MIBs Depot

ENLOGIC-PDU-MIB

Registered at
1.3.6.1.4.1.38446
Last updated
2015-06-18 00:00
Organization
Enlogic
Revisions
2014-10-28 00:00, 2014-06-05 00:00, 2014-04-30 00:00, 2013-06-05 00:00, 2013-05-31 00:00, 2013-03-28 00:00, 2013-03-21 00:00, 2013-01-24 00:00, 2013-01-06 00:00, 2012-12-28 00:00, 2012-09-28 00:00, 2012-09-25 00:00, 2012-09-18 00:00, 2012-09-13 00:00
Namespace
enlogic
Source file
ENLOGIC-PDU-MIB
Digest
sha256:199dbcc3860d2de8b6ccb46c0a85564337373f929e395cf25ed5837fbea5a876

Description

This MIB describes the SNMP functions of the Enlogic PDU.

Imports

FromSymbols
INET-ADDRESS-MIBInetAddress, InetAddressType
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-MIBsysContact, sysLocation, sysName
SNMPv2-SMIInteger32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, enterprises, iso
SNMPv2-TCDisplayString, MacAddress, TEXTUAL-CONVENTION, TruthValue

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

ENLOGIC-PDU-MIB
INET-ADDRESS-MIB
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
pdu
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1
pduNamePlate
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.1
pduNamePlateTableSize
OBJECT-TYPE
The total number of PDUs
1.3.6.1.4.1.38446.1.1.1Integer32 (1..256)read-onlycurrent
pduNamePlateTable
OBJECT-TYPE
A table of PDU nameplate data
1.3.6.1.4.1.38446.1.1.2not-accessiblecurrent
pduNamePlateEntry
OBJECT-TYPE
Nameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize.
1.3.6.1.4.1.38446.1.1.2.1not-accessiblecurrent
pduNamePlateIndex
OBJECT-TYPE
The index of the PDU nameplate table entry
1.3.6.1.4.1.38446.1.1.2.1.1Integer32 (1..256)not-accessiblecurrent
pduNamePlateName
OBJECT-TYPE
A user-defined string identifying the PDU
1.3.6.1.4.1.38446.1.1.2.1.2DisplayStringread-onlycurrent
pduNamePlateLocation
OBJECT-TYPE
A user-defined string identifying the location of PDU
1.3.6.1.4.1.38446.1.1.2.1.3DisplayStringread-onlycurrent
pduNamePlateInetAddressType
OBJECT-TYPE
The type of address format
1.3.6.1.4.1.38446.1.1.2.1.4InetAddressTyperead-onlycurrent
pduNamePlateIPAddress
OBJECT-TYPE
The current IP address. A value of 0.0.0.0 indicates an error or an unset option
1.3.6.1.4.1.38446.1.1.2.1.5InetAddressread-onlycurrent
pduNamePlateInetNetMask
OBJECT-TYPE
The current netmask. A value of 0.0.0.0 indiates an error or an unset option
1.3.6.1.4.1.38446.1.1.2.1.6InetAddressread-onlycurrent
pduNamePlateInetGateway
OBJECT-TYPE
The current gateway. A value of 0.0.0.0 indicates an error or an unset option
1.3.6.1.4.1.38446.1.1.2.1.7InetAddressread-onlycurrent
pduNamePlateMACAddress
OBJECT-TYPE
The assigned MAC address for the PDU
1.3.6.1.4.1.38446.1.1.2.1.8MacAddressread-onlycurrent
pduNamePlateUTCTimeOffset
OBJECT-TYPE
The difference in hours and minutes from Coordinated Universal Time(UTC) for the time used in a particular time zone
1.3.6.1.4.1.38446.1.1.2.1.9DisplayStringread-onlycurrent
pduNamePlateModelNumber
OBJECT-TYPE
The PDU model number
1.3.6.1.4.1.38446.1.1.2.1.10DisplayStringread-onlycurrent
pduNamePlateSerialNumber
OBJECT-TYPE
The PDU serial number
1.3.6.1.4.1.38446.1.1.2.1.11DisplayStringread-onlycurrent
pduNamePlateDateofManufacture
OBJECT-TYPE
The date the PDU was manufactured in mm/dd/yyyy format
1.3.6.1.4.1.38446.1.1.2.1.12DisplayStringread-onlycurrent
pduNamePlateFirmwareVersion
OBJECT-TYPE
The PDU firmware version
1.3.6.1.4.1.38446.1.1.2.1.13DisplayStringread-onlycurrent
pduNamePlateFirmwareVersionTimeStamp
OBJECT-TYPE
Timestamp of when the PDU firmware was last updated
1.3.6.1.4.1.38446.1.1.2.1.14DisplayStringread-onlycurrent
pduNamePlateType
OBJECT-TYPE
The type of Unit, PDU or Inline Meter
1.3.6.1.4.1.38446.1.1.2.1.15INTEGER {pdu(0), inlineMeter(1)}read-onlycurrent
pduUnit
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.2
pduUnitTableSize
OBJECT-TYPE
The number of units.
1.3.6.1.4.1.38446.1.2.1Integer32 (1..256)read-onlycurrent
pduUnitConfigTable
OBJECT-TYPE
A table of PDU configuration data
1.3.6.1.4.1.38446.1.2.2not-accessiblecurrent
pduUnitConfigEntry
OBJECT-TYPE
Configuration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize
1.3.6.1.4.1.38446.1.2.2.1not-accessiblecurrent
pduUnitConfigIndex
OBJECT-TYPE
The index of the PDU Unit Config Entry
1.3.6.1.4.1.38446.1.2.2.1.1Integer32 (1..256)not-accessiblecurrent
pduUnitConfigName
OBJECT-TYPE
A user-defined string identifying the PDU
1.3.6.1.4.1.38446.1.2.2.1.2DisplayStringread-writecurrent
pduUnitConfigLocation
OBJECT-TYPE
A user-defined string identifying the location of the PDU
1.3.6.1.4.1.38446.1.2.2.1.3DisplayStringread-writecurrent
pduUnitConfigDisplayOrientation
OBJECT-TYPE
Indicates the intended physical orientation of the oLED display displayNormal (1) indicates normal orientation. displayReverse (2) indicates upside down orientation
1.3.6.1.4.1.38446.1.2.2.1.4INTEGER {displayNormal(1), displayReverse(2)}read-writecurrent
pduUnitConfigColdstartDelay
OBJECT-TYPE
The amount of time, specified in seconds, between when power is provided to the PDU and when the PDU start providing basic master power to the outlets
1.3.6.1.4.1.38446.1.2.2.1.5Unsigned32 (0..3600)read-writecurrent
pduUnitConfigGlobalOutletStateOnStartup
OBJECT-TYPE
The outlet state on device startup; applies to all outlets unless overridden at the outlet level
1.3.6.1.4.1.38446.1.2.2.1.6INTEGER {off(0), on(1), lastKnownState(2)}read-writecurrent
pduUnitConfigLowerCriticalThreshold
OBJECT-TYPE
User-defined lower critical unit active power alarm threshold measured in Watts
1.3.6.1.4.1.38446.1.2.2.1.7Unsigned32read-writecurrent
pduUnitConfigLowerWarningThreshold
OBJECT-TYPE
User-defined lower non-critical (warning) unit active power alarm threshold measured in Watts
1.3.6.1.4.1.38446.1.2.2.1.8Unsigned32read-writecurrent
pduUnitConfigUpperCriticalThreshold
OBJECT-TYPE
User-defined upper critical unit active power alarm threshold measured in Watts
1.3.6.1.4.1.38446.1.2.2.1.9Unsigned32read-writecurrent
pduUnitConfigUpperWarningThreshold
OBJECT-TYPE
User-defined upper non-critical (warning) unit active power alarm threshold measured in Watts
1.3.6.1.4.1.38446.1.2.2.1.10Unsigned32read-writecurrent
pduUnitConfigAlarmResetThreshold
OBJECT-TYPE
The hysteresis used for deassertions in Watts
1.3.6.1.4.1.38446.1.2.2.1.11Unsigned32read-writecurrent
pduUnitConfigAlarmStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
1.3.6.1.4.1.38446.1.2.2.1.12Unsigned32read-writecurrent
pduUnitConfigEnabledThresholds
OBJECT-TYPE
A bit string indicating which alarm thresholds are enabled
1.3.6.1.4.1.38446.1.2.2.1.13Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
pduUnitConfigPeakPowerReset
OBJECT-TYPE
Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and return the noOperation(1) value.
1.3.6.1.4.1.38446.1.2.2.1.14INTEGER {noOperation(1), reset(2)}read-writecurrent
pduUnitConfigEnergyReset
OBJECT-TYPE
Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
1.3.6.1.4.1.38446.1.2.2.1.15INTEGER {noOperation(1), reset(2), notSupported(3)}read-writecurrent
pduUnitConfigOutletPeakPowerReset
OBJECT-TYPE
Setting this OID to reset (2) will cause the outlet peak power meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
1.3.6.1.4.1.38446.1.2.2.1.16INTEGER {noOperation(1), reset(2), notSupported(3)}read-writecurrent
pduUnitConfigOutletEnergyReset
OBJECT-TYPE
Setting this OID to reset (2) will cause the outlet energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
1.3.6.1.4.1.38446.1.2.2.1.17INTEGER {noOperation(1), reset(2), notSupported(3)}read-writecurrent
pduUnitConfigUsb
OBJECT-TYPE
Setting this OID to off(0) will disable the USB port. Setting this OID to on(1) will enable the USB port.
1.3.6.1.4.1.38446.1.2.2.1.18INTEGER {off(0), on(1)}read-writecurrent
pduUnitConfigSsh
OBJECT-TYPE
Setting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection.
1.3.6.1.4.1.38446.1.2.2.1.19INTEGER {off(0), on(1)}read-writecurrent
pduUnitConfigResetNetworkManagementCard
OBJECT-TYPE
Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC.
1.3.6.1.4.1.38446.1.2.2.1.20INTEGER {noOperation(0), reset(1)}read-writecurrent
pduUnitConfigDaisyChainState
OBJECT-TYPE
Setting this OID to daisychain(0) will enable daisychain mode.
1.3.6.1.4.1.38446.1.2.2.1.21INTEGER {daisychain(0)}read-writecurrent
pduUnitPropertiesTable
OBJECT-TYPE
A table of PDU properties
1.3.6.1.4.1.38446.1.2.3not-accessiblecurrent
pduUnitPropertiesEntry
OBJECT-TYPE
A unit properties entry containing objects for a particular unit.
