MIBs Depot

HAWK-I2-MIB

Registered at
1.3.6.1.4.1.3711
Last updated
2006-06-27 12:00
Organization
Sinetica Corporation
Revisions
2006-06-27 12:00, 2006-03-07 12:00
Namespace
sinetica
Source file
HAWK-I2-MIB
Digest
sha256:e7cc2c126100d13a45ee697208a48c9ed202b3211e69635d5095be0a1558706a

Description

The MIB module for the Sinetica Hawk-i2.

Contact

Development Department Sinetica Corporation Ltd. Willow House Llancayo Court Usk Monmouthshire NP15 1HY U.K. Tel: +44 (0)871 226 5679 Fax: +44 (0)845 456 3562 Web: www.sinetica.co.uk E-mail: info@sinetica.co.uk

Imports

FromSymbols
INET-ADDRESS-MIBInetAddress, InetAddressType
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, enterprises, iso
SNMPv2-TCDisplayString, MacAddress, RowStatus, TEXTUAL-CONVENTION, TruthValue

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

HAWK-I2-MIB
INET-ADDRESS-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Textual conventions

NameOIDSyntaxAccessStatus
ContactState
TEXTUAL-CONVENTION
Represents the state of a set of contacts.
current
DisplayString
type
EnableState
TEXTUAL-CONVENTION
Represents the state of an enabling flag.
current
InputContactState
TEXTUAL-CONVENTION
Represents the state of a set of input contacts.
current
InputDataType
TEXTUAL-CONVENTION
Represents the type of data read at an input.
current
OutputControlState
TEXTUAL-CONVENTION
Represents the control setiing for an output.
current
RelayState
TEXTUAL-CONVENTION
Represents the energised state of a relay.
current

