GUDEADS-EPC2X6-MIB
- Registered at
- 1.3.6.1.4.1.28507.01.3.6.1.4.1.28507.6
- Last updated
- 2007-03-05 13:56
- Organization
- Gude Analog- und Digitalsysteme GmbH
- Revisions
- 2007-03-05 13:56
- Namespace
- gude
- Source file
GUDEADS-EPC2X6-MIB- Digest
sha256:8384ec62c0f204e89010f4cda3998771d0a6dbf29221426f63c6abe3e24cdb85
Contact
http://www.gudeads.com/
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-SMI | Counter32, Integer32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
GUDEADS-EPC2X6-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| events OBJECT-IDENTITY | 1.3.6.1.4.1.28507.0 | |||
| gadsEPC2x6 OBJECT-IDENTITY | 1.3.6.1.4.1.28507.6 | |||
| epc2x6Objects OBJECT-IDENTITY | 1.3.6.1.4.1.28507.6.1 | |||
| epc2x6SNMPaccess OBJECT-IDENTITY | 1.3.6.1.4.1.28507.6.1.1 | |||
| epc2x6TrapCtrl OBJECT-TYPE 0 = off 1 = Ver. 1 2 = Ver. 2c | 1.3.6.1.4.1.28507.6.1.1.1 | Integer32 (0..2) | read-write | current |
| epc2x6TrapIPTable OBJECT-TYPE list of all Trap receiver | 1.3.6.1.4.1.28507.6.1.1.2 | not-accessible | current | |
| epc2x6TrapIPEntry OBJECT-TYPE an entry containing management informations regarding the list of trap receivers | 1.3.6.1.4.1.28507.6.1.1.2.1 | not-accessible | current | |
| epc2x6TrapIPIndex OBJECT-TYPE A unique value, greater than zero, for each receiver slot. | 1.3.6.1.4.1.28507.6.1.1.2.1.1 | Integer32 (1..8) | not-accessible | current |
| epc2x6TrapIPAddr OBJECT-TYPE IP Address specifying one Trap receiver slot. A value of '00000000'H disables this slot. | 1.3.6.1.4.1.28507.6.1.1.2.1.2 | IpAddress | read-write | current |
| epc2x6TrapIPPort OBJECT-TYPE IP Port specifying one Trap receiver slot. A value of 0 disables this slot. | 1.3.6.1.4.1.28507.6.1.1.2.1.3 | Integer32 (0..1024) | read-write | current |
| epc2x6powerports OBJECT-IDENTITY | 1.3.6.1.4.1.28507.6.1.2 | |||
| epc2x6portNumber OBJECT-TYPE The number of PowerPorts | 1.3.6.1.4.1.28507.6.1.2.1 | Integer32 (1..12) | read-only | current |
| epc2x6portTable OBJECT-TYPE list of all EPC Powerports | 1.3.6.1.4.1.28507.6.1.2.2 | not-accessible | current | |
| epc2x6portEntry OBJECT-TYPE An entry containing management information applicable to a particular powerport. | 1.3.6.1.4.1.28507.6.1.2.2.1 | not-accessible | current | |
| epc2x6PortIndex OBJECT-TYPE A unique value, greater than zero, for each PowerPort. | 1.3.6.1.4.1.28507.6.1.2.2.1.1 | Integer32 (1..12) | not-accessible | current |
| epc2x6PortName OBJECT-TYPE A textual string containing name of a PowerPort. | 1.3.6.1.4.1.28507.6.1.2.2.1.2 | OCTET STRING (SIZE(0..15)) | read-only | current |
| epc2x6PortState OBJECT-TYPE current state a PowerPort | 1.3.6.1.4.1.28507.6.1.2.2.1.3 | INTEGER {off(0), on(1)} | read-write | current |
| epc2x6PortSwitchCount OBJECT-TYPE The total number of switch actions ocurred on a PowerPort. Does not count switch commands which will not switch the ralay state, so just real relay switches are displayed here. | 1.3.6.1.4.1.28507.6.1.2.2.1.4 | Counter32 | read-only | current |
| epc2x6PortStartupMode OBJECT-TYPE set Mode of startup sequence (off, on , remember last state) | 1.3.6.1.4.1.28507.6.1.2.2.1.5 | INTEGER {off(0), on(1), laststate(2)} | read-write | current |
| epc2x6PortStartupDelay OBJECT-TYPE Delay in sec for startup action | 1.3.6.1.4.1.28507.6.1.2.2.1.6 | Integer32 | read-write | current |
| epc2x6PortRepowerTime OBJECT-TYPE Delay in sec for repower port after switching off | 1.3.6.1.4.1.28507.6.1.2.2.1.7 | Integer32 (0..65535) | read-write | current |
| epc2x6portFuses OBJECT-TYPE Bit State of Fuses (Bit 0 = Fuse1, Bit 1 = Fuse2) | 1.3.6.1.4.1.28507.6.1.2.3 | Integer32 (0..3) | read-only | current |
| epc2x6Temperature OBJECT-TYPE actual Temperature, if sensor is not supported '9998', not connected '9999' is given back as result | 1.3.6.1.4.1.28507.6.1.3 | Integer32 | read-only | current |
| epc2x6Conf OBJECT-IDENTITY | 1.3.6.1.4.1.28507.6.3 | |||
| epc2x6Groups OBJECT-IDENTITY | 1.3.6.1.4.1.28507.6.3.1 | |||
| epc2x6Compls OBJECT-IDENTITY | 1.3.6.1.4.1.28507.6.3.2 |
Notifications
| Name | OID | Status |
|---|---|---|
| epc2x6witchEvt1 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.1 | current |
| epc2x6witchEvt2 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.2 | current |
| epc2x6witchEvt3 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.3 | current |
| epc2x6witchEvt4 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.4 | current |
| epc2x6witchEvt5 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.5 | current |
| epc2x6witchEvt6 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.6 | current |
| epc2x6witchEvt7 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.7 | current |
| epc2x6witchEvt8 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.8 | current |
| epc2x6witchEvt9 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.9 | current |
| epc2x6witchEvt10 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.10 | current |
| epc2x6witchEvt11 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.11 | current |
| epc2x6witchEvt12 NOTIFICATION-TYPE Event is triggered when | 1.3.6.1.4.1.28507.0.12 | current |
| epc2x6FuseEvt NOTIFICATION-TYPE | 1.3.6.1.4.1.28507.0.13 | current |
| epc2x6TempEvt NOTIFICATION-TYPE change of temperature | 1.3.6.1.4.1.28507.0.14 | current |
Conformance
| Name | OID | Status |
|---|---|---|
| epc2x6BasicGroup OBJECT-GROUP Basic objects. | 1.3.6.1.4.1.28507.6.3.1.1 | current |
| epc2x6NotificationGroup NOTIFICATION-GROUP | 1.3.6.1.4.1.28507.6.3.1.2 | current |