1.3.6.1.4.1.38446.1.2.3.1not-accessiblecurrent
pduUnitPropertiesIndex
OBJECT-TYPE
The index of the PDU properties table entry
1.3.6.1.4.1.38446.1.2.3.1.1Integer32 (1..256)not-accessiblecurrent
pduUnitPropertiesName
OBJECT-TYPE
A user-defined string identifying the PDU
1.3.6.1.4.1.38446.1.2.3.1.2DisplayStringread-onlycurrent
pduUnitPropertiesOutletCount
OBJECT-TYPE
The total number of outlets on the PDU
1.3.6.1.4.1.38446.1.2.3.1.3Integer32 (1..256)read-onlycurrent
pduUnitPropertiesSwitchedOutletCount
OBJECT-TYPE
The total number of switched outlets on the PDU
1.3.6.1.4.1.38446.1.2.3.1.4Integer32 (1..256)read-onlycurrent
pduUnitPropertiesMeteredOutletCount
OBJECT-TYPE
The total number of metered outlets on the PDU
1.3.6.1.4.1.38446.1.2.3.1.5Integer32 (1..256)read-onlycurrent
pduUnitPropertiesInputPhaseCount
OBJECT-TYPE
The total number of phases on the PDU
1.3.6.1.4.1.38446.1.2.3.1.6Integer32 (1..256)read-onlycurrent
pduUnitPropertiesCircuitBreakerCount
OBJECT-TYPE
The total number of circuit breaker on the PDU
1.3.6.1.4.1.38446.1.2.3.1.7Integer32 (0..255)read-onlycurrent
pduUnitPropertiesMaxExternalSensorCount
OBJECT-TYPE
The maximum number of external sensors that can be connected to the PDU
1.3.6.1.4.1.38446.1.2.3.1.8Integer32 (0..255)read-onlycurrent
pduUnitPropertiesConnExternalSensorCount
OBJECT-TYPE
The current number of external sensors connected to the PDU
1.3.6.1.4.1.38446.1.2.3.1.9Integer32 (0..255)read-onlycurrent
pduUnitPropertiesRatedVoltage
OBJECT-TYPE
The PDU voltage rating in Volts
1.3.6.1.4.1.38446.1.2.3.1.10DisplayStringread-onlycurrent
pduUnitPropertiesRatedMaxCurrent
OBJECT-TYPE
The PDU current rating in Amps
1.3.6.1.4.1.38446.1.2.3.1.11DisplayStringread-onlycurrent
pduUnitPropertiesRatedFrequency
OBJECT-TYPE
The PDU frequency rating in Hz
1.3.6.1.4.1.38446.1.2.3.1.12DisplayStringread-onlycurrent
pduUnitPropertiesRatedPower
OBJECT-TYPE
The PDU VA (VoltAmps) rating.
1.3.6.1.4.1.38446.1.2.3.1.13DisplayStringread-onlycurrent
pduUnitPropertiesOrientation
OBJECT-TYPE
The PDU orientation
1.3.6.1.4.1.38446.1.2.3.1.14INTEGER {horizontal(1), vertical(2)}read-onlycurrent
pduUnitPropertiesOutletLayout
OBJECT-TYPE
The outlet layout for the PDU. Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... seqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... seqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... seqPhToPhGrouped(4) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-2, Group 2:2-3, Group 3:3-1. seqPhToNGrouped(5) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N. seqPToN1516PToPGrouped(6) indicates outlet layout as follows: This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2, Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1. seqPhToPh2xGrouped(7) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3, Group 4:2-3, Group 5:3-1, Group 6:3-1. seqPhToN2xGrouped(8) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N, Group 4:2-N, Group 5:3-N, Group 6:3-N. seqNotApplicable(9):
1.3.6.1.4.1.38446.1.2.3.1.15INTEGER {seqPhaseToNuetral(1), seqPhaseToPhase(2), seqPhToNeu21PhToPh(3), seqPhToPhGrouped(4), seqPhToNGrouped(5), seqPToN1516PToPGrouped(6), seqPhToPh2xGrouped(7), seqPhToN2xGrouped(8), seqNotApplicable(9)}read-onlycurrent
pduUnitPropertiesDaisyChainMemberType
OBJECT-TYPE
The daisy-chain member type
1.3.6.1.4.1.38446.1.2.3.1.16INTEGER {standalone(1), parent(2), child(3)}read-onlycurrent
pduUnitPropertiesServerCount
OBJECT-TYPE
The number of servers
1.3.6.1.4.1.38446.1.2.3.1.17Integer32 (0..255)read-onlycurrent
pduUnitStatusTable
OBJECT-TYPE
A table of PDU status information
1.3.6.1.4.1.38446.1.2.4not-accessiblecurrent
pduUnitStatusEntry
OBJECT-TYPE
Status information from the PDU being queried
1.3.6.1.4.1.38446.1.2.4.1not-accessiblecurrent
pduUnitStatusIndex
OBJECT-TYPE
The index of the PDU status table entry
1.3.6.1.4.1.38446.1.2.4.1.1Integer32 (1..256)not-accessiblecurrent
pduUnitStatusName
OBJECT-TYPE
A user-defined string identifying the PDU
1.3.6.1.4.1.38446.1.2.4.1.2DisplayStringread-onlycurrent
pduUnitStatusLoadState
OBJECT-TYPE
Returns the present load status of the PDU based on Active Power.
1.3.6.1.4.1.38446.1.2.4.1.3INTEGER {upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)}read-onlycurrent
pduUnitStatusActivePower
OBJECT-TYPE
Returns power consumption, in Watts(W), of the PDU being queried.
1.3.6.1.4.1.38446.1.2.4.1.4Integer32read-onlycurrent
pduUnitStatusApparentPower
OBJECT-TYPE
Returns power consumption, in Volt-Amps(VA) of the PDU load being queried.
1.3.6.1.4.1.38446.1.2.4.1.5Integer32read-onlycurrent
pduUnitStatusPeakPower
OBJECT-TYPE
Returns peak power consumption, in Watts(W), of the PDU being queried.
1.3.6.1.4.1.38446.1.2.4.1.6Integer32read-onlycurrent
pduUnitStatusPeakPowerTimestamp
OBJECT-TYPE
Indicates the date and time that peak power consumption occurred
1.3.6.1.4.1.38446.1.2.4.1.7DisplayStringread-onlycurrent
pduUnitStatusPeakPowerStartTime
OBJECT-TYPE
Indicates the date and time of the last device peak power reset
1.3.6.1.4.1.38446.1.2.4.1.8DisplayStringread-onlycurrent
pduUnitStatusEnergy
OBJECT-TYPE
Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime.
1.3.6.1.4.1.38446.1.2.4.1.9Integer32read-onlycurrent
pduUnitStatusResettableEnergy
OBJECT-TYPE
A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).
1.3.6.1.4.1.38446.1.2.4.1.10Integer32read-onlycurrent
pduUnitStatusEnergyStartTime
OBJECT-TYPE
Indicates the date and time of the last device energy meter reset
1.3.6.1.4.1.38446.1.2.4.1.11DisplayStringread-onlycurrent
pduUnitStatusOutletsEnergyStartTime
OBJECT-TYPE
Indicates the date and time of the last outlets energy meter reset
1.3.6.1.4.1.38446.1.2.4.1.12DisplayStringread-onlycurrent
pduInputPhase
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.3
pduInputPhaseTableSize
OBJECT-TYPE
The number of PDU Input Phases
1.3.6.1.4.1.38446.1.3.1Integer32 (1..256)read-onlycurrent
pduInputPhaseConfigTable
OBJECT-TYPE
A table of PDU Input Phase configuration data
1.3.6.1.4.1.38446.1.3.2not-accessiblecurrent
pduInputPhaseConfigEntry
OBJECT-TYPE
An input phase entry containing objects for a particular input phase.
1.3.6.1.4.1.38446.1.3.2.1not-accessiblecurrent
pduInputPhaseConfigIndex
OBJECT-TYPE
The index of the PDU Input Phase configuration table entry
1.3.6.1.4.1.38446.1.3.2.1.1Integer32 (1..256)not-accessiblecurrent
pduInputPhaseConfigCount
OBJECT-TYPE
The total number of Input Phases
1.3.6.1.4.1.38446.1.3.2.1.2Integer32 (1..256)read-onlycurrent
pduInputPhaseConfigOverloadRestriction
OBJECT-TYPE
This OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
1.3.6.1.4.1.38446.1.3.2.1.3INTEGER {alwaysAllowTurnOn(1), restrictOnUpperWarning(2), restrictOnUpperCritical(3), notSupported(4)}read-writecurrent
pduInputPhaseConfigCurrentLowerCriticalThreshold
OBJECT-TYPE
User-defined lower critical input phase current alarm threshold in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.3.2.1.4Unsigned32read-writecurrent
pduInputPhaseConfigCurrentLowerWarningThreshold
OBJECT-TYPE
User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.3.2.1.5Unsigned32read-writecurrent
pduInputPhaseConfigCurrentUpperCriticalThreshold
OBJECT-TYPE
User-defined upper critical input phase current alarm threshold in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.3.2.1.6Unsigned32read-writecurrent
pduInputPhaseConfigCurrentUpperWarningThreshold
OBJECT-TYPE
User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.3.2.1.7Unsigned32read-writecurrent
pduInputPhaseConfigVoltageLowerCriticalThreshold
OBJECT-TYPE
User-defined lower critical input phase voltage alarm threshold in Volts(V).
1.3.6.1.4.1.38446.1.3.2.1.8Unsigned32read-writecurrent
pduInputPhaseConfigVoltageLowerWarningThreshold
OBJECT-TYPE
User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V).
1.3.6.1.4.1.38446.1.3.2.1.9Unsigned32read-writecurrent
pduInputPhaseConfigVoltageUpperCriticalThreshold
OBJECT-TYPE
User-defined upper critical input phase voltage alarm threshold in Volts(V).
1.3.6.1.4.1.38446.1.3.2.1.10Unsigned32read-writecurrent
pduInputPhaseConfigVoltageUpperWarningThreshold
OBJECT-TYPE
User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V).
1.3.6.1.4.1.38446.1.3.2.1.11Unsigned32read-writecurrent
pduInputPhaseConfigCurrentAlarmResetThreshold
OBJECT-TYPE
The hysteresis used for current alarm deassertions in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.3.2.1.12Unsigned32read-writecurrent
pduInputPhaseConfigCurrentAlarmStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a current state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
1.3.6.1.4.1.38446.1.3.2.1.13Integer32read-writecurrent
pduInputPhaseConfigCurrentEnabledThresholds
OBJECT-TYPE
A bit string indicating which current alarm thresholds are enabled.
1.3.6.1.4.1.38446.1.3.2.1.14Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
pduInputPhaseConfigVoltageAlarmResetThreshold
OBJECT-TYPE
The hysteresis used for voltage alarm deassertions in Volts(V).
1.3.6.1.4.1.38446.1.3.2.1.15Unsigned32read-writecurrent
pduInputPhaseConfigVoltageAlarmStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a voltage state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
1.3.6.1.4.1.38446.1.3.2.1.16Integer32read-writecurrent
pduInputPhaseConfigVoltageEnabledThresholds
OBJECT-TYPE
A bit string indicating which voltage alarm thresholds are enabled.
1.3.6.1.4.1.38446.1.3.2.1.17Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
pduInputPhasePropertiesTable
OBJECT-TYPE
A table of PDU Input Phase properties
1.3.6.1.4.1.38446.1.3.3not-accessiblecurrent
pduInputPhasePropertiesEntry
OBJECT-TYPE
An input phase properties entry containing objects for a particular input phase.
