MIBs Depot

LIEBERT-GP-ENVIRONMENTAL-MIB

Registered at
1.3.6.1.4.1.476.1.42.1.5.1
1.3.6.1.4.1.476.1.42.3.4.1
1.3.6.1.4.1.476.1.42.3.4.2
1.3.6.1.4.1.476.1.42.3.4.3
1.3.6.1.4.1.476.1.42.3.4.4
1.3.6.1.4.1.476.1.42.3.4.5
1.3.6.1.4.1.476.1.42.3.4.6
1.3.6.1.4.1.476.1.42.3.4.7
1.3.6.1.4.1.476.1.42.3.4.8
1.3.6.1.4.1.476.1.42.3.4.9
Last updated
2015-07-21 00:00
Organization
Liebert Corporation
Revisions
2008-11-17 00:00, 2008-07-02 00:00, 2008-01-10 00:00, 2007-05-29 00:00, 2006-08-15 00:00, 2006-02-22 00:00
Namespace
liebert
Source file
LIEBERT-GP-ENVIRONMENTAL-MIB
Digest
sha256:641ab7d92cbd07a20e4021a615ff1568d20596bf7cf2e9d823333b1b20e84035

Description

The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2015 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.

Contact

Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com Author: Gregory M. Hoge

Imports

FromSymbols
LIEBERT-GP-REGISTRATION-MIBlgpEnvironmental, liebertEnvironmentalModuleReg
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIInteger32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

LIEBERT-GP-ENVIRONMENTAL-MIB
LIEBERT-GP-REGISTRATION-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
lgpEnvTemperature
OBJECT-IDENTITY
This sub-tree is used to register Liebert temperature object identifiers.
1.3.6.1.4.1.476.1.42.3.4.1current
lgpEnvTemperatureWellKnown
OBJECT-IDENTITY
Liebert well known temperature objects are identified by OIDs that reside in this sub-tree.
1.3.6.1.4.1.476.1.42.3.4.1.1current
lgpEnvControlTemperature
OBJECT-IDENTITY
Temperature measurement used as control feedback.
1.3.6.1.4.1.476.1.42.3.4.1.1.1current
lgpEnvReturnAirTemperature
OBJECT-IDENTITY
Temperature measurement of return air.
1.3.6.1.4.1.476.1.42.3.4.1.1.2current
lgpEnvSupplyAirTemperature
OBJECT-IDENTITY
Temperature measurement of supply air.
1.3.6.1.4.1.476.1.42.3.4.1.1.3current
lgpAmbientTemperature
OBJECT-IDENTITY
Ambient temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.1.4current
lgpInverterTemperature
OBJECT-IDENTITY
Temperature measurement of the inverter.
1.3.6.1.4.1.476.1.42.3.4.1.1.5current
lgpBatteryTempterature
OBJECT-IDENTITY
Temperature measurement of the battery.
1.3.6.1.4.1.476.1.42.3.4.1.1.6current
lgpAcDcConverterTemperature
OBJECT-IDENTITY
Temperature measurement of the AC-to-DC Converter.
1.3.6.1.4.1.476.1.42.3.4.1.1.7current
lgpPfcTemperature
OBJECT-IDENTITY
Temperature measurement of the power factor correction circuitry.
1.3.6.1.4.1.476.1.42.3.4.1.1.8current
lgpTransformerTemperature
OBJECT-IDENTITY
Temperature measurement of the transformer.
1.3.6.1.4.1.476.1.42.3.4.1.1.9current
lgpLocalTemperature
OBJECT-IDENTITY
Temperature measurement of local temperature sensor.
1.3.6.1.4.1.476.1.42.3.4.1.1.10current
lgpLocal1Temperature
OBJECT-IDENTITY
Temperature and humidity measurements of Local Sensor 1.
1.3.6.1.4.1.476.1.42.3.4.1.1.10.1current
lgpLocal2Temperature
OBJECT-IDENTITY
Temperature and humidity measurements of Local Sensor 2.
1.3.6.1.4.1.476.1.42.3.4.1.1.10.2current
lgpLocal3Temperature
OBJECT-IDENTITY
Temperature and humidity measurements of Local Sensor 3.
1.3.6.1.4.1.476.1.42.3.4.1.1.10.3current
lgpDigitalScrollCompressorTemperature
OBJECT-IDENTITY
Temperature and humidity measurements of a digital Scroll Compressor.
1.3.6.1.4.1.476.1.42.3.4.1.1.11current
lgpDigitalScrollCompressor1Temperature
OBJECT-IDENTITY
Temperature and humidity measurements of a digital Scroll Compressor 1.
1.3.6.1.4.1.476.1.42.3.4.1.1.11.1current
lgpDigitalScrollCompressor2Temperature
OBJECT-IDENTITY
Temperature and humidity measurements of a digital Scroll Compressor 2.
1.3.6.1.4.1.476.1.42.3.4.1.1.11.2current
lgpChillWaterTemperature
OBJECT-IDENTITY
Temperature measurements of a chill water system.
1.3.6.1.4.1.476.1.42.3.4.1.1.12current
lgpCoolantTemperature
OBJECT-IDENTITY
Temperature measurements of an environmental system's coolant.
1.3.6.1.4.1.476.1.42.3.4.1.1.13current
lgpEnvEnclosureTemperatureSensors
OBJECT-IDENTITY
Enclosure temperature sensors
1.3.6.1.4.1.476.1.42.3.4.1.1.14current
lgpEnvEnclosureTemperatureSensor1
OBJECT-IDENTITY
Enclosure temperature sensor 1
1.3.6.1.4.1.476.1.42.3.4.1.1.14.1current
lgpEnvEnclosureTemperatureSensor2
OBJECT-IDENTITY
Enclosure temperature sensor 2
1.3.6.1.4.1.476.1.42.3.4.1.1.14.2current
lgpEnvEnclosureTemperatureSensor3
OBJECT-IDENTITY
Enclosure temperature sensor 3
1.3.6.1.4.1.476.1.42.3.4.1.1.14.3current
lgpEnvEnclosureTemperatureSensor4
OBJECT-IDENTITY
Enclosure temperature sensor 4
1.3.6.1.4.1.476.1.42.3.4.1.1.14.4current
lgpEnvValueAmbientRoomTemperature
OBJECT-IDENTITY
Temperature outside enclosure.
1.3.6.1.4.1.476.1.42.3.4.1.1.15current
lgpEnvDewPointTemperature
OBJECT-IDENTITY
The calculated temperature outside of the enclosure at which condensation is likely to occur.
1.3.6.1.4.1.476.1.42.3.4.1.1.16current
lgpEnvEnclosureTemperature
OBJECT-IDENTITY
Temperature inside of enclosure.
1.3.6.1.4.1.476.1.42.3.4.1.1.17current
lgpEnvAdjustedTemperature
OBJECT-IDENTITY
The current temperature set-point which is computed by the system and may be temporarily different from the user set-point because of external factors.
1.3.6.1.4.1.476.1.42.3.4.1.1.18current
lgpEnvExternalSensors
OBJECT-IDENTITY
External sensors to monitor environmental variables such as temperature and humidity
1.3.6.1.4.1.476.1.42.3.4.1.1.19current
lgpEnvExternalAirSensorA
OBJECT-IDENTITY
Temperature and humidity measurements from external air sensor A.
