CPS-MIB
- Registered at
- 1.3.6.1.4.1.3808
- Namespace
- cyberpower
- Source file
CPS-MIB- Digest
sha256:e302e8eeee193b89ce097997179192e8e3101455e8ab8f65c099f85e42073492
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Gauge32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
CPS-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| cps OBJECT-IDENTITY | 1.3.6.1.4.1.3808 | |||
| products OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1 | |||
| hardware OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1 | |||
| ups OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1 | |||
| upsIdent OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.1 | |||
| upsBaseIdent OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.1.1 | |||
| upsBaseIdentModel OBJECT-TYPE The UPS model name. | 1.3.6.1.4.1.3808.1.1.1.1.1.1 | DisplayString | read-only | mandatory |
| upsBaseIdentName OBJECT-TYPE The UPS identified name could be set by the administrator. | 1.3.6.1.4.1.3808.1.1.1.1.1.2 | DisplayString | read-write | mandatory |
| upsAdvanceIdent OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.1.2 | |||
| upsAdvanceIdentFirmwareRevision OBJECT-TYPE The UPS firmware revision. | 1.3.6.1.4.1.3808.1.1.1.1.2.1 | DisplayString | read-only | mandatory |
| upsAdvanceIdentDateOfManufacture OBJECT-TYPE The UPS manufacture date in mm/dd/yy format. | 1.3.6.1.4.1.3808.1.1.1.1.2.2 | DisplayString | read-only | mandatory |
| upsAdvanceIdentSerialNumber OBJECT-TYPE The UPS serial number in the internal microprocessor. | 1.3.6.1.4.1.3808.1.1.1.1.2.3 | DisplayString | read-only | mandatory |
| upsAdvanceIdentAgentFirmwareRevision OBJECT-TYPE The SNMP agent firmware revision. | 1.3.6.1.4.1.3808.1.1.1.1.2.4 | DisplayString | read-only | mandatory |
| upsAdvanceIdentLCDFirmwareVersion OBJECT-TYPE The revision number of the UPS LCD firmware. | 1.3.6.1.4.1.3808.1.1.1.1.2.5 | DisplayString | read-only | mandatory |
| upsAdvanceIdentPowerRating OBJECT-TYPE The Volt-Amp rating of the UPS. | 1.3.6.1.4.1.3808.1.1.1.1.2.6 | INTEGER | read-only | mandatory |
| upsAdvanceIdentLoadPower OBJECT-TYPE The power rating(Watts) of the UPS. | 1.3.6.1.4.1.3808.1.1.1.1.2.7 | INTEGER | read-only | mandatory |
| upsAdvanceIdentCurrentRating OBJECT-TYPE The output current rating of the UPS. Measured in tenths of Amps. | 1.3.6.1.4.1.3808.1.1.1.1.2.8 | INTEGER | read-only | mandatory |
| upsAdvanceIdentAgentSerialNumber OBJECT-TYPE A string identifying the serial number of the Agent. | 1.3.6.1.4.1.3808.1.1.1.1.2.9 | DisplayString | read-only | mandatory |
| upsBattery OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.2 | |||
| upsBaseBattery OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.2.1 | |||
| upsBaseBatteryStatus OBJECT-TYPE The UPS battery status. A batteryLow(3) value means the battery will be exhausted soon under the current load. The amount of low battery run time can be configured by the upsAdvanceConfigLowBatteryRunTime. | 1.3.6.1.4.1.3808.1.1.1.2.1.1 | INTEGER {unknown(1), batteryNormal(2), batteryLow(3), batteryNotPresent(4)} | read-only | mandatory |
| upsBaseBatteryTimeOnBattery OBJECT-TYPE The UPS wasted battery time since the UPS has transfered to backup mode. | 1.3.6.1.4.1.3808.1.1.1.2.1.2 | TimeTicks | read-only | mandatory |
| upsBaseBatteryLastReplaceDate OBJECT-TYPE The UPS batteries last replaced date in mm/dd/yyyy format. This value is originally set when manufactured. If batteries replaced, administrator should reset this value. | 1.3.6.1.4.1.3808.1.1.1.2.1.3 | DisplayString | read-write | mandatory |
| upsBaseBatteryAgeRecommand OBJECT-TYPE Recommended battery life in month | 1.3.6.1.4.1.3808.1.1.1.2.1.4 | INTEGER | read-only | mandatory |
| upsAdvanceBattery OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.2.2 | |||
| upsAdvanceBatteryCapacity OBJECT-TYPE The battery capacity expressed in percentage. | 1.3.6.1.4.1.3808.1.1.1.2.2.1 | Gauge | read-only | mandatory |
| upsAdvanceBatteryVoltage OBJECT-TYPE The battery voltage expressed in 1/10 VDC. | 1.3.6.1.4.1.3808.1.1.1.2.2.2 | INTEGER | read-only | mandatory |
| upsAdvanceBatteryTemperature OBJECT-TYPE The UPS battery temperature expressed in Celsius. | 1.3.6.1.4.1.3808.1.1.1.2.2.3 | Gauge | read-only | mandatory |
| upsAdvanceBatteryRunTimeRemaining OBJECT-TYPE The UPS battery remaining run time. | 1.3.6.1.4.1.3808.1.1.1.2.2.4 | TimeTicks | read-only | mandatory |
| upsAdvanceBatteryReplaceIndicator OBJECT-TYPE This value indicates if UPS batteries need to be replaced. | 1.3.6.1.4.1.3808.1.1.1.2.2.5 | INTEGER {noBatteryNeedsReplacing(1), batteryNeedsReplacing(2)} | read-only | mandatory |
| upsAdvanceBatteryFullChargeVoltage OBJECT-TYPE The battery charged voltage expressed in 1/10 VDC. | 1.3.6.1.4.1.3808.1.1.1.2.2.6 | INTEGER | read-only | mandatory |
| upsAdvanceBatteryCurrent OBJECT-TYPE The battery current expressed in percentage. | 1.3.6.1.4.1.3808.1.1.1.2.2.7 | INTEGER | read-only | mandatory |
| upsAdvanceBatteryVoltageRating OBJECT-TYPE The DC voltage rating of the battery set. | 1.3.6.1.4.1.3808.1.1.1.2.2.8 | INTEGER | read-only | mandatory |
| upsAdvanceBatteryLife OBJECT-TYPE The battery life expressed in 1/100 percentage. | 1.3.6.1.4.1.3808.1.1.1.2.2.9 | INTEGER | read-only | mandatory |
| upsInput OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.3 | |||
| upsBaseInput OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.3.1 | |||
| upsBaseInputPhase OBJECT-TYPE The AC input phase. | 1.3.6.1.4.1.3808.1.1.1.3.1.1 | INTEGER | read-only | mandatory |
| upsAdvanceInput OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.3.2 | |||
| upsAdvanceInputLineVoltage OBJECT-TYPE The input line voltage in 1/10 VAC. | 1.3.6.1.4.1.3808.1.1.1.3.2.1 | Gauge | read-only | mandatory |
| upsAdvanceInputMaxLineVoltage OBJECT-TYPE The maximum input line voltage in 1/10 VAC over the previous 1 minute period. | 1.3.6.1.4.1.3808.1.1.1.3.2.2 | Gauge | read-only | mandatory |
| upsAdvanceInputMinLineVoltage OBJECT-TYPE The minimum input line voltage in 1/10 VAC over the previous 1 minute period. | 1.3.6.1.4.1.3808.1.1.1.3.2.3 | Gauge | read-only | mandatory |
| upsAdvanceInputFrequency OBJECT-TYPE The input line frequency in 1/10 Hz. | 1.3.6.1.4.1.3808.1.1.1.3.2.4 | Gauge | read-only | mandatory |
| upsAdvanceInputLineFailCause OBJECT-TYPE The reason of UPS power failure. This value is set to: - noTransfer(1), if UPS is in utility mode. - highLineVoltage(2), if UPS switch to battery mode by reason of input voltage over the high transfer vloltage. - brownout(3), if UPS switch to battery mode by reason of input voltage under the low transfer vloltage. - selfTest(4), if the UPS was commanded to do a self test. | 1.3.6.1.4.1.3808.1.1.1.3.2.5 | INTEGER {noTransfer(1), highLineVoltage(2), brownout(3), selfTest(4)} | read-only | mandatory |
| upsAdvanceInputStatus OBJECT-TYPE Display the present status of the utility power supplied to the UPS. | 1.3.6.1.4.1.3808.1.1.1.3.2.6 | INTEGER {normal(1), overVoltage(2), underVoltage(3), frequencyFailure(4), blackout(5)} | read-only | mandatory |
| upsOutput OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.4 | |||
| upsBaseOutput OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.4.1 | |||
| upsBaseOutputStatus OBJECT-TYPE The UPS output status. | 1.3.6.1.4.1.3808.1.1.1.4.1.1 | INTEGER {unknown(1), onLine(2), onBattery(3), onBoost(4), onSleep(5), off(6), rebooting(7), onECO(8), onBypass(9), onBuck(10), onOverload(11)} | read-only | mandatory |
| upsBaseOutputPhase OBJECT-TYPE The output phase. | 1.3.6.1.4.1.3808.1.1.1.4.1.2 | INTEGER | read-only | mandatory |
| upsBaseOutputWorkingFrequency OBJECT-TYPE The frequency of the UPS output power. | 1.3.6.1.4.1.3808.1.1.1.4.1.3 | DisplayString | read-only | mandatory |
| upsAdvanceOutput OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.4.2 | |||
| upsAdvanceOutputVoltage OBJECT-TYPE The UPS output voltage in 1/10 VAC. | 1.3.6.1.4.1.3808.1.1.1.4.2.1 | Gauge | read-only | mandatory |
| upsAdvanceOutputFrequency OBJECT-TYPE The UPS output frequency in 1/10 Hz. | 1.3.6.1.4.1.3808.1.1.1.4.2.2 | Gauge | read-only | mandatory |
| upsAdvanceOutputLoad OBJECT-TYPE The UPS output load expressed in percentage | 1.3.6.1.4.1.3808.1.1.1.4.2.3 | Gauge | read-only | mandatory |
| upsAdvanceOutputCurrent OBJECT-TYPE The UPS output current in 1/10 Amps. | 1.3.6.1.4.1.3808.1.1.1.4.2.4 | Gauge | read-only | mandatory |
| upsAdvanceOutputPower OBJECT-TYPE The total output active power of the UPS system in W. | 1.3.6.1.4.1.3808.1.1.1.4.2.5 | Gauge | read-only | mandatory |
| upsConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.5 | |||
| upsBaseConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.5.1 | |||
| upsBaseConfigNumDevices OBJECT-TYPE The number of equipment plugged into the UPS. | 1.3.6.1.4.1.3808.1.1.1.5.1.1 | INTEGER | read-only | mandatory |
| upsBaseConfigDeviceTable OBJECT-TYPE A list of equipment plugged into the UPS. The numbers of entries are given by the value of upsBaseConfigNumDevices. | 1.3.6.1.4.1.3808.1.1.1.5.1.2 | not-accessible | mandatory | |
| upsBaseConfigDeviceEntry OBJECT-TYPE The equipment plugged in to the UPS. | 1.3.6.1.4.1.3808.1.1.1.5.1.2.1 | not-accessible | mandatory | |
| deviceIndex OBJECT-TYPE The index of the equipment plugged into the UPS. | 1.3.6.1.4.1.3808.1.1.1.5.1.2.1.1 | INTEGER (1..255) | read-only | mandatory |
| deviceName OBJECT-TYPE The name of the equipment plugged into the UPS. | 1.3.6.1.4.1.3808.1.1.1.5.1.2.1.2 | DisplayString | read-write | mandatory |
| vaRating OBJECT-TYPE The VA rating of the equipment plugged into the UPS. | 1.3.6.1.4.1.3808.1.1.1.5.1.2.1.3 | INTEGER | read-write | mandatory |
| acceptThisDevice OBJECT-TYPE An equipment is plugged if yes, unplugged if no. | 1.3.6.1.4.1.3808.1.1.1.5.1.2.1.4 | INTEGER {yes(1), no(2)} | read-write | mandatory |
| upsAdvanceConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.5.2 | |||
| upsAdvanceConfigOutputVoltage OBJECT-TYPE The standard UPS output voltage in VAC. The possible values are 100, 110, 120, 127, 208, 220, 230, and 240. If a value other than a possible value is set, it will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.1 | INTEGER | read-write | mandatory |
| upsAdvanceConfigHighTransferVolt OBJECT-TYPE Adjust the high transfer vloltage in VAC. The high transfer vloltage will become the UPS default value subtracts this value. The allowed values depend on the output: 100-127 volt system allow settings of 0-15. 208-240 volt system allow settings of 0-30. If the adjustable value is over the allowed values, it will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.2 | INTEGER | read-write | mandatory |
| upsAdvanceConfigLowTransferVolt OBJECT-TYPE Adjust the low transfer vloltage in VAC. The low transfer vloltage will become the UPS default value adds this value. The allowed values depend on the output: 100-127 volt system allow settings of 0-15. 208-240 volt system allow settings of 0-30. If the adjustable value is over the allowed values, it will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.3 | INTEGER | read-write | mandatory |
| upsAdvanceConfigAlarm OBJECT-TYPE This value is set to handle audible alarms when power failure. | 1.3.6.1.4.1.3808.1.1.1.5.2.4 | INTEGER {timed(1), enable(2), disable(3), mute(4)} | read-write | mandatory |
| upsAdvanceConfigAlarmTimer OBJECT-TYPE The time after power failure at which the UPS begins giving audible alarms. This timer is effective only if the value of upsAdvanceConfigAlarm is timed(1). Accepted values are between 0 to 60 seconds. If a value other than a supported value is set, the value will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.5 | TimeTicks | read-write | mandatory |
| upsAdvanceConfigMinReturnCapacity OBJECT-TYPE The minimum battery capacity that UPS will return from a low battery shutdown condition. The possible values are between 0 to 40. If a value other than a supported value is set, the value will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.6 | INTEGER | read-write | mandatory |
| upsAdvanceConfigSensitivity OBJECT-TYPE The sensitivity of the UPS to power failure detection. | 1.3.6.1.4.1.3808.1.1.1.5.2.7 | INTEGER {auto(1), low(2), medium(3), high(4)} | read-write | mandatory |
| upsAdvanceConfigLowBatteryRunTime OBJECT-TYPE The desired run time, in seconds, UPS will enter in a low battery sequence. The possible values are 120, 300, 420, 600. If a value other than a supported value is set, the value will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.8 | TimeTicks | read-write | mandatory |
| upsAdvanceConfigReturnDelay OBJECT-TYPE The delay time the UPS will turn on after power recovery. The value is also used in a 'reboot' or 'wake up' sequence. The possible values are 0 to 600 seconds. If a value other than a supported value is set, the value will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.9 | TimeTicks | read-write | mandatory |
| upsAdvanceConfigShutoffDelay OBJECT-TYPE The delay time the UPS will remain on after receiving a turn off command. The possible values are between 60 to 5940 seconds. If a value other than a supported value is set, the value will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.10 | TimeTicks | read-write | mandatory |
| upsAdvanceConfigSleepDelay OBJECT-TYPE The delay time the UPS will enter sleep mode after receiving a sleep command. WThe possible values are between 60 to 5940 seconds. If a value other than a supported value is set, the value will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.11 | TimeTicks | read-write | mandatory |
| upsAdvanceConfigSetEEPROMDefaults OBJECT-TYPE Reset the UPS EEPROM parameters to default values. | 1.3.6.1.4.1.3808.1.1.1.5.2.12 | INTEGER {noSetEEPROMDefaults(1), setEEPROMDefaults(2)} | read-write | mandatory |
| upsAdvanceConfigAutoRestore OBJECT-TYPE When this option is enabled, the UPS will restore output immediately when the utility power restores.When this option is disabled, the UPS will not restore output at that moment and users have to turn it on manually at a later time. | 1.3.6.1.4.1.3808.1.1.1.5.2.13 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| upsAdvanceConfigRechargedCapacity OBJECT-TYPE When the utility power restores, the UPS will start to recharge until the specified battery capacity in percentage is met before restoring output power. The possible values are 0, 15, 30, 45, 60, 75, and 90. If a value other than a possible value is set, it will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.14 | INTEGER | read-write | mandatory |
| upsAdvanceConfigColdStart OBJECT-TYPE Set the ability of the UPS can start in the absence of input power.When this option is enabled the UPS can be turned on without having input power. | 1.3.6.1.4.1.3808.1.1.1.5.2.15 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| upsAdvanceConfigDeepDischargeProtection OBJECT-TYPE When the UPS is on Battery Mode with 0% load and the status remains for the time configured,the RMCARD will enforce the UPS to Sleep Mode and the output will be turned off. The possible values are 0, 20, 40, and 60 minutes. If a value other than a possible value is set, it will not be accepted. | 1.3.6.1.4.1.3808.1.1.1.5.2.16 | INTEGER | read-write | mandatory |
| upsAdvanceConfigSleepAfterAllClientShut OBJECT-TYPE If this option is enabled, UPS will enter sleep mode after utility power failed and remaining MSDT+2 minutes.More information about MSDT please reference to help page of UPS - > PowerPanel List. | 1.3.6.1.4.1.3808.1.1.1.5.2.17 | INTEGER {disable(1), enable(2)} | read-write | mandatory |
| upsAdvanceConfigLowBatteryThreshold OBJECT-TYPE When the UPS supplies battery power and the remaining capacity is lower than this threshold, the UPS will sound an alarm. The value expressed in percentage. | 1.3.6.1.4.1.3808.1.1.1.5.2.18 | INTEGER | read-write | mandatory |
| upsControl OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.6 | |||
| upsBaseControl OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.6.1 | |||
| upsBaseControlConserveBattery OBJECT-TYPE UPS on battery will enter sleeping when the variable is set to turnOffUpsToConserveBattery(2). When utility power recovers the UPS will turn back on. Trying to turn off a UPS that is not on battery mode will cause badValue error. It is no effective to set this value to noTurnOffUps(1). | 1.3.6.1.4.1.3808.1.1.1.6.1.1 | INTEGER {noTurnOffUps(1), turnOffUpsToConserveBattery(2)} | read-write | mandatory |
| upsAdvanceControl OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.6.2 | |||
| upsAdvanceControlUpsOff OBJECT-TYPE UPS will shutdown when the variable is set to turnUpsOff(2). UPS will shutdown after a delay period specified by upsAdvanceConfigShutoffDelay when the variable is Set to turnUpsOffGracefully(3). Without regard to the utility state the UPS will not provide output power in this state. It is no effective to set this value to noTurnUpsOff(1). | 1.3.6.1.4.1.3808.1.1.1.6.2.1 | INTEGER {noTurnUpsOff(1), turnUpsOff(2), turnUpsOffGracefully(3)} | read-write | mandatory |
| upsAdvanceControlRebootUps OBJECT-TYPE UPS will shutdown and turn back on when the variable is set to rebootUps(2). It is no effective to set this value to noRebootUps(1). | 1.3.6.1.4.1.3808.1.1.1.6.2.2 | INTEGER {noRebootUps(1), rebootUps(2)} | read-write | mandatory |
| upsAdvanceControlUpsSleep OBJECT-TYPE UPS will enter sleep mode when the variable is set to putUpsToSleep(2). UPS will enter sleep mode after a delay period specified by upsAdvanceConfigSleepDelay when the variable is Set to putUpsToSleepGracefully(3). Without regard to the utility state the UPS will not provide output power in sleep mode. Output power will recover when specified time has elapsed. It is no effective to set this value to noPutUpsToSleep(1). | 1.3.6.1.4.1.3808.1.1.1.6.2.3 | INTEGER {noPutUpsToSleep(1), putUpsToSleep(2), putUpsToSleepGracefully(3)} | read-write | mandatory |
| upsAdvanceControlSimulatePowerFail OBJECT-TYPE UPS will transfer to backup mode when the variable is set to simulatePowerFailure(2). It is no effective to set this value to noFlashAndBeep(1). | 1.3.6.1.4.1.3808.1.1.1.6.2.4 | INTEGER {noSimulatePowerFailure(1), simulatePowerFailure(2)} | read-write | mandatory |
| upsAdvanceControlFlashAndBeep OBJECT-TYPE UPS will beep and simultaneously turn on the panel lights when the variable is set to flashAndBeep(2). It is no effective to set this value to noSimulatePowerFailure(1). | 1.3.6.1.4.1.3808.1.1.1.6.2.5 | INTEGER {noFlashAndBeep(1), flashAndBeep(2)} | read-write | mandatory |
| upsAdvanceControlTurnOnUPS OBJECT-TYPE UPS will turned on immediately when the variable is set to turnOnUPS(2). It is no effective to set this value to noTurnOnUPS(1). | 1.3.6.1.4.1.3808.1.1.1.6.2.6 | INTEGER {noTurnOnUPS(1), turnOnUPS(2)} | read-write | mandatory |
| upsAdvanceSleepAfterDelay OBJECT-TYPE UPS will enter sleep mode after indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. | 1.3.6.1.4.1.3808.1.1.1.6.2.7 | INTEGER (-1..600) | read-write | mandatory |
| upsTest OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.7 | |||
| upsBaseTest OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.7.1 | |||
| upsAdvanceTest OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.7.2 | |||
| upsAdvanceTestDiagnosticSchedule OBJECT-TYPE The schedule of the UPS automatic selftest. | 1.3.6.1.4.1.3808.1.1.1.7.2.1 | INTEGER {unknown(1), biweekly(2), weekly(3), atTurnOn(4), never(5)} | read-write | mandatory |
| upsAdvanceTestDiagnostics OBJECT-TYPE UPS will do a diagnostic selftest when the variable is set to testDiagnostics(2). It is no effective to set this value to noTestDiagnostics(1). | 1.3.6.1.4.1.3808.1.1.1.7.2.2 | INTEGER {noTestDiagnostics(1), testDiagnostics(2)} | read-write | mandatory |
| upsAdvanceTestDiagnosticsResults OBJECT-TYPE The last UPS selftest result. | 1.3.6.1.4.1.3808.1.1.1.7.2.3 | INTEGER {ok(1), failed(2), invalidTest(3), testInProgress(4)} | read-only | mandatory |
| upsAdvanceTestLastDiagnosticsDate OBJECT-TYPE The last UPS selftest date in mm/dd/yy format. | 1.3.6.1.4.1.3808.1.1.1.7.2.4 | DisplayString | read-only | mandatory |
| upsAdvanceTestIndicators OBJECT-TYPE UPS will perform a panel indicator test when the variable is set to testIndicators(2). It is no effective to set this value to noTestIndicators(1). | 1.3.6.1.4.1.3808.1.1.1.7.2.5 | INTEGER {noTestIndicators(1), testIndicators(2)} | read-write | mandatory |
| upsAdvanceTestRuntimeEstimation OBJECT-TYPE UPS will discharge to calibrate the UPS runtime when the variable is set to performEstimation(2). This test runs until the UPS is in a low battery condition. UPS will cancel the discharge after setting performEstimation(2) when the variable is set to cancelCurrentEstimation(3). It is no effective to set this value to noPerformEstimation(1). The result of the runtime test will be stored in upsAdvanceTestEstimationResults. | 1.3.6.1.4.1.3808.1.1.1.7.2.6 | INTEGER {noPerformEstimation(1), performEstimation(2), cancelCurrentEstimation(3)} | read-write | mandatory |
| upsAdvanceTestEstimationResults OBJECT-TYPE The last runtime estimation result. This value means : - ok(1), if a successful runtime estimation. - invalidEstimation(2), if runtime estimation failure. - estimationInProgress(3), if estimation is processing now. | 1.3.6.1.4.1.3808.1.1.1.7.2.7 | INTEGER {ok(1), invalidEstimation(2), estimationInProgress(3)} | read-only | mandatory |
| upsAdvanceTestEstimationDate OBJECT-TYPE The last UPS runtime estimation date | 1.3.6.1.4.1.3808.1.1.1.7.2.8 | DisplayString | read-only | mandatory |
| upsOutlet OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.8 | |||
| upsBankOutletControl OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.8.1 | |||
| upsBankOutletControlTable OBJECT-TYPE Allows for control of the outlet banks. | 1.3.6.1.4.1.3808.1.1.1.8.1.1 | not-accessible | mandatory | |
| upsBankOutletControlEntry OBJECT-TYPE The outlet to control. | 1.3.6.1.4.1.3808.1.1.1.8.1.1.1 | not-accessible | mandatory | |
| upsBankControlIndex OBJECT-TYPE The index to the outlet entry. | 1.3.6.1.4.1.3808.1.1.1.8.1.1.1.1 | INTEGER (1..24) | read-only | mandatory |
| upsBankControlOutletCommand OBJECT-TYPE Getting this variable will return the outlet bank state. If the outlet bank is on, the immediateOn (1) value will be returned. If the outlet bank is off, the immediateOff (2) value will be returned. If the outlet bank is critical (uncontrollable), the criticalBank (4) value will be returned. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. | 1.3.6.1.4.1.3808.1.1.1.8.1.1.1.2 | INTEGER {immediateOn(1), immediateOff(2), bankNotExist(3), criticalBank(4)} | read-write | mandatory |
| upsPhase OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.9 | |||
| upsPhaseInput OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.9.1 | |||
| upsPhaseInputTableSize OBJECT-TYPE Getting this OID will return the phase number. | 1.3.6.1.4.1.3808.1.1.1.9.1.1 | INTEGER | read-only | mandatory |
| upsPhaseInputTable OBJECT-TYPE Allows for getting the Phase Input in the UPS | 1.3.6.1.4.1.3808.1.1.1.9.1.2 | not-accessible | mandatory | |
| upsPhaseInputEntry OBJECT-TYPE The UPS Phase Input Access. | 1.3.6.1.4.1.3808.1.1.1.9.1.2.1 | not-accessible | mandatory | |
| upsPhaseInputTableIndex OBJECT-TYPE The index to the UPS Phase Input entry. | 1.3.6.1.4.1.3808.1.1.1.9.1.2.1.1 | INTEGER (3) | read-only | mandatory |
