EES-POWER-MIB
- Registered at
- 1.3.6.1.4.1.6302
- Last updated
- 2015-04-10 08:57
- Organization
- Emerson Energy Systems (EES)
- Namespace
- emerson
- Source file
EES-POWER-MIB- Digest
sha256:0a2648473adc77541851c7a79cfff53cbdb7c60da7f7ff48a3f6defb2a596f48
Description
Emerson Energy Systems (EES) Power MIB, revision D.
Contact
Emerson Energy Systems 141 82 Stockholm Sweden
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Counter32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | DateAndTime, DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
EES-POWER-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| Status TEXTUAL-CONVENTION This integer value represents the operational or administrative status of the system. Also used as alarm severity. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) warning - OA, lowest level of 'abnormal' status (4) minor - A3 (5) major - MA (6) critical - CA, highest level of 'abnormal' status Administrative values: (7) unmanaged (8) restricted (9) testing (10) disabled | current | |||
| StatusChange TEXTUAL-CONVENTION Indicates 'activated' (1) or 'deactivated' (2) alarm events. | current |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| ees OBJECT-IDENTITY | 1.3.6.1.4.1.6302 | |||
| pysmi_global OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2 | |||
| ident OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.1 | |||
| identManufacturer OBJECT-TYPE The name of the equipment manufacturer. | 1.3.6.1.4.1.6302.2.1.1.1 | DisplayString | read-only | current |
| identModel OBJECT-TYPE The manufacturers model designation of the power system. | 1.3.6.1.4.1.6302.2.1.1.2 | DisplayString | read-only | current |
| identControllerFirmwareVersion OBJECT-TYPE The firmware (software) version of the controller. | 1.3.6.1.4.1.6302.2.1.1.3 | DisplayString | read-only | current |
| identName OBJECT-TYPE The name of the power plant. This object should be set by the administrator. | 1.3.6.1.4.1.6302.2.1.1.4 | DisplayString | read-write | current |
| identSNMPCfgVer OBJECT-TYPE The snmp cfg version | 1.3.6.1.4.1.6302.2.1.1.5 | DisplayString | read-only | current |
| identControllerSerialNumber OBJECT-TYPE The serial number of this controller | 1.3.6.1.4.1.6302.2.1.1.6 | DisplayString | read-only | current |
| system OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.2 | |||
| systemStatus OBJECT-TYPE Status of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) warning - OA, lowest level of 'abnormal' status (4) minor - A3 (5) major - MA (6) critical - CA, highest level of 'abnormal' status (7) unmanaged (8) restricted (9) testing (10) disabled | 1.3.6.1.4.1.6302.2.1.2.1 | Status | read-only | current |
| systemVoltage OBJECT-TYPE System voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.2 | Integer32 | read-only | current |
| systemCurrent OBJECT-TYPE System current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.3 | Integer32 | read-only | current |
| systemUsedCapacity OBJECT-TYPE Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.4 | Integer32 | read-only | current |
| psBattery OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.2.5 | |||
| psBatteryVoltage OBJECT-TYPE Battery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.5.1 | Integer32 | read-only | current |
| psTotalBatteryCurrent OBJECT-TYPE Battery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.5.2 | Integer32 | read-only | current |
