MIBs Depot

EATON-ATS2-MIB

Registered at
1.3.6.1.4.1.534.10.2
Last updated
2014-07-31 12:00
Organization
Eaton Corporation
Revisions
2014-07-31 12:00
Namespace
eaton
Source file
EATON-ATS2-MIB
Digest
sha256:8b87e932d7b50fa66585d2a42e27e43ab1f3af64e576deaeabb5fcdfefc6286c

Description

The MIB module for Eaton ATS (Automatic Transfer Switch).

Contact

www.eaton.com

Imports

FromSymbols
EATON-OIDSsts
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMICounter32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

EATON-ATS2-MIB
EATON-OIDS
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Textual conventions

NameOIDSyntaxAccessStatus
UnixTimeStamp
TEXTUAL-CONVENTION
Unix time stamp. Measured in seconds since January 1, 1970.
current

Objects

NameOIDSyntaxAccessStatus
ats2Ident
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.1
ats2IdentManufacturer
OBJECT-TYPE
The manufacturer name.
1.3.6.1.4.1.534.10.2.1.1DisplayString (SIZE(0..16))read-onlycurrent
ats2IdentModel
OBJECT-TYPE
Device model name.
1.3.6.1.4.1.534.10.2.1.2DisplayString (SIZE(0..32))read-onlycurrent
ats2IdentFWVersion
OBJECT-TYPE
Device F/W version.
1.3.6.1.4.1.534.10.2.1.3DisplayString (SIZE(0..16))read-onlycurrent
ats2IdentRelease
OBJECT-TYPE
The released date.
1.3.6.1.4.1.534.10.2.1.4DisplayString (SIZE(0..16))read-onlycurrent
ats2IdentSerialNumber
OBJECT-TYPE
Device serial number
1.3.6.1.4.1.534.10.2.1.5DisplayString (SIZE(0..20))read-onlycurrent
ats2IdentPartNumber
OBJECT-TYPE
Device part number
1.3.6.1.4.1.534.10.2.1.6DisplayString (SIZE(0..20))read-onlycurrent
ats2IdentAgentVersion
OBJECT-TYPE
Communication Card F/W version
1.3.6.1.4.1.534.10.2.1.7DisplayString (SIZE(0..20))read-onlycurrent
ats2Measure
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.2
ats2Input
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.2.1
ats2InputDephasing
OBJECT-TYPE
The dephasing in between Source 1 and Source 2.
1.3.6.1.4.1.534.10.2.2.1.1INTEGERread-onlycurrent
ats2InputTable
OBJECT-TYPE
The table of input information.
1.3.6.1.4.1.534.10.2.2.2not-accessiblecurrent
ats2InputEntry
OBJECT-TYPE
The input information of each source input: <node>.1 source1 <node>.2 source2
1.3.6.1.4.1.534.10.2.2.2.1not-accessiblecurrent
ats2InputIndex
OBJECT-TYPE
Index to input.
1.3.6.1.4.1.534.10.2.2.2.1.1INTEGER {source1(1), source2(2)}read-onlycurrent
ats2InputVoltage
OBJECT-TYPE
The input voltage in front of relay. Units are 0.1 V.
1.3.6.1.4.1.534.10.2.2.2.1.2INTEGERread-onlycurrent
ats2InputFrequency
OBJECT-TYPE
The input frequency. Units are 0.1 Hz.
1.3.6.1.4.1.534.10.2.2.2.1.3INTEGERread-onlycurrent
ats2Output
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.2.3
ats2OutputVoltage
OBJECT-TYPE
The output voltage. Units are 0.1 V.
1.3.6.1.4.1.534.10.2.2.3.1INTEGERread-onlycurrent
ats2OutputCurrent
OBJECT-TYPE
The output current. Units are 0.1 A.
1.3.6.1.4.1.534.10.2.2.3.2INTEGERread-onlycurrent