Objects

NameOIDSyntaxAccessStatus
sinetica
OBJECT-IDENTITY
1.3.6.1.4.1.3711
traps
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.0
v1
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1
objects
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1
inputs
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.1
ipCommon
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.1.1
ipEnable
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.1.1.1
ipSelect
OBJECT-TYPE
Selects the channel to be enabled or disabled by ipInsert. A value of 0 selects no channel.
1.3.6.1.4.1.3711.24.1.1.1.1.1.1INTEGER (0..24)read-writecurrent
ipInsert
OBJECT-TYPE
Inserts or removes the channel selected by ipSelect - causes an entry for that channel to be created or deleted in the relevant tables. - Read behaviour is undefined.
1.3.6.1.4.1.3711.24.1.1.1.1.1.2InputDataTyperead-writecurrent
ipTHA
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.1.2
ipTempScaleFlag
OBJECT-TYPE
Temperature scale (Celsius/Fahrenheit) for temperature monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.1INTEGER {celsius(1), fahrenheit(2), kelvin(3)}read-writecurrent
ipTHATable
OBJECT-TYPE
A table giving data for all enabled inputs with analogue-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.2not-accessiblecurrent
ipTHAEntry
OBJECT-TYPE
A conceptual row containing information about one analogue-type input.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1not-accessiblecurrent
ipTHAChan
OBJECT-TYPE
The input number.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.1INTEGER (0..24)read-onlycurrent
ipTHARS
OBJECT-TYPE
The analogue-type input table row status.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.2RowStatusread-onlycurrent
ipTHAName
OBJECT-TYPE
The name of this input
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.3DisplayString (SIZE(0..15))read-writecurrent
ipTHALocn
OBJECT-TYPE
A system-defined name for the physical location of this input, e.g. MCU.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.4DisplayString (SIZE(0..4))read-onlycurrent
ipTHAAutoDetect
OBJECT-TYPE
Indicates that the type of data this input is monitoring is selected automatically.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.5TruthValueread-writecurrent
ipTHAType
OBJECT-TYPE
Indicates the type of data this input is monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.6InputDataTyperead-writecurrent
ipTHAValue
OBJECT-TYPE
The current reading in the relevant measurement units.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.7INTEGER (-200..1000)read-onlycurrent
ipTHAScaling
OBJECT-TYPE
Scaling factor for ipTHAValue when ipTHAType=analogue.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.8INTEGER (0..100)read-writecurrent
ipTHAOffset
OBJECT-TYPE
Calibration offset in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.9INTEGER (-100..100)read-writecurrent
ipTHAHysteresis
OBJECT-TYPE
Hysteresis on threshold levels in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.2.1.10INTEGER (-100..100)read-writecurrent
ipTHATrapsCfg
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.1.2.3
ipTHAThreshTable
OBJECT-TYPE
A table listing the trap threshold levels for all enabled inputs with analogue-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1not-accessiblecurrent
ipTHAThreshEntry
OBJECT-TYPE
A conceptual row containing threshold information for one analogue-type input.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1not-accessiblecurrent
ipTHAThreshChan
OBJECT-TYPE
The input number.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.1INTEGER (0..24)read-onlycurrent
ipTHAThreshRS
OBJECT-TYPE
The analogue-type input table row status.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.2RowStatusread-onlycurrent
ipTHAUCL
OBJECT-TYPE
The Upper Critical Limit for this input in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.3INTEGER (-200..1000)read-writecurrent
ipTHAUWL
OBJECT-TYPE
The Upper Warning Limit for this input in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.4INTEGER (-200..1000)read-writecurrent
ipTHALWL
OBJECT-TYPE
The Lower Warning Limit for this input in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.5INTEGER (-200..1000)read-writecurrent
ipTHALCL
OBJECT-TYPE
The Lower Critical Limit for this input in the same units as for ipTHAValue.
1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.6INTEGER (-200..1000)read-writecurrent
ipTHATrapEnTable
OBJECT-TYPE
The table that controls trap enabling for all enabled inputs with analogue-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2not-accessiblecurrent
ipTHATrapEnEntry
OBJECT-TYPE
A conceptual row containing trap enabling information for one analogue-type input.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1not-accessiblecurrent
ipTHATrapEnChan
OBJECT-TYPE
The input number.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.1INTEGER (0..24)read-onlycurrent
ipTHATrapEnRS
OBJECT-TYPE
The analogue-type input table row status.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.2RowStatusread-onlycurrent
ipTHAUCLTrapEn
OBJECT-TYPE
Enables and disables input UCL alarm traps.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.3TruthValueread-writecurrent
ipTHAUWLTrapEn
OBJECT-TYPE
Enables and disables input UWL alarm traps.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.4TruthValueread-writecurrent
ipTHALWLTrapEn
OBJECT-TYPE
Enables and disables input LWL alarm traps.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.5TruthValueread-writecurrent
ipTHALCLTrapEn
OBJECT-TYPE
Enables and disables input LCL alarm traps.
1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.6TruthValueread-writecurrent
ipTHATrapPerTable
OBJECT-TYPE
The table that controls trap repetition for all enabled inputs with analogue-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.2.3.3not-accessiblecurrent
