MIBs Depot

CCPOWER-MIB

Registered at
1.3.6.1.4.1.18642
Namespace
ccpower
Source file
CCPOWER-MIB
Digest
sha256:3d83a9ac2c9b6fd0e037c809ddfe4cda5a3d4baae95d5c85458dc42a1cf0b8c5

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

CCPOWER-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
ccpower
OBJECT-IDENTITY
1.3.6.1.4.1.18642
dcSystem
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1
readWriteObjects
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.1
settings
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.1.1
floatVoltage
OBJECT-TYPE
Rectifier DC Output Voltage. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.1INTEGERread-writemandatory
overloadCurrent
OBJECT-TYPE
Current which when exceeded will cause an alarm. Return value is XXXX representing XXXX amps.
1.3.6.1.4.1.18642.1.1.1.2INTEGERread-writemandatory
highVoltageAlarm
OBJECT-TYPE
Voltage which when exceeded will cause an alarm. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.3INTEGERread-writemandatory
lowVoltageAlarm
OBJECT-TYPE
Voltage which when exceeded will cause an alarm. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.4INTEGERread-writemandatory
disconnect1Voltage
OBJECT-TYPE
Voltage which when exceeded will cause a specific load to disconnect. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.5INTEGERread-writemandatory
disconnect1Temperature
OBJECT-TYPE
Temperature which when exceeded will cause a specific load to disconnect. Return value is XX representing XX °C.
1.3.6.1.4.1.18642.1.1.1.6INTEGERread-writemandatory
disconnect1LoadShedSundayOff
OBJECT-TYPE
Time on Sunday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.7DisplayStringread-writemandatory
disconnect1LoadShedMondayOff
OBJECT-TYPE
Time on Monday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.8DisplayStringread-writemandatory
disconnect1LoadShedTuesdayOff
OBJECT-TYPE
Time on Tuesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.9DisplayStringread-writemandatory
disconnect1LoadShedWednesdayOff
OBJECT-TYPE
Time on Wednesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.10DisplayStringread-writemandatory
disconnect1LoadShedThursdayOff
OBJECT-TYPE
Time on Thursday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.11DisplayStringread-writemandatory
disconnect1LoadShedFridayOff
OBJECT-TYPE
Time on Friday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.12DisplayStringread-writemandatory
disconnect1LoadShedSaturdayOff
OBJECT-TYPE
Time on Saturday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.13DisplayStringread-writemandatory
disconnect2Voltage
OBJECT-TYPE
Voltage which when exceeded will cause a specific load to disconnect. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.14INTEGERread-writemandatory
disconnect2Temperature
OBJECT-TYPE
Temperature which when exceeded will cause a specific load to disconnect. Return value is XX representing XX °C.
1.3.6.1.4.1.18642.1.1.1.15INTEGERread-writemandatory
disconnect2LoadShedSundayOff
OBJECT-TYPE
Time on Sunday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.16DisplayStringread-writemandatory
disconnect2LoadShedMondayOff
OBJECT-TYPE
Time on Monday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.17DisplayStringread-writemandatory
disconnect2LoadShedTuesdayOff
OBJECT-TYPE
Time on Tuesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.18DisplayStringread-writemandatory
disconnect2LoadShedWednesdayOff
OBJECT-TYPE
Time on Wednesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.19DisplayStringread-writemandatory
disconnect2LoadShedThursdayOff
OBJECT-TYPE
Time on Thursday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.20DisplayStringread-writemandatory
disconnect2LoadShedFridayOff
OBJECT-TYPE
Time on Friday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.21DisplayStringread-writemandatory
disconnect2LoadShedSaturdayOff
OBJECT-TYPE
Time on Saturday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.22DisplayStringread-writemandatory
disconnect3Voltage
OBJECT-TYPE
Voltage which when exceeded will cause a specific load to disconnect. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.23INTEGERread-writemandatory
disconnect3Temperature
OBJECT-TYPE
Temperature which when exceeded will cause a specific load to disconnect. Return value is XX representing XX °C.