ats2OperationMode
OBJECT-TYPE
The operation mode.
1.3.6.1.4.1.534.10.2.2.4INTEGER {initialization(1), diagnosis(2), off(3), source1(4), source2(5), safe(6), fault(7)}read-onlycurrent
ats2Status
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.3
ats2InputStatus
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.3.1
ats2InputStatusDephasing
OBJECT-TYPE
The dephasing status in between Source 1 and Source 2.
1.3.6.1.4.1.534.10.2.3.1.1INTEGER {normal(1), outOfRange(2)}read-onlycurrent
ats2InputStatusTable
OBJECT-TYPE
The table of input status.
1.3.6.1.4.1.534.10.2.3.2not-accessiblecurrent
ats2InputStatusEntry
OBJECT-TYPE
The input flow status: <node>.1 source1 <node>.2 source2
1.3.6.1.4.1.534.10.2.3.2.1not-accessiblecurrent
ats2InputStatusIndex
OBJECT-TYPE
Index of input entry.
1.3.6.1.4.1.534.10.2.3.2.1.1INTEGER {source1(1), source2(2)}read-onlycurrent
ats2InputStatusFrequency
OBJECT-TYPE
The status of input frequency.
1.3.6.1.4.1.534.10.2.3.2.1.2INTEGER {good(1), outOfRange(2)}read-onlycurrent
ats2InputStatusGood
OBJECT-TYPE
The summarized status of input AC flow.
1.3.6.1.4.1.534.10.2.3.2.1.3INTEGER {voltageOrFreqOutofRange(1), voltageAndFreqNormalRange(2), voltageDeratedRangeAndFreqNormalRange(3), voltageAndFreqNormalRangeWaveformNok(4)}read-onlycurrent
ats2InputStatusInternalFailure
OBJECT-TYPE
The internal fault status of input.
1.3.6.1.4.1.534.10.2.3.2.1.4INTEGER {good(1), internalFailure(2)}read-onlycurrent
ats2InputStatusVoltage
OBJECT-TYPE
The status of input voltage.
1.3.6.1.4.1.534.10.2.3.2.1.5INTEGER {normalRange(1), deratedRange(2), outofRange(3), missing(4)}read-onlycurrent
ats2InputStatusUsed
OBJECT-TYPE
The status of input relay.
1.3.6.1.4.1.534.10.2.3.2.1.6INTEGER {notPoweringLoad(1), poweringLoad(2)}read-onlycurrent
ats2OutputStatus
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.3.3
ats2StatusInternalFailure
OBJECT-TYPE
Output fault.
1.3.6.1.4.1.534.10.2.3.3.1INTEGER {good(1), internalFailure(2)}read-onlycurrent
ats2StatusOutput
OBJECT-TYPE
Output powered status.
1.3.6.1.4.1.534.10.2.3.3.2INTEGER {outputNotPowered(1), outputPowered(2)}read-onlycurrent
ats2StatusOverload
OBJECT-TYPE
The output overload status.
1.3.6.1.4.1.534.10.2.3.3.3INTEGER {noOverload(1), warningOverload(2), criticalOverload(3)}read-onlycurrent
ats2StatusOverTemperature
OBJECT-TYPE
The over temperature status.
1.3.6.1.4.1.534.10.2.3.3.4INTEGER {noOverTemperature(1), overTemperature(2)}read-onlycurrent
ats2StatusShortCircuit
OBJECT-TYPE
Short circuit status.
1.3.6.1.4.1.534.10.2.3.3.5INTEGER {noShortCircuit(1), shortCircuit(2)}read-onlycurrent
ats2StatusCommunicationLost
OBJECT-TYPE
Communication failure status.
1.3.6.1.4.1.534.10.2.3.3.6INTEGER {good(1), communicationLost(2)}read-onlycurrent
ats2StatusConfigurationFailure
OBJECT-TYPE
Configuration failure status.
1.3.6.1.4.1.534.10.2.3.3.7INTEGER {good(1), configurationFailure(2)}read-onlycurrent
ats2Config
