DellrPDU-MIB
- Registered at
- 1.3.6.1.4.1.674.10903
- Namespace
- dell
- Source file
DellrPDU-MIB- Digest
sha256:68b082a2fbfb325f37d7ec1ef20d9e0c5dde96a98cb0f38cecab2e10518d454c
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Gauge32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
DellrPDU-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| RpduCommNoneOKLostType type | ||||
| RpduEnableDisableType type | ||||
| RpduLowNormalNearOverloadType type | ||||
| RpduNormalAlarmType type | ||||
| RpduNotPBMinLowNrmlOHiMaxType type | ||||
| RpduOtherToNonrecoverableType type | ||||
| RpduOutletPhaseLayoutType type |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| dell OBJECT-IDENTITY | 1.3.6.1.4.1.674 | |||
| pdu OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903 | |||
| pdusub OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200 | |||
| software OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.1 | |||
| hardware OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2 | |||
| productID OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.100 | |||
| productIDDisplayName OBJECT-TYPE Name of this product for display purposes. | 1.3.6.1.4.1.674.10903.200.2.100.1 | DisplayString | read-write | mandatory |
| productIDDescription OBJECT-TYPE A short description of this product. | 1.3.6.1.4.1.674.10903.200.2.100.2 | DisplayString | read-write | mandatory |
| productIDVendor OBJECT-TYPE The name of the product manufacturer. | 1.3.6.1.4.1.674.10903.200.2.100.3 | DisplayString | read-only | mandatory |
| productIDVersion OBJECT-TYPE The hardware version of this product. | 1.3.6.1.4.1.674.10903.200.2.100.4 | DisplayString | read-only | mandatory |
| productIDBuildNumber OBJECT-TYPE The software build number of the product populating the MIB. | 1.3.6.1.4.1.674.10903.200.2.100.5 | DisplayString | read-only | mandatory |
| productIDURL OBJECT-TYPE The URL of the Web-based application to manage this device, should the device provide one. | 1.3.6.1.4.1.674.10903.200.2.100.6 | DisplayString | read-only | mandatory |
| productIDDeviceNetworkName OBJECT-TYPE Operating system-specific computer name if product SNMP service is hosted. | 1.3.6.1.4.1.674.10903.200.2.100.7 | DisplayString | read-write | mandatory |
| productStatus OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.110 | |||
| productStatusGlobalStatus OBJECT-TYPE The current status of the product. This is a summary of the status for the entire product including any metered devices. The SNMP monitor performs a get to retrieve additional data when this status is abnormal. Valid values 1: Other 2: Unknown 3: OK 4: Non-critical 5: Critical 6: Non-recoverable. | 1.3.6.1.4.1.674.10903.200.2.110.1 | RpduOtherToNonrecoverableType | read-only | mandatory |
| productStatusLastGlobalStatus OBJECT-TYPE The status before the current status which induced an initiative to issue a global status change trap. | 1.3.6.1.4.1.674.10903.200.2.110.2 | RpduOtherToNonrecoverableType | read-only | mandatory |
| productStatusTimeStamp OBJECT-TYPE The last time that the SNMP table geometries changed or attribute data was significantly updated. Management applications use this OID to trigger a refresh of data acquired from the MIB. This time should be a relative timestamp, for example, the value of MIB II SysUpTime when the values are updated. | 1.3.6.1.4.1.674.10903.200.2.110.3 | INTEGER | read-only | mandatory |
| productStatusRESERVED1 OBJECT-TYPE RESERVED | 1.3.6.1.4.1.674.10903.200.2.110.4 | DisplayString | read-only | mandatory |
| productStatusRESERVED2 OBJECT-TYPE RESERVED | 1.3.6.1.4.1.674.10903.200.2.110.5 | DisplayString | read-only | mandatory |
| productStatusRESERVED3 OBJECT-TYPE RESERVED | 1.3.6.1.4.1.674.10903.200.2.110.6 | DisplayString | read-only | mandatory |
| rPDU OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200 | |||
| rPDUIdentD OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.100 | |||
| rPDUIdentTableSize OBJECT-TYPE The number of connected Rack PDUs. | 1.3.6.1.4.1.674.10903.200.2.200.100.1 | INTEGER | read-only | mandatory |
| rPDUIdentTable OBJECT-TYPE A table of Rack PDU identification data. | 1.3.6.1.4.1.674.10903.200.2.200.100.2 | not-accessible | mandatory | |
| rPDUIdentEntry OBJECT-TYPE Identification data from the Rack PDU being queried. | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1 | not-accessible | mandatory | |
| rPDUIdentIndex OBJECT-TYPE The index to the Rack PDU identification table entry. | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.1 | INTEGER | read-only | mandatory |
| rPDUIdentNameD OBJECT-TYPE A user-defined string identifying the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.2 | DisplayString | read-write | mandatory |
| rPDUIdentLocation OBJECT-TYPE A user-defined string identifying the location of the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.3 | DisplayString | read-write | mandatory |
| rPDUIdentHardwareRevD OBJECT-TYPE The Rack PDU hardware version. | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.4 | DisplayString | read-only | mandatory |
| rPDUIdentFirmwareRevD OBJECT-TYPE The Rack PDU firmware version. | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.5 | DisplayString | read-only | mandatory |
| rPDUIdentDateOfManufactureD OBJECT-TYPE The date the Rack PDU was manufactured in mm/dd/yyyy format. | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.6 | DisplayString | read-only | mandatory |
| rPDUIdentModelNumberD OBJECT-TYPE The Rack PDU model number. | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.7 | DisplayString | read-only | mandatory |
| rPDUIdentSerialNumberD OBJECT-TYPE The Rack PDU serial number. | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.8 | DisplayString | read-only | mandatory |
| rPDUDevice OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.110 | |||
| rPDUDeviceTableSize OBJECT-TYPE The number of connected Rack PDUs. | 1.3.6.1.4.1.674.10903.200.2.200.110.1 | INTEGER | read-only | mandatory |
| rPDUDeviceStatusTable OBJECT-TYPE A table of Rack PDU status information. | 1.3.6.1.4.1.674.10903.200.2.200.110.2 | not-accessible | mandatory | |
| rPDUDeviceStatusEntry OBJECT-TYPE Status information from the Rack PDU being queried. | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1 | not-accessible | mandatory | |
| rPDUDeviceStatusIndex OBJECT-TYPE The index to the Rack PDU status table entry. | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.1 | INTEGER | read-only | mandatory |
