MIBs Depot

EATON-EPDU-MIB

Registered at
1.3.6.1.4.1.534.6.6.7
Last updated
2018-05-30 15:00
Organization
Eaton Corporation
Revisions
2018-05-30 15:00, 2017-09-11 12:00, 2017-04-20 12:00, 2015-02-23 12:00, 2014-09-29 12:00, 2013-12-18 12:00, 2013-09-02 12:00, 2013-05-29 12:00, 2013-02-21 12:00, 2011-11-21 12:00, 2011-10-24 12:00, 2011-02-07 15:29
Namespace
eaton
Source file
EATON-EPDU-MIB
Digest
sha256:c89143c92fe221e22fa80b79e5d1c2ed2979ff068e77ff609a9eea913925a68c

Description

The MIB module for Eaton ePDUs (Enclosure Power Distribution Units).

Contact

www.eaton.com/epdu

Imports

FromSymbols
EATON-OIDSpduAgent
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
SNMPv2-SMICounter32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, enterprises, iso
SNMPv2-TCDateAndTime, DisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

EATON-EPDU-MIB
EATON-OIDS
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Textual conventions

NameOIDSyntaxAccessStatus
UnixTimeStamp
TEXTUAL-CONVENTION
Unix time stamp. Measured in seconds since January 1, 1970.
current