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.4
ats2ConfigTime
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.4.1
ats2ConfigTimeRTC
OBJECT-TYPE
Clock value. This could be from either a real-time clock (in which case it is likely writeable) or from a time server via NTP (probably read-only). (since 1/1/1970 at 1:00:00).
1.3.6.1.4.1.534.10.2.4.1.1UnixTimeStampread-writecurrent
ats2ConfigTimeTextDate
OBJECT-TYPE
The present date in MM/DD/YYYY text format.
1.3.6.1.4.1.534.10.2.4.1.2DisplayString (SIZE(0..10))read-onlycurrent
ats2ConfigTimeTextTime
OBJECT-TYPE
The present time in hh:mm:ss text format.
1.3.6.1.4.1.534.10.2.4.1.3DisplayString (SIZE(0..8))read-onlycurrent
ats2ConfigInputVoltageRating
OBJECT-TYPE
The input voltage rating. Unit is 1 V.
1.3.6.1.4.1.534.10.2.4.2INTEGERread-onlycurrent
ats2ConfigInputFrequencyRating
OBJECT-TYPE
The input frequency rating. Unit is 1 Hz.
1.3.6.1.4.1.534.10.2.4.3INTEGERread-onlycurrent
ats2ConfigOutputVoltage
OBJECT-TYPE
The output voltage config. Unit is 1 V.
1.3.6.1.4.1.534.10.2.4.4INTEGERread-writecurrent
ats2ConfigPreferred
OBJECT-TYPE
The preferred source.
1.3.6.1.4.1.534.10.2.4.5INTEGER {source1(1), source2(2)}read-writecurrent
ats2ConfigSensitivity
OBJECT-TYPE
The AC Blackout Sensitivity.
1.3.6.1.4.1.534.10.2.4.6INTEGER {normal(1), highSensitivity(2), lowSensitivity(3)}read-writecurrent
ats2ConfigTransferMode
OBJECT-TYPE
behavior configuration when transfering from one source to other source not synchronized.
1.3.6.1.4.1.534.10.2.4.7INTEGER {standard(1), gap(2)}read-writecurrent
ats2ConfigTransferTest
OBJECT-TYPE
The status of transfer test.
1.3.6.1.4.1.534.10.2.4.8INTEGER {doneAndPassed(1), doneAndWarning(2), doneAndError(3), aborted(4), inProgress(5), noTestInitiated(6)}read-onlycurrent
ats2ConfigBrownoutLow
OBJECT-TYPE
Setting of input brownout low voltage. Unit is 1 V.
1.3.6.1.4.1.534.10.2.4.9INTEGERread-onlycurrent
ats2ConfigBrownoutLowDerated
OBJECT-TYPE
Setting of input brownout low derated voltage. Unit is 1 V.
1.3.6.1.4.1.534.10.2.4.10INTEGERread-onlycurrent
ats2ConfigBrownoutHigh
OBJECT-TYPE
Setting of input brownout high voltage. Unit is 1 V.
1.3.6.1.4.1.534.10.2.4.11INTEGERread-onlycurrent
ats2ConfigHysteresisVoltage
OBJECT-TYPE
Hysteresis between loss point and comeback point. Unit is 1 V.
1.3.6.1.4.1.534.10.2.4.12INTEGERread-onlycurrent
ats2Environment
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.5
ats2EnvRemoteTemp
OBJECT-TYPE
The reading of an EMP's temperature sensor.
1.3.6.1.4.1.534.10.2.5.1INTEGER (-100..200)read-onlycurrent
ats2EnvRemoteHumidity
OBJECT-TYPE
The reading of an EMP's humidity sensor.
1.3.6.1.4.1.534.10.2.5.2INTEGER (0..100)read-onlycurrent
ats2EnvNumContacts
OBJECT-TYPE
The number of Contacts in the ats2ContactSenseTable. This object indicates the number of rows in the ats2ContactSenseTable.
1.3.6.1.4.1.534.10.2.5.3INTEGER (1..1024)read-onlycurrent