| rPDUDeviceStatusName OBJECT-TYPE A user-defined string identifying the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.2 | DisplayString | read-write | mandatory |
| rPDUDeviceStatusPower OBJECT-TYPE The power consumption of the Rack PDU load in 1/100 of KWatts. | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.3 | INTEGER | read-only | mandatory |
| rPDUDeviceStatusEnergy OBJECT-TYPE A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.4 | INTEGER | read-only | mandatory |
| rPDUDeviceStatusCommandPending OBJECT-TYPE Indicates whether the device is processing a pending command. If the commandPendingUnknown (3) value is returned, all devices receiving power from the Rack PDU should be shut down. The Rack PDU's power should then be cycled to clear this condition. | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.5 | INTEGER {commandPending(1), noCommandPending(2), commandPendingUnknown(3)} | read-only | mandatory |
| rPDUDeviceStatusLoadState OBJECT-TYPE Indicates the present load status of the Rack PDU Device being queried. | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.6 | RpduLowNormalNearOverloadType | read-only | mandatory |
| rPDUDeviceConfigTable OBJECT-TYPE A table of Rack PDU configuration data. | 1.3.6.1.4.1.674.10903.200.2.200.110.3 | not-accessible | mandatory | |
| rPDUDeviceConfigEntry OBJECT-TYPE Configuration data from the Rack PDU being queried. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1 | not-accessible | mandatory | |
| rPDUDeviceConfigIndex OBJECT-TYPE The index to the Rack PDU table entry. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.1 | INTEGER | read-only | mandatory |
| rPDUDeviceConfigName OBJECT-TYPE A user-defined string identifying the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.2 | DisplayString | read-write | mandatory |
| rPDUDeviceConfigLocation OBJECT-TYPE The Location of the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.3 | DisplayString | read-write | mandatory |
| rPDUDeviceConfigColdstartDelay OBJECT-TYPE The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4 | INTEGER | read-write | mandatory |
| rPDUDeviceCfgLowLoadPwrThresh OBJECT-TYPE The user-defined low power draw alarm threshold, measured in tenths of kilowatts. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.5 | INTEGER | read-write | mandatory |
| rPDUDeviceCfgNerOvloadPwrThresh OBJECT-TYPE The user-defined near power overload threshold, measured in tenths of kilowatts. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.6 | INTEGER | read-write | mandatory |
| rPDUDeviceCfgOverloadPwrThresh OBJECT-TYPE The user-defined power overload threshold, measured in tenths of kilowatts. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.7 | INTEGER | read-write | mandatory |
| rPDUDeviceConfigPowerHeadroom OBJECT-TYPE The amount of input power that is available to the connected devices in hundredths of kilowatt-hours. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.8 | INTEGER | read-only | mandatory |
| rPDUDeviceConfigPeakPower OBJECT-TYPE The highest input power level recorded by the connected devices in hundredths of kilowatt-hours. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.9 | INTEGER | read-only | mandatory |
| rPDUDeviceCfgPeakPwrStartTime OBJECT-TYPE The time, in hh:mm:ss, when the device started recording the highest input power level. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.10 | DisplayString | read-only | mandatory |
| rPDUDeviceConfigPeakPwrCapTime OBJECT-TYPE The time, in hh:mm:ss, when the highest input power level was recorded by the device. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.11 | DisplayString | read-only | mandatory |
| rPDUDeviceCfgPeakPowerHeadroom OBJECT-TYPE The highest level of input power that is available to the connected devices in hundredths of kilowatt-hours. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.12 | INTEGER | read-only | mandatory |
| rPDUDeviceCfgEnergyStartTime OBJECT-TYPE The time, in hh:mm:ss, when the device started recording the input energy level. | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.13 | DisplayString | read-only | mandatory |
| rPDUDevicePropertiesTable OBJECT-TYPE A table of Rack PDU properties. | 1.3.6.1.4.1.674.10903.200.2.200.110.4 | not-accessible | mandatory | |
| rPDUDevicePropertiesEntry OBJECT-TYPE Properties of the Rack PDU being queried. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1 | not-accessible | mandatory | |
| rPDUDevicePropertiesIndex OBJECT-TYPE The index to the Rack PDU properties table entry. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.1 | INTEGER | read-only | mandatory |
| rPDUDevicePropertiesName OBJECT-TYPE A user-defined string identifying the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.2 | DisplayString | read-write | mandatory |
| rPDUDevicePropertiesNumOutlets OBJECT-TYPE The number of outlets on the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.3 | INTEGER | read-only | mandatory |
| rPDUDevicePropertiesNumSwdOuts OBJECT-TYPE The number of switched outlets on the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.4 | INTEGER | read-only | mandatory |
| rPDUDevicePropertiesNumMtrdOuts OBJECT-TYPE The number of metered outlets on the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.5 | INTEGER | read-only | mandatory |
| rPDUDevicePropertiesNumPhases OBJECT-TYPE The number of phases present in the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.6 | INTEGER | read-only | mandatory |
| rPDUDevicePropertiesNumBreakers OBJECT-TYPE The number of breakers present in the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.7 | INTEGER | read-only | mandatory |
| rPDUDevicePropertiesMaxCurntRtg OBJECT-TYPE The maximum current rating, measured in Amps, for the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.8 | INTEGER | read-only | mandatory |
| rPDUDevicePropertiesOutlayout OBJECT-TYPE The phase wiring for the Rack PDU outlets. PhaseToNeutral and PhaseToPhase: outlets wired consecutively; PhaseToNeutralGrouped and PhaseToPhaseGrouped: groups of outlets wired consecutively. | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.9 | INTEGER {phaseToNeutral(1), phaseToPhase(2), phaseToNeutralGrouped(3), phaseToPhaseGrouped(4)} | read-only | mandatory |
| rPDUDeviceControlTable OBJECT-TYPE A table of Rack PDU control data. | 1.3.6.1.4.1.674.10903.200.2.200.110.5 | not-accessible | mandatory | |
| rPDUDeviceControlEntry OBJECT-TYPE Control data from the Rack PDU being queried. | 1.3.6.1.4.1.674.10903.200.2.200.110.5.1 | not-accessible | mandatory | |
