MIBs Depot

DKSF-48-4-X-X-1

Registered at
1.3.6.1.4.1.25728.48
Last updated
2015-08-13 00:00
Organization
Alentis Electronics
Revisions
2015-08-13 00:00, 2015-06-18 00:00, 2015-05-28 00:00, 2015-05-06 00:00, 2015-03-26 00:00, 2013-11-01 00:00, 2013-04-11 00:00, 2012-05-31 00:00, 2012-04-17 00:00, 2012-03-23 00:00, 2011-09-23 00:00, 2011-03-24 00:00, 2010-10-14 00:00, 2010-09-20 00:00, 2010-05-31 00:00, 2010-04-14 00:00
Namespace
netping
Source file
DKSF-48-4-X-X-1
Digest
sha256:d91d1690dd77313607f91697842a451296d619514aae8a55cd3d1af61f65a8c0

Description

Generic MIB for NetPing remote sensing and control

Contact

developers@netping.ru

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-MIBsnmpTraps
SNMPv2-SMICounter32, Counter64, Gauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION, TimeStamp, TruthValue

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

DKSF-48-4-X-X-1
SNMPv2-CONF
SNMPv2-MIB
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
lightcom
OBJECT-IDENTITY
1.3.6.1.4.1.25728
npReboot
OBJECT-IDENTITY
1.3.6.1.4.1.25728.911
npSoftReboot
OBJECT-TYPE
Write 1 to reboot device after current operations completition
1.3.6.1.4.1.25728.911.1INTEGERread-writecurrent
npResetStack
OBJECT-TYPE
Write 1 to re-initialize network stack
1.3.6.1.4.1.25728.911.2INTEGERread-writecurrent
npForcedReboot
OBJECT-TYPE
Write 1 to immediate forced reboot
1.3.6.1.4.1.25728.911.3INTEGERread-writecurrent
npGsm
OBJECT-IDENTITY
1.3.6.1.4.1.25728.3800
npGsmInfo
OBJECT-IDENTITY
1.3.6.1.4.1.25728.3800.1
npGsmFailed
OBJECT-TYPE
Firmware's GSM module status
1.3.6.1.4.1.25728.3800.1.1INTEGER {ok(0), failed(1), fatalError(2)}read-onlycurrent
npGsmRegistration
OBJECT-TYPE
Status of modem registration in GSM network (AT+CREG? result)
1.3.6.1.4.1.25728.3800.1.2INTEGER {impossible(0), homeNetwork(1), searching(2), denied(3), unknown(4), roaming(5), infoUpdate(255)}read-onlycurrent
npGsmStrength
OBJECT-TYPE
GSM signal strength. 0..31 = 0..100%, 99 = unknown or n/a, 255 = updating info
1.3.6.1.4.1.25728.3800.1.3INTEGER (0..255)read-onlycurrent
npGsmSendSms
OBJECT-TYPE
Send arbitrary SMS. Format: [phone_number,phone_number,...] Message One to four destination phone numbers If [] and numbers omitted, mesagge will be sent to preset numbers from SMS setup Only Latin characters allowed in message body
1.3.6.1.4.1.25728.3800.1.9DisplayStringread-writecurrent
npGsmTraps
OBJECT-IDENTITY
1.3.6.1.4.1.25728.3800.2
npGsmTrapPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.25728.3800.2.0
npRelay
OBJECT-IDENTITY
1.3.6.1.4.1.25728.5500
npRelayTable
OBJECT-TYPE
Watchdog and outlet/relay control table
1.3.6.1.4.1.25728.5500.5not-accessiblecurrent
npRelayEntry
OBJECT-TYPE
Relay/outlet table row
1.3.6.1.4.1.25728.5500.5.1not-accessiblecurrent
npRelayN
OBJECT-TYPE
The N of output relay
1.3.6.1.4.1.25728.5500.5.1.1INTEGER (1..8)read-onlycurrent
npRelayMode
OBJECT-TYPE
Control of relay: 0 - manual off 1 - manual on 2 - watchdog 3 - schedule 4 - both schedule and watchdog (while switched on by schedule) 5 - logic
1.3.6.1.4.1.25728.5500.5.1.2INTEGER {off(0), on(1), watchdog(2), schedule(3), scheduleAndWatchdog(4), logic(5)}read-writecurrent
