EATON-PDU-MIB
- Registered at
- 1.3.6.1.4.1.534.6.6.4
- Last updated
- 2007-01-08 00:00
- Organization
- Eaton Corporation
- Revisions
- 2007-01-08 00:00
- Namespace
- eaton
- Source file
EATON-PDU-MIB- Digest
sha256:25ef47a2edc8d94dda38bcdf4ef7dac8a411ded2ca8e85aa367f64b53c01076d
Description
The MIB module for Eaton PDUs (Power Distribution Units). Copyright (C) Eaton Corporation (2007).
Contact
Eaton Power Quality Technical Support (PQTS) group www.eaton.com/powerxpert Technical Resource Center phone numbers United States: 1.800.843.9433 or 919.870.3028 Canada: 1.800.461.9166 ext. 260 All other countries: Call your local service representative.
Imports
| From | Symbols |
|---|---|
| EATON-OIDS | pduAgent |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-SMI | Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
EATON-OIDS EATON-PDU-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| NonNegativeInteger TEXTUAL-CONVENTION This data type is a non-negative value. | current | |||
| PositiveInteger TEXTUAL-CONVENTION This data type is a non-zero and non-negative value. | current |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| eatonPduMIBObjects OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.6.4.1 | |||
| mainPdu OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.6.4.1.1 | |||
| pduNameplate OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.6.4.1.1.1 | |||
| pduRatingVA OBJECT-TYPE The full VA rating of this PDU (for all phases). | 1.3.6.1.4.1.534.6.6.4.1.1.1.1 | PositiveInteger | read-only | current |
| pduNominalOutputVoltage OBJECT-TYPE The nominal Output Voltage of this PDU (as distributed to the panels). May differ from the nominal Input Voltage if the PDU has an input transformer. This is either Line-to-Line or Line-to-Neutral, as indicated in pduOutputVoltageUnits. | 1.3.6.1.4.1.534.6.6.4.1.1.1.2 | PositiveInteger | read-only | current |
| pduNumPhases OBJECT-TYPE The number of lines (phases) for this PDU. The number of Input phases must equal the number of Output phases. | 1.3.6.1.4.1.534.6.6.4.1.1.1.3 | PositiveInteger | read-only | current |
| pduNumPanels OBJECT-TYPE The number of panels or subfeeds contained in this PDU system. This determines the number of rows found in the panel tables. | 1.3.6.1.4.1.534.6.6.4.1.1.1.4 | PositiveInteger | read-only | current |
| pduInput OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.6.4.1.1.2 | |||
| pduFrequency OBJECT-TYPE The present frequency reading for the full PDU. | 1.3.6.1.4.1.534.6.6.4.1.1.2.1 | NonNegativeInteger | read-only | current |
| pduInputVA OBJECT-TYPE The present VA input demand of the full PDU system. | 1.3.6.1.4.1.534.6.6.4.1.1.2.2 | NonNegativeInteger | read-only | current |
| pduInputPower OBJECT-TYPE The present input power demand of the full PDU system. | 1.3.6.1.4.1.534.6.6.4.1.1.2.3 | NonNegativeInteger | read-only | current |
| pduInputPowerFactor OBJECT-TYPE The input power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf. | 1.3.6.1.4.1.534.6.6.4.1.1.2.4 | Integer32 (-100..100) | read-only | current |
| pduGroundCurrent OBJECT-TYPE The present current in the PDU's ground phase. Ideally, this value stays at 0. | 1.3.6.1.4.1.534.6.6.4.1.1.2.5 | NonNegativeInteger | read-only | current |
| pduInputVoltageUnits OBJECT-TYPE Indicates whether the pduInputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'. | 1.3.6.1.4.1.534.6.6.4.1.1.2.6 | DisplayString (SIZE(0..31)) | read-only | current |
| pduInputNumPhases OBJECT-TYPE The number of input phases for this PDU. This variable indicates the number of rows in the pduInputTable. | 1.3.6.1.4.1.534.6.6.4.1.1.2.7 | PositiveInteger | read-only | current |
| pduInputTable OBJECT-TYPE A list of input table entries. The number of entries is given by the value of pduInputNumPhases. | 1.3.6.1.4.1.534.6.6.4.1.1.2.8 | not-accessible | current | |
| pduInputEntry OBJECT-TYPE An entry containing information applicable to a particular input phase. | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1 | not-accessible | current | |
| pduInputPhaseIndex OBJECT-TYPE The input line identifier. | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.1 | PositiveInteger | not-accessible | current |
| pduInputPhaseVoltage OBJECT-TYPE The present input voltage for this phase. | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.2 | NonNegativeInteger | read-only | current |
| pduInputPhaseCurrent OBJECT-TYPE The present input current for this phase. | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.3 | NonNegativeInteger | read-only | current |
