LIEBERT-GP-ENVIRONMENTAL-MIB
- Registered at
- 1.3.6.1.4.1.476.1.42.1.5.11.3.6.1.4.1.476.1.42.3.4.11.3.6.1.4.1.476.1.42.3.4.21.3.6.1.4.1.476.1.42.3.4.31.3.6.1.4.1.476.1.42.3.4.41.3.6.1.4.1.476.1.42.3.4.51.3.6.1.4.1.476.1.42.3.4.61.3.6.1.4.1.476.1.42.3.4.71.3.6.1.4.1.476.1.42.3.4.81.3.6.1.4.1.476.1.42.3.4.9
- Last updated
- 2015-07-21 00:00
- Organization
- Liebert Corporation
- Revisions
- 2008-11-17 00:00, 2008-07-02 00:00, 2008-01-10 00:00, 2007-05-29 00:00, 2006-08-15 00:00, 2006-02-22 00:00
- Namespace
- liebert
- Source file
LIEBERT-GP-ENVIRONMENTAL-MIB- Digest
sha256:641ab7d92cbd07a20e4021a615ff1568d20596bf7cf2e9d823333b1b20e84035
Description
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2015 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Contact
Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com Author: Gregory M. Hoge
Imports
| From | Symbols |
|---|---|
| LIEBERT-GP-REGISTRATION-MIB | lgpEnvironmental, liebertEnvironmentalModuleReg |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
LIEBERT-GP-ENVIRONMENTAL-MIB LIEBERT-GP-REGISTRATION-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| lgpEnvTemperature OBJECT-IDENTITY This sub-tree is used to register Liebert temperature object identifiers. | 1.3.6.1.4.1.476.1.42.3.4.1 | current | ||
| lgpEnvTemperatureWellKnown OBJECT-IDENTITY Liebert well known temperature objects are identified by OIDs that reside in this sub-tree. | 1.3.6.1.4.1.476.1.42.3.4.1.1 | current | ||
| lgpEnvControlTemperature OBJECT-IDENTITY Temperature measurement used as control feedback. | 1.3.6.1.4.1.476.1.42.3.4.1.1.1 | current | ||
| lgpEnvReturnAirTemperature OBJECT-IDENTITY Temperature measurement of return air. | 1.3.6.1.4.1.476.1.42.3.4.1.1.2 | current | ||
| lgpEnvSupplyAirTemperature OBJECT-IDENTITY Temperature measurement of supply air. | 1.3.6.1.4.1.476.1.42.3.4.1.1.3 | current | ||
| lgpAmbientTemperature OBJECT-IDENTITY Ambient temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.1.4 | current | ||
| lgpInverterTemperature OBJECT-IDENTITY Temperature measurement of the inverter. | 1.3.6.1.4.1.476.1.42.3.4.1.1.5 | current | ||
| lgpBatteryTempterature OBJECT-IDENTITY Temperature measurement of the battery. | 1.3.6.1.4.1.476.1.42.3.4.1.1.6 | current | ||
| lgpAcDcConverterTemperature OBJECT-IDENTITY Temperature measurement of the AC-to-DC Converter. | 1.3.6.1.4.1.476.1.42.3.4.1.1.7 | current | ||
| lgpPfcTemperature OBJECT-IDENTITY Temperature measurement of the power factor correction circuitry. | 1.3.6.1.4.1.476.1.42.3.4.1.1.8 | current | ||
| lgpTransformerTemperature OBJECT-IDENTITY Temperature measurement of the transformer. | 1.3.6.1.4.1.476.1.42.3.4.1.1.9 | current | ||
| lgpLocalTemperature OBJECT-IDENTITY Temperature measurement of local temperature sensor. | 1.3.6.1.4.1.476.1.42.3.4.1.1.10 | current | ||
| lgpLocal1Temperature OBJECT-IDENTITY Temperature and humidity measurements of Local Sensor 1. | 1.3.6.1.4.1.476.1.42.3.4.1.1.10.1 | current | ||
| lgpLocal2Temperature OBJECT-IDENTITY Temperature and humidity measurements of Local Sensor 2. | 1.3.6.1.4.1.476.1.42.3.4.1.1.10.2 | current | ||
| lgpLocal3Temperature OBJECT-IDENTITY Temperature and humidity measurements of Local Sensor 3. | 1.3.6.1.4.1.476.1.42.3.4.1.1.10.3 | current | ||
| lgpDigitalScrollCompressorTemperature OBJECT-IDENTITY Temperature and humidity measurements of a digital Scroll Compressor. | 1.3.6.1.4.1.476.1.42.3.4.1.1.11 | current | ||
| lgpDigitalScrollCompressor1Temperature OBJECT-IDENTITY Temperature and humidity measurements of a digital Scroll Compressor 1. | 1.3.6.1.4.1.476.1.42.3.4.1.1.11.1 | current | ||
| lgpDigitalScrollCompressor2Temperature OBJECT-IDENTITY Temperature and humidity measurements of a digital Scroll Compressor 2. | 1.3.6.1.4.1.476.1.42.3.4.1.1.11.2 | current | ||
| lgpChillWaterTemperature OBJECT-IDENTITY Temperature measurements of a chill water system. | 1.3.6.1.4.1.476.1.42.3.4.1.1.12 | current | ||
| lgpCoolantTemperature OBJECT-IDENTITY Temperature measurements of an environmental system's coolant. | 1.3.6.1.4.1.476.1.42.3.4.1.1.13 | current | ||
| lgpEnvEnclosureTemperatureSensors OBJECT-IDENTITY Enclosure temperature sensors | 1.3.6.1.4.1.476.1.42.3.4.1.1.14 | current | ||
| lgpEnvEnclosureTemperatureSensor1 OBJECT-IDENTITY Enclosure temperature sensor 1 | 1.3.6.1.4.1.476.1.42.3.4.1.1.14.1 | current | ||
| lgpEnvEnclosureTemperatureSensor2 OBJECT-IDENTITY Enclosure temperature sensor 2 | 1.3.6.1.4.1.476.1.42.3.4.1.1.14.2 | current | ||
| lgpEnvEnclosureTemperatureSensor3 OBJECT-IDENTITY Enclosure temperature sensor 3 | 1.3.6.1.4.1.476.1.42.3.4.1.1.14.3 | current | ||
| lgpEnvEnclosureTemperatureSensor4 OBJECT-IDENTITY Enclosure temperature sensor 4 | 1.3.6.1.4.1.476.1.42.3.4.1.1.14.4 | current | ||
| lgpEnvValueAmbientRoomTemperature OBJECT-IDENTITY Temperature outside enclosure. | 1.3.6.1.4.1.476.1.42.3.4.1.1.15 | current | ||
| lgpEnvDewPointTemperature OBJECT-IDENTITY The calculated temperature outside of the enclosure at which condensation is likely to occur. | 1.3.6.1.4.1.476.1.42.3.4.1.1.16 | current | ||
| lgpEnvEnclosureTemperature OBJECT-IDENTITY Temperature inside of enclosure. | 1.3.6.1.4.1.476.1.42.3.4.1.1.17 | current | ||
| lgpEnvAdjustedTemperature OBJECT-IDENTITY The current temperature set-point which is computed by the system and may be temporarily different from the user set-point because of external factors. | 1.3.6.1.4.1.476.1.42.3.4.1.1.18 | current | ||
| lgpEnvExternalSensors OBJECT-IDENTITY External sensors to monitor environmental variables such as temperature and humidity | 1.3.6.1.4.1.476.1.42.3.4.1.1.19 | current | ||
| lgpEnvExternalAirSensorA OBJECT-IDENTITY Temperature and humidity measurements from external air sensor A. | 1.3.6.1.4.1.476.1.42.3.4.1.1.19.1 | current | ||
| lgpEnvExternalAirSensorADewPoint OBJECT-IDENTITY Dewpoint temperature for External Air Sensor A. | 1.3.6.1.4.1.476.1.42.3.4.1.1.19.2 | current | ||
| lgpEnvExternalAirSensorB OBJECT-IDENTITY Temperature and humidity measurements from external air sensor B. | 1.3.6.1.4.1.476.1.42.3.4.1.1.19.3 | current | ||
| lgpEnvExternalAirSensorBDewPoint OBJECT-IDENTITY Dewpoint temperature for External Air Sensor B. | 1.3.6.1.4.1.476.1.42.3.4.1.1.19.4 | current | ||
| lgpEnvSupplyFluidTemperature OBJECT-IDENTITY The current temperature of the fluid being supplied. | 1.3.6.1.4.1.476.1.42.3.4.1.1.20 | current | ||
| lgpEnvSupplyRefrigerantTemperature OBJECT-IDENTITY The current temperature of the refrigerant being supplied. | 1.3.6.1.4.1.476.1.42.3.4.1.1.21 | current | ||
| lgpEnvMinDesiredRoomAirTemperature OBJECT-IDENTITY The minimum desired room air temperature. If the room air temperature falls below this set point, the unit will reduce the cooling. | 1.3.6.1.4.1.476.1.42.3.4.1.1.22 | current | ||
| lgpEnvDewPointTemperatures OBJECT-IDENTITY This sub-tree identifies well-known dew point temperatures in the system. | 1.3.6.1.4.1.476.1.42.3.4.1.1.23 | current | ||
| lgpEnvInletDewPointTemperature OBJECT-IDENTITY Dew point temperature measured at the inlet of the unit. | 1.3.6.1.4.1.476.1.42.3.4.1.1.23.1 | current | ||
| lgpEnvTemperatureFahrenheit OBJECT-IDENTITY This sub-tree contains OIDs that are used to control and monitor temperature using the Fahrenheit temperature scale. | 1.3.6.1.4.1.476.1.42.3.4.1.2 | current | ||