| rPDUDeviceControlIndex OBJECT-TYPE The index to the Rack PDU control table entry. | 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.1 | INTEGER | read-only | mandatory |
| rPDUDeviceControlName OBJECT-TYPE A user-defined string identifying the Rack PDU. | 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.2 | DisplayString | read-write | mandatory |
| rPDUDeviceControlCommand OBJECT-TYPE Setting this OID to turnAllOnNow (1) will turn all outlets on immediately. Setting this OID to turnAllOnSequence (2) will turn all outlets on as defined by each outlet's sPDUOutletPowerOnTime OID value. Setting this OID to turnAllOff (3) will turn all outlets off immediately. Setting this OID to rebootAllNow (4) will reboot all outlets immediately. Setting this OID to rebootAllSequence (5) reboots all outlets, with power returned to the outlets in the sequence defined by each outlet's rPDUOutSwitchedCfgPowerOnTime OID value. Setting this OID to rebootAllSequence (5) will cause a turnAllOffSequence to be performed. Once all outlets are off, the Rack PDU will then delay the rPDUOutSwtchedCfgRebootDuration OID time, and then perform a turnAllOnSequence. Setting this OID to turnAllOffSequence (7) will turn all outlets off as defined by each outlet's rPDUOutSwitchedCfgPowerOffTime OID value. Getting this OID will return the noCommand (6) value. | 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.3 | INTEGER {turnAllOnNow(1), turnAllOnSequence(2), turnAllOffNow(3), rebootAllNow(4), rebootAllSequence(5), noCommand(6), turnAllOffSequence(7)} | read-write | mandatory |
| rPDUPhase OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.120 | |||
| rPDUPhaseTableSize OBJECT-TYPE The number of connected Rack PDU phases. | 1.3.6.1.4.1.674.10903.200.2.200.120.1 | INTEGER | read-only | mandatory |
| rPDUPhaseStatusTable OBJECT-TYPE A table of Rack PDU phase status data. | 1.3.6.1.4.1.674.10903.200.2.200.120.2 | not-accessible | mandatory | |
| rPDUPhaseStatusEntry OBJECT-TYPE Status data from the currently queried Rack PDU phase. | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1 | not-accessible | mandatory | |
| rPDUPhaseStatusIndex OBJECT-TYPE The index to the Rack PDU phase status table entry. | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.1 | INTEGER | read-only | mandatory |
| rPDUPhaseStatusNumber OBJECT-TYPE The numeric phase ID. | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.2 | INTEGER | read-only | mandatory |
| rPDUPhaseStatusLoadState OBJECT-TYPE Indicates the present load status of the Rack PDU phase being queried. | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.3 | RpduLowNormalNearOverloadType | read-only | mandatory |
| rPDUPhaseStatusCurrent OBJECT-TYPE Indicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried. | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.4 | INTEGER | read-only | mandatory |
| rPDUPhaseStatusVoltage OBJECT-TYPE Indicates the Voltage, in Volts, of the Rack PDU phase being queried. | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.5 | INTEGER | read-only | mandatory |
| rPDUPhaseStatusPower OBJECT-TYPE Indicates the load power, in hundredths of kilowatts, consumed on the Rack PDU phase being queried. | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.6 | INTEGER | read-only | mandatory |
| rPDUPhaseConfigTable OBJECT-TYPE A table of Rack PDU phase configuration data. | 1.3.6.1.4.1.674.10903.200.2.200.120.3 | not-accessible | mandatory | |
| rPDUPhaseConfigEntry OBJECT-TYPE Configuration data from the currently queried Rack PDU phase. | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1 | not-accessible | mandatory | |
| rPDUPhaseConfigIndex OBJECT-TYPE The index to the Rack PDU phase configuration table entry. | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.1 | INTEGER | read-only | mandatory |
| rPDUPhaseConfigNumber OBJECT-TYPE The numeric phase ID. | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.2 | INTEGER | read-only | mandatory |
| rPDUPhaseCfgOverloadRestriction OBJECT-TYPE This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded. | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.3 | INTEGER {alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3)} | read-write | mandatory |
| rPDUPhCfgLowLoadCurntThreshold OBJECT-TYPE The user-defined threshold for low phase current load, in Amps. | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.4 | INTEGER | read-write | mandatory |
| rPDUPhCfgNerOverloadCurntThresh OBJECT-TYPE The user-defined near phase overload warning threshold in Amps. | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.5 | INTEGER | read-write | mandatory |
| rPDUPhCfgOverloadCurntThreshold OBJECT-TYPE The user-defined phase overload current threshold in Amps. | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.6 | INTEGER | read-write | mandatory |
| rPDUOutlet OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.130 | |||
| rPDUOutletSwitched OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.130.1 | |||
| rPDUOutletSwitchedTableSize OBJECT-TYPE The number of switched outlets on connected Rack PDUs. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.1 | INTEGER | read-only | mandatory |
| rPDUOutletSwitchedStatusTable OBJECT-TYPE A table of Rack PDU switched outlet status information. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2 | not-accessible | mandatory | |
| rPDUOutletSwitchedStatusEntry OBJECT-TYPE Status information for the currently-queried Rack PDU switched outlet. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1 | not-accessible | mandatory | |
| rPDUOutletSwitchedStatusIndex OBJECT-TYPE The index to the Rack PDU switched outlet status information table entry. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.1 | INTEGER | read-only | mandatory |
| rPDUOutletSwitchedStatusNumber OBJECT-TYPE The numeric switched outlet ID. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.2 | INTEGER | read-only | mandatory |
| rPDUOutletSwitchedStatusName OBJECT-TYPE The user-defined switched outlet ID string. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.3 | DisplayString | read-write | mandatory |
| rPDUOutletSwitchedStatusState OBJECT-TYPE Indicates the present status of the Rack PDU switched outlet being queried. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.4 | INTEGER {on(1), off(2), unknown(3)} | read-only | mandatory |
| rPDUOutletSwitchedStatCmdPnding OBJECT-TYPE Indicates whether the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices receiving power from the Rack PDU should be shut down. The Rack PDU's power should then be cycled to clear this condition. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.5 | INTEGER {commandPending(1), noCommandPending(2), commandPendingUnknown(3)} | read-only | mandatory |