| psBatteryCapacity OBJECT-TYPE Calculated capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.5.3 | Integer32 | read-only | current |
| psBatteryNominalCapacity OBJECT-TYPE nominal installed capacity, stored as mAh. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.5.4 | Integer32 | read-only | current |
| psBatteryTable OBJECT-TYPE Battery Table. | 1.3.6.1.4.1.6302.2.1.2.5.5 | not-accessible | current | |
| psBatteryEntry OBJECT-TYPE Battery Measurement Table Entry. | 1.3.6.1.4.1.6302.2.1.2.5.5.1 | not-accessible | current | |
| psBatteryIndex OBJECT-TYPE Automatically generated index object. | 1.3.6.1.4.1.6302.2.1.2.5.5.1.1 | Integer32 (1..16777215) | read-only | current |
| psBatteryCurrent OBJECT-TYPE Battery current in Amps. | 1.3.6.1.4.1.6302.2.1.2.5.5.1.2 | Integer32 | read-only | current |
| psBatteryName OBJECT-TYPE Battery shunt name. | 1.3.6.1.4.1.6302.2.1.2.5.5.1.3 | DisplayString | read-only | current |
| psInput OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.2.6 | |||
| psInputLineAVoltage OBJECT-TYPE The AC line A voltage, stored as mV. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.6.1 | Integer32 | read-only | current |
| psInputLineBVoltage OBJECT-TYPE The AC line B voltage, stored as mV. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.6.2 | Integer32 | read-only | current |
| psInputLineCVoltage OBJECT-TYPE The AC line C voltage, stored as mV. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.6.3 | Integer32 | read-only | current |
| psTemperature OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.2.7 | |||
| psTemperature1 OBJECT-TYPE The first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.7.1 | Integer32 | read-only | current |
| psTemperature2 OBJECT-TYPE The second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.. | 1.3.6.1.4.1.6302.2.1.2.7.2 | Integer32 | read-only | current |
| psTemperatureTable OBJECT-TYPE Temperature Measurement Table. | 1.3.6.1.4.1.6302.2.1.2.7.3 | not-accessible | current | |
| psTemperatureEntry OBJECT-TYPE Temperature Measurement Table Entry. | 1.3.6.1.4.1.6302.2.1.2.7.3.1 | not-accessible | current | |
| psTemperatureIndex OBJECT-TYPE Temperature Probe Number | 1.3.6.1.4.1.6302.2.1.2.7.3.1.1 | Integer32 (1..71) | read-only | current |
| psTemperatureMeasurement OBJECT-TYPE Temperature Value In Centigrade. | 1.3.6.1.4.1.6302.2.1.2.7.3.1.2 | Integer32 | read-only | current |
| psTemperatureName OBJECT-TYPE Configured Temperature Probe Name. | 1.3.6.1.4.1.6302.2.1.2.7.3.1.3 | DisplayString | read-only | current |
| psTemperatureType OBJECT-TYPE Temperature Probe Type | 1.3.6.1.4.1.6302.2.1.2.7.3.1.4 | INTEGER {none(0), ambient(1), battery(2)} | read-only | current |
| psTemperatureAlarmStatus OBJECT-TYPE Temperature Probe Alarm Status | 1.3.6.1.4.1.6302.2.1.2.7.3.1.5 | INTEGER {high(0), low(1), fail(2), none(3)} | read-only | current |
| psStatusCommunication OBJECT-TYPE The status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent. | 1.3.6.1.4.1.6302.2.1.2.8 | INTEGER {unknown(1), normal(2), interrupt(3)} | read-only | current |
| psStatusBatteryMode OBJECT-TYPE The status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoostCharging(9), AutoBoostCharging(10), CyclicBoostCharging(11), MasterBoostCharging(12), MasterBateryTesting(13). | 1.3.6.1.4.1.6302.2.1.2.9 | INTEGER {unknown(1), floatCharging(2), shortTest(3), bcForTest(4), manualTesting(5), planTesting(6), acFailTesting(7), acFail(8), manualBC(9), autoBC(10), cyclicBC(11), masterBC(12), masterBT(13)} | read-only | current |
