Description

The MIB module for Eaton PDUs (Power Distribution Units). Copyright (C) Eaton Corporation (2007).

Contact

Eaton Power Quality Technical Support (PQTS) group www.eaton.com/powerxpert Technical Resource Center phone numbers United States: 1.800.843.9433 or 919.870.3028 Canada: 1.800.461.9166 ext. 260 All other countries: Call your local service representative.

Imports

FromSymbols
EATON-OIDSpduAgent
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-SMIInteger32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

EATON-OIDS
EATON-PDU-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Textual conventions

NameOIDSyntaxAccessStatus
NonNegativeInteger
TEXTUAL-CONVENTION
This data type is a non-negative value.
current
PositiveInteger
TEXTUAL-CONVENTION
This data type is a non-zero and non-negative value.
current

Objects

NameOIDSyntaxAccessStatus
eatonPduMIBObjects
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.4.1
mainPdu
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.4.1.1
pduNameplate
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.4.1.1.1
pduRatingVA
OBJECT-TYPE
The full VA rating of this PDU (for all phases).
1.3.6.1.4.1.534.6.6.4.1.1.1.1PositiveIntegerread-onlycurrent
pduNominalOutputVoltage
OBJECT-TYPE
The nominal Output Voltage of this PDU (as distributed to the panels). May differ from the nominal Input Voltage if the PDU has an input transformer. This is either Line-to-Line or Line-to-Neutral, as indicated in pduOutputVoltageUnits.
1.3.6.1.4.1.534.6.6.4.1.1.1.2PositiveIntegerread-onlycurrent
pduNumPhases
OBJECT-TYPE
The number of lines (phases) for this PDU. The number of Input phases must equal the number of Output phases.
1.3.6.1.4.1.534.6.6.4.1.1.1.3PositiveIntegerread-onlycurrent
pduNumPanels
OBJECT-TYPE
The number of panels or subfeeds contained in this PDU system. This determines the number of rows found in the panel tables.
1.3.6.1.4.1.534.6.6.4.1.1.1.4PositiveIntegerread-onlycurrent
pduInput
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.4.1.1.2
pduFrequency
OBJECT-TYPE
The present frequency reading for the full PDU.
1.3.6.1.4.1.534.6.6.4.1.1.2.1NonNegativeIntegerread-onlycurrent
pduInputVA
OBJECT-TYPE
The present VA input demand of the full PDU system.
1.3.6.1.4.1.534.6.6.4.1.1.2.2NonNegativeIntegerread-onlycurrent
pduInputPower
OBJECT-TYPE
The present input power demand of the full PDU system.
1.3.6.1.4.1.534.6.6.4.1.1.2.3NonNegativeIntegerread-onlycurrent
pduInputPowerFactor
OBJECT-TYPE
The input power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
1.3.6.1.4.1.534.6.6.4.1.1.2.4Integer32 (-100..100)read-onlycurrent
pduGroundCurrent
OBJECT-TYPE
The present current in the PDU's ground phase. Ideally, this value stays at 0.
1.3.6.1.4.1.534.6.6.4.1.1.2.5NonNegativeIntegerread-onlycurrent
pduInputVoltageUnits
OBJECT-TYPE
Indicates whether the pduInputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
1.3.6.1.4.1.534.6.6.4.1.1.2.6DisplayString (SIZE(0..31))read-onlycurrent
pduInputNumPhases
OBJECT-TYPE
The number of input phases for this PDU. This variable indicates the number of rows in the pduInputTable.
1.3.6.1.4.1.534.6.6.4.1.1.2.7PositiveIntegerread-onlycurrent
pduInputTable
OBJECT-TYPE
A list of input table entries. The number of entries is given by the value of pduInputNumPhases.
1.3.6.1.4.1.534.6.6.4.1.1.2.8not-accessiblecurrent
pduInputEntry
OBJECT-TYPE
An entry containing information applicable to a particular input phase.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1not-accessiblecurrent
pduInputPhaseIndex
OBJECT-TYPE
The input line identifier.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.1PositiveIntegernot-accessiblecurrent
pduInputPhaseVoltage
OBJECT-TYPE
The present input voltage for this phase.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.2NonNegativeIntegerread-onlycurrent
pduInputPhaseCurrent
OBJECT-TYPE
The present input current for this phase.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.3NonNegativeIntegerread-onlycurrent
pduInputPhasePercentLoad
OBJECT-TYPE
The percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduInputPhaseCurrent to the rated input current.
1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.4Integer32 (0..200)read-onlycurrent
pduOutput
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.4.1.1.3
pduOutputKilowattHours
OBJECT-TYPE
The accumulated kilowatt-hour value for the full PDU system since the last reset.
1.3.6.1.4.1.534.6.6.4.1.1.3.1NonNegativeIntegerread-onlycurrent
pduOutputVA
OBJECT-TYPE
The present VA output of the full PDU system.
1.3.6.1.4.1.534.6.6.4.1.1.3.2NonNegativeIntegerread-onlycurrent
pduOutputPower
OBJECT-TYPE
The present output power of the full PDU system.
1.3.6.1.4.1.534.6.6.4.1.1.3.3NonNegativeIntegerread-onlycurrent
pduOutputPowerFactor
OBJECT-TYPE
The output power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
1.3.6.1.4.1.534.6.6.4.1.1.3.4Integer32 (-100..100)read-onlycurrent
pduNeutralCurrent
OBJECT-TYPE
The present current in the PDU's output neutral phase. Ideally, this value stays at 0.
