HAWK-I2-MIB
- Registered at
- 1.3.6.1.4.1.3711
- Last updated
- 2006-06-27 12:00
- Organization
- Sinetica Corporation
- Revisions
- 2006-06-27 12:00, 2006-03-07 12:00
- Namespace
- sinetica
- Source file
HAWK-I2-MIB- Digest
sha256:e7cc2c126100d13a45ee697208a48c9ed202b3211e69635d5095be0a1558706a
Description
The MIB module for the Sinetica Hawk-i2.
Contact
Development Department Sinetica Corporation Ltd. Willow House Llancayo Court Usk Monmouthshire NP15 1HY U.K. Tel: +44 (0)871 226 5679 Fax: +44 (0)845 456 3562 Web: www.sinetica.co.uk E-mail: info@sinetica.co.uk
Imports
| From | Symbols |
|---|---|
| INET-ADDRESS-MIB | InetAddress, InetAddressType |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, MacAddress, RowStatus, TEXTUAL-CONVENTION, TruthValue |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
HAWK-I2-MIB INET-ADDRESS-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| ContactState TEXTUAL-CONVENTION Represents the state of a set of contacts. | current | |||
| DisplayString type | ||||
| EnableState TEXTUAL-CONVENTION Represents the state of an enabling flag. | current | |||
| InputContactState TEXTUAL-CONVENTION Represents the state of a set of input contacts. | current | |||
| InputDataType TEXTUAL-CONVENTION Represents the type of data read at an input. | current | |||
| OutputControlState TEXTUAL-CONVENTION Represents the control setiing for an output. | current | |||
| RelayState TEXTUAL-CONVENTION Represents the energised state of a relay. | current |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| sinetica OBJECT-IDENTITY | 1.3.6.1.4.1.3711 | |||
| traps OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.0 | |||
| v1 OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1 | |||
| objects OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1 | |||
| inputs OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.1 | |||
| ipCommon OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.1.1 | |||
| ipEnable OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.1.1.1 | |||
| ipSelect OBJECT-TYPE Selects the channel to be enabled or disabled by ipInsert. A value of 0 selects no channel. | 1.3.6.1.4.1.3711.24.1.1.1.1.1.1 | INTEGER (0..24) | read-write | current |
| ipInsert OBJECT-TYPE Inserts or removes the channel selected by ipSelect - causes an entry for that channel to be created or deleted in the relevant tables. - Read behaviour is undefined. | 1.3.6.1.4.1.3711.24.1.1.1.1.1.2 | InputDataType | read-write | current |
| ipTHA OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.1.2 | |||
| ipTempScaleFlag OBJECT-TYPE Temperature scale (Celsius/Fahrenheit) for temperature monitoring. | 1.3.6.1.4.1.3711.24.1.1.1.2.1 | INTEGER {celsius(1), fahrenheit(2), kelvin(3)} | read-write | current |
| ipTHATable OBJECT-TYPE A table giving data for all enabled inputs with analogue-type monitoring. | 1.3.6.1.4.1.3711.24.1.1.1.2.2 | not-accessible | current | |
| ipTHAEntry OBJECT-TYPE A conceptual row containing information about one analogue-type input. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1 | not-accessible | current | |
| ipTHAChan OBJECT-TYPE The input number. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.1 | INTEGER (0..24) | read-only | current |
| ipTHARS OBJECT-TYPE The analogue-type input table row status. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.2 | RowStatus | read-only | current |
| ipTHAName OBJECT-TYPE The name of this input | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.3 | DisplayString (SIZE(0..15)) | read-write | current |
| ipTHALocn OBJECT-TYPE A system-defined name for the physical location of this input, e.g. MCU. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.4 | DisplayString (SIZE(0..4)) | read-only | current |
| ipTHAAutoDetect OBJECT-TYPE Indicates that the type of data this input is monitoring is selected automatically. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.5 | TruthValue | read-write | current |
| ipTHAType OBJECT-TYPE Indicates the type of data this input is monitoring. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.6 | InputDataType | read-write | current |
| ipTHAValue OBJECT-TYPE The current reading in the relevant measurement units. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.7 | INTEGER (-200..1000) | read-only | current |
| ipTHAScaling OBJECT-TYPE Scaling factor for ipTHAValue when ipTHAType=analogue. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.8 | INTEGER (0..100) | read-write | current |
| ipTHAOffset OBJECT-TYPE Calibration offset in the same units as for ipTHAValue. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.9 | INTEGER (-100..100) | read-write | current |
| ipTHAHysteresis OBJECT-TYPE Hysteresis on threshold levels in the same units as for ipTHAValue. | 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.10 | INTEGER (-100..100) | read-write | current |
| ipTHATrapsCfg OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.1.2.3 | |||
| ipTHAThreshTable OBJECT-TYPE A table listing the trap threshold levels for all enabled inputs with analogue-type monitoring. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.1 | not-accessible | current | |
| ipTHAThreshEntry OBJECT-TYPE A conceptual row containing threshold information for one analogue-type input. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1 | not-accessible | current | |
| ipTHAThreshChan OBJECT-TYPE The input number. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.1 | INTEGER (0..24) | read-only | current |
| ipTHAThreshRS OBJECT-TYPE The analogue-type input table row status. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.2 | RowStatus | read-only | current |
| ipTHAUCL OBJECT-TYPE The Upper Critical Limit for this input in the same units as for ipTHAValue. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.3 | INTEGER (-200..1000) | read-write | current |
