Objects

NameOIDSyntaxAccessStatus
danthermCooling
OBJECT-IDENTITY
1.3.6.1.4.1.46651
controllerCC3000
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1
systemStatus
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.1
onBoardTempr
OBJECT-TYPE
Controller On-Board temperature in Degree Celcius
1.3.6.1.4.1.46651.1.1.1INTEGER (-41..101)read-onlymandatory
roomTempr
OBJECT-TYPE
Room Sensor or Zone 1 Sensor temperature in Degree Celcius
1.3.6.1.4.1.46651.1.1.2INTEGER (-41..101)read-onlymandatory
hotSpotTempr
OBJECT-TYPE
Hot Spot Sensor or Zone 2 Sensor temperature in Degree Celcius
1.3.6.1.4.1.46651.1.1.3INTEGER (-41..101)read-onlymandatory
outdoor1Tempr
OBJECT-TYPE
Ambient Sensor 1 or Zone 1 Ambient Sensor. temperature in Degree Celcius
1.3.6.1.4.1.46651.1.1.4INTEGER (-41..101)read-onlymandatory
outdoor2Tempr
OBJECT-TYPE
Ambient Sensor 2 or Zone 2 Ambient Sensor. temperature in Degree Celcius
1.3.6.1.4.1.46651.1.1.5INTEGER (-41..101)read-onlymandatory
shelterTempr
OBJECT-TYPE
Shelter Temperature. Valid for Single-Zone solution
1.3.6.1.4.1.46651.1.1.6INTEGER (-41..101)read-onlymandatory
outdoorCombinedTempr
OBJECT-TYPE
Cobined minimum Outdoor Temeperature. Valid for Single-Zone solution
1.3.6.1.4.1.46651.1.1.7INTEGER (-41..101)read-onlymandatory
fan1RPM
OBJECT-TYPE
Fan 1 Rotation Per Minute
1.3.6.1.4.1.46651.1.1.8INTEGER (0..10000)read-onlymandatory
fan2RPM
OBJECT-TYPE
Fan 2 Rotation Per Minute
1.3.6.1.4.1.46651.1.1.9INTEGER (0..10000)read-onlymandatory
fan1SpeedPercentage
OBJECT-TYPE
Fan 1 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal
1.3.6.1.4.1.46651.1.1.10INTEGER (0..100)read-onlymandatory
fan2SpeedPercentage
OBJECT-TYPE
Fan 2 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal
1.3.6.1.4.1.46651.1.1.11INTEGER (0..100)read-onlymandatory
damper1Position
OBJECT-TYPE
Damper 1 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open
1.3.6.1.4.1.46651.1.1.12INTEGER (0..100)read-onlymandatory
damper2Position
OBJECT-TYPE
Damper 2 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open
1.3.6.1.4.1.46651.1.1.13INTEGER (0..100)read-onlymandatory
humidity
OBJECT-TYPE
Internal or external humidity in Rh%
1.3.6.1.4.1.46651.1.1.14INTEGER (0..100)read-onlymandatory
dewpoint
OBJECT-TYPE
Internal or external DewPoint based on Humidity; in Degree Celcius
1.3.6.1.4.1.46651.1.1.15INTEGER (-41..101)read-onlymandatory
atmosphericPressure
OBJECT-TYPE
Atmospheric pressure or Pressure of installed enclosure in KiloPascal
1.3.6.1.4.1.46651.1.1.16INTEGER (0..10000)read-onlymandatory
flowPressure
OBJECT-TYPE
Filter flow Pressure in Pascal
1.3.6.1.4.1.46651.1.1.17INTEGER (-1000..1000)read-onlymandatory
fan1Status
OBJECT-TYPE
Fan 1 operation status. 0 - Off; 1 - On -; 2 - Emergency/Boost
1.3.6.1.4.1.46651.1.1.18INTEGER (0..2)read-onlymandatory
fan2Status
OBJECT-TYPE
Fan 2 operation status. 0 - Off; 1 - On -; 2 - Emergency/Boost
1.3.6.1.4.1.46651.1.1.19INTEGER (0..2)read-onlymandatory
damper1Status
OBJECT-TYPE
Damper 1 operation status. 0 - Closed; 1 - Open; 2 - Dynamic or Temperature Compensation; 2 - Emergency/Boost
1.3.6.1.4.1.46651.1.1.20INTEGER (0..3)read-onlymandatory
damper2Status
OBJECT-TYPE
Damper 2 Shutter Open Percentage. 0 - Closed; 1 - Open; 2 - Dynamic or Temperature Compensation; 2 - Emergency/Boost
1.3.6.1.4.1.46651.1.1.21INTEGER (0..3)read-onlymandatory
aircond1Status
OBJECT-TYPE
Airconditioner 1 operation status. 0 - Off; 1 - Restart timeout; 2 - On
1.3.6.1.4.1.46651.1.1.22INTEGER (0..2)read-onlymandatory
aircond2Status
OBJECT-TYPE
Airconditioner 2 operation status. 0 - Off; 1 - Restart timeout; 2 - On
1.3.6.1.4.1.46651.1.1.23INTEGER (0..2)read-onlymandatory
heaterStatus
OBJECT-TYPE
heater operation status. 0 - Off; 1 - On
1.3.6.1.4.1.46651.1.1.24INTEGER (0..1)read-onlymandatory
shelter1Status
OBJECT-TYPE
Shelter Status in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively. 0 - Inactive or None State 1 - Heating State 2 - Re-Cycling State 3 - Free Cooling State 4 - Active or Aircon Coolign State 5 - Emergency State 6 - Intermediate state( strategy transistion)
1.3.6.1.4.1.46651.1.1.25INTEGER (0..6)read-onlymandatory
shelter2Status
OBJECT-TYPE
Shelter Status in Dual-Zone mode or Zone 2 Status. 0 - Inactive or None State 1 - Heating State 2 - Re-Cycling State 3 - Free Cooling State 4 - Active or Aircon Coolign State 5 - Emergency State 6 - Intermediate state( strategy transistion)
1.3.6.1.4.1.46651.1.1.26INTEGER (0..6)read-onlymandatory
shelter1Mode
OBJECT-TYPE
Shelter Run time mode in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively. 0 - Free Cooling Mode 1 - Standard Mode 2 - Power Save Mode 3 - Air conditioner Mode
1.3.6.1.4.1.46651.1.1.27INTEGER (0..3)read-onlymandatory
shelter2Mode
OBJECT-TYPE
Shelter Run time mode in Dual-Zone mode or Zone 2 Status. 0 - Free Cooling Mode 1 - Standard Mode 2 - Power Save Mode 3 - Air conditioner Mode
1.3.6.1.4.1.46651.1.1.28INTEGER (0..3)read-onlymandatory
shelter1Setpoint
OBJECT-TYPE
Shelter run time Cooling Set point in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively. Cooling setpoint can be offset by following functions RH function Night mode Digital inputs
1.3.6.1.4.1.46651.1.1.29INTEGER (-41..80)read-onlymandatory
shelter2Setpoint
OBJECT-TYPE
Shelter run time Cooling Set point in Dual-Zone mode or Zone 2 Status. Cooling setpoint can be offset by following functions RH function Night mode Digital inputs
1.3.6.1.4.1.46651.1.1.30INTEGER (-41..80)read-onlymandatory
errorStatus
OBJECT-TYPE
controller internal error status. Binary bit position - alarm drive state: 0 - inactive , 1 - active 0 - voltage low 1 - voltage high 2 - tempr low 3 - tempr limit 1 4 - tempr limit 2 5 - tempr limit 3 6 - humid. low 7 - humid. high 8 - fltr pressure 1 9 - fltr pressure 2 10 - fan 1 11 - fan 2 12 - onboard sens 13 - room sens 14 - hotspot sens 15 - ambient 1 sens 16 - ambient 2 sens 17 - dig 1 i/p 18 - dig 2 i/p 19 - dig 3 i/p 20 - filter i/p 1 21 - filter i/p 2 22 - network 23 - int storage 24 - sd card
1.3.6.1.4.1.46651.1.1.31INTEGER (0..33554432)read-onlymandatory
maskedErrorStatus
OBJECT-TYPE
Controller Output Error status. Binary Bit Position - Alarm Drive State: 0 - Inactive , 1 - Active 0 - Voltage Low 1 - Voltage High 2 - Tempr Low 3 - Tempr Limit 1 4 - Tempr Limit 2 5 - Tempr Limit 3 6 - Humid. Low 7 - Humid. High 8 - Fltr Pressure 1 9 - Fltr Pressure 2 10 - Fan 1 11 - Fan 2 12 - Onboard Sens 13 - Room Sens 14 - Hotspot Sens 15 - Ambient 1 Sens 16 - Ambient 2 Sens 17 - Dig 1 I/P 18 - Dig 2 I/P 19 - Dig 3 I/P 20 - Filter I/P 1 21 - Filter I/P 2 22 - Network 23 - Int storage 24 - SD Card
1.3.6.1.4.1.46651.1.1.32INTEGER (0..33554432)read-onlymandatory
voltage
OBJECT-TYPE
System Voltage in DC.
