MIBs Depot

ORION-BASE-MIB

Registered at
1.3.6.1.4.1.20246.2.1.1.2
1.3.6.1.4.1.20246.2.3.1.1.1
Last updated
2008-02-21 14:39
Organization
Delta Energy Systems (Switzerland) AG
Revisions
2012-04-27 12:00, 2012-01-26 14:15, 2011-06-20 07:34, 2011-02-10 09:01, 2010-06-16 10:27, 2010-02-24 10:46, 2009-09-04 09:52, 2008-02-21 14:39, 2008-01-18 08:35, 2006-07-27 10:26, 2006-03-02 08:55, 2006-02-23 09:32, 2005-06-03 11:07
Namespace
delta
Source file
ORION-BASE-MIB
Digest
sha256:a073e2d78f71bec0b56e80fd308b41d5706861cd7b586b723adda8fec9d2dd2a

Description

MIB for managing a DC power system with PSC 3.

Contact

postal: Delta Energy Systems (Switzerland) AG Freiburgstrasse 251, CH-3018 Bern-Buempliz web: www.deltapowersolutions.com email: patrick.camina@delta-es.com

Imports

FromSymbols
GLOBAL-REGmodules, orion
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-SMIGauge32, Integer32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

GLOBAL-REG
ORION-BASE-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
orionBaseMib
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1
controllerConfs
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.1
controllerGroups
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.1.1
controllerCompl
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.1.2
controllerObjects
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2
dcSystemInfo
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.1
dcSiteName
OBJECT-TYPE
An administratively-assigned site name for this DC-power system.
1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1DisplayString (SIZE(0..16))read-writecurrent
dcSystemName
OBJECT-TYPE
An administratively-assigned system name for this DC-power system.
1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2DisplayString (SIZE(0..16))read-writecurrent
dcSystemDateTime
OBJECT-TYPE
ISO 8601 representation of controller´s local date/time. The value is in the format YYYY-MM-DDThh:mm:ss. An example of a valid string is: '2004-10-04T13:45:00'.
1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3DisplayString (SIZE(19))read-writecurrent
dcSoftwareVersion
OBJECT-TYPE
The controller´s software version e.g V2.50Build1.
1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4DisplayString (SIZE(10..12))read-onlycurrent
dcSystemAlarms
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.2
dcEventHistoryTable
OBJECT-TYPE
Controller´s event history table that shows the content of the default log file.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1not-accessiblecurrent
dcEventHistoryEntry
OBJECT-TYPE
A particular Event History entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1not-accessiblecurrent
dcEventHistoryIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1Integer32 (1..10000)not-accessiblecurrent
dcEventHistoryTimestamp
OBJECT-TYPE
ISO8601 timestamp representation of a particular entry in the form YYYY-MM-DDThh:mm:ss.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2DisplayString (SIZE(19))read-onlycurrent
dcEventHistoryMessage
OBJECT-TYPE
Event message of a particular entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3DisplayString (SIZE(1..255))read-onlycurrent
dcAlarmTable
OBJECT-TYPE
Table that shows all currently active alarm sources causing urgent or non-urgent alarm(s).
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2not-accessiblecurrent
dcAlarmEntry
OBJECT-TYPE
A particular active alarm source entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1not-accessiblecurrent
dcAlarmIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1Integer32 (1..16)not-accessiblecurrent
dcAlarmEventCategory
OBJECT-TYPE
Specifies the type of alarm source.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2INTEGER {unknown(1), urgent(2), nonUrgent(3), critical(4)}read-onlycurrent
dcAlarmEventName
OBJECT-TYPE
Name of a particular alarm source entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3DisplayString (SIZE(1..35))read-onlycurrent
dcAlarmEventIdentifier
OBJECT-TYPE
Unique alarm event identifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4Gauge32read-onlycurrent
dcAlarmEventValue
OBJECT-TYPE
Event status that corresponds to alarm event identifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5INTEGER {false(1), true(3)}read-onlycurrent
dcNumberUrgentAlarms
OBJECT-TYPE
Number of currently active urgent alarm sources. A zero value indicates that urgent alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3Gauge32read-onlycurrent
dcNumberNonUrgentAlarms
OBJECT-TYPE
Number of currently active non urgent alarm sources. A zero value indicates that non urgent alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4Gauge32read-onlycurrent
dcMainsFailureAlarm
OBJECT-TYPE
Mains failure alarm.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5INTEGER {inactive(1), active(2)}read-onlycurrent
dcUrgentAlarmIdentifier
OBJECT-TYPE
Current unique urgent alarm event identifier. A zero value indicates that urgent alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6Gauge32read-onlycurrent
dcUrgentAlarmValue
OBJECT-TYPE
Current urgent alarm event status that corresponds to the urgent alarm identifier. If the urgent alarm identifier is zero then the alarm value is false.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7INTEGER {false(1), indeterminate(2), true(3)}read-onlycurrent
dcNonUrgentAlarmIdentifier
OBJECT-TYPE
Current unique non urgent alarm event identifier. A zero value indicates that non urgent alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8Gauge32read-onlycurrent
dcNonUrgentAlarmValue
OBJECT-TYPE