| psSMNumber OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.2.10 | |||
| psSMACNumber OBJECT-TYPE The number of SM AC module. | 1.3.6.1.4.1.6302.2.1.2.10.1 | Integer32 | read-only | current |
| psSMBATNumber OBJECT-TYPE The number of SM BAT module. | 1.3.6.1.4.1.6302.2.1.2.10.2 | Integer32 | read-only | current |
| psSMIONumber OBJECT-TYPE The number of SM IO module. | 1.3.6.1.4.1.6302.2.1.2.10.3 | Integer32 | read-only | current |
| psRectifier OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.2.11 | |||
| numberOfInstalledRectifiers OBJECT-TYPE number of rectifiers, stored as integer. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.11.1 | Integer32 | read-only | current |
| numberOfRectifiersCommunicating OBJECT-TYPE number of rectifiers communicating, stored as integer. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.11.2 | Integer32 | read-only | current |
| rectifiersUsedCapacity OBJECT-TYPE Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.11.3 | Integer32 | read-only | current |
| psRectifierTable OBJECT-TYPE Table holding information about indivual rectifiers. | 1.3.6.1.4.1.6302.2.1.2.11.4 | not-accessible | current | |
| psRectifierEntry OBJECT-TYPE An entry (conceptual row) in the rectifierInfoTable. | 1.3.6.1.4.1.6302.2.1.2.11.4.1 | not-accessible | current | |
| psRectifierIndex OBJECT-TYPE Automatically generated index object. | 1.3.6.1.4.1.6302.2.1.2.11.4.1.1 | Integer32 (1..16777215) | read-only | current |
| psRectifierProductNumber OBJECT-TYPE Rectifier Product Number. | 1.3.6.1.4.1.6302.2.1.2.11.4.1.2 | DisplayString | read-only | current |
| psRectifierHWVersion OBJECT-TYPE Rectifier Hardware Revision. | 1.3.6.1.4.1.6302.2.1.2.11.4.1.3 | DisplayString | read-only | current |
| psRectifierSWVersion OBJECT-TYPE Rectifier Software Revision. | 1.3.6.1.4.1.6302.2.1.2.11.4.1.4 | DisplayString | read-only | current |
| psRectifierSerialNumber OBJECT-TYPE Rectifier Serial Number. | 1.3.6.1.4.1.6302.2.1.2.11.4.1.5 | DisplayString | read-only | current |
| psRectifierCurrent OBJECT-TYPE Rectifier Current. | 1.3.6.1.4.1.6302.2.1.2.11.4.1.6 | Integer32 | read-only | current |
| psRectifierIdent OBJECT-TYPE Rectifier physical location identifier. | 1.3.6.1.4.1.6302.2.1.2.11.4.1.7 | DisplayString | read-only | current |
| psRectifierFail OBJECT-TYPE The type of alarm change. One of (1) activated (2) deactivated | 1.3.6.1.4.1.6302.2.1.2.11.4.1.8 | StatusChange | read-only | current |
| psDistribution OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.2.12 | |||
| psTotalLoadCurrent OBJECT-TYPE Total Load current, stored as integer. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.12.1 | Integer32 | read-only | current |
| psDistributionLoadTable OBJECT-TYPE Distribution Table. | 1.3.6.1.4.1.6302.2.1.2.12.2 | not-accessible | current | |
| psDistributionLoadEntry OBJECT-TYPE Distribution Measurement Table Entry. | 1.3.6.1.4.1.6302.2.1.2.12.2.1 | not-accessible | current | |
| psDistributionLoadIndex OBJECT-TYPE Automatically generated index object. | 1.3.6.1.4.1.6302.2.1.2.12.2.1.1 | Integer32 (1..268386303) | not-accessible | current |
| psDistributionLoadCurrent OBJECT-TYPE Distribution current in Amps. | 1.3.6.1.4.1.6302.2.1.2.12.2.1.2 | Integer32 | read-only | current |