1.3.6.1.4.1.46651.1.1.33INTEGER (0..80)read-onlymandatory
digitalInputStatus
OBJECT-TYPE
Controller Alarm Drive Status. Binary Bit Position - Digital Input State: 0 - Inactive , 1 - Active 0 - DIG 1 I/P 1 - DIG 2 I/P 2 - DIG 3 I/P 3 - FILTER GUARD DIGI 1 I/P 4 - FILTER GUARD DIGI 2 I/P
1.3.6.1.4.1.46651.1.1.34INTEGER (0..16)read-onlymandatory
alarmDriveStatus
OBJECT-TYPE
Controller Alarm Drive Status. Binary Bit Position - Alarm Drive State: 0 - Inactive , 1 - Active 0 - ALARM 1 1 - ALARM 2 2 - ALARM 3 3 - ALARM 4 4 - ALARM 5 5 - ALARM 6 6 - ALARM 7 7 - ALARM 8 8 - ALARM 9 9 - ALARM 10
1.3.6.1.4.1.46651.1.1.35INTEGER (0..1024)read-onlymandatory
fan1OpertdurHour
OBJECT-TYPE
Fan 1 operation duration - Hour
1.3.6.1.4.1.46651.1.1.36INTEGER (0..65535)read-writemandatory
fan1OpertdurMin
OBJECT-TYPE
Fan 1 operation duration - Minute
1.3.6.1.4.1.46651.1.1.37INTEGER (0..59)read-writemandatory
fan2OpertdurHour
OBJECT-TYPE
Fan 2 operation duration - Hour
1.3.6.1.4.1.46651.1.1.38INTEGER (0..65535)read-writemandatory
fan2OpertdurMin
OBJECT-TYPE
Fan 2 operation duration - Minute
1.3.6.1.4.1.46651.1.1.39INTEGER (0..59)read-writemandatory
aircon1OpertdurHour
OBJECT-TYPE
Airconditioner 1 operation duration - Hour
1.3.6.1.4.1.46651.1.1.40INTEGER (0..65535)read-writemandatory
aircon1OpertdurMin
OBJECT-TYPE
Airconditioner 1 operation duration - Minute
1.3.6.1.4.1.46651.1.1.41INTEGER (0..59)read-writemandatory
aircon2OpertdurHour
OBJECT-TYPE
Airconditioner 2 operation duration - Hour
1.3.6.1.4.1.46651.1.1.42INTEGER (0..65535)read-writemandatory
aircon2OpertdurMin
OBJECT-TYPE
Airconditioner 2 operation duration - Minute
1.3.6.1.4.1.46651.1.1.43INTEGER (0..59)read-writemandatory
heaterOpertdurHour
OBJECT-TYPE
Heater operation duration - Hour
1.3.6.1.4.1.46651.1.1.44INTEGER (0..65535)read-writemandatory
heaterOpertdurMin
OBJECT-TYPE
Heater operation duration - Minute
1.3.6.1.4.1.46651.1.1.45INTEGER (0..59)read-writemandatory
ccSN
OBJECT-TYPE
CC3000 Controller serial number
1.3.6.1.4.1.46651.1.1.46OCTET STRINGread-writemandatory
fanbox1SN
OBJECT-TYPE
Free cooling FanBox unit 1 serial number
1.3.6.1.4.1.46651.1.1.47OCTET STRINGread-writemandatory
fanbox2SN
OBJECT-TYPE
Free cooling FanBox unit 2 serial number
1.3.6.1.4.1.46651.1.1.48OCTET STRINGread-writemandatory
aircond1SN
OBJECT-TYPE
Aicodnitioner unit 1 serial number
1.3.6.1.4.1.46651.1.1.49OCTET STRINGread-writemandatory
aircond2SN
OBJECT-TYPE
Aicodnitioner unit 2 serial number
1.3.6.1.4.1.46651.1.1.50OCTET STRINGread-writemandatory
fwVersion
OBJECT-TYPE
CC3000 Firmware version
1.3.6.1.4.1.46651.1.1.51OCTET STRINGread-onlymandatory
highlevelControl
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.2
coolSetpointZone1
OBJECT-TYPE
Cooling Setpoint Zone/Shelter 1
1.3.6.1.4.1.46651.1.2.1INTEGER (-41..101)read-writemandatory
coolSetpointZone2
OBJECT-TYPE
Cooling Setpoint Zone/Shelter 2
1.3.6.1.4.1.46651.1.2.2INTEGER (-41..101)read-writemandatory
heaterSetpoint
OBJECT-TYPE
Heater Setpoint
1.3.6.1.4.1.46651.1.2.3INTEGER (-41..101)read-writemandatory
backupConfig
OBJECT-TYPE
Configuration Backup to Internal memory and SD card. 0 - No change, 1 - Backup
1.3.6.1.4.1.46651.1.2.4INTEGER (0..1)read-writemandatory
restoreConfig
OBJECT-TYPE
Configuration restore from Internal memory. 0 - No change, 1 - Restore
1.3.6.1.4.1.46651.1.2.5INTEGER (0..1)read-writemandatory
systemReset
OBJECT-TYPE
Colling System reset or restart. 0 - No change, 1 - Restart
1.3.6.1.4.1.46651.1.2.6INTEGER (0..1)read-writemandatory
year
OBJECT-TYPE
Calender - Year
1.3.6.1.4.1.46651.1.2.7INTEGER (2015..2099)read-writemandatory
month
OBJECT-TYPE
Calender - Month
1.3.6.1.4.1.46651.1.2.8INTEGER (1..12)read-writemandatory
date
OBJECT-TYPE
Calender - Date
1.3.6.1.4.1.46651.1.2.9INTEGER (1..31)read-writemandatory
hour
OBJECT-TYPE
Clock - Hour
1.3.6.1.4.1.46651.1.2.10INTEGER (0..23)read-writemandatory
minute
OBJECT-TYPE
Clock - Minute
1.3.6.1.4.1.46651.1.2.11INTEGER (0..59)read-writemandatory
fan1Config
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.3
saveReloadConff1
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.3.1INTEGER (0..1)read-writemandatory
offTemprf1
OBJECT-TYPE
Fan OFF temperature
1.3.6.1.4.1.46651.1.3.2INTEGER (-41..101)read-writemandatory
idleOnTemprf1
OBJECT-TYPE
Fan Idle Speed On temperature
1.3.6.1.4.1.46651.1.3.3INTEGER (-41..101)read-writemandatory
idleEntryTemprf1
OBJECT-TYPE
Idle entry temperature
1.3.6.1.4.1.46651.1.3.4INTEGER (-41..101)read-writemandatory
midPoint1Temprf1
OBJECT-TYPE
Mid point 1 entry temperature
1.3.6.1.4.1.46651.1.3.5INTEGER (-41..101)read-writemandatory
setPointTemprf1
OBJECT-TYPE
Set Point temperature
1.3.6.1.4.1.46651.1.3.6INTEGER (-41..101)read-writemandatory
midPoint2Temprf1
OBJECT-TYPE
Mid point 2 entry temperature
1.3.6.1.4.1.46651.1.3.7INTEGER (-41..101)read-writemandatory
highSpeedTemprf1
OBJECT-TYPE
high Speed entry temperature