Current non urgent alarm event status that corresponds to non urgent alarm identifier. If the non urgent alarm identifier is zero then the alarm value is false.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9INTEGER {false(1), indeterminate(2), true(3)}read-onlycurrent
dcUrgentAlarmName
OBJECT-TYPE
Current alarm name for urgent alarm that corresponds to urgent alarm identifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10DisplayString (SIZE(0..35))read-onlycurrent
dcNonUrgentAlarmName
OBJECT-TYPE
Current alarm name for active non urgent alarm that corresponds to non urgent alarm identifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11DisplayString (SIZE(0..35))read-onlycurrent
dcGenericAlarmTable
OBJECT-TYPE
Table that shows ten alarm event assignments that can be configured via WEB interface.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12not-accessiblecurrent
dcGenericAlarmEntry
OBJECT-TYPE
A particular generic alarm entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1not-accessiblecurrent
dcGenericAlarmIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1Integer32 (1..16)not-accessiblecurrent
dcGenericAlarmEventName
OBJECT-TYPE
Plain text name of the assigned alarm event. Empty if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2DisplayString (SIZE(0..35))read-onlycurrent
dcGenericAlarmEventIdentifier
OBJECT-TYPE
Unique numeric identifier of the assigned alarm event. Zero if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3Gauge32read-onlycurrent
dcGenericAlarmEventValue
OBJECT-TYPE
Current value of the assigned alarm event. Value is false if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4INTEGER {false(1), true(2)}read-onlycurrent
dcNumberCriticalAlarms
OBJECT-TYPE
Number of currently active critical alarm sources. A zero value indicates that critical alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.13Gauge32read-onlycurrent
dcCriticalAlarmIdentifier
OBJECT-TYPE
Current unique critical alarm event identifier. A zero value indicates that critical alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.14Gauge32read-onlycurrent
dcCriticalAlarmValue
OBJECT-TYPE
Current critical alarm event status that corresponds to the critical alarm identifier. If the critical alarm identifier is zero then the alarm value is false.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.15INTEGER {false(1), indeterminate(2), true(3)}read-onlycurrent
dcCriticalAlarmName
OBJECT-TYPE
Current alarm name for active critical alarm that corresponds to critical alarm identifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.16DisplayString (SIZE(0..35))read-onlycurrent
dcSystemMonitor
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.3
dcSystemVoltage
OBJECT-TYPE
The measured system voltage. The max. value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1Integer32read-onlycurrent
dcLoadCurrent
OBJECT-TYPE
The measured load current. The max. value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2Integer32read-onlycurrent
dcBatteryCurrent
OBJECT-TYPE
The measured battery current. The max. value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3Integer32read-onlycurrent
dcBatteryTemperature
OBJECT-TYPE
The measured battery temperature. The max. value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4Integer32read-onlycurrent
dcChargeState
OBJECT-TYPE
Battery charge state.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5INTEGER {float(1), discharge(2), equalize(3), boost(4), battTest(5), recharge(6), sepCharge(7), evCtrlCharge(8)}read-onlycurrent
dcCurrentLimit
OBJECT-TYPE
Battery current limit.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6INTEGER {inactive(1), active(2)}read-onlycurrent
dcRectifierCurrent
OBJECT-TYPE
Total current of all working rectifier modules. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7Integer32read-onlycurrent
dcSystemPower
OBJECT-TYPE
Calculated system power. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8Integer32read-onlycurrent
dcRectifier
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.4
dcNumberRectifiers
OBJECT-TYPE
The configured number of rectifiers plugged into the system. The maximum number of rectifiersi is 128.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1Gauge32 (0..128)read-onlycurrent
dcNumberRectifiersFailure
OBJECT-TYPE
Number of rectifiers that are not properly working.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2Gauge32 (0..128)read-onlycurrent
dcNumberRectifiersOkay
OBJECT-TYPE
Number of rectifiers that are properly working.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3Gauge32 (0..128)read-onlycurrent
dcRectifierTable
OBJECT-TYPE
Table that shows all currently active rectifier modules.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4not-accessiblecurrent
dcRectifierEntry
OBJECT-TYPE
A particular rectifier entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1not-accessiblecurrent
dcRectifierIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1Integer32 (1..128)not-accessiblecurrent
dcRectifierIdentifier
OBJECT-TYPE
Unique rectifier identifier. If positioning active the position number scheme is used otherwise the rectifier instance is used to identify a rectifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2DisplayString (SIZE(1..16))read-onlycurrent
dcRectifierStatus
OBJECT-TYPE
Specifies status of rectifiers.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3INTEGER {unknown(1), off(2), on(3)}read-onlycurrent
dcRectifierGroupTable
OBJECT-TYPE
Table that shows all available rectifier groups.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5not-accessiblecurrent
dcRectifierGroupEntry
OBJECT-TYPE