1.3.6.1.4.1.38446.1.3.3.1not-accessiblecurrent
pduInputPhasePropertiesIndex
OBJECT-TYPE
The index of the PDU Input Phase status entry
1.3.6.1.4.1.38446.1.3.3.1.1Integer32 (1..256)not-accessiblecurrent
pduInputPhasePropertiesCount
OBJECT-TYPE
The numeric Input Phase ID
1.3.6.1.4.1.38446.1.3.3.1.2Integer32 (1..256)read-onlycurrent
pduInputPhaseStatusTable
OBJECT-TYPE
A table of PDU Input Phase status data
1.3.6.1.4.1.38446.1.3.4not-accessiblecurrent
pduInputPhaseStatusEntry
OBJECT-TYPE
An input phase status entry containing objects for a particular input phase.
1.3.6.1.4.1.38446.1.3.4.1not-accessiblecurrent
pduInputPhaseStatusIndex
OBJECT-TYPE
The index of the PDU Input Phase status entry
1.3.6.1.4.1.38446.1.3.4.1.1Integer32 (1..256)not-accessiblecurrent
pduInputPhaseStatusCount
OBJECT-TYPE
The numeric Input Phase ID
1.3.6.1.4.1.38446.1.3.4.1.2Integer32 (1..256)read-onlycurrent
pduInputPhaseStatusCurrentState
OBJECT-TYPE
Indicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton.
1.3.6.1.4.1.38446.1.3.4.1.3INTEGER {upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)}read-onlycurrent
pduInputPhaseStatusVoltageState
OBJECT-TYPE
Indicates the present voltage status of the PDU Input Phase being queried
1.3.6.1.4.1.38446.1.3.4.1.4INTEGER {upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)}read-onlycurrent
pduInputPhaseStatusCurrent
OBJECT-TYPE
Returns the current draw, in hundredths of Amps(A), of the load on the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
1.3.6.1.4.1.38446.1.3.4.1.5Integer32read-onlycurrent
pduInputPhaseStatusVoltage
OBJECT-TYPE
Returns the voltage, in Volts(V), of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
1.3.6.1.4.1.38446.1.3.4.1.6Integer32read-onlycurrent
pduInputPhaseStatusActivePower
OBJECT-TYPE
Returns power consumption, in Watts(W), consumed on the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
1.3.6.1.4.1.38446.1.3.4.1.7Integer32read-onlycurrent
pduInputPhaseStatusApparentPower
OBJECT-TYPE
Returns power consumption, in Volt-Amps(VA), of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
1.3.6.1.4.1.38446.1.3.4.1.8Integer32read-onlycurrent
pduInputPhaseStatusPowerFactor
OBJECT-TYPE
Returns the ratio of active to apparent power of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
1.3.6.1.4.1.38446.1.3.4.1.9Integer32read-onlycurrent
pduCircuitBreaker
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.4
pduCircuitBreakerTableSize
OBJECT-TYPE
The number of PDU Circuit Breakers
1.3.6.1.4.1.38446.1.4.1Integer32 (1..256)read-onlycurrent
pduCircuitBreakerConfigTable
OBJECT-TYPE
A table of PDU Circuit Breaker configuration data
1.3.6.1.4.1.38446.1.4.2not-accessiblecurrent
pduCircuitBreakerConfigEntry
OBJECT-TYPE
A circuit breaker configuration entry containing objects for a particular circuit breaker.
1.3.6.1.4.1.38446.1.4.2.1not-accessiblecurrent
pduCircuitBreakerConfigIndex
OBJECT-TYPE
The index of the PDU Circuit Breaker configuration table entry
1.3.6.1.4.1.38446.1.4.2.1.1Integer32 (1..256)not-accessiblecurrent
pduCircuitBreakerConfigCount
OBJECT-TYPE
The number of circuit breakers on the PDU
1.3.6.1.4.1.38446.1.4.2.1.2Integer32 (0..255)read-onlycurrent
pduCircuitBreakerName
OBJECT-TYPE
The label of the circuit breaker
1.3.6.1.4.1.38446.1.4.2.1.3DisplayStringread-onlycurrent
pduCircuitBreakerConfigOverloadRestriction
OBJECT-TYPE
This OID controls the behavior of a Switched PDU Circuit Breaker when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Circuit Breaker to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
1.3.6.1.4.1.38446.1.4.2.1.4INTEGER {alwaysAllowTurnOn(1), restrictOnUpperWarning(2), restrictOnUpperCritical(3), notSupported(4)}read-writecurrent
pduCircuitBreakerConfigLowerCriticalThreshold
OBJECT-TYPE
User-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.4.2.1.5Unsigned32read-writecurrent
pduCircuitBreakerConfigLowerWarningThreshold
OBJECT-TYPE
User-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.4.2.1.6Unsigned32read-writecurrent
pduCircuitBreakerConfigUpperCriticalThreshold
OBJECT-TYPE
User-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.4.2.1.7Unsigned32read-writecurrent
pduCircuitBreakerConfigUpperWarningThreshold
OBJECT-TYPE
User-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.4.2.1.8Unsigned32read-writecurrent
pduCircuitBreakerConfigAlarmResetThreshold
OBJECT-TYPE
The hysteresis used for deassertions in hundredths of Amps(A).
1.3.6.1.4.1.38446.1.4.2.1.9Unsigned32read-writecurrent
pduCircuitBreakerConfigAlarmStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
1.3.6.1.4.1.38446.1.4.2.1.10Unsigned32read-writecurrent
pduCircuitBreakerConfigEnabledThresholds
OBJECT-TYPE
A bit string indicating which alarm thresholds are enabled.
1.3.6.1.4.1.38446.1.4.2.1.11Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
pduCircuitBreakerPropertiesTable
OBJECT-TYPE
A table of PDU circuit breaker properties
1.3.6.1.4.1.38446.1.4.3not-accessiblecurrent
pduCircuitBreakerPropertiesEntry
OBJECT-TYPE
A circuit breaker properties entry containing objects for a particular circuit breaker.
1.3.6.1.4.1.38446.1.4.3.1not-accessiblecurrent
pduCircuitBreakerPropertiesIndex
OBJECT-TYPE
The index of the PDU Circuit Breaker properties table entry
1.3.6.1.4.1.38446.1.4.3.1.1Integer32 (1..256)not-accessiblecurrent
pduCircuitBreakerPropertiesCount
OBJECT-TYPE
The number of Circuit Breakers
1.3.6.1.4.1.38446.1.4.3.1.2Integer32 (0..255)read-onlycurrent
pduCircuitBreakerPropertiesInputLayout
OBJECT-TYPE
This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to circuit breaker are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to circuit breaker are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to circuit breaker are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to circuit breaker are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to circuit breaker are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to circuit breaker are connected from Phase 3 to Phase1.
1.3.6.1.4.1.38446.1.4.3.1.3INTEGER {seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6)}read-onlycurrent
pduCircuitBreakerStatusTable
OBJECT-TYPE
A table of PDU circuit breaker status data
1.3.6.1.4.1.38446.1.4.4not-accessiblecurrent
pduCircuitBreakerStatusEntry
OBJECT-TYPE
A circuit breaker status entry containing objects for a particular circuit breaker.
1.3.6.1.4.1.38446.1.4.4.1not-accessiblecurrent
pduCircuitBreakerStatusIndex
OBJECT-TYPE
The index of the PDU Circuit Breaker status table entry
1.3.6.1.4.1.38446.1.4.4.1.1Integer32 (1..256)not-accessiblecurrent
pduCircuitBreakerStatusCount
OBJECT-TYPE
The number of Circuit Breakers
1.3.6.1.4.1.38446.1.4.4.1.2Integer32 (0..255)read-onlycurrent
pduCircuitBreakerLabel
OBJECT-TYPE
The label on the PDU identifying the circuit breaker
1.3.6.1.4.1.38446.1.4.4.1.3DisplayStringread-onlycurrent
pduCircuitBreakerStatusLoadState
OBJECT-TYPE
Indicates the present load status of the PDU Circuit Breaker being queried
1.3.6.1.4.1.38446.1.4.4.1.4INTEGER {upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5), off(6)}read-onlycurrent
pduCircuitBreakerStatusCurrent
OBJECT-TYPE
Returns the current draw, in hundredths of Amps(A), of the load on the PDU Circuit Breaker being queried.
1.3.6.1.4.1.38446.1.4.4.1.5Integer32read-onlycurrent
pduOutlet
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.5
pduOutletSwitchedTableSize
OBJECT-TYPE
The number of PDU Outlets
1.3.6.1.4.1.38446.1.5.1Integer32 (1..256)read-onlycurrent
pduOutletSwitchedConfigTable
OBJECT-TYPE
A table of PDU Switched Outlet configuration data
1.3.6.1.4.1.38446.1.5.2not-accessiblecurrent
pduOutletSwitchedConfigEntry
OBJECT-TYPE
An outlet configuration entry containing objects for a particular outlet.
1.3.6.1.4.1.38446.1.5.2.1not-accessiblecurrent
pduOutletSwitchedConfigIndex
OBJECT-TYPE
The index of the PDU Switched Outlet configuration table entry
1.3.6.1.4.1.38446.1.5.2.1.1Integer32 (1..256)not-accessiblecurrent
pduOutletSwitchedName
OBJECT-TYPE
The user-defined name for the Switched Outlet
1.3.6.1.4.1.38446.1.5.2.1.2DisplayStringread-writecurrent
pduOutletSwitchedStateOnStartup
OBJECT-TYPE
The outlet state on device startup; overrides the global value pduUnitConfigGlobalOutletStateOnStartup.
1.3.6.1.4.1.38446.1.5.2.1.3INTEGER {off(0), on(1), lastKnownState(2)}read-writecurrent
pduOutletSwitchedConfigPowerOnTime
OBJECT-TYPE
The amount of delay, in seconds, between when power is provided to outlets the outlet and when this outlet starts providing power
1.3.6.1.4.1.38446.1.5.2.1.4Integer32read-writecurrent
pduOutletSwitchedConfigPowerOffTime
OBJECT-TYPE
The amount of time, in seconds, this outlet will delay powering off
1.3.6.1.4.1.38446.1.5.2.1.5Integer32read-writecurrent
pduOutletSwitchedConfigRebootDuration
OBJECT-TYPE
The amount of time, in seconds, this outlet will remain in powered off state before returning to power on state during a reboot action.
1.3.6.1.4.1.38446.1.5.2.1.6Integer32read-writecurrent
pduOutletSwitchedPropertiesTable
OBJECT-TYPE
A table of PDU Switched Outlet properties
1.3.6.1.4.1.38446.1.5.3not-accessiblecurrent
pduOutletSwitchedPropertiesEntry
OBJECT-TYPE
An outlet properties entry containing objects for a particular outlet.
1.3.6.1.4.1.38446.1.5.3.1not-accessiblecurrent
pduOutletSwitchedPropertiesIndex
OBJECT-TYPE
The index of the PDU Switched Outlet properties table entry
1.3.6.1.4.1.38446.1.5.3.1.1Integer32 (1..256)not-accessiblecurrent
pduOutletSwitchedPropertiesNumber
OBJECT-TYPE
The numeric Switched Outlet ID
1.3.6.1.4.1.38446.1.5.3.1.2Integer32 (1..256)read-onlycurrent
pduOutletSwitchedPropertiesName
OBJECT-TYPE
The user-defined switched outlet ID string
1.3.6.1.4.1.38446.1.5.3.1.3DisplayStringread-onlycurrent
pduOutletSwitchedPropertiesInputPhaseLayout
OBJECT-TYPE
This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Phase1.