| pduInputPhasePercentLoad OBJECT-TYPE The percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduInputPhaseCurrent to the rated input current. | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.4 | Integer32 (0..200) | read-only | current |
| pduOutput OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.6.4.1.1.3 | |||
| pduOutputKilowattHours OBJECT-TYPE The accumulated kilowatt-hour value for the full PDU system since the last reset. | 1.3.6.1.4.1.534.6.6.4.1.1.3.1 | NonNegativeInteger | read-only | current |
| pduOutputVA OBJECT-TYPE The present VA output of the full PDU system. | 1.3.6.1.4.1.534.6.6.4.1.1.3.2 | NonNegativeInteger | read-only | current |
| pduOutputPower OBJECT-TYPE The present output power of the full PDU system. | 1.3.6.1.4.1.534.6.6.4.1.1.3.3 | NonNegativeInteger | read-only | current |
| pduOutputPowerFactor OBJECT-TYPE The output power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf. | 1.3.6.1.4.1.534.6.6.4.1.1.3.4 | Integer32 (-100..100) | read-only | current |
| pduNeutralCurrent OBJECT-TYPE The present current in the PDU's output neutral phase. Ideally, this value stays at 0. | 1.3.6.1.4.1.534.6.6.4.1.1.3.5 | NonNegativeInteger | read-only | current |
| pduRatedOutputCurrent OBJECT-TYPE The rated current value for one PDU Output phase at full load (100%). | 1.3.6.1.4.1.534.6.6.4.1.1.3.6 | PositiveInteger | read-only | current |
| pduOutputVoltageUnits OBJECT-TYPE Indicates whether the pduOutputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'. | 1.3.6.1.4.1.534.6.6.4.1.1.3.7 | DisplayString (SIZE(0..31)) | read-only | current |
| pduOutputNumPhases OBJECT-TYPE The number of output phases for this PDU. This variable indicates the number of rows in the pduOutputTable. | 1.3.6.1.4.1.534.6.6.4.1.1.3.8 | PositiveInteger | read-only | current |
| pduOutputTable OBJECT-TYPE A list of output table entries. The number of entries is given by the value of pduOutputNumPhases. | 1.3.6.1.4.1.534.6.6.4.1.1.3.9 | not-accessible | current | |
| pduOutputEntry OBJECT-TYPE An entry containing information applicable to a particular output phase. | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1 | not-accessible | current | |
| pduOutputPhaseIndex OBJECT-TYPE The output line identifier. | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.1 | PositiveInteger | not-accessible | current |
| pduOutputPhaseVoltage OBJECT-TYPE The present output voltage for this phase. | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.2 | NonNegativeInteger | read-only | current |
| pduOutputPhaseCurrent OBJECT-TYPE The present output current for this phase. | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.3 | NonNegativeInteger | read-only | current |
| pduOutputPhasePercentLoad OBJECT-TYPE The percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduOutputPhaseCurrent to pduRatedOutputCurrent. | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.4 | Integer32 (0..200) | read-only | current |
| pduPanel OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.6.4.1.2 | |||
| panelRatingsTable OBJECT-TYPE A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels. | 1.3.6.1.4.1.534.6.6.4.1.2.1 | not-accessible | current | |
| panelRatingsEntry OBJECT-TYPE An entry containing information applicable to a particular output phase. | 1.3.6.1.4.1.534.6.6.4.1.2.1.1 | not-accessible | current | |
| panelNumber OBJECT-TYPE Index for the Panel Ratings and Meters tables. Corresponds to the physical panel number in the PDU system. There must be a #1. The maximum value is 16. Panels are not required to be numbered sequentially. | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.1 | PositiveInteger | not-accessible | current |
| panelRatedVoltage OBJECT-TYPE The nominal Voltage of this panel (as distributed to the breakers or subfeeds). This is either Line-to-Line or Line-to-Neutral, as indicated in panelVoltageUnits. | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.2 | PositiveInteger | read-only | current |
| panelRatedBreakerCurrent OBJECT-TYPE The rated current value for one panel (input) phase at full load (100%). This is set by the panel's input breaker; if there is no input breaker for this panel, then this object is not accessible. | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.3 | PositiveInteger | read-only | current |
| panelNumPhases OBJECT-TYPE The number of lines (phases) for this panel. | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.4 | PositiveInteger | read-only | current |