Objects

NameOIDSyntaxAccessStatus
eaton
OBJECT-IDENTITY
1.3.6.1.4.1.534
products
OBJECT-IDENTITY
1.3.6.1.4.1.534.6
pduAgent
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6
notifications
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.7.0
units
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.7.1
unitsPresent
OBJECT-TYPE
Each unit is identified by a Strapping Index. This object returns a comma-delimited list of the Strapping Indexes of all units present in the strapping group. For example, if units 0, 1, 5, and 7 are present, this value will be '0,1,5,7'. For units that do not support strapping, a Strapping Index of '0' is assumed.
1.3.6.1.4.1.534.6.6.7.1.1DisplayStringread-onlycurrent
unitTable
OBJECT-TYPE
A list of units. In most cases this list will only contain one entry. However, some units have a 'strapping' feature which allow units to be daisy-chained together such that all of them can be accessed through the SNMP interface of the master. If strapping is enabled, the strapping indexes of the units that can be accessed will be listed in the unitsPresent object.
1.3.6.1.4.1.534.6.6.7.1.2not-accessiblecurrent
unitEntry
OBJECT-TYPE
An entry for a PDU.
1.3.6.1.4.1.534.6.6.7.1.2.1not-accessiblecurrent
strappingIndex
OBJECT-TYPE
For units that support 'strapping' functionality, this will be a unique value for each unit. If units do not support 'strapping', this will always be '0'.
1.3.6.1.4.1.534.6.6.7.1.2.1.1Integer32 (0..23)accessible-for-notifycurrent
productName
OBJECT-TYPE
Name of the product.
1.3.6.1.4.1.534.6.6.7.1.2.1.2OCTET STRING (SIZE(1..127))read-onlycurrent
partNumber
OBJECT-TYPE
Part number of the unit.
1.3.6.1.4.1.534.6.6.7.1.2.1.3OCTET STRINGread-onlycurrent
serialNumber
OBJECT-TYPE
Serial number of the unit.
1.3.6.1.4.1.534.6.6.7.1.2.1.4OCTET STRINGread-onlycurrent
firmwareVersion
OBJECT-TYPE
Firmware version.
1.3.6.1.4.1.534.6.6.7.1.2.1.5OCTET STRINGread-onlycurrent
unitName
OBJECT-TYPE
Descriptive name for the unit.
1.3.6.1.4.1.534.6.6.7.1.2.1.6OCTET STRING (SIZE(1..63))read-writecurrent
lcdControl
OBJECT-TYPE
Control the local LCD.
1.3.6.1.4.1.534.6.6.7.1.2.1.7INTEGER {notApplicable(0), lcdScreenOff(1), lcdKeyLock(2), lcdScreenOffAndKeyLock(3)}read-writecurrent
clockValue
OBJECT-TYPE
Clock value. This could be from either a real-time clock (in which case it is likely writeable) or from a time server via NTP (probably read-only).
1.3.6.1.4.1.534.6.6.7.1.2.1.8DateAndTimeread-writecurrent
temperatureScale
OBJECT-TYPE
Scale used to return temperature objects.
1.3.6.1.4.1.534.6.6.7.1.2.1.9INTEGER {celsius(0), fahrenheit(1)}read-writecurrent
unitType
OBJECT-TYPE
Technical capabilities of the PDU. Functionality is as follows: Monitored (MI) - input and usually section/group monitoring. Advanced Monitored (AM) - input, section/group, and outlet monitoring. Switched (SW) - input and section/group monitoring, outlet switching. Basic (BA) - no communication card. Inline Monitored (IL) - input and usually one section/group monitoring.
1.3.6.1.4.1.534.6.6.7.1.2.1.10INTEGER {unknown(0), switched(1), advancedMonitored(2), managed(3), monitored(4), basic(5), inlineMonitored(6)}read-onlycurrent
systemType
OBJECT-TYPE
Architecture of the ePDU electronic.
1.3.6.1.4.1.534.6.6.7.1.2.1.11INTEGER {unknown(0), g3ePDU(1), g3HDePDU(2)}read-onlycurrent
inputCount
OBJECT-TYPE
Number of inputs on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.20Integer32read-onlycurrent
groupCount
OBJECT-TYPE
Number of groups on this ePDU. Groups include breakers, outlet sections, and user-defined groups.
1.3.6.1.4.1.534.6.6.7.1.2.1.21Integer32read-onlycurrent
outletCount
OBJECT-TYPE
Number of outlets on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.22Integer32read-onlycurrent
temperatureCount
OBJECT-TYPE
Max number of temperature measurements on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.23Integer32read-onlycurrent
humidityCount
OBJECT-TYPE
Max number of humidity measurements on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.24Integer32read-onlycurrent
contactCount
OBJECT-TYPE
Max number of contact sensors on this ePDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.25Integer32read-onlycurrent
communicationStatus
OBJECT-TYPE
Status of the internal communication with the PDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.30INTEGER {good(0), communicationLost(1)}read-onlycurrent
internalStatus
OBJECT-TYPE
Status of the internal failure inside the PDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.31INTEGER {good(0), internalFailure(1)}read-onlycurrent
strappingStatus
OBJECT-TYPE
Status of the external communication with a strapping unit.
1.3.6.1.4.1.534.6.6.7.1.2.1.32INTEGER {good(0), communicationLost(1)}read-onlycurrent
userName
OBJECT-TYPE
Username used to log into the PDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.40OCTET STRING (SIZE(0..31))accessible-for-notifycurrent
commInterface
OBJECT-TYPE
Communications interface used to log into the PDU.
1.3.6.1.4.1.534.6.6.7.1.2.1.41INTEGER {serial(0), usb(1), telnet(2), web(3), ftp(4), xml(5)}accessible-for-notifycurrent
unitControlTable
OBJECT-TYPE
A list of units that have controllable outlets.
1.3.6.1.4.1.534.6.6.7.1.3not-accessiblecurrent
unitControlEntry
OBJECT-TYPE
An entry for a PDU which has controllable outlets.
1.3.6.1.4.1.534.6.6.7.1.3.1not-accessiblecurrent
unitControlOffCmd
OBJECT-TYPE
Unit-level outlet control command. Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 : Cancel a pending unit-level Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object.
1.3.6.1.4.1.534.6.6.7.1.3.1.2Integer32 (-1..99999)read-writecurrent
unitControlOnCmd
OBJECT-TYPE
Unit-level outlet control command. Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value. 0-n : Time in seconds until the outlet Sequence On command is issued -1 : Cancel a pending unit-level On command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object.
1.3.6.1.4.1.534.6.6.7.1.3.1.3Integer32 (-1..99999)read-writecurrent
inputs
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.7.3
inputTable
OBJECT-TYPE
List of inputs to the PDU.
1.3.6.1.4.1.534.6.6.7.3.1not-accessiblecurrent
inputEntry
OBJECT-TYPE