| upsPhaseInputVoltage OBJECT-TYPE Getting this OID will return the input voltage that each phase of the UPS can provide. It is represented in 1/10 VAC. | 1.3.6.1.4.1.3808.1.1.1.9.1.2.1.2 | INTEGER | read-only | mandatory |
| upsPhaseInputCurrent OBJECT-TYPE Getting this OID will return the input current that each phase of the UPS can provide. It is represented in 1/10 Amps. | 1.3.6.1.4.1.3808.1.1.1.9.1.2.1.3 | INTEGER | read-only | mandatory |
| upsPhaseInputFrequency OBJECT-TYPE Getting this OID will return the input frequency that each phase of the UPS can provide. It is represented in 1/10 Hz. | 1.3.6.1.4.1.3808.1.1.1.9.1.2.1.4 | INTEGER | read-only | mandatory |
| upsPhaseInputPowerFactor OBJECT-TYPE Getting this OID will return the input power factor that each phase of the UPS can provide. It is represented in 1/100. | 1.3.6.1.4.1.3808.1.1.1.9.1.2.1.5 | INTEGER | read-only | mandatory |
| upsPhaseOutput OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.9.2 | |||
| upsPhaseOutputTableSize OBJECT-TYPE Getting this OID will return the Phase number. | 1.3.6.1.4.1.3808.1.1.1.9.2.1 | INTEGER | read-only | mandatory |
| upsPhaseOutputTable OBJECT-TYPE Allows for getting the Phase Output in the UPS | 1.3.6.1.4.1.3808.1.1.1.9.2.2 | not-accessible | mandatory | |
| upsPhaseOutputEntry OBJECT-TYPE The UPS Phase Output Access. | 1.3.6.1.4.1.3808.1.1.1.9.2.2.1 | not-accessible | mandatory | |
| upsPhaseOutputTableIndex OBJECT-TYPE The index to the UPS Phase Output entry. | 1.3.6.1.4.1.3808.1.1.1.9.2.2.1.1 | INTEGER (3) | read-only | mandatory |
| upsPhaseOutputVoltage OBJECT-TYPE Getting this OID will return the output voltage that each phase of the UPS can provide. It is represented in 1/10 VAC. | 1.3.6.1.4.1.3808.1.1.1.9.2.2.1.2 | INTEGER | read-only | mandatory |
| upsPhaseOutputCurrent OBJECT-TYPE Getting this OID will return the output current that each phase of the UPS can provide. It is represented in 1/10 Amps. | 1.3.6.1.4.1.3808.1.1.1.9.2.2.1.3 | INTEGER | read-only | mandatory |
| upsPhaseOutputFrequency OBJECT-TYPE Getting this OID will return the output frequency that each phase of the UPS can provide. It is represented in 1/10 Hz. | 1.3.6.1.4.1.3808.1.1.1.9.2.2.1.4 | INTEGER | read-only | mandatory |
| upsPhaseOutputPowerFactor OBJECT-TYPE Getting this OID will return the output power factor that each phase of the UPS can provide. It is represented in 1/100. | 1.3.6.1.4.1.3808.1.1.1.9.2.2.1.5 | INTEGER | read-only | mandatory |
| upsPhaseOutputPower OBJECT-TYPE Getting this OID will return the output power that each phase of the UPS can provide. It is represented in Watt. | 1.3.6.1.4.1.3808.1.1.1.9.2.2.1.6 | INTEGER | read-only | mandatory |
| upsPhaseBypass OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.9.3 | |||
| upsPhaseBypassTableSize OBJECT-TYPE Getting this OID will return the Phase number. | 1.3.6.1.4.1.3808.1.1.1.9.3.1 | INTEGER | read-only | mandatory |
| upsPhaseBypassTable OBJECT-TYPE Allows for getting the Phase Bypass in the UPS | 1.3.6.1.4.1.3808.1.1.1.9.3.2 | not-accessible | mandatory | |
| upsPhaseBypassEntry OBJECT-TYPE The UPS Phase Bypass Access. | 1.3.6.1.4.1.3808.1.1.1.9.3.2.1 | not-accessible | mandatory | |
| upsPhaseBypassTableIndex OBJECT-TYPE The index to the UPS Phase Bypass entry. | 1.3.6.1.4.1.3808.1.1.1.9.3.2.1.1 | INTEGER (3) | read-only | mandatory |
| upsPhaseBypassVoltage OBJECT-TYPE Getting this OID will return the bypass voltage that each phase of the UPS can provide. It is represented in 1/10 VAC. | 1.3.6.1.4.1.3808.1.1.1.9.3.2.1.2 | INTEGER | read-only | mandatory |
| upsPhaseBypassCurrent OBJECT-TYPE Getting this OID will return the bypass current that each phase of the UPS can provide. It is represented in 1/10 Amps. | 1.3.6.1.4.1.3808.1.1.1.9.3.2.1.3 | INTEGER | read-only | mandatory |
| upsPhaseBypassFrequency OBJECT-TYPE Getting this OID will return the bypass frequency that each phase of the UPS can provide. It is represented in 1/10 Hz. | 1.3.6.1.4.1.3808.1.1.1.9.3.2.1.4 | INTEGER | read-only | mandatory |
| upsPhaseBypassPowerFactor OBJECT-TYPE Getting this OID will return the bypass power factor that each phase of the UPS can provide. It is represented in 1/100. | 1.3.6.1.4.1.3808.1.1.1.9.3.2.1.5 | INTEGER | read-only | mandatory |
| upsSystem OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.1.10 | |||
| upsStatus OBJECT-TYPE The UPS system status. | 1.3.6.1.4.1.3808.1.1.1.10.1 | INTEGER {normal(1), overheat(2), hardwarefault(3)} | read-only | mandatory |
| eswitch OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.2 | |||
| eSwitchIdent OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.2.1 | |||
| eSwitchIdentHardwareRev OBJECT-TYPE The hardware revision set at the factory. | 1.3.6.1.4.1.3808.1.1.2.1.1 | DisplayString | read-only | mandatory |
| eSwitchIdentFirmwareRev OBJECT-TYPE The firmware revision set at the factory. | 1.3.6.1.4.1.3808.1.1.2.1.2 | DisplayString | read-only | mandatory |
| eSwitchIdentDateOfManufacture OBJECT-TYPE The manufacture date in mm/dd/yy format. | 1.3.6.1.4.1.3808.1.1.2.1.3 | DisplayString | read-only | mandatory |
| eSwitchIdentModelName OBJECT-TYPE The model name set at the factory. This value need to consist with safty report. | 1.3.6.1.4.1.3808.1.1.2.1.4 | DisplayString | read-only | mandatory |
| eSwitchBase OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.2.2 | |||
| eSwitchNumber OBJECT-TYPE The numbers of switch have been attached to the system. | 1.3.6.1.4.1.3808.1.1.2.2.1 | INTEGER | read-only | mandatory |
| eSwitchBaseTable OBJECT-TYPE A list of switch information. The number of entries is given by the value of eSwitchNumber. | 1.3.6.1.4.1.3808.1.1.2.2.2 | not-accessible | mandatory | |
| eSwitchBaseEntry OBJECT-TYPE An entry information of the individual switch. | 1.3.6.1.4.1.3808.1.1.2.2.2.1 | not-accessible | mandatory | |
| eSwitchID OBJECT-TYPE The power switch ID number. | 1.3.6.1.4.1.3808.1.1.2.2.2.1.1 | INTEGER (0..16) | read-only | mandatory |
| eSwitchOutletNum OBJECT-TYPE The number of outlets provided in the switch. | 1.3.6.1.4.1.3808.1.1.2.2.2.1.2 | INTEGER | read-only | mandatory |
| eSwitchOutletState OBJECT-TYPE Getting this OID will reply the status of all outlets in the switch. '0' for outlet off, '1' for outlet on. The index from left to right is outlet#8, #7, #6, #5, #4, #3, #2, #1. For Example: If the string is '01011010', it means the outlets status are the following: outlet #8 is off, outlet #7 is on, outlet #6 is off, outlet #5 is on, outlet #4 is on, outlet #3 is off, outlet #2 is on, outlet #1 is off. | 1.3.6.1.4.1.3808.1.1.2.2.2.1.3 | DisplayString | read-only | mandatory |
| eSwitchBaseCtrTable OBJECT-TYPE A list of switch control parameters. The number of entries is given by the value of eSwitchNumber. | 1.3.6.1.4.1.3808.1.1.2.2.3 | not-accessible | mandatory | |
| eSwitchBaseCtrEntry OBJECT-TYPE An entry control information of individual switches. | 1.3.6.1.4.1.3808.1.1.2.2.3.1 | not-accessible | mandatory | |
| eSwitchCtrID OBJECT-TYPE Select the switch ID to be controlled. | 1.3.6.1.4.1.3808.1.1.2.2.3.1.1 | INTEGER (0..16) | read-write | mandatory |
| eSwitchActOutlet OBJECT-TYPE The action outlets to be controlled. | 1.3.6.1.4.1.3808.1.1.2.2.3.1.2 | INTEGER | read-write | mandatory |
| eSwitchActType OBJECT-TYPE The on/off type of the action outlets. 1 for duration off, 2 for duration on, 3 for immediately off, 4 for immediately on, and 5 for reboot. | 1.3.6.1.4.1.3808.1.1.2.2.3.1.3 | INTEGER | read-write | mandatory |
| ePDU OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3 | |||
| ePDUIdent OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.1 | |||
| ePDUIdentName OBJECT-TYPE The name of the Rack PDU. The maximum string size is device dependent. | 1.3.6.1.4.1.3808.1.1.3.1.1 | DisplayString | read-write | mandatory |
| ePDUIdentHardwareRev OBJECT-TYPE The hardware revision of the Rack PDU. This value is set at the factory. | 1.3.6.1.4.1.3808.1.1.3.1.2 | DisplayString | read-only | mandatory |
| ePDUIdentFirmwareRev OBJECT-TYPE An 8-byte ID string identifying the Rack PDU firmware revision. This value is set at the factory. | 1.3.6.1.4.1.3808.1.1.3.1.3 | DisplayString | read-only | mandatory |
| ePDUIdentDateOfManufacture OBJECT-TYPE The date when the Rack PDU was manufactured in mm/dd/yyyy format. This value is set at the factory. The year 2000 will be represented by 00. | 1.3.6.1.4.1.3808.1.1.3.1.4 | DisplayString | read-only | mandatory |
| ePDUIdentModelNumber OBJECT-TYPE A 10-character string identifying the model number of the Rack PDU. This value is set at the factory. | 1.3.6.1.4.1.3808.1.1.3.1.5 | DisplayString | read-only | mandatory |
| ePDUIdentSerialNumber OBJECT-TYPE A 12-character string identifying the serial number of the Rack PDU. This value is set at the factory. | 1.3.6.1.4.1.3808.1.1.3.1.6 | DisplayString | read-only | mandatory |
| ePDUIdentDeviceRating OBJECT-TYPE Getting this OID will return the electrical rating of the device. | 1.3.6.1.4.1.3808.1.1.3.1.7 | INTEGER | read-only | mandatory |
| ePDUIdentDeviceNumOutlets OBJECT-TYPE Getting this OID will return the number of outlets contained in the device. | 1.3.6.1.4.1.3808.1.1.3.1.8 | INTEGER | read-only | mandatory |
| ePDUIdentDeviceNumPhases OBJECT-TYPE Getting this OID will return the number of phases supported by the device. | 1.3.6.1.4.1.3808.1.1.3.1.9 | INTEGER | read-only | mandatory |
| ePDUIdentDeviceNumBreakers OBJECT-TYPE Getting this OID will return the number of circuit breakers supported by the device. This is the same as the number of banks of outlets. 0 will be returned if the unit has no phase breakers. | 1.3.6.1.4.1.3808.1.1.3.1.10 | INTEGER | read-only | mandatory |
| ePDUIdentDeviceBreakerRating OBJECT-TYPE Getting this OID will return rating of the circuit breakers on the device if it has any. | 1.3.6.1.4.1.3808.1.1.3.1.11 | INTEGER | read-only | mandatory |
| ePDUIdentDeviceOrientation OBJECT-TYPE Getting this OID will return the intended physical orientation of the device. OrientHorizonatal(1) indicates Horizontal. OrientVertical(2) indicates Vertical. | 1.3.6.1.4.1.3808.1.1.3.1.12 | INTEGER {orientHorizontal(1), orientVertical(2)} | read-only | mandatory |
| ePDUIdentDeviceOutletLayout OBJECT-TYPE Getting this OID will return outlet layout for the device. SeqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... SeqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... SeqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... SeqPhToPhGrouped(4) indicates outlet layout as follows: Otlts1-8::(3-1),Otlts9-16::(2-3),Otlts17-24::(1-2). | 1.3.6.1.4.1.3808.1.1.3.1.13 | INTEGER {seqPhaseToNeutral(1), seqPhaseToPhase(2), seqPhToNeu21PhToPh(3), seqPhToPhGrouped(4)} | read-only | mandatory |
| ePDUIdentDeviceDisplayOrientation OBJECT-TYPE Getting this OID will return the intended physical orientation of the Seven-Segment Display. displayNormal(1) indicates Normal. displayReverse(2)indicates Upside-Down. displayRotate90(3) indicates rotate 90 degree. displayRotate270(4) indicates rotate 270 degree. displayAuto(5) indicates auto-detect and rotate. | 1.3.6.1.4.1.3808.1.1.3.1.14 | INTEGER {displayNormal(1), displayReverse(2), displayRotate90(3), displayRotate270(4), displayAuto(5)} | read-write | mandatory |
| ePDUIdentDeviceLinetoLineVoltage OBJECT-TYPE Getting/Setting this OID will return/set the Line to Line Volatage. The valid range is between 0V to 440V | 1.3.6.1.4.1.3808.1.1.3.1.15 | INTEGER | read-write | mandatory |
| ePDUIdentIndicator OBJECT-TYPE PDU will perform a panel indicator test when the variable is set to testIndicators(2). It is no effective to set this value to noTestIndicators(1). | 1.3.6.1.4.1.3808.1.1.3.1.16 | INTEGER {noTestIndicators(1), testIndicators(2)} | read-write | mandatory |
| ePDULoad OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.2 | |||
| ePDULoadDevice OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.2.1 | |||
| ePDULoadDevMaxPhaseLoad OBJECT-TYPE Getting this OID will return the maximum rated power that each phase of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the unit is banked. | 1.3.6.1.4.1.3808.1.1.3.2.1.1 | INTEGER | read-only | mandatory |
| ePDULoadDevNumPhases OBJECT-TYPE The number of phases available with this Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.2.1.2 | INTEGER | read-only | mandatory |
| ePDULoadDevMaxBankLoad OBJECT-TYPE Getting this OID will return the maximum rated power that a bank of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the device does not have any banks. | 1.3.6.1.4.1.3808.1.1.3.2.1.3 | INTEGER | read-only | mandatory |
| ePDULoadDevNumBanks OBJECT-TYPE The number of banks of outlets available with this Rack PDU. A bank of outlets has a unique circuit breaker for a subset of the total number of outlets on the ePDU. 0 will be returned if the unit no banks. | 1.3.6.1.4.1.3808.1.1.3.2.1.4 | INTEGER | read-only | mandatory |
| ePDULoadDevBankTableSize OBJECT-TYPE The size of the Bank Table. | 1.3.6.1.4.1.3808.1.1.3.2.1.5 | INTEGER | read-only | mandatory |
| ePDULoadDevBankTable OBJECT-TYPE Allows for getting the Bank Max Load in the Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.2.1.6 | not-accessible | mandatory | |
| ePDULoadDevBankEntry OBJECT-TYPE The Rack PDU Banks Access. | 1.3.6.1.4.1.3808.1.1.3.2.1.6.1 | not-accessible | mandatory | |
| ePDULoadDevBankIndex OBJECT-TYPE The index to the Rack PDU bank entry. | 1.3.6.1.4.1.3808.1.1.3.2.1.6.1.1 | INTEGER (1..10) | read-only | mandatory |
| ePDULoadDevBankNumber OBJECT-TYPE Getting this OID will return the bank number. | 1.3.6.1.4.1.3808.1.1.3.2.1.6.1.2 | INTEGER | read-only | mandatory |
| ePDULoadDevBankMaxLoad OBJECT-TYPE Getting this OID will return the maximum rated power that each bank of the Rack PDU can provide. It is represented in Amps. | 1.3.6.1.4.1.3808.1.1.3.2.1.6.1.3 | INTEGER | read-only | mandatory |
| ePDULoadDevMaxOutletTableSize OBJECT-TYPE The size of the Outlet Table. | 1.3.6.1.4.1.3808.1.1.3.2.1.7 | INTEGER | read-only | mandatory |
| ePDULoadDevMaxOutletTable OBJECT-TYPE Allows for getting the Max Outlet Load in an Outlet Monitored Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.2.1.8 | not-accessible | mandatory | |
| ePDULoadDevMaxOutletEntry OBJECT-TYPE This gives access to Max Outlet Load of an Outlet Monitored Rack PDU | 1.3.6.1.4.1.3808.1.1.3.2.1.8.1 | not-accessible | mandatory | |
| ePDULoadDevOutletIndex OBJECT-TYPE The index to the Outlet Monitored Rack PDU Max Outlet Load entry. | 1.3.6.1.4.1.3808.1.1.3.2.1.8.1.1 | INTEGER (1..24) | read-only | mandatory |
| ePDULoadDevOutletNumber OBJECT-TYPE Getting this OID will return the Outlet number. | 1.3.6.1.4.1.3808.1.1.3.2.1.8.1.2 | INTEGER | read-only | mandatory |
| ePDULoadDevMaxOutletLoad OBJECT-TYPE Getting this OID will return the maximum rated power that each Outlet of an Outlet Monitored Rack PDU can provide. It is represented in Amps. | 1.3.6.1.4.1.3808.1.1.3.2.1.8.1.3 | INTEGER | read-only | mandatory |
| ePDULoadPhaseConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.2.2 | |||
| ePDULoadPhaseConfigTable OBJECT-TYPE Allows for configuration of each Rack PDU phase. The number of entries is contained in the ePDULoadDevNumPhases OID. | 1.3.6.1.4.1.3808.1.1.3.2.2.1 | not-accessible | mandatory | |
| ePDULoadPhaseConfigEntry OBJECT-TYPE The Rack PDU phase to configure. | 1.3.6.1.4.1.3808.1.1.3.2.2.1.1 | not-accessible | mandatory | |
| ePDULoadPhaseConfigIndex OBJECT-TYPE The index to the Rack PDU phase entry. | 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.1 | INTEGER {phase1(1), phase2(2), phase3(3)} | read-only | mandatory |
| ePDULoadPhaseConfigLowLoadThreshold OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. Maximum value must be less than the value returned by the ePDULoadPhaseConfigNearOverloadThreshold OID. | 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.2 | INTEGER | read-write | mandatory |
| ePDULoadPhaseConfigNearOverloadThreshold OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the ePDULoadPhaseConfigLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadPhaseConfigOverloadThreshold OID. | 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.3 | INTEGER | read-write | mandatory |
| ePDULoadPhaseConfigOverloadThreshold OBJECT-TYPE A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the ePDULoadPhaseConfigNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadDevMaxPhaseLoad OID. | 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.4 | INTEGER | read-write | mandatory |
| ePDULoadPhaseConfigAlarm OBJECT-TYPE Getting this OID will return the current Phase Alarm. | 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.5 | INTEGER {noLoadAlarm(1), underCurrentAlarm(2), nearOverCurrentAlarm(3), overCurrentAlarm(4)} | read-only | mandatory |
| ePDULoadStatus OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.2.3 | |||
| ePDULoadStatusTable OBJECT-TYPE Allows for getting of status of each Rack PDU phase/bank. The number of entries is calculated by adding the number of phases (ePDULoadDevNumPhases OID) and the number of banks of outlets (ePDULoadDevNumBanks) Number of entries = #phases + #banks. NOTE: If a device has phase and bank information, all phase information shall precede the bank information. | 1.3.6.1.4.1.3808.1.1.3.2.3.1 | not-accessible | mandatory | |
| ePDULoadStatusEntry OBJECT-TYPE The Rack PDU phase/bank to gather status from. | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1 | not-accessible | mandatory | |
| ePDULoadStatusIndex OBJECT-TYPE The index to the Rack PDU phase/bank entry. All phase information will precede any bank information | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.1 | INTEGER (1..10) | read-only | mandatory |
| ePDULoadStatusLoad OBJECT-TYPE Getting this OID will return the phase/bank load measured in tenths of Amps. | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.2 | Gauge | read-only | mandatory |
| ePDULoadStatusLoadState OBJECT-TYPE Getting this OID will return the phase/bank load state. loadNormal(1) indicates that the phase/bank is operating properly within the ePDULoadConfigLowLoadThreshold and ePDULoadConfigNearOverloadThreshold OID values. loadLow(2) indicates that the phase/bank load has dropped below the ePDULoadConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. loadNearOverload(3) indicates that the phase/bank load is greater than or equal to the ePDULoadConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. loadOverload(4) indicates that the phase/bank load is greater than or equal to the ePDULoadConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.3 | INTEGER {loadNormal(1), loadLow(2), loadNearOverload(3), loadOverload(4)} | read-only | mandatory |
| ePDULoadStatusPhaseNumber OBJECT-TYPE The phase number to which this record refers. | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.4 | INTEGER | read-only | mandatory |
| ePDULoadStatusBankNumber OBJECT-TYPE The bank number to which this record refers. A value of 0 will be returned if any bank is not present or if it is phase related. | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.5 | INTEGER | read-only | mandatory |
| ePDULoadStatusVoltage OBJECT-TYPE Getting this OID will return the phase/bank voltage measured in 0.1 volts. | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.6 | INTEGER | read-only | mandatory |
| ePDULoadStatusActivePower OBJECT-TYPE Getting this OID will return the phase/bank active power measured in watts. | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.7 | INTEGER | read-only | mandatory |
| ePDULoadStatusApparentPower OBJECT-TYPE Getting this OID will return the phase/bank apparent power measured in VA. | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.8 | INTEGER | read-only | mandatory |
| ePDULoadStatusPowerFactor OBJECT-TYPE Getting this OID will return power factor of the output measured in hundredths. A value of 100 representing a unity power factor (1.00). | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.9 | INTEGER | read-only | mandatory |
| ePDULoadStatusEnergy OBJECT-TYPE Getting this OID will return the phase/bank apparent power measured in 0.1 kilowatt-hours. | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.10 | INTEGER | read-only | mandatory |
| ePDULoadStatusEnergyStartTime OBJECT-TYPE Getting this OID will return the date and time of the last energy meter reset | 1.3.6.1.4.1.3808.1.1.3.2.3.1.1.11 | DisplayString | read-only | mandatory |
| ePDULoadBankConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.2.4 | |||
| ePDULoadBankConfigTable OBJECT-TYPE Allows for configuration of each Rack PDU bank. The number of entries is contained in the ePDULoadDevNumBanks OID. | 1.3.6.1.4.1.3808.1.1.3.2.4.1 | not-accessible | mandatory | |
| ePDULoadBankConfigEntry OBJECT-TYPE The Rack PDU bank to configure. | 1.3.6.1.4.1.3808.1.1.3.2.4.1.1 | not-accessible | mandatory | |
| ePDULoadBankConfigIndex OBJECT-TYPE The index to the Rack PDU bank entry. | 1.3.6.1.4.1.3808.1.1.3.2.4.1.1.1 | INTEGER (1..10) | read-only | mandatory |
| ePDULoadBankConfigLowLoadThreshold OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. Maximum value must be less than the value returned by the ePDULoadBankConfigNearOverloadThreshold OID. | 1.3.6.1.4.1.3808.1.1.3.2.4.1.1.2 | INTEGER | read-write | mandatory |
| ePDULoadBankConfigNearOverloadThreshold OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the ePDULoadBankConfigLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadBankConfigOverloadThreshold OID. | 1.3.6.1.4.1.3808.1.1.3.2.4.1.1.3 | INTEGER | read-write | mandatory |
| ePDULoadBankConfigOverloadThreshold OBJECT-TYPE A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the ePDULoadBankConfigNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadDevMaxBankLoad OID. | 1.3.6.1.4.1.3808.1.1.3.2.4.1.1.4 | INTEGER | read-write | mandatory |
| ePDULoadBankConfigAlarm OBJECT-TYPE Getting this OID will return the current Bank Alarm. | 1.3.6.1.4.1.3808.1.1.3.2.4.1.1.5 | INTEGER {noLoadAlarm(1), underCurrentAlarm(2), nearOverCurrentAlarm(3), overCurrentAlarm(4)} | read-only | mandatory |
| ePDUOutlet OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.3 | |||
| ePDUOutletDevice OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.3.1 | |||
| ePDUOutletDevCommand OBJECT-TYPE Setting this OID to immediateAllOn (2) will turn all outlets on immediately. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will reboot all outlets immediately. Setting this OID to delayedAllOn (5) will turn all outlets on as defined by each outlet's ePDUOutletConfigPowerOnTime OID value. Setting this OID to delayedAllOff (6) will turn all outlets off as defined by each outlet's ePDUOutletConfigPowerOffTime OID value. Setting this OID to delayedAllReboot (7) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest ePDUOutletConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be canceled. Getting this OID will return the noCommandAll (1) value. | 1.3.6.1.4.1.3808.1.1.3.3.1.1 | INTEGER {noCommandAll(1), immediateAllOn(2), immediateAllOff(3), immediateAllReboot(4), delayedAllOn(5), delayedAllOff(6), delayedAllReboot(7), cancelAllPendingCommands(8)} | read-write | mandatory |
| ePDUOutletDevColdstartDelay OBJECT-TYPE The amount of delay, in seconds, between when power is provided to the Switched Rack PDU and when the Switched Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes). | 1.3.6.1.4.1.3808.1.1.3.3.1.2 | INTEGER | read-write | mandatory |