| lgpEnvTemperatureSettingDegF OBJECT-TYPE The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegC' with the value converted to Celsius. | 1.3.6.1.4.1.476.1.42.3.4.1.2.1 | Integer32 | read-write | current |
| lgpEnvTemperatureToleranceDegF OBJECT-TYPE The acceptable variance from 'lgpEnvTemperatureSettingDegF', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegC' with the value converted to Celsius. | 1.3.6.1.4.1.476.1.42.3.4.1.2.2 | Integer32 | read-write | current |
| lgpEnvTemperatureTableDegF OBJECT-TYPE A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegC' where Fahrenheit values are converted to Celsius. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3 | not-accessible | current | |
| lgpEnvTemperatureEntryDegF OBJECT-TYPE This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegF'. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1 | not-accessible | current | |
| lgpEnvTemperatureIdDegF OBJECT-TYPE This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegF'. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.1 | Unsigned32 | read-only | current |
| lgpEnvTemperatureDescrDegF OBJECT-TYPE A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.2 | OBJECT IDENTIFIER | read-only | current |
| lgpEnvTemperatureMeasurementDegF OBJECT-TYPE The measured temperature value. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.3 | Integer32 | read-only | current |
| lgpEnvTemperatureHighThresholdDegF OBJECT-TYPE The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.4 | Integer32 | read-write | current |
| lgpEnvTemperatureLowThresholdDegF OBJECT-TYPE The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.5 | Integer32 | read-write | current |
| lgpEnvTemperatureSetPointDegF OBJECT-TYPE The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.6 | Integer32 | read-write | current |
| lgpEnvTemperatureDailyHighDegF OBJECT-TYPE The daily high temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.7 | Integer32 | read-only | current |
| lgpEnvTemperatureDailyLowDegF OBJECT-TYPE The daily low temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.8 | Integer32 | read-only | current |
| lgpEnvTempDailyHighTimeHourDegF OBJECT-TYPE The hours digit of the time corresponding to the daily high temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.9 | Integer32 (0..23) | read-only | current |
| lgpEnvTempDailyHighTimeMinuteDegF OBJECT-TYPE The minutes digit of the time corresponding to the daily high temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.10 | Integer32 (0..59) | read-only | current |
| lgpEnvTempDailyHighTimeSecondDegF OBJECT-TYPE The seconds digit of the time corresponding to the daily high temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.11 | Integer32 (0..59) | read-only | current |
| lgpEnvTempDailyLowTimeHourDegF OBJECT-TYPE The hours digit of the time corresponding to the daily low temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.12 | Integer32 (0..23) | read-only | current |
| lgpEnvTempDailyLowTimeMinuteDegF OBJECT-TYPE The minutes digit of the time corresponding to the daily low temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.13 | Integer32 (0..59) | read-only | current |
| lgpEnvTempDailyLowTimeSecondDegF OBJECT-TYPE The seconds digit of the time corresponding to the daily low temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.14 | Integer32 (0..59) | read-only | current |
| lgpEnvTemperatureMeasurementTenthsDegF OBJECT-TYPE The measured temperature value. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.50 | Integer32 | read-only | current |
| lgpEnvTemperatureHighThresholdTenthsDegF OBJECT-TYPE The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.51 | Integer32 | read-write | current |
| lgpEnvTemperatureLowThresholdTenthsDegF OBJECT-TYPE The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.52 | Integer32 | read-write | current |
| lgpEnvTemperatureSetPointTenthsDegF OBJECT-TYPE The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.53 | Integer32 | read-write | current |
| lgpEnvTemperatureDeadBandTenthsDegF OBJECT-TYPE The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.60 | Integer32 | read-write | current |
| lgpEnvTempHeatingPropBandTenthsDegF OBJECT-TYPE The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where heating will be proportionally controlled. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.61 | Integer32 | read-write | current |
| lgpEnvTempCoolingPropBandTenthsDegF OBJECT-TYPE The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where cooling will be proportionally controlled. | 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.62 | Integer32 | read-write | current |
| lgpEnvTemperatureDeadbandRangeDegF OBJECT-TYPE The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. | 1.3.6.1.4.1.476.1.42.3.4.1.2.4 | Integer32 | read-write | current |
| lgpEnvTemperatureCelsius OBJECT-IDENTITY This sub-tree contains OIDs that are used to control and monitor temperature using the Celsius temperature scale. | 1.3.6.1.4.1.476.1.42.3.4.1.3 | current | ||
| lgpEnvTemperatureSettingDegC OBJECT-TYPE The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegF' with the value converted to Fahrenheit. | 1.3.6.1.4.1.476.1.42.3.4.1.3.1 | Integer32 | read-write | current |
| lgpEnvTemperatureToleranceDegC OBJECT-TYPE The acceptable variance from 'lgpEnvTemperatureSettingDegC', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegF' with the value converted to Fahrenheit. | 1.3.6.1.4.1.476.1.42.3.4.1.3.2 | Integer32 | read-write | current |
| lgpEnvTemperatureTableDegC OBJECT-TYPE A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegF' where Celsius values are converted to Fahrenheit. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3 | not-accessible | current | |
| lgpEnvTemperatureEntryDegC OBJECT-TYPE This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegC'. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1 | not-accessible | current | |
| lgpEnvTemperatureIdDegC OBJECT-TYPE This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegC'. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.1 | Unsigned32 | read-only | current |
| lgpEnvTemperatureDescrDegC OBJECT-TYPE A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.2 | OBJECT IDENTIFIER | read-only | current |
| lgpEnvTemperatureMeasurementDegC OBJECT-TYPE The measured temperature value. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.3 | Integer32 | read-only | current |
| lgpEnvTemperatureHighThresholdDegC OBJECT-TYPE The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.4 | Integer32 | read-write | current |
| lgpEnvTemperatureLowThresholdDegC OBJECT-TYPE The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.5 | Integer32 | read-write | current |
| lgpEnvTemperatureSetPointDegC OBJECT-TYPE The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.6 | Integer32 | read-write | current |
| lgpEnvTemperatureDailyHighDegC OBJECT-TYPE The daily high temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.7 | Integer32 | read-only | current |
| lgpEnvTemperatureDailyLowDegC OBJECT-TYPE The daily low temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.8 | Integer32 | read-only | current |
| lgpEnvTempDailyHighTimeHourDegC OBJECT-TYPE The hours digit of the time corresponding to the daily high temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.9 | Integer32 (0..23) | read-only | current |
