcEvtCtrlChargeType OBJECT-TYPE Selected event control charge type. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.2 | INTEGER {none(1), voltageControlled(2), noBatteryCharge(3), currentLimitation(4)} | read-write | current |
| dcEvtCtrlChargeParameter OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3 | |||
| dcEvtCtrlChargeVoltage OBJECT-TYPE Voltage used for event control charge. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.1 | Integer32 | read-write | current |
| dcEvtCtrlChargeTempCompEnabled OBJECT-TYPE Enable/disable temperature compensation during event control charge. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.2 | INTEGER {no(1), yes(2)} | read-write | current |
| dcEvtCtrlChargeMaxIBatt OBJECT-TYPE Max. IBatt used for event control charge. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.3 | Integer32 | read-write | current |
| dcTempComp OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8 | |||
| dcTempCompType OBJECT-TYPE Enable/disable battery temperature compensation. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.1 | INTEGER {no(1), linear(2), multi-stage(3)} | read-write | current |
| dcSlope OBJECT-TYPE Temperature compensation coefficient for system voltage. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.2 | Integer32 | read-write | current |
| dcStartTemp OBJECT-TYPE Lower limit for the area in which the temperature compensation is active. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.3 | Integer32 | read-write | current |
| dcStopTemp OBJECT-TYPE Upper limit for the area in which the temperature compensation is active. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.4 | Integer32 | read-write | current |
| dcMaxVoltage OBJECT-TYPE Upper limit for the area in which the temperature compensation is not controlling the system voltage. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.5 | Integer32 | read-write | current |
| dcLowStopVoltage OBJECT-TYPE The temperature compensation will not control the charging voltage above this parameter at low temperatures. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.6 | Integer32 | read-write | current |
| dcLowStartTemp OBJECT-TYPE High temperature limit of the lower range. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.7 | Integer32 | read-write | current |
| dcLowTempSlope OBJECT-TYPE Compensation factor applied inside the low range. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.8 | Integer32 | read-write | current |
| dcHighStartTemp OBJECT-TYPE The low temperature limit of the higher range. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.9 | Integer32 | read-write | current |
| dcHighTempSlope OBJECT-TYPE Compensation factor applied inside the high range. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.10 | Integer32 | read-write | current |
| dcHighStopVoltage OBJECT-TYPE The temperature compensation will not control the charging voltage below this parameter at high temperatures. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.11 | Integer32 | read-write | current |
| dcRunawayTemp OBJECT-TYPE A threshold for detecting thermal runaway of the battery. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.12 | Integer32 | read-write | current |
| dcRunawayVoltage OBJECT-TYPE Charging voltage while Runaway Temp has been exceeded. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13 | Integer32 | read-write | current |
| dcTempSupervision OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9 | |||
| dcHighTemp OBJECT-TYPE Temperature threshold for high battery temperature alarm 10°C ... 70°C | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.1 | Integer32 | read-write | current |
| dcHighTempHyst OBJECT-TYPE Hysteresis for the High Temp 1°C ... 70°C | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.2 | Integer32 | read-write | current |
| dcInputOutput OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6 | |||
| dcControlEventTable OBJECT-TYPE Table that shows ten output event assignments that can be configured via WEB interface. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1 | not-accessible | current | |
| dcControlEventEntry OBJECT-TYPE A particular generic output entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1 | not-accessible | current | |
| dcControlEventIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1 | Integer32 (1..16) | not-accessible | current |
| dcControlEventName OBJECT-TYPE Plain text name of the assigned control event. Empty if not configure. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2 | DisplayString (SIZE(0..35)) | read-only | current |
| dcControlEventIdentifier OBJECT-TYPE Unique numeric identifier of the assigned control event. Zero if not configured. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3 | Gauge32 | read-only | current |
| dcControlEventValue OBJECT-TYPE Current value of the assigned control event. Value is false if not configured. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4 | INTEGER {false(1), true(2)} | read-write | current |
| dcMisc OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7 | |||
| dcTrapDestinationTable OBJECT-TYPE Trap table that shows all configured trap destinations. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1 | not-accessible | current | |