| ePDUOutletDevNumCntrlOutlets OBJECT-TYPE The number of controlled outlets on this Switched Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.3.1.3 | INTEGER | read-only | mandatory |
| ePDUOutletDevNumTotalOutlets OBJECT-TYPE The total number of outlets on this Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.3.1.4 | INTEGER | read-only | mandatory |
| ePDUOutletDevMonitoredOutlets OBJECT-TYPE The total number of monitored outlets on this Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.3.1.5 | INTEGER | read-only | mandatory |
| ePDUOutletDevColdstartState OBJECT-TYPE The ePDU outlet state after coldstart. Allowed values are: 1 - all outlets on after coldstart. 2 - outlet status same as previous state. | 1.3.6.1.4.1.3808.1.1.3.3.1.6 | INTEGER {allOn(1), previous(2)} | read-write | mandatory |
| ePDUOutletPhase OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.3.2 | |||
| ePDUOutletPhaseTable OBJECT-TYPE Allows for management of outlets on a per phase basis. | 1.3.6.1.4.1.3808.1.1.3.3.2.1 | not-accessible | mandatory | |
| ePDUOutletPhaseEntry OBJECT-TYPE The phase to manage. | 1.3.6.1.4.1.3808.1.1.3.3.2.1.1 | not-accessible | mandatory | |
| ePDUOutletPhaseIndex OBJECT-TYPE The index to the Switched Rack PDU phase entry. | 1.3.6.1.4.1.3808.1.1.3.3.2.1.1.1 | INTEGER {phase1(1), phase2(2), phase3(3)} | read-only | mandatory |
| ePDUOutletPhaseOverloadRestriction OBJECT-TYPE This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigOverloadThreshold OID is exceeded. | 1.3.6.1.4.1.3808.1.1.3.3.2.1.1.2 | INTEGER {alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3)} | read-write | mandatory |
| ePDUOutletControl OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.3.3 | |||
| ePDUOutletControlTable OBJECT-TYPE Allows for control of the individual outlets. The number of entries is contained in the ePDUOutletDevNumCntrlOutlets OID. | 1.3.6.1.4.1.3808.1.1.3.3.3.1 | not-accessible | mandatory | |
| ePDUOutletControlEntry OBJECT-TYPE The outlet to control. | 1.3.6.1.4.1.3808.1.1.3.3.3.1.1 | not-accessible | mandatory | |
| ePDUOutletControlIndex OBJECT-TYPE The index to the outlet entry. | 1.3.6.1.4.1.3808.1.1.3.3.3.1.1.1 | INTEGER (1..24) | read-only | mandatory |
| ePDUOutletControlOutletName OBJECT-TYPE The name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. This OID is provided for informational purposes only. | 1.3.6.1.4.1.3808.1.1.3.3.3.1.1.2 | DisplayString | read-only | mandatory |
| ePDUOutletControlOutletPhase OBJECT-TYPE The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1. | 1.3.6.1.4.1.3808.1.1.3.3.3.1.1.3 | INTEGER {phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | mandatory |
| ePDUOutletControlOutletCommand OBJECT-TYPE Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will immediately reboot the outlet. Setting this variable to delayedOn (4) will turn the outlet on after the ePDUOutletConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (5) will turn the outlet off after the ePDUOutletConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched Rack PDU to perform a delayedOff command, wait the ePDUOutletConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (7) will cause any pending command to this outlet to be canceled. Setting this variable to outletIdentify (8) will cause PDU LED to display the number of the outlet. | 1.3.6.1.4.1.3808.1.1.3.3.3.1.1.4 | INTEGER {immediateOn(1), immediateOff(2), immediateReboot(3), delayedOn(4), delayedOff(5), delayedReboot(6), cancelPendingCommand(7), outletIdentify(8)} | read-write | mandatory |
| ePDUOutletControlOutletBank OBJECT-TYPE The bank associated with this outlet. | 1.3.6.1.4.1.3808.1.1.3.3.3.1.1.5 | INTEGER | read-only | mandatory |
| ePDUOutletConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.3.4 | |||
| ePDUOutletConfigTable OBJECT-TYPE Allows for configuration of individual outlets. The number of entries is contained in the ePDUOutletDevNumCntrlOutlets OID. | 1.3.6.1.4.1.3808.1.1.3.3.4.1 | not-accessible | mandatory | |
| ePDUOutletConfigEntry OBJECT-TYPE The outlet to configure. | 1.3.6.1.4.1.3808.1.1.3.3.4.1.1 | not-accessible | mandatory | |
| ePDUOutletConfigIndex OBJECT-TYPE The index to the outlet entry. | 1.3.6.1.4.1.3808.1.1.3.3.4.1.1.1 | INTEGER (1..24) | read-only | mandatory |
| ePDUOutletConfigOutletName OBJECT-TYPE The name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. | 1.3.6.1.4.1.3808.1.1.3.3.4.1.1.2 | DisplayString | read-write | mandatory |
| ePDUOutletConfigOutletPhase OBJECT-TYPE The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1. | 1.3.6.1.4.1.3808.1.1.3.3.4.1.1.3 | INTEGER {phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | mandatory |
| ePDUOutletConfigPowerOnTime OBJECT-TYPE The amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 - never power on. 0 - power on immediately. 1 to 7200 - power on up to 7200 seconds after being commanded. | 1.3.6.1.4.1.3808.1.1.3.3.4.1.1.4 | INTEGER | read-write | mandatory |
| ePDUOutletConfigPowerOffTime OBJECT-TYPE The amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never power off. 0 - power off immediately. 1 to 7200 - power off up to 7200 seconds after being commanded. | 1.3.6.1.4.1.3808.1.1.3.3.4.1.1.5 | INTEGER | read-write | mandatory |
| ePDUOutletConfigRebootDuration OBJECT-TYPE During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed range is any value between 5 and 60 seconds (1 minute). | 1.3.6.1.4.1.3808.1.1.3.3.4.1.1.6 | INTEGER | read-write | mandatory |
| ePDUOutletConfigOutletBank OBJECT-TYPE The bank associated with this outlet. | 1.3.6.1.4.1.3808.1.1.3.3.4.1.1.7 | INTEGER | read-only | mandatory |
| ePDUOutletConfigMonitoredTableSize OBJECT-TYPE The size of the Outlet Config Monitored Table | 1.3.6.1.4.1.3808.1.1.3.3.4.2 | INTEGER | read-only | mandatory |
| ePDUOutletConfigMonitoredTable OBJECT-TYPE Allows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.3.4.3 | not-accessible | mandatory | |
| ePDUOutletConfigMonitoredEntry OBJECT-TYPE This gives access to Monitored Outlet entries | 1.3.6.1.4.1.3808.1.1.3.3.4.3.1 | not-accessible | mandatory | |
| ePDUOutletConfigMonitoredIndex OBJECT-TYPE The index to the RACK PDU Phase entry. | 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.1 | INTEGER (1..24) | read-only | mandatory |
| ePDUOutletConfigMonitoredName OBJECT-TYPE The name of the Monitored Outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. | 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.2 | DisplayString | read-write | mandatory |
| ePDUOutletConfigMonitoredNumber OBJECT-TYPE The outlet number of an Outlet Monitored RACK PDU. | 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.3 | INTEGER | read-only | mandatory |
| ePDUOutletConfigMonitoredLowLoadThreshold OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in watts. A warning will be issued when the load is less than the threshold value. A threshold value of 0 effectively disables this warning. Maximum value must be less than the value returned by the ePDUOutletConfigMonitoredNearOverloadThreshold OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4 | INTEGER | read-write | mandatory |
| ePDUOutletConfigMonitoredNearOverloadThreshold OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in watts. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the ePDUOutletConfigMonitoredLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDUOutletConfigMonitoredOverloadThreshold OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.5 | INTEGER | read-write | mandatory |
| ePDUOutletConfigMonitoredOverloadThreshold OBJECT-TYPE A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in watts. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the ePDUOutletConfigMonitoredNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadDevMaxOutletLoad OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.6 | INTEGER | read-write | mandatory |
| ePDUOutletConfigMonitoredPeakLoadReset OBJECT-TYPE Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this oid will do nothing and return noAction (1) if the PDU support this feature, return notSupport (3) if the PDU do not support this feature. | 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.7 | INTEGER {noAction(1), reset(2), notSupport(3)} | read-write | mandatory |
| ePDUOutletConfigMonitoredEnergyReset OBJECT-TYPE Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this oid will do nothing and return noAction (1) if the PDU support this feature, return notSupport (3) if the PDU do not support this feature. | 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.8 | INTEGER {noAction(1), reset(2), notSupport(3)} | read-write | mandatory |
| ePDUOutletStatus OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.3.5 | |||
| ePDUOutletStatusTable OBJECT-TYPE Allows for getting of status of individual outlets. The number of entries is contained in the ePDUOutletDevNumCntrlOutlets OID. | 1.3.6.1.4.1.3808.1.1.3.3.5.1 | not-accessible | mandatory | |
| ePDUOutletStatusEntry OBJECT-TYPE The outlet to gather status from. | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1 | not-accessible | mandatory | |
| ePDUOutletStatusIndex OBJECT-TYPE The index to the outlet entry. | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.1 | INTEGER (1..24) | read-only | mandatory |
| ePDUOutletStatusOutletName OBJECT-TYPE The name of the outlet. The maximum string size is device dependent. This OID is provided for informational purposes only. | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.2 | DisplayString | read-only | mandatory |
| ePDUOutletStatusOutletPhase OBJECT-TYPE The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1. | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.3 | INTEGER {phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | mandatory |
| ePDUOutletStatusOutletState OBJECT-TYPE Getting this variable will return the outlet state. If the outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusOff (2) value will be returned. | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.4 | INTEGER {outletStatusOn(1), outletStatusOff(2)} | read-only | mandatory |
| ePDUOutletStatusCommandPending OBJECT-TYPE Getting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusNoCommandPending (2) will be returned. | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.5 | INTEGER {outletStatusCommandPending(1), outletStatusNoCommandPending(2)} | read-only | mandatory |
| ePDUOutletStatusOutletBank OBJECT-TYPE The bank associated with this outlet. | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.6 | INTEGER | read-only | mandatory |
| ePDUOutletStatusLoad OBJECT-TYPE Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in tenths of Amps. | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.7 | Gauge | read-only | mandatory |
| ePDUOutletStatusActivePower OBJECT-TYPE Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in watts | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.8 | Gauge | read-only | mandatory |
| ePDUOutletStatusAlarm OBJECT-TYPE Getting this OID will return the current outlet alarm | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.9 | INTEGER {noLoadAlarm(1), underCurrentAlarm(2), nearOverCurrentAlarm(3), overCurrentAlarm(4)} | read-only | mandatory |
| ePDUOutletStatusPeakPower OBJECT-TYPE The peak power consumption of the Rack PDU load in watts. This value can be reset by setting the oid ePDUOutletConfigMonitoredPeakLoadReset to reset (2) | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.10 | Gauge | read-only | mandatory |
| ePDUOutletStatusPeakPowerTime OBJECT-TYPE Get this oid shows the date and time that peak power consumption occurred | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.11 | DisplayString | read-only | mandatory |
| ePDUOutletStatusPeakPowerStart OBJECT-TYPE Get this oid shows the date and time that peak power consumption started | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.12 | DisplayString | read-only | mandatory |
| ePDUOutletStatusEnergy OBJECT-TYPE Energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. This value can be reset by setting the oid ePDUOutletConfigMonitoredEnergyReset to reset (2) | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.13 | Gauge | read-only | mandatory |
| ePDUOutletStatusEnergyStartTime OBJECT-TYPE Indicates the date and time of the last device energy meter reset | 1.3.6.1.4.1.3808.1.1.3.3.5.1.1.14 | DisplayString | read-only | mandatory |
| ePDUOutletBank OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.3.6 | |||
| ePDUOutletBankTable OBJECT-TYPE Allows for management of outlets on a per bank basis. | 1.3.6.1.4.1.3808.1.1.3.3.6.1 | not-accessible | mandatory | |
| ePDUOutletBankEntry OBJECT-TYPE The bank to manage. | 1.3.6.1.4.1.3808.1.1.3.3.6.1.1 | not-accessible | mandatory | |
| ePDUOutletBankIndex OBJECT-TYPE The index to the Switched Rack PDU bank entry. | 1.3.6.1.4.1.3808.1.1.3.3.6.1.1.1 | INTEGER (1..10) | read-only | mandatory |
| ePDUOutletBankOverloadRestriction OBJECT-TYPE This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the ePDULoadBankConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the ePDULoadBankConfigOverloadThreshold OID is exceeded. | 1.3.6.1.4.1.3808.1.1.3.3.6.1.1.2 | INTEGER {alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3)} | read-write | mandatory |
| ePDUPowerSupply OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.4 | |||
| ePDUPowerSupplyDevice OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.4.1 | |||
| ePDUPowerSupply1Status OBJECT-TYPE Getting this OID will return powerSupply1Ok(1) if power supply 1 is functioning normally. If not functioning normally, this OID will return powerSupply1Failed(2). | 1.3.6.1.4.1.3808.1.1.3.4.1.1 | INTEGER {powerSupplyOneOk(1), powerSupplyOneFailed(2)} | read-only | mandatory |
| ePDUPowerSupply2Status OBJECT-TYPE Getting this OID will return powerSupply2Ok(1) if power supply 2 is functioning normally. If not functioning normally, this OID will return powerSupply2Failed(2). Metered Rack PDUs do not have a redundant powersupply. | 1.3.6.1.4.1.3808.1.1.3.4.1.2 | INTEGER {powerSupplyTwoOk(1), powerSupplyTwoFailed(2), powerSupplyTwoNotPresent(3)} | read-only | mandatory |
| ePDUPowerSupplyAlarm OBJECT-TYPE Getting this OID will return powerSupply Alarm | 1.3.6.1.4.1.3808.1.1.3.4.1.3 | INTEGER {allAvailablePowerSuppliesOK(1), powerSupplyOneFailed(2), powerSupplyTwoFailed(3), powerSupplyOneandTwoFailed(4)} | read-only | mandatory |
| ePDUStatus OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.3.5 | |||
| ePDUStatusBankTableSize OBJECT-TYPE The size of the Status Bank Table | 1.3.6.1.4.1.3808.1.1.3.5.1 | INTEGER | read-only | mandatory |
| ePDUStatusBankTable OBJECT-TYPE Allows for getting of status of each Rack PDU Bank | 1.3.6.1.4.1.3808.1.1.3.5.2 | not-accessible | mandatory | |
| ePDUStatusBankEntry OBJECT-TYPE This gives access to Bank entries | 1.3.6.1.4.1.3808.1.1.3.5.2.1 | not-accessible | mandatory | |
| ePDUStatusBankIndex OBJECT-TYPE The index to the RACK PDU Bank entry. | 1.3.6.1.4.1.3808.1.1.3.5.2.1.1 | INTEGER (1..10) | read-only | mandatory |
| ePDUStatusBankNumber OBJECT-TYPE Getting this OID will return the bank number. | 1.3.6.1.4.1.3808.1.1.3.5.2.1.2 | INTEGER | read-only | mandatory |
| ePDUStatusBankState OBJECT-TYPE Getting this OID will return the bank load state. bankLoadNormal(1) indicates that the bank is operating properly within the ePDULoadBankConfigLowLoadThreshold and ePDULoadBankConfigNearOverloadThreshold OID values. bankLoadLow(2) indicates that the bank load has dropped below the ePDULoadBankConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. bankLoadNearOverload(3) indicates that the bank load is greater than or equal to the ePDULoadBankConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. bankLoadOverload(4) indicates that the bank load is greater than or equal to the ePDULoadBankConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. | 1.3.6.1.4.1.3808.1.1.3.5.2.1.3 | INTEGER {bankLoadNormal(1), bankLoadLow(2), bankLoadNearOverload(3), bankLoadOverload(4)} | read-only | mandatory |
| ePDUStatusPhaseTableSize OBJECT-TYPE The size of the Status Phase Table | 1.3.6.1.4.1.3808.1.1.3.5.3 | INTEGER | read-only | mandatory |
| ePDUStatusPhaseTable OBJECT-TYPE Allows for getting of status of each Rack PDU Phase | 1.3.6.1.4.1.3808.1.1.3.5.4 | not-accessible | mandatory | |
| ePDUStatusPhaseEntry OBJECT-TYPE This gives access to Phase entries | 1.3.6.1.4.1.3808.1.1.3.5.4.1 | not-accessible | mandatory | |
| ePDUStatusPhaseIndex OBJECT-TYPE The index to the RACK PDU Phase entry. | 1.3.6.1.4.1.3808.1.1.3.5.4.1.1 | INTEGER (1..10) | read-only | mandatory |
| ePDUStatusPhaseNumber OBJECT-TYPE Getting this OID will return the phase number. | 1.3.6.1.4.1.3808.1.1.3.5.4.1.2 | INTEGER | read-only | mandatory |
| ePDUStatusPhaseState OBJECT-TYPE Getting this OID will return the Phase load state. phaseLoadNormal(1) indicates that the Phase is operating properly within the ePDULoadPhaseConfigLowLoadThreshold and ePDULoadPhaseConfigNearOverloadThreshold OID values. phaseLoadLow(2) indicates that the Phase load has dropped below the ePDULoadPhaseConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadNearOverload(3) indicates that the Phase load is greater than or equal to the ePDULoadPhaseConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadOverload(4) indicates that the Phase load is greater than or equal to the ePDULoadPhaseConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. | 1.3.6.1.4.1.3808.1.1.3.5.4.1.3 | INTEGER {phaseLoadNormal(1), phaseLoadLow(2), phaseLoadNearOverload(3), phaseLoadOverload(4)} | read-only | mandatory |
| ePDUStatusOutletTableSize OBJECT-TYPE The size of the Status Outlet Table | 1.3.6.1.4.1.3808.1.1.3.5.5 | INTEGER | read-only | mandatory |
| ePDUStatusOutletTable OBJECT-TYPE Allows for getting of status of each Outlet of an Outlet Monitored Rack PDU. | 1.3.6.1.4.1.3808.1.1.3.5.6 | not-accessible | mandatory | |
| ePDUStatusOutletEntry OBJECT-TYPE This gives access to Outlet entries | 1.3.6.1.4.1.3808.1.1.3.5.6.1 | not-accessible | mandatory | |
| ePDUStatusOutletIndex OBJECT-TYPE The index to the RACK PDU Outlet entry. | 1.3.6.1.4.1.3808.1.1.3.5.6.1.1 | INTEGER (1..24) | read-only | mandatory |
| ePDUStatusOutletNumber OBJECT-TYPE Getting this OID will return the Outlet number. | 1.3.6.1.4.1.3808.1.1.3.5.6.1.2 | INTEGER | read-only | mandatory |
| ePDUStatusOutletState OBJECT-TYPE Getting this OID will return the Outlet load state. outletLoadNormal(1) indicates that the Outlet is operating properly within the ePDUOutletConfigMonitoredLowLoadThreshold and ePDUOutletConfigMonitoredNearOverloadThreshold OID values. outletLoadLow(2) indicates that the Outlet load has dropped below the ePDUOutletConfigMonitoredLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. outletLoadNearOverload(3) indicates that the Outlet load is greater than or equal to the ePDUOutletConfigMonitoredNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. outletLoadOverload(4) indicates that the Outlet load is greater than or equal to the ePDUOutletConfigMonitoredOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. | 1.3.6.1.4.1.3808.1.1.3.5.6.1.3 | INTEGER {outletLoadNormal(1), outletLoadLow(2), outletLoadNearOverload(3), outletLoadOverload(4)} | read-only | mandatory |
| ePDUStatusInputVoltage OBJECT-TYPE The input voltage in 0.1 Volt. | 1.3.6.1.4.1.3808.1.1.3.5.7 | INTEGER | read-only | mandatory |
| ePDUStatusInputFrequency OBJECT-TYPE The input frequency in 0.1 Hertz. | 1.3.6.1.4.1.3808.1.1.3.5.8 | INTEGER | read-only | mandatory |
| environmentSensor OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.4 | |||
| envirIdent OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.4.1 | |||
| envirIdentName OBJECT-TYPE The name of the environment sensor. The maximum string size is device dependent. | 1.3.6.1.4.1.3808.1.1.4.1.1 | DisplayString | read-write | mandatory |
| envirIdentLocation OBJECT-TYPE The location of the environment sensor. The maximum string size is device dependent. | 1.3.6.1.4.1.3808.1.1.4.1.2 | DisplayString | read-write | mandatory |
| envirTemp OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.4.2 | |||
| envirTemperature OBJECT-TYPE The environment temperature expressed in 1/10 Fahrenheit | 1.3.6.1.4.1.3808.1.1.4.2.1 | INTEGER | read-only | mandatory |
| envirTempHighThreshold OBJECT-TYPE The high temperature threshold of the environment sensor. The value expressed in Fahrenheit. | 1.3.6.1.4.1.3808.1.1.4.2.2 | INTEGER | read-write | mandatory |
| envirTempLowThreshold OBJECT-TYPE The low temperature threshold of the environment sensor. The value expressed in Fahrenheit. | 1.3.6.1.4.1.3808.1.1.4.2.3 | INTEGER | read-write | mandatory |
| envirTempRateOfChange OBJECT-TYPE The rate of change of the temperature. The value expressed in Fahrenheit per 5 minute. | 1.3.6.1.4.1.3808.1.1.4.2.4 | INTEGER | read-write | mandatory |
| envirTempHysteresis OBJECT-TYPE The number of degrees beyond the temperature thresholds at which an active temperature alarm will be cleared. This configuration setting applies to all temperature thresholds. Units are displayed in Fahrenheit. | 1.3.6.1.4.1.3808.1.1.4.2.5 | INTEGER | read-write | mandatory |
| envirTemperatureCelsius OBJECT-TYPE The environment temperature expressed in 1/10 Celsius | 1.3.6.1.4.1.3808.1.1.4.2.6 | INTEGER | read-only | mandatory |
| envirTempCelsiusHighThreshold OBJECT-TYPE The high temperature threshold of the environment sensor. The value expressed in Celsius. | 1.3.6.1.4.1.3808.1.1.4.2.7 | INTEGER | read-write | mandatory |
| envirTempCelsiusLowThreshold OBJECT-TYPE The low temperature threshold of the environment sensor. The value expressed in Celsius. | 1.3.6.1.4.1.3808.1.1.4.2.8 | INTEGER | read-write | mandatory |
| envirTempCelsiusRateOfChange OBJECT-TYPE The rate of change of the temperature. The value expressed in Celsius per 5 minute. | 1.3.6.1.4.1.3808.1.1.4.2.9 | INTEGER | read-write | mandatory |
| envirTempCelsiusHysteresis OBJECT-TYPE The number of degrees beyond the temperature thresholds at which an active temperature alarm will be cleared. This configuration setting applies to all temperature thresholds. Units are displayed in Celsius. | 1.3.6.1.4.1.3808.1.1.4.2.10 | INTEGER | read-write | mandatory |
| envirHumid OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.4.3 | |||
| envirHumidity OBJECT-TYPE The environment relative humidity expressed in persentage. | 1.3.6.1.4.1.3808.1.1.4.3.1 | INTEGER | read-only | mandatory |
| envirHumidHighThreshold OBJECT-TYPE The high relative humidity threshold of the environment sensor. The value expressed in persentage. | 1.3.6.1.4.1.3808.1.1.4.3.2 | INTEGER | read-write | mandatory |
| envirHumidLowThreshold OBJECT-TYPE The low relative humidity threshold of the environment sensor. The value expressed in persentage. | 1.3.6.1.4.1.3808.1.1.4.3.3 | INTEGER | read-write | mandatory |
| envirHumidRateOfChange OBJECT-TYPE The rate of change of the relative humidity. The value expressed in persentage per 5 minute. | 1.3.6.1.4.1.3808.1.1.4.3.4 | INTEGER | read-write | mandatory |
| envirHumidHysteresis OBJECT-TYPE The number of degrees beyond the relative humidity thresholds at which an active relative humidity alarm will be cleared. This configuration setting applies to all relative humidity thresholds. Units are displayed in persentage. | 1.3.6.1.4.1.3808.1.1.4.3.5 | INTEGER | read-write | mandatory |
| envirContact OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.4.4 | |||