1.3.6.1.4.1.18642.1.1.1.24INTEGERread-writemandatory
disconnect3LoadShedSundayOff
OBJECT-TYPE
Time on Sunday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.25DisplayStringread-writemandatory
disconnect3LoadShedMondayOff
OBJECT-TYPE
Time on Monday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.26DisplayStringread-writemandatory
disconnect3LoadShedTuesdayOff
OBJECT-TYPE
Time on Tuesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.27DisplayStringread-writemandatory
disconnect3LoadShedWednesdayOff
OBJECT-TYPE
Time on Wednesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.28DisplayStringread-writemandatory
disconnect3LoadShedThursdayOff
OBJECT-TYPE
Time on Thursday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.29DisplayStringread-writemandatory
disconnect3LoadShedFridayOff
OBJECT-TYPE
Time on Friday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.30DisplayStringread-writemandatory
disconnect3LoadShedSaturdayOff
OBJECT-TYPE
Time on Saturday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.31DisplayStringread-writemandatory
reconnect1Voltage
OBJECT-TYPE
Voltage which when reached will cause a specific load to reconnect. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.32INTEGERread-writemandatory
reconnect1LoadShedSundayOn
OBJECT-TYPE
Time which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.33DisplayStringread-writemandatory
reconnect1LoadShedMondayOn
OBJECT-TYPE
Time on Monday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.34DisplayStringread-writemandatory
reconnect1LoadShedTuesdayOn
OBJECT-TYPE
Time on Tuesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.35DisplayStringread-writemandatory
reconnect1LoadShedWednesdayOn
OBJECT-TYPE
Time on Wednesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.36DisplayStringread-writemandatory
reconnect1LoadShedThursdayOn
OBJECT-TYPE
Time on Thursday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.37DisplayStringread-writemandatory
reconnect1LoadShedFridayOn
OBJECT-TYPE
Time on Friday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.38DisplayStringread-writemandatory
reconnect1LoadShedSaturdayOn
OBJECT-TYPE
Time on Saturday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.39DisplayStringread-writemandatory
reconnect2Voltage
OBJECT-TYPE
Voltage which when reached will cause a specific load to reconnect. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.40INTEGERread-writemandatory
reconnect2LoadShedSundayOn
OBJECT-TYPE
Time on Sunday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.41DisplayStringread-writemandatory
reconnect2LoadShedMondayOn
OBJECT-TYPE
Time on Monday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.42DisplayStringread-writemandatory
reconnect2LoadShedTuesdayOn
OBJECT-TYPE
Time on Tuesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.43DisplayStringread-writemandatory
reconnect2LoadShedWednesdayOn
OBJECT-TYPE
Time on Wednesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.44DisplayStringread-writemandatory
reconnect2LoadShedThursdayOn
OBJECT-TYPE
Time on Thursday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.45DisplayStringread-writemandatory
reconnect2LoadShedFridayOn
OBJECT-TYPE
Time on Friday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.46DisplayStringread-writemandatory
reconnect2LoadShedSaturdayOn
OBJECT-TYPE
Time on Saturday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.47DisplayStringread-writemandatory
reconnect3Voltage
OBJECT-TYPE
Voltage which when reached will cause a specific load to reconnect. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.48INTEGERread-writemandatory
reconnect3LoadShedSundayOn
OBJECT-TYPE
Time on Sunday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.49DisplayStringread-writemandatory
reconnect3LoadShedMondayOn
OBJECT-TYPE
Time on Monday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.50DisplayStringread-writemandatory
reconnect3LoadShedTuesdayOn
OBJECT-TYPE
Time on Tuesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.51DisplayStringread-writemandatory
reconnect3LoadShedWednesdayOn
OBJECT-TYPE
Time on Wednesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.52DisplayStringread-writemandatory
reconnect3LoadShedThursdayOn
OBJECT-TYPE
Time on Thursday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.53DisplayStringread-writemandatory
reconnect3LoadShedFridayOn
OBJECT-TYPE
Time on Friday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.54DisplayStringread-writemandatory
reconnect3LoadShedSaturdayOn
OBJECT-TYPE
Time on Saturday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.