1.3.6.1.4.1.46651.1.3.8INTEGER (-41..101)read-writemandatory
extendHighSpeedEntryTemprf1
OBJECT-TYPE
Extended high Speed entry temperature
1.3.6.1.4.1.46651.1.3.9INTEGER (-41..101)read-writemandatory
extendHighSpeedExitTemprf1
OBJECT-TYPE
Extended high Speed exit temperature
1.3.6.1.4.1.46651.1.3.10INTEGER (-41..101)read-writemandatory
boostEntryTemprf1
OBJECT-TYPE
Boost Speed entry temperature
1.3.6.1.4.1.46651.1.3.11INTEGER (-41..101)read-writemandatory
boostExitTemprf1
OBJECT-TYPE
Boost Speed entry temperature
1.3.6.1.4.1.46651.1.3.12INTEGER (-41..101)read-writemandatory
idleRPMf1
OBJECT-TYPE
Idle speed RPM
1.3.6.1.4.1.46651.1.3.13INTEGER (0..9999)read-writemandatory
midPointRPMf1
OBJECT-TYPE
Midpoint Speed RPM
1.3.6.1.4.1.46651.1.3.14INTEGER (0..9999)read-writemandatory
highSpeedRPMf1
OBJECT-TYPE
high Speed RPM
1.3.6.1.4.1.46651.1.3.15INTEGER (0..9999)read-writemandatory
extendHighSpeedRPMf1
OBJECT-TYPE
Extended high Speed RPM
1.3.6.1.4.1.46651.1.3.16INTEGER (0..9999)read-writemandatory
idleDutyCyclef1
OBJECT-TYPE
Idle Speed Duty Cycle
1.3.6.1.4.1.46651.1.3.17INTEGER (0..100)read-writemandatory
midDutyCyclef1
OBJECT-TYPE
Midpoint speed Duty Cycle
1.3.6.1.4.1.46651.1.3.18INTEGER (0..100)read-writemandatory
highSpeedDutyCyclef1
OBJECT-TYPE
high speed Duty Cycle
1.3.6.1.4.1.46651.1.3.19INTEGER (0..100)read-writemandatory
extendHighSpeedDutyCyclef1
OBJECT-TYPE
Extended high speed Duty Cycle
1.3.6.1.4.1.46651.1.3.20INTEGER (0..100)read-writemandatory
boostDutyCyclef1
OBJECT-TYPE
Boost speed Duty Cycle
1.3.6.1.4.1.46651.1.3.21INTEGER (0..100)read-writemandatory
deadBandRPMf1
OBJECT-TYPE
Dead band RPM
1.3.6.1.4.1.46651.1.3.22INTEGER (0..1000)read-writemandatory
overrideDigi1f1
OBJECT-TYPE
0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.3.23INTEGER (0..120)read-writemandatory
overrideDigi2f1
OBJECT-TYPE
0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.3.24INTEGER (0..120)read-writemandatory
overrideDigi3f1
OBJECT-TYPE
0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.3.25INTEGER (0..120)read-writemandatory
overrideSensorfailf1
OBJECT-TYPE
0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.3.26INTEGER (0..120)read-writemandatory
sensorSelectf1
OBJECT-TYPE
0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature
1.3.6.1.4.1.46651.1.3.27INTEGER (0..5)read-writemandatory
tachoPulseperrotationf1
OBJECT-TYPE
Number of Tacho pulses per cycle rotation for given fan
1.3.6.1.4.1.46651.1.3.28INTEGER (0..100)read-writemandatory
closedLoopenablef1
OBJECT-TYPE
Closed Loop control enable or disable for given Fan. 0 - Enable. 1 - Disable
1.3.6.1.4.1.46651.1.3.29INTEGER (0..1)read-writemandatory
controlTypef1
OBJECT-TYPE
0 - 0-10V DC control. 1 - PWM control
1.3.6.1.4.1.46651.1.3.30INTEGER (0..1)read-writemandatory
enablef1
OBJECT-TYPE
0 - Disable Fan control. 1 - Enabel fan control
1.3.6.1.4.1.46651.1.3.31INTEGER (0..1)read-writemandatory
fan2Config
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.4
saveReloadConff2
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.4.1INTEGER (0..1)read-writemandatory
offTemprf2
OBJECT-TYPE
Fan OFF temperature
1.3.6.1.4.1.46651.1.4.2INTEGER (-41..101)read-writemandatory
idleOnTemprf2
OBJECT-TYPE
Fan Idle Speed On temperature
1.3.6.1.4.1.46651.1.4.3INTEGER (-41..101)read-writemandatory
idleEntryTemprf2
OBJECT-TYPE
Idle entry temperature
1.3.6.1.4.1.46651.1.4.4INTEGER (-41..101)read-writemandatory
midPoint1Temprf2
OBJECT-TYPE
Mid point 1 entry temperature
1.3.6.1.4.1.46651.1.4.5INTEGER (-41..101)read-writemandatory
setPointTemprf2
OBJECT-TYPE
Set Point temperature
1.3.6.1.4.1.46651.1.4.6INTEGER (-41..101)read-writemandatory
midPoint2Temprf2
OBJECT-TYPE
Mid point 2 entry temperature
1.3.6.1.4.1.46651.1.4.7INTEGER (-41..101)read-writemandatory
highSpeedTemprf2
OBJECT-TYPE
high Speed entry temperature
1.3.6.1.4.1.46651.1.4.8INTEGER (-41..101)read-writemandatory
extendHighSpeedEntryTemprf2
OBJECT-TYPE
Extended high Speed entry temperature
1.3.6.1.4.1.46651.1.4.9INTEGER (-41..101)read-writemandatory
extendHighSpeedExitTemprf2
OBJECT-TYPE
Extended high Speed exit temperature
1.3.6.1.4.1.46651.1.4.10INTEGER (-41..101)read-writemandatory
boostEntryTemprf2
OBJECT-TYPE
Boost Speed entry temperature
1.3.6.1.4.1.46651.1.4.11INTEGER (-41..101)read-writemandatory
boostExitTemprf2
OBJECT-TYPE
Boost Speed entry temperature
1.3.6.1.4.1.46651.1.4.12INTEGER (-41..101)read-writemandatory
idleRPMf2
OBJECT-TYPE
Idle speed RPM
1.3.6.1.4.1.46651.1.4.13INTEGER (0..9999)read-writemandatory
midPointRPMf2
OBJECT-TYPE
Midpoint Speed RPM
1.3.6.1.4.1.46651.1.4.14INTEGER (0..9999)read-writemandatory
highSpeedRPMf2
OBJECT-TYPE
high Speed RPM
1.3.6.1.4.1.46651.1.4.15INTEGER (0..9999)read-writemandatory
extendHighSpeedRPMf2
OBJECT-TYPE
Extended high Speed RPM
1.3.6.1.4.1.46651.1.4.16INTEGER (0..9999)read-writemandatory
idleDutyCyclef2
OBJECT-TYPE
Idle Speed Duty Cycle