| panelNumBreakers OBJECT-TYPE The number of breakers contained in this panel. This determines the number of rows found in the breaker tables. | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.5 | PositiveInteger | read-only | current |
| panelVoltageUnits OBJECT-TYPE Indicates whether the panelPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'. | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.6 | DisplayString (SIZE(0..31)) | read-only | current |
| panelMetersTable OBJECT-TYPE A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels. | 1.3.6.1.4.1.534.6.6.4.1.2.2 | not-accessible | current | |
| panelMetersEntry OBJECT-TYPE An entry containing meter readings applicable to a particular panel. | 1.3.6.1.4.1.534.6.6.4.1.2.2.1 | not-accessible | current | |
| panelTotalKilowattHours OBJECT-TYPE The accumulated kilowatt-hours for this panel since it was commissioned and put into service, or since the last reset of the system KHW measures. | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.1 | NonNegativeInteger | read-only | current |
| panelMonthlyKilowattHours OBJECT-TYPE The accumulated kilowatt-hours for this panel since the beginning of this calendar month, or since the last reset of the system KHW measures. | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.2 | NonNegativeInteger | read-only | current |
| panelYtdKilowattHours OBJECT-TYPE The accumulated kilowatt-hours for this panel since the beginning of this calendar year (YTD), or since the last reset of the system KHW measures. | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.3 | NonNegativeInteger | read-only | current |
| panelVA OBJECT-TYPE The present VA (input) demand of this panel. | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.4 | NonNegativeInteger | read-only | current |
| panelPower OBJECT-TYPE The present power (input) demand of this panel. | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.5 | NonNegativeInteger | read-only | current |
| panelPowerFactor OBJECT-TYPE The input power factor for this panel. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf. | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.6 | Integer32 (-100..100) | read-only | current |
| panelNeutralCurrent OBJECT-TYPE The present neutral phase current for this panel. | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.7 | NonNegativeInteger | read-only | current |
| panelPhaseMetersTable OBJECT-TYPE A sparsely populated (ie, not sequentially panel numbered) table of ratings for each panel. The number of entries is given by the sum of panelNumPhases for pduNumPanels. | 1.3.6.1.4.1.534.6.6.4.1.2.3 | not-accessible | current | |
| panelPhaseMetersEntry OBJECT-TYPE An entry containing meter readings applicable to a particular phase of a particular panel. | 1.3.6.1.4.1.534.6.6.4.1.2.3.1 | not-accessible | current | |
| panelPhaseIndex OBJECT-TYPE The line or phase identifier. | 1.3.6.1.4.1.534.6.6.4.1.2.3.1.1 | PositiveInteger | not-accessible | current |
| panelPhaseVoltage OBJECT-TYPE The present voltage for this phase. | 1.3.6.1.4.1.534.6.6.4.1.2.3.1.2 | NonNegativeInteger | read-only | current |
| panelPhaseCurrent OBJECT-TYPE The present current for this phase. | 1.3.6.1.4.1.534.6.6.4.1.2.3.1.3 | NonNegativeInteger | read-only | current |
| panelPhasePercentLoad OBJECT-TYPE The percentage of the panel power capacity presently being used on this line, normally based on the ratio of panelPhaseCurrent to the rated phase current. | 1.3.6.1.4.1.534.6.6.4.1.2.3.1.4 | Integer32 (0..200) | read-only | current |
| pduBreaker OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.6.4.1.3 | |||
| breakerRatingsTable OBJECT-TYPE A sparsely populated (ie, not sequentially numbered) table of ratings and fixed values for each breaker. The number of entries is given by the value of panelNumBreakers for this panel. | 1.3.6.1.4.1.534.6.6.4.1.3.1 | not-accessible | current | |
| breakerRatingsEntry OBJECT-TYPE An entry containing information applicable to a particular output phase. | 1.3.6.1.4.1.534.6.6.4.1.3.1.1 | not-accessible | current | |
| breakerNumber OBJECT-TYPE Index for the Breaker Ratings and Meters tables. Corresponds to the physical breaker number in the PDU system. Breakers are not required to be numbered sequentially. | 1.3.6.1.4.1.534.6.6.4.1.3.1.1.1 | PositiveInteger | not-accessible | current |
| breakerName OBJECT-TYPE Name given by the administrator to identify this breaker. | 1.3.6.1.4.1.534.6.6.4.1.3.1.1.2 | DisplayString (SIZE(0..31)) | read-only | current |