1.3.6.1.4.1.18642.1.1.1.55DisplayStringread-writemandatory
equalizeTime
OBJECT-TYPE
Number of hours the equalize voltage is to be applied. Return value is XXX representing XX.X hours.
1.3.6.1.4.1.18642.1.1.1.56INTEGERread-writemandatory
equalizeVoltage
OBJECT-TYPE
Equalize voltage to be applied. Return value is XXX representing XX.X volts.
1.3.6.1.4.1.18642.1.1.1.57INTEGERread-writemandatory
batteryResistancePercentChange
OBJECT-TYPE
Resistance percentange change that when reached will cause an alarm. Return value is XXX representing XXX %.
1.3.6.1.4.1.18642.1.1.1.58INTEGERread-writemandatory
batteryResistanceTestInterval
OBJECT-TYPE
Battery resistance test interval. Return value is XX representing XX weeks.
1.3.6.1.4.1.18642.1.1.1.59INTEGERread-writemandatory
loadShedTimeControl
OBJECT-TYPE
Load shed time control enabled/disabled status. Return value: 1 = time control enabled, 2 = time control disabled.
1.3.6.1.4.1.18642.1.1.1.60INTEGER {enabled(1), disabled(2)}read-writemandatory
batteryFloatCurrent
OBJECT-TYPE
Battery float current. Return value is XXX representing XXX amps.
1.3.6.1.4.1.18642.1.1.1.61INTEGERread-writemandatory
readOnlyObjects
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.2
rectifiers
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.2.1
rectifierFloatVoltage
OBJECT-TYPE
Rectifier float voltage. Return value is XXX representing XX.X volts. Valid ranges are 24.0 to 57.0 volts.
1.3.6.1.4.1.18642.1.2.1.1INTEGERread-onlymandatory
rectifierLoadCurrent
OBJECT-TYPE
Rectifier DC load current. Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 5000 amps.
1.3.6.1.4.1.18642.1.2.1.2INTEGERread-onlymandatory
batteries
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.2.2
batteryCurrent
OBJECT-TYPE
Battery current. Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 1000 amps.
1.3.6.1.4.1.18642.1.2.2.1INTEGERread-onlymandatory
batteryTemperature
OBJECT-TYPE
Battery temperature. Return value is XX representing XX °C. Valid ranges are -40 to 99 °C.
1.3.6.1.4.1.18642.1.2.2.2INTEGERread-onlymandatory
batteryResistanceReference
OBJECT-TYPE
Initial battery resistance. Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms.
1.3.6.1.4.1.18642.1.2.2.3INTEGERread-onlymandatory
batteryResistanceReading
OBJECT-TYPE
Last battery resistance reading. Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms.
1.3.6.1.4.1.18642.1.2.2.4INTEGERread-onlymandatory
batteryResistanceChange
OBJECT-TYPE
Percent change from last battery resistance reading. Return value is XXX representing XXX %. Valid ranges are 001 to 999 %.
1.3.6.1.4.1.18642.1.2.2.5INTEGERread-onlymandatory
batteryCycles1
OBJECT-TYPE
Number of discharge/recharge cycles less than 1 minute. Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles.
1.3.6.1.4.1.18642.1.2.2.6INTEGERread-onlymandatory
batteryCycles1to5
OBJECT-TYPE
Number of discharge/recharge cycles from 1 to 5 minutes. Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles.
1.3.6.1.4.1.18642.1.2.2.7INTEGERread-onlymandatory
batteryCycles5to15
OBJECT-TYPE
Number of discharge/recharge cycles from 5 to 15 minutes. Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles.
1.3.6.1.4.1.18642.1.2.2.8INTEGERread-onlymandatory
batteryCycles15
OBJECT-TYPE
Number of discharge/recharge cycles greater than 15 minutes. Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles.