1.3.6.1.4.1.46651.1.4.17INTEGER (0..100)read-writemandatory
midDutyCyclef2
OBJECT-TYPE
Midpoint speed Duty Cycle
1.3.6.1.4.1.46651.1.4.18INTEGER (0..100)read-writemandatory
highSpeedDutyCyclef2
OBJECT-TYPE
high speed Duty Cycle
1.3.6.1.4.1.46651.1.4.19INTEGER (0..100)read-writemandatory
extendHighSpeedDutyCyclef2
OBJECT-TYPE
Extended high speed Duty Cycle
1.3.6.1.4.1.46651.1.4.20INTEGER (0..100)read-writemandatory
boostDutyCyclef2
OBJECT-TYPE
Boost speed Duty Cycle
1.3.6.1.4.1.46651.1.4.21INTEGER (0..100)read-writemandatory
deadBandRPMf2
OBJECT-TYPE
Dead band RPM
1.3.6.1.4.1.46651.1.4.22INTEGER (0..1000)read-writemandatory
overrideDigi1f2
OBJECT-TYPE
0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.4.23INTEGER (0..120)read-writemandatory
overrideDigi2f2
OBJECT-TYPE
0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.4.24INTEGER (0..120)read-writemandatory
overrideDigi3f2
OBJECT-TYPE
0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.4.25INTEGER (0..120)read-writemandatory
overrideSensorfailf2
OBJECT-TYPE
0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.4.26INTEGER (0..120)read-writemandatory
sensorSelectf2
OBJECT-TYPE
0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature
1.3.6.1.4.1.46651.1.4.27INTEGER (0..5)read-writemandatory
tachoPulseperrotationf2
OBJECT-TYPE
Number of Tacho pulses per cycle rotation for given fan
1.3.6.1.4.1.46651.1.4.28INTEGER (0..100)read-writemandatory
closedLoopenablef2
OBJECT-TYPE
Closed Loop control enable or disable for given Fan. 0 - Enable. 1 - Disable
1.3.6.1.4.1.46651.1.4.29INTEGER (0..1)read-writemandatory
controlTypef2
OBJECT-TYPE
0 - 0-10V DC control. 1 - PWM control
1.3.6.1.4.1.46651.1.4.30INTEGER (0..1)read-writemandatory
enablef2
OBJECT-TYPE
0 - Disable Fan control. 1 - Enabel fan control
1.3.6.1.4.1.46651.1.4.31INTEGER (0..1)read-writemandatory
damper1Config
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.5
saveReloadConfd1
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.5.1INTEGER (0..1)read-writemandatory
lowercloseTemprd1
OBJECT-TYPE
Damper lower closing temperature
1.3.6.1.4.1.46651.1.5.2INTEGER (-41..101)read-writemandatory
setPointd1
OBJECT-TYPE
Damper opening temperature
1.3.6.1.4.1.46651.1.5.3INTEGER (-41..101)read-writemandatory
upperOpentempd1
OBJECT-TYPE
Damper upper opening temperature
1.3.6.1.4.1.46651.1.5.4INTEGER (-41..101)read-writemandatory
upperClosetempd1
OBJECT-TYPE
Damper upper closing temperature
1.3.6.1.4.1.46651.1.5.5INTEGER (-41..101)read-writemandatory
emgncyClosetempd1
OBJECT-TYPE
Damper emergency closing temperature
1.3.6.1.4.1.46651.1.5.6INTEGER (-41..101)read-writemandatory
emgncyopentempd1
OBJECT-TYPE
Damper emergency open temperature
1.3.6.1.4.1.46651.1.5.7INTEGER (-41..101)read-writemandatory
overrideDigi1d1
OBJECT-TYPE
0 - Damper close. 1 - Damper open. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.5.8INTEGER (0..120)read-writemandatory
overrideDigi2d1
OBJECT-TYPE
0 - Damper close. 1 - Damper open. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.5.9INTEGER (0..120)read-writemandatory
overrideDigi3d1
OBJECT-TYPE
0 - Damper close. 1 - Damper open. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.5.10INTEGER (0..120)read-writemandatory
overrideSensorFaild1
OBJECT-TYPE
0 - Damper close. 1 - Damper open. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.5.11INTEGER (0..120)read-writemandatory
sensSelectd1
OBJECT-TYPE
0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature
1.3.6.1.4.1.46651.1.5.12INTEGER (0..5)read-writemandatory
runDurationd1
OBJECT-TYPE
Damper Run time in minutes
1.3.6.1.4.1.46651.1.5.13INTEGER (30..300)read-writemandatory
enabled1
OBJECT-TYPE
0 - Disable. 1 - ONOFF. 2 - Dynamic
1.3.6.1.4.1.46651.1.5.14INTEGER (0..2)read-writemandatory
damper2Config
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.6
saveReloadConfd2
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.6.1INTEGER (0..1)read-writemandatory
lowercloseTemprd2
OBJECT-TYPE
Damper lower closing temperature
1.3.6.1.4.1.46651.1.6.2INTEGER (-41..101)read-writemandatory
setPointd2
OBJECT-TYPE
Damper opening temperature
1.3.6.1.4.1.46651.1.6.3INTEGER (-41..101)read-writemandatory
upperOpentempd2
OBJECT-TYPE
Damper upper opening temperature
1.3.6.1.4.1.46651.1.6.4INTEGER (-41..101)read-writemandatory
upperClosetempd2
OBJECT-TYPE
Damper upper closing temperature
1.3.6.1.4.1.46651.1.6.5INTEGER (-41..101)read-writemandatory
emgncyClosetempd2
OBJECT-TYPE
Damper emergency closing temperature
1.3.6.1.4.1.46651.1.6.6INTEGER (-41..101)read-writemandatory
emgncyopentempd2
OBJECT-TYPE
Damper emergency open temperature
1.3.6.1.4.1.46651.1.6.7INTEGER (-41..101)read-writemandatory
overrideDigi1d2
OBJECT-TYPE
0 - Damper close. 1 - Damper open. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.6.8INTEGER (0..120)read-writemandatory
overrideDigi2d2
OBJECT-TYPE