| ipTHAUWL OBJECT-TYPE The Upper Warning Limit for this input in the same units as for ipTHAValue. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.4 | INTEGER (-200..1000) | read-write | current |
| ipTHALWL OBJECT-TYPE The Lower Warning Limit for this input in the same units as for ipTHAValue. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.5 | INTEGER (-200..1000) | read-write | current |
| ipTHALCL OBJECT-TYPE The Lower Critical Limit for this input in the same units as for ipTHAValue. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.6 | INTEGER (-200..1000) | read-write | current |
| ipTHATrapEnTable OBJECT-TYPE The table that controls trap enabling for all enabled inputs with analogue-type monitoring. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.2 | not-accessible | current | |
| ipTHATrapEnEntry OBJECT-TYPE A conceptual row containing trap enabling information for one analogue-type input. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1 | not-accessible | current | |
| ipTHATrapEnChan OBJECT-TYPE The input number. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.1 | INTEGER (0..24) | read-only | current |
| ipTHATrapEnRS OBJECT-TYPE The analogue-type input table row status. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.2 | RowStatus | read-only | current |
| ipTHAUCLTrapEn OBJECT-TYPE Enables and disables input UCL alarm traps. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.3 | TruthValue | read-write | current |
| ipTHAUWLTrapEn OBJECT-TYPE Enables and disables input UWL alarm traps. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.4 | TruthValue | read-write | current |
| ipTHALWLTrapEn OBJECT-TYPE Enables and disables input LWL alarm traps. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.5 | TruthValue | read-write | current |
| ipTHALCLTrapEn OBJECT-TYPE Enables and disables input LCL alarm traps. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.6 | TruthValue | read-write | current |
| ipTHATrapPerTable OBJECT-TYPE The table that controls trap repetition for all enabled inputs with analogue-type monitoring. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.3 | not-accessible | current | |
| ipTHATrapPerEntry OBJECT-TYPE A conceptual row containing trap repetition information for one analogue-type input. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1 | not-accessible | current | |
| ipTHATrapPerChan OBJECT-TYPE The input number. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.1 | INTEGER (0..24) | read-only | current |
| ipTHATrapPerRS OBJECT-TYPE The table row status. | 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.2 | RowStatus | read-only | current |
| ipTHATrapUCLPer OBJECT-TYPE Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds | 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.3 | INTEGER (30..32000) | read-write | current |
| ipTHATrapUWLPer OBJECT-TYPE Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds | 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.4 | INTEGER (30..32000) | read-write | current |
| ipTHATrapLWLPer OBJECT-TYPE Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds | 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.5 | INTEGER (30..32000) | read-write | current |
| ipTHATrapLCLPer OBJECT-TYPE Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds | 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.6 | INTEGER (30..32000) | read-write | current |
| ipContact OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.1.3 | |||
| ipContTable OBJECT-TYPE A table listing the parameters and data for all enabled inputs with contact-type monitoring. | 1.3.6.1.4.1.3711.24.1.1.1.3.1 | not-accessible | current | |
| ipContEntry OBJECT-TYPE A conceptual row containing information about one contact input. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1 | not-accessible | current | |
| ipContChan OBJECT-TYPE The input number. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.1 | INTEGER (0..24) | read-only | current |
| ipContRS OBJECT-TYPE The contact input table row status. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.2 | RowStatus | read-only | current |
| ipContName OBJECT-TYPE The name of this input | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.3 | DisplayString (SIZE(0..15)) | read-write | current |
| ipContLocn OBJECT-TYPE A system-defined name for the physical location of this input, e.g. MCU. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.4 | DisplayString (SIZE(0..4)) | read-only | current |
| ipContAutoDetect OBJECT-TYPE Indicates that the type of data this input is monitoring is selected automatically. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.5 | TruthValue | read-write | current |
| ipContNormState OBJECT-TYPE The normal state for this contact. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.6 | ContactState | read-write | current |
| ipContCurrState OBJECT-TYPE The current state of this contact. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.7 | InputContactState | read-only | current |
| ipContTrigMode OBJECT-TYPE The contact trigger mode, level, +ve edge, -ve edge. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.8 | INTEGER {positiveEdge(1), negativeEdge(2), level(3)} | read-write | current |
| ipContReset OBJECT-TYPE Resets the contact after triggering in edge mode. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.9 | Unsigned32 | read-write | current |
| ipContTrapEn OBJECT-TYPE Configure contact input traps. | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.10 | INTEGER {critical(1), warning(2), information(3), disabled(255)} | read-write | current |
| ipContTrapPeriod OBJECT-TYPE Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds | 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.11 | INTEGER (30..32000) | read-write | current |
| outputs OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.2 | |||