1.3.6.1.4.1.18642.1.2.2.9INTEGERread-onlymandatory
batteryCycles15LastCycleDate
OBJECT-TYPE
Last cycle date of batteryCycles15. Return value is MM-DD-YY, HH-MM.
1.3.6.1.4.1.18642.1.2.2.10DisplayStringread-onlymandatory
batteryCycles15LastDuration
OBJECT-TYPE
Duration of batteryCycles15 last cycle. Return value is XXXX representing XXXX minutes.
1.3.6.1.4.1.18642.1.2.2.11INTEGERread-onlymandatory
batteryTestFault
OBJECT-TYPE
Battery failure has occured during battery restistance test. Return value: 1 = Abort 1, 2 = Abort 2, 3 = Abort 3, 4 = None.
1.3.6.1.4.1.18642.1.2.2.12INTEGER {abort1(1), abort2(2), abort3(3), none(4)}read-onlymandatory
factorySettings
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.2.3
floatVoltagePresets
OBJECT-TYPE
Float voltage factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.1DisplayStringread-onlymandatory
highVoltageAlarmPresets
OBJECT-TYPE
High voltage alarm factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.2DisplayStringread-onlymandatory
lowVoltageAlarmPresets
OBJECT-TYPE
Low voltage alarm factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.3DisplayStringread-onlymandatory
disconnect1VoltagePresets
OBJECT-TYPE
Disconnect voltage 1 factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.4DisplayStringread-onlymandatory
disconnect1TemperaturePreset
OBJECT-TYPE
Disconnect temperature 1 factory setting. Return value is XX °C.
1.3.6.1.4.1.18642.1.2.3.5DisplayStringread-onlymandatory
disconnect1LoadShedSundayPresets
OBJECT-TYPE
Disconnect 1 load shed Sunday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.6DisplayStringread-onlymandatory
disconnect1LoadShedMondayPresets
OBJECT-TYPE
Disconnect 1 load shed Monday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.7DisplayStringread-onlymandatory
disconnect1LoadShedTuesdayPresets
OBJECT-TYPE
Disconnect 1 load shed Tuesday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.8DisplayStringread-onlymandatory
disconnect1LoadShedWednesdayPresets
OBJECT-TYPE
Disconnect 1 load shed Wednesday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.9DisplayStringread-onlymandatory
disconnect1LoadShedThursdayPresets
OBJECT-TYPE
Disconnect 1 load shed Thursday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.10DisplayStringread-onlymandatory
disconnect1LoadShedFridayPresets
OBJECT-TYPE
Disconnect 1 load shed Friday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.11DisplayStringread-onlymandatory
disconnect1LoadShedSaturdayPresets
OBJECT-TYPE
Disconnect 1 load shed Saturday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.12DisplayStringread-onlymandatory
reconnectVoltage1Presets
OBJECT-TYPE
Reconnect voltage 1 factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.13DisplayStringread-onlymandatory
disconnect2VoltagePresets
OBJECT-TYPE
Disconnect voltage 2 factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.14DisplayStringread-onlymandatory
disconnect2TemperaturePreset
OBJECT-TYPE
Disconnect temperature 2 factory setting. Return value is XX °C.
