MIBs Depot

EES-POWER-MIB

Registered at
1.3.6.1.4.1.6302
Last updated
2015-04-10 08:57
Organization
Emerson Energy Systems (EES)
Namespace
emerson
Source file
EES-POWER-MIB
Digest
sha256:0a2648473adc77541851c7a79cfff53cbdb7c60da7f7ff48a3f6defb2a596f48

Description

Emerson Energy Systems (EES) Power MIB, revision D.

Contact

Emerson Energy Systems 141 82 Stockholm Sweden

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMICounter32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDateAndTime, DisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

EES-POWER-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Textual conventions

NameOIDSyntaxAccessStatus
Status
TEXTUAL-CONVENTION
This integer value represents the operational or administrative status of the system. Also used as alarm severity. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) warning - OA, lowest level of 'abnormal' status (4) minor - A3 (5) major - MA (6) critical - CA, highest level of 'abnormal' status Administrative values: (7) unmanaged (8) restricted (9) testing (10) disabled
current
StatusChange
TEXTUAL-CONVENTION
Indicates 'activated' (1) or 'deactivated' (2) alarm events.
current

Objects

NameOIDSyntaxAccessStatus
ees
OBJECT-IDENTITY
1.3.6.1.4.1.6302
pysmi_global
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2
ident
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.1
identManufacturer
OBJECT-TYPE
The name of the equipment manufacturer.
1.3.6.1.4.1.6302.2.1.1.1DisplayStringread-onlycurrent
identModel
OBJECT-TYPE
The manufacturers model designation of the power system.
1.3.6.1.4.1.6302.2.1.1.2DisplayStringread-onlycurrent
identControllerFirmwareVersion
OBJECT-TYPE
The firmware (software) version of the controller.
1.3.6.1.4.1.6302.2.1.1.3DisplayStringread-onlycurrent
identName
OBJECT-TYPE
The name of the power plant. This object should be set by the administrator.
1.3.6.1.4.1.6302.2.1.1.4DisplayStringread-writecurrent
identSNMPCfgVer
OBJECT-TYPE
The snmp cfg version
1.3.6.1.4.1.6302.2.1.1.5DisplayStringread-onlycurrent
identControllerSerialNumber
OBJECT-TYPE
The serial number of this controller
1.3.6.1.4.1.6302.2.1.1.6DisplayStringread-onlycurrent
system
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.2
systemStatus
OBJECT-TYPE
Status of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) warning - OA, lowest level of 'abnormal' status (4) minor - A3 (5) major - MA (6) critical - CA, highest level of 'abnormal' status (7) unmanaged (8) restricted (9) testing (10) disabled
1.3.6.1.4.1.6302.2.1.2.1Statusread-onlycurrent
systemVoltage
OBJECT-TYPE
System voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.2Integer32read-onlycurrent
systemCurrent
OBJECT-TYPE
System current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.3Integer32read-onlycurrent
systemUsedCapacity
OBJECT-TYPE
Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.4Integer32read-onlycurrent
psBattery
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.2.5
psBatteryVoltage
OBJECT-TYPE
Battery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.1Integer32read-onlycurrent
psTotalBatteryCurrent
OBJECT-TYPE
Battery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.2Integer32read-onlycurrent
psBatteryCapacity
OBJECT-TYPE
Calculated capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.3Integer32read-onlycurrent
psBatteryNominalCapacity
OBJECT-TYPE
nominal installed capacity, stored as mAh. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.4Integer32read-onlycurrent
psBatteryTable
OBJECT-TYPE
Battery Table.
1.3.6.1.4.1.6302.2.1.2.5.5not-accessiblecurrent
psBatteryEntry
OBJECT-TYPE
Battery Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.5.5.1not-accessiblecurrent
psBatteryIndex
OBJECT-TYPE
Automatically generated index object.
1.3.6.1.4.1.6302.2.1.2.5.5.1.1Integer32 (1..16777215)read-onlycurrent