An entry for a particular input.
1.3.6.1.4.1.534.6.6.7.3.1.1not-accessiblecurrent
inputIndex
OBJECT-TYPE
A unique value for each input. Its value ranges from 1 to inputCount.
1.3.6.1.4.1.534.6.6.7.3.1.1.1Integer32 (1..2)accessible-for-notifycurrent
inputType
OBJECT-TYPE
Type of input - single phase, split phase, three phase delta, or three phase wye.
1.3.6.1.4.1.534.6.6.7.3.1.1.2INTEGER {singlePhase(1), splitPhase(2), threePhaseDelta(3), threePhaseWye(4)}read-onlycurrent
inputFrequency
OBJECT-TYPE
Units are 0.1 Hz; divide by ten to get Hz.
1.3.6.1.4.1.534.6.6.7.3.1.1.3Integer32read-onlycurrent
inputFrequencyStatus
OBJECT-TYPE
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
1.3.6.1.4.1.534.6.6.7.3.1.1.4INTEGER {good(0), outOfRange(1)}read-onlycurrent
inputVoltageCount
OBJECT-TYPE
Number of input voltage measurements on this ePDU.
1.3.6.1.4.1.534.6.6.7.3.1.1.5Integer32read-onlycurrent
inputCurrentCount
OBJECT-TYPE
Number of input current measurements on this ePDU.
1.3.6.1.4.1.534.6.6.7.3.1.1.6Integer32read-onlycurrent
inputPowerCount
OBJECT-TYPE
Number of rows in the inputPowerTable.
1.3.6.1.4.1.534.6.6.7.3.1.1.7Integer32read-onlycurrent
inputPlugType
OBJECT-TYPE
Identifies which plug is on the input.
1.3.6.1.4.1.534.6.6.7.3.1.1.8INTEGER {other1Phase(100), iecC14Inlet(101), iecC20Inlet(102), iec316P6(103), iec332P6(104), iec360P6(105), iecC14Plug(106), iecC20Plug(107), nema515(120), nemaL515(121), nema520(122), nemaL520(123), nema615(124), nemaL615(125), nemaL530(126), nema620(127), nemaL620(128), nemaL630(129), cs8265(130), french(150), schuko(151), uk(152), other2Phase(200), nemaL1420(201), nemaL1430(202), other3Phase(300), iec516P6(301), iec460P9(302), iec560P9(303), iec532P6(304), iec563P6(306), nemaL1520(320), nemaL2120(321), nemaL1530(322), nemaL2130(323), cs8365(324), nemaL2220(325), nemaL2230(326), bladeUps208V(350), bladeUps400V(351)}read-onlycurrent
inputFeedColor
OBJECT-TYPE
Color code of the input feed.
1.3.6.1.4.1.534.6.6.7.3.1.1.9Unsigned32 (0..16777215)read-writecurrent
inputFeedName
OBJECT-TYPE
A descriptive name for the input.
1.3.6.1.4.1.534.6.6.7.3.1.1.10OCTET STRING (SIZE(1..31))read-writecurrent
inputVoltageTable
OBJECT-TYPE
A list of input voltage measurements. The number of entries is given by inputVoltageCount.
1.3.6.1.4.1.534.6.6.7.3.2not-accessiblecurrent
inputVoltageEntry
OBJECT-TYPE
An entry for a particular input voltage measurement.
1.3.6.1.4.1.534.6.6.7.3.2.1not-accessiblecurrent
inputVoltageIndex
OBJECT-TYPE
A unique value for each input voltage measurement. Its value ranges from 1 to inputVoltageCount.
1.3.6.1.4.1.534.6.6.7.3.2.1.1Integer32 (1..3)accessible-for-notifycurrent
inputVoltageMeasType
OBJECT-TYPE
Value indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1.
1.3.6.1.4.1.534.6.6.7.3.2.1.2INTEGER {singlePhase(1), phase1toN(2), phase2toN(3), phase3toN(4), phase1to2(5), phase2to3(6), phase3to1(7)}read-onlycurrent
inputVoltage
OBJECT-TYPE
An input voltage measurement value. Units are millivolts.
1.3.6.1.4.1.534.6.6.7.3.2.1.3Integer32read-onlycurrent
inputVoltageThStatus
OBJECT-TYPE
Status of the measured input voltage relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.3.2.1.4INTEGER {good(0), lowWarning(1), lowCritical(2), highWarning(3), highCritical(4)}read-onlycurrent
inputVoltageThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.2.1.5Integer32 (-1..500000)read-writecurrent
inputVoltageThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.2.1.6Integer32 (-1..500000)read-writecurrent
inputVoltageThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.2.1.7Integer32 (-1..500000)read-writecurrent
inputVoltageThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.2.1.8Integer32 (-1..500000)read-writecurrent
inputCurrentTable
OBJECT-TYPE
A list of input current measurements. The number of entries is given by inputCurrentCount.
1.3.6.1.4.1.534.6.6.7.3.3not-accessiblecurrent
inputCurrentEntry
OBJECT-TYPE
An entry for a particular input current measurement.
1.3.6.1.4.1.534.6.6.7.3.3.1not-accessiblecurrent
inputCurrentIndex
OBJECT-TYPE
A unique value for each input current measurement. Its value ranges from 1 to inputCurrentCount.
1.3.6.1.4.1.534.6.6.7.3.3.1.1Integer32 (1..4)accessible-for-notifycurrent
inputCurrentMeasType
OBJECT-TYPE
Which input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.
1.3.6.1.4.1.534.6.6.7.3.3.1.2INTEGER {singlePhase(1), neutral(2), phase1(3), phase2(4), phase3(5)}read-onlycurrent
inputCurrentCapacity
OBJECT-TYPE
Rated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Units are milliamps.
1.3.6.1.4.1.534.6.6.7.3.3.1.3Integer32read-onlycurrent
inputCurrent
OBJECT-TYPE
An input current measurement value. Units are milliamps.
1.3.6.1.4.1.534.6.6.7.3.3.1.4Integer32read-onlycurrent
inputCurrentThStatus
OBJECT-TYPE
Status of the measured input current relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.3.3.1.5INTEGER {good(0), lowWarning(1), lowCritical(2), highWarning(3), highCritical(4)}read-onlycurrent
inputCurrentThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.6Integer32 (-1..100000)read-writecurrent
inputCurrentThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.7Integer32 (-1..100000)read-writecurrent
inputCurrentThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.8Integer32 (-1..100000)read-writecurrent
inputCurrentThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.9Integer32 (-1..100000)read-writecurrent
inputCurrentCrestFactor
OBJECT-TYPE
Current crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.10Integer32read-onlycurrent
inputCurrentPercentLoad
OBJECT-TYPE
Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.3.1.11Integer32read-onlycurrent
inputPhaseDesignator
OBJECT-TYPE
Alphanumeric physical name for the input.
1.3.6.1.4.1.534.6.6.7.3.3.1.12DisplayString (SIZE(2..4))read-onlycurrent
inputPowerTable
OBJECT-TYPE
A list of input power measurements. The number of entries is given by inputPowerCount.
1.3.6.1.4.1.534.6.6.7.3.4not-accessiblecurrent
inputPowerEntry
OBJECT-TYPE
An entry for an input power measurement.
1.3.6.1.4.1.534.6.6.7.3.4.1not-accessiblecurrent
inputPowerIndex
OBJECT-TYPE
A unique value for each input power measurement. Its value ranges from 1 to inputPowerCount.