1.3.6.1.4.1.18642.1.2.3.15DisplayStringread-onlymandatory
disconnect2LoadShedSundayPresets
OBJECT-TYPE
Disconnect 2 load shed Sunday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.16DisplayStringread-onlymandatory
disconnect2LoadShedMondayPresets
OBJECT-TYPE
Disconnect 2 load shed Monday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.17DisplayStringread-onlymandatory
disconnect2LoadShedTuesdayPresets
OBJECT-TYPE
Disconnect 2 load shed Tuesday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.18DisplayStringread-onlymandatory
disconnect2LoadShedWednesdayPresets
OBJECT-TYPE
Disconnect 2 load shed Wednesday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.19DisplayStringread-onlymandatory
disconnect2LoadShedThursdayPresets
OBJECT-TYPE
Disconnect 2 load shed Thursday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.20DisplayStringread-onlymandatory
disconnect2LoadShedFridayPresets
OBJECT-TYPE
Disconnect 2 load shed Friday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.21DisplayStringread-onlymandatory
disconnect2LoadShedSaturdayPresets
OBJECT-TYPE
Disconnect 2 load shed Saturday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.22DisplayStringread-onlymandatory
reconnect2VoltagePresets
OBJECT-TYPE
Reconnect voltage 2 factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.23DisplayStringread-onlymandatory
disconnect3VoltagePresets
OBJECT-TYPE
Disconnect voltage 3 factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.24DisplayStringread-onlymandatory
disconnect3TemperaturePreset
OBJECT-TYPE
Disconnect temperature 3 factory setting. Return value is XX °C.
1.3.6.1.4.1.18642.1.2.3.25DisplayStringread-onlymandatory
disconnect3LoadShedSundayPresets
OBJECT-TYPE
Disconnect 3 load shed Sunday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.26DisplayStringread-onlymandatory
disconnect3LoadShedMondayPresets
OBJECT-TYPE
Disconnect 3 load shed Monday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.27DisplayStringread-onlymandatory
disconnect3LoadShedTuesdayPresets
OBJECT-TYPE
Disconnect 3 load shed Tuesday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.28DisplayStringread-onlymandatory
disconnect3LoadShedWednesdayPresets
OBJECT-TYPE
Disconnect 3 load shed Wednesday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.29DisplayStringread-onlymandatory
disconnect3LoadShedThursdayPresets
OBJECT-TYPE
Disconnect 3 load shed Thursday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.30DisplayStringread-onlymandatory
disconnect3LoadShedFridayPresets
OBJECT-TYPE
Disconnect 3 load shed Friday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.31DisplayStringread-onlymandatory
disconnect3LoadShedSaturdayPresets
OBJECT-TYPE
Disconnect 3 load shed Saturday time settings. Return value is XX:Xx off, XX:XX on.
1.3.6.1.4.1.18642.1.2.3.32DisplayStringread-onlymandatory
reconnect3VoltagePresets
OBJECT-TYPE
Reconnect voltage 3 factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.33DisplayStringread-onlymandatory
overloadCurrentPresets
OBJECT-TYPE
Overload current factory setting range. Return value is XXXX amps min, XXXX amps max.
1.3.6.1.4.1.18642.1.2.3.34DisplayStringread-onlymandatory
maximumCurrentPreset
OBJECT-TYPE
Maximum current factory setting. Return value is XXXX amps.
1.3.6.1.4.1.18642.1.2.3.35DisplayStringread-onlymandatory
batteryFloatCurrentPresets
OBJECT-TYPE
Battery float current factory settings. Return value is XXX amps min, XXX amps max.
1.3.6.1.4.1.18642.1.2.3.36DisplayStringread-onlymandatory
equalizeTimePresets
OBJECT-TYPE
Equalize time factory setting range. Return value is 00.0 hours min, XX.X hours max.
1.3.6.1.4.1.18642.1.2.3.37DisplayStringread-onlymandatory
equalizeVoltagePresets
OBJECT-TYPE
Equalize voltage factory setting range. Return value is XX.X volts min, XX.X volts max.
1.3.6.1.4.1.18642.1.2.3.38DisplayStringread-onlymandatory
batteryResistancePresets
OBJECT-TYPE
Battery resistance percent change factory setting range. Return value is XXX % min, XXX % max.
1.3.6.1.4.1.18642.1.2.3.39DisplayStringread-onlymandatory
batteryTestIntervalPresets
OBJECT-TYPE
Battery resistance test interval factory setting range. Return value is XX weeks min, XX weeks max.