ipTHATrapPerEntry
OBJECT-TYPE
A conceptual row containing trap repetition information for one analogue-type input.
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1not-accessiblecurrent
ipTHATrapPerChan
OBJECT-TYPE
The input number.
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.1INTEGER (0..24)read-onlycurrent
ipTHATrapPerRS
OBJECT-TYPE
The table row status.
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.2RowStatusread-onlycurrent
ipTHATrapUCLPer
OBJECT-TYPE
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.3INTEGER (30..32000)read-writecurrent
ipTHATrapUWLPer
OBJECT-TYPE
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.4INTEGER (30..32000)read-writecurrent
ipTHATrapLWLPer
OBJECT-TYPE
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.5INTEGER (30..32000)read-writecurrent
ipTHATrapLCLPer
OBJECT-TYPE
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.6INTEGER (30..32000)read-writecurrent
ipContact
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.1.3
ipContTable
OBJECT-TYPE
A table listing the parameters and data for all enabled inputs with contact-type monitoring.
1.3.6.1.4.1.3711.24.1.1.1.3.1not-accessiblecurrent
ipContEntry
OBJECT-TYPE
A conceptual row containing information about one contact input.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1not-accessiblecurrent
ipContChan
OBJECT-TYPE
The input number.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.1INTEGER (0..24)read-onlycurrent
ipContRS
OBJECT-TYPE
The contact input table row status.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.2RowStatusread-onlycurrent
ipContName
OBJECT-TYPE
The name of this input
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.3DisplayString (SIZE(0..15))read-writecurrent
ipContLocn
OBJECT-TYPE
A system-defined name for the physical location of this input, e.g. MCU.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.4DisplayString (SIZE(0..4))read-onlycurrent
ipContAutoDetect
OBJECT-TYPE
Indicates that the type of data this input is monitoring is selected automatically.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.5TruthValueread-writecurrent
ipContNormState
OBJECT-TYPE
The normal state for this contact.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.6ContactStateread-writecurrent
ipContCurrState
OBJECT-TYPE
The current state of this contact.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.7InputContactStateread-onlycurrent
ipContTrigMode
OBJECT-TYPE
The contact trigger mode, level, +ve edge, -ve edge.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.8INTEGER {positiveEdge(1), negativeEdge(2), level(3)}read-writecurrent
ipContReset
OBJECT-TYPE
Resets the contact after triggering in edge mode.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.9Unsigned32read-writecurrent
ipContTrapEn
OBJECT-TYPE
Configure contact input traps.
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.10INTEGER {critical(1), warning(2), information(3), disabled(255)}read-writecurrent
ipContTrapPeriod
OBJECT-TYPE
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.1.3.1.1.11INTEGER (30..32000)read-writecurrent
outputs
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.2
opEnable
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.2.1
opSelect
OBJECT-TYPE
Selects the channel to be enabled or disabled by opEnable. A value of 0 selects no channel.
1.3.6.1.4.1.3711.24.1.1.2.1.1INTEGER (0..24)read-writecurrent
opInsert
OBJECT-TYPE
Enables or disables the channel selected by opSelect - causes an entry for that channel to be created or deleted in the relevant tables. - Read behaviour is undefined.
1.3.6.1.4.1.3711.24.1.1.2.1.2EnableStateread-writecurrent
opTable
OBJECT-TYPE
A table listing the parameters and data for all outputs that are enabled and available (i.e. its extension unit is connected).
1.3.6.1.4.1.3711.24.1.1.2.2not-accessiblecurrent
opEntry
OBJECT-TYPE
A conceptual row containing information about one output.
1.3.6.1.4.1.3711.24.1.1.2.2.1not-accessiblecurrent
opChan
OBJECT-TYPE
The output number.
1.3.6.1.4.1.3711.24.1.1.2.2.1.1INTEGER (0..18)read-onlycurrent
opRS
OBJECT-TYPE
The contact input table row status.
1.3.6.1.4.1.3711.24.1.1.2.2.1.2RowStatusread-onlycurrent
opName
OBJECT-TYPE
A user-defined name for this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.3DisplayString (SIZE(0..15))read-writecurrent
opLocn
OBJECT-TYPE
A system-defined name for the physical location of this output, e.g. MCU.
1.3.6.1.4.1.3711.24.1.1.2.2.1.4DisplayString (SIZE(0..4))read-onlycurrent
opNormState
OBJECT-TYPE
Sets or reads the required normal state of this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.5RelayStateread-writecurrent
opCurrState
OBJECT-TYPE
Reads the current state of this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.6RelayStateread-onlycurrent
opOnDelTime
OBJECT-TYPE
Sets the 'on' delay time for this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.7Unsigned32read-writecurrent
opOffDelTime
OBJECT-TYPE
Sets the 'off' delay time for this output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.8Unsigned32read-writecurrent
opBooleanEqn
OBJECT-TYPE
Boolean equation string
1.3.6.1.4.1.3711.24.1.1.2.2.1.9DisplayStringread-writecurrent
opTrapEn
OBJECT-TYPE
Configure output traps.
1.3.6.1.4.1.3711.24.1.1.2.2.1.10INTEGER {critical(1), warning(2), information(3), disabled(255)}read-writecurrent
opTrapPeriod
OBJECT-TYPE
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
1.3.6.1.4.1.3711.24.1.1.2.2.1.11INTEGER (30..32000)read-writecurrent
opControlState
OBJECT-TYPE
Reads the current control state of an output.
1.3.6.1.4.1.3711.24.1.1.2.2.1.12OutputControlStateread-writecurrent
keypads
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.4
kpEnable
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.4.1