ats2ContactSenseTable
OBJECT-TYPE
A list of Contact Sensing table entries. The number of entries is given by the value of ats2EnvNumContacts.
1.3.6.1.4.1.534.10.2.5.4not-accessiblecurrent
ats2ContactsTableEntry
OBJECT-TYPE
An entry containing information applicable to a particular Contact input.
1.3.6.1.4.1.534.10.2.5.4.1not-accessiblecurrent
ats2ContactIndex
OBJECT-TYPE
The Contact identifier; identical to the Contact Number. This object is not-accessible to MIB browsers, but had to be changed to read-only to satisfy SMIv2 syntax checkers if it is included in traps.
1.3.6.1.4.1.534.10.2.5.4.1.1INTEGER (1..1024)read-onlycurrent
ats2ContactType
OBJECT-TYPE
The normal state for this contact. The 'other' (not 'Normally') state is the Active state for generating the ats2tdContactActiveNotice trap. If anyChange(3) is selected, then this trap is sent any time the contact changes to either Open or Closed. No traps are sent if the Contact is set to notUsed(4). In many cases, the configuration for Contacts may be done by other means, so this object may be read-only.
1.3.6.1.4.1.534.10.2.5.4.1.2INTEGER {normallyOpen(1), normallyClosed(2), anyChange(3), notUsed(4)}read-writecurrent
ats2ContactState
OBJECT-TYPE
The current state of the Contact input; the value is based on the open/closed input state and the setting for ats2ContactType. When entering the openWithNotice(3) and closedWithNotice(4) states, no entries added to the ats2AlarmTable, but the ats2tdContactActiveNotice trap is sent.
1.3.6.1.4.1.534.10.2.5.4.1.3INTEGER {open(1), closed(2), openWithNotice(3), closedWithNotice(4)}read-onlycurrent
ats2ContactDescr
OBJECT-TYPE
A label identifying the Contact. This object should be set by the administrator.
1.3.6.1.4.1.534.10.2.5.4.1.4DisplayString (SIZE(0..63))read-writecurrent
ats2EnvRemoteTempLowerLimit
OBJECT-TYPE
The Lower Limit of the EMP temperature; if ats2EnvRemoteTemp falls below this value, the ats2RemoteTempBad alarm will occur.
1.3.6.1.4.1.534.10.2.5.5INTEGER (-100..200)read-writecurrent
ats2EnvRemoteTempUpperLimit
OBJECT-TYPE
The Upper Limit of the EMP temperature; if ats2EnvRemoteTemp rises above this value, the ats2RemoteTempBad alarm will occur. This value should be greater than ats2EnvRemoteTempLowerLimit.
1.3.6.1.4.1.534.10.2.5.6INTEGER (-100..200)read-writecurrent
ats2EnvRemoteHumidityLowerLimit
OBJECT-TYPE
The Lower Limit of the EMP humidity reading; if ats2EnvRemoteHumidity falls below this value, the ats2RemoteHumidityBad alarm will occur.
1.3.6.1.4.1.534.10.2.5.7INTEGER (0..100)read-writecurrent
ats2EnvRemoteHumidityUpperLimit
OBJECT-TYPE
The Upper Limit of the EMP humidity reading; if ats2EnvRemoteHumidity rises above this value, the ats2RemoteHumidityBad alarm will occur. This value should be greater than ats2EnvRemoteHumidityLowerLimit.
1.3.6.1.4.1.534.10.2.5.8INTEGER (0..100)read-writecurrent
ats2Traps
OBJECT-IDENTITY
1.3.6.1.4.1.534.10.2.10