| lgpEnvTempDailyHighTimeMinuteDegC OBJECT-TYPE The minutes digit of the time corresponding to the daily high temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.10 | Integer32 (0..59) | read-only | current |
| lgpEnvTempDailyHighTimeSecondDegC OBJECT-TYPE The seconds digit of the time corresponding to the daily high temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.11 | Integer32 (0..59) | read-only | current |
| lgpEnvTempDailyLowTimeHourDegC OBJECT-TYPE The hours digit of the time corresponding to the daily low temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.12 | Integer32 (0..23) | read-only | current |
| lgpEnvTempDailyLowTimeMinuteDegC OBJECT-TYPE The minutes digit of the time corresponding to the daily low temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.13 | Integer32 (0..59) | read-only | current |
| lgpEnvTempDailyLowTimeSecondDegC OBJECT-TYPE The seconds digit of the time corresponding to the daily low temperature measurement. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.14 | Integer32 (0..59) | read-only | current |
| lgpEnvTemperatureMeasurementTenthsDegC OBJECT-TYPE The measured temperature value. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.50 | Integer32 | read-only | current |
| lgpEnvTemperatureHighThresholdTenthsDegC OBJECT-TYPE The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.51 | Integer32 | read-write | current |
| lgpEnvTemperatureLowThresholdTenthsDegC OBJECT-TYPE The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.52 | Integer32 | read-write | current |
| lgpEnvTemperatureSetPointTenthsDegC OBJECT-TYPE The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.53 | Integer32 | read-write | current |
| lgpEnvTemperatureDeadBandTenthsDegC OBJECT-TYPE The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.60 | Integer32 | read-write | current |
| lgpEnvTempHeatingPropBandTenthsDegC OBJECT-TYPE The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where heating will be proportionally controlled. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.61 | Integer32 | read-write | current |
| lgpEnvTempCoolingPropBandTenthsDegC OBJECT-TYPE The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where cooling will be proportionally controlled. | 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.62 | Integer32 | read-write | current |
| lgpEnvTemperatureDeadbandRangeDegC OBJECT-TYPE The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. | 1.3.6.1.4.1.476.1.42.3.4.1.3.4 | Integer32 | read-write | current |
| lgpEnvTemperatureControlMode OBJECT-TYPE A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature object that is used for control. | 1.3.6.1.4.1.476.1.42.3.4.1.4 | OBJECT IDENTIFIER | read-only | current |
| lgpEnvHumidity OBJECT-IDENTITY This sub-tree is used to register Liebert humidity object identifiers. | 1.3.6.1.4.1.476.1.42.3.4.2 | current | ||
| lgpEnvHumidityWellKnown OBJECT-IDENTITY Liebert well known humidity objects are defined by OIDs that reside in this sub-tree. | 1.3.6.1.4.1.476.1.42.3.4.2.1 | current | ||
| lgpEnvControlHumidity OBJECT-IDENTITY Humidity measurement used as control feedback. | 1.3.6.1.4.1.476.1.42.3.4.2.1.1 | current | ||
| lgpEnvReturnAirHumidity OBJECT-IDENTITY Humidity measurement of return air. | 1.3.6.1.4.1.476.1.42.3.4.2.1.2 | current | ||
| lgpEnvSupplyAirHumidity OBJECT-IDENTITY Humidity measurement of supply air. | 1.3.6.1.4.1.476.1.42.3.4.2.1.3 | current | ||
| lgpEnvValueAmbientHumidity OBJECT-IDENTITY Humidity outside enclosure. | 1.3.6.1.4.1.476.1.42.3.4.2.1.4 | current | ||
| lgpEnvHumidityRelative OBJECT-IDENTITY This sub-tree contains OIDs that are used to control and monitor relative humidity. | 1.3.6.1.4.1.476.1.42.3.4.2.2 | current | ||
| lgpEnvHumiditySettingRel OBJECT-TYPE The humidity setting used to control the well known humidity point. | 1.3.6.1.4.1.476.1.42.3.4.2.2.1 | Integer32 | read-write | current |
| lgpEnvHumidityToleranceRel OBJECT-TYPE Acceptable variance from lgpEnvHumiditySettingRel, without initiating a control action. | 1.3.6.1.4.1.476.1.42.3.4.2.2.2 | Integer32 | read-write | current |
| lgpEnvHumidityTableRel OBJECT-TYPE A list of humidity table entries. The table contains zero, one, or many rows, depending upon the number of humidity objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3 | not-accessible | current | |
| lgpEnvHumidityEntryRel OBJECT-TYPE This entry defines the contents of the rows for the table 'lgpEnvHumidityTableRel'. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1 | not-accessible | current | |
| lgpEnvHumidityIdRel OBJECT-TYPE This OID is used as an index to identify a row in the table 'lgpEnvHumidityTableRel'. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.1 | Unsigned32 | read-only | current |
| lgpEnvHumidityDescrRel OBJECT-TYPE A reference to a humidity description object. The object referenced should not be accessible, but rather be used to provide a unique description of the humidity. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.2 | OBJECT IDENTIFIER | read-only | current |
| lgpEnvHumidityMeasurementRel OBJECT-TYPE The measured humidity value. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.3 | Integer32 | read-only | current |
| lgpEnvHumidityHighThresholdRel OBJECT-TYPE The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.4 | Integer32 | read-write | current |
| lgpEnvHumidityLowThresholdRel OBJECT-TYPE The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.5 | Integer32 | read-write | current |
| lgpEnvHumiditySetPoint OBJECT-TYPE The humidity setting used to control the well known humidity object 'lgpEnvHumidityDescrRel'. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.6 | Integer32 | read-write | current |
| lgpEnvHumidityDailyHigh OBJECT-TYPE The daily high relative humidity measurement. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.7 | Integer32 | read-only | current |
| lgpEnvHumidityDailyLow OBJECT-TYPE The daily low relative humidity measurement. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.8 | Integer32 | read-only | current |
| lgpEnvHumidityDailyHighTimeHour OBJECT-TYPE The hours digit of the time corresponding to the daily high humidity measurement. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.9 | Integer32 (0..23) | read-only | current |
| lgpEnvHumidityDailyHighTimeMinute OBJECT-TYPE The minutes digit of the time corresponding to the daily high humidity measurement. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.10 | Integer32 (0..59) | read-only | current |
| lgpEnvHumidityDailyHighTimeSecond OBJECT-TYPE The seconds digit of the time corresponding to the daily high humidity measurement. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.11 | Integer32 (0..59) | read-only | current |
| lgpEnvHumidityDailyLowTimeHour OBJECT-TYPE The hours digit of the time corresponding to the daily low humidity measurement. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.12 | Integer32 (0..23) | read-only | current |
| lgpEnvHumidityDailyLowTimeMinute OBJECT-TYPE The minutes digit of the time corresponding to the daily low humidity measurement. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.13 | Integer32 (0..59) | read-only | current |