kpSelect
OBJECT-TYPE
Selects the keypad to be enabled or disabled by kpEnable. A value of 0 selects no keypad.
1.3.6.1.4.1.3711.24.1.1.4.1.1INTEGER (0..24)read-writecurrent
kpInsert
OBJECT-TYPE
Enables or disables the keypad selected by kpSelect - causes an entry for that keypad to be created or deleted in the relevant tables. - Read behaviour is undefined.
1.3.6.1.4.1.3711.24.1.1.4.1.2EnableStateread-writecurrent
kpCtlTable
OBJECT-TYPE
A table listing the parameters and data for the keypads.
1.3.6.1.4.1.3711.24.1.1.4.2not-accessiblecurrent
kpCtlEntry
OBJECT-TYPE
A conceptual row containing information about one keypad.
1.3.6.1.4.1.3711.24.1.1.4.2.1not-accessiblecurrent
kpNumber
OBJECT-TYPE
The keypad number.
1.3.6.1.4.1.3711.24.1.1.4.2.1.1INTEGER (1..2)read-onlycurrent
kpRS
OBJECT-TYPE
The keypad table row status.
1.3.6.1.4.1.3711.24.1.1.4.2.1.2RowStatusread-onlycurrent
kpManufacturer
OBJECT-TYPE
The name of the manufacturer of the keypad.
1.3.6.1.4.1.3711.24.1.1.4.2.1.3DisplayString (SIZE(0..15))read-writecurrent
kpName
OBJECT-TYPE
A name identifying the keypad.
1.3.6.1.4.1.3711.24.1.1.4.2.1.4DisplayString (SIZE(0..15))read-writecurrent
kpDoorLatchTimeOut
OBJECT-TYPE
Time-out value in seconds for which the door latch is held open.
1.3.6.1.4.1.3711.24.1.1.4.2.1.5Unsigned32read-writecurrent
kpRtnToStndbyTimeOut
OBJECT-TYPE
Time-out value in seconds for Return to Standby Mode
1.3.6.1.4.1.3711.24.1.1.4.2.1.6INTEGER (0..99)read-writecurrent
kpEntryCodeValid
OBJECT-TYPE
Set if previous keypad entry was valid.
1.3.6.1.4.1.3711.24.1.1.4.2.1.7TruthValueread-onlycurrent
kpDoorOpenTimeOut
OBJECT-TYPE
Time-out value in seconds for Door Open.
1.3.6.1.4.1.3711.24.1.1.4.2.1.8INTEGER (0..99)read-writecurrent
kpRemoteDoorOpen
OBJECT-TYPE
Set to open the door.
1.3.6.1.4.1.3711.24.1.1.4.2.1.9TruthValueread-writecurrent
kpInUseTrapEn
OBJECT-TYPE
'keypad in use' trap enable
1.3.6.1.4.1.3711.24.1.1.4.2.1.10INTEGER {critical(1), warning(2), information(3), disabled(255)}read-writecurrent
acus
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.5
acuEnable
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.5.1
acuSelect
OBJECT-TYPE
Selects the ACU to be enabled or disabled by acuEnable. A value of 0 selects no ACU.
1.3.6.1.4.1.3711.24.1.1.5.1.1INTEGER (0..24)read-writecurrent
acuInsert
OBJECT-TYPE
Enables or disables the ACU selected by acuSelect - causes an entry for that ACU to be created or deleted in the relevant tables. - Read behaviour is undefined.
1.3.6.1.4.1.3711.24.1.1.5.1.2EnableStateread-writecurrent
acuCtlTable
OBJECT-TYPE
A table listing the parameters and data for the ACUs.
1.3.6.1.4.1.3711.24.1.1.5.2not-accessiblecurrent
acuCtlEntry
OBJECT-TYPE
A conceptual row containing information about one ACU.
1.3.6.1.4.1.3711.24.1.1.5.2.1not-accessiblecurrent
acuNumber
OBJECT-TYPE
The ACU number.
1.3.6.1.4.1.3711.24.1.1.5.2.1.1INTEGER (1..6)read-onlycurrent
acuCtlRS
OBJECT-TYPE
The ACU table row status.
1.3.6.1.4.1.3711.24.1.1.5.2.1.2RowStatusread-onlycurrent
acuManufacturer
OBJECT-TYPE
The name of the manufacturer of the ACU.
1.3.6.1.4.1.3711.24.1.1.5.2.1.3DisplayString (SIZE(0..15))read-writecurrent
acuName
OBJECT-TYPE
A name identifying the ACU.
1.3.6.1.4.1.3711.24.1.1.5.2.1.4DisplayString (SIZE(0..15))read-writecurrent
acuDoorLatchTimeOut
OBJECT-TYPE
Time-out value in seconds for which the door latch is held open.
1.3.6.1.4.1.3711.24.1.1.5.2.1.5Unsigned32read-writecurrent
acuRtnToStndbyTimeOut
OBJECT-TYPE
Time-out value in seconds for Return to Standby Mode
1.3.6.1.4.1.3711.24.1.1.5.2.1.6INTEGER (0..99)read-writecurrent
acuEntryCodeValid
OBJECT-TYPE
Set if previous ACU entry was valid.
1.3.6.1.4.1.3711.24.1.1.5.2.1.7TruthValueread-onlycurrent
acuDoorOpenTimeOut
OBJECT-TYPE
Time-out value in seconds for Door Open.
1.3.6.1.4.1.3711.24.1.1.5.2.1.8INTEGER (0..99)read-writecurrent
acuRemoteDoorOpen
OBJECT-TYPE
Set to open the door.
1.3.6.1.4.1.3711.24.1.1.5.2.1.9TruthValueread-writecurrent
acuInUseTrapEn
OBJECT-TYPE
'ACU in use' trap enable
1.3.6.1.4.1.3711.24.1.1.5.2.1.10INTEGER {critical(1), warning(2), information(3), disabled(255)}read-writecurrent
access
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.6
accUserCtl
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.6.1
accUserInstance
OBJECT-TYPE
A value of 0 causes an access user to be created in the relevant tables. A non-zero value causes the nominated access user table entries to be deleted.
1.3.6.1.4.1.3711.24.1.1.6.1.1Unsigned32read-writecurrent
accUserTable
OBJECT-TYPE
A table controlling the access users.
1.3.6.1.4.1.3711.24.1.1.6.1.2not-accessiblecurrent
accUserEntry
OBJECT-TYPE
A conceptual row containing information about one ACU user.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1not-accessiblecurrent
accUserNumber
OBJECT-TYPE
The the access user-table entry number.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.1INTEGER (0..20)read-onlycurrent
accUserRS
OBJECT-TYPE
The access user table row status.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.2RowStatusread-onlycurrent
accUserName
OBJECT-TYPE
A name identifying the access user.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.3DisplayString (SIZE(0..15))read-writecurrent
accUserCode
OBJECT-TYPE
The user's access code.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.4OCTET STRING (SIZE(0..15))read-writecurrent
accUserPrivileges
OBJECT-TYPE
The ACUs and keypads that the user is allowed to gain access through - comma-separated numerical strings.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.5DisplayString (SIZE(0..11))read-writecurrent
accUserExpires
OBJECT-TYPE
A text string which specifies when the access code in the row expires. The format is defined by the application.
1.3.6.1.4.1.3711.24.1.1.6.1.2.1.6DisplayStringread-writecurrent
accUserSetup
OBJECT-TYPE