Notifications

NameOIDStatus
ats2TrapCommunicationLost
NOTIFICATION-TYPE
Communication with the ATS failed.
1.3.6.1.4.1.534.10.2.10.1current
ats2TrapCommunicationRecovered
NOTIFICATION-TYPE
Communication with the ATS recovered.
1.3.6.1.4.1.534.10.2.10.2current
ats2TrapOutputPowered
NOTIFICATION-TYPE
The ATS powers the load.
1.3.6.1.4.1.534.10.2.10.3current
ats2TrapOutputNotPowered
NOTIFICATION-TYPE
The ATS does not powers the load.
1.3.6.1.4.1.534.10.2.10.4current
ats2TrapOverload
NOTIFICATION-TYPE
The ATS has sensed a critical overload.
1.3.6.1.4.1.534.10.2.10.5current
ats2TrapNoOverLoad
NOTIFICATION-TYPE
The critical overload disappeared.
1.3.6.1.4.1.534.10.2.10.6current
ats2TrapInternalFailure
NOTIFICATION-TYPE
The ATS has an internal failure (sum of all HW internal failure).
1.3.6.1.4.1.534.10.2.10.7current
ats2TrapNoInternalFailure
NOTIFICATION-TYPE
The ATS internal failure disappeared.
1.3.6.1.4.1.534.10.2.10.8current
ats2TrapSource1Normal
NOTIFICATION-TYPE
Source 1 returns to normal.
1.3.6.1.4.1.534.10.2.10.9current
ats2TrapSource1OutOfRange
NOTIFICATION-TYPE
Source 1 out of range.
1.3.6.1.4.1.534.10.2.10.10current
ats2TrapSource2Normal
NOTIFICATION-TYPE
Source 2 returns to normal.
1.3.6.1.4.1.534.10.2.10.11current
ats2TrapSource2OutOfRange
NOTIFICATION-TYPE
Source 2 out of range.
1.3.6.1.4.1.534.10.2.10.12current
ats2TrapSourceDesynchronized
NOTIFICATION-TYPE
Source 1 and Source 2 phase are desynchronized.
1.3.6.1.4.1.534.10.2.10.13current
ats2TrapSourceSynchronized
NOTIFICATION-TYPE
Source 1 and Source 2 phase are synchronized.
1.3.6.1.4.1.534.10.2.10.14current
ats2TrapOutputPoweredBySource1
NOTIFICATION-TYPE
Source 1 powers the output.
1.3.6.1.4.1.534.10.2.10.15current
ats2TrapOutputPoweredBySource2
NOTIFICATION-TYPE
Source 2 powers the output.
1.3.6.1.4.1.534.10.2.10.16current
ats2TrapRemoteTempLow
NOTIFICATION-TYPE
The remote temperature, ats2EnvRemoteTemp, has fallen below the set lower limit, ats2EnvRemoteTempLowerLimit.
1.3.6.1.4.1.534.10.2.10.20current
ats2TrapRemoteTempHigh
NOTIFICATION-TYPE
The remote temperature, ats2EnvRemoteTemp, has risen above the set upper limit, xupsEnvRemoteTempUpperLimit.
1.3.6.1.4.1.534.10.2.10.21current
ats2TrapRemoteTempNormal
NOTIFICATION-TYPE
The remote temperature, ats2EnvRemoteTemp, is inside the interval defined by the lower limit and the upper limit.
1.3.6.1.4.1.534.10.2.10.22current
ats2TrapRemoteHumidityLow
NOTIFICATION-TYPE
The remote humidity, ats2EnvRemoteHumidity, has fallen below the set lower limit, ats2EnvRemoteHumidityLowerLimit.
1.3.6.1.4.1.534.10.2.10.23current
ats2TrapRemoteHumidityHigh
NOTIFICATION-TYPE
The remote humidity, ats2EnvRemoteHumidity, has risen above the set upper limit, ats2EnvRemoteHumidityUpperLimit.
1.3.6.1.4.1.534.10.2.10.24current
ats2TrapRemoteHumidityNormal
NOTIFICATION-TYPE
The remote humidity, ats2EnvRemoteHumidity, is inside the interval defined by the lower limit and the upper limit.
1.3.6.1.4.1.534.10.2.10.25current
ats2Contact1ActiveNotice
NOTIFICATION-TYPE
The Contact 1 is in its Active state. The following are the situations that generate this trap: For ats2ContactType: and ats2ContactState: normallyOpen(1) and closedWithNotice(4) normallyClosed(2) and openWithNotice(3) anyChange(3) and openWithNotice(3) or closedWithNotice(4)
1.3.6.1.4.1.534.10.2.10.26current
ats2Contact1InactiveNotice
NOTIFICATION-TYPE
The Contact 1 has changed to its Inactive state.
1.3.6.1.4.1.534.10.2.10.27current
ats2Contact2ActiveNotice
NOTIFICATION-TYPE
The Contact 2 is in its Active state. The following are the situations that generate this trap: For ats2ContactType: and ats2ContactState: normallyOpen(1) and closedWithNotice(4) normallyClosed(2) and openWithNotice(3) anyChange(3) and openWithNotice(3) or closedWithNotice(4)
1.3.6.1.4.1.534.10.2.10.28current
ats2Contact2InactiveNotice
NOTIFICATION-TYPE
The Contact 2 has changed to its Inactive state.
1.3.6.1.4.1.534.10.2.10.29current
ats2TestTrap
NOTIFICATION-TYPE
Sent whenever the trap test feature is used by the communication card.
1.3.6.1.4.1.534.10.2.10.40current