1.3.6.1.4.1.38446.1.5.3.1.4INTEGER {seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6)}read-onlycurrent
pduOutletSwitchedPropertiesCircuitBreaker
OBJECT-TYPE
The numeric Circuit Breaker ID
1.3.6.1.4.1.38446.1.5.3.1.5Integer32 (1..256)read-onlycurrent
pduOutletSwitchedStatusTable
OBJECT-TYPE
A table of PDU Switched Outlet status data
1.3.6.1.4.1.38446.1.5.4not-accessiblecurrent
pduOutletSwitchedStatusEntry
OBJECT-TYPE
Status data from the PDU Switched Outlet being queried
1.3.6.1.4.1.38446.1.5.4.1not-accessiblecurrent
pduOutletSwitchedStatusIndex
OBJECT-TYPE
The index of the PDU Switched Outlet status table entry
1.3.6.1.4.1.38446.1.5.4.1.1Integer32 (1..256)not-accessiblecurrent
pduOutletSwitchedStatusNumber
OBJECT-TYPE
The numeric Switched Outlet ID
1.3.6.1.4.1.38446.1.5.4.1.2Integer32 (1..256)read-onlycurrent
pduOutletSwitchedStatusName
OBJECT-TYPE
The user-defined switched outlet ID string
1.3.6.1.4.1.38446.1.5.4.1.3DisplayStringread-onlycurrent
pduOutletSwitchedStatusState
OBJECT-TYPE
Indicates the present switch state of the PDU switched outlet being queried
1.3.6.1.4.1.38446.1.5.4.1.4INTEGER {off(0), on(1)}read-onlycurrent
pduOutletSwitchedControlTable
OBJECT-TYPE
A table of PDU Switched Outlet status data
1.3.6.1.4.1.38446.1.5.5not-accessiblecurrent
pduOutletSwitchedControlEntry
OBJECT-TYPE
Status data from the PDU Switched Outlet being queried
1.3.6.1.4.1.38446.1.5.5.1not-accessiblecurrent
pduOutletSwitchedControlIndex
OBJECT-TYPE
The index to the PDU switched outlet control data table entry
1.3.6.1.4.1.38446.1.5.5.1.1Integer32 (1..256)not-accessiblecurrent
pduOutletSwitchedControlNumber
OBJECT-TYPE
The numeric Switched Outlet ID
1.3.6.1.4.1.38446.1.5.5.1.2Integer32 (1..256)read-onlycurrent
pduOutletSwitchedControlName
OBJECT-TYPE
The user-defined switched outlet ID string
1.3.6.1.4.1.38446.1.5.5.1.3DisplayStringread-onlycurrent
pduOutletSwitchedControlCommand
OBJECT-TYPE
Getting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (1) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (7) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (1) will immediately turn the outlet off. Setting this variable to immediateReboot (5) will cause the Switched PDU to perform an immediateOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (4) will turn the outlet on after the pduOutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (3) will turn the outlet off after the pduOutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched PDU to perform a delayedOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command.
1.3.6.1.4.1.38446.1.5.5.1.4INTEGER {immediateOff(1), immediateOn(2), delayedOff(3), delayedOn(4), immediateReboot(5), delayedReboot(6), outletUnknown(7)}read-writecurrent
pduOutletMeteredTableSize
OBJECT-TYPE
The number of PDU Outlets
1.3.6.1.4.1.38446.1.5.6Integer32 (1..256)read-onlycurrent
pduOutletMeteredConfigTable
OBJECT-TYPE
A table of PDU Metered Outlet configuration data
1.3.6.1.4.1.38446.1.5.7not-accessiblecurrent
pduOutletMeteredConfigEntry
OBJECT-TYPE
An outlet configuration entry containing objects for a particular outlet.
1.3.6.1.4.1.38446.1.5.7.1not-accessiblecurrent
pduOutletMeteredConfigIndex
OBJECT-TYPE
The index of the PDU Metered Outlet configuration table entry
1.3.6.1.4.1.38446.1.5.7.1.1Integer32 (1..256)not-accessiblecurrent
pduOutletMeteredName
OBJECT-TYPE
The user-defined name for the Metered Outlet
1.3.6.1.4.1.38446.1.5.7.1.2DisplayStringread-writecurrent
pduOutletMeteredConfigLowerCriticalThreshold
OBJECT-TYPE
User-defined lower critical outlet active power alarm threshold in Watts(W).
1.3.6.1.4.1.38446.1.5.7.1.3Unsigned32read-writecurrent
pduOutletMeteredConfigLowerWarningThreshold
OBJECT-TYPE
User-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W).
1.3.6.1.4.1.38446.1.5.7.1.4Unsigned32read-writecurrent
pduOutletMeteredConfigUpperCriticalThreshold
OBJECT-TYPE
User-defined upper critical outlet active power alarm threshold in Watts(W).
1.3.6.1.4.1.38446.1.5.7.1.5Unsigned32read-writecurrent
pduOutletMeteredConfigUpperWarningThreshold
OBJECT-TYPE
User-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W).
1.3.6.1.4.1.38446.1.5.7.1.6Unsigned32read-writecurrent
pduOutletMeteredConfigAlarmResetThreshold
OBJECT-TYPE
The hysteresis used for deassertions in Watts(W).
1.3.6.1.4.1.38446.1.5.7.1.7Unsigned32read-writecurrent
pduOutletMeteredConfigAlarmStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
1.3.6.1.4.1.38446.1.5.7.1.8Unsigned32read-writecurrent
pduOutletMeteredConfigEnabledThresholds
OBJECT-TYPE
A bit string indicating which alarm thresholds are enabled.
1.3.6.1.4.1.38446.1.5.7.1.9Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)}read-writecurrent
pduOutletMeteredPropertiesTable
OBJECT-TYPE
A table of PDU Metered Outlet properties
1.3.6.1.4.1.38446.1.5.8not-accessiblecurrent
pduOutletMeteredPropertiesEntry
OBJECT-TYPE
Configuration data from the PDU Metered Outlet being queried
1.3.6.1.4.1.38446.1.5.8.1not-accessiblecurrent
pduOutletMeteredPropertiesIndex
OBJECT-TYPE
The index of the PDU Metered Outlet properties table entry
1.3.6.1.4.1.38446.1.5.8.1.1Integer32 (1..256)not-accessiblecurrent
pduOutletMeteredPropertiesNumber
OBJECT-TYPE
The numeric Metered Outlet ID
1.3.6.1.4.1.38446.1.5.8.1.2Integer32 (1..256)read-onlycurrent
pduOutletMeteredPropertiesName
OBJECT-TYPE
The user-defined Metered outlet ID string
1.3.6.1.4.1.38446.1.5.8.1.3DisplayStringread-onlycurrent
pduOutletMeteredPropertiesInputPhaseLayout
OBJECT-TYPE
This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Phase1.
1.3.6.1.4.1.38446.1.5.8.1.4INTEGER {seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6)}read-onlycurrent
pduOutletMeteredPropertiesCircuitBreaker
OBJECT-TYPE
The numeric Circuit Breaker ID
1.3.6.1.4.1.38446.1.5.8.1.5Integer32 (1..256)read-onlycurrent
pduOutletMeteredPropertiesPowerRating
OBJECT-TYPE
Maximum power rating of the PDU metered outlet
1.3.6.1.4.1.38446.1.5.8.1.6Integer32read-onlycurrent
pduOutletMeteredStatusTable
OBJECT-TYPE
A table of PDU Metered Outlet status data
1.3.6.1.4.1.38446.1.5.9not-accessiblecurrent
pduOutletMeteredStatusEntry
OBJECT-TYPE
Status data from the PDU Metered Outlet being queried
1.3.6.1.4.1.38446.1.5.9.1not-accessiblecurrent
pduOutletMeteredStatusIndex
OBJECT-TYPE
The index of the PDU Metered Outlet status table entry
1.3.6.1.4.1.38446.1.5.9.1.1Integer32 (1..256)not-accessiblecurrent
pduOutletMeteredStatusNumber
OBJECT-TYPE
The numeric Metered Outlet ID
1.3.6.1.4.1.38446.1.5.9.1.2Integer32 (1..256)read-onlycurrent
pduOutletMeteredStatusName
OBJECT-TYPE
The user-defined Metered outlet ID string
1.3.6.1.4.1.38446.1.5.9.1.3DisplayStringread-onlycurrent
pduOutletMeteredStatusLoadState
OBJECT-TYPE
Returns the present load status of the PDU metered outlet being queried.
1.3.6.1.4.1.38446.1.5.9.1.4INTEGER {upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)}read-onlycurrent
pduOutletMeteredStatusCurrent
OBJECT-TYPE
Returns the current draw, in hundredths of Amps(A), of the load on the PDU outlet being queried.
1.3.6.1.4.1.38446.1.5.9.1.5Integer32read-onlycurrent
pduOutletMeteredStatusActivePower
OBJECT-TYPE
Returns the power draw, in Watts(W), of the load on the PDU outlet being queried.
1.3.6.1.4.1.38446.1.5.9.1.6Integer32read-onlycurrent
pduOutletMeteredStatusPowerFactor
OBJECT-TYPE
Returns the ratio of active to apparent power of the PDU Outlet being queried
1.3.6.1.4.1.38446.1.5.9.1.7Integer32read-onlycurrent
pduOutletMeteredStatusPeakPower
OBJECT-TYPE
Returns peak power consumption, in Watts(W), of the Rack PDU outlet being queried.
1.3.6.1.4.1.38446.1.5.9.1.8Integer32read-onlycurrent
pduOutletMeteredStatusPeakPowerTimeStamp
OBJECT-TYPE
Indicates the date and time that this metered outlet's peak power consumption occurred
1.3.6.1.4.1.38446.1.5.9.1.9DisplayStringread-onlycurrent
pduOutletMeteredStatusPeakPowerStartTime
OBJECT-TYPE
Indicates the start date and time that this metered outlet began recording peak power observations
1.3.6.1.4.1.38446.1.5.9.1.10DisplayStringread-onlycurrent
pduOutletMeteredStatusResettableEnergy
OBJECT-TYPE
A user resettable energy meter measuring outlet load energy consumption in tenths of Kilowatt-Hours(kWh).
1.3.6.1.4.1.38446.1.5.9.1.11Integer32read-onlycurrent
pduExternalSensor
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.6
pduExternalSensorTableSize
OBJECT-TYPE
The total number of External Sensors
1.3.6.1.4.1.38446.1.6.1Integer32 (1..256)read-onlycurrent
pduExternalSensorNamePlateTable
OBJECT-TYPE
A table of PDU ExternalSensorNamePlate data
1.3.6.1.4.1.38446.1.6.2not-accessiblecurrent
pduExternalSensorNamePlateEntry
OBJECT-TYPE
External Sensor Name Plate data from the external sensor being queried. The number of entries equals the value of pduExternalSensorNamePlateTableSize.