1.3.6.1.4.1.18642.1.2.3.40DisplayStringread-onlymandatory
alarmStatus
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.2.4
highVoltageAlarmStatus
OBJECT-TYPE
High voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.1INTEGER {inactive(1), active(2)}read-onlymandatory
lowVoltageAlarmStatus
OBJECT-TYPE
Low voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.2INTEGER {inactive(1), active(2)}read-onlymandatory
overloadAlarmStatus
OBJECT-TYPE
Overload alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.3INTEGER {inactive(1), active(2)}read-onlymandatory
breakerAlarmStatus
OBJECT-TYPE
Breaker alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.4INTEGER {inactive(1), active(2)}read-onlymandatory
acFailureAlarmStatus
OBJECT-TYPE
AC failure alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.5INTEGER {inactive(1), active(2)}read-onlymandatory
fanFailureAlarmStatus
OBJECT-TYPE
Fan failure alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.6INTEGER {inactive(1), active(2)}read-onlymandatory
rectifierFailureAlarmStatus
OBJECT-TYPE
Rectifier failure alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.7INTEGER {inactive(1), active(2)}read-onlymandatory
majorAlarmStatus
OBJECT-TYPE
Major alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.8INTEGER {inactive(1), active(2)}read-onlymandatory
lowVoltageDisconnect1TemperatureAlarmStatus
OBJECT-TYPE
Low voltage disconnect 1 high temperature alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.9INTEGER {inactive(1), active(2)}read-onlymandatory
lowVoltageDisconnect2TemperatureAlarmStatus
OBJECT-TYPE
Low voltage disconnect 2 high temperature alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.10INTEGER {inactive(1), active(2)}read-onlymandatory
lowVoltageDisconnect3TemperatureAlarmStatus
OBJECT-TYPE
Low voltage disconnect 3 high temperature alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.11INTEGER {inactive(1), active(2)}read-onlymandatory
lowVoltageDisconnect1VoltageAlarmStatus
OBJECT-TYPE
Low voltage disconnect 1 low voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.12INTEGER {inactive(1), active(2)}read-onlymandatory
lowVoltageDisconnect2VoltageAlarmStatus
OBJECT-TYPE
Low voltage disconnect 2 low voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.13INTEGER {inactive(1), active(2)}read-onlymandatory
lowVoltageDisconnect3VoltageAlarmStatus
OBJECT-TYPE
Low voltage disconnect 3 low voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.14INTEGER {inactive(1), active(2)}read-onlymandatory
batteryResistanceAlarmStatus
OBJECT-TYPE
Battery resistance alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.15INTEGER {inactive(1), active(2)}read-onlymandatory
batteryCurrentAlarmStatus
OBJECT-TYPE
Battery resistance alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.16INTEGER {inactive(1), active(2)}read-onlymandatory
batteryTestAbortCondition1AlarmStatus
OBJECT-TYPE
Battery test abort condition 1 alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.17INTEGER {inactive(1), active(2)}read-onlymandatory
batteryTestAbortCondition2AlarmStatus
OBJECT-TYPE
Battery test abort condition 2 alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.18INTEGER {inactive(1), active(2)}read-onlymandatory
batteryTestAbortCondition3AlarmStatus
OBJECT-TYPE
Battery test abort condition 3 alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.19INTEGER {inactive(1), active(2)}read-onlymandatory
batteryDisconnectAlarmStatus
OBJECT-TYPE
Battery disconnect alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.20INTEGER {inactive(1), active(2)}read-onlymandatory
fuseAlarmStatus
OBJECT-TYPE
Fuse alarm status. Return value 1 = alarm inactive, 2 = alarm active.
1.3.6.1.4.1.18642.1.2.4.21INTEGER {inactive(1), active(2)}read-onlymandatory
digitalSensorAlarms
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.2.5
systemAlarms
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.2.6
digitalSensorAlarmClears
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.2.7
systemAlarmClears
OBJECT-IDENTITY
1.3.6.1.4.1.18642.1.2.8

Notifications

NameOIDStatus
breakerTrap
NOTIFICATION-TYPE
Breaker has tripped.