| psDistributionLoadName OBJECT-TYPE Distribution name. | 1.3.6.1.4.1.6302.2.1.2.12.2.1.3 | DisplayString | read-only | current |
| psDistributionGeneralTable OBJECT-TYPE Distribution Table. | 1.3.6.1.4.1.6302.2.1.2.12.3 | not-accessible | current | |
| psDistributionGeneralEntry OBJECT-TYPE Distribution Measurement Table Entry. | 1.3.6.1.4.1.6302.2.1.2.12.3.1 | not-accessible | current | |
| psDistributionGeneralIndex OBJECT-TYPE Automatically generated index object. | 1.3.6.1.4.1.6302.2.1.2.12.3.1.1 | Integer32 (1..268386303) | not-accessible | current |
| psDistributionGeneralCurrent OBJECT-TYPE Distribution current in Amps. | 1.3.6.1.4.1.6302.2.1.2.12.3.1.2 | Integer32 | read-only | current |
| psDistributionGeneralName OBJECT-TYPE Distribution name. | 1.3.6.1.4.1.6302.2.1.2.12.3.1.3 | DisplayString | read-only | current |
| psConverter OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.2.13 | |||
| numberOfInstalledConverters OBJECT-TYPE number of converters, stored as integer. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.13.1 | Integer32 | read-only | current |
| numberOfConvertersCommunicating OBJECT-TYPE number of converters communicating, stored as integer. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.13.2 | Integer32 | read-only | current |
| convertersUsedCapacity OBJECT-TYPE Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.13.3 | Integer32 | read-only | current |
| psConverterVoltage OBJECT-TYPE Converter voltage in mV. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.13.4 | Integer32 | read-only | current |
| psTotalConverterCurrent OBJECT-TYPE Total Converter current in Amps. The integer 2147483647 represents invalid value. | 1.3.6.1.4.1.6302.2.1.2.13.5 | Integer32 | read-only | current |
| psConverterTable OBJECT-TYPE Table holding information about indivual converters. | 1.3.6.1.4.1.6302.2.1.2.13.6 | not-accessible | current | |
| psConverterEntry OBJECT-TYPE An entry (conceptual row) in the ConverterInfoTable. | 1.3.6.1.4.1.6302.2.1.2.13.6.1 | not-accessible | current | |
| psConverterIndex OBJECT-TYPE Automatically generated index object. | 1.3.6.1.4.1.6302.2.1.2.13.6.1.1 | Integer32 (1..100) | read-only | current |
| psConverterProductNumber OBJECT-TYPE Converter Product Number. | 1.3.6.1.4.1.6302.2.1.2.13.6.1.2 | DisplayString | read-only | current |
| psConverterHWVersion OBJECT-TYPE Converter Hardware Revision. | 1.3.6.1.4.1.6302.2.1.2.13.6.1.3 | DisplayString | read-only | current |
| psConverterSWVersion OBJECT-TYPE Converter Software Revision. | 1.3.6.1.4.1.6302.2.1.2.13.6.1.4 | DisplayString | read-only | current |
| psConverterSerialNumber OBJECT-TYPE Converter Serial Number. | 1.3.6.1.4.1.6302.2.1.2.13.6.1.5 | DisplayString | read-only | current |
| psConverterCurrent OBJECT-TYPE Converter Current. | 1.3.6.1.4.1.6302.2.1.2.13.6.1.6 | Integer32 | read-only | current |
| psConverterIdent OBJECT-TYPE Converter physical location identifier. | 1.3.6.1.4.1.6302.2.1.2.13.6.1.7 | DisplayString | read-only | current |
| psConverterFail OBJECT-TYPE The type of alarm change. One of (1) activated (2) deactivated | 1.3.6.1.4.1.6302.2.1.2.13.6.1.8 | StatusChange | read-only | current |
| psControl OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.2.14 | |||
| controlBatteryTest OBJECT-TYPE Control battery test, start(1), stop (0). | 1.3.6.1.4.1.6302.2.1.2.14.1 | Integer32 | read-write | current |