A particular rectifier group entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1not-accessiblecurrent
dcRectifierGroupIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.1Integer32 (1)not-accessiblecurrent
dcRectifierGroupName
OBJECT-TYPE
Rectifier group name to identify an individual device parameter set.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.2DisplayString (SIZE(1..16))read-onlycurrent
dcRectifierGroupRectifierType
OBJECT-TYPE
Rectifier type defined for this group.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.3INTEGER {unknown48V(1), fR48V2000W(2), dPR1200B48(3), dPR1500B48(4), dPR600B48(5), dPR7200B48(6), fR48to60V2000W(7), unknown24V(8), unknown60V(9), dPR600B60(10), dPR3500B48(11), dPR3500B24(12), dPR300B48(13), dPR1600B48(14), dPR2700B48(15), dPR2400B48(16), dPR4000B48(17), dPR2900B48(18), dPR4000B48to60(19), dPR850B48(20), dPR2000B48(21)}read-onlycurrent
dcRectifierGroupDefaultVoltage
OBJECT-TYPE
This default voltage is used by rectifiers when there is no connection to PSC 3.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.4Integer32read-writecurrent
dcRectifierGroupDefaultCurrentLimit
OBJECT-TYPE
This default current limit is used by rectifiers when there is no connection to PSC 3.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.5Integer32read-writecurrent
dcRectifierGroupDefaultPowerLimit
OBJECT-TYPE
This default power limit is used by rectifiers when there is no connection to PSC 3.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.6Integer32read-writecurrent
dcRectifierGroupInputLowOff
OBJECT-TYPE
Threshold for low AC input voltage. It can is used to adjust the behaviour of the power system to the available AC network limitation.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.7Integer32read-writecurrent
dcRectifierGroupInputLowOn
OBJECT-TYPE
For details see dcRectifierGroupInputLowOff.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.8Integer32read-writecurrent
dcRectifierGroupStartupVoltage
OBJECT-TYPE
Startup parameters are the values that rectifiers use during the start-up phase. These parameters allow starting the system smoothly after a mains failure even on a discharged battery and even without PSC 3.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.9Integer32read-writecurrent
dcRectifierGroupStartupCurrentLimit
OBJECT-TYPE
For details see dcRectifierGroupStartupVoltage.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.10Integer32read-writecurrent
dcRectifierGroupStartupPowerLimit
OBJECT-TYPE
For details see dcRectifierGroupStartupVoltage.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.11Integer32read-writecurrent
dcRectifierGroupStartupTimeLimit
OBJECT-TYPE
For details see dcRectifierGroupStartupVoltage.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.12Gauge32read-writecurrent
dcRectifierGroupPowerupDelay
OBJECT-TYPE
This parameter is used after a mains failure to delay the start-up of all rectifiers.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.13Gauge32read-writecurrent
dcRectifierGroupPowerupTime
OBJECT-TYPE
This parameter used after a mains failure and allows defining a time within all rectifiers needs to start-up one after another.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.14Gauge32read-writecurrent
dcRectifierGroupUmaxOff
OBJECT-TYPE
Overvoltage protection value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.15Integer32read-writecurrent
dcRectifierFunctions
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6
dcEfficiencyCycling
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1
dcEfficiencyCyclingEnabled
OBJECT-TYPE
Enable/disable efficiency cycling.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.1INTEGER {no(1), yes(2)}read-writecurrent
dcLimitSwitchingTimes
OBJECT-TYPE
Enable/disable limit switching times.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.2INTEGER {no(1), yes(2)}read-writecurrent
dcForceSwitchingOncePerMonth
OBJECT-TYPE
Enable/disable force switching once per month.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.3INTEGER {no(1), yes(2)}read-writecurrent
dcMaximumLoadStep
OBJECT-TYPE
Maximum load setup.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.4Integer32read-writecurrent
dcMinimumLoadStep
OBJECT-TYPE
Minimum load setup.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.5Integer32read-writecurrent
dcPowerLimitation
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2
dcPowerLimitationTable
OBJECT-TYPE
Table that shows parameters of the available power limitation functions.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1not-accessiblecurrent
dcPowerLimitationEntry
OBJECT-TYPE
A particular power limitation entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1not-accessiblecurrent
dcPowerLimitationIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.1Integer32 (1..16)not-accessiblecurrent
dcPowerLimitationEventName
OBJECT-TYPE
Name of the power limitation event.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.2DisplayString (SIZE(1..35))read-onlycurrent
dcPowerLimitationStatus
OBJECT-TYPE
Status of power limitation.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.3INTEGER {disabled(1), inactive(2), powerLimit(3)}read-onlycurrent
dcPowerLimitationType
OBJECT-TYPE
Power limitation type.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.4INTEGER {dynamic(1), fixedLimit(2)}read-onlycurrent
dcPowerLimitationLimit
OBJECT-TYPE
Limit used for power limitation.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.5Integer32read-writecurrent
dcPowerLimitationNoBatteryDischarge
OBJECT-TYPE