1.3.6.1.4.1.534.6.6.4.1.1.3.5NonNegativeIntegerread-onlycurrent
pduRatedOutputCurrent
OBJECT-TYPE
The rated current value for one PDU Output phase at full load (100%).
1.3.6.1.4.1.534.6.6.4.1.1.3.6PositiveIntegerread-onlycurrent
pduOutputVoltageUnits
OBJECT-TYPE
Indicates whether the pduOutputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
1.3.6.1.4.1.534.6.6.4.1.1.3.7DisplayString (SIZE(0..31))read-onlycurrent
pduOutputNumPhases
OBJECT-TYPE
The number of output phases for this PDU. This variable indicates the number of rows in the pduOutputTable.
1.3.6.1.4.1.534.6.6.4.1.1.3.8PositiveIntegerread-onlycurrent
pduOutputTable
OBJECT-TYPE
A list of output table entries. The number of entries is given by the value of pduOutputNumPhases.
1.3.6.1.4.1.534.6.6.4.1.1.3.9not-accessiblecurrent
pduOutputEntry
OBJECT-TYPE
An entry containing information applicable to a particular output phase.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1not-accessiblecurrent
pduOutputPhaseIndex
OBJECT-TYPE
The output line identifier.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.1PositiveIntegernot-accessiblecurrent
pduOutputPhaseVoltage
OBJECT-TYPE
The present output voltage for this phase.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.2NonNegativeIntegerread-onlycurrent
pduOutputPhaseCurrent
OBJECT-TYPE
The present output current for this phase.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.3NonNegativeIntegerread-onlycurrent
pduOutputPhasePercentLoad
OBJECT-TYPE
The percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduOutputPhaseCurrent to pduRatedOutputCurrent.
1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.4Integer32 (0..200)read-onlycurrent
pduPanel
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.4.1.2
panelRatingsTable
OBJECT-TYPE
A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
1.3.6.1.4.1.534.6.6.4.1.2.1not-accessiblecurrent
panelRatingsEntry
OBJECT-TYPE
An entry containing information applicable to a particular output phase.
1.3.6.1.4.1.534.6.6.4.1.2.1.1not-accessiblecurrent
panelNumber
OBJECT-TYPE
Index for the Panel Ratings and Meters tables. Corresponds to the physical panel number in the PDU system. There must be a #1. The maximum value is 16. Panels are not required to be numbered sequentially.
1.3.6.1.4.1.534.6.6.4.1.2.1.1.1PositiveIntegernot-accessiblecurrent
panelRatedVoltage
OBJECT-TYPE
The nominal Voltage of this panel (as distributed to the breakers or subfeeds). This is either Line-to-Line or Line-to-Neutral, as indicated in panelVoltageUnits.
1.3.6.1.4.1.534.6.6.4.1.2.1.1.2PositiveIntegerread-onlycurrent
panelRatedBreakerCurrent
OBJECT-TYPE
The rated current value for one panel (input) phase at full load (100%). This is set by the panel's input breaker; if there is no input breaker for this panel, then this object is not accessible.
1.3.6.1.4.1.534.6.6.4.1.2.1.1.3PositiveIntegerread-onlycurrent
panelNumPhases
OBJECT-TYPE
The number of lines (phases) for this panel.
1.3.6.1.4.1.534.6.6.4.1.2.1.1.4PositiveIntegerread-onlycurrent
panelNumBreakers
OBJECT-TYPE
The number of breakers contained in this panel. This determines the number of rows found in the breaker tables.
1.3.6.1.4.1.534.6.6.4.1.2.1.1.5PositiveIntegerread-onlycurrent
panelVoltageUnits
OBJECT-TYPE
Indicates whether the panelPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
1.3.6.1.4.1.534.6.6.4.1.2.1.1.6DisplayString (SIZE(0..31))read-onlycurrent
panelMetersTable
OBJECT-TYPE
A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
1.3.6.1.4.1.534.6.6.4.1.2.2not-accessiblecurrent
panelMetersEntry
OBJECT-TYPE
An entry containing meter readings applicable to a particular panel.
1.3.6.1.4.1.534.6.6.4.1.2.2.1not-accessiblecurrent
panelTotalKilowattHours
OBJECT-TYPE
The accumulated kilowatt-hours for this panel since it was commissioned and put into service, or since the last reset of the system KHW measures.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.1NonNegativeIntegerread-onlycurrent
panelMonthlyKilowattHours
OBJECT-TYPE
The accumulated kilowatt-hours for this panel since the beginning of this calendar month, or since the last reset of the system KHW measures.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.2NonNegativeIntegerread-onlycurrent
panelYtdKilowattHours
OBJECT-TYPE
The accumulated kilowatt-hours for this panel since the beginning of this calendar year (YTD), or since the last reset of the system KHW measures.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.3NonNegativeIntegerread-onlycurrent
panelVA
OBJECT-TYPE
The present VA (input) demand of this panel.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.4NonNegativeIntegerread-onlycurrent
panelPower
OBJECT-TYPE
The present power (input) demand of this panel.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.5NonNegativeIntegerread-onlycurrent
panelPowerFactor
OBJECT-TYPE
The input power factor for this panel. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.6Integer32 (-100..100)read-onlycurrent
panelNeutralCurrent
OBJECT-TYPE
The present neutral phase current for this panel.
1.3.6.1.4.1.534.6.6.4.1.2.2.1.7NonNegativeIntegerread-onlycurrent