| lgpEnvHumidityDailyLowTimeSecond OBJECT-TYPE The seconds digit of the time corresponding to the daily low humidity measurement. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.14 | Integer32 (0..59) | read-only | current |
| lgpEnvHumidityDeadBand OBJECT-TYPE The deadband region around the setpoint value (lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.15 | Integer32 | read-write | current |
| lgpEnvHumidifyPropBand OBJECT-TYPE The proportional region below the setpoint value (lgpEnvHumiditySetPoint) where humidifying will be proportionally controlled. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.16 | Integer32 | read-write | current |
| lgpEnvDehumidifyPropBand OBJECT-TYPE The proportional region above the setpoint value (lgpEnvHumiditySetPoint) where dehumidifying will be proportionally controlled. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17 | Integer32 | read-write | current |
| lgpEnvHumidityMeasurementRelTenths OBJECT-TYPE The measured humidity value. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.50 | Integer32 | read-only | current |
| lgpEnvHumidityHighThresholdRelTenths OBJECT-TYPE The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.51 | Integer32 | read-write | current |
| lgpEnvHumidityLowThresholdRelTenths OBJECT-TYPE The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification. | 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.52 | Integer32 | read-write | current |
| lgpEnvHumidityDeadbandRange OBJECT-TYPE The allowable deviation above and below the humidity set point used to create a no control region, a dead-band, where humidifying and dehumidifying control are disabled. | 1.3.6.1.4.1.476.1.42.3.4.2.2.4 | Integer32 | read-write | current |
| lgpEnvState OBJECT-IDENTITY This sub-tree is used to register Liebert environmental state object identifiers. | 1.3.6.1.4.1.476.1.42.3.4.3 | current | ||
| lgpEnvStateSystem OBJECT-TYPE The present state of the system. | 1.3.6.1.4.1.476.1.42.3.4.3.1 | INTEGER {on(1), off(2), standby(3)} | read-only | current |
| lgpEnvStateCooling OBJECT-TYPE The present state of the cooling subsystem. | 1.3.6.1.4.1.476.1.42.3.4.3.2 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateHeating OBJECT-TYPE The present state of the heating subsystem. | 1.3.6.1.4.1.476.1.42.3.4.3.3 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateHumidifying OBJECT-TYPE The present state of the humidifier subsystem. | 1.3.6.1.4.1.476.1.42.3.4.3.4 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateDehumidifying OBJECT-TYPE The present state of the dehumidifier subsystem | 1.3.6.1.4.1.476.1.42.3.4.3.5 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateEconoCycle OBJECT-TYPE The present state of the Econ-o-cycle subsystem. | 1.3.6.1.4.1.476.1.42.3.4.3.6 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateFan OBJECT-TYPE The present state of the system fan. | 1.3.6.1.4.1.476.1.42.3.4.3.7 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateGeneralAlarmOutput OBJECT-TYPE The present state of the general alarm output. This indicates if an alarm is active in the system. | 1.3.6.1.4.1.476.1.42.3.4.3.8 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateCoolingCapacity OBJECT-TYPE The percentage of the cooling capacity presently in use. | 1.3.6.1.4.1.476.1.42.3.4.3.9 | Unsigned32 | read-only | current |
| lgpEnvStateHeatingCapacity OBJECT-TYPE The percentage of the heating capacity presently in use. | 1.3.6.1.4.1.476.1.42.3.4.3.10 | Unsigned32 | read-only | current |
| lgpEnvStateAudibleAlarm OBJECT-TYPE The present state of the audible alarm output. | 1.3.6.1.4.1.476.1.42.3.4.3.11 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateCoolingUnits OBJECT-IDENTITY This sub-tree contains OIDs that are used to indicate the status of cooling units. | 1.3.6.1.4.1.476.1.42.3.4.3.12 | current | ||
| lgpEnvStateCoolingUnit1 OBJECT-TYPE The present state of cooling unit 1. | 1.3.6.1.4.1.476.1.42.3.4.3.12.2 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateCoolingUnit2 OBJECT-TYPE The present state of cooling unit 2. | 1.3.6.1.4.1.476.1.42.3.4.3.12.3 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateCoolingUnit3 OBJECT-TYPE The present state of cooling unit 3. | 1.3.6.1.4.1.476.1.42.3.4.3.12.4 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateCoolingUnit4 OBJECT-TYPE The present state of cooling unit 4. | 1.3.6.1.4.1.476.1.42.3.4.3.12.5 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateHeatingUnits OBJECT-IDENTITY This sub-tree contains OIDs that are used to indicate the status of heating units. | 1.3.6.1.4.1.476.1.42.3.4.3.13 | current | ||
| lgpEnvStateHeatingUnit1 OBJECT-TYPE The present state of heating unit 1. | 1.3.6.1.4.1.476.1.42.3.4.3.13.2 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateHeatingUnit2 OBJECT-TYPE The present state of heating unit 2. | 1.3.6.1.4.1.476.1.42.3.4.3.13.3 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateHeatingUnit3 OBJECT-TYPE The present state of heating unit 3. | 1.3.6.1.4.1.476.1.42.3.4.3.13.4 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateHeatingUnit4 OBJECT-TYPE The present state of heating unit 4. | 1.3.6.1.4.1.476.1.42.3.4.3.13.5 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateOperatingReason OBJECT-TYPE The reason for the current operating state of the system. | 1.3.6.1.4.1.476.1.42.3.4.3.14 | INTEGER {none(1), localUser(2), alarm(3), schedule(4), remoteUser(5), externalDevice(6), localDisplay(7)} | read-only | current |
| lgpEnvStateOperatingMode OBJECT-TYPE The present operating mode of the system. | 1.3.6.1.4.1.476.1.42.3.4.3.15 | INTEGER {auto(1), manual(2)} | read-only | current |
| lgpEnvStateFanCapacity OBJECT-TYPE The percentage of the fan capacity presently in use. | 1.3.6.1.4.1.476.1.42.3.4.3.16 | Unsigned32 | read-only | current |
| lgpEnvStateFreeCoolingCapacity OBJECT-TYPE The percentage of the free cooling capacity presently in use. | 1.3.6.1.4.1.476.1.42.3.4.3.17 | Unsigned32 | read-only | current |
| lgpEnvStateDehumidifyingCapacity OBJECT-TYPE The percentage of the dehumidifying capacity presently in use. | 1.3.6.1.4.1.476.1.42.3.4.3.18 | Unsigned32 | read-only | current |
| lgpEnvStateHumidifyingCapacity OBJECT-TYPE The percentage of the humidifying capacity presently in use. | 1.3.6.1.4.1.476.1.42.3.4.3.19 | Unsigned32 | read-only | current |
| lgpEnvStateFreeCooling OBJECT-TYPE The present state of the system free cooling process of heat exchange. When 'off', free cooling is not in use. When 'on' free cooling is in use. When 'start', free cooling is preparing to turn on. When 'unavailable', the state information is unavailable. | 1.3.6.1.4.1.476.1.42.3.4.3.20 | INTEGER {on(1), off(2), start(3), unavailable(4)} | read-only | current |
| lgpEnvStateElectricHeater OBJECT-TYPE The present state of the electric heaters. | 1.3.6.1.4.1.476.1.42.3.4.3.21 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateHotWater OBJECT-TYPE The present state of hot water system. | 1.3.6.1.4.1.476.1.42.3.4.3.22 | INTEGER {on(1), off(2)} | read-only | current |
| lgpEnvStateOperatingEfficiency OBJECT-TYPE The ratio of cooling energy provided to the amount of total energy being used. | 1.3.6.1.4.1.476.1.42.3.4.3.23 | Unsigned32 | read-only | current |