1.3.6.1.4.1.534.6.6.7.3.4.1.1Integer32 (1..12)not-accessiblecurrent
inputPowerMeasType
OBJECT-TYPE
Value indicates what is being measured in this table row.
1.3.6.1.4.1.534.6.6.7.3.4.1.2INTEGER {unknown(0), phase1(1), phase2(2), phase3(3), total(4)}read-onlycurrent
inputVA
OBJECT-TYPE
An input VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.4.1.3Integer32read-onlycurrent
inputWatts
OBJECT-TYPE
An input Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.4.1.4Integer32read-onlycurrent
inputWh
OBJECT-TYPE
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well.
1.3.6.1.4.1.534.6.6.7.3.4.1.5Unsigned32 (0..4294967295)read-writecurrent
inputWhTimer
OBJECT-TYPE
Timestamp of when input Watt-hours (inputWh) was last reset.
1.3.6.1.4.1.534.6.6.7.3.4.1.6UnixTimeStampread-onlycurrent
inputPowerFactor
OBJECT-TYPE
An input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.4.1.7Integer32read-onlycurrent
inputVAR
OBJECT-TYPE
An input VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.4.1.8Integer32read-onlycurrent
inputTotalPowerTable
OBJECT-TYPE
A list of total input power measurements.
1.3.6.1.4.1.534.6.6.7.3.5not-accessiblecurrent
inputTotalPowerEntry
OBJECT-TYPE
An entry for a total input power measurement.
1.3.6.1.4.1.534.6.6.7.3.5.1not-accessiblecurrent
inputTotalVA
OBJECT-TYPE
An input VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.5.1.3Integer32read-onlycurrent
inputTotalWatts
OBJECT-TYPE
An input Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.5.1.4Integer32read-onlycurrent
inputTotalWh
OBJECT-TYPE
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well.
1.3.6.1.4.1.534.6.6.7.3.5.1.5Unsigned32 (0..4294967295)read-writecurrent
inputTotalWhTimer
OBJECT-TYPE
Timestamp of when input Watt-hours (inputWh) was last reset.
1.3.6.1.4.1.534.6.6.7.3.5.1.6UnixTimeStampread-onlycurrent
inputTotalPowerFactor
OBJECT-TYPE
An input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.5.1.7Integer32read-onlycurrent
inputTotalVAR
OBJECT-TYPE
An input VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.3.5.1.8Integer32read-onlycurrent
inputPowerCapacity
OBJECT-TYPE
Typical power capacity of the input. A negative value indicates that the hardware current capacity is unknown.
1.3.6.1.4.1.534.6.6.7.3.5.1.9Integer32read-onlycurrent
groups
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.7.5
groupTable
OBJECT-TYPE
A list of groups. The number of entries is given by groupCount.
1.3.6.1.4.1.534.6.6.7.5.1not-accessiblecurrent
groupEntry
OBJECT-TYPE
An entry for a particular group.
1.3.6.1.4.1.534.6.6.7.5.1.1not-accessiblecurrent
groupIndex
OBJECT-TYPE
A unique value for each group. Its value ranges from 1 to groupCount.
1.3.6.1.4.1.534.6.6.7.5.1.1.1Integer32 (1..64)accessible-for-notifycurrent
groupID
OBJECT-TYPE
Alphanumeric designator for the group. This value may be written on the face of the unit.
1.3.6.1.4.1.534.6.6.7.5.1.1.2DisplayString (SIZE(2..4))read-onlycurrent
groupName
OBJECT-TYPE
A descriptive name for the group.
1.3.6.1.4.1.534.6.6.7.5.1.1.3OCTET STRING (SIZE(1..31))read-writecurrent
groupType
OBJECT-TYPE
The type of the group.
1.3.6.1.4.1.534.6.6.7.5.1.1.4INTEGER {unknown(0), breaker1pole(1), breaker2pole(2), breaker3pole(3), outletSection(4), userDefined(5)}read-onlycurrent
groupBreakerStatus
OBJECT-TYPE
Only applicable to breaker-groups. Indicates whether a breaker is turned off or on.
1.3.6.1.4.1.534.6.6.7.5.1.1.5INTEGER {notApplicable(0), breakerOn(1), breakerOff(2)}read-onlycurrent
groupChildCount
OBJECT-TYPE
Number of children for this group.
1.3.6.1.4.1.534.6.6.7.5.1.1.6Integer32read-onlycurrent
groupColor
OBJECT-TYPE
Background color code of the group. Color codes are decimal values.
1.3.6.1.4.1.534.6.6.7.5.1.1.7Unsigned32 (0..16777215)read-onlycurrent
groupDesignator
OBJECT-TYPE
Alphanumeric physical name for the group. This value may be written on the face of the unit.
1.3.6.1.4.1.534.6.6.7.5.1.1.8DisplayString (SIZE(2..4))read-onlycurrent
groupInputIndex
OBJECT-TYPE
Identifies the input on which the group is connected.
1.3.6.1.4.1.534.6.6.7.5.1.1.9Integer32read-onlycurrent
groupChildTable
OBJECT-TYPE
A list of children for this group. For example, this table will link to all of the outlets that are contained in a particular group.
1.3.6.1.4.1.534.6.6.7.5.2not-accessiblecurrent
groupChildEntry
OBJECT-TYPE
An entry for a particular child.
1.3.6.1.4.1.534.6.6.7.5.2.1not-accessiblecurrent
groupChildIndex
OBJECT-TYPE
A unique value for each child. Its value ranges from 1 to groupChildCount.
1.3.6.1.4.1.534.6.6.7.5.2.1.1Integer32 (1..32)not-accessiblecurrent
groupChildType
OBJECT-TYPE
The type of the child.
1.3.6.1.4.1.534.6.6.7.5.2.1.2INTEGER {unknown(0), section(2), custom(3), outlet(4)}read-onlycurrent
groupChildOID
OBJECT-TYPE
Object ID of a child object.
1.3.6.1.4.1.534.6.6.7.5.2.1.3OBJECT IDENTIFIERread-onlycurrent
groupVoltageTable
OBJECT-TYPE
A list of group voltage measurements. There can be only one voltage measurement for each group.
1.3.6.1.4.1.534.6.6.7.5.3not-accessiblecurrent
groupVoltageEntry
OBJECT-TYPE
An entry for a group voltage measurement.
1.3.6.1.4.1.534.6.6.7.5.3.1not-accessiblecurrent
groupVoltageMeasType
OBJECT-TYPE
Value indicates what voltage is being measured in this table row.
1.3.6.1.4.1.534.6.6.7.5.3.1.2INTEGER {unknown(0), singlePhase(1), phase1toN(2), phase2toN(3), phase3toN(4), phase1to2(5), phase2to3(6), phase3to1(7)}read-onlycurrent
groupVoltage
OBJECT-TYPE
Units are millivolts.
1.3.6.1.4.1.534.6.6.7.5.3.1.3Integer32read-onlycurrent
groupVoltageThStatus
OBJECT-TYPE
Status of the measured group voltage relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.5.3.1.4INTEGER {good(0), lowWarning(1), lowCritical(2), highWarning(3), highCritical(4)}read-onlycurrent
groupVoltageThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.3.1.5Integer32 (-1..500000)read-writecurrent
groupVoltageThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.3.1.6Integer32 (-1..500000)read-writecurrent
groupVoltageThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.3.1.7Integer32 (-1..500000)read-writecurrent
groupVoltageThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.3.1.8Integer32 (-1..500000)read-writecurrent