| envirContactTableSize OBJECT-TYPE The number of the contact in the environment sensor. | 1.3.6.1.4.1.3808.1.1.4.4.1 | INTEGER | read-only | mandatory |
| envirContactTable OBJECT-TYPE Allows for getting of information of each contact of the environment sensor. | 1.3.6.1.4.1.3808.1.1.4.4.2 | not-accessible | mandatory | |
| envirContactEntry OBJECT-TYPE This gives access to contact entries | 1.3.6.1.4.1.3808.1.1.4.4.2.1 | not-accessible | mandatory | |
| envirContactIndex OBJECT-TYPE The index to the contact of the environment sensor. | 1.3.6.1.4.1.3808.1.1.4.4.2.1.1 | INTEGER (1..4) | read-only | mandatory |
| envirContactName OBJECT-TYPE Getting or setting the name of the contact of the environment sensor. | 1.3.6.1.4.1.3808.1.1.4.4.2.1.2 | DisplayString | read-write | mandatory |
| envirContactStatus OBJECT-TYPE Getting this OID will return the Contact Status. | 1.3.6.1.4.1.3808.1.1.4.4.2.1.3 | INTEGER {contactNormal(1), contactAbnormal(2)} | read-only | mandatory |
| envirContactNormalState OBJECT-TYPE Set the contact normal state. | 1.3.6.1.4.1.3808.1.1.4.4.2.1.4 | INTEGER {normalOpen(1), normalClose(2)} | read-write | mandatory |
| ats OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5 | |||
| atsIdent OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.1 | |||
| atsIdentName OBJECT-TYPE The name of the ATS. The maximum string size is device dependent. | 1.3.6.1.4.1.3808.1.1.5.1.1 | DisplayString | read-write | mandatory |
| atsIdentModelName OBJECT-TYPE A string identifying the model name of the Automatic Transfer Switch. This value is set at the factory. | 1.3.6.1.4.1.3808.1.1.5.1.2 | DisplayString | read-only | mandatory |
| atsIdentHardwareRev OBJECT-TYPE The hardware revision of the Automatic Transfer Switch. This value is set at the factory. | 1.3.6.1.4.1.3808.1.1.5.1.3 | DisplayString | read-only | mandatory |
| atsIdentFirmwareRev OBJECT-TYPE A string identifying the Automatic Transfer Switch firmware revision. | 1.3.6.1.4.1.3808.1.1.5.1.4 | DisplayString | read-only | mandatory |
| atsIdentSerialNumber OBJECT-TYPE A string identifying the serial number of the Automatic Transfer Switch. This value is set at the factory. | 1.3.6.1.4.1.3808.1.1.5.1.5 | DisplayString | read-only | mandatory |
| atsIdentDateOfManufacture OBJECT-TYPE The date when the Automatic Transfer Switch was manufactured in mm/dd/yyyy format. This value is set at the factory. | 1.3.6.1.4.1.3808.1.1.5.1.6 | DisplayString | read-only | mandatory |
| atsIdentDeviceRatingVoltage OBJECT-TYPE A string identifing the Automatic Transfer Switch rating voltage. | 1.3.6.1.4.1.3808.1.1.5.1.7 | DisplayString | read-only | mandatory |
| atsIdentDeviceRatingCurrent OBJECT-TYPE This gives the device rating current in Amps | 1.3.6.1.4.1.3808.1.1.5.1.8 | INTEGER | read-only | mandatory |
| atsIdentDeviceOutletNum OBJECT-TYPE This gives the outlet number of the device | 1.3.6.1.4.1.3808.1.1.5.1.9 | INTEGER | read-only | mandatory |
| atsIdentAgentModelName OBJECT-TYPE A string identifying the model name of the Agent. | 1.3.6.1.4.1.3808.1.1.5.1.10 | DisplayString | read-only | mandatory |
| atsIdentAgentHardwareRevision OBJECT-TYPE The hardware revision of the Agent. | 1.3.6.1.4.1.3808.1.1.5.1.11 | DisplayString | read-only | mandatory |
| atsIdentAgentFirmwareRevision OBJECT-TYPE A string identifying the Agent firmware revision. | 1.3.6.1.4.1.3808.1.1.5.1.12 | DisplayString | read-only | mandatory |
| atsIdentAgentSerialNumber OBJECT-TYPE A string identifying the serial number of the Agent. | 1.3.6.1.4.1.3808.1.1.5.1.13 | DisplayString | read-only | mandatory |
| atsStatus OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.2 | |||
| atsStatusDevice OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.2.1 | |||
| atsStatusCommStatus OBJECT-TYPE This variable returns the current communication status between the Automatic Transfer Switch and the Agent. | 1.3.6.1.4.1.3808.1.1.5.2.1.1 | INTEGER {atsNeverDiscovered(1), atsCommEstablished(2), atsCommLost(3)} | read-only | mandatory |
| atsStatusSelectedSource OBJECT-TYPE This variable returns the current source of power. | 1.3.6.1.4.1.3808.1.1.5.2.1.2 | INTEGER {sourceA(1), sourceB(2)} | read-only | mandatory |
| atsStatusRedundancyState OBJECT-TYPE This variable returns the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails. atsFullyRedundant(2) indicates that the ATS will switch over to the alternate power source if the current source fails. | 1.3.6.1.4.1.3808.1.1.5.2.1.3 | INTEGER {atsRedundancyLost(1), atsFullyRedundant(2)} | read-only | mandatory |
| atsStatusPhaseSyncStatus OBJECT-TYPE This variable returns the status of the phase sync. | 1.3.6.1.4.1.3808.1.1.5.2.1.4 | INTEGER {inSync(1), outOfSync(2)} | read-only | mandatory |
| atsStatusDevSourceRelayStatus OBJECT-TYPE This variable returns the status of the source relay. | 1.3.6.1.4.1.3808.1.1.5.2.1.5 | INTEGER {sourceRelayNormal(1), sourceRelayFail(2)} | read-only | mandatory |
| atsStatusDevInRelayStatus OBJECT-TYPE This variable returns the status of the input relay. | 1.3.6.1.4.1.3808.1.1.5.2.1.6 | INTEGER {inputRelayNormal(1), inputRelayFail(2)} | read-only | mandatory |
| atsStatusDevOutRelayStatus OBJECT-TYPE This variable returns the status of the Output relay. | 1.3.6.1.4.1.3808.1.1.5.2.1.7 | INTEGER {outputRelayNormal(1), outputRelayFail(2)} | read-only | mandatory |
| atsStatusDevLCDCommStatus OBJECT-TYPE This variable returns the communication status of the LCD. | 1.3.6.1.4.1.3808.1.1.5.2.1.8 | INTEGER {lcdCommNormal(1), lcdCommFail(2)} | read-only | mandatory |
| atsStatusDevDB9CommStatus OBJECT-TYPE This variable returns the communication status of the DB9. | 1.3.6.1.4.1.3808.1.1.5.2.1.9 | INTEGER {db9CommNormal(1), db9CommFail(2)} | read-only | mandatory |
| atsStatusPowerSupplyTable OBJECT-TYPE A list of power supply table entries. | 1.3.6.1.4.1.3808.1.1.5.2.1.10 | not-accessible | mandatory | |
| atsStatusPowerSupplyEntry OBJECT-TYPE An entry containing power supply information applicable to a particular input. | 1.3.6.1.4.1.3808.1.1.5.2.1.10.1 | not-accessible | mandatory | |
| atsStatusPowerSupplyTableIndex OBJECT-TYPE The input identifier. | 1.3.6.1.4.1.3808.1.1.5.2.1.10.1.1 | INTEGER (1..10) | read-only | mandatory |
| atsStatusPowerSupplyInputSource OBJECT-TYPE The input source to the power supply. | 1.3.6.1.4.1.3808.1.1.5.2.1.10.1.2 | INTEGER {sourceA(1), sourceB(2)} | read-only | mandatory |
| atsStatusPowerSupply12VStatus OBJECT-TYPE This variable returns the status of the power supply A 12V in system. | 1.3.6.1.4.1.3808.1.1.5.2.1.10.1.3 | INTEGER {powerSupplyOK(1), powerSupplyFailure(2)} | read-only | mandatory |
| atsStatusPowerSupply5VStatus OBJECT-TYPE This variable returns the status of the power supply A 5V in system. | 1.3.6.1.4.1.3808.1.1.5.2.1.10.1.4 | INTEGER {powerSupplyOK(1), powerSupplyFailure(2)} | read-only | mandatory |
| atsStatusPowerSupply3p3VStatus OBJECT-TYPE This variable returns the status of the power supply A 3.3V in system. | 1.3.6.1.4.1.3808.1.1.5.2.1.10.1.5 | INTEGER {powerSupplyOK(1), powerSupplyFailure(2)} | read-only | mandatory |
| atsStatusInput OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.2.2 | |||
| atsStatusInputNum OBJECT-TYPE The number of input feeds to this device. This variable indicates the number of rows in the status input table. | 1.3.6.1.4.1.3808.1.1.5.2.2.1 | INTEGER | read-only | mandatory |
| atsStatusInputTable OBJECT-TYPE A list of input table entries. The number of entries is given by the value of atsNumInputs. | 1.3.6.1.4.1.3808.1.1.5.2.2.2 | not-accessible | mandatory | |
| atsStatusInputEntry OBJECT-TYPE An entry containing information applicable to a particular input. | 1.3.6.1.4.1.3808.1.1.5.2.2.2.1 | not-accessible | mandatory | |
| atsStatusInputTableIndex OBJECT-TYPE The input identifier. | 1.3.6.1.4.1.3808.1.1.5.2.2.2.1.1 | INTEGER (1..10) | read-only | mandatory |
| atsStatusInputName OBJECT-TYPE A name given to a particular input. | 1.3.6.1.4.1.3808.1.1.5.2.2.2.1.2 | DisplayString | read-write | mandatory |
| atsStatusNumInputPhase OBJECT-TYPE The number of input phases utilized in this device. The sum of all the atsStatusNumInputPhase variable indicates the number of rows in the status input phase table. | 1.3.6.1.4.1.3808.1.1.5.2.2.2.1.3 | INTEGER | read-only | mandatory |
| atsStatusInputVoltageOrientation OBJECT-TYPE The input voltage orientation: 1: unknown for this Source 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase 2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1. | 1.3.6.1.4.1.3808.1.1.5.2.2.2.1.4 | INTEGER {unknown(1), singlePhase(2), splitPhase(3), threePhasePhaseToNeutral(4), threePhasePhaseToPhase(5)} | read-only | mandatory |
| atsStatusInputVoltage OBJECT-TYPE The input voltage in 0.1 Volt. | 1.3.6.1.4.1.3808.1.1.5.2.2.2.1.5 | INTEGER | read-only | mandatory |
| atsStatusInputFrequency OBJECT-TYPE The input frequency in 0.1 Hertz. | 1.3.6.1.4.1.3808.1.1.5.2.2.2.1.6 | INTEGER | read-only | mandatory |
| atsStatusInputVolState OBJECT-TYPE The input voltage status. | 1.3.6.1.4.1.3808.1.1.5.2.2.2.1.7 | INTEGER {normal(1), overVoltage(2), underVoltage(3)} | read-only | mandatory |
| atsStatusInputFreqState OBJECT-TYPE The input frequency status. | 1.3.6.1.4.1.3808.1.1.5.2.2.2.1.8 | INTEGER {normal(1), overFrequency(2), underFrequency(3)} | read-only | mandatory |
| atsStatusInputPhaseTable OBJECT-TYPE A list of input table entries. The number of entries is given by the sum of the atsNumInputPhases. | 1.3.6.1.4.1.3808.1.1.5.2.2.3 | not-accessible | mandatory | |
| atsStatusInputPhaseEntry OBJECT-TYPE An entry containing information applicable to a particular input phase. | 1.3.6.1.4.1.3808.1.1.5.2.2.3.1 | not-accessible | mandatory | |
| atsStatusInputPhaseTableIndex OBJECT-TYPE The input identifier. | 1.3.6.1.4.1.3808.1.1.5.2.2.3.1.1 | INTEGER (1..10) | read-only | mandatory |
| atsStatusInputPhaseIndex OBJECT-TYPE The input phase identifier. | 1.3.6.1.4.1.3808.1.1.5.2.2.3.1.2 | INTEGER (1..10) | read-only | mandatory |
| atsStatusInputPhaseVoltage OBJECT-TYPE The input voltage in VAC, or -1 if it's unsupported by this Source. | 1.3.6.1.4.1.3808.1.1.5.2.2.3.1.3 | INTEGER | read-only | mandatory |
| atsStatusInputPhaseCurrent OBJECT-TYPE The input current in amperes, or -1 if it's unsupported by this Source. | 1.3.6.1.4.1.3808.1.1.5.2.2.3.1.4 | INTEGER | read-only | mandatory |
| atsStatusInputPhasePower OBJECT-TYPE The input power in Watts, or -1 if it's unsupported by this Source. | 1.3.6.1.4.1.3808.1.1.5.2.2.3.1.5 | INTEGER | read-only | mandatory |
| atsConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.3 | |||
| atsConfigPreferredSource OBJECT-TYPE This variable returns the preferred source of power when both sources are OK. | 1.3.6.1.4.1.3808.1.1.5.3.1 | INTEGER {sourceA(1), sourceB(2), none(3)} | read-write | mandatory |
| atsConfigNominalVoltage OBJECT-TYPE This variable returns the nominal voltage of the input. | 1.3.6.1.4.1.3808.1.1.5.3.2 | INTEGER | read-write | mandatory |
| atsConfigVoltageSensitivity OBJECT-TYPE This variable defines the sensitivity to changes in voltage: high(1) for best protection, low(3) for frequent small line voltage changes. | 1.3.6.1.4.1.3808.1.1.5.3.3 | INTEGER {high(1), medium(2), low(3)} | read-write | mandatory |
| atsConfigTransferVoltageRange OBJECT-TYPE This variable defines the range of acceptable voltage from a power source. If the voltage measured from the selected input source is not within this range, the Automatic Transfer Switch will switch over (transfer) to the alternate power source. | 1.3.6.1.4.1.3808.1.1.5.3.4 | INTEGER {wide(1), medium(2), narrow(3)} | read-write | mandatory |
| atsConfigNarrowRangeValue OBJECT-TYPE To configure the Narrow Range value of acceptable voltage from a power source. | 1.3.6.1.4.1.3808.1.1.5.3.5 | INTEGER | read-write | mandatory |
| atsConfigMediumRangeValue OBJECT-TYPE To configure the Medium Range value of acceptable voltage from a power source. | 1.3.6.1.4.1.3808.1.1.5.3.6 | INTEGER | read-write | mandatory |
| atsConfigWideRangeValue OBJECT-TYPE To configure the Wide Range value of acceptable voltage from a power source. | 1.3.6.1.4.1.3808.1.1.5.3.7 | INTEGER | read-write | mandatory |
| atsConfigFrequencyDeviation OBJECT-TYPE To configure the frequency deviation. | 1.3.6.1.4.1.3808.1.1.5.3.8 | INTEGER (1..3) | read-write | mandatory |
| atsConfigDevLCDOffTime OBJECT-TYPE The amount of time (in seconds) which LCD turn off automatically after it remains idle for. | 1.3.6.1.4.1.3808.1.1.5.3.9 | INTEGER | read-write | mandatory |
| atsControl OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.4 | |||
| atsCtrlResetATS OBJECT-TYPE Setting this variable will cause the Automatic Transfer Switch to reboot or reset relative setting to default value. | 1.3.6.1.4.1.3808.1.1.5.4.1 | INTEGER {none(1), rboot(2), reset(3)} | read-write | mandatory |
| atsCtrlClearEventCounts OBJECT-TYPE Setting this variable will clear all event counts in Automatic Transfer Switch. Returns (-1) if unsupported. | 1.3.6.1.4.1.3808.1.1.5.4.2 | INTEGER {none(1), clear(2)} | read-write | mandatory |
| atsLoad OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.5 | |||
| atsLoadDevice OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.5.1 | |||
| atsLoadDevPhaseTableSize OBJECT-TYPE The size of the Phase Table. | 1.3.6.1.4.1.3808.1.1.5.5.1.1 | INTEGER | read-only | mandatory |
| atsLoadDevPhaseTable OBJECT-TYPE Allows for getting the Phase Max Load in the ATS. | 1.3.6.1.4.1.3808.1.1.5.5.1.2 | not-accessible | mandatory | |
| atsLoadDevPhaseEntry OBJECT-TYPE The ATS Phases Access. | 1.3.6.1.4.1.3808.1.1.5.5.1.2.1 | not-accessible | mandatory | |
| atsLoadDevPhaseTableIndex OBJECT-TYPE The index to ATS phase entry. | 1.3.6.1.4.1.3808.1.1.5.5.1.2.1.1 | INTEGER (1..10) | read-only | mandatory |
| atsLoadDevPhase OBJECT-TYPE For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), phase3 (3), phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1. | 1.3.6.1.4.1.3808.1.1.5.5.1.2.1.2 | INTEGER {phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | mandatory |
| atsLoadDevPhaseMaxLoad OBJECT-TYPE Getting this OID will return the maximum rated power that each phase of the ATS can provide. It is represented in Amps. | 1.3.6.1.4.1.3808.1.1.5.5.1.2.1.3 | INTEGER | read-only | mandatory |
| atsLoadDevBankTableSize OBJECT-TYPE The size of the Bank Table. | 1.3.6.1.4.1.3808.1.1.5.5.1.3 | INTEGER | read-only | mandatory |
| atsLoadDevBankTable OBJECT-TYPE Allows for getting the Bank Max Load in the ATS. | 1.3.6.1.4.1.3808.1.1.5.5.1.4 | not-accessible | mandatory | |
| atsLoadDevBankEntry OBJECT-TYPE The ATS Banks Access. | 1.3.6.1.4.1.3808.1.1.5.5.1.4.1 | not-accessible | mandatory | |
| atsLoadDevBankTableIndex OBJECT-TYPE The index to the ATS bank entry. | 1.3.6.1.4.1.3808.1.1.5.5.1.4.1.1 | INTEGER {total(1), bank1(2), bank2(3), bank3(4)} | read-only | mandatory |
| atsLoadDevBankMaxLoad OBJECT-TYPE Getting this OID will return the maximum rated power that each bank of the ATS can provide. It is represented in Amps. | 1.3.6.1.4.1.3808.1.1.5.5.1.4.1.2 | INTEGER | read-only | mandatory |
| atsLoadStatus OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.5.2 | |||
| atsLoadStatusPhaseTableSize OBJECT-TYPE The size of the Phase Table. | 1.3.6.1.4.1.3808.1.1.5.5.2.1 | INTEGER | read-only | mandatory |
| atsLoadStatusPhaseTable OBJECT-TYPE Allows for getting the Phase Load status in the ATS. | 1.3.6.1.4.1.3808.1.1.5.5.2.2 | not-accessible | mandatory | |
| atsLoadStatusPhaseEntry OBJECT-TYPE The ATS Phases Access. | 1.3.6.1.4.1.3808.1.1.5.5.2.2.1 | not-accessible | mandatory | |
| atsLoadStatusPhaseTableIndex OBJECT-TYPE The index to ATS phase entry. | 1.3.6.1.4.1.3808.1.1.5.5.2.2.1.1 | INTEGER (1..10) | read-only | mandatory |
| atsLoadStatusPhase OBJECT-TYPE For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), phase3 (3), phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1. | 1.3.6.1.4.1.3808.1.1.5.5.2.2.1.2 | INTEGER {phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | mandatory |
| atsLoadStatusPhaseLoad OBJECT-TYPE The output current in 0.1 amperes drawn by the load on the ATS | 1.3.6.1.4.1.3808.1.1.5.5.2.2.1.3 | INTEGER | read-only | mandatory |
| atsLoadStatusPhaseLoadState OBJECT-TYPE Getting this OID will return the phase load state. | 1.3.6.1.4.1.3808.1.1.5.5.2.2.1.4 | INTEGER {normal(1), lowLoad(2), nearOverLoad(3), overLoad(4)} | read-only | mandatory |
| atsLoadStatusPhasePower OBJECT-TYPE The output power in Watts. | 1.3.6.1.4.1.3808.1.1.5.5.2.2.1.5 | INTEGER | read-only | mandatory |
| atsLoadStatusBankTableSize OBJECT-TYPE The size of the Bank Table. | 1.3.6.1.4.1.3808.1.1.5.5.2.3 | INTEGER | read-only | mandatory |
| atsLoadStatusBankTable OBJECT-TYPE Allows for getting the Bank Load status in the ATS. | 1.3.6.1.4.1.3808.1.1.5.5.2.4 | not-accessible | mandatory | |
| atsLoadStatusBankEntry OBJECT-TYPE The ATS Bank Access. | 1.3.6.1.4.1.3808.1.1.5.5.2.4.1 | not-accessible | mandatory | |
| atsLoadStatusBankTableIndex OBJECT-TYPE The index to ATS bank entry. | 1.3.6.1.4.1.3808.1.1.5.5.2.4.1.1 | INTEGER {total(1), bank1(2), bank2(3), bank3(4)} | read-only | mandatory |
| atsLoadStatusBankPhase OBJECT-TYPE Getting this OID will return the phase number. | 1.3.6.1.4.1.3808.1.1.5.5.2.4.1.2 | INTEGER {phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | mandatory |
| atsLoadStatusBankLoad OBJECT-TYPE The output current in 0.1 amperes drawn by the load on the ATS | 1.3.6.1.4.1.3808.1.1.5.5.2.4.1.3 | INTEGER | read-only | mandatory |
| atsLoadStatusBankLoadState OBJECT-TYPE Getting this OID will return the bank load state. | 1.3.6.1.4.1.3808.1.1.5.5.2.4.1.4 | INTEGER {normal(1), lowLoad(2), nearOverLoad(3), overLoad(4)} | read-only | mandatory |
| atsLoadStatusBankPower OBJECT-TYPE The output power in Watts. | 1.3.6.1.4.1.3808.1.1.5.5.2.4.1.5 | INTEGER | read-only | mandatory |
| atsLoadStatusBankEnergy OBJECT-TYPE Getting this OID will return the phase/bank apparent power measured in 0.1 kilowatt-hours. | 1.3.6.1.4.1.3808.1.1.5.5.2.4.1.6 | INTEGER | read-only | mandatory |
| atsLoadStatusBankStartTime OBJECT-TYPE Getting this OID will return the date and time of the last energy meter reset | 1.3.6.1.4.1.3808.1.1.5.5.2.4.1.7 | INTEGER | read-only | mandatory |
| atsLoadConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.5.3 | |||
| atsLoadCfgPhaseTableSize OBJECT-TYPE The size of the Phase Table. | 1.3.6.1.4.1.3808.1.1.5.5.3.1 | INTEGER | read-only | mandatory |
| atsLoadCfgPhaseTable OBJECT-TYPE Allows for configuration of each ATS phase. | 1.3.6.1.4.1.3808.1.1.5.5.3.2 | not-accessible | mandatory | |
| atsLoadCfgPhaseEntry OBJECT-TYPE The ATS phase to configure. | 1.3.6.1.4.1.3808.1.1.5.5.3.2.1 | not-accessible | mandatory | |
| atsLoadCfgPhaseTableIndex OBJECT-TYPE The index to the ATS phase entry. | 1.3.6.1.4.1.3808.1.1.5.5.3.2.1.1 | INTEGER (1..10) | read-only | mandatory |
| atsLoadCfgPhase OBJECT-TYPE For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), phase3 (3), phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1. | 1.3.6.1.4.1.3808.1.1.5.5.3.2.1.2 | INTEGER {phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | mandatory |
| atsLoadCfgPhaseLowLoad OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. | 1.3.6.1.4.1.3808.1.1.5.5.3.2.1.3 | INTEGER | read-write | mandatory |
| atsLoadCfgPhaseNearOverLoad OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. | 1.3.6.1.4.1.3808.1.1.5.5.3.2.1.4 | INTEGER | read-write | mandatory |
| atsLoadCfgPhaseOverLoad OBJECT-TYPE A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. | 1.3.6.1.4.1.3808.1.1.5.5.3.2.1.5 | INTEGER | read-write | mandatory |
| atsLoadCfgPhaseOutletRestriction OBJECT-TYPE This OID controls the behavior of a ATS phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigOverloadThreshold OID is exceeded. | 1.3.6.1.4.1.3808.1.1.5.5.3.2.1.6 | INTEGER {alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3)} | read-write | mandatory |
| atsLoadCfgBankTableSize OBJECT-TYPE The size of the Bank Table. | 1.3.6.1.4.1.3808.1.1.5.5.3.3 | INTEGER | read-only | mandatory |
| atsLoadCfgBankTable OBJECT-TYPE Allows for configuration of each ATS bank. | 1.3.6.1.4.1.3808.1.1.5.5.3.4 | not-accessible | mandatory | |
| atsLoadCfgBankEntry OBJECT-TYPE The ATS phase to configure. | 1.3.6.1.4.1.3808.1.1.5.5.3.4.1 | not-accessible | mandatory | |
| atsLoadCfgBankTableIndex OBJECT-TYPE The index to the ATS bank entry. | 1.3.6.1.4.1.3808.1.1.5.5.3.4.1.1 | INTEGER {total(1), bank1(2), bank2(3), bank3(4)} | read-only | mandatory |
| atsLoadCfgBankLowLoad OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. | 1.3.6.1.4.1.3808.1.1.5.5.3.4.1.2 | INTEGER | read-write | mandatory |
| atsLoadCfgBankNearOverLoad OBJECT-TYPE A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. | 1.3.6.1.4.1.3808.1.1.5.5.3.4.1.3 | INTEGER | read-write | mandatory |
| atsLoadCfgBankOverLoad OBJECT-TYPE A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. | 1.3.6.1.4.1.3808.1.1.5.5.3.4.1.4 | INTEGER | read-write | mandatory |
| atsLoadCfgBankOutletRestriction OBJECT-TYPE This OID controls the behavior of a ATS phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigOverloadThreshold OID is exceeded. | 1.3.6.1.4.1.3808.1.1.5.5.3.4.1.5 | INTEGER {alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3)} | read-write | mandatory |
| atsOutlet OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.6 | |||
| atsOutletDevice OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.5.6.1 | |||
| atsOutletDevTotalOutletNum OBJECT-TYPE The total number of outlets on the ATS. | 1.3.6.1.4.1.3808.1.1.5.6.1.1 | INTEGER | read-only | mandatory |
| atsOutletDevCtrlOutletNum OBJECT-TYPE The number of controlled outlets on the ATS. | 1.3.6.1.4.1.3808.1.1.5.6.1.2 | INTEGER | read-only | mandatory |
| atsOutletDevColdStartDelay OBJECT-TYPE The amount of delay, in seconds, between when power is provided to the ATS and when the ATS provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes). | 1.3.6.1.4.1.3808.1.1.5.6.1.3 | INTEGER | read-write | mandatory |
| atsOutletDevColdStartState OBJECT-TYPE The ATS outlet state after coldstart. Allowed values are: 1 - all outlets on after coldstart. 2 - outlet status same as previous state. | 1.3.6.1.4.1.3808.1.1.5.6.1.4 | INTEGER {allOn(1), previous(2)} | read-write | mandatory |
| atsOutletDevLocalCtrl OBJECT-TYPE To configure enable or disable outlet local control function. | 1.3.6.1.4.1.3808.1.1.5.6.1.5 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| atsOutletDevCommand OBJECT-TYPE Setting this OID to immediateAllOn (2) will turn all outlets on immediately. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will reboot all outlets immediately. Setting this OID to delayedAllOn (5) will turn all outlets on as defined by each outlet's atsOutletCfgPowerOnTime OID value. Setting this OID to delayedAllOff (6) will turn all outlets off as defined by each outlet's atsOutletCfgPowerOffTime OID value. Setting this OID to delayedAllReboot (7) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack ATS will then delay the largest atsOutletCfgRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack ATS to be canceled. Getting this OID will return the noCommandAll (1) value. | 1.3.6.1.4.1.3808.1.1.5.6.1.6 | INTEGER {noCommandAll(1), immediateAllOn(2), immediateAllOff(3), immediateAllReboot(4), delayedAllOn(5), delayedAllOff(6), delayedAllReboot(7), cancelAllPendingCommands(8)} | read-write | mandatory |