1.3.6.1.4.1.476.1.42.3.4.1.1.19.1current
lgpEnvExternalAirSensorADewPoint
OBJECT-IDENTITY
Dewpoint temperature for External Air Sensor A.
1.3.6.1.4.1.476.1.42.3.4.1.1.19.2current
lgpEnvExternalAirSensorB
OBJECT-IDENTITY
Temperature and humidity measurements from external air sensor B.
1.3.6.1.4.1.476.1.42.3.4.1.1.19.3current
lgpEnvExternalAirSensorBDewPoint
OBJECT-IDENTITY
Dewpoint temperature for External Air Sensor B.
1.3.6.1.4.1.476.1.42.3.4.1.1.19.4current
lgpEnvSupplyFluidTemperature
OBJECT-IDENTITY
The current temperature of the fluid being supplied.
1.3.6.1.4.1.476.1.42.3.4.1.1.20current
lgpEnvSupplyRefrigerantTemperature
OBJECT-IDENTITY
The current temperature of the refrigerant being supplied.
1.3.6.1.4.1.476.1.42.3.4.1.1.21current
lgpEnvMinDesiredRoomAirTemperature
OBJECT-IDENTITY
The minimum desired room air temperature. If the room air temperature falls below this set point, the unit will reduce the cooling.
1.3.6.1.4.1.476.1.42.3.4.1.1.22current
lgpEnvDewPointTemperatures
OBJECT-IDENTITY
This sub-tree identifies well-known dew point temperatures in the system.
1.3.6.1.4.1.476.1.42.3.4.1.1.23current
lgpEnvInletDewPointTemperature
OBJECT-IDENTITY
Dew point temperature measured at the inlet of the unit.
1.3.6.1.4.1.476.1.42.3.4.1.1.23.1current
lgpEnvTemperatureFahrenheit
OBJECT-IDENTITY
This sub-tree contains OIDs that are used to control and monitor temperature using the Fahrenheit temperature scale.
1.3.6.1.4.1.476.1.42.3.4.1.2current
lgpEnvTemperatureSettingDegF
OBJECT-TYPE
The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegC' with the value converted to Celsius.
1.3.6.1.4.1.476.1.42.3.4.1.2.1Integer32read-writecurrent
lgpEnvTemperatureToleranceDegF
OBJECT-TYPE
The acceptable variance from 'lgpEnvTemperatureSettingDegF', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegC' with the value converted to Celsius.
1.3.6.1.4.1.476.1.42.3.4.1.2.2Integer32read-writecurrent
lgpEnvTemperatureTableDegF
OBJECT-TYPE
A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegC' where Fahrenheit values are converted to Celsius.
1.3.6.1.4.1.476.1.42.3.4.1.2.3not-accessiblecurrent
lgpEnvTemperatureEntryDegF
OBJECT-TYPE
This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegF'.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1not-accessiblecurrent
lgpEnvTemperatureIdDegF
OBJECT-TYPE
This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegF'.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.1Unsigned32read-onlycurrent
lgpEnvTemperatureDescrDegF
OBJECT-TYPE
A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.2OBJECT IDENTIFIERread-onlycurrent
lgpEnvTemperatureMeasurementDegF
OBJECT-TYPE
The measured temperature value.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.3Integer32read-onlycurrent
lgpEnvTemperatureHighThresholdDegF
OBJECT-TYPE
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.4Integer32read-writecurrent
lgpEnvTemperatureLowThresholdDegF
OBJECT-TYPE
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.5Integer32read-writecurrent
lgpEnvTemperatureSetPointDegF
OBJECT-TYPE
The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.6Integer32read-writecurrent
lgpEnvTemperatureDailyHighDegF
OBJECT-TYPE
The daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.7Integer32read-onlycurrent
lgpEnvTemperatureDailyLowDegF
OBJECT-TYPE
The daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.8Integer32read-onlycurrent
lgpEnvTempDailyHighTimeHourDegF
OBJECT-TYPE
The hours digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.9Integer32 (0..23)read-onlycurrent
lgpEnvTempDailyHighTimeMinuteDegF
OBJECT-TYPE
The minutes digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.10Integer32 (0..59)read-onlycurrent
lgpEnvTempDailyHighTimeSecondDegF
OBJECT-TYPE
The seconds digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.11Integer32 (0..59)read-onlycurrent
lgpEnvTempDailyLowTimeHourDegF
OBJECT-TYPE
The hours digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.12Integer32 (0..23)read-onlycurrent
lgpEnvTempDailyLowTimeMinuteDegF
OBJECT-TYPE
The minutes digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.13Integer32 (0..59)read-onlycurrent
lgpEnvTempDailyLowTimeSecondDegF
OBJECT-TYPE
The seconds digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.14Integer32 (0..59)read-onlycurrent
lgpEnvTemperatureMeasurementTenthsDegF
OBJECT-TYPE
The measured temperature value.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.50Integer32read-onlycurrent
lgpEnvTemperatureHighThresholdTenthsDegF
OBJECT-TYPE
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.51Integer32read-writecurrent
lgpEnvTemperatureLowThresholdTenthsDegF
OBJECT-TYPE
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.52Integer32read-writecurrent
lgpEnvTemperatureSetPointTenthsDegF
OBJECT-TYPE
The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.53Integer32read-writecurrent
lgpEnvTemperatureDeadBandTenthsDegF
OBJECT-TYPE
The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.60Integer32read-writecurrent
lgpEnvTempHeatingPropBandTenthsDegF
OBJECT-TYPE
The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where heating will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.61Integer32read-writecurrent
lgpEnvTempCoolingPropBandTenthsDegF
OBJECT-TYPE
The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where cooling will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.62Integer32read-writecurrent
lgpEnvTemperatureDeadbandRangeDegF
OBJECT-TYPE
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.
1.3.6.1.4.1.476.1.42.3.4.1.2.4Integer32read-writecurrent
lgpEnvTemperatureCelsius
OBJECT-IDENTITY
This sub-tree contains OIDs that are used to control and monitor temperature using the Celsius temperature scale.
1.3.6.1.4.1.476.1.42.3.4.1.3current
lgpEnvTemperatureSettingDegC
OBJECT-TYPE
The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegF' with the value converted to Fahrenheit.
1.3.6.1.4.1.476.1.42.3.4.1.3.1Integer32read-writecurrent
lgpEnvTemperatureToleranceDegC
OBJECT-TYPE
The acceptable variance from 'lgpEnvTemperatureSettingDegC', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegF' with the value converted to Fahrenheit.
1.3.6.1.4.1.476.1.42.3.4.1.3.2Integer32read-writecurrent
lgpEnvTemperatureTableDegC
OBJECT-TYPE
A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegF' where Celsius values are converted to Fahrenheit.