| rPDUOutletSwitchedStatPhLayout OBJECT-TYPE Phase description of the currently-queried Rack PDU switched outlet. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.6 | RpduOutletPhaseLayoutType | read-only | mandatory |
| rPDUOutletSwitchedConfigTable OBJECT-TYPE A table of Rack PDU switched outlet configuration data. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3 | not-accessible | mandatory | |
| rPDUOutletSwitchedConfigEntry OBJECT-TYPE Configuration data from the currently-queried Rack PDU switched outlet. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1 | not-accessible | mandatory | |
| rPDUOutletSwitchedConfigIndex OBJECT-TYPE The index to the Rack PDU switched outlet configuration table entry. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.1 | INTEGER | read-only | mandatory |
| rPDUOutletSwitchedConfigNumber OBJECT-TYPE The numeric switched outlet ID. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.2 | INTEGER | read-only | mandatory |
| rPDUOutletSwitchedConfigName OBJECT-TYPE The user-defined switched outlet ID string. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.3 | DisplayString | read-write | mandatory |
| rPDUOutSwitchedCfgPowerOnTime OBJECT-TYPE The amount of time, in seconds, between when power is provided to the Rack PDU and when this switched outlet starts providing power. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.4 | INTEGER | read-write | mandatory |
| rPDUOutSwitchedCfgPowerOffTime OBJECT-TYPE The amount of time, in seconds, this outlet will delay turning off. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.5 | INTEGER | read-write | mandatory |
| rPDUOutSwtchedCfgRebootDuration OBJECT-TYPE After turning off power during a reboot sequence, the amount of time, in seconds, to wait before turning on power to this outlet again. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.6 | INTEGER | read-write | mandatory |
| rPDUOutletSwitchedControlTable OBJECT-TYPE A table of Rack PDU switched outlet control data. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4 | not-accessible | mandatory | |
| rPDUOutletSwitchedControlEntry OBJECT-TYPE Control data for the currently-queried Rack PDU switched outlet. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1 | not-accessible | mandatory | |
| rPDUOutletSwitchedControlIndex OBJECT-TYPE The index to the Rack PDU switched outlet control data table entry. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.1 | INTEGER | read-only | mandatory |
| rPDUOutletSwitchedControlNumber OBJECT-TYPE The numeric switched outlet ID. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.2 | INTEGER | read-only | mandatory |
| rPDUOutletSwitchedControlName OBJECT-TYPE The user-defined switched outlet ID string. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.3 | DisplayString | read-write | mandatory |
| rPDUOutletSwitchedControlCmd OBJECT-TYPE Getting this variable will return the outlet state. If the outlet is on, the outletOn (1) value will be returned. If the outlet is off, the outletOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices receiving power from the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to outletOn (1) will turn the outlet on. Setting this variable to outletOff (2) will turn the outlet off. Setting this variable to outletReboot (3) will reboot the outlet. Setting this variable to outletOnWithDelay (5) will turn the outlet on after the rPDUOutSwitchedCfgPowerOnTime OID has elapsed. Setting this variable to outletOffWithDelay (6) will turn the outlet off after the rPDUOutSwitchedCfgPowerOffTime OID has elapsed. Setting this variable to outletRebootWithDelay (7) will turn the outlet off after the rPDUOutSwitchedCfgPowerOffTime OID has elapsed, wait the rPDUOutSwtchedCfgRebootDuration OID time, then turn the outlet back on. | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.4 | INTEGER {outletOn(1), outletOff(2), outletReboot(3), outletUnknown(4), outletOnWithDelay(5), outletOffWithDelay(6), outletRebootWithDelay(7)} | read-write | mandatory |
| rPDUOutletMetered OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.130.2 | |||
| rPDUOutletMeteredTableSize OBJECT-TYPE The number of metered outlets on connected Rack PDUs. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.1 | INTEGER | read-only | mandatory |
| rPDUOutletMeteredStatusTable OBJECT-TYPE A table of Rack PDU metered outlet status data. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2 | not-accessible | mandatory | |
| rPDUOutletMeteredStatusEntry OBJECT-TYPE Status data from the currently-queried Rack PDU metered outlet. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1 | not-accessible | mandatory | |
| rPDUOutletMeteredStatusIndex OBJECT-TYPE The index to the Rack PDU metered status table entry. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.1 | INTEGER | read-only | mandatory |
| rPDUOutletMeteredStatusNumber OBJECT-TYPE The numeric metered outlet ID. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.2 | INTEGER | read-only | mandatory |
| rPDUOutletMeteredStatusName OBJECT-TYPE The user-defined metered outlet ID string. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.3 | DisplayString | read-write | mandatory |
| rPDUOutletMeteredStatusLayout OBJECT-TYPE Phase description of currently queried Rack PDU metered outlet. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.4 | RpduOutletPhaseLayoutType | read-only | mandatory |
| rPDUOutMeteredStatPowerRating OBJECT-TYPE The power rating for the currently queried Rack PDU metered outlet. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.5 | INTEGER | read-only | mandatory |
| rPDUOutletMeteredStatusCurrent OBJECT-TYPE Indicates the current draw, in Amps, of the load on the Rack PDU outlet being queried. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.6 | INTEGER | read-only | mandatory |
| rPDUOutletMeteredStatusEnergy OBJECT-TYPE A user resettable energy meter measuring Rack PDU load energy consumption in kilowatt-hours. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.7 | INTEGER | read-only | mandatory |
| rPDUOutletMeteredStatusPower OBJECT-TYPE Indicates the power draw of the load on the Rack PDU outlet being queried. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.8 | INTEGER | read-only | mandatory |