Enable/disable no battery discharge during power limitation.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.6INTEGER {no(1), yes(2)}read-writecurrent
dcBattery
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5
dcFloatCharge
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1
dcUsys20
OBJECT-TYPE
Voltage to regulate to at 20°C. If temperature compensation is used, this voltage will vary.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1Integer32read-writecurrent
dcBatteryTest
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2
dcBatteryTestParameter
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1
dcBatteryTestUsupport
OBJECT-TYPE
Support charge voltage for the battery.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1Integer32read-writecurrent
dcBatteryTestDuration
OBJECT-TYPE
Battery test duration.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2Gauge32read-writecurrent
dcBatteryTestInterval
OBJECT-TYPE
Minimal time between programmed battery tests as start condition.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3Gauge32read-writecurrent
dcBatteryTestDischargeCurrent
OBJECT-TYPE
Battery discharge current. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4Integer32read-writecurrent
dcBatteryTestMinDuration
OBJECT-TYPE
Minimum battery test duration during which time a battery test is not stopped in case of a voltage below the support voltage or a current difference higher than the specified value defined in Idiff measurement is detected.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5Gauge32read-writecurrent
dcBatteryTestVoltageWithinUfloat
OBJECT-TYPE
Battery voltage must be within Ufloat +/- set voltage for a given time (see also dcBatteryTestVoltageWithinUfloatPeriod) in order to start a battery test.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.6Integer32read-writecurrent
dcBatteryTestVoltageWithinUfloatPeriod
OBJECT-TYPE
For details see dcBatteryTestVoltageWithinUfloat parameter.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.7Gauge32read-writecurrent
dcBatteryTestTempFrom
OBJECT-TYPE
Battery temperature must be within temperature range given by dcBatteryTestTempFrom and dcBatteryTestTempTo, so that a battery test can be started.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.8Integer32read-writecurrent
dcBatteryTestTempTo
OBJECT-TYPE
For details see dcBatteryTestTempFrom parameter.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.9Integer32read-writecurrent
dcBatteryTestIntervalEnabled
OBJECT-TYPE
Enable/disable interval. For more details see dcBatteryTestInterval.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.10INTEGER {no(1), yes(2)}read-writecurrent
dcBatteryTestStartTimeFrom
OBJECT-TYPE
Defines start time window for battery test. The possible time window is defined as the range between dcBatteryTestStartTimeFrom and dcBatteryTestStartTimeTo. The value is in the format 'hh:mm:ss'.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.11DisplayString (SIZE(8))read-writecurrent
dcBatteryTestStartTimeTo
OBJECT-TYPE
For details see dcBatteryTestStartTimeFrom.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.12DisplayString (SIZE(8))read-writecurrent
dcBatteryTestResults
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2
dcBatteryTestDateTime
OBJECT-TYPE
ISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test result available.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1DisplayString (SIZE(19))read-onlycurrent
dcBatteryTestResult
OBJECT-TYPE
Result of last performed battery test.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2INTEGER {none(1), failed(2), aborted(3), loadFailure(4), okay(5), abortedManual(6), abortedEvCtrlCharge(7), abortedInhibitEv(8)}read-onlycurrent
dcBatteryTestEndVoltage
OBJECT-TYPE
System voltage at the end of the last performed battery test. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3Integer32read-onlycurrent
dcBatteryTestControl
OBJECT-TYPE
Start/stop of battery test. This special charge mode is used to check the capacity of a battery. Please note that a battery test can be started even if the battery is not fully charged. In this case the test result is ambiguous and the set failure event will become active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3INTEGER {start(1), stop(2)}read-writecurrent
dcBatteryTestStatus
OBJECT-TYPE
Status of battery test.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4INTEGER {inactive(1), starting(2), stopping(3), constantCurrent(4), timeBased(5), energyBased(6), recovery(7), realLoad(8), stop(9)}read-onlycurrent
dcBatteryTestFailureEvent
OBJECT-TYPE
Reset battery test failure event.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5INTEGER {reset(1)}read-writecurrent
dcBatteryTestType
OBJECT-TYPE
Battery test type used.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.6INTEGER {none(1), constantCurrent(2), realLoad(5)}read-writecurrent
dcBatteryParameter
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3
dcTotalBatteryCapacity
OBJECT-TYPE
Total battery capacity for all available batteries.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1Gauge32read-onlycurrent
dcBatteryStringTable
OBJECT-TYPE
Table that shows parameters of the available battery strings.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2not-accessiblecurrent
dcBatteryStringEntry
OBJECT-TYPE
A particular battery string entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1not-accessiblecurrent
dcBatteryStringIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.1Integer32 (1..16)not-accessiblecurrent
dcBatteryStringName
OBJECT-TYPE
Name of the battery string.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.2DisplayString (SIZE(1..16))read-onlycurrent