| atsOutletStatusTableSize OBJECT-TYPE The size of the outlet status table. | 1.3.6.1.4.1.3808.1.1.5.6.2 | INTEGER | read-only | mandatory |
| atsOutletStatusTable OBJECT-TYPE Allows for getting of status of individual outlets. | 1.3.6.1.4.1.3808.1.1.5.6.3 | not-accessible | mandatory | |
| atsOutletStatusEntry OBJECT-TYPE The outlet to gather status from. | 1.3.6.1.4.1.3808.1.1.5.6.3.1 | not-accessible | mandatory | |
| atsOutletStatusTableIndex OBJECT-TYPE The index to the outlet entry. | 1.3.6.1.4.1.3808.1.1.5.6.3.1.1 | INTEGER (1..19) | read-only | mandatory |
| atsOutletStatusOutletName OBJECT-TYPE The name of the outlet. The maximum string size is device dependent. This OID is provided for informational purposes only. | 1.3.6.1.4.1.3808.1.1.5.6.3.1.2 | DisplayString | read-only | mandatory |
| atsOutletStatusOutletState OBJECT-TYPE Getting this variable will return the outlet state. If the outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusOff (2) value will be returned. | 1.3.6.1.4.1.3808.1.1.5.6.3.1.3 | INTEGER {outletStatusOn(1), outletStatusOff(2)} | read-only | mandatory |
| atsOutletStatusOutletCmdPending OBJECT-TYPE Getting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusNoCommandPending (2) will be returned. | 1.3.6.1.4.1.3808.1.1.5.6.3.1.4 | INTEGER {outletStatusCommandPending(1), outletStatusNoCommandPending(2)} | read-only | mandatory |
| atsOutletStatusOutletPhase OBJECT-TYPE The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1. | 1.3.6.1.4.1.3808.1.1.5.6.3.1.5 | INTEGER {phase1(1), phase2(2), phase3(3), phase1-2(4), phase2-3(5), phase3-1(6)} | read-only | mandatory |
| atsOutletStatusOutletBank OBJECT-TYPE The bank associated with this outlet. | 1.3.6.1.4.1.3808.1.1.5.6.3.1.6 | INTEGER | read-only | mandatory |
| atsOutletCtrlTableSize OBJECT-TYPE The size of the outlet control table. | 1.3.6.1.4.1.3808.1.1.5.6.4 | INTEGER | read-only | mandatory |
| atsOutletCtrlTable OBJECT-TYPE Allows for control of the individual outlets. | 1.3.6.1.4.1.3808.1.1.5.6.5 | not-accessible | mandatory | |
| atsOutletCtrlEntry OBJECT-TYPE The outlet to control. | 1.3.6.1.4.1.3808.1.1.5.6.5.1 | not-accessible | mandatory | |
| atsOutletCtrlTableIndex OBJECT-TYPE The index to the outlet entry. | 1.3.6.1.4.1.3808.1.1.5.6.5.1.1 | INTEGER (1..19) | read-only | mandatory |
| atsOutletCtrlOutletName OBJECT-TYPE The name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. This OID is provided for informational purposes only. | 1.3.6.1.4.1.3808.1.1.5.6.5.1.2 | DisplayString | read-only | mandatory |
| atsOutletCtrlCommand OBJECT-TYPE Getting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (3) will immediately turn the outlet off. Setting this variable to immediateReboot (4) will immediately reboot the outlet. Setting this variable to delayedOn (5) will turn the outlet on after the ePDUOutletConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (6) will turn the outlet off after the ePDUOutletConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (7) will cause the ATS to perform a delayedOff command, wait the atsOutletCfgRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (8) will cause any pending command to this outlet to be canceled. | 1.3.6.1.4.1.3808.1.1.5.6.5.1.3 | INTEGER {none(1), immediateOn(2), immediateOff(3), immediateReboot(4), delayedOn(5), delayedOff(6), delayedReboot(7), cancelPendingCommand(8)} | read-write | mandatory |
| atsOutletCfgTableSize OBJECT-TYPE The size of the outlet config table. | 1.3.6.1.4.1.3808.1.1.5.6.6 | INTEGER | read-only | mandatory |
| atsOutletCfgTable OBJECT-TYPE Allows for configuration of individual outlets. | 1.3.6.1.4.1.3808.1.1.5.6.7 | not-accessible | mandatory | |
| atsOutletCfgEntry OBJECT-TYPE The outlet to configure. | 1.3.6.1.4.1.3808.1.1.5.6.7.1 | not-accessible | mandatory | |
| atsOutletCfgTableIndex OBJECT-TYPE The index to the outlet entry. | 1.3.6.1.4.1.3808.1.1.5.6.7.1.1 | INTEGER (1..19) | read-only | mandatory |
| atsOutletCfgOutletName OBJECT-TYPE The name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. | 1.3.6.1.4.1.3808.1.1.5.6.7.1.2 | DisplayString | read-write | mandatory |
| atsOutletCfgPowerOnTime OBJECT-TYPE The amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 - never power on. 0 - power on immediately. 1 to 7200 - power on up to 7200 seconds after being commanded. | 1.3.6.1.4.1.3808.1.1.5.6.7.1.3 | INTEGER | read-write | mandatory |
| atsOutletCfgPowerOffTime OBJECT-TYPE The amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never power off. 0 - power off immediately. 1 to 7200 - power off up to 7200 seconds after being commanded. | 1.3.6.1.4.1.3808.1.1.5.6.7.1.4 | INTEGER | read-write | mandatory |
| atsOutletCfgRebootDuration OBJECT-TYPE During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed range is any value between 5 and 60 seconds (1 minute). | 1.3.6.1.4.1.3808.1.1.5.6.7.1.5 | INTEGER | read-write | mandatory |
| ePDU2 OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6 | |||
| ePDU2Role OBJECT-TYPE Get this oid shows the role the PDU played on Daisy Chain Group. The PDU as a Host can access whole ePDU2 content, and the PDU be standalong or a Slave can access itself instead. | 1.3.6.1.4.1.3808.1.1.6.1 | INTEGER {standalone(1), host(2), slave(3)} | read-only | mandatory |
| ePDU2Ident OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6.2 | |||
| ePDU2IdentTableSize OBJECT-TYPE PDU as a Host response total PDU ident number on daisy chain. PDU as a Slave can only response 1. | 1.3.6.1.4.1.3808.1.1.6.2.1 | INTEGER | read-only | mandatory |
| ePDU2IdentTable OBJECT-TYPE A table of Rack PDU identification information. | 1.3.6.1.4.1.3808.1.1.6.2.2 | not-accessible | mandatory | |
| ePDU2IdentEntry OBJECT-TYPE Identification data from Rack PDU being queried. | 1.3.6.1.4.1.3808.1.1.6.2.2.1 | not-accessible | mandatory | |
| ePDU2IdentIndex OBJECT-TYPE The index to the Rack PDU identification table entry. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.1 | INTEGER (1..4) | read-only | mandatory |
| ePDU2IdentModuleIndex OBJECT-TYPE The Rack PDU identification table entry numeric ID. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.2 | INTEGER | read-only | mandatory |
| ePDU2IdentName OBJECT-TYPE A user-defined string identifying the name of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.3 | DisplayString | read-only | mandatory |
| ePDU2IdentLocation OBJECT-TYPE A user-defined string identifying the location of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.4 | DisplayString | read-only | mandatory |
| ePDU2IdentContact OBJECT-TYPE A user-defined string identifying the person to contact of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.5 | DisplayString | read-only | mandatory |
| ePDU2IdentHardwareRev OBJECT-TYPE The Rack PDU hardware version. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.6 | DisplayString | read-only | mandatory |
| ePDU2IdentFirmwareRev OBJECT-TYPE The Rack PDU firmware version. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.7 | DisplayString | read-only | mandatory |
| ePDU2IdentDateOfManufacture OBJECT-TYPE The date the Rack PDU was manufactured in mm/dd/yyyy format. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.8 | DisplayString | read-only | mandatory |
| ePDU2IdentModelName OBJECT-TYPE The Rack PDU model number. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.9 | DisplayString | read-only | mandatory |
| ePDU2IdentSerialNumber OBJECT-TYPE The Rack PDU serial number. | 1.3.6.1.4.1.3808.1.1.6.2.2.1.10 | DisplayString | read-only | mandatory |
| ePDU2IdentIndicator OBJECT-TYPE PDU will perform a panel indicator test when the variable is set to testIndicators(2). It is no effective to set this value to noTestIndicators(1). | 1.3.6.1.4.1.3808.1.1.6.2.2.1.11 | INTEGER {noTestIndicators(1), testIndicators(2)} | read-write | mandatory |
| ePDU2Device OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6.3 | |||
| ePDU2DeviceTableSize OBJECT-TYPE A Host Rack PDU response total number of Rack PDUs on daisy chain. Rack PDU as a Slave can only response 1. | 1.3.6.1.4.1.3808.1.1.6.3.1 | INTEGER | read-only | mandatory |
| ePDU2DeviceConfigTable OBJECT-TYPE A table of Rack PDU configuration data. | 1.3.6.1.4.1.3808.1.1.6.3.2 | not-accessible | mandatory | |
| ePDU2DeviceConfigEntry OBJECT-TYPE Configuration data from Rack PDU being queried. | 1.3.6.1.4.1.3808.1.1.6.3.2.1 | not-accessible | mandatory | |
| ePDU2DeviceConfigIndex OBJECT-TYPE The index to the Rack PDU table entry. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.1 | INTEGER (1..4) | read-only | mandatory |
| ePDU2DeviceConfigModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.2 | INTEGER | read-only | mandatory |
| ePDU2DeviceConfigName OBJECT-TYPE A user-defined string identifying the name of Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.3 | DisplayString | read-write | mandatory |
| ePDU2DeviceConfigLocation OBJECT-TYPE A user-defined string identifying the location of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.4 | DisplayString | read-write | mandatory |
| ePDU2DeviceConfigContact OBJECT-TYPE A user-defined string identifying the person to contact of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.5 | DisplayString | read-write | mandatory |
| ePDU2DeviceConfigDisplayOrientation OBJECT-TYPE Getting this OID will return the intended physical orientation of the Seven-Segment Display. displayNormal(1) indicates Normal. displayReverse(2)indicates Upside-Down. displayRotate90(3) indicates rotate 90 degree. displayRotate270(4) indicates rotate 270 degree. displayAuto(5) indicates auto-detect and rotate. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.6 | INTEGER {displayNormal(1), displayReverse(2), displayRotate90(3), displayRotate270(4), displayAuto(5)} | read-write | mandatory |
| ePDU2DeviceConfigColdstartDelay OBJECT-TYPE The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes). | 1.3.6.1.4.1.3808.1.1.6.3.2.1.7 | INTEGER | read-write | mandatory |
| ePDU2DeviceConfigCurrentLowLoadThreshold OBJECT-TYPE User-defined low current draw alarm threshold, measured in Amps. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.8 | INTEGER | read-write | mandatory |
| ePDU2DeviceConfigCurrentNearOverloadThreshold OBJECT-TYPE User-defined near overload current threshold, measured in Amps. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.9 | INTEGER | read-write | mandatory |
| ePDU2DeviceConfigCurrentOverloadThreshold OBJECT-TYPE User-defined current overload threshold, measured in Amps. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.10 | INTEGER | read-write | mandatory |
| ePDU2DeviceConfigPeakLoadReset OBJECT-TYPE Setting this OID to resetAll (2) will cause the existing peak current value of Rack PDU and its outlets to be replaced by the current load current value. Setting this OID to resetDevice (3) to reset the Rack PDU only. Setting this OID to resetOutlets (4) to reset the PDU outlets only. Getting this OID will do nothing and return the noOperation(1) value. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.11 | INTEGER {noOperation(1), resetAll(2), resetDevice(3), resetOutlets(4)} | read-write | mandatory |
| ePDU2DeviceConfigEnergyReset OBJECT-TYPE Setting this OID to resetAll (2) will cause the device energy meter value to be reset to zero. Setting this OID to resetDevice (3) to reset the Rack PDU only. Setting this OID to resetOutlets (4) to reset the PDU outlets only. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.12 | INTEGER {noOperation(1), resetAll(2), resetDevice(3), resetOutlets(4)} | read-write | mandatory |
| ePDU2DeviceConfigPowerLowLoadThreshold OBJECT-TYPE User-defined low power draw alarm threshold, measured in Watts. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.13 | INTEGER | read-write | mandatory |
| ePDU2DeviceConfigPowerNearOverloadThreshold OBJECT-TYPE User-defined near overload power threshold, measured in Watts. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.14 | INTEGER | read-write | mandatory |
| ePDU2DeviceConfigPowerOverloadThreshold OBJECT-TYPE User-defined power overload threshold, measured in Watts. | 1.3.6.1.4.1.3808.1.1.6.3.2.1.15 | INTEGER | read-write | mandatory |
| ePDU2DeviceInfoTable OBJECT-TYPE A table of Rack PDU information. | 1.3.6.1.4.1.3808.1.1.6.3.3 | not-accessible | mandatory | |
| ePDU2DeviceInfoEntry OBJECT-TYPE Information of the Rack PDU being queried. | 1.3.6.1.4.1.3808.1.1.6.3.3.1 | not-accessible | mandatory | |
| ePDU2DeviceInfoIndex OBJECT-TYPE The index to the Rack PDU Information table entry. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.1 | INTEGER (1..4) | read-only | mandatory |
| ePDU2DeviceInfoModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.2 | INTEGER | read-only | mandatory |
| ePDU2DeviceInfoName OBJECT-TYPE A user-defined string identifying the name of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.3 | DisplayString | read-only | mandatory |
| ePDU2DeviceInfoRating OBJECT-TYPE The electrical rating of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.4 | INTEGER | read-only | mandatory |
| ePDU2DeviceInfoNumOutlets OBJECT-TYPE The number of outlets on the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.5 | INTEGER | read-only | mandatory |
| ePDU2DeviceInfoSwitchedOutlets OBJECT-TYPE The number of switched outlets on the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.6 | INTEGER | read-only | mandatory |
| ePDU2DeviceInfoMeteredOutlets OBJECT-TYPE The number of metered outlets on the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.7 | INTEGER | read-only | mandatory |
| ePDU2DeviceInfoNumPhases OBJECT-TYPE The number of phases present in the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.8 | INTEGER | read-only | mandatory |
| ePDU2DeviceInfoNumBreakers OBJECT-TYPE The number of metered banks present in the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.9 | INTEGER | read-only | mandatory |
| ePDU2DeviceInfoBreakerRating OBJECT-TYPE The maximum current rating, measured in Amps, for the Rack PDU. Getting this OID will return rating of the circuit breakers on the device if it has any. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.10 | INTEGER | read-only | mandatory |
| ePDU2DeviceInfoOrientation OBJECT-TYPE Rack PDU orientation. | 1.3.6.1.4.1.3808.1.1.6.3.3.1.11 | INTEGER {orientHorizontal(1), orientVertical(2)} | read-only | mandatory |
| ePDU2DeviceInfoOutletLayout OBJECT-TYPE Getting this OID will return outlet layout for the device. SeqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... SeqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... SeqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... SeqPhToPhGrouped(4) indicates outlet layout as follows: Otlts1-8::(3-1),Otlts9-16::(2-3),Otlts17-24::(1-2). | 1.3.6.1.4.1.3808.1.1.6.3.3.1.12 | INTEGER {seqPhaseToNeutral(1), seqPhaseToPhase(2), seqPhToNeu21PhToPh(3), seqPhToPhGrouped(4)} | read-only | mandatory |
| ePDU2DeviceStatusTable OBJECT-TYPE A table of Rack PDU current status. | 1.3.6.1.4.1.3808.1.1.6.3.4 | not-accessible | mandatory | |
| ePDU2DeviceStatusEntry OBJECT-TYPE Status data from the Rack PDU being queried. | 1.3.6.1.4.1.3808.1.1.6.3.4.1 | not-accessible | mandatory | |
| ePDU2DeviceStatusIndex OBJECT-TYPE The index to the Rack PDU status table entry. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.1 | INTEGER (1..4) | read-only | mandatory |
| ePDU2DeviceStatusModuleIndex OBJECT-TYPE The Rack PDU numeric ID | 1.3.6.1.4.1.3808.1.1.6.3.4.1.2 | INTEGER | read-only | mandatory |
| ePDU2DeviceStatusName OBJECT-TYPE A user-defined string identifying the name of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.3 | DisplayString | read-only | mandatory |
| ePDU2DeviceStatusLoadState OBJECT-TYPE Indicates the present load status of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.4 | INTEGER {noLoadAlarm(1), underCurrentAlarm(2), nearOverCurrentAlarm(3), overCurrentAlarm(4)} | read-only | mandatory |
| ePDU2DeviceStatusCurrentLoad OBJECT-TYPE The power consumption of the Rack PDU load in tenths of Amps. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.5 | Gauge | read-only | mandatory |
| ePDU2DeviceStatusCurrentPeakLoad OBJECT-TYPE The peak power consumption of the Rack PDU load in tenths of Amps. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.6 | Gauge | read-only | mandatory |
| ePDU2DeviceStatusPeakLoadTimestamp OBJECT-TYPE Indicates the date and time that peak load occurred. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.7 | DisplayString | read-only | mandatory |
| ePDU2DeviceStatusPeakLoadStartTime OBJECT-TYPE Indicates the date and time of the last device peak load reset. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.8 | DisplayString | read-only | mandatory |
| ePDU2DeviceStatusEnergy OBJECT-TYPE A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.9 | Gauge | read-only | mandatory |
| ePDU2DeviceStatusEnergyStartTime OBJECT-TYPE Indicates the date and time of the last device energy meter reset. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.10 | DisplayString | read-only | mandatory |
| ePDU2DeviceStatusCommandPending OBJECT-TYPE Indicates whether or not the device is processing a pending command. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.11 | INTEGER {commandPending(1), noCommandPending(2)} | read-only | mandatory |
| ePDU2DeviceStatusPowerSupplyAlarm OBJECT-TYPE Indicates a power supply alarm is active when value equals alarm (2). | 1.3.6.1.4.1.3808.1.1.6.3.4.1.12 | INTEGER {normal(1), alarm(2)} | read-only | mandatory |
| ePDU2DeviceStatusPowerSupply1Status OBJECT-TYPE Indicates whether or not an alarm is active in Power Supply 1. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.13 | INTEGER {normal(1), alarm(2)} | read-only | mandatory |
| ePDU2DeviceStatusPowerSupply2Status OBJECT-TYPE Indicates whether or not an alarm is active in Power Supply 2. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.14 | INTEGER {normal(1), alarm(2)} | read-only | mandatory |
| ePDU2DeviceStatusApparentPower OBJECT-TYPE The apparent power consumption of the Rack PDU load in VoltAmps (VA). | 1.3.6.1.4.1.3808.1.1.6.3.4.1.15 | Gauge | read-only | mandatory |
| ePDU2DeviceStatusPowerFactor OBJECT-TYPE The power factor of the Rack PDU load in hundredths. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.16 | Gauge | read-only | mandatory |
| ePDU2DeviceStatusRoleType OBJECT-TYPE Get this oid shows the role the PDU played on Daisy Chain Group. The PDU as a Host can access whole ePDU2 content, and the PDU be standalong or a Slave can access itself instead. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.17 | INTEGER {standalone(1), host(2), slave(3)} | read-only | mandatory |
| ePDU2DeviceStatusPowerLoad OBJECT-TYPE The power consumption of the Rack PDU load in Watts. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.18 | Gauge | read-only | mandatory |
| ePDU2DeviceStatusPowerPeakLoad OBJECT-TYPE The peak power consumption of the Rack PDU load in Watts. | 1.3.6.1.4.1.3808.1.1.6.3.4.1.19 | Gauge | read-only | mandatory |
| ePDU2DeviceControlTable OBJECT-TYPE A table of Rack PDU control data. | 1.3.6.1.4.1.3808.1.1.6.3.5 | not-accessible | mandatory | |
| ePDU2DeviceControlEntry OBJECT-TYPE Control data from Rack PDU being queried. | 1.3.6.1.4.1.3808.1.1.6.3.5.1 | not-accessible | mandatory | |
| ePDU2DeviceControlIndex OBJECT-TYPE The index to the Rack PDU control table entry. | 1.3.6.1.4.1.3808.1.1.6.3.5.1.1 | INTEGER (1..4) | read-only | mandatory |
| ePDU2DeviceControlModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.3.5.1.2 | INTEGER | read-only | mandatory |
| ePDU2DeviceControlName OBJECT-TYPE A user-defined string identifying the name of the Rack PDU. | 1.3.6.1.4.1.3808.1.1.6.3.5.1.3 | DisplayString | read-only | mandatory |
| ePDU2DeviceControlCommand OBJECT-TYPE Setting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to immediateAllOff (2) will turn all outlets off immediately. Setting this OID to immediateAllReboot (3) will cause an immediateAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the ePDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateAllOn command. Setting this OID to delayedAllOn (4) will turn all outlets on as defined by each outlet's ePDU2OutletSwitchedConfigPowerOnTime OID value. Setting this OID to delayedAllOff (5) will turn all outlets off as defined by each outlet's ePDU2OutletSwitchedConfigPowerOffTime OID value. Setting this OID to delayedAllReboot (6) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest ePDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to cancelAllPendingCommand (7) will cause all pending commands on the Switched Rack PDU to be cancelled. Setting this OID to noCommand (8) will have no effect. Getting this OID will return the noCommand (8) value. | 1.3.6.1.4.1.3808.1.1.6.3.5.1.4 | INTEGER {immediateAllOn(1), immediateAllOff(2), immediateAllReboot(3), delayedAllOn(4), delayedAllOff(5), delayedAllReboot(6), cancelAllPendingCommand(7), noCommand(8)} | read-write | mandatory |
| ePDU2Phase OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6.4 | |||
| ePDU2PhaseTableSize OBJECT-TYPE A Host Rack PDU response total phase number of Rack PDUs on daisy chain. Rack PDU as a Slave can only response itself number of phase. | 1.3.6.1.4.1.3808.1.1.6.4.1 | INTEGER | read-only | mandatory |
| ePDU2PhaseConfigTable OBJECT-TYPE A table of Rack PDU phase configuration data. | 1.3.6.1.4.1.3808.1.1.6.4.2 | not-accessible | mandatory | |
| ePDU2PhaseConfigEntry OBJECT-TYPE Configuration data from currently queried Rack PDU phase. | 1.3.6.1.4.1.3808.1.1.6.4.2.1 | not-accessible | mandatory | |
| ePDU2PhaseConfigIndex OBJECT-TYPE The index to the Rack PDU phase configuration table entry. | 1.3.6.1.4.1.3808.1.1.6.4.2.1.1 | INTEGER (1..12) | read-only | mandatory |
| ePDU2PhaseConfigModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.4.2.1.2 | INTEGER | read-only | mandatory |
| ePDU2PhaseConfigNumber OBJECT-TYPE The numeric phase ID. | 1.3.6.1.4.1.3808.1.1.6.4.2.1.3 | INTEGER | read-only | mandatory |
| ePDU2PhaseConfigOverloadRestriction OBJECT-TYPE This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the ePDU2PhaseConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the ePDU2PhaseConfigOverloadThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (-1). Attempts to set this OID in these models will fail. | 1.3.6.1.4.1.3808.1.1.6.4.2.1.4 | INTEGER {notSupported(-1), alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3)} | read-write | mandatory |
| ePDU2PhaseConfigLowLoadThreshold OBJECT-TYPE User-defined low load phase current threshold in Amps. | 1.3.6.1.4.1.3808.1.1.6.4.2.1.5 | INTEGER | read-write | mandatory |
| ePDU2PhaseConfigNearOverloadThreshold OBJECT-TYPE User-defined near phase overload current warning threshold in Amps. | 1.3.6.1.4.1.3808.1.1.6.4.2.1.6 | INTEGER | read-write | mandatory |
| ePDU2PhaseConfigOverloadThreshold OBJECT-TYPE User-defined phase overload current threshold in Amps | 1.3.6.1.4.1.3808.1.1.6.4.2.1.7 | INTEGER | read-write | mandatory |
| ePDU2PhaseConfigPhasePeakLoadReset OBJECT-TYPE Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value. | 1.3.6.1.4.1.3808.1.1.6.4.2.1.8 | INTEGER {noOperation(1), reset(2)} | read-write | mandatory |
| ePDU2PhaseInfoTable OBJECT-TYPE A table of Rack PDU phase information. | 1.3.6.1.4.1.3808.1.1.6.4.3 | not-accessible | mandatory | |
| ePDU2PhaseInfoEntry OBJECT-TYPE Information data from currently queried Rack PDU phase. | 1.3.6.1.4.1.3808.1.1.6.4.3.1 | not-accessible | mandatory | |