1.3.6.1.4.1.476.1.42.3.4.1.3.3not-accessiblecurrent
lgpEnvTemperatureEntryDegC
OBJECT-TYPE
This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegC'.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1not-accessiblecurrent
lgpEnvTemperatureIdDegC
OBJECT-TYPE
This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegC'.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.1Unsigned32read-onlycurrent
lgpEnvTemperatureDescrDegC
OBJECT-TYPE
A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.2OBJECT IDENTIFIERread-onlycurrent
lgpEnvTemperatureMeasurementDegC
OBJECT-TYPE
The measured temperature value.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.3Integer32read-onlycurrent
lgpEnvTemperatureHighThresholdDegC
OBJECT-TYPE
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.4Integer32read-writecurrent
lgpEnvTemperatureLowThresholdDegC
OBJECT-TYPE
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.5Integer32read-writecurrent
lgpEnvTemperatureSetPointDegC
OBJECT-TYPE
The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.6Integer32read-writecurrent
lgpEnvTemperatureDailyHighDegC
OBJECT-TYPE
The daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.7Integer32read-onlycurrent
lgpEnvTemperatureDailyLowDegC
OBJECT-TYPE
The daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.8Integer32read-onlycurrent
lgpEnvTempDailyHighTimeHourDegC
OBJECT-TYPE
The hours digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.9Integer32 (0..23)read-onlycurrent
lgpEnvTempDailyHighTimeMinuteDegC
OBJECT-TYPE
The minutes digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.10Integer32 (0..59)read-onlycurrent
lgpEnvTempDailyHighTimeSecondDegC
OBJECT-TYPE
The seconds digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.11Integer32 (0..59)read-onlycurrent
lgpEnvTempDailyLowTimeHourDegC
OBJECT-TYPE
The hours digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.12Integer32 (0..23)read-onlycurrent
lgpEnvTempDailyLowTimeMinuteDegC
OBJECT-TYPE
The minutes digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.13Integer32 (0..59)read-onlycurrent
lgpEnvTempDailyLowTimeSecondDegC
OBJECT-TYPE
The seconds digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.14Integer32 (0..59)read-onlycurrent
lgpEnvTemperatureMeasurementTenthsDegC
OBJECT-TYPE
The measured temperature value.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.50Integer32read-onlycurrent
lgpEnvTemperatureHighThresholdTenthsDegC
OBJECT-TYPE
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.51Integer32read-writecurrent
lgpEnvTemperatureLowThresholdTenthsDegC
OBJECT-TYPE
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.52Integer32read-writecurrent
lgpEnvTemperatureSetPointTenthsDegC
OBJECT-TYPE
The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.53Integer32read-writecurrent
lgpEnvTemperatureDeadBandTenthsDegC
OBJECT-TYPE
The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.60Integer32read-writecurrent
lgpEnvTempHeatingPropBandTenthsDegC
OBJECT-TYPE
The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where heating will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.61Integer32read-writecurrent
lgpEnvTempCoolingPropBandTenthsDegC
OBJECT-TYPE
The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where cooling will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.62Integer32read-writecurrent
lgpEnvTemperatureDeadbandRangeDegC
OBJECT-TYPE
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.
1.3.6.1.4.1.476.1.42.3.4.1.3.4Integer32read-writecurrent
lgpEnvTemperatureControlMode
OBJECT-TYPE
A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature object that is used for control.
1.3.6.1.4.1.476.1.42.3.4.1.4OBJECT IDENTIFIERread-onlycurrent
lgpEnvHumidity
OBJECT-IDENTITY
This sub-tree is used to register Liebert humidity object identifiers.
1.3.6.1.4.1.476.1.42.3.4.2current
lgpEnvHumidityWellKnown
OBJECT-IDENTITY
Liebert well known humidity objects are defined by OIDs that reside in this sub-tree.
1.3.6.1.4.1.476.1.42.3.4.2.1current
lgpEnvControlHumidity
OBJECT-IDENTITY
Humidity measurement used as control feedback.
1.3.6.1.4.1.476.1.42.3.4.2.1.1current
lgpEnvReturnAirHumidity
OBJECT-IDENTITY
Humidity measurement of return air.
1.3.6.1.4.1.476.1.42.3.4.2.1.2current
lgpEnvSupplyAirHumidity
OBJECT-IDENTITY
Humidity measurement of supply air.
1.3.6.1.4.1.476.1.42.3.4.2.1.3current
lgpEnvValueAmbientHumidity
OBJECT-IDENTITY
Humidity outside enclosure.
1.3.6.1.4.1.476.1.42.3.4.2.1.4current
lgpEnvHumidityRelative
OBJECT-IDENTITY
This sub-tree contains OIDs that are used to control and monitor relative humidity.
1.3.6.1.4.1.476.1.42.3.4.2.2current
lgpEnvHumiditySettingRel
OBJECT-TYPE
The humidity setting used to control the well known humidity point.
1.3.6.1.4.1.476.1.42.3.4.2.2.1Integer32read-writecurrent
lgpEnvHumidityToleranceRel
OBJECT-TYPE
Acceptable variance from lgpEnvHumiditySettingRel, without initiating a control action.
1.3.6.1.4.1.476.1.42.3.4.2.2.2Integer32read-writecurrent
lgpEnvHumidityTableRel
OBJECT-TYPE
A list of humidity table entries. The table contains zero, one, or many rows, depending upon the number of humidity objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
1.3.6.1.4.1.476.1.42.3.4.2.2.3not-accessiblecurrent
lgpEnvHumidityEntryRel
OBJECT-TYPE
This entry defines the contents of the rows for the table 'lgpEnvHumidityTableRel'.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1not-accessiblecurrent
lgpEnvHumidityIdRel
OBJECT-TYPE
This OID is used as an index to identify a row in the table 'lgpEnvHumidityTableRel'.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.1Unsigned32read-onlycurrent
lgpEnvHumidityDescrRel
OBJECT-TYPE
A reference to a humidity description object. The object referenced should not be accessible, but rather be used to provide a unique description of the humidity.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.2OBJECT IDENTIFIERread-onlycurrent
lgpEnvHumidityMeasurementRel
OBJECT-TYPE
The measured humidity value.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.3Integer32read-onlycurrent
lgpEnvHumidityHighThresholdRel
OBJECT-TYPE
The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.4Integer32read-writecurrent
lgpEnvHumidityLowThresholdRel
OBJECT-TYPE
The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.5Integer32read-writecurrent
lgpEnvHumiditySetPoint
OBJECT-TYPE
The humidity setting used to control the well known humidity object 'lgpEnvHumidityDescrRel'. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.6Integer32read-writecurrent
lgpEnvHumidityDailyHigh
OBJECT-TYPE
The daily high relative humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.7Integer32read-onlycurrent
lgpEnvHumidityDailyLow
OBJECT-TYPE
The daily low relative humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.8Integer32read-onlycurrent
lgpEnvHumidityDailyHighTimeHour
OBJECT-TYPE
The hours digit of the time corresponding to the daily high humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.9Integer32 (0..23)read-onlycurrent
lgpEnvHumidityDailyHighTimeMinute
OBJECT-TYPE
The minutes digit of the time corresponding to the daily high humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.10Integer32 (0..59)read-onlycurrent
lgpEnvHumidityDailyHighTimeSecond
OBJECT-TYPE
The seconds digit of the time corresponding to the daily high humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.11Integer32 (0..59)read-onlycurrent
lgpEnvHumidityDailyLowTimeHour
OBJECT-TYPE
The hours digit of the time corresponding to the daily low humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.12Integer32 (0..23)read-onlycurrent
lgpEnvHumidityDailyLowTimeMinute
OBJECT-TYPE
The minutes digit of the time corresponding to the daily low humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.13Integer32 (0..59)read-onlycurrent
lgpEnvHumidityDailyLowTimeSecond
OBJECT-TYPE
The seconds digit of the time corresponding to the daily low humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.14Integer32 (0..59)read-onlycurrent
lgpEnvHumidityDeadBand
OBJECT-TYPE
The deadband region around the setpoint value (lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.15Integer32read-writecurrent
lgpEnvHumidifyPropBand
OBJECT-TYPE
The proportional region below the setpoint value (lgpEnvHumiditySetPoint) where humidifying will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.16Integer32read-writecurrent
lgpEnvDehumidifyPropBand
OBJECT-TYPE
The proportional region above the setpoint value (lgpEnvHumiditySetPoint) where dehumidifying will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17Integer32read-writecurrent
lgpEnvHumidityMeasurementRelTenths
OBJECT-TYPE
The measured humidity value.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.50Integer32read-onlycurrent
lgpEnvHumidityHighThresholdRelTenths
OBJECT-TYPE
The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.51Integer32read-writecurrent
lgpEnvHumidityLowThresholdRelTenths
OBJECT-TYPE
The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.52Integer32read-writecurrent
lgpEnvHumidityDeadbandRange
OBJECT-TYPE
The allowable deviation above and below the humidity set point used to create a no control region, a dead-band, where humidifying and dehumidifying control are disabled.