psBatteryCurrent
OBJECT-TYPE
Battery current in Amps.
1.3.6.1.4.1.6302.2.1.2.5.5.1.2Integer32read-onlycurrent
psBatteryName
OBJECT-TYPE
Battery shunt name.
1.3.6.1.4.1.6302.2.1.2.5.5.1.3DisplayStringread-onlycurrent
psInput
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.2.6
psInputLineAVoltage
OBJECT-TYPE
The AC line A voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.1Integer32read-onlycurrent
psInputLineBVoltage
OBJECT-TYPE
The AC line B voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.2Integer32read-onlycurrent
psInputLineCVoltage
OBJECT-TYPE
The AC line C voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.3Integer32read-onlycurrent
psTemperature
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.2.7
psTemperature1
OBJECT-TYPE
The first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.7.1Integer32read-onlycurrent
psTemperature2
OBJECT-TYPE
The second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value..
1.3.6.1.4.1.6302.2.1.2.7.2Integer32read-onlycurrent
psTemperatureTable
OBJECT-TYPE
Temperature Measurement Table.
1.3.6.1.4.1.6302.2.1.2.7.3not-accessiblecurrent
psTemperatureEntry
OBJECT-TYPE
Temperature Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.7.3.1not-accessiblecurrent
psTemperatureIndex
OBJECT-TYPE
Temperature Probe Number
1.3.6.1.4.1.6302.2.1.2.7.3.1.1Integer32 (1..71)read-onlycurrent
psTemperatureMeasurement
OBJECT-TYPE
Temperature Value In Centigrade.
1.3.6.1.4.1.6302.2.1.2.7.3.1.2Integer32read-onlycurrent
psTemperatureName
OBJECT-TYPE
Configured Temperature Probe Name.
1.3.6.1.4.1.6302.2.1.2.7.3.1.3DisplayStringread-onlycurrent
psTemperatureType
OBJECT-TYPE
Temperature Probe Type
1.3.6.1.4.1.6302.2.1.2.7.3.1.4INTEGER {none(0), ambient(1), battery(2)}read-onlycurrent
psTemperatureAlarmStatus
OBJECT-TYPE
Temperature Probe Alarm Status
1.3.6.1.4.1.6302.2.1.2.7.3.1.5INTEGER {high(0), low(1), fail(2), none(3)}read-onlycurrent
psStatusCommunication
OBJECT-TYPE
The status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.
1.3.6.1.4.1.6302.2.1.2.8INTEGER {unknown(1), normal(2), interrupt(3)}read-onlycurrent
psStatusBatteryMode
OBJECT-TYPE
The status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoostCharging(9), AutoBoostCharging(10), CyclicBoostCharging(11), MasterBoostCharging(12), MasterBateryTesting(13).
1.3.6.1.4.1.6302.2.1.2.9INTEGER {unknown(1), floatCharging(2), shortTest(3), bcForTest(4), manualTesting(5), planTesting(6), acFailTesting(7), acFail(8), manualBC(9), autoBC(10), cyclicBC(11), masterBC(12), masterBT(13)}read-onlycurrent
psSMNumber
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.2.10
psSMACNumber
OBJECT-TYPE
The number of SM AC module.
1.3.6.1.4.1.6302.2.1.2.10.1Integer32read-onlycurrent
psSMBATNumber
OBJECT-TYPE
The number of SM BAT module.
1.3.6.1.4.1.6302.2.1.2.10.2Integer32read-onlycurrent
psSMIONumber
OBJECT-TYPE
The number of SM IO module.
1.3.6.1.4.1.6302.2.1.2.10.3Integer32read-onlycurrent
psRectifier
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.2.11
numberOfInstalledRectifiers
OBJECT-TYPE
number of rectifiers, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.1Integer32read-onlycurrent
numberOfRectifiersCommunicating
OBJECT-TYPE
number of rectifiers communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.2Integer32read-onlycurrent
rectifiersUsedCapacity
OBJECT-TYPE
Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.3Integer32read-onlycurrent
psRectifierTable
OBJECT-TYPE
Table holding information about indivual rectifiers.
1.3.6.1.4.1.6302.2.1.2.11.4not-accessiblecurrent
psRectifierEntry
OBJECT-TYPE
An entry (conceptual row) in the rectifierInfoTable.
1.3.6.1.4.1.6302.2.1.2.11.4.1not-accessiblecurrent
psRectifierIndex
OBJECT-TYPE
Automatically generated index object.
1.3.6.1.4.1.6302.2.1.2.11.4.1.1Integer32 (1..16777215)read-onlycurrent
psRectifierProductNumber
OBJECT-TYPE