| ePDU2PhaseInfoIndex OBJECT-TYPE The index to the Rack PDU phase properties table entry. | 1.3.6.1.4.1.3808.1.1.6.4.3.1.1 | INTEGER (1..12) | read-only | mandatory |
| ePDU2PhaseInfoModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.4.3.1.2 | INTEGER | read-only | mandatory |
| ePDU2PhaseInfoNumber OBJECT-TYPE The numeric phase ID. | 1.3.6.1.4.1.3808.1.1.6.4.3.1.3 | INTEGER | read-only | mandatory |
| ePDU2PhaseStatusTable OBJECT-TYPE A table of Rack PDU phase status data | 1.3.6.1.4.1.3808.1.1.6.4.4 | not-accessible | mandatory | |
| ePDU2PhaseStatusEntry OBJECT-TYPE Status data from currently queried Rack PDU phase | 1.3.6.1.4.1.3808.1.1.6.4.4.1 | not-accessible | mandatory | |
| ePDU2PhaseStatusIndex OBJECT-TYPE The index to the Rack PDU phase status table entry. | 1.3.6.1.4.1.3808.1.1.6.4.4.1.1 | INTEGER (1..13) | read-only | mandatory |
| ePDU2PhaseStatusModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.4.4.1.2 | INTEGER | read-only | mandatory |
| ePDU2PhaseStatusNumber OBJECT-TYPE The numeric phase ID. | 1.3.6.1.4.1.3808.1.1.6.4.4.1.3 | INTEGER | read-only | mandatory |
| ePDU2PhaseStatusLoadState OBJECT-TYPE Indicates the present load status of the Rack PDU phase being queried. | 1.3.6.1.4.1.3808.1.1.6.4.4.1.4 | INTEGER {normal(1), lowLoad(2), nearOverload(3), overload(4)} | read-only | mandatory |
| ePDU2PhaseStatusLoad OBJECT-TYPE Indicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried. | 1.3.6.1.4.1.3808.1.1.6.4.4.1.5 | Gauge | read-only | mandatory |
| ePDU2PhaseStatusVoltage OBJECT-TYPE Indicates the Voltage, in tenths of Volts, of the Rack PDU phase being queried | 1.3.6.1.4.1.3808.1.1.6.4.4.1.6 | Gauge | read-only | mandatory |
| ePDU2PhaseStatusPower OBJECT-TYPE Indicates the load power, in watts, consumed on the Rack PDU phase being queried | 1.3.6.1.4.1.3808.1.1.6.4.4.1.7 | Gauge | read-only | mandatory |
| ePDU2PhaseStatusApparentPower OBJECT-TYPE Indicates the load apparent power, in VoltAmps (VA), consumed on the Rack PDU phase being queried | 1.3.6.1.4.1.3808.1.1.6.4.4.1.8 | Gauge | read-only | mandatory |
| ePDU2PhaseStatusPowerFactor OBJECT-TYPE Indicates the load power factor, in hundredths, of the Rack PDU phase being queried | 1.3.6.1.4.1.3808.1.1.6.4.4.1.9 | Gauge | read-only | mandatory |
| ePDU2PhaseStatusPeakLoad OBJECT-TYPE The peak current of the Rack PDU phase load in tenths of Amps | 1.3.6.1.4.1.3808.1.1.6.4.4.1.10 | Gauge | read-only | mandatory |
| ePDU2PhaseStatusPeakLoadTimestamp OBJECT-TYPE Indicates the date and time the phase peak current occurred. | 1.3.6.1.4.1.3808.1.1.6.4.4.1.11 | DisplayString | read-only | mandatory |
| ePDU2PhaseStatusPeakLoadStartTime OBJECT-TYPE Indicates the date and time of the last phase peak current reset. | 1.3.6.1.4.1.3808.1.1.6.4.4.1.12 | DisplayString | read-only | mandatory |
| ePDU2PhaseStatusLineToLineVoltage OBJECT-TYPE Indicates the Line to Line Voltage, in tenths of Volts, of the Rack PDU phase being queried | 1.3.6.1.4.1.3808.1.1.6.4.4.1.13 | Gauge | read-only | mandatory |
| ePDU2Bank OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6.5 | |||
| ePDU2BankTableSize OBJECT-TYPE A Host Rack PDU response total bank number of Rack PDUs on daisy chain. Rack PDU as a Slave can only response itself number of bank. | 1.3.6.1.4.1.3808.1.1.6.5.1 | INTEGER | read-only | mandatory |
| ePDU2BankConfigTable OBJECT-TYPE A table of Rack PDU bank configuration data. | 1.3.6.1.4.1.3808.1.1.6.5.2 | not-accessible | mandatory | |
| ePDU2BankConfigEntry OBJECT-TYPE Configuration data from currently queried Rack PDU bank. | 1.3.6.1.4.1.3808.1.1.6.5.2.1 | not-accessible | mandatory | |
| ePDU2BankConfigIndex OBJECT-TYPE The index to the Rack PDU bank configuration table entry. | 1.3.6.1.4.1.3808.1.1.6.5.2.1.1 | INTEGER (1..12) | read-only | mandatory |
| ePDU2BankConfigModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.5.2.1.2 | INTEGER | read-only | mandatory |
| ePDU2BankConfigNumber OBJECT-TYPE The numeric bank ID. | 1.3.6.1.4.1.3808.1.1.6.5.2.1.3 | INTEGER | read-only | mandatory |
| ePDU2BankConfigOverloadRestriction OBJECT-TYPE This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the ePDU2BankConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the ePDU2BankConfigOverloadThreshold OID is exceeded. | 1.3.6.1.4.1.3808.1.1.6.5.2.1.4 | INTEGER {alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3)} | read-write | mandatory |
| ePDU2BankConfigLowLoadThreshold OBJECT-TYPE User-defined low load bank current threshold in Amps. | 1.3.6.1.4.1.3808.1.1.6.5.2.1.5 | INTEGER | read-write | mandatory |
| ePDU2BankConfigNearOverloadThreshold OBJECT-TYPE User-defined near bank overload current warning threshold in Amps. | 1.3.6.1.4.1.3808.1.1.6.5.2.1.6 | INTEGER | read-write | mandatory |
| ePDU2BankConfigOverloadThreshold OBJECT-TYPE User-defined bank overload current threshold in Amps | 1.3.6.1.4.1.3808.1.1.6.5.2.1.7 | INTEGER | read-write | mandatory |
| ePDU2BankConfigPeakLoadReset OBJECT-TYPE Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value. | 1.3.6.1.4.1.3808.1.1.6.5.2.1.8 | INTEGER {noOperation(1), reset(2)} | read-write | mandatory |
| ePDU2BankInfoTable OBJECT-TYPE A table of Rack PDU bank information. | 1.3.6.1.4.1.3808.1.1.6.5.3 | not-accessible | mandatory | |
| ePDU2BankInfoEntry OBJECT-TYPE Information data from currently queried Rack PDU bank. | 1.3.6.1.4.1.3808.1.1.6.5.3.1 | not-accessible | mandatory | |
| ePDU2BankInfoIndex OBJECT-TYPE The index to the Rack PDU bank properties table entry. | 1.3.6.1.4.1.3808.1.1.6.5.3.1.1 | INTEGER (1..12) | read-only | mandatory |
| ePDU2BankInfoModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.5.3.1.2 | INTEGER | read-only | mandatory |
| ePDU2BankInfoNumber OBJECT-TYPE The numeric bank ID. | 1.3.6.1.4.1.3808.1.1.6.5.3.1.3 | INTEGER | read-only | mandatory |
| ePDU2BankStatusTable OBJECT-TYPE A table of Rack PDU bank status data | 1.3.6.1.4.1.3808.1.1.6.5.4 | not-accessible | mandatory | |
| ePDU2BankStatusEntry OBJECT-TYPE Status data from currently queried Rack PDU bank | 1.3.6.1.4.1.3808.1.1.6.5.4.1 | not-accessible | mandatory | |
| ePDU2BankStatusIndex OBJECT-TYPE The index to the Rack PDU bank status table entry. | 1.3.6.1.4.1.3808.1.1.6.5.4.1.1 | INTEGER (1..12) | read-only | mandatory |
| ePDU2BankStatusModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.5.4.1.2 | INTEGER | read-only | mandatory |
| ePDU2BankStatusNumber OBJECT-TYPE The numeric bank ID. | 1.3.6.1.4.1.3808.1.1.6.5.4.1.3 | INTEGER | read-only | mandatory |
| ePDU2BankStatusLoadState OBJECT-TYPE Indicates the present load status of the Rack PDU bank being queried. | 1.3.6.1.4.1.3808.1.1.6.5.4.1.4 | INTEGER {normal(1), lowLoad(2), nearOverload(3), overload(4)} | read-only | mandatory |
| ePDU2BankStatusLoad OBJECT-TYPE Indicates the current draw, in tenths of Amps, of the load on the Rack PDU bank being queried. | 1.3.6.1.4.1.3808.1.1.6.5.4.1.5 | Gauge | read-only | mandatory |
| ePDU2BankStatusPeakLoad OBJECT-TYPE The peak current of the Rack PDU bank load in tenths of Amps. | 1.3.6.1.4.1.3808.1.1.6.5.4.1.6 | Gauge | read-only | mandatory |
| ePDU2BankStatusPeakLoadTimestamp OBJECT-TYPE Indicates the date and time the bank peak current occurred. | 1.3.6.1.4.1.3808.1.1.6.5.4.1.7 | DisplayString | read-only | mandatory |
| ePDU2BankStatusPeakLoadStartTime OBJECT-TYPE Indicates the date and time of the last bank peak current reset. | 1.3.6.1.4.1.3808.1.1.6.5.4.1.8 | DisplayString | read-only | mandatory |
| ePDU2Outlet OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6.6 | |||
| ePDU2OutletSwitched OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6.6.1 | |||
| ePDU2OutletSwitchedTableSize OBJECT-TYPE The number of switched outlets on connected Rack PDUs. | 1.3.6.1.4.1.3808.1.1.6.6.1.1 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedConfigTable OBJECT-TYPE A table of Rack PDU switched outlet configuration data. | 1.3.6.1.4.1.3808.1.1.6.6.1.2 | not-accessible | mandatory | |
| ePDU2OutletSwitchedConfigEntry OBJECT-TYPE Configuration data from currently queried Rack PDU switched outlet. | 1.3.6.1.4.1.3808.1.1.6.6.1.2.1 | not-accessible | mandatory | |
| ePDU2OutletSwitchedConfigIndex OBJECT-TYPE The index to the Rack PDU switched outlet configuration table entry. | 1.3.6.1.4.1.3808.1.1.6.6.1.2.1.1 | INTEGER (1..96) | read-only | mandatory |
| ePDU2OutletSwitchedConfigModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.6.1.2.1.2 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedConfigNumber OBJECT-TYPE The numeric switched outlet ID. | 1.3.6.1.4.1.3808.1.1.6.6.1.2.1.3 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedConfigName OBJECT-TYPE The user-defined switched outlet name string. | 1.3.6.1.4.1.3808.1.1.6.6.1.2.1.4 | DisplayString | read-write | mandatory |
| ePDU2OutletSwitchedConfigPowerOnTime OBJECT-TYPE The amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 - never power on. 0 - power on immediately. 1 to 7200 - power on up to 7200 seconds after being commanded. | 1.3.6.1.4.1.3808.1.1.6.6.1.2.1.5 | INTEGER | read-write | mandatory |
| ePDU2OutletSwitchedConfigPowerOffTime OBJECT-TYPE The amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never power off. 0 - power off immediately. 1 to 7200 - power off up to 7200 seconds after being commanded. | 1.3.6.1.4.1.3808.1.1.6.6.1.2.1.6 | INTEGER | read-write | mandatory |
| ePDU2OutletSwitchedConfigRebootDuration OBJECT-TYPE During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed range is any value between 5 and 60 seconds (1 minute). | 1.3.6.1.4.1.3808.1.1.6.6.1.2.1.7 | INTEGER | read-write | mandatory |
| ePDU2OutletSwitchedInfoTable OBJECT-TYPE A table of Rack PDU switched outlet information. | 1.3.6.1.4.1.3808.1.1.6.6.1.3 | not-accessible | mandatory | |
| ePDU2OutletSwitchedInfoEntry OBJECT-TYPE Information of the currently queried Rack PDU switched outlet. | 1.3.6.1.4.1.3808.1.1.6.6.1.3.1 | not-accessible | mandatory | |
| ePDU2OutletSwitchedInfoIndex OBJECT-TYPE The index to the Rack PDU switched outlet information table entry. | 1.3.6.1.4.1.3808.1.1.6.6.1.3.1.1 | INTEGER (1..96) | read-only | mandatory |
| ePDU2OutletSwitchedInfoModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.6.1.3.1.2 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedInfoNumber OBJECT-TYPE The numeric switched outlet ID. | 1.3.6.1.4.1.3808.1.1.6.6.1.3.1.3 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedInfoName OBJECT-TYPE The numeric switched outlet name. | 1.3.6.1.4.1.3808.1.1.6.6.1.3.1.4 | DisplayString | read-only | mandatory |
| ePDU2OutletSwitchedInfoPhaseLayout OBJECT-TYPE This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that the outlet is wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that the outlet is wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that the outlet is wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that the outlet is wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that the outlet is wired from Phase 3 to Phase 1. | 1.3.6.1.4.1.3808.1.1.6.6.1.3.1.5 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedInfoBank OBJECT-TYPE The numeric bank ID. | 1.3.6.1.4.1.3808.1.1.6.6.1.3.1.6 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedStatusTable OBJECT-TYPE A table of Rack PDU switched outlet status information. | 1.3.6.1.4.1.3808.1.1.6.6.1.4 | not-accessible | mandatory | |
| ePDU2OutletSwitchedStatusEntry OBJECT-TYPE Status information for currently queried Rack PDU switched outlet. | 1.3.6.1.4.1.3808.1.1.6.6.1.4.1 | not-accessible | mandatory | |
| ePDU2OutletSwitchedStatusIndex OBJECT-TYPE The index to the Rack PDU switched outlet status information table entry. | 1.3.6.1.4.1.3808.1.1.6.6.1.4.1.1 | INTEGER (1..96) | read-only | mandatory |
| ePDU2OutletSwitchedStatusModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.6.1.4.1.2 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedStatusNumber OBJECT-TYPE The numeric switched outlet ID. | 1.3.6.1.4.1.3808.1.1.6.6.1.4.1.3 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedStatusName OBJECT-TYPE The user-defined switched outlet name string. | 1.3.6.1.4.1.3808.1.1.6.6.1.4.1.4 | DisplayString | read-only | mandatory |
| ePDU2OutletSwitchedStatusState OBJECT-TYPE Indicates the present switch state of the Rack PDU switched outlet being queried. | 1.3.6.1.4.1.3808.1.1.6.6.1.4.1.5 | INTEGER {outletStatusOn(1), outletStatusOff(2)} | read-only | mandatory |
| ePDU2OutletSwitchedStatusCommandPending OBJECT-TYPE Getting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusNoCommandPending (2) will be returned. | 1.3.6.1.4.1.3808.1.1.6.6.1.4.1.6 | INTEGER {outletStatusCommandPending(1), outletStatusNoCommandPending(2)} | read-only | mandatory |
| ePDU2OutletSwitchedControlTable OBJECT-TYPE A table of Rack PDU switched outlet control data. | 1.3.6.1.4.1.3808.1.1.6.6.1.5 | not-accessible | mandatory | |
| ePDU2OutletSwitchedControlEntry OBJECT-TYPE Control data for currently queried Rack PDU switched outlet. | 1.3.6.1.4.1.3808.1.1.6.6.1.5.1 | not-accessible | mandatory | |
| ePDU2OutletSwitchedControlIndex OBJECT-TYPE The index to the Rack PDU switched outlet control data table entry. | 1.3.6.1.4.1.3808.1.1.6.6.1.5.1.1 | INTEGER (1..96) | read-only | mandatory |
| ePDU2OutletSwitchedControlModuleIndex OBJECT-TYPE The user-defined Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.6.1.5.1.2 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedControlNumber OBJECT-TYPE The numeric switched outlet ID. | 1.3.6.1.4.1.3808.1.1.6.6.1.5.1.3 | INTEGER | read-only | mandatory |
| ePDU2OutletSwitchedControlName OBJECT-TYPE The user-defined switched outlet name string. | 1.3.6.1.4.1.3808.1.1.6.6.1.5.1.4 | DisplayString | read-only | mandatory |
| ePDU2OutletSwitchedControlCommand OBJECT-TYPE Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will immediately reboot the outlet. Setting this variable to delayedOn (4) will turn the outlet on after the ePDUOutletConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (5) will turn the outlet off after the ePDUOutletConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched Rack PDU to perform a delayedOff command, wait the ePDUOutletConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (7) will cause any pending command to this outlet to be canceled. Setting this variable to outletIdentify (8) will cause PDU LED to display the number of the outlet. | 1.3.6.1.4.1.3808.1.1.6.6.1.5.1.5 | INTEGER {immediateOn(1), immediateOff(2), immediateReboot(3), delayedOn(4), delayedOff(5), delayedReboot(6), cancelPendingCommand(7), outletIdentify(8)} | read-write | mandatory |
| ePDU2OutletMetered OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6.6.2 | |||
| ePDU2OutletMeteredTableSize OBJECT-TYPE The number of metered outlets on connected Rack PDUs. | 1.3.6.1.4.1.3808.1.1.6.6.2.1 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredConfigTable OBJECT-TYPE A table of Rack PDU metered outlet configuration data. | 1.3.6.1.4.1.3808.1.1.6.6.2.2 | not-accessible | mandatory | |
| ePDU2OutletMeteredConfigEntry OBJECT-TYPE Configuration data from currently queried Rack PDU metered outlet. | 1.3.6.1.4.1.3808.1.1.6.6.2.2.1 | not-accessible | mandatory | |
| ePDU2OutletMeteredConfigIndex OBJECT-TYPE The index to the Rack PDU metered outlet configuration table entry. | 1.3.6.1.4.1.3808.1.1.6.6.2.2.1.1 | INTEGER (1..96) | read-only | mandatory |
| ePDU2OutletMeteredConfigModuleIndex OBJECT-TYPE The user-defined Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.6.2.2.1.2 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredConfigNumber OBJECT-TYPE The numeric metered outlet ID. | 1.3.6.1.4.1.3808.1.1.6.6.2.2.1.3 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredConfigName OBJECT-TYPE The user-defined metered outlet name string. | 1.3.6.1.4.1.3808.1.1.6.6.2.2.1.4 | DisplayString | read-write | mandatory |
| ePDU2OutletMeteredConfigLowLoadThreshold OBJECT-TYPE User-defined outlet low load current threshold in Watts. | 1.3.6.1.4.1.3808.1.1.6.6.2.2.1.5 | INTEGER | read-write | mandatory |
| ePDU2OutletMeteredConfigNearOverloadThreshold OBJECT-TYPE User-defined outlet near overload warning threshold in Watts. | 1.3.6.1.4.1.3808.1.1.6.6.2.2.1.6 | INTEGER | read-write | mandatory |
| ePDU2OutletMeteredConfigOverloadThreshold OBJECT-TYPE User-defined outlet overload current threshold in Watts. | 1.3.6.1.4.1.3808.1.1.6.6.2.2.1.7 | INTEGER | read-write | mandatory |
| ePDU2OutletMeteredInfoTable OBJECT-TYPE A table of Rack PDU metered outlet information. | 1.3.6.1.4.1.3808.1.1.6.6.2.3 | not-accessible | mandatory | |
| ePDU2OutletMeteredInfoEntry OBJECT-TYPE Information of currently queried Rack PDU metered outlet. | 1.3.6.1.4.1.3808.1.1.6.6.2.3.1 | not-accessible | mandatory | |
| ePDU2OutletMeteredInfoIndex OBJECT-TYPE The index to the Rack PDU metered information table entry. | 1.3.6.1.4.1.3808.1.1.6.6.2.3.1.1 | INTEGER (1..96) | read-only | mandatory |
| ePDU2OutletMeteredInfoModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.6.2.3.1.2 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredInfoNumber OBJECT-TYPE The numeric metered outlet ID. | 1.3.6.1.4.1.3808.1.1.6.6.2.3.1.3 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredInfoName OBJECT-TYPE The user-defined metered outlet name string. | 1.3.6.1.4.1.3808.1.1.6.6.2.3.1.4 | DisplayString | read-only | mandatory |
| ePDU2OutletMeteredInfoLayout OBJECT-TYPE This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that the outlet is wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that the outlet is wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that the outlet is wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that the outlet is wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that the outlet is wired from Phase 3 to Phase 1. | 1.3.6.1.4.1.3808.1.1.6.6.2.3.1.5 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredInfoRating OBJECT-TYPE Maximum power rating of Rack PDU metered outlet. | 1.3.6.1.4.1.3808.1.1.6.6.2.3.1.6 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredInfoBank OBJECT-TYPE This outlet's numeric bank ID. | 1.3.6.1.4.1.3808.1.1.6.6.2.3.1.7 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredStatusTable OBJECT-TYPE A table of Rack PDU metered outlet status data. | 1.3.6.1.4.1.3808.1.1.6.6.2.4 | not-accessible | mandatory | |
| ePDU2OutletMeteredStatusEntry OBJECT-TYPE Status data from currently queried Rack PDU metered outlet. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1 | not-accessible | mandatory | |
| ePDU2OutletMeteredStatusIndex OBJECT-TYPE The index to the Rack PDU metered status table entry. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.1 | INTEGER (1..96) | read-only | mandatory |
| ePDU2OutletMeteredStatusModuleIndex OBJECT-TYPE The Rack PDU numeric ID. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.2 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredStatusNumber OBJECT-TYPE The numeric metered outlet ID. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.3 | INTEGER | read-only | mandatory |
| ePDU2OutletMeteredStatusName OBJECT-TYPE The user-defined metered outlet name string. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.4 | DisplayString | read-only | mandatory |
| ePDU2OutletMeteredStatusAlarm OBJECT-TYPE Getting this OID will return the current outlet alarm. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.5 | INTEGER {noLoadAlarm(1), underCurrentAlarm(2), nearOverCurrentAlarm(3), overCurrentAlarm(4)} | read-only | mandatory |
| ePDU2OutletMeteredStatusLoad OBJECT-TYPE Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in tenths of Amps. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.6 | Gauge | read-only | mandatory |
| ePDU2OutletMeteredStatusActivePower OBJECT-TYPE Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in watts. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.7 | Gauge | read-only | mandatory |
| ePDU2OutletMeteredStatusPeakPower OBJECT-TYPE The peak power consumption of the Rack PDU load in watts. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.8 | Gauge | read-only | mandatory |
| ePDU2OutletMeteredStatusPeakPowerTimestamp OBJECT-TYPE Get this oid shows the date and time that peak power consumption occurred. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.9 | DisplayString | read-only | mandatory |
| ePDU2OutletMeteredStatusPeakPowerStartTime OBJECT-TYPE Get this oid shows the date and time that peak power consumption started. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.10 | DisplayString | read-only | mandatory |
| ePDU2OutletMeteredStatusEnergy OBJECT-TYPE Energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.11 | Gauge | read-only | mandatory |
| ePDU2OutletMeteredStatusEnergyStart OBJECT-TYPE Indicates the date and time of the last device energy meter reset. | 1.3.6.1.4.1.3808.1.1.6.6.2.4.1.12 | DisplayString | read-only | mandatory |
| ePDU2Sensor OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6.7 | |||
| ePDU2SensorTableSize OBJECT-TYPE ePDU2SensorTableSize | 1.3.6.1.4.1.3808.1.1.6.7.1 | INTEGER | read-only | mandatory |
| ePDU2Group OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.6.8 | |||
| ePDU2GroupNumberOfDevices OBJECT-TYPE Getting this OID will return the number of Rack PDU devices contributing to the Daisy Chain group power and energy values. Queries to slave units in an Daisy Chain group will return 0. | 1.3.6.1.4.1.3808.1.1.6.8.1 | INTEGER | read-only | mandatory |
| ePDU2GroupTotalPower OBJECT-TYPE Getting this OID will return the total power consumption of the Rack PDU Daisy Chain group devices in watts. Queries to slave units in an Daisy Chain group will return 0. | 1.3.6.1.4.1.3808.1.1.6.8.2 | Gauge | read-only | mandatory |
| ePDU2GroupTotalEnergy OBJECT-TYPE Getting this OID will return the total energy consumption of the Rack PDU Daisy Chain group devices in tenths of kilowatt-hours. To reset the energy meters for each of the Rack PDU devices that contribute to this value, see the ePDU2GroupEnergyReset OID. To view the start time for each of the Rack PDU device energy meters that contribute to this value, see the ePDU2DeviceStatusEnergyStartTime OID. Queries to slave units in an Daisy Chain group will return 0. | 1.3.6.1.4.1.3808.1.1.6.8.3 | Gauge | read-only | mandatory |
| ePDU2GroupEnergyReset OBJECT-TYPE Setting this OID to reset (2) will cause the device energy meter value on each device in the Rack PDU Daisy Chain group to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. | 1.3.6.1.4.1.3808.1.1.6.8.4 | INTEGER {noOperation(1), reset(2)} | read-write | mandatory |
| ePDU2GroupPeakRecordReset OBJECT-TYPE Setting this OID to reset (2) will cause the device peak record value on each device in the Rack PDU Daisy Chain group to be reset to current load/power. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. | 1.3.6.1.4.1.3808.1.1.6.8.5 | INTEGER {noOperation(1), reset(2)} | read-write | mandatory |
| battmgr OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.7 | |||
| bmIdent OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.7.1 | |||
| bmIdentModelName OBJECT-TYPE Battery manager model name. | 1.3.6.1.4.1.3808.1.1.7.1.1 | DisplayString | read-only | mandatory |
| bmIdentHardwareRev OBJECT-TYPE Battery manager hardware version. | 1.3.6.1.4.1.3808.1.1.7.1.2 | DisplayString | read-only | mandatory |
| bmIdentFirmwareRev OBJECT-TYPE Battery manager firmware version. | 1.3.6.1.4.1.3808.1.1.7.1.3 | DisplayString | read-only | mandatory |