1.3.6.1.4.1.476.1.42.3.4.2.2.4Integer32read-writecurrent
lgpEnvState
OBJECT-IDENTITY
This sub-tree is used to register Liebert environmental state object identifiers.
1.3.6.1.4.1.476.1.42.3.4.3current
lgpEnvStateSystem
OBJECT-TYPE
The present state of the system.
1.3.6.1.4.1.476.1.42.3.4.3.1INTEGER {on(1), off(2), standby(3)}read-onlycurrent
lgpEnvStateCooling
OBJECT-TYPE
The present state of the cooling subsystem.
1.3.6.1.4.1.476.1.42.3.4.3.2INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateHeating
OBJECT-TYPE
The present state of the heating subsystem.
1.3.6.1.4.1.476.1.42.3.4.3.3INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateHumidifying
OBJECT-TYPE
The present state of the humidifier subsystem.
1.3.6.1.4.1.476.1.42.3.4.3.4INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateDehumidifying
OBJECT-TYPE
The present state of the dehumidifier subsystem
1.3.6.1.4.1.476.1.42.3.4.3.5INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateEconoCycle
OBJECT-TYPE
The present state of the Econ-o-cycle subsystem.
1.3.6.1.4.1.476.1.42.3.4.3.6INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateFan
OBJECT-TYPE
The present state of the system fan.
1.3.6.1.4.1.476.1.42.3.4.3.7INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateGeneralAlarmOutput
OBJECT-TYPE
The present state of the general alarm output. This indicates if an alarm is active in the system.
1.3.6.1.4.1.476.1.42.3.4.3.8INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateCoolingCapacity
OBJECT-TYPE
The percentage of the cooling capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.9Unsigned32read-onlycurrent
lgpEnvStateHeatingCapacity
OBJECT-TYPE
The percentage of the heating capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.10Unsigned32read-onlycurrent
lgpEnvStateAudibleAlarm
OBJECT-TYPE
The present state of the audible alarm output.
1.3.6.1.4.1.476.1.42.3.4.3.11INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateCoolingUnits
OBJECT-IDENTITY
This sub-tree contains OIDs that are used to indicate the status of cooling units.
1.3.6.1.4.1.476.1.42.3.4.3.12current
lgpEnvStateCoolingUnit1
OBJECT-TYPE
The present state of cooling unit 1.
1.3.6.1.4.1.476.1.42.3.4.3.12.2INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateCoolingUnit2
OBJECT-TYPE
The present state of cooling unit 2.
1.3.6.1.4.1.476.1.42.3.4.3.12.3INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateCoolingUnit3
OBJECT-TYPE
The present state of cooling unit 3.
1.3.6.1.4.1.476.1.42.3.4.3.12.4INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateCoolingUnit4
OBJECT-TYPE
The present state of cooling unit 4.
1.3.6.1.4.1.476.1.42.3.4.3.12.5INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateHeatingUnits
OBJECT-IDENTITY
This sub-tree contains OIDs that are used to indicate the status of heating units.
1.3.6.1.4.1.476.1.42.3.4.3.13current
lgpEnvStateHeatingUnit1
OBJECT-TYPE
The present state of heating unit 1.
1.3.6.1.4.1.476.1.42.3.4.3.13.2INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateHeatingUnit2
OBJECT-TYPE
The present state of heating unit 2.
1.3.6.1.4.1.476.1.42.3.4.3.13.3INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateHeatingUnit3
OBJECT-TYPE
The present state of heating unit 3.
1.3.6.1.4.1.476.1.42.3.4.3.13.4INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateHeatingUnit4
OBJECT-TYPE
The present state of heating unit 4.
1.3.6.1.4.1.476.1.42.3.4.3.13.5INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateOperatingReason
OBJECT-TYPE
The reason for the current operating state of the system.
1.3.6.1.4.1.476.1.42.3.4.3.14INTEGER {none(1), localUser(2), alarm(3), schedule(4), remoteUser(5), externalDevice(6), localDisplay(7)}read-onlycurrent
lgpEnvStateOperatingMode
OBJECT-TYPE
The present operating mode of the system.
1.3.6.1.4.1.476.1.42.3.4.3.15INTEGER {auto(1), manual(2)}read-onlycurrent
lgpEnvStateFanCapacity
OBJECT-TYPE
The percentage of the fan capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.16Unsigned32read-onlycurrent
lgpEnvStateFreeCoolingCapacity
OBJECT-TYPE
The percentage of the free cooling capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.17Unsigned32read-onlycurrent
lgpEnvStateDehumidifyingCapacity
OBJECT-TYPE
The percentage of the dehumidifying capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.18Unsigned32read-onlycurrent
lgpEnvStateHumidifyingCapacity
OBJECT-TYPE
The percentage of the humidifying capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.19Unsigned32read-onlycurrent
lgpEnvStateFreeCooling
OBJECT-TYPE
The present state of the system free cooling process of heat exchange. When 'off', free cooling is not in use. When 'on' free cooling is in use. When 'start', free cooling is preparing to turn on. When 'unavailable', the state information is unavailable.
1.3.6.1.4.1.476.1.42.3.4.3.20INTEGER {on(1), off(2), start(3), unavailable(4)}read-onlycurrent
lgpEnvStateElectricHeater
OBJECT-TYPE
The present state of the electric heaters.
1.3.6.1.4.1.476.1.42.3.4.3.21INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateHotWater
OBJECT-TYPE
The present state of hot water system.
1.3.6.1.4.1.476.1.42.3.4.3.22INTEGER {on(1), off(2)}read-onlycurrent
lgpEnvStateOperatingEfficiency
OBJECT-TYPE
The ratio of cooling energy provided to the amount of total energy being used.
1.3.6.1.4.1.476.1.42.3.4.3.23Unsigned32read-onlycurrent
lgpEnvComponentStateTable
OBJECT-TYPE
This table contains a list of the units components that have a state associated with them. The table contains zero, one, or more rows, depending upon the number of components associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
1.3.6.1.4.1.476.1.42.3.4.3.50not-accessiblecurrent
lgpEnvComponentStateEntry
OBJECT-TYPE
This entry defines the attributes to be populated in the various columns of the 'lgpEnvComponentStateTable'.