0 - Damper close. 1 - Damper open. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.6.9INTEGER (0..120)read-writemandatory
overrideDigi3d2
OBJECT-TYPE
0 - Damper close. 1 - Damper open. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.6.10INTEGER (0..120)read-writemandatory
overrideSensorFaild2
OBJECT-TYPE
0 - Damper close. 1 - Damper open. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.6.11INTEGER (0..120)read-writemandatory
sensSelectd2
OBJECT-TYPE
0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature
1.3.6.1.4.1.46651.1.6.12INTEGER (0..5)read-writemandatory
runDurationd2
OBJECT-TYPE
Damper Run time in minutes
1.3.6.1.4.1.46651.1.6.13INTEGER (30..300)read-writemandatory
enabled2
OBJECT-TYPE
0 - Disable. 1 - ONOFF. 2 - Dynamic
1.3.6.1.4.1.46651.1.6.14INTEGER (0..2)read-writemandatory
aircon1Config
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.7
saveReloadConfac1
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.7.1INTEGER (0..1)read-writemandatory
oNTemprac1
OBJECT-TYPE
Air Conditioner ON temperature
1.3.6.1.4.1.46651.1.7.2INTEGER (-41..101)read-writemandatory
oFFTemprac1
OBJECT-TYPE
Air Conditioner OFF temperature
1.3.6.1.4.1.46651.1.7.3INTEGER (-41..101)read-writemandatory
overrideDigi1ac1
OBJECT-TYPE
0 - AC OFF. 1 - AC ON. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.7.4INTEGER (0..120)read-writemandatory
overrideDigi2ac1
OBJECT-TYPE
0 - AC OFF. 1 - AC ON. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.7.5INTEGER (0..120)read-writemandatory
overrideDigi3ac1
OBJECT-TYPE
0 - AC OFF. 1 - AC ON. 120 - No action on Over ride
1.3.6.1.4.1.46651.1.7.6INTEGER (0..120)read-writemandatory
overrideSensorFailac1
OBJECT-TYPE
0 - AC OFF. 1 - AC ON. 120 - No action on Over ride
1.3.6.1.4.1.46651.1.7.7INTEGER (0..120)read-writemandatory
sensSelectac1
OBJECT-TYPE
0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature
1.3.6.1.4.1.46651.1.7.8INTEGER (0..5)read-writemandatory
minimumRunDurationac1
OBJECT-TYPE
Minimum AC Run time in seconds
1.3.6.1.4.1.46651.1.7.9INTEGER (60..3600)read-writemandatory
restartTimeoutac1
OBJECT-TYPE
Restart timer in seconds
1.3.6.1.4.1.46651.1.7.10INTEGER (60..3600)read-writemandatory
enableac1
OBJECT-TYPE
0 - Disable. 1 - Enable.
1.3.6.1.4.1.46651.1.7.11INTEGER (0..1)read-writemandatory
aircon2Config
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.8
saveReloadConfac2
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.8.1INTEGER (0..1)read-writemandatory
onTemprac2
OBJECT-TYPE
Air Conditioner ON temperature
1.3.6.1.4.1.46651.1.8.2INTEGER (-41..101)read-writemandatory
offTemprac2
OBJECT-TYPE
Air Conditioner OFF temperature
1.3.6.1.4.1.46651.1.8.3INTEGER (-41..101)read-writemandatory
overrideDigi1ac2
OBJECT-TYPE
0 - AC OFF. 1 - AC ON. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.8.4INTEGER (0..120)read-writemandatory
overrideDigi2ac2
OBJECT-TYPE
0 - AC OFF. 1 - AC ON. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.8.5INTEGER (0..120)read-writemandatory
overrideDigi3ac2
OBJECT-TYPE
0 - AC OFF. 1 - AC ON. 120 - No action on Over ride
1.3.6.1.4.1.46651.1.8.6INTEGER (0..120)read-writemandatory
overrideSensorFailac2
OBJECT-TYPE
0 - AC OFF. 1 - AC ON. 120 - No action on Over ride
1.3.6.1.4.1.46651.1.8.7INTEGER (0..120)read-writemandatory
sensSelectac2
OBJECT-TYPE
0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature
1.3.6.1.4.1.46651.1.8.8INTEGER (0..5)read-writemandatory
minimumRunDurationac2
OBJECT-TYPE
Minimum AC Run time in seconds
1.3.6.1.4.1.46651.1.8.9INTEGER (60..3600)read-writemandatory
restartTimeoutac2
OBJECT-TYPE
Restart timer in seconds
1.3.6.1.4.1.46651.1.8.10INTEGER (60..3600)read-writemandatory
enableac2
OBJECT-TYPE
0 - Disable. 1 - Enable.
1.3.6.1.4.1.46651.1.8.11INTEGER (0..1)read-writemandatory
heaterConfig
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.9
saveReloadConfhtr
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.9.1INTEGER (0..1)read-writemandatory
onTemprhtr
OBJECT-TYPE
Heater ON temperature
1.3.6.1.4.1.46651.1.9.2INTEGER (-41..101)read-writemandatory
offTemprhtr
OBJECT-TYPE
Heater OFF temperature
1.3.6.1.4.1.46651.1.9.3INTEGER (-41..101)read-writemandatory
overrideDigi1htr
OBJECT-TYPE
0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.9.4INTEGER (0..120)read-writemandatory
overrideDigi2htr
OBJECT-TYPE
0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride.
1.3.6.1.4.1.46651.1.9.5INTEGER (0..120)read-writemandatory
overrideDigi3htr
OBJECT-TYPE
0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride
1.3.6.1.4.1.46651.1.9.6INTEGER (0..120)read-writemandatory
overrideSensorFailhtr
OBJECT-TYPE
0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride
1.3.6.1.4.1.46651.1.9.7INTEGER (0..120)read-writemandatory
sensSelecthtr
OBJECT-TYPE
0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature
1.3.6.1.4.1.46651.1.9.8INTEGER (0..5)read-writemandatory
enablehtr
OBJECT-TYPE
0 - Disable. 1 - Enable.