A free form octet string for programming accUserTable. The format is defined by the application.
1.3.6.1.4.1.3711.24.1.1.6.1.3OCTET STRINGread-writecurrent
pdus
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.7
pduCommon
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.7.1
pdusEnable
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.7.1.1
pduSelect
OBJECT-TYPE
Selects the PDU to be enabled or disabled by pduEnable. A value of 0 selects no PDU.
1.3.6.1.4.1.3711.24.1.1.7.1.1.1INTEGER (0..6)read-writecurrent
pduInsert
OBJECT-TYPE
Enables or disables the PDU selected by pduSelect - causes an entry for that PDU to be created or deleted in the relevant tables. - Read behaviour is undefined.
1.3.6.1.4.1.3711.24.1.1.7.1.1.2EnableStateread-writecurrent
pduTable
OBJECT-TYPE
A table containing information about each enabled PDU.
1.3.6.1.4.1.3711.24.1.1.7.1.2not-accessiblecurrent
pduEntry
OBJECT-TYPE
A conceptual row containing information about one PDU.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1not-accessiblecurrent
pduNumber
OBJECT-TYPE
The PDU number.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.1INTEGER (1..8)read-onlycurrent
pduRS
OBJECT-TYPE
The PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.2RowStatusread-onlycurrent
pduName
OBJECT-TYPE
A string identifying the PDU.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.3DisplayString (SIZE(0..15))read-writecurrent
pduOutEn
OBJECT-TYPE
Enables/disables PDU power outlet control - causes an entry for outlets to be created in each relevant PDU table.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.4TruthValueread-writecurrent
pduMonEn
OBJECT-TYPE
Enables/disables PDU power monitoring - causes an entry for monitoring to be created in each relevant PDU table.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.5TruthValueread-writecurrent
pduCommsFail
OBJECT-TYPE
Indicates comms. status for the PDU.
1.3.6.1.4.1.3711.24.1.1.7.1.2.1.6INTEGER {commsGood(1), commsFailed(2), commsBadData(3)}read-onlycurrent
pduOutlets
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.7.2
pduOutAll
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.7.2.1
pduOutCycleAll
OBJECT-TYPE
Sets the required state of all power outlets on all connected PDUs.
1.3.6.1.4.1.3711.24.1.1.7.2.1.1INTEGER {up(1), down(2)}read-writecurrent
pduOutCycleAllPwd
OBJECT-TYPE
Controls access to setting the required state of all power outlets on all connected PDUs.
1.3.6.1.4.1.3711.24.1.1.7.2.1.2DisplayString (SIZE(0..7))read-writecurrent
pduOutCycleAllAbort
OBJECT-TYPE
Abort command for pduOutCycleAll.
1.3.6.1.4.1.3711.24.1.1.7.2.1.3Unsigned32read-writecurrent
pduOutGlobalCycleDelay
OBJECT-TYPE
Sets the delay period for pduOutCycleAll and pduOutCycle commands before they start to execute.
1.3.6.1.4.1.3711.24.1.1.7.2.1.4Unsigned32read-writecurrent
pduOutGlobalRebootTime
OBJECT-TYPE
Sets the off to on delay period for a pdu outlet reboot.
1.3.6.1.4.1.3711.24.1.1.7.2.1.5Unsigned32read-writecurrent
pduOutGlobalCycleAbortTime
OBJECT-TYPE
Time delay to abort power outlet setting task.
1.3.6.1.4.1.3711.24.1.1.7.2.1.6Unsigned32read-writecurrent
pduOutCmnTable
OBJECT-TYPE
A table containing information about the power outlets of all PDUs enabled for outlet control.
1.3.6.1.4.1.3711.24.1.1.7.2.2not-accessiblecurrent
pduOutCmnEntry
OBJECT-TYPE
A conceptual row containing information about the power outlets of one PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1not-accessiblecurrent
pduOutCmnPduNumber
OBJECT-TYPE
The PDU number.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.1INTEGER (1..8)read-onlycurrent
pduOutCmnRS
OBJECT-TYPE
The PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.2RowStatusread-onlycurrent
pduNumOfOutlets
OBJECT-TYPE
The number of switchable outlets on the PDU - determines the number of entries to be created in the outlet table for the relevant PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.3INTEGER (1..32)read-writecurrent
pduOutCycle
OBJECT-TYPE
Sets the required state of all power outlets on the PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.4INTEGER {up(1), down(2)}read-writecurrent
pduOutCyclePwd
OBJECT-TYPE
Password controling access to setting the required state of all power outlets on the PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.5DisplayString (SIZE(0..7))read-writecurrent
pduOutCycleAbortTask
OBJECT-TYPE
Abort power outlet setting task.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.6Unsigned32read-writecurrent
pduOutCycleAbortTime
OBJECT-TYPE
Time delay to abort power outlet setting task.
1.3.6.1.4.1.3711.24.1.1.7.2.2.1.7Unsigned32read-writecurrent
pduOutTable
OBJECT-TYPE
A table listing the states and descriptions for each outlet on the PDU.
1.3.6.1.4.1.3711.24.1.1.7.2.3not-accessiblecurrent
pduOutEntry
OBJECT-TYPE
A row containing information about one PDU outlet.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1not-accessiblecurrent
pduOutPduNumber
OBJECT-TYPE
The PDU number on which the outlet resides.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.1INTEGER (1..8)read-onlycurrent
pduOutNumber
OBJECT-TYPE
The outlet number.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.2INTEGER (1..32)read-onlycurrent
pduOutRS
OBJECT-TYPE
The PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.3RowStatusread-onlycurrent
pduOutName
OBJECT-TYPE
A name identifying the outlet.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.4DisplayString (SIZE(0..31))read-writecurrent
pduOutOn
OBJECT-TYPE
The current state for this outlet.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.5INTEGER {on(1), off(2), reboot(3)}read-writecurrent
pduOutPwd
OBJECT-TYPE
The password for this outlet.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.6DisplayString (SIZE(0..7))read-writecurrent
pduOutCycleDelay
OBJECT-TYPE