| lgpEnvComponentStateTable OBJECT-TYPE This table contains a list of the units components that have a state associated with them. The table contains zero, one, or more rows, depending upon the number of components associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored. | 1.3.6.1.4.1.476.1.42.3.4.3.50 | not-accessible | current | |
| lgpEnvComponentStateEntry OBJECT-TYPE This entry defines the attributes to be populated in the various columns of the 'lgpEnvComponentStateTable'. | 1.3.6.1.4.1.476.1.42.3.4.3.50.1 | not-accessible | current | |
| lgpEnvComponentStateIndex OBJECT-TYPE This is the index indicating the nth element of the table. | 1.3.6.1.4.1.476.1.42.3.4.3.50.1.1 | Unsigned32 | not-accessible | current |
| lgpEnvComponentStateDescr OBJECT-TYPE A reference to a component description object. The object referenced should not be accessible, but rather be used to provide a unique description of the component being described in the row of the table. | 1.3.6.1.4.1.476.1.42.3.4.3.50.1.2 | OBJECT IDENTIFIER | read-only | current |
| lgpEnvComponentState OBJECT-TYPE not-specified The state of the component is unknown. on The component is on. off The component is off. | 1.3.6.1.4.1.476.1.42.3.4.3.50.1.3 | INTEGER {not-specified(0), on(1), off(2)} | read-only | current |
| lgpEnvValveTable OBJECT-TYPE This table contains a list of the unit valves that have information associated with them. The table contains zero, one, or more rows, depending upon the number of valves associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored. | 1.3.6.1.4.1.476.1.42.3.4.3.70 | not-accessible | current | |
| lgpEnvValveEntry OBJECT-TYPE This entry defines the attributes to be populated in the various columns of the 'lgpEnvValveTable'. | 1.3.6.1.4.1.476.1.42.3.4.3.70.1 | not-accessible | current | |
| lgpEnvValveIndex OBJECT-TYPE This is the index indicating the nth element of the table. | 1.3.6.1.4.1.476.1.42.3.4.3.70.1.1 | Unsigned32 | not-accessible | current |
| lgpEnvValveDescr OBJECT-TYPE A reference to a valve description object. The object referenced should not be accessible, but rather be used to provide a unique description of the valve being described in the row of the table. | 1.3.6.1.4.1.476.1.42.3.4.3.70.1.2 | OBJECT IDENTIFIER | read-only | current |
| lgpEnvValveState OBJECT-TYPE not-specified The state of the component is unknown. open The valve is open. off The valve is closed. | 1.3.6.1.4.1.476.1.42.3.4.3.70.1.3 | INTEGER {not-specified(0), open(1), closed(2)} | read-only | current |
| lgpEnvValvePositionTenths OBJECT-TYPE This gives a value describing the position of the valve. | 1.3.6.1.4.1.476.1.42.3.4.3.70.1.20 | Unsigned32 | read-only | current |
| lgpEnvConfig OBJECT-IDENTITY This sub-tree is used to register Liebert environmental configuration object identifiers. | 1.3.6.1.4.1.476.1.42.3.4.4 | current | ||
| lgpEnvConfigReheatLockout OBJECT-TYPE If locked-out the reheats will not operate even if controller calls for its operation. | 1.3.6.1.4.1.476.1.42.3.4.4.1 | INTEGER {lockedOut(1), notLockedOut(2)} | read-write | current |
| lgpEnvConfigHumLockout OBJECT-TYPE If locked-out the humidifier will not operate even if controller calls for its operation. | 1.3.6.1.4.1.476.1.42.3.4.4.2 | INTEGER {lockedOut(1), notLockedOut(2)} | read-write | current |
| lgpEnvConfigRestartDelay OBJECT-TYPE When utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is restored. A Restart Delay of zero denotes a manual restart, the unit will NOT automatically restart. | 1.3.6.1.4.1.476.1.42.3.4.4.4 | Unsigned32 | read-write | current |
| lgpEnvConfigRemoteShutdown OBJECT-TYPE When in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing. | 1.3.6.1.4.1.476.1.42.3.4.4.7 | INTEGER {disabled(1), enabled(2)} | read-write | current |
| lgpEnvConfigCoolingServiceInterval OBJECT-TYPE The amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this value an lgpConditionServiceCooling will be activated. Once service has been completed the cooling service timer should be reset to 0. | 1.3.6.1.4.1.476.1.42.3.4.4.8 | Unsigned32 | read-write | current |
| lgpEnvConfigHumidifierServiceInterval OBJECT-TYPE The amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this value an lgpConditionServiceHumidifier will be activated. Once service has been completed humidifier service timer should be reset to 0. | 1.3.6.1.4.1.476.1.42.3.4.4.9 | Unsigned32 | read-write | current |
| lgpEnvConfigFilterServiceInterval OBJECT-TYPE The amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this value an lgpConditionChangeFilter will be activated. Once service has been completed the filter service timer should be reset to 0. | 1.3.6.1.4.1.476.1.42.3.4.4.10 | Unsigned32 | read-write | current |
| lgpEnvConfigSleepModeDeadbandRangeDegC OBJECT-TYPE The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation. | 1.3.6.1.4.1.476.1.42.3.4.4.11 | Integer32 | read-write | current |
| lgpEnvConfigSleepModeDeadbandRangeDegF OBJECT-TYPE The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation. | 1.3.6.1.4.1.476.1.42.3.4.4.12 | Integer32 | read-write | current |
| lgpEnvConfigSupplyTempLowLimitDegF OBJECT-TYPE The minimum allowable supply temperature. | 1.3.6.1.4.1.476.1.42.3.4.4.13 | Integer32 | read-write | current |
| lgpEnvConfigSupplyTempLowLimitDegC OBJECT-TYPE The minimum allowable supply temperature. | 1.3.6.1.4.1.476.1.42.3.4.4.14 | Integer32 | read-write | current |
| lgpEnvConfigTemperatureIntegTime OBJECT-TYPE The value used as the integration factor in the proportional integral derivative (PID) temperature calculation. | 1.3.6.1.4.1.476.1.42.3.4.4.15 | Integer32 | read-write | current |
| lgpEnvConfigLocalTemperatureUnit OBJECT-TYPE The local temperature unit of the system. | 1.3.6.1.4.1.476.1.42.3.4.4.16 | INTEGER {degC(1), degF(2)} | read-write | current |
| lgpEnvConfigSleepMode OBJECT-TYPE The configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day. If 'disabled', the device will operate continually and not sleep at all. If 'auto', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day unless the environmental conditions fall outside the desired operation ranges. | 1.3.6.1.4.1.476.1.42.3.4.4.17 | INTEGER {enabled(1), disabled(2), auto(3)} | read-write | current |
| lgpEnvConfigHumidityIntegTime OBJECT-TYPE The value used as the integration factor in the proportional integral derivative (PID) humidity calculation. | 1.3.6.1.4.1.476.1.42.3.4.4.18 | Integer32 | read-write | current |
| lgpEnvConfigFreecoolingDeltaDegF OBJECT-TYPE The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling. | 1.3.6.1.4.1.476.1.42.3.4.4.19 | Integer32 | read-write | current |
| lgpEnvConfigFreecoolingDeltaDegC OBJECT-TYPE The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling. | 1.3.6.1.4.1.476.1.42.3.4.4.20 | Integer32 | read-write | current |
| lgpEnvConfigSupplyTempLowLimit OBJECT-TYPE The system configuration parameter to enable or disable the supply air low temperature limit. | 1.3.6.1.4.1.476.1.42.3.4.4.21 | INTEGER {disabled(1), enabled(2)} | read-write | current |
| lgpEnvConfigSensorEventsStandard OBJECT-TYPE The system configuration parameter to enable or disable the standard sensor events. | 1.3.6.1.4.1.476.1.42.3.4.4.22 | INTEGER {disabled(1), enabled(2)} | read-write | current |