1.3.6.1.4.1.46651.1.9.9INTEGER (0..1)read-writemandatory
humidityConfig
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.10
saveReloadConfhum
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.10.1INTEGER (0..1)read-writemandatory
rhEntryhum
OBJECT-TYPE
Humidity function entry value
1.3.6.1.4.1.46651.1.10.2INTEGER (40..100)read-writemandatory
rhExithum
OBJECT-TYPE
Humidity function exit value
1.3.6.1.4.1.46651.1.10.3INTEGER (40..100)read-writemandatory
coolingmodehum
OBJECT-TYPE
0 - Freecooling. 1 - Standard. 2 - Power save. 3 - Aircon.
1.3.6.1.4.1.46651.1.10.4INTEGER (0..3)read-writemandatory
temprsetpoffsethum
OBJECT-TYPE
Cooling setpoint offset
1.3.6.1.4.1.46651.1.10.5INTEGER (-10..10)read-writemandatory
rhSensPositionhum
OBJECT-TYPE
0 - Indoor. 1 - Outdoor
1.3.6.1.4.1.46651.1.10.6INTEGER (0..1)read-writemandatory
enablehum
OBJECT-TYPE
0 - Disable. 1 - Enable.
1.3.6.1.4.1.46651.1.10.7INTEGER (0..1)read-writemandatory
systemConfig
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.11
saveReloadConfsysc
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.11.1INTEGER (0..1)read-writemandatory
vdcLowEntrysys
OBJECT-TYPE
Low voltage shut down entry
1.3.6.1.4.1.46651.1.11.2INTEGER (18..60)read-writemandatory
vdcLowExitsys
OBJECT-TYPE
Low voltage shut down exit
1.3.6.1.4.1.46651.1.11.3INTEGER (18..60)read-writemandatory
vdcHighEntrysys
OBJECT-TYPE
High voltage shut down entry
1.3.6.1.4.1.46651.1.11.4INTEGER (18..60)read-writemandatory
vdcHighExitsys
OBJECT-TYPE
High voltage shut down exit
1.3.6.1.4.1.46651.1.11.5INTEGER (18..60)read-writemandatory
temprLowlimitsys
OBJECT-TYPE
Low temperature alarm limit
1.3.6.1.4.1.46651.1.11.6INTEGER (-40..80)read-writemandatory
temprHighlimit1sys
OBJECT-TYPE
High temperature alarm limit 1
1.3.6.1.4.1.46651.1.11.7INTEGER (-40..80)read-writemandatory
temprHighlimit2sys
OBJECT-TYPE
High temperature alarm limit 2
1.3.6.1.4.1.46651.1.11.8INTEGER (-40..80)read-writemandatory
temprHighlimit3sys
OBJECT-TYPE
High temperature alarm limit 3
1.3.6.1.4.1.46651.1.11.9INTEGER (-40..80)read-writemandatory
temprlimithyssys
OBJECT-TYPE
Temperature alarm limit hysteresis
1.3.6.1.4.1.46651.1.11.10INTEGER (-20..20)read-writemandatory
rhLowlimitsys
OBJECT-TYPE
Humidity alarm low limit %RH
1.3.6.1.4.1.46651.1.11.11INTEGER (0..100)read-writemandatory
rhHighlimitsys
OBJECT-TYPE
Humidity alarm High limit %RH
1.3.6.1.4.1.46651.1.11.12INTEGER (0..100)read-writemandatory
flowpresslimit1sys
OBJECT-TYPE
Flow pressure limit 1 Pa
1.3.6.1.4.1.46651.1.11.13INTEGER (60..400)read-writemandatory
flowpresslimit2sys
OBJECT-TYPE
Flow pressure limit 2 Pa
1.3.6.1.4.1.46651.1.11.14INTEGER (60..400)read-writemandatory
flowpresshyssys
OBJECT-TYPE
Flow pressure limit hysteresis Pa
1.3.6.1.4.1.46651.1.11.15INTEGER (0..400)read-writemandatory
coolingzonessys
OBJECT-TYPE
1 - One cooling zone, 2 - Two cooling zones
1.3.6.1.4.1.46651.1.11.16INTEGER (1..2)read-writemandatory
coolingModesys
OBJECT-TYPE
0 - FC, 1 - Std, 2 - Ps, 3 - Acon
1.3.6.1.4.1.46651.1.11.17INTEGER (0..3)read-writemandatory
negCoolingDeltaOverridesys
OBJECT-TYPE
0 - Disable, 1 - Enable
1.3.6.1.4.1.46651.1.11.18INTEGER (0..1)read-writemandatory
negCoolingDeltaHyssys
OBJECT-TYPE
Negative cooling delta hysteresis
1.3.6.1.4.1.46651.1.11.19INTEGER (-10..10)read-writemandatory
coolingDeltatempsys
OBJECT-TYPE
Cooling delta temperature
1.3.6.1.4.1.46651.1.11.20INTEGER (-10..10)read-writemandatory
shelterTemprsys
OBJECT-TYPE
0 - RA, 1 - HS, 2 - Both
1.3.6.1.4.1.46651.1.11.21INTEGER (0..2)read-writemandatory
acleadlagsys
OBJECT-TYPE
0 - Disable, 1 - Enable
1.3.6.1.4.1.46651.1.11.22INTEGER (0..1)read-writemandatory
coolingModeXzonesys
OBJECT-TYPE
0 - FC, 1 - Std, 2 - Ps, 3 - Acon
1.3.6.1.4.1.46651.1.11.23INTEGER (0..3)read-writemandatory
negCoolingDeltaOverrideXzonesys
OBJECT-TYPE
0 - Disable, 1 - Enable
1.3.6.1.4.1.46651.1.11.24INTEGER (0..1)read-writemandatory
negCoolingDeltaHysXzonesys
OBJECT-TYPE
Negative cooling delta hysteresis
1.3.6.1.4.1.46651.1.11.25INTEGER (-10..10)read-writemandatory
coolingDeltatempXzonesys
OBJECT-TYPE
Cooling delta temperature
1.3.6.1.4.1.46651.1.11.26INTEGER (-10..10)read-writemandatory
fan1Zonesys
OBJECT-TYPE
1 - Fan 1 for Zone 1, 2 - Fan 1 for zone 2
1.3.6.1.4.1.46651.1.11.27INTEGER (1..2)read-writemandatory
fan2Zonesys
OBJECT-TYPE
1 - Fan 2 for Zone 1, 2 - Fan 2 for zone 2
1.3.6.1.4.1.46651.1.11.28INTEGER (1..2)read-writemandatory
ac1Zonesys
OBJECT-TYPE
1 - AC 1 for Zone 1, 2 - AC 1 for zone 2
1.3.6.1.4.1.46651.1.11.29INTEGER (1..2)read-writemandatory
ac2Zonesys
OBJECT-TYPE
1 - AC 2 for Zone 1, 2 - AC 2 for zone 2
1.3.6.1.4.1.46651.1.11.30INTEGER (1..2)read-writemandatory
damper1Zonesys
OBJECT-TYPE
1 - Damper 1 for Zone 1, 2 - Damper 1 for zone 2
1.3.6.1.4.1.46651.1.11.31INTEGER (1..2)read-writemandatory
damper2Zonesys
OBJECT-TYPE
1 - Damper 2 for Zone 1, 2 - Damper 2 for zone 2
1.3.6.1.4.1.46651.1.11.32INTEGER (1..2)read-writemandatory
heaterZonesys
OBJECT-TYPE
1 - Heater for Zone 1, 2 - Heater for zone 2
1.3.6.1.4.1.46651.1.11.33INTEGER (1..2)read-writemandatory
statusLogsys
OBJECT-TYPE
0 - Disable, 1 - Enable
1.3.6.1.4.1.46651.1.11.34INTEGER (0..1)read-writemandatory
logintervalsys
OBJECT-TYPE
Log interval in minutes
1.3.6.1.4.1.46651.1.11.35INTEGER (1..60)read-writemandatory
