CYCLADES-ACS-PM-MIB
- Registered at
- 1.3.6.1.4.1.2925.4.5
- Last updated
- 2005-08-29 00:00
- Organization
- Cyclades Corporation
- Revisions
- 2005-08-29 00:00, 2003-10-17 00:00
- Namespace
- cyclades
- Source file
CYCLADES-ACS-PM-MIB- Digest
sha256:4489098a2d02fd5fac9559192b0f1b5a1f8303a16cf80a021772d8f295fad152
Description
This module defines objects of the Proxy for PM
Contact
postal : Cyclades Corporation 3541 Gateway Boulevard Fremont, CA 94538, USA e-mail : Technical Support support@cyclades.com
Imports
| From | Symbols |
|---|---|
| CYCLADES-ACS-MIB | cyACSMgmt |
| IF-MIB | InterfaceIndex, InterfaceIndexOrZero |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
CYCLADES-ACS-MIB CYCLADES-ACS-PM-MIB CYCLADES-MIB IANAifType-MIB IF-MIB SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| cyNumberOfPM OBJECT-TYPE The total number of PM's connected on the unit | 1.3.6.1.4.1.2925.4.5.1 | Integer32 | read-only | current |
| cyPMTable OBJECT-TYPE Allows to read information about each connected PM | 1.3.6.1.4.1.2925.4.5.2 | not-accessible | current | |
| cyPMEntry OBJECT-TYPE Information about the connected PM | 1.3.6.1.4.1.2925.4.5.2.1 | not-accessible | current | |
| cyPMSerialPortNumber OBJECT-TYPE The number of the serial port when the PM is connected. | 1.3.6.1.4.1.2925.4.5.2.1.1 | InterfaceIndex | read-only | current |
| cyPMNumberOutlets OBJECT-TYPE Number of outlets. | 1.3.6.1.4.1.2925.4.5.2.1.2 | Integer32 | read-only | current |
| cyPMNumberUnits OBJECT-TYPE Total number of PM unists that are accessed by this serial port. | 1.3.6.1.4.1.2925.4.5.2.1.3 | Integer32 | read-only | current |
| cyPMCurrent OBJECT-TYPE Current reading for the PM. | 1.3.6.1.4.1.2925.4.5.2.1.4 | DisplayString | read-only | current |
| cyPMVersion OBJECT-TYPE The software version of the PM. | 1.3.6.1.4.1.2925.4.5.2.1.5 | DisplayString | read-only | current |
| cyPMTemperature OBJECT-TYPE The PM temperature. | 1.3.6.1.4.1.2925.4.5.2.1.6 | DisplayString | read-only | current |
| cyPMCommand OBJECT-TYPE A character string for the user to send commands to PM. He can use it to does the save command. Or to list the outlets that need to be turned off, or turned on , or cycled or locked or unlocked as a group. The command is the first word and is followed by a space and the outlet list (otulets commands). Valid commands are 'on', 'off', 'cycle', 'lock', 'unlock', 'save'. | 1.3.6.1.4.1.2925.4.5.2.1.7 | DisplayString (SIZE(1..100)) | read-write | current |
| cyPMUnitTable OBJECT-TYPE Allow operations on specific PM unit connected | 1.3.6.1.4.1.2925.4.5.3 | not-accessible | current | |
| cyPMUnitEntry OBJECT-TYPE Allow operations on outlet | 1.3.6.1.4.1.2925.4.5.3.1 | not-accessible | current | |
| cyPMUnitNumber OBJECT-TYPE The number of the PM unit in the daisy-chained mode. | 1.3.6.1.4.1.2925.4.5.3.1.1 | InterfaceIndex | not-accessible | current |
| cyPMUnitVersion OBJECT-TYPE The software version of this PM unit. | 1.3.6.1.4.1.2925.4.5.3.1.2 | DisplayString | read-only | current |
| cyPMUnitOutlets OBJECT-TYPE Number of outlets of this PM unit. | 1.3.6.1.4.1.2925.4.5.3.1.3 | Integer32 | read-only | current |
| cyPMUnitFirstOutlet OBJECT-TYPE Number of the first outlet of this PM unit. | 1.3.6.1.4.1.2925.4.5.3.1.4 | Integer32 | read-only | current |
| cyPMUnitCurrent OBJECT-TYPE Current of this PM unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) | 1.3.6.1.4.1.2925.4.5.3.1.5 | Integer32 | read-only | current |
| cyPMUnitMaxCurrent OBJECT-TYPE Maximum current of this PM unit in AMP. The value of this object is the maximum current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the maximum current is 0.5 AMP.) | 1.3.6.1.4.1.2925.4.5.3.1.6 | Integer32 | read-only | current |
| cyPMUnitTemperature OBJECT-TYPE Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | 1.3.6.1.4.1.2925.4.5.3.1.7 | Integer32 | read-only | current |
| cyPMUnitMaxTemperature OBJECT-TYPE Maximum temperature value of this PM unit in Celsius degrees. The value of this object is the maximum temperature in degrees C * 10. You need to translate the readed value(Ex. : value is 240, the maximum temperature is 24 Celsius). If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | 1.3.6.1.4.1.2925.4.5.3.1.8 | Integer32 | read-write | current |
| cyOutletTable OBJECT-TYPE Allow operations on outlet | 1.3.6.1.4.1.2925.4.5.4 | not-accessible | current | |
| cyOutletEntry OBJECT-TYPE Allow operations on outlet | 1.3.6.1.4.1.2925.4.5.4.1 | not-accessible | current | |
| cyOutletNumber OBJECT-TYPE The outlet number on the PM. Zero is ALL outlets. | 1.3.6.1.4.1.2925.4.5.4.1.1 | InterfaceIndexOrZero | not-accessible | current |
| cyOutletName OBJECT-TYPE The name given to a particular outlet Maximum size is 8 characters. | 1.3.6.1.4.1.2925.4.5.4.1.2 | DisplayString (SIZE(1..8)) | read-write | current |
| cyOutletServer OBJECT-TYPE Alias of the Server connected to this outlet . | 1.3.6.1.4.1.2925.4.5.4.1.3 | DisplayString | read-only | current |
| cyOutletPower OBJECT-TYPE Getting this object will return the power state of the outlet. Valid return states are UNKNOW, OFF and ON. Setting this object will change the power state of the outlet. | 1.3.6.1.4.1.2925.4.5.4.1.4 | INTEGER {off(0), on(1), cycle(2), unknow(3)} | read-write | current |
| cyOutletLock OBJECT-TYPE Getting this object will return the lock state of the outlet. Setting this object will change the lock state of the outlet. | 1.3.6.1.4.1.2925.4.5.4.1.5 | INTEGER {unlock(0), lock(1), unknow(2)} | read-write | current |
| cyOutletPUInterval OBJECT-TYPE The power unit interval of this outlet in seconds. The value of this object is the actual interval in seconds * 10. You need to translate the readed value (Ex. : value is 5, the interval is 0.5 seconds.) | 1.3.6.1.4.1.2925.4.5.4.1.6 | Integer32 | read-write | current |