| dcTrapDestinationEntry OBJECT-TYPE A particular trap destination entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1 | not-accessible | current | |
| dcTrapDestinationIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1 | Integer32 (1..10) | not-accessible | current |
| dcTrapDestinationIp OBJECT-TYPE IP address of the trap destination. Value is 0.0.0.0 if IP address is not configured. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2 | IpAddress | read-write | current |
| dcTrapDestinationPort OBJECT-TYPE Port number of the trap destination. By default port 162 is used. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3 | Gauge32 | read-write | current |
| dcFileProcessingStatus OBJECT-TYPE File processing status for software and setup up/downloads. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2 | INTEGER {idle(1), inProgress(2), successful(3), error(4), unknown(5)} | read-only | current |
| dcResendActiveAlarmTraps OBJECT-TYPE Resend all active Urgent, Non Urgent, and Critical Alarm Traps. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.4 | INTEGER {resend(1)} | read-write | current |
| dcConfig OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8 | |||
| dcDefaultLogEventTable OBJECT-TYPE Event config table for default log. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1 | not-accessible | current | |
| dcDefaultLogEventEntry OBJECT-TYPE A particular event entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1 | not-accessible | current | |
| dcDefaultLogEventIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.1 | Integer32 (0..1000) | not-accessible | current |
| dcDefaultLogEventName OBJECT-TYPE Plain text name of the event that can be logged. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.2 | DisplayString (SIZE(1..35)) | read-only | current |
| dcDefaultLogEventLogged OBJECT-TYPE If yes then this event is logged otherwise not. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.3 | INTEGER {no(1), yes(2)} | read-write | current |
| dcEventProcessingEventTable OBJECT-TYPE Event config table for event ORs. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2 | not-accessible | current | |
| dcEventProcessingEventEntry OBJECT-TYPE A particular event entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1 | not-accessible | current | |
| dcEventProcessingEventIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.1 | Integer32 (0..1000) | not-accessible | current |
| dcEventProcessingEventName OBJECT-TYPE Plain text name of the input event. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.2 | DisplayString (SIZE(1..35)) | read-only | current |
| dcEventProcessingEventAssigned OBJECT-TYPE If yes then the input event is assigned to the selected event. Please note, that it is only possible to change assignment of event ORs. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.3 | INTEGER {no(1), yes(2)} | read-write | current |
| dcEventProcessingEventType OBJECT-TYPE Type of the input event. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.4 | INTEGER {unknown(1), eventOR(2)} | read-only | current |
| dcEventProcessingEventSelected OBJECT-TYPE Reference to dcEventProcessingEventIndex in order to select a specific event. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.3 | Gauge32 | read-write | current |
| dcLvdTable OBJECT-TYPE Table lists all available LVDs. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4 | not-accessible | current | |
| dcLvdEntry OBJECT-TYPE A particular LVD entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1 | not-accessible | current | |
| dcLvdIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.1 | Integer32 (1..96) | not-accessible | current |
| dcLvdName OBJECT-TYPE Name of the LVD. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.2 | DisplayString (SIZE(1..16)) | read-only | current |
| dcLvdDisconnectDelay OBJECT-TYPE Time delay from the activation of the source event, after which the LVD event is switched. The value is in the format 'hh:mm:ss'. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.3 | DisplayString (SIZE(8)) | read-write | current |
| dcMeasurement OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9 | |||
| dcMeasurementTable OBJECT-TYPE Table lists all available measurements. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1 | not-accessible | current | |
| dcMeasurementEntry OBJECT-TYPE A particular measurement entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1 | not-accessible | current | |
| dcMeasurementIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.1 | Integer32 (1..500) | not-accessible | current |
| dcMeasurementName OBJECT-TYPE Name of the measurement. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.2 | DisplayString (SIZE(1..16)) | read-only | current |
| dcMeasurementValue OBJECT-TYPE Unscaled calibrated value of the measurement. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.3 | Integer32 | read-only | current |
| dcMeasurementScaleFactor OBJECT-TYPE Scale factor as power of 10 to be multiplied with measurement value. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.4 | Integer32 | read-only | current |
| dcMeasurementUnit OBJECT-TYPE Unit of the measurement. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.5 | INTEGER {unknown(1), none(2), voltDC(3), voltAC(4), ampere(5), ampereHour(6), degreeCelsius(7), temperatureCoefficient(8), watt(9), wattHour(10), seconds(11), percent(12), hertz(13), voltAmpere(14), voltAmpereReactive(15), voltAmpereReactiveHour(16)} | read-only | current |