groupCurrentTable
OBJECT-TYPE
A list of group current measurements. There can be only one current measurement for each group.
1.3.6.1.4.1.534.6.6.7.5.4not-accessiblecurrent
groupCurrentEntry
OBJECT-TYPE
An entry for a group current measurement.
1.3.6.1.4.1.534.6.6.7.5.4.1not-accessiblecurrent
groupCurrentCapacity
OBJECT-TYPE
Rated current capacity of the group. Units are milliamps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups).
1.3.6.1.4.1.534.6.6.7.5.4.1.2Integer32read-onlycurrent
groupCurrent
OBJECT-TYPE
A group current measurement value. Units are milliamps.
1.3.6.1.4.1.534.6.6.7.5.4.1.3Integer32read-onlycurrent
groupCurrentThStatus
OBJECT-TYPE
Status of the measured group current relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.5.4.1.4INTEGER {good(0), lowWarning(1), lowCritical(2), highWarning(3), highCritical(4)}read-onlycurrent
groupCurrentThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.5Integer32 (-1..100000)read-writecurrent
groupCurrentThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.6Integer32 (-1..100000)read-writecurrent
groupCurrentThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.7Integer32 (-1..100000)read-writecurrent
groupCurrentThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.8Integer32 (-1..100000)read-writecurrent
groupCurrentCrestFactor
OBJECT-TYPE
Current crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.9Integer32read-onlycurrent
groupCurrentPercentLoad
OBJECT-TYPE
Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.4.1.10Integer32read-onlycurrent
groupPowerTable
OBJECT-TYPE
A list of group power measurements. There can be only one power measurement for each group.
1.3.6.1.4.1.534.6.6.7.5.5not-accessiblecurrent
groupPowerEntry
OBJECT-TYPE
An entry for a group power measurement.
1.3.6.1.4.1.534.6.6.7.5.5.1not-accessiblecurrent
groupVA
OBJECT-TYPE
A group VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.5.1.2Integer32read-onlycurrent
groupWatts
OBJECT-TYPE
A group Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.5.1.3Integer32read-onlycurrent
groupWh
OBJECT-TYPE
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well.
1.3.6.1.4.1.534.6.6.7.5.5.1.4Unsigned32 (0..4294967295)read-writecurrent
groupWhTimer
OBJECT-TYPE
Timestamp of when group Watt-hours (groupWh) was last reset.
1.3.6.1.4.1.534.6.6.7.5.5.1.5UnixTimeStampread-onlycurrent
groupPowerFactor
OBJECT-TYPE
A group PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.5.1.6Integer32read-onlycurrent
groupVAR
OBJECT-TYPE
A group VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.5.5.1.7Integer32read-onlycurrent
groupControlTable
OBJECT-TYPE
A list of controllable groups.
1.3.6.1.4.1.534.6.6.7.5.6not-accessiblecurrent
groupControlEntry
OBJECT-TYPE
An entry for a controllable group.
1.3.6.1.4.1.534.6.6.7.5.6.1not-accessiblecurrent
groupControlStatus
OBJECT-TYPE
Current state of a controlled group. A value of 'mixed' means that that the outlets within the group have differing states.
1.3.6.1.4.1.534.6.6.7.5.6.1.2INTEGER {off(0), on(1), rebooting(2), mixed(3)}read-onlycurrent
groupControlOffCmd
OBJECT-TYPE
Group-level outlet control command. Once the command is issued, the outlets in the group will turn Off immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-level Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object.
1.3.6.1.4.1.534.6.6.7.5.6.1.3Integer32 (-1..99999)read-writecurrent
groupControlOnCmd
OBJECT-TYPE
Group-level outlet control command. Once the command is issued, the outlets in the group will turn On immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-level On command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object.
1.3.6.1.4.1.534.6.6.7.5.6.1.4Integer32 (-1..99999)read-writecurrent
groupControlRebootCmd
OBJECT-TYPE
Group-level outlet control command. For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn back On. For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime seconds from when the command is issued. 0-n : Time in seconds until the Reboot command is issued -1 : Cancel a pending group-level Reboot command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object.
1.3.6.1.4.1.534.6.6.7.5.6.1.5Integer32 (-1..0)read-writecurrent
outlets
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.7.6
outletTable
OBJECT-TYPE
A list of outlets. The number of entries is given by outletCount.
1.3.6.1.4.1.534.6.6.7.6.1not-accessiblecurrent
outletEntry
OBJECT-TYPE
An entry for a particular outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1not-accessiblecurrent
outletIndex
OBJECT-TYPE
A unique value for each outlet. its value ranges from 1 to outletCount.
1.3.6.1.4.1.534.6.6.7.6.1.1.1Integer32 (1..64)accessible-for-notifycurrent
outletID
OBJECT-TYPE
Alphanumeric designator for the outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.2DisplayString (SIZE(2..4))read-onlycurrent
outletName
OBJECT-TYPE
A descriptive name for the outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.3OCTET STRING (SIZE(1..31))read-writecurrent
outletParentCount
OBJECT-TYPE
Number of parents for this outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.4Integer32read-onlycurrent
outletType
OBJECT-TYPE
The physical type of outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.5INTEGER {unknown(0), iecC13(1), iecC19(2), uk(10), french(11), schuko(12), nema515(20), nema51520(21), nema520(22), nemaL520(23), nemaL530(24), nema615(25), nema620(26), nemaL620(27), nemaL630(28), nemaL715(29), rf203p277(30), sdg300(31)}read-onlycurrent
outletDesignator
OBJECT-TYPE
Alphanumeric physical name for the outlet.
1.3.6.1.4.1.534.6.6.7.6.1.1.6DisplayString (SIZE(2..4))read-onlycurrent
outletPhaseID
OBJECT-TYPE
Value indicates which phases are connected to each outlet in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, phase 3 to phase 1, split-phase with phases 1 and 2, split phase with phases 2 and 3, split phase with phases 3 and 1, three-phase delta, and three-phase wye.
1.3.6.1.4.1.534.6.6.7.6.1.1.7INTEGER {singlePhase(1), phase1toN(2), phase2toN(3), phase3toN(4), phase1to2(5), phase2to3(6), phase3to1(7), phase12N(8), phase23N(9), phase31N(10), phase123(11), phase123N(12)}read-onlycurrent