1.3.6.1.4.1.476.1.42.3.4.3.50.1not-accessiblecurrent
lgpEnvComponentStateIndex
OBJECT-TYPE
This is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.4.3.50.1.1Unsigned32not-accessiblecurrent
lgpEnvComponentStateDescr
OBJECT-TYPE
A reference to a component description object. The object referenced should not be accessible, but rather be used to provide a unique description of the component being described in the row of the table.
1.3.6.1.4.1.476.1.42.3.4.3.50.1.2OBJECT IDENTIFIERread-onlycurrent
lgpEnvComponentState
OBJECT-TYPE
not-specified The state of the component is unknown. on The component is on. off The component is off.
1.3.6.1.4.1.476.1.42.3.4.3.50.1.3INTEGER {not-specified(0), on(1), off(2)}read-onlycurrent
lgpEnvValveTable
OBJECT-TYPE
This table contains a list of the unit valves that have information associated with them. The table contains zero, one, or more rows, depending upon the number of valves associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
1.3.6.1.4.1.476.1.42.3.4.3.70not-accessiblecurrent
lgpEnvValveEntry
OBJECT-TYPE
This entry defines the attributes to be populated in the various columns of the 'lgpEnvValveTable'.
1.3.6.1.4.1.476.1.42.3.4.3.70.1not-accessiblecurrent
lgpEnvValveIndex
OBJECT-TYPE
This is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.4.3.70.1.1Unsigned32not-accessiblecurrent
lgpEnvValveDescr
OBJECT-TYPE
A reference to a valve description object. The object referenced should not be accessible, but rather be used to provide a unique description of the valve being described in the row of the table.
1.3.6.1.4.1.476.1.42.3.4.3.70.1.2OBJECT IDENTIFIERread-onlycurrent
lgpEnvValveState
OBJECT-TYPE
not-specified The state of the component is unknown. open The valve is open. off The valve is closed.
1.3.6.1.4.1.476.1.42.3.4.3.70.1.3INTEGER {not-specified(0), open(1), closed(2)}read-onlycurrent
lgpEnvValvePositionTenths
OBJECT-TYPE
This gives a value describing the position of the valve.
1.3.6.1.4.1.476.1.42.3.4.3.70.1.20Unsigned32read-onlycurrent
lgpEnvConfig
OBJECT-IDENTITY
This sub-tree is used to register Liebert environmental configuration object identifiers.
1.3.6.1.4.1.476.1.42.3.4.4current
lgpEnvConfigReheatLockout
OBJECT-TYPE
If locked-out the reheats will not operate even if controller calls for its operation.
1.3.6.1.4.1.476.1.42.3.4.4.1INTEGER {lockedOut(1), notLockedOut(2)}read-writecurrent
lgpEnvConfigHumLockout
OBJECT-TYPE
If locked-out the humidifier will not operate even if controller calls for its operation.
1.3.6.1.4.1.476.1.42.3.4.4.2INTEGER {lockedOut(1), notLockedOut(2)}read-writecurrent
lgpEnvConfigRestartDelay
OBJECT-TYPE
When utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is restored. A Restart Delay of zero denotes a manual restart, the unit will NOT automatically restart.
1.3.6.1.4.1.476.1.42.3.4.4.4Unsigned32read-writecurrent
lgpEnvConfigRemoteShutdown
OBJECT-TYPE
When in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing.
1.3.6.1.4.1.476.1.42.3.4.4.7INTEGER {disabled(1), enabled(2)}read-writecurrent
lgpEnvConfigCoolingServiceInterval
OBJECT-TYPE
The amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this value an lgpConditionServiceCooling will be activated. Once service has been completed the cooling service timer should be reset to 0.
1.3.6.1.4.1.476.1.42.3.4.4.8Unsigned32read-writecurrent
lgpEnvConfigHumidifierServiceInterval
OBJECT-TYPE
The amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this value an lgpConditionServiceHumidifier will be activated. Once service has been completed humidifier service timer should be reset to 0.
1.3.6.1.4.1.476.1.42.3.4.4.9Unsigned32read-writecurrent
lgpEnvConfigFilterServiceInterval
OBJECT-TYPE
The amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this value an lgpConditionChangeFilter will be activated. Once service has been completed the filter service timer should be reset to 0.
1.3.6.1.4.1.476.1.42.3.4.4.10Unsigned32read-writecurrent
lgpEnvConfigSleepModeDeadbandRangeDegC
OBJECT-TYPE
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.
1.3.6.1.4.1.476.1.42.3.4.4.11Integer32read-writecurrent
lgpEnvConfigSleepModeDeadbandRangeDegF
OBJECT-TYPE
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.
1.3.6.1.4.1.476.1.42.3.4.4.12Integer32read-writecurrent
lgpEnvConfigSupplyTempLowLimitDegF
OBJECT-TYPE
The minimum allowable supply temperature.
1.3.6.1.4.1.476.1.42.3.4.4.13Integer32read-writecurrent
lgpEnvConfigSupplyTempLowLimitDegC
OBJECT-TYPE
The minimum allowable supply temperature.
1.3.6.1.4.1.476.1.42.3.4.4.14Integer32read-writecurrent
lgpEnvConfigTemperatureIntegTime
OBJECT-TYPE
The value used as the integration factor in the proportional integral derivative (PID) temperature calculation.
1.3.6.1.4.1.476.1.42.3.4.4.15Integer32read-writecurrent
lgpEnvConfigLocalTemperatureUnit
OBJECT-TYPE
The local temperature unit of the system.
1.3.6.1.4.1.476.1.42.3.4.4.16INTEGER {degC(1), degF(2)}read-writecurrent
lgpEnvConfigSleepMode
OBJECT-TYPE
The configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day. If 'disabled', the device will operate continually and not sleep at all. If 'auto', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day unless the environmental conditions fall outside the desired operation ranges.
1.3.6.1.4.1.476.1.42.3.4.4.17INTEGER {enabled(1), disabled(2), auto(3)}read-writecurrent
lgpEnvConfigHumidityIntegTime
OBJECT-TYPE
The value used as the integration factor in the proportional integral derivative (PID) humidity calculation.
1.3.6.1.4.1.476.1.42.3.4.4.18Integer32read-writecurrent
lgpEnvConfigFreecoolingDeltaDegF
OBJECT-TYPE
The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
1.3.6.1.4.1.476.1.42.3.4.4.19Integer32read-writecurrent
lgpEnvConfigFreecoolingDeltaDegC
OBJECT-TYPE
The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
1.3.6.1.4.1.476.1.42.3.4.4.20Integer32read-writecurrent
lgpEnvConfigSupplyTempLowLimit
OBJECT-TYPE
The system configuration parameter to enable or disable the supply air low temperature limit.
1.3.6.1.4.1.476.1.42.3.4.4.21INTEGER {disabled(1), enabled(2)}read-writecurrent
lgpEnvConfigSensorEventsStandard
OBJECT-TYPE
The system configuration parameter to enable or disable the standard sensor events.