1.3.6.1.4.1.38446.1.6.2.1not-accessiblecurrent
pduExternalSensorNamePlateIndex
OBJECT-TYPE
The index of the PDU External Sensor status table entry
1.3.6.1.4.1.38446.1.6.2.1.1Integer32 (0..255)not-accessiblecurrent
pduExternalSensorNamePlateName
OBJECT-TYPE
A user-defined string identifying the external sensor
1.3.6.1.4.1.38446.1.6.2.1.2DisplayStringread-writecurrent
pduExternalSensorNamePlateDescription
OBJECT-TYPE
A user-defined description of the external sensor
1.3.6.1.4.1.38446.1.6.2.1.3DisplayStringread-writecurrent
pduExternalSensorNamePlateLocation
OBJECT-TYPE
A user-defined string identifying the location of the PDU
1.3.6.1.4.1.38446.1.6.2.1.4DisplayStringread-writecurrent
pduExternalSensorNamePlateSerialNumber
OBJECT-TYPE
The serial number of the external sensor being queried
1.3.6.1.4.1.38446.1.6.2.1.5DisplayStringread-onlycurrent
pduExternalSensorNamePlateType
OBJECT-TYPE
The type of external sensor.
1.3.6.1.4.1.38446.1.6.2.1.6INTEGER {temperature(1), humidity(2), doorSwitch(3), dryContact(4), spotFluid(5), ropeFluid(6), smoke(7), beacon(8), airVelocity(9), modbusAdapter(17), hidAdapter(18)}read-onlycurrent
pduExternalSensorNamePlateUnits
OBJECT-TYPE
The base units the external sensor is measured in. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
1.3.6.1.4.1.38446.1.6.2.1.7INTEGER {logic(0), degreeC(1), degreeF(2), percent(3), mps(4)}read-onlycurrent
pduExternalSensorNamePlateIdentifier
OBJECT-TYPE
Unique identifier of the external sensor.
1.3.6.1.4.1.38446.1.6.2.1.8Integer32read-onlycurrent
pduExternalSensorConfigTable
OBJECT-TYPE
A table of PDU External Sensor configuration data
1.3.6.1.4.1.38446.1.6.3not-accessiblecurrent
pduExternalSensorConfigEntry
OBJECT-TYPE
Configuration data from the PDU External Sensor being queried
1.3.6.1.4.1.38446.1.6.3.1not-accessiblecurrent
pduExternalSensorConfigIndex
OBJECT-TYPE
The index of the PDU External Sensor configuration table entry
1.3.6.1.4.1.38446.1.6.3.1.1Integer32 (0..255)not-accessiblecurrent
pduExternalSensorConfigLowerCriticalThreshold
OBJECT-TYPE
User-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits.
1.3.6.1.4.1.38446.1.6.3.1.2Unsigned32read-writecurrent
pduExternalSensorConfigLowerWarningThreshold
OBJECT-TYPE
User-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits.
1.3.6.1.4.1.38446.1.6.3.1.3Unsigned32read-writecurrent
pduExternalSensorConfigUpperCriticalThreshold
OBJECT-TYPE
User-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits.
1.3.6.1.4.1.38446.1.6.3.1.4Unsigned32read-writecurrent
pduExternalSensorConfigUpperWarningThreshold
OBJECT-TYPE
User-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits.
1.3.6.1.4.1.38446.1.6.3.1.5Unsigned32read-writecurrent
pduExternalSensorConfigAlarmResetThreshold
OBJECT-TYPE
The hysteresis used for deassertions.
1.3.6.1.4.1.38446.1.6.3.1.6Unsigned32read-writecurrent
pduExternalSensorConfigAlarmStateChangeDelay
OBJECT-TYPE
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
1.3.6.1.4.1.38446.1.6.3.1.7Unsigned32read-writecurrent
pduExternalSensorConfigEnabledThresholds
OBJECT-TYPE
A bit string indicating which alarm thresholds are enabled.
1.3.6.1.4.1.38446.1.6.3.1.8Bits {lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3), binarySensorAlarm(4)}read-writecurrent
pduExternalSensorConfigAlarmState
OBJECT-TYPE
User defined alarm state of external sensor
1.3.6.1.4.1.38446.1.6.3.1.9INTEGER {off(0), on(1)}read-writecurrent
pduExternalSensorStatusTable
OBJECT-TYPE
A table of PDU External Sensor status data
1.3.6.1.4.1.38446.1.6.4not-accessiblecurrent
pduExternalSensorStatusEntry
OBJECT-TYPE
Status data from the PDU External Sensor being queried
1.3.6.1.4.1.38446.1.6.4.1not-accessiblecurrent
pduExternalSensorStatusIndex
OBJECT-TYPE
The index of the PDU External Sensor status table entry
1.3.6.1.4.1.38446.1.6.4.1.1Integer32 (0..255)not-accessiblecurrent
pduExternalSensorStatusName
OBJECT-TYPE
The user-defined name for the External Sensor
1.3.6.1.4.1.38446.1.6.4.1.2DisplayStringread-onlycurrent
pduExternalSensorStatusAisle
OBJECT-TYPE
Indicates whether the external sensor is in a hot or cold aisle
1.3.6.1.4.1.38446.1.6.4.1.3INTEGER {hotAisle(1), coldAisle(2)}read-writecurrent
pduExternalSensorStatusCommStatus
OBJECT-TYPE
The communications status of the sensor
1.3.6.1.4.1.38446.1.6.4.1.4INTEGER {notInstalled(1), commsOk(2), commsLost(3)}read-onlycurrent
pduExternalSensorStatusState
OBJECT-TYPE
This OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold.
1.3.6.1.4.1.38446.1.6.4.1.5INTEGER {notPresent(0), alarmed(1), normal(2), belowLowerCritical(3), belowLowerWarning(4), aboveUpperWarning(5), aboveUpperCritical(6)}read-onlycurrent
pduExternalSensorStatusValue
OBJECT-TYPE
Sensor reading in pduExternalSensorConfigUnits value.
1.3.6.1.4.1.38446.1.6.4.1.6Integer32read-onlycurrent
pduExternalSensorStatusTimeStamp
OBJECT-TYPE
The sensor reading timestamp.
1.3.6.1.4.1.38446.1.6.4.1.7DisplayStringread-onlycurrent
pduExternalSensorStatusHighPrecisionValue
OBJECT-TYPE
Temperature sensor reading in tenths of pduExternalSensorConfigUnits value. This OID is applied to temperature sensor only
1.3.6.1.4.1.38446.1.6.4.1.8Integer32read-onlycurrent
pduServerPing
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.7
pduServerPingTableSize
OBJECT-TYPE
The total number of Servers
1.3.6.1.4.1.38446.1.7.1Integer32 (0..255)read-onlycurrent
pduServerPingTable
OBJECT-TYPE
A table of Server Ping data
1.3.6.1.4.1.38446.1.7.2not-accessiblecurrent
pduServerPingEntry
OBJECT-TYPE
Server Ping data from the server being queried. The number of entries equals the value of pduServerPingTableSize.
1.3.6.1.4.1.38446.1.7.2.1not-accessiblecurrent
pduServerPingIndex
OBJECT-TYPE
The index of the PDU pduServerPing table entry
1.3.6.1.4.1.38446.1.7.2.1.1Integer32 (0..255)not-accessiblecurrent
pduServerPingServerIPAddress
OBJECT-TYPE
The IP Address/host name of the server
1.3.6.1.4.1.38446.1.7.2.1.2DisplayStringread-onlycurrent
pduServerPingEnabled
OBJECT-TYPE
Is ping enabled for this server?
1.3.6.1.4.1.38446.1.7.2.1.3INTEGER {false(0), true(1)}read-writecurrent
pduSmartCabinet
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.8
pduUnitSmartCabinetTableSize
OBJECT-TYPE
The total number of Smart Cabinet Configuration
1.3.6.1.4.1.38446.1.8.1Integer32 (0..255)read-onlycurrent
pduUnitSmartCabinetTable
OBJECT-TYPE
A table of Smart Cabinet information
1.3.6.1.4.1.38446.1.8.2not-accessiblecurrent
pduUnitSmartCabinetEntry
OBJECT-TYPE
Information of Smart Cabinet
1.3.6.1.4.1.38446.1.8.2.1not-accessiblecurrent
pduUnitSmartCabinetIndex
OBJECT-TYPE
The index of the PDU Smart Cabinet table entry
1.3.6.1.4.1.38446.1.8.2.1.1Integer32 (1..256)not-accessiblecurrent
pduUnitSmartCabinetCardUserName
OBJECT-TYPE
User name of ID card
1.3.6.1.4.1.38446.1.8.2.1.2DisplayStringread-onlycurrent
pduUnitSmartCabinetCardID
OBJECT-TYPE
Card ID.
1.3.6.1.4.1.38446.1.8.2.1.3Integer32read-onlycurrent
pduUnitSmartCabinetTimestamp
OBJECT-TYPE
Indicates the date and time of information update
1.3.6.1.4.1.38446.1.8.2.1.4DisplayStringread-onlycurrent
pduUnitSmartCabinetDoor
OBJECT-TYPE
Aisle of Smart Cabinet.
1.3.6.1.4.1.38446.1.8.2.1.5INTEGER {HotAisle(1), ColdAisle(2)}read-onlycurrent
pduUnitSmartCabinetControl
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.8.3
pduUnitSmartCabinetControlUserName
OBJECT-TYPE
User name of ID card
1.3.6.1.4.1.38446.1.8.3.1DisplayStringread-writecurrent
pduUnitSmartCabinetControlCardID
OBJECT-TYPE
Card ID.
1.3.6.1.4.1.38446.1.8.3.2Integer32read-writecurrent
pduUnitSmartCabinetControlTimestamp
OBJECT-TYPE
Indicates the date and time of information update
1.3.6.1.4.1.38446.1.8.3.3DisplayStringread-writecurrent
pduUnitSmartCabinetControlDoor
OBJECT-TYPE
Aisle of Smart Cabinet.
1.3.6.1.4.1.38446.1.8.3.4INTEGER {HotAisle(1), ColdAisle(2)}read-writecurrent
pduUnitSmartCabinetCardIDEdit
OBJECT-TYPE
Smart Cabinet edit CardID
1.3.6.1.4.1.38446.1.8.3.5INTEGER {grant(0), remove(1)}read-writecurrent
pduUnitSmartCabinetColdAisleLockState
OBJECT-TYPE
Smart Cabinet ColdAisle lock state
1.3.6.1.4.1.38446.1.8.3.6INTEGER {unlock(0), lock(1), notPresent(2)}read-writecurrent
pduUnitSmartCabinetHotAisleLockState
OBJECT-TYPE
Smart Cabinet HotAisle lock state
1.3.6.1.4.1.38446.1.8.3.7INTEGER {unlock(0), lock(1), notPresent(2)}read-writecurrent
pduTraps
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.9
trapsInfo
OBJECT-IDENTITY
1.3.6.1.4.1.38446.1.9.1
trapsInfoTable
OBJECT-TYPE
A list of Trap Information entries. The number of entries are given by the value of pduUnitTableSize.