| lgpEnvConfigSensorEvents1 OBJECT-TYPE The system configuration parameter to enable or disable sensor 1 events. | 1.3.6.1.4.1.476.1.42.3.4.4.23 | INTEGER {disabled(1), enabled(2)} | read-write | current |
| lgpEnvConfigSleepModeDeadbandRange OBJECT-TYPE The system configuration parameter to enable or disable the use of the sleep interval dead-band range in the sleep mode temperature calculations and control algorithm. | 1.3.6.1.4.1.476.1.42.3.4.4.24 | INTEGER {disabled(1), enabled(2)} | read-write | current |
| lgpEnvConfigAutoConfiguration OBJECT-TYPE The system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and humidity control parameters. | 1.3.6.1.4.1.476.1.42.3.4.4.25 | INTEGER {disabled(1), enabled(2)} | read-write | current |
| lgpEnvConfigDeltaGlycolType OBJECT-TYPE The system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cooling. If 'disabled', the system will use the valve temperature to initiate free cooling. If 'contact', a input to the system will initiate free cooling. If 'valve', the system compares the room and glycol temperature differential with the valve temperature to initiate free cooling. If the temperature differential is greater than or equal to the valve temperature, free cooling will be initiated. | 1.3.6.1.4.1.476.1.42.3.4.4.26 | INTEGER {disabled(1), contact(2), value(3)} | read-write | current |
| lgpEnvConfigChillWaterControl OBJECT-TYPE The system configuration parameter to enable or disable the minimum chill water temperature control. | 1.3.6.1.4.1.476.1.42.3.4.4.27 | INTEGER {disabled(1), enabled(2)} | read-write | current |
| lgpEnvConfigInfaredFlushRate OBJECT-TYPE The Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan when the 'humidifier is in operation. | 1.3.6.1.4.1.476.1.42.3.4.4.28 | Unsigned32 | read-write | current |
| lgpEnvConfigHumidityControl OBJECT-TYPE The present configured state of the automatic humidity compensation algorithm. | 1.3.6.1.4.1.476.1.42.3.4.4.29 | INTEGER {relative(1), compensated(2), predictive(3)} | read-write | current |
| lgpEnvConfigCompressorLockout OBJECT-TYPE The system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for their operation. | 1.3.6.1.4.1.476.1.42.3.4.4.30 | INTEGER {lockedOut(1), notLockedOut(2)} | read-write | current |
| lgpEnvConfigReheatAndHumidifierLockout OBJECT-TYPE The system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the controller calls for their operation. | 1.3.6.1.4.1.476.1.42.3.4.4.31 | INTEGER {lockedOut(1), notLockedOut(2)} | read-write | current |
| lgpEnvOperationalTimeTable OBJECT-TYPE A list of environmental operational time ranges for a given environmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistics' group. This table contains zero, one, or many rows, depending upon the number of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. | 1.3.6.1.4.1.476.1.42.3.4.4.32 | not-accessible | current | |
| lgpEnvOperationalTimeEntry OBJECT-TYPE This entry defines the contents of the columns for the table 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.4.32.1 | not-accessible | current | |
| lgpEnvOperationTimeIndex OBJECT-TYPE This is the index indicating the nth element of the table. | 1.3.6.1.4.1.476.1.42.3.4.4.32.1.1 | Unsigned32 | not-accessible | current |
| lgpEnvOperationTimePoint OBJECT-TYPE An OID representing a well known operation point. These object identifiers can indicate a point, location, or mode of an operation for which a measurement is recorded. The OID's name usually implies a location of the measurement point such as 'fan', 'compressor', etc. | 1.3.6.1.4.1.476.1.42.3.4.4.32.1.2 | OBJECT IDENTIFIER | read-only | current |
| lgpEnvOperationTimeSubID OBJECT-TYPE This is a sub identifier for the 'lgpEnvOperationPoint'. It indicates the instance number of the well known operation point. For example, a system could have two fans installed. This variable would identify fan 1 with a lgpEnvOperationSubID equal to 1 and fan 2 with a lgpEnvOperationSubID equal to 2. | 1.3.6.1.4.1.476.1.42.3.4.4.32.1.3 | Integer32 | read-only | current |
| lgpEnvOperationTimeUnit OBJECT-TYPE An OID representing a well known operation time unit type. These object identifiers indicate the units of the operation time. The OID's name usually implies a measurement type such as 'lgpEnvHours', etc. | 1.3.6.1.4.1.476.1.42.3.4.4.32.1.4 | OBJECT IDENTIFIER | read-only | current |
| lgpEnvOperationTimeValue OBJECT-TYPE The actual operation time value of the 'lgpEnvOperationTimePoint'. If multiple operation times are available for a 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them. | 1.3.6.1.4.1.476.1.42.3.4.4.32.1.5 | Integer32 | read-write | current |
| lgpEnvOperationTimeHighWarning OBJECT-TYPE The high warning time of the operation designated by the 'lgpEnvOperationTimePoint'. If operation times are available at a single 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them. | 1.3.6.1.4.1.476.1.42.3.4.4.32.1.6 | Integer32 | read-write | current |
| lgpEnvConfigTempControlAlgorithm OBJECT-TYPE Selects the algorithm for controlling temperature. | 1.3.6.1.4.1.476.1.42.3.4.4.33 | INTEGER {pi(1), pid(2), intelligent(3), proportional(4)} | read-write | current |
| lgpEnvConfigFanSpeedMode OBJECT-TYPE Changes the function of the fan speed output. If auto, then the fan speed is modulated. If manual, the fan speed output follows lgpEnvConfigFanSpeedCapacity. | 1.3.6.1.4.1.476.1.42.3.4.4.34 | INTEGER {manual(1), auto(2)} | read-write | current |
| lgpEnvConfigFanSpeedCapacity OBJECT-TYPE Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ranges may differ from unit to unit). | 1.3.6.1.4.1.476.1.42.3.4.4.35 | Unsigned32 | read-write | current |
| lgpEnvConfigBmsResetTimer OBJECT-TYPE The current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to continue controlling the fan speed, it must reset this timer. Typical values range from 0 to 120 minutes (actual valid ranges may differ from unit to unit). | 1.3.6.1.4.1.476.1.42.3.4.4.36 | Unsigned32 | read-write | current |
| lgpEnvConfigDisableSensorOffsetDegC OBJECT-TYPE If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used. | 1.3.6.1.4.1.476.1.42.3.4.4.37 | Integer32 | read-write | current |
| lgpEnvConfigDisableSensorOffsetDegF OBJECT-TYPE If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used. | 1.3.6.1.4.1.476.1.42.3.4.4.38 | Integer32 | read-write | current |
| lgpEnvConfigCabinetSensorAlarms OBJECT-TYPE Enable or Disable Cabinet Sensor Alarms. | 1.3.6.1.4.1.476.1.42.3.4.4.39 | INTEGER {disabled(0), enabled(1)} | read-write | current |
| lgpEnvConfigAirTemperatureControlSensor OBJECT-TYPE Sensor from which air temperature measurements will be used for cooling and heating control. | 1.3.6.1.4.1.476.1.42.3.4.4.42 | INTEGER {supply(1), remote(2), return(3)} | read-write | current |
| lgpEnvConfigFanSpeedControlSensor OBJECT-TYPE Sensor from which air temperature measurements will be used for fan speed control. | 1.3.6.1.4.1.476.1.42.3.4.4.43 | INTEGER {supply(1), remote(2), return(3)} | read-write | current |
| lgpEnvConfigMinFanSpeed OBJECT-TYPE Sets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'. | 1.3.6.1.4.1.476.1.42.3.4.4.44 | Unsigned32 | read-write | current |
| lgpEnvConfigMaxFanSpeed OBJECT-TYPE Sets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'. | 1.3.6.1.4.1.476.1.42.3.4.4.45 | Unsigned32 | read-write | current |