| rPDUOutletMeteredStatPeakPower OBJECT-TYPE The highest power level recorded by the currently queried Rack PDU metered outlet, in kilowatts. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.9 | INTEGER | read-only | mandatory |
| rPDUOutMeteredStatPeakPwrTime OBJECT-TYPE Indicates the date and time that peak power consumption occured | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.10 | DisplayString | read-only | mandatory |
| rPDUOutMeteredStatusLoadState OBJECT-TYPE Indicates the present load status of the Rack PDU Outlet being queried. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.11 | RpduLowNormalNearOverloadType | read-only | mandatory |
| rPDUOutletMeteredConfigTable OBJECT-TYPE A table of Rack PDU metered outlet configuration data. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4 | not-accessible | mandatory | |
| rPDUOutletMeteredConfigEntry OBJECT-TYPE Configuration data from the currently queried Rack PDU metered outlet. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1 | not-accessible | mandatory | |
| rPDUOutletMeteredConfigIndex OBJECT-TYPE The index to the Rack PDU metered outlet configuration table entry. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.1 | INTEGER | read-only | mandatory |
| rPDUOutletMeteredConfigNumber OBJECT-TYPE The numeric switched outlet ID. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.2 | INTEGER | read-only | mandatory |
| rPDUOutletMeteredConfigName OBJECT-TYPE The user-defined metered outlet ID string. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.3 | DisplayString | read-write | mandatory |
| rPDUOutMtredCfgLowLdCurntThresh OBJECT-TYPE The user-defined low load outlet current threshold, in Amps. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.4 | INTEGER | read-write | mandatory |
| rPDUOutMtrdCfgNrOvdCurntThresh OBJECT-TYPE The user-defined near outlet overload warning threshold, in Amps. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.5 | INTEGER | read-write | mandatory |
| rPDUOutMtredCfgOvrldCurntThresh OBJECT-TYPE The user-defined outlet overload current threshold, in Amps. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.6 | INTEGER | read-write | mandatory |
| rPDUOutMeteredEnergyStartTime OBJECT-TYPE The time, in hh:mm:ss, when the currently queried Rack PDU metered outlet started recording the input energy level. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.5 | DisplayString | read-only | mandatory |
| rPDUOutMeteredPeakPwrStartTime OBJECT-TYPE The time, in hh:mm:ss, when the currently queried Rack PDU metered outlet started recording the highest level of input power that is available to the connected device. | 1.3.6.1.4.1.674.10903.200.2.200.130.2.6 | DisplayString | read-only | mandatory |
| rPDUPowerSupply OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.140 | |||
| rPDUPowerSupplyAlarmD OBJECT-TYPE Getting this OID will return the status of the power supply alarm. | 1.3.6.1.4.1.674.10903.200.2.200.140.1 | INTEGER {allAvailablePowerSuppliesOK(1), powerSupplyFailed(2)} | read-only | mandatory |
| rPDUPowerSupplyVoltage OBJECT-TYPE The voltage provided by the power supply in tenths of volts. | 1.3.6.1.4.1.674.10903.200.2.200.140.2 | INTEGER | read-only | mandatory |
| rPDUSensor OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.150 | |||
| rPDUSensorStatus OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.150.1 | |||
| rPDUSensorStatusTableSize OBJECT-TYPE The number of connected temperature sensors. | 1.3.6.1.4.1.674.10903.200.2.200.150.1.1 | INTEGER | read-only | mandatory |
| rPDUSensorStatusTable OBJECT-TYPE A table of temperature sensor status data. | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2 | not-accessible | mandatory | |
| rPDUSensorStatusEntry OBJECT-TYPE Status information from the temperature sensor being queried. | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1 | not-accessible | mandatory | |
| rPDUSensorStatusIndex OBJECT-TYPE The index to the status data table entry. | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.1 | INTEGER | read-only | mandatory |
| rPDUSensorStatusName OBJECT-TYPE The user-defined sensor ID string. | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.2 | DisplayString | read-write | mandatory |
| rPDUSensorStatusType OBJECT-TYPE The type of the sensor. | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.3 | INTEGER {none(1), temperature(2), temperatureHumidity(3)} | read-only | mandatory |
| rPDUSensorTemp OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.150.2 | |||
| rPDUSensorTempTableSize OBJECT-TYPE The number of connected temperature sensors. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.1 | INTEGER | read-only | mandatory |
| rPDUSensorTempStatusTable OBJECT-TYPE A table of temperature sensor status data. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2 | not-accessible | mandatory | |
| rPDUSensorTempStatusEntry OBJECT-TYPE Status information from the temperature sensor being queried. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1 | not-accessible | mandatory | |
| rPDUSensorTempStatusIndex OBJECT-TYPE The index to the temperature status data table entry. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.1 | INTEGER | read-only | mandatory |
| rPDUSensorTempStatusName OBJECT-TYPE The user-defined temperature-humidity sensor ID string. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.2 | DisplayString | read-write | mandatory |
| rPDUSensorTempStatusCommStatus OBJECT-TYPE The communications status of the sensor. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.3 | RpduCommNoneOKLostType | read-only | mandatory |
| rPDUSensorTempStatusTempF OBJECT-TYPE The sensor temperature reading in tenths of degrees Fahrenheit. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.4 | INTEGER | read-only | mandatory |
| rPDUSensorTempStatusTempC OBJECT-TYPE The sensor temperature reading in tenths of degrees Celsius. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.5 | INTEGER | read-only | mandatory |
| rPDUSensorTempStatusAlarmStatus OBJECT-TYPE The alarm status of the sensor. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.6 | RpduNotPBMinLowNrmlOHiMaxType | read-only | mandatory |
| rPDUSensorTempConfigTable OBJECT-TYPE A table of temperature-humidity sensor configuration data. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3 | not-accessible | mandatory | |
| rPDUSensorTempConfigEntry OBJECT-TYPE Configuration data from the temperature-humidity sensor being queried. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1 | not-accessible | mandatory | |