| opEnable OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.2.1 | |||
| opSelect OBJECT-TYPE Selects the channel to be enabled or disabled by opEnable. A value of 0 selects no channel. | 1.3.6.1.4.1.3711.24.1.1.2.1.1 | INTEGER (0..24) | read-write | current |
| opInsert OBJECT-TYPE Enables or disables the channel selected by opSelect - causes an entry for that channel to be created or deleted in the relevant tables. - Read behaviour is undefined. | 1.3.6.1.4.1.3711.24.1.1.2.1.2 | EnableState | read-write | current |
| opTable OBJECT-TYPE A table listing the parameters and data for all outputs that are enabled and available (i.e. its extension unit is connected). | 1.3.6.1.4.1.3711.24.1.1.2.2 | not-accessible | current | |
| opEntry OBJECT-TYPE A conceptual row containing information about one output. | 1.3.6.1.4.1.3711.24.1.1.2.2.1 | not-accessible | current | |
| opChan OBJECT-TYPE The output number. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.1 | INTEGER (0..18) | read-only | current |
| opRS OBJECT-TYPE The contact input table row status. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.2 | RowStatus | read-only | current |
| opName OBJECT-TYPE A user-defined name for this output. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.3 | DisplayString (SIZE(0..15)) | read-write | current |
| opLocn OBJECT-TYPE A system-defined name for the physical location of this output, e.g. MCU. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.4 | DisplayString (SIZE(0..4)) | read-only | current |
| opNormState OBJECT-TYPE Sets or reads the required normal state of this output. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.5 | RelayState | read-write | current |
| opCurrState OBJECT-TYPE Reads the current state of this output. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.6 | RelayState | read-only | current |
| opOnDelTime OBJECT-TYPE Sets the 'on' delay time for this output. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.7 | Unsigned32 | read-write | current |
| opOffDelTime OBJECT-TYPE Sets the 'off' delay time for this output. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.8 | Unsigned32 | read-write | current |
| opBooleanEqn OBJECT-TYPE Boolean equation string | 1.3.6.1.4.1.3711.24.1.1.2.2.1.9 | DisplayString | read-write | current |
| opTrapEn OBJECT-TYPE Configure output traps. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.10 | INTEGER {critical(1), warning(2), information(3), disabled(255)} | read-write | current |
| opTrapPeriod OBJECT-TYPE Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds | 1.3.6.1.4.1.3711.24.1.1.2.2.1.11 | INTEGER (30..32000) | read-write | current |
| opControlState OBJECT-TYPE Reads the current control state of an output. | 1.3.6.1.4.1.3711.24.1.1.2.2.1.12 | OutputControlState | read-write | current |
| keypads OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.4 | |||
| kpEnable OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.4.1 | |||
| kpSelect OBJECT-TYPE Selects the keypad to be enabled or disabled by kpEnable. A value of 0 selects no keypad. | 1.3.6.1.4.1.3711.24.1.1.4.1.1 | INTEGER (0..24) | read-write | current |
| kpInsert OBJECT-TYPE Enables or disables the keypad selected by kpSelect - causes an entry for that keypad to be created or deleted in the relevant tables. - Read behaviour is undefined. | 1.3.6.1.4.1.3711.24.1.1.4.1.2 | EnableState | read-write | current |
| kpCtlTable OBJECT-TYPE A table listing the parameters and data for the keypads. | 1.3.6.1.4.1.3711.24.1.1.4.2 | not-accessible | current | |
| kpCtlEntry OBJECT-TYPE A conceptual row containing information about one keypad. | 1.3.6.1.4.1.3711.24.1.1.4.2.1 | not-accessible | current | |
| kpNumber OBJECT-TYPE The keypad number. | 1.3.6.1.4.1.3711.24.1.1.4.2.1.1 | INTEGER (1..2) | read-only | current |
| kpRS OBJECT-TYPE The keypad table row status. | 1.3.6.1.4.1.3711.24.1.1.4.2.1.2 | RowStatus | read-only | current |
| kpManufacturer OBJECT-TYPE The name of the manufacturer of the keypad. | 1.3.6.1.4.1.3711.24.1.1.4.2.1.3 | DisplayString (SIZE(0..15)) | read-write | current |
| kpName OBJECT-TYPE A name identifying the keypad. | 1.3.6.1.4.1.3711.24.1.1.4.2.1.4 | DisplayString (SIZE(0..15)) | read-write | current |
| kpDoorLatchTimeOut OBJECT-TYPE Time-out value in seconds for which the door latch is held open. | 1.3.6.1.4.1.3711.24.1.1.4.2.1.5 | Unsigned32 | read-write | current |
| kpRtnToStndbyTimeOut OBJECT-TYPE Time-out value in seconds for Return to Standby Mode | 1.3.6.1.4.1.3711.24.1.1.4.2.1.6 | INTEGER (0..99) | read-write | current |
| kpEntryCodeValid OBJECT-TYPE Set if previous keypad entry was valid. | 1.3.6.1.4.1.3711.24.1.1.4.2.1.7 | TruthValue | read-only | current |
| kpDoorOpenTimeOut OBJECT-TYPE Time-out value in seconds for Door Open. | 1.3.6.1.4.1.3711.24.1.1.4.2.1.8 | INTEGER (0..99) | read-write | current |
| kpRemoteDoorOpen OBJECT-TYPE Set to open the door. | 1.3.6.1.4.1.3711.24.1.1.4.2.1.9 | TruthValue | read-write | current |
| kpInUseTrapEn OBJECT-TYPE 'keypad in use' trap enable | 1.3.6.1.4.1.3711.24.1.1.4.2.1.10 | INTEGER {critical(1), warning(2), information(3), disabled(255)} | read-write | current |
| acus OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.5 | |||
| acuEnable OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.5.1 | |||
| acuSelect OBJECT-TYPE Selects the ACU to be enabled or disabled by acuEnable. A value of 0 selects no ACU. | 1.3.6.1.4.1.3711.24.1.1.5.1.1 | INTEGER (0..24) | read-write | current |
| acuInsert OBJECT-TYPE Enables or disables the ACU selected by acuSelect - causes an entry for that ACU to be created or deleted in the relevant tables. - Read behaviour is undefined. | 1.3.6.1.4.1.3711.24.1.1.5.1.2 | EnableState | read-write | current |
| acuCtlTable OBJECT-TYPE A table listing the parameters and data for the ACUs. | 1.3.6.1.4.1.3711.24.1.1.5.2 | not-accessible | current | |