| controlRelay8 OBJECT-TYPE Control relay8, close(1), open(0). | 1.3.6.1.4.1.6302.2.1.2.14.2 | Integer32 | read-write | current |
| controlRelay7 OBJECT-TYPE Control relay7, close(1), open(0). | 1.3.6.1.4.1.6302.2.1.2.14.3 | Integer32 | read-write | current |
| controlRelay6 OBJECT-TYPE Control relay6, close(1), open(0). | 1.3.6.1.4.1.6302.2.1.2.14.4 | Integer32 | read-write | current |
| controlRelayTest OBJECT-TYPE Control Relay test, start(1), stop (0). | 1.3.6.1.4.1.6302.2.1.2.14.5 | Integer32 | read-write | current |
| psEquipmentSignalTable OBJECT-TYPE Table of indexed equipment signal values. | 1.3.6.1.4.1.6302.2.1.2.15 | not-accessible | current | |
| equipmentSignalTableEntry OBJECT-TYPE An entry (conceptual row) in the psEquipment Signal Table. | 1.3.6.1.4.1.6302.2.1.2.15.1 | not-accessible | current | |
| psEquipmentSignalTableEntryIndex OBJECT-TYPE The unique sequence number of this equipment signal. | 1.3.6.1.4.1.6302.2.1.2.15.1.1 | Integer32 (1..268386303) | read-only | current |
| psEquipmentSignalValue OBJECT-TYPE Indexed equipment signal value. | 1.3.6.1.4.1.6302.2.1.2.15.1.2 | Integer32 | read-only | current |
| alarmLastTrapNo OBJECT-TYPE The sequence number of last submitted alarm trap, also last row in alarmTrapTable. | 1.3.6.1.4.1.6302.2.1.3 | Counter32 | read-only | current |
| alarmActiveAlarmTable OBJECT-TYPE Table holding information about the currently active alarms. | 1.3.6.1.4.1.6302.2.1.4 | not-accessible | current | |
| activeAlarmEntry OBJECT-TYPE An entry (conceptual row) in the alarmTrapTable. | 1.3.6.1.4.1.6302.2.1.4.1 | not-accessible | current | |
| alarmIndex OBJECT-TYPE The unique sequence number of this alarm trap. | 1.3.6.1.4.1.6302.2.1.4.1.1 | Counter32 | read-only | current |
| alarmTime OBJECT-TYPE Date and time when event occured (local time), including timezone if supported by controller. | 1.3.6.1.4.1.6302.2.1.4.1.2 | DateAndTime | read-only | current |
| alarmStatusChange OBJECT-TYPE The type of alarm change. One of (1) activated (2) deactivated | 1.3.6.1.4.1.6302.2.1.4.1.3 | StatusChange | read-only | current |
| alarmSeverity OBJECT-TYPE The severity of the alarm. One of (3) warning - OA, lowest level of alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest level of alarm severity | 1.3.6.1.4.1.6302.2.1.4.1.4 | Status | read-only | current |
| alarmDescription OBJECT-TYPE Free-text description of alarm. | 1.3.6.1.4.1.6302.2.1.4.1.5 | DisplayString | read-only | current |
| alarmType OBJECT-TYPE Alarm type, i.e. an integer specifying the type of alarm. | 1.3.6.1.4.1.6302.2.1.4.1.6 | Integer32 | read-only | current |
| powerEvents OBJECT-IDENTITY | 1.3.6.1.4.1.6302.2.1.5 |
Notifications
| Name | OID | Status |
|---|---|---|
| alarmTrap NOTIFICATION-TYPE An alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this trap: * alarmIndex - The unique sequence number of this alarm trap. * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmStatusChange - (1) activated or (2) deactivated. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm. | 1.3.6.1.4.1.6302.2.1.5.1 | current |
| alarmActiveTrap NOTIFICATION-TYPE An alarm trap is sent when an alarm occurs (activated) Variables in this trap * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm. | 1.3.6.1.4.1.6302.2.1.5.2 | current |
| alarmCeaseTrap NOTIFICATION-TYPE An alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this trap: * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm. | 1.3.6.1.4.1.6302.2.1.5.3 | current |