panelPhaseMetersTable
OBJECT-TYPE
A sparsely populated (ie, not sequentially panel numbered) table of ratings for each panel. The number of entries is given by the sum of panelNumPhases for pduNumPanels.
1.3.6.1.4.1.534.6.6.4.1.2.3not-accessiblecurrent
panelPhaseMetersEntry
OBJECT-TYPE
An entry containing meter readings applicable to a particular phase of a particular panel.
1.3.6.1.4.1.534.6.6.4.1.2.3.1not-accessiblecurrent
panelPhaseIndex
OBJECT-TYPE
The line or phase identifier.
1.3.6.1.4.1.534.6.6.4.1.2.3.1.1PositiveIntegernot-accessiblecurrent
panelPhaseVoltage
OBJECT-TYPE
The present voltage for this phase.
1.3.6.1.4.1.534.6.6.4.1.2.3.1.2NonNegativeIntegerread-onlycurrent
panelPhaseCurrent
OBJECT-TYPE
The present current for this phase.
1.3.6.1.4.1.534.6.6.4.1.2.3.1.3NonNegativeIntegerread-onlycurrent
panelPhasePercentLoad
OBJECT-TYPE
The percentage of the panel power capacity presently being used on this line, normally based on the ratio of panelPhaseCurrent to the rated phase current.
1.3.6.1.4.1.534.6.6.4.1.2.3.1.4Integer32 (0..200)read-onlycurrent
pduBreaker
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.4.1.3
breakerRatingsTable
OBJECT-TYPE
A sparsely populated (ie, not sequentially numbered) table of ratings and fixed values for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
1.3.6.1.4.1.534.6.6.4.1.3.1not-accessiblecurrent
breakerRatingsEntry
OBJECT-TYPE
An entry containing information applicable to a particular output phase.
1.3.6.1.4.1.534.6.6.4.1.3.1.1not-accessiblecurrent
breakerNumber
OBJECT-TYPE
Index for the Breaker Ratings and Meters tables. Corresponds to the physical breaker number in the PDU system. Breakers are not required to be numbered sequentially.
1.3.6.1.4.1.534.6.6.4.1.3.1.1.1PositiveIntegernot-accessiblecurrent
breakerName
OBJECT-TYPE
Name given by the administrator to identify this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.1.1.2DisplayString (SIZE(0..31))read-onlycurrent
breakerRatedCurrent
OBJECT-TYPE
The rated current value of this breaker (for one phase) at full load (100%).
1.3.6.1.4.1.534.6.6.4.1.3.1.1.3PositiveIntegerread-onlycurrent
breakerNumPhases
OBJECT-TYPE
The number of lines (phases) for this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.1.1.4PositiveIntegerread-onlycurrent
breakerMetersTable
OBJECT-TYPE
A sparsely populated (ie, not sequentially numbered) table of ratings for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
1.3.6.1.4.1.534.6.6.4.1.3.2not-accessiblecurrent
breakerMetersEntry
OBJECT-TYPE
An entry containing meter readings applicable to a particular breaker.
1.3.6.1.4.1.534.6.6.4.1.3.2.1not-accessiblecurrent
breakerTotalKilowattHours
OBJECT-TYPE
The accumulated kilowatt-hours for this breaker since it was commissioned and put into service, or since the last reset of the panel KHW measures.
1.3.6.1.4.1.534.6.6.4.1.3.2.1.1NonNegativeIntegerread-onlycurrent
breakerMonthlyKilowattHours
OBJECT-TYPE
The accumulated kilowatt-hours for this breaker since the beginning of this calendar month, or since the last reset of the panel KHW measures.
1.3.6.1.4.1.534.6.6.4.1.3.2.1.2NonNegativeIntegerread-onlycurrent
breakerYtdKilowattHours
OBJECT-TYPE
The accumulated kilowatt-hours for this breaker since the beginning of this calendar year (YTD), or since the last reset of the panel KHW measures.
1.3.6.1.4.1.534.6.6.4.1.3.2.1.3NonNegativeIntegerread-onlycurrent
breakerPhaseMetersTable
OBJECT-TYPE
A sparsely populated (ie, not sequentially breaker numbered) table of ratings for each breaker. The number of entries is given by the sum of breakerNumPhases for panelNumBreakers for all panels (pduNumPanels).
1.3.6.1.4.1.534.6.6.4.1.3.3not-accessiblecurrent
breakerPhaseMetersEntry
OBJECT-TYPE
An entry containing meter readings applicable to a particular phase of a particular breaker on a particular panel.
1.3.6.1.4.1.534.6.6.4.1.3.3.1not-accessiblecurrent
breakerPhaseIndex
OBJECT-TYPE
The line or phase identifier.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.1PositiveIntegernot-accessiblecurrent
breakerPhaseVA
OBJECT-TYPE
The present VA (input) demand of this phase on this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.2NonNegativeIntegerread-onlycurrent
breakerPhasePower
OBJECT-TYPE
The present power (input) demand of phase on this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.3NonNegativeIntegerread-onlycurrent
breakerPhasePowerFactor
OBJECT-TYPE
The input power factor for this phase on this breaker. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.4Integer32 (-100..100)read-onlycurrent
breakerPhaseCurrent
OBJECT-TYPE
The present current for this phase of this breaker.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.5NonNegativeIntegerread-onlycurrent
breakerPhasePercentLoad
OBJECT-TYPE
The percentage of the breaker power capacity presently being used on this line, normally based on the ratio of breakerPhaseCurrent to the breakerRatedCurrent.
1.3.6.1.4.1.534.6.6.4.1.3.3.1.6Integer32 (0..200)read-onlycurrent
eatonPduConformance
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.4.2