| bmIdentLCDHardwareRev OBJECT-TYPE Battery manager LCD hardware version. | 1.3.6.1.4.1.3808.1.1.7.1.4 | DisplayString | read-only | mandatory |
| bmIdentLCDFirmwareRev OBJECT-TYPE Battery manager LCD firmware version. | 1.3.6.1.4.1.3808.1.1.7.1.5 | DisplayString | read-only | mandatory |
| bmIdentDateOfManufacture OBJECT-TYPE Battery manager manufacture date. | 1.3.6.1.4.1.3808.1.1.7.1.6 | DisplayString | read-only | mandatory |
| bmIdentSerialNumber OBJECT-TYPE Battery manager serial number. | 1.3.6.1.4.1.3808.1.1.7.1.7 | DisplayString | read-only | mandatory |
| bmIdentName OBJECT-TYPE Battery manager system identification name. | 1.3.6.1.4.1.3808.1.1.7.1.8 | DisplayString | read-write | mandatory |
| bmIdentLocation OBJECT-TYPE Battery manager system location. | 1.3.6.1.4.1.3808.1.1.7.1.9 | DisplayString | read-write | mandatory |
| bmProperty OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.7.2 | |||
| bmPropertyStringMax OBJECT-TYPE Battery manager max string count supported. | 1.3.6.1.4.1.3808.1.1.7.2.1 | INTEGER | read-only | mandatory |
| bmPropertyMaxProbeOnString OBJECT-TYPE Battery manager max probes on a string supported. | 1.3.6.1.4.1.3808.1.1.7.2.2 | INTEGER | read-only | mandatory |
| bmPropertyInputVoltageRange OBJECT-TYPE Battery manager line input voltage range. | 1.3.6.1.4.1.3808.1.1.7.2.3 | DisplayString | read-only | mandatory |
| bmPropertyProbesRating OBJECT-TYPE Battery probes model rating. | 1.3.6.1.4.1.3808.1.1.7.2.4 | INTEGER {probeUnknown(1), probe2V(2), probe4V(3), probe6V(4), probe12V(5), probeMixed(6)} | read-only | mandatory |
| bmConfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.7.3 | |||
| bmConfigBattAH OBJECT-TYPE Battery manager battery AH type configuration, unit in 0.1 AH. | 1.3.6.1.4.1.3808.1.1.7.3.1 | INTEGER | read-write | mandatory |
| bmConfigStringCount OBJECT-TYPE Battery manager string count setting. | 1.3.6.1.4.1.3808.1.1.7.3.2 | INTEGER | read-write | mandatory |
| bmConfigProbesCountOnString OBJECT-TYPE Battery manager probe count on a string setting. | 1.3.6.1.4.1.3808.1.1.7.3.3 | INTEGER | read-write | mandatory |
| bmConfigLowVoltAlarmThreshold OBJECT-TYPE Battery low voltage alarm threshold setting, unit in 0.1 volt. | 1.3.6.1.4.1.3808.1.1.7.3.4 | INTEGER | read-write | mandatory |
| bmConfigHighVoltAlarmThreshold OBJECT-TYPE Battery high voltage alarm threshold setting, unit in 0.1 volt. | 1.3.6.1.4.1.3808.1.1.7.3.5 | INTEGER | read-write | mandatory |
| bmConfigVoltDiffAlarmThreshold OBJECT-TYPE Batteries within a string voltage difference threshold, unit in 0.1 volt. | 1.3.6.1.4.1.3808.1.1.7.3.6 | INTEGER | read-write | mandatory |
| bmConfigLowTempAlarmThreshold OBJECT-TYPE Battery low temperature alarm threshold, unit in 0.1 degree C. | 1.3.6.1.4.1.3808.1.1.7.3.7 | INTEGER | read-write | mandatory |
| bmConfigHighTempAlarmThreshold OBJECT-TYPE Battery high temperature alarm threshold, unit in 0.1 degree C. | 1.3.6.1.4.1.3808.1.1.7.3.8 | INTEGER | read-write | mandatory |
| bmConfigLowResAlarmThreshold OBJECT-TYPE Battery low resistance alarm threshold, unit in 0.01 mOhm. | 1.3.6.1.4.1.3808.1.1.7.3.9 | INTEGER | read-write | mandatory |
| bmConfigHighResAlarmThreshold OBJECT-TYPE Battery high resistance alarm threshold, unit in 0.01 mOhm. | 1.3.6.1.4.1.3808.1.1.7.3.10 | INTEGER | read-write | mandatory |
| bmConfigLowResWarnThreshold OBJECT-TYPE Battery low resistance warning threshold, unit in 0.01 mOhm. | 1.3.6.1.4.1.3808.1.1.7.3.11 | INTEGER | read-write | mandatory |
| bmConfigHighResWarnThreshold OBJECT-TYPE Battery high resistance warning threshold, unit in 0.01 mOhm. | 1.3.6.1.4.1.3808.1.1.7.3.12 | INTEGER | read-write | mandatory |
| bmConfigResHealthAlarmThreshold OBJECT-TYPE Battery resistance health alarm threshold, unit in percentage and should larger than 100. | 1.3.6.1.4.1.3808.1.1.7.3.13 | INTEGER | read-write | mandatory |
| bmConfigResHealthWarnThreshold OBJECT-TYPE Battery resistance health warn threshold, unit in percentage and should larger than 100. | 1.3.6.1.4.1.3808.1.1.7.3.14 | INTEGER | read-write | mandatory |
| bmConfigLowVoltAlarmThreshold10mV OBJECT-TYPE Battery low voltage alarm threshold setting, unit in 10 mV (0.01 volt). | 1.3.6.1.4.1.3808.1.1.7.3.15 | INTEGER | read-write | mandatory |
| bmConfigHighVoltAlarmThreshold10mV OBJECT-TYPE Battery high voltage alarm threshold setting, unit in 10 mV (0.01 volt). | 1.3.6.1.4.1.3808.1.1.7.3.16 | INTEGER | read-write | mandatory |
| bmConfigMergeFeature OBJECT-TYPE String merge feature setting. | 1.3.6.1.4.1.3808.1.1.7.3.17 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| bmControl OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.7.4 | |||
| bmControlSysytemIdenticator OBJECT-TYPE Battery manager will perform a panel indicator test when the variable is set to testIndicators(2). Get this oid will get noTestIndicators(1). | 1.3.6.1.4.1.3808.1.1.7.4.1 | INTEGER {noTestIndicators(1), testIndicators(2)} | read-write | mandatory |
| bmControlProbeIndicator OBJECT-TYPE Battery manager will perform a probe indicator test when the variable is set to testIndicators(2). Get this oid will get noTestIndicators(1). | 1.3.6.1.4.1.3808.1.1.7.4.2 | INTEGER {noTestIndicators(1), testIndicators(2)} | read-write | mandatory |
| bmProbes OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.7.5 | |||
| bmProbesNum OBJECT-TYPE Current connected probe number. | 1.3.6.1.4.1.3808.1.1.7.5.1 | INTEGER | read-only | mandatory |
| bmProbesTableSize OBJECT-TYPE Current configured probe number. | 1.3.6.1.4.1.3808.1.1.7.5.2 | INTEGER | read-only | mandatory |
| bmProbesTable OBJECT-TYPE Allows for getting of status of probes. | 1.3.6.1.4.1.3808.1.1.7.5.3 | not-accessible | mandatory | |
| bmProbesEntry OBJECT-TYPE The status of probes installation to gather status from. | 1.3.6.1.4.1.3808.1.1.7.5.3.1 | not-accessible | mandatory | |
| bmProbesIndex OBJECT-TYPE Probes table index | 1.3.6.1.4.1.3808.1.1.7.5.3.1.1 | INTEGER (1..960) | read-only | mandatory |
| bmProbesPackIndex OBJECT-TYPE The battery pack number the probe installed. | 1.3.6.1.4.1.3808.1.1.7.5.3.1.2 | INTEGER (1..64) | read-only | mandatory |
| bmProbesStringIndex OBJECT-TYPE The string number the probe installed. | 1.3.6.1.4.1.3808.1.1.7.5.3.1.3 | INTEGER (1..16) | read-only | mandatory |
| bmProbesBattIndex OBJECT-TYPE The battery number the probe installed. | 1.3.6.1.4.1.3808.1.1.7.5.3.1.4 | INTEGER (1..960) | read-only | mandatory |
| bmProbesVoltageTableSize OBJECT-TYPE The size of the battery voltage table | 1.3.6.1.4.1.3808.1.1.7.5.4 | INTEGER | read-only | mandatory |
| bmProbesVoltageTable OBJECT-TYPE Allows for getting of voltage of batteries. | 1.3.6.1.4.1.3808.1.1.7.5.5 | not-accessible | mandatory | |
| bmProbesVoltageEntry OBJECT-TYPE Batteries voltage status. | 1.3.6.1.4.1.3808.1.1.7.5.5.1 | not-accessible | mandatory | |
| bmProbesVoltageIndex OBJECT-TYPE The index of the voltage status entry. | 1.3.6.1.4.1.3808.1.1.7.5.5.1.1 | INTEGER (1..960) | read-only | mandatory |
| bmProbesVoltagePackIndex OBJECT-TYPE The battery pack index to the voltage record. | 1.3.6.1.4.1.3808.1.1.7.5.5.1.2 | INTEGER (1..64) | read-only | mandatory |
| bmProbesVoltageStringIndex OBJECT-TYPE The battery string index to the voltage record. | 1.3.6.1.4.1.3808.1.1.7.5.5.1.3 | INTEGER (1..16) | read-only | mandatory |
| bmProbesVoltageBattIndex OBJECT-TYPE The battery index to the voltage record within its string. | 1.3.6.1.4.1.3808.1.1.7.5.5.1.4 | INTEGER (1..960) | read-only | mandatory |
| bmProbesVoltageProbeIndex OBJECT-TYPE The probe index to the voltage record. | 1.3.6.1.4.1.3808.1.1.7.5.5.1.5 | INTEGER (1..960) | read-only | mandatory |
| bmProbesVoltageAlarmStatus OBJECT-TYPE The battery voltage alarm status. | 1.3.6.1.4.1.3808.1.1.7.5.5.1.6 | INTEGER {voltageNormal(1), voltageWarnLow(2), voltageWarnHigh(3), voltageAlarmLow(4), voltageAlarmHigh(5)} | read-only | mandatory |
| bmProbesVoltage OBJECT-TYPE Getting this oid to get battery voltage, unit in 10mV (0.01 volt). | 1.3.6.1.4.1.3808.1.1.7.5.5.1.7 | INTEGER | read-only | mandatory |
| bmProbesVoltageEqualPercentage OBJECT-TYPE Getting this oid to get battery voltage equalizing power, unit in percentage. | 1.3.6.1.4.1.3808.1.1.7.5.5.1.8 | INTEGER | read-only | mandatory |
| bmProbesTempTableSize OBJECT-TYPE The size of the Temperature table | 1.3.6.1.4.1.3808.1.1.7.5.6 | INTEGER | read-only | mandatory |
| bmProbesTempTable OBJECT-TYPE Allows for getting of temperature of probes. | 1.3.6.1.4.1.3808.1.1.7.5.7 | not-accessible | mandatory | |
| bmProbesTempEntry OBJECT-TYPE Temperature status entry. | 1.3.6.1.4.1.3808.1.1.7.5.7.1 | not-accessible | mandatory | |
| bmProbesTempIndex OBJECT-TYPE The index of the temperature entry. | 1.3.6.1.4.1.3808.1.1.7.5.7.1.1 | INTEGER (1..960) | read-only | mandatory |
| bmProbesTempPackIndex OBJECT-TYPE The battery pack index of the temperature entry. | 1.3.6.1.4.1.3808.1.1.7.5.7.1.2 | INTEGER (1..64) | read-only | mandatory |
| bmProbesTempStringIndex OBJECT-TYPE The index to the string. | 1.3.6.1.4.1.3808.1.1.7.5.7.1.3 | INTEGER (1..16) | read-only | mandatory |
| bmProbesTempBattIndex OBJECT-TYPE The index to the battery. | 1.3.6.1.4.1.3808.1.1.7.5.7.1.4 | INTEGER (1..960) | read-only | mandatory |
| bmProbesTempProbeIndex OBJECT-TYPE The index to the probe. | 1.3.6.1.4.1.3808.1.1.7.5.7.1.5 | INTEGER (1..960) | read-only | mandatory |
| bmProbesTempAlarmStatus OBJECT-TYPE The alarm status of the temperature. | 1.3.6.1.4.1.3808.1.1.7.5.7.1.6 | INTEGER {temperatureNormal(1), temperatureWarnLow(2), temperatureWarnHigh(3), temperatureAlarmLow(4), temperatureAlarmHigh(5)} | read-only | mandatory |
| bmProbesTemperature OBJECT-TYPE The temperature record, measure in 0.1 degree C. | 1.3.6.1.4.1.3808.1.1.7.5.7.1.7 | INTEGER (-40..60) | read-only | mandatory |
| bmProbesResTableSize OBJECT-TYPE The size of the Resistance table | 1.3.6.1.4.1.3808.1.1.7.5.8 | INTEGER | read-only | mandatory |
| bmProbesResTable OBJECT-TYPE Allows for getting of resistance of probes. | 1.3.6.1.4.1.3808.1.1.7.5.9 | not-accessible | mandatory | |
| bmProbesResEntry OBJECT-TYPE The resistance status entry. | 1.3.6.1.4.1.3808.1.1.7.5.9.1 | not-accessible | mandatory | |
| bmProbesResIndex OBJECT-TYPE The index of the resistance entry. | 1.3.6.1.4.1.3808.1.1.7.5.9.1.1 | INTEGER (1..960) | read-only | mandatory |
| bmProbesResPackIndex OBJECT-TYPE The battery pack index to the resistance entry. | 1.3.6.1.4.1.3808.1.1.7.5.9.1.2 | INTEGER (1..64) | read-only | mandatory |
| bmProbesResStringIndex OBJECT-TYPE The index to the string. | 1.3.6.1.4.1.3808.1.1.7.5.9.1.3 | INTEGER (1..16) | read-only | mandatory |
| bmProbesResBattIndex OBJECT-TYPE The index to the battery. | 1.3.6.1.4.1.3808.1.1.7.5.9.1.4 | INTEGER (1..960) | read-only | mandatory |
| bmProbesResProbeIndex OBJECT-TYPE The index to the probe. | 1.3.6.1.4.1.3808.1.1.7.5.9.1.5 | INTEGER (1..960) | read-only | mandatory |
| bmProbesResAlarmStatus OBJECT-TYPE The alarm status of the battery resistance. | 1.3.6.1.4.1.3808.1.1.7.5.9.1.6 | INTEGER {resistanceNormal(1), resistanceWarnLow(2), resistanceWarnHigh(3), resistanceAlarmLow(4), resistanceAlarmHigh(5)} | read-only | mandatory |
| bmProbesResistance OBJECT-TYPE The resistance of the battery, unit in 0.01 mOhm. | 1.3.6.1.4.1.3808.1.1.7.5.9.1.7 | INTEGER (-40..60) | read-only | mandatory |
| bmProbesResHealth OBJECT-TYPE The resistance health status, unit in percentage. | 1.3.6.1.4.1.3808.1.1.7.5.9.1.8 | INTEGER (-40..60) | read-only | mandatory |
| bmFuncRes OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.7.6 | |||
| bmFuncResMeasure OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.7.6.1 | |||
| bmFuncResMeasureInterval OBJECT-TYPE The time interval for battery manager to exercising resistance measurement, unit in hour(s). | 1.3.6.1.4.1.3808.1.1.7.6.1.1 | INTEGER | read-write | mandatory |
| bmFuncResMeasureManualCmd OBJECT-TYPE This oid allows user to manual resistance measurement. Set this oid to measureResNow(2) to measure resistance immediately. Get bmFuncResMeasureLastCmdResult oid to check command acceptance. | 1.3.6.1.4.1.3808.1.1.7.6.1.2 | INTEGER {noResMeasure(1), resMeasureNow(2)} | read-write | mandatory |
| bmFuncResMeasureManualResult OBJECT-TYPE Get this oid to confirm the last manual command result. | 1.3.6.1.4.1.3808.1.1.7.6.1.3 | INTEGER {resNoManualResult(1), resManualProcessing(2), resManualComplete(3), resManualReject(9)} | read-only | mandatory |
| bmFuncResMeasureLastUpdate OBJECT-TYPE When resistance measurement complete either by auto or manual, this oid will update to the last update time. | 1.3.6.1.4.1.3808.1.1.7.6.1.4 | DisplayString | read-only | mandatory |
| bmFuncEqual OBJECT-IDENTITY | 1.3.6.1.4.1.3808.1.1.7.7 | |||
| bmFuncEqualEnable OBJECT-TYPE Battery voltage equalization configuration. | 1.3.6.1.4.1.3808.1.1.7.7.1 | INTEGER {enable(1), disable(2)} | read-write | mandatory |
| bmFuncEqualActiveCond OBJECT-TYPE Volatge equalization will active when the voltage difference larger than this value, unit in 10mV. | 1.3.6.1.4.1.3808.1.1.7.7.2 | INTEGER | read-write | mandatory |
| bmFuncEqualStatus OBJECT-TYPE This oid shows the current equalization status. | 1.3.6.1.4.1.3808.1.1.7.7.3 | INTEGER {equalActive(1), equalFailed(2), equalNotActive(3), equalNotSupport(9)} | read-only | mandatory |
| bmFuncEqualStartTime OBJECT-TYPE This oid shows the last equalization start time. | 1.3.6.1.4.1.3808.1.1.7.7.4 | DisplayString | read-only | mandatory |
| bmFuncEqualElapseTime OBJECT-TYPE This oid shows the elapsed time since last equalization started. | 1.3.6.1.4.1.3808.1.1.7.7.5 | TimeTicks | read-only | mandatory |
| cpsmgmt OBJECT-IDENTITY | 1.3.6.1.4.1.3808.2 | |||
| mconfig OBJECT-IDENTITY | 1.3.6.1.4.1.3808.2.1 | |||
| mconfigNumTrapAccepters OBJECT-TYPE The number of receivers to send traps to. | 1.3.6.1.4.1.3808.2.1.1 | INTEGER | read-only | mandatory |
| mconfigTrapAccepterTable OBJECT-TYPE A list of receivers to send traps to. The numbers of entries are given by the value of mconfigNumTrapAccepters. | 1.3.6.1.4.1.3808.2.1.2 | not-accessible | mandatory | |
| mconfigTrapAccepterEntry OBJECT-TYPE The receivers to send traps to. | 1.3.6.1.4.1.3808.2.1.2.1 | not-accessible | mandatory | |
| trapIndex OBJECT-TYPE The trap receiver entry index. | 1.3.6.1.4.1.3808.2.1.2.1.1 | INTEGER (1..10) | not-accessible | mandatory |
| accepterAddr OBJECT-TYPE The trap receiver IP address. | 1.3.6.1.4.1.3808.2.1.2.1.2 | IpAddress | read-write | mandatory |
| communityString OBJECT-TYPE The trap receiver community name. | 1.3.6.1.4.1.3808.2.1.2.1.3 | DisplayString | read-write | mandatory |
| severityDegree OBJECT-TYPE The trap receiver severity level. Traps are marked in severity level as informational(1), warning(2), severe(3). Only send the traps of equal or greater severity than this value to the receiver. | 1.3.6.1.4.1.3808.2.1.2.1.4 | INTEGER {information(1), warning(2), severe(3)} | read-only | mandatory |
| accepterActive OBJECT-TYPE A receiver will accept traps if yes, and none if no. | 1.3.6.1.4.1.3808.2.1.2.1.5 | INTEGER {yes(1), no(2)} | read-write | mandatory |
| mconfigDHCPEnabled OBJECT-TYPE The system will automatically obtain its IP from a DHCP server if yes, and none if no. | 1.3.6.1.4.1.3808.2.1.3 | INTEGER {yes(1), no(2)} | read-write | mandatory |
| mconfigMyAddr OBJECT-TYPE The system IP address. | 1.3.6.1.4.1.3808.2.1.4 | IpAddress | read-only | mandatory |
| mconfigClock OBJECT-IDENTITY | 1.3.6.1.4.1.3808.2.1.5 | |||
| mconfigClockDate OBJECT-TYPE The current date in the mm/dd/yyyy format. Example: 01/01/2000. | 1.3.6.1.4.1.3808.2.1.5.1 | DisplayString | read-write | mandatory |
| mconfigClockTime OBJECT-TYPE The current time in the hh:mm:ss 24H format. | 1.3.6.1.4.1.3808.2.1.5.2 | DisplayString | read-write | mandatory |
| mtrapinfo OBJECT-IDENTITY | 1.3.6.1.4.1.3808.2.2 | |||
| mtrapinfoInteger OBJECT-TYPE Allow CPS traps with an integer argument for providing detail information. Not being defined in the MIB, only reply 0. | 1.3.6.1.4.1.3808.2.2.1 | INTEGER | read-only | mandatory |
| mtrapinfoIpAddress OBJECT-TYPE Allow CPS traps with an IP address argument for providing detail information. Not being defined in the MIB, only reply 0.0.0.0. | 1.3.6.1.4.1.3808.2.2.2 | IpAddress | read-only | mandatory |
| mtrapinfoString OBJECT-TYPE Allow CPS traps with an octet string argument for providing detail information. Not being defined in the MIB, only reply a NULL string. | 1.3.6.1.4.1.3808.2.2.3 | DisplayString | read-only | mandatory |
| mtrapinfoGauge OBJECT-TYPE Allow CPS traps with an Gauge argument for providing detail information. Not being defined in the MIB, only reply 0. | 1.3.6.1.4.1.3808.2.2.4 | Gauge | read-only | mandatory |
| mtrapinfoTimeTicks OBJECT-TYPE Allow CPS traps with an TimeTicks argument for providing detail information. Not being defined in the MIB, only reply 0. | 1.3.6.1.4.1.3808.2.2.5 | TimeTicks | read-only | mandatory |
| mtrapinfoBmEventId OBJECT-TYPE Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeed. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal. | 1.3.6.1.4.1.3808.2.2.6 | INTEGER | read-only | mandatory |
| mcontrol OBJECT-IDENTITY | 1.3.6.1.4.1.3808.2.3 | |||
| mcontrolRestart OBJECT-TYPE Setting this OID to restartCurrentSystem (2) will restart the current system. Setting this OID to restartCurrentAgent (3) will restart the current agent. Setting this OID to restartCurrentSystemAnd Agent (4) will restart the current the current system and agent. | 1.3.6.1.4.1.3808.2.3.1 | INTEGER {none(1), restartCurrentSystem(2), restartCurrentAgent(3), restartCurrentSystemAndAgent(4)} | read-write | mandatory |
| mcontrolReset OBJECT-TYPE Setting this OID to resetCurrentSystem (2) will reset the current system. Setting this OID to resetCurrentAgent (3) will reset the current agent. Setting this OID to resetCurrentSystemAndAgenta (4) will reset the current system and the current agent. | 1.3.6.1.4.1.3808.2.3.2 | INTEGER {none(1), resetCurrentSystem(2), resetCurrentAgent(3), resetCurrentSystemAndAgent(4)} | read-write | mandatory |
Notifications
| Name | OID | Status |
|---|---|---|
| communicationLost NOTIFICATION-TYPE SEVERE: Communication with the UPS has been lost. | 1.3.6.1.4.1.3808.0.1 | |
| upsOverload NOTIFICATION-TYPE SEVERE: The UPS has sensed an overload condition. | 1.3.6.1.4.1.3808.0.2 | |
| upsDiagnosticsFailed NOTIFICATION-TYPE SEVERE: The UPS battery test failed. | 1.3.6.1.4.1.3808.0.3 | |
| upsDischarged NOTIFICATION-TYPE SEVERE: The UPS has started a runtime estimation process. | 1.3.6.1.4.1.3808.0.4 | |
| upsOnBattery NOTIFICATION-TYPE WARNING: Utility power failed, transfer to backup mode. | 1.3.6.1.4.1.3808.0.5 | |
| upsBoostOn NOTIFICATION-TYPE WARNING: The UPS has enabled boost, low utility voltage. | 1.3.6.1.4.1.3808.0.6 | |
| lowBattery NOTIFICATION-TYPE SEVERE: The UPS battery capacity is low than threshold, soon to be exhausted. | 1.3.6.1.4.1.3808.0.7 | |
| communicationEstablished NOTIFICATION-TYPE INFORMATIONAL: Communication to the UPS has been established. | 1.3.6.1.4.1.3808.0.8 | |
| powerRestored NOTIFICATION-TYPE INFORMATIONAL: Utility power restored, return from backup mode. | 1.3.6.1.4.1.3808.0.9 | |
| upsDiagnosticsPassed NOTIFICATION-TYPE INFORMATIONAL: The UPS battery test passed. | 1.3.6.1.4.1.3808.0.10 | |
| returnFromLowBattery NOTIFICATION-TYPE INFORMATIONAL: The UPS has returned from a low battery condition. | 1.3.6.1.4.1.3808.0.11 | |
| upsTurnedOff NOTIFICATION-TYPE WARNING: The UPS has been turned off. | 1.3.6.1.4.1.3808.0.12 | |
| upsSleeping NOTIFICATION-TYPE WARNING: The UPS entered sleep mode. Output power will not be provided. | 1.3.6.1.4.1.3808.0.13 | |
| upsWokeUp NOTIFICATION-TYPE INFORMATION: The UPS woke up from sleep mode. Output power is being provided. | 1.3.6.1.4.1.3808.0.14 | |
| upsRebootStarted NOTIFICATION-TYPE WARNING: The UPS started reboot sequence. | 1.3.6.1.4.1.3808.0.15 | |
| upsOverTemp NOTIFICATION-TYPE SEVERE: The UPS inner temperature is too high. | 1.3.6.1.4.1.3808.0.16 | |
| returnFromOverTemp NOTIFICATION-TYPE INFORMATIONAL: The UPS over temperature condition cleared. | 1.3.6.1.4.1.3808.0.17 | |
| upsBuckOn NOTIFICATION-TYPE WARNING: The UPS has enabled buck, high utility voltage. | 1.3.6.1.4.1.3808.0.18 | |
| returnFromOverLoad NOTIFICATION-TYPE INFORMATIONAL: The UPS has returned from an overload condition. | 1.3.6.1.4.1.3808.0.19 | |
| returnFromDischarged NOTIFICATION-TYPE INFORMATIONAL: The UPS runtime estimation completed. | 1.3.6.1.4.1.3808.0.20 | |
| upsScheduleShutdown NOTIFICATION-TYPE WARNING: The UPS has started its schedule shutdown sequence. | 1.3.6.1.4.1.3808.0.21 | |
| upsEnterSleep NOTIFICATION-TYPE WARNING: The UPS started sleep sequence. | 1.3.6.1.4.1.3808.0.22 | |
| upsChargerFailure NOTIFICATION-TYPE WARNING: The battery charger is abnormal. | 1.3.6.1.4.1.3808.0.23 | |
| returnFromChargerFailure NOTIFICATION-TYPE INFORMATIONAL: The charger returned from a failure condition. | 1.3.6.1.4.1.3808.0.24 | |
| upsTurnoffStarted NOTIFICATION-TYPE WARNING: The UPS started turn off sequence. | 1.3.6.1.4.1.3808.0.25 | |
| upsTurnedOn NOTIFICATION-TYPE WARNING: The UPS has been turned on. | 1.3.6.1.4.1.3808.0.26 | |
| upsRemoteCommandFailed NOTIFICATION-TYPE WARNING: The UPS remote command failed. | 1.3.6.1.4.1.3808.0.27 | |
| upsLostRedundant NOTIFICATION-TYPE WARNING: Not enough power redundancy modules. | 1.3.6.1.4.1.3808.0.28 | |
| upsSignalClientShutdown NOTIFICATION-TYPE SEVERE: The UPS has signaled clients to shutdown. | 1.3.6.1.4.1.3808.0.29 | |
| upsEmergencyPowerOff NOTIFICATION-TYPE Emergency Power Off (EPO) | 1.3.6.1.4.1.3808.0.30 | |
| nclBankOn NOTIFICATION-TYPE INFORMATIONAL: Non-Critical bank has been turned on. | 1.3.6.1.4.1.3808.0.31 | |
| nclBankOff NOTIFICATION-TYPE INFORMATIONAL: Non-Critical bank has been turned off. | 1.3.6.1.4.1.3808.0.32 | |
| upsCommandCancel NOTIFICATION-TYPE INFORMATION: The cancel command has been executed. | 1.3.6.1.4.1.3808.0.33 | |
| upsStartBatteryTest NOTIFICATION-TYPE INFORMATION: The UPS has started a battery test process. | 1.3.6.1.4.1.3808.0.34 | |
| upsRemainRuntimeLowThanThreshold NOTIFICATION-TYPE WARNING: The UPS remaining runtime is lower than threshold. | 1.3.6.1.4.1.3808.0.35 | |
| nclBankStartScheduleOff NOTIFICATION-TYPE INFORMATION: Non-Critial bank has started its schedule off sequence. | 1.3.6.1.4.1.3808.0.36 | |
| upsEstimationAbort NOTIFICATION-TYPE WARNING: The UPS runtime estimation aborted. | 1.3.6.1.4.1.3808.0.37 | |
| upsHardwareFault NOTIFICATION-TYPE WARNING: The UPS hardware fault. | 1.3.6.1.4.1.3808.0.38 | |
| upsBatteryNotPresent NOTIFICATION-TYPE WARNING: Battery is not present. | 1.3.6.1.4.1.3808.0.39 | |
| upsWiringFault NOTIFICATION-TYPE WARNING: The UPS wiring fault has been detected. | 1.3.6.1.4.1.3808.0.40 | |
| upsWiringFaultCleared NOTIFICATION-TYPE INFORMATION: The UPS wiring fault has been cleared. | 1.3.6.1.4.1.3808.0.41 | |
| upsEnterBypassMode NOTIFICATION-TYPE WARNING: The UPS enters bypass mode. | 1.3.6.1.4.1.3808.0.42 | |
| upsReturnFromBypassMode NOTIFICATION-TYPE INFORMATION: The UPS leaves bypass mode. | 1.3.6.1.4.1.3808.0.43 | |
| upsBypassOverload NOTIFICATION-TYPE WARNING: The UPS bypass overload. | 1.3.6.1.4.1.3808.0.44 | |
| upsBypassOverloadCleared NOTIFICATION-TYPE INFORMATION: The UPS bypass overload has been cleared. | 1.3.6.1.4.1.3808.0.45 | |
| upsEnterECOMode NOTIFICATION-TYPE WARNING: The UPS enters ECO mode. | 1.3.6.1.4.1.3808.0.46 | |