| acuCtlEntry OBJECT-TYPE A conceptual row containing information about one ACU. | 1.3.6.1.4.1.3711.24.1.1.5.2.1 | not-accessible | current | |
| acuNumber OBJECT-TYPE The ACU number. | 1.3.6.1.4.1.3711.24.1.1.5.2.1.1 | INTEGER (1..6) | read-only | current |
| acuCtlRS OBJECT-TYPE The ACU table row status. | 1.3.6.1.4.1.3711.24.1.1.5.2.1.2 | RowStatus | read-only | current |
| acuManufacturer OBJECT-TYPE The name of the manufacturer of the ACU. | 1.3.6.1.4.1.3711.24.1.1.5.2.1.3 | DisplayString (SIZE(0..15)) | read-write | current |
| acuName OBJECT-TYPE A name identifying the ACU. | 1.3.6.1.4.1.3711.24.1.1.5.2.1.4 | DisplayString (SIZE(0..15)) | read-write | current |
| acuDoorLatchTimeOut OBJECT-TYPE Time-out value in seconds for which the door latch is held open. | 1.3.6.1.4.1.3711.24.1.1.5.2.1.5 | Unsigned32 | read-write | current |
| acuRtnToStndbyTimeOut OBJECT-TYPE Time-out value in seconds for Return to Standby Mode | 1.3.6.1.4.1.3711.24.1.1.5.2.1.6 | INTEGER (0..99) | read-write | current |
| acuEntryCodeValid OBJECT-TYPE Set if previous ACU entry was valid. | 1.3.6.1.4.1.3711.24.1.1.5.2.1.7 | TruthValue | read-only | current |
| acuDoorOpenTimeOut OBJECT-TYPE Time-out value in seconds for Door Open. | 1.3.6.1.4.1.3711.24.1.1.5.2.1.8 | INTEGER (0..99) | read-write | current |
| acuRemoteDoorOpen OBJECT-TYPE Set to open the door. | 1.3.6.1.4.1.3711.24.1.1.5.2.1.9 | TruthValue | read-write | current |
| acuInUseTrapEn OBJECT-TYPE 'ACU in use' trap enable | 1.3.6.1.4.1.3711.24.1.1.5.2.1.10 | INTEGER {critical(1), warning(2), information(3), disabled(255)} | read-write | current |
| access OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.6 | |||
| accUserCtl OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.6.1 | |||
| accUserInstance OBJECT-TYPE A value of 0 causes an access user to be created in the relevant tables. A non-zero value causes the nominated access user table entries to be deleted. | 1.3.6.1.4.1.3711.24.1.1.6.1.1 | Unsigned32 | read-write | current |
| accUserTable OBJECT-TYPE A table controlling the access users. | 1.3.6.1.4.1.3711.24.1.1.6.1.2 | not-accessible | current | |
| accUserEntry OBJECT-TYPE A conceptual row containing information about one ACU user. | 1.3.6.1.4.1.3711.24.1.1.6.1.2.1 | not-accessible | current | |
| accUserNumber OBJECT-TYPE The the access user-table entry number. | 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.1 | INTEGER (0..20) | read-only | current |
| accUserRS OBJECT-TYPE The access user table row status. | 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.2 | RowStatus | read-only | current |
| accUserName OBJECT-TYPE A name identifying the access user. | 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.3 | DisplayString (SIZE(0..15)) | read-write | current |
| accUserCode OBJECT-TYPE The user's access code. | 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.4 | OCTET STRING (SIZE(0..15)) | read-write | current |
| accUserPrivileges OBJECT-TYPE The ACUs and keypads that the user is allowed to gain access through - comma-separated numerical strings. | 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.5 | DisplayString (SIZE(0..11)) | read-write | current |
| accUserExpires OBJECT-TYPE A text string which specifies when the access code in the row expires. The format is defined by the application. | 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.6 | DisplayString | read-write | current |
| accUserSetup OBJECT-TYPE A free form octet string for programming accUserTable. The format is defined by the application. | 1.3.6.1.4.1.3711.24.1.1.6.1.3 | OCTET STRING | read-write | current |
| pdus OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.7 | |||
| pduCommon OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.7.1 | |||
| pdusEnable OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.7.1.1 | |||
| pduSelect OBJECT-TYPE Selects the PDU to be enabled or disabled by pduEnable. A value of 0 selects no PDU. | 1.3.6.1.4.1.3711.24.1.1.7.1.1.1 | INTEGER (0..6) | read-write | current |
| pduInsert OBJECT-TYPE Enables or disables the PDU selected by pduSelect - causes an entry for that PDU to be created or deleted in the relevant tables. - Read behaviour is undefined. | 1.3.6.1.4.1.3711.24.1.1.7.1.1.2 | EnableState | read-write | current |
| pduTable OBJECT-TYPE A table containing information about each enabled PDU. | 1.3.6.1.4.1.3711.24.1.1.7.1.2 | not-accessible | current | |
| pduEntry OBJECT-TYPE A conceptual row containing information about one PDU. | 1.3.6.1.4.1.3711.24.1.1.7.1.2.1 | not-accessible | current | |
| pduNumber OBJECT-TYPE The PDU number. | 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.1 | INTEGER (1..8) | read-only | current |
| pduRS OBJECT-TYPE The PDU table row status. | 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.2 | RowStatus | read-only | current |
| pduName OBJECT-TYPE A string identifying the PDU. | 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.3 | DisplayString (SIZE(0..15)) | read-write | current |
| pduOutEn OBJECT-TYPE Enables/disables PDU power outlet control - causes an entry for outlets to be created in each relevant PDU table. | 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.4 | TruthValue | read-write | current |
| pduMonEn OBJECT-TYPE Enables/disables PDU power monitoring - causes an entry for monitoring to be created in each relevant PDU table. | 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.5 | TruthValue | read-write | current |
| pduCommsFail OBJECT-TYPE Indicates comms. status for the PDU. | 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.6 | INTEGER {commsGood(1), commsFailed(2), commsBadData(3)} | read-only | current |
| pduOutlets OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.7.2 | |||
| pduOutAll OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.7.2.1 | |||