1.3.6.1.4.1.38446.1.9.1.1not-accessiblecurrent
trapsInfoEntry
OBJECT-TYPE
An entry containing objects used in traps
1.3.6.1.4.1.38446.1.9.1.1.1not-accessiblecurrent
trapsInfoIndex
OBJECT-TYPE
The index of the traps table entry
1.3.6.1.4.1.38446.1.9.1.1.1.1Integer32 (1..256)not-accessiblecurrent
userName
OBJECT-TYPE
The user currently logged in.
1.3.6.1.4.1.38446.1.9.1.1.1.2DisplayStringread-onlycurrent
userUpdated
OBJECT-TYPE
The user added, deleted, or modified.
1.3.6.1.4.1.38446.1.9.1.1.1.3DisplayStringread-onlycurrent
firmwareVersion
OBJECT-TYPE
The version of Firmware.
1.3.6.1.4.1.38446.1.9.1.1.1.4DisplayStringread-onlycurrent
roleUpdated
OBJECT-TYPE
The role added, deleted, or modified.
1.3.6.1.4.1.38446.1.9.1.1.1.5DisplayStringread-onlycurrent
smtpRecipients
OBJECT-TYPE
Comma separated list of SMTP recipients
1.3.6.1.4.1.38446.1.9.1.1.1.6DisplayStringread-onlycurrent
smtpServer
OBJECT-TYPE
The IP address/host name of the SMTP server
1.3.6.1.4.1.38446.1.9.1.1.1.7DisplayStringread-onlycurrent
pduIndex
OBJECT-TYPE
A unique value for PDU. Its value ranges between 1 and the value of PDU count
1.3.6.1.4.1.38446.1.9.1.2Integer32accessible-for-notifycurrent
externalSensorIndex
OBJECT-TYPE
A unique value for each sensor. Its value ranges between 1 and the value of external sensor count.
1.3.6.1.4.1.38446.1.9.1.3Integer32accessible-for-notifycurrent
serverPing
OBJECT-TYPE
Whether server ping has been enabled or disabled and whether the server is reachable or not reachable
1.3.6.1.4.1.38446.1.9.1.4INTEGER {pingEnable(1), pingDisable(2), serverReachable(3), serverNotReachable(4)}accessible-for-notifycurrent
usbDevice
OBJECT-TYPE
Whether a USB device has been connected or disconnected
1.3.6.1.4.1.38446.1.9.1.5INTEGER {connected(1), disconnected(2)}accessible-for-notifycurrent
errorDescription
OBJECT-TYPE
Description of the Error
1.3.6.1.4.1.38446.1.9.1.6DisplayStringaccessible-for-notifycurrent
daisyChain
OBJECT-TYPE
Whether a daisy chain member has been connected or disconnected
1.3.6.1.4.1.38446.1.9.1.7INTEGER {connected(1), disconnected(2)}accessible-for-notifycurrent
systemCommunication
OBJECT-TYPE
Whether the Network management card has lost contact with daisy a chain member.
1.3.6.1.4.1.38446.1.9.1.8INTEGER {ok(1), lost(2)}accessible-for-notifycurrent
esp
OBJECT-IDENTITY
1.3.6.1.4.1.38446.2
espNamePlate
OBJECT-IDENTITY
1.3.6.1.4.1.38446.2.1
espNamePlateTable
OBJECT-TYPE
A table of es PDU nameplate data
1.3.6.1.4.1.38446.2.1.2not-accessiblecurrent
espNamePlateEntry
OBJECT-TYPE
Nameplate data from the PDU being queried. The numbers of entries equals the value of espNamePlateTableSize.
1.3.6.1.4.1.38446.2.1.2.1not-accessiblecurrent
espNamePlateIndex
OBJECT-TYPE
The index of the es PDU nameplate table entry
1.3.6.1.4.1.38446.2.1.2.1.1Integer32 (1..256)not-accessiblecurrent
espNamePlateName
OBJECT-TYPE
A user-defined string identifying the es PDU
1.3.6.1.4.1.38446.2.1.2.1.2DisplayStringread-onlycurrent
espNamePlateLocation
OBJECT-TYPE
A user-defined string identifying the location of PDU
1.3.6.1.4.1.38446.2.1.2.1.3DisplayStringread-onlycurrent
espNamePlateInetAddressType
OBJECT-TYPE
The type of address format
1.3.6.1.4.1.38446.2.1.2.1.4InetAddressTyperead-onlycurrent
espNamePlateIPAddress
OBJECT-TYPE
The current IP address. A value of 0.0.0.0 indicates an error or an unset option
1.3.6.1.4.1.38446.2.1.2.1.5InetAddressread-onlycurrent
espNamePlateInetNetMask
OBJECT-TYPE
The current netmask. A value of 0.0.0.0 indiates an error or an unset option
1.3.6.1.4.1.38446.2.1.2.1.6InetAddressread-onlycurrent
espNamePlateInetGateway
OBJECT-TYPE
The current gateway. A value of 0.0.0.0 indicates an error or an unset option
1.3.6.1.4.1.38446.2.1.2.1.7InetAddressread-onlycurrent
espNamePlateMACAddress
OBJECT-TYPE
The assigned MAC address for the PDU
1.3.6.1.4.1.38446.2.1.2.1.8MacAddressread-onlycurrent
espNamePlateUTCTimeOffset
OBJECT-TYPE
The difference in hours and minutes from Coordinated Universal Time(UTC) for the time used in a particular time zone
1.3.6.1.4.1.38446.2.1.2.1.9DisplayStringread-onlycurrent
espNamePlateModelNumber
OBJECT-TYPE
The PDU model number
1.3.6.1.4.1.38446.2.1.2.1.10DisplayStringread-onlycurrent
espNamePlateSerialNumber
OBJECT-TYPE
The PDU serial number
1.3.6.1.4.1.38446.2.1.2.1.11DisplayStringread-onlycurrent
espNamePlateDateofManufacture
OBJECT-TYPE
The date the PDU was manufactured in mm/dd/yyyy format
1.3.6.1.4.1.38446.2.1.2.1.12DisplayStringread-onlycurrent
espNamePlateFirmwareVersion
OBJECT-TYPE
The PDU firmware version
1.3.6.1.4.1.38446.2.1.2.1.13DisplayStringread-onlycurrent
espNamePlateFirmwareVersionTimeStamp
OBJECT-TYPE
Timestamp of when the PDU firmware was last updated
1.3.6.1.4.1.38446.2.1.2.1.14DisplayStringread-onlycurrent
espNamePlateType
OBJECT-TYPE
The type of Unit, PDU or Inline Meter
1.3.6.1.4.1.38446.2.1.2.1.15INTEGER {pdu(0), inlineMeter(1)}read-onlycurrent
espUnit
OBJECT-IDENTITY
1.3.6.1.4.1.38446.2.2
espUnitConfigTable
OBJECT-TYPE
A table of PDU configuration data
1.3.6.1.4.1.38446.2.2.2not-accessiblecurrent
espUnitConfigEntry
OBJECT-TYPE
Configuration data from the PDU being queried. The number of entries equals the value of espUnitTableSize
1.3.6.1.4.1.38446.2.2.2.1not-accessiblecurrent
espUnitConfigIndex
OBJECT-TYPE
The index of the PDU Unit Config Entry
1.3.6.1.4.1.38446.2.2.2.1.1Integer32 (1..256)not-accessiblecurrent
espUnitConfigName
OBJECT-TYPE
A user-defined string identifying the PDU
1.3.6.1.4.1.38446.2.2.2.1.2DisplayStringread-writecurrent
espUnitConfigLocation
OBJECT-TYPE
A user-defined string identifying the location of the PDU
1.3.6.1.4.1.38446.2.2.2.1.3DisplayStringread-writecurrent
espUnitConfigEnergyReset
OBJECT-TYPE
Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
1.3.6.1.4.1.38446.2.2.2.1.15INTEGER {noOperation(1), reset(2), notSupported(3)}read-writecurrent
espUnitConfigResetNetworkManagementCard
OBJECT-TYPE
Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC.
1.3.6.1.4.1.38446.2.2.2.1.20INTEGER {noOperation(0), reset(1)}read-writecurrent
espUnitPropertiesTable
OBJECT-TYPE
A table of PDU properties
1.3.6.1.4.1.38446.2.2.3not-accessiblecurrent
espUnitPropertiesEntry
OBJECT-TYPE
A unit properties entry containing objects for a particular unit.
1.3.6.1.4.1.38446.2.2.3.1not-accessiblecurrent
espUnitPropertiesIndex
OBJECT-TYPE
The index of the PDU properties table entry
1.3.6.1.4.1.38446.2.2.3.1.1Integer32 (1..256)not-accessiblecurrent
espUnitPropertiesName
OBJECT-TYPE
A user-defined string identifying the PDU
1.3.6.1.4.1.38446.2.2.3.1.2DisplayStringread-onlycurrent
espUnitPropertiesOutletCount
OBJECT-TYPE
The total number of outlets on the PDU
1.3.6.1.4.1.38446.2.2.3.1.3Integer32 (1..256)read-onlycurrent
espUnitPropertiesSwitchedOutletCount
OBJECT-TYPE
The total number of switched outlets on the PDU
1.3.6.1.4.1.38446.2.2.3.1.4Integer32 (1..256)read-onlycurrent
espUnitPropertiesMeteredOutletCount
OBJECT-TYPE
The total number of metered outlets on the PDU
1.3.6.1.4.1.38446.2.2.3.1.5Integer32 (1..256)read-onlycurrent
espUnitPropertiesInputPhaseCount
OBJECT-TYPE
The total number of phases on the PDU
1.3.6.1.4.1.38446.2.2.3.1.6Integer32 (1..256)read-onlycurrent
espUnitPropertiesCircuitBreakerCount
OBJECT-TYPE
The total number of circuit breaker on the PDU
1.3.6.1.4.1.38446.2.2.3.1.7Integer32 (0..255)read-onlycurrent
espUnitPropertiesMaxExternalSensorCount
OBJECT-TYPE
The maximum number of external sensors that can be connected to the PDU
1.3.6.1.4.1.38446.2.2.3.1.8Integer32 (0..255)read-onlycurrent
espUnitPropertiesConnExternalSensorCount
OBJECT-TYPE
The current number of external sensors connected to the PDU
1.3.6.1.4.1.38446.2.2.3.1.9Integer32 (0..255)read-onlycurrent
espUnitPropertiesRatedVoltage
OBJECT-TYPE
The PDU voltage rating in Volts
1.3.6.1.4.1.38446.2.2.3.1.10DisplayStringread-onlycurrent
espUnitPropertiesRatedMaxCurrent
OBJECT-TYPE
The PDU current rating in Amps
1.3.6.1.4.1.38446.2.2.3.1.11DisplayStringread-onlycurrent
espUnitPropertiesRatedFrequency
OBJECT-TYPE
The PDU frequency rating in Hz
1.3.6.1.4.1.38446.2.2.3.1.12DisplayStringread-onlycurrent
espUnitPropertiesRatedPower
OBJECT-TYPE
The PDU VA (VoltAmps) rating.