outletParentTable
OBJECT-TYPE
A list of parents for this outlet. For example, this table will link to all of the groups that have this outlet as a child.
1.3.6.1.4.1.534.6.6.7.6.2not-accessiblecurrent
outletParentEntry
OBJECT-TYPE
An entry for a particular parent.
1.3.6.1.4.1.534.6.6.7.6.2.1not-accessiblecurrent
outletParentIndex
OBJECT-TYPE
A unique value for each parent. Its value ranges from 1 to outletParentCount.
1.3.6.1.4.1.534.6.6.7.6.2.1.1Integer32 (1..32)not-accessiblecurrent
outletParentType
OBJECT-TYPE
The type of the parent.
1.3.6.1.4.1.534.6.6.7.6.2.1.2INTEGER {unknown(0), breaker(1), section(2), custom(3)}read-onlycurrent
outletParentOID
OBJECT-TYPE
Object ID of a parent object.
1.3.6.1.4.1.534.6.6.7.6.2.1.3OBJECT IDENTIFIERread-onlycurrent
outletVoltageTable
OBJECT-TYPE
A list of outlet voltage measurements.
1.3.6.1.4.1.534.6.6.7.6.3not-accessiblecurrent
outletVoltageEntry
OBJECT-TYPE
An entry for an outlet voltage measurement.
1.3.6.1.4.1.534.6.6.7.6.3.1not-accessiblecurrent
outletVoltage
OBJECT-TYPE
Units are millivolts.
1.3.6.1.4.1.534.6.6.7.6.3.1.2Integer32read-onlycurrent
outletVoltageThStatus
OBJECT-TYPE
Status of the measured outlet voltage relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.6.3.1.3INTEGER {good(0), lowWarning(1), lowCritical(2), highWarning(3), highCritical(4)}read-onlycurrent
outletVoltageThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.3.1.4Integer32 (-1..500000)read-writecurrent
outletVoltageThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.3.1.5Integer32 (-1..500000)read-writecurrent
outletVoltageThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.3.1.6Integer32 (-1..500000)read-writecurrent
outletVoltageThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.3.1.7Integer32 (-1..500000)read-writecurrent
outletCurrentTable
OBJECT-TYPE
A list of outlet current measurements.
1.3.6.1.4.1.534.6.6.7.6.4not-accessiblecurrent
outletCurrentEntry
OBJECT-TYPE
An entry for an outlet current measurement.
1.3.6.1.4.1.534.6.6.7.6.4.1not-accessiblecurrent
outletCurrentCapacity
OBJECT-TYPE
Rated current capacity of the outlet. Units are milliamps. A negative value indicates that the hardware current capacity is unknown.
1.3.6.1.4.1.534.6.6.7.6.4.1.2Integer32read-onlycurrent
outletCurrent
OBJECT-TYPE
An outlet current measurement value. Units are milliamps.
1.3.6.1.4.1.534.6.6.7.6.4.1.3Integer32read-onlycurrent
outletCurrentThStatus
OBJECT-TYPE
Status of the measured outlet current relative to the configured thresholds. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.4INTEGER {good(0), lowWarning(1), lowCritical(2), highWarning(3), highCritical(4)}read-onlycurrent
outletCurrentThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.5Integer32 (-1..100000)read-writecurrent
outletCurrentThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.6Integer32 (-1..100000)read-writecurrent
outletCurrentThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.7Integer32 (-1..100000)read-writecurrent
outletCurrentThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.8Integer32 (-1..100000)read-writecurrent
outletCurrentCrestFactor
OBJECT-TYPE
Current crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.9Integer32read-onlycurrent
outletCurrentPercentLoad
OBJECT-TYPE
Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.4.1.10Integer32read-onlycurrent
outletPowerTable
OBJECT-TYPE
A list of outlet power measurements.
1.3.6.1.4.1.534.6.6.7.6.5not-accessiblecurrent
outletPowerEntry
OBJECT-TYPE
An entry for an outlet power measurement.
1.3.6.1.4.1.534.6.6.7.6.5.1not-accessiblecurrent
outletVA
OBJECT-TYPE
An outlet VA value. Units are VA. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.5.1.2Integer32read-onlycurrent
outletWatts
OBJECT-TYPE
An outlet Watts value. Units are Watts. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.5.1.3Integer32read-onlycurrent
outletWh
OBJECT-TYPE
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well.
1.3.6.1.4.1.534.6.6.7.6.5.1.4Unsigned32 (0..4294967295)read-writecurrent
outletWhTimer
OBJECT-TYPE
Timestamp of when outlet Watt-hours (outletWh) was last reset.
1.3.6.1.4.1.534.6.6.7.6.5.1.5UnixTimeStampread-onlycurrent
outletPowerFactor
OBJECT-TYPE
An outlet PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.5.1.6Integer32read-onlycurrent
outletVAR
OBJECT-TYPE
An outlet VAR value. Units are VAR. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.6.5.1.7Integer32read-onlycurrent
outletControlTable
OBJECT-TYPE
A list of controllable outlets.
1.3.6.1.4.1.534.6.6.7.6.6not-accessiblecurrent
outletControlEntry
OBJECT-TYPE
An entry for a controllable outlet.
1.3.6.1.4.1.534.6.6.7.6.6.1not-accessiblecurrent
outletControlStatus
OBJECT-TYPE
Current state of a controlled outlet.
1.3.6.1.4.1.534.6.6.7.6.6.1.2INTEGER {off(0), on(1), pendingOff(2), pendingOn(3)}read-onlycurrent
outletControlOffCmd
OBJECT-TYPE
Outlet control command. Once the command is issued, the outlet will turn Off immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object.
1.3.6.1.4.1.534.6.6.7.6.6.1.3Integer32 (-1..99999)read-writecurrent
outletControlOnCmd
OBJECT-TYPE
Outlet control command. Once the command is issued, the outlet will turn On immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet On command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object.
1.3.6.1.4.1.534.6.6.7.6.6.1.4Integer32 (-1..99999)read-writecurrent
outletControlRebootCmd
OBJECT-TYPE
Outlet control command. For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn back On. For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime seconds from when the command is issued. 0-n : Time in seconds until the Reboot command is issued -1 : Cancel a pending outlet Reboot command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object.
1.3.6.1.4.1.534.6.6.7.6.6.1.5Integer32 (-1..99999)read-writecurrent
outletControlPowerOnState
OBJECT-TYPE
Determines the outlet state when power is applied to the unit. 0 : not restart at device startup 1 : should sequence back ON in line with outletControlSequenceTime 2 : should take the state the outlet had when power was lost. If the state was ON, should sequence back ON in line with outletControlSequenceTime.