The on/off delay for this outlet in seconds.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.7Unsigned32read-onlycurrent
pduOutRebootPeriod
OBJECT-TYPE
The pduOutOn reboot off period for this outlet in seconds.
1.3.6.1.4.1.3711.24.1.1.7.2.3.1.8Unsigned32read-onlycurrent
pduMonitor
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.7.3
pduMonTable
OBJECT-TYPE
A table containing monitor information for all PDUs enabled for monitoring.
1.3.6.1.4.1.3711.24.1.1.7.3.1not-accessiblecurrent
pduMonEntry
OBJECT-TYPE
A conceptual row containing monitor information for one PDU.
1.3.6.1.4.1.3711.24.1.1.7.3.1.1not-accessiblecurrent
pduMonPduNumber
OBJECT-TYPE
The PDU number.
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.1INTEGER (1..8)read-onlycurrent
pduMonRS
OBJECT-TYPE
The PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.2RowStatusread-onlycurrent
pduRMSVoltsValue
OBJECT-TYPE
RMS Volts value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.3INTEGER (0..500)read-onlycurrent
pduRMSAmpsValue
OBJECT-TYPE
RMS current value in 0.1 Amps
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.4INTEGER (0..500)read-onlycurrent
pduTotalEnergyValue
OBJECT-TYPE
Total energy value in 0.1 kWh
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.5INTEGER (0..9999999)read-onlycurrent
pduMeanKVAValue
OBJECT-TYPE
Kilo Volt-Amperes value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.6INTEGER (0..100000)read-onlycurrent
pduMeanKWattsValue
OBJECT-TYPE
Kilo Watts value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.7INTEGER (0..100000)read-onlycurrent
pduPwrFactorValue
OBJECT-TYPE
Power factor value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.1.1.8INTEGER (0..100)read-onlycurrent
pduTrapThreshTable
OBJECT-TYPE
A table containing information about the trap threshold values for all PDUs enabled for monitoring.
1.3.6.1.4.1.3711.24.1.1.7.3.2not-accessiblecurrent
pduTrapThreshEntry
OBJECT-TYPE
A conceptual row containing information about the trap threshold values for one PDU.
1.3.6.1.4.1.3711.24.1.1.7.3.2.1not-accessiblecurrent
pduTrapThreshPduNumber
OBJECT-TYPE
The PDU number.
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.1INTEGER (1..8)read-onlycurrent
pduTrapThreshRS
OBJECT-TYPE
The PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.2RowStatusread-onlycurrent
pduRMSVoltsUCL
OBJECT-TYPE
rms UCL value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.3INTEGER (0..500)read-writecurrent
pduRMSVoltsUWL
OBJECT-TYPE
rms UWL value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.4INTEGER (0..500)read-writecurrent
pduRMSVoltsLWL
OBJECT-TYPE
rms LWL value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.5INTEGER (0..500)read-writecurrent
pduRMSVoltsLCL
OBJECT-TYPE
rms LCL value in volts
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.6INTEGER (0..500)read-writecurrent
pduRMSAmpsUCL
OBJECT-TYPE
rms UCL value in 0.1 amps
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.7INTEGER (0..500)read-writecurrent
pduRMSAmpsUWL
OBJECT-TYPE
rms UWL value in 0.1 amps
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.8INTEGER (0..500)read-writecurrent
pduRMSAmpsLWL
OBJECT-TYPE
rms LWL value in 0.1 amps
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.9INTEGER (0..500)read-writecurrent
pduRMSAmpsLCL
OBJECT-TYPE
rms LCL value in 0.1 amps
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.10INTEGER (0..500)read-writecurrent
pduEnergyUCL
OBJECT-TYPE
Total energy UCL value in 0.1 kWh
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.11INTEGER (0..9999999)read-writecurrent
pduEnergyUWL
OBJECT-TYPE
Total energy UWL value in 0.1 kWh
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.12INTEGER (0..9999999)read-writecurrent
pduMeanKVAUCL
OBJECT-TYPE
Mean kVA UCL value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.13INTEGER (0..100000)read-writecurrent
pduMeanKVAUWL
OBJECT-TYPE
Mean kVA UWL value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.14INTEGER (0..100000)read-writecurrent
pduMeanKVALWL
OBJECT-TYPE
Mean kVA LWL value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.15INTEGER (0..100000)read-writecurrent
pduMeanKVALCL
OBJECT-TYPE
Mean kVA LCL value in 0.1 kVA
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.16INTEGER (0..100000)read-writecurrent
pduMeanKWattsUCL
OBJECT-TYPE
Mean power UCL value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.17INTEGER (0..100000)read-writecurrent
pduMeanKWattsUWL
OBJECT-TYPE
Mean power UWL value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.18INTEGER (0..100000)read-writecurrent
pduMeanKWattsLWL
OBJECT-TYPE
Mean power LWL value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.19INTEGER (0..100000)read-writecurrent
pduMeanKWattsLCL
OBJECT-TYPE
Mean power LCL value in 0.1 kW
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.20INTEGER (0..100000)read-writecurrent
pduPwrFactorUCL
OBJECT-TYPE
Power factor UCL value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.21INTEGER (0..100)read-writecurrent
pduPwrFactorUWL
OBJECT-TYPE
Power factor UWL value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.22INTEGER (0..100)read-writecurrent
pduPwrFactorLWL
OBJECT-TYPE
Power factor LWL value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.23INTEGER (0..100)read-writecurrent
pduPwrFactorLCL
OBJECT-TYPE
Power factor LCL value in 0.01
1.3.6.1.4.1.3711.24.1.1.7.3.2.1.24INTEGER (0..100)read-writecurrent
pduTrapEnTable
OBJECT-TYPE
The table which controls threshold value trap enabling for all PDUs enabled for monitoring.
1.3.6.1.4.1.3711.24.1.1.7.3.3not-accessiblecurrent
pduTrapEnEntry
OBJECT-TYPE
A conceptual row containing information about one PDU.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1not-accessiblecurrent
pduTrapEnPduNumber
OBJECT-TYPE
The PDU number.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.1INTEGER (1..8)read-onlycurrent