alarm1NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.36INTEGER (0..1)read-writemandatory
alarm2NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.37INTEGER (0..1)read-writemandatory
alarm3NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.38INTEGER (0..1)read-writemandatory
alarm4NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.39INTEGER (0..1)read-writemandatory
alarm5NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.40INTEGER (0..1)read-writemandatory
alarm6NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.41INTEGER (0..1)read-writemandatory
alarm7NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.42INTEGER (0..1)read-writemandatory
alarm8NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.43INTEGER (0..1)read-writemandatory
alarm9NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.44INTEGER (0..1)read-writemandatory
alarm10NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.45INTEGER (0..1)read-writemandatory
alarm1Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.46INTEGER (0..100)read-writemandatory
alarm2Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.47INTEGER (0..100)read-writemandatory
alarm3Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.48INTEGER (0..100)read-writemandatory
alarm4Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.49INTEGER (0..100)read-writemandatory
alarm5Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.50INTEGER (0..100)read-writemandatory
alarm6Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.51INTEGER (0..100)read-writemandatory
alarm7Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.52INTEGER (0..100)read-writemandatory
alarm8Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.53INTEGER (0..100)read-writemandatory
alarm9Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.54INTEGER (0..100)read-writemandatory
alarm10Delaysys
OBJECT-TYPE
Alarm output delay in seconds
1.3.6.1.4.1.46651.1.11.55INTEGER (0..100)read-writemandatory
ac1NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.56INTEGER (0..1)read-writemandatory
ac2NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.57INTEGER (0..1)read-writemandatory
dig1NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.58INTEGER (0..1)read-writemandatory
dig2NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.59INTEGER (0..1)read-writemandatory
dig3NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.60INTEGER (0..1)read-writemandatory
dig2funcoverridesys
OBJECT-TYPE
0 - Override, 1 - setpoint offset, 2 - mode X
1.3.6.1.4.1.46651.1.11.61INTEGER (0..2)read-writemandatory
dig3funcoverridesys
OBJECT-TYPE
0 - Override, 1 - setpoint offset, 2 - mode X
1.3.6.1.4.1.46651.1.11.62INTEGER (0..2)read-writemandatory
dig2offsetsys
OBJECT-TYPE
Cooling setpoint offset
1.3.6.1.4.1.46651.1.11.63INTEGER (-10..10)read-writemandatory
dig3offsetsys
OBJECT-TYPE
Cooling setpoint offset
1.3.6.1.4.1.46651.1.11.64INTEGER (-10..10)read-writemandatory
dig2trigModesys
OBJECT-TYPE
0 - FC, 1 - Std, 2 - Ps, 3 - Acon
1.3.6.1.4.1.46651.1.11.65INTEGER (0..3)read-writemandatory
dig3TrigModesys
OBJECT-TYPE
0 - FC, 1 - Std, 2 - Ps, 3 - Acon
1.3.6.1.4.1.46651.1.11.66INTEGER (0..3)read-writemandatory
filterGuard1NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.67INTEGER (0..1)read-writemandatory
filterGuard2NONCsys
OBJECT-TYPE
0 - NO, 1 - NC
1.3.6.1.4.1.46651.1.11.68INTEGER (0..1)read-writemandatory
temprUnitsCFsys
OBJECT-TYPE
0 - Celcius, 1 - Fahrenheit
1.3.6.1.4.1.46651.1.11.69INTEGER (0..1)read-writemandatory
languageEnglishsys
OBJECT-TYPE
0 - Disable, 1 - Enable
1.3.6.1.4.1.46651.1.11.70INTEGER (0..1)read-writemandatory
alarmConfig
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.12
saveReloadConfAlm
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Alarm Mapping reloaded
1.3.6.1.4.1.46651.1.12.1INTEGER (0..1)read-writemandatory
alarm1mask
OBJECT-TYPE
Alarm drive 1 Mask [Can have multiple Alarm Errors]. Bit Position - Value - Alarm Drive State: 0 - Unselect, 1 - Select 1 - 1 - Voltage Low 2 - 2 - Voltage High 3 - 4 - Tempr Low 4 - 8 - Tempr Limit 1 5 - 16 - Tempr Limit 2 6 - 32 - Tempr Limit 3 7 - 64 - Humid. Low 8 - 128 - Humid. High 9 - 256 - Fltr Pressure 1 10 - 512 - Fltr Pressure 2 11 - 1024 - Fan 1 12 - 2048 - Fan 2 13 - 4096 - Onboard Sens 14 - 8192 - Room Sens 15 - 16384 - Hotspot Sens 16 - 32768 - Ambient 1 Sens 17 - 65536 - Ambient 2 Sens 18 - 131072 - Dig 1 I/P 19 - 262144 - Dig 2 I/P 20 - 524288 - Dig 3 I/P 21 - 1048576 - Filter I/P 1 22 - 2097152 - Filter I/P 2 23 - 4194304 - Network 24 - 8388608 - Int storage 25 - 16777216 - SD Card
1.3.6.1.4.1.46651.1.12.2INTEGER (0..33554432)read-writemandatory
alarm2mask
OBJECT-TYPE
Alarm drive 2 Mask [Can have multiple Alarm Errors]. Bit Position - Value - Alarm Drive State: 0 - Unselect, 1 - Select 1 - 1 - Voltage Low 2 - 2 - Voltage High 3 - 4 - Tempr Low 4 - 8 - Tempr Limit 1 5 - 16 - Tempr Limit 2 6 - 32 - Tempr Limit 3 7 - 64 - Humid. Low 8 - 128 - Humid. High 9 - 256 - Fltr Pressure 1 10 - 512 - Fltr Pressure 2 11 - 1024 - Fan 1 12 - 2048 - Fan 2 13 - 4096 - Onboard Sens 14 - 8192 - Room Sens 15 - 16384 - Hotspot Sens 16 - 32768 - Ambient 1 Sens 17 - 65536 - Ambient 2 Sens 18 - 131072 - Dig 1 I/P 19 - 262144 - Dig 2 I/P 20 - 524288 - Dig 3 I/P 21 - 1048576 - Filter I/P 1 22 - 2097152 - Filter I/P 2 23 - 4194304 - Network 24 - 8388608 - Int storage 25 - 16777216 - SD Card