1.3.6.1.4.1.476.1.42.3.4.4.22INTEGER {disabled(1), enabled(2)}read-writecurrent
lgpEnvConfigSensorEvents1
OBJECT-TYPE
The system configuration parameter to enable or disable sensor 1 events.
1.3.6.1.4.1.476.1.42.3.4.4.23INTEGER {disabled(1), enabled(2)}read-writecurrent
lgpEnvConfigSleepModeDeadbandRange
OBJECT-TYPE
The system configuration parameter to enable or disable the use of the sleep interval dead-band range in the sleep mode temperature calculations and control algorithm.
1.3.6.1.4.1.476.1.42.3.4.4.24INTEGER {disabled(1), enabled(2)}read-writecurrent
lgpEnvConfigAutoConfiguration
OBJECT-TYPE
The system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and humidity control parameters.
1.3.6.1.4.1.476.1.42.3.4.4.25INTEGER {disabled(1), enabled(2)}read-writecurrent
lgpEnvConfigDeltaGlycolType
OBJECT-TYPE
The system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cooling. If 'disabled', the system will use the valve temperature to initiate free cooling. If 'contact', a input to the system will initiate free cooling. If 'valve', the system compares the room and glycol temperature differential with the valve temperature to initiate free cooling. If the temperature differential is greater than or equal to the valve temperature, free cooling will be initiated.
1.3.6.1.4.1.476.1.42.3.4.4.26INTEGER {disabled(1), contact(2), value(3)}read-writecurrent
lgpEnvConfigChillWaterControl
OBJECT-TYPE
The system configuration parameter to enable or disable the minimum chill water temperature control.
1.3.6.1.4.1.476.1.42.3.4.4.27INTEGER {disabled(1), enabled(2)}read-writecurrent
lgpEnvConfigInfaredFlushRate
OBJECT-TYPE
The Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan when the 'humidifier is in operation.
1.3.6.1.4.1.476.1.42.3.4.4.28Unsigned32read-writecurrent
lgpEnvConfigHumidityControl
OBJECT-TYPE
The present configured state of the automatic humidity compensation algorithm.
1.3.6.1.4.1.476.1.42.3.4.4.29INTEGER {relative(1), compensated(2), predictive(3)}read-writecurrent
lgpEnvConfigCompressorLockout
OBJECT-TYPE
The system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for their operation.
1.3.6.1.4.1.476.1.42.3.4.4.30INTEGER {lockedOut(1), notLockedOut(2)}read-writecurrent
lgpEnvConfigReheatAndHumidifierLockout
OBJECT-TYPE
The system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the controller calls for their operation.
1.3.6.1.4.1.476.1.42.3.4.4.31INTEGER {lockedOut(1), notLockedOut(2)}read-writecurrent
lgpEnvOperationalTimeTable
OBJECT-TYPE
A list of environmental operational time ranges for a given environmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistics' group. This table contains zero, one, or many rows, depending upon the number of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
1.3.6.1.4.1.476.1.42.3.4.4.32not-accessiblecurrent
lgpEnvOperationalTimeEntry
OBJECT-TYPE
This entry defines the contents of the columns for the table 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.4.32.1not-accessiblecurrent
lgpEnvOperationTimeIndex
OBJECT-TYPE
This is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.4.4.32.1.1Unsigned32not-accessiblecurrent
lgpEnvOperationTimePoint
OBJECT-TYPE
An OID representing a well known operation point. These object identifiers can indicate a point, location, or mode of an operation for which a measurement is recorded. The OID's name usually implies a location of the measurement point such as 'fan', 'compressor', etc.
1.3.6.1.4.1.476.1.42.3.4.4.32.1.2OBJECT IDENTIFIERread-onlycurrent
lgpEnvOperationTimeSubID
OBJECT-TYPE
This is a sub identifier for the 'lgpEnvOperationPoint'. It indicates the instance number of the well known operation point. For example, a system could have two fans installed. This variable would identify fan 1 with a lgpEnvOperationSubID equal to 1 and fan 2 with a lgpEnvOperationSubID equal to 2.
1.3.6.1.4.1.476.1.42.3.4.4.32.1.3Integer32read-onlycurrent
lgpEnvOperationTimeUnit
OBJECT-TYPE
An OID representing a well known operation time unit type. These object identifiers indicate the units of the operation time. The OID's name usually implies a measurement type such as 'lgpEnvHours', etc.
1.3.6.1.4.1.476.1.42.3.4.4.32.1.4OBJECT IDENTIFIERread-onlycurrent
lgpEnvOperationTimeValue
OBJECT-TYPE
The actual operation time value of the 'lgpEnvOperationTimePoint'. If multiple operation times are available for a 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.
1.3.6.1.4.1.476.1.42.3.4.4.32.1.5Integer32read-writecurrent
lgpEnvOperationTimeHighWarning
OBJECT-TYPE
The high warning time of the operation designated by the 'lgpEnvOperationTimePoint'. If operation times are available at a single 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.
1.3.6.1.4.1.476.1.42.3.4.4.32.1.6Integer32read-writecurrent
lgpEnvConfigTempControlAlgorithm
OBJECT-TYPE
Selects the algorithm for controlling temperature.
1.3.6.1.4.1.476.1.42.3.4.4.33INTEGER {pi(1), pid(2), intelligent(3), proportional(4)}read-writecurrent
lgpEnvConfigFanSpeedMode
OBJECT-TYPE
Changes the function of the fan speed output. If auto, then the fan speed is modulated. If manual, the fan speed output follows lgpEnvConfigFanSpeedCapacity.
1.3.6.1.4.1.476.1.42.3.4.4.34INTEGER {manual(1), auto(2)}read-writecurrent
lgpEnvConfigFanSpeedCapacity
OBJECT-TYPE
Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ranges may differ from unit to unit).
1.3.6.1.4.1.476.1.42.3.4.4.35Unsigned32read-writecurrent
lgpEnvConfigBmsResetTimer
OBJECT-TYPE
The current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to continue controlling the fan speed, it must reset this timer. Typical values range from 0 to 120 minutes (actual valid ranges may differ from unit to unit).
1.3.6.1.4.1.476.1.42.3.4.4.36Unsigned32read-writecurrent
lgpEnvConfigDisableSensorOffsetDegC
OBJECT-TYPE
If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.
1.3.6.1.4.1.476.1.42.3.4.4.37Integer32read-writecurrent
lgpEnvConfigDisableSensorOffsetDegF
OBJECT-TYPE
If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.
1.3.6.1.4.1.476.1.42.3.4.4.38Integer32read-writecurrent
lgpEnvConfigCabinetSensorAlarms
OBJECT-TYPE
Enable or Disable Cabinet Sensor Alarms.
1.3.6.1.4.1.476.1.42.3.4.4.39INTEGER {disabled(0), enabled(1)}read-writecurrent
lgpEnvConfigAirTemperatureControlSensor
OBJECT-TYPE
Sensor from which air temperature measurements will be used for cooling and heating control.
1.3.6.1.4.1.476.1.42.3.4.4.42INTEGER {supply(1), remote(2), return(3)}read-writecurrent
lgpEnvConfigFanSpeedControlSensor
OBJECT-TYPE
Sensor from which air temperature measurements will be used for fan speed control.