| pduOutCycleAll OBJECT-TYPE Sets the required state of all power outlets on all connected PDUs. | 1.3.6.1.4.1.3711.24.1.1.7.2.1.1 | INTEGER {up(1), down(2)} | read-write | current |
| pduOutCycleAllPwd OBJECT-TYPE Controls access to setting the required state of all power outlets on all connected PDUs. | 1.3.6.1.4.1.3711.24.1.1.7.2.1.2 | DisplayString (SIZE(0..7)) | read-write | current |
| pduOutCycleAllAbort OBJECT-TYPE Abort command for pduOutCycleAll. | 1.3.6.1.4.1.3711.24.1.1.7.2.1.3 | Unsigned32 | read-write | current |
| pduOutGlobalCycleDelay OBJECT-TYPE Sets the delay period for pduOutCycleAll and pduOutCycle commands before they start to execute. | 1.3.6.1.4.1.3711.24.1.1.7.2.1.4 | Unsigned32 | read-write | current |
| pduOutGlobalRebootTime OBJECT-TYPE Sets the off to on delay period for a pdu outlet reboot. | 1.3.6.1.4.1.3711.24.1.1.7.2.1.5 | Unsigned32 | read-write | current |
| pduOutGlobalCycleAbortTime OBJECT-TYPE Time delay to abort power outlet setting task. | 1.3.6.1.4.1.3711.24.1.1.7.2.1.6 | Unsigned32 | read-write | current |
| pduOutCmnTable OBJECT-TYPE A table containing information about the power outlets of all PDUs enabled for outlet control. | 1.3.6.1.4.1.3711.24.1.1.7.2.2 | not-accessible | current | |
| pduOutCmnEntry OBJECT-TYPE A conceptual row containing information about the power outlets of one PDU. | 1.3.6.1.4.1.3711.24.1.1.7.2.2.1 | not-accessible | current | |
| pduOutCmnPduNumber OBJECT-TYPE The PDU number. | 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.1 | INTEGER (1..8) | read-only | current |
| pduOutCmnRS OBJECT-TYPE The PDU table row status. | 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.2 | RowStatus | read-only | current |
| pduNumOfOutlets OBJECT-TYPE The number of switchable outlets on the PDU - determines the number of entries to be created in the outlet table for the relevant PDU. | 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.3 | INTEGER (1..32) | read-write | current |
| pduOutCycle OBJECT-TYPE Sets the required state of all power outlets on the PDU. | 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.4 | INTEGER {up(1), down(2)} | read-write | current |
| pduOutCyclePwd OBJECT-TYPE Password controling access to setting the required state of all power outlets on the PDU. | 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.5 | DisplayString (SIZE(0..7)) | read-write | current |
| pduOutCycleAbortTask OBJECT-TYPE Abort power outlet setting task. | 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.6 | Unsigned32 | read-write | current |
| pduOutCycleAbortTime OBJECT-TYPE Time delay to abort power outlet setting task. | 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.7 | Unsigned32 | read-write | current |
| pduOutTable OBJECT-TYPE A table listing the states and descriptions for each outlet on the PDU. | 1.3.6.1.4.1.3711.24.1.1.7.2.3 | not-accessible | current | |
| pduOutEntry OBJECT-TYPE A row containing information about one PDU outlet. | 1.3.6.1.4.1.3711.24.1.1.7.2.3.1 | not-accessible | current | |
| pduOutPduNumber OBJECT-TYPE The PDU number on which the outlet resides. | 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.1 | INTEGER (1..8) | read-only | current |
| pduOutNumber OBJECT-TYPE The outlet number. | 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.2 | INTEGER (1..32) | read-only | current |
| pduOutRS OBJECT-TYPE The PDU table row status. | 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.3 | RowStatus | read-only | current |
| pduOutName OBJECT-TYPE A name identifying the outlet. | 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.4 | DisplayString (SIZE(0..31)) | read-write | current |
| pduOutOn OBJECT-TYPE The current state for this outlet. | 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.5 | INTEGER {on(1), off(2), reboot(3)} | read-write | current |
| pduOutPwd OBJECT-TYPE The password for this outlet. | 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.6 | DisplayString (SIZE(0..7)) | read-write | current |
| pduOutCycleDelay OBJECT-TYPE The on/off delay for this outlet in seconds. | 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.7 | Unsigned32 | read-only | current |
| pduOutRebootPeriod OBJECT-TYPE The pduOutOn reboot off period for this outlet in seconds. | 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.8 | Unsigned32 | read-only | current |
| pduMonitor OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.7.3 | |||
| pduMonTable OBJECT-TYPE A table containing monitor information for all PDUs enabled for monitoring. | 1.3.6.1.4.1.3711.24.1.1.7.3.1 | not-accessible | current | |
| pduMonEntry OBJECT-TYPE A conceptual row containing monitor information for one PDU. | 1.3.6.1.4.1.3711.24.1.1.7.3.1.1 | not-accessible | current | |
| pduMonPduNumber OBJECT-TYPE The PDU number. | 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.1 | INTEGER (1..8) | read-only | current |
| pduMonRS OBJECT-TYPE The PDU table row status. | 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.2 | RowStatus | read-only | current |
| pduRMSVoltsValue OBJECT-TYPE RMS Volts value in volts | 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.3 | INTEGER (0..500) | read-only | current |
| pduRMSAmpsValue OBJECT-TYPE RMS current value in 0.1 Amps | 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.4 | INTEGER (0..500) | read-only | current |
| pduTotalEnergyValue OBJECT-TYPE Total energy value in 0.1 kWh | 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.5 | INTEGER (0..9999999) | read-only | current |
| pduMeanKVAValue OBJECT-TYPE Kilo Volt-Amperes value in 0.1 kVA | 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.6 | INTEGER (0..100000) | read-only | current |
| pduMeanKWattsValue OBJECT-TYPE Kilo Watts value in 0.1 kW | 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.7 | INTEGER (0..100000) | read-only | current |