1.3.6.1.4.1.38446.2.2.3.1.13DisplayStringread-onlycurrent
espUnitStatusTable
OBJECT-TYPE
A table of PDU status information
1.3.6.1.4.1.38446.2.2.4not-accessiblecurrent
espUnitStatusEntry
OBJECT-TYPE
Status information from the PDU being queried
1.3.6.1.4.1.38446.2.2.4.1not-accessiblecurrent
espUnitStatusIndex
OBJECT-TYPE
The index of the PDU status table entry
1.3.6.1.4.1.38446.2.2.4.1.1Integer32 (1..256)not-accessiblecurrent
espUnitStatusName
OBJECT-TYPE
A user-defined string identifying the PDU
1.3.6.1.4.1.38446.2.2.4.1.2DisplayStringread-onlycurrent
espUnitStatusLoadState
OBJECT-TYPE
Returns the present load status of the PDU based on Active Power.
1.3.6.1.4.1.38446.2.2.4.1.3INTEGER {upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)}read-onlycurrent
espUnitStatusActivePower
OBJECT-TYPE
Returns power consumption, in Watts(W), of the PDU being queried.
1.3.6.1.4.1.38446.2.2.4.1.4Integer32read-onlycurrent
espUnitStatusApparentPower
OBJECT-TYPE
Returns power consumption, in Volt-Amps(VA) of the PDU load being queried.
1.3.6.1.4.1.38446.2.2.4.1.5Integer32read-onlycurrent
espUnitStatusEnergy
OBJECT-TYPE
Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime.
1.3.6.1.4.1.38446.2.2.4.1.9Integer32read-onlycurrent
espUnitStatusResettableEnergy
OBJECT-TYPE
A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).
1.3.6.1.4.1.38446.2.2.4.1.10Integer32read-onlycurrent
espUnitStatusEnergyStartTime
OBJECT-TYPE
Indicates the date and time of the last device energy meter reset
1.3.6.1.4.1.38446.2.2.4.1.11DisplayStringread-onlycurrent
espInputPhase
OBJECT-IDENTITY
1.3.6.1.4.1.38446.2.3
espInputPhaseConfigTable
OBJECT-TYPE
A table of PDU Input Phase configuration data
1.3.6.1.4.1.38446.2.3.2not-accessiblecurrent
espInputPhaseConfigEntry
OBJECT-TYPE
An input phase entry containing objects for a particular input phase.
1.3.6.1.4.1.38446.2.3.2.1not-accessiblecurrent
espInputPhaseConfigIndex
OBJECT-TYPE
The index of the PDU Input Phase configuration table entry
1.3.6.1.4.1.38446.2.3.2.1.1Integer32 (1..256)not-accessiblecurrent
espInputPhaseConfigCount
OBJECT-TYPE
The total number of Input Phases
1.3.6.1.4.1.38446.2.3.2.1.2Integer32 (1..256)read-onlycurrent
espInputPhaseStatusTable
OBJECT-TYPE
A table of PDU Input Phase status data
1.3.6.1.4.1.38446.2.3.4not-accessiblecurrent
espInputPhaseStatusEntry
OBJECT-TYPE
An input phase status entry containing objects for a particular input phase.
1.3.6.1.4.1.38446.2.3.4.1not-accessiblecurrent
espInputPhaseStatusIndex
OBJECT-TYPE
The index of the PDU Input Phase status entry
1.3.6.1.4.1.38446.2.3.4.1.1Integer32 (1..256)not-accessiblecurrent
espInputPhaseStatusCount
OBJECT-TYPE
The numeric Input Phase ID
1.3.6.1.4.1.38446.2.3.4.1.2Integer32 (1..256)read-onlycurrent
espInputPhaseStatusCurrentState
OBJECT-TYPE
Indicates the present current status of the PDU Input Phase being queried
1.3.6.1.4.1.38446.2.3.4.1.3INTEGER {upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)}read-onlycurrent
espInputPhaseStatusVoltageState
OBJECT-TYPE
Indicates the present voltage status of the PDU Input Phase being queried
1.3.6.1.4.1.38446.2.3.4.1.4INTEGER {upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)}read-onlycurrent
espInputPhaseStatusCurrent
OBJECT-TYPE
Returns the current draw, in hundredths of Amps(A), of the load on the PDU Input Phase being queried.
1.3.6.1.4.1.38446.2.3.4.1.5Integer32read-onlycurrent
espInputPhaseStatusVoltage
OBJECT-TYPE
Returns the voltage, in Volts(V), of the PDU Input Phase being queried.
1.3.6.1.4.1.38446.2.3.4.1.6Integer32read-onlycurrent
espInputPhaseStatusActivePower
OBJECT-TYPE
Returns power consumption, in Watts(W), consumed on the PDU Input Phase being queried.
1.3.6.1.4.1.38446.2.3.4.1.7Integer32read-onlycurrent
espInputPhaseStatusApparentPower
OBJECT-TYPE
Returns power consumption, in Volt-Amps(VA), of the PDU Input Phase being queried.
1.3.6.1.4.1.38446.2.3.4.1.8Integer32read-onlycurrent
espInputPhaseStatusPowerFactor
OBJECT-TYPE
Returns the ratio of active to apparent power of the PDU Input Phase being queried.
1.3.6.1.4.1.38446.2.3.4.1.9Integer32read-onlycurrent
espCircuitBreaker
OBJECT-IDENTITY
1.3.6.1.4.1.38446.2.4
espCircuitBreakerConfigTable
OBJECT-TYPE
A table of PDU Circuit Breaker configuration data
1.3.6.1.4.1.38446.2.4.2not-accessiblecurrent
espCircuitBreakerConfigEntry
OBJECT-TYPE
A circuit breaker configuration entry containing objects for a particular circuit breaker.
1.3.6.1.4.1.38446.2.4.2.1not-accessiblecurrent
espCircuitBreakerConfigIndex
OBJECT-TYPE
The index of the PDU Circuit Breaker configuration table entry
1.3.6.1.4.1.38446.2.4.2.1.1Integer32 (1..256)not-accessiblecurrent
espCircuitBreakerConfigCount
OBJECT-TYPE
The number of circuit breakers on the PDU
1.3.6.1.4.1.38446.2.4.2.1.2Integer32 (0..255)read-onlycurrent
espCircuitBreakerName
OBJECT-TYPE
The label of the circuit breaker
1.3.6.1.4.1.38446.2.4.2.1.3DisplayStringread-onlycurrent
espCircuitBreakerPropertiesTable
OBJECT-TYPE
A table of PDU circuit breaker properties
1.3.6.1.4.1.38446.2.4.3not-accessiblecurrent
espCircuitBreakerPropertiesEntry
OBJECT-TYPE
A circuit breaker properties entry containing objects for a particular circuit breaker.
1.3.6.1.4.1.38446.2.4.3.1not-accessiblecurrent
espCircuitBreakerPropertiesIndex
OBJECT-TYPE
The index of the PDU Circuit Breaker properties table entry
1.3.6.1.4.1.38446.2.4.3.1.1Integer32 (1..256)not-accessiblecurrent
espCircuitBreakerPropertiesCount
OBJECT-TYPE
The number of Circuit Breakers
1.3.6.1.4.1.38446.2.4.3.1.2Integer32 (0..255)read-onlycurrent
espCircuitBreakerPropertiesInputLayout
OBJECT-TYPE
This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to circuit breaker are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to circuit breaker are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to circuit breaker are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to circuit breaker are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to circuit breaker are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to circuit breaker are connected from Phase 3 to Phase1.
1.3.6.1.4.1.38446.2.4.3.1.3INTEGER {seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6)}read-onlycurrent
espCircuitBreakerStatusTable
OBJECT-TYPE
A table of PDU circuit breaker status data
1.3.6.1.4.1.38446.2.4.4not-accessiblecurrent
espCircuitBreakerStatusEntry
OBJECT-TYPE
A circuit breaker status entry containing objects for a particular circuit breaker.
1.3.6.1.4.1.38446.2.4.4.1not-accessiblecurrent
espCircuitBreakerStatusIndex
OBJECT-TYPE
The index of the PDU Circuit Breaker status table entry
1.3.6.1.4.1.38446.2.4.4.1.1Integer32 (1..256)not-accessiblecurrent
espCircuitBreakerStatusCount
OBJECT-TYPE
The number of Circuit Breakers
1.3.6.1.4.1.38446.2.4.4.1.2Integer32 (0..255)read-onlycurrent
espCircuitBreakerLabel
OBJECT-TYPE
The label on the PDU identifying the circuit breaker
1.3.6.1.4.1.38446.2.4.4.1.3DisplayStringread-onlycurrent
espCircuitBreakerStatusLoadState
OBJECT-TYPE
Indicates the present load status of the PDU Circuit Breaker being queried
1.3.6.1.4.1.38446.2.4.4.1.4INTEGER {upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5), off(6)}read-onlycurrent
espCircuitBreakerStatusCurrent
OBJECT-TYPE
Returns the current draw, in hundredths of Amps(A), of the load on the PDU Circuit Breaker being queried.
1.3.6.1.4.1.38446.2.4.4.1.5Integer32read-onlycurrent
espExternalSensor
OBJECT-IDENTITY
1.3.6.1.4.1.38446.2.6
espExternalSensorNamePlateTable
OBJECT-TYPE
A table of PDU ExternalSensorNamePlate data
1.3.6.1.4.1.38446.2.6.2not-accessiblecurrent
espExternalSensorNamePlateEntry
OBJECT-TYPE
External Sensor Name Plate data from the external sensor being queried. The number of entries equals the value of espExternalSensorNamePlateTableSize.
1.3.6.1.4.1.38446.2.6.2.1not-accessiblecurrent
espExternalSensorNamePlateIndex
OBJECT-TYPE
The index of the PDU External Sensor status table entry
1.3.6.1.4.1.38446.2.6.2.1.1Integer32 (0..255)not-accessiblecurrent
espExternalSensorNamePlateName
OBJECT-TYPE
A user-defined string identifying the external sensor
1.3.6.1.4.1.38446.2.6.2.1.2DisplayStringread-onlycurrent
espExternalSensorNamePlateSerialNumber
OBJECT-TYPE
The serial number of the external sensor being queried
1.3.6.1.4.1.38446.2.6.2.1.5DisplayStringread-onlycurrent
espExternalSensorNamePlateType
OBJECT-TYPE
The type of external sensor.