| upsReturnFromECOMode NOTIFICATION-TYPE WARNING: The UPS leaves ECO mode. | 1.3.6.1.4.1.3808.0.47 | |
| upsBatteryOverThreeYear NOTIFICATION-TYPE WARNING: Battery has been 3 years from last Replacement. | 1.3.6.1.4.1.3808.0.48 | |
| upsBatteryExpiration NOTIFICATION-TYPE WARNING: The battery may not work well anymore. | 1.3.6.1.4.1.3808.0.49 | |
| upsBatteryReplacement NOTIFICATION-TYPE WARNING: The battery has been replaced. | 1.3.6.1.4.1.3808.0.50 | |
| upsModuleInvertorAlarm NOTIFICATION-TYPE WARNING: The UPS module invertor alarm. | 1.3.6.1.4.1.3808.0.51 | |
| upsModuleRectifierAlarm NOTIFICATION-TYPE WARNING: The UPS module rectifier alarm. | 1.3.6.1.4.1.3808.0.52 | |
| upsModuleFanAlarm NOTIFICATION-TYPE WARNING: The UPS module fan alarm. | 1.3.6.1.4.1.3808.0.53 | |
| upsModuleManualShutdown NOTIFICATION-TYPE WARNING: The UPS module manual shutdown. | 1.3.6.1.4.1.3808.0.54 | |
| upsModuleOverload NOTIFICATION-TYPE WARNING: The UPS module overload. | 1.3.6.1.4.1.3808.0.55 | |
| upsFirmwareUpgradeStart NOTIFICATION-TYPE WARNING: UPS firmware starts to update. | 1.3.6.1.4.1.3808.0.56 | |
| upsFirmwareUpgradeEnd NOTIFICATION-TYPE WARNING: UPS firmware update is over. | 1.3.6.1.4.1.3808.0.57 | |
| upsRFC1628TrapOnBattery NOTIFICATION-TYPE WARNING: RFC1628: UPS is on battery. | 1.3.6.1.4.1.3808.0.58 | |
| upsRFC1628TrapTestCompleted NOTIFICATION-TYPE WARNING: RFC1628: UPS test completed. | 1.3.6.1.4.1.3808.0.59 | |
| upsRFC1628TrapAlarmEntryAdded NOTIFICATION-TYPE WARNING: RFC1628: Alarm entry added. | 1.3.6.1.4.1.3808.0.60 | |
| failAuthViaHTTP NOTIFICATION-TYPE WARNING: Login authorization failure via HTTP. | 1.3.6.1.4.1.3808.0.61 | |
| passwordChange NOTIFICATION-TYPE INFORMATION: The password has been changed. | 1.3.6.1.4.1.3808.0.62 | |
| failAuthViaConsole NOTIFICATION-TYPE WARNING: Login authorization failure via Console. | 1.3.6.1.4.1.3808.0.63 | |
| configFileUpload NOTIFICATION-TYPE INFORMATION: Configuration file uploaded. | 1.3.6.1.4.1.3808.0.64 | |
| adminLoginInfo NOTIFICATION-TYPE INFORMATION: Administrator login. | 1.3.6.1.4.1.3808.0.65 | |
| adminLogoutInfo NOTIFICATION-TYPE INFORMATION: Administrator logout. | 1.3.6.1.4.1.3808.0.66 | |
| deviceLoginInfo NOTIFICATION-TYPE INFORMATION: Device login. | 1.3.6.1.4.1.3808.0.67 | |
| deviceLogoutInfo NOTIFICATION-TYPE INFORMATION: Device logout. | 1.3.6.1.4.1.3808.0.68 | |
| configurationChanged NOTIFICATION-TYPE INFORMATION: Configuration has been changed. | 1.3.6.1.4.1.3808.0.69 | |
| clientRegistered NOTIFICATION-TYPE Information: PowerPanel client has been registered. | 1.3.6.1.4.1.3808.0.70 | |
| clientRemoved NOTIFICATION-TYPE Information: PowerPanel client has been removed. | 1.3.6.1.4.1.3808.0.71 | |
| testEvent NOTIFICATION-TYPE Information: Test Event. | 1.3.6.1.4.1.3808.0.72 | |
| outletUserLoginInfo NOTIFICATION-TYPE Information: Outlet User login. | 1.3.6.1.4.1.3808.0.73 | |
| outletUserLogoutInfo NOTIFICATION-TYPE Information: Outlet User logout. | 1.3.6.1.4.1.3808.0.74 | |
| ePDUCommunicationEstablished NOTIFICATION-TYPE INFORMATIONAL: Communication with a Rack PDU has been established. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.3808.0.100 | |
| ePDUCommunicationLost NOTIFICATION-TYPE SEVERE: Communication with a Rack PDU has been lost. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.3808.0.101 | |
| ePDUOutletOn NOTIFICATION-TYPE INFORMATIONAL: An outlet on a Switched Rack PDU has turned on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.102 | |
| ePDUOutletOff NOTIFICATION-TYPE INFORMATIONAL: An outlet on a Switched Rack PDU has turned off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.103 | |
| ePDUDeviceConfigChange NOTIFICATION-TYPE INFORMATIONAL: A device configuration change has been made on a Rack PDU. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.3808.0.104 | |
| ePDUOutletConfigChange NOTIFICATION-TYPE INFORMATIONAL: An outlet configuration change has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.105 | |
| ePDULowLoad NOTIFICATION-TYPE WARNING: A Rack PDU has violated the low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.106 | |
| ePDULowLoadCleared NOTIFICATION-TYPE INFORMATIONAL: The low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.107 | |
| ePDUNearOverload NOTIFICATION-TYPE WARNING: A Rack PDU is near an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.108 | |
| ePDUNearOverloadCleared NOTIFICATION-TYPE INFORMATIONAL: The near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.109 | |
| ePDUOverload NOTIFICATION-TYPE SEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.110 | |
| ePDUOverloadCleared NOTIFICATION-TYPE INFORMATIONAL: The overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.111 | |
| ePDUDelayOutletOnCommand NOTIFICATION-TYPE INFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to turn on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.112 | |
| ePDUDelayOutletOffCommand NOTIFICATION-TYPE INFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to turn off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.113 | |
| ePDUDelayOutletRebootCommand NOTIFICATION-TYPE INFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to reboot. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.114 | |
| ePDUCancelPendingCommand NOTIFICATION-TYPE INFORMATIONAL: A cancel pending command has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number (0 indicates all outlets). The fourth argument is the outlet name (or device name if all outlets). | 1.3.6.1.4.1.3808.0.115 | |
| ePDULineUndervoltage NOTIFICATION-TYPE SEVERE: Utility Line Undervoltage The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.116 | |
| ePDULineUndervoltageCleared NOTIFICATION-TYPE INFORMATIONAL: Utility Line Undervoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.117 | |
| ePDULineOvervoltage NOTIFICATION-TYPE SEVERE: Utility Line Overvoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.118 | |
| ePDULineOvervoltageCleared NOTIFICATION-TYPE INFORMATIONAL: Utility Line Overvoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | 1.3.6.1.4.1.3808.0.119 | |
| ePDUPowerSupply1Fail NOTIFICATION-TYPE SEVERE: Power Supply 1 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.3808.0.120 | |
| ePDUPowerSupply1Ok NOTIFICATION-TYPE INFORMATIONAL: Power Supply 1 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.3808.0.121 | |
| ePDUPowerSupply2Fail NOTIFICATION-TYPE SEVERE: Power Supply 2 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.3808.0.122 | |
| ePDUPowerSupply2Ok NOTIFICATION-TYPE INFORMATIONAL: Power Supply 2 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.3808.0.123 | |
| ePDUBankLowLoad NOTIFICATION-TYPE WARNING: A Rack PDU bank has violated the low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is the bank number. | 1.3.6.1.4.1.3808.0.124 | |
| ePDUBankLowLoadCleared NOTIFICATION-TYPE INFORMATIONAL: The low load condition on a Rack PDU bank has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the bank number. | 1.3.6.1.4.1.3808.0.125 | |
| ePDUBankNearOverload NOTIFICATION-TYPE WARNING: A Rack PDU bank is near an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the bank number. | 1.3.6.1.4.1.3808.0.126 | |
| ePDUBankNearOverloadCleared NOTIFICATION-TYPE INFORMATIONAL: The near overload condition on a Rack PDU bank has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase/bank number. | 1.3.6.1.4.1.3808.0.127 | |
| ePDUBankOverload NOTIFICATION-TYPE SEVERE: A Rack PDU bank is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the bank number. | 1.3.6.1.4.1.3808.0.128 | |
| ePDUBankOverloadCleared NOTIFICATION-TYPE INFORMATIONAL: The overload condition on a Rack PDU bank has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the bank number. | 1.3.6.1.4.1.3808.0.129 | |
| ePDUComponentCommunicationEstablished NOTIFICATION-TYPE INFORMATIONAL: Component communication lost has been cleared. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.3808.0.130 | |
| ePDUComponentCommunicationLost NOTIFICATION-TYPE SEVERE: Component communication lost. The first argument is the serial number. The second argument is the device name. | 1.3.6.1.4.1.3808.0.131 | |
| ePDUOutletLowLoad NOTIFICATION-TYPE WARNING: A Rack PDU has violated the outlet low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.132 | |
| ePDUOutletLowLoadCleared NOTIFICATION-TYPE INFORMATIONAL: The outlet low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.133 | |
| ePDUOutletNearOverload NOTIFICATION-TYPE WARNING: A Rack PDU is near an outlet overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.134 | |
| ePDUOutletNearOverloadCleared NOTIFICATION-TYPE INFORMATIONAL: The outlet near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.135 | |
| ePDUOutletOverload NOTIFICATION-TYPE SEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.136 | |
| ePDUOutletOverloadCleared NOTIFICATION-TYPE INFORMATIONAL: The outlet overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.137 | |
| envHighTemperatureViolation NOTIFICATION-TYPE WARNING: The environment high temperature threshold has been violated. | 1.3.6.1.4.1.3808.0.200 | |
| envHighTemperatureBack NOTIFICATION-TYPE INFORMATION: The environment temperature returned from high value. | 1.3.6.1.4.1.3808.0.201 | |
| envLowTemperatureViolation NOTIFICATION-TYPE WARNING: The environment low temperature threshold has been violated. | 1.3.6.1.4.1.3808.0.202 | |
| envLowTempBack NOTIFICATION-TYPE INFORMATION: The environment temperature returned from low value. | 1.3.6.1.4.1.3808.0.203 | |
| envHighHumidityViolation NOTIFICATION-TYPE WARNING: The environment high humidity threshold has been violated. | 1.3.6.1.4.1.3808.0.204 | |
| envHighHumidityBack NOTIFICATION-TYPE INFORMATION: The environment humidity return from high value. | 1.3.6.1.4.1.3808.0.205 | |
| envLowHumidityViolation NOTIFICATION-TYPE WARNING: The environment low humidity threshold has been violated. | 1.3.6.1.4.1.3808.0.206 | |
| envLowHumdBack NOTIFICATION-TYPE INFORMATION: The environment humidity return from low value. | 1.3.6.1.4.1.3808.0.207 | |
| envDryContactAbnormal NOTIFICATION-TYPE INFORMATION: The Contact is abnormal. | 1.3.6.1.4.1.3808.0.208 | |
| envDryContactNormal NOTIFICATION-TYPE INFORMATION: The Contact has returned from abnormal. | 1.3.6.1.4.1.3808.0.209 | |
| envConntected NOTIFICATION-TYPE INFORMATION: The Environment Sensor has been connected. | 1.3.6.1.4.1.3808.0.210 | |
| envDisconntected NOTIFICATION-TYPE INFORMATION: The Environment Sensor has been disconnected. | 1.3.6.1.4.1.3808.0.211 | |
| envRateOfTemperatureChangeAbnormal NOTIFICATION-TYPE INFORMATION: The rate of temperature change is abnormal. | 1.3.6.1.4.1.3808.0.212 | |
| envRateOfHumdChangeAbnormal NOTIFICATION-TYPE INFORMATION: The rate of humidity change is abnormal. | 1.3.6.1.4.1.3808.0.213 | |
| atsSwitchSource NOTIFICATION-TYPE INFORMATIONAL: ATS has switched source. The first argument is the device name. The second argument is the serial number. The third argument is the selected source. | 1.3.6.1.4.1.3808.0.301 | |
| atsSourceFault NOTIFICATION-TYPE WARNING: Source fault occurs. The first argument is the device name. The second argument is the serial number. The third argument is the source name. | 1.3.6.1.4.1.3808.0.302 | |
| atsSourceFaultCleared NOTIFICATION-TYPE INFORMATIONAL: Source fault has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name. | 1.3.6.1.4.1.3808.0.303 | |
| atsRedundancyFail NOTIFICATION-TYPE WARNING: Redundancy fails. The first argument is the device name. The second argument is the serial number. The third argument is the source name. | 1.3.6.1.4.1.3808.0.304 | |
| atsRedundancyRestored NOTIFICATION-TYPE INFORMATIONAL: Redundancy has been restored. The first argument is the device name. The second argument is the serial number. The third argument is the source name. | 1.3.6.1.4.1.3808.0.305 | |
| atsInputHighVoltage NOTIFICATION-TYPE WARNING: The upper voltage limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the phase voltage. | 1.3.6.1.4.1.3808.0.306 | |
| atsInputHighVoltageCleared NOTIFICATION-TYPE INFORMATIONAL: The upper voltage condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the phase voltage. | 1.3.6.1.4.1.3808.0.307 | |
| atsInputLowVoltage NOTIFICATION-TYPE WARNING: The lower voltage limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the phase voltage. | 1.3.6.1.4.1.3808.0.308 | |
| atsInputLowVoltageCleared NOTIFICATION-TYPE INFORMATIONAL: The lower voltage condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the phase voltage. | 1.3.6.1.4.1.3808.0.309 | |
| atsInputHighFrequency NOTIFICATION-TYPE WARNING: The upper frequency limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the input frequency. | 1.3.6.1.4.1.3808.0.310 | |
| atsInputHighFrequencyCleared NOTIFICATION-TYPE INFORMATIONAL: The upper frequency condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the input frequency. | 1.3.6.1.4.1.3808.0.311 | |
| atsInputLowFrequency NOTIFICATION-TYPE WARNING: The lower frequency limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the input frequency. | 1.3.6.1.4.1.3808.0.312 | |
| atsInputLowFrequencyCleared NOTIFICATION-TYPE INFORMATIONAL: The lower frequency condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the input frequency. | 1.3.6.1.4.1.3808.0.313 | |
| atsCommunicationLost NOTIFICATION-TYPE MAJOR: ATS communication lost. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.314 | |
| atsCommunicationEstablished NOTIFICATION-TYPE INFORMATIONAL: ATS communication has been established. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.315 | |
| atsLCDCommunicationLost NOTIFICATION-TYPE WARNING: LCD communication lost. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.316 | |
| atsLCDCommunicationLostCleared NOTIFICATION-TYPE INFORMATIONAL: LCD communication lost has been cleared. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.317 | |
| atsDB9CommunicationLost NOTIFICATION-TYPE WARNING: DB9 communication lost. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.318 | |
| atsDB9CommunicationLostCleared NOTIFICATION-TYPE INFORMATIONAL: DB9 communication lost has been cleared. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.319 | |
| atsPowerSupplyFault NOTIFICATION-TYPE CRITICAL: Power supply failure. The first argument is the device name. The second argument is the serial number. The third argument is the input source of the power supply. | 1.3.6.1.4.1.3808.0.320 | |
| atsPowerSupplyFaultCleared NOTIFICATION-TYPE CRITICAL: Power supply failure. The first argument is the device name. The second argument is the serial number. The third argument is the input source of the power supply. | 1.3.6.1.4.1.3808.0.321 | |
| atsDevHardwareFault NOTIFICATION-TYPE CRITICAL: Device hardware failure. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.322 | |
| atsDevHardwareFaultCleared NOTIFICATION-TYPE INFORMATIONAL: Device hardware failure has been cleared. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.323 | |
| atsSourceConfigChanged NOTIFICATION-TYPE INFORMATIONAL: A source configuration change has been made. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.324 | |
| atsDeviceConfigChanged NOTIFICATION-TYPE INFORMATIONAL: A device configuration change has been made. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.325 | |
| atsOutletConfigChanged NOTIFICATION-TYPE INFORMATIONAL: A outlet configuration change has been made. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.326 | |
| atsEventCountsCleared NOTIFICATION-TYPE INFORMATIONAL: Event counts has been cleared. The first argument is the device name. The second argument is the serial number. | 1.3.6.1.4.1.3808.0.327 | |
| atsOverload NOTIFICATION-TYPE WARNING: The load has exceeded overload threshold. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load. | 1.3.6.1.4.1.3808.0.328 | |
| atsOverloadCleared NOTIFICATION-TYPE INFORMATIONAL: The overload condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load. | 1.3.6.1.4.1.3808.0.329 | |
| atsNearOverload NOTIFICATION-TYPE WARNING: The load has exceeded near overload threshold. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load. | 1.3.6.1.4.1.3808.0.330 | |
| atsNearOverloadCleared NOTIFICATION-TYPE INFORMATIONAL: The near overload condition has beed cleared. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load. | 1.3.6.1.4.1.3808.0.331 | |
| atsLowLoad NOTIFICATION-TYPE WARNING: The load has been lower than low load threshold. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load. | 1.3.6.1.4.1.3808.0.332 | |
| atsLowLoadCleared NOTIFICATION-TYPE INFORMATIONAL: The low load condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load. | 1.3.6.1.4.1.3808.0.333 | |
| atsOutletOnCommand NOTIFICATION-TYPE INFORMATIONAL: An outlet on ATS has been assigned to turn on. The first argument is the device name. The second argument is the serial number. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.334 | |
| atsOutletOffCommand NOTIFICATION-TYPE INFORMATIONAL: An outlet on ATS has been assigned to turn off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.335 | |
| atsOutletRebootCommand NOTIFICATION-TYPE INFORMATIONAL: An outlet on ATS has been assigned to reboot. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.336 | |
| atsCancelPendingCommand NOTIFICATION-TYPE INFORMATIONAL: A cancel pending command has been made on ATS. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number (0 indicates all outlets). The fourth argument is the outlet name (or device name if all outlets). | 1.3.6.1.4.1.3808.0.337 | |
| atsOutletOn NOTIFICATION-TYPE INFORMATIONAL: An outlet on ATS has turned on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.338 | |
| atsOutletOff NOTIFICATION-TYPE INFORMATIONAL: An outlet on ATS has turned off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | 1.3.6.1.4.1.3808.0.339 | |
| pduDeviceEvent NOTIFICATION-TYPE INFORMATIONAL: A PDU device event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the device table index. | 1.3.6.1.4.1.3808.0.400 | |
| pduDeviceAlarm NOTIFICATION-TYPE Alarm: A PDU device alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the device table index. | 1.3.6.1.4.1.3808.0.401 | |
| pduDeviceAlarmClear NOTIFICATION-TYPE INFORMATIONAL: A PDU device alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the device table index. | 1.3.6.1.4.1.3808.0.402 | |
| pduPhaseEvent NOTIFICATION-TYPE INFORMATIONAL: A PDU phase event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the phase table index. The foutrh argument is the phase number. | 1.3.6.1.4.1.3808.0.403 | |
| pduPhaseAlarm NOTIFICATION-TYPE Alarm: A PDU phase alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the phase table index. The foutrh argument is the phase number. | 1.3.6.1.4.1.3808.0.404 | |
| pduPhaseAlarmClear NOTIFICATION-TYPE INFORMATIONAL: A PDU phase alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase table index. The foutrh argument is the phase number. | 1.3.6.1.4.1.3808.0.405 | |
| pduBankEvent NOTIFICATION-TYPE INFORMATIONAL: A PDU bank event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the bank table index. The foutrh argument is the bank number. | 1.3.6.1.4.1.3808.0.406 | |
| pduBankAlarm NOTIFICATION-TYPE Alarm: A PDU bank alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the bank table index. The foutrh argument is the bank number. | 1.3.6.1.4.1.3808.0.407 | |
| pduBankAlarmClear NOTIFICATION-TYPE INFORMATIONAL: A PDU bank alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the bank table index. The foutrh argument is the bank number. | 1.3.6.1.4.1.3808.0.408 | |
| pduOutletSwitchedEvent NOTIFICATION-TYPE INFORMATIONAL: A PDU switched outlet event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name. | 1.3.6.1.4.1.3808.0.409 | |
| pduOutletSwitchedAlarm NOTIFICATION-TYPE Alarm: A PDU switched outlet alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name. | 1.3.6.1.4.1.3808.0.410 | |
| pduOutletSwitchedAlarmClear NOTIFICATION-TYPE INFORMATIONAL: A PDU switched outlet alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name. | 1.3.6.1.4.1.3808.0.411 | |
| pduOutletMeteredEvent NOTIFICATION-TYPE INFORMATIONAL: A PDU metered outlet event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name. | 1.3.6.1.4.1.3808.0.412 | |
| pduOutletMeteredAlarm NOTIFICATION-TYPE Alarm: A PDU metered outlet alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name. | 1.3.6.1.4.1.3808.0.413 | |
| pduOutletMeteredAlarmClear NOTIFICATION-TYPE INFORMATIONAL: A PDU metered outlet alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name. | 1.3.6.1.4.1.3808.0.414 | |
| pduDaisyChainEvent NOTIFICATION-TYPE INFORMATIONAL: A PDU daisy-chain event has been happened. The first argument is the host serial number. The second argument is the host device name. The third argument is the event device table index. The foutrh argument is the event device serial number. The fifth argument is the event device name. | 1.3.6.1.4.1.3808.0.415 | |
| pduDaisyChainAlarm NOTIFICATION-TYPE Alarm: A PDU daisy-chain alarm has been detected. The first argument is the host serial number. The second argument is the host device name. The third argument is the alarm device table index. The foutrh argument is the alarm device serial number. The fifth argument is the alarm device name. | 1.3.6.1.4.1.3808.0.416 | |
| pduDaisyChainAlarmClear NOTIFICATION-TYPE INFORMATIONAL: A PDU daisy-chain alarm has been cleared. The first argument is the host serial number. The second argument is the host device name. The third argument is the alarm device table index. The foutrh argument is the alarm deice serial number. The fifth argument is the alarm device name. | 1.3.6.1.4.1.3808.0.417 | |
| bmSystemAlarm NOTIFICATION-TYPE ALARM: System alarm occurance. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the alarm event specific identifier. The fifth argument is the trap information string. | 1.3.6.1.4.1.3808.0.600 | |
| bmSystemWarning NOTIFICATION-TYPE WARNING: System warning occurance. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the alarm event specific identifier. The fifth argument is the trap information string. | 1.3.6.1.4.1.3808.0.601 | |
| bmSystemInfo NOTIFICATION-TYPE INFO: System information. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the alarm event specific identifier. The fifth argument is the trap information string. | 1.3.6.1.4.1.3808.0.602 | |
| bmProbesAlarm NOTIFICATION-TYPE ALARM: Probe alarm event. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the string index the probe located. The fifth argument is the battery index the probe located. The sixth argument is the alarm event specific identifier. The seventh argument is the trap information string. | 1.3.6.1.4.1.3808.0.603 | |
| bmSProbesWarning NOTIFICATION-TYPE WARNING: Probe warning event. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the string index the probe located. The fifth argument is the battery index the probe located. The sixth argument is the alarm event specific identifier. The seventh argument is the trap information string. | 1.3.6.1.4.1.3808.0.604 | |
| bmProbesInfo NOTIFICATION-TYPE INFO: Probe information. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the string index the probe located. The fifth argument is the battery index the probe located. The sixth argument is the alarm event specific identifier. The seventh argument is the trap information string. | 1.3.6.1.4.1.3808.0.605 |