| dcMeterPanel OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10 | |||
| dcMeterPanelEventTable OBJECT-TYPE Table lists all available meter panel events. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1 | not-accessible | current | |
| dcMeterPanelEventEntry OBJECT-TYPE A particular meter panel event entry. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1 | not-accessible | current | |
| dcMeterPanelEventIndex OBJECT-TYPE Table index. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.1 | Integer32 (1..128) | not-accessible | current |
| dcMeterPanelEventName OBJECT-TYPE Name of the event. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.2 | DisplayString (SIZE(1..16)) | read-only | current |
| dcMeterPanelEventValue OBJECT-TYPE Value of the event. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.3 | INTEGER {false(1), indeterminate(2), true(3)} | read-only | current |
| dcMeterPanelEventHourMeterValue OBJECT-TYPE Value of the hour meter event. | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.4 | Gauge32 | read-only | current |
| controllerEvents OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.3 | |||
| controllerEventObjects OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1 | |||
| controllerEventsV2 OBJECT-IDENTITY | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0 |
Notifications
| Name | OID | Status |
|---|---|---|
| systemNonUrgentAlarm NOTIFICATION-TYPE The controller reports that one or more elements have changed into none urgent alarm state. | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1 | current |
| systemUrgentAlarm NOTIFICATION-TYPE The controller reports that one or more elements have changed into urgent alarm state. | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2 | current |
| systemCriticalAlarm NOTIFICATION-TYPE The controller reports that one or more elements have changed into critical alarm state. | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.3 | current |
Conformance
| Name | OID | Status |
|---|---|---|
| systemInfoGroup OBJECT-GROUP The collection of system info scalar objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1 | current |
| systemAlarmGroup OBJECT-GROUP The collection of system alarm scalar objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2 | current |
| systemMonitorGroup OBJECT-GROUP The collection of system monitor scalar objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3 | current |
| rectifierGroup OBJECT-GROUP The collection of rectifier scalar objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4 | current |
| eventHistoryTableGroup OBJECT-GROUP The collection of event history table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5 | current |
| alarmTableGroup OBJECT-GROUP The collection of alarm table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6 | current |
| rectifierTableGroup OBJECT-GROUP The collection of rectifier table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7 | current |
| notificationsGroup NOTIFICATION-GROUP The group of all controller notifications. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8 | current |
| genericAlarmTableGroup OBJECT-GROUP Assignment of events to alarm table entries. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9 | current |
| batteryGroup OBJECT-GROUP The collection of battery scalar objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10 | current |
| controlEventTableGroup OBJECT-GROUP Assignment of control events to table entries. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11 | current |
| trapDestinationTableGroup OBJECT-GROUP Trap destionation table. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12 | current |
| miscGroup OBJECT-GROUP The collection of miscellaneous objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13 | current |
| rectifierGroupTableGroup OBJECT-GROUP The collection of rectifier group table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.14 | current |
| batteryStringTableGroup OBJECT-GROUP The collection of battery string table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.15 | current |
| defaultLogEventTableGroup OBJECT-GROUP The collection of default log event table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.16 | current |
| eventProcessingEventTableGroup OBJECT-GROUP The collection of event processing event table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.17 | current |
| lvdTableGroup OBJECT-GROUP The collection of LVD table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.18 | current |
| powerLimitationTableGroup OBJECT-GROUP The collection of power limitation table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.19 | current |
| measurementTableGroup OBJECT-GROUP The collection of measurement table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.20 | current |
| meterPanelEventTableGroup OBJECT-GROUP The collection of meter panel event table objects. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.21 | current |
| controllerBasicCompl MODULE-COMPLIANCE The basic implementation requirements for the controller MIB. | 1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1 | current |