1.3.6.1.4.1.38446.2.6.2.1.6INTEGER {temperature(1), humidity(2), doorSwitch(3), dryContact(4), spotFluid(5), ropeFluid(6), smoke(7), beacon(8)}read-onlycurrent
espExternalSensorNamePlateUnits
OBJECT-TYPE
The base units the external sensor is measured in. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
1.3.6.1.4.1.38446.2.6.2.1.7INTEGER {logic(0), degreeC(1), degreeF(2), percent(3)}read-onlycurrent
espExternalSensorConfigTable
OBJECT-TYPE
A table of PDU External Sensor configuration data
1.3.6.1.4.1.38446.2.6.3not-accessiblecurrent
espExternalSensorConfigEntry
OBJECT-TYPE
Configuration data from the PDU External Sensor being queried
1.3.6.1.4.1.38446.2.6.3.1not-accessiblecurrent
espExternalSensorConfigIndex
OBJECT-TYPE
The index of the PDU External Sensor configuration table entry
1.3.6.1.4.1.38446.2.6.3.1.1Integer32 (0..255)not-accessiblecurrent
espExternalSensorConfigAlarmState
OBJECT-TYPE
User defined alarm state of external sensor
1.3.6.1.4.1.38446.2.6.3.1.9INTEGER {off(0), on(1)}read-writecurrent
espExternalSensorStatusTable
OBJECT-TYPE
A table of PDU External Sensor status data
1.3.6.1.4.1.38446.2.6.4not-accessiblecurrent
espExternalSensorStatusEntry
OBJECT-TYPE
Status data from the PDU External Sensor being queried
1.3.6.1.4.1.38446.2.6.4.1not-accessiblecurrent
espExternalSensorStatusIndex
OBJECT-TYPE
The index of the PDU External Sensor status table entry
1.3.6.1.4.1.38446.2.6.4.1.1Integer32 (0..255)not-accessiblecurrent
espExternalSensorStatusName
OBJECT-TYPE
The user-defined name for the External Sensor
1.3.6.1.4.1.38446.2.6.4.1.2DisplayStringread-onlycurrent
espExternalSensorStatusAisle
OBJECT-TYPE
Indicates whether the external sensor is in a hot or cold aisle
1.3.6.1.4.1.38446.2.6.4.1.3INTEGER {hotAisle(1), coldAisle(2)}read-writecurrent
espExternalSensorStatusCommStatus
OBJECT-TYPE
The communications status of the sensor
1.3.6.1.4.1.38446.2.6.4.1.4INTEGER {notInstalled(1), commsOk(2), commsLost(3)}read-onlycurrent
espExternalSensorStatusState
OBJECT-TYPE
This OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold.
1.3.6.1.4.1.38446.2.6.4.1.5INTEGER {notPresent(0), alarmed(1), normal(2), belowLowerCritical(3), belowLowerWarning(4), aboveUpperWarning(5), aboveUpperCritical(6)}read-onlycurrent
espExternalSensorStatusValue
OBJECT-TYPE
Sensor reading in espExternalSensorConfigUnits value.
1.3.6.1.4.1.38446.2.6.4.1.6Integer32read-onlycurrent
espExternalSensorStatusHighPrecisionValue
OBJECT-TYPE
Temperature sensor reading in tenths of espExternalSensorConfigUnits value. This OID is applied to temperature sensor only
1.3.6.1.4.1.38446.2.6.4.1.8Integer32read-onlycurrent
espTraps
OBJECT-IDENTITY
1.3.6.1.4.1.38446.2.9
espTrapsInfoIndex
OBJECT-TYPE
The index of the traps table entry
1.3.6.1.4.1.38446.2.9.1Integer32 (1..256)not-accessiblecurrent
espUserName
OBJECT-TYPE
The user currently logged in.
1.3.6.1.4.1.38446.2.9.2DisplayStringread-onlycurrent
espFirmwareVersion
OBJECT-TYPE
The version of Firmware.
1.3.6.1.4.1.38446.2.9.4DisplayStringread-onlycurrent
espIndex
OBJECT-TYPE
A unique value for PDU. Its value ranges between 1 and the value of PDU count
1.3.6.1.4.1.38446.2.9.5Integer32accessible-for-notifycurrent
espExternalSensorIndex
OBJECT-TYPE
A unique value for each sensor. Its value ranges between 1 and the value of external sensor count.
1.3.6.1.4.1.38446.2.9.6Integer32accessible-for-notifycurrent
espErrorDescription
OBJECT-TYPE
Description of the Error
1.3.6.1.4.1.38446.2.9.7DisplayStringaccessible-for-notifycurrent

Notifications

NameOIDStatus
networkCardStart
NOTIFICATION-TYPE
The network card has started
1.3.6.1.4.1.38446.1.9.2current
networkCardReset
NOTIFICATION-TYPE
The network card was reset via the web or command line interface.
1.3.6.1.4.1.38446.1.9.3current
userLogin
NOTIFICATION-TYPE
A user logged in
1.3.6.1.4.1.38446.1.9.4current
userLogoff
NOTIFICATION-TYPE
A user logged off
1.3.6.1.4.1.38446.1.9.5current
userAuthenticationFailed
NOTIFICATION-TYPE
A user authentication attempt failed.
1.3.6.1.4.1.38446.1.9.6current
userSessionTimeout
NOTIFICATION-TYPE
A user session timed out
1.3.6.1.4.1.38446.1.9.7current
userAdded
NOTIFICATION-TYPE
A user account was added to system.
1.3.6.1.4.1.38446.1.9.8current
userModified
NOTIFICATION-TYPE
A user account was modified.
1.3.6.1.4.1.38446.1.9.9current
userDeleted
NOTIFICATION-TYPE
A user account was deleted.
1.3.6.1.4.1.38446.1.9.10current
roleAdded
NOTIFICATION-TYPE
A user role was added.
1.3.6.1.4.1.38446.1.9.11current
roleModified
NOTIFICATION-TYPE
A user role was modified.
1.3.6.1.4.1.38446.1.9.12current
roleDeleted
NOTIFICATION-TYPE
A user role was deleted.
1.3.6.1.4.1.38446.1.9.13current
firmwareUpdateStarted
NOTIFICATION-TYPE
A firmware update has started.
1.3.6.1.4.1.38446.1.9.14current
firmwareUpdateCompleted
NOTIFICATION-TYPE
The firmware update has completed.
1.3.6.1.4.1.38446.1.9.15current
userBlocked
NOTIFICATION-TYPE
A user is blocked.
1.3.6.1.4.1.38446.1.9.16current
outletControl
NOTIFICATION-TYPE
Outlet control operation applied.
1.3.6.1.4.1.38446.1.9.17current
userPasswordChange
NOTIFICATION-TYPE
A user password was changed.
1.3.6.1.4.1.38446.1.9.18current
passwordSettingsChange
NOTIFICATION-TYPE
One or more password policy settings were changed.
1.3.6.1.4.1.38446.1.9.19current
logFileCleared
NOTIFICATION-TYPE
The log file has been cleared.
1.3.6.1.4.1.38446.1.9.21current
pduConfigurationFileImported
NOTIFICATION-TYPE
PDU configuration file was imported.
1.3.6.1.4.1.38446.1.9.22current
pduConfigurationFileExported
NOTIFICATION-TYPE
PDU configuration file was exported
1.3.6.1.4.1.38446.1.9.23current
pduUnitActivePowerStateChange
NOTIFICATION-TYPE
PDU unit active power state changes.
1.3.6.1.4.1.38446.1.9.24current
pduInputphaseVoltageStateChange
NOTIFICATION-TYPE
PDU input phase voltage state changes.
1.3.6.1.4.1.38446.1.9.25current
pduInputphaseCurrentStateChange
NOTIFICATION-TYPE
PDU input phase Current state changes.
1.3.6.1.4.1.38446.1.9.26current
pduCircuitBreakerCurrentStateChange
NOTIFICATION-TYPE
PDU Circuit Breaker Current state changes.
1.3.6.1.4.1.38446.1.9.27current
pduOutletActivePowerStateChange
NOTIFICATION-TYPE
PDU Metered Outlet Active Power state changes.
1.3.6.1.4.1.38446.1.9.28current
pduExternalSensorStateChange
NOTIFICATION-TYPE
PDU External Sensor state changes.
1.3.6.1.4.1.38446.1.9.29current
smtpTransmissionFailure
NOTIFICATION-TYPE
SMTP message transmission failed.
1.3.6.1.4.1.38446.1.9.30current
ldapError
NOTIFICATION-TYPE
A LDAP error occurred
1.3.6.1.4.1.38446.1.9.31current
firmwareUpdateFailed
NOTIFICATION-TYPE
A firmware update has failed.
1.3.6.1.4.1.38446.1.9.32current
serverPingState
NOTIFICATION-TYPE
The Ping feature has been enabled.
1.3.6.1.4.1.38446.1.9.33current
bootloaderState
NOTIFICATION-TYPE
Enter into Bootloader mode
1.3.6.1.4.1.38446.1.9.34current
daisyChainState
NOTIFICATION-TYPE
A daisy chain member has been connected or disconnected.
1.3.6.1.4.1.38446.1.9.35current
systemInternalCommunicationLost
NOTIFICATION-TYPE
Network management card has lost contaction with internal boards.
1.3.6.1.4.1.38446.1.9.36current
SmartCabinetLockUnlocked
NOTIFICATION-TYPE
The Cabinet lock is unlocked.
1.3.6.1.4.1.38446.1.9.37current
SmartCabinetLockLocked
NOTIFICATION-TYPE
The Cabinet lock is locked
1.3.6.1.4.1.38446.1.9.38current
SmartCabinetSwapCard
NOTIFICATION-TYPE
Card is swapped
1.3.6.1.4.1.38446.1.9.39current
SmartCabinetLockerLockDoorOpen
NOTIFICATION-TYPE
Locker locked but door open
1.3.6.1.4.1.38446.1.9.40current
SmartCabinetLockerUnlockDoorClose
NOTIFICATION-TYPE
Locker unlocked but door close
1.3.6.1.4.1.38446.1.9.41current
systemReboot
NOTIFICATION-TYPE
System has rebooted
1.3.6.1.4.1.38446.1.9.50current
espNetworkCardStart
NOTIFICATION-TYPE
The network card has started
1.3.6.1.4.1.38446.2.9.8current
espNetworkCardReset
NOTIFICATION-TYPE
The network card was reset via the web or command line interface.
1.3.6.1.4.1.38446.2.9.9current
espFirmwareUpdateCompleted
NOTIFICATION-TYPE
The firmware update has completed.
1.3.6.1.4.1.38446.2.9.10current
espUserPasswordChange
NOTIFICATION-TYPE
A user password was changed.
1.3.6.1.4.1.38446.2.9.11current
espLogFileCleared
NOTIFICATION-TYPE
The log file has been cleared.
1.3.6.1.4.1.38446.2.9.12current
espConfigurationFileExported
NOTIFICATION-TYPE
PDU configuration file was exported
1.3.6.1.4.1.38446.2.9.13current
espUnitActivePowerStateChange
NOTIFICATION-TYPE
PDU unit active power state changes.
1.3.6.1.4.1.38446.2.9.14current
espInputphaseVoltageStateChange
NOTIFICATION-TYPE
PDU input phase voltage state changes.
1.3.6.1.4.1.38446.2.9.15current
espInputphaseCurrentStateChange
NOTIFICATION-TYPE
PDU input phase Current state changes.
1.3.6.1.4.1.38446.2.9.16current
espCircuitBreakerCurrentStateChange
NOTIFICATION-TYPE
PDU Circuit Breaker Current state changes.
1.3.6.1.4.1.38446.2.9.17current
espExternalSensorStateChange
NOTIFICATION-TYPE
PDU External Sensor state changes.
1.3.6.1.4.1.38446.2.9.18current
espConfigurationFileImported
NOTIFICATION-TYPE
PDU configuration file was imported
1.3.6.1.4.1.38446.2.9.19current
espNetworkUp
NOTIFICATION-TYPE
PDU Network is up
1.3.6.1.4.1.38446.2.9.20current