| pduPwrFactorValue OBJECT-TYPE Power factor value in 0.01 | 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.8 | INTEGER (0..100) | read-only | current |
| pduTrapThreshTable OBJECT-TYPE A table containing information about the trap threshold values for all PDUs enabled for monitoring. | 1.3.6.1.4.1.3711.24.1.1.7.3.2 | not-accessible | current | |
| pduTrapThreshEntry OBJECT-TYPE A conceptual row containing information about the trap threshold values for one PDU. | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1 | not-accessible | current | |
| pduTrapThreshPduNumber OBJECT-TYPE The PDU number. | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.1 | INTEGER (1..8) | read-only | current |
| pduTrapThreshRS OBJECT-TYPE The PDU table row status. | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.2 | RowStatus | read-only | current |
| pduRMSVoltsUCL OBJECT-TYPE rms UCL value in volts | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.3 | INTEGER (0..500) | read-write | current |
| pduRMSVoltsUWL OBJECT-TYPE rms UWL value in volts | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.4 | INTEGER (0..500) | read-write | current |
| pduRMSVoltsLWL OBJECT-TYPE rms LWL value in volts | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.5 | INTEGER (0..500) | read-write | current |
| pduRMSVoltsLCL OBJECT-TYPE rms LCL value in volts | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.6 | INTEGER (0..500) | read-write | current |
| pduRMSAmpsUCL OBJECT-TYPE rms UCL value in 0.1 amps | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.7 | INTEGER (0..500) | read-write | current |
| pduRMSAmpsUWL OBJECT-TYPE rms UWL value in 0.1 amps | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.8 | INTEGER (0..500) | read-write | current |
| pduRMSAmpsLWL OBJECT-TYPE rms LWL value in 0.1 amps | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.9 | INTEGER (0..500) | read-write | current |
| pduRMSAmpsLCL OBJECT-TYPE rms LCL value in 0.1 amps | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.10 | INTEGER (0..500) | read-write | current |
| pduEnergyUCL OBJECT-TYPE Total energy UCL value in 0.1 kWh | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.11 | INTEGER (0..9999999) | read-write | current |
| pduEnergyUWL OBJECT-TYPE Total energy UWL value in 0.1 kWh | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.12 | INTEGER (0..9999999) | read-write | current |
| pduMeanKVAUCL OBJECT-TYPE Mean kVA UCL value in 0.1 kVA | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.13 | INTEGER (0..100000) | read-write | current |
| pduMeanKVAUWL OBJECT-TYPE Mean kVA UWL value in 0.1 kVA | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.14 | INTEGER (0..100000) | read-write | current |
| pduMeanKVALWL OBJECT-TYPE Mean kVA LWL value in 0.1 kVA | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.15 | INTEGER (0..100000) | read-write | current |
| pduMeanKVALCL OBJECT-TYPE Mean kVA LCL value in 0.1 kVA | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.16 | INTEGER (0..100000) | read-write | current |
| pduMeanKWattsUCL OBJECT-TYPE Mean power UCL value in 0.1 kW | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.17 | INTEGER (0..100000) | read-write | current |
| pduMeanKWattsUWL OBJECT-TYPE Mean power UWL value in 0.1 kW | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.18 | INTEGER (0..100000) | read-write | current |
| pduMeanKWattsLWL OBJECT-TYPE Mean power LWL value in 0.1 kW | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.19 | INTEGER (0..100000) | read-write | current |
| pduMeanKWattsLCL OBJECT-TYPE Mean power LCL value in 0.1 kW | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.20 | INTEGER (0..100000) | read-write | current |
| pduPwrFactorUCL OBJECT-TYPE Power factor UCL value in 0.01 | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.21 | INTEGER (0..100) | read-write | current |
| pduPwrFactorUWL OBJECT-TYPE Power factor UWL value in 0.01 | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.22 | INTEGER (0..100) | read-write | current |
| pduPwrFactorLWL OBJECT-TYPE Power factor LWL value in 0.01 | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.23 | INTEGER (0..100) | read-write | current |
| pduPwrFactorLCL OBJECT-TYPE Power factor LCL value in 0.01 | 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.24 | INTEGER (0..100) | read-write | current |
| pduTrapEnTable OBJECT-TYPE The table which controls threshold value trap enabling for all PDUs enabled for monitoring. | 1.3.6.1.4.1.3711.24.1.1.7.3.3 | not-accessible | current | |
| pduTrapEnEntry OBJECT-TYPE A conceptual row containing information about one PDU. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1 | not-accessible | current | |
| pduTrapEnPduNumber OBJECT-TYPE The PDU number. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.1 | INTEGER (1..8) | read-only | current |
| pduTrapEnRS OBJECT-TYPE The PDU table row status. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.2 | RowStatus | read-only | current |
| pduRMSVoltsUCLTrapEn OBJECT-TYPE Enables Volts UCL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.3 | TruthValue | read-write | current |
| pduRMSVoltsUWLTrapEn OBJECT-TYPE Enables UWL Volts trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.4 | TruthValue | read-write | current |
| pduRMSVoltsLWLTrapEn OBJECT-TYPE Enables LWL Volts trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.5 | TruthValue | read-write | current |
| pduRMSVoltsLCLTrapEn OBJECT-TYPE Enables LCL Volts trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.6 | TruthValue | read-write | current |
| pduRMSAmpsUCLTrapEn OBJECT-TYPE Enables UCL current trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.7 | TruthValue | read-write | current |
| pduRMSAmpsUWLTrapEn OBJECT-TYPE Enables UWL current trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.8 | TruthValue | read-write | current |