dcBatteryStringMaxIBatt
OBJECT-TYPE
Maximum battery charging current for this string. This parameter can be set individually for each battery. PSC 3 then regulates the system voltage such that the maximum battery charging current of each battery is respected.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.3Integer32read-writecurrent
dcBatteryStringCapacity
OBJECT-TYPE
Capacity of battery can be defined individually. It is used to calculate the expected backup time of the system.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.4Gauge32read-writecurrent
dcLossOfBackupTime
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3
dcLossOfBackupTimeEnabled
OBJECT-TYPE
Enable/disable loss of backup time functionality.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.1INTEGER {no(1), yes(2)}read-writecurrent
dcLossOfBackupTimeStatus
OBJECT-TYPE
Status of loss of backup time functionality.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.2INTEGER {inactive(1), ok(2), occured(3), fail(4)}read-onlycurrent
dcExpectedBackupTime
OBJECT-TYPE
Expected backup time value. Based on the given value for the parameter expected backup time, the corresponding maximum discharge current is calculated.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.3Gauge32read-writecurrent
dcEqualize
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4
dcEqualizeControl
OBJECT-TYPE
Start/stop of battery equalize which is a special charge mode that applies a higher voltage to the batteries than the float charge. This ensures that the cells are all equally charged.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1INTEGER {start(1), stop(2)}read-writecurrent
dcEqualizeStatus
OBJECT-TYPE
Current status of battery equalize.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2INTEGER {inactive(1), starting(2), stopping(3), preparing(4), cooking(5), recovering(6)}read-onlycurrent
dcEqualizeEnabled
OBJECT-TYPE
Enable/disable equalize.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.3INTEGER {no(1), yes(2)}read-writecurrent
dcEqualizeParameter
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4
dcEqualizeVoltage
OBJECT-TYPE
Voltage used for equalize.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.1Integer32read-writecurrent
dcEqualizeDuration
OBJECT-TYPE
Duration of equalize.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.2Gauge32read-writecurrent
dcEqualizeUseBattRoomFanEnabled
OBJECT-TYPE
Enable/disable battery room fan during equalize.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.3INTEGER {no(1), yes(2)}read-writecurrent
dcEqualizeLeadTime
OBJECT-TYPE
Lead time for equalize.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.4Gauge32read-writecurrent
dcEqualizeTimeLag
OBJECT-TYPE
Time lag for equalize.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.5Gauge32read-writecurrent
dcEqualizeInterval
OBJECT-TYPE
Interval for equalize as start condition.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.6Gauge32read-writecurrent
dcEqualizeStartTimeIntervalFrom
OBJECT-TYPE
Defines start time window for equqlize. The possible time window is defined as the range between dcEqualizeStartTimeIntervalFrom and dcEqualizeStartTimeIntervalTo. The value is in the format 'hh:mm:ss'.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.7DisplayString (SIZE(8))read-writecurrent
dcEqualizeStartTimeIntervalTo
OBJECT-TYPE
For detail see dcEqualizeStartTimeIntervalFrom.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.8DisplayString (SIZE(8))read-writecurrent
dcEqualizeInhibitAfterBoost
OBJECT-TYPE
Inhibit after boost as start condition.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.9Gauge32read-writecurrent
dcBoostCharge
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5
dcBoostChargeControl
OBJECT-TYPE
Start/stop of boost charge which is a special charge mode that applies a higher voltage to the batteries than the float charge. This mode is started after a discharge phase to recharge the batteries faster.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1INTEGER {start(1), stop(2)}read-writecurrent
dcBoostChargeStatus
OBJECT-TYPE
Current status of boost charge.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2INTEGER {inactive(1), starting(2), stopping(3), cooking(4), recovering(5)}read-onlycurrent
dcBoostChargeType
OBJECT-TYPE
Boost charge type.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.3INTEGER {none(1), currentBased(2), timeBased(3), energyBased(4)}read-writecurrent
dcBoostChargeParameter
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4
dcBoostChargeVoltage
OBJECT-TYPE
Voltage used for boost charge.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.1Integer32read-writecurrent
dcBoostChargeMaxDuration
OBJECT-TYPE
Defines the maximum allowed time for boost charge to prevent that the battery is charged forever.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.2Gauge32read-writecurrent
dcBoostChargeUseBattRoomFanEnabled
OBJECT-TYPE
Enable/disable battery room fan during boost charge.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.3INTEGER {no(1), yes(2)}read-writecurrent
dcBoostChargeTimeLag
OBJECT-TYPE
Time lag used for boost charge.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.4Gauge32read-writecurrent
dcBoostChargeIstart
OBJECT-TYPE
For current based boost charge, the parameters Istart and Istop are the battery current values at which boost charge starts or stops.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.5Integer32read-writecurrent
dcBoostChargeIstop
OBJECT-TYPE
