DKSF-253-6-X-A-X
- Registered at
- 1.3.6.1.4.1.25728.2531.3.6.1.4.1.25728.9700
- Last updated
- 2015-09-29 00:00
- Organization
- Alentis Electronics
- Revisions
- 2015-09-29 00:00, 2014-11-19 00:00, 2014-06-12 00:00, 2011-02-04 00:00, 2010-08-30 00:00, 2010-08-20 00:00, 2010-08-13 00:00, 2010-08-11 00:00, 2010-07-08 00:00, 2010-04-14 00:00
- Namespace
- netping
- Source file
DKSF-253-6-X-A-X- Digest
sha256:f7240e5843b2db44700b6db44c5d0d1827f629acf9166a947cbf14b07200c155
Description
MIB for NetPing remote sensing and control
Contact
developers@netping.ru
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-MIB | snmpTraps |
| SNMPv2-SMI | Counter32, Counter64, Gauge32, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, enterprises, iso, mib-2 |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION, TimeStamp, TruthValue |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
DKSF-253-6-X-A-X SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| lightcom OBJECT-IDENTITY | 1.3.6.1.4.1.25728 | |||
| npReboot OBJECT-IDENTITY | 1.3.6.1.4.1.25728.911 | |||
| npSoftReboot OBJECT-TYPE Write 1 to reboot device after current operations completition | 1.3.6.1.4.1.25728.911.1 | INTEGER | read-write | current |
| npResetStack OBJECT-TYPE Write 1 to re-initialize network stack | 1.3.6.1.4.1.25728.911.2 | INTEGER | read-write | current |
| npForcedReboot OBJECT-TYPE Write 1 to immediate forced reboot | 1.3.6.1.4.1.25728.911.3 | INTEGER | read-write | current |
| npIo OBJECT-IDENTITY | 1.3.6.1.4.1.25728.8900 | |||
| npIoTable OBJECT-TYPE Digital Input/output Table | 1.3.6.1.4.1.25728.8900.1 | not-accessible | current | |
| npIoEntry OBJECT-TYPE Digital Input/output Table Row | 1.3.6.1.4.1.25728.8900.1.1 | not-accessible | current | |
| npIoLineN OBJECT-TYPE Number of IO line, from 1 to max supported | 1.3.6.1.4.1.25728.8900.1.1.1 | INTEGER (1..4) | read-only | current |
| npIoLevelIn OBJECT-TYPE Input level, 0 or 1 | 1.3.6.1.4.1.25728.8900.1.1.2 | INTEGER (0..1) | read-only | current |
| npIoLevelOut OBJECT-TYPE Output level, 0 or 1. Write -1 to flip output. | 1.3.6.1.4.1.25728.8900.1.1.3 | INTEGER {flip(-1), low(0), high(1)} | read-write | current |
| npIoMemo OBJECT-TYPE IO line memo | 1.3.6.1.4.1.25728.8900.1.1.6 | DisplayString | read-only | current |
| npIoPulseCounter OBJECT-TYPE Pulse Counter (counts positive fronts) Write 0 to reset. | 1.3.6.1.4.1.25728.8900.1.1.9 | Counter32 | read-write | current |
| npIoSinglePulseDuration OBJECT-TYPE Set duration of single pulse on IO output line, 100ms to 25500ms, min. step is 100ms | 1.3.6.1.4.1.25728.8900.1.1.12 | INTEGER (100..25500) | read-write | current |
| npIoSinglePulseStart OBJECT-TYPE Write 1 to start single pulse on IO output. Output will be inverted for time, specified by npIoSinglePulseDuration | 1.3.6.1.4.1.25728.8900.1.1.13 | INTEGER | read-write | current |
| npIoTraps OBJECT-IDENTITY | 1.3.6.1.4.1.25728.8900.2 | |||
| npIoTrapPrefix OBJECT-IDENTITY | 1.3.6.1.4.1.25728.8900.2.0 | |||
| npIoTrapLineN OBJECT-TYPE Trap data, Number of IO line | 1.3.6.1.4.1.25728.8900.2.1 | INTEGER (1..4) | read-only | current |
| npIoTrapLevelIn OBJECT-TYPE Trap data, new Input level, 0 or 1 | 1.3.6.1.4.1.25728.8900.2.2 | INTEGER (0..1) | read-only | current |
| npIoTrapMemo OBJECT-TYPE Trap data, IO line memo | 1.3.6.1.4.1.25728.8900.2.6 | DisplayString | read-only | current |
| npIoTrapLevelIn1 OBJECT-TYPE Trap data, current Input level Line 1, value 0 or 1 | 1.3.6.1.4.1.25728.8900.2.21 | INTEGER (0..1) | read-only | current |
| npIoTrapLevelIn2 OBJECT-TYPE Trap data, current Input level Line 2, value 0 or 1 | 1.3.6.1.4.1.25728.8900.2.22 | INTEGER (0..1) | read-only | current |
| npIoTrapLevelIn3 OBJECT-TYPE Trap data, current Input level Line 3, value 0 or 1 | 1.3.6.1.4.1.25728.8900.2.23 | INTEGER (0..1) | read-only | current |
| npIoTrapLevelIn4 OBJECT-TYPE Trap data, current Input level Line 4, value 0 or 1 | 1.3.6.1.4.1.25728.8900.2.24 | INTEGER (0..1) | read-only | current |
| npElecMeter OBJECT-IDENTITY | 1.3.6.1.4.1.25728.9700 | |||
| npElecTable OBJECT-TYPE Electricity Meter Table | 1.3.6.1.4.1.25728.9700.1 | not-accessible | current | |
| npElecEntry OBJECT-TYPE Electricity Meter Table Table Row | 1.3.6.1.4.1.25728.9700.1.1 | not-accessible | current | |
| npElecIndex OBJECT-TYPE Number of elec.meter, associated with IO line | 1.3.6.1.4.1.25728.9700.1.1.1 | INTEGER (1..4) | read-only | current |
| npElecPulsesPerKwh OBJECT-TYPE Pulses on IO line input per 1 kWh of consumed energy | 1.3.6.1.4.1.25728.9700.1.1.2 | INTEGER | read-write | current |
| npElecPower OBJECT-TYPE Power, Watts, based on pulse rate/interval, 5 minute average | 1.3.6.1.4.1.25728.9700.1.1.3 | Gauge32 | read-only | current |
| npElecEnergy OBJECT-TYPE Energy counter, kWh, based on pulse count | 1.3.6.1.4.1.25728.9700.1.1.4 | Counter32 | read-write | current |
| npElecEnergy100 OBJECT-TYPE Energy counter, kWh*100, based on pulse count | 1.3.6.1.4.1.25728.9700.1.1.5 | Counter32 | read-write | current |
Notifications
| Name | OID | Status |
|---|---|---|
| npIoTrap NOTIFICATION-TYPE Input state of IO line is changed | 1.3.6.1.4.1.25728.8900.2.0.1 | current |