| rPDUSensorTempConfigIndex OBJECT-TYPE The index to the temperature-humidity sensor configuration data table entry. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.1 | INTEGER | read-only | mandatory |
| rPDUSensorTempConfigName OBJECT-TYPE The user-defined temperature-humidity sensor ID string. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.2 | DisplayString | read-write | mandatory |
| rPDUSensorTempCfgTempMaxThreshF OBJECT-TYPE The sensor maximum temperature alarm threshold in Fahrenheit. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.3 | INTEGER | read-write | mandatory |
| rPDUSnsorTempCfgTempHighThreshF OBJECT-TYPE The sensor high temperature warning alarm threshold in Fahrenheit. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.4 | INTEGER | read-write | mandatory |
| rPDUSnsorTempCfgTempHysteresisF OBJECT-TYPE The sensor temperature hysteresis setting in Fahrenheit. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.5 | INTEGER | read-write | mandatory |
| rPDUSensorTempCfgTempMaxThreshC OBJECT-TYPE The sensor maximum temperature alarm threshold in Celsius. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.6 | INTEGER | read-write | mandatory |
| rPDUSnsorTempCfgTempHighThreshC OBJECT-TYPE The sensor high temperature warning alarm threshold in Celsius. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.7 | INTEGER | read-write | mandatory |
| rPDUSnsorTempCfgTempHysteresisC OBJECT-TYPE The sensor temperature hysteresis setting in Celsius. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.8 | INTEGER | read-write | mandatory |
| rPDUSnsorTempCfgAlarmGeneration OBJECT-TYPE Indicates whether the Temp Alarm Generation is enabled. | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.9 | RpduEnableDisableType | read-write | mandatory |
| rPDUSensorHumidity OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.150.3 | |||
| rPDUSensorHumidityTableSize OBJECT-TYPE The number of connected temperature-humidity sensors. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.1 | INTEGER | read-only | mandatory |
| rPDUSensorHumidityStatusTable OBJECT-TYPE A table of temperature-humidity sensor status data. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2 | not-accessible | mandatory | |
| rPDUSensorHumidityStatusEntry OBJECT-TYPE Status information from the temperature-humidity sensor being queried. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1 | not-accessible | mandatory | |
| rPDUSensorHumidityStatusIndex OBJECT-TYPE The index to the temperature-humidity status data table entry. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.1 | INTEGER | read-only | mandatory |
| rPDUSensorHumidityStatusName OBJECT-TYPE The user-defined temperature-humidity sensor ID string. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.2 | DisplayString | read-write | mandatory |
| rPDUSnsorHumidityStatCommStatus OBJECT-TYPE The communications status of the sensor. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.3 | RpduCommNoneOKLostType | read-only | mandatory |
| rPDUSnsorHumStatRelativeHumdity OBJECT-TYPE The sensor humidity reading in percent relative humidity. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.4 | INTEGER | read-only | mandatory |
| rPDUSnsorHumStatusAlarmStatus OBJECT-TYPE The alarm status of the sensor. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.5 | RpduNotPBMinLowNrmlOHiMaxType | read-only | mandatory |
| rPDUSensorHumidityConfigTable OBJECT-TYPE A table of temperature-humidity sensor configuration data. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3 | not-accessible | mandatory | |
| rPDUSensorHumidityConfigEntry OBJECT-TYPE Configuration data from the temperature-humidity sensor being queried. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1 | not-accessible | mandatory | |
| rPDUSensorHumidityConfigIndex OBJECT-TYPE The index to the temperature-humidity sensor configuration data table entry. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.1 | INTEGER | read-only | mandatory |
| rPDUSensorHumidityConfigName OBJECT-TYPE The user-defined temperature-humidity sensor ID string. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.2 | DisplayString | read-write | mandatory |
| rPDUSnsorHumCfgHumdityLowThresh OBJECT-TYPE The sensor low humidity warning alarm threshold in percent relative humidity. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.3 | INTEGER | read-write | mandatory |
| rPDUSnsorHumCfgHumdityMinThresh OBJECT-TYPE The sensor minimum humidity alarm threshold in percent relative humidity. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.4 | INTEGER | read-write | mandatory |
| rPDUSnsorHumCfgHumdtyHysteresis OBJECT-TYPE The sensor humidity hysteresis setting in percent relative humidity. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.5 | INTEGER | read-write | mandatory |
| rPDUSnsorHumCfgAlarmGeneration OBJECT-TYPE Indicates whether the Humidity Alarm Generation is enabled. | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.6 | RpduEnableDisableType | read-write | mandatory |
| rPDUSensorDiscrete OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.150.4 | |||
| rPDUSensorDiscreteTableSize OBJECT-TYPE The number of connected discrete sensors. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.1 | INTEGER | read-only | mandatory |
| rPDUSensorDiscreteStatusTable OBJECT-TYPE A table of discrete sensor status data. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2 | not-accessible | mandatory | |
| rPDUSensorDiscreteStatusEntry OBJECT-TYPE Status information from the discrete sensor being queried. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1 | not-accessible | mandatory | |
| rPDUSensorDiscreteStatusIndex OBJECT-TYPE The index to the discrete sensor status data table entry. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.1 | INTEGER | read-only | mandatory |
| rPDUSensorDiscreteStatusName OBJECT-TYPE The user-defined discrete sensor ID string. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.2 | DisplayString | read-write | mandatory |
| rPDUSnsorDiscreteStatCurntState OBJECT-TYPE The current state of the discrete sensor, open, closed, or unknown. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.3 | INTEGER {open(1), closed(2), unknown(3)} | read-only | mandatory |
| rPDUSnsorDiscreteStatAlarmState OBJECT-TYPE Indicates the alarm status of the discrete sensor input. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.4 | RpduNormalAlarmType | read-only | mandatory |