For details see dcBoostChargeIstart.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.6Integer32read-writecurrent
dcBoostChargeInhibitTime
OBJECT-TYPE
A start condition for all types of boost charge. It defines the time from last boost charge stop to the next acceptable boost charge start.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.7Gauge32read-writecurrent
dcSystemVoltageSupervision
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6
dcUaMax
OBJECT-TYPE
If the system voltage is outside the range specified by the values UaMin (lower alarm voltage)/UaMax (upper alarm voltage), the system event 'S Ua low'/'S Ua high' is activated. The values for the parameters UaMin and UaMax are not temperature compensated.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.1Integer32read-writecurrent
dcUaMin
OBJECT-TYPE
For details see dcUaMax.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.2Integer32read-writecurrent
dcUsMax
OBJECT-TYPE
If the voltage is outside the range defined by the parameters UsMin (lower safety voltage)/UsMax (upper safety voltage), the system event 'S Us low'/'S Us high' is activated. If temperature compensation is enabled, the levels for Us min and / Us max are automatically temperature compensated to correspond to the required system voltage. The parameters are defined at 20°C.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.3Integer32read-writecurrent
dcUsMin
OBJECT-TYPE
For details see dcUsMax.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.4Integer32read-writecurrent
dcBoD
OBJECT-TYPE
Voltage threshold for Battery on Discharge alarm.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.5Integer32read-writecurrent
dcHysteresis
OBJECT-TYPE
Hysteresis used for Ua and Us.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.6Integer32read-writecurrent
dcSuppressUaLowEnabled
OBJECT-TYPE
Suppress Ua Low alarm during mains failure.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.7INTEGER {no(1), yes(2)}read-writecurrent
dcSuppressUsLowEnabled
OBJECT-TYPE
Suppress Us Low alarm during mains failure.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.8INTEGER {no(1), yes(2)}read-writecurrent
dcEnableUsTempComp
OBJECT-TYPE
Checkbox to enable the automatic temperature compensation for the Us thresholds (Us min, Us max).
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.9INTEGER {no(1), yes(2)}read-writecurrent
dcEvtCtrlCharge
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7
dcEvtCtrlChargeStatus
OBJECT-TYPE
Event control charge status.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1INTEGER {inactive(1), voltageControlled(2), noBatteryCharge(3), currentLimitation(4)}read-onlycurrent
dcEvtCtrlChargeType
OBJECT-TYPE
Selected event control charge type.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.2INTEGER {none(1), voltageControlled(2), noBatteryCharge(3), currentLimitation(4)}read-writecurrent
dcEvtCtrlChargeParameter
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3
dcEvtCtrlChargeVoltage
OBJECT-TYPE
Voltage used for event control charge.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.1Integer32read-writecurrent
dcEvtCtrlChargeTempCompEnabled
OBJECT-TYPE
Enable/disable temperature compensation during event control charge.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.2INTEGER {no(1), yes(2)}read-writecurrent
dcEvtCtrlChargeMaxIBatt
OBJECT-TYPE
Max. IBatt used for event control charge.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.3Integer32read-writecurrent
dcTempComp
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8
dcTempCompType
OBJECT-TYPE
Enable/disable battery temperature compensation.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.1INTEGER {no(1), linear(2), multi-stage(3)}read-writecurrent
dcSlope
OBJECT-TYPE
Temperature compensation coefficient for system voltage.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.2Integer32read-writecurrent
dcStartTemp
OBJECT-TYPE
Lower limit for the area in which the temperature compensation is active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.3Integer32read-writecurrent
dcStopTemp
OBJECT-TYPE
Upper limit for the area in which the temperature compensation is active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.4Integer32read-writecurrent
dcMaxVoltage
OBJECT-TYPE
Upper limit for the area in which the temperature compensation is not controlling the system voltage.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.5Integer32read-writecurrent
dcLowStopVoltage
OBJECT-TYPE
The temperature compensation will not control the charging voltage above this parameter at low temperatures.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.6Integer32read-writecurrent
dcLowStartTemp
OBJECT-TYPE
High temperature limit of the lower range.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.7Integer32read-writecurrent
dcLowTempSlope
OBJECT-TYPE
Compensation factor applied inside the low range.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.8Integer32read-writecurrent
dcHighStartTemp
OBJECT-TYPE
The low temperature limit of the higher range.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.9Integer32read-writecurrent
dcHighTempSlope
OBJECT-TYPE
Compensation factor applied inside the high range.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.10Integer32read-writecurrent
dcHighStopVoltage
OBJECT-TYPE
The temperature compensation will not control the charging voltage below this parameter at high temperatures.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.11Integer32read-writecurrent
dcRunawayTemp
OBJECT-TYPE
A threshold for detecting thermal runaway of the battery.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.12Integer32read-writecurrent