1.3.6.1.4.1.46651.1.12.3INTEGER (0..33554432)read-writemandatory
alarm3mask
OBJECT-TYPE
Alarm drive 3 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card
1.3.6.1.4.1.46651.1.12.4INTEGER (0..25)read-writemandatory
alarm4mask
OBJECT-TYPE
Alarm drive 4 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card
1.3.6.1.4.1.46651.1.12.5INTEGER (0..25)read-writemandatory
alarm5mask
OBJECT-TYPE
Alarm drive 5 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card
1.3.6.1.4.1.46651.1.12.6INTEGER (0..25)read-writemandatory
alarm6mask
OBJECT-TYPE
Alarm drive 6 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card
1.3.6.1.4.1.46651.1.12.7INTEGER (0..25)read-writemandatory
alarm7mask
OBJECT-TYPE
Alarm drive 7 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card
1.3.6.1.4.1.46651.1.12.8INTEGER (0..25)read-writemandatory
alarm8mask
OBJECT-TYPE
Alarm drive 8 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card
1.3.6.1.4.1.46651.1.12.9INTEGER (0..25)read-writemandatory
alarm9mask
OBJECT-TYPE
Alarm drive 9 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card
1.3.6.1.4.1.46651.1.12.10INTEGER (0..25)read-writemandatory
alarm10mask
OBJECT-TYPE
Alarm drive 10 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card
1.3.6.1.4.1.46651.1.12.11INTEGER (0..25)read-writemandatory
nightModeConfig
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.13
saveReloadConfNm
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.13.1INTEGER (0..1)read-writemandatory
starttimeHournm
OBJECT-TYPE
Night Mode Start time hour
1.3.6.1.4.1.46651.1.13.2INTEGER (0..24)read-writemandatory
startTimeMinutesnm
OBJECT-TYPE
Night Mode Start time minutes
1.3.6.1.4.1.46651.1.13.3INTEGER (0..59)read-writemandatory
endTimeHournm
OBJECT-TYPE
Night Mode End time hour
1.3.6.1.4.1.46651.1.13.4INTEGER (0..24)read-writemandatory
endTimeMinutesnm
OBJECT-TYPE
Night Mode End time minutes
1.3.6.1.4.1.46651.1.13.5INTEGER (0..59)read-writemandatory
fanMaxRPMnm
OBJECT-TYPE
% of max fan speed
1.3.6.1.4.1.46651.1.13.6INTEGER (0..100)read-writemandatory
setPointOffsetnm
OBJECT-TYPE
Cooling setpoint offset
1.3.6.1.4.1.46651.1.13.7INTEGER (-10..10)read-writemandatory
coolingModenm
OBJECT-TYPE
0 - Freecooling. 1 - Standard. 2 - Power save. 3 - Aircon.
1.3.6.1.4.1.46651.1.13.8INTEGER (0..3)read-writemandatory
enablenm
OBJECT-TYPE
0 - Disable. 1 - Enable.
1.3.6.1.4.1.46651.1.13.9INTEGER (0..1)read-writemandatory
networkConfig
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.14
saveReloadConfNW
OBJECT-TYPE
0 - Discard modifications, 1 - Save Modifications. Configuration reloaded
1.3.6.1.4.1.46651.1.14.1INTEGER (0..1)read-writemandatory
dhcpenable
OBJECT-TYPE
0 - Static IP, 1 - Dynamic IP
1.3.6.1.4.1.46651.1.14.2INTEGER (0..1)read-writemandatory
ipaddr
OBJECT-TYPE
System IP Address
1.3.6.1.4.1.46651.1.14.3OCTET STRINGread-writemandatory
subnetmask
OBJECT-TYPE
Sub-net Mask
1.3.6.1.4.1.46651.1.14.4OCTET STRINGread-writemandatory
gatewayIPaddr
OBJECT-TYPE
Default Gateway IP Address
1.3.6.1.4.1.46651.1.14.5OCTET STRINGread-writemandatory
ntpIPaddr
OBJECT-TYPE
DNS IP Address
1.3.6.1.4.1.46651.1.14.6OCTET STRINGread-writemandatory
snmpPort
OBJECT-TYPE
SNMP Agent Port
1.3.6.1.4.1.46651.1.14.7INTEGER (0..65535)read-writemandatory
trapServer1IPaddr
OBJECT-TYPE
SNMP TRAP manager 1 IP address
1.3.6.1.4.1.46651.1.14.8OCTET STRINGread-writemandatory
trapServer1port
OBJECT-TYPE
SNMP TRAP manager 1 Port Number
1.3.6.1.4.1.46651.1.14.9INTEGER (0..65535)read-writemandatory
trapServer2IPaddr
OBJECT-TYPE
SNMP TRAP manager 2 IP address
1.3.6.1.4.1.46651.1.14.10OCTET STRINGread-writemandatory
trapServer2port
OBJECT-TYPE
SNMP TRAP manager 2 Port Number
1.3.6.1.4.1.46651.1.14.11INTEGER (0..65535)read-writemandatory
trapServer3IPaddr
OBJECT-TYPE
SNMP TRAP manager 3 IP address
1.3.6.1.4.1.46651.1.14.12OCTET STRINGread-writemandatory
trapServer3port
OBJECT-TYPE
SNMP TRAP manager 3 Port Number
1.3.6.1.4.1.46651.1.14.13INTEGER (0..65535)read-writemandatory
snmpCommunity
OBJECT-TYPE
SNMP Read/write Community string
1.3.6.1.4.1.46651.1.14.14OCTET STRINGread-writemandatory
hostName
OBJECT-TYPE
System Netwrok Host name
1.3.6.1.4.1.46651.1.14.15OCTET STRINGread-writemandatory
trapError
OBJECT-IDENTITY
1.3.6.1.4.1.46651.1.15
errorNumber
OBJECT-TYPE
Error Number corresponding to CC3000 controller Error.
1.3.6.1.4.1.46651.1.15.1INTEGER {VoltageLow(1), VoltageHigh(2), TemprLow(3), TemprLimit1(4), TemprLimit2(5), TemprLimit3(6), HumidLow(7), HumidHigh(8), FltrPressure1(9), FltPressure2(10), Fan1(11), Fan2(12), OnboardSens(13), RoomSens(14), HotspotSens(15), Ambient1Sens(16), Ambient2Sens(17), Dig1IP(18), Dig2IP(19), Dig3IP(20), FilterIP1(21), FilterIP2(22), Network(23), Intstorage(24), SDCard(25)}not-accessiblemandatory
status
OBJECT-TYPE
Error Status Active/SET or Inactive/CLEAR.
1.3.6.1.4.1.46651.1.15.2INTEGER {ALARMclear(0), ALARMset(1)}not-accessiblemandatory
value
OBJECT-TYPE
Value Corresponding to Error Occurance Instance.
1.3.6.1.4.1.46651.1.15.3OCTET STRINGnot-accessiblemandatory
info
OBJECT-TYPE
Description of Current Error.
1.3.6.1.4.1.46651.1.15.4OCTET STRINGnot-accessiblemandatory

Notifications

NameOIDStatus
cc3000Trap
NOTIFICATION-TYPE
Trap From CC300 Controller. Contains TRAP information
1.3.6.1.4.1.46651.0.1