1.3.6.1.4.1.18642.0.0
fuseTrap
NOTIFICATION-TYPE
Fuse has opened.
1.3.6.1.4.1.18642.0.1
batteryDisconnectTrap
NOTIFICATION-TYPE
Battery disconnect has operated.
1.3.6.1.4.1.18642.0.2
programmableTrap
NOTIFICATION-TYPE
Programmable alarm has occurred.
1.3.6.1.4.1.18642.0.3
highVoltageTrap
NOTIFICATION-TYPE
Float voltage has exceeded preset value. Return value: High voltage alarm XX.X volts.
1.3.6.1.4.1.18642.0.4
lowVoltageTrap
NOTIFICATION-TYPE
Float voltage is below preset value. Return value: Low voltage alarm XX.X volts.
1.3.6.1.4.1.18642.0.5
loadOverCurrentTrap
NOTIFICATION-TYPE
Load current has exceeded preset value. Return value: Load over current alarm XXXX amps.
1.3.6.1.4.1.18642.0.6
batteryFloatCurrentTrap
NOTIFICATION-TYPE
Battery float current has exceeded preset value. Return value: Battery float current alarm XXXX amps.
1.3.6.1.4.1.18642.0.7
loadDisconnect1VoltageTrap
NOTIFICATION-TYPE
Load disconnect 1 voltage has dropped below preset value. Return value: Load disconnect 1 voltage XX.X volts.
1.3.6.1.4.1.18642.0.8
loadDisconnect2VoltageTrap
NOTIFICATION-TYPE
Load disconnect 2 voltage has dropped below preset value. Return value: Load disconnect 2 voltage XX.X volts.
1.3.6.1.4.1.18642.0.9
loadDisconnect3VoltageTrap
NOTIFICATION-TYPE
Load disconnect 3 voltage has dropped below preset value. Return value: Load disconnect 3 voltage XX.X volts.
1.3.6.1.4.1.18642.0.10
loadDisconnect1TemperatureTrap
NOTIFICATION-TYPE
Load disconnect 1 temperature has exceeded preset value. Return value: Load disconnect 1 temperature alarm XX °C.
1.3.6.1.4.1.18642.0.11
loadDisconnect2TemperatureTrap
NOTIFICATION-TYPE
Load disconnect 2 temperature has exceeded preset value. Return value: Load disconnect 2 temperature alarm XX °C.
1.3.6.1.4.1.18642.0.12
loadDisconnect3TemperatureTrap
NOTIFICATION-TYPE
Load disconnect 3 temperature has exceeded preset value. Return value: Load disconnect 3 temperature alarm XX °C.
1.3.6.1.4.1.18642.0.13
rectifierFailureTrap
NOTIFICATION-TYPE
Rectifier failure. Return value: Rectifier failure.
1.3.6.1.4.1.18642.0.14
fanFailureTrap
NOTIFICATION-TYPE
Rectifier fan has failed. Return value: Fan failure.
1.3.6.1.4.1.18642.0.15
acFailureTrap
NOTIFICATION-TYPE
Rectifier has lost AC input power. Return value: AC failure.
1.3.6.1.4.1.18642.0.16
majorFailureTrap
NOTIFICATION-TYPE
Multiple failures of AC, rectififers, fans or a programmed alarm. Return value: Multiple AC, fan, rectifier or optional alarm failures has occurred.
1.3.6.1.4.1.18642.0.17
batteryResistanceTrap
NOTIFICATION-TYPE
Battery resistance has increased by a programmed percentage. Return value: Battery resistance alarm X.XXXX ohms, XXX %.
1.3.6.1.4.1.18642.0.18
batteryTestAbort1Trap
NOTIFICATION-TYPE
Battery failure abort 1 has occured during battery resistance test. Return value: Battery test failure: Abort 1.