| rPDUSensorDiscreteConfigTable OBJECT-TYPE A table of discrete sensor configuration data. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3 | not-accessible | mandatory | |
| rPDUSensorDiscreteConfigEntry OBJECT-TYPE Configuration data from the discrete sensor being queried. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1 | not-accessible | mandatory | |
| rPDUSensorDiscreteConfigIndex OBJECT-TYPE The index to the discrete sensor configuration data table entry. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.1 | INTEGER | read-only | mandatory |
| rPDUSensorDiscreteConfigName OBJECT-TYPE The user-defined discrete sensor ID string. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.2 | DisplayString | read-write | mandatory |
| rPDUSnsorDiscreteCfgNormalState OBJECT-TYPE Indicates the normal state of the discrete input contact. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.3 | INTEGER {open(1), closed(2)} | read-write | mandatory |
| rPDUSnsorDiscrteAlarmGeneration OBJECT-TYPE Indicates whether Discrete Alarm Generation is enabled. | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.4 | RpduEnableDisableType | read-write | mandatory |
| mtrapargsD OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.160 | |||
| contactNumber OBJECT-TYPE This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. | 1.3.6.1.4.1.674.10903.200.2.200.160.1 | INTEGER | read-only | mandatory |
| outletNumber OBJECT-TYPE This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. | 1.3.6.1.4.1.674.10903.200.2.200.160.2 | INTEGER | read-only | mandatory |
| mtrapargsString OBJECT-TYPE This OID allows traps to be sent with an octet string argument that may not be defined in the MIB. A get of this OID will return a NULL string. | 1.3.6.1.4.1.674.10903.200.2.200.160.3 | DisplayString | read-only | mandatory |
| phaseNumber OBJECT-TYPE This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. | 1.3.6.1.4.1.674.10903.200.2.200.160.4 | INTEGER | read-only | mandatory |
| sensorNumber OBJECT-TYPE This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. | 1.3.6.1.4.1.674.10903.200.2.200.160.5 | INTEGER | read-only | mandatory |
| deviceNameD OBJECT-TYPE This OID allows traps to be sent with an octet string argument that may not be defined in the MIB. A get of this OID will return a NULL string. | 1.3.6.1.4.1.674.10903.200.2.200.160.6 | DisplayString | read-only | mandatory |
| serialNumber OBJECT-TYPE This OID allows traps to be sent with an octet string argument that may not be defined in the MIB. A get of this OID will return a NULL string. | 1.3.6.1.4.1.674.10903.200.2.200.160.7 | DisplayString | read-only | mandatory |
| testTrapargsInteger OBJECT-TYPE This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. | 1.3.6.1.4.1.674.10903.200.2.200.160.8 | INTEGER | read-only | mandatory |
| events OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.2.200.500 | |||
| system OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.3 | |||
| sysRPDUV1 OBJECT-IDENTITY | 1.3.6.1.4.1.674.10903.200.3.1 |
Notifications
| Name | OID | Status |
|---|---|---|
| deviceCommunicationLostCleared NOTIFICATION-TYPE INFORMATIONAL: Lost communication with device has been re-established. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1 | |
| deviceCommunicationLostSet NOTIFICATION-TYPE CRITICAL: Lost communication with device. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.2 | |
| componentCommLostCleared NOTIFICATION-TYPE INFORMATIONAL: Lost communication with an on board component has been re-established. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.3 | |
| componentCommLostSet NOTIFICATION-TYPE CRITICAL: Lost communication with an on board component. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.4 | |
| cANBusOffCleared NOTIFICATION-TYPE INFORMATIONAL: CAN bus off condition was cleared. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.5 | |
| canBusOffSet NOTIFICATION-TYPE MINOR: CAN bus off condition was set. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.6 | |
| powerSupplyFailureCleared NOTIFICATION-TYPE INFORMATIONAL: Unit's power supply voltage is no longer out of tolerance. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.7 | |
| powerSupplyFailureSet NOTIFICATION-TYPE CRITICAL: Unit's power supply voltage is out of tolerance. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.8 | |
| keypadButtonStuckCleared NOTIFICATION-TYPE INFORMATIONAL: Keypad button stuck has been cleared. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.9 | |
| keypadButtonStuckSet NOTIFICATION-TYPE MINOR: Keypad button stuck has been set. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.10 | |
| dryContactAbnormalCleared NOTIFICATION-TYPE INFORMATIONAL: Dry Contact is no longer in an abnormal state. The first argument is the serial number. The second argument is the device name. The third argument is the contact number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.11 | |
| dryContactAbnormalSet NOTIFICATION-TYPE CRITICAL: Dry Contact has moved to an abnormal state. The first argument is the serial number. The second argument is the device name. The third argument is the contact number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.12 | |
| deviceLowLoadCleared NOTIFICATION-TYPE INFORMATIONAL: Device load is no longer below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.13 | |
| deviceLowLoadSet NOTIFICATION-TYPE MINOR: Device load has fallen below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.14 | |
| deviceNearOverLoadCleared NOTIFICATION-TYPE INFORMATIONAL: Device load no longer exceeds the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.15 | |
| deviceNearOverLoadSet NOTIFICATION-TYPE MINOR: Device load has exceeded the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.16 | |
| deviceOverLoadCleared NOTIFICATION-TYPE INFORMATIONAL: Device load no longer exceeds the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.17 | |
| deviceOverLoadSet NOTIFICATION-TYPE CRITICAL: Device load has exceeded the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.18 | |
| phaseLowLoadCleared NOTIFICATION-TYPE INFORMATIONAL: Phase load is no longer below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.19 | |
| phaseLowLoadSet NOTIFICATION-TYPE MINOR: Phase load has fallen below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.20 | |
| phaseNearOverLoadCleared NOTIFICATION-TYPE INFORMATIONAL: Phase load no longer exceeds the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.21 | |
| phaseNearOverLoadSet NOTIFICATION-TYPE MINOR: Phase load has exceeded the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.22 | |