1.3.6.1.4.1.476.1.42.3.4.4.43INTEGER {supply(1), remote(2), return(3)}read-writecurrent
lgpEnvConfigMinFanSpeed
OBJECT-TYPE
Sets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
1.3.6.1.4.1.476.1.42.3.4.4.44Unsigned32read-writecurrent
lgpEnvConfigMaxFanSpeed
OBJECT-TYPE
Sets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
1.3.6.1.4.1.476.1.42.3.4.4.45Unsigned32read-writecurrent
lgpEnvConfigFanSpeedPropBandDegC
OBJECT-TYPE
Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.4.46Integer32read-writecurrent
lgpEnvConfigFanSpeedPropBandDegF
OBJECT-TYPE
Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.4.47Integer32read-writecurrent
lgpEnvControl
OBJECT-IDENTITY
This sub-tree is used to register Liebert environmental control object identifiers.
1.3.6.1.4.1.476.1.42.3.4.5current
lgpEnvControlShutdownAfterDelay
OBJECT-TYPE
Setting this object will shutdown (i.e., turn off) the system after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. When read, lgpEnvControlShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any lgpEnvControlShutdownAfterDelay already in effect.
1.3.6.1.4.1.476.1.42.3.4.5.1Integer32 (-1..2147483647)read-writecurrent
lgpEnvControlStartupAfterDelay
OBJECT-TYPE
Setting this object will start the system after the indicated number of seconds. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the system is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any lgpEnvControlStartupAfterDelay countdown in progress. When read, lgpEnvControlStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.
1.3.6.1.4.1.476.1.42.3.4.5.2Integer32 (-1..2147483647)read-writecurrent
lgpEnvSleepIntervalTimeTable
OBJECT-TYPE
A sleep time interval table containing a list of the start and stop times to be used to take a device online or offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
1.3.6.1.4.1.476.1.42.3.4.5.3not-accessiblecurrent
lgpEnvSleepIntervalTimeEntry
OBJECT-TYPE
This entry defines the contents of the columns for the table 'lgpEnvSleepIntervalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.5.3.1not-accessiblecurrent
lgpEnvSleepTimeIndex
OBJECT-TYPE
This is the index indicating the row of the table 'lgpEnvSleepIntervalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.1Unsigned32not-accessiblecurrent
lgpEnvSleepTimeSubID
OBJECT-TYPE
This is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'. It indicates the instance number of the 'lgpEnvSleepIntervalTimeEntry'. For example, a system could have two sleep intervals and the first interval's sub ID would be 1 and the second interval's sub ID would be 2.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.2Integer32read-onlycurrent
lgpEnvSleepTimeStartHour
OBJECT-TYPE
This is the hours digit of the time when the system will be put online.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.3Integer32 (0..23)read-writecurrent
lgpEnvSleepTimeStartMinute
OBJECT-TYPE
This is the minutes digit of the time when the system will be put online.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.4Integer32 (0..59)read-writecurrent
lgpEnvSleepTimeStopHour
OBJECT-TYPE
This is the hours digit containing the time when the system will be taken offline.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.5Integer32 (0..23)read-writecurrent
lgpEnvSleepTimeStopMinute
OBJECT-TYPE
This is the minutes digit containing the time when the system will be taken offline.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.6Integer32 (0..59)read-writecurrent
lgpEnvSleepDayTable
OBJECT-TYPE
A sleep table containing a list of the days of the week the system will be offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
1.3.6.1.4.1.476.1.42.3.4.5.4not-accessiblecurrent
lgpEnvSleepDayEntry
OBJECT-TYPE
This entry defines the contents of the columns for the table 'lgpEnvSleepDayTable'.
1.3.6.1.4.1.476.1.42.3.4.5.4.1not-accessiblecurrent
lgpEnvSleepDayIndex
OBJECT-TYPE
This is the index indicating the row of the table 'lgpEnvSleepDayTable'.
1.3.6.1.4.1.476.1.42.3.4.5.4.1.1Unsigned32not-accessiblecurrent
lgpEnvSleepDay
OBJECT-TYPE
This is a sub identifier for the day of the week within 'lgpEnvSleepDayTable'.
1.3.6.1.4.1.476.1.42.3.4.5.4.1.2INTEGER {sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7)}read-onlycurrent
lgpEnvSleepAllDayEnabled
OBJECT-TYPE
The all day sleep functionality has been enabled for the corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'.
1.3.6.1.4.1.476.1.42.3.4.5.4.1.3INTEGER {yes(1), no(2)}read-writecurrent
lgpEnvStatistics
OBJECT-IDENTITY
This sub-tree is used to register Liebert environmental statistic object identifiers.
1.3.6.1.4.1.476.1.42.3.4.6current
lgpEnvStatisticsComp1RunHr
OBJECT-TYPE
Accumulated run hours of compressor 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.1Unsigned32read-onlycurrent
lgpEnvStatisticsComp2RunHr
OBJECT-TYPE
Accumulated run hours of compressor 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.2Unsigned32read-onlycurrent
lgpEnvStatisticsFanRunHr
OBJECT-TYPE
Accumulated run hours of the main fan. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.3Unsigned32read-onlycurrent
lgpEnvStatisticsHumRunHr
OBJECT-TYPE
Accumulated run hours of the humidifier. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.4Unsigned32read-onlycurrent
lgpEnvStatisticsReheat1RunHr
OBJECT-TYPE
Accumulated run hours of reheat element 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.7Unsigned32read-onlycurrent
lgpEnvStatisticsReheat2RunHr
OBJECT-TYPE
Accumulated run hours of reheat element 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.8Unsigned32read-onlycurrent
lgpEnvStatisticsReheat3RunHr
OBJECT-TYPE
Accumulated run hours of reheat element 3. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.9Unsigned32read-onlycurrent
lgpEnvStatisticsCoolingModeHrs
OBJECT-TYPE
Accumulated run hours while lgpEnvStateCooling is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.10Unsigned32read-onlycurrent
lgpEnvStatisticsHeatingModeHrs
OBJECT-TYPE
Accumulated run hours while lgpEnvStateHeating is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.11Unsigned32read-onlycurrent
lgpEnvStatisticsHumidifyModeHrs
OBJECT-TYPE
Accumulated run hours of the humidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.12Unsigned32read-onlycurrent
lgpEnvStatisticsDehumidifyModeHrs
OBJECT-TYPE
Accumulated run hours of the dehumidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.13Unsigned32read-onlycurrent
lgpEnvStatisticsHotGasRunHr
OBJECT-TYPE
Accumulated run hours of the hot gas system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.14Unsigned32read-onlycurrent
lgpEnvStatisticsHotWaterRunHr
OBJECT-TYPE
Accumulated run hours of the hot water system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.15Unsigned32read-onlycurrent
lgpEnvStatisticsFreeCoolRunHr
OBJECT-TYPE
Accumulated run hours of the free cooling process. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.16Unsigned32read-onlycurrent
lgpEnvStatisticsComp3RunHr
OBJECT-TYPE
Accumulated run hours of compressor 3.
1.3.6.1.4.1.476.1.42.3.4.6.17Unsigned32read-onlycurrent
lgpEnvStatisticsComp4RunHr
OBJECT-TYPE
Accumulated run hours of compressor 4.
1.3.6.1.4.1.476.1.42.3.4.6.18Unsigned32read-onlycurrent
lgpEnvPoints
OBJECT-IDENTITY
This sub-tree is used to register Liebert environmental point object identifiers.