npRelayStartReset
OBJECT-TYPE
Write 1 to start reset (switch relay off for some time)
1.3.6.1.4.1.25728.5500.5.1.3INTEGERread-writecurrent
npRelayMemo
OBJECT-TYPE
Relay memo
1.3.6.1.4.1.25728.5500.5.1.6DisplayStringread-onlycurrent
npRelayFlip
OBJECT-TYPE
Write -1 to flip between manual on and manual off states of relay
1.3.6.1.4.1.25728.5500.5.1.14INTEGER {flip(-1)}read-onlycurrent
npRelayState
OBJECT-TYPE
Actual relay state at the moment, regardless of source of control. 0 - relay is off 1 - relay is on
1.3.6.1.4.1.25728.5500.5.1.15INTEGER {off(0), on(1)}read-onlycurrent
npRelayPowered
OBJECT-TYPE
AC presence on output. 0 - no AC dew to relay switched off or no ac on input 1 - AC is present
1.3.6.1.4.1.25728.5500.5.1.16INTEGER {no(0), yes(1)}read-onlycurrent
npPwr
OBJECT-IDENTITY
1.3.6.1.4.1.25728.5800
npPwrTable
OBJECT-TYPE
Watchdog and outlet/relay control table
1.3.6.1.4.1.25728.5800.3not-accessiblecurrent
npPwrEntry
OBJECT-TYPE
Watchdog control table row
1.3.6.1.4.1.25728.5800.3.1not-accessiblecurrent
npPwrChannelN
OBJECT-TYPE
The id of watchdog/power channel
1.3.6.1.4.1.25728.5800.3.1.1INTEGER (1..4)read-onlycurrent
npPwrStartReset
OBJECT-TYPE
Deprecated in current FW version: Write 1 to start forced reset. On read: 0 - normal operation 1 - reset is active 2 - reboot pause is active or watchdog is inactive
1.3.6.1.4.1.25728.5800.3.1.2INTEGER (0..2)read-onlyobsolete
npPwrResetsCounter
OBJECT-TYPE
Counter of watchdog resets Write 0 to clear.
1.3.6.1.4.1.25728.5800.3.1.4INTEGER (0..65535)read-writecurrent
npPwrRepeatingResetsCounter
OBJECT-TYPE
Counter of continous failed watchdog resets
1.3.6.1.4.1.25728.5800.3.1.5INTEGER (0..65535)read-onlycurrent
npPwrMemo
OBJECT-TYPE
Watchdog channel memo
1.3.6.1.4.1.25728.5800.3.1.6DisplayStringread-onlycurrent
npIr
OBJECT-IDENTITY
1.3.6.1.4.1.25728.7900
npIrCtrl
OBJECT-IDENTITY
1.3.6.1.4.1.25728.7900.1
npIrPlayCmd
OBJECT-TYPE
Write IR command number to send IR command
1.3.6.1.4.1.25728.7900.1.1INTEGER (1..16)read-writecurrent
npIrReset
OBJECT-TYPE
Write 1 to reset IR transiever. After reset, send IR command and check npIrStatus.
1.3.6.1.4.1.25728.7900.1.2INTEGER (0..1)read-writecurrent
npIrStatus
OBJECT-TYPE
IR transiever status
1.3.6.1.4.1.25728.7900.1.3INTEGER {commandCompleted(0), protocolError(1), commandAccepted(2), errorUnknown(16), errorBadNumber(17), errorEmptyRecord(18), errorFlashChip(19), errorTimeout(20), errorExtBusBusy(21)}read-onlycurrent
npSmoke
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8200
npSmokeTable
OBJECT-TYPE
Smoke Sensors Table
1.3.6.1.4.1.25728.8200.1not-accessiblecurrent
npSmokeEntry
OBJECT-TYPE
Smoke Sensors Table Row
1.3.6.1.4.1.25728.8200.1.1not-accessiblecurrent
npSmokeSensorN
OBJECT-TYPE
The id of 1Wire Smoke sensor, 1 to 4
1.3.6.1.4.1.25728.8200.1.1.1INTEGER (1..4)read-onlycurrent
npSmokeStatus
OBJECT-TYPE
Status of Smoke sensor
1.3.6.1.4.1.25728.8200.1.1.2INTEGER {ok(0), alarm(1), off(4), failed(5)}read-onlycurrent
npSmokePower
OBJECT-TYPE
Controls power on Smoke sensor current loop
1.3.6.1.4.1.25728.8200.1.1.3INTEGER {off(0), on(1)}read-writecurrent
npSmokeReset
OBJECT-TYPE
Write 1 to switch off for approx. 10s to reset sensor