| pduRMSAmpsLWLTrapEn OBJECT-TYPE Enables LWL current trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.9 | TruthValue | read-write | current |
| pduRMSAmpsLCLTrapEn OBJECT-TYPE Enables LCL current trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.10 | TruthValue | read-write | current |
| pduEnergyUCLTrapEn OBJECT-TYPE Enables UCL total energy trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.11 | TruthValue | read-write | current |
| pduEnergyUWLTrapEn OBJECT-TYPE Enables UWL total energy trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.12 | TruthValue | read-write | current |
| pduMeanKVAUCLTrapEn OBJECT-TYPE Enables mean kVA UCL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.13 | TruthValue | read-write | current |
| pduMeanKVAUWLTrapEn OBJECT-TYPE Enables mean kVA UWL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.14 | TruthValue | read-write | current |
| pduMeanKVALWLTrapEn OBJECT-TYPE Enables mean kVA LWL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.15 | TruthValue | read-write | current |
| pduMeanKVALCLTrapEn OBJECT-TYPE Enables mean kVA LCL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.16 | TruthValue | read-write | current |
| pduMeanKWattsUCLTrapEn OBJECT-TYPE Enables mean power UCL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.17 | TruthValue | read-write | current |
| pduMeanKWattsUWLTrapEn OBJECT-TYPE Enables mean power UWL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.18 | TruthValue | read-write | current |
| pduMeanKWattsLWLTrapEn OBJECT-TYPE Enables mean power LWL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.19 | TruthValue | read-write | current |
| pduMeanKWattsLCLTrapEn OBJECT-TYPE Enables mean power LCL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.20 | TruthValue | read-write | current |
| pduPwrFactorUCLTrapEn OBJECT-TYPE Enables power factor UCL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.21 | TruthValue | read-write | current |
| pduPwrFactorUWLTrapEn OBJECT-TYPE Enables power factor UWL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.22 | TruthValue | read-write | current |
| pduPwrFactorLWLTrapEn OBJECT-TYPE Enables power factor LWL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.23 | TruthValue | read-write | current |
| pduPwrFactorLCLTrapEn OBJECT-TYPE Enables power factor LCL trap. | 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.24 | TruthValue | read-write | current |
| pduTrapPerTable OBJECT-TYPE The table which controls threshold value trap repetition for all PDUs enabled for monitoring. | 1.3.6.1.4.1.3711.24.1.1.7.3.4 | not-accessible | current | |
| pduTrapPerEntry OBJECT-TYPE A conceptual row containing information about one PDU. | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1 | not-accessible | current | |
| pduTrapPduNumber OBJECT-TYPE The PDU number. | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.1 | INTEGER (1..8) | read-only | current |
| pduTrapPerRS OBJECT-TYPE The PDU table row status. | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.2 | RowStatus | read-only | current |
| pduRMSVoltsUCLTrapPer OBJECT-TYPE Sets UCL Volts trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.3 | INTEGER (30..32000) | read-write | current |
| pduRMSVoltsUWLTrapPer OBJECT-TYPE Sets UWL Volts trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.4 | INTEGER (30..32000) | read-write | current |
| pduRMSVoltsLWLTrapPer OBJECT-TYPE Sets LWL Volts trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.5 | INTEGER (30..32000) | read-write | current |
| pduRMSVoltsLCLTrapPer OBJECT-TYPE Sets LCL Volts trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.6 | INTEGER (30..32000) | read-write | current |
| pduRMSAmpsUCLTrapPer OBJECT-TYPE Sets UCL current trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.7 | INTEGER (30..32000) | read-write | current |
| pduRMSAmpsUWLTrapPer OBJECT-TYPE Sets UWL current trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.8 | INTEGER (30..32000) | read-write | current |
| pduRMSAmpsLWLTrapPer OBJECT-TYPE Sets LWL current trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.9 | INTEGER (30..32000) | read-write | current |
| pduRMSAmpsLCLTrapPer OBJECT-TYPE Sets LCL current trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.10 | INTEGER (30..32000) | read-write | current |
| pduEnergyUCLTrapPer OBJECT-TYPE Sets UCL total energy trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.11 | INTEGER (30..32000) | read-write | current |
| pduEnergyUWLTrapPer OBJECT-TYPE Sets UWL total energy trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.12 | INTEGER (30..32000) | read-write | current |
| pduMeanKVAUCLTrapPer OBJECT-TYPE Sets mean kVA UCL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.13 | INTEGER (30..32000) | read-write | current |
| pduMeanKVAUWLTrapPer OBJECT-TYPE Sets mean kVA UWL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.14 | INTEGER (30..32000) | read-write | current |
| pduMeanKVALWLTrapPer OBJECT-TYPE Sets mean kVA LWL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.15 | INTEGER (30..32000) | read-write | current |
| pduMeanKVALCLTrapPer OBJECT-TYPE Sets mean kVA LCL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.16 | INTEGER (30..32000) | read-write | current |
| pduMeanKWattsUCLTrapPer OBJECT-TYPE Sets mean power UCL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.17 | INTEGER (30..32000) | read-write | current |
| pduMeanKWattsUWLTrapPer OBJECT-TYPE Sets mean power UWL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.18 | INTEGER (30..32000) | read-write | current |
| pduMeanKWattsLWLTrapPer OBJECT-TYPE Sets mean power LWL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.19 | INTEGER (30..32000) | read-write | current |
| pduMeanKWattsLCLTrapPer OBJECT-TYPE Sets mean power LCL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.20 | INTEGER (30..32000) | read-write | current |