pduTrapEnRS
OBJECT-TYPE
The PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.2RowStatusread-onlycurrent
pduRMSVoltsUCLTrapEn
OBJECT-TYPE
Enables Volts UCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.3TruthValueread-writecurrent
pduRMSVoltsUWLTrapEn
OBJECT-TYPE
Enables UWL Volts trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.4TruthValueread-writecurrent
pduRMSVoltsLWLTrapEn
OBJECT-TYPE
Enables LWL Volts trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.5TruthValueread-writecurrent
pduRMSVoltsLCLTrapEn
OBJECT-TYPE
Enables LCL Volts trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.6TruthValueread-writecurrent
pduRMSAmpsUCLTrapEn
OBJECT-TYPE
Enables UCL current trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.7TruthValueread-writecurrent
pduRMSAmpsUWLTrapEn
OBJECT-TYPE
Enables UWL current trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.8TruthValueread-writecurrent
pduRMSAmpsLWLTrapEn
OBJECT-TYPE
Enables LWL current trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.9TruthValueread-writecurrent
pduRMSAmpsLCLTrapEn
OBJECT-TYPE
Enables LCL current trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.10TruthValueread-writecurrent
pduEnergyUCLTrapEn
OBJECT-TYPE
Enables UCL total energy trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.11TruthValueread-writecurrent
pduEnergyUWLTrapEn
OBJECT-TYPE
Enables UWL total energy trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.12TruthValueread-writecurrent
pduMeanKVAUCLTrapEn
OBJECT-TYPE
Enables mean kVA UCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.13TruthValueread-writecurrent
pduMeanKVAUWLTrapEn
OBJECT-TYPE
Enables mean kVA UWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.14TruthValueread-writecurrent
pduMeanKVALWLTrapEn
OBJECT-TYPE
Enables mean kVA LWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.15TruthValueread-writecurrent
pduMeanKVALCLTrapEn
OBJECT-TYPE
Enables mean kVA LCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.16TruthValueread-writecurrent
pduMeanKWattsUCLTrapEn
OBJECT-TYPE
Enables mean power UCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.17TruthValueread-writecurrent
pduMeanKWattsUWLTrapEn
OBJECT-TYPE
Enables mean power UWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.18TruthValueread-writecurrent
pduMeanKWattsLWLTrapEn
OBJECT-TYPE
Enables mean power LWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.19TruthValueread-writecurrent
pduMeanKWattsLCLTrapEn
OBJECT-TYPE
Enables mean power LCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.20TruthValueread-writecurrent
pduPwrFactorUCLTrapEn
OBJECT-TYPE
Enables power factor UCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.21TruthValueread-writecurrent
pduPwrFactorUWLTrapEn
OBJECT-TYPE
Enables power factor UWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.22TruthValueread-writecurrent
pduPwrFactorLWLTrapEn
OBJECT-TYPE
Enables power factor LWL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.23TruthValueread-writecurrent
pduPwrFactorLCLTrapEn
OBJECT-TYPE
Enables power factor LCL trap.
1.3.6.1.4.1.3711.24.1.1.7.3.3.1.24TruthValueread-writecurrent
pduTrapPerTable
OBJECT-TYPE
The table which controls threshold value trap repetition for all PDUs enabled for monitoring.
1.3.6.1.4.1.3711.24.1.1.7.3.4not-accessiblecurrent
pduTrapPerEntry
OBJECT-TYPE
A conceptual row containing information about one PDU.
1.3.6.1.4.1.3711.24.1.1.7.3.4.1not-accessiblecurrent
pduTrapPduNumber
OBJECT-TYPE
The PDU number.
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.1INTEGER (1..8)read-onlycurrent
pduTrapPerRS
OBJECT-TYPE
The PDU table row status.
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.2RowStatusread-onlycurrent
pduRMSVoltsUCLTrapPer
OBJECT-TYPE
Sets UCL Volts trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.3INTEGER (30..32000)read-writecurrent
pduRMSVoltsUWLTrapPer
OBJECT-TYPE
Sets UWL Volts trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.4INTEGER (30..32000)read-writecurrent
pduRMSVoltsLWLTrapPer
OBJECT-TYPE
Sets LWL Volts trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.5INTEGER (30..32000)read-writecurrent
pduRMSVoltsLCLTrapPer
OBJECT-TYPE
Sets LCL Volts trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.6INTEGER (30..32000)read-writecurrent
pduRMSAmpsUCLTrapPer
OBJECT-TYPE
Sets UCL current trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.7INTEGER (30..32000)read-writecurrent
pduRMSAmpsUWLTrapPer
OBJECT-TYPE
Sets UWL current trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.8INTEGER (30..32000)read-writecurrent
pduRMSAmpsLWLTrapPer
OBJECT-TYPE
Sets LWL current trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.9INTEGER (30..32000)read-writecurrent
pduRMSAmpsLCLTrapPer
OBJECT-TYPE
Sets LCL current trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.10INTEGER (30..32000)read-writecurrent
pduEnergyUCLTrapPer
OBJECT-TYPE
Sets UCL total energy trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.11INTEGER (30..32000)read-writecurrent
pduEnergyUWLTrapPer
OBJECT-TYPE
Sets UWL total energy trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.12INTEGER (30..32000)read-writecurrent
pduMeanKVAUCLTrapPer
OBJECT-TYPE
Sets mean kVA UCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.13INTEGER (30..32000)read-writecurrent
pduMeanKVAUWLTrapPer
OBJECT-TYPE
Sets mean kVA UWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.14INTEGER (30..32000)read-writecurrent
pduMeanKVALWLTrapPer
OBJECT-TYPE
Sets mean kVA LWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.15INTEGER (30..32000)read-writecurrent
pduMeanKVALCLTrapPer
OBJECT-TYPE
Sets mean kVA LCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.16INTEGER (30..32000)read-writecurrent
pduMeanKWattsUCLTrapPer
OBJECT-TYPE