| phaseOverLoadCleared NOTIFICATION-TYPE INFORMATIONAL: Phase load no longer exceeds the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.23 | |
| phaseOverLoadSet NOTIFICATION-TYPE CRITICAL: Phase load has exceeded the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.24 | |
| outletLowLoadCleared NOTIFICATION-TYPE INFORMATIONAL: Outlet load is no longer below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.25 | |
| outletLowLoadSet NOTIFICATION-TYPE MINOR: Outlet load had fallen below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.26 | |
| outletNearOverLoadCleared NOTIFICATION-TYPE INFORMATIONAL: Outlet load no longer exceeds the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.27 | |
| outletNearOverLoadSet NOTIFICATION-TYPE MINOR: Outlet load has exceeded the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.28 | |
| outletOverLoadCleared NOTIFICATION-TYPE INFORMATIONAL: Outlet load no longer exceeds the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.29 | |
| outletOverLoadSet NOTIFICATION-TYPE CRITICAL: Outlet load has exceeded the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.30 | |
| sensorDisconnectedCleared NOTIFICATION-TYPE INFORMATIONAL: Sensor disconnected condition cleared. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.31 | |
| sensorDisconnectedSet NOTIFICATION-TYPE MINOR: Sensor disconnected condition set. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.32 | |
| sensorTypeIndeterminateCleared NOTIFICATION-TYPE INFORMATIONAL: Sensor type indeterminate condition cleared. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.33 | |
| sensorTypeIndeterminateSet NOTIFICATION-TYPE MINOR: Sensor type indeterminate condition set. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.34 | |
| sensorTypeUnsupportedCleared NOTIFICATION-TYPE INFORMATIONAL: Sensor type unsupported condition cleared. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.35 | |
| sensorTypeUnsupportedSet NOTIFICATION-TYPE MINOR: Sensor type unsupported condition set. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.36 | |
| maxTemperatureExceededCleared NOTIFICATION-TYPE INFORMATIONAL: Sensor Temperature no longer exceeds the 'Max Temperature' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.37 | |
| maxTemperatureExceededSet NOTIFICATION-TYPE CRITICAL: Sensor Temperature has exceeded the 'Max Temperature' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.38 | |
| highTemperatureExceededCleared NOTIFICATION-TYPE INFORMATIONAL: Sensor Temperature no longer exceeds the 'High Temperature' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.39 | |
| highTemperatureExceededSet NOTIFICATION-TYPE MINOR: Sensor Temperature has exceeded the 'High Temperature' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.40 | |
| lowHumidityExceededCleared NOTIFICATION-TYPE INFORMATIONAL: Sensor Humidity is no longer below the 'Low Humidity' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.41 | |
| lowHumidityExceededSet NOTIFICATION-TYPE MINOR: Sensor Humidity has fallen below the 'Low Humidity' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.42 | |
| minHumidityExceededCleared NOTIFICATION-TYPE INFORMATIONAL: Sensor Humidity is no longer below the 'Min Humidity' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.43 | |
| minHumidityExceededSet NOTIFICATION-TYPE CRITICAL: Sensor Humidity has fallen below the 'Min Humidity' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.44 | |
| outletTurnOn NOTIFICATION-TYPE INFORMATIONAL: An outlet has turned on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.45 | |
| outletTurnOff NOTIFICATION-TYPE INFORMATIONAL: An outlet has turned off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.46 | |
| actionCancelled NOTIFICATION-TYPE INFORMATIONAL: An outlet action has been cancelled. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.47 | |
| deviceConfigurationChange NOTIFICATION-TYPE INFORMATIONAL: A device configuration has been changed. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.48 | |
| sensorConfigurationChange NOTIFICATION-TYPE INFORMATIONAL: A sensor configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.49 | |
| outletConfigurationChange NOTIFICATION-TYPE INFORMATIONAL: An outlet configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.50 | |
| phaseConfigurationChange NOTIFICATION-TYPE INFORMATIONAL: A phase configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.51 | |
| dryContactConfigurationChange NOTIFICATION-TYPE INFORMATIONAL: A dry contact configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is the contact number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.52 | |
| actionInit NOTIFICATION-TYPE INFORMATIONAL: An outlet action has been initialized. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.53 | |
| actionFailed NOTIFICATION-TYPE MINOR: An outlet action has failed to complete. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.54 | |
| actionDeleted NOTIFICATION-TYPE INFORMATIONAL: An outlet action has been deleted. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.55 | |
| syncCommandFailed NOTIFICATION-TYPE MINOR: An outlet sync command to another unit has failed. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.56 | |
| mPOPicFwDownloadStarted NOTIFICATION-TYPE INFORMATIONAL: MPO pic fw download started. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.57 | |
| mPOPicFwDownloadComplete NOTIFICATION-TYPE INFORMATIONAL: MPO pic fw download complete. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.58 | |
| mPOPicFwDownloadAborted NOTIFICATION-TYPE INFORMATIONAL: MPO pic fw download aborted. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.59 | |
| sensorCommEstablished NOTIFICATION-TYPE INFORMATIONAL: Sensor comm established. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.60 | |
| configChangeSNMP NOTIFICATION-TYPE MINOR: The SNMP configuration has been changed. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1000 | |
| accessViolationConsole NOTIFICATION-TYPE MINOR: Someone attempted console login with incorrect password three times. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1001 | |
| accessViolationHTTP NOTIFICATION-TYPE MINOR: Someone attempted login via HTTP with incorrect password. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1002 | |
| dellTestTrap NOTIFICATION-TYPE INFORMATIONAL: Trap used to test SNMP trap functionality. The first argument is a place holder for test variables. | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1003 |