1.3.6.1.4.1.18642.0.19
batteryTestAbort2Trap
NOTIFICATION-TYPE
Battery failure abort 2 has occured during battery resistance test. Return value: Battery test failure: Abort 2.
1.3.6.1.4.1.18642.0.20
batteryTestAbort3Trap
NOTIFICATION-TYPE
Battery failure abort 3 has occured during battery resistance test. Return value: Battery test failure: Abort 3.
1.3.6.1.4.1.18642.0.21
breakerTrapClear
NOTIFICATION-TYPE
Breaker alarm has been cleared.
1.3.6.1.4.1.18642.0.100
fuseTrapClear
NOTIFICATION-TYPE
Fuse alarm has been cleared.
1.3.6.1.4.1.18642.0.101
batteryDisconnectTrapClear
NOTIFICATION-TYPE
Battery disconnect alarm has been cleared.
1.3.6.1.4.1.18642.0.102
programmableTrapClear
NOTIFICATION-TYPE
Programmable alarm has been cleared.
1.3.6.1.4.1.18642.0.103
highVoltageTrapClear
NOTIFICATION-TYPE
High voltage alarm has been cleared.
1.3.6.1.4.1.18642.0.104
lowVoltageTrapClear
NOTIFICATION-TYPE
Low voltage alarm has been cleared.
1.3.6.1.4.1.18642.0.105
loadOverCurrentTrapClear
NOTIFICATION-TYPE
Load over current alarm has been cleared.
1.3.6.1.4.1.18642.0.106
batteryFloatCurrentTrapClear
NOTIFICATION-TYPE
Battery float current alarm has been cleared.
1.3.6.1.4.1.18642.0.107
loadDisconnect1VoltageTrapClear
NOTIFICATION-TYPE
Load disconnect 1 voltage alarm has been cleared.
1.3.6.1.4.1.18642.0.108
loadDisconnect2VoltageTrapClear
NOTIFICATION-TYPE
Load disconnect 2 voltage alarm has been cleared.
1.3.6.1.4.1.18642.0.109
loadDisconnect3VoltageTrapClear
NOTIFICATION-TYPE
Load disconnect 3 voltage alarm has been cleared.
1.3.6.1.4.1.18642.0.110
loadDisconnect1TemperatureTrapClear
NOTIFICATION-TYPE
Load disconnect 1 temperature alarm has been cleared.
1.3.6.1.4.1.18642.0.111
loadDisconnect2TemperatureTrapClear
NOTIFICATION-TYPE
Load disconnect 2 temperature alarm has been cleared.
1.3.6.1.4.1.18642.0.112
loadDisconnect3TemperatureTrapClear
NOTIFICATION-TYPE
Load disconnect 3 temperature alarm has been cleared.
1.3.6.1.4.1.18642.0.113
rectifierFailureTrapClear
NOTIFICATION-TYPE
Rectififer failure alarm has been cleared.
1.3.6.1.4.1.18642.0.114
fanFailureTrapClear
NOTIFICATION-TYPE
Fan failure alarm has been cleared.
1.3.6.1.4.1.18642.0.115
acFailureTrapClear
NOTIFICATION-TYPE
AC failure alarm been cleared.
1.3.6.1.4.1.18642.0.116
majorFailureTrapClear
NOTIFICATION-TYPE
Major failure alarm has been cleared.
1.3.6.1.4.1.18642.0.117
batteryResistanceTrapClear
NOTIFICATION-TYPE
Battery resistance alarm has been cleared.
1.3.6.1.4.1.18642.0.118
batteryTestAbort1TrapClear
NOTIFICATION-TYPE
Battery test abort 1 alarm has been cleared.
1.3.6.1.4.1.18642.0.119
batteryTestAbort2TrapClear
NOTIFICATION-TYPE
Battery test abort 2 alarm has been cleared.
1.3.6.1.4.1.18642.0.120
batteryTestAbort3TrapClear
NOTIFICATION-TYPE
Battery test abort 3 alarm has been cleared.
1.3.6.1.4.1.18642.0.121