Sets mean power UCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.17INTEGER (30..32000)read-writecurrent
pduMeanKWattsUWLTrapPer
OBJECT-TYPE
Sets mean power UWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.18INTEGER (30..32000)read-writecurrent
pduMeanKWattsLWLTrapPer
OBJECT-TYPE
Sets mean power LWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.19INTEGER (30..32000)read-writecurrent
pduMeanKWattsLCLTrapPer
OBJECT-TYPE
Sets mean power LCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.20INTEGER (30..32000)read-writecurrent
pduPwrFactorUCLTrapPer
OBJECT-TYPE
Sets power factor UCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.21INTEGER (30..32000)read-writecurrent
pduPwrFactorUWLTrapPer
OBJECT-TYPE
Sets power factor UWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.22INTEGER (30..32000)read-writecurrent
pduPwrFactorLWLTrapPer
OBJECT-TYPE
Sets power factor LWL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.23INTEGER (30..32000)read-writecurrent
pduPwrFactorLCLTrapPer
OBJECT-TYPE
Sets power factor LCL trap repeat rate in seconds
1.3.6.1.4.1.3711.24.1.1.7.3.4.1.24INTEGER (30..32000)read-writecurrent
inventory
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.99
invProdSignature
OBJECT-TYPE
Product data signature.
1.3.6.1.4.1.3711.24.1.1.99.1DisplayString (SIZE(0..7))read-onlycurrent
invProdFormatVer
OBJECT-TYPE
Product data format version.
1.3.6.1.4.1.3711.24.1.1.99.2DisplayString (SIZE(0..7))read-onlycurrent
invManufCode
OBJECT-TYPE
Manufacturer code.
1.3.6.1.4.1.3711.24.1.1.99.3DisplayString (SIZE(0..15))read-onlycurrent
invOrderNum
OBJECT-TYPE
Order number.
1.3.6.1.4.1.3711.24.1.1.99.4DisplayString (SIZE(0..7))read-onlycurrent
invBatchNum
OBJECT-TYPE
Batch number.
1.3.6.1.4.1.3711.24.1.1.99.5DisplayString (SIZE(0..7))read-onlycurrent
invProdTestTime
OBJECT-TYPE
Data and time of production test.
1.3.6.1.4.1.3711.24.1.1.99.6DisplayString (SIZE(0..15))read-onlycurrent
invUnitName
OBJECT-TYPE
Unit name.
1.3.6.1.4.1.3711.24.1.1.99.7DisplayString (SIZE(0..15))read-onlycurrent
invUnitPartNum
OBJECT-TYPE
Unit part number.
1.3.6.1.4.1.3711.24.1.1.99.8DisplayString (SIZE(0..31))read-onlycurrent
invHwRevision
OBJECT-TYPE
Hardware revision number.
1.3.6.1.4.1.3711.24.1.1.99.9DisplayString (SIZE(0..31))read-onlycurrent
invFwRevision
OBJECT-TYPE
Firmware revision number.
1.3.6.1.4.1.3711.24.1.1.99.10DisplayString (SIZE(0..15))read-onlycurrent
invSerialNum
OBJECT-TYPE
Serial number.
1.3.6.1.4.1.3711.24.1.1.99.11DisplayString (SIZE(0..15))read-onlycurrent
invDefaultIPAddrType
OBJECT-TYPE
The type of the IP addresses.
1.3.6.1.4.1.3711.24.1.1.99.12InetAddressTyperead-onlycurrent
invDefaultIPAddr
OBJECT-TYPE
Default unit IP address.
1.3.6.1.4.1.3711.24.1.1.99.13InetAddressread-onlycurrent
invDefaultSubNetMask
OBJECT-TYPE
Default unit sub-network mask.
1.3.6.1.4.1.3711.24.1.1.99.14InetAddressread-onlycurrent
invDefaultGWAddr
OBJECT-TYPE
Default unit default gateway address.
1.3.6.1.4.1.3711.24.1.1.99.15InetAddressread-onlycurrent
invMacAddr
OBJECT-TYPE
Unit medium access control (MAC) address.
1.3.6.1.4.1.3711.24.1.1.99.16MacAddressread-onlycurrent
invOk
OBJECT-TYPE
Confirms that the inventory record isn't corrupted.
1.3.6.1.4.1.3711.24.1.1.99.20TruthValueread-onlycurrent
invInputCount
OBJECT-TYPE
The maximum number of inputs that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.99.50INTEGER (0..24)read-onlycurrent
invOutputCount
OBJECT-TYPE
The maximum number of outputs that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.99.51INTEGER (0..24)read-onlycurrent
invKeypadCount
OBJECT-TYPE
The maximum number of keypads that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.99.52INTEGER (0..2)read-onlycurrent
invAcuCount
OBJECT-TYPE
The maximum number of ACU's that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.99.53INTEGER (0..6)read-onlycurrent
invAccessUserCount
OBJECT-TYPE
The maximum number of user entries on the unit
1.3.6.1.4.1.3711.24.1.1.99.54INTEGER (0..20)read-onlycurrent
invPduCount
OBJECT-TYPE
The maximum number of PDU's that can be connected to the unit
1.3.6.1.4.1.3711.24.1.1.99.55INTEGER (0..6)read-onlycurrent
trapInfo
OBJECT-IDENTITY
1.3.6.1.4.1.3711.24.1.1.100
trapCode
OBJECT-TYPE
A decimal number to be carried on notifications of types 1 to 4 identifying the event which caused it. The format of this number is BBEEffCCT where BB is the number of the relevant MIB branch. EE indicates what type of event caused the notification. This value is dependent upon branch number and implementation. CC is the channel number which was the source of the notification. T discriminates the type of data, e.g. temperature. This value is dependent upon branch number and implementation. ff future use. Fields are packed with leading zeros and are set to zero if not relevant to a particular notification.
1.3.6.1.4.1.3711.24.1.1.100.1Unsigned32read-onlycurrent
trapDescription
OBJECT-TYPE
A string to be carried on notifications of types 1 to 4 identifying the event which caused it. The format of this string is as follows. Field 1 - type of notification, e.g. warning, critical, etc. Field 2 - data source, e.g. inputs. Generally this relates to a particular MIB branch. Field 3 - channel number, e.g. input 1. Field 4 - event, i.e. what caused the trap. Field 5 - value at which the event occured, e.g. 900, indicating 90% humidity. Field 6 - type of data, e.g. relative humidity Fields are omitted if not relevant to a particular notification.
1.3.6.1.4.1.3711.24.1.1.100.2DisplayString (SIZE(0..63))read-onlycurrent

Notifications

NameOIDStatus
alarmCritical
NOTIFICATION-TYPE
Critical alarm.
1.3.6.1.4.1.3711.24.0.1current
alarmWarning
NOTIFICATION-TYPE
Warning alarm.
1.3.6.1.4.1.3711.24.0.2current
alarmInformation
NOTIFICATION-TYPE
Information alarm.
1.3.6.1.4.1.3711.24.0.3current
alarmCleared
NOTIFICATION-TYPE
Alarm cleared.
1.3.6.1.4.1.3711.24.0.4current