1.3.6.1.4.1.476.1.42.3.4.7current
lgpEnvWellKnownPoints
OBJECT-IDENTITY
This sub-tree registers well known Liebert Environmental Points. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
1.3.6.1.4.1.476.1.42.3.4.7.1current
lgpEnvFanPoint
OBJECT-IDENTITY
This identifier represents a well known fan measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.1current
lgpEnvCompressorPoint
OBJECT-IDENTITY
This identifier represents a well known compressor measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.2current
lgpEnvElectricHeaterPoint
OBJECT-IDENTITY
This identifier represents a well known electric heater measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.3current
lgpEnvChilledWaterPoint
OBJECT-IDENTITY
This identifier represents a well known chilled water measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.4current
lgpEnvHumidifierPoint
OBJECT-IDENTITY
This identifier represents a well known humidifier measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.5current
lgpEnvDehumidifierPoint
OBJECT-IDENTITY
This identifier represents a well known dehumidifier measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.6current
lgpEnvFreeCoolingPoint
OBJECT-IDENTITY
This identifier represents a well known free-cooling measurement process.
1.3.6.1.4.1.476.1.42.3.4.7.1.7current
lgpEnvHotWaterPoint
OBJECT-IDENTITY
This identifier represents a well known hot water measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.8current
lgpEnvHotGasPoint
OBJECT-IDENTITY
This identifier represents a well known hot gas measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.9current
lgpEnvBatteryCabinetPoint
OBJECT-IDENTITY
This identifier represents a well known cabinet point. To determine the cabinet being described in a multi-cabinet system, this point implements two additional indexes. The first index describes the module being supplied with battery power. The second index identifies the number of the battery cabinet, which is typically a sequential number. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpEnvBatteryCabinetPoint' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4
1.3.6.1.4.1.476.1.42.3.4.7.1.10current
lgpEnvPumpPoints
OBJECT-IDENTITY
This sub-tree identifies well-known pumps in the system.
1.3.6.1.4.1.476.1.42.3.4.7.1.11current
lgpEnvPump1Point
OBJECT-IDENTITY
This identifier represents pump 1.
1.3.6.1.4.1.476.1.42.3.4.7.1.11.1current
lgpEnvPump2Point
OBJECT-IDENTITY
This identifier represents pump 2.
1.3.6.1.4.1.476.1.42.3.4.7.1.11.2current
lgpEnvCompressorPoints
OBJECT-IDENTITY
This sub-tree identifies well-known compressors in the system.
1.3.6.1.4.1.476.1.42.3.4.7.1.12current
lgpEnvCompressor1Point
OBJECT-IDENTITY
This identifier represents compressor 1.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.1current
lgpEnvCompressor1APoint
OBJECT-IDENTITY
This identifier represents compressor 1A.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.1current
lgpEnvCompressor1BPoint
OBJECT-IDENTITY
This identifier represents compressor 1B.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.2current
lgpEnvCompressor2Point
OBJECT-IDENTITY
This identifier represents compressor 2.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.2current
lgpEnvCompressor2APoint
OBJECT-IDENTITY
This identifier represents compressor 2A.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.1current
lgpEnvCompressor2BPoint
OBJECT-IDENTITY
This identifier represents compressor 2B.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.2current
lgpEnvValvePoints
OBJECT-IDENTITY
This sub-tree identifies well-known valves in the system.
1.3.6.1.4.1.476.1.42.3.4.7.1.13current
lgpEnvHotGasValve1Point
OBJECT-IDENTITY
This identifier represents hot gas valve 1.
1.3.6.1.4.1.476.1.42.3.4.7.1.13.1current
lgpEnvHotGasValve2Point
OBJECT-IDENTITY
This identifier represents hot gas valve 2.
1.3.6.1.4.1.476.1.42.3.4.7.1.13.2current
lgpEnvRemoteSensorStatisticPoints
OBJECT-IDENTITY
This sub-tree identifies well-known remote sensor statistics in the system.
1.3.6.1.4.1.476.1.42.3.4.7.1.14current
lgpEnvRemoteSensorMinimumPoint
OBJECT-IDENTITY
This identifier represents the minimum value for remote sensor readings.
1.3.6.1.4.1.476.1.42.3.4.7.1.14.1current
lgpEnvRemoteSensorMaximumPoint
OBJECT-IDENTITY
This identifier represents the maximum value for remote sensor readings.
1.3.6.1.4.1.476.1.42.3.4.7.1.14.2current
lgpEnvRemoteSensorAveragePoint
OBJECT-IDENTITY
This identifier represents the average value for remote sensor readings.
1.3.6.1.4.1.476.1.42.3.4.7.1.14.3current
lgpEnvUnits
OBJECT-IDENTITY
This sub-tree is used to register Liebert environmental unit object identifiers.
1.3.6.1.4.1.476.1.42.3.4.8current
lgpEnvWellKnownUnits
OBJECT-IDENTITY
This sub-tree registers well known Liebert Environmental Units. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
1.3.6.1.4.1.476.1.42.3.4.8.1current
lgpEnvHours
OBJECT-IDENTITY
This identifier represents well known time unit of hours.
1.3.6.1.4.1.476.1.42.3.4.8.1.1current
lgpEnvRemoteSensors
OBJECT-IDENTITY
This sub-tree is used to register Liebert environmental remote sensor object identifiers.
1.3.6.1.4.1.476.1.42.3.4.9current
lgpEnvRemoteSensorCalc
OBJECT-TYPE
Calculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control.
1.3.6.1.4.1.476.1.42.3.4.9.1INTEGER {average(1), maximum(2)}read-writecurrent
lgpEnvRemoteSensorTable
OBJECT-TYPE
This table contains a list of remote sensors attached to the environmental unit. The table contains zero, one, or more rows, depending upon the number of sensors attached to the unit.
1.3.6.1.4.1.476.1.42.3.4.9.10not-accessiblecurrent
lgpEnvRemoteSensorEntry
OBJECT-TYPE
This entry defines the attributes to be populated in the various columns of the 'lgpEnvRemoteSensorTable'.
1.3.6.1.4.1.476.1.42.3.4.9.10.1not-accessiblecurrent
lgpEnvRemoteSensorIndex
OBJECT-TYPE
This is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.1Unsigned32not-accessiblecurrent
lgpEnvRemoteSensorId
OBJECT-TYPE
This is the sensor number identifying the sensor.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.2Unsigned32read-onlycurrent
lgpEnvRemoteSensorMode
OBJECT-TYPE
Function assigned to remote sensor. When set to control(2) the sensor will be used in calculation of remote sensor temperature which may be used for heating and cooling control. When set to disable(0) the remote sensor reading is not available. When set to reference(1) the remote sensor reading is available but not used for control.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.3INTEGER {disable(0), reference(1), control(2)}read-writecurrent
lgpEnvRemoteSensorUsrLabel
OBJECT-TYPE
User assigned remote sensor label.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.4DisplayStringread-writecurrent
lgpEnvRemoteSensorTempMeasurementDegF
OBJECT-TYPE
Temperature measured at the temperature sensor reported in degrees Fahrenheit.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.5Integer32read-onlycurrent
lgpEnvRemoteSensorTempMeasurementDegC
OBJECT-TYPE
Temperature measured at the temperature sensor reported in degrees Celsius.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.6Integer32read-onlycurrent