1.3.6.1.4.1.534.6.6.7.6.6.1.6INTEGER {off(0), on(1), lastState(2)}read-writecurrent
outletControlSequenceDelay
OBJECT-TYPE
Time delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on delay. Set to -1 to exclude this outlet from Global Sequence On commands.
1.3.6.1.4.1.534.6.6.7.6.6.1.7Integer32 (-1..99999)read-writecurrent
outletControlRebootOffTime
OBJECT-TYPE
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
1.3.6.1.4.1.534.6.6.7.6.6.1.8Integer32 (1..99999)read-writecurrent
outletControlSwitchable
OBJECT-TYPE
Determines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled.
1.3.6.1.4.1.534.6.6.7.6.6.1.9INTEGER {switchable(1), notSwitchable(2)}read-writecurrent
outletControlShutoffDelay
OBJECT-TYPE
Time delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this parameter first then write it to the command outletControlOffCmd.
1.3.6.1.4.1.534.6.6.7.6.6.1.10Integer32 (-1..99999)read-writecurrent
outletGlobalTable
OBJECT-TYPE
A list of globlal configuration on all outlets.
1.3.6.1.4.1.534.6.6.7.6.7not-accessiblecurrent
outletGlobalEntry
OBJECT-TYPE
An entry for a global variable on all outlets.
1.3.6.1.4.1.534.6.6.7.6.7.1not-accessiblecurrent
outletAutomaticShutoff
OBJECT-TYPE
Determines the state of all outlets when the unit is power off: 0 : not applicable (read only) 1 : Keep the outlet relays in the current position when the PDU is powered down 2 : Makes the outlet relays go to the position that shutoffs the outlets when the PDU is powered down
1.3.6.1.4.1.534.6.6.7.6.7.1.2INTEGER {notApplicable(0), keepTheCurrentPosition(1), shutoffTheOutlets(2)}read-writecurrent
environmental
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.7.7
temperatureTable
OBJECT-TYPE
A list of temperature probe measurements. The number of entries is given by temperatureCount.
1.3.6.1.4.1.534.6.6.7.7.1not-accessiblecurrent
temperatureEntry
OBJECT-TYPE
An entry for a temperature measurement.
1.3.6.1.4.1.534.6.6.7.7.1.1not-accessiblecurrent
temperatureIndex
OBJECT-TYPE
A unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount.
1.3.6.1.4.1.534.6.6.7.7.1.1.1Integer32 (1..2)accessible-for-notifycurrent
temperatureName
OBJECT-TYPE
A descriptive name for the temperature probe.
1.3.6.1.4.1.534.6.6.7.7.1.1.2OCTET STRING (SIZE(1..31))read-writecurrent
temperatureProbeStatus
OBJECT-TYPE
Indicates whether a probe is connected or not.
1.3.6.1.4.1.534.6.6.7.7.1.1.3INTEGER {bad(-1), disconnected(0), connected(1)}read-onlycurrent
temperatureValue
OBJECT-TYPE
Units are in tenths of a degree according to the scale specified by temperatureScale (either Fahrenheit or Celsius). Divide by ten to get degrees.
1.3.6.1.4.1.534.6.6.7.7.1.1.4Integer32read-onlycurrent
temperatureThStatus
OBJECT-TYPE
Status of the measured temperature relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.7.1.1.5INTEGER {good(0), lowWarning(1), lowCritical(2), highWarning(3), highCritical(4)}read-onlycurrent
temperatureThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.1.1.6Integer32 (-1..150000)read-writecurrent
temperatureThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.1.1.7Integer32 (-1..150000)read-writecurrent
temperatureThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.1.1.8Integer32 (-1..150000)read-writecurrent
temperatureThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.1.1.9Integer32 (-1..150000)read-writecurrent
humidityTable
OBJECT-TYPE
A list of humidity probe measurements. The number of entries is given by humidityCount.
1.3.6.1.4.1.534.6.6.7.7.2not-accessiblecurrent
humidityEntry
OBJECT-TYPE
An entry for a humidity measurement.
1.3.6.1.4.1.534.6.6.7.7.2.1not-accessiblecurrent
humidityIndex
OBJECT-TYPE
A unique value for each humidity probe measurement. Its value ranges from 1 to humidityCount.
1.3.6.1.4.1.534.6.6.7.7.2.1.1Integer32 (1..2)accessible-for-notifycurrent
humidityName
OBJECT-TYPE
A descriptive name for the humidity probe.
1.3.6.1.4.1.534.6.6.7.7.2.1.2OCTET STRING (SIZE(1..31))read-writecurrent
humidityProbeStatus
OBJECT-TYPE
Indicates whether a probe is connected or not.
1.3.6.1.4.1.534.6.6.7.7.2.1.3INTEGER {bad(-1), disconnected(0), connected(1)}read-onlycurrent
humidityValue
OBJECT-TYPE
Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH.
1.3.6.1.4.1.534.6.6.7.7.2.1.4Integer32read-onlycurrent
humidityThStatus
OBJECT-TYPE
Status of the measured humidity relative to the configured thresholds.
1.3.6.1.4.1.534.6.6.7.7.2.1.5INTEGER {good(0), lowWarning(1), lowCritical(2), highWarning(3), highCritical(4)}read-onlycurrent
humidityThLowerWarning
OBJECT-TYPE
Lower warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.2.1.6Integer32 (-1..1000)read-writecurrent
humidityThLowerCritical
OBJECT-TYPE
Lower critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.2.1.7Integer32 (-1..1000)read-writecurrent
humidityThUpperWarning
OBJECT-TYPE
Upper warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.2.1.8Integer32 (-1..1000)read-writecurrent
humidityThUpperCritical
OBJECT-TYPE
Upper critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
1.3.6.1.4.1.534.6.6.7.7.2.1.9Integer32 (-1..1000)read-writecurrent
contactTable
OBJECT-TYPE
A list of contact sensors. The number of entries is given by contactCount.
1.3.6.1.4.1.534.6.6.7.7.3not-accessiblecurrent
contactEntry
OBJECT-TYPE
An entry for a contact sensor
1.3.6.1.4.1.534.6.6.7.7.3.1not-accessiblecurrent
contactIndex
OBJECT-TYPE
A unique value for each contact sensor. Its value ranges from 1 to contactCount.
1.3.6.1.4.1.534.6.6.7.7.3.1.1Integer32 (1..3)accessible-for-notifycurrent
contactName
OBJECT-TYPE
A descriptive name for the contact sensor.
1.3.6.1.4.1.534.6.6.7.7.3.1.2OCTET STRING (SIZE(1..31))read-writecurrent
contactProbeStatus
OBJECT-TYPE
Indicates whether a probe is connected or not. Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be read.
1.3.6.1.4.1.534.6.6.7.7.3.1.3INTEGER {bad(-1), disconnected(0), connected(1)}read-onlycurrent
contactState
OBJECT-TYPE
The state of the contact sensor.
1.3.6.1.4.1.534.6.6.7.7.3.1.4INTEGER {contactBad(-1), contactOpen(0), contactClosed(1)}read-onlycurrent
conformance
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.7.25
objectGroups
OBJECT-IDENTITY
1.3.6.1.4.1.534.6.6.7.25.5