| lgpEnvConfigFanSpeedPropBandDegC OBJECT-TYPE Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled. | 1.3.6.1.4.1.476.1.42.3.4.4.46 | Integer32 | read-write | current |
| lgpEnvConfigFanSpeedPropBandDegF OBJECT-TYPE Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled. | 1.3.6.1.4.1.476.1.42.3.4.4.47 | Integer32 | read-write | current |
| lgpEnvControl OBJECT-IDENTITY This sub-tree is used to register Liebert environmental control object identifiers. | 1.3.6.1.4.1.476.1.42.3.4.5 | current | ||
| lgpEnvControlShutdownAfterDelay OBJECT-TYPE Setting this object will shutdown (i.e., turn off) the system after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. When read, lgpEnvControlShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any lgpEnvControlShutdownAfterDelay already in effect. | 1.3.6.1.4.1.476.1.42.3.4.5.1 | Integer32 (-1..2147483647) | read-write | current |
| lgpEnvControlStartupAfterDelay OBJECT-TYPE Setting this object will start the system after the indicated number of seconds. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the system is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any lgpEnvControlStartupAfterDelay countdown in progress. When read, lgpEnvControlStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted. | 1.3.6.1.4.1.476.1.42.3.4.5.2 | Integer32 (-1..2147483647) | read-write | current |
| lgpEnvSleepIntervalTimeTable OBJECT-TYPE A sleep time interval table containing a list of the start and stop times to be used to take a device online or offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. | 1.3.6.1.4.1.476.1.42.3.4.5.3 | not-accessible | current | |
| lgpEnvSleepIntervalTimeEntry OBJECT-TYPE This entry defines the contents of the columns for the table 'lgpEnvSleepIntervalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.5.3.1 | not-accessible | current | |
| lgpEnvSleepTimeIndex OBJECT-TYPE This is the index indicating the row of the table 'lgpEnvSleepIntervalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.5.3.1.1 | Unsigned32 | not-accessible | current |
| lgpEnvSleepTimeSubID OBJECT-TYPE This is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'. It indicates the instance number of the 'lgpEnvSleepIntervalTimeEntry'. For example, a system could have two sleep intervals and the first interval's sub ID would be 1 and the second interval's sub ID would be 2. | 1.3.6.1.4.1.476.1.42.3.4.5.3.1.2 | Integer32 | read-only | current |
| lgpEnvSleepTimeStartHour OBJECT-TYPE This is the hours digit of the time when the system will be put online. | 1.3.6.1.4.1.476.1.42.3.4.5.3.1.3 | Integer32 (0..23) | read-write | current |
| lgpEnvSleepTimeStartMinute OBJECT-TYPE This is the minutes digit of the time when the system will be put online. | 1.3.6.1.4.1.476.1.42.3.4.5.3.1.4 | Integer32 (0..59) | read-write | current |
| lgpEnvSleepTimeStopHour OBJECT-TYPE This is the hours digit containing the time when the system will be taken offline. | 1.3.6.1.4.1.476.1.42.3.4.5.3.1.5 | Integer32 (0..23) | read-write | current |
| lgpEnvSleepTimeStopMinute OBJECT-TYPE This is the minutes digit containing the time when the system will be taken offline. | 1.3.6.1.4.1.476.1.42.3.4.5.3.1.6 | Integer32 (0..59) | read-write | current |
| lgpEnvSleepDayTable OBJECT-TYPE A sleep table containing a list of the days of the week the system will be offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. | 1.3.6.1.4.1.476.1.42.3.4.5.4 | not-accessible | current | |
| lgpEnvSleepDayEntry OBJECT-TYPE This entry defines the contents of the columns for the table 'lgpEnvSleepDayTable'. | 1.3.6.1.4.1.476.1.42.3.4.5.4.1 | not-accessible | current | |
| lgpEnvSleepDayIndex OBJECT-TYPE This is the index indicating the row of the table 'lgpEnvSleepDayTable'. | 1.3.6.1.4.1.476.1.42.3.4.5.4.1.1 | Unsigned32 | not-accessible | current |
| lgpEnvSleepDay OBJECT-TYPE This is a sub identifier for the day of the week within 'lgpEnvSleepDayTable'. | 1.3.6.1.4.1.476.1.42.3.4.5.4.1.2 | INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7)} | read-only | current |
| lgpEnvSleepAllDayEnabled OBJECT-TYPE The all day sleep functionality has been enabled for the corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'. | 1.3.6.1.4.1.476.1.42.3.4.5.4.1.3 | INTEGER {yes(1), no(2)} | read-write | current |
| lgpEnvStatistics OBJECT-IDENTITY This sub-tree is used to register Liebert environmental statistic object identifiers. | 1.3.6.1.4.1.476.1.42.3.4.6 | current | ||
| lgpEnvStatisticsComp1RunHr OBJECT-TYPE Accumulated run hours of compressor 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.1 | Unsigned32 | read-only | current |
| lgpEnvStatisticsComp2RunHr OBJECT-TYPE Accumulated run hours of compressor 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.2 | Unsigned32 | read-only | current |
| lgpEnvStatisticsFanRunHr OBJECT-TYPE Accumulated run hours of the main fan. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.3 | Unsigned32 | read-only | current |
| lgpEnvStatisticsHumRunHr OBJECT-TYPE Accumulated run hours of the humidifier. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.4 | Unsigned32 | read-only | current |
| lgpEnvStatisticsReheat1RunHr OBJECT-TYPE Accumulated run hours of reheat element 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.7 | Unsigned32 | read-only | current |
| lgpEnvStatisticsReheat2RunHr OBJECT-TYPE Accumulated run hours of reheat element 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.8 | Unsigned32 | read-only | current |
| lgpEnvStatisticsReheat3RunHr OBJECT-TYPE Accumulated run hours of reheat element 3. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.9 | Unsigned32 | read-only | current |
| lgpEnvStatisticsCoolingModeHrs OBJECT-TYPE Accumulated run hours while lgpEnvStateCooling is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.10 | Unsigned32 | read-only | current |
| lgpEnvStatisticsHeatingModeHrs OBJECT-TYPE Accumulated run hours while lgpEnvStateHeating is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.11 | Unsigned32 | read-only | current |
| lgpEnvStatisticsHumidifyModeHrs OBJECT-TYPE Accumulated run hours of the humidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.12 | Unsigned32 | read-only | current |
| lgpEnvStatisticsDehumidifyModeHrs OBJECT-TYPE Accumulated run hours of the dehumidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.13 | Unsigned32 | read-only | current |
| lgpEnvStatisticsHotGasRunHr OBJECT-TYPE Accumulated run hours of the hot gas system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.14 | Unsigned32 | read-only | current |
| lgpEnvStatisticsHotWaterRunHr OBJECT-TYPE Accumulated run hours of the hot water system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.15 | Unsigned32 | read-only | current |
| lgpEnvStatisticsFreeCoolRunHr OBJECT-TYPE Accumulated run hours of the free cooling process. This value may be duplicated in the 'lgpEnvOperationalTimeTable'. | 1.3.6.1.4.1.476.1.42.3.4.6.16 | Unsigned32 | read-only | current |
| lgpEnvStatisticsComp3RunHr OBJECT-TYPE Accumulated run hours of compressor 3. | 1.3.6.1.4.1.476.1.42.3.4.6.17 | Unsigned32 | read-only | current |
| lgpEnvStatisticsComp4RunHr OBJECT-TYPE Accumulated run hours of compressor 4. | 1.3.6.1.4.1.476.1.42.3.4.6.18 | Unsigned32 | read-only | current |
| lgpEnvPoints OBJECT-IDENTITY This sub-tree is used to register Liebert environmental point object identifiers. | 1.3.6.1.4.1.476.1.42.3.4.7 | current | ||