Rectifier Product Number.
1.3.6.1.4.1.6302.2.1.2.11.4.1.2DisplayStringread-onlycurrent
psRectifierHWVersion
OBJECT-TYPE
Rectifier Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.11.4.1.3DisplayStringread-onlycurrent
psRectifierSWVersion
OBJECT-TYPE
Rectifier Software Revision.
1.3.6.1.4.1.6302.2.1.2.11.4.1.4DisplayStringread-onlycurrent
psRectifierSerialNumber
OBJECT-TYPE
Rectifier Serial Number.
1.3.6.1.4.1.6302.2.1.2.11.4.1.5DisplayStringread-onlycurrent
psRectifierCurrent
OBJECT-TYPE
Rectifier Current.
1.3.6.1.4.1.6302.2.1.2.11.4.1.6Integer32read-onlycurrent
psRectifierIdent
OBJECT-TYPE
Rectifier physical location identifier.
1.3.6.1.4.1.6302.2.1.2.11.4.1.7DisplayStringread-onlycurrent
psRectifierFail
OBJECT-TYPE
The type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.2.11.4.1.8StatusChangeread-onlycurrent
psDistribution
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.2.12
psTotalLoadCurrent
OBJECT-TYPE
Total Load current, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.12.1Integer32read-onlycurrent
psDistributionLoadTable
OBJECT-TYPE
Distribution Table.
1.3.6.1.4.1.6302.2.1.2.12.2not-accessiblecurrent
psDistributionLoadEntry
OBJECT-TYPE
Distribution Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.12.2.1not-accessiblecurrent
psDistributionLoadIndex
OBJECT-TYPE
Automatically generated index object.
1.3.6.1.4.1.6302.2.1.2.12.2.1.1Integer32 (1..268386303)not-accessiblecurrent
psDistributionLoadCurrent
OBJECT-TYPE
Distribution current in Amps.
1.3.6.1.4.1.6302.2.1.2.12.2.1.2Integer32read-onlycurrent
psDistributionLoadName
OBJECT-TYPE
Distribution name.
1.3.6.1.4.1.6302.2.1.2.12.2.1.3DisplayStringread-onlycurrent
psDistributionGeneralTable
OBJECT-TYPE
Distribution Table.
1.3.6.1.4.1.6302.2.1.2.12.3not-accessiblecurrent
psDistributionGeneralEntry
OBJECT-TYPE
Distribution Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.12.3.1not-accessiblecurrent
psDistributionGeneralIndex
OBJECT-TYPE
Automatically generated index object.
1.3.6.1.4.1.6302.2.1.2.12.3.1.1Integer32 (1..268386303)not-accessiblecurrent
psDistributionGeneralCurrent
OBJECT-TYPE
Distribution current in Amps.
1.3.6.1.4.1.6302.2.1.2.12.3.1.2Integer32read-onlycurrent
psDistributionGeneralName
OBJECT-TYPE
Distribution name.
1.3.6.1.4.1.6302.2.1.2.12.3.1.3DisplayStringread-onlycurrent
psConverter
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.2.13
numberOfInstalledConverters
OBJECT-TYPE
number of converters, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.1Integer32read-onlycurrent
numberOfConvertersCommunicating
OBJECT-TYPE
number of converters communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.2Integer32read-onlycurrent
convertersUsedCapacity
OBJECT-TYPE
Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.3Integer32read-onlycurrent
psConverterVoltage
OBJECT-TYPE
Converter voltage in mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.4Integer32read-onlycurrent
psTotalConverterCurrent
OBJECT-TYPE
Total Converter current in Amps. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.5Integer32read-onlycurrent
psConverterTable
OBJECT-TYPE
Table holding information about indivual converters.
1.3.6.1.4.1.6302.2.1.2.13.6not-accessiblecurrent
psConverterEntry
OBJECT-TYPE
An entry (conceptual row) in the ConverterInfoTable.
1.3.6.1.4.1.6302.2.1.2.13.6.1not-accessiblecurrent
psConverterIndex
OBJECT-TYPE
Automatically generated index object.
1.3.6.1.4.1.6302.2.1.2.13.6.1.1Integer32 (1..100)read-onlycurrent
psConverterProductNumber
OBJECT-TYPE
Converter Product Number.
1.3.6.1.4.1.6302.2.1.2.13.6.1.2DisplayStringread-onlycurrent
psConverterHWVersion
OBJECT-TYPE
Converter Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.13.6.1.3DisplayStringread-onlycurrent
psConverterSWVersion
OBJECT-TYPE
Converter Software Revision.
1.3.6.1.4.1.6302.2.1.2.13.6.1.4DisplayStringread-onlycurrent
psConverterSerialNumber