Notifications

NameOIDStatus
notifyUserLogin
NOTIFICATION-TYPE
Sent whenever a user logs in.
1.3.6.1.4.1.534.6.6.7.0.1current
notifyUserLogout
NOTIFICATION-TYPE
Sent whenever a user logs out.
1.3.6.1.4.1.534.6.6.7.0.2current
notifyFailedLogin
NOTIFICATION-TYPE
Sent when someone attempts to log in and fails. On some models, may be sent after three failed login attempts.
1.3.6.1.4.1.534.6.6.7.0.3current
notifyBootUp
NOTIFICATION-TYPE
Sent whenever an ePDU finishes booting up (hard or soft reboot).
1.3.6.1.4.1.534.6.6.7.0.4current
notifyInputVoltageThStatus
NOTIFICATION-TYPE
Sent whenever an input voltage threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.11current
notifyInputCurrentThStatus
NOTIFICATION-TYPE
Sent whenever an input current threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.12current
notifyInputFrequencyStatus
NOTIFICATION-TYPE
Sent whenever the input frequency status changes.
1.3.6.1.4.1.534.6.6.7.0.13current
notifyGroupVoltageThStatus
NOTIFICATION-TYPE
Sent whenever a group voltage threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.21current
notifyGroupCurrentThStatus
NOTIFICATION-TYPE
Sent whenever a group current threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.22current
notifyGroupBreakerStatus
NOTIFICATION-TYPE
Sent whenever a group status changes to indicate whether the circuit breaker is on or off.
1.3.6.1.4.1.534.6.6.7.0.23current
notifyOutletVoltageThStatus
NOTIFICATION-TYPE
Sent whenever an outlet voltage threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.31current
notifyOutletCurrentThStatus
NOTIFICATION-TYPE
Sent whenever an outlet current threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.32current
notifyOutletControlStatus
NOTIFICATION-TYPE
Sent whenever an outlet state On / Off changes.
1.3.6.1.4.1.534.6.6.7.0.33current
notifyTemperatureThStatus
NOTIFICATION-TYPE
Sent whenever a temperature threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.41current
notifyHumidityThStatus
NOTIFICATION-TYPE
Sent whenever a humidity threshold status changes.
1.3.6.1.4.1.534.6.6.7.0.42current
notifyContactState
NOTIFICATION-TYPE
Sent whenever a contact sensor state changes.
1.3.6.1.4.1.534.6.6.7.0.43current
notifyProbeStatus
NOTIFICATION-TYPE
Sent whenever the environment probe status changes.
1.3.6.1.4.1.534.6.6.7.0.44current
notifyCommunicationStatus
NOTIFICATION-TYPE
Sent whenever the PDU communication status changes.
1.3.6.1.4.1.534.6.6.7.0.51current
notifyInternalStatus
NOTIFICATION-TYPE
Sent whenever the PDU internal status changes.
1.3.6.1.4.1.534.6.6.7.0.52current
notifyTest
NOTIFICATION-TYPE
Sent whenever the trap test feature is used by the communication card.
1.3.6.1.4.1.534.6.6.7.0.53current
notifyStrappingStatus
NOTIFICATION-TYPE
Sent whenever the strapping communication status changes.
1.3.6.1.4.1.534.6.6.7.0.54current

Conformance

NameOIDStatus
eatonEpduCompliances
MODULE-COMPLIANCE
The requirements for conforming to the ePDU MIB.
1.3.6.1.4.1.534.6.6.7.25.1current
epduRequiredGroup
OBJECT-GROUP
Minimal objects are required to conform to this MIB.
1.3.6.1.4.1.534.6.6.7.25.5.1current
epduOptionalGroup
OBJECT-GROUP
Most objects in this MIB are optional.
1.3.6.1.4.1.534.6.6.7.25.5.2current
epduNotifyGroup
NOTIFICATION-GROUP
These notifications will be supported depending on the features of the ePDU. Check the web interface for options to turn these notifications on/off. If an option is not listed, then the ePDU likely does not support that notification.
1.3.6.1.4.1.534.6.6.7.25.5.3current