dcRunawayVoltage
OBJECT-TYPE
Charging voltage while Runaway Temp has been exceeded.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13Integer32read-writecurrent
dcTempSupervision
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9
dcHighTemp
OBJECT-TYPE
Temperature threshold for high battery temperature alarm 10°C ... 70°C
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.1Integer32read-writecurrent
dcHighTempHyst
OBJECT-TYPE
Hysteresis for the High Temp 1°C ... 70°C
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.2Integer32read-writecurrent
dcInputOutput
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.6
dcControlEventTable
OBJECT-TYPE
Table that shows ten output event assignments that can be configured via WEB interface.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1not-accessiblecurrent
dcControlEventEntry
OBJECT-TYPE
A particular generic output entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1not-accessiblecurrent
dcControlEventIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1Integer32 (1..16)not-accessiblecurrent
dcControlEventName
OBJECT-TYPE
Plain text name of the assigned control event. Empty if not configure.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2DisplayString (SIZE(0..35))read-onlycurrent
dcControlEventIdentifier
OBJECT-TYPE
Unique numeric identifier of the assigned control event. Zero if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3Gauge32read-onlycurrent
dcControlEventValue
OBJECT-TYPE
Current value of the assigned control event. Value is false if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4INTEGER {false(1), true(2)}read-writecurrent
dcMisc
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.7
dcTrapDestinationTable
OBJECT-TYPE
Trap table that shows all configured trap destinations.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1not-accessiblecurrent
dcTrapDestinationEntry
OBJECT-TYPE
A particular trap destination entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1not-accessiblecurrent
dcTrapDestinationIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1Integer32 (1..10)not-accessiblecurrent
dcTrapDestinationIp
OBJECT-TYPE
IP address of the trap destination. Value is 0.0.0.0 if IP address is not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2IpAddressread-writecurrent
dcTrapDestinationPort
OBJECT-TYPE
Port number of the trap destination. By default port 162 is used.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3Gauge32read-writecurrent
dcFileProcessingStatus
OBJECT-TYPE
File processing status for software and setup up/downloads.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2INTEGER {idle(1), inProgress(2), successful(3), error(4), unknown(5)}read-onlycurrent
dcResendActiveAlarmTraps
OBJECT-TYPE
Resend all active Urgent, Non Urgent, and Critical Alarm Traps.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.4INTEGER {resend(1)}read-writecurrent
dcConfig
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.8
dcDefaultLogEventTable
OBJECT-TYPE
Event config table for default log.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1not-accessiblecurrent
dcDefaultLogEventEntry
OBJECT-TYPE
A particular event entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1not-accessiblecurrent
dcDefaultLogEventIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.1Integer32 (0..1000)not-accessiblecurrent
dcDefaultLogEventName
OBJECT-TYPE
Plain text name of the event that can be logged.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.2DisplayString (SIZE(1..35))read-onlycurrent
dcDefaultLogEventLogged
OBJECT-TYPE
If yes then this event is logged otherwise not.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.3INTEGER {no(1), yes(2)}read-writecurrent
dcEventProcessingEventTable
OBJECT-TYPE
Event config table for event ORs.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2not-accessiblecurrent
dcEventProcessingEventEntry
OBJECT-TYPE
A particular event entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1not-accessiblecurrent
dcEventProcessingEventIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.1Integer32 (0..1000)not-accessiblecurrent
dcEventProcessingEventName
OBJECT-TYPE
Plain text name of the input event.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.2DisplayString (SIZE(1..35))read-onlycurrent
dcEventProcessingEventAssigned
OBJECT-TYPE
If yes then the input event is assigned to the selected event. Please note, that it is only possible to change assignment of event ORs.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.3INTEGER {no(1), yes(2)}read-writecurrent
dcEventProcessingEventType
OBJECT-TYPE
Type of the input event.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.4INTEGER {unknown(1), eventOR(2)}read-onlycurrent
dcEventProcessingEventSelected
OBJECT-TYPE
Reference to dcEventProcessingEventIndex in order to select a specific event.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.3Gauge32read-writecurrent
dcLvdTable
OBJECT-TYPE
Table lists all available LVDs.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4not-accessiblecurrent
dcLvdEntry
OBJECT-TYPE
A particular LVD entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1not-accessiblecurrent
dcLvdIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.1Integer32 (1..96)not-accessiblecurrent
dcLvdName
OBJECT-TYPE
Name of the LVD.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.2DisplayString (SIZE(1..16))read-onlycurrent
dcLvdDisconnectDelay
OBJECT-TYPE
Time delay from the activation of the source event, after which the LVD event is switched. The value is in the format 'hh:mm:ss'.