| lgpEnvWellKnownPoints OBJECT-IDENTITY This sub-tree registers well known Liebert Environmental Points. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied. | 1.3.6.1.4.1.476.1.42.3.4.7.1 | current | ||
| lgpEnvFanPoint OBJECT-IDENTITY This identifier represents a well known fan measurement point. | 1.3.6.1.4.1.476.1.42.3.4.7.1.1 | current | ||
| lgpEnvCompressorPoint OBJECT-IDENTITY This identifier represents a well known compressor measurement point. | 1.3.6.1.4.1.476.1.42.3.4.7.1.2 | current | ||
| lgpEnvElectricHeaterPoint OBJECT-IDENTITY This identifier represents a well known electric heater measurement point. | 1.3.6.1.4.1.476.1.42.3.4.7.1.3 | current | ||
| lgpEnvChilledWaterPoint OBJECT-IDENTITY This identifier represents a well known chilled water measurement point. | 1.3.6.1.4.1.476.1.42.3.4.7.1.4 | current | ||
| lgpEnvHumidifierPoint OBJECT-IDENTITY This identifier represents a well known humidifier measurement point. | 1.3.6.1.4.1.476.1.42.3.4.7.1.5 | current | ||
| lgpEnvDehumidifierPoint OBJECT-IDENTITY This identifier represents a well known dehumidifier measurement point. | 1.3.6.1.4.1.476.1.42.3.4.7.1.6 | current | ||
| lgpEnvFreeCoolingPoint OBJECT-IDENTITY This identifier represents a well known free-cooling measurement process. | 1.3.6.1.4.1.476.1.42.3.4.7.1.7 | current | ||
| lgpEnvHotWaterPoint OBJECT-IDENTITY This identifier represents a well known hot water measurement point. | 1.3.6.1.4.1.476.1.42.3.4.7.1.8 | current | ||
| lgpEnvHotGasPoint OBJECT-IDENTITY This identifier represents a well known hot gas measurement point. | 1.3.6.1.4.1.476.1.42.3.4.7.1.9 | current | ||
| lgpEnvBatteryCabinetPoint OBJECT-IDENTITY This identifier represents a well known cabinet point. To determine the cabinet being described in a multi-cabinet system, this point implements two additional indexes. The first index describes the module being supplied with battery power. The second index identifies the number of the battery cabinet, which is typically a sequential number. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpEnvBatteryCabinetPoint' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4 | 1.3.6.1.4.1.476.1.42.3.4.7.1.10 | current | ||
| lgpEnvPumpPoints OBJECT-IDENTITY This sub-tree identifies well-known pumps in the system. | 1.3.6.1.4.1.476.1.42.3.4.7.1.11 | current | ||
| lgpEnvPump1Point OBJECT-IDENTITY This identifier represents pump 1. | 1.3.6.1.4.1.476.1.42.3.4.7.1.11.1 | current | ||
| lgpEnvPump2Point OBJECT-IDENTITY This identifier represents pump 2. | 1.3.6.1.4.1.476.1.42.3.4.7.1.11.2 | current | ||
| lgpEnvCompressorPoints OBJECT-IDENTITY This sub-tree identifies well-known compressors in the system. | 1.3.6.1.4.1.476.1.42.3.4.7.1.12 | current | ||
| lgpEnvCompressor1Point OBJECT-IDENTITY This identifier represents compressor 1. | 1.3.6.1.4.1.476.1.42.3.4.7.1.12.1 | current | ||
| lgpEnvCompressor1APoint OBJECT-IDENTITY This identifier represents compressor 1A. | 1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.1 | current | ||
| lgpEnvCompressor1BPoint OBJECT-IDENTITY This identifier represents compressor 1B. | 1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.2 | current | ||
| lgpEnvCompressor2Point OBJECT-IDENTITY This identifier represents compressor 2. | 1.3.6.1.4.1.476.1.42.3.4.7.1.12.2 | current | ||
| lgpEnvCompressor2APoint OBJECT-IDENTITY This identifier represents compressor 2A. | 1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.1 | current | ||
| lgpEnvCompressor2BPoint OBJECT-IDENTITY This identifier represents compressor 2B. | 1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.2 | current | ||
| lgpEnvValvePoints OBJECT-IDENTITY This sub-tree identifies well-known valves in the system. | 1.3.6.1.4.1.476.1.42.3.4.7.1.13 | current | ||
| lgpEnvHotGasValve1Point OBJECT-IDENTITY This identifier represents hot gas valve 1. | 1.3.6.1.4.1.476.1.42.3.4.7.1.13.1 | current | ||
| lgpEnvHotGasValve2Point OBJECT-IDENTITY This identifier represents hot gas valve 2. | 1.3.6.1.4.1.476.1.42.3.4.7.1.13.2 | current | ||
| lgpEnvRemoteSensorStatisticPoints OBJECT-IDENTITY This sub-tree identifies well-known remote sensor statistics in the system. | 1.3.6.1.4.1.476.1.42.3.4.7.1.14 | current | ||
| lgpEnvRemoteSensorMinimumPoint OBJECT-IDENTITY This identifier represents the minimum value for remote sensor readings. | 1.3.6.1.4.1.476.1.42.3.4.7.1.14.1 | current | ||
| lgpEnvRemoteSensorMaximumPoint OBJECT-IDENTITY This identifier represents the maximum value for remote sensor readings. | 1.3.6.1.4.1.476.1.42.3.4.7.1.14.2 | current | ||
| lgpEnvRemoteSensorAveragePoint OBJECT-IDENTITY This identifier represents the average value for remote sensor readings. | 1.3.6.1.4.1.476.1.42.3.4.7.1.14.3 | current | ||
| lgpEnvUnits OBJECT-IDENTITY This sub-tree is used to register Liebert environmental unit object identifiers. | 1.3.6.1.4.1.476.1.42.3.4.8 | current | ||
| lgpEnvWellKnownUnits OBJECT-IDENTITY This sub-tree registers well known Liebert Environmental Units. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied. | 1.3.6.1.4.1.476.1.42.3.4.8.1 | current | ||
| lgpEnvHours OBJECT-IDENTITY This identifier represents well known time unit of hours. | 1.3.6.1.4.1.476.1.42.3.4.8.1.1 | current | ||
| lgpEnvRemoteSensors OBJECT-IDENTITY This sub-tree is used to register Liebert environmental remote sensor object identifiers. | 1.3.6.1.4.1.476.1.42.3.4.9 | current | ||
| lgpEnvRemoteSensorCalc OBJECT-TYPE Calculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control. | 1.3.6.1.4.1.476.1.42.3.4.9.1 | INTEGER {average(1), maximum(2)} | read-write | current |
| lgpEnvRemoteSensorTable OBJECT-TYPE This table contains a list of remote sensors attached to the environmental unit. The table contains zero, one, or more rows, depending upon the number of sensors attached to the unit. | 1.3.6.1.4.1.476.1.42.3.4.9.10 | not-accessible | current | |
| lgpEnvRemoteSensorEntry OBJECT-TYPE This entry defines the attributes to be populated in the various columns of the 'lgpEnvRemoteSensorTable'. | 1.3.6.1.4.1.476.1.42.3.4.9.10.1 | not-accessible | current | |
| lgpEnvRemoteSensorIndex OBJECT-TYPE This is the index indicating the nth element of the table. | 1.3.6.1.4.1.476.1.42.3.4.9.10.1.1 | Unsigned32 | not-accessible | current |
| lgpEnvRemoteSensorId OBJECT-TYPE This is the sensor number identifying the sensor. | 1.3.6.1.4.1.476.1.42.3.4.9.10.1.2 | Unsigned32 | read-only | current |
| lgpEnvRemoteSensorMode OBJECT-TYPE Function assigned to remote sensor. When set to control(2) the sensor will be used in calculation of remote sensor temperature which may be used for heating and cooling control. When set to disable(0) the remote sensor reading is not available. When set to reference(1) the remote sensor reading is available but not used for control. | 1.3.6.1.4.1.476.1.42.3.4.9.10.1.3 | INTEGER {disable(0), reference(1), control(2)} | read-write | current |
| lgpEnvRemoteSensorUsrLabel OBJECT-TYPE User assigned remote sensor label. | 1.3.6.1.4.1.476.1.42.3.4.9.10.1.4 | DisplayString | read-write | current |
| lgpEnvRemoteSensorTempMeasurementDegF OBJECT-TYPE Temperature measured at the temperature sensor reported in degrees Fahrenheit. | 1.3.6.1.4.1.476.1.42.3.4.9.10.1.5 | Integer32 | read-only | current |