Conformance

NameOIDStatus
pduNameplateGroup
OBJECT-GROUP
The pduNameplate subgroup objects.
1.3.6.1.4.1.534.6.6.4.2.1current
pduInputGroup
OBJECT-GROUP
The pduInput Meters subgroup objects.
1.3.6.1.4.1.534.6.6.4.2.2current
pduOutputGroup
OBJECT-GROUP
The pduOutput Meters subgroup objects.
1.3.6.1.4.1.534.6.6.4.2.3current
panelRatingsGroup
OBJECT-GROUP
The panelRatings table objects.
1.3.6.1.4.1.534.6.6.4.2.4current
panelMetersGroup
OBJECT-GROUP
The BreakerMeters Table objects.
1.3.6.1.4.1.534.6.6.4.2.5current
panelPhaseMetersGroup
OBJECT-GROUP
The BreakerPhaseMeters Table objects.
1.3.6.1.4.1.534.6.6.4.2.6current
breakerRatingsGroup
OBJECT-GROUP
The breakerRatings table objects.
1.3.6.1.4.1.534.6.6.4.2.7current
breakerMetersGroup
OBJECT-GROUP
The breakerMeters table objects.
1.3.6.1.4.1.534.6.6.4.2.8current
breakerPhaseMetersGroup
OBJECT-GROUP
The breakerPhaseMeters table objects.
1.3.6.1.4.1.534.6.6.4.2.9current
pdu3phaseCompliance
MODULE-COMPLIANCE
The compliance statement for a normal 3-phase PDU, which implements the full set of objects.
1.3.6.1.4.1.534.6.6.4.2.10current