1.3.6.1.4.1.25728.8200.1.1.4INTEGERread-writecurrent
npSmokeMemo
OBJECT-TYPE
Smoke sensor memo
1.3.6.1.4.1.25728.8200.1.1.6DisplayStringread-onlycurrent
npSmokeTraps
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8200.2
npSmokeTrapPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8200.2.0
npSmokeTrapSensorN
OBJECT-TYPE
The id of 1Wire Smoke sensor, 1 to 4
1.3.6.1.4.1.25728.8200.2.1INTEGER (1..4)read-onlycurrent
npSmokeTrapStatus
OBJECT-TYPE
New status of Smoke sensor
1.3.6.1.4.1.25728.8200.2.2INTEGER {ok(0), alarm(1), off(4), failed(5)}read-onlycurrent
npSmokeTrapMemo
OBJECT-TYPE
Smoke sensor memo
1.3.6.1.4.1.25728.8200.2.6DisplayStringread-onlycurrent
npRelHumidity
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8400
npRelHumSensor
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8400.2
npRelHumSensorValueH
OBJECT-TYPE
Relative humidity value, %
1.3.6.1.4.1.25728.8400.2.2INTEGER (0..100)read-onlycurrent
npRelHumSensorStatus
OBJECT-TYPE
Status of the Rel.Humidity Sensor One 1=Normal, 0=Error or Sensor isn't connected
1.3.6.1.4.1.25728.8400.2.3INTEGER {error(0), ok(1)}read-onlycurrent
npRelHumSensorValueT
OBJECT-TYPE
Sensor temperature, deg.C
1.3.6.1.4.1.25728.8400.2.4INTEGER (-60..200)read-onlycurrent
npRelHumSensorStatusH
OBJECT-TYPE
Status of Relative Humiduty
1.3.6.1.4.1.25728.8400.2.5INTEGER {sensorFailed(0), belowSafeRange(1), inSafeRange(2), aboveSafeRange(3)}read-onlycurrent
npRelHumSafeRangeHigh
OBJECT-TYPE
Relative Humidity safe range, top margin, %RH
1.3.6.1.4.1.25728.8400.2.7INTEGER (0..100)read-onlycurrent
npRelHumSafeRangeLow
OBJECT-TYPE
Relative Humidity safe range, bottom margin, %RH
1.3.6.1.4.1.25728.8400.2.8INTEGER (0..100)read-onlycurrent
npRelHumSensorValueT100
OBJECT-TYPE
Sensor temperature, deg.C * 100 (fixed point two decimal places) Used to get access to the fractional part of T value
1.3.6.1.4.1.25728.8400.2.9Integer32read-onlycurrent
npRelHumTraps
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8400.9
npRelHumTrapPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8400.9.0
npThermo
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8800
npThermoTable
OBJECT-TYPE
Thermo Sensors Table
1.3.6.1.4.1.25728.8800.1not-accessiblecurrent
npThermoEntry
OBJECT-TYPE
Thermo Sensors Table Row
1.3.6.1.4.1.25728.8800.1.1not-accessiblecurrent
npThermoSensorN
OBJECT-TYPE
The id of temperature sensor, 1 to 8
1.3.6.1.4.1.25728.8800.1.1.1INTEGER (1..8)read-onlycurrent
npThermoValue
OBJECT-TYPE
Temperature, deg.C
1.3.6.1.4.1.25728.8800.1.1.2INTEGER (-60..280)read-onlycurrent
npThermoStatus
OBJECT-TYPE
Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)
1.3.6.1.4.1.25728.8800.1.1.3INTEGER {failed(0), low(1), norm(2), high(3)}read-onlycurrent
npThermoLow
OBJECT-TYPE
Bottom margin of normal temperature range, deg.C
1.3.6.1.4.1.25728.8800.1.1.4INTEGER (-60..280)read-onlycurrent
npThermoHigh
OBJECT-TYPE
Top margin of normal temperature range, deg.C
1.3.6.1.4.1.25728.8800.1.1.5INTEGER (-60..280)read-onlycurrent
npThermoMemo
OBJECT-TYPE
T channel memo
1.3.6.1.4.1.25728.8800.1.1.6DisplayStringread-onlycurrent
npThermoTraps
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8800.2
npThermoTrapPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8800.2.0
npThermoTrapSensorN
OBJECT-TYPE
The id of temperature sensor, 1 to 8
1.3.6.1.4.1.25728.8800.2.1INTEGER (1..8)read-onlycurrent
npThermoTrapValue
OBJECT-TYPE
Temperature, deg.C
1.3.6.1.4.1.25728.8800.2.2INTEGER (-60..280)read-onlycurrent
npThermoTrapStatus
OBJECT-TYPE
Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)
1.3.6.1.4.1.25728.8800.2.3INTEGER {failed(0), low(1), norm(2), high(3)}read-onlycurrent
npThermoTrapLow
OBJECT-TYPE
Bottom margin of normal temperature range, deg.C
1.3.6.1.4.1.25728.8800.2.4INTEGER (-60..280)read-onlycurrent
npThermoTrapHigh
OBJECT-TYPE
Top margin of normal temperature range, deg.C
1.3.6.1.4.1.25728.8800.2.5INTEGER (-60..280)read-onlycurrent
npThermoTrapMemo
OBJECT-TYPE
T channel memo
1.3.6.1.4.1.25728.8800.2.6DisplayStringread-onlycurrent
npIo
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8900
npIoTable
OBJECT-TYPE
Digital Input/output Table
1.3.6.1.4.1.25728.8900.1not-accessiblecurrent
npIoEntry
OBJECT-TYPE
Digital Input/output Table Row
1.3.6.1.4.1.25728.8900.1.1not-accessiblecurrent
npIoLineN
OBJECT-TYPE
Number of IO line, from 1 to max supported
1.3.6.1.4.1.25728.8900.1.1.1INTEGER (1..4)read-onlycurrent
npIoLevelIn
OBJECT-TYPE
Input level, 0 or 1
1.3.6.1.4.1.25728.8900.1.1.2INTEGER (0..1)read-onlycurrent
npIoLevelOut
OBJECT-TYPE
Output level, 0 or 1
1.3.6.1.4.1.25728.8900.1.1.3INTEGER (0..1)read-writecurrent
npIoMemo
OBJECT-TYPE
IO line memo
1.3.6.1.4.1.25728.8900.1.1.6DisplayStringread-onlycurrent
npIoPulseCounter
OBJECT-TYPE
Pulse Counter on IO input line (counts positive fronts) Write 0 to reset.
1.3.6.1.4.1.25728.8900.1.1.9Counter32read-writecurrent
npIoSinglePulseDuration
OBJECT-TYPE
Set duration of single pulse on IO output line, 100ms to 25500ms, min. step is 100ms
1.3.6.1.4.1.25728.8900.1.1.12INTEGER (100..25500)read-writecurrent
npIoSinglePulseStart
OBJECT-TYPE
Write 1 to start single pulse on IO output. Output will be inverted for time, specified by npIoSinglePulseDuration
1.3.6.1.4.1.25728.8900.1.1.13INTEGERread-writecurrent
npIoTraps
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8900.2
npIoTrapPrefix
OBJECT-IDENTITY
1.3.6.1.4.1.25728.8900.2.0
npIoTrapLineN
OBJECT-TYPE
Trap data, Number of IO line
1.3.6.1.4.1.25728.8900.2.1INTEGER (1..2)read-onlycurrent
npIoTrapLevelIn
OBJECT-TYPE
Trap data, new Input level, 0 or 1
1.3.6.1.4.1.25728.8900.2.2INTEGER (0..1)read-onlycurrent
npIoTrapMemo
OBJECT-TYPE
Trap data, IO line memo
1.3.6.1.4.1.25728.8900.2.6DisplayStringread-onlycurrent

Notifications

NameOIDStatus
npGsmTrap
NOTIFICATION-TYPE
GSM modem or SMS firmware problems
1.3.6.1.4.1.25728.3800.2.0.1current
npSmokeTrap
NOTIFICATION-TYPE
Status of 1W Smoke sensor has changed
1.3.6.1.4.1.25728.8200.2.0.1current
npRelHumTrap
NOTIFICATION-TYPE
Status of Relative Humidity RH sensor has changed!
1.3.6.1.4.1.25728.8400.9.0.1current
npThermoTrap
NOTIFICATION-TYPE
Status of Thermo sensor is changed (crossing of normal temp. range)
1.3.6.1.4.1.25728.8800.2.0.1current
npIoTrap
NOTIFICATION-TYPE
Input state of IO line is changed
1.3.6.1.4.1.25728.8900.2.0.1current