1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.3DisplayString (SIZE(8))read-writecurrent
dcMeasurement
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.9
dcMeasurementTable
OBJECT-TYPE
Table lists all available measurements.
1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1not-accessiblecurrent
dcMeasurementEntry
OBJECT-TYPE
A particular measurement entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1not-accessiblecurrent
dcMeasurementIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.1Integer32 (1..500)not-accessiblecurrent
dcMeasurementName
OBJECT-TYPE
Name of the measurement.
1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.2DisplayString (SIZE(1..16))read-onlycurrent
dcMeasurementValue
OBJECT-TYPE
Unscaled calibrated value of the measurement.
1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.3Integer32read-onlycurrent
dcMeasurementScaleFactor
OBJECT-TYPE
Scale factor as power of 10 to be multiplied with measurement value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.4Integer32read-onlycurrent
dcMeasurementUnit
OBJECT-TYPE
Unit of the measurement.
1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.5INTEGER {unknown(1), none(2), voltDC(3), voltAC(4), ampere(5), ampereHour(6), degreeCelsius(7), temperatureCoefficient(8), watt(9), wattHour(10), seconds(11), percent(12), hertz(13), voltAmpere(14), voltAmpereReactive(15), voltAmpereReactiveHour(16)}read-onlycurrent
dcMeterPanel
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.2.10
dcMeterPanelEventTable
OBJECT-TYPE
Table lists all available meter panel events.
1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1not-accessiblecurrent
dcMeterPanelEventEntry
OBJECT-TYPE
A particular meter panel event entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1not-accessiblecurrent
dcMeterPanelEventIndex
OBJECT-TYPE
Table index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.1Integer32 (1..128)not-accessiblecurrent
dcMeterPanelEventName
OBJECT-TYPE
Name of the event.
1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.2DisplayString (SIZE(1..16))read-onlycurrent
dcMeterPanelEventValue
OBJECT-TYPE
Value of the event.
1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.3INTEGER {false(1), indeterminate(2), true(3)}read-onlycurrent
dcMeterPanelEventHourMeterValue
OBJECT-TYPE
Value of the hour meter event.
1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.4Gauge32read-onlycurrent
controllerEvents
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.3
controllerEventObjects
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.3.1
controllerEventsV2
OBJECT-IDENTITY
1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0

Notifications

NameOIDStatus
systemNonUrgentAlarm
NOTIFICATION-TYPE
The controller reports that one or more elements have changed into none urgent alarm state.
1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1current
systemUrgentAlarm
NOTIFICATION-TYPE
The controller reports that one or more elements have changed into urgent alarm state.
1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2current
systemCriticalAlarm
NOTIFICATION-TYPE
The controller reports that one or more elements have changed into critical alarm state.
1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.3current

Conformance

NameOIDStatus
systemInfoGroup
OBJECT-GROUP
The collection of system info scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1current
systemAlarmGroup
OBJECT-GROUP
The collection of system alarm scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2current
systemMonitorGroup
OBJECT-GROUP
The collection of system monitor scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3current
rectifierGroup
OBJECT-GROUP
The collection of rectifier scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4current
eventHistoryTableGroup
OBJECT-GROUP
The collection of event history table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5current
alarmTableGroup
OBJECT-GROUP
The collection of alarm table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6current
rectifierTableGroup
OBJECT-GROUP
The collection of rectifier table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7current
notificationsGroup
NOTIFICATION-GROUP
The group of all controller notifications.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8current
genericAlarmTableGroup
OBJECT-GROUP
Assignment of events to alarm table entries.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9current
batteryGroup
OBJECT-GROUP
The collection of battery scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10current
controlEventTableGroup
OBJECT-GROUP
Assignment of control events to table entries.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11current
trapDestinationTableGroup
OBJECT-GROUP
Trap destionation table.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12current
miscGroup
OBJECT-GROUP
The collection of miscellaneous objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13current
rectifierGroupTableGroup
OBJECT-GROUP
The collection of rectifier group table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.14current
batteryStringTableGroup
OBJECT-GROUP
The collection of battery string table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.15current
defaultLogEventTableGroup
OBJECT-GROUP
The collection of default log event table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.16current
eventProcessingEventTableGroup
OBJECT-GROUP
The collection of event processing event table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.17current
lvdTableGroup
OBJECT-GROUP
The collection of LVD table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.18current
powerLimitationTableGroup
OBJECT-GROUP
The collection of power limitation table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.19current
measurementTableGroup
OBJECT-GROUP
The collection of measurement table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.20current
meterPanelEventTableGroup
OBJECT-GROUP
The collection of meter panel event table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.21current
controllerBasicCompl
MODULE-COMPLIANCE
The basic implementation requirements for the controller MIB.
1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1current