| pduPwrFactorUCLTrapPer OBJECT-TYPE Sets power factor UCL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.21 | INTEGER (30..32000) | read-write | current |
| pduPwrFactorUWLTrapPer OBJECT-TYPE Sets power factor UWL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.22 | INTEGER (30..32000) | read-write | current |
| pduPwrFactorLWLTrapPer OBJECT-TYPE Sets power factor LWL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.23 | INTEGER (30..32000) | read-write | current |
| pduPwrFactorLCLTrapPer OBJECT-TYPE Sets power factor LCL trap repeat rate in seconds | 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.24 | INTEGER (30..32000) | read-write | current |
| inventory OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.99 | |||
| invProdSignature OBJECT-TYPE Product data signature. | 1.3.6.1.4.1.3711.24.1.1.99.1 | DisplayString (SIZE(0..7)) | read-only | current |
| invProdFormatVer OBJECT-TYPE Product data format version. | 1.3.6.1.4.1.3711.24.1.1.99.2 | DisplayString (SIZE(0..7)) | read-only | current |
| invManufCode OBJECT-TYPE Manufacturer code. | 1.3.6.1.4.1.3711.24.1.1.99.3 | DisplayString (SIZE(0..15)) | read-only | current |
| invOrderNum OBJECT-TYPE Order number. | 1.3.6.1.4.1.3711.24.1.1.99.4 | DisplayString (SIZE(0..7)) | read-only | current |
| invBatchNum OBJECT-TYPE Batch number. | 1.3.6.1.4.1.3711.24.1.1.99.5 | DisplayString (SIZE(0..7)) | read-only | current |
| invProdTestTime OBJECT-TYPE Data and time of production test. | 1.3.6.1.4.1.3711.24.1.1.99.6 | DisplayString (SIZE(0..15)) | read-only | current |
| invUnitName OBJECT-TYPE Unit name. | 1.3.6.1.4.1.3711.24.1.1.99.7 | DisplayString (SIZE(0..15)) | read-only | current |
| invUnitPartNum OBJECT-TYPE Unit part number. | 1.3.6.1.4.1.3711.24.1.1.99.8 | DisplayString (SIZE(0..31)) | read-only | current |
| invHwRevision OBJECT-TYPE Hardware revision number. | 1.3.6.1.4.1.3711.24.1.1.99.9 | DisplayString (SIZE(0..31)) | read-only | current |
| invFwRevision OBJECT-TYPE Firmware revision number. | 1.3.6.1.4.1.3711.24.1.1.99.10 | DisplayString (SIZE(0..15)) | read-only | current |
| invSerialNum OBJECT-TYPE Serial number. | 1.3.6.1.4.1.3711.24.1.1.99.11 | DisplayString (SIZE(0..15)) | read-only | current |
| invDefaultIPAddrType OBJECT-TYPE The type of the IP addresses. | 1.3.6.1.4.1.3711.24.1.1.99.12 | InetAddressType | read-only | current |
| invDefaultIPAddr OBJECT-TYPE Default unit IP address. | 1.3.6.1.4.1.3711.24.1.1.99.13 | InetAddress | read-only | current |
| invDefaultSubNetMask OBJECT-TYPE Default unit sub-network mask. | 1.3.6.1.4.1.3711.24.1.1.99.14 | InetAddress | read-only | current |
| invDefaultGWAddr OBJECT-TYPE Default unit default gateway address. | 1.3.6.1.4.1.3711.24.1.1.99.15 | InetAddress | read-only | current |
| invMacAddr OBJECT-TYPE Unit medium access control (MAC) address. | 1.3.6.1.4.1.3711.24.1.1.99.16 | MacAddress | read-only | current |
| invOk OBJECT-TYPE Confirms that the inventory record isn't corrupted. | 1.3.6.1.4.1.3711.24.1.1.99.20 | TruthValue | read-only | current |
| invInputCount OBJECT-TYPE The maximum number of inputs that can be connected to the unit | 1.3.6.1.4.1.3711.24.1.1.99.50 | INTEGER (0..24) | read-only | current |
| invOutputCount OBJECT-TYPE The maximum number of outputs that can be connected to the unit | 1.3.6.1.4.1.3711.24.1.1.99.51 | INTEGER (0..24) | read-only | current |
| invKeypadCount OBJECT-TYPE The maximum number of keypads that can be connected to the unit | 1.3.6.1.4.1.3711.24.1.1.99.52 | INTEGER (0..2) | read-only | current |
| invAcuCount OBJECT-TYPE The maximum number of ACU's that can be connected to the unit | 1.3.6.1.4.1.3711.24.1.1.99.53 | INTEGER (0..6) | read-only | current |
| invAccessUserCount OBJECT-TYPE The maximum number of user entries on the unit | 1.3.6.1.4.1.3711.24.1.1.99.54 | INTEGER (0..20) | read-only | current |
| invPduCount OBJECT-TYPE The maximum number of PDU's that can be connected to the unit | 1.3.6.1.4.1.3711.24.1.1.99.55 | INTEGER (0..6) | read-only | current |
| trapInfo OBJECT-IDENTITY | 1.3.6.1.4.1.3711.24.1.1.100 | |||
| trapCode OBJECT-TYPE A decimal number to be carried on notifications of types 1 to 4 identifying the event which caused it. The format of this number is BBEEffCCT where BB is the number of the relevant MIB branch. EE indicates what type of event caused the notification. This value is dependent upon branch number and implementation. CC is the channel number which was the source of the notification. T discriminates the type of data, e.g. temperature. This value is dependent upon branch number and implementation. ff future use. Fields are packed with leading zeros and are set to zero if not relevant to a particular notification. | 1.3.6.1.4.1.3711.24.1.1.100.1 | Unsigned32 | read-only | current |
| trapDescription OBJECT-TYPE A string to be carried on notifications of types 1 to 4 identifying the event which caused it. The format of this string is as follows. Field 1 - type of notification, e.g. warning, critical, etc. Field 2 - data source, e.g. inputs. Generally this relates to a particular MIB branch. Field 3 - channel number, e.g. input 1. Field 4 - event, i.e. what caused the trap. Field 5 - value at which the event occured, e.g. 900, indicating 90% humidity. Field 6 - type of data, e.g. relative humidity Fields are omitted if not relevant to a particular notification. | 1.3.6.1.4.1.3711.24.1.1.100.2 | DisplayString (SIZE(0..63)) | read-only | current |
Notifications
| Name | OID | Status |
|---|---|---|
| alarmCritical NOTIFICATION-TYPE Critical alarm. | 1.3.6.1.4.1.3711.24.0.1 | current |
| alarmWarning NOTIFICATION-TYPE Warning alarm. | 1.3.6.1.4.1.3711.24.0.2 | current |
| alarmInformation NOTIFICATION-TYPE Information alarm. | 1.3.6.1.4.1.3711.24.0.3 | current |
| alarmCleared NOTIFICATION-TYPE Alarm cleared. | 1.3.6.1.4.1.3711.24.0.4 | current |