| breakerRatedCurrent OBJECT-TYPE The rated current value of this breaker (for one phase) at full load (100%). | 1.3.6.1.4.1.534.6.6.4.1.3.1.1.3 | PositiveInteger | read-only | current |
| breakerNumPhases OBJECT-TYPE The number of lines (phases) for this breaker. | 1.3.6.1.4.1.534.6.6.4.1.3.1.1.4 | PositiveInteger | read-only | current |
| breakerMetersTable OBJECT-TYPE A sparsely populated (ie, not sequentially numbered) table of ratings for each breaker. The number of entries is given by the value of panelNumBreakers for this panel. | 1.3.6.1.4.1.534.6.6.4.1.3.2 | not-accessible | current | |
| breakerMetersEntry OBJECT-TYPE An entry containing meter readings applicable to a particular breaker. | 1.3.6.1.4.1.534.6.6.4.1.3.2.1 | not-accessible | current | |
| breakerTotalKilowattHours OBJECT-TYPE The accumulated kilowatt-hours for this breaker since it was commissioned and put into service, or since the last reset of the panel KHW measures. | 1.3.6.1.4.1.534.6.6.4.1.3.2.1.1 | NonNegativeInteger | read-only | current |
| breakerMonthlyKilowattHours OBJECT-TYPE The accumulated kilowatt-hours for this breaker since the beginning of this calendar month, or since the last reset of the panel KHW measures. | 1.3.6.1.4.1.534.6.6.4.1.3.2.1.2 | NonNegativeInteger | read-only | current |
| breakerYtdKilowattHours OBJECT-TYPE The accumulated kilowatt-hours for this breaker since the beginning of this calendar year (YTD), or since the last reset of the panel KHW measures. | 1.3.6.1.4.1.534.6.6.4.1.3.2.1.3 | NonNegativeInteger | read-only | current |
| breakerPhaseMetersTable OBJECT-TYPE A sparsely populated (ie, not sequentially breaker numbered) table of ratings for each breaker. The number of entries is given by the sum of breakerNumPhases for panelNumBreakers for all panels (pduNumPanels). | 1.3.6.1.4.1.534.6.6.4.1.3.3 | not-accessible | current | |
| breakerPhaseMetersEntry OBJECT-TYPE An entry containing meter readings applicable to a particular phase of a particular breaker on a particular panel. | 1.3.6.1.4.1.534.6.6.4.1.3.3.1 | not-accessible | current | |
| breakerPhaseIndex OBJECT-TYPE The line or phase identifier. | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.1 | PositiveInteger | not-accessible | current |
| breakerPhaseVA OBJECT-TYPE The present VA (input) demand of this phase on this breaker. | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.2 | NonNegativeInteger | read-only | current |
| breakerPhasePower OBJECT-TYPE The present power (input) demand of phase on this breaker. | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.3 | NonNegativeInteger | read-only | current |
| breakerPhasePowerFactor OBJECT-TYPE The input power factor for this phase on this breaker. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf. | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.4 | Integer32 (-100..100) | read-only | current |
| breakerPhaseCurrent OBJECT-TYPE The present current for this phase of this breaker. | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.5 | NonNegativeInteger | read-only | current |
| breakerPhasePercentLoad OBJECT-TYPE The percentage of the breaker power capacity presently being used on this line, normally based on the ratio of breakerPhaseCurrent to the breakerRatedCurrent. | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.6 | Integer32 (0..200) | read-only | current |
| eatonPduConformance OBJECT-IDENTITY | 1.3.6.1.4.1.534.6.6.4.2 |
Conformance
| Name | OID | Status |
|---|---|---|
| pduNameplateGroup OBJECT-GROUP The pduNameplate subgroup objects. | 1.3.6.1.4.1.534.6.6.4.2.1 | current |
| pduInputGroup OBJECT-GROUP The pduInput Meters subgroup objects. | 1.3.6.1.4.1.534.6.6.4.2.2 | current |
| pduOutputGroup OBJECT-GROUP The pduOutput Meters subgroup objects. | 1.3.6.1.4.1.534.6.6.4.2.3 | current |
| panelRatingsGroup OBJECT-GROUP The panelRatings table objects. | 1.3.6.1.4.1.534.6.6.4.2.4 | current |
| panelMetersGroup OBJECT-GROUP The BreakerMeters Table objects. | 1.3.6.1.4.1.534.6.6.4.2.5 | current |
| panelPhaseMetersGroup OBJECT-GROUP The BreakerPhaseMeters Table objects. | 1.3.6.1.4.1.534.6.6.4.2.6 | current |
| breakerRatingsGroup OBJECT-GROUP The breakerRatings table objects. | 1.3.6.1.4.1.534.6.6.4.2.7 | current |
| breakerMetersGroup OBJECT-GROUP The breakerMeters table objects. | 1.3.6.1.4.1.534.6.6.4.2.8 | current |
| breakerPhaseMetersGroup OBJECT-GROUP The breakerPhaseMeters table objects. | 1.3.6.1.4.1.534.6.6.4.2.9 | current |
| pdu3phaseCompliance MODULE-COMPLIANCE The compliance statement for a normal 3-phase PDU, which implements the full set of objects. | 1.3.6.1.4.1.534.6.6.4.2.10 | current |