OBJECT-TYPE
Converter Serial Number.
1.3.6.1.4.1.6302.2.1.2.13.6.1.5DisplayStringread-onlycurrent
psConverterCurrent
OBJECT-TYPE
Converter Current.
1.3.6.1.4.1.6302.2.1.2.13.6.1.6Integer32read-onlycurrent
psConverterIdent
OBJECT-TYPE
Converter physical location identifier.
1.3.6.1.4.1.6302.2.1.2.13.6.1.7DisplayStringread-onlycurrent
psConverterFail
OBJECT-TYPE
The type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.2.13.6.1.8StatusChangeread-onlycurrent
psControl
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.2.14
controlBatteryTest
OBJECT-TYPE
Control battery test, start(1), stop (0).
1.3.6.1.4.1.6302.2.1.2.14.1Integer32read-writecurrent
controlRelay8
OBJECT-TYPE
Control relay8, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.2Integer32read-writecurrent
controlRelay7
OBJECT-TYPE
Control relay7, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.3Integer32read-writecurrent
controlRelay6
OBJECT-TYPE
Control relay6, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.4Integer32read-writecurrent
controlRelayTest
OBJECT-TYPE
Control Relay test, start(1), stop (0).
1.3.6.1.4.1.6302.2.1.2.14.5Integer32read-writecurrent
psEquipmentSignalTable
OBJECT-TYPE
Table of indexed equipment signal values.
1.3.6.1.4.1.6302.2.1.2.15not-accessiblecurrent
equipmentSignalTableEntry
OBJECT-TYPE
An entry (conceptual row) in the psEquipment Signal Table.
1.3.6.1.4.1.6302.2.1.2.15.1not-accessiblecurrent
psEquipmentSignalTableEntryIndex
OBJECT-TYPE
The unique sequence number of this equipment signal.
1.3.6.1.4.1.6302.2.1.2.15.1.1Integer32 (1..268386303)read-onlycurrent
psEquipmentSignalValue
OBJECT-TYPE
Indexed equipment signal value.
1.3.6.1.4.1.6302.2.1.2.15.1.2Integer32read-onlycurrent
alarmLastTrapNo
OBJECT-TYPE
The sequence number of last submitted alarm trap, also last row in alarmTrapTable.
1.3.6.1.4.1.6302.2.1.3Counter32read-onlycurrent
alarmActiveAlarmTable
OBJECT-TYPE
Table holding information about the currently active alarms.
1.3.6.1.4.1.6302.2.1.4not-accessiblecurrent
activeAlarmEntry
OBJECT-TYPE
An entry (conceptual row) in the alarmTrapTable.
1.3.6.1.4.1.6302.2.1.4.1not-accessiblecurrent
alarmIndex
OBJECT-TYPE
The unique sequence number of this alarm trap.
1.3.6.1.4.1.6302.2.1.4.1.1Counter32read-onlycurrent
alarmTime
OBJECT-TYPE
Date and time when event occured (local time), including timezone if supported by controller.
1.3.6.1.4.1.6302.2.1.4.1.2DateAndTimeread-onlycurrent
alarmStatusChange
OBJECT-TYPE
The type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.4.1.3StatusChangeread-onlycurrent
alarmSeverity
OBJECT-TYPE
The severity of the alarm. One of (3) warning - OA, lowest level of alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest level of alarm severity
1.3.6.1.4.1.6302.2.1.4.1.4Statusread-onlycurrent
alarmDescription
OBJECT-TYPE
Free-text description of alarm.
1.3.6.1.4.1.6302.2.1.4.1.5DisplayStringread-onlycurrent
alarmType
OBJECT-TYPE
Alarm type, i.e. an integer specifying the type of alarm.
1.3.6.1.4.1.6302.2.1.4.1.6Integer32read-onlycurrent
powerEvents
OBJECT-IDENTITY
1.3.6.1.4.1.6302.2.1.5

Notifications

NameOIDStatus
alarmTrap
NOTIFICATION-TYPE
An alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this trap: * alarmIndex - The unique sequence number of this alarm trap. * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmStatusChange - (1) activated or (2) deactivated. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm.
1.3.6.1.4.1.6302.2.1.5.1current
alarmActiveTrap
NOTIFICATION-TYPE
An alarm trap is sent when an alarm occurs (activated) Variables in this trap * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm.
1.3.6.1.4.1.6302.2.1.5.2current
alarmCeaseTrap
NOTIFICATION-TYPE
An alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this trap: * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm.
1.3